York Yocc Yohc 12 60 User Manual

EN/FR  
E N G L I S H  
035M00003-000  
INSTALLATION &  
OWNER’S MANUAL  
MINISPLIT FLOOR/CEILING  
AIR CONDITIONER  
MODELS : YOCC-YOHC 12-60  
REQUIRED TOOLS  
PART LIST  
1. Screw Driver  
2. Hexagonal Wrench  
3. Torque Wrench  
4. Spanner  
9. Manifold Guage  
10. Gas Leak Detector  
11. Vacuum Pump  
12. Pipe Clamp  
INDOOR UNIT  
❥✱YOCC-YOHC  
5. Reamer  
13. Pipe Cutter  
14. Flare Tool Set  
15. Electrical Circuit Tester  
6. Hole Core Drill  
7. Tape Measure  
8. Thermometer  
EXTENDED PARTS  
1. Refrigerant Pipe : See Technical Specication  
2. Pipe Insulation Material (Polyethylene foam 9 mm thick)  
3. Vinyl Tape  
4. Putty  
INSTALLATION ACCESSORIES  
Description  
Qty  
USE  
SAFETY PRECAUTIONS  
Hook  
For wall mounting installation  
• Please read this installation manual carefully before starting installation  
of the unit.  
2
• This air conditioning system contains refrigerant under pressure, rotating  
parts and electrical connection which may be dangerous and can cause  
injury. Installation and maintenance of this air conditioning system should  
only be carried out by trained and qualied personnel.  
• After unpacking, please check the unit carefully for possible damage.  
• Before undertaking any work on the unit, make sure that the power supply  
has been disconnected.  
Hanging arm  
For ceiling installation  
2
2
Tapping Screw (ST2.9x10-C-H)  
Remote Controller  
CAUTIONS FOR INSTALLATION  
• Do not store or unpack the unit  
in a wet area or expose to rain  
or water.  
• Do not conduct installation in wet  
area or in the rain.  
1
Frame  
Alkalina dry batteries (AM4)  
1
2
It may cause the unit to short circuit and may  
result electric shocks or re.  
It is a high risk to cause the electrical shocks.  
• Do not install in a place where  
ammable gas may leak.  
• This system is designed for  
domestic or residential use only.  
Install & Owner’s manual and User’s  
guide  
Installation  
Owner's man  
&
User'  
s
Guide  
ual  
It may cause re.  
If used in certain environments, such as a  
manufacturing workplace, the equipment may  
not function efciently.  
YODC-YOJC 30-36  
990  
YODC-YOJC 48-60  
400 940  
CEILING INSTALLATION  
336.4  
181.4  
624  
Hanging arm  
DC Inverter R-410A  
650  
Chart 7  
MODEL  
A
B
C
D
E
H
REMARK  
1. Remove the side board and the grille. (Refer to Chart 8)  
(For models 48000 and 60000 Btu/h, do not remove the grille.)  
18 840 550 335 360 310 677  
24 894 590 333 355 302 860  
36 990 624 366 396 340 960  
48 940 600 376 400 340 1245  
R-410A  
A
B
Side board  
Grille  
INSTALLATION IN THE FOLLOWING PLACES  
MAY RESULT IN TROUBLE  
Chart 8  
2. Locate the hanging arm on the hanging screw bolt. (Refer to Chart 9)  
Prepare the mounting bolts on the unit. (Refer to Chart 10)  
8•• 13mm  
Screw nut  
Washer  
Hanging  
screw bolt  
Mounting bolt (max. 40 mm)  
Hanging arm  
Chart 9  
Chart 10  
Installation of the indoor unit in direct sun light.  
Installation in the unit in wrong direction.  
3. Hang the unit on the hanging arm by sliding backward. Securely tighten the  
mounting bolts on both sides. (Refer to Chart 9)  
Hanging  
screw bolt  
Hanging arm  
Mounting bolt  
D. Connecting point of refrigerant pipe  
(D. gas side)  
Installation of outdoor units too close or,  
blowing discharged air into each other.  
Installation of the indoor unit in a place where  
there is an obstacle near the air inlet or outlet.  
E. Connecting point of refrigerant pipe  
(E. Liquid side)  
Drain point  
Chart 11  
Installation of the outdoor unit in a place  
exposed regularly to a strong wind.  
Installation of the indoor unit at too high > 30 cm  
a position.  
ATTENTION: The gures above are based on model with 18000 Btu/h as rated  
capacity, which may differ from the unit you purchased.  
The dimension of the unit  
Capacity  
(Btu/h)  
INDOOR UNIT INSTALLATION  
Installing Ø10 hanging screw bolts. (4 bolts)  
A
B
C
D
E
F
G
H
Please refer to the following gure for the distance measurement between the  
screw bolts.  
Please install with Ø10 hanging screw bolts.  
12000-24000 Btu/h  
36000 Btu/h  
990 660 206 505 506 907 200 203  
1280 660 206 795 506 1195 200 203  
1670 680 244 1070 450 1542 200 240  
The handling to the ceiling varies from the constructions, consult the construction  
personnels for the specic procedures.  
48000-60000 Btu/h  
• Note: The dimension of 12000 Btu/h and 24000 Btu/h are the same  
The dimension of 48000 Btu/h and 60000 Btu/h are the same  
1. The size of the ceiling to be handled ... ... do keep the ceiling at. Consolidate  
the roof beam for possible vibration.  
2. Cut off the roof beam.  
Outdoor unit  
3. Strengthen the place cut off, and consolidate the roof beam.  
Carry out the pipe and line operation in the ceiling after nishing the installation  
of the main body. While choosing where to start the operation, determine the  
direction of the pipes to be drawn out. Especially in case there is a ceiling, position  
the refrigerant pipes, drain pipes, indoor & outdoor lines to the connection places  
before hanging up the machine.  
YODC-YOJC 12  
285  
YODC-YOJC 18  
845  
YODC-YOJC 24  
895  
750  
300  
313  
301.5  
The installation of hanging screw bolts.  
163  
590  
141.5  
560.1  
62  
530  
110  
❥✱The Specication of Power  
Wooden construction  
New concrete bricks  
12000~18000 Btu/h 24000-36000 Btu/h 36000-60000 Btu/h  
(Cooling&Heating) (Cooling&Heating) (Cooling&Heating)  
TYPE  
Put the square timber traversely over  
the roof beam, then install the hanging  
screw bolts. (Refer to Chart 1)  
Inlaying or embedding the screw bolts.  
(Refer to Chart 2)  
PHASE  
POWER  
1-PHASE  
220-240V~, 50Hz  
20/16  
1-PHASE  
220-240V~, 50Hz  
40/25  
3-PHASE  
380V 3N~, 50Hz  
40/20  
FREQUENCY AND VOLT  
CIRCUIT BREAKER/FUSE (A)  
INDOOR UNIT POWER WIRING (mm2)  
GROUND WIRING  
Timber over the beam  
3x2.5  
5x2.5  
2.0  
2.5  
2.5  
(Blade shape insertion)  
Chart 2  
(Slide insertion)  
OUTDOOR UNIT  
POWER WIRING  
STRONG ELECTRIC  
SIGNAL  
INDOOR/OUTDOOR  
CONNECTING  
WIRING  
3x2.5  
3x2.5  
5x2.5  
Roof beam  
Ceiling  
5x2.0  
(3x2.0)  
3x2.0  
(2x2.0)  
3x2.0  
(2x2.0)  
(mm2)  
WEAK ELECTRIC  
SIGNAL  
1-core sheild wire  
1x0.5mm2  
2-core sheild wire  
2x0.5mm2  
Hanging screw bolts  
Chart 1  
12000~18000 Btu/h 24000-36000 Btu/h 36000-60000 Btu/h  
TYPE  
(Cooling Only)  
(Cooling Only)  
(Cooling Only)  
PHASE  
FREQUENCY AND VOLT  
1-PHASE  
220-240V~, 50Hz  
40/25  
1-PHASE  
220-240V~, 50Hz  
40/20  
3-PHASE  
380V 3N~, 50Hz  
40/25  
POWER  
For Original concrete bricks  
Steel roof beam structre  
CIRCUIT BREAKER/FUSE (A)  
INDOOR UNIT POWER WIRING (mm2)  
GROUND WIRING  
3x2.5  
3x2.5  
5x2.5  
Use embedding screw bolt. (Refer to  
Chart 3)  
Install and use directly the supporting  
angle steel. (Refer to chart 4)  
Hanging screw bolt  
2.0  
2.0  
2.0  
OUTDOOR UNIT  
POWER WIRING  
STRONG ELECTRIC  
SIGNAL  
INDOOR/OUTDOOR  
CONNECTING  
WIRING  
3x2.0  
1x2.0  
5x2.0  
1x2.0  
Steel bar  
3x2.0  
Embedding screw bolt  
(mm2)  
WEAK ELECTRIC  
SIGNAL  
(Pipe hanging and embedding  
screw bolt)  
Supporting  
angle steel  
Hanging bolts  
Chart 4  
Chart 18  
Chart 3  
❥✱Wiring Chart  
Installing wiring chart, refer to link circuit chart for details.  
CONNECT THE DRAIN PIPE  
Power supply  
1. Install indoor unit drain pipe  
The outlet has PTI screw thread, Please use sealing materials and pipe sheath  
(tting) when connecting PVC pipes.  
Switch/Fuse  
(Available locally)  
Power wiring (indoor)  
Cautions  
Power linking wiring (Outdoor)  
The drain pipe of indoor unit must be heat insulated, or it will condense dew,  
as well as the connections of the indoor unit.  
Hard PVC binder must be used for pipe connection, and make sure there is no  
leakage.  
With the connection part to the indoor unit, please be noted not to impose  
pressure on the side of indoor unit pipes.  
When the declivity of the drain pipe downwards is over 1/100, there should not  
be any winding.  
Indoor  
Unit  
Outdoor  
Unit  
Ground wiring  
Strong elec-signal link wiring  
Weak elec-signal link wiring  
Ground wiring  
Ground the air conditioner properly in case to affect its anti-interference function  
Chart 19  
The total length of the drain pipe when pulled out traversely shall not exceed  
20m, when the pipe is over long, a prop stand must be installed to prevent  
winding.  
CAUTION: When wiring, please choose the corresponding chart, or it may  
cause damage.  
Refer to the gures on the right for the installation of the pipes.  
Put as deep as possible  
(about 10cm)  
INDOOR UNIT  
1.5m~2m  
Bend  
L
N
1
2(N)  
XT1  
XT2  
S shape  
Insulating  
Y&G  
Downward  
Downward declivity  
material  
Y&G  
POWER:  
220-240V~50Hz  
declivity lower  
than 1/100  
VP30  
lower than 1/100  
3-core cable 3x2.5mm2  
2. Drainage test  
Check whether the drainpipe is unhindered  
New built house should have this test done before paving the ceiling.  
12000 Btu/h (1 PHASE)  
3. Drain Elbow Installation  
Air Conditioner Link-circuit  
(For R-410A, Cooling & Heating)  
18000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit  
(For R-410A, R-407C and R-22,  
Cooling & Heating)  
5-core cable 5x2.0mm2  
Fit the seal into the drain elbow, then insert the drain elbow into the base pan  
hole of outdoor unit, rotate 90° to securely assemble them. Connect the drain  
elbow with an extension  
1-core sheild wire 1x0.5mm2  
drain hose (Locally purchased),  
in case of the condensate  
draining off the outdoor unit  
during the heating mode.  
(Refer to Chart 17)  
The base pan  
hole of outdoor  
Seal  
Chart 20  
Drain elbow  
The base pan hole  
of outdoor unit  
Seal  
Drain elbow  
Chart 17  
INDOOR UNIT  
L
N
1
2
3
XT1  
XT2  
T3  
E
WIRING  
Y&G  
POWER:  
220-240V~50Hz  
❥✱Attaching wiring  
1. The air conditioner should use separate power supply with rated voltage  
2. The external power supply to the air conditioner should have ground wiring,  
which is linked to the ground wiring of the indoor and outdoor unit.  
3. The wiring work should be done by qualied persons according to circuit  
drawing.  
3-core cable 3x2.5mm2  
3-core cable 3x2.0mm2  
3-core cable 3x2.5mm2  
24000Btu/h (1 PHASE)  
1-core sheild wire 1x0.5mm2  
Air Conditioner Link-circuit  
(For R-410A, Cooling & Heating)  
24000-36000Btu/h (1 PHASE)  
Air Conditioner Link-circuit  
(For R-407C, Cooling & Heating)  
4. A leakage protector should be installed according to the National Standard  
concerning electrical appliance.  
5. Be sure to locate the power wiring and the signal wring well to avoid cross-  
disturbance and their contact with connecting pipe or stop valve body.  
6. The wiring attached to this air conditioner is 10m long. Be sure to prolong it  
with wiring of the same type and proper length if necessary. Generally, do not  
twist two wiring together unless the joint is soldered well and covered with  
insulator tape.  
Chart 21  
7. Do not turn on the power until you have checked carefully after wiring.  
INDOOR UNIT  
2
3
Y&G  
INDOOR UNIT  
A
B
C
N
1
XT2  
XT1  
INDOOR UNIT  
XT1  
L
N
1
2(N)  
L
N
1
2
3
POWER:  
220-240V~50Hz  
POWER:  
380V 3N~50Hz  
POWER:  
220-240V~50Hz  
3-core cable 3x2.5mm2  
1-core cable 1x2.0mm2  
3-core cable 3x2.5mm2  
5-core cable 5x2.5mm2  
5-core cable 5x2.5mm2  
3-core cable 3x1.5mm2  
3-core cable 3x2.0mm2  
3-core cable 3x2.5mm2  
Y&G  
12000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-410A and R-407C, Cooling  
Only)  
18000 Btu/h (1 PHASE)  
36000~60000 Btu/h (3 PHASE)  
Air Conditioner Link-circuit (For R-410A, R-407C and R-22,  
Cooling & Heating)  
24000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-410A, Cooling Only)  
Air Conditioner Link-circuit (For R-410A, Cooling Only)  
Chart 22  
Chart 23  
Chart 24  
INDOOR UNIT  
INDOOR UNIT  
INDOOR UNIT  
L
N
1
2(N)  
L
N
1
2
3
A
B
C
N
1
XT1  
XT1  
T3  
XT2  
E
POWER:  
220-240V~50Hz  
POWER:  
380V 3N~50Hz  
3-core cable 3x2.5mm2  
Y&G  
POWER:  
220-240V~50Hz  
3-core cable 5x2.5mm2  
3-core cable 3x2.5mm2  
3-core cable 3x2.5mm2  
5-core cable 5x2.5mm2  
1-core sheild wire 1x0.5mm2  
3-core cable 3x2.0mm2  
1-core cable 1x2.0mm2  
36000~60000 Btu/h (3 PHASE)  
Air Conditioner Link-circuit (For R-410A, R-407C and R-22,  
Cooling Only)  
18000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-22, Cooling Only)  
24000~36000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-22, Cooling only)  
Chart 25  
Chart 26  
Chart 27  
INDOOR UNIT  
INDOOR UNIT  
INDOOR UNIT  
XT1  
L
N
1
2
3
L
N
1
2
3
L
N
1
2
3
XT1  
XT2  
T3  
E
POWER:  
220-240V~50Hz  
XT1  
T3  
XT2  
E
Y&G  
1-core cable 1x2.5mm2  
3-core cable 3x2.5mm2  
Y&G  
POWER:  
220-240V~50Hz  
POWER:  
220-240V~50Hz  
3-core cable 3x2.5mm2  
3-core cable 3x2.5mm2  
3-core cable 3x2.0mm2  
3-core cable 3x2.0mm2  
3-core cable 3x2.5mm2  
3-core cable 3x2.5mm2  
1-core sheild wire 1x0.5mm2  
1-core sheild wire 1x0.5mm2  
3-core cable 3x2.5mm2  
24000~36000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-22, Cooling & Heating)  
24000~36000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-407C, Cooling Only)  
30000~36000 Btu/h (1 PHASE)  
Air Conditioner Link-circuit (For R-407C, Cooling & Heating)  
Chart 28  
Chart 29  
Chart 30  
DC Inverter R-410A  
INDOOR UNIT  
INDOOR UNIT  
INDOOR UNIT  
T3 GND +5V  
T3 GND +5V  
2
3(4)5  
2
3(4)5  
A
B
C
N
1
A
B
C
N
1
X
Y
(E)  
P
Q
L
N
XT1  
XT1  
Y&G  
XT2  
Y&G  
XT2  
Y/G  
POWER:  
380V~50Hz  
POWER:  
380V~50Hz  
Power supply  
1-Phase  
220-240V~ (3-core cable 3x1.0mm2  
)
5-core cable 3x2.5mm2  
4-core cable 3x2.0mm2  
5-core cable 3x2.5mm2  
4-core cable 3x2.0mm2  
3-core sheild cable  
5-core cable 3x2.5mm2  
5-core cable 3x2.5mm2  
2-core sheild wire 1x0.5mm2  
2-core sheild wire 1x0.5mm2  
Power supply  
1-Phase  
220-240V~ (3-core cable 3x2.5mm2  
)
24000~30000 Btu/h (3 PHASE)  
Air Conditioner Link-circuit (For R-407C, Cooling only)  
24000~30000 Btu/h (3 PHASE)  
Air Conditioner Link-circuit (For R-407C, Cooling & Heating)  
Chart 31  
Chart 32  
For 18000-24000 Btu/h  
POWER  
TIMER  
COMP  
❥✱Refrigerant Piping  
Connections (FLARE  
Connections)  
E
M
E
R
G
E
N
C
Y
S
W
I
T
C
H
DC Inverter R-410A  
INDOOR UNIT  
P
Q
(E)  
L1 L2 L3  
N
Y/G  
To avoid alteration of unit capacities,  
check that piping lengths and changes in  
elevation are kept to a strict minimum.  
L
D
3-core sheild cable  
Before connection the refrigerant lines,  
follow the procedures below (if precharged  
connection lines are not supplied):  
Power supply  
3-Phase  
380-415V~ (5-core cable 5x2.5mm2  
)
– Select copper pipe diameters according  
to the size of unit to be installed.  
– Install the refrigeration lines, checking  
that no foreign bodies get inside the  
piping.  
Power supply  
1-Phase  
220-240V~ (3-core cable 3x2.5mm2  
)
L
H
POWER  
TIMER  
COMP  
E
M
E
R
G
E
N
C
Y
S
W
I
T
C
H
– Install the are connectors andare the  
ends of the pipes.  
For 36000-60000 Btu/h  
❥✱Maximum Piping Lengths  
Low Pressure  
Unit size  
D (m)  
L (m)  
09  
12  
15  
10  
12  
15  
18  
12  
18  
15  
18  
12  
25  
22  
25  
20  
35  
22  
25  
20  
45  
26  
30  
24  
55  
26  
30  
24  
65  
26  
30  
24  
High Pressure  
Manifold  
Outdoor  
Unit  
Indoor  
Unit  
Gas Line  
H (m)  
Liquid Line  
Note : Where the difference in elevation between the indoor unit and the outdoor unit is greater than  
5 meters, install an oil trap every 5 meters.  
The suction line must have a 2% gradient up to the compressor on horizontal  
sections.  
Where piping lengths are unusually long and include a large number of oil  
traps, it may be necessary to adjust to compressor charge.  
R-22/R-407C  
Gas Valve  
Liquid Valve  
Pressure Tap  
Refrigerant charge to be added per extra metre of piping length when  
more than 7.5 meters.  
This unit is shipped complete with a charge of R-22/R-407C refrigerant that will  
be sufcient for an interconnecting piping length of 7.5 meters.  
Unit size  
g/m  
07  
09  
12  
18  
25  
35  
45  
55  
65  
15  
15  
15  
40  
40  
40  
60  
60  
60  
TEST OPERATION  
CHECK THIS ITEM BEFORE START OPERATION  
Indoor  
• Check the unit is rmly xed.  
Outdoor  
• Check the connecting pipes are tighten securely.  
• Check the pipe insulation.  
• Check the drainage.  
Check the are nut connections, valve stem cap connections and service cap  
connections for gas leak with a leak detector or soap water.  
• Check the connection of the grounding wire.  
TROUBLESHOOTING GUIDE  
Problem  
Probable cause  
Remedy  
A. The air conditioner does not  
run.  
1. Power Failure.  
1. Wait for Power resume.  
2. Replace the fuse or reset the breaker.  
3. Find the cause and x it.  
4. Replace the faulty component.  
5. Retighten the connection.  
6. Check Thermostat setting.  
7. Find the cause then replace Capacitor.  
8. Check and retighten.  
2. Fuse blown or circuit breaker open.  
3. Voltage is too low.  
4. Faulty contactor or relay.  
5. Electrical connections loose.  
6. Thermostat adjustment too low (in heating mode) or too high  
(in cooling mode).  
7. Faulty Capacitor.  
8. Incorrect wiring, terminal loose.  
9. Pressure switch tripped.  
9. Find the cause before reset.  
B. The outdoor fan runs but the  
compressor will not start.  
1. Motor winding cut or grounded.  
2. Faulty Capacitor.  
1. Check the wiring and the compressor winding resistance.  
2. Find the cause then replace Capacitor.  
C. There is insufcient heating or 1. There is a gas leak.  
cooling.  
1. Remove charge, repair, evacuate and recharge.  
2. Insulate them separately.  
3. Wait while unit has enough time to cool the room.  
2. Liquid and gas line insulated together.  
3. The room was probably very hot (cool) when you started the system.  
D. The compressor run  
continuously.  
1. Thermostat adjustment too low (in heating mode) or too high  
(in cooling mode).  
2. Faulty fan.  
3. Refrigerant charge too low, leak.  
4. Air or incondensables in refrigerant circuit.  
1. Check Thermostat setting.  
2. Check condenser air circulation.  
3. Find leak, repair and recharge.  
4. Remove charge, evacuate and recharge.  
E. The compressor starts but  
shuts down quickly.  
1. Too much or too little refrigerant.  
2. Faulty compressor.  
3. Air or incondensables in refrigerant circuit.  
4. Changeover valve damaged or blocked open (heat pump unit).  
1. Remove charge, evacuate and recharge.  
2. Determine the cause and replace compressor.  
3. Remove charge, evacuate and recharge.  
4. Replace it.  
F. Clicking sound is heard from  
the air conditioner.  
In heating or cooling operation any plastic parts may expand or shrink due to In heating or cooling operation any plastic parts may expand  
a sudden temperature change in this event, a clicking sound may occur.  
or shrink due to a sudden temperature change in this event,  
a clicking sound may occur.  
NORMAL FUNCTION OF THE AIR CONDITIONER  
PROTECTION FUNCTION  
Auto Restart Function  
The following symptoms do not indicate air conditioner malfunction.  
The unit will automatically restart after loss of the electrical power supply. When power is  
restored; the unit operation will restart according to all parameters set before the loss of  
power.  
1. The system does not operate  
The system does not restart immediately  
after the ON/OFF button is pressed.  
ANTI-ICE and ANTI-OVERHEAT  
If the OPERATION lamp lights, the system is  
in normal condition.  
The safety device operates to prevent overload of the system.  
After 3 minutes, the system will turn on again automatically.  
This feature is used to prevent the indoor unit from freezing during cool or dry operation  
and overheating in heat mode. During execution of anti-ice operation and anti-overheating,  
the compressor will stop operating and the fan will continue to run until the coil temperature  
reaches predetermined set points, at which time the unit will resume normal operation.  
The system does not restart immediately when  
TEMPERATURE SETTING changed.  
Low Voltage  
The feature is used to protect against any damage to the unit caused by uctuation of voltage.  
If voltage is lower than the lower limit for approximately 10 seconds or longer, compressor  
operation will be temporarily stopped. Normal operation will resume when the voltage returns  
above the set limit for a minimum of 10 seconds. If the time elapsed is less than 3 minutes  
then the compressor start up will be delayed until 3 minutes has passed.  
If the OPERATION lamp lights, the system is in normal condition.  
If the timer light is ashing operation is being delayed by the safety  
device. It does not restart immediately because the compressor  
has been stopped and requested to start within the delay period.  
A safety device operates to prevent overload of the system.  
After 3 minutes, the system will turn on again automatically.  
Filter Care and Filter Alarm  
Replace Air Purifying lter if tted.  
The system does not start immediately after the power supply is turned on.  
Wait one minute until the microcomputer is prepared for operation.  
The lters should be cleaned regularly, i.e, once a month, or more frequently depending on  
conditions. The control is equipped with a lter alarm; After a certain numbers of hours of  
operation, ashing lights will indicate that it is time to clean the lter. The alarm is reset by  
pressing the lter button or the transmitter.  
1.1 White mist comes out of a unit  
When humidity is high during cooling operation.  
(In dusty locations or after construction work)  
If the inside of an indoor unit is contaminated,  
the temperature distribution inside a room may  
become uneven. It is necessary to clean the inside  
of the indoor unit. The unit should be cleaned by  
a qualied service person familiar with the unit.  
MAINTENANCE  
The units are designed to operate for long periods of time with a minimum of maintenance.  
However, the following operation must be performed regularly.  
Maintenance Operations  
Recommended Frequency  
When the system is changed over to HEATING OPERATION  
or after DEFROST OPERATION. Moisture generated on  
the coil by the DEFROST becomes vapour and exists.  
Air lter  
Clean  
Every month or more often if necessary  
Every month or more often if necessary  
Each season before start up*  
Unit casing  
Clean  
Drain pan and evacuation piping  
Indoor/outdoor coils  
Compressor  
Clean and check for obstructions  
1.2 Noise of air conditioners  
Clean  
Each season before start up*  
A continuous ow “Shuh” sound is heard when the systems is in COOLING  
or DEFROST OPERATION. This is the sound of refrigerant  
gas owing through both indoor and outdoor units.  
No need  
* This operation must be carried out by qualied personnel only.  
A “Shuh” sound which is heard at the start or  
immediately after operation. It may also be heard  
BEFORE MAINTENANCE  
at the start or immediately after a DEFROST OPERATION.  
This is the noise of refrigerant caused by the start and stop of the ow.  
S
Turn off the main breaker or disconnect the main power supply.  
Notes  
A “Pishi-pishi” squeaking sound is heard when the system is in  
operation or just after operation. Expansion and contraction of plastic  
parts caused by temperature change makes this noise.  
Don’t spill water : There is a danger of electric shock.  
Don’t used petrol, paint thinner, benzene or polishing agents  
: They may deform or scratch the unit.  
1.3 Dust from the units  
Dust may blow out from the unit when starting after long off cycles.  
Dust absorbed by the unit blows out.  
CLEANING THE UNIT  
The units give off odours. The unit absorbs the smell of rooms,  
furniture, cigarettes, etc., and then emits them.  
Wipe the unit with a soft dry cloth only.  
If the unit is very dirty, wipe it with a cloth soaked  
in warm water (Not more than 40°C).  
Not more than  
40°C  
EMERGENCY OPERATION  
Units are equipped with a switch to run  
emergency operation mode. Pushing the  
emergency switch turns the unit on;  
CLEANING THE AIR FILTER  
pushing it again turns if off (toggle action).  
During emergency operation, the remote  
controller cannot be used and the power  
LED light will ash at intervals, while the  
other LED lights will indicate the operation  
of the Diagnostic Codes.  
EMERGENCY  
OPERATION  
1. Remove the air lter.  
Open front grille  
and pull llter  
3. Drying  
Drying the air lter by hair  
drying or direct sunlight.  
outward front grille.  
In Emergency Operation and cooling units  
the temperature will be set at 24°C and the fan on Auto.  
Heating units will switch to auto mode at a temperature set  
point of 24°C and the fan will run on auto mode.  
After a power failure the unit restarts automatically in the same  
mode as before the failure, when power is resumed.  
2. Cleaning  
4. Reinstall the air lter.  
If the llter is very dirty,  
clean it with water  
(approx 30°C).  
Approx 30 °C  
TECHNICAL SPECIFICATION  
Floor/Ceiling YOCC (YOEC-YODC) COOLING R-410A 50Hz Rev.291106  
Set  
YOCC12FSA(B)AAR  
YOEC12FS-A(B)AR  
YOCC18FSA(B)AAR  
YOEC18FS-A(B)AR  
YOCC24FSA(B)AAR  
YOEC24FS-A(B)AR  
YOCC30FSA(B)ACR  
YOEC30FS-A(B)CR  
YOCC30FSA(B)AAR  
YOEC30FS-A(B)AR  
YODC30FS-A(B)AR  
1,220-240V,50Hz  
YOCC36FSA(B)AAR  
YOEC36FS-A(B)AR  
YODC36FS-A(B)AR  
1,220-240V,50Hz  
YOCC36FSA(B)ACR  
YOEC36FS-A(B)CR  
YODC36FS-A(B)CR  
3,380V,50Hz  
YOCC48FSA(B)ACR  
YOEC48FS-A(B)CR  
YODC48FS-A(B)CR  
3,380V,50Hz  
48,000  
14  
YOCC60FSA(B)ACR  
YOEC60FS-A(B)CR  
YODC60FS-A(B)CR  
3,380V,50Hz  
60,000  
Model  
Indoor unit  
Outdoor Unit  
YODC12FS-A(B)AR  
1,220-240V,50Hz  
12,000  
YODC18FS-A(B)AR  
1,220-240V,50Hz  
YODC24FS-A(B)AR  
1,220-240V,50Hz  
24,000  
YODC30FS-A(B)CR  
3,380V,50Hz  
Power supply  
Ph-V-Hz  
Btu/h  
kW  
kcal/h  
W
A
L/h  
W
18,000  
5.4  
4,536  
1,900  
8.5  
1.8  
2,600  
13  
36.8  
30,000  
9.2  
7,560  
3,450  
6.4  
3
5,200  
8.8  
97  
30,000  
9.2  
7,560  
3,450  
16.4  
3
5,200  
25  
97  
36,000  
10.5  
9,072  
3,800  
19.2  
3.6  
5,200  
26.3  
97  
36,000  
10.5  
9,072  
3,800  
6.4  
3.8  
5,200  
8.8  
61  
SCROLL  
3,650  
6.58  
61  
Inner  
Capacity  
3.5  
3,024  
1,200  
5.3  
7.1  
6,048  
2,600  
12.1  
2.4  
3,300  
16.5  
61  
17  
15,120  
5,800  
9.8  
Cooling  
12,096  
4,900  
8.2  
Input  
Rated current  
Moisture Removal  
1.2  
4.8  
6
Max. input consumption  
Max. current  
Starting current  
1,400  
7.2  
26  
6,100  
10.3  
66  
SCROLL  
4,750  
8.22  
66  
Inner  
/
118/108/101  
2.5μF/450V  
820/695/620  
3
7,200  
12.2  
67  
SCROLL  
5,750  
9.77  
67  
Inner  
/
118/108/101  
2.5μF/450V  
820/695/620  
3
A
A
Type  
Input  
ROTARY  
1,145  
5.3  
26  
Inner  
35/370μF/V  
104/98  
1.5μF/450V  
1,190/1,000/890  
2
ROTARY  
1,870  
8.75  
36.8  
Inner  
50/370μF/V  
110/104/98  
2.5μF/450V  
1,280/1,190/1,000  
3
ROTARY  
2,430  
11.4  
61  
Inner  
50/400μF/V  
110/104/98  
2.5μF/450V  
1,280/1,190/1,000  
3
SCROLL  
3,650  
6.58  
61  
SCROLL  
3,650  
17.65  
97  
Inner  
60μF/440V  
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
SCROLL  
3,650  
17.65  
97  
Inner  
60μF/440V  
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
W
A
A
Rated current (RLA)  
Locked rotor Amp (LRA)  
Thermal protector  
Capacitor  
Input  
Capacitor  
Speed (Hi/Mid/Low)  
Number of rows  
Fin spacing  
Compressor  
Inner  
μF  
W
μF  
r/min  
/
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
/
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
Indoor fan motor  
Indoor coil  
mm  
1.7  
1.7  
1.7  
1.7  
1.7  
1.7  
1.7  
1.7  
1.7  
Fin type  
Tube outside dia.and type  
Coil length height width  
Hydrophilic aluminum  
Ø9.53 innergroove tube  
905 203 66  
1,400/1,200/1,000  
45/43/40  
mm  
mm  
m3/h  
dB(A)  
mm  
mm  
kg  
W
μF  
r/min  
804 254 44  
600/480/400  
43/41/38  
995 660 198  
1,075 744 278  
30/37  
56  
2.5μF/450V  
800  
804 254 66  
800/600/500  
43/41/38  
995 660 198  
1,075 744 278  
30/37  
130  
2.5μF/450V  
750  
804 254 66  
1,000/900/700  
45/43/40  
995 660 198  
1,075 744 278  
30/37  
130  
3μF/450V  
800  
905 203 66  
1,200/1,000/800  
45/43/40  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
905 203 66  
1,400/1,200/1,000  
45/43/40  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
905 203 66  
1,400/1,200/1,000  
45/43/40  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
1,150 254 66  
2,000/1,800/1,600  
47/45/42  
1,670 680 240  
1,764 760 329  
52/62  
138+156  
3.5 2μF/450V  
800  
1,150 254 66  
2,000/1,800/1,600  
47/45/42  
1,670 680 240  
1,764 760 329  
52/62  
138+156  
3.5 2μF/450V  
800  
Indoor air ow (Hi/Mid/Low)  
Indoor noise level (Hi/Mid/Low)  
Dimension (W*H*D)  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
Indoor unit  
Packing (W*H*D)  
Net/Gross weight  
Input  
Capacitor  
Speed  
Outdoor fan  
motor  
Number of rows  
Fin spacing  
Fin type  
Tube outside dia. and type  
Coil length height width  
2
1.4  
2
1.7  
2
1.5  
2
1.7  
2
1.7  
2
1.7  
2
1.7  
2
1.8  
2
1.8  
mm  
Outdoor coil  
Unhydrophilic aluminum  
Ø9.53, Innergroove tube  
955 915 44  
5,000  
mm  
mm  
651 559 44  
2,100  
43  
760 590 285  
887 655 355  
44/48  
775 660 44  
2,400  
48  
845 695 335  
970 770 395  
57/62  
850 810 44  
3,000  
55  
895 860 330  
1,043 915 395  
68/70  
955 915 44  
5,000  
57  
990 960 360  
1,120 1,090 435  
90/102  
955 915 44  
5,000  
57  
990 960 360  
1,120 1,090 435  
90/102  
955 915 44  
5,000  
57  
990 960 360  
1,120 1,090 435  
90/102  
715 1,220 44  
6,000  
58  
940 1,245 340  
1,058 1,380 435  
112/127  
715 1,220 44  
6,000  
58  
940 1,245 340  
1,058 1,380 435  
112/127  
Outdoor air ow  
Outdoor noise level  
m3/h  
dB(A)  
mm  
57  
Dimension (W*H*D)  
Packing (W*H*D)  
Net/Gross weight  
990 960 360  
1,120 1,090 435  
90/102  
Outdoor unit  
mm  
kg  
Refrigerant type/Quantity  
Design pressure (high side/low side)  
Liquid side  
g
R-410A/1,100  
4.2/2.5  
6.35 (1/4)  
12.7 (1/2)  
25  
15  
17~30  
18~45  
63/138/155  
R-410A/2,000  
4.2/2.5  
6.35 (1/4)  
12.7 (1/2)  
25  
15  
17~30  
18~45  
49/104/126  
R-410A/2,600  
4.2/2.5  
9.53 (3/8)  
16 (5/8)  
30  
15  
17~30  
18~45  
44/94/101  
R-410A/3,000  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
18~45  
27/55/62  
R-410A/3,000  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
18~45  
27/55/62  
R-410A/3,000  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
18~45  
27/55/62  
R-410A/3,000  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
18~45  
27/55/62  
R-410A/3,700  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
50  
30  
17~30  
18~45  
25/50/54  
R-410A/3,900  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
50  
30  
17~30  
18~45  
25/50/54  
MPa  
mm (inch)  
mm (inch)  
m
m
ºC  
Refrigerant  
piping  
Gas side  
Max. pipe length  
Max. difference in level  
Operation temp  
Ambient temp  
Qty’per 20’& 40’Fcl  
ºC  
Pieces  
TECHNICAL SPECIFICATION  
❥✱Floor/Ceiling YOHC (YOKC-YOJC)R-410A 50Hz Rev.291106  
Set  
YOHC12FSA(B)AAR  
YOKC12FS-A(B)AR  
YOHC18FSA(B)AAR  
YOKC18FS-A(B)AR  
YOHC24FSA(B)AAR  
YOKC24FS-A(B)AR  
YOHC30FSA(B)ACR  
YOKC30FS-A(B)CR  
YOJC30FS-A(B)CR  
3,380V, 50Hz  
YOHC30FSA(B)AAR  
YOKC30FS-A(B)AR  
YOJC30FS-A(B)AR  
1,220-240V, 50Hz  
YOHC36FSA(B)AAR  
YOKC36FS-A(B)AR  
YOJC36FS-A(B)AR  
1,220-240V, 50Hz  
36,000  
10.5  
YOHC36FSA(B)ACR  
YOKC36FS-A(B)CR  
YOJC36FS-A(B)CR  
3,380V, 50Hz  
YOHC48FSA(B)ACR  
YOKC48FS-A(B)CR  
YOJC48FS-A(B)CR  
3,380V, 50Hz  
48,000  
14  
YOHC60FSA(B)ACR  
YOKC60FS-A(B)CR  
YOJC60FS-A(B)CR  
3,380V, 50Hz  
60,000  
17  
Model  
Indoor unit  
Outdoor Unit  
YOJC12FS-A(B)AR  
1,220-240V, 50Hz  
YOJC18FS-A(B)AR  
1,220-240V, 50Hz  
YOJC24FS-A(B)AR  
1,220-240V, 50Hz  
Power supply  
Ph-V-Hz  
Btu/h  
kW  
kcal/h  
W
A
Btu/h  
kW  
kcal/h  
W
A
L/h  
W
A
12,000  
3.5  
3,024  
1,200  
6
13,000  
3.8  
3,276  
1,130  
5
1.2  
1,500  
7
26  
18,000  
5.4  
4,536  
1,900  
8.5  
20,500  
6
5,166  
1,850  
8
1.8  
2,400  
11.5  
36.8  
24,000  
7.1  
6,048  
2,700  
12  
27,300  
8
6,880  
2,800  
12.5  
30,000  
9.2  
7,560  
3,750  
6.3  
32,000  
9.4  
8,064  
3,500  
5.2  
3
4,620  
7.1  
61  
SCROLL  
3,650  
30,000  
9.2  
7,560  
3,750  
16.3  
32,000  
9.4  
8,064  
3,500  
15.2  
3
4,620  
21  
97  
SCROLL  
3,650  
17.65  
97  
Inner  
36,000  
10.5  
9,072  
3,750  
6.6  
39,000  
11.4  
9,828  
3,700  
6.5  
3.8  
4,400  
8
61  
SCROLL  
3,650  
Capacity  
Cooling  
9,072  
3,750  
16.3  
39,000  
11.4  
9,828  
3,500  
15.2  
3.6  
4,620  
21  
97  
SCROLL  
3,650  
17.65  
12,096  
4,700  
8.2  
52,000  
15.2  
13,104  
4,900  
8.6  
15,120  
6,000  
9.8  
68,000  
20  
17,136  
6,000  
9.8  
Input  
Rated current  
Capacity  
Heating  
Input  
Rated current  
Moisture Removal  
2.4  
4.8  
6
Max. input consumption  
Max. current  
Starting current  
3,300  
14.5  
61  
5,870  
10.7  
66  
SCROLL  
4,750  
8.22  
66  
Inner  
/
118/108/101  
2.5μF/450V  
820/695/620  
3
25.4 22  
1.7  
7,500  
12.8  
67  
SCROLL  
5,750  
9.77  
67  
Inner  
/
118/108/101  
2.5μF/450V  
820/695/620  
3
25.4 22  
1.7  
A
Type  
Input  
ROTARY  
1,145  
5.3  
26  
Inner  
35/370μF/V  
104/98  
1.5μF/450V  
1,190/1,000/890  
2
ROTARY  
1,870  
8.75  
36.8  
Inner  
50/370μF/V  
110/104/98  
2.5μF/450V  
1,280/1,190/1,000  
3
ROTARY  
2,430  
11.4  
61  
Inner  
50/400μF/V  
110/104/98  
2.5μF/450V  
1,280/1,190/1,000  
3
W
A
A
Rated current (RLA)  
Locked rotor Amp (LRA)  
Thermal protector  
Capacitor  
Input  
Capacitor  
Speed (Hi/Med/Low)  
Number of rows  
Tube pitch(a) row pitch(b)  
Fin spacing  
6.58  
61  
Inner  
6.58  
61  
Inner  
Compressor  
Indoor fan motor  
Indoor coil  
97  
Inner  
μF  
W
μF  
r/min  
/
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
60μF/440V  
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
60μF/440V  
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
/
142/134/132  
3.5μF/450V  
1,310/1,200/1,000  
3
mm  
mm  
25.4 22  
1.7  
25.4 22  
1.7  
25.4 22  
1.7  
25.4 22  
1.7  
25.4 22  
1.7  
25.4 22  
1.7  
25.4 22  
1.7  
Fin type  
Tube outside dia. and type  
Coil length height width  
Hydrophilic aluminum  
Ø9.53 innergroove tube  
905 203 66  
1,400/1,200/1,000  
45/43/40  
mm  
mm  
m3/h  
dB(A)  
mm  
mm  
kg  
W
μF  
r/min  
804 254 44  
600/480/400  
43/41/38  
995 660 198  
1,075 744 278  
29/35  
56  
2.5μF/450V  
800  
804 254 66  
800/600/500  
43/41/38  
995 660 198  
1,075 744 278  
30/37  
130  
2.5μF/450V  
750  
804 254 66  
1,000/900/700  
45/43/40  
995 660 198  
1,075 744 278  
30/37  
130  
3μF/450V  
800  
905 203 66  
1,200/1,000/800  
45/43/40  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
905 203 66  
1,400/1,200/1,000  
45/43/40  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
905 203 66  
1,400/1,200/1,000  
45/43/40  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
1,150 254 66  
2,000/1,800/1,600  
47/45/42  
1,670 680 240  
1,764 760 329  
52/62  
138+156  
3.5 2μF/450V  
800  
1,150 254 66  
2,000/1,800/1,600  
47/45/42  
1,670 680 240  
1,764 760 329  
52/62  
138+156  
3.5 2μF/450V  
800  
Indoor air ow (Hi/Mid/Low)  
Indoor noise level (Hi/Mid/Lo)  
Dimension (W*H*D)  
1,285 660 198  
1,365 744 278  
34/42  
307  
10μF/450V  
740  
Indoor unit  
Packing (W*H*D)  
Net/Gross weight  
Input  
Capacitor  
Speed  
Outdoor fan  
motor  
Number of rows  
Tube pitch(a) row pitch(b)  
Fin spacing  
2
2
25.4 22  
1.7  
Hydrophilic aluminum  
2
2
2
25.4 22  
1.7  
2
25.4 22  
1.7  
2
25.4 22  
1.7  
2
25.4 22  
1.8  
2
25.4 22  
1.8  
mm  
mm  
25.4 22  
1.4  
25.4 22  
1.5  
25.4 22  
1.7  
Outdoor coil  
Fin type  
Unhydrophilic aluminium  
Hydrophilic aluminum  
Tube outside dia. and type  
Coil length height width  
Number of circuits  
mm  
mm  
Ø9.53x0.35,Innergroove tube  
651 559 44  
2
2,100  
775 660 44  
3
2,400  
850 810 44  
4
3,000  
955 915 44  
8
5,000  
955 915 44  
8
5,000  
955 915 44  
8
5,000  
955 915 44  
8
5,000  
715 1220 44  
4
6,000  
715 1220 44  
4
6,000  
58  
940 1,245 340  
1,058 1,380 435  
112/127  
R-410A/4,200  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
50  
30  
17~30  
Outdoor air ow  
Outdoor noise level  
m3/h  
dB(A)  
mm  
mm  
kg  
43  
48  
55  
57  
57  
57  
57  
58  
Dimension (W*H*D)  
Packing (W*H*D)  
Net/Gross weight  
760 590 285  
887 655 355  
44/48  
R-410A/1,120  
4.2/2.5  
6.35 (1/4)  
12.7 (1/2)  
25  
15  
17~30  
845 695 335  
970 770 395  
57/62  
R-410A/2,050  
4.2/2.5  
6.35 (1/4)  
12.7 (1/2)  
25  
15  
17~30  
895 860 330  
1,043 915 395  
68/70  
R-410A/2,600  
4.2/2.5  
9.53 (3/8)  
16 (5/8)  
30  
15  
17~30  
990 960 360  
1,120 1,090 435  
90/102  
R-410A/3,100  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
990 960 360  
1,120 1,090 435  
90/102  
R-410A/3,450  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
990 960 360  
1,120 1,090 435  
90/102  
R-410A/3,450  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
990 960 360  
1,120 1,090 435  
90/102  
R-410A/3,100  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
30  
20  
17~30  
940 1,245 340  
1,058 1,380 435  
112/127  
R-410A/4,000  
4.2/2.5  
12.7 (1/2)  
19 (3/4)  
50  
30  
17~30  
-7~45  
25/50/54  
Outdoor unit  
Refrigerant type/Quantity  
Design pressure (high side/low side)  
Liquid side  
g
MPa  
mm (inch)  
mm (inch)  
m
m
ºC  
Refrigerant  
piping  
Gas side  
Max. pipe length  
Max. difference in level  
Operation temp  
Ambient temp  
Qty’per 20’& 40’Fcl  
ºC  
Pieces  
-7~45  
63/138/155  
-7~45  
49/104/126  
-7~45  
44/94/101  
-7~45  
27/55/62  
-7~45  
27/55/62  
-7~45  
27/55/62  
-7~45  
27/55/62  
-7~45  
25/50/54  
Floor/Ceiling DC Inverter “YOHC” R-410A, 50Hz  
Set  
Indoor  
Outdoor  
YOHC18DSBAAR  
YOKC18DS-BAR  
YOHC24DSBAAR  
YOKC24DS-BAR  
YOJC24DS-BAR  
220~240-1-50  
24,000  
2,220  
YOHC36DSBACR  
YOKC36DS-BCR  
YOJC36DS-BCR  
380V~3~ 50Hz  
36,000  
YOHC48DSBACR  
YOKC48DS-BCR  
YOJC48DS-BCR  
380V~3~ 50Hz  
48,000  
YOHC60DSBACR  
Model  
YOKC60DS-BCR  
YOJC60DS-BCR  
380V~3~ 50Hz  
60,000  
4,940  
11.47  
62,000  
4,880  
YOJC18DS-BAR  
220~240-1-50  
18,000  
1,550  
Power supply  
Cooling  
V-Ph-Hz  
Btu/h  
W
Capacity  
Input  
3,290  
8.77  
40,000  
3,160  
8.33  
3,880  
10.17  
1.1  
4,300  
11.47  
53,000  
4,170  
10.99  
4,850  
12.98  
1.16  
Rated current  
Capacity  
Input  
A
Btu/h  
W
6.8  
9.25  
21,000  
1,680  
7.35  
28,000  
2,250  
9.4  
2,750  
11  
1.15  
Heating  
Rated current  
A
11.4  
5,990  
15.69  
1.23  
Max. input consumption  
Max. current  
Starting current  
W
A
A
2,500  
10  
1.08  
Type  
Input  
DC Inverter Rotary  
DC Inverter Scroll  
3,665  
7.8  
W
A
A
1,650  
8
28  
1,650  
8
28  
3,665  
7.8  
28  
Thermal  
3,665  
7.8  
28  
Rated current (RLA)  
Locked rotor Amp (LRA)  
Protector  
Compressor  
28  
Capacitor  
μF  
ml  
50  
480  
50  
480  
50  
500  
AC Motor  
134  
3.5  
1,265/1,165/1,075  
50  
500  
50  
500  
Refrigerant oil  
Type  
Input  
W
μF  
r/min  
110  
2.5  
110  
2.5  
89.5  
2.5  
1,170/1,070/995  
59  
2.5  
Indoor fan motor  
Indoor coil  
Capacitor  
Speed (Hi/Me/Lo)  
Number of rows  
Fin spacing  
Fin type  
Tube outside dia.  
Tube Material  
Coil length height width  
1,310/1,190/1,020  
1,310/1,190/1,020  
1,145*1,035*975  
3
1.8  
3
1.8  
3
1.8  
3
1.8  
3
1.8  
mm  
mm  
Hydrophilic aluminium  
Ø9.52  
Innergroove tube  
905 203 66  
1,400/1,200/1,000  
45/43/40  
1,285 660 198  
1,379 744 296  
37/42  
307  
10  
mm  
m3/h  
dB(A)  
mm  
mm  
kg  
W
μF  
r/min  
828 254 66  
910/810/700  
49.5/-/-  
980 660 195  
1,089 744 296  
29/35  
129  
3
770  
2
828 254 66  
910/810/700  
53/-/-  
980 660 195  
1,089 744 296  
29/35  
150  
3
800  
2
1150 254 66  
2,000/1,800/1,600  
47/45/42  
1,670 680 240  
1,764 760 329  
1150 254 66  
2,000/1,800/1,600  
47/45/42  
1,670 680 240  
1,764 760 329  
Indoor air ow (Hi/Me/Lo)  
Indoor noise level (Hi/Me/Lo)  
Dimension (W*H*D)  
Indoor unit  
Packing (W*H*D)  
Net/Gross weight  
Input  
Capacitor  
Speed  
Number of rows  
Fin spacing  
Fin type  
Tube outside dia.  
Tube Material  
Coil length height width  
Number of circuits  
54/61  
150*2  
3.5*2  
800  
1
1.8  
54/61  
150*2  
3.5*2  
800  
1
1.8  
Outdoor fan motor  
740  
1
1.7  
mm  
mm  
mm  
1.7  
1.5  
Hydrophilic aluminium  
Ø9.52  
Innergroove tube  
955 915 22  
8
5,000  
57  
990 960 340  
1,120 1,015 435  
106/111  
Outdoor coil  
630 660 44  
4
2,400  
620 813 44  
2
3,000  
715 610 22  
1,150 305 66  
4
6,000  
58  
940 1,245 340  
1,058 1,300 435  
117/126  
4
6,000  
58  
940 1,245 340  
1,058 1,300 435  
112/127  
Outdoor air ow  
Outdoor noise level  
m3/h  
dB(A)  
mm  
mm  
kg  
56  
55  
Dimension (W*H*D)  
Packing (W*H*D)  
Net/Gross weight  
840 677 310  
965 770 395  
62.5/66.5  
1,650  
894 860 302  
1,043 915 395  
72/76.5  
Outdoor unit  
Refrigerant R-410A  
Throttle type  
Refrigerant piping  
g
2,200  
2,600  
EXV&Capillary  
9.53/16  
3,550  
4,200  
Liquid side/Gas side  
mm  
6.35/12.7  
9.53/16  
9.53/16  
9.53/16  
Remark: The above design and specications are subject to change without prior notice for product improvement.  
DE - COMMISSIONING DISMANTLING & DISPOSAL  
This product contains refrigerant under pressure, rotating parts, and electrical connections which may be a danger and cause injury!  
All work must only be carried out by competent persons using suitable protective clothing and safety precautions.  
Read the Manual  
Risk of electric shock  
Unit is remotely controlled and  
may start without warning  
1. Isolate all sources of electrical supply to the unit including any control system supplies switched by the unit. Ensure that all points of electrical and gas isolation are secured in the OFF position. The supply  
cables and gas pipework may then be disconnected and removed. For points of connection refer to unit installation instructions.  
2. Remove all refrigerant from each system of the unit into a suitable container using a refrigerant reclaim or recovery unit. This refrigerant may then be reused, if appropriate, or returned to the manufacturer  
for disposal. Under No circumstances should refrigerant be vented to atmosphere. Where appropriate, drain the refrigerant oil from each system into a suitable container and dispose of according to  
local laws and regulations governing disposal of oily wastes.  
3. Packaged unit can generally be removed in one piece after disconnection as above. Any xing down bolts should be removed and then unit lifted from position using the points provided and equipment of  
adequate lifting capacity. Reference MUST be made to the unit installation instructions for unit weight and correct methods of lifting. Note that any residual or spilt refrigerant oil should be mopped up and  
disposed of as described above.  
4. After removal from position the unit parts may be disposed of according to local laws and regulations.  

Minolta Di2510 User Manual
Oki Executive Series 1624n User Manual
Olympus Camedia Bu 300 User Manual
Panasonic Cs S18jku User Manual
Panasonic Cu E18gkr User Manual
Sanyo Eneloop Nc Mqn06 User Manual
Savin C6055 User Manual
Sharp Mx C311 User Manual
Xerox Workcentre Pe16 User Manual
Xerox Workcentre Pro 232 User Manual