FORM 115.20-NOM6 (1106)  
					SEQUENCE OF OPERATION  
					YCW With a Chilled Water Coil  
					The unit will respond to a cooling command from  
					the thermostat by powering a water control valve  
					open. The fan will operate at the speed selected at the  
					thermostat. When the space reaches the temperature  
					setpoint at the thermostat, the cooling valve will close  
					and the fan will continue to operate.  
					When using the T200 thermostat, the stat will auto-  
					matically regulate the fan speed based on the differ-  
					ence between the space temp and setpoint - @ 4˚F off  
					setpoint, the fan will run @ HI; @ 3˚F off setpoint, the  
					fan will run @ MED; @ 2˚F off setpoint, the fan will  
					run @ LO. When the thermostat is satisfied, the water  
					valve will be deenergized and the fan will revert to  
					LO speed.  
					When using the T420 manual C/O thermostat and the  
					TB3-3/TB2-5 jumper is in place, the fan will con-  
					tinue to operate at the fan speed selected. Removing  
					the jumper will cause the fan to shut down when the  
					thermostat is satisfied.  
					The YCWE With Both a Chilled Water Coil and  
					Electric Heating Coil.  
					The unit control thermostat, on a call for heating, will  
					energize the heater contactor(s). When the thermostat  
					is set for cooling, it will energize the chilled water  
					valve on a call for cooling. The fan will operate at  
					the speed selected at the thermostat. When the space  
					reaches the temperature setpoint at the thermostat,  
					the cooling valve will close (on cooling) or the heat-  
					ing contactors will open (on heating) and the fan will  
					continue to operate.  
					When using the T200 thermostat, the stat will auto-  
					matically regulate the fan speed based on the differ-  
					ence between the space temp and setpoint - @ 4˚F off  
					setpoint, the fan will run @ HI; @ 3˚F off setpoint, the  
					fan will run @ MED; @ 2˚F off setpoint, the fan will  
					run @ LO. When the thermostat is satisfied, the water  
					valve will be deenergized and the fan will revert to  
					LO speed.  
					When using the T420 manual C/O thermostat and the  
					TB3-3/TB2-5 jumper is in place, the fan will con-  
					tinue to operate at the fan speed selected. Removing  
					the jumper will cause the fan to shut down when the  
					thermostat is satisfied.  
					The YCW-HW with Both a Chilled Water Coil and a  
					Hot Water Coil.  
					The unit control thermostat, on a call for heating, will  
					energize the hot water control valve. When the ther-  
					mostat is set for cooling, it will energize the chilled  
					water valve on a call for cooling. The fan will operate  
					at the speed selected at the thermostat. When the space  
					reaches the temperature setpoint at the thermostat, the  
					cooling valve will close (on cooling) or the heating  
					valve will close (on heating) and the fan will continue  
					to operate.  
					When using the T421 auto C/O thermostat and the  
					TB3-3/TB2-5 jumper is in place, the fan will con-  
					tinue to operate at the fan speed selected. Removing  
					the jumper will cause the fan to shut down when the  
					thermostat is satisfied.  
					When using the T200 thermostat, the stat will auto-  
					matically regulate the fan speed based on the differ-  
					ence between the space temp and setpoint - @ 4˚F off  
					setpoint, the fan will run @ HI; @ 3˚F off setpoint, the  
					fan will run @ MED; @ 2˚F off setpoint, the fan will  
					run @ LO. When the thermostat is satisfied, the water  
					valve will be deenergized (on cooling) or the heating  
					contactor will open (on heating) and the fan will revert  
					to LO speed.  
					When using the T420 manual C/O thermostat and the  
					TB3-3/TB2-5 jumper is in place, the fan will con-  
					tinue to operate at the fan speed selected. Removing  
					the jumper will cause the fan to shut down when the  
					thermostat is satisfied.  
					When using the T421 auto C/O thermostat and the  
					TB3-3/TB2-5 jumper is in place, the fan will con-  
					tinue to operate at the fan speed selected. Removing  
					the jumper will cause the fan to shut down when the  
					thermostat is satisfied.  
					9
					JOHNSON CONTROLS