FORM 150.64-EG1 (505)
AIR-COOLED
SCROLL CHILLERS
STYLE D
YCAL0041 – YCAL0065
50 AND 60HZ
47 – 60 TON
165 – 210 KW
R-22
FORM 150.64-EG1
Introduction
YORK Air-Cooled Scroll Chillers provide chilled water for all air conditioning applications using
central station air handling or terminal units. They are completely self-contained and are designed
for outdoor (roof or ground level) installation. Each unit includes hermetic scroll compressors,
a liquid cooler, air cooled condenser, and a weather resistant microprocessor control center, all
mounted on a pressed steel base.
YORK INTERNATIONAL
3
Specification
GENERAL
tion for the cooler down to -20°F (-29°C) ambient. The
cooler is covered with 3/4” (19mm) flexible, closed-cell,
foam insulation (K~0.25).
The 47 - 60 Ton (165 - 210 kW) YCAL models are
shipped complete from the factory ready for installation
and use.
Brazed plate heat exchangers shall be UL(Underwriters
Laboratories) listed. Installing contractor must include
accommodations in the chilled water piping to allow
proper drainage and venting of the heat exchanger.
Water inlet and outlet connections are grooved for com-
patibility with factory supplied victaulic connections.
The unit is pressure-tested, evacuated, and fully charged
with Refrigerant-22 (HCFC-22) and includes an initial
oil charge. After assembly, a complete operational test
is performed with water flowing through the cooler to
assure that the refrigeration circuit operates correctly.
A strainer with a mesh size between .5 and 1.5 mm (40
mesh) is recommended upstream of the heat exchanger
to prevent clogging.
The unit structure is heavy-gauge, galvanized steel. This
galvanized steel is coated with baked-on powder paint,
which, when subjected to ASTM B117 1000 hour, salt
spray testing, yields a minimum ASTM 1654 rating of
“6”. Corrosion resistant wire mesh panels are added to
protect the condenser coil from incidental damage and
restrict unauthorized access to internal components.
Units are designed in accordance with NFPA 70 (Na-
tional Electric Code),ASHRAE/ANSI 15 Safety code for
mechanical refrigeration,ASME, Listed and labeled with
Intertek Testing Services (ETL) and rated in accordance
with ARI Standard 550/590-2003.
CONDENSER
Coils – Fin and tube condenser coils of seamless, inter-
nally-enhanced, high-condensing-coefficient, corrosion
resistant copper tubes are arranged in staggered rows,
mechanically expanded into aluminum fins. Integral
subcooling is included. The design working pressure of
the coil is 450 PSIG (31 bar).
Low Sound Fans – The condenser fans are composed
of corrosion resistant aluminum hub and glass-fiberrein-
forced composite blades molded into a low noise airfoil
section. They are designed for maximum efficiency and
are statically and dynamically balanced for vibration free
operation. They are directly driven by independent mo-
tors, and positioned for vertical air discharge. All blades
are statically and dynamically balanced for vibration-free
operation. The fan guards are constructed of heavy-
gauge, rust-resistant, PVCcoated steel wire.
COMPRESSORS
The chiller has suction-gas cooled, hermetic, scroll com-
pressors. The YCALcompressors incorporate a compli-
ant scroll design in both the axial and radial direction.All
rotating parts are statically and dynamically balanced.A
large internal volume and oil reservoir provides greater
liquid tolerance. Compressor crankcase heaters are also
included for extra protection against liquid migration.
COOLER
Motors – The fan motors are Totally EnclosedAir-Over,
squirrel-cage type, current protected. They feature
ball bearings that are double-sealed and permanently
lubricated.
The cooler is equipped with a heater controlled by a
separate thermostat. The heater provides freeze protec-
4
YORK INTERNATIONAL
FORM 150.64-EG1
MILLENNIUM CONTROL CENTER
All controls are contained in a NEMA 3R/12 (and
equivalent to IP55*) cabinet with hinged outer door and
includes:
UNIT ON/OFF switch
The microprocessor control center is capable of dis-
playing the following:
Liquid Crystal Display with Light Emitting Diode back-
lighting for outdoor viewing:
Two display lines
Twenty characters per line
• Return and leaving liquid temperature
• Low leaving liquid temperature cutout setting
• Low ambient temperature cutout setting
• Outdoor air temperature
Color coded 12-button non-tactile keypad with sections
for:
DISPLAY/PRINT of typical information:
Chilled liquid temperatures
• English or Metric data
• Suction pressure cutout setting
• Each system suction pressure
• Discharge pressure (optional)
Ambient temperature
System pressures (each circuit)
Operating hours and starts (each compressor)
Print calls up to the liquid crystal display:
Operating data for the systems
• Liquid Temperature Reset via a YORK ISN DDC or
Building Automation System (by others) via:
History of fault shutdown data for up to
the last six fault shutdown conditions
An RS-232 port, in conjunction with this
press-to-print button, is provided to permit
the capability of hard copy print-outs via a
separate printer (by others).
- a pulse width modulated (PWM) input as stan-
dard
- a 4-20 milliamp or 0 -10 VDC input, or contact
closure with the optional B.A.S. interface option
• Anti-recycle timer status for each system
• Anti-coincident system start timer condition
• Compressor run status
ENTRY section to:
ENTER setpoints or modify system values
• No cooling load condition
• Day, date and time
SETPOINTS updating can be performed to:
Chilled liquid temperature setpoint and range
Remote reset temperature range
Set daily schedule/holiday for start/stop
Manual override for servicing
Low and high ambient cutouts
Number of compressors
• Daily start/stop times
• Holiday status
• Automatic or manual system lead/lag control
• Lead system definition
• Compressor starts & operating hours
(each compressor)
Low liquid temperature cutout
Low suction pressure cutout
High discharge pressure cutout
Anti-recycle timer (compressor start cycle
time)
• Status of hot gas valves, evaporator heater
and fan operation
• Run permissive status
• Number of compressors running
• Liquid solenoid valve status
• Load & unload timer status
• Water pump status
Anti-coincident timer (delay compressor
starts)
UNIT section to:
Set time
Set unit options
*
Intensity of Protection European Standard
YORK INTERNATIONAL
5
Provisions are included for: pumpdown at shutdown;
optional remote chilled water temperature reset and two
steps of demand load limiting from an external building
automation system. Unit alarm contacts are standard.
POWER PANEL
Each panel contains:
• Compressor power terminals
• Compressor motor starting contactors per l.E.C.**
• Control power terminals to accept incoming for
115-1-60 control power
The operating program is stored in non-volatile memory
(EPROM) to eliminate chiller failure due to AC powered
failure/battery discharge. Programmed setpoints are
retained in lithium battery-backed RTC memory for 5
years minimum.
• Fan contactors & overload current protection
The power wiring is routed through liquid-tight conduit
to the compressors and fans.
** International Electrotechnical Commission
6
YORK INTERNATIONAL
FORM 150.64-EG1
Options and Accessories
includes the Discharge Pressure Transducer / Readout-
Capability option.) (Field-Mounted.)
POWER OPTIONS:
COMPRESSOR POWER CONNECTIONS – Single-
point (YCAL0041-0065) terminal block connection(s) are
provided as standard. The following power connections
are available as options. (See electrical data for specific
voltage and options availability.) (Factory-Mounted.)
BUILDINGAUTOMATION SYSTEM INTERFACE – The
factory addition of a Printed Circuit Board to accept a
4-20 milliamp, 0-10VDC or contact closure input to reset
the leaving chiller liquid temperature from a BuildingAu-
tomation System. (Only one of following options can be
offered on a unit at a time: BAS, Remote Control Panel
or Multi-unit Sequence Control.) (Factory-Mounted.)
(The standard unit capabilities include remote startstop,
remote water temperature reset via a PWM input signal
or up to two steps of demand (load) limiting depending
on model.) (The standard control panel can be directly
connected to a YORK Building Automated System via
the standard onboard RS485 communication port.)
SINGLE-POINT SUPPLY TERMINAL BLOCK – (stan-
dard on YCAL0041 - 0065 models). Includes enclosure,
terminal-block and interconnecting wiring to the com-
pressors. Separate external protection must be supplied,
by others, in the incoming compressor-power wiring. (Do
not include this option if either the SinglePoint NonFused
Disconnect Switch or Single-Point Circuit Breaker op-
tions have been included.)
LANGUAGE LCD AND KEYPAD DISPLAY – Spanish,
French, and German unit LCD controls and keypad
display available. Standard language is English.
SINGLE-POINT NON-FUSED DISCONNECT SWITCH
– Unit-mounted disconnect switch with external, lockable
handle (in compliance with Article 440-14 of N.E.C.),
can be supplied to isolate the unit power voltage for
servicing. Separate external fusing must be supplied,
by others in the power wiring, which must comply with
the National Electrical Code and/or local codes.
DISCHARGE PRESSURE TRANSDUCERS AND
READOUT CAPABILITY – The addition of pressure
transducers allows models to sense and display dis-
charge pressure. This is recommended for brine chilling
applications. (This option is included with either the low
or high ambient kits.) (Factory-Mounted.)
SINGLE-POINT CIRCUIT BREAKER –Aunit mounted
circuit breaker with external, lockable handle (in com-
pliance with N.E.C. Article 440-14), can be supplied
to isolate the power voltage for servicing. (This option
includes the Single-Point Power connection.)
•
Suction Pressure Transducers: Permits unit to
sense and display suction pressure. This capability
is standard on YCAL0041-0065 models.
CONTROL TRANSFORMER – Converts unit power
voltage to 115-1-60 (0.5 or 1.0 KVA capacity). Fac-
tory mounting includes primary and secondary wiring
between the transformer and the control panel. (Fac-
tory-Mounted.)
MOTOR CURRENT MODULE – Capable of monitoring
compressor motor current. Provides extra protection
against compressor reverse rotation, phase-loss and
phase imbalance. Option consists of one module per
electrical system. (Factory-Mounted.)
POWER FACTOR CORRECTION CAPACITORS – Will
correct unit compressor power factors to a 0.90-0.95.
(Factory-Mounted.)
OPTIVIEW REMOTE CONTROL PANEL - Graphical
interface panel to remotely control and monitor up to 8
different units. (Refer to form 201.18-SG4 for detailed
information)
CONTROL OPTIONS:
AMBIENT KIT (LOW) – Units will operate to 25°F (-4°C).
This accessory includes all necessary components to
permit chiller operation to 0°F (-18°C). (This option in-
cludes the Discharge Pressure Transducer / Readout
Capability option.) For proper head pressure control in
applications below 25°F (-4°C), where wind gusts may
exceed five mph, it is recommended that Optional Con-
denser Louvered Enclosure Panels also be included.
(Factory-Mounted.)
MULTI-UNIT SEQUENCING – A separate Sequencing
Control Center is provided to handle sequencing control
of up to eight chillers in parallel based on mixed liquid
temperature (interconnecting wiring by others). (Only
one of following options can be offered on a unit at a
time: BAS, Remote Control Panel or Multi-unit Sequence
Control.) (Factory-Mounted.)
COMPRESSOR, PIPING, EVAPORATOR
OPTIONS:
AMBIENT KIT (HIGH) – Required if units are to operate
when the ambient temperature is above 115°F (46°C).
Includes discharge pressure transducers. (This option
LOW TEMPERATURE BRINE – Required for brine
YORK INTERNATIONAL
7
chilling below 30°F (-1°C) leaving brine temperature
for YCAL0041 - 0065 models. Option includes resized
thermal expansion valve. (Factory-Mounted)
REMOTE DX COOLER – A split system arrangement
with the cooler, leaving & return water sensors, liquid
line solenoid valves, filter driers, sightglasses & TXVs
shipped loose for field connection to the air-cooled con-
densing section. The DX cooler and outdoor section will
have a nitrogen holding charge. Interconnecting rigid
piping, wiring and refrigerant are by others. Includes
YORK Service startup. See Form 150.62-NM1.1 (200)
for other application information. (This option includes
the Crankcase Heater option.)(Field-Mounted.)
CHICAGO CODE RELIEF VALVES – Unit will be pro-
vided with relief valves to meet Chicago code require-
ments. (Factory-Mounted)
SERVICE ISOLATION VALVE – Service suction and
discharge (ball type) isolation valves are added to unit
per system. This option also includes a system high
pressure relief valve in compliance with ASHRAE 15.
(Factory-Mounted)
CONDENSER AND CABINET OPTIONS:
Condenser coil protection against corrosive environ-
ments is available by choosing any of the following op-
tions. For additional application recommendations, refer
to FORM 150.12-ES1. (Factory-Mounted.)
HOT GAS BY-PASS – Permits continuous, stable opera-
tion at capacities below the minimum step of compressor
unloading to as low as 5% capacity (depending on both
the unit and operating conditions) by introducing an
artificial load on the cooler. Hot gas by-pass is installed
on only refrigerant system #1 on two-circuited units.
(Factory-Mounted)
PRE-COATED FIN CONDENSER COILS – The unit's
coils are constructed with black epoxy coated aluminum
fins. This can provide corrosion resistance comparable
to copper-fin coils in typical seashore locations. Either
these or the post-coated coils (below), are recommend-
ed for units being installed at the seashore or where salt
spray may hit the unit.
DX COOLER 300 PSIG (21 bar) DWP WATERSIDE
– The waterside will be of 300 PSIG (21 bar) instead of
the standard 150 PSIG DWP. 300 PSIG R.F. flanges are
included on the DX cooler nozzles. (Factory-Mounted.)
The companion flanges will be field-supplied by oth-
ers.
POST-COATED DIPPED CONDENSER COILS – The
unit's coils are constructed with dipped-cured condenser
coils. This is another choice for seashore and other
corrosive applications (with the exception of strong al-
kalies, oxidizers and wet bromine, chlorine and fluorine
in concentrations greater than 100 ppm).
FLANGES (VICTAULIC TYPE) – Consists of two (2)
Flange adapters for grooved end pipe (standard 150
psi [10.5 bar] cooler).
FLOW SWITCH – The flow switch or its equivalent must
be furnished with each unit.
COPPER FIN CONDENSER COILS – The unit's coils
are constructed with copper fins. (This is not recom-
mended for units in areas where they may be exposed
to acid rain.)
150 PSIG (10.5 bar) DWP – For standard units. Johnson
Controls model F61MG-1C Vapor-proof SPDT, NEMA
4X switch (150 PSIG [10.5 bar] DWP), -20°F to 250°F
(-29°C to 121°C), with 1” NPT connection for upright
mounting in horizontal pipe. (Field-Mounted.)
ENCLOSURE PANELS (UNIT) – Tamperproof En-
closure Panels prevent unauthorized access to units.
Enclosure Panels can provide an aesthetically pleas-
ing alternative to expensive fencing. Additionally, for
proper head pressure control, YORK recommends the
use of :
300 psig (21 bar) DWP – For units with optional 300
PSIG (21 bar) DX cooler. McDonnell & Miller model
FS74W Vapor-proof SPDT, NEMA4X switch (300 PSIG
(21 bar) DWP), -20°F to 300°F (-29°C to 149°C), with 1¼
inch MPT connection for upright mounting in horizontal
pipe. (Field-Mounted.)
LOUVERED PANELS (Full Unit) – Louvered panels
surround the front, back, and sides of the unit. They
prevent unauthorized access and visually screen unit
components. Unrestricted air flow is permitted through
generously sized louvered openings. This option is ap-
plicable for any outdoor design ambient temperature up
to 115°F (46°C). (Factory-Mounted.)
DIFFERENTIAL PRESSURE SWITCH – Alternative
to an above mentioned flow switch. Pretempco model
DPS300AP40PF-82582-5 (300 psi max. working pres-
sure), SPDT 5 amp 125/250VAC switch, Range 0 - 40
PSID, deadband 0.5 - 0.8 psi, with 1/4” NPTE Pressure
Connections.
SOUND ATTENUATION – One or both of the follow-
ing sound attenuation options are recommended for
8
YORK INTERNATIONAL
FORM 150.64-EG1
residential or other similar sound-sensitive locations.
Louvered Panels can be ordered for winter applications
where wind gusts may exceed five miles per hour. The
following types of enclosure options are available:
of welded PVC, reinforced for temperature and UV
resistance. (Factory-Mounted.)
ULTRA QUIET FANS – Lower RPM, 8-pole fan motors
are used with steeper-pitch fans. (Factory-Mounted.)
COMPRESSORACOUSTICSOUNDBLANKET– Each
compressor is individually enclosed by an acoustic
sound blanket. The sound blankets are made with one
layer of acoustical absorbent textile fiber of 5/8” (15mm)
thickness; one layer of anti-vibrating heavy material
thickness of 1/8” (3mm). Both are closed by two sheets
VIBRATION ISOLATORS – Level adjusting, spring
type 1” (25.4mm) or seismic deflection or neoprene
pad isolators for mounting under unit base rails. (Field-
Mounted.)
YORK INTERNATIONAL
9
This page intentionally left blank.
10
YORK INTERNATIONAL
FORM 150.64-EG1
Selection Data
GUIDE TO SELECTION
6. Ethylene Glycol Correction Factors – The fol-
lowing factors are to be applied to the standard
ratings for units cooling ethylene glycol.
Capacity ratings for YORK YCAL PackagedAir-Cooled
Liquid Chillers, shown on pages 16 through 39 cover
the majority of design applications for these units. For
unusual applications or uses beyond the scope of this
catalog, please consult your nearest YORK Office or
representative.
ETHYLENE GLYCOL
%
COMPR
KW
GPM
°F/TON
PRESS FREEZE
TONS
WEIGHT
DROP
1.049
1.124
1.258
1.430
1.650
PT
26.2
17.9
6.7
10
20
30
40
50
0.996
0.991
0.984
0.976
0.968
0.999
0.998
0.997
0.995
0.994
24.3
25.1
25.9
26.9
28.0
SELECTION RULES
-8.1
-28.9
1. Ratings – Ratings may be interpolated, but must
not be extrapolated. The Ratings given on pages 16
through 39 and the DESIGN PARAMETERS given
on page 11 indicate the limits of application for these
chillers.
7. Propylene Glycol Correction Factors – The fol-
lowing factors are to be applied to the standard
ratings for units cooling propylene glycol.
2. Cooler Water – Ratings are based upon 2.4 GPM
per ton which is equal to a 10°F chilled water range
and a 0.0001 fouling factor for the cooler at sea level.
Tables on pages 16 through 39 give capacity, com-
pressor kW required, cooler GPM and unit EER.
PROPYLENE GLYCOL
%
COMPR
KW
GPM
°F/TON
PRESS FREEZE
TONS
WEIGHT
DROP
1.014
1.104
1.234
1.399
1.599
PT
26
19
9
10
20
30
40
50
0.995
0.984
0.973
0.960
0.943
0.999
0.997
0.994
0.992
0.989
24.0
24.3
24.9
25.6
26.6
3. Condenser – Ratings are given in terms of air on
condenser in degrees Fahrenheit.
4. Copper Fin Condenser Ratings – Since the ther-
mal conductivity of copper is slightly higher than
aluminum, apply the following corrections to the
standard ratings. Tons x 0.97 and compressor kW
x 0.99.
-6
-28
METHOD OF SELECTION
5. Performance Data Correction Factors – Ratings
are based on 0.0001 cooler fouling factor, 10°F
chilled water range and at sea level. For operation at
different conditions, apply the appropriate correction
factor from the following table.
To select of YORK Packaged Air-Cooled Liquid Chiller,
the following data must be known:
1. Design Capacity in tons refrigeration (TR).
2. Entering and Leaving Liquid Temperatures.
3. Outside ambient air temperature in degrees F.
4. GPM of chilled liquid.
FOULING FACTOR
0.0001
0.00025
TEMP
SPLIT
ALTITUDE
COMPR
COMPR
TONS
TONS
kW
kW
Determine capacity requirements from the following
formula:
8
0.990
1.000
1.012
1.021
0.987
0.997
1.009
1.018
0.983
0.994
1.005
1.014
0.980
0.990
1.002
1.011
0.998
1.000
1.003
1.005
1.005
1.008
1.010
1.012
1.014
1.016
1.019
1.021
1.023
1.025
1.028
1.030
0.979
0.991
1.002
1.012
0.978
0.988
1.000
1.009
0.975
0.985
1.111
1.006
0.971
0.982
0.993
1.002
0.996
0.998
1.001
1.003
1.003
1.006
1.008
1.010
1.012
1.014
1.017
1.019
1.021
1.023
1.026
1.028
10
12
14
8
10
12
14
8
10
12
14
8
10
12
14
SEA LEVEL
TR x 24
RANGE (°F)
GPM =
EXAMPLE – WATER CHILLING
2000 FT.
4000 FT.
6000 FT.
1. Given: Provide a capacity of 50 tons at 42 F leav-
ing water at 10 F range. 0.0001FF, 85 F air on the
condenser, at sea level and 60 Hz.
2. Find: Unit Size, Compressor KW Output
3. From the ratings on page 18.
Select: YCAL0061 (English Units)
YORK INTERNATIONAL
11
a. 56.1 Tons
7. Determine average full load Compressor kW at 34
tons
b. 55.9 Compressor KW
c. 10.7 Unit EER
34tons
x(41.77) = 41.93CompressorkW
4. Calculate Compressor kW at 50 Tons:
33.87tons
8. Determine E.G. GPM:
50
kW =
x55.9kW = 49.8kW
Tons ×Gal.°F / min/ Tonfactor
56.1
5. Calculate GPM:
GPM =
34.0× 26.1
GPM =
= 88.7(GPM)
(50Tons)× 24
10
GPM =
= 120GPM
9. Determine Cooler Pressure Drop:
6. From page ____, read 6 ft of water cooler pressure
drop from GPM:
a. See E.G. correction factors for 30% by weight
E.G.
READ: 1.258 Pressure Drop factor
b. See page 14 at 88.7 GPM for YCAL0045
READ: 6.5_Water H2O PD
7. A YCAL0061 is suitable.
EXAMPLE - BRINE CHILLING
Example - Brine Chilling
c. Cooler Pressure Drop = 6.5 x 1.258 or 8.17
A YCAL0045 is suitable.
1. Given: Provide a capacity of 34 tons cooling 30% by
weight Ethylene Glycol from 50 F to 40 F, 0.00025FF,
95 F air on the condenser, 60 Hz and 4000 ft. alti-
tude.
2. Determine:
a. Unit Size
b. KW Input
c. Ethylene Glycol GPM
d. Cooler Pressure Drop
3. See E.G. correction factors, for 30% by weight
E.G.
READ: 0.984 Tons Factor
0.997 Compr. KW factor
26.1 Gal,/ F/Tons Factor
4. See Performance Data Correction Factors for
0.00025 fouling factor and 4,000 ft. altitude.
READ: 0.975 Tons factor
1.012 kW factor
5. From RATINGS on page 16.
SELECT: YCAL0045 (English Units)
35.3 Tons
41.1 Compressor kW
6. Determine YCAL0045 brine cooling capacity and
Compressor kW requirement from pg 14:
a. TONS: = 35.3 x 0.984 x 0.975 = 33.87
b. Compr. KW = 41.1 x 0.997 x 1.012 = 41.77
12
YORK INTERNATIONAL
FORM 150.64-EG1
Design Parameters
ENGLISH
LEAVING WATER
YCAL
COOLER FLOW (GPM)
AIR ON CONDENSER (°F)
TEMPERATURE (°F)
MIN
40
40
40
40
40
40
MAX
55
MIN
40
40
40
60
60
60
MAX
200
200
200
300
300
300
MIN
0
MAX
125
125
125
125
125
125
0041
0045
0051
0055
0061
0065
55
0
55
0
55
0
55
0
55
0
SI UNITS
LEAVING WATER
TEMPERATURE (°DC)
YCAL
COOLER FLOW (L/S)
AIR ON CONDENSER (°C)
MIN
4.4
4.4
4.4
4.4
4.4
4.4
MAX
12.8
12.8
12.8
12.8
12.8
12.8
MIN
2.5
2.5
2.5
3.8
3.8
3.8
MAX
12.6
12.6
12.6
18.9
18.9
18.9
MIN
-17.7
-17.7
-17.7
-17.7
-17.7
-17.7
MAX
51.7
51.7
51.7
51.7
51.7
51.7
0041
0045
0051
0055
0061
0065
NOTES:
1. For leaving brine temperature below 40°F (4.4°C), contact your nearest YORK Office for application requirements.
2. For leaving water temperature higher than 55°F (12.8°C), contact the nearest YORK Office for application guidelines.
3. The evaporator is protected against freezing to -20°F (-28.8°C) with an electric heater as standard.
4. For operation at temperatures below 25°F (-3.9°C), the optional Low Ambient Kit will need to be installed on the system (for YCAL0041-0065
models only).
5. For operation at temperatures above 115°F (46.1°C), the optional High Ambient Kit will need to be installed on the system.
YORK INTERNATIONAL
13
Water Pressure Drop
ENGLISH
100
10
1
A
B
C
D
10
100
FLOW, GPM
1000
Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum and maximum
flow points.
14
YORK INTERNATIONAL
FORM 150.64-EG1
SI
1000
100
10
A
B
C
D
1
1
10
FLOW, L/S
100
Note: Water Pressure Drop Curves may extend past the minimum and maximum water flow ranges. See page 13 for minimum and maximum
flow points.
YORK INTERNATIONAL
15
Ratings - R-22 (60Hz - English Units)
IPLV= 13.9
100.0
MODEL: YCAL0041EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
35.8
37.0
38.1
38.7
39.3
40.6
41.8
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
39.9
40.1
40.4
40.6
40.7
41.0
41.2
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
30.3
30.6
30.8
31.0
31.1
31.4
31.7
12.0
12.3
12.6
12.7
12.9
13.2
13.5
35.1
36.2
37.4
38.0
38.6
39.8
41.0
32.0
32.2
32.5
32.6
32.8
33.0
33.3
11.2
11.5
11.8
11.9
12.1
12.4
12.6
34.4
35.5
36.7
37.2
37.8
39.0
40.2
33.8
34.0
34.3
34.4
34.5
34.8
35.1
10.5
10.8
11.0
11.2
11.3
11.6
11.8
33.7
34.8
35.9
36.4
37.0
38.2
39.4
35.7
35.9
36.2
36.3
36.5
36.7
37.0
9.8
32.9
34.0
35.1
35.6
36.2
37.3
38.5
37.7
38.0
38.2
38.4
38.5
38.8
39.1
9.1
9.4
32.1
33.2
34.3
34.8
35.3
36.5
37.6
8.5
8.7
8.9
9.0
9.2
9.4
9.6
10.0
10.3
10.4
10.6
10.8
11.1
9.6
9.7
9.8
10.1
10.3
IPLV= 14.0
100.0
MODEL: YCAL0045EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
39.0
40.3
41.5
42.2
42.8
44.1
45.5
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
43.5
43.8
44.1
44.2
44.4
44.7
45.1
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
33.4
33.7
34.0
34.1
34.3
34.6
35.0
12.0
12.3
12.6
12.7
12.9
13.2
13.4
38.1
39.3
40.6
41.2
41.9
43.2
44.5
35.1
35.4
35.7
35.9
36.0
36.4
36.7
11.2
11.5
11.8
11.9
12.1
12.3
12.6
37.2
38.4
39.7
40.3
40.9
42.2
43.5
37.0
37.3
37.6
37.7
37.9
38.2
38.6
10.5
10.8
11.0
11.2
11.3
11.6
11.8
36.3
37.5
38.7
39.3
40.0
41.2
42.5
39.0
39.3
39.6
39.8
39.9
40.3
40.6
9.8
35.4
36.6
37.8
38.4
39.0
40.2
41.5
41.2
41.5
41.8
41.9
42.1
42.4
42.8
9.1
9.3
34.4
35.6
36.8
37.4
38.0
39.2
40.5
8.4
8.7
8.9
9.0
9.1
9.4
9.6
10.0
10.3
10.4
10.5
10.8
11.0
9.6
9.7
9.8
10.1
10.3
IPLV= 14.3
100.0
MODEL: YCAL0051EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
45.0
46.4
47.9
48.7
49.5
51.0
52.6
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
50.8
51.1
51.4
51.6
51.7
52.1
52.4
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
38.9
39.2
39.5
39.7
39.8
40.1
40.5
12.1
12.4
12.8
12.9
13.1
13.4
13.7
43.9
45.4
46.9
47.6
48.4
49.9
51.4
41.0
41.3
41.6
41.7
41.9
42.2
42.5
11.3
11.6
11.9
12.1
12.2
12.5
12.8
42.8
44.3
45.8
46.5
47.2
48.8
50.3
43.2
43.5
43.8
43.9
44.1
44.4
44.7
10.5
10.8
11.1
11.3
11.4
11.7
12.0
41.8
43.2
44.7
45.4
46.1
47.6
49.1
45.6
45.9
46.2
46.3
46.5
46.8
47.1
9.8
40.7
42.1
43.6
44.3
45.0
46.5
48.0
48.1
48.4
48.7
48.9
49.0
49.3
49.7
9.1
9.4
39.7
41.1
42.5
43.2
43.9
45.3
46.8
8.4
8.7
8.9
9.1
9.2
9.4
9.7
10.1
10.4
10.5
10.6
10.9
11.2
9.6
9.8
9.9
10.2
10.4
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
16
YORK INTERNATIONAL
FORM 150.64-EG1
IPLV= 13.9
MODEL: YCAL0041EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
LCWT
(°F)
TONS
31.3
32.4
33.4
34.0
34.5
35.6
36.7
EER
7.9
8.1
8.3
8.4
8.5
8.7
9.0
TONS
30.5
31.5
32.5
33.1
33.6
34.7
35.8
EER
7.3
7.5
7.7
7.8
7.9
8.1
8.3
TONS
29.6
30.6
31.6
32.1
32.7
33.7
34.8
KW
47.4
47.6
47.9
48.0
48.1
48.4
48.6
EER
6.7
6.9
7.1
7.2
7.3
7.5
7.7
TONS
28.7
29.7
30.7
31.2
31.7
32.8
33.8
EER
6.2
6.4
6.5
6.6
6.7
6.9
7.1
TONS
27.8
28.7
29.7
30.2
30.7
31.8
32.8
KW
53.2
53.4
53.7
53.8
53.9
54.1
54.4
EER
5.7
5.8
6.0
6.1
6.2
6.4
6.6
40.0
42.0
44.0
45.0
46.0
48.0
50.0
42.2
42.5
42.7
42.9
43.0
43.3
43.6
44.7
45.0
45.2
45.3
45.5
45.7
46.0
50.2
50.4
50.7
50.8
50.9
51.2
51.4
IPLV= 14.0
MODEL: YCAL0045EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
33.5
34.6
35.8
36.4
37.0
38.2
39.4
EER
7.8
8.0
8.2
8.4
8.5
8.7
8.9
TONS
32.5
33.6
34.8
35.4
36.0
37.2
38.4
EER
7.2
7.4
7.6
7.7
7.8
8.0
8.3
TONS
31.5
32.6
33.7
34.3
34.9
36.0
37.2
KW
51.4
51.7
52.0
52.1
52.3
52.7
53.0
EER
6.6
6.8
7.0
7.1
7.2
7.4
7.6
TONS
30.4
31.5
32.6
33.2
33.8
34.9
36.1
EER
6.1
6.3
6.5
6.6
6.7
6.8
7.0
TONS
29.3
30.4
31.5
32.0
32.6
33.7
34.9
EER
5.6
5.7
5.9
6.0
6.1
6.3
6.5
40.0
42.0
44.0
45.0
46.0
48.0
50.0
45.9
46.2
46.5
46.7
46.9
47.2
47.6
48.6
48.9
49.2
49.4
49.5
49.8
50.2
54.4
54.7
55.0
55.1
55.3
55.6
56.0
57.5
57.8
58.1
58.3
58.5
58.8
59.1
IPLV= 14.3
MODEL: YCAL0051EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
38.6
39.9
41.3
42.0
42.7
44.1
45.6
EER
7.8
8.0
8.3
8.4
8.5
8.7
9.0
TONS
37.5
38.8
40.1
40.8
41.5
42.9
44.3
EER
7.2
7.4
7.7
7.8
7.9
8.1
8.3
TONS
36.3
37.6
38.9
39.6
40.3
41.6
43.0
KW
59.9
60.2
60.6
60.8
60.9
61.3
61.7
EER
6.7
6.9
7.1
7.2
7.3
7.5
7.7
TONS
35.1
36.4
37.7
38.3
39.0
40.3
41.7
EER
6.1
6.3
6.5
6.6
6.7
6.9
7.1
TONS
33.9
35.1
36.4
37.0
37.7
39.0
40.3
EER
5.6
5.8
6.0
6.1
6.1
6.3
6.5
40.0
42.0
44.0
45.0
46.0
48.0
50.0
53.7
54.0
54.3
54.5
54.6
55.0
55.3
56.7
57.0
57.4
57.5
57.7
58.0
58.4
63.3
63.6
64.0
64.2
64.4
64.7
65.1
66.8
67.2
67.6
67.8
68.0
68.3
68.7
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YORK INTERNATIONAL
17
Ratings - R-22 (60Hz - English Units) - Cont.
IPLV= 13.6
100.0
MODEL: YCAL0055EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
48.6
50.2
51.8
52.7
53.5
55.2
57.0
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
55.1
55.4
55.7
55.9
56.1
56.4
56.7
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
42.1
42.4
42.7
42.8
43.0
43.3
43.6
11.9
12.3
12.6
12.8
12.9
13.3
13.6
47.6
49.2
50.8
51.6
52.5
54.2
55.9
44.4
44.7
44.9
45.1
45.2
45.5
45.9
11.2
11.5
11.8
12.0
12.1
12.4
12.8
46.6
48.2
49.8
50.6
51.4
53.1
54.7
46.8
47.1
47.4
47.5
47.7
48.0
48.3
10.5
10.7
11.0
11.2
11.3
11.6
11.9
45.6
47.1
48.7
49.5
50.3
51.9
53.6
49.4
49.7
50.0
50.2
50.3
50.6
50.9
9.7
44.6
46.1
47.6
48.4
49.1
50.7
52.4
52.2
52.5
52.8
52.9
53.1
53.4
53.7
9.1
9.3
43.5
44.9
46.4
47.2
48.0
49.5
51.1
8.4
8.7
8.9
9.0
9.2
9.4
9.7
10.0
10.3
10.4
10.6
10.9
11.2
9.6
9.7
9.9
10.1
10.4
IPLV= 14.2
100.0
MODEL: YCAL0061EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
56.8
58.7
60.6
61.5
62.5
64.5
66.5
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
65.5
66.0
66.5
66.7
67.0
67.5
68.0
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
49.8
50.2
50.6
50.9
51.1
51.5
52.0
12.1
12.4
12.7
12.8
13.0
13.3
13.6
55.6
57.5
59.4
60.3
61.3
63.2
65.2
52.6
53.0
53.4
53.6
53.9
54.3
54.8
11.3
11.5
11.8
12.0
12.1
12.4
12.7
54.5
56.3
58.1
59.1
60.0
61.9
63.9
55.5
56.0
56.4
56.6
56.8
57.3
57.8
10.5
10.8
11.0
11.2
11.3
11.6
11.9
53.3
55.0
56.9
57.8
58.7
60.6
62.5
58.7
59.1
59.6
59.8
60.0
60.5
61.0
9.8
52.0
53.8
55.6
56.5
57.4
59.2
61.1
62.0
62.5
62.9
63.2
63.4
63.9
64.4
9.1
9.3
50.8
52.5
54.2
55.1
56.0
57.8
59.7
8.4
8.7
8.9
9.0
9.1
9.4
9.6
10.0
10.3
10.4
10.6
10.8
11.1
9.6
9.7
9.8
10.1
10.3
IPLV= 14.5
100.0
MODEL: YCAL0065EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
&
80.0
KW
&
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
&
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
72.2
72.8
73.4
73.7
74.0
74.7
75.3
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
&
&
&
59.9
61.8
63.9
64.9
65.9
68.0
70.2
61.4
61.9
62.5
62.7
63.0
63.6
64.2
10.6
10.8
11.1
11.2
11.3
11.6
11.9
58.5
60.5
62.5
63.5
64.5
66.5
68.7
64.8
65.3
65.9
66.2
66.5
67.1
67.7
9.8
57.2
59.1
61.0
62.0
63.0
65.0
67.1
68.4
68.9
69.5
69.8
70.1
70.8
71.4
9.1
9.4
55.8
57.6
59.6
60.5
61.5
63.5
65.5
8.5
8.7
8.9
9.0
9.1
9.4
9.6
64.5
66.5
67.6
68.7
70.8
73.1
55.7
56.2
56.5
56.8
57.3
57.9
12.4
12.7
12.8
13.0
13.3
13.6
63.2
65.2
66.3
67.3
69.5
71.6
58.7
59.2
59.5
59.8
60.4
61.0
11.6
11.9
12.0
12.1
12.4
12.7
10.1
10.3
10.4
10.6
10.8
11.1
9.6
9.7
9.8
10.1
10.3
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
18
YORK INTERNATIONAL
FORM 150.64-EG1
IPLV= 13.6
125.0
MODEL: YCAL0055EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
LCWT
(°F)
TONS
42.3
43.8
45.3
46.0
46.8
48.3
49.8
EER
7.8
8.1
8.3
8.4
8.5
8.8
9.0
TONS
41.2
42.6
44.0
44.7
45.5
47.0
48.5
EER
7.2
7.5
7.7
7.8
7.9
8.1
8.3
TONS
39.9
41.3
42.7
43.4
44.2
45.6
47.1
KW
64.8
65.2
65.6
65.8
65.9
66.3
66.7
EER
6.7
6.9
7.1
7.2
7.3
7.5
7.7
TONS
29.0
30.0
31.1
31.6
32.2
33.3
34.4
EER
6.4
6.6
6.8
6.9
7.0
7.2
7.4
TONS
28.0
29.0
30.1
30.6
31.1
32.2
33.3
KW
50.6
50.9
51.2
51.3
51.4
51.7
51.9
EER
5.9
6.0
6.2
6.3
6.4
6.6
6.8
40.0
42.0
44.0
45.0
46.0
48.0
50.0
58.2
58.5
58.8
59.0
59.1
59.5
59.9
61.4
61.8
62.1
62.3
62.5
62.8
63.2
48.0
48.3
48.5
48.6
48.7
49.0
49.2
IPLV= 14.2
MODEL: YCAL0061EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
49.5
51.1
52.9
53.7
54.6
56.4
58.2
EER
7.8
8.0
8.2
8.4
8.5
8.7
8.9
TONS
48.2
49.8
51.5
52.3
53.2
54.9
56.7
EER
7.2
7.4
7.6
7.7
7.8
8.0
8.2
TONS
46.8
48.4
50.0
50.9
51.7
53.4
55.1
KW
77.2
77.8
78.3
78.6
78.9
79.4
80.0
EER
6.7
6.9
7.1
7.2
7.2
7.4
7.6
TONS
45.4
46.9
48.5
49.3
50.2
51.8
53.5
EER
6.2
6.3
6.5
6.6
6.7
6.9
7.0
TONS
34.7
35.9
37.2
37.8
38.5
39.8
41.1
EER
5.9
6.1
6.2
6.3
6.4
6.6
6.8
40.0
42.0
44.0
45.0
46.0
48.0
50.0
69.2
69.7
70.2
70.5
70.7
71.3
71.8
73.1
73.6
74.1
74.4
74.7
75.3
75.8
81.5
82.1
82.7
83.0
83.3
83.9
84.5
63.9
64.3
64.7
64.9
65.1
65.6
66.0
IPLV= 14.5
MODEL: YCAL0065EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
54.3
56.2
58.0
59.0
59.9
61.9
63.9
EER
7.9
8.1
8.3
8.4
8.5
8.7
8.9
TONS
52.8
54.6
56.5
57.4
58.3
60.3
62.2
EER
7.3
7.5
7.6
7.7
7.8
8.0
8.2
TONS
51.3
53.1
54.9
55.8
56.7
58.6
60.5
KW
85.1
85.8
86.5
86.8
87.2
87.9
88.6
EER
6.7
6.9
7.1
7.2
7.2
7.4
7.6
TONS
49.7
51.4
53.2
54.1
55.0
56.8
58.7
EER
6.2
6.3
6.5
6.6
6.7
6.8
7.0
TONS
38.2
39.6
28.9
29.4
29.9
31.0
32.0
EER
5.7
5.9
7.0
7.1
7.2
7.4
7.6
40.0
42.0
44.0
45.0
46.0
48.0
50.0
76.3
76.9
77.5
77.8
78.2
78.8
79.5
80.6
81.2
81.9
82.2
82.5
83.2
83.9
89.9
90.6
91.3
91.7
92.1
92.8
93.5
73.1
73.6
42.9
43.1
43.2
43.4
43.6
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YORK INTERNATIONAL
19
Ratings - R-22 (60Hz - SI Units)
MODEL: YCAL0041EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
KW
35.0
KW
40.0
KW
45.0
KW
50.0
KW
LCWT
(°C)
KW
COP
3.5
3.5
3.6
3.7
3.8
3.9
3.9
KW
COP
3.1
3.1
3.2
3.3
3.4
3.4
3.5
KW
COP
2.7
2.8
2.8
2.9
3.0
3.0
3.1
KW
COP
2.4
2.4
2.5
2.6
2.6
2.7
2.7
KW
COP
2.1
2.1
2.2
2.2
2.3
2.3
2.4
KW
COP
1.8
1.8
1.9
1.9
2.0
2.0
2.1
5.0
6.0
126.9 31.1
130.6 31.3
134.3 31.6
138.1 31.8
142.0 32.1
145.9 32.3
149.9 32.6
122.4 34.3
125.9 34.5
129.6 34.7
133.2 35.0
137.0 35.2
140.8 35.5
144.6 35.8
117.6
37.9
112.5
115.8
119.2
41.9
42.1
42.3
107.1 46.4
101.3 51.5
104.4 51.7
107.6 51.9
121.0 38.1
124.5 38.3
128.1 38.6
131.7 38.8
135.4 39.1
139.1 39.3
110.3
113.6
116.9
46.6
46.9
47.1
7.0
8.0
122.7 42.6
126.1 42.8
129.7 43.1
133.3 43.4
110.9
114.1
117.5
52.1
52.4
52.6
9.0
120.3 47.3
123.8 47.6
127.3 47.8
10.0
11.0
120.9 52.8
MODEL: YCAL0045EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
KW
107.3 55.8
LCWT
(°C)
KW
COP
3.5
3.6
3.6
3.7
3.8
3.8
3.9
KW
KW
COP
3.1
3.1
3.2
3.3
3.4
3.4
3.5
KW
COP
2.7
2.8
2.8
2.9
3.0
3.0
3.1
KW
COP
2.4
2.4
2.5
2.5
2.6
2.7
2.7
KW
KW
50.4
50.6
COP
2.0
2.1
2.2
2.2
2.3
2.3
2.4
KW
COP
1.8
1.8
1.9
1.9
1.9
2.0
2.0
5.0
6.0
138.1 34.2
142.1 34.5
146.1 34.7
150.2 35.0
154.3 35.3
158.5 35.7
162.7 36.0
132.3 37.5
136.2 37.8
140.1 38.1
144.1 38.4
148.2 38.7
152.3 39.0
156.4 39.3
126.4 41.3
130.2 41.6
134.1 41.9
138.0 42.2
142.0 42.5
146.0 42.8
150.0 43.1
120.4 45.6
124.1 45.8
127.9 46.1
131.7 46.4
135.5 46.7
139.4 47.1
143.3 47.4
114.1
117.7
110.7
114.3
117.9
56.0
56.3
56.6
7.0
121.4 50.9
125.0 51.2
128.7 51.5
132.5 51.9
136.4 52.2
8.0
9.0
121.5 56.9
125.2 57.2
128.9 57.5
10.0
11.0
MODEL: YCAL0051EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
LCWT
(°C)
KW
COP
3.5
3.6
3.7
3.8
3.8
3.9
4.0
KW
KW
COP
3.1
3.2
3.2
3.3
3.4
3.5
3.5
KW
COP
2.7
2.8
2.8
2.9
3.0
3.1
3.1
KW
COP
2.4
2.4
2.5
2.5
2.6
2.7
2.7
KW
KW
COP
2.0
2.1
2.2
2.2
2.3
2.3
2.4
KW
KW
COP
1.8
1.8
1.9
1.9
2.0
2.0
2.1
5.0
6.0
159.2 39.9
163.9 40.1
168.6 40.4
173.5 40.7
178.3 41.0
183.3 41.3
188.3 41.6
152.4 43.8
157.0 44.1
161.7 44.3
166.4 44.6
171.2 44.9
176.0 45.2
180.9 45.5
145.7 48.3
150.2 48.5
154.7 48.8
159.3 49.1
164.0 49.4
168.7 49.7
173.4 50.0
138.8 53.2
143.2 53.5
147.5 53.8
152.0 54.1
156.5 54.4
161.1 54.7
165.7 55.0
131.6 58.8
135.8 59.1
140.0 59.4
144.4 59.7
148.7 60.0
153.2 60.3
157.7 60.7
123.9 64.8
127.9 65.2
132.0 65.5
136.2 65.8
140.4 66.2
144.7 66.5
149.0 66.9
7.0
8.0
9.0
10.0
11.0
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
20
YORK INTERNATIONAL
FORM 150.64-EG1
MODEL: YCAL0055EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
KW
35.0
KW
40.0
KW
45.0
KW
50.0
LCWT
(°C)
KW
COP
3.5
3.5
3.6
3.7
3.8
3.9
4.0
KW
COP
3.1
3.1
3.2
3.3
3.4
3.5
3.5
KW
COP
2.7
2.8
2.8
2.9
3.0
3.1
3.1
KW
COP
2.4
2.4
2.5
2.6
2.6
2.7
2.7
KW
COP
2.1
2.1
2.2
2.2
2.3
2.3
2.4
KW
KW
COP
1.8
1.9
1.9
2.0
2.0
2.1
2.2
5.0
6.0
172.2 43.1
177.4 43.4
182.6 43.6
187.9 43.9
193.3 44.2
198.8 44.5
204.4 44.8
166.0 47.5
170.9 47.7
176.0 48.0
181.1 48.3
186.4 48.5
191.7 48.8
197.1 49.1
159.3 52.3
164.1 52.6
169.0 52.9
173.9 53.2
179.0 53.4
184.1 53.7
189.4 54.0
152.2 57.7
156.8 58.0
161.6 58.3
166.3 58.6
171.1 58.9
176.1 59.2
181.1 59.6
144.6 63.6
149.0 63.9
153.6 64.3
158.2 64.6
162.9 64.9
167.7 65.3
172.5 65.6
102.4 49.2
105.7 49.4
109.0 49.6
7.0
8.0
112.4
115.9
119.4
49.8
50.1
50.3
9.0
10.0
11.0
122.9 50.5
MODEL: YCAL0061EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
KW
LCWT
(°C)
KW
COP
3.5
3.6
3.6
3.7
3.8
3.9
4.0
KW
KW
COP
3.1
3.1
3.2
3.3
3.4
3.4
3.5
KW
COP
2.7
2.8
2.8
2.9
3.0
3.0
3.1
KW
COP
2.4
2.4
2.5
2.5
2.6
2.7
2.7
KW
KW
COP
2.1
2.1
2.2
2.2
2.3
2.3
2.4
KW
COP
1.8
1.8
1.9
1.9
2.0
2.1
2.1
5.0
6.0
201.3 51.1
207.2 51.5
213.3 51.9
219.5 52.3
225.7 52.7
232.1 53.1
238.6 53.5
193.8 56.4
199.6 56.8
205.4 57.2
186.0 62.2
191.6 62.6
197.3 63.1
203.0 63.5
208.9 63.9
214.9 64.4
221.0 64.8
177.8 68.7
183.2 69.2
188.7 69.6
194.2 70.1
199.9 70.5
205.7 71.0
169.3 75.8
174.4 76.3
179.7 76.8
185.1 77.3
190.5 77.8
196.0 78.3
201.7 78.8
160.3 83.6
165.2 84.1
170.2 84.7
175.4 85.2
143.0 63.5
147.3 63.9
151.7 64.2
7.0
8.0
211.4
57.6
9.0
217.5 58.0
223.7 58.4
230.0 58.9
10.0
11.0
211.6
71.5
MODEL: YCAL0065EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
LCWT
(°C)
KW
COP
3.5
3.6
3.6
3.7
3.8
3.9
4.0
KW
KW
COP
3.1
3.2
3.2
3.3
3.4
3.4
3.5
KW
COP
2.7
2.8
2.8
2.9
3.0
3.0
3.1
KW
COP
2.4
2.4
2.5
2.5
2.6
2.7
2.7
KW
KW
COP
2.1
2.1
2.2
2.2
2.3
2.3
2.4
KW
KW
COP
1.8
1.8
1.9
1.9
2.0
2.0
2.1
5.0
6.0
221.3 56.6
227.7 57.1
234.3 57.6
241.1 58.1
247.9 58.6
254.9 59.1
262.1 59.6
213.0 62.3
219.3 62.8
225.7 63.3
232.2 63.8
238.9 64.3
245.7 64.9
252.6 65.4
204.4 68.7
210.5 69.2
216.7 69.7
223.0 70.3
229.4 70.8
236.0 71.4
242.7 71.9
195.3 75.7
201.2 76.3
207.2 76.9
213.3 77.4
219.5 78.0
225.8 78.6
232.3 79.2
185.7 83.6
191.3 84.2
197.1 84.8
203.0 85.4
209.0 86.0
215.1 86.7
221.3 87.3
175.5 92.3
180.9 92.9
186.5 93.6
192.1 94.2
197.9 94.9
162.8 73.4
167.7 74.0
7.0
8.0
9.0
10.0
11.0
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YORK INTERNATIONAL
21
Ratings - R-22 (50Hz - English Units)
IPLV= 16.2
100.0
MODEL: YCAL0041EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
30.4
31.4
32.4
33.0
33.5
34.5
35.6
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
32.2
32.3
32.5
32.6
32.7
33.0
33.2
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
23.6
23.8
24.0
24.1
24.2
24.5
24.7
13.6
13.9
14.3
14.4
14.6
15.0
15.3
29.8
30.8
31.8
32.3
32.8
33.8
34.9
25.1
25.3
25.5
25.6
25.7
25.9
26.2
12.6
12.9
13.3
13.4
13.6
13.9
14.2
29.1
30.1
31.1
31.6
32.1
33.1
34.2
26.7
26.9
27.1
27.2
27.3
27.5
27.7
11.7
12.0
12.3
12.5
12.6
12.9
13.2
28.5
29.5
30.4
30.9
31.4
32.5
33.5
28.4
28.6
28.8
28.9
29.0
29.2
29.4
10.8
11.1
11.4
11.6
11.7
12.0
12.3
27.9
28.8
29.8
30.2
30.7
31.7
32.8
30.2
30.4
30.6
30.7
30.8
31.0
31.2
10.0
10.3
10.6
10.7
10.8
11.1
11.4
27.2
28.1
29.1
29.5
30.0
31.0
32.0
9.2
9.5
9.7
9.9
10.0
10.3
10.5
IPLV= 16.1
100.0
MODEL: YCAL0045EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
32.9
34.0
35.1
35.7
36.2
37.4
38.5
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
35.0
35.3
35.5
35.6
35.7
36.0
36.3
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
25.9
26.2
26.4
26.5
26.7
26.9
27.2
13.6
13.9
14.2
14.4
14.5
14.9
15.2
32.2
33.3
34.4
34.9
35.5
36.6
37.8
27.5
27.8
28.0
28.1
28.2
28.5
28.8
12.6
12.9
13.2
13.4
13.5
13.8
14.2
31.5
32.6
33.7
34.2
34.7
35.9
37.0
29.2
29.4
29.7
29.8
29.9
30.2
30.5
11.7
12.0
12.3
12.4
12.6
12.9
13.2
30.8
31.8
32.9
33.4
34.0
35.1
36.2
31.0
31.2
31.5
31.6
31.7
32.0
32.3
10.8
11.1
11.4
11.5
11.7
11.9
12.2
30.0
31.1
32.1
32.6
33.2
34.2
35.3
32.9
33.2
33.4
33.5
33.7
33.9
34.2
10.0
10.2
10.5
10.6
10.8
11.1
11.3
29.2
30.2
31.3
31.8
32.3
33.4
34.4
9.2
9.4
9.7
9.8
10.0
10.2
10.5
IPLV= 15.7
100.0
MODEL: YCAL0051EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
37.9
39.1
40.4
41.0
41.7
43.0
44.4
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
41.3
41.5
41.7
41.9
42.0
42.2
42.5
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
30.8
31.0
31.3
31.4
31.5
31.8
32.1
13.3
13.7
14.0
14.2
14.4
14.7
15.1
37.1
38.3
39.6
40.2
40.9
42.2
43.5
32.6
32.9
33.1
33.2
33.4
33.6
33.9
12.4
12.7
13.1
13.2
13.4
13.7
14.1
36.3
37.5
38.8
39.4
40.0
41.3
42.6
34.6
34.8
35.1
35.2
35.3
35.6
35.8
11.5
11.8
12.2
12.3
12.5
12.8
13.1
35.5
36.7
37.9
38.5
39.2
40.4
41.7
36.7
36.9
37.1
37.3
37.4
37.6
37.9
10.7
11.0
11.3
11.4
11.6
11.9
12.2
34.6
35.8
37.0
37.6
38.3
39.5
40.8
38.9
39.1
39.4
39.5
39.6
39.9
40.1
9.9
33.8
34.9
36.1
36.7
37.3
38.5
39.8
9.1
9.4
10.1
10.4
10.6
10.7
11.0
11.3
9.6
9.8
9.9
10.2
10.4
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
22
YORK INTERNATIONAL
FORM 150.64-EG1
IPLV= 16.2
125.0
MODEL: YCAL0041EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
LCWT
(°F)
TONS
40.0
42.0
44.0
45.0
46.0
48.0
50.0
EER
8.5
8.7
9.0
9.1
9.2
9.5
9.7
TONS
25.7
26.6
27.5
28.0
28.5
29.4
30.4
EER
7.8
8.0
8.2
8.4
8.5
8.7
8.9
TONS
25.0
25.8
26.7
27.2
27.6
28.6
29.5
KW
39.0
39.2
39.4
39.5
39.6
39.8
40.0
EER
7.1
7.3
7.5
7.6
7.8
8.0
8.2
TONS
24.1
25.0
25.9
26.3
26.8
27.7
28.6
EER
6.5
6.7
6.9
7.0
7.1
7.3
7.5
TONS
23.2
24.1
24.9
25.4
25.8
26.7
27.6
KW
44.4
44.6
44.8
44.9
45.0
45.2
45.4
EER
5.8
6.0
6.2
6.3
6.4
6.6
6.8
26.5
27.4
28.3
28.8
29.3
30.2
31.2
34.3
34.5
34.7
34.8
34.9
35.1
35.3
36.5
36.7
36.9
37.0
37.1
37.3
37.5
41.6
41.8
42.0
42.1
42.2
42.4
42.6
IPLV= 16.1
MODEL: YCAL0045EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
40.0
42.0
44.0
45.0
46.0
48.0
50.0
EER
8.4
8.7
8.9
9.0
9.2
9.4
9.6
TONS
27.6
28.5
29.5
30.0
30.5
31.5
32.6
EER
7.7
7.9
8.2
8.3
8.4
8.6
8.9
TONS
26.6
27.6
28.6
29.1
29.6
30.6
31.6
KW
42.2
42.5
42.7
42.8
42.9
43.2
43.4
EER
7.0
7.2
7.5
7.6
7.7
7.9
8.1
TONS
25.7
26.6
27.6
28.1
28.5
29.5
30.5
EER
6.4
6.6
6.8
6.9
7.0
7.2
7.4
TONS
24.7
25.6
26.5
27.0
27.5
28.4
29.4
EER
5.8
6.0
6.2
6.3
6.4
6.6
6.7
28.4
29.4
30.4
30.9
31.4
32.5
33.5
37.3
37.5
37.7
37.8
38.0
38.2
38.5
39.7
39.9
40.1
40.2
40.4
40.6
40.9
45.0
45.2
45.4
45.6
45.7
45.9
46.2
47.9
48.2
48.4
48.5
48.6
48.9
49.1
IPLV= 15.7
MODEL: YCAL0051EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
40.0
42.0
44.0
45.0
46.0
48.0
50.0
EER
8.4
8.6
8.9
9.0
9.1
9.4
9.6
TONS
31.9
33.0
34.2
34.7
35.3
36.5
37.7
EER
7.7
7.9
8.2
8.3
8.4
8.6
8.9
TONS
30.9
32.0
33.1
33.7
34.2
35.4
36.6
KW
49.3
49.5
49.8
49.9
50.0
50.3
50.5
EER
7.1
7.3
7.5
7.6
7.7
7.9
8.2
TONS
29.8
30.9
32.0
32.6
33.1
34.3
35.4
EER
6.5
6.7
6.9
7.0
7.1
7.3
7.5
TONS
28.7
29.8
30.9
31.4
32.0
33.1
34.2
EER
5.9
6.1
6.3
6.4
6.5
6.6
6.8
32.8
34.0
35.1
35.7
36.3
37.5
38.8
43.8
44.0
44.3
44.4
44.5
44.7
45.0
46.4
46.7
46.9
47.0
47.2
47.4
47.7
52.3
52.5
52.8
52.9
53.0
53.3
53.6
55.4
55.7
56.0
56.1
56.2
56.5
56.8
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YORK INTERNATIONAL
23
Ratings - R-22 (50Hz - English Units) - Cont.
IPLV= 15.0
100.0
MODEL: YCAL0055EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
41.2
42.6
44.0
44.7
45.4
46.9
48.4
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
44.9
45.1
45.4
45.5
45.6
45.8
46.1
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
33.8
34.0
34.3
34.4
34.5
34.7
35.0
13.1
13.5
13.8
14.0
14.2
14.6
14.9
40.4
41.7
43.1
43.8
44.5
46.0
47.5
35.7
36.0
36.2
36.3
36.4
36.7
36.9
12.2
12.6
12.9
13.1
13.3
13.6
14.0
39.6
40.9
42.3
43.0
43.7
45.1
46.5
37.8
38.0
38.3
38.4
38.5
38.8
39.0
11.4
11.7
12.0
12.2
12.4
12.7
13.0
38.7
40.0
41.4
42.1
42.7
44.1
45.6
40.0
40.3
40.5
40.6
40.7
40.9
41.2
10.6
10.9
11.2
11.3
11.5
11.8
12.1
37.8
39.1
40.4
41.1
41.8
43.1
44.5
42.4
42.6
42.8
43.0
43.1
43.3
43.6
9.8
36.9
38.2
39.5
40.1
40.8
42.1
43.5
9.1
9.4
10.1
10.4
10.5
10.7
11.0
11.3
9.6
9.8
9.9
10.2
10.4
IPLV= 15.7
100.0
MODEL: YCAL0061EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
48.0
49.6
51.2
52.0
52.9
54.6
56.3
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
53.3
53.6
54.0
54.2
54.3
54.7
55.1
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
40.0
40.3
40.6
40.7
40.9
41.2
41.6
13.1
13.5
13.8
14.0
14.2
14.5
14.9
47.0
48.6
50.2
51.0
51.8
53.5
55.2
42.3
42.6
42.9
43.1
43.3
43.6
43.9
12.2
12.5
12.9
13.0
13.2
13.5
13.8
46.0
47.6
49.1
49.9
50.8
52.4
54.1
44.8
45.1
45.5
45.6
45.8
46.1
46.5
11.3
11.6
12.0
12.1
12.3
12.6
12.9
45.0
46.6
48.1
48.9
49.7
51.3
52.9
47.5
47.8
48.1
48.3
48.5
48.8
49.1
10.5
10.8
11.1
11.2
11.4
11.7
12.0
44.0
45.5
47.0
47.8
48.6
50.2
51.8
50.3
50.6
51.0
51.1
51.3
51.6
52.0
9.8
43.0
44.4
45.9
46.7
47.4
49.0
50.6
9.0
9.3
10.0
10.3
10.4
10.6
10.8
11.1
9.5
9.7
9.8
10.0
10.3
IPLV= 15.8
100.0
MODEL: YCAL0065EC
AIR TEMPERATURE ON - CONDENSER (°F)
75.0
KW
80.0
KW
85.0
KW
90.0
KW
95.0
KW
LCWT
(°F)
TONS
52.5
54.2
55.9
56.8
57.7
59.6
61.4
EER TONS
EER TONS
EER TONS
EER TONS
EER TONS
KW
58.7
59.1
59.6
59.8
60.0
60.4
60.9
EER
40.0
42.0
44.0
45.0
46.0
48.0
50.0
44.2
44.5
44.9
45.1
45.3
45.7
46.1
13.1
13.4
13.8
13.9
14.1
14.4
14.7
51.4
53.1
54.8
55.7
56.6
58.4
60.2
46.7
47.1
47.5
47.7
47.9
48.3
48.7
12.2
12.5
12.8
13.0
13.1
13.4
13.7
50.3
52.0
53.7
54.6
55.4
57.2
59.0
49.4
49.8
50.2
50.4
50.6
51.0
51.5
11.3
11.6
11.9
12.1
12.2
12.5
12.8
49.2
50.9
52.5
53.4
54.2
56.0
57.7
52.3
52.7
53.1
53.3
53.5
54.0
54.4
10.5
10.8
11.1
11.2
11.3
11.6
11.9
48.1
49.7
51.3
52.2
53.0
54.7
56.5
55.4
55.8
56.2
56.4
56.7
57.1
57.5
9.7
46.9
48.5
50.1
50.9
51.7
53.4
55.1
9.0
9.2
10.0
10.2
10.4
10.5
10.8
11.0
9.5
9.6
9.7
10.0
10.2
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
24
YORK INTERNATIONAL
FORM 150.64-EG1
IPLV= 15.0
125.0
MODEL: YCAL0055EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
LCWT
(°F)
TONS
40.0
42.0
44.0
45.0
46.0
48.0
50.0
EER
8.4
8.6
8.9
9.0
9.1
9.4
9.7
TONS
35.0
36.2
37.4
38.1
38.7
40.0
41.3
EER
7.7
8.0
8.2
8.3
8.4
8.7
8.9
TONS
33.9
35.1
36.3
36.9
37.6
38.8
40.1
KW
53.3
53.6
53.8
54.0
54.1
54.4
54.7
EER
7.1
7.3
7.6
7.7
7.8
8.0
8.2
TONS
32.8
34.0
35.2
35.8
36.4
37.6
38.9
EER
6.5
6.7
6.9
7.0
7.1
7.3
7.6
TONS
31.7
32.8
34.0
34.6
35.2
36.4
37.6
KW
59.7
60.0
60.3
60.5
60.6
60.9
61.2
EER
6.0
6.2
6.4
6.4
6.5
6.7
6.9
36.0
37.2
38.5
39.1
39.8
41.1
42.4
47.5
47.8
48.0
48.2
48.3
48.5
48.8
50.3
50.6
50.9
51.0
51.1
51.4
51.7
56.4
56.7
57.0
57.1
57.3
57.6
57.9
IPLV= 15.7
MODEL: YCAL0061EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
40.0
42.0
44.0
45.0
46.0
48.0
50.0
EER
8.3
8.6
8.8
8.9
9.0
9.3
9.5
TONS
40.7
42.1
43.6
44.3
45.0
46.5
48.0
EER
7.7
7.9
8.1
8.2
8.3
8.5
8.8
TONS
39.5
40.9
42.3
43.0
43.7
45.1
46.6
KW
63.5
63.8
64.3
64.5
64.7
65.1
65.5
EER
7.0
7.2
7.4
7.5
7.6
7.9
8.1
TONS
38.2
39.5
40.9
41.6
42.3
43.7
45.2
EER
6.4
6.6
6.8
6.9
7.0
7.2
7.4
TONS
36.8
38.1
39.5
40.2
40.8
42.2
43.7
EER
5.9
6.1
6.2
6.3
6.4
6.6
6.8
41.9
43.3
44.8
45.5
46.3
47.8
49.3
56.5
56.8
57.2
57.4
57.6
57.9
58.3
59.9
60.3
60.6
60.8
61.0
61.4
61.8
67.3
67.7
68.1
68.3
68.5
68.9
69.4
71.3
71.7
72.2
72.4
72.6
73.0
73.5
IPLV= 15.8
MODEL: YCAL0065EC
AIR TEMPERATURE ON - CONDENSER (°F)
115.0
105
KW
110.0
KW
120.0
KW
125.0
KW
LCWT
(°F)
TONS
40.0
42.0
44.0
45.0
46.0
48.0
50.0
EER
8.3
8.5
8.7
8.8
9.0
9.2
9.4
TONS
44.3
45.8
47.4
48.2
49.0
50.6
52.2
EER
7.6
7.8
8.0
8.1
8.2
8.5
8.7
TONS
42.8
44.3
45.9
46.7
47.4
49.0
50.6
KW
69.9
70.4
70.9
71.2
71.4
72.0
72.5
EER
7.0
7.2
7.4
7.5
7.6
7.8
8.0
TONS
41.3
42.8
44.3
45.1
45.8
47.4
49.0
EER
6.3
6.5
6.7
6.8
6.9
7.1
7.3
TONS
39.6
41.1
42.6
43.4
44.1
35.1
36.3
EER
5.8
5.9
6.1
6.2
6.3
7.2
7.4
45.6
47.2
48.8
49.6
50.4
52.0
53.7
62.2
62.7
63.1
63.3
63.6
64.0
64.5
65.9
66.4
66.9
67.1
67.4
67.9
68.4
74.2
74.7
75.2
75.5
75.7
76.3
76.8
78.7
79.2
79.8
80.1
80.3
54.3
54.6
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YORK INTERNATIONAL
25
Ratings - R-22 (50Hz - SI Units)
MODEL: YCAL0041EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
KW
35.0
KW
40.0
KW
45.0
KW
50.0
KW
LCWT
(°C)
KW
COP
3.9
4.0
4.1
4.2
4.3
4.4
4.5
KW
COP
3.4
3.5
3.6
3.7
3.7
3.8
3.9
KW
COP
3.0
3.0
3.1
3.2
3.3
3.3
3.4
KW
95.2
98.1
COP
2.6
2.6
2.7
2.8
2.8
2.9
3.0
KW
90.4
93.3
96.1
99.1
COP
2.2
2.3
2.3
2.4
2.4
2.5
2.6
KW
85.1
87.8
90.6
93.4
96.3
99.2
COP
1.9
1.9
2.0
2.0
2.1
2.1
2.2
5.0
6.0
107.8 24.3
103.7 27.1
106.9 27.3
99.6
30.3
33.9
34.1
38.1
38.2
38.4
38.6
42.8
43.0
43.2
43.3
43.5
43.7
111.0
114.2
117.5
24.5
24.7
24.9
102.6 30.5
105.7 30.6
108.8 30.8
7.0
110.0
113.2
116.4
119.7
27.5
27.6
27.9
28.1
101.1 34.3
104.1 34.5
107.2 34.6
8.0
9.0
120.8 25.1
124.2 25.3
127.6 25.5
112.0
115.2
118.4
31.0
31.2
31.4
102.0 38.8
105.0 39.0
108.1 39.2
10.0
11.0
110.3
113.5
34.8
35.0
123.1 28.3
102.2 43.9
MODEL: YCAL0045EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
LCWT
(°C)
KW
COP
3.9
4.0
4.1
4.2
4.2
4.3
4.4
KW
KW
29.7
29.9
30.1
COP
3.4
3.5
3.6
3.7
3.7
3.8
3.9
KW
COP
3.0
3.0
3.1
3.2
3.3
3.3
3.4
KW
COP
2.6
2.6
2.7
2.7
2.8
2.9
2.9
KW
96.7
99.7
KW
41.3
41.5
COP
2.2
2.2
2.3
2.4
2.4
2.5
2.5
KW
90.6
93.5
96.5
99.6
KW
46.3
46.5
46.7
46.9
COP
1.8
1.9
1.9
2.0
2.0
2.1
2.2
5.0
6.0
116.7
26.7
112.2
115.6
119.0
107.4 33.1
102.2 36.9
105.4 37.1
108.6 37.3
120.2 26.9
123.7 27.1
127.2 27.3
130.8 27.6
134.4 27.8
138.1 28.1
110.7
114.0
117.3
33.3
33.5
33.7
7.0
102.8 41.7
106.0 41.9
109.2 42.2
8.0
122.4 30.3
125.9 30.6
129.4 30.8
133.0 31.1
111.9
115.2
118.6
37.6
37.8
38.0
9.0
120.7 33.9
124.2 34.2
127.7 34.4
102.7 47.1
105.8 47.3
109.0 47.6
10.0
11.0
112.4
115.7
42.4
42.6
122.0 38.2
MODEL: YCAL0051EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
KW
50.0
LCWT
(°C)
KW
COP
3.9
3.9
4.0
4.1
4.2
4.3
4.4
KW
KW
COP
3.4
3.5
3.5
3.6
3.7
3.8
3.9
KW
COP
2.9
3.0
3.1
3.2
3.2
3.3
3.4
KW
COP
2.5
2.6
2.7
2.7
2.8
2.9
2.9
KW
COP
2.2
2.2
2.3
2.4
2.4
2.5
2.5
KW
KW
COP
1.9
1.9
2.0
2.0
2.1
2.1
2.2
5.0
6.0
134.2 31.6
138.2 31.9
142.3 32.1
146.4 32.3
150.6 32.5
154.9 32.8
159.2 33.0
129.2 35.1
133.1 35.3
137.1 35.5
141.1 35.8
145.2 36.0
149.3 36.2
153.5 36.5
123.9 39.0
127.7 39.2
131.5 39.4
135.4 39.6
139.3 39.9
143.4 40.1
147.4 40.4
118.2
43.4
112.0
115.5
119.1
48.2
48.5
48.7
105.3 53.6
108.7 53.9
121.8 43.6
125.5 43.8
129.3 44.0
133.1 44.3
137.0 44.5
140.9 44.7
7.0
112.1
115.6
119.2
54.1
54.3
54.6
8.0
122.7 48.9
126.4 49.1
130.1 49.4
134.0 49.6
9.0
10.0
11.0
122.8 54.8
126.5 55.1
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
26
YORK INTERNATIONAL
FORM 150.64-EG1
MODEL: YCAL0055EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
KW
35.0
KW
40.0
KW
45.0
KW
50.0
LCWT
(°C)
KW
COP
3.8
3.9
4.0
4.1
4.2
4.3
4.4
KW
COP
3.3
3.4
3.5
3.6
3.7
3.8
3.9
KW
COP
2.9
3.0
3.1
3.2
3.2
3.3
3.4
KW
COP
2.5
2.6
2.7
2.7
2.8
2.9
2.9
KW
COP
2.2
2.3
2.3
2.4
2.4
2.5
2.6
KW
KW
57.8
58.1
COP
1.9
1.9
2.0
2.0
2.1
2.1
2.2
5.0
6.0
146.1 34.7
150.5 34.9
155.0 35.1
159.5 35.3
164.2 35.5
168.9 35.7
173.7 36.0
140.9 38.4
145.1 38.6
149.5 38.8
153.9 39.0
158.3 39.2
162.9 39.4
167.5 39.6
135.3 42.5
139.4 42.7
143.6 42.9
147.9 43.1
152.2 43.3
156.6 43.6
161.1 43.8
129.3 47.1
133.3 47.3
137.4 47.6
141.5 47.8
145.6 48.0
149.9 48.2
154.2 48.5
122.9 52.2
126.7 52.5
130.6 52.7
134.6 53.0
138.6 53.2
142.7 53.4
146.8 53.7
115.9
119.6
7.0
123.3 58.4
127.1 58.7
131.0 58.9
134.9 59.2
138.9 59.5
8.0
9.0
10.0
11.0
MODEL: YCAL0061EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
LCWT
(°C)
KW
COP
3.8
3.9
4.0
4.1
4.1
4.2
4.3
KW
KW
COP
3.3
3.4
3.5
3.6
3.6
3.7
3.8
KW
COP
2.9
3.0
3.0
3.1
3.2
3.3
3.3
KW
COP
2.5
2.6
2.6
2.7
2.8
2.8
2.9
KW
KW
COP
2.2
2.2
2.3
2.3
2.4
2.4
2.5
KW
KW
COP
1.9
1.9
2.0
2.0
2.0
2.1
2.1
5.0
6.0
170.1 41.1
175.2 41.3
180.3 41.6
185.6 41.9
190.9 42.2
196.4 42.5
201.9 42.8
163.9 45.5
168.8 45.8
173.8 46.1
178.9 46.4
184.0 46.7
189.3 47.0
194.7 47.3
157.4 50.5
162.2 50.7
167.0 51.1
171.9 51.4
176.9 51.7
182.0 52.0
187.2 52.3
150.5 56.0
155.1 56.3
159.8 56.7
164.6 57.0
169.4 57.3
174.3 57.6
179.3 58.0
143.0 62.2
147.5 62.5
152.0 62.9
156.6 63.3
161.2 63.6
165.9 64.0
170.7 64.3
134.7 69.0
139.0 69.4
143.3 69.8
147.8 70.2
152.2 70.6
156.7 71.0
161.3 71.4
7.0
8.0
9.0
10.0
11.0
MODEL: YCAL0065EC
AIR TEMPERATURE ON - CONDENSER (°C)
25.0
KW
30.0
35.0
KW
40.0
KW
45.0
50.0
LCWT
(°C)
KW
COP
3.8
3.9
4.0
4.0
4.1
4.2
4.3
KW
KW
COP
3.3
3.4
3.5
3.5
3.6
3.7
3.8
KW
COP
2.9
3.0
3.0
3.1
3.2
3.2
3.3
KW
COP
2.5
2.6
2.6
2.7
2.7
2.8
2.9
KW
KW
COP
2.1
2.2
2.3
2.3
2.4
2.4
2.5
KW
KW
COP
1.8
1.9
1.9
2.0
2.0
2.1
2.1
5.0
6.0
186.0 45.4
191.4 45.7
197.0 46.0
202.7 46.4
208.4 46.8
214.3 47.1
220.3 47.5
179.1 50.2
184.4 50.5
189.8 50.9
195.3 51.3
200.9 51.6
206.6 52.0
212.4 52.4
171.9 55.6
177.0 56.0
182.2 56.4
187.6 56.7
193.0 57.1
198.5 57.5
204.1 58.0
164.0 61.7
169.0 62.1
174.1 62.5
179.3 62.9
184.5 63.3
189.8 63.8
195.2 64.2
155.3 68.5
160.2 69.0
165.1 69.4
170.1 69.9
175.2 70.3
180.3 70.8
185.6 71.3
145.5 76.2
150.2 76.7
155.0 77.2
159.9 77.7
164.8 78.1
169.8 78.6
174.9 79.2
7.0
8.0
9.0
10.0
11.0
NOTES:
1. kW = Compressor Input Power
2. EER = Chiller EER (includes power from compressors, fans, and the control panels 0.8 kW)
3. LCWT = Leaving Chilled Water Temperature
4. Ratings are based upon 2.4 GPM cooler water per ton and 0.0001 fouling factor
5. Rated in accordance with ARI Standard 550/590-98
6. The shaded points are certified in accordance with ARI Standard 550/590-98
YORK INTERNATIONAL
27
Part Load Ratings - R-22 (English Units)
YCAL0041
KW
YCAL0055
KW
% FULL
LOAD
DISPL.
% FULL
LOAD
DISPL.
Ambient
°F
UNIT
EER
Ambient
°F
UNIT
EER
TONS
TONS
100.0
75.0
50.0
25.0
35.0
28.2
20.2
10.6
38.2
24.5
14.0
6.1
95.0
83.3
69.7
55.0
9.6
100.0
73.5
47.0
23.5
47.6
37.2
25.0
13.0
52.8
32.3
17.2
7.8
95.0
81.9
66.5
55.0
9.6
11.2
14.4
17.0
11.4
14.6
16.3
IPLV: 14.0 EER
IPLV: 13.6 EER
YCAL0045
YCAL0061
% FULL
LOAD
DISPL.
% FULL
LOAD
DISPL.
Ambient
UNIT
EER
Ambient
UNIT
EER
TONS
KW
TONS
KW
°F
°F
100.0
73.2
50.0
23.2
37.8
30.3
22.1
10.8
41.8
26.0
15.5
95.0
83.0
70.0
55.0
9.6
100.0
69.3
46.2
23.1
55.7
42.4
30.1
15.7
62.9
35.8
20.4
95.0
80.7
67.5
55.0
9.6
11.5
14.5
17.0
11.9
15.2
17.5
6.2
9.1
IPLV: 14.1 EER
IPLV: 14.3 EER
YCAL0051
YCAL0065
% FULL
LOAD
DISPL.
% FULL
LOAD
DISPL.
Ambient
°F
UNIT
EER
Ambient
°F
UNIT
EER
TONS
KW
TONS
KW
100.0
69.2
48.3
20.9
43.5
33.7
24.4
13.3
48.7
28.3
17.2
7.2
95.0
81.4
68.6
55.0
9.6
100.0
71.5
50.0
21.5
60.0
47.4
34.7
16.2
68.3
40.3
25.3
9.0
95.0
82.4
69.6
55.0
9.6
11.9
14.6
18.7
12.1
14.5
18.2
IPLV: 14.4 EER
IPLV: 14.5 EER
28
YORK INTERNATIONAL
FORM 150.64-EG1
Part Load Ratings - R-22 (SI)
YCAL0041
YCAL055
Comp Ambient
% FULL
LOAD
DISPL.
% FULL
LOAD
DISPL.
Comp Ambient
KW
UNIT
COP
UNIT
COP
KW
KW
°C
KW
°C
100.0
75.0
50.0
25.0
123.0
99.0
71.2
37.4
38.2
24.5
14.0
35.0
28.5
21.0
12.8
2.8
3.3
4.2
5.0
100.0
73.5
47.0
23.5
167.3
130.8
87.8
52.8
32.3
17.2
35.0
27.7
19.2
12.8
2.8
3.4
4.3
4.8
6.1
45.6
7.8
IPLV: 4.10 COP
IPLV: 4.00 COP
YCAL0045
YCAL0061
% FULL
LOAD
DISPL.
% FULL
LOAD
DISPL.
Comp Ambient
UNIT
COP
Comp Ambient
UNIT
COP
KW
KW
KW
°C
KW
°C
100.0
73.2
50.0
23.2
133.1
106.5
77.6
41.8
26.0
15.5
35.0
28.3
21.1
12.8
2.8
3.4
4.2
5.0
100.0
69.3
46.2
23.1
195.8
149.0
106.0
55.3
62.9
35.8
20.4
35.0
27.0
19.7
12.8
2.8
3.5
4.5
5.1
37.9
6.2
9.1
IPLV: 4.12 COP
IPLV: 4.18 COP
YCAL0051
YCAL0065
% FULL
LOAD
DISPL.
% FULL
LOAD
DISPL.
Comp Ambient
UNIT
COP
Comp Ambient
UNIT
SCOP
KW
KW
KW
°C
KW
°C
100.0
69.2
48.3
20.9
153.1
118.5
85.7
48.7
28.3
17.2
35.0
27.5
20.3
12.8
2.8
3.5
4.3
5.5
100.0
71.5
50.0
21.5
211.1
166.6
121.9
56.9
68.3
40.3
25.3
35.0
28.0
20.9
12.8
2.8
3.6
4.3
5.3
46.8
7.2
9.0
IPLV: 4.23 COP
IPLV: 4.24 COP
YORK INTERNATIONAL
29
Physical Data
60Hz
Dimension
General Unit Data
Nominal Compressor Capacity
Refrigerant
Charge,
Operating,
R-22 (lbs)
Oil Charge,
gallons
Shipping
Weight
Operating
Weight
Circuit 1
Ciruict 2
Num-
YCAL
Model
No.
Nomi-
nal
Tons,
R-22
ber of
Refrig-
erant
Length Width Height
Alumi-
num
Fin
Alumi-
num
Fin
Copper
Fin
Coils,
lbs
Copper
Fin
Coils,
lbs
Com- Com- Com- Com- Com- Com-
pres- pres- pres- pres- pres- pres-
sor 1 sor 2 sor 3 sor 4 sor 5 sor 6
Circuits
ckt1/ckt2
ckt1/ckt2
Coils,
lbs
Coils,
lbs
144.8 90.6
144.8 90.6
144.8 90.6
144.8 90.6
144.8 90.6
153.6 90.6
47.8
47.8
47.8
62.6
62.6
62.6
34.9
38.0
43.4
47.4
56.0
60.1
2
2
2
2
2
2
35/35
40/35
40/45
50/50
55/55
60/55
1.7/1.7
1.7/1.7
1.7/2.2
2.2/2.2
2.3/2.2
2.3/2.2
2942 3300 2967 3325
2968 3326 3001 3359
3448 3985 3480 4017
3558 4035 3595 4073
3863 4436 3908 4481
4097 4703 4142 4748
10
12
12
15
20
20
10
12
12
13
15
20
-
-
-
-
-
-
10
10
13
13
15
15
10
10
15
15
15
15
-
-
-
-
-
-
0041
0045
0051
0055
0061
0065
50Hz
Dimension
General Unit Data
Nominal Compressor Capacity
Num-
Refrigerant
ber of
Refrig-
erant
Charge,
Operating,
R-22 (kg)
Oil Charge,
liters
Operating
Weight
Shipping Weight
Circuit 1
Circuit 2
YCAL
Model
No.
Nomi-
nal
KW,
R-22
Circuits
Length Width Height
Alumi- Cop- Alumi- Cop- Com- Com- Com- Com- Com- Com-
ckt1/ckt2 num Fin per Fin num Fin per Fin pres- pres- pres- pres- pres- pres-
Coils, lb Coils, lb Coils, lb Coils, lb sor 1 sor 2 sor 3 sor 4 sor 5 sor 6
ckt1/ckt2
145.8 91.20 47.75 29.6
145.8 91.20 47.75 32.3
145.8 91.20 47.75 37.3
145.8 91.20 62.73 40.2
145.8 91.20 62.73 47.6
154.6 91.20 62.73 50.9
2.0
2.0
2.0
2.0
2.0
2.0
35.0 / 35.0
40.0 / 35.0
40.0 / 45.0
50.0 / 50.0
55.0 / 55.0
60.0 / 55.0
1.7 / 1.7
1.7 / 1.7
1.7 / 2.2
2.2 / 2.2
2.3 / 2.2
2.3 / 2.2
2942.0 3300.0 2967.0 3325.0 8.3
2968.0 3326.0 3001.0 3359.0 10.0
3448.0 3985.0 3480.0 4017.0 10.0
3558.0 4035.0 3595.0 4073.0 12.5
3863.0 4436.0 3908.0 4481.0 16.7
4097.0 4703.0 4142.0 4748.0 16.7
8.3
-
-
-
-
-
-
8.3
8.3
8.3
8.3
-
-
-
-
-
-
0041
0045
0051
0055
0061
0065
10.0
10.0
10.8
12.5
16.7
10.8
10.8
12.5
12.5
12.5
12.5
12.5
12.5
30
YORK INTERNATIONAL
FORM 150.64-EG1
60Hz
Condenser
Condenser Fans, Low Sound
Number of
Condenser Fans, Ultra Quiet
Evaporator
Maxi-
mum
Refrig-
erant
Side
Nomi-
Maxi-
mum
Mini- Maxi-
mum mum
Number of
Rows
Number of
Fans
nal
Water
Con-
nec-
Fans
Fins
per
Inch
Fan
Power
hp/fan
Total
Chiller
CFM
Total Water Water
Chiller Volume, Side
CFM gallons Pres-
sure,
Chiller Chiller
Water Water
Flow Flow
Rate, Rate,
gpm gpm
Total Face
Area ft2
Fan
RPM
Fan
RPM
Fan hp
Pres-
sure,
PSIG
tions
Size,
inches
Ckt. 1/Ckt. 2
Ckt. 1/Ckt. 2
ckt1/ckt2
PSIG
87.0
87.0
2/2
2/2
3/3
2/2
3/2
3/3
17
17
17
17
17
13
2/2
2/2
2/2
2/2
2/2
2/2
2
2
2
2
2
2
1140 47400
1140 47400
1140 47400
1140 52000
1140 52000
1140 52000
2/2
2/2
2/2
2/2
2/2
2/2
2
2
2
2
2
2
838 47400 2.7
838 47400 3.5
838 47400 3.5
838 52000 4.1
838 52000 4.9
838 52000 4.9
300
300
300
300
300
300
450
450
450
450
450
450
40
40
40
60
60
60
200
200
200
300
300
300
3
3
3
3
3
3
87.0
116.0
116.0
128.0
50Hz
Condenser
Condenser Fans, Low Sound
Fan
Condenser Fans, Ultra Quiet
Evaporator
Maxi-
mum
Refrig-
erant
Side
Maxi-
mum
Mini- Maxi-
mum mum
Chiller Chiller
Water Water
Flow Flow
Rate, Rate,
gpm gpm
Number of
Rows
Number of
Power
kw/fan
Number of Fans
Fans
Total
Face
Area
m2
Nominal
Water Con-
nections
Total
Chiller
fpm
Fan
Power
kw/fan
Total Water Water
Chiller Volume, Side
CFM gallons Pres-
sure,
Fins
per cm
Fan
RPM
Fan
RPM
Pres-
sure,
psig
Size, inches
Ckt. 1/Ckt. 2
Ckt. 1/Ckt. 2
ckt1/ckt2
psig
87.0
87.0
2.0 / 2.0
2.0 / 2.0
3.0 / 3.0
2.0 / 2.0
3.0 / 2.0
3.0 / 3.0
17.0
17.0
17.0
17.0
17.0
13.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
1.2
1.2
1.2
1.2
1.2
1.2
950.0 39500.0
950.0 39500.0
950.0 39500.0
950.0 43333.3
950.0 43333.3
950.0 43333.3
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
2.0 / 2.0
1.2 698.3 39500.0 2.7 300.0 450.0 40.0 200.0
1.2 698.3 39500.0 3.5 300.0 450.0 40.0 200.0
1.2 698.3 39500.0 3.5 300.0 450.0 40.0 200.0
1.2 698.3 43333.3 4.1 300.0 450.0 60.0 300.0
1.2 698.3 43333.3 4.9 300.0 450.0 60.0 300.0
1.2 698.3 43333.3 4.9 300.0 450.0 60.0 300.0
3.0
3.0
3.0
3.0
3.0
3.0
87.0
116.0
116.0
128.0
YORK INTERNATIONAL
31
Sound Data
60Hz Line Frequency
Low Noise Fan R-22
63
92
92
91
93
93
94
125
91
91
92
95
95
94
250
92
92
92
95
95
95
500
90
90
91
93
93
93
1000
86
86
87
90
2000
81
81
82
85
4000
77
77
78
81
8000
74
74
75
77
dBA
92
92
92
95
95
95
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
90
90
86
86
82
82
77
77
60Hz Line Frequency
Low Noise Fan with compressor sound blankets installed R-22
63
92
92
91
93
93
94
125
91
91
92
95
95
94
250
92
92
92
95
95
95
500
90
90
90
93
93
93
1000
86
86
86
89
2000
81
81
81
84
4000
77
77
77
80
8000
73
73
73
76
dBA
91
91
91
94
94
94
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
89
89
84
84
80
80
76
75
60Hz Line Frequency
Ultra Quiet Fan R-22
63
94
94
94
96
96
96
125
88
88
90
93
93
92
250
88
88
89
91
91
91
500
87
87
88
90
90
90
1000
83
83
84
87
2000
79
79
80
83
4000
75
75
76
79
8000
74
74
75
77
dBA
88
88
90
92
92
92
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
87
87
84
84
80
81
77
77
60Hz Line Frequency
Ultra Quiet Fan with compressor sound blankets installed R-22
63
94
94
94
96
96
96
125
88
88
90
93
93
92
250
88
88
89
91
91
91
500
85
85
86
89
89
89
1000
82
82
83
85
2000
77
77
78
81
4000
74
74
74
77
8000
73
73
73
76
dBA
87
87
88
91
91
91
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
85
86
81
81
78
78
76
75
32
YORK INTERNATIONAL
FORM 150.64-EG1
50Hz Line Frequency
Low Noise Fan R-22
63
88
88
88
89
90
90
125
87
87
89
92
91
91
250
88
88
89
92
91
91
500
87
87
87
90
90
90
1000
83
83
83
86
2000
78
78
79
82
4000
74
74
75
78
8000
dBA
88
88
89
91
92
92
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
71
71
72
74
74
73
86
86
82
83
78
79
50Hz Line Frequency
Low Noise Fan with compressor sound blankets installed R-22
63
88
88
88
89
90
90
125
87
87
89
92
91
91
250
88
88
89
92
91
91
500
86
86
86
89
89
89
1000
82
82
82
85
2000
77
77
77
80
4000
73
73
73
76
8000
69
69
69
72
dBA
87
87
88
90
90
90
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
85
85
80
80
76
77
72
72
50Hz Line Frequency
Ultra Quiet Fan R-22
63
90
90
90
92
92
92
125
84
84
88
90
90
89
250
84
84
86
88
88
87
500
84
84
85
87
87
87
1000
80
80
81
84
2000
75
75
78
80
4000
72
72
73
76
8000
71
71
72
74
dBA
85
85
87
89
89
89
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
84
84
81
81
77
78
74
73
50Hz Line Frequency
Ultra Quiet Fan with compressor sound blankets installed R-22
63
90
90
90
92
92
92
125
84
84
88
90
90
89
250
84
84
86
88
88
87
500
82
82
82
85
85
85
1000
78
78
79
82
2000
73
73
74
77
4000
70
70
71
74
8000
69
69
69
72
dBA
84
84
84
87
87
87
YCAL0041
YCAL0045
YCAL0051
YCAL0055
YCAL0061
YCAL0065
82
82
77
77
74
74
72
72
YORK INTERNATIONAL
33
Dimensions - YCAL0041 (English)
6 3/4"
3 1/4"
7/8" TYP.
3 15/16"
VIEW B-B
BOTTOM OF PANEL
LIQUID IN
ELECTRICAL ACCESS
PANEL
47 3/4"
46 15/16"
34 5/8"
9 15/16"
15 3/4"
3" VICTAULIC (typ)
LIQUID OUT
12 5/8"
45 1/8"
90 1/4" BASE WIDTH
LEFT END
Aluminum
Center of Gravity (in.)
Copper
Center of Gravity (in.)
YCAL
0041
YCAL
0041
X
Y
X
Y
59.6
43.6
63.6
43.7
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
34
YORK INTERNATIONAL
FORM 150.64-EG1
9/16" DIA MOUNTING HOLES(typ)
1 1/16"
COIL
END
COOLER
END
90 9/16"
END CAP
WIDTH
45 5/16"
1 1/16"
9 13/16"
9 13/16"
ORIGIN
TOP VIEW
21 13/16"
Y
X
C
G
5 5/16"
38"
CONTROL PANEL
B
B
25 3/8"
13 5/8"
TWO LIFTING HOLES
BOTH SIDES
13 15/16"
15 1/16"
X
Z
144 13/16"
C
G
FRONT VIEW
YORK INTERNATIONAL
35
Dimensions - YCAL0045 (English)
6 3/4"
3 1/4"
7/8" TYP.
3 15/16"
VIEW B-B
BOTTOM OF PANEL
LIQUID IN
ELECTRICAL ACCESS
PANEL
47 3/4"
46 15/16"
34 5/8"
9 15/16"
15 3/4"
3" VICTAULIC (typ)
LIQUID OUT
12 5/8"
45 1/8"
90 1/4" BASE WIDTH
LEFT END
Aluminum
Center of Gravity (in.)
Copper
Center of Gravity (in.)
YCAL
0045
YCAL
0045
X
Y
X
Y
59.2
43.5
63.2
43.7
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
36
YORK INTERNATIONAL
FORM 150.64-EG1
9/16" DIA MOUNTING HOLES(typ)
1 1/16"
COIL
END
COOLER
END
90 9/16"
END CAP
WIDTH
45 5/16"
1 1/16"
9 13/16"
9 13/16"
ORIGIN
TOP VIEW
20 1/16"
Y
X
C
G
5 5/16"
38"
CONTROL PANEL
B
B
25 3/8"
13 5/8"
TWO LIFTING HOLES
BOTH SIDES
13 15/16"
15 1/16"
Z
YORK INTERNATIONAL
37
Dimensions - YCAL0051 (English)
6 3/4"
3 1/4"
7/8" TYP.
3 15/16"
VIEW B-B
BOTTOM OF PANEL
LIQUID IN
ELECTRICAL ACCESS
PANEL
47 3/4"
46 15/16"
34 5/8"
9 15/16"
15 3/4"
3" VICTAULIC (typ)
LIQUID OUT
12 5/8"
45 1/8"
90 1/4" BASE WIDTH
LEFT END
Aluminum
Center of Gravity (in.)
Copper
Center of Gravity (in.)
YCAL
0051
YCAL
0051
X
Y
X
Y
59.2
42.6
64.3
42.9
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
38
YORK INTERNATIONAL
FORM 150.64-EG1
9/16" DIA MOUNTING HOLES(typ)
1 1/16"
COIL
END
COOLER
END
90 9/16"
END CAP
WIDTH
45 5/16"
1 1/16"
9 13/16"
9 13/16"
ORIGIN
TOP VIEW
20 1/16"
Y
X
C
G
5 5/16"
38"
CONTROL PANEL
B
B
25 3/8"
13 5/8"
TWO LIFTING HOLES
BOTH SIDES
13 15/16"
15 1/16"
X
Z
144 13/16"
C
G
FRONT VIEW
YORK INTERNATIONAL
39
Dimensions - YCAL0055EC - (English)
6 3/4"
3 1/4"
7/8" TYP.
VIEW B-B
3 15/16"
BOTTOM OF PANEL
LIQUID IN
62 5/8"
ELECTRICAL ACCESS
PANEL
61 7/8"
34 11/16"
9 15/16"
15 3/4"
3" VICTAULIC (typ)
LIQUID OUT
12 5/8"
45 1/8"
90 1/4" BASE WIDTH
LEFT END
Aluminum
Center of Gravity (in.)
Copper
Center of Gravity (in.)
YCAL
0055
YCAL
0055
X
Y
X
Y
57.9
43.0
62.5
43.2
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
40
YORK INTERNATIONAL
FORM 150.64-EG1
9/16" DIA MOUNTING HOLES(typ)
1 1/16"
COIL
END
COOLER
END
90 9/16"
END CAP
WIDTH
45 5/16"
1 1/16"
9 13/16"
9 13/16"
ORIGIN
TOP VIEW
18 7/16"
Y
X
C
G
5 3/16"
38"
CONTROL
PANEL
B
B
25 3/8"
28 9/16"
TWO LIFTING HOLES
BOTH SIDES
14"
15 1/16"
X
Z
144 13/16"
C
G
FRONT VIEW
YORK INTERNATIONAL
41
Dimensions - YCAL0061 (English)
6 3/4"
3 1/4"
7/8" TYP.
VIEW B-B
3 15/16"
BOTTOM OF PANEL
LIQUID IN
62 5/8"
ELECTRICAL ACCESS
PANEL
61 7/8"
34 11/16"
9 15/16"
15 3/4"
3" VICTAULIC (typ)
LIQUID OUT
12 5/8"
43 1/8"
90 1/4" BASE WIDTH
LEFT END
Aluminum
Center of Gravity (in.)
Copper
Center of Gravity (in.)
YCAL
0061
YCAL
0061
X
Y
X
Y
56.6
45.2
61.8
45.8
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
42
YORK INTERNATIONAL
FORM 150.64-EG1
9/16" DIA MOUNTING HOLES(typ)
1 1/16"
COIL
END
COOLER
END
90 9/16"
END CAP
WIDTH
43 5/16"
1 1/16"
9 13/16"
9 13/16"
ORIGIN
TOP VIEW
16 11/16"
Y
X
C
G
5 3/16"
38"
CONTROL
PANEL
B
B
25 3/8"
28 9/16"
TWO LIFTING HOLES
BOTH SIDES
14"
15 1/16"
X
Z
144 13/16"
C
G
FRONT VIEW
YORK INTERNATIONAL
43
Dimensions - YCAL0065 (English)
6 3/4"
3 1/4"
7/8" TYP.
VIEW B-B
3 15/16"
BOTTOM OF PANEL
LIQUID IN
62 5/8"
61 7/8"
ELECTRICAL ACCESS
PANEL
34 11/16"
9 15/16"
15 3/4"
3" VICTAULIC (typ)
LIQUID OUT
12 5/8"
43 1/8"
90 1/4" BASE WIDTH
LEFT END
Aluminum
Copper
Center of Gravity (in.)
YCAL
Center of Gravity (in.)
YCAL
0065
X
Y
X
Y
0065
59.7
44.9
65.2
44.9
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reli-
able operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable
airflow patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety
cutouts; however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall
– 6'; rear to wall – 6'; cooler end to wall – 4'0"; coil end to wall - 6'; top – no obstructions allowed; distance between adjacent units – 10'.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
6".
44
YORK INTERNATIONAL
FORM 150.64-EG1
9/16" DIA MOUNTING HOLES(typ)
1 1/16"
COIL
END
COOLER
END
90 9/16"
END CAP
WIDTH
43 5/16"
1 1/16"
ORIGIN
9 13/16"
9 13/16"
TOP VIEW
16 11/16"
Y
X
5 3/16"
C
G
38"
CONTROL
PANEL
B
B
25 3/8"
28 9/16"
TWO LIFTING HOLES
BOTH SIDES
16"
15 1/16"
Z
153 5/8"
X
C
FRONT VIEW
G
YORK INTERNATIONAL
45
Dimensions - YCAL0041 (SI)
171
82
22 TYP.
100
VIEW B-B
BOTTOM OF PANEL
LIQUID IN
ELECTRICAL ACCESS
PANEL
1213
1192
879
252
401
76 VICTAULIC (typ)
LIQUID OUT
321
1146
2292 BASE WIDTH
LEFT END
Aluminum
Copper
Center of Gravity (in.)
Center of Gravity (in.)
YCAL
0041
YCAL
0041
X
Y
X
Y
1513.7
1107.0
1616.1
1111.1
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
46
YORK INTERNATIONAL
FORM 150.64-EG1
14 DIA MOUNTING HOLES(typ)
28
COIL
END
COOLER
END
2301
END CAP
WIDTH
1150
28
249
249
ORIGIN
TOP VIEW
554
Y
X
C
G
135
965
CONTROL PANEL
B
B
645
346
TWO LIFTING HOLES
BOTH SIDES
355
383
Z
3678
X
C
G
FRONT VIEW
YORK INTERNATIONAL
47
Dimensions - YCAL0045 (SI)
171
82
22 TYP.
100
VIEW B-B
BOTTOM OF PANEL
LIQUID IN
ELECTRICAL ACCESS
PANEL
1213
1192
879
252
401
76 VICTAULIC (typ)
LIQUID OUT
321
1146
2292 BASE WIDTH
LEFT END
Aluminum
Copper
Center of Gravity (in.)
Center of Gravity (in.)
YCAL
0045
YCAL
0045
X
Y
X
Y
1503.5
1105.5
1605.9
1109.7
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
48
YORK INTERNATIONAL
FORM 150.64-EG1
14 DIA MOUNTING HOLES(typ)
28
COIL
END
COOLER
END
2301
END CAP
WIDTH
1150
28
249
249
ORIGIN
TOP VIEW
509
Y
X
C
G
135
965
CONTROL PANEL
B
B
645
346
TWO LIFTING HOLES
BOTH SIDES
355
383
Z
3678
X
C
G
FRONT VIEW
YORK INTERNATIONAL
49
Dimensions - YCAL0051 (SI)
171
82
22 TYP.
100
VIEW B-B
BOTTOM OF PANEL
LIQUID IN
ELECTRICAL ACCESS
PANEL
1213
1192
879
252
401
76 VICTAULIC (typ)
LIQUID OUT
321
1146
2292 BASE WIDTH
LEFT END
Aluminum
Copper
Center of Gravity (in.)
Center of Gravity (in.)
YCAL
0051
YCAL
0051
X
Y
X
Y
1504.6
1082.4
1633.0
1090.8
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
50
YORK INTERNATIONAL
FORM 150.64-EG1
14 DIA MOUNTING HOLES(typ)
28
COIL
END
COOLER
END
2301
END CAP
WIDTH
1150
28
249
249
ORIGIN
TOP VIEW
509
Y
X
C
G
135
965
CONTROL PANEL
B
B
645
346
TWO LIFTING HOLES
BOTH SIDES
355
383
Z
YORK INTERNATIONAL
51
Dimensions -YCAL0055 (SI)
171
82
22 TYP.
VIEW B-B
100
BOTTOM OF PANEL
LIQUID IN
1590
ELECTRICAL ACCESS
PANEL
1572
880
252
401
76 VICTAULIC (typ)
LIQUID OUT
321
1146
2292 BASE WIDTH
LEFT END
Aluminum
Copper
Center of Gravity (in.)
Center of Gravity (in.)
YCAL
0055
YCAL
0055
X
Y
X
Y
1470.3
1092.0
1586.9
1098.3
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
52
YORK INTERNATIONAL
FORM 150.64-EG1
14 DIA MOUNTING HOLES(typ)
28
COIL
END
COOLER
END
2301
END CAP
WIDTH
1151
28
249
249
ORIGIN
TOP VIEW
468
Y
X
C
G
131
965
CONTROL
PANEL
B
B
645
726
TWO LIFTING HOLES
BOTH SIDES
356
383
Z
3678
X
C
G
FRONT VIEW
YORK INTERNATIONAL
53
Dimensions - YCAL0061 (SI)
171
82
22 TYP.
VIEW B-B
100
BOTTOM OF PANEL
LIQUID IN
1590
ELECTRICAL ACCESS
PANEL
1572
880
252
401
76 VICTAULIC (typ)
LIQUID OUT
321
1095
2292 BASE WIDTH
LEFT END
Aluminum
Center of Gravity (in.)
Copper
Center of Gravity (in.)
YCAL
0061
YCAL
0061
X
Y
X
Y
1438.0
1147.1
1569.3
1162.9
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
54
YORK INTERNATIONAL
FORM 150.64-EG1
14 DIA MOUNTING HOLES(typ)
28
L2
L1
COIL
END
COOLER
END
2301
END CAP
WIDTH
1100
R2
28
R1
249
249
ORIGIN
TOP VIEW
424
Y
X
C
G
131
965
CONTROL
PANEL
B
B
645
726
TWO LIFTING HOLES
BOTH SIDES
356
383
Z
3678
X
C
G
FRONT VIEW
YORK INTERNATIONAL
55
Dimensions - YCAL0065 (SI)
171
82
22 TYP.
VIEW B-B
100
BOTTOM OF PANEL
LIQUID IN
1590
1572
ELECTRICAL ACCESS
PANEL
880
252
401
76 VICTAULIC (typ)
LIQUID OUT
321
1095
2292 BASE WIDTH
LEFT END
Aluminum
Copper
Center of Gravity (in.)
Center of Gravity (in.)
YCAL
0065
YCAL
0065
X
Y
X
Y
1517.6
1140.3
1655.5
1141.1
NOTE: All dimensions are in mm unless specified otherwise.
NOTE:
Placement on a level surface of free of obstructions (including snow, for winter operation) or air circulation ensures rated performance, reliable
operation, and ease of maintenance. Site restrictions may compromise minimum clearances indicated below, resulting in unpredictable airflow
patterns and possible diminished performance. YORK’s unit controls will optimize operation without nuisance high-pressure safety cutouts;
however, the system designer must consider potential performance degradation. Recommended minimum clearances: front to wall – 2m;
rear to wall – 2m; cooler end to wall – 1.2m; coil end to wall - 2m; top – no obstructions allowed; distance between adjacent units – 3m.
No more than one adjacent wall may be higher than the unit. 1" nominal deflection isolators (not shown) will increase overall unit height by
152mm.
56
YORK INTERNATIONAL
FORM 150.64-EG1
14 DIA MOUNTING HOLES(typ)
28
L2
L1
COIL
END
COOLER
END
2301
END CAP
WIDTH
1100
R2
28
R1
249
249
ORIGIN
TOP VIEW
424
Y
X
C
G
131
965
CONTROL
PANEL
B
B
645
726
TWO LIFTING HOLES
BOTH SIDES
356
383
Z
3678
X
C
G
FRONT VIEW
YORK INTERNATIONAL
57
Isolator Selections
ONE INCH DEFLECTION SPRING ISOLATOR CROSS-REFERENCE
CIP-X-
Illustration shows single spring CIP-B or CIP-C mount.
Mounting may be
EQUIPMENT BASE
operated 1/2" above
Free & Operating
Height.
A
Dowel Pin is 3/8" dia. for
CIP-A & 1/2" thereafter
NOTE-
FERROUS HOUSING
CIP Mounts are not
to be used in seismic
or wind load
SIDE ACCESS INTERNAL
ADJUSTMENT BOLT
Turn clockwise to load
spring and maintain Free
& Operating Height.
TYPE CIP DIMENSIONS (inches)†
applications.
Free
Ht.
Min
Ht.
Size
A
L
T
W
SW HCL HCW MBD SBC
/
61
71
2
4
11
13
2
4
7 1
/
23
31
4
7
7
61/
8
3
3
CIP-B
CIP-C
53
65
4
8
81
/
87
/
/
/
/
51
63
/
/
/
8
/
1
/
4
4
8
2
4
2
FREE &
OPERATING
HEIGHT
16
16
/
77
/
63
/
/
9
/
/
/
8
/
8
4
16
/
4
NON-SKID NEOPRENE
ACOUSTICAL ISOLATION PAD
†Casting dimensions may vary ±1/8"
L
(Bolting to floor is not necessary for
indoor applications)
T
W
SBC
HCL
MAX BOLT
DIA. - MBD
All springs have additional
travel to solid equal to 50%
of the rated deflection.
Slot Width - SW
HCW
BASE PLATE DIMENSIONS
FOR UNITS WITH ALL POINT LOADS LESS THATN 1404 LBS (637 KG)
Weight Range (lbs)
239 to 384 lbs
Weight Range (kg)
108 to 174 kg
174 to 290 kg
290 to 386 kg
386 to 483 kg
483 to 637 kg
Model Number
CIP-B-
Color
Red
384 to 639 lbs
CIP-B-
White
Blue
639 to 851 lbs
CIP-B-
851 to 1064 lbs
1064 to 1404 lbs
CIP-B-
Gray
Black
CIP-B-
FOR UNITS WITH ANY POINT LOAD ABOVE 1404 LBS (637 KG)
Weight Range (lbs)
Up to 851 lbs
Weight Range (kg)
Up to 386 kg
Model Number
CIP-C-
Color
Black
Yellow
Black
851 to 1149 lbs
1149 to 1489 lbs
386 to 521 kg
521 to 675 kg
CIP-C-
CIP-C-
Yellow w/
Red
1489 to 1786 lbs
1786 to 2028 lbs
675 to 910 kg
910 to 920 kg
CIP-C-
CIP-C-
Yellow w/
Green
2028 to 2254 lbs
2254 to 2936 lbs
920 to 1022 kg
1022 to 1332 kg
CIP-C-
CIP-C-
Red w/ Red
Red w/ Green
58
YORK INTERNATIONAL
FORM 150.64-EG1
NEOPRENE ISOLATOR CROSS-REFERENCE
ND-X
"CS" Cap Screw
D
"MBD" Max. Bolt Dia.
Steel Plate - Top &
Bottom Neoprene
covered to prevent
corrosion
BC
L
H
W
T
ENGLISH
T
Size
ND-C
ND-D
ND-E
D
H
L
W
2 5/16
4
BC
4 1/80
5
CS
MBD
2 9/16
3 3/ 8
4 1/ 2
2 3/ 4
2 3/ 4
4 3/ 4
5 1/ 2
6 1/ 4
7 3/ 8
1/ 4
5/16
1/ 4
SI
1/2- 13 x 1”
1/2- 13 x 1”
1/2- 13 x 1”
1/ 2"
1/ 2"
1/ 2"
5 1/80
6 1/80
ND-C
ND-D
ND-E
65.1
85.7
114.3
69.9
69.9
120.7
139.7
158.8
187.3
6.4
7.9
6.4
58.7
101.6
127.3
101.9
127.0
152.7
1/2- 13 x 1”
1/2- 13 x 1”
1/2- 13 x 1”
1/ 2"
1/ 2"
1/ 2"
Weight Range
(lbs)
Weight Range
(kg)
Model Number
Color
Up to 751 lbs
751 to 1651 lbs
1651 to 3226 lbs
Up to 341 kg
341 to 749 kg
749 to 1463 kg
ND-C
ND-D
ND-E
Yellow
Yellow
Yellow
YORK INTERNATIONAL
59
Isolator Details (cont'd)
TWO INCH DEFLECTION, SEISMIC SPRING ISOLATOR CROSS-REFERENCE
SLRS
SLRS-2-C2 has 2 springs.
"D" Tap - 4 Holes unless
otherwise requested
E
Vertical Limit
E
E
Stops-Out of
contact during
normal operation
E
H
MBD -Max
Bolt
Diameter
Rubber
Snubbing
Collar
T
HCL
L
Adjustment
Bolt
HCW
W
Non-Skid Neoprene Pad-
Pad can be removed if
mounts are welded
into position.
Internal
Neoprene
Acoustical
Pad
Lower
Restraining
Nut
Enclosed
Steel
Housing
ENGLISH
SIZE
H
T
D
E
L
HCL
W
HCW MBD
2-C2 8 1/2
3/8
5/8 1 3/8 14 12 1/4 5 1/4 3 1/ 2 5/8"
SI
SIZE
H
T
D
E
L
HCL
W
HCW MBD
2-C2 215.9 9.5
15.9 34.9 355.6 311.2 133.4 88.9 5/8"
*Weight Range
Weight Range
Model Number
Color
(lbs)
(kg)
Up to 358 lbs
Up to 162 kg
162 to 201 kg
201 to 264 kg
264 to 335 kg
335 to 471 kg
471 to 679 kg
679 to 933 kg
933 to 1188 kg
1188 to 1442 kg
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
SLRS-2-C2-
Red
White
358 to 443 lbs
443 to 582 lbs
582 to 783 lbs
783 to 1038 lbs
1038 to 1497 lbs
1497 to 2058 lbs
2058 to 2619 lbs
2619 to 3180 lbs
Black
Blue
Green
Gray
Silver
Gray w/ red
Silver w/ red
60
YORK INTERNATIONAL
FORM 150.64-EG1
INTENTIONALLY LEFT BLANK
YORK INTERNATIONAL
61
Electrical Data
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory
Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system
providing power to the transformer: -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps, -46, add 1.3 amps;
-58, add 1 amps.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not
recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at
ambient temperatures in excess of 95ºF (35ºC) is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440-22.
5. Circuit breakers must be UL listed and CSA certified and maximum size is based on 225% of the rated load amps
for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Otherwise, an
HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is based on 225% of the rated
load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by the
unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per phase
of the wire range specified. Actual wire size and number of wires per phase must be determined based on the
National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.
Table 250-95. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100, and is intended for isolating the
unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not intended
to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code & Local Codes.
62
YORK INTERNATIONAL
FORM 150.64-EG1
OVER CURRENT PROTECTION,
SEE NOTE B
CONTROL
POWER
MCA
UNIT VOLTAGE
NF DISC Sw
NOTE A
UNIT
MIN
MAX
MODELS w/o
CONTROL
TRANS
VOLTAGE
115-1-60/50
15A
10A
15A
30 A / 240V
-17
-28
-40
-46
-50
-58
200-1-60
230-1-60
15A
15A
15A
15A
15A
15A
10A
10A
10A
10A
10A
10A
15A
15A
15A
15A
15A
15A
30 A / 240V
30 A / 240V
30 A / 480V
30 A / 480V
30A / 415V
30 A / 600V
MODELS w/
CONTROL
TRANS
380-1-60
460-1-60
380/415-1-60
575-1-60
A. Minimum #14 AWG, 75°C, Copper Recommended
B. Minimum and Maximum Over Current Protection, Dual Element Fuse or Circuit Breaker
VOLTAGE RANGE
VOLTAGE CODE
UNIT POWER
MIN.
MAX.
220
253
440
506
440
633
-17
-28
-40
-46
-50
-58
200-3-60
230-3-60
180
207
342
414
342
517
380/415-3-60
460-3-60
380/415-3-50
575-3-60
LEGEND
ACR-LINE
C.B.
ACROSS THE LINE START
CIRCUIT BREAKER
DUAL ELEMENT FUSE
DISCONNECT SWITCH
FACTORY MOUNTED CIRCUIT BREAKER
FULL LOAD AMPS
D.E.
DISC SW
FACT MOUNT CB
FLA
HZ
HERTZ
MAX
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MINIMUM
MINIMUM NON FUSED
RATED LOAD AMPS
SINGLE POINT WIRING
MCA
MIN
MIN NF
RLA
S.P. WIRE
UNIT MTD SERV SW UNIT MOUNTED SERVICE (NON-FUSED DISCONNECT
SWITCH)
LRA
LOCKED ROTOR AMPS
YORK INTERNATIONAL
63
Electrical Data - 60Hz
YCAL0041 - YCAL0065
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional).)
FIELD WIRING LUGS6
TERMINAL BLOCK (std)
FIELD WIRING LUGS6
NF DISC. SWITCH (opt)
D.E. FUSE
CKT. BKR.5
MIN N/F
VOLT MCA1 DISC
SW2
MODEL
YCAL
LUGS/
PHASE
LUGS/
REC. MAX4 REC. MAX
LUG WIRE RANGE
LUG WIRE RANGE
PHASE
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
200
230
380
460
575
197
184
107
90
250
250
150
100
100
250
250
150
100
100
250
250
150
150
100
400
400
150
150
100
400
400
200
150
150
400
400
200
150
150
225
200
125
100
80
225
200
125
100
80
225
200
125
100
80
225
200
125
100
80
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
3/0 - 250MCM
0041
0045
0051
0055
0061
0065
71
199
186
108
91
225
200
125
100
80
225
200
125
100
80
225
200
125
100
80
225
200
125
100
80
71
228
212
123
103
81
250
225
150
110
90
250
250
150
110
90
250
225
150
110
90
250
250
150
110
90
3/0 - 250MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
3/0 - 250MCM
250
233
135
113
89
300
250
150
125
100
300
300
175
150
110
350
300
175
150
110
300
300
150
125
100
300
300
175
150
110
350
300
175
150
125
300
250
150
125
100
300
300
175
150
110
350
300
175
150
110
300
300
150
125
100
300
300
175
150
110
350
300
175
150
125
3/0 - 250MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
250MCM - 500MCM
250MCM - 500MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
250MCM - 500MCM
250MCM - 500MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
274
255
148
125
98
292
272
158
132
104
See Notes on page 100.
64
YORK INTERNATIONAL
FORM 150.64-EG1
YCAL0041 - YCAL0065
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional).)
SYSTEM #1 COMPRESSOR & FAN
COMPR. #1 COMPR. #2
SYSTEM #2 COMPRESSOR & FAN
COMPR. #1 COMPR. #2
FIELD WIRING LUGS6
CIRCUIT BREAKER (opt)
FANS
FANS
LUGS/ PHASE
LUG WIRE RANGE
RLA
LRA
RLA
LRA
QTY FLA(EA) RLA
LRA
RLA
LRA
QTY FLA(EA)
1
1
1
1
1
1
1
1
1
1
2
2
1
1
1
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
3/0 - 250MCM
39.1
36.2
20.9
17.2
13.8
40.0
37.0
21.3
17.6
14.1
40.0
37.0
21.3
17.6
14.1
53.8
49.8
28.7
23.7
19.0
68.3
63.3
36.5
30.1
24.1
68.3
63.3
36.5
30.1
24.1
250
250
155
125
100
250
250
155
125
100
350
350
195
167
125
374
374
235
187
150
505
505
280
225
180
505
505
280
225
180
39.1
36.2
20.9
17.2
13.8
40.0
37.0
21.3
17.6
14.1
40.0
37.0
21.3
17.6
14.1
49.4
45.8
26.4
21.8
17.4
53.8
49.8
28.7
23.7
19.0
68.3
63.3
36.5
30.1
24.1
250
250
155
125
100
250
250
155
125
100
350
350
195
167
125
316
316
199
158
126
425
425
239
198
148
505
505
280
225
180
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
7.6
7.4
4.5
4
39.1
36.2
20.9
17.2
13.8
39.1
36.2
20.9
17.2
13.8
49.4
45.8
26.4
21.8
17.4
49.4
45.8
26.4
21.8
17.4
53.8
49.8
28.7
23.7
19.0
53.8
49.8
28.7
23.7
19.0
250
250
155
125
100
250
250
155
125
100
316
316
199
158
126
316
316
199
158
126
425
425
239
198
148
425
425
239
198
148
39.1
36.2
20.9
17.2
13.8
39.1
36.2
20.9
17.2
13.8
53.8
49.8
28.7
23.7
19.0
53.8
49.8
28.7
23.7
19.0
53.8
49.8
28.7
23.7
19.0
53.8
49.8
28.7
23.7
19.0
250
250
155
125
100
250
250
155
125
100
374
374
235
187
150
374
374
235
187
150
425
425
239
198
148
425
425
239
198
148
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
3/0 - 250MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
3/0 - 250MCM
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
3/0 - 250MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
250MCM - 500MCM
250MCM - 500MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
250MCM - 500MCM
250MCM - 500MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
2.9
7.6
7.4
4.5
4
2.9
2.9
YORK INTERNATIONAL
65
Electrical Data - 50Hz
YCAL0041 - YCAL0065
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional).)
FIELD WIRING LUGS6
FIELD WIRING LUGS6
NF DISC. SWITCH (opt)
D.E. FUSE
CKT. BKR.5
MIN
MCA1 N/F DISC
SW2
TERMINAL BLOCK (std)
MODEL
YCAL
VOLT
LUGS/
PHASE
LUGS/
PHASE
REC. MAX4 REC. MAX
LUG WIRE RANGE
LUG WIRE RANGE
380/415
380/415
380/415
380/415
380/415
380/415
90
91
100
100
150
150
150
150
100
100
110
125
150
150
100
100
110
125
150
150
100
100
110
125
150
150
100
100
110
125
150
150
1
1
1
1
1
1
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
6awg - 500MCM
1
1
1
1
1
1
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
0041
0045
0051
0055
0061
0065
103
113
124
132
66
YORK INTERNATIONAL
FORM 150.64-EG1
YCAL0041 - YCAL0065
SINGLE POINT FIELD SUPPLIED POWER WIRING (See Fig. 2)
(One Field Provided Power Supply to the chiller. Field connections to Factory Provided Power Terminal Block (standard), Non-Fused Discon-
nect Switch (optional) or Circuit Breaker (optional).)
FIELD WIRING LUGS6
SYSTEM #1 COMPRESSOR & FAN
COMPR. #1 COMPR. #2 FANS
SYSTEM #2 COMPRESSOR & FAN
COMPR. #1 COMPR. #2 FANS
CIRCUIT BREAKER (opt)
LUGS/
PHASE
FLA
(EA)
FLA
(EA)
LUG WIRE RANGE
RLA
LRA
RLA
LRA
QTY
RLA
LRA
RLA
LRA
QTY
1
1
1
1
1
1
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
6awg - 350MCM
17.2
17.6
17.6
23.7
30.1
30.1
125
125
158
187
225
225
17.2
17.6
17.6
21.8
23.7
30.1
125
125
158
127
198
225
2
2
2
2
2
2
4
4
4
4
4
4
17.2
17.2
21.8
21.8
23.7
23.7
125
125
127
127
167
198
17.2
17.2
23.7
23.7
23.7
23.7
125
125
187
187
167
198
2
2
2
2
2
2
4
4
4
4
4
4
YORK INTERNATIONAL
67
FIG. 1 – STANDARD POWER SUPPLY WIRING – (YCAL 0014 - 0080)
Power Wiring
68
YORK INTERNATIONAL
FORM 150.64-EG1
)
YORK INTERNATIONAL
69
70
YORK INTERNATIONAL
FORM 150.64-EG1
Control Wiring
FLOW SW
REMOTE START/STOP
13
14
PWM INPUT
13
20
13
LOAD LIMIT INPUT
21
CTB1
*
* Factory wired with optional transformer.
LD03611
YORK INTERNATIONAL
71
Application Data
UNIT LOCATION
for special installation requirements. Roof installations
should incorporate the use of spring-type isolators to
minimize the transmission of vibration into the building
structure.
The YCAL chillers are designed for outdoor installation.
When selecting a site for installation, be guided by the
following conditions:
1. For outdoor locations of the unit, select a place
having an adequate supply of fresh air for the con-
denser.
GROUND LEVELINSTALLATIONS – It is important that
the units be installed on a substantial base that will not
settle, causing strain on the liquid lines and resulting in
possible leaks. A one-piece concrete slab with footers
extending below the frost line is highly recommended.
Additionally, the slab should not be tied to the main
building foundation, as noises will telegraph.
2. Avoid locations beneath windows or between
structures where normal operating sounds may be
objectionable.
3. Installation sites may be either on a roof, or at ground
level. (See FOUNDATION.)
Mounting holes (11/16” diameter) are provided in the
steel channel for bolting the unit to its foundation. See
DIMENSIONS.
4. The condenser fans are the propeller-type, and
are not recommended for use with duct work in the
condenser air stream.
For ground level installations, precautions should be
taken to protect the unit from tampering by or injury
to unauthorized persons. Screws on access panels
will prevent casual tampering; however, further safety
precautions, such as unit enclosure options, a fenced-in
enclosure, or locking devices on the panels may be ad-
visable. Check local authorities for safety regulations.
5. When it is desirable to surround the unit(s), it is
recommended that the screening be able to pass
the required chiller CFM without exceeding 0.1” of
water external static pressure.
6. Protection against corrosive environments is avail-
able by supplying the units with either copper fin,
cured epoxy-dipped, or epoxy-coated fins on the
condenser coils. The epoxy-dipped or epoxy-coated
coils should be offered with any units being installed
at the seashore or where salt spray may hit the
unit.
CHILLED LIQUID PIPING
The chilled liquid piping system should be laid out so
that the circulating pump discharges into the cooler.
The inlet and outlet cooler liquid connections are given
in DIMENSIONS.
Hand stop valves are recommended for use in all lines
to facilitate servicing. Drain connections should be
provided at all low points to permit complete drainage
of the cooler and system piping. Additionally, a strainer
(40 mesh) is recommended for use on the INLET line
to the cooler.
In installations where winter operation is intended and
snow accumulations are expected, additional height
must be provided to ensure normal condenser air
flow.
Recommended clearances for units are given in DI-
MENSIONS. When the available space is less, the
unit(s) must be equipped with the discharge pressure
transducer option to permit high pressure unloading in
the event that air recirculation were to occur.
Pressure gauge connections are recommended for
installation in the inlet and outlet water lines. Gauges
are not furnished with the unit and are to be furnished
by other suppliers.
FOUNDATION
The chilled liquid lines that are exposed to outdoor am-
bients should be wrapped with a supplemental heater
cable and covered with insulation. As an alternative,
ethylene glycol should be added to protect against
freezeup during low ambient periods.
The unit should be mounted on a flat and level founda-
tion, ground or roof, capable of supporting the entire
operating weight of the equipment. Operating weights
are given in the PHYSICAL DATA tables.
A flow switch is available as an accessory on all units.
The flow switch (or its equivalent) must be installed in
the leaving water piping of the cooler and must not be
ROOF LOCATIONS – Choose a spot with adequate
structural strength to safely support the entire weight
of the unit and service personnel. Care must be taken
not to damage the roof during installation. If the roof is
“bonded”, consult the building contractor or architect
72
YORK INTERNATIONAL
FORM 150.64-EG1
Typical Piping for Brazed-Plate
Coolers
Notes:
1. Placement on a level surface free of obstructions
(including snow, for winter operation) or air recircula-
tion ensures rated performance, reliable operation
and ease of maintenance.
2. Piping and wiring shown is for reference use only
and is not in accordance with any national or local
standards.
3. All wiring and piping must comply with applicable
local and national codes.
4. All wiring and piping must follow standard piping
techniques as discussed in the ASHRAE hand-
book.
5. A strainer with a mesh size between .5 and 1.5 mm
is recommended upstream of the heat exchanger to
prevent clogging.
Vibration
Eliminators
Vent
Strainer
INLET
Isolation
Valves
Shut Off
Valves
Pressure
Gauge
Flow
Switch
OUTLET
Drain
Vibration
Eliminators
YORK INTERNATIONAL
73
Guide Specifications
PART 1 – GENERAL
workmanship and material for a period of one year
from date of initial start-up or eighteen (18) months
from date of shipment, whichever occurs first.
1.01
SCOPE
A. The requirements of the General Conditions, Sup-
plementary Conditions, Division 1, and Drawings
apply to all Work herein.
1.03
DELIVERY AND HANDLING
A. Unit shall be delivered to job site fully assembled,
and charged with refrigerant and oil by the Manu-
facturer. (Contractor is responsible for providing and
installing the refrigerant charge including the charge
required for the field installed interconnecting piping.
Chiller components shall ship with a dry nitrogen
holding charge – Remote Evaporator option).
B. Provide Microprocessor controlled, multiple-scroll
compressor, air-cooled, liquid chillers of the sched-
uled capacities as shown and indicated on the
Drawings, including but not limited to:
1. Chiller package
2. Electrical power and control connections
3. Chilled water connections
B. Unit shall be stored and handled per Manufacturer’s
instructions.
4. Change of refrigerant oil (for factory mounted
evaporator) or (evaporator shipped separately
for field installation and piping by contractor)
PART 2 - PRODUCTS
2.01
CHILLER MATERIALS AND COMPONENTS
1.02
QUALITY ASSURANCE
A. General: Install and commission, as shown on the
schedules and plans, factory assembled, charged,
and tested air cooled scroll compressor chiller(s) as
specified herein. Chiller shall be designed, selected,
and constructed using a refrigerant with Flamma-
bility rating of “1”, as defined by ANSI/ASHRAE
STANDARD - 34 Number Designation and Safety
Classification of Refrigerants. Chiller shall include,
but is not limited to: a complete system with a single
refrigerant circuit 35 tons (123kW) and below, and
not less than two refrigerant circuits above 35 tons
(123kW), scroll compressors, direct expansion
type evaporator, air-cooled condenser, refrigerant,
lubrication system, interconnecting wiring, safety
and operating controls including capacity controller,
control center, motor starting components, and
special features as specified herein or required for
safe, automatic operation.
A. Products shall be Designed, Tested, Rated and
Certified in accordance with, and installed in com-
pliance with applicable sections of the following
Standards and Codes:
1. ANSI/ASHRAE Standard 15 – Safety Code for
Mechanical Refrigeration
2. ASHRAE 90.1– Energy Efficiency compli
ance.
3. ANSI/NFPA Standard 70 – National Electrical
Code (N.E.C.).
4. ASME Boiler & Pressure Vessel Code, Sec
tion VIII, Division 1.
5. ARI Standard 550/590 – Positive Displacement
Compressors and Air Cooled Rotary Screw
Water-Chilling Packages.
6. Conform to Intertek Testing Services, formerly
ETL, for construction of chillers and provide
ETL/cETL Listing label.
7. Manufactured in facility registered to ISO
9002.
B. Cabinet: External structural members shall be con-
structed of heavy gauge, galvanized steel coated
with baked on powder paint which, when subject to
ASTM B117, 1000 hour, 5% salt spray test, yields
minimumASTM 1654 rating of “6”.Add Wire Panels
of heavy gauge, welded wire-mesh, coated to resist
corrosion, to protect condenser coils from incidental
damage and restrict unauthorized access to internal
components. Factory installed.
8. OSHA - Occupational Safety and Health Act
B. Factory Test: Chiller shall be pressure-tested, evac-
uated and fully charged with refrigerant and oil, and
shall be factory operational run tested with water
flowing through the vessel.
C. Chiller manufacturer shall have a factory trained
and supported service organization that is within a
50 mile radius of the site.
2.02
COMPRESSORS
D. Warranty: Manufacturer shall Warrant all equipment
and material of its manufacture against defects in
Compressors: Shall be hermetic, scroll-type, in-
cluding:
1. Compliant design for axial and radial sealing
74
YORK INTERNATIONAL
FORM 150.64-EG1
2. Refrigerant flow through the compressor with 100%
suction cooled motor.
2. Low Noise Fans: Shall be dynamically and
statically bal anced, direct drive, corrosion re
sistant glass fiber reinforced composite blades
molded into a low noise, full-airfoil cross section,
3. Large suction side free volume and oil sump to
provide liquid handling capability.
4. Compressor crankcase heaters to provide extra
liquid migration protection.
providing
sound. Each fan
to prevent crossflow
vertical air discharge and low
initsowncompartment
during fan
5. Annular discharge check valve and reverse vent
assembly to provide low pressure drop, silent shut-
down and reverse rotation protection.
cycling. Guards of heavy gauge,
(polyvinylchloride) coated or galvanized
steel.
P V C
6. Initial Oil charge.
7. Oil Level sightglass.
8. Vibration isolator mounts for compressors.
3. Fan Motors: High efficiency, direct drive, 6 pole,
3 phase, insulation class “F”, current protected,
Totally Enclosed Air-Over (TEAO), rigid
mounted, with double sealed, permanently lu-
bricated, ball bearings.
9. Brazed-type connections for fully hermetic refrig-
erant circuits.
2.03
REFRIGERANT CIRCUIT COMPONENTS
Each refrigerant circuit shall include: liquid line shutoff
valve with charging port, low side pressure relief device,
filter-drier, solenoid valve, sight glass with moisture indi-
cator, expansion valves, and flexible, closed-cell foam
insulated suction line.
2.05
CONTROLS
A. General: Automatic start, stop, operating, and pro-
tection sequences across the range of scheduled
conditions and transients.
2.04
HEAT EXCHANGERS
B. Microprocessor Enclosure: Rain and dust tight
NEMA 3R/12 (IP55) powder painted steel cabinet
with hinged, latched, and gasket sealed door.
A. Evaporator:
1. Evaporator shall be brazed-plate stainless
steel construction, single or dual circuit heat
exchangers capable of refrigerant working
pressure of 450 psig (3103 kPa) and
C. Microprocessor Control Center:
1. Automatic control of compressor start/stop,
anti-coincidence and anti-recycle timers, au-
tomatic pumpdown on shutdown, condenser
fans, evaporator pump, evaporator heater, unit
alarm contacts, and chiller operation from 0°F
to 125°F (-18°C to 52°C) ambient. Automatic
reset to normal chiller operation after power
failure.
liquid side pressure of 150 psig (1034 kPa)
(Option for 300 psig [2068 kPa] available.)
2. Evaporator shall be covered in 3/4" (19mm)
flexible, closed cell insulation, thermal conduc
tivity of 0.26k (BTU/HR-FT2-°F]/in.) maximum.
3. C o o l e r s h a l l h a v e t h e r m o s t a t i
cally controlled heaters to protect to -20°F
(29°C) ambient in off-cycle.
2. Remote water temperature reset via a Pulse
Width Modulated (PWM) input signal or up to
two steps of demand (load) limiting.
4. Brazed plate heat exchangers shall be UL
listed.
3. Software stored in non-volatile memory, with
programmed setpoints retained in lithium bat-
tery backed real time clock (RTC) memory for
minimum 5 years.
5. Installing contractor must include accomoda
tions in the chilled water piping to allow prop
er drainage and venting of the heat exchang
er. A strainer with a mesh size between 0.5
and 1.5mm (40 mesh) is recommended up
stream of the heat exchanger to prevent clog
ging.
4. Forty character liquid crystal display, descrip-
tions in English (or Spanish, French, Italian, or
German), numeric data in English (or Metric)
units. Sealed keypad with sections for Setpoints,
Display/Print, Entry, Unit Options & clock, and
On/Off Switch.
B. Air Cooled Condenser:
1. Coils: Internally enhanced, seamless copper
tubes, mechanically expanded into aluminum
alloy fins with full height collars. Subcooling coil
an integral part of condenser. Design working
pressure shall be 450 PSIG (31 bar).
5. Programmable Setpoints (within Manufacturer
limits): display language; chilled liquid tempera-
ture setpoint and range, remote reset tempera-
ture range, set daily schedule/holiday for start/
stop, manual override for servicing, low and high
ambient cutouts, number of compressors, low
YORK INTERNATIONAL
75
liquid temperature cutout, low suction pressure
cutout, high discharge pressure cutout, anti-re-
cycle timer (compressor start cycle time), and
anti-coincident timer (delay compressor
starts).
A. Power Panels:
1. NEMA 3R/12 (IP55) rain/dust tight, powder
painted steel cabinets with hinged, latched, and
gasket sealed outer doors. Provide main power
connection(s), control power connections, com-
pressor and fan motor start contactors, current
overloads, and factory wiring.
6. Display Data: Return and leaving liquid tem-
peratures, low leaving liquid temperature cut-
out setting, low ambient temperature cutout set-
ting, outdoor air temperature, English or metric
data, suction pressure cutout setting, each
system suction pressure,discharge pres-
sure (standard on YCAL0041-0065 models),
liquid temperature reset via a YORK ISN DDC
or Building Automation System (by others) via
PWM input as standard or a 4-20milliamp or 0-
10 VDC input or contact closure with optional
BAS interface, anti-recycle timer status for each
compressor, anti-coincident system start timer
condition, compressor run status, no cooling
load condition, day, date and time, daily start/
stop times, holiday status, automatic or manual
system lead/lag control, lead system definition,
compressor starts/operating hours (each), sta-
tus of hot gas valves, evaporator heater and
fan operation, run permissive status, number
of compressors running, liquid solenoid valve
status, load & unload timer status, water pump
status.
2. Power supply shall enter unit at a single loca-
tion, be 3 phase of scheduled voltage, and
connect to individual terminal blocks per com-
pressor. Separate disconnecting means and/
or external branch circuit protection (by Con-
tractor) required per applicable local or national
codes.
B. Exposed compressor, control and fan motor power
wiring shall be routed through liquid tight conduit.
2.07
ACCESSORIES AND OPTIONS
Some accessories and options supercede standard
product features. Your YORK representative will be
pleased to provide assistance.
A. Microprocessor controlled, Factory installedAcross-
the-Line type compressor motor starters as stan-
dard.
7. System Safeties: Shall cause individual com
pressor systems to perform auto shut down;
manual reset required after the third trip in 90
minutes. Includes: high discharge pressure, low
suction pressure, high pressure switch, and
motor protector. Compressor motor protector
shall protect against damage due to high input
current or thermal overload of windings.
B. Outdoor Ambient Temperature Control
1. Low Ambient Control: Permits unit operation to
0°F ambient. .
2. High Ambient Control: Permits unit operation
above 115°F ambient.
C. Power Supply Connections:
8. Unit Safeties: Shall be automatic reset and
cause compressors to shut down if low ambi-
ent, low leaving chilled liquid temperature, un-
der voltage, and flow switch operation. Contrac-
tor shall provide flow switch and wiring per chiller
manufacturer requirements.
1. Single Point Power Supply: Single point Termi-
nal Block for field connection and interconnect-
ing wiring to the compressors. Separate exter-
nal protection must be supplied, by others, in
the incoming power wiring, which must comply
with the National Electric Code and/or local
codes. Standard unit controls to 25°F
ambient. Low Ambient Control standard on
YCAL0041-0065 models
9. Alarm Contacts: Low ambient, low leaving
chilled liquid temperature, low voltage, low
battery, and (per compressor circuit): high dis-
charge pressure, and low suction pressure.
2. Single Point Power Supply with individual Sys-
tem Breakers: Single or Terminal Block(s) for
field connection and factory interconnecting
wiring to factory supplied system breakers .
Available on YCAL0090-0134 models.
D. Manufacturer shall provide any controls not listed
above, necessary for automatic chiller operation.
Mechanical Contractor shall provide field control
wiring necessary to interface sensors to the chiller
control system.
3. Single Point or Disconnect: Single or Dual point
Non-Fused Disconnect(s) and lockable exter-
nal handle (in compliance with Article 440-14
2.06
POWER CONNECTION AND DISTRI-
BUTION
76
YORK INTERNATIONAL
FORM 150.64-EG1
100ppm).
of N.E.C.) can be supplied to isolate the unit
power voltage for servicing. Separate external
fusing must be supplied, by others, in the in
coming power wiring, which must comply with
the National Electric Code and/or local codes.
I. Protective Chiller Panels (Factory or Field Mounted
1. Louvered Panels (condenser coils only):
Painted steel as per remainder of unit cabinet,
over external condenser coil faces.
4. Single Point Disconnect with Individual System
Breakers: Single point Terminal Block with Non-
Fused Disconnect and lockable external handle
(in compliance with Article 440-14 of N.E.C.)
can be supplied to isolate power voltage for
servicing. Factory interconnecting wiring from
disconnect to factory supplied circuit breakers.
Available on YCAL0041-0065.
2. Wire Panels (full unit): Heavy gauge, welded
wire-mesh,PVC-coatedtoresistcorrosion,topro-
tect condenser coils from incidental damage
and restrict unauthorized access to internal
components.
3. Louvered Panels (full unit): Painted steel as per
remainder of unit cabinet, to protect condenser
coils from incidental damage, visually screen
internal components, and prevent unauthorized
access to internal components.
5. Single Point Circuit Breaker: Single point Ter-
minal Block with Circuit Breaker and lockable
external handle (in compliance with Article 440
14 of N.E.C.) can be supplied to isolate power
voltage for servicing. Incoming power wiring
must comply with the National Electric Code
and/or local codes. Single Point Circuit Break
ers available on YCAL0041-0065 models.
4. Louvered/Wire Panels: Louvered steel panels
on external condenser coil faces, painted as
per remainder of unit cabinet. Heavy gauge,
welded wire-mesh, coated to resist corrosion,
around base of machine to restrict unauthorized
access.
D. Pressure Transducers and Readout Capability
1. Discharge Pressure Transducers: Permits unit
to sense and display discharge pressure. Stan-
dard on YCAL0080-0134 models.
J. Flow Switch (Field-mounted): Vapor proof SPDT,
NEMA 4X switch ( ___150 PSIG or ___300 PSIG),
-20°F to 250°F.
K. Differential Pressure Switch: Alternative to an
above mentioned flow switch. Pretempco model
DPS300A-P40PF-82582-5 (300 psi max. working
pressure) SPDT 5 amp 125/250VAC switch, Range
0 - 40 PSID, deadband 0.5 - 0.8 psi, with 1/4” NPTE
Pressure Connections.
E. Control Power Transformer: Converts unit power
voltage to 120-1-60 (500 VA capacity). Factory-
mounting includes primary and secondary wiring
between the transformer and the control panel.
F. Motor Current Module: Capable of monitoring com-
pressor motor current. Provides extra protection
against compressor reverse rotation, phase-loss
and phase imbalance. Option consists of one mod-
ule per electrical system. (Factory-mounted.)
L. Evaporator options:
1. Provide 1½" cooler insulation in lieu of standard
¾".
2. Provide DX Cooler with 300 PSIG water-side
design working pressure in lieu of standard 150
PSIG.
3. Provide Raised Face Flanges for field instal-
lation on cooler nozzles and field piping:
a. 150 PSIG, welded Flanges.
b. 300 PSIG, welded Flanges.
G. Power Factor Correction Capacitors: Provided to
correct unit compressor factors to a 0.90-0.95.
H. Condenser Coil Environmental Protection:
1. Pre-Coated: Epoxy coated aluminum fin stock to
guard from corrosive agents and insulate
against galvanic potential. For mild seashore
or industrial locations.
M. Service Isolation valves: Service suction and dis
charge (ball type) isolation valves are added to unit
per system. This option also includes a system high
pressure relief valve in compliance with ASHRAE
15. (Factory-mounted.)
2. Copper Fin: Provide copper fins in lieu of alumi-
num.
3. Post-Coated Dipped: Dipped-cured coating on
condenser coils for seashore and other corro-
sive applications (with the exception of strong
alkalis, oxidizers, and wet bromine, chlorine and
fluorine in concentrations greater than
N. Remote Cooler: Manufacturer shall provide sep-
arately: chiller less evaporator, leaving and return
YORK INTERNATIONAL
77
on mixed liquid temperature.
water sensors, and liquid line components (solenoid
valves, filter driers, sight glasses, and TXVs), as
discrete elements of a complete factory system.
Contractor shall be field erect system and provide
interconnecting refrigerant piping and wiring in
accordance with Manufacturer recommendations,
and project plans and schedules. Where not oth-
erwise specified, Contractor provided system piping
shall be in accordance with applicable sections of
ASHRAE Handbook.
X. Sound Reduction (Factory-mounted):
1. Ultra quiet, low speed, reduced noise fans
2. Compressor Acoustic Sound Blankets
Y. Vibration Isolation (Field-mounted):
1. Neoprene Pad Isolators.
2. 1 Inch Deflection Spring Isolators: Level ad-
justable, spring and cage type isolators for
mounting under the unit base rails.
O. Hot Gas By-Pass: Permits continuous, stable op-
eration at capacities below the minimum step of
unloading to as low as 5% capacity (depending on
both the unit & operating conditions) by introducing
an artificial load on the cooler. Hot gas by-pass is
installed on only one refrigerant circuit (System
#1).
3. 2 Inch Deflection Seismic Isolators: Level ad-
justable, restrained mounts in rugged welded
steel housing with vertical and horizontal limit
stops. Housings shall be designed to withstand
a minimum 1.0g accelerated force in all direc-
tions to 2 inches.
PART 3 - EXECUTION
P. Microprocessor Membrane Keypad Graphics on in
lieu of Standard English:
3.01
INSTALLATION
1. French language.
2. German language.
3. Spanish language.
4. Italian language.
A. General: Rig and Install in full accordance with
Manufacturers requirements, Project drawings, and
Contract documents.
B. Location: Locate chiller as indicated on drawings,
including cleaning and service maintenance clear-
ance per Manufacturer instructions.Adjust and level
chiller on support structure. If equipment provided
exceeds height of scheduled chiller, installing con-
tractor is responsible for additional costs associated
with extending the height of parapet or screening
walls/enclosures
Q. Thermal Storage: Leaving chilled liquid setpoint
range for charge cycle from 25°F to 20°F minimum,
with automatic reset of the leaving brine temperature
up to 40°F above the setpoint. (Works with Option
T)
R. Low Temperature Process Brine: Leaving chilled
liquid setpoint range 20°F to 30°F.
C. Components: Installing Contractor shall provide and
install all auxiliary devices and accessories for fully
operational chiller.
S. Chicago Code Relief Valves to meet Chicago Code
requirements.
T. BuildingAutomation System (EMS) Reset Interface:
Chiller to accept 4 to 20mA, 0 to 10 VDC, or discrete
contact closure input to reset the leaving chilled
liquid temperature.
D. Electrical: Coordinate electrical requirements and
connections for all power feeds with Electrical Con-
tractor (Division 16).
E. Controls: Coordinate all control requirements and
connections with Controls Contractor.
U. Remote Control Panel (Field-mounted): Auxiliary
panel for remote user interface for functions nor-
mally made at the unit control center. Available on
YCAL0014-0080 models.
F. Finish: Installing Contractor shall paint damaged and
abraded factory finish with touch-up paint matching
factory finish.
V. OptiView Remote Control Panel (Field-mounted):
Graphical interface panel to remotely control and
monitor up to 8 different units.
W. Multi-Unit Sequencing Panel (Field-mounted):
Separate Sequencing control center is provided to
permit control of up to eight chillers in parallel based
78
YORK INTERNATIONAL
FORM 150.64-EG1
YORK INTERNATIONAL
79
Subject to change without notice. Prin
ALL RIGHT
P.O.Box 1592 York, Pennsylvania USA 17405-1592
Copyright © by York International Corporation 2004
Form 150.62-EG1 (103)
Supersedes: 150.62-EG1 (102)
RPC 3M 303 9.28
Codes: DXL, ET2
|