					261660-YTG-D-0708   ® DESCRIPTION   YORK Sunline Magnum™ units are convertible single pack-   age high efficiency rooftops. All models have independent   dual refrigerant circuits for efficient part load operation.   Although the units are primarily designed for curb mounting   on a roof, they can also be slab-mounted at ground level or   set on steel beams above a finished roof.   TECHNICAL GUIDE   All units include:   • Powder Paint finish that meets ASTM-B-117 1000 hour   salt spray standards   • Two-stage cooling provided by dual independent   refrigeration circuits with expansion valves, filter-driers,   high and low pressure/loss of charge switches and   freezestats   SINGLE PACKAGE GAS/ELECTRIC UNITS   AND SINGLE PACKAGE AIR   CONDITIONERS   • • Scroll compressors   Two-stage heating provided by dual independent heat   exchangers with aluminized steel tubes, redundant gas   valves, spark ignition with induced draft logic   DJ 180, 210, 240 & 300   15 & 25 NOMINAL TONS   • • Permanently lubricated motors   12.00 EER (15 TONS), 11.70 EER (17.5 TONS),   11.3 EER (20 TONS), 10.5 EER (25 TONS)   Bottom or side air discharge configuration capability   (field convertible)   • • Belt Drive Blower Motor with high static drive option   Constant supply air volume (CV) with optional variable   air volume (VAV)   • • • • • • Manufactured under the quality standards of ISO9001   S implicity® Control Board   Zero-25% fixed air damper with hood   Copper tube/aluminum fin coils   Hinged filter access and tool free latched doors   Hinged tool free blower, blower motor, filters and electri-   cal panel access   • • • • Rigging holes in base rails for lifting   Single point power connection   Complete factory package - tested, charged and wired   CSA agency approvals on all units   WARRANTY   • • One-year parts warranty   A Five-year parts warranty on the compressors and   electric heat elements   • Ten-year parts warranty on the gas-fired heat   exchangers   FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE   
			
				  
				
					261660-YTG-D-0708   PRODUCT NOMENCLATURE   15-25 Ton Magnum™ Model Number Nomenclature   D J 180 N24 A 2 A AA 1 0 1 2 4 A   Product Category   Product Style   D = A/C, Single Pkg., R-22   A = Style A   Product Identifier   Configuration Options (not required for all units)   These four digits will not be assigned until a quote is requested, or an order placed.   J = 11.0+ EER A/C   SS Drain Pan   CPC Controller, DFS, APS   Nominal Cooling Capacity   Johnson Controller UNT 1126 (N2 protocol), DFS, APS   Honeywell Controller, DFS, APS   Novar Controller, DFS, APS   180 = 15 Ton   210 = 17.5 Ton   240 = 20 Ton   300 = 25 Ton   Simplicity IntelliComfort Controller   Simplicity IntelliComfort Controller w/ModLinc   York Commercial Comfort System (YCCS) Rtu Controller   Hot Gas Bypass (Standard on VAV, Optional on CV)   Heat Type and Nominal Heat Capacity   C00 = Cooling Only. No field installed   electric heat   Variable Air Volume, VFD (not available with factory installed BAS options)   Variable Air Volume, VFD with ModLINC (not available with factory installed BAS options)   Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)   Variable Air Volume, VFD and Manual Bypass with ModLINC (not available with factory installed BAS options)   Variable Air Volume, VFD (BAS ready)   Gas Heat Options   N24 = 240 MBH Output Aluminized Steel   N32 = 320 MBH Output Aluminized Steel   S24 = 240 MBH Output Stainless Steel   S32 = 320 MBH Output Stainless Steel   Variable Air Volume, VFD and Manual Bypass (BAS ready)   Variable Air Volume, VFD Ready (for customer provided, field installed drive)   Variable Air Volume, VFD Ready with ModLINC (for customer-provided, field-installed drive)   2" Pleated filters   Electric Heat Options   4" Pleated filters   E18 = 18 KW   E36 = 36 KW   E54 = 54 KW   E72 = 72 KW   BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)   Double Wall Construction   Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned   Product Generation   Airflow   1 = First Generation   2 = Second Generation   A = Std. Drive   B = Std. Drive/Single Input Econo.   C = Std. Drive/Single Input Econo./Power Exhaust   (Downflow Only)   D = Std. Drive/Motorized Damper   Additional Options   Hinged Filter Door & Tool Free Access Cabinet   E = Std. Drive/Motorized Damper/Barometric Relief   J = Std. Drive/Single Input Econo./Barometric Relief   N = Hi Static Drive   P = Hi Static Drive/Single Input Econo.   Q = Hi Static Drive/Single Input Econo./Power Exhaust   (Downflow Only)   R = Hi Static Drive/Motorized Damper   K = Hi Static Drive/Motorized Damper/Barometric Relief   S = Hi Static Drive/Single Input Econo./Barometric Relief   Standard Cabinet   AA = None   BA = Hinged Filter Door & Tool Free Access Panels   BB = Phase Monitor, Hinged Filter Door & Tool Free   Access Panels   AB = Phase Monitor   AC = Coil Guard   AD = Dirty Filter Switch   BC = Coil Guard, Hinged Filter Door & Tool Free   Access Panels   AE = Phase Monitor & Coil Guard   AF = Phase Monitor & Dirty Filter Switch   AG = Coil Guard & Dirty Filter Switch   AH = Phase Monitor, Coil Guard & Dirty Filter Switch   RC = Coil Guard & American Flag   TA = Technicoat Condenser Coil   TJ = Technicoat Evaporator Coil   TS = Technicoat Evaporator & Condenser Coils   BD = Dirty Filter Switch, Hinged Filter Door &   Tool Free Access Panels   BE = Phase Monitor & Coil Guard, Hinged Filter   Door & Tool Free Access Panels   BF = Phase Monitor & Dirty Filter Switch, Hinged   Filter Door & Tool Free Access Panels   BG = Coil Guard & Dirty Filter Switch, Hinged Filter   Door & Tool Free Access Panels   Voltage   2 = 208/230-3-60   4 = 460-3-60   5 = 575-3-60   BH = Phase Monitor, Coil Guard & Dirty Filter Switch,   Hinged Filter Door & Tool Free Access Panels   ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be   located in digits 15-18.   Installation Options   A = No Options Installed   N = Options 2 & 3   P = Options 2 & 4   Q = Options 2, 3, & 4   R = Options 3 & 4   S = Option 5   T = Options 1 & 5   U = Options 1, 3, & 5   V = Options 1, 4, & 5   W = Options 1, 3, 4, & 5   X = Options 3 & 5   Y = Options 4 & 5   Z = Options 3, 4 & 5   B = Option 1   C = Option 2   D = Options 1 & 2   E = Option 3   F = Option 4   G = Options 1 & 3   H = Options 1 & 4   J = Options 1, 2 & 3   K = Options 1, 2, & 4   L = Options 1,3 & 4   M = Options 1, 2, 3, & 4   Options   1 = Disconnect   2 = Non-Pwr'd Conv. Outlet   3 = Smoke Detector S.A.   4 = Smoke Detector R.A.   5 = Pwr'd Conv. Outlet   Johnson Controls Unitary Products   3 
			
				
					261660-YTG-D-0708   • • Low Ambient - An integrated low-ambient control   allows all units to operate in the cooling mode down   to 0ºF outdoor ambient without additional assis-   tance. Optionally, the control board can be pro-   grammed to lockout the compressors when the   outdoor air temperature is low or when free cooling   is available.   FEATURES   All models are available with a wide variety of factory-   mounted options such as stainless steel heat exchangers,   phase monitor, dirty filter switch, and coil guard to make them   suitable for almost every application.   All units are self-contained and assembled on full perimeter   base rails with holes in the four corners for overhead rigging.   Every unit is completely piped, wired, charged and tested at   the factory to simplify the field installation and to provide   years of dependable operation.   Anti-Short Cycle Protection - To aid compressor   life, an anti-short cycle delay is incorporated into the   standard controls. Compressor reliability is further   ensured by programmable minimum run times. For   testing, the anti short cycle delay can be temporarily   overridden with the push of a button.   All models (including those with an economizer) are suitable   for either bottom or horizontal duct connections. Models with   factory installed power exhaust are suitable for bottom   duct connections only. For bottom duct, you remove the   sheet metal panels from the supply and return air openings   through the base of the unit. For horizontal duct, you replace   the supply and return air panels on the rear of the unit with a   side duct flange accessory.   • • Lead-Lag - An integrated Lead-Lag option allows   equal run time hours on all compressors, thereby   extending the life of all compressors. This option is   selectable on the unit control board.   Fan Delays - Fan on and fan off delays are fully pro-   grammable. Furthermore, the heating and cooling   fan delay times are independent of one another. All   units are programmed with default values based   upon their configuration of cooling and heat.   All models are available with these “factory mounted” outdoor   air damper options:   • Single enthalpy economizer with or without power   exhaust   • • • Safety Monitoring - The control board monitors the   high and low-pressure switches, the freezestats, the   gas valve, if applicable, and the temperature limit   switch on gas and electric heat units. The unit con-   trol board will alarm on ignition failures, compressor   lockouts and repeated limit switch trips.   • • • BAS-ready economizer with or without power exhaust   Motorized outdoor air damper   Barometric Relief Damper   A fixed outdoor air intake assembly will be shipped in the   return air compartment of all units ordered without an econo-   mizer or motorized outdoor air damper option. The assembly   includes a rain hood with a damper that can be set for 10, 15   or 25% outdoor air. With bottom duct connections, the intake   damper assembly should be mounted over the opening in the   return air panel. With horizontal ductwork, it should be   mounted on the return air duct.   Nuisance Trip Protection and Strikes - To prevent   nuisance trouble calls, the control board uses a   “three times, you’re out” philosophy. The high and   low-pressure switches and the freezestats must trip   three times within two hours before the unit control   board will lock out the associated compressor.   On Board Diagnostics - Each alarm will energize a   trouble light on the thermostat, if so equipped, and   flash an alarm code on the control board LED. Each   high and low-pressure switch alarm as well as each   freezestat alarm has its own flash code. The control   board saves the five most recent alarms in memory,   and these alarms can be reviewed at any time.   Alarms and programmed values are retained   through the loss of power.   All supply air blowers are equipped with a belt drive that can   be adjusted to meet the exact requirements of the job. A high   static drive option is available for applications with a higher   CFM and/or static pressure requirement. A variable air vol-   ume (VAV) option using a variable frequency drive is available   for applications requiring a constant supply duct pressure. A   differential pressure transducer is used to monitor supply duct   static pressure and return a speed reference signal to the VFD   to control the output of the indoor blower motor.   All units have long lasting powder paint cabinets with 1000   hour salt spray test approval under ASTM-B117 procedures.   All compressors include scroll compressors and internal pres-   sure relief. Every refrigerant circuit includes an expansion   valve, a liquid line filter-drier, a discharge line high pressure   switch and a suction line with a freezestat and low pressure/   loss of charge switch to protect all system components. A hot   gas bypass option, consisting of an adjustable compressor   discharge bypass valve, is available for low cooling load   applications.   All models are CSA approved.   • Warranty - All models include a one-year limited parts   warranty on the complete unit. Compressors and electric   heater elements carry a five-year warranty. Gas heat   exchangers carry a 10-year parts warranty.   • Gas Heat Operation - All gas heat units are built with   two heating sections for two equal stages of capacity   control. Each section includes a durable heat exchanger   • S implicity® Controls - S implicity® control boards have   standardized a number of features previously available   only as options or by utilizing additional controls.   4 Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   LOCATION OF VFD (Optional)   LOCATION OF VFD BYPASS (Optional)   FIGURE 1 - UNIT CUTAWAY   with aluminized steel or optional stainless steel tubes, a   redundant gas valve, spark ignition, power venting, an   ignition module for 100% shut-off and all of the safety   controls required to meet the latest ANSI standards.   The enthalpy system contains one sensor that monitors   the outdoor air and determines when the air is cool   enough and dry enough to provide free cooling.   The rainhood is painted to match the basic unit and must   be field-assembled before installing.   The gas supply piping can be routed into the heating   compartment through a hole in the base pan of the unit   or through a knockout in the piping panel on the front of   the unit.   • BAS-READY ECONOMIZER - Includes a slide-in / plug-   in damper assembly with fully modulating spring-return   motor actuator with zero to 95-degree rotation capable of   introducing up to 100% outdoor air with nominal 1% leak-   age type dampers.   • Electric Heat Operation - All electric heat models (fac-   tory installed only) are wired for a single power source   and include a bank of nickel chromium elements   mounted at the discharge of the supply air blower to pro-   vide a high velocity and uniform distribution of air across   the heating elements. Every element is fully protected   against excessive current and temperature by fuses and   two thermal limit switches.   Actuator requires 2-10 VDC input from an external   source, such as a field-installed or factory-installed BAS   controller. BAS-ready actuators have an adjustable auxil-   iary end-switch for optional power exhaust control.   For units with optional VAV or Simplicity® Intelli-Com-   fort™ control, a factory-installed, dry bulb sensor deter-   mines if outdoor air temperature is low enough to provide   free-cooling operation. (Field-installed humidity sensors   for either outdoor air or outdoor & return air streams are   available for single enthalpy and differential enthalpy   configurations, respectively).   The power supply wiring can be routed into the control   box through a threaded pipe connection in the base pan   of the unit or through a knockout in the wiring panel on   the front of the unit.   • BAS Controls - York’s Magnum™ series units offer fac-   ® tory mounted BAS controls such as S implicity Intelli-   The rainhood is painted to match the basic unit and must   be field-assembled before installing.   Comfort™, Novar, Honeywell, Johnson, York Commercial   Comfort System (YCCS) and CPC.   • POWER EXHAUST - Our single economizer options are   available with power exhaust. Whenever the outdoor air   intake dampers are opened for free cooling, the exhaust   fan will be energized to prevent the conditioned space   from being over-pressurized during economizer opera-   tion. BAS-ready economizer actuators have an adjustable   auxiliary end-switch to provide a range of damper positions   available to energize power exhaust. For units with optional   FACTORY-INSTALLED OPTIONS   • SINGLE INPUT ELECTRONIC ENTHALPY ECONO-   MIZERS - Includes a slide-in / plug-in damper assembly   with fully modulating spring-return motor actuator capa-   ble of introducing up to 100% outdoor air with nominal   1% leakage type dampers.   Johnson Controls Unitary Products   5 
			
				
					261660-YTG-D-0708   VAV, power exhaust is energized by means of a binary out-   put signal from the unit's VAV control board.   bracket, the maximum recommended drive dimensions   are as follows:   For 5-hp motor applications ........................13” H x 6” W x 7” D   For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D   The exhaust fan, motor and controls are installed and   wired at the factory. The rain hood must be assembled   and installed in the field.   If the drive will not fit in the allotted space, then it will   have to be mounted elsewhere; either within the building   on a perpendicular wall which is not subjected to exces-   sive temperature, vibration, humidity, dust, corrosive   gas, explosive gas, etc., or within an appropriate enclo-   sure rated for outside installation to safeguard against   moisture, dust and excessive heat.   The power exhaust option can only be used on bot-   tom duct configurations.   • MOTORIZED OUTDOOR AIR INTAKE DAMPER -   Includes a slide-in / plug-in damper assembly with a 2-   position, spring return motor actuator which opens to a   pre-set position whenever the supply air blower is oper-   ating and will drive fully closed when the blower unit   shuts down.   A terminal block located in the control box is provided for   field connection of the VFD controls.   The rain hood is painted to match the basic unit and   must be field assembled before installing.   • HOT GAS BYPASS - To allow for low cooling load oper-   ation, a direct-acting pressure-modulating bypass control   valve installed on the system #1 discharge line is used to   divert high temperature, high pressure refrigerant around   the TXV in order to maintain a desired minimum evapo-   rator pressure. HGBP is standard on all units with VAV   and optional with CV units.   • BAROMETRIC RELIEF DAMPER - This damper option   can be used to relieve internal building air pressure on   units with an economizer without power exhaust. This   accessory includes a rain hood, a bird screen and a fully   assembled damper. With bottom duct connections, the   damper should be mounted over the opening in the   return air panel. With horizontal ductwork, the accessory   should be mounted on the return air duct.   • • FILTER OPTIONS - Standard units are shipped with 2”   throw-away filters installed. 2” pleated and 4” pleated fil-   ters are offered as a factory installed option.   • • • PHENOLIC COATED EVAPORATOR AND CON-   DENSER COILS - Special coating process that utilizes   Technicoat 10-1" processes. Coating is applied by total   immersion of the complete coil for maximum protection.   CONVENIENCE OUTLET - This 110 volt outlet can be   “powered” by the unit with a stepdown transformer or   you may order the unit with a “non-powered” conve-   nience outlet that can be wired in the field.   ELECTRIC HEATERS wired for single point power sup-   ply. These nickel chromium heater elements are pro-   vided with limit and automatic reset capability to prevent   operation at excessive temperatures.   • • DISCONNECT SWITCH - For gas heat units and cooling   units with electric heat, a HACR breaker sized to the unit   is provided. For cooling only units, a switch sized to the   largest electric heat available for the particular unit is   provided. Factory installed option only.   VARIABLE AIR VOLUME (VAV) - A factory-installed   variable frequency drive (VFD), mounted in the Blower   Access compartment, is used to control the speed of the   indoor blower motor in order to maintain a constant static   pressure in the supply duct. A pressure transducer and   VAV control board are mounted inside the control box.   The drive comes completely wired and pre-programmed   from the factory.   DOUBLE WALL CONSTRUCTION - Optional double   wall construction is available to provide smooth inner   surfaces for easy and effective cleaning to reduce risk of   dirt and bacterial accumulation. Fiberglass insulation is   sandwiched between heavy gauge steel sheets to form a   durable, rigid casing to withstand higher working pres-   sures and impact forces. The heavy-duty construction   provides excellent acoustic and thermal insulation and   eliminates erosion of insulation material and contamina-   tion of the air stream.   An optional, factory-installed manual bypass switch   available with factory-installed VFD can be found in the   Blower Motor Access compartment. The switch can be   used to either route power to the VFD for modulating   control of the blower motor, to bypass the drive and oper-   ate the motor at full speed, or to power the drive (and not   the motor) for diagnostic purposes.   • BAS - Building Automation System Controls (avail-   able on two-system cooling product only).   S implicity® INTELLI-Comfort™ CONTROL - The York®   S implicity® INTELLI-Comfort™ control is factory installed.   It includes a supply air sensor, a return air sensor, and an   outside air sensor. There are provisions for a field installed   dirty filter indicator switch, an air-proving switch, an Out-   side Air Humidity sensor, a Return Air Humidity sensor, an   Inside IAQ sensor, and an Outside Air IAQ sensor. Con-   struction mode operation, 365-day real time clock with 7   day programming plus holiday scheduling is built-in. Two   different modes of demand ventilation are achieved   Due to space limitations, VAV is not available with any of   the factory-installed BAS options described below, but is   available with ‘BAS-ready’ models. Terminal blocks are   provided in the control box for field wiring of the cus-   tomer-installed BAS.   A ‘VFD-ready’ option provides the provisions for a cus-   tomer-installed drive. The unit comes with a mounting   bracket installed in the Blower Access compartment   which may accommodate other vendor’s drives depend-   ing on their size. In order to utilize the unit’s mounting   through the INTELLI-Comfort™ using CO sensors. It   2 6 Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   uses an inside CO sensor to perform Demand Ventila-   power to the control board if smoke is detected within the   air compartment.   2 tion. It can also use an Outside CO sensor to perform Dif-   2 ferential Demand Ventilation. It uses a Patented Comfort   Ventilation algorithm to provide comfortable ventilation air   temperature. The patented economizer-loading algorithm   will protect the equipment when harsh operating condi-   tions exist. Humidity in the occupied space or return duct   can be monitored and controlled via humidity sensors and   the on-board connection for hot gas re-heat system. It   uses the INTELLI-Start™ algorithm to maximize energy   savings by recovering the building from the Unoccupied   Setpoints to the Occupied Setpoints just in time for the   Occupied Time Period to begin. The S implicity® INTELLI-   Comfort™ balances space temperature, ventilation air   Factory installed smoke detectors in the return air   may be subjected to freezing temperatures during   “off” times due to outside air infiltration. These   smoke detectors have an operation limit of 32°F to   131°F. Smoke detectors installed in areas that   could be outside those limitations will have to be   moved to prevent having false alarms.   • • • COIL GUARD - Customers can purchase a coil guard kit   to protect the condenser coil from damage. This is not a   hail guard kit.   temperature, CO and humidity for ultimate comfort.   2 S implicity® INTELLI-Comfort™ with ModLINC CON-   TROL - The York® S implicity® INTELLI-Comfort™ with   ModLINC control is factory installed. It includes all the   features of the INTELLI-Comfort™ control with an addi-   tional control to translate communications from MOD-   BUS to the BACnet MSTP protocol.   STAINLESS STEEL HEAT EXCHANGER - For applica-   tions in corrosive environments, this option provides a   full stainless steel heat exchanger assembly.   STAINLESS STEEL DRAIN PAN - An optional rust-   proof stainless steel drain pan is available to provide   years of trouble-free operation in corrosive environ-   ments.   Novar® BAS CONTROL - The Novar® ETC-3 building   automation system controller is factory installed.   Includes supply air sensor, return air sensor, dirty filter   indicator switch, and air proving switch.   • PHASE MONITORS - Designed to prevent unit damage.   The phase monitor will shut the unit down in an out-of-   phase condition.   JOHNSON CONTROLS BAS CONTROL - The Johnson   Control YK-UNT-1126 building automation system con-   troller is factory installed. Includes supply air sensor,   return air sensor, dirty filter indicator switch, and air prov-   ing switch.   • • HIGH STATIC DRIVE - Includes a belt and blower pulley   upgrade to enhance blower performance.   DIRTY FILTER SWITCH - This kit includes a differential   pressure switch that energizes the fault light on the unit   thermostat, indicating that there is an abnormally high   pressure drop across the filters. Factory installed option   or field installed accessory.   CPC BAS CONTROL - The Computer Process Controls   Model 810-3060 ARTC Advanced Rooftop building auto-   mation system controller is factory installed. Includes   supply air sensor, return air sensor, dirty filter indicator   switch and air proving switch.   • • HINGED FILTER DOOR/”TOOL FREE” BLOWER AND   ACCESS PANELS (not hinged) - This option allows for   easy access and maintenance.   HONEYWELL BAS CONTROL - The Honeywell   W7750C building automation system controller is factory   installed. Includes air supply sensor, return air sensor,   dirty filter indicator switch, and air proving switch.   NOTE:Knobs are shipped separately within the unit to   prevent shipping damage. These must be field   installed for tool free operation.   HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR,   FILTER AND ELECTRIC ACCESS PANELS - This   option allows for complete hinged and tool free access to   the unit's blower, blower motor, filters and electrical panel   sections.   YORK COMMERCIAL COMFORT SYSTEM (YCCS) -   Provides rooftop system integration for YCCS single   zone, change-over bypass and VAV systems.   • SMOKE DETECTORS - (supply air & return air) The   smoke detectors stop operation of the unit by interrupting   Johnson Controls Unitary Products   7 
			
				
					261660-YTG-D-0708   • • SIDE DUCT FLANGES - One-inch flanges replace the   supply and return air panels on the rear of the unit to   accommodate horizontal duct connections. These   flanges can also be used individually for bottom supply/   horizontal return or horizontal supply/bottom return. They   cannot be used on units with power exhaust.   FIELD-INSTALLED ACCESSORIES   • SINGLE INPUT ELECTRONIC ENTHALPY ECONO-   MIZERS - Includes a slide-in / plug-in damper assembly   with fully modulating spring-return motor actuator capa-   ble of introducing up to 100% outdoor air with nominal   1% leakage type dampers.   The enthalpy system contains one sensor that monitors   the outdoor air and determines when the air is cool   enough and dry enough to provide free cooling.   BAROMETRIC RELIEF DAMPER - This damper acces-   sory can be used to relieve internal building air pressure   on units with an economizer without power exhaust. This   accessory includes a rain hood, a bird screen and a fully   assembled damper. With bottom duct connections, the   damper should be mounted over the opening in the   return air panel. With horizontal ductwork, the accessory   should be mounted on the return air duct.   The rainhood is painted to match the basic unit and must   be field-assembled before installing.   • MOTORIZED OUTDOOR AIR INTAKE DAMPER -   Includes a slide-in / plug-in damper assembly with a 2-   position, spring return motor actuator which opens to   some pre-set position whenever the supply air blower is   operating and will drive fully closed when the blower unit   shuts down.   • • HIGH STATIC DRIVE - A smaller blower pulley and a   shorter belt increase the speed of the supply air blower   for applications with a higher CFM and/or static pressure   requirements.   The rain hood is painted to match the basic unit and   must be field assembled before installing.   ENTHALPY ACCESSORY CONTROL KIT - This kit   contains the required components to convert a single   enthalpy economizer to dual enthalpy.   • ROOF CURBS - Fourteen-inch high roof curbs provide a   water-tight seal between the unit and the finished roof.   These full perimeter curbs meet the requirements of the   National Roofing Contractors Association (NRCA) and   are shipped knocked-down for field assembly.   • • BURGLAR BARS - Mount in the supply and return   openings to prevent entry into the duct work.   They're designed to fit inside the base rails of the unit   and include both a wood nailing strip and duct hanger   supports.   FLUE EXHAUST EXTENSION KIT - In locations with   wind or weather conditions which may interfere with   proper exhausting of furnace combustion products, this   kit can be installed to prevent the flue exhaust from   entering nearby fresh air intakes.   • • • HIGH ALTITUDE NATURAL GAS - Burner orifices and   pilot orifices are provided for proper furnace operation at   altitudes up to 6,000 feet.   • • WOOD SKID - Allows unit to be handled with 90” forks.   PROPANE - Burner orifices, pilot orifices and gas valve   parts are provided to convert a natural gas furnace to   propane.   CO SENSOR - Senses CO levels and automatically   2 2 overrides the economizer when levels rise above the   present limits.   HIGH ALTITUDE PROPANE - Burner orifices and pilot   orifices are provided for proper furnace operation at alti-   tudes up to 6,000 feet. This accessory supplements the   basic propane conversion kit.   • COIL GUARD - Customers can purchase a coil guard kit   to protect the condenser coil from damage. This is not a   hail guard kit.   • PHASE MONITORS - Designed to prevent unit damage.   The phase monitor will shut the unit down in an out-of-   phase condition.   8 Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   1 TABLE 1: SOUND POWER RATING   SOUND POWER (db 10-12 Watts)   ESP   IWG   BLOWER   UNIT   SIZE   Octave Band Centerline Frequency (Hz)   dB(A)   @ 10Ft.2   56   CFM   SWL   dB(A)   RPM   BHP   63   125   250   500   1,000   2,000   4,000   8,000   6,000   8,000   1.00   1.00   1.30   1,080   1,120   1160   4.60   6.65   12.5   99   99   89   92   98   82   85   91   84   87   93   77   80   86   72   75   81   67   70   76   89   92   98   180   210/240   300   102   108   102   108   59   10,000   65   1.   These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The   dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan   manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee   requiring a dBA value or sound data in any other form than sound power level ratings.   2.   At a distance of 10 feet from the blower.   1 TABLE 3: GAS HEAT RATIINGS   TABLE 2: CAPACITY RATINGS - (ARI 360)   EER2   IPLV3   MODEL   MBH INPUT   MBH OUTPUT   MODEL   MBH   300   240   320   240   320   240   320   240   320   DJ180N/S24   DJ180N/S32   COOLING ONLY   DJ180C/E00   DJ210C/E00   DJ240C/E00   DJ300C/E00   400   178   208   230   292   12.0   11.7   11.3   10.5   12.5   12.7   12.0   11.2   300   DJ210N/S24   DJ210N/S32   400   300   DJ240N/S24   DJ240N/S32   COOLING WITH GAS HEAT   DJ180N/S   400   178   208   230   292   12.0   11.7   11.3   10.5   12.5   12.7   12.0   11.2   300   DJ300N/S24   DJ300N/S32   DJ210N/S   400   DJ240N/S   NOTE: All gas units are two-stage heating.   First stage is 50% of total.   S.S.E. = Steady State Efficiency (80%) - output divided by input.   DJ300N/S   COOLING WITH ELECTRIC HEAT   DJ180E18   DJ180E36   DJ180E54   DJ180E72   DJ210E18   DJ210E36   DJ210E54   DJ210E72   DJ240E18   DJ240E36   DJ240E54   DJ240E72   DJ300E18   DJ300E36   DJ300E54   DJ300E72   178   178   176   176   208   208   206   206   230   230   228   228   292   292   290   290   12.0   12.0   11.8   11.8   11.7   11.7   11.5   11.5   11.3   11.3   11.1   11.1   10.5   10.5   10.3   10.3   12.5   12.5   12.2   12.2   12.7   12.7   12.4   12.4   12.0   12.0   11.7   11.7   11.2   11.2   11.0   11.0   For units with VFD and electric or gas heat, the   speed of the indoor blower motor continues to   be controlled by duct static pressure via the   VAV control board.   If there are VAV boxes present in the duct sys-   tem, the boxes must be driven to the full-open   position using a customer-supplied power   source to assure adequate airflow across elec-   tric heating elements or gas heat exchanger   tubes.   1.   2.   3.   Certified in accordance with the Unitary Large Equip-   ment certification program which is based on ARI Stan-   dard 340/360.   EER = Energy Efficiency Ratio at full load - the cooling   capacity in Btu’s per hour (Btuh) divided by the power   input in watts, expressed in Btuh per watt (Btuh/watt).   IPLV = Integrated Part Load Value.   Johnson Controls Unitary Products   9 
			
				  
				
					261660-YTG-D-0708   TABLE 4: COOLING CAPACITIES FOR DJ180   Temperature of Air on Condenser Coil   Air on Evaporator Coil   85°F   95°F   2 Total Total2   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   80 77 74   Total Total   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   WB   (°F)   1 CFM   Cap.1 Input   (MBH) (kW) 86   Cap. Input   68 (MBH) (kW) 86   83   71   - 83   80   77   74   71   - 68   - 72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   206.8 11.94 119.7 106.8 94.0 81.2 68.3   - 196.1 12.98 115.7 102.9 90.1 77.3 64.4   187.4 11.64 148.6 135.7 122.9 110.1 97.2 84.4 71.6 178.1 12.70 144.6 131.8 119.0 106.1 93.3 80.5 67.6   169.3 11.37 169.3 162.1 149.3 136.5 123.6 110.8 98.0 161.7 12.49 161.7 157.0 144.2 131.4 118.5 105.7 92.9   166.8 11.36 166.8 164.1 151.3 138.5 125.6 112.8 100.0 163.4 12.53 163.4 160.3 147.5 134.7 121.8 109.0 96.2   4500   212.8 12.00 132.2 117.0 101.8 86.7 71.5   - - 201.2 13.06 127.9 112.7 97.6 82.4 67.2   - - 192.8 11.70 163.5 148.3 133.2 118.0 102.8 87.7 72.5 182.8 12.78 159.2 144.0 128.8 113.7 98.5 83.3 68.2   174.2 11.43 174.2 170.7 161.7 146.6 131.4 116.3 101.1 166.0 12.57 166.0 163.6 156.2 141.0 125.9 110.7 95.5   171.6 11.42 171.6 170.3 163.9 148.8 133.6 118.4 103.3 167.7 12.61 167.7 166.2 159.8 144.6 129.4 114.3 99.1   5250   6000   6600   7200   218.9 12.06 144.7 127.2 109.7 92.2 74.7   - - 206.4 13.14 140.0 122.5 105.1 87.6 70.1   - - 198.3 11.76 178.4 160.9 143.4 125.9 108.4 90.9 73.4 187.5 12.86 173.7 156.2 138.7 121.2 103.7 86.2 68.7   179.2 11.49 179.2 179.2 174.2 156.7 139.2 121.7 104.2 170.2 12.65 170.2 170.2 168.2 150.7 133.2 115.7 98.2   176.5 11.48 176.5 176.5 176.5 159.0 141.5 124.0 106.6 172.0 12.69 172.0 172.0 172.0 154.5 137.0 119.5 102.0   224.3 12.14 156.2 136.7 117.2 97.8 78.3   - - 211.4 13.22 150.4 131.0 111.5 92.0 72.5   - - 203.2 11.83 192.2 172.8 153.3 133.8 114.3 94.9 75.4 192.0 12.93 185.1 166.7 147.2 127.7 108.2 88.8 69.3   183.6 11.57 183.6 183.6 181.1 161.7 142.2 122.7 103.2 174.3 12.72 174.3 174.3 173.3 153.8 134.4 114.9 95.4   180.9 11.56 180.9 180.9 180.9 161.4 141.9 122.5 103.0 176.2 12.76 176.2 176.2 176.2 156.7 137.2 117.7 98.3   229.7 12.22 167.7 146.3 124.8 103.3 81.9   - - 216.4 13.30 160.8 139.4 117.9 96.4 75.0   - - 208.1 11.91 206.1 184.6 163.2 141.7 120.3 98.8 77.3 196.6 13.01 196.6 177.1 155.7 134.2 112.8 91.3 69.8   188.1 11.64 188.1 188.1 188.1 166.6 145.1 123.7 102.2 178.5 12.80 178.5 178.5 178.5 157.0 135.6 114.1 92.6   185.3 11.63 185.3 185.3 185.3 163.8 142.3 120.9 99.4 180.4 12.84 180.4 180.4 180.4 158.9 137.4 116.0 94.5   105°F   115°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   184.9 14.46 111.3 98.5 85.6 72.8 60.0   - - 173.7 15.93 106.8 94.0 81.2 68.3 55.5   - - 167.9 14.19 140.0 127.2 114.3 101.5 88.7 75.9 63.0 157.7 15.68 135.4 122.6 109.7 96.9 84.1 71.2 58.4   152.9 14.00 152.9 149.0 136.2 123.4 110.5 97.7 84.9 144.1 15.50 144.1 141.0 128.2 115.4 102.5 89.7 76.9   155.3 14.03 155.3 152.1 139.3 126.5 113.6 100.8 88.0 147.3 15.53 147.3 143.9 131.1 118.3 105.4 92.6 79.8   4500   5250   6000   6600   7200   189.7 14.51 123.4 108.2 93.1 77.9 62.7   - - 178.3 15.95 118.9 103.7 88.6 73.4 58.2   - - 172.3 14.24 154.6 139.5 124.3 109.1 94.0 78.8 63.6 161.8 15.70 150.1 134.9 119.8 104.6 89.4 74.3 59.1   156.9 14.05 156.9 155.0 148.1 132.9 117.7 102.6 87.4 147.8 15.52 147.8 146.3 139.9 124.8 109.6 94.4 79.3   159.4 14.08 159.4 157.8 151.4 136.2 121.1 105.9 90.8 151.2 15.55 151.2 149.5 143.1 127.9 112.7 97.6 82.4   194.6 14.56 135.5 118.0 100.5 83.0 65.5   - - 182.8 15.97 131.0 113.5 96.0 78.5 61.0   - - 176.7 14.29 169.2 151.7 134.2 116.7 99.3 81.8 64.3 166.0 15.72 164.8 147.3 129.8 112.3 94.8 77.3 59.8   160.9 14.09 160.9 160.9 159.9 142.4 124.9 107.4 89.9 151.6 15.54 151.6 151.6 151.6 134.1 116.6 99.1 81.6   163.5 14.13 163.5 163.5 163.5 146.0 128.5 111.0 93.5 155.0 15.56 155.0 155.0 155.0 137.5 120.0 102.6 85.1   199.3 14.65 145.7 126.3 106.8 87.3 67.8   - - 187.1 16.07 141.1 121.6 102.1 82.6 63.1   - - 180.9 14.38 177.2 162.1 142.6 123.1 103.7 84.2 64.7 169.9 15.82 169.3 157.5 138.1 118.6 99.1 79.6 60.1   164.8 14.18 164.8 164.8 164.3 144.8 125.3 105.8 86.3 155.2 15.64 155.2 155.2 155.2 135.7 116.2 96.8 77.3   167.4 14.21 167.4 167.4 167.4 148.0 128.5 109.0 89.5 158.7 15.66 158.7 158.7 158.7 139.2 119.7 100.3 80.8   203.9 14.74 156.0 134.5 113.1 91.6 70.1   - - 191.5 16.18 151.2 129.7 108.2 86.8 65.3   - - 185.2 14.47 185.2 172.5 151.0 129.5 108.1 86.6 65.2 173.8 15.93 173.8 167.8 146.3 124.9 103.4 81.9 60.5   168.6 14.27 168.6 168.6 168.6 147.2 125.7 104.2 82.8 158.8 15.74 158.8 158.8 158.8 137.3 115.9 94.4 72.9   171.4 14.30 171.4 171.4 171.4 149.9 128.4 107.0 85.5 162.4 15.77 162.4 162.4 162.4 140.9 119.4 98.0 76.5   125°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   162.5 17.41 102.4 89.5 76.7 63.9 51.0   - - 147.5 17.18 130.8 118.0 105.1 92.3 79.5 66.6 53.8   135.2 17.00 135.2 133.0 120.2 107.4 94.5 81.7 68.9   139.2 17.02 139.2 135.7 122.9 110.1 97.2 84.4 71.6   4500   5250   6000   6600   7200   166.8 17.40 114.4 99.2 84.1 68.9 53.7   - - 151.3 17.17 145.5 130.4 115.2 100.1 84.9 69.7 54.6   138.8 16.99 138.8 137.7 131.8 116.6 101.5 86.3 71.1   142.9 17.01 142.9 141.1 134.7 119.6 104.4 89.2 74.1   171.0 17.38 126.4 108.9 91.4 73.9 56.5   - - 155.2 17.16 155.2 142.8 125.3 107.8 90.3 72.8 55.3   142.3 16.98 142.3 142.3 142.3 125.9 108.4 90.9 73.4   146.6 17.00 146.6 146.6 146.6 129.1 111.6 94.1 76.6   175.0 17.50 136.4 116.9 97.4 77.9 58.5   - - 158.8 17.27 158.8 153.0 133.5 114.0 94.5 75.0 55.6   145.6 17.10 145.6 145.6 145.6 126.7 107.2 87.7 68.2   150.0 17.12 150.0 150.0 150.0 130.5 111.0 91.5 72.0   179.0 17.62 146.3 124.9 103.4 81.9 60.5   - - 162.4 17.38 162.4 162.4 141.7 120.2 98.7 77.3 55.8   148.9 17.21 148.9 148.9 148.9 127.5 106.0 84.5 63.1   153.4 17.23 153.4 153.4 153.4 131.9 110.4 89.0 67.5   1.   2.   The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower   Performance table for the kW of the supply air blower motor.   These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.   10   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 5: COOLING CAPACITIES FOR DJ210   Temperature of Air on Condenser Coil   Air on Evaporator Coil   85°F   95°F   2 Total Total2   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   80 77 74   Total Total   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   WB   (°F)   1 CFM   Cap.1 Input   (MBH) (kW) 86   Cap. Input   68 (MBH) (kW) 86   83   71   - 83   80   77   74   71   - 68   - 72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   238.9 14.24 142.6 125.5 108.4 91.3 74.2   - 222.9 15.81 136.5 119.4 102.3 85.2 68.1   221.2 13.83 178.6 161.5 144.4 127.3 110.2 93.1 76.0 207.1 15.38 172.8 155.7 138.6 121.5 104.4 87.2 70.1   207.4 13.57 207.4 192.8 175.7 158.5 141.4 124.3 107.2 197.6 15.09 197.6 181.0 163.8 146.7 129.6 112.5 95.4   197.6 13.52 197.6 195.7 178.6 161.4 144.3 127.2 110.1 186.0 15.06 186.0 181.8 164.7 147.6 130.5 113.4 96.3   6000   246.1 14.36 154.5 135.8 117.0 98.3 79.5   - - 231.8 15.91 149.7 130.9 112.2 93.4 74.6   - - 227.9 13.95 193.5 174.7 156.0 137.2 118.4 99.7 80.9 215.4 15.48 189.4 170.7 151.9 133.2 114.4 95.6 76.9   213.7 13.69 213.7 206.4 189.7 170.9 152.2 133.4 114.6 205.5 15.19 205.5 197.1 179.6 160.9 142.1 123.4 104.6   203.6 13.64 203.6 202.6 192.8 174.1 155.3 136.5 117.8 193.5 15.15 193.5 191.3 180.6 161.8 143.1 124.3 105.5   6500   7000   7875   8750   253.4 14.48 166.5 146.1 125.7 105.3 84.9   - - 240.7 16.00 162.8 142.4 122.0 101.6 81.2   - - 234.6 14.06 208.3 187.9 167.5 147.1 126.7 106.3 85.9 223.6 15.57 206.1 185.7 165.3 144.8 124.4 104.0 83.6   220.0 13.80 220.0 220.0 203.7 183.3 162.9 142.5 122.1 213.3 15.28 213.3 213.3 195.4 175.0 154.6 134.2 113.8   209.6 13.75 209.6 209.6 207.1 186.7 166.2 145.8 125.4 200.9 15.24 200.9 200.9 196.4 176.0 155.6 135.2 114.8   258.4 14.56 180.9 157.6 134.4 111.2 87.9   - - 243.3 16.09 176.8 153.6 130.3 107.1 83.8   - - 239.3 14.14 225.6 202.4 179.1 155.9 132.6 109.4 86.1 226.0 15.65 217.3 199.8 176.5 153.3 130.0 106.8 83.5   224.4 13.88 224.4 224.4 216.2 193.0 169.7 146.5 123.2 215.6 15.36 215.6 215.6 206.7 183.4 160.2 136.9 113.7   213.8 13.82 213.8 213.8 212.5 189.2 166.0 142.8 119.5 203.0 15.32 203.0 203.0 200.8 177.6 154.3 131.1 107.8   263.5 14.63 195.3 169.2 143.1 117.0 91.0   - - 245.9 16.17 190.8 164.7 138.7 112.6 86.5   - - 243.9 14.21 242.9 216.8 190.7 164.7 138.6 112.5 86.4 228.4 15.73 228.4 213.9 187.8 161.7 135.6 109.5 83.5   228.7 13.95 228.7 228.7 228.7 202.6 176.6 150.5 124.4 217.9 15.43 217.9 217.9 217.9 191.8 165.8 139.7 113.6   217.9 13.90 217.9 217.9 217.9 191.8 165.8 139.7 113.6 205.2 15.40 205.2 205.2 205.2 179.1 153.0 126.9 100.9   105°F   115°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   210.2 17.65 131.0 113.9 96.8 79.7 62.6   - - 197.6 19.49 125.5 108.3 91.2 74.1 57.0   - - 195.1 17.21 167.5 150.4 133.3 116.2 99.1 82.0 64.9 183.1 19.04 162.2 145.1 128.0 110.9 93.8 76.7 59.6   186.9 17.01 186.9 170.6 153.5 136.4 119.3 102.2 85.1 176.3 18.92 176.3 160.2 143.1 126.0 108.9 91.8 74.7   174.4 16.80 174.4 172.3 155.2 138.1 121.0 103.9 86.8 162.8 18.55 162.8 162.8 145.7 128.6 111.5 94.4 77.3   6000   6500   7000   7875   8750   218.3 17.77 143.8 125.0 106.3 87.5 68.7   - - 204.8 19.63 137.9 119.1 100.3 81.6 62.8   - - 202.6 17.33 183.9 165.1 146.4 127.6 108.8 90.1 71.3 189.9 19.18 178.3 159.5 140.8 122.0 103.3 84.5 65.8   194.1 17.12 194.1 186.0 168.5 149.8 131.0 112.2 93.5 182.8 19.06 182.8 174.8 157.4 138.6 119.9 101.1 82.4   181.1 16.92 181.1 180.1 170.4 151.7 132.9 114.1 95.4 168.8 18.69 168.8 168.8 160.3 141.5 122.8 104.0 85.2   226.4 17.89 156.6 136.2 115.7 95.3 74.9   - - 212.1 19.77 150.3 129.9 109.5 89.0 68.6   - - 210.1 17.45 200.2 179.8 159.4 139.0 118.6 98.2 77.8 196.6 19.32 194.4 174.0 153.6 133.2 112.7 92.3 71.9   201.3 17.24 201.3 201.3 183.6 163.1 142.7 122.3 101.9 189.3 19.20 189.3 189.3 171.7 151.3 130.9 110.5 90.0   187.8 17.03 187.8 187.8 185.6 165.2 144.8 124.4 104.0 174.8 18.82 174.8 174.8 174.8 154.4 134.0 113.6 93.2   228.5 17.97 171.3 148.0 124.8 101.5 78.3   - - 213.7 19.85 165.7 142.5 119.2 96.0 72.7   - - 212.1 17.53 207.1 193.3 171.9 148.6 125.4 102.2 78.9 198.1 19.40 197.0 186.8 167.3 144.0 120.8 97.5 74.3   203.2 17.32 203.2 203.2 194.3 171.0 147.8 124.5 101.3 190.7 19.28 190.7 190.7 181.9 158.6 135.4 112.1 88.9   189.6 17.11 189.6 189.6 188.5 165.2 142.0 118.7 95.5 176.1 18.90 176.1 176.1 176.1 152.9 129.6 106.4 83.1   230.6 18.05 186.0 159.9 133.8 107.7 81.7   - - 215.2 19.94 181.1 155.1 129.0 102.9 76.8   - - 214.0 17.61 214.0 206.7 184.4 158.3 132.2 106.1 80.0 199.5 19.48 199.5 199.5 181.0 154.9 128.8 102.7 76.6   205.0 17.40 205.0 205.0 205.0 178.9 152.8 126.8 100.7 192.1 19.36 192.1 192.1 192.1 166.0 139.9 113.8 87.8   191.3 17.19 191.3 191.3 191.3 165.2 139.1 113.0 87.0 177.4 18.98 177.4 177.4 177.4 151.3 125.2 99.1 73.1   125°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   184.9 21.33 119.9 102.8 85.7 68.6 51.5   - - 171.1 20.87 156.9 139.8 122.7 105.6 88.5 71.4 54.3   165.7 20.84 165.7 149.9 132.7 115.6 98.5 81.4 64.3   151.2 20.30 151.2 151.2 136.2 119.1 102.0 84.9 67.8   6000   6500   7000   7875   8750   191.4 21.49 132.0 113.2 94.4 75.7 56.9   - - 177.1 21.03 172.7 154.0 135.2 116.5 97.7 79.0 60.2   171.5 21.00 171.5 163.6 146.3 127.5 108.8 90.0 71.3   156.5 20.46 156.5 156.5 150.1 131.4 112.6 93.8 75.1   197.8 21.65 144.0 123.6 103.2 82.8 62.3   - - 183.1 21.19 183.1 168.1 147.7 127.3 106.9 86.5 66.1   177.3 21.16 177.3 177.3 159.8 139.4 119.0 98.6 78.2   161.8 20.61 161.8 161.8 161.8 143.6 123.2 102.8 82.4   198.9 21.74 160.2 136.9 113.7 90.4 67.2   - - 184.1 21.27 184.1 180.2 162.6 139.4 116.2 92.9 69.7   178.2 21.24 178.2 178.2 169.5 146.3 123.0 99.8 76.5   162.6 20.69 162.6 162.6 162.6 140.5 117.3 94.0 70.8   199.9 21.82 176.3 150.2 124.2 98.1 72.0   - - 185.1 21.35 185.1 185.1 177.6 151.5 125.4 99.3 73.2   179.2 21.32 179.2 179.2 179.2 153.1 127.0 100.9 74.8   163.5 20.77 163.5 163.5 163.5 137.4 111.3 85.2 59.2   1.   2.   The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower   Performance table for the kW of the supply air blower motor.   These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.   Johnson Controls Unitary Products   11   
			
				  
				
					261660-YTG-D-0708   TABLE 6: COOLING CAPACITIES FOR DJ240   Temperature of Air on Condenser Coil   Air on Evaporator Coil   85°F   95°F   2 Total Total2   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   80 77 74   Total Total   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   WB   (°F)   1 CFM   Cap.1 Input   (MBH) (kW) 86   Cap. Input   68 (MBH) (kW) 86   83   71   - 83   80   77   74   71   - 68   - 72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   273.1 16.90 149.8 132.7 115.6 98.5 81.4   - 257.3 18.45 150.2 133.1 116.0 98.9 81.8   248.6 16.43 197.6 180.5 163.4 146.3 129.1 112.0 94.9 237.3 17.83 192.3 175.1 158.0 140.9 123.8 106.7 89.6   231.2 16.44 227.9 210.8 193.7 176.6 159.5 142.4 125.3 215.2 17.64 215.2 200.8 183.7 166.6 149.5 132.4 115.3   216.6 15.98 216.6 210.2 193.1 176.0 158.9 141.8 124.7 221.2 17.98 221.2 213.2 196.1 179.0 161.8 144.7 127.6   6000   278.7 16.96 165.8 145.6 125.4 105.1 84.9   - - 264.7 18.51 167.2 146.9 126.7 106.5 86.3   - - 253.8 16.49 217.5 197.3 177.1 156.9 136.7 116.5 96.2 244.2 17.89 213.1 192.9 172.7 152.4 132.2 112.0 91.8   236.0 16.50 234.4 225.8 210.0 189.8 169.6 149.4 129.2 221.5 17.70 221.5 214.3 200.7 180.5 160.3 140.0 119.8   221.1 16.04 221.1 217.9 209.3 189.1 168.9 148.7 128.5 227.6 18.04 227.6 223.6 214.2 194.0 173.8 153.5 133.3   7000   8000   8700   9400   284.4 17.02 181.8 158.4 135.1 111.8 88.4   - - 272.2 18.58 184.1 160.8 137.4 114.1 90.8   - - 259.0 16.55 237.5 214.2 190.9 167.5 144.2 120.9 97.6 251.0 17.95 233.9 210.6 187.3 164.0 140.6 117.3 94.0   240.8 16.56 240.8 240.8 226.3 203.0 179.7 156.4 133.0 227.7 17.76 227.7 227.7 217.7 194.4 171.0 147.7 124.4   225.6 16.10 225.6 225.6 225.6 202.3 178.9 155.6 132.3 234.0 18.10 234.0 234.0 232.3 209.0 185.7 162.4 139.0   291.0 17.43 193.1 167.5 141.8 116.1 90.4   - - 277.5 18.98 195.6 169.9 144.2 118.5 92.9   - - 265.0 16.95 251.7 226.0 200.3 174.7 149.0 123.3 97.6 256.0 18.33 247.4 222.2 196.5 170.8 145.2 119.5 93.8   246.4 16.96 246.4 246.4 237.6 211.9 186.2 160.5 134.9 232.2 18.14 232.2 232.2 227.2 201.5 175.8 150.1 124.5   230.8 16.49 230.8 230.8 230.8 205.2 179.5 153.8 128.1 238.6 18.50 238.6 238.6 237.7 212.1 186.4 160.7 135.0   297.7 17.84 204.5 176.5 148.5 120.5 92.4   - - 282.9 19.38 207.0 179.0 151.0 123.0 94.9   - - 271.0 17.35 265.8 237.8 209.8 181.8 153.7 125.7 97.7 260.9 18.72 260.9 233.7 205.7 177.7 149.7 121.7 93.6   252.0 17.36 252.0 252.0 248.8 220.7 192.7 164.7 136.7 236.6 18.53 236.6 236.6 236.6 208.6 180.6 152.6 124.6   236.1 16.88 236.1 236.1 236.1 208.1 180.1 152.0 124.0 243.2 18.89 243.2 243.2 243.2 215.1 187.1 159.1 131.1   105°F   115°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   244.1 20.09 146.5 129.4 112.3 95.2 78.1   - - 230.8 21.72 142.8 125.7 108.6 91.5 74.4   - - 225.3 19.63 186.7 169.6 152.5 135.4 118.3 101.2 84.1 213.4 21.43 181.2 164.1 147.0 129.9 112.8 95.7 78.6   202.7 19.37 202.7 194.9 177.7 160.6 143.5 126.4 109.3 190.2 21.09 190.2 188.9 171.8 154.7 137.6 120.5 103.4   211.7 19.63 211.7 205.7 188.6 171.5 154.4 137.3 120.2 202.2 21.28 202.2 198.2 181.1 164.0 146.9 129.8 112.7   6000   7000   8000   8700   9400   250.6 20.15 162.5 142.2 122.0 101.8 81.6   - - 236.4 21.79 157.8 137.5 117.3 97.1 76.9   - - 231.3 19.69 206.2 185.9 165.7 145.5 125.3 105.1 84.9 218.5 21.50 199.2 179.0 158.8 138.6 118.4 98.1 77.9   208.1 19.43 208.1 204.2 193.1 172.9 152.7 132.5 112.3 194.8 21.16 194.8 194.1 185.6 165.4 145.1 124.9 104.7   217.3 19.70 217.3 214.3 204.9 184.7 164.5 144.3 124.1 207.0 21.35 207.0 205.1 195.7 175.4 155.2 135.0 114.8   257.0 20.22 178.4 155.1 131.7 108.4 85.1   - - 241.9 21.87 172.7 149.4 126.0 102.7 79.4   - - 237.3 19.76 225.6 202.3 178.9 155.6 132.3 109.0 85.6 223.6 21.58 217.3 193.9 170.6 147.3 123.9 100.6 77.3   213.5 19.50 213.5 213.5 208.5 185.2 161.9 138.5 115.2 199.4 21.24 199.4 199.4 199.4 176.0 152.7 129.4 106.1   222.9 19.77 222.9 222.9 221.3 197.9 174.6 151.3 128.0 211.9 21.43 211.9 211.9 210.2 186.9 163.5 140.2 116.9   264.1 20.56 191.3 165.6 139.9 114.3 88.6   - - 250.6 22.15 187.0 161.3 135.6 110.0 84.3   - - 243.8 20.09 238.0 215.7 190.0 164.4 138.7 113.0 87.3 231.7 21.85 228.5 209.3 183.6 157.9 132.2 106.6 80.9   219.4 19.83 219.4 219.4 216.9 191.2 165.5 139.8 114.2 206.6 21.51 206.6 206.6 206.6 180.9 155.2 129.5 103.9   229.0 20.10 229.0 229.0 228.2 202.5 176.9 151.2 125.5 219.5 21.70 219.5 219.5 218.7 193.0 167.3 141.7 116.0   271.1 20.91 204.1 176.1 148.1 120.1 92.1   - - 259.4 22.43 201.3 173.3 145.2 117.2 89.2   - - 250.3 20.43 250.3 229.2 201.1 173.1 145.1 117.1 89.1 239.7 22.13 239.7 224.6 196.6 168.6 140.5 112.5 84.5   225.2 20.16 225.2 225.2 225.2 197.2 169.2 141.1 113.1 213.8 21.78 213.8 213.8 213.8 185.7 157.7 129.7 101.7   235.2 20.43 235.2 235.2 235.2 207.1 179.1 151.1 123.1 227.2 21.98 227.2 227.2 227.2 199.2 171.1 143.1 115.1   125°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   217.6 23.35 139.1 122.0 104.9 87.8 70.7   - - 201.4 23.23 175.7 158.6 141.5 124.4 107.3 90.2 73.1   177.7 22.82 177.7 177.7 165.8 148.7 131.6 114.5 97.4   192.7 22.93 192.7 190.8 173.7 156.5 139.4 122.3 105.2   6000   7000   8000   8700   9400   222.2 23.43 153.1 132.8 112.6 92.4 72.2   - - 205.6 23.31 192.3 172.1 151.9 131.7 111.4 91.2 71.0   181.5 22.90 181.5 181.5 178.0 157.8 137.6 117.4 97.1   196.8 23.01 196.8 195.8 186.4 166.2 146.0 125.7 105.5   226.8 23.51 167.0 143.7 120.3 97.0 73.7   - - 209.9 23.39 208.9 185.6 162.3 138.9 115.6 92.3 68.9   185.2 22.98 185.2 185.2 185.2 166.9 143.5 120.2 96.9   200.8 23.09 200.8 200.8 199.1 175.8 152.5 129.1 105.8   237.2 23.74 182.7 157.0 131.3 105.7 80.0   - - 219.5 23.61 219.0 202.8 177.1 151.5 125.8 100.1 74.4   193.7 23.19 193.7 193.7 193.7 170.6 144.9 119.2 93.6   210.0 23.30 210.0 210.0 209.2 183.5 157.8 132.1 106.5   247.6 23.96 198.4 170.4 142.4 114.3 86.3   - - 229.1 23.84 229.1 220.0 192.0 164.0 136.0 107.9 79.9   202.3 23.41 202.3 202.3 202.3 174.3 146.3 118.2 90.2   219.2 23.52 219.2 219.2 219.2 191.2 163.2 135.1 107.1   1.   2.   The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower   Performance table for the kW of the supply air blower motor.   These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.   12   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 7: COOLING CAPACITIES FOR DJ300   Temperature of Air on Condenser Coil   Air on Evaporator Coil   85°F   95°F   2 Total Total2   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   80 77 74   Total Total   Sensible Capacity (MBH)*   Return Dry Bulb (°F)   WB   (°F)   1 CFM   Cap.1 Input   (MBH) (kW) 86   Cap. Input   68 (MBH) (kW) 86   83   71   - 83   80   77   74   71   - 68   - 72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   332.2 21.58 206.4 185.0 163.6 142.3 120.9   - 324.4 25.42 191.5 170.2 148.8 127.4 106.0   327.2 21.26 256.1 234.7 213.3 192.0 170.6 149.2 127.8 305.5 24.73 245.9 224.5 203.1 181.7 160.4 139.0 117.6   321.0 20.60 320.3 298.9 277.5 256.1 234.7 213.4 192.0 301.1 24.23 295.5 274.2 252.8 231.4 210.0 188.6 167.2   313.6 20.57 313.6 305.9 284.5 263.1 241.8 220.4 199.0 292.2 24.07 292.2 277.1 255.7 234.3 212.9 191.5 170.1   7500   329.6 22.39 217.2 191.9 166.6 141.4 116.1   - - 326.8 25.46 207.5 182.3 157.0 131.7 106.4   - - 324.6 22.06 267.8 242.5 217.3 192.0 166.7 141.4 116.2 307.7 24.76 264.9 239.6 214.4 189.1 163.8 138.5 113.3   318.4 21.37 318.0 307.3 282.6 257.3 232.0 206.8 181.5 303.3 24.26 300.5 289.8 266.7 241.5 216.2 190.9 165.7   311.1 21.34 311.1 307.2 289.7 264.5 239.2 213.9 188.6 294.3 24.10 294.3 286.7 269.8 244.5 219.3 194.0 168.7   8750   10000   11250   12500   326.9 23.20 228.0 198.8 169.6 140.5 111.3   - - 329.1 25.49 223.5 194.4 165.2 136.1 106.9   - - 321.9 22.86 279.5 250.3 221.2 192.0 162.8 133.7 104.5 309.9 24.79 283.9 254.7 225.6 196.4 167.3 138.1 108.9   315.8 22.15 315.8 315.8 287.7 258.5 229.4 200.2 171.0 305.5 24.29 305.5 305.5 280.7 251.6 222.4 193.2 164.1   308.5 22.12 308.5 308.5 294.9 265.8 236.6 207.5 178.3 296.4 24.13 296.4 296.4 283.9 254.8 225.6 196.5 167.3   333.6 23.42 241.2 208.0 174.8 141.6 108.4   - - 336.1 25.73 238.9 205.7 172.5 139.3 106.1   - - 328.6 23.07 294.3 261.1 227.9 194.7 161.5 128.3 95.1 316.4 25.02 302.0 268.8 235.5 202.3 169.1 135.9 102.7   322.3 22.35 322.3 322.3 296.5 263.3 230.0 196.8 163.6 311.9 24.52 311.9 311.9 293.1 259.9 226.7 193.5 160.3   314.9 22.32 314.9 314.9 304.0 270.7 237.5 204.3 171.1 302.7 24.36 302.7 302.7 296.5 263.2 230.0 196.8 163.6   340.4 23.63 254.5 217.3 180.0 142.7 105.5   - - 343.1 25.96 254.3 217.1 179.8 142.5 105.3   - - 335.2 23.28 309.2 271.9 234.7 197.4 160.2 122.9 85.6 323.0 25.25 320.0 282.8 245.5 208.2 171.0 133.7 96.5   328.8 22.55 328.8 328.8 305.2 268.0 230.7 193.5 156.2 318.4 24.74 318.4 318.4 305.5 268.2 231.0 193.7 156.5   321.3 22.53 321.3 321.3 313.0 275.7 238.4 201.2 163.9 309.0 24.58 309.0 309.0 309.0 271.7 234.4 197.2 159.9   105°F   115°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   301.8 27.73 184.5 163.2 141.8 120.4 99.0   - - 279.1 30.03 177.6 156.2 134.8 113.4 92.0   - - 289.0 27.27 238.8 217.4 196.0 174.6 153.2 131.9 110.5 272.6 29.81 231.6 210.3 188.9 167.5 146.1 124.7 103.3   283.6 26.57 280.8 259.7 238.3 216.9 195.5 174.1 152.7 266.0 28.91 266.0 245.2 223.8 202.4 181.0 159.6 138.3   271.5 26.43 271.5 260.3 238.9 217.6 196.2 174.8 153.4 250.9 28.79 250.9 243.6 222.2 200.8 179.4 158.1 136.7   7500   8750   306.8 27.83 201.3 176.1 150.8 125.5 100.2   - - 286.9 30.20 195.1 169.8 144.6 119.3 94.0   - - 293.9 27.37 259.0 233.7 208.5 183.2 157.9 132.7 107.4 280.1 29.98 253.1 227.9 202.6 177.3 152.0 126.8 101.5   288.3 26.67 286.9 276.4 253.4 228.1 202.8 177.6 152.3 273.3 29.07 273.3 262.9 240.0 214.8 189.5 164.2 138.9   276.1 26.53 276.1 270.5 254.1 228.8 203.5 178.3 153.0 257.9 28.96 257.9 254.2 238.3 213.1 187.8 162.5 137.3   311.8 27.93 218.1 188.9 159.8 130.6 101.5   - - 294.6 30.38 212.7 183.5 154.4 125.2 96.0   - - 298.7 27.47 279.3 250.1 220.9 191.8 162.6 133.5 104.3 287.6 30.16 274.6 245.5 216.3 187.1 158.0 128.8 99.7   293.1 26.77 293.1 293.1 268.5 239.3 210.2 181.0 151.9 280.7 29.24 280.7 280.7 256.3 227.1 198.0 168.8 139.6   280.6 26.63 280.6 280.6 269.2 240.0 210.9 181.7 152.6 264.8 29.13 264.8 264.8 254.5 225.3 196.2 167.0 137.8   10000   11250   12500   318.7 28.19 233.1 199.9 166.7 133.5 100.3   - - 301.4 30.66 227.3 194.1 160.9 127.7 94.5   - - 305.4 27.73 294.9 263.7 230.5 197.3 164.1 130.9 97.7 294.3 30.44 287.8 258.7 225.5 192.3 159.1 125.9 92.7   299.6 27.02 299.6 299.6 280.1 246.9 213.7 180.5 147.3 287.2 29.52 287.2 287.2 267.2 234.0 200.8 167.6 134.3   286.8 26.88 286.8 286.8 280.9 247.7 214.5 181.2 148.0 270.9 29.40 270.9 270.9 265.3 232.1 198.9 165.7 132.5   325.6 28.46 248.2 210.9 173.6 136.4 99.1   - - 308.2 30.95 242.0 204.8 167.5 130.2 93.0   - - 312.0 27.99 310.5 277.4 240.1 202.8 165.6 128.3 91.1 300.9 30.72 300.9 272.0 234.7 197.4 160.2 122.9 85.7   306.0 27.27 306.0 306.0 291.8 254.5 217.3 180.0 142.8 293.6 29.79 293.6 293.6 278.1 240.8 203.6 166.3 129.0   293.0 27.13 293.0 293.0 292.5 255.3 218.0 180.8 143.5 277.0 29.68 277.0 277.0 276.1 238.9 201.6 164.3 127.1   125°F   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   72   67   62   57   256.5 32.33 170.6 149.2 127.8 106.4 85.0   - - 256.1 32.35 224.5 203.1 181.8 160.4 139.0 117.6 96.2   248.4 31.25 248.4 230.7 209.3 187.9 166.5 145.2 123.8   230.3 31.16 230.3 226.9 205.5 184.1 162.7 141.3 120.0   7500   8750   266.9 32.57 188.9 163.6 138.4 113.1 87.8   - - 266.3 32.60 247.2 222.0 196.7 171.4 146.2 120.9 95.6   258.4 31.48 258.4 249.5 226.7 201.4 176.1 150.9 125.6   239.7 31.39 239.7 237.9 222.6 197.3 172.1 146.8 121.5   277.3 32.82 207.3 178.1 148.9 119.8 90.6   - - 276.5 32.84 270.0 240.8 211.7 182.5 153.3 124.2 95.0   268.3 31.71 268.3 268.3 244.1 214.9 185.7 156.6 127.4   249.0 31.63 249.0 249.0 239.7 210.6 181.4 152.3 123.1   10000   11250   12500   284.0 33.13 221.6 188.3 155.1 121.9 88.7   - - 283.2 33.15 280.7 253.7 220.5 187.3 154.1 120.8 87.6   274.8 32.01 274.8 274.8 254.2 221.0 187.8 154.6 121.4   255.0 31.92 255.0 255.0 249.7 216.5 183.3 150.1 116.9   290.7 33.44 235.9 198.6 161.3 124.1 86.8   - - 289.8 33.46 289.8 266.6 229.3 192.0 154.8 117.5 80.3   281.3 32.32 281.3 281.3 264.4 227.1 189.9 152.6 115.3   261.0 32.22 261.0 261.0 259.7 222.4 185.2 147.9 110.7   1.   2.   The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower   Performance table for the kW of the supply air blower motor.   These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.   Johnson Controls Unitary Products   13   
			
				  
				
					261660-YTG-D-0708   order to use the indoor blower tables for high altitude applica-   tions, certain corrections are necessary.   CFM, STATIC PRESSURE, AND POWER - ALTI-   TUDE AND TEMPERATURE CORRECTIONS   A centrifugal fan is a "constant volume" device. This means   that, if the rpm remains constant, the CFM delivered is the   same regardless of the density of the air. However, since the   air at high altitude is less dense, less static pressure will be   generated and less power will be required than a similar   application at sea level. Air density correction factors are   The information below should be used to assist in application   of product when being applied at altitudes at or exceeding   1000 feet above sea level.   The air flow rates listed in the standard blower performance   tables are based on standard air at sea level. As the altitude   or temperature increases, the density of air decreases. In   TABLE 8: ALTITUDE CORRECTION FACTORS   ALTITUDE (FEET)   AIR TEMP   0 1000   1.022   1.002   0.982   0.964   0.947   0.929   0.912   2000   0.986   0.966   0.948   0.930   0.913   0.897   0.880   3000   0.950   0.931   0.913   0.896   0.880   0.864   0.848   4000   0.916   0.898   0.880   0.864   0.848   0.833   0.817   5000   0.882   0.864   0.848   0.832   0.817   0.802   0.787   6000   0.849   0.832   0.816   0.801   0.787   0.772   0.758   7000   0.818   0.802   0.787   0.772   0.758   0.744   0.730   8000   0.788   0.772   0.757   0.743   0.730   0.716   0.703   9000   0.758   0.743   0.729   0.715   0.702   0.689   0.676   10000   0.729   0.715   0.701   0.688   0.676   0.663   0.651   40   50   1.060   1.039   1.019   1.000   0.982   0.964   0.946   60   70   80   90   100   The examples below will assist in determining the airflow per-   formance of the product at altitude.   blower tables to select the blower speed and the BHP   requirement.   Example 1: What are the corrected CFM, static pressure,   and BHP at an elevation of 5,000 ft. if the blower performance   data is 6,000 CFM, 1.5 IWC and 4.0 BHP?   Solution: As in the example above, no temperature informa-   tion is given so 70°F is assumed.   The 1.5" static pressure given is at an elevation of 5,000 ft.   The first step is to convert this static pressure to equivalent   sea level conditions.   Solution: At an elevation of 5,000 ft the indoor blower will still   deliver 6,000 CFM if the rpm is unchanged. However, Table   8 must be used to determine the static pressure and BHP.   Since no temperature data is given, we will assume an air   temperature of 70°F. Table 8 shows the correction factor to   be 0.832.   Sea level static pressure = 1.5 / .832 = 1.80"   Enter the blower table at 6000 sCFM and static pressure of   1.8". The rpm listed will be the same rpm needed at 5,000 ft.   Corrected static pressure = 1.5 x 0.832 = 1.248 IWC   Corrected BHP = 4.0 x 0.832 = 3.328   Suppose that the corresponding BHP listed in the table is 3.2.   This value must be corrected for elevation.   Example 2: A system, located at 5,000 feet of elevation, is to   BHP at 5,000 ft = 3.2 x .832 = 2.66   deliver 6,000 CFM at a static pressure of 1.5". Use the unit   14   Johnson Controls Unitary Products   
			
			
				
					261660-YTG-D-0708   FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR   Johnson Controls Unitary Products   15   
			
				  
				
					261660-YTG-D-0708   TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY   180 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   6000   BHP   BLOWER   SPEED,   (RPM)   4500   BHP   5250   BHP   6750   BHP   7200   BHP   ESP   KW   ESP   KW   ESP   KW   ESP   KW   ESP   KW   208 VOLT AND STANDARD DRIVE   850   870   6.0**   5.5   4.5   3.5   3.0   2.0   1.0   0.9   1.0   1.1   1.2   1.3   1.4   1.5   2.4   2.5   2.6   2.9   3.0   3.1   3.2   2.2   2.3   2.4   2.6   2.7   2.8   2.9   0.7   0.8   0.9   1.0   1.1   1.2   1.3   3.0   3.1   3.4   3.6   3.7   3.8   3.9   2.7   2.8   3.0   3.2   3.3   3.4   3.5   0.5   0.6   0.7   0.8   0.9   1.0   1.1   3.2   3.5   3.7   4.0   4.1   4.2   4.5   2.9   3.1   3.3   3.6   3.7   3.8   4.0   - - - - - - 0.2   0.3   0.5   0.6   0.7   0.9   4.1   4.4   4.7   4.8.   5.0   5.2   3.7   3.9   4.2   4.3   4.5   4.7   - - - 915   0.2   0.4   0.5   0.6   0.7   4.5   4.9   5.1   5.4   5.7   4.0   4.4   4.6   4.8   5.1   965   980   1010   1040   208 VOLT AND HIGH STATIC DRIVE   965   980   6.0   5.5   4.5   3.5   3.0   2.0   1.0   1.2   1.3   1.5   1.6   1.7   1.9   2.1   2.9   3.0   3.2   3.4   3.5   3.7   3.9   2.6   2.7   2.9   3.0   3.1   3.3   3.5   1.0   1.1   1.3   1.4   1.5   1.7   2.0   3.6   3.7   3.9   4.0   4.2   4.5   4.7   3.2   3.3   3.5   3.6   3.8   4.0   4.2   0.8   0.9   1.1   1.2   1.3   1.5   1.8   4.0   4.1   4.5   4.7   4.9   5.1   5.5   3.6   3.7   4.0   4.2   4.4   4.6   4.9   0.5   0.6   0.8   1.0   1.2   - 4.7   4.8   5.1   5.5   5.7   - 4.2   4.3   4.6   4.9   5.1   - 0.4   5.0   4.4   0.5   5.1   4.6   1025   1065   1095   1130   1170   0.7   5.6   5.0   - - - - - - - - - - - - - - - 230/460/575 VOLT AND STANDARD DRIVE   870   915   6.0**   5.0   4.0   3.5   2.0   1.0   1.0   1.1   1.2   1.3   1.5   1.6   2.4   2.6   2.9   3.0   3.2   3.3   2.2   2.4   2.6   2.7   2.9   3.0   0.8   0.9   1.0   1.1   1.3   1.4   3.1   3.3   3.6   3.7   3.9   4.0   2.8   3.0   3.2   3.3   3.5   3.6   0.6   0.7   0.8   0.9   1.1   1.2   3.5   3.7   4.0   4.1   4.5   4.7   3.1   3.3   3.6   3.7   4.0   4.2   0.2   0.3   0.5   0.6   0.9   1.0   4.1   4.4   4.7   4.8   5.3   5.5   3.7   3.9   4.2   4.3   4.7   4.9   - - - 0.2   0.4   0.5   0.7   - 4.5   5.0   5.1   5.7   - 4.0   4.4   4.6   5.1   - 965   980   1040   1065   230/460/575 VOLT AND HIGH STATIC DRIVE   980   6.0   4.5   4.0   3.5   2.5   1.5   1.0   1.3   1.5   1.6   1.7   1.9   2.1   2.2   2.9   3.2   3.4   3.5   3.7   3.9   4.0   2.6   2.9   3.0   3.1   3.3   3.5   3.6   1.1   1.3   1.4   1.5   1.7   2.0   2.1   3.7   3.9   4.0   4.2   4.5   4.7   4.8   3.3   3.5   3.6   3.8   4.0   4.2   4.3   0.9   1.1   1.2   1.3   1.5   1.8   2.0   4.1   4.5   4.7   4.9   5.1   5.5   5.7   3.7   4.0   4.2   4.4   4.6   4.9   5.1   0.6   0.9   1.0   1.2   - 4.8   5.3   5.5   5.7   - 4.3   4.7   4.9   5.1   - 0.5   5.1   4.6   1040   1065   1095   1130   1170   1190   0.7   5.7   5.1   - - - - - - - - - - - - - - - - - - - - - NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.   2.Refer to Table 13 for additional static resistances.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   16   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY   210 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   BLOWER   SPEED,   (RPM)   6000   BHP   7000   BHP   8000   BHP   9000   ESP   KW   ESP   KW   ESP   KW   ESP   BHP   KW   208 VOLT AND STANDARD DRIVE   870   900   930   950   980   1015   6.0**   5.0   4.0   3.0   2.0   1.0   0.4   0.8   1.1   1.3   1.6   1.9   2.1   3.2   4.1   4.6   5.3   5.9   1.8   2.7   3.4   3.9   4.5   5.0   0.1   0.5   0.9   1.1   1.4   1.7   2.3   3.5   4.5   5.1   5.8   6.5   2.0   2.9   3.8   4.3   4.9   5.5   - - - - - - 0.2   0.6   0.8   1.2   1.5   3.8   4.9   5.5   6.3   7.0   3.2   4.1   4.6   5.3   5.9   - - - 0.1   0.4   0.7   1.0   5.1   5.9   6.9   7.7   4.3   5.0   5.8   6.5   208 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.0   3.5   3.0   2.5   2.0   1.0   1.3   1.6   1.8   1.9   2.0   2.1   2.3   2.4   4.6   5.3   5.8   6.1   6.2   6.4   6.6   6.7   3.9   4.5   4.9   5.1   5.2   5.4   5.5   5.6   1.1   1.4   1.7   1.8   1.9   2.0   2.1   2.2   5.1   5.8   6.3   6.5   6.8   7.0   7.2   7.3   4.3   4.9   5.3   5.5   5.7   5.9   6.0   6.1   0.8   1.2   1.5   1.6   1.7   1.8   1.9   2.1   5.5   6.3   6.9   7.1   7.4   7.6   7.8   7.9   4.6   5.3   5.8   6.0   6.2   6.4   6.6   6.7   0.4   0.7   1.0   1.1   1.2   1.3   1.5   - 5.9   6.9   7.5   7.8   8.1   8.3   8.6   - 5.0   5.8   6.3   6.6   6.8   7.0   7.2   - 1010   1020   1035   1050   1075   1100   230/460/575 VOLT AND STANDARD DRIVE   870   900   6.0**   5.0   4.0   3.5   2.5   1.5   1.0   0.4   0.8   1.1   1.3   1.6   1.9   2.0   2.1   3.2   4.1   4.6   5.3   5.9   6.1   1.8   2.7   3.4   3.9   4.5   5.0   5.1   0.1   0.5   0.9   1.1   1.4   1.7   1.8   2.3   3.5   4.5   5.1   5.8   6.5   6.6   2.0   2.9   3.8   4.3   4.9   5.5   5.6   - - - - - - 0.2   0.6   0.8   1.2   1.5   1.6   3.8   4.9   5.5   6.3   7.0   7.3   3.2   4.1   4.6   5.3   5.9   6.1   - - - 930   0.1   0.4   0.7   1.0   1.1   5.1   5.9   6.9   7.7   7.9   4.3   5.0   5.8   6.5   6.7   950   980   1015   1025   230/460/575 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.0   3.5   3.0   2.0   1.5   1.0   1.3   1.6   1.9   2.0   2.1   2.3   2.4   2.5   4.6   5.3   5.9   6.2   6.4   6.6   6.7   6.8   3.9   4.5   5.0   5.2   5.4   5.5   5.6   5.7   1.1   1.4   1.7   1.9   2.0   2.1   2.2   2.3   5.1   5.8   6.5   6.8   7.0   7.2   7.3   7.4   4.3   4.9   5.5   5.7   5.9   6.0   6.1   6.2   0.8   1.2   1.5   1.7   1.8   1.9   2.1   2.2   5.5   6.3   7.0   7.4   7.6   7.8   7.9   8.1   4.6   5.3   5.9   6.2   6.4   6.6   6.7   6.8   0.4   0.7   1.0   1.2   1.3   1.5   - 5.9   6.9   7.7   8.1   8.3   8.6   - 5.0   5.8   6.5   6.8   7.0   7.2   - 1015   1035   1050   1080   1100   1120   - - - NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.   2.Refer to Table 13 for additional static resistances.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   Johnson Controls Unitary Products   17   
			
				  
				
					261660-YTG-D-0708   TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY   240 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   8000   BHP   BLOWER   SPEED,   (RPM)   6000   BHP   7000   BHP   9000   BHP   9400   BHP   ESP   KW   ESP   KW   ESP   KW   ESP   KW   ESP   KW   208 VOLT AND STANDARD DRIVE   870   900   930   950   980   1015   6.0**   5.0   4.0   3.0   2.0   1.0   0.4   0.8   1.1   1.3   1.6   1.9   2.1   3.2   4.1   4.6   5.3   5.9   1.8   2.7   3.4   3.9   4.5   5.0   0.1   0.5   0.9   1.1   1.4   1.7   2.3   3.5   4.5   5.1   5.8   6.5   2.0   2.9   3.8   4.3   4.9   5.5   - - - - - - - - - - - - 0.2   0.6   0.8   1.2   1.5   3.8   4.9   5.5   6.3   7.0   3.2   4.1   4.6   5.3   5.9   - - - 0.1   0.4   0.7   1.0   5.1   5.9   6.9   7.7   4.3   5.0   5.8   6.5   - - - - - - 0.2   0.6   7.3   8.2   6.1   6.9   208 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.0   3.5   3.0   2.5   2.0   1.0   1.3   1.6   1.8   1.9   2.0   2.1   2.3   2.4   4.6   5.3   5.8   6.1   6.2   6.4   6.6   6.7   3.9   4.5   4.9   5.1   5.2   5.4   5.5   5.6   1.1   1.4   1.7   1.8   1.9   2.0   2.1   2.2   5.1   5.8   6.3   6.5   6.8   7.0   7.2   7.3   4.3   4.9   5.3   5.5   5.7   5.9   6.0   6.1   0.8   1.2   1.5   1.6   1.7   1.8   1.9   2.1   5.5   6.3   6.9   7.1   7.4   7.6   7.8   7.9   4.6   5.3   5.8   6.0   6.2   6.4   6.6   6.7   0.4   0.7   1.0   1.1   1.2   1.3   1.5   - 5.9   6.9   7.5   7.8   8.1   8.3   8.6   - 5.0   5.8   6.3   6.6   6.8   7.0   7.2   - - 0.2   0.5   0.6   0.7   - - 7.3   7.9   8.3   8.6   - - 6.1   6.7   7.0   7.3   - 1010   1020   1035   1050   1075   1100   - - - - - - 230/460/575 VOLT AND STANDARD DRIVE   870   900   6.0**   5.0   4.0   3.5   2.5   1.5   1.0   0.4   0.8   1.1   1.3   1.6   1.9   2.0   2.1   3.2   4.1   4.6   5.3   5.9   6.1   1.8   2.7   3.4   3.9   4.5   5.0   5.1   0.1   0.5   0.9   1.1   1.4   1.7   1.8   2.3   3.5   4.5   5.1   5.8   6.5   6.6   2.0   2.9   3.8   4.3   4.9   5.5   5.6   - - - - - - - - - - - - 0.2   0.6   0.8   1.2   1.5   1.6   3.8   4.9   5.5   6.3   7.0   7.3   3.2   4.1   4.6   5.3   5.9   6.1   - - - 930   0.1   0.4   0.7   1.0   1.1   5.1   5.9   6.9   7.7   7.9   4.3   5.0   5.8   6.5   6.7   - - - 950   - - - 980   0.2   0.6   0.7   7.3   8.2   8.6   6.1   6.9   7.3   1015   1025   230/460/575 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.0   3.5   3.0   2.0   1.5   1.0   1.3   1.6   1.9   2.0   2.1   2.3   2.4   2.5   4.6   5.3   5.9   6.2   6.4   6.6   6.7   6.8   3.9   4.5   5.0   5.2   5.4   5.5   5.6   5.7   1.1   1.4   1.7   1.9   2.0   2.1   2.2   2.3   5.1   5.8   6.5   6.8   7.0   7.2   7.3   7.4   4.3   4.9   5.5   5.7   5.9   6.0   6.1   6.2   0.8   1.2   1.5   1.7   1.8   1.9   2.1   2.2   5.5   6.3   7.0   7.4   7.6   7.8   7.9   8.1   4.6   5.3   5.9   6.2   6.4   6.6   6.7   6.8   0.4   0.7   1.0   1.2   1.3   1.5   - 5.9   6.9   7.7   8.1   8.3   8.6   - 5.0   5.8   6.5   6.8   7.0   7.2   - - 0.2   0.6   0.7   - - 7.3   8.2   8.6   - - 6.1   6.9   7.3   - 1015   1035   1050   1080   1100   1120   - - - - - - - - - - - - NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.   2.Refer to Table 13 for additional static resistances.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   18   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT   180 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   6000   BHP   BLOWER   SPEED,   (RPM)   4500   BHP   5250   BHP   6750   BHP   7200   ESP   KW   ESP   KW   ESP   KW   ESP   KW   ESP   BHP   KW   208 VOLT AND STANDARD DRIVE   850   870   6.0**   5.5   4.5   3.5   3.0   2.0   1.0   0.9   1.0   1.1   1.2   1.3   1.4   1.6   2.4   2.5   2.6   2.7   2.9   3.0   3.2   2.1   2.2   2.4   2.5   2.6   2.7   2.9   0.6   0.7   0.8   0.9   1.0   1.1   1.3   2.9   3.0   3.1   3.2   3.4   3.6   3.8   2.6   2.7   2.8   2.9   3.0   3.2   3.4   0.3   0.4   0.5   0.6   0.7   0.8   1.0   3.4   3.5   3.6   3.7   3.8   4.0   4.4   3.0   3.1   3.2   3.3   3.4   3.6   3.9   - - - - - - - - - - - - 915   0.2   0.4   0.5   0.6   0.8   4.1   4.4   4.5   4.7   5.0   3.7   3.0   4.0   4.2   4.5   - - - 965   0.2   0.3   0.4   0.6   5.0   5.1   5.4   5.6   4.5   4.6   4.8   5.0   980   1010   1040   208 VOLT AND HIGH STATIC DRIVE   965   980   6.0   5.5   4.5   3.5   2.0   1.0   1.2   1.3   1.4   1.6   1.9   2.1   2.7   2.9   3.1   3.4   3.6   3.9   2.5   2.6   2.8   3.0   3.2   3.5   0.9   1.0   1.2   1.4   1.7   1.9   3.2   3.4   3.6   3.9   4.4   4.7   2.9   3.0   3.2   3.5   3.9   4.2   0.6   0.7   0.9   1.1   1.4   1.6   3.7   3.8   4.1   4.5   5.0   5.5   3.3   3.4   3.7   4.0   4.5   4.9   0.4   0.5   0.7   0.9   1.2   - 4.4   4.5   4.8   5.1   5.8   - 3.9   4.0   4.3   4.6   5.2   - 0.2   0.3   0.4   - 5.0   5.1   5.5   - 4.5   4.6   4.9   - 1025   1065   1125   1170   - - - - - - 230/460/575 VOLT AND STANDARD DRIVE   870   915   6.0**   5.0   4.0   3.5   2.5   1.5   1.0   1.0   1.1   1.2   1.3   1.4   1.5   1.6   2.5   2.6   2.7   2.9   3.0   3.1   3.4   2.2   2.4   2.5   2.6   2.7   2.8   3.0   0.7   0.8   0.9   1.0   1.1   1.2   1.4   3.0   3.1   3.2   3.4   3.6   3.7   3.9   2.7   2.8   2.9   3.0   3.2   3.3   3.5   0.4   0.5   0.6   0.7   0.8   0.9   1.1   3.5   3.6   3.7   3.8   4.0   4.2   4.5   3.1   3.2   3.3   3.4   3.6   3.8   4.0   - - - - - - 0.2   0.4   0.5   0.6   0.7   0.9   4.1   4.4   4.5   4.7   4.9   5.1   3.7   3.9   4.0   4.2   4.4   4.6   - - - 965   0.2   0.3   0.4   0.5   - 5.0   5.1   5.4   5.7   - 4.5   4.6   4.8   5.1   - 980   1015   1050   1065   230/460/575 VOLT AND HIGH STATIC DRIVE   980   6.0   4.5   4.0   2.5   1.5   1.0   1.3   1.6   1.7   1.9   2.1   2.2   2.9   3.2   3.4   3.6   3.9   4.0   2.6   2.9   3.0   3.2   3.5   3.6   1.0   1.3   1.4   1.7   1.8   1.9   3.4   3.8   3.9   4.4   4.7   4.8   3.0   3.4   3.5   3.9   4.2   4.3   0.7   1.0   1.1   1.4   1.6   1.7   3.8   4.4   4.5   5.0   5.5   5.6   3.4   3.9   4.0   4.5   4.9   5.0   0.5   0.8   0.9   1.2   - 4.5   5.0   5.1   5.8   - 4.0   4.5   4.6   5.2   - 0.3   5.1   4.6   1045   1065   1125   1170   1190   0.6   5.6   5.0   - - - - - - - - - - - - - - - NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.   2.Refer to the additional Static Resistances table.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   Johnson Controls Unitary Products   19   
			
				  
				
					261660-YTG-D-0708   TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT   210 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   BLOWER   SPEED,   (RPM)   6000   BHP   7000   BHP   8000   BHP   9000   BHP   ESP   KW   ESP   KW   ESP   KW   ESP   KW   208 VOLT AND STANDARD DRIVE   870   900   930   950   980   995   1015   6.0**   5.0   4.0   3.0   2.0   1.5   1.0   1.3   1.4   1.6   1.7   1.9   2.1   2.2   3.6   3.8   4.1   4.2   4.5   4.6   4.8   3.0   3.2   3.4   3.6   3.8   3.9   4.0   0.7   0.9   1.1   1.3   1.5   1.6   1.7   4.3   4.7   5.0   5.1   5.4   5.5   4.7   3.7   4.0   4.2   4.3   4.5   4.7   4.8   0.2   0.4   0.6   0.8   1.0   1.1   1.2   5.1   5.6   5.9   6.0   6.3   6.4   6.6   4.3   4.7   5.0   5.1   5.3   5.4   5.6   - - - - - - 0.1   0.2   0.4   0.5   0.7   6.7   6.9   7.2   7.5   7.8   5.7   5.8   6.1   6.3   6.6   208 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.5   3.5   2.5   2.0   1.0   1.7   1.9   2.1   2.3   2.5   2.6   2.9   4.2   4.5   4.5   4.9   5.1   5.3   5.6   3.6   3.8   3.9   4.1   4.3   4.4   4.7   1.3   1.5   1.6   1.8   2.0   2.1   2.3   5.1   5.4   5.5   5.8   6.1   6.3   6.8   4.3   4.5   4.7   4.9   5.1   5.3   5.7   0.8   1.0   1.1   1.3   1.4   1.5   1.8   6.0   6.3   6.4   6.7   7.1   7.3   7.9   5.1   5.3   5.4   5.7   6.0   6.2   6.6   0.2   0.4   0.5   0.7   0.9   1.0   - 6.9   7.2   7.5   8.0   8.4   8.6   - 5.8   6.1   6.3   6.7   7.0   7.2   - 995   1025   1050   1065   1100   230/460/575 VOLT AND STANDARD DRIVE   870   900   6.0**   5.0   4.0   3.5   2.5   2.0   1.5   1.0   1.3   1.4   1.6   1.7   1.9   2.1   2.2   2.3   3.6   3.8   4.1   4.2   4.5   4.6   4.8   4.9   3.0   3.2   3.4   3.6   3.8   3.9   4.0   4.1   0.7   0.9   1.1   1.3   1.5   1.6   1.7   1.8   4.3   4.7   5.0   5.1   5.4   5.5   5.7   5.8   3.7   4.0   4.2   4.3   4.5   4.7   4.8   4.9   0.2   0.4   0.6   0.8   1.0   1.1   1.2   1.3   5.1   5.6   5.9   6.0   6.3   6.4   6.6   6.7   4.3   4.7   5.0   5.1   5.3   5.4   5.6   5.7   - - - - - - 930   0.1   0.2   0.4   0.5   0.6   0.7   6.7   6.9   7.2   7.5   7.8   8.0   5.7   5.8   6.1   6.3   6.6   6.7   950   965   995   1015   1025   230/460/575 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.5   4.0   3.5   3.0   2.5   1.5   1.0   1.7   1.9   2.1   2.2   2.3   2.5   2.6   2.9   3.1   4.2   4.5   4.6   4.8   4.9   5.1   5.3   5.6   5.8   3.6   3.8   3.9   4.0   4.1   4.3   4.4   4.7   4.9   1.3   1.5   1.6   1.7   1.8   2.0   2.1   2.3   2.5   5.1   5.4   5.5   5.7   5.8   6.1   6.3   6.8   7.0   4.3   4.5   4.7   4.8   4.9   5.1   5.3   4.7   5.9   0.8   1.0   1.1   1.2   1.3   1.4   1.5   1.8   1.9   6.0   6.3   6.4   6.6   6.7   7.1   7.3   7.9   8.3   5.1   5.3   5.4   5.6   5.7   6.0   6.2   6.6   6.9   0.2   0.4   0.5   0.6   0.7   0.9   1.0   - 6.9   7.2   7.5   7.8   8.0   8.4   8.6   - 5.8   6.1   6.3   6.6   6.7   7.0   7.2   - 995   1015   1025   1050   1065   1100   1120   - - - NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.   2.Refer to the additional Static Resistances table.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   20   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT   240 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   8000   BHP   BLOWER   SPEED,   (RPM)   6000   BHP   7000   BHP   9000   BHP   9400   ESP   KW   ESP   KW   ESP   KW   ESP   KW   ESP   BHP   KW   208 VOLT AND STANDARD DRIVE   870   900   930   950   980   995   1015   6.0**   5.0   4.0   3.0   2.0   1.5   1.0   1.3   1.4   1.6   1.7   1.9   2.1   2.2   3.6   3.8   4.1   4.2   4.5   4.6   4.8   3.0   3.2   3.4   3.6   3.8   3.9   4.0   0.7   0.9   1.1   1.3   1.5   1.6   1.7   4.3   4.7   5.0   5.1   5.4   5.5   4.7   3.7   4.0   4.2   4.3   4.5   4.7   4.8   0.2   0.4   0.6   0.8   1.0   1.1   1.2   5.1   5.6   5.9   6.0   6.3   6.4   6.6   4.3   4.7   5.0   5.1   5.3   5.4   5.6   - - - - - - - - - - - - - - - 0.1   0.2   0.4   0.5   0.7   6.7   6.9   7.2   7.5   7.8   5.7   5.8   6.1   6.3   6.6   - - - 0.1   0.2   - 8.5   8.6   - 7.1   7.3   - 208 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.5   3.5   2.5   2.0   1.0   1.7   1.9   2.1   2.3   2.5   2.6   2.9   4.2   4.5   4.5   4.9   5.1   5.3   5.6   3.6   3.8   3.9   4.1   4.3   4.4   4.7   1.3   1.5   1.6   1.8   2.0   2.1   2.3   5.1   5.4   5.5   5.8   6.1   6.3   6.8   4.3   4.5   4.7   4.9   5.1   5.3   5.7   0.8   1.0   1.1   1.3   1.4   1.5   1.8   6.0   6.3   6.4   6.7   7.1   7.3   7.9   5.1   5.3   5.4   5.7   6.0   6.2   6.6   0.2   0.4   0.5   0.7   0.9   1.0   - 6.9   7.2   7.5   8.0   8.4   8.6   - 5.8   6.1   6.3   6.7   7.0   7.2   - - - - 0.1   8.5   7.1   995   0.2   8.6   7.3   1025   1050   1065   1100   - - - - - - - - - - - - 230/460/575 VOLT AND STANDARD DRIVE   870   900   6.0**   5.0   4.0   3.5   2.5   2.0   1.5   1.0   1.3   1.4   1.6   1.7   1.9   2.1   2.2   2.3   3.6   3.8   4.1   4.2   4.5   4.6   4.8   4.9   3.0   3.2   3.4   3.6   3.8   3.9   4.0   4.1   0.7   0.9   1.1   1.3   1.5   1.6   1.7   1.8   4.3   4.7   5.0   5.1   5.4   5.5   5.7   5.8   3.7   4.0   4.2   4.3   4.5   4.7   4.8   4.9   0.2   0.4   0.6   0.8   1.0   1.1   1.2   1.3   5.1   5.6   5.9   6.0   6.3   6.4   6.6   6.7   4.3   4.7   5.0   5.1   5.3   5.4   5.6   5.7   - - - - - - - - - - - - 930   0.1   0.2   0.4   0.5   0.6   0.7   6.7   6.9   7.2   7.5   7.8   8.0   5.7   5.8   6.1   6.3   6.6   6.7   - - - - - - 950   965   0.1   0.2   - 8.5   8.6   - 7.1   7.3   - 995   1015   1025   - - - 230/460/575 VOLT AND HIGH STATIC DRIVE   950   980   6.0   5.0   4.5   4.0   3.5   3.0   2.5   1.5   1.0   1.7   1.9   2.1   2.2   2.3   2.5   2.6   2.9   3.1   4.2   4.5   4.6   4.8   4.9   5.1   5.3   5.6   5.8   3.6   3.8   3.9   4.0   4.1   4.3   4.4   4.7   4.9   1.3   1.5   1.6   1.7   1.8   2.0   2.1   2.3   2.5   5.1   5.4   5.5   5.7   5.8   6.1   6.3   6.8   7.0   4.3   4.5   4.7   4.8   4.9   5.1   5.3   4.7   5.9   0.8   1.0   1.1   1.2   1.3   1.4   1.5   1.8   1.9   6.0   6.3   6.4   6.6   6.7   7.1   7.3   7.9   8.3   5.1   5.3   5.4   5.6   5.7   6.0   6.2   6.6   6.9   0.2   0.4   0.5   0.6   0.7   0.9   1.0   - 6.9   7.2   7.5   7.8   8.0   8.4   8.6   - 5.8   6.1   6.3   6.6   6.7   7.0   7.2   - - - - 0.1   8.5   7.1   995   0.2   8.6   7.3   1015   1025   1050   1065   1100   1120   - - - - - - - - - - - - - - - - - - - - NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.   2.Refer to the additional Static Resistances table.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   Johnson Controls Unitary Products   21   
			
				  
				
					261660-YTG-D-0708   TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT   300 MBH - BOTTOM DUCT CONNECTIONS   MOTOR   PULLEY   (TURNS   OPEN)*   CFM   10000   BHP   BLOWER   SPEED,   (RPM)   7500   BHP   8750   BHP   11250   BHP   12500   BHP   ESP   KW   ESP   KW   ESP   KW   ESP   KW   ESP   KW   208 VOLT AND STANDARD DRIVE   975   6.0   5.0   4.0   3.0   2.0   1.0   0.0   1.2   1.4   1.6   1.8   2.0   2.2   2.4   5.9   6.2   6.6   6.9   7.3   7.7   8.0   4.9   5.1   5.4   5.7   6.0   6.3   6.6   5.0   0.7   0.9   1.1   1.3   1.6   1.8   7.3   7.7   8.1   8.5   8.9   9.3   9.7   6.0   6.3   6.7   7.0   7.3   7.6   8.0   - - - - - - - - - - - - - - - - - - - - - - - - - - - 1005   1040   1070   1100   1135   1165   - - - - - - 0.2   0.4   0.6   0.8   1.0   9.7   10.2   10.6   11.1   11.6   8.0   8.3   8.7   9.1   9.5   - - - - - - - - - - - - 0.2   13.5   11.0   208 VOLT AND HIGH STATIC DRIVE   1140   1180   1215   1255   1290   1330   1365   6.0   5.0   4.0   3.0   2.0   1.0   0.0   2.2   2.5   2.7   3.0   3.2   3.5   3.7   7.7   8.2   6.3   6.7   7.0   7.4   7.8   8.2   8.6   1.6   1.9   2.1   2.4   2.7   3.0   3.2   9.4   9.9   7.7   8.1   8.5   9.0   9.4   9.9   10.3   0.9   1.2   1.4   1.7   2.0   2.3   2.6   11.2   11.8   12.3   12.9   13.5   14.1   14.7   9.2   9.7   - - - - - - - - - - - - - - - - - - - - - - - - 0.3   0.6   0.9   1.2   1.5   1.8   13.7   14.3   15.0   15.6   16.4   17.0   11.2   11.7   12.3   12.8   13.4   13.9   8.6   10.4   11.0   11.5   12.0   12.6   10.1   10.6   11.1   11.6   12.1   9.1   9.5   10.0   10.5   230/460/575 VOLT AND STANDARD DRIVE   975   6.0*   5.0   4.0   3.0   2.0   1.0   0.0   1.4   1.6   1.8   2.0   2.1   2.4   2.6   5.9   6.2   6.6   6.9   7.3   7.7   8.0   4.9   5.1   5.4   5.7   6.0   6.3   6.6   1.0   1.2   1.4   1.6   1.8   2.0   2.2   7.3   7.7   8.1   8.5   8.9   9.3   9.7   6.0   6.3   6.7   7.0   7.3   7.6   8.0   0.5   0.7   0.9   1.1   1.3   1.6   1.8   8.8   9.2   7.2   7.6   8.0   8.3   8.7   9.1   9.5   - - - - - - - 1005   1040   1070   1100   1135   1165   0.1   0.3   0.6   0.8   1.0   1.3   10.9   11.4   11.9   12.4   13.0   13.5   8.9   - - 9.7   9.4   - - - 10.2   10.6   11.1   11.6   9.8   - - - 10.2   10.6   11.0   0.2   0.4   0.7   14.3   14.9   15.5   11.7   12.2   12.7   230/460/575 VOLT AND HIGH STATIC DRIVE   1140   1180   1215   1255   1290   1330   1365   6.0   5.0   4.0   3.0   2.0   1.0   0.0   2.4   2.7   2.9   3.2   3.4   3.7   3.9   7.7   8.2   6.3   6.7   7.0   7.4   7.8   8.2   8.6   2.1   2.3   2.6   2.9   3.1   3.4   3.7   9.4   9.9   7.7   8.1   8.5   9.0   9.4   9.9   10.3   1.6   1.9   2.2   2.5   2.7   3.0   3.3   11.2   11.8   12.3   12.9   13.5   14.1   14.7   9.2   9.7   1.1   1.4   1.7   2.0   2.2   2.6   2.9   13.1   13.7   14.3   15.0   15.6   16.4   17.0   10.7   11.2   11.7   12.3   12.8   13.4   13.9   0.5   0.8   1.1   1.4   - 15.0   15.8   16.4   17.2   - 12.3   12.9   13.5   14.1   - 8.6   10.4   11.0   11.5   12.0   12.6   10.1   10.6   11.1   11.6   12.1   9.1   9.5   10.0   10.5   - - - - - - NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.   2.Refer to the additional Static Resistances table.   ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total   static pressure of the blower.   * Do NOT close the pulley below 1 turn open.   ** Factory setting.   22   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 16: BLOWER MOTOR AND DRIVE DATA   BELT   (NOTCHED)   1 ADJUSTABLE MOTOR PULLEY   FIXED BLOWER PULLEY   OUTSIDE PITCH   MOTOR   BLOWER   DRIVE RANGE   (RPM)   MODEL   SIZE   OUTSIDE PITCH   PITCH   LENGTH QTY.   (IN.)   EFF.   (%)   DESIG-   NATION   BORE DESIG-   (IN.) NATION   BORE DESIG-   (IN.) NATION   HP FRAME   DIA.   (IN.)   DIA.   (IN.)   DIA.   (IN.)   DIA.   (IN.)   Standard 850/1065   BK90   1-1/8   BK80   8.75   7.75   11.75   10.75   11.3   8.4   1 BX81   BX78   BX83   BX81   82.8   79.8   84.8   82.8   86.0   84.0   1 1 1 1 1 1 2 15 TON   5 184 T   83   89   91   1VP56   1VP68   5.35   6.75   7.5   4.3-5.3   High   965/1190   Static   7.4   1 Standard 870/1025   BK120   11.4   10.4   11.1   9.5   1-3/16   1-3/16   17.5 &   20 TON   7.5 213 T   15 254 T   1-3/8   High   5.5-6.5   6.2-7.4   950/1120   Static   BK110   Standard 975/1165   1B5V110   1-7/16 5VX860   1-7/16 5VX840   25 TON   1VP75X   1-5/8   High   1140/1365   Static   1B5V94   9.7   1.   2.   All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because   they are located in the moving air, upstream of any heating device.   Do NOT close this pulley below 1 turn open.   1 TABLE 17: STATIC RESISTANCES   RESISTANCE, IWG   CFM   DESCRIPTION   15 TON   6000   0.1   17.5 TON   20 TON   25 TON   9400 7500 10000 12500   4500   7200 6000   7500   0.1   0.4   0.5   0.5   0.5   0.1   0.3   9000 6000   8000   0.1   0.4   0.5   0.5   0.5   0.1   0.3   WET INDOOR COIL   0.1   0.3   0.3   0.4   0.4   0.1   0.1   0.1   0.4   0.5   0.5   0.5   0.1   0.3   0.1   0.4   0.4   0.5   0.5   0.1   0.2   0.1   0.5   0.5   0.6   0.6   0.2   0.5   0.1   0.4   0.4   0.5   0.5   0.1   0.2   0.1   0.5   0.5   0.6   0.6   0.2   0.5   0.1   0.4   0.5   0.5   0.5   0.1   0.3   0.1   0.5   0.5   0.6   0.6   0.2   0.5   0.1   0.6   0.6   0.7   0.7   0.3   0.6   18 KW   36 KW   54 KW   72 KW   0.4   0.4   ELECTRIC HEAT OPTIONS   0.5   0.5   ECONOMIZER OPTION   0.1   HORIZONTAL DUCT CONNECTIONS2   0.2   1.   Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for   exception.)   2.   Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values   on the respective unit’s blower performance table.   TABLE 18: POWER EXHAUST PERFORMANCE   STATIC RESISTANCE OF RETURN DUCTWORK, IWG   0.3 0.4 0.5   MOTOR   SPEED1   0.2   0.6   CFM   kW   CFM   kW   CFM   kW   CFM   kW   CFM   kW   HIGH2   MEDIUM   LOW   5250   4900   4400   0.83   0.77   0.72   4500   3900   3700   0.85   0.79   0.74   4200   3500   3000   0.88   0.82   0.78   3750   2900   - 0.93   0.85   - 3000   0.99   - - - - 1.   Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.   The factory setting.   2.   Johnson Controls Unitary Products   23   
			
				  
				
					261660-YTG-D-0708   TABLE 19: DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET   COMPRESSORS   HEATER OPTION   MAX.   FUSE/   BRKR1   SIZE   (AMPS)   90   ID   MIN.   MODEL   (TON-   OD FAN   MOTORS   FLA EACH   CONV   OUTLET   AMPS   BLOWER   MOTOR   FLA   CIRCUIT   AMPACITY   (AMPS)   VOLTAGE   RLA   LRA   MODEL KW STAGES AMPS   EACH   EACH   NAGE)   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   0.0   ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 74.2   74.2   112.9   160.1   169.4   73.2   73.2   126.3   147.9   191.2   36.1   36.1   63.1   74.0   95.6   28.2   29.0   50.7   59.3   76.7   86.0   86.0   118.7   165.9   175.2   86.0   86.0   133.3   154.9   198.2   43.2   43.2   66.6   77.5   99.1   35.0   35.0   53.6   62.2   79.5   13.5   27.0   40.6   54.1   0.0   37.5   75.1   112.6   150.1   ~ 90   208   230   460   575   208   230   460   575   22.4   22.4   10.9   8.3   164   164   100   78   2.1   2.1   1.1   0.9   2.1   2.1   1.1   0.9   15.4   15.4   7.2   0.0   0.0   0.0   0.0   0.0   0.0   0.0   0.0   125   175   200   90   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 17.3   34.6   52.0   69.3   ~ 90   150   175   225   45   180   (15)   45   70   90   110   35   35   5.9   60   70   90   110   110   125   175   200   110   110   150   175   225   50   13.5   27.0   40.6   54.1   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   37.5   75.1   112.6   150.1   ~ 43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 25.6   25.6   12.8   10.3   190   190   95   20.0   20.0   10.0   8.2   210   (17 1/2)   50   70   90   110   45   18.0   36.0   54.0   72.0   17.3   34.6   52.0   69.3   45   60   70   75   90   NOTE 1: HACR Type per NEC.   24   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 19: DJ ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET (CONTINUED)   COMPRESSORS   HEATER OPTION   MAX.   FUSE/   ID   MIN.   MODEL   (TON-   OD FAN   MOTORS   FLA EACH   CONV   OUTLET   AMPS   BLOWER   MOTOR   FLA   CIRCUIT   AMPACITY   (AMPS)   BRKR1   SIZE   (AMPS)   125   125   125   175   200   125   125   150   175   225   70   VOLTAGE   RLA   LRA   MODEL KW STAGES AMPS   EACH   EACH   NAGE)   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   0.0   ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 110.4   110.4   118.7   165.9   175.2   110.4   110.4   133.3   154.9   198.2   56.5   13.5   27.0   40.6   54.1   0.0   37.5   75.1   112.6   150.1   ~ 208   230   460   575   208   230   460   575   33.6   33.6   17.3   13.5   47.1   47.1   19.6   15.8   225   225   114   80   3.7   3.7   1.9   1.5   3.7   3.7   1.9   1.5   20.0   20.0   10.0   8.2   0.0   0.0   0.0   0.0   0.0   0.0   0.0   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 17.3   34.6   52.0   69.3   ~ 240   (20)   56.5   70   66.6   77.5   99.1   70   90   110   50   50   44.6   44.6   53.6   60   62.2   79.5   70   90   159.4   159.4   159.4   189.1   198.4   159.4   159.4   159.4   178.2   221.5   71.0   200   200   200   200   225   200   200   200   200   250   90   13.5   27.0   40.6   54.1   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   37.5   75.1   112.6   150.1   ~ 43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 245   245   125   100   38.6   38.6   19.3   15.4   300   (25)   71.0   78.3   90   90   89.1   110.7   57.0   100   125   70   18.0   36.0   54.0   72.0   17.3   34.6   52.0   69.3   57.0   62.6   71.2   70   70   80   88.5   100   NOTE 1: HACR Type per NEC.   Johnson Controls Unitary Products   25   
			
				  
				
					261660-YTG-D-0708   TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET   COMPRESSORS   HEATER OPTION   MAX.   FUSE/   ID   MIN.   MODEL   (TON-   OD FAN   MOTORS   FLA EACH   CONV   OUTLET   AMPS   BLOWER   MOTOR   FLA   CIRCUIT   AMPACITY   (AMPS)   BRKR1   SIZE   (AMPS)   100   100   150   175   200   100   100   150   175   225   50   VOLTAGE   RLA   LRA   MODEL   STAGES AMPS   KW   EACH   EACH   NAGE)   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   0.0   ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 84.2   84.2   125.4   172.6   181.9   83.2   13.5   27.0   40.6   54.1   0.0   37.5   75.1   112.6   150.1   ~ 208   230   460   575   208   230   460   575   22.4   22.4   10.9   8.3   164   164   100   78   2.1   2.1   1.1   0.9   2.1   2.1   1.1   0.9   15.4   15.4   7.2   10.0   10.0   5.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 17.3   34.6   52.0   69.3   ~ 84.6   138.8   160.4   203.7   41.1   180   (15)   42.3   50   69.4   80.2   101.9   32.2   34.0   70   90   110   40   40   5.9   4.0   55.7   60   64.3   81.7   96.0   70   90   110   110   150   200   200   110   110   150   175   225   60   13.5   27.0   40.6   54.1   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   37.5   75.1   112.6   150.1   ~ 43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 96.0   25.6   25.6   12.8   10.3   190   190   95   20.0   20.0   10.0   8.2   10.0   10.0   5.0   131.2   178.4   187.7   96.0   96.0   145.8   167.4   210.7   48.2   48.2   72.9   210   (17 1/2)   60   80   83.7   105.4   39.0   90   110   45   18.0   36.0   54.0   72.0   17.3   34.6   52.0   69.3   39.0   58.6   67.2   45   60   70   75   4.0   84.5   90   NOTE 1: HACR Type per NEC.   26   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED)   COMPRESSORS   HEATER OPTION   MAX.   FUSE/   ID   MIN.   MODEL   (TON-   OD FAN   MOTORS   FLA EACH   CONV   OUTLET   AMPS   BLOWER   MOTOR   FLA   CIRCUIT   AMPACITY   (AMPS)   BRKR1   SIZE   (AMPS)   150   150   150   200   200   150   150   150   175   225   70   VOLTAGE   RLA   LRA   MODEL   STAGES AMPS   KW   EACH   EACH   NAGE)   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   None   E18   E36   E54   E72   0.0   ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 1 2 2 2 ~ 120.4   120.4   131.2   178.4   187.7   120.4   120.4   145.8   167.4   210.7   61.5   13.5   27.0   40.6   54.1   0.0   37.5   75.1   112.6   150.1   ~ 208   230   460   575   208   230   460   575   33.6   33.6   17.3   13.5   47.1   47.1   19.6   15.8   225   225   114   80   3.7   3.7   1.9   1.5   3.7   3.7   1.9   1.5   20.0   20.0   10.0   8.2   10.0   10.0   5.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 17.3   34.6   52.0   69.3   ~ 240   (20)   61.5   70   72.9   83.7   105.4   48.6   48.6   80   90   110   60   60   4.0   58.6   60   67.2   84.5   70   90   169.4   169.4   169.4   201.6   210.9   169.4   169.4   169.4   190.7   234.0   76.0   200   200   200   225   225   200   200   200   225   250   90   13.5   27.0   40.6   54.1   0.0   18.0   36.0   54.0   72.0   0.0   18.0   36.0   54.0   72.0   0.0   37.5   75.1   112.6   150.1   ~ 43.3   86.6   129.9   173.2   ~ 21.7   43.3   65.0   86.6   ~ 245   245   125   100   38.6   38.6   19.3   15.4   10.0   10.0   5.0   300   (25)   76.0   84.5   90   90   95.3   117.0   61.0   110   125   70   18.0   36.0   54.0   72.0   17.3   34.6   52.0   69.3   61.0   67.6   76.2   70   70   90   4.0   93.5   100   NOTE 1: HACR Type per NEC.   Johnson Controls Unitary Products   27   
			
				  
				
					261660-YTG-D-0708   1 TABLE 21: DJ VOLTAGE LIMITATIONS   VOLTAGE LIMITATIONS   VOLTAGE   POWER   SUPPLY   MIN.   MAX.   VOLTAGE   208/230-3-60   187   253   LIMITATIONS   414   518   506   630   460-3-60   575-3-60   1.   Utilization Range “A” in accordance with ARI Standard   110.   TABLE 22: PHYSICAL DATA   MODELS   DJ180   DJ210   DJ240   DJ300   CENTRIFUGAL BLOWER (Dia. x Wd.)   FAN MOTOR HP   15x15   5.0   18x15   7.5   18x15   7.5   18x15   15   EVAPORATOR   BLOWER   ROWS DEEP   4 EVAPORATOR   COIL   FINS PER INCH   13.5   25   FACE AREA (Sq. Ft.)   PROPELLER DIA. (In.) (Each)   24   1/3   24   1/3   30   3/4   30   3/4   CONDENSER FAN   (Four Per Unit)   FAN MOTOR HP   NOM. CFM TOTAL   ROWS DEEP   (Each)   (Each)   4,000   4,000   5,000   5,000   2 CONDENSER   COIL   FINS PER INCH   FACE AREA (Sq. Ft.)   20   63.8   COMPRESSOR   (Qty. Per Unit)   SCROLL   2 QUANTITY PER UNIT (12" X 24" X 2"   TOTAL FACE AREA (Sq. Ft.)   12   24   FILTERS   CHARGE   SYSTEM No.1   SYSTEM No. 2   COOLING ONLY   23/0   23/8   24/0   24/0   2540   2740   2780   23/8   23/8   23/8   23/8   2660   2860   2900   REFRIGERANT   22 (Lb./Oz.)   2260   2460   2500   2560   2760   2800   BASIC UNIT   N24   N32   GAS / ELECTRIC   DOUBLE WALL   260   160   ECONOMIZER   ECONOMIZER WITH   POWER EXHAUST   MOTORIZED DAMPER   245   150   25   30   35   40   10   18 KW   OPTIONS   36 KW   54 KW   72 KW   OPERATING   WEIGHTS   (LBS.)   ELECTRIC HEATER   HOT GAS BYPASS   SUPPLY FAN VFD   ROOF CURB   185   45   BAROMETRIC DAMPER   ECONOMIZER / MOTORIZED   DAMPER RAIN HOOD   ECONOMIZER / POWER   EXHAUST RAIN HOOD   WOOD SKID   55   90   220   28   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   TABLE 23: SUPPLY FAN VFD WEIGHTS, IN LBS.   TABLE 24: ELECTRIC HEAT CORRECTION   FACTORS   SUPPLY FAN MOTOR   230V   460V   575V   kW CAP. MULTI-   PLIER   W/O MANUAL BYPASS   NOMINAL VOLTAGE   VOLTAGE   25   30   30   30   25   30   30   30   30   30   35   40   5.0 hp   7.5 hp   208   230   460   575   1.00   0.92   0.92   0.92   208   240   480   600   10.0 hp   15.0 hp   W/MANUAL BYPASS   5.0 hp   30   35   35   40   30   35   35   35   35   35   40   45   7.5 hp   10.0 hp   15.0 hp   CONTROL WIRING   COOLING / HEATING (24 VOLT THERMOSTAT)   THERMOSTAT1   TERMINALS   UNIT TERMINAL   BLOCK 1TB2   COOLING ONLY (24 VOLT THERMOSTAT)   THERMOSTAT1   R RH   RC   Y1   Y2   TERMINALS   Y1   Y2   W1   UNIT TERMINAL   BLOCK 1 TB2   RC   RH   R ADD   JUMPER   W2   G Y1   Y2   Y1   Y2   ADD   JUMPER   W1   W2   B W1   W2   G W1   W2   24 VOLT   TRANSFORMER   X 3 3 A1   A2   Y3   G G B X B 124 Volt Thermostat 2TH04701024 or 2TH04701524   (with Subbase 2TB04700324).   LED1   24 VOLT   TRANSFORMER   LED2   4 A1   A2   NOT USED   2Terminal strip 1TB - located on relay board in 24-volt section   of the unit control box.   4 COM   A1   3Second stage heating is not required on units with a single stage   electric heater.   ADD   JUMPER   A2   T POWER WIRING   T L1   Refer to the   TO REMOTE SENSOR   2THO4702224 IF USED   LINE VOLTAGE   TERMINAL   BLOCK 2TB   ELECTRICAL DATA   tables to size the   power wiring, the   fuses and the   L2   L3   1Electronic programmable thermostat 2ET04700224 (includes subbase).   2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.   3Second stage heating is not required on units with a single stage electric heater.   4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers   when the thermostat switches to the set-back position.   IN CONTROL BOX   disconnect switch.   GROUND LUG   NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.   FIGURE 3 - TYPICAL DJ FIELD WIRING DIAGRAM   Johnson Controls Unitary Products   29   
			
				  
				
					261660-YTG-D-0708   ECONOMIZER / MOTORIZED DAMPER   FIXED OUTDOOR INTAKE AIR AND   POWER EXHAUST RAIN HOODS   (See detail Y)   BLOWER MOTOR   ACCESS (Location   of Optional VFD Bypass)   BLOWER ACCESS   (Location of   Optional VFD)   BLOWER   COMPARTMENT   ACCESS   COMPRESSOR ACCESS   180-19/32   (Auxiliary)   DOT PLUG   (For pressure   drop reading)   52-5/8   GAS OR ELECTRIC   HEAT   ACCESS   COIL   GUARD   KIT   VENT AIR   OUTLET   HOODS   COMBUSTION   AIR INLET HOOD   21.00   9-3/4   (C) GAS   SUPPLY   ENTRY   CONDENSER   COILS   7-1/8   136-1/4   (A) CONTROL WIRING   ENTRY   92   6-3/8   46-5/8   5 DISCONNECT   SWITCH   LOCATION   11-1/2   CONTROL BOX   ACCESS   5-7/8   (B) POWER   35   WIRING   ENTRY   BOTTOM SUPPLY   AND RETURN   AIR OPENINGS   (See Note)   35-1/4   RETURN   AIR   33   2-3/4   SUPPLY   AIR   3-3/4   21-1/2   UNIT BASE RAILS   Shown separately to illustrate   Bottom Duct openings. Power   and Gas Piping Connection   location.   (D)   GAS SUPPLY   ENTRY   (B) POWER WIRING   ENTRY   11-1/8   NOTE:   For curb mounted units, refer to the curb hanger   dimensions of the curb for proper size of the   supply and return air duct connections.   8-1/8   (A) CONTROL WIRING   ENTRY   12-1/2   46-5/8   9-1/4   9-3/4   FIGURE 4 - FRONT VIEW DIMENSIONS   TABLE 25: UTILITIES ENTRY DATA   OPENING SIZE   HOLE   USED FOR   (DIA.)   1-1/8” KO   Side   Control Wiring   A 3/4” NPS (Fem.)   3-5/8” KO   Bottom   Side   B Power Wiring   3” NPS (Fem.)   Bottom   1 2-3/8” KO   C D Gas Piping (Front)   , 2 1-11/16” Hole   Gas Piping (Bottom)   1.   2.   One-inch gas piping NPT required.   Opening in the bottom of the unit can be located by the slice in   the insulation.   NOTE: All entry holes should be field sealed to prevent rain   water entry into the building.   30   Johnson Controls Unitary Products   
			
				  
				
					261660-YTG-D-0708   EVAPORATOR   SECTION   DOT PLUG   (For pressure   drop reading)   40-3/8"   FILTER   ACCESS   SUPPLY   AIR   RETURN   AIR   COMPRESSOR   ACCESS   OUTDOOR   AIR   40-1/2"   SUPPLY AIR   ACCESS   18-5/8"   1" NPT FEMALE   COND. DRAIN   CONNECTION   27-3/4"   Dimensions listed are for side   5-1/8"   RETURN AIR   ACCESS   duct flange openings; see   Field Accessories for Side   Duct Flange Kit.   OUTDOOR AIR   COMPARTMENT   ACCESS   39-5/8"   REAR   VIEW   FIGURE 5 - REAR VIEW DIMENSIONS   NOTE:Units are shipped with the bottom duct openings   covered. An accessory flange kit is available for   connecting side ducts.   For bottom duct applications:   For side duct applications:   1. Remove the side panels from the supply and return air   compartments to gain access to the bottom supply and   return air duct covers.   1. Replace the side panels on the supply and return air   compartments with the side duct flange accessory kit   panels.   2. Remove and discard the bottom duct covers. Duct   openings are closed with sheet metal covers except   when the unit includes a power exhaust option. The   covering consists of a heavy black paper composition.   2. Connect ductwork to the flanges on those panels.   3. Replace the side supply and return air compartment   panels.   Johnson Controls Unitary Products   31   
			
				  
				
					261660-YTG-D-0708   NOTE: ELEC / ELEC Models: Units and ductwork are   approved for zero clearance to combustible material   when equipped with electric heaters.   TABLE 26: MINIMUM CLEARANCES   LOCATION   CLEARANCE   36”   Front   24” (Less Economizer)   49” (With Economizer)   Rear   GAS / ELEC Models: A 1” clearance must be   provided between any combustible material and the   supply air ductwork for a distance of 3 feet from the   unit.   24” (Less Economizer)   Left Side (Filter Access)   Right Side (Cond. Coil)   3 36” (With Economizer)   36”   0”   1 Below Unit   The products of combustion must not be allowed to   accumulate within a confined space and recirculate.   72” With 36” Maximum   Horizontal Overhang (For   Condenser Air Discharge)   2 Above Unit   Locate unit so that the vent air outlet hood is at least:   1.   2.   Units may be installed on combustible floors made from wood or   class A, B, or C roof covering material.   • Three (3) feet above any force air inlet located   within 10 horizontal feet (excluding those integral to   the unit).   Units must be installed outdoors. Overhanging structures or   shrubs should not obstruct condenser air discharge outlet.   3. If economizer is factory installed, the unassembled rain hood   must be removed from its ride along position in front of evapora-   tor coil, or in the outdoor air compartment, prior to final installa-   tion.   • Four (4) feet below, four horizontal feet from, or one   foot above any door or gravity air inlet into the   building.   • Four (4) feet from electric and gas meters,   regulators and relief equipment.   ECONOMIZER   MOTORIZED   DAMPER   POWER EXHAUST   RAIN HOOD   (on Return Air Compartment)   SUPPLY AIR   RAIN HOOD   (on Outdoor Air Compartment)   COMPARTMENT   ECONOMIZER / MOTORIZED DAMPER   AND POWER EXHAUST RAIN HOODS   FIXED   OUTDOOR AIR   INTAKE HOOD   (located on   Return Air   Compartment)   36-5/8”   1“ CONDENSATE   DRAIN   (Must be trapped)   16-1/8”   5”   28-3/16”   92”   REAR VIEW   LH VIEW   DETAIL “Y”   UNIT WITH RAIN HOODS   FIGURE 6 - UNIT DIMENSIONS DJ180, 210, 240 & 300 (RAINHOOD)   32   Johnson Controls Unitary Products   
			
			
				
					261660-YTG-D-0708   FIGURE 7 - UNIT CENTER OF GRAVITY   ROOF JACK   INSTALLATION   ROOF CURB   INSTALLATION   SLAB ON   GROUND   INSTALLATION   FIGURE 8 - TYPICAL UNIT APPLICATIONS   Johnson Controls Unitary Products   33   
			
			
				
					261660-YTG-D-0708   B E F C D C A A D B FIGURE 9 - FOUR AND SIX POINT LOADS   TABLE 27: FOUR AND SIX POINT LOADS   Total   Shipping   Weight   2660   4 Point Loads (lbs)   Unit Size   A B C D 180 Gas   210 Gas   240 Gas   300 Gas   180 Elec   210 Elec   240 Elec   300 Elec   454   510   516   531   419   476   481   496   847   954   964   992   784   888   899   927   885   954   964   992   819   888   899   927   474   510   516   531   438   476   481   496   2928   2960   3046   2460   2728   2760   2846   Total   Shipping   Weight   2660   6 Point Loads (lbs)   Unit Size   A B C D E F 180 Gas   210 Gas   240 Gas   300 Gas   180 Elec   210 Elec   240 Elec   300 Elec   302   340   344   354   280   317   321   331   316   340   344   354   292   317   321   331   453   488   493   508   419   455   460   474   590   636   643   661   546   592   599   618   565   636   643   661   523   592   599   618   434   488   493   508   401   455   460   474   2928   2960   3046   2460   2728   2760   2846   NOTE: These weights are with economizer, and high option heat (gas or electric)   34   Johnson Controls Unitary Products   
			
			
				
					261660-YTG-D-0708   25-1/4"   FIGURE 10 - UNIT ROOF CURB DIMENSIONS   2. The 58-1/2” overall dimension of the ducts allows duct-   work penetration between roof joists that are spaced on   72” centers.   Note: Ducts can be installed into the curb from the roof. All   electrical and gas line connections can be made inside the   curb.   FIGURE 11 - ROOF CURB DUCT OPENINGS   DIMENSION   1. The 2” space between the ducts allows for “jumping” an   existing roof joist.   FIGURE 12 - CUT AWAY OF ROOF CURB   Johnson Controls Unitary Products   35   
			
			
				
					261660-YTG-D-0708   THERMOSTAT   TERMINALS   CONTROL   TERMINAL   BLOCK   W1   W1   W2   Y1   G 1 W2   Y1   2 Y2   OCC   P P1   Y2   X G R C Smoke   Detector   R SD   C Jumper 3   R SD   SD   C 4 RC   5 OCC   24 VAC   Class 2   6 X TERMINALS ON   A LIMITED   NUMBER OF   THERMOSTATS   1 2 3 4 5 6 Second stage heating not required on single stage heating units.   Second stage cooling not required on single stage cooling units.   Jumper is required if there is no Smoke Detector circuit.   Jumper is required for any combination of R, RC, or RH.   OCC is an output from the thermostat to indicate the Occupied condition.   X is an input to the thermostat to display Error Status conditions.   FIGURE 13 - TYPICAL SIMPLICITY® WIRING DIAGRAM   36   Johnson Controls Unitary Products   
			
				
					261660-YTG-D-0708   They shall have built-in field convertible duct connections for   down discharge supply/return or horizontal discharge supply/   return, and be available with factory installed options or field   installed accessories. The units shall be factory wired, piped,   charged with R-22 refrigerant and factory tested prior to ship-   ment. All unit wiring shall be both numbered and color coded.   All units shall be manufactured in a facility certified to ISO   9001 standards and the cooling performance shall be rated in   accordance with DOE and ARI test procedures. Units shall   be ETL & CGA listed, classified to ANSIZ21.47 standards, UL   1995/CAN/CSA No. 236-M90 conditions.   GUIDE SPECIFICATIONS   GENERAL   Units shall be manufactured by York International Unitary   Products Group in an ISO 9001 certified facility.   York's Sunline Magnum™ units are convertible single pack-   age units. All models have dual independent refrigerant cir-   cuits for efficient part load operation and maximum comfort   control. Although the units are primarily designed for curb   mounting on a roof, they can also be slab-mounted at ground   level or set on steel beams above a finished roof. Cooling   only, cooling with gas heat and cooling with electric heat   models are available with a wide variety of factory-mounted   options and field-installed accessories to make them suitable   for almost every application. All units are self-contained and   assembled on full perimeter base rails with holes in the four   corners for overhead rigging. Every unit is completely piped,   wired, charged and tested at the factory to simplify the field   installation and to provide years of dependable operation. All   models (including those with an economizer) are suitable for   either bottom or horizontal duct connections. Models with   power exhaust are suitable for bottom duct connections only.   For bottom duct, remove the sheet metal panels from the   supply and return air openings through the base of the unit.   For horizontal duct, replace the supply and return air panels   on the rear of the unit with a side duct flange accessory. All   supply air blowers are equipped with a belt drive that can be   adjusted to meet the exact requirements of the job.   UNIT CABINET   Unit cabinet shall be constructed of G90 galvanized steel, with   exterior surfaces coated with a non-chalking, powdered paint   finish, certified at 1000 hours salt spray test per ASTM-B117   standards. Indoor blower section shall be insulated with a min-   imum 1/2" thick insulation, coated on the airside. Aluminum foil   faced insulation shall be used in the furnace compartment and   be fastened with ridged fasteners to prevent insulation from   entering the air stream. Cabinet panels shall be "large" size,   easily removable for servicing and maintenance. Full perimeter   base rails shall be provided to assure reliable transit of equip-   ment, overhead rigging and proper sealing on roof curb appli-   cations. Disposable 2" filters shall be furnished and be   accessible through a removable access door, sealed airtight.   Units filter track shall be designed to accommodate either 1" or   2" filters. Fan performance measuring ports shall be provided   on the outside of the cabinet to allow accurate air measure-   ments of evaporator fan performance without removing panels   or creating air by-pass of the coils. Condensate pan shall be   internally sloped and conform to ASHRAE 62-89 self-draining   standards. Condensate connection shall be a minimum of 1"   I.D. female and be a ridged mount connection. Unit shall incor-   porate a fixed outdoor air damper with an outdoor air intake   opening covered with a bird screen and a rain hood painted to   match the exterior of the unit.   Each unit shall have 4 condenser fan motors. A high static   drive option is available for applications with a higher CFM   and/or static pressure requirement. All compressors include   crankcase heat and internal pressure relief. Every refrigerant   circuit includes an expansion valve, a liquid line filter-drier, a   discharge line high pressure switch and a suction line with a   freezestat and low pressure/loss of charge switch. The unit   control circuit includes a 75 VA transformer, a 24-volt circuit   breaker and a relay board with two compressor lockout cir-   cuits, a terminal strip for thermostat wiring, plus an additional   set of pin connectors to simplify the interface of additional field   controls. All units have long lasting powder paint cabinets with   1000 hour salt spray test approval under ASTM-B117 proce-   dures. All 208/230 and 460-volt models are ETL approved. All   208/230 and 575-volt models are CGA approved. All models   include a 1-year limited warranty on the complete unit. Com-   pressors and electric heater elements carry an additional 4-   year warranty. Aluminized steel tubular heat exchangers carry   an additional 9-year warranty.   INDOOR (EVAPORATOR) FAN ASSEMBLY   Fan shall be a belt drive assembly and include an adjustable-   pitch motor pulley. Job site selected (B.H.P.) brake horsepower   shall not exceed the motors nameplate horsepower rating, plus   the service factor. Units shall be designed not to operate above   service factor. Fan wheel shall be double-inlet type with for-   ward-curved blades, dynamically balanced to operate smoothly   throughout the entire range of operation. Airflow design shall be   constant air volume.   A variable air volume (VAV) option using a variable frequency   drive (VFD) is available for applications requiring a constant   supply duct static pressure. Units equipped for VAV shall be   controlled by a duct pressure transducer with a 0 - 5” WC pres-   sure range. The pressure transducer shall provide a 0 - 5 VDC   output signal to a VAV control board which, in turn shall provide   a 2 - 10 VDC speed reference signal to the VFD. The VAV con-   trol board shall operate using factory-installed Supply Air,   Return Air and Outside Air Temperature Sensors. Units   equipped with VFD’s shall have factory-installed manual   bypass as an option.   DESCRIPTION   Units shall be factory-assembled, single packaged, DJ***N   Electric Cooling/Gas Heat, DJ***C/E Electric Cooling/   Optional Electric Heat, designed for outdoor mounted instal-   lation. The 15,17.5, and 20 ton units shall have minimum   EER ratings of 11.1. The 25 ton unit shall have a minimum   EER rating of 10.5.   Johnson Controls Unitary Products   37   
			
				
					261660-YTG-D-0708   OUTDOOR (CONDENSER) FAN ASSEMBLY   b. Unit shall incorporate a lockout circuit which pro-   vides reset capability at the space thermostat or   base unit, should any of the following standard   safety devices trip and shut off compressor.   The outdoor fans shall be of the direct-driven propeller type,   discharge air vertically, have aluminum blades riveted to cor-   rosion resistant steel spider brackets and shall be dynami-   cally balanced for smooth operation. The 4 outdoor fan   motors shall be totally enclosed with permanently lubricated   bearings, internally protected against overload conditions and   staged independently.   c. Loss-of-charge/Low-pressure switch.   1. High-pressure switch.   2. Freeze-protection thermostat, evaporator coil. If   any of the above safety devices trip, a LED   (light-emitting diode) indicator shall flash a   diagnostic code that indicates which safety   switch has tripped.   REFRIGERANT COMPONENTS   Compressors:   a. Shall be Scroll compressors internally protected with   internal high-pressure relief and over temperature   protection.   d. Unit shall incorporate "AUTO RESET" compressor   over temperature, over current protection.   b. Shall have internal spring isolation and sound muf-   fling to minimize vibration and noise, and be exter-   nally isolated on a dedicated, independent   mounting.   e. Unit shall operate with conventional thermostat   designs and have a low voltage terminal strip for   easy hook-up.   f. Unit control board shall have on-board diagnostics   and fault code display.   Coils:   a. Evaporator and condenser coils shall have alumi-   num plate fins mechanically bonded to seamless   internally enhanced copper tubes with all joints   brazed. Special Phenolic coating shall be available   as a factory option.   g. Standard controls shall include anti-short cycle and   low voltage protection, and permit cooling operation   down to 0 °F.   h. Control board shall monitor each refrigerant safety   switch independently.   b. Evaporator and Condenser coils shall be of the   direct expansion, draw-thru, design.   Refrigerant Circuit and Refrigerant Safety Components shall   include:   i.   Control board shall retain last 5 fault codes in non   volatile memory, which will not be lost in the event of   a power loss.   a. Balance-port thermostatic expansion valve with   independent circuit feed system.   GAS HEATING SECTION (DJ***N MODELS)   b. Filter drier/strainer to eliminate any moisture or for-   eign matter.   Shall be designed with induced draft combustion with post   purge logic and energy saving direct spark ignition, redun-   dant main gas valve. Ventor wheel shall be constructed of   stainless steel for corrosion resistance. The heat exchanger   shall be of the tubular type, constructed of T1-40 aluminized   steel for corrosion resistance and allowing minimum mixed   air entering temperature of 25° F. Burners shall be of the in-   shot type, constructed of aluminum coated steel and contain   air mixture adjustments. All gas piping shall enter the unit   cabinet at a single location through either the side or curb,   without any field modifications. An integrated control board   shall provide timed control of evaporator fan functioning and   burner ignition. Heating section shall be provided with the fol-   lowing minimum protection:   c. Accessible service gage connections on both suc-   tion and discharge lines to charge, evacuate, and   measure refrigerant pressure during any necessary   servicing or troubleshooting, without losing charge.   d. The refrigeration system shall provide at least 15° F   of sub-cooling at design conditions.   e. All models shall have two independent circuits.   f. Hot gas bypass option shall be factory-installed on   compressor #1 discharge line to provide cooling in   low-load applications. HGBP shall be a standard   feature on VAV models and an optional feature on   CV models.   a. Primary and auxiliary high-temperature limit   switches.   UNIT CONTROLS   b. Induced draft motor speed sensor.   a. Unit shall be complete with self-contained low-volt-   age control circuit protected by a resetable circuit   breaker on the 24-volt transformer side.   c. Flame roll out switch (automatic reset).   d. Flame proving controls. Unit shall have two inde-   pendent stages of capacity.   38   Johnson Controls Unitary Products   
			
				
					261660-YTG-D-0708   ELECTRIC HEATING (DJ***C/E MODELS)   ters shall be provided. Simultaneous economizer/com-   pressor operation is also possible. Dampers shall fully   close on power loss.   Nickel chromium electric heating elements shall be provided   as required by the application with 1 or 2 stage control, as   required, from 13.5 KW to 72 KW capacities. The heating   section shall have a primary limit control(s) and automatic   reset to prevent the heating element system from operating   at an excessive temperature. Units with Electric Heating shall   be wired for a single point power supply with branch circuit   fusing (where required).   • BAS-READY ECONOMIZER - Outdoor and return air   dampers that are interlocked and positioned by a fully-   modulating, spring return damper actuator. The maxi-   mum leakage rate for the outdoor air intake dampers   shall not exceed 2% when dampers are fully closed and   operating against a pressure differential of 0.5 IWG.   For units with optional VAV or Simplicity® Intelli-Com-   fort™ control, free-cooling shall be available while the   outdoor dry bulb temperature (OAT) remains below a   programmable set-point of the controller. Field-installed   humidity sensors for either outdoor air or outdoor &   return air streams are available to provide free-cooling   based on single-enthalpy or dual-enthalpy configura-   tions, respectively. If free-cooling is available, a call for   cooling shall modulate the economizer in order to main-   tain a supply air temperature (SAT) programmable set-   point. With the use of a field-installed indoor air quality   sensor, the controller shall provide Demand Ventilation   by modulating the economizer dampers to allow more   UNIT OPERATING CHARACTERISTICS   Unit shall be capable of starting and running at 125° F   outdoor temperature, exceeding maximum load criteria of   ARI Standard 340/360. The compressor, with standard   controls, shall be capable of operation down to 25° F outdoor   temperature. Accessory low ambient kit shall be available for   operation to 0° F. Unit shall be provided with fan time delay to   prevent cold air delivery before heat exchanger warms up   (Gas heat only).   ELECTRICAL REQUIREMENTS   outside airflow upon detection of elevated indoor CO   2 All unit power wiring shall enter unit cabinet at a single factory   provided location and be capable of side or bottom entry, to   minimize roof penetrations and avoid unit field modifications.   Separate side and bottom openings shall be provided for the   control wiring.   concentrations above a programmable set-point. With an   additional field-installed outdoor air quality sensor, Differ-   ential Demand Ventilation shall be provided.   The outdoor intake opening shall be covered with a rain   hood that matches the exterior of the unit. Water elimina-   tor/filters shall be provided.   STANDARD LIMITED WARRANTIES   Simultaneous economizer/compressor operation is also   possible. Dampers shall fully close on power loss.   • • • • Compressor 5 Years   • MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and   return air dampers that are interlocked and positioned by   a 2-position, spring-return damper actuator. The maxi-   mum leakage rate for the outdoor air intake dampers   shall not exceed 2% when dampers are fully closed and   operating against a pressure differential of 0.5 IWG. A   unit-mounted potentiometer shall be provided to adjust   the outdoor and return air damper assembly to take in   the design CFM of outdoor air to meet the ventilation   requirements of the conditioned space during normal   operation. Whenever the indoor fan motor is energized,   the dampers open up to one of two pre-selected posi-   tions - regardless of the outdoor air enthalpy. Dampers   return to the fully closed position when the indoor fan   motor is de-energized. Dampers shall fully close on   power loss.   Heat Exchanger 10 Years   Electric Heat Element 5 Years   Other Parts 1 Year   OPTIONAL OUTDOOR AIR (Shall be made available by   either/or):   • ELECTRONIC ENTHALPY AUTOMATIC ECONO-   MIZER - Outdoor and return air dampers that are inter-   locked and positioned by a fully-modulating, spring-   return damper actuator. The maximum leakage rate for   the outdoor air intake dampers shall not exceed 2%   when dampers are fully closed and operating against a   pressure differential of 0.5 IWG. A unit-mounted potenti-   ometer shall be provided to adjust the outdoor and return   air damper assembly to take in CFM of outdoor air to   meet the minimum ventilation requirement of the condi-   tioned space during normal operation. During econo-   mizer operation, a mixed-air temperature control shall   modulate the outdoor and return air damper assembly to   prevent the supply air temperature from dropping below   55°F. Changeover from compressor to economizer oper-   ation shall be provided by an integral electronic enthalpy   control that feeds input into the basic module. The out-   door intake opening shall be covered with a rain hood   that matches the exterior of the unit. Water eliminator/fil-   OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE   • • ROOF CURB - 14" high, full perimeter curb with wood   nailer (shipped knocked-down).   100% BAROMETRIC RELIEF DAMPER - Contains a   rain hood, air inlet screen, exhaust damper and mount-   ing hardware. Used to relieve internal air pressure   through the unit.   Johnson Controls Unitary Products   39   
			
				  
				
					• • • • • • PROPANE CONVERSION KIT - Contains new orifices   and gas valve parts to convert from natural to L.P. gas.   One per unit required.   • • • STAINLESS STEEL HEAT EXCHANGER   STAINLESS STEEL DRAIN PAN   TECHNICOAT PHENOLIC COATED CONDENSER   AND EVAPORATOR COIL   HIGH ALTITUDE - NATURAL GAS - Contains orifices   required for applications between 2000 and 6000 feet   altitude.   • • • • • • • • ELECTRONIC SINGLE ENTHALPY ECONOMIZER   DIRTY FILTER SWITCH   HIGH ALTITUDE - PROPANE GAS - Contains orifices   required for applications between 2000 and 6000 feet   altitude. Must be used with propane conversion kit.   DOUBLE WALL   PHASE MONITOR   BURGLAR BARS - Designed to work with above roof   curbs, depending on unit model. Fits duct openings of   curb supply and return air openings.   COIL GUARD   POWERED GFI CONVENIENCE OUTLET   NON-POWERED GFI CONVENIENCE OUTLET   SIDE DUCT FLANGE - Supply and return air duct   flanges for side duct applications. Do not use on units   with power exhaust.   ® BAS CONTROLS - S implicity Intelli-Comfort™, CPC,   JOHNSON, HONEYWELL, NOVAR, YORK COMMER-   CIAL COMFORT SYSTEM (YCCS)   HIGH STATIC DRIVE - Includes blower pulley and belt   for higher CFM and/or static pressure requirements.   • • • BAS READY ECONOMIZER (2-10 V.D.C. Actuator with-   out a controller)   • • WOOD SKID - Allows unit to be handled with 90" forks.   HINGED FILTER DOOR ACCESS AND TOOL FREE   ACCESS PANELS   ECONOMIZER/MOTORIZED DAMPER RAIN HOOD   (DJN/E/C300 only) - Contains all hood panels and the   hardware for assembling.   HINGED TOOL FREE BLOWER, BLOWER MOTOR,   FILTER AND ELECTRICAL ACCESS PANELS   • • • ANTI-RECYCLE TIMER - Assures 5-minute off time   between compressor cycles.   • • • • • • HIGH STATIC DRIVE   2" PLEATED FILTERS   LOW AMBIENT KIT - Provides unit cooling operation   down to 0°F.   4" THROW AWAY FILTERS   DISCONNECT SWITCH   COIL GUARD KIT - Guard for cooling coil.   SUPPLY AIR SMOKE DETECTOR   RETURN AIR SMOKE DETECTOR   OTHER FACTORY INSTALLED OPTIONS   • POWER EXHAUST OPTION - To work in conjunction   with economizers.   Subject to change without notice. Printed in U.S.A.   261660-YTG-D-0708   Copyright © 2008 by Johnson Controls, Inc. All rights reserved.   Supersedes: 261660-YTG-C-0707   Johnson Controls Unitary Products   5005 York Drive   Norman, OK 73069   |