036-21044-003-A-0304
®
TECHNICAL
GUIDE 50Hz
TM
DESCRIPTION
®
®
YORK Predator units are convertible single packages with a
common footprint cabinet and common roof curb for all 7-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits. The units were designed for
light commercial applications and can be easily installed on a roof
curb, slab, roof jack, or frame.
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
DM090, 120, 150
®
All Predator units are self-contained and assembled on rigid full
perimeter base rails allowing for 3-way forklift access and over-
head rigging. Every unit is completely charged, wired, piped, and
tested at the factory to provide a quick and easy field installation.
All units are convertible between side and down airflow. A single
economizer design is used on side and down discharge applica-
tions, as well as all tonnage sizes.
7-1/2, 10, 12-1/2 NOMINAL TONS
9.0 - 10.0 EER
380/415-3-50
®
Predator units are available in the following configurations: cool-
ing only, cooling with electric heat, and cooling with gas heat.
Electric heaters are available as factory-installed options or as
field-installed accessories.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21044-003-A-0304
™ Control Board w/
Screw Connector for T-stat
Wiring and Network Connection
Filter Access
(2” Filters)
Terminal Block
for Hi-Voltage
Connection
Disconnect Location
(Optional Disconnect Switch)
Filter-Drier (Solid Core)
Condenser
Section
Second model
nameplate inside
hinged access
panel
Slide-out motor
and blower
assembly for
easy adjustment
and service
Dual stage
cooling for
maximum
comfort
Belt-Drive
Blower Motor
Power Ventor Motor
Compressor
#2 Access
(High-Eff
Compressor
w/ crankcase
heater)
20-gauge aluminized
steel tubular heat
exchanger for long life
(stainless steel option)
Base Rails w/ Fork-
lift Slots (3 Sides) &
Lifting Holes
Two-stage gas heat-
ing to maintain
warm, comfortable
temperature
Roof curbs in eight- and
fourteen-inch heights.
Slide-Out Drain
Pan w/ Steel 3/4”
NPT Connection
Roof curbs for transitioning
from York Sunline™ foot-
print to the DM Series foot-
print are also available
(field-installed accessory)
Tool-less
door latch
Side entry power
and control wiring
knockouts
Intelligent control board for
safe and efficient operation
Compressor #1 Access (High-Eff
Compressor w/ crankcase heater)
FIGURE 1 - PREDATOR® COMPONENT LOCATION
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
FEATURES
•
•
Standard Efficiency– All standard efficiency units have
a minimum EER of 9.0 (2.64 CoP). Gas/electric units
have electronic spark ignition and power vented combus-
tion with steady state efficiencies of 80%.
Both the unit control board and ignition control board uti-
lize flash codes to aid in diagnosis of unit malfunctions.
Unique alarm codes quickly identify the source of the
unit alarm.
®
Service Friendly – The Predator incorporates a num-
ber of enhancements which improve serviceability.
All units use the same standard filter size. This stan-
dardization removes any confusion on which filter sizes
are needed for replacement.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
The non-corrosive drain pan slides out of the unit to per-
mit easy cleaning. The drain pan is accessed by remov-
ing the drain pan cover plate on the rear of the unit.
Once the plate is removed, the drain pan slides out
through the rear of the unit.
Service time is reduced through the use of hinged, tool-
less panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unautho-
rized persons. It is recommended that the panels be
secured with screws once service is complete.
®
All Predator units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
•
Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively through-
out the units.
Unitary Products
3
036-21044-003-A-0304
®
•
•
Balanced Heating – The Predator offers “Ultimate
•
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
st
nd
Heating Comfort” with a balance between 1 and 2
stage gas heating. The 1 stage of a gas heat Predator
unit provides 60% of the heating capacity. Balanced
heating allows the unit to better maintain desired temper-
atures.
st
®
Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side sup-
ply/return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
•
System Protection - Suction line freezestats are sup-
plied on all units to protect against loss of charge and coil
frosting when the economizer operates at low outdoor air
temperatures while the compressors are running. Every
unit has solid-core liquid line filter-driers and high and
low-pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compres-
sors do not require crankcase heaters. Phase Monitors
are standard on units with scroll compressors. This
accessory monitors the incoming power to the unit and
protects the unit from phase loss and reversed phase
rotation.
•
•
Reliable – From the beginning – All units undergo com-
puter automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term –
All Predator units are painted with a long lasting, pow-
der paint that stands up over the life of the unit. The paint
used has been proven by a 750 hour salt spray test.
®
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
•
Advanced Controls - 3FJMIF@FQV™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
®
To further simplify planning and installation, Predator
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
(610 mm) on-center joists or between 48” (1219 mm) on-
center joists.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F (-17.8°C) outdoor ambient without additional
assistance. Optionally, the control board can be
programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
piped to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
•
•
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit
and protect the unit during shipment. The rails offer fork-
lift access from 3 sides, and rigging holes are available
so that an overhead crane can be used to place the units
on a roof.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. A clearly identified location is provided to mount a
field supplied electrical disconnect switch. Utility con-
nections can be made quickly and with a minimum
amount of field labor.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
All units are shipped with 2” (51 mm) filters installed.
4
Unitary Products
036-21044-003-A-0304
•
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to han-
dle most airflow requirements. For high static applica-
tions, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units
can supply nominal airflow at a minimum of 1.5” (375 Pa)
ESP.
•
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
•
•
Aluminized Steel Gas Heat Exchanger - For applica-
tions in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
FACTORY INSTALLED OPTIONS
YORK offers several equipment options factory installed, for
the Predator line.
®
®
•
•
Electric Heaters - The electric heaters range from 9kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
•
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to assemble
and mount the outdoor air hood (Provided). The econo-
mizer has spring return, fully modulating damper actua-
tors and is capable of introducing up to 100% outdoor air.
As the outdoor air intake dampers open, the return air
dampers close. The changeover from mechanical refrig-
eration to economizer operation is regulated by the stan-
dard single enthalpy input. There is an optional input
dual dry bulb available. To meet regulated air standards,
Disconnect Switch - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
•
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
the economizer control accepts an optional CO input for
2
demand ventilation. With single enthalpy input, the econ-
omizer control monitors outdoor air. The dual enthalpy kit
provides a second input used to monitor the return air.
With a dual input kit installed, the economizer control
compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible.
Phase Monitors - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of
phase condition. (Standard on units with Scroll Com-
pressors.)
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
•
•
Horizontal Economizer - (Without barometric relief) -
All features as the downflow economizer exist except
you must order the barometric relief separately. You
must order a 1EH0408 if you are installing a power
exhaust. You can order a 1RD0411 Barometric Relief
for horizontal flow economizers only.
•
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
BAS Ready Economizer -(With barometric relief) -
The economizer is provided with a Belimo actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully modu-
lating dampers capable of introducing up to 100% out-
side air. Also include 2” (51 mm) pleated filters.
•
•
•
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
•
•
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
Unitary Products
5
036-21044-003-A-0304
•
•
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
•
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
•
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
FIELD INSTALLED ACCESSORIES
YORK offers several equipment accessories for field instal-
lation, for the Predator line.
CO Sensor - Senses CO levels and automatically
2
2
®
overrides the economizer when levels rise above the
preset limits.
®
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters.
•
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the econo-
•
•
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
mizer control accepts an optional CO input for demand
2
•
•
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit pro-
vides a second input used to monitor the return air. With
a dual input kit installed, the economizer control com-
pares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
•
Horizontal Economizer - (Without barometric relief) -
All features as the downflow economizer exist except
you must order the barometric relief separately. You
must order a 1EH0408 if you are installing a power
exhaust. You can order a 1RD0411 Barometric Relief
for horizontal flow economizer.
•
•
Gas Heat High Altitude Kit - This kit converts a gas
heat unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and pro-
pane.
•
•
•
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains
the main burner orifices and gas valve replacement
springs.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
•
•
Gas Piping Kit - Contains pipe nipples, fittings and gas
cock required for gas supply connection with external
shut off.
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief/power exhaust hood when
applying to a horizontal flow application.
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the elec-
tric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
•
Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
6
Unitary Products
036-21044-003-A-0304
•
Low Limit / Compressor Lockout Kit
in 8” (203 mm) and 14” (356 mm) heights. For applica-
tions with security concerns, burglar bars are available
for the duct openings of the roof curbs.
1. Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during
cold outdoor conditions where there is a risk of
returning liquid refrigerant back to the compressors.
•
Roof Curb Transition - Single Piece Adapter (10” (254
mm) High) - Roof curbs for transitioning from Sunline™
®
units to Predator Magnum. Fits 7.5 to 12.5 Sunline™
2. Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing
the units first stage heating means when there is a
demand for cooling during cold outside conditions.
roof curbs only.
•
•
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
•
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
Thermostat - The units are designed to operate with 24-
volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only ther-
mostats, depending upon unit configuration.
•
•
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
Unitary Products
7
036-21044-003-A-0304
NOMENCLATURE
7½ - 12½ Ton Predator Model Number Nomenclature
D M 090 N10 A 7 A AA 3
Product Generation
Product Category
3 = Third Generation
D = Air Cond., Single Package
Voltage
Installation Options
Additional Options
Product Identifier
A = No Options Installed
B = Option 1
C = Option 2
7 = 380/415-3-50
(See Next Page)
M = R-22 Standard Efficiency
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2 & 4
L = Options 1, 3 & 4
M = Options 1, 2, 3 & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3 & 4
R = Options 3 & 4
Nominal Cooling Capacity - MBH
090 = 7-½ Ton
120 = 10 Ton
150 = 12-½ Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
Options
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
1 = Disconnect
2 = Non-Pwr’d Conv Outlet
3 = Smoke Detector S. A.
4 = Smoke Detector R. A.
Electric Heat Options
E09 = 9 kW Electric Heat
E18 = 18 kW Electric Heat
E24 = 24 kW Electric Heat
E36 = 36 kW Electric Heat
E54 = 54 kW Electric Heat
Airflow
A = Standard Motor
B = Standard Motor/Economizer/Barometric Relief (Downflow only)
C = Standard Motor/Economizer/Power Exhaust (Downflow only)
D = Standard Motor/Motorized Damper (Downflow only)
E = Standard Motor/Horizontal Economizer (No Barometric Relief)
L = Standard Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
M = Standard Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
N = High Static Motor
P = High Static Motor/Economizer/Barometric Relief (Downflow only)
Q = High Static Motor/Economizer/Power Exhaust (Downflow only)
R = High Static Motor/Motorized Damper (Downflow only)
S = High Static Motor/Horizontal Economizer (No Barometric Relief)
Y = High Static Motor/BAS Ready Econ (NoBASController)/Barometric Relief w/2" Pleated Filters (Downflow only)
Z = High Static Motor/BAS Ready Econ (NoBASController)/Power Exhaust w/2" Pleated Filters (Downflow only)
8
Unitary Products
036-21044-003-A-0304
NOMENCLATURE ADDITIONAL OPTIONS:ì
AA None
AB Phase Monitor
AC Coil Guard
AD Dirty Filter Switch
AE Phase Monitor & Coil Guard
AF Phase Monitor & Dirty Filter Switch
AG Coil Guard & Dirty Filter Switch
AH Phase Monitor, Coil Guard, & Dirty Filter Switch
CA CPC Controller with Dirty Filter Switch & Air Proving Switch
CB CPC Controller, DFS, APS & Phase Monitor
CC CPC Controller, DFS, APS & Coil Guard
CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CE CPC Controller, DFS, APS & Technicoat Cond. Coil
CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CJ CPC Controller, DFS, APS & Technicoat Evap. Coil
CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CR CPC Controller, DFS, APS, Technicoat Cond Coils, Phase Monitor, & 2” Pleated Filters
CV CPC Controller, DFS, APS, & 2” Pleated Filters
CX CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, Coil Guard
HA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
HB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard
HD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
HE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
HG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
HH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
HJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
HN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Unitary Products
9
036-21044-003-A-0304
HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
JB Johnson UNT Controller, DFS, APS & Phase Monitor
JC Johnson UNT Controller, DFS, APS & Coil Guard
JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
JE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
JF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
JG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
JH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
JJ
JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
JN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
NB Novar ETC-3 Controller, DFS, APS & Phase Monitor
NC Novar ETC-3 Controller, DFS, APS & Coil Guard
ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
NK Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
NL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
NM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
TA Technicoat Condenser Coil
TB Technicoat Condenser Coil & Phase Monitor
TC Technicoat Condenser Coil & Coil Guard
TD Technicoat Condenser Coil & Dirty Filter Switch
TE Technicoat Condenser Coil, Phase Monitor, & Coil Guard
TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
10
Unitary Products
036-21044-003-A-0304
TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
TH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TJ Technicoat Evaporator Coil
TK Technicoat Evaporator Coil & Phase Monitor
TL Technicoat Evaporator Coil & Coil Guard
TM Technicoat Evaporator Coil & Dirty Filter Switch
TN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
TR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
TS Technicoat Evaporator & Condenser Coils
TT Technicoat Evaporator & Condenser Coils & Phase Monitor
TU Technicoat Evaporator & Condenser Coils & Coil Guard
TV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
TY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
RC Coil Guard, Heavy Mil Clear Shipping Bag, Made in U.S.A. Flag Decal
Unitary Products
11
036-21044-003-A-0304
TABLE 1: PHYSICAL DATA
Models
120
Component
090
150
Blower, Centrifugal
Dia. X Wd. in.
(Dia. X Wd. mm.)
15 x 15
(381 x 381)
15 x 15
(381 x 381)
15 x 15
(381 x 381)
Evaporator
Blower
Motor, Standard - HP (kW)
Motor, Optional - HP (kW)
Rows
1-1/2 (1.1)
2 (1.5)
2
2 (1.5)
4 (3)
4 (3)
N/A
3
4
Fins per 2.54 cm (1 in.)
Height - in. (mm.)
15
15
15
Evaporator
Coil
32 (810)
40 (1020)
40 (1020)
2
2
10.6 (0.98)
13.2 (1.23)
13.2 (1.23)
Face Area - ft. (m )
Propeller Dia. - in. (mm.) ea.
Motor - HP (kW) ea.
24 (610)
1/3 (0.25)
3700 (1.75)
1
24 (610)
3/4 (0.56)
3700 (1.75)
1
24 (610)
3/4 (0.56)
3700 (1.75)
2
Condenser
Fan
(2 per Unit)
3
Airflow - CFM (m /s) ea.
Rows (each)
Fins per inch (2.54 mm)
Height - in. (mm.)
Condenser
Coil
(2 per unit)
20
20
20
28 (711)
44 (1120)
44 (1120)
2
2
9.2 (.86)
14.5 (1.35)
14.5 (1.35)
Face Area - ft. (m )
System 1 - lbs. (kg.)
System 2 - lbs. (kg.)
Quantity
4.38 (1.99)
4.13 (1.87)
2
6.75 (3.06)
6.13 (2.78)
2
11.0 (4.99)
10.0 (4.54)
2
Refrigerant
Charge
Compressors
Air Filters
Type
Recip
Recip
Scroll
Size
25 x 20 x 2
(635 x 508 x 51)
25 x 20 x 2
(635 x 508 x 51)
25 x 20 x 2
(635 x 508 x 51)
Wd. x Ht. x Thickness in.
(Wd. x Ht. x Thickness mm.)
Number Per Unit
4
4
4
12
Unitary Products
036-21044-003-A-0304
TABLE 2: CAPACITY RATINGS IMPERIAL
Cooling Capacity
(80 / 67-95°F)
Nominal
Electric
Heat
Gas Heat Capacity
Model
Sound
Rating
(dB)
Gas Line
Size
(in. OD)
Input
(MBH)
Output
Temp
Capacity
(MBH) Rise (°F)
1
Cooling Cap. (MBH)
Options
MBH
EER
(kW)
7, 14,
18, 27
DM
89
9.00
87
-
-
-
-
090
10
15
-
-
-
-
-
-
-
-
120
180
96
15-45
30-60
3/4
3/4
144
14, 18,
27, 41
DM
15
116
9.0
-
85
-
-
-
-
-
120
150
-
138
-
-
180
-
144
-
20-50
-
3/4
-
14, 18,
27, 41
DM
15
9.0
-
84
-
-
180
144
10-40
3/4
1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V.
TABLE 3: CAPACITY RATINGS METRIC
Cooling Capacity
Nominal
Gas Heat Capacity
Model
Electric
Heat
Sound
Rating
(dB)
(27/19-35°C)
Temp
Output
Rise
Gas Line
Size
(mm. OD)
Input
(kW)
Capacity
Cooling Cap.
(kW)
(kW)
2
1
Options
kW
(°C)
CoP
(kW)
7, 14,
18, 27
DM
26.1
2.64
87
-
-
-
090
(26.4)
10
15
-
-
-
-
-
-
-
-
35.1
52.7
28.1
42.2
8.3-25
17-33
19.05
19.05
14, 18,
27, 41
DM
15
34.0
2.64
85
-
-
-
-
-
120
(35.1)
-
40.4
-
-
2.64
-
-
52.7
-
42.2
-
11-28
-
19.05
-
14, 18,
27, 41
DM
15
84
-
150
(43.9)
-
52.7
42.2
5.6-22
19.05
1. Electric heaters rated at 415V. See tables 10 through 12 for kW ratings at 380V
2. CoP = Co-efficient of Performance (CoP = Cooling Capacity (kW) / Power Input (kW))
Unitary Products
13
036-21044-003-A-0304
TABLE 4: COOLING CAPACITY 7-1/2 TON UNIT - IMPERIAL
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
1
1
Tot.
Tot.
Tot.
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
WB
(°F)
1
2
2
CFM
2250
2625
3000
3375
3750
Cap.
Input
Input
(MBH)
(kW)
(MBH)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
104
96
88
84
107
99
90
87
110
102
93
8.6
8.4
8.2
8.2
8.7
8.5
8.3
8.2
8.8
8.6
8.3
8.3
8.8
8.6
8.4
8.3
8.9
8.7
8.4
8.4
60
74
87
84
66
81
90
87
72
88
93
89
77
94
95
91
83
101
97
92
54
68
81
83
59
73
87
86
63
79
93
89
68
84
95
91
72
89
97
92
47
61
75
77
51
66
80
83
55
71
86
89
58
74
91
91
61
78
95
92
41
55
68
71
43
58
73
75
46
62
77
80
48
64
81
81
49
67
84
81
34
48
62
64
36
51
65
68
37
53
69
71
38
54
71
71
38
56
73
70
-
-
98
90
80
78
101
92
83
81
104
95
86
83
106
97
87
84
108
99
88
9.2
9.0
8.6
8.6
9.3
9.1
8.7
8.7
9.4
9.2
8.8
8.8
9.4
9.2
8.9
8.9
9.5
9.3
8.9
8.9
57
71
80
78
63
78
83
81
69
86
86
83
74
92
87
84
79
97
88
86
50
64
75
77
55
71
80
80
60
77
86
83
64
82
87
84
68
86
88
86
44
58
69
71
48
63
75
77
51
68
81
83
54
72
85
84
57
75
88
86
37
51
63
64
40
55
68
69
43
59
72
74
44
62
75
74
46
64
77
75
31
45
56
58
32
48
60
62
34
51
64
66
34
52
65
64
34
53
66
63
-
-
42
55
58
-
43
58
60
-
44
60
63
-
44
61
61
-
35
49
51
-
35
50
53
-
36
51
54
-
35
51
51
-
39
50
51
-
40
52
54
-
42
55
57
-
42
55
55
-
32
43
45
-
33
45
46
-
33
46
48
-
32
45
45
-
89
112
104
95
91
115
106
97
45
62
59
33
51
48
42
55
52
30
44
41
92
86
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
91
81
73
71
94
84
75
74
97
87
78
76
99
88
79
77
101
90
81
79
9.8
9.5
9.1
9.1
9.9
9.6
9.3
9.3
10.0
9.7
9.4
9.4
10.1
9.8
9.4
9.4
10.1
9.8
9.5
9.5
54
67
73
71
60
74
75
74
66
82
78
76
71
85
79
77
76
89
81
79
48
61
71
71
52
67
74
73
57
73
78
76
61
78
79
77
65
82
81
79
41
54
64
64
45
59
70
70
49
64
76
76
51
68
78
77
54
71
81
79
35
48
58
58
37
52
62
63
40
55
67
67
41
58
68
67
43
60
69
68
28
42
51
52
30
44
55
55
31
47
58
58
31
48
58
57
32
49
58
56
-
-
84
73
66
65
87
76
68
67
89
78
70
69
91
80
71
70
93
81
73
72
10.4
10.0
9.7
51
64
66
65
57
71
68
67
63
78
70
69
68
79
71
70
73
81
73
72
45
57
66
65
50
63
68
67
54
69
70
69
58
74
71
70
62
79
73
72
39
51
59
58
42
56
65
64
46
60
70
69
48
64
71
70
51
67
73
72
32
45
53
52
35
48
57
56
37
52
61
60
38
54
61
60
40
56
62
60
26
38
46
45
27
40
49
48
28
43
53
51
28
44
51
50
29
45
50
49
-
-
35
45
45
-
37
47
47
-
38
49
50
-
38
48
47
-
29
38
39
-
29
40
40
-
29
41
41
-
28
38
37
-
32
40
39
-
33
42
41
-
34
44
43
-
34
42
40
-
25
34
33
-
25
34
33
-
25
35
34
-
24
32
30
-
2250
2625
3000
3375
3750
9.7
10.5
10.1
9.8
9.8
10.6
10.2
9.9
9.9
10.7
10.3
10.0
10.0
10.8
10.4
10.1
10.1
38
47
45
27
36
34
34
39
38
23
28
27
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
77
65
59
58
80
67
60
60
82
69
62
62
84
71
64
63
85
72
65
64
11.0
10.5
10.2
10.2
11.1
10.6
10.3
10.3
11.2
10.8
10.4
10.5
11.4
10.9
10.5
10.6
11.5
11.0
10.6
10.7
49
60
59
58
55
67
60
60
60
69
62
62
65
71
64
63
70
72
65
64
42
54
59
58
47
60
60
60
51
65
62
62
55
70
64
63
59
72
65
64
36
48
54
52
39
52
59
57
43
56
62
62
45
60
64
63
48
63
65
64
30
41
48
46
32
44
52
49
34
48
56
53
35
50
55
53
37
52
54
53
23
35
42
39
24
37
44
42
25
39
47
44
26
40
45
43
26
41
43
42
-
-
1
2
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
28
35
33
-
29
37
34
-
30
38
36
-
30
35
33
-
22
29
26
-
22
29
27
-
21
29
27
-
20
25
23
-
2250
2625
3000
3375
3750
30
31
31
19
20
20
14
Unitary Products
036-21044-003-A-0304
TABLE 5: COOLING CAPACITY 26.4 KW UNIT - METRIC
Air On
Temperature of Air on Condenser Coil 29°C
Evap. Coil
Temperature of Air on Condenser Coil 35°C
1
1
Tot.
Tot.
Tot.
Tot.
Sensible Capacity (kW)
Return Dry Bulb (°F)
Sensible Capacity (kW)
Return Dry Bulb (°C)
WB
(°C)
3
1
2
1
2
m /s
Cap.
(kW)
Input
(kW)
Cap.
(kW)
Input
(kW)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
31
28
26
25
31
29
27
25
32
30
27
26
33
30
28
27
34
31
28
27
8.6
8.4
8.2
8.2
8.7
8.5
8.3
8.2
8.8
8.6
8.3
8.3
8.8
8.6
8.4
8.3
8.9
8.7
8.4
8.4
18
22
26
25
19
24
26
25
21
26
27
26
23
28
28
27
24
29
28
27
16
20
24
24
17
22
26
25
19
23
27
26
20
25
28
27
21
26
28
27
14
18
22
23
15
19
24
24
16
21
25
26
17
22
27
27
18
23
28
27
12
16
20
21
13
17
21
22
13
18
23
24
14
19
24
24
14
20
25
24
10
14
18
19
10
15
19
20
11
16
20
21
11
16
21
21
11
16
21
21
-
-
29
26
24
23
30
27
24
24
31
28
25
24
31
28
25
25
32
29
26
25
9.2
9.0
8.6
8.6
9.3
9.1
8.7
8.7
9.4
9.2
8.8
8.8
9.4
9.2
8.9
8.9
9.5
9.3
8.9
8.9
17
21
24
23
18
23
24
24
20
25
25
24
22
27
25
25
23
29
26
25
15
19
22
23
16
21
24
23
18
23
25
24
19
24
25
25
20
25
26
25
13
17
20
21
14
18
22
23
15
20
24
24
16
21
25
25
17
22
26
25
11
15
18
19
12
16
20
20
13
17
21
22
13
18
22
22
13
19
23
22
9
-
-
9
12
16
17
-
13
17
18
-
13
18
18
-
13
18
18
-
10
14
15
-
10
15
15
-
10
15
16
-
10
15
15
-
13
16
17
9
11
15
15
-
12
15
16
-
12
16
17
-
12
16
16
-
1.06
1.24
1.42
1.59
1.77
13
13
-
10
13
14
-
10
14
14
-
14
18
18
10
15
19
19
10
15
19
19
10
15
19
19
9
13
13
-
9
13
12
13
18
17
10
15
14
12
16
15
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
27
24
21
21
28
25
22
22
28
25
23
22
29
26
23
23
29
26
24
23
9.8
9.5
9.1
9.1
9.9
9.6
9.3
9.3
10.0
9.7
9.4
9.4
10.1
9.8
9.4
9.4
10.1
9.8
9.5
9.5
16
20
21
21
18
22
22
22
19
24
23
22
21
25
23
23
22
26
24
23
14
18
21
21
15
20
22
22
17
21
23
22
18
23
23
23
19
24
24
23
12
16
19
19
13
17
20
21
14
19
22
22
15
20
23
23
16
21
24
23
10
14
17
17
11
15
18
18
12
16
20
20
12
17
20
20
13
18
20
20
8
-
-
8
11
11
-
25
21
19
19
25
22
20
20
26
23
21
20
27
23
21
21
27
24
21
21
10.4
10.0
9.7
15
19
19
19
17
21
20
20
19
23
21
20
20
23
21
21
21
24
21
21
13
17
19
19
15
19
20
20
16
20
21
20
17
22
21
21
18
23
21
21
11
15
17
17
12
16
19
19
13
18
21
20
14
19
21
21
15
20
21
21
9
8
-
9
-
7
10
10
-
12
15
15
9
13
16
16
9
14
17
17
9
14
17
17
9
10
13
13
-
11
14
14
-
11
14
15
-
11
14
14
-
13
15
15
10
14
17
16
11
15
18
18
11
16
18
18
12
16
18
18
11
14
13
8
12
14
14
8
13
15
15
8
13
15
15
8
1.06
1.24
1.42
1.59
1.77
12
11
-
10
12
12
-
10
13
12
-
10
12
12
-
9.7
10.5
10.1
9.8
8
7
12
12
-
10
10
-
9.8
10.6
10.2
9.9
9
7
12
12
-
10
10
-
7
9
9
-
7
8
9.9
10.7
10.3
10.0
10.0
10.8
10.4
10.1
10.1
8
11
11
-
8
11
10
14
17
17
11
14
13
13
15
14
10
12
11
8
Temperature of Air on Condenser Coil 52°C
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
23
19
17
17
23
20
18
18
24
20
18
18
25
21
19
19
25
21
19
19
11.0
10.5
10.2
10.2
11.1
10.6
10.3
10.3
11.2
10.8
10.4
10.5
11.4
10.9
10.5
10.6
11.5
11.0
10.6
10.7
14
18
17
17
16
20
18
18
18
20
18
18
19
21
19
19
21
21
19
19
12
16
17
17
14
17
18
18
15
19
18
18
16
20
19
19
17
21
19
19
11
14
16
15
12
15
17
17
13
17
18
18
13
18
19
19
14
19
19
19
9
7
-
8
10
10
-
-
1
2
These capacities are gross ratings. For net
capacity, deduct air blower motor. Refer to the
appropriate Blower Performance Table for the
kW of the supply air blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
12
14
13
9
10
12
12
7
11
13
12
7
11
14
13
7
12
13
13
8
6
8
8
-
6
9
8
-
6
9
8
-
6
7
7
-
1.06
1.24
1.42
1.59
1.77
13
15
14
10
14
16
16
10
15
16
16
11
15
16
16
9
11
10
-
9
11
10
-
9
10
10
-
9
9
12
12
12
5
6
6
9
Unitary Products
15
036-21044-003-A-0304
TABLE 6: COOLING CAPACITY 10 TON UNIT - IMPERIAL
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
1
1
Tot.
Tot.
Tot.
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
WB
(°F)
1
2
2
CFM
3000
3500
4000
4500
5000
Cap.
Input
Input
(MBH)
(kW)
(MBH)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
148
134
125
123
149
136
126
124
150
137
127
125
153
139
130
127
156
141
132
129
11.2
10.8
10.5
10.6
11.4
11.0
10.6
10.7
11.6
11.2
10.8
10.9
11.7
11.3
10.9
11.0
11.7
11.4
11.0
11.1
82
102
73
94
65
85
56
77
95
99
59
81
48
68
86
90
49
71
90
94
50
73
94
98
52
76
98
99
53
79
-
-
137
124
115
110
139
126
117
112
141
128
119
113
143
129
120
115
144
130
122
116
12.0
11.6
11.2
11.4
12.2
11.7
11.4
11.5
12.4
11.9
11.5
11.7
12.4
12.0
11.6
11.7
12.5
12.1
11.7
11.8
79
98
71
90
62
81
54
73
93
93
56
76
97
97
58
80
45
64
84
84
46
66
87
87
47
68
90
90
50
73
91
88
53
79
92
86
-
-
60
78
82
-
61
80
84
-
62
82
87
-
63
85
86
-
51
69
73
-
51
70
74
-
50
71
75
-
50
72
72
-
56
75
76
-
56
77
77
-
56
78
78
-
60
78
75
-
47
67
67
-
46
67
67
-
45
67
67
-
47
64
61
-
121 112 103
123 116 107
89
111 101
124 120 110 100
124 120 114 104
115 110 101
110 110 101
86
79
69
91
76
96
66
86
106
117 114 107
112 112 107
93
115 103
119 119 113 102
113 113 113 102
97
85
74
97
62
85
82
70
91
120 108
127 127 117 106
125 125 122 110
105
92
78
65
90
103
90
76
63
86
130 116 103
130 130 125 111
127 127 125 112
122 113 100
120 120 117 104
115 115 115 101
113
98
83
68
94
113
98
83
68
93
139 124 109
132 132 132 117 102
129 129 129 114 100
65
87
85
50
72
70
130 123 108
122 122 122 107
116 116 116 101
64
77
71
49
62
56
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
129
114
109
104
130
115
110
105
131
116
111
105
133
118
112
107
135
120
114
109
12.8
12.3
11.9
12.1
13.0
12.5
12.1
12.3
13.1
12.7
12.3
12.4
13.2
12.7
12.4
12.5
13.3
12.8
12.5
12.6
75
94
67
86
58
77
95
93
62
82
50
68
86
84
52
72
91
89
54
76
96
94
58
82
98
94
63
87
99
94
41
60
78
76
42
62
81
79
43
64
84
82
45
68
84
80
48
73
84
79
-
-
122
105
102
98
122
105
102
97
121
105
102
97
124
107
104
99
13.5
13.0
12.6
12.8
13.7
13.2
12.8
13.0
13.9
13.4
13.0
13.2
14.0
13.5
13.1
13.3
14.1
13.6
13.2
13.4
71
90
102
98
78
97
102 100
97
85
63
81
97
93
68
88
54
73
89
85
58
78
95
91
62
83
46
64
80
76
48
68
85
81
51
72
90
86
54
77
91
86
57
82
92
87
37
56
72
68
38
58
75
71
39
60
79
74
40
63
78
73
42
67
77
72
-
-
51
69
67
-
52
71
69
-
52
73
70
-
55
71
67
-
43
61
59
-
42
61
59
-
41
61
59
-
42
58
54
-
47
63
59
-
48
65
61
-
48
67
62
-
50
64
60
-
38
55
51
-
38
55
51
-
37
55
51
-
37
51
46
-
3000
3500
4000
4500
5000
109 103
104 102
82
72
92
102
110 107 101
105 103
89
110
111 111 108
105 105 105
98
115 108
112 112 111
107 107 107
99
66
87
95
74
95
78
99
105
102 102 102
97
94
107 102
104 104 104
99
102
110 110
106 106 106
102 102 102
97
80
97
67
90
85
72
95
99
87
99
72
96
107
92
77
127
110
106
102
120 116 102
114 114 114
109 109 109
58
69
64
43
54
49
52
62
57
37
47
42
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
115
96
96
92
113
95
95
90
112
94
93
89
115
96
96
92
118
99
99
14.2
13.7
13.3
13.5
14.5
13.9
13.5
13.8
14.7
14.2
13.8
14.0
14.8
14.3
13.8
14.1
14.9
14.4
13.9
14.2
67
85
96
92
74
93
95
90
82
94
93
89
89
96
96
92
96
99
99
95
59
77
91
85
64
84
92
87
70
91
93
89
76
96
96
92
81
99
99
95
50
68
83
77
54
74
89
83
58
79
93
89
62
85
96
92
66
90
99
95
42
60
74
68
44
64
79
73
47
68
84
77
49
72
84
79
51
76
84
80
33
51
66
59
34
54
69
63
35
56
73
66
36
58
71
65
37
61
69
65
-
-
1
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
43
57
51
-
44
59
53
-
44
61
54
-
45
58
52
-
34
48
42
-
33
49
42
-
33
49
43
-
32
44
39
-
3000
3500
4000
4500
5000
2
46
54
50
31
39
35
95
16
Unitary Products
036-21044-003-A-0304
TABLE 7: COOLING CAPACITY 35.1 KW UNIT - METRIC
Air On
Temperature of Air on Condenser Coil 29°C
Evap. Coil
Temperature of Air on Condenser Coil 35°C
1
1
Tot.
Tot.
Tot.
Tot.
Sensible Capacity (kW)
Return Dry Bulb (°C)
Sensible Capacity (kW)
Return Dry Bulb (°C)
WB
(°C)
3
1
2
1
2
m /s
Cap.
(kW)
Input
(kW)
Cap.
(kW)
Input
(kW)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
43
39
37
36
44
40
37
36
44
40
37
37
45
41
38
37
46
41
39
38
11.2
10.8
10.5
10.6
11.4
11.0
10.6
10.7
11.6
11.2
10.8
10.9
11.7
11.3
10.9
11.0
11.7
11.4
11.0
11.1
24
30
35
36
26
33
36
36
28
35
37
37
31
38
38
37
33
41
39
38
22
28
33
34
23
30
35
35
25
32
37
37
27
34
38
37
29
36
39
38
19
25
30
31
20
27
32
34
22
28
34
36
23
30
37
37
24
32
39
38
16
22
28
29
17
24
29
31
18
25
31
32
19
26
33
33
20
28
34
34
14
20
25
26
14
21
26
28
15
22
28
29
15
22
29
29
16
23
30
29
-
-
40
36
34
32
41
37
34
33
41
37
35
33
42
38
35
34
42
38
36
34
12.0
11.6
11.2
11.4
12.2
11.7
11.4
11.5
12.4
11.9
11.5
11.7
12.4
12.0
11.6
11.7
12.5
12.1
11.7
11.8
23
29
34
32
25
31
34
33
27
34
35
33
30
36
35
34
33
38
36
34
21
26
32
32
22
28
34
33
24
30
35
33
26
33
35
34
29
36
36
34
18
24
30
30
19
25
31
31
20
27
33
33
22
29
34
34
24
32
36
34
16
21
27
27
16
22
28
28
17
23
30
30
19
25
31
30
20
27
31
30
13
19
25
25
13
19
25
26
14
20
26
26
15
21
27
26
16
23
27
25
-
-
17
23
24
-
18
23
25
-
18
24
25
-
19
25
25
-
15
20
21
-
15
21
22
-
15
21
22
-
15
21
21
-
16
22
22
-
16
23
23
-
16
23
23
-
18
23
22
-
14
20
20
-
13
20
20
-
13
20
20
-
14
19
18
-
1.42
1.65
1.89
2.12
2.36
19
26
25
15
21
20
19
23
21
14
18
16
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
38
34
32
30
38
34
32
31
38
34
32
31
39
35
33
31
40
35
33
32
12.8
12.3
11.9
12.1
13.0
12.5
12.1
12.3
13.1
12.7
12.3
12.4
13.2
12.7
12.4
12.5
13.3
12.8
12.5
12.6
22
28
32
30
24
30
32
31
26
32
32
31
29
34
33
31
31
35
33
32
20
25
30
30
21
27
31
30
23
29
32
31
25
32
33
31
27
34
33
32
17
23
28
27
18
24
30
29
19
26
32
31
21
28
32
31
23
30
33
32
15
20
25
25
15
21
27
26
16
22
28
27
17
24
29
27
18
26
29
27
12
18
23
22
12
18
24
23
13
19
25
24
13
20
25
24
14
21
25
23
-
-
36
31
30
29
36
31
30
29
36
31
30
29
36
31
31
29
37
32
31
30
13.5
13.0
12.6
12.8
13.7
13.2
12.8
13.0
13.9
13.4
13.0
13.2
14.0
13.5
13.1
13.3
14.1
13.6
13.2
13.4
21
26
30
29
23
29
30
29
25
31
30
29
27
31
31
29
30
32
31
30
18
24
29
27
20
26
29
28
22
28
30
29
24
30
31
29
25
32
31
30
16
21
26
25
17
23
28
27
18
24
30
29
20
26
31
29
21
28
31
30
13
19
24
22
14
20
25
24
15
21
26
25
16
22
27
25
17
24
27
25
11
16
21
20
11
17
22
21
11
18
23
22
12
19
23
21
12
20
22
21
-
-
15
20
20
-
15
21
20
-
15
21
21
-
16
21
20
-
13
18
17
-
12
18
17
-
12
18
17
-
12
17
16
-
14
18
17
-
14
19
18
-
14
20
18
-
15
19
17
-
11
16
15
-
11
16
15
-
11
16
15
-
11
15
14
-
1.42
1.65
1.89
2.12
2.36
17
20
19
13
16
14
15
18
17
11
14
12
Temperature of Air on Condenser Coil 52°C
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
34
28
28
27
33
28
28
26
33
27
27
26
34
28
28
27
35
29
29
28
14.2
13.7
13.3
13.5
14.5
13.9
13.5
13.8
14.7
14.2
13.8
14.0
14.8
14.3
13.8
14.1
14.9
14.4
13.9
14.2
20
25
28
27
22
27
28
26
24
27
27
26
26
28
28
27
28
29
29
28
17
23
27
25
19
25
27
26
21
27
27
26
22
28
28
27
24
29
29
28
15
20
24
22
16
22
26
24
17
23
27
26
18
25
28
27
19
27
29
28
12
18
22
20
13
19
23
21
14
20
25
23
14
21
25
23
15
22
25
23
10
15
19
17
10
16
20
18
10
16
21
19
10
17
21
19
11
18
20
19
-
-
1
2
These capacities are gross ratings. For net
capacity, deduct air blower motor. Refer to the
appropriate Blower Performance Table for the
kW of the supply air blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
12
17
15
-
13
17
15
-
13
18
16
-
13
17
15
-
10
14
12
-
10
14
12
-
10
15
12
-
1.42
1.65
1.89
2.12
2.36
9
13
11
-
9
12
10
13
16
15
Unitary Products
17
036-21044-003-A-0304
TABLE 8: COOLING CAPACITY 12-1/2 TON UNIT - IMPERIAL
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
1
1
Tot.
Tot.
Tot.
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
WB
(°F)
1
2
2
CFM
3750
4375
5000
5625
6250
Cap.
Input
Input
(MBH)
(kW)
(MBH)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
150
140
123
118
155
145
127
122
161
150
132
126
165
153
135
129
169
157
138
133
11.8
11.5
11.2
11.3
11.8
11.5
11.2
11.3
11.8
11.5
11.3
11.3
11.9
11.6
11.3
11.4
11.9
11.6
11.4
11.4
90
80
69
94
58
83
95
95
63
90
47
72
84
84
50
77
90
90
53
82
96
96
65
-
-
143
132
117
111
148
137
121
115
153
142
125
119
157
146
129
123
162
150
132
126
13.0
12.6
12.4
12.5
13.0
12.5
12.4
12.4
12.9
12.5
12.3
12.4
13.1
12.6
12.5
12.5
13.2
12.8
12.6
12.7
88
78
67
90
56
79
91
90
61
86
99
97
65
92
45
69
80
79
48
73
86
84
50
78
92
90
62
95
93
89
74
-
-
115 104
123 116 105
118 116 105
61
73
73
-
64
77
77
-
67
82
82
-
84
82
79
-
51
63
63
-
52
65
65
-
53
67
67
-
68
65
62
-
111 101
117 112 102
111 111 100
58
70
68
-
61
73
72
-
63
77
75
-
79
77
73
-
47
59
57
-
48
61
59
-
49
63
61
-
62
60
56
-
101
88
75
98
86
73
99
128 115 102
127 124 115 103
122 121 115 103
124 111
121 119 111
115 115 110
111
96
82
67
97
109
94
80
140 126 111
132 132 125 111
126 126 125 111
132 115
149 141 134 118 101
135 135 132 115
129 129 129 112
153 134 116
157 157 157 138 120 101
138 138 138 119 101
133 133 133 114 95
136 122 107
125 125 121 106
119 119 119 105
99
82
129 112
95
79
143 136 128 112
129 129 126 110
123 123 123 106
148 130 111
150 150 150 131 112
132 132 132 113
126 126 126 107
98
96
78
97
93
83
63
58
94
76
70
75
58
51
82
77
95
89
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
135
124
110
105
139
129
114
109
144
133
118
113
148
136
120
115
151
139
123
118
14.3
13.8
13.6
13.8
14.3
13.8
13.6
13.7
14.3
13.8
13.6
13.7
14.4
13.9
13.7
13.8
14.5
14.0
13.8
13.9
86
108
110 108
105 105
96
119 108
114 113 106
109 109 103
75
97
64
87
97
94
70
95
54
76
86
84
58
82
93
91
62
89
43
65
75
73
45
70
81
78
47
74
86
83
55
86
86
82
63
98
86
81
-
-
127
117
103
99
15.6
15.1
14.9
15.0
15.6
15.1
14.9
15.0
15.6
15.1
14.9
15.0
15.7
15.2
15.0
15.1
15.8
15.3
15.0
15.2
83
105
103 103
99
93
115 104
107 106 101
103 103
102 88
124 114
110 110 110
106 106 106
72
94
62
83
92
89
67
91
51
73
81
78
55
79
88
85
59
85
95
91
64
93
95
91
70
40
62
71
67
42
66
76
72
44
70
80
76
48
77
79
75
52
83
77
73
-
-
55
65
62
-
57
68
66
-
59
72
69
-
69
69
65
-
44
54
52
-
44
56
53
-
45
57
54
-
53
53
49
-
51
60
57
-
53
63
59
-
56
66
62
-
60
62
58
-
41
49
46
-
41
50
47
-
41
51
47
-
43
46
41
-
3750
4375
5000
5625
6250
99
80
83
131
121
107
103
135
124
110
106
138
127
112
108
140
129
115
110
97
73
99
106
91
76
130 118 103
118 118 115 101
113 113 112
121 105 88
135 129 119 103
120 120 119 103
115 115 115
137 119 100
139 139 135 116
123 123 123 105
98
72
114
98
81
127 122 110
112 112 112
108 108 108
126 107
129 129 120 102
115 115 115
110 110 110
99
81
89
79
67
62
61
49
43
65
59
54
46
40
36
96
91
118 118 118
99
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
119
109
97
16.9
16.4
16.1
16.3
16.9
16.4
16.1
16.3
16.9
16.4
16.1
16.3
17.0
16.5
16.2
16.4
17.1
16.5
16.3
16.5
80
101
97
93
90
70
91
97
93
77
59
80
87
83
64
88
96
91
70
95
48
69
77
72
52
75
83
78
56
81
89
84
57
84
88
84
59
87
87
84
37
59
66
62
39
62
70
66
41
66
75
70
41
67
72
67
40
69
69
65
-
-
1
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
48
55
51
-
50
58
53
-
52
60
55
-
51
55
51
-
37
44
40
-
37
45
40
-
37
46
41
-
34
38
34
-
3750
4375
5000
5625
6250
93
122
112
100
96
126
115
102
99
128
117
104
101
130
119
106
102
110 100
100 100
96
99
115 110
102 102 102
2
96
85
99
107
99
91
99
74
117 115 101
104 104 104
101 101 101
115
96
78
119 119 106
106 106 106
102 102 102
50
50
46
31
31
28
18
Unitary Products
036-21044-003-A-0304
TABLE 9: COOLING CAPACITY 43.9 KW UNIT - METRIC
Air On
Temperature of Air on Condenser Coil 29°C
Evap. Coil
Temperature of Air on Condenser Coil 35°C
1
1
Tot.
Tot.
Tot.
Tot.
Sensible Capacity (kW)
Return Dry Bulb (°C)
Sensible Capacity (kW)
Return Dry Bulb (°C)
WB
(°C)
3
1
2
1
2
m /s
Cap.
(kW)
Input
(kW)
Cap.
(kW)
Input
(kW)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
44
41
36
35
46
42
37
36
47
44
39
37
48
45
39
38
49
46
40
39
11.8
11.5
11.2
11.3
11.8
11.5
11.2
11.3
11.8
11.5
11.3
11.3
11.9
11.6
11.3
11.4
11.9
11.6
11.4
11.4
26
34
36
35
29
37
37
36
33
41
39
37
39
44
39
38
45
46
40
39
23
31
34
34
26
34
36
36
28
37
39
37
34
41
39
38
39
46
40
39
20
27
31
31
22
30
34
34
24
33
37
37
29
39
39
38
34
46
40
39
17
24
28
28
18
26
30
30
20
28
32
32
24
34
34
33
28
41
35
33
14
21
25
25
15
23
26
26
15
24
28
28
19
30
29
28
23
35
30
28
-
-
42
39
34
33
43
40
35
34
45
42
37
35
46
43
38
36
47
44
39
37
13.0
12.6
12.4
12.5
13.0
12.5
12.4
12.4
12.9
12.5
12.3
12.4
13.1
12.6
12.5
12.5
13.2
12.8
12.6
12.7
26
33
34
33
29
36
35
34
32
40
37
35
38
42
38
36
44
44
39
37
23
30
33
33
25
33
35
34
28
36
37
35
33
40
38
36
38
44
39
37
20
26
30
29
21
29
33
32
23
31
35
35
28
38
37
36
33
44
39
37
16
23
27
26
18
25
29
28
19
27
31
31
23
33
32
31
27
38
33
31
13
20
24
23
14
21
25
25
15
23
27
26
18
28
27
26
22
33
28
26
-
-
18
21
21
-
19
23
23
-
20
24
24
-
25
24
23
-
15
18
18
-
15
19
19
-
15
20
20
-
20
19
18
-
17
20
20
-
18
22
21
-
19
23
22
-
23
22
21
-
14
17
17
-
14
18
17
-
14
18
18
-
18
18
16
-
1.77
2.06
2.36
2.65
2.95
30
24
22
24
19
17
27
22
21
22
17
15
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
39
36
32
31
41
38
33
32
42
39
34
33
43
40
35
34
44
41
36
35
14.3
13.8
13.6
13.8
14.3
13.8
13.6
13.7
14.3
13.8
13.6
13.7
14.4
13.9
13.7
13.8
14.5
14.0
13.8
13.9
25
32
32
31
28
35
33
32
31
38
34
33
36
40
35
34
40
41
36
35
22
29
32
31
24
32
33
32
27
35
34
33
31
38
35
34
35
41
36
35
19
25
28
28
21
28
31
30
22
30
34
33
26
35
35
34
29
40
36
35
16
22
25
25
17
24
27
27
18
26
30
29
21
30
30
29
24
34
31
29
13
19
22
21
13
20
24
23
14
22
25
24
16
25
25
24
18
29
25
24
-
-
37
34
30
29
38
35
31
30
40
36
32
31
40
37
33
32
41
38
34
32
15.6
15.1
14.9
15.0
15.6
15.1
14.9
15.0
15.6
15.1
14.9
15.0
15.7
15.2
15.0
15.1
15.8
15.3
15.0
15.2
24
31
30
29
27
34
31
30
30
36
32
31
33
37
33
32
37
38
34
32
21
28
30
29
23
30
31
30
26
33
32
31
29
36
33
32
32
38
34
32
18
24
27
26
20
27
30
28
21
29
32
31
24
32
33
32
26
35
34
32
15
21
24
23
16
23
26
25
17
25
28
27
19
27
28
27
21
30
28
27
12
18
21
20
12
19
22
21
13
21
24
22
14
22
23
22
15
24
23
21
-
-
16
19
18
-
17
20
19
-
17
21
20
-
20
20
19
-
13
16
15
-
13
16
15
-
13
17
16
-
15
15
14
-
15
18
17
-
16
18
17
-
16
19
18
-
18
18
17
-
12
14
13
-
12
15
14
-
12
15
14
-
13
13
12
-
1.77
2.06
2.36
2.65
2.95
23
20
18
18
14
13
19
17
16
13
12
10
Temperature of Air on Condenser Coil 52°C
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
22
19
17
14
35
32
28
27
36
33
29
28
37
34
30
29
37
34
31
29
38
35
31
30
16.9
16.4
16.1
16.3
16.9
16.4
16.1
16.3
16.9
16.4
16.1
16.3
17.0
16.5
16.2
16.4
17.1
16.5
16.3
16.5
24
30
28
27
26
32
29
28
29
34
30
29
31
34
31
29
34
35
31
30
20
27
28
27
23
29
29
28
25
32
30
29
27
34
31
29
28
35
31
30
17
23
26
24
19
26
28
27
21
28
30
29
22
29
31
29
23
31
31
30
14
20
22
21
15
22
24
23
16
24
26
25
17
25
26
25
17
26
26
24
11
17
19
18
11
18
21
19
12
19
22
20
12
20
21
20
12
20
20
19
-
-
1
2
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBh = 3.415
x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
14
16
15
-
15
17
16
-
15
18
16
-
15
16
15
-
11
13
12
-
11
13
12
-
11
13
12
-
10
11
10
-
1.77
2.06
2.36
2.65
2.95
15
15
14
9
9
8
Unitary Products
19
036-21044-003-A-0304
TABLE 10: ELECTRICAL DATA 7-1/2 TON
MCA
Max Fuse Size
OD
Min. Circuit
Ampacity
(Amps)
Max Fuse2
w/Power
Size (Amps)
Supply Blower Pwr Exh
w/Power
Exhaust
(Amps)
Compressors
Fan
Motor FLA
Motor
Exhaust
(Amps)
Electric
Heater
Model No.
Motors
Actual Heater
Voltage1
kW
Amps
1.5 HP 2 HP
1.5 HP
(1.1
2 HP
(1.5
1.5 HP 2 HP 1.5 HP 2 HP
(1.1
kW)
1.5 HP
(1.1
kW)
2 HP
(1.5
kW)
RLA
ea.
LRA
ea.
FLA
ea.
(1.1
kW)
(1.5
kW)
FLA
(1.5
kW)
(1.1
kW)
(1.5
kW)
kW)
25.2
25.2
26.8
33.9
45.8
25.2
25.2
28.9
36.5
49.5
kW)
26.1
26.1
28.0
35.0
47.0
26.1
26.1
30.0
37.6
50.7
None
-
-
27.4
27.4
29.6
36.6
48.6
27.4
27.4
31.6
39.3
52.3
28.3
28.3
30.7
37.7
49.7
28.3
28.3
32.7
40.4
53.4
30
30
30
35
50
30
30
30
40
50
30
30
30
35
50
30
30
30
40
60
35
35
35
40
50
35
35
35
40
60
35
35
35
40
50
35
35
35
40
60
2TP04520950
2TP04521850
2TP04522450
2TP04523650
None
5.6
8.5
380
415
8.3
8.3
62
62
1.1
1.1
4.3
4.3
5.2
5.2
2.2
2.2
11.3
15.0
21.3
-
17.2
22.8
32.4
-
2TP04520950
2TP04521850
2TP04522450
2TP04523650
6.7
9.3
13.5
17.9
25.4
18.8
24.9
35.3
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
2. Maximum HACR breaker of the same amp size is acceptable.
TABLE 11: ELECTRICAL DATA 10 TON
MCA
Max Fuse Size
w/Power
Exhaust
OD
Supply Blower Pwr Exh
Compressors Fan
Min. Circuit
Ampacity
(Amps)
Max Fuse2
w/Power
Exhaust
(Amps)
Motor FLA
Motor
Size (Amps)
Electric
Heater
Model No.
Motors
Actual Heater
(Amps)
Voltage1
kW
Amps
2 HP
(1.5
kW)
4 HP
(3
kW)
RLA LRA
FLA
ea.
2 HP
4 HP
2 HP
4 HP
2 HP
4 HP
2 HP
4 HP
FLA
ea.
ea.
(1.5 kW) (3 kW)
(1.5 kW) (3 kW) (1.5 kW) (3 kW) (1.5 kW) (3 kW)
None
-
-
29.0
29.0
35.0
47.0
70.7
29.0
30.0
37.6
50.7
76.8
31.3
31.3
37.9
49.8
73.6
31.3
32.9
40.5
53.5
79.6
31.2
31.2
37.7
49.7
73.4
31.2
32.7
40.4
53.4
79.5
33.5
33.5
40.6
52.6
76.3
33.5
35.6
43.3
56.3
82.4
35
35
35
50
80
35
35
40
60
80
40
40
40
50
80
40
40
45
60
80
40
40
40
50
80
40
40
45
60
80
40
40
45
60
80
40
40
45
60
90
2TP04521850
2TP04522450
2TP04523650
2TP04525450
None
11.3
15.0
21.3
33.8
-
17.2
22.8
32.4
51.4
-
380
415
9.6
79
1.1
1.1
5.2
5.2
7.5
7.5
2.2
2.2
2TP04521850
2TP04522450
2TP04523650
2TP04525450
13.5
17.9
25.4
40.4
18.8
24.9
35.3
56.2
9.6
79
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
2. Maximum HACR breaker of the same amp size is acceptable.
TABLE 12: ELECTRICAL DATA 12-1/2 TON
Max Fuse
Size
w/Power
Exhaust
(Amps)
Max
Min. Cir-
cuit
Ampacity Exhaust
(Amps)
MCA
OD
Fan
Motors
Supply Air
Blower
Motor FLA
Fuse2
Size
Pwr Exh
Motor
w/Power
Compressors
Electric
Heater
Model No.
Actual
kW
Heater
Amps
Voltage1
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
4 HP
(3 kW)
4 HP
(3 kW)
4 HP
(3 kW)
4 HP
(3 kW)
4 HP (3 kW)
FLA
None
-
-
36.7
36.7
37.9
49.8
73.6
36.7
36.7
40.5
53.5
79.6
38.9
38.9
40.6
52.6
76.3
38.9
38.9
43.3
56.3
82.4
45
45
45
50
80
45
45
45
60
80
50
50
50
60
80
50
50
50
60
90
2TP04521850
2TP04522450
2TP04523650
2TP04525450
None
11.3
15.0
21.3
33.8
-
17.2
22.8
32.4
51.4
-
380
415
12.0
12.0
91
1.1
1.1
7.5
2.2
2TP04521850
2TP04522450
2TP04523650
2TP04525450
13.5
17.9
25.4
40.4
18.8
24.9
35.3
56.2
101
7.5
2.2
1. Unit voltage limitations: minimum utilization 342 volts, maximum utilization 457 volts.
2. Maximum HACR breaker of the same amp size is acceptable.
20
Unitary Products
036-21044-003-A-0304
TABLE 13: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
0.2
0.4
0.6
0.8
1.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3698 1382 1.48 3527 1249 1.34
3591 1424 1.53 3288 1242 1.33 3093 1120
1.20
3430 1451 1.56 3183 1276 1.37 2819 1104
1.18 2550
977
1.05
3312 1490 1.60 2975 1287 1.38 2593 1101
1.18
-
-
-
-
-
-
-
-
-
-
-
-
-
3086 1480 1.59 2679 1269 1.36 2154 1059 1.14
-
-
TABLE 14: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.75
1.55
1.33
-
1.38
1.24
1.10
-
1.11
0.99
0.88
-
1.66
1.46
1.20
-
1.25
1.12
0.98
-
1.00
0.90
0.78
-
100
149
199
249
-
-
-
-
-
-
1.69
1.50
1.22
-
1.42
1.28
1.10
-
1.14
1.02
0.88
-
-
-
-
-
-
-
-
-
-
1.62
1.40
1.02
1.45
1.29
1.06
1.16
1.03
0.85
1.56
1.26
1.49
1.27
1.19
1.02
1.46
1.48
1.18
-
-
-
-
-
-
TABLE 15: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
0.4
0.6
0.8
1.0
1.2
1.4
1.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4052 1830 1.96 3715 1559 1.67
4016 1933 2.07 3677 1667 1.79 3342 1422 1.52
3991 2032 2.18 3639 1745 1.87 3270 1504 1.61 2858 1261 1.35
3953 2151 2.31 3576 1833 1.97 3191 1573 1.69 2702 1307 1.40
-
-
-
-
-
-
-
-
-
-
-
-
3802 2195 2.35 3544 1941 2.08 3040 1626 1.74 2327 1290 1.38
-
-
-
-
-
-
-
-
-
3379 2001 2.15 2913 1674 1.80
2552 1642 1.76
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Unitary Products
21
036-21044-003-A-0304
TABLE 16: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
3
In
Out
In
Out
In
Out
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
100
149
199
249
299
349
399
-
-
-
-
-
-
-
-
-
-
-
-
1.91
1.74
1.54
1.28
-
1.83
1.67
1.50
1.31
-
1.46
1.33
1.20
1.05
-
1.75
1.56
1.25
-
-
-
-
-
-
-
-
-
1.90
1.72
1.51
1.10
-
1.93
1.75
1.57
1.29
-
1.55
1.40
1.26
1.03
-
1.58
1.42
1.14
-
-
-
-
-
-
1.88
1.69
1.43
-
2.03
1.83
1.63
-
1.63
1.47
1.30
-
1.35
1.26
1.01
-
-
-
1.87
1.67
1.37
-
2.15
1.94
1.67
-
1.72
1.55
1.34
-
-
-
-
-
-
-
-
-
-
-
-
-
1.79
1.59
1.20
2.20
2.00
1.64
1.76
1.60
1.31
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 17: BLOWER PERFORMANCE 10 TON STANDARD MOTOR - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
4820 2675 2.87 4582 2362 2.53 4319 2080 2.23 4086 1842 1.98 3863 1648 1.77 3590 1430 1.53
4522 2496 2.68 4307 2215 2.38 4025 1941 2.08 3713 1678 1.80 3464 1499 1.61 3149 1291 1.38
0.4
0.6
0.8
1.0
1.2
1.4
4223 2332 2.50 3973 2062 2.21 3656 1783 1.91 3363 1550 1.66 3026 1350 1.45
-
-
-
-
-
-
-
-
-
-
-
-
3913 2174 2.33 3679 1923 2.06 3262 1619 1.74 2721 1330 1.43
-
-
-
-
-
-
-
-
-
3521 1978 2.12 3104 1693 1.82
2790 1660 1.78
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 18: BLOWER PERFORMANCE 10 TON STANDARD MOTOR - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
100
149
199
249
299
349
2.27
2.13
1.99
1.85
1.66
1.32
2.68
2.50
2.33
2.17
1.98
1.66
2.14
2.00
1.87
1.74
1.58
1.33
2.16
2.03
1.88
1.74
1.46
-
2.36
2.22
2.06
1.92
1.69
-
1.89
1.77
1.65
1.54
1.35
-
2.04
1.90
1.73
1.54
-
2.08
1.94
1.78
1.62
-
1.66
1.55
1.43
1.30
-
1.93
1.75
1.59
1.28
-
1.84
1.68
1.55
1.33
-
1.47
1.34
1.24
1.06
-
1.82
1.65
1.32
1.69
1.43
1.14
1.63
1.50
1.20
1.49
1.29
1.03
1.43
1.35
1.08
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
22
Unitary Products
036-21044-003-A-0304
TABLE 19: BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4960 2495 2.68
5091 2745 2.94 4646 2314 2.48
5078 2937 3.15 4839 2584 2.77 4347 2153 2.31
5075 3117
3.34 4767 2730 2.93 4487 2377 2.55 3946 1942 2.08
5068 3308 3.55 4742 2881 3.09 4427 2513 2.69 4108 2159 2.32 3501 1723 1.85
5079 3595 3.86 4787 3105 3.33 4452 2713 2.91 4012 2259 2.42 3665 1926 2.07
4739 3316 3.56 4482 2892 3.10 4098 2474 2.65 3543 2006 2.15 3057 1642 1.76
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4461 3111
3997 2782 2.98 3400 2219 2.38
3496 2480 2.66
3.34 4070 2621 2.81 3552 2160 2.32
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 20: BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
100
149
199
249
299
349
399
448
498
548
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.34
2.50
2.00
2.40
2.28
2.12
1.94
1.73
1.44
-
2.75
2.58
2.38
2.16
1.93
1.64
-
2.20
2.07
1.90
1.73
1.54
1.31
-
2.19
2.31
1.85
-
-
-
-
-
-
-
-
-
2.40
2.25
2.09
1.89
1.67
-
2.94
2.73
2.51
2.26
2.01
-
2.35
2.18
2.01
1.81
1.60
-
2.05
2.15
1.72
-
-
-
-
-
-
2.40
2.24
2.10
1.93
1.68
-
3.12
2.88
2.71
2.47
2.16
-
2.49
2.30
2.17
1.98
1.73
-
1.86
1.94
1.55
-
-
-
2.39
2.26
2.12
1.92
1.60
-
3.31
3.11
2.89
2.62
2.22
-
2.65
2.48
2.31
2.10
1.78
-
1.65
1.72
1.38
2.40
2.24
2.11
1.89
1.65
3.60
3.32
3.11
2.78
2.48
2.88
2.65
2.49
2.23
1.98
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Unitary Products
23
036-21044-003-A-0304
TABLE 21: BLOWER PERFORMANCE 12-1/2 TON - SIDE DUCT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
-
-
-
-
-
-
6130 4171 4.47 5915 3774 4.05 5610 3309 3.55 5396 2948 3.16 4960 2495 2.68
5850 3932 4.22 5648 3565 3.82 5363 3136 3.36 5091 2745 2.94 4646 2314 2.48
5870 4273 4.58 5567 3715 3.98 5406 3380 3.62 5078 2937 3.15 4839 2584 2.77 4347 2153 2.31
5652 4087 4.38 5327 3518 3.77 5075 3117 3.34 4767 2730 2.93 4487 2377 2.55 3946 1942 2.08
5350 3820 4.10 5068 3308 3.55 4742 2881 3.09 4427 2513 2.69 4108 2159 2.32
5079 3595 3.86 4787 3105 3.33 4452 2713 2.91 4012 2259 2.42 3665 1926 2.07
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4739 3316 3.56 4482 2892 3.10 4098 2474 2.65
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4461 3111
3.34 4070 2621 2.81
-
-
-
-
-
-
3997 2782 2.98
-
-
-
TABLE 22: BLOWER PERFORMANCE 12-1/2 TON - SIDE DUCT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
100
149
199
249
299
349
399
448
498
-
-
-
2.89
2.76
2.63
2.51
2.39
2.26
2.12
1.92
-
4.17
3.93
3.72
3.52
3.31
3.11
2.89
2.62
-
3.34
3.15
2.97
2.81
2.65
2.48
2.31
2.10
-
2.79
2.67
2.55
2.40
2.24
2.10
1.93
-
3.77
3.57
3.38
3.12
2.88
2.71
2.47
-
3.02
2.85
2.70
2.49
2.30
2.17
1.98
2.65
2.53
2.40
2.25
2.09
1.89
-
3.31
3.14
2.94
2.73
2.51
2.26
-
2.65
2.51
2.35
2.18
2.01
1.81
-
2.55
2.40
2.28
2.12
1.94
1.73
-
2.95
2.75
2.58
2.38
2.16
1.93
-
2.36
2.20
2.07
1.90
1.73
1.54
-
2.34
2.50
2.00
-
-
-
2.19
2.31
1.85
2.77
2.67
2.52
2.40
2.24
2.11
1.89
4.27
4.09
3.82
3.60
3.32
3.11
2.78
3.42
3.27
3.06
2.88
2.65
2.49
2.23
2.05
2.15
1.72
1.86
1.94
1.55
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
24
Unitary Products
036-21044-003-A-0304
TABLE 23: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
1.90
1.60
1.53
1.40
1.22
-
1.49
1.37
1.21
1.05
-
1.32
1.19
1.05
-
1.20
1.08
0.95
-
0.2
0.4
0.6
0.8
1.0
-
-
-
3838 1772
3530 1491
3361 1425
3012 1301
2484 1141
3487 1385
3173 1275
2707 1131
3260 1234
3091 1119
2667 1006
1.79
3299 1485 1.592 3589 1670
3355 1506 1.62 3240 1535
3095 1409 1.51 2791 1380
2846
1111
1.65
1.48
2333
980
2151
887
2088
-
978
-
-
-
-
-
-
-
-
-
1.31
2519 1219
2241 1216 1.30
-
-
-
-
TABLE 24: BLOWER PERFORMANCE 7-1/2 TON STANDARD MOTOR - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
50
-
-
-
1.81
1.69
1.53
1.32
1.06
1.77
1.67
1.54
1.38
1.22
1.42
1.34
1.23
1.10
0.97
1.67
1.59
1.42
1.17
-
1.49
1.43
1.30
1.14
-
1.19
1.14
1.04
0.91
-
1.65
1.50
1.28
0.99
-
1.39
1.27
1.13
0.98
-
1.11
1.02
0.90
0.78
-
1.54
1.34
1.10
-
1.23
1.11
0.98
-
0.99
0.89
0.78
-
1.46
1.26
1.01
-
1.12
1.01
0.89
-
0.90
0.80
0.71
-
100
149
199
249
1.56
1.58
1.46
1.19
1.48
1.51
1.41
1.22
1.19
1.21
1.13
0.98
-
-
-
-
-
-
TABLE 25: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
1.88
1.74
1.58
1.41
1.23
-
1.63
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3884 1754
3576 1624
3183 1473
2707 1311
2146 1151
3611 1520
3282 1400
2862 1263
2352 1119
1.98
1.81
1.64
1.47
1.32
-
1.50
3837 1843
3491 1691
3083 1530
2614 1372
2082 1227
2.07
1.90
1.73
1.56
-
1.35
-
4054 2201 2.36 3766 1926
2.18
2.00
1.80
1.61
-
1.20
-
3735 2037
3362 1861
2938 1682
2461 1506
3412 1769
3014 1611
2572 1457
2.27
2.07
1.86
1.63
3626 2112
3227 1931
2778 1733
2279 1522
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Unitary Products
25
036-21044-003-A-0304
TABLE 26: BLOWER PERFORMANCE 7-1/2 TON OPTIONAL MOTOR - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
In
(kW)
Out
3
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
3
3
3
3
3
m /s
m /s
m /s
m /s
(kW)
m /s
m /s
50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1.83
1.75
1.62
1.47
1.31
1.15
-
1.40 1.70
1.30 1.55
1.18 1.35
1.05 1.11
1.52
1.22
100
149
199
249
-
-
-
1.81
1.84
1.69
1.53
1.37
1.23
-
1.47 1.69
1.35 1.50
1.22 1.28
1.10 1.01
1.40
1.12
-
-
-
1.91
1.76
2.20
2.04
1.86
1.68
1.51
-
1.76 1.78
1.63 1.61
1.49 1.42
1.35 1.21
1.93
1.77
1.61
1.46
-
1.54 1.65
1.42 1.46
1.29 1.23
1.17 0.98
1.26
1.01
-
1.12
0.90
1.71
2.11
1.93
1.73
1.52
1.69 1.59
1.54 1.39
1.39 1.16
0.92
-
-
-
-
-
-
-
-
-
-
-
-
299 1.52
0.98
-
-
-
-
-
-
349 1.31
1.20
-
-
-
-
-
-
-
-
-
-
399
1.08
1.22
-
-
-
-
TABLE 27: BLOWER PERFORMANCE 10 TON STANDARD MOTOR - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
1.89
1.71
1.58
1.51
0.2
0.4
0.6
0.8
1.0
1.2
4543 2511
4311 2381
4032 2232
3706 2068
3333 1892
2914 1711
2.69 4362 2250 2.41 4139 1996 2.14 3911 1766
3719 1594
3386 1471
3518 1407
3153 1293
2.55
2.39
2.22
2.03
1.83
2.28
2.13
1.95
1.76
-
2.01
1.84
1.66
-
1.76
1.39
4115 2127
3804 1982
3428 1818
2989 1644
3862 1871
3508 1720
3078 1548
3611 1644
3246 1506
1.61
2971 1332 1.43
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 28: BLOWER PERFORMANCE 10 TON STANDARD MOTOR - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
50
2.14
2.03
1.90
1.75
1.57
1.38
2.51
2.38
2.23
2.07
1.89
1.71
2.01
1.91
1.79
1.65
1.51
1.37
2.06
1.94
1.80
1.62
1.41
-
2.25
2.13
1.98
1.82
1.64
-
1.80
1.70
1.59
1.45
1.32
-
1.95
1.82
1.66
1.45
-
2.00
1.87
1.72
1.55
-
1.60
1.50
1.38
1.24
-
1.85
1.77
1.41
1.75
1.59
1.27
1.66
1.41
1.13
100
149
199
249
299
1.70
1.64
1.31
1.60
1.47
1.18
1.49
1.29
1.03
1.53
1.51
1.20
1.40
1.33
1.07
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
26
Unitary Products
036-21044-003-A-0304
TABLE 29: BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
-
2.86
2.70
2.46
2.30
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4966 2666
4721 2515
4605 2290
4344 2145
-
-
-
2.65
2.49
4919 2473
4665 2324
-
-
3.24
3.05
2.85
2.65
2.44
2.24
2.04
-
4929 3022
4668 2841
4388 2656
4089 2467
3771 2277
3434 2089
3078 1904
4450 2353 2.52 4048 1991 2.13
-
3.43
3.23
3.03
2.82
2.61
2.41
2.20
-
4908 3197
4651 3013
4377 2823
4087 2631
3780 2437
3455 2243
3114 2051
4391 2171 2.33 4151 2183 2.34 3717 1829 1.96
4096 2015 2.16 3825 2008 2.15 3352 1664 1.78
3779 1858 1.99 3471 1830 1.96 2951 1499 1.61
3.71
3.49
3.27
3.04
2.82
2.60
2.39
4915 3456
4653 3253
4372 3046
4070 2837
3748 2629
3406 2425
3044 2228
3442 1703 1.83 3090 1652 1.77
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3084 1552 1.66
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 30: BLOWER PERFORMANCE 10 TON OPTIONAL MOTOR - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
In
(kW)
Out
(kW)
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW)
2.29
2.15
1.99
1.83
1.66
1.50
-
(kW)
1.83
1.72
1.59
1.46
1.33
1.20
-
50
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.34
2.67
2.51
2.35
2.18
2.01
1.83
1.65
-
2.13 2.17
2.01 2.05
1.88 1.91
1.75 1.75
1.61 1.58
1.46 1.39
100
149
199
249
-
-
-
-
-
-
2.32
2.47
2.32
2.17
2.01
1.86
1.70
1.55
-
1.98 2.23
1.86 2.10
1.74 1.96
1.61 1.81
1.49 1.64
1.36 1.46
-
-
-
-
2.33
3.02
2.84
2.66
2.47
2.28
2.09
1.90
-
2.42 2.20
2.27 2.07
2.12 1.93
1.97 1.78
1.82 1.62
1.67 1.46
-
2.32
3.20
3.01
2.82
2.63
2.44
2.24
2.05
-
2.56 2.20
2.41 2.07
2.26 1.93
2.10 1.78
1.95 1.62
1.79 1.45
2.32
3.46
3.25
3.05
2.84
2.63
2.43
2.23
2.76 2.20
2.60 2.07
2.44 1.93
2.27 1.78
2.10 1.63
1.94 1.47
299 2.20
349 2.06
1.32
-
-
-
-
-
399
1.92
1.24
-
-
-
-
-
-
-
-
-
-
448 1.77
1.52
-
-
-
-
-
-
-
-
-
498 1.61
1.64
-
-
-
-
-
-
-
-
-
548
1.44
1.78
-
-
-
-
-
-
Unitary Products
27
036-21044-003-A-0304
TABLE 31: BLOWER PERFORMANCE 12-1/2 TON - DOWNSHOT (IMPERIAL)
Turns Open
ESP
(iwg)
0
1
2
3
4
5
CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP CFM Watts BHP
4.32
4.12
3.92
3.71
3.49
3.27
3.04
2.82
3.80
3.62
3.43
3.23
3.03
2.82
2.61
-
3.43
3.24
3.05
2.85
3.09
2.90
2.68
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
5576 4015
5376 3839
5155 3652
4915 3456
4653 3253
4372 3046
4070 2837
3748 2629
5370 3547
5147 3376
4908 3197
4651 3013
4377 2823
4087 3621
3780 2437
5171 3197
4929 3022
4668 2841
4388 2656
5007 2884
4735 2704
4411 2501
4721 2515 2.70 4344 2145 2.30
4450 2353 2.52 4048 1991 2.13
4151 2183 2.34 3717 1829 1.96
4035 2281 2.45 3825 2008 2.15
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
4089 2467 2.65 3608 2051 2.20
-
-
-
-
-
-
-
-
-
-
-
-
3771 2277 2.44
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
TABLE 32: BLOWER PERFORMANCE 12-1/2 TON - DOWNSHOT (METRIC)
Turns Open
ESP
(Pa)
0
1
2
3
4
5
In
Out
In
Out
In
Out
In
Out
In
Out
In
Out
3
3
3
3
3
3
m /s
m /s
m /s
m /s
m /s
m /s
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
(kW) (kW)
100
149
199
249
299
349
399
448
2.63
2.54
2.43
2.32
2.20
2.06
1.92
1.77
4.01
3.84
3.65
3.46
3.25
3.05
2.84
2.63
3.21
3.07
2.92
2.76
2.60
2.44
2.27
2.10
2.53
2.43
2.32
2.20
2.07
1.93
1.78
-
3.55
3.38
3.20
3.01
2.82
2.63
2.44
-
2.84
2.70
2.56
2.41
2.26
2.10
1.95
-
2.44
2.33
2.20
2.07
1.93
1.78
-
3.20
3.02
2.84
2.66
2.47
2.28
-
2.56
2.42
2.27
2.12
1.97
1.82
-
2.36
2.23
2.08
1.90
1.70
-
2.88
2.70
2.50
2.28
2.05
-
2.31
2.16
2.00
1.83
1.64
-
2.23
2.51
2.01
2.05
2.15
1.72
2.10
2.35
1.88
1.91
1.99
1.59
1.96
2.18
1.75
1.75
1.83
1.46
1.81
2.01
1.61
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES FOR TABLES 13 THROUGH 32:
•
•
•
•
“Turns Open” refers to the setting of the variable pitch
motor sheave, where “0 Turns Open” is fully closed.
Blower performance includes dry coil and 2” (51mm)
throw-away filters.
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resis-
tances have been deducted from the total static pressure
of the blower.
28
Unitary Products
036-21044-003-A-0304
TABLE 33: ADDITIONAL STATIC RESISTANCE (IMPERIAL)
2
Electric Heat KW
1
2 3
CFM
Cooling Only
Economizer
9
18
24
36
54
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Unitary Products
29
036-21044-003-A-0304
TABLE 34: ADDITIONAL STATIC RESISTANCE (METRIC)
2
Electric Heat kW
3
1
2 3
M S
Cooling Only
Economizer
9
18
24
36
54
0.89
0.99
1.08
1.18
1.27
1.36
1.46
1.55
1.65
1.74
1.83
1.93
1.02
2.12
2.21
2.30
2.40
2.49
2.59
2.68
2.77
2.87
2.96
14.9
17.4
19.9
22.4
27.3
29.8
34.8
39.7
44.7
49.7
57.1
62.1
69.5
74.5
82.0
89.4
96.9
104.3
111.8
119.2
129.1
139.1
149.0
5.0
5.0
12.4
14.9
17.4
19.9
22.4
24.8
29.8
32.3
37.3
42.2
47.2
52.2
57.1
62.1
69.5
74.5
82.0
86.9
94.4
101.8
109.3
116.7
124.2
14.9
17.4
19.9
22.4
24.8
27.3
32.3
34.8
39.7
44.7
49.7
54.6
59.6
64.6
72.0
77.0
84.4
91.9
99.3
106.8
114.2
121.7
131.6
17.4
19.9
22.4
24.8
29.8
32.3
37.3
42.2
47.2
52.2
57.1
62.1
69.5
74.5
82.0
86.9
94.4
101.8
109.3
116.7
124.2
131.6
139.1
19.9
22.4
24.8
27.3
32.3
34.8
39.7
44.7
49.7
49.7
59.6
64.6
72.0
77.0
84.4
91.9
99.3
106.8
114.2
121.7
131.6
139.1
146.5
24.8
27.3
5.0
32.3
5.0
34.8
7.5
39.7
7.5
44.7
7.5
49.7
7.5
54.6
9.9
59.6
9.9
64.6
9.9
69.5
9.9
77.0
12.4
12.4
12.4
12.4
14.9
14.9
14.9
14.9
17.4
17.4
17.4
84.4
91.9
99.3
106.8
114.2
121.7
131.6
139.1
146.5
154.0
161.4
1. Add these resistance values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 62.1 Pa, the unit will deliver less M3S during full economizer operation.
TABLE 35: ELECTRIC HEAT MINIMUM SUPPLY AIR
- IMPERIAL
TABLE 36: ELECTRIC HEAT MINIMUM SUPPLY AIR
- METRIC
UNIT MODEL SIZE, NOMINAL TONS
7.5
MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE, NOMINAL TONS
HEATER
HEATER
7.5
10
12.5
10
12.5
VOLTAGE
kW
VOLTAGE
kW
3
MINIMUM SUPPLY AIR M S
2250
N/A
N/A
9
1.06
N/A
1.42
1.42
1.42
1.42
N/A
9
2250
2250
2250
N/A
3000
3000
3000
3000
3750
3750
3750
3750
18
24
36
54
1.06
1.06
1.06
N/A
1.76
1.76
1.76
1.76
18
24
36
54
380/415
380/415
30
Unitary Products
036-21044-003-A-0304
TABLE 37: INDOOR BLOWER SPECIFICATIONS
MOTOR
MOTOR SHEAVE
BLOWER SHEAVE
MODEL
BELT
1
HP
Eff.
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
RPM
1-1/2
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 87% 1.15
56
56
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
4.3-5.3
7/8
7/8
1VM50
1VM50
1VM50
1VP56
1VP56
7.5
6.5
7
1
1
1
1
1
AK79
AK69
AK74
AK66
BK72
A55
A53
A54
B55
B55
DM090
2
2
4
4
56
7/8
DM120
DM150
184T
184T
1-1/8
1-1/8
6.2
6.2
4.3 - 5.3
1. 1425 RPM on 50 Hz.
F
R
O
N
T
F
R
O
N
T
L
E
F
T
L
E
F
T
D
C
B
C
B
A
A
E
F
D
FIGURE 2 - UNIT 4 POINT LOAD
FIGURE 4 - UNIT 6 POINT LOAD
TABLE 39: 6 POINT LOAD WEIGHT
TABLE 38: 4 POINT LOAD WEIGHT
Locations (lbs. (kg.))
Location (lbs. (kg.))
Model
Model
A
B
C
D
E
F
A
B
C
D
158
(71.6)
142
(64.4)
128
(58)
187
(84.8)
207
(93.9
230
(104)
230
(104)
197
(89.3)
287
(130)
336
(152)
090
120
150
090
120
150
168
(76.2)
151
(68.4)
136
(61.7)
198
(89.8)
219
(99.3)
244
(110.7)
245
(111)
209
(94)
305
(138)
357
(162)
180
(81.6)
161
(73)
145
(65.8)
212
(96.2)
235
(107)
262
(118.8)
262
(118)
224
(101)
327
(148)
382
(173)
TABLE 40: UNIT WEIGHT
N
O
T
E
:
(
d
m
x
x
x
)
i
n
d
i
i
c
n
a
t
e
i
s
i
m
e
n
s
o
s
n
Shipping Weight
Operating Weight
lbs. (kg)
Model
i
l
l
i
m
e
t
e
r
s
lbs. (kg)
2
4
"
090
120
150
1082 (490.6)
1143 (518.6)
1202 (545.3)
1077 (488.4)
1138 (516.3)
1197 (543.1)
4
1
"
(
6
1
0
)
(
1
0
4
0
)
F
R
O
N
T
L
E
F
T
FIGURE 3 - UNIT CENTER OF GRAVITY
Unitary Products
31
036-21044-003-A-0304
30-11/32
(770)
See Detail
B
50-3/4
(1290)
Control
Entry
Ø 7/8
(22)
Power
Entry
Ø 2-1/2
(65)
4-1/4
(110)
Power
Entry
Ø 2-1/2
(65)
11-1/2
(290)
Convenience
Power
Outlet
For Baserail
Dimensions
See Detail C
Entry
Ø 7/8
(22)
FRONT
17-3/16
(435)
30-3/16
(765)
For Drain
Dimensions
See Detail D
89
6-3/16
(155)
59
24-3/16
(615)
(1500)
LEFT
27
(685)
(2260)
NOTE: (xxx) indicates dimensions
given in millimeters
FIGURE 5 - UNIT DIMENSIONS
2
-
3
/
8
G
a
s
P
i
p
e
I
n
l
e
t
DETAIL C
(
6
0
)
DETAIL B
3
-
3
/
4
5
-
1
/
4
(
9
5
)
B
P
a
a
s
n
e
(
1
3
5
)
1
7
-
1
3
/
1
6
(
4
5
0
)
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
3
-
9
/
1
6
(
9
0
)
TABLE 41: UNIT CLEARANCES 1
2
Right
72(1830)
36(915)
36(915)
12(305)
Top
DETAIL D
Front
Left
36(915)
0(0)
3
4
Rear
Bottom
1. In inches and millimeters, in.(mm).
2. Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
3. To remove the slide-out drain pan, a rear clearance of 60”
(1525 mm) is required. If space is unavailable, the drain
pan can be removed through the front by separating the cor-
ner wall.
5
-
3
/
8
(
1
3
5
)
4. Units may be installed on combustible floors.
32
Unitary Products
036-21044-003-A-0304
R
I
G
H
T
8
(
0
-
5
5
/
0
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
2
0
)
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
(
5
1
0
)
S
U
P
P
L
Y
6
5
2
0
(
1
0
)
(
5
1
0
)
2
(
T
Y
)
P
.
R
E
T
U
R
N
5
0
3
0
(
7
6
0
)
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
(
1
2
8
5
)
8
0
1
4
F
R
O
N
T
O
R
(
2
5
)
(
3
5
5
)
N
O
T
E
:
(
D
M
X
X
M
X
)
I
N
S
D
I
C
N
A
S
T
E
S
I
E
N
M
I
O
I
N
I
L
L
I
E
T
E
R
S
FIGURE 6 - PREDATOR® ROOF CURB DIMENSIONS
2
T
5
Y
P
(
0
)
2
3
3
0
-
1
/
2
(
5
8
5
)
(
7
7
5
)
5
(
0
-
1
8
/
5
2
4
0
1
2
)
(
1
0
)
2
6
8
0
-
5
/
8
R
E
T
U
R
N
(
6
6
0
)
(
2
0
5
0
)
S
U
P
P
L
Y
1
0
(
2
5
5
)
7
6
-
5
/
8
(
1
9
4
5
)
5
9
-
1
/
4
9
3
4
9
F
R
O
N
T
(
1
5
0
5
)
(
2
0
)
R
I
G
H
T
6
4
-
1
/
4
(
1
6
3
0
)
FIGURE 7 - SUNLINE™ TO PREDATOR® TRANSITION ROOF CURB
Unitary Products
33
036-21044-003-A-0304
3
2
-
1
1
/
1
6
(
8
3
0
)
N
O
T
E
:
(
D
M
X
X
M
X
)
I
N
S
D
I
C
N
A
S
T
E
S
I
E
N
M
I
O
I
N
6
-
1
3
/
1
6
6
-
1
3
/
1
6
I
L
L
I
E
T
E
R
S
(
1
7
5
)
(
1
7
5
)
6
-
1
3
/
1
6
(
1
7
5
)
2
4
(
6
1
0
)
2
7
-
1
/
2
(
7
0
0
)
2
1
(
5
3
5
)
L
E
F
T
1
8
(
4
5
5
)
1
9
-
3
/
1
6
(
4
8
5
)
1
-
3
/
1
6
1
7
-
3
/
1
6
1
2
-
5
/
1
6
(
5
4
0
)
(
4
3
5
)
(
3
1
5
)
1
4
-
2
3
/
3
2
B
C
C
O
E
o
t
t
o
m
P
o
w
e
r
,
(
3
7
5
)
B
s
o
t
t
o
m
g
a
s
o
o
n
n
t
v
r
o
l
a
n
d
F
R
O
N
T
1
6
-
3
/
8
u
p
p
l
y
e
n
t
r
y
e
n
i
e
n
c
e
(
4
1
5
)
u
t
l
e
y
t
W
i
r
i
n
g
1
8
-
1
/
1
6
n
t
r
(
4
6
0
)
6
3
-
1
1
/
0
2
1
6
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)
1
8
-
1
/
4
(
4
6
5
)
2
8
-
1
/
4
R
e
t
u
r
n
(
7
2
0
)
A
i
r
S
u
p
p
l
y
A
i
r
1
8
-
1
/
4
(
4
6
5
)
1
8
-
1
/
1
6
(
4
6
0
)
2
-
3
1
/
3
2
(
7
5
)
5
-
5
/
3
2
2
8
-
1
/
4
(
1
3
0
)
(
7
2
0
)
3
1
-
1
1
/
1
6
N
O
T
E
:
(
X
X
X
)
i
n
d
i
c
a
t
e
s
m
i
l
l
i
m
e
t
e
r
s
(
8
0
5
)
FIGURE 9 - REAR DUCT DIMENSIONS
34
Unitary Products
036-21044-003-A-0304
FIGURE 10 -COOLING UNIT WITH GAS HEAT WIRING DIAGRAM
Unitary Products
35
FIGURE 11 -COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM
Subject to change without notice. Printed in U.S.A.