246645-YTG-C-0708
®
TECHNICAL
GUIDE
DESCRIPTION
®
YORK Predator® units are convertible single packages
with a common footprint cabinet and common roof curb for
all 6-1/2 through 12-1/2 ton models. All units have two
compressors with independent refrigeration circuits to pro-
vide two stages of cooling. The units were designed for
commercial applications and can be easily installed on a
roof curb, slab, or frame.
All Predator® units are self-contained and assembled on
rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide
a quick and easy field installation.
STANDARD EFFICIENCY
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
DM 078, 090, 102, 120 and 150
All units are convertible between side and down airflow. A
independent economizer design is used on side and down
discharge applications, as well as all tonnage sizes.
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS
9.0 EER
Predator® units are available in the following configura-
tions: cooling only, cooling with electric heat, and cooling
with gas heat. Electric heaters are available as factory-
installed options or field-installed accessories.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246645-YTG-C-0708
Filter drier
(solid core)
Simplicity™ control board
w/screw connector for T-stat
wiring and network connections
Filter access
(2” throw-away)
Disconnect location
(optional disconnect switch)
Terminal block for
hi-voltage connection
Condenser section
Second model
nameplate
Slide-out motor and
blower assembly for
easy adjustment
and service
inside hinged
access panel
Dual stage
cooling for
maximum
comfort
Belt-drive
blower motor
Power ventor motor
Compressor #2
access (high-
efficiency
compressor
w/crankcase
heater)
20-gauge alumi-
nized steel tubular
heat exchanger for
long life (stainless
steel option)
Two-stage gas
heating to maintain
warm, comfortable
temperature
Base rails w/forklift
slots (three sides)
and lifting holes
Slide-out drain pan
with steel 3/4” NPT,
female connection
Intelligent control
board for safe and
efficient operation
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
York Sunline™ footprint to
the ZH Series footprints are
also available (field-installed
accessory)
Compressor #1 access
(high-efficiency compressor
w/crankcase heater)
Side entry power
and control wiring
knockouts
Toolless
door latch
FIGURE 1 - PREDATOR® COMPONENT LOCATION (DM 120 SHOWN)
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
FEATURES
•
Standard Efficiency– All standard efficiency units have
a minimum EER of 9.0. Gas/electric units have elec-
tronic spark ignition and power vented combustion with
steady state efficiencies of 80%.
Both the unit control board and ignition control board utilize
flash codes to aid in diagnosis of unit malfunctions. Unique
alarm codes quickly identify the source of the unit alarm.
•
Service Friendly – The Predator® incorporates a num-
All units use the same standard filter size. This stan-
dardization removes any confusion on which filter sizes
are needed for replacement.
ber of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
The non-corrosive drain pan slides out of the unit to per-
mit easy cleaning. The drain pan is accessed by remov-
ing the drain pan cover plate on the rear of the unit.
Once the plate is removed, the drain pan slides out
through the rear of the unit.
Service time is reduced through the use of hinged, tool-
less panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other unauthor-
ized persons. It is recommended that the panels be
secured with screws once service is complete.
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
•
Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively through-
out the units.
Johnson Controls Unitary Products
3
246645-YTG-C-0708
•
•
Balanced Heating – The Predator® offers “Ultimate Heat-
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
st
nd
ing Comfort” with a balance between 1 and 2 stage
st
gas heating. The 1 stage of a gas heat Predator® unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side sup-
ply/return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
•
•
Reliable – From the beginning – All units undergo com-
puter automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term –
All Predator® units are painted with a long lasting, pow-
der paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
•
System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frost-
ing when the economizer operates at low outdoor air tem-
peratures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and low-
pressure switches. Internal compressor protection is stan-
dard on all compressors. Crankcase heaters are standard
on reciprocating compressors. Scroll compressors do not
require crankcase heaters. Phase Monitors are standard
on units with scroll compressors. This accessory monitors
the incoming power to the unit and protects the unit from
phase loss and reversed phase rotation.
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator®
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
•
Advanced Controls - S implicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
piped to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
•
•
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit
and protect the unit during shipment. The rails offer fork-
lift access from 3 sides, and rigging holes are available
so that an overhead crane can be used to place the units
on a roof.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the
unit. A clearly identified location is provided to mount a
field supplied electrical disconnect switch. Utility con-
nections can be made quickly and with a minimum
amount of field labor.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
All units are shipped with 2” filters installed.
•
•
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to han-
dle most airflow requirements. For high static applica-
tions, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units
can supply nominal airflow at a minimum of 1.5” ESP.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry an
additional 10-year warranty.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
4
Johnson Controls Unitary Products
246645-YTG-C-0708
ers close. The changeover from mechanical refrigera-
tion to economizer operation is regulated by the
standard single enthalpy input. There is an optional
input dual dry bulb available. To meet regulated air
standards, the economizer control accepts an optional
FACTORY INSTALLED OPTIONS
®
YORK offers several equipment options factory installed, for
the Predator® line.
•
Optional Factory Installed Economizers - Predator
units offer a variety of optional factory installed econo-
mizers with low leak dampers. The outdoor air enthalpy
sensor enables economizer operation if the outdoor
enthalpy is less than the setpoint of the economizer logic
mizer for your application.
CO input for demand ventilation. With single enthalpy
2
input, the economizer control monitors outdoor air. The
dual enthalpy kit provides a second input used to mon-
itor the return air. With a dual input kit installed, the
economizer control compares the values of the two
enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
•
Downflow Economizer - (With barometric relief) -
The economizer is provided with a single enthalpy
input. The economizer is 2% low leakage type, and is
shipped installed and wired. The installer needs only
to assemble and mount the outdoor air hood (Pro-
vided). The economizer has spring return, fully modu-
lating damper actuators and is capable of introducing
up to 100% outdoor air. As the outdoor air intake
dampers open, the return air dampers close. The
changeover from mechanical refrigeration to econo-
mizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry
bulb available. To meet regulated air standards, the
•
•
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
economizer control accepts an optional CO input for
2
demand ventilation. With single enthalpy input, the
economizer control monitors outdoor air. The dual
enthalpy kit provides a second input used to monitor
the return air. With a dual input kit installed, the econ-
omizer control compares the values of the two
enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
•
•
Aluminized Steel Gas Heat Exchanger - For applica-
tions in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
•
•
Stainless Steel Drain Pan - An optional rust-proof stain-
less steel drain pan is available to provide years of trou-
ble-free operation in corrosive environments.
•
•
Horizontal Economizer - (Without barometric
relief) - All features of the downflow economizer
exist except you must order the duct mount baro-
metric relief separately. You must order a 1EH0408
if you are installing a power exhaust. You can
order a 1RD0411 Barometric Relief for horizontal
flow economizers only.
Electric Heaters - The electric heaters range from 9kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
BAS Ready Economizer -(With barometric relief)
- The economizer is provided with a Belimo actuator
that requires a 0-10V DC input from an external
source (i.e., field installed building automation sys-
tem controller). Power exhaust options are avail-
able. The economizer is 2% low leakage type with
spring return and fully modulating dampers capable
of introducing up to 100% outside air. Also include 2”
pleated filters.
•
•
Disconnect Switch - For gas heat units and cooling
units with electric heat, an HACR breaker sized to the
unit is provided. For cooling only units, a switch sized to
the largest electric heat available for the particular unit is
provided. Factory installed option only.
Convenience Outlet - (Non-Powered /Powered) - This
option locates a 120V single-phase GFCI outlet with
cover, on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source
and wiring. The “Powered” option is powered by a step-
down transformer in the unit. Factory installed option only.
•
Slab Economizer for Energy Recovery Ventilators-
(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input.
The economizer is 2% low leakage type, and is
shipped installed and wired. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air damp-
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
Johnson Controls Unitary Products
5
246645-YTG-C-0708
•
S implicity™ INTELLI-Comfort™ with ModLINC
Control - The York® S implicity™ INTELLI-Comfort™
with ModLINC control is factory installed. It includes all
the features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
"off" times due to out side air infiltration. These
smoke detectors have an operational limit of 32 °F
to 131°F. Smoke detectors installed in areas that
could be out side those limitations will have to be
moved to prevent having false alarms.
•
•
•
Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
•
•
Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
•
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
York Commercial Comfort System (YCCS) - Provides
rooftop system integration for YCCS single zone and
change-over bypass systems.
•
•
•
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
FIELD INSTALLED ACCESSORIES
Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
®
YORK offers several equipment accessories for field instal-
lation, for the Predator® line.
BAS - Building Automation System Controls S implic-
ity™ INTELLI-Comfort™ Control - The York® S implic-
ity™ INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field installed
dirty filter indicator switch, an air-proving switch, an Out-
side Air Humidity sensor, a Return Air Humidity sensor, an
Inside IAQ sensor, and an Outside Air IAQ sensor. Con-
struction mode operation, 365-day real time clock with 7
day programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved
•
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the out-
door air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO input for demand ventila-
2
through the INTELLI-Comfort™ using CO sensors. It
2
tion. With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a sec-
ond input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values
of the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible
uses an inside CO sensor to perform Demand Ventilation.
2
It can also use an Outside CO sensor to perform Differen-
2
tial Demand Ventilation. It uses a Patented Comfort Venti-
lation algorithm to provide comfortable ventilation air
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating conditions
exist. Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the on-
board connection for hot gas re-heat system. It uses the
INTELLI-Start™ algorithm to maximize energy savings by
recovering the building from the Unoccupied Setpoints to
the Occupied Setpoints just in time for the Occupied Time
Period to begin. The S implicity™ INTELLI-Comfort™ bal-
•
•
Horizontal Economizer - (Without barometric relief) -
All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator-
(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
ances space temperature, ventilation air temperature, CO
and humidity for ultimate comfort.
2
6
Johnson Controls Unitary Products
246645-YTG-C-0708
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the out-
door air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
•
•
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
control accepts an optional CO input for demand ventila-
2
tion. With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a sec-
ond input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values
of the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
•
•
•
•
Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet. Con-
version kits are available for natural gas and propane.
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
You can order 1EH0409 Barometric Relief/FA Hood
for field installations without an ERV.
•
•
•
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Gas Piping Kit - Contains pipe nipples, fittings and gas
cock required for gas supply connection with external
shut off.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the elec-
tric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a hori-
zontal flow application.
•
Low Limit / Compressor Lockout Kit
•
•
Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air entry.
1. Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during
cold outdoor conditions where there is a risk of
returning liquid refrigerant back to the compressors.
2. Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing
the units first stage heating means when there is a
demand for cooling during cold outside conditions.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
•
•
Permanent Filters - Permanent filters are available.
•
•
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8” and 14” heights. For applications with security con-
cerns, burglar bars are available for the duct openings of
the roof curbs.
CO Sensor - Senses CO levels and automatically
2
2
overrides the economizer when levels rise above the
preset limits.
•
Roof Curb Transition - Single Piece Adapter (10” High) -
Roof curbs for transitioning from Sunline™ units to Preda-
tor® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters.
•
•
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
•
•
Coil Guard - Field installed decorative wire coil guard.
Thermostat - The units are designed to operate with 24-
volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only ther-
mostats, depending upon unit configuration.
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
Johnson Controls Unitary Products
7
246645-YTG-C-0708
TABLE 1: ACCESSORIES
Part Number
Description
Weight
1RC0470
Roof Curb, 8" Height
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1RC0471
Roof Curb, 14" Height
1RC0472
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
1FA0411
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
1FA0412
2MD04702724
2MD04703324
2EE04705424
2EE04705524
2EE04705224
2EE04705624
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
124 lbs.
97 lbs.
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V(For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
-
-
-
-
-
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
1RD0411
1EH0408
25 lbs.
1EH0409
-
-
-
-
2AQ04700424
2AQ04700324
2SD04700424
2MK04700624
1CG0419
CO2 Detector Space Mount
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models)
-
8
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 1: ACCESSORIES (CONTINUED)
Part Number
Description
Weight
1CG0420
1CG0427
1CG0428
1HG0411
1HG0415
1GP0405
1NP0442
1HA0442
1HA0443
1FE0412
Coil Guard (Gas / Electric models)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet
Coil Guard (Gas / Electric Models), 42" Tall Cabinet
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Gas Piping Kit
Propane Conversion Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Flue Exhaust Extension Kit
2BC04700106
2BC04700151
2BC04700154
1FL0402
Gas Heat Kit, -60 deg F, 230V
Gas Heat Kit, -60 deg F, 460V
Gas Heat Kit, -60 deg F, 575V
Permanent Filter Kit (Includes (4) Four Filters)
Permanent Filter Kit, (Includes (4) Four Filters) 42" Tall Cabinet
Dirty Filter Switch
1FL0423
2DF0401
1FF0410
Filter Frame Kit, Metal
1FF0411
Metal Filter Frame Kit, 42" Tall Cabinet
Johnson Controls Unitary Products
9
246645-YTG-C-0708
NOMENCLATURE
®
6.5-12.5 Ton York Model Number Nomenclature
D M 090 N10 A 2 A AA 3 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
B = Style B
C = Style C
Product Identifier
M = 9.0 EER A/C
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Nominal Cooling Capacity
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
078 = 6.5 Ton
090 = 7.5 Ton
102 = 8.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller
2" Pleated filters
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
BAS Ready Unit with Belimo Economizer
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Gas Heat Options
Product Generation
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
N20 = 200 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel
3 = Third Generation
4 = Fourth Generation
Additional Options
Electric Heat Options
AA = None
RC = Coil Guard, Shipping Bag & American Flag
AB = Phase Monitor
TA = Technicoat Condenser Coil
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Airflow
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
Installation Options
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
A = No Options Installed
B = Option 1
C = Option 2
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
D = Options 1 & 2
E = Option 3
N = Hi Static Mtr.
F = Option 4
P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only)
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only)
R = Hi Static Mtr./Motorized Damper (Downflow Only)
S = Hi Static Mtr./Horizontal Economizer (No Baro.)
T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Voltage
2 = 208/230-3-60
3 = 380-3-60
4 = 460-3-60
5 = 575-3-60
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
10
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 2: DM PHYSICAL DATA
Component
Models
102
078
090
120
150
Blower, Centrifugal (Dia. X Wd. in.)
15 x 15
1-1/2
2
12 x 12
2
12 X 12
15 x 15
2
15 x 15
3
Evaporator
Blower
Motor, Standard (HP)
Motor, Optional (HP)
Rows
3
3
3
3
5
2
2
3
2
3
Fins per Inch
Height (in.)
15
15
15
15
15
Evaporator
Coil
30
32
32
40
40
Face Area (ft.2 each)
Propeller Dia. (in., each)
Motor (HP, each)
CFM, Nominal (each)
Rows (each)
9.9
24
10.67
24
10.67
24
13.2
24
13.2
24
Condenser
Fan
(2 per Unit)
1/3
1700
1
3/4
3/4
2200
1
3/4
2200
1
3/4
2200
1
2200
2
Condenser
Coil
(2 per unit)
Fins per Inch
20
20
20
20
20
Height (in. each)
24
28
36
44
44
Face Area (ft.2 each)
System 1 (lb./oz.)
System 2 (lb./oz.)
Quantity
7.9
4/6
4/0
2
9.33
4/10
3/14
2
12
14.5
6/12
6/12
2
14.5
10/12
11/0
2
5/8
5/2
2
Refrigerant
Charge
Compressors
Air Filters
Type
Recip
25x20x2
4
Recip
25x16x2
4
Recip.
25x16x2
4
Recip
25x20x2
4
Scroll
25x20x2
4
Size (Wd. x Ht. x Thickness in.)
Number Per Unit
Johnson Controls Unitary Products
11
246645-YTG-C-0708
TABLE 3: DM CAPACITY RATINGS
Cooling Capacities
Gas Heat Capacity
Nominal
Electric Heat
*
ARI Ratings
Sound
Rating
Gas Line
Size
(in. OD)
Size
CFM
Model
(Tons)
‡
Seasonal Temp.
Efficiency Rise
Capacity
†
Input Output
(MBH) (MBH)
(dB)
MBH EER IPLV
(kW)
(%)
(°F)
Cooling
Only
-
-
-
-
-
-
-
-
-
Electric
Heat
078
(6-1/2)
9, 18, 24, 34
-
-
77
9.0
9.0
9.0
9.0
9.3
9.45
2600
84
89
90
90
90
Gas Heat
Gas Heat
-
-
120
180
96
80
80
20-50
35-65
3/4
3/4
144
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
090
(7-1/2)
18, 34
86
9.2
2886
Gas Heat
Gas Heat
-
-
120
180
96
80
80
15-45
30-60
3/4
3/4
144
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
102
(8-1/2)
9, 18, 24, 34
99
10.04 3400
Gas Heat
Gas Heat
-
-
120
180
96
80
80
15-45
30-60
3/4
3/4
144
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
120
(10)
9, 24, 34 54
120
9.10
4000
Gas Heat
Gas Heat
-
-
180
240
144
192
80
80
20-50
35-65
3/4
3/4
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
150
(12-1/2)
9, 24, 34, 54
144
9.25
4500
Gas Heat
Gas Heat
-
-
180
240
144
192
80
80
10-40
25-55
3/4
3/4
*
†
‡
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
Rated in accordance with ARI 270 standard.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING
208/230-3-60
460-3-60
MIN.
187
432
540
MAX.
252
504
575-3-60
630
12
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 5: COOLING CAPACITY DM078 (6-1/2 TON) UNIT
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Cap.*
(MBH)
Tot.
Input†
(kW)
Tot.
Cap.* Input†
(MBH)
Tot.
WB
(°F)
CFM
1950
2275
2600
2925
3250
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
87
80
71
66
91
83
74
69
94
87
77
72
95
88
77
73
96
89
78
74
6.8
6.7
6.4
6.4
6.9
6.7
6.5
6.5
7.0
6.8
6.6
6.6
7.0
6.8
6.6
6.6
7.0
6.8
6.6
6.6
49
61
71
66
54
67
74
69
59
74
77
72
63
78
77
73
67
83
78
74
43
55
66
66
47
61
72
69
52
66
77
72
55
70
77
73
58
73
78
74
37
50
61
61
41
54
66
67
44
58
72
72
46
61
75
73
48
64
78
74
32
44
55
56
34
47
60
60
37
51
64
65
37
52
66
64
38
54
68
64
26
38
50
50
28
41
53
54
29
43
57
57
29
44
58
56
29
44
59
54
-
-
78
73
63
59
82
76
66
62
86
80
69
65
85
79
69
64
85
78
68
64
7.3
7.1
6.9
6.8
7.4
7.2
6.9
6.9
7.5
7.3
7.0
7.0
7.5
7.3
7.1
7.0
7.5
7.3
7.1
7.1
45
57
63
59
50
64
66
62
56
70
69
65
60
74
69
64
64
78
68
64
40
52
61
59
44
57
65
62
48
63
69
65
51
66
69
64
54
70
68
64
34
46
56
54
37
51
61
60
41
55
67
65
43
58
67
64
44
60
68
64
28
41
50
49
31
44
55
53
33
48
59
57
34
49
59
56
35
50
58
54
23
35
45
43
24
38
48
46
26
40
52
50
25
40
50
47
25
41
49
45
-
-
33
44
44
-
34
47
47
-
36
49
49
-
35
49
47
-
27
39
39
-
28
40
40
-
28
42
42
-
26
40
38
-
29
39
37
-
31
42
40
-
33
44
42
-
32
42
39
-
24
33
32
-
24
35
33
-
25
37
35
-
23
33
30
-
35
49
45
25
39
35
31
39
35
21
29
25
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
73
66
64
54
76
68
67
56
78
71
69
58
78
70
69
58
78
70
69
57
7.8
7.5
7.4
7.3
7.9
7.6
7.5
7.4
8.0
7.7
7.5
7.5
8.0
7.7
7.6
7.5
8.1
7.8
7.6
7.6
43
54
61
54
48
60
65
56
53
66
69
58
57
68
69
58
61
70
69
57
37
48
57
54
41
54
62
56
45
59
67
58
48
62
68
58
52
66
69
57
31
43
52
48
34
47
57
53
38
51
62
58
40
54
64
58
42
57
67
57
26
37
46
43
28
40
50
46
30
44
54
50
31
46
56
49
32
48
57
48
20
32
41
37
21
34
44
40
22
36
47
42
23
37
47
40
23
38
48
38
-
-
67
58
66
48
69
60
67
49
71
61
69
50
71
62
69
51
71
62
70
51
8.3
7.9
7.9
7.8
8.4
8.0
8.0
7.9
8.4
8.1
8.0
7.9
8.5
8.2
8.1
8.0
8.6
8.3
8.2
8.1
40
51
59
48
45
56
64
49
49
61
69
50
54
62
69
51
59
62
70
51
35
45
54
48
38
50
59
49
42
55
64
50
46
58
67
51
49
62
70
51
29
40
48
43
32
43
52
46
34
47
57
50
37
51
61
51
40
55
66
51
23
34
42
37
25
37
46
40
27
39
49
43
28
42
53
42
30
45
56
41
18
29
37
31
18
30
39
33
19
32
42
35
20
33
44
33
20
35
46
31
-
-
26
35
32
-
27
37
33
-
28
39
35
-
28
38
32
-
21
30
26
-
21
31
27
-
21
31
27
-
20
30
23
-
23
31
26
-
24
33
27
-
24
34
28
-
25
35
25
-
17
26
20
-
17
26
20
-
17
26
20
-
16
27
16
-
1950
2275
2600
2925
3250
28
38
28
19
28
19
25
37
22
16
27
12
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
62
51
67
42
63
52
68
43
63
52
69
43
64
53
70
44
65
54
71
44
8.8
8.4
8.4
8.3
8.8
8.4
8.5
8.3
8.9
8.5
8.5
8.4
9.0
8.6
8.6
8.5
9.1
8.7
8.8
8.6
38
48
57
42
42
52
63
43
46
52
69
43
52
53
70
44
57
54
71
44
32
42
50
42
35
46
56
43
39
50
62
43
43
53
66
44
47
54
71
44
27
37
44
37
29
40
48
40
31
43
52
43
34
47
58
44
38
52
65
44
21
31
39
31
22
33
41
33
23
35
44
35
26
39
50
35
28
42
55
34
15
25
33
26
16
27
35
27
16
28
37
28
17
30
41
26
18
32
45
25
-
-
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
20
27
20
-
20
28
20
-
20
29
20
-
21
32
18
-
14
22
15
-
13
22
14
-
12
21
13
-
13
24
9
1950
2275
2600
2925
3250
†
-
23
36
15
13
26
5
Johnson Controls Unitary Products
13
246645-YTG-C-0708
TABLE 6: COOLING CAPACITY DM090 (7-1/2 TON) UNIT
Temperature of Air on Condenser Coil
Air on Evap-
orator Coil
75°F
85°F
*
*
†
†
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Total Total
Cap.
Total Total
Cap.
WB
CFM
*
*
Input
Input
(°F)
(MBH) (kW)
(MBH) (kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
101.7
96.3
89.4
88.6
105.2
99.6
92.5
91.6
108.7
102.9
95.6
7.2
7.1
7.0
6.9
7.3
7.2
7.0
7.0
7.3
7.2
7.1
7.0
7.3
7.2
7.1
7.1
7.4
7.2
7.1
7.1
57.5 51.1 44.7 38.3 31.8
-
-
96.7
7.8
7.6
7.5
7.5
7.8
7.7
7.5
7.5
7.9
7.8
7.6
7.6
7.9
7.8
7.6
7.6
7.9
7.8
7.6
7.6
55.8 49.4 43.0 36.6 30.1
-
-
73.3 66.8 60.4 54.0 47.6 41.2 34.8 90.8
89.4 80.1 73.7 67.3 60.9 54.4 48.0 83.5
88.6 85.9 79.5 73.1 66.7 60.3 53.8 83.7
70.8 64.4 58.0 51.6 45.2 38.8 32.4
83.5 77.4 71.0 64.5 58.1 51.7 45.3
83.7 81.9 75.5 69.0 62.6 56.2 49.8
2250
63.7 56.2 48.6 41.0 33.4
-
-
99.9
61.8 54.2 46.6 39.1 31.5
-
-
67
80.9 73.3 65.7 58.1 50.5 43.0 35.4 93.8
92.5 87.8 80.1 72.5 65.0 57.4 49.8 86.2
91.6 90.3 86.5 78.9 71.3 63.7 56.1 86.5
78.1 70.6 63.0 55.4 47.8 40.2 32.6
86.2 83.2 77.0 69.4 61.9 54.3 46.7
86.5 85.6 81.9 74.3 66.7 59.2 51.6
2625
62
57
72
70.0 61.2 52.5 43.7 35.0
-
-
103.1
67.8 59.1 50.3 41.6 32.8
-
-
67
88.5 79.7 71.0 62.2 53.5 44.7 36.0 96.8
95.6 95.6 86.6 77.8 69.1 60.3 51.6 89.0
94.7 94.7 93.4 84.6 75.9 67.2 58.4 89.2
85.4 76.7 67.9 59.2 50.4 41.7 32.9
89.0 89.0 83.1 74.3 65.6 56.8 48.1
89.2 89.2 88.4 79.6 70.9 62.1 53.4
3000
62
57
72
94.7
110.1
104.2
96.8
74.1 64.1 54.2 44.2 34.3
-
-
104.4
72.3 62.4 52.4 42.5 32.5
-
-
67
93.8 83.3 73.3 63.3 53.4 43.4 33.5 98.0
96.8 96.8 91.1 81.2 71.2 61.2 51.3 90.1
95.9 95.9 95.2 85.3 75.3 65.4 55.4 90.4
90.7 80.7 70.8 60.8 50.8 40.9 30.9
90.1 90.1 86.6 76.6 66.6 56.7 46.7
90.4 90.4 89.9 80.0 70.0 60.0 50.1
3375
62
57
72
67
62
57
95.9
111.5
105.5
98.0
78.3 67.1 55.9 44.7 33.5
-
-
105.7
76.9 65.7 54.5 43.3 32.2
-
-
99.1 86.8 75.6 64.4 53.3 42.1 30.9 99.2
98.0 98.0 95.7 84.5 73.3 62.1 51.0 91.2
97.1 97.1 97.1 85.9 74.7 63.6 52.4 91.5
95°F
96.0 84.8 73.6 62.4 51.2 40.1 28.9
91.2 91.2 90.0 78.8 67.7 56.5 45.3
91.5 91.5 91.5 80.3 69.1 57.9 46.8
105°F
3750
97.1
72
67
62
57
72
91.8
85.3
77.5
78.9
94.6
87.9
79.9
81.3
97.5
90.6
82.3
83.8
98.7
91.7
83.3
84.8
99.9
92.8
84.4
85.9
8.4
8.2
8.0
8.0
8.4
8.3
8.1
8.1
8.5
8.3
8.1
8.2
8.5
8.4
8.2
8.2
8.5
8.4
8.2
8.2
54.1 47.7 41.3 34.9 28.4
-
-
85.6
9.0
8.7
8.6
8.6
9.0
8.8
8.6
8.7
9.1
8.9
8.7
8.7
9.1
8.9
8.8
8.8
9.2
8.9
8.8
8.8
51.6 45.2 38.8 32.3 25.9
-
-
68.4 62.0 55.6 49.2 42.8 36.3 29.9 78.0
77.5 74.6 68.2 61.8 55.4 49.0 42.6 72.4
78.9 77.8 71.4 65.0 58.6 52.1 45.7 73.2
65.4 59.0 52.6 46.2 39.8 33.4 26.9
72.4 70.5 64.0 57.6 51.2 44.8 38.4
73.2 71.7 65.3 58.9 52.5 46.1 39.6
2250
59.9 52.3 44.7 37.1 29.6
-
-
87.9
57.1 49.6 42.0 34.4 26.8
-
-
67
75.4 67.8 60.2 52.7 45.1 37.5 29.9 80.1
79.9 78.5 73.9 66.3 58.8 51.2 43.6 74.3
81.3 80.8 77.4 69.8 62.2 54.6 47.0 75.2
71.7 64.6 57.0 49.4 41.8 34.3 26.7
74.3 73.3 69.4 61.8 54.2 46.6 39.1
75.2 74.4 70.7 63.2 55.6 48.0 40.4
2625
62
57
72
65.7 56.9 48.2 39.4 30.7
-
-
90.2
62.7 54.0 45.2 36.5 27.7
-
-
67
82.4 73.6 64.9 56.1 47.4 38.6 29.9 82.1
82.3 82.3 79.6 70.9 62.1 53.4 44.6 76.2
83.8 83.8 83.3 74.6 65.8 57.1 48.3 77.1
78.0 70.1 61.4 52.6 43.9 35.1 26.4
76.2 76.2 74.7 66.0 57.2 48.5 39.7
77.1 77.1 76.2 67.4 58.7 49.9 41.2
3000
62
57
72
70.6 60.6 50.7 40.7 30.7
-
-
91.5
67.7 57.7 47.8 37.8 27.8
-
-
67
87.6 78.2 68.2 58.3 48.3 38.3 28.4 83.3
83.3 83.3 82.0 72.0 62.1 52.1 42.1 77.3
84.8 84.8 84.6 74.6 64.7 54.7 44.7 78.2
81.2 74.8 64.9 54.9 44.9 35.0 25.0
77.3 77.3 76.6 66.6 56.6 46.7 36.7
78.2 78.2 77.8 67.8 57.8 47.9 37.9
3375
62
57
72
67
62
57
75.5 64.3 53.1 42.0 30.8
-
-
92.8
72.7 61.5 50.3 39.2 28.0
-
-
92.8 82.7 71.6 60.4 49.2 38.0 26.9 84.5
84.4 84.4 84.4 73.2 62.0 50.8 39.6 78.4
85.9 85.9 85.9 74.7 63.5 52.3 41.1 79.3
115°F
84.5 79.4 68.3 57.2 46.0 34.8 23.6
78.4 78.4 78.4 67.2 56.1 44.9 33.7
79.3 79.3 79.3 68.1 57.0 45.8 34.6
125°F
3750
72
67
62
57
72
79.5
70.7
67.3
67.6
81.2
72.2
68.7
69.0
82.9
73.7
70.1
70.4
84.3
74.9
71.3
71.6
85.7
76.1
72.5
72.8
9.6
9.3
9.1
9.1
9.6
9.4
9.2
9.2
9.7
9.5
9.3
9.3
9.8
9.5
9.3
9.3
9.8
9.5
9.4
9.4
49.1 42.6 36.2 29.8 23.4
-
-
73.4
10.1
9.8
9.7
9.7
10.2
9.9
9.8
9.8
10.3
10.0
9.9
46.5 40.1 33.7 27.3 20.9
-
-
62.5 56.0 49.6 43.2 36.8 30.4 24.0 63.4
67.3 66.3 59.9 53.4 47.0 40.6 34.2 62.2
67.6 65.6 59.2 52.8 46.4 40.0 33.5 61.9
59.5 53.1 46.6 40.2 33.8 27.4 21.0
62.2 62.1 55.7 49.2 42.8 36.4 30.0
61.9 59.5 53.1 46.7 40.3 33.9 27.4
2250
54.4 46.8 39.2 31.7 24.1
-
-
74.5
51.7 44.1 36.5 28.9 21.3
-
-
67
68.1 61.3 53.8 46.2 38.6 31.0 23.4 64.3
68.7 68.2 64.8 57.3 49.7 42.1 34.5 63.1
69.0 68.0 64.1 56.6 49.0 41.4 33.8 62.8
64.3 58.1 50.5 42.9 35.4 27.8 20.2
63.1 63.0 60.3 52.7 45.1 37.6 30.0
62.8 61.6 57.5 49.9 42.4 34.8 27.2
2625
62
57
72
59.8 51.0 42.3 33.5 24.8
-
-
75.5
56.8 48.1 39.3 30.6 21.8
-
-
67
73.7 66.6 57.9 49.1 40.4 31.6 22.9 65.2
70.1 70.1 69.8 61.1 52.3 43.6 34.8 64.0
70.4 70.4 69.1 60.3 51.6 42.8 34.1 63.7
65.2 63.2 54.4 45.7 36.9 28.2 19.4
64.0 64.0 64.0 56.2 47.4 38.7 29.9
63.7 63.7 62.0 53.2 44.5 35.7 27.0
3000
62
57
72
9.9
64.8 54.9 44.9 34.9 25.0
-
-
77.0
10.4
10.0
9.9
61.9 52.0 42.0 32.1 22.1
-
-
67
74.9 71.4 61.5 51.5 41.6 31.6 21.6 66.5
71.3 71.3 71.2 61.2 51.2 41.3 31.3 65.3
71.6 71.6 70.9 61.0 51.0 41.0 31.1 65.0
66.5 66.5 58.1 48.2 38.2 28.2 18.3
65.3 65.3 65.3 55.8 45.8 35.8 25.9
65.0 65.0 64.1 54.1 44.2 34.2 24.2
3375
62
57
72
67
62
57
9.9
69.9 58.7 47.5 36.3 25.2
-
-
78.6
10.4
10.1
10.0
9.9
67.1 55.9 44.7 33.5 22.4
-
-
76.1 76.1 65.1 53.9 42.7 31.6 20.4 67.8
72.5 72.5 72.5 61.3 50.1 38.9 27.8 66.5
72.8 72.8 72.8 61.6 50.4 39.3 28.1 66.2
67.8 67.8 61.9 50.7 39.5 28.3 17.2
66.5 66.5 66.5 55.4 44.2 33.0 21.8
66.2 66.2 66.2 55.1 43.9 32.7 21.5
3750
*
The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
†
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
14
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 7: COOLING CAPACITY DM102 (8-1/2 TON) UNIT
Temperature of Air on Condenser Coil
Air on Evap-
orator Coil
75°F
85°F
*
*
†
†
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
Total Total
Cap.
Total Total
Cap.
WB
CFM
*
*
Input
Input
(°F)
(MBH) (kW)
(MBH) (kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
123.8
112.4
106.9
99.3
7.4
7.3
7.1
7.1
7.4
7.3
7.2
7.1
7.5
7.4
7.2
7.2
7.5
7.4
7.3
7.3
7.6
7.5
7.3
7.3
68.9 61.6 54.3 47.1 39.8
-
-
114.8
8.0
7.9
7.7
7.7
8.1
7.9
7.7
7.8
8.2
8.0
7.8
7.8
8.2
8.0
7.8
7.9
8.3
8.1
7.9
7.9
65.3 58.0 50.8 43.5 36.2
-
-
85.2 78.0 70.7 63.4 56.2 48.9 41.6 104.3
106.9 95.5 88.1 80.8 73.5 66.3 59.0 96.4
99.3 98.9 91.5 84.2 76.9 69.7 62.4 93.2
81.9 74.6 67.3 60.1 52.8 45.5 38.3
96.4 90.7 83.5 76.2 68.9 61.6 54.4
93.2 92.9 85.7 78.4 71.1 63.9 56.6
2550
127.6
115.9
110.3
102.4
131.5
119.4
113.7
105.5
134.7
122.3
116.4
108.1
137.9
125.3
119.2
110.7
75.6 67.0 58.5 49.9 41.3
-
-
118.7
72.0 63.4 54.8 46.2 37.6
-
-
67
93.2 84.6 76.0 67.4 58.8 50.2 41.7 107.8
110.3 104.6 94.7 86.1 77.5 69.0 60.4 99.7
102.4 102.2 98.4 89.8 81.2 72.6 64.0 96.3
89.9 81.3 72.7 64.1 55.5 46.9 38.3
99.7 96.9 90.1 81.5 72.9 64.3 55.7
96.3 96.2 92.5 83.9 75.3 66.7 58.1
2975
62
57
72
82.4 72.5 62.6 52.6 42.7
-
-
122.6
78.7 68.7 58.8 48.9 39.0
-
-
67
101.2 91.3 81.3 71.4 61.5 51.6 41.7 111.3
113.7 113.7 101.4 91.5 81.5 71.6 61.7 103.0
105.5 105.5 105.3 95.4 85.5 75.5 65.6 99.5
97.9 88.0 78.0 68.1 58.2 48.3 38.4
103.0 103.0 96.7 86.8 76.9 67.0 57.1
99.5 99.5 99.3 89.4 79.5 69.5 59.6
3400
62
57
72
88.7 77.5 66.2 54.9 43.6
-
-
125.2
85.0 73.7 62.4 51.1 39.8
-
-
67
110.0 97.3 86.0 74.7 63.4 52.1 40.9 113.7
116.4 116.4 110.3 99.0 87.7 76.4 65.1 105.2
108.1 108.1 108.0 96.7 85.4 74.1 62.8 101.6
105.4 94.1 82.8 71.5 60.2 48.9 37.6
105.2 105.2 102.1 90.8 79.5 68.2 56.9
101.6 101.6 101.5 90.2 78.9 67.6 56.4
3825
62
57
72
67
62
57
95.1 82.4 69.8 57.1 44.4
-
-
127.8
91.3 78.7 66.0 53.3 40.7
-
-
118.8 103.4 90.7 78.0 65.4 52.7 40.0 116.1
119.2 119.2 119.2 106.5 93.8 81.2 68.5 107.4
110.7 110.7 110.7 98.0 85.3 72.6 60.0 103.8
95°F
112.9 100.2 87.6 74.9 62.2 49.6 36.9
107.4 107.4 107.4 94.8 82.1 69.4 56.8
103.8 103.8 103.8 91.1 78.4 65.8 53.1
105°F
4250
72
67
62
57
72
105.8
96.1
86.0
87.0
109.7
99.7
89.1
90.2
113.6
103.2
92.3
8.7
8.5
8.3
8.3
8.8
8.5
8.3
8.4
8.8
8.6
8.4
8.4
8.9
8.6
8.4
8.5
8.9
8.7
8.5
8.5
61.7 54.5 47.2 39.9 32.6
-
-
96.9
9.4
9.1
8.9
8.9
9.4
9.1
9.0
9.0
9.5
9.2
9.0
9.1
9.5
9.2
9.1
9.1
9.6
9.3
9.1
9.1
58.0 50.8 43.5 36.2 29.0
-
-
78.5 71.3 64.0 56.7 49.5 42.2 34.9 86.6
86.0 86.0 78.8 71.6 64.3 57.0 49.7 79.4
87.0 87.0 79.9 72.6 65.3 58.1 50.8 79.5
74.3 67.0 59.7 52.5 45.2 37.9 30.7
79.4 78.9 71.7 64.4 57.1 49.9 42.6
79.5 79.4 72.2 65.0 57.7 50.4 43.2
2550
68.3 59.7 51.1 42.5 34.0
-
-
100.5
64.6 56.0 47.4 38.8 30.2
-
-
67
86.6 78.0 69.4 60.8 52.2 43.6 35.0 89.8
89.1 89.1 85.4 76.8 68.3 59.7 51.1 82.3
90.2 90.2 86.6 78.0 69.4 60.8 52.2 82.5
81.5 73.7 65.1 56.5 47.9 39.3 30.7
82.3 82.1 78.1 69.5 60.9 52.3 43.7
82.5 82.4 78.7 70.1 61.5 52.9 44.3
2975
62
57
72
74.9 65.0 55.1 45.2 35.3
-
-
104.0
71.1 61.2 51.3 41.3 31.4
-
-
67
94.6 84.7 74.7 64.8 54.9 45.0 35.1 93.0
92.3 92.3 92.1 82.1 72.2 62.3 52.4 85.3
93.5 93.5 93.3 83.4 73.5 63.5 53.6 85.4
88.7 80.3 70.4 60.5 50.6 40.7 30.8
85.3 85.3 84.5 74.6 64.6 54.7 44.8
85.4 85.4 85.1 75.2 65.3 55.4 45.5
3400
62
57
72
93.5
115.7
105.1
94.0
81.2 70.0 58.7 47.4 36.1
-
-
105.6
77.4 66.1 54.8 43.5 32.2
-
-
67
100.8 90.9 79.6 68.3 57.0 45.7 34.4 94.5
94.0 94.0 93.9 82.6 71.3 60.0 48.7 86.6
95.2 95.2 95.1 83.8 72.5 61.2 49.9 86.7
92.3 85.7 75.3 64.0 52.7 41.4 30.1
86.6 86.6 86.2 74.9 63.6 52.3 41.0
86.7 86.7 86.6 75.3 64.0 52.7 41.4
3825
62
57
72
67
62
57
95.2
117.7
107.0
95.7
87.6 74.9 62.2 49.6 36.9
-
-
107.3
83.7 71.0 58.3 45.7 33.0
-
-
107.0 97.1 84.4 71.8 59.1 46.4 33.7 95.9
95.7 95.7 95.7 83.0 70.4 57.7 45.0 87.9
96.9 96.9 96.9 84.2 71.5 58.9 46.2 88.1
115°F
95.9 91.0 80.2 67.5 54.8 42.1 29.5
87.9 87.9 87.9 75.3 62.6 49.9 37.3
88.1 88.1 88.1 75.4 62.7 50.1 37.4
125°F
4250
96.9
72
67
62
57
72
88.0
77.2
72.9
72.1
91.2
80.0
75.5
74.7
94.5
82.8
78.2
77.4
95.6
83.9
79.2
78.3
96.8
84.9
80.2
79.3
10.0
9.7
9.6
9.6
10.1
9.7
9.6
9.6
10.1
9.8
9.7
9.7
10.2
9.8
9.7
9.7
10.2
9.9
9.8
9.8
54.3 47.1 39.8 32.5 25.3
-
-
79.1
10.7
10.2
10.2
10.2
10.7
10.3
10.2
10.2
10.8
10.4
10.3
10.3
10.9
10.4
10.4
10.4
10.9
10.5
10.4
10.4
50.7 43.4 36.1 28.8 21.6
-
-
70.0 62.8 55.5 48.2 40.9 33.7 26.4 67.7
72.9 71.8 64.5 57.3 50.0 42.7 35.5 66.3
72.1 71.9 64.6 57.3 50.1 42.8 35.5 64.6
65.8 58.5 51.2 44.0 36.7 29.4 22.1
66.3 64.7 57.4 50.1 42.9 35.6 28.3
64.6 64.3 57.0 49.7 42.4 35.2 27.9
2550
60.8 52.2 43.6 35.0 26.4
-
-
82.0
57.0 48.4 39.8 31.3 22.7
-
-
67
76.4 69.4 60.8 52.2 43.6 35.0 26.4 70.2
75.5 75.0 70.7 62.1 53.5 44.9 36.3 68.7
74.7 74.6 70.8 62.2 53.6 45.0 36.4 67.0
70.2 65.1 56.5 47.9 39.3 30.7 22.1
68.7 68.0 63.4 54.8 46.2 37.6 29.0
67.0 66.8 62.9 54.3 45.7 37.1 28.5
2975
62
57
72
67.2 57.3 47.4 37.5 27.6
-
-
84.9
63.4 53.5 43.6 33.7 23.7
-
-
67
82.8 76.0 66.1 56.2 46.3 36.4 26.4 72.6
78.2 78.2 76.9 67.0 57.1 47.1 37.2 71.2
77.4 77.4 77.0 67.1 57.1 47.2 37.3 69.3
72.6 71.7 61.8 51.9 41.9 32.0 22.1
71.2 71.2 69.3 59.4 49.5 39.6 29.6
69.3 69.3 68.8 58.9 49.0 39.1 29.2
3400
62
57
72
73.5 62.2 50.9 39.6 28.3
-
-
85.6
69.6 58.3 47.1 35.8 24.5
-
-
67
83.9 80.4 71.0 59.7 48.4 37.1 25.8 73.2
79.2 79.2 78.5 67.2 55.9 44.6 33.4 71.8
78.3 78.3 78.1 66.8 55.5 44.3 33.0 69.9
73.2 73.2 66.7 55.4 44.1 32.8 21.5
71.8 71.8 70.8 59.6 48.3 37.0 25.7
69.9 69.9 69.7 58.4 47.1 35.8 24.5
3825
62
57
72
67
62
57
79.8 67.1 54.4 41.8 29.1
-
-
86.3
75.9 63.2 50.5 37.9 25.2
-
-
84.9 84.9 75.9 63.2 50.5 37.9 25.2 73.8
80.2 80.2 80.2 67.5 54.8 42.1 29.5 72.4
79.3 79.3 79.3 66.6 53.9 41.3 28.6 70.5
73.8 73.8 71.6 58.9 46.3 33.6 20.9
72.4 72.4 72.4 59.7 47.0 34.4 21.7
70.5 70.5 70.5 57.8 45.1 32.5 19.8
4250
*
The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
†
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
15
246645-YTG-C-0708
TABLE 8: COOLING CAPACITY DM120 (10 TON) UNIT
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Tot.
Tot.
Cap.* Input†
(MBH)
Tot.
Tot.
Cap.* Input†
(MBH)
WB
(°F)
Return Dry Bulb (°F)
CFM
3000
3500
4000
4500
5000
(kW)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
132
124
116
110
135
127
119
112
138
130
121
115
141
132
124
117
144
135
126
119
11.0
10.7
10.5
10.3
11.1
10.8
10.6
10.4
11.2
10.9
10.7
10.5
11.3
11.0
10.7
10.5
11.3
11.0
10.8
10.6
76
96
68
87
59
79
98
50
70
89
92
53
74
95
98
56
78
42
62
81
83
43
64
84
87
44
66
88
91
45
69
92
90
45
71
95
90
-
-
125
116
106
106
129
120
110
109
133
124
113
113
135
126
115
115
138
128
117
117
11.7
11.4
11.1
11.1
11.8
11.5
11.2
11.2
12.0
11.7
11.3
11.3
12.0
11.7
11.4
11.4
12.1
11.8
11.5
11.5
74
93
65
84
57
75
91
95
62
82
99
48
67
82
86
52
72
89
93
55
77
95
40
58
74
78
41
62
79
83
43
65
84
88
43
66
85
88
43
67
86
87
-
-
53
72
75
-
54
74
77
-
55
76
80
-
55
78
77
-
45
64
66
-
44
64
67
-
43
65
68
-
42
65
64
-
50
65
69
-
52
69
73
-
54
72
76
-
53
72
74
-
41
57
61
-
42
58
63
-
42
60
65
-
39
58
61
-
115 106
110 109 101
83
104
118 114 105
112 112 108
91
113 101
121 121 111 100
115 115 115 103
106 100
106 103
82
102
110 106
109 108 103
90
112 100
113 113 107
113 113 111 100
96
119 106
115 115 112
115 115 114 101
102
126 111
117 117 116 101
117 117 117 102
73
94
63
84
72
92
79
67
90
78
67
89
98
85
71
95
58
82
83
70
92
56
79
98
122 108
124 124 118 105
117 117 117 104
105
90
75
60
86
87
72
96
58
81
130 116 101
126 126 125 110
119 119 119 105
56
80
75
41
65
60
52
71
72
37
57
57
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
117
107
97
12.4
12.0
11.6
11.7
12.5
12.1
11.7
11.8
12.7
12.2
11.9
11.9
12.8
12.3
12.0
12.0
12.9
12.4
12.1
12.1
70
89
97
98
78
62
80
94
96
68
88
99
53
71
85
88
58
78
93
95
63
84
45
63
77
79
48
68
83
85
51
72
89
91
53
75
91
93
54
78
93
95
36
54
68
71
38
57
73
75
39
61
77
80
39
62
77
80
40
63
78
80
-
-
109
97
88
13.1
12.5
12.2
12.3
13.2
12.6
12.3
12.4
13.4
12.8
12.4
12.5
13.5
12.9
12.5
12.6
13.6
13.0
12.7
12.7
67
85
88
91
75
94
91
94
82
103
94
97
89
106
96
99
96
58
76
88
89
64
83
91
93
70
91
94
97
76
98
96
99
81
50
67
80
81
54
73
87
88
59
79
94
95
63
84
96
98
66
90
99
41
59
71
72
44
63
76
78
47
68
82
83
49
71
83
85
51
75
84
87
33
50
62
64
34
53
66
67
35
56
70
71
36
58
70
72
37
60
69
72
-
-
46
60
62
-
47
62
65
-
49
65
68
-
49
64
66
-
37
51
54
-
37
52
55
-
37
54
56
-
35
51
53
-
42
54
55
-
43
56
57
-
44
59
60
-
45
56
59
-
33
45
46
-
33
46
47
-
33
47
48
-
31
43
45
-
3000
3500
4000
4500
5000
98
91
121
110
100
102
124
113
103
105
127
116
106
107
130
119
108
110
113
100
91
98
100
102 100
86
94
74
96
116
103
94
107
103 103 100
105 105 103
93
112 102
106 106 104
107 107 106
97
79
66
88
119
106
96
99
99
84
69
93
123
109
99
117 108
108 108 107
110 110 110
48
63
65
33
48
50
109 104
99 99
102 102 102
45
54
57
30
39
42
102
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
101
87
79
83
105
90
81
86
108
92
84
88
112
96
87
91
115
99
89
13.8
13.0
12.7
12.9
14.0
13.2
12.9
13.0
14.1
13.3
13.0
13.1
14.2
13.4
13.1
13.2
14.4
13.6
13.3
13.4
64
80
79
83
71
89
81
86
78
92
84
88
86
96
87
91
93
99
89
94
55
72
79
82
61
79
81
85
66
86
84
88
72
94
87
91
78
99
89
94
46
63
74
74
51
69
80
80
55
75
84
87
59
80
87
90
63
86
89
94
38
55
65
65
40
59
70
70
43
63
75
75
46
67
75
77
48
71
75
79
29
46
57
56
30
49
60
60
31
51
64
63
32
54
62
64
33
56
60
65
-
-
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
38
48
48
-
39
50
50
-
40
52
52
-
41
49
51
-
29
40
39
-
29
40
40
-
28
40
40
-
27
35
37
-
3000
3500
4000
4500
5000
†
41
45
50
27
30
35
94
16
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 9: COOLING CAPACITY DM150 (12-1/2 TON) UNIT
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Cap.*
(MBH)
Tot.
Input†
(kW)
Tot.
Cap.* Input†
(MBH)
Tot.
WB
(°F)
CFM
3750
4375
5000
5625
6250
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
154
152
145
144
158
156
148
147
161
159
151
150
161
158
151
150
160
158
150
149
12.0
11.8
11.6
11.6
12.0
11.8
11.7
11.7
12.1
11.8
11.7
11.7
12.1
11.9
11.7
11.7
12.1
11.9
11.7
11.7
93
82
71
61
90
50
79
39
69
96
29
58
85
90
26
57
85
91
22
56
86
92
16
50
81
83
10
45
76
74
151
147
138
138
155
150
142
142
158
154
145
145
157
153
144
144
157
152
143
143
13.4
13.1
13.0
13.0
13.5
13.2
13.0
13.0
13.5
13.2
13.1
13.1
13.5
13.2
13.1
13.1
13.5
13.2
13.1
13.0
91
80
70
98
59
88
48
77
38
66
91
94
37
68
94
98
36
69
97
27
56
80
84
24
55
81
85
22
55
83
87
16
50
76
78
10
45
69
69
122 112 101
145 138 128 117 106
144 143 133 122 111 101
101
133 120 107
148 145 136 123 111
147 147 141 129 116 104
110
120 109
138 134 123 112 101
138 137 126 116 105
89
76
63
95
51
82
38
70
98
100
87
75
62
93
50
80
131 118 106
142 139 132 119 107
142 141 136 123 111
95
81
66
99
52
85
37
70
109
95
80
65
98
51
84
143 129 114
151 151 144 130 115 101
150 150 150 136 121 106
142 128 113
145 145 141 126 112
145 145 145 131 116 101
115
147 133 116 100
144 144 142 126 109
144 144 144 128 111
122 103
152 138 119 101
116
99
83
66
49
83
33
67
97
99
82
66
49
83
32
66
92
94
28
63
88
88
150 133 117 100
151 151 147 131 114
150 150 150 133 116 100
122 103
156 138 119 100
150 150 150 132 113
149 149 149 130 112
84
66
47
82
28
63
94
93
84
66
47
82
143 143 143 125 106
143 143 143 125 106
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
144
139
130
130
148
143
134
134
152
147
137
137
151
145
136
136
149
144
134
135
15.1
14.7
14.5
14.5
15.1
14.8
14.6
14.6
15.2
14.9
14.6
14.7
15.3
14.9
14.7
14.7
15.3
14.9
14.7
14.7
88
77
66
96
56
85
45
74
94
96
47
79
34
63
83
85
34
66
87
89
34
68
91
93
30
65
85
86
26
61
79
79
24
53
72
74
22
53
75
77
20
54
77
79
13
48
68
69
7
138
131
122
122
142
135
126
126
146
139
129
129
144
137
127
127
142
135
125
126
16.7
16.2
16.0
16.1
16.8
16.4
16.1
16.2
16.9
16.5
16.2
16.3
17.0
16.6
16.3
16.4
17.0
16.6
16.3
16.4
85
74
63
93
53
82
97
97
57
89
42
71
86
86
44
77
93
93
47
82
31
61
75
75
32
64
80
81
32
68
85
86
28
64
78
78
23
59
70
70
21
50
65
65
19
51
68
68
18
53
71
71
11
47
61
61
4
117 106
130 126 115 104
130 128 117 106
114 103
122 118 107
122 118 108
3750
4375
5000
5625
6250
98
85
72
60
91
95
82
70
129 117 104
134 131 125 113 100
134 132 127 114 102
127 115 102
126 124 118 106
126 124 118 106
107
93
78
63
98
49
83
105
91
76
61
97
141 127 112
137 137 135 121 106
137 137 137 123 108
139 126 111
129 129 129 115 100
129 129 129 115 100
113
96
80
63
98
47
82
111
94
77
61
97
44
80
94
94
42
78
88
88
142 131 115
136 136 135 118 102
136 136 136 119 103
119 100
144 136 117
137 130 113
127 127 127 111
127 127 127 111
82
63
99
44
80
97
97
116
97
79
60
97
43
60
60
135 134 115
125 125 125 107
126 126 126 107
41
51
51
134 134 134 116
135 135 135 116
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
131
124
114
114
136
128
117
118
140
132
121
121
137
129
119
119
134
127
117
117
18.3
17.8
17.5
17.6
18.4
18.0
17.6
17.8
18.6
18.2
17.8
18.0
18.7
18.2
17.9
18.0
18.8
18.3
18.0
18.1
81
71
60
90
49
79
89
87
54
88
99
97
60
96
39
68
78
77
42
75
86
85
45
81
94
92
42
79
87
86
39
76
79
79
28
58
68
66
29
62
74
72
30
67
80
78
25
62
70
69
20
58
61
61
17
47
57
55
17
50
61
59
16
52
65
63
9
46
53
53
2
39
42
42
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
111 100
114 110 100
3750
4375
5000
5625
6250
114 109
92 80
124 113 100
117 116 112
118 115 110
98
67
†
103
89
74
132 125 111
121 121 121 109
121 121 121 107
108
92
75
58
95
129 129 112
119 119 119 103
119 119 119 102
113
95
76
57
95
98
98
127 127 113
117 117 117
117 117 117
Johnson Controls Unitary Products
17
246645-YTG-C-0708
TABLE 10: ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
1.5
HP
2
HP
1.5
HP
2
HP
1.5
HP
2
1.5
2
1.5
HP
50
50
70
80
2
HP
50
50
70
80
110
50
50
80
90
125
30
30
35
45
60
20
20
30
40
50
FLA FLA
HP HP HP
None
--
6.8
13.5
18
25.5
--
--
38.0
38.0
54.6
70.2
96.2
38.0
38.0
61.9
79.9
40.0 43.5 45.5 50 50
40.0 43.5 45.5 50 50
57.1 61.5 64.0 60 60
72.7 77.1 79.6 80 80
2TP04520925
2TP04521825
2TP04522425
2TP04523625
None
18.9
37.5
50.0
70.8
--
208
230
460
12.8 110.0
1.5
1.5
0.8
0.6
6.2
6.2
3.1
2.4
8.2
8.2
4.1
3.6
5.5
5.5
2.2
1.8
0.0
0.0
0.0
0.0
98.7 103.1 105.6 100 100 110
40.0 43.5 45.5 50 50
40.0 43.5 45.5 50 50
64.4 68.8 71.3 70 70
82.4 86.8 89.3 80 90
50
50
70
90
2TP04520925
2TP04521825
2TP04522425
2TP04523625
None
2TP04520946
2TP04521846
2TP04522446
2TP04523646
None
2TP04520958
2TP04521858
2TP04522458
2TP04523658
9
21.7
43.3
57.7
12.8 110.0
18
24
34
--
81.8 110.0 112.5 116.9 119.4 110 125 125
--
20.7
20.7
30.9
40
21.7 22.9 23.9 25 25
21.7 22.9 23.9 25 25
32.2 33.7 34.9 35 35
41.2 42.7
56.2 57.7
16.3 16.9 18.1 20 20
16.3 16.9 18.1 20 20
26.2 26.9 28.4 25 30
33.4 34.1 35.6 35 35
45.4 46.1 47.6 45 50
25
25
35
45
60
20
20
30
35
50
9
11.3
22.6
30.1
42.7
--
7.1
5.1
54.0
44.0
18
24
34
--
44
59
40 45
60 60
55
15.1
15.1
24.7
31.9
43.9
9
9.0
575
18
24
34
18.1
24.1
34.1
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 11: ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
1.5
HP
2
HP
1.5
HP
2
HP
1.5
HP
2
1.5
2
1.5
HP
60
60
80
90
2
HP
60
60
80
100
125
60
FLA FLA
HP HP HP
None
--
6.8
13.5
18
25.5
--
--
48.0
48.0
67.1
82.7
50.0 53.5 55.5 60 60
50.0 53.5 55.5 60 60
69.6 74.0 76.5 70 70
85.2 89.6 92.1 90 90
2TP04520925
2TP04521825
2TP04522425
2TP04523625
None
18.9
37.5
50.0
208
230
460
12.8 110.0
1.5
1.5
0.8
0.6
6.2
6.2
3.1
2.4
8.2
8.2
4.1
3.6
5.5
5.5
2.2
1.8
10.0
10.0
5.0
70.8 108.7 111.2 115.6 118.1 110 125 125
--
48.0
48.0
74.4
92.4
50.0 53.5 55.5 60 60
50.0 54.2 56.7 60 60
76.9 81.3 83.8 80 80
60
60
90
2TP04520925
2TP04521825
2TP04522425
2TP04523625
None
2TP04520946
2TP04521846
2TP04522446
2TP04523646
None
2TP04520958
2TP04521858
2TP04522458
2TP04523658
9
21.7
43.3
57.7
60
90
12.8 110.0
18
24
34
--
94.9 99.3 101.8 100 100 100
110
150
35
81.8 122.5 125.0 129.4 131.9 125 125 150
--
25.7
25.7
37.2
46.2
61.2
19.1
19.1
29.7
36.9
48.9
26.7 27.9 28.9 30 30
26.7 27.9 28.9 30 30
38.4 39.9 41.2 40 40
30
30
40
50
70
25
25
35
40
60
9
11.3
22.6
30.1
42.7
--
35
7.1
5.1
54.0
44.0
18
24
34
--
45
47.5
62.5
49
64
50.2 50 50
65.2 70 70
60
70
20.3 20.9 22.1 20 25
20.3 21.1 22.6 20 25
31.2 31.9 33.4 30 35
38.4 39.1 40.6 40 40
50.4 51.1 52.6 50 60
25
9
9.0
25
575
4.0
18
24
34
18.1
24.1
34.1
35
45
60
*
Maximum HACR breaker of the same AMP size is applicable.
18
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 12: ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/O PWRD CONV. OUTLET
Supply
Blower Motor
FLA
Pwr
Conv
Outlet
Max Fuse Size
w/Power Exhaust
(Amps)
OD Fan
Motors
Pwr Exh
Motor
Min. Circuit
MCA w/Power
Max Fuse*
Compressors
Ampacity (Amps) Exhaust (Amps) Size (Amps)
Electric Heater
Model No.
Actual
KW
Heater
Amps
Voltage
RLA
ea.
LRA
ea.
FLA
ea.
2 HP 3 HP
FLA
FLA
2 HP
3 HP
2 HP
3 HP
2 HP 3 HP 2 HP
3 HP
None
--
--
41.1
41.1
57.1
72.7
98.7
43.8
43.8
60.5
76.1
102.1
46.6
46.6
64.0
79.6
105.6
49.3
49.3
67.3
83.0
109.0
50
50
60
80
50
50
70
80
50
50
60
60
2TP04540925
2TP04541825
2TP04542425
2TP04543625
6.8
18.9
37.5
50.0
70.8
208
230
460
575
11.5
11.5
6.4
84.0
84.0
42.0
34.0
3.5
3.5
1.6
1.3
8.2
8.2
4.1
3.6
10.9
10.9
5.3
5.5
0.0
13.5
18.0
25.5
70
70
80
110
90
110
100 110
None
--
--
41.1
41.1
64.4
82.4
112.5
43.8
43.8
67.8
85.8
115.9
46.6
46.6
71.3
89.3
119.4
49.3
49.3
74.6
92.7
122.7
50
50
70
90
50
50
70
90
50
50
60
60
2TP04540925
2TP04541825
2TP04542425
2TP04543625
9.0
21.7
43.3
57.7
81.8
5.5
2.2
1.8
0.0
0.0
0.0
18.0
24.0
34.0
80
80
90
125
100
125
125 125
None
--
--
21.7
21.7
32.2
41.2
56.2
22.9
22.9
33.7
42.7
57.7
23.9
23.9
34.9
44
25.1
25.1
36.4
45.5
60.5
25
25
35
45
60
25
25
35
45
60
30
30
35
45
60
30
30
40
50
70
2TP04540946
2TP04541846
2TP04542446
2TP04543646
9
11.3
22.6
30.1
42.7
18
24
34
59
None
--
--
17.7
17.7
26.2
33.4
45.4
18.2
18.2
26.8
34
19.5
19.5
28.4
35.6
47.6
20
20
20
20
30
35
50
20
20
30
35
50
20
20
30
40
50
25
25
30
40
50
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
5.1
4.1
18
24
34
18.1
24.1
34.1
29
36.2
48.3
46
TABLE 13: ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD EFFICIENCY W/PWRD CONV. OUTLET
Supply
Blower Motor
FLA
Pwr
Conv
Outlet
Max Fuse Size
w/Power Exhaust
(Amps)
OD Fan
Motors
Pwr Exh
Motor
Min. Circuit
MCA w/Power
Max Fuse*
Compressors
Ampacity (Amps) Exhaust (Amps) Size (Amps)
Electric Heater
Model No.
Actual
KW
Heater
Amps
Voltage
RLA
ea.
LRA
ea.
FLA
ea.
2 HP 3 HP
FLA
FLA
2 HP
3 HP
2 HP
3 HP
2 HP 3 HP 2 HP
3 HP
None
--
--
51.1
51.1
69.6
85.2
111.2
53.8
53.8
73.0
88.6
114.6
56.6
56.6
76.5
92.1
118.1
59.3
59.3
79.8
95.5
121.5
60
60
70
90
60
60
80
90
60
60
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
6.8
18.9
37.5
50.0
70.8
208
230
460
575
11.5
11.5
6.4
84.0
84.0
42.0
34.0
3.5
3.5
1.6
1.3
8.2
8.2
4.1
3.6
10.9
10.9
5.3
5.5
10.0
13.5
18.0
25.5
80
80
100
125
100
125
125 125
None
--
--
51.1
51.1
76.9
94.9
125.0
53.8
53.8
80.3
98.3
128.4
56.6
56.7
59.3
60.1
60
60
80
60
60
90
60
60
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
9.0
21.7
43.3
57.7
81.8
5.5
2.2
1.8
10.0
5.0
18.0
24.0
34.0
83.8
87.1
90
90
101.8
131.9
105.2
135.2
100 100
125 150
110
150
110
150
None
--
--
26.7
26.7
38.4
47.5
62.5
27.9
27.9
39.9
49
28.9
28.9
41.2
50.2
65.2
30.1
30.1
42.7
51.7
66.7
30
30
40
50
70
30
30
40
50
70
35
35
45
60
70
35
35
45
60
70
2TP04540946
2TP04541846
2TP04542446
2TP04543646
9
11.3
22.6
30.1
42.7
18
24
34
64
None
--
--
21.7
21.7
31.2
38.4
50.4
22.2
22.2
31.8
39
23.5
23.5
33.4
40.6
52.6
24
24
25
25
35
40
60
25
25
35
40
60
25
25
35
45
60
25
25
35
45
60
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
5.1
4.1
4.0
18
24
34
18.1
24.1
34.1
34
41.2
53.3
51
Johnson Controls Unitary Products
19
246645-YTG-C-0708
TABLE 14: ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
Max Fuse Size
Pwr
Conv
Outlet
Min. Circuit MCA w/Power
OD Fan Supply Blower Pwr Exh
Max Fuse*
Size (Amps)
w/Power
Exhaust
(Amps)
Compressors
Ampacity
(Amps)
Exhaust
(Amps)
Motors
Motor FLA
Motor
Electric Heater Actual Heater
Voltage
Model No.
KW
Amps
RLA
ea.
LRA
ea.
FLA
ea.
3 HP
3 HP
FLA
FLA
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP
None
--
6.8
13.5
18
25.5
--
--
44.2
44.2
60.5
76.1
44.2
44.2
60.5
76.1
49.7
49.7
67.3
83.0
49.7
49.7
67.3
83.0
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
60
60
70
90
110
60
60
80
100
125
30
30
40
50
70
25
25
30
40
50
60
60
70
90
110
60
60
80
100
125
30
30
40
50
70
25
25
30
40
50
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
2TP04540946
2TP04541846
2TP04542446
2TP04543646
None
2TP04540958
2TP04541858
2TP04542458
2TP04543658
18.9
37.5
50.0
70.8
--
21.7
43.3
57.7
81.8
--
11.3
22.6
30.1
42.7
--
208
230
460
575
11.7
11.7
6.4
88.0
88.0
42.0
36.0
3.5
3.5
1.6
1.3
10.9
10.9
5.3
10.9
5.5
5.5
2.2
1.8
0.0
102.1 102.1 109.0 109.0
44.2
44.2
67.8
85.8
44.2
44.2
67.8
85.8
50.4
50.4
74.6
92.7
50.4
50.4
74.6
92.7
9
10.9
5.3
0.0
0.0
0.0
18
24
34
--
115.9 115.9 122.7 122.7
22.9
22.9
33.7
42.7
57.7
18.2
18.2
26.8
34
22.9
22.9
33.7
42.7
57.7
18.2
18.2
26.8
34
25.1
25.1
36.4
45.5
60.5
20
20
29
36.2
48.3
25.1
25.1
36.4
45.5
60.5
20
20
29
36.2
48.3
9
18
24
34
--
9
9.0
5.1
4.1
4.1
18
24
34
18.1
24.1
34.1
46
46
TABLE 15: ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
Max Fuse Size
Pwr
Conv
Outlet
Min. Circuit MCA w/Power
OD Fan Supply Blower Pwr Exh
Max Fuse*
Size (Amps)
w/Power
Exhaust
(Amps)
Compressors
Ampacity
(Amps)
Exhaust
(Amps)
Motors
Motor FLA
Motor
Electric Heater Actual Heater
Voltage
Model No.
KW
Amps
RLA
ea.
LRA
ea.
FLA
ea.
3 HP
3 HP
FLA
FLA
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP
None
--
--
54.2
54.2
73.0
88.6
54.2
54.2
73.0
88.6
59.7
59.7
79.8
95.5
59.7
59.7
79.8
95.5
60
60
60
60
70
70
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
6.8
18.9
37.5
50.0
70.8
208
230
460
575
11.7
11.7
6.4
88.0
88.0
42.0
36.0
3.5
3.5
1.6
1.3
10.9
10.9
5.3
10.9
5.5
5.5
2.2
1.8
10.0
13.5
18
25.5
80
80
80
80
90
125
90
125
100
125
100
125
114.6 114.6 121.5 121.5
None
--
9
--
54.2
54.2
80.3
98.3
54.2
54.2
80.3
59.7
59.7
87.1
59.7
59.7
87.1
60
60
60
60
70
70
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
21.7
43.3
57.7
81.8
10.9
5.3
10.0
10.0
10.0
18
24
34
90
90
90
90
98.3 105.2 105.2
100
150
100
150
110
150
110
150
128.4 128.4 135.2 135.2
None
--
--
27.9
27.9
39.9
49
27.9
27.9
39.9
49
30.1
30.1
42.7
51.7
66.7
30.1
30.1
42.7
51.7
66.7
30
30
40
50
70
30
30
40
50
70
35
35
45
60
70
35
35
45
60
70
2TP04540946
2TP04541846
2TP04542446
2TP04543646
9
11.3
22.6
30.1
42.7
18
24
34
64
64
None
--
--
22.2
22.2
31.8
39
22.2
22.2
31.8
39
24
24
24
24
25
25
35
40
60
25
25
35
40
60
25
25
35
45
60
25
25
35
45
60
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
5.1
4.1
4.1
18
24
34
18.1
24.1
34.1
34
34
41.2
53.3
41.2
53.3
51
51
20
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 16: ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
2
HP
3
HP
2
HP
3
HP
2
3
2
3
2
HP
70
3
HP
70
70
90
FLA
FLA
HP
HP
HP HP
None
--
13.5
18
25.5
40.6
--
--
51.9
57.1
72.7
54.6 57.4 60.1 60 70
60.5 64.0 67.3 60 70
76.1 79.6 83.0 80 80
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
70.8
70
208
230
460
16.3 150.0
3.5
3.5
1.6
1.3
8.2 10.9
8.2 10.9
5.5
0.0
80
98.7 102.1 105.6 109.0 100 110
112.7 151.1 154.5 158.0 161.4 175 175
110
175
70
110
175
70
--
51.9
64.4
82.4
54.6 57.4 60.1 60 70
67.8 71.3 74.6 70 70
85.8 89.3 92.7 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
24
34
54
--
18
24
34
54
--
43.3
57.7
80
80
16.3 150.0
5.5
2.2
1.8
0.0
0.0
0.0
90
100
125
175
45
81.8 112.5 115.9 119.4 122.7 125 125
129.9 140.2 143.5 147.0 150.4 150 175
125
175
45
--
33.2
33.2
41.2
56.2
70.1
22.2
26.2
33.4
45.4
56.5
34.4 35.4 36.6 40 45
34.4 35.4 36.6 40 45
22.6
30.1
42.7
67.8
--
45
45
11.5
7.1
75.0
62.0
4.1
3.6
5.3
4.1
42.7
57.7
44
59
45.5 45 45
60.5 60 60
45
50
60
70
71.6 72.8 74.3 80 80
22.7 24 24.5 25 25
26.8 28.4 29 30 30
35.6 36.2 35 35
47.6 48.3 50 50
57.1 58.7 59.3 70 70
80
80
30
30
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
24
34
54
18.1
24.1
34.1
54.2
30
30
575
34
46
40
40
50
50
70
70
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 17: ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY WITH PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
2
HP
3
HP
2
HP
3
HP
2
3
2
3
2
3
FLA
FLA
HP
HP
HP HP
HP
80
HP
80
None
--
13.5
18
25.5
40.6
--
--
37.5
50.0
61.9
69.6
85.2
64.6 67.4 70.1 70 80
73.0 76.5 79.8 70 80
88.6 92.1 95.5 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
80
80
208
230
460
16.3 150.0
3.5
3.5
1.6
1.3
8.2 10.9
8.2 10.9
5.5
10.0
100
125
175
80
100
125
175
80
70.8 111.2 114.6 118.1 121.5 125 125
112.7 163.6 167.0 170.5 173.9 175 175
--
61.9
76.9
94.9
64.6 67.4 70.1 70 80
80.3 83.8 87.1 80 90
98.3 101.8 105.2 100 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
24
34
54
--
18
24
34
54
--
43.3
57.7
90
90
16.3 150.0
5.5
2.2
1.8
10.0
5.0
110
150
175
50
110
150
175
50
81.8 125.0 128.4 131.9 135.2 125 150
129.9 152.7 156.0 159.5 162.9 175 175
--
38.2
38.4
47.5
62.5
76.3
26.2
31.2
38.4
50.4
61.5
39.4 40.4 41.6 45 50
39.9 41.2 42.7 45 50
50.2 51.7 50 50
65.2 66.7 70 70
77.8 79.1 80.6 90 90
26.7 28 28.5 30 30
31.8 33.4 34 35 35
40.6 41.2 40 40
52.6 53.3 60 60
62.1 63.7 64.3 70 70
22.6
30.1
42.7
67.8
--
50
50
11.5
7.1
75.0
62.0
4.1
3.6
5.3
4.1
49
64
60
60
70
70
90
90
35
35
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
24
34
54
18.1
24.1
34.1
54.2
35
35
575
4.0
39
51
45
45
60
60
70
70
*
Maximum HACR breaker of the same AMP size is applicable.
Johnson Controls Unitary Products
21
246645-YTG-C-0708
TABLE 18: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max
Fuse
Size
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps) w/Power
RLA
ea.
LRA
ea.
FLA
ea.
3
5
HP
3
5
HP
3
5
3
5
3
5
FLA
FLA
HP
HP
HP
HP HP HP HP HP
None
--
13.5
18
25.5
40.6
--
18
24
34
54
--
18
24
34
54
--
18
24
34
54
--
37.5
50.0
62.9 68.1 68.4 73.6 80 80 80 90
62.9 68.1 68.4 73.8 80 80 80 90
76.1 82.6 83.0 89.5 80 90 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
208
230
460
20.0 146.0
3.5
3.5
1.6
1.3
10.9 16.1
10.9 16.1
5.5
0.0
70.8 102.1 108.6 109.0 115.5 110 110 110 125
112.7 154.5 161.0 161.4 167.9 175 175 175 175
--
43.3
57.7
81.8 115.9 122.4 122.7 129.2 125 125 125 150
129.9 143.5 150.0 150.4 156.9 175 175 175 175
--
22.6
30.1
42.7
67.8
--
18.1
24.1
34.1
54.2
62.9 68.1 68.4 73.6 80 80 80 90
67.8 74.3 74.6 81.1 80 80 80 90
85.8 92.3 92.7 99.2 90 100 100 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
20.0 146.0
5.5
2.2
1.8
0.0
0.0
0.0
27.4 30.2 29.6 32.4 35 35 35 40
33.7 37.2 36.4 39.9 35 40 40 40
8.4
6.7
73.0
60.0
5.3
4.1
8.1
6.0
42.7 46.2 45.5
57.7 61.2 60.5
49
64
45 50 50 50
60 70 70 70
71.6 75.1 74.3 77.8 80 90 80 90
21.8 23.7 23.6 25.5 25 30 30 30
2TP04521858
2TP04522458
2TP04523658
2TP04525458
26.8 29.2
29
31.4 30 30 30 35
575
34
46
36.4 36.2 38.6 35 40 40 40
48.4 48.3 50.6 50 50 50 60
57.1 59.5 59.3 61.7 70 70 70 70
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 19: ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY W/PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max
Fuse
Size
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps) w/Power
RLA
ea.
LRA
ea.
FLA
ea.
3
5
HP
3
5
HP
3
5
3
5
3
5
FLA
FLA
HP
HP
HP
HP HP HP HP HP
None
--
13.5
18
25.5
40.6
--
18
24
34
54
--
18
24
34
54
--
18
24
34
54
--
37.5
50.0
72.9 78.1 78.4 83.6 90 90 90 100
73.0 79.5 79.8 86.3 90 90 90 100
88.6 95.1 95.5 102.0 90 100 100 110
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
208
230
460
20.0 146.0
3.5
3.5
1.6
1.3
10.9 16.1
10.9 16.1
5.5
10.0
70.8 114.6 121.1 121.5 128.0 125 125 125 150
112.7 167.0 173.5 173.9 180.4 175 175 175 200
--
43.3
57.7
81.8 128.4 134.9 135.2 141.7 150 150 150 150
129.9 156.0 162.5 162.9 169.4 175 175 175 175
--
22.6
30.1
42.7
67.8
--
18.1
24.1
34.1
54.2
72.9 78.1 78.4 83.6 90 90 90 100
80.3 86.8 87.1 93.6 90 90 90 100
98.3 104.8 105.2 111.7 100 110 110 125
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
20.0 146.0
5.5
2.2
1.8
10.0
5.0
32.4 35.2 34.6 37.4 40 40 40 45
39.9 43.4 42.7 46.2 40 45 45 50
8.4
6.7
73.0
60.0
5.3
4.1
8.1
6.0
49
64
52.5 51.7 55.2 50 60 60 60
67.5 66.7 70.2 70 70 70 80
77.8 81.3 80.6 84.1 90 90 90 90
25.8 27.7 27.6 29.5 30 30 30 35
2TP04521858
2TP04522458
2TP04523658
2TP04525458
31.8 34.2
34
36.4 35 35 35 40
575
4.0
39
51
41.4 41.2 43.6 40 45 45 45
53.4 53.3 55.6 60 60 60 60
62.1 64.5 64.3 66.7 70 70 70 70
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 20: ELECTRIC HEAT MULTIPLIERS
•
•
•
Blower performance includes dry coil and 2” throwaway
filters.
VOLTAGE
kW Cap. Multiplier
NOMINAL
RATING
208
0.75
0.92
0.92
0.92
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
240
230
480
600
460
ESP (External Static Pressure) given is that available for
the supply and return air duct system. All internal resis-
tances have been deducted from the total static pressure
of the blower.
575
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.
22
Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 31: ADDITIONAL STATIC RESISTANCE DM078, 120 AND 150
Electric Heat KW
*
† ‡
CFM
Cooling Only
Economizer
9
18
24
36
54
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
*
†
‡
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 32: ADDITIONAL STATIC RESISTANCE DM090, 102
Electric Heat KW†
24
*
† ‡
CFM
Cooling Only
Economizer
9
18
36
54
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
-0.004
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.09
0.10
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.33
0.05
0.06
0.07
0.08
0.09
0.1
0.06
0.07
0.08
0.09
0.1
0.07
0.08
0.09
0.1
0.08
0.09
0.1
0.1
0.11
0.13
0.14
0.16
0.18
0.2
0.11
0.13
0.14
0.16
0.18
0.2
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.11
0.13
0.14
0.16
0.18
0.2
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.22
0.24
0.26
0.28
0.31
0.34
0.22
0.24
0.26
0.29
0.22
0.24
*
†
‡
Deduct these resistance values to the available static resistance in the respective Blower Performance Tables.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Unitary Products
33
246645-YTG-C-0708
TABLE 33: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE (NOMINAL TONS)
HEATER
078 (6.5)
090 (7.5)
102 (8.5)
120 (10)
150 (12.5)
VOLTAGE
kW
MINIMUM SUPPLY AIR CFM
1950
1950
1950
1950
N/A
2250
2250
2250
2250
N/A
2550
2550
2550
2550
N/A
N/A
3000
3000
3000
3500
N/A
N/A
3750
3750
3750
4000
N/A
9
18
24
36
54
9
208/230
1950
1950
1950
1950
N/A
2250
2250
2250
2250
N/A
2550
2550
2550
2550
N/A
3000
3000
3000
3000
N/A
3750
3750
3750
3750
N/A
18
24
36
54
9
480
600
1950
1950
1950
1950
N/A
2250
2250
2250
2250
N/A
2550
2550
2550
2550
N/A
3000
3000
3000
3500
3750
3750
3750
3750
18
24
36
54
TABLE 34: INDOOR BLOWER SPECIFICATIONS
MOTOR
RPM Eff.
1-1/2 1725 80% 1.15
MOTOR SHEAVE
BLOWER SHEAVE
MODEL
DM078
DM090
DM102
DM120
DM150
BELT
HP
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
56
56
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
4.3 - 5.3
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
9.5
7.5
6.5
6.0
6.0
5.7
8.5
7.0
7.0
6.7
1
1
1
1
1
1
1
1
1
1
AK99
AK79
AK69
AK64
AK64
AK61
AK89
AK74
AK74
BK77
A58
A55
A49
A49
A49
A49
A56
A54
A54
BX55
2
2
3
3
3
2
3
3
5
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 87% 1.15
56
56
56
56
56
56
56
184T
TABLE 35: POWER EXHAUST SPECIFICATIONS
MOTOR
RPM*
ELECTRICAL
POWER EXHAUST
FUSE
SIZE
CFM@
0.1 ESP
VOLT
PHASE
MODEL
HP
QTY
LRA
24.9
FLA
5.0
MCA
2PE0473225
2PE0473246
2PE0473258
208/230
460
1
1
1
6.3
2.8
1.9
10
5
1075
1050
0.75
1
2.2
3,800
N/A
575
1.5
4
*
Motors are multi-tapped and factory wired for high speed.
34
Johnson Controls Unitary Products
246645-YTG-C-0708
Y
X
FRONT
LEFT
X
Y
Unit Model Number
DM078
47 1/2
38
25 1/2
23
DM090
38
23
DM102
F
R
O
N
T
47 1/2
47 1/2
25 1/2
25 1/2
DM120
L
E
F
T
B
C
DM150
A
FIGURE 3 - UNIT CENTER OF GRAVITY
D
FIGURE 2 - UNIT 4 POINT LOAD
TABLE 36: 4 POINT LOAD WEIGHT
Location (lbs.)
Model
A
B
C
D
DM078
DM090
DM102
DM120
DM150
228
192
195
245
262
195
143
146
209
224
285
224
228
305
327
333
301
306
357
382
F
R
O
N
T
L
E
F
T
D
C
B
A
E
F
FIGURE 4 - UNIT 6 POINT LOAD
Johnson Controls Unitary Products
35
246645-YTG-C-0708
TABLE 37: 6 POINT LOAD WEIGHT
TABLE 38: UNIT WEIGHT
Model
DM078
DM090
DM102
DM120
DM150
Shipping Weight (lbs.)
Operating Weight (lbs.)
Locations (lbs.)
Model
1046
865
1041
860
A
B
C
D
E
F
DM078
DM090
DM102
DM120
DM150
156
135
137
168
180
140
110
112
151
161
127
91
185
142
145
198
212
205
172
145
219
235
228
211
214
244
262
880
875
1121
1200
1116
1195
93
136
145
30-11/32
See Detail
A
X
Control
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
Power
Entry
4-1/4
Ø 2-1/2
11-1/2
Convenience
Power
Outlet
Entry
For Baserail
Dimensions
See Detail B
Ø 7/8
FRONT
17-3/16
For Drain
Dimensions
See Detail C
30-3/16
24-3/16
6-3/16
59
LEFT
89
27
FIGURE 5 - UNIT DIMENSIONS
TABLE 40: UNIT CLEARANCES
TABLE 39: UNIT HEIGHT
72”
36”
36”
Right
12”
36”
0”
X
Top*
Unit Model Number
DM078
50 3/4
42
Front
Left
DM090
Rear†
Bottom‡
42
DM102
*
Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.
50 3/4
50 3/4
DM120
DM150
†
To remove the slide-out drain pan, a rear clearance of
60” is required. If space is unavailable, the drain pan
can be removed through the front by separating the
corner wall.
DETAIL A
G
a
s
P
i
p
e
I
n
l
e
t
‡
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
5
-
1
/
4
B
P
a
a
s
n
e
1
7
-
1
3
/
1
6
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
36
Johnson Controls Unitary Products
246645-YTG-C-0708
DETAIL C
DETAIL B
2-3/8
5
-
3
/
8
3-3/4
3-9/16
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
F
R
O
N
T
8
o
r
1
4
FIGURE 6 - PREDATOR® ROOF CURB DIMENSIONS
Johnson Controls Unitary Products
37
246645-YTG-C-0708
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
F
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 7 - SUNLINE™ TO PREDATOR® TRANSITION ROOF CURBS
32-11/16
6-13/16
Supply
Air
6-13/16
6-13/16
Return
Air
24
LEFT
27-1/2
21
18
21-3/16
19-3/16
17-3/16
12-5/16
7-1/8
FRONT
14-23/32
16-3/8
Bottom
Bottom
Bottom
Gas Supply Entry
18-1/16
19-5/8
Condensate
Drain
Power, Control and
Convenience Outlet
Wiring Entries
63-1/2
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)
38
Johnson Controls Unitary Products
246645-YTG-C-0708
REAR DUCT DIMENSIONS
DIMENSION
CABINET SIZE
“A”
“B”
“C”
50 3/4”
42”
28 1/4
27 3/4
18 1/16
12 1/16
28 1/4
27 1/2
FIGURE 9 - REAR DUCT DIMENSIONS
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
Relief Hood for
Power Exhaust or
Barometric Relief
26
25 3/4
26
30 1/4
FIGURE 10 - DOWNFLOW ECONOMIZER HOOD DETAIL
Johnson Controls Unitary Products
39
246645-YTG-C-0708
TABLE 41: ECONOMIZER USAGE
Application
Cabinet Height
Description
Model
Bottom Return
Side Return
All
All
Downflow economizer with barometric relief
Horizontal economizer without barometric relief
Slab Economizer, 42” tall cabinet
2EE04705424
2EE04705524*
2EE04705624†
2EE04705224†
42"
50"
ERV or End Return
Slab Economizer, 50” tall cabinet
*
†
Barometric relief must be ordered separately and installed in duct work.
Barometric relief or fresh air hood not included. Must be ordered separately.
2EE04705424
Fresh Air Hood Fresh Air Damper Return Air Damper
Barometric Relief Damper
2EE04705424
2EE04705424
2EE04705424
2EE04705424
Barometric Relief Hood
FIGURE 11 - FACTORY INSTALLED DOWNFLOW ECONOMIZER
2EE04705424
Fresh Air Hood
2EE04705424
2EE04705424
2PE047032XX
Power Exhaust
Fresh Air Damper Return Air Damper
2EE04705424
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
FIGURE 12 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST
40
Johnson Controls Unitary Products
246645-YTG-C-0708
2EE04705524
Return Air Damper
Field Installed
Duct Work
2EE04705524
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04705524
Fresh Air Hood
FIGURE 13 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
1EH0409 Barometric
Relief Hood
FIGURE 14 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST
Johnson Controls Unitary Products
41
246645-YTG-C-0708
GUIDE SPECIFICATIONS
PREDATOR®
DM 078, 090, 102, 120 & 150
9.0 EER
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. YORK® Pred-
ator® units are convertible single packages with a common
footprint cabinet and common roof curb for all 6-1/2 through
12-1/2 ton models. All units have two compressors with inde-
pendent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications
and can be easily installed on a roof curb, slab, or frame. All
Predator® units are self-contained and assembled on rigid full
perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
sizes. Predator® units are available in the following configura-
tions: cooling only, cooling with electric heat, and cooling with
gas heat. Electric heaters are available as factory-installed
options and field-installed accessories.
fan performance without removing panels or creating bypass
of the coils. Condensate pan shall be slide out design, con-
structed of a non corrosive material, internally sloped and
conforming to ASHRAE 62-B9 standards. Condensate con-
nection shall be a minimum of ¾” I.D. female and be rigid
mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall
not exceed the motors nameplate horsepower rating plus the
service factor. Units shall be designed to operate within the
service factor. Fan wheel shall be double inlet type with for-
ward curve blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed
and permanently lubricated for longer life and no mainte-
nance. Entire blower assembly and motor shall be slide out
design.
DESCRIPTION
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge
air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically bal-
anced for smooth operation. The outdoor fan motors shall
have permanently lubricated bearings internally protected
against overload conditions and staged independently. A
cleaning window shall be provided on two sides of the units
for coil cleaning.
Units shall be factory assembled, single package, (Elec/Elec,
Gas/Elec), designed for outdoor installation. Units shall have
a minimum EER of 9.0. They shall have built in field convert-
ible duct connections for down discharge supply/return or
horizontal discharge supply/return and be available with fac-
tory installed options or field installed accessories. The units
shall be factory wired, piped and charged with R-22 refriger-
ant and factory tested prior to shipment. All unit wiring shall
be both numbered and color coded. The cooling performance
shall be rated in accordance with DOE and ARI test proce-
dures. Units shall be CSA certified to ANSI Z21.47 and UL
1995/CAN/CSA No. 236-M90 standards.
REFRIGERANT COMPONENTS
Compressors:
A. Shall be fully hermetic type, direct drive, internally pro-
tected with internal high-pressure relief and over temper-
ature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of + or – 10% of the
unit nameplate voltage.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hours salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up
to 1” thick insulation coated on the airside. Aluminum foil
faced insulation shall be used in the unit’s compartments and
be fastened to prevent insulation from entering the air
stream. Cabinet doors shall be hinged with tool-less access
for easy servicing and maintenance. Full perimeter base rails
shall be provided to assure reliable transit of equipment,
overhead rigging, fork truck access and proper sealing on
roof curb applications. Disposable 2” filters shall be furnished
and be accessible through hinged access door. Fan perfor-
mance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
B. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
A. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
B. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
46
Johnson Controls Unitary Products
246645-YTG-C-0708
Refrigerant Circuit and Refrigerant Safety Components shall
include:
shot type, constructed of aluminum-coated steel. All gas pip-
ing shall enter the unit cabinet at a single location, through
either the side or bottom, without any field modifications. An
integrated control board shall provide timed control of evapo-
rator fan functioning and burner ignition. Heating section shall
be provided with the following minimum protection:
A. Independent fixed-orifice or thermally operated expan-
sion devices.
B. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
A. Primary and auxiliary high-temperature limit switches.
B. Induced draft pressure sensor.
C. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
C. Flame roll out switch (manual reset).
D. Flame proving controls. Unit shall have two independent
st
nd
D. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
stages of capacity (60% 1 stage, 100% 2 stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
Unit Controls:
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two
states of capacity all sizes. The heating section shall have a
primary limit control(s) (automatic reset) to prevent the heat-
ing element system from operating at an excessive tempera-
ture. The Heating Section assembly shall slide out of the unit
for easy maintenance and service. Units with Electric Heating
Sections shall be wired for a single point power supply with
branch circuit fusing (where required).
A. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
B. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
C. Loss-of-charge/Low-pressure switch.
(1) High-pressure switch.
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF out-
door temperature, exceeding maximum load criteria of ARI
Standard 340/360. The compressor, with standard controls,
shall be capable of operation down to 0 ºF outdoor tempera-
ture. Unit shall be provided with fan time delay to prevent cold
air delivery before heat exchanger warms up. (Gas heat only)
(2) Freeze-protection thermostat, evaporator coil. If any
of the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that indi-
cates which safety switch has tripped.
D. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
E. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
F. Unit control board shall have on-board diagnostics and
fault code display.
STANDARD LIMITED WARRANTIES - Compressor – 5
Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5
Years, Parts – 1 Year
G. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall
be made available by either/or):
H. Control board shall monitor each refrigerant safety
switch independently.
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER – Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer oper-
ation, a mixed-air temperature control shall modulate the
I. Control board shall retain last 5 fault codes in non-vola-
tile memory, which will not be lost in the event of a power
loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft
combustion with post purge logic, energy saving direct spark
ignition, and redundant main gas valve. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 40 ºF. Burners shall be of the in-
Johnson Controls Unitary Products
47
outdoor and return air damper assembly to prevent the
supply air temperature from dropping below 55 ºF.
Changeover from compressor to economizer operation
shall be provided by an integral electronic enthalpy con-
trol that feeds input into the basic module. The outdoor
intake opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/filters
shall be provided. Simultaneous economizer/compressor
operation is also possible. Dampers shall fully close on
power loss. Available with barometric relief or power
exhaust.
•
•
•
COIL GUARD - Designed to prevent condenser coil
damage.
BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high-
pressure drop across the filters.
•
•
BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor
and return air dampers that are interlocked and posi-
tioned by a 2-position, spring-return damper actuator.
The maximum leakage rate for the outdoor air intake
dampers shall not exceed 2% when dampers are fully
closed and operating against a pressure differential of
0.5 IWG. A unit-mounted potentiometer shall be provided
to adjust the outdoor and return air damper assembly to
take in the design CFM of outdoor air to meet the ventila-
tion requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected posi-
tions – regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest elec-
tric heat available.
•
STAINLESS STEEL HEAT EXCHANGER – For applica-
tions in a corrosive environment, this option provides a
full stainless steel heat exchanger assembly.
•
•
STAINLESS STEEL DRAIN PAN – Provides years of
trouble-free operation in corrosive environments.
SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air com-
partments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
•
ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
ADDITIONAL FACTORY INSTALLED OPTIONS
BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
•
•
ALTERNATE INDOOR BLOWER MOTOR – For appli-
cations with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
CONVENIENCE OUTLET (POWERED/NON-POW-
ERED) – Unit can be provided with an optional 120VAC
GFCI outlet with cover on the corner of the unit housing
the compressors.
•
•
PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
–60 ºF GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
•
•
ELECTRIC HEAT - Electric heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
•
•
ECONOMIZER (Downflow and Horizontal flow)
POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
PHASE MONITOR - Designed to prevent damage in out-
of-phase condition.
•
DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Subject to change without notice. Printed in U.S.A.
246645-YTG-C-0708
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Supersedes: 246645-YTG-B-0606
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
|
Lexmark 13b0503 User Manual
Multiquip Trash Pump Qp4tz User Manual
Newair Acp 1000e User Manual
Samsung Inkjet Facsimile Sf 331p User Manual
Sanyo Rs1211 User Manual
Schumacher Se 1252ma User Manual
Sony Found Not Kdl 32xbr6 User Manual
Toshiba Eo1 33057 User Manual
Trane Air Conditioner Tcont800as11aa User Manual
Xerox All In One Printer M15i User Manual