262259-YTG-B-0107
®
DESCRIPTION
YORK Sunline 2000™ units are convertible single package
high efficiency rooftops. All models have independent dual
refrigerant circuits for efficient part load operation. Although
the units are primarily designed for curb mounting on a roof,
they can also be slab-mounted at ground level or set on steel
beams above a finished roof.
TECHNICAL GUIDE
All units include:
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE AIR
CONDITIONERS
•
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
Two-stage cooling provided by dual independent
refrigeration circuits with expansion valves, filter-driers,
high and low pressure/loss of charge switches and
freezestats
DM 180, 240 & 300
•
•
Scroll compressors (25T model only)
15, 20 & 25 NOMINAL TONS
Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
•
•
Permanently lubricated motors
Bottom or side air discharge configuration capability
(field convertible)
•
•
Belt Drive Blower Motor with high static drive option
Constant supply air volume (CV) with optional variable
air volume (VAV)
•
•
•
•
•
•
•
•
•
Manufactured under the quality standards of ISO9001
S implicity® Control Board
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and tooless latched doors
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units
WARRANTY
•
•
One-year parts warranty
A Five-year parts warranty on the compressors and
electric heat elements
•
Ten-year parts warranty on the gas-fired heat
exchangers
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
262259-YTG-B-0107
PRODUCT NOMENCLATURE
15-25 Ton Sunline 2000™ Model Number Nomenclature
D M 180 N24 A 2 A AA 1 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
Product Identifier
M = 8.5-9.0 EER A/C
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Nominal Cooling Capacity
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
180 = 15 Ton
240 = 20 Ton
300 = 25 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume (VFD) - Not Available with Factory Installed BAS Options
Variable Air Volume (VFD With Manual Bypass) - Not Available with Factory Installed BAS Options
Variable Air Volume (VFD-Ready for Customer Installed Drive)
2" Pleated filters
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No field installed
electric heat
Gas Heat Options
4" Pleated filters
N24 = 240 MBH Output Aluminized Steel
N32 = 320 MBH Output Aluminized Steel
S24 = 240 MBH Output Stainless Steel
S32 = 320 MBH Output Stainless Steel
BAS Ready Unit with Belimo Economizer
Double Wall Construction
Heat Reclaim Coil Options (2 or 3 Row, 1-5/8" or 2-1/8" Stub Out) (WJ and WR models only)
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Electric Heat Options
Product Generation
E18 = 18 KW
E36 = 36 KW
E54 = 54 KW
E72 = 72 KW
1 = First Generation
2 = Second Generation
Additional Options
Hinged Filter Door & Toolless Access Cabinet
Airflow
Standard Cabinet
A = Std. Drive
B = Std. Drive/Single Input Econo.
C = Std. Drive/Single Input Econo./Power Exhaust
(Downflow Only)
D = Std. Drive/Motorized Damper
N = Hi Static Drive
AA = None
AB = Phase Monitor
BA = Hinged Filter Door & Toolless Access Panels
BB = Phase Monitor, Hinged Filter Door & Toolless
Access Panels
AC = Coil Guard
AD = Dirty Filter Switch
BC = Coil Guard, Hinged Filter Door & Toolless
Access Panels
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
P = Hi Static Drive/Single Input Econo.
Q = Hi Static Drive/Single Input Econo./Power Exhaust
(Downflow Only)
BD = Dirty Filter Switch, Hinged Filter Door &
Toolless Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Toolless Access Panels
R = Hi Static Drive/Motorized Damper
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Toolless Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Toolless Access Panels
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Toolless Access Panels
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Unitary Products Group
3
262259-YTG-B-0107
•
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
•
•
Lead-Lag - An integrated Lead-Lag option allows
equal run time hours on all compressors, thereby
extending the life of all compressors. This option is
selectable on the unit control board.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
All models are available with these “factory mounted” outdoor
air damper options:
•
•
•
Single enthalpy economizer
•
•
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Single enthalpy economizer with power exhaust
Motorized outdoor air damper
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement. A variable air vol-
ume (VAV) option using a variable frequency drive is avail-
able for applications requiring a constant supply duct
pressure. A differential pressure transducer is used to moni-
tor supply duct static pressure and return a speed reference
signal to the VFD to control the output of the indoor blower
motor.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
All compressors include scroll compressors and internal pres-
sure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot
gas bypass option, consisting of an adjustable compressor
discharge bypass valve, is available for low cooling load
applications.
All models are CSA approved.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
S implicity® Controls - S implicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
Gas Heat Operation - All gas heat units are built with
two heating sections for two equal stages of capacity
control. Each section includes a durable heat exchanger
4
Unitary Products Group
262259-YTG-B-0107
ELECTRIC HEATER LOCATION
(OPTIONAL ELECTRIC/ELECTRIC UNITS)
HIGH EFFICIENCY COMPRESSORS
WITH CRANKCASE HEATERS
20 GAUGE ALUMINIZED STEEL
TUBULAR HEAT EXCHANGERS
LONG LASTING
POWDER PAINT FINISH
COPPER TUBE/ALUMINUM FIN
CONDENSER COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP
ECONOMIZER HOOD
ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL WIRING ENTRY
KNOCKOUT FOR
SIDE POWER WIRING ENTRY SIDE
2" DISPOSABLE
FILTERS
TERMINAL BLOCK
(For Single Point Power Supply
with Electric Heat)
ELECTRIC\ELECTRIC UNITS
OUTDOOR AIR OPENING
FOR SLIDE-IN/PLUG-IN
INTERNAL ECONOMIZER(OPTION)
BOTTOM POWER & CONTROL
WIRING ENTRY
KNOCKOUTS FOR SIDE
GAS SUPPLY ENTRY
SIDE AND BOTTOM
SUPPLY & RETURN AIR
DUCT OPENINGS(SIDE X SIDE)
HOLE FOR BOTTOM
GAS SUPPLY ENTRY
POWER VENTOR MOTOR
WITH POST PURGE CYCLE
1" NPTI
CONDENSATE DRAIN
GAS/ELECTRIC
UNIT SHOWN
BELT-DRIVE
BLOWER MOTOR
LOCATION OF VFD (Optional)
FULL PERIMETER 14 GUAGE BASE
RAILS WITH LIFTING HOLES
LOCATION OF VFD Bypass (Optional)
FIGURE 1 - UNIT CUTAWAY
with aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
POWER EXHAUST - Our single economizer options are
available with power exhaust. Whenever the outdoor air
intake dampers are opened for free cooling, the exhaust
fan will be energized to prevent the conditioned space
from being over-pressurized during economizer operation.
•
Electric Heat Operation - All electric heat models (fac-
tory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to pro-
vide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.
The power exhaust option can only be used on bot-
tom duct configurations.
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
•
BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as S implicity® INTELLI-Com-
fort™, Novar, Honeywell, Johnson, and CPC.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
Unitary Products Group
5
262259-YTG-B-0107
•
•
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
you may order the unit with a “non-powered” conve-
nience outlet that can be wired in the field.
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the speed of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
•
BAS - Building Automation System Controls (avail-
able on two-system cooling product only).
S implicity® INTELLI-Comfort™ CONTROL - The York®
S implicity® INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and oper-
ate the motor at full speed, or to power the drive (and not
the motor) for diagnostic purposes.
Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the cus-
tomer-installed BAS.
using CO sensors. It uses an inside CO sensor to per-
2
2
form Demand Ventilation. It can also use an Outside CO
2
sensor to perform Differential Demand Ventilation. It
uses a Patented Comfort Ventilation algorithm to provide
comfortable ventilation air temperature. The patented
economizer-loading algorithm will protect the equipment
when harsh operating conditions exist. Humidity in the
occupied space or return duct can be monitored and
controlled via humidity sensors and the on-board con-
nection for hot gas re-heat system. It uses the INTELLI-
Start™ algorithm to maximize energy savings by recov-
ering the building from the Unoccupied Setpoints to the
Occupied Setpoints just in time for the Occupied Time
Period to begin. The S implicity® INTELLI-Comfort™ bal-
ances space temperature, ventilation air temperature,
A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment
which may accommodate other vendor’s drives depend-
ing on their size. In order to utilize the unit’s mounting
bracket, the maximum recommended drive dimensions
are as follows:
For 5-hp motor applications........................ 10” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications ........ 13” H x 8” W x 8” D
If the customer-installed drive will not fit in the allotted
space, then it will have to be mounted within a NEMA-4
enclosure for outside installation or inside the building on
a perpendicular wall not subjected to excessive tempera-
ture, vibration, humidity, dust, corrosive gas, explosive
gas, etc.
CO and humidity for ultimate comfort.
2
S implicity® INTELLI-Comfort™ with ModLINC CON-
TROL - The York® S implicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
A terminal block located in the control box is provided for
field connection of the VFD controls.
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
HOT GAS BYPASS - To allow for low cooling load oper-
ation, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evapo-
rator pressure. HGBP is standard on all units with VAV
and optional with CV units.
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system con-
troller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air prov-
ing switch.
•
•
FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated fil-
ters are offered as a factory installed option.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or
6
Unitary Products Group
262259-YTG-B-0107
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
“off” times due to out side air infiltration. these smoke
detectors have an operational limit of 32°F to 131°F.
smoke detectors installed in areas that could be out
side those limitations will have to be moved to prevent
having false alarms.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
•
•
•
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•
•
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
STAINLESS STEEL DRAIN PAN- An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
•
HIGH SPEED DRIVE - Includes a belt and blower pulley
upgrade to enhance blower performance.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
•
SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
•
HINGED FILTER DOOR/”TOOLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
NOTE:Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
•
HIGH SPEED DRIVE - A smaller blower pulley and a
shorter belt increase the speed of the supply air blower
for applications with a higher CFM and/or static pressure
requirements.
Unitary Products Group
7
262259-YTG-B-0107
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
•
WOOD SKID - Allows unit to be handled with 90” forks.
CO SENSOR - Senses CO levels and automatically
2
2
overrides the economizer when levels rise above the
present limits.
•
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
8
Unitary Products Group
262259-YTG-B-0107
1
TABLE 1: SOUND POWER RATING
-12
SOUND POWER (db 10
Watts)
ESP
IWG
BLOWER
UNIT
SIZE
Octave Band Centerline Frequency (Hz)
dB(A)
@
10Ft.2
CFM
SWL
dB(A)
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
180
240
300
6,000
8,000
1.00
1.00
1.30
1,080
1,120
1160
4.60
6.65
12.5
99
99
89
92
98
82
85
91
84
87
93
77
80
86
72
75
81
67
70
76
89
92
98
56
102
108
102
108
59
10,000
65
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
1
TABLE 3: GAS HEAT RATIINGS
TABLE 2: CAPACITY RATINGS - (ARI 360)
MODEL
MBH INPUT
MBH OUTPUT
EER2
IPLV3
MODEL
MBH
300
400
300
400
300
400
240
320
240
320
240
320
DM180N/S24
DM180N/S32
COOLING ONLY
DM180C/E00
DM240C/E00
DM300C/E00
176
234
272
8.7
8.6
8.5
9.2
8.05
9.2
DM240N/S24
DM240N/S32
DM300N/S24
DM300N/S32
COOLING WITH GAS HEAT
DM180N/S
176
232
272
8.5
8.5
8.5
9.0
8.05
9.0
DM240N/S
NOTE: All gas units are two-stage heating.
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.
DM300N/S
COOLING WITH ELECTRIC HEAT
DM180E18
DM180E36
DM180E54
DM180E72
DM240E18
DM240E36
DM240E54
DM240E72
DM300E18
DM300E36
DM300E54
DM300E72
176
176
174
174
234
234
232
232
272
272
270
270
8.7
8.6
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
8.5
9.2
9.1
8.7
8.7
8.05
8.05
8.05
8.05
9.1
For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.
9.1
If there are VAV boxes present in the duct sys-
tem, the boxes must be driven to the full-open
position using a customer-supplied power
source to assure adequate airflow across elec-
tric heating elements or gas heat exchanger
tubes.
9.0
9.0
1. Certified in accordance with the Unitary Large Equip-
ment certification program which is based on ARI Stan-
dard 340/360.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated Part Load Value.
Unitary Products Group
9
262259-YTG-B-0107
TABLE 4: DM 180 COOLING CAPACITIES (15 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
223.2
206.6
190.0
171.6
171.6
232.6
215.3
198.0
178.8
178.8
242.0
224.0
206.0
186.0
186.0
230.0
211.5
191.0
191.0
236.0
217.0
195.9
195.9
16.6
15.9
15.2
14.8
14.7
16.8
16.1
15.4
15.0
14.9
17.0
16.3
15.6
15.2
15.1
16.5
15.8
15.4
15.3
16.7
16.0
15.6
15.5
116.8 95.5
74.1
-
-
-
-
-
-
212.0
195.5
179.0
161.6
161.6
221.5
204.3
187.0
168.8
168.8
231.0
213.0
195.0
176.0
176.0
217.9
199.5
180.1
180.1
222.8
204.0
184.1
184.1
17.5
16.8
16.1
15.6
15.5
17.7
17.0
16.3
15.8
15.7
17.9
17.2
16.5
16.0
15.9
17.4
16.7
16.2
16.1
17.6
16.9
16.4
16.3
110.9 89.5
68.2
-
-
-
-
-
-
143.3 121.9 100.5 79.2
137.8 116.5 95.1 73.7
4500
5250
6000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
169.8 148.4 127.0 105.6 84.2
164.8 143.4 122.0 100.6 79.2
171.6 171.6 152.5 131.1 109.8 88.4
171.6 171.6 158.4 137.0 115.7 94.3
161.6 161.6 144.7 123.3 101.9 80.6
161.6 161.6 148.1 126.7 105.3 83.9
131.7 105.8 80.5
-
-
-
-
-
-
129.3 99.8
74.6
-
-
-
-
-
-
159.8 134.5 109.3 84.0
154.6 129.3 104.0 78.8
187.9 163.3 138.0 112.7 87.5
179.9 158.8 133.5 108.2 83.0
178.8 178.8 165.8 140.5 115.2 89.9
178.8 178.8 172.2 146.9 121.7 96.4
168.8 168.8 158.4 133.1 107.8 82.5
168.8 168.8 162.0 136.8 111.5 86.2
146.6 116.2 87.0
-
-
-
-
-
-
147.6 110.2 81.0
-
-
-
-
-
-
176.3 147.2 118.0 88.8
171.3 142.2 113.0 83.8
206.0 178.2 149.0 119.8 90.7
195.0 174.2 145.0 115.8 86.7
186.0 186.0 179.0 149.8 120.7 91.5
186.0 186.0 186.0 156.8 127.7 98.5
176.0 176.0 172.0 142.8 113.7 84.5
176.0 176.0 176.0 146.8 117.7 88.5
195.9 162.7 129.5 96.2
-
-
-
189.6 156.3 123.1 89.9
-
-
-
211.5 197.6 163.5 130.3 97.1
199.5 189.1 158.0 124.8 91.6
6750
7500
191.0 191.0 187.5 154.3 121.0 87.8
191.0 191.0 191.0 157.8 124.5 91.3
180.1 180.1 178.1 144.9 111.6 78.4
180.1 180.1 180.1 146.9 113.6 80.4
215.4 178.2 140.9 103.6
-
-
-
207.8 170.5 133.3 96.0
-
-
-
217.0 217.0 178.0 140.7 103.5
204.0 204.0 171.0 133.7 96.5
195.9 195.9 195.9 158.7 121.4 84.2
195.9 195.9 195.9 158.7 121.4 84.2
184.1 184.1 184.1 146.9 109.6 72.3
184.1 184.1 184.1 146.9 109.6 72.3
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
200.9
184.4
168.0
151.6
151.6
210.4
193.2
176.0
158.8
158.8
220.0
202.0
184.0
166.0
166.0
205.8
187.5
169.2
169.2
209.7
191.0
172.3
172.3
18.4
17.7
17.0
16.4
16.3
18.6
17.9
17.2
16.6
16.5
18.8
18.1
17.4
16.8
16.7
18.3
17.6
17.0
16.9
18.5
17.8
17.2
17.1
105.0 83.6
62.2
-
-
-
-
188.8
173.2
157.5
143.7
143.7
196.9
180.6
164.3
149.9
149.9
205.0
188.0
171.0
156.0
156.0
192.1
174.8
159.4
159.4
196.2
178.5
162.9
162.9
19.4
18.6
17.8
17.3
17.3
19.6
18.8
18.0
17.4
17.4
19.8
19.0
18.2
17.6
17.6
19.2
18.4
17.8
17.8
19.4
18.6
18.0
18.0
101.7 80.3
58.9
-
-
-
-
132.4 111.0 89.6
68.2
-
128.2 106.8 85.5 64.1
153.4 133.4 112.0 90.6
-
4500
5250
6000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
159.8 138.4 117.0 95.6
74.2
-
69.2
-
151.6 151.6 136.9 115.5 94.1
151.6 151.6 137.7 116.4 95.0
72.8
143.7 143.7 129.0 107.6 86.2
143.7 143.7 129.4 108.0 86.7
64.9
73.6
65.3
126.8 93.9
68.6
-
-
-
-
-
-
126.7 90.3
65.0
-
-
-
-
149.4 124.1 98.8
73.5
144.8 119.5 94.2 69.0
162.2 148.7 123.5 98.2
-
171.9 154.3 129.0 103.7 78.5
73.0
-
158.8 158.8 151.0 125.7 100.4 75.1
158.8 158.8 151.9 126.6 101.3 76.1
149.9 149.9 142.3 117.0 91.7
149.9 149.9 142.7 117.4 92.2
66.4
66.9
148.6 104.2 75.0
-
-
-
-
-
-
151.6 100.2 71.0
-
-
-
-
166.3 137.2 108.0 78.8
161.3 132.2 103.0 73.8
-
-
184.0 170.2 141.0 111.8 82.7
171.0 164.1 135.0 105.8 76.7
156.0 156.0 155.5 126.3 97.2
156.0 156.0 156.0 126.8 97.7
166.0 166.0 165.0 135.8 106.7 77.5
166.0 166.0 166.0 136.8 107.7 78.5
68.0
68.5
-
183.2 150.0 116.8 83.6
-
-
-
176.4 145.4 112.2 78.9
-
187.5 180.6 152.5 119.3 86.1
174.8 171.3 147.0 113.8 80.6
159.4 159.4 159.2 126.0 92.8
159.4 159.4 159.4 126.2 93.0
-
6750
7500
169.2 169.2 168.7 135.4 102.2 69.0
169.2 169.2 169.2 135.9 102.7 69.5
59.5
59.8
-
200.1 162.9 125.6 88.4
-
-
191.5 158.6 121.3 84.0
-
191.0 191.0 164.0 126.7 89.5
172.3 172.3 172.3 135.1 97.8
172.3 172.3 172.3 135.1 97.8
-
178.5 178.5 159.0 121.7 84.5
162.9 162.9 162.9 125.6 88.3
162.9 162.9 162.9 125.6 88.3
-
60.5
60.5
51.1
51.1
10
Unitary Products Group
262259-YTG-B-0107
TABLE 4: DM 180 COOLING CAPACITIES (15 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
115°F
SENSIBLE CAPACITY, MBH
COIL
TOTAL POWER
ENTERING DRY BULB, °F
1
2
CAP.
INPUT
KW
WB
°F
MBH
CFM
90
85
80
75
70
65
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
176.8
161.9
147.0
135.8
135.8
183.4
167.9
152.5
140.9
140.9
190.0
174.0
158.0
146.0
146.0
178.4
162.0
149.7
149.7
182.8
166.0
153.4
153.4
20.4
19.5
18.6
18.1
18.2
20.5
19.6
18.8
18.3
18.4
20.7
19.8
18.9
18.4
18.5
20.1
19.2
18.6
18.7
20.3
19.4
18.9
19.0
98.3 77.0
55.6
-
-
-
-
124.1 102.7 81.3 59.9
147.0 128.4 107.0 85.6
135.8 135.8 121.1 99.7
135.8 135.8 121.1 99.7
-
4500
64.2
78.3
78.3
-
-
56.9
56.9
126.5 86.6
61.3
-
-
140.2 114.9 89.6 64.4
152.5 143.2 118.0 92.7
-
-
5250
6000
67.5
-
140.9 140.9 133.6 108.3 83.0
140.9 140.9 133.6 108.3 83.0
57.7
57.7
154.6 96.3
67.0
-
-
-
-
156.3 127.2 98.0 68.8
158.0 158.0 129.0 99.8
-
-
70.7
146.0 146.0 146.0 116.8 87.7
146.0 146.0 146.0 116.8 87.7
58.5
58.5
-
169.6 140.7 107.5 74.3
-
162.0 162.0 141.5 108.3 75.1
149.7 149.7 149.7 116.5 83.3
149.7 149.7 149.7 116.5 83.3
-
6750
7500
50.1
50.1
-
182.8 154.3 117.0 79.7
-
166.0 166.0 154.0 116.7 79.5
153.4 153.4 153.4 116.1 78.9
153.4 153.4 153.4 116.1 78.9
-
41.6
41.6
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 1.5 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Unitary Products Group
11
262259-YTG-B-0107
TABLE 5: DM 240 COOLING CAPACITIES (20 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
322.5
291.2
260.0
225.8
225.8
331.2
299.1
267.0
231.9
231.9
340.0
307.0
274.0
238.0
238.0
313.5
279.8
243.0
243.0
320.0
285.5
248.0
248.0
22.3
21.6
20.9
20.3
19.9
22.3
21.6
20.9
20.3
19.9
22.3
21.6
20.9
20.3
19.9
21.9
21.2
20.6
20.2
22.2
21.5
20.9
20.5
159.6 131.1 102.6
-
-
-
-
-
-
298.6
272.3
246.0
213.1
213.1
308.3
281.1
254.0
220.1
220.1
318.0
290.0
262.0
227.0
227.0
297.7
269.0
233.1
233.1
305.5
276.0
239.1
239.1
23.9
22.9
21.9
21.3
20.8
24.0
23.0
22.0
21.4
20.9
24.1
23.1
22.1
21.5
21.0
23.5
22.5
21.8
21.3
23.8
22.8
22.2
21.7
154.3 125.8 97.3
-
-
-
-
-
-
194.3 165.8 137.3 108.8
188.7 160.1 131.6 103.1
6000
7000
8000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
229.0 200.5 172.0 143.5 115.0
223.0 194.5 166.0 137.5 109.0
225.8 225.8 192.7 164.2 135.7 107.2
225.8 225.8 194.2 165.7 137.2 108.7
213.1 213.1 185.3 156.8 128.3 99.7
213.1 213.1 190.3 161.8 133.3 104.8
186.6 147.0 113.3
-
-
-
-
-
-
180.9 140.3 106.6
-
-
-
-
-
-
219.0 185.3 151.6 118.0
211.7 178.0 144.3 110.6
251.5 223.7 190.0 156.3 122.6
242.5 215.7 182.0 148.3 114.6
231.9 231.9 212.8 179.2 145.5 111.8
231.9 231.9 214.6 180.9 147.2 113.5
220.1 220.1 203.1 169.4 135.7 102.1
220.1 220.1 208.7 175.0 141.3 107.6
213.5 162.9 124.0
-
-
-
-
-
-
207.5 154.9 116.0
-
-
-
-
-
-
243.8 204.9 166.0 127.1
234.8 195.9 157.0 118.1
274.0 246.9 208.0 169.1 130.2
262.0 236.9 198.0 159.1 120.2
238.0 238.0 233.0 194.1 155.2 116.4
238.0 238.0 235.0 196.1 157.2 118.4
227.0 227.0 221.0 182.1 143.2 104.4
227.0 227.0 227.0 188.1 149.2 110.4
273.3 229.1 184.8 140.5
-
-
-
264.6 220.3 176.0 131.8
-
-
-
279.8 266.2 231.5 187.2 142.9
269.0 256.4 222.0 177.7 133.4
9000
243.0 243.0 240.5 196.2 151.9 107.7
243.0 243.0 241.5 197.2 152.9 108.7
233.1 233.1 230.1 185.8 141.5 97.2
233.1 233.1 233.1 188.8 144.5 100.2
302.9 253.2 203.5 153.9
-
-
-
294.4 244.7 195.1 145.4
-
-
-
285.5 285.5 255.0 205.3 155.6
276.0 276.0 246.0 196.3 146.6
10000
248.0 248.0 248.0 198.3 148.6 99.0
248.0 248.0 248.0 198.3 148.6 99.0
239.1 239.1 239.1 189.4 139.8 90.1
239.1 239.1 239.1 189.4 139.8 90.1
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
274.7
253.3
232.0
200.4
200.4
285.3
263.2
241.0
208.2
208.2
296.0
273.0
250.0
216.0
216.0
282.0
258.3
223.1
223.1
291.0
266.5
230.3
230.3
25.5
24.2
22.9
22.3
21.7
25.7
24.4
23.1
22.5
21.9
25.9
24.6
23.3
22.7
22.1
25.0
23.7
23.1
22.5
25.4
24.1
23.5
22.9
148.9 120.4 91.9
-
-
-
-
-
-
255.9
236.4
217.0
192.0
192.0
266.2
246.0
225.8
199.8
199.8
276.5
255.5
234.5
207.5
207.5
261.2
239.8
212.1
212.1
267.0
245.0
216.7
216.7
27.0
25.6
24.2
23.5
23.0
27.1
25.7
24.3
23.6
23.1
27.3
25.9
24.5
23.8
23.2
26.2
24.8
24.1
23.6
26.6
25.2
24.5
23.9
142.4 113.9 85.4
-
-
-
-
-
-
183.0 154.5 126.0 97.4
177.2 148.7 120.2 91.7
6000
7000
8000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
217.0 188.5 160.0 131.5 103.0
209.5 183.5 155.0 126.5 98.0
200.4 200.4 177.9 149.4 120.8 92.3
200.4 200.4 186.4 157.9 129.4 100.8
192.0 192.0 172.2 143.7 115.1 86.6
192.0 192.0 179.5 151.0 122.4 93.9
175.2 133.7 100.0
-
-
-
-
-
-
171.7 126.2 92.5
-
-
-
-
-
-
204.4 170.7 137.0 103.3
197.5 163.8 130.1 96.4
233.5 207.7 174.0 140.3 106.6
222.0 201.4 167.8 134.1 100.4
208.2 208.2 193.4 159.7 126.0 92.3
208.2 208.2 202.7 169.0 135.3 101.6
199.8 199.8 186.3 152.6 118.9 85.2
199.8 199.8 194.2 160.5 126.8 93.1
201.5 146.9 108.0
-
-
-
-
-
-
201.0 138.4 99.5
-
-
-
-
-
-
225.8 186.9 148.0 109.1
217.8 178.9 140.0 101.1
250.0 226.9 188.0 149.1 110.2
234.5 219.4 180.5 141.6 102.7
216.0 216.0 209.0 170.1 131.2 92.4
216.0 216.0 219.0 180.1 141.2 102.4
207.5 207.5 200.5 161.6 122.7 83.9
207.5 207.5 209.0 170.1 131.2 92.4
255.8 211.6 167.3 123.0
-
-
-
241.1 201.2 156.9 112.6
-
-
-
258.3 246.7 212.5 168.2 123.9
239.8 232.2 202.3 158.0 113.7
9000
223.1 223.1 219.6 175.3 131.1 86.8
223.1 223.1 224.6 180.3 136.1 91.8
212.1 212.1 208.6 164.3 120.0 75.7
212.1 212.1 212.8 168.6 124.3 80.0
285.9 236.3 186.6 136.9
-
-
-
264.4 223.5 173.8 124.1
-
-
-
266.5 266.5 237.0 187.3 137.6
245.0 245.0 224.0 174.3 124.6
10000
230.3 230.3 230.3 180.6 130.9 81.2
230.3 230.3 230.3 180.6 130.9 81.2
216.7 216.7 216.7 167.0 117.3 67.6
216.7 216.7 216.7 167.0 117.3 67.6
12
Unitary Products Group
262259-YTG-B-0107
TABLE 5: DM 240 COOLING CAPACITIES (20 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
115°F
SENSIBLE CAPACITY, MBH
COIL
TOTAL POWER
ENTERING DRY BULB, °F
1
2
CAP.
INPUT
KW
WB
°F
MBH
CFM
90
85
80
75
70
65
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
237.1
219.5
202.0
183.6
183.6
247.0
228.8
210.5
191.3
191.3
257.0
238.0
219.0
199.0
199.0
240.4
221.3
201.0
201.0
242.9
223.5
203.1
203.1
28.5
27.0
25.5
24.7
24.2
28.5
27.0
25.6
24.8
24.3
28.6
27.1
25.6
24.8
24.3
27.5
26.0
25.1
24.6
27.8
26.3
25.5
25.0
135.9 107.4 78.9
-
-
-
-
-
-
171.5 143.0 114.5 85.9
6000
202.0 178.5 150.0 121.5 93.0
183.6 183.6 166.5 138.0 109.4 80.9
183.6 183.6 172.5 144.0 115.5 87.0
168.2 118.6 85.0
-
-
-
-
-
-
190.6 156.9 123.2 89.5
7000
8000
210.5 195.2 161.5 127.8 94.1
191.3 191.3 179.2 145.5 111.8 78.1
191.3 191.3 185.8 152.1 118.4 84.7
200.5 129.9 91.0
-
-
-
-
-
-
209.8 170.9 132.0 93.1
219.0 211.9 173.0 134.1 95.2
199.0 199.0 192.0 153.1 114.2 75.4
199.0 199.0 199.0 160.1 121.2 82.4
226.3 190.8 146.5 102.2
-
-
-
221.3 217.7 192.0 147.7 103.4
9000
201.0 201.0 197.5 153.3 109.0 64.7
201.0 201.0 201.0 156.8 112.5 68.2
242.9 210.7 161.0 111.3
-
-
-
223.5 223.5 211.0 161.3 111.6
10000
203.1 203.1 203.1 153.4 103.7 54.0
203.1 203.1 203.1 153.4 103.7 54.0
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Unitary Products Group
13
262259-YTG-B-0107
TABLE 6: DM 300 COOLING CAPACITIES (25 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
364.9
341.5
318.1
290.0
287.2
367.6
344.0
320.4
292.1
289.2
370.2
346.5
322.7
294.1
291.3
348.9
325.1
296.2
293.3
351.4
327.4
298.2
295.3
24.2
23.7
23.2
23.1
22.7
24.2
23.7
23.2
23.1
22.7
24.2
23.7
23.2
23.1
22.7
23.5
23.0
22.9
22.6
23.4
22.9
22.8
22.4
197.4 161.8 126.1
-
-
-
-
-
-
349.9
326.3
302.8
279.5
276.6
355.6
331.7
307.8
284.1
281.1
361.3
337.0
312.7
288.6
285.6
342.3
317.6
293.2
290.1
347.6
322.6
297.7
294.6
26.9
26.4
25.9
25.4
25.4
27.0
26.5
25.9
25.4
25.4
27.1
26.5
26.0
25.5
25.5
26.6
26.0
25.5
25.5
26.6
26.1
25.6
25.6
188.9 153.3 117.6
-
-
-
-
-
-
237.8 202.2 166.5 130.9
230.5 194.8 159.2 123.6
7500
8750
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
278.2 242.5 206.9 171.2 135.6
272.1 236.4 200.8 165.1 129.5
290.0 290.0 259.7 224.1 188.4 152.8
287.2 287.2 259.1 223.5 187.8 152.2
279.5 279.5 247.5 211.8 176.2 140.5
276.6 276.6 251.1 215.5 179.8 144.2
214.3 173.3 131.2
-
-
-
-
-
-
209.9 165.4 123.3
-
-
-
-
-
-
257.4 215.3 173.2 131.0
251.1 209.0 166.9 124.8
300.5 257.2 215.1 173.0 130.8
292.4 252.6 210.5 168.3 126.2
292.1 292.1 270.1 228.0 185.8 143.7
289.2 289.2 269.4 227.3 185.1 143.0
284.1 284.1 259.4 217.3 175.1 133.0
281.1 281.1 263.2 221.1 179.0 136.9
231.3 184.9 136.3
-
-
-
-
-
-
230.8 177.6 129.0
-
-
-
-
-
-
277.0 228.4 179.8 131.2
271.8 223.2 174.6 126.0
10000
322.7 271.9 223.3 174.7 126.1
312.7 268.7 220.1 171.5 122.9
294.1 294.1 280.4 231.8 183.2 134.6
291.3 291.3 279.7 231.1 182.5 133.9
288.6 288.6 271.3 222.7 174.1 125.5
285.6 285.6 275.3 226.7 178.1 129.5
301.9 246.6 191.2 135.9
-
-
-
293.9 238.6 183.2 127.9
-
-
-
325.1 292.9 237.6 182.2 126.9
317.6 286.4 231.0 175.7 120.3
11250
12500
296.2 296.2 297.8 242.5 187.1 131.8
293.3 293.3 289.6 234.3 178.9 123.6
293.2 293.2 284.5 229.2 173.8 118.5
290.1 290.1 285.0 229.6 174.3 118.9
326.9 264.8 202.7 140.6
-
-
-
316.0 253.9 191.8 129.7
-
-
-
327.4 314.0 251.9 189.8 127.7
322.6 304.0 241.9 179.8 117.7
298.2 298.2 315.2 253.1 191.0 128.9
295.3 295.3 299.6 237.5 175.4 113.3
297.7 297.7 297.7 235.6 173.5 111.4
294.6 294.6 294.6 232.5 170.4 108.3
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
334.8
311.2
287.6
269.0
266.0
343.6
319.3
295.1
276.1
273.0
352.4
327.5
302.7
283.1
280.0
335.7
310.2
290.2
286.9
343.9
317.8
297.3
293.9
29.7
29.1
28.5
27.7
28.0
29.8
29.2
28.7
27.8
28.1
29.9
29.3
28.8
27.9
28.3
29.6
29.0
28.1
28.5
29.9
29.3
28.4
28.8
180.4 144.8 109.1
-
-
-
-
-
-
316.8
294.4
272.1
253.0
250.3
323.0
300.2
277.4
258.0
255.3
329.2
306.0
282.8
263.0
260.2
311.8
288.2
267.9
265.1
317.6
293.5
272.9
270.1
32.8
32.3
31.7
30.8
31.3
33.0
32.4
31.8
30.9
31.4
33.1
32.5
31.9
31.1
31.5
32.8
32.2
31.3
31.7
33.0
32.4
31.5
32.0
162.5 126.9 91.3
-
-
-
-
-
-
223.2 187.5 151.9 116.3
211.3 175.6 140.0 104.3
7500
8750
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
266.0 230.3 194.7 159.0 123.4
260.0 224.3 188.7 153.1 117.4
269.0 269.0 235.2 199.6 163.9 128.3
266.0 266.0 243.1 207.5 171.8 136.2
253.0 252.8 218.1 182.5 146.8 111.2
250.3 250.3 223.0 187.4 151.7 116.1
205.4 157.5 115.4
-
-
-
-
-
-
194.4 139.0 96.9
-
-
-
-
-
-
244.9 202.7 160.6 118.5
232.9 190.8 148.7 106.5
284.3 248.0 205.8 163.7 121.6
271.4 242.6 200.5 158.4 116.2
276.1 276.1 248.7 206.6 164.5 122.3
273.0 273.0 257.1 214.9 172.8 130.7
258.0 257.9 231.7 189.5 147.4 105.3
255.3 255.3 236.8 194.7 152.6 110.5
230.4 170.2 121.6
-
-
-
-
-
-
226.3 151.1 102.5
-
-
-
-
-
-
266.5 217.9 169.3 120.7
254.6 206.0 157.4 108.8
10000
302.7 265.6 217.0 168.4 119.8
282.8 260.8 212.2 163.6 115.0
283.1 283.1 262.2 213.6 165.0 116.4
280.0 280.0 271.0 222.4 173.8 125.2
263.0 263.0 245.2 196.6 148.0 99.4
260.2 260.2 250.7 202.1 153.5 104.9
285.9 230.5 175.2 119.8
-
-
-
272.1 216.8 161.4 106.1
-
-
-
310.2 279.8 224.5 169.1 113.8
288.2 271.3 217.6 162.3 106.9
11250
12500
290.2 290.2 271.2 215.9 160.5 105.2
286.9 286.9 280.4 225.0 169.7 114.3
267.9 267.9 251.5 196.2 140.8 85.5
265.1 265.1 257.2 201.8 146.5 91.1
305.2 243.1 181.0 118.9
-
-
-
289.7 227.6 165.5 103.4
-
-
-
317.8 294.1 232.0 169.9 107.8
293.5 281.7 223.0 160.9 98.8
297.3 297.3 280.3 218.2 156.1 94.0
293.9 293.9 289.7 227.6 165.5 103.4
272.9 272.9 257.9 195.8 133.7 71.6
270.1 270.1 263.7 201.6 139.5 77.4
14
Unitary Products Group
262259-YTG-B-0107
TABLE 6: DM 300 COOLING CAPACITIES (25 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
115°F
SENSIBLE CAPACITY, MBH
COIL
TOTAL POWER
ENTERING DRY BULB, °F
1
2
CAP.
INPUT
KW
WB
°F
MBH
CFM
90
85
80
75
70
65
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
298.7
277.7
256.6
236.9
234.7
302.4
281.1
259.8
239.9
237.6
306.1
284.5
263.0
242.8
240.5
287.9
266.1
245.7
243.3
291.3
269.3
248.6
246.2
36.0
35.4
34.8
34.0
34.5
36.1
35.5
34.9
34.1
34.6
36.3
35.7
35.1
34.2
34.8
35.9
35.3
34.5
35.0
36.1
35.5
34.7
35.2
144.7 109.0 73.4
-
-
-
-
-
-
199.3 163.7 128.1 92.4
7500
254.0 218.4 182.7 147.1 111.5
236.9 236.6 201.0 165.4 129.7 94.1
234.7 234.7 202.9 167.2 131.6 96.0
183.4 120.5 78.3
-
-
-
-
-
-
221.0 178.8 136.7 94.6
8750
258.5 237.2 195.1 153.0 110.9
239.9 239.7 214.6 172.5 130.4 88.2
237.6 237.6 216.6 174.5 132.4 90.3
222.2 131.9 83.3
-
-
-
-
-
-
242.6 194.0 145.4 96.8
10000
263.0 256.1 207.5 158.9 110.3
242.8 242.8 228.2 179.6 131.0 82.4
240.5 240.5 230.4 181.8 133.2 84.6
258.4 203.1 147.7 92.4
-
-
-
266.1 262.7 210.8 155.4 100.1
11250
12500
245.7 245.7 231.8 176.5 121.1 65.8
243.3 243.3 234.0 178.7 123.3 68.0
274.2 212.1 150.0 87.9
-
-
-
269.3 269.3 214.1 152.0 89.9
248.6 248.6 235.5 173.4 111.3 49.2
246.2 246.2 237.7 175.6 113.5 51.4
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
15
262259-YTG-B-0107
order to use the indoor blower tables for high altitude applica-
tions, certain corrections are necessary.
CFM, STATIC PRESSURE, AND POWER - ALTI-
TUDE AND TEMPERATURE CORRECTIONS
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In
TABLE 7: ALTITUDE CORRECTION FACTORS
ALTITUDE (FEET)
AIR TEMP
0
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
40
50
1.060
1.039
1.019
1.000
0.982
0.964
0.946
60
70
80
90
100
The examples below will assist in determining the airflow per-
formance of the product at altitude.
blower tables to select the blower speed and the BHP
requirement.
Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower performance
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature informa-
tion is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Solution: At an elevation of 5,000 ft., the indoor blower will
still deliver 6,000 CFM if the rpm is unchanged. However,
BHP. Since no temperature data is given, we will assume an
air temperature of 70°F. Table 7 shows the correction factor
to be 0.832.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to
BHP at 5,000 ft = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
16
Unitary Products Group
262259-YTG-B-0107
FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
Unitary Products Group
17
262259-YTG-B-0107
TABLE 8: SUPPLY AIR BLOWER PERFORMANCE (15 TON) -
COOLING ONLY 180 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
6000
BHP
BLOWER
SPEED,
(RPM)
4500
BHP
5250
BHP
6750
BHP
7200
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
850
870
6.0**
5.5
4.5
3.5
3.0
2.0
1.0
0.9
1.0
1.1
1.2
1.3
1.4
1.5
2.4
2.5
2.6
2.9
3.0
3.1
3.2
2.2
2.3
2.4
2.6
2.7
2.8
2.9
0.7
0.8
0.9
1.0
1.1
1.2
1.3
3.0
3.1
3.4
3.6
3.7
3.8
3.9
2.7
2.8
3.0
3.2
3.3
3.4
3.5
0.5
0.6
0.7
0.8
0.9
1.0
1.1
3.2
3.5
3.7
4.0
4.1
4.2
4.5
2.9
3.1
3.3
3.6
3.7
3.8
4.0
-
-
-
-
-
-
0.2
0.3
0.5
0.6
0.7
0.9
4.1
4.4
4.7
4.8.
5.0
5.2
3.7
3.9
4.2
4.3
4.5
4.7
-
-
-
915
0.2
0.4
0.5
0.6
0.7
4.5
4.9
5.1
5.4
5.7
4.0
4.4
4.6
4.8
5.1
965
980
1010
1040
208 VOLT AND HIGH SPEED DRIVE
965
980
6.0
5.5
4.5
3.5
3.0
2.0
1.0
1.2
1.3
1.5
1.6
1.7
1.9
2.1
2.9
3.0
3.2
3.4
3.5
3.7
3.9
2.6
2.7
2.9
3.0
3.1
3.3
3.5
1.0
1.1
1.3
1.4
1.5
1.7
2.0
3.6
3.7
3.9
4.0
4.2
4.5
4.7
3.2
3.3
3.5
3.6
3.8
4.0
4.2
0.8
0.9
1.1
1.2
1.3
1.5
1.8
4.0
4.1
4.5
4.7
4.9
5.1
5.5
3.6
3.7
4.0
4.2
4.4
4.6
4.9
0.5
0.6
0.8
1.0
1.2
-
4.7
4.8
5.1
5.5
5.7
-
4.2
4.3
4.6
4.9
5.1
-
0.4
5.0
4.4
0.5
5.1
4.6
1025
1065
1095
1130
1170
0.7
5.6
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
915
6.0**
5.0
4.0
3.5
2.0
1.0
1.0
1.1
1.2
1.3
1.5
1.6
2.4
2.6
2.9
3.0
3.2
3.3
2.2
2.4
2.6
2.7
2.9
3.0
0.8
0.9
1.0
1.1
1.3
1.4
3.1
3.3
3.6
3.7
3.9
4.0
2.8
3.0
3.2
3.3
3.5
3.6
0.6
0.7
0.8
0.9
1.1
1.2
3.5
3.7
4.0
4.1
4.5
4.7
3.1
3.3
3.6
3.7
4.0
4.2
0.2
0.3
0.5
0.6
0.9
1.0
4.1
4.4
4.7
4.8
5.3
5.5
3.7
3.9
4.2
4.3
4.7
4.9
-
-
-
0.2
0.4
0.5
0.7
-
4.5
5.0
5.1
5.7
-
4.0
4.4
4.6
5.1
-
965
980
1040
1065
230/460/575 VOLT AND HIGH SPEED DRIVE
980
6.0
4.5
4.0
3.5
2.5
1.5
1.0
1.3
1.5
1.6
1.7
1.9
2.1
2.2
2.9
3.2
3.4
3.5
3.7
3.9
4.0
2.6
2.9
3.0
3.1
3.3
3.5
3.6
1.1
1.3
1.4
1.5
1.7
2.0
2.1
3.7
3.9
4.0
4.2
4.5
4.7
4.8
3.3
3.5
3.6
3.8
4.0
4.2
4.3
0.9
1.1
1.2
1.3
1.5
1.8
2.0
4.1
4.5
4.7
4.9
5.1
5.5
5.7
3.7
4.0
4.2
4.4
4.6
4.9
5.1
0.6
0.9
1.0
1.2
-
4.8
5.3
5.5
5.7
-
4.3
4.7
4.9
5.1
-
0.5
5.1
4.6
1040
1065
1095
1130
1170
1190
0.7
5.7
5.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
18
Unitary Products Group
262259-YTG-B-0107
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
8000
BHP
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
9000
BHP
9400
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
1015
6.0**
5.0
4.0
3.0
2.0
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.1
3.2
4.1
4.6
5.3
5.9
1.8
2.7
3.4
3.9
4.5
5.0
0.1
0.5
0.9
1.1
1.4
1.7
2.3
3.5
4.5
5.1
5.8
6.5
2.0
2.9
3.8
4.3
4.9
5.5
-
-
-
-
-
-
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
3.8
4.9
5.5
6.3
7.0
3.2
4.1
4.6
5.3
5.9
-
-
-
0.1
0.4
0.7
1.0
5.1
5.9
6.9
7.7
4.3
5.0
5.8
6.5
-
-
-
-
-
-
0.2
0.6
7.3
8.2
6.1
6.9
208 VOLT AND HIGH SPEED DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.5
2.0
1.0
1.3
1.6
1.8
1.9
2.0
2.1
2.3
2.4
4.6
5.3
5.8
6.1
6.2
6.4
6.6
6.7
3.9
4.5
4.9
5.1
5.2
5.4
5.5
5.6
1.1
1.4
1.7
1.8
1.9
2.0
2.1
2.2
5.1
5.8
6.3
6.5
6.8
7.0
7.2
7.3
4.3
4.9
5.3
5.5
5.7
5.9
6.0
6.1
0.8
1.2
1.5
1.6
1.7
1.8
1.9
2.1
5.5
6.3
6.9
7.1
7.4
7.6
7.8
7.9
4.6
5.3
5.8
6.0
6.2
6.4
6.6
6.7
0.4
0.7
1.0
1.1
1.2
1.3
1.5
-
5.9
6.9
7.5
7.8
8.1
8.3
8.6
-
5.0
5.8
6.3
6.6
6.8
7.0
7.2
-
-
0.2
0.5
0.6
0.7
-
-
7.3
7.9
8.3
8.6
-
-
6.1
6.7
7.0
7.3
-
1010
1020
1035
1050
1075
1100
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.0
2.1
3.2
4.1
4.6
5.3
5.9
6.1
1.8
2.7
3.4
3.9
4.5
5.0
5.1
0.1
0.5
0.9
1.1
1.4
1.7
1.8
2.3
3.5
4.5
5.1
5.8
6.5
6.6
2.0
2.9
3.8
4.3
4.9
5.5
5.6
-
-
-
-
-
-
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
1.6
3.8
4.9
5.5
6.3
7.0
7.3
3.2
4.1
4.6
5.3
5.9
6.1
-
-
-
930
0.1
0.4
0.7
1.0
1.1
5.1
5.9
6.9
7.7
7.9
4.3
5.0
5.8
6.5
6.7
-
-
-
950
-
-
-
980
0.2
0.6
0.7
7.3
8.2
8.6
6.1
6.9
7.3
1015
1025
230/460/575 VOLT AND HIGH SPEED DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.0
1.5
1.0
1.3
1.6
1.9
2.0
2.1
2.3
2.4
2.5
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
3.9
4.5
5.0
5.2
5.4
5.5
5.6
5.7
1.1
1.4
1.7
1.9
2.0
2.1
2.2
2.3
5.1
5.8
6.5
6.8
7.0
7.2
7.3
7.4
4.3
4.9
5.5
5.7
5.9
6.0
6.1
6.2
0.8
1.2
1.5
1.7
1.8
1.9
2.1
2.2
5.5
6.3
7.0
7.4
7.6
7.8
7.9
8.1
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
0.4
0.7
1.0
1.2
1.3
1.5
-
5.9
6.9
7.7
8.1
8.3
8.6
-
5.0
5.8
6.5
6.8
7.0
7.2
-
-
0.2
0.6
0.7
-
-
7.3
8.2
8.6
-
-
6.1
6.9
7.3
-
1015
1035
1050
1080
1100
1120
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Unitary Products Group
19
262259-YTG-B-0107
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT
180 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
6000
BHP
BLOWER
SPEED,
(RPM)
4500
BHP
5250
BHP
6750
BHP
7200
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
850
870
6.0**
5.5
4.5
3.5
3.0
2.0
1.0
0.9
1.0
1.1
1.2
1.3
1.4
1.6
2.4
2.5
2.6
2.7
2.9
3.0
3.2
2.1
2.2
2.4
2.5
2.6
2.7
2.9
0.6
0.7
0.8
0.9
1.0
1.1
1.3
2.9
3.0
3.1
3.2
3.4
3.6
3.8
2.6
2.7
2.8
2.9
3.0
3.2
3.4
0.3
0.4
0.5
0.6
0.7
0.8
1.0
3.4
3.5
3.6
3.7
3.8
4.0
4.4
3.0
3.1
3.2
3.3
3.4
3.6
3.9
-
-
-
-
-
-
-
-
-
-
-
-
915
0.2
0.4
0.5
0.6
0.8
4.1
4.4
4.5
4.7
5.0
3.7
3.0
4.0
4.2
4.5
-
-
-
965
0.2
0.3
0.4
0.6
5.0
5.1
5.4
5.6
4.5
4.6
4.8
5.0
980
1010
1040
208 VOLT AND HIGH SPEED DRIVE
965
980
6.0
5.5
4.5
3.5
2.0
1.0
1.2
1.3
1.4
1.6
1.9
2.1
2.7
2.9
3.1
3.4
3.6
3.9
2.5
2.6
2.8
3.0
3.2
3.5
0.9
1.0
1.2
1.4
1.7
1.9
3.2
3.4
3.6
3.9
4.4
4.7
2.9
3.0
3.2
3.5
3.9
4.2
0.6
0.7
0.9
1.1
1.4
1.6
3.7
3.8
4.1
4.5
5.0
5.5
3.3
3.4
3.7
4.0
4.5
4.9
0.4
0.5
0.7
0.9
1.2
-
4.4
4.5
4.8
5.1
5.8
-
3.9
4.0
4.3
4.6
5.2
-
0.2
0.3
0.4
-
5.0
5.1
5.5
-
4.5
4.6
4.9
-
1025
1065
1125
1170
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
915
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.5
2.6
2.7
2.9
3.0
3.1
3.4
2.2
2.4
2.5
2.6
2.7
2.8
3.0
0.7
0.8
0.9
1.0
1.1
1.2
1.4
3.0
3.1
3.2
3.4
3.6
3.7
3.9
2.7
2.8
2.9
3.0
3.2
3.3
3.5
0.4
0.5
0.6
0.7
0.8
0.9
1.1
3.5
3.6
3.7
3.8
4.0
4.2
4.5
3.1
3.2
3.3
3.4
3.6
3.8
4.0
-
-
-
-
-
-
0.2
0.4
0.5
0.6
0.7
0.9
4.1
4.4
4.5
4.7
4.9
5.1
3.7
3.9
4.0
4.2
4.4
4.6
-
-
-
965
0.2
0.3
0.4
0.5
-
5.0
5.1
5.4
5.7
-
4.5
4.6
4.8
5.1
-
980
1015
1050
1065
230/460/575 VOLT AND HIGH SPEED DRIVE
980
6.0
4.5
4.0
2.5
1.5
1.0
1.3
1.6
1.7
1.9
2.1
2.2
2.9
3.2
3.4
3.6
3.9
4.0
2.6
2.9
3.0
3.2
3.5
3.6
1.0
1.3
1.4
1.7
1.8
1.9
3.4
3.8
3.9
4.4
4.7
4.8
3.0
3.4
3.5
3.9
4.2
4.3
0.7
1.0
1.1
1.4
1.6
1.7
3.8
4.4
4.5
5.0
5.5
5.6
3.4
3.9
4.0
4.5
4.9
5.0
0.5
0.8
0.9
1.2
-
4.5
5.0
5.1
5.8
-
4.0
4.5
4.6
5.2
-
0.3
5.1
4.6
1045
1065
1125
1170
1190
0.6
5.6
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
20
Unitary Products Group
262259-YTG-B-0107
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
8000
BHP
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
9000
BHP
9400
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
995
1015
6.0**
5.0
4.0
3.0
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
3.6
3.8
4.1
4.2
4.5
4.6
4.8
3.0
3.2
3.4
3.6
3.8
3.9
4.0
0.7
0.9
1.1
1.3
1.5
1.6
1.7
4.3
4.7
5.0
5.1
5.4
5.5
4.7
3.7
4.0
4.2
4.3
4.5
4.7
4.8
0.2
0.4
0.6
0.8
1.0
1.1
1.2
5.1
5.6
5.9
6.0
6.3
6.4
6.6
4.3
4.7
5.0
5.1
5.3
5.4
5.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1
0.2
0.4
0.5
0.7
6.7
6.9
7.2
7.5
7.8
5.7
5.8
6.1
6.3
6.6
-
-
-
0.1
0.2
-
8.5
8.6
-
7.1
7.3
-
208 VOLT AND HIGH SPEED DRIVE
950
980
6.0
5.0
4.5
3.5
2.5
2.0
1.0
1.7
1.9
2.1
2.3
2.5
2.6
2.9
4.2
4.5
4.5
4.9
5.1
5.3
5.6
3.6
3.8
3.9
4.1
4.3
4.4
4.7
1.3
1.5
1.6
1.8
2.0
2.1
2.3
5.1
5.4
5.5
5.8
6.1
6.3
6.8
4.3
4.5
4.7
4.9
5.1
5.3
5.7
0.8
1.0
1.1
1.3
1.4
1.5
1.8
6.0
6.3
6.4
6.7
7.1
7.3
7.9
5.1
5.3
5.4
5.7
6.0
6.2
6.6
0.2
0.4
0.5
0.7
0.9
1.0
-
6.9
7.2
7.5
8.0
8.4
8.6
-
5.8
6.1
6.3
6.7
7.0
7.2
-
-
-
-
0.1
8.5
7.1
995
0.2
8.6
7.3
1025
1050
1065
1100
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
2.3
3.6
3.8
4.1
4.2
4.5
4.6
4.8
4.9
3.0
3.2
3.4
3.6
3.8
3.9
4.0
4.1
0.7
0.9
1.1
1.3
1.5
1.6
1.7
1.8
4.3
4.7
5.0
5.1
5.4
5.5
5.7
5.8
3.7
4.0
4.2
4.3
4.5
4.7
4.8
4.9
0.2
0.4
0.6
0.8
1.0
1.1
1.2
1.3
5.1
5.6
5.9
6.0
6.3
6.4
6.6
6.7
4.3
4.7
5.0
5.1
5.3
5.4
5.6
5.7
-
-
-
-
-
-
-
-
-
-
-
-
930
0.1
0.2
0.4
0.5
0.6
0.7
6.7
6.9
7.2
7.5
7.8
8.0
5.7
5.8
6.1
6.3
6.6
6.7
-
-
-
-
-
-
950
965
0.1
0.2
-
8.5
8.6
-
7.1
7.3
-
995
1015
1025
-
-
-
230/460/575 VOLT AND HIGH SPEED DRIVE
950
980
6.0
5.0
4.5
4.0
3.5
3.0
2.5
1.5
1.0
1.7
1.9
2.1
2.2
2.3
2.5
2.6
2.9
3.1
4.2
4.5
4.6
4.8
4.9
5.1
5.3
5.6
5.8
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
1.3
1.5
1.6
1.7
1.8
2.0
2.1
2.3
2.5
5.1
5.4
5.5
5.7
5.8
6.1
6.3
6.8
7.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
4.7
5.9
0.8
1.0
1.1
1.2
1.3
1.4
1.5
1.8
1.9
6.0
6.3
6.4
6.6
6.7
7.1
7.3
7.9
8.3
5.1
5.3
5.4
5.6
5.7
6.0
6.2
6.6
6.9
0.2
0.4
0.5
0.6
0.7
0.9
1.0
-
6.9
7.2
7.5
7.8
8.0
8.4
8.6
-
5.8
6.1
6.3
6.6
6.7
7.0
7.2
-
-
-
-
0.1
8.5
7.1
995
0.2
8.6
7.3
1015
1025
1050
1065
1100
1120
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Unitary Products Group
21
262259-YTG-B-0107
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT
300 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
10000
BHP
BLOWER
SPEED,
(RPM)
7500
BHP
8750
BHP
11250
BHP
12500
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
975
6.0
5.0
4.0
3.0
2.0
1.0
0.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
5.0
0.7
0.9
1.1
1.3
1.6
1.8
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
6.3
6.7
7.0
7.3
7.6
8.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
-
-
-
-
-
-
0.2
0.4
0.6
0.8
1.0
9.7
10.2
10.6
11.1
11.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
-
-
-
-
-
0.2
13.5
11.0
208 VOLT AND HIGH SPEED DRIVE
1140
1180
1215
1255
1290
1330
1365
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.2
2.5
2.7
3.0
3.2
3.5
3.7
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
1.6
1.9
2.1
2.4
2.7
3.0
3.2
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
0.9
1.2
1.4
1.7
2.0
2.3
2.6
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.3
0.6
0.9
1.2
1.5
1.8
13.7
14.3
15.0
15.6
16.4
17.0
11.2
11.7
12.3
12.8
13.4
13.9
8.6
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.1
9.5
10.0
10.5
230/460/575 VOLT AND STANDARD DRIVE
975
6.0*
5.0
4.0
3.0
2.0
1.0
0.0
1.4
1.6
1.8
2.0
2.1
2.4
2.6
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
1.0
1.2
1.4
1.6
1.8
2.0
2.2
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
6.3
6.7
7.0
7.3
7.6
8.0
0.5
0.7
0.9
1.1
1.3
1.6
1.8
8.8
9.2
7.2
7.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
0.1
0.3
0.6
0.8
1.0
1.3
10.9
11.4
11.9
12.4
13.0
13.5
8.9
-
-
9.7
9.4
-
-
-
10.2
10.6
11.1
11.6
9.8
-
-
-
10.2
10.6
11.0
0.2
0.4
0.7
14.3
14.9
15.5
11.7
12.2
12.7
230/460/575 VOLT AND HIGH SPEED DRIVE
1140
1180
1215
1255
1290
1330
1365
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.4
2.7
2.9
3.2
3.4
3.7
3.9
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
2.1
2.3
2.6
2.9
3.1
3.4
3.7
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
1.6
1.9
2.2
2.5
2.7
3.0
3.3
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
1.1
1.4
1.7
2.0
2.2
2.6
2.9
13.1
13.7
14.3
15.0
15.6
16.4
17.0
10.7
11.2
11.7
12.3
12.8
13.4
13.9
0.5
0.8
1.1
1.4
-
15.0
15.8
16.4
17.2
-
12.3
12.9
13.5
14.1
-
8.6
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.1
9.5
10.0
10.5
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
15 HP Motor is required.
22
Unitary Products Group
262259-YTG-B-0107
TABLE 13: BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
1
MOTOR
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
BLOWER
DRIVE RANGE
(RPM)
MODEL
SIZE
OUTSIDE PITCH
PITCH
LENGTH QTY.
(IN.)
EFF.
(%)
DESIG-
NATION
BORE DESIG-
(IN.) NATION
BORE DESIG-
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
(IN.) NATION
Standard 850/1065
BK90
8.75
7.75
11.75
10.75
11.3
8.4
1
BX81
BX68
BX83
BX81
BX81
82.8
69.8
84.8
82.8
82.8
84.0
1
1
1
1
1
1
2
High
15 TON
20 TON
25 TON
5
184 T
83
89
1VP56
1VP68
5.35
6.75
4.3-5.3
1-1/8
BK80
Speed 965/1190
Access
7.4
1
Standard 870/1025
BK120
11.4
10.4
11.1
9.5
1-3/16
1-3/16
1-7/16
2
2
High
7.5 213 T
5.5-6.5
5.5-6.5
1-3/8
Speed 950/1120
Access
BK110
Standard 950/1120 10 215 T 89.5
High
Speed 1140/1365 15 254 T
Access
1VP68
6.75
7.5
1-3/8 1B5V110
91
1VP75X
6.2-7.4 1-5/8 1B5V94
9.7
1-7/16 5VX840
1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because
they are located in the moving air, upstream of any heating device.
2. Do NOT close this pulley below 1 turn open.
1
TABLE 14: STATIC RESISTANCES
RESISTANCE, IWG
CFM
DESCRIPTION
15 TON
6000
0.1
20 TON
8000
0.1
25 TON
10000
0.1
4500
0.1
0.3
0.3
0.4
0.4
0.1
0.1
7200
0.1
0.4
0.5
0.5
0.5
0.1
0.3
6000
0.1
0.4
0.4
0.5
0.5
0.1
0.2
9400
0.1
0.5
0.5
0.6
0.6
0.2
0.5
7500
0.1
0.4
0.5
0.5
0.5
0.1
0.3
12500
0.1
WET INDOOR COIL
18 KW
36 KW
54 KW
72 KW
0.4
0.4
0.5
0.6
0.4
0.5
0.5
0.6
ELECTRIC HEAT OPTIONS
0.5
0.5
0.6
0.7
0.5
0.5
0.6
0.7
ECONOMIZER OPTION
0.1
0.1
0.2
0.3
HORIZONTAL DUCT CONNECTIONS2
0.2
0.3
0.5
0.6
1. Deduct these resistance values from the available external static pressures shown in the respective Blower Performance Table (See Note 2 for
exception.)
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures to the ESP values
on the respective unit’s blower performance table.
TABLE 15: POWER EXHAUST PERFORMANCE
STATIC RESISTANCE OF RETURN DUCTWORK, IWG
MOTOR
SPEED1
0.2
0.3
0.4
0.5
0.6
CFM
kW
CFM
kW
CFM
kW
CFM
kW
CFM
kW
HIGH2
MEDIUM
LOW
5250
4900
4400
0.83
0.77
0.72
4500
3900
3700
0.85
0.79
0.74
4200
3500
3000
0.88
0.82
0.78
3750
2900
-
0.93
0.85
-
3000
0.99
-
-
-
-
1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.
Unitary Products Group
23
262259-YTG-B-0107
TABLE 16: DM 180, 240 ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
100
100
125
175
200
100
100
150
175
225
50
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
0.0
-
-
85.4
85.4
13.5
27.0
40.6
54.1
0.0
1
2
2
2
-
37.5
75.1
112.6
150.1
-
43.3
86.6
129.9
173.2
-
208
230
460
575
208
230
460
575
19.2
19.2
9.6
124
124
62
4.5
4.3
2.2
1.7
4.5
4.3
2.2
1.7
14.0
14.0
7.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
111.2
158.4
167.7
85.0
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
85.0
125.8
147.4
190.7
42.6
180
(15)
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
21.7
43.3
65.0
86.6
-
17.3
34.6
52.0
69.3
-
37.5
75.1
112.6
150.1
-
42.6
62.9
73.7
50
70
90
95.4
33.7
33.7
110
40
40
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
7.7
50
5.3
49.9
58.6
75.9
50
70
90
110.3
110.3
118.2
165.4
174.7
109.9
109.9
132.8
154.4
197.7
55.1
125
125
125
175
200
125
125
150
175
225
60
13.5
27.0
40.6
54.1
0.0
1
2
2
2
-
19.2
19.2
9.6
124
124
62
19.6
19.6
9.8
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
43.3
86.6
129.9
173.2
-
21.7
43.3
65.0
86.6
-
240
(20)
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
55.1
60
66.4
77.2
98.6
70
90
110
50
50
44.5
44.5
53.6
18.0
36.0
54.0
72.0
1
2
2
2
17.3
34.6
52.0
69.3
7.7
50
8.2
60
62.2
79.5
70
90
NOTE 1: HACR Type per NEC.
24
Unitary Products Group
262259-YTG-B-0107
TABLE 17: DM 300 ELECTRICAL DATA STANDARD MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
150
150
150
200
200
150
150
150
175
225
80
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
129.3
129.3
129.3
175.9
185.2
126.9
126.9
140.8
162.4
205.7
63.5
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
43.3
86.6
129.9
173.2
-
208
230
460
575
41.0
41.0
20.5
17.3
255
255
145
102
4.5
4.3
2.2
1.7
28.0
26.0
13.0
10.0
0.0
0.0
0.0
0.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
21.7
43.3
65.0
86.6
-
17.3
34.6
52.0
69.3
63.5
70.4
81.2
80
80
90
102.9
52.3
52.3
110
60
60
18.0
36.0
54.0
72.0
1
2
2
2
55.8
64.5
81.8
60
70
90
NOTE 1: HACR Type per NEC.
TABLE 18: DM 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
175
175
175
200
225
175
175
175
200
250
90
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
139.9
139.9
141.9
189.1
198.4
139.5
139.5
156.5
178.2
221.5
69.8
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
208
230
460
575
41.0
41.0
20.5
17.3
255
255
145
102
4.5
4.3
2.2
1.7
38.6
38.6
19.3
15.4
0.0
0.0
0.0
0.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
43.3
86.6
129.9
173.2
-
21.7
43.3
65.0
86.6
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
69.8
90
78.3
89.1
110.7
57.7
57.7
90
100
125
70
70
70
18.0
36.0
54.0
72.0
1
2
2
2
17.3
34.6
52.0
69.3
62.6
71.2
88.5
80
100
NOTE 1: HACR Type per NEC.
Unitary Products Group
25
262259-YTG-B-0107
TABLE 19: DM 180, 240 ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
BRKR1
SIZE
ID
MIN.
CIRCUIT
AMPACITY
(AMPS)
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
(AMPS)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
0.0
-
-
95.4
95.4
110
110
125
175
200
110
110
150
175
225
50
13.5
27.0
40.6
54.1
0.0
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
1
2
2
2
-
37.5
75.1
112.6
150.1
-
43.3
86.6
129.9
173.2
-
208
230
460
575
208
230
460
575
19.2
19.2
9.6
124
124
62
4.5
4.3
2.2
1.7
4.5
4.3
2.2
1.7
14.0
14.0
7.0
10.0
10.0
5.0
123.7
170.9
180.2
95.0
95.0
138.3
159.9
203.2
47.6
180
(15)
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
13.5
27.0
40.6
54.1
0.0
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
21.7
43.3
65.0
86.6
-
17.3
34.6
52.0
69.3
-
37.5
75.1
112.6
150.1
-
47.6
69.1
80.0
50
70
90
101.6
37.7
37.7
110
45
45
7.7
50
5.3
4.0
54.9
63.6
80.9
60
70
90
120.3
120.3
130.7
177.9
187.2
119.9
119.9
145.3
166.9
210.2
60.1
125
125
150
200
200
125
125
150
175
225
70
19.2
19.2
9.6
124
124
62
19.6
19.6
9.8
10.0
10.0
5.0
18.0
36.0
54.0
72.0
0.0
18.0
36.0
54.0
72.0
0.0
1
2
2
2
-
1
2
2
2
-
43.3
86.6
129.9
173.2
-
21.7
43.3
65.0
86.6
-
240
(20)
60.1
70
72.6
83.5
105.1
48.5
48.5
80
90
110
50
50
18.0
36.0
54.0
72.0
1
2
2
2
17.3
34.6
52.0
69.3
7.7
50
8.2
4.0
58.6
60
67.2
84.5
70
90
NOTE 1: HACR Type per NEC.
26
Unitary Products Group
262259-YTG-B-0107
TABLE 20: DM 300 ELECTRICAL DATA STANDARD MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
175
175
175
200
200
175
175
175
175
225
80
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
139.3
139.3
141.2
188.4
197.7
136.9
136.9
153.3
174.9
218.2
68.5
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
43.3
86.6
129.9
173.2
-
208
230
460
575
41.0
41.0
20.5
17.3
255
255
145
102
4.5
4.3
2.2
1.7
28.0
26.0
13.0
10.0
10.0
10.0
5.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
21.7
43.3
65.0
86.6
-
17.3
34.6
52.0
69.3
68.5
76.6
87.5
80
80
90
109.1
56.3
56.3
110
70
70
18.0
36.0
54.0
72.0
1
2
2
2
4.0
60.8
69.5
86.8
70
70
90
NOTE 1: HACR Type per NEC.
TABLE 21: DM 300 ELECTRICAL DATA HIGH STATIC MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
175
175
175
225
225
175
175
175
225
250
90
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
149.9
149.9
154.4
201.6
210.9
149.5
149.5
169.0
190.7
234.0
74.8
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
208
230
460
575
41.0
41.0
20.5
17.3
255
255
145
102
4.5
4.3
2.2
1.7
38.6
38.6
19.3
15.4
10.0
10.0
5.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
43.3
86.6
129.9
173.2
-
21.7
43.3
65.0
86.6
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
74.8
90
84.5
95.3
117.0
61.7
61.7
90
110
125
70
70
70
18.0
36.0
54.0
72.0
1
2
2
2
17.3
34.6
52.0
69.3
4.0
67.6
76.2
93.5
90
100
NOTE 1: HACR Type per NEC.
Unitary Products Group
27
262259-YTG-B-0107
1
TABLE 22: DM VOLTAGE LIMITATIONS
VOLTAGE LIMITATIONS
VOLTAGE
POWER
SUPPLY
MIN.
MAX.
VOLTAGE
208/230-3-60
187
253
LIMITATIONS
414
518
506
630
460-3-60
575-3-60
1. Utilization Range “A” in accordance with ARI Standard
110.
TABLE 23: PHYSICAL DATA
MODELS
DM180
DM240
DM300
CENTRIFUGAL BLOWER (Dia. x Wd.)
FAN MOTOR HP, STANDARD/HI STATIC
ROWS DEEP
15x15
5.0
18x15
7.5
3
18x15
10/15
4
EVAPORATOR
BLOWER
3
EVAPORATOR COIL FINS PER INCH
13.5
20
FACE AREA (Sq. Ft.)
15.5
20.52
PROPELLER DIA. (In.) (Each)
30
CONDENSER FAN
(Two Per Unit)
FAN MOTOR HP
NOM. CFM TOTAL
ROWS DEEP
(Each)
(Each)
1
6,500
2
7,200
2
7,200
2
20
43.3
-
CONDENSER
COIL
FINS PER INCH
FACE AREA (Sq. Ft.)
13
36
1
20
43.3
-
5 TON HERMETIC (RECIP.)
COMPRESSOR
(Qty. Per Unit)
11
10 TON TANDEM (RECIP.)
2
-
12.5 TON (SCROLL)
-
-
2
QUANTITY PER UNIT (12" X 24" X 2" or 4”)
QUANTITY PER UNIT (16" X 20" X 2" or 4”)
QUANTITY PER UNIT (16" X 25" X 2" or 4”)
QUANTITY PER UNIT (18" X 24" X 2" or 4”)
TOTAL FACE AREA (Sq. Ft.)
-
-
-
-
4
4
FILTERS
CHARGE
-
4
4
5
-
-
15
17/8
8/8
1900
2100
2140
20
24
18/0
18/0
2291
2491
2531
SYSTEM No.1
SYSTEM No. 2
COOLING ONLY
18/0
18/0
2100
2300
2340
160
REFRIGERANT
22 (Lb./Oz.)
BASIC UNIT
N24
N32
GAS / ELECTRIC
ECONOMIZER
ECONOMIZER WITH
POWER EXHAUST
245
MOTORIZED DAMPER
150
25
30
35
40
10
18 KW
36 KW
54 KW
72 KW
ELECTRIC HEATER
OPERATING
WEIGHTS
(LBS.)
HOT GAS BYPASS
SUPPLY FAN VFD
ROOF CURB
175
200
185
45
185
220
BAROMETRIC DAMPER
ECONOMIZER / MOTORIZED
DAMPER RAIN HOOD
ECONOMIZER / POWER
EXHAUST RAIN HOOD
WOOD SKID
55
90
220
1. This compressor will be energized first.
28
Unitary Products Group
262259-YTG-B-0107
TABLE 24: SUPPLY FAN VFD WEIGHTS, IN LBS.
TABLE 25: ELECTRIC HEAT CORRECTION
FACTORS
SUPPLY FAN MOTOR
230V
460V
575V
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
W/O MANUAL BYPASS
25
30
30
30
25
30
30
30
30
30
35
40
208
230
460
575
1.00
0.92
0.92
0.92
5.0 hp
7.5 hp
208
240
480
600
10.0 hp
15.0 hp
W/MANUAL BYPASS
5.0 hp
30
35
35
40
30
35
35
35
35
35
40
45
7.5 hp
10.0 hp
15.0 hp
CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
UNIT TERMINAL
BLOCK 1TB2
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
R
RH
RC
Y1
Y2
TERMINALS
Y1
Y2
W1
UNIT TERMINAL
BLOCK 1 TB2
RC
RH
R
ADD
JUMPER
W2
G
Y1
Y2
Y1
Y2
ADD
JUMPER
W1
W2
B
W1
W2
G
W1
W2
24 VOLT
TRANSFORMER
X
3
3
A1
A2
Y3
G
G
B
X
B
124 Volt Thermostat 2TH04701024 or 2TH04701524
(with Subbase 2TB04700324).
LED1
24 VOLT
TRANSFORMER
LED2
4
A1
A2
NOT USED
2Terminal strip 1TB - located on relay board in 24-volt section
of the unit control box.
4
COM
A1
3Second stage heating is not required on units with a single stage
electric heater.
ADD
JUMPER
A2
T
POWER WIRING
T
L1
Refer to the
TO REMOTE SENSOR
2THO4702224 IF USED
LINE VOLTAGE
TERMINAL
BLOCK 2TB
ELECTRICAL DATA
tables to size the
power wiring, the
fuses and the
L2
L3
1Electronic programmable thermostat 2ET04700224 (includes subbase).
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3Second stage heating is not required on units with a single stage electric heater.
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
when the thermostat switches to the set-back position.
IN CONTROL BOX
disconnect switch.
GROUND LUG
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.
FIGURE 3 - TYPICAL DM FIELD WIRING DIAGRAM
Unitary Products Group
29
262259-YTG-B-0107
BLOWER ACCESS
(Location Of
Optional VFD)
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
FIELD-SUPPLIED
BLOWER MOTOR ACCESS
(Location Of Optional
VFD Bypass)
DISCONNECT SWITCH
COMPRESSOR
ACCESS
LOCATION
BLOWER
COMPARTMENT
ACCESS
(Auxiliary)
COIL
GUARD
DOT PLUG
(For pressure
Drop Reading)
48-5/8"(15 TON)
52-5/8" (20, 25 TON)
ELECTRIC/
GAS HEAT
ACCESS
CONDENSER
COILS
VENT AIR
OUTLET
HOODS
21"
5"
7-1/8"
COMBUSTION
AIR INLET
HOOD
6-3/8"
9-3/4"
5-7/8"
92"
)
(C)
(A)
GAS SUPPLY
ENTRY
CONTROL WIRING
ENTRY
46-5/8"
CONTROL BOX
ACCESS
11-1/2"
(B)
35"
POWER WIRING
ENTRY
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
FRONT
VIEW
RETURN
AIR
3-3/4"
33"
SUPPLY
AIR
2-3/4" 21-1/2"
11-1/8"
All dimensions are in inches. They are
subject to change without notice. Certified
dimensions will be provided upon request.
UNIT BASE WITH RAILS
(B)
(D)
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations
POWER WIRING
ENTRY
GAS SUPPLY
ENTRY
(A)
CONTROL WIRING
ENTRY
8-1/8"
NOTE:
46-5/8"
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
9-1/4"
12-1/2"
9-3/4"
FIGURE 4 - UNIT DIMENSIONS & CLEARANCES 15, 20 & 25 TON
TABLE 26: UTILITIES ENTRY DATA
OPENING SIZE
HOLE
USED FOR
(DIA.)
1-1/8” KO
Side
Bottom
Side
Control Wiring
A
3/4” NPS (Fem.)
3-5/8” KO
B
Power Wiring
3” NPS (Fem.)
Bottom
1
2-3/8” KO
C
D
Gas Piping (Front)
,
1
2
1-11/16” Hole
Gas Piping (Bottom)
1. One-inch gas piping NPT required.
2. Opening in the bottom of the unit can be located by the slice in
the insulation.
NOTE: All entry holes should be field sealed to prevent rain
water entry into the building.
30
Unitary Products Group
262259-YTG-B-0107
EVAPORATOR
SECTION
DOT PLUG
(For pressure
drop reading)
40-3/8"
FILTER
ACCESS
SUPPLY
AIR
RETURN
AIR
COMPRESSOR
ACCESS
OUTDOOR
AIR
40-1/2"
SUPPLY AIR
ACCESS
18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION
27-3/4"
Dimensions listed are for side
5-1/8"
RETURN AIR
ACCESS
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.
OUTDOOR AIR
COMPARTMENT
ACCESS
28-5/8” (15 TON)
39-5/8" (20, 25 TON)
REAR
VIEW
FIGURE 5 - REAR VIEW DIMENSIONS
NOTE:Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for
connecting side ducts.
For bottom duct applications:
For side duct applications:
1. Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
1. Replace the side panels on the supply and return air
compartments with the side duct flange accessory kit
panels.
2. Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.
2. Connect ductwork to the flanges on those panels.
3. Replace the side supply and return air compartment
panels.
Unitary Products Group
31
262259-YTG-B-0107
NOTE: ELEC / ELEC Models: Units and ductwork are
TABLE 27: MINIMUM CLEARANCES
approved for zero clearance to combustible material
when equipped with electric heaters.
LOCATION
CLEARANCE
36”
Front
24” (Less Economizer)
49” (With Economizer)
Rear
GAS / ELEC Models: A 1” clearance must be
provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the
unit.
24” (Less Economizer)
Left Side (Filter Access)
Right Side (Cond. Coil)
3
36” (With Economizer)
36”
0”
1
Below Unit
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)
2
Above Unit
Locate unit so that the vent air outlet hood is at least:
1. Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
• Three (3) feet above any force air inlet located
within 10 horizontal feet (excluding those integral to
the unit).
2. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters,
regulators and relief equipment.
ECONOMIZER
MOTORIZED
DAMPER
POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)
SUPPLY AIR
COMPARTMENT
RAIN HOOD
ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS
(on Outdoor Air Compartment)
FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
Compartment)
36-5/8”
1“ CONDENSATE
DRAIN
(Must be trapped)
16-1/8”
5”
28-3/16”
92”
REAR VIEW
LH VIEW
DETAIL “Y”
UNIT WITH RAIN HOODS
FIGURE 6 - UNIT DIMENSIONS DM180, 240 & 300 (RAINHOOD)
32
Unitary Products Group
262259-YTG-B-0107
FIGURE 7 - CENTER OF GRAVITY
FIGURE 8 - TYPICAL UNIT APPLICATIONS
Unitary Products Group
33
262259-YTG-B-0107
B
E
F
C
D
A
A
F
R
O
N
T
F
R
O
N
T
C
B
D
FIGURE 9 - FOUR AND SIX POINT LOADS
TABLE 28: FOUR AND SIX POINT LOADS
Total
4 Point Loads (lbs)
Unit Size
Shipping
Weight
A
B
C
D
180 Gas
240 Gas
300 Gas
180 Elec
240 Elec
300 Elec
2300
2500
2531
2100
2300
2331
539
538
593
492
295
546
563
563
645
514
517
594
612
715
674
558
658
621
586
684
619
536
630
570
Total
6 Point Loads (lbs)
Unit Size
Shipping
Weight
A
B
C
D
E
F
180 Gas
240 Gas
300 Gas
180 Elec
240 Elec
300 Elec
2300
2500
2531
2100
2300
2331
351
334
390
320
307
359
367
350
412
335
322
379
392
426
436
358
392
402
416
502
456
380
462
420
399
481
430
364
442
396
375
407
407
343
375
375
34
Unitary Products Group
262259-YTG-B-0107
MIN. ROOF OPENING:
SUPPLY AIR*
BACK OF UNIT
39-7/8" WIDE X 61-7/8" Long
OUTDOOR COIL
END OF UNIT
RETURN AIR*
DUCT SUPPORT RAILS
4"
2"
22-3/4"
2"
4"
33-1/8"
14-1/4" (15 Ton)
25-1/4" (20, 25 Ton)
35-7/8"
84"
115-5/16" (15 Ton)
126-1/4" (20, 25 Ton)
4"
*Supply and Return Air (including duct support rails)
as shown, are typical for bottom duct applications.
DUCT SIZES:
Supply Air = 22-1/2" x 35-5/8"
Return Air = 32-7/8" x 35-5/8"
FRONT
OF
For location of horizontal duct applications
(on back of unit), refer to Unit Dimension details.
UNIT
FIGURE 10 -UNIT ROOF CURB DIMENSIONS
2. The 58-1/2” overall dimension of the ducts allows duct-
work penetration between roof joists that are spaced on
72” centers.
NOTE: Ducts can be installed into the curb from the roof. All
electrical and gas line connections can be made
inside the curb.
FIGURE 11 -ROOF CURB DUCT OPENINGS
DIMENSION
1. The 2” space between the ducts allows for “jumping” an
existing roof joist.
Unitary Products Group
35
262259-YTG-B-0107
THERMOSTAT
TERMINALS
CONTROL
TERMINAL
BLOCK
W1
W1
W2
Y1
G
1
W2
Y1
2
Y2
OCC
P
G
R
C
P1
Y2
X
Smoke
Detector
R
Jumper 3
R
SD
SD
C
4
SD
C
RC
5
OCC
24 VAC
Class 2
6
X
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
1
2
3
4
5
6
Second stage heating not required on single stage heating units.
Second stage cooling not required on single stage cooling units.
Jumper is required if there is no Smoke Detector circuit.
Jumper is required for any combination of R, RC, or RH.
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.
FIGURE 13 -TYPICAL S implicity® CONTROL WIRING DIAGRAM
36
Unitary Products Group
262259-YTG-B-0107
ment. All unit wiring shall be both numbered and color coded.
All units shall be manufactured in a facility certified to ISO
9001 standards and the cooling performance shall be rated in
accordance with DOE and ARI test procedures. Units shall be
CGA listed, classified to ANSIZ21.47 standards, UL 1995/
CAN/CSA No. 236-M90 conditions.
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline 2000™ units are convertible single package
units. All models have dual independent refrigerant circuits
for efficient part load operation and maximum comfort control.
Although the units are primarily designed for curb mounting
on a roof, they can also be slab-mounted at ground level or
set on steel beams above a finished roof. Cooling only, cool-
ing with gas heat and cooling with electric heat models are
available with a wide variety of factory-mounted options and
field-installed accessories to make them suitable for almost
every application. All units are self-contained and assembled
on full perimeter base rails with holes in the four corners for
overhead rigging. Every unit is completely piped, wired,
charged and tested at the factory to simplify the field installa-
tion and to provide years of dependable operation. All models
(including those with an economizer) are suitable for either
bottom or horizontal duct connections. Models with power
exhaust are suitable for bottom duct connections only. For
bottom duct, remove the sheet metal panels from the supply
and return air openings through the base of the unit. For hori-
zontal duct, replace the supply and return air panels on the
rear of the unit with a side duct flange accessory. All supply
air blowers are equipped with a belt drive that can be
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel, with
exterior surfaces coated with a non-chalking, powdered paint
finish, certified at 1000 hours salt spray test per ASTM-B117
standards. Indoor blower section shall be insulated with a min-
imum 1/2" thick insulation, coated on the airside. Aluminum
foil faced insulation shall be used in the furnace compartment
and be fastened with ridged fasteners to prevent insulation
from entering the air stream. Cabinet panels shall be "large"
size, easily removable for servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging and proper sealing on roof
curb applications. Disposable 2" filters shall be furnished and
be accessible through a removable access door, sealed air-
tight. Units filter track shall be designed to accommodate
either 2" or 4" filters. Fan performance measuring ports shall
be provided on the outside of the cabinet to allow accurate air
measurements of evaporator fan performance without remov-
ing panels or creating air by-pass of the coils. Condensate
pan shall be internally sloped and conform to ASHRAE 62-89
self-draining standards. Condensate connection shall be a
minimum of 1" I.D. female and be a ridged mount connection.
Unit shall incorporate a fixed outdoor air damper with an out-
door air intake opening covered with a bird screen and a rain
hood painted to match the exterior of the unit.
adjusted to meet the exact requirements of the job.
Each unit shall have 2 condenser fan motors. A high speed
drive accessory is available for applications with a higher
CFM and/or static pressure requirement. All compressors
include crankcase heat and internal pressure relief. Every
refrigerant circuit includes an expansion valve, a liquid line fil-
ter-drier, a discharge line high pressure switch and a suction
line with a freezestat and low pressure/loss of charge switch.
The unit control circuit includes a 75 VA transformer, a 24-volt
circuit breaker and a relay board with two compressor lockout
circuits, a terminal strip for thermostat wiring, plus an addi-
tional set of pin connectors to simplify the interface of addi-
tional field controls. All units have long lasting powder paint
cabinets with 1000 hour salt spray test approval under
ASTM-B117 procedures. All models are CSA approved. All
models include a 1-year limited warranty on the complete
unit. Compressors and electric heater elements carry an
additional 4-year warranty. Aluminized steel tubular heat
exchangers carry an additional 9-year warranty.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable-
pitch motor pulley. Job site selected (B.H.P.) brake horse-
power shall not exceed the motors nameplate horsepower
rating, plus the service factor. Units shall be designed not to
operate above service factor. Fan wheel shall be double-inlet
type with forward-curved blades, dynamically balanced to
operate smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
A variable air volume (VAV) option using a variable frequency
drive (VFD) is available for applications requiring a constant
supply duct static pressure. Units equipped for VAV shall be
controlled by a duct pressure transducer with a 0 - 5” WC
pressure range. The pressure transducer shall provide a 0 - 5
VDC output signal to a VAV control board which, in turn shall
provide a 2 - 10 VDC speed reference signal to the VFD.
Units equipped with VFD’s shall have factory-installed man-
ual bypass as an option.
DESCRIPTION
Units shall be factory-assembled, single packaged, DM***N
Electric Cooling/Gas Heat, DM***C/E Electric Cooling/
Optional Electric Heat, designed for outdoor mounted instal-
lation. The 15, 20 and 25 ton units shall have minimum EER
ratings of 8.5.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to cor-
rosion resistant steel spider brackets and shall be dynami-
cally balanced for smooth operation. The 2 outdoor fan
motors shall be totally enclosed with permanently lubricated
They shall have built-in field convertible duct connections for
down discharge supply/return or horizontal discharge supply/
return, and be available with factory installed options or field
installed accessories. The units shall be factory wired, piped,
charged with R-22 refrigerant and factory tested prior to ship-
Unitary Products Group
37
262259-YTG-B-0107
bearings, internally protected against overload conditions and
staged independently.
diagnostic code that indicates which safety
switch has tripped.
REFRIGERANT COMPONENTS
d. Unit shall incorporate "AUTO RESET" compressor
over temperature, over current protection.
Compressors:
e. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
a. Shall be Scroll (25T only) compressors internally
protected with internal high-pressure relief and over
temperature protection.
f. Unit control board shall have on-board diagnostics
and fault code display.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent
mounting.
g. Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0 °F.
Coils:
h. Control board shall monitor each refrigerant safety
switch independently.
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
i.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
GAS HEATING SECTION (DM***N MODELS)
Shall be designed with induced draft combustion with post
purge logic and energy saving direct spark ignition, redun-
dant main gas valve. Ventor wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25° F. Burners shall be of the in-
shot type, constructed of aluminum coated steel and contain
air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
d. The refrigeration system shall provide at least 15° F
of sub-cooling at design conditions.
a. Primary and auxiliary high-temperature limit
switches.
e. All models shall have two independent circuits.
f. Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in
low-load applications. HGBP shall be a standard
feature on VAV models and an optional feature on
CV models.
b. Induced draft motor speed sensor.
c. Flame roll out switch (automatic reset).
d. Flame proving controls. Unit shall have two inde-
pendent stages of capacity.
UNIT CONTROLS
ELECTRIC HEATING (DM***C/E MODELS)
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resettable circuit
breaker on the 24-volt transformer side.
Nickel chromium electric heating elements shall be provided
as required by the application with 1 or 2 stage control, as
required, from 13.5 KW to 72 KW capacities. The heating
section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating
at an excessive temperature. Units with Electric Heating shall
be wired for a single point power supply with branch circuit
fusing (where required).
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c. Loss-of-charge/Low-pressure switch.
1. High-pressure switch.
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125° F
outdoor temperature, exceeding maximum load criteria of
ARI Standard 340/360. The compressor, with standard
controls, shall be capable of operation down to 0° F outdoor
2. Freeze-protection thermostat, evaporator coil. If
any of the above safety devices trip, a LED
(light-emitting diode) indicator shall flash a
38
Unitary Products Group
262259-YTG-B-0107
temperature. Unit shall be provided with fan time delay to
prevent cold air delivery before heat exchanger warms up
(Gas heat only).
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14" high, full perimeter curb with wood
nailer (shipped knocked-down).
ELECTRICAL REQUIREMENTS
•
100% BAROMETRIC RELIEF DAMPER - Contains a
rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure
through the unit.
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
•
•
•
•
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
STANDARD LIMITED WARRANTIES
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
•
•
•
•
Compressor 5 Years
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
BURGLAR BARS - Designed to work with above roof
curbs, depending on unit model. Fits duct openings of
curb supply and return air openings.
•
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on units
with power exhaust.
HIGH SPEED DRIVE - Includes blower pulley and belt
for higher CFM and/or static pressure requirements.
•
•
WOOD SKID - Allows unit to be handled with 90" forks.
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD
(DMN/E/C300 only) - Contains all hood panels and the
hardware for assembling.
•
•
ANTI-RECYCLE TIMER - Assures 5-minute off time
between compressor cycles.
COIL GUARD KIT - Guard for cooling coil.
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
•
•
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in
the design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected posi-
tions - regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
•
•
•
•
•
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
BAS CONTROLS (S implicity® INTELLI-Comfort™ CPC,
JOHNSON, HONEYWELL, NOVAR)
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
Unitary Products Group
39
•
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
•
•
•
4" PLEATED FILTERS
DISCONNECT SWITCH
•
•
HIGH SPEED DRIVE
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
2" THROW AWAY FILTERS
Subject to change without notice. Printed in U.S.A.