262260-YTG-E-1008
®
DESCRIPTION
YORK Sunline Ultra™ units are convertible single package
high efficiency rooftops. All models have independent dual
refrigerant circuits for efficient part load operation. Although
the units are primarily designed for curb mounting on a roof,
they can also be slab-mounted at ground level or set on steel
beams above a finished roof.
TECHNICAL GUIDE
All units include:
•
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
SINGLE PACKAGE GAS/ELECTRIC UNITS
AND SINGLE PACKAGE
Two-stage cooling provided by dual independent refriger-
ation circuits with expansion valves, filter-driers, high and
low pressure/loss of charge switches and freezestats
•
•
Hermetically sealed scroll compressors with crankcase
heaters
AIR CONDITIONERS
DH 180, 210, 240 & 300
Two-stage heating provided by dual independent heat
exchangers with aluminized steel tubes, redundant gas
valves, spark ignition with induced draft logic
15, 17.5, 20 & 25 NOMINAL TONS
10.8 EER (15 TONS), 10.2 EER (17.5 TONS), 9.7 EER (20
TONS) AND 9.6 EER (25 TONS)
•
•
Permanently lubricated motors
Bottom or side air discharge configuration capability
(field convertible)
•
•
Belt drive blower motor with high static drive options
Constant supply air volume (CV) with optional variable
air volume (VAV)
•
•
•
•
•
•
Manufactured under the quality standards of ISO9001
Twenty-four volt control circuit with compressor lock-out
Zero-25% fixed air damper with hood
Copper tube/aluminum fin coils
Hinged filter access and tool free latched doors optional
Hinged tool free blower, blower motor, filters and electri-
cal panel access optional
•
•
•
•
Rigging holes in base rails for lifting
Single point power connection
Complete factory package - tested, charged and wired
CSA agency approvals on all units
WARRANTY
•
•
•
Factory Limited Parts Warranty
One-year parts warranty
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
262260-YTG-E-1008
PRODUCT NOMENCLATURE
15-25 Ton Sunline Ultra™ Model Number Nomenclature
D H 180 N24 A 2 A AA 1 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
H = 10.0-11.0 EER A/C
SS Drain Pan
CPC Controller, DFS, APS
Nominal Cooling Capacity
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
180 = 15 Ton
210 = 17.5 Ton
240 = 20 Ton
300 = 25 Ton
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD (not available with factory installed BAS options)
Variable Air Volume, VFD with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass with ModLINC (not available with factory installed BAS options)
Variable Air Volume, VFD (BAS ready)
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No field installed
electric heat
Gas Heat Options
N24 = 240 MBH Output Aluminized Steel
N32 = 320 MBH Output Aluminized Steel
S24 = 240 MBH Output Stainless Steel
S32 = 320 MBH Output Stainless Steel
Variable Air Volume, VFD and Manual Bypass (BAS ready)
Variable Air Volume, VFD Ready (for customer provided, field installed drive)
Variable Air Volume, VFD Ready with ModLINC (for customer-provided, field-installed drive)
2" Pleated filters
Electric Heat Options
4" Pleated filters
E18 = 18 KW
E36 = 36 KW
E54 = 54 KW
E72 = 72 KW
BAS Ready Economizer (2-10 V.D.C. Actuator without a controller)
Double Wall Construction
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
Airflow
1 = First Generation
2 = Second Generation
A = Std. Motor
B = Std. Motor/Economizer
C = Std. Motor/Economizer/Power Exhaust
(Downflow Only)
Additional Options
Hinged Filter Door & Tool Free Access Cabinet
D = Std. Motor/Motorized Damper
E = Std. Motor/Motorized Damper/Barometric Relief
J = Std. Motor/Economizer/Barometric Relief
N = Hi Static
Standard Cabinet
AA = None
BA = Hinged Filter Door & Tool Free Access Panels
BB = Phase Monitor, Hinged Filter Door & Tool Free
Access Panels
P = Hi Static/Economizer
AB = Phase Monitor
Q = Hi Static/Economizer/Power Exhaust
(Downflow Only)
R = Hi Static/Motorized Damper
K = Hi Static/Motorized Damper/Barometric Relief
S = Hi Static/Economizer/Barometric Relief
AC = Coil Guard
AD = Dirty Filter Switch
BC = Coil Guard, Hinged Filter Door & Tool Free
Access Panels
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
BD = Dirty Filter Switch, Hinged Filter Door &
Tool Free Access Panels
BE = Phase Monitor & Coil Guard, Hinged Filter
Door & Tool Free Access Panels
BF = Phase Monitor & Dirty Filter Switch, Hinged
Filter Door & Tool Free Access Panels
BG = Coil Guard & Dirty Filter Switch, Hinged Filter
Door & Tool Free Access Panels
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
BH = Phase Monitor, Coil Guard & Dirty Filter Switch,
Hinged Filter Door & Tool Free Access Panels
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products
3
262260-YTG-E-1008
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assis-
tance. Optionally, the control board can be pro-
grammed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
FEATURES
All models are available with a wide variety of factory-
mounted options such as stainless steel heat exchangers,
phase monitor, dirty filter switch, and coil guard to make them
suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at
the factory to simplify the field installation and to provide
years of dependable operation.
•
The S implicity® control board used in this product will
effectively operate the cooling system down to 0°F
when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying this
product for process cooling applications (computer
rooms, switchgear, etc.), please reference applications
bulletin AE-011-07 or call the applications department
for Unitary Products @ 1-877-UPG-SERV for
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. Models with
factory installed power exhaust are suitable for bottom
duct connections only. For bottom duct, you remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you replace
the supply and return air panels on the rear of the unit with a
side duct flange accessory.
guidance. Additional accessories may be needed for
stable operation at temperatures below 30°F.
All models are available with these “factory mounted” outdoor
air damper options:
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
•
Single enthalpy economizer with or without power
exhaust
•
•
•
BAS-ready economizer with or without power exhaust
Motorized outdoor air damper
Barometric Relief Damper
•
•
Lead-Lag - An integrated Lead-Lag option allows
equal run time hours on all compressors, thereby
extending the life of all compressors. This option is
selectable on the unit control board.
A fixed outdoor air intake assembly will be shipped in the
return air compartment of all units ordered without an econo-
mizer or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10, 15
or 25% outdoor air. With bottom duct connections, the intake
damper assembly should be mounted over the opening in the
return air panel. With horizontal ductwork, it should be
mounted on the return air duct.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
All supply air blowers are equipped with a belt drive that can
be adjusted to meet the exact requirements of the job. A high
static drive option is available for applications with a higher
CFM and/or static pressure requirement. A variable air volume
(VAV) option using a variable frequency drive is available for
applications requiring a constant supply duct pressure. A dif-
ferential pressure transducer is used to monitor supply duct
static pressure and return a speed reference signal to the VFD
to control the output of the indoor blower motor.
•
•
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
All compressors include scroll compressors and internal pres-
sure relief. Every refrigerant circuit includes an expansion
valve, a liquid line filter-drier, a discharge line high pressure
switch and a suction line with a freezestat and low pressure/
loss of charge switch to protect all system components. A hot
gas bypass option, consisting of an adjustable compressor
discharge bypass valve, is available for low cooling load
applications.
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
®
®
•
S implicity Controls - S implicity control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
4
Johnson Controls Unitary Products
262260-YTG-E-1008
ELECTRIC HEATER LOCATION
(OPTIONAL ELECTRIC/ELECTRIC UNITS)
HIGH EFFICIENCY COMPRESSORS
WITH CRANKCASE HEATERS
20 GAUGE ALUMINIZED STEEL
TUBULAR HEAT EXCHANGERS
LONG LASTING
POWDER PAINT FINISH
COPPER TUBE/ALUMINUM FIN
CONDENSER COILS
LOW VOLTAGE RELAY BOARD
AND TERMINAL STRIP
ECONOMIZER HOOD
ELECTRICAL DISCONNECT
MOUNTING LOCATION
(Field installed)
KNOCKOUT FOR
SIDE CONTROL WIRING ENTRY
KNOCKOUT FOR
SIDE POWER WIRING ENTRY SIDE
2" DISPOSABLE
FILTERS
TERMINAL BLOCK
(For Single Point Power Supply
with Electric Heat)
ELECTRIC\ELECTRIC UNITS
OUTDOOR AIR OPENING
FOR SLIDE-IN/PLUG-IN
INTERNAL ECONOMIZER(OPTION)
BOTTOM POWER & CONTROL
WIRING ENTRY
KNOCKOUTS FOR SIDE
GAS SUPPLY ENTRY
SIDE AND BOTTOM
SUPPLY & RETURN AIR
HOLE FOR BOTTOM
GAS SUPPLY ENTRY
DUCT OPENINGS(SIDE X SIDE)
POWER VENTOR MOTOR
1" NPTI
CONDENSATE DRAIN
GAS/ELECTRIC
UNIT SHOWN
WITH POST PURGE CYCLE
BELT-DRIVE
BLOWER MOTOR
LOCATION OF VFD (Optional)
FULL PERIMETER 14 GAUGE BASE
RAILS WITH LIFTING HOLES
LOCATION OF VFD BYPASS (Optional)
FIGURE 1 - UNIT CUTAWAY
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
•
BAS Controls - York’s Sunline™ series units offer factory
®
mounted BAS controls such as S implicity Intelli-
®
Comfort™, Novar , Honeywell, Johnson, York Commer-
All models are CSA approved.
cial Comfort System (YCCS) and CPC.
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
Gas Heat Operation - All gas heat units are built with
two heating sections for two equal stages of capacity
control. Each section includes a durable heat exchanger
with aluminized steel or optional stainless steel tubes, a
redundant gas valve, spark ignition, power venting, an
ignition module for 100% shut-off and all of the safety
controls required to meet the latest ANSI standards.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
BAS-READY ECONOMIZER - Includes a slide-in / plug-
in damper assembly with fully modulating spring-return
motor actuator with zero to 95-degree rotation capable of
introducing up to 100% outdoor air with nominal 1% leak-
age type dampers.
•
Electric Heat Operation - All electric heat models (fac-
tory installed only) are wired for a single power source
and include a bank of nickel chromium elements
mounted at the discharge of the supply air blower to pro-
vide a high velocity and uniform distribution of air across
the heating elements. Every element is fully protected
against excessive current and temperature by fuses and
two thermal limit switches.
Actuator requires 2-10 VDC input from an external
source, such as a field-installed or factory-installed BAS
controller. BAS-ready actuators have an adjustable auxil-
iary end-switch for optional power exhaust control.
For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, a factory-installed, dry bulb sensor deter-
mines if outdoor air temperature is low enough to provide
free-cooling operation. (Field-installed humidity sensors
for either outdoor air or outdoor & return air streams are
The power supply wiring can be routed into the control
box through a threaded pipe connection in the base pan
of the unit or through a knockout in the wiring panel on
the front of the unit.
Johnson Controls Unitary Products
5
262260-YTG-E-1008
available for single enthalpy and differential enthalpy
configurations, respectively).
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and oper-
ate the motor at full speed, or to power the drive (and not
the motor) for diagnostic purposes.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
POWER EXHAUST - Our economizer options are avail-
able with power exhaust. Whenever the outdoor air intake
dampers are opened for free cooling, the exhaust fan will
be energized to prevent the conditioned space from being
over-pressurized during economizer operation. BAS-
ready economizer actuators have an adjustable auxiliary
end-switch to provide a range of damper positions available
to energize power exhaust. For units with optional VAV,
power exhaust is energized by means of a binary output
signal from the unit's VAV control board.
Due to space limitations, VAV is not available with any of
the factory-installed BAS options described below, but is
available with ‘BAS-ready’ models. Terminal blocks are
provided in the control box for field wiring of the cus-
tomer-installed BAS.
A ‘VFD-ready’ option provides the provisions for a cus-
tomer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment
which may accommodate other vendor’s drives depend-
ing on their size. In order to utilize the unit’s mounting
bracket, the maximum recommended drive dimensions
are as follows:
The exhaust fan, motor and controls are installed and
wired at the factory. The rain hood must be assembled
and installed in the field.
For 5-hp motor applications ........................10” H x 6” W x 7” D
For 7.5 thru 15-hp motor applications.........13” H x 8” W x 8” D
The power exhaust option can only be used on bot-
tom duct configurations.
If the drive will not fit in the allotted space, then it will
have to be mounted elsewhere; either within the building
on a perpendicular wall which is not subjected to exces-
sive temperature, vibration, humidity, dust, corrosive
gas, explosive gas, etc., or within an appropriate enclo-
sure rated for outside installation to safeguard against
moisture, dust and excessive heat.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is oper-
ating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
A terminal block located in the control box is provided for
field connection of the VFD controls.
•
BAROMETRIC RELIEF DAMPER - This damper option
can be used to relieve internal building air pressure on
units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
HOT GAS BYPASS - To allow for low cooling load oper-
ation, a direct-acting pressure-modulating bypass control
valve installed on the system #1 discharge line is used to
divert high temperature, high pressure refrigerant around
the TXV in order to maintain a desired minimum evapo-
rator pressure. HGBP is standard on all units with VAV
and optional with CV units.
•
•
FILTER OPTIONS - Standard units are shipped with 2”
throw-away filters installed. 2” pleated and 4” pleated fil-
ters are offered as a factory installed option.
•
•
•
PHENOLIC COATED EVAPORATOR AND CON-
DENSER COILS - Special coating process that utilizes
Technicoat 10-1" processes. Coating is applied by total
immersion of the complete coil for maximum protection.
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or
you may order the unit with a “non-powered” conve-
nience outlet that can be wired in the field.
ELECTRIC HEATERS wired for single point power sup-
ply. These nickel chromium heater elements are pro-
vided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
DISCONNECT SWITCH - A HACR breaker sized to the
unit max fuse size is provided. Factory installed option
only.
VARIABLE AIR VOLUME (VAV) - A factory-installed
variable frequency drive (VFD), mounted in the Blower
Access compartment, is used to control the speed of the
indoor blower motor in order to maintain a constant static
pressure in the supply duct. A pressure transducer and
VAV control board are mounted inside the control box.
The drive comes completely wired and pre-programmed
from the factory.
•
BAS - Building Automation System Controls (avail-
able on two-system cooling product only).
S implicity® INTELLI-Comfort™ CONTROL - The York®
S implicity® INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sen-
sor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
6
Johnson Controls Unitary Products
262260-YTG-E-1008
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
YORK COMMERCIAL COMFORT SYSTEM (YCCS) -
Provides rooftop system integration for YCCS single
zone, change-over bypass and VAV systems.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
using CO sensors. It uses an inside CO sensor to per-
2
2
form Demand Ventilation. It can also use an Outside CO
2
sensor to perform Differential Demand Ventilation. It
uses a Patented Comfort Ventilation algorithm to provide
comfortable ventilation air temperature. The patented
economizer-loading algorithm will protect the equipment
when harsh operating conditions exist. Humidity in the
occupied space or return duct can be monitored and
controlled via humidity sensors and the on-board con-
nection for hot gas re-heat system. It uses the INTELLI-
Start™ algorithm to maximize energy savings by recov-
ering the building from the Unoccupied Setpoints to the
Occupied Setpoints just in time for the Occupied Time
Period to begin. The S implicity® INTELLI-Comfort™ bal-
ances space temperature, ventilation air temperature,
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
“off” times due to out side air infiltration. these smoke
detectors have an operational limit of 32°F to 131°F.
smoke detectors installed in areas that could be out
side those limitations will have to be moved to prevent
having false alarms.
•
•
•
•
•
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
CO and humidity for ultimate comfort.
2
S implicity® INTELLI-Comfort™ with ModLINC CON-
TROL - The York® S implicity® INTELLI-Comfort™ with
ModLINC control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an addi-
tional control to translate communications from MOD-
BUS to the BACnet MSTP protocol.
STAINLESS STEEL HEAT EXCHANGER - For applica-
tions in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
STAINLESS STEEL DRAIN PAN- An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
Novar® BAS CONTROL - The Novar® building automa-
tion system controller is factory installed. Includes supply
air sensor, return air sensor, dirty filter indicator switch,
and air proving switch.
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower per-
formance.
JOHNSON CONTROLS BAS CONTROL - The John-
son Control YK-UNT-1126 building automation system
controller is factory installed. Includes supply air sen-
sor, return air sensor, dirty filter indicator switch, and air
proving switch.
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
HINGED FILTER DOOR/”TOOL FREE” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
NOTE: Knobs are shipped separately within the unit to pre-
vent shipping damage. These must be field installed
for tool free operation.
Johnson Controls Unitary Products
7
262260-YTG-E-1008
•
HINGED/"TOOL FREE" BLOWER, BLOWER MOTOR,
FILTER AND ELECTRIC ACCESS PANELS - This
option allows for complete hinged and tool free access to
the unit's blower, blower motor, filters and electrical panel
sections.
tudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
•
SIDE DUCT FLANGES - One-inch flanges replace the
supply and return air panels on the rear of the unit to
accommodate horizontal duct connections. These
flanges can also be used individually for bottom supply/
horizontal return or horizontal supply/bottom return. They
cannot be used on units with power exhaust.
FIELD-INSTALLED ACCESSORIES
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONO-
MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capa-
ble of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
BAROMETRIC RELIEF DAMPER - This damper acces-
sory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower per-
formance.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER -
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
•
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
ROOF CURBS - Fourteen-inch high roof curbs provide a
water-tight seal between the unit and the finished roof.
These full perimeter curbs meet the requirements of the
National Roofing Contractors Association (NRCA) and
are shipped knocked-down for field assembly.
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
They're designed to fit inside the base rails of the unit
and include both a wood nailing strip and duct hanger
supports.
•
•
WOOD SKID - Allows unit to be handled with 90” forks.
CO SENSOR - Senses CO levels and automatically
2
2
•
•
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-of-
phase condition.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at alti-
8
Johnson Controls Unitary Products
262260-YTG-E-1008
1
TABLE 1: INDOOR SOUND POWER RATING
-12
SOUND POWER (db 10
Octave Band Centerline Frequency (Hz)
Watts)
ESP
IWG
BLOWER
UNIT
SIZE
dB(A)
CFM
SWL
@
dB(A)
2
RPM
BHP
63
125
250
500
1,000
2,000
4,000
8,000
10Ft.
180
210, 240
300
6,000
8,000
1.00
1.00
1.30
1,080
1,120
1,160
4.60
6.65
12.5
99
99
89
92
98
82
85
91
84
87
93
77
80
86
72
75
81
67
70
76
89
92
98
56
102
108
102
108
59
10,000
65
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA val-
ues provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no
way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or
sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
1
1
TABLE 2: CAPACITY RATINGS - (ARI 360)
TABLE 3: GAS HEAT RATINGS
2
3
MODEL
MBH
EER
IPLV
MODEL
MBH INPUT
MBH OUTPUT
COOLING ONLY
300
240
DH180N/S24
DH180N/S32
DH210N/S24
DH210N/S32
DH240N/S24
DH240N/S32
DH300N/S24
DH300N/S32
4
DH180C00
DH210C00
DH240C00
DH300C00
10.8
10.2
9.7
11.3
10.8
10.2
9.6
178
400
300
400
300
400
300
400
320
240
320
240
320
240
320
205
223
271
9.6
COOLING WITH GAS HEAT
4
DH180N/S
DH210N/S
DH240N/S
DH300N/S
10.8
10.2
9.7
11.3
10.8
10.2
9.6
178
205
223
271
9.6
COOLING WITH ELECTRIC HEAT
4
DH180E18
10.8
11.3
11.3
11.0
178
178
176
176
1. All units are two-stage heating. First stage is 50% of total.
4
4
4
DH180E36
DH180E54
10.8
10.5
SSE = Steady State Efficiency (80%) - Output divided by Input
DH180E72
DH210E18
DH210E36
DH210E54
DH210E72
DH240E18
DH240E36
DH240E54
DH240E72
DH300E18
DH300E36
DH300E54
DH300E72
10.5
10.2
10.2
10.0
10.0
9.6
11.0
10.8
10.8
10.6
10.6
10.1
10.1
9.7
205
205
203
203
223
223
221
219
271
271
269
269
For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to be
controlled by duct static pressure via the VAV con-
trol board.
9.6
9.5
9.5
9.6
9.6
9.7
9.6
9.6
If there are VAV boxes present in the duct system,
the boxes must be driven to the full-open position
using a customer-supplied power source to assure
adequate airflow across electric heating elements or
gas heat exchanger tubes.
9.5
9.5
9.4
9.4
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. IPLV = Integrated part load value.
4. Deduct 2 MBH @ 208V.
Johnson Controls Unitary Products
9
262260-YTG-E-1008
TABLE 4: DH 180 COOLING CAPACITIES (15 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
223.0
211.0
199.0
181.3
178.5
231.5
219.0
206.5
188.1
185.3
240.0
227.0
214.0
195.0
192.0
226.4
213.5
194.5
191.5
225.8
213.0
194.0
191.0
11.3
11.2
11.1
10.8
10.5
11.3
11.2
11.2
10.9
10.6
11.4
11.3
11.2
10.9
10.6
11.2
11.2
10.8
10.5
11.2
11.1
10.8
10.5
100.4 79.0
57.7
-
-
-
-
-
-
218.1
203.0
188.0
173.0
170.1
225.0
209.5
194.0
178.5
175.6
232.0
216.0
200.0
184.0
181.0
217.6
201.5
185.4
182.4
219.2
203.0
186.8
183.7
12.9
12.6
12.3
12.1
12.1
12.9
12.6
12.4
12.2
12.2
13.0
12.7
12.4
12.2
12.2
12.8
12.5
12.2
12.2
12.8
12.5
12.3
12.3
99.3 77.9
56.5
-
-
-
-
-
-
133.1 111.7 90.3
68.9
130.5 109.2 87.8 66.4
161.8 140.4 119.0 97.6
4500
5250
6000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
165.8 144.4 123.0 101.6 80.2
76.2
181.3 178.6 157.3 135.9 114.5 93.1
178.5 179.1 162.3 140.9 119.6 98.2
173.0 169.9 148.5 127.2 105.8 84.4
170.1 170.1 151.1 129.7 108.3 86.9
107.2 87.6
62.3
-
-
-
-
-
-
112.3 87.0
61.8
-
-
-
-
-
-
148.2 122.9 97.7
72.4
146.4 121.2 95.9 70.6
189.2 158.3 133.0 107.7 82.5
180.5 155.3 130.0 104.7 79.5
188.1 186.8 170.1 144.9 119.6 94.3
185.3 185.5 175.7 150.4 125.1 99.8
178.5 177.0 162.3 137.0 111.7 86.5
175.6 175.6 165.0 139.8 114.5 89.2
114.0 96.2
67.0
-
-
-
-
-
-
125.3 96.2
67.0
-
-
-
-
-
-
163.3 134.2 105.0 75.8
162.3 133.2 104.0 74.8
212.6 172.2 143.0 113.8 84.7
199.3 170.2 141.0 111.8 82.7
195.0 195.0 183.0 153.8 124.7 95.5
192.0 192.0 189.0 159.8 130.7 101.5
184.0 184.0 176.0 146.8 117.7 88.5
181.0 181.0 179.0 149.8 120.7 91.5
178.0 144.8 111.6 78.4
-
-
-
176.0 142.7 109.5 76.3
-
-
-
212.8 185.2 152.0 118.8 85.6
201.2 181.7 148.5 115.3 82.1
6750
7500
194.5 194.5 188.5 155.3 122.1 88.9
191.5 191.5 190.0 156.8 123.6 90.4
185.4 185.4 181.4 148.2 115.0 81.8
182.4 182.4 181.4 148.1 114.9 81.7
192.8 155.5 118.2 81.0
-
-
-
189.6 152.3 115.1 77.8
-
-
-
213.0 198.3 161.0 123.7 86.5
203.0 193.3 156.0 118.7 81.5
194.0 194.0 194.0 156.7 119.5 82.2
191.0 191.0 191.0 153.8 116.5 79.3
186.8 186.8 186.8 149.5 112.2 75.0
183.7 183.7 183.7 146.5 109.2 71.9
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
213.2
195.1
177.0
164.6
161.8
218.6
200.0
181.5
168.8
165.9
224.0
205.0
186.0
173.0
170.0
208.9
189.5
176.3
173.2
212.7
193.0
179.5
176.4
14.5
14.0
13.5
13.4
13.7
14.5
14.0
13.6
13.5
13.7
14.6
14.1
13.6
13.5
13.8
14.3
13.8
13.6
14.0
14.4
13.9
13.8
14.1
98.2 76.8
55.4
-
-
-
-
198.8
182.7
166.5
155.6
152.2
203.9
187.3
170.8
159.5
156.1
209.0
192.0
175.0
163.5
160.0
195.8
178.5
166.8
163.2
199.7
182.0
170.0
166.4
16.1
15.4
14.8
14.7
15.0
16.2
15.5
14.8
14.8
15.1
16.3
15.6
14.9
14.9
15.2
15.7
15.0
15.0
15.3
15.9
15.2
15.1
15.5
97.0 75.6
54.2
-
-
-
-
128.0 106.6 85.2
63.8
-
125.1 103.7 82.4 61.0
153.3 131.9 110.5 89.1
-
4500
5250
6000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
157.8 136.4 115.0 93.6
72.2
-
67.7
-
164.6 161.2 139.8 118.4 97.1
161.8 161.2 139.8 118.4 97.1
75.7
155.6 153.8 135.7 114.3 93.0
152.2 151.9 134.0 112.6 91.3
71.6
75.7
69.9
117.4 86.5
61.2
-
-
-
-
-
-
117.3 84.6
59.4
-
-
-
-
144.7 119.4 94.1
68.8
140.7 115.5 90.2 64.9
164.1 146.3 121.0 95.7
-
171.9 152.3 127.0 101.7 76.5
70.5
-
168.8 167.1 154.4 129.1 103.9 78.6
165.9 165.6 154.4 129.1 103.9 78.6
159.5 158.7 148.6 123.3 98.1
156.1 156.0 146.8 121.5 96.2
72.8
70.9
136.6 96.2
67.0
-
-
-
-
-
-
137.6 93.7
64.5
-
-
-
-
-
-
161.3 132.2 103.0 73.8
156.3 127.2 98.0 68.8
186.0 168.2 139.0 109.8 80.7
175.0 160.7 131.5 102.3 73.2
173.0 173.0 169.0 139.8 110.7 81.5
170.0 170.0 169.0 139.8 110.7 81.5
163.5 163.5 161.5 132.3 103.2 74.0
160.0 160.0 159.5 130.3 101.2 72.0
173.9 140.7 107.4 74.2
-
-
-
170.2 137.0 103.8 70.6
-
-
-
189.5 178.2 145.0 111.8 78.6
178.5 170.1 139.3 106.0 72.8
166.8 166.8 165.8 132.6 99.4
163.2 163.2 163.0 129.7 96.5
6750
7500
176.3 176.3 174.3 141.0 107.8 74.6
173.2 173.2 172.7 139.5 106.3 73.1
66.1
63.3
-
186.4 149.2 111.9 74.6
-
-
-
184.1 146.8 109.6 72.3
-
193.0 188.3 151.0 113.7 76.5
182.0 179.6 147.0 109.7 72.5
170.0 170.0 170.0 132.8 95.5
166.4 166.4 166.4 129.1 91.9
-
179.5 179.5 179.5 142.3 105.0 67.7
176.4 176.4 176.4 139.1 101.9 64.6
58.3
54.6
10
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 4: DH 180 COOLING CAPACITIES (15 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
115°F
SENSIBLE CAPACITY, MBH
COIL
TOTAL POWER
ENTERING DRY BULB, °F
1
2
CAP.
INPUT
KW
WB
°F
MBH
CFM
90
85
80
75
70
65
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
184.5
170.3
156.0
146.5
142.7
189.3
174.6
160.0
150.2
146.3
194.0
179.0
164.0
154.0
150.0
182.8
167.5
157.3
153.2
186.6
171.0
160.6
156.4
17.8
16.9
16.0
16.1
16.4
17.9
17.0
16.1
16.2
16.5
18.0
17.1
16.2
16.3
16.6
17.2
16.3
16.4
16.7
17.3
16.4
16.5
16.8
95.8 74.4
53.0
-
-
-
-
122.3 100.9 79.5 58.1
148.8 127.4 106.0 84.6
-
4500
63.2
-
146.5 146.5 131.6 110.3 88.9
142.7 142.7 128.2 106.8 85.5
67.5
64.1
117.2 82.8
57.5
-
-
-
-
136.8 111.5 86.3 61.0
156.4 140.3 115.0 89.7
-
5250
6000
64.5
-
150.2 150.2 142.8 117.6 92.3
146.3 146.3 139.1 113.8 88.6
67.0
63.3
138.6 91.2
62.0
-
-
-
-
151.3 122.2 93.0 63.8
164.0 153.2 124.0 94.8
-
-
65.7
154.0 154.0 154.0 124.8 95.7
150.0 150.0 150.0 120.8 91.7
66.5
62.5
-
166.5 133.3 100.1 66.9
-
167.5 162.1 133.5 100.3 67.1
157.3 157.3 157.3 124.1 90.9
153.2 153.2 153.2 120.0 86.8
-
6750
7500
57.7
53.6
-
181.8 144.5 107.3 70.0
-
171.0 171.0 143.0 105.7 68.5
160.6 160.6 160.6 123.3 86.1
156.4 156.4 156.4 119.1 81.9
-
48.8
44.6
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Johnson Controls Unitary Products
11
262260-YTG-E-1008
TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
241.5
232.2
223.0
204.4
200.4
250.1
240.5
231.0
211.7
207.6
258.7
248.8
238.9
219.0
214.7
253.0
243.0
222.7
218.3
257.2
247.0
226.4
222.0
13.9
13.2
12.6
12.4
12.6
14.5
13.8
13.1
12.9
13.1
15.1
14.4
13.7
13.5
13.7
14.5
13.8
13.6
13.8
14.6
13.9
13.7
13.9
119.5 94.6
69.6
-
-
-
-
-
-
240.2
226.1
212.0
193.5
191.2
248.8
234.2
219.6
200.5
198.0
257.4
242.3
227.2
207.4
204.9
246.9
231.6
211.4
208.8
251.6
235.9
215.3
212.7
15.6
15.1
14.5
14.3
14.3
16.0
15.4
14.9
14.7
14.7
16.4
15.8
15.2
15.0
15.0
15.9
15.3
15.1
15.1
16.0
15.4
15.2
15.2
119.7 94.8
69.9
-
-
-
-
-
-
159.7 134.8 109.8 84.9
156.3 131.4 106.4 81.5
5250
6125
7000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
199.9 174.9 150.0 125.1 100.1
192.9 167.9 143.0 118.1 93.1
204.4 204.4 182.1 157.1 132.2 107.2
200.4 200.4 183.1 158.2 133.2 108.3
193.5 193.5 170.5 145.5 120.6 95.6
191.2 191.2 171.8 146.9 121.9 97.0
136.3 104.8 75.3
-
-
-
-
-
-
140.3 105.8 76.3
-
-
-
-
-
-
177.8 148.3 118.9 89.4
175.2 145.7 116.2 86.7
219.4 191.9 162.4 132.9 103.4
210.0 185.6 156.2 126.7 97.2
211.7 211.7 197.2 167.7 138.2 108.7
207.6 207.6 198.3 168.8 139.3 109.9
200.5 200.5 186.1 156.6 127.2 97.7
198.0 198.0 187.6 158.1 128.6 99.1
153.0 115.0 81.0
-
-
-
-
-
-
160.9 116.7 82.7
-
-
-
-
-
-
195.9 161.9 127.9 93.9
194.0 160.0 126.0 92.0
238.9 208.8 174.8 140.8 106.8
227.2 203.3 169.3 135.3 101.3
219.0 219.0 212.3 178.3 144.3 110.2
214.7 214.7 213.5 179.5 145.5 111.4
207.4 207.4 201.8 167.8 133.8 99.7
204.9 204.9 203.4 169.4 135.4 101.3
214.9 176.1 137.4 98.6
-
-
-
212.6 173.9 135.2 96.4
-
-
-
243.0 227.9 187.8 149.0 110.3
231.6 219.6 181.6 142.9 104.1
7875
8750
222.7 222.7 219.4 180.6 141.9 103.1
218.3 218.3 217.7 179.0 140.2 101.5
211.4 211.4 208.6 169.8 131.1 92.3
208.8 208.8 208.1 169.3 130.6 91.8
233.8 190.3 146.9 103.4
-
-
-
231.2 187.8 144.3 100.8
-
-
-
247.0 247.0 200.7 157.2 113.8
235.9 235.9 193.9 150.4 107.0
226.4 226.4 226.4 183.0 139.5 96.0
222.0 222.0 222.0 178.5 135.0 91.6
215.3 215.3 215.3 171.9 128.4 84.9
212.7 212.7 212.7 169.3 125.8 82.3
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
238.9
219.9
201.0
182.6
182.0
247.5
235.0
215.5
195.8
195.1
256.1
235.8
215.5
195.8
195.1
240.9
220.2
200.0
199.3
246.0
224.8
204.2
203.5
17.4
16.9
16.5
16.3
16.1
17.6
17.2
16.7
16.5
16.3
17.7
17.2
16.7
16.5
16.3
17.3
16.8
16.6
16.4
17.4
16.9
16.7
16.5
120.0 95.0
70.1
-
-
-
-
-
-
228.3
209.9
191.5
176.2
176.4
235.7
223.4
203.8
187.4
187.8
243.0
223.4
203.8
187.5
187.8
228.3
208.3
191.6
191.9
233.2
212.8
195.7
196.0
15.0
14.6
14.2
14.0
13.9
17.2
19.0
18.5
18.2
18.1
19.5
19.0
18.5
18.2
18.1
19.1
18.6
18.3
18.2
19.2
18.7
18.4
18.3
116.1 91.2
66.2
-
-
-
-
-
-
152.9 128.0 103.0 78.1
148.0 123.0 98.1 73.1
5250
6125
7000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
185.9 160.9 136.0 111.1 86.1
179.8 154.8 129.9 105.0 80.0
182.6 182.6 158.8 133.9 108.9 84.0
182.0 182.0 160.5 135.5 110.6 85.6
176.2 176.2 152.7 127.8 102.9 77.9
176.4 176.4 153.3 128.3 103.4 78.4
144.4 106.7 77.2
-
-
-
-
-
-
143.3 102.8 73.3
-
-
-
-
-
-
172.5 143.1 124.0 84.1
167.5 138.0 108.6 79.1
200.7 179.4 163.8 120.4 90.9
191.8 173.3 143.8 114.3 84.8
189.2 189.2 191.3 145.6 116.1 86.6
188.5 188.5 193.3 147.4 117.9 88.4
181.8 181.8 169.1 139.6 110.1 80.6
182.1 182.1 169.7 140.2 110.7 81.2
168.8 118.4 84.4
-
-
-
-
-
-
170.4 114.4 80.4
-
-
-
-
-
-
192.1 158.1 124.1 90.1
187.1 153.1 119.1 85.0
215.5 197.8 163.8 129.8 95.8
203.8 191.7 157.7 123.7 89.7
195.8 195.8 191.3 157.3 123.3 89.2
195.1 195.1 193.3 159.3 125.3 91.2
187.5 187.5 185.5 151.4 117.4 83.4
187.8 187.8 186.1 152.0 118.0 84.0
210.4 171.7 132.9 94.2
-
-
-
205.3 166.5 127.8 89.0
-
-
-
220.2 211.3 175.5 136.7 98.0
208.3 202.2 169.3 130.5 91.8
7875
8750
200.0 200.0 197.8 159.0 120.3 81.5
199.3 199.3 198.4 159.7 120.9 82.2
191.6 191.6 190.6 151.8 113.1 74.3
191.9 191.9 191.0 152.3 113.5 74.8
228.7 185.2 141.8 98.3
-
-
-
223.5 180.0 136.5 93.1
-
-
-
224.8 224.8 187.1 143.6 100.2
212.8 212.8 180.9 137.4 93.9
204.2 204.2 204.2 160.8 117.3 73.8
203.5 203.5 203.5 160.0 116.6 73.1
195.7 195.7 195.7 152.2 108.7 65.3
196.0 196.0 196.0 152.5 109.1 65.6
12
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
115°F
125°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
KW
WB
MBH
MBH
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
217.8
199.9
182.0
169.7
170.9
223.9
205.5
187.1
174.4
175.7
229.9
211.0
192.1
179.1
180.4
215.7
196.4
183.1
184.4
220.4
200.7
187.1
188.5
12.5
12.2
12.0
11.8
11.8
16.9
16.5
16.1
15.8
15.8
21.2
20.7
20.2
19.9
19.9
20.8
20.3
20.0
20.0
20.9
20.4
20.1
20.1
112.3 87.3
62.4
-
-
-
-
207.3
189.9
172.5
163.2
165.4
212.0
194.2
176.5
167.0
169.2
216.8
198.6
180.4
170.8
173.1
203.1
184.5
174.7
177.0
207.7
188.7
178.6
181.0
10.1
9.9
108.4 83.5
58.5
-
-
-
-
143.0 118.0 93.1
68.1
-
138.0 113.1 88.1
63.2
-
5250
6125
7000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
173.7 148.7 123.8 98.9
73.9
-
9.7
167.6 142.6 117.7 92.8
67.8
-
169.7 169.7 146.7 121.7 96.8
170.9 170.9 146.0 121.1 96.1
71.8
9.5
163.2 163.2 140.6 115.6 90.7
165.4 165.4 138.8 113.8 88.9
65.7
71.2
9.6
63.9
142.1 98.9
69.4
-
-
-
-
-
-
16.5
16.2
15.8
15.6
15.7
23.0
22.5
22.0
21.6
21.7
22.6
22.1
21.7
21.8
22.7
22.2
21.8
21.9
141.0 95.0
65.5
-
-
-
-
162.5 133.0 103.5 74.1
157.5 128.0 98.5
69.1
-
182.9 167.2 137.7 108.2 78.7
174.0 161.1 131.6 102.1 72.6
167.0 167.0 157.2 127.7 98.2
169.2 169.2 155.2 125.7 96.2
-
174.4 174.4 163.1 133.6 104.2 74.7
175.7 175.7 162.4 132.9 103.4 74.0
68.7
66.7
172.0 110.4 76.4
-
-
-
-
173.6 106.4 72.4
-
-
-
-
-
-
182.0 148.0 114.0 80.0
-
177.0 143.0 109.0 74.9
192.1 185.6 151.6 117.6 83.6
179.1 179.1 179.6 145.6 111.6
180.4 180.4 178.8 144.8 110.8
-
77.5
76.7
-
180.4 179.5 145.5 111.5 77.5
170.8 170.8 170.8 139.7 105.7 71.7
173.1 173.1 171.6 137.5 103.5 69.5
200.1 161.4 122.6 83.9
-
195.0 156.3 117.5 78.8
-
-
-
196.4 193.2 163.1 124.4 85.6
-
184.5 184.1 156.9 118.2 79.4
174.7 174.7 174.7 137.4 98.7
177.0 177.0 176.3 137.5 98.8
7875
8750
183.1 183.1 183.4 144.6 105.9 67.1
184.4 184.4 183.6 144.9 106.1 67.4
59.9
60.0
-
218.2 174.8 131.3 87.8
-
-
-
207.7 169.5 126.1 82.6
-
200.7 200.7 174.6 131.1 87.7
188.7 188.7 168.4 124.9 81.4
178.6 178.6 178.6 135.1 91.6
181.0 181.0 181.0 137.5 94.0
-
187.1 187.1 187.1 143.6 100.2 56.7
188.5 188.5 188.5 145.0 101.5 58.1
48.1
50.5
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance
Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Johnson Controls Unitary Products
13
262260-YTG-E-1008
TABLE 6: DH 240 COOLING CAPACITIES (20 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
277.0
263.0
249.0
240.6
237.8
287.0
272.5
258.0
249.3
246.4
297.0
282.0
267.0
258.0
255.0
295.2
279.5
270.1
266.9
308.4
292.0
282.2
278.9
19.1
18.6
18.0
17.9
17.7
17.9
17.4
16.9
16.7
16.5
16.7
16.2
15.7
15.6
15.4
13.7
13.3
13.2
13.0
11.2
10.8
10.7
10.6
159.2 130.7 102.2
-
-
-
-
-
-
262.0
249.0
236.0
228.6
226.7
272.0
258.5
245.0
237.3
235.4
282.0
268.0
254.0
246.0
244.0
280.7
266.0
257.6
255.5
293.3
278.0
269.2
267.1
20.5
20.1
19.6
19.4
19.1
19.4
18.9
18.5
18.3
18.1
18.2
17.8
17.4
17.2
17.0
15.3
15.0
14.8
14.6
12.8
12.5
12.4
12.2
153.7 125.2 96.7
-
-
-
-
-
-
196.1 167.6 139.1 110.6
190.4 161.8 133.3 104.8
6000
7000
8000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
233.0 204.5 176.0 147.5 119.0
227.0 198.5 170.0 141.5 113.0
240.6 240.6 215.3 186.8 158.3 129.8
237.8 237.8 213.7 185.2 156.7 128.1
228.6 228.6 204.2 175.7 147.1 118.6
226.7 226.7 203.3 174.8 146.3 117.8
189.9 145.8 112.1
-
-
-
-
-
-
187.6 140.0 106.3
-
-
-
-
-
-
219.9 186.3 152.6 118.9
214.1 180.4 146.7 113.0
250.0 226.7 193.0 159.3 125.6
240.5 220.7 187.0 153.3 119.6
249.3 249.3 236.2 202.5 168.8 135.1
246.4 246.4 234.3 200.6 166.9 133.3
237.3 237.3 224.6 190.9 157.2 123.5
235.4 235.4 223.7 190.0 156.3 122.6
220.5 160.9 122.0
-
-
-
-
-
-
221.5 154.9 116.0
-
-
-
-
-
-
243.8 204.9 166.0 127.1
237.8 198.9 160.0 121.1
267.0 248.9 210.0 171.1 132.2
254.0 242.9 204.0 165.1 126.2
258.0 258.0 257.0 218.1 179.2 140.4
255.0 255.0 255.0 216.1 177.2 138.4
246.0 246.0 245.0 206.1 167.2 128.4
244.0 244.0 244.0 205.1 166.2 127.4
275.1 228.1 183.8 139.5
-
-
-
265.0 220.8 176.5 132.2
-
-
-
279.5 270.4 232.5 188.2 143.9
266.0 260.4 225.0 180.7 136.4
9000
270.1 270.1 269.6 225.3 181.0 136.7
266.9 266.9 266.9 222.7 178.4 134.1
257.6 257.6 257.1 212.8 168.6 124.3
255.5 255.5 255.5 211.2 167.0 122.7
306.4 251.2 201.5 151.9
-
-
-
292.3 242.6 192.9 143.3
-
-
-
292.0 292.0 255.0 205.3 155.6
278.0 278.0 246.0 196.3 146.6
10000
282.2 282.2 282.2 232.5 182.8 133.1
278.9 278.9 278.9 229.2 179.5 129.8
269.2 269.2 269.2 219.6 169.9 120.2
267.1 267.1 267.1 217.4 167.7 118.0
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
247.1
235.0
223.0
216.5
215.6
257.0
244.5
236.0
225.3
224.3
267.0
254.0
241.0
234.0
233.0
266.1
252.5
245.2
244.1
278.2
264.0
256.3
255.2
21.9
21.5
21.2
20.9
20.6
20.8
20.5
20.1
19.8
19.6
19.7
19.4
19.1
18.8
18.6
16.9
16.7
16.4
16.2
14.4
14.2
14.0
13.8
148.1 119.6 91.1
-
-
-
-
-
-
232.2
221.1
210.0
205.4
204.0
241.6
230.1
218.5
213.7
212.2
251.0
239.0
227.0
222.0
220.5
251.1
238.5
233.3
231.7
263.2
250.0
244.5
242.8
23.3
22.9
22.6
22.2
21.9
22.3
21.9
21.6
21.2
21.0
21.3
20.9
20.6
20.2
20.0
18.4
18.1
17.8
17.6
16.0
15.7
15.4
15.3
144.0 115.5 87.0
-
-
-
-
-
-
184.6 156.1 127.6 99.0
180.0 151.5 123.0 94.5
6000
7000
8000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
221.0 192.5 164.0 135.5 107.0
209.0 187.5 159.0 130.5 102.0
216.5 216.5 193.0 164.5 136.0 107.5
215.6 215.6 193.0 164.5 136.0 107.5
205.4 205.4 183.0 154.5 126.0 97.5
204.0 204.0 182.6 154.1 125.6 97.1
185.3 134.3 100.6
-
-
-
-
-
-
184.7 132.6 96.0
-
-
-
-
-
-
208.2 174.5 140.8 107.1
203.1 169.4 135.7 102.0
231.0 214.7 182.0 147.3 113.6
218.0 206.2 175.5 141.8 108.1
225.3 225.3 213.0 179.3 145.6 111.9
224.3 224.3 213.0 179.3 145.6 111.9
213.7 213.7 202.0 168.3 134.6 100.9
212.2 212.2 201.6 167.9 134.2 100.5
222.5 148.9 110.0
-
-
-
-
-
-
225.5 149.8 105.0
-
-
-
-
-
-
231.8 192.9 154.0 115.1
226.3 187.4 148.5 109.6
241.0 236.9 198.0 159.1 120.2
227.0 224.9 192.0 153.1 114.2
234.0 234.0 233.0 194.1 155.2 116.4
233.0 233.0 233.0 194.1 155.2 116.4
222.0 222.0 221.0 182.1 143.2 104.4
220.5 220.5 220.5 181.6 142.7 103.9
255.0 213.4 169.2 124.9
-
-
-
244.7 208.0 163.7 119.4
-
-
-
252.5 250.4 217.5 173.2 128.9
238.5 237.5 211.6 167.3 123.1
9000
245.2 245.2 244.7 200.4 156.1 111.8
244.1 244.1 244.1 199.8 155.6 111.3
233.3 233.3 232.8 188.5 144.2 99.9
231.7 231.7 231.7 187.4 143.1 98.8
278.2 234.0 184.3 134.7
-
-
-
263.2 228.5 178.9 129.2
-
-
-
264.0 264.0 237.0 187.3 137.6
250.0 250.0 231.3 181.6 131.9
10000
256.3 256.3 256.3 206.7 157.0 107.3
255.2 255.2 255.2 205.6 155.9 106.2
244.5 244.5 244.5 194.8 145.1 95.5
242.8 242.8 242.8 193.2 143.5 93.8
14
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 6: DH 240 COOLING CAPACITIES (20 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
115°F
SENSIBLE CAPACITY, MBH
COIL
TOTAL POWER
ENTERING DRY BULB, °F
1
2
CAP.
INPUT
KW
WB
°F
MBH
CFM
90
85
80
75
70
65
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
217.3
207.2
197.0
194.2
192.4
226.2
215.6
205.0
202.1
200.2
235.0
224.0
213.0
210.0
208.0
236.1
224.5
221.3
219.2
248.2
236.0
232.7
230.5
24.8
24.3
23.9
23.5
23.2
23.8
23.4
23.0
22.5
22.3
22.8
22.4
22.0
21.6
21.4
20.0
19.6
19.2
19.1
17.5
17.2
16.9
16.7
139.8 111.3 82.8
-
-
-
-
-
-
175.4 146.9 118.4 89.9
6000
197.0 182.5 154.0 125.5 97.0
194.2 194.2 173.0 144.5 116.0 87.5
192.4 192.4 172.2 143.7 115.2 86.7
184.2 131.0 91.4
-
-
-
-
-
-
198.1 164.4 130.7 97.0
7000
8000
205.0 197.8 170.0 136.3 102.6
202.1 202.1 191.0 157.3 123.6 89.9
200.2 200.2 190.1 156.4 122.7 89.0
228.5 150.8 100.0
-
-
-
-
-
-
220.8 181.9 143.0 104.1
213.0 213.0 186.0 147.1 108.2
210.0 210.0 209.0 170.1 131.2 92.4
208.0 208.0 208.0 169.1 130.2 91.4
234.5 202.5 158.2 113.9
-
-
-
224.5 224.5 205.8 161.5 117.2
9000
221.3 221.3 220.8 176.6 132.3 88.0
219.2 219.2 219.2 175.0 130.7 86.4
248.2 223.0 173.4 123.7
-
-
-
236.0 236.0 225.5 175.8 126.1
10000
232.7 232.7 232.7 183.0 133.3 83.6
230.5 230.5 230.5 180.8 131.1 81.4
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Johnson Controls Unitary Products
15
262260-YTG-E-1008
TABLE 7: DH 300 COOLING CAPACITIES (25 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
75°F
85°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
371.3
334.4
297.6
290.9
281.0
373.9
336.8
299.7
293.0
282.9
376.6
339.1
301.7
295.0
284.9
341.5
303.7
297.0
286.8
343.8
305.7
299.1
288.7
19.7
19.3
18.8
18.3
18.2
19.7
19.3
18.9
18.3
18.2
19.8
19.3
18.9
18.4
18.3
20.3
19.8
19.3
19.2
21.3
20.8
20.2
20.1
191.8 156.2 120.6
-
-
-
-
-
-
348.9
318.7
288.4
277.6
272.4
353.3
322.7
292.0
281.1
275.8
357.7
326.7
295.7
284.6
279.3
330.7
299.3
288.1
282.7
334.8
303.0
291.6
286.1
21.5
21.1
20.8
20.1
20.1
21.6
21.3
21.0
20.3
20.3
21.8
21.5
21.1
20.5
20.4
22.2
21.8
21.2
21.1
22.9
22.6
21.8
21.8
185.5 149.8 114.2
-
-
-
-
-
-
233.0 197.4 161.8 126.1
226.6 190.9 155.3 119.7
7500
8750
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
274.2 238.6 203.0 167.3 131.7
267.7 232.0 196.4 160.8 125.1
290.9 284.9 246.4 210.8 175.1 139.5
281.0 281.0 261.8 226.1 190.5 154.9
277.6 274.6 238.9 203.3 167.7 132.0
272.4 272.4 249.6 214.0 178.3 142.7
219.7 168.5 126.4
-
-
-
-
-
-
214.0 162.4 120.3
-
-
-
-
-
-
253.8 211.7 169.6 127.5
247.8 205.7 163.6 121.5
288.0 254.9 212.8 170.7 128.5
281.7 249.0 206.9 164.7 122.6
293.0 290.0 258.3 216.2 174.1 132.0
282.9 282.9 274.5 232.4 190.3 148.1
281.1 279.6 251.7 209.5 167.4 125.3
275.8 275.8 262.9 220.8 178.7 136.5
247.6 180.9 132.3
-
-
-
-
-
-
242.4 175.0 126.4
-
-
-
-
-
-
274.6 226.0 177.4 128.8
269.0 220.4 171.8 123.2
10000
301.7 271.2 222.6 174.0 125.4
295.7 265.9 217.3 168.7 120.1
295.0 295.0 270.2 221.6 173.0 124.4
284.9 284.9 287.2 238.6 190.0 141.4
284.6 284.6 264.4 215.8 167.2 118.6
279.3 279.3 276.2 227.6 179.0 130.4
290.9 235.5 180.2 124.8
-
-
-
288.3 232.9 177.6 122.2
-
-
-
303.7 281.3 226.0 170.6 115.3
299.3 279.9 224.5 169.2 113.8
11250
12500
297.0 297.0 275.0 219.7 164.3 109.0
286.8 286.8 287.9 232.6 177.2 121.9
288.1 288.1 273.2 217.8 162.5 107.1
282.7 282.7 281.2 225.8 170.5 115.1
307.1 245.0 182.9 120.8
-
-
-
307.5 245.4 183.3 121.2
-
-
-
305.7 291.5 229.4 167.3 105.2
303.0 293.9 231.8 169.7 107.6
299.1 299.1 279.8 217.7 155.6 93.5
288.7 288.7 288.7 226.6 164.5 102.4
291.6 291.6 282.0 219.9 157.8 95.7
286.1 286.1 286.1 224.0 161.9 99.8
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
95°F
105°F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
SENSIBLE CAPACITY, MBH
ENTERING DRY BULB, °F
TOTAL POWER
TOTAL
POWER
1
2
1
2
CAP.
INPUT
KW
CAP.
INPUT
WB
MBH
MBH
KW
CFM
°F
90
85
80
75
70
65
90
85
80
75
70
65
77
72
326.6
302.9
279.2
264.2
263.7
332.8
308.6
284.4
269.2
268.7
338.9
314.3
289.7
274.2
273.7
320.0
294.9
279.2
278.6
325.7
300.2
284.1
283.6
23.2
23.0
22.8
22.0
22.0
23.5
23.3
23.1
22.3
22.3
23.8
23.6
23.4
22.6
22.6
24.1
23.9
23.0
23.0
24.6
24.3
23.5
23.5
179.1 143.5 107.9
-
-
-
-
-
-
314.3
288.7
263.1
253.6
251.0
319.5
293.5
267.5
257.8
255.2
324.6
298.2
271.8
261.9
259.3
303.0
276.2
266.1
263.4
307.8
280.5
270.3
267.6
26.2
25.8
25.3
24.5
24.6
26.4
25.9
25.4
24.7
24.8
26.6
26.1
25.6
24.9
24.9
26.5
26.0
25.2
25.3
26.8
26.3
25.6
25.6
163.3 127.7 92.0
-
-
-
-
-
-
220.1 184.5 148.8 113.2
209.2 173.5 137.9 102.2
7500
8750
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
261.1 225.5 189.8 154.2 118.5
254.1 219.4 183.7 148.1 112.5
264.2 264.2 231.5 195.8 160.2 124.6
263.7 263.7 237.4 201.8 166.1 130.5
253.6 253.6 225.7 190.1 154.5 118.8
251.0 251.0 222.7 187.1 151.4 115.8
208.2 156.3 114.2
-
-
-
-
-
-
197.7 139.8 97.6
-
-
-
-
-
-
241.8 199.7 157.5 115.4
230.6 188.5 146.3 104.2
275.4 243.0 200.9 158.8 116.7
263.0 237.2 195.0 152.9 110.8
269.2 269.2 245.0 202.9 160.8 118.7
268.7 268.7 251.3 209.2 167.1 124.9
257.8 257.8 239.6 197.5 155.4 113.3
255.2 255.2 236.4 194.2 152.1 110.0
237.3 169.1 120.5
-
-
-
-
-
-
232.2 151.9 103.3
-
-
-
-
-
-
263.5 214.9 166.3 117.7
252.0 203.4 154.8 106.2
10000
289.7 260.6 212.0 163.4 114.8
271.8 254.9 206.3 157.7 109.1
274.2 274.2 258.6 210.0 161.4 112.8
273.7 273.7 265.2 216.6 168.0 119.4
261.9 261.9 253.5 204.9 156.3 107.7
259.3 259.3 250.0 201.4 152.8 104.2
285.6 230.3 174.9 119.6
-
-
-
271.3 215.9 160.6 105.2
-
-
-
294.9 278.4 223.1 167.7 112.4
276.2 266.7 213.9 158.5 103.2
11250
12500
279.2 279.2 271.4 216.0 160.7 105.3
278.6 278.6 274.4 219.0 163.7 108.3
266.1 266.1 261.9 206.5 151.2 95.8
263.4 263.4 257.0 201.6 146.3 90.9
307.8 245.7 183.6 121.5
-
-
-
290.5 228.4 166.3 104.2
-
-
-
300.2 296.2 234.1 172.0 109.9
280.5 278.5 221.4 159.3 97.2
284.1 284.1 284.1 222.0 159.9 97.8
283.6 283.6 283.6 221.5 159.4 97.3
270.3 270.3 270.3 208.2 146.1 84.0
267.6 267.6 263.9 201.8 139.7 77.6
16
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 7: DH 300 COOLING CAPACITIES (25 TON) (CONTINUED)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
115°F
SENSIBLE CAPACITY, MBH
COIL
TOTAL POWER
ENTERING DRY BULB, °F
1
2
CAP.
INPUT
KW
WB
°F
MBH
CFM
90
85
80
75
70
65
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
302.0
274.5
247.1
242.9
238.3
306.2
278.4
250.5
246.3
241.6
310.4
282.2
254.0
249.7
244.9
286.0
257.4
253.1
248.2
289.8
260.9
256.4
251.5
29.3
28.5
27.7
27.1
27.2
29.3
28.5
27.8
27.1
27.3
29.4
28.6
27.8
27.2
27.3
28.9
28.1
27.4
27.6
29.1
28.3
27.7
27.8
147.5 111.8 76.2
-
-
-
-
-
-
198.2 162.6 126.9 91.3
7500
247.1 213.3 177.7 142.0 106.4
242.9 242.9 220.0 184.3 148.7 113.1
238.3 238.3 208.0 172.3 136.7 101.1
187.3 123.2 81.1
-
-
-
-
-
-
219.4 177.3 135.1 93.0
8750
250.5 231.3 189.2 147.0 104.9
246.3 246.3 234.2 192.1 150.0 107.8
241.6 241.6 221.4 179.3 137.2 95.1
227.1 134.6 86.0
-
-
-
-
-
-
240.5 191.9 143.3 94.7
10000
254.0 249.2 200.6 152.0 103.4
249.7 249.7 248.4 199.8 151.2 102.6
244.9 244.9 234.9 186.3 137.7 89.1
256.9 201.6 146.2 90.9
-
-
-
257.4 255.1 204.7 149.3 94.0
11250
12500
253.1 253.1 252.4 197.1 141.7 86.4
248.2 248.2 239.6 184.2 128.9 73.5
273.3 211.2 149.1 87.0
-
-
-
260.9 260.9 208.7 146.6 84.5
256.4 256.4 256.4 194.3 132.2 70.1
251.5 251.5 244.3 182.2 120.1 58.0
1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-
mance Table for the KW of the supply air blower motor.
2. These ratings include the condenser fan motors (Total 2.1 KW) and the compressor motors but not the supply air blower motor.
Nominal Rating
Johnson Controls Unitary Products
17
262260-YTG-E-1008
order to use the indoor blower tables for high altitude applica-
tions, certain corrections are necessary.
CFM, STATIC PRESSURE, AND POWER - ALTI-
TUDE AND TEMPERATURE CORRECTIONS
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In
TABLE 8: ALTITUDE CORRECTION FACTORS
ALTITUDE (FEET)
AIR TEMP
0
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
40
50
1.060
1.039
1.019
1.000
0.982
0.964
0.946
60
70
80
90
100
The examples below will assist in determining the airflow per-
formance of the product at altitude.
blower tables to select the blower speed and the BHP
requirement.
Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower performance
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature informa-
tion is given so 70°F is assumed.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table
8 must be used to determine the static pressure and BHP.
Since no temperature data is given, we will assume an air
temperature of 70°F. Table 8 shows the correction factor to be
0.832.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
Example 2: A system, located at 5,000 feet of elevation, is to
BHP at 5,000 ft = 3.2 x .832 = 2.66
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
18
Johnson Controls Unitary Products
262260-YTG-E-1008
FIGURE 2 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
Johnson Controls Unitary Products
19
262260-YTG-E-1008
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - COOLING ONLY
180 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
6000
BHP
BLOWER
SPEED,
(RPM)
4500
BHP
5250
BHP
6750
BHP
7200
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
850
870
6.0**
5.5
4.5
3.5
3.0
2.0
1.0
0.9
1.0
1.1
1.2
1.3
1.4
1.5
2.4
2.5
2.6
2.9
3.0
3.1
3.2
2.2
2.3
2.4
2.6
2.7
2.8
2.9
0.7
0.8
0.9
1.0
1.1
1.2
1.3
3.0
3.1
3.4
3.6
3.7
3.8
3.9
2.7
2.8
3.0
3.2
3.3
3.4
3.5
0.5
0.6
0.7
0.8
0.9
1.0
1.1
3.2
3.5
3.7
4.0
4.1
4.2
4.5
2.9
3.1
3.3
3.6
3.7
3.8
4.0
-
-
-
-
-
-
0.2
0.3
0.5
0.6
0.7
0.9
4.1
4.4
4.7
4.8.
5.0
5.2
3.7
3.9
4.2
4.3
4.5
4.7
-
-
-
915
0.2
0.4
0.5
0.6
0.7
4.5
4.9
5.1
5.4
5.7
4.0
4.4
4.6
4.8
5.1
965
980
1010
1040
208 VOLT AND HIGH STATIC DRIVE
965
980
6.0
5.5
4.5
3.5
3.0
2.0
1.0
1.2
1.3
1.5
1.6
1.7
1.9
2.1
2.9
3.0
3.2
3.4
3.5
3.7
3.9
2.6
2.7
2.9
3.0
3.1
3.3
3.5
1.0
1.1
1.3
1.4
1.5
1.7
2.0
3.6
3.7
3.9
4.0
4.2
4.5
4.7
3.2
3.3
3.5
3.6
3.8
4.0
4.2
0.8
0.9
1.1
1.2
1.3
1.5
1.8
4.0
4.1
4.5
4.7
4.9
5.1
5.5
3.6
3.7
4.0
4.2
4.4
4.6
4.9
0.5
0.6
0.8
1.0
1.2
-
4.7
4.8
5.1
5.5
5.7
-
4.2
4.3
4.6
4.9
5.1
-
0.4
5.0
4.4
0.5
5.1
4.6
1025
1065
1095
1130
1170
0.7
5.6
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
915
6.0**
5.0
4.0
3.5
2.0
1.0
1.0
1.1
1.2
1.3
1.5
1.6
2.4
2.6
2.9
3.0
3.2
3.3
2.2
2.4
2.6
2.7
2.9
3.0
0.8
0.9
1.0
1.1
1.3
1.4
3.1
3.3
3.6
3.7
3.9
4.0
2.8
3.0
3.2
3.3
3.5
3.6
0.6
0.7
0.8
0.9
1.1
1.2
3.5
3.7
4.0
4.1
4.5
4.7
3.1
3.3
3.6
3.7
4.0
4.2
0.2
0.3
0.5
0.6
0.9
1.0
4.1
4.4
4.7
4.8
5.3
5.5
3.7
3.9
4.2
4.3
4.7
4.9
-
-
-
0.2
0.4
0.5
0.7
-
4.5
5.0
5.1
5.7
-
4.0
4.4
4.6
5.1
-
965
980
1040
1065
230/460/575 VOLT AND HIGH STATIC DRIVE
980
6.0
4.5
4.0
3.5
2.5
1.5
1.0
1.3
1.5
1.6
1.7
1.9
2.1
2.2
2.9
3.2
3.4
3.5
3.7
3.9
4.0
2.6
2.9
3.0
3.1
3.3
3.5
3.6
1.1
1.3
1.4
1.5
1.7
2.0
2.1
3.7
3.9
4.0
4.2
4.5
4.7
4.8
3.3
3.5
3.6
3.8
4.0
4.2
4.3
0.9
1.1
1.2
1.3
1.5
1.8
2.0
4.1
4.5
4.7
4.9
5.1
5.5
5.7
3.7
4.0
4.2
4.4
4.6
4.9
5.1
0.6
0.9
1.0
1.2
-
4.8
5.3
5.5
5.7
-
4.3
4.7
4.9
5.1
-
0.5
5.1
4.6
1040
1065
1095
1130
1170
1190
0.7
5.7
5.1
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 11 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
20
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - COOLING ONLY
210 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
8000
BHP
9000
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
1015
6.0**
5.0
4.0
3.0
2.0
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.1
3.2
4.1
4.6
5.3
5.9
1.8
2.7
3.4
3.9
4.5
5.0
0.1
0.5
0.9
1.1
1.4
1.7
2.3
3.5
4.5
5.1
5.8
6.5
2.0
2.9
3.8
4.3
4.9
5.5
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
3.8
4.9
5.5
6.3
7.0
3.2
4.1
4.6
5.3
5.9
-
-
-
0.1
0.4
0.7
1.0
5.1
5.9
6.9
7.7
4.3
5.0
5.8
6.5
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.5
2.0
1.0
1.3
1.6
1.8
1.9
2.0
2.1
2.3
2.4
4.6
5.3
5.8
6.1
6.2
6.4
6.6
6.7
3.9
4.5
4.9
5.1
5.2
5.4
5.5
5.6
1.1
1.4
1.7
1.8
1.9
2.0
2.1
2.2
5.1
5.8
6.3
6.5
6.8
7.0
7.2
7.3
4.3
4.9
5.3
5.5
5.7
5.9
6.0
6.1
0.8
1.2
1.5
1.6
1.7
1.8
1.9
2.1
5.5
6.3
6.9
7.1
7.4
7.6
7.8
7.9
4.6
5.3
5.8
6.0
6.2
6.4
6.6
6.7
0.4
0.7
1.0
1.1
1.2
1.3
1.5
-
5.9
6.9
7.5
7.8
8.1
8.3
8.6
-
5.0
5.8
6.3
6.6
6.8
7.0
7.2
-
1010
1020
1035
1050
1075
1100
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.0
2.1
3.2
4.1
4.6
5.3
5.9
6.1
1.8
2.7
3.4
3.9
4.5
5.0
5.1
0.1
0.5
0.9
1.1
1.4
1.7
1.8
2.3
3.5
4.5
5.1
5.8
6.5
6.6
2.0
2.9
3.8
4.3
4.9
5.5
5.6
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
1.6
3.8
4.9
5.5
6.3
7.0
7.3
3.2
4.1
4.6
5.3
5.9
6.1
-
-
-
930
0.1
0.4
0.7
1.0
1.1
5.1
5.9
6.9
7.7
7.9
4.3
5.0
5.8
6.5
6.7
950
980
1015
1025
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.0
1.5
1.0
1.3
1.6
1.9
2.0
2.1
2.3
2.4
2.5
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
3.9
4.5
5.0
5.2
5.4
5.5
5.6
5.7
1.1
1.4
1.7
1.9
2.0
2.1
2.2
2.3
5.1
5.8
6.5
6.8
7.0
7.2
7.3
7.4
4.3
4.9
5.5
5.7
5.9
6.0
6.1
6.2
0.8
1.2
1.5
1.7
1.8
1.9
2.1
2.2
5.5
6.3
7.0
7.4
7.6
7.8
7.9
8.1
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
0.4
0.7
1.0
1.2
1.3
1.5
-
5.9
6.9
7.7
8.1
8.3
8.6
-
5.0
5.8
6.5
6.8
7.0
7.2
-
1015
1035
1050
1080
1100
1120
-
-
-
NOTES: 1.Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2.Refer to Table 13 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total
static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Johnson Controls Unitary Products
21
262260-YTG-E-1008
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - COOLING ONLY
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
8000
BHP
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
9000
BHP
9400
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
1015
6.0**
5.0
4.0
3.0
2.0
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.1
3.2
4.1
4.6
5.3
5.9
1.8
2.7
3.4
3.9
4.5
5.0
0.1
0.5
0.9
1.1
1.4
1.7
2.3
3.5
4.5
5.1
5.8
6.5
2.0
2.9
3.8
4.3
4.9
5.5
-
-
-
-
-
-
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
3.8
4.9
5.5
6.3
7.0
3.2
4.1
4.6
5.3
5.9
-
-
-
0.1
0.4
0.7
1.0
5.1
5.9
6.9
7.7
4.3
5.0
5.8
6.5
-
-
-
-
-
-
0.2
0.6
7.3
8.2
6.1
6.9
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.5
2.0
1.0
1.3
1.6
1.8
1.9
2.0
2.1
2.3
2.4
4.6
5.3
5.8
6.1
6.2
6.4
6.6
6.7
3.9
4.5
4.9
5.1
5.2
5.4
5.5
5.6
1.1
1.4
1.7
1.8
1.9
2.0
2.1
2.2
5.1
5.8
6.3
6.5
6.8
7.0
7.2
7.3
4.3
4.9
5.3
5.5
5.7
5.9
6.0
6.1
0.8
1.2
1.5
1.6
1.7
1.8
1.9
2.1
5.5
6.3
6.9
7.1
7.4
7.6
7.8
7.9
4.6
5.3
5.8
6.0
6.2
6.4
6.6
6.7
0.4
0.7
1.0
1.1
1.2
1.3
1.5
-
5.9
6.9
7.5
7.8
8.1
8.3
8.6
-
5.0
5.8
6.3
6.6
6.8
7.0
7.2
-
-
0.2
0.5
0.6
0.7
-
-
7.3
7.9
8.3
8.6
-
-
6.1
6.7
7.0
7.3
-
1010
1020
1035
1050
1075
1100
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
0.4
0.8
1.1
1.3
1.6
1.9
2.0
2.1
3.2
4.1
4.6
5.3
5.9
6.1
1.8
2.7
3.4
3.9
4.5
5.0
5.1
0.1
0.5
0.9
1.1
1.4
1.7
1.8
2.3
3.5
4.5
5.1
5.8
6.5
6.6
2.0
2.9
3.8
4.3
4.9
5.5
5.6
-
-
-
-
-
-
-
-
-
-
-
-
0.2
0.6
0.8
1.2
1.5
1.6
3.8
4.9
5.5
6.3
7.0
7.3
3.2
4.1
4.6
5.3
5.9
6.1
-
-
-
930
0.1
0.4
0.7
1.0
1.1
5.1
5.9
6.9
7.7
7.9
4.3
5.0
5.8
6.5
6.7
-
-
-
950
-
-
-
980
0.2
0.6
0.7
7.3
8.2
8.6
6.1
6.9
7.3
1015
1025
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.0
3.5
3.0
2.0
1.5
1.0
1.3
1.6
1.9
2.0
2.1
2.3
2.4
2.5
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
3.9
4.5
5.0
5.2
5.4
5.5
5.6
5.7
1.1
1.4
1.7
1.9
2.0
2.1
2.2
2.3
5.1
5.8
6.5
6.8
7.0
7.2
7.3
7.4
4.3
4.9
5.5
5.7
5.9
6.0
6.1
6.2
0.8
1.2
1.5
1.7
1.8
1.9
2.1
2.2
5.5
6.3
7.0
7.4
7.6
7.8
7.9
8.1
4.6
5.3
5.9
6.2
6.4
6.6
6.7
6.8
0.4
0.7
1.0
1.2
1.3
1.5
-
5.9
6.9
7.7
8.1
8.3
8.6
-
5.0
5.8
6.5
6.8
7.0
7.2
-
-
0.2
0.6
0.7
-
-
7.3
8.2
8.6
-
-
6.1
6.9
7.3
-
1015
1035
1050
1080
1100
1120
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes fixed outdoor air, 2” T/A filters, a dry evaporator coil and no electric heat.
2. Refer to Table 11 for additional static resistances.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
22
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (15 TON) - GAS HEAT
180 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
6000
BHP
BLOWER
SPEED,
(RPM)
4500
BHP
5250
BHP
6750
BHP
7200
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
850
870
6.0**
5.5
4.5
3.5
3.0
2.0
1.0
0.9
1.0
1.1
1.2
1.3
1.4
1.6
2.4
2.5
2.6
2.7
2.9
3.0
3.2
2.1
2.2
2.4
2.5
2.6
2.7
2.9
0.6
0.7
0.8
0.9
1.0
1.1
1.3
2.9
3.0
3.1
3.2
3.4
3.6
3.8
2.6
2.7
2.8
2.9
3.0
3.2
3.4
0.3
0.4
0.5
0.6
0.7
0.8
1.0
3.4
3.5
3.6
3.7
3.8
4.0
4.4
3.0
3.1
3.2
3.3
3.4
3.6
3.9
-
-
-
-
-
-
-
-
-
-
-
-
915
0.2
0.4
0.5
0.6
0.8
4.1
4.4
4.5
4.7
5.0
3.7
3.0
4.0
4.2
4.5
-
-
-
965
0.2
0.3
0.4
0.6
5.0
5.1
5.4
5.6
4.5
4.6
4.8
5.0
980
1010
1040
208 VOLT AND HIGH STATIC DRIVE
965
980
6.0
5.5
4.5
3.5
2.0
1.0
1.2
1.3
1.4
1.6
1.9
2.1
2.7
2.9
3.1
3.4
3.6
3.9
2.5
2.6
2.8
3.0
3.2
3.5
0.9
1.0
1.2
1.4
1.7
1.9
3.2
3.4
3.6
3.9
4.4
4.7
2.9
3.0
3.2
3.5
3.9
4.2
0.6
0.7
0.9
1.1
1.4
1.6
3.7
3.8
4.1
4.5
5.0
5.5
3.3
3.4
3.7
4.0
4.5
4.9
0.4
0.5
0.7
0.9
1.2
-
4.4
4.5
4.8
5.1
5.8
-
3.9
4.0
4.3
4.6
5.2
-
0.2
0.3
0.4
-
5.0
5.1
5.5
-
4.5
4.6
4.9
-
1025
1065
1125
1170
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
915
6.0**
5.0
4.0
3.5
2.5
1.5
1.0
1.0
1.1
1.2
1.3
1.4
1.5
1.6
2.5
2.6
2.7
2.9
3.0
3.1
3.4
2.2
2.4
2.5
2.6
2.7
2.8
3.0
0.7
0.8
0.9
1.0
1.1
1.2
1.4
3.0
3.1
3.2
3.4
3.6
3.7
3.9
2.7
2.8
2.9
3.0
3.2
3.3
3.5
0.4
0.5
0.6
0.7
0.8
0.9
1.1
3.5
3.6
3.7
3.8
4.0
4.2
4.5
3.1
3.2
3.3
3.4
3.6
3.8
4.0
-
-
-
-
-
-
0.2
0.4
0.5
0.6
0.7
0.9
4.1
4.4
4.5
4.7
4.9
5.1
3.7
3.9
4.0
4.2
4.4
4.6
-
-
-
965
0.2
0.3
0.4
0.5
-
5.0
5.1
5.4
5.7
-
4.5
4.6
4.8
5.1
-
980
1015
1050
1065
230/460/575 VOLT AND HIGH STATIC DRIVE
980
6.0
4.5
4.0
2.5
1.5
1.0
1.3
1.6
1.7
1.9
2.1
2.2
2.9
3.2
3.4
3.6
3.9
4.0
2.6
2.9
3.0
3.2
3.5
3.6
1.0
1.3
1.4
1.7
1.8
1.9
3.4
3.8
3.9
4.4
4.7
4.8
3.0
3.4
3.5
3.9
4.2
4.3
0.7
1.0
1.1
1.4
1.6
1.7
3.8
4.4
4.5
5.0
5.5
5.6
3.4
3.9
4.0
4.5
4.9
5.0
0.5
0.8
0.9
1.2
-
4.5
5.0
5.1
5.8
-
4.0
4.5
4.6
5.2
-
0.3
5.1
4.6
1045
1065
1125
1170
1190
0.6
5.6
5.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Johnson Controls Unitary Products
23
262260-YTG-E-1008
TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT
210 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
8000
BHP
9000
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
995
1015
6.0**
5.0
4.0
3.0
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
3.6
3.8
4.1
4.2
4.5
4.6
4.8
3.0
3.2
3.4
3.6
3.8
3.9
4.0
0.7
0.9
1.1
1.3
1.5
1.6
1.7
4.3
4.7
5.0
5.1
5.4
5.5
4.7
3.7
4.0
4.2
4.3
4.5
4.7
4.8
0.2
0.4
0.6
0.8
1.0
1.1
1.2
5.1
5.6
5.9
6.0
6.3
6.4
6.6
4.3
4.7
5.0
5.1
5.3
5.4
5.6
-
-
-
-
-
-
0.1
0.2
0.4
0.5
0.7
6.7
6.9
7.2
7.5
7.8
5.7
5.8
6.1
6.3
6.6
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
3.5
2.5
2.0
1.0
1.7
1.9
2.1
2.3
2.5
2.6
2.9
4.2
4.5
4.5
4.9
5.1
5.3
5.6
3.6
3.8
3.9
4.1
4.3
4.4
4.7
1.3
1.5
1.6
1.8
2.0
2.1
2.3
5.1
5.4
5.5
5.8
6.1
6.3
6.8
4.3
4.5
4.7
4.9
5.1
5.3
5.7
0.8
1.0
1.1
1.3
1.4
1.5
1.8
6.0
6.3
6.4
6.7
7.1
7.3
7.9
5.1
5.3
5.4
5.7
6.0
6.2
6.6
0.2
0.4
0.5
0.7
0.9
1.0
-
6.9
7.2
7.5
8.0
8.4
8.6
-
5.8
6.1
6.3
6.7
7.0
7.2
-
995
1025
1050
1065
1100
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
2.3
3.6
3.8
4.1
4.2
4.5
4.6
4.8
4.9
3.0
3.2
3.4
3.6
3.8
3.9
4.0
4.1
0.7
0.9
1.1
1.3
1.5
1.6
1.7
1.8
4.3
4.7
5.0
5.1
5.4
5.5
5.7
5.8
3.7
4.0
4.2
4.3
4.5
4.7
4.8
4.9
0.2
0.4
0.6
0.8
1.0
1.1
1.2
1.3
5.1
5.6
5.9
6.0
6.3
6.4
6.6
6.7
4.3
4.7
5.0
5.1
5.3
5.4
5.6
5.7
-
-
-
-
-
-
930
0.1
0.2
0.4
0.5
0.6
0.7
6.7
6.9
7.2
7.5
7.8
8.0
5.7
5.8
6.1
6.3
6.6
6.7
950
965
995
1015
1025
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
4.0
3.5
3.0
2.5
1.5
1.0
1.7
1.9
2.1
2.2
2.3
2.5
2.6
2.9
3.1
4.2
4.5
4.6
4.8
4.9
5.1
5.3
5.6
5.8
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
1.3
1.5
1.6
1.7
1.8
2.0
2.1
2.3
2.5
5.1
5.4
5.5
5.7
5.8
6.1
6.3
6.8
7.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
4.7
5.9
0.8
1.0
1.1
1.2
1.3
1.4
1.5
1.8
1.9
6.0
6.3
6.4
6.6
6.7
7.1
7.3
7.9
8.3
5.1
5.3
5.4
5.6
5.7
6.0
6.2
6.6
6.9
0.2
0.4
0.5
0.6
0.7
0.9
1.0
-
6.9
7.2
7.5
7.8
8.0
8.4
8.6
-
5.8
6.1
6.3
6.6
6.7
7.0
7.2
-
995
1015
1025
1050
1065
1100
1120
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
24
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 14: SUPPLY AIR BLOWER PERFORMANCE (20 TON) - GAS HEAT
240 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
8000
BHP
BLOWER
SPEED,
(RPM)
6000
BHP
7000
BHP
9000
BHP
9400
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
BHP
KW
208 VOLT AND STANDARD DRIVE
870
900
930
950
980
995
1015
6.0**
5.0
4.0
3.0
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
3.6
3.8
4.1
4.2
4.5
4.6
4.8
3.0
3.2
3.4
3.6
3.8
3.9
4.0
0.7
0.9
1.1
1.3
1.5
1.6
1.7
4.3
4.7
5.0
5.1
5.4
5.5
4.7
3.7
4.0
4.2
4.3
4.5
4.7
4.8
0.2
0.4
0.6
0.8
1.0
1.1
1.2
5.1
5.6
5.9
6.0
6.3
6.4
6.6
4.3
4.7
5.0
5.1
5.3
5.4
5.6
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.1
0.2
0.4
0.5
0.7
6.7
6.9
7.2
7.5
7.8
5.7
5.8
6.1
6.3
6.6
-
-
-
0.1
0.2
-
8.5
8.6
-
7.1
7.3
-
208 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
3.5
2.5
2.0
1.0
1.7
1.9
2.1
2.3
2.5
2.6
2.9
4.2
4.5
4.5
4.9
5.1
5.3
5.6
3.6
3.8
3.9
4.1
4.3
4.4
4.7
1.3
1.5
1.6
1.8
2.0
2.1
2.3
5.1
5.4
5.5
5.8
6.1
6.3
6.8
4.3
4.5
4.7
4.9
5.1
5.3
5.7
0.8
1.0
1.1
1.3
1.4
1.5
1.8
6.0
6.3
6.4
6.7
7.1
7.3
7.9
5.1
5.3
5.4
5.7
6.0
6.2
6.6
0.2
0.4
0.5
0.7
0.9
1.0
-
6.9
7.2
7.5
8.0
8.4
8.6
-
5.8
6.1
6.3
6.7
7.0
7.2
-
-
-
-
0.1
8.5
7.1
995
0.2
8.6
7.3
1025
1050
1065
1100
-
-
-
-
-
-
-
-
-
-
-
-
230/460/575 VOLT AND STANDARD DRIVE
870
900
6.0**
5.0
4.0
3.5
2.5
2.0
1.5
1.0
1.3
1.4
1.6
1.7
1.9
2.1
2.2
2.3
3.6
3.8
4.1
4.2
4.5
4.6
4.8
4.9
3.0
3.2
3.4
3.6
3.8
3.9
4.0
4.1
0.7
0.9
1.1
1.3
1.5
1.6
1.7
1.8
4.3
4.7
5.0
5.1
5.4
5.5
5.7
5.8
3.7
4.0
4.2
4.3
4.5
4.7
4.8
4.9
0.2
0.4
0.6
0.8
1.0
1.1
1.2
1.3
5.1
5.6
5.9
6.0
6.3
6.4
6.6
6.7
4.3
4.7
5.0
5.1
5.3
5.4
5.6
5.7
-
-
-
-
-
-
-
-
-
-
-
-
930
0.1
0.2
0.4
0.5
0.6
0.7
6.7
6.9
7.2
7.5
7.8
8.0
5.7
5.8
6.1
6.3
6.6
6.7
-
-
-
-
-
-
950
965
0.1
0.2
-
8.5
8.6
-
7.1
7.3
-
995
1015
1025
-
-
-
230/460/575 VOLT AND HIGH STATIC DRIVE
950
980
6.0
5.0
4.5
4.0
3.5
3.0
2.5
1.5
1.0
1.7
1.9
2.1
2.2
2.3
2.5
2.6
2.9
3.1
4.2
4.5
4.6
4.8
4.9
5.1
5.3
5.6
5.8
3.6
3.8
3.9
4.0
4.1
4.3
4.4
4.7
4.9
1.3
1.5
1.6
1.7
1.8
2.0
2.1
2.3
2.5
5.1
5.4
5.5
5.7
5.8
6.1
6.3
6.8
7.0
4.3
4.5
4.7
4.8
4.9
5.1
5.3
4.7
5.9
0.8
1.0
1.1
1.2
1.3
1.4
1.5
1.8
1.9
6.0
6.3
6.4
6.6
6.7
7.1
7.3
7.9
8.3
5.1
5.3
5.4
5.6
5.7
6.0
6.2
6.6
6.9
0.2
0.4
0.5
0.6
0.7
0.9
1.0
-
6.9
7.2
7.5
7.8
8.0
8.4
8.6
-
5.8
6.1
6.3
6.6
6.7
7.0
7.2
-
-
-
-
0.1
8.5
7.1
995
0.2
8.6
7.3
1015
1025
1050
1065
1100
1120
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
Johnson Controls Unitary Products
25
262260-YTG-E-1008
TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT
300 MBH - BOTTOM DUCT CONNECTIONS
MOTOR
PULLEY
(TURNS
OPEN)*
CFM
10000
BHP
BLOWER
SPEED,
(RPM)
7500
BHP
8750
BHP
11250
BHP
12500
BHP
ESP
KW
ESP
KW
ESP
KW
ESP
KW
ESP
KW
208 VOLT AND STANDARD DRIVE
975
6.0
5.0
4.0
3.0
2.0
1.0
0.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
5.0
0.7
0.9
1.1
1.3
1.6
1.8
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
6.3
6.7
7.0
7.3
7.6
8.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
-
-
-
-
-
-
0.2
0.4
0.6
0.8
1.0
9.7
10.2
10.6
11.1
11.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
-
-
-
-
-
0.2
13.5
11.0
208 VOLT AND HIGH STATIC DRIVE
1140
1180
1215
1255
1290
1330
1365
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.2
2.5
2.7
3.0
3.2
3.5
3.7
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
1.6
1.9
2.1
2.4
2.7
3.0
3.2
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
0.9
1.2
1.4
1.7
2.0
2.3
2.6
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.3
0.6
0.9
1.2
1.5
1.8
13.7
14.3
15.0
15.6
16.4
17.0
11.2
11.7
12.3
12.8
13.4
13.9
8.6
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.1
9.5
10.0
10.5
230/460/575 VOLT AND STANDARD DRIVE
975
6.0*
5.0
4.0
3.0
2.0
1.0
0.0
1.4
1.6
1.8
2.0
2.1
2.4
2.6
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
1.0
1.2
1.4
1.6
1.8
2.0
2.2
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
6.3
6.7
7.0
7.3
7.6
8.0
0.5
0.7
0.9
1.1
1.3
1.6
1.8
8.8
9.2
7.2
7.6
8.0
8.3
8.7
9.1
9.5
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
0.1
0.3
0.6
0.8
1.0
1.3
10.9
11.4
11.9
12.4
13.0
13.5
8.9
-
-
9.7
9.4
-
-
-
10.2
10.6
11.1
11.6
9.8
-
-
-
10.2
10.6
11.0
0.2
0.4
0.7
14.3
14.9
15.5
11.7
12.2
12.7
230/460/575 VOLT AND HIGH STATIC DRIVE
1140
1180
1215
1255
1290
1330
1365
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.4
2.7
2.9
3.2
3.4
3.7
3.9
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
2.1
2.3
2.6
2.9
3.1
3.4
3.7
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
1.6
1.9
2.2
2.5
2.7
3.0
3.3
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
1.1
1.4
1.7
2.0
2.2
2.6
2.9
13.1
13.7
14.3
15.0
15.6
16.4
17.0
10.7
11.2
11.7
12.3
12.8
13.4
13.9
0.5
0.8
1.1
1.4
-
15.0
15.8
16.4
17.2
-
12.3
12.9
13.5
14.1
-
8.6
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.1
9.5
10.0
10.5
-
-
-
-
-
-
NOTES: 1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.
15 HP Motor is required.
26
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 16: BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
1
ADJUSTABLE MOTOR PULLEY
FIXED BLOWER PULLEY
OUTSIDE PITCH
MOTOR
BLOWER
DRIVE RANGE
(RPM)
MODEL
SIZE
OUTSIDE PITCH
PITCH
LENGTH QTY.
(IN.)
EFF.
(%)
DESIG-
NATION
BORE DESIG-
(IN.) NATION
BORE DESIG-
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
DIA.
(IN.)
(IN.) NATION
Standard 850/1065
BK90
1-1/8
BK80
8.75
7.75
11.75
10.75
11.3
8.4
1
BX70
BX68
BX83
BX81
BX81
82.8
69.8
84.8
82.8
82.8
84.0
1
1
1
1
1
1
2
15 TON
5
184 T
83
89
1VP56
1VP68
5.35
6.75
4.3-5.3
High
965/1190
Static
7.4
1
Standard 870/1025
BK120
11.4
10.4
11.1
9.5
1-3/16
1-3/16
1-7/16
17.5 &
20 TON
2
2
7.5 213 T
1-3/8
5.5-6.5
5.5-6.5
High
950/1120
Static
BK110
Standard 950/1120 10 215 T 89.5
High
1VP68
6.75
7.5
1-3/8 1B5V110
25 TON
1140/1365 15 254 T
91
1VP75X
6.2-7.4 1-5/8 1B5V94
9.7
1-7/16 5VX840
Static
1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because
they are located in the moving air, upstream of any heating device.
2. Do NOT close this pulley below 1 turn open.
1
TABLE 17: STATIC RESISTANCES
RESISTANCE, IWG
CFM
DESCRIPTION
15 TON
17.5 TON
20 TON
25 TON
4500 6000 7200 6000 8000 9000 6000 7000 9400 7500 10000 12500
WET COIL
0.1
0.3
0.3
0.4
0.4
0.1
0.1
0.4
0.4
0.5
0.5
0.1
0.1
0.4
0.5
0.5
0.5
0.1
0.1
0.4
0.4
0.5
0.5
0.1
0.2
0.1
0.4
0.5
0.5
0.5
0.1
0.3
0.1
0.5
0.5
0.6
0.6
0.2
0.5
0.1
0.4
0.4
0.5
0.5
0.1
0.1
0.4
0.5
0.5
0.5
0.1
0.1
0.5
0.5
0.6
0.6
0.2
0.1
0.4
0.5
0.5
0.5
0.1
0.1
0.6
0.5
0.6
0.6
0.2
0.1
0.6
0.6
0.7
0.7
0.3
18kW
36kW
54kW
72kW
ELECTRIC HEAT
OPTIONS
(DH models only)
ECONOMIZER OPTION
HORIZONTAL DUCT CONNECTIONS2
0.1
0.2
0.3
0.2
0.3
0.5
0.3
0.5
0.6
1. Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for
Horizontal Duct Connections.
2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures
to the ESP values on the respective unit’s blower performance table.
TABLE 18: POWER EXHAUST PERFORMANCE
STATIC RESISTANCE OF RETRUN DUCTWORK, IWG
MOTOR
SPEED1
0.2
0.3
0.4
0.5
0.6
CFM
kW
CFM
kW
CFM
kW
CFM
kW
CFM
kW
HIGH2
MEDIUM
LOW
5250
4900
4400
0.83
0.77
0.72
4500
3900
3700
0.85
0.79
0.74
4200
3500
3000
0.88
0.82
0.78
3750
2900
-
0.93
0.85
-
3000
0.99
-
-
-
-
1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.
Johnson Controls Unitary Products
27
262260-YTG-E-1008
TABLE 19: DH 180, 210 & 240 ELECTRICAL DATA WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
BRKR1
SIZE
(AMPS)
90
ID
MIN.
CIRCUIT
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS AMPACITY
(AMPS)
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
--
13.5
27
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
70.9
70.9
109.7
156.9
166.2
70.5
37.5
74.9
112.7
150.2
--
43.3
86.6
129.9
173.2
--
21.7
43.3
65.0
86.6
--
17.3
34.6
52.0
69.3
--
37.5
74.9
112.7
150.2
--
43.3
86.6
129.9
173.2
--
21.7
43.3
65.0
86.6
--
17.3
34.6
52.0
69.3
--
37.5
74.9
112.7
150.2
--
43.3
86.6
129.9
173.2
--
21.7
43.3
65.0
86.6
--
17.3
34.6
52.0
69.3
90
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
21.8
21.8
11.0
9.6
184
184
90
4.5
4.3
2.2
1.7
4.5
4.3
2.2
1.7
4.5
4.3
2.2
1.7
12.8
12.8
6.4
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
110
175
200
90
40.6
54.1
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
13.5
27
40.6
54.1
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
13.5
27
40.6
54.1
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
70.5
90
124.3
145.9
189.2
35.6
35.6
62.1
73.0
94.6
30.2
30.2
125
175
225
45
45
70
80
110
35
35
50
DH180
(15)
73
5.2
49.8
58.5
75.8
86.6
70
90
110
110
125
175
200
110
110
150
175
225
50
50
70
90
110
40
86.6
25.6
25.6
12.8
10.2
32.1
32.1
14.3
12.9
190
190
95
20.0
20.0
10.0
7.5
118.7
165.9
175.2
86.2
86.2
133.3
154.9
198.2
43.2
43.2
66.6
77.5
99.1
33.9
33.9
DH210
(17 1/2)
40
60
70
90
75
52.7
61.3
78.7
101.2
101.2
118.7
165.9
175.2
100.8
100.8
133.3
154.9
198.2
46.6
46.6
66.6
77.5
99.1
39.9
39.9
52.7
61.3
125
125
125
175
200
125
125
150
175
225
60
60
70
90
110
50
237
237
130
85
20.0
20.0
10.0
7.5
DH240
(20)
18.0
36.0
54.0
72.0
50
60
70
90
78.7
NOTE 1: HACR Type per NEC.
28
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 20: DH 300 ELECTRICAL DATA STANDARD MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
150
150
150
200
200
150
150
150
175
225
70
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
120.5
120.5
128.7
175.9
185.2
118.1
118.1
140.8
162.4
205.7
56.1
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
43.3
86.6
129.9
173.2
-
208
230
460
575
37.1
37.1
17.2
12.4
239
239
125
80
4.5
4.3
2.2
1.7
28.0
26.0
13.0
10.0
0.0
0.0
0.0
0.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
21.7
43.3
65.0
86.6
-
17.3
34.6
52.0
69.3
56.1
70.4
81.2
70
80
90
102.9
41.3
41.3
110
50
50
18.0
36.0
54.0
72.0
1
2
2
2
55.8
64.5
81.8
60
70
90
NOTE 1: HACR Type per NEC.
TABLE 21: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
150
150
150
200
225
150
150
175
200
250
80
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
131.5
131.5
141.9
189.1
198.4
131.1
131.1
156.5
178.2
221.5
62.9
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
208
230
460
575
37.1
37.1
17.2
12.4
239
239
125
80
4.5
4.3
2.2
1.7
38.6
38.6
19.3
15.4
0.0
0.0
0.0
0.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
43.3
86.6
129.9
173.2
-
21.7
43.3
65.0
86.6
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
62.9
80
78.3
89.1
110.7
47.5
47.5
80
100
125
60
60
70
18.0
36.0
54.0
72.0
1
2
2
2
17.3
34.6
52.0
69.3
62.6
71.2
88.5
80
100
NOTE 1: HACR Type per NEC.
Johnson Controls Unitary Products
29
262260-YTG-E-1008
TABLE 22: DH 180, 210 & 240 ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
CIRCUIT
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
BRKR1
SIZE
(AMPS)
100
100
125
175
200
100
100
150
175
225
50
50
70
90
110
40
40
60
70
90
110
110
150
200
200
110
110
150
175
225
60
60
80
90
110
45
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS AMPACITY
(AMPS)
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
--
13.5
27
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
1
2
2
2
--
80.9
80.9
122.2
169.4
178.7
80.5
37.5
74.9
112.7
150.2
--
43.3
86.6
129.9
173.2
--
21.7
43.3
65.0
86.6
--
17.3
34.6
52.0
69.3
--
37.5
74.9
112.7
150.2
--
43.3
86.6
129.9
173.2
--
21.7
43.3
65.0
86.6
--
17.3
34.6
52.0
69.3
--
37.5
74.9
112.7
150.2
--
43.3
86.6
129.9
173.2
--
21.7
43.3
65.0
86.6
--
17.3
34.6
52.0
69.3
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
208-3-60
230-3-60
460-3-60
575-3-60
21.8
21.8
11.0
9.6
184
184
90
4.5
4.3
2.2
1.7
4.5
4.3
2.2
1.7
4.5
4.3
2.2
1.7
12.8
12.8
6.4
10.0
10.0
5.0
40.6
54.1
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
13.5
27
40.6
54.1
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
13.5
27
40.6
54.1
--
18.0
36.0
54.0
72.0
--
18.0
36.0
54.0
72.0
--
82.6
136.8
158.4
201.7
40.6
41.3
68.4
79.2
100.9
34.2
34.2
54.8
63.5
80.8
96.6
96.6
131.2
178.4
187.7
96.2
DH180
(15)
73
5.2
4.0
25.6
25.6
12.8
10.2
32.1
32.1
14.3
12.9
190
190
95
20.0
20.0
10.0
7.5
10.0
10.0
5.0
96.2
145.8
167.4
210.7
48.2
48.2
72.9
83.7
105.4
37.9
37.9
57.7
DH210
(17 1/2)
45
60
70
90
75
4.0
66.3
83.7
111.2
111.2
131.2
178.4
187.7
110.8
110.8
145.8
167.4
210.7
51.6
51.6
72.9
83.7
105.4
43.9
125
125
150
200
200
125
125
150
175
225
60
60
80
90
110
50
237
237
130
85
20.0
20.0
10.0
7.5
10.0
10.0
5.0
DH240
(20)
18.0
36.0
54.0
72.0
43.9
57.7
66.3
83.7
50
60
70
90
4.0
NOTE 1: HACR Type per NEC.
30
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 23: DH 300 ELECTRICAL DATA STANDARD MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
150
150
150
200
200
150
150
175
175
225
70
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
130.5
130.5
141.2
188.4
197.7
128.1
128.1
153.3
174.9
218.2
61.1
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
43.3
86.6
129.9
173.2
-
208
230
460
575
37.1
37.1
17.2
12.4
239
239
125
80
4.5
4.3
2.2
1.7
28.0
26.0
13.0
10.0
10.0
10.0
5.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
21.7
43.3
65.0
86.6
-
17.3
34.6
52.0
69.3
61.1
76.6
87.5
70
80
90
109.1
45.3
45.3
110
50
50
18.0
36.0
54.0
72.0
1
2
2
2
4.0
60.8
69.5
86.8
70
70
90
NOTE 1: HACR Type per NEC.
TABLE 24: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITH POWERED CONVENIENCE OUTLET
COMPRESSORS
HEATER OPTION
MAX.
FUSE/
ID
MIN.
MODEL
(TON-
OD FAN
MOTORS
FLA EACH
CONV
OUTLET
AMPS
BLOWER
MOTOR
FLA
CIRCUIT
AMPACITY
(AMPS)
BRKR1
SIZE
(AMPS)
175
175
175
225
225
175
175
175
225
250
80
VOLTAGE
RLA
LRA
MODEL KW STAGES AMPS
EACH
EACH
NAGE)
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
None
E18
E36
E54
E72
-
-
-
141.5
141.5
154.4
201.6
210.9
141.1
141.1
169.0
190.7
234.0
67.9
13.5
27.0
40.6
54.1
-
1
2
2
2
-
37.5
74.9
112.7
150.2
-
208
230
460
575
37.1
37.1
17.2
12.4
239
239
125
80
4.5
4.3
2.2
1.7
38.6
38.6
19.3
15.4
10.0
10.0
5.0
18.0
36.0
54.0
72.0
-
1
2
2
2
-
43.3
86.6
129.9
173.2
-
21.7
43.3
65.0
86.6
-
300
(25)
18.0
36.0
54.0
72.0
-
1
2
2
2
-
67.9
80
84.5
95.3
117.0
51.5
51.5
90
110
125
60
60
70
18.0
36.0
54.0
72.0
1
2
2
2
17.3
34.6
52.0
69.3
4.0
67.6
76.2
93.5
90
100
NOTE 1: HACR Type per NEC.
Johnson Controls Unitary Products
31
262260-YTG-E-1008
1
TABLE 26: ELECTRIC HEAT CORRECTION
FACTORS
TABLE 25: DH VOLTAGE LIMITATIONS
VOLTAGE
POWER SUPPLY
kW CAP. MULTI-
PLIER
MIN.
MAX.
NOMINAL VOLTAGE
VOLTAGE
208/230-3-60
187
253
208
230
460
575
1.00
0.92
0.92
0.92
208
240
480
600
414
518
506
506
460-3-60
575-3-60
1. Utilization Range “A” in accordance with ARI Standard
110.
CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT1
TERMINALS
UNIT TERMINAL
BLOCK 1TB2
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT1
R
RH
RC
Y1
Y2
TERMINALS
Y1
Y2
W1
UNIT TERMINAL
BLOCK 1 TB2
RC
RH
R
ADD
JUMPER
W2
G
Y1
Y2
Y1
Y2
ADD
JUMPER
W1
W2
B
W1
W2
G
W1
W2
24 VOLT
TRANSFORMER
X
3
3
A1
A2
Y3
G
G
B
X
B
124 Volt Thermostat 2TH04701024 or 2TH04701524
(with Subbase 2TB04700324).
LED1
24 VOLT
TRANSFORMER
LED2
4
A1
A2
NOT USED
2Terminal strip 1TB - located on relay board in 24-volt section
of the unit control box.
4
COM
A1
3Second stage heating is not required on units with a single stage
electric heater.
ADD
JUMPER
A2
T
POWER WIRING
T
L1
Refer to the
TO REMOTE SENSOR
2THO4702224 IF USED
LINE VOLTAGE
TERMINAL
BLOCK 2TB
ELECTRICAL DATA
tables to size the
power wiring, the
fuses and the
L2
L3
1Electronic programmable thermostat 2ET04700224 (includes subbase).
2Terminal block 1TB- located on relay board in 24-volt section of the unit control box.
3Second stage heating is not required on units with a single stage electric heater.
4Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers
when the thermostat switches to the set-back position.
IN CONTROL BOX
disconnect switch.
GROUND LUG
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.
FIGURE 3 - TYPICAL DH FIELD WIRING DIAGRAM
32
Johnson Controls Unitary Products
262260-YTG-E-1008
TABLE 27: PHYSICAL DATA
DH
MODELS
Centrifugal Blower (Dia. x Wd. in.)
180
210
18 x 15
7.5
4
240
18 x 15
7.5
4
300
18 x 15
10/15
4
15 x 15
EVAPORATOR
BLOWER
Fan Motor HP Standard/Hi Static
Rows Deep
5
4
13.5
15.5
30
EVAPORATOR
COIL
Fins Per Inch
13.5
20.0
30
13.5
20.0
30
13.5
25.0
30
Face Area (Sq. Ft.
Propeller Dia. (in.) (Each)
Fan Motor Hp (Each)
Nom. CFM (Each)
CONDENSER
FANS
1
1
1
1
(Two Per Unit)
5765
3
7000
3
7000
3
7200
2
Rows Deep (Each)
CONDENSER
COILS
Fins Per Inch (Each)
13
15
15
20
(Two Per Unit)
Face Area (Sq. Ft.) (Total)
7.5 Ton Scroll
36.0
2
43.3
2
43.3
-
43.3
-
COMPRESSOR
(Qty. Per Unit)
10 Ton Scroll
-
-
2
-
12.5 Ton Scroll
-
-
-
2
Quantity Per Unit (16” X 20” X 2” or 4“)
Quantity Per Unit (16” X 25” X 2” or 4“)
Quantity Per Unit (18” X 24” X 2” or 4“)
Total Face Area (sq. ft.)
-
4
4
4
-
4
4
4
AIR
FILTERS
5
-
-
-
15.0
23/10
21/10
20.0
24/0
24/8
20.0
24/2
27/2
20.0
21/1
21/1
System #1
System #2
Refrigerant 22
(lbs./oz.)
CHARGE
TABLE 28: OPERATING WEIGHTS (LBS.)
MODEL SIZE
15 TON
17.5 TON
20 TON
2100
25 TON
2345
DH (Cooling Only)
1900
2100
2140
1950
2150
2190
BASIC
UNIT
240Mbh
2300
2545
DH
(Gas/Electric)
320Mbh
2340
2585
Economizer
160
Economizer with
Power Exhaust
245
Motorized Damper
150
25
30
35
40
10
18kW
36kW
54kW
72kW
OPTIONS
Electric Heater
(DH only)
Hot Gas Bypass
Supply Fan VFD
Roof Curb
185
175
185
185
Barometric Damper
45
55
Economizer/Motorized Damper Rain Hood
Economizer/Power Exhaust Rain Hood
Wood Skid
ACCY.
90
220
TABLE 29: SUPPLY FAN VFD WEIGHTS, IN LBS.
SUPPLY FAN MOTOR
230V
460V
575V
W/O MANUAL BYPASS
25
30
30
30
25
30
30
30
30
30
35
40
5.0 hp
7.5 hp
10.0 hp
15.0 hp
W/MANUAL BYPASS
5.0 hp
30
35
35
40
30
35
35
35
35
35
40
45
7.5 hp
10.0 hp
15.0 hp
Johnson Controls Unitary Products
33
262260-YTG-E-1008
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
BLOWER ACCESS
(Location Of
Optional VFD)
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER MOTOR ACCESS
(Location Of Optional
VFD Bypass)
COMPRESSOR
ACCESS
(See detail "X")
BLOWER
COMPARTMENT
ACCESS
OPTIONAL COIL
GUARD KIT
(Auxiliary)
DOT PLUG
(For pressure
Drop Reading)
48-5/8" (15 Ton)
52-5/8" (17.5 thru 25 Ton)
ELECTRIC
GAS HEAT
ACCESS
CONDENSER
COILS
VENT AIR
OUTLET
HOODS
21"
5"
7-1/8"
COMBUSTION
AIR INLET
HOOD
6-3/8"
9-3/4"
92"
(C)
5-7/8"
(A)
GAS SUPPLY
ENTRY
CONTROL WIRING
ENTRY
46-5/8"
CONTROL BOX
ACCESS
11-1/2"
(B)
35"
POWER WIRING
ENTRY
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
FRONT
VIEW
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
RETURN
AIR
3-3/4"
33"
SUPPLY
AIR
2-3/4"
21-1/2"
11-1/8"
OUTDOOR AIR
(Economizer)
UNIT BASE WITH RAILS
(B)
(D)
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations
All dimensions are in inches. They are
subject to change without notice. Certi-
fied dimensions will be provided upon
request.
POWER WIRING
ENTRY
GAS SUPPLY
ENTRY
(A)
CONTROL WIRING
ENTRY
8-1/8"
9-3/4"
NOTE:
46-5/8"
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
9-1/4"
12-1/2"
FIGURE 4 - UNIT DIMENSIONS DH180, 210, 240 & 300 (FRONT VIEW)
TABLE 30: UTILITIES ENTRY DATA
OPENING SIZE
HOLE
USED FOR
(DIA.)
1-1/8” KO
Side
A
Control Wiring
3/4” NPS (Fem.)
3-5/8” KO
Bottom
Side
Bottom
1
Power Wiring
B
3” NPS (Fem.)
C
D
2-3/8” KO
Gas Piping (Front)
,
2
1-11/16” Hole
Gas Piping (Bottom)
1. One-inch gas piping NPT required.
2. Opening in the bottom of the unit can be located by the slice in
the insulation.
NOTE: All entry holes should be field sealed to prevent rain
water entry into the building.
34
Johnson Controls Unitary Products
262260-YTG-E-1008
EVAPORATOR
SECTION
DOT PLUG
(For pressure
drop reading)
40-3/8"
FILTER
ACCESS
SUPPLY
AIR
RETURN
AIR
COMPRESSOR
ACCESS
OUTDOOR
AIR
40-1/2"
SUPPLY AIR
ACCESS
18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION
27-3/4"
Dimensions listed are for side
5-1/8"
RETURN AIR
ACCESS
duct flange openings; see
Field Accessories for Side
Duct Flange Kit.
OUTDOOR AIR
COMPARTMENT
ACCESS
28-5/8” (15 TON)
39-5/8"
(17.5 thru 25 TON)
REAR
VIEW
FIGURE 5 - REAR VIEW DIMENSIONS
NOTE:Units are shipped with the bottom duct openings
covered. An accessory flange kit is available for
connecting side ducts.
For bottom duct applications:
For side duct applications:
1. Remove the side panels from the supply and return air
compartments to gain access to the bottom supply and
return air duct covers.
1. Replace the side panels on the supply and return air
compartments with the side duct flange accessory kit
panels.
2. Remove and discard the bottom duct covers. Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.
2. Connect ductwork to the flanges on those panels.
3. Replace the side supply and return air compartment
panels.
Johnson Controls Unitary Products
35
262260-YTG-E-1008
NOTE: ELEC / ELEC Models: Units and ductwork are
approved for zero clearance to combustible material
when equipped with electric heaters.
TABLE 31: MINIMUM CLEARANCES
LOCATION
CLEARANCE
36”
Front
24” (Less Economizer)
49” (With Economizer)
Rear
GAS / ELEC Models: A 1” clearance must be
provided between any combustible material and the
supply air ductwork for a distance of 3 feet from the
unit.
24” (Less Economizer)
Left Side (Filter Access)
Right Side (Cond. Coil)
3
36” (With Economizer)
36”
0”
1
Below Unit
The products of combustion must not be allowed to
accumulate within a confined space and recirculate.
72” With 36” Maximum
Horizontal Overhang (For
Condenser Air Discharge)
2
Above Unit
Locate unit so that the vent air outlet hood is at least:
1. Units may be installed on combustible floors made from wood or
class A, B, or C roof covering material.
• Three (3) feet above any force air inlet located
within 10 horizontal feet (excluding those integral to
the unit).
2. Units must be installed outdoors. Overhanging structures or
shrubs should not obstruct condenser air discharge outlet.
3. If economizer is factory installed, the unassembled rain hood
must be removed from its ride along position in front of evapora-
tor coil, or in the outdoor air compartment, prior to final installa-
tion.
• Four (4) feet below, four horizontal feet from, or one
foot above any door or gravity air inlet into the
building.
• Four (4) feet from electric and gas meters,
regulators and relief equipment.
ECONOMIZER
MOTORIZED
DAMPER
POWER EXHAUST
RAIN HOOD
(on Return Air Compartment)
SUPPLY AIR
RAIN HOOD
(on Outdoor Air Compartment)
COMPARTMENT
ECONOMIZER / MOTORIZED DAMPER
AND POWER EXHAUST RAIN HOODS
FIXED
OUTDOOR AIR
INTAKE HOOD
(located on
Return Air
Compartment)
36-5/8”
1“ CONDENSATE
DRAIN
(Must be trapped)
16-1/8”
5”
28-3/16”
92”
REAR VIEW
LH VIEW
DETAIL “Y”
UNIT WITH RAIN HOODS
FIGURE 6 - UNIT DIMENSIONS DH180, 210, 240 & 300 (RAINHOOD)
36
Johnson Controls Unitary Products
262260-YTG-E-1008
(17.5, 20 & 25 Ton)
FIGURE 7 - UNIT CENTER OF GRAVITY
FIGURE 8 - TYPICAL UNIT APPLICATIONS
Johnson Controls Unitary Products
37
262260-YTG-E-1008
E
B
F
C
D
A
A
C
F
R
O
N
T
F
R
O
N
T
FIGURE 9 - UNIT 4 POINT LOAD
FIGURE 10 - UNIT 6 POINT LOAD
TABLE 32: DH 180, 210, 240 & 300 4 POINT LOAD WEIGHT DISTRIBUTION
OPERATING
UNIT MODEL
WEIGHT
(lb)
A
B
C
D
DH180C00
DH180N24
DH180N32
DH210C00
DH210N24
DH210N32
DH240C00
DH240N24
DH240N32
DH300C00
DH300N24
DH300N32
1900
2100
2140
1950
2150
2190
2100
2300
2340
2345
2545
2585
445
492
501
457
504
513
492
539
548
461
501
509
484
535
545
497
548
558
535
586
596
502
545
553
506
559
570
519
572
583
559
612
623
720
781
794
465
514
524
477
526
536
514
563
573
662
718
729
TABLE 33: DH 180, 210, 240 & 300 6 POINT LOAD WEIGHT DISTRIBUTION
OPERATING
UNIT MODEL
WEIGHT
(lb)
A
B
C
D
E
F
DH180C00
DH180N24
DH180N32
DH210C00
DH210N24
DH210N32
DH240C00
DH240N24
DH240N32
DH300C00
DH300N24
DH300N32
1900
2100
2140
1950
2150
2190
2100
2300
2340
2345
2545
2585
293
324
330
300
331
337
324
354
360
303
329
334
306
338
344
314
346
352
338
370
377
321
348
353
323
357
364
332
366
372
357
391
398
339
368
374
342
378
385
351
387
394
378
414
421
487
528
537
327
362
369
336
370
377
362
396
403
460
499
507
309
342
348
317
350
357
342
374
381
435
472
479
38
Johnson Controls Unitary Products
262260-YTG-E-1008
(17.5 thru
25 Ton)
(17.5 thru
25 Ton)
FIGURE 11 - UNIT ROOF CURB DIMENSIONS
(17.5 & 20 Ton)
FIGURE 12 - ROOF CURB DUCT OPENINGS
DIMENSIONS
FIGURE 13 - CUT AWAY OF ROOF CURB
1. The 2” space between the ducts allows for “jumping” an
existing roof joist.
2. The 58-1/2” overall dimension of the ducts allows
ductwork penetration between roof joists that are
spaced on 72” centers.
NOTE: Ducts can be installed into the curb from the roof. All
electrical and gas line connections can be made
inside the curb.
Johnson Controls Unitary Products
39
262260-YTG-E-1008
FIGURE 14 - TYPICAL ROOFTOP INSTALLATION
THERMOSTAT
TERMINALS
CONTROL
TERMINAL
BLOCK
W1
W1
W2
Y1
G
1
W2
Y1
2
Y2
OCC
P
P1
Y2
X
G
R
C
Smoke
Detector
R
SD
C
Jumper 3
R
SD
SD
C
4
RC
5
OCC
24 VAC
Class 2
6
X
TERMINALS ON
A LIMITED
NUMBER OF
THERMOSTATS
1
Second stage heating not required on single stage heating units.
2
Second stage cooling not required on single stage cooling units.
3
Jumper is required if there is no Smoke Detector circuit.
4
Jumper is required for any combination of R, RC, or RH.
5
OCC is an output from the thermostat to indicate the Occupied condition.
X is an input to the thermostat to display Error Status conditions.
6
®
FIGURE 15 - TYPICAL S IMPLICIT Y CONTROL WIRING DIAGRAM
40
Johnson Controls Unitary Products
262260-YTG-E-1008
supply/return, and be available with factory installed options
or field installed accessories. The units shall be factory
wired, piped, charged with R-22 refrigerant and factory
tested prior to shipment. All unit wiring shall be both num-
bered and color coded. All units shall be manufactured in a
facility certified to ISO 9001 standards and the cooling per-
formance shall be rated in accordance with DOE and ARI
test procedures. Units shall be CSA listed, classified to
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-M90
conditions.
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by Unitary Products in an ISO
9001 certified facility.
York's Sunline Ultra™ units are convertible single package
units. All models have dual independent refrigerant circuits
for efficient part load operation and maximum comfort con-
trol. Although the units are primarily designed for curb
mounting on a roof, they can also be slab-mounted at
ground level or set on steel beams above a finished roof.
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factory-
mounted options and field-installed accessories to make
them suitable for almost every application. All units are self-
contained and assembled on full perimeter base rails with
holes in the four corners for overhead rigging. Every unit is
completely piped, wired, charged and tested at the factory
to simplify the field installation and to provide years of
dependable operation. All models (including those with an
economizer) are suitable for either bottom or horizontal duct
connections. Models with power exhaust are suitable for
bottom duct connections only. For bottom duct, remove the
sheet metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, replace the
supply and return air panels on the rear of the unit with a
side duct flange accessory. All supply air blowers are
equipped with a belt drive that can be adjusted to meet the
exact requirements of the job. A high static drive option is
available for applications with a higher CFM and/or static
pressure requirement.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel, with
exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hour salt spray test per ASTM-
B117 standards. Indoor blower section shall be insulated
with a minimum 1/2" thick insulation, coated on the airside.
Aluminum foil faced insulation shall be used in the furnace
compartment and be fastened with ridged fasteners to pre-
vent insulation from entering the air stream. Cabinet panels
shall be "large" size, easily removable for servicing and
maintenance. Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 2" fil-
ters shall be furnished and be accessible through a remov-
able access door, sealed airtight. Units filter track shall be
designed to accommodate either 2" or 4" filters. Fan perfor-
mance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evapora-
tor fan performance without removing panels or creating air
by-pass of the coils. Condensate pan shall be internally
sloped and conform to ASHRAE 62-89 self-draining stan-
dards. Condensate connection shall be a minimum of 1" I.D.
female and be a ridged mount connection. Unit shall incor-
porate a fixed outdoor air damper with an outdoor air intake
opening covered with a bird screen and a rain hood painted
to match the exterior of the unit.
Each unit shall have 2 condenser fan motors. All compres-
sors include crankcase heat and internal pressure relief.
Every refrigerant circuit includes an expansion valve, a liq-
uid line filter-drier, a discharge line high pressure switch and
a suction line with a freezestat and low pressure/loss of
charge switch. The unit control circuit includes a 75 VA
transformer, a 24-volt circuit breaker and a relay board with
two compressor lockout circuits, a terminal strip for thermo-
stat wiring, plus an additional set of pin connectors to sim-
plify the interface of additional field controls. All models are
CSA approved. All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater ele-
ments carry an additional 4-year warranty. Aluminized steel
tubular heat exchangers carry an additional 9-year warranty.
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable-
pitch motor pulley. Job site selected (B.H.P.) brake horse-
power shall not exceed the motors nameplate horsepower
rating, plus the service factor. Units shall be designed not to
operate above service factor. Fan wheel shall be double-inlet
type with forward-curved blades, dynamically balanced to
operate smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
DESCRIPTION
A variable air volume (VAV) option using a variable frequency
drive (VFD) is available for applications requiring a constant
supply duct static pressure. Units equipped for VAV shall be
controlled by a duct pressure transducer with a 0 - 5” WC pres-
sure range. The pressure transducer shall provide a 0 - 5 VDC
output signal to a VAV control board which, in turn shall provide
a 2 - 10 VDC speed reference signal to the VFD. The VAV
control board shall operate using factory-installed Supply
Air, Return Air and Outside Air Temperature Sensors. Units
equipped with VFD’s shall have factory-installed manual
bypass as an option.
Units shall be factory-assembled, single packaged, DH***N
Electric Cooling/Gas Heat, DH***C/E Electric Cooling/
Optional Electric Heat, designed for outdoor mounted instal-
lation. The 15 ton units shall have minimum EER ratings of
10.8, the 17.5 ton units shall have minimum EER ratings of
10.2, the 20 ton units shall have minimum EER ratings of 9.7
and the 25 ton units shall have minimum EER ratings of 9.6.
They shall have built-in field convertible duct connections
for down discharge supply/return or horizontal discharge
Johnson Controls Unitary Products
41
262260-YTG-E-1008
OUTDOOR (CONDENSER) FAN ASSEMBLY
2. Freeze-protection thermostat, evaporator coil. If
any of the above safety devices trip, a LED
(light-emitting diode) indicator shall flash a
diagnostic code that indicates which safety
switch has tripped.
The outdoor fans shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to cor-
rosion resistant steel spider brackets and shall be dynami-
cally balanced for smooth operation. The 2 outdoor fan
motors shall be totally enclosed with permanently lubricated
bearings, internally protected against overload conditions and
staged independently.
d. Unit shall incorporate "AUTO RESET" compressor
over temperature, over current protection.
e. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
REFRIGERANT COMPONENTS
Compressors:
f. Unit control board shall have on-board diagnostics
and fault code display.
a. Shall be Scroll compressors internally protected with
internal high-pressure relief and over temperature
protection.
g. Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0 °F.
b. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent mounting.
h. Control board shall monitor each refrigerant safety
switch independently.
Coils:
i.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
GAS HEATING SECTION (DH***N MODELS)
Shall be designed with induced draft combustion with post
purge logic and energy saving direct spark ignition, redun-
dant main gas valve. Ventor wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25° F. Burners shall be of the in-
shot type, constructed of aluminum coated steel and contain
air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
b. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Balance-port thermostatic expansion valve with
independent circuit feed system.
b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft motor speed sensor.
d. The refrigeration system shall provide at least 15° F
of sub-cooling at design conditions.
c. Flame roll out switch (automatic reset).
e. All models shall have two independent circuits.
d. Flame proving controls. Unit shall have two inde-
pendent stages of capacity.
f. Hot gas bypass option shall be factory-installed on
compressor #1 discharge line to provide cooling in
low-load applications. HGBP shall be a standard
feature on VAV models and an optional feature on
CV models.
ELECTRIC HEATING (DH***C/E MODELS)
Nickel chromium electric heating elements shall be provided
as required by the application with 1 or 2 stage control, as
required, from 13.5 KW to 72 KW capacities. The heating
section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating
at an excessive temperature. Units with Electric Heating shall
be wired for a single point power supply with branch circuit
fusing (where required).
UNIT CONTROLS
a. Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125° F
outdoor temperature, exceeding maximum load criteria of
ARI Standard 340/360. The compressor, with standard
c. Loss-of-charge/Low-pressure switch.
1. High-pressure switch.
42
Johnson Controls Unitary Products
262260-YTG-E-1008
controls, shall be capable of operation down to 0° F outdoor
temperature. Unit shall be provided with fan time delay to
prevent cold air delivery before heat exchanger warms up
(Gas heat only).
cooling shall modulate the economizer in order to main-
tain a supply air temperature (SAT) programmable set-
point. With the use of a field-installed indoor air quality
sensor, the controller shall provide Demand Ventilation
by modulating the economizer dampers to allow more
ELECTRICAL REQUIREMENTS
outside airflow upon detection of elevated indoor CO
2
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
concentrations above a programmable set-point. With an
additional field-installed outdoor air quality sensor, Differ-
ential Demand Ventilation shall be provided.
The outdoor intake opening shall be covered with a rain
hood that matches the exterior of the unit. Water elimina-
tor/filters shall be provided.
STANDARD LIMITED WARRANTIES
•
•
•
•
Compressor 5 Years
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers shall
not exceed 2% when dampers are fully closed and operat-
ing against a pressure differential of 0.5 IWG. A unit-
mounted potentiometer shall be provided to adjust the
outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation require-
ments of the conditioned space during normal operation.
Whenever the indoor fan motor is energized, the dampers
open up to one of two pre-selected positions - regardless
of the outdoor air enthalpy. Dampers return to the fully
closed position when the indoor fan motor is de-ener-
gized. Dampers shall fully close on power loss.
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully
close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14" high, full perimeter curb with wood
nailer (shipped knocked-down).
•
100% BAROMETRIC RELIEF DAMPER - Contains a
rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure
through the unit.
•
•
•
•
•
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
•
BAS-READY ECONOMIZER - Outdoor and return air
dampers that are interlocked and positioned by a fully-
modulating, spring return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG.
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
BURGLAR BARS - Designed to work with above roof
curbs, depending on unit model. Fits duct openings of
curb supply and return air openings.
For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, free-cooling shall be available while the
outdoor dry bulb temperature (OAT) remains below a
programmable set-point of the controller. Field-installed
humidity sensors for either outdoor air or outdoor &
return air streams are available to provide free-cooling
based on single-enthalpy or dual-enthalpy configura-
tions, respectively. If free-cooling is available, a call for
SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on units
with power exhaust.
Johnson Controls Unitary Products
43
•
HIGH STATIC DRIVE - May include a belt, blower pulley,
motor pulley or a motor change to enhance blower per-
formance.
•
•
•
•
•
•
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
•
•
WOOD SKID - Allows unit to be handled with 90" forks.
POWERED GFI CONVENIENCE OUTLET
NON-POWERED GFI CONVENIENCE OUTLET
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD -
Contains all hood panels and the hardware for assem-
bling.
®
BAS CONTROLS - S implicity Intelli-Comfort™, CPC,
JOHNSON, HONEYWELL, NOVAR, YORK COMMER-
CIAL COMFORT SYSTEM (YCCS)
•
•
ANTI-RECYCLE TIMER - Assures 5-minute off time
between compressor cycles.
•
•
HINGED FILTER DOOR ACCESS AND TOOL FREE
ACCESS PANELS
COIL GUARD KIT - Guard for cooling coil.
OTHER FACTORY INSTALLED OPTIONS
HINGED TOOL FREE BLOWER, BLOWER MOTOR,
FILTER AND ELECTRICAL ACCESS PANELS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
•
•
•
•
•
HIGH STATIC DRIVE
•
•
•
STAINLESS STEEL HEAT EXCHANGER
STAINLESS STEEL DRAIN PAN
2" THROW AWAY FILTERS
4" PLEATED FILTERS
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
DISCONNECT SWITCH
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
Subject to change without notice. Printed in U.S.A.
262260-YTG-E-1008
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.
Supersedes: 262260-YTG-D-0708
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
|