York D2eb030 User Manual

360101-XTG-B-0508  
®
DESCRIPTION  
TECHNICAL GUIDE  
AFFINITY™ SERIES  
These packaged cooling air conditioners are designed for  
outdoor installation. Only utility and duct connections are  
required at the point of installation.  
Field-installed electric heater accessories are available to  
provide electric heat combined with electric cooling.  
SINGLE PACKAGE  
COOLING UNITS  
STANDARD FEATURES / BENEFITS  
OPERATING EFFICIENCY - All units provide high operating  
D2EB030 THRU 060  
2.5 THRU 5 TON  
8.8 - 9.4 EER  
efficiencies and have a minimum EER of 8.8 or above.  
ON SITE FLEXIBILITY - All model sizes share a common,  
compact design cabinet with a single footprint. The installer has  
the flexibility of setting one curb and placing the proper tonnage  
unit on that curb after the internal load has been determined.  
Field convertible duct connections from side shot to down shot  
allows the installer to have greater flexibility and needs to carry  
less inventory.  
EXPORT ONLY  
LOWER INSTALLATION COST - Installation time and costs  
are reduced by easy power and control wiring connections. The  
small base dimension means less space is required on the  
ground or roof, plus, the installer can fit this unit between the  
wheel wells of full size pick-up truck. All models are well under  
400 pounds.  
All units are completely wired, charged with R-22 and tested  
prior to shipment. Unique test stations using a new state of the  
art computerized process system are used to insure product  
quality. Refrigerant charge, and component part numbers are  
verified via computers at installation. Vital run test statistics  
such as system pressure, motor currents, air velocity and  
temperature and unit vibration are monitored and recorded by  
the system to insure unit performance.  
Equal size, side supply and return duct connections allows easy  
hook-up of ducts to match low crawl spaces without transition  
pieces.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
   
360101-XTG-B-0508  
CONDENSER COIL GRILLE - A multi-piece totally enclosed,  
rigidly mounted condenser coil grille provides protection from  
objects and personal after installation and provides protection  
during transit and installation.  
STANDARD FEATURES/BENEFITS (CONT.)  
UTILITY CONNECTIONS MADE EASY - Electrical utility  
knockouts are provided through the bottom as well as the side  
of the unit. Utility connections can be made quickly and with a  
minimum amount of field labor. A field supplied and field  
installed electrical disconnect switch must be installed.  
LOW OPERATING SOUND LEVEL - The upward air flow carries  
the normal operating noise up and away from the living area. The  
rigid top panel effectively isolates any motor sound. Isolator  
mounted compressor and the rippled fins of the condenser coil  
muffle the normal fan motor and compressor operating sounds.  
The unique formed base pan also aids in sound alterations with it's  
“Super-Structure” design. This design strategically places  
embossments in the pan for optimum strength and rigidity.  
CONVERTIBLE AIRFLOW DESIGN - The bottom duct  
openings are covered when they leave the factory ready to be  
used for a side supply / side return application. If a bottom supply  
/ bottom return application is desired, you simply remove the two  
panels from the bottom of the unit and place them in the side  
supply / side return duct openings. No panel cutting is required  
and no accessory panel is necessary. Convertible airflow design  
allows maximum field flexibility and minimum inventory.  
FAN SYSTEM - All models operate over a wide range of design  
conditions with a 3-speed direct-drive fan motor. These units  
easily match all types of applications and provides greater on  
site flexibility to match comfort requirement.  
CONDENSATE PAN - A non-corrosive, long-lasting, water-tight  
pan is positioned below the evaporator coil to collect and drain  
all condensate. Less collection of stagnate condensate will  
build-up. The condensate pan conforms to ASHRAE 62-89  
standards (Ventilation for Acceptable Indoor Air Quality).  
SIMPLE CONTROL CIRCUIT - A low voltage printed circuit  
board contains a low voltage terminal strip. The electrical  
control box is not located in the compressor compartment. All  
wiring internal to the unit is color/number coded.  
CONDENSATE DRAIN - The heavy duty, 3/4 inch NPTI copper  
connection is more tolerable during installation and is more  
durable over time. The connection is rigidly mounted to assure  
proper fit and leak tight seal.  
PROTECTED COMPRESSOR - The compressor is internally  
protected against high pressure and temperature. This is  
accomplished by the simultaneous operation of high pressure  
relief valve and a temperature sensor which protect the  
compressor if undesirable operating conditions occur.  
DURABLE FINISH - With a heavy duty cabinet made of powder-  
painted, galvanized steel the neutral color blends into  
EXCLUSIVE COIL DESIGN - Grooved copper tubes and  
enhanced aluminum fin construction improves heat transfer for  
maximum efficiency and durability.  
surrounding areas. The powered paint, provides a better paint to  
steel bond, which resists corrosion and rust creep. The special  
primer formulas and glossy earth tone finish insure less fading  
when exposed to sunlight and offers a more attractive on site  
appearance. This paint finish exceeds ASTM-B117 standards for  
1000 hours salt spray rating, the highest in the industry.  
LOW MAINTENANCE - Long life, permanently lubricated  
condenser and evaporator fan motor bearings need no annual  
maintenance adding greater reliability to the unit. Blower  
assembly can be easily removed for cleaning by the unique  
“Slip- Track” slide-out blower assembly.  
FULL PERIMETER BASE RAILS - The easily removable base  
rails provide a solid foundation for the entire unit and protects  
the unit during shipment. The rails provide fork lift access from  
all sides, and rigging holes are also provided so that an  
overhead crane can be used to place the units on a roof. On  
applications when the unit is placed on a pad, the base will  
keep the unit off the pad to deter corrosion. On applications  
where height is limited, the 2-3/8 inch high base rails may be  
removed on location.  
SECURED SERVICE ACCESS PORTS - Protected, externally  
mounted, re-usable service access ports are provided on both  
the high and low lines for ease of evacuating and charging the  
system. No final field mounting required.  
EASY SERVICE ACCESS - A large, single panel covers the  
electrical controls and makes servicing easy. The blower  
compartment has an additional large panel with a built-in  
handle tab. Removing this panel will allow the blower assembly  
to slide-out for easy removal for maintenance and ease of  
trouble shooting.  
MORE ATTRACTIVE APPEARANCE - A single piece “Water  
Shed” top cover containing a top discharge condenser fan  
arrangement requires less square footage on installation and  
provides a wider variety of installations. The one piece design  
adds greater water integrity. Rounded corners with water drip  
edges add to the attractive appearance. The cabinet panels  
have a non-fibrous insulation that does not add insulation fibers  
into conditioned area.  
REPLACEMENT PARTS - The installer has no need to carry  
an inventory of unique parts or needs special training to replace  
any of the components parts for these units. All are easily  
obtained from Source 1 or other part houses.  
TOP DISCHARGE - The top discharge condenser fan does not  
disrupt neighboring areas and does not dry-out vegetation  
surrounding the unit. The warm air from the top mounted fan is  
blown up away from the structure and any landscaping. This  
allows compact location on multi-unit applications.  
FIELD-INSTALLED ACCESSORIES  
ECONOMIZER DOWN DISCHARGE / SUPPLY KIT -  
Modulating integrated economizer provides simultaneous  
operation between the mechanical cooling and economizer  
Johnson Controls Unitary Products  
3
 
360101-XTG-B-0508  
operation. Independent blade design insures proper control and  
less than 1% leak rate. Includes hood and mesh bird screen  
filter integrated into the hood, dry bulb sensor and relief  
damper. Separate field accessories of single enthalpy and dual  
enthalpy are also available.  
MOTORIZED FRESH AIR DAMPER - Designed for duct  
mounted side return and unit mounted down shot return  
applications. Damper capable of providing 0% thru 50% of  
outdoor air (field supplied). Closes on power loss, includes  
hood and screen assembly.  
SINGLE ENTHALPY SENSOR - Sensor replaces dry bulb  
sensor standard in economizer kit. Provides improved  
economizer operation by sensing the dry bulb temperature from  
outdoors plus the enthalpy content of the outdoor air.  
RECTANGLE TO ROUND ADAPTERS - Kit includes one  
supply and one return air rectangle to round duct adapter.  
Adapters are preformed and designed to fit over current duct  
openings on the base unit. Transition is from 15” square to 14”  
round.  
DUAL ENTHALPY SENSOR - Additional sensor to single  
enthalpy sensor. Sensor senses both the return air temperature  
dry bulb and humidity in conjunction with the single enthalpy to  
determine the most economical mix. Single Enthalpy sensor  
also required.  
ROOF CURBS - NRCA approved curbs provide proper fit to  
base unit for rooftop installations. Curbs are designed to be  
assembled through hinge pins in each corner. Kit also provides  
seal strip to assure a water tight seal. Eight and 14 inch high  
roof curbs are available.  
UPGRADE SAFETY PACKAGE - Contains screw-in type High  
pressure, Low Pressure/Loss of Charge switch, freeze protection  
switch and lockout relay. Switches are placed onto existing  
schrader ports located in the unit by furnished adapters. When  
abnormal conditions are sensed through the pressure switches,  
the unit will lock out preventing any further operation until reset or  
problem is corrected. Package agency approved.  
MANUAL OUTDOOR DAMPER - Provides 0% thru 50%  
outdoor air capability (field adjustable). Designed for duct  
mounted side return and unit mounted down shot return  
applications. Includes hood and screen assembly.  
WALL THERMOSTAT - The units are designed to operate with  
24-volt electronic and electro-mechanical thermostats. All units  
can operate with single stage heat / single stage cool  
thermostats - with or without the economizer.  
HAIL GUARD KIT - Kit contains protected grilles made of  
expanded aluminum grilles with full perimeter inch frame.  
Sloped hoods are also included to assure maximum protection..  
LOW AMBIENT KIT - Kit provides necessary hardware to  
convert unit to operate in cooling cycle down to 0 °F. Standard  
unit operation 45 °F.  
ANTI SHORT CYCLE TIMER - Automatically prevents the  
compressor from restarting for 5 minutes after cycled off. Not  
required if Thermostat 2ET07700224 and 2ET04700224 are  
used.  
TRANSFORMER KIT - Kit provides necessary hardware to  
provide single phase models from factory furnished 40 VA  
transformer capability to 75 VA transformer capability.  
FILTER / FRAME KIT (Single Phase only) - Kit contains the  
necessary hardware to field install return air filters into the base  
unit. Pre-cut filter racks and appropriate cleanable standard  
size filters are shipped in one kit. (1" filter is supplied) This kit is  
available for single phase horizontal or vertical duct application  
only. Standard in all 3 Phase models.  
ELECTRIC HEATERS - Each heater package provides easy  
installation of electric heat strips. Slide in design with plug in  
harness and agency approved. Heaters are available from 5.0  
KW sizes and are designed for single point connection.  
DIRECT DRIVE  
CONDENSER  
FAN MOTOR  
HIGHLY EFFICIENT ENHANCED  
COPPER TUBE/ALUMINUM FIN  
EVAPORATOR COIL  
BACK AND BOTTOM  
RETURN AIR  
HIGHLY EFFICIENT  
ENHANCED COPPER  
TUBE/ALUMINUM FIN  
CONDENSER COIL  
AND SUPPLY AIR  
DUCT OPENING  
DECORATIVE  
PROTECTIVE  
COIL GUARD  
HIGH VOLTAGE  
TERMINAL BLOCK  
LOW VOLTAGE  
TERMINAL BLOCK  
LONG LASTING  
POWDER PAINT  
FINISH EARTH  
3-SPEED DIRECT DRIVE  
BLOWER MOTOR WITH  
TONE COLOR  
HIGH EFFICIENCY  
COMPRESSOR  
RIGIDLY  
SLIDE-OUT BLOWER ASSEMBLY  
HEAVY GAUGE  
REMOVABLE  
BASE RAILS  
MOUNTED  
FIGURE 1 - UNIT CUTAWAY  
4
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
TABLE 1: PHYSICAL DATA  
DEB  
042  
MODELS  
030  
10 X 8  
½
036  
048  
060  
11 x 10  
1
EVAPORATOR  
BLOWER  
CENTRIFUGAL BLOWER (Dia. x Wd. in.)  
FAN MOTOR HP  
10 x 8  
11 X 10  
11 x 10  
3
3
3
4
4
4
ROWS DEEP  
FINS PER INCH  
2
15  
2
15  
2
15  
2
13  
3
16  
EVAPORATOR  
COIL  
FACE AREA (Sq. Ft.)  
PROPELLER DIA. (in.)  
FAN MOTOR HP  
NOM. CFM TOTAL  
ROWS DEEP  
4.38  
22  
1/4  
2,400  
1
4.38  
22  
1/4  
2,400  
1
4.38  
22  
1/4  
2,400  
5.62  
22  
1/4  
2,800  
1
5.26  
22  
1/4  
2,800  
1
CONDENSER  
FAN  
1
CONDENSER  
COIL  
CHARGE  
FILTER  
COMPRESSOR  
FINS PER INCH  
20  
8.3  
3 / 13  
18  
8.3  
3 / 10  
16  
11.7  
4 / 8  
13  
16.4  
5 / 15  
20  
16.4  
5 /15  
FACE AREA (Sq. Ft.)  
REFRIGERANT 22 (lbs./oz.)  
FACE AREA (Sq. Ft.) / Qty. / Size  
HERMETIC, QTY. = 1 (Type)  
2.14 / 2 / 14" x 22"  
Recip.  
Recip.  
Recip.  
Scroll  
Scroll  
TABLE 2: RATINGS - ARI  
Cooling Capacity1  
80/67-95 °F  
Electric Heat  
Nom. Capacity  
KW  
Electric Heat  
Nom. Capacity  
KW  
Sound Rating2  
(decibels)  
Model DEB  
MBH  
EER  
(single phase)  
(three phase)  
030  
036  
042  
048  
060  
29.0  
35.2  
40.5  
46.5  
59.0  
8.9  
8.7  
9.4  
8.8  
8.8  
79  
81  
83  
81  
79  
5.0, 7.5, 10.0, 15.0  
5.0, 7.5, 10.0, 15.0  
5.0, 7.5, 10.0, 15.0  
10.0, 15.0, 20.0, 25.0  
10.0, 15.0, 20.0, 25.0  
-
10.0, 15.0  
10.0, 15.0  
10.0, 15.0, 20.0, 25.0  
10.0, 15.0, 20.0, 25.0  
1. Certified in accordance with the Unitary Small Equipment certification program, which is based on ARI Standard 210/  
240.  
2. Rated in accordance with ARI Standard 270.  
EER = Energy Efficiency Ratio - the total cooling output in BTU's during a normal annual usage period for cooling divided by the total electric  
power input in watt-hours during the same period.  
Johnson Controls Unitary Products  
5
   
360101-XTG-B-0508  
TABLE 3: COOLING CAPACITIES - 2-1/2 TON (DEB030)  
AIR ON INDOOR COIL  
1,000 CFM  
TEMPERATURE  
OF AIR ON  
OUTDOOR COIL  
750 CFM  
WB °F  
875 CFM  
WB °F  
67 62  
1,125 CFM  
WB °F  
1,250 CFM  
WB °F  
WB °F  
72  
67  
62  
57  
72  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
Net Cap  
MBH  
Total Power  
Input kW  
32.3 29.8 27.5 28.1 32.6 30.1 27.8 28.4 33.0 30.4 28.1 28.7 33.5 30.9 28.4 29.1 33.9 31.3 28.8 29.5  
2.94 2.92 2.83 2.81 3.02 3.00 2.90 2.88 3.10 3.08 2.98 2.96 3.20 3.18 3.08 3.06 3.31 3.28 3.18 3.16  
86  
83  
80  
77  
74  
71  
68  
18.2 23.6 27.5 28.1 20.1 25.8 27.8 28.4 21.9 28.0 28.1 28.7 23.3 29.6 28.4 29.1 24.8 31.3 28.8 29.5  
16.1 21.4 25.5 26.3 17.5 23.3 26.8 27.5 19.0 25.1 28.1 28.7 20.0 26.4 28.4 29.1 21.1 27.7 28.8 29.5  
14.0 19.3 23.3 24.1 15.0 20.7 25.1 25.9 16.0 22.2 26.8 27.7 16.7 23.1 27.8 28.6 17.3 24.0 28.8 29.5  
11.8 17.2 21.2 22.0 12.5 18.2 22.5 23.4 13.1 19.3 23.9 24.8 13.4 19.7 24.5 25.3 13.6 20.2 25.1 25.8  
9.7 15.0 19.1 19.9 10.0 15.7 20.0 20.9 10.2 16.3 21.0 21.9 10.1 16.4 21.2 22.0 9.9 16.5 21.4 22.1  
85 °F  
-
-
12.9 16.9 17.7  
10.8 14.8 15.6  
-
-
13.2 17.5 18.3  
10.6 15.0 15.8  
-
-
13.4 18.0 19.0  
10.5 15.1 16.1  
-
-
13.1 17.9 18.7  
9.8 14.5 15.3  
-
-
12.8 17.7 18.4  
9.1 13.9 14.6  
Net Cap  
MBH  
Total Power  
Input kW  
29.1 27.5 24.4 24.8 30.2 28.6 25.3 25.7 31.3 29.7 26.2 26.7 30.9 29.3 25.9 26.4 30.5 28.9 25.6 26.0  
3.17 3.11 3.04 3.03 3.24 3.17 3.10 3.09 3.30 3.23 3.16 3.15 3.43 3.36 3.29 3.27 3.56 3.49 3.41 3.39  
86  
83  
80  
77  
74  
71  
68  
17.5 22.2 24.4 24.8 19.5 24.7 25.3 25.7 21.6 27.2 26.2 26.7 23.1 28.1 25.9 26.4 24.6 28.9 25.6 26.0  
15.4 20.1 24.1 23.9 17.0 22.2 25.2 25.3 18.7 24.3 26.2 26.7 19.8 25.7 25.9 26.4 20.9 27.0 25.6 26.0  
13.2 18.0 22.0 21.8 14.5 19.7 24.1 23.8 15.8 21.4 26.2 25.9 16.5 22.4 25.9 26.0 17.2 23.3 25.6 26.0  
11.1 15.8 19.9 19.6 12.0 17.2 21.6 21.3 12.8 18.5 23.3 23.0 13.1 19.0 22.6 22.6 13.4 19.6 21.8 22.3  
9.0 13.7 17.7 17.5 9.4 14.6 19.1 18.8 9.9 15.6 20.4 20.1 9.8 15.7 19.2 19.3 9.7 15.9 18.1 18.6  
95 °F  
-
-
11.6 15.6 15.3  
9.4 13.5 13.2  
-
-
12.1 16.5 16.3  
9.6 14.0 13.7  
-
-
12.7 17.5 17.2  
9.7 14.6 14.3  
-
-
12.4 15.9 16.0  
9.1 12.6 12.7  
-
-
12.1 14.4 14.8  
8.4 10.6 11.1  
Net Cap  
MBH  
Total Power  
Input kW  
26.7 24.8 22.2 22.3 27.8 25.8 23.1 23.2 28.9 26.8 24.0 24.1 28.6 26.5 23.7 23.9 28.3 26.3 23.5 23.6  
3.38 3.28 3.22 3.22 3.45 3.35 3.29 3.28 3.52 3.42 3.36 3.35 3.66 3.55 3.49 3.48 3.79 3.68 3.62 3.61  
86  
83  
80  
77  
74  
71  
68  
16.5 21.3 22.2 22.3 18.5 23.4 23.1 23.2 20.5 25.6 24.0 24.1 22.0 25.9 23.7 23.9 23.5 26.3 23.5 23.6  
14.4 19.2 22.0 21.8 16.0 21.2 23.0 22.9 17.6 23.3 24.0 24.1 18.7 24.3 23.7 23.9 19.7 25.3 23.5 23.6  
12.3 17.0 19.8 19.6 13.5 18.7 21.8 21.6 14.7 20.4 23.8 23.5 15.4 21.3 23.6 23.6 16.0 22.2 23.5 23.6  
10.1 14.9 17.7 17.5 10.9 16.2 19.3 19.0 11.8 17.5 20.9 20.6 12.0 18.0 20.3 20.3 12.3 18.5 19.8 19.9  
8.0 12.7 15.6 15.3 8.4 13.7 16.8 16.5 8.9 14.6 17.9 17.7 8.7 14.7 17.0 16.9 8.6 14.8 16.0 16.2  
105 °F  
115 °F  
125 °F  
-
-
10.6 13.4 13.2  
8.5 11.3 11.1  
-
-
11.1 14.2 14.0  
8.6 11.7 11.5  
-
-
11.7 15.0 14.8  
8.7 12.1 11.9  
-
-
11.4 13.7 13.6  
8.0 10.3 10.3  
-
-
11.0 12.3 12.5  
7.3 8.6 8.7  
Net Cap  
MBH  
Total Power  
Input kW  
24.3 22.0 20.0 19.8 25.4 22.9 20.8 20.7 26.4 23.9 21.7 21.5 26.2 23.7 21.6 21.4 26.1 23.6 21.4 21.3  
3.58 3.45 3.41 3.41 3.66 3.52 3.48 3.48 3.74 3.60 3.56 3.56 3.89 3.74 3.69 3.69 4.03 3.87 3.83 3.83  
86  
83  
80  
77  
74  
71  
68  
15.6 20.3 20.0 19.8 17.5 22.1 20.8 20.7 19.5 23.9 21.7 21.5 20.9 23.7 21.6 21.4 22.3 23.6 21.4 21.3  
13.4 18.2 19.8 19.6 15.0 20.3 20.7 20.6 16.5 22.3 21.7 21.5 17.6 23.0 21.6 21.4 18.6 23.6 21.4 21.3  
11.3 16.1 17.7 17.5 12.5 17.7 19.5 19.3 13.6 19.4 21.3 21.1 14.2 20.3 21.4 21.2 14.9 21.1 21.4 21.3  
9.1 13.9 15.5 15.3 9.9 15.2 17.0 16.8 10.7 16.5 18.4 18.2 10.9 16.9 18.1 17.9 11.1 17.4 17.7 17.6  
7.0 11.8 13.4 13.2 7.4 12.7 14.4 14.2 7.8 13.6 15.5 15.3 7.6 13.6 14.7 14.6 7.4 13.7 14.0 13.8  
-
-
9.6 11.2 11.1  
7.5 9.1 8.9  
-
-
10.1 11.9 11.7  
7.6 9.4 9.2  
-
-
10.6 12.6 12.4  
7.7 9.7 9.5  
-
-
10.3 11.4 11.2  
7.0 8.1 7.9  
-
-
10.0 10.2 10.1  
6.2 6.5 6.4  
Net Cap  
MBH  
Total Power  
Input kW  
21.9 19.2 17.8 17.4 22.9 20.1 18.6 18.2 23.9 21.0 19.4 19.0 23.9 21.0 19.4 18.9 23.9 20.9 19.4 18.9  
3.8 3.6 3.6 3.6 3.9 3.7 3.7 3.7 4.0 3.8 3.8 3.8 4.1 3.9 3.9 3.9 4.3 4.1 4.0 4.0  
86  
83  
80  
77  
74  
71  
68  
14.6 19.4 17.8 17.4 16.5 20.8 18.6 18.2 18.4 22.2 19.4 19.0 19.8 21.6 19.4 18.9 21.2 20.9 19.4 18.9  
12.5 17.2 17.6 17.5 14.0 19.3 18.5 18.2 15.5 21.3 19.4 19.0 16.5 21.6 19.4 18.9 17.4 21.9 19.4 18.9  
10.3 15.1 15.5 15.3 11.4 16.7 17.2 17.0 12.6 18.4 18.9 18.7 13.1 19.2 19.1 18.8 13.7 20.1 19.4 18.9  
8.2 13.0 13.3 13.2 8.9 14.2 14.7 14.5 9.6 15.5 16.0 15.8 9.8 15.9 15.8 15.5 10.0 16.3 15.6 15.2  
6.0 10.8 11.2 11.1 6.4 11.7 12.1 12.0 6.7 12.6 13.1 12.9 6.5 12.6 12.5 12.2 6.3 12.6 11.9 11.5  
-
-
8.7 9.1 8.9  
6.5 6.9 6.8  
-
-
9.2 9.6 9.4  
6.6 7.1 6.9  
-
-
9.6 10.1 10.0  
6.7 7.2 7.0  
-
-
9.3 9.2 8.9  
5.9 5.8 5.5  
-
-
8.9 8.2 7.7  
5.2 4.5 4.0  
1. These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity  
ALL SENSIBLE CAPACITIES  
6
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
TABLE 4: COOLING CAPACITIES - 3 TON (DEB036)  
AIR ON INDOOR COIL  
TEMPERATURE  
900 CFM  
1,050  
WB °F  
1,200  
WB °F  
1,350  
1,500  
OF AIR ON  
WB °F  
WB °F  
WB °F  
OUTDOOR COIL  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
Net Cap  
MBH  
Total Power  
Input kW  
34.7 32.3 28.5 28.4 36.9 34.3 30.3 30.1 39.0 36.4 32.1 31.9 39.9 37.1 32.7 32.6 40.7 37.9 33.4 33.2  
3.61 3.52 3.46 3.46 3.62 3.53 3.47 3.47 3.63 3.55 3.48 3.48 3.70 3.61 3.55 3.55 3.77 3.68 3.61 3.61  
86  
83  
80  
77  
74  
71  
68  
19.7 25.4 28.5 28.4 22.2 28.5 30.3 30.1 24.6 31.5 32.1 31.9 26.3 33.5 32.7 32.6 28.0 35.5 33.4 33.2  
17.2 22.9 26.7 28.4 19.2 25.5 29.4 30.1 21.1 28.0 32.1 31.9 22.4 29.5 32.7 32.6 23.6 31.0 33.4 33.2  
14.6 20.3 24.2 26.0 16.1 22.4 26.7 28.7 17.6 24.5 29.2 31.4 18.4 25.6 30.4 32.3 19.1 26.6 31.6 33.2  
12.0 17.7 21.6 23.4 13.1 19.4 23.7 25.6 14.1 21.0 25.7 27.9 14.4 21.6 26.4 28.3 14.6 22.1 27.2 28.8  
9.5 15.2 19.1 20.8 10.1 16.4 20.6 22.6 10.6 17.5 22.2 24.4 10.4 17.6 22.5 24.3 10.2 17.6 22.7 24.3  
85 °F  
-
-
12.6 16.5 18.3  
10.0 13.9 15.7  
-
-
13.3 17.6 19.6  
10.3 14.6 16.5  
-
-
14.1 18.7 20.9  
10.6 15.2 17.4  
-
-
13.6 18.5 20.4  
9.6 14.5 16.4  
-
-
13.2 18.2 19.8  
8.7 13.7 15.4  
Net Cap  
MBH  
Total Power  
Input kW  
32.5 30.4 27.8 26.8 34.4 32.2 29.4 28.4 36.3 34.0 31.0 29.9 37.2 34.8 31.8 30.7 38.1 35.7 32.6 31.5  
3.85 3.74 3.70 3.68 3.85 3.75 3.71 3.68 3.86 3.75 3.71 3.69 3.93 3.82 3.78 3.76 4.01 3.90 3.86 3.83  
86  
83  
80  
77  
74  
71  
68  
18.5 24.3 27.8 26.8 21.0 27.4 29.4 28.4 23.4 30.5 31.0 29.9 24.8 32.0 31.8 30.7 26.1 33.4 32.6 31.5  
16.0 21.7 25.7 26.6 18.0 24.4 28.4 28.2 19.9 27.0 31.0 29.9 20.8 28.0 31.8 30.7 21.6 29.0 32.6 31.5  
13.4 19.2 23.2 24.0 14.9 21.3 25.8 26.7 16.4 23.5 28.4 29.4 16.8 24.0 29.0 30.0 17.1 24.5 29.6 30.7  
10.8 16.6 20.6 21.4 11.9 18.3 22.8 23.7 12.9 20.0 24.9 25.9 12.8 20.0 25.0 26.1 12.7 20.0 25.1 26.2  
8.3 14.0 18.0 18.9 8.9 15.3 19.7 20.6 9.4 16.5 21.4 22.4 8.8 16.0 21.0 22.1 8.2 15.5 20.7 21.7  
95 °F  
-
-
11.5 15.5 16.3  
8.9 12.9 13.7  
-
-
12.2 16.7 17.6  
9.2 13.7 14.6  
-
-
13.0 17.9 18.9  
9.5 14.4 15.4  
-
-
12.0 17.1 18.1  
8.1 13.1 14.1  
-
-
11.1 16.2 17.3  
6.6 11.7 12.8  
Net Cap  
MBH  
Total Power  
Input kW  
29.5 27.4 25.0 24.4 31.4 29.2 26.6 26.0 33.3 31.0 28.2 27.6 34.1 31.7 28.9 28.3 35.0 32.5 29.6 29.0  
4.05 3.92 3.93 3.85 4.07 3.94 3.95 3.87 4.09 3.96 3.97 3.89 4.15 4.02 4.02 3.95 4.21 4.08 4.08 4.00  
86  
83  
80  
77  
74  
71  
68  
17.5 23.3 25.0 24.4 19.9 26.3 26.6 26.0 22.3 29.2 28.2 27.6 23.6 30.3 28.9 28.3 24.8 31.4 29.6 29.0  
15.0 20.7 24.0 24.3 16.9 23.3 26.1 25.9 18.8 25.9 28.2 27.6 19.6 26.8 28.9 28.3 20.3 27.6 29.6 29.0  
12.4 18.1 21.4 21.7 13.9 20.3 23.9 24.3 15.3 22.4 26.5 26.8 15.6 22.8 26.9 27.3 15.8 23.1 27.3 27.7  
9.8 15.6 18.8 19.1 10.8 17.3 20.9 21.2 11.8 18.9 23.0 23.3 11.6 18.8 22.9 23.3 11.4 18.7 22.8 23.2  
7.3 13.0 16.3 16.6 7.8 14.2 17.9 18.2 8.3 15.4 19.5 19.8 7.6 14.8 18.9 19.3 6.9 14.2 18.4 18.8  
105 °F  
115 °F  
125 °F  
-
-
10.4 13.7 14.0  
7.9 11.1 11.4  
-
-
11.2 14.8 15.2  
8.2 11.8 12.1  
-
-
11.9 16.0 16.3  
8.4 12.5 12.8  
-
-
10.8 14.9 15.3  
6.9 10.9 11.3  
-
-
9.7 13.9 14.3  
5.3 9.4 9.8  
Net Cap  
MBH  
Total Power  
Input kW  
26.5 24.4 22.2 22.0 28.4 26.2 23.8 23.6 30.4 28.0 25.5 25.2 31.1 28.6 26.1 25.8 31.8 29.3 26.7 26.4  
4.25 4.11 4.16 4.03 4.28 4.14 4.19 4.06 4.31 4.17 4.22 4.09 4.36 4.21 4.27 4.13 4.40 4.25 4.31 4.17  
86  
83  
80  
77  
74  
71  
68  
16.5 22.2 22.2 22.0 18.9 25.1 23.8 23.6 21.2 28.0 25.5 25.2 22.4 28.6 26.1 25.8 23.5 29.3 26.7 26.4  
14.0 19.7 22.2 22.0 15.9 22.3 23.8 23.6 17.7 24.9 25.5 25.2 18.4 25.6 26.1 25.8 19.0 26.3 26.7 26.4  
11.4 17.1 19.6 19.4 12.8 19.2 22.1 21.8 14.2 21.4 24.5 24.3 14.4 21.6 24.8 24.5 14.5 21.8 25.0 24.7  
8.8 14.5 17.1 16.9 9.8 16.2 19.0 18.8 10.7 17.9 21.0 20.8 10.4 17.6 20.8 20.5 10.1 17.3 20.5 20.3  
6.3 12.0 14.5 14.3 6.8 13.2 16.0 15.8 7.2 14.4 17.5 17.3 6.4 13.6 16.8 16.5 5.6 12.9 16.1 15.8  
-
-
9.4 11.9 11.7  
6.8 9.4 9.2  
-
-
10.1 13.0 12.7  
7.1 9.9 9.7  
-
-
10.9 14.0 13.8  
7.4 10.5 10.3  
-
-
9.6 12.8 12.5  
5.6 8.8 8.6  
-
-
8.4 11.6 11.3  
3.9 7.1 6.9  
Net Cap  
MBH  
Total Power  
Input kW  
23.5 21.4 19.4 19.6 25.4 23.2 21.1 21.3 27.4 25.0 22.7 22.9 28.0 25.5 23.2 23.4 28.6 26.1 23.7 23.9  
4.5 4.3 4.4 4.2 4.5 4.3 4.4 4.2 4.5 4.4 4.5 4.3 4.6 4.4 4.5 4.3 4.6 4.4 4.5 4.3  
86  
83  
80  
77  
74  
71  
68  
15.5 21.2 19.4 19.6 17.8 24.0 21.1 21.3 20.1 26.7 22.7 22.9 21.2 27.0 23.2 23.4 22.2 27.2 23.7 23.9  
13.0 18.6 20.4 19.7 14.8 21.2 21.6 21.3 16.6 23.8 22.7 22.9 17.2 24.4 23.2 23.4 17.7 24.9 23.7 23.9  
10.4 16.1 17.9 17.1 11.8 18.2 20.2 19.4 13.1 20.3 22.6 21.7 13.2 20.4 22.6 21.7 13.2 20.4 22.7 21.8  
7.8 13.5 15.3 14.6 8.7 15.2 17.2 16.4 9.6 16.8 19.1 18.2 9.2 16.4 18.7 17.7 8.8 16.0 18.2 17.3  
5.3 10.9 12.7 12.0 5.7 12.1 14.2 13.3 6.1 13.3 15.6 14.7 5.2 12.4 14.7 13.8 4.3 11.5 13.8 12.8  
-
-
8.4 10.2 9.4  
5.8 7.6 6.9  
-
-
9.1 11.1 10.3  
6.1 8.1 7.3  
-
-
9.8 12.1 11.2  
6.3 8.6 7.7  
-
-
8.4 10.7 9.8  
4.4 6.7 5.8  
-
-
7.0 9.3 8.4  
2.6 4.8 3.9  
1. These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity  
ALL SENSIBLE CAPACITIES  
Johnson Controls Unitary Products  
7
 
360101-XTG-B-0508  
TABLE 5: COOLING CAPACITIES - 3-1/2 TON (DEB042)  
AIR ON INDOOR COIL  
TEMPERATURE  
1,050 CFM  
1,225  
WB °F  
1,400  
WB °F  
1,575  
1,750  
OF AIR ON  
WB °F  
WB °F  
WB °F  
OUTDOOR COIL  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
Net Cap  
MBH  
Total Power  
Input kW  
40.7 39.0 36.5 34.1 42.0 40.3 37.7 35.2 43.3 41.6 38.8 36.3 43.9 42.1 39.3 36.8 44.4 42.6 39.8 37.2  
4.09 3.82 3.77 3.75 4.16 3.89 3.83 3.81 4.23 3.95 3.90 3.88 4.38 4.10 4.04 4.02 4.54 4.25 4.18 4.16  
86  
83  
80  
77  
74  
71  
68  
23.8 31.3 36.5 34.1 26.1 34.2 37.7 35.2 28.5 37.0 38.8 36.3 30.5 39.4 39.3 36.8 32.6 41.9 39.8 37.2  
20.8 28.3 34.6 34.1 22.6 30.6 36.7 35.2 24.4 32.9 38.8 36.3 25.9 34.8 39.3 36.8 27.3 36.6 39.8 37.2  
17.8 25.4 31.6 31.9 19.1 27.1 33.8 34.1 20.3 28.8 36.0 36.3 21.2 30.1 37.6 36.8 22.1 31.4 39.2 37.2  
14.9 22.4 28.6 28.9 15.5 23.6 30.3 30.6 16.2 24.7 31.9 32.2 16.6 25.5 32.9 32.1 16.9 26.2 34.0 32.0  
11.9 19.4 25.6 26.0 12.0 20.0 26.7 27.0 12.1 20.7 27.8 28.1 11.9 20.8 28.3 27.5 11.7 21.0 28.8 26.8  
85 °F  
-
-
16.4 22.7 23.0  
13.4 19.7 20.0  
-
-
16.5 23.2 23.5  
12.9 19.6 20.0  
-
-
16.6 23.7 24.1  
12.5 19.6 20.0  
-
-
16.2 23.6 22.8  
11.5 19.0 18.2  
-
-
15.8 23.6 21.6  
10.6 18.3 16.4  
Net Cap  
MBH  
Total Power  
Input kW  
38.7 36.7 34.0 32.7 40.1 38.1 35.2 33.9 41.6 39.4 36.5 35.2 42.1 39.9 36.9 35.6 42.6 40.3 37.4 36.0  
4.16 4.06 3.96 3.98 4.23 4.13 4.03 4.05 4.30 4.19 4.10 4.11 4.44 4.33 4.23 4.25 4.59 4.47 4.37 4.39  
86  
83  
80  
77  
74  
71  
68  
23.0 30.4 34.0 32.7 25.4 33.3 35.2 33.9 27.8 36.3 36.5 35.2 29.9 38.3 36.9 35.6 32.0 40.3 37.4 36.0  
20.0 27.4 33.2 32.7 21.9 29.8 34.9 33.9 23.7 32.2 36.5 35.2 25.2 34.1 36.9 35.6 26.7 36.0 37.4 36.0  
17.0 24.4 30.3 30.4 18.3 26.3 32.6 32.8 19.7 28.2 35.0 35.2 20.6 29.5 36.2 35.6 21.5 30.8 37.4 36.0  
14.0 21.4 27.3 27.5 14.8 22.7 29.1 29.3 15.6 24.1 30.9 31.1 15.9 24.8 31.5 30.9 16.3 25.6 32.1 30.8  
11.0 18.4 24.3 24.5 11.3 19.2 25.5 25.7 11.5 20.0 26.8 27.0 11.3 20.2 26.9 26.3 11.1 20.4 26.9 25.5  
95 °F  
-
-
15.4 21.3 21.5  
12.4 18.3 18.5  
-
-
15.6 22.0 22.2  
12.1 18.4 18.7  
-
-
15.9 22.7 22.9  
11.8 18.6 18.8  
-
-
15.5 22.2 21.6  
10.9 17.6 17.0  
-
-
15.2 21.7 20.3  
10.0 16.5 15.1  
Net Cap  
MBH  
Total Power  
Input kW  
36.2 33.9 30.8 31.2 37.6 35.1 32.0 32.4 38.9 36.4 33.1 33.6 39.4 36.8 33.5 34.0 39.9 37.3 33.9 34.4  
4.40 4.28 4.20 4.22 4.47 4.35 4.27 4.29 4.54 4.42 4.34 4.35 4.69 4.57 4.48 4.50 4.84 4.71 4.63 4.64  
86  
83  
80  
77  
74  
71  
68  
22.4 29.3 30.8 31.2 24.8 32.1 32.0 32.4 27.3 34.9 33.1 33.6 29.3 36.1 33.5 34.0 31.4 37.3 33.9 34.4  
19.4 26.3 30.5 31.2 21.3 28.8 31.8 32.4 23.2 31.3 33.1 33.6 24.7 33.2 33.5 34.0 26.2 35.1 33.9 34.4  
16.4 23.3 27.8 28.8 17.7 25.3 30.1 31.2 19.1 27.2 32.4 33.6 20.0 28.6 33.1 34.0 21.0 29.9 33.9 34.4  
13.4 20.3 24.8 25.8 14.2 21.7 26.5 27.6 15.0 23.1 28.3 29.5 15.4 23.9 28.5 29.3 15.8 24.7 28.7 29.1  
10.4 17.3 21.8 22.8 10.7 18.2 23.0 24.1 10.9 19.0 24.2 25.4 10.7 19.3 23.8 24.7 10.6 19.5 23.5 23.9  
105 °F  
115 °F  
125 °F  
-
-
14.3 18.8 19.8  
11.4 15.8 16.8  
-
-
14.7 19.4 20.6  
11.1 15.9 17.0  
-
-
15.0 20.1 21.3  
10.9 16.0 17.2  
-
-
14.6 19.2 20.0  
10.0 14.5 15.4  
-
-
14.3 18.3 18.7  
9.1 13.1 13.5  
Net Cap  
MBH  
Total Power  
Input kW  
33.8 31.1 27.7 29.8 35.0 32.2 28.8 30.9 36.3 33.4 29.8 32.0 36.7 33.8 30.1 32.3 37.2 34.2 30.5 32.7  
4.64 4.51 4.44 4.46 4.71 4.58 4.51 4.53 4.78 4.65 4.58 4.59 4.94 4.80 4.73 4.75 5.09 4.96 4.88 4.90  
86  
83  
80  
77  
74  
71  
68  
21.7 28.3 27.7 29.8 24.2 30.8 28.8 30.9 26.7 33.4 29.8 32.0 28.8 33.8 30.1 32.3 30.9 34.2 30.5 32.7  
18.7 25.3 27.7 29.8 20.7 27.8 28.8 30.9 22.6 30.3 29.8 32.0 24.2 32.3 30.1 32.3 25.7 34.2 30.5 32.7  
15.7 22.3 25.3 27.1 17.1 24.3 27.5 29.5 18.5 26.3 29.8 32.0 19.5 27.7 30.1 32.3 20.5 29.1 30.5 32.7  
12.7 19.3 22.3 24.1 13.6 20.7 24.0 26.0 14.4 22.2 25.7 27.9 14.9 23.0 25.5 27.7 15.3 23.8 25.3 27.5  
9.7 16.3 19.3 21.1 10.0 17.2 20.4 22.5 10.3 18.1 21.6 23.8 10.2 18.4 20.8 23.0 10.1 18.6 20.1 22.3  
-
-
13.3 16.3 18.1  
10.3 13.3 15.2  
-
-
13.7 16.9 18.9  
10.1 13.4 15.4  
-
-
14.0 17.5 19.7  
9.9 13.4 15.6  
-
-
13.7 16.2 18.4  
9.1 11.5 13.7  
-
-
13.4 14.8 17.1  
8.2 9.6 11.9  
Net Cap  
MBH  
Total Power  
Input kW  
31.4 28.3 24.6 28.3 32.5 29.3 25.5 29.3 33.6 30.4 26.4 30.3 34.0 30.7 26.7 30.7 34.5 31.1 27.1 31.1  
4.9 4.7 4.7 4.7 4.9 4.8 4.7 4.8 5.0 4.9 4.8 4.8 5.2 5.0 5.0 5.0 5.3 5.2 5.1 5.2  
86  
83  
80  
77  
74  
71  
68  
21.1 27.2 24.6 28.3 23.6 29.6 25.5 29.3 26.1 31.9 26.4 30.3 28.3 31.5 26.7 30.7 30.4 31.1 27.1 31.1  
18.1 24.2 25.0 28.3 20.0 26.8 25.7 29.3 22.0 29.4 26.4 30.3 23.6 31.3 26.7 30.7 25.2 33.3 27.1 31.1  
15.1 21.3 22.8 25.5 16.5 23.3 25.0 27.9 17.9 25.3 27.2 30.3 19.0 26.7 27.1 30.7 20.0 28.2 27.1 31.1  
12.1 18.3 19.8 22.5 13.0 19.7 21.4 24.4 13.9 21.2 23.1 26.3 14.3 22.1 22.5 26.1 14.8 23.0 21.9 25.9  
9.1 15.3 16.8 19.5 9.4 16.2 17.9 20.8 9.8 17.1 19.0 22.2 9.7 17.4 17.8 21.4 9.5 17.7 16.6 20.7  
-
-
12.3 13.8 16.5  
9.3 10.8 13.5  
-
-
12.7 14.4 17.3  
9.1 10.8 13.8  
-
-
13.1 14.9 18.1  
9.0 10.8 14.0  
-
-
12.8 13.2 16.8  
8.1 8.5 12.1  
-
-
12.5 11.4 15.5  
7.3 6.2 10.2  
1. These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity  
ALL SENSIBLE CAPACITIES  
8
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
TABLE 6: COOLING CAPACITIES - 4 TON (DEB048)  
AIR ON INDOOR COIL  
1600 CFM  
TEMPERATURE  
1200 CFM  
1400 CFM  
WB °F  
1800 CFM  
WB °F  
2000 CFM  
WB °F  
OF AIR ON  
WB °F  
WB °F  
OUTDOOR COIL  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
Net Cap  
MBH  
Total Power  
Input kW  
49.2 46.1 41.6 41.3 50.6 47.4 42.9 42.5 52.1 48.8 44.1 43.7 52.8 49.4 44.7 44.2 53.4 50.1 45.2 44.8  
4.47 4.44 4.35 4.33 4.59 4.57 4.47 4.45 4.72 4.69 4.59 4.57 4.78 4.76 4.66 4.63 4.85 4.83 4.72 4.70  
86  
83  
80  
77  
74  
71  
68  
28.3 35.7 41.3 41.3 31.5 39.6 42.7 42.5 34.7 43.5 44.1 43.7 37.1 46.3 44.7 44.2 39.5 49.1 45.2 44.8  
24.9 32.3 37.8 39.5 27.4 35.6 41.0 41.6 30.0 38.9 44.1 43.7 31.8 41.0 44.7 44.2 33.5 43.2 45.2 44.8  
21.4 28.9 34.4 36.1 23.4 31.6 37.6 39.4 25.4 34.2 40.7 42.7 26.5 35.7 42.5 43.8 27.6 37.2 44.3 44.8  
18.0 25.5 31.0 32.7 19.4 27.5 33.5 35.4 20.7 29.5 36.1 38.1 21.2 30.4 37.2 38.5 21.6 31.2 38.3 38.9  
14.6 22.1 27.6 29.3 15.3 23.5 29.5 31.3 16.0 24.9 31.4 33.4 15.8 25.1 31.9 33.1 15.7 25.3 32.4 32.9  
85 °F  
-
-
18.6 24.2 25.8  
15.2 20.7 22.4  
-
-
19.4 25.4 27.3  
15.4 21.4 23.2  
-
-
20.2 26.7 28.7  
15.5 22.1 24.1  
-
-
19.8 26.6 27.8  
14.4 21.3 22.5  
-
-
19.3 26.4 26.9  
13.4 20.4 21.0  
Net Cap  
MBH  
Total Power  
Input kW  
47.2 43.4 39.3 38.8 48.6 44.7 40.5 40.0 50.0 46.0 41.7 41.1 48.9 45.0 40.8 40.2 47.8 44.0 39.9 39.3  
4.88 4.85 4.74 4.74 5.00 4.97 4.86 4.86 5.13 5.09 4.98 4.98 5.23 5.20 5.09 5.08 5.34 5.31 5.19 5.19  
86  
83  
80  
77  
74  
71  
68  
27.7 34.7 39.3 38.8 30.6 38.3 40.5 40.0 33.6 41.9 41.7 41.1 35.3 42.9 40.8 40.2 37.0 44.0 39.9 39.3.  
24.2 31.3 36.5 37.9 26.6 34.2 39.1 39.5 28.9 37.2 41.7 41.1 30.0 38.3 40.8 40.2 31.0 39.5 39.9 39.3  
20.8 27.9 33.0 34.5 22.5 30.2 35.8 37.4 24.3 32.5 38.5 40.2 24.7 33.0 39.1 39.8 25.0 33.5 39.7 39.3  
17.4 24.5 29.6 31.1 18.5 26.2 31.7 33.3 19.6 27.9 33.9 35.6 19.3 27.7 33.8 34.5 19.1 27.6 33.8 33.3  
14.0 21.0 26.2 27.7 14.5 22.1 27.7 29.3 14.9 23.2 29.2 30.9 14.0 22.4 28.5 29.1 13.1 21.6 27.8 27.4  
95 °F  
-
-
17.6 22.8 24.2  
14.2 19.4 20.8  
-
-
18.1 23.7 25.2  
14.0 19.6 21.2  
-
-
18.5 24.5 26.2  
13.9 19.9 21.6  
-
-
17.1 23.2 23.8  
11.8 17.9 18.5  
-
-
15.7 21.9 21.4  
9.7 15.9 15.5  
Net Cap  
MBH  
Total Power  
Input kW  
45.5 40.1 37.8 37.4 46.1 40.6 38.3 37.9 46.7 41.1 38.8 38.3 46.3 40.8 38.5 38.0 46.0 40.4 38.2 37.7  
5.37 5.30 5.21 5.21 5.49 5.43 5.34 5.33 5.62 5.55 5.46 5.45 5.72 5.66 5.56 5.55 5.83 5.76 5.66 5.65  
86  
83  
80  
77  
74  
71  
68  
27.0 33.2 37.8 37.4 29.6 36.1 38.3 37.9 32.3 39.1 38.8 38.3 34.3 39.7 38.5 38.0 36.4 40.4 38.2 37.7  
23.6 29.8 35.7 36.3 25.6 32.2 37.3 37.3 37.6 34.7 38.8 38.3 29.0 36.3 38.5 38.0 30.4 38.0 38.2 37.7  
20.1 26.4 32.3 32.9 21.5 28.2 34.6 35.2 22.9 30.0 36.8 37.5 23.7 31.0 37.5 37.6 24.5 32.0 38.1 37.7  
16.7 22.9 28.9 29.5 17.5 24.2 30.5 31.2 18.3 25.4 32.1 32.8 18.4 25.7 32.1 32.3 18.5 26.0 32.1 31.8  
13.3 19.5 25.5 26.1 13.5 20.1 26.5 27.1 13.6 20.7 27.5 28.2 13.1 20.4 26.8 27.0 12.5 20.1 26.2 25.8  
105 °F  
115 °F  
125 °F  
-
-
16.1 22.0 22.7  
12.7 18.6 19.2  
-
-
16.1 22.4 23.1  
12.0 18.4 19.0  
-
-
16.0 22.8 23.5  
11.6 18.1 18.8  
-
-
15.1 21.5 21.7  
9.8 16.2 16.4  
-
-
14.1 20.2 19.8  
8.1 14.3 13.9  
Net Cap  
MBH  
Total Power  
Input kW  
43.9 36.7 36.3 36.0 43.6 36.5 36.1 35.8 43.3 36.3 35.8 35.5 43.7 36.6 36.2 35.8 44.1 36.9 36.5 36.2  
5.86 5.76 5.69 5.67 5.98 5.88 5.81 5.80 6.11 6.01 5.94 5.92 6.22 6.11 6.04 6.02 6.32 6.21 6.14 6.12  
86  
83  
80  
77  
74  
71  
68  
26.3 31.7 36.3 36.0 28.6 34.0 36.1 35.8 30.9 36.3 35.8 35.5 33.4 36.6 36.2 35.8 35.8 36.9 36.5 36.2  
22.9 28.3 35.0 34.8 24.6 30.2 35.4 35.1 26.3 32.2 35.8 35.5 28.1 34.3 36.2 35.8 29.8 36.4 36.5 36.2  
19.5 24.8 31.6 31.3 20.5 26.2 33.3 33.1 21.6 27.6 35.1 34.8 22.7 29.0 35.8 35.5 23.9 30.5 36.5 36.2  
16.1 21.4 28.2 27.9 16.5 22.2 29.3 29.0 17.0 22.9 30.4 30.1 17.4 23.7 30.4 30.2 17.9 24.5 30.5 30.2  
12.6 18.0 24.7 24.5 12.5 18.1 25.2 25.0 12.3 18.2 25.7 25.4 12.1 18.4 25.1 24.8 12.0 18.5 24.5 24.2  
-
-
14.6 21.3 21.1  
11.1 17.9 17.6  
-
-
14.1 21.2 20.9  
10.0 17.1 16.9  
-
-
13.6 21.1 20.8  
8.9 16.4 16.1  
-
-
13.1 19.8 19.5  
7.8 14.5 14.2  
-
-
12.6 18.6 18.3  
6.6 12.6 12.3  
Net Cap  
MBH  
Total Power  
Input kW  
42.2 33.4 34.8 34.6 41.1 32.4 33.8 33.7 40.0 31.4 32.9 32.7 41.1 32.4 33.8 33.7 42.2 33.4 34.8 34.6  
6.3 6.2 6.2 6.1 6.5 6.3 6.3 6.3 6.6 6.5 6.4 6.4 6.7 6.6 6.5 6.5 6.8 6.7 6.6 6.6  
86  
83  
80  
77  
74  
71  
68  
25.6 30.1 34.8 34.6 27.6 31.8 33.8 33.7 29.6 31.4 32.9 32.7 32.4 32.4 33.8 33.7 35.2 33.4 34.8 34.6  
22.2 26.7 34.3 33.2 23.6 28.2 33.6 32.9 25.0 29.8 32.9 32.7 27.1 32.3 33.8 33.7 29.3 33.4 34.8 34.6  
18.8 23.3 30.8 29.8 19.5 24.2 32.1 30.9 20.3 25.1 32.9 32.1 21.8 27.0 33.8 33.3 23.3 28.9 34.8 34.6  
15.4 19.9 27.4 26.3 15.5 20.2 28.0 26.9 15.6 20.4 28.6 27.4 16.5 21.7 28.8 28.0 17.3 22.9 28.9 28.6  
12.0 16.5 24.0 22.9 11.5 16.1 24.0 22.8 11.0 15.8 24.0 22.7 11.2 16.4 23.4 22.7 11.4 17.0 22.9 22.7  
-
-
13.0 20.6 19.5  
9.6 17.2 16.1  
-
-
12.1 19.9 18.8  
8.0 15.9 14.7  
-
-
11.1 19.3 18.1  
6.4 14.6 13.4  
-
-
11.1 18.1 17.4  
5.7 12.8 12.1  
-
-
11.0 17.0 16.7  
5.1 11.0 10.7  
1. These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity  
ALL SENSIBLE CAPACITIES  
Johnson Controls Unitary Products  
9
 
360101-XTG-B-0508  
TABLE 7: COOLING CAPACITIES - 5 TON (DEB060)  
AIR ON INDOOR COIL  
1600 CFM  
TEMPERATURE  
1200 CFM  
1400 CFM  
WB °F  
1800 CFM  
WB °F  
2000 CFM  
WB °F  
OF AIR ON  
WB °F  
WB °F  
OUTDOOR COIL  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
Net Cap  
MBH  
Total Power  
Input kW  
65.2 59.2 52.9 53.4 67.2 61.1 54.5 55.1 69.2 62.9 56.2 56.7 70.3 63.9 57.1 57.6 71.4 64.9 58.0 58.6  
5.68 5.60 4.45 5.41 5.87 5.79 5.63 5.59 6.06 5.98 5.82 5.77 6.25 6.16 6.00 5.95 6.43 6.35 6.18 6.13  
86  
83  
80  
77  
74  
71  
68  
37.9 46.9 52.9 53.4 41.7 51.4 54.5 55.1 45.6 56.0 56.2 56.7 49.1 60.1 57.1 57.6 52.6 64.2 58.0 58.6  
33.6 42.6 50.2 51.9 36.7 46.4 53.2 54.3 39.8 50.1 56.2 56.7 42.5 53.4 57.1 57.6 45.2 56.7 58.0 58.6  
29.3 38.3 45.9 47.6 31.6 41.3 49.5 51.3 33.9 44.3 53.1 55.0 35.8 46.8 55.6 56.8 37.7 49.3 58.0 58.6  
25.1 34.0 41.7 43.3 26.6 36.3 44.5 46.2 28.1 38.5 47.3 49.2 29.2 40.2 48.9 50.2 30.3 41.8 50.6 51.1  
20.8 29.8 37.4 39.0 21.5 31.2 39.4 41.2 22.3 32.7 41.5 43.4 22.5 33.5 42.3 43.5 22.8 34.4 43.1 43.7  
85 °F  
-
-
25.5 33.1 34.7  
21.2 28.8 30.5  
-
-
26.2 34.4 36.1  
21.1 29.3 31.1  
-
-
26.8 35.6 37.5  
21.0 29.8 31.7  
-
-
26.9 35.6 36.9  
20.2 29.0 30.2  
-
-
26.9 35.7 36.2  
19.5 28.2 28.8  
Net Cap  
MBH  
Total Power  
Input kW  
60.1 54.7 48.7 49.4 62.5 56.9 50.7 51.3 64.9 59.1 52.6 53.3 65.7 59.9 53.3 54.0 66.5 60.6 53.9 54.6  
6.25 6.13 6.02 5.97 6.42 6.30 6.19 6.13 6.59 6.47 6.35 6.30 6.78 6.66 6.54 6.48 6.97 6.84 6.72 6.66  
86  
83  
80  
77  
74  
71  
68  
35.5 44.5 48.7 49.4 39.4 49.2 50.7 51.3 43.3 53.9 52.6 53.3 47.0 57.2 53.3 54.0 50.8 60.6 53.9 54.6  
31.2 40.2 47.6 48.7 34.4 44.1 50.1 51.0 37.5 48.0 52.6 53.3 40.4 51.7 53.3 54.0 43.3 55.3 53.9 54.6  
27.0 35.9 43.3 44.4 39.3 39.1 47.1 48.2 31.7 42.2 50.9 52.1 33.8 45.0 52.4 53.4 35.9 47.8 53.9 54.6  
22.7 31.7 39.0 40.1 24.3 34.0 42.0 43.2 25.8 36.4 45.0 46.3 27.1 38.4 45.7 46.7 28.4 40.4 46.4 47.2  
18.4 27.4 34.8 35.8 19.2 29.0 37.0 38.1 20.0 30.5 39.2 40.4 20.5 31.7 39.1 40.1 21.0 32.9 39.0 39.7  
95 °F  
-
-
23.1 30.5 31.5  
18.8 26.2 27.3  
-
-
23.9 31.9 33.1  
18.9 26.9 28.0  
-
-
24.7 33.4 34.6  
18.9 27.5 28.8  
-
-
25.1 32.5 33.4  
18.4 25.8 26.8  
-
-
25.5 31.5 32.3  
18.0 24.1 24.8  
Net Cap  
MBH  
Total Power  
Input kW  
55.5 50.2 45.0 45.3 57.9 52.3 46.9 47.2 60.2 54.4 48.8 49.1 60.9 55.0 49.3 49.7 61.6 55.6 49.9 50.2  
6.90 6.73 6.63 6.58 7.07 6.90 6.79 6.75 7.25 7.06 6.96 6.91 7.47 7.28 7.17 7.12 7.69 7.50 7.38 7.33  
86  
83  
80  
77  
74  
71  
68  
33.5 42.4 45.0 45.3 37.5 47.1 46.9 47.2 41.4 51.8 48.8 49.1 44.9 53.7 49.3 49.7 48.3 55.6 49.9 50.2  
29.2 38.1 44.0 44.5 32.4 42.2 46.4 46.8 35.6 46.3 48.8 49.1 38.2 49.5 49.3 49.7 40.8 52.8 49.9 50.2  
24.9 33.8 39.8 40.2 27.4 37.1 43.6 44.2 29.8 40.5 47.5 48.1 31.6 42.9 48.7 49.2 33.4 45.3 49.9 50.2  
20.6 29.6 35.5 36.0 22.3 32.1 38.6 39.1 24.0 34.6 41.7 42.3 24.9 36.3 42.1 42.5 25.9 37.9 42.4 42.8  
16.4 25.3 31.2 31.7 17.2 27.0 33.5 34.1 18.1 28.8 35.9 36.4 18.3 29.6 35.4 35.9 18.5 30.4 35.0 35.3  
105 °F  
115 °F  
125 °F  
-
-
21.0 26.9 27.4  
16.7 22.7 23.1  
-
-
22.0 28.5 29.0  
16.9 23.4 23.9  
-
-
23.0 30.0 30.6  
17.1 24.2 24.8  
-
-
23.0 28.8 29.2  
16.3 22.1 22.6  
-
-
23.0 27.5 27.9  
15.5 20.1 20.4  
Net Cap  
MBH  
Total Power  
Input kW  
51.0 45.7 41.3 41.3 53.2 47.6 43.1 43.1 55.5 49.6 45.0 44.9 56.0 50.2 45.4 45.4 56.6 50.7 45.9 45.8  
7.56 7.33 7.23 7.20 7.73 7.50 7.39 7.36 7.90 7.66 7.56 7.52 8.15 7.90 7.80 7.76 8.40 8.15 8.04 8.00  
86  
83  
80  
77  
74  
71  
68  
31.4 40.3 41.3 41.3 35.5 45.0 43.1 43.1 39.6 49.6 45.0 44.9 42.7 50.2 45.4 45.4 45.8 50.7 45.9 45.8  
27.2 36.0 40.5 40.4 30.5 40.3 42.7 42.7 33.7 44.5 45.0 44.9 36.1 47.4 45.4 45.4 38.4 50.3 45.9 45.8  
22.9 31.7 36.2 36.1 25.4 35.2 40.2 40.1 27.9 38.7 44.2 44.1 29.4 40.8 45.0 45.0 30.9 42.9 45.9 45.8  
18.6 27.5 32.0 31.8 20.3 30.2 35.2 35.0 22.1 32.9 38.4 38.2 22.8 34.1 38.4 38.3 23.5 35.4 38.4 38.4  
14.3 23.2 27.7 27.6 15.3 25.1 30.1 30.0 16.2 27.0 32.5 32.4 16.1 27.5 31.8 31.7 16.0 27.9 31.0 30.9  
-
-
18.9 23.4 23.3  
14.6 19.1 19.0  
-
-
20.1 25.0 24.9  
15.0 20.0 19.9  
-
-
21.2 26.7 26.6  
15.4 20.9 20.7  
-
-
20.9 25.1 25.0  
14.2 18.5 18.4  
-
-
20.5 23.5 23.5  
13.0 16.1 16.0  
Net Cap  
MBH  
Total Power  
Input kW  
46.5 41.1 37.7 37.3 48.6 43.0 39.4 39.0 50.7 44.9 41.1 40.7 51.2 45.3 41.5 41.1 51.7 45.7 41.9 41.5  
8.2 7.9 7.8 7.8 8.4 8.1 8.0 8.0 8.5 8.3 8.2 8.1 8.8 8.5 8.4 8.4 9.1 8.8 8.7 8.7  
86  
83  
80  
77  
74  
71  
68  
29.4 38.2 37.7 37.3 33.6 42.9 39.4 39.0 37.7 44.9 41.1 40.7 40.5 45.3 41.5 41.1 43.3 45.7 41.9 41.5  
25.1 33.9 37.0 36.3 28.5 38.3 39.0 38.5 31.9 42.8 41.1 40.7 33.9 45.3 41.5 41.1 35.9 45.7 41.9 41.5  
20.8 29.6 32.7 32.0 23.4 33.3 36.8 36.0 26.0 36.9 40.9 40.0 27.2 38.7 41.4 40.7 28.4 40.4 41.9 41.5  
16.6 25.3 28.4 27.7 18.4 28.2 31.7 31.0 20.2 31.1 35.0 34.2 20.6 32.0 34.7 34.1 21.0 32.9 34.4 34.0  
12.3 21.1 24.1 23.4 13.3 23.2 26.7 25.9 14.4 25.3 29.2 28.4 14.0 25.4 28.1 27.5 13.5 25.5 27.0 26.6  
-
-
16.8 19.9 19.2  
12.5 15.6 14.9  
-
-
18.1 21.6 20.8  
13.1 16.6 15.8  
-
-
19.5 23.4 22.5  
13.6 17.5 16.7  
-
-
18.7 21.5 20.8  
12.1 14.8 14.2  
-
-
18.0 19.5 19.1  
10.6 12.1 11.7  
1. These are net capacity ratings. The indoor blower motor heat has already been subtracted from the gross cooling capacity  
ALL SENSIBLE CAPACITIES  
10  
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
TABLE 8: SIDE AND BOTTOM SUPPLY AIR BLOWER PERFORMANCE  
Blower  
Speed  
Setting CFM  
External Static Pressure (Inches Water Gauge)  
0.4 0.5 0.6 0.7 0.8  
CFM CFM CFM CFM CFM  
Model No.  
DEB  
0.1  
0.2  
CFM  
-
0.3  
CFM  
-
0.9  
CFM  
1.0  
CFM  
1.1  
CFM  
W
-
W
-
W
-
W
W
W
W
W
W
W
-
-
-
-
-
-
-
-
W
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
High  
-
-
-
1171 504 1080 486 990 468 888 456 786 444  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
030  
(2.5)  
Medium 1080 351 1021 341 961 331 902 321 841 305 781 290  
Low  
High  
Medium 1465 531 1395 512 1325 492 1255 473 1167 446 1079 419 992 392  
Low  
High  
Medium  
Low  
-
-
-
-
-
-
-
-
-
-
-
-
810 261 765 240  
-
-
-
-
-
-
-
-
-
-
-
-
1440 605 1361 581 1273 555 1185 530 1097 504 1004 480 912 456  
036  
(3.0)  
-
-
-
-
-
-
-
-
1316 473 1260 455 1204 438 1148 420 1069 396 990 372 911 348  
-
-
-
-
-
-
1728 725 1633 697 1527 666 1422 635 1317 605 1205 576 1094 547  
1674 614 1590 590 1506 567 1400 535 1295 502 1190 470 1063 428  
042  
(3.5)  
-
-
-
-
1579 567 1512 546 1444 525 1377 504 1282 476 1188 447 1093 418  
-
-
-
High  
-
-
1985 870 1939 850 1897 830 1813 800 1728 770 1644 740 1559 707 1474 673 1389 640  
048  
(4.0)  
Medium 1694 690 1662 673 1629 657 1597 640 1542 623 1486 607 1431 590 1336 563 1240 537  
Low  
High  
Medium 2339 1170 2275 1118 2211 1067 2147 1015 2083 963 2019 912 1955 860 1854 824 1753 788 1652 752  
Low 1929 940 1877 903 1824 867 1772 830 1720 793 1667 757 1615 720 1586 706 1557 691 1528 677  
-
-
-
-
1385 520 1349 510 1312 500 1276 490 1235 480  
-
-
-
-
-
-
-
-
-
-
-
-
2450 1213 2366 1165 2282 1117 2198 1068 2114 1020 1989 993 1864 967 1739 940  
060  
(5.0)  
TABLE 9: ADDITIONAL STATIC RESISTANCE  
Resistance, IWG  
CFM  
Description  
500  
.01  
.00  
.01  
.02  
600  
.01  
.00  
.02  
.03  
700  
.01  
.00  
.02  
.03  
800  
.02  
.01  
.02  
.03  
900  
.03  
.01  
.02  
.04  
1,000  
.04  
1,100  
.05  
1,200  
.06  
1,300  
.07  
1,400  
.08  
1,500  
.09  
1,600  
.09  
Wet Evaporator Coil  
Economizer  
.01  
.01  
.02  
.03  
.04  
.05  
.06  
Filter/Frame Kit  
Electric Heat  
.02  
.03  
.03  
.03  
.03  
.04  
.05  
.04  
.05  
.06  
.07  
.08  
.09  
.10  
Note:1. Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
2. The pressure thru the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct  
system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
CONTROL WIRING  
THERMOSTAT  
UNIT TERMINAL STRIP  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors  
can cause improper and dangerous  
**  
** =  
R
R
Minimum wire size of 18 AWG  
wire should be used for all field  
installed 24 volt wire.  
operation. Verify proper operation  
after servicing.  
24 VOLT  
G
Y
G
TRANSFORMER  
Y
W
C
PROGRAMMABLE  
THERMOSTAT ONLY  
NOTE:  
W
C
*
HEAT ANTICIPATOR  
SHOULD BE SET AT 0.25  
AMPS FOR ALL MODELS  
* =  
Only required on units with  
supplemental electric heat.  
POWER WIRING  
CONTACTOR  
CONTACTOR  
FIELD SUPPLIED  
DISCONNECT  
FIELD SUPPLIED  
DISCONNECT  
THREE  
PHASE  
SINGLE  
PHASE  
POWER  
SUPPLY  
POWER  
SUPPLY  
GROUND  
REFER TO ELECTRICAL DATA  
REFER TO ELECTRICAL DATA  
LUG  
GROUND  
LUG  
TABLES TO SIZE THE DISCON-  
NECT SWITCH, WIRING AND  
OVERCURRENT PROTECTION.  
TABLES TO SIZE THE DISCON-  
NECT SWITCH, WIRING AND  
OVERCURRENT PROTECTION.  
FIGURE 2 - TYPICAL FIELD WIRING DIAGRAM  
Johnson Controls Unitary Products  
11  
     
360101-XTG-B-0508  
TABLE 10: ELECTRICAL DATA  
VOLTAGE  
SUPPLY  
AIR  
BLOWER CIRCUIT  
MOTOR AMPACITY  
FLA  
MAX.  
HACR  
BREAKER POWER  
SIZE,  
AMPS  
30  
COND.  
FAN  
MOTOR,  
FLA  
MAX.  
FUSE2  
SIZE,  
COMPRESSOR  
LIMITATIONS1  
MINIMUM  
UNIT  
MODEL  
DEB  
POWER  
SUPPLY  
TRANSFORMER  
SIZE (VA)  
FACTOR  
MIN. MAX. RLA  
LRA  
AMPS  
30  
36  
42  
48  
60  
36  
42  
48  
60  
36  
42  
48  
60  
36  
42  
48  
60  
208/230-1-60 187  
208/230-1-60 187  
208/230-1-60 187  
208/230-1-60 187  
208/230-1-60 187  
208/230-3-60 187  
208/230-3-60 187  
208/230-3-60 187  
208/230-3-60 187  
253  
253  
253  
253  
253  
253  
253  
253  
253  
504  
504  
504  
504  
630  
630  
630  
630  
14.7  
17.3  
15.5  
24.4  
28.9  
10.9  
11.5  
14.1  
16.0  
5.8  
73  
94  
1.1  
1.1  
1.1  
1.3  
1.3  
1.1  
1.1  
0.7  
1.3  
0.6  
0.6  
0.6  
0.7  
0.4  
0.4  
0.6  
0.6  
2.6  
3.5  
3.5  
4.0  
4.0  
3.5  
3.5  
4.0  
7.0  
1.8  
1.8  
2.0  
3.5  
1.5  
1.5  
1.6  
2.8  
22.1  
26.2  
23.9  
35.8  
44.4  
18.2  
19.0  
22.3  
28.3  
9.6  
30  
35  
30  
45  
60  
25  
25  
30  
40  
15  
15  
15  
20  
15  
15  
15  
15  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
0.96  
40  
40  
40  
40  
40  
75  
75  
75  
75  
75  
75  
75  
75  
75  
75  
75  
75  
35  
86  
30  
140  
45  
165  
60  
78.0  
88.0  
105.0  
125.0  
40.0  
42.0  
55.0  
67.0  
32.0  
44.0  
44.0  
50.0  
25  
25  
30  
40  
460-3-60  
460-3-60  
460-3-60  
460-3-60  
575-3-60  
575-3-60  
575-3-60  
575-3-60  
414  
414  
414  
414  
518  
518  
518  
518  
15  
5.8  
9.7  
15  
7.1  
11.5  
14.2  
7.6  
15  
8.0  
20  
4.5  
15  
5.8  
9.1  
15  
5.6  
9.3  
15  
6.4  
11.4  
15  
1. Rated in accordance with ARI Standard 110, utilization range “A”.  
2. Dual element, time delay type.  
KW CAP.  
NOMINAL VOLTAGE VOLTAGE  
MULTIPLIER  
ELECTRIC HEAT  
CORRECTION  
FACTORS  
208  
230  
.75  
.92  
240  
480  
600  
460  
575  
.92  
.92  
TABLE 11: ELECTRICAL DATA (COOLING / ELECTRIC HEAT)  
SUPPLY  
COND. FAN  
MOTORS BLOWER  
MOTOR  
AIR  
MAX FUSE/  
SIZE  
(AMPS)  
2
COMPRESSOR  
ELECTRIC HEAT ACCESSORY  
MODEL  
DEB  
POWER  
SUPPLY  
MCA  
(AMPS)  
MAX HACR  
1
BREAKER SIZE  
RLA  
LRA  
FLA  
FLA  
MODEL NO. STAGE  
KW  
TOTAL AMPS  
2NH04500506  
2NH04500706  
2NH04501006  
2NH04501506  
2NH04501006  
2NH04501506  
2NH04500506  
2NH04500706  
2NH04501006  
2NH04501506  
2NH04501006  
2NH04501506  
2NH04502006  
2NH04502506  
2NH04501006  
2NH04501506  
2NH04502006  
2NH04502506  
2NH04501025  
2NH04501525  
1
2
2
2
2
2
1
2
2
2
2
2
2
2
2
2
2
2
1
1
3.8/5.0*  
18.1/20.8  
27.3/31.3  
36.1/41.7  
54.2/62.5  
36.1/41.7  
54.2/62.5  
18.1/20.8  
27.1/31.3  
36.1/41.7  
54.2/62.5  
36.1/41.7  
54.2/62.5  
72.2/83.3  
25.8/29.3  
37.1/42.3  
48.4/55.3  
71.0/81.4  
49.5/56.5  
72.1/82.5  
26.9/30.4  
38.2/43.4  
49.5/56.5  
72.1/82.5  
50.1/57.1  
72.1/83.1  
95.3/109.2  
30/30  
40/45  
50/60  
80/90  
50/60  
80/90  
35/35  
40/45  
50/60  
80/90  
60/60  
80/90  
100/110  
30/30  
40/45  
50/60  
80/90  
50/60  
80/90  
35/35  
40/45  
50/60  
80/90  
60/60  
80/90  
100/110  
125/150  
70/70  
80/90  
100/125  
125/150  
35/35  
45/50  
5.6/7.5*  
030 208/230-1-60 12.0  
036 208/230-1-60 17.3  
042 208/230-1-60 15.5  
73.0  
1.1  
2.6  
7.5/10.0*  
11.3/15.0*  
7.5/10.0*  
11.3/15.0*  
3.8/5.0*  
94.0  
86.0  
1.1  
1.1  
3.5  
3.5  
5.6/7.5*  
7.5/10.0*  
11.3/15.0*  
7.5/10.0*  
11.3/15.0*  
15.0/20.0*  
048 208/230-1-60 24.4  
140.0  
1.3  
4.0  
18.8/25.0* 90.3/104.2 117.8/135.2 125/150  
7.5/10.0*  
11.3/15.0*  
15.0/20.0*  
36.1/41.7  
54.2/62.5  
72.2/83.3  
53.9/60.8  
76.5/86.9  
99.0/112.9  
70/70  
80/90  
060 208/230-1-60 38.0  
036 208/230-3-60 10.9  
165.0  
78.0  
1.3  
1.1  
7.0  
3.5  
100/125  
18.8/25.0* 90.3/104.2 121.6/139.0 125/150  
7.5/10.0*  
20.8/24.1  
31.3/36.1  
30.4/34.4  
43.5/49.5  
35/35  
45/50  
11.3/15.0*  
12  
Johnson Controls Unitary Products  
   
360101-XTG-B-0508  
TABLE 11: ELECTRICAL DATA (COOLING / ELECTRIC HEAT) (CONTINUED)  
SUPPLY  
COND. FAN  
MOTORS BLOWER  
MOTOR  
AIR  
MAX FUSE/  
SIZE  
(AMPS)  
2
COMPRESSOR  
ELECTRIC HEAT ACCESSORY  
MODEL  
DEB  
POWER  
SUPPLY  
MCA  
(AMPS)  
MAX HACR  
1
BREAKER SIZE  
RLA  
LRA  
FLA  
FLA  
MODEL NO. STAGE  
KW  
7.5/10.0*  
11.3/15.0*  
7.5/10.0*  
11.3/15.0*  
15.0/20.0*  
18.8/25.0*  
7.5/10.0*  
11.3/15.0*  
15.0/20.0*  
18.8/25.0*  
10.0**  
TOTAL AMPS  
2NH04501025  
2NH04501525  
2NP04501025  
2NP04501525  
2NP04502025  
2NH04502525  
2NH04501025  
2NH04501525  
2NH04502025  
2NH04502525  
2NH04501046  
2NH04501546  
2NH04501046  
2NH04501546  
2NP04501046  
2NH04501546  
2NH04502046  
2NH04502546  
2NH04501046  
2NH04501546  
2NP04502046  
2NP04502546  
2NH04501058  
2NH04501558  
2NH04501058  
2NH04501558  
2NH04501058  
2NH04501558  
2NH04502058  
2NH04502558  
2NH04501058  
2NH04501558  
2NP04502058  
2NP04502558  
1
1
1
1
2
2
1
1
2
2
1
1
1
1
1
1
2
2
1
1
2
2
1
1
1
1
1
1
2
2
1
1
2
2
20.8/24.1  
31.3/36.1  
20.8/24.1  
31.3/36.1  
41.7/48.1  
52.1/60.1  
20.8/24.1  
31.3/36.1  
41.7/48.1  
52.1/60.1  
12  
30.4/34.4  
43.5/49.5  
31.1/35/1  
44.1/50.1  
57.1/65.1  
70.2/80.2  
34.8/38.8  
47.8/53.9  
60.9/68.9  
73.9/83.9  
17.3  
35/35  
45/50  
35/40  
45/60  
60/70  
80/90  
40/40  
50/60  
70/70  
80/90  
20  
35/35  
45/50  
35/40  
45/60  
60/70  
80/90  
40/40  
50/60  
70/70  
80/90  
20  
042 208/230-3-60 11.5  
048 208/230-3-60 14.1  
88.0  
1.1  
3.5  
105.0  
125.0  
0.7  
1.3  
4.0  
7.0  
060 208/230-3-60 16.0  
036  
042  
460-3-60  
460-3-60  
5.8  
5.8  
40.0  
42.0  
0.6  
0.6  
1.8  
1.8  
15.0**  
18  
24.8  
25  
25  
10.0**  
12  
17.3  
20  
20  
15.0**  
18  
24.8  
25  
25  
10.0**  
12  
17.5  
20  
20  
15.0**  
18  
25.1  
30  
30  
048  
060  
460-3-60  
460-3-60  
7.1  
8.0  
55.0  
67.0  
0.8  
0.7  
2.0  
3.5  
20.0**  
24.1  
32.6  
35  
35  
25.0**  
30.1  
40.1  
45  
45  
10.0**  
12  
19.4  
20  
20  
15.0**  
18  
26.9  
30  
30  
20.0**  
24.1  
34.4  
35  
35  
25.0**  
30.1  
42  
45  
45  
10.0***  
15.0***  
10.0***  
15.0***  
10.0***  
15.0***  
20.0***  
25.0***  
10.0***  
15.0***  
20.0***  
25.0***  
9.6  
13.9  
15  
15  
036  
042  
575-3-60  
575-3-60  
4.5  
5.8  
32.0  
44.0  
0.4  
0.4  
1.5  
1.5  
14.4  
19.9  
20  
20  
9.6  
13.9  
15  
15  
14.4  
19.9  
20  
20  
9.6  
14  
15  
15  
14.4  
20  
25  
25  
048  
060  
575-3-60  
575-3-60  
5.6  
6.4  
44.0  
50.0  
0.6  
0.6  
1.6  
2.8  
19.2  
26.1  
30  
30  
24.1  
32.1  
35  
35  
9.6  
15.5  
20  
20  
14.4  
21.5  
25  
25  
19.2  
27.6  
30  
30  
24.1  
33.6  
35  
35  
1. Dual element, time delay type.  
2. Standard circuit breakers may be used in Canada and on applications over 60 amps where the heaters are separately fused.  
* = KW listed is for 240 volts, use table on previous page for 208 or 230 volts.  
** = KW listed is for 480 volts, use table on previous page for 460 volts.  
*** = KW listed is for 600 volts, use table on previous page for 575 volts.  
Johnson Controls Unitary Products  
13  
360101-XTG-B-0508  
HIGH VOLTAGE CONN.  
" DIA. KNOCKOUT  
FRONT  
“A”  
COMPRESSOR  
SERVICE ACCESS  
HIGH VOLTAGE CONN.  
" DIA. KNOCKOUT  
COMPARTMENT PANEL  
DIMENSION  
LOW VOLTAGE CONN.  
“ DIA. KNOCKOUT  
UNIT SIZE  
“A”  
(OVERALL)  
2
030 - 042  
048 - 060  
33  
41  
SIDE SUPPLY  
AIR OPENING  
REFRIGERANT  
CONNECTIONS  
SIDE RETURN  
AIR OPENING  
ELECTRICAL/FILTER  
SERVICE ACCESS  
COMPARTMENT PANEL  
HIGH VOLTAGE CONN.  
" DIA. KNOCKOUT  
(OVERALL)  
2
(OVERALL)  
1
LOW VOLTAGE CONN.  
“ DIA. KNOCKOUT  
UNIT CONDENSATE  
CONNECTION “ NPTI  
(TRAP REQUIRED)  
4
FRONT  
HIGH VOLTAGE  
CONN. “ x " DIA.  
KNOCKOUT  
SIDE SUPPLY  
AIR OPENING  
BACK  
CONDENSER  
COIL  
6
SIDE RETURN  
AIR OPENING  
CONDENSATE  
DRAIN “ NPTI  
BOTTOM SUPPLY  
AIR OPENING  
2
1
CLEARANCES  
(Minimum)  
Front  
Back  
12"  
0"  
15  
15  
4
Left Side (Filter Access) 24"  
1
15  
Right Side  
24"  
0"  
Below Unit 1  
BOTTOM RETURN  
AIR OPENING  
36" (For Condenser  
Above Unit 2  
Air Discharge)  
1
1 Units may be installed on combustible floors made from wood or class A,  
B or C roof covering material.  
2 Units must be installed outdoors. Overhanging structures or shrubs  
should not obstruct outdoor air discharge outlet.  
FIGURE 3 - UNIT DIMENSIONS  
14  
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
TABLE 12: UNIT WEIGHTS  
Corner Weights  
Shipping  
Unit Size  
Operating  
Weight  
Economizer  
(lbs.)  
Roof Curb  
(lbs.)  
Weight  
A
85  
91  
94  
92  
105  
B
81  
80  
83  
88  
100  
C
D
030  
036  
042  
048  
060  
333  
338  
347  
368  
376  
328  
333  
342  
363  
371  
82  
78  
80  
92  
84  
86  
88  
91  
97  
87  
8" - 70  
14" - 75  
40  
CENTER OF GRAVITY  
D
B
C
FRONT  
A
OF  
UNIT  
26  
FIGURE 4 - CENTER OF GRAVITY  
Johnson Controls Unitary Products  
15  
   
360101-XTG-B-0508  
TYPICAL APPLICATIONS  
SUPPLY AIR  
DUCT  
RETURN AIR  
DUCT  
FIELD SUPPLIED  
DISCONNECT SWITCH  
LOCATED TO REAR OF UNIT  
TO POWER SUPPLY  
CONTROL WIRING  
TO INDOOR  
THERMOSTAT  
FIGURE 5 - TYPICAL SLAB ON GROUND INSTALLATION  
FIELD SUPPLIED  
DISCONNECT SWITCH  
MOUNTED ON UNIT  
TO POWER SUPPLY  
CONTROL WIRING  
TO INDOOR THERMOSTAT  
SUPPLY AIR  
DUCT  
ROOF CURB  
INSTALLATION  
ROOF CURB  
REAR DUCT  
RETURN AIR  
DUCT  
INSTALLATION  
BOTTOM DUCT  
SLAB ON GROUND  
INSTALLATION  
FIGURE 6 - TYPICAL ROOF CURB INSTALLATION  
16  
Johnson Controls Unitary Products  
     
360101-XTG-B-0508  
1
4
OPENING FOR  
RETURN AIR DUCT  
22  
OPENING FOR  
SUPPLY AIR DUCT  
1
14  
FRONT  
WOOD NAILER  
INSULATED  
PANELS  
RECOMMENDED DUCT SIZE  
SUPPLY AIR DUCT  
RETURN AIR DUCT  
" x  
" x  
"
"
FIGURE 7 - ROOF CURB DIMENSIONS (8” Roof curb also available)  
1"  
" x 1" WIDE GASKETING FOR CURB FRAME  
AND ALL DUCT SUPPORT SURFACES  
UNIT BASE RAIL  
COUNTERFLASHING  
CANT STRIP  
UNIT BASE  
WOOD NAILER  
8" MIN. ABOVE FINISHED ROOF  
14"  
INSULATION AND ROOFING MATERIAL  
CURB FRAME  
INSULATION  
ROOF DECK AND ROOFING MATERIAL  
FIGURE 8 - ROOF CURB APPLICATION  
Johnson Controls Unitary Products  
17  
   
360101-XTG-B-0508  
SEE  
DETAIL  
"A"  
OPTIONAL CCH  
S / P CONFIGURATION  
CCH  
BLK  
BLK  
L1  
T1  
D / P CONFIGURATION  
CCH  
BLK  
L1  
BLK  
2
L
M1 - 2  
L2  
T2  
DETAIL "A"  
15695BASH0301  
FIGURE 9 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY) DEB MODELS  
18  
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
TYPICAL WIRING DIAGRAM NOTES  
TYPICAL WIRING DIAGRAM LEGEND  
- F 9  
- 6  
(N O  
T U S E D )  
-
2
- M  
3
, 2 3 0 V C O IL  
-
-
-
-
FIGURE 10 -TYPICAL WIRING DIAGRAM (208/230-3-60 POWER SUPPLY) DEB MODELS  
Johnson Controls Unitary Products  
19  
 
360101-XTG-B-0508  
2
FIGURE 11 -TYPICAL WIRING DIAGRAM (460-3-60 AND 575-3-60 POWER SUPPLY) DEB MODELS  
20  
Johnson Controls Unitary Products  
 
360101-XTG-B-0508  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
MECHANICAL SPECIFICATIONS  
1. Fan shall be direct drive, multi-speed design. Job site  
selected (BHP) brake horse power shall not exceed the  
motors nameplate horse power rating.  
GENERAL DESCRIPTION  
Units shall be factory-assembled, single packaged, Electric  
Cooling units, designed for outdoor mounted installation. They  
shall have built in, equal size, field convertible duct connections  
for down discharge supply/return or horizontal discharge  
supply/return.  
2. Fan wheel shall be double-inlet type with forward-curved  
blades, dynamically balanced to operate smoothly  
throughout the entire range of operation. Airflow design  
shall be constant air volume.  
3. Bearings shall be sealed and permanently lubricated for  
longer life and no maintenance.  
The units shall be factory wired, piped, charged with R-22  
refrigerant and factory tested prior to shipment. All unit wiring  
shall be both numbered and color coded.  
4. Fan assembly shall be “Slip Track” (slide-out) design for  
easy removal and cleaning.  
All units shall be manufactured in a facility certified to ISO 9001  
standards, and the cooling performance shall be tested in  
accordance with ARI test procedures. Units shall be certified to  
UL 1995/CAN/CSA C22.2 No. 236 standards.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
1. The outdoor fan shall be of the direct-driven propeller type,  
discharge air vertically, have aluminum blades riveted to  
corrosion resistant steel spider bracket and shall be  
statically balanced for smooth operation.  
UNIT CABINET  
1. Unit cabinet shall be constructed of galvanized steel, with  
exterior surfaces coated with a non-chalking, powdered  
paint finish, certified at 1000 hours salt spray test per  
ASTMB117 standards.  
2. The outdoor fan motor shall be totally enclosed with  
permanently lubricated bearings and internally protected  
against overload conditions.  
2. The unit top shall be a single piece “Water Shed” design,  
with drip edges and no-seam corners to provide optimum  
water integrity  
REFRIGERANT COMPONENTS  
1. Compressors:  
3. Unit shall have a rigidly mounted condenser coil guard to  
provide protection from objects and personnel after  
installation.  
a. Shall be fully hermetic reciprocating type, direct drive,  
internally protected with internal high-pressure relief and  
over temperature protection. The hermetic motor shall be  
suction gas cooled and have a voltage range of + or -  
10% of the unit nameplate voltage.  
4. Indoor blower section shall be insulated with up to 3/4”  
thick, aluminum, foil faced insulation, fastened to prevent  
insulation from entering the air stream.  
b Shall have internal isolation and sound muffling to  
minimize vibration and noise, and be externally isolated  
on a dedicated, independent mounting.  
5. Cabinet panels shall be “large” size, easily removable for  
servicing and maintenance, with built-in lift handles.  
6. Unit shall be built on a formed, “Super-Structure” design  
base pan, with embossments at critical points to add  
strength, rigidity and aid in minimizing sound.  
2. Coils:  
a. Evaporator and condenser coils shall have aluminum  
plate fins mechanically bonded to seamless internally-  
enhanced copper tubes with all joints brazed.  
7. Full perimeter base rails shall be provided to assure  
reliable transit of equipment, overhead rigging, fork truck  
access and proper sealing on roof curb applications. Base  
rails shall be removable, when required, to lower unit  
height.  
b Evaporator and Condenser coils shall be of the direct  
expansion, draw-thru design.  
3. Refrigerant Circuit and Refrigerant Safety Components  
shall include:  
8. Filters shall be furnished and be accessible through a  
removable access door, sealed air tight. (Single phase  
models - accessory kit available. Three phase models -  
standard from factory.)  
a. Independent fixed-orifice expansion devices.  
b. Filter/strainer to eliminate any foreign matter.  
c. Accessible service gauge connections on both suction  
and discharge lines to charge, evacuate, and measure  
refrigerant pressure during any necessary servicing or  
troubleshooting, without losing charge and without  
disrupting condenser or evaporator air flow.  
9. Units vertical discharge and return duct configuration shall  
be designed to fit between standard 24” O.C. beams  
without modification to building structure, duct work and  
base unit.  
10. Condensate pan shall be internally sloped and conform to  
ASHRAE 62-89 self-draining standards, with 3/4” NPTI  
copper, ridged mount connection.  
d The refrigeration system shall provide at least 10° F of  
liquid sub-cooling at design conditions.  
4. Unit Controls:  
a. Unit shall contain a large, low voltage Terminal Board for  
easy connection of field low voltage wiring.  
Johnson Controls Unitary Products  
21  
 
360101-XTG-B-0508  
b. Controls shall be mounted in a large control box with tilt-  
out, hinged access door, allowing easy access for trouble  
shooting and maintenance without affecting the normal  
system operation pressures.  
4. Units with electric heating sections shall be wired for a  
single point power supply, with branch circuit fusing (where  
required).  
UNIT OPERATING CHARACTERISTICS  
c. Unit shall have large, easily removable panels, covering  
electrical controls and compressor, allowing easy access  
for any necessary maintenance or servicing.  
1. Unit shall be capable of starting and running at 125° F  
outdoor temperature, exceeding maximum load criteria of  
ARI Standard 210/240.  
ELECTRIC HEATING SECTION  
2. The compressor, with standard controls, shall be capable  
of operation down to 45° F outdoor temperature. Accessory  
low ambient kit shall be available for operation to 0° F.  
1. An electric heating section, with nickel chromium elements,  
shall be provided in a range of 5 thru 25 KW, offering two  
stages of capacity - 7 KW and above on single phase  
heaters, and 20 KW and above on three phase heaters.  
ELECTRICAL REQUIREMENTS  
2. The heating section shall have a primary limit control(s)  
and automatic reset, to prevent the heating element  
system from operating at an excessive temperature.  
All unit power wiring shall enter unit cabinet at a single factory  
provided location and be capable of side or bottom entry, to  
minimize roof penetrations and avoid unit field modifications.  
Separate side and bottom openings shall be provided for the  
control wiring.  
3. The heating section assembly shall slide out of the unit for  
easy maintenance and service.  
22  
Johnson Controls Unitary Products  
360101-XTG-B-0508  
Johnson Controls Unitary Products  
23  
Subject to change without notice. Printed in U.S.A.  
360101-XTG-B-0508  
Copyright © 2008 by Johnson Controls, Inc. All rights reserved.  
Supersedes: 360101-XTG-A-0108  
Johnson Controls Unitary Products  
5005 York Drive  
Norman, OK 73069  

Mitsubishi Electronics Peh 25eka User Manual
Murphy Diesel Fuel Check Valves Ckv1wps User Manual
Nutone 9198nt User Manual
Rival Vs120 S User Manual
Schumacher Automatic Psw 70300a User Manual
Schumacher Sf 6242a User Manual
Sears 53ds900077 User Manual
Sharp Replacement Filter Fzc100hfu User Manual
Soleus Air Air Conditioner Gb Ttw 12esez User Manual
Tripp Lite Aps Powerverter User Manual