036-21359-001-B-0302
DESCRIPTION
®
Sunline™ 2000 series convertible package rooftop mod-
els have two independent refrigerant circuits for efficient
part load operation. Although the units are primarily
designed for curb mounting on a roof, they can also be
slab-mounted at ground level or set on steel beams above
a finished roof.
Cooling only, cooling with gas heat and cooling with electric
heat models are available with a wide variety of factory-
mounted options and field-installed accessories to make
them suitable for almost every application.
Technical Guide
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead
rigging.
Every unit is completely piped, wired, charged and tested
at the factory to simplify field installation and to provide
years of dependable operation. Powder paint cabinets pro-
vide an exceptionally durable finish with the 750 hour salt
spray process per ASTM-B117 test standard.
All models (including those with an economizer) are suit-
able for either bottom or horizontal duct connections. Mod-
els with power exhaust are suitable for bottom duct
connections only. For bottom duct, you remove the sheet
metal panels from the supply and return air openings
through the base of the unit. For horizontal duct, you
replace the supply and return air panels on the rear of the
unit with a side duct flange accessory.
SINGLE PACKAGE
GAS / ELECTRIC UNITS AND
SINGLE PACKAGE AIR CONDITIONERS
All models are available with five different outdoor air
damper options:
D2CE / D2CG 300 CONSTANT VOLUME
25 NOMINAL TONS
8.5 EER
• Single enthalpy economizer
• Differential (dual) enthalpy economizer
• Single enthalpy economizer with power exhaust
SUNLINE 2000 ™
• Differential (dual) enthalpy economizer with
power exhaust
• Motorized outdoor air damper
A fixed outdoor air intake assembly is shipped in the return
air compartment of all units ordered without an economizer
or motorized outdoor air damper option. The assembly
includes a rain hood with a damper that can be set for 10,
15 or 25% outdoor air. With bottom duct connections, the
intake damper assembly should be mounted over the
opening in the return air panel. With horizontal ductwork, it
should be mounted on the return air duct.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21359-001-B-0302
ANTI-RECYCLE TIMERS
FIELD-INSTALLED ACCESSORIES
Two solid state timers prevent the compressors from
short-cycling. Once a compressor is de-energized, it
will remain de-energized for approximately five min-
utes.
SINGLE INPUT ELECTRONIC ENTHALPY
ECONOMIZERS
Includes a slide-in/plug-in damper assembly with fully
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
HIGH ALTITUDE NATURAL GAS
Burner orifices and pilot orifices are provided for proper
furnace operation at altitudes up to 6,000 feet.
The enthalpy system contains one sensor that
monitors the outdoor air and determines when the air is
cool enough and dry enough to provide “free” cooling.
PROPANE
Burner orifices, pilot orifices and gas valve parts are
provided to convert a natural gas furnace to propane.
The rainhood is painted to match the basic unit and
must be field-assembled before installing.
HIGH ALTITUDE PROPANE
Power exhaust is not available as a field installed
option.
Burner orifices and pilot orifices are provided for proper
furnace operation at altitudes up to 6,000 feet. This
accessory supplements the basic propane conversion
kit.
DUAL INPUT ELECTRONIC ENTHALPY
ECONOMIZERS
Includes a slide-in / plug-in damper assembly with fully
modulating spring-return monitor actuator capable of
introducing up to 100% outdoor air with nominal 1%
leakage type dampers.
SIDE DUCT FLANGES
One inch flanges replace the supply and return air pan-
els on the rear of the unit to accommodate horizontal
duct connections. These flanges can also be used indi-
vidually for bottom supply/horizontal return or horizon-
tal supply/bottom return. They cannot be used on units
with power exhaust.
This enthalpy system contains one sensor that moni-
tors the outdoor air and one sensor that monitors the
return air. The logic module compares these two val-
ues and modulates the dampers providing the maxi-
mum efficiency of economizer system.
BAROMETRIC RELIEF DAMPER
This damper accessory can be used to relieve internal
air pressure on units with an economizer but no power
exhaust. This accessory includes a rain hood, a bird
screen and a fully assembled damper. With bottom
duct connections, the damper should be mounted over
the opening in the return air panel. With horizontal
ductwork, the accessory should be mounted on the
return air duct.
The rainhood is painted to match the basic unit and
must be field-assembled before installing.
Power exhaust is not available as a field installed
option.
MOTORIZED OUTDOOR AIR INTAKE DAMPER
Includes a slide-in/plug-in damper assembly with a
2-position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower
is operating and will drive fully closed when the blower
unit shuts down.
ECONOMIZER / POWER EXHAUST RAIN HOODS
A rain hood accessory must be used on units with an
economizer, a motorized damper, or a combined econ-
omizer with power exhaust option. These accessories
include all the hood panels, the necessary components
and hardware for field assembly.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
Power exhaust is not available as a field installed
option.
HIGH SPEED DRIVE
A smaller blower pulley and a shorter belt increase the
speed of the supply air blower for applications with a
higher CFM and/or static pressure requirement.
ROOF CURBS
Fourteen inch high roof curbs provide a water-tight seal
between the unit and the finished roof. These full
perimeter curbs meet the requirements of the National
Roofing Contractors Association (NRCA) and are
shipped knocked-down for field assembly. They're
designed to fit inside the base rails of the unit and
include both a wood nailing strip and duct hanger sup-
ports.
LOW AMBIENT CONTROLS TO 0°F
An autotransformer and a thermostat maintain stable
system operation by reducing the speed of the con-
denser fan motor at low outdoor temperatures. The kit
Unitary Products Group
3
036-21359-001-B-0302
also includes a 1-phase motor to replace the unit's
standard 3-phase condenser fan motor. Standard units
can operate down to 45°F.
Provides coil guard and fastners.
COIL GUARD KIT
E
(
L
E
C
T
R
I
C
H
E
A
T
E
R
L
O
C
A
T
I
O
N
L
P
O
N
G
L
A
S
T
I
N
O
G
P
T
I
O
N
A
L
E
L
E
C
T
R
H
I
I
C
G
/
H
E
L
E
E
F
C
F
T
I
R
C
I
I
C
E
N
U
C
N
Y
I
T
S
S
C
)
R
O
L
L
C
O
M
P
R
E
S
S
O
R
S
O
W
D
E
R
P
A
I
N
T
F
I
N
I
S
H
C
C
O
O
P
N
P
E
R
T
U
B
E
/
A
L
U
M
I
N
U
M
F
I
N
2
T
0
G
A
U
G
E
A
L
U
M
I
N
I
Z
E
D
S
T
E
E
L
D
E
N
S
E
R
C
O
I
L
S
U
B
U
L
A
R
H
E
A
T
E
X
C
H
A
N
G
E
R
S
L
A
O
W
V
O
L
T
A
G
E
R
E
L
A
Y
B
O
A
R
D
E
C
O
N
O
M
I
Z
E
R
H
O
O
D
N
D
T
E
R
M
I
A
N
L
S
T
R
I
P
E
M
(
L
E
C
T
R
I
C
A
L
D
I
S
C
O
N
N
E
C
T
O
U
N
T
I
N
G
L
O
C
A
T
I
O
N
F
i
e
l
d
i
n
s
t
a
l
l
e
d
)
K
S
N
I
O
C
K
O
U
T
F
O
R
D
E
C
O
N
T
R
O
L
W
I
R
I
N
G
E
N
T
R
Y
K
S
N
I
O
C
K
O
U
T
F
O
R
D
E
P
O
W
E
R
W
I
R
I
N
G
E
N
T
R
Y
S
I
D
E
2
F
"
D
I
S
P
O
S
A
B
L
E
T
(
w
E
E
R
M
I
N
A
L
B
L
O
C
K
I
L
T
E
R
S
F
o
t
r
S
i
n
g
l
e
P
o
i
n
t
P
o
w
e
r
S
u
p
p
l
y
i
h
E
l
e
c
t
r
i
c
H
e
a
t
)
L
E
C
T
R
I
C
/
E
L
E
C
T
R
I
C
U
N
I
T
S
U
T
D
O
O
R
A
I
R
O
P
E
N
I
N
G
F
I
O
R
S
L
I
D
E
-
I
N
/
P
L
U
G
-
I
N
B
W
O
T
T
O
M
P
O
W
E
R
&
C
O
N
T
R
O
L
N
T
E
R
N
A
L
E
C
O
N
O
M
I
Z
E
R
(
O
P
T
I
O
N
)
I
R
I
N
G
E
N
T
R
Y
K
G
N
O
C
K
O
U
T
S
F
O
R
S
I
D
E
S
S
D
I
U
D
E
A
N
D
B
O
T
T
O
M
A
S
S
U
P
P
L
Y
E
N
T
R
Y
H
G
O
L
E
F
O
R
B
O
T
T
O
M
P
P
L
Y
&
R
E
T
U
R
N
A
I
R
A
S
S
U
P
P
L
Y
E
N
T
R
Y
U
C
T
O
P
E
N
I
N
G
S
(
S
I
D
E
X
S
I
D
E
)
P
W
O
W
E
R
V
E
N
T
O
R
M
O
T
O
R
N
P
I
T
1
C
"
N
P
T
I
I
T
H
P
O
S
T
P
U
R
G
E
C
Y
C
L
E
B
B
E
L
L
T
-
D
R
I
V
E
O
N
D
E
N
S
A
T
E
D
R
A
I
N
O
W
E
R
M
O
T
O
R
F
R
U
L
L
P
E
R
I
M
E
T
E
R
1
4
G
U
A
G
E
B
A
S
E
A
I
L
S
W
I
T
H
L
I
F
T
I
N
G
H
O
L
E
S
CAPACITY RATINGS - (ARI 360)*
MODEL MBH EER IPLV
COOLING WITH GAS HEAT
MODEL
COOLING WITH ELECTRIC HEAT
MBH EER IPLV
D2CG300N240
D2CG300N320
COOLING ONLY
D2CE300
290
8.5
8.3
D2CE300E018
D2CE300E036
D2CE300E054
D2CE300E072
290
290
287
284
8.5
8.5
8.5
8.5
8.6
8.6
8.2
8.2
290
8.5
8.3
290
8.5
8.7
*.
Outside the scope of ARI Standard 340/360.
EER=Energy Efficiency Rating at full load-the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per
watt (Btuh/watt).
IPLV - Integrated part load value.
NOTE: All cooling is three stage.
Note: All gas units are two-stage heating. First stage is 50% of total.
GAS HEAT RATINGS
All models are 80% Steady State Efficiency (S.S.E.).
MBH Input
MBH Output
MODEL
Stage
1&2
300
Stage
1&2
240
Stage 1
Stage 1
D2CG300N240
D2CG300N320
150
200
120
160
400
320
Sound Power (db 10-12 Watts)
Octave Band Centerline Frequency (Hz) SWL
IWG RPM BHP 63 125 250 500 1,000 2,000 4,000 8,000 db(A)
ESP
Blower
Unit CFM
db(A)
@ 10 Ft.*
65
Size
)
300 10,000 1.30 1,160 12.5 108 108 98 91
93
86
81
76
98
*.
At a distance of 10 ft.from the blower.
NOTE: These values have been derived using a model of sound propagation,
measuring the indoor ambient sound levels ten feet from the source. The dBA
values provided are for reference only. Calculation of dBA values cover matters
of system design and application. This constitutes an exception to any specifi-
cation or guarantee requiring a dBA value or sound data in any other form than
sound power level ratings.
4
Unitary Products Group
036-21359-001-B-0302
COOLING CAPACITIES- 25 TON (DCE / DCG300)
Tem pera ture of Air on Con denser Coil
Air On
Evaporator
Coil
85?F
95?F
SensibleCapacity1, MBH
SensibleCapacity1, MBH
Total Power
Cap.1 Input2
Total Power
Cap.1 Input2
WB
CFM
EnteringDryBulb, ?F
86 83 80 77 74 71 68
EnteringDryBulb, ?F
86 83 80 77 74 71 68
MBH
KW
MBH
KW
?F
72
371
340
329
329
365
336
324
324
359
332
318
318
354
326
314
314
349
321
310
310
318
290
282
282
27.1 277 240 203 167 130
-
-
354
28.8 268 231 195 158 122
-
-
67
12,000
62
26.1 335 299 262 226 189 152 116 325
25.5 329 329 329 293 256 219 183 315
25.5 329 329 329 292 256 219 183 314
27.7 324 288 251 214 178 141 105
27.1 315 315 315 278 241 205 168
27.1 314 314 314 278 241 205 168
57
72
27.0 260 226 193 159 125
-
-
348
28.6 257 223 189 155 122
-
-
67
11,000
62
25.9 317 283 249 216 182 148 114 321
25.3 324 324 313 279 245 212 178 309
25.3 324 324 315 281 247 214 180 309
27.5 312 279 245 211 178 144 110
26.9 309 309 307 273 239 206 172
26.9 309 309 309 275 242 208 174
57
72
26.8 244 213 182 151 120
-
-
342
28.5 245 214 184 153 122
-
-
67
10,000
62
25.7 298 268 237 206 175 144 113 317
25.2 318 318 296 265 235 204 173 304
25.1 318 318 301 270 239 208 177 304
27.4 301 270 239 208 177 146 115
26.8 304 304 299 268 237 207 176
26.7 304 304 304 273 242 211 180
57
72
26.6 229 201 173 145 117
-
-
338
28.2 228 200 172 144 116
-
-
67
9,000
62
25.5 280 252 224 196 168 141 113 312
25.0 314 306 282 254 226 198 170 300
25.0 314 308 286 258 230 203 175 300
27.1 279 251 223 195 167 139 111
26.5 300 295 280 253 225 197 169
26.5 300 297 285 257 229 201 173
57
72
26.4 215 190 165 140 115
-
-
334
28.0 211 186 161 136 111
-
-
67
8,000
62
25.3 262 237 212 187 162 137 112 307
24.8 310 293 268 243 218 193 168 297
24.8 310 297 272 247 222 197 172 297
26.9 257 232 207 182 157 132 107
26.3 297 287 262 237 212 187 162
26.3 297 291 266 241 216 191 166
57
72
25.2 186 167 148 129 110
-
-
304
26.8 177 158 138 119 100
-
-
67
6,000
62
24.0 226 206 187 168 149 130 111 277
23.7 277 258 240 221 201 192 163 270
23.7 281 262 243 224 205 186 167 270
25.5 213 194 175 156 137 118 99
25.2 262 243 225 206 187 167 148
25.2 266 247 228 209 190 171 152
57
Tem pera ture of Air on Con denser Coil
Air On
Evaporator
Coil
105?F
115?F
SensibleCapacity1, MBH
SensibleCapacity1, MBH
Total Power
Cap.1 Input2
Total Power
Cap.1 Input2
WB
CFM
EnteringDryBulb, ?F
86 83 80 77 74 71 68
EnteringDryBulb, ?F
86 83 80 77 74 71 68
MBH
KW
MBH
KW
?F
72 337
67 310
62 300
57 299
72 331
67 306
62 295
57 294
72 326
67 302
62 290
57 290
72 322
67 297
62 286
57 286
72 319
67 293
62 283
57 283
72 290
67 264
62 258
57 258
30.7 264 228 191 155 118
-
-
320
32.6 261 224 188 151 114
-
-
29.5 309 283 246 210 173 137 100 294
28.8 300 300 300 263 226 190 153 285
28.8 299 299 299 263 226 190 153 285
31.3 294 278 242 205 169 132 95
30.5 285 285 285 248 212 175 138
30.5 285 285 285 248 211 175 138
12,000
11,000
10,000
9,000
30.5 254 221 187 153 119
-
-
315
32.3 252 218 185 151 117
-
-
29.3 302 276 242 208 174 141 107 291
28.5 295 295 294 260 226 192 159 280
28.5 294 294 294 261 227 193 160 280
31.0 291 273 239 205 171 138 104
30.3 280 280 280 246 213 179 145
30.3 280 280 280 246 213 179 145
30.2 244 213 183 152 121
-
-
310
32.1 243 212 181 151 120
-
-
29.0 294 268 237 206 176 145 114 287
28.3 290 290 287 256 226 195 164 276
28.2 290 290 290 259 228 197 166 275
30.8 287 267 236 205 174 143 112
30.0 276 276 276 245 214 183 152
29.9 275 275 275 244 214 183 152
30.0 228 200 172 144 116
-
-
306
31.8 228 200 172 144 116
-
-
28.8 276 251 223 195 167 139 111 283
28.1 286 284 271 243 215 187 159 272
28.1 286 285 273 245 217 189 161 272
30.5 274 251 223 195 167 139 111
29.8 272 272 262 234 206 178 150
29.7 272 272 261 234 206 178 150
29.8 212 187 162 137 112
-
-
303
31.6 213 188 163 138 113
-
-
28.6 259 234 209 184 159 134 109 278
28.0 283 278 255 230 205 180 155 269
28.0 283 280 257 232 207 182 157 269
30.3 260 235 210 185 160 135 110
29.6 269 269 248 223 198 173 148
29.6 269 269 248 223 198 173 148
8,000
28.3 180 161 141 122 103
-
-
276
30.0 183 164 145 125 106
-
-
26.9 224 200 181 162 142 123 104 251
26.6 258 241 223 204 184 165 146 245
26.6 258 242 224 205 186 167 148 245
28.5 222 203 194 165 146 127 108
28.2 245 239 220 201 182 163 144
28.2 245 240 221 202 182 163 144
6,000
1These ca paci ties are gross rat ings. For net ca pac ity, de duct the heat of the sup ply air blower mo tor, MBH = 3.415 x KW. Ref er to the ap pro pri ate Blower
Per form ance Ta ble for the KW of the sup ply air blower mo tor.
2These rat ings in clude the con denser fan mo tors (To tal 2.3 KW) and the com pres sor mo tors but not the sup ply air blower mo tor.
NominalRating
AllSensibleCapacity
Unitary Products Group
5
036-21359-001-B-0302
BLOWER PERFORMANCE- 25 TON (DCE/DCG300)
DCE300-BOTTOMDUCTCONNECTIONS (COOLINGAPPLICATIONS)
7500 CFM
8750 CFM
10000 CFM
11250CFM
12500 CFM
BLOWER PULLEY
TURNS
OPEN:
SPEED
(rpm)
ESP
(iwg)
OUTPUT INPUT
(kW)
ESP
(iwg)
OUTPUT INPUT
ESP
(iwg)
STANDARD DRIVE:
OUTPUT INPUT
ESP
(iwg)
OUTPUT INPUT
(kW)
ESP
(iwg)
OUTPUT INPUT
(kW)
(bhp)
(bhp)
(kW)
(bhp)
(kW)
(bhp)
(bhp)
975
6.0*
5.0
4.0
3.0
2.0
1.0
0.0
1.4
1.6
1.8
2.0
2.1
2.4
2.6
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
1.0
1.2
1.4
1.6
1.8
2.0
2.2
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
0.5
0.7
0.9
1.1
1.3
1.6
1.8
8.8
7.2
7.6
8.0
8.3
8.7
9.1
9.5
-
-
-
8.9
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
6.3
6.7
7.0
7.3
7.6
8.0
9.2
9.7
0.1
0.3
0.6
0.8
1.0
1.3
10.9
11.4
11.9
12.4
13.0
13.5
9.4
9.8
-
-
-
10.2
10.6
11.1
11.6
-
-
-
10.2
10.6
11.0
0.2
0.4
0.7
14.3
14.9
15.5
11.7
12.2
12.7
ACCESSORY DRIVE:
1140
1180
1215
1255
1290
1330
1365
NOTES:
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.4
2.7
2.9
3.2
3.4
3.7
3.9
7.7
8.2
6.3
6.7
7.0
7.4
7.8
8.2
8.6
2.1
2.3
2.6
2.9
3.1
3.4
3.7
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
1.6
1.9
2.2
2.5
2.7
3.0
3.3
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
1.1
1.4
1.7
2.0
2.2
2.6
2.9
13.1
13.7
14.3
15.0
15.6
16.4
17.0
10.7
11.2
11.7
12.3
12.8
13.4
13.9
0.5
0.8
1.1
1.4
-
15.0
15.8
16.4
17.2
-
12.3
12.9
13.5
14.1
-
8.6
9.1
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
9.5
10.0
10.5
-
-
-
-
-
-
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
BLOWER PERFORMANCE - 25 TON (DCE/DCG300)
DCG300 -BOTTOMDUCTCONNECTIONS (COOLINGAPPLICATIONS)
7500 CFM
8750 CFM
10000 CFM
11250 CFM
12500 CFM
BLOWER PULLEY
TURNS
OPEN:
SPEED
(rpm)
ESP
(iwg)
OUTPUT INPUT
(kW)
ESP
(iwg)
OUTPUT INPUT
ESP
(iwg)
STANDARD DRIVE:
OUTPUT INPUT
ESP
(iwg)
OUTPUT INPUT ESP
(kW)
OUTPUT INPUT
(kW)
(bhp)
(bhp)
(kW)
(bhp)
(kW)
(bhp)
(iwg)
(bhp)
975
6.0*
5.0
4.0
3.0
2.0
1.0
0.0
1.2
1.4
1.6
1.8
2.0
2.2
2.4
5.9
6.2
6.6
6.9
7.3
7.7
8.0
4.9
5.1
5.4
5.7
6.0
6.3
6.6
0.5
0.7
0.9
1.1
1.3
1.6
1.8
7.3
7.7
8.1
8.5
8.9
9.3
9.7
6.0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1005
1040
1070
1100
1135
1165
6.3
6.7
7.0
7.3
7.6
8.0
-
-
9.7
-
-
-
-
0.2
0.4
0.6
0.8
1.0
8.0
8.3
8.7
9.1
9.5
-
-
-
-
10.2
10.6
11.1
11.6
-
-
-
-
-
-
-
-
0.2
13.5
11.0
ACCESSORY DRIVE:
1140
1180
1215
1255
1290
1330
1365
NOTES:
6.0
5.0
4.0
3.0
2.0
1.0
0.0
2.2
2.5
2.7
3.0
3.2
3.5
3.7
7.7
8.2
8.6
9.1
9.5
10.0
10.5
6.3
6.7
7.0
7.4
7.8
8.2
8.6
1.6
1.9
2.1
2.4
2.7
3.0
3.2
9.4
9.9
7.7
8.1
8.5
9.0
9.4
9.9
10.3
0.9
1.2
1.4
1.7
2.0
2.3
2.6
11.2
11.8
12.3
12.9
13.5
14.1
14.7
9.2
9.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
0.3
0.6
0.9
1.2
1.5
1.8
13.7
14.3
15.0
15.6
16.4
17.0
11.2
11.7
12.3
12.8
13.4
13.9
10.4
11.0
11.5
12.0
12.6
10.1
10.6
11.1
11.6
12.1
Blower performance is based on cooling only unit, with fixed outdoor air, 2" T/A filters and a dry evaporator coil.
Refer to page 7 for additional static resistances.
ESP - External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the
blower.
* FACTORY SETTING
6
Unitary Products Group
036-21359-001-B-0302
ELECTRICAL DATA - Units With ElectricHeat
MINIMUM
CIRCUIT
MAXIMUM
OVERCURRENT
DEVICE (1)
ELECTRIC HEATER OPTION
MODEL
D2CE
POWER
SUPPLY
AMPACITY
MODEL
kW(1)
STAGES AMPS
(AMPS)(AMPS)
139.5
142.1
189.0
198.4
139.5
156.5
178.2
221.5
68.3
300A25
300A25
300A25
300A25
300A25
300A25
300A25
300A25
300A46
300A46
300A46
300A46
300A58
300A58
300A58
300A58
208-3-60
208-3-60
208-3-60
208-3-60
230-3-60
230-3-60
230-3-60
230-3-60
460-3-60
460-3-60
460-3-60
460-3-60
575-3-60
575-3-60
575-3-60
575-3-60
E018
E036
E054
E072
E018
E036
E054
E072
E018
E036
E054
E072
E018
E036
E054
E072
13.5
27.0
40.6
54.1
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
18.0
36.0
54.0
72.0
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
37.5
75.1
112.6
150.1
43.3
86.6
129.9
173.2
21.7
43.3
65.0
86.6
17.3
34.6
52.0
69.3
175
175
200
225
175
175
200
250
80
78.3
89.1
80
100
125
70
110.7
56.1
62.6
70
71.2
80
88.5
100
1
NOMINALVOLTAGE
VOLTAGE
208
230
KWCAP.MULTIPLIER
208
240
480
600
1.00
0.92
0.92
0.92
460
575
PHYSICAL DATA
BASIC UNITS
OPERATING WEIGHTS
DCE/DCG/DCV
MODEL
DCE
Wd. DCinV.)18
SIZE
(Cool
(MBH)300
ing
MODELS
300
(Dia.
15
CEN
TRIFU
GAL
BLOWER
x
x
15 (Cool
ing
EVAPORATOR
BLOWER
FAN MO TOR HP
ROWS DEEP
FINS PER INCH
N240
2930
2970
2995
3035
160
BasicUnit DCG (Gas / Elec tric)
4
13.5
25.0
N320
N240
N320
EVAPORATOR
COIL
DCV (Gas / Elec tric)
Economizer
FACE AREA (Sq. Ft.)
PRO PEL LER DIA. (in.) (Each)30
CONDENSER
FAN
(Two Per Unit)
Economizerwith
PowerExhaust
Options MotorizedDamper
FAN
MO
(Each)
TOR
HP
245
NOM. CFM TO TAL
ROWS DEEP
FINS PER INCH
FACE AREA (Sq. Ft.)
7200
3
15
150
25
30
CONDENSER
COIL
18 KW
36 KW
54 KW
72 KW
ElectricHeater
(Elec/Elec only)
43.3
35
40
COMPRESSOR 12.5 TON, SCROLL, HER METIC,
(Qty. Per Unit) TAN DEM (2 STAGE, 50% ea.)
2
QUAN
QUAN
QUAN
TITY
TITY
TITY
PER
PER
PER
UNIT
UNIT
UNIT
21.4
(16" Roof Curb X
20"
25"
(14" EconomizeXr/MotorizedDa2m0"per
1X85
45
X
2")2
2")4
2")3
BarometricDamper
(16"
X
AIR
FILTERS
X
Accesso-
55
Rain Hood
TO TAL FACE AREA (sq. ft.)
REFRIGERANT
22 (lbs./oz.)
ries
Economizer/PowerExhaustRain
Hood
90
SYS TEM NO. 1
20/8
20/0
CHARGE
Wood Skid
220
SYS TEM NO. 2
Unitary Products Group
7
036-21359-001-B-0302
BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
MOTOR1
ADJUSTABLEMOTORPULLEY
FIXED BLOWER PUL LEY
OUTSIDE PITCH
BLOWER
DRIVE RANGE
(RPM)
MODEL
SIZE
OUT-
SIDE
DIA.
PITCH
DIA.
(IN.)
PITCH
LENGTH QTY.
(IN.)
EFF.
(%)
DESIG-
NATION
BORE DESIG-
(IN.) NATION
BORE DESIG-
(IN.) NATION
HP FRAME
DIA.
(IN.)
DIA.
(IN.)
(IN.)
Stan-
975/1165
dard
High
1B5V110 11.3
11.1 1-7/16 5VX860 86.0
9.5 1-7/16 5VX840 84.0
1
1
1LVP58B70
A
6.2-
7.4
25 TON
15 254T 91
7.5
1 5/8
Speed 1140/1365
Access
1B5V94
9.7
1All mo tors have a nomi nal speed of 1800 RPM, a 1.15 serv ice fac tor and a solid base. They can op er ate to the limit of their serv ice fac tor be cause they are lo cated in the mov ing air, upstream
of any heat ing de vice.
STATIC RESISTANCES*
AIRFLOW (CFM)
7500
ESP
(IWG)
8750
ESP
(IWG)
10000
ESP
(IWG)
11250
ESP
(IWG)
12500
ESP
(IWG)
DESCRIPTION
DEDUCTIONS: (SUBTRACT VALUES BELOW FROM UNIT'S AVAILABLE ESP)
ALLOWANCE FOR WET COIL:
ECONOMIZER (RETURN DUCT):
18kW ELECTRIC HEAT:
0.10
0.06
0.31
0.38
0.62
0.68
0.10
0.09
0.43
0.52
0.84
0.93
0.10
0.11
0.56
0.68
1.10
1.21
0.10
0.14
0.71
0.87
1.39
1.54
0.10
0.18
0.87
1.07
1.72
1.90
36kW ELECTRIC HEAT:
54kW ELECTRIC HEAT:
72kW ELECTRIC HEAT:
ADDITIONS: (ADD VALUES BELOW TO UNIT'S AVAILABLE ESP)
HORIZONTAL (SIDE) SUPPLY DUCT:
HORIZONTAL (SIDE) RETURN DUCT:
0.31
0.05
0.26
0.05
0.27
0.05
0.31
0.05
0.41
0.05
POWER EXHAUST PERFORMANCE
STATICRESISTANCEOFRETURNDUCTWORK,IWG
0.3 0.4 0.5
MOTOR
SPEED
0.2
0.6
CFM
5250
KW
CFM
4500
KW
CFM
4200
KW
CFM
3750
KW
CFM
3000
KW
HIGH*
0.83
0.85
0.88
0.93
0.99
MEDIUM
4900
4400
0.77
0.72
3900
3700
0.79
0.74
3500
3000
0.82
0.78
2900
-
0.85
-
-
-
-
-
LOW
*FactorySetting
Power Ex haust mo tor is a 3/4 HP, PSC type with sleeve bear ings, a 48 frame and in her ent protection.
ELECTRICAL DATA- Cool ing Only Units and Units With Gas Heat
ELECTRICAL DATA - Cooling Only Units & Units With Gas Heat
COMPRESSORS
(QTY. 2)
COND. FAN
(#1 & #2)
SUPPLY AIR
MINIMUM
CIRCUIT
MAXIMUM
BLOWER MOTOR
POWER
SUPPLY
OVERCURRENT
MODEL NO.
RLA
LRA
HP
FLA
AMPACITY
(AMPS)
DEVICE (1)
(AMPS)
HP
RLA
(ea.)
(ea.)
(ea.)
(ea.)
D2CE300 208/230-3-60
41.4
20.0
16.4
312
150
108
1
1
1
4.2
2.1
2.0
15
15
15
38.6
19.3
15.4
139.5
68.3
56.1
175
80
& D2CG300
460-3-60
575-3-60
70
VOLTAGE
POWERSUPPLY
MIN.
MAX.
253
VOLTAGE
LIMITATIONS**
208/230-3-60
460-3-60
187
414
518
506
575-3-60
630
**Rated in ac cor dance with ARI Stan dard 110, utili za tion range “A”.
8
Unitary Products Group
036-21359-001-B-0302
FIELD WIRING - DCE/DCG ELECTRIC/ELECTRIC AND GAS/ELECTRIC UNITS
C
O
N
T
R
O
L
W
I
R
I
N
G
C
O
O
L
M
I
N
G
O
N
L
Y
(
2
4
V
O
L
T
T
H
E
R
M
O
S
T
A
T
)
C
O
O
L
I
N
G
/
H
E
A
T
I
N
G
(
2
4
1
U
N
I
T
T
E
R
M
I
N
A
L
1
T
H
E
R
O
S
T
A
T
T
H
E
R
M
O
S
T
A
T
U
N
I
T
T
E
R
M
I
N
A
L
2
2
B
L
O
C
K
1
T
B
T
E
R
M
I
N
A
L
S
T
E
R
M
I
N
A
L
S
B
L
O
C
K
1
T
B
R
R
R
W
H
R
Y
1
Y
1
Y
2
Y
2
R
C
Y
Y
1
2
W
1
W
1
W
2
W
2
Y
1
A
J
D
D
G
G
U
M
P
E
R
Y
2
B
X
G
B
X
W
1
A
A
1
2
A
A
1
2
2
T
4
V
O
L
T
R
A
N
S
F
O
R
M
E
R
3
2
1
2
2
T
4
V
o
l
t
T
h
e
r
m
o
s
t
a
t
2
T
H
0
4
7
0
1
2
2
4
.
e
r
m
i
n
a
l
b
l
o
c
k
1
T
B
-
l
o
c
a
t
e
d
o
n
r
e
l
a
y
b
o
a
r
d
i
n
2
4
-
v
o
l
t
s
e
c
t
i
o
n
2
T
4
V
O
L
T
o
f
t
h
e
u
n
i
t
c
o
n
t
r
o
l
b
o
x
.
G
R
A
N
S
F
O
R
M
E
R
1
2
3
2
T
S
4
V
o
l
t
T
h
e
r
m
o
s
t
a
t
2
T
H
0
4
7
0
1
0
2
4
(
w
i
t
h
s
u
b
b
a
s
e
2
T
B
0
4
7
0
0
2
2
4
o
r
e
r
m
i
n
a
l
b
l
o
c
k
1
T
B
-
l
o
c
a
t
e
d
o
n
o
f
t
h
e
u
n
i
t
c
o
n
t
r
o
l
b
o
x
.
C
O
O
L
I
N
G
/
H
E
A
T
I
N
G
(
E
L
E
C
T
R
O
N
I
C
T
H
E
R
M
O
S
T
A
e
c
o
n
d
s
t
a
g
e
h
e
a
t
i
n
g
i
s
n
o
t
r
e
q
1
e
l
e
c
t
r
i
c
h
e
a
t
e
r
.
T
H
E
R
M
O
S
T
A
T
U
N
I
T
T
E
R
M
I
N
A
L
2
T
E
R
M
I
N
A
L
S
B
L
O
C
K
1
T
B
R
C
R
R
H
Y
1
P
O
W
E
R
W
I
R
I
N
G
Y
Y
1
2
Y
2
W
1
R
E
D
t
p
f
d
s
e
f
e
r
t
o
t
h
e
A
J
D
D
L
T
B
I
C
I
N
E
V
O
L
T
A
G
E
L
E
C
T
R
I
C
A
L
3
W
2
W
W
1
2
U
M
P
E
R
E
R
M
C
I
N
A
L
A
T
A
L
O
K
2
T
B
a
b
l
e
s
t
o
s
i
z
2
T
4
V
O
L
T
G
N
U
N
I
T
o
w
e
r
w
i
r
i
n
g
L
1
R
A
N
S
F
O
R
M
E
R
B
G
O
N
T
R
O
L
B
O
X
u
s
e
s
a
n
d
t
h
e
L
L
2
3
i
s
c
o
n
n
e
c
t
X
B
w
i
t
c
h
.
G
R
O
U
N
D
L
U
G
4
A
A
1
2
L
E
D
1
4
L
E
D
2
N
U
O
S
T
O
E
D
C
O
M
A
1
A
2
T
T
T
2
O
R
E
M
O
T
E
S
E
N
S
O
R
T
H
0
4
7
0
2
2
2
4
I
F
U
S
E
D
1
2
3
4
E
T
S
T
l
e
c
t
r
o
n
i
c
p
r
o
g
r
a
m
m
a
b
l
e
T
h
e
r
m
o
s
t
a
t
2
E
T
0
4
7
0
0
2
2
4
(
i
n
c
l
u
d
e
s
s
u
b
b
e
r
m
i
n
a
a
l
b
l
o
c
k
1
T
B
-
l
o
c
a
t
e
d
o
n
r
e
l
a
y
b
o
a
u
r
n
d
i
n
2
4
t
-
v
o
l
t
s
e
g
c
l
t
i
o
n
o
e
c
o
n
d
s
t
a
g
e
h
e
a
t
i
n
g
i
s
n
o
t
r
e
q
u
i
r
e
d
o
n
i
t
s
w
i
h
a
s
i
n
e
s
t
a
g
e
r
m
i
n
l
s
A
1
a
n
d
A
2
p
r
o
v
i
d
e
a
r
e
l
a
y
o
u
t
p
u
t
t
o
c
l
o
s
e
t
h
e
o
u
t
d
o
o
r
w
h
e
n
t
h
e
t
h
e
r
m
o
s
t
a
t
s
w
i
t
c
h
e
s
t
o
t
h
e
s
e
t
-
b
a
c
k
p
o
s
i
t
i
o
n
.
F
a
n
s
w
i
t
c
h
m
u
s
t
b
e
i
n
"
O
N
"
p
o
s
i
t
i
o
n
f
o
r
m
i
n
i
m
u
m
v
e
n
t
i
l
a
t
i
o
n
d
u
r
i
Unitary Products Group
9
036-21359-001-B-0302
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
All dimensions are in inches. They are
subject to change without notice. Certified
dimensionswillbeprovideduponrequest.
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER
ACCESS
COMPRESSOR
ACCESS
(See detail "X")
BLOWER MOTOR
ACCESS
UTILITIES ENTRY DATA
OPENING
OPTIONAL COIL
GUARD KIT
BLOWER
COMPARTMENT
ACCESS
48-5/8" (15TON)
52-5/8" (20TON)
(Auxiliary)
HOLE
SIZE
(DIA.)
USED FOR
DOT PLUG
(For pressure
Drop Reading)
1-1/8" KO
3/4" NPS (Fem.)
3-5/8" KO
Control
Wiring
Front
Bottom
Front
Bottom
Pip
A
B
CONDENSER
COILS
Power
Wiring
21"
5"
3" NPS (Fem.)
KO
1
C2-3/8"
Gas
ing
(Front)
125-1/4" (15 TON)
136-1/4" (20 TON)
Gas Pip ing (Bot-
tom)1,2
D
1-11/16" Hole
FRONT
VIEW
9-3/4"
5-7/8"
ELECTRIC HEAT
ACCESS
92"
1
1" pip ing MPT re quired
(A)
CONTROL WIRING
ENTRY
2 Open ing in the bot tom of the unit can be lo cated by the slice
in the in su la tion.
CONTROL BOX
ACCESS
11-1/2"
(B)
35"
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
POWER WIRING
ENTRY
RETURN AIR
SUPPLY AIR
OUTDOOR AIR
24-1/4" (15 TON)
36-1/4" (20 TON)
RETURN
AIR
3-3/4"
33"
SUPPLY
AIR
2-3/4"
21-1/2"
OUTDOOR AIR
(Economizer)
UNIT BASE WITH RAILS
Shown separately to illustrate
Bottom Duct openings and Power
Connection locations
(B)
POWER WIRING
ENTRY
(A)
CONTROL WIRING
ENTRY
8-1/8"
9-3/4"
NOTE:
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
9-1/4"
12-1/2"
ECONOMIZER / MOTORIZED DAMPER,
FIXED OUTDOOR INTAKE AIR AND
POWER EXHAUST RAIN HOODS
(See detail "Y")
BLOWER
ACCESS
CLEARANCES
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
BLOWER MOTOR
ACCESS
COMPRESSOR
Front
Back
36"
ACCESS
(See detail "X")
BLOWER
COMPARTMENT
ACCESS
24" (Less Econo mizer)
49" (With Econo mizer)
OPTIONAL
COIL GUARD
KIT
(Auxiliary)
DOT PLUG
(For pressure
Drop Reading)
24" (Less Econo mizer)
36" (With Econo mizer)
52-5/8
LeftSide(FilterAccess)
GAS HEAT
ACCESS
Right Side (Cond. Coil)
BelowUnit1
36"
20"
CONDENSER
COILS
VENT AIR
OUTLET
HOODS
72" With 36" Maxi mum
Hori zon tal Over hang
(For Con denser Air
Dis charge)
21"
5"
Above Unit2
7-1/8"
COMBUSTION
AIR INLET
HOOD
136-1/4
6-3/8"
9-3/4"
92"
1Units(applicableinU.S.A. only)maybeinstalledoncombustiblefloors
(C)
5-7/8"
(A)
GAS SUPPLY
ENTRY
made from wood or class A, B or C roof cov er ing ma te rial.
2
CONTROL WIRING
ENTRY
46-5/8"
Units must be in stalled ou doors. Over hang ing struc tures or shrubs should
not ob struct con denser air dis charge out let.
CONTROL BOX
ACCESS
11-1/2"
(B)
35"
POWER WIRING
ENTRY
BOTTOM SUPPLY
AND RETURN
AIR OPENINGS
(See Note)
NOTE:
RETURN AIELEC/ELECModels: Units and duct work are ap proved for zero clear ance to
combustiblematerialswhenequippedwithelectricheaters.
FRONT
VIEW
35-1/4
RETURN
AIR
3-3/4"
SUPPLY AIGAS/ELEC Mod els: A 1" clear ance must be pro vided be tween any
combustiblematerialandthesupplyairductworkforadistanceof3feet
OUTDOOR from the unit.
33"
SUPPLY
AIR
2-3/4"
21-1/2"
11-1/8"
OUTDOOR The prod ucts of com bus tion must not be al lowed to ac cu mu late within a
(Economize
confinedspaceandrecirculate.
UNIT BASE WITH RAILS
(B)
Lo cate unit so that the vent air out let hood is at least:
(D)
Shown separately to illustrate
Bottom Duct openings, Power
and Gas Piping Connection
locations
POWER WIRING
ENTRY
GAS SUPPLY
ENTRY
?
Three (3) feet above any forced air in let lo cated within 10 hori zon tal feet (ex-
clud ing those in te gral to the unit).
(A)
CONTROL WIRING
ENTRY
8-1/8"
9-3/4"
NOTE:
?
Four(4)feetbelow,4horizontalfeetfrom,or1footaboveanydoororgravity
air in let into the build ing.
46-5/8"
For curb mounted units, refer to the curb hanger
dimensions of the curb for the proper size of the
supply and return air duct connections.
9-1/4"
12-1/2"
10
Unitary Products Group
036-21359-001-B-0302
CONDENSER
SECTION
DUCT COVERS - Units are shipped with the bottom
duct openings covered. An accessory flange kit is available for
connecting side ducts.
EVAPORATOR
SECTION
GAUGE LINE
ACCESS
DOT PLUG
(For pressure
drop reading)
For bottom duct applications:
40-3/8"
1
Remove the side panels from the supply and return
air
FILTER
compartments to gain access to the bottom supply and
return air duct covers.
ACCESS
SUPPLY
AIR
RETURN
AIR
5-1/2"
COMPRESSOR
ACCESS
2
Remove and discard the bottom duct covers. (Duct
openings are closed with sheet metal covers except
when the unit includes a power exhaust option. The
covering consists of a heavy black paper composition.)
OUTDOOR
AIR
40-1/2"
SUPPLY AIR
ACCESS
18-5/8"
1" NPT FEMALE
COND. DRAIN
CONNECTION
27-3/4"
5-1/8"
RETURN AIR
ACCESS
OUTDOOR AIR
COMPARTMENT
ACCESS
3
Replace the side supply and return air compartment
panels.
29-5/8" (15 TON)
39-5/8" (20 TON)
REAR
VIEW
For side duct applications;
1
Replace the side panels on the supply and return air
compartments with the accessory flange kit panels.
2
Connect ductwork to the duct flanges on the rear of the
unit.
E
M
D
R
(
C
O
N
O
M
I
Z
E
R
O
T
O
P
R
I
Z
E
D
P
O
W
E
E
X
R
H
A
U
S
T
A
A
M
I
E
R
S
C
U
P
A
P
I
L
R
Y
R
A
H
I
N
O
O
D
N
H
O
O
D
O
M
P
A
R
T
M
E
N
T
E
A
C
N
O
D
N
O
M
/
M
O
I
Z
T
E
O
R
R
D
I
A
Z
M
E
P
D
E
R
(
o
R
n
e
t
A
u
i
C
r
r
o
n
m
p
a
r
t
m
e
n
t
)
o
n
O
u
t
d
o
o
r
A
i
r
C
o
m
p
a
r
t
m
e
n
t
)
P
O
W
E
E
X
R
H
A
R
U
A
S
H
I
T
N
O
O
D
S
F
O
I
X
E
u
D
U
T
D
A
O
I
O
R
R
I
N
T
H
A
O
K
E
O
D
(
l
o
c
a
t
e
d
o
n
R
e
o
t
m
r
n
A
i
r
3
4
-
1
/
4
"
C
p
a
r
t
m
e
n
t
)
1
D
(
"
C
O
N
D
E
N
S
T
A
T
E
R
A
I
N
1
6
-
1
/
8
"
M
u
s
t
b
e
t
r
a
p
p
e
d
)
5
"
3
6
"
9
2
"
3
6
-
1
/
4
"
2
"
6
6
-
1
/
2
"
L
H
V
I
E
W
R
E
A
R
V
I
E
W
D
E
T
A
I
L
"
Y
"
U
N
I
T
W
I
T
H
R
A
I
N
H
O
O
D
S
Unitary Products Group
11
036-21359-001-B-0302
B
E
F
C
D
A
A
F
R
O
N
T
F
R
O
N
T
C
B
D
4 Point Loads
6 Point Loads
4 - POINT LOADS (LBS)
DCE
UNIT
TOTAL
2,890
A
B
C
D
300
487
619
646
508
DCE
DCE
6 - POINT LOADS (LBS)
UNIT
TOTAL
2,890
A
B
C
D
E
F
300
415
471
528
551
492
433
NOTE: These weights are with economizer and 24kW electric heat.
4 - POINT LOADS (LBS)
DCG
UNIT
TOTAL
3,130
A
B
C
D
300
615
671
962
882
6 - POINT LOADS (LBS)
DCG
UNIT
TOTAL
3,130
A
B
C
D
E
F
300
418
438
533
658
603
510
NOTE: These weights are with economizer, high heat and oversized motor.
12
Unitary Products Group
036-21359-001-B-0302
3.69"
BASE RAIL
3.56"
Unitary Products Group
13
036-21359-001-B-0302
14
Unitary Products Group
036-21359-001-B-0302
7. Condensate pan shall be internally sloped and
conform to ASHARE 62-89 self-draining standards.
Condensate connection shall be a minimum of 1"
I.D. female and be a ridged mount connection.
MECHANICAL SPECIFICATIONS
GENERAL DESCRIPTION
Units shall be factory-assembled, single packaged,
(DCG Electric Cooling/Gas Heat, DCE Electric Cooling/
Optional Electric Heat), designed for outdoor mounted
installation. Units shall have minimum EER ratings of
8.5. They shall have built in field convertible duct con-
nections for down discharge supply/return or horizontal
discharge supply/return, and be available with factory
installed options or field installed accessories.
8. Unit shall incorporate a fixed outdoor air damper
with an outdoor air intake opening covered with a
bird screen and a rain hood painted to match the
exterior of the unit.
INDOOR (EVAPORATOR) FAN ASSEMBLY
1. Fan shall be a belt drive assembly and include an
adjustable-pitch motor pulley. Job site selected
(B.H.P.) brake horse power shall not exceed the
motors nameplate horse power rating, plus the ser-
vice factor. Units shall be designed not to operate
above service factor.
The units shall be factory wired, piped, charged with R-
22 refrigerant and factory tested prior to shipment. All
unit wiring shall be both numbered and color coded.
Enclosed in each unit shall be a factory test log sheet
consisting of the unit tested pressures, temperatures
and amps, as tested prior to shipment.
All units shall be manufactured in a facility certified to
ISO 9001 standards and the cooling performance shall
be rated in accordance with DOE and ARI test proce-
dures. Units shall be ETL & CGA listed, classified to
ANSIZ21.47 standards, UL 1995/CAN/CSA No. 236-
M90 conditions.
2. Fan wheel shall be double-inlet type with forward-
curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation.
Airflow design shall be constant air volume.
3. Bearings shall be sealed and permanently lubri-
cated for longer life and no maintenance.
UNIT CABINET
1. Unit cabinet shall be constructed of G90 galva-
nized steel, with exterior surfaces coated with a
non-chalking, powered paint finish, certified at 750
hours salt spray test per ASTM-B117 standards.
OUTDOOR (CONDENSER) FAN ASSEMBLY
1. The outdoor fans shall be of the direct-driven pro-
peller type, discharge air vertically, have blades
riveted to corrosion resistant steel spider brackets
and shall be dynamically balanced for smooth
operation.
2. Indoor blower section shall be insulated with up to
1" thick insulation, coated on the air side. Alumi-
num foil faced insulation shall be used in the fur-
nace compartment and be fastened with ridged
fasteners to prevent insulation from entering the air
stream.
2. The 2 outdoor fan motors shall be totally enclosed
with permanently lubricated bearings, internally
protected against overload conditions and staged
independently.
3. Cabinet panels shall be “large” size, easily remov-
able for servicing and maintenance.
REFRIGERANT COMPONENTS
1. Compressors:
4. Full perimeter base rails shall be provided to
assure reliable transit of equipment, overhead rig-
ging and proper sealing on roof curb applications.
A. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or
- 10% of the unit nameplate voltage.
5. Disposable 2" filters shall be furnished and be
accessible through a removable access door,
sealed air tight. Units filter track shall be designed
to accommodate either 1" or 2" filters.
B. Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on
mounting.
a
dedicated, independent
6. Fan performance measuring ports shall be pro-
vided on the outside of the cabinet to allow accu-
rate air measurements of evaporator fan
performance without removing panels or creating
air by-pass of the coils.
2
Coils:
A. Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally-enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
15
Unitary Products Group
036-21359-001-B-0302
B. Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
resistance and allowing minimum mixed air enter-
ing temperature of 25 °F.
C. Condenser coils shall be protected with factory
installed coil guards
3. Burners shall be of the in-shot type, constructed of
aluminum coated steel and contain air mixture
adjustments.
3. Refrigerant Circuit and Refrigerant Safety Compo-
nents shall include:
4. All gas piping shall enter the unit cabinet at a single
location through either the side or curb, without any
field modifications.
A. Balance-port thermostatic expansion valve with
independent circuit feed system.
B. Filter drier/strainer to eliminate any moisture or for-
eign matter.
5. An integrated control board shall provide timed
control of evaporator fan functioning and burner
ignition.
C. Accessible service gage connections on both suc-
tion and discharge lines to charge, evacuate, and
measure refrigerant pressure during any necessary
servicing or troubleshooting, without losing charge.
6. Heating section shall be provided with the following
minimum protection:
D. The refrigeration system shall provide at least 15 °F
of sub-cooling at design conditions.
A. Primary and auxiliary high-temperature limit
switches.
E. All Models shall have two independent circuits..
4. Unit Controls:
B. Induced draft motor speed sensor.
C. Flame roll out switch (manual reset).
D. Flame proving controls.
A. Unit shall be complete with self contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24 volt transformer side.
7
Unit shall have two independent stages of capacity.
B. Unit shall incorporate a lock-out circuit which pro-
vides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor:
ELECTRIC HEATING (DCE MODELS)
1. Nickel chromium electric heating elements shall be
provided as required by the application with 1 or 2
stage control, as required, from 13.5 KW to 72 KW
capacity.
1. Loss-of-charge/Low-pressure switch.
2. High-pressure switch.
2. The heating section shall have a primary limit con-
trol(s) and automatic reset to prevent the heating
element system from operating at an excessive
temperature.
3. Freeze-protection thermostat, evaporator coil.
If any of the above safety devices trip, an LED (light-
emitting diode) indicator shall illuminate.
3. Units with Electric Heating shall be wired for a sin-
gle point power supply with branch circuit fusing
(where required).
C. Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
D. Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
UNIT OPERATING CHARACTERISTICS
1. Unit shall be capable of starting and running at 125
°F outdoor temperature, exceeding maximum load
criteria of ARI Standard 210/240.
GAS HEATING SECTION (DCG MODELS)
1. Shall be designed with induced draft combustion
with post purge logic and energy saving direct
spark ignition, redundant main gas valve. Ventor
wheel shall be constructed of stainless steel for
corrosion resistance.
2. The compressor, with standard controls, shall be
capable of operation down to 25 °F outdoor tem-
perature. Accessory low ambient kit shall be avail-
able for operation to 0 °F.
2. The heat exchanger shall be of the tubular type,
constructed of T1-40 aluminized steel for corrosion
3. Unit shall be provided with fan time delay to pre-
vent cold air delivery before heat exchanger warms
up. (Gas heat only)
16
Unitary Products Group
036-21359-001-B-0302
ELECTRICAL REQUIREMENTS
space during normal operation. During economizer
operation, a mixed-air temperature control shall
modulate the outdoor and return air damper
assembly to prevent the supply air temperature
from dropping below 55°F. Changeover from com-
pressor to economizer operation shall be provided
by two integral electronic enthalpy controls - one
that senses outdoor air and one that senses indoor
air. Both enthalpy sensors supply input to the logic
module which modulates both sets of dampers for
maximum economizer savings. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/
filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers
shall fully close on power loss.
All unit power wiring shall enter unit cabinet at a single
factory provided location and be capable of side or bot-
tom entry, to minimize roof penetrations and avoid unit
field modifications. Separate side and bottom openings
shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES
Compressor- 5 Years
Heat Exchanger - 10 Years
Elect. Heat. Elem.- 5 Years
Parts- 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available
by either/or):
1
ELECTRONIC ENTHALPY AUTOMATIC ECON-
OMIZER - Outdoor and return air dampers that are
interlocked and positioned by a fully-modulating,
spring-return damper actuator. The maximum leak-
age rate for the outdoor air intake dampers shall
not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5
IWG. A unit-mounted potentiometer shall be pro-
vided to adjust the outdoor and return air damper
assembly to take in CFM of outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer
operation, a mixed-air temperature control shall
modulate the outdoor and return air damper
assembly to prevent the supply air temperature
from dropping below 55°F. Changeover from com-
pressor to economizer operation shall be provided
by an integral electronic enthalpy control that feeds
input into the basic module. The outdoor intake
opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/
filters shall be provided. Simultaneous economizer/
compressor operation is also possible. Dampers
shall fully close on power loss.
3
MOTORIZED OUTDOOR AIR DAMPERS - Out-
door and return air dampers that are interlocked
and positioned by
a
2-position, spring-return
damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed
2% when dampers are fully closed and operating
against a pressure differential of 0.5 IWG. A unit-
mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take
in the design CFM of outdoor air to meet the venti-
lation requirements of the conditioned space during
normal operation. Whenever the indoor fan motor
is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor
air enthalpy. Dampers return to the fully closed
position when the indoor fan motor is de-ener-
gized. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAIL-
ABLE
1. ROOF CURB - 14" high, full perimeter curb with
wood nailer (shipped knocked-down).
2. BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure
through the unit during economizer operation.
2. DUAL INPUT DIFFERENTIAL ELECTRONIC
ENTHALPY AUTOMATIC ECONOMIZER - Out-
door and return air dampers that are interlocked
and positioned by a fully-modulating, spring-return
damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed
2% when dampers are fully closed and operating
against a pressure differential of 0.5 IWG. A unit
mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take
in the design CFM of outdoor air to meet the mini-
mum ventilation requirement of the conditioned
3. PROPANE CONVERSION KIT - Contains new ori-
fices and gas valve parts to convert from natural to
L.P. gas. One per unit required.
4. HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000
feet altitude.
Unitary Products Group
17
036-21359-001-B-0302
5. HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000
feet altitude. Must be used with propane conver-
sion kit.
12. ANTI-RECYCLE TIMER - Assures 5-minute off-time
between compressor cycles.
13. LOW AMBIENT KIT - Provides unit cooling opera-
tion down to 0°F.
6. BURGLAR BARS - Designed to work with above
roofcurbs, depending on unit model. Fits duct
openings of curb supply and return air openings.
OTHER FACTORY INSTALLED OPTIONS
1
POWER EXHAUST OPTION - To work in conjunc-
tion with economizers.
7. SIDE DUCT FLANGE - Supply and return air duct
flanges for side duct applications. Do not use on
units with power exhaust.
2. TECHNICOAT PHENOLIC COATED COND. COIL
3. ELECTRONIC ENTHALPY ECONOMIZER
8. HIGH SPEED DRIVE - Includes blower pulley and
belt for higher CFM and/or static pressure require-
ments.
4. DUAL INPUT ELECTRONIC ENTHALPY ECON-
OMIZER
9. WOOD SKID - Allows unit to be handled with 90"
forks.
10. ECONOMIZER/MOTORIZED DAMPER RAIN HOOD
(DCE/CG300 only) - Contains all hood panels and
the hardware for assembling.
11. THERMOSTATS - Multiple models available from
A.C.O., M.C.O., Electronic or Electrical Mechanical
versions.
18
Unitary Products Group
036-21359-001-B-0302
Unitary Products Group
19
036-21359-001-B-0302
20
Unitary Products Group
036-21359-001-B-0302
Unitary Products Group
21
036-21359-001-B-0302
22
Unitary Products Group
036-21359-001-B-0302
Unitary Products Group
23
Subject to change without notice. Printed in U.S.A.
CD: 6-21359
036-21359-001-B-0302
Supersedes: 036-21359-001-A-0302
Copyright © by Unitary Products Group 2002. All rights reserved.
Unitary
Products
Group
5005
Norman
OK
73069
York
Drive
|