528194-YTG-F-1210
®
Description
TECHNICAL GUIDE
R-410A
ASHRAE 90.1 COMPLIANT
®
®
YORK Predator units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or frame.
ZF SERIES
6-1/2 - 12-1/2 TON
60 Hertz
®
All Predator units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and down
discharge applications, as well as all tonnage sizes.
®
Predator units are available in the following configurations:
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed options
or field-installed accessories.
All units provide constant supply air volume. A variable air
volume (VAV) option, featuring a variable frequency drive, is
available on 6-1/2 through 12-1/2 ton models.
ZF 6-1/2 THROUGH 10 TON
Tested in accordance with:
ZF12-1/2 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
528194-YTG-F-1210
Nomenclature
®
6.5-12.5 Ton York Model Number Nomenclature
Z F 090 N10 A 2 A AA 5 0 1 2 4 A
Product Style
Product Category
Z = A/C, Single Pkg., R-410A
A = Style A
B = Style B
C = Style C
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
Product Identifier
F = 11.2 + EER A/C
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Nominal Cooling Capacity
Simplicity IntelliComfort Controller
078 = 6.5 Ton
090 = 7.5 Ton
102 = 8.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
Simplicity IntelliComfort Controller w/Simplicity®LINC
York Commercial Comfort System (YCCS) Rtu Controller
Hot Gas Bypass (Standard on VAV, Optional on CV)
Variable Air Volume, VFD (not available with factory installed BAS options)
Variable Air Volume, VFD with Simplicity®LINC (not available with factory installed BAS options)
Variable Air Volume, VFD and Manual Bypass
(not available with factory installed BAS options)
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
Variable Air Volume, VFD and Manual Bypass with Simplicity®LINC
(not available with factory installed BAS options)
Variable Air Volume, VFD (BAS ready)
Gas Heat Options
Variable Air Volume, VFD and Manual Bypass (BAS ready)
Variable Air Volume, VFD Ready (for customer-provided, field-installed drive)
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
N20 = 200 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel
Variable Air Volume, VFD Ready with Simplicity®LINC
(for customer-provided, field-installed drive)
2" Pleated filters
4" Pleated filters
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Shipping Bag
Electric Heat Options
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
Product Generation
5 = Fifth Generation
Additional Options
AG = Coil Guard & Dirty Filter Switch
Airflow
AA = None
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard, Shipping Bag & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
AB = Phase Monitor
A = Std. Motor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static
Installation Options
P = Hi Static/Econo./Barometric Relief
(Downflow Only)
Q = Hi Static/Econo./Power Exhaust
(Downflow Only)
R = Hi Static/Motorized Damper (Downflow Only)
S = Hi Static/Horizontal Economizer (No Baro.)
T = Hi Static/Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static/Slab Econo./Barometric Relief
(Downflow only)
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products
3
528194-YTG-F-1210
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
Features and Benefits
Standard Features
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and low-
pressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
standard on units with scroll compressors. This accessory
monitors the incoming power to the unit and protects the
unit from phase loss and reversed phase rotation.
• High Efficiency – High efficiency units reach as high as
11.2 EER. Gas/electric units have electronic spark ignition
and power vented combustion with steady state efficiencies
of 80%. These efficiencies exceed all legislated minimum
levels and provide low operating costs.
®
• Service Friendly – The Predator incorporates a number
of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
•
Advanced Controls - Simplicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to
0F outdoor ambient without additional assistance.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air temper-
ature is low or when free cooling is available.
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The Simplicity® control board used in this product
will effectively operate the cooling system down to
0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying
this product for process cooling applications (com-
puter rooms, switchgear, etc.), please reference
applications bulletin AE-011-07 or call the applica-
tions department for Unitary Products @ 1-877-
UPG-SERV for guidance. Additional accessories
may be needed for stable operation at temperatures
below 30° F.
Both the unit control board and ignition control board utilize
flash codes to aid in diagnosis of unit malfunctions. Unique
alarm codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
®
All Predator units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
•
Anti-Short Cycle Protection - To aid compressor life,
an anti-short cycle delay is incorporated into the stan-
dard controls. Compressor reliability is further ensured
by programmable minimum run times. For testing, the
anti-short cycle delay can be temporarily overridden
with the push of a button.
• Coil Technology – ZF condensers utilize Micro-Channel
“all aluminum” condensers which provide improved heat
transfer capabilities and reduced charge volumes.
• Environmentally Aware – For improved Indoor Air
Quality, a combination of foil faced and elastometric
rubber insulation is used exclusively throughout the units.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units
are programmed with default values based upon their
configuration of cooling and heat.
®
• Balanced Heating – The Predator offers “Ultimate
st
nd
Heating Comfort” with a balance between 1 and 2 stage
®
gas heating. The first stage of a gas heat Predator unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit control
board will alarm on ignition failures, compressor lock-
outs and repeated limit switch trips.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and low-pres-
4
Johnson Controls Unitary Products
528194-YTG-F-1210
sure switches and the freezestats must trip three times
within two hours before the unit control board will lock
out the associated compressor.
• Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10-
year warranty.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained through
the loss of power.
Factory Installed Options
®
YORK offers several equipment options factory installed, for
®
the Predator line.
• Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air enthalpy sensor
enables economizer operation if the outdoor enthalpy is
less than the setpoint of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
• Reliable – From the beginning – All units undergo
computer automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term – All
• Downflow Economizer - (With barometric relief) -
The economizer is provided with a single enthalpy input.
The economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to
®
Predator units are painted with a long lasting, powder
paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
• Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
assemble and mount the outdoor air hood (Provided).
The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to
100% outdoor air. As the outdoor air intake dampers
open, the return air dampers close. The changeover
from mechanical refrigeration to economizer operation is
regulated by the standard single enthalpy input. There is
an optional input dual dry bulb available. To meet
regulated air standards, the economizer control accepts
®
To further simplify planning and installation, Predator ZF
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
an optional CO input for demand ventilation. With
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
2
single enthalpy input, the economizer control monitors
outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
• Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
• Horizontal Economizer - (Without barometric relief) -
All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
• Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field
supplied electrical disconnect switch. Utility connections can
be made quickly and with a minimum amount of field labor.
• BAS Ready Economizer -(With barometric relief) -
The economizer is provided with an actuator that
requires a 2-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully
modulating dampers capable of introducing up to 100%
outside air. Also include 2” pleated filters. BAS Ready
actuators have an adjustable auxiliary end-switch for
optional power exhaust control.
All units are shipped with 2” throw-away filters installed.
• Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5” ESP.
A variable air volume (VAV) option using a variable
frequency drive is available on 6-1/2 through 12-1/2 ton,
ZF models for applications requiring a constant supply
duct pressure. A differential pressure transducer is used
to monitor supply duct static pressure while a VAV control
board provides a speed reference signal to the VFD to
control the output of the indoor blower motor.
For units with optional VAV or Simplicity® Intelli-
Comfort™ control, a factory-installed, dry bulb sensor
determines if outdoor air temperature is low enough to
provide free-cooling operation. (Field-installed humidity
sensors for either outdoor air or outdoor & return air
streams are available for single enthalpy and differential
enthalpy configurations respectively).
Johnson Controls Unitary Products
5
528194-YTG-F-1210
•Slab Economizer for Energy Recovery Ventilators-
If the drive will not fit in the allotted space, then it will have
to be mounted elsewhere; either within the building on a
perpendicular wall which is not subjected to excessive
temperature, vibration, humidity, dust, corrosive gas,
explosive gas, etc., or within an appropriate enclosure
rated for outside installation to safeguard against
moisture, dust and excessive heat. A terminal block
located in the control box is provided for field connection
of the VFD controls.
(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to economizer
operation is regulated by the standard single enthalpy
input. There is an optional input dual dry bulb available.
To meet regulated air standards, the economizer control
• Aluminized Steel Gas Heat Exchanger - For
applications in non-corrosive environments.
• Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
accepts an optional CO input for demand
2
ventilation.With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit
provides a second input used to monitor the return air.
With a dual input kit installed, the economizer control
compares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the
maximum efficiency possible.
• Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
• Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
• Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
• Disconnect Switch - For gas heat units and cooling units
with electric heat, a HACR breaker sized to the unit is
provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry. Factory installed option or field
installed accessory.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
• Variable Air Volume (VAV); 6-1/2 through 12-1/2 ton -
A factory-installed variable frequency drive (VFD),
mounted in the Blower Access compartment, is used to
control the speed of the indoor blower motor in order to
maintain a constant static pressure in the supply duct. A
pressure transducer and VAV control board are mounted
inside the control box. The drive comes completely wired
and preprogrammed from the factory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air configurations.
• Filters – 2” Pleated MERV 7 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
An optional, factory-installed manual bypass switch
available with factory-installed VFD can be found in the
Blower Motor Access compartment. The switch can be
used to either route power to the VFD for modulating
control of the blower motor, to bypass the drive and
operate the motor at full speed, or to power the drive (and
not the motor) for diagnostic purposes.
Factory-installed smoke detectors may be subjected to
extreme temperatures during "off" times due to outside air
infiltration. These smoke detectors have an operational
range of -4 °F to 158°F. Smoke detectors installed in areas
that could be outside this range will have to be relocated to
prevent false alarms.
Due to space limitations, VAV is not available with any of
the factory-installed BAS options, but is available with
‘BAS-ready’ models. Terminal blocks are provided in the
control box for field wiring of the customer-installed BAS
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
A ‘VFD-ready’ option provides the provisions for a
customer-installed drive. The unit comes with a mounting
bracket installed in the Blower Access compartment which
may accommodate other vendor’s drives depending on
their size. In order to utilize the unit’s mounting bracket,
the maximum recommended drive dimensions are limited
to approximately 9” H x 5” W x 7.5” D.
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
6
Johnson Controls Unitary Products
528194-YTG-F-1210
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• Hot Gas Bypass - Allows operation during low load
conditions while avoiding coil frosting and damage to
compressor. When suction pressure falls below valve
setpoint, the valve modulates hot gas to the inlet of the
evaporator.
• York Commercial Comfort System (YCCS) - Provides
rooftop system integration for YCCS single zone and
change-over bypass systems (Not offered on ZR units.).
Field Installed Accessories
®
YORK offers several equipment accessories for field
HGBP is standard on all units with VAV, and optional with
constant-volume units.
®
installation, for the Predator line.
• Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
Control Options
®
• BAS - Building Automation System Controls Simplicity
INTELLI-Comfort™ Control - The York Simplicity
®
®
INTELLI-Comfort™ control is factory installed. It includes a
supply air sensor, a return air sensor, and an outside air
sensor. There are provisions for a field installed dirty filter
indicator switch, an air-proving switch, an Outside Air
Humidity sensor, a Return Air Humidity sensor, an Inside
IAQ sensor, and an Outside Air IAQ sensor. Construction
mode operation, 365-day real time clock with 7 day
programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved through
control accepts an optional CO input for demand
2
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
the INTELLI-Comfort™ using CO sensors. It uses an
2
inside CO sensor to perform Demand Ventilation. It can
2
also use an Outside CO sensor to perform Differential
Demand Ventilation. It uses a Patented Comfort Ventilation
algorithm to provide comfortable ventilation air
2
• Horizontal Economizer - (Without barometric relief) -
All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating conditions
exist. Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the on-
board connection for hot gas re-heat system. It uses the
INTELLI-Start™ algorithm to maximize energy savings by
recovering the building from the Unoccupied Setpoints to
the Occupied Setpoints just in time for the Occupied Time
• Slab Economizer for Energy Recovery Ventilator-
(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
®
Period to begin. The Simplicity INTELLI-Comfort™
balances space temperature, ventilation air temperature,
CO and humidity for ultimate comfort.
2
®
• Simplicity INTELLI-Comfort™ with Simplicity®LINC
®
Control - The York® Simplicity INTELLI-Comfort™ with
Simplicity®LINC control is factory installed. It includes all
the features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
control accepts an optional CO input for demand
2
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Incudes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
ventilation.With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
• Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
Johnson Controls Unitary Products
7
528194-YTG-F-1210
You can order 1EH0409 Barometric Relief/FA Hood for
field installations without an ERV.
valve and controls will continue to function properly at
extremely low temperatures.
• Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
• Gas Heat High Altitude Kit - This kit converts a gas heat
unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and propane.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
• Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains the
main burner orifices and gas valve replacement springs.
• Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
• Gas Piping Kit - Contains pipe nipples, fittings and gas cock
required for gas supply connection with external shut off.
• Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. The 54kW/208-240 volt, Field-installed heater
kit is not available with VAV units due to a lack of space to
accommodate the heater’s fuse block accessory.
• Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
All heaters are dual staged. Cooling units include an
adapter panel for easy installation of the electric heaters.
Necessary hardware and connectors are included with the
heaters. All heaters are intended for single point power
supply.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
• CO Sensor - Senses CO levels and automatically
2
2
overrides the economizer when levels rise above the
preset limits.
• Metal Frame Filter Kit - Metal frame with polyester filter
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Roof Curb Transition - Single Piece Adapter (10” High) -
Roof curbs for transitioning from Sunline™ units to
Predator units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
• Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can be
installed to prevent the flue exhaust from entering nearby
fresh air intakes.
®
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24-
volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
• -60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
8
Johnson Controls Unitary Products
528194-YTG-F-1210
Accessories
Field Installed Acessories - Non-Electrical
MODEL
VOLTAGE DESCRIPTION
WHERE USED
1BD0408
All
All
All
All
All
Burglar Bars, Downflow
All Cabinets
1CG0419
1CG0420
1CG0427
1CG0428
Coil Guard
Coil Guard
Coil Guard
Coil Guard
(Electric / Electric Models), 50” Tall Standard Cabinets
(Gas / Electric Models), 50" Tall Standard Cabinets
(Electric / Electric Models), 42” Tall Cabinets
(Gas / Electric Models), 42" Tall Cabinets
All Tall (50") Standard Cabinets, (Excludes 12.5T "V"
cabinets)
All Short (42") Standard Cabinets
All Cabinets
All Tall 50" Cabinets
All Tall 42" Cabinets
All Tall 50" Cabinets
All Tall 42" Cabinets
All Cabinets
1HG0411
1HG0415
1FE0411
1FF0414
1FF0415
1FL0402
1FL0423
1GP0405
1HA0442
1HA0443
1NP0442
1RC0470
1RC0471
All
All
All
All
All
All
All
All
All
All
All
All
All
Hail Guard Kit
Hail Guard Kit
Flue Exhaust Extension Kit
2" only Metal Filter Frame Kit
2" only Metal Filter Frame Kit
Permanent 2" only Filter Kit Includes (4) Four Filters)
Permanent 2" only Filter Kit (Includes (4) four Filters)
Gas Piping Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Propane Conversion Kit
All 6 - 12T Cabinets
All 6 - 12T Cabinets
All 6 - 12T Cabinets
All Cabinets
Roof Curb, 8" Height
Roof Curb, 14" Height
All Cabinets
Roof Curb, Transition (7.5 T thru 12.5T Sunline to
Predator 3- 12T)
Wooden Crate for extra protection during shipping and
handling
1RC0472
1WC0412
All
All
All Cabinets
Standard Cabinets Only (not applicable to units 119" in
length)
Field Installed Acessories - Electric Heat
MODEL
VOLTAGE DESCRIPTION
WHERE USED
2TP04520925
2TP04520946
2TP04520958
2TP04531825
2TP04531846
2TP04521858
2TP04532425
2TP04532446
2TP04522458
2TP04533625
2TP04533646
2TP04523658
2TP04525425
2TP04525446
2TP04525458
2TP04540925
2TP04540946
2TP04540958
2TP04541825
2TP04541846
2TP04541858
2TP04542425
2TP04542446
2TP04542458
2TP04543625
2TP04543646
2TP04543658
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
230
460
575
9kW Electric Heat
18kW Electric Heat
24kW Electric Heat
36kW Electric Heat
54kW Electric Heat
9kW Electric Heat
18kW Electric Heat
24kW Electric Heat
36kW Electric Heat
All 50" Cabinet 6.5 and 8.5 Ton Models
All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models
All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models
All 50" Cabinet 6.5, 8.5, 10 and 12.5 Ton Models
All 50" 10 and 12.5 Ton Models
All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models
All 42" 6.5, 7.5 and 8.5 Ton Models
All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models
All 42" Cabinet 6.5, 7.5 and 8.5 Ton Models
Johnson Controls Unitary Products
9
528194-YTG-F-1210
Accessories (Continued)
Field Installed Acessories - Fresh Air
MODEL
VOLTAGE DESCRIPTION
WHERE USED
All Cabinets
All Cabinets
Barometric Relief Kit for Power Exhaust, Downflow
All
All
1EH0407
Application (Includes Hood)
Barometric Relief Kit for Power Exhaust, Horizontal
Application
1EH0408
Barometric Relief/Hood Kit - Required for field installed
slab economizer without ERV
Manual Outside Air Damper 0-35%, Downflow
Manual Outside Air Damper 0-100%, Downflow
Barometric Relief Kit for Horizontal Applications
Dual Enthalpy Control
1EH0409
1FA0413
1FA0414
1RD0411
2EC04700924
All
All
All
All
All
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
Downflow Economizer, Slab type for ERV, (no
Barometric Relief or FA hood)
2EE04705724
All
All 50" Cabinets
Downflow Economizer, Slab type for ERV, (no
Barometric Relief or FA hood)
Downflow Economizer with Barometric Relief
Horizontal Economizer without Barometric Relief
Motorized Damper, Downflow without Barometric Relief All Cabinets
Motorized Damper, Horizontal
Power Exhaust 230V Downflow or Horizontal
Power Exhaust 460V Downflow or Horizontal
Power Exhaust 575V Downflow or Horizontal
2EE04705824
2EE04705924
2EE04706024
2MD04703224
2MD04703724
2PE04703225*
2PE04703246*
2PE04703258*
All
All
All
All
All
230
460
575
All 42" Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
All Cabinets
* Must be installed in return Duct on Horizontal Applications and a 1EH0408 is required.
Field Installed Acessories - Controls
MODEL
2AP0401
2AQ04700324
2AQ04700424
2DF0402
VOLTAGE DESCRIPTION
WHERE USED
All Units
All Units
All Units
All Units
All Units
All
All
All
All
All
Air Proving Switch
CO2 Space Accessory
CO2 Unit Accessory
Dirty Air Switch
2DH04700024
Humidistat
All Gen 4 or older units with 2" Filter only capable
Cabinets
All Gen 5 units with 2" & 4" Filters
All Gen 5 units with 2" & 4" Filters
All Gen 5 units with 2" & 4" Filters
2SD04700624
2SD04700824
2SD04700924
2SD04701024
All
All
All
All
Smoke Detector for Supply or Return
Smoke Detector for Supply
Smoke Detector for Return
Smoke Detector for Supply and Return
Field Installed Acessories - Electrical
MODEL
VOLTAGE DESCRIPTION
WHERE USED
2BC04700106
2BC04700151
2BC04700154
2LA04704632
230
460
575
All
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Gas heat kit, -60ºF
Low Ambient Kit
All Units
All Units
All Units
All 3 - 10T units (excludes 12.5T "V" cabinets)
®
sizes. Predator units are available in the following
Guide Specifications
configurations: cooling only, cooling with electric heat, cooling
with gas heat, heat pump, and heat pump with electric heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
GENERAL
Units shall be manufactured by York International Unitary
Products in an ISO 9001 certified facility. YORK® Predator
®
units are convertible single packages with a common footprint
cabinet and common roof curb for all 6-1/2 through 12-1/2 ton
models. All units have two compressors with independent R-
410A refrigeration circuits to provide 2 stages of cooling. The
units were designed for light commercial applications and can
DESCRIPTION
Units shall be factory assembled, single package, (Elec/Elec, Gas/
Elec), designed for outdoor installation. They shall have built in
field convertible duct connections for down discharge supply/return
or horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410A refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and ARI test procedures. Units shall
be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-
M90 standards.
®
be easily installed on a roof curb, slab, or frame. All Predator
units are self-contained and assembled on rigid full perimeter
base rails allowing for 3-way forklift access and overhead
rigging. Every unit is completely charged with R-410A, wired,
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
10
Johnson Controls Unitary Products
528194-YTG-F-1210
UNIT CABINET
a. Evaporator coils shall have aluminum plate fins
mechanically bonded to seamless internally enhanced
copper tubes with all joints brazed. Special Phenolic
coating shall be available as a factory option.
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished as standard and be accessible through hinged access
door. Fan performance measuring ports shall be provided on
the outside of the cabinet to allow accurate air measurements
of evaporator fan performance without removing panels or
creating bypass of the coils. Condensate pan shall be slide out
design, constructed of a non corrosive material, internally
sloped and conforming to ASHRAE 62-B9 standards.
Condensate connection shall be a minimum of ¾” I.D. female
and be rigid mount connection.
b. Evaporator coils shall be of the direct expansion, draw-
thru design.
c. Condenser coils shall have Mirco-Channel aluminum
tube, aluminum fins.
d. Condenser coils shall be of the direct expansion, draw-
thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice or thermally operated
expansion devices.
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
INDOOR (EVAPORATOR) FAN ASSEMBLY
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the ser-
vice factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
c. Loss-of-charge/Low-pressure switch.
• High-pressure switch.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
• Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
REFRIGERANT COMPONENTS
Compressors:
f. Unit control board shall have on-board diagnostics and
fault code display.
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
h. Control board shall monitor each refrigerant safety switch
independently.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
i. Control board shall retain last 5 fault codes in non-
volatile memory, which will not be lost in the event of a
power loss.
Coils:
Johnson Controls Unitary Products
11
528194-YTG-F-1210
GAS HEATING SECTION (IF EQUIPPED)
intake dampers shall not exceed 2% when dampers are
fully closed and operating against a pressure differential
of 0.5 IWG. A unit-mounted potentiometer shall be
provided to adjust the outdoor and return air damper
assembly to take in outdoor air to meet the minimum
ventilation requirement of the conditioned space during
normal operation. During economizer operation, a mixed-
air temperature control shall modulate the outdoor and
return air damper assembly to prevent the supply air
temperature from dropping below 55 ºF. Changeover from
compressor to economizer operation shall be provided by
an integral electronic enthalpy control that feeds input into
the basic module. The outdoor intake opening shall be
covered with a rain hood that matches the exterior of the
unit. Water eliminator/filters shall be provided.
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft com-
bustion with post purge logic, energy saving direct spark igni-
tion, and redundant main gas valve. The heat exchanger shall
be of the tubular type, constructed of T1-40 aluminized steel for
corrosion resistance and allowing minimum mixed air entering
temperature of 40 ºF. Burners shall be of the in-shot type, con-
structed of aluminum-coated steel. All gas piping shall enter the
unit cabinet at a single location, through either the side or bot-
tom, without any field modifications. An integrated control board
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief or power exhaust.
a. Primary and auxiliary high-temperature limit switches.
b. Induced draft pressure sensor.
c. Flame roll out switch (manual reset).
d. Flame proving controls.
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
e. All two stage units shall have two independent stages of
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return
to the fully closed position when the indoor fan motor is
de-energized. Dampers shall fully close on power loss.
st
nd
capacity (60% 1 stage, 100% 2 stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two states
of capacity all sizes. The heating section shall have a primary
limit control(s) (automatic reset) to prevent the heating element
system from operating at an excessive temperature. The Heat-
ing Section assembly shall slide out of the unit for easy mainte-
nance and service. Units with Electric Heating Sections shall be
wired for a single point power supply with branch circuit fusing
(where required).
ADDITIONAL FACTORY INSTALLED OPTIONS
UNIT OPERATING CHARACTERISTICS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of ARI Standard
340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature. Unit
shall be provided with fan time delay to prevent cold air delivery
before heat exchanger warms up. (Gas heat only)
• Variable Air Volume (VAV) – The VAV option using a
varible frequency drive (VFD) shall be available on 6-1/2
through 12-1/2 ton, models for applications requiring a
constant supply-duct static pressure. Unts equipped for
VAV shall be controlled by a duct pressure transducer
with a 0 - 5” WC pressure range. The pressure transducer
shall provide a 0 - 5 VDC output signal to a VAV control
board which, in turn shall provide a 2 - 10 VDC speed
reference signal to the VFD. The VAV control board shall
operate using factory-installed Supply Air, Return Air and
Outside Air Temperature Sensors with a nominal
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Heat Exchanger – 10 Years, Elect. Heat Elem. – 5 Years,
Parts – 1 Year
resistance of 10,000 Ohms. Units equipped with VFD’s
shall have factory-installed manual bypass as an option.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER
– Outdoor and return air dampers that are interlocked and
positioned by a fully-modulating, spring-return damper
actuator. The maximum leakage rate for the outdoor air
• ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
12
Johnson Controls Unitary Products
528194-YTG-F-1210
• PHASE MONITOR - Designed to prevent damage in out-
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
of-phase condition.
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high-
pressure drop across the filters.
• PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
• BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
• 60ºF GAS HEAT KIT – Provides an electric heat kit for the
gas compartment for use in extreme low ambient
conditions.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• STAINLESS STEEL HEAT EXCHANGER – For
applications in a corrosive environment, this option
provides a full stainless steel heat exchanger assembly.
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
Johnson Controls Unitary Products
13
528194-YTG-F-1210
Physical Data
ZF078-150 Physical Data
Component
Models
ZF102
8.5
ZF078
6.5
ZF090
7.5
ZF120
10
ZF150
12.5
Nominal Tonnage
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Mbh)
ARI net capacity (Mbh)
EER
81000
78000
11.2
90000
88000
11.2
104000
101000
11.2
126000
120000
11.2
156000
150000
11.2
IEER
13
12.1
12.5
12.5
12.7
IPLV
12.9
12.1
12.5
12.6
13.06
4100
Nominal CFM
2600
6.95
2500
7.87
3000
4000
System power (KW)
Refrigerant type
Refrigerant charge (lb-oz)
System 1
8.60
10.70
R-410A
13.40
R-410A
R-410A
R-410A
R-410A
4-12
4-10
4-12
4-10
4-14
5-0
6-8
6-8
7-8
7-8
System 2
ARI HEATING PERFORMANCE
Heating model
10
15
180
144
-
10
15
180
144
-
10
15
180
144
-
15
20
240
192
-
15
20
240
192
-
Heat input (K Btu)
Heat output (K Btu)
AFUE %
120
96
120
96
120
96
180
144
-
180
144
-
-
-
-
Steady state efficiency (%)
No. burners
80
80
80
80
80
80
80
80
80
80
4
6
4
6
4
6
6
8
6
8
No. stages
21
21
21
21
21
21
21
21
21
21
Temperature Rise Range (ºF)
Gas Limit Setting (ºF)
Gas piping connection (in.)
DIMENSIONS (inches)
Length
20-50
165
3/4
35-65
165
3/4
15-45
165
3/4
30-60
165
3/4
10-40
215
3/4
25-55
195
3/4
20-50
195
3/4
35-65
160
3/4
10-40
195
3/4
25-55
160
3/4
89
59
89
59
89
59
89
59
119-1/2
Width
59
Height
42
42
50-3/4
1020
50-3/4
1060
50-3/4
1253
OPERATING WT. (lbs.)
COMPRESSORS
Type
860
880
Recip
2
Recip
2
Recip
2
Recip
2
Scroll
2
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
18.5
1
18.5
1
18.5
1
29.0
1
29.0
1
Fins per inch
23
23
23
23
23
Tube diameter (in.)/mm
.71/18
.71/18
.71/18
.71/18
1/25
2-pass
2-pass
2-pass
2-pass
2-pass
Circuitry Type
Microchannel
Microchannel
Microchannel
Microchannel
Microchannel
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
Rows
10.6
3
10.6
3
13.2
3
13.2
4
13.2
3
Fins per inch
15
15
15
15
15
Tube diameter
Circuitry Type
0.375
Intertwined
TXV
0.375
Intertwined
TXV
0.375
Intertwined
TXV
0.375
Intertwined
TXV
0.375
Intertwined
TXV
Refrigerant control
14
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Physical Data (Continued)
Component
Models
ZF102
8.5
ZF078
6.5
ZF090
7.5
ZF120
10
ZF150
12.5
Nominal Tonnage
CONDENSER FAN DATA
Quantity of Fans
Fan diameter (Inch)
Type
2
24
2
24
2
24
2
24
4
24
Prop
Direct
2
Prop
Direct
2
Prop
Direct
2
Prop
Direct
2
Prop
Direct
4
Drive type
Quantity of motors
Motor HP each
No. speeds
1/3
3/4
3/4
3/4
3/4
1
1
1
1
1
RPM
850
6200
1110
7600
1110
8300
1110
9500
1110
13900
Nominal total CFM
BELT DRIVE EVAP FAN DATA
Quantity
1
1
1
1
1
Fan Size (Inch)
Type
12 x 12
Centrifugal
12 x 12
15 x 15
Centrifugal
15 x 15
Centrifugal
15 x 15
Centrifugal
Centrifugal
Motor Sheave
Blower Sheave
Belt
1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VM50 1VP56
AK74
A49
AK64
A49
2
AK74
A49
AK61
A49
3
AK89
A56
2
AK74
A54
3
AK84
A56
2
AK74
A54
3
AK74
A54
3
BK77
BX55
5
Motor HP each
RPM
1-1/2
1725
56
1-1/2
1725
56
1725
56
1725
56
1725
56
1725
56
1725
56
1725
56
1725
56
1725
184T
Frame size
FILTERS
Quantity - Size
4 - (24 x 16 x 2)2, 3 4 - (24 x 16 x 2)2, 3 4 - (24 x 20 x 2)2, 3 4 - (24 x 20 x 2)2, 3 4 - (24 x 20 x 2)2, 3
4 - (24 x 16 x 4)4 4 - (24 x 16 x 4)4 4 - (24 x 20 x 4)4 4 - (24 x 20 x 4)4 4 - (24 x 20 x 4)4
ST
nd
1.
1
Stage 60% of 2 Stage
2. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3
3. 2 In. Pleated, Optional, MERV 7
4. 4 In. Pleated, Optional, MERV 13
Johnson Controls Unitary Products
15
528194-YTG-F-1210
ZF078-150 Unit Limitations
Unit Limitations
Applied Voltage
Size
(Tons)
Model
ZF
Unit Voltage
Outdoor DB Temp
Min
187
432
540
187
432
540
187
432
540
187
432
540
187
432
540
Max
252
504
630
252
504
630
252
504
630
252
504
630
252
504
630
Max (°F)
125
125
125
125
125
125
125
125
125
125
125
125
125
125
125
208/230-3-60
460-3-60
078
(6.5)
575-3-60
208/230-3-60
460-3-60
090
(7.5)
ZF
575-3-60
208/230-3-60
460-3-60
102
(8.5)
ZF
575-3-60
208/230-3-60
460-3-60
120
(10)
ZF
575-3-60
208/230-3-60
460-3-60
150
(12.5)
ZF
575-3-60
16
Johnson Controls Unitary Products
528194-YTG-F-1210
Capacity Performance
ZF078-150 Cooling Capacities
ZF078 (6.5 Ton)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
WB
(°F)
CFM
2
90
85
75°F
34.0
46.4
58.7
72.4
38.0
51.5
65.1
77.5
79.2
41.9
56.7
71.4
82.5
81.9
45.9
61.9
77.8
87.6
84.6
65.9
82.9
89.5
86.5
70.0
80
75
70
65
90
85
85°F
32.5
44.2
55.8
69.4
36.2
49.1
61.9
73.1
74.4
40.0
54.0
68.1
76.8
76.9
43.7
58.9
74.2
80.4
79.4
63.1
79.3
82.0
81.0
67.3
84.5
83.6
82.5
105°F
28.5
39.3
50.0
61.3
31.9
43.8
55.7
63.3
61.4
35.3
48.4
61.4
65.3
63.3
38.7
52.9
67.1
67.3
65.3
57.1
70.9
68.5
66.4
61.3
74.8
69.7
67.6
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
102.9
94.8
86.7
79.2
106.6
98.2
89.8
82.0
79.2
110.2
101.6
92.9
84.8
81.9
113.9
104.9
95.9
87.6
84.6
107.2
98.0
89.5
86.5
109.4
100.1
91.4
88.3
5.0
5.0
5.0
5.0
5.0
5.0
5.0
5.0
4.9
5.0
5.0
5.0
5.0
4.9
5.0
5.0
5.0
5.0
4.9
5.0
5.0
5.0
4.9
5.0
5.0
5.0
4.9
41.5
53.8
66.1
79.2
46.7
60.3
73.8
82.0
79.2
52.0
66.7
81.5
84.8
81.9
57.2
73.2
89.2
87.6
84.6
78.2
94.6
89.5
86.5
83.1
26.6
38.9
51.3
61.4
29.3
42.8
56.3
67.5
71.1
31.9
46.7
61.4
73.6
77.5
34.5
50.5
66.5
79.7
83.9
53.6
70.6
85.5
86.1
56.8
74.7
91.4
88.3
-
-
-
96.2
88.3
80.3
72.8
99.6
91.4
83.1
75.4
74.4
103.0
94.4
85.9
77.9
76.9
106.3
97.5
88.7
80.4
79.4
99.5
90.5
82.0
81.0
101.4
92.3
83.6
82.5
5.6
5.5
5.5
5.4
5.6
5.5
5.5
5.4
5.4
5.6
5.5
5.5
5.4
5.4
5.6
5.5
5.5
5.5
5.4
5.6
5.5
5.5
5.4
5.6
5.5
5.5
5.4
39.9
51.6
63.3
72.8
44.9
57.8
70.6
75.4
74.4
49.9
63.9
78.0
77.9
76.9
54.9
70.1
85.3
80.4
79.4
75.3
88.8
82.0
81.0
80.4
92.3
83.6
82.5
25.0
36.7
48.4
58.6
27.6
40.4
53.3
64.4
66.4
30.1
44.1
58.1
70.3
72.5
32.6
47.8
63.0
76.2
78.5
51.0
67.2
79.9
80.5
54.2
71.4
83.6
82.5
-
-
-
31.5
43.8
54.0
-
-
-
29.3
41.0
51.1
-
-
-
1625
36.4
46.6
-
-
33.6
43.7
-
-
39.1
36.3
-
-
34.1
47.6
58.8
62.4
-
-
-
31.7
44.6
55.8
57.7
-
-
-
1950
2275
2600
38.9
50.0
53.6
-
-
35.9
47.1
49.1
-
-
41.3
38.4
44.9
40.4
-
-
36.6
51.4
63.6
67.5
-
-
-
34.2
48.2
60.4
62.5
-
-
-
41.3
53.5
57.4
-
-
38.3
50.5
52.6
-
-
43.5
40.6
47.4
42.7
-
-
39.2
55.2
68.3
72.6
41.4
58.4
73.3
73.8
43.6
61.6
78.2
75.1
-
-
-
36.6
51.8
65.0
67.3
38.8
55.0
67.8
68.4
41.0
58.3
70.5
69.4
-
-
-
43.8
57.0
61.2
-
40.7
53.8
56.2
-
45.7
49.9
-
42.7
45.0
-
46.1
61.0
61.6
-
-
42.9
55.6
56.2
-
-
2925
3250
48.7
49.3
-
43.5
44.1
-
100.1 87.9
48.4
65.0
61.9
-
45.1
57.4
56.3
-
91.4
88.3
91.4
88.3
95°F
30.9
41.9
53.0
66.5
34.4
46.6
58.8
68.7
69.5
38.0
51.3
64.7
71.0
71.8
41.6
56.0
70.5
73.3
74.1
60.3
75.8
74.6
75.5
64.6
81.1
75.9
76.8
51.8
48.7
44.2
43.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
89.6
81.7
73.9
66.5
92.6
84.5
76.5
68.7
69.5
95.7
87.3
79.0
71.0
71.8
98.7
90.1
81.5
73.3
74.1
91.7
83.0
74.6
75.5
93.4
84.4
75.9
76.8
6.1
6.1
6.0
5.9
6.1
6.1
6.0
5.9
5.9
6.2
6.1
6.0
5.9
6.0
6.2
6.1
6.0
6.0
6.0
6.1
6.0
6.0
6.0
6.1
6.0
6.0
6.0
38.3
49.3
60.4
66.5
43.0
55.2
67.4
68.7
69.5
47.8
61.1
74.4
71.0
71.8
52.6
67.0
81.5
73.3
74.1
72.4
83.0
74.6
75.5
77.7
84.4
75.9
76.8
23.5
34.5
45.6
55.7
25.8
38.0
50.2
61.4
61.7
28.2
41.5
54.9
67.0
67.4
30.6
45.1
59.5
72.7
73.1
48.3
63.8
74.3
74.9
51.5
68.1
75.9
76.8
-
-
-
82.4
74.8
67.2
61.3
85.1
77.3
69.4
63.3
61.4
87.8
79.7
71.7
65.3
63.3
90.5
82.2
73.9
67.3
65.3
83.6
75.2
68.5
66.4
85.1
76.4
69.7
67.6
6.7
6.6
6.5
6.4
6.7
6.6
6.5
6.4
6.4
6.8
6.7
6.5
6.4
6.4
6.8
6.7
6.6
6.5
6.4
6.7
6.6
6.5
6.4
6.7
6.6
6.5
6.4
33.7
46.6
59.4
61.3
40.4
52.3
64.2
63.3
61.4
47.1
58.1
69.0
65.3
63.3
53.7
63.8
73.9
67.3
65.3
69.1
75.1
68.5
66.4
74.3
76.4
69.7
67.6
21.2
31.9
42.7
51.7
23.4
35.3
47.2
57.2
53.9
25.6
38.7
51.7
62.6
59.0
27.8
42.0
56.2
68.0
64.1
45.1
60.4
68.9
65.9
48.3
64.6
69.7
67.6
-
-
-
27.1
38.2
48.3
-
-
-
24.6
35.4
44.4
-
-
-
1625
1950
30.8
40.9
-
-
28.1
37.1
-
-
33.5
29.8
-
-
29.4
41.6
52.8
53.1
-
-
-
26.8
38.7
48.6
45.4
-
-
-
33.0
44.2
44.5
-
-
30.2
40.1
36.9
-
-
35.6
31.6
35.9
28.4
-
-
31.8
45.1
57.2
57.6
-
-
-
29.0
42.0
52.9
49.3
-
-
-
2275
2600
35.3
47.4
47.8
-
-
32.3
43.2
39.6
-
-
37.6
33.5
38.0
29.9
-
-
34.1
48.5
61.7
62.1
36.3
51.7
62.2
62.9
38.4
55.0
62.8
63.7
-
-
-
31.1
45.3
57.2
53.2
33.2
48.4
56.9
53.9
35.2
51.5
56.6
54.5
-
-
-
37.5
50.7
51.1
-
34.4
46.3
42.4
-
39.7
40.1
-
35.4
31.5
-
39.7
50.2
50.9
-
-
36.5
44.9
41.9
-
-
2925
3250
38.2
38.8
-
33.0
30.0
-
41.9
49.7
50.6
-
38.5
43.6
41.5
-
36.6
37.5
30.5
28.5
Johnson Controls Unitary Products
17
528194-YTG-F-1210
ZF078 (6.5 Ton) (Continued)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
1
WB
(°F)
CFM
1625
2
2
90
85
115°F
26.1
36.6
47.1
56.1
29.4
41.0
52.6
57.8
53.2
32.6
45.4
58.2
59.6
54.8
35.9
49.8
63.7
61.4
56.5
53.9
66.1
62.4
57.4
58.0
68.4
63.4
58.4
80
75
70
65
90
85
125°F
22.9
33.9
44.1
50.9
26.8
38.1
49.5
52.4
45.1
30.8
42.4
54.9
53.9
46.4
34.7
46.7
58.6
55.5
47.7
50.7
59.5
56.3
48.4
54.7
60.5
57.2
49.1
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
75.2
67.9
60.5
56.1
77.6
70.0
62.4
57.8
53.2
80.0
72.2
64.3
59.6
54.8
82.3
74.3
66.2
61.4
56.5
75.5
67.3
62.4
57.4
76.8
68.4
63.4
58.4
7.3
7.1
7.0
6.8
7.3
7.2
7.0
6.9
6.8
7.4
7.2
7.0
6.9
6.8
7.4
7.2
7.1
7.0
6.9
7.3
7.1
7.0
6.9
7.3
7.1
7.0
6.9
29.2
43.8
58.4
56.1
37.8
49.4
61.0
57.8
53.2
46.3
55.0
63.6
59.6
54.8
54.9
60.6
66.2
61.4
56.5
65.8
67.3
62.4
57.4
71.0
68.4
63.4
58.4
18.9
29.3
39.8
47.7
20.9
32.6
44.2
52.9
46.1
23.0
35.8
48.6
58.2
50.6
25.1
39.0
52.9
63.4
55.2
42.0
57.0
63.4
56.8
45.0
61.1
63.4
58.4
-
-
-
68.0
60.9
53.8
50.9
70.1
62.7
55.4
52.4
45.1
72.1
64.6
57.0
53.9
46.4
74.2
66.4
58.6
55.5
47.7
67.4
59.5
56.3
48.4
68.5
60.5
57.2
49.1
7.9
7.7
7.5
7.3
7.9
7.7
7.5
7.4
7.2
8.0
7.8
7.6
7.4
7.2
8.0
7.8
7.6
7.5
7.3
7.8
7.6
7.5
7.3
7.9
7.7
7.5
7.4
28.3
41.0
53.8
50.9
37.5
46.5
55.4
52.4
45.1
46.8
51.9
57.0
53.9
46.4
56.0
57.3
58.6
55.5
47.7
62.5
59.5
56.3
48.4
67.6
60.5
57.2
49.1
16.6
26.8
36.9
43.7
18.5
29.8
41.2
48.7
38.3
20.4
32.9
45.4
53.8
42.2
22.3
36.0
49.7
55.5
46.2
38.9
53.6
56.3
47.7
41.7
57.6
57.2
49.1
-
-
-
22.1
32.6
40.5
-
-
-
19.6
29.8
36.6
-
-
-
25.4
33.3
-
-
22.7
29.4
-
-
26.0
22.3
-
-
24.2
35.8
44.5
37.7
-
-
-
21.5
32.9
40.4
29.9
-
-
-
1950
2275
2600
27.4
36.1
29.2
-
-
24.5
32.1
21.6
-
-
27.7
23.8
20.8
13.3
-
-
26.2
39.0
48.6
41.0
-
-
-
23.4
35.9
44.3
32.7
-
-
-
29.4
39.0
31.4
-
-
26.4
34.8
23.2
-
-
29.4
25.3
21.8
13.7
-
-
28.2
42.1
52.6
44.4
30.1
45.1
51.5
44.9
32.0
48.1
50.4
45.4
-
-
-
25.3
39.0
48.1
35.6
27.0
41.8
46.2
35.9
28.8
44.6
44.3
36.2
-
-
-
31.4
41.9
33.6
-
28.3
37.4
24.9
-
31.1
22.8
-
26.8
14.2
-
33.2
39.7
33.0
-
-
30.0
34.4
24.1
-
-
2925
3250
27.8
21.1
-
22.6
12.3
-
35.1
37.5
32.4
-
31.7
31.3
23.3
-
24.5
19.4
18.4
10.3
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
18
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF090 (7.5 Ton)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
WB
CFM
2
(°F)
90
85
75°F
41.4
55.1
68.8
82.1
45.0
59.7
74.5
87.4
95.1
48.5
64.3
80.1
92.8
97.4
52.1
69.0
85.8
98.2
99.8
73.6
80
75
70
65
90
85
85°F
39.2
52.3
65.3
79.2
42.7
56.8
70.8
83.1
88.3
46.2
61.3
76.4
87.1
90.5
49.7
65.8
81.9
91.0
92.7
70.6
87.8
93.5
95.3
75.5
80
75
70
65
77
119.9
110.5
101.1
91.2
6.0
6.0
6.0
6.1
6.0
6.0
6.1
6.1
6.0
6.1
6.1
6.1
6.1
6.0
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.0
6.1
6.1
6.1
6.0
49.5
63.2
76.9
91.2
54.1
68.8
83.6
93.6
95.1
58.7
74.5
90.3
95.9
97.4
63.2
80.1
97.0
98.2
99.8
85.8
33.3
47.0
60.7
72.7
35.8
50.6
65.3
78.3
85.3
38.4
54.2
70.0
83.9
91.4
41.0
57.8
74.7
89.5
97.5
61.4
79.4
-
-
-
112.2
103.0
93.7
6.6
6.6
6.6
6.6
6.7
6.7
6.6
6.6
6.5
6.7
6.7
6.7
6.6
6.6
6.8
6.7
6.7
6.7
6.6
6.7
6.7
6.7
6.6
6.7
6.7
6.7
6.6
47.2
60.2
73.2
84.5
51.8
65.8
79.8
86.7
88.3
56.3
71.4
86.4
88.8
90.5
60.9
76.9
93.0
91.0
92.7
82.8
99.8
93.5
95.3
88.7
31.3
44.3
57.3
68.8
33.7
47.8
61.8
74.1
79.5
36.2
51.2
66.3
79.5
85.2
38.6
54.7
70.7
84.8
91.0
58.4
75.6
90.5
94.4
62.2
80.5
96.1
97.9
-
-
-
72
38.8
52.5
64.6
-
-
-
36.4
49.4
60.8
-
-
-
1875
67
44.4
56.4
-
-
41.4
52.9
-
-
62
77
72
48.3
84.5
44.9
123.0
113.3
103.6
93.6
-
115.1
105.6
96.1
-
41.4
56.2
69.2
76.1
-
-
-
38.8
52.8
65.1
70.5
-
-
-
2250
2625
3000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
47.1
60.0
67.0
-
-
43.8
56.1
61.5
-
-
50.9
86.7
47.1
95.1
57.9
88.3
52.5
126.0
116.1
106.2
95.9
-
118.0
108.2
98.5
-
44.1
59.9
73.8
81.2
-
-
-
41.2
56.2
69.4
75.2
-
-
-
49.7
63.7
71.1
-
-
46.1
59.3
65.1
-
-
53.5
88.8
49.3
97.4
61.0
90.5
55.0
129.1
118.9
108.8
98.2
-
120.8
110.9
100.9
91.0
-
46.7
63.6
78.4
86.3
49.3
67.2
84.6
-
-
-
43.5
59.6
73.7
79.9
46.2
63.4
78.3
82.2
48.9
67.2
82.8
84.6
-
-
-
52.4
67.3
75.2
-
48.5
62.6
68.7
-
56.1
64.1
-
51.4
57.6
-
99.8
92.7
122.5
112.0
101.1
102.8
126.1
115.3
104.1
105.8
114.0
103.7
93.5
106.1 91.5
101.1 101.1 96.8
55.0
72.5
77.3
-
-
51.2
66.1
70.0
-
-
3375
3750
60.3
65.1
-
53.9
57.9
-
102.8 102.8 101.6 89.4
95.3
91.5
78.3
65.1
84.1
51.9
70.9
117.1
106.5
96.1
115.3 97.3
57.6
77.7
79.4
-
106.5 93.7
53.9
69.6
71.4
-
104.1 104.1 104.1 90.9
105.8 105.8 105.8 92.6
95°F
64.5
66.1
96.1
97.9
96.1
97.9
105°F
33.5
46.1
58.6
70.3
36.7
50.2
63.8
72.3
75.0
39.8
54.4
69.0
74.3
76.9
42.9
58.5
74.1
76.4
78.7
63.0
79.4
78.2
80.5
67.5
84.6
79.9
82.4
56.3
58.1
97.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
104.6
95.4
86.3
77.8
107.2
97.9
88.6
79.8
81.6
109.9
100.4
90.8
81.8
83.6
112.6
102.8
93.0
83.8
85.7
105.4
95.4
86.0
87.9
108.1
97.8
88.1
90.1
7.3
7.2
7.1
7.0
7.3
7.3
7.2
7.1
7.1
7.4
7.3
7.2
7.1
7.1
7.4
7.4
7.3
7.2
7.1
7.4
7.3
7.2
7.2
7.4
7.3
7.2
7.2
44.9
57.2
69.6
77.8
49.4
62.8
76.1
79.8
81.6
54.0
68.3
82.6
81.8
83.6
58.5
73.8
89.1
83.8
85.7
79.9
93.4
86.0
87.9
86.0
97.8
88.1
90.1
37.1
49.5
61.8
76.3
40.5
53.9
67.2
78.8
81.6
44.0
58.3
72.6
81.3
83.6
47.4
62.7
77.9
83.8
85.7
67.6
84.1
86.0
87.9
72.6
90.2
88.1
90.1
29.3
41.7
54.0
64.8
31.6
45.0
58.3
69.9
73.7
34.0
48.2
62.5
75.0
79.1
36.3
51.5
66.8
80.2
84.5
55.4
71.8
84.1
87.3
59.3
76.9
88.1
90.1
-
-
-
95.9
87.2
78.5
71.0
98.3
89.4
80.5
72.8
75.0
100.8
91.6
82.5
74.6
76.9
103.2
93.9
84.5
76.4
78.7
96.0
86.5
78.2
80.5
98.2
88.4
79.9
82.4
7.9
7.8
7.6
7.5
8.0
7.8
7.7
7.6
7.6
8.0
7.9
7.8
7.6
7.6
8.1
7.9
7.8
7.7
7.7
8.0
7.8
7.7
7.7
8.0
7.9
7.7
7.7
40.1
53.9
67.7
71.0
45.5
59.1
72.7
72.8
75.0
50.9
64.3
77.6
74.6
76.9
56.3
69.4
82.5
76.4
78.7
75.0
85.5
78.2
80.5
80.6
88.4
79.9
82.4
25.7
38.2
50.8
60.2
27.8
41.4
54.9
65.1
67.2
29.9
44.5
59.1
70.0
72.3
32.0
47.6
63.2
74.9
77.3
51.0
67.8
77.4
79.9
54.5
72.4
79.9
82.4
-
-
-
33.9
46.3
57.1
-
-
-
30.4
43.0
52.3
-
-
-
1875
2250
38.5
49.3
-
-
35.1
44.5
-
-
41.5
36.7
-
-
36.1
49.4
61.0
64.8
-
-
-
32.5
46.1
56.2
58.3
-
-
-
40.5
52.2
56.0
-
-
37.2
47.3
49.5
-
-
43.3
38.5
47.1
40.6
-
-
38.2
52.5
65.0
69.1
-
-
-
34.6
49.2
60.1
62.4
-
-
-
2625
3000
42.5
55.0
59.1
-
-
39.3
50.2
52.5
-
-
45.0
40.3
49.1
42.6
-
-
40.4
55.7
69.0
73.4
43.2
59.6
71.9
75.0
46.0
63.5
74.8
76.7
-
-
-
36.7
52.3
64.0
66.4
39.1
55.8
65.4
67.9
41.5
59.4
66.9
69.4
-
-
-
44.5
57.9
62.2
-
41.4
53.0
55.5
-
46.8
51.1
-
42.1
44.6
-
47.4
59.7
62.8
-
-
43.9
53.5
55.9
-
-
3375
3750
47.4
50.6
-
41.5
43.9
-
50.2
61.4
63.4
-
46.3
53.9
56.3
-
48.1
50.1
40.9
43.3
Johnson Controls Unitary Products
19
528194-YTG-F-1210
ZF090 (7.5 Ton) (Continued)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
1
WB
(°F)
CFM
1875
2
2
90
85
115°F
30.0
42.7
55.4
64.2
32.8
46.6
60.4
65.8
68.5
35.6
50.5
65.4
67.4
70.1
38.4
54.4
70.3
68.9
71.8
58.4
74.7
70.3
73.2
62.4
79.1
71.7
74.7
80
75
70
65
90
85
125°F
26.4
39.3
52.3
57.4
28.9
43.0
57.0
58.7
61.9
31.4
46.6
61.8
60.1
63.4
33.9
50.2
66.5
61.5
64.8
53.8
68.6
62.5
65.9
57.3
69.8
63.6
67.0
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
87.3
79.0
70.7
64.2
89.5
81.0
72.5
65.8
68.5
91.6
82.9
74.3
67.4
70.1
93.8
84.9
76.0
68.9
71.8
86.6
77.6
70.3
73.2
88.3
79.1
71.7
74.7
8.6
8.4
8.1
8.0
8.6
8.4
8.2
8.1
8.0
8.7
8.5
8.3
8.1
8.1
8.7
8.5
8.3
8.2
8.2
8.6
8.4
8.2
8.2
8.6
8.4
8.2
8.2
35.4
50.6
65.8
64.2
41.6
55.4
69.2
65.8
68.5
47.9
60.2
72.6
67.4
70.1
54.1
65.1
76.0
68.9
71.8
70.1
77.6
70.3
73.2
75.2
79.1
71.7
74.7
22.1
34.8
47.5
55.5
24.0
37.8
51.6
60.2
60.7
25.8
40.7
55.6
64.9
65.4
27.7
43.7
59.6
69.6
70.2
46.7
63.8
70.7
72.4
49.7
67.9
71.7
74.7
-
-
-
78.6
70.8
62.9
57.4
80.6
72.5
64.5
58.7
61.9
82.5
74.2
66.0
60.1
63.4
84.4
75.9
67.5
61.5
64.8
77.2
68.6
62.5
65.9
78.5
69.8
63.6
67.0
9.2
8.9
8.6
8.5
9.3
9.0
8.7
8.5
8.5
9.3
9.1
8.8
8.6
8.6
9.4
9.1
8.9
8.7
8.7
9.2
8.9
8.7
8.7
9.2
8.9
8.8
8.8
31.6
47.3
62.9
57.4
39.1
51.8
64.5
58.7
61.9
46.5
56.2
66.0
60.1
63.4
53.9
60.7
67.5
61.5
64.8
65.2
68.6
62.5
65.9
69.8
69.8
63.6
67.0
18.5
31.4
44.3
50.8
20.1
34.2
48.2
55.3
54.2
21.8
36.9
52.1
59.8
58.6
23.4
39.7
56.0
61.5
63.0
42.3
59.7
62.5
65.0
44.9
63.4
63.6
67.0
-
-
-
26.9
39.6
47.6
-
-
-
23.4
36.3
42.9
-
-
-
31.7
39.7
-
-
28.4
34.9
-
-
31.8
27.0
-
-
28.9
42.7
51.4
51.9
-
-
-
25.4
39.4
46.5
45.4
-
-
-
2250
2625
3000
33.9
42.5
43.0
-
-
30.6
37.7
36.6
-
-
33.7
28.9
34.2
27.7
-
-
30.9
45.8
55.1
55.7
-
-
-
27.3
42.5
50.2
48.9
-
-
-
36.0
45.4
45.9
-
-
32.8
40.5
39.3
-
-
35.6
30.9
36.1
29.6
-
-
32.9
48.9
58.9
59.5
35.0
52.0
59.0
60.7
37.0
55.2
59.0
62.0
-
-
-
29.2
45.5
53.8
52.5
30.9
48.3
52.5
53.5
32.5
51.0
51.2
54.6
-
-
-
38.2
48.2
48.7
-
35.0
43.3
42.0
-
37.5
38.0
-
32.8
31.5
-
40.3
47.2
49.0
-
-
36.8
41.0
42.1
-
-
3375
3750
35.5
37.3
-
29.6
30.6
-
42.4
46.3
49.3
-
38.6
38.7
42.2
-
33.6
36.5
26.3
29.8
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
20
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF102 (8.5 Ton)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
WB
CFM
2
(°F)
90
85
75°F
45.9
61.3
76.7
80
75
70
65
90
85
85°F
43.2
57.8
72.5
88.9
48.3
64.6
80.8
94.8
98.0
53.5
71.3
80
75
70
65
77
137.6
125.2
112.8
103.0
142.9
130.1
117.2
107.0
106.1
148.3
134.9
121.6
111.0
110.1
153.7
139.8
126.0
115.0
114.1
144.9
130.5
119.2
118.2
149.9
135.1
123.4
122.4
6.9
6.9
6.8
6.7
7.0
6.9
6.9
6.8
6.7
7.1
7.0
6.9
6.8
6.8
7.1
7.1
7.0
6.9
6.8
7.1
7.0
6.9
6.8
7.1
7.0
6.9
6.8
55.6
71.0
86.3
36.2
51.6
67.0
79.1
39.9
56.8
73.8
87.1
-
-
-
126.6
115.4
104.3
95.3
7.7
7.5
7.4
7.3
7.7
7.6
7.5
7.3
7.3
7.8
7.7
7.6
7.4
7.4
7.9
7.8
7.6
7.5
7.5
7.8
7.7
7.5
7.5
7.8
7.7
7.5
7.5
52.6
67.3
81.9
95.3
59.3
75.5
91.7
99.1
99.1
66.0
83.8
33.7
48.4
63.1
75.7
37.4
53.6
69.8
83.9
87.1
41.0
58.8
76.6
-
-
-
72
41.9
57.3
69.4
-
-
-
39.0
53.6
66.3
-
-
-
2125
67
47.6
59.7
-
-
44.2
56.9
-
-
62
77
72
103.0 90.1
50.0
47.5
62.1
79.1
96.0
51.0
67.9
84.9
-
131.6
120.0
108.4
99.1
-
45.7
62.7
76.0
82.6
-
-
-
42.6
58.9
72.9
76.1
-
-
-
2550
2975
3400
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
51.6
64.9
71.5
-
-
47.9
61.9
65.1
-
-
107.0 98.4
53.8
51.0
106.1 104.8 93.7
60.4
99.1
54.2
68.6
87.1
56.1
74.6
43.6
62.1
80.6
-
136.7
124.6
112.6
102.9
102.9
141.7
129.2
116.7
106.7
106.7
131.5
118.8
108.6
108.6
133.8
120.8
110.5
110.4
-
49.6
68.0
82.5
-
-
46.3
64.1
79.5
83.0
-
-
-
105.6 93.1
55.5
70.0
77.3
-
-
101.6 89.1
51.6
67.0
70.5
-
-
111.0 106.7 95.1
57.5
102.9 100.8 92.0
102.9 102.3 95.5
54.5
110.1 109.4 102.4 89.8
64.8
58.0
75.1
95.2
61.2
81.3
47.3
67.3
-
-
72.6
92.0
58.6
78.0
44.6
64.0
83.4
-
53.4
73.4
-
-
-
50.0
69.3
-
-
-
115.3 101.3 87.4
59.5
75.2
83.1
-
111.4 97.4
55.3
72.1
75.9
-
115.0 115.0 103.1 89.1
114.1 114.1 111.0 97.1
61.2
69.2
-
106.7 106.7 100.1 86.1
106.7 106.7 103.9 89.9
58.1
61.9
-
101.8 86.7
71.5
56.4
77.7
98.5
83.2
68.0
52.7
73.3
125.2 108.0 92.9
62.6
83.0
-
116.1 103.8 88.6
58.1
74.8
76.7
-
-
3825
4250
119.2 119.2 113.2 98.1
67.9
71.4
-
108.6 108.6 105.3 90.1
108.6 108.6 107.2 91.9
59.6
61.5
-
118.2 118.2 116.7 101.6 86.5
108.3 92.0
75.8
59.5
82.1
-
104.9 88.5
72.0
55.5
77.3
135.1 114.6 98.3
65.8
-
120.8 110.3 93.8
60.9
77.6
77.5
-
123.4 123.4 123.4 107.1 90.8
122.4 122.4 122.4 106.2 89.9
95°F
74.6
73.6
110.5 110.5 110.5 94.0
110.4 110.4 110.4 94.0
105°F
61.1
61.1
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
115.6
105.6
95.7
8.4
8.2
8.1
7.9
8.4
8.3
8.1
7.9
8.0
8.5
8.4
8.2
8.0
8.0
8.6
8.4
8.3
8.1
8.1
8.5
8.3
8.1
8.1
8.5
8.3
8.1
8.2
49.6
63.6
77.5
87.6
56.4
72.0
87.5
91.2
92.0
63.3
80.4
97.5
94.8
95.7
70.1
88.8
40.4
54.4
68.3
87.6
45.6
61.2
76.7
91.2
91.2
50.8
67.9
85.1
94.8
95.2
56.0
74.7
31.2
45.2
59.1
72.4
34.8
50.3
65.9
80.7
80.4
38.4
55.5
72.6
88.9
88.6
41.9
60.6
79.4
97.2
96.8
64.4
84.3
97.4
97.6
68.2
-
-
-
106.8
97.2
87.5
81.4
110.8
100.8
90.7
84.4
85.1
114.8
104.4
94.0
87.4
88.2
118.8
108.0
97.2
90.5
91.2
106.7
96.1
89.4
90.1
105.4
94.9
88.3
89.0
9.1
8.8
8.6
8.4
9.2
8.9
8.7
8.5
8.5
9.3
9.0
8.8
8.6
8.6
9.3
9.1
8.9
8.7
8.7
9.2
8.9
8.7
8.8
9.2
9.0
8.8
8.8
44.1
60.7
77.2
81.4
53.5
68.7
83.9
84.4
85.1
62.9
76.7
90.6
87.4
88.2
72.3
84.8
97.2
90.5
91.2
91.0
96.1
89.4
90.1
97.1
94.9
88.3
89.0
37.9
51.5
65.2
81.4
42.8
58.0
73.1
84.4
84.7
47.6
64.4
81.1
87.4
88.0
52.5
70.8
89.1
90.5
91.2
75.7
91.8
89.4
90.1
80.6
94.6
88.3
89.0
28.7
42.4
56.0
67.5
32.0
47.2
62.4
75.2
74.1
35.3
52.0
68.8
82.9
81.6
38.6
56.9
75.2
90.6
89.2
60.5
79.9
89.4
89.1
64.1
84.7
88.3
89.0
-
-
-
36.0
50.0
63.2
-
-
-
33.2
46.8
58.3
-
-
-
2125
2550
40.8
54.1
-
-
37.7
49.1
-
-
87.6
44.9
40.0
120.3
110.0
99.7
-
-
39.5
55.1
69.8
69.6
-
-
-
36.4
51.6
64.4
63.3
-
-
-
44.3
59.0
58.8
-
-
40.9
53.6
52.5
-
-
91.2
48.2
42.9
92.0
47.9
41.8
125.0
114.3
103.6
94.8
-
-
43.0
60.2
76.5
76.2
-
-
-
39.7
56.4
70.5
69.3
-
-
-
2975
3400
47.7
64.0
63.7
-
-
44.1
58.2
56.9
-
-
51.6
45.8
95.7
51.3
44.6
129.8
118.6
107.5
98.4
-
-
46.5
65.3
83.1
82.7
49.0
68.9
82.0
82.3
51.5
72.6
80.9
81.8
-
-
-
42.9
61.2
76.6
75.3
45.2
64.7
74.2
73.9
47.5
68.2
71.7
72.5
-
-
-
107.5 93.4
51.2
69.0
68.6
-
47.3
62.7
61.3
-
98.4
99.3
95.2
98.4
99.3
79.8
54.9
54.6
-
48.7
47.4
-
99.3
118.1
107.1
98.0
107.1 99.7
53.6
66.6
66.9
-
-
49.5
58.9
58.6
-
-
3825
4250
98.0
98.9
98.0
98.9
51.3
51.5
-
43.7
43.4
-
98.9
117.7
106.6
97.6
101.5 84.9
106.6 105.9 89.2
55.9
64.3
65.1
-
51.6
55.2
56.0
-
97.6
98.5
97.6
98.5
97.6
98.5
47.6
48.5
38.7
39.4
98.5
Johnson Controls Unitary Products
21
528194-YTG-F-1210
ZF102 (8.5 Ton) (Continued)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
1
WB
(°F)
CFM
2125
2
2
90
85
115°F
35.3
48.7
62.0
75.1
39.9
54.7
69.6
77.6
78.2
44.5
60.8
77.2
80.0
80.7
49.0
66.9
84.8
82.5
83.2
71.6
84.0
80.7
81.4
76.3
83.2
78.9
79.6
80
75
70
65
90
85
125°F
30.9
45.8
58.8
68.8
37.0
51.5
66.1
70.7
71.3
43.2
57.3
73.3
72.6
73.3
49.3
63.0
76.7
74.5
75.2
67.6
74.1
72.1
72.7
72.1
71.5
69.6
70.2
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
98.1
88.7
79.2
75.1
101.4
91.6
81.8
77.6
78.2
104.6
94.5
84.4
80.0
80.7
107.8
97.4
87.0
82.5
83.2
95.3
85.1
80.7
81.4
93.2
83.2
78.9
79.6
9.8
9.5
9.2
9.0
9.9
9.6
9.3
9.1
9.1
10.0
9.7
9.4
9.2
9.2
10.1
9.8
9.5
9.3
9.3
9.8
9.5
9.3
9.4
9.9
9.6
9.4
9.4
38.6
57.8
77.0
75.1
50.6
65.5
80.3
77.6
78.2
62.6
73.1
83.6
80.0
80.7
74.5
80.8
87.0
82.5
83.2
86.8
85.1
80.7
81.4
92.7
83.2
78.9
79.6
26.2
39.5
52.8
62.5
29.2
44.0
58.9
69.7
67.7
32.2
48.6
64.9
76.8
74.7
35.2
53.1
71.0
84.0
81.6
56.5
75.6
81.5
80.6
59.9
80.2
78.9
79.6
-
-
-
89.4
80.2
70.9
68.8
91.9
82.4
72.9
70.7
71.3
94.4
84.6
74.8
72.6
73.3
96.8
86.8
76.7
74.5
75.2
83.9
74.1
72.1
72.7
81.0
71.5
69.6
70.2
10.5
10.1
9.7
38.9
54.9
70.9
68.8
51.5
62.2
72.9
70.7
71.3
64.1
69.5
74.8
72.6
73.3
76.7
76.7
76.7
74.5
75.2
82.5
74.1
72.1
72.7
81.0
71.5
69.6
70.2
23.7
36.7
49.7
57.6
26.4
40.9
55.4
64.2
61.4
29.1
45.1
61.1
70.8
67.7
31.8
49.3
66.8
74.5
74.1
52.6
71.2
72.1
72.1
55.8
71.5
69.6
70.2
-
-
-
30.4
43.7
53.4
-
-
-
27.6
40.6
48.4
-
-
-
34.6
44.2
-
-
31.4
39.3
-
-
35.1
9.6
30.2
-
10.6
10.2
9.8
-
33.3
48.2
59.0
57.0
-
-
-
30.2
44.8
53.5
50.7
-
-
-
2550
2975
3400
37.5
48.3
46.3
-
-
34.1
42.9
40.1
-
-
37.6
9.7
32.2
35.6
9.7
29.4
-
10.7
10.3
9.9
-
36.3
52.7
64.6
62.4
-
-
-
32.9
48.9
58.6
55.6
-
-
-
40.4
52.3
50.2
-
-
36.8
46.4
43.4
-
-
40.0
9.8
34.3
37.9
9.8
31.2
-
10.8
10.4
10.1
9.9
-
39.3
57.2
70.2
67.8
41.4
60.5
66.3
65.5
43.5
63.8
62.5
63.2
-
-
-
35.6
53.1
63.7
60.4
37.6
56.2
58.5
57.1
39.6
59.3
53.3
53.9
-
-
-
43.3
56.3
54.0
-
39.4
50.0
46.7
-
42.5
40.2
-
36.3
33.0
-
9.9
10.5
10.1
10.0
10.0
10.6
10.2
10.0
10.1
45.3
51.2
50.4
-
-
41.2
43.5
42.1
-
-
3825
4250
36.1
35.3
-
28.5
27.2
-
47.4
46.1
46.8
-
43.1
37.0
37.6
-
29.7
30.4
20.8
21.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
22
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF120 (10 Ton)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
WB
CFM
2
(°F)
90
85
75°F
56.3
72.9
80
75
70
65
90
85
85°F
51.8
68.3
84.8
80
75
70
65
77
165.2
149.2
133.2
121.8
170.9
154.3
137.7
125.9
120.2
176.6
159.4
142.3
130.1
124.2
182.2
164.5
146.8
134.3
128.2
168.0
149.9
137.1
130.9
171.4
153.0
139.9
133.5
7.4
7.5
7.5
7.5
7.4
7.4
7.4
7.5
7.4
7.4
7.4
7.4
7.5
7.4
7.3
7.4
7.4
7.4
7.4
7.4
7.4
7.4
7.4
7.4
7.4
7.5
7.4
67.4
84.0
45.3
61.8
78.4
-
-
-
153.8
138.9
124.0
112.8
159.0
143.5
128.1
116.5
112.6
164.1
148.2
132.3
120.3
116.3
169.2
152.8
136.4
124.1
119.9
155.6
138.9
126.3
122.1
158.4
141.4
128.6
124.3
8.3
8.3
8.2
8.2
8.3
8.3
8.2
8.2
8.2
8.3
8.3
8.2
8.2
8.2
8.3
8.3
8.2
8.2
8.2
8.3
8.3
8.2
8.2
8.3
8.3
8.2
8.2
62.7
79.2
95.7
40.9
57.4
73.9
-
-
-
72
50.8
67.3
82.0
-
-
-
46.5
63.0
77.1
-
-
-
2500
67
100.5 89.4
56.3
70.9
-
-
52.1
66.2
-
-
62
77
72
121.8 105.9 93.0
59.8
112.8 103.2 88.0
55.3
76.4
94.5
63.0
81.2
49.7
67.8
86.0
-
71.2
89.4
58.2
76.4
45.2
63.4
81.6
-
54.5
72.7
-
-
50.4
68.5
84.1
-
-
3000
3500
4000
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
112.6 99.3
59.3
75.4
83.0
-
-
107.6 94.6
55.5
71.1
75.8
-
-
125.9 115.4 102.0 88.7
120.2 120.2 109.7 96.3
62.1
116.5 110.1 97.1
58.0
69.7
112.6 112.6 101.9 88.9
62.8
85.3
69.7
54.1
73.9
-
-
79.7
99.6
64.6
84.5
49.4
69.3
-
-
105.0 89.5
58.3
78.0
-
-
54.2
74.1
-
-
124.8 109.2 93.6
62.4
79.9
-
119.5 104.3 89.2
58.9
75.9
81.1
-
-
130.1 124.8 111.1 95.5
64.3
120.3 117.1 106.2 91.1
116.3 116.3 111.4 96.3
60.8
124.2 124.2 119.4 103.8 88.2
72.6
66.0
94.3
76.4
58.6
79.9
-
-
-
-
88.2
70.9
53.7
75.3
-
-
115.6 97.7
62.0
-
-
109.8 92.5
58.0
79.6
-
-
-
136.9 119.1 101.2 83.3
65.5
131.4 114.1 96.9
62.3
80.8
134.3 134.3 120.1 102.2 84.4
128.2 128.2 129.1 111.3 93.4
66.5
75.5
-
124.1 124.1 115.3 98.0
63.5
69.2
-
119.9 119.9 121.0 103.7 86.4
124.0 104.8 85.6
66.4
-
117.7 99.1
80.5
61.8
-
144.9 127.7 108.5 89.2
70.0
-
136.4 122.2 103.5 84.9
66.3
-
4500
5000
137.1 137.1 130.0 110.8 91.5
130.9 130.9 131.3 112.1 92.9
72.3
73.7
-
126.3 126.3 122.0 103.3 84.7
122.1 122.1 122.6 104.0 85.4
66.0
66.7
-
132.5 111.9 91.3
70.7
-
125.7 105.7 85.7
65.6
-
153.0 136.3 115.7 95.1
74.5
-
141.4 130.2 110.2 90.2
70.2
-
139.9 139.9 139.9 119.3 98.7
133.5 133.5 133.5 113.0 92.4
95°F
78.1
71.8
128.6 128.6 128.6 108.6 88.6
124.3 124.3 124.3 104.3 84.3
105°F
68.6
64.2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
142.4
128.6
114.8
103.8
147.0
132.8
118.6
107.1
105.0
151.6
137.0
122.3
110.5
108.3
156.2
141.1
126.0
113.9
111.6
143.3
127.9
115.6
113.3
145.5
129.9
117.4
115.1
9.2
9.1
9.0
8.8
9.2
9.1
9.0
8.9
8.9
9.3
9.2
9.1
8.9
8.9
9.3
9.2
9.1
8.9
8.9
9.2
9.1
9.0
9.0
9.2
9.1
9.0
9.0
58.1
74.5
90.9
47.3
63.7
80.2
36.6
53.0
69.4
-
-
-
129.8
117.4
104.9
94.6
10.2
9.9
56.2
74.6
93.0
94.6
65.1
82.5
45.6
63.8
82.1
92.9
50.3
69.8
34.9
53.1
71.4
82.3
37.6
57.1
76.7
89.9
91.0
40.3
61.2
82.0
97.4
-
-
-
42.3
58.7
72.3
-
-
-
42.4
60.6
71.6
-
-
-
2500
3000
48.0
61.5
-
-
9.7
49.9
60.8
-
-
103.8 100.4 83.0
50.8
9.5
50.1
66.1
84.3
53.4
71.6
40.7
58.9
77.1
-
133.5
120.8
108.0
97.3
10.2
10.0
9.8
-
46.2
64.4
79.5
81.4
-
-
-
44.5
64.0
77.2
78.3
-
-
-
102.5 89.8
51.7
66.7
68.7
-
-
100.0 89.4
51.3
64.5
65.6
-
-
107.1 104.9 92.2
105.0 105.0 94.1
54.0
9.5
97.3
97.9
74.0
90.5
96.2
97.9
54.9
75.8
51.8
56.0
97.9
9.6
52.9
74.1
94.2
59.4
79.5
44.7
64.8
84.8
-
137.3
124.1
111.0
100.1
100.6
141.0
127.5
114.0
102.8
103.4
129.6
115.9
104.5
105.1
131.7
117.7
106.2
106.8
10.3
10.1
9.8
-
50.1
70.1
-
-
46.5
67.4
82.8
82.7
-
-
-
3500
4000
114.2 99.5
55.4
72.0
74.1
-
-
106.9 96.7
100.1 99.5
52.7
68.1
68.1
-
-
110.5 109.4 101.4 86.7
108.3 108.3 103.5 88.8
57.3
9.6
53.5
59.4
9.7
100.6 100.6 97.4
53.4
82.1
65.4
48.8
70.6
-
-
10.4
10.1
9.9
82.9
98.4
59.6
81.8
43.0
65.2
-
104.0 87.3
54.0
75.8
-
-
-
48.6
70.8
-
-
-
125.9 109.2 92.5
59.1
77.2
79.5
-
113.9 104.0 87.4
54.2
71.8
70.6
-
113.9 113.9 110.5 93.9
111.6 111.6 112.9 96.2
60.5
62.8
-
9.7
102.8 102.8 105.0 88.4
103.4 103.4 103.8 87.2
55.2
54.0
-
9.7
111.4 93.4
75.3
57.2
80.6
10.2
9.9
105.3 87.4
69.5
51.5
75.2
127.9 116.7 98.6
62.5
77.8
77.8
-
-
115.8 109.5 93.1
57.2
69.7
69.4
-
-
4500
5000
115.6 115.6 114.0 95.9
113.3 113.3 114.0 95.9
59.7
59.7
-
9.7
104.5 104.5 105.6 87.6
105.1 105.1 105.3 87.4
51.8
51.5
-
9.7
118.9 99.4
80.0
60.5
10.2
9.9
112.2 93.0
73.7
54.5
79.5
129.9 124.2 104.8 85.3
117.4 117.4 117.4 97.9
115.1 115.1 115.1 95.6
65.8
78.4
76.1
-
117.7 114.9 98.8
60.3
67.6
68.3
-
59.0
56.7
9.7
106.2 106.2 106.2 86.9
106.8 106.8 106.8 87.5
48.4
49.0
9.8
Johnson Controls Unitary Products
23
528194-YTG-F-1210
ZF120 (10 Ton) (Continued)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
1
WB
(°F)
CFM
2500
2
2
90
85
115°F
43.9
63.9
84.0
85.5
47.2
68.1
88.9
87.5
90.8
50.5
72.2
93.9
89.6
93.0
53.8
76.3
80
75
70
65
90
85
125°F
42.9
64.0
85.2
76.3
45.8
66.3
86.8
77.7
83.7
48.7
68.6
88.4
79.2
85.3
51.6
70.8
90.0
80.6
86.9
75.4
91.7
82.2
88.5
80.0
93.5
83.7
90.2
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
117.2
106.1
95.0
11.2
10.8
10.4
10.1
11.2
10.9
10.5
10.2
10.3
11.3
10.9
10.6
10.3
10.4
11.4
11.0
10.6
10.4
10.5
11.1
10.7
10.4
10.5
11.1
10.7
10.5
10.6
54.3
74.7
95.0
85.5
64.1
80.7
97.4
87.5
90.8
73.9
86.8
99.7
89.6
93.0
83.7
92.9
33.2
53.2
73.3
81.6
34.5
55.4
76.3
87.5
87.8
35.9
57.6
79.3
93.5
91.3
37.2
59.8
82.3
99.5
94.7
63.6
-
-
-
104.6
94.9
85.2
76.3
106.6
96.7
86.8
77.7
83.7
108.6
98.5
88.4
79.2
85.3
110.6
100.3
90.0
80.6
86.9
102.2
91.7
82.2
88.5
104.2
93.5
83.7
90.2
12.1
11.6
11.1
10.8
12.3
11.7
11.2
10.9
11.0
12.4
11.8
11.3
11.0
11.1
12.5
11.9
11.4
11.1
11.2
12.0
11.5
11.1
11.3
12.1
11.5
11.2
11.3
64.4
74.8
85.2
76.3
71.1
78.9
86.8
77.7
83.7
77.9
83.1
88.4
79.2
85.3
84.6
87.3
90.0
80.6
86.9
93.1
91.7
82.2
88.5
98.9
93.5
83.7
90.2
31.5
53.3
75.2
76.3
31.5
53.7
75.9
77.7
83.7
31.5
54.0
76.5
79.2
85.2
31.5
54.3
77.2
80.6
85.7
57.7
82.0
82.2
87.9
61.2
86.9
83.7
90.2
-
-
-
42.5
62.6
70.9
-
-
-
42.6
64.5
70.2
-
-
-
51.8
60.1
-
-
53.8
59.4
-
-
85.5
49.4
48.7
120.1
108.7
97.4
-
-
42.7
63.6
74.9
75.2
-
-
-
41.0
63.2
72.6
72.1
-
-
-
3000
3500
4000
51.0
62.2
62.5
-
-
50.6
60.0
59.4
-
-
87.5
49.6
47.3
90.8
49.8
46.8
122.9
111.3
99.7
-
-
43.0
64.7
78.9
76.7
-
-
-
39.4
62.0
75.0
70.6
-
-
-
50.1
64.3
62.1
-
-
47.4
60.5
56.1
-
-
89.6
49.7
45.9
93.0
47.5
41.5
125.8
113.9
102.0
91.7
-
-
43.2
65.7
82.9
78.2
45.8
69.8
79.4
78.8
48.4
73.8
75.9
79.4
-
-
-
37.8
60.7
77.4
69.2
40.1
64.4
71.2
70.3
42.3
68.0
64.9
71.4
-
-
-
102.0 98.8
49.2
66.4
61.6
-
44.2
61.0
52.7
-
91.7
95.1
99.2
91.7
95.1
81.4
49.8
45.1
-
44.5
36.2
-
95.1
115.9
103.8
93.3
103.8 102.2 87.6
52.0
61.6
61.0
-
-
46.7
53.5
52.6
-
-
4500
5000
93.3
96.8
93.3
96.8
97.2
96.6
67.4
43.8
43.2
-
35.8
34.9
-
96.8
117.9
105.6
95.0
105.5 86.5
105.6 105.6 92.8
54.7
56.8
60.4
-
49.2
46.0
52.5
-
95.0
98.5
95.0
98.5
95.0
98.5
37.8
41.3
27.2
33.7
98.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
24
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF150 (12.5 Ton)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
WB
(°F)
CFM
3125
2
90
85
75°F
62.8
86.4
80
75
70
65
90
85
85°F
60.7
83.5
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
192.8
179.7
166.6
150.6
200.7
187.1
173.4
156.8
152.3
208.7
194.5
180.2
163.0
158.3
216.6
201.8
187.1
169.2
164.3
203.6
188.7
170.7
165.7
205.4
190.4
172.2
167.2
10.1
9.8
9.6
9.5
10.1
9.9
9.6
9.5
9.5
10.1
9.9
9.7
9.6
9.5
10.1
9.9
9.7
9.6
9.6
9.9
9.7
9.6
9.6
10.0
9.8
9.7
9.7
75.6
99.3
49.9
73.5
-
-
-
-
185.3
171.3
157.2
142.2
192.2
177.6
163.0
147.5
144.4
199.1
184.0
168.9
152.8
149.5
206.0
190.3
174.7
158.1
154.7
193.2
177.3
160.4
157.0
196.0
179.9
162.8
159.3
11.1
10.9
10.7
10.6
11.1
10.9
10.8
10.6
10.6
11.2
11.0
10.8
10.7
10.6
11.2
11.0
10.8
10.7
10.7
11.1
10.9
10.8
10.7
11.1
10.9
10.8
10.8
73.4
96.2
48.0
70.8
-
-
-
-
60.6
84.3
-
58.1
80.9
-
122.9 110.0 97.1
71.4
-
119.1 106.4 93.6
68.2
-
150.6 133.0 119.1 106.2 93.3
80.4
142.2 132.0 115.5 102.8 90.1
77.4
83.8
69.2
54.6
80.5
-
-
-
-
-
-
81.3
66.8
52.4
77.4
-
-
-
-
109.7 95.1
66.0
106.2 91.8
63.0
-
-
3750
4375
5000
135.6 121.0 106.5 91.9
77.3
131.2 116.8 102.4 88.0
73.5
156.8 145.1 130.5 115.9 101.3 86.7
152.3 152.3 138.3 123.7 109.1 94.5
147.5 140.7 126.3 111.9 97.4
83.0
144.4 144.4 132.5 118.1 103.7 89.3
92.0
75.7
59.4
-
-
-
-
-
-
89.2
73.0
56.9
-
-
-
-
-
-
120.2 103.9 87.6
71.3
116.3 100.1 84.0
67.9
148.3 132.1 115.8 99.5
83.2
143.4 127.2 111.1 95.0
78.8
163.0 157.1 141.9 125.6 109.3 93.0
158.3 158.3 150.4 134.1 117.8 101.5
152.8 149.4 137.0 120.9 104.8 88.6
149.5 149.5 143.9 127.7 111.6 95.4
100.2 82.2
64.2
-
-
-
-
-
-
97.1
79.2
61.4
-
-
-
-
-
-
130.6 112.6 94.6
76.7
126.3 108.5 90.6
72.8
161.1 143.1 125.1 107.1 89.1
155.5 137.7 119.8 102.0 84.1
169.2 169.2 153.3 135.3 117.3 99.3
164.3 164.3 162.5 144.5 126.5 108.5
158.1 158.1 147.8 130.0 112.1 94.3
154.7 154.7 155.2 137.3 119.5 101.6
138.4 119.4 100.5 81.5
-
-
-
134.4 115.4 96.4
77.5
-
-
-
171.4 151.7 132.8 113.8 94.8
165.5 146.5 127.6 108.6 89.6
5625
6250
170.7 170.7 162.7 143.8 124.8 105.8
165.7 165.7 164.8 145.8 126.9 107.9
160.4 160.4 155.3 136.3 117.3 98.3
157.0 157.0 157.2 138.2 119.2 100.3
146.2 126.2 106.3 86.3
-
-
-
142.5 122.4 102.3 82.1
-
-
-
181.6 160.4 140.4 120.5 100.5
175.5 155.4 135.3 115.1 95.0
172.2 172.2 172.2 152.2 132.2 112.3
167.2 167.2 167.2 147.2 127.2 107.3
95°F
162.8 162.8 162.8 142.7 122.5 102.4
159.3 159.3 159.3 139.2 119.0 98.9
105°F
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
177.9
162.8
147.8
133.8
183.7
168.2
152.6
138.2
136.4
189.6
173.5
157.5
142.6
140.7
195.4
178.9
162.3
147.0
145.1
182.7
165.9
150.2
148.2
186.6
169.4
153.4
151.4
12.1
12.0
11.8
11.7
12.2
12.0
11.9
11.7
11.7
12.2
12.1
11.9
11.8
11.8
12.3
12.1
12.0
11.8
11.8
12.2
12.0
11.9
11.8
12.2
12.0
11.9
11.9
71.1
93.2
58.6
80.6
46.0
68.1
-
-
-
165.4
151.1
136.8
125.4
170.9
156.1
141.4
129.6
127.8
176.4
161.2
145.9
133.8
131.9
181.9
166.2
150.5
138.0
136.0
169.5
153.5
140.7
138.7
172.8
156.5
143.4
141.4
13.5
13.4
13.3
13.1
13.5
13.4
13.3
13.1
13.1
13.6
13.5
13.3
13.2
13.2
13.6
13.5
13.4
13.2
13.2
13.5
13.4
13.2
13.2
13.5
13.4
13.2
13.2
65.9
88.4
53.7
75.9
41.2
63.4
85.7
-
-
-
55.6
77.6
-
-
51.0
73.2
-
-
3125
3750
115.2 102.7 90.1
65.1
86.9
-
-
111.0 98.2
60.7
81.1
-
-
133.8 131.0 111.9 99.4
74.3
125.4 124.0 106.1 93.6
68.6
78.7
64.5
50.2
74.3
-
-
73.4
97.7
59.2
83.6
45.1
69.4
-
-
102.8 88.5
60.0
84.0
-
-
55.3
79.6
-
-
126.8 112.6 98.3
69.8
-
122.1 107.9 93.8
65.5
-
138.2 136.3 122.1 107.8 93.5
136.4 136.4 126.8 112.5 98.3
79.3
129.6 128.7 116.1 102.0 87.8
127.8 127.8 118.7 104.6 90.4
73.7
84.0
76.3
86.3
70.3
54.4
80.4
-
-
-
-
-
-
80.9
64.8
49.0
75.4
-
-
-
-
112.4 96.4
64.4
107.0 91.2
59.6
-
4375
5000
138.4 122.4 106.5 90.5
74.5
133.2 117.7 101.9 86.1
70.3
-
142.6 141.7 132.2 116.2 100.2 84.2
140.7 140.7 137.3 121.3 105.4 89.4
133.8 133.3 126.2 110.4 94.6
131.9 131.9 129.0 113.2 97.4
78.8
81.6
93.9
76.2
58.5
-
-
-
-
-
-
88.4
70.3
52.9
81.4
-
-
-
-
-
-
122.0 104.3 86.6
68.9
116.3 98.9
64.0
150.0 132.3 114.6 96.9
79.2
144.3 127.5 110.0 92.5
75.1
147.0 147.0 142.3 124.6 106.9 89.2
145.1 145.1 147.8 130.1 112.4 94.7
138.0 138.0 136.2 118.7 101.3 83.8
136.0 136.0 139.2 121.8 104.3 86.9
130.4 111.4 92.4
73.4
-
-
-
124.3 105.6 86.9
68.2
-
-
-
159.7 141.3 122.3 103.4 84.4
150.4 136.1 117.4 98.7
80.0
5625
6250
150.2 150.2 147.9 128.9 109.9 90.9
148.2 148.2 149.6 130.6 111.6 92.6
140.7 140.7 139.8 121.1 102.4 83.7
138.7 138.7 140.3 121.6 102.9 84.2
138.8 118.5 98.3
78.0
-
-
-
132.3 112.4 92.4
72.5
-
-
-
169.4 150.4 130.1 109.8 89.5
156.5 144.8 124.8 104.9 84.9
153.4 153.4 153.4 133.1 112.8 92.5
151.4 151.4 151.4 131.1 110.8 90.5
143.4 143.4 143.4 123.5 103.5 83.6
141.4 141.4 141.4 121.4 101.5 81.5
Johnson Controls Unitary Products
25
528194-YTG-F-1210
ZF150 (12.5 Ton) (Continued)
Temperature of Air on Condenser Coil
Air on
Evaporator Coil
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Sensible Capacity (MBh)
Return Dry Bulb (°F)
Total
Capacity
(MBh)
Total
Input
(kW)
Total
Capacity
(MBh)
Total
Input
(kW)
1
1
WB
(°F)
CFM
3125
2
2
90
85
115°F
48.8
80
75
70
65
90
85
125°F
44.0
80
75
70
65
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
152.8
139.4
125.9
117.0
158.0
144.1
130.1
121.0
119.1
163.2
148.8
134.4
125.0
123.0
168.3
153.5
138.7
128.9
126.9
156.2
141.1
131.2
129.2
158.9
143.6
133.5
131.4
14.9
14.8
14.7
14.5
14.9
14.8
14.7
14.5
14.6
14.9
14.8
14.7
14.6
14.6
15.0
14.9
14.8
14.6
14.6
14.9
14.8
14.6
14.6
14.9
14.8
14.6
14.6
60.7
83.7
36.4
58.8
81.2
-
-
-
-
140.3
127.6
114.9
108.6
145.1
132.0
118.9
112.4
110.5
150.0
136.4
122.9
116.1
114.2
154.8
140.8
126.8
119.9
117.9
143.0
128.7
121.7
119.6
145.1
130.6
123.5
121.4
16.2
16.2
16.1
15.9
16.3
16.2
16.1
15.9
16.0
16.3
16.2
16.1
15.9
16.0
16.3
16.3
16.2
16.0
16.0
16.2
16.2
16.0
16.0
16.2
16.2
16.0
16.0
52.4
79.0
31.5
54.2
76.8
-
-
-
-
71.3
46.3
68.8
-
66.6
41.7
64.4
82.0
-
-
106.7 93.7
56.3
75.4
-
-
102.4 89.2
51.9
69.6
-
-
117.0 117.0 100.3 87.8
62.9
108.6 108.6 94.4
57.2
68.1
92.7
54.0
78.7
40.0
64.6
-
-
62.7
87.7
48.8
73.8
34.9
59.8
84.8
-
50.6
75.2
-
-
45.9
70.8
-
-
3750
4375
5000
117.4 103.3 89.3
61.2
82.1
82.6
-
-
112.6 98.7
56.9
76.4
74.7
-
-
121.0 121.0 110.2 96.2
119.1 119.1 110.7 96.6
68.1
112.4 112.4 104.3 90.3
110.5 110.5 102.6 88.6
62.5
68.5
60.8
75.4
59.2
43.6
70.5
-
-
73.0
96.4
53.7
80.9
38.2
65.5
-
-
101.7 86.1
54.8
81.7
-
-
50.0
77.3
-
-
128.0 113.0 97.3
66.1
-
122.8 108.2 92.8
61.9
83.2
81.4
-
-
125.0 125.0 120.1 104.5 88.9
123.0 123.0 120.6 105.0 89.4
73.3
116.1 116.1 114.1 98.7
114.2 114.2 112.3 96.8
67.8
73.8
66.0
82.8
64.4
47.2
76.3
-
-
-
-
83.3
58.5
41.5
71.2
-
-
110.7 93.5
59.1
-
-
105.1 88.1
54.2
-
-
-
138.7 122.6 105.4 88.2
71.0
126.8 117.7 100.8 83.8
66.8
128.9 128.9 130.1 112.9 95.7
126.9 126.9 130.6 113.4 96.2
78.4
79.0
-
119.9 119.9 119.9 107.0 90.0
117.9 117.9 117.9 105.0 88.1
73.1
71.1
-
118.3 99.9
81.4
63.0
-
112.2 94.1
75.9
57.8
-
141.1 130.9 112.5 94.1
75.6
-
128.7 125.7 107.6 89.4
71.3
-
5625
6250
131.2 131.2 131.8 113.3 94.9
129.2 129.2 131.0 112.6 94.2
76.5
75.7
-
121.7 121.7 121.7 105.6 87.5
119.6 119.6 119.6 103.6 85.4
69.3
67.3
-
125.8 106.2 86.6
66.9
-
119.4 100.0 80.7
61.4
-
143.6 139.2 119.6 99.9
80.3
-
130.6 130.6 114.3 95.0
75.7
-
133.5 133.5 133.5 113.8 94.2
131.4 131.4 131.4 111.8 92.1
74.6
72.5
123.5 123.5 123.5 104.2 84.9
121.4 121.4 121.4 102.1 82.8
65.6
63.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
26
Johnson Controls Unitary Products
528194-YTG-F-1210
Airflow Performance
ZF078-150 Side Duct Application
ZF078 (6.5 Ton) Side Duct
Air Flow
Available External Static Pressure - IWG1
0.8 1.0 1.2 1.4
0.2
0.4
0.6
1.6
1.8
2.0
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 1.5 HP & Drive
Hi Static 2 HP & Drive
1800
2000
2200
2400
2600
2800
3000
3200
3400
751
776
804
835
869
906
945
987
0.22
0.35
0.50
0.66
0.84
1.03
813
838
866
897
931
968
0.43
0.56
0.71
0.87
1.05
872
897
925
956
990
0.62
0.75
0.90
929
954
982
0.78
985 0.93 1040 1.07 1095 1.20 1150 1.33 1206 1.46 1265 1.59
0.92 1010 1.07 1064 1.20 1119 1.33 1175 1.46 1231 1.59 1289 1.72
1.06 1038 1.21 1092 1.35 1147 1.48 1203 1.61 1259 1.73 1317 1.87
1.06 1013 1.22 1069 1.37 1124 1.51 1178 1.64 1234 1.77 1290 1.90 1348 2.03
1.24 1047 1.40 1103 1.55 1158 1.69 1212 1.82 1268 1.95 1324 2.07 1382 2.21
1.25 1027 1.43 1084 1.60 1139 1.75 1194 1.89 1249 2.02 1304 2.14 1361 2.27
-
-
-
-
-
-
-
-
1.25 1007 1.46 1066 1.65 1123 1.81 1179 1.96 1234 2.10 1288 2.23
-
-
-
-
-
-
-
-
-
-
-
-
1.48 1048 1.69 1107 1.88 1165 2.04 1220 2.19
-
-
-
-
-
-
-
-
1030 1.73 1092 1.94 1151 2.12 1208 2.29
-
-
2 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZF090 (7.5 Ton) Side Duct
Available External Static Pressure - IWG1
Air Flow
(CFM)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 1.5 HP & Drive
Hi Static 3 HP & Drive
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
776
804
835
869
906
945
987
0.35
0.50
0.66
0.84
1.03
838
866
897
931
968
0.56
0.71
0.87
1.05
897
925
956
990
0.75
0.90
954
982
0.92 1010 1.07 1064 1.20 1119 1.33 1175 1.46 1231 1.59 1289 1.72
1.06 1038 1.21 1092 1.35 1147 1.48 1203 1.61 1259 1.73 1317 1.87
1.06 1013 1.22 1069 1.37 1124 1.51 1178 1.64 1234 1.77 1290 1.90 1348 2.03
1.24 1047 1.40 1103 1.55 1158 1.69 1212 1.82 1268 1.95 1324 2.07 1382 2.21
1.25 1027 1.43 1084 1.60 1139 1.75 1194 1.89 1249 2.02 1304 2.14 1361 2.27 1419 2.40
1.25 1007 1.46 1066 1.65 1123 1.81 1179 1.96 1234 2.10 1288 2.23 1344 2.36 1400 2.48 1458 2.62
1.48 1048 1.69 1107 1.88 1165 2.04 1220 2.19 1275 2.33 1330 2.46 1385 2.59 1442 2.71 1500 2.85
1030 1.73 1092 1.94 1151 2.12 1208 2.29 1264 2.44 1319 2.58 1374 2.71 1429 2.84 1485 2.96 1544 3.10
1076 1.99 1138 2.20 1197 2.39 1254 2.56 1310 2.71 1364 2.84 1419 2.97 1475 3.10 1531 3.23 1589 3.36
1124 2.27 1185 2.48 1245 2.67 1302 2.84 1357 2.99 1412 3.12 1467 3.25 1522 3.38
-
-
-
-
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZF102 (8.5 Ton) Side Duct
Available External Static Pressure - IWG1
Air Flow
(CFM)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
980 1.80 1025 2.05 1068 2.35
2600
2800
3000
3200
3400
3600
3800
4000
4200
628
648
666
684
702
721
742
765
789
0.56
0.67
0.80
0.95
1.11
1.28
1.47
1.67
1.87
678
698
717
735
753
772
793
815
840
0.76
0.87
1.00
1.15
1.31
1.48
1.67
1.86
2.07
730
750
768
786
804
824
844
867
891
0.93
1.04
1.17
1.32
1.48
1.65
1.84
2.04
2.24
781
801
820
838
856
875
896
918
943
1.09
1.20
1.33
1.48
1.64
1.81
2.00
2.19
2.40
833
853
871
889
907
927
947
970
995
1.25
1.36
1.49
1.63
1.79
1.97
2.15
883
903
922
940
958
977
998
1.41
1.52
1.65
1.80
933
953
971
989
1.59
1.70 1000 1.91 1046 2.16 1088 2.46
1.83 1019 2.04 1064 2.29 1106 2.59
1.98 1037 2.19 1082 2.44 1124 2.74
1.96 1007 2.14 1055 2.35 1100 2.60 1142 2.90
2.13 1027 2.31 1074 2.52 1119 2.77
2.32 1047 2.50 1095 2.71 1140 2.96
-
-
-
-
-
-
-
-
2.35 1020 2.51 1070 2.70 1117 2.91
2.56 1045 2.72 1094 2.90
-
-
-
-
-
-
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
27
528194-YTG-F-1210
ZF120 (10 Ton) Side Duct
Air Flow
Available External Static Pressure - IWG1
0.8 1.0 1.2 1.4
0.2
0.4
0.6
1.6
1.8
2.0
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
675
686
699
713
728
745
763
783
805
828
852
879
906
0.53
0.63
0.75
0.88
1.02
1.18
1.36
1.55
1.77
2.00
2.25
2.52
2.81
726
738
750
764
779
796
815
835
856
879
904
930
958
0.74
0.84
0.96
1.09
1.23
1.39
1.57
1.76
1.98
2.21
2.46
2.73
776
787
800
814
829
846
864
884
906
929
953
980
0.94
1.04
1.16
1.28
1.43
1.59
1.76
1.96
2.17
2.41
824
835
847
861
877
893
912
932
953
976
1.12
1.23
1.34
1.47
1.61
1.77
1.95
2.15
2.36
870
881
893
907
923
939
958
978
999
1.30
1.41
1.52
1.65
1.79
1.95
914
925
938
952
967
984
1.48
1.58
1.70
1.83
957
969
981
995
1.65 1000 1.82 1041 1.99 1082 2.17
1.76 1011 1.93 1052 2.10 1093 2.27
1.87 1024 2.04 1065 2.21 1106 2.39
2.00 1037 2.17 1079 2.34 1119 2.52
1.97 1010 2.14 1053 2.31 1094 2.48 1135 2.66
2.13 1027 2.30 1069 2.47 1111 2.64 1152 2.82
2.13 1002 2.31 1046 2.48 1088 2.65 1129 2.82 1170 3.00
2.33 1022 2.50 1066 2.67 1108 2.84 1149 3.02 1190 3.19
2.54 1044 2.72 1087 2.89 1129 3.06 1171 3.23 1211 3.41
2.59 1022 2.77 1067 2.95 1110 3.12 1152 3.29
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.66 1001 2.85 1047 3.03 1092 3.20 1135 3.37
-
-
-
-
-
-
2.93 1027 3.12 1073 3.30
-
-
-
-
-
-
-
-
3.02 1007 3.22 1055 3.41
-
-
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZF150 (12.5 Ton) Side Duct
Available External Static Pressure - IWG1
Air Flow
(CFM)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive
Standard 3 HP & Drive
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
684
709
734
761
789
818
847
877
907
937
967
997
1.00
1.15
1.30
1.48
1.66
1.87
2.09
2.33
2.59
2.86
741
765
791
818
846
875
904
934
963
993
1.16
1.30
1.46
1.63
1.82
2.03
2.25
2.49
794
818
844
871
899
928
957
986
1.32
1.46
1.62
1.79
1.98
2.19
844
868
894
921
949
978
1.48
1.62
1.78
1.95
2.14
892
916
942
969
997
1.65
1.79
1.94
940
964
990
1.81
988
1.97 1036 2.12 1087 2.27 1141 2.42
1.95 1012 2.11 1061 2.26 1112 2.42 1166 2.56
2.10 1038 2.26 1087 2.42 1137 2.57 1191 2.72
2.12 1017 2.28 1065 2.44 1114 2.59 1164 2.75 1218 2.89
2.31 1045 2.47 1093 2.63 1142 2.78 1192 2.93 1246 3.08
2.35 1026 2.51 1074 2.67 1121 2.83 1170 2.99 1221 3.14 1275 3.29
2.41 1007 2.57 1055 2.73 1103 2.90 1151 3.06 1199 3.21 1250 3.36 1304 3.51
2.65 1036 2.81 1085 2.97 1132 3.14 1180 3.29 1229 3.45 1280 3.60 1334 3.75
2.75 1016 2.91 1066 3.07 1115 3.23 1162 3.39 1210 3.55 1259 3.71 1310 3.86 1364 4.01
3.02 1046 3.18 1096 3.34 1145 3.50 1192 3.66 1240 3.82 1289 3.98 1340 4.13 1394 4.28
3.15 1023 3.31 1076 3.47 1126 3.63 1175 3.79 1222 3.95 1270 4.11 1319 4.27 1370 4.42 1424 4.57
3.45 1053 3.61 1106 3.77 1156 3.93 1205 4.09 1252 4.26 1300 4.41 1349 4.57 1400 4.72 1454 4.87
1027 3.77 1083 3.93 1136 4.09 1186 4.25 1235 4.41 1282 4.57 1330 4.73 1379 4.89 1430 5.04 1484 5.19
1057 4.11 1113 4.26 1166 4.42 1216 4.59 1264 4.75 1312 4.91 1360 5.07 1409 5.22
-
-
-
-
-
-
-
-
-
-
-
-
1086 4.46 1143 4.61 1196 4.77 1246 4.93 1294 5.10 1342 5.26
-
-
-
-
-
-
-
-
1116 4.82 1172 4.98 1225 5.14 1275 5.30
Hi Static 5 HP & Drive
-
-
-
-
5 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
28
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Bottom Duct Application
ZF078 (6.5 Ton) Bottom Duct
Air Flow
Available External Static Pressure - IWG1
0.8 1.0 1.2 1.4
0.2
0.4
0.6
1.6
1.8
2.0
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 1.5 HP & Drive
Hi Static 2 HP & Drive
1800
2000
2200
2400
2600
2800
3000
3200
3400
775
803
838
878
923
971
0.31
0.45
0.60
0.78
0.98
850
878
913
953
997
0.53
0.67
0.82
924
952
986
0.72 998 0.89 1072 1.05 1147 1.20 1224 1.35 1303 1.51 1384 1.69 1469 1.89
0.86 1026 1.03 1100 1.19 1175 1.34 1252 1.49 1331 1.65 1412 1.83 1497 2.03
1.01 1060 1.19 1134 1.34 1210 1.49 1286 1.65 1365 1.81 1447 1.98 1532 2.18
1.00 1027 1.19 1100 1.36 1174 1.52 1250 1.67 1327 1.82 1405 1.98 1487 2.16
-
-
-
-
-
-
-
-
-
-
-
-
1.20 1071 1.39 1145 1.56 1219 1.72 1294 1.87 1371 2.02 1450 2.18
-
-
-
-
-
-
-
-
-
-
1.20 1046 1.42 1119 1.61 1193 1.78 1267 1.94 1343 2.09 1419 2.24
-
-
-
-
-
-
-
-
1023 1.44 1097 1.66 1171 1.85 1245 2.03 1319 2.18
-
-
-
-
-
-
-
-
-
-
-
-
1077 1.71 1151 1.93 1225 2.12 1299 2.29
1133 1.99 1208 2.21
-
-
-
-
-
-
-
-
2 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZF090 (7.5 Ton) Bottom Duct
Available External Static Pressure - IWG1
Air Flow
(CFM)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 1.5 HP & Drive
Hi Static 3 HP & Drive
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
803
838
878
923
971
0.45
0.60
0.78
0.98
878
913
953
997
0.67
0.82
952
986
0.86 1026 1.03 1100 1.19 1175 1.34 1252 1.49 1331 1.65 1412 1.83 1497 2.03
1.01 1060 1.19 1134 1.34 1210 1.49 1286 1.65 1365 1.81 1447 1.98 1532 2.18
1.00 1027 1.19 1100 1.36 1174 1.52 1250 1.67 1327 1.82 1405 1.98 1487 2.16 1572 2.36
1.20 1071 1.39 1145 1.56 1219 1.72 1294 1.87 1371 2.02 1450 2.18 1532 2.36 1617 2.56
1.20 1046 1.42 1119 1.61 1193 1.78 1267 1.94 1343 2.09 1419 2.24 1498 2.40 1580 2.58 1665 2.78
1023 1.44 1097 1.66 1171 1.85 1245 2.03 1319 2.18 1394 2.33 1471 2.49 1550 2.65 1632 2.82 1717 3.02
1077 1.71 1151 1.93 1225 2.12 1299 2.29 1373 2.45 1448 2.60 1525 2.75 1604 2.91 1686 3.09 1771 3.29
1133 1.99 1208 2.21 1282 2.41 1356 2.58 1430 2.73 1505 2.88 1582 3.04 1661 3.20 1742 3.37
-
-
-
-
-
-
1192 2.30 1267 2.52 1341 2.71 1414 2.88 1489 3.04 1564 3.19 1641 3.34
1253 2.63 1327 2.85 1401 3.04 1475 3.21 1549 3.37
-
-
-
-
-
-
-
-
-
-
-
-
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZF102 (8.5 Ton) Bottom Duct
Available External Static Pressure - IWG1
Air Flow
(CFM)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
4
FS
674
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
2800
3000
3200
3400
3600
3800
4000
4200
0.71
0.86
1.01
1.17
1.34
1.53
1.74
1.97
2.21
731
746
764
785
808
833
861
892
924
0.88
1.02
1.17
1.33
1.51
1.70
1.90
2.13
2.37
786
801
819
840
863
888
916
947
979
1.05
1.20
1.35
1.51
1.68
1.87
2.08
2.31
838
854
872
892
915
941
969
999
1.24
1.38
1.53
1.69
1.87
2.06
887
903
921
941
964
990
1.42
1.56
1.71
1.87
933
948
966
987
1.59
1.73
974
989
1.74 1010 1.87 1040 1.97 1064 2.03
1.88 1025 2.01 1056 2.11 1080 2.17
689
707
728
751
776
804
835
867
1.88 1007 2.03 1043 2.16 1074 2.26 1098 2.32
2.04 1028 2.20 1064 2.33 1094 2.42 1118 2.48
2.05 1010 2.22 1051 2.37 1087 2.50 1117 2.60 1141 2.66
2.24 1035 2.41 1076 2.56 1112 2.69 1142 2.79 1167 2.85
2.26 1018 2.44 1063 2.61 1104 2.77 1140 2.90 1170 2.99 1194
-
-
-
2.49 1048 2.67 1094 2.84 1135 2.99
-
-
-
-
-
-
-
-
-
-
2.55 1032 2.73 1081 2.91 1127 3.08
-
-
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932
4. Field Supplied Drive.
Johnson Controls Unitary Products
29
528194-YTG-F-1210
ZF120 (10 Ton) Bottom Duct
Air Flow
Available External Static Pressure - IWG1
0.8 1.0 1.2 1.4
0.2
0.4
0.6
1.6
1.8
2.0
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive
Standard 2 HP & Drive
Hi Static 3 HP & Drive
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
722
744
769
797
828
861
897
935
976
0.83
0.97
1.13
1.32
1.52
1.75
2.00
2.27
776
798
823
851
882
915
951
989
0.97
1.12
1.28
1.46
1.67
1.90
828
850
875
903
934
967
1.11
1.26
1.42
1.60
1.81
878
900
925
953
983
1.25
1.39
1.55
926
949
974
1.37
1.52
973
995
1.50 1018 1.62 1063 1.74 1106 1.86 1149 1.99
1.64 1041 1.76 1085 1.88 1128 2.00 1171 2.13
1.68 1020 1.80 1066 1.92 1110 2.05 1153 2.17 1196 2.29
1.74 1001 1.86 1048 1.99 1093 2.11 1138 2.23 1181 2.35 1224 2.48
1.94 1032 2.07 1078 2.19 1124 2.32 1168 2.44 1212 2.56 1254 2.68
2.04 1017 2.17 1065 2.30 1112 2.42 1157 2.54 1201 2.67 1245 2.79 1287 2.91
2.15 1002 2.29 1052 2.42 1101 2.55 1147 2.67 1193 2.80 1237 2.92 1280 3.04 1323 3.16
2.42 1041 2.56 1091 2.69 1139 2.82 1186 2.95 1231 3.07 1275 3.19 1319 3.31 1362 3.43
2.57 1030 2.72 1082 2.86 1132 2.99 1180 3.12 1227 3.24 1272 3.36
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1019 2.88 1073 3.03 1125 3.17 1175 3.30 1223 3.43
1065 3.22 1119 3.36
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
ZF150 (12.5 Ton) Bottom Duct
Available External Static Pressure - IWG1
Air Flow
(CFM)
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP & Field Supplied Drive
Standard 3 HP & Drive
Hi Static 5 HP & Drive
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
823
860
898
936
975
1.28
1.48
1.71
1.97
861
898
935
974
1.47
1.67
1.90
906
942
980
1.64
1.84
955
992
1.80 1007 1.95 1059 2.12 1109 2.29 1155 2.50 1194 2.73 1225 3.01
2.00 1044 2.16 1095 2.32 1145 2.50 1191 2.70 1231 2.94 1262 3.22
2.07 1030 2.23 1081 2.39 1133 2.55 1183 2.73 1229 2.94 1269 3.17 1300 3.45
2.16 1019 2.33 1068 2.49 1120 2.64 1172 2.81 1222 2.98 1267 3.19 1307 3.42 1338 3.70
2.24 1013 2.43 1057 2.60 1107 2.76 1158 2.92 1210 3.08 1260 3.26 1306 3.46 1346 3.70 1377 3.97
1014 2.54 1052 2.73 1096 2.90 1146 3.05 1197 3.21 1249 3.38 1299 3.55 1345 3.76 1385 3.99 1416 4.27
1053 2.85 1091 3.04 1135 3.21 1185 3.37 1236 3.53 1288 3.69 1338 3.87 1384 4.07 1424 4.31 1455 4.58
1091 3.19 1129 3.38 1174 3.55 1223 3.71 1275 3.86 1327 4.03 1377 4.20 1423 4.41 1462 4.64 1494 4.92
1130 3.54 1168 3.73 1213 3.90 1262 4.06 1314 4.22 1365 4.38 1415 4.56 1461 4.76 1501 5.00 1532 5.27
1168 3.92 1206 4.11 1251 4.28 1300 4.44 1352 4.59 1404 4.76 1454 4.94 1500 5.14 1539 5.37
-
-
-
-
-
-
-
-
-
-
1206 4.31 1244 4.50 1288 4.67 1338 4.83 1389 4.99 1441 5.15 1491 5.33 1537 5.53
-
-
-
-
-
-
-
-
1243 4.72 1281 4.91 1326 5.08 1375 5.24 1427 5.40 1479 5.56
-
-
-
-
-
-
-
-
-
-
-
-
1280 5.15 1318 5.34 1362 5.51
1316 5.60
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5 HP & Field Supplied Drive
1. Blower performance includes gas heat exchangers and 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
30
Johnson Controls Unitary Products
528194-YTG-F-1210
RPM Selection
Size
Max
BHP
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
Motor
Sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower
Sheave
AK74
AK64
AK74
AK61
AK94
AK74
AK84
AK74
AK74
BK77
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
1 Turn
Open
1084
1256
1084
1312
843
Fully
Closed
1134
1308
1134
1365
882
Model
HP
(Tons)
Open
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
Open
Open
Open
Open
1035
1207
1035
1265
805
1.5
2
887
936
986
078
(6.5)
ZF
ZF
ZF
ZF
ZF
1039
887
1094
936
1150
986
1.5
3
090
(7.5)
1088
690
1147
728
1205
767
2
102
(8.5)
3
887
936
986
1035
906
1084
949
1134
992
2
776
819
863
120
(10)
3
887
936
986
1035
1035
1216
1084
1084
1272
1134
1134
N/A
3
887
936
986
150
(12.5)
5
1095
1136
1175
Additional Static Resistance
Size
Electric Heat kW2
24
,
Model
CFM
Cooling Only1
Economizer2 3
4” Filter2
(Tons)
9
18
36
54
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.00
-0.01
-0.01
-0.02
-0.03
-0.04
-0.05
-0.06
-0.07
-0.08
-0.09
-0.09
-0.10
-0.11
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.30
0.35
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.20
0.21
0.23
0.24
0.25
0.26
0.12
0.13
0.14
0.16
0.17
0.19
0.20
0.22
0.26
0.27
0.29
0.32
0.35
0.38
0.41
0.44
0.47
0.51
0.55
0.58
0.62
0.67
0.71
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
078 (6.5)
090 (7.5)
ZF
102 (8.5)
120 (10)
150 (12.5)
ZF
1. Add these values to the available static resistance in the respective Blower Performance Tables.
2. Deduct these values from the available external static pressure shown in the respective Blower Performance Tables.
3. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is
less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Johnson Controls Unitary Products
31
528194-YTG-F-1210
Drive Selection
1. Determine side or bottom supply duct Application.
2. Determine desired airflow.
3. Calculate or measure the amount of external static pressure.
4. Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5. Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
6. Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7. Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8. Determine turns open to obtain the desired operation point.
Example
1. 2600 CFM
2. 1.6 iwg
3. Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.
4. Using the RPM selection table below, Size X and Model Y is found.
5. 1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6. 1268 RPM is within the range of the 2 HP drives.
7. Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.
Airflow Performance
Example Supply Air Blower Performance
Available External Static Pressure - IWG
Air Flow
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
(CFM)
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
Standard 1.5 HP & Drive
Alternate 2 HP & Drive
2200
2400
2600
2800
804
835
869
906
0.50
0.66
0.84
1.03
866
897
931
968
0.71
0.87
1.05
925
956
990
0.90
982
1.06 1038 1.21 1092 1.35 1147 1.48 1203 1.61 1259 1.73 1317 1.87
1.06 1013 1.22 1069 1.37 1124 1.51 1178 1.64 1234 1.77 1290 1.90 1348 2.03
1.24 1047 1.40 1103 1.55 1158 1.69 1212 1.82 1268 1.95 1324 2.07 1382 2.21
1.25 1027 1.43 1084 1.60 1139 1.75 1194 1.89 1249 2.02 1304 2.14 1361 2.27
-
-
Table X: RPM Selection
Size
(Tons)
Max
BHP
1.73
2.30
Motor
Sheave
1VM50
1VM50
Blower
Sheave
AK74
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns
1 Turn
Open
1079
Fully
Closed
1126
Model
HP
Open
Open
Open
Open
Open
1035
1207
1.5
2
N/A
897
945
991
X
Y
AK64
N/A
1039
1094
1150
1256
1308
32
Johnson Controls Unitary Products
528194-YTG-F-1210
Altitude/Temperature Correction Factors
Air
Altitude (Ft.)
5000
Temp.
40
0
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
1.060
1.039
1.019
1.000
0.982
0.964
0.946
0.882
0.864
0.848
0.832
0.817
0.802
0.787
50
60
70
80
90
100
1.100
1.050
1.000
0.950
0.900
0.850
0.800
0.750
0.700
0.650
0.600
Sea Level
1000 ft
2000 ft
3000 ft
4000 ft
5000 ft
6000 ft
7000 ft
8000 ft
9000 ft
10000 ft
40
50
60
70
80
90
100
Air Temperature (ºF)
Johnson Controls Unitary Products
33
528194-YTG-F-1210
Gas Heat Minimum Supply Air
Supply Air (CFM)
Size
Model
(Tons)
Heat Size
Cooling
Heating
Min
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
Min
Max
3250
3250
3750
3750
4250
4250
5000
5000
6250
6250
10
15
10
15
10
15
15
20
15
20
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
1950
1950
2250
2250
2550
2550
3000
3000
3750
3750
078
(6.5)
ZF
ZF
ZF
ZF
ZF
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Electric Heat Minimum Supply Air
Minimum Supply Air (CFM)
Heater kW
Size
Model
(Tons)
Voltage
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
18
24
36
54
-
-
-
-
-
-
-
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
1950
1950
1950
2250
2250
2250
2550
2550
2550
3000
3000
3000
3750
3750
3750
1950
1950
1950
2250
2250
2250
2550
2550
2550
3000
3000
3000
3750
3750
3750
1950
1950
1950
2250
2250
2250
2550
2550
2550
3000
3000
3000
3750
3750
3750
078
(6.5)
ZF
090
(7.5)
ZF
102
(8.5)
ZF
-
-
3500
3000
3500
4000
3750
3750
120
(10)
ZF
-
-
-
-
208/230-3-60
460-3-60
600-3-60
150
(12.5)
ZF
-
Indoor Blower Specifications
Motor
RPM Eff.
Motor Sheave
Blower Sheave
Size
(Tons)
Model
Belt
Datum Dia.
(in.)
Datum Dia.
(in.)
7.0
HP
SF
Frame
Bore (in.) Model
Bore (in.)
Model
1-1/2 1725
1725
1-1/2 1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
56
56
56
56
56
56
56
56
56
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
4.3 - 5.3
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1-1/8
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
1
1
1
1
1
1
1
1
1
1
AK74
AK64
AK74
AK61
AK94
AK74
AK84
AK74
AK74
BK77
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
078
(6.5)
090
ZF
ZF
ZF
ZF
ZF
2
6.0
7.0
5.7
9.0
7.0
8.0
7.0
7.0
(7.5)
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
102
(8.5)
120
(10)
150
(12.5)
1725 0.87 1.15
184T
6.7
Power Exhaust Specifications
Motor
RPM1
Motor
CFM @
0.1 ESP
Model
Voltage
Fuse Size
HP
3/4
3/4
3/4
QTY
LRA
7.8
FLA
5
MCA
6.3
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
1075
1075
1050
1
1
1
10
5
3800
3.4
2.2
1.5
2.8
3800
575-1-60
2.9
1.9
4
3800
1. Motors are multi-tapped and factory wired for high speed.
34
Johnson Controls Unitary Products
528194-YTG-F-1210
Electric Heat Multipliers
Voltage
kW Capacity Multipliers1
Nominal
Applied
208
0.75
0.92
0.92
0.92
240
230
480
600
460
575
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Indoor Sound Power Levels
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
Blower
Size
(Tons)
ESP
(IWG)
Sound Rating1
dB (A)
Model
CFM
RPM
BHP
63
125
250
500
1000
2000
4000
8000
078
(6.5)
ZF
ZF
ZF
ZF
ZF
2600
3000
3400
4000
5000
0.6
0.6
0.6
0.6
0.6
812
854
872
959
1132
1.14
74
77
80
83
87
71
73
73
71
69
65
65
60
090
(7.5)
1.47
1.65
2.29
3.74
74
77
80
84
76
79
82
86
76
79
82
86
74
77
80
84
72
75
78
82
68
71
74
78
68
71
74
78
63
66
69
73
102
(8.5)
120
(10)
150
(12.5)
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Outdoor Sound Power Levels
ZF078-150
Octave Band Centerline Frequency (Hz)
Size
(Tons)
Sound Rating1
dB (A)
Model
ZF
63
125
250
500
1000
2000
4000
8000
078
(6.5)
84
89
91
92
88
86.0
87.5
86.0
82.5
79.0
73.5
68.5
62.0
090
(7.5)
ZF
89.5
91.5
99.5
91.0
92.0
93.5
94.5
92.5
89.0
92.5
92.0
90.0
87.5
89.0
90.0
85.0
84.0
85.5
87.0
81.5
78.5
80.5
81.0
77.0
73.5
76.0
76.0
73.0
66.5
71.0
70.0
66.5
102
(8.5)
ZF
120
(10)
ZF
150
(12.5)
ZF
1. Rated in accordance with ARI 270 standard.
Johnson Controls Unitary Products
35
528194-YTG-F-1210
Electrical Data
ZF078-150 Standard Motor - Without Powered Convenience Outlet
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/
Pwr Exh
(Amps)
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
-
6.8
13.5
18
25.5
-
-
-
29.9
31.1
54.3
70
35.4
38
35
35
60
70
100
35
35
70
80
110
20
20
35
40
60
15
15
25
35
45
50
50
60
70
100
50
50
70
80
110
20
20
35
40
60
20
20
25
35
45
50
50
60
80
100
50
50
70
90
125
25
25
35
45
60
20
20
25
35
45
40
40
70
80
110
40
45
70
90
125
20
20
35
45
60
15
20
30
35
50
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
10.8
21.7
28.9
40.9
-
208 9.3
230 9.3
460 4.9
575 3.8
208 11.9
230 11.9
460 5.2
575 4.8
208 12.2
230 12.2
460 5.8
575 4.4
68
68
34
28
88
88
44
36
88
88
44
36
14.5
14.5
7.7
6
1.5
6.0
5.5
0
61.2
76.8
102.9
35.4
41.4
68.5
86.5
116.6
17.8
20
96
29.9
34.6
61.6
79.7
109.7
15.6
17.3
30.8
39.8
54.9
12.2
13.8
24.7
31.9
43.9
39.8
39.8
54.3
70
9
1.5
0.8
0.6
3.5
3.5
1.6
1.3
3.5
3.5
1.6
1.3
6.0
3.0
2.4
6.0
6.0
3.0
2.4
6.8
6.8
3.4
2.7
5.5
2.2
1.8
5.5
5.5
2.2
1.8
5.5
5.5
2.2
1.8
0
0
0
0
0
0
0
0
0
0
0
18
24
34
-
078
(6.5)
9
18
24
34
-
33.6
42.6
57.6
14
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
8.7
16.1
26.9
34.1
46.1
45.3
45.3
61.2
76.8
102.9
45.3
45.3
68.5
86.5
116.6
20.1
20.1
33.6
42.6
57.6
17.6
17.6
26.9
34.1
46.1
46.8
46.8
62.2
77.8
103.9
46.8
46.8
69.5
87.5
117.6
21.9
21.9
34.1
43.1
58.1
17
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
18.5
18.5
8.1
7.5
19
96
39.8
39.8
61.6
79.7
109.7
17.9
17.9
30.8
39.8
54.9
15.8
15.8
24.7
31.9
43.9
41.3
41.3
55.3
71
9
18
24
34
-
090
(7.5)
9
1
2
2
2
-
10.8
21.7
28.9
40.9
-
18
24
34
-
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
8.7
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
97
41.3
41.3
62.6
80.7
110.7
19.7
19.7
31.3
40.3
55.4
15.2
15.2
25
9
19
18
24
34
-
102
(8.5)
9
1
2
2
2
-
1
2
2
2
10.8
21.7
28.9
40.9
-
9
18
24
34
-
9
8.7
17
5.5
18
24
34
17.3
23.1
32.7
27.3
34.5
46.5
32.2
44.3
36
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
2
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
1
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
3
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/
Pwr Exh
(Amps)
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
-
13.5
18
25.5
40.6
-
18
24
34
54
-
-
-
45.1
55.3
71
50.6
62.2
77.8
103.9
156.2
50.6
69.5
87.5
117.6
145.3
25.5
34.1
43.1
58.1
72
19.7
27.3
34.5
46.5
57.6
81.1
81.1
81.3
107.4
159.7
81.1
81.1
91.0
121.1
148.8
40.9
40.9
44.8
59.9
73.7
30.5
30.5
36.0
48.0
59.1
50
60
60
70
2
2
2
2
-
2
2
2
2
-
37.5
50.0
70.8
112.7
-
43.3
57.7
81.8
129.9
-
208 13.9 110 21.7
3.5
6.8
5.5
0
80
80
97
100
150
50
70
90
110
175
60
70
90
149.4
45.1
62.6
80.7
110.7
138.4
23.3
31.3
40.3
55.4
69.2
17.9
25
230 13.9 110 21.7
3.5
1.6
1.3
3.5
3.5
1.6
1.3
6.8
3.4
2.7
9.6
9.6
4.8
3.9
5.5
2.2
1.8
5.5
5.5
2.2
1.8
0
0
0
0
0
0
0
125
150
30
125
175
30
120
(10)
18
24
34
54
-
18
24
34
54
-
13.5
18
25.5
40.6
-
2
2
2
2
-
2
2
2
2
-
2
2
2
2
-
21.7
28.9
40.9
65.0
-
17.3
23.1
32.7
52.0
-
37.5
50.0
70.8
112.7
-
35
45
60
35
45
60
460 7.4
55
43
11.5
8.7
36
80
20
25
80
25
30
575 5.6
32.2
44.3
55.3
75.6
75.6
75.6
100.5
152.9
75.6
75.6
84.2
114.2
141.9
38.7
38.7
42.1
57.1
71.0
28.7
28.7
33.7
45.8
56.8
35
45
60
35
50
60
90
90
90
100
100
100
110
175
100
100
100
125
175
50
208 23.1 160
110
175
90
18
24
34
54
-
18
24
34
54
-
2
2
2
2
-
2
2
2
2
-
43.3
57.7
81.8
129.9
-
21.7
28.9
40.9
65.0
-
90
90
125
175
50
230 23.1 160
36
150
(12.5)
50
50
460 12.2
87
62
19
50
60
80
50
60
80
35
35
35
35
35
40
18
24
34
54
2
2
2
2
17.3
23.1
32.7
52.0
575 8.7
13.5
50
70
50
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
37
528194-YTG-F-1210
ZF078-150 Hi Static Motor - Without Powered Convenience Outlet
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW Stages Amps
(Amps)
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
-
6.8
13.5
18
25.5
-
-
-
30.7
32.1
55.3
71
36.2
39
40
40
60
80
100
40
40
70
90
125
20
20
35
45
60
15
15
25
35
45
50
50
60
80
110
50
50
70
90
125
20
20
35
45
60
20
20
30
35
50
50
50
60
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
45
45
70
80
110
45
45
70
90
125
20
25
35
45
60
15
20
30
35
50
60
60
70
90
110
60
60
80
100
125
25
25
40
45
60
20
20
30
40
50
60
60
70
90
110
60
60
80
100
125
25
25
40
45
60
20
20
30
40
50
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
10.8
21.7
28.9
40.9
-
208 9.3
230 9.3
460 4.9
575 3.8
208 11.9
230 11.9
460 5.2
575 4.8
208 12.2
230 12.2
460 5.8
575 4.4
68
68
34
28
88
88
44
36
88
88
44
36
14.5
14.5
7.7
6
1.5
6.8
5.5
0
62.2
77.8
103.9
36.2
42.4
69.5
87.5
117.6
18.2
20.5
34.1
43.1
58.1
14.3
16.5
27.3
34.5
46.5
48.9
48.9
65.7
81.3
107.4
48.9
48.9
73
97
30.7
35.6
62.6
80.7
110.7
16
17.8
31.3
40.3
55.4
12.5
14.2
25
9
1.5
0.8
0.6
3.5
3.5
1.6
1.3
3.5
3.5
1.6
1.3
6.8
3.4
2.7
9.6
9.6
4.8
3.9
9.6
9.6
4.8
3.9
5.5
2.2
1.8
5.5
5.5
2.2
1.8
5.5
5.5
2.2
1.8
0
0
0
0
0
0
0
0
0
0
0
18
24
34
-
078
(6.5)
9
18
24
34
-
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
8.7
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
32.2
44.3
43.4
43.4
58.8
74.5
100.5
43.4
43.4
66.1
84.2
114.2
19.7
19.7
33.1
42.1
57.1
17.3
17.3
26.5
33.7
45.8
44.1
44.1
58.8
74.5
100.5
44.1
44.1
66.1
84.2
114.2
21.1
21.1
33.1
42.1
57.1
16.4
16.4
26.5
33.7
45.8
18.5
18.5
8.1
7.5
19
9
18
24
34
-
91
121.1
21.9
22.3
35.8
44.8
59.9
19.1
19.1
28.8
36
090
(7.5)
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
10.8
21.7
28.9
40.9
-
18
24
34
-
9
8.7
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
48
49.6
49.6
65.7
81.3
107.4
49.6
49.6
73
9
19
18
24
34
-
91
121.1
23.3
23.3
35.8
44.8
59.9
18.2
18.2
28.8
36
102
(8.5)
9
1
2
2
2
-
1
2
2
2
10.8
21.7
28.9
40.9
-
9
18
24
34
-
9
8.7
5.5
18
24
34
17.3
23.1
32.7
48
38
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)
2
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
1
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
3
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW Stages Amps
(Amps)
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
-
13.5
18
25.5
40.6
-
18
24
34
54
-
-
-
47.9
58.8
74.5
100.5
152.9
47.9
66.1
84.2
114.2
141.9
24.7
33.1
42.1
57.1
71
19.1
26.5
33.7
45.8
56.8
81.2
81.2
81.5
107.5
159.9
81.2
81.2
91.2
121.2
148.9
41.5
41.5
45.6
60.6
74.5
30.9
30.9
36.5
48.5
59.6
53.4
65.7
81.3
107.4
159.7
53.4
73
60
60
60
70
2
2
2
2
-
2
2
2
2
-
37.5
50.0
70.8
112.7
-
43.3
57.7
81.8
129.9
-
208 13.9 110 21.7
3.5
9.6
5.5
0
80
90
110
175
60
70
90
110
175
60
80
230 13.9 110 21.7
3.5
1.6
1.3
3.5
3.5
1.6
1.3
9.6
4.8
5.5
2.2
1.8
5.5
5.5
2.2
1.8
0
0
0
0
0
0
0
91
100
125
175
30
121.1
148.8
26.9
35.8
44.8
59.9
73.7
20.9
28.8
36
125
175
30
120
(10)
18
24
34
54
-
18
24
34
54
-
13.5
18
25.5
40.6
-
2
2
2
2
-
2
2
2
2
-
2
2
2
2
-
21.7
28.9
40.9
65.0
-
17.3
23.1
32.7
52.0
-
37.5
50.0
70.8
112.7
-
35
45
60
40
45
60
460 7.4
55
43
11.5
8.7
36
80
20
30
80
25
30
575 5.6
3.9
35
50
70
40
50
70
48
59.1
86.7
86.7
88.3
114.4
166.7
86.7
86.7
98.0
128.1
155.8
43.7
43.7
48.3
63.4
77.2
32.7
32.7
38.7
50.8
61.8
100
100
100
110
175
100
100
100
125
175
50
100
100
100
125
175
100
100
100
150
175
50
208 23.1 160
15.2
15.2
7.6
18
24
34
54
-
18
24
34
54
-
2
2
2
2
-
2
2
2
2
-
43.3
57.7
81.8
129.9
-
21.7
28.9
40.9
65.0
-
230 23.1 160
36
150
(12.5)
50
50
460 12.2
87
62
19
50
70
90
50
70
90
35
35
40
40
40
40
18
24
34
54
2
2
2
2
17.3
23.1
32.7
52.0
575 8.7
13.5
6.1
50
70
60
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
39
528194-YTG-F-1210
ZF078-150 Standard Motor - With Powered Convenience Outlet
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW Stages Amps
(Amps)
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
-
6.8
13.5
18
25.5
-
-
-
40.1
43.6
66.8
82.5
108.5
40.1
47.1
74.1
92.2
122.2
20.7
23.5
37.1
46.1
61.1
16.2
18.8
29.7
36.9
48.9
49.8
49.8
66.8
82.5
108.5
49.8
49.8
74.1
92.2
122.2
22.9
23.5
37.1
46.1
61.1
19.8
19.8
29.7
36.9
48.9
51.3
51.3
67.8
83.5
109.5
51.3
51.3
75.1
93.2
123.2
24.7
24.7
37.6
46.6
61.6
19.2
19.2
30
45.6
50.5
73.7
89.3
115.4
45.6
53.9
81
50
50
70
90
110
50
50
80
100
125
25
25
40
50
70
20
20
30
40
50
60
60
70
90
110
60
60
80
100
125
25
25
40
50
70
20
20
30
40
50
60
60
70
90
110
60
60
80
100
125
30
30
40
50
70
20
20
30
40
50
50
60
80
90
125
50
60
90
100
150
25
30
40
50
70
20
25
35
40
60
60
60
80
90
125
60
60
90
100
150
30
30
40
50
70
25
25
35
40
60
60
60
80
100
125
60
60
90
100
150
30
30
45
50
70
25
25
35
40
60
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
10.8
21.7
28.9
40.9
-
208 9.3
230 9.3
460 4.9
575 3.8
208 11.9
230 11.9
460 5.2
575 4.8
208 12.2
230 12.2
460 5.8
575 4.4
68
68
34
28
88
88
44
36
88
88
44
36
14.5
14.5
7.7
6
1.5
6.0
5.5
10
9
1.5
0.8
0.6
3.5
3.5
1.6
1.3
3.5
3.5
1.6
1.3
6.0
3.0
2.4
6.0
6.0
3.0
2.4
6.8
6.8
3.4
2.7
5.5
2.2
1.8
5.5
5.5
2.2
1.8
5.5
5.5
2.2
1.8
10
5
18
24
34
-
99
129.1
22.9
26.3
39.8
48.8
63.9
18
078
(6.5)
9
18
24
34
-
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
8.7
21.1
31.9
39.1
51.1
55.3
55.3
73.7
89.3
115.4
55.3
55.3
81
4
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
18.5
18.5
8.1
7.5
19
10
10
5
9
18
24
34
-
99
129.1
25.1
26.3
39.8
48.8
63.9
21.6
21.6
31.9
39.1
51.1
56.8
56.8
74.7
90.3
116.4
56.8
56.8
82
090
(7.5)
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
10.8
21.7
28.9
40.9
-
18
24
34
-
9
8.7
4
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
10
10
5
9
19
18
24
34
-
100
130.1
26.9
26.9
40.3
49.3
64.4
21
21.5
32.3
39.5
51.5
102
(8.5)
9
1
2
2
2
-
1
2
2
2
10.8
21.7
28.9
40.9
-
9
18
24
34
-
9
8.7
5.5
4
18
24
34
17.3
23.1
32.7
37.2
49.3
40
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Standard Motor - With Powered Convenience Outlet (Continued)
2
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
1
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
3
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW Stages Amps
(Amps)
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
-
13.5
18
25.5
40.6
-
18
24
34
54
-
-
-
55.1
67.8
83.5
109.5
161.9
55.1
75.1
93.2
123.2
150.9
28.3
37.6
46.6
61.6
75.5
21.9
30
60.6
74.7
90.3
116.4
168.7
60.6
82
60
70
70
80
2
2
2
2
-
2
2
2
2
-
37.5
50.0
70.8
112.7
-
43.3
57.7
81.8
129.9
-
208 13.9 110 21.7
3.5
6.8
5.5
10
90
100
125
175
70
110
175
60
80
90
230 13.9 110 21.7
3.5
1.6
1.3
3.5
3.5
1.6
1.3
6.8
3.4
2.7
9.6
9.6
4.8
3.9
5.5
2.2
1.8
5.5
5.5
2.2
1.8
10
5
100
100
125
175
35
100
150
175
35
130.1
157.8
30.5
40.3
49.3
64.4
78.2
23.7
32.3
39.5
51.5
62.6
91.1
91.1
93.8
119.9
172.2
91.1
91.1
103.5
133.6
161.3
45.9
45.9
51.1
66.1
80.0
34.5
34.5
41.0
53.0
64.1
120
(10)
18
24
34
54
-
18
24
34
54
-
13.5
18
25.5
40.6
-
2
2
2
2
-
2
2
2
2
-
2
2
2
2
-
21.7
28.9
40.9
65.0
-
17.3
23.1
32.7
52.0
-
37.5
50.0
70.8
112.7
-
40
50
70
45
50
70
460 7.4
55
43
11.5
8.7
36
80
25
30
90
25
35
575 5.6
4
37.2
49.3
60.3
85.6
85.6
87.0
113.0
165.4
85.6
85.6
96.7
126.7
154.4
43.7
43.7
48.3
63.4
77.2
32.7
32.7
38.7
50.8
61.8
40
50
70
40
60
70
100
100
100
125
175
100
100
100
150
175
50
110
110
110
125
175
110
110
110
150
175
50
208 23.1 160
10
10
5
18
24
34
54
-
18
24
34
54
-
2
2
2
2
-
2
2
2
2
-
43.3
57.7
81.8
129.9
-
21.7
28.9
40.9
65.0
-
230 23.1 160
36
150
(12.5)
50
50
460 12.2
87
62
19
50
70
90
60
70
90
40
40
40
40
40
45
18
24
34
54
2
2
2
2
17.3
23.1
32.7
52.0
575 8.7
13.5
4
60
70
60
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
41
528194-YTG-F-1210
ZF078-150 Hi Static Motor - With Powered Convenience Outlet
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW Stages Amps
(Amps)
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
-
6.8
13.5
18
25.5
-
-
-
40.9
44.6
67.8
83.5
109.5
40.9
48.1
75.1
93.2
123.2
21.1
24
37.6
46.6
61.6
16.5
19.2
30
46.4
51.5
74.7
90.3
116.4
46.4
54.9
82
50
50
70
90
110
50
50
80
100
125
25
25
40
50
70
20
20
30
40
50
60
60
80
90
125
60
60
80
100
150
25
30
40
50
70
25
25
35
40
60
60
60
80
90
125
60
60
80
100
150
30
30
40
50
70
25
25
35
40
60
50
60
80
100
125
50
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
10.8
21.7
28.9
40.9
-
208 9.3
230 9.3
460 4.9
575 3.8
208 11.9
230 11.9
460 5.2
575 4.8
208 12.2
230 12.2
460 5.8
575 4.4
68
68
34
28
88
88
44
36
88
88
44
36
14.5
14.5
7.7
6
1.5
6.8
5.5
10
9
60
1.5
0.8
0.6
3.5
3.5
1.6
1.3
3.5
3.5
1.6
1.3
6.8
3.4
2.7
9.6
9.6
4.8
3.9
9.6
9.6
4.8
3.9
5.5
2.2
1.8
5.5
5.5
2.2
1.8
5.5
5.5
2.2
1.8
10
5
18
24
34
-
90
100
100
150
25
30
45
130.1
23.3
26.8
40.3
49.3
64.4
18.3
21.5
32.3
39.5
51.5
58.9
58.9
78.2
93.8
119.9
58.9
58.9
85.5
103.5
133.6
26.9
28.5
42.1
51.1
66.1
23.1
23.1
33.8
41
078
(6.5)
9
18
24
34
-
50
70
20
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
8.7
25
35
40
4
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
37.2
49.3
53.4
53.4
71.3
87
60
70
70
18.5
18.5
8.1
7.5
19
10
10
5
80
100
125
70
70
90
113
53.4
53.4
78.6
96.7
126.7
24.7
25.8
39.3
48.3
63.4
21.3
21.3
31.5
38.7
50.8
54.1
54.1
71.3
87
9
18
24
34
-
110
150
30
090
(7.5)
9
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
1
2
2
2
-
10.8
21.7
28.9
40.9
-
30
45
60
18
24
34
-
70
25
25
9
8.7
4
18
24
34
-
6.8
13.5
18
25.5
-
17.3
23.1
32.7
-
18.9
37.5
50.0
70.8
-
21.7
43.3
57.7
81.8
-
35
45
53
60
70
70
59.6
59.6
78.2
93.8
119.9
59.6
59.6
85.5
103.5
133.6
28.3
28.5
42.1
51.1
66.1
22.2
23
10
10
5
80
100
125
70
70
90
113
54.1
54.1
78.6
96.7
126.7
26.1
26.1
39.3
48.3
63.4
20.4
20.7
31.5
38.7
50.8
9
19
18
24
34
-
110
150
30
102
(8.5)
9
1
2
2
2
-
1
2
2
2
10.8
21.7
28.9
40.9
-
30
45
60
9
18
24
34
-
70
25
25
9
8.7
5.5
4
18
24
34
17.3
23.1
32.7
33.8
41
53
35
45
60
42
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)
2
OD Fan Supply
Pwr
Exh
Motor Outlet
Pwr
Conv
Max Fuse /
Breaker
1
2
Compressors
(each)
MCA
Max Fuse /
Breaker
Size
(Amps)
3
Motors
(each)
Blower
Motor
Electric Heat Option
1
3
Size
(Tons)
MCA
w/Pwr
Exh
(Amps)
Volt
Size w/ Pwr
Exh
(Amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW Stages Amps
(Amps)
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
-
13.5
18
25.5
40.6
-
18
24
34
54
-
-
-
57.9
71.3
87
63.4
78.2
93.8
119.9
172.2
63.4
85.5
103.5
133.6
161.3
31.9
42.1
51.1
66.1
80
70
80
70
80
2
2
2
2
-
2
2
2
2
-
37.5
50.0
70.8
112.7
-
43.3
57.7
81.8
129.9
-
208 13.9 110 21.7
3.5
9.6
5.5
10
90
100
125
175
70
113
125
175
70
165.4
57.9
78.6
96.7
126.7
154.4
29.7
39.3
48.3
63.4
77.2
23.1
31.5
38.7
50.8
61.8
91.2
91.2
94.0
120.0
172.4
91.2
91.2
103.7
133.7
161.4
46.5
46.5
51.8
66.9
80.7
34.9
34.9
41.5
53.5
64.6
80
90
230 13.9 110 21.7
3.5
1.6
1.3
3.5
3.5
1.6
1.3
9.6
4.8
5.5
2.2
1.8
5.5
5.5
2.2
1.8
10
5
100
150
175
35
110
150
175
35
120
(10)
18
24
34
54
-
18
24
34
54
-
13.5
18
25.5
40.6
-
2
2
2
2
-
2
2
2
2
-
2
2
2
2
-
21.7
28.9
40.9
65.0
-
17.3
23.1
32.7
52.0
-
37.5
50.0
70.8
112.7
-
40
50
70
45
60
70
460 7.4
55
43
11.5
8.7
36
90
25
35
90
30
35
24.9
33.8
41
575 5.6
3.9
4
40
60
70
45
60
70
53
64.1
96.7
96.7
100.8
126.9
179.2
96.7
96.7
110.5
140.6
168.3
48.7
48.7
54.6
69.6
83.5
36.7
36.7
43.7
55.8
66.8
110
110
110
125
175
110
110
110
150
175
50
110
110
110
150
200
110
110
125
150
175
60
208 23.1 160
15.2
15.2
7.6
10
10
5
18
24
34
54
-
18
24
34
54
-
2
2
2
2
-
2
2
2
2
-
43.3
57.7
81.8
129.9
-
21.7
28.9
40.9
65.0
-
230 23.1 160
36
150
(12.5)
50
60
460 12.2
87
62
19
60
70
90
60
70
90
40
40
45
45
45
45
18
24
34
54
2
2
2
2
17.3
23.1
32.7
52.0
575 8.7
13.5
6.1
4
60
70
60
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
Johnson Controls Unitary Products
43
528194-YTG-F-1210
Typical ZF078-120 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
Johnson Controls Unitary Products
45
528194-YTG-F-1210
Typical ZF078-120 Cooling Unit with/without Electric Heat Wiring
46
Johnson Controls Unitary Products
528194-YTG-F-1210
Typical ZF150 Cooling Unit with Gas Heat 230 Volt Wiring Diagram
Johnson Controls Unitary Products
47
528194-YTG-F-1210
Typical ZF150 Cooling Unit with Gas Heat 460/575 Volt Wiring Diagram
48
Johnson Controls Unitary Products
528194-YTG-F-1210
Typical ZF150 Cooling Unit with/without Electric Heat Wiring Diagram
Johnson Controls Unitary Products
49
528194-YTG-F-1210
Typical ZF078-150 Factory Installed VFD (Option)
50
Johnson Controls Unitary Products
528194-YTG-F-1210
Typical ZF078-150 Factory Installed VFD with Manual Bypass (Option)
Johnson Controls Unitary Products
51
528194-YTG-F-1210
Typical ZF078-150 Factory Installed VFD with CCS Control (Option)
52
Johnson Controls Unitary Products
528194-YTG-F-1210
Typical ZF078-150 Factory Installed VFD and Manual Bypass with CCS Control (Option)
Johnson Controls Unitary Products
53
528194-YTG-F-1210
Typical ZF078-150 BAS Ready Unit with Factory Installed VFD (Option)
54
Johnson Controls Unitary Products
528194-YTG-F-1210
Typical ZF078-150 BAS Ready Unit with Factory Installed VFD and Manual Bypass (Option)
Johnson Controls Unitary Products
55
528194-YTG-F-1210
Typical ZF078-150 VFD Ready Unit (Option)
56
Johnson Controls Unitary Products
528194-YTG-F-1210
Weights and Dimensions
ZF078-150 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
D
FRONT
LEFT
LEFT
C
B
C
B
A
A
E
F
D
Y
X
FRONT
LEFT
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
Weight (lbs.)
Shipping Operating
Center of Gravity
4 Point Load Location (lbs.)
6 Point Load Location (lbs.)
Model
ZF
X
Y
A
B
C
D
A
B
C
D
E
F
865
885
860
860
38
24
200
149
218
292
140
114
95
138
167
205
ZF
38
38
38
47
24
24
24
25
205
238
247
251
153
177
184
280
223
258
268
381
299
347
360
341
144
167
173
164
117
136
141
176
97
142
164
171
259
171
198
206
240
210
243
253
223
ZF
1025
1065
1258
1020
1060
1253
113
117
190
ZF
(10)
150
(12.5)
ZF
Johnson Controls Unitary Products
57
528194-YTG-F-1210
ZF078-150 Unit Accessory Weights
Unit Accessory
Weight (lbs.)
Shipping
Operating
Economizer
Power Exhaust
90
40
49
110
30
85
35
49
110
30
Electric Heat1
Gas Heat2
Variable Frequency Drive3
1. Weight given is for the maximum heater size available
(54KW).
2. Weight given is for the maximum number of tube heat
exchangers available (8 tube).
3. Weight includes mounting hardware, controls and manual
bypass option (ZF Only).
ZF078-150 Unit Dimensions
ZF078 - 120
29.69
15.25
15.38
59.00
15.38
Ø 24.47 TYP. 2 PL.
B
See detail A for gas inlet
A
C
D
E
11 3/8
F
See detail B for drain location
LEFT
59
4 3/16
FRONT
89
21 3/16
27 5/16
58
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF150
29.95
30.11
45.64
14.92
14.92
58.09
14.92
Ø 24.47 TYP. 4 PL.
B
See detail A for gas inlet
A
C
D
E
11 3/8
F
See detail B for drain location
LEFT
4 3/16
21 3/16
FRONT
59
27 5/16
89
ZF078-150 Unit Physical Dimensions
Unit Model Number
Dimension (in.)
C
A
B
D
E
F
078
090
102
120
150
42
42
50 3/4
50 3/4
50 3/4
89
89
89
89
119 1/2
22 1/8
22 1/8
30 3/16
30 3/16
30 3/16
18 3/16
18 3/16
24 3/16
24 3/16
24 3/16
15 3/16
15 3/16
17 3/16
17 3/16
17 3/16
6 3/16
6 3/16
6 3/16
6 3/16
6 3/16
Johnson Controls Unitary Products
59
528194-YTG-F-1210
Detail A
3.184
3.184
Gas Pipe Inlet
Gas Pipe Inlet
Ø 2.000
Ø 2.000
Gas Exhaust Vent
Gas Exhaust Vent
Ø 3.126
Ø 3.126
17.541
14.594
7.715
7.705
4.737
4.727
42” CABINET
50 3/4” CABINET
Detail B
5-3/8
3/4” FPT
ZF078-150 Unit Clearances
Direction
Top1
Distance (in.)
Direction
Distance (in.)
72
36
36
Right
Left
Bottom2
12
36
0
Front
Rear
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
60
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Unit Bottom Duct Openin
89
32 11/16
6 13/16
6 13/16
SUPPLY
AIR
RETURN
AIR
24
27 1/2
18
LEFT
21
RIGHT
20 1/8
19 1/8
17 1/8
12 5/16
Bottom condensate drain
14 1/2
25 9/16
Bottom gas
supply entry
16 3/8
18 1/16
FRONT
TOP VIEW
Bottom power, control
and convenience outlet
wiring entry
3X Ø 0.875
Ø 2.469
Johnson Controls Unitary Products
61
528194-YTG-F-1210
ZF078-150 Unit Electrical Entry
Disconnect Swith Cover
Power Entry Ø 2-1/2
Control Entry Ø 7/8
Power Entry Ø 2-1/2
Convenience Outlet Cover
Convenience Outlet
Power Entry Ø 7/8
FRONT
ZF078-120 Unit Side Duct Openings
18-1/4
Dot Plugs
A
Return
Air
Supply Air
D
B
2-31/32
5-5/32
C
31-11/16
62
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF150 Unit Side Duct Openings
Dot Plugs
18-1/4
A
B
D
5-5/32
2-7/8
C
31-5/8
ZF Side Duct Dimensions
Dimension (in.)
Unit Model Number
A
B
C
D
078
090
102
120
150
27 3/4
27 3/4
28 1/4
28 1/4
28 1/4
12 1/16
12 1/16
18 1/16
18 1/16
18 1/16
27 1/2
27 1/2
28 1/4
28 1/4
28 1/4
16
16
18 1/4
18 1/4
18 1/4
ZF078-150 Unit Left Duct Opening
30-3/8
4-5/16
Johnson Controls Unitary Products
63
528194-YTG-F-1210
ZF078-150 Unit Accessory Dimensions
ZF078-150 Roof Curb
RIGHT
80-5/8
20
INSULATED DECK UNDER
CONDENSER SECTION
SUPPLY
20
6
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
FRONT
8 or 14
ZF078-150 Transition Roof Curb
2 TYP
4
23
30-1/2
50-1/2
80-5/8
26
RETURN
SUPPLY
10
76-5/8
94
59-1/4
64-1/4
FRONT
RIGHT
64
Johnson Controls Unitary Products
528194-YTG-F-1210
ZF078-150 Economizer Assembly
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
Relief Hood for
Power Exhaust or
Barometric Relief
26
25 3/4
26
30 1/4
Johnson Controls Unitary Products
65
528194-YTG-F-1210
Economizer Options
Economizer Usage
Application
Bottom Return
Side Return
Cabinet Height
Description
Model
All
All
Downflow economizer with barometric relief
Horizontal economizer without barometric relief
Slab Economizer, 42” tall cabinet
2EE04705924
2EE047060241
2EE047058242
2EE047057242
42"
50"
ERV or End Return
Slab Economizer, 50” tall cabinet
1. Barometric relief must be ordered seperately and installed in duct work.
2. Barometric relief or fresh air hood not included. Must be ordered seperately.
Factory Installed Downflow Economizer
2EE04705924
2EE04705924
2EE04705924
2EE04705924
Barometric Relief Damper
2EE04705924
Barometric Relief Hood
Fresh Air Hood Fresh Air Damper Return Air Damper
Field Installed Downflow Economizer W/Power Exhaust
2EE04705924
Fresh Air Hood
2EE04705924
2EE04705924
2PE047032XX
Power Exhaust
2EE04705924
Fresh Air Damper Return Air Damper
2EE04705924
Barometric Relief Hood
Barometric Relief Damper
66
Johnson Controls Unitary Products
528194-YTG-F-1210
Field Installed Horizontal Economizer W/Power Exhaust
2EE04706024
Return Air Damper
Field Installed
Duct Work
2EE04706024
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04706024
Fresh Air Hood
Slab Economizer Downflow W/Power Exhaust
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
1EH0409 Barometric
Relief Hood
Johnson Controls Unitary Products
67
Slab Economizer End Return W/Power Exhaust
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
2PE047032XX
Power Exhaust
1EH0409
Barometric Relief Damper
Subject to change without notice. Printed in U.S.A.
Copyright © 2011 by Johnson Controls, Inc. All rights reserved.
528194-YTG-F-1210
Supersedes: 528194-YTG-E-0810
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
|
Lifebreath 200max User Manual
Motorola Battery Charger Wpln4116 User Manual
Philips 5375cb User Manual
Ridgid 140276002 User Manual
Roper Air Conditioner User Manual
Soleus Air Gh Pac 12e1 User Manual
Soleus Air Kfihp 09 Id User Manual
Stoptech Automobile Parts 98 180 1470 User Manual
Summer Infant 02134a User Manual
York Air Conditioner Ycjd18 Thru 60 User Manual