York 036 21103 003 User Manual

036-21103-003 Rev. A (0403)  
DESCRIPTION  
®
The HRA Series condensing unit is the outdoor part of a ver-  
satile system of air conditioning. It is designed to be custom  
matched with one of UPG’s complete line of evaporator sec-  
tions, each designed to serve a specific function. Matching  
Air Handlers are available for upflow, downflow or horizontal  
applications to provide a complete system. Electric Heaters  
are available if required. Add-On coils are available for use  
with upflow, downflow or horizontal furnaces and air handlers.  
TECHNICAL GUIDE  
FEATURES  
QUALITY CONDENSER COILS - The coil is constructed  
of enhanced copper tube and aluminum fins.  
SPLIT-SYSTEM AIR CONDITIONERS  
10 SEER 50 HZ  
COIL PROTECTION - Coils are protected from damage by  
a polymer mesh applied between the coil face, and a PVC  
coated steel coil guard.  
H*RA018S78 THRU H*RA036S78 (1 PH)  
H*RA036S50 THRU H*RA060S50 (3PH)  
PROTECTED COMPRESSOR - The compressor is inter-  
nally protected against high pressure and temperature.  
This is accomplished by the simultaneous operation of  
high pressure relief valve and a temperature sensor which  
protects the compressor if undesirable operating condi-  
tions occur. A liquid line filter-drier further protects the  
compressor.  
(1.5 THRU 5 NOMINAL TONS)  
DURABLE FINISH - Cabinet is made of pre-painted steel.  
The pre-treated flat galvanized steel provides a better  
paint to steel bond, which resists corrosion and rust creep.  
Special primer formulas and matted-textured finish insure  
less fading when exposed to sunlight.  
LOWER INSTALLED COST - Installation time and costs  
are reduced by easy power and control wiring connections.  
Discharge line heat exchanger knockouts are provided, if  
required. Available in sweat connect models only. The unit  
contains enough refrigerant for matching indoor coils and  
15 feet of interconnecting piping. The small base dimen-  
sion means less space is required on the ground or roof.  
TOP DISCHARGE - The warm air from the top mounted  
fan is blown up away from the structure and any landscap-  
ing. This allows compact location on multi-unit applica-  
tions.  
LOW OPERATING SOUND LEVEL - The upward air flow  
carries the normal operating noise up away from the living  
area. The rigid top panel effectively isolates any motor  
sound. Isolator mounted compressor and the rippled fins of  
the condenser coil muffle the normal fan motor and com-  
pressor operating sounds.  
LOW MAINTENANCE - Long life permanently lubricated  
motor-bearings need no annual servicing.  
Due to continuous product improvement, specifications  
are subject to change without notice.  
EASY SERVICE ACCESS - Fully exposed refrigerant con-  
nections, a single panel covering the electrical controls  
and the molex plug in the control box connecting the con-  
denser fan, make for easy servicing of the unit.  
up-to-date technical information.  
SECURED SERVICE VALVES - Secured re-usable ser-  
vice valves are provided on both the liquid and vapor  
sweat connections for ease of evacuating and charging.  
FACTORY TESTED - to verify system operation and con-  
trol functioning before shipment.  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
036-21103-003 Rev. A (0403)  
Additional R-22 Charge / Orifice Size for Various Matched Systems - 1 & 3 Phase  
Additional R-22 Charge / Orifice Size for Various Matched Systems  
Outdoor Unit (H1RA)  
018S78  
51  
024S78  
57  
030S78  
69  
036S78  
71  
036S50  
71  
048S50  
84  
060S50  
1
Unit Orifice(s)  
Factory R-22 Charge, lbs-oz  
3 - 13  
3 - 14  
3 - 14  
4 - 11  
4 - 11  
7 - 10  
9 - 12  
2
Indoor Coil  
System Orifice + Additional Charge, Oz  
Coil Orifice  
G2FD024S14,17  
G2FD030S17  
G2FD036S17  
G2FD036S21  
G2FD042S21  
G2FD048S21,24  
G2FD060S24  
61  
65  
75  
75  
78  
78  
90  
51 + 0  
57 + 0  
69 + 0  
69 + 3  
71 + 0  
71 + 2  
71 + 0  
71 + 2  
71 + 4  
84 + 0  
90 + 0  
COOLING CAPACITY - With Air Handler Coils  
AIR HANDLER  
COOLING  
3
COIL  
UNIT MODEL  
2
NET MBH  
RATED  
CFM  
MODEL  
ELECTRIC  
1
MODEL  
W
KW SEER  
EER  
SEER/TXV  
HEAT KW  
TOTAL SENS.  
1 PHASE HRA / NAH  
H1RA018S78 N1AHB1293  
H1RA024S78 N1AHB1293  
5,8,10,15,18  
5,8,10,15,18  
5,8,10,15,18  
5,8,10,15,18  
5,8,10,15,18  
17  
17  
17  
17  
17  
G2FD024S17  
G2FD030S17  
G2FD030S17  
G2FD036S17  
G2FD036S17  
650  
18.1  
23.4  
28.9  
29.6  
33.5  
12.9  
16.8  
20.0  
20.6  
25.2  
1.86  
2.87  
3.45  
3.57  
3.83  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
850  
N1AHB1293  
H1RA030S78  
1000  
1000  
1250  
N1AHB1293  
H1RA036S78 N1AHB1293  
3 PHASE HRA / NAH  
N1AHB1293  
H1RA036S50 N1AHB1293  
N1AHC1693  
5,8,10,15,18  
5,8,10,15,18  
5,8,10,15,20  
5,8,10,15,18  
5,8,10,15,18  
17  
17  
21  
21  
24  
G2FD036S17  
G2FD036S21  
G2FD042S21  
G2FD048S21  
G2FD060S24  
1200  
33.6  
34.4  
35.1  
48.8  
60.5  
24.9  
25.5  
25.9  
35.9  
43.0  
3.81  
3.87  
3.93  
4.82  
6.29  
--  
--  
--  
1200  
1250  
1600  
1900  
H1RA048S50 N1AHC1693  
H1RA060S50 N1AHD2093  
--  
--  
--  
--  
--  
--  
1 PHASE HRA / FRP (SINGLE PHASE)  
H1RA018S78 F2RP024N93  
H1RA024S78 F2RP024N93  
H1RA030S78 F2RP036N93  
H1RA036S78 F2RP036N93  
5,7.5,10  
5,7.5,10  
18  
18  
21  
21  
--  
--  
--  
--  
650  
850  
18.1  
23.4  
29.6  
34.3  
12.9  
16.8  
20.6  
25.6  
1.86  
2.87  
3.57  
3.86  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
5,7.5,10,15  
5,7.5,10,15  
1000  
1250  
3 PHASE HRA / FRP (SINGLE PHASE)  
H1RA036S50 F2RP036N93  
H1RA048S50 F2RP048N93  
H1RA060S50 F2RP060N93  
10,15  
10,15  
10,15  
21  
24  
24  
--  
--  
--  
1200  
1600  
1900  
34.4  
48.8  
60.5  
25.5  
35.9  
43.0  
3.87  
4.82  
6.29  
--  
--  
--  
--  
--  
--  
--  
--  
--  
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.  
KW includes compressor, outdoor fan and indoor blower motor watts. Add-on coils include 365 watts/1000 CFM for blower motor.  
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at a 95°F outdoor ambient divided by the total electric power in watt-hours at  
those conditions.  
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the  
total electric power  
input in watt-hours during the same period.  
1.  
TXV = Thermal Expansion Valve kit required. Use 1TV700 series kit.  
Single phase units require single phase 2HK heaters — Three phase units require three phase 2HK heaters. (29) indicates 460 volt use only.  
G2FD coils available with a factory installed horizontal drain pan. Replace “S” with “H” in the model number.  
2.  
3.  
— = Not Applicable.  
Unitary Products Group  
3
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE  
AIR TEMP ON CONDENSER  
95°F 115°F  
SUCT. T/P  
@ COMPR.  
MODEL  
75°F  
125°F  
TEMP.  
PSIG  
61.5  
68.5  
76.0  
84.0  
61.5  
68.5  
76.0  
84.0  
61.5  
68.5  
76.0  
84.0  
61.5  
68.5  
76.0  
84.0  
61.5  
68.5  
76.0  
84.0  
61.5  
68.5  
76.0  
84.0  
61.5  
68.5  
76.0  
84.0  
MBH  
13.1  
14.8  
16.5  
18.4  
21.3  
24.1  
26.7  
29.6  
28.0  
31.5  
35.1  
38.9  
30.6  
34.4  
38.3  
38.9  
29.6  
33.2  
36.9  
40.7  
43.2  
48.1  
53.2  
58.4  
50.6  
55.6  
60.9  
66.3  
KW  
1.36  
1.42  
1.48  
1.55  
1.59  
1.68  
1.77  
1.85  
2.31  
2.44  
2.52  
2.62  
3.14  
3.28  
3.42  
2.62  
3.24  
3.37  
3.51  
3.65  
4.17  
4.37  
4.58  
4.79  
5.23  
5.37  
5.48  
5.58  
MBH  
13.1  
14.8  
16.5  
18.4  
17.7  
20.1  
22.3  
24.9  
24.4  
27.5  
30.7  
34.2  
27.0  
30.4  
33.9  
34.2  
27.8  
31.2  
34.7  
38.2  
39.1  
43.6  
48.3  
53.2  
48.7  
54.1  
59.7  
65.6  
KW  
1.36  
1.42  
1.48  
1.55  
1.93  
2.04  
2.16  
2.27  
2.65  
2.78  
2.91  
3.04  
3.48  
3.64  
3.81  
3.04  
3.52  
3.68  
3.84  
4.00  
4.87  
5.11  
5.35  
5.60  
5.73  
5.97  
6.19  
6.40  
MBH  
10.6  
12.8  
13.7  
15.2  
14.7  
16.7  
18.9  
21.1  
20.1  
22.8  
25.9  
28.8  
23.1  
26.1  
29.1  
28.8  
25.1  
28.2  
31.4  
34.6  
34.4  
38.5  
42.8  
47.2  
45.2  
50.8  
56.7  
62.8  
KW  
1.46  
1.55  
1.62  
1.71  
2.14  
2.27  
2.40  
2.55  
2.86  
3.02  
3.17  
3.34  
3.79  
3.98  
4.17  
3.34  
3.73  
3.91  
4.10  
4.28  
5.50  
5.80  
6.11  
6.41  
6.11  
6.44  
6.76  
7.08  
MBH  
9.3  
KW  
1.52  
1.61  
1.69  
1.78  
2.23  
2.38  
2.53  
2.67  
2.96  
3.31  
3.48  
3.48  
3.89  
4.10  
4.30  
3.48  
3.78  
3.97  
4.16  
4.36  
5.87  
6.22  
6.57  
6.91  
6.24  
6.61  
6.98  
7.35  
35  
40  
45  
50  
35  
40  
45  
50  
35  
40  
45  
50  
35  
40  
45  
50  
35  
40  
45  
50  
35  
40  
45  
50  
35  
40  
45  
50  
10.6  
12.2  
13.7  
13.3  
15.1  
17.1  
19.4  
18.0  
23.4  
23.4  
26.3  
21.0  
23.7  
26.6  
26.3  
23.4  
26.4  
29.3  
32.4  
31.9  
35.8  
39.8  
44.0  
42.7  
48.4  
54.5  
60.8  
H1RA018S78  
H1RA024S78  
H1RA030S78  
H1RA036S78  
H1RA036S50  
H1RA048S50  
H1RA060S50  
1.For condensing unit only. Does not include effect of evaporator motor power or heat.  
2.Performance based on 15” superheat and 15" sub-cooling at condensing unit.  
a.Increase capacity 1% for each 2...increase in sub-cooling.  
b.Decrease capacity 1% for each 2 decrease in sub-cooling.  
3.Sub-cooling in excess of 20...may result in excessively high condensing temperature with air on condenser above 115° Maximum recommended condensing  
temperature is 140..F.  
4
Unitary Products Group  
036-21103-003 Rev. A (0403)  
ACCESSORIES  
Refer to Price Manual for specific model numbers.  
SOUND RATINGS  
Compressor Blanket - Designed to further reduce the nor-  
mal operating sound.  
SOUND  
RATINGS  
DECIBELS  
UNIT MODEL  
Hard Start Kit (Single Phase Units) - provides required  
starting torque for use with thermal expansion valve.  
018  
024  
030  
036  
048  
060  
76  
78  
82  
82  
82  
80  
Outdoor Thermostat - 2TD06700124 - Consists of an  
adjustable outdoor thermostat and relay in a vented enclo-  
sure. It provides additional second stage control of the sup-  
plemental resistance heat.(Balance Point Control)  
TYPICAL INSTALLATION - H*RA018S78 THRU 036S78 (1 PH) & H*RA 036S50 THRU 060S50 (3 PH)  
MINIMUM 18” SERVICE ACCESS  
CLEARANCE ON ONE SIDE  
THERMOSTAT  
TO FURNACE OR  
AIR HANDLER  
TERMINAL BLOCK  
60” OVERHEAD  
CLEARANCE  
WEATHERPROOF  
DISCONNECT  
SWITCH  
NEC CLASS 1 WIRING  
NEC CLASS 2 WIRING  
10” CLEARANCE  
COIL AREA  
TO INDOOR COIL  
SEAL OPENING(S) WITH  
PERMAGUM OR EQUIVALENT  
NOTE: ALL OUTDOOR WIRING MUST  
BE WEATHERPROOF.  
CONTROL ACCESS PANEL  
Unitary Products Group  
5
036-21103-003 Rev. A (0403)  
TYPICAL FIELD WIRING - 1 PH APPLICATION (018S78 - 036S78)  
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES  
POWER WIRING  
POWER WIRING  
230-1-50  
24 VOLT CONTROL WIRING  
MINIMUM 18 GA. WIRE  
(NEC CLASS 2)  
CONTROL WIRING  
FACTORY WIRING  
FURNACE OR AIR HANDLER TERMINAL BLOCK  
*
TERMINAL W IS ONLY  
REQUIRED ON SYSTEMS  
WITH HEAT.  
C
Y
R
G
W
CONTACTOR  
TERMINALS  
GND.  
LUG  
*
COIL  
Y
R
G
W
ROOM THERMOSTAT  
CONDENSING UNIT  
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.  
TYPICAL FIELD WIRING - 3 PH APPLICATION (036S50 - 060S50)  
ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES  
POWER WIRING  
380/415-3-50  
POWER WIRING  
24 VOLT CONTROL WIRING  
MINIMUM 18 GA. WIRE  
(NEC CLASS 2)  
CONTROL WIRING  
FACTORY WIRING  
FURNACE OR AIR HANDLER TERMINAL BLOCK  
C
Y
R
G
W
*
TERMINAL W IS ONLY  
REQUIRED ON SYSTEMS  
WITH HEAT.  
CONTACTOR  
TERMINALS  
GND.  
LUG  
*
COIL  
Y
R
G
W
ROOM THERMOSTAT  
CONDENSING UNIT  
ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY.  
6
Unitary Products Group  
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA018S78A  
G2FD024S17  
IDCFM  
500  
650  
80  
800  
CONDENSING  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
80  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
18.3  
10.6  
1.55  
17.8  
10.6  
1.76  
17.3  
10.6  
1.79  
16.0  
10.0  
1.99  
14.6  
9.4  
18.1  
10.8  
1.55  
17.2  
10.7  
1.74  
16.3  
10.5  
1.75  
14.7  
10.0  
1.94  
13.1  
9.5  
16.5  
10.5  
1.53  
15.4  
10.2  
0.95  
14.2  
9.8  
18.4  
11.0  
1.71  
18.0  
11.3  
1.95  
17.6  
11.6  
1.95  
16.5  
11.4  
2.19  
15.3  
11.2  
2.18  
13.7  
11.1  
2.28  
18.2  
11.6  
1.71  
17.5  
11.7  
1.93  
16.8  
11.8  
1.92  
15.3  
11.4  
2.14  
13.8  
11.0  
2.12  
11.6  
10.0  
2.21  
17.2  
11.9  
1.69  
16.1  
11.6  
1.90  
15.0  
11.4  
1.88  
13.3  
10.7  
2.09  
11.7  
10.0  
2.07  
9.9  
18.4  
11.4  
1.68  
18.2  
12.0  
1.95  
17.9  
12.5  
1.92  
17.0  
12.7  
2.19  
16.0  
12.9  
2.16  
14.3  
12.7  
2.26  
18.3  
12.4  
1.67  
17.8  
12.8  
1.93  
17.3  
13.1  
1.89  
15.9  
12.8  
2.14  
14.4  
12.5  
2.10  
12.1  
11.5  
2.19  
17.8  
13.3  
1.66  
16.8  
13.1  
1.90  
15.8  
12.9  
1.85  
14.1  
12.2  
2.09  
12.3  
11.5  
2.04  
10.4  
10.6  
2.13  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
1.71  
12.6  
9.2  
T.C.  
105  
115  
125  
S.C.  
K.W  
1.90  
11.0  
8.5  
T.C.  
S.C.  
K.W  
2.01  
13.0  
9.4  
1.94  
11.1  
8.5  
1.90  
9.3  
T.C.  
S.C.  
7.8  
9.2  
K.W  
2.11  
2.04  
1.98  
2.15  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
N1AHB1293  
F2RP024N93  
Coil  
G2FD024S17  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
Unitary Products Group  
7
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA024S78A  
G2FD030S17  
IDCFM  
650  
850  
80  
1050  
80  
CONDENSER  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
26.4  
15.4  
2.15  
25.4  
15.3  
2.31  
24.4  
15.3  
2.47  
22.5  
14.7  
2.62  
20.6  
14.2  
2.76  
17.8  
13.3  
2.89  
25.3  
15.6  
2.11  
23.9  
15.1  
2.26  
22.5  
14.6  
2.40  
20.1  
13.8  
2.53  
17.7  
13.0  
2.65  
15.2  
12.4  
2.78  
24.0  
15.4  
2.08  
21.8  
14.4  
1.16  
19.6  
13.4  
2.31  
17.6  
12.7  
2.44  
15.6  
11.9  
2.56  
13.3  
11.4  
2.69  
26.6  
16.2  
2.17  
25.7  
16.4  
2.33  
24.9  
16.6  
2.50  
23.2  
16.4  
2.66  
21.5  
16.3  
2.81  
18.7  
15.4  
2.94  
25.7  
16.7  
2.13  
24.6  
16.6  
2.28  
23.4  
16.6  
2.44  
21.1  
15.9  
2.57  
18.8  
15.2  
2.70  
15.9  
14.3  
2.82  
24.6  
16.8  
2.10  
22.8  
16.2  
2.23  
20.9  
15.7  
2.35  
18.6  
14.7  
2.47  
16.3  
13.8  
2.59  
14.0  
13.1  
2.72  
26.7  
16.9  
2.18  
26.1  
17.4  
2.36  
25.4  
17.9  
2.53  
23.9  
18.1  
2.70  
22.4  
18.3  
2.86  
19.5  
17.4  
2.99  
26.1  
17.8  
2.15  
25.2  
18.2  
2.31  
24.3  
18.5  
2.47  
22.1  
17.9  
2.61  
19.8  
17.3  
2.74  
16.7  
16.1  
2.85  
25.2  
18.2  
2.12  
23.7  
18.1  
2.26  
22.2  
17.9  
2.39  
19.6  
16.8  
2.51  
16.9  
15.6  
2.62  
14.7  
14.7  
2.75  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
T.C.  
105  
115  
125  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
N1AHB1293  
F2RP024N93  
Coil  
G2FD030S17  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
8
Unitary Products Group  
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA030S78A  
G2FD030S17  
IDCFM  
650  
850  
80  
1050  
CONDENSER  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
80  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
26.4  
15.4  
2.39  
25.4  
15.3  
2.67  
24.4  
15.3  
2.71  
22.5  
14.7  
2.98  
20.6  
14.2  
3.00  
17.8  
13.3  
3.13  
25.3  
15.6  
2.35  
23.9  
15.1  
2.62  
22.5  
14.6  
2.64  
20.1  
13.8  
2.89  
17.7  
13.0  
2.88  
15.2  
12.4  
3.02  
24.0  
15.4  
2.32  
21.8  
14.4  
1.40  
19.6  
13.4  
2.55  
17.6  
12.7  
2.80  
15.6  
11.9  
2.80  
13.3  
11.4  
2.93  
26.6  
16.2  
2.53  
25.7  
16.4  
2.82  
24.9  
16.6  
2.86  
23.2  
16.4  
3.14  
21.5  
16.3  
3.17  
18.7  
15.4  
3.30  
25.7  
16.7  
2.49  
24.6  
16.6  
2.76  
23.4  
16.6  
2.80  
21.1  
15.9  
3.05  
18.8  
15.2  
3.05  
15.9  
14.3  
3.18  
24.6  
16.8  
2.46  
22.8  
16.2  
2.71  
20.9  
15.7  
2.71  
18.6  
14.7  
2.95  
16.3  
13.8  
2.95  
14.0  
13.1  
3.08  
26.7  
16.9  
2.56  
26.1  
17.4  
2.93  
25.4  
17.9  
2.91  
23.9  
18.1  
3.27  
22.4  
18.3  
3.24  
19.5  
17.4  
3.37  
26.1  
17.8  
2.53  
25.2  
18.2  
2.88  
24.3  
18.5  
2.85  
22.1  
17.9  
3.18  
19.8  
17.3  
3.12  
16.7  
16.1  
3.23  
25.2  
18.2  
2.50  
23.7  
18.1  
2.83  
22.2  
17.9  
2.77  
19.6  
16.8  
3.08  
16.9  
15.6  
3.00  
14.7  
14.7  
3.13  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
T.C.  
105  
115  
125  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
N1AHB1293  
N1AHB1293  
F2RP036N93  
Coil  
G2FD030S17  
G2FD036S17  
1.00  
1.02  
1.02  
1.00  
1.03  
1.03  
1.00  
1.03  
1.03  
Unitary Products Group  
9
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA036S50A  
G2FD036S17  
IDCFM  
1100  
1250  
80  
1400  
80  
CONDENSER  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
38.6  
26.0  
3.20  
36.4  
24.8  
3.56  
34.2  
23.6  
3.52  
31.9  
22.5  
3.88  
29.7  
21.3  
3.84  
27.6  
20.6  
3.92  
36.0  
25.7  
3.12  
33.7  
24.5  
3.48  
31.3  
23.3  
3.44  
29.0  
22.2  
3.80  
26.6  
21.0  
3.76  
24.3  
20.0  
3.92  
33.4  
25.3  
3.04  
31.0  
24.2  
1.88  
28.5  
23.0  
3.36  
26.0  
21.9  
3.72  
23.5  
20.7  
3.68  
21.0  
19.4  
3.92  
39.0  
25.8  
3.30  
36.9  
25.2  
3.75  
34.8  
24.5  
3.74  
32.8  
23.9  
4.19  
30.7  
23.2  
4.18  
28.1  
22.7  
4.38  
36.4  
26.4  
3.34  
34.2  
25.5  
3.75  
31.9  
24.6  
3.70  
29.6  
23.7  
4.11  
27.4  
22.8  
4.06  
24.9  
21.6  
4.26  
33.9  
27.1  
3.38  
31.4  
25.9  
3.75  
28.9  
24.7  
3.66  
26.5  
23.5  
4.03  
24.0  
22.3  
3.94  
21.7  
20.5  
4.14  
39.4  
25.6  
2.99  
37.5  
25.5  
3.53  
35.5  
25.4  
3.55  
33.6  
25.3  
4.09  
31.7  
25.2  
4.11  
28.6  
24.8  
4.43  
36.8  
27.2  
3.15  
34.7  
26.5  
3.61  
32.5  
25.9  
3.55  
30.3  
25.2  
4.01  
28.1  
24.5  
3.95  
25.5  
23.2  
4.19  
34.3  
28.8  
3.31  
31.9  
27.5  
3.69  
29.4  
26.3  
3.55  
27.0  
25.1  
3.93  
24.5  
23.9  
3.79  
22.4  
21.7  
3.95  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
T.C.  
105  
115  
125  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
NAHB1293  
NAHB1293  
NAHC1693  
F2RP036N93  
Coil  
G2FD036S17  
G2FD036S21  
G2FD042S21  
1.00  
1.02  
1.04  
1.02  
1.00  
1.02  
1.04  
1.02  
1.00  
1.02  
1.03  
1.02  
10  
Unitary Products Group  
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA036S78A  
G2FD036S17  
IDCFM  
1050  
1250  
80  
1450  
CONDENSER  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
80  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
38.7  
23.4  
3.30  
37.4  
23.5  
3.74  
36.0  
23.6  
3.80  
32.6  
22.6  
4.17  
29.2  
21.5  
4.16  
25.5  
20.3  
4.29  
36.8  
23.5  
3.25  
34.8  
24.0  
3.65  
32.7  
24.5  
3.67  
29.1  
22.1  
4.00  
25.5  
19.6  
3.95  
22.4  
18.8  
4.12  
35.0  
23.4  
3.21  
31.9  
22.2  
1.95  
28.7  
21.0  
3.51  
25.5  
19.6  
3.85  
22.3  
18.2  
3.81  
19.6  
17.4  
3.99  
39.1  
24.4  
3.59  
37.7  
24.7  
4.06  
36.4  
25.0  
4.09  
33.2  
24.3  
4.53  
30.1  
23.6  
4.50  
26.2  
22.3  
4.65  
34.7  
24.8  
3.54  
34.1  
25.2  
4.00  
33.5  
25.6  
3.99  
29.9  
23.6  
4.36  
26.3  
21.6  
4.27  
22.8  
20.5  
4.43  
35.6  
24.8  
3.50  
32.6  
23.9  
3.90  
29.6  
22.9  
3.83  
26.3  
21.5  
4.21  
23.1  
20.0  
4.12  
20.0  
18.9  
4.29  
39.4  
25.4  
3.48  
38.1  
25.9  
4.00  
36.7  
26.4  
3.99  
33.9  
26.1  
4.49  
31.0  
25.7  
4.45  
26.9  
24.3  
4.61  
32.5  
26.1  
3.43  
33.4  
26.4  
3.94  
34.3  
26.7  
3.92  
30.7  
25.2  
4.32  
27.0  
23.6  
4.19  
23.1  
22.2  
4.35  
36.2  
26.2  
3.39  
33.4  
25.5  
3.84  
30.5  
24.8  
3.76  
27.2  
23.3  
4.17  
23.8  
21.8  
4.04  
20.4  
20.3  
4.20  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
T.C.  
105  
115  
125  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
N1AHB1293  
F2RP036N93  
Coil  
G2FD036S17  
1.00  
1.02  
1.00  
1.02  
1.00  
1.01  
Unitary Products Group  
11  
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA048S50A  
G2FD048S21  
IDCFM  
1400  
1450  
80  
1500  
80  
CONDENSER  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
66.1  
34.2  
4.49  
58.8  
33.2  
4.93  
51.5  
32.1  
5.36  
44.2  
31.1  
5.82  
36.9  
30.1  
5.76  
39.5  
28.2  
6.11  
57.0  
34.3  
4.83  
51.6  
33.1  
5.03  
46.3  
31.9  
5.22  
40.9  
30.7  
5.67  
35.6  
29.5  
5.61  
35.3  
27.9  
5.93  
47.9  
34.3  
4.70  
44.5  
32.9  
4.80  
41.1  
31.6  
5.08  
37.7  
30.2  
5.53  
34.3  
28.9  
5.46  
31.1  
27.5  
5.75  
63.5  
34.7  
4.99  
57.7  
33.9  
5.60  
51.8  
33.1  
5.67  
45.9  
32.4  
6.16  
40.0  
31.6  
6.12  
39.6  
27.1  
6.43  
55.8  
35.1  
5.09  
51.2  
34.0  
5.57  
46.6  
32.9  
5.51  
42.0  
31.7  
5.99  
37.4  
30.6  
5.93  
35.4  
28.8  
6.23  
48.1  
35.6  
4.96  
44.7  
34.1  
5.42  
41.4  
32.6  
5.35  
38.0  
31.1  
5.81  
34.7  
29.6  
5.75  
31.3  
30.5  
6.03  
61.0  
35.1  
4.98  
56.5  
34.6  
5.50  
52.1  
34.1  
5.47  
47.6  
33.6  
5.99  
43.1  
33.1  
5.96  
39.7  
25.9  
6.23  
54.6  
36.0  
4.84  
50.8  
34.9  
5.34  
46.9  
33.8  
5.29  
43.0  
32.8  
5.79  
39.1  
31.7  
5.74  
35.6  
29.7  
6.01  
48.3  
36.8  
4.70  
45.0  
35.2  
5.18  
41.7  
33.6  
5.11  
38.4  
32.0  
5.59  
35.1  
30.3  
5.52  
31.6  
33.6  
5.79  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
T.C.  
105  
115  
125  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
NAHC1693  
Coil  
G2FD048S21  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
F2RP048N93  
12  
Unitary Products Group  
036-21103-003 Rev. A (0403)  
COOLING PERFORMANCE DATA  
AIR CONDITIONER MODEL NO.  
INDOOR COIL MODEL NO.  
H1RA060S50A  
G*FD060S24A  
IDCFM  
1650  
1900  
80  
2150  
CONDENSER  
ENTERING AIR  
TEMPERATURE  
ID DB (°F)  
ID WB (°F)  
T.C.  
85  
80  
70  
85  
70  
85  
80  
70  
72  
67  
57  
72  
67  
57  
72  
67  
57  
65.0  
41.8  
5.40  
63.9  
41.8  
6.11  
62.8  
41.8  
6.21  
60.6  
40.9  
6.92  
58.5  
40.1  
7.03  
52.9  
38.7  
7.31  
62.4  
41.5  
5.36  
60.7  
41.1  
6.04  
59.1  
40.7  
6.12  
55.3  
39.4  
6.74  
51.5  
38.2  
6.76  
47.7  
36.7  
7.09  
59.6  
41.0  
5.28  
56.5  
39.8  
5.91  
53.5  
38.6  
5.94  
49.3  
36.8  
6.57  
45.1  
35.0  
6.59  
40.4  
32.8  
6.84  
65.8  
44.7  
5.81  
64.7  
44.7  
6.57  
63.5  
44.6  
6.63  
61.5  
44.0  
7.38  
59.6  
43.4  
7.44  
54.2  
42.0  
7.78  
62.8  
44.0  
5.76  
61.4  
43.7  
6.49  
60.0  
43.5  
6.53  
56.6  
42.4  
7.22  
53.3  
41.3  
7.22  
48.5  
39.4  
7.53  
60.0  
43.6  
5.69  
57.5  
42.5  
6.38  
55.0  
41.5  
6.39  
50.7  
39.8  
7.05  
46.5  
38.2  
7.02  
41.9  
35.8  
7.29  
66.6  
47.5  
5.62  
65.4  
47.5  
4.41  
64.3  
47.5  
6.45  
62.4  
47.1  
7.24  
60.6  
46.8  
7.25  
55.5  
45.4  
7.64  
63.3  
46.5  
5.56  
62.1  
46.4  
4.34  
60.8  
46.2  
6.33  
58.0  
45.3  
7.10  
55.1  
44.4  
7.08  
49.4  
42.1  
7.36  
60.5  
46.1  
5.50  
58.5  
45.3  
4.27  
56.5  
44.4  
6.23  
52.2  
42.9  
6.93  
47.9  
41.4  
6.84  
43.5  
38.9  
7.13  
75  
85  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
95  
S.C.  
K.W  
T.C.  
105  
115  
125  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
T.C.  
S.C.  
K.W  
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.  
Multipliers for determining the performance with other indoor sections.  
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the  
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.  
T.C.  
S.C.  
KW  
Air Handler  
NAHD2093  
Coil  
G2FD060S24  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
F2RP060N93  
Unitary Products Group  
13  
036-21103-003 Rev. A (0403)  
MATCHING INDOOR COMPNENTS  
ADD-ON COILS - FOR FURNACE APPLICATION  
G2FD*  
MULTI-POSITION  
(UPFLOW, HORIZONTAL  
AND DOWNFLOW)  
AIR HANDLERS  
F2RP  
FAN COIL UNITS  
(UPFLOW, HORIZONTAL)  
N1AH  
MODULAR  
BLOWER  
G2FD*  
COIL  
P6UH  
FURNACE  
14  
Unitary Products Group  
036-21103-003 Rev. A (0403)  
NOTES  
Unitary Products Group  
15  
Subject to change without notice. Printed in U.S.A.  
036-21103-003 Rev. A (0403)  
Copyright © by York International Corp. 2003. All rights reserved.  
Supersedes: 036-21103-002 Rev. A (1101)  
Unitary  
Product  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Lexmark X654 Mfp User Manual
Philips Tea1104t User Manual
Ricoh 3010 User Manual
Ryobi Am00180 User Manual
Samsung Officeserv 7100 User Manual
Schumacher Pst 1000 User Manual
Sharp Mx 5001n User Manual
Soleus Air Air Conditioner Gm Ttw 12hc User Manual
Soleus Air Sg Wac 12ese User Manual
Xerox Synergix 8850 User Manual