Toshiba Rav Sm800xt E User Manual

FILE NO. SVM-03021  
SERVICE MANUAL  
AIR-CONDITIONER  
UNDER CEILING / CONSOLE TYPE  
RAV-SM560XT-E / RAV-SM560AT-E  
RAV-SM800XT-E / RAV-SM800AT-E  
R410A  
Sep., 2003  
1. SPECIFICATIONS  
1-1. Indoor Unit  
Model name  
RAV-SM560XT-E  
RAV-SM800XT-E  
Heating  
Cooling  
Heating  
Average  
Cooling  
Average  
Standard capacity (Note 1)  
kW  
5.0  
5.6  
6.7  
8.0  
(1.5 – 5.6) (1.5 – 6.3)  
(2.2 – 8.0) (2.2 – 9.0)  
Heating low temp. capacity (Note 1) (kW)  
Energy consumption effect ratio (Cooling)  
Power supply  
4.9  
5.8  
2.67 [D]  
3.29 [C]  
2.98  
2.46 [E]  
3.00 [D]  
2.73  
1 phase 220 – 240V 50Hz  
(A) 8.95 – 8.20 8.13 – 7.46 13.15 – 12.06 12.91 – 11.84  
Running current  
Electrical  
characteristics  
Power consumption  
(kW)  
(kW)  
(%)  
1.87  
1.7  
2.72  
2.67  
(Low temp.)  
Power factor  
Main unit  
2.18  
2.29  
95  
95  
94  
94  
Pure white  
–––  
Appearance  
Model  
Panel color  
Height  
Width  
Ceiling panel  
(Sold separately)  
–––  
(mm)  
(mm)  
(mm)  
(mm)  
(mm)  
(mm)  
(kg)  
633  
Main unit  
1093  
208  
Depth  
Outer  
dimension  
Height  
Width  
–––  
Ceiling panel  
–––  
(Sold separately)  
Depth  
–––  
Main unit  
23  
Total weight  
Ceiling panel  
–––  
Heat exchanger  
Finned tube  
Fan  
Multi blade fan  
Fan unit  
Air filter  
Standard air flow High (Mid./Low) (m3/h)  
800 (680/580)  
900(750/550)  
Motor  
(W)  
50  
Washable filter  
Controller (Sold separately)  
Gas side  
Wireless remote control  
(mm)  
(mm)  
12.7 (1/2”)  
15.9 (5/8”)  
Dimensions pipe  
Liquid side  
6.4 (1/4”)  
9.5 (3/8”)  
Drain port  
(Nominal dia.)  
(dB•A)  
25 (Polyvinyl chloride tube)  
36 46  
Sound level  
High (Mid./Low) (Note 2)  
43  
39  
42  
37  
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616  
based on the reference piping length 7.5 m with 0 meter height.  
Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values  
measured in the actual operating environment become larger than the indicated values due to the effects of  
external sound.  
Note  
: Rated conditions  
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB  
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB  
– 1 –  
• Operation characteristic curve  
<Cooling>  
<Heating>  
14  
14  
12  
10  
12  
RAV-SM800XT-E  
RAV-SM800XT-E  
10  
8
8
6
6
RAV-SM560XT-E  
4
2
0
RAV-SM560XT-E  
4
2
• Conditions  
• Conditions  
Indoor : DB27˚C/WB19˚C  
Outdoor : DB35˚C  
Air flow : High  
Indoor : DB20˚C  
Outdoor : DB7˚C/WB6˚C  
Air flow : High  
Pipe length : 7.5m  
230V  
Pipe length : 7.5m  
230V  
0
0
0
15 20  
40  
60 70 80  
100  
1520  
40  
60  
80 90 100  
Compressor speed (rps)  
Compressor speed (rps)  
• Capacity variation ratio according to temperature  
<Cooling>  
<Heating>  
120  
110  
100  
90  
80  
70  
60  
50  
40  
30  
20  
10  
0
105  
100  
95  
90  
85  
80  
75  
70  
65  
60  
• Conditions  
• Conditions  
Indoor : DB27˚C/WB19˚C  
Indoor : DB20˚C  
55  
Indoor air flow : High  
Pipe length : 7.5m  
Indoor air flow : High  
Pipe length : 7.5m  
50  
-14 -12 -10 -8 -6 -4 -2  
0
2
4
6
8
10  
32 33 34 35 36 37 38 39 40 41 42 43  
Outsoor temp. (˚C)  
Outsoor temp. (˚C)  
– 2 –  
1-2. Outdoor Unit  
Model name  
Appearance  
RAV-SM560AT-E  
RAV-SM800AT-E  
Silky shade (Muncel 1Y8.5/0.5)  
1 phase 230V (220 – 240V) 50Hz  
(Power exclusive to outdoor is required.)  
Power supply  
Type  
Hermetic compressor  
Compressor  
Motor  
Pole  
(kW)  
(kg)  
1.1  
1.6  
4 poles  
Refrigerant charged  
Refrigerant control  
R410A 0.9  
R410A 1.5  
Pulse motor valve  
Standard length  
20 (without additional charge)  
Max. total length  
Over 20m  
(m)  
30  
50  
Pipe  
Add 20g/m (Max. 200g)  
Add 40g/m (Max. 1200g)  
Outdoor lower  
Outdoor higher  
(m)  
(m)  
15  
30  
Height difference  
Height  
Width  
Depth  
(mm)  
(mm)  
(mm)  
(kg)  
595  
780  
270  
35  
795  
780  
270  
55  
Outer  
dimension  
Total weight  
Heat exchanger  
Finned tube  
Propeller fan  
Fan  
Fan unit  
Standard air flow High  
Motor  
(m³/h)  
(W)  
2400  
43  
3400  
63  
Gas side  
(mm)  
(mm)  
Ø12.7 (1/2”)  
Ø6.4 (1/4”)  
Ø15.9 (5/8”)  
Ø9.5 (3/8”)  
Connecting  
pipe  
Liquid side  
Discharge temp. sensor  
Over-current sensor  
Compressor thermo.  
Protection device  
Sound level  
(Note 2)  
High (Mid./Low)  
(Cooling/Heating)  
(dB•A)  
46/48  
48/50  
Note 1 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in  
the actual operating environment become larger than the indicated values due to the effects of external sound.  
Note 2 : Rated conditions  
Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB  
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB  
– 3 –  
2. CONSTRUCTION VIEWS  
2-1. Indoor Unit  
Front panel  
208  
1093  
Knock out system  
Grille air inlet  
Back body  
200 Min  
1093  
1015  
742  
For stud bolt  
(Ø8 – Ø10)  
Installation plate  
Mount plate  
For stud bolt (Ø6)  
450  
20  
20  
M10 Suspention bolt  
Ø74  
57  
Wireless remote control  
Knock out system  
18  
UNDER CEILING & CONSOLE INSTALLATION  
– 4 –  
2-2. Outdoor Unit (RAV-SM560AT-E)  
Drain hole (2-Ø20 x 88 long hole)  
Drain hole (Ø25)  
83  
600  
97  
A legs  
115.3 125  
30  
780  
B legs  
Discharge guard  
Discharge guide mounting hole  
(4-Ø4 embossing)  
115.3  
216  
49.5  
147  
Valve cover  
31  
23  
Earth  
terminal  
25  
220  
500 (Fan center dividing)  
Charge port  
31  
134  
Protective net mounting hole  
(2-Ø4 embossing)  
43  
707  
30  
Protective net mounting hole  
(4-Ø4 embossing)  
Refrigerant pipe connecting port  
(Ø12.7 flare at gas side)  
Refrigerant pipe connecting port  
(Ø6.4 flare at liquid side)  
Space required for service  
600  
Ø11 x 14 U-  
shape holes  
2-Ø11 x 14 U-shape holes  
(For Ø8–Ø10 anchor bolt)  
600  
Suction port  
52  
36  
2-Ø6 hole  
Product  
external  
line  
R15  
2-Ø6 hole  
300  
or more  
150  
R15  
600  
36  
52  
or more  
Product  
external line  
Discharge  
(Minimum  
distance up to wall)  
port  
Ø11 x 14 U-shape hole  
500  
Discharge  
port  
Details of A legs  
Details of B legs  
2-Ø11 x 14 long hole  
(For Ø8–Ø10 anchor bolt)  
or more  
– 5 –  
2-3.Outdoor Unit (RAV-SM800AT-E)  
Knockout  
(For draining) Drain hole (Ø20 x 88 burring hole)  
Drain hole (Ø25 burring hole)  
Installation bolt hole  
(Ø12 x 17 U-shape holes)  
29  
90  
191  
Suction  
port  
20  
Part B  
Suction  
port  
Details of B part  
Details of A part  
Knockout  
(For draining)  
Discharge  
port  
43  
26 60  
150  
Part A  
95  
300  
900  
Installation bolt hole  
(Ø12 x 17 U-shape holes)  
314  
Handles  
(Both sides)  
Refrigerant pipe connecting port  
(Ø9.5 flare at liquid side)  
Refrigerant pipe connecting port  
(Ø15.9 flare at gas side)  
2
60 27  
96  
1
Z
Discharge guide  
mounting hole  
(4-Ø4 embossing)  
300  
307  
Knockout for lower piping  
86  
7
28  
320  
Z views  
Space required for service  
2-Ø12 x 17 U-shape holes  
(For Ø8–Ø10 anchor bolt)  
600  
2
46  
Suction port  
1
150  
or more  
150  
or more  
Discharge  
(Minimum  
distance up to wall)  
port  
58  
161  
27  
30  
45  
1
2
500  
Discharge  
port  
2-Ø12 x 17 long hole  
(For Ø8–Ø10 anchor bolt)  
or more  
400  
– 6 –  
3. SYSTEMATIC REFRIGERATING CYCLE DIAGRAM  
3-1. RAV-SM560XT-E / RAV-SM560AT-E  
Indoor unit  
TCJ  
sensor  
Air heat exchanger  
TC sensor  
Outer diameter of refrigerant pipe  
Gas side A  
Liquid side B  
6.4 mm  
12.7 mm  
Refrigerant pipe  
at liquid side  
Outer dia. B  
Refrigerant pipe  
at gas side  
Outer dia. A  
Max  
30m  
Packed valve  
Packed valve  
Outer dia. B  
Outer dia. A  
Outdoor unit  
PMV  
(SKV-18D26)  
TS sensor  
TO sensor  
TD sensor  
Strainer  
4-way valve  
(VT7101D)  
TE  
sensor  
Heat exchanger  
Muffler  
8 multiple thread  
ripple 1 row 22 stages  
FP1.3 flat fin  
19 x L160  
Distributor  
Rotary compressor  
(DA130A1F-23F)  
R410A 0.9 kg  
Cooling  
Heating  
Pressure  
Pipe surface temperature (°C)  
Compressor  
Indoor/Outdoor  
temp. conditions  
(DB/WB) (°C)  
revolutions  
per second  
(rps)  
Indoor heat Outdoor heat  
exchanger exchanger  
Indoor  
fan  
(MPa)  
Discharge  
Suction  
Pd  
Ps  
0.9  
1.0  
0.5  
0.6  
1.1  
0.2  
(TD)  
85  
(TS)  
13  
13  
7
(TC)  
10  
(TE)  
47  
60  
5
Indoor  
27/19  
32/24  
18/15.5  
20/–  
Outdoor  
35/–  
*
Standard 3.1  
74  
71  
HIGH  
HIGH  
LOW  
HIGH  
LOW  
HIGH  
Cooling  
Overload  
Low load  
3.8  
0.9  
96  
12  
43/–  
25  
10  
28  
–5/–  
Standard 2.8  
87  
3
46  
1
87  
7/6  
Heating Overload  
Low load  
3.3  
1.7  
78  
22  
–20  
55  
16  
–22  
55  
30.–  
24/18  
–20/(70%)  
110  
26  
110  
0
* 4 poles are provided to this compressor.  
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.  
– 7 –  
3-2. RAV-SM800XT-E / RAV-SM800AT-E  
Indoor unit  
TCJ  
sensor  
Air heat exchanger  
TC sensor  
Outer diameter of refrigerant pipe  
Gas side A  
Liquid side B  
9.5 mm  
15.9 mm  
Refrigerant pipe  
at liquid side  
Refrigerant pipe  
at gas side  
Outer dia. B  
Outer dia. A  
Max  
50m  
Packed valve  
Packed valve  
Pd  
Ps  
Outer dia. B  
Outer dia. A  
Outdoor unit  
Modulating (PMV)  
(SKV-18D26)  
Strainer  
TS sensor  
TD sensor  
TO sensor  
Strainer  
TE  
sensor  
4-way valve  
(STF-0213Z)  
Capillary  
3 x 2  
x L530  
Muffler  
Accumulator  
(1500cc)  
Heat exchanger8  
1 row 30 stages  
FP1.3 flat fin  
25 x L210  
25 x L160  
Rotary compressor  
(DA220A2F-20L)  
R410A 1.5 kg  
Cooling  
Heating  
Pressure  
Pipe surface temperature (°C)  
Compressor  
revolutions  
per second  
(rps)  
Indoor/Outdoor  
temp. conditions  
(DB/WB) (°C)  
Indoor heat Outdoor heat  
exchanger exchanger  
Indoor  
fan  
(MPa)  
Pd  
Discharge  
Suction  
Ps  
0.9  
1.1  
0.8  
0.6  
1.1  
0.2  
(TD)  
89  
(TS)  
8
(TC)  
8
(TE)  
40  
46  
1
Indoor  
27/19  
32/24  
18/15.5  
20/–  
Outdoor  
35/–  
*
Standard 3.3  
Overload 3.7  
64  
45  
24  
70  
24  
90  
HIGH  
HIGH  
LOW  
HIGH  
LOW  
HIGH  
Cooling  
87  
17  
2
14  
1
43/–  
Low load  
Standard 3.3  
Heating Overload 3.1  
Low load 2.0  
1.0  
22  
–5/–  
93  
0
54  
52  
25  
0
7/6  
75  
20  
–26  
15  
–25  
30.–  
24/18  
–20/(70%)  
90  
0
* 4 poles are provided to this compressor.  
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.  
– 8 –  
4. WIRING DIAGRAM  
4-1. Indoor Unit  
HEAT  
EXCHANGER  
SENSOR  
(TCJ)  
SWITCH PCB  
MCC-1428B  
CN101  
1 2 3  
FOR FLOAT SWITCH  
1 2  
1 2  
(OPTION)  
When you use float  
switch you should cut J401  
1 2 3  
1 2 3  
CN402  
1 2  
CN100  
CN05  
IC03  
CN03  
1 2  
THERMO  
SENSOR  
(TA)  
BLK  
BLK  
J401  
2 2  
1 1  
WHI  
10 10  
9 9  
8 8  
7 7  
6 6  
5 5  
4 4  
3 3  
2 2  
1 1  
CN25  
10 10  
9 9  
8 8  
7 7  
6 6  
5 5  
4 4  
3 3  
2 2  
1 1  
CN13  
BLU  
BLU  
BLU  
BLU  
BLU  
BLU  
BLU  
BLU  
BLU  
POWER  
DC12V  
BLK  
BLK  
SUPPLY  
CIRCUIT  
HEAT  
2 2  
1 1  
CN01  
4
DC5V  
EXCHANGER  
SENSOR  
(TC)  
C02  
DB01  
1
R506  
CR502  
1 1  
2 2  
3 3  
4 4  
5 5  
CN10  
CR501  
R01  
WHI  
WHI  
1 1  
2 2  
3 3  
4 4  
5 5  
6 6  
C01  
RY501  
RED  
BLK  
RED  
BLK  
BRW  
RED  
ORN  
YEL  
PNK  
BLU  
1 1  
2 2  
3 3  
4 4  
5 5  
6 6  
CN07  
5
C501  
MCC-1428A  
3 3  
2 2  
1 1  
3 3  
2 2  
1 1  
BLU  
PUR  
GRY  
BRW  
GRY  
YEL  
C15  
IC04  
R405  
CR401  
CN11  
FAN-MOTOR  
RY401  
LOUVER  
MOTOR  
100”C  
R507  
R09  
3
2
1
FOR DRAIN PUMP  
(OPTION)  
R21  
CN401  
FUSE  
250VAC  
R22  
3
SG01  
F01  
T6.3A  
P04  
CN23  
CN30  
CN31  
BLK  
GRN&YEL  
INDOOR  
TERMINAL  
INDOOR  
UNIT  
2
1 2 3  
BLOCK  
OUTDOOR  
UNIT  
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS  
Diagnosis result  
Color  
Identification  
BRW : BROWN  
RED : RED  
Check items  
OPERATION Check to see if OPERATION indicator goes on and off when the main switch  
1
2
3
4
5
or breaker is turned on.  
indicator  
WHI : WHITE  
YEL : YELLOW  
BLU : BLUE  
BLK : BLACK  
GRY : GRAY  
Check the power supply voltage between 1 - 2 (Refer to the name plate.)  
Chack the fluctuate voltage between 2 - 3 (DC15 to 60V)  
Terminal  
block  
Fuse  
6.3A  
Check to see if the fuse blows out. (Check the varistor. : R22, R21)  
PNK : PINK  
ORN : ORANGE  
GRN&YEL : GREEN&  
YELLOW  
Check the voltage at the No.8 pin on CN13 connector of the infrared receiver.  
(Check the transformer and the power supply circuit of the rated voltage.)  
DC 5V  
GRN : GREEN  
PUR : PURPLE  
Check the voltage at the brown lead of the louver motor.  
(Check the transformer and the power supply circuit of the rated voltage.)  
DC 12V  
– 9 –  
4-2. Outdoor Unit (RAV-SM560AT-E)  
REACTOR  
Q200  
DB01  
THERMOSTAT  
FOR  
COMPRESSOR  
CONVERTER  
MODULE  
IGBT MODULE  
BRW  
ORN  
2 1  
2 1  
BLU  
CN500  
2 1  
2 1  
~ ~  
A E G  
P10  
+
P19  
P09  
P08  
TE  
P20  
P07  
P17 P18  
1 1  
CN600  
2 2  
TD  
1 1  
2 2  
3 3  
ELECTRONIC  
STARTER  
CN601  
CT  
POWER  
RELAY  
TO  
TS  
1 1  
2 2  
CN602  
CN603  
P.C. BOARD  
(MCC-813)  
3 2 1  
3 2 1  
4
1 1  
2 2  
3 3  
C12  
3
C13  
C14  
RELAY  
Q300  
CM  
1 1  
2 2  
3 3  
CN701  
P06  
COMPRESSOR  
COIL FOR  
4-WAY VALVE  
BLK  
SURGE  
ABSORBER  
F04  
FUSE  
2
T3. 15A  
250V~  
BLK  
YEL  
RED  
ORN  
RED  
GRY  
1 1  
2 2  
3 3  
4 4  
5 5  
6 6  
VARISTOR  
PMV  
FUSE  
T25A  
F01  
2
PULSE  
250V~  
MODULATING  
CN703  
VALVE  
P13  
P12  
P02  
P03 P01  
P14  
CN300  
P11  
5 4 3 2 1  
5 4 3 2 1  
3 2 1  
3 2 1  
CN301  
TERMINAL OF COMPRESSOR  
BLACK (C)  
2 1  
2 1  
PUR  
WHITE (S)  
1
2
3 L  
1
N
FM  
REACTOR  
RED (R)  
TO  
INDOOR  
UNIT  
POWER  
FAN MOTOR  
The sign in ( ) is displayed  
in the terminalcover  
SUPPLY  
220 to 240  
50Hz  
Color Identification  
BLK : BLACK  
BLU : BLUE  
RED : RED  
GRY : GRAY  
PNK : PINK  
GRN : GREEN  
WHI : WHITE  
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS  
BRW : BROWN  
ORN : ORANGE  
YEL : YELLOW  
PUR : PURPLE  
Check  
items  
Diagnosis result  
TERMINAL BLOCK  
There is no supply voltage  
(AC220 to 240V) between L - N , 1 - 2  
There is no voltage (DC15 to 25V) 2 - 3  
Power supply and connecting  
cable check  
1
NOTE  
FUSE  
CM  
: Compressor  
T25A 250V to fuse (F01) blown  
Converter module (DB01) and  
electrolytic capacitor (C12 to C14) check  
IGBT module (Q200) check  
Fan motor check  
PMV : Pulse modulating valve  
2
3
4
T3.15A 250V to fuse (F04) blown  
FM  
TE  
TD  
TO  
TS  
: Fan motor  
: Heat exchanger Temp. Sensor  
: Discharge Temp. Sensor  
: Outdoor Temp. Sensor  
: Suction Temp. Sensor  
ELECTROLYTIC CAPACITOR VOLTAGE (C12, C13, C14)  
DC320V not available between  
+ – terminal of electrolytic capacitor  
T25A fuse (F01) check  
P.C. board and converter  
module (DB01) check  
IGBT : Insulated Gate Bipolar Transistor  
DB01 : Converter module  
: Curreut Transformer  
Q300 : Fan motor driver module  
INVERTER OUTPUT (Inverter and compressor connector out of position)  
(Please confirm within six minutes after instructing in the drive.)  
Voltage between each line of inverter side  
conector pins are not equal.  
CT  
IGBT module and  
P.C. board check  
– 10 –  
4-3. Outdoor Unit (RAV-SM800AT-E)  
+
T03  
CT  
BU  
EU  
BV  
EV  
BW  
EW  
BX  
BY  
BZ  
CN09  
CN10  
CN11  
RED  
WHI  
BLK  
Compressor  
CM  
IGBT  
T04  
CT  
THERMOSTAT  
FOR  
module  
COMPRESSOR  
ORN  
2 2  
1 1  
CN604  
CN605  
4
TE  
POWER SUPPLY CIRCUIT  
(FOR P.C. BOARD)  
2 2  
1 1  
CN500  
CN700  
ORN  
4-WAY VALVE COIL  
2 2  
1 1  
TS  
TD  
GRN  
Q200  
F04  
2
FUSE  
3.15A  
3 3  
2
1 1  
3 3  
1 1  
3
1
CN600  
CN601  
P20  
YEL  
BLU  
C13  
P19  
P18  
P17  
3
C12  
2 2  
1 1  
FAN MOTOR  
TO  
5 5  
4 4  
3 3  
2 2  
1 1  
C11  
F02  
C10  
Fan  
circuit  
2
CN300  
CN301  
FM  
FUSE  
15A  
G
BLU  
YEL  
E
A
~
3 3  
1 1  
3 3  
CN302  
Converter  
module  
CN04  
2
3 3  
2 2  
1 1  
1 1  
POWER  
RELAY  
F300  
FUSE  
T5A  
~
+
BLK  
WHI  
BLU  
RED  
PNK  
5 5  
4 4  
3 3  
2 2  
1 1  
5 5  
4 4  
3 3  
2 2  
1 1  
DB01  
ORN  
RY01  
R05  
6 6  
5 5  
4 4  
3 3  
2 2  
1 1  
P10  
CN800  
CN06  
P.C. BOARD  
(MCC-1359)  
P11  
P13  
REACTOR  
PMV  
CN702  
2 2  
1 1  
REACTOR  
2 2  
1 1  
R06  
2 2  
1 1  
2 2  
1 1  
CN04  
ORN  
BLK  
WHI  
RED  
P12  
P09  
CN05  
T02  
CT  
5 5  
4 4  
3 3  
2 2  
1 1  
5 5  
4 4  
3 3  
2 2  
1 1  
P08  
P15  
PHOTO COUPLER  
BRN  
CN01  
P14  
CN13  
SUB  
P.C. BOARD  
(MCC-1398)  
F01  
2
F01  
FUSE  
T3.15A  
VARISTOR  
SURGE  
ABSORBER  
FUSE  
2
25A  
CN02  
CN01  
CN02  
WHI  
CN03  
REACTOR  
1 2 3  
1 2 3  
RED  
BLK  
GRY  
WHI  
RED  
TERMINAL OF COMPRESSOR  
BLACK(C)  
1 2 3 L N  
1
TO  
POWER  
WHITE(S)  
The sign in ( )  
is displayed  
in the terminal  
cover  
INDOOR SUPPLY  
UNIT 220-240V  
~50Hz  
RED(R)  
SIMPLE CHECK POINTS FOR DIAGNOSING FAULTS  
Check  
items  
Diagnosis result  
TERMINAL BLOCK  
There is no supply voltage  
Connecting cable check  
1
(AC220 to 240V) between L - N , 1 - 2  
There is no voltage (DC15 to 25V) 2 - 3  
FUSE  
25A fuse (F01) blown, 15A fuse (F02) blown  
3.15A fuse (F04) blown,  
Converter module (DB01) and electrolytic  
capacitor (C10 to C13) check IGBT  
module (Q200) check, Fan motor check  
SUB P.C. board check  
2
3
4
T5A fuse (F300) blown (SUB P.C. board)  
T3.15A fuse (F01) blown (SUB P.C. board)  
Color Identification  
ELECTROLYTIC CAPACITOR VOLTAGE (C10, C11, C12, C13)  
DC320V not available between  
terminal of electrolytic capacitor  
BLK : BLACK  
WHI : WHITE  
BRN : BROWN  
ORN : ORANGE  
YEL : YELLOW  
PUR : PURPLE  
25A fuse (F01) check  
P.C. board and coverter  
module (DB01) check  
+
BLU : BLUE  
RED : RED  
GRY : GRAY  
PNK : PINK  
GRN : GREEN  
INVERTER OUTPUT (CN09, CN10, CN11)  
(Please confirm within six minutes after instructing in the drive.)  
Voltage between each line of inverterside  
conector pins are not equal.  
IGBT module and  
P.C. board check  
– 11 –  
5. SPECIFICATION OF ELECTRICAL PARTS  
5-1. Indoor Unit  
No.  
Parts name  
Fan motor (for indoor)  
Grille motor  
Type  
Specifications  
Output (Rated) 50 W, 220 – 240 V  
DC 12 V  
1
2
3
4
5
AFP-220-50-4A  
MP35EA12  
Thermo. sensor (TA-sensor)  
550 mm  
10 kat 25°C  
Heat exchanger sensor (TC-sensor)  
Heat exchanger sensor (TCJ-sensor)  
6 mm, 500 mm  
6 mm, 500 mm  
10 kat 25°C  
10 kat 25°C  
5-2. Outdoor Unit (RAV-SM560AT-E)  
No.  
1
Parts name  
Type  
Specifications  
Output (Rated) 40 W  
3 phase, 4P, 1100 W  
1=10 mH, 16A  
Fan motor  
Compressor  
Reactor  
ICF-140-43-1  
2
DA130A1F-23F  
3
CH-57  
4
Outdoor temp. sensor (To-sensor)  
Heat exchanger sensor (Te-sensor)  
Suction temp. sensor (Ts-sensor)  
Discharge temp. sensor (Td-sensor)  
Fuse (Switching power (Protect))  
Fuse (Inverter, input (Current protect)  
4-way valve solenoid coil  
10 kat 25°C  
5
10 kat 25°C  
6
10 kat 25°C  
7
50 kat 25°C  
8
T3.15 A, AC 250 V  
25 A, AC 250 V  
9
10  
11  
STF-0108G  
US-622  
Compressor thermo. (Protection)  
ON : 90 ± 5°C, OFF : 125 ± 4°C  
5-3. Outdoor Unit (RAV-SM800AT-E)  
No.  
1
Parts name  
Type  
Specifications  
Output (Rated) 63 W, 220 – 240 V  
3 phase, 4P, 1600 W  
Fan motor  
Compressor  
Reactor  
ICF-140-63-1  
2
DA220A2F-20L  
3
CH-47  
4
Outdoor temp. sensor (To-sensor)  
Heat exchanger sensor (Te-sensor)  
Suction temp. sensor (Ts-sensor)  
Discharge temp. sensor (Td-sensor)  
Fuse (Switching power (Protect))  
Fuse (Inverter, input (Current protect)  
4-way valve solenoid coil  
10 kat 25°C  
10 kat 25°C  
10 kat 25°C  
50 kat 25°C  
T3.15 A, AC 250 V  
25 A, AC 250 V  
5
6
7
8
9
10  
11  
DKV-M0ZS743B0  
US-622  
Compressor thermo. (Protection)  
ON : 90 ± 5°C, OFF : 125 ± 4°C  
– 12 –  
6. REFRIGERANT R410A  
This air conditioner adopts the new refrigerant HFC  
(R410A) which does not damage the ozone layer.  
(5) After completion of installation work, check to  
make sure that there is no refrigeration gas  
leakage.  
The working pressure of the new refrigerant R410A is  
1.6 times higher than conventional refrigerant (R22).  
The refrigerating oil is also changed in accordance  
with change of refrigerant, so be careful that water,  
If the refrigerant gas leaks into the room, coming  
into contact with fire in the fan-driven heater,  
space heater, etc., a poisonous gas may occur.  
dust, and existing refrigerant or refrigerating oil are not (6) When an air conditioning system charged with a  
entered in the refrigerant cycle of the air conditioner  
using the new refrigerant during installation work or  
servicing time.  
large volume of refrigerant is installed in a small  
room, it is necessary to exercise care so that,  
even when refrigerant leaks, its concentration  
does not exceed the marginal level.  
If the refrigerant gas leakage occurs and its  
concentration exceeds the marginal level, an  
oxygen starvation accident may result.  
The next section describes the precautions for air  
conditioner using the new refrigerant. Conforming to  
contents of the next section together with the general  
cautions included in this manual, perform the correct  
and safe work.  
(7) Be sure to carry out installation or removal  
according to the installation manual.  
Improper installation may cause refrigeration  
trouble, water leakage, electric shock, fire, etc.  
6-1. Safety During Installation/Servicing  
As R410A’s pressure is about 1.6 times higher than  
that of R22, improper installation/servicing may cause  
a serious trouble. By using tools and materials exclu-  
sive for R410A, it is necessary to carry out installation/  
servicing safely while taking the following precautions  
into consideration.  
(8) Unauthorized modifications to the air conditioner  
may be dangerous. If a breakdown occurs please  
call a qualified air conditioner technician or  
electrician.  
Improper repair’s may result in water leakage,  
electric shock and fire, etc.  
(1) Never use refrigerant other than R410A in an air  
conditioner which is designed to operate with  
R410A.  
6-2. Refrigerant Piping Installation  
If other refrigerant than R410A is mixed, pressure 6-2-1. Piping materials and joints used  
in the refrigeration cycle becomes abnormally  
For the refrigerant piping installation, copper pipes and  
high, and it may cause personal injury, etc. by a  
joints are mainly used. Copper pipes and joints suit-  
rupture.  
able for the refrigerant must be chosen and installed.  
(2) Confirm the used refrigerant name, and use tools  
and materials exclusive for the refrigerant R410A.  
The refrigerant name R410A is indicated on the  
visible place of the outdoor unit of the air condi-  
tioner using R410A as refrigerant. To prevent  
mischarging, the diameter of the service port  
differs from that of R22  
Furthermore, it is necessary to use clean copper pipes  
and joints whose interior surfaces are less affected by  
contaminants.  
(1) Copper pipes  
It is necessary to use seamless copper pipes  
which are made of either copper or copper alloy  
and it is desirable that the amount of residual oil is  
less than 40 mg/10 m. Do not use copper pipes  
having a collapsed, deformed or discolored  
portion (especially on the interior surface).  
Otherwise, the expansion valve or capillary tube  
may become blocked with contaminants.  
As an air conditioner using R410A incurs pressure  
higher than when using R22, it is necessary to  
choose adequate materials.  
(3) If a refrigeration gas leakage occurs during  
installation/servicing, be sure to ventilate fully.  
If the refrigerant gas comes into contact with fire,  
a poisonous gas may occur.  
(4) When installing or removing an air conditioner,  
do not allow air or moisture to remain in the  
refrigeration cycle. Otherwise, pressure in the  
refrigeration cycle may become abnormally high  
so that a rupture of personal injury may be  
caused.  
Thicknesses of copper pipes used with R410A are  
as shown in Table 6-2-1. Never use copper pipes  
thinner than 0.8 mm even when it is available on  
the market.  
– 13 –  
Table 6-2-1 Thicknesses of annealed copper pipes  
Thickness (mm)  
Nominal diameter  
Outer diameter (mm)  
R410A  
0.80  
R22  
0.80  
0.80  
0.80  
1.00  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.80  
12.70  
15.88  
0.80  
1.00  
(2) Joints  
b) Socket joints  
For copper pipes, flare joints or socket joints are  
used. Prior to use, be sure to remove all  
contaminants.  
Socket joints are such that they are brazed for  
connections, and used mainly for thick pipings  
whose diameter is larger than 20 mm.  
Thicknesses of socket joints are as shown in  
Table 6-2-2.  
a) Flare joints  
Flare joints used to connect the copper pipes  
cannot be used for pipings whose outer  
diameter exceeds 20 mm. In such a case,  
socket joints can be used.  
Sizes of flare pipe ends, flare joint ends and  
flare nuts are as shown in Tables 6-2-3 to 6-2-6  
below.  
Table 6-2-2 Minimum thicknesses of socket joints  
Reference outer diameter of  
Minimum joint thickness  
(mm)  
Nominal diameter  
copper pipe jointed (mm)  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.50  
0.60  
0.70  
0.80  
12.70  
15.88  
6-2-1. Processing of piping materials  
d) Flare processing  
Make certain that a clamp bar and copper pipe  
have been cleaned.  
By means of the clamp bar, perform the flare  
processing correctly.  
Use either a flare tool for R410A or conven-  
tional flare tool.  
Flare processing dimensions differ according to  
the type of flare tool. When using a conven-  
tional flare tool, be sure to secure “dimension A”  
by using a gauge for size adjustment.  
When performing the refrigerant piping installation,  
care should be taken to ensure that water or dust does  
not enter the pipe interior, that no other oil other than  
lubricating oils used in the installed air conditioner is  
used, and that refrigerant does not leak. When using  
lubricating oils in the piping processing, use such  
lubricating oils whose water content has been removed.  
When stored, be sure to seal the container with an  
airtight cap or any other cover.  
(1) Flare Processing procedures and precautions  
a) Cutting the pipe  
D  
A
By means of a pipe cutter, slowly cut the pipe  
so that it is not deformed.  
b) Removing burrs and chips  
If the flared section has chips or burrs,  
refrigerant leakage may occur. Carefully  
remove all burrs and clean the cut surface  
before installation.  
Fig. 6-2-1 Flare processing dimensions  
c) Insertion of flare nut  
– 14 –  
Table 6-2-3 Dimensions related to flare processing for R410A  
A (mm)  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Conventional flare tool  
Clutch type Wing nut type  
1.0 to 1.5 1.5 to 2.0  
Flare tool for R410A  
clutch type  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0 to 0.5  
1.0 to 1.5  
1.0 to 1.5  
1.0 to 1.5  
1.5 to 2.0  
2.0 to 2.5  
2.0 to 2.5  
12.70  
15.88  
Table 6-2-4 Dimensions related to flare processing for R22  
A (mm)  
Outer  
diameter  
(mm)  
Nominal  
diameter  
Thickness  
(mm)  
Conventional flare tool  
Flare tool for R22  
clutch type  
Clutch type  
Wing nut type  
1.0 to 1.5  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0 to 0.5  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
1.0 to 1.5  
12.70  
15.88  
1.5 to 2.0  
1.5 to 2.0  
Table 6-2-5 Flare and flare nut dimensions for R410A  
Outer  
diameter  
(mm)  
Flare nut  
width  
(mm)  
Dimension (mm)  
Thickness  
Nominal  
diameter  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
9.1  
9.2  
6.5  
13  
20  
23  
25  
17  
22  
26  
29  
13.2  
16.6  
19.7  
13.5  
16.0  
19.0  
9.7  
12.70  
15.88  
12.9  
16.0  
Table 6-2-6 Flare and flare nut dimensions for R22  
Outer  
diameter  
(mm)  
Flare nut  
width  
(mm)  
Dimension (mm)  
Thickness  
Nominal  
diameter  
(mm)  
A
B
C
D
1/4  
3/8  
1/2  
5/8  
3/4  
6.35  
9.52  
0.8  
0.8  
0.8  
1.0  
1.0  
9.0  
9.2  
6.5  
13  
20  
20  
23  
34  
17  
22  
24  
27  
36  
13.0  
16.2  
19.4  
23.3  
13.5  
16.0  
19.0  
24.0  
9.7  
12.70  
15.88  
19.05  
12.9  
16.0  
19.2  
– 15 –  
°
to 46  
°
45  
43  
°
to 45  
°
Fig. 6-2-2 Relations between flare nut and flare seal surface  
(2) Flare connecting procedures and precautions  
When it is strong, the flare nut may crack and  
may be made non-removable. When choosing  
the tightening torque, comply with values  
designated by manufacturers. Table 6-2-7  
shows reference values.  
a) Make sure that the flare and union portions do  
not have any scar or dust, etc.  
b) Correctly align the processed flare surface with  
the union axis.  
Note:  
c) Tighten the flare with designated torque by  
means of a torque wrench. The tightening  
torque for R410A is the same as that for  
conventional R22. Incidentally, when the torque  
is weak, the gas leakage may occur.  
When applying oil to the flare surface, be sure to use  
oil designated by the manufacturer. If any other oil is  
used, the lubricating oils may deteriorate and cause  
the compressor to burn out.  
Table 6-2-7 Tightening torque of flare for R410A [Reference values]  
Tightening torque of torque  
wrenches available on the market  
N·m (kgf·m)  
Nominal  
diameter  
Outer diameter  
(mm)  
Tightening torque  
N·m (kgf·cm)  
1/4  
3/8  
1/2  
5/8  
6.35  
9.52  
14 to 18 (140 to 180)  
33 to 42 (330 to 420)  
50 to 62 (500 to 620)  
63 to 77 (630 to 770)  
16 (160), 18 (180)  
42 (420)  
12.70  
15.88  
55 (550)  
65 (650)  
– 16 –  
6-3.Tools  
6-3-1. Required tools  
The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to  
prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and  
opposite side dimension of flare nut (For 12.70 copper pipe) of the refrigerant piping are lengthened.  
The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,  
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.  
(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))  
(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)  
(3) Tools commonly used for R410A and for conventional refrigerant (R22)  
The table below shows the tools exclusive for R410A and their interchangeability.  
Tools exclusive for R410A (The following tools for R410A are required.)  
Tools whose specifications are changed for R410A and their interchangeability  
R410A air conditioner  
installation  
Conventional air  
conditioner installation  
No.  
Used tool  
Usage  
Existence of  
new equipment conventional  
Whether  
Whether new equipment  
can be used with  
for R410A  
equipment can  
be used  
conventional refrigerant  
1
2
Flare tool  
Copper pipe gauge  
Pipe flaring  
Flaring by  
Yes  
*(Note 1)  
for adjusting projection conventional flare  
Yes  
*(Note 1)  
*(Note 1)  
margin  
tool  
Connection of  
flare nut  
3
4
Torque wrench  
Yes  
Yes  
Evacuating,  
refrigerant charge,  
run check, etc.  
Gauge manifold  
Charge hose  
5
6
Vacuum pump adapter Vacuum evacuating  
Yes  
Yes  
Electronic balance for  
Refrigerant charge  
refrigerant charging  
7
8
9
!
Refrigerant cylinder  
Leakage detector  
Charging cylinder  
Refrigerant charge  
Gas leakage check  
Refrigerant charge  
Yes  
Yes  
(Note 2)  
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection  
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.  
(Note 2) Charging cylinder for R410A is being currently developed.  
General tools (Conventional tools can be used.)  
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as  
the general tools.  
(1) Vacuum pump  
(4) Reamer  
(5) Pipe bender  
(9) Hole core drill (65)  
(10) Hexagon wrench  
(Opposite side 4 mm)  
(11) Tape measure  
(12) Metal saw  
Use vacuum pump by  
attaching vacuum pump adapter. (6) Level vial  
(2) Torque wrench  
(3) Pipe cutter  
(7) Screwdriver (+, –)  
(8) Spanner of Monkey wrench  
Also prepare the following equipments for other installation method and run check.  
(1) Clamp meter  
(2) Thermometer  
(3) Insulation resistance tester  
(4) Electroscope  
– 17 –  
6-4. Recharging of Refrigerant  
When it is necessary to recharge refrigerant, charge the specified amount of new refrigerant according to the  
following steps.  
Recover the refrigerant, and check no refrigerant  
remains in the equipment.  
When the compound gauge’s pointer has indi-  
cated -0.1 Mpa (-76 cmHg), place the handle Low  
in the fully closed position, and turn off the  
Connect the charge hose to packed valve service  
vacuum pump’s power switch.  
port at the outdoor unit’s gas side.  
Keep the status as it is for 1 to 2 minutes, and  
ensure that the compound gauge’s pointer does  
not return.  
Connect the charge hose of the vacuum pump  
adapter.  
Open fully both packed valves at liquid and gas  
Set the refrigerant cylinder to the electronic  
sides.  
balance, connect the connecting hose to the  
cylinder and the connecting port of the electronic  
balance, and charge liquid refrigerant.  
Place the handle of the gauge manifold Low in  
the fully opened position, and turn on the vacuum  
pump’s power switch. Then, evacuating the  
refrigerant in the cycle.  
(For refrigerant charging, see the figure below.)  
1 Never charge refrigerant exceeding the specified amount.  
2 If the specified amount of refrigerant cannot be charged, charge refrigerant bit by bit in COOL mode.  
3 Do not carry out additional charging.  
When additional charging is carried out if refrigerant leaks, the refrigerant composition changes in the  
refrigeration cycle, that is characteristics of the air conditioner changes, refrigerant exceeding the  
specified amount is charged, and working pressure in the refrigeration cycle becomes abnormally high  
pressure, and may cause a rupture or personal injury.  
(Liquid side)  
(INDOOR unit)  
(OUTDOOR unit)  
Opened  
Closed  
(Gas side)  
Refrigerant cylinder  
(With siphon pipe)  
Check valve  
Open/Close valve  
for charging  
Service port  
Electronic balance for refrigerant charging  
Fig. 6-4-1 Configuration of refrigerant charging  
– 18 –  
1 Be sure to make setting so that liquid can be charged.  
2 When using a cylinder equipped with a siphon, liquid can be charged without turning it upside down.  
It is necessary for charging refrigerant under condition of liquid because R410A is mixed type of refrigerant.  
Accordingly, when charging refrigerant from the refrigerant cylinder to the equipment, charge it turning the  
cylinder upside down if cylinder is not equipped with siphon.  
[Cylinder with siphon]  
[Cylinder without siphon]  
Gauge manifold  
Gauge manifold  
OUTDOOR unit  
OUTDOOR unit  
c y l i n d e r  
R e f r i g e r a n t  
Refrigerant  
cylinder  
Electronic  
balance  
Electronic  
balance  
Siphon  
R410A refrigerant is HFC mixed refrigerant.  
Therefore, if it is charged with gas, the composition  
of the charged refrigerant changes and the  
characteristics of the equipment varies.  
Fig. 6-4-2  
6-5. Brazing of Pipes  
1 Phosphor bronze brazing filler tends to react  
with sulfur and produce a fragile compound  
water solution, which may cause a gas leakage.  
Therefore, use any other type of brazing filler at  
a hot spring resort, etc., and coat the surface  
with a paint.  
6-5-1. Materials for brazing  
(1) Silver brazing filler  
Silver brazing filler is an alloy mainly composed of  
silver and copper. It is used to join iron, copper or  
copper alloy, and is relatively expensive though it  
excels in solderability.  
2 When performing brazing again at time of  
servicing, use the same type of brazing filler.  
(2) Phosphor bronze brazing filler  
Phosphor bronze brazing filler is generally used to  
join copper or copper alloy.  
6-5-2. Flux  
(1) Reason why flux is necessary  
By removing the oxide film and any foreign  
matter on the metal surface, it assists the flow of  
brazing filler.  
(3) Low temperature brazing filler  
Low temperature brazing filler is generally called  
solder, and is an alloy of tin and lead. Since it is  
weak in adhesive strength, do not use it for  
refrigerant pipes.  
In the brazing process, it prevents the metal  
surface from being oxidized.  
By reducing the brazing filler’s surface tension,  
the brazing filler adheres better to the treated  
metal.  
– 19 –  
(2) Characteristics required for flux  
Activated temperature of flux coincides with the  
brazing temperature.  
6-5-3. Brazing  
As brazing work requires sophisticated techniques,  
experiences based upon a theoretical knowledge, it  
must be performed by a person qualified.  
In order to prevent the oxide film from occurring in the  
pipe interior during brazing, it is effective to proceed  
with brazing while letting dry Nitrogen gas (N2) flow.  
Due to a wide effective temperature range, flux  
is hard to carbonize.  
It is easy to remove slag after brazing.  
The corrosive action to the treated metal and  
brazing filler is minimum.  
It excels in coating performance and is harmless  
to the human body.  
Never use gas other than Nitrogen gas.  
(1) Brazing method to prevent oxidation  
1 Attach a reducing valve and a flow-meter to the  
Nitrogen gas cylinder.  
As the flux works in a complicated manner as  
described above, it is necessary to select an  
adequate type of flux according to the type and  
shape of treated metal, type of brazing filler and  
brazing method, etc.  
2 Use a copper pipe to direct the piping material,  
and attach a flow-meter to the cylinder.  
3 Apply a seal into the clearance between the  
piping material and inserted copper pipe for  
Nitrogen in order to prevent backflow of the  
Nitrogen gas.  
(3) Types of flux  
Noncorrosive flux  
Generally, it is a compound of borax and boric  
acid.  
It is effective in case where the brazing  
temperature is higher than 800°C.  
4 When the Nitrogen gas is flowing, be sure to  
keep the piping end open.  
5 Adjust the flow rate of Nitrogen gas so that it is  
lower than 0.05 m3/Hr or 0.02 Mpa (0.2 kgf/  
cm2) by means of the reducing valve.  
6 After performing the steps above, keep the  
Nitrogen gas flowing until the pipe cools down  
to a certain extent (temperature at which pipes  
are touchable with hands).  
Activated flux  
Most of fluxes generally used for silver brazing  
are this type.  
It features an increased oxide film removing  
capability due to the addition of compounds  
such as potassium fluoride, potassium chloride  
and sodium fluoride to the borax-boric acid  
compound.  
7 Remove the flux completely after brazing.  
(4) Piping materials for brazing and used brazing  
filler/flux  
M
Flow meter  
Piping  
material  
Used brazing  
filler  
Used  
flux  
Stop valve  
Copper - Copper Phosphor copper  
Do not use  
Paste flux  
Vapor flux  
Nitrogen gas  
cylinder  
Copper - Iron  
Iron - Iron  
Silver  
Silver  
From Nitrogen cylinder  
1 Do not enter flux into the refrigeration cycle.  
2 When chlorine contained in the flux remains  
within the pipe, the lubricating oil deteriorates.  
Therefore, use a flux which does not contain  
chloring.  
3 When adding water to the flux, use water which  
does not contain chlorine (e.g. distilled water or  
ion-exchange water).  
Pipe  
Nitrogen  
gas  
Rubber plug  
Fig. 6-5-1 Prevention of oxidation during brazing  
4 Remove the flux after brazing.  
– 20 –  
7. CONTROL BLOCK DIAGRAM  
Indoor Unit Control Panel  
M.C.U.  
8 MHz  
Heat Exchanger Sensor (TCJ)  
Heat Exchanger Sensor (TC)  
Temperature Sensor  
Hi POWER  
Display  
Functions  
Louver Control  
FILTER Sign  
Display  
3-minute Delay at Restart for Compressor  
Motor Revolution Control  
PRE DEF.  
Sign Display  
Infrared Rays Signal Receiver  
Processing  
(Temperature Processing)  
TIMER  
Display  
Initiallizing Circuit  
Infrared  
Timer  
Rays  
OPERATION  
Display  
Clock Frequence  
Oscillator Circuit  
36.7 kHz  
Drain Pump ON/OFF  
Serial Signal Communication  
Indoor Fan  
Motor  
Power Supply  
Circuit  
Louver ON/OFF Signal  
Louver Driver  
Remote  
Control  
Louver Motor  
Serial Signal  
Transmitter/  
Receiver  
Noise Filter  
Relay  
RY401  
Float  
Switch  
Drain  
Pump  
From Outdoor Unit  
Serial Signal Communication  
REMOTE CONTROL  
Infrared Rays  
Remote Control  
Operation (START/STOP)  
Operation Mode Selection  
AUTO, COOL, DRY, HEAT, FAN ONLY  
Temperature Setting  
Fan Speed Selection  
ON TIMER Setting  
OFF TIMER Setting  
Louver Auto Swing  
Louver Direction Setting  
ECO  
Hi power  
Filter Reset  
– 21 –  
8. OPERATION DESCRIPTION  
8-1. When power supply is reset  
8-3. Air volume control  
(1) Distinction of outdoor units  
(1) Operation with [HIGH (H)], [MED (M)], [LOW (L)],  
or [AUTO] mode is performed by the command  
from the remote control.  
When the power supply is reset, the outdoors are  
distinguished, and control is exchanged according  
to the distinguished result.  
(2) When [FAN] button is set to AUTO, the indoor fan  
motor operates as shown in Fig. 8-3-1, Fig. 8-3-2  
and Table 8-3-1.  
(2) Setting of the indoor fan speed  
Based on EEPROM data, rspeed of the indoor fan  
is selected.  
<COOL>  
Remarks: Air speed  
°C  
8-2. Operation mode selection  
+3  
M+  
(1) Based on the operation mode selecting command  
from the remote control, the operation mode is  
selected.  
+2.5  
*1  
+2  
*1  
+1.5  
Table 8-2-1  
*1  
+1  
Remote control  
Outline of control  
command  
+0.5  
Preset  
temp.  
0
STOP  
FAN  
Air conditioner stops.  
Fan operation  
0.5  
COOL  
DRY  
Cooling operation  
Dry operation  
NOTE :  
*1: The values marked with *1 are calculated and  
controlled by the difference in motor speed  
between M+ and L–.  
HEAT  
AUTO  
Heating operation  
Automatic operation  
Fig. 8-3-1  
(2) Automatic Operation  
The air conditioner selects and operates in one  
of the operating modes of cooling, heating or  
fan only, depending on the room temperature.  
If the AUTO mode is uncomfortable, you can  
select the desired conditions manually.  
Table 8-2-2  
Room temperature in operation  
Operating condition  
Cooling  
operation  
Performs the cooling operation at a temperature 1°C  
higher than the setting.  
The set temperature +1°C or higher  
(in case that the room is hot)  
Fan only  
operation  
Performs the fan only operation (low speed) while  
monitoring the room temperature. When the room  
temperature changes, the air conditioner will select the  
cooling or heating mode.  
The set temperature –1°C to +1°C  
Heating  
operation  
Performs the heating operation at a temperature 1°C  
lower than the setting.  
The set temperature –1°C or lower  
(in case that the room is cold)  
– 22 –  
<HEAT>  
8-4. Cool air discharge preventive control  
In heating operation, the indoor heat exchanger  
restricts revolving speed of the fan motor to prevent a  
cold draft. The upper limit of the revolving speed is  
shown in Fig. 8-4-1 and Table 8-4-1.  
°C  
0
Preset  
temp.  
L
0.5  
1  
1.5  
2  
*1  
*2  
Manual  
(One of  
5 steps)  
+
M
AUTO  
*4  
46  
45  
34  
33  
5.0  
5.5  
LH  
H
33  
32  
21  
20  
[FAN AUTO]  
(Up to  
setting  
speed)  
SUL*3  
NOTE :  
*2 A+4 A+4  
SUL*1  
Stop  
*1, *2 : The values marked with *1 and *2 are  
calculated and controlled by the difference in  
motor speed between M+ and L.  
A8 A8  
*6  
*5  
Fig. 8-3-2  
NOTES :  
*1: The fan stops for 2 minutes after thermostat-OFF.  
Table 8-3-1  
*2: A is 24°C when the preset temperature is 24°C or  
more and A is the preset temperature when it is  
under 24°C.  
RAV-SM560XT-E  
RAV-SM800XT-E  
MODEL  
Cooling  
Motor speed Air flow level Motor speed Air flow level  
(rpm)  
1060  
950  
(m3/h)  
800  
690  
580  
830  
730  
600  
(rpm)  
1190  
1010  
850  
(m3/h)  
900  
750  
650  
980  
800  
650  
HIGH  
MED  
LOW  
HIGH  
MED  
LOW  
*3: SUL means Super Ultra Low.  
and  
*4: Calculated from difference in motor speed  
between SUL and HIGH.  
Fan only  
800  
1120  
970  
1300  
1070  
860  
Heating  
Fig. 8-4-1 Cold draft preventing control  
820  
*5 and *6:  
LOW+MED  
2
LOW+ =  
MED+ =  
Table 8-4-1  
MED+HIGH  
2
Fan  
speed  
*5  
*6  
Starting period  
Stabilized period  
AUTO  
Up until 12 minutes  
passed after starting  
the unit  
From 12 to 25 minutes  
passed after starting  
the unit and room  
temperature is 3°C  
lower than preset  
temperature  
From 12 to 25 minutes  
passed after starting  
the unit and room  
temperature is  
between preset  
temperature and 3°C  
lower than preset  
temperature  
25 minutes or more  
passed after starting  
the unit  
Manual Room temperature  
(L – H) < Preset temperature  
–4°C  
Room temperature  
Preset temperature  
–3.5°C  
– 23 –  
8-5. Freeze preventive control (Low  
temperature release)  
8-7. Louver control  
(1) Vertical air flow louver  
Position of veritcal air flow louver is automatically  
controlled according to the operation mode.  
Besides, position of vertical air flow louver can be  
arbitrarily set by pressing [FIX] button.  
The louver position which is set by [FIX] button is  
stored in the microcomputer, and the louver is  
automatically set at the stored position for the next  
operation.  
The cooling operation (including Dry operation) is  
performed as follows based on the detected  
temperature of Tc sensor or Tcj sensor.  
When [J] zone is detected for T1 minutes (Following  
figure), the commanded frequency is decreased from  
the real operation frequency. After then the  
commanded frequency changes every 2 minutes while  
operation is performed in [J] zone.  
(2) Swing  
T1  
If [SWING] button is pressed when the indoor unit  
is in operation, the vertical air flow louver starts  
swinging. When [SWING] button is pressed, it  
stops swinging.  
Normal  
1 minute  
In [K] zone, time counting is interrupted and the  
operation is held.  
8-8. Filter sign display  
When [I] zone is detected, the timer is cleared and the  
operation returns to the normal operation.  
(1) The operation time of the indoor fan is calculated,  
the filter lamp (Orange) on the display part of the  
main unit goes on when the specified time (240H)  
has passed. When a wired remote controller is  
connected, the filter reset signal is sent to the  
remote controller, and also it is displayed on LCD  
of the wired remote control.  
(°C)  
7
6
5
A
I
K
J
(2) When the filter reset signal has been received  
from the wired remote control after [FILTER] lamp  
has gone on or when the filter check button  
(Temporary button) is pushed, time of the  
calculation timer is cleared. In this case, the  
measurement time is reset if the specified time  
has passed, and display on LCD and the display  
on the main unit disappear.  
Fig. 8-5-1  
In heating operation, the freeze-preventive control  
works if 4-way valve is not exchanged and the  
condition is satisfied.  
Remarks:  
Remarks:  
[FILTER] goes on  
Tcj : Indoor heat exchanger sensor temperature  
8-6. High-temp release control  
The heating operation is performed as follows based  
on the detected temperature of Tc sensor.  
When [M] zone is detected, the commanded  
frequency is decreased from the real operation  
frequency. After then the commanded frequency  
changes every 30 seconds while operation is  
performed in [M] zone.  
In [N] zone, the commanded frequency is held.  
When [L] zone is detected, the commanded  
frequency is returned to the original value by  
approx. 6Hz every 60 seconds.  
Tc (°C)  
M
55 A  
N
52  
48 B  
L
Fig. 8-6-1  
– 24 –  
8-9-1. How to set auto restart function  
8-9. Auto Restart Function  
To set the auto restart function, proceed as follows:  
The power supply to the unit must be on; the function  
will not set if the power is off.  
Push the [TEMPORARY] button located in the center  
of the front panel continuously for three seconds.  
The unit receives the signal and beeps three times.  
The unit then restarts operating automatically in the  
event of power supply being accidentally shut down.  
The indoor unit is equipped with an automatic  
restarting function which allows the unit to restart  
operating with the set operating conditions in the event  
of power supply being accidentally shut down. The  
operation will resume without warning three minutes  
after power is restored.  
This function is not set to work when shipped from the  
factory. Therefore it is necessary to set it to work.  
When the unit is on standby (Not operating)  
Operation  
Motions  
Push [TEMPORARY] button for more  
than three seconds.  
The unit is on standby.  
The unit starts to operate.  
The green lamp is on.  
After approx. three seconds,  
0
The unit beeps three times  
and continues to operate.  
The lamp changes from  
green to orange.  
3S  
Hi POWER FILTER  
PRE.D  
TEMPORARY  
button  
If the unit is not required to operate at this time, push [TEMPORARY]  
button once more or use the remote control to turn it off.  
When the unit is in operation  
Operation  
Motions  
Push [TEMPORARY] button for more  
than three seconds.  
The unit is in operation.  
The unit stops operating.  
The green lamp is on.  
The green lamp is turned off.  
After approx. three seconds,  
The unit beeps three times.  
0
3S  
Hi POWER FILTER  
PRE.D  
TEMPORARY  
button  
If the unit is required to operate at this time, push [TEMPORARY]  
button once more or use the remote control to turn it on.  
While this function is being set, if the unit is in  
operation, the orange lamp is on.  
This function can not be set if the timer operation  
has been selected.  
When the unit is turned on by this function, the  
louver will not swing even though it was swinging  
automatically before shutting down.  
While the filter check lamp is on, the  
TEMPORARY button has the function of filter  
reset button.  
– 25 –  
8-9-2. How to cancel auto restart function  
To cancel auto restart function, proceed as follows:  
Repeat the setting prodedure: the unit receives the  
signal and beeps three times.  
The unit will be required to be turned on with the  
remote control after the main power supply is turned  
off.  
When the unit is on standby (Not operating)  
Operation  
Motions  
Push [TEMPORARY] button for more  
than three seconds.  
The unit is on standby.  
The unit starts to operate.  
The orange lamp is on.  
After approx. three seconds,  
0
The unit beeps three times  
and continues to operate.  
The lamp changes from  
orange to green.  
3S  
Hi POWER FILTER  
PRE.D  
TEMPORARY  
button  
If the unit is not required to operate at this time, push [TEMPORARY]  
button once more or use the remote control to turn it off.  
When the unit is in operation  
Operation  
Motions  
Push [TEMPORARY] button for more  
than three seconds.  
The unit is in operation.  
The unit stops operating.  
The orange lamp is on.  
The orange lamp is turned off.  
After approx. three seconds,  
The unit beeps three times.  
0
3S  
Hi POWER FILTER  
PRE.D  
TEMPORARY  
button  
If the unit is required to operate at this time, push [TEMPORARY]  
button once more or use the remote control to turn it on.  
While this function is being set, if the unit is in  
operation, the orange lamp is on.  
8-10. Filter Check Lamp  
When the elapsed time reaches 1000 hours, the filter  
check lamp indicates. After cleaning the filters, turn off  
the filter check lamp.  
8-9-3. Power failure during timer operation  
When the unit is in Timer operation, if it is turned off  
because of power failure, the timer operation is  
cancelled. Therefore, set the timer operation again.  
8-10-1. How to turn off filter check lamp  
(1) Press [FILTER] button on the remote control.  
(2) Push [TEMPORARY] button on the indoor unit.  
Note:  
If [TEMPORARY] button is pushed while the filter  
check lamp is not indicating, the indoor unit will start  
the Automatic Operation.  
– 26 –  
9. INSTALLATION PROCEDURE  
Remark per EMC Directive 89/336/EEC  
To prevent flicker impressions during the start of the compressor (technical process) following installation  
conditions do apply.  
1. The power connection for the air conditioner has to be done at the main power distribution. This distribution  
has to be of an impedance.  
Normally the required impedance is reached at a 32A fusing point. Air conditioner fuse has to be 16A max.!  
2. No other equipment should be connected to this power line.  
3. For detailed installation acceptance, please contact your power supplier whether its restriction does apply  
for products like washing machines, air conditioners or electrical ovens.  
4. For power details of the air conditioner, refer to the rating plate of the product.  
9-1. Installation Diagram of Indoor and Outdoor Units  
(Under Ceiling Installation)  
Pipe shield  
(Console Installation)  
Hook  
1 Installation plate  
7 Zeolite filter  
4 Mounting  
screw  
9 Filter frame  
8 Purifying filter  
Air filter  
# Pan head wood screw  
% Wireless remote controller  
Before install the wireless  
remote controller  
" Remote controller holder  
With the remote controller cover  
open, load the batteries supplied  
correctly, observing their polarity.  
Insulate the refrigerant pipes  
separately with insulation, not  
together.  
% Wireless remote controller  
Cover  
! Batteries  
Min 6 mm thick heat resisting  
polyethylene foam  
– 27 –  
9-2. PRECAUTIONS FOR SAFETY  
Ensure that all Local, National and International regulations are satisfied.  
Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.  
The precautions described below include the important items regarding safety. Observe them without fail.  
After the installation work, perform a trial operation to check for any problem.  
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.  
Turn off the main power supply switch (or breaker) before the unit maintenance.  
Ask the customer to keep the Installation Manual together with the Owner’s Manual.  
New Refrigerant Air Conditioner Installation  
CAUTION  
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.  
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its  
pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant,  
refrigerating oil has also been changed. Therefore, during installation work, be sure that water, dust, former  
refrigerant, or refrigerating oil does not enter the refrigerating cycle.  
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging  
port of the main unit and installation tools are charged from those for the conventional refrigerant.  
Accordingly the exclusive tools are required for the new refrigerant (R410A).  
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust  
does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance  
force and impurity in it.  
To Disconnect the Appliance from Main Power Supply  
CAUTION  
This appliance must be connected to the main power supply by means of a switch with a contact separation  
of at least 3 mm.  
The installation fuse (25A D type  
) must be used for the power supply line of this conditioner.  
WARNING  
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner.  
Inappropriate installation may result in water leakage, electric shock or fire.  
Turn off the main power supply switch or breaker before attempting any electrical work.  
Make sure all power switches are off. Failure to do so may cause electric shock.  
Connect the connecting cable correctly.  
If the connecting cable is connected in a wrong way, electric parts may be damaged.  
When moving the air conditioner for the installation into another place, be very careful not to enter  
any gaseous matter other than the specified refrigerant into the refrigeration cycle.  
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes  
abnormally high and it may resultingly causes pipe burst and injuries on persons.  
Do not modify this unit by removing any of the safety guards or by by-passing any of the safety  
interlock switches.  
Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical  
parts.  
Do not store it in a wet basement or expose to rain or water.  
– 28 –  
After unpacking the unit, examine it carefully if there are possible damage.  
Do not install in a place that might increase the vibration of the unit.  
To avoid personal injury (with sharp edges), be careful when handling parts.  
Perform installation work properly according to the Installation Manual.  
Inappropriate installation may result in water leakage, electric shock or fire.  
When the air conditioner is installed in a small room, provide appropriate measures to ensure that  
the concentration of refrigerant leakage occur in the room does not exceed the critical level.  
Install the air conditioner securely in a location where the base can sustain the weight adequately.  
Perform the specified installation work to guard against an earthquake.  
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.  
If refrigerant gas has leaked during the installation work, ventilate the room immediately.  
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.  
After the installation work, confirm that refrigerant gas does not leak.  
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range,  
noxious gas might generate.  
Electrical work must be performed by a qualified electrician in accordance with the Installation  
Manual. Make sure the air conditioner uses an exclusive power supply.  
An insufficient power supply capacity or inappropriate installation may cause fire.  
Use the specified cables for wiring connect the terminals securely fix.To prevent external forces  
applied to the terminals from affecting the terminals.  
Be sure to provide grounding.  
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.  
Conform to the regulations of the local electric company when wiring the power supply.  
Inappropriate grounding may cause electric shock.  
Do not install the air conditioner in a location subject to a risk of exposure to a combustible gas.  
If a combustible gas leaks, and stays around the unit, a fire may occur.  
– 29 –  
9-3. Accessory parts and Parts to be procured locally  
9-3-1. Accessory parts  
Part  
No  
Part  
No  
Part name  
Q’ty  
Shape  
Part name  
Q’ty  
Shape  
Installation plate  
1
Purifying filter  
1
1
2
8
9
!
"
#
Filter frame  
Battery  
2
2
1
2
Installation Manual  
Owner’s Manual  
1
1
3
4
5
Remote controller  
holder  
Mounting screw  
4 x 25 S  
8
1
Pan head wood  
screw 3.1 x 16 S  
Flexible pipe  
Pipe shield  
1
1
$
%
Drain nipple  
(Packaged with the  
outdoor unit)  
1
1
6
7
Wireless remote  
controller  
Zeolite filter  
9-3-2. Parts to be procured locally  
Connecting pipe (Liquid side)  
(6.35 mm (diam.), Nominal (diam.) 1/4" thick 0.8 mm)  
RAV-SM560XT-E, RAV-SM560AT-E  
Connecting cable  
H07RN-F or 245IEC66 (1.5 mm2 or more)  
Thermal insulation for refrigerant pipe  
(10 mm or more, thermal insulating foam polyethylene)  
(9.52 mm (diam.), Nominal (diam.) 3/8" thick 0.8 mm)  
RAV-SM800XT-E, RAV-SM800AT-E  
Thermal insulation for drain pipe  
(10 mm or more, foam polyethylene)  
Connecting pipe (Gas side)  
(12.7 mm (diam.), Nominal (diam.) 1/2" thick 0.8 mm)  
RAV-SM560XT-E, RAV-SM560AT-E  
Drain pipe (Outer 26 mm (diam.))  
Tapes  
(15.9 mm (diam.), Nominal (diam.) 5/8" thick 1.0 mm)  
RAV-SM800XT-E, RAV-SM800AT-E  
Grounding cable (2.0 mm (diam.) or more)  
Power supply cord  
2.5 mm2 (H07RN-F or 245IEC66) or 3.5 mm2 (AWG-12)  
– 30 –  
9-4. SELECTION OF INSTALLATION PLACE  
WARNING  
Install the air conditioner where there is sufficient strength to withstand the weight of the unit.  
If the strength is not sufficient, the unit may fall down resulting in injury.  
CAUTION  
Upon approval of the customer, install the air conditioner in a place that satisfies the following  
conditions.  
Place where the unit can be installed horizontally.  
Place where a sufficient servicing space can be ensured for safe maintenance and check.  
Place where drained water will not cause any problem.  
Avoid installing in the following places.  
Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide  
gas (hot spring). (Should the unit be used in these places, special protective measures are needed.)  
Place exposed to oil, vapor, oil smoke or corrosive gas.  
Place where organic solvent is used nearby.  
Place close to a machine generating high frequency.  
Place where noise of the outdoor unit is easy to transmit.  
(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of  
noise.)  
Place with poor ventilation.  
Where the ceiling height is more than 3 m.  
Where the floor/wall/ceiling structure is unable to support the weight of the unit.  
9-5. INSTALLATION OF INDOOR UNIT  
WARNING  
Install the air conditioner certainly at a place to sufficiently withstand the weight.  
If the strength is insufficient, the unit may fall down resulting in human injury.  
Perform a specified installation work to guard against an earthquake.  
An incomplete installation can cause accidents by the units falling and dropping.  
Locate the unit so as to provide uniform circulation of chilled air.  
Avoid locating the unit as shown in the bad-marked figures below:  
Good location  
Bad location  
Bad location  
Evenly hot or cooled  
Shaded area well hot or cooled  
Shaded area well hot or cooled  
If a good location is not possible, use a fan to circulate the air evenly throughout the room.  
– 31 –  
9-5-1. Installation Place  
9-5-2. Before Installation  
A place which provides the spaces around the  
indoor unit as shown in the above diagram.  
A place where there is no obstacle near the air inlet  
and outlet.  
A place that allows easy installation of the piping to  
the outdoor unit.  
<Remove the Air inlet grille>  
1. Open the Air inlet grille by both hands.  
2. Loosen three screws for fixing the Panel arm. Do  
not remove the screws at this time.  
1
2
2
A place which allows the Front panel to be opened.  
1
CAUTION  
Direct sunlight or fluorescent light to the indoor  
unit’s wireless receiver should be avoided.  
The microprocessor in the indoor unit should not  
be too close to RF noise sources.  
Screw  
Panel arm  
Fig. 9-5-3  
(For details, see the owner’s manual.)  
3. First, move the Air inlet grille upward, then turn it  
backwards.  
<Remote controller>  
4. Remove the Grille stopper from the axis of the Front  
panel. After that, remove the Air inlet grille.  
5. Remove the Panel arms from the Front panel.  
A place where there are no obstacles such as a  
curtain that may block the signal from the indoor unit.  
Do not install the remote controller in a place  
exposed to direct sunlight or close to a heating  
source, such as a stove.  
3
Panel arm  
Keep the remote controller at least 1 m apart from  
the nearest TV set or stereo equipment. (This is  
necessary to prevent image disturbances or noise  
interference.)  
Grille stopper  
3
5
The location of the remote controller should be  
determined as shown below.  
<Remote controller usage>  
Under Ceiling Installation  
Fig. 9-5-4  
Ceiling  
9-5-3. After Installation  
<Install the Air inlet grille>  
1. Insert the three Panel Arms on the Air inlet grille  
and fix each securely by screws.  
Wall  
Remote controller  
Reception range  
Reception  
Remote  
range  
controller  
Fig. 9-5-1  
Panel arm  
Console Installation  
7 m  
Remote controller  
Fig. 9-5-5  
Reception  
range  
Wall  
CAUTION  
Reception  
range  
Remote  
controller  
The screws that fixed with Panel Arms must not  
be loose.  
Floor  
* Axial distance  
Fig. 9-5-2  
NOTICE  
The Paper pattern is inside the package box cover.  
Do not bend and dispose of it before installing.  
– 32 –  
2. Set the Air inlet grille arm to the axis of the Front  
panel.  
<Install the indoor unit>  
1. Remove the Side covers and the Installation plate  
3. Insert the Grille stopper to the correct position and  
fix it securely with screws.  
1.  
2. Insert the Suspension bolts into the metal fittings of  
the indoor unit.  
4. Push the Air inlet grille to the correct position.  
Axis of the  
Front panel  
3. Set to nuts, spring washers and washers on both  
sides of the metal fittings and then move the indoor  
unit backward.  
Air inlet  
grille arm  
4. Secure it with the M10 Nuts. (4 pcs.)  
5. Attach the Side covers to the unit.  
Rib  
1 Installation plate  
Suspension bolt  
Suspension bolt  
Side cover  
Fig. 9-5-6  
3
2
9-5-4. Under Ceiling Installation  
4
For the installation of the indoor unit use the Paper  
pattern, which is inside the package box cover.  
Side cover  
<Install the Suspension bolts>  
Nut (M10)  
Install the Suspension bolts so that it can support  
the indoor unit.  
Fig. 9-5-9  
1093  
240 mm or more  
1015  
<Condition for Installation>  
The unit must not decline more than 15 mm in either  
axis.  
15 mm  
140  
Fig. 9-5-7  
15 mm  
Adjust distance to ceiling before installation.  
Fig. 9-5-10  
Suspension  
Nut (M10)  
bolt  
<Piping and Drain Hose Installation>  
Spring  
Washer  
washer  
The piping direction can be 4 ways as illustrated.  
The Drain hose is only one way.  
Suspension  
bolt (M10)  
Upper piping  
Washer  
Spring  
washer  
Nut (M10)  
Fig. 9-5-8  
Rear upper piping  
Side piping  
Rear piping Drain hose  
Fig. 9-5-11  
– 33 –  
How to install the Drain hose.  
Other direction piping.  
1. Remove the two screws and the Drain band.  
1. Cut the slit of connecting only upper direction.  
Slit for upper piping  
2. Cut a slit for the drain hose hole.  
Cover for rear  
upper piping  
Cover for side piping  
Slit for drain hose hole  
Drain hose  
Drain band  
Fig. 9-5-16  
Screws  
2. Connect the Flexible pipe 5 to the large pipe  
Fig. 9-5-12  
(Gas side).  
3. Place the Drain hose on the U-shape space and  
secure it with the Drain band and two screws.  
Big pipe  
5 Flexible pipe  
Fig. 9-5-17  
Fig. 9-5-13  
Rear side piping with Drain hose. (Recommended  
direction)  
Ceiling  
175 mm  
or more  
Rear piping hole 80  
140 mm  
Ceiling  
Wall  
Fig. 9-5-14  
1. Cut or remove the determined direction slit or cover.  
2. Pipes and the Drain hose should be fixed together  
by the Drain band with two screws.  
Cut  
Fig. 9-5-15  
– 34 –  
9-5-5. Console Installation  
<Install the indoor unit>  
Select the terminal of Selector-SW from [C position]  
Install the Installation plate 1 at the wall according  
to [F position].  
to the Paper pattern.  
Hang the indoor unit on the hooks of the Installation  
plate 1.  
Fix the lower portion of the indoor unit with Mounting  
screws 4 (2 places).  
Indoor unit  
Hook  
1 Installation  
plate  
Fig. 9-5-18  
<Cutting a hole and mounting the Installation plate>  
When installing the rear piping, determine the pipe  
hole position, drill the pipe hole (80 mm) at a slight  
downward slant to the outdoor side.  
4 Mounting screw  
For mounting of the Installation plate 1, use the  
Paper pattern, which is inside the package box cover.  
1093  
375 mm  
or more  
742  
4 Mounting screw  
Fig. 9-5-21  
<Condition for installation>  
140  
The unit must not decline more than 15 mm in either  
axis.  
Floor  
Rear piping hole 80  
15 mm  
Fig. 9-5-19  
Anchor bolt  
Projection  
15 mm or less  
5 mm dia. hole  
Fig. 9-5-22  
4 Mounting screw  
4 x 25 s  
<Piping and Drain Hose Installation>  
The piping direction can  
be the following 3 ways  
with the Drain hose.  
Clip anchor  
(local parts)  
Fig. 9-5-20  
CAUTION  
Each piping direction  
should be connected with  
the Flexible pipe 5.  
Failure to firmly install the unit may result in personal  
injury and property damage if the unit falls.  
Rear piping  
Side piping  
Bottom piping  
In case of block, brick, concrete or similar type walls,  
Fig. 9-5-22  
make 5 mm dia. holes in the wall.  
Insert clip anchors for appropriate Mounting screws  
Cut or remove the  
determined direction  
slit or cover.  
4.  
NOTE :  
Slit for upper  
piping  
Cover for  
side piping  
Secure four corners and lower parts of the  
Installation plate 1 with 6 to 8 mounting screws to  
install it.  
Cover for rear  
upper piping  
Fig. 9-5-23  
– 35 –  
9-6. DRAIN PIPING WORK  
9-6-1. Drainage  
1. Run the Drain hose sloping downward.  
NOTE :  
The hole should be made at a slight downward slant on the outdoor side.  
Under Ceiling Installation  
Console Installation  
50 mm or more  
50 mm or more  
Fig. 9-6-1  
NOTICE  
In case of upward drainage from the unit, (Under Ceiling Installation), it is necessary to use the Drain pump  
kit of optional part.  
CAUTION  
1. Do not raise the Drain hose.  
2. Do not put the Drain hose into water.  
3. Do not form the Drain hose into a wave shape.  
4. Do not put the Drain hose end in the drainage ditch.  
2. Open the louver manually and put some water into it.  
Then check the flow of water from the Drain hose.  
Fig. 9-6-2  
3. When connecting the Extension drain hose; insulate the connecting part of Extension drain hose with the  
Pipe shield.  
Pipe shield  
Extension drain hose  
Inside the room  
Drain hose  
Fig. 9-6-3  
CAUTION  
Arrange the drain pipe for proper drainage from the unit.  
Improper drainage can result in dew-dropping. (Provide by customer)  
– 36 –  
9-7. REFRIGERANT PIPING  
9-7-1. Refrigerant Piping  
1. If the outdoor units are to be mounted on a wall, make sure that the platform supporting is sufficiently strong.  
The platform should be designed and manufactured to maintain its strength over a long period of time, and  
sufficient consideration should be given to ensuring that the outdoor unit will not fall.  
2. Use copper pipe with 0.8 mm or more thickness.  
3. Flare nut and flare works are also different from those of the conventional refrigerant. Take out the flare nut  
attached to the main unit of the air conditioner, and use it.  
CAUTION  
IMPORTANT 4 POINTS FOR PIPING WORK  
1. Take away dust and moisture from the inside of the connecting pipes.  
2. Tight connection (between pipes and unit)  
3. Evacuate the air in the connecting pipes using VACUUM PUMP.  
4. Check the gas leakage. (Connected points)  
9-7-2. Permissible Piping Length and Head  
The maximum piping length from the outdoor to indoor unit  
The maximum height difference outdoor/indoor unit  
Outdoor unit is above  
30 m  
Outdoor unit is below  
15 m  
30 m (Without charge 20 m)  
(RAV-SM560AT-E)  
50 m (Without charge 20 m)  
(RAV-SM800AT-E)  
<Flaring>  
Insert a flare nut into the pipe, and flare the pipe.  
B
As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools  
newly manufactured for R410A are recommended.  
However, the conventional tools can be used by adjusting projection margin of  
the copper pipe.  
Fig. 9-7-1  
Projection margin in flaring : B (Unit : mm)  
Rigid (Clutch type)  
Imperial (Wing nut type)  
R410A tool used  
Conventional tools used  
Outer diam. of copper pipe  
6.35/9.52  
R410A  
R22  
Outer diam.  
of copper pipe  
R410A  
0 to 0.5  
0 to 0.5  
R22  
R410A  
R22  
1.5 to 2.0  
2.0 to 2.5  
1.0 to 1.5  
1.5 to 2.0  
6.35/9.52  
12.7/15.9  
(Same as left) 1.0 to 1.5  
(Same as left) 1.0 to 1.5  
0.5 to 1.0  
0.5 to 1.0  
12.7/15.9  
Flaring dia meter size : A (Unit : mm)  
* In the case of the flaring for R410A with the  
conventional flare tool, pull out it approx. 0.5 mm  
more than that for R22 to adjust to the specified  
flare size.  
+0  
0.4  
A
Outer diam. of copper pipe  
R410A  
9.1  
R22  
9.0  
6.35  
The copper pipe gauge is useful for adjusting  
projection margin size.  
12.7/15.9  
16.6  
16.2  
A
Fig. 9-7-2  
– 37 –  
<Tightening connection>  
9-7-3. Pipe Shield for Flare Nut Connection  
Align the centers of the connecting pipes and tighten  
the flare nut as far as possible with your fingers. Then  
tighten the nut with a spanner and torque wrench as  
shown in the figure.  
Joints in liquid and gas pipes of the indoor unit should  
be insulated with an attached Pipe shield $.  
<How to install the pipe shield>  
1. Cut the Pipe shield $ to appropriate length.  
CAUTION  
2. Set the Pipe shield $.  
Do not apply excess torque. Otherwise, the nut  
may crack depending on the conditions.  
3. In case of a ceiling installation, orient the slit at the  
top of the pipe.  
4. Fix the Pipe shield $ with vinyl tape.  
(Unit : N•m)  
Slit  
Vinyl tape  
Outer diam. of copper pipe  
6.35 mm (diam.)  
Tightening torque  
14 to 18 (1.4 to 1.8 kgf•m)  
33 to 42 (3.3 to 4.2 kgf•m)  
50 to 62 (5.0 to 6.2 kgf•m)  
63 to 77 (6.3 to 7.7 kgf•m)  
9.52 mm (diam.)  
12.7 mm (diam.)  
15.9 mm (diam.)  
$ Pipe shield  
Fig. 9-7-5  
Tightening torque of flare pipe connections  
Pressure of R410A becomes higher than that of  
R22. (Approx. 1.6 times) Therefore, using a torque  
wrench, tighten firmly the flare pipe connecting  
sections which connect the indoor and outdoor units  
up to the specified tightening torque.  
Incorrect connections may cause not only a gas  
leakage, but also a trouble of the refrigeration cycle  
or compressor damage.  
Flare at  
indoor unit side  
Flare at  
outdoor unit side  
Fig. 9-7-3  
Half union  
Flare nut  
Externally  
Internally  
threaded side  
threaded side  
Use a wrench to secure.  
Use a torque wrench to tighten.  
Fig. 9-7-4  
– 38 –  
9-8. EVACUATING  
NOTE :  
AIR PURGE  
Use the vacuum pump, vacuum pump adapters, and  
gauge manifold referring to the manuals attached to  
each tool before using them.  
Evacuate the air in the connecting pipe and in the  
indoor unit using vacuum pump.  
Do not use the refrigerant in the outdoor unit.  
For details, see the manual of vacuum pump.  
For the vacuum pump, check oil is filled up to the  
specified line of the oil gauge.  
9-8-1. Use a vacuum pump  
While the air is purged, check again that the  
connecting port of charge hose, which has a  
projection to push the valve core, is firmly connected  
to the charge port.  
Be sure to use a vacuum pump with counter-flow  
prevention function so that inside oil of the pump does  
not flow backward into pipe of the air conditioner when  
the pump stops.  
Valve handling precautions  
1. Connect the charge hose from the manifold valve to  
the service port of the gas side packed valve.  
Open the valve stem or the handle until it strikes  
the stopper. It is unnecessary to apply further  
force.  
2. Connect the charge hose to the port of vacuum  
pump.  
Securely tighten the cap with a torque wrench.  
3. Open fully the low pressure side handle of the  
gauge manifold valve.  
Cap tightening torque  
4. Operate the vacuum pump to start for evacuating.  
Perform evacuating for about 35 minutes if the  
piping length is total 30 meters for model SM560  
and 50 meters for model SM800.  
6.4  
14 to 18 N•m (1.4 to 1.8 kgf•m)  
33 to 42 N•m (3.3 to 4.2 kgf•m)  
33 to 42 N•m (3.3 to 4.2 kgf•m)  
20 to 25 N•m (2.0 to 2.5 kgf•m)  
14 to 18 N•m (1.4 to 1.8 kgf•m)  
9.5  
Valve size  
12.7  
15.9  
(assuming a pump capacity of 27 liters per minute.)  
Then confirm that the compound pressure gauge  
reading is –101 kPa (–76 cmHg).  
Charge port  
5. Close the low pressure side valve handle of gauge  
manifold.  
9-8-2. Additional refrigerant  
1. The amount of refrigerant put into the outdoor unit  
at the factory is sufficient to fill up to 20 m of  
refrigerant piping work.  
6. Open fully the valve stem of the packed valves  
(both sides of Gas and Liquid).  
7. Remove the charging hose from the service port.  
8. Securely tighten the caps on the packed valves.  
2. If the length of the refrigerant piping work is 20 m or  
less, addition of refrigerant at the installation site is  
unnecessary.  
3. If the length of the piping work exceeds 20 m, extra  
refrigerant must be added. Refer to the outdoor  
installation manual for details of the extra amounts.  
4. Overcharge or undercharge of refrigerant in the  
outdoor unit may cause malfunction of the  
compressor.  
Add Only R410A Refrigerant to These Units  
– 39 –  
9-8-3. Heat insulation  
Cover  
1. Provide heat insulation on the refrigerant piping on  
both the liquid side and gas side separately, and  
ensure that all joints in the insulation are completely  
sealed (without gap).  
2. Since the temperature of the piping on the gas side  
increases during heating operations, the heat  
insulating material used must be able to withstand  
temperatures of more than 120°C.  
Do not put the spanner or  
torque wrench, etc. on the  
cover.  
The valve may be broken.  
3. Use the pipe insulation supplied in the accessory  
pack to insulate the piping connecting section on  
the indoor unit side.  
Fig. 9-8-3  
9-8-4. Packed valve handling precautions  
On the contrary, use a single spanner to loosen or  
Open the valve stem all the way out; do not try to  
open it beyond the stopper.  
tighten the flare nut of the valve at liquid side.  
Valve unit  
Securely tighten the valve stem cap in torque as  
follows:  
Gas side (12.7 mm (diam.))  
Liquid side (9.52 mm (diam.))  
Liquid side (6.35 mm (diam.))  
Service port  
50 to 62 N•m (5.0 to 6.2 kgf•m)  
33 to 42 N•m (3.3 to 4.2 kgf•m)  
14 to 18 N•m (1.4 to 1.8 kgf•m)  
14 to 18 N•m (1.4 to 1.8 kgf•m)  
Handle  
Pull out the handle and  
using cutting pliers, etc.  
turn it counterclockwise  
by 90°. (Open fully)  
Hexagonal wrench is required.  
Charge port  
Flare nut  
Fig. 9-8-4  
Valve unit  
Fig. 9-8-1  
<For RAV-SM800AT-E model>  
Push in handle.  
As shown in the figure, be sure to use a double  
spanner to loosen or tighten the flare nut of the  
valve at gas side. If using a single spanner, the nut  
cannot be tightened with necessary tightening  
torque.  
Charge port  
Flare nut  
SM800 type valve at gas side  
Fig. 9-8-5  
Cover  
Cap  
Piping valve  
Handle  
Closed completely  
Opened fully  
Loosened  
Tightened  
Fig. 9-8-6  
Flare nut  
Fig. 9-8-2  
– 40 –  
Compound pressure gauge  
Pressure gauge  
–101 kPa (–76 cmHg)  
Handle Lo  
Manifold valve  
Handle Hi  
(Keep fully closed)  
Charge hose  
(For R410A only)  
Charge hose  
(For R410A only)  
Service port (Valve  
core (Setting pin))  
Vacuum pump adapter for  
counter-flow prevention  
(For R410A only)  
Vacuum  
pump  
Packed valve at gas side  
Fig. 9-8-7  
<For RAV-SM560AT-E model>  
Compound pressure gauge  
Pressure gauge  
–101 kPa (–76 cmHg)  
Handle Lo  
Manifold valve  
Handle Hi  
(Keep fully closed)  
Charge hose  
(For R410A only)  
Charge hose  
(For R410A only)  
Vacuum pump adapter for  
counter-flow prevention  
(For R410A only)  
Vacuum  
pump  
Packed valve (Gas side)  
Service port (Valve core (Setting pin))  
Fig. 9-8-8  
Flare nut  
Valve unit  
Stopper  
Charge cap  
Charge port  
Valve rod  
Fig. 9-8-9  
– 41 –  
9-9. ELECTRICAL WORK  
For the air conditioner that has no power cord.  
NOTE :  
For selection and connection method of the power  
supply cords, refer to the details in the Installation  
Manual of the outdoor unit.  
CAUTION  
If incorrect/incomplete wiring is carried out, it  
may cause an electrical fire or smoke.  
Fig. 9-9-2  
Prepare the power supply for exclusive use with  
the air conditioner.  
NOTE :  
Be sure to use the cord clamps specified posi-  
tions with attached to the product.  
Connect the earth line to the metallic part (i mark)  
located at the side of 3P terminal.  
Do not damage or scratch the conductive core  
and inner insulator of power and inter-connecting  
cables when peeling them.  
9-9-3. Wiring between units  
Be sure to comply with local cords on running the  
wire from outdoor unit to indoor unit (size of wire  
and wiring method etc.)  
1. Connect the wires between the units correctly.  
Errors made in the connections can result in the  
unit malfunctioning.  
Use the power cord and Inter-connecting cable  
with specified thickness, specified type, and  
protective devices specified.  
2. Connect the control wires between the outdoor unit  
and indoor unit as shown in the figure below:  
9-9-4. Wiring Connections  
Terminal cover  
9-9-1. How to wire  
Screws  
1. Connect the connecting cable to the terminal as  
identified with their respective matched numbers on  
the terminal block of indoor and outdoor unit.  
H07RN-F or 245IEC66 (1.5 mm2 or more)  
Cord clamp  
2. Insulate the unsheathed redundant cords  
(conductors) with electrical insulation tape. Process  
them so that they do not touch any electrical or  
metal parts.  
Earth terminal  
3. For inter-unit wiring, do not use a cut wire jointed to  
another on the way.  
9-9-2. Stripping length of connecting cable  
Fig. 9-9-3  
1. Remove the Terminal cover and the Cord clamp.  
50  
2. Insert the connecting cable into the pipe hole on the  
wall.  
40  
3. Insert the connecting cable fully into the terminal  
block and secure it tightly with the screw.  
Tightening Torque: 1.2 N•m (0.12 kgf•m)  
Earth line  
4. Fix the connecting cable by the Cord clamp with  
two screws.  
Fig. 9-9-1  
5. Fix the Terminal cover.  
NOTE :  
Use stranded wire only.  
Wire type : More than 1.5 mm2 (H07RN-F or  
245IEC66) or 1.3 mm2 (AWG-16)  
– 42 –  
9-10. FINAL INSTALLATION CHECKS  
9-10-1. Precautions  
9-10-5. Test Operation  
Ensure that the electrical cable used for power supply  
and control of the system is unable to come into  
contact with either service valves or piping work which  
are not insulated.  
To switch the TEST RUN (COOL) mode, press  
TEMPORARY button for 10 sec.  
(The beeper will make a short beep.)  
9-10-2. Electrical wiring  
When installation is complete, check that all power  
supply and interconnecting wiring has been  
appropriately protected.  
Hi POWER FILTER  
PRE.D  
9-10-3. Refrigerant piping  
When refrigerant and drain piping have been  
completed. Ensure that all pipework is fully insulated  
and apply finishing tape to seal the insulation.  
TEMPORARY  
button  
9-10-4. Check and Test Operation  
Fig. 9-10-2  
Pressure of R410A is approx. 1.6 times of that of  
R22. If installation work is incompletely finished, a  
gas leakage may occur at the cases such as  
pressure rise during operation.  
Therefore, be sure to test the piping connections for  
leakage.  
9-10-6. Auto Restart Setting  
This product is designed so that, after a power failure,  
it can restart automatically in the same operating  
mode as before the power failure.  
Check the flare nut connections, valve stem cap  
connections and service port cap fittings for gas  
leak with a leak detector or soap water.  
Information  
The product was shipped with Auto Restart  
function in the off position. Turn it on as required.  
Piping cover  
Cord clamp  
<How to set the Auto Restart>  
Press and hold the TEMPORARY button for about  
3 seconds. After 3 seconds, the electronic beeper  
makes three short beeps to tell you the Auto Restart  
has been selected.  
Indoor/Outdoor  
connecting  
cables  
Flare nut  
connections  
(Indoor unit)  
To cancel the Auto Restart, follow the steps  
described in the section Auto Restart Function of  
the Owner’s Manual.  
Power cable  
Valve cover  
Fig. 9-10-1  
– 43 –  
9-10-7. Useful Functions (SM800AT-E only)  
<Self-Diagnosis by LED Indication>  
In addition to the code checking by remote controller of the indoor unit, troubles of the outdoor unit can be diagnosed by LED indications on  
the cycle control P.C. board of the outdoor unit. Utilize them for various checks.  
For the check by remote controller of the indoor unit, refer to the installation Manual of the indoor unit.  
Before a check, confirm each bit of the DIP switch is set to OFF position.  
LED indication and code checking  
Cycle control P.C. board  
DIP switch  
LED indication  
Cause  
SW800  
D800  
\
D801  
[
D802  
[
D803  
[
Heat exchanger sensor (TE) error  
Suction sensor (TS) error  
[
[
\
[
\
\
[
[
Discharge sensor (TD) error  
High-pressure protection error  
[
\
[
\
[
\
[
[
Outdoor temperature sensor (TO) error  
DC outside fan error  
\
\
\
[
LED  
indication  
\
[
[
\
Communication error between IPDU  
Discharge temp. error  
[
\
\
[
ON  
D800  
: Red  
\
\
[
\
EEPROM error  
\
1
2
3
4
[
[
\
\
Communication error between IPDU  
G-Tr short-circuit protection  
D801  
\
: Yellow  
: Yellow  
: Yellow  
[
[
[
D802  
\
[
[
[
[
Detect circuit error  
[
[
Current sensor error  
D803  
\
[
[
[
\
[
Comp. lock error  
[
Comp. break down  
: Rapid flash  
[ : Go off  
\ : Go on  
[
[
[
[
Phase missing detection, Detection of coming-off of CT current sensor  
Serial communication error by thermo. operation of Comp. case  
\
9-10-8. Installation/Servicing Tools  
<Changes in the product and components>  
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, the service port  
diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)  
In order to increase the pressure resisting strength of the refrigerant piping, flare processing diameter and size of opposite side of flare  
nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)  
New tools for R410A  
New tools for R410A  
Applicable to R22 model  
Changes  
Gauge manifold  
As pressure is high, it is impossible to measure by means of conventional gauge.  
In order to prevent any other refrigerant from being charged, each port diameter is  
changed.  
Charge hose  
In order to increase pressure resisting strength, hose materials and port size are  
changed (to 1/2 UNF 20 threads per inch).  
When purchasing a charge hose, be sure to check the port size.  
Electronic balance  
for refrigerant charging  
As pressure is hight and gasification speed is fast, it is difficult to read the  
indicated value by means of charging cylinder, as air bubbles occur.  
Torque wrench  
(nominal diam. 1/2, 5/8)  
The size of opposite sides of flare nuts have been increased. Incidentally, a  
common wrench is used for nominal diameters 1/4 and 3/8.  
By increasing the clamp bar’s receiving hole, strength of spring in the tool has  
been improved.  
Flare tool  
(clutch type)  
Gauge for projection adjustment  
Vacuum pump adapter  
Used when flare is made with using conventional flare tool.  
Connected to the conventional vacuum pump. It is necessary to use an adapter to  
prevent vacuum pump oil from flowing back to the charge hose.  
The charge hose connecting part has two ports-one for conventional refrigerant  
(7/16 UNF 20 threads per inch) and one for R410A. If the vacuum pump oil  
(mineral) mixes with R410A a sludge may occur and damage the equipment.  
Gas leakage detector  
Exclusive for HFC refrigerant.  
Incidentally, the “refrigerant cylinder” comes with the refrigerant designation (R410A) and protector coating in the U. S’s ARI specified rose  
color (ARI color code: PMS 507).  
Also, the “charge port and packing for refrigerant cylinder” require 1/2 UNF 20 threads per inch corresponding to the charge hose’s port size.  
– 44 –  
9-11. ENVIRONMENT  
9-11-1. Environmental Issues  
<Product maintenance>  
1. To minimize the chances of environmental damage and to ensure the efficient operation of the unit, it is  
recommended to have the air conditioner periodically checked and serviced by a qualified engineer.  
<Product disposal>  
1. Please dispose of the air conditioner unit in an environmentally responsible manner.  
Recycling is the preferred disposal method.  
2. When disposing of an air conditioner system, contact either the manufacture, your local environmental control  
authority or a local waste disposal company for advice.  
3. Ensure all packing material is either recycled or disposed of in accordance with local regulations.  
4. The refrigerant gas within the unit should only be removed by an authorized company.  
WARNING  
Discharge of refrigerant to atmosphere is illegal and may lead to prosecution.  
– 45 –  
10.TROUBLESHOOTING  
10-1-2. Troubleshooting procedure  
10-1. Summary of Troubleshooting  
When a trouble occurred, check the parts along with  
the following procedure.  
10-1-1. Before troubleshooting  
(1) Required tools/instruments  
e and d screwdrivers, spanners, radio  
cutting pliers, nippers, etc.  
Trouble  
Confirmation of check code by service mode  
Tester, thermometer, pressure gauge, etc.  
(2) Confirmation points before check  
1 The following operations are normal.  
a) Compressor does not operate.  
Is not 3-minutes delay (3 minutes after  
compressor OFF)?  
Check defective position and parts.  
NOTE :  
For cause of a trouble, power conditions or malfunc-  
tion/erroneous diagnosis of microcomputer due to  
outer noise is considered except the items to be  
checked. If there is any noise source, change the  
cables of the signal line to shield cables.  
Does not thermostat turn off?  
Does not timer operate during fan  
operation?  
Is not outside high-temperature operation  
controlled in heating operation?  
b) Indoor fan does not rotate.  
Does not cool air discharge preventive  
control work in heating operation?  
c) Outdoor fan does not rotate or air volume  
changes.  
10-1-3. Outline of Judgment  
A primary judgment to detect cause of error exists on  
the indoor unit or outdoor unit is performed in the  
following procedure.  
<Judgment by flashing display on the indoor  
unit display part>  
Does not high-temperature release opera-  
tion control work in heating operation?  
Does not outside low-temperature opera-  
tion control work in cooling operation?  
Is not defrost operation performed?  
d) ON/OFF operation cannot be performed from  
remote control.  
The indoor unit monitors operating status of the air  
conditioner, and if a protective circuit works, contents  
of the self-diagnosis are displayed with a block  
restricted to the following cases on the indoor unit  
display part (Sensor).  
Is not forced operation performed?  
Is not the control operation performed from  
outside/remote side?  
2 Did you return the cabling to the initial  
positions?  
3 Are connecting cables between indoor unit and  
receiving unit correct?  
Table 10-1-1  
Remote  
control code  
Block display  
Contents of self-diagnosis  
Check code  
––  
00  
01  
02  
03  
––  
Operation lamp display flashes. (1Hz)  
Operation lamp display flashes. (5Hz)  
Operation/timer lamp displays flash. (5Hz)  
Operation/defrost lamp displays flash. (5Hz)  
Operation/timer/defrost lamp displays flash. (5Hz)  
––  
Power failure (In power ON)  
Indoor P.C. board  
––  
0b to 0F, 11, 12, b5, b6  
04  
Inter-unit cables/transmission system  
Outdoor P.C. board  
Cycle system, etc.  
14 to 19, 1A, 1C  
1d, 1E, 1F, 21  
1b, 8b  
––  
– 46 –  
10-2. Self-Diagnosis by Remote Control  
(Check Code)  
(1) If the lamps are indicated as shown 00 to 03 in  
Table 10-1-1, exchanger the self-diagnosis by the  
remote control.  
(2) When the remote control is set to the service  
mode, the indoor controller diagnoses the  
operation condition and indicate the information of  
the self-diagnosis on the display of the remote  
control with the check codes. If a fault is detected,  
all lamps on the indoor unit will blink at 5 Hz and it  
will beep for 10 seconds (Pi, Pi, Pi....). The timer  
lamp usually blinks (5 Hz) during the self-diagnosis.  
10-2-1. How to use remote control in service mode  
(1) Press [CHECK] button with a tip of pencil to set the  
remote control to the service mode.  
“00” is indicated on the display of the remote  
control.  
SET  
CLR  
RESET CLOCK CHECK  
The timer lamp on the indoor unit blinks  
continuously. (5 times per 1 sec.)  
(2) Press [TIMER 8] button.  
If there is no fault with a code, the indoor unit will  
beep once (Pi) and the display of the remote  
control will change as follows:  
AUTOA  
00  
01  
02 1d  
1E  
22  
Check the unit with all 35 check codes (00 to 22).  
as shown in Table 10-2-1.  
PRESET  
Press [TIMER 9] button to change the check  
code backwards.  
START/STOP  
AUTO  
FAN  
SWING  
FIX  
MODE  
If there is a fault, the indoor unit will beep for 10  
seconds (Pi, Pi, Pi...).  
ECO  
Hi-POWER  
TIMER  
Note the check code on the display of the remote  
control.  
MEMO  
ON  
OFF  
SET  
CLR  
2-digits alphanumeric will be indicated on the  
display.  
FILTER  
RESET CLOCK CHECK  
All lamps on the indoor unit will blink. (5 times  
per 1 sec.)  
(3) Press [CLR] button. After service finish for clear  
service code in memory.  
“7F” is indicated on the display of the remote  
control.  
Alphanumeric characters are used for the check code.  
(4) Press [START/STOP] button to release the service  
mode.  
is 5.  
is A.  
is C.  
is 6.  
is B.  
is D.  
The display of the remote control returns to as it  
was before service mode was engaged.  
– 47 –  
Table 10-2-1  
Operation of diagnostic function  
Judgement and action  
Check  
code  
Check  
code  
Unit  
status  
Block  
Symptom  
Condition  
Indoor  
P.C. board  
The indoor thermo sensor (TA) is  
defective.  
Disconnection or short-circuit  
Operation  
continues.  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the indoor thermo sensor (TA).  
2. Check the indoor P.C. board.  
The indoor heat exchanger  
sensor (TC) is defective.  
Disconnection or short-circuit  
Operation  
continues.  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the indoor heat exchanger  
sensor (TC).  
2. Check the indoor P.C. board.  
The indoor fan motor or its circuit  
is defective.  
All off  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the connector circuit of the  
indoor fan motor (CN10).  
2. Check the indoor fan motor.  
3. Check the indoor P.C. board.  
The part other than the above  
parts on the indoor P.C. board is  
defective.  
Operation  
continues.  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the indoor P.C. board.  
(EEPROM and peripheral circuits)  
EEPROM access error  
IOL operation  
All off  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
Overload operation of refrigerating cycle  
The block is  
unidentifi-  
able  
The variation of TC, 5 minutes  
after starting the compressor,  
is 2K or less.  
Operation  
continues.  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check whether or not the TC sensor  
comes off.  
2. Check whether or not it is possible to  
operate the compressor and the  
outdoor fan motor.  
3. Check gas leak.  
The serial signals can not be  
Operation  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. In the case of the outdoor unit not  
operating at all;  
Check the crossover cable and  
connect it properly.  
Check the outdoor P.C. board.  
2. In the case of the outdoor unit operating  
normally;  
Check whether or not both of serial  
LED (Green) and serial LED (Orange)  
is blinking.  
Cable  
connection  
transmitted and received between continues.  
indoor and outdoor units.  
The crossover wire is  
connected wrongly.  
The serial signal transmitting  
circuit on the outdoor P.C. board  
is defective.  
The serial signal receiving  
circuit on the indoor P.C. board  
is defective.  
If the serial LED (Green) is not  
blinking, check the outdoor P.C. board.  
If the serial LED (Orange) is not  
blinking, check the indoor P.C. board.  
The operation command signals  
are not transmitted from the  
indoor unit to the outdoor unit.  
Operation  
continues.  
The lamp on the  
indoor unit blinks  
when error is  
defected. And it  
returns to the  
If the operation command signals continue  
to be transmitted between 2 and 3 of the  
indoor terminal block, replace the outdoor  
P.C. board.  
normal condition  
when recovering  
from errors.  
Outdoor  
P.C. board  
The outdoor thermo sensor (TE)  
is defective.  
Disconnection or short-circuit  
All off  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the outdoor thermo sensor (TE).  
2. Check the outdoor P.C. board.  
The outdoor heat exchanger (TD) All off  
sensor is defective.  
Disconnection or short-circuit  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the outdoor heat exchanger  
sensor (TD).  
2. Check the outdoor P.C. board.  
The reply serial signal has been  
transmitted when starting the  
unit, but stops being transmitted  
shortly after.  
Operation  
continues.  
The lamp on the  
indoor unit blinks  
when error is  
defected. And it  
returns to the  
1. Repeatedly turn the indoor unit on and  
off with the interval of approx. 10 to 40  
minutes. (The check code is not  
indicated during operation.) And supply  
gas. (Check gas leak.)  
Other parts  
(including  
compressor)  
1. Compressor thermo operation  
Gas shortage  
normal condition  
when recovering  
from errors.  
2. The indoor unit operates normally  
during the check.  
If the reply serial signal continues to be  
transmitted between 2 and 3 of the  
indoor terminal block, replace the  
outdoor P.C. board.  
Gas leak  
2. Instantaneous power failure  
If the signal stops between them,  
replace the indoor P.C. board.  
The discharge temperature is  
over 120°C.  
All off  
All off  
The lamp on the  
indoor unit blinks  
when error is  
defected.  
1. Check the heat exchanger sensor (TD).  
2. Gas purging  
The IOL operation is defective.  
The lamp on the  
indoor unit blinks  
when error is  
detected.  
When turning on the unit, the normal  
phase (RST) is detected but T-R waveform  
has not been detected for 120 seconds or  
more.  
– 48 –  
Table 10-2-2  
Operation of diagnostic function  
Judgement and action  
Check  
code  
Unit  
status  
Block  
Symptom  
Condition  
[MODE]  
[TIMER] lamp  
5Hz flash  
The serial signal is not output  
from outdoor unit to indoor unit.  
Miscabling of inter-unit cables  
Defective serial sending circuit  
on outdoor P.C. board  
Defective serial receiving circuit  
on outdoor P.C. board  
Compressor case thermo  
operation  
Operation  
continues.  
Displayed when  
error is detected  
1. Outdoor unit does not completely  
operate.  
Inter-unit cable check, correction of  
miscabling  
Outdoor P.C. board check, P.C. board  
cables check  
Compressor case thermo check  
2. In normal operation  
When outdoor sending serial LED  
(Green) flashes, the receiving serial  
LED (Orange) also flashes. : Indoor  
P.C. board (Main P.C. board) check  
When the receiving serial LED (Orange)  
does not flash: Outdoor P.C. board  
check  
BUS communication circuit error  
* BUS communication was  
interrupted over the specified  
time.  
Operation  
continues  
(According  
to remote  
control of  
indoor  
Displayed when  
error is detected  
1. Communication line check, miscabling  
check  
Power supply check for central control  
(Central control remote control, etc.)  
and indoor unit  
2. Communication check (XY terminal)  
3. Indoor P.C. board check  
4. Central control check  
unit)  
(Communication P.C. board)  
Error in 4-way valve system  
Indoor heat exchanger  
temperature rise after start of  
cooling operation.  
Indoor heat exchanger  
temperature fall after start of  
heating operation.  
Operation  
continues.  
Displayed when  
error is detected  
1. Check 4-way valve.  
2. Check 2-way valve and non-return  
valve.  
3. Check indoor heat exchanger sensor  
(TC).  
4. Check indoor P.C. board  
(Main P.C. board).  
Error in other cycles  
Operation  
continues.  
Displayed when  
error is detected  
1. Compressor case thermo operation.  
2. Coming-off of detection part of indoor  
heat exchanger sensor.  
Indoor heat exchanger temp  
(TC) does not vary after start of  
cooling/ heating operation.  
3. Check indoor heat exchanger sensor  
(TC).  
*
4. Check indoor P.C. board  
(Main P.C. board).  
[MODE] lamp  
5Hz flash  
Coming-off, disconnection or  
short of indoor temp sensor (TA)  
Operation  
continues.  
Displayed when  
error is detected  
1. Check indoor temp sensor (TA).  
2. Check indoor P.C. board  
(Main P.C. board).  
Coming-off, disconnection or  
short of indoor temp sensor (TC)  
Operation  
continues.  
Displayed when  
error is detected  
1. Check indoor temp sensor (TC).  
2. Check indoor P.C. board  
(Main P.C. board).  
Coming-off, disconnection or  
short of indoor temp sensor  
(TCJ)  
Operation  
continues.  
Displayed when  
error is detected  
1. Check indoor temp sensor (TCJ).  
2. Check indoor P.C. board (Main P.C.  
board).  
[MODE] lamp  
5Hz flash  
Error in indoor fan system  
Revolutions frequency error of fan  
All stop  
Displayed when  
error is detected  
1. Check indoor fan motor connector  
circuit (CN210).  
2. Check indoor fan.  
3. Check indoor P.C. board  
(Main P.C. board).  
Error in indoor unit or other  
positions  
1. EEPROM access error  
Operation  
continues.  
Displayed when  
error is detected  
1. Check indoor P.C. board  
(EEPROM and peripheral circuits)  
(Main P.C. board).  
Outside error input  
Detected by input voltage level  
from outside devices  
Operation  
continues.  
Displayed when  
error is detected  
1. Check outside devices.  
2. Check indoor P.C. board  
(Main P.C. board).  
Outside interlock input  
Detected by input voltage level  
from outside devices  
All stop  
Displayed when  
error is detected  
*: No display in the setting at shipment  
– 49 –  
Table 10-2-3  
Operation of diagnostic function  
Judgement and action  
Check code  
Symptom  
Unit status  
Condition  
Inverter over-current protective circuit  
operates.  
(For a short time)  
All stop  
Displayed when  
error is detected  
1. Inverter immediately stops even if restarted.  
Compressor rare short  
2. Check IPDU.  
Cabling error  
Error on current detection circuit  
Current value is high at AC side even  
while compressor stops.  
All stop  
Displayed when  
error is detected  
1. Compressor immediately stops even if restarted.  
: Check IPDU.  
2. Phase-missing operation of power supply  
Phase of power supply is missed.  
Check power voltage of R, S, T.  
Coming-off, disconnection or short of  
outdoor temp sensor  
All stop  
All stop  
All stop  
Displayed when  
error is detected  
1. Check outdoor temp sensor (TE, TS).  
2. Check CDB.  
Coming-off, disconnection or short of  
outdoor temp sensor  
Displayed when  
error is detected  
1. Check outdoor temp sensor (TD).  
2. Check CDB.  
Compressor drive output error  
Tin thermistor temp, Tin error  
(IPDU heat sink temp. is high.)  
Communication error between IPDU  
Connector coming-off between CDB and  
IPDU  
Displayed when  
error is detected  
1. Abnormal overload operation of refrigerating  
cycle  
2. Loosening of screws and contact error of IPDU  
and heat sink  
3. Cooling error of heat sink  
4. Check cabling of CDB and IPDU.  
Compressor does not rotate. (Over-current All stop  
protective circuit works when constant time  
passed after activation of compressor.)  
Displayed when  
error is detected  
1. Compressor error (Compressor lock, etc.)  
: Replace compressor.  
2. Cabling trouble of compressor (Phase missing)  
Discharge temp error  
Discharge temp over specified value was  
detected.  
All stop  
Displayed when  
error is detected  
1. Check refrigerating cycle. (Gas leak)  
2. Error of electron control valve  
3. Check pipe sensor (TD).  
Compressor breakdown  
Operation frequency lowered and stops  
though operation had started.  
All stop  
Displayed when  
error is detected  
1. Check power voltage. (AC200V±20V)  
2. Overload operation of refrigerating cycle  
3. Check current detection circuit at AC side.  
High-voltage protection error by TE sensor All stop  
TE temp over specified value was  
detected.  
Displayed when  
error is detected  
1. Overload operation of refrigerating cycle  
2. Check outdoor temp sensor (TE).  
DC outdoor fan motor error  
IDC operation or lock was detected by  
DC outdoor fan driving.  
All stop  
Displayed when  
error is detected  
1. Position detection error  
2. Over-current protection circuit operation of  
outdoor fan drive unit  
Check CDB.  
Refer to Judgment of outdoor fan.  
Error on IPDU position detection circuit  
All stop  
Displayed when  
error is detected  
1. Position detection circuit operates even if driving  
by removing 3P connector of compressor.  
Replace IPDU.  
Coming-off, disconnection or short of  
outdoor temp sensor  
Operation  
continues.  
Displayed when  
error is detected  
1. Check outdoor temp sensor (TO).  
2. Check P.C. board.  
– 50 –  
10-3. Troubleshooting for Each Check Code  
[1A error]  
Are connections of CN301 and  
CN300 of CDB correct?  
YES  
Does the fan rotate without trouble  
when handling the fan with hands under condition  
of removing CN301 and CN300 from CDB?  
NO  
NO  
CN301  
YES  
The status that the resistance values  
between leads below are 50 to 80 Ω  
for 40 W motor (ICF-140-43) and 25 to 55 Ω  
for 60 W motor (ICF-140-63-1) is normal.  
Between 1 (Red lead) and 2 (White lead)  
Between 2 (White lead) and 3 (Black lead)  
Between 3 (Black lead) and 1 (Red lead)  
of motor winding of connector (CN301)  
CN300  
YES  
The status that there is  
5k to 20kresistance values between  
1 (Yellow lead) and 4 (Pink lead)  
of motor position detection of connector  
(CN300, CN302) is normal.  
For RAV-SM560AT-E, CN300 changes to  
CN301, and CN301 to CN300, respectively.  
NO  
YES  
Normal fan motor  
(CDB error)  
Defective fan motor  
NOTE :  
However, GND circuit error inside of the motor is rarely detected even if the above check is carried out. When  
the circuit does not become normal even if P.C. board has been replaced, replace outdoor fan motor.  
RAV-SM560AT-E  
Control P.C. board  
CN300  
RAV-SM800AT-E  
CDB P.C. board  
CN301  
Objective P.C. board  
Fan motor winding  
Motor position detection  
CN301  
CN300  
– 51 –  
[14 error]  
NO  
NO  
Is power voltage normal?  
YES  
Improve the power supply line.  
Check and correct circuit cables.  
Correct connection of connector.  
Check and correct reactor connection.  
Are connections of  
cabling/connector normal?  
YES  
* For RAV-SM560AT-E,  
check RY01 on the control P.C. board.  
Is not 14 errors output  
when an operation is performed by  
removing 3P connector of compressor?  
YES  
NO  
Does RY01 relay of  
IPDU operate?  
NO  
YES  
* Single-phase type is not  
provided to RAV-SM560AT-E.  
Replace IPDU.  
YES  
Is not AC fuse fused?  
NO  
* Replace control P.C. board  
of RAV-SM560AT-E.  
Replace IPDU.  
NO  
Is compressor normal?  
YES  
* Replace control P.C. board  
of RAV-SM560AT-E.  
Check IPDU.  
Defect Replace  
Check rare short of compressor trouble.  
Defect Replace  
[16 error]  
NO  
NO  
Are connections of  
cable/connector normal?  
Check and correct circuit cabling  
such as cabling to compressor.  
YES  
Is compressor normal?  
YES  
YES  
Is not earthed?  
NO  
Compressor error  
Compressor error  
Replace  
Replace  
YES  
Is not winding shorted?  
(Is resistance between windings 0.6 to 1.2  
?)  
NO  
YES  
Is not winding opened?  
NO  
Compressor error  
Replace  
Check IPDU P.C. board  
Defect  
Replace  
– 52 –  
[18 error]  
Are connections of  
TE/TS sensor connectors of  
CDB CN604/CN605 normal?  
NO  
Correct connection of connector.  
YES  
* (For RAV-SM560AT-E, CN600TE sensor and CN603 TS sensor)  
NO  
Are characteristics of TE/TS sensor  
resistance values normal?  
Replace TE and TS sensors.  
* Refer to Characteristics-3.  
YES  
Check CDB.  
* For RAV-SM560AT-E, replace the control B.C. board  
Defect  
Replace  
[19 error]  
NO  
Is connection of TD sensor connector  
of CDB CN600 normal?  
Correct connection of connector.  
YES  
* (For RAV-SM560AT-E, CN601 on control P.C. board  
NO  
)
Are characteristics of TD sensor  
resistance value normal?  
Replace TD sensors.  
YES  
Check control P.C. board.  
* Refer to Characteristics-4.  
Defect  
Replace  
[1C error]* Except RAV-SM560AT-E  
Are connections of  
CDB CN800 and CDB IPDU CN06  
connectors normal?  
NO  
Correct connection of connector.  
YES  
YES  
NO  
Check cabling between IPDU  
and CDB and connector.  
Was the error just after  
power ON determined?  
Are cabling/connector normal?  
YES  
NO  
IPDU P.C. board error  
Defect  
Replace  
YES  
NO  
Improve and eliminate the cause.  
Is there no abnormal overload?  
NO  
Is IPDU P.C. board come to  
closely contact with heat sink?  
Correct mounting.  
YES  
IPDU P.C. board error  
Defect  
Replace  
– 53 –  
[1D error]  
NO  
NO  
NO  
Is power voltage normal?  
YES  
Improve power line.  
Check and correct circuit cabling such  
as cabling to compressor  
(phase missing) and connector.  
Are connections of  
cable/connector normal?  
YES  
NO  
NO  
Is there no  
slackened refrigerant?  
Compressor lock  
Replace  
Is compressor normal?  
YES  
YES  
Does electron expansion  
valve normally operate?  
Check TE and TS sensors.  
Check electron expansion valve.  
Replace  
Replace  
YES  
Check IPDU and CDB  
.
* For RAV-SM560AT-E, check control P.C. board.  
Defect  
Replace  
Defect  
Replace  
[1E error]  
NO  
NO  
Is protective control such as  
discharge temprelease control normal?  
Are connections of  
cable/connector normal?  
Correct the cabling and  
connection of connector.  
YES  
YES  
Check parts. Defect  
Replace  
NO  
Check and correct the charged  
refrigerant amount.  
Is charged refrigerant amount normal?  
YES  
YES  
Is not abnormal overload?  
NO  
Improve and delete the cause  
NO  
Are characteristics of  
TD sensor resistance value normal?  
Replace TD sensor.  
Check CDB.  
* Refer to Characteristics-4.  
YES  
Defect  
Replace  
* For RAV-SM560AT-E, check control P.C. board.  
[1F error]  
NO  
Is power voltage normal?  
Improve power line.  
YES  
YES  
NO  
Is not abnormal overload?  
NO  
Improve and delete the cause.  
Is the circuit detected by  
current sensor normal?  
Check and correct circuit cables.  
Check IPDU.  
YES  
Defect  
Replace  
* For RAV-SM560AT-E, check control P.C. board.  
– 54 –  
[21 error]  
Is high-voltage  
protective operation by  
TE sensor normal?  
NO  
YES  
NO  
Is connection of cabling  
connector normal?  
Correct connection of  
cabling connector.  
YES  
Check TE sensor.  
Defect  
Replace  
NO  
Does cooling outdoor fan  
normally operate?  
YES  
NO  
NO  
Is connection of  
connector normal?  
Correct connection of  
connector.  
YES  
Is fan motor normal?  
YES  
Replace fan motor.  
NO  
Does electron control  
valve normally operate?  
YES  
YES  
NO  
Do not TD and TO sensors  
come off the detection part?  
Correct coming-off.  
Check TE, TC, TS sensors.  
Replace electron expansion valve.  
NO  
Are characteristics of  
TD, TO, TC sensor resistance  
values normal?  
Replace TD, TO,  
and TC sensors.  
YES  
* Refer to Characteristics-3 and 4.  
Check charged refrigerant amount.  
Check liquid/gas valves.  
Check CDB.  
Defect Replace  
Check abnormal overload.  
* For RAV-SM560AT-E, check control P.C. board.  
– 55 –  
Relational graph of temperature sensor resistance value and temperature  
20  
10  
0
40  
30  
TA sensor  
TC, TCJ sensor  
Caracteristics-2  
Caracteristics-1  
Resistance  
(k  
Resistance  
(k  
)
)
20  
10  
0
10 20 30  
40 50  
10  
0
10 20  
30 40 50 60 70  
Temperature [°C]  
Temperature [°C]  
TE, TO, TS sensor  
20  
200  
Caracteristics-3  
Resistance  
(k  
(10°C or lower)  
100  
Resistance  
(k  
)  
)  
(10°C or higher)  
10  
0
0
10  
0
10 20 30  
40 50 60 70  
Temperature [°C]  
TD sensor  
20  
200  
Caracteristics-4  
Resistance  
(k  
(50°C or lower)  
100  
Resistance  
(k  
(50°C or higher)  
10  
)  
)  
0
0
50  
100  
Temperature [°C]  
– 56 –  
10-4 Compressor does not operate.  
<Primary check>  
(1) Is the preset temperature higher than the room temperature in cooling operation?  
(2) Is the crossover cable connected properly?  
<Inspection procedure>  
-Cooling only model-  
Turn on power supply.  
Refer to 9-6-1 Power  
can not be turned on .  
NO  
Does OPERATION lamp blink?  
YES  
Thermo sensor or heat  
exchanger sensor  
is defective.  
Is resistance value of thermo  
sensor (TA) and heat exchanger  
sensor (TC) normal?  
Does miniature relay RY04  
switch on and off due to  
temperature changes?  
NO  
NO  
NO  
YES  
YES  
Replace thermo  
sensor or heat  
exchanger sensor.  
Microcontroller is defective.  
Is it possible to detect  
AC 220 240 V between  
2 and 3 on the terminal block?  
Miniature relay RY04 is defective.  
Replace P.C. board.  
YES  
NO  
NO  
NO  
Rewire or replace  
defective cords.  
Are all of compressor  
cords normal?  
YES  
Is compressor motor  
winding normal?  
(Check winding resistor.)  
Compressor is defective.  
Capacitor is defective.  
Replace compressor.  
Replace capacitor.  
YES  
Is capacitor for  
compressor normal?  
YES  
NO  
NO  
Is overload relay normal?  
YES  
Overload relay is defective.  
Compressor is defective.  
Replace overload relay.  
Replace compressor.  
Does compressor start?  
YES  
Does compressor stop  
after a while?  
YES  
Is gas quantity normal?  
(Check gas pressure.)  
NO  
Supply gas.  
Gas shortage (Gas leak)  
YES  
Compressor is defective.  
YES  
Replace P.C. board.  
– 57 –  
<Inspection procedure>  
-Cooling and heating model-  
Turn on power supply.  
Refer to item Power  
can not be turned on .  
NO  
Does OPERATION  
lamp blink?  
YES  
Refer to 9-9 Troubleshooting  
for Remote Control .  
NO  
Is it possible to start  
unit by remote control?  
YES  
Is it possible to detect  
DC 15 60 V between  
2 and 3 on terminal block?  
Check TA and TC sensors  
or refer to 01 04 in Table 9-4-1.  
NO  
NO  
NO  
YES  
Connect crossover  
cable properly.  
Is crossover cable normal?  
YES  
Is it possible to detect  
AC 12 V on secondary side  
(CN06) of transformer?  
Replace outdoor  
transformer.  
YES  
NO  
Replace outdoor  
P.C. board.  
Is it possible to detect  
DC 5 V at Q60 and 12 V at Q50?  
YES  
Refer to item 9-8-3 How to  
check outdoor P.C. board.  
NO  
All lamps on  
indoor unit normal?  
YES  
Are TD and TE sensors normal?  
(TD=17.9 kat 50°C)  
NO  
Replace sensors.  
(TE=10 kat 25°C)  
YES  
NO  
NO  
Is it possible to detect  
AC 220 240 V at CN11?  
Replace outdoor  
P.C. board.  
YES  
Does MG switch operate?  
Replace MG switch.  
(Next Page)  
– 58 –  
YES  
NO  
NO  
Rewire or replace  
defective cords.  
Are all of compressor cords normal?  
YES  
Is compressor motor winding normal?  
(Check winding resistor.)  
Compressor is defective.  
Replace compressor.  
YES  
NO  
NO  
NO  
NO  
Is capacitor for compressor normal?  
YES  
Replace capacitor.  
Replace overload relay.  
Replace compressor.  
Supply gas.  
Capacitor is defective.  
Is overload relay normal?  
YES  
Overload relay is defective.  
Does compressor start?  
YES  
Compressor is defective.  
Gas shortage (Gas leak)  
Does compressor stop after a while?  
YES  
Is gas quantity normal?  
(Check gas pressure.)  
YES  
Compressor is defective.  
YES  
Replace P.C. board.  
– 59 –  
11. DETACHMENTS  
11-1. Indoor Unit  
No.  
Part name  
Procedures  
Remarks  
Air Inlet grille  
1
<How to remove the Air inlet grille>  
1) Stop the operation of the Air conditioner  
and turn off its main power supply.  
2) Open the Air inlet grille with both hands.  
Air inlet grille  
3) Unfasten 3 screws (about two to three  
rounds) for fixing the Panel arms.  
4) Move the Air inlet grille toward.  
Panel arm  
5) Remove the Grille stopper from the axis of  
the Front panel. After that, remove the Air  
inlet grille.  
Grille stopper  
Air inlet grille  
Panel arm  
6) Remove the Panel arms from the Front panel.  
<How to install the Air inlet grille>  
1) Insert three Panel arms on the Air inlet  
grille and fix each securely by screws.  
2) Set the Air inlet grille arm to the axis of the  
Front panel.  
3) Insert the Grille stopper to the correct  
position and fix it securely with screws.  
4) Push the Air inlet grille to the correct position.  
– 60 –  
No.  
Part name  
Procedures  
Remarks  
Front panel  
2
<How to remove the Front panel>  
1) Remove the Air inlet grille. (1)  
2) In case of the Drain hose is installed  
through the Front panel.  
: Remove the Drain band from the Front  
panel.  
: Cut away the Opening base for piping  
from Front panel and keep parts.  
Drain panel  
Drain band  
Cap screws  
3) Open 3 Cap screws and remove the  
screws.  
Front Panel  
4) Remove 5 screws fixing the Front panel.  
Screws  
5) Remove the hooks of the Panel LED nearly  
side from the Drain pan.  
(Continue)  
– 61 –  
No.  
Part name  
Procedures  
Remarks  
Front panel  
2
6) Remove both side hooks and remove the  
Front panel by turn to air inlet part  
direction.  
Hook  
<How to install the Front panel>  
1) In case of the Drain hose installation  
through the Front panel, install the opening  
base for piping in the Back body by a screw  
(M4 x 12). Prepare it by yourself.  
2) Fit the Front panel in the Drain pan. Then  
fix it in the Drain pan with 2 hooks in the  
center of the air outlet.  
3) Fix 5 hooks around the Front panel with  
conformation the Guide-rib is inserting into  
the Back body.  
4) Fix 8 screws and close 3 Cap screws.  
5) Install the Drain band into the Front panel.  
6) Check the gap between the Front panel  
and the Back body.  
Guide-rib  
3
<How to remove the Drain pan>  
Drain pan  
assembly  
1) Remove the Air inlet grille and the Front  
panel. (1, 2)  
2) Remove the Louver motor from the Drain  
pan.  
Louver motor  
Electrical wire  
3) Remove the shaft of Horizontal louver.  
4) Remove the LED base and Electrical wire.  
LED base  
Shaft of Horizontal lover  
TA sensor  
Drain hose  
5) Remove the TA sensor wire.  
6) Remove the Drain hose.  
(Continue)  
– 62 –  
No.  
Part name  
Drain pan  
assembly  
Procedures  
Remarks  
Screw  
3
7) Remove 7 screws and remove the Drain  
pan assembly.  
Drain Pan  
Screw  
Electrical parts  
assembly  
4
<How to remove the Electrical parts assembly>  
Refrigeration  
assembly  
1) Remove the Air inlet grille, the Front panel  
and the Drain pan assembly. (1, 2, 3)  
2) Remove the Terminal cover.  
TC sensor  
Connecting  
cable  
Earth wire  
Cord clamp  
3) Unfasten the screw of Cord clamp and  
disconnect the connecting cable.  
4) Remove the Connector cover and  
disconnect the Fan motor cords.  
TCJ  
sensor  
5) Remove the TC sensor, TCJ sensor and  
earth wire from Refrigeration assembly.  
6) Remove the Electrical parts assembly.  
NOTE : When install the electrical parts  
assembly, fix the screw after the Back body  
is fixed.  
Electrical parts  
assembly  
Fan motor cords  
5
<How to remove the Refrigeration assembly>  
Refrigeration  
assembly  
1) Remove the Air inlet grille, the Front panel  
and the Drain pan assembly. (1, 2, 3)  
2) Stop the gas at the Outdoor unit.  
3) Remove 2 pipes from the Refrigeration  
assembly.  
TCJ sensor  
TC sensor  
Pipe holder  
Earth wire  
4) Remove the TC sensor and TCJ sensor  
from holder.  
5) Remove the pipe holder.  
6) Remove the earth wire.  
(Continue)  
– 63 –  
No.  
Part name  
Procedures  
Remarks  
Refrigeration  
assembly  
5
7) Remove 2 screws and remove the  
refrigeration assembly with pushing it to  
right hand.  
2 Screws  
Fan cover  
6
<How to remove the Multiblade fan and  
Fan motor>  
Multiblade fan  
and Fan motor  
1) Remove the Air inlet grille and the Front  
panel. (1, 2)  
2) Disconnect 2 connectors.  
3) Remove the Fan covers.  
4) Remove the Motor band with holding the  
Fan motor and then remove the Fan motor  
with the Multi-blade fans.  
Motor band  
Motor  
2 Connectors  
Multi-blade fan  
5) Unfasten the Set-screw and remove the  
Multi-blade fans.  
– 64 –  
11-2. Outdoor Unit (RAV-SM560AT-E)  
No.  
Part name  
Procedure  
CAUTION  
Remarks  
 Common  
procedure  
Valve  
cover  
Never forget to put on the gloves at  
working time, otherwise an injury will be  
caused by the parts, etc.  
1. Detachment  
1) Stop operation of the air conditioner, and  
turn off the main switch of the breaker for  
air conditioner.  
2) Remove the valve cover.  
(ST1T Ø4 x 10L, 1 pc.)  
Wiring  
cover  
• After removing screw, remove the valve  
cover pulling it downward.  
3) Remove wiring cover (ST1T Ø4 x 10L, 2  
pcs.), and then remove connecting cable.  
4) Remove the upper cabinet.  
(ST1T Ø4 x 10L, 2 pcs.)  
• After taking off screws, remove the  
upper cabinet pulling it upward.  
Upper cabinet  
2. Attachment  
1) Attach the waterproof cover.  
CAUTION  
Be sure to attach a waterproof cover.  
If it is not attached, there is a possibility  
that water enters inside of the outdoor unit.  
Water-proof  
cover  
Cord clamp  
2) Attach the upper cabinet.  
(ST1T Ø4 x 10L, 2 pcs.)  
• Hook the rear side of the upper cabinet  
to claw of the rear cabinet, and then put  
it on the front cabinet.  
Rear cabinet  
3) Perform cabling of connecting cables, and  
fix with cord clamp.  
(ST1T Ø4 x 10L 3 pcs.)  
4) Attach the wiring cover.  
(ST1T Ø4 x 10L, 2 pcs.)  
Claw  
5) Attach the valve cover.  
(ST1T Ø4 x 10L, 1 pc.)  
• Insert the upper part of the upper  
cabinet, set hooking claw of the valve  
cover to the slit (at three positions) of the  
main body, and then attach it pushing  
upward.  
– 65 –  
No.  
Part name  
Procedure  
Remarks  
Front cabinet  
1. Detachment  
Motor support  
1) Perform work of item 1 of .  
2) Remove screws (ST1T Ø4 x 10L, 2 pcs.)  
of the front cabinet and the inverter cover.  
3) Take off screws of the front cabinet and  
the bottom plate. (ST1T Ø4 x 10L 3 pcs.)  
4) Take off screws of the front cabinet and  
the motor support.  
(ST1T Ø4 x 10L, 2 pcs.)  
• The left side of the front side if made to  
insert to the rear cabinet, so remove it  
pulling upward.  
For single-phase type models,  
also take off this screw  
Front cabinet  
Front cabinet (Left side)  
3. Attachment  
1) Insert hook at the left side of the front side  
into the rear cabinet.  
2) Hook the lower part at the right side of the  
front to concavity of the bottom plate.  
Insert the hook of the rear cabinet into the  
slit of the front cabinet.  
Slit  
Claw  
3) Attach the removed screws to the original  
positions.  
Slit  
Hook  
Cord clamp  
Front cabinet  
Concavity at  
bottom plate  
Lower  
slit  
– 66 –  
No.  
Part name  
Procedure  
Remarks  
ƒ Inverter  
1. Detachment  
1) Perform work of item 1 of .  
Screws  
assembly  
2) Take off screws of the upper part of the  
front cabinet.  
• If removing the inverter cover under this  
condition, P.C. board can be checked.  
Front cabinet  
• If there is no space in the upper part of  
the upper cabinet, perform work of .  
Inverter cover  
CAUTION  
Be careful to check the inverter because  
high-voltage circuit is incorporated in it.  
3) Perform discharging by connecting + , –  
polarities by discharging resistance  
(approx. 100, 40W) or plug of soldering  
iron to + , – terminals of the C14  
(printed as “CAUTION HIGH VOLTAGE”)  
electrolytic capacitor (500µF) of P.C.  
board.  
Cord clamp  
WARNING  
The electrolytic capacitor may not nor-  
mally discharge according to error con-  
tents and the voltage may remain.There-  
fore, be sure to discharge the capacitor.  
Screws  
WARNING  
Plug of  
soldering iron  
For discharging, never use a screwdriver  
and others for short-circuiting between +  
and – electrodes. As the electrolytic  
capacitor is one with a large capacity, it is  
very dangerous because a large electric  
spark will occur.  
Discharging  
position  
(Discharging  
period  
10 seconds  
or more)  
4) Take off screws (ST1T Ø4 x 10L, 2 pcs.)  
fixing the main body and the inverter box.  
Inverter  
assembly  
5) Remove various lead wires from the  
holder at upper part of the inverter box  
and wiring holder at right side of the  
terminal block.  
6) Remove the lead wire from the bundled  
part at left side of the terminal block.  
7) Pull the inverter box upward.  
8) Disconnect connectors of various lead  
wires.  
REQUIREMENT  
Remove the connectors  
with locking function by  
pushing the part indicated  
by the arrow mark.  
As each connector has a lock mechanism,  
avoid to remove the connector by holding  
the lead wire, but by holding the connector.  
– 67 –  
No.  
Part name  
Procedure  
Remarks  
Control P.C.  
1) Disconnect lead wires and connectors  
connected from the control P.C. board  
assembly to other parts.  
board assembly  
Take off  
earth screws.  
1. Lead wires  
• Connection with the power terminal  
block: 3 wires (Black, White, Orange)  
• Earth wire: 1 wire (Black)  
2. Connectors  
Power line  
• Connection with compressor:  
Remove 3P connector.  
Inverter box  
(Metal sheet)  
• Connection with reactor:  
Remove the relay connectors from  
P07, 08 (2P, White) and P12, 13 (2P,  
Yellow)  
Control P.C.  
board assembly  
P.C. board base  
CN300 : Outdoor fan (3P, White)  
CN301 : Position detection (5P, White)  
CN701 : 4-way valve (3P, Yellow)  
CN600 :TE sensor (2P, White)  
CN601 :TD sensor (3P, White)  
CN603 :TS sensor (3P, White)  
CN602 :TO sensor (3P, White)  
CN500 : Case thermo. (2P, White)  
CN703 : PMV (6P, White)  
Hooking claws  
(4 positions)  
2) Remove the inverter box (Metal plate).  
3) Remove the control board assembly from  
P.C. board base. (Remove the heat sink  
and the control board assembly as they  
are screwed.)  
Control P.C.  
board assembly  
NOTES:  
1. CN300, CN301 and CN701, etc. at the  
control board assembly side are connec-  
tors with locking function.Therefore,  
remove the connector while pushing the  
part indicated by an arrow mark.  
P.C. board base  
2. Remove 4 hooking claws of P.C. board  
base, and remove upward the heat sink  
with hands.  
4) Take off 3 screws fixing the heat sink and  
main control board assembly side, and  
replace the board with a new one.  
NOTE:  
Heat sink  
Inverter box  
(Metal sheet)  
When mounting a new board, check that the  
board is correctly set in the groove of the  
base holder of P.C. board base. Attach the  
P.C. board so that the heat sink comes  
securely contact with the metal sheet.  
– 68 –  
No.  
Part name  
Procedure  
Remarks  
Rear cabinet  
1) Perform works of items 1 of  and , ƒ.  
2) Take off fixed screws for the bottom plate.  
(ST1T Ø4 x 10L, 3 pcs.)  
3) Take off fixed screws for the heat ex-  
changer. (ST1T Ø4 x 10L, 2 pcs.)  
Rear cabinet  
4) Take off fixed screw for the valve mounting  
plate. (ST1T Ø4 x 10L, 1 pc.)  
Fan motor  
1) Perform works of items 1 of  and .  
2) Take off the flange nut fixing the fan motor  
and the propeller.  
Flange nut  
Turning it clockwise, the flange nut can  
be loosened. (To tighten the flange nut,  
turn counterclockwise.)  
3) Remove the propeller fan.  
4) Disconnect the connector for fan motor  
from the inverter.  
5) Take off the fixing screws (3 pcs.) holding  
by hands so that the fan motor does not  
fall.  
Loosen the nut by  
turning clockwise  
NOTE:  
Tighten the flange nut with torque 4.9Nm  
(50kgf/cm).  
Propeller fan  
Fan  
motor  
– 69 –  
No.  
Part name  
Procedure  
Remarks  
Compressor  
1) Perform works of items 1 of  and  
, ƒ, , .  
Partition plate  
2) Discharge refrigerant gas.  
3) Remove the partition plate.  
(ST1T Ø4 x 10L, 2 pcs.)  
4) Remove the noise-insulator.  
5) Remove the terminal covers of the  
compressor, and disconnect lead  
wires of the compressor and the  
compressor thermo assembly from  
the terminal.  
6) Remove pipes connected to the  
compressor with a burner.  
Compressor  
lead  
CAUTION  
Pay attention to that flame does not  
involve 4-way valve or PMV. (If doing  
so, a malfunction may be caused.)  
Case thermo  
7) Take off the fixing screws of the  
bottom plate and heat exchanger.  
(ST1T Ø4 x 10L, 2 pcs.)  
Heat exchanger  
8) Take off the fixing screws of the valve  
clamping plate to the bottom plate.  
Remove  
(Discharge pipe)  
9) Pull upward he refrigerating cycle.  
10) Take off nut fixing the compressor  
to the bottom place.  
Remove  
(Suction pipe)  
Screw  
Valve  
support board  
CAUTION  
When reconnecting the lead wires to  
the compressor terminals after  
replacement of the compressor, be  
sure to caulk the Faston terminal  
without loosening.  
Screws (2 pcs.)  
Compressor bolt (3 pcs.)  
ˆ Reactor  
1) Perform works of item 1 of  and ƒ.  
Partition  
plate  
2) First take off two screws (ST1T Ø4 x  
10L) of the reactor fixed to the reactor  
support.  
Reactor  
support board  
Reactor  
3) Remove the reactor support from the  
partition plate.  
(ST1T Ø4 x 10L, 4 pcs.)  
4) Take off two screws (ST1T Ø4 x 10L)  
directly attached to the partition plate.  
– 70 –  
No.  
Part name  
Procedure  
Remarks  
Pulse Modulating 1. Detachment  
Valve (PMV) coil  
1) Perform works of items  and .  
Positioning extrusion  
PMV body  
2) Release the coil from the concavity by  
turning it, and remove coil from the  
PMV.  
2. Attachment  
1) Put the coil deep into the bottom  
position.  
2) Fix the coil firmly by turning it to the  
concavity.  
Concavity  
PMV coil  
Š Fan guard  
1. Detachment  
1) Perform works of items 1 of , and .  
Minus screwdriver  
2) Remove the front cabinet, and put it  
down so that fan guard side directs  
downward.  
CAUTION  
Perform works on a corrugated card-  
board, cloth, etc. to prevent flaw on the  
product.  
3) Remove the hooking claws by pushing  
with minus screwdriver along with the  
arrow mark in the right figure, and  
remove the fan guard.  
Front cabinet  
Hooking claw  
Front cabinet  
2. Attachment  
1) Insert claws of the fan guard in the hole  
of the front cabinet. Push the hooking  
claws (10 positions) with hands and  
then fix the claws.  
CAUTION  
All the attaching works have completed.  
Check that all the hooking claws are  
fixed to the specified positions.  
Fan guard  
– 71 –  
11-3. Outdoor Unit (RAV-SM800AT-E)  
No.  
Part name  
Procedure  
Remarks  
 Common  
procedure  
CAUTION  
Never forget to put on the gloves at  
working time, otherwise an injury will be  
caused by the parts, etc.  
Front  
cabinet  
1. Detachment  
1) Stop operation of the air conditioner, and  
also turn off switch of the breaker.  
2) Remove the front panel.  
(ST1T Ø4 x 10L, 3 pcs.)  
• After taking off screws, remove the front  
panel by pulling it downward.  
3) Disconnect the connecting cables and  
power cord from the terminals and cord  
clamp.  
Upper plate  
of cabinet  
4) Remove the upper cabinet.  
(ST1T Ø4 x 10L, 6 pcs.)  
2. Attachment  
1) Attach the waterproof cover.  
Water-proof  
cove  
CAUTION  
Be sure to attach a waterproof cover.  
If it is not attached, there is a possibility  
that water enters inside of the outdoor unit.  
2) Attach the upper cabinet.  
(ST1T Ø4 x 10L, 6 pcs.)  
3) Connect the connecting cable and power  
cord at the terminal and fix them with cord  
clamp.  
CAUTION  
Using bundling band sold at a market, be  
sure to fix the power cables and indoor/  
outdoor connecting cables along the inter-  
unit cable so that they do not come to  
contact with the compressor, valves and  
cables at gas side, and the discharge pipe.  
4) Attach the front cabinet.  
(ST1T Ø4 x 10L, 3 pcs.)  
– 72 –  
No.  
Part name  
Procedure  
Remarks  
Discharge port 1. Detachment  
cabinet  
1) Perform work of item 1 of .  
Side cabinet  
Inverter  
2) Take off screws (ST1T Ø4 x 10L, 3 pcs.) of  
discharge port cabinet for the partition  
plate.  
3) Take off screws (ST1T Ø4 x 10L, 2 pcs.) of  
discharge port cabinet for the bottom  
plate.  
4) Take off screw (ST1T Ø4 x 10L, 1 pc.) of  
discharge port cabinet for the heat ex-  
changer.  
Fin guard  
5) Take off screws (ST1T Ø4 x 10L, 2 pcs.) of  
discharge port cabinet for the fin guard.  
2. Attachment  
1) Put the upper left side of the discharge  
port cabinet on the end plate of the heat  
exchanger, and then fix it with screw.  
(ST1T Ø4 x 10L, 1 pc.)  
2) Attach the removed screws to the original  
positions.  
Discharge port  
End plate of the  
heat exchanger  
ƒ Side cabinet  
1) Perform work of item 1 of .  
2) Remove screw fixing the inverter and the  
side cabinet. (ST1T Ø4 x 10, 1 pc.)  
3) Remove screws of the side cabinet and  
the valve support plate.  
(ST1T Ø4 x 10, 2 pcs.)  
4) Remove screw of the side cabinet and the  
cabling panel (Rear).  
(ST1T Ø4 x 10, 1 pc.)  
5) Remove screw of the side cabinet and the  
bottom plate. (ST1T Ø4 x 10, 1 pc.)  
Valve support plate  
Inverter  
Side cabinet  
6) Remove screw of the side cabinet and the  
fin guard (Heat exchanger).  
(ST1T Ø4 x 10, 2 pcs.)  
Side cabinet  
Valve support  
plate  
Cabling panel  
(Rear)  
– 73 –  
No.  
Part name  
Procedure  
Remarks  
Inverter  
1) Perform works of items of 1) to 5) of .  
assembly  
Screw  
2) Take off screw (ST1T Ø4 x 10L, 1 pc.) of  
the upper left part of the inverter cover.  
Inverter  
assembly  
• If removing the inverter cover under this  
condition, P.C. board can be checked.  
• If there is no space in the upper part of  
the upper cabinet, perform works of  
items 6) to 7) of (1) and remove the  
partition fixing plate.  
Holder  
(ST1T Ø4 x 10L, 1 pc.)  
CAUTION  
Be careful to check the inverter because  
high-voltage circuit is incorporated in it.  
Inverter  
cover  
3) Perform discharging by connecting the  
discharging resistance (approx. 100,  
40W) or plug of soldering iron to + , –  
terminals of the C10 too 13 (printed as  
“CAUTION HIGH VOLTAGE”) electrolytic  
capacitor (760µF) of P.C. board.  
Inverter  
assembly  
Plug of  
soldering iron  
WARNING  
The electrolytic capacitor may not nor-  
mally discharge according to error con-  
tents and the voltage may remain.There-  
fore, be sure to discharge the capacitor.  
Left time:  
10 sec. or more  
WARNING  
Inverter assembly  
For discharging, never use a screwdriver  
and others for short-circuiting between +  
and – electrodes. As the electrolytic  
capacitor is one with a large capacity, it is  
very dangerous because a large electric  
spark will occur.  
4) Remove various lead wires from the  
holder at upper part of the inverter box.  
5) Remove the hook for the partition plate  
(lower left side).  
Hook for the side  
cabinet (lower left side)  
Screw  
6) Remove the hook for the side cabinet  
(lower left side) and the screw, and lift up  
the inverter assembly upward. (ST1T Ø4 x  
10L, 1 pc.) In this time, cut off the band  
bundling each lead wire.  
7) Disconnect connectors of various lead  
wires.  
Remove the connectors  
with locking function by  
pushing the part indicated  
by the arrow mark.  
REQUIREMENT  
As each connector has a lock mechanism,  
avoid to remove the connector by holding  
the lead wire, but by holding the connector.  
– 74 –  
No. Part name  
Procedure  
Remarks  
Control P.C.  
board  
1) Remove the inverter box from P.C. board base.  
Inverter box (Metal sheet)  
2) Disconnect lead wires and connectors con-  
nected from the control P.C. board assembly to  
other parts.  
assembly  
1. Lead wires:  
With the power terminal block: 2 pcs.  
(Single phase) (Red, White)  
With the compressor: 3 pcs.  
(Red, White, Black)  
P.C. board  
base  
2. Connectors  
CN301 : Outdoor fan (3P, White) *Note 1)  
CN300 : Position detection (5P, White)  
CN700 : 4-way valve (3P, Yellow) *Note 1)  
CN702 : PMV coil (6P, White)  
Cycle control  
P.C. board  
assembly  
Inverter  
CN600 :TD sensor (3P, White)  
control  
P.C. board  
assembly  
CN605 :TS sensor (3P, White) *Note 1)  
CN604 :TE sensor (2P, White) *Note 1)  
CN601 :TO sensor (2P, White)  
Cycle control  
CN02 : Indoor/Outdoor connecting  
terminal block (2P, Black)  
P.C. board  
assembly  
CN500 : Case thermo (2P, White) *Note 1)  
CN14, CN15 : Reactor (3P, Relay  
connector, Blue) *Note 1)  
*Note 1)  
Remove the connector while releasing locking of  
the housing.  
3) Remove the control P.C. board assembly from  
P.C. board base. (Remove the heat sink and  
the inverter control P.C. board assembly as  
they are screwed.)  
Inverter  
control  
P.C. board  
assembly  
Note 2)  
Remove the heat sink upward by taking off two  
claws of P.C. base and holding the heat sink.  
Inverter  
control  
P.C. board  
assembly  
4) Take off three screws fixing the heat sink to the  
control P.C. board assembly.  
5) Mount a new control P.C. board assembly.  
Note 3)  
Groove for  
P.C. boaed  
When mounting a new board, check that it is  
correctly set in the groove of the base holder of  
P.C. board base.  
Inverter box  
(Metal sheet)  
Heat sink  
– 75 –  
No.  
Part name  
Procedure  
Remarks  
Fan motor  
1) Perform works of items 1) to 5), 7) of   
2) Remove the flange nut fixing the fan motor  
and the propeller fan.  
Flange  
nut  
• Loosen the flange nut by turning clock-  
wise. (To tighten the flange nut, turn it  
counterclockwise.)  
3) Remove the propeller fan.  
4) Remove the lead wire from the hook fixing  
the fan motor lead wires on the motor  
base. (Three positions)  
Loosen by turning  
clockwise  
5) Disconnect the connector for fan motor  
from the inverter.  
6) Take off the fixing screws (4 pcs.) while  
holding by hands so that the fan motor  
does not fall.  
NOTE :  
Tighten the flange nut with torque 9.8Nm  
(100kgf/cm).  
Propeller fan  
Fan motor  
Fixing claws for  
fan motor lead  
wires (3 positions)  
Motor base  
– 76 –  
No. Part name  
Procedure  
Remarks  
Compressor 1) Perform works of items , , ƒ, , and  
.  
Motor  
base  
2) Evacuate refrigerant gas.  
3) Disconnect the connector for fan motor from  
the inverter.  
4) Take off screws fixing the motor base to the  
bottom plate. (ST1T Ø4 x 10L, 2 pcs.)  
5) Remove the motor base together with the  
fan motor and the propeller fan.  
6) Take off screws fixing the partition plate to  
the valve support plate.  
Partition plate  
(ST1T Ø4 x 10L, 2 pcs.)  
7) Remove the valve support plate.  
(M6 x 4 pcs.)  
8) Take off screws of the partition plate and the  
bottom plate. (ST1T Ø4 x 10L, 2 pcs.)  
9) Take off screws of the partition plate and the  
heat exchanger. (ST1T Ø4 x 10L, 2 pcs.)  
Valve support  
Screw  
10) Remove the noise-insulator.  
11) Remove the terminal covers of the com-  
pressor, and disconnect lead wires of the  
compressor and the compressor thermo  
assembly from the terminal.  
Partition  
plate  
12) Remove pipes connected to the compres-  
sor with a burner.  
CAUTION  
Pay attention to that flame does not involve  
4-way valve or PMV. (If doing so, a malfunc-  
tion may be caused.)  
Valve  
support  
13) Pull the refrigerating cycle upward.  
14) Take off nut fixing the compressor on the  
bottom plate. (3 pcs.)  
15) Pull the compressor toward you.  
CAUTION  
Compressor  
lead wire  
When reconnecting the lead wires to the  
compressor terminals after replacement of  
the compressor, be sure to caulk the Faston  
terminal without loosening.  
Case thermo  
Remove  
(Discharge  
pipe)  
Remove  
(Suction  
pipe)  
Compressor  
nut (3 pcs.)  
– 77 –  
No.  
Part name  
Procedure  
Remarks  
ˆ Reactor  
1) Perform works of items 1 of  and .  
2) Take off screws fixing the reactor.  
(Ø4 x 10L , 2 pcs. per one reactor.  
An outdoor unit has two reactors on the  
partition plate.)  
Partition plate  
Screws  
Reactor  
Pulse Modulating 1. Detachment  
Valve (PMV) coil  
1) Perform works of items 1 of  and ƒ.  
Positioning extrusion  
PMV body  
2) Remove the coil from PMV body while  
pulling it upward.  
2. Attachment  
1) Match the positioning extrusion of the coil  
surely to the concavity of PMV body to fix it.  
Concavity  
PMV coil  
– 78 –  
No.  
Part name  
Procedure  
Remarks  
Š Fan guard  
1. Detachment  
1) Perform works of items 1 of  and .  
Discharge  
port cabinet  
2) Remove the air flow cabinet, and put it  
down so that the fan guard side directs  
downward.  
Bell mouth  
Perform work on a corrugated card-  
board, cloth, etc. to prevent flaw to the  
product.  
Remove  
two screws  
3) Take off screws fixing the bell mouth.  
(ST1Tf4 x 10L, 2 pcs.)  
Bell mouth  
4) Remove the bell mouth.  
5) Remove the hooking claws by pushing  
with minus screwdriver along with the  
arrow mark as shown in right figure.  
Discharge  
port cabinet  
2. Attachment  
1) Insert claw of the fan guard in hole of the  
discharge panel. Push the hooking claws  
(5 positions) with hands and fix the claws.  
Minus screwdriver  
Fan guard  
After all the attachment works are  
completed, check that all the hooking  
claws are fixed to the specified posi-  
tions.  
2) Mount the bell mouth by hooking three  
claws at upper side of the bell mouth in the  
slits on the discharge cabinet.  
3) After attachment, fix the bell mouth with  
screws. (ST1Tf4 x 10L, 2 pcs.)  
Hooking claw  
Discharge port cabinet  
Slit (3 positions)  
Bell mouth  
Claw (3 positions)  
– 79 –  
12. EXPLODED VIEWS AND PARTS LIST  
12-1. Indoor Unit (E-Parts Assy)  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
401  
401  
402  
403  
404  
405  
43T69348 PC Board (RAV-SM560XT-E)  
43T69349 PC Board (RAV-SM800XT-E)  
43T50004 Temperature sensor  
43T60002 Terminal Block, 3P  
43T62003 Cord clamp  
406  
407  
407  
408  
409  
43T50302 Temperature sensor  
43T69348 PC Board (RAV-SM560XT-E)  
43T69349 PC Board (RAV-SM800XT-E)  
43T08349 Switch cover  
43T50306 Temperature Sensor (TCJ Sensor)  
43T69315 Display unit  
– 80 –  
12-2. Indoor Unit  
220  
222  
217  
218  
227  
224  
214  
208  
207  
223  
208  
212  
216  
203  
235  
206  
219  
204  
225  
202  
221  
226  
213  
211  
210  
229  
209  
215  
233  
228  
231  
234  
235  
205  
201  
230  
232  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
43T09312 Air Inlet Grille  
43T00357 Panel Arm Assy  
43T00358 Front Panel Assy  
43T01004 Mark  
219  
220  
221  
222  
223  
224  
225  
226  
227  
228  
229  
230  
231  
232  
233  
43T03303 Back Body Assy  
43T09314 Vertical Louver  
43T49303 Pipe Holder  
43T19304 Cover Body L  
43T19305 Cover Body R  
43T19306 Cover Body LD  
43T19307 Bush Body R  
43T19308 Bush Body D  
43T82302 Installation Plate  
43T60314 Terminal Cover  
43T62303 Connector Cover  
43T83003 Remote control Holder  
43T69309 Wireless Remote control  
43T85399 Owner’s Manual  
43T49304 Flexible pipe, 12.7 Assy  
(SM560XT-E)  
43T79303 Drain Band  
43T80302 Air Filter  
43T00359 Cap Screw C  
43T00360 Cap Screw LR  
43T20303 Fan Cover  
43T20304 Motor Band Assy  
43T20305 Multiblade Fan  
43T19309 Screw Set (D-T)  
43T21325 Fan Motor  
43T72301 Drain Pan Assy  
43T79304 Drain Hose Assy  
43T19303 Louver Motor Assy  
43T09313 Horizontal Louver  
43T44331 Refrigeration Assy, 12.7  
(SM560XT-E)  
233  
43T49310 Flexible pipe, 15.9 Assy  
(SM800XT-E)  
234  
235  
43T80003 Filter Frame  
218  
43T44332 Refrigeration Assy, 15.9  
(SM800XT-E)  
43T00365 Grille Stopper Assy  
– 81 –  
12-3. Outdoor Unit (RAV-SM560AT-E)  
4
31  
INVERTER  
11  
25  
17  
2
30  
13,14  
29  
10  
9
18  
7
8
28  
21,  
22  
23,  
24  
6
26  
27  
12  
3
15  
16  
20  
5
19  
1
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
16  
17  
43105037 Cabinet, Front, PCM  
43100239 Cabinet, Back, PCM  
43042468 Base, Ass’y  
43005508 Cabinet, UP, PCM  
43119460 Guard, Fan, PP  
43119448 Cover, Packed, Valve  
43062230 Cover, Wiring, Ass’y  
43047667 Nut, Flange  
43020329 Fan, Propeller, PJ421  
4302C033 Motor, Fan, ICF-140-43-1  
4314G128 Condenser, Ass’y  
43041609 Compressor, DA130A1F-23F  
43050407 Thermostat, Bimetal  
43063317 Holder, Thermostat  
43097206 Bolt, Compressor, M6  
43049749 Rubber, Cushion  
18  
19  
43146617 Solenoid, Coil, LB64045  
43046385 Valve, Pulse, Modulating,  
SKV-18D26  
43046394 Coil, PMV, DKV-MOZS744BO  
43046392 Valve, Packed, 6.35, AO  
43147195 Bonnet, 1/2 IN  
43046393 Valve, Packed, 12.7,  
HKU-R410A-H4  
43147196 Bonnet, 1/4 IN, 6.4 CU  
43055521 Reactor, CH-57  
43063321 Holder, Sensor, 4-8, 9.52  
43063322 Holder, Sensor, 6-11.4, 12.7  
43063325 Holder, Sensor, 6-6.35, 8  
43063332 Holder, Sensor  
43089160 Cap, Waterproof  
43032441 Nipple, Drain  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
43046363 Valve, 4-WAY, VT7101D  
– 82 –  
12-4. Outdoor Unit (RAV-SM800AT-E)  
4
5
11  
37  
10  
9
8
2
32  
21,22  
36  
34  
24  
23  
30  
14  
7
35  
1
6
31  
3
13  
27  
19  
25  
28  
29  
18  
15  
33  
26  
16,17  
20  
12  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
01  
02  
03  
04  
05  
06  
07  
08  
09  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
43191634 Cabinet, Air Outled  
43191636 Cabinet, Front, Ass’y  
43191635 Cabinet, Side, Ass’y  
43191637 Panel, Upper  
20  
21  
22  
23  
43097204 Nut  
43046344 Valve, 4-WAY, CHV-0213  
43046348 Coil, Solenoid, VHV-01A150A1  
43046385 Valve, Pulse, Modulating,  
SKV-18D26  
43046386 Coil, PMV, DKV-MO25743BO  
43048066 Accumulator Ass’y  
43146584 Valve, Packed, 9.52DIA, HKT9.52  
43047401 Bonnet, 3/8 IN, 9.52 CU  
43146613 Valve, Ball, B5/8F  
43195029 Bonnet  
43005489 Guard, Fin  
43191630 Guard, Fan, PP-K  
43122065 Bell Mouth, Plastic  
43047667 Nut, Flange  
43120123 Fan, Propeller, PJ491, AS-G  
43121693 Motor, Fan, ICF-140-63-1  
4314G117 Condenser, Ass’y  
43191515 Panel, Front, Piping  
43191605 Panel, Back, Piping  
43119390 Hanger  
43041772 Compressor Ass’y  
43050407 Thermostat, Bimetal  
43063317 Holder, Thermostat  
43005482 Base Ass’y  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
43148169 Strainer  
43148176 Strainer  
43058266 Reactor, CH-47-Z-K  
43063321 Holder, Sensor, 4-8, 9.52  
43063322 Holder, Sensor, 6-11.4, 12.7  
43063325 Holder, Sensor, 6-6.35, 8  
43063332 Holder, Sensor  
43049739 Cushion, Rubber  
43032441 Nipple, Drain  
– 83 –  
12-5. Outdoor Unit (Inverter Assy, RAV-SM560AT-E)  
702  
TE Sensor  
TS Sensor  
TO Sensor  
TD Sensor  
701  
705  
703  
704  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
701  
702  
703  
43050334 Sensor, TD (F4), TD Sensor  
43050382 Sensor, TC (F6), TC Sensor  
43062228 Base, P.C. Board, ABS  
704  
705  
43160469 Terminal Block, 6P, AC250V, 20A  
4316V182 P.C. Board Ass’y, MCC-813  
– 84 –  
12-6. Outdoor Unit (Inverter Assy, RAV-SM800AT-E)  
INVERTER COVER  
708  
702  
701  
TO Sensor  
TE Sensor  
TS Sensor  
TD Sensor  
706  
INVERTER BOX  
707  
704  
Location  
No.  
Part  
No.  
Location  
No.  
Part  
No.  
Description  
Description  
701  
702  
704  
43050334 Sensor, TD (F4), TD Sensor  
43050382 Sensor, TC (F6), TC Sensor  
43160469 Terminal Block, 6P, AC250V, 20A  
706  
707  
708  
43162042 Base, P.C. Board, ABS  
4316V183 P.C. Board Ass’y, CDB, MCC-1398  
4316V184 P.C. Board Ass’y, IPDU, MCC-1359  
– 85 –  
T O S H IB A C A R R IE R ( T H A IL A N D ) C O . , LT D .  
1 4 4 / 9 MOO 5 , BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI,  
AMPHUR MUANG, PATHUMTHANI 1 2 0 0 0 , THAILAND.  

Panasonic Kx Ft37nz User Manual
Pioneer Automobile Parts Gbgt Series User Manual
Primera Technology Network Disc Duplication Printing System User Manual
Saft Batteries Automobile Parts Lsh User Manual
Sanyo Uf 811 User Manual
Sanyo Uf553443r User Manual
Schumacher Se 125a User Manual
Sharp Al 1340 User Manual
Shibaura N843l User Manual
Toshiba All In One Printer E Studio756 User Manual