STUDER Innotec
Xtender
INSTALLATION AND OPERATING INSTRUCTIONS
Unit combining inverter, battery charger and transfer system.
Xtender
XTH 3000-12
XTH 5000-24
XTH 6000-48
XTH 8000-48
+
BTS-01 temperature sensor
STUDER Innotec
Rue des Casernes 57
CH – 1950 Sion
Tel. +41 (0)27 205 60 80
Fax. +41 (0)27 205 60 88
Customer service:
Sales department:
Technical assistance:
Website:
Installation and operating Instructions
Xtender V1.3
Page 1
STUDER Innotec
Xtender
1 Introduction
Congratulations! You are about to install and use a device from the Xtender range. You have chosen
a high-tech device that will play a central role in energy saving for your electrical installation. The
Xtender has been designed to work as an inverter / charger with advanced functions, which can be
used in a completely modular way and guarantee the faultless functioning of your energy system.
When the Xtender is connected to a generator or network, the latter directly supplies the consumers,
and the Xtender works like a battery charger and backup device if necessary. The powerful battery
charger has an exceptional high efficiency and power factor correction (PFC) close to 1. It
guarantees excellent battery charging in all situations. The charge profile is freely configurable
according to the type of battery used or the method of usage. The charge voltage is corrected
depending on the temperature, thanks to the optional external sensor. The power of the charger is
modulated in real time dependent according to the demand of the equipment connected at the
Xtender output and the power of the energy source (network or generator). It can even temporarily
backup the source if the consumer demand exceeds the source capacity.
The Xtender continuously monitors the source to which it is connected (network or generator) and
disconnects itself immediately if the source is missing, disturbed or does not correspond to the
quality criteria (voltage, frequency, etc.). It will then function in independent mode, thanks to the
integrated inverter. This inverter, which has an extremely robust design, benefits from STUDER
Innotec’s many years of experience and expertise in this area. It could supply any type of load
without faults, enjoying reserves of additional power that is unmatched on the market. All your
equipment will be perfectly provided with energy and protected from power outages in systems
where energy supply is unpredictable (unreliable network) or voluntarily limited or interrupted, such
as hybrid installations on remote sites or mobile installations.
The parallel and/or three-phase network operation of the Xtender offers modularity and flexibility and
enables optimum adaptation of your system to your energy requirements.
The RCC-02/03 control, display and programming centre (optional) enables optimum configuration
of the system and guarantees the operator continuous control for all important configurations in the
installation.
In order to guarantee perfect commissioning and functioning of your installation, please read this
manual carefully. It contains all the necessary information relating to the functioning of the inverters /
chargers in the Xtender series. The setting up of such a system requires special expertise and may
only be carried out by qualified personnel familiar with the applicable local regulations.
2 General information
2.1 Operating instructions
This manual is an integral part of each inverter/charger from the Xtender series.
It covers the following models and accessories:
Xtender: XTH 3000-12 – XTH 5000-24 – XTH 6000-48 – XTH 8000-48
Temperature sensor: BTS-01
For greater clarity, the device is referred to in this manual as Xtender, unit or device, when the
description of its functioning applies indiscriminately to different Xtender models.
These operating instructions serve as a guideline for the safe and efficient usage of the Xtender.
Anyone who installs or uses an Xtender can rely completely on these operating instructions, and is
bound to observe all the safety instructions and indications contained. The installation and
commissioning of the Xtender must be entrusted to a qualified professional. The installation and
usage must conform to the local safety instructions and applicable standards in the country
concerned.
Installation and operating Instructions
Xtender V1.3
Page 3
STUDER Innotec
Xtender
2.2 Conventions
This symbol is used to indicate the presence of a dangerous voltage that is sufficient to
constitute a risk of electric shock.
This symbol is used to indicate a risk of material damage.
This symbol is used to indicate information that is important or which serves to optimise
your system.
All values mentioned hereafter, followed by a configuration no. indicate that this value may be
modified with the help of the RCC-02/03 remote control.
In general, the default values are not mentioned and are replaced by a configuration no. in the
following format: {xxxx}. The default values for this configuration are specified in the configuration
table, p. 34.
All configuration values modified by the operator or installer must be transferred into the same table.
If a parameter not appearing in the list (advanced configurations) has been modified by an
authorised person with technical knowledge, they will indicate the number of the modified
parameter(s), the specifications of the configuration(s) and the new value set, at the end of the same
table.
All figures and letters indicated in brackets refer to items of figures in the separate manual “Appendix
to the installation and operating instructions” supplied with the device.
The figures in brackets refer to elements belonging to the Xtender.
The uppercase letters in brackets refer to AC cabling elements.
The lowercase letters in brackets refer to battery cabling elements.
2.3 Quality and warranty
During the production and assembly of the Xtender, each unit undergoes several checks and tests.
These are carried out with strict adherence to the established procedures. Each Xtender has a serial
number allowing complete follow-up on the checks, according to the particular data for each device.
For this reason it is very important never to remove the type plate (appendix I – fig. 3b) which shows
the serial number. The manufacture, assembly and tests for each Xtender are carried out in their
entirety by our factory in Sion (CH). The warranty for this equipment depends upon the strict
application of the instructions appearing in this manual.
The warranty period for the Xtender is 2 years.
XCLUSION OF WARRANTY
2.3.1 E
No warranty claims will be accepted for damage resulting from handling, usage or processing that
does not explicitly appear in this manual. Cases of damage arising from the following causes are
notably excluded from the warranty:
•
Surge voltage on the battery input (for example, 48 V on the battery input of an XTH 3000-
12)
•
•
•
•
•
Incorrect polarity of the battery
The accidental ingress of liquids into the device or oxidation resulting from condensation
Damage resulting from falls or mechanical shocks
Modifications carried out without the explicit authorisation of Studer Innotec
Nuts or screws that have not been tightened sufficiently during the installation or
maintenance
•
•
•
Damage due to atmospheric surge voltage (lightning)
Damage due to inappropriate transportation or packaging
Disappearance of original marking elements
Installation and operating Instructions
Xtender V1.3
Page 4
STUDER Innotec
Xtender
XCLUSION OF LIABILITY
2.3.2 E
The placement, commissioning, use, maintenance and servicing of the Xtender cannot be the
subject of monitoring by Studer Innotec. For this reasons we assume no responsibility and liability for
damage, costs or losses resulting from an installation that does not conform to the instructions,
defective functioning or deficient maintenance. The use of a Studer Innotec inverter is the
responsibility of the customer in all cases.
This equipment is neither designed nor guaranteed to supply installations used for vital medical care
nor any other critical installation carrying significant potential damage risks to people or the
environment.
We assume no responsibility for the infringement of patent rights or other rights of third parties that
result from using the inverter.
Studer Innotec reserves the right to make any modifications to the product without prior notification.
2.4 Warnings and notes
GENERAL
2.4.1
This manual is an integral part of the device and must be kept available for the operator
and installer. It must remain close to the installation so that it may be consulted at any time.
The configuration table available at the end of the manual (p. 34) must be kept up to date in the
event of modification of the configurations by the operator or installer. The person in charge of
installation and commissioning must be wholly familiar with the precautionary measures and the
local applicable regulations.
When the Xtender is running, it generates voltage that can be potentially lethal. Work on or
close to the installation must only be carried out by thoroughly trained and qualified
personnel. Do not attempt to carry out ongoing maintenance of this product yourself. The
Xtender or the generator connected to it may start up automatically under certain
predetermined conditions.
When working on the electrical installation, it is important to be certain that the source of
DC voltage coming from the battery as well as the source of AC voltage coming from a
generator or network have been disconnected from the electrical installation.
Even when the Xtender has been disconnected from the supply sources (AC and DC), a
dangerous voltage may remain at the outputs. To eliminate this risk you must switch the
Xtender OFF using the ON/OFF button (1). After 10 seconds the electronics is discharged
and intervention may take place without any danger.
All elements connected to the Xtender must comply with the applicable laws and regulations.
Persons not holding written authorisation from Studer Innotec are not permitted to proceed with any
change, modification or repairs that may be required. Only original parts may be used for authorised
modifications or replacements.
This manual contains important safety information. Read the safety and working instructions
carefully before using the Xtender. Adhere to all the warnings given on the device as well as in the
manual, by following all the instructions with regard to operation and use.
The Xtender is only designed for interior use and must under no circumstances be subjected to rain,
snow or other humid or dusty conditions.
The maximum specifications of the device shown on the type plate, as at fig. 1b, must be adhered
to.
In the event of use in motorised vehicles, the Xtender must be protected from dust, splash water
and any other humid condition. It must also be protected from vibration by installing absorbent parts.
RECAUTIONS FOR USING THE BATTERIES
2.4.2 P
Lead-acid or gel batteries produce a highly explosive gas with normal use. No source of sparks or
fire should be present in the immediate vicinity of the batteries. The batteries must be kept in a well-
ventilated place and be installed in such a way as to avoid accidental short-circuits when connecting.
Installation and operating Instructions
Xtender V1.3
Page 5
STUDER Innotec
Xtender
Never try to charge frozen batteries.
When working with the batteries, a second person must be present in order to lend assistance in the
event of problems.
Sufficient fresh water and soap must be kept to hand to allow adequate and immediate washing of
the skin or eyes affected by accidental contact with the acid.
In the event of accidental contact of the eyes with acid, they must be washed carefully with cold
water for 15 minutes. Then immediately consult a doctor.
Battery acid can be neutralised with baking soda. A sufficient quantity of baking soda must be
available for this purpose.
Particular care is required when working close to the batteries with metal tools. Tools such as
screwdrivers, open-ended spanners, etc. may cause short-circuits. Consequently occurring sparks
may cause the battery to explode.
When working with the batteries, all metal jewellery such as rings, bracelet watches, earrings, etc.,
must be taken off. The current output by the batteries during a short-circuit is sufficiently powerful to
melt the metal and cause severe burns.
In all cases, the instructions of the battery manufacturer must be followed carefully.
3 Assembly and installation
3.1 Handling and moving
The weight of the Xtender is between 35 and 50kg depending upon the model. Use an appropriate
lifting method as well as help from a third party when installing the equipment.
3.2 Storage
The equipment must be stored in a dry environment at an ambient temperature of between
-20°C and 60°C. It stay in the location where it is to be used a minimum of 24 hours before being
set up.
3.3 Unpacking
When unpacking, check that the equipment has not been damaged during transportation and that
all accessories listed below are present. Any fault must be indicated immediately to the product
distributor or the contact given at the back of this manual.
Check the packaging and the Xtender carefully.
Standard accessories:
Installation and operating instructions, c.f. Appendix 1
Mounting plate – fig. 2a (18)
2 conduit glands for the battery cable
3.4 Installation site
The installation site for the Xtender is of particular importance and must satisfy the following criteria:
Protected from any unauthorised person.
Protected from water and dust and in a place with no condensation.
It must not be situated directly above the battery or in a cabinet with it.
No easily inflammable material should be placed directly underneath or close to the Xtender.
Ventilation apertures must always remain clear and be at least 15cm from any obstacle that may
affect the ventilation of the equipment according to fig. 2b.
In mobile applications it is important to select an installation site that ensures as low a vibration level
as possible.
Installation and operating Instructions
Xtender V1.3
Page 6
STUDER Innotec
Xtender
3.5 Fastening
The Xtender is a heavy unit and must be mounted to a wall designed to bear such a load.
A simple wooden panel is insufficient.
The Xtender must be installed vertically with sufficient space around it to guarantee adequate
ventilation of the device (see figs. 2a and 2b).
If the Xtender is installed in a closed cabinet this must have sufficient ventilation to guarantee an
ambient temperature that conforms to the operation of the Xtender.
Firstly, fit the mounting bracket (18) supplied with the device, using 2 Ø <6-8 mm> screws**.
Then hang the Xtender on the bracket. Fasten the unit permanently using 2 Ø <6-8 mm> screws**
on to the two notches located at the underside of the case.
**: These items are not delivered with the device.
It is imperative to ensure complete and safe fastening of the device. A device that is simply
hung may detach and cause severe damage.
In motor vehicles or when the support may be subject to strong vibrations, the Xtender must be
mounted on anti-vibration supports.
3.6 Connections
ENERAL RECOMMENDATIONS
3.6.1 G
The Xtender falls within protection class I (has a PE connection terminal). It is vital that a protective
earth is connected to the AC IN and/or AC OUT PE terminals. An additional protective earth is
located between the two fastening screws at the bottom of the unit (fig. 2b-(17)).
In all cases, the PE conductor for the equipment must at least be connected to the PE for
all equipment in protection class I upstream and downstream of the Xtender (equipotential
bonding). It is imperative that the legislation in force for the application concerned be
adhered to.
Tighten of the input (13) and output (14) terminals by means of a no. 3 screwdriver and those for the
“REMOTE ON/OFF” (7) and “AUX.CONTAC” (8) by means of a no. 1 screwdriver.
The cable sections of these terminals must conform to local regulations.
All connection cables as well as the battery cables must be mounted using cable restraints in order
to avoid any traction on the connection.
Battery cables must also be as short as possible and the section must conform with the applicable
regulations and standards. Sufficiently tighten the clamps on the “battery” inputs (fig. 4a (11) and
(12)).
EVICE CONNECTION COMPARTMENT
3.6.2 D
The unit’s connection compartment must remain permanently closed when in operation. It
is imperative to close the protection cap on the connection terminals after each intervention
in the device.
After opening, check that all sources of AC and DC voltage (batteries) have been
disconnected or put out of service.
Installation and operating Instructions
Xtender V1.3
Page 7
STUDER Innotec
Xtender
Fig. 4a
12
11
14
13
8
1
2
7
1 2 3
A
B
5
10
6
L
L
AUX1
AUX2
AC Input
AC O
utput
Warning!
9
Check battery polarity (+/-) before connecting
A wrong connexion may damage the systen
!
2
4
3
1
OFF
ON
Open
Terminated
Main
switch
Temp.
Sens.
Pos. Denomination Description
Comment
1
ON/OFF
Main switch
Main on/off switch
See chapter The real time clock 7.1 - p
24.
2
Temp. Sens Connector for the battery
temperature sensor
See chapter 6.4.2 – p. 24.
Only connect the original Studer BTS-01
sensor
3
Com. Bus
Double connector for
See chapter 4.5.9 – p. 14.
connecting peripherals such as The two termination switches (4) for the
the RCC002/03 or other
Xtender units
Switch for terminating the
communication bus.
communication bus both remain in
position T (terminated) except when both
connectors are in use.
4
5
6
7
O / T
(Open /
Terminated)
--
3.3 V (CR-2032) lithium ion type Used as a permanent supply for the
battery socket
internal clock. See chapter The real time
clock 6.2.11 - p 21.
--
Jumper for programming the
off/on switch by dry contact
See chapter 6.2.12 – p. 21 and fig. 8b
point (6) and (7). They are positioned at A-
1/2 and B-2/3 by default
REMOTE
ON/OFF
Connection terminals for dry
on/off remote connection.
See chapter 6.2.12– p. 21).
When the control via dry contact is not
being used, a bridge must be present
between the two terminals.
8
9
AUXILIARY
CONTACT
Auxiliary contact
(See chapter 6.2.10– p. 21)
Take care not to exceed the admissible
loads
--
Activation indicators for auxiliary See chapter 6.2.10– p. 21
contacts 1 and 2
10 L1/L2/L3
11 +BAT
Phase selection jumpers.
See chapter 6.3.1. – p.22.
Jumper default at position L1
Positive pole battery connection Carefully read chapter 4.5 – p.12
terminals Take care with the polarity of the battery
Installation and operating Instructions
Xtender V1.3
Page 8
STUDER Innotec
Xtender
12 -BAT
Negative pole battery
connection terminals
and when tightening the clamp.
See chapter 4.5.7 - p. 14.
Note: It is imperative that the PE terminal
be connected.
13 AC Input
Connection terminals for the
alternative power supply
(generator or public network)
Connection terminals for the
device output.
14 AC Output
See chapter 4.5.6 - p. 14.
Note: Increased voltages may appear on
the terminals, even in the absence of
voltage at the input of the inverter.
4 Cabling
The connection of the Xtender inverter / charger is an important installation step.
It may only be carried out by qualified personnel and in accordance with the applicable local
regulations and standards. The installation must always comply with these standards.
Pay attention that connections are completely tightened and that each wire is connected at the right
place.
4.1 Choice of system
The Xtender may be used in different system types, each of which must meet the standards and
particular requirements associated with the application or site of installation. Only an appropriately
qualified installer can advise you effectively on the applicable standards with regard to the various
systems and the country concerned.
Examples of cabling are presented in appendix I of this manual, fig. 5 and following. Please carefully
read the notes associated with these examples in the tables on p. 27 and following.
YBRID TYPE STAND ALONE SYSTEMS
4.1.1 H
-
The Xtender can be used as a primary supply system for grid-remote sites where a renewable
energy source (solar or hydraulic) is generally available and a generator is used as backup. In this
case, batteries are generally recharged by a supply source such as solar modules, wind power or
small hydropower systems. These supply sources must have their own voltage and/or current
regulation system and are connected directly to the battery. (Example, fig. 11)
When the energy supply is insufficient, a generator is used as a back-up energy source. This allows
the batteries to be recharged and direct supply to consumers via the Xtender transfer relay.
When the input voltage source is a low power generator (lower than the Xtender power) the
factory settings (adapted to grid-connection) must be modified according to the
“generator” column in the configuration table on p. 34.
RID CONNECTED EMERGENCY SYSTEMS
4.1.2 G
-
The Xtender can be used as an emergency system, also known as an uninterruptible power supply
(UPS) – enabling a reliable supply to a site connected to an unreliable network. In the event of an
interruption to the energy supply from the public network, the Xtender, connected to a battery,
substitutes the faulty source and enables a support supply to the users connected downstream.
These will be supplied as long as the energy stored in the battery allows. The battery will quickly be
recharged at the next reconnection to the public grid.
Various application examples are described in figs. 8a – 8c in appendix I.
The use of the Xtender as a UPS must be carried out by qualified personnel who have
been checked by the responsible local authorities. The diagrams in the appendix are given
for information and as a supplement. The applicable local standards and regulations must
be adhered to.
NTEGRATED MOBILE SYSTEMS
4.1.3 I
These systems are meant to be temporarily connected to the grid and ensure the supply of the
mobile system when this is disconnected from the grid. The main applications are for boats, service
Installation and operating Instructions
Xtender V1.3
Page 9
STUDER Innotec
Xtender
vehicles and leisure vehicles. In these cases, two separate AC inputs are often required, one
connected to the grid and the other connected to an on-board generator. Switching between two
sources must be carried out using an automatic or manual reversing switch, conforming to the
applicable local regulations. The Xtender has a single AC input.
Various application examples are described in figs. 10a – 10b – 10c).
ULTI UNIT SYSTEMS
4.1.4 M
-
Whatever system is selected, it is possible to realise systems composed of several units of the same
type and the same power output. Up to three Xtenders in parallel or three extenders forming a
three-phase grid or three times two with three Xtenders in parallel forming a three-phase / parallel
grid, may be thus combined.
4.2 Earthing system
The Xtender is a protection class I unit, which is intended for cabling in a grid type TT, TN-S or TNC-
S. The earthing of the neutral conductor (E) is carried out at a sole installation point, upstream of the
RCD circuit breaker (D).
The Xtender can be operated with any earthing system. In all cases it is imperative that the
protective earth be connected in compliance with the applicable standards and regulations. The
information, notes, recommendations and diagram mentioned in this manual are subject to local
installation regulations in every case. The installer is responsible for the conformity of the installation
with the applicable local standards.
OBILE INSTALLATION OR INSTALLATION CONNECTED TO THE GRID VIA PLUG CONNECTOR
4.2.1 M
When the input of the device is connected directly to the grid via a plug, the length of the cable must
not exceed 2 m and the plug must remain accessible.
In the absence of voltage at the input, the neutral and live are interrupted, thereby guaranteeing
complete isolation and protection of the cabling upstream of the Xtender.
The earthing system downstream of the Xtender is determined by the upstream earthing system
when the grid is present. In the absence of the grid, the earthing system downstream of the inverter
is in isolated mode. The safety of the installation is guaranteed by the equipotential bonding.
The connection (link) between the neutrals (C) upstream and downstream of the Xtender is
not permitted in this configuration.
This connection type guarantees the optimal continuity for supplying the Xtender loads. The first
isolation fault will not lead to an interruption in the supply.
If the installation requires the use of a permanent isolation controller this would have to be de-
activated when the TT network is present at the Xtender input.
All sockets and protection class I devices connected downstream of the Xtender must be
properly connected to the earth (earthed socket). The cabling rules above remain valid,
including fixed installations, in all cases where the Xtender input is connected to the grid via
a plug connector.
IXED INSTALLATION
4.2.2 F
The installation may be equivalent to a mobile installation (with interrupted neutral).
In a fixed installation where the neutral is connected to the earth at a single installation point
upstream of the Xtender, it is permissible to carry out a connection of the neutrals in order to
preserve an unchanged earthing system downstream, independent of the operating mode of the
Xtender. This choice has the advantage of keeping the protection devices downstream of the
Xtender. This connection can be executed according to the examples in appendix 1, or carried out
by modifying the configuration {1486}
In this case the appearance of the first fault will lead to the installation stopping or the disconnection
of the protection devices upstream and/or downstream of the Xtender.
Safety is guaranteed by the equipotential bonding and by any RCD circuit-breakers placed
downstream.
Installation and operating Instructions
Xtender V1.3
Page 10
STUDER Innotec
Xtender
This connection (C) is not permitted if a socket is installed upstream of the Xtender.
NSTALLATION WITH AUTOMATIC
4.2.3 I
NEUTRAL SWITCHING
PE-
In certain applications, it is desirable to keep the neutral upstream and downstream of the Xtender
separated (C) while reestablishing the earthing system (TN-S, TT or TNC-S) in the absence of
voltage at the input. This can be programmed by the configuration {1485} via the RCC-02/03
remote control. This modification must be carried out possessing technical knowledge, at the
responsibility of the installer and in conformity with the applicable regulations and standards.
This allows adherence to the requirements for an earth-neutral connection at the source.
4.3 Recommendations for dimensioning the system
IMENSIONING THE BATTERY
4.3.1 D
The battery capacity is dimensioned according to the requirements of the user – that is 5 to 10 times
its average daily consumption. The discharge depth of the battery will therefore be limited and the
service life of the battery will be extended.
On the other hand, the Xtender must have a battery capacity that is large enough to be able to take
full advantage of the performance of the equipment. The minimum capacity of the batteries
(expressed in Ah) is generally dimensioned in the following way: five times the rated power output of
the Xtender / the battery voltage. For example, the model XTH 8048 must have a battery of a
minimum capacity of 7000*5/48=730 Ah (C 10). Because of the inverter’s extreme overload capacity,
it is often recommended that this value be rounded up. An under-dimensioned battery may lead to
an accidental and undesired stopping of the Xtender in the event of high instances of use. This
stoppage will be due to a voltage that is insufficient on the battery, subject to a strong discharge
current.
The battery will be selected with regard to the greatest value resulting from the calculations set out
above.
The battery capacity determines the adjustment of the configuration {1137} “battery charge current”.
A value between 0.1 and 0.2 x C batt. [Ah] (C10) enables an optimum charge to be guaranteed.
The method proposed below is strictly indicative and in no way constitutes a guarantee of
perfect dimensioning. The installer is solely responsible for good dimensioning and
installation
IMENSIONING THE INVERTER
4.3.2 D
The inverter is dimensioned in such a way that the rated power output covers the power of all the
consumers which will be used at the same time. A dimensioning margin of 20 to 30% is
recommended to guarantee that the Xtender will work well in an ambient temperature of more than
25 °C.
IMENSIONING THE GENERATOR
4.3.3 D
The power output of the generator must be the same or more than the average daily power.
Optimally, it should be two or three times this power. Thanks to the smart boost function it is not
necessary to over-dimension the generator. Indeed, the loads those are temporarily higher than the
power of the generator will be supplied by the inverter. Ideally it should not have a power output by
phase that is less than half of the power of the Xtender(s) present at this phase.
The power available downstream of the inverter when the generator is working is the same
as the sum of the two powers.
Installation and operating Instructions
Xtender V1.3
Page 11
STUDER Innotec
Xtender
IMENSIONING THE ALTERNATIVE ENERGY SOURCES
4.3.4 D
In a hybrid system, the alternative energy sources such as the solar generator, wind power and
small hydropower should, in principle, be dimensioned in such a way as to be able to cover the
average daily consumption.
4.4 Wiring diagrams
The diagrams shown in the appendix of this document are subsidiary. The applicable local
installation regulations and standards must be adhered to.
The elements referred to with an uppercase letter denote the alternate current (AC) part.
The elements referred to with a lowercase letter denote the direct current (DC) part.
4.5 Connecting the battery
Lead batteries are usually available in 2 V, 6 V or 12 V block types. In the majority of cases, in order
to obtain an operating voltage that is correct for Xtender usage, several batteries must be connected
in series or in parallel depending on the circumstances.
In multi-unit systems, all Xtenders from the same system must be connected according to
the same battery bank.
The various cabling options are presented in figures 5a-5b (12 V), 5c-5e (24 V) and 6a to 6d (48 V) in
appendix I of this manual.
INIMUM BATTERY CABLE CROSS SECTION
4.5.1
M
-
XTH3000-12
XTH5000-24
XTH6000-48
XTH8000-48
90 mm2
90 mm2
70 mm2
90 mm2
The cable sections recommended above are valid for lengths less than 3 m. beyond this length it is
strongly recommended to over-section the battery cables.
The battery cables must also be as short as possible.
It is always preferable to keep the cable at the negative pole of the battery as short as possible.
ONNECTING THE BATTERY TENDER SIDE
4.5.2 C
(X
)
Insert the conduit glands supplied on the battery cable before tightening the cable clamp. Crimp the
cable clamps and fasten the conduit gland on the device. Repeat this for the second battery cable.
Fix the battery cables to the appropriate connections „+ Battery “and „- Battery “. The M8 screws
must be very well tightened.
INPUT PROTECTION
4.5.3 DC
In order to avoid any further loss and protection
redundancy, the Xtender does not have an
internal fuse. A protection device (f) must be
installed as close as possible to the battery and
sized as per the table opposite:
Unit
Fuse on the battery side
XTH-3000-12
XTH-5000-24
XTH-6000-48
XTH-8000-48
400 A
350 A
250 A
300 A
Installation and operating Instructions
Xtender V1.3
Page 12
STUDER Innotec
Xtender
BATTERY SIDE CONNECTION
4.5.4
-
Before connecting the battery, carefully check the voltage and polarity of the battery using
a voltmeter.
Incorrect polarity or surge voltage may seriously damage the device.
Prepare the batteries for connection: appropriate battery clamps, protection device (f), cable in good
conditions with correctly fitted clamps.
Fasten the negative cable on to the negative pole (-) of the battery and the positive cable on the
open protection device (f).
The battery cables must be protected by one of the following measures in all cases:
- protection device (fuse) at each pole
- protection device (fuse) on the pole connected to the earth
- mechanical envelope making an accidental short-circuit impossible.
When connecting the battery, a spark may occur when connecting the second pole. This
spark is due to the load of the internal filtering capacity of the Xtender.
When connecting the battery it is necessary to check that the configuration values of the Xtender
conform to the recommendations of the battery manufacturer. Non-conforming values may be
dangerous and/or seriously damage the batteries. The default values of the battery’s charge
threshold level are shown in fig. 3a and specified in the configuration table p.34. If they prove not to
conform, it is necessary to modify them via the RCC 02/03 remote control before connecting the
voltage sources on the AC input. Studer Innotec is not responsible for default values not
corresponding with the recommendations of the manufacturer.
If the factory settings are modified, the new values must be entered on the configuration table
on p. 34 of this manual. The default values proposed by Studer Innotec are the usual values for gel
batteries (VRLA or AGM).
The calibre of the protection device (f) must be adapted to the cable section and also mounted as
close as possible to the battery.
The clamps must be carefully fixed and tightened sufficiently to guarantee minimum loss.
Insufficient tightening may cause dangerous heating at the connection point.
For safety reasons, we recommend an annual check on the tightness of all connections.
For mobile installation the connections should be checked more frequently for tightness.
The cabling and connection of the installation should only be carried out by an appropriately qualified
professional. The installation material such as cables, connectors, distribution boxes, fuses, etc.
must be adapted and must conform to the applicable laws and regulations the application under
consideration.
ARTHING THE BATTERY
4.5.5 E
One of the two battery conductors can be earthed. This may be either the positive or negative pole.
In all cases the installation must conform to the local regulations and usage or specific standards
associated with the application.
In case of earthing, the earthing conductor section must at least be equivalent to the section of the
battery conductor. The earthing of the equipment must also adhere to these regulations. In this case
the use of the additional earthing screw is recommended (fig. 2b (17)), which is located at the front
of the device between the two lower fastening screws.
Installation and operating Instructions
Xtender V1.3
Page 13
STUDER Innotec
Xtender
ONNECTING THE CONSUMERS AT THE
4.5.6 C
OUTPUT
230 V AC
High voltages may be present on the connection terminals (13) and (14). Make sure that
the inverter is deactivated and that there is no AC or DC voltage present on the AC IN
terminals and battery terminals, before proceeding with the connection.
The 230 V consumers must be connected on the “AC OUT” (14) connection terminals with the wire
section conforming to the standards with regard to the rated current at the Xtender output (see fig.
1a). Distribution must conform to the local standards and regulations, and generally, be realised via a
distribution table.
The Xtender terminals are marked in the following way:
N = neutral, L = live
= protective earth (connected to the case of the device).
Due to the source backup function (smart boost) the current at the output of the device
may be higher than the rated current of the inverter. It is the sum of the current supplied by
the additional source and the current supplied by the inverter. In this case, the
dimensioning of the output cables will be carried out by adding the current indicated on the
protection device (H) located on the upstream of the unit, to the nominal current of the
inverter. (See fig. 1a and chap. 6.2.6 – p. 19)
If the assistance function at the source (smart boost) is not used, the calibre of the protection device
for the output (F) will be established at a maximum value equal to the rated current of the inverter, or
at the maximum value of the protection device at the input (H) if this is exceeds the rated current of
the inverter.
An additional earthing terminal (15) is present between the two fastening screws at the
bottom of the unit. It can be used instead of a connection on the input terminals of the
device, particularly when cable sections are used at the output that do not allow use of a
three-wire cable (live, earth and neutral) through the conduit glands of the connection
cables of the input and output (AC IN and AC OUT), or when the earthing of one of the
points of the battery requires a cable section greater than the the PE conductor section of
the AC IN and/or AC OUT line.
ONNECTING THE
4.5.7 C
SUPPLY SOURCES
AC
The Xtender is intended to be supplied by alternative voltage sources such as the public grid or a
generator. Check that the rated voltage of the source corresponds to the rated voltage (34) of the
Xtender specified on the type plate (fig. 3b).
The source must be connected to the input terminals marked “AC INPUT” (13) with sufficient wire
section, depending on the power output of the source, and protected by a protection device of the
appropriate calibre. This will be at the maximum equal to the current I AC in max (35) specified on
the type plate (fig. 3b).
The terminals are marked in the following way: N = neutral, L = live, PE = protective earth
(connected to the case of the device).
IRING AUXILIARY CONTACTS
4.5.8 W
These contacts are reversing contacts that are potential-free. The admissible currents and voltages
for these contacts are 16 A: 250 VAC/24VDC or 3 A: 50 VDC max. The representation of the
contact near the terminals corresponds to the status of the contact in idle mode (light indicator (5)
off). The cabling of these auxiliary contracts depends solely on the application and cannot be
described in this manual.
The factory-set functions for these 2 auxiliary contacts are covered in the chapter 6.2.10 – p.21.
ONNECTING THE COMMUNICATIONS CABLES
4.5.9 C
The Xtender is equipped with a pair of RJ45/8 connectors that allow information transfer via a
communication bus for different consumer types which have the proprietary protocol of Studer
Innotec. In this network all parties in the network are connected in series (chain).
Installation and operating Instructions
Xtender V1.3
Page 14
STUDER Innotec
Xtender
The length of the communication bus cable must not exceed 300 m.
In a system comprising a single Xtender, the connection of the RCC-02 or RCC-03 may be
conducted without stopping the Xtender (warm).
The communication bus will be used to interconnect other Xtender inverters in the case of a multi-
unit application or to connect other types of users who have the proprietary protocol of Studer
Innotec. In these cases, the installation must be switched off using the main “ON/OFF” button (1) to
connect the units via the communication bus.
The 2 switches of terminal of the communication bus, “Com. Bus" (4) both remain in
position T (terminated) except when both connectors are in use. In this case, and only in
this case, both must be placed in the O open position. If one of the two connectors is not
in use, the two termination switches (14) will be in position T.
CONNECTING THE TEMPERATURE SENSOR
4.5.10
(BTS-01)
The temperature sensor, BTS-01 is supplied with a 3 m cable fitted with RJ11/6-type plugs. It may
be connected or disconnected at any time (including when the device is in use) using the
corresponding socket (2) marked “Temp. Sens.” on the Xtender. Plug the connectors into the
socket (2) until they click in. The temperature sensor sleeve may simply be stuck onto the battery or
directly next to it. The temperature sensor will be recognised automatically and the correction made
immediately.
5 Powering up the installation
It is imperative that the closing cap for the connection compartment be installed and
screwed tight before the installation is energised. There are dangerous voltages within the
interior of the connection compartment.
The connection of the Xtender must be carried out in the order given below. Any disassembly must
be carried out in the reverse order.
1. Connecting the battery
Too high or inappropriate a battery voltage may seriously damage the Xtender. For
example, installing a 24 V battery in the Xtender 3000-12.
If the Xtender has been connected the wrong way around by accident (incorrect polarity of
the battery) it is highly likely that the protection fuse on the battery cable may melt and will
have to be replaced. If such is the case, it will be necessary to disconnect all the
connections to the Xtender including the battery. If, after replacing the fuse, the Xtender
proves not to work correctly after reconnecting the battery with the correct polarity, it will
have to be returned to your distributor for repair.
2.
Putting the Xtender(s) in operation
using the main ON/OFF switch (1). The Xtender is
supplied and is ready for operation. If you require immediate start-up of the inverter when the
battery is powered up, the main switch (1) must be in the “ON” position and the
configuration {1111} activated.
3.
4.
Connecting the consumers at the output
: Activate the output protection device (F) if existing,
and/or press the ON/OFF button (41). The light indicator “AC out” (46) lights up or flashes (in
the event of an absence of consumers).
Activating the input circuit breaker(s) (H)
If an AC source (generator or electrical grid) valid in
frequency and voltage is present at the AC input, the device automatically goes into transfer
and will start to charge the batteries. The consumers at the output are therefore supplied
directly by the power source present at the input.
Your installation is now in operation. If particular configuration or adjustment is required by the
system, it is recommended to carry this out immediately. Adjustments must be made with the RCC-
02/03 remote control. Please refer to the operating instructions for this accessory.
Installation and operating Instructions
Xtender V1.3
Page 15
STUDER Innotec
Xtender
6 Description and functioning
The Xtender is a sine wave inverter with a battery charger. It has been developed for use as a stand-
alone installation to supply AC voltage (not connected to the grid) or as a continuous supply.
6.1 Circuit diagram
17
K1
L
L
100nF
2,2nF
2,2nF
2,2nF
2,2nF
K3
K4
K2
N
N
4x2,7MΩ
16
14
13
11
BATTERY
f
10nF
10nF
9
AC
DC
b
t
12
f
10
Multimode Power Center
XTH-5000-24
DSP
6
RJ45
8p
O
T 4
RJ11
6p
Remote
On/Off
8p
7
a
Bus termination
Temp.
2
CAN bus
3
max 300m
e
RCC-02
6.2 Description of the main functions
NVERTER
6.2.1 I
The Xtender is equipped with a high-performance inverter which supplies a perfect and very precise
sine wave. Any unit designed for the 230 V/50 Hz electrical grid may connect to it without any
problem, up to the rated power out of your Xtender. The inverter is protected against overloads and
short-circuits.
Thanks to the largely over-dimensioned performance level, loads of up to three times greater than
the Xtender’s rated output can be faultlessly supplied for short periods of use, thus allowing motors
to be started up without any problem.
When the Xtender is operating the LED “ON” (43) is glowing.
When the Xtender is in inverter mode, the LED “AC out” (46) is glowing. If it flashes, the inverter is in
“load search” mode (see following chapter “Automatic load detection”).
UTOMATIC LOAD DETECTION
6.2.2 A
In order to save battery energy, the Xtender inverter stops and automatically goes into load search
when the detected load is lower than the sensitivity set by the configuration {1187}. It automatically
goes back into operation when a power consumer greater than this value demands it. The indicator
(46) flashes if the inverter is in “load search” mode, which also indicates that the AC voltage is
present at the output in an intermittent form.
The detection threshold for the absence of loads can be adjusted according to the configuration
Installation and operating Instructions
Xtender V1.3
Page 16
STUDER Innotec
Xtender
range {1187} by means of the RCC-02/03 remote control. When the configuration is set to 0 the
inverter will still operate even in the absence of any consumer.
When the load search sensitivity {1187} is set to 0 in a paralleled multi-units system, the
master/slave behaviour is inhibited and all the inverter will be always functional whatever the
load is.
In standby mode the system will thus consume minimal power from the battery (see table of
technical data p. 36).
RANSFER RELAY
6.2.3 T
The Xtender can be connected to an alternative power source such as a generator or public network.
When the voltage at the entry satisfies the voltage {1199+470} and frequency {1505-1506}
parameters, the transfer relay will be activated after a delay {1528}. This delay may be
adjusted(extended) to allow a fully stabile status of the generator before transfer.
When the transfer relay is activated, the voltage present at the input of the Xtender is available at the
output for the consumers connected. At the same time the battery charger goes into operation.
When the transfer relay of the Xtender is active, the voltage at the output of the Xtender is
equivalent to that which is present at the input and cannot be influenced or improved by the
Xtender. The consumers are supplied by the source present at the “AC IN” input via the
transfer relay.
The maximum current of the transfer relay is 50 A. This means that the permanent power of the
consumers must be a maximum of 11,500 W at 230 V (18000 W for the XTH 8000-48 if smart
boost {1126} is activated). (see chap. 6.2.6 p. 19). If the battery charger is in operation, part of this
power will be used for the battery charge.
The sharing of energy between consumers and the battery charger is adjusted automatically (see
chap. 6.2.5 – p. 19). The transfer relay will be deactivated when the input voltage no longer satisfies
the configuration {1199} or {1432} min. and max. voltage and frequency at the input or when the
current limit {1107} is exceeded, if the exceeding of this limit is prohibited {1436} It then passes
immediately into inverter mode. In this case the loads are supplied exclusively by the battery via the
inverter (see chap. 6.2.6 – p. 19). This switching always takes place automatically. The presence of
increased dynamic loads (such as pneumatic angle grinders, etc.) may lead to an undesirable
opening of the transfer relay due to the weakness of the source. To this case, a delay in the opening
of the transfer relay can be adjusted with the parameter {1198}.
The transfer normally takes place without any interruption when the generator stops. It would
typically be 40 ms in the event of the immediate loss of input voltage at “AC IN”.
6.2.3.1 Fast voltage loss detection mode (fast transfer):
When the Xtender is connected to the public grid or to a generator supplying stable and clean AC
voltage, a fast voltage loss detection mode {1435} can be used. In this mode, perturbation or lack of
voltage of less than 1 millisecond can be detected, switching the unit in inverter mode immediately.
The sensitivity of this detection is adjustable with the parameter {1510}. This mode guarantee a zero
or maximum of 15 ms transfer time
This mode should not be used in presence of highly disturbed utility grid or with a low power
generator or a generator supplying a poor quality voltage
ATTERY CHARGER
6.2.4 B
The battery charger for the Xtender is completely automatic and is designed in such a way as to
guarantee an optimum charge for the majority of the lead-acid or gel batteries. Once the transfer
relay is activated, the battery charger goes into operation and the charge indicator (44) lights up.
The battery charger is designed in such a way as to guarantee charging of the battery that is as
complete as possible. The charging process is at four levels by default and guarantees optimum
charging of the batteries. The charging current is given by the configuration {1138} and can be
adjusted continuously from 0 to the nominal value with the help of the RCC-02/03.
Installation and operating Instructions
Xtender V1.3
Page 17
STUDER Innotec
Xtender
The charge cycle, programmed by default,
as shown in the example described in the
figure opposite, runs automatically.
The line (28) indicates the development of
the battery voltage.
ACin=OK
{1138}
{1156}
{1140}
{1159}
The lower line (29) indicates the battery
current (input and output).
28
29
The cycle starts with a continuous current
charge (a) adjusted by default according to
the configuration {1138}. If the ambient
temperature is increased or the ventilation
blocked, the current may be reduced and
become lower than the selected current.
a
e
d
Cycle de charge simplifié, sans limitation de
courant d'entrée
Once the absorption voltage {1156) is reached, the cycle passes to voltage adjustment mode (d),
known as the absorption phase, the duration of which is set by the configuration {1157}. The
minimum interval between two absorption cycles is limited by the configuration {1161).
At the expiry of the absorption time, or if the absorption current is lower than the configuration
{1159}, the voltage is set to a lower value {1140}. This phase (e) is known as the maintenance or
“floating” phase.
If the battery voltage is lower than the critical disconnection threshold {1488} operation of
the charger will be automatically prevented. Only the transfer relay is authorised to operate
in this case. The battery must then be recharged by an external source up to a voltage
higher than the critical disconnection threshold in order to allow the Xtender charger to
operate.
Given the limiting function for the input current (see the following p. 19), it is perfectly normal for the
charge current to be lower than the selected current if the limit of the AC input current {1107} is
reached (b). In this event the AC IN indicator (45) flashes.
If the “smart boost” function is activated {1126} and the power required by the consumer exceeds
the power of the source, the battery will be discharged (c) despite the presence of the grid or the
generator. In this case the LED “charge” (4) goes out. The consumers must ensure that they have
average consumption that is less than the power of the source (generator or public grid) in order to
avoid a complete discharge of the battery. These situations are set out in the figure below.
ACin=OK
{1156}
{1140}
{1143}
28
{1138}
In
0
29
Out
a
d
e
a
b c a
d
e c
Fig 3a
Charge cycle example with input current limitation and "smart boost”
If the BTS-01 temperature sensor is used, the voltage adjustment thresholds for the battery are
corrected in real time by means of the battery temperature. The value of this correction is set by the
configuration {1139} in the configuration table p. 34.
Installation and operating Instructions
Xtender V1.3
Page 18
STUDER Innotec
Xtender
Much more complex charge profiles or exclusion of the charger can be configured using
the RCC-03/03 remote control.
Configuration of the battery is the responsibility of the operator. Incorrect configuration that
does not correspond to the charging methods of the battery recommended by the
manufacturer may be dangerous and/or considerably diminish the battery service life. If the
factory settings are modified, it is imperative that the new values be entered in the
configuration table p. 34
IMITING THE INPUT CURRENT BY LIMITING THE CHARGER CURRENT
6.2.5 L
In order to best use the resources available at the input (depending on the generator size or the grid
output) the Xtender has a system known as power sharing.
This is a system that allows the current of the charger to be limited – from its target value {1138} to
0 – according to the current used at the output in relation to the maximum current available at the
input set by the configuration {1107}. The greater the current at the output, the more the part of the
current at the input assigned to charging the battery is reduced. If the current exceeds the limit
{1107}, the transfer relay will remain closed and the input source is likely to be overloaded bringing
the protection device (H) to open. Exceeding the limit can be forbidden by the configuration of the
parameter {1436}. If so, if the input current limit {1107} is reached, the transfer relay will be open and
the consumer will remain supplied exclusively by the inverter (battery) as long as the output current
exceeds the limit of the input current.
This system allows the sharing of power available by giving priority to the AC output (AC out) and to
the consumers who are connected to it. The charger will only use the power not utilised at the
output to ensure that the battery is charged. Once the charge current decreases by going into
“power sharing” mode, the indicator (45) flashes.
The limit value of the input current is set by the configuration {1107} and may be adjusted via the
RCC-02/03 remote control.
In the case of mobile applications the installation of an RCC-02/03 remote control is
recommended, in order to be able to adapt the value of the input current limit if necessary,
for each connection to a protected grid.
.
If the power usage at the output is greater than the input current value, the Xtender cannot
limit the current. This situation will then lead to the stoppage of the generator due to
overcharging or will release the upstream protection circuit for the Xtender. This major
drawback can be prevented by using the “smart boost” function described below.
HE INVERTER AS SOURCE BACKUP SMART BOOST FUNCTION
6.2.6 T
(“
”
)
The combined usage of the power sharing function and the smart boost function allows this
drawback to be overcome as mentioned above. The source backup function supplements efficiently
the charger current limiting function in order to ensure optimum protection of the fuse upstream of
the device. This system proves to be a decisive advantage particularly in all mobile systems (boats,
leisure vehicles and service vehicles) that are frequently connected to sources with a limited value
such as a portable or camping power supply. Despite a limited source, all the greater power
applications downstream of the Xtender remain functional.
When this function is activated, the battery can be fully discharged despite the presence of
the grid or the generator. The average power consumed by the user must not exceed the
power of the source, at the risk of discharging the battery.
The smart boost function is deactivated by default. To activate the function the RCC-02/03 remote
Installation and operating Instructions
Xtender V1.3
Page 19
STUDER Innotec
Xtender
control is required. When this function is activated {1126}, it allows the current from the battery to be
supplied to the user in order to guarantee that the current at the input of the device does not exceed
the limit set {1107}.
If the input current limit is exceeded, the transfer relay will be opened immediately, thereby
protecting the upstream protection device. If the exceeding of the input current value limit is due to a
short-circuit downstream, the transfer relay will remain activated and the protection upstream of the
Xtender (H) will be requested.
The installation cabling must take this particular function into account, which allows a current
equivalent to the sum of all power outputs in the inverter and the AC source to be available at the
output.
If you have, for example, a 5 kW (22 A) source and an Xtender of 5 kW, the power available at the
output will be 10 kW. The downstream cabling must therefore be dimensioned accordingly. In this
example, the output cable must be dimensioned to support a current of 45 A. A dimensioning table,
fig. 1a, will help you to determine the output currents that dimension the protection devices and the
cable sections to be applied.
If the Xtender is connected to a generator, this must have a power at least equal to half of
the power of the Xtender(s) to which it is connected.
NPUT CURRENT CONTROLLED BY INPUT VOLTAGE
6.2.7 I
When AC sources with variable power are connected to the Xtender's ACin, a particular parameter
setting insure a permanent availability of the nominal power at the Xtender's output thanks to the
Smartboost function. It's notably the case with "Dynawatt" 230Vac alternator coupled with variable
speed traction engines. These kinds of sources have a variable voltage according to the available
power. For this type of application, it's necessary to activate the parameter {1527}. So, the input
current limit {1107} will be regulated between zero to the programmed value, for an input voltage
whitch varies between {1309} and {1309}+{1433}
ATTERY PROTECTION
6.2.8 B
The battery is protected in all cases against deep discharge. The indicator (52) flashes once when
the battery has reached the disconnection threshold {1108} and the inverter will stop some time
after {1190}. This threshold can be dynamically corrected {1191} with an advanced algorithm tha
computes automatically the battery voltage compensation in function of the instantaneous power.
This correction may also be manually fixed {1532} by setting the low voltage disconnection at full
load {1109}. These dynamic corrections can be desactivated by stting the parameter {1191} . The
inverter will stop immediately if a critically low voltage value set by the configuration {1188} is
reached. The inverter will restart automatically when the battery voltage has reached the restarting
threshold {1110}.
This restarting threshold {1110} can be automatically readjusted if the parametewr {1194} is
activated, in order to better protect the battery against repeated cycling in an "almost empty " state
of charge. The restarting threshold is then incremented {1298} up to a maximum value {1195},
whenever the LVD (low voltage disconnection) is reached. The restarting threshold will be reset to its
initial value when the value of parameter {1307} is reached.
If the inverter is repeatedly {1304} encountering a low voltage disconnection in a short period {1404},
it will stop permanently and will only start again via an operator’s manual restart.
TENDER PROTECTION
6.2.9 X
The Xtender is protected electronically against overloads, short-circuit, overheating and reverse
current (cabling of a voltage source on AC out).
In the event of overload or short-circuit at the output, the inverter stops for some seconds and
restarts. If the inverter is repeatedly encountering this situation {1300} in a short period, it will stop
permanently and will only start again via an operator’s manual control.
If the battery voltage exceeds the value set by the configuration {1121} the inverter stops and starts
up again when the voltage is less than {1110}. If the Xtender is repeatedly encountering this situation
{1303} in a short period {1403}, it will stop permanently and will only start up again via an operator’s
manual control.
Installation and operating Instructions
Xtender V1.3
Page 20
STUDER Innotec
Xtender
A battery voltage greater than 1.66 x the nominal voltage may lead to significant damage or
destroy the device.
Overheating of the Xtender, Insufficient ventilation, increased ambient temperature or obstructed
ventilation may lead to overheating of certain internal components of the unit. In this case, the device
will automatically limit its power output as long as this abnormal situation persists.
The Xtender is protected from reverse polarity by means of an external fuse installed on the battery.
UXILIARY CONTACTS
6.2.10 A
The Xtender has two dry reversing contacts that are potential-free. The status of the contacts in idle
mode (deactivated) is indicated by the annotations, N.C. = normally closed and N.O. = normally
open.
Maximum contact loads: 230 Vac / 24 Vdc: 16 A or: max. 50Vdc/ 3A
These dry contacts are programmed by default for the following functions:
Contact no. 1 (AUX 1): The contact has a function of automatic star of generator (two wire). Contact
will be activated when the battery voltage is, during a given time {1247/48}/{1250/51}/{1253/54},
less than the value given by parameter {1246/49/52}. The contact will be deactivated or when the
charge cycle as reached absobtion, or when the "Aux. 1 deactivation voltage" {1255} is reached
during a pre-determinated time {1256}
The voltage of the battery is automatically compensated according to the instantaneous
battery current the same way as it is done for compensation of LVD (see chapter 6.2.8 –
p.20) if parameter {1191} is activated
Contact no. 2 (AUX2) : alarm contact by default. It is deactivated when the inverter is out of service
or is working at reduced performance, either because of manual control or if there is an operational
fault such as overload, undervoltage of the battery, overtemperature, etc.
The functions of the two auxiliary contracts can be modified and programmed variously with the help
of the RCC-02/03 control.
If the operator or installer requires different behaviour for the auxiliary contacts, they are both freely
and individually programmable depending on the battery voltage and the inverter status and the
internal clock.
The intelligent programming of the auxiliary contacts allows many applications to be considered
such as:
Automatic startup of the generator (two or three wires)
Automatic load shedding of the inverter (2 sequences)
Global or individual alarm
Automatic disconnection (load shedding) of the source
HE REAL TIME CLOCK
6.2.11 T
The Xtender has a real time clock that allows the functioning of the auxiliary contacts to be managed,
in particular. This clock must be adjusted via the use of the RCC-02/03 remote control.
EMOTE CONTROL ON OFF
6.2.12 R
/
The functioning of the Xtender may be interrupted by opening the connection, normally between the
two terminal points “REMOTE ON/OFF”, fig. 8a-(7). Operation will recommence when this
connection is re-established. The device is delivered with a bridge between the 2 points of this
terminal.
It is also possible to control this function according to the different variants indicated in fig. 8b. If a
variant is used, the jumpers (6) must be positioned at 1 a-b and 2 a-b.
Operating voltage: Max. 60 V eff. (I max. 30 mA)
In multi-unit configurations (see below) the interruption of operation of just one of the system’s units
by the cabled control (7) involves the immediate interruption of operation of the other units of the
system. This input can be used, for example, as an emergency stop.
Installation and operating Instructions
Xtender V1.3
Page 21
STUDER Innotec
Xtender
6.3 Multi-unit configurations
Several Xtenders can be used in the same system, either to create a three-phase system or to
increase the power output of a single or two phases. The implementation of this configuration
requires particular precautions and it must be installed and commissioned by qualified personnel
only.
When multi-unit system is commissioned, the software's version of every units will be
automatically checked and units may refuse to start in case of incompatibility. If so, an
upgrade of every units is be required with the RCC-02/03 and the last software version
available by the manufacturer. (Read the RCC-02 user's manual to perform this operation).
The inverters selected must be of the same type and the same rated power output. There is a
shared battery bank.
In these multi-unit system, the units must be interconnected via a communication bus connected to
the connectors (3) by cable (art. no. CAB-RJ45-2) of a maximum length of metres. Interrupting this
connection in a multi-unit system will lead to the stoppage – after 5 seconds – of all the units in the
system.
Various application examples are described from fig. 12 to fig. 19 of Appendix I.
It is important to read and adhere to the descriptions associated with each of the figures
mentioned above
In multi-unit system,it is not recommended to employ the manual setting {1532} of the LVD
dynamic correction.
In configurations carrying several Xtenders, each unit is controlled independently using the ON/OFF
push button (41). When the on/off control is given via the RCC-02/03 remote control, it is applied
simultaneously to all units.
HREE PHASE SYSTEM
6.3.1 T
-
Three Xtenders of the same type can be used and combined in order to establish a three-phase grid.
An example of cabling in three-phase is given at figs. 13.-14.
When 3 Xtenders are cabled to form a three-phase grid, the cabled phases at the input determine
the jumper position for selecting the phase (10). It is vital to determine and select the phase for each
Xtender. If the grid is not available at the input of the master unit (phase 1), all the units of the system
will switch to inverter mode. If only a single-phase source is available, it must be connected to phase
1. The other two phases will therefore be supplied by the other two working units in inverter mode.
NCREASING THE POWER AND CONNECTION IN PARALLEL
6.3.2 I
Up to three Xtenders can be cabled in parallel in order to increase the system’s rated power output.
In this configuration, all the ACin inputs of the Xtender must be cabled. One of the units functions as
master and will decide on the operation or suspension of the units in parallel according to the
consumer’s power demand. The yield of the installation is therefore still optimal.
An example of parallel connection is given in fig.12. and the comments on p. 27.
When the load search sensitivity {1187} is set to 0 in a paralleled multi-units system, the
master/slave behaviour is inhibited and all the inverter will be always functional whatever the
load is.
OMBINED SYSTEM
6.3.3 C
It is possible to combine a three-phase system with one or several phases made up of 2 or 3
Xtenders in parallel. An example of cabling is given at fig. 15.
It is therefore possible to combine up to nine Xtenders by running three Xtenders parallel in a three-
phase grid. Examples of cabling are given in figs. 16 to 18 and the comments on p. 27.
Installation and operating Instructions
Xtender V1.3
Page 22
STUDER Innotec
Xtender
6.4 Accessories
ONTROL CENTRE AND
6.4.1 C
REMOTE CONTROL DISPLAY
RCC-02/03 (
)
An RCC-02/03 remote display and programming unit can be optionally connected to the Xtender via
one of the two RJ45-8-type “Com. Bus” (3) connectors.
These connectors may only be used for connecting a CAN-ST compatible accessory, excluding any
other connection such as LAN, Ethernet, ISDN, etc.
The RCC-02/03 control centre is vital for modifying device configurations.
It also allows the following functions:
•
•
•
•
•
•
Display of function synopsis
Display of the measured operational values (current / voltage / power output, etc.)
Updating of software or implementation of customised software
Storage of inverter configuration
Updating of inverter configurations
Storage of error message history
RCC-02
RCC-03
The features of the RCC-02 and the RCC-03 are the same. They only differ in their external
appearance. The RCC-02 is designed for wall mounting, whereas the RCC-03 is designed as a
board device.
The RCC-03 model must be taken off the table to allow access to the SD card slot (during updating,
for example).
Model N°: RCC-02: Dimensions: H x W x D / / 170 x 168 x 43.5mm
RCC-03: Dimensions: H x W x D / / 130 x 120 x 42.2mm
The two remote control models are delivered with a 2 m cable by default.
Cables of specific lengths (5 m, 20 m and 50 m) can be ordered.
The article no. is as follows: CAB-RJ45-xx. The length in metres is specified as xx
Up to 3 RCC-02/03 remote controls can be connected in series on the communication bus of one
Xtender or an Xtender multi-inverter system. In a system comprising a single Xtender, the
connection of the RCC-02 or RCC-03 may be conducted without stopping the Xtender (warm).
When connecting an RCC-02/03 remote control in a multi-unit system, it is recommended that all
units in the system be stopped and that the communication bus on the device on which the
connection is being made be terminated.
The 2 switches for terminating the communication bus, “Com. Bus" (4) both remain in
position T (terminated) except when both connectors are in use. In this case, and only in
this case, both must be placed in the O (open) position. If one of the two connectors is not
in use, the two termination switches (14) will be in position T.
Installation and operating Instructions
Xtender V1.3
Page 23
STUDER Innotec
Xtender
TEMPERATURE SENSOR
6.4.2 BTS-01
The operating voltages for lead batteries vary depending on the
temperature. A temperature sensor is optionally available to correct the
battery voltage and guarantee an optimum charge whatever the battery
temperature. The correction factor given by the correction of the sensor is
set by the configuration {1139}
Article no. for the temperature sensor (including a cable of 3 m): BTS-01.
Dimensions: H x W x D / / 58 x 51.5 x 22 mm
7 Control
7.1 Main on/off control
This switch (1) interrupts the electronic supply and all the
Xtender peripherals. The residual consumption on the
battery is therefore less than 1 mA.
The ON/OFF switch is used only for the complete
stoppage of the whole system.
Multimode Power Centre
Inverter + Charger + Autom. transfer + Input current manager
XTH-5000-24
Blinking indicator
7.2 Display and control parts
The Xtender has a ON/OFF button and light indicators at
the front of the device, allowing clear identification of
the operating mode.
(41) The ON/OFF button allows the startup or
complete stoppage of the system such as it has been
programmed. In the systems comprising several units,
each unit is started or stopped individually. For a
simultaneous startup of all the units use the dry contact
control (see chap. 6.2.12 – p. 21) or the ON/OFF
button of the RCC-02/03 remote control.
Load search
Input limited
46
45
44
43
42
Float
Absorption
Auto restart
Overload
Overtemp.
Bat. over volt.
41
Even when the equipment has stopped,
dangerous voltages may be present at the
Xtender input.
(42) This indicator lights up when the equipment has been stopped manually using the ON/OFF
button (41). It also allows the cause of an unintentional stoppage of the device to be indicated via
the different flashes, the imminence of a stoppage or the temporary limitation of its performance.
The table below describes the type of fault according to the number of flashes on the indicator (42)
Indicated alarm
Comment
1x (Imminent) stoppage as a If the device has not yet stopped, it is recommended to
result of low battery voltage. disconnect all non-priority consumers and/or start up the
generator. If the Xtender has stopped it will restart
automatically when the battery voltage has reached the correct
value again {1110}. It can be restarted manually using the
ON/OFF button (41) as long as the battery voltage is higher
than the critical threshold {1488}.
See also chapter 6.2.9 – p. 20.
Installation and operating Instructions
Xtender V1.3
Page 24
STUDER Innotec
Xtender
2x Stoppage due to overload in In this event the equipment will make several attempts restart
the equipment, due to either {1133} every few seconds and will stop if the overload remains
a short-circuit or too high a (see chap. 6.2.9 – p. 20). It is vital to eliminate the cause of the
load for the inverter.
overload without restarting. Restarting is carried out manually
by pressing the button (41).
3x Decrease in the rated output This may be due to too great a load for the device, at too high
of the device due to a too an ambient temperature or counteracted or obstructed
high internal temperature.
ventilation. The power output of the device will therefore be
limited to around 50% of the Pnom. including in charger mode
or smart boost mode.
4x Battery voltage higher than
Check the cause of this excess voltage. The equipment will
the maximum limit set by the restart automatically when the voltage falls below the threshold
configuration {1121}.
value {1122}.
see chap. 6.2.9 – p. 20
5x No transfer. Insufficient power In this case, the Xtender remains in operation in inverter mode
from the source
until the output power decrease below the input limit and does
not allow the transfer relay to close. You must increase the
input current limit {1107}, or authorise the exceeding of this
limit {1436} or authorise backup on the source {1126}, or
disconnect some consumers (decrease of loads).
6x Startup prevented due to Voltage is present at the device output. Check your cabling:
unwanted voltage at the correct the fault and start the installation again using a manual
device output.
control on the button (41).
7x Indicates missing voltage on Check the input protection devices (H) for all the system units.
one of the units of the system
in a multi-unit configuration.
(43) This indicator is glowing continuously when the device is working.
It flashes when the equipment is temporarily stopped due to a fault displayed by the indicator (42) or
a ON/OFF control cabled at the ”Remote ON/OFF” input (7), or when the equipment is intentionally
put to idle mode by the master unit in a multi-inverter parallel system (see chap. chap.6.3.2 - p. 22).
The equipment will restart automatically when the conditions that led to the temporary
stoppage have gone away.
(44) This indicator is glowing continuously when the charger is working and has not yet reached his
absorption phase.
It flashes twice during the absorption phase and once during the floating phase.
If the smart boost mode has been activated, this indicator goes out temporarily when source
backup is required by users (loads).
(45) This indicator is glowing continuously when a n alternative voltage with correct values, either in
frequency {1112-1505-1506}, or in voltage {1199} is present at the AC IN input of the device and
the current limit set by the user has not been reached. It flashes when the current limit at the input
{1107} set by the user has been reached. In this case the charger current is reduced in order to
guarantee priority supply to the users (see chap. 6.2.5 p. 19). If the input current is exceeded
nevertheless, the Xtender goes back to inverter mode (transfer relay open) and the indicator (42) will
keep flashing as long as the user current exceeds the limit value of the input current {1107}.
If the smart boost mode (see chapter 6.2.6 – p.19) is used and the inverter is part of the user supply
– therefore the battery is discharged – the “charge” indicator (44) will be glowing.
(46) This indicator is glowing continuously when an alternative voltage of 230V is present at the
equipment output. It flashes when the device is in “load search” mode according to chapter 6.2.2 –
p. 16.
Installation and operating Instructions
Xtender V1.3
Page 25
STUDER Innotec
Xtender
8 Maintenance of the installation
With the exception of the periodic checking of connections (tightening and general condition) the
Xtender does not require any special maintenance.
9 Product recycling
The models of the Xtender series conform to the European directive
2002/95/EC on hazardous substances and does not contain the following
elements: lead, cadmium, mercury, hexavalent chrome, PBB or PBDE.
To dispose of this product, please use the service for the collection of electrical
waste and observe all applicable obligations according to the place of purchase.
10 EC declaration of conformity
The inverter and accessories described in this manual comply with the following standards:
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2, Dir. 89/336/EEC,
LVD 73/23/EEC, EN 50091-2, EN 60950-1.
CH -1950 Sion, 31 January 2007
STUDER Innotec (R. Studer)
Installation and operating Instructions
Xtender V1.3
Page 26
STUDER Innotec
Xtender
11 Comments of annexes’ figures
Fig. Description and comment
Dimensioning table for the downstream protection device (F). See chap. 4.5.6 – p.14.
Type plate and series no.
1a
1b
See chapter 16 - p. 32.
The intactness of this label is vital for any possible warranty claims. It must not be altered
or removed.
Dimensions and fastening the device
The support (wall) must be appropriate for supporting the increased weight of the device
without any risk.
2a
2b
3a
Installation distance
Insufficient distance or an increased ambient temperature can reduce the rated power
output of the device.
Battery charge cycle
Charge cycles that are more complex than those described in chap. 6.2.4 – p. 17 of this
manual may be programmed via the RCC-02/03 remote control.
Simplified battery charge cycle:
See chapter 6.2.4 - p. 17.
Device connection box
3b
4a
See chapter 3.6.2 – p. 7.
4b
5a
5b
5c
5d
6a
6b
6c
6d
7
Control table See chapter 7.2-p. 24.
12 V battery: connection in series and in parallel / series for 2 V cell
12 V battery: connection of 12 V battery in parallel
24 V battery: connection in series and in parallel / series for 2 V cell
24 V battery: connection in series and in parallel / series for 12 V battery block
48 V battery: connection in series and in parallel / series for 12 V battery block
48 V battery: connection in series for 12 V battery block
48V battery: Series connection of 2V cell
48 V battery: connection in parallel / series for 2 V cell
Xtender circuit diagram
8a
Single-phase installation (AC and DC part)
This example illustrates the most routinely used installation, allowing the attainment of an
emergency system or a hybrid system (remote sites) ensuring the supply in single-phase
from a generator and/or the battery when the AC source is absent. See also chapter
4.1.1.1 / 4.1.2 – p. 9.
8b
ON/OFF remote control variants
This example illustrates the various options for connecting the “REMOTE ON/OFF” input
(7), enabling the ON and OFF controls of the Xtender via a contact or a voltage source.
See also chap. 6.2.12 – p. 21.
The maximum length for this control should not exceed 5 m.
Installation with three-phrase source and secured single-phase output – AC and DC
part
In this example, the three-phase users will only be supplied when the generator or grid are
operating.
Fixed installation with plug connection to the single-phase source – AC part
Special feature: The connection of the neutral upstream and downstream of the Xtender
(C) is prohibited in this configuration (presence of a plug upstream). See also chapter 4.2.1
– p. 10.
Fixed single-phase installation with connection by plug to a three-phase source – AC
part
8c
9a
9b
Special feature: The connection of the neutral upstream and downstream of the 'Xtender
(C) is prohibited in this configuration (presence of a plug upstream). See also chapter 4.2.1
– p. 10.
Installation and operating Instructions
Xtender V1.3
Page 27
STUDER Innotec
Xtender
Fig. Description and comment
10a
Example of installation in a vehicle (AC part)
Special features: The connection of the neutral (C) is not permitted (presence of a socket
upstream). The earth-neutral connection is absent in inverter mode (neutral stand-alone
system). The safety is guaranteed by the equipotential bonding (frame). The automatic re-
establishment of the earth-neutral connection downstream of the device in inverter mode
can be programmed. Consult the table of figures, item (V).
See also chapter 4.2.1 – p. 10.
10b
10c
Example of installation in a boat without an isolation transformer (AC part)
Special feature: Where there are multiple sources, for example connection to the dock and
on-board generator, a source reverser (X) guaranteeing switching with phase and neutral
interruption must be installed.
Installation example in a boat, with isolation transformer
Characteristic: With several power sources, like shore connection and onboard generator,
a switchover (X) must be installed, to safely switch between the different voltage supplies
with guaranteed interruption of the phase and neutral conductors. Moreover, an earth
must be formed (E) after the isolation transformer.
11
12
Example of a hybrid installation:
This is the most common system used to establish an emergency system or a hybrid
system (grid-remote sites) ensuring a single-phase supply from a generator and/or the
battery.
Special feature: In a hybrid installation, the sources for recharging a battery (k-m) are
connected directly to the batterie via their own control system. This does not interfere with
the Xtender charger. See also chapter 4.1.1 – p. 9.
Example of parallel connection of 2 or 3 Xtenders
1. Only Xtenders of the same power output may be connected in parallel.
2. Wiring precautions: The cable lengths and cross-sections of AC in input (A) and AC
out output (B) must be the same for all inverters in parallel in the same phase.
3. Variant: The sum of the lengths of the cables (A1) + (B1) of Xtender 1 must be the
same as the sum of the lengths of the cables (A1) + (B1) of Xtender 2, and ditto for
Xtender 3
4. The AC input for each Xtender must be protected individually by a protection device
(H) of the appropriate size.
5. The protection device at the output of the Xtender (F) can be shared and of
appropriate calibre at the sum of the currents of the devices in parallel.
6. If necessary, the ON/OFF remote control (r) will be implemented on only one of the
devices of the installation and suspends or authorises the operation of all the Xtenders
in the installation.
13
14
Example of three-phase cabling of 3 Xtenders – three-phase input
Special features: When 3 Xtenders are cabled to form a three-phase grid, the cabled
phases at the input determine the jumper position for selecting the phase (10). It is vital to
determine and select the phase for each Xtender.
See also chapter 6.3.1 – p. 22.
The comments for fig. 12 - 4 to 6 are valid.
Example of three-phase cabling of 3 Xtenders – single-phase input
Special feature: In a three-phase configuration, if only one phase is available as a source,
only one Xtender will be wired on that source. Phase 2 and 3 will be permanently fed from
the two other units connected only to the battery (not connected to ACin).
It is vital to determine and select the phase for each Xtender.
See also chapter 6.3.1– p. 22.
The comments for fig. 12 are valid.
15
Example of three-phase, input and output wired, with reinforced phase
Special feature: This installation allows a three-phase supply with a reinforced phase The
reinforced phase may be incorporated on two or even three inverters in parallel. The
protection device at the output on which 2 or 3 Xtenders are cabled must be calibrated
according to the sum of the maximum currents of the devices in parallel.
The comments for fig. 12 to 13 are valid.
Installation and operating Instructions
Xtender V1.3
Page 28
STUDER Innotec
Xtender
Fig. Description and comment
16
Example of cabling of 9 Xtenders in three-phase and parallel – AC part
Special feature: In fixed high power installations, it is advised that a shared neutral be
retained, distributed to all parties in the grid (see (C))
The comments for figs. 12 to 15 are valid.
17
18
19
Example of cabling of 9 Xtenders in three-phase and parallel – DC part (distribution
bar)
Example of cabling of 9 Xtenders in three-phase and parallel – DC part in star
formation
Connection of remote controls RCC-02/03
At a Xtender or at a system with several Xtender maximally 3 remote controls can be
attached.
12 Figure element's (DC part)
Elem. Description
Comment
a
RCC-02/03
remote control
This device allows complete configuration of the installation as well as
displaying the system behaviour. It is recommended but not
necessary for the installation to function well. See chapter 6.4.1 – p.
23.
b
Battery
The battery capacity is constituted according to figures 5a to 6d
based on the required voltage. Note: It is vital that the voltage and the
polarity of the battery be checked before connecting to the inverter.
An overload or incorrect polarity could seriously damage the Xtender.
Correct dimensioning of the batteries is essential for trouble free
operation of the system. See chapter 4.3.1 – p. 11.
Communications cable. Only an original cable supplied by Studer
Innotec may be used. The total length of the communications cable
must not exceed 100 m for 3 x RCC-02/03 or 300 m for a single
RCC-02/03.
e
f
Communications
cable
Protection devices A fuse-type device, thermal circuit breaker or magnetic-thermal circuit
breaker (see fig. 8a) must be installed on at least one of the two
battery conductors. It will ideally be placed on the positive pole of the
battery and as close as possible to this. The calibre of the device is
selected according to the cable section used.
If the negative pole of the battery is not earthed, it must also be
protected by such a device.
h
j
k
Distribution bar
Distribution bar
Wind-powered
Positive pole of the battery
Negative pole of the battery
One or more wind-powered generators or/and micro-hydro with their
or/and
micro- own regulation system may be used to directly charge the battery. Its
hxdro generator
dimensioning does not depend on the Xtender and does not interfere
with it.
L
m
Solar generator
One or more solar-powered generators with their own regulation
system may be used to directly charge the battery. Its dimensioning
does not depend on the Xtender and does not interfere with it.
r
t
Remote
via dry contact
control A control device may be connected to the terminals (7) of the
Xtender. See chapter 6.2.12 – p. 21.
The length of the connection cable must not exceed 5 m.
The sensor is placed in immediate proximity to the battery. If the
installation comprises several Xtenders, a single sensor is connected
to one of the units. See chap. 6.4.2 p.24
BTS-01
temperature
sensor
Installation and operating Instructions
Xtender V1.3
Page 29
STUDER Innotec
Xtender
13 Figure element's (AC part)
Elem. Description
Comment
A
B
C
Input supply cable The section is determined by means of the maximum current at
source and the protection device (H). In multi-unit systems, cables (A)
of the same phase must have the same length and section (see
comment fig. 12-2/3).
Output
cable
supply In multi-unit systems, cables (B) of the same phase must have the
same length and section (see comment fig. 12-2/3). The section must
be selected by means of the Xtender’s output current given on the
type plate and the protection device selected for the input (see fig.
1a).
Connection of the See chapter 4.2 - p. 10.
neutrals In a fixed installation where the neutral is connected to the earth at a
single installation point upstream of the Xtender, it is permissible to
carry out a connection of the neutrals in order to preserve an
unchanged earthing system downstream, independent of the
operating mode of the Xtender. This choice shows the advantage of
keeping the differential protection devices downstream of the
Xtender.
This connection (C) is not permitted if a socket is installed upstream
of the Xtender.
D
E
Differential circuit A protection device must be installed downstream of he source (G or
breaker
U) according to the local requirements and in compliance with the
applicable regulations and standards.
Earth-neutral
The neutral is earthed at a single point of the installation, downstream
connection bridge of the source and upstream of the protection device(s) at the default
current (DDR). When several sources are available, each source must
have an earthed neutral. If the source has to be retained with an
isolated earthing system (IT) the applicable local provisions and
regulations must be applied.
F
AC
output A protection device dimensioned in dependence of the cable section
protection devices used may be installed downstream of the Xtender (main circuit
for the Xtender
Generator
breaker before distribution). The cable section is to be dimensioned
according to the calculation table of maximum output current (fig. 1).
The Xtender has an internal current limitation the value of which is
stated on the type plate Fig. 1b (35).
The generator is dimensioned according to the requirements of the
user. Its rated current will determine the configuration adjustment
{1107} “maximum current of the AC source”.
G
H
Protection devices The protection device at the input of the Xtender must be
at the Xtender dimensioned according to the power output of the source at the
input
cable section used. It will not exceed a calibre equivalent to the input
current “I AC in” given on the type plate of the unit Fig. 1b (35).
J
K
Connection plug / If the Xtender is connected to an AC source by means of a plug, the
socket
connection cable must not exceed a length of 2 m, and the socket
must remain permanently accessible. The socket will be protected by
a protection device of appropriate calibre. The connection of the
neutrals (C) is prohibited in this case.
L
P
R
S
Secured grid
Distribution to the users supplied by the grid or the generator when
this is present or by the Xtender within the limit of its power output
from energy stored in the battery. This distribution is carried out in
conformity with the local standards and regulations.
Installation and operating Instructions
Xtender V1.3
Page 30
STUDER Innotec
Xtender
Elem. Description
Comment
T
U
V
Non-secured grid Distribution to users supplied exclusively via the present grid or the
generator.
This distribution is carried out in conformity with the local standards
and regulations.
Public grid
The connection to the public grid imposes adherence to the local
standards and regulations at the responsibility of the installer. The
installation should, in principle, be checked and approved by an
official body.
Automatic earth- This connection is deactivated by default. In may be used in certain
neutral connection specific cases for automatically re-establishing the neutral system
type TT (TNC, TNS, TNC-S) when the Xtender is in inverter mode.
The activation is carried out via RCC-02/03 remote control
configuration {1485}. This operation may only be carried out by
qualified personnel, under the responsibility of these personnel, and in
conformity with the local standards and regulations. See 4.2.3– p.11
W
X
Galvanic isolator
This device (optional) is generally used to reduce the risk of
electrolytic corrosion due to the direct current when a boat is
connected at the dock.
Source reversing When the installation has more than one supply source, it is
switch
necessary to install a switching device between the sources,
simultaneously switching the neutral and the phase(s) of these
sources. In all cases this device (manual or automatic) must
guarantee interruption of the connected source before its connection
to another source.
Y
Isolation
transformer
This device (optional) prevents the risk of galvanic corrosion due to
direct currents when a boat is connected at the dock.
14 Elements of connexion cabinet (Fig 4a)
Pos. Denomination Description
Comment
See chapter 7.1 - p 24.
1
ON/OFF
Main on/off switch
Main switch
2
Temp. Sens Connector for the battery See chapter 6.4.2 – p. 24.
temperature sensor Only connect the original Studer BTS-01
sensor
3
4
Com. Bus
Double
connector
for See chapter 4.5.9 – p. 14.
connecting peripherals such as The two termination switches (4) for the
the RCC002/03 or other communication bus both remain in
Xtender units
position T (terminated) except when both
connectors are in use.
O / T
Switch for terminating the
/ communication bus.
(Open
Terminated)
--
5
6
3.3 V (CR-2032) lithium ion type Used as a permanent supply for the
battery socket internal clock. See chapter 6.2.11 - p 21.
Jumper for programming the See chapter 6.2.12 – p. 21 and fig. 8b
--
off/on switch by dry contact
point (6) and (7). They are positioned at A-
1/2 and B-2/3 by default
7
REMOTE
ON/OFF
Connection terminals for dry See chapter 6.2.12– p. 21).
on/off remote connection.
Auxiliary contact
When the control via dry contact is not
being used, a bridge must be present
between the two terminals.
(See chapter 6.2.10– p. 21)
Take care not to exceed the admissible
loads
8
9
AUXILIARY
CONTACT
--
Activation indicators for auxiliary See chapter 6.2.10– p. 21
contacts 1 and 2
Installation and operating Instructions
Xtender V1.3
Page 31
STUDER Innotec
Xtender
Pos. Denomination Description
Comment
See chapter 6.3.1. – p.22.
10 L1/L2/L3
Phase selection jumpers.
Jumper default at position L1
11 +BAT
Positive pole battery connection Carefully read chapter 4.5 – p.12
terminals
Negative
Take care with the polarity of the battery
and when tightening the clamp.
battery
12 -BAT
pole
connection terminals
Connection terminals for the See chapter 4.5.7 - p. 14.
alternative power supply Note: It is imperative that the PE terminal
(generator or public network) be connected.
Connection terminals for the See chapter 4.5.6 - p. 14.
device output. Note: Increased voltages may appear on
13 AC Input
14 AC Output
the terminals, even in the absence of
voltage at the input of the inverter.
15 Control and display parts for the Xtender (fig. 4b)
See chapter 7.2 - p. 24.
Pos. Denomin Description
ation
Comments
ON/OFF
41
ON/OFF button
The ON/OFF button allows the start up or complete stoppage
of the system such as it has been programmed. When there
are several units in the same system, each unit must be
started up or stopped individually using this button.
42 OFF
43 ON
Light
indicator When the light indicator flashes it indicates the cause of the
for stoppage of stoppage of the unit, its imminent stoppage or the limitation of
the unit
Light
its rated power output according to chapter 7.2 - p.24.
indicator This indicator is glowing continuously when the device is
showing that the working. It flashes when the equipment is at a temporary
equipment is in stop. Note: The equipment will restart automatically when the
operation
conditions that led to the temporary stoppage have gone
away.
44 Charge Light
indicator This indicator is glowing continuously when the charger is in
showing that the operation and has not yet reached the absorption phase.
battery is being It flashes twice during the absorption phase and once during
charged
the maintenance phase.
If smart boost mode has been activated it is possible that this
indicator will go out temporarily when source backup is
required by users. (See chapter 6.2.6 - p. 19)
45 AC in
Light
showing
indicator This indicator is glowing continuously when an alternative
the voltage with correct values is present at the AC IN input (13)
presence
correct
synchronised
input voltage
of of the device and the current limit {1107) set by the user has
and not been reached. It flashes when this limit is reached (see
chapter 6.2.5 – p. 19).
46 AC out
Light
showing
indicator This indicator is glowing continuously when an alternative
the voltage of 230V is present at the device output. It flashes
presence of a when the device is in “load search” mode due to the absence
voltage at the of users. (See chapter 6.2.3 – p. 16)
output
16 Type plate elements (fig. 1b)
Pos. Denomination Description
Comments
31 Model
Model
32 Pnom/P30
Rated power output / power for 30 minutes
Installation and operating Instructions
Xtender V1.3
Page 32
STUDER Innotec
Xtender
Pos. Denomination Description
Comments
33 U Battery
Rated battery voltage (input area)
See chapter 6.2.8– p.
20
34 U ACin
Rated AC input voltage (input area)
Maximum current at input / output
See chapter 6.2.3 – p.
17
See chapter 6.2.6 - p.
35 I ACin/out
19.
36 U ACout
37 I Charge
Rated output voltage
Maximum charger current
Or according to {1286}
See chapter 6.2.4 - p.
17
38 SN:xxxxxxxxxx Serial no.
39 IPxx
Protection degree according to IEC 60529
Installation and operating Instructions
Xtender V1.3
Page 33
STUDER Innotec
Xtender
17 Table of standard configurations
No. of
Units
Fact. Mod.
Denomination / description
config.
value
value
1107 Maximum current of the AC source
1108 Undervoltage of the empty battery
1109 Sub-voltage of the charged battery
1110 Restart voltage of the inverter after undervoltage of the battery
1111 Automatic startup at power up
A
30
V/cell
V/cell
V/cell
y/n
1.93
1.75
2
no
1112 Inverter frequency
Hz
50
1121 Maximum DC voltage for stopping the Xtender
1126 Source assistance (Smart Boost) permitted
1138 Battery charge current
V/cell
y/n
A
2.84
no
60
1139 Battery voltage correction according to the temperature
mV/°C/ -5
cell
1140 Battery maintenance voltage
V/cell
V/cell
min.
V/cell
sec.
V/cell
h
2.27
2.1
30
1.93
180
2.4
2
1143 Voltage 1 to allow a new battery cycle
1144 Duration of under voltage 1 to allow a new cycle
1145 Voltage 2 to allow a new battery cycle
1146 Duration of under voltage 2 to allow a new cycle
1156 Battery absorption voltage
1157 Duration of absorption
1159 Current at end of absorption
Adc
h
%
sec.
min.
y/n
10
3
10
0.8
3
yes
non
2.08
8
180
50
1161 Minimum interval between absorptions
1187 Sensitivity of the charge detection (100% approx.25W)
1189 Time interval between load search pulses
1190 Duration of undervoltage of battery before disconnection
1191 Dynamic compensation for undervoltage
1194 Battery adaptive low voltage allowed
1195 Max voltage for adaptive low voltage
1198 Time elapsing before transfer relay opens
1199 ACin voltage causing the opening of the transfer relay
1200 Immediate open critical threshold for the transfer
1246 Auxiliary contact 1 activated by voltage 1 {1247} after delays
{1248}
o/n
V/cell
sec.
Vac
Vac
y/n
yes
1247 Voltage 1under which auxiliary contact 1 is activated
1248 Delays on voltage 1 to activate auxiliary contact 1
1249 Auxiliary contact 1 activated by voltage 2 {1250} after delays
{1251}
V/cell
min.
y/n
1.95
1
yes
1250 Voltage 2 under which auxiliary contact 1 is activated
1251 Delays on voltage 2 to activate auxiliary contact 1
1252 Auxiliary contact 1 activated by voltage 3 {1253} after delays
{1254}
V/cell
min.
y/n
2
10
yes
1253 Voltage 3 under which auxiliary contact 1 is activated
1254 Delays on voltage 3 to activate auxiliary contact 1
V/cell
min.
2.05
60
1255 Voltage 1above which auxiliary contact 1 is deactivated after delays V/cell
2.25
60
yes
120
1
yes
80
5
1256 Delays on voltage {1255} to deactivate auxiliary contact 1
1258 Auxiliary contact 1 activated by power 1
1259 Power 1 above which auxiliary contact 1 is activated after delays
1260 Duration of power 1 for activating auxiliary contact 1
1261 Auxiliary contact 1 activated by power 2
1262 Power 2 above which auxiliary contact 1 is activated after delays
1263 Duration of power 2 for activating auxiliary contact 1
1264 Auxiliary contact 1 activated by power 3
min.
y/n
%
min.
y/n
%
min.
y/n
Vac
no
230
1286 Output voltage
Installation and operating Instructions
Xtender V1.3
Page 34
STUDER Innotec
Xtender
No. of
config.
Units
Fact. Mod.
Denomination / description
value
value
1298 Increment step of the adaptive low voltage method
1300 Number of overloads permitted before definite stoppage
mV/cell 20
--
3
1303 Number of battery overvoltages accepted before definite stoppage --
3
3
2.2
185
60
0
270
20
1304 Number of battery undervoltages permitted before final stop
1307 Reset voltage for adaptive correction
--
V/cell
Vac
sec.
sec.
Vac
V
1309 Minimum ACin voltage to authorise charging
1403 Period for counting battery overvoltages
1404 Period for counting battery undervoltages
1432 Maximum ACin voltage to switch to inverter mode
1433 Adaptation range of the charge current according to the input
voltage
1436 Allow to exceed AC input current without opening the transfer relay y/n
yes
10
no
1.5
15
5
1470 ACin voltage hysteresis for closing the transfer relay
1485 Automatic earth-neutral connection in inverter mode
1488 Critical under voltage of the battery
Vac
y/n
V/cell
Hz
1505 Delta of higher frequency accepted
1506 Delta of lower frequency accepted
Hz
1516 Auxiliary contact 1 deactivated by floating mode
1517 Auxiliary contact 2 deactivated by floating mode
1527 Decrease max input limit current with AC-In voltage
1528 Delay before closing transfer relay
y/n
y/n
o/n
Min.
yes
no
n
0
1532 Kind of dynamic compensation
Auto/Man Auto
To modify the configurations, please refer to the operating instructions for the RCC-02/03
remote control
Installation and operating Instructions
Xtender V1.3
Page 35
STUDER Innotec
Xtender
18 Technical data
Model
XTH 3000-12 XTH 5000-24 XTH 6000-48 XTH 8000-48
Inverter
Rated battery voltage
Input voltage range
Continuous power @ 25 °C
Smart boost power
30 minute load @ 25 °C
5 second load @ 25 °C
Maximum load
Maximum asymmetrical load
Load detection (standby)
Admissible cos phi
12 V
24 V
48 V
48 V
9.5 - 17 V
2500 VA
3000VA
3000 VA
19 - 34 V
4500 VA
5000 VA
5000 VA
38 - 68 V
5000 VA
6000 VA
6000 VA
39 - 68 V
7,000 VA
8000 VA
8000 VA
3 x Pcont
Up to short-circuit
Up to Pnom
2 to 25 W
0.1 – 1
Maximum efficiency
93%
94%
96%
96%
Open-circuit power OFF/standby/ON 1.3W/2.2W/14W 1.8W/2.5W/18W 2.2W/3W/22W 2.2W/3.8W/26 W
Output voltage
Output frequency
Harmonic distortion
Overcharge and short-circuit
Overheating protection
Battery charger
Sine wave 230 Vac (+/-2%) / 180-245 Vac
50 Hz adjustable 45-65 Hz +/- 0.05% (quartz-controlled)
<2%
Automatic disconnection then 2 startup attempts
Alarm prior to disconnection and automatic restart
6-phase battery charger
Adjustable charge current
Input current sharing system
Maximum input voltage
AC input voltage range
Admissible input frequency
(PFC)
Programmable I-U-Uo-equalisation-Uo(low)-U(periodic)
0 - 140 A
0 - 100 A
0 - 120 A
0 - 160 A
1 - 50 A
265 Vac
Level of detection adjustable from 150 to 230 Vac
45 - 65 Hz
EN 61000-3-2
Battery control (factory value / adjustable range with RCC-02)
End of absorption
Absorption voltage
Periodic absorption voltage
Floating voltage
Reduced maintenance voltage
Equalisation
End of equalisation
Equalisation voltage
Low voltage disconnection
Reduced floating duration
Periodical absorption
Temperature compensation
General data
by duration: 2h / 0.25 - 18 h or by current <10A / 2 - 50 A
14.4V / 9.5-18 V 28.8V / 19-36 V
- / 9.5 - 18 V - / 19 - 36 V
13.6V / 9.5-18 V 27.2V / 19-36 V
- / 9.5 - 18 V - / 19 - 36 V
57.6V / 38 - 72 V
- / 38 - 72 V
54.4V / 38 - 72 V
-- / 38 - 72 V
By number of cycles ( - / - 100) or at fixed intervals ( - / 52 weeks)
By duration 2h / 0.25 – 10h or by current - / 5 – 50 A
- / 9.5 - 18 V
10.8V / 9.5-18 V 21.6V /19-36 V
- / 0 - 32 days
- / 0 - 10 hours
- / 19-36 V
- / 38 - 72 V
43.2V / 38 - 72 V
-5 / 0 to-8 mV/°C/cell (optional BTC-01)
Auxiliary contacts
2 independent contacts 16 A - 250 Vac (potential-free 3 points)
Maximum transfer relay current
Maximum transfer time
Weight
Dimensions: H x W x D [mm]
Protection degree
50 A
0-15 ms
40 kg
230x300x500
IP20
34 kg
42 kg
46 kg
Conformity
EN 61000-6-1, EN 61000-6-3, EN 55014, EN 55022, EN 61000-3-2,
Dir. 89/336/EEC, LVD 73/23/EEC
Operating temperature range
Ventilation
-20 to 55 °C
Forced from 45 °C
Noise level
Warranty
<40 dB / <50 dB (without / with ventilation)
2 years
Options
Battery temperature sensor:
BTS-01
Remote control and programming centre for wall mounting: RCC-02
Remote control and programming centre for panel mounting: RCC-03
Installation and operating Instructions
Xtender V1.3
Page 36
|