MULTI SPLIT TYPE, HEAT PUMP AIR CONDITIONERS
Technical service manual
R410A Cassette Inverter multi Series
Indoor Models
SMF-C09AI
SMF-C12AI
SMF-C18AI
Outdoor Models
SMF-4E27AI
1
1. Features:
1) Fashion design, quality life;
2) Low operation noise;
3) High efficiency screw fan;
4) Equal, fast, wide-angle cooling, more comfortable.
3
2.Specification
indoor unit
Model
SMF-C09AI
SMF-C12AI
SMF-C18AI
1Ph,220-240V~,50Hz 1Ph,220-240V~,50Hz 1Ph,220-240V~,50Hz
Power supply
Capacity
Ph-V-Hz
BTU/h
BTU/h
Mpa
9,000
11,000
4.2/2.5
3.7
12,000
13,000
4.2/2.5
3.7
18,000
20,500
4.2/2.5
3.7
Cooling Capacity
Heating Capacity
Design Pressure (Hi/Lo)
Max. Operating Pressure
Model
Mpa
YDK45-4F
Welling
80
YDK45-4F
Welling
80
YDK45-4F
Welling
80
Brand
Indoor fan motor
Power Input
W
1.5uF/450V
750/660/540
2
1.5uF/450V
830/730/680
2
2.5uF/450V
930/830/660
2
Capacitor
uF
Speed(hi/mi/lo)
a.Number of rows
b.Tube pitch(a)x row pitch(b)
c.Fin spacing
r/min
21x13.37
1.3
21x13.37
1.3
21x13.37
1.3
mm
mm
Hydrophilic aluminium Hydrophilic aluminium Hydrophilic aluminium
d.Fin type (code)
Indoor coil
Ф7.94, innergroove
tube
Ф7.94, innergroove
tube
Ф7.94, innergroove
tube
e.Tube outside dia.and type
mm
mm
1185X210X26.7
1185X210X26.7
1185X210X26.7
f.Coil length x height x width
g.Number of circuits
5
5
5
600/500/420
36/33/30
680/580/500
36/33/30
860/760/650
43/40/38
Indoor air flow (Hi/Mi/Lo)
m3/h
Indoor noise level (Hi/Mi/Lo)
dB(A)
φ6.35 (1/4’)
φ9.53 (3/8’)
φ6.35 (1/4’)
φ12.7 (1/2’)
φ6.35 (1/4’)
φ12.7 (1/2’)
Liquid side/ Gas side
mm(inch)
Pipe size
580×254×580
580×254×580
580×254×580
Indoor
Dimension (W*H*D)
Packing (W*H*D)
mm
mm
unit(body)
750x340×750
750x340×750
750x340×750
4
21/28
650x30x650
715x115x715
3/5
21/28
650x30x650
715x115x715
3/5
28/36
650x30x650
715x115x715
3/5
Net/Gross weight(body)
Dimension (W*H*D)
Kg
mm
mm
Kg
Indoor
unit(panel)
Packing
(W*H*D)
Net/Gross weight(panel)
m2
14-21
18-26
35-40
Application area
Qty per 20’/40’/40’HQ
Pieces
5
OUTDOOR UNIT:
Outdoor Model
SMF4E27AI
double
1Ph,220-240V~,50Hz
Indoor unit combination
Power supply
single
Treble
Quadplex
Ph-V-Hz
Btu/h
W
Cooling Capacity range
7000~18000
750~1870
3.1~7.8
14000~24000
21000~26000
2050~2600
27000
2650
11.1
Rated input power range
Rated current range
EER
1450~2430
6.1~10.1
Cooling
Heating
A
8.56~10.9
10.2
Heating Capacity range
Rated input power range
Rated current range
COP
Btu/h
W
9000~18000
850~1790
3.5~7.5
16000~25000
1470~2520
6.1~10.5
21000~27000
2020~2650
28000
2700
11.3
A
8.43~11.1
10.4
Max. input consumption
W
A
4500
25
Max. current
Model
BA160X2CS-20KU
Rotary inverter
GD Toshiba
18000(60HZ)
1690(60HZ)
11.6(60HZ)
60
Type
Brand
Capacity
Btu/h
W
Input
Compressor
Rated current(RLA)
Locked rotor Amp(LRA)
Thermal protector
Capacitor
A
A
Internal
uF
ml
85UF/250V
Refrigerant oil
fan
Model
RB68AF/α68TF/T-68
750 ml
Outdoor
motor
YDK100-6
Welling
Brand
6
Input
W
uF
169(HIGH)
5uF/500VAC
900(HIGH)
2
Capacitor
Speed
r/min
a.Number of rows
b.Tube pitch(a)x row pitch(b)
c.Fin spacing
mm
mm
25.4×22
1.5
Outdoor coil
d.Fin type (code)
e.Tube outside dia.and type
f.Coil length x height x width
g.Number of circuits
Hydrophilic aluminium
φ9.53 innergroove tube
850×810×44
2
mm
mm
Outdoor air flow
m3/h
dB(A)
mm
3500
Outdoor noise level
57
Dimension(W*H*D)
Packing (W*H*D)
Net/Gross weight
895X860X330
1043X915X395
80/84
Outdoor unit
mm
Kg
Refrigerant type and charge
Design pressure(Hi/Lo)
g
R410A, 2700
4.2/2.5
MPa
mm(inch)
Liquid side/ Gas side
6.35(1/4)/9.53(3/8)
Max. refrigerant pipe length for
each unit
Refrigerant
piping
m
m
20
10
Max. difference in level between
indoor and outdoor unit
Connection wiring
Plug type
No
No
Thermostat type
Electronic control
17~43
℃
℃
Cooling
heating
Operation temp
-7~21
7
Qty’per 20’ /40’ /40'HQ
set
Notes:
1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB;
Outdoor temp: 35°CDB;
Equivalent ref. Piping: 8m(horizontal)
Outdoor operating frequency:78Hz
Indoor combination:7K X4, setting temp.:17℃,setting fan speed: high speed.
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB;
Outdoor temp: 7°CDB, 6°CWB;
Equivalent ref. Piping: 8m(horizontal)
Outdoor operating frequency:85Hz
Indoor combination:7K X4, setting temp.:30℃,setting fan speed: high speed.
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an anechoic room.
8
3.Outline and dimension
Indoor unit(7k/9k/12k/18k):
Hook
Panel
Body
Nut
Ceiling
600
Chart 4
401(Hook-location)
580(Body)
67
600(Ceiling hole)
650(Panel)
Outdoor unit
1013
895
163
590
141
COMP
9
4.Indoor unit combination:
Caution on combination
The one-drive-four outdoor unit SMF-4E27AI nominal cooling capacity is 8kw(under
condition of ambient temp. 35℃db/24℃wb, indoor temp. 27℃db/19℃wb). According to
refrigeration design criterion, total indoor unit capacity should be equal to outdoor capacity,
otherwise, we can not guarantee best performance and safe operation. Although, we made
special design on refrigeration system regarding customer’s requirements. Based on this,
when indoor total capacity exceed outdoor capacity, the machine can still run. Under this
condition, the single indoor unit capacity will attenuate. That means you can not gain the
nominal capacity, but smaller than it. We are out of responsibility if customers don’t follow the
notice below:
1. You can connect two, three or four indoor units according to your need;
2. The total indoor unit nominal capacity should not exceed 11.3kw(42% more than nominal
capacity);
3. There should be no more than one 18k (either cassette or duct) indoor unit when four
indoor units are connected, and other indoor unit should be all 7k;
4. When three or four indoor units are connected, there should be no more than one cassette.
If the cassette is present, the other duct should be all 7K
5. There is no limit to two indoor units combination.
6. When heating, capacity attenuate sharply if indoor unit capacity exceed too much.
10
5. Capacity table
SMF-4E27AI (7k+7k+7k+7k)
COOLING
Indoor
OUTDOOR TEMPERATURE DRY
21ºC
25ºC
30ºC
35ºC
40ºC
45ºC
Conditions
Total capacity kW
Sensitive capacity kW
Input kW.
7.63
6.11
1.95
8.36
6.69
2.06
9.09
7.27
2.17
10.45
8.36
2.50
7.30
5.84
2.23
7.99
6.40
2.36
8.69
6.95
2.48
9.99
7.99
2.85
7.03
5.63
2.51
7.70
6.16
2.65
8.37
6.70
2.79
9.63
7.70
3.21
6.64
5.31
2.79
7.27
5.81
2.95
7.90
6.32
3.10
9.09
6.37
5.10
3.07
6.98
5.58
3.24
7.58
6.07
3.41
8.72
6.98
3.92
6.17
4.94
3.35
6.76
5.41
3.53
7.35
5.88
3.72
8.45
6.76
4.28
21ºC D
15ºC W
Total capacity kW
Sensitive capacity kW
Input kW.
24ºC D
17ºC W
Total capacity kW
Sensitive capacity kW
Input kW.
27ºC D
19ºC W
Total capacity kW
Sensitive capacity kW
Input kW.
32ºC D
7.27
3.57
23ºC W
HEATING
OUTDOOR CONDITIONS
4ºC D 0ºC D -5ºC D -7ºC D -15ºC D
3ºC W -1ºC W -6ºC W -8ºC W -16ºC W
Indoor
24ºC D 12ºC D 7ºC D
Conditions
18ºC W 11ºC W 6ºC W
Capacity
kW
14.66
5.52
11.73
4.42
11.02
4.15
10.20
3.84
9.38
3.53
8.16
9.78
3.68
9.18
3.46
8.50
3.20
7.82
2.94
6.80
8.80
3.50
8.26
3.28
7.65
3.04
7.04
2.80
6.12
8.31
3.31
7.80
3.11
7.23
2.88
6.65
2.65
5.78
7.33
3.13
6.89
2.94
6.38
2.72
5.87
2.50
5.10
6.84
2.94
6.43
2.76
5.95
2.56
5.47
2.36
4.76
6.35
2.58
5.97
2.42
5.53
2.24
5.08
2.06
4.42
15ºC
18ºC
20ºC
22ºC
27ºC
Input kW.
Capacity
kW
13.77
5.18
Input kW.
Capacity
kW
12.75
4.80
Input kW.
Capacity
kW
11.73
4.42
Input kW.
Capacity
kW
10.20
Input kW.
3.84
3.07
2.56
2.43
2.30
2.18
2.05
1.79
11
6. WIRING DIAGRAM
Indoor unit:
12
Outdoor unit (SMF-4E27AI)
13
7. Electric control functions:
7.1 Protection
1. 3 minutes delay at restart for compressor.
2. Temperature protection of compressor top, compressor stops when the temp. of top of
compressor is more than 120℃, compressor runs when the temp. of top of compressor is less
than 105℃.
3. When AC voltage ³ 270V for 30 seconds, Outdoor Unit stops operation and alarms.
When AC voltage £ 260V for 30 seconds, Outdoor Unit resumes operation.
4. Inverter module protection, Inverter module Protection itself has a protection function
against current, voltage and temperature.
5. Sensor protection at open circuit and breaking disconnection.
6. Fan Speed is out of control. When Indoor Fan Speed is too high(higher than High
Fan+300RPM)or too low(lower than 400RPM), the unit stops and LED displays failure
information and can’t return to normal operation automatically.
7. Cross Zero signal error warning. If there is no Cross Zero signals in 4 minutes, the unit
stops and LED displays failure information and can’t return to normal operation automatically.
8. Current protection: When the current is more than 25A, the compressor stops.
9. Outdoor condenser high temperature protection: Under cooling mode, if T3>65℃ for 3
minutes, the compressor will stop. When T3<52℃, the protection is not valid.
10. Outdoor low temperature protection: If the outdoor temperature is lower than -15℃ for
1hour, the compressor and fan motor will stop. If the outdoor temperature is higher than -12℃
for 10 minutes and the compressor stops operation for 1h, or the outdoor temperature is
higher than 5℃ for 10 minutes, then restart and enter into the prior operation mode.
11. Compressor pre-heating function: When the outdoor temperature is lower than 3℃ and
the compressor stops operation for more than 3 hours, or the outdoor temperature is lower
than 3℃ and the power is just put on, the compressor enters into pre-heating condition. When
outdoor temp. is more than 5℃ or user operate it, pre-heating condition will finish.
7.2 Operating mode
7.2.1 Cooling mode
1.Indoor fan keeps running, fan speed can be set in high/mid/low/ Auto:
2.Auto fan at cooling mode: (T=Indoor Temp.-Setting Temp.)
Condition
T<1.5℃
1.5℃<T<4℃
T>4℃
Indoor fan speed
Room temp. up
Low
Mid.
High
High
Mid.
Low
Room temp. down
T> 3℃
1℃<T<3℃
T<1℃
3.Anti-freezing control to indoor evaporator at cooling mode( T: evaporator temp. )
Evaporator Temp.
Compressor
T< 4℃
Off
On
T > 8℃
14
7.2.2 Dehumidifying mode
1.The indoor fan is fixed in low speed
2. Low room temperature protection:
When room temperature decreases to below 10℃, indoor fan stop, when room temperature
restores to over 12℃, indoor fan start.
3. At dehumidifying mode, the anti-freezing function of the indoor heat exchanger is the same
as that of cooling mode.
7.2.3 Heating mode
1. Indoor Fan actions at heating mode
Indoor Fan can be set at HIGH/MID/LOW/AUTO by using a remote controller, but Anti-cold
wind function prevails.
Anti-cold wind control function at heating mode
Condition
Indoor fan speed
T= Indoor exchanger
temp.
Indoor exchanger temp. T<34℃
Off
up
34℃<T<37℃
37℃<T<44℃
T> 44℃
Breeze
Low speed
Setting fan speed
Indoor exchanger temp. T> 38℃
Setting fan speed
Low speed
Breeze
down
33℃<T<38℃
24℃<T<33℃
T<24℃
Off
1. Auto wind at heating mode
Room temp. up
Condition
T=Indoor Temp.-Setting Temp.
T<1.5℃
Indoor fan speed
High
Mid.
Low
High
Mid.
Low
1.5℃<T<2.5℃
T>2.5℃
Room temp. down
T<1.0℃
1.0℃<T<2.0℃
T>2.0℃
2. Indoor evaporator high-temperature protection at heating mode
Condition
T= Indoor exchanger temp.
T<48℃
Compressor
On
53℃<T<63℃
T>63℃
Decrease frequency of compressor
Off
7.2.4 Defrost operation
1. Defrosting condition:
The temperature of outdoor heat exchanger remains consecutively lower than -2°c for more
than 40 minutes,
2. Ending condition of defrosting
15
If one of following conditions is satisfied, end the defrost and turn into heating mode:
a. The defrost time has reached to 10 minutes.
b. When the temperature of outdoor heat exchanger rises up to 15°C.
3. Defrosting Actions:
a. Compressor runs.
b. 4 way valve switches off,
c. Outdoor fan switches off
d. Indoor fan running according to anti-cold wind function in heating mode.
4. Automatic operation mode
The air conditioner automatically selects one of the following operation modes: cooling,
heating or fan only according to the temp. difference between room temp. (TA) and set
temp. (TS).
TA—TS
Operation mode
TA—TS>2℃
-1℃≤TA-TS≤+2℃
TA-TS<-1℃
Cooling
Fan-only
Heating (air-only for cooling only type)
7.3 Mode conflict
The indoor units can not work cooling mode and heating at same time.
Heating mode has a priority.
7.3.1 Definition
Cooling mode
Heating Mode
Fan
No
Yes
No
Off
No
No
No
No
Cooling mode
Heating Mode
Fan
No
Yes
No
Yes
No
Yes
No
Off
No
No
No: No mode conflict;
Yes: Mode conflict
7.3.2 In case of one Indoor unit working in cooling mode or fan mode, and another indoor
unit is set to heating mode, the indoor unit working in cooling mode or fan mode will
change to stand by. The outdoor unit will work in heating mode.
7.3.3 In case of one Indoor unit working in heating mode, and another indoor unit is set to
cooling mode or fan mode, the indoor unit setting to cooling mode or fan mode will
change to stand by.
7.4 Manual switch
Mode changes when push this button.
Cooing modeà Auto modeàUnit offà Cooing mode
At Cooing mode, after 30 minutes cooling operation whose fan speed is set as low, the
A/C operates with a setting temp. of 24℃.
At auto mode, the A/C operates with a set temp. of 24℃
7.5 Timer Function
16
1. The maximum length of timer is 24 hours and the minimum resolving power is 15 minutes.
2. Timer on: first turn off the A/C, the A/C will be automatically on at the set time.
3. Timer off: first turn on the A/C, the A/C will be automatically off at the set time
4. Timer on/off function( on time is earlier than off time): first turn off the A/C, it will be
automatically on at set time, and later be off at the set time, then unit turns on at set time.
5. Timer off/on function( off time is earlier than on time): first turn on the A/C, it will be
automatically off at set time, and later be on at the set time, then unit turns off at set time.
7.6 Auto restart function
In case of a sudden power failure, this function automatically sets the unit to previous settings
before the power failure when power returns.
7.7 Cooling capacity test frequency locked.
When test the cooling capacity, the frequency can be locked at 78Hz by following the below:
1. Set the indoor temp. to 17℃ and high speed;
2. Push the outdoor check button for 5 seconds, then its frequency can be fixed at 78Hz.
After the test is over, turn off the indoor to exit.
When test the heating capacity, the frequency can be locked at 85Hz by following the below:
1. Set the indoor temp. to 30℃ and high speed;
2. Push the outdoor check button for 5 seconds, then its frequency can be fixed at 78Hz.
After the test is over, turn off the indoor to exit.
7.8 Indoor unit indicator display function:
Operation Timer De-frost Alarm State
★
X
X
X
★
X
X
X
Indoor room temp. sensor open or short-circuit
Indoor pipe temp. sensor open or short-circuit
Indoor and outdoor communication error
Water level alarm
X
X
★
X
★
X
X
X
★
★
★
★
★
★
★
★
X
X
X
EEPROM error
●
X
X
Inverter module protection
●
●
X
X
Outdoor sensor open or short circuit
Outdoor voltage protection
●
X
X
●
●
★
Compressor top temp. protection
Mode conflict
●
★
X
X
Outdoor current protection
★ flash, ● light, X extinguished.
17
7.9 Outdoor unit LED display function:
1. When stand-by it display number of indoor unit online;
2. When operation it display frequency of outdoor unit;
3. When defrost it display “df”;
4. When a protection or error occurred, it display as the following table:
Display
E0
Explanation
EEPROM error
E1
No 1 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
No 2 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
No 3 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
Outdoor temp. sensor or connector of temp. sensor is defective
Compressor voltage protection
E2
E3
E4
E5
E6
No 4 Indoor units pipe temp. sensor or connector of pipe temp. sensor is defective
Indoor and outdoor communication error
E7
P0
Compressor top protection against temperature
High pressure protection
P1
P2
Low pressure protection
P3
Compressor current protection
P4
Inverter module protection
P5
Outdoor low temp. protection
P6
Condenser high-temperature protection
7.10 Check function:
There is a check button on outdoor pcb. When push this button, the outdoor LED can display
in sequence:
Capacity demand→Running mode →revised capacity → fan state →No.1 evaporator pipe
temp. →No.2 evaporator pipe temp.→No.3 evaporator pipe temp.→No.4 evaporator pipe
temp.→outdoor pipe temp. → Outdoor temp. →discharge gas temp.→current of outdoor unit
→ No. 1 opening degree of electronic expansion valve → No. 2 opening degree of EXV →
No. 3 opening degree of EXV→No. 4 opening degree of EXV→indoor unit number→last
protection/error code→capacity demand(cycle)
Explanation for the some display content:
1. Running mode:
Display
Corresponding mode
Off
Cooling mode
Heating mode
0
1
2
18
2. Fan state:
Display
Corresponding mode
0
1
2
Off
Low fan
High fan
3. Opening degree of EXV:
Opening degree equals the display data times 8;
4. Number of indoor unit
The indoor unit that can communicate with outdoor unit normally.
7.11 Outdoor fan speed control
There is one fan with two-speed, the fan speed is controlled according ambient temp. After
the compressor stop, 30 seconds later the fan stop.
When cooling:
> 27
<27
>25
<25
High speed
Low speed
High speed
Low speed
Ambient temp.rise
Ambient
temp.decline
When heating:
Ambient temp.rise
> 14
<14
>12
<12
Low speed
High speed
Low speed
High speed
Ambient
temp.decline
7.12 Oil return function
If operation frequency is lower than 54Hz in 2 hours consecutively, it will be increased to 62Hz
for 3 minutes. Then it recovers to the former operation frequency.
19
12
13
Pipe Temperature Sensor
Evaporator Ass'y
Fixing clamp, evaaporater
Deseparating board, left
Inlet pipe, eva
Ass'y
1
1
1
1
1
1
1
1
1
1
1
4
1
2
1
1
1
2
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
50118121032
50118121011
50112111011
50112111012
50118121009
50118121002
50112111014
50112111015
50236113805
50112111017
50112111018
50112111019
50112111020
50118121036
50112111021
50112111022
50112111023
50112111024
50112111025
50112111026
50118121041
50118121042
50112111027
50112111028
50112111029
50112111030
50112111031
50112111032
50112111033
50112111032
50224121049
50112111039
10324121004
50218131002
50118121053
50118121020
10718121808
11318111004
10112121815
50118121016
50118121022
2244050004
2154209004
2124200413
2124200404
2164209006
2165239000
2124200406
2110011001
2240041405
2124200405
2124200401
2124200402
2124200411
2274200401
2114209078
2114200444
2124200421
2114200446
2114200443
2114200441
2114200420
2334209008
2114200447
2114200445
2240028001
2114208051
8104200409
8104200402
8104200403
8104200402
2335509100
2124200407
2334209040
2124200423
2274200402
2135239000
2230090015
2230080071
2240119047
2114090018
2114090005
14
15
16
17
Outlet pipe, eva
Wire crossing board
Fan
18
19
20
Fan Motor
21
Fan Motor Underlay
Base Pan Ass'y
Fixing board, water pan
Sealing board, pipe out
Rubber, wire crossing
Panel Ass'y
22
23
24
25
26
26.1
26.2
26.3
26.4
26.5
26.6
26.7
26.8
26.9
Air inlet grille
Switch cover, air inlet grille
Switch, air inlet grille
Filter
Control box
LED holder
Control board
Cover, control box
Fan guide
26.10 Swing motor
26.11 Panel
26.12 Install cover, swing motor
26.13 Install cover I
26.14 Install cover II
26.15 Install cover I
27
Remoter
28
Control Box Cover
E-control Assy
Control Box
29
29.1
29.2
29.3
29.4
29.5
29.6
29.7
29.8
Rubber, wire crossing
PCB Ass'y
Transformer
Relay
Capacity
Base, wire fixing
Cover, wire fixing
21
11
12
Drain Pump Holder
Pipe Temperature Sensor
Evaporator Ass'y
Fixing clamp, evaaporater
Deseparating board, left
Inlet pipe, eva
1
1
1
1
1
1
1
1
1
1
1
1
4
1
2
1
1
1
2
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
50112111010
50118121032
50118121011
50112111011
50112111012
50118121009
50118121002
50112111014
50112111015
50236113805
50112111017
50112111018
50112111019
50112111020
50118121036
50112111021
50112111022
50112111023
50112111024
50112111025
50112111026
50118121041
50118121042
50112111027
50112111028
50112111029
50112111030
50112111031
50112111032
50112111033
50112111032
50224121049
50112111039
10324121004
50218131002
50118121053
50118121020
10718121808
11318111004
10112121815
50118121016
50118121022
2124200409
2244050004
2154209004
2124200413
2124200404
2164209006
2164209109
2124200406
2110011001
2240041405
2124200405
2124200401
2124200402
2124200411
2274200401
2114209078
2114200444
2124200421
2114200446
2114200443
2114200441
2114200420
2334209008
2114200447
2114200445
2240028001
2114208051
8104200409
8104200402
8104200403
8104200402
2335509100
2124200407
2334209040
2124200423
2274200402
2135239000
2230090015
2230080071
2240119047
2114090018
2114090005
Ass'y
13
14
15
16
17
Outlet pipe, eva
Wire crossing board
Fan
18
19
20
Fan Motor
21
Fan Motor Underlay
Base Pan Ass'y
Fixing board, water pan
Sealing board, pipe out
Rubber, wire crossing
Panel Ass'y
22
23
24
25
26
26.1
26.2
26.3
26.4
26.5
26.6
26.7
26.8
26.9
Air inlet grille
Switch cover, air inlet grille
Switch, air inlet grille
Filter
Control box
LED holder
Control board
Cover, control box
Fan guide
26.10 Swing motor
26.11 Panel
26.12 Install cover, swing motor
26.13 Install cover I
26.14 Install cover II
26.15 Install cover I
27
Remoter
28
Control Box Cover
E-control Assy
Control Box
29
29.1
29.2
29.3
29.4
29.5
29.6
29.7
29.8
Rubber, wire crossing
PCB Ass'y
Transformer
Relay
Capacity
Base, wire fixing
Cover, wire fixing
23
15
16
Deseparating board, left
Inlet pipe, eva
1
1
1
1
1
1
1
1
4
1
2
1
1
1
2
1
1
1
1
1
4
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
50112111012
50118121009
50118121002
50112111014
50112111015
50236113805
50112111017
50112111018
50112111019
50112111020
50118121036
50112111021
50112111022
50112111023
50112111024
50112111025
50112111026
50118121041
50118121042
50112111027
50112111028
50112111029
50112111030
50112111031
50112111032
50112111033
50112111032
50224121049
50112111039
10324121004
50218131002
50118121053
50118121020
10718121808
11318111004
13607111808
50118121016
50118121022
2124200404
2164209006
2164209109
2124200406
2110011001
2240041405
2124200405
2124200401
2124200402
2124200411
2274200401
2114209078
2114200444
2124200421
2114200446
2114200443
2114200441
2114200420
2334209008
2114200447
2114200445
2240028001
2114208051
8104200409
8104200402
8104200403
8104200402
2335509100
2124200407
2334209040
2124200423
2274200402
2135239000
2230090015
2230080071
2240119019
2114090018
2114090005
17
Outlet pipe, eva
Wire crossing board
Fan
18
19
20
Fan Motor
21
Fan Motor Underlay
Base Pan Ass'y
Fixing board, water pan
Sealing board, pipe out
Rubber, wire crossing
Panel Ass'y
22
23
24
25
26
26.1
26.2
26.3
26.4
26.5
26.6
26.7
26.8
26.9
Air inlet grille
Switch cover, air inlet grille
Switch, air inlet grille
Filter
Control box
LED holder
Control board
Cover, control box
Fan guide
26.10 Swing motor
26.11 Panel
26.12 Install cover, swing motor
26.13 Install cover I
26.14 Install cover II
26.15 Install cover I
27
Remoter
28
Control Box Cover
E-control Assy
Control Box
29
29.1
29.2
29.3
29.4
29.5
29.6
29.7
29.8
Rubber, wire crossing
PCB Ass'y
Transformer
Relay
Capacity
Base, wire fixing
Cover, wire fixing
25
SMF-4E27AI
1
2
Clamp for front net
8
1
1
1
1
1
1
1
1
1
1
2113511801
2114550002
2123549027
2240041722
2124550017
2124532935
2124820000
2124530063
2115029006
2124532936
2124532912
Propeller fan
Holder for fan motor
fan motor
3
4
5
Front net
6
Front clapboard
Separating board
Left clapboard
Little handle
7
8
9
10
11
Cover
Supporter of back
26
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
electrical box assembly
Rear net
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2335739000
2114820000
2154709047
2114540003
2165739017
2165739004
2115739000
2165739002
2165739000
2125739003
2124532903
2125739002
2113560000
2165739006
2125739004
2165739019
2125019019
2230100814
2230100815
2140062190
2125020303
2125020305
2125020306
2230100810
Condenser Ass'y
Handle
D high pressure valve assembly.
C high pressure valve assembly.
Big handle
B high pressure valve assembly.
A high pressure valve assembly.
Rear right clapboard
Cabinet,Front-Right
installation board for valve
drain pan
Capillary pipe Ass'y
Base Pan
Ass'y
four way valve assembly
inductance box
reactance
reactance
Compressor
upper cover of inductance
base of inductance
surrounding board for inductance
reactance
27
|