Schneider Electric Duradrive Direct Coupled Actuators Ma40 704x User Manual |
MA40-704X Series,
MA4X-707X Series,
MA4X-715X Series
DuraDrive Series Spring Return
Two-Position Actuators
General Instructions
Application
DuraDrive™ Direct Coupled Actuators are designed to
be used in both damper and valve control applications.
The follow general instructions are for damper
applications, refer to the Applicable Literature table for
valve literature.
The MA40-704X, MA4X-707X and MA4X-715X series
spring return actuators are used for the on-off, fail safe
control of dampers and valves in HVAC systems.
MA40-707X
MA40-715X
Features
• Two-position actuator controlled by SPST controller
• 133 lb-in (15 N-m), 60 lb-in (7 N-m), and 35 lb-in
(4 N-m) torque models
• 24 Vac/DC, 120 Vac, and 230 Vac models
• Rugged die cast housings rated for NEMA 2 / IP54
• Overload protection throughout rotation
MA40-704X
• Optional built-in auxiliary switch to provide for
interfacing or signaling
• Provides 95° of rotation
• Visual position indicator provided
• Provides true mechanical clockwise or
counterclockwise spring return operation for reliable
fail safe application and positive close-off in air tight
damper applications
• Direct mount to round or square damper shafts
• Rotation limiting available
• MA4X-7153 series actuators can be double-
mounted (gang mounting) to accommodate high
torque application requirements
MA41-707X
MA41-715X
• Five year warranty
• MA41-707X-XXX and MA41-715X-XXX equipped
with manual override
Printed in U.S.A. 1/10
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
SPECIFICATIONS
Actuator Inputs
Control Signal: On-off, spring return. SPST control contacts or Triacs (500 mA rated).
Class 1.
Connections: 3 ft. (91 cm) appliance cables, 1/2 in. conduit connector. For M20 Metric
conduit, use AM-756 adaptor.
Actuator Outputs
Electrical:
Auxiliary Switches,
MA4X-715X-502 and MA4X-707X-502 Two SPDT 7A (2.5A) @250 Vac, UL listed;
one fixed @ 5° and one adjustable 25 to 85°.
MA40-7040-501 and MA40-7041 -501 One SPDT 6A (1.5A) @250 Vac, UL listed;
adjustable 0 to 95° (0 to 1 scale).
MA40-7043-501 One SPDT 6A (1.5A) @24 Vac, UL listed; adjustable 0 to 95°
(0 to 1 scale).
Mechanical:
Stroke, Angle of rotation 95° ± 5° maximum. Adjustable 30° to 95° with AM-689 installed
on MA4X-715X or MA4X-707X series. Stroke limiter is standard on MA40-704X series.
Damper Shaft Clamp,
MA40-704X The factory installed universal clamp is used for shafts up to 5/8”
(15 mm) diameter or up to 1/2" (13 mm) square. AM-710 accessory clamp is required
when mounting actuators to shafts up to 3/4" (19 mm) diameter or up to 1/2" (13 mm)
square.
MA4X-715X or MA4X-707X The factory installed universal clamp is used for shafts
up to 3/4" (19 mm) diameter or up to 1/2" (13 mm) square. AM-687 accessory clamp
is required when mounting actuators to shafts up to 1.05" (27 mm) in diameter or up
to 5/8" (15 mm) square.
Position Indicator, Visual indicator.
MA4X-715X and MA4X-707X, -5 to 90° (-5° is spring return position).
MA40-704X, 0 to 1 (0 is spring return position).
Nominal Damper Area, Actuator sizing should be done in accordance with damper
manufacturer’s specification.
Direction of Rotation, Clockwise or counterclockwise rotation determined by actuator
mounting.
o
o
Manual Override, MA41-707X and MA41-715X rotation is adjustable from -5 to 85
using manual override crank.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 F to 160°F (-40 to 71°C).
Operating, -22 to 140°F (-30 to 60°C).
Humidity: 15 to 95% RH, non-condensing.
Location:
MA4X-715X and MA4X-707X, NEMA 1 (IEC IP30). NEMA 2 (IEC IP54) with conduit
connector in the down position.
MA40-704X, NEMA 2 (IEC IP54) no restrictions.
Agency Listings
UL 873: Underwriters Laboratories (File # E9429 Category Temperature-Indicating and
Regulating Equipment).
CUL: UL Listed for use in Canada by Underwriters Laboratories. Canadian Standards
C22.2 No. 24.
European Community: EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
Australia: This product meets requirements to bear the C-Tick Mark according to the terms
specified by the Communications Authority under the Radiocommunications Act 1992.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
3
Table-1 Model Chart.
Approximate
Timing in
Seconds @ 70°
(21°C)a
Output Torque
Rating
Actuator Power Input
VA
lb-in (N-m)b
Auxiliary
Switch
Part Numbers
Voltage
Watts
Running
60
Holding
Spring
Powered
Maximum Manual
Minimum
DC
Amps
Return
Stall
Override
50 Hz
50
60
Hz
50 Hz 60 Hz
Hz
Hz
MA40-7153
No
Twoc
No
No
No
MA40-7153-
502
24 Vac
± 20%
22-30
Vdc
9.8
9.7 7.5 7.5
0.29
2.8
3.6
4.6
0.8
2.0
2.8
5.0
3.3
0.8
1.2
MA41-7153
Yes
Yes
No
MA41-7153-
502
Twoc
No
MA40-7150
MA40-7150-
502
Twoc
No
No
120 Vac
±10%
11.7 10.0 8.8 8.4
—
<190
<30
133 (15)
350 (40)
MA41-7150
Yes
Yes
No
MA41-7150-
502
Twoc
No
MA40-7151
MA40-7151-
502
Twoc
No
No
230 Vac
±10%
15.5 10.6 9.5 8.5
—
MA41-7151
Yes
Yes
No
MA41-7151-
502
Twoc
No
MA40-7073
MA40-7073-
502
24 Vac
± 20%
22-30
Vdc
Twoc
No
No
4.8
4.8 3.2 3.2
0.13
MA41-7073
Yes
Yes
No
MA41-7073-
502
Twoc
No
MA40-7070
MA40-7070-
502
Twoc
No
No
120 Vac
±10%
10.7
5.6 4.2 3.6
—
<80
<40
60 (7)
250 (28)
MA41-7070
Yes
Yes
No
MA41-7070-
502
Twoc
No
MA40-7071
MA40-7071-
502
Twoc
No
No
230 Vac
±10%
17.0
4.4
8.0 5.1 4.0
—
2.7
0.8
1.4
0.8
MA41-7071
Yes
Yes
No
MA41-7071-
502
Twoc
No
MA40-7043
24 Vac
± 20%
22-30
Vdc
4.4 2.9 2.9
0.11
MA40-7043-
501
Oned
No
MA40-7040
No
Oned
No
No
No
No
No
120 Vac
±10%
<50
<26
35 (4)
150 (17)
6.4
5.8
4.3 3.8 3.4
4.6 4.1 3.9
—
—
1.6
1.5
1.2
1.2
MA40-7040-
501
MA40-7041
230 Vac
±10%
MA40-7041-
501
Oned
a
Timing was measured with no load applied to the actuator.
De-rating is required at low temperatures.
One adjustable from 25 to 85° rotation and one set to operate @ 5° fixed.
One adjustable from 0 to 95° rotation (0 to 1 scale).
b
c
d
4
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
ACCESSORIES
For use with MA4X-7XXX:
AM-671
AM-672
AM-673
AM-674
AM-675
AM-676
AM-714
AM-756
AM-761
AM-762
Universal Mounting Bracket, AM-693 is required
Universal Mounting Bracket, AM-693 is required
Mounting Bracket
Weather Shield
Base Mounting Plate for AM-674
Universal Shaft Extension
Weather Shield (polycarbonate)
Metric Conduit Adapter M20 x 1.5 to 1/2" NPT
7-inch Anti-rotation Bracket
9-inch Anti-rotation Bracket
For use with MA40-7043:
AM-709
AM-710
AM-711
AM-712
AM-713
Position Indicator and Stroke Limiter
Universal Clamp for up to 3/4" diameter shafts
Crankarm for up to 1/2" round shaft
Crankarm Adapter Kit
Mounting Bracket for Honeywell Mod IV, M6415
type actuators and new installations
Crankarm Adapter Kit for Honeywell Mod IV,
M6415 type actuators and new installations
AM-715
For use with MX4X-7073, MX4X-7153
AM-686
AM-687
Damper Position Indicator
Universal Clamp for up to 1.05" (27 mm) diameter
shafts
AM-688
AM-689
AM-690
AM-691
AM-692
AM-693
AM-758
AM-759
AM-760
AM-763
Replacement Universal Clamp
Rotation Limiter
Crankarm for round shafts up to 3/4" (19 mm)
Crankarm for jackshafts up to 1.05" (27 mm)
V-bolt Kit for AM-690 and AM-691 Crankarm
Damper Linkage Kit
Short "U" Mounting Bracket
Tall "U" Mounting Bracket
Slotted "L" Mounting Bracket
1/8" Hex Crank for Manual Override
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
5
TYPICAL APPLICATIONS (wiring diagrams)
Optional Auxiliary
Switches
24 Vac Transformer
or 22-30 Vdc
Aux Switches
MA4X-7XXX-502
MA4X-7153
MA4X-7073
MA4X-7153-502
MA4X-7073-502
Blk
Com
Hot (+DC)
Grn/Yel
Com
NC
Org
Line
Volts
Aux Switch 1
25 to 85°
Adjustable
Red
Vio
Yel
NO
1
2
3
Com
NC
Org/Wht
Vio/Wht
Yel/Wht
SPST Control Contact
Aux Switch 2
5° Fixed
NO
MA4X-7150
MA4X-7151
MA4X-7070
Wire No. 1
Wire No. 2
Com
Hot
120 Vac or
230 Vac
L1 N
L2 H
1
2
Provide overload protection and disconnect as required.
Grn/Yel
MA4X-7071
Actuators mounted on separate shafts may be wired in
parallel. All actuator black wires are connected to the
transformer common and all red wires are connected to
the hot lead. Power consumption must be observed.
1
MA4X-7150-502
MA4X-7151-502
MA4X-7070-502
MA4X-7071-502
Voltage
Wire 1
Wire 2
3
For end position indication, interlock control, fan startup,
etc., MA4X-715X-502, and MA4X-707X-502 models
incorporate two built-in auxiliary switches.
120 Vac
230 Vac
White
Blue
Black
2
Brown
MX40-707X-502 and MX40-715X-502 units manufactured prior to the date code 0141
(October 6, 2001) used the following color coding for the auxiliary switches:
Auxiliary Switch 1
Orange:
Yellow:
Violet:
Fixed auxiliary switch common (com)
Fixed auxiliary switch normally closed (NC)
Fixed auxiliary switch normally open (NO)
Auxiliary Switch 2
Orange/white:
Violet/white:
Yellow/white:
Adjustable auxiliary switch common (com)
Adjustable auxiliary switch normally closed (NC)
Adjustable auxiliary switch normally open (NO)
The label information on these units is incorrect. If replacing these units, the auxiliary switch
operation of the replacement actuator will be per the product label.
Figure-1 Typical Wiring Diagram for 24 Vac Basic and Double Auxiliary Switch Models.
6
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
120 Vac or
230 Vac
MA40-7040
MA40-7041
Wire No. 1
Wire No. 2
Neutral
Hot
L1 N
L2 H
1
Green/Yellow
2
MA40-7040-501
MA40-7041-501
1
2
3
Provide overload protection and disconnect as
required.
120 Vac or
230 Vac
Wire No. 1
Wire No. 2
Neutral
Actuators may be wired in parallel. Power
consumption must be observed.
L1 N
L2 H
2
Hot
Green/Yellow
1
For end position indication, interlock control, fan
startup, etc., MA40-704X-501 model incorporates
one built-in auxiliary switch. See Specifications
section for details.
0 to 1 Scale
Adjustable
Orange
Violet
COM.
N.C.
Voltage
120 Vac
230 Vac
Wire 1
Wire 2
Black
3
Auxiliary Switch 1
White
Yellow
N.O.
Light Blue
Brown
Figure-2 Typical Wiring Diagram for 120 Vac or 230 Vac Basic and Single Auxiliary Switch Models.
MA40-7043
Black
Red
Common
Hot
(1)
(2)
Line
Volts
24 Vac
2
Green/Yellow
1
SPST Control Contact
MA40-7043-501
1
2
Provide overload protection and disconnect as
required.
Black
Red
Common
Line
Volts
24 Vac
Hot
Green/Yellow
2
Actuators may be wired in parallel. Power
consumption must be observed. Actuator may also
be powered by 24 Vdc.
1
3
For end position indication, interlock control, fan
startup, etc., MA40-7043-501 model incorporates
one built-in auxiliary switch. See Specifications
section for details.
SPST Control Contact
0 to 1 Scale
Adjustable
Orange
Violet
N.C.
N.O.
Auxiliary Switch 1
3
Yellow
Figure-3 Typical Wiring Diagram for 24 Vac Basic and Single Auxiliary Switch Models.
INSTALLATION
Inspection
Inspect the package for damage. If damaged, notify the appropriate carrier immediately. If
undamaged, open the package and inspect the device for obvious damage. Return
damaged products.
Requirements
• Job wiring diagrams
• Tools (not provided):
– #8 sheet metal screws
– 10mm open end wrench or socket wrench
– 7/16 inch, open end wrench or socket wrench
– 1/8 inch, allen wrench
– Appropriate screwdriver(s)
• Appropriate accessories
• Training: Installer must be a qualified, experienced technician
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
7
Precautions
General
Warning:
• Electrical shock hazard! Disconnect the power supply (line power) before installation to
prevent electric shock and equipment damage.
• Make all connections in accordance with the job wiring diagram and in accordance
with national and local electrical codes. Use copper conductors only.
Caution:
• Avoid electrical noise interference. Do not install near large contactors, electrical
machinery, or welding equipment.
• Do not drill holes in actuator body. Six pre-drilled holes are located on each side, under
the label, to accept #10-24 thread-forming screws for mounting accessories.
Caution: The MX41-707X and MX41-715X actuators are equipped with a manual
override.
• The manual override is to be used only when power is not applied to the unit.
• If the universal clamp is not set to 0° on the position indicator, manually wind the
actuator in the direction indicated with hex wrench from -5° to 0° and lock with a
screwdriver.
• When operating manual override, back off 5° from full open mechanical stop to ensure
proper release.
• Do not attempt to use the manual override with actuators mounted in tandem. Damage
to the gear train may occur.
Federal Communications Commission (FCC)
Note: This equipment has been tested and found to comply with the limits for a Class B
digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in residential installations. This
equipment generates, uses, and can radiate radio frequency energy and may cause
harmful interference if not installed and used in accordance with the instructions. Even
when instructions are followed, there is no guarantee that interference will not occur in a
particular—Which can be determined by turning the equipment off and on—the user is
encouraged to try to correct the interference by one or more of the following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment to an outlet on a circuit different from that to which the receiver
is connected.
• Consult the dealer or an experienced radio/television technician for help.
Canadian Department of Communications (DOC)
Note: This Class B digital apparatus meets all requirements of the Canadian Interference-
Causing Equipment Regulations.
Cet appareil numerique de la classe B respecte toutes les exigences du Reglement sur le
material broilleur du Canada.
European Standard EN 55022
Warning: This is a Class B digital (European Classification) product. In a domestic
environment this product may cause radio interference in which case the user may be
required to take adequate measures.
Location
Caution: Avoid locations where excessive moisture, corrosive fumes, vibration, or
explosive vapors are present.
8
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
Mounting
Caution: To remain in NEMA 2/IP54 compliance, the MA4X-715X and MA4X-707X series
actuators should be mounted with conduit end down.
Mount the TAC DuraDrive Actuator directly on the damper shaft in locations that clear the
maximum dimensions of the actuator case and allow the actuator to be mounted flush to the
surface of the terminal box and perpendicular to the damper shaft.
Note: Some terminal boxes have sheet metal screw heads or other protrusions near the
damper shaft. In these cases, a spacer or shim may be added under the anti-rotation
bracket of the actuator to make the actuator perpendicular to the shaft.
Damper Actuator Sizing
Correct sizing of the actuator is necessary for proper control of dampers. The area of
damper that can be controlled by a given actuator is dependent upon the type of damper,
the quality of the damper, the pressure drop across the damper in the closed position, and
the velocity of the air flow through the damper. To obtain actual damper torque requirements,
contact the damper manufacturer.
Damper Shaft Sizing
Use the “Long Damper Shaft” mounting instructions if the damper shaft is at least 3-1/2"
(90 mm) long.
Use the “Short Damper Shaft” mounting instructions if the damper shaft is shorter than 3-1/2"
(90 mm) or the area around the damper shaft is too narrow to allow standard mounting, as
described in the “Short Damper Shaft” mounting section.
MA40-704X Series Installation
Note: The MA40-704X series actuator comes equipped with standard universal mounting
clamp. For damper shafts larger than 5/8" (16 mm) in diameter, the AM-710 universal
mounting clamp is required (order separately). The AM-710 clamp accommodates shafts
sizes up to 3/4" (19 mm) diameter shafts.
Long Shaft
Short Shaft
Min. 3/4" (20 mm)
Min. 3 1/2" (90 mm)
3/8" to 3/4" Diameter (10 mm to 20 mm)
3/8" to 1/2" Square (10 mm to 13 mm)
Move the damper to its normal position. Verify the controller action is set to match the
damper application.
Normally closed damper: when damper is closed, actuator position indicator should
be at 0°. When damper is open, actuator position indicator should be at 90°.
Normally opened damper: when damper is open, actuator position indicator should
be at 0°. When damper is closed, actuator position indicator should be at 90°.
A - Left
A - Right
Shaft Rotates
Clockwise
To Open
Shaft Rotates
Counterclockwise
To Open
This step determines
shaft rotation. Linkage
may change damper direction.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
9
B - Left - Long Shaft
B - Right - Long Shaft
2
1
2
2
R
2
L
3
1
1
3
L
4
4
"L" Marker
"R" Marker
1. Assemble mounting clamp.
2. Assemble retaining clip.
3. Place actuator over shaft.
4. Hand tighten clamp nuts.
Universal
mounting clamp.
1
2
Universal
mounting clamp.
1
2
Correct clamp mounting
position if actuator is
in normal spring
Retaining clip.
.4
.2
.4
.2
Retaining clip.
return position
(before preload)
0
0
L
R
B - Left - Short Shaft
B - Right - Short Shaft
B
B
2
"L" Marker
2
A
L
R
A
4
3
4
3
L
R
1
1
3
3
1
"R" Marker
1
2
2
2
2
1
2
3
Universal clamp.
1
2
3
Universal clamp.
Retaining clip.
A. Assemble damper position indicator.
B. Assemble retaining clip.
1. Position mounting clamp.
2. Assemble retaining clip.
Retaining clip.
Damper position indicator.
Damper position indicator.
3. Slide actuator over shaft.
4. Hand tighten clamp nuts.
Correct pointer mounting
position if actuator is
.4
.4
.2
.2
in normal spring
return position
0
0
L
(before preload)
R
10
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
C - Left and Right
Center the
Universal Bracket in the Slot
1
.8
.6
.4
.2
0
1/2
1/2
1
5
x 1
7
8
x 2
6
#8 Sheet Metal
Screw
1
5. Center bracket in slot.
6. Drill two holes.
7. Start one screw.
8. Swing bracket down.
D- Left
D- Right
C
L
C
L
Centerline
Centerline
10
10
12
14
14
5°
5°
11
13
11
13
9. Loosen clamp nuts.
10. Check that the shaft is in full zero position.
11. Swing actuator 5° in the direction of travel. Do not move shaft.
12. Tighten clamp nuts to 4 to 6 lb-ft (5.4 to 8.2 N-m) of torque.
13. Move bottom of actuator back into position.
14. Pivot bracket back into position.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
11
E- Left
E - Right
1
1
.8
.6
.4
.2
.8
.6
.4
.2
0
0
x 2
x 2
15
15
15. Tighten bracket screws.
Correct clamp mounting
position
.4
.2
.4
.2
(after 5˚ preload)
0
0
L
R
MA4X-707X and MA4X-715X Series Installation
Caution: Do not drill additional holes in the actuator body. Six pre-drilled holes are located
on each side, under the label, to accept #10-24 thread-forming screws for mounting
accessories.
Note: The MA40-707X and MA40-715X series actuators come equipped with standard
universal mounting clamp installed. For damper shafts larger than 3/4" (19 mm) in
diameter, the AM-687 universal mounting clamp is required (order separately). The AM-687
clamp accommodates round shaft sizes up to 1.05" (27 mm) in diameter or 5/8" (16 mm)
square shafts.
Caution: The MA41-707X and MA41-715X actuators are equipped with a manual
override.
• The manual override to be used only when power is not applied to the unit.
• If the universal clamp is not set to 0° on the position indicator, manually wind the
actuator in the direction indicated with hex wrench from -5° to 0° and lock with a
screwdriver.
• When operating manual override, back off 5° from full open mechanical stop to ensure
proper release.
• Do not attempt to use the manual override with actuators mounted in tandem. Damage
to the gear train could occur.
• Using power tools to adjust the manual override will cause damage to the gears.
• To unlock manual override without power, crank the manual override in the direction
indicated a minimum of 5°.
12
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
Long Shaft
Short Shaft
Min. 3/4" (20 mm)
Min. 3 1/2" (90 mm)
3/8" to 3/4" Diameter (10 mm to 20 mm)
3/8" to 1/2" Square (10 mm to 13 mm)
Move the damper to its normal position. Verify the controller action is set to match the
damper application.
Normally closed damper: when damper is closed, actuator position indicator should
be at 0°. When damper is open, actuator position indicator should be at 90°.
Normally opened damper: when damper is open, actuator position indicator should
be at 0°. When damper is closed actuator position indicator should be at 90°.
A - Left
A - Right
Shaft Rotates
Clockwise
To Open
Shaft Rotates
Counterclockwise
To Open
This step determines
shaft rotation. Linkage
may change damper direction.
For MA41-707X and MA41-715X only (manual override).
For MA40-707X and MA40-715X, proceed to step C.
B
If position indicator does not point to zero:Unlock the actuator.
Insert hex wrench into manual override.
Crank the actuator so the indicator points to 0°.
Lock the actuator.
R
Manual Override
R
L
R
L
Fully engage hex wrench
into manual override before
winding.
Unlock
Caution: Do not crank the manual
override if power is applied
to the actuator.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
13
- Long Shaft
C - Left
C - Right - Long Shaft
2
1
2
2
R
2
L
3
1
1
3
4
4
"L" Marker
R
L
LOCK
R
L
O
L
C
K
"R" Marker
1. Assemble mounting clamp.
2. Assemble retaining clip.
3. Place actuator over shaft.
4. Hand tighten clamp nuts.
Universal
mounting clamp.
Universal
mounting clamp.
1
2
1
2
Retaining clip.
Retaining clip.
For MA40-707X and MA40-715X actuators:
Correct clamp mounting
Correct clamp mounting
position if actuator is
locked with 5° preload.
position if actuator is
in normal spring
return position
L
R
R
L
C - Left - Short Shaft
C - Right - Short Shaft
B
B
2
"L" Marker
A
A
L
R
4
3
4
3
L
R
1
1
3
3
1
"R" Marker
1
2
2
2
2
1
2
3
Universal clamp.
1
2
3
Universal clamp.
A. Assemble damper position indicator.
B. Assemble retaining clip.
1. Position mounting clamp.
2. Assemble retaining clip.
Retaining clip.
Retaining clip.
Damper position indicator.
Damper position indicator.
3. Slide actuator over shaft.
4. Hand tighten clamp nuts.
For MA41-707X and MA41-715X actuators:
For MA40-707X and MA40-715X actuators:
Correct pointer mounting
position if actuator is
in normal spring
Correct pointer mounting
position if actuator is
locked at 5° preload.
return position
L
R
L
R
14
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
D - Left and Right
Center the
Universal Bracket in the Slot
R
1/2
1/2
5
1
7
x 2
6
#8 Sheet Metal
1
5. Center bracket in slot.
6. Drill two holes.
7. Start one screw.
Screw
x 1
For MA41-707X and MA41-715X actuators, insert and tighten both screws.
8. Swing bracket down (MA40 actuator only).
8
E- Left
E- Right
C
L
C
L
Centerline
Centerline
10
10
9
11
13
11
13
9. Loosen clamp nuts.
10. Check that the shaft is in full zero position.
For MA41-707X and MA41-715X only:
11. Tighten clamp nuts to 8 - 10 ft-lb (11 - 14 Nm).
This completes the installation for MA41-704X
and MA41-715X.
15
15
For MA40-707X and MA40-715X only:
12. Swing actuator 5° in the direction of travel. Do
not move shaft.
5°
5°
12
14
12
14
13. Tighten clamp nuts to 8 - 10 ft-lb (11 - 14 Nm).
14. Move bottom of actuator back into position.
15. Pivot bracket back into position.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
15
F- Left
F- Right
L
R
x 2
x 2
16
16
For MA40-707X and MA40-715X only:
16. Tighten bracket screws.
For MA40-707X and MA40-715X actuators:
Correct pointer position
after mounting.
L
R
For MA41-707X and MA41-715X actuators:
Correct pointer position
after mounting.
R
L
The lock on MA41-707X and MA41-715X will release on first power-up.
16
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
Jackshaft Installation
(MA40-704X Series)
The MA40-704X actuator is designed for use with jackshafts up to 3/4" (19 mm) in diameter.
In most applications, the MA40-704X actuator may be mounted in the same manner as a
standard damper shaft application. If the jackshaft diameter is larger than 5/8" (16 mm) in
diameter, the optional AM-710 universal clamp must be used.
(MA4X-715X and MA4X-707X Series)
The MA4X-715X and MA4X-707X actuators are designed for use with jackshafts up to 1.05"
(27 mm) in diameter. In most applications, the actuator may be mounted in the same manner
as a standard damper shaft application. If the jackshaft diameter is larger than 3/4" (19 mm)
in diameter, the optional AM-687 universal clamp must be used.
Multiple Actuator Mounting
If more torque is required than one actuator can provide a second actuator may be mounted
to the damper shaft, using the AM-673 multiple mounting bracket. See Figure-4.
Multiple actuators may be powered from one transformer provided the following rules are
followed:
• The total current draw of the actuators (VA rating) is less than or equal to the rating of
the transformer and less than the rating of the control circuit.
• Polarity on the secondary of the transformer is strictly followed.
– All L2 wires from all actuators are connected to the common lead on the
transformer.
– All L1 wires from all actuators are connected to the hot lead.
Caution: Mixing the L2 and L1 wires on one lead of the transformer may result in erratic
operation or failure of the actuator and/or controls.
Caution: Do not attempt to use the manual override with actuators mounted in tandem.
Damage to the gear train may occur.
Multiple actuators positioned by the same control signal may be powered from multiple
transformers provided the following rules are followed:
• The transformers are properly sized.
• All L2 wires from all actuators are tied together and tied to the negative lead of the
control signal.
Table-2 Power Wiring Color Code.
Part Number
L1
L2
MA4X-7XX3
MA4X-7XX3-502
Red
Black
MA4X-7XX0
MA4X-7XXX-502
Black
White
MA4X-7XX1
MA4X-7XXX-502
Brown
Light Blue
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
17
AM-673
M7A1-502
SBIE
Figure-4 Mounting Multiple Actuators.
Wiring Requirements
Control and Power Leads
applications.
Note: Class 2 control and power lead wiring must be routed separately from line voltage
wiring and any other non-class 2 circuits. Line voltage, auxiliary switch, and auxiliary switch
leads must be connected to a class 1 circuit.
Table-3 Power Wiring Data.
Maximum Wire Run in ft. (m) (5% Voltage Drop)
Actuator Voltage
Part Number
14 AWG
16 AWG
18 AWG
MA4X-7153
MA4X-7153-502
MA40-7043
24 Vac
22-30 Vdc
330 (101)
200 (61)
130 (40)
24 Vac
22-30 Vdc
1100 (335)
600 (183)
700 (213)
500 (152)
440 (134)
254 (77)
MA40-7043-501
MA4X-7073
24 Vac
22-30 Vdc
MA4X-7073-502
18
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
Auxiliary Switches
The MA40-704X-501 series actuators include one built-in SPDT auxiliary switch which can
be used for interfacing or signaling (e.g., for fan start-up). The switch is adjustable between
0° and 95° of rotation (0 to 1 scale).
The MA4X-715X-502 and MA4X-707X-502 series actuators include two built-in SPDT
auxiliary switches which can be used for interfacing or signaling (e.g., for fan start-up). The
switch position near the normal (spring return) position is fixed at 5°. The other is adjustable
between 25° and 85° of rotation.
Adjusting the Switching Point
Adjusting the switching point for MA40-704X-501
1. The actuator must be in its normal (spring return) position.
2. Use a flat screw driver to rotate the switch pointer until it is at the desired switch position
on the 0 to 1 scale.
Adjusting the switching point for MA4X-715X-502 or MA4X-707X-502
1. The actuator must be in its normal (spring return) position.
2. Insert a 1/8" allen wrench into the hex hole located in the center of the adjustable switch
pointer.
3. Rotate the wrench until the switch pointer is at the desired switch position in degrees,
from 25 to 85°.
Table-4 Auxiliary Switch Rating.
Part Number
MA40-7043-501
MA40-7040-501
MA40-7041-501
MA4X-707X-502
MA4X-715X-502
Voltage
Resistive Load
Inductive Load
24 Vac
6A
1.5A
250 Vac
250 Vac
6A
7A
1.5A
2.5A
Rotation Limitation
Rotation Limitation for MA40-704X Series
The Stop Block is used in conjunction with the tab on the universal clamp or the AM-709
position indicator. In order to function properly, the clamp or indicator must be mounted
correctly.
The Stop Block controls the rotational output of the MA40-704X and MF40-704X-501
actuators. It is used in applications where a damper has a designed rotation that is less than
90°, for example with a 45° or 60° rotating damper.
1. Determine the amount of damper rotation required. The actuator stop block provides
limited rotation from 40° to 95°.
2. Loosen the screw securing the stop block to the actuator.
Note: The actuator is shipped with the Stop Block mounted to the “L” side. If the damper
application requires the “R” side face the installer, simply remove the Stop Block and screw
and move it to the new location.
3. Slide the stop block into position, so that its edge lines up with the degree graduation
on the actuator face which corresponds with the required rotation. See Figure-5.
4. Secure the stop block in place.
5. Test the damper rotation by applying power. Re-adjust if necessary.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
19
1
1
.8
.8
.6
.6
.4
.4
.2
.2
L
R
0
0
1
.8
.6
.4
R
.2
0
Figure-5 Adjusting Stop Block for Limited Rotation.
Rotation Limitation for MA4X-715X and MA4X-707X Series
The AM-689 rotation limiter is used in conjunction with the tab on the universal clamp or the
AM-686 position indicator which comes with the AM-689. In order to function properly, the
clamp or indicator must be mounted correctly.
The AM-689 rotation limiter controls the rotational output of the MA4X-715X, MA4X-715X-
502, MA4X-707X, and MA4X-707X-502 actuators. It is used in applications where a damper
has a designed rotation that is less than 90°, for example with a 45° or 60° rotating damper.
1. Determine the amount of damper rotation required.
2. Locate the AM-689 rotation limiter on the actuator so that its edge lines up with the
degree graduation on the actuator face which corresponds with the required rotation.
3. Find the appropriate cross-hair location through the slot of the rotation limiter. This is
the mounting location for the retaining screw.
4. Pierce through the label material to allow easy fastening of the retaining screw.
5. Position the rotation limiter back to the desired position, making sure the locating “teeth”
on the rotation limiter are engaged into the locating holes on the actuator.
6. Fasten the rotation limiter to the actuator using the self-tapping screw provided.
7. Test the damper rotation by applying power. Re-adjust if necessary.
Screw secured at
these cross hairs.
Angle of rotation
is now set at 40.
90
80
90
80
70
70
60
50
40
30
60
50
40
30
90
80
70
60
50
40
30
Figure-6 Securing the AM-689 Rotation Limiter.
20
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
CHECKOUT
After the entire system has been installed and the actuator has been powered up, the
following check can be made for proper system operation. Check for correct operation of the
damper while actuator is being stroked.
1. Apply power to the actuator. Actuator and damper should be driven to their powered
position.
2. On the MA4X-7XXX-50X models, check for correct auxiliary switch operation.
3. Break power to the actuator. Actuator and damper should return to their normal, or
spring return position.
Table-5 Power Wiring Color Code.
Part Number
L1
L2
MA4X-7XX3
MA4X-7XX3-502
Red
Black
MA4X-7XX0
MA4X-7XXX-502
Black
White
MA4X-7XX1
MA4X-7XXX-502
Brown
Light Blue
THEORY OF
OPERATION
The actuators are mounted directly onto a damper shaft using a universal V-clamp. When
power is applied, the actuator rotates 95° to its powered position, at the same time tensing
the spring return safety mechanism. When power is removed, the spring returns the actuator
to its normal position. The actuators provide true mechanical spring return operation for
reliable, positive close-off on air tight dampers.
The MA4X-707X, MA4X-707X-502, MA4X-715X, and MA4X-715X-502 actuators are
equipped with a graduated position indicator showing -5° to 90°. The MA40-704X and
MA40-704X-501 are equipped with a graduated position indicator showing 0 to 1.
The MA40-704X-501 models are provided with 1 built in auxiliary switch. The SPDT switch
is provided for interfacing or signaling, for example, fan start-up. The switching function is
adjustable between 0° to 95° rotation (0 to 1 scale).
The MA4X-715X-502 and MA4X-707X-502 models are provided with 2 built in auxiliary
switches. The SPDT switches are provided for interfacing or signaling, for example, fan
start-up. The switching function is adjustable on one switch between 25° to 85° rotation and
the other switch is fixed at 5°.
The MA41-707X-XXX and MA41-715X-XXX actuators are equipped with a manual override
mechanism. This allows the actuator to be manually positioned at any point between -5o and
85o. This mechanism is accessible on both sides of the actuator and can be used to ensure
tight close-offs for valves and dampers. The manual override should not be used while a unit
is powered or on units that are mounted in tandem.
MAINTENANCE
FIELD REPAIR
Regular maintenance of the total system is recommended to assure sustained optimum
performance. The actuators are maintenance free.
None. Replace with a functional actuator.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
21
DIMENSIONAL DATA
3-1/2
(89)
2-25/64
(61)
4
(103)
6 Holes for
#10-24 Screws
1
2-7/64
(53)
10-1/2 (267)
7-1/2 (191)
Dimensions shown
are in inches (mm).
1
Note: These are not through holes. Use hardware supplied in
TAC approved AM kits.
Figure-7 MA4X-707X or MA4X-715X Series Mounting Dimensions.
22
© Copyright 2010 Schneider Electric All Rights Reserved.
F-26642-8
s
6-51/64 (172)
6-13/64 (157)
1
13/32 (10)
(25)
4
3-5/32 (80)
(103)
2
(50)
47/64 (19)
3-21/32 (93)
4-57/64 (125)
3 Holes for
#10-24 Screws
1
49/64 (19)
3-1/2 (62)
2-13/32
(61)
Dimensions shown
are in inches (mm).
1/4 (6.4)
1
Note: These are not through holes. Use hardware supplied in
TAC approved AM kits.
Figure-8 MA40-704X Series Mounting Dimensions.
F-26642-8
© Copyright 2010 Schneider Electric All Rights Reserved.
23
On October 1st, 2009, TAC became the Buildings business of its parent company Schneider Electric. This document reflects the visual identity of Schneider Electric,
however there remains references to TAC as a corporate brand in the body copy. As each document is updated, the body copy will be changed to reflect appropriate
corporate brand changes.
Copyright 2010, Schneider Electric
Schneider Electric
1354 Clifford Avenue
P.O. Box 2940
All brand names, trademarks and registered
trademarks are the property of their respective
owners. Information contained within this
document is subject to change without notice.
Loves Park, IL 61132-2940
F-26642-8
|