For Indoor Unit
INSTALLATION INSTRUCTIONS
COOL/DRY/HEAT Model
– Inverter Split System Air Conditioner –
This air conditioner uses the new refrigerant R410A.
Contents
Model Combinations
Page
Combine indoor and outdoor units only as listed
below.
IMPORTANT!
Please Read Before Starting .................................. 2
Indoor Unit
KMHS0772
KMHS0972
KMHS1272
KMHS1872
KMHS2472
Outdoor Unit
CMH1972
CMH2472
CMH3172
1. GENERAL .......................................................... 3
1-1. Tools Required for Installation (not supplied)
1-2. Accessories Supplied with Unit
1-3. Optional Copper Tubing Kit
1-4. Type of Copper Tube and Insulation Material
1-5. Additional Materials Required for Installation
2. INSTALLATION SITE SELECTION ................... 4
2-1. Indoor Unit
Power Source:
60 Hz, single-phase, 230 / 208 VAC
2-2. Embedding the Tubing and Wiring
3. HOW TO INSTALL THE INDOOR UNIT .............. 6
3-1. Remove the Rear Panel from the Unit
3-2. Make a Hole
Combinations of indoor and outdoor units
Connect indoor and outdoor units only in the combi-
nations listed in the catalog or installation manual.
3-3. Install the Rear Panel on the Wall
3-4. Remove the Grille to Install the Indoor Unit
3-5. Shape the Indoor Side Tubing
3-6. Wiring Instructions
CAUTION
3-7. Wiring Instructions for Inter-unit Connections
3-8. Mounting
3-9. Drain Hose
Connecting any other model may result in
operation failure and system damage.
4. HOWTOTEST RUNTHE AIR CONDITIONER .... 16
Be sure to read the yellow instruction sheet
attached to the outdoor unit for models using the
new refrigerant R410A.
5. REMOTE CONTROL UNIT INSTALLATION
POSITION ......................................................... 17
5-1. Mounting on a Wall
6. ADDRESS SWITCH.......................................... 18
6-1. Address Setting of the Remote
Control Unit
7. CONNECTING A HOME AUTOMATION
DEVICE.............................................................. 19
NOTE
The illustrations are based on the typical appearance of
a standard model. Consequently, the shape may differ
from that of the air conditioner that you are installing.
8. INSTALLATION CHECK SHEET ...................... 19
In Canada
SANYO FISHER COMPANY
SANYO Canada Inc.
A DIVISION OF SANYO NORTH AMERICA CORPORATION
21605 Plummer Street
300 Applewood Crescent, Concord
Ontario, L4K 5C7, Canada
Chatsworth, CA 91311 U.S.A.
85264189998000 © SANYO 2006
1. General
6. Sabre saw or key hole saw
7. Hacksaw
8. Core bits
9. Hammer
10. Drill
This booklet briefly outlines where and how to install the
air conditioning system. Please read over the entire set
of instructions for the indoor and outdoor units and make
sure all accessory parts listed are with the system before
beginning.
11. Tube cutter
1-1. Tools Required for Installation (not supplied)
1. Standard screwdriver
12. Tube flaring tool
13. Torque wrench
14. Adjustable wrench
15. Reamer (for deburring)
2. Phillips head screwdriver
3. Knife or wire stripper
4. Tape measure
5. Carpenter’s level
1-2. Accessories Supplied with Unit
Table 1
Parts
Figure
Qʼty
Parts
Figure
Qʼty
Parts
Clamp
Figure
Qʼty
Truss-head
Remote
Tapping screw
Phillips
1
10
1
control unit
5/32
/8" (4 16 mm)
5
Remote control
unit holder
1
2
8
1
2
Rawl plug
Air clean filter
Packed in the indoor unit.
Drain hose
adapter
AAA alkaline
battery
1-3. Optional Copper Tubing Kit
Copper tubing for connecting the outdoor unit to the
indoor unit is available in kits which contain the narrow
and wide tubing, fittings and insulation. Consult your
nearest sales outlet or A/C workshop.
2. Foamed polyethylene insulation for the specified
copper tubes as required to precise length of tubing.
Wall thickness of the insulation should be not less
than 5/16" (8 mm).
3. Use insulated copper wire for field wiring. Wire size
varies with the total length of wiring. Refer to 3-6.
Wiring Instructions for details.
1-4. Type of Copper Tube and Insulation Material
If you wish to purchase these materials separately from
a local source, you will need:
1. Deoxidized annealed copper tube for refrigerant tub-
ing as detailed in Table 2.
Check local electrical codes
and regulations before
obtaining wire. Also, check
any specified instructions or
limitations.
CAUTION
Cut each tube to the appropriate lengths 1' to 1'4"
(30 cm to 40 cm) to dampen vibration between units.
Table 2
Narrow Tube
Model
Wide Tube
Outer Dia.
Thickness
Outer Dia.
Thickness
KMHS0772
KMHS0972
KMHS1272
KMHS1872
KMHS2472
1/4" (6.35 mm)
1/4" (6.35 mm)
1/4" (6.35 mm)
1/4" (6.35 mm)
1/4" (6.35 mm)
0.0314" (0.8 mm)
0.0314" (0.8 mm)
0.0314" (0.8 mm)
3/8" (9.52 mm)
3/8" (9.52 mm)
3/8" (9.52 mm)
0.0314" (0.8 mm)
0.0314" (0.8 mm)
0.0314" (0.8 mm)
0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)
0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)
3
1-5. Additional Materials Required for Installation
1. Refrigeration (armored) tape
2. Insulated staples or clamps for connecting wire
(See local codes)
3. Putty
4. Refrigeration lubricant
5. Clamps or saddles to secure refrigerant tubing
Indoor unit
2. Installation Site Selection
2-1. Indoor Unit
To prevent abnormal heat generation
WARNING
and the possibility of fire, do not
place obstacles, enclosures and
grilles in front of or surrounding the
air conditioner in a way that may
block air flow.
Drain hose
Outside drainage
AVOID:
G direct sunlight.
Fig. 1
G nearby heat sources that may affect performance of the
unit.
6" (15 cm)
min.
2" (5 cm)
min.
2" (5 cm)
min.
G areas where leakage of flammable gas may be expected.
G placing or allowing any obstructions near the A/C inlet or
outlet.
Front View
G installing in rooms that contain instant-on (rapid-start)
fluorescent lamps. (These may prevent the A/C from
receiving signals.)
Fig. 2
Tubing length (L1)
INDOOR
UNIT (1)
G places where large amounts of oil mist exist.
INDOOR
G installing in locations where there are devices that
UNIT (2)
generate high-frequency emissions.
Elevation
L2
L3
difference (H1) OUTDOOR
UNIT
H2
H3
DO:
G select an appropriate position from which every corner of
INDOOR
UNIT (3)
H4
INDOOR
L4
UNIT (4)
the room can be uniformly cooled. (High on a wall is best.)
Fig. 3a
G select a location that will hold the weight of the unit.
G select a location where tubing and drain hose have the
shortest run to the outside. (Fig. 1)
CAUTION
G allow room for operation and maintenance as well as
Indoor unit
Wall
unrestricted air flow around the unit. (Fig. 2)
For stable operation of the
air conditioner, do not
install wall-mounted type
indoor units less than 5'
(1.5 m) from floor level.
G install the unit within the maximum elevation difference
(H1, H2, H3, H4) above or below the outdoor unit and
within a total tubing length (L1+L2+L3, L1+L2+L3+L4)
from the outdoor unit as detailed in Table 3 and Fig. 3a.
Minimum height
from floor level
5' (1.5 m)
Floor level
Fig. 3b
4
G Install the indoor unit more than 3.3' (1 m) away from any
antenna or power lines or connecting wires used for tele-
vision, radio, telephone, security system, or intercom.
Electrical noise from any of these sources may affect
operation.
G install in a sturdy manner to avoid increased operating
noise.
Table 3
Max.
Allowable
Tubing Length
per unit
Max. Allowable Total
Tubing Length
at shipment
Limit of
Total Tubing Length
(L1+L2+L3) or
(L1+L2+L3+L4)
(ft.)
Limit of Elevation
Difference
(H1, H2, H3, H4)
(ft.)
Required Amount
of Additional
Refrigerant
Model
(L1+L2+L3) or
(L1+L2+L3+L4)
(ft.)
(oz./ft.)*
(ft.)
CMH1972
CMH2472
CMH3172
82
82
150 (L1+L2+L3)
150 (L1+L2+L3)
50
50
50
—
150 (L1+L2+L3+L4)
150 (L1+L2+L3+L4)
200 (L1+L2+L3+L4)
230 (L1+L2+L3+L4)
0.22
0.22
100
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.
No additional charge of compressor oil is necessary.
2-2. Embedding the Tubing and Wiring
G Before beginning embedding installation work, consult
fully with agencies or offices related to the building’s
foundation, construction, electricity, and water.
G Wait to make connections to the embedded portion.
Each connection step is described later in this
manual.
G Securely cover the end of the embedded tubing to
prevent intrusion of dirt or moisture.
G If an embedded tube is to be left for a long time, fill
the tube with nitrogen and seal both ends securely.
If a tube is left open for an extended time, moisture in
the air inside the tubing may condense into water
droplets, and lead to water contamination of the refrig-
erant circuit.
G In order to prevent insulation breakdown and ground
faults, do not allow wiring ends to come in contact with
rainwater, or be subjected to condensation or dew.
G Apply sufficient thermal insulation to the refrigerant
tubing and drain pipes.
5
3. How to Install the Indoor Unit
3-1. Remove the Rear Panel from the Unit
(1) Remove and discard the set screw on the rear
panel. (Fig. 6)
(2) Press the 2 L marks on the frame cover and disen-
gage the stationary tabs from the frame. (Fig. 7)
Set screw only for transportation
(3) Remove the rear panel.
Fig. 6
NOTE
Tubing can be extended in 5 directions as shown in Fig.
8. Select the direction you need providing the shortest
run to the outside unit.
Rear panel
G When left tubing is to be done, switch the drain hose
and drain cap. (For details, refer to “Switching drain
hose and drain cap” on page 14.)
3-2. Make a Hole
(1) Place the rear panel from the indoor unit on the wall
at the location selected. Make sure the panel is hori-
zontal, using a carpenter’s level or tape measure to
measure down from the ceiling. Wait until after cut-
ting the hole before attaching the rear panel to the
wall.
marks
Fig. 7
Right-rear
tubing
Left
(recommended)
tubing
(2) Determine which side of the unit you should make
the hole for tubing and wiring. (Fig. 9a or 9b)
Left-rear
tubing
Right tubing
NOTE
Downward tubing
In the case of left-rear tubing, use the measurement
points from the edge of the rear panel for precise place-
ment of the hose outlet. (Fig. 9a or 9b)
Fig. 8
(KMHS0772, KMHS0972, KMHS1272)
(3) Before making the hole, check carefully that no
studs or pipes are directly run behind the spot to be
cut.
2-3/4" (70 mm)
Also avoid areas where elec-
trical wiring or conduits are
located.
CAUTION
The above precautions are also applicable if tubing
goes through the wall in any other location.
Fig. 9a
(KMHS1872, KMHS2472)
2-3/8" (60 mm)
Fig. 9b
6
(4) Using a sabre saw, key hole saw or hole-cutting drill
attachment, cut a hole in the wall. See Table 4 and
Fig. 10.
NOTE
Hole should be made at a slight downward slant to the
outdoor side.
Table 4
Indoor
side
Outdoor
side
Hole Dia.
KMHS0772/0972/1272
KMHS1872/2472
2-9/16" (65 mm)
3-5/32" (80 mm)
(5) Measure the thickness of the wall from the inside
edge to the outside edge and cut PVC pipe at a
slight angle 1/4" (6 mm) shorter than the thickness of
the wall. (Fig. 11)
Fig. 10
PVC pipe (Locally purchased)
(6) Place the plastic cover over the end of the pipe (for
indoor side only) and insert the pipe in the wall.
(Fig. 12)
Cut at slight angle
3-3. Install the Rear Panel on the Wall
Fig. 11
Be sure to confirm that the wall is strong enough to sus-
pend the unit.
INSIDE
OUTSIDE
PVC pipe
Wall
See either Item a) or b) below depending on the wall type.
Plastic cover
(Locally purchased)
a) If Wooden Wall
Slight
angle
(1) Attach the rear panel to the wall with the 8 screws
provided. (Fig. 13a or 13b)
Fig. 12
If you are not able to line up the holes in the rear
panel with the beam locations marked on the wall,
use rawl plugs or toggle bolts to go through the
holes on the panel or drill 3/16" (5 mm) dia. holes in
the panel over the stud locations and then mount the
rear panel.
(KMHS0772, KMHS0972, KMHS1272)
(2) Double check with a carpenter’s level or tape mea-
sure that the panel is level. This is important to install
the unit properly. (Fig. 14)
Fig. 13a
(3) Make sure the panel is flush against the wall. Any
space between the wall and unit will cause noise
and vibration.
(KMHS1872, KMHS2472)
b) If Block, Brick, Concrete or Similar Type Wall
Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawl
plugs for appropriate mounting screws. (Fig. 15)
Fig. 13b
Fig. 14
3/16"
(4.8 mm) dia. hole
Rawl plug
Fig. 15
7
Grille
Air intake grille
3-4. Remove the Grille to Install the Indoor Unit
3-4-1. Indoor unit types
(KMHS0772, KMHS0972, KMHS1272)
Basically, these models can be installed and wired without
removing the grille. If access to any internal part is needed,
follow the steps as given below.
Fig. 16a
Be sure to wear work gloves
CAUTION
during installation to avoid being
cut by the sharp aluminum fins
of the heat exchanger.
How to remove the grille
(1) Grasp both ends of the air intake grille, and remove it by
opening towards the front and pulling towards you. (Fig.
16a)
Screw cover
Fig. 16b
Cover
(2) Remove the 2 screws. (Fig. 16b)
Thermistor
(3) Remove the screw on the right side cover plate and
open the cover. (Fig. 17a)
(4) Take out the thermistor from the grille. (Fig. 17b)
(5) Pull the lower part of the grille toward you to remove.
(Fig. 18a)
Thermistor
Fig. 17b
Fig. 17a
(6) Use a standard screwdriver to push on the tabs to
remove the grille.
Tab
*
Grille
Frame
How to replace the grille
*
(1) Reinstall the grille into the lower part while aligning
its tabs on the upper part. (Fig. 18b) Insert the tabs
in the slots and push the lower part of the grille back
into position.
Tab
(2) Make sure that the grille and frame are firmly fitted
together by engaging the tabs.
Fig. 18a
(3) Attach the thermistor on the grille. (Fig. 17a)
*
(4) Close the cover and replace the screw. (Fig. 17a)
*
(5) Affix the grille with the 2 previously removed screws.
(Fig. 16b)
(6) Install the air intake grille.
(a) Allow the edge of the air intake grille to slide into
the top of the indoor unit, and then insert it all
the way inside. (Fig. 19a)
Fig. 18b
(b) Press the bottom right and left corners of the air
intake grille to attach it to the indoor unit. (Fig. 19b)
Groove
NOTE
Pin
Attach so that the round pins at the top right and left corners
of the air intake grille are inserted into the grooves at the top
right and left of the
indoor unit.
Fig. 19b
Fig. 19a
8
Grille
Air intake grille
3-4-2. Indoor unit types
(KMHS1872, KMHS2472)
Basically, these models can be installed and wired with-
out removing the grille. If access to any internal part is
needed, follow the steps as given below.
How to remove the grille
Fig. 16a-1
(1) Grasp both ends of the air intake grille, and remove
it by opening towards the front and pulling towards
you. (Fig. 16a-1)
(2) Remove the 3 screws. (Fig. 16b-1)
(3) Remove the screw on the right side cover plate and
open the cover. (Fig. 17a-1)
Fig. 16b-1
(4) Take out the thermistor from the grille. (Fig. 17b-1)
Cover
(5) Press the 3 tabs at the top of the grille and the 3
tabs on the front face to separate the grille from the
frame. (Fig. 18a-1)
Thermistor
Thermistor
(6) Pull the grill toward you to remove it.
How to replace the grille
Fig. 17b-1
Fig. 17a-1
(1) When installing the grille, place the bottom of the
grille into the frame first. (Fig. 18b-1)
Tab
Then insert the tabs on the top of the grille and on
the front face into the frame.
(2) Make sure that the grille and frame are firmly fitted
together by engaging the tabs.
(3) Attach the thermistor on the grille. (Fig. 17a-1)
(4) Close the cover and replace the screw. (Fig. 17a-1)
Tab
(5) Affix the grille with the 3 previously removed screws.
(Fig. 16b-1)
Fig. 18a-1
(6) Install the air intake grille.
(a) Allow the edge of the air intake grille to slide into
the top of the indoor unit, and then insert it all the
way inside. (Fig. 19a-1)
(b) Press the bottom right and left corners and center
of the air intake grille to attach it to the indoor
unit. (Fig. 19b-1)
Fig. 18b-1
NOTE
Groove
Attach so that the round pins at the top right and left cor-
ners of the air intake grille are inserted into the grooves
at the top right and left of the indoor unit.
Pin
Fig. 19a-1
Fig. 19b-1
9
3-5. Shape the Indoor Side Tubing
(1) Arrangement of tubing by directions
a) Right or left tubing
Frame
Cut out the corner of the right/left frame with a
hacksaw or the like. (Figs. 20 and 21)
Left tubing
outlet
b) Right-rear or left-rear tubing
In this case, the corner of the frame need not be
cut.
(2) To mount the indoor unit on the rear panel:
Fig. 20
Hang the 2 mounting slots of the unit on the
upper tabs of the rear panel. (Fig. 22)
Frame
3-6. Wiring Instructions
General precautions on wiring
Right tubing
outlet
(1) Before wiring, confirm the rated voltage of the unit as
shown on its nameplate, then carry out the wiring
closely following the wiring diagram.
(2) Provide a power outlet to be used exclusively for
each unit, with a power supply disconnect and cir-
cuit breaker for overcurrent protection provided in
the exclusive line.
Fig. 21
(3) To prevent possible hazard due to insulation failure,
the unit must be grounded.
(4) Each wiring connection must be done tightly and in
accordance with the wiring system diagram. Wrong
wiring may cause the unit to misoperate or become
damaged.
Fig. 22
(5) Do not allow wiring to touch the refrigerant tubing,
compressor, or any moving parts of the fan.
(6) Unauthorized changes in the internal wiring can be
very dangerous. The manufacturer will accept no
responsibility for any damage or misoperation that
occurs as a result of such unauthorized changes.
10
3-7. Wiring Instructions for Inter-unit Connections
Rear
panel
Wall
(1) Insert the inter-unit wiring (according to local codes)
into the through-the-wall PVC pipe. Run the wiring
toward the indoor side allowing approx. 10" (25 cm)
to extend from the wall face. (Fig. 24)
Plastic
cover
(2) Grasp both ends of the air intake grille, and remove
it by opening towards the front and pulling towards
you.
Wiring
10"
(25 cm)
(3) Remove the screw on the right side cover plate and
open the cover. (Fig. 25)
Fig. 24
Fig. 25
Fig. 26a
(4) Route the inter-unit wiring from the back of the
indoor unit and pull it toward the front for connec-
tion. (Figs. 26a and 26b)
Cover
(5) Connect the inter-unit wiring to the corresponding
terminals on the terminal plate (Figs. 26a and 26b)
while referring to the wiring diagram.
(6) Be sure to secure the wiring with the provided
clamp.
NOTE
When closing the air intake grille, press the bottom right
and left corners and center. (Fig. 27)
Please refer to “How to replace the grille” on page 8 or 9
for installing the air intake grille.
Terminal
plate
Fig. 27
Inter-unit
wiring
Earth
plate
Lock nut
Top of conduit
connector
Fig. 26b
11
Loose wiring may cause the
terminal to overheat or result
in unit malfunction. A fire
hazard may also exist.There-
fore, be sure all wiring is
tightly connected.
WARNING
When connecting each power wire to the corresponding
terminal, follow the instructions “How to connect wiring
to the terminal” and fasten the wire securely tight with
the fixing screw of the terminal plate.
9/32"
(7 mm)
(ACTUAL
STRIP
SIZE
SIZE)
How to connect wiring to the terminal
a) For Indoor Unit
Fig. 28
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the wire about 9/32" (7 mm).
See the label (Fig. 28) near the terminal plate.
Solid wire
Loop
(2) Using a screwdriver, loosen the terminal screw on
the terminal plate.
(3) Insert the wire and tighten the terminal screw com-
pletely using a screwdriver.
Insulation
b) For Outdoor Unit
Fig. 29
I For solid core wiring (or F-cable)
Stranded wire
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the solid wire about 15/16" (25
mm). (Fig. 29)
Ring
connector
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
(3) Using the pliers, bend the solid wire to form a loop
suitable for the terminal screw.
Fig. 30
(4) Shape the loop wire properly, place it on the termi-
nal plate and fix it securely with the removed termi-
nal screw using a screwdriver.
Twist wire ends
I For stranded wiring
(1) Cut the wire end with a cutting pliers, then strip the
insulation to expose the stranded wiring about 3/8"
(10 mm) and tightly twist the wire ends. (Figs. 30
and 31)
Fig. 31
(2) Using a screwdriver, remove the terminal screw(s)
on the terminal plate.
Special
washer
Screw
(3) Using a ring connector fastener or pliers, securely
clamp each stripped wire end with a ring connector.
(Fig. 30)
Screw and
Ring connector
Terminal plate
special washer
Wire
Ring
connector
(4) Place the ring connector wire, and replace and
tighten the removed terminal screw using a screw-
driver. (Fig. 32)
Wire
Fig. 32
12
3-8. Mounting
(1) To install the indoor unit, mount the indoor unit onto
the 2 tabs on the upper part of the rear plate.
(2) Hold down the air discharge outlet and press the
lower part of the indoor unit until it clicks to securely
fasten to the 2 tabs on the lower part of the rear
plate. (Fig. 33)
Push
NOTE
For tubing, choose either the right or left tubing direction
and follow the steps below. This work can be made easi-
er by placing padding material (such as styrofoam) at the
rear right side of the indoor unit. (Fig. 34)
Fig. 33
I Right-side tubing
(1) Shape the refrigerant tubing so that it can easily go
into the wall hole. (Fig. 35)
(2) Push the wiring, refrigerant tubing, and drain hose
through the hole in the wall. Adjust the indoor unit so
it is securely seated on the rear panel. (Fig. 36)
Padding material
(3) Carefully bend the tubing (if necessary) to run along
the wall in the direction of the outdoor unit and then
tape as far as the fittings. (See Caution on page 15
in the outdoor unit installation manual.) The drain
hose should come straight down the wall to a point
where water runoff won’t stain the wall.
Fig. 34
Rear panel
Cover
Refrigerant
tubing
(4) Connect the refrigerant tubing to the outdoor unit.
(After performing a leak test on the connecting part,
insulate it with the tubing insulation. (Fig. 37a))
Also, refer to Section 3-6. Tubing connections in the
outdoor unit installation manual.
Inter-unit
wiring
Drain hose
(5) Assemble the refrigerant tubing, drain hose, and
conduit (including inter-unit wiring) as shown in
Fig. 37b.
Fig. 35
Refrigerant tubing
Insulation
Fig. 37a
Conduit
Drain hose
Fig. 36
Inter-unit wiring
Fig. 37b
13
I Left-side tubing
Rear panel
(1) Lead the tubing and drain hose through the wall,
allowing sufficient length for connection. Then bend
the tubing using a tube bender to make the attach-
ment. (Fig. 38)
Hole in wall
Wide tube
Narrow tube
Bent part
(2) Switch the drain hose and drain cap.
Fig. 38
Switching drain hose and drain cap
(a) Locate the drain hose and the drain cap. (Fig.
39)
(b) Remove the screws fastening the drain hose on
the right side, and pull out the drain hose to
remove it. (Fig. 39)
Drain cap
(c) Apply moderate force to pull off the drain cap
on the left side. (If you cannot pull it off by hand,
use a long-nose pliers.)
Drain hose
Fig. 39
(d) Reattach the drain hose to the left side and the
drain cap to the right side. (Fig. 40a)
Drain hose
Drain hose
Slide the drain hose fully onto the drain pan outlet
until the drain hose edge is pushed into the insula-
tion. Check that the screw holes in the drain bracket
and the drain pan outlet are aligned and securely in
contact, then fasten them with the screw. (After
attaching the drain hose, check that it is attached
securely.) (Fig. 40c)
Clamp
Drain cap
Drain cap
Use a Phillips screwdriver to push the drain cap in
firmly. (If it is difficult to push in, wet the cap with
water first.)
Fig. 40a
Screw hole
(3) Install the indoor unit on the rear panel.
(4) Connect the tubing and wiring led inside from out-
doors.
Drain pan outlet
(5) After completing a leak test, bundle the tubing
together with armoring tape and store it inside the
tubing storage area at the back of the indoor unit
and hold it with clamps. (Figs. 40a and 41)
Insulation
Drain bracket
Drain bracket
Screw
Drain hose
Drain hose
Fig. 40c
Fig. 40b
Refrigerant tubing
Inter-unit wiring
Conduit
Fig. 41
14
To unmount indoor unit
Press the 2 L marks on the lower part of the indoor unit
and unlatch the tabs. Then lift the indoor unit and
unmount. (Fig. 42)
3-9. Drain Hose
a) The drain hose should be slanted downward to the
outdoors. (Fig. 43)
b) Never form a trap in the course of the hose.
c) If the drain hose will run in the room, insulate the
hose with insulation* so that chilled condensation
will not damage furniture or floors. (Fig. 44)
Push
* Foamed polyethylene or its equivalent is recom-
Fig. 42
mended.
Do not supply power to the
WARNING
unit or operate it until all
tubing and wiring to the out-
side unit are completed.
Slant
Indoor
unit
Drain
hose
Risk of Electric Shock
Fig. 43
Condensation
Insulation material
(Locally purchased)
must be used.
Fig. 44
15
4. How to Test Run the Air Conditioner
After turning on power to the air conditioner, use the remote
controller and follow the steps below to conduct the test run.
(1) Set the remote controller in Test Run mode.
(Fig. 59a)
a) Press and hold the ION button.
b) Then press and hold the 1HR TIMER button.
c) At the same time, press the ACL (reset) button once.
Use a pointed object such as the tip of a pen to press
the ACL button.
ON/OFF
operation
button
ION
button
• After a few seconds, “ ” appears and “oP-1” blinks in
the remote controller display area.
(Fig. 59b)
1HR.
TIMER
button
d) Release the 1HR TIMER button.
e) Release the ION button.
(2) Start Cooling mode test run by pressing the ON/OFF
operation button of the remote controller. (Fig. 59a)
• This starts the fan producing uncooled forced air with
the 4 indicator lamps (OPERATION lamp, TIMER
lamp, QUIET lamp, and ION lamp) on the main unit
blinking. (Fig. 59c)
• After 3 minutes, the system shifts into cooling opera-
tion, and cool air will start to be felt. Cool mode test
run is unaffected by the room temperature.
ACL
A
(Reset)
button
Fig. 59a
(3) Press the ON/OFF operation button of the remote con-
troller again to stop the test run. (Fig. 59a)
(4) Finally press the ACL (reset) button of the remote con-
troller to release it from Test Run mode to return to nor-
mal mode. (Fig. 59a)
• “ ” and “oP-1” will disappear from the remote con-
troller display area.
IMPORTANT
After the test run is completed, be sure to press the ACL
(reset) button to return to normal mode. The air conditioner
will not operate correctly if this is not done.
Fig. 59b
OPERATION lamp
TIMER lamp
QUIET lamp
ION lamp
Fig. 59c
16
5. Remote Control Unit Installation Position
The remote control unit can be operated from either a
non-fixed position or a wall-mounted position.
To ensure that the air conditioner operates correctly, do
not install the remote control unit in the following places:
G In direct sunlight
G Behind a curtain or other place where it is covered
G More than 26' (8 m) away from the air conditioner
G In the path of the air conditioner’s airstream
G Where it may become extremely hot or cold
G Where it may be subject to electrical or magnetic
interference
G Where there is an obstacle between the remote con-
trol unit and the air conditioner (since a check signal
is sent from the remote control unit every 5 minutes)
5-1. Mounting on a Wall
Before mounting the remote control unit, press the
ON/OFF operation button at the mounting location to
make sure that the air conditioner operates from that
location. The indoor unit should make a beeping sound
to indicate that it has received the signal.
Rear side
Remote control unit mount
Press
Mounting screws
5/32 × 5/8" (4 × 16 mm)
(Included)
Hole
Set in
place
To prevent loss of the remote control
unit, you can connect the remote
control unit to the mount by passing
a string through the remote control
unit and attachment hole.
To take out the remote control unit, pull it forward.
Fig. 61
17
6. Address Switch
Tab
6-1. Address Setting of the Remote Control Unit
The address can be set in order to prevent interference
between remote controllers when two Sanyo indoor units
are installed near each other. The address is normally
set to “A.” To set a different address, it is necessary to
change the address on the second remote controller.
Fig. 62
NOTE
Once changed, you cannot restore the original address
setting of the air conditioner.
(1) Switch on the power source.
(2) Break the address-setting tab marked “A” on the
second remote controller to change the address
(Fig. 62). When the tab is removed, the address is
automatically set to B (Fig. 63).
ACL button
(3) Press and hold the remote controller ION button and
1 HR TIMER button. At the same time, press the
ACL(reset) button. Use a thin object such as the tip
of a pen to press the ACL button. When this has
been done, “oP-1” (test run) appears, blinking, in the
remote controller clock display area.
Fig. 63
(4) Each time the 1 HR TIMER button is pressed, the
display changes as shown below. Press this button
2 times to change the display to “oP-7” (address
setting). (Fig. 64)
Test run mode
Selfdiagnostic mode
Adress setting mode
ON/OFF
operation
button
ION
button
(5) “oP-7” has now been selected for address setting.
1HR.
(6) Press the ON/OFF operation button on the remote
controller. (Fig. 64) Check that the “beep”signal-
received sound is heard from the second indoor unit
(approximately 5 times). The sound you hear is the
signal that the remote controller address has been
changed.
TIMER
button
(7) Finally press the remote controller ACL (reset) but-
ton to cancel the blinking “oP-7” display.
(Fig. 64)
Changing of the second remote controller address is
now completed.
ACL
A
(Reset)
button
Fig. 64
18
7. Connecting a Home Automation device
The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will
be used, connect it to this terminal.
8. Installation Check Sheet
The strength of the installation location is sufficient to support the A/C weight.
The indoor and outdoor units are installed level and vertically.
The power and voltage are as specified.
Inter-unit cables are securely inserted into the
terminal block.
Inter-unit cables are securely fixed.
The power cord and inter-unit cables are not connected anywhere along their
paths.
The ground wire is securely connected.
Thermal insulation has been applied to the tubing connections.
Drain connections are secure and water drains properly.
Putty has been used to close the hole in the wall.
Remote controller signals are being positively received.
19
|