Sanyo C2432a User Manual

SANYO AIR CONDITIONING PRODUCTS  
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS  
SPECIFICATIONS - SECTION 15700  
Covers Sanyo System Models > 24KS32A, 24KLS32A  
(See plans for specified model(s) & details)  
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - WALL MOUNT TYPE  
1) GENERAL SPECIFICATIONS  
Furnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s), consisting of  
an indoor, high wall mounted evaporator/blower section & matching outdoor condensing section.  
System(s) shall bear the ARI label showing that the system(s) is ARI 210 or 240 & 270 Certified.  
Systems shall be listed by CSA International and bear the C-CSA US label. Matching systems  
shall meet or exceed the minimum, Federally mandated Seasonal Energy Efficiency Rating  
(SEER) of 10 as certified by the ARI testing programs. System(s) indoor & outdoor units will  
operate at sound levels equal to or below specified system(s) (see plans). Installation & Owners  
Manuals shall be provided with each system.  
Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper  
tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on  
both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.  
System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-  
charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor  
units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),  
shall be sized, installed & grounded by the installer in conformance with the National Electrical  
Code (N.E.C.), local codes, as well as, manufacturer’s instructions.  
System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote  
controller with LCD display that provides access to all system functions, and transmits programs  
to the indoor microprocessor every 5 minutes. Infrared remote controller shall be capable of  
operating system mounted up to 26’ from the indoor section, according to manufacturer’s  
recommendations & instructions. System(s) shall have the capability of continuous operation in  
the case of a lost or damaged remote controller, utilizing a factory installed, integral manual  
switch in conjunction with the system microprocessor.  
1A) System Infrared Remote Controller Functions will include: system mode selection,  
programmable temperature control, 24hour programmable timer, one (1) hour off timer,  
automatic three (3) speed indoor fan speed control, constant fan speed selection, night setback  
mode, automatic sweep/flap control, multiple system control using a single controller.  
1B) System Features will include: Sanyo high efficiency, rotary compressor, cap tube refrigerant  
control, indoor coil freeze protection, built-in auto restart after power failure, short cycle time  
-1-  
control circuit fuse & microprocessor, factory wired & mounted, that receives & processes all  
commands & transmissions from the system Infrared Remote Controller. Indoor unit(s) shall also  
contain an Operation Switch with visible lamps for operation, standby & timer functions, as well  
as, a system test switch & a manual ON/OFF switch. Unit(s) shall contain a room sensor  
thermistor, a coil temperature safety thermistor to prevent freeze-up in the A/C mode, a factory  
installed condensate drain pan, drain hose & fitting, and refrigeration line connections with flare  
nuts. Unit(s) shall contain knockouts on both sides of the casing that allow refrigerant lines to be  
brought to the unit from multiple directions. A motorized louver/flap, controlled by the infrared  
remote controller, shall provide automatic, full oscillating supply airflow, as well as being capable  
of being placed in a set, stationary position. Unit(s) shall also contain adjustable, horizontal air  
louvers to provide user defined, directional airflow. Unit(s) shall be provided with anti-mold, poly  
type washable air filters that can be easily removed without removing indoor unit casing. Indoor  
unit(s) shall be powered by voltage from the matching outdoor unit(s).  
4) AVAILABLE SANYO ACCESSORIES – All Wall Mount Models  
Insulated Copper Line Sets, Condensate Pumps,  
Optional wired remote(RCS-KS2432AWD)  
Outdoor Section Mounting Brackett, and Odor Control Filters.  
-3-  

Lexmark All In One Printer 31n User Manual
Philips Se155 User Manual
Ricoh Aficio Dsm616 User Manual
Sanyo N 700aacl User Manual
Smart Ups Apcrbc133j User Manual
Sterling Automobile Parts Sfc A 50 User Manual
Toshiba Air Conditioner Rav Sm454mut E User Manual
Toshiba E Studio 352 User Manual
Xerox Workcentre Pro C2128 User Manual
York Predator 150 User Manual