Sanyo 12rs11 User Manual

SANYO AIR CONDITIONING PRODUCTS  
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS & HEAT PUMPS  
SPECIFICATIONS - SECTION 15700  
Covers Sanyo System Models > 12RS11, 12RLS11 (See plans for specified models & details)  
DUCTLESS SPLIT SYSTEM AIR CONDITIONERS - RECESSED CEILING MOUNT  
1) GENERAL SPECIFICATIONS  
Furnish & install a Sanyo manufactured Ductless, Split System Air Conditioner(s) consisting of an  
indoor recessed ceiling mounted evaporator/blower section & matching outdoor condensing  
section. System(s) shall bear the ARI label showing that the system(s) is ARI 210 or 240 & 270  
Certified. Systems shall be listed by ETL Testing Laboratories and bear the ETL label. Matching  
systems shall meet or exceed the minimum, Federally mandated Seasonal Energy Efficiency  
Rating (SEER) of 10, as certified by the ARI testing programs. System(s) indoor & outdoor units  
will operate at sound levels equal to or below specified system(s) (see plans). Installation &  
Owners Manuals shall be provided with each system.  
Matching indoor & outdoor sections shall be connected by deoxidized, annealed refrigerant copper  
tubing, type “L”, cleaned & capped. All systems shall have flared refrigeration connections on  
both indoor & outdoor sections. Size & insulate tubing according to manufacturer’s specifications.  
System(s) indoor & outdoor sections shall be completely factory assembled & wired, with a pre-  
charge of refrigerant. A single power source shall provide voltage to both the outdoor & indoor  
units. Electrical wire & connections to outdoor section, and between indoor & outdoor section(s),  
shall be sized, installed & grounded by the installer in conformance with the National Electrical  
Code (N.E.C.), local codes, as well as, manufacturer’s instructions.  
System(s) shall be equipped with a microprocessor control system, utilizing an infrared remote  
controller with LCD display that provides access to all system functions, and transmits room  
conditions & programs to the indoor microprocessor every 3 minutes. Infrared remote controller  
shall be capable of operating system mounted up to 26’ from the indoor section, according to  
manufacturer’s recommendations & instructions. System(s) shall have the capability of continuous  
operation in the case of a lost or damaged remote controller, utilizing a factory installed, integral  
manual switch in conjunction with the system microprocessor.  
System Infrared Remote Controller Functions will include: system mode selection,  
programmable temperature control, 24 hour programmable timer, automatic three (3) speed indoor  
fan speed control, constant fan speed selection, night setback mode, user selectable room  
temperature sensor located on either infrared remote controller or indoor unit, multiple system  
control using a single controller.  
System Features will include: Sanyo high efficiency, rotary compressor, with suction line  
accumulator, a strainer, cap tube refrigerant control, indoor coil freeze protection, built-in auto  
restart after power failure, short cycle time delay, low ambient cooling operation to zero degrees  
-1-  
wired, that receives & processes all commands & transmissions from the system Infrared Remote  
Controller. Indoor unit(s) shall also contain an Operation Switch with visible lamps for operation,  
standby & timer functions, as well as, a system test switch & a manual ON/OFF switch. Unit(s)  
shall contain an air sensor thermistor, a coil freeze safety thermistor to prevent freeze-up, a factory  
installed light-duty condensate drain pump, drain pan, hose & fitting, and refrigeration line  
connections with flare nuts.  
Indoor section shall be provided with factory assembled supply & return air grille with a  
motorized louver/flap on the supply air opening. The motorized louver/flap, controlled by the  
infrared remote controller, shall provide automatic, full oscillating supply airflow, as well as being  
capable of being placed in a set, stationary position. Unit(s) shall also contain adjustable,  
horizontal air louvers to provide user defined, directional airflow. Indoor unit(s) will be furnished  
with an in-ceiling plenum, which surrounds the evaporator coil section. Unit(s) shall be capable of  
utilizing fresh, outside air up to a maximum of 10% of the rated CFM of the system. Unit(s) shall  
be furnished with long life, anti-mold, poly type washable air filters that can be easily removed  
without removing indoor unit casing. Indoor unit(s) shall be powered by voltage from the  
matching outdoor unit(s).  
4) AVAILABLE SANYO ACCESSORIES – Recessed Ceiling Mount Models  
Insulated Copper Line Sets, Remote Controller Locking Bracket, Condensate Pumps, Outdoor  
Section Wall Mounting Bracket.  
-3-  

Murphy Diesel Fuel Check Valves Prv70 User Manual
Oki Office 87 User Manual
Panasonic Kx F2710nz User Manual
Samsung Sh24zv User Manual
Sanyo C2672r User Manual
Sanyo Nc Mdu01 User Manual
Tripp Lite Apsx750 User Manual
Xerox 50 User Manual
Zebra Technologies 11280100000 User Manual
Zebra Technologies Zp 450 User Manual