This system uses
R-410A
M00036-V00
CONTENTS
Safety considerations
1
2
Accessories
Installation recommendations (indoor unit)
Installation recommendations (outdoor unit)
Electrical installation
3
4
5
Wiring system diagram
6_7
Electrical connections for indoor and outdoor units
Refrigerant line connections
8
9
Refrigerant R410A: special precautions when installing unit
Tightening refrigerant piping connections
System evacuation
10
11
12
13
Additional charge
Gas leak check
14
15
Checking and testing operation
Technical specifications
Outline and dimensions
Parts diagram (indoor unit)
Parts list (indoor unit)
16
17
18
19
20
21
Parts diagram (outdoor unit)
Parts list (outdoor unit)
Installation & service manual
SAFETY CONSIDERATIONS
This manual is a guide for properly installing the Williamson-Thermoflo Wall-mounted split air conditioner. Improper
installation can result in unsafe and dangerous conditions that will void the factory warranty. Prior to installation, read
these instructions and any instructions that are packaged with separate pieces of equipment that make up the system.
Please read these instructions thoroughly and carefully before attempting installation or operation. Failure to follow these
instructions may result in improper installation, operation, service, or maintenance, possibly resulting in fire, electrical
shock, property damage, personal injury, or death.
General:
This device must be installed in compliance with national electrical standards.
About the indoor unit
1. There must be no obstacles near the air inlet and outlet.
2. Install the indoor unit on a surface that can support its weight.
3. Choose a position that enables the piping and wiring to be easily connected to the outdoor unit.
4. Leave enough clearance beneath the indoor unit to enable the filters to be removed without hinderance.
5. Maintain sufficient clearance around the indoor unit.
6. Make sure that the water from the drain hose runs away correctly and safely.
7- Install the indoor unit on a strong wall which is not subject to vibration.
8- Do NOT install the unit where it will be exposed to direct sunlight.
About outdoor unit
1. The outdoor unit must NEVER be placed on its side or upside down, as the compressor lubrication oil will run in the
cooling circuit and seriously damage the unit.
3. Choose a location where the noise of the air conditioner when running and the discharged air do not disturb any neighbors.
4. Choose a position that enables the piping and wiring to be easily connected to the indoor unit.
5. Install the outdoor unit on a flat, stable surface that can support its weight and does not generate any unnecessary
noise and vibration.
6. Position the outdoor unit so that the air flow is directed away from exterior walls, as indicated by the arrows on the top
of the unit.
7. Maintain sufficient clearance around the outdoor unit.
8. If the outdoor unit is installed above grade with brackets, ensure that its base is firmly fixed in position.
Installation& service manual _1
ACCESSORIES
The following accessories are supplied with the air conditioner.
• The quantities are indicated in parenthesi s.
Accessories in the Indoor Unit Case
Remote control
holder (1)
“AAA” batteries for
remote control (2)
Installation plate (1)
Remote control (1)
Owner’s manual (1)
Installation manual (1)
Service manual (1)
Warranty (1)
Interconnecting wiring and conduits
from the outdoor unit to the indoor unit
are not provided with the air conditioner.
Accessories in the Outdoor Unit Case
Wall plastic sleeve (1)
Rubber leg (4)
Installation & service manual _2
INSTALLATION RECOMMENDATIONS (INDOOR UNIT)
3
1. Before fixing the installation plate to a wall, you must determine the position of the 2
/4
in (70 mm) hole through which
the conduit, piping and drain hose pass to connect the indoor unit to the outdoor unit. The piping and conduit can be con-
nected from the: Rear, Right or Left side of indoor unit.
INCORRECT
CORRECT
2. Determine the position of the pipe and drain hose hole using one of the figures shown, and drill the hole with an inner
3
diameter of 70 mm (2
/4
inch) so that it slants slightly downwards.
3. The correct mounting of the indoor unit is as shown below.
2 3/8 in minimum
Left side 2 in
minimum
Right side 2 in
minimum
POSITION THE MOUNTING PLATE LEVEL
59 in minimum
59 to 79 in
minimum
CORRECT
INCORRECT
INCORRECT
Caution:
Take servicing into consideration and leave the spacing shown in the figure above. Also install the unit where
it can be removed.
Installation & service manual _3
INSTALLATION RECOMMENDATIONS (OUTDOOR UNIT)
Attach the outdoor unit with 4 anchor bolts and nuts (not supplied) positioned as per dimensions A, B.
24SRAO-HE
9SRAO-HE
21 3/8
13
12SRAO-HE | 15SRAO-HE 18SRAO-HE
A (in)
B (in)
25
24 3/8
15
23
15
13 3/8
A
24 in minimum
Air inlet
9 in minimum
12 in minimum
Air outlet
24 in minimum
16 in minimum
Caution:
The outdoor unit should not be exposed to strong winds or where it is very dusty.
- Take your neighbors into consideration so that they will not be disturbed by air blowing into their window
or by noise.
- Provide enough space between the wall and the unit, so that the airflow is not blocked. Also, for efficient
operation, leave enough clearance on both sides and front.
Installation & service manual _4
ELECTRICAL INSTALLATION
1. The air conditioner shall be installed by a qualified technician in accordance with national and local electrical codes.
2. A disconnect switch shall be installed near the outdoor unit for easy disconnect of power to the air conditioner.
3. An electrical circuit dedicated to the air conditioner shall be used for the power supply to the air conditioner.
4. Interconnecting wiring and conduits from the outdoor unit to the indoor unit are not provided with the air conditioner.
5. The supply voltage, size of over current protective device, and size of supply conductors for the air conditioner are as
shown below.
BTU
6. Unit must be installed in accordance with all applicable federal, state and local codes.
7. Check local electrical codes and regulations before obtaining wire.
8. Use copper supply wires only.
9. Each wiring connection must be done tightly and in accordance with the wiring system diagram. Improper wiring may
cause the unit to malfunction or become damaged.
Installation & service manual _5
WIRING SYSTEM DIAGRAMS
9SRA-HE | 12SRA-HE | 15SRA-HE (115V - 60Hz)
INDOOR UNIT
L1
DISPLAY AND
RECEIVE BOARD
9
N
Terminal block of indoor unit
FUSE
3.15 A
COMPULSIVE SWITCHING
PIPE SENSOR
2
2
ACN
ACL
BU
BN
OR
3
2
1
3
2
1
TEMP SENSOR
IN FAN
2
5
3
2
1
CMU
5
STEP
MOTOR
INDOOR CONTROL BOARD
INDOOR UNIT WIRING DIAGRAM
L1 N
3
2
1
Terminal block
of outdoor unit
OUTDOOR UNIT
Power supply,
1 phase, 60 Hz
CAPACITOR
BN
RD
L1
N
R
PROTECTOR
WH
C
S
COMPRESSOR
HIGH
PRESSURE
SWITCH
BU
BU
NO
COM
LOW
PRESSURE
SWITCH
ACN
3
2
1
3
2
1
BN
5
OUT
FAN
FUSE
3.15 A
OUTDOOR TEMP SENSOR
CMU
2
2
OR
OUTDOOR PIPE SENSOR
OUTDOOR CONTROL BOARD
OUTDOOR UNIT WIRING DIAGRAM
Installation & service manual _6
WIRING SYSTEM DIAGRAMS
18SRA-HE | 24SRA-HE (208-230V - 60Hz)
INDOOR UNIT
L1
DISPLAY AND
RECEIVE BOARD
9
L2
Terminal block of indoor unit
FUSE
3.15 A
COMPULSIVE SWITCHING
PIPE SENSOR
2
2
ACN
ACL
BU
BN
OR
3
2
1
3
2
1
TEMP SENSOR
IN FAN
2
5
3
2
1
CMU
5
STEP
MOTOR
INDOOR CONTROL BOARD
INDOOR UNIT WIRING DIAGRAM
L1 L2
3
2
1
Terminal block
of outdoor unit
OUTDOOR UNIT
Power supply,
1 phase, 60 Hz
CAPACITOR
BN
RD
L1
L2
R
PROTECTOR
WH
C
S
COMPRESSOR
HIGH
PRESSURE
SWITCH
BU
BU
NO
COM
LOW
PRESSURE
SWITCH
ACN
3
2
1
3
2
1
BN
5
OUT
FAN
FUSE
3.15 A
OUTDOOR TEMP SENSOR
CMU
2
OR
OUTDOOR CONTROL BOARD
OUTDOOR UNIT WIRING DIAGRAM
Installation & service manual _7
ELECTRICAL CONNECTIONS FOR INDOOR AND OUTDOOR UNITS
INDOOR UNIT
1. The indoor unit is powered from the outdoor unit. A sufficient length of conduit and wiring shall be used from the
outdoor unit to the indoor unit.
2. To access the terminal block inside the indoor unit, remove the screw on the cover plate. (See Fig. A.)
3. Connect the inter unit conductors to terminals marked 1,2,3, on the indoor unit corresponding to the same numbered
terminals from the outdoor unit. (See Fig.B.)
Figure A
Figure B
Terminal block of indoor unit
Terminal block
Cover plate
OUTDOOR UNIT
1. Two conduit connection openings are provided on the outdoor unit: one for incoming power supply and the second one for
the inter unit wiring.
2. Remove the terminal box cover to access the terminal block.
3. Connect the power supply conductors to terminal marked L1, N or L1, L2, and the grounding wire to terminal
marked
.
4. Connect the inter unit conductors to terminals marked , 3, 2, 1.
18SRA-HE | 24SRA-HE (208-230V - 60Hz)
9SRA-HE | 12SRA-HE | 15SRA-HE (115V - 60Hz)
Conduit
connectors
Conduit
connectors
Conduit
Conduit
Incoming power supply
Incoming power supply
To indoor unit
To indoor unit
Installation & service manual _8
REFRIGERATION LINE CONNECTIONS
When connecting the refrigerant tubing
- Keep all tubing runs as short as possible.
- Use the flare method for connecting tubing.
- Apply refrigerant lubricant to the matching surfaces of the flare and union tubes before connecting them, then tighten
the nut with a torque wrench for a leak-free connection.
- Check carefully for leaks before starting the test run.
Compressor
3-Way valve
2-Way valve
Capillary tube
Models
9SRA-HE
12SRA-HE 15SRA-HE 18SRA-HE 24SRA-HE
Refrigeration Tubing
Connection method
Refrigerant tube outer diameter
Flare
1/4
1/2
49
Flare
1/4
1/2
49
Flare
1/4
1/2
49
Flare
1/4
5/8
49
Flare
3/8
5/8
49
in. Liquid
in. Suction
Limit of tubing length
ft.
ft.
Limit of elevation difference between the two units
20
20
20
20
20
Installation & service manual _9
REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN INSTALLING UNIT
Caution:
The compressor POE oil for R-410A units is extremely susceptible to moisture absorption and could cause
compressor failure. Do not leave system open to atmosphere any longer than necessary for installation.
General Information
Systems using R-410A refrigerant run at a pressure of approximately 1.6 times that of similar systems using R-22 and the
energy efficiency is comparable. The R-410A refrigerant is a 50:50 mixture of R-32 and R-125.
When installing equipment using R-410A refrigerant, there are a number of standards that must be met:
• Ester oil is used for R-410A.
• It’s important to work with absolute cleanliness.
• Brazing must be done with the use of Nitrogen.
• The system must always be charged in the liquid state.
When refrigerant R-410A is used, the composition will differ depending on whether or not it is a gaseous state.
Consequently, always charge the refrigerant while it is in a liquid state.
General Precautions – Refrigerant leaking
The composition of refrigerant R-410A changes when it is gaseous state. Thus, when there is a refrigerant leak the basic
performance of the air conditioner may be degraded because of a change in composition of the remaining refrigerant.
Therefore, do not add new refrigerant. Instead, recover the remaining refrigerant with the refrigerant recovery unit. Then,
after evacuation, totally recharge the unit with the specified amount of new refrigerant at it’s normal mixed composition state.
Tubing Precautions
The refrigerant R-410A is less is more easily affected by dust or moisture than R-22 refrigerant. Make sure to temporally
cover the ends of the tubing with caps or tape prior installation.
Never use tubing which is less than 0.03 inch in thickness (Standard Specification ASTM B-280), since air conditioners with
R-410A refrigerant are subject to higher pressures than those using R-22 refrigerant.
Installation & service manual _10
TIGHTENING REFRIGERANT PIPING CONNECTIONS
Caution:
Remove the protection caps on the pipes and connect the assembly piping to each connector. First,
tighten the nuts manually and then with a wrench by applying the tightening torque shown below.
Flare nut size and tightening torque
Class 2 (for R410A)
Applicable size
Diamètre (mm) x Tightening torque (Nm)
1/4 “
3/8 “
1/2 “
5/8 “
3/4 “
17 x 14 to 18
22 x 34 to 42
26 x 49 to 61
29 x 68 to 82
36 x 100 to 120
Installation & service manual _11
SYSTEM EVACUATION
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve
stems closed and caps installed. Do not open the valves until the system is evacuated.
1. Connect the vacuum pump with 250-micron capability to the services valves.
2. Evacuate the system to 250 microns or less using suction and liquid service valves. Using both valves is necessary for some
compressors create a mechanical seal separating the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes. Typically pressure will rise during this period
• If the pressure rises to 1000 microns or less and remains steady the system is considered leak-free; proceed to startup.
• If the pressure rises above 1000 microns but holds steady below 2000 microns, moisture and/or noncondensibles may
be present or the system may have a small leak. Return to step 2: If the same result is encountered, check for leaks as
previously indicated and repair as necessary then repeat evacuation.
• If pressure rises above 2000 microns, a leak is present. Check for a leaks as previously indicated and repair as
necessary then repeat evacuation.
Manifold valve
High pressure side valve
Low pressure side valve
Charging hose
Charging hose
Vacuum pump
A
B
Caution:
Refrigerant must not be discharged into the atmosphere.
After connecting the piping, check the joints for leakage with a gas leak detector.
Installation & service manual _12
ADDITIONAL CHARGE AND DISTANCE
Refrigerant suitable for a piping length of 20 ft (6 m) is charged in the outdoor unit at the factory. When the pipe is longer
than 20 ft (6 m), additional charging is necessary. This operation can only be performed by a qualified refrigeration
specialist. Additional amount must be added for each extra 3.3 ft (1 m), see the table below:
12SRA-HE | 15SRA-HE |
Models
9SRA-HE
24SRA-HE
18SRA-HE
Additional refrigerant
20 g (0.7 oz)
40 g (1.41 oz)
30 g (1.06 oz)
Models
9SRA-HE | 12SRA-HE | 15SRA-HE | 18SRA-HE | 24SRA-HE
Limit of tubing length
ft (m)
49 (15)
Limit of elevation
between the two unit
20 (6)
Installation & service manual _13
GAS LEAK CHECK
Check that no gas escapes from the connections by using a leak detector or soapy water.
A and B are the liquid and suction valves of the outdoor unit.
C and D are the extremities of the indoor unit flared connections.
Indoor unit check points
C
D
A
B
Liquid and suction valves
Installation & service manual _14
CHECKING AND TESTING OPERATIONS
Perform the operation test after completing the gas leak check of the flare nut connections and the electrical connections.
1. To begin the test, turn on the power.
2. Press the auxiliary control button in the indoor unit or use the remote control to start the unit.
3. Check that all air conditioner functions are operating normally. A protection feature prevents the air conditioner from
being started immediately after the unit has been turned off. There is a delay of 3 minutes for the air conditioner to restart
and operate.
4. Press the auxiliary control button to end the operation test.
9 000-12 000 BTU
15 000-18 000-24 000 BTU
Auxiliary control button
Auxiliary control button
Installation & service manual _15
TECHNICAL SPECIFICATIONS
SPECIFICATIONS
18SRA-HE
24SRA-HE
15SRA-HE
9SRA-HE
12SRA-HE
MODELS
Performance ratings
Nominal capacity
18 000
13.5
24 000
13
15 000
14
R-410A
3.5
559
47-44-40
55
95 (35)
64 (18)
109 (43)
32 (0)
9 000
15
R-410A
1.9
382
44-40-33
50
95 (35)
64 (18)
109 (43)
32 (0)
12 000
13.5
R-410A
3.1
441
45-42-34
52
95 (35)
64 (18)
109 (43)
32 (0)
BTU/h
Cooling
Cooling
S.E.E.R
Refrigerant type
BTU/hW
R-410A
4.1
R-410A
5.2
Dehumidifying capacity
Airflow circulation (High)
Indoor sound rating (High-Medium-Low)
Outdoor sound rating
Pt./H
CFM
dB(A)
dB(A)
°F (°C)
647
765
48-44-40
56
52-49-45
59
Temperature
Indoor air intake
95 (35)
64 (18)
109 (43)
32 (0)
95 (35)
64 (18)
109 (43)
32 (0)
Maximum
Minimum
Maximum
Minimum
Outdoor air intake
°F (°C)
Electrical data
Voltage rating
V
115
60 / 1
7.7
15
15
115
60 / 1
10.7
15
208~230
60 / 1
6.8 / 6.4
15
115
60 / 1
10.6
15
208~230
60 / 1
9.6 / 8.7
20
Frequency / Phase
Running amperes
Hz / ø
A
A
A
Cooling
Minimum circuit ampacity
Maximum overcurrent protection
(Time delay fuse or HACR type circuit breaker)
Refrigeration tubing
25
15
20
25
Connection method
Refrigerant tube outer diameter
Flare
1/4
5/8
49
Flare
3/8
5/8
49
Flare
1/4
1/2
49
Flare
1/4
1/2
49
Flare
1/4
1/2
49
Liquid
Suction
in.
Limit of tubing length
ft.
ft.
Limit of elevation difference between the two units
Dimensions & weight
20
20
20
20
20
Width
Height
Depth
Shipping
Net
Width
Height
Depth
Shipping
Net
31 1/2
10 7/8
8 1/4
22
Indoor unit
Dimensions
31 1/2
10 7/8
8 1/4
22
in.
42 1/2
13
9 1/4
39
35
38 3/4
12 5/8
7 1/2
33
38 3/4
12 5/8
7 1/2
33
lbs
in.
Weight
19
19
29
29
33 7/8
25 5/8
12
31 3/4
23 1/2
11 1/4
92
38 1/4
37 1/2
14 1/4
150
Outdoor unit
Dimensions
33 7/8
25 5/8
12
37 1/2
33 3/4
13 3/4
139
101
95
lbs
101
95
Weight
88
130
141
*Note: Design and specifications are subject to change without notice for product improvement.
Comply with ARI STANDARD 210/240.
Installation & service manual _16
OUTLINE AND DIMENSIONS
Models: 9SRA-HE | 12SRA-HE | 15SRA-HE | 18SRA-HE | 24SRA-HE
C
Indoor unit
B
Outdoor unit
D
H
E
I
9SRA-HE
10 7/8
31 1/2
8 1/4
31 3/4
11
23
1/2
11 1/4
14 1/8
12SRA-HE 15SRA-HE 18SRA-HE 24SRA-HE
In
A
B
C
D
E
10 7/8
31 1/2
8 1/4
33 7/8
12
12 5/8
38 3/4
7 1/2
33 7/8
12
12 5/8
38 3/4
7 1/2
37 1/2
14
13
43 1/2
9 1/4
38 1/4
14 1/2
36
1 1/2
14 1/4
16 1/4
25
5/8
25
5/8
32 1/4
1 1/2
F
G
H
I
12
14 3/4
12
14 3/4
13 3/4
16 1/4
Installation & service manual _17
PARTS DIAGRAM (INDOOR UNIT)
INSIDE UNIT
9SRAI-HE
12SRAI-HE
15SRAI-HE
18SRAI-HE
24SRAI-HE
Installation & service manual _18
PARTS LIST (INSIDE UNIT)
Inside unit - spare parts
REF.
DESCRIPTION
NO
QTY
9SRAI-HE
12SRAI-HE
15SRAI-HE
18SRAI-HE
24SRAI-HE
Faceplate (including display glass)
Lamp board holder
Lamp Board (3 lights) + infrared lense
Lamp board back cover
Control Box Cover
Terminal block Cover
Plastic Cover
1
1
P00844
P00864
P00848
P00866
P00852
P00856
N/A
P00844
P00864
P00848
P00866
P00852
P00856
N/A
P00845
P00865
P00849
P00867
P00853
P00857
N/A
1
2
P00843
P00846
P00847
P00850
P00851
P00854
P00855
P00858
P00861
L00140
L00027
P00874
P00875
P00876
L00138
P00878
P00881
P00882
P00883
P00884
K00086
P00889
P00892
P00895
K00090
P00901
P00904
P00907
P00910
P00913
P00916
P00919
P00877
P00925
P00928
P00931
P00898
P00843
P00846
P00847
P00850
P00851
P00854
P00855
P00858
P00861
L00141
L00027
P00874
P00875
P00876
L00138
P00878
P00868
P00882
P00883
P00884
K00086
P00889
P00892
P00895
K00090
P00901
P00904
P00907
P00910
P00913
P00916
P00919
P00877
P00925
P00928
P00931
P00898
1
3
1
4
5
1
1
6
1
7
P00859
P00862
L00142
L00027
P00874
P00875
P00876
L00138
P00879
P00869
P00882
P00883
P00885
K00087
P00890
P00893
P00896
K00091
P00902
P00905
P00908
P00911
P00914
P00917
P00920
P00886
P00926
P00929
P00932
P00899
P00859
P00862
L00143
L00027
P00874
P00875
P00876
L00138
P00879
P00870
P00882
P00883
P00885
K00088
P00872
P00873
P00896
K00091
P00902
P00905
P00908
P00911
P00914
P00917
P00920
P00886
P00926
P00929
P00932
P00899
P00860
P00863
L00144
L00027
P00874
P00875
P00876
L00138
P00880
P00871
P00882
P00883
P00885
K00089
P00891
P00894
P00897
K00092
P00903
P00906
P00909
P00912
P00915
P00918
P00921
P00924
P00927
P00930
P00933
P00900
8
Filters
2
9
Middle Base
1
10
11
12
13
14
15
16
17
18
19
20
21
Rating plate (WILLIAMSON)
Wiring circuit diagram
Wireless remote control
Wireless remote control holder
Terminal Block
1
1
1
1
1
Nameplate (WILLIAMSON)
Control Box
1
1
Controller PCB
1
Sensors
1
Sensor Bracket
1
Rubber plug (back drain)
Fan Motor Assembly
Fan motor cushion
Fan motor
1
kit
1
21-1
21-2
1
Evaporator Assembly
Cross Flow Fan Assembly
Cross Flow Fan
22
23
23-1
1
kit
1
Cushion - Cross flow fan
Left Cover (Cross flow fan)
Drain Hose
23-2
24
1
1
1
25
26
27
28
29
30
31
32
33
Blade (vertical movement)
Fan guard metal grid
Discharge frame assembly
Step Motor
1 or 2
1
1
1
Louvers (horizontal movement)
Base Assembly
2
1
Wall Hook Bracket
Screw cap
1
3
Installation & service manual _19
PARTS DIAGRAM (OUTDOOR UNIT)
OUTSIDE UNIT
9SRAO-HE
12SRAO-HE
15SRAO-HE
18SRAO-HE
24SRAO-HE
Installation & service manual _20
PARTS LIST (OUTSIDE UNIT)
Outside unit - spare parts
REF.
DESCRIPTION
NO
QTY
9SRAO-HE
12SRAO-HE
15SRAO-HE
18SRAO-HE
24SRAO-HE
1
2
3
4
5
6
7
8
9
Cabinet | Front L | Painted (including fan cover)
Control box cover
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Kit
1
3
3
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
4
1
1
P00730
P00734
P00738
P00740
P00744
L00139
P00747
P00749
P00752
P00756
P00757
P00760
P00763
P00766
P00731
P00734
P00738
P00741
P00744
L00139
P00747
P00735
P00752
P00756
P00757
P00761
P00764
P00767
P00731
P00734
P00738
P00741
P00744
L00139
P00747
P00735
P00752
P00756
P00757
P00761
P00764
P00767
P00732
P00734
P00739
P00742
P00745
L00139
P00748
P00750
P00754
P00758
P00759
P00737
P00746
P00768
P00753
P00773
P00777
K00084
P00785
P00787
P00793
P00797
P00801
P00805
P00807
P00811
P00814
P00818
P00823
L00029
L00148
P00830
P00835
P00839
P00841
P00842
P00772
P00945
P00946
P00733
P00734
P00739
P00743
P00745
L00139
P00748
P00751
P00755
P00736
P00759
P00762
P00765
P00769
include with ref. #1
P00774
P00777
K00085
P00786
P00787
P00794
P00797
P00801
P00805
P00807
P00811
P00815
P00819
P00824
L00029
L00149
P00833
P00836
P00840
P00841
P00842
P00772
P00945
P00946
Propeller fan
Motor bracket
Fan motor
Nameplate (WILLIAMSON)
PCB outdoor
Control box
Capacitor | Compressor
10 Capacitor clamp
11 Terminal block
12 Divider wall
13 Cabinet | top | Painted
14 Condenser assembly
15 Cabinet | Front R | Painted
16 Base Assembly / Painted
17 Capillary assembly
18 Compressor assembly
18-1 Compressor
include with ref. #1 include with ref. #1 include with ref. #1
P00770
P00775
K00082
P00783
P00787
P00791
P00795
P00799
P00803
P00807
P00811
P00812
P00816
P00820
L00028
L00145
P00831
P00829
P00837
P00841
P00842
P00772
P00945
P00946
P00771
P00776
K00083
P00784
P00787
P00791
P00795
P00799
P00803
P00807
P00811
P00813
P00817
P00821
L00028
L00146
P00832
P00834
P00838
P00841
P00842
P00772
P00945
P00946
P00771
P00776
K00083
P00784
P00787
P00791
P00795
P00799
P00803
P00807
P00811
P00813
P00817
P00821
L00028
L00147
P00832
P00834
P00838
P00841
P00842
P00772
P00945
P00946
18-2 Special nut | M8
18-3 Rubber seat
18-4 Terminal gasket
18-5 Terminal cover
19 Noise insulation
20 Sensor bracket
21 Rubber caps
22 Steel Grid
23 Cabinet | Back R | Painted
24 Side plastic cover
25 Electric Diagram
26 Rating Plate (WILLIAMSON)
27 Two-Way valve (Liquid)
28 Three-Way valve (Succion)
29 Valve panel
30 Outdoor heat exchanger thermistor
31 Discharge temperature thermistor
32 Rubber legs
33 Low pressure switch
34 High pressure swicth
Installation & service manual _21
NOTE
Installation & service manual
8201 W. Calumet Road, Milwaukee, WI 53223 USA
|