Mitsubishi Electronics Peh 7mya User Manual

AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS  
DATA BOOK  
Series : PE(H)  
Model  
Service ref.  
PE-7MYC  
PE-8MYC  
PE-10MYC  
PE-15MYC  
PE-20MYC  
PE-7MYC-EU  
PE-8MYC-EU  
PE-10MYC-EU  
PE-15MYC-EU  
PE-20MYC-EU  
Cooling only  
Heat pump  
PEH-5MYA  
PEH-7MYA  
PEH-8MYA  
PEH-10MYA  
PEH-15MYA  
PEH-20MYA  
PEH-5MYA-EU  
PEH-7MYA-EU  
PEH-8MYA-EU  
PEH-10MYA-EU  
PEH-15MYA-EU  
PEH-20MYA-EU  
SAFETY FOR USE  
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully  
for correct installation.  
Since the caution items shown here contain important description relative to safety, please  
observe them without fail.  
Erroneous handling gives a high possibility to induce serious results such as  
death or heavy injury.  
Warning  
Erroneous handling may induce serious injury depending on the situation.  
Caution  
After reading, please keep it with you together the Instruction Manual, and read it again at the  
movement of the unit.  
Warning  
Never repair the unit, remodel or transfer it to  
another site by yourself.  
Ask your dealer or specialized subcontractor  
for installation.  
Conducting installation work by yourself improperly  
may cause a fire, electric shock or water leakage.  
If they are performed improperly, water leakage, electric  
shock or fire may result. If you need to have the unit  
repaired or moved, consult your dealer.  
For installation, conduct the work correctly by  
following the Installation Manual.  
Improper installation may cause a fire, electrical shock  
or water leakage.  
Use only the specified refrigerant (R-22) to charge  
the refrigerant circuit.  
Do not mix it with any other refrigerant and do not  
allow air to remain in the circuit.  
Air enclosed in the circuit can cause high pressure resulting  
in a rupture and other hazards.  
Install the unit on a spot sufficiently durable against  
the unit weight.  
Insufficient durability can cause an injury by the falling  
down of unit.  
Ventilate the room if refrigerant leaks during  
Installation.  
The refrigerant heated generates poisonous gas by  
decomposition which can cause poisoning.  
All electric work must be performed by licensed  
technician, according to local regulations and the  
instructions given in this manual.  
The units should be powered by dedicated power  
lines.  
After completing installation work, make sure that  
refrigerant gas has not leaked.  
Power lines with insufficient capacity or improper  
electrical work may result in electric shock or fire.  
If refrigerant gas has leaked and exposed to fan heater,  
stove, oven and so on, it may generate noxious gases.  
Please do the gas leakage inspection before starting.  
Use only the specified cables for wiring. The  
connections must be made secured without  
tension the terminals.  
Improper connection or fastening can cause a fire or  
electrical shock.  
Take a proper measure to suppress the critical  
concentration of refrigerant if leaked when  
installing the unit in a small room.  
The limit density is made not to be exceeded even if the  
refrigerant leaks by any chance.  
You are necessary to ventilation measures to prevent  
the accident. If the refrigerant leaks, hypoxia accident  
may caused.  
The unit should be installed according to the  
instructions in order to minimize the risk of damage  
from earthquakes, typhoons or strong winds.  
Improper installation work can cause an injury by the  
falling down of the unit.  
The outdoor unit must be installed on stable, level  
surface, in a place where there is no accumulation  
of snow , leaves or rubbish.  
For the countermeasure to be taken, consult your  
dealer.  
The outdoor unit should be installed in a location  
where air and noise emitted by the unit will not  
disturb the neighbors. The indoor unit should be  
securely installed.  
The terminal block cover of unit must be firmly  
attached to prevent entry of dust and moisture.  
Improper mounting of the cover cause electric shock or  
fire.  
If the unit is loosely mounted, it may fall, and cause injury.  
Use only optional parts authorised by Mitsubishi  
Electric.  
If the accessories are installed improperly, water  
leakage, electric shock or fire may result.  
Ask your dealer or an authorised company to install  
them.  
The heating of refrigerant is noted.  
When the refrigerant touches the fire etc., it was decom-  
posed and a poisonous gas is generated.  
Do not use the welding machine etc., in the room close up  
of the installation of the air conditioner.  
- 2 -  
Caution  
Arrange the configuration of wiring not to bring up  
Never install on the place where a combustible  
gas might leak.  
The gas may ignite or explode when the gas leaks and  
collects in surround of the unit.  
the panel and terminal cover, and fasten the panel  
and terminal cover securely.  
The poor mounting of the panel or terminal cover may  
cause the heat generation of the terminal connection,  
a fire or electrical shock.  
When the unit is installed at telecommunication  
centers or hospitals, take a proper provision  
against noise.  
The erroneous operation of air conditioner may be  
induced by inverter equipment, independent power  
device, medical equipment or communication  
equipment.  
Do not wash the unit with water.  
If washed with water, electric shock may be caused.  
Do not handle the switch with wet hands.  
Otherwise electric shock can be resulted.  
Be very careful about unit transportation.  
For special use as for foods, animals/plants,  
precision equipment or art objects, the applicability  
should be confirmed beforehand.  
As the use for the applications other than that  
designed originally may result in the deterioration of the  
quality. Consult your dealer in this regard.  
The unit should not be carried by only one person if it is  
more than 20kg. It occasionally causes the damage of  
the unit and health to be impaired.  
Some unit use PP bands for packing. Do not use any PP  
band for delivery purpose. It may cause the injury.  
Do not touch the heat exchanger fins with your bear hands.  
Doing so may cut your hands.  
When carrying in outdoor unit, be sure to support it at four  
points. Carrying in and lifting with 3-point support may  
make outdoor unit unstable, resulting in a fall of it.  
Be sure to safety dispose the packing materials.  
Packing materials, such as catches and other metal or  
wooden parts, may cause stabs or other injuries.  
Do not use the unit under a special atmosphere.  
Installing the unit at the following places may cause a  
trouble, a place where is much machine oil, salt ,  
humidity or dust, spa district, a place full of sulfur gas,  
volatile gas, or corrosive gas, a place near high  
frequency processing machine.  
Thermal insulation of the drain pipes is necessary  
prevent dew condensation.  
If the drain pipes are not properly insulated,  
condensation will result and drip on ceiling, floor or other  
possessions.  
Do not leave the mounting base being damaged.  
The damaged base may cause the falling down of the  
unit which may give injury.  
Turn on the main power switch more than 6 hours  
before starting operation.  
Do not turn the main power switch OFF during seasons  
of heavy use, doing so can result in failure.  
The unit should be securely installed level surface.  
When the unit inclines, it causes the water leak and the  
breakdown.  
Please confirm the horizontal with the spirit level.  
Do not touch the compressor or refrigerant piping  
without wearing glove on your hands.  
Touching directly such part can cause a burn or  
frostbite as it becomes high or low temperature  
according to the refrigerant state.  
Install drain piping (hose) according to this  
Installation Manual to ensure proper drainage.  
Improper drain piping (hose) may cause water leakage  
and damage to furniture or other possessions.  
The unit must be properly earth connected.  
Do not connect the earth wire to gas pipe, city water  
pipe, lightning rod or telephone earth wire.  
Do not touch the metal edges inside the unit  
without wearing glove on your hands.  
Touching directly it may injure your hands.  
Improper earth connection may cause electrical shock.  
Do not remove the panel or the fan guard from the  
unit when it is running.  
You could be injured if you touch rotating, hot or high-  
voltage parts.  
When installing at a watery place, provide an  
electric leak breaker.  
Failure to mount the electric leak breaker may cause  
electrical shock.  
Do not operate the air conditioner without the air  
filter set place.  
Use breaker or fuse with proper capacity.  
Make sure that each appliance has a main power  
Dust may accumulate, and cause a failure.  
switch.  
Using a wire or copper wire instead of proper capacity  
can cause fire or trouble.  
At emergency (if you smell something burning), stop  
operation and turn the power source switch off.  
Continuing the operation without eliminating the  
emergency state may cause a machine trouble, fire, or  
electrical shock.  
Other appliances connected to the same line could cause  
an overload.  
For the power lines, use standard cables of  
sufficient current capacity.  
Otherwise, current leakage, overheating or fire may  
occur.  
After stopping operation, be sure to wait for five  
minutes before turning off the main power switch.  
Otherwise, water leakage or unit failure may occur.  
When installing the power lines, do not apply  
tension to the cables.  
The tighten or loosen the connections may cause generate  
heat and cause fire.  
Remote controller is not installed for the place  
where direct sunshine strikes.  
Remote controller is not pushed with the thing  
sharpening ahead.  
It occasionally causes the electric shock and the break-  
down.  
A thing embarrassed which gets wet under the unit  
is not put.  
When the room is high humidity or when the drain pipe  
is clogged, water may drip from the indoor unit.  
- 3 -  
A COMPLETE LINE UP  
PEH-5  
14.4  
PE(H)-7  
17.9  
PE(H)-8  
22.0  
PE(H)-10 PE(H)-15 PE(H)-20  
28.8  
44.0  
150,200  
37,900  
44.0  
57.6  
196,600  
49,600  
57.6  
kW  
Btu/h  
kcal/h  
kW  
49,150  
12,400  
14.4  
61,000  
15,400  
18.8  
75,100  
18,900  
22.0  
98,300  
24,800  
28.8  
Cooling capacity  
Heating capacity  
(PEH only)  
49,150  
12,400  
64,100  
16,200  
75,100  
18,900  
98,300  
24,800  
150,200  
37,900  
196,600  
49,600  
Btu/h  
kcal/h  
Note: Cooling & heating capacities are based following conditions.  
Cooling: Indoor:27 DB, 19 WB; Outdoor: 35 DB  
Heating: Indoor:21 DB; Outdoor: 7 DB, 6 WB (PEH only)  
Cooling and Heating capacities are based 5m pipe length  
Indoor unit  
Example PEH-7  
Outdoor unit  
Example PUH-7  
- 4 -  
FEATURES  
Labour saving installation.  
High sensible cooling capacity.  
The sensible cooling capacity has been significantly  
improved through balanced optimised heat  
exchanger design.  
The unit operation can commence immediately after  
connecting to the power supply, refrigerant piping,  
drain piping, ducting and control system.  
Comfort heating. (PEH only)  
The PEH series are designed to provide effective  
heating even when the outside temperature is down  
Wide electrical control capability.  
All series is flexible mechanical control  
configuration.  
In addition Global Remote Controller is prepared as  
special order.  
The Global Remote Controller gives the programmable  
weekly timer, compressor anti-short cycle timer(3min.),  
cool/heat/fan/auto changeover etc.(Heat and auto  
changeover are only PEH.)  
The factory standard is for provision of 24 volt terminal  
block to enable a field wired control of contractors  
choice to be connected.  
to -10  
.
Highly efficient operation.  
The EER(Energy Efficiency Ratio) on these models  
is greatly improved by revised design specifications  
and by being manufactured stringently to Mitsubishi  
Electric high quality standards.  
Flexibility of Supply Air Delivery  
PE, PEH-15,20 feature belt driven Supply Air fans  
enabling accurate matching of actual airflow rates  
to the specified quantities. Accurate commissioning  
is assisted by the capability to change pulleys and  
belts if necessary to achieve the desired air balance.  
Please consult your local Mitsubishi Electric Sales  
office for application advice on these control.  
Low ambient cooling. (Special order)  
In applications with relatively high internal loads,  
there may be a requirement for all series to  
operate on cooling at low ambient conditions.  
Special order parts is available to maintain the  
refrigeration circuit in balance at outdoor temperatures  
as low as -5  
.
Please consult your local Mitsubishi Electric Sales  
office for application advice on these parts.  
Grobal Remote Controller  
DESCRIPTIONS  
With the development of all series demands  
for such features as light weight, compactness,  
Mitsubishi Electric air conditioners series PE(H)/PU(H)  
are available in a wide range of sizes and models to  
enables the designer to select the best model for  
each application.  
All series units are completely assembled, wired and  
strictly tested at the factory.  
increased capacity, appropriate static pressure, air  
flow control, and having flexibility of inter facing  
energy saving electronic controls, Mitsubishi  
Electric have met market expectations.  
- 5-  
MECHANICAL SPECIFICATIONS  
General  
Condenser Coils  
All units are factory assembled, piped, internally wired.  
They are also tested and checked under a strict quality  
control system in the factory.  
Unnecessary power input due to higher discharge  
pressure is avoided by high performance designs of  
cross-finned coil.  
Exterior surfaces of all units of outdoor unit are  
phosphatized, zinc-coated steel with powder coating  
and ivory white baked enamel finish.  
Condenser coils are made of 9.52mm OD, 0.35mm  
thick seamless copper tubes mechanically bonded to  
0.12mm thick aluminium fins and factory pressure  
and leak tested at 3.3MPa.  
Refrigeration Controls  
Refrigeration controls include condenser fan,  
evaporator fan and compressor contactors.  
Evaporator Fans  
The sirocco fans are made of galvanised steel and  
balanced to proved accurate air flow performance at  
low noise level.  
Compressors  
All units have high efficiency type hermetic line starting  
compressors.  
Condenser Fan  
Compressors are equipped with thermal overload  
protector, over-current relay and high pressure  
protection control.  
The direct-drive propeller fan is dynamically balanced,  
to ensure smooth airflow.  
Crankcase heaters are standard.  
A weatherproof three-phase squirrel cage induction  
motor is used to drive the condenser fan.  
Evaporator Coils  
Highly efficient cross-finned coil are applied to provide a  
larger cooling capacity with low air speed on the coil.  
Coils are made of 9.52mm OD and 0.35mm thick  
seamless copper tubing mechanically bonded to 0.12mm  
thick aluminium fins and are factory leak tested at a  
pressure of 3.3MPa. They are provided with strainers  
attached to the capillary tubes to further ensure a clean  
system.  
TYPICAL INSTALLATION EXAMPLE  
PU(H)  
PE(H)  
PE(H)  
PU(H)  
- 6-  
MODEL-DESIGNATION BREAKDOWN  
1
P E-10 M Y C  
Service reference  
Design Sequence  
Electrical Supply  
Y = 3 phase 380~415V 50Hz 4 wires  
In case of PE(H)-7 Indoor unit  
Y = 1 phase 220~240V 50Hz 2 wires  
(
)
Compressor Horsepower  
5 = 5 HP  
7 = 7 HP  
8 = 7.5 HP  
10= 10 HP  
15= 15 HP  
20= 20 HP  
Series Number  
PE = Indoor unit  
PEH = Indoor unit  
PU = Outdoor unit  
PUH = Outdoor unit  
- 7 -  
SPECIFICATIONS  
Cooling only  
PE-7~20MYC  
PE-15MYC  
PE-20MYC  
Model name  
PE-7MYC  
PE-8MYC  
PE-10MYC  
Service  
reference  
PE-15MYC-EU  
PE-20MYC-EU  
PE-7MYC-EU  
PE-8MYC-EU  
PE-10MYC-EU  
1PH 2W220~240V 50Hz  
3PH 4W380 ~ 415V 50Hz  
3PH 4W380 ~ 415V 50Hz  
Power supply  
Indoor  
3PH 4W 380~415V 50Hz  
17.9  
Outdoor  
Total cooling capacity  
22.0  
28.8  
44.0  
150,200  
37,900  
35.2  
57.6  
196,600  
49,600  
46.1  
kW  
Btu/h  
kcal/h  
kW  
61,100  
75,100  
18,900  
17.6  
98,300  
24,800  
23.0  
15,400  
14.3  
Sensible cooling capacity  
48,800  
60,100  
15,100  
78,500  
19,800  
120,200  
30,200  
157,300  
39,600  
Btu/h  
kcal/h  
%
12,300  
Capacity step  
Refrigerant  
Refrigerant charge  
0-100  
0-50-100  
R-22  
8.7  
kg  
5.7  
5.0  
2 ✕ 4.8  
2 ✕ 9.7  
Capillary tube  
PE-10MYC  
Refrigerant control  
PE-15MYC  
PE-20MYC  
Indoor Unit  
PE-7MYC  
PE-8MYC  
Model name  
Service  
reference  
PE-15MYC-EU  
PE-20MYC-EU  
PE-7MYC-EU  
PE-8MYC-EU  
PE-10MYC-EU  
Galvanized steel  
External finish  
Dimension  
706  
865  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
428  
1,993  
212  
1,615  
1,690  
180  
1,415  
650  
70  
67  
84  
Net weight  
Cross fin coil  
Indoor coil  
Centrifugal (Galvanized) - Direct drive  
Centrifugal (Galvanized) - Belt drive  
Indoor fan  
Indoor fan motor  
Three phase induction motor  
Single phase induction motor  
1 ✕ 3.7  
180  
1 ✕ 0.7  
70  
1 ✕ 1.0  
90  
kW  
CMM  
1 ✕ 2.2  
140  
No. ✕ Motor output  
1 ✕ 0.21  
60  
Indoor fan air flow  
CFM  
L/S  
2,119  
1,000  
2,472  
1,167  
12.5  
125  
3,179  
1,500  
4,945  
2,333  
6,358  
3,000  
External static  
pressure  
mmAq  
Pa  
20  
200  
55  
56  
59  
25.4  
61  
62  
Sound pressure level  
Drain connection  
dB(A)  
mm  
Outdoor unit  
PU-7MYC  
PU-8MYC  
PU-10MYC  
PU-15MYC  
PU-20MYC  
Model name  
Service  
reference  
PU-7MYC1-EU(S)  
PU-8MYC1-EU(S) PU-10MYC1-EU(S) PU-15MYC1-EU(S) PU-20MYC1-EU(S)  
Acrylic resin coating  
Munsell 5Y 8/1  
External finish  
Color  
980  
1,400  
700  
1,230  
998  
961  
1,996  
Dimension  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
998  
230  
360  
205  
285  
Net weight  
202  
Hermetic line start(reciprocating)  
Compressor  
2 ✕ 7.5  
No. ✕ Motor output  
1 ✕ 5.5  
1 ✕ 7.5  
kW  
2 ✕ 5.5  
1 ✕ 5.0  
Outdoor coil  
Cross fin coil  
Outdoor fan  
Propeller-Direct drive  
Outdoor fan motor  
No. ✕ Motor output  
Outdoor fan air flow  
Three phase induction motor  
2 ✕ 0.09  
190  
2 ✕ 0.15  
220  
1 ✕ 0.24  
240  
2 ✕ 0.24  
480  
kW  
CMM  
CFM  
L/S  
210  
7,415  
3,000  
65  
6,711  
3,167  
65  
7,770  
3,667  
65  
8,477  
4,000  
67  
16,954  
8,000  
68  
Sound pressure level  
Protection devices  
dB(A)  
High pressure switch, freeze & frost protection, Fuse  
Over current relay (comp & indoor fan, outdoor fan)  
Internal thermostat (comp & indoor fan, outdoor fan)  
Note1.Cooling capacity is based on the following conditions.  
Indoor;27ËšCDB,19ËšCWB, Outdoor;35ËšCDB  
Cooling capacity is based 5m pipe length.  
2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.  
3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.  
4.The measuring point of the Sound pressure level is 1m from the unit surface.  
5.Specification subject to change without notice.  
- 8 -  
PEH-5,7,8MYA  
Model name  
Service  
reference  
Heat pump  
PEH-5MYA  
PEH-7MYA  
PEH-7MYA-EU  
PEH-8MYA  
PEH-5MYA-EU  
PEH-8MYA-EU  
1PH 2W220~240V 50Hz  
3PH 4W380~415V 50Hz  
3PH 4W380~415V 50Hz  
Power supply  
Indoor  
3PH 4W380~415V 50Hz 3PH 4W380~415V 50Hz  
3PH 4W380~415V 50Hz  
Outdoor  
22.0  
75,100  
18,900  
17.6  
14.4  
49,150  
12,400  
11.5  
17.9  
61,100  
15,400  
14.3  
Total cooling capacity  
kW  
Btu/h  
kcal/h  
kW  
Sensible cooling capacity  
Sensible heating capacity  
39,400  
10,000  
14.4  
48,800  
12,300  
18.8  
60,100  
15,100  
22.0  
Btu/h  
kcal/h  
kW  
Btu/h  
kcal/h  
49,150  
12,400  
64,100  
16,200  
75,100  
18,900  
Capacity step  
0-100  
R-22  
%
Refrigerant  
Refrigerant charge  
Refrigerant control  
kg  
5.0  
5.7  
6.6  
Capillary tube  
Indoor Unit  
PEH-5MYA  
PEH-7MYA  
PEH-8MYA  
Model name  
Service  
reference  
PEH-5MYA-EU  
PEH-7MYA-EU  
PEH-8MYA-EU  
External finish  
Dimension  
Galvanized steel  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
428  
650  
1,415  
70  
1,095  
60  
67  
Net weight  
Cross fin coil  
Indoor coil  
Centrifugal (Galvanized) - Direct drive  
Indoor fan  
Indoor fan motor  
Three phase induction motor  
Three phase induction motor Single phase induction motor  
kW  
No. ✕ Motor output  
1 ✕ 0.45  
1 ✕ 0.21  
1 ✕ 0.7  
CMM  
42  
60  
70  
Indoor fan air flow  
CFM  
L/S  
1,483  
700  
2,119  
1,000  
2,472  
1,167  
External static  
pressure  
mmAq  
Pa  
12.5  
125  
55  
56  
Sound pressure level  
Drain connection  
Outdoor unit  
dB(A)  
mm  
25.4  
PUH-7MYC  
PUH-5MYE  
PUH-8MYC  
PUH-8MYC1-EU(S)  
PUH-8MYE  
Model name  
Service  
reference  
PUH-5MYE-EU  
PUH-7MYC1-EU(S)  
PUH-8MYE-EU  
Acrylic resin coating  
External finish  
Color  
Munsell 5Y 8/1  
1,175  
1,000  
550  
1,175  
1,250  
550  
980  
1,400  
700  
Dimension  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
188  
214  
Net weight  
211  
150  
Hermetic line start(reciprocating)  
Compressor  
No. ✕ Motor output  
kW  
1 ✕ 3.73  
1 ✕ 5.5  
Outdoor coil  
Cross fin coil  
Outdoor fan  
Propeller-Direct drive  
Outdoor fan motor  
No. ✕ Motor output  
Outdoor fan air flow  
Three phase induction motor  
1 ✕ 0.15  
95  
2 ✕ 0.09  
167  
1 ✕ 0.35  
200  
kW  
CMM  
CFM  
L/S  
3,355  
1,583  
57  
5,898  
2,783  
65  
7,063  
3,333  
65  
Sound pressure level  
Protection devices  
dB(A)  
High pressure switch, freeze & frost protection, Fuse  
Over current relay (comp & indoor fan, outdoor fan)  
Internal thermostat (comp & indoor fan, outdoor fan)  
Note 1. Cooling and heating capacities are based on the following conditions.  
Cooling indoor; 27ËšCDB, 19ËšCWB, outdoor :35ËšCDB  
Heating indoor; 21ËšCDB,  
outdoor :7.0ËšCDB, 6.0ËšCWB  
Cooling and heating capacities are based 5m pipe length.  
2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.  
3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.  
4.The measuring point of the Sound pressure level is 1m from the unit surface.  
5.Specification subject to change without notice.  
- 9 -  
PEH-10,15,20MYA  
Model name  
Heat pump  
PEH-10MYA  
PEH-15MYA  
PEH-20MYA  
Service  
reference  
PEH-10MYA-EU  
PEH-15MYA-EU  
PEH-20MYA-EU  
Power supply  
Indoor  
3PH 4W380 ~ 415V 50Hz  
3PH 4W380 ~ 415V 50Hz  
44.0  
Outdoor  
28.8  
98,300  
24,800  
23.0  
57.6  
196,600  
49,600  
46.0  
Total cooling capacity  
kW  
Btu/h  
kcal/h  
kW  
150,200  
37,900  
35.2  
Sensible cooling capacity  
Sensible heating capacity  
78,500  
19,800  
28.8  
Btu/h  
kcal/h  
kW  
120,200  
30,200  
44.0  
157,000  
39,600  
57.6  
98,300  
24,800  
0-100  
Btu/h  
kcal/h  
150,200  
37,800  
196,600  
49,500  
Capacity step  
0-50-100  
%
R-22  
Refrigerant  
Refrigerant charge  
Refrigerant control  
kg  
9.9  
2 ✕ 6.6  
2 ✕ 9.7  
Capillary tube  
Indoor Unit  
Model name  
PEH-10MYA  
PEH-15MYA  
PEH-20MYA  
Service  
reference  
PEH-10MYA-EU  
PEH-15MYA-EU  
Galvanized steel  
PEH-20MYA-EU  
External finish  
Dimension  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
428  
706  
865  
1,615  
1,690  
180  
1,993  
212  
650  
84  
Net weight  
Cross fin coil  
Indoor coil  
Centrifugal (Galvanized) - Direct drive  
Centrifugal (Galvanized) - Belt drive  
Indoor fan  
Indoor fan motor  
Three phase induction motor  
1 ✕ 1.0  
90  
1 ✕ 2.2  
140  
1 ✕ 3.7  
180  
kW  
CMM  
No. ✕ Motor output  
Indoor fan air flow  
CFM  
L/S  
4,945  
2,333  
6,358  
3,000  
3,179  
1,500  
20  
External static  
pressure  
mmAq  
Pa  
12.5  
125  
59  
200  
61  
62  
Sound pressure level  
Drain connection  
dB(A)  
mm  
25.4  
PUH-10MYC  
PUH-10MYE  
PUH-15MYC  
PUH-20MYC  
Outdoor unit  
Model name  
Service  
reference  
PUH-10MYC1-EU(S)  
PUH-10MYE-EU  
PUH-15MYC1-EU(S)  
PUH-20MYC1-EU(S)  
Acrylic resin coating  
Munsell 5Y 8/1  
External finish  
Color  
980  
1,400  
700  
1,175  
1,250  
550  
1,200  
Dimension  
Height  
Width  
Depth  
mm  
mm  
mm  
kg  
1,951  
1,080  
240  
221  
431  
472  
Net weight  
Hermetic line start(reciprocating)  
Compressor  
No. ✕ Motor output  
kW  
1 ✕ 7.5  
2 ✕ 5.5  
2 ✕ 7.5  
Outdoor coil  
Cross fin coil  
Outdoor fan  
Propeller-Direct drive  
Outdoor fan motor  
No. ✕ Motor output  
Outdoor fan air flow  
Three phase induction motor  
2 ✕ 0.15  
190  
0.35  
200  
2 ✕ 0.35  
2 ✕ 185  
2 ✕ 6,534  
2 ✕ 3,083  
69  
kW  
CMM  
CFM  
L/S  
6,711  
3,167  
7,063  
3,333  
Sound pressure level  
Protection devices  
dB(A)  
65  
High pressure switch, freeze & frost protection, Fuse  
Over current relay (comp & indoor fan, outdoor fan)  
Internal thermostat (comp & indoor fan, outdoor fan)  
Note 1. Cooling and heating capacities are based on the following conditions.  
Cooling indoor; 27ËšCDB, 19ËšCWB, outdoor :35ËšCDB  
Heating indoor; 21ËšCDB,  
outdoor :7.0ËšCDB, 6.0ËšCWB  
Cooling and heating capacities are based 5m pipe length.  
2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.  
3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.  
4.The measuring point of the Sound pressure level is 1m from the unit surface.  
5.Specification subject to change without notice.  
- 10 -  
ELECTRICAL DATA  
PE-7~20MYC-EU  
Cooling  
PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU  
VOLT  
ITEM  
PU-7MYC1-EU  
PU-8MYC1-EU  
7.8  
PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU  
TOTAL INPUT  
kW  
A
7.2  
14.6  
-
10.1  
18.9  
74  
17.6  
29.6  
83  
22.0  
39.1  
78  
TOTAL RUN CURRENT  
POWER FACTOR  
14.2  
74  
%
A
PE-7  
240V  
START CURRENT  
74  
83  
82  
119  
140  
6.0  
10.7  
0.8  
3.2  
0.4  
0.7  
6.8  
12.3  
0.6  
1.2  
0.4  
8.6  
15.9  
1.0  
2.0  
0.5  
1.0  
2X7.65  
2X12.45  
1.7  
2X9.2  
2X15.95  
2.4  
4.8  
2X0.6  
2X1.2  
COMPRESSOR INPUT  
RUN CURRENT  
kW  
A
PE-  
8
20  
INDOOR FAN INPUT  
RUN CURRENT  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
415V  
3.5  
0.6  
1.2  
kW  
A
0.7  
TOTAL INPUT  
kW  
A
7.2  
15.9  
-
7.8  
15.5  
74  
10.1  
20.7  
74  
17.6  
32.3  
83  
22.0  
42.7  
78  
TOTAL RUN CURRENT  
POWER FACTOR  
START CURRENT  
%
A
PE-7  
220V  
81  
91  
90  
131  
152  
6.0  
11.6  
0.8  
3.5  
0.4  
0.8  
6.8  
13.4  
0.6  
1.3  
0.4  
0.8  
8.6  
17.6  
1.0  
2.1  
0.5  
1.0  
2X7.65  
2X13.65  
1.7  
2X9.2  
2X17.55  
2.4  
5.2  
2X0.6  
2X1.2  
COMPRESSOR INPUT  
RUN CURRENT  
kW  
A
PE-  
8
20  
INDOOR FAN INPUT  
RUN CURRENT  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
380V  
3.8  
0.6  
1.2  
kW  
A
- 11 -  
PEH-5,7,8MYA-EU  
Cooling  
PEH-5MYA-EU  
PEH-7MYA-EU  
PEH-8MYA-EU  
VOLT  
ITEM  
PUH-5MYE-EU  
5.5  
PUH-7MYC1-EU  
PUH-8MYC1-EU  
PUH-8MYE-EU  
7.9  
TOTAL INPUT  
kW  
A
7.2  
14.6  
-
7.8  
14.2  
76  
TOTAL RUN CURRENT  
POWER FACTOR  
9.5  
80  
69  
14.7  
75  
83  
%
A
PEH-7  
240V  
START CURRENT  
74  
83  
4.7  
8.1  
0.54  
0.9  
0.25  
0.5  
6.0  
10.7  
0.8  
3.2  
0.4  
0.7  
6.8  
12.3  
0.6  
1.2  
0.4  
0.7  
6.77  
12.3  
0.6  
1.2  
0.53  
1.2  
COMPRESSOR INPUT  
RUN CURRENT  
INDOOR FAN INPUT  
RUN CURRENT  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
PEH-  
8
20  
kW  
A
415V  
kW  
A
TOTAL INPUT  
kW  
A
5.5  
10.4  
80  
7.2  
15.9  
-
7.8  
15.5  
76  
7.9  
16.0  
75  
TOTAL RUN CURRENT  
POWER FACTOR  
START CURRENT  
%
A
PEH-7  
220V  
69  
81  
91  
91  
4.7  
8.85  
0.54  
1.0  
0.25  
0.55  
6.0  
11.6  
0.8  
3.5  
0.4  
0.8  
6.8  
13.4  
0.6  
1.3  
0.4  
0.8  
6.77  
13.4  
0.6  
1.3  
0.53  
1.3  
COMPRESSOR INPUT  
RUN CURRENT  
INDOOR FAN INPUT  
RUN CURRENT  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
PEH-  
8
20  
kW  
A
380V  
kW  
A
Heating  
PEH-5MYA-EU  
PEH-7MYA-EU  
PEH-8MYA-EU  
VOLT  
ITEM  
PUH-5MYE-EU  
4.5  
PUH-7MYC1-EU  
PUH-8MYC1-EU  
PUH-8MYE-EU  
6.6  
TOTAL INPUT  
kW  
A
6.3  
13.6  
-
6.5  
12.4  
73  
TOTAL RUN CURRENT  
POWER FACTOR  
8.5  
73  
69  
12.9  
71  
83  
%
A
PEH-7  
240V  
START CURRENT  
74  
83  
3.7  
5.1  
9.7  
0.8  
3.2  
0.4  
0.7  
5.5  
10.5  
0.6  
1.2  
0.4  
0.7  
5.47  
10.5  
0.6  
1.2  
0.53  
1.2  
COMPRESSOR INPUT  
RUN CURRENT  
INDOOR FAN INPUT  
RUN CURRENT  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
PEH-  
7.1  
0.54  
0.9  
0.25  
0.5  
8
20  
kW  
A
415V  
kW  
A
TOTAL INPUT  
kW  
A
6.3  
14.9  
-
6.5  
13.6  
73  
6.6  
14.1  
71  
4.5  
9.2  
74  
TOTAL RUN CURRENT  
POWER FACTOR  
START CURRENT  
%
A
PEH-7  
220V  
81  
91  
91  
69  
5.1  
10.6  
0.8  
3.5  
0.4  
0.8  
5.5  
11.5  
0.6  
1.3  
0.4  
0.8  
5.47  
11.5  
0.6  
1.3  
0.53  
1.3  
COMPRESSOR INPUT  
RUN CURRENT  
INDOOR FAN INPUT  
RUN CURRENT  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
3.7  
7.75  
0.54  
1.0  
0.25  
0.55  
PEH-  
8
20  
kW  
A
380V  
kW  
A
- 12 -  
PEH-10,15,20MYA-EU  
Cooling  
PEH-10MYA-EU  
PEH-15MYA-EU  
PUH-15MYC1-EU  
16.9  
PEH-20MYA-EU  
PUH-20MYC1-EU  
21.8  
VOLT  
ITEM  
PUH-10MYC1-EU  
PUH-10MYE-EU  
10.2  
19.1  
74  
TOTAL INPUT  
kW  
A
10.1  
18.9  
74  
TOTAL RUN CURRENT  
POWER FACTOR  
30.9  
76  
119  
39.3  
77  
140  
%
A
PEH-7  
240V  
START CURRENT  
82  
82  
8.57  
15.9  
1.0  
8.67  
15.9  
1.0  
2X6.77  
2X12.2  
2.3  
2X9.12  
2X16.1  
2.5  
COMPRESSOR INPUT  
RUN CURRENT  
INDOOR FAN INPUT  
RUN CURRENT  
kW  
A
PEH-  
8
20  
kW  
A
415V  
2.0  
2.0  
4.1  
4.7  
0.53  
1.0  
0.53  
1.2  
2X0.53  
2X1.2  
2X0.53  
2X1.2  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
TOTAL INPUT  
kW  
A
10.1  
20.7  
74  
10.2  
21.0  
74  
16.9  
33.7  
76  
21.8  
42.9  
77  
TOTAL RUN CURRENT  
POWER FACTOR  
START CURRENT  
%
A
PEH-7  
220V  
90  
90  
131  
152  
2X9.12  
2X17.6  
2.5  
8.57  
17.6  
1.0  
8.67  
17.6  
1.0  
2X6.77  
2X13.3  
2.3  
COMPRESSOR INPUT  
RUN CURRENT  
INDOOR FAN INPUT  
RUN CURRENT  
kW  
A
PEH-  
8
20  
kW  
A
380V  
2.1  
2.1  
4.5  
5.1  
0.53  
1.1  
0.53  
1.3  
2X0.53  
2X1.3  
2X0.53  
2X1.3  
OUTDOOR FAN INPUT  
RUN CURRENT  
kW  
A
Heating  
PEH-10MYA-EU  
PEH-15MYA-EU  
PUH-15MYC1-EU  
14.5  
PEH-20MYA-EU  
PUH-20MYC1-EU  
17.2  
VOLT  
ITEM  
PUH-10MYC1-EU  
PUH-10MYE-EU  
8.6  
TOTAL INPUT  
kW  
A
8.3  
16.0  
72  
TOTAL RUN CURRENT  
POWER FACTOR  
16.2  
72  
82  
26.9  
75  
115  
33.2  
72  
136  
%
A
PEH-7  
240V  
START CURRENT  
82  
6.77  
13.0  
1.0  
7.07  
13.0  
1.0  
COMPRESSOR INPUT  
RUN CURRENT  
kW  
A
2X5.57  
2X10.2  
2.3  
2X6.82  
2X13.05  
2.5  
PEH-  
8
20  
kW  
A
INDOOR FAN INPUT  
RUN CURRENT  
415V  
2.0  
2.0  
4.1  
4.7  
0.53  
1.0  
0.53  
1.2  
2X0.53  
2X1.2  
2X0.53  
2X1.2  
kW  
A
OUTDOOR FAN INPUT  
RUN CURRENT  
TOTAL INPUT  
kW  
A
8.3  
17.5  
72  
8.6  
17.8  
72  
14.5  
29.4  
75  
17.2  
36.3  
72  
TOTAL RUN CURRENT  
POWER FACTOR  
START CURRENT  
%
A
PEH-7  
220V  
90  
90  
126  
148  
6.77  
14.4  
1.0  
COMPRESSOR INPUT  
RUN CURRENT  
kW  
A
7.07  
14.4  
1.0  
2X5.57  
2X11.15  
2.3  
2X6.82  
2X14.25  
2.5  
PEH-  
8
20  
kW  
A
INDOOR FAN INPUT  
RUN CURRENT  
380V  
2.1  
2.1  
4.5  
5.1  
0.53  
1.1  
kW  
A
0.53  
1.3  
2X0.53  
2X1.3  
2X0.53  
2X1.3  
OUTDOOR FAN INPUT  
RUN CURRENT  
- 13 -  
SELECTION PROCEDURE  
1. Model Selection (With actual examples)  
First step, to select the approximate model:  
Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.  
Second step, to select the model:  
To select the model, the following conditions must be known:  
(1) Total cooling load or sensible cooling load  
(2) Indoor conditioned temperature (WB*1, DB)  
(3) Designed outdoor temperature (DB)*2  
(4) Designed air flow  
(5) Designed external static pressure (= Wind pressure loss of air duct)*3  
Notes:  
*1. The correct WB is required since it has a serious effect on the capacity.  
*2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest  
temperature during an air conditioning time frame is the "designed outdoor temperature". However, it is  
recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from  
the calculation to avoid selection of an excessively large capacity model.  
*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance  
is used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced  
during actual operation causing the generation of high operating sounds and carry-over of condensed water.  
(Step-1) Confirmation of operation range  
Confirm that the conditions given above for the model to be selected are within the  
operation range listed on Page 36.  
(Step-2) Calculation of actual air flow, external static pressure, and fan motor input  
Based on the designed air flow and external static pressure, obtain the actual air flow,  
actual external static pressure, and fan motor power input from the fan performance  
table for the model selected. For an explanation of how to use the fan performance  
table, see the following examples.  
Example: PE-8MYC, 50Hz  
Example 1. (To operate with values near to the designed air flow and external static pressure.)  
Condition : Designed air flow 70CMM  
Designed external static pressure 60Pa  
Calculation : The designed point is A. Therefore, duct resistance line passing A is  
Fan Performance Curve 50Hz  
Fan speed  
(rpm)  
(Pa)  
dotted line.  
450  
Recommended Range  
Therefore, actual point is B for ∆ connection  
Actual air flow = 77CMM  
400  
350  
300  
For connection  
1400  
1300  
operation line  
Actual external static pressure = 70Pa  
Notes: Duct resustance line is secondary curve.  
B
1200  
A
250  
200  
150  
100  
60Pa  
1100  
1000  
For connection  
operation line  
900  
800  
50  
0
50  
55  
60  
65  
70  
75 77 80  
Air flow (CMM)  
- 14 -  
(Step-3) Calculation of net capacity  
Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the  
actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages  
16~35). Then, calculate the net capacity from the formula below by using the fan motor input obtained  
in Step-2.  
Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW)  
OUTDOOR DBËšC  
Example: PE-8MYC  
INDOOR INDOOR  
40.0  
Condition:  
DBËšC  
26  
WBËšC  
19  
Q kW SHC kW SHF  
21.3 16.3 0.77  
T/I kW  
8.3  
Indoor conditioned temp. : 26ËšCDB, 19ËšCWB  
Designed outdoor temp. : 40ËšCDB  
Actual air flow : 77CMM  
Fan motor input : 0.6kW (See P.11)  
Calculation :  
Factor for Various Air Flow  
CMM  
L/S  
60  
70  
80  
The sections of the gross capacity table applicable  
for the above conditions are shown right.  
PE-8MYC-EU  
COOLING  
AIR VOLUME  
1,000  
1,167  
1,330  
CAPACITY  
TOTAL INPUT  
SHC  
0.976  
0.991  
0.963  
1.0  
1.0  
1.0  
1.025  
1.009  
1.044  
At 26ËšCDB, 19ËšCWB of Indoor,  
Q = 21.3, SHC = 16.3, T/I = 8.3  
Therefore, when air flow is 77(CMM)  
Q = 21.3 ✕ (1+(1.025 - 1.0) ✕ 7/10*) 21.7(kW)  
SHC = 16.3 ✕ (1+(1.044 - 1.0) ✕ 7/10*) 16.8(kW)  
T/I = 8.3 ✕ (1+(1.009-1.0))✕ 7/10*) 8.4(kW)  
Note * : 7/10 = (77-70)/(80-70)  
Therfore, the net capacity is,  
Net total cooling capacity = 21.7 (kw) - 0.6(kW)  
= 21.1 (kW)  
Net sensible cooling capacity = 16.8 (kW) - 0.6 (kW)  
= 16.2 (kW)  
2. Efficiency Calculation  
• System energy efficienty  
• Refrigerant cycle energy efficienty  
Net cooling capacity (kW)  
Compressor input (kW)  
Gross total cooling capacity (kW)  
(1) COP =  
(2) ERR =  
(1) COP =  
(2) ERR =  
Compressor input (kW)  
Net cooling capacity (kW)  
Total input (kW)  
Gross total cooling capacity (kW)  
Total input (kW)  
1kW = 3412Btu/h  
Notes: 1. COP : Coefficient of performance  
2. EER : Energy efficiency ratio  
3. Temperature condition of COP, EER (ARI Standard Ratings)  
Indoor entering air temp. : 80ËšFDB (=27ËšCDB), 66ËšFWB(=19ËšCWB)  
Outdoor entering air temp. : 95ËšFDB (=35ËšCDB)  
4. Total input = Compressor input + Indoor fan motor input + Outdoor fan motor input (page 11).  
- 15 -  
CAPACITY TABLES  
- 16 -  
- 17 -  
- 18 -  
- 19 -  
- 20 -  
- 21 -  
- 22 -  
- 23 -  
- 24 -  
- 25 -  
- 26 -  
- 27 -  
- 28 -  
- 29 -  
- 30 -  
- 31 -  
- 32 -  
- 33 -  
- 34 -  
- 35 -  
OPERATION RANGE  
The range of working temperatures is as below.  
Make sure which unit you are using and confirm the range of application.  
Cooling  
Heating (PEH only)  
50  
15  
10  
5
46  
40  
30  
20  
10  
Range for  
continuous operation  
0
Range for  
continuous operation  
- 5  
-10  
0
-5  
Range for  
-15  
continuous operation  
Use for low ambient  
cooling parts  
-10  
10  
15  
20 2425  
30  
10  
15  
20  
25 27 30  
Indoor temp.(ËšCWB)  
Indoor temp.(ËšCDB)  
Note  
Caution:  
As an applicable humidity outside standard for both indoors and outdoors, we  
recommend use within a range of 35-80% relative humidity.  
The use of your air conditioner  
outside the range of working  
temperature and humidity can  
result in serious failure.  
However, it is a condition that there is no be dewy in surfaces of electric parts.  
- 36 -  
FAN PERFORMANCE  
PE-7MYC-EU  
PEH-7MYA-EU  
PEH-5MYA-EU  
Fan Performance Curve  
50Hz  
Fan Performance Curve  
50Hz  
Fan speed  
(rpm)  
Fan speed  
(rpm)  
(Pa)  
450  
(Pa)  
450  
Recommended Range  
Recommended Range  
400  
350  
300  
400  
350  
300  
1400  
1300  
For Hi speed  
operation line  
1200  
For connection  
operation line  
250  
200  
150  
100  
250  
200  
150  
100  
1300  
1200  
For Low speed  
operation line  
1100  
1000  
900  
For connection  
operation line  
1100  
1000  
800  
50  
0
50  
0
900  
50  
800  
45  
35  
40  
55  
48 50  
55  
60  
65  
70 72 75  
Air flow (CMM)  
Air flow (CMM)  
PE-10MYC-EU  
PEH-10MYA-EU  
PE-8MYC-EU  
PEH-8MYA-EU  
Fan Performance Curve  
50Hz  
Fan Performance Curve  
Fan speed  
(rpm)  
Fan speed  
(rpm)  
50Hz  
(Pa)  
450  
(Pa)  
450  
Recommended Range  
Recommended Range  
400  
350  
300  
400  
350  
300  
For connection  
operation line  
For connection  
operation line  
1400  
1300  
1400  
1300  
1200  
1200  
250  
200  
150  
100  
250  
200  
150  
100  
1100  
1000  
For connection  
operation line  
For connection  
operation line  
1100  
1000  
900  
800  
50  
0
50  
0
800  
90  
900  
- 37 -  
60  
70  
80  
100  
50  
55  
60  
65  
70  
75  
80  
Air flow (CMM)  
Air flow (CMM)  
Airflow  
Model  
CMM  
L/S  
PE-15MYC-EU, PEH-15MYA-EU  
Total static  
pressure  
(Pa)  
PE-15MYC-EU  
PEH-15MYA-EU  
110  
1830  
768  
139.7  
5.5  
254  
10  
B45  
2.2  
898  
114.3  
4.5  
120  
130  
2170  
768  
139.7  
5.5  
140  
2330  
768  
139.7  
5.5  
150  
2500  
768  
139.7  
5.5  
160  
2670  
170  
2830  
-
-
-
-
-
2000  
FAN SPEED  
rpm  
768  
139.7  
5.5  
-
-
-
-
-
-
-
PULLEYSIZE  
(MOTOR SIDE)  
mm  
inch  
200  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
mm  
inch  
inch  
kw  
254  
10  
B45  
2.2  
254  
10  
254  
10  
254  
10  
B45  
2.2  
B45  
2.2  
B45  
2.2  
-
-
Fan Performance Curve  
50Hz  
MOTOR  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
898  
114.3  
4.5  
898  
114.3  
4.5  
898  
114.3  
4.5  
898  
114.3  
4.5  
898  
114.3  
4.5  
177.8  
7
898  
114.3  
4.5  
177.8  
(Pa)  
Recommended Range  
300  
177.8  
7
177.8  
7
177.8  
7
177.8  
7
177.8  
7
1000  
7
Fan speed  
(rpm)  
B38X2 B38X2 B38X2  
B38X2 B38X2 B38X2  
B38X2  
2.2  
971  
139.7  
5.5  
203.2  
8
B40X2  
3.7  
1067  
152.4  
MOTOR  
2.2  
942  
152.4  
6
228.6  
9
B44  
2.2  
1008  
127  
5
2.2  
942  
152.4  
6
2.2  
942  
152.4  
6
2.2  
942  
152.4  
6
2.2  
971  
139.7  
5.5  
2.2  
971  
139.7  
5.5  
203.2  
8
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1300  
800  
600  
228.6  
9
228.6  
9
228.6  
9
203.2  
8
400  
1200  
B44  
2.2  
1008  
127  
5
B44  
2.2  
1008  
127  
5
B44  
2.2  
1008  
127  
5
B40X2 B40X2  
MOTOR  
3.7  
1067  
152.4  
6
3.7  
1067  
152.4  
6
203.2  
8
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1100  
1000  
6
500  
177.8  
7
177.8  
7
177.8  
7
177.8  
7
203.2  
8
203.2  
8
B40X2  
3.7  
1119  
139.7  
5.5  
177.8  
B37X2 B37X2 B37X2  
B37X2 B40X2 B40X2  
MOTOR  
3.7  
1119  
139.7  
5.5  
177.8  
7
3.7  
1119  
139.7  
5.5  
3.7  
1119  
139.7  
5.5  
3.7  
1119  
139.7  
5.5  
3.7  
1119  
139.7  
5.5  
3.7  
1119  
139.7  
5.5  
177.8  
7
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
400  
200  
600  
700  
800  
177.8  
7
177.8  
7
177.8  
7
177.8  
7
900  
7
B38X2 B38X2 B38X2  
B38X2 B38X2 B38X2  
B38X2  
3.7  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
800  
700  
MOTOR  
3.7  
1190  
127  
5
152.4  
6
3.7  
1190  
127  
5
3.7  
1190  
127  
5
3.7  
1190  
127  
5
3.7  
-
-
3.7  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
600  
152.4  
6
152.4  
6
152.4  
6
-
-
500  
B36X2 B36X2 B36X2  
B36X2  
-
MOTOR  
3.7  
1258  
177.8  
7
203.2  
8
3.7  
3.7  
3.7  
-
0
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
110  
120  
130  
140  
150  
160  
170  
Air flow (CMM)  
standard point  
B42  
3.7  
MOTOR  
Std.  
PE-20MYC-EU  
PEH-20MYA-EU  
Airflow  
Model  
CMM  
L/S  
PE-20MYC-EU, PEH-20MYA-EU  
Total static  
pressure  
(Pa)  
150  
160  
180  
200  
3330  
692  
127  
5
220  
3670  
-
240  
4000  
2500  
627  
127  
5
279.4  
11  
2670  
627  
127  
5
279.4  
11  
3000  
692  
127  
5
FAN SPEED  
rpm  
-
-
-
-
-
-
PULLEYSIZE  
(MOTOR SIDE)  
mm  
inch  
-
-
200  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
mm  
inch  
inch  
kw  
254  
10  
254  
10  
-
-
-
Fan Performance Curve  
B44X2 B44X2 B42X2  
B42X2  
3.7  
773  
127  
5
MOTOR  
3.7  
768  
139.7  
5.5  
254  
10  
3.7  
768  
139.7  
5.5  
254  
10  
3.7  
773  
127  
5
-
-
773  
127  
5
228.6  
9
(Pa)  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
773  
127  
5
228.6  
9
Recommended Range  
1000  
Fan speed  
(rpm)  
300  
228.6  
9
228.6  
9
B43X2 B43X2 B40X2  
B40X2 B40X2 B40X2  
MOTOR  
3.7  
942  
152.4  
6
228.6  
9
3.7  
942  
152.4  
6
228.6  
9
3.7  
942  
152.4  
6
3.7  
942  
152.4  
6
3.7  
942  
152.4  
6
228.6  
9
3.7  
942  
152.4  
6
228.6  
9
1300  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
800  
600  
228.6  
9
228.6  
9
400  
1200  
B42X2 B42X2 B42X2  
B42X2 B41X2 B41X2  
MOTOR  
3.7  
1008  
127  
5
177.8  
7
3.7  
1008  
127  
5
177.8  
7
3.7  
1008  
127  
5
3.7  
1067  
152.4  
6
5.5  
1067  
152.4  
6
203.2  
8
5.5  
1067  
152.4  
6
203.2  
8
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1100  
1000  
500  
177.8  
7
203.2  
8
B37X2 B37X2 B37X2  
B39X2 B39X2 B39X2  
MOTOR  
3.7  
1119  
139.7  
5.5  
177.8  
7
3.7  
1119  
139.7  
5.5  
177.8  
7
3.7  
1119  
139.7  
5.5  
5.5  
1119  
139.7  
5.5  
5.5  
1119  
139.7  
5.5  
177.8  
7
5.5  
-
-
900  
800  
700  
600  
400  
200  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
600  
700  
800  
177.8  
7
177.8  
7
-
B37X2 B37X2 B37X2  
B37X2 B37X2  
-
MOTOR  
5.5  
1229  
152.4  
6
177.8  
7
5.5  
1229  
152.4  
6
177.8  
7
5.5  
1229  
152.4  
6
5.5  
5.5  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
1229  
152.4  
6
177.8  
7
177.8  
7
0
B38X2 B38X2 B38X2  
B38X2  
MOTOR  
5.5  
1258  
177.8  
7
203.2  
8
5.5  
1258  
177.8  
7
203.2  
8
5.5  
1258  
177.8  
7
203.2  
8
5.5  
150 160  
180  
195200  
220  
240  
FAN SPEED  
PULLEYSIZE  
(MOTOR SIDE)  
PULLEYSIZE  
(FAN SIDE)  
BELT SIZE  
rpm  
mm  
inch  
mm  
inch  
inch  
kw  
-
-
-
-
-
-
-
Air flow (CMM)  
standard point  
B41X2 B41X2 B41X2  
5.5 5.5 5.5  
MOTOR  
Std.  
- 38 -  
Pulley outside dimensions are shown below: (Unit : mm)  
(1) Shape of belt groove  
e
f
w
L0  
V-belt  
thickness  
(Reference)  
Shape of Nominal  
V-belt Dia. Ã¸P.C (Ëš  
a
)
W
L0  
K
K0  
e
f
r
1
r2  
r3  
r1  
r3  
a
Over 125  
Under 160  
34 15.86  
r
2
r
2
Over 160  
36  
38  
12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0  
1~2  
11  
16.07  
16.29  
B
Under 200  
Over 200  
Sectional plan of V-belt  
16.5mm  
40Ëš  
B type  
(2) Shape of motor pulley boss (Unit : mm)  
C
MOTOR  
CAPACITY  
(kW)  
A
B
C
+0.028  
+ 0.128  
+ 0.007  
+0.018  
2.2, 3.7  
5.5  
28  
31  
41  
8
+ 0.007  
-0.018  
+ 0.128  
+ 0.009  
+0.028  
+ 0.007  
+0.018  
-0.018  
38  
10  
- 39 -  
SOUND DATA  
Indoor units  
Sound Levels  
OCTAVE BAND FREQ. Hz  
PWL  
SPL  
MODEL  
dB(A)  
dB(A)  
63Hz  
60.5  
125Hz  
57.5  
250Hz  
57.5  
500Hz  
52.5  
1000Hz  
50.5  
2000Hz  
43  
4000Hz  
34.5  
8000Hz  
28.5  
PEH-5MYA-EU  
63  
55  
PE-7MYC-EU  
PEH-7MYA-EU  
PE-8MYC-EU  
PEH-8MYA-EU  
PE-10MYC-EU  
PEH-10MYA-EU  
PE-15MYC-EU  
PEH-15MYA-EU  
PE-20MYC-EU  
PEH-20MYA-EU  
62  
63  
62  
25  
32  
60  
61  
54  
55  
53  
54  
50  
51  
42.5  
43.5  
48  
37  
38  
31.5  
32.5  
36  
63  
64  
67  
69  
70  
55  
56  
59  
61  
62  
62.5  
40  
58.5  
47  
59.5  
52  
53  
43.5  
52  
36.5  
51  
55  
57.5  
57.5  
44  
49  
53.5  
56.5  
53  
Outdoor units  
Sound Levels  
OCTAVE BAND FREQ. Hz  
PWL  
SPL  
MODEL  
dB(A)  
dB(A)  
63Hz  
68  
125Hz  
58  
250Hz  
57  
500Hz  
52.5  
1000Hz  
52  
2000Hz  
47.5  
4000Hz  
49  
8000Hz  
40  
68  
57  
65  
65  
PUH-5MYE-EU  
PU-7MYC1-EU  
PUH-7MYC1-EU  
PU-8MYC1-EU  
PUH-8MYC1-EU  
76  
62  
62  
63.5  
63.5  
62  
62  
62  
62  
60  
60  
57.5  
57.5  
54  
54  
54  
54  
76  
76  
76  
65  
65  
PUH-8MYE-EU  
45.4  
64.5  
58  
65  
58  
64  
58.5  
62.5  
61  
60  
60  
57  
51.5  
54.5  
47  
53  
PU-10MYC1-EU  
PUH-10MYC1-EU  
45.4  
68  
58  
72  
69  
51  
51  
58  
70  
58.5  
65  
61  
60  
62  
65  
65  
60  
57  
59  
64  
64  
51.5  
53  
47  
76  
78  
79  
80  
80  
65  
67  
68  
69  
69  
PUH-10MYE-EU  
PU-15MYC1-EU  
49.5  
53  
PU-20MYC1-EU  
66  
70.5  
59  
65  
56.5  
55  
43  
64  
50.5  
51.5  
PUH-15MYC1-EU  
PUH-20MYC1-EU  
43  
59  
64.5  
55.5  
Position mesurement  
Indoor unit  
Outdoor unit  
PE(H)  
PU(H)  
1m  
Service  
panel side  
Inlet  
Outlet  
1m  
1m  
- 40 -  
OUTLINE DIMENSIONS  
PEH-5  
POWER SUPPLY  
104  
135 66  
782  
130 130 130 130 130  
34  
66  
CABLE ENTRY ø27  
HOLES:18-ø3.1  
(Bottom side)  
CONTROL  
CABLE ENTRY ø27  
(Bottom side)  
AIR INLET DUCT  
FLANGE  
105 40  
OPTIONAL PARTS  
CABLE ENTRY ø27  
(Bottom side)  
960  
20  
20  
CONTROL BOX  
HOLES:14-ø3.1  
HOLES:4-ø12  
55  
130 130 130  
55  
AIR OUTLET DUCT  
FLANGE  
1095  
1000  
920  
650  
530  
50  
15  
70  
40  
40  
15  
210  
500  
210  
REFRIGERANT  
PIPE ø19.05  
(3/4)  
REFRIGERANT  
PIPE ø12.7  
(1/2)  
AIR OUTLET  
AIR INLET  
944  
33  
562  
DRAIN:RC1  
PE(H)-7,8  
104  
1102  
34  
31  
HOLES:24- 3.1  
POWER SUPPLY  
CABLE ENTRY 27  
135 31  
130 130 130 130 130 130 130 130  
(Bottom side)  
CONTROL  
CABLE ENTRY 27  
(Bottom side)  
AIR INLET DUCT  
FLANGE  
40  
105  
OPTIONAL PARTS  
CABLE ENTRY 27  
(Bottom side)  
1280  
20  
20  
CONTROL BOX  
HOLES:22- 3.1  
HOLES:4- 12  
45  
130 130 130 130 130 130 130  
45  
AIR OUTLET DUCT  
FLANGE  
1415  
1320  
1240  
1000  
650  
530  
50  
15  
70  
40  
40  
15  
120  
120  
REFRIGERANT PIPE  
25.4  
(1)  
REFRIGERANT PIPE  
15.88  
(5/8)  
AIR  
AIR  
OUTLET  
INLET  
562  
33  
1264  
DRAIN:Rc1  
- 41 -  
PE(H)-10  
104  
1302  
34  
POWER SUPPLY  
CABLE ENTRY 27  
(Bottom side)  
HOLES:26- 3.1  
66 130 130 130 130 130 130 130 130 130 66  
135  
105  
AIR INLET DUCT  
FLANGE  
40  
CONTROL  
CABLE ENTRY 27  
(Bottom side)  
OPTIONAL PARTS  
CABLE ENTRY 27  
(Bottom side)  
1480  
20  
20  
CONTROL BOX  
HOLES:22- 3.1  
45  
130 130 130 130 130 130 130  
45  
HOLES:4- 12  
AIR OUTLET DUCT  
FLANGE  
1615  
1520  
650  
530  
70  
50  
40  
40  
1440  
1000  
220  
220  
15  
15  
REFRIGERANT PIPE  
28.6  
(1-1/8)  
REFRIGERANT PIPE  
15.88  
(5/8)  
AIR  
OUTLET  
AIR  
INLET  
1464  
33  
562  
DRAIN:Rc 1  
PE(H)-15  
1690  
1418  
1300=130X10  
HOLES:34- 3.1  
70 120  
49  
AIR INLET DUCT  
FLANGE  
59  
59  
130  
POWER SUPPLY  
CABLE ENTRY 27  
(BOTTOM SIDE)  
CONTROL  
CABLE ENTRY 27  
(BOTTOM SIDE)  
REFRIGERANT  
PIPE 15.88 (5/8)  
REFRIGERANT  
PIPE 25.4 (1)  
25  
25  
OPTIONAL PARTS  
1637  
HOLES:4- 12  
CABLE ENTRY 27  
REFRIGERANT  
PIPE 15.88 (5/8)  
CONTROL BOX  
REFRIGERANT  
PIPE 25.4 (1)  
34  
130  
81  
AIR OUTLET DUCT  
FLANGE  
46  
46  
910=130X7  
1002  
HOLES:24- 3.1  
484  
101  
VIEW A  
865  
746  
69  
50  
15  
15  
AIR OUTLET  
AIR INLET  
AIR OUTLET  
AIR INLET  
A
1587  
50  
50  
DRAIN: Rc1  
- 42 -  
PE(H)-20  
1993  
1648  
1560=130X12  
HOLES:38- 3.1  
70 193  
49  
AIR INLET DUCT  
FLANGE  
44  
44  
130  
POWER SUPPLY  
CABLE ENTRY  
(BOTTOM SIDE)  
27  
CONTROL  
CABLE ENTRY 27  
(BOTTOM SIDE)  
REFRIGERANT  
PIPE 15.88 (5/8)  
REFRIGERANT  
PIPE 28.6  
25  
1940  
OPTIONAL PARTS  
CABLE ENTRY 27  
25  
(1-1/8)  
HOLES:4- 12  
REFRIGERANT  
PIPE 15.88 (5/8)  
CONTROL BOX  
REFRIGERANT  
PIPE 28.6 (1-1/8)  
130  
AIR OUTLET DUCT  
FLANGE  
44  
81  
21  
1170=130X9  
1212  
21  
142  
HOLES:28- 3.1  
536  
865  
746  
VIEW A  
50  
69  
50  
15  
15  
AIR OUTLET  
AIR INLET  
AIR OUTLET  
AIR INLET  
A
1890  
50  
50  
DRAIN:Rc 1  
- 43 -  
PUH-5  
AIR INLET  
AIR INLET  
Holes :4-12X20  
AIR OUTLET  
21  
1040  
1000  
21  
550  
SERVICE PANEL  
131  
126  
REFRIGERANT PIPE  
ø12.7 (1/2)  
CABLE ENTRY  
Holes : 2-ø15  
21  
REFRIGERANT PIPE  
ø19.05(3/4)  
Hole : ø15  
275  
275  
18  
75  
400  
75  
PU(H)-7,8,10  
(Upper blow)  
AIR INLET  
AIR INLET  
200  
1000  
CABLE ENTRY 25X40  
AIR OUTLET  
350  
700  
Holes: 4-12X20  
SERVICE PANEL  
REFRIGERANT PIPE  
ø15.88 (5/8)  
AIR INLET  
120  
REFRIGERANT PIPE  
PU(H)- 7,8:ø25.4(1)  
PU(H)- 10:ø28.6(1-1/8)  
34  
18  
108  
160  
25  
1400  
25  
540  
700  
25  
25  
- 44 -  
PUH-8,10  
(Side blow)  
AIR INLET  
AIR INLET  
Holes : 4-12X20  
21  
1290  
1250  
21  
AIR OUTLET  
550  
SERVICE PANEL  
REFRIGERANT PIPE  
ø15.88(5/8)  
130  
CABLE ENTRY  
44  
49  
56  
REFRIGERANT PIPE  
PUH-8:ø25.4(1)  
PUH-10:ø28.6(1-1/8)  
Hole : ø15  
Holes : 2-ø15  
275  
275  
75  
400  
75  
PU-15  
AIR INLET  
AIR INLET  
AIR INLET  
998  
AIR OUTLET  
998  
HOLES: 4-Uø15  
SERVICE PANEL  
REFRIGERANT PIPE  
ø15.88(5/8)  
REFRIGERANT PIPE  
ø25.4(1)  
No.1  
No.2  
78  
CONTROL  
169  
242  
CABLE ENTRY ø27  
50  
137  
721  
137  
POWER SUPPLY  
CABLE ENTRY ø43  
- 45 -  
PU-20  
AIR INLET  
AIR INLET  
AIR INLET  
HOLES: 6-ø15  
No.1  
No.2  
2036  
17  
17  
REFRIGERANT PIPE  
ø28.6(1-1/8)  
REFRIGERANT PIPE  
ø15.88(5/8)  
1996  
AIR OUTLET  
998  
SERVICE PANEL  
CONTROL  
CABLE ENTRY ø27  
POWER SUPPLY  
CABLE ENTRY ø47  
213 80  
392  
756475  
PUH-15,20  
Holes : 4-12X20  
27  
2005  
994  
27  
830  
478.5  
CONTROL BOX  
SERVICE PANEL  
REFRIGERANT PIPE  
ø15.88 (5/8)  
REFRIGERANT PIPE  
PUH-15:ø25.4(1)  
PUH-20:ø28.6(1-1/8)  
No.2  
No.1  
68  
25  
911  
128  
1080  
54  
1951  
2059  
54  
- 46 -  
Note: In the case of installation are shown below, it is possible to use the unit by connecting the duct.  
However, the pressure loss must be 30Pa (3mmAg) or less.  
Duct work is local supply.  
DUCT  
DUCT  
- 47 -  
WIRING DIAGRAMS  
PE-7MYC-EU (STANDARD)  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
C4  
1
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
PU-7MYC1-EU  
N
BLUE  
2
3
1
2
3
WHITE  
BLACK  
RED  
WHITE  
BLACK  
F3(3.15A)  
MF2  
MF3  
PE  
WHITE  
BLACK  
49C  
C5  
52C  
51F2  
TB5  
15  
63H  
GRAY  
51C  
CZ2  
CZ2  
CH  
30  
CZ  
CR2  
14  
52C  
30  
CZ  
JUMPER  
Power supply, Single Phase  
TB4  
C1  
TB2  
L
TB4  
5
RED  
1
2
50Hertz  
51F1  
220 240Volt,  
52F  
C1  
RED  
5
6
Hi  
6
7
BROWN  
C
MF1  
Low  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
PE-7MYC-EU  
N
SW2(FIELD SUPPLY)  
BLUE  
BLUE  
4
TB4  
52F  
F1  
(3.15A)  
GRAY  
1
RED  
SWITCH BOX  
(FIELD SUPPLY)  
CZ1  
PE  
TB3 15  
F2  
51F1  
(3.15A)  
15  
23WA  
C3  
1
OUTDOOR  
26L  
SW1  
C3  
3
Tr  
FZ  
CZ2  
AC  
AC  
24V  
220  
240V  
2
3
TB4  
30FZ  
CR1  
CZ1  
14  
14  
52F  
30  
FZ  
FZ  
GRAY  
4
BLUE  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Please remove the jumper wire ( Mark) in the above  
diagram if you use the Switch <SW2> at local.  
If the Switch <SW2> is not used, the Fan motor  
(indoor) drives at high speed.  
TB1  
F1  
5
Crankcase heater  
Fuse (3.15A)  
6.Specification subject to change without notice.  
3
Caution,  
Transformer  
Internal thermostat  
Over current relay  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
(compressor)  
(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (on)  
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
Run capacitor  
26L  
Option controller connection.  
PAC-204RC (Option)  
terminal no.  
CZ1, 2  
30CZ, FZ  
Symbol No. Function  
1
2
3
4
Power (Active)  
Cooling operation  
Fan operation  
24VAC(L)  
COMP  
FAN HI  
24VAC(N)  
TB4  
Power (Neutral)  
C
C1, 3 ~ 5  
CR1, 2  
Connector  
Surge killer  
- 48 -  
PE-8,10MYC-EU (STANDARD)  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
C4  
1
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
PU-8, 10MYC1-EU  
N
2
3
1
2
3
WHITE  
BLACK  
RED  
BLUE  
WHITE  
BLACK  
F3(3.15A)  
MF2  
MF3  
PE  
WHITE  
BLACK  
49C  
C5  
52C  
51F2  
TB5  
15  
63H  
GRAY  
51C  
CZ2  
CZ2  
CH  
30  
CZ  
CR2  
14  
52C  
30  
CZ  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB2  
L1  
51F1  
52F  
C1  
C2  
RED  
1
RED  
1
2
3
RED  
2
3
WHITE  
BLUE  
WHITE  
BLUE  
WHITE  
BLACK  
L2  
L3  
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
F1(3.15A)  
RED  
PE-8,10MYC-EU  
N
51F1  
52F  
TB4  
1
GRAY  
C1  
4
SWITCH BOX  
(FIELD SUPPLY)  
PE  
CZ1  
TB3 15  
49F  
C1  
5
F2  
(3.15A)  
15  
C3  
1
23WA  
OUTDOOR  
26L  
C3  
3
Tr  
SW1  
CZ2  
FZ  
AC  
220  
240V  
AC  
24V  
CR1  
2
3
30FZ  
TB4  
14  
14  
52F  
CZ1  
30  
FZ  
FZ  
GRAY  
4
BLUE  
Attach the accessory  
Remove  
C1  
C2  
1
2
3
1
2
3
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
1
2
3
MF1  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
TB1  
5
Crankcase heater  
Fuse (3.15A)  
Transformer  
Internal thermostat  
Internal thermostat  
Over current relay  
Note:1.The dotted lines show field wiring.  
F1  
3
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
(indoor fan)  
(compressor)  
(compressor)  
49F  
5.Specification subject to change without notice.  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
26L  
CZ1, 2  
30CZ, FZ  
Option controller connection.  
PAC-204RC (Option)  
C1~5  
CR1, 2  
Symbol No. Function  
terminal no.  
1
2
3
4
Power (Active)  
Cooling operation  
Fan operation  
24VAC(L)  
COMP  
FAN HI  
24VAC(N)  
TB4  
Power (Neutral)  
- 49 -  
PE-15MYC-EU (STANDARD)  
TB1  
L1  
OUTDOOR UNIT  
52C1  
51C1  
RED  
RED  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
RED  
L2  
L3  
WHITE  
BLACK  
WHITE  
BLACK  
MC1  
MF2  
WHITE  
BLACK  
52F2  
51F2  
C1  
N
1
2
3
BLUE  
RED  
RED  
52C2  
51C2  
WHITE  
BLACK  
WHITE  
BLACK  
PE  
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
WHITE  
BLACK  
WHITE  
BLACK  
MC2  
PU-15MYC1-EU ---100A  
F3 (3.15A)  
51  
F2  
52  
C1  
52  
C2  
49C1  
51C1  
49C2  
51C2  
TB4  
52  
C1  
52  
C2  
11 12  
GRAY  
CZ  
2-1  
63H1  
63H2  
30  
CH1 CH2  
CZ  
2-2  
2
30  
CZ1  
CZ2-1  
CR3  
CZ2-2  
CR2  
CZ2  
52  
C1  
52  
C2  
52  
F2  
2
13  
30  
30  
CZ2  
CZ1  
TB2  
51F1  
52F1  
INDOOR UNIT  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
L1  
L2  
L3  
RED  
WHITE  
BLACK  
MF1  
BLUE  
N
F1  
52F1  
(3.15A)  
1
PE  
GRAY  
TB3  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
PE-15MYC-EU ---30A  
C3  
1
CZ CZ  
1-1 1-2  
SWITCH BOX (FIELD SUPPLY)  
26L1  
F2  
(3.15A)  
C3  
3
TB3  
Tr  
C8  
1
OUTDOOR  
11 12  
11 12  
AC  
26L2  
AC  
220  
24V  
240V  
C8  
3
23  
WA  
23  
WA  
SW1  
FZ  
CZ  
2-1  
CZ  
2-2  
30  
FZ  
CR1  
3
4
2
52  
F1  
TB3  
30  
FZ  
CZ  
CZ  
1-2  
13  
FZ  
1-1  
GRAY  
13  
5
Symbol  
MC1,2  
MF1  
Name  
Note:1.The dotted lines show field wiring.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
MF2  
5.Specification subject to change without notice.  
52C1,2  
52F1  
52F2  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
TB1  
CH1,2  
F1  
Tr  
4
current, Over current relays <51C1,2>, <51F1,2,3> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
3
49C1,2  
51C1,2  
51F1  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
51F2  
Option controller connection.  
63H1,2  
26L1,2  
FZ  
PAC-204RC (Option)  
Symbol No. Function  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
terminal no.  
1
2
3
4
5
Power (Active)  
Cooling operation  
Cooling operation  
Fan operation  
24VAC(L)  
COMP1  
COMP2  
FAN HI  
30FZ  
Auxiliary relay (fan)  
TB3  
CZ1-1,2/2-1,2 Auxiliary relay  
30CZ1,2  
<SW1>  
<23WA>  
C1, 3, 8  
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
Power (Neutral)  
24VAC(N)  
CR1  
2
3
Timer  
- 50 -  
PE-20MYC-EU (STANDARD)  
TB1  
OUTDOOR UNIT  
51C1  
51C2  
52C1  
52C2  
52F2  
L1  
L2  
L3  
RED  
RED  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
MC1  
MC2  
WHITE  
BLACK  
N
BLUE  
RED  
RED  
PE  
WHITE  
BLACK  
WHITE  
BLACK  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PU-20MYC1-EU---125A  
51F2  
51F3  
C1  
C2  
1
2
3
RED  
RED  
(3.15A)  
F3  
WHITE  
BLACK  
WHITE  
BLACK  
MF2  
MF3  
1
2
3
RED  
RED  
49C1  
49C2  
52  
52  
WHITE  
BLACK  
WHITE  
BLACK  
C1 C2  
51  
F2  
51  
F3  
52  
C1  
52  
C2  
63H1  
51C1  
63H2  
51C2  
TB4  
11 12  
GRAY  
CH1 CH2  
2
CZ  
2-1  
30  
CZ1  
30  
CZ2  
CZ2-1  
52  
CR3  
CZ2-2  
CR2  
CZ  
2-2  
52  
F2  
52  
2
C1  
C2  
30  
30  
CZ2  
CZ1  
13  
TB2  
51F1  
52F1  
INDOOR UNIT  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
L1  
L2  
L3  
RED  
WHITE  
BLACK  
MF1  
52F1  
BLUE  
N
F1  
(3.15A)  
1
PE  
GRAY  
TB3  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
PE-20MYC-EU---30A  
C3  
1
CZ CZ  
1-1 1-2  
SWITCH BOX (FIELD SUPPLY)  
26L1  
F2  
(3.15A)  
C3  
3
TB3  
Tr  
C8  
1
OUTDOOR  
11 12  
11 12  
AC  
26L2  
AC  
220  
C8  
3
24V  
240V  
23  
23  
WA  
SW1  
FZ  
WA  
CZ  
2-1  
CZ  
2-2  
30  
FZ  
CR1  
3
4
2
52  
F1  
TB3  
30  
FZ  
CZ  
CZ  
1-2  
13  
FZ  
1-1  
5
GRAY  
13  
Symbol  
MC1,2  
MF1  
MF2,3  
52C1,2  
52F1  
Name  
Note:1.The dotted lines show field wiring.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
Caution,  
52F2  
TB1  
1.To protect each Fan motor and Compressor from abnormal  
4
current, Over current relays <51C1,2>, <51F1,2,3> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
CH1,2  
F1  
Tr  
3
49C1,2  
51C1,2  
51F1,2  
51F2,3  
63H1,2  
26L1,2  
FZ  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
2
3
4
5
Power (Active)  
Cooling operation  
Cooling operation  
Fan operation  
24VAC(L)  
COMP1  
COMP2  
FAN HI  
30FZ  
Auxiliary relay (fan)  
TB3  
CZ1-1,2/2-1,2 Auxiliary relay  
30CZ1,2  
<SW1>  
<23WA>  
C1~3, 8  
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Power (Neutral)  
24VAC(N)  
CR1  
2
3
Surge killer  
Timer  
- 51 -  
PE-7MYC-EU  
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
C4  
C5  
F3(3.15A)  
1
2
3
1
2
3
RED  
RED  
PU-7MYC1-EU  
N
BLUE  
WHITE  
BLACK  
RED  
WHITE  
BLACK  
MF2  
MF3  
PE  
49C  
WHITE  
BLACK  
TB5  
15  
52C  
GRAY  
51F2  
63H  
CZ2  
51C  
CZ2  
14  
CH  
30  
CZ  
CR2  
52C  
30  
CZ  
JUMPER  
Power supply, Single Phase  
50Hertz  
TB4  
C1  
TB2  
L
TB4  
5
1
2
RED  
51F1  
220 240Volt,  
52F  
C1  
RED  
5
6
Hi  
6
7
BROWN  
BLUE  
C
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
Low  
PE-7MYC-EU  
SW2(FIELD SUPPLY)  
4
N
BLUE  
F1  
TB4  
52F  
(3.15A)  
GRAY  
1
RED  
SWITCH BOX  
(FIELD SUPPLY)  
CZ1  
PE  
51F1  
F2  
(3.15A)  
TM  
(3MIN)  
C3  
1
TB3  
23WA  
15  
26L  
15  
OUTDOOR  
SW1  
Tr  
C3  
3
FZ  
AC  
220  
240V  
CZ2  
AC  
24V  
2
3
TB4  
30FZ  
TM  
CR1  
CZ1  
14  
14  
52F  
30  
FZ  
FZ  
GRAY  
4
BLUE  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Please remove the jumper wire ( Mark) in the above  
diagram if you use the Switch <SW2> at local.  
If the Switch <SW2> is not used, the Fan motor  
(indoor) drives at high speed.  
TB1  
F1  
5
6.When PAC-204RC is used, Timer(TM)is unneccessary.  
7.Specification subject to change without notice.  
3
(compressor)  
(compressor)  
Internal thermostat  
Over current relay  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (on)  
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
Run capacitor  
26L  
CZ1, 2  
30CZ, FZ  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
2
3
4
Power (Active)  
Cooling operation  
Fan operation  
24VAC(L)  
COMP  
FAN HI  
24VAC(N)  
TB4  
C
Power (Neutral)  
C1, 3~5  
CR1, 2  
TM  
Connector  
Surge killer  
Timer (Anti short cycle)  
- 52 -  
PE-8,10MYC-EU  
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
C4  
1
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
PU-8, 10MYC1-EU  
BLUE  
N
2
3
1
2
3
WHITE  
BLACK  
RED  
WHITE  
BLACK  
F3(3.15A)  
MF2  
MF3  
PE  
WHITE  
BLACK  
49C  
C5  
52C  
51F2  
TB5  
15  
63H  
GRAY  
51C  
CZ2  
CZ2  
CH  
30  
CZ  
CR2  
14  
52C  
30  
CZ  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
51F  
52F  
C1  
C2  
1
RED  
RED  
1
2
3
RED  
2
3
WHITE  
BLUE  
WHITE  
BLUE  
L2  
L3  
WHITE  
BLACK  
MF1  
1
F3(3.15A)  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
PE-8, 10MYC-EU  
RED  
N
TB4  
52F  
GRAY  
51F1  
SWITCH BOX  
(FIELD SUPPLY)  
CZ1  
PE  
C1  
4
F2  
(3.15A)  
49F  
TM  
(3MIN)  
C1  
5
23WA  
TB3  
15  
C3  
1
OUTDOOR  
15  
26L  
SW1  
Tr  
C3  
3
FZ  
CZ2  
AC  
24V  
AC  
220  
CR1 240V  
TM  
30FZ  
TB4  
2
3
14  
14  
52F  
CZ1  
30  
FZ  
FZ  
GRAY  
4
BLUE  
Attach the accessory  
Remove  
C1  
C2  
1
2
3
1
2
3
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
1
2
3
MF1  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
TB1  
F1  
5
Note:1.The dotted lines show field wiring.  
3
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Transformer  
(indoor fan)  
(compressor)  
(compressor)  
Internal thermostat  
Internal thermostat  
Over current relay  
49F  
5.When PAC-204RC is used, Timer(TM)is unneccessary.  
6.Specification subject to change without notice.  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
26L  
CZ1, 2  
30CZ, FZ  
Option controller connection.  
PAC-204RC (Option)  
terminal no.  
C1~ 5  
CR1, 2  
TM  
Symbol No. Function  
1
2
3
4
Power (Active)  
Cooling operation  
Fan operation  
24VAC(L)  
Timer (Anti short cycle)  
COMP  
FAN HI  
24VAC(N)  
TB4  
Power (Neutral)  
- 53 -  
PE-15MYC-EU  
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)  
OUTDOOR UNIT  
TB1  
52C1  
51C1  
RED  
RED  
L1  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC1  
MF2  
WHITE  
BLACK  
51F2  
52F2  
C1  
N
1
2
3
RED  
RED  
52C2  
51C2  
BLUE  
WHITE  
BLACK  
WHITE  
BLACK  
PE  
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
WHITE  
BLACK  
WHITE  
BLACK  
MC2  
PU-15MYC1-EU ··· 100A  
F3(3.15A)  
51  
F2  
49C1  
51C1  
52  
C1  
52  
C2  
49C2  
51C2  
CZ2-2  
CZ2-1  
TB4  
52  
52  
TM  
(3min)  
C1 C2  
11 12  
GRAY  
52  
C2  
TM  
(3min)  
52  
C1  
52  
C2  
52  
C1  
CZ  
2-1  
63H1  
63H2  
CH1 CH2  
CZ  
2-2  
2(2sec)  
CR3  
30  
CZ1  
30  
CZ2  
CR2  
CZ2-1  
52  
CZ2-2  
52  
C2  
52  
F2  
2
TM  
C1  
13  
30  
CZ1  
30  
CZ2  
TB2  
51F1  
52F1  
INDOOR UNIT  
L1  
L2  
L3  
RED  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
WHITE  
BLACK  
MF1  
N
BLUE  
F1  
52F1  
(3.15A)  
1
GRAY  
PE  
TB3  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
CZ  
1-1  
CZ  
1-2  
C3  
1
PE-15MYC-EU ··· 30A  
SWITCH BOX (FIELD SUPPLY)  
26L1  
F2  
(3.15A)  
C3  
3
TB3  
Tr  
AC  
C8  
1
OUTDOOR  
11  
12  
12  
26L2  
AC  
24V  
220~  
240V  
11  
C8  
3
23  
WA  
23  
WA  
SW1  
FZ  
CZ  
2-1  
CZ  
2-2  
30  
FZ  
CR1  
3
4
2
52  
F1  
TB3  
30  
FZ  
CZ  
1-1  
CZ  
1-2  
13  
FZ  
GRAY  
5
13  
Symbol  
Name  
MC1,2  
MF1  
MF2  
52C1,2  
52F1  
52F2  
TB1~4  
CH1,2  
F1~3  
Tr  
49C1,2  
51C1,2  
51F1  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.When PAC-204RC is used, Timer(TM)is unneccessary.  
6.Specification subject to change without notice.  
Caution,  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,  
do not change factory set value of Over current relays.  
2.To protect the starting Compressor<MC1,2>at the same time, Timer  
<2> is installed. Therefore, do not change factory set value of this Timer.  
3.To protect the starting Compressor<52C1,2>frequently, Timer  
<TM> is installed. Therefore, do not change factory set value of this Time  
51F2  
63H1,2  
26L1,2  
FZ  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
30FZ  
Auxiliary relay (fan)  
CZ1-1,2/2-1,2 Auxiliary relay  
Option controller connection.  
30CZ1,2  
<SW1>  
<23WA>  
C1, 3, 8  
CR1~3  
2
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
24VAC(L)  
1
2
3
4
5
Power (Active)  
Cooling operation  
Cooling operation  
Fan operation  
COMP1  
COMP2  
FAN HI  
TB3  
Timer  
TM  
Timer (Anti short cycle.)  
Power (Neutral)  
24VAC(N)  
- 54 -  
PE-20MYC-EU  
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)  
OUTDOOR UNIT  
TB1  
52C1  
51C1  
51C2  
RED  
RED  
L1  
L2  
L3  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
MC1  
MC2  
WHITE  
BLACK  
BLUE  
N
52C2  
RED  
RED  
PE  
WHITE  
BLACK  
WHITE  
BLACK  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PU-20MYC1-EU ··· 125A  
52F2  
51F2  
51F3  
C1  
1
RED  
WHITE  
BLACK  
RED  
F3(3.15A)  
2
3
WHITE  
BLACK  
MF2  
MF3  
C2  
1
2
3
RED  
WHITE  
BLACK  
RED  
WHITE  
BLACK  
49C1  
49C2  
52 52  
C1 C2  
CZ2-2  
CZ2-1  
51  
F2  
51  
F3  
52  
52  
TM  
(3min)  
C1  
C2  
63H1  
51C1  
63H2  
51C2  
52  
C2  
TM  
(3min)  
52  
52  
TB4  
C1  
C2  
52  
C1  
11 12  
GRAY  
CH1 CH2  
2(2sec)  
CR3  
CZ  
2-1  
30  
CZ1  
30  
CR2  
CZ2-1  
52  
CZ2-2  
CZ  
2-2  
CZ2  
52  
52  
F2  
2
TM  
C1  
C2  
30  
30  
CZ2  
CZ1  
13  
TB2  
51F1  
52F1  
INDOOR UNIT  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
L1  
L2  
L3  
RED  
WHITE  
BLACK  
MF1  
N
BLUE  
F1  
(3.15A)  
52F1  
1
GRAY  
PE  
TB3  
51F1  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PE-20MYC-EU ··· 30A  
CZ  
1-1  
CZ  
1-2  
C3  
1
SWITCH BOX (FIELD SUPPLY)  
26L1  
F2  
C3  
3
(3.15A)  
TB3  
Tr  
AC  
C8  
1
OUTDOOR  
11  
11  
12  
12  
26L2  
AC  
24V  
220~  
240V  
C8  
3
SW1  
23  
WA  
23  
WA  
FZ  
CZ  
2-1  
CZ  
2-2  
30  
FZ  
CR1  
3
4
2
52  
F1  
TB3  
30  
FZ  
CZ  
CZ  
1-2  
13  
FZ  
1-1  
GRAY  
5
13  
Symbol  
MC1,2  
MF1  
MF2,3  
52C1,2  
52F1  
Name  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
52F2  
5.When PAC-204RC is used, Timer(TM)is unneccessary.  
6.Specification subject to change without notice.  
TB1~4  
CH1,2  
F1~3  
Caution,  
Tr  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,  
do not change factory set value of Over current relays.  
49C1,2  
51C1,2  
51F1  
2.To protect the starting Compressor <MC1,2>at the same time, Timer  
<2> is installed. Therefore, do not change factory set value of this Time  
3.To protect the starting Compressor<52C1,2> frequently, Timer  
<TM> is installed. Therefore, do not change factory set value of this Ti  
51F2,3  
63H1,2  
26L1,2  
FZ  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
30FZ  
Auxiliary relay (fan)  
CZ1-1,2/2-1,2 Auxiliary relay  
Option controller connection.  
30CZ1,2  
<SW1>  
<23WA>  
C1~3, 8  
CR1~3  
2
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
Timer  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
24VAC(L)  
COMP1  
COMP2  
FAN HI  
1
2
3
4
5
Power (Active)  
Cooling operation  
Cooling operation  
Fan operation  
TB3  
TM  
Timer (Anti short cycle.)  
Power (Neutral)  
24VAC(N)  
- 55 -  
PE-7MYC-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
Power supply,  
3Phase  
TB1  
L1  
52C  
51C  
380 415Volt,50Hertz  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
52F3  
51F2  
C4  
C6  
2
F3(3.15A)  
WHITE  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
1
2
3
RED  
RED  
PU-7MYC1-EU  
N
BLUE  
WHITE  
BLACK  
BLACK  
RED  
3
1
WHITE  
BLACK  
MF2  
49C  
PE  
52F2  
51F2  
1
23C  
5
52C  
C4  
4
TB5  
3
15  
52F4  
49F  
GRAY  
1
RED  
H
C4  
5
2
3
WHITE  
BLACK  
MF3  
63H  
CZ2  
52  
F3  
52  
F2  
C5  
51C  
CZ2  
52F3  
52F2  
52F4  
CR2  
CH  
14  
30  
CZ  
52C  
30  
CZ  
JUMPER  
Power Supply, Single Phase  
220 240Volt,50Hertz  
TB4  
C1  
TB2  
L
TB4  
5
1
2
RED  
51F1  
52F1  
C1  
RED  
5
Hi  
6
7
BROWN  
BLUE  
C
6
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
Low  
PE-7MYC-EU  
4
N
SW2(FIELD SUPPLY)  
BLUE  
F1  
TB4  
(3.15A)  
52F1  
GRAY  
1
RED  
SWITCH BOX  
CZ1  
(FIELD SUPPLY)  
PE  
TB3 15  
51F1  
F2  
(3.15A)  
C3  
1
15  
23WA  
OUTDOOR  
26L  
SW1  
C3  
3
Tr  
FZ  
CZ2  
AC  
24V  
AC  
220  
2
3
240V  
TB4  
30FZ  
CR1  
CZ1  
14  
14  
52F1  
30  
FZ  
FZ  
GRAY  
4
BLUE  
Note:1.The dotted lines show field wiring.  
Compressor motor  
Fan motor (indoor)  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Please remove the jumper wire ( Mark) in the above  
diagram if you use the Switch <SW2> at local.  
If the Switch <SW2> is not used, the Fan motor  
(indoor) drives at high speed.  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Ambient temperature  
Terminal block  
52F1  
52F2  
23C  
TB1  
CH  
F1  
4
6.Specification subject to change without notice.  
5
Crankcase heater  
Fuse (3.15A)  
Transformer  
Internal thermostat  
Internal thermostat(fan O/D)  
Over current relay  
Over current relay(fanI/D,O/D)  
Thermostat (freeze protection)  
High-pressure switch  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (on)  
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
Run capacitor  
Caution,  
3
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
Tr  
(compressor)  
49F  
26L  
(compressor)  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
CZ1, 2  
30CZ, FZ  
1
2
3
4
Power (Active)  
Cooling operation  
Fan operation  
24VAC(L)  
COMP  
FAN HI  
24VAC(N)  
TB4  
Power (Neutral)  
C
C1, 3~6  
CR1, 2  
Connector  
Surge killer  
- 56 -  
PE-8,10MYC-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
Power Supply, 3Phase  
TB1  
380 415Volt, 50Hertz  
52C  
51C  
RED  
RED  
L1  
L2  
L3  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
MC  
52F3  
51F2  
C6  
CIRCUIT BREAKER  
(FIELD SUPPLY)100A  
C4  
WHITE  
1
2
3
RED  
2
3
1
RED  
PU-8,10MYC1-EU  
N
BLUE  
WHITE  
BLACK  
WHITE  
BLACK  
BLACK  
RED  
F3(3.15A)  
MF2  
52F2  
PE  
49C  
51F2  
1
23C  
5
52C  
52F4  
1
RED  
C4  
4
3
2
3
WHITE  
BLACK  
MF3  
49F2  
H
TB5  
GRAY  
C4  
5
15  
C5  
63H  
52  
F3  
52  
F2  
51C  
CZ2  
CZ2  
52F3  
52F2  
52F4  
CH  
30  
CZ  
CR2  
14  
52C  
30  
CZ  
Power Supply, 3Phase  
380 415Volt, 50Hertz  
TB2  
L1  
51F  
52F1  
C1  
C2  
1
2
3
RED  
RED  
1
2
3
RED  
WHITE  
BLUE  
WHITE  
BLUE  
WHITE  
BLACK  
L2  
L3  
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY)15A  
F1(3.15A)  
PE-8,10MYC-EU  
RED  
N
TB4  
1
52F1  
GRAY  
51F1  
SWITCH BOX  
(FIELD SUPPLY)  
C1  
4
PE  
CZ1  
TB3 15  
49F1  
F2  
(3.15A)  
C1  
5
C3  
1
15  
23WA  
OUTDOOR  
26L  
C3  
3
Tr  
SW1  
CZ2  
FZ  
AC  
AC  
220  
240V  
24V  
CR1  
2
3
30FZ  
TB4  
14  
14  
52F1  
CZ1  
30  
FZ  
FZ  
GRAY  
4
BLUE  
Attach the accessory  
Remove  
C1  
C2  
1
2
3
1
2
3
1
2
3
MF1  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Ambient temperature  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
52F1  
52F2  
23C  
TB1  
CH  
4
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5
F1  
3
5.Specification subject to change without notice.  
Transformer  
Tr  
49F1  
49F2  
(indoor fan)  
(outdoor fan)  
(compressor)  
(compressor)  
Internal thermostat  
Internal thermostat  
Internal thermostat  
Over current relay  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
Over current relay(fanI/D,O/D)  
Thermostat (freeze protection)  
High-pressure switch  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
26L  
Option controller connection.  
CZ1, 2  
30CZ, FZ  
PAC-204RC (Option)  
terminal no.  
Symbol No. Function  
1
2
3
4
Power (Active)  
Cooling operation  
Fan operation  
24VAC(L)  
COMP  
FAN HI  
24VAC(N)  
TB4  
C1~6  
CR1, 2  
Power (Neutral)  
- 57 -  
PE-15MYC-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
OUTDOOR UNIT  
TB1  
52C1  
51C1  
RED  
RED  
L1  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC1  
C2  
WHITE  
BLACK  
51F2  
52F3  
C1  
1
N
RED  
RED  
2
RED  
52C2  
51C2  
BLUE  
2
3
3
1
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
RED  
PE  
RED  
MF2  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
WHITE  
BLACK  
WHITE  
BLACK  
MC2  
52F2  
PU-15MYC1-EU ··· 100A  
F3(3.15A)  
51  
F2  
49C1  
51C1  
52  
C1  
52  
49C2  
C2  
TB4  
52  
52  
C1 C2  
51C2  
63H2  
26D  
11 12  
GRAY  
CZ  
2-1  
63H1  
H
CH1 CH2  
CZ  
2-2  
2
52  
F3  
52  
F2  
30  
30  
CR3  
CR2  
CZ2-1  
52  
CZ2-2  
CZ1  
CZ2  
52  
C2  
52  
F2  
52  
F3  
2
C1  
13  
30  
CZ1  
30  
CZ2  
TB2  
51F1  
52F1  
INDOOR UNIT  
L1  
L2  
L3  
RED  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
WHITE  
BLACK  
MF1  
52F1  
N
BLUE  
F1  
(3.15A)  
1
GRAY  
PE  
TB3  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
PE-15MYC-EU ··· 30A  
C3  
1
SWITCH BOX (FIELD SUPPLY)  
CZ  
1-1  
CZ  
1-2  
26L1  
F2  
(3.15A)  
C3  
3
TB3  
Tr  
C8  
1
OUTDOOR  
12  
11  
AC  
220~  
240V  
26L2  
AC  
11  
12  
C8  
3
24V  
SW1  
23  
23  
FZ  
WA  
WA  
CZ  
2-1  
CZ  
2-2  
30  
FZ  
CR1  
3
4
2
52  
F1  
TB3  
30  
FZ  
CZ  
1-1  
CZ  
1-2  
13  
FZ  
GRAY  
5
13  
Symbol  
MC1,2  
MF1  
MF2  
52C1,2  
52F1  
Name  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
Thermostat (freeze protection)  
Auxiliary relay (fan)  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
52F2  
TB1~4  
CH1,2  
F1~3  
Tr  
49C1,2  
51C1,2  
51F1  
51F2,3  
63H1,2  
26L1,2  
FZ  
Caution,  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays <51C1,2>,<51F1,2> are installed. Therefore,  
do not change factory set value of Over current relays.  
2.To protect the starting Compressor <MC1,2>at the same time,Timer  
<2> is installed. Therefore, do not change factory set value of this Timer.  
30FZ  
Auxiliary relay (fan)  
CZ1-1,2/2-1,2 Auxiliary relay  
Option controller connection.  
30CZ1,2  
<SW1>  
<23WA>  
C1~3, 8  
CR1~3  
2
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
Timer  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
24VAC(L)  
COMP1  
COMP2  
FAN HI  
1
2
3
4
5
Power (Active)  
Cooling operation  
Cooling operation  
Fan operation  
TB3  
26D  
Thermostat (ambient temp.)  
Power (Neutral)  
24VAC(N)  
- 58 -  
PE-20MYC-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
OUTDOOR UNIT  
Power supply, 3 Phase  
TB1  
L1  
380~415 Volt, 50Hertz  
52C1  
52C2  
51C1  
51C2  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC1  
MC2  
WHITE  
BLACK  
N
RED  
RED  
BLUE  
PE  
WHITE  
BLACK  
WHITE  
BLACK  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PU-20MYC1-EU ··· 125A  
51F2  
C1  
52F2  
TB5  
TB5  
F3(3.15A)  
1
2
3
RED  
L1-1  
L2-1  
L3-1  
L1-2  
L2-2  
L3-2  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
MF2  
49C1  
49C2  
52  
52  
51F3  
C1 C2  
52F3  
51  
F2  
51  
F3  
52  
52  
C1 C2  
52F4  
63H1  
51C1  
63H2  
51C2  
Tr2  
26D3  
26D1  
FZ  
4
FZ  
2
FZ  
2
FZ  
3
FZ  
5
FZ FZ FZ  
5
6
7
CH1 CH2  
TB4  
51F4  
C2  
52F5  
TB6  
TB6  
2
1
2
3
RED  
L1-1  
L2-1  
L3-1  
L1-2  
L2-2  
L3-2  
RED  
RED  
26D2  
H
H
26D4  
11 12  
GRAY  
RED  
WHITE  
BLACK  
30  
CZ1  
30  
CZ2  
WHITE  
BLACK  
WHITE  
BLACK  
CR3  
CZ2-1  
52  
CR2  
CZ2-2  
52  
52  
F2  
52  
F4  
52  
F5  
52  
F7  
MF3  
FZ2  
FZ5  
WHITE  
BLACK  
CZ  
2-1  
2
51F5  
C1  
C2  
52  
F3  
52  
F6  
52F6  
H
H
CZ  
2-2  
30  
CZ1  
30  
CZ2  
FZ3  
FZ6  
FZ  
3
FZ  
6
52F7  
Tr3  
FZ4  
FZ7  
13  
INDOOR UNIT  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
TB2  
L1  
51F1  
52F1  
RED  
L2  
L3  
WHITE  
BLACK  
MF1  
N
BLUE  
F1  
52F1  
(3.15A)  
1
GRAY  
PE  
TB3  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
C3  
1
PE-20MYC-EU ··· 30A  
CZ CZ  
1-1 1-2  
SWITCH BOX (FIELD SUPPLY)  
26L1  
F2  
C3  
3
(3.15A)  
TB3  
Tr1  
AC  
C8  
1
OUTDOOR  
11 12  
11 12  
26L2  
AC  
220~  
240V  
C8  
3
24V  
SW1  
23  
23  
FZ1  
WA  
WA  
CZ  
2-1  
CZ  
2-2  
30  
FZ  
CR1  
3
4
2
52  
TB3  
F1  
30  
FZ  
CZ  
1-1  
CZ  
1-2  
13  
FZ1  
GRAY  
5
13  
Symbol  
MC1,2  
MF1  
MF2,3  
52C1,2  
52F1  
52F2~7  
TB1~6  
CH1,2  
F1~3  
Name  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
Caution,  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays <51C1,2>,<51F1~5> are installed. Therefore,  
do not change factory set value of Over current relays.  
2.To protect the starting Compressor <MC1,2>at the same time,Timer  
<2> is installed. Therefore, do not change factory set value of this Timer.  
Tr1~3  
49C1,2  
51C1,2  
51F1  
51F2~F5  
63H1,2  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
26L1,2  
FZ1  
Thermostat (freeze protection)  
Auxiliary relay (fanI/D)  
30FZ  
Auxiliary relay (fanI/D)  
CZ1-1,2/2-1,2 Auxiliary relay  
Option controller connection.  
30CZ1,2  
<SW1>  
<23WA>  
C1~3, 8  
CR1~3  
2
Auxiliary relay (check)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Surge killer  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
24VAC(L)  
COMP1  
COMP2  
FAN HI  
1
2
3
4
5
Power (Active)  
Cooling operation  
Cooling operation  
Fan operation  
Timer  
TB3  
26D1~4  
FZ2~7  
Thermostat (ambient temp.)  
Auxiliary relay (fan O/D)  
Power (Neutral)  
24VAC(N)  
- 59 -  
PEH-5MYA-EU (STANDARD)  
Power Supply, 3Phase  
TB1  
MC  
50Hertz  
52C  
INTERNAL  
380~415Volt,  
51C  
RED  
RED  
L1  
L2  
L3  
PROTECTOR  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
51F2  
C4  
X1  
1
RED  
RED  
N
BLUE  
2
3
WHITE  
BLACK  
WHITE  
BLACK  
F3(3.15A)  
MF2  
PE  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
HZ2  
PUH-5MYE-EU···50A  
T1  
X3 X1 X2  
X1  
52C  
51F2  
C7  
3
26  
TB4  
15  
13  
D2  
63H  
GRAY  
C7  
1
51C  
CZ2  
21  
S4  
T1  
CZ2 HZ2  
C6  
1
26  
X3  
CH  
X2  
D1  
30  
CZ  
CR2  
C6  
3
14  
52C  
30  
CZ  
X1  
X2  
Power Supply, 3Phase  
50Hertz  
TB2  
380~415Volt,  
51F1  
C2  
52F  
C1  
WHITE  
BLUE  
RED  
1
2
3
1
L1  
L2  
L3  
RED  
RED  
X
Y
Z
U
2
WHITE  
BLACK  
WHITE  
V
MF1  
3
W
BLUE  
F1  
(3.15A)  
RED  
F1  
N
TB3  
52F  
PE  
GRAY  
1
51F1  
SWITCH BOX  
(FIELD SUPPLY)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
CZ1 HZ1  
C1  
4
PEH-5MYA-EU···15A  
TB3 15  
13  
F2  
(3.15A)  
SW1  
15  
13  
COOL  
C
HEAT  
49F  
OUTDOOR  
H
SW2  
Tr  
C1  
5
CZ2 HZ2  
23  
WA  
FZ  
AC  
AC  
220~  
24V  
CR1  
240V  
3
2
4
TB3  
30FZ  
14  
14  
52F  
HZ1  
CZ1  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Attach the accessory  
Symbol  
Name  
MC  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Transformer  
Remove  
C2  
C1  
1
2
3
2
3
1
MF1  
MF2  
52C  
52F  
TB1~4  
CH  
2
3
1
MF1  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
F1~3  
Tr  
49F  
Internal thermostat(indoor fan)  
Over current relay(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Note:1.The dotted lines show field wiring.  
51C  
51F1,2  
63H  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Specification subject to change without notice.  
26D1,2 Thermostat (defrost)  
Caution,  
21S4  
FZ  
4-Way valve  
Auxiliary relay (fan)  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C>,<51F1,2>are installed. Therefore,  
do not change factory set value of Over current relays.  
CZ1,2  
HZ1,2  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Option controller connection.  
30CZ,FZ Auxiliary relay (check)  
X1  
X2,3  
<SW1>  
<SW2>  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
2
3
Power (Active)  
24VAC(L)  
COMP1  
4WV  
Cooling operation  
Revercing Valve  
for Heating operation  
Fan operation  
<23WA> Thermostat (room temp.)  
C1,2,4,6,7 Connector  
T1  
TB3  
4
5
FAN HI  
24VAC(N)  
Timer (defrost)  
Surge killer  
Power (Neutral)  
CR1,2  
- 60 -  
PEH-7MYA-EU (STANDARD)  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
C4  
X1  
1
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
PUH-7MYC1-EU  
BLUE  
N
2
3
1
2
3
WHITE  
BLACK  
RED  
WHITE  
BLACK  
F3(3.15A)  
MF2  
MF3  
PE  
WHITE  
BLACK  
HZ2  
49C  
C5  
T1  
X3 X1 X2  
X1  
52C  
51F2  
C7  
3
26  
TB5  
15  
13  
D2  
63H  
GRAY  
C7  
1
51C  
CZ2  
21  
T1  
S4  
HZ2  
CZ2  
C6  
1
26  
X3  
CH  
X2  
D1  
30  
CZ  
CR2  
C6  
3
14  
52C  
30  
CZ  
X1  
X2  
JUMPER  
Power supply,  
220 240Volt,  
Single Phase  
50Hertz  
TB4  
C1  
TB2  
L
TB4  
6
RED  
1
2
51F1  
52F  
C1  
RED  
5
6
Hi  
7
8
BROWN  
C
MF1  
Low  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
PEH-7MYA-EU  
N
SW3(FIELD SUPPLY)  
BLUE  
BLUE  
4
TB4  
52F  
F1  
(3.15A)  
GRAY  
1
RED  
SWITCH BOX  
(FIELD SUPPLY)  
CZ1 HZ1  
PE  
51F1  
TB3 15  
13  
F2  
(3.15A)  
SW1  
15  
13  
COOL  
HEAT  
OUTDOOR  
C3  
1
H
C
HZ1  
26L  
SW2  
Tr  
23  
C3  
3
WA  
FZ  
HZ2  
CZ2  
AC  
220  
240V  
24V  
3
2
4
TB4  
30FZ  
CR1  
CZ1 HZ1  
14  
14  
52F  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Note:1.The dotted lines show field wiring.  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Please remove the jumper wire ( Mark) in the above  
diagram if you use the Switch <SW3> at local.  
If the Switch <SW3> is not used, the Fan motor  
(indoor) drives at high speed.  
TB1  
5
Crankcase heater  
Fuse (3.15A)  
6.Specification subject to change without notice.  
F1  
3
Transformer  
Internal thermostat  
Over current relay  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Caution,  
(compressor)  
(compressor)  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
26L  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
CZ1, 2  
HZ1, 2  
30CZ, FZ  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP  
2
TB3  
Reversing valve  
for Heating operation  
4WV  
3
4
5
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
3
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
Run capacitor  
C
C1, C3  
7
Connector  
T1  
Timer (defrost)  
CR1, 2  
Surge killer  
- 61 -  
PEH-8,10MYA-EU (STANDARD)  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
C4  
X1  
1
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
BLUE  
N
2
3
1
2
3
WHITE  
BLACK  
RED  
WHITE  
BLACK  
F3(3.15A)  
MF2  
PE  
WHITE  
BLACK  
PUH-8, 10MYC1-EU ··· 100A  
PUH-8,10MYE-EU ···100A  
HZ2  
MF3  
49C  
C5  
MF3 is only PUH-8,10MYC1-EU.  
T1  
X3 X1 X2  
X1  
52C  
51F2  
C7  
3
26  
TB4 (In case of PUH-8,10MYE-EU)  
TB5 (In case of PUH-8,10MYC1-EU)  
15  
13  
D2  
63H  
GRAY  
C7  
1
51C  
CZ2  
21  
S4  
T1  
HZ2  
CZ2  
C6  
1
26  
X3  
CH  
X2  
D1  
30  
CZ  
CR2  
C6  
3
14  
52C  
30  
CZ  
X1  
X2  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB2  
L1  
51F1  
52F  
C1  
C2  
1
RED  
RED  
1
2
3
RED  
2
3
WHITE  
BLUE  
WHITE  
BLUE  
WHITE  
BLACK  
L2  
L3  
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
F1(3.15A)  
RED  
PEH-8,10MYA-EU  
N
TB4  
1
52F  
GRAY  
F2  
51F1  
SWITCH BOX  
(FIELD SUPPLY)  
C1  
4
PE  
CZ1 HZ1  
TB3 15  
13  
49F  
C1  
5
SW1  
(3.15A)  
15  
13  
HEAT  
COOL  
C
OUTDOOR  
C3  
1
H
HZ1  
FZ  
26L  
Tr  
SW2  
CZ2  
HZ2  
C3  
3
23  
WA  
AC  
AC  
220  
240V  
24V  
CR1  
3
2
4
30FZ  
TB4  
14  
14  
52F  
CZ1 HZ1  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Attach the accessory  
Remove  
C1  
C2  
1
2
3
1
2
3
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
1
2
3
MF1  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
TB1  
F1  
5
Note:1.The dotted lines show field wiring.  
3
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Transformer  
(indoor fan)  
(compressor)  
(compressor)  
Internal thermostat  
Internal thermostat  
Over current relay  
49F  
5.Specification subject to change without notice.  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
26L  
Auxiliary relay (fan)  
CZ1, 2  
HZ1, 2  
30CZ, FZ  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP  
2
TB4  
Reversing valve  
for Heating operation  
4WV  
3
Thermostat (room temp.)  
Connector (C5 is PUH-8,10MYC1-EU only.)  
Timer (defrost)  
4
5
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
C1~7  
T1  
CR1, 2  
Surge killer  
- 62 -  
PEH-15,20MYA-EU (STANDARD)  
L1  
L2  
L3  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
N
BLUE  
RED  
RED  
PE  
WHITE  
BLACK  
WHITE  
BLACK  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
RED  
RED  
PUH-15MYC1-EU---100A  
PUH-20MYC1-EU---125A  
WHITE  
BLACK  
WHITE  
BLACK  
HZ2  
(3.15A)  
F3  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
T2  
3
T1  
3
49C1  
49C2  
X1 X2 X5  
C6  
X3  
X2 X6  
C7  
X4  
26  
D3  
26  
D4  
GRAY  
63H1  
51C1  
63H2  
51C2  
C6  
C4  
C7  
C5  
1
1
1
1
CH1 CH2  
26  
D2  
26  
D1  
X3  
X4  
2
30  
CZ1  
30  
CZ2  
C4  
3
3
C5  
CZ2-1  
CR3  
CR2  
CZ2-2  
S4-2  
S4-1  
L1  
L2  
L3  
RED  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
WHITE  
BLACK  
BLUE  
N
F1  
(3.15A)  
GRAY  
PE  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
PEH-15,20MYA-EU---30A  
C3  
1
CZ CZ  
1-1 1-2  
HZ1  
26L1  
F2  
(3.15A)  
C3  
3
C8  
1
HZ1  
COOL  
C
HEAT  
AC  
26L2  
AC  
220  
C8  
3
24V  
240V  
H
C
H
30  
FZ  
CR1  
1-1  
1-2  
GRAY  
Note:1.The dotted lines show field wiring.  
Symbol  
MC1,2  
MF1  
MF2,3  
52C1,2  
52F  
Name  
Compressor motor  
Fan motor (indoor)  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Fan motor (outdoor)  
5.Specification subject to change without notice.  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Caution,  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C1,2>,<51F1,2,3> are installed. Therefore,  
do not change factory set value of Over current relays.  
TB1  
4
CH1,2  
F1  
Tr  
3
Transformer  
49C1,2  
51C1,2  
51F1  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
Auxiliary relay (fan)  
Auxiliary relay (fan)  
Option controller connection.  
PAC-204RC (Option)  
51F2,3  
63H1,2  
26L1,2  
26D1  
Symbol No. Function  
terminal no.  
1
2
Power (Active)  
24VAC(L)  
COMP1  
Cooling or Heating  
4
operation  
21S4-1,2  
FZ  
30FZ  
Cooling or Heating  
operation  
COMP2  
4WV  
3
4
TB3  
Reversing valve  
for Heating operation  
CZ1-1,2/2-1,2 Auxiliary relay  
5
6
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
HZ1,2  
30CZ1,2  
X1,2  
Auxiliary relay (heater)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Thermostat (room temp.)  
Connector  
X3  
6
<SW1>  
<SW2>  
<23WA>  
C1~8  
T1,2  
Timer (defrost)  
2
CR1  
Timer  
Surge killer  
3
- 63 -  
PEH-5MYA-EU  
SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,  
(
PROTECT FOR COOL AIR BLOW.  
)
Power Supply, 3Phase  
TB1  
L1  
MC  
50Hertz  
52C  
51C  
INTERNAL  
380~415Volt,  
RED  
RED  
PROTECTOR  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
51F2  
C4  
X1  
1
RED  
RED  
N
BLUE  
2
3
WHITE  
BLACK  
WHITE  
BLACK  
F3(3.15A)  
MF2  
PE  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
HZ2  
PUH-5MYE-EU···-50A  
T1  
X3 X1 X2  
X1  
52C  
51F2  
C7  
3
26  
TB4  
15  
13  
16  
D2  
63H  
GRAY  
C7  
1
X3  
17  
51C  
CZ2  
21  
S4  
T1  
HZ2  
CZ2  
C6  
1
26  
X3  
CH  
X2  
D1  
30  
CZ  
CR2  
C6  
3
14  
52C  
30  
CZ  
X1  
X2  
Power Supply, 3Phase  
50Hertz  
TB2  
380~415Volt,  
51F1  
C2  
52F  
C1  
WHITE  
BLUE  
RED  
1
2
3
1
L1  
L2  
L3  
RED  
RED  
X
Y
Z
U
V
W
2
3
WHITE  
BLACK  
WHITE  
BLUE  
MF1  
F1  
(3.15A)  
RED  
N
TB3  
52F  
PE  
GRAY  
1
51F1  
SWITCH BOX  
(FIELD SUPPLY)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PEH-5MYA-EU···U15A  
CZ1 HZ1  
C1  
4
OUT  
DOOR  
16  
F2  
TM  
SW1  
HEAT  
(3.15A)  
16  
(3MIN)  
49F  
COOL  
TB3 15  
15  
13  
13  
X3  
17  
17  
C
H
Tr  
SW2  
C1  
5
23  
OUTDOOR  
FZ  
WA  
TM  
AC  
24V  
AC  
220~  
CZ2  
HZ2  
CR1  
3
2
4
240V  
TB3  
30FZ  
14  
14  
52F  
CZ1  
HZ1  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Attach the accessory  
Symbol  
MC  
Symbol  
21S4  
FZ  
Name  
Name  
4-Way valve  
Auxiliary relay (fan)  
C2  
Remove  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
C1  
1
2
3
2
3
1
MF1  
MF2  
52C  
52F  
2
3
1
CZ1,2  
HZ1,2  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
MF1  
Contactor (compressor)  
Contactor (fan I/D)  
30CZ,FZ Auxiliary relay (check)  
TB1~4 Terminal block  
X1  
Contactor (fan O/D)  
CH  
Crankcase heater  
Fuse (3.15A)  
Transformer  
X2,3  
Auxiliary relay (defrost)  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
F1~3  
Tr  
<SW1> Switch (operation mode)  
<SW2> Switch (on)  
49F  
51C  
Internal thermostat(indoor fan) <23WA> Thermostat (room temp.)  
Over current relay(compressor) C1~4,6,7 Connector  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.When PAC-204RC is used, Timer(TM)is unneccessary.  
6.Specification subject to change without notice.  
51F1,2 Over current relay(fanI/D,O/D) T1  
Timer (defrost)  
63H  
High-pressure switch  
CR1,2  
TM  
Surge killer  
26D1,2 Thermostat (defrost)  
Timer (Anti short cycle)  
Option controller connection.  
Symbol No. Function  
Caution,  
PAC-204RC (Option)  
terminal no.  
24VAC(L)  
COMP1  
4WV  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C>,<51F1,2>are installed. Therefore,  
do not change factory set value of Over current relays.  
1
2
3
Power (Active)  
Cooling operation  
Revercing Valve  
for Heating operation  
Fan operation  
TB3  
4
5
FAN HI  
24VAC(N)  
Power (Neutral)  
- 64 -  
PEH-7MYA-EU  
SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,  
(
PROTECT FOR COOL AIR BLOW.  
)
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
X1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
C4  
C5  
F3(3.15A)  
1
2
3
1
2
3
RED  
RED  
PUH-7MYC1-EU  
N
BLUE  
WHITE  
BLACK  
RED  
WHITE  
BLACK  
MF2  
MF3  
HZ2  
PE  
49C  
WHITE  
BLACK  
TB5  
T1  
15  
13  
X3 X1 X2  
X1  
16  
52C  
GRAY  
51F2  
63H  
X3  
17  
C7  
3
26  
D2  
CZ2 HZ2  
C7  
1
51C  
CZ2  
21  
T1  
S4  
C6  
1
14  
X3  
26  
D1  
CH  
X2  
30  
CZ  
CR2  
C6  
3
52C  
30  
CZ  
X2  
X1  
JUMPER  
Power supply, Single Phase  
50Hertz  
TB4  
C1  
TB2  
L
TB4  
6
1
2
RED  
51F1  
220 240Volt,  
52F  
C1  
RED  
5
6
Hi  
7
8
BROWN  
BLUE  
C
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
Low  
PEH-7MYA-EU  
SW3(FIELD SUPPLY)  
4
N
BLUE  
F1  
TB4  
52F  
(3.15A)  
GRAY  
1
RED  
SWITCH BOX  
CZ1 HZ1  
(FIELD SUPPLY)  
51F1  
PE  
F2  
(3.15A)  
TM  
SW1  
HEAT  
(3MIN)  
TB3  
13  
15  
COOL  
C3  
1
OUT  
DOOR  
26L  
15  
13  
16  
HZ1  
C
H
SW2  
OUTDOOR  
C3  
3
Tr  
23  
16  
X3  
17  
17  
WA  
FZ  
AC  
220  
240V  
CZ2  
HZ2  
AC  
24V  
3
2
4
TB4  
30FZ  
TM  
CR1  
CZ1 HZ1  
14  
14  
52F  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.Please remove the jumper wire ( Mark) in the above  
diagram if you use the Switch <SW3> at local.  
If the Switch <SW3> is not used, the Fan motor  
(indoor) drives at high speed.  
TB1  
F1  
5
Crankcase heater  
Fuse (3.15A)  
3
6.When PAC-204RC is used, Timer(TM)is unneccessary.  
7.Specification subject to change without notice.  
Transformer  
Internal thermostat  
Over current relay  
(compressor)  
(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Caution,  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
26L  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
CZ1, 2  
HZ1, 2  
30CZ, FZ  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP  
2
TB4  
Reversing valve  
for Heating operation  
4WV  
3
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
Run capacitor  
3
4
5
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
C
C1, 3~7  
Connector  
T1  
Timer (defrost)  
CR1, 2  
TM  
Surge killer  
Timer (Anti short cycle)  
- 65 -  
PEH-8,10MYA-EU  
SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,  
(
PROTECT FOR COOL AIR BLOW.  
)
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB1  
L1  
52C  
51C  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
51F2  
C4  
X1  
1
RED  
RED  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
PUH-8, 10MYE-EU  
PUH-8, 10MYC1-EU  
BLUE  
N
2
3
1
2
3
WHITE  
BLACK  
RED  
WHITE  
BLACK  
F3(3.15A)  
MF2  
PE  
WHITE  
BLACK  
HZ2  
MF3  
49C  
C5  
MF3 is only PUH-8,10MYC1-EU.  
T1  
X3 X1 X2  
X1  
52C  
51F2  
C7  
3
26  
TB4 (In case of PUH-8,10MYE-EU)  
TB5 (In case of PUH-8,10MYC1-EU)  
16  
X3  
17  
15  
13  
D2  
63H  
GRAY  
C7  
1
51C  
CZ2  
21  
T1  
S4  
HZ2  
CZ2  
C6  
1
26  
X3  
CH  
X2  
D1  
30  
CZ  
CR2  
C6  
3
14  
52C  
30  
CZ  
X1  
X2  
Power supply,  
380 415Volt,  
3Phase  
50Hertz  
TB2  
L1  
51F  
52F  
C1  
C2  
1
RED  
RED  
1
2
3
RED  
2
3
WHITE  
BLUE  
WHITE  
BLUE  
L2  
L3  
WHITE  
BLACK  
MF1  
1
F3(3.15A)  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
PEH-8, 10MYA-EU  
RED  
N
BLUE  
TB4  
51F1  
52F  
GRAY  
C1  
4
SWITCH BOX  
CZ1 HZ1  
TM  
(FIELD SUPPLY)  
PE  
49F  
OUT  
DOOR  
F2  
C1  
5
16  
SW1  
(3.15A)  
(3MIN)  
COOL  
C
HEAT  
16  
X3  
17  
17  
TB3  
13  
13  
15  
C3  
1
OUTDOOR  
15  
H
HZ1  
FZ  
26L  
Tr  
SW2  
C3  
3
23  
WA  
CZ2 HZ2  
AC  
24V  
AC  
220  
TM  
CR1 240V  
3
2
4
30FZ  
TB4  
14  
14  
52F  
CZ1 HZ1  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Attach the accessory  
Remove  
C1  
C2  
1
2
3
1
2
3
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
1
2
3
MF1  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
This circuit diagram shows connections.  
(If the external static Pressure is less  
than 30 Pa, change to connections.)  
TB1  
5
Crankcase heater  
Fuse (3.15A)  
Transformer  
Note:1.The dotted lines show field wiring.  
F1  
3
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
(indoor fan)  
(compressor)  
(compressor)  
Internal thermostat  
Internal thermostat  
Over current relay  
Over current relay(fanI/D,O/D)  
High-pressure switch  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
49F  
5.When PAC-204RC is used, Timer(TM)is unneccessary.  
6.Specification subject to change without notice.  
Caution,  
26L  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
Auxiliary relay (fan)  
CZ1, 2  
HZ1, 2  
30CZ, FZ  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
Power (Active)  
24VAC(L)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Thermostat (room temp.)  
Connector (C5 is PUH-8,10MYC-EU only.)  
Timer (defrost)  
Cooling or Heating  
COMP  
2
operation  
TB4  
Reversing valve  
for Heating operation  
Fan operation  
Power (Neutral)  
4WV  
3
4
5
FAN HI  
24VAC(N)  
C1~7  
- 66 -  
CR1, 2  
Surge killer  
Timer (Anti short cycle)  
PEH-15,20MYA-EU  
(SPECIAL WIRING : ANTI SHORT CYCLE TIMER)  
OUTDOOR UNIT  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
TB1  
52C1  
51C1  
RED  
RED  
L1  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC1  
MF2  
WHITE  
BLACK  
51F2  
C1  
N
X1  
1
2
3
RED  
RED  
BLUE  
WHITE  
BLACK  
WHITE  
BLACK  
PE  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
PUH-15MYC1-EU ··· 100A  
PUH-20MYC1-EU ··· 125A  
52C2  
51C2  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
MC2  
MF3  
51F3  
C2  
X2  
(3.15A)  
HZ2  
1
2
3
RED  
F3  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
T1  
3
T2  
3
CZ2-1  
49C1  
49C2  
CZ2-2  
X1 X2 X5  
C6  
X3  
X2 X6  
C7  
X4  
51  
F2  
51  
F3  
TM  
(3min)  
52  
52  
C1 C2  
TM  
(3min)  
26  
D3  
26  
D4  
52  
TB4  
11 12 13  
C2  
63H1  
51C1  
63H2  
51C2  
52  
C1  
52  
C1  
52  
C2  
C6  
C4  
1
C7  
C5  
1
GRAY  
1
1
CH1 CH2  
26  
D1  
26  
D2  
CZ  
2-1  
X3  
X4  
2
HZ2  
CZ  
2-2  
30  
CZ1  
30  
CZ2  
C4  
T1  
3
3
C5  
CR2  
CR3  
CZ2-1  
CZ2-2  
52  
TM  
21  
S4-2  
52  
C1  
2
X3  
X2  
X6  
C2  
30  
CZ1  
30  
CZ2  
21  
S4-1  
X1  
X5  
T2  
X4  
14  
TB2  
INDOOR UNIT  
Power supply, 3 Phase  
380~415 Volt, 50Hertz  
51F1  
52F  
L1  
L2  
L3  
RED  
WHITE  
BLACK  
MF1  
N
BLUE  
F1  
52F  
(3.15A)  
1
GRAY  
PE  
TB3  
F2  
(3.15A)  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
CZ  
1-1  
CZ  
1-2  
HZ1  
Tr  
PEH-15,20MYA-EU ··· 30A  
C3  
1
AC  
SWITCH BOX (FIELD SUPPLY)  
SW1  
AC  
220~  
240V  
26L1  
24V  
C3  
3
OUT  
DOOR  
TB3  
HZ1  
11  
12  
13  
C8  
1
COOL HEAT  
OUTDOOR  
26L2  
11  
12  
13  
C
H
C
H
C8  
3
SW2  
CZ  
2-1  
FZ  
23  
WA  
HZ2  
CZ  
2-2  
30  
FZ  
3
2
4
5
TB3  
CR1  
30  
FZ  
CZ  
1-1  
CZ  
1-2  
14  
HZ1  
FZ  
52F  
GRAY  
6
14  
Symbol  
MC1,2  
MF1  
Name  
Compressor motor  
Fan motor (indoor)  
MF2,3  
52C1,2  
52F  
TB1~4  
CH1,2  
F1~3  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
5.When PAC-204RC is used, Timer(TM)is unneccessary.  
6.Specification subject to change without notice.  
Tr  
Transformer  
Internal thermostat(compressor)  
49C1,2  
51C1,2  
51F1  
51F2,3  
63H1,2  
26L1,2  
26D1~4  
21S4-1,2  
FZ  
Over current relay(compressor)  
Over current relay(fanI/D)  
Over current relay(fanO/D)  
High-pressure switch  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
Auxiliary relay (fan)  
Auxiliary relay (fan)  
Caution,  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,  
do not change factory set value of Over current relays.  
2.To protect the starting Compressor <MC1,2>at the same time, Timer  
<2> is installed. Therefore, do not change factory set value of this Timer.  
3.To protect the starting Compressor<52C1,2> frequently, Timer  
<TM> is installed. Therefore, do not change factory set value of this Timer.  
30FZ  
CZ1-1,2/2-1,2 Auxiliary relay  
HZ1,2  
30CZ1,2  
X1,2  
X3~6  
<SW1>  
<SW2>  
<23WA>  
C1~8  
T1,2  
Auxiliary relay (heater)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Timer (defrost)  
Option controller connection.  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP1  
2
Cooling or Heating  
operation  
Reversing valve  
for Heating operation  
COMP2  
4WV  
3
4
TB3  
2
Timer  
Surge killer  
Timer (Anti short cycle)  
5
6
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
CR1~3  
TM  
- 67 -  
PEH-7MYA-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
Power supply,  
3Phase  
TB1  
L1  
52C  
51C  
380 415Volt,50Hertz  
RED  
RED  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC  
52F3  
X1  
51F2  
C4  
C8  
2
F3(3.15A)  
WHITE  
CIRCUIT BREAKER  
(FIELD SUPPLY) 100A  
1
2
3
RED  
RED  
PUH-7MYC1-EU  
N
BLUE  
WHITE  
BLACK  
BLACK  
RED  
3
1
WHITE  
BLACK  
MF2  
HZ2  
49C  
HZ2  
PE  
52F2  
TB5  
15  
13  
51F2  
T1  
1
X3 X1 X2  
X1  
23C  
5
52C  
GRAY  
C4  
4
3
C7  
52F4  
49F  
3
1
RED  
H
CZ2 HZ2  
26  
D2  
C4  
5
2
3
WHITE  
BLACK  
MF3  
63H  
C7  
1
52  
F3  
52  
F2  
C5  
21  
S4  
T1  
51C  
CZ2  
C6  
1
14  
52F3  
52F2  
52F4  
CR2  
X3  
26  
D1  
CH  
X2  
30  
CZ  
C6  
3
52C  
30  
CZ  
X1  
X2  
JUMPER  
Power Supply, Single Phase  
220 240Volt,50Hertz  
TB4  
C1  
TB2  
L
TB4  
6
1
2
RED  
51F1  
52F1  
C1  
RED  
5
6
Hi  
7
8
BROWN  
C
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY) 15A  
Low  
PEH-7MYA-EU  
4
N
SW3(FIELD SUPPLY)  
BLUE  
F1  
BLUE  
TB4  
52F1  
(3.15A)  
GRAY  
1
RED  
SWITCH BOX  
CZ1 HZ1  
(FIELD SUPPLY)  
PE  
51F1  
TB3 15  
13  
F2  
(3.15A)  
SW1  
15  
13  
COOL  
C
HEAT  
C3  
1
OUTDOOR  
26L  
H
HZ1  
SW2  
C3  
3
Tr  
23  
WA  
FZ  
CZ2  
HZ2  
AC  
AC  
24V  
220  
3
2
4
240V  
TB4  
30FZ  
CR1  
CZ1 HZ1  
14  
14  
52F1  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
MC  
MF1  
FZ  
CZ1, 2  
HZ1, 2  
30CZ, FZ  
X1  
Compressor motor  
Fan motor (indoor)  
Auxiliary relay (fan)  
3.Color of earth wire is yellow and green twisting.  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
Run capacitor  
Connector  
Timer (defrost)  
Surge killer  
4-Way valve  
Thermostat (defrost)  
Thermostat (freeze protection)  
4.Not specified color of wire is brown.  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Contactor (fan O/D)  
Ambient temperature  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
MF2, 3  
52C  
52F1  
52F2, 3  
52F4  
23C  
TB1  
CH  
F1  
5.Please remove the jumper wire ( Mark) in the above  
diagram if you use the Switch <SW3> at local.  
If the Switch <SW3> is not used, the Fan motor  
(indoor) drives at high speed.  
X2, 3  
6.Specification subject to change without notice.  
<SW1>  
<SW2>  
<SW3>  
<23WA>  
C
C1, 3  
T1  
CR1, 2  
21S4  
Caution,  
5
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
3
Tr  
8
Transformer  
(compressor)  
(fan O/D)  
(compressor)  
49C  
49F  
51C  
51F1,2  
63H  
Internal thermostat  
Internal thermostat  
Over current relay  
Option controller connection.  
Over current relay(fanI/D,O/D) 26D1, 2  
PAC-204RC (Option)  
High-pressure switch  
26L  
Symbol No. Function  
terminal no.  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP  
2
TB4  
Reversing valve  
for Heating operation  
4WV  
3
4
5
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
- 68 -  
PEH-8,10MYA-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
Power Supply, 3Phase  
TB1  
380 415Volt, 50Hertz  
52C  
51C  
RED  
RED  
L1  
L2  
L3  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
MC  
52F3  
51F2  
X1  
C8  
CIRCUIT BREAKER  
(FIELD SUPPLY)100A  
C4  
WHITE  
1
2
3
RED  
2
3
1
RED  
PUH-8,10MYC1-EU  
N
BLUE  
WHITE  
BLACK  
WHITE  
BLACK  
BLACK  
RED  
F3(3.15A)  
PUH-8,10MYE-EU  
MF2  
HZ2  
52F2  
PE  
49C  
HZ2  
51F2  
T1  
C7  
1
X3 X1 X2  
X1  
23C  
5
52C  
52F4  
C5  
1
RED  
C4  
4
3
MF3 is only PUH-8,10MYC1-EU.  
MF3  
2
3
WHITE  
BLACK  
3
49F2  
H
26  
D2  
C4  
5
TB4 (In case of PUH-8,10MYE-EU)  
TB5 (In case of PUH-8,10MYC1-EU)  
C7  
1
63H  
15  
13  
52  
F3  
52  
F2  
GRAY  
21  
S4  
T1  
51C  
CZ2  
C6  
1
26  
D1  
52F3  
52F2  
52F4  
X3  
CZ2 HZ2  
CH  
X2  
30  
CZ  
C6  
CR2  
3
52C  
30  
CZ  
X2  
X1  
14  
Power Supply, 3Phase  
380 415Volt, 50Hertz  
TB2  
L1  
51F  
52F1  
C1  
C2  
1
RED  
RED  
1
2
3
RED  
2
3
WHITE  
BLUE  
WHITE  
BLUE  
WHITE  
BLACK  
L2  
L3  
MF1  
CIRCUIT BREAKER  
(FIELD SUPPLY)15A  
F1(3.15A)  
RED  
PEH-8,10MYA-EU  
N
TB4  
1
52F1  
51F1  
GRAY  
F2  
C1  
4
SWITCH BOX  
PE  
CZ1 HZ1  
(FIELD SUPPLY)  
49F1  
TB3 15  
13  
C1  
5
SW1  
HEAT  
(3.15A)  
15  
13  
COOL  
C
C3  
1
OUTDOOR  
H
26L  
HZ1  
FZ  
Tr  
SW2  
CZ2 HZ2  
C3  
3
23  
WA  
AC  
AC  
220  
240V  
24V  
CR1  
3
2
4
30FZ  
TB4  
14  
14  
52F1  
CZ1  
HZ1  
30  
FZ  
FZ  
GRAY  
5
BLUE  
Note:1.The dotted lines show field wiring.  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
MC  
MF1  
FZ  
CZ1, 2  
HZ1, 2  
30CZ, FZ  
X1  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Contactor (fan O/D)  
Contactor (fan O/D)  
Ambient temperature  
Terminal block  
Crankcase heater  
Fuse (3.15A)  
Auxiliary relay (fan)  
Auxiliary relay (compressor)  
Auxiliary relay (4-way valve)  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Switch (Fan Hi-Low)  
Thermostat (room temp.)  
High-pressure switch  
Connector (C5 is PUH-8,10MYC1-EU only.)  
Timer (defrost)  
MF2, 3  
52C  
52F1  
52F2, 3  
52F4  
23C  
TB1  
CH  
F1  
Tr  
49C  
49F1  
49F2  
51C  
5.Specification subject to change without notice.  
Caution,  
X2, 3  
1.To protect each Fan motor and Compressor from abnormal  
current, Over current relays <51C>, <51F1,2> are installed.  
Therefore, do not change factory set value of Over current  
relays.  
<SW1>  
<SW2>  
<SW3>  
<23WA>  
63H  
C1~8  
T1  
CR1, 2  
21S4  
26D1, 2  
26L  
5
3
Transformer  
Option controller connection.  
(compressor)  
(fan I/D)  
(fan O/D)  
Internal thermostat  
Internal thermostat  
Internal thermostat  
Over current relay  
PAC-204RC (Option)  
Surge killer  
4-Way valve  
Thermostat (defrost)  
Thermostat (freeze protection)  
Symbol No. Function  
terminal no.  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP  
(compressor)  
2
Over current relay(fanI/D,O/D)  
51F1,2  
TB4  
Reversing valve  
for Heating operation  
4WV  
3
4
5
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
- 69 -  
PEH-15,20MYA-EU  
(SPECIAL ORDER : LOW AMBIENT COOLING)  
OUTDOOR UNIT  
TB1  
L1  
52C1  
51C1  
RED  
RED  
Power supply,  
3 Phase  
380~415 Volt,  
50Hertz  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
L2  
L3  
MC1  
WHITE  
BLACK  
51F2  
C1  
RED  
52F2  
TB5  
TB5  
N
1
2
3
RED  
L1-1  
L2-1  
L3-1  
L1-2  
L2-2  
L3-2  
RED  
BLUE  
RED  
WHITE  
BLACK  
WHITE  
BLACK  
PE  
WHITE  
BLACK  
MF2  
WHITE  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F3  
BLACK  
52C2  
51C2  
52F3  
RED  
RED  
PUH-15MYC1-EU ··· 100A  
PUH-20MYC1-EU ··· 125A  
WHITE  
BLACK  
WHITE  
BLACK  
MC2  
52F4  
Tr2  
F3  
(3.15A)  
HZ2  
51F4  
C2  
RED  
52F5  
T1  
3
T2  
TB6  
TB6  
1
2
3
RED  
L1-1  
L2-1  
L3-1  
L1-2  
L2-2  
L3-2  
X1 X2 X5  
X3  
X2 X6  
X4  
RED  
RED  
49C1  
49C2  
WHITE  
BLACK  
WHITE  
BLACK  
WHITE  
BLACK  
MF3  
WHITE  
BLACK  
C6  
C7  
3
52  
52  
51F5  
51  
F2  
51  
F3  
26  
D3  
26  
D4  
C1 C2  
52F6  
FZ  
4
26D5  
26D7  
C6  
C4  
1
C7  
C5  
1
FZ  
2
FZ  
7
FZ  
2
FZ  
3
FZ  
5
FZ  
5
FZ  
6
63H1  
51C1  
63H2  
51C2  
1
1
52F7  
Tr3  
CH1 CH2  
TB4  
11 12 13  
26  
D1  
26  
D2  
H
H
26D8  
26D6  
52  
F2  
X3  
X4  
52  
F4  
52  
F5  
52  
F7  
GRAY  
FZ2  
FZ5  
C4  
3
3
C5  
2
52  
52  
F6  
H
30  
CZ1  
30  
CZ2  
H
CZ  
2-1  
CR3  
21  
S4-2  
CR2  
CZ2-1  
F3  
CZ2-2  
52  
HZ2  
T1  
X3  
X2  
X6  
FZ3  
FZ6  
CZ  
2-2  
FZ  
3
FZ  
6
52  
C1  
21  
S4-1  
2
C2  
X1  
X5  
T2  
X4  
30  
CZ1  
30  
CZ2  
FZ4  
FZ7  
14  
TB2  
L1  
INDOOR UNIT  
Power supply,  
3 Phase  
380~415 Volt,  
50Hertz  
51F1  
52F1  
RED  
L2  
L3  
WHITE  
BLACK  
MF1  
N
BLUE  
F1  
52F  
(3.15A)  
1
GRAY  
PE  
TB3  
CIRCUIT BREAKER  
(FIELD SUPPLY)  
51F1  
CZ CZ  
1-1 1-2  
HZ1  
PEH-15,20MYA-EU ··· 30A  
C3  
1
SWITCH BOX (FIELD SUPPLY)  
SW1  
F2  
26L1  
(3.15A)  
TB3  
Tr1  
C3  
3
11 12 13  
11 12 13  
COOL HEAT  
C8  
1
AC  
HZ1  
FZ1  
OUTDOOR  
AC  
220~  
240V  
26L2  
24V  
C
H
C
H
SW2  
C8  
3
CZ  
2-1  
23  
WA  
HZ2  
CZ  
2-2  
30  
FZ  
CR1  
3
2
4
5
TB3  
52  
F1  
CZ  
1-1  
CZ  
1-2  
14  
FZ1  
HZ1  
30  
FZ  
GRAY  
6
14  
Symbol  
MC1,2  
MF1  
MF2,3  
52C1,2  
52F1  
TB1~6  
CH1,2  
F1~3  
Name  
Compressor motor  
Fan motor (indoor)  
Fan motor (outdoor)  
Contactor (compressor)  
Contactor (fan I/D)  
Terminal block  
Note:1.The dotted lines show field wiring.  
Crankcase heater  
Fuse (3.15A)  
2.The figure in the parentheses show field supply parts.  
3.Color of earth wire is yellow and green twisting.  
4.Not specified color of wire is brown.  
Tr1~3  
Transformer  
49C1,2  
51C1,2  
51F1~5  
63H1,2  
Internal thermostat(compressor)  
Over current relay(compressor)  
Over current relay(fanI/D,O/D)  
High-pressure switch  
5.Specification subject to change without notice.  
Caution,  
1.To protect each Fan motor and Compressor from abnormal current,  
Over current relays<51C1,2>,<51F1~5>are installed. Therefore,  
do not change factory set value of Over current relays.  
26L1,2  
Thermostat (freeze protection)  
Thermostat (defrost)  
4-Way valve  
26D1~4  
21S4-1,2  
FZ1,30FZ  
Auxiliary relay (fan I/D)  
2.To protect the starting Compressor <MC1,2>at the same time,Timer  
CZ1-1,2/2-1,2 Auxiliary relay  
HZ1,2  
30CZ1,2  
X1,2  
Auxiliary relay (heater)  
<2> is installed. Therefore, do not change factory set value of this Timer.  
Auxiliary relay (check)  
Contactor (fan O/D)  
Auxiliary relay (defrost)  
Switch (operation mode)  
Switch (on)  
Thermostat (room temp.)  
Connector  
Timer (defrost)  
Timer  
Surge killer  
Thermostat (ambient temp.)  
Contactor (fan O/D)  
Auxiliary relay (fan O/D)  
X3~6  
Option controller connection.  
<SW1>  
<SW2>  
<23WA>  
C1~8  
T1,2  
2
CR1~3  
26D5~8  
52F2~7  
FZ2~7  
PAC-204RC (Option)  
Symbol No. Function  
terminal no.  
1
Power (Active)  
Cooling or Heating  
operation  
24VAC(L)  
COMP1  
2
Cooling or Heating  
operation  
Reversing valve  
for Heating operation  
COMP2  
4WV  
3
4
TB3  
5
6
Fan operation  
Power (Neutral)  
FAN HI  
24VAC(N)  
- 70 -  
ELECTRICAL OPERATION FLOW CHARTS  
PE-7,8,10MYC-EU  
PEH-5MYA-EU, PEH-7,8,10MYA-EU  
START  
POWER ON  
START  
POWER ON  
CH ON  
CH ON  
30FZ,30CZ ON (SELF HOLD)  
30FZ,30CZ ON (SELF HOLD)  
NO  
NO  
SW2 ON?  
SW1 ON?  
YES  
YES  
FZ ON  
FZ ON  
52F ON  
MF1 OPERATE  
52F ON  
MF1 OPERATE  
NO  
SW1 COOL?  
HZ1,2 ON  
21S4 ON  
NO  
23WA ON?  
YES  
YES  
NO  
CZ1,2  
ON  
23WA ON?  
NO  
23WA ON?  
YES  
YES  
52C  
MC  
MF2, 3 OPERATE  
ON  
OPERATE  
CZ1  
ON  
CZ1,2  
ON  
52C  
MC  
MF2, 3 OPERATE  
ON  
OPERATE  
CH  
OFF  
52C  
MC  
ON  
OPERATE  
MF2, 3 OPERATE  
CH  
OFF  
SAFETY  
NO  
DEVICE OFF?  
CH OFF  
YES  
SAFETY  
DEVICE OFF?  
NO  
30CZ OFF  
NO  
CONDENSING  
TEMP -12  
?
52C  
MC  
MF1  
OFF  
STOP  
Note  
YES  
YES  
26D1, 2 ON  
30CZ OFF  
MF2,3 STOP  
52C  
MC  
MF1  
OFF  
STOP  
Note  
X1 ON  
X2 ON (SELF HOLD)  
MF2,3 STOP  
CH  
ON  
21S4 OFF  
MF2, 3 STOP  
SERVICE CALL  
CH  
ON  
NO  
CONDENSING  
TEMP  
6
?
SERVICE CALL  
YES  
26D1, 2 OFF  
Note.  
1. When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.  
But the unit doesn't work correctly (not cooling and heating ).  
X1, 2 OFF  
Then, turn off the power supply and check outdoor unit.  
21S4 ON  
MF2, 3 OPERATE  
- 71 -  
PE-15MYC-EU  
PE-20MYC-EU  
START  
POWER ON  
START  
POWER ON  
CH1,2 ON  
CH1,2 ON  
30FZ,30CZ1,2 ON (SELF HOLD)  
30FZ,30CZ1,2 ON (SELF HOLD)  
NO  
NO  
SW1 ON?  
SW1 ON?  
YES  
YES  
FZ ON  
FZ ON  
52F1 ON  
52F1 ON  
MF1 OPERATE  
MF1 OPERATE  
NO  
NO  
23WA ON?  
23WA ON?  
YES  
YES  
CZ1-1,CZ2-1 ON  
CZ1-1,CZ2-1 ON  
52C1 ON  
52C1 ON  
MC1 OPERATE  
MF2 OPERATE  
MC1 OPERATE  
MF2 OPERATE  
CH 1  
OFF  
CH 1  
OFF  
CZ1-2,CZ2-2 ON  
TIMER 2 ON  
CZ1-2,CZ2-2 ON  
TIMER 2 ON  
NO  
NO  
PASS THE 3 MIN?  
PASS THE 3 MIN?  
52C2 ON  
52C2 ON  
MC2 OPERATE  
MC2 OPERATE  
MF3 OPERATE  
CH2 OFF  
CH2 OFF  
No.1 SAFETY  
DEVICE OFF?  
No.2 SAFETY  
DEVICE OFF?  
No.1 SAFETY  
DEVICE OFF?  
No.2 SAFETY  
DEVICE OFF?  
NO  
NO  
NO  
NO  
YES  
YES  
YES  
YES  
30CZ1 OFF  
30CZ2 OFF  
30CZ1 OFF  
30CZ2 OFF  
52C1  
MC1  
MF2  
OFF  
STOP  
STOP  
52C2  
MC2  
MF2  
OFF  
STOP  
STOP  
52C1  
MC1  
MF2,3 STOP  
OFF  
STOP  
52C2  
MC2  
MF2,3 STOP  
OFF  
STOP  
CH1 ON  
CH2 ON  
CH1 ON  
CH2 ON  
SERVICE CALL  
SERVICE CALL  
Note.  
When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.  
But the unit doesn't work correctly (not cooling ).  
Then, turn off the power supply and check outdoor unit.  
When the fault of indoor unit is occurred, both indoor unit and outdoor unit is stop.  
- 72 -  
PEH-15,20MYA-EU  
START  
POWER ON  
CH1,2 ON  
30FZ,30CZ1,2 ON (SELF HOLD)  
NO  
SW2 ON?  
YES  
FZ ON  
52F1 ON  
MF1 OPERATE  
NO  
HZ1,2 ON  
SW1 COOL?  
21S4-1,2 ON  
T1,T2 ON  
YES  
NO  
NO  
23WA ON?  
23WA ON?  
YES  
YES  
CZ1-1,CZ2-1 ON  
CZ1-1,CZ2-1 ON  
52C1  
MC1  
MF2  
ON  
OPERATE  
OPERATE  
52C1  
MC1  
MF2  
ON  
OPERATE  
OPERATE  
CH 1  
OFF  
CH 1  
OFF  
CZ1-2,CZ2-2 ON  
TIMER ON  
CZ1-2,CZ2-2 ON  
TIMER ON  
2
2
NO  
NO  
PASS THE 3 MIN?  
YES  
PASS THE 3 MIN?  
YES  
NO  
CONDENSING  
TEMP -12  
?
52C2  
MC2  
MF3  
ON  
OPERATE  
OPERATE  
52C2  
MC2  
MF3  
ON  
OPERATE  
OPERATE  
YES  
ON  
26D1  
4
CH 2  
OFF  
CH 2  
OFF  
X1,2,5,6 ON  
X3,4  
ON (SELF HOLD)  
21S4-1,2 OFF  
MF2, 3 STOP  
No.1 SAFETY  
DEVICE OFF?  
No.2 SAFETY  
DEVICE OFF?  
No.1 SAFETY  
DEVICE OFF?  
No.2 SAFETY  
DEVICE OFF?  
NO  
NO  
NO  
NO  
NO  
YES  
YES  
YES  
YES  
CONDENSING  
TEMP  
6
?
30CZ1 OFF  
30CZ2 OFF  
30CZ1 OFF  
30CZ2 OFF  
YES  
52C1  
MC1  
MF2  
OFF  
STOP  
STOP  
52C2  
MC2  
MF3  
OFF  
STOP  
STOP  
52C1  
MC1  
MF2  
OFF  
STOP  
STOP  
52C2  
MC2  
MF3  
OFF  
STOP  
STOP  
26D1  
X1  
4
OFF  
6
OFF  
CH1 ON  
CH2 ON  
CH1 ON  
CH2 ON  
21S4-1,2 ON  
MF2, 3 OPERATE  
SERVICE CALL  
SERVICE CALL  
Note.  
When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.  
But the unit doesn't work correctly (not cooling ).  
Then, turn off the power supply and check outdoor unit.  
When the fault of indoor unit is occurred, both indoor unit and outdoor unit is stop.  
- 73 -  
REFRIGERANT SCHEMATICS  
PE-7,8,10,15,20MYC-EU  
INDOOR  
PE  
OUTDOOR  
PU  
Evaporator  
Condenser  
High  
pressure  
switch  
Service  
port  
Check  
joint  
Strainer  
Ball valve  
Interconnecting refrigerant piping  
(by others)  
COOL  
Muffler  
Accumulator  
Check  
joint  
Compressor  
Interconnecting refrigerant piping  
(by others)  
Strainer  
Capillary  
Tube  
Ball valve  
Note:PE-15,20MYC-EU is comprised of two refrigerant cycles.  
PEH-5,7,8,10,15,20MYA-EU  
INDOOR  
PEH  
OUTDOOR  
PUH  
Evaporator  
Condenser  
High  
pressure  
switch  
Service  
port  
Check  
joint  
4-Way  
valve  
Strainer  
Ball valve  
Strainer  
Interconnecting refrigerant piping  
(by others)  
HEAT COOL  
Muffler  
Accumulator  
Check  
joint  
Compressor  
Capillary  
Tube  
Capillary  
Tube  
Inter connecting refrigerant piping  
(by others)  
Check  
valve  
Strainer  
Strainer  
Check  
valve  
Ball valve  
Note:PEH-15,20MYA-EU is comprised of two refrigerant cycles.  
- 74 -  
SAFETY & CONTROL DEVICES  
PE-7,8,10MYC-EU  
PE-15,20MYC-EU  
PE-7MYC-EU  
PU-7MYC1-EU  
PE-8MYC-EU  
PU-8MYC1-EU  
PE-10MYC-EU  
PU-10MYC1-EU  
ITEM  
NO.  
COMPRESSOR OVER CURRENT RELAY  
COMPRESSOR INTERNAL THERMOSTAT  
HIGH PRESSURE SWITCH  
51C  
49C  
63H  
51F1  
19.0A  
22.0A  
31.0A  
105 ± 5 ËšC OFF  
83 ± 11 ËšC ON  
2.94MPa OFF  
3.5A  
INDOOR FAN MOTOR OVER CURRENT RELAY  
5.0A  
5.0A  
INDOOR FAN MOTOR INTERNAL THERMOSTAT  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
-
150 Ëš C OFF  
2.5A  
51F2  
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT  
FUSE  
-
150 ËšC OFF  
3.15A  
F1  
3
PE-15MYC-EU  
PE-20MYC-EU  
ITEM  
NO.  
PU-15MYC1-EU PU-20MYC1-EU  
COMPRESSOR OVER CURRENT RELAY  
COMPRESSOR INTERNAL THERMOSTAT  
HIGH PRESSURE SWITCH  
51C1,2  
49C  
63  
22.0A 31.0A  
105 ± 5 ËšC OFF 83 Â± 11 ËšC ON  
3.24MPa OFF  
INDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT  
FUSE  
51F1  
51F2,3  
-
4.6A  
7.2A  
2.5A  
150 ËšC OFF  
3.15A  
F1  
3
- 75 -  
PEH-7,8,10MYA-EU  
PEH-15,20MYA-EU  
PEH-8MYA-EU  
PUH-8MYC1-EU  
PUH-8MYE-EU  
PEH-5MYA-EU  
PUH-5MYE-EU  
PEH-7MYA-EU  
PUH-7MYC1-EU  
ITEM  
NO.  
COMPRESSOR OVER CURRENT RELAY  
COMPRESSOR INTERNAL THERMOSTAT  
51C  
49C  
15.0A  
19.0A  
22.0A  
110 ± 5ËšC OFF  
61 ± 9ËšC ON  
105 ± 5ËšC OFF  
83 ± 11ËšC ON  
HIGH PRESSURE SWITCH  
63H  
26D1  
26D2  
51F1  
2.94MPa OFF  
-12 ± 2 ËšC ON  
6 ± 2 ËšC OFF  
5.0A  
FROST PROTECTOR  
INDOOR FAN MOTOR OVER CURRENT RELAY  
3.5A  
3.5A  
INDOOR FAN MOTOR INTERNAL THERMOSTAT  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
-
150Ëš C OFF  
2.5A  
51F2  
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT  
FUSE  
-
150ËšC OFF  
3.15A  
F1  
3
PEH-10MYA-EU  
PUH-10MYC1-EU  
PUH-10MYE-EU  
PEH-15MYA-EU  
PUH-15MYC1-EU  
PEH-20MYA-EU  
PUH-20MYC1-EU  
ITEM  
NO.  
COMPRESSOR OVER CURRENT RELAY  
COMPRESSOR INTERNAL THERMOSTAT  
HIGH PRESSURE SWITCH  
51C1,2  
49C  
63H  
26D1  
26D2  
51F1  
51F  
31.0A  
22.0A  
31.0A  
105 ± 5 Ëš C OFF 83 ± 11ËšC ON  
2.94MPa OFF  
-12 ± 2 ËšC ON  
FROST PROTECTOR  
6 ± 2 ËšC OFF  
INDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR OVER CURRENT RELAY  
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT  
FUSE  
5.0A  
4.6A  
2.5A  
7.2A  
-
150Ëš C OFF  
3.15A  
F1  
3
- 76 -  
SPECIAL ORDER  
Model  
Service ref.  
Model  
-
-
PE-7MYC  
PE-8MYC  
PE-10MYC PE-15MYC PE-20MYC  
Cooling only  
Heat pump  
PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU  
Description  
PEH-5MYA PEH-7MYA PEH-8MYA PEH-10MYA PEH-15MYA PEH-20MYA  
Service ref.  
PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU  
Release  
2000 year  
*
Low Ambient Cooling  
Global Remote Controller  
Anti corrosion  
(Service reference)  
(PUH-8MYC-EUS, (PUH-10MYC-EUS,  
(PUH-5MYE-EUS) (PUH-7MYC-EUS)  
(PUH-15MYC-EUS) (PUH-20MYC-EUS)  
PUH-8MYE-EUS)  
PUH-10MYE-EUS)  
* Low ambient cooling  
It is possible to conduct cooling operation under an outdoor temperature even down to -5 ËšC.  
- 77 -  
PHYSICAL DATA  
PE-7,8,1015,20MYC-EU  
]
[
PRODUCT  
PACKAGE AIR COOLED HEATPUMP UNITS  
Product type  
PE SERIES  
PE-10MYC-EU  
PU-10MYC1-EU  
28.8  
Product number :  
Indoor unit  
Outdoor unit  
PE-7MYC-EU  
PU-7MYC1-EU  
17.9  
PE-8MYC-EU  
PU-8MYC1-EU  
22.0  
PE-15MYC-EU  
PU-15MYC1-EU  
44.0  
PE-20MYC-EU  
PU-20MYC1-EU  
57.6  
Cooling capacity (AS1861)  
kW  
kW  
kW  
14.3  
17.6  
23.0  
35.2  
46.1  
Sensible Cooling capacity (AS1861)  
Cooling power consumption (Input)  
Basic temperature condition cooling  
Basic temperature condition cooling  
7.2  
7.8  
10.1  
16.9  
22.7  
Indoor  
Outdoor  
27 DB/19 WB  
35 DB  
[ELECTRICAL]  
<Indoor unit>  
Volts  
Hz  
240  
415  
50  
Design voltage  
Cy  
cles  
Power supply  
Volts 1PH-240V  
3PH-415V  
240/24  
415  
Control voltage  
Voltage change  
Voltage change  
Fan motor output  
Fan motor current  
Max.  
Min.  
Volts  
Volts  
240  
220  
380  
HP(kW) 0.28(0.21) 0.94(0.70) 1.34(1.0) 2.95(2.2) 4.96(3.7)  
Amps  
3.2  
1.2  
2.0  
3.5  
4.8  
<Outdoor unit>  
Design voltage  
Cycles  
Volts  
Hz  
415  
50  
Power supply  
Voltage change  
Voltage change  
Volts  
Volts  
Volts  
3PH-415V  
415  
Max.  
Min.  
380  
HP(kW) 2X0.12(2X0.09)  
2X0.2(2X0.15)  
0.32(0.24) 2X0.32(2X0.24)  
Fan motor output  
Fan motor current  
Amps  
0.7  
1.0  
1.2  
2X1.2  
[COMPRESSOR]  
Make  
MITSUBISHI  
Model  
Type  
JH519YE JH521YE JH527YE  
HERMETIC LINE START (RECIPROCATING)  
JH521YE JH527YE  
Number of compressor  
Nominal motor  
Locked rotor current  
Normal run current (AS1861)  
Swept volume  
Bore  
1
2
HP(kW) 6.7(5.0)  
7.4(5.5) 10.1(7.5)  
83  
15.5  
160.8  
10.1(7.5)  
85  
19.2  
7.4(5.5)  
83  
15.5  
Amps  
Amps  
cc/rev  
mm  
76  
13.0  
149  
85  
19.2  
201  
ø44.45  
201  
160.8  
Stroke  
mm  
24.0  
25.9  
Speed  
Number of cylinders  
rpm  
2900  
5
4
4
3000  
5
4500  
ml  
3000  
4500  
Oil charge  
Type of oil  
DIAMOND MS32(N-1) OR SUNISO 3GS(D)  
watts  
62  
72  
62  
72  
Crankcase heater  
[REFRIGERATION SYSTEM]  
Refrigerant  
Refrigerant charge per circuit  
Number of refrigerant control  
Refrigerant control  
R22  
8.7  
kg  
m
5.7  
5.0  
1
4.8  
9.7  
2
Capillary tube  
50  
Limit of pipe's length  
mtrs  
mtrs  
20 (In case of indoor unit above outdoor unit)  
30 (In case of outdoor unit above indoor unit)  
Limit of pipe's height difference  
- 78 -  
Product number  
Indoor unit  
Outdoor unit  
PE-7MYC-EU  
PU-7MYC1-EU  
PE-8MYC-EU  
PU-8MYC1-EU  
PE-10MYC-EU  
PU-10MYC1-EU  
PE-15MYC-EU  
PU-15MYC1-EU  
PE-20MYC-EU  
PU-20MYC1-EU  
[INDOOR AIR CIRCUIT]  
2
Number of blowers  
Diameter of blowers  
Width of blowers  
mm  
mm  
250  
380  
245  
275  
270  
374  
Direct drive  
Belt drive  
Blower drive  
2.2  
3.5  
2333  
3.7  
4.8  
3000  
kW  
A
L/s  
Pa  
mm  
mm  
0.21  
3.2  
1000  
0.70  
1.2  
1167  
125  
1.00  
2.0  
1500  
Fan motor output  
Fan motor run current  
Air quantity  
External static pressure  
Supply air dimensions(hxw)  
Return air dimensions(hxw)  
[EVAPORATOR]  
200  
341 X 1102  
248 X 998  
341X1302  
412X1000 412X1209  
596X1415  
Number of evaporator  
Face area  
1
0.50  
0.86  
1.00  
sq.m  
0.42  
4
Rows deep  
4
15  
24  
Rows high  
1300  
3.0  
1415  
2.7  
1615  
3.0  
Finned length  
Face velocity  
mm  
m/s  
1100  
2.2  
2.8  
Fin per meter  
474/2.11  
513/1.95 474/2.11 513/1.95  
0.115  
Aluminium / Ring  
Fin material thickness  
Fin material/Type  
Tube diameter  
Gauge of copper tube  
Pipe type  
mm  
mm  
mm  
9.52  
0.35  
Plain tube  
Groove tube  
Number of circuit  
10  
16  
24  
[OUTDOOR AIR CIRCUIT]  
Number of fans  
Diameter of fan  
Blower drive  
2
600  
1
2
mm  
954  
Direct drive  
Quantity of motor  
Fan motor output  
Fan motor run current  
2
1
2
0.24  
2X0.36  
kW  
A
L/s  
2X0.09  
0.7  
3167  
2X0.15  
1.0  
1.2  
4000  
2X1.2  
8000  
quantity  
Air  
3000  
3667  
[CONDENSER]  
Number of condensers  
Face area  
Rows deep  
Rows high  
2
sq.m  
2 X 2.1  
32  
1.32  
2
40  
1.35  
2
30  
1
2
30  
30  
mm  
m/s  
2706  
2696  
1299  
1.5  
1775  
3.0  
Finned length  
Face velocity  
1.4  
1.5  
6.25/1.6  
474 / 2.7 625 / 1.6 538 / 1.86  
0.115  
Fin per meter/Pitch  
Fin material thickness  
Fin material/Type  
Tube diameter/Gauge  
Pipe type  
mm  
mm  
Aluminium / Ring  
9.52 / 0.35  
Groove tube  
Plain tube  
6
Number of circuit  
7
11  
- 79 -  
Product number  
Indoor unit  
Outdoor unit  
PE-7MYC-EU  
PU-7MYC1-EU  
PE-8MYC-EU  
PU-8MYC1-EU  
PE-10MYC-EU  
PU-10MYC1-EU  
PE-15MYC-EU  
PU-15MYC1-EU  
PE-20MYC-EU  
PU-20MYC1-EU  
[ENCLOSURE AND FRAME]  
mm  
mm  
mm  
mm  
mm  
mm  
428  
706  
height  
width  
depth  
height  
width  
depth  
1415  
1615  
1690  
1993  
Dimension  
Indoor unit  
650  
980  
1400  
700  
865  
1230  
998  
961  
1996  
Outdoor unit  
Dimension  
998  
External finish (indoor unit)  
Galvanized steel  
Acrylic resin coationg (Color: Munsell 5Y8/1)  
(outdoor unit)  
External finish  
mm  
mm  
kg  
1.2  
25.4  
84  
230  
59  
65  
67  
76  
Panel thickness  
Condense drain size  
Weight Indoor unit  
Weight Outdoor unit  
Sound pressure level (indoor unit)  
Sound pressure level (outdoor unit)  
Sound power level (indoor unit)  
Sound power level (outdoor unit)  
180  
285  
61  
67  
69  
212  
360  
62  
68  
70  
67  
202  
55  
65  
63  
70  
205  
56  
65  
64  
kg  
dbA  
dbA  
dbA  
dbA  
76  
76  
78  
79  
- 80 -  
PEH-5,7,8MYA-EU  
]
[
PRODUCT  
PACKAGE AIR COOLED HEATPUMP UNITS  
PEH SERIES  
Product type  
Product number :  
Indoor unit  
Outdoor unit  
PEH-5MYA-EU  
PUH-5MYE-EU  
14.4  
PEH-7MYA-EU  
PUH-7MYC1-EU  
17.9  
PEH-8MYA-EU  
PUH-8MYC1-EU  
PUH-8MYE-EU  
22.0  
17.6  
7.8  
22.0  
6.5  
Cooling capacity (AS1861)  
kW  
kW  
kW  
kW  
kW  
11.5  
6.0  
14.4  
14.3  
7.2  
18.8  
6.3  
Sensible Cooling capacity (AS1861)  
Cooling power consumption (Input)  
Heating capacity (AS1861)  
Heating power consumption  
4.5  
Indoor  
Outdoor  
Indoor  
Basic temperature condition cooling  
Basic temperature condition cooling  
Basic temperature condition heating  
Basic temperature condition heating  
27 DB/19 WB  
35 DB  
21 DB  
7
DB/6 WB  
Outdoor  
[ELECTRICAL]  
<Indoor unit>  
Volts  
Hz  
Design voltage  
415  
240  
415  
Cy  
50  
cles  
Power supply  
Volts  
3PH-415V  
1PH-240V  
3PH-415V  
Control voltage  
Voltage change  
Voltage change  
Fan motor output  
Fan motor current  
240/24  
Max.  
Min.  
Volts  
Volts  
HP(kW)  
Amps  
415  
380  
0.6(0.45)  
415  
380  
0.94(0.70)  
240  
220  
0.28(0.21)  
1.1/1.0  
3.2  
1.2  
<Outdoor unit>  
Design voltage  
Cycles  
Volts  
Hz  
415  
50  
Power supply  
Voltage change  
Voltage change  
Fan motor output  
Fan motor current  
Volts  
Volts  
Volts  
HP(kW)  
Amps  
3PH-415V  
415  
Max.  
Min.  
380  
0.2(0.15)  
1.0  
0.47(0.35)  
2X0.12(2X0.09)  
0.7  
[COMPRESSOR]  
Make  
Model  
Copeland  
CRNQ-0500-TFD  
MITSUBISHI  
JH521YE  
JH519YE  
Type  
HERMETIC LINE START (RECIPROCATING)  
1
Number of compressor  
Nominal motor  
Locked rotor current  
Normal run current (AS1861)  
Swept volume  
Bore  
HP(kW)  
Amps  
Amps  
cc/rev  
mm  
5.0(3.73)  
6.7(5.0)  
7.4(5.5)  
65  
76  
83  
8.6  
101.92  
13.0  
149  
15.5  
160.8  
ø49.78  
26.19  
ø44.45  
Stroke  
mm  
25.9  
24.0  
rpm  
2900  
Speed  
2
1952  
CALUMET RO 15 OR WITCO 3GS  
40  
4
3000  
Number of cylinders  
Oil charge  
Type of oil  
ml  
DIAMOND MS32(N-1) OR SUNISO 3GS(D)  
watts  
62  
Crankcase heater  
[REFRIGERATION SYSTEM]  
Refrigerant  
R22  
kg  
5.7  
6.6  
Refrigerant charge per circuit  
Number of refrigerant controls  
Refrigerant control  
5.0  
1
Capillary tube  
4-way valve  
Reverse cycle defrost  
50  
Reverse cycle valve  
Defrost system  
Limit of pipe's length  
m
mtrs  
mtrs  
20 (In case of indoor unit above outdoor unit)  
30 (In case of outdoor unit above indoor unit)  
Limit of pipe's height difference  
- 81 -  
Product number  
Indoor unit  
Outdoor unit  
PEH-5MYA-EU  
PUH-5MYE-EU  
PEH-7MYA-EU  
PUH-7MYC1-EU  
PEH-8MYA-EU  
PUH-8MYC1-EU  
PUH-8MYE-EU  
[INDOOR AIR CIRCUIT]  
1
2
Number of blowers  
Diameter of blowers  
Width of blowers  
mm  
mm  
250  
275  
245  
275  
Direct drive  
Blower drive  
0.45  
1.1/1.0  
700  
100  
342X781  
248X498  
0.21  
3.2  
1000  
0.70  
1.2  
1167  
kW  
A
L/s  
Pa  
mm  
mm  
Fan motor output  
Fan motor run current  
Nominal air quantity  
External static pressure  
Supply air dimensions(hxw)  
Return air dimensions(hxw)  
[EVAPORATOR]  
125  
341X1102  
342X1118  
248X998  
Number of evaporator  
Face area  
Rows deep  
Rows high  
Finned length  
1
4
sq.m  
0.3  
0.42  
15  
15  
780  
2.5  
1100  
2.2  
1100  
2.8  
mm  
m/s  
Face velocity  
513/1.95  
474/2.11  
474/2.11  
Fin per meter / pitch  
Fin material thickness  
Fin material/Type  
Fin coating  
Tube diameter  
Gauge of copper tube  
Pipe type  
0.115  
mm  
Aluminium / Ring  
NA 510 D*1  
9.52  
mm  
mm  
0.35  
Plain tube  
10  
Groove tube  
7
Groove tube  
Number of circuit  
[OUTDOOR AIR CIRCUIT]  
Number of fans  
Diameter of fan  
Blower drive  
1
2
600  
1
800  
mm  
Direct drive  
1
0.35  
1.2  
1
0.35  
1.2  
Quantity of motor  
Fan motor output  
Fan motor run current  
2
2X0.09  
0.7  
kW  
A
L/s  
1583  
2783  
3333  
Nominal air quantity  
[CONDENSER]  
Number of condensers  
Face area  
2
2X2.1  
2
1
1.3  
1
1.58  
sq.m  
Rows deep  
Rows high  
44  
30  
44  
mm  
m/s  
Finned length  
Face velocity  
1000  
1.56  
2706  
1.35  
1400  
1.95  
Fin per meter/Pitch  
Fin material thickness  
Fin material/Type  
Tube diameter/Gauge  
Pipe type  
513/1.95  
474 /2.11  
0.115  
Aluminium / Ring  
513 /1.95  
mm  
mm  
9.52 / 0.35  
Groove tube  
7
Number of circuit  
11  
11  
Specifications subject to change without noice  
*1 Corrosion proof property : Salt spray JIS Z 2371, 500hrs Humiditiy test 50C 98% 500hrs.  
*2 Corrosion proof property : Salt spray JIS Z 2371, 1000hrs Humiditiy test 50C 98% 1000hrs.  
- 82 -  
Product number  
Indoor unit  
Outdoor unit  
PEH-5MYA-EU  
PUH-5MYE-EU  
PEH-7MYA-EU  
PUH-7MYC1-EU  
PE-8MYA-EU  
PUH-8MYC1-EU  
PUH-8MYE-EU  
[ENCLOSURE AND FRAME]  
428  
mm  
mm  
mm  
mm  
mm  
mm  
height  
width  
depth  
height  
width  
depth  
1095  
1415  
Dimension  
Indoor unit  
650  
980  
1400  
1175  
1000  
550  
1175  
1250  
550  
Outdoor unit  
Dimension  
700  
External finish (indoor unit)  
Galvanized steel  
Acrylic resin coationg (Color: Munsell 5Y8/1)  
(outdoor unit)  
External finish  
mm  
mm  
kg  
1.2  
25.4  
Panel thickness  
Condense drain size  
Weight Indoor unit  
Weight Outdoor unit  
Sound pressure level (indoor unit)  
Sound pressure level (outdoor unit)  
Sound power level (indoor unit)  
Sound power level (outdoor unit)  
60  
150  
67  
211  
70  
56  
64  
kg  
214  
65  
188  
dbA  
dbA  
dbA  
dbA  
55  
63  
57  
68  
76  
- 83 -  
PEH-10,15,20MYA-EU  
]
[
PRODUCT  
PACKAGE AIR COOLED HEATPUMP UNITS  
PEH SERIES  
Product type  
Product number :  
Indoor unit  
Outdoor unit  
PEH-15MYA-EU  
PUH-15MYC1-EU  
44.0  
PEH-20MYA-EU  
PUH-20MYC1-EU  
57.6  
PEH-10MYA-EU  
PUH-10MYC1-EU  
PUH-10MYE-EU  
28.8  
23.0  
10.1  
28.8  
8.3  
Cooling capacity (AS1861)  
kW  
kW  
kW  
kW  
kW  
35.2  
16.8  
44.0  
14.1  
46.0  
22.7  
57.6  
19.3  
Sensible Cooling capacity (AS1861)  
Cooling power consumption (Input)  
Heating capacity (AS1861)  
Heating power consumption  
Indoor  
Outdoor  
Indoor  
Basic temperature condition cooling  
Basic temperature condition cooling  
Basic temperature condition heating  
Basic temperature condition heating  
27 DB/19 WB  
35 DB  
21 DB  
7
DB/6 WB  
Outdoor  
[ELECTRICAL]  
<Indoor unit>  
Volts  
Hz  
Design voltage  
415  
50  
Cy  
cles  
Power supply  
Volts  
3PH-415V  
240/24  
415  
Control voltage  
Voltage change  
Voltage change  
Fan motor output  
Fan motor current  
Max.  
Min.  
Volts  
Volts  
HP(kW)  
Amps  
380  
1.34(1.0)  
2.0  
1.34(1.0)  
2.0  
2.95(2.20)  
4.1  
4.96(3.70)  
4.7  
<Outdoor unit>  
Design voltage  
Cycles  
Volts  
Hz  
415  
50  
Power supply  
Voltage change  
Voltage change  
Fan motor output  
Fan motor current  
Volts  
Volts  
Volts  
HP(kW)  
Amps  
3PH-415V  
415  
Max.  
Min.  
380  
2X0.2(2X0.15)  
1.0  
0.47(0.35)  
1.2  
2X0.47(2X0.35)  
2X1.2  
[COMPRESSOR]  
Make  
Model  
MITSUBISHI  
JH521YE  
HERMETIC LINE START (RECIPROCATING)  
JH527YE  
JH527YE  
Type  
Number of compressor  
Nominal motor  
Locked rotor current  
Normal run current (AS1861)  
Swept volume  
Bore  
1
10.1(7.5)  
85  
19.2  
201  
2
HP(kW)  
Amps  
Amps  
cc/rev  
mm  
7.4(5.5)  
83  
15.5  
10.1(7.5)  
85  
19.2  
160.8  
201  
ø44.45  
25.9  
Stroke  
mm  
rpm  
Speed  
Number of cylinders  
2900  
5
4
5
ml  
4500  
3000  
4500  
Oil charge  
Type of oil  
DIAMOND MS32(N-1) OR SUNISO 3GS(D)  
watts  
72  
62  
72  
Crankcase heater  
[REFRIGERATION SYSTEM]  
Refrigerant  
R22  
kg  
6.6  
9.7  
Refrigerant charge per circuit  
Number of refrigerant controls  
Refrigerant control  
Reverse cycle valve  
Defrost system  
9.9  
1
2
Capillary tube  
4-way valve  
Reverse cycle defrost  
50  
m
Limit of pipe's length  
mtrs  
mtrs  
20 (In case of indoor unit above outdoor unit)  
30 (In case of outdoor unit above indoor unit)  
Limit of pipe's height difference  
- 84 -  
Product number  
Indoor unit  
Outdoor unit  
PEH-15MYA-EU  
PUH-15MYC1-EU  
PEH-20MYA-EU  
PUH-20MYC1-EU  
PEH-10MYA-EU  
PUH-10MYC1-EU  
PUH-10MYE-EU  
[INDOOR AIR CIRCUIT]  
2
Number of blowers  
Diameter of blowers  
Width of blowers  
mm  
mm  
250  
275  
Direct drive  
280  
245  
275  
Belt drive  
Blower drive  
1.00  
2.0  
1500  
1.00  
1.8  
1500  
2.20  
4.5  
2333  
3.70  
4.7  
3000  
kW  
A
L/s  
Pa  
mm  
mm  
Fan motor output  
Fan motor run current  
Nominal air quantity  
External static pressure  
Supply air dimensions(hxw)  
Return air dimensions(hxw)  
[EVAPORATOR]  
125  
200  
341X1302  
342X1318  
412X1000  
412X1209  
248X998  
596X1415  
Number of evaporator  
Face area  
1
0.50  
2
sq.m  
0.86  
0.98  
Rows deep  
4
15  
1300  
3.0  
24  
Rows high  
Finned length  
Face velocity  
1415  
2.7  
1615  
3.0  
mm  
m/s  
513/1.95  
513/1.95  
0.115  
592/1.69  
Fin per meter / pitch  
Fin material thickness  
Fin material/Type  
Fin coating  
mm  
Aluminium / Ring  
NA 510 D*1 (NA 549*2)  
mm  
mm  
9.52  
0.35  
Tube diameter  
Gauge of copper tube  
Pipe type  
Groove tube  
16  
Plain tube  
Number of circuit  
10  
24  
[OUTDOOR AIR CIRCUIT]  
Number of fans  
Diameter of fan  
Blower drive  
2
600  
1
2
mm  
800  
Direct drive  
1
0.35  
1.2  
2
Quantity of motor  
Fan motor output  
Fan motor run current  
2
kW  
A
2X0.15  
1.0  
2X0.35  
1.3  
L/s  
3167  
2X3083  
3333  
Nominal air quantity  
[CONDENSER]  
Number of condensers  
Face area  
2
1
1.58  
2
sq.m  
2X2.1  
2X1.07  
2X1.32  
Rows deep  
3
Rows high  
30  
44  
37  
mm  
m/s  
Finned length  
Face velocity  
2706  
1.35  
1400  
1.95  
2800  
2.89  
2.34  
Fin per meter/Pitch  
Fin material thickness  
Fin material/Type  
Tube diameter/Gauge  
Pipe type  
474/2.11  
513/1.95  
0.115  
Aluminium / Ring  
474 /2.11  
mm  
mm  
9.52 / 0.35  
Groove tube  
Number of circuit  
11  
11  
14  
16  
Specifications subject to change without noice  
*1 Corrosion proof property : Salt spray JIS Z 2371, 500hrs Humiditiy test 50ËšC 98% 500hrs.  
*2 Corrosion proof property : Salt spray JIS Z 2371, 1000hrs Humiditiy test 50ËšC 98% 1000hrs.  
(anti corrosion as special order)  
- 85 -  
Product number  
Indoor unit  
Outdoor unit  
PEH-15MYA-EU  
PUH-15MYC1-EU  
PEH-20MYA-EU  
PUH-20MYC1-EU  
PEH-10MYA-EU  
PUH-10MYC1-EU  
PUH-10MYE-EU  
[ENCLOSURE AND FRAME]  
428  
1615  
650  
706  
865  
1200  
1951  
1080  
mm  
mm  
mm  
mm  
mm  
mm  
height  
width  
depth  
height  
width  
depth  
1690  
1993  
Dimension  
Indoor unit  
980  
1400  
700  
1175  
1250  
550  
Outdoor unit  
Dimension  
External finish (indoor unit)  
Galvanized steel  
Acrylic resin coationg (Color: Munsell 5Y8/1)  
(outdoor unit)  
External finish  
mm  
mm  
kg  
1.2  
25.4  
Panel thickness  
Condense drain size  
Weight Indoor unit  
Weight Outdoor unit  
Sound pressure level (indoor unit)  
Sound pressure level (outdoor unit)  
Sound power level (indoor unit)  
Sound power level (outdoor unit)  
180  
431  
61  
212  
472  
62  
84  
221  
kg  
240  
dbA  
dbA  
dbA  
dbA  
59  
65  
67  
76  
69  
80  
69  
70  
- 86 -  
INSTALLATION  
Space required around unit.  
1.  
Indoor unit  
Dimension of the unit and space necessary for sevicing.  
PE(H)-15,20  
PEH-5 PE(H)-7, 8, 10  
180  
380  
B
A
200  
400  
B
A
Ceiling access panel  
Ceiling access panel  
A
B
A
B
PEH - 5  
PE(H) - 7, 8  
PE(H) - 10  
1560 1000  
1880 1320  
2080 1520  
PE(H) - 15  
PE(H) - 20  
2187 1587  
2490 1890  
Outdoor unit  
Secure enough space necessary for servicing, installing, and for proper function of the unit.  
To prevent short-cycling, remove obstacles as much as possible.  
PUH-5, 8, 10 (Side blow)  
(1) At a single installation  
Service panel  
Inlet surface  
150 over  
Inlet surface  
150 over  
150 over  
500 over  
Inlet  
surface  
Inlet  
surface  
Outlet surface  
300 over  
Outlet surface  
Service panel  
With the inlet surface facing a wall.  
With the outlet surface facing a wall.  
(2) Relation of unit when many set up unit.  
300  
over  
500 over  
500 over  
500 over  
500 over  
Please set the unit that the inlet air and the outlet air are not influenced.  
- 87 -  
PU(H)-7,8, 10 (Upper blow)  
(1) At a single installation  
The obstacle is on the outlet side. (Fig 1)  
The obstacle is in three directions. (Fig 2,3)  
The obstacle is in four directions. (Fig 4)  
ceiling  
1200  
over  
However, the  
outlet side must  
be opened.  
The right and left side  
and the back and forth  
side must be opened.  
300 over  
500 over  
Service Panel  
Fig 2  
Fig 1  
If this side is service  
panel, you need 500  
over. If this side is inlet,  
you need 300 over.  
All "A" is 500 over.  
However, outlet side  
must be opened.  
And the obstacle in  
two directions must be  
lower than the unit.  
However, if the service  
panel is an interior side,  
the right or left side  
need 500 over.  
A
A
300 over  
300 over  
Fig 3  
Fig 4  
(2) Relation of unit when many set up unit. (Fig 5,6,7)  
If this side is  
service panel,  
you need 500 over.  
If this side is inlet,  
you need 300 over.  
Service-panel  
A
A
A
A
300 over  
300 over  
500  
over  
500 over  
300 over  
Fig 6 All "A" is 500 over.  
Fig 5  
Service-panel  
A
A
A
A
A
Fig 7 All "A" is 500 over in any case.  
- 88 -  
PU-15  
(1) At a single installation  
The obstacle is on the outlet side. (Fig 1)  
The obstacle is in four directions. (Fig 2)  
300 over  
500 over  
ceiling  
However, the outlet  
1500  
over  
side must be opened.  
The right and left side  
and the back and forth  
side must be opened.  
300 over  
300 over  
Service Panel  
Fig 1  
Fig 2  
(2) Relation of unit when many set up unit. (Fig 3,4)  
If this side is service panel, you  
need 500 over.  
If this side is inlet, you need 300 over.  
Service-panel  
If this side is  
If this side is  
service panel, you  
need 500 over.  
If this side is inlet,  
you need 300 over.  
service panel, you  
need 500 over.  
If this side is inlet,  
you need 300 over.  
500  
A
A
A
over  
300 over  
300 over  
Fig 4 All "A" is 500 over.  
Service-panel  
Fig 3  
PU-20  
(1) At a single installation  
The obstacle is on the outlet side. (Fig 1)  
The obstacle is in four directions. (Fig 2)  
300 over  
However, the outlet  
side must be opened.  
ceiling  
500 over  
1500  
over  
300 over  
300 over  
The right and left side  
and the back and forth  
side must be opened.  
Service Panel  
Fig 2  
Fig 1  
(2) Relation of unit when many set up unit. (Fig 3,4,5)  
300 over  
500 over  
Service-panel  
If this side is  
If this side is  
servicepanel, you  
need 500 over.  
servicepanel, you  
need 500 over.  
500  
If this side is inlet,  
you need 300 over.  
If this side is inlet,  
you need 300 over.  
300 over  
over  
A
A
A
300 over  
A
Service-panel  
Fig 4 All "A" is 500 over.  
Fig 3  
If this side is  
service panel, you  
need 500 over.  
If this side is inlet,  
you need 300 over.  
300 over  
A
A
A
300 over  
Fig 5 All "A" is 500 over in any case.  
- 89 -  
PUH-15, 20  
(1) At a single installation  
The obstacle is on the outlet side. (Fig 1)  
The obstacle is in four directions. (Fig 2)  
The obstacle is in three directions. (Fig 3,4)  
ceiling  
1500  
over  
However, outlet side  
must be opened.  
500 over  
300 over  
The right and left side  
and the back and forth  
side mustbeopened.  
And the obstacle in  
two directions must be  
lower than the unit.  
300 over  
Service Panel  
Fig 2  
Fig 1  
However, the outlet side must be opened.  
300 over  
Service-panel  
500 over  
300 over  
300 over  
Service-panel  
Fig 3  
Fig 4  
(2) Relation of unit when many set up unit. (Fig 5,6,7)  
500 over  
Service-panel  
If this side is  
If this side is  
servicepanel, you  
need 500 over.  
servicepanel, you  
need 500 over.  
500  
If this side is inlet,  
you need 300 over.  
If this side is inlet,  
you need 300 over.  
300 over  
over  
300 over  
A
A
A
A
Service-panel  
Fig 5  
Fig 6 All "A" is 500 over.  
If this side is  
service panel, you  
need 500 over.  
If this side is inlet,  
you need 300 over.  
300 over  
A
A
A
300 over  
Fig 7 All "A" is 500 over in any case.  
2. Preparation before installing  
Reinforcement  
Indoor unit  
Please use the specified hanging bolt in any case.  
Hanging bolt is local supply.  
Please use the method below or use the angle and the  
rectangular lumber, etc. and install the hanging bolt.  
Insert etc  
100-150kg  
Hanging bolt  
M10 (PEH-5,PE(H)-7,8,10)  
M12 (PE(H)-15,20)  
- 90 -  
3. Installation of the unit.  
Indoor unit  
Please carry the packed until parallelly to installed place.  
Please install the unit before construction of the ceiling -lined.  
PEH-5 PE(H)- 7, 8, 10  
U washer  
Nut  
Washer  
Nut  
PE(H)- 15, 20  
Nut (M10)  
Nut (M10)  
Washer  
Washer  
Ceiling  
Nut (M10)  
Nut (M10)  
Outdoor unit  
Fix unit tightly with bolts as shown below so that unit will be securely fixed  
in place use concrete or angle foundation of unit.  
At the time of bottom piping of refrigerant pipe, build a 100mm or higher  
foundation so that piping will go through bottom of unit.  
Anchor bolt (local arrangement)  
PUH-5 PU(H)-7, 8, 10 M8  
PU(H)-15, 20  
M10  
Installation pitch  
Concrete foundation  
- 91 -  
Duct construction.  
Provide canvas flexible ducting between unit when connect to the duct-work.  
The duct unit must use a nonflammable material.  
Provide sufficient insulation for prevent dewdrop.  
Duct earth  
Canvas Duct  
Duct earth  
Canvas Duct  
Duct  
Duct  
Drain pan  
Inlet  
Outlet  
Duct-work length 850mm or more  
Lifting method.  
When the unit is to be lifted and moved, attach ropes to the suspension plates(3 p.c.s)  
provided on the top of the unit.  
When the unit is lifted, it 's center of gravity tends to shift the unit one side and so balance,  
such as that in the figure below, should be attained.  
The angles at which the ropes suspend the unit should be at least 60 at the compressor end  
and at least 45 at the condenser end. Care should be taken to avoid contact with the main unit  
while carrying.  
It is necessary to protect the unit with the blanket so that the ropes should not injure the unit.  
Hook (as directly aligned over  
the center of gravity as possible.  
MITSUBISHI  
ELECTRIC  
Example PUH-15, 20  
- 92 -  
Piping connection  
Warning.  
Please follow the following procedures, during the piping connection work is carried out.  
If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve.  
It might cause the injury.  
In case of Brazing type  
1. Open the ball valve cap before removing the by-pass tube.  
Then, turn the knob of the ball valve from ’close’ to ’open’  
position.  
2. Please repeat to close and open the ball valve of gas and liquid side at the same time (3 times or more).  
And finally make sure the ball valve is at close position.  
CLOSE  
OPEN  
3. Cut part A (two places) of the by-pass tube as shown in figure below.  
Caution  
CUT  
There will be small amount of refrigerant gushed  
out of the by-pass tube at the moment.  
CUT  
4. Make sure that the ball valve is wrapped with enough wet cloth, during the brazing of the by-pass tube  
(for cooling purpose). Make sure the temperature of ball valve is below 100 degree centigrade. (If the  
temperature of the ball valve is over 100 degree centigrade, the refrigerant and valve sheet might gush  
out from the ball valve. It might cause the injury.)  
enough wet  
cloth  
5. Please make sure the ball valve is cool enough when removing the by-pass tube. Wait for a while for  
further cooling of the ball valve, before the piping connection work begins.  
6. When the piping connection begins. Again, make sure that the ball valve is wrapped with enough wet  
cloth, during the brazing for cooling the ball valve. Make sure the temperature of ball valve is below 100  
degree centigrade. (If the temperature of the ball valve is over 100 degree centigrade, the refrigerant and  
valve sheet might gush out from the ball valve. It might cause the injury.)  
7. Before charging the refrigerant, vacuum the pipes to clear all the air and water.  
8. Charge the additional amount of refrigerant according to the table.  
9.Turn the knob of the ball valve to ’open’ position after leak check.  
10. Finally, put the cap back to the ball valve.  
- 93 -  
In case of Flare, Flange type  
1. PROCEDURE TO CONNECT THE EXTENSION PIPE.  
Proceed with the connection as follows:  
(1) Open the ball valve cap before cutting the by-pass tube.(Fig.1)  
(2) Check the ball valve section is completely closed.(Fig.2)  
(3) Cut two parts of the by-pass tube.(Fig.4)  
Fig. 1  
Valve knob  
Caution  
Valve knob  
There will be small amount of refrigerant gushed out  
of the by-pass tube at the moment.  
(4) Remove the connection pipe assy.(Fig.5)  
Throw away the packing.  
Open  
Close  
Fig. 2  
cut  
Fig. 3  
Do not brazing the pipe while the flange assy connect the ball  
valve. (Except the PUH-5)  
(5) Remove the by-pass tube.(Fig.6)  
Braze the extension pipe with the flange assy. (Except the PUH-5)  
cut  
(6) Connect the extension pipes with the packing between the ball  
valve and the flange.(Fig.7)  
Fig. 4  
Use the attached new packing certainly.  
Pipe assy  
Unit side  
Fig. 5  
2. HANDLING PRECAUTIONS.  
(1) The extension pipes should be connected with the valve knob  
completely closed. (Fig.2)  
throw away  
Check leak test the part of flange and flare.  
By-pass tube  
(2) Before charging the refrigerant, vacuum the pipes to clear all the air  
and water.  
Flange assy  
Extension pipe  
(3) Charge the additional amount of refrigerant according to the table.  
(4) Turn the ball valve knob to "Open" position after leak check again.  
(Fig.3)  
Fig. 6  
(5) Finally, put the cap back to the ball valve.  
Unit side  
Extension pipe  
Fig. 7  
use the attached new packing  
- 94 -  
Refrigerant piping.  
4.  
Extension piping and installation parts are field supply.  
Perform the work only after carefully reading the  
appropriate instructions.  
A
Install the unit where the refrigerant piping is shortest,  
the difference between the indoor unit and outdoor unit  
is smallest.  
When the outdoor unit is lower.  
As pipes purchased in the market may contain  
dust, below them off with dry inlet gas.  
Take care not to allow dust and water content to enter  
the piping during pipe processing or installing.  
Minimize the number of bends, and make the bending  
radius as long as possible.  
B
Always observe the restriction(allowable length, height  
difference, pipe diameter) on the refrigerant piping.  
For soldering & brazing, use high-quality materials.  
When the outdoor unit is higher.  
Never purge air with a refrigerant. Always use a vacuum pump for purging.  
Provide proper insulation to the piping . Insufficient insulation cause poor cooling/heating  
performance or condensation drip, leading to unexpected trouble.  
Do not insulate gas or low pressure pipe and liquid or high pressure pipe together.  
For the connection of the refrigerant piping, leave the valve of the outdoor unit fully closed  
(as set before shipment), and no operate it until the connection between the indoor/outdoor  
units and refrigerant piping, refrigerant leak test and evacuation work have been completed.  
The maximum permissible values are shown below.  
Remove the cover (grommet) attached sheet metal at exit of heat exchanger pipe of indoor  
unit before connecting the local piping.  
(This cover is protect the pipe from sheet metal edge at unit transportation.)  
Please insulate liquid pipe & gas pipe (two places for each) with an insulated pipe of the  
attachment after connecting piping.  
Bad example  
Good example  
Finishing tape  
Insulating material  
Insulating material  
Finishing tape  
Liquid pipe  
Liquid pipe  
Electric wire  
Gas pipe  
Electric wire  
Gas pipe  
PEH-5 PE(H)-7 PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20  
Dimension A (m)  
20  
20  
20  
20  
20  
20  
Dimension B (m)  
Number of bends  
30  
15  
50  
30  
15  
50  
30  
15  
50  
30  
15  
50  
30  
15  
50  
30  
15  
50  
Total piping length (m)  
Liquid pipe (mm)  
Piping  
12.7  
15.88  
25.4  
15.88  
25.4  
15.88  
28.6  
2x15.88 2x15.88  
2x25.4 2x28.6  
size  
Gas pipe (mm)  
19.05  
- 95 -  
Airtight test  
Airtight test should be made by pressurizing nitrogen gas to 3Mpa.  
For the test method, refer to the following figure.  
(Make a test with the valve closed. Be also sure to pressurize both liquid and gas pipe.)  
The test result can be judged good if the pressure has not been reduced after leaving  
for about one day after completion of nitrogen pressurization.  
Nitrogen gas  
To indoor unit  
System analyzer  
Low knob  
a.  
b.  
c.  
d.  
e.  
f
b
g
h
i
High knob  
c
Valve  
f.  
Liquid gas  
g.  
e
d
a
j
Gas pipe  
Outdoor unit  
Service port  
h.  
i.  
j.  
Evacuation  
Evacuation should be made from the service port provided on the outdoor unit’s valve to  
the vacuum pump commonly used for both liquid pipe and gas pipe.  
(Make evacuation from both liquid pipe and gas pipe with valve closed.)  
Remember :Never carry out air purge by refrigerant.  
System analyzer  
To indoor unit  
a.  
b.  
c.  
d.  
e.  
e
b
f
Low knob  
High knob  
h
Valve  
Liquid gas  
g
a
f.  
g.  
c
d
Gas pipe  
i
j
h.  
i.  
j.  
Outdoor unit  
Service port  
Vacuum pump  
Additional refrigerant charge  
The mount of refrigerant charged in this unit is a appropriate for 5-meter long refrigerant pipes.  
Refer to the table below and add the corresponding amount of refrigerant if the pipes are  
extended.  
The outdoor unit of PE-5,8,10 have side  
blow type and upper blow type.  
(The refrigerant is charged in the outdoor unit.)  
Factory charge refer to the table below.  
Factory charge  
Refrigerant piping length  
30m 35m 40m 45m 50m  
5m 10m 15m 20m 25m  
Outdoor unit  
unit  
PU-7  
Upper blow  
Side blow  
PU-8  
PU-7  
5.7  
5.0  
0
0.8 1.6  
2.4 3.2 4.0 4.8 5.6  
6.4 7.2  
PU-10  
PU-15  
PU-8  
charge  
mount  
R-22  
PU-10  
PU-15  
PU-20  
8.7  
0
2x0.8 2x1.6 2x2.4 2x3.2 2x4.0 2x4.8 2x5.6 2x6.4  
2x7.2  
PU-20  
charge  
mount  
R-22  
2x4.8  
2x9.7  
0
0
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5  
0.8 1.6 2.4 3.2 4.0 4.8 5.6 6.4 7.2  
PUH-5  
PUH-7  
PUH-8  
PUH-10  
PUH-15  
PUH-20  
(kg)  
5.0  
PUH-5  
(kg)  
PUH-7  
PUH-8  
PUH-10  
5.7  
6.6  
9.9  
0
0
0.8 1.7 2.5 3.3 4.2 5.0 5.8 6.7 7.5  
PUH-8  
6.6  
9.9  
PUH-10  
2x0.8 2x1.7 2x2.5 2x3.3 2x4.2 2x5.0 2x5.8 2x6.7  
2x7.5  
PUH-15 2x6.6  
2x9.7  
PUH-20  
- 96 -  
Drain piping  
5.  
•Incline the drain piping to the outside (drain side) as shown in the figure below.  
•The outlet of the indoor unit drain pipe is Rc1.  
•After completion of piping, confirm that drainage is good and that there are no leaks.  
Indoor unit drain piping  
Install thermal insulation  
to prevent dew  
The drain piping should have a drain trap.  
>
A 70mm  
=
>
>
x
B= 2 C= 70mm  
Slope  
20mm/m  
>
C 35mm  
=
Drain piping  
Drain pan  
The drain pipe  
should extend  
Drain trap  
Open drain  
below this level.  
- 97 -  
Electric wiring  
6.  
Construct the earth connection.  
All electrical work must be carried out by a suitable qualified electrical trades-person and in  
accordance with local supply authority requirements and associated regulators.  
The outdoor unit is to be wired directly from an electrical distribution board either by a circuit  
breaker (preferred) or HRC fuse.  
Fix power source wiring to control box by using buffer bushing for tensible force (PG  
connection or the like). Connect control wiring to control terminal block through the knockout  
hole of control box using ordinary bushing.  
NOTE: Earth wiring must be connected.  
Arrangement such as terminal block in control box  
Control module of indoor unit  
Control module of indoor unit  
PEH-5, PE(H)-7, 8,10  
PE(H)-15, 20  
PE(H)-7 only  
Terminal block for  
connection wires to  
Outdoor unit and  
remote controller  
PEH-15, 20 only  
F1  
30FZ  
F1 3.15A  
F1  
Tr  
Terminal block for  
connection wires to  
Outdoor unit and  
remote controller  
C
FZ  
F2 3.15A  
F2  
TB3  
F2  
30FZ  
PEH-15, 20 52F&51F1  
PE-15, 20 52F1&51F1  
CZ1-1  
PEH only  
Tr  
52F  
&
51F1  
CZ1-2  
TB3  
Terminal block for  
power supply wires  
Terminal block for  
power supply wires  
FZ  
TB2  
PEH-15, 20 HZ1  
PE-15, 20  
FZ  
HZ1  
CZ1  
TB2  
Screw for earth  
connection  
Bush and band for  
the power supply  
Bush and band for  
the power supply  
Bush for the thermistor  
Bush for the thermistor  
Screw for earth  
connection  
Bush and band for the connection wires  
to Outdoor unit and remote controller  
Bush and band for the connection wires  
to Outdoor unit and remote controller  
Control module of outdoor unit (PUH-5, 8, 10)  
Side blow  
Screw for earth  
connection  
51F2  
30CZ  
X3  
T1  
X2  
F3  
52C  
&
51C  
Terminal block  
for power supply  
wires  
CZ2 HZ2  
TB1  
TB4  
X1  
Terminal block for  
connection wires  
to Indoor unit  
Band for wires  
- 98 -  
Control module of outdoor unit PU-15  
Control module of outdoor unit PU(H)-7, 8, 10  
Upper blow  
PUH only  
F3  
Terminal block for  
power supply wires  
T1  
F3  
52C  
&
51C  
2
F3 3.1  
52C1  
&
51C1  
52C2  
&
51C2  
52F2  
&
PUH only  
TB1  
51F2  
30CZ1 30CZ2  
CZ  
CZ  
51F2  
2-1 2-2  
TB4  
X1  
PUH only  
Screw for earth  
connection  
Terminal block for  
connectioon wires  
to Indoor unit  
Terminal block for  
connection wires to  
Indoor unit  
Bush for wires  
TB5  
X2  
X3  
Screw for earth  
TB1  
connection  
Terminal block for  
power supply wires  
Band for wires  
Control module of outdoor unit PU-20  
Control module of outdoor unit PUH-15,20  
52F2&  
51F2  
Screw for earth  
connection  
52C2  
&
51C2  
51F3  
51F2  
51F3  
X3  
X4  
X5  
T1  
T2  
2
F3  
52C1  
&
51C1  
52C2  
&
51C2  
30 30  
CZ1CZ2  
52C1  
2
X1  
X2  
X6 30CZ1 30CZ2  
CZ  
CZ  
&
TB1  
51C1  
2-1 2-1  
HZ2  
TB4  
CZ  
2-2  
CZ  
2-1  
Screw for earth  
connection  
TB4  
Terminal block for  
connection wires  
to Indoor unit  
F3  
TB1  
Terminal block for  
connectioon wires  
to Indoor unit  
Terminal block for  
power supply wires  
Bush for wires  
Terminal block for  
power supply wires  
Bush for wires  
- 99 -  
Method for connecting electric wire  
Please do the wiring after consulting the electric power  
company of jurisdiction beforehand in the instruction.  
(1) The entire wiring diagram of unit.  
a
a
Power supply  
b. Main switch/fuse (field supply)  
a.  
b
d
b
PE  
PE  
c.  
Power supply wiring for outdoor unit  
Power supply wiring for indoor unit  
In case of PE-7,8,10  
In case of PE-15,20  
j
j
c
d.  
e.  
Outdoor unit  
Indoor unit  
PEH-5, 7, 8, 10  
f.  
g
Connection wiring for indoor  
/ outdoor units (polarity)  
In case of PEH-15,20  
g.  
i
In case of PE-7, 8, 10  
e
f
Remote controller (field supply)  
h.  
In case of PE-15, 20  
h
PEH-5, 7, 8, 10  
Connection wiring for indoor  
/ remote controller (no polarity)  
i.  
j.  
In case of PEH-15, 20  
Earth  
(2) Power supply construction and electric wiring connection of indoor and outdoor unit.  
In case of  
PEH-5  
In case of PE(H)-15,20  
PE(H)-7,8,10  
B
G
H
H
A
3phase  
PE(H)-7:Single phase  
PE  
N
L1  
L2  
L3  
13 14 15  
11 12 13 14  
PEH-5  
PE(H)-7,8,10  
PE(H)-15,20  
15A  
15A  
30A  
C
C
D 3 phase  
PUH-5  
50A  
50A  
60A  
100A  
125A  
PU(H)-7,8  
PU(H)-10  
PU(H)-15  
PU(H)-20  
PEH only  
PEH only  
13 14 15  
PE  
N
L1  
L2  
L3  
11 12 13 14  
G
H
H
E
F
Indoor unit  
A.  
B. Power cable wiring  
Control cable wiring  
C.  
(Fixing wire-- Do not remove)  
D. Outdoor unit  
Breaker  
E.  
F. Fuse  
G. Power supply terminal bed  
H. Control cable terminal bed  
- 100 -  
(3) Indoor unit and remote controller.(OPTION:PAC-204RC)  
Connect the wires on the basis of the following wiring diagram.  
PE(H)-15,20  
PEH-5, PE(H)-7,8,10  
TB4  
1
TB3  
1
GRAY  
GRAY  
F2  
(3.15A)  
F2  
(3.15A)  
Tr  
Tr  
AC24V  
GRAY  
AC  
220  
240V  
AC24V  
GRAY  
AC  
220  
240V  
TB4  
TB3  
2
3
2
3
4
CZ CZ  
1-1 1-2  
FZ  
FZ  
CZ1  
4
5
(4) Wiring example (For metal piping)  
Over current  
Breaker  
capacity  
Power  
cable  
Control  
Earth cable  
protection switch  
wiring  
15A  
15A  
15A  
PEH - 5  
2.0mm2  
15A  
15A  
15A  
2.0mm2 over  
2.0mm2over  
2.0mm2over  
2.0mm2over  
2.0mm2over  
PE(H) - 7 2.0mm2  
PE(H) - 8 2.0mm2  
Cable or  
wire of  
0.75mm2  
(24VDC)  
2.0mm2  
2.0mm2  
15A  
30A  
15A  
30A  
PE(H) -10  
PE(H) -15  
2.0mm2  
30A  
2.0mm2over  
30A  
PE(H) -20  
8mm 2  
50A  
50A  
8mm2over  
8mm2over  
PUH - 5  
PU(H) - 7 8mm 2  
50A  
50A  
The grounding wire must be of the same  
diameter as the power cable wires.  
Table above is an example.  
The selection of other capacities should be  
determined in accordance with the relevant  
standards.  
Cable or  
8mm 2  
50A  
60A  
8mm 2over wire of  
PU(H) - 8  
50A  
0.75mm2  
(24VDC)  
PU(H) -10 14mm2  
PU(H) -15 14mm2  
PU(H) -20 22mm2  
60A  
14mm2 over  
14mm2 over  
22mm2 over  
100A  
125A  
100A  
125A  
(5) Selecting earth leakage breaker (NV)  
To select NF or NV instead of a combination of Class B fuse switch use the following.  
In the case of Class B fuse rated 15A.  
Fuse  
Earth leakage breaker  
(class B)  
(with over-load protection)  
NV is a product of  
PEH - 5  
15A  
15A  
15A  
15A  
NV30-CA  
15A 30mA 0.1s or less  
15A 30mA 0.1s or less  
15A 30mA 0.1s or less  
15A 30mA 0.1s or less  
MITSUBISHI ELECTRIC.  
Table above is an example.  
The selection of other  
capacities should be  
PE(H) - 7  
PE(H) - 8  
PE(H) - 10  
NV30-CA  
NV30-CA  
NV30-CA  
determined in accordance with  
the relevant standards.  
PE(H) -15  
PE(H) -20  
PUH - 5  
30A  
30A  
50A  
NV50-CP  
NV50-CP  
NV50-CA  
30A 30mA 0.1s or less  
30A 30mA 0.1s or less  
50A 100mA 0.1s or less  
Note.  
PU(H) - 7  
PU(H) - 8  
PU(H) - 10  
PU(H) - 15  
PU(H) - 20  
50A  
50A  
NV50-CA  
NV50-CA  
NV60-CA  
50A 100mA 0.1s or less  
50A 100mA 0.1s or less  
60A 100mA 0.1s or less  
All electrical wiring must be  
comply with local electrical  
authority regulations.  
60A  
100A  
125A  
NV100-CP 100A 100mA 0.1s or less  
NV225-CP 125A 100mA 0.1s or less  
- 101 -  
7. The putting condition of the belt.  
(PE(H)-15,20 only)  
1.Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below.  
2.Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1  
below at the proper flexion. (A=4.5mm)  
3.Adjust the suitable tension after the belt sit properly across the pulley (after more 24-28 hours working).  
When the new belt is used, adjust the suitable tension about the 1.3 times of the maximum value of the  
flexion load.  
4.Readjust the belt every 2,000 hours after the first adjustment.  
Exchange the belt when the belt's surroundings length has expanded by 2% including the first expansion  
of the belt. (about 1%)  
(about 8,000 hours converted working time)  
table  
parallel angle  
note  
K ( )  
pulley  
pulley  
10 or less gap of 3mm every 1m  
K
Flexion load(W)  
1.4 2.2kg  
K
K
A
A=4.5mm  
K
Figure1 Parallel degree of pulley  
Figure2 Belt tension  
8. Before starting the Trial run.  
Check items  
(1) Check to see wheter there are refrigerant leakage, and slack power or transmission cable.  
(2) Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and  
ground.  
(3) Do not operate in the case of 1.0M ohm or less.  
Note : Never carry out megger-ohm check over terminal control board.  
Otherwise the control board would be broken.  
(4) Check to see wheter both gas and liquid valves are fully opened.  
Note : Be sure to tighten caps.  
(5) Turn universal power supply at least 6 hours before gettig test run in order to current to crank heater.  
If current-carrying hours are too short, it may result in a malfunction of compressor.  
(6) Confirm operation of high-pressure switch.  
If the two lead wires of the outdoor unit fan motor are disconnected from the connector and cooling  
is performed, the high-pressure switch should operate and stop the unit after 5 to 10 minutes.  
(7) Confirm that the fans of the indoor and outdoor unit rotate in the correct direction.  
Change the power supply phase connections if it is rotating in the reverse direction.  
Perform trial operation after completion of the above items.  
- 102 -  
INSTRUCTIONS FOR USE  
1.Check points for operation.  
Check the following points before you operate your air conditioner.  
(1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet.  
Indoor unit  
Inlet grille  
Outlet grille  
Ceiling  
Ceiling  
Obstacle blocking air outlet  
Obstacle blocking air inlet  
Outdoor unit  
Obstacle blocking air inlet.  
(2)Make sure the air conditioner is properly grounded by checking the ground terminal.  
Ground  
- 103 -  
2.Caution for use.  
Keep the following points in mind to safeguard against failures and breakdowns.  
(1) This air conditioner does not restart within 3min.  
after shut down.  
3 Minutes  
(These models have a crankcase heater in the  
compressor. If the air conditioner is shut down  
for a short time, please do not turn the power  
switch to OFF, but turn the operation switch to OFF.)  
Operation  
Shutdown  
(2) If the air conditioner is shut down by a power failure,  
set the operation switch to OFF. When the power  
is restored, normal air conditioner operation can  
be resumed.  
(3) Do not stick rods or other objects through the air  
outlet during operation since this may result in  
equipment damage or personal injury.  
3.Maintenance.  
For superior performance and lasting durability, please do not forget to conduct  
proper and regular maintenance.  
Warning  
1.Do not wash the unit with water.  
If washed with water, electrical shock may be caused.  
2.Ahead of the maintenance.  
For safety, turn the power source off before service work.  
3.1 Cleaning the Air Filter  
Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location.  
Clean more regularly if the air filter gets very dirty.  
If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate.  
Failure to clean the air filter may result in equipment breakdown or malfunctions.  
3.2 Cleaning panels  
Clean dirt off front panel as follows.  
Use a household neutral cleanser such as for dishes or  
vegetables. Moisten a soft cloth with the cleanser, then wipe  
lightly. Next,wipe three or four times with another soft cloth  
moisten with water. Finally, wipe off all the remaining  
cleanser with a soft cloth.  
Fingermarks  
Grease  
Neutral  
Cleanser  
Moisten a soft cloth with the alcohol, then wipe off lightly.  
Isopropyl alcohol is sold at stores as reagents in small  
quantities.  
Adhesive  
Paste  
Isopropyl  
alcohol  
Note:  
Alcohol is highly combustible. Take extreme care  
when handling. Also, do not use paint or adhesive  
thinner.  
- 104 -  
3.3 Cleaning the Outdoor Unit Heat Exchanger  
If you use your air conditioner for prolonged periods,  
the outdoor heat exchanger will become dirty, impairing  
its function and reducing air conditioners performance.  
Consult your equipment supplier or air conditioning  
contractor on how to clean the heat exchanger.  
Heat  
exchanger  
4.When beginning to use air conditioner again.  
Please turn on the power supply after confirming an following check is done and  
abnormality is not found.  
(1) It is confirmed that air inlet and outlet are not blocked.  
(2) It is confirmed that the earth connection line does not come off.  
The earth connection line is occasionally installed in the outdoor unit.  
(3) It is confirmed that there are neither lifting , blocking , nor bending about the drain-hose.  
Keep the power switch ON for more than 6hours before starting operation,  
to operate the crankcase heater to drive refrigerant out of oil.  
Do not turn the power supply OFF during seasons of heavy use.  
Doing so can result in failure .  
5.When the air conditioner is not to be used for a long time.  
(1) If the air conditioner is not to be used for a long time due to a seasonal change etc.,run it for 4-5hours  
with the air blowing until the inside is completely dry.  
Failing to do so can result the growth of unhygienic, unhealthy mold in scattered areas throughout  
the room.  
(2) When it is not to be used for an extended time, keep the < power supply >turned OFF.  
If the power supply is kept on, several watts or several tens of watts will be wasted.  
Also, the accumulation of dust, etc., can result in fire.  
5-1 In case of failure.  
(1) Never remodel the air conditioner.  
Consult your dealer for any repair service.  
Improper repair work can result in water leakage, electric shock, fire, etc.  
(2) If the poser breaker is frequently activated, get in touch with your dealer.  
Leaving the unit as it is under such conditions can result in fire or failure.  
(3) If the refrigeration gas blows out or leaks, stop the operation of the air conditioner.  
(4) Thoroughly ventilate the room, and contact your dealer.  
Leaving the unit as it is can result in accidents due to oxygen deficiency.  
6.Transferring work, and construction  
6-1 Transfer of installation.  
(1) When removing and reinstalling the air conditioner when you enlarge your home, remodel, or move,  
consult with your dealer in advance to ascertain the cost of the professional engineering work required  
for transferring the installation.  
(2) Please do not mix the one other than a specified refrigerant when you add the refrigerant (R-22) at the  
installation and the transferring.  
(3) When moving or reinstalling the air conditioner, consult with your dealer.  
Defective installation can result in electric shock, fire, etc.  
- 105 -  
6-2 Place for installation.  
Please do not use the unit in the following places.  
(1) Place where a lot of oil (The machine oil is contained), moistures, and dust exist.  
(2) Place where a lot of salinities such as beach districts exists.  
(3) Place where sulfur gas, volatile gas, and corroded gas are filled.  
(4) Place where acid solution is frequently used.  
(5) Place where special spray is frequently used.  
(6) Hot spring zone.  
(7) Never machine (high cycle welding machine etc.) generating highcycle.  
(8) Place where ventilation entrance of outdoor units is closed by snowfall.  
(9) The unit must be installed on stable, level surface.  
The main body might corrode when the unit is used in such a place, the refrigerant leak, the performance of  
the unit decrease remarkably, and it cause the damage of parts of the unit.  
6-3 Regarding electric work.  
(1) The electrical work must be undertaken by a person who is qualified as an electric engineer according to  
the (technical standard respecting electrical installation), (internal wiring rules), and the installation  
instruction manual with the absolute use of exclusive circuits.  
(2) Please install a special power supply in the power supply.  
(3) Please install the earth connection for the electric shock prevention.  
(4) Never connect the grounding wire to a gas pipe, water pipe, arrester, or telephone grounding wires.  
For details, consult with your dealer.  
(5) In some types of installation sites, the installation of an earth leakage breaker is mandatory. For details,  
consult with your dealer.  
(6) The breaker and the fuse must use the one of correct capacity.  
6-4 Conseration of the noise.  
(1) Take sufficient measures against noise when installing the air conditioners at hospitals or  
communication-related businesses.  
(2) If the air conditioner is used in any of the above-mentioned environments, frequent operational failure  
can be excepted.  
It is advisable to avoid these type of installation sites.  
For further details, consult with your dealer.  
(3) Choose a place where cool or warm air and noise from the outdoor air outlet of the air conditioner do  
not inconvenience the neighbours.  
(4) If any alien object is placed near the air outlet of the unit, decreased performance and increased noise  
can result.  
Avoid placing any obstacles adjacent to the air outlet.  
(5) If the air conditioner produces any abnormal sound, consult with your dealer.  
6-5 Disposing of the unit.  
When you need to dispose of the unit, consult your dealer.  
If pipes are removed incorrectly, refrigerant (fluorocarbon gas) may blow out and come into contact with  
your skin, causing injury.  
Releasing refrigerant into the atmosphere also damages the environments.  
6-6 Maintenance and inspection.  
(1) If the air conditioner is used throughout several seasons, the insides can get dirty, reducing the  
performance.  
(2) Depending upon the conditions of usage, foul odours can be generated and drainage can deteriorate  
due to dust and dirt, etc.  
- 106 -  
7.Trouble shooting  
Before you ask for repair service, check the following points:  
Cause  
Troubleshooting  
State of Machine  
Press the [ON/OFF] button after power restoration.  
Power failure.  
The power supply is turned OFF.  
Turn the power supply ON.  
Replace fuse.  
It does not run.  
The fuse in the power supply is gone.  
The earth leakage breaker is gone.  
Improper temperature adjustment.  
Put in the earth leakage breaker.  
Air flows out but it does not cool or heat  
enough.  
After checking the set temperature.  
Clean up the filter.  
The filter is filled with dust and dirt.  
There are some obstacles at the air inlet and  
outlet of the units.  
Remove.  
Windows and doors are open.  
Insufficient refrigerant charge.  
Close.  
Contact with your installing contractor.  
Wait for a while.  
Cool or warm air does not come out.  
The restart-preventing circuit is in operation for  
3 minutes.  
(To protect the compressor, a 3-minute restart-  
preventing circuit is built into the unit.  
Therefore, there are occasions sometimes when  
the compressor does not start running immediately.  
There are cases when it does not run for as long  
as 3 minutes.)  
Wait for a while.  
(Heating operation starts after ending defrosting  
operation.)  
Indoor unit operation was started anew during  
the heating and defrosting operation.  
(5 10 HP only)  
The set temperature of thermostat is  
excessively high for cooling.  
excessively low for heating. (PEH only)  
For temperature control,  
decrease the set temperature at cooling.  
increase the set temperature at heating. (PEH only)  
Fan runs but compressor do not run.  
The room temperature is  
excessively low for cooling.  
Can not be operated as it is out of temperature  
control range.  
excessively high for heating. (PEH only)  
Fan runs but stops immediately.  
Air outlet and inlet are blocked.  
Remove blocking matter.  
Fogged white steam is discharged from  
the indoor unit.  
When the indoor temperature and humidity are It is not a breakdown.  
high, such a phenomenon is occasionally had  
at the beginning of system operation.  
Please use as it is.  
Water or steam is discharged from the  
outdoor unit.  
At cooling, water which places to cooling piping It is not a breakdown.  
and piping connection part drops.  
When heating, water which places to the heat  
exchanger drops. (PEH only)  
Please use as it is.  
On heating, the air flow stops although a set  
temperature is not reached. (PEH only)  
Frost adheres to the outdoor coil when the  
temperature on the outside is low and humidity Please use as it is.  
is high. This frost is melted.  
It is not a breakdown.  
- 107 -  
HOW TO OPERATE (OPTION PAC-204RC)  
Display section  
G
B
C
H
A
A
B
[Current/start/ending time] Display  
Operation mode  
Displays the status of operation.  
D F  
C
[Checking] Display  
This displays indication when some abnormality  
occurs in the unit.  
E
D
E
F
[Set temperature] Display  
Displays the set temperature.  
[Operation] Lamp  
Lights up during operation, goes off during stop.  
[Room temperature] Display  
Displays the temperature of the air sucked in  
during operation.  
G [Fan speed] Display  
This displays indication High-speed or Low-speed.  
H [Key lock] Display  
This display indication during key lock function active.  
For purposes of explanation, all the displays on this page are shown  
in their lit condition. This configuration does not occur in the actual  
unit.  
Before starting operation  
* Make sure that the power supply is turned ON before use. (Keep the power supply turned ON at all times  
when the air conditioner is in use. Use of the unit without power can result in compressor failure.)  
Warning:  
Check and confirm the power circuit before use. For the contents, refer to the previously described chapter  
[Crucial points to be observedfor safety].  
1-1 ON / OFF  
A
Start an operation  
Press the [ON/OFF] button  
Operation lamp lights up and operation starts.  
1
Stop an operation  
Press the [ON/OFF] button again  
Operation lamp goes off and operation stops.  
* Once the buttons have been set, pressing of the [ON/OFF] button  
only can repeat the same operation thereafter.  
* During operation, the operation lamp above the [ON/OFF] button  
lights up.  
A
Operation lamp  
Caution:  
Even if the operation button is pressed immediately after the operation is once stopped, operation is not  
restarted for about 3 minutes. This function protects the machine. It automatically starts operation after the  
lapse of approximately 3 minutes.  
- 108 -  
1-2 Selecting operation  
When selecting operation  
A
Press the [MODE] button  
Consecutive press of the [MODE] button switches the operation  
over to "FAN", "COOL", "HEAT" and  
of operation,check the display.  
"AUTO". For the contents  
For fan  
Press the [MODE] button and bring up the "FAN"  
display.  
1
* The fan operation functions to circulate the air in the room.  
* The temperature of the room cannot be set by fan operation.  
Caution:  
Never expose your body directly to cool air for a long time.  
Excessive exposure to cool air is bad for your health, and  
should therefore be avoided.  
A
Operation mode display  
For cooling  
Press the [MODE] button and bring up the "COOL" display.  
For heating  
Press the [MODE] button and bring up the "HEAT" display.  
Caution:  
* When the air conditioner is used together with burners, thoroughly  
ventilate the area. Insufficient ventilation can result in accidents due to oxygen deficiency.  
* Never place a burner at a place where it is exposed to the airflow from the air conditioner.  
Doing so can result in imperfect combustion of the burner.  
For Auto change over  
Press the [MODE]button and bring up the "AUTO" display  
This function is special order. Please consult your local Mitsubishi Electric Sales office for application  
advice on this function.  
Because this function need low ambient cooling parts as option.  
Indoor temperature can be set within the following range.  
Indoor temperature setting range:17~30ËšC  
1-3 Room temperature adjustment  
To change room temperature  
A
1
Press the room temperature button and set the room tempe-  
rature of your choice.  
Press  
or  
once changes the setting by 1 .  
If the pressing is continued, the setting continues to change by 1 .  
1
* Indoor temperature can be set within the following range.  
Cooling  
Heating  
19 30  
17 28  
* It is impossible to set the room temperature by the air-blow  
operation  
1 Press  
and  
together, the unit of temperature  
A
Set temperature display and room  
temperature display  
change " " (degree-centigrade) and " " (degree-Fahren-  
heit)  
F
- 109 -  
1-4 Time setting  
Clock key  
A
B
1 Press the key one time will activate set clock mode.  
Press the key again will disable set clock mode.  
2 4  
Under set clock mode, the real time clock and present day  
setting can be changed by pressing Day key, Hour key or  
Minute key.  
2
3
7-Days timer key  
1 There are two keys for timer. One is ON Timer, another is  
Off Timer.  
5
Press the key one time will activate set timer mode.  
Press the key again will disable set timer mode.  
1
4
2 4  
Under set timer mode, the 7-days timer setting can be  
changed by pressing Day key, Hour key or Minute key.  
A
B
Current time display  
Timer Hold/Resume display  
Day key  
2
During set clock mode or set timer mode, press the key will change the day setting.  
Hour key  
3
During set clock mode or set timer mode, press the key will change the hour setting.  
Minute key  
4
During set clock mode or set timer mode, press the key will change the minute setting.  
Timer Hold/Resume key  
If 7-days timer is set, then the word "Timer Active" is displayed.  
5
To clear all the timers setting, Press and hold the hold key until the word "Timer Active" is not displayed.  
To resume the timer setting after timers have been held, press and hold the key until the word " Timer  
Active" is displayed.  
1-5 Other function  
Key lock  
1
Press the "MINUTE" key three times consecutively,  
"KEY LOCK" symbol will appear on LCD screen.  
At this time, only "ON-OFF" key is valid.  
This function purpose is protect from mischief of child etc.  
To cancel the key lock function, Please press "MINUTE" key  
three times consecutively again.  
Test run  
2
Press the "TEST" key two times consecutively.  
The unit will run and finished automatically after two hours.  
2
1
- 110 -  
1-6.Trouble shooting  
Before you ask for repair service, check the following points:  
Cause  
Troubleshooting  
State of Machine  
It does not run  
Remote Controller  
"ON-OFF "display is  
not lit up  
No display appears  
even when the [ON/  
OFF] button is  
pressed.  
Press the [ON/OFF] button after power restoration.  
Power failure  
The power supply is turned OFF.  
Turn the power supply ON.  
Replace fuse.  
The fuse in the power supply is gone.  
The earth leakage breaker is gone.  
Put in the earth leakage breaker.  
After checking the set temperature and inlet  
temperature on the liquid crystal display, refer to  
[To change room temperature] on page 107, and  
operate the adjustment button.  
Air flows out but it  
does not cool  
enough or heat  
enough.  
The liquid crystal  
display shows that  
it is in the state of  
operation.  
Improper temperature adjustment.  
Clean up the filter.  
The filter is filled with dust and dirt.  
There are some obstacles at the air inlet and  
outlet of the indoor and outdoor units.  
Remove.  
Close.  
Windows and doors are open.  
Wait for a while.  
(To protect the compressor, a 3-minute restart-  
preventing circuit is built into the indoor unit.  
Therefore, there are occasions sometimes when  
the compressor does not start running immedi-  
ately. There are cases when it does not run for as  
long as 3 minutes.)  
The liquid crystal  
display shows that  
it is in operation.  
The restart-preventing circuit is in operation for  
3 minutes.  
Cool air or warm air  
does not come out.  
Wait for a while.  
(Heating operation starts after ending defrosting  
operation.)  
Indoor unit operation was started anew during  
the heating and defrosting operation.  
(5 10 HP only)  
Can not change to  
Heat mode when  
DIP switch1 is not correct  
Change the DIP switch off to on.  
(Refer to Instruction manual for Installation.)  
Can not change  
to Heat mode  
press the "MODE" key.  
Error Display  
Indicate  
E01  
Cause  
Troubleshooting  
Automatically reset to restoration error.  
Room temperature sensor open.  
E02  
Room temperature sensor short.  
Automatically reset to restoration error.  
Push the On-Off switch.(OFF to ON)  
E03  
Error input from Indoor unit or  
Outdoor unit.  
- 111 -  
SPECIFICATION GUIDELINES  
Air to air reverse cycle split air conditioning system.  
The systems shall operate at out door ambient temperatures as high as  
.
The system shall have a total cooling capacity of  
at DB and  
kW or greater with an indoor air quantity of  
L/s  
WB entering indoor coil temperature with a  
temperature entering the outdoor coil.  
The system shall have a sensible heat capacity of  
kW or greater with a room DB temperature of  
.
The total heating capacity (without electric element heaters) shall be kW or greater at  
WB outdoor air conditions, with  
DB,  
of indoor air entering indoor coil at  
DB.  
The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be  
equipped with a crankcase heater.  
Coils shall be of non-ferrous construction with mechanically bonded aluminum plate fins Outdoor coils  
shall be made, of 9.52mm OD, 0.35mm thick formless copper tubes mechanically bonded to 0.12mm  
thick aluminum plate fins.  
Face area of the coil shall not be less than  
3.3 MPa pressure. The indoor coil face area shall be not less than  
m2 The coil shall be factory pressure and leak tested at  
m2  
.
Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to  
ensure smooth airflow and shall discharge vertically and be direct driven by a weatherproof three  
phase squirrel cage  
kW induction motor.  
The system shall be factory wired and all electrical wiring must comply with the Local wiring code (Controls  
and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal  
and current sensitive overload devices.  
An automatic defrost control shall be included to accomplish defrosting (only if required) every  
for a period of minutes.  
minutes  
High pressure switch (pre-set) shall be factory installed.  
The enclosure is weatherproof casing constructed of phosphatized, zinc coated steel with powder coating.  
(OUTDOOR UNIT)  
The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall  
be located in the pillars. (OUTDOOR UNIT)  
The unit shall have a drain connection provided (25mm BSP:male thread).  
The enclosure shall have openings provided for power connections.  
Access for both service and installation shall be provided to compressors, control wiring, and fans.  
Side panels and top panels shall be removable for easy service access.  
)
mm (INDOOR UNIT  
The unit maximum dimensions shall be : height:  
: height:  
mm, width:  
mm, width:  
mm and depth:  
mm and depth:  
mm (OUTDOOR UNIT)  
Due to continuous product development, these guidelines are subject to change.  
- 112 -  
MEMO  
- 113 -  
DATA BOOK PE,PEH  
MITSUBISHI ELECTRIC CORPORATION  
HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100-0005,TELEX J24532 CABLE MELCO TOKYO  
New publication effective Dec. 1999.  
Specifications subject to change without notice.  
Issuued in Dec. 1999 MEE99K014  

Mitsubishi Electronics P500ymf C User Manual
Philips Sc486 Dectsbc User Manual
Precisionaire 425t Panel User Manual
Radio Shack 23 039 User Manual
Ricoh Aficio Mp C3000 User Manual
Sanyo Stb0810c1 User Manual
Sanyo Uf553450l User Manual
Soleus Air Soleusair Sg Ttw 12hc 26 User Manual
Tanaka Pf 2600 User Manual
Tru Test 2 J User Manual