AIR-COOLED SPLIT-TYPE DUCTED AIR CONDITIONERS
DATA BOOK
Series : PE(H)
Model
Service ref.
PE-7MYC
PE-8MYC
PE-10MYC
PE-15MYC
PE-20MYC
PE-7MYC-EU
PE-8MYC-EU
PE-10MYC-EU
PE-15MYC-EU
PE-20MYC-EU
Cooling only
Heat pump
PEH-5MYA
PEH-7MYA
PEH-8MYA
PEH-10MYA
PEH-15MYA
PEH-20MYA
PEH-5MYA-EU
PEH-7MYA-EU
PEH-8MYA-EU
PEH-10MYA-EU
PEH-15MYA-EU
PEH-20MYA-EU
SAFETY FOR USE
Before conducting installation work, please read this ''SAFETY FOR USE'' carefully
for correct installation.
Since the caution items shown here contain important description relative to safety, please
observe them without fail.
Erroneous handling gives a high possibility to induce serious results such as
death or heavy injury.
Warning
Erroneous handling may induce serious injury depending on the situation.
Caution
After reading, please keep it with you together the Instruction Manual, and read it again at the
movement of the unit.
Warning
Never repair the unit, remodel or transfer it to
another site by yourself.
Ask your dealer or specialized subcontractor
for installation.
Conducting installation work by yourself improperly
may cause a fire, electric shock or water leakage.
If they are performed improperly, water leakage, electric
shock or fire may result. If you need to have the unit
repaired or moved, consult your dealer.
For installation, conduct the work correctly by
following the Installation Manual.
Improper installation may cause a fire, electrical shock
or water leakage.
Use only the specified refrigerant (R-22) to charge
the refrigerant circuit.
Do not mix it with any other refrigerant and do not
allow air to remain in the circuit.
Air enclosed in the circuit can cause high pressure resulting
in a rupture and other hazards.
Install the unit on a spot sufficiently durable against
the unit weight.
Insufficient durability can cause an injury by the falling
down of unit.
Ventilate the room if refrigerant leaks during
Installation.
The refrigerant heated generates poisonous gas by
decomposition which can cause poisoning.
All electric work must be performed by licensed
technician, according to local regulations and the
instructions given in this manual.
The units should be powered by dedicated power
lines.
After completing installation work, make sure that
refrigerant gas has not leaked.
Power lines with insufficient capacity or improper
electrical work may result in electric shock or fire.
If refrigerant gas has leaked and exposed to fan heater,
stove, oven and so on, it may generate noxious gases.
Please do the gas leakage inspection before starting.
Use only the specified cables for wiring. The
connections must be made secured without
tension the terminals.
Improper connection or fastening can cause a fire or
electrical shock.
Take a proper measure to suppress the critical
concentration of refrigerant if leaked when
installing the unit in a small room.
The limit density is made not to be exceeded even if the
refrigerant leaks by any chance.
You are necessary to ventilation measures to prevent
the accident. If the refrigerant leaks, hypoxia accident
may caused.
The unit should be installed according to the
instructions in order to minimize the risk of damage
from earthquakes, typhoons or strong winds.
Improper installation work can cause an injury by the
falling down of the unit.
The outdoor unit must be installed on stable, level
surface, in a place where there is no accumulation
of snow , leaves or rubbish.
For the countermeasure to be taken, consult your
dealer.
The outdoor unit should be installed in a location
where air and noise emitted by the unit will not
disturb the neighbors. The indoor unit should be
securely installed.
The terminal block cover of unit must be firmly
attached to prevent entry of dust and moisture.
Improper mounting of the cover cause electric shock or
fire.
If the unit is loosely mounted, it may fall, and cause injury.
Use only optional parts authorised by Mitsubishi
Electric.
If the accessories are installed improperly, water
leakage, electric shock or fire may result.
Ask your dealer or an authorised company to install
them.
The heating of refrigerant is noted.
When the refrigerant touches the fire etc., it was decom-
posed and a poisonous gas is generated.
Do not use the welding machine etc., in the room close up
of the installation of the air conditioner.
- 2 -
Caution
Arrange the configuration of wiring not to bring up
Never install on the place where a combustible
gas might leak.
The gas may ignite or explode when the gas leaks and
collects in surround of the unit.
the panel and terminal cover, and fasten the panel
and terminal cover securely.
The poor mounting of the panel or terminal cover may
cause the heat generation of the terminal connection,
a fire or electrical shock.
When the unit is installed at telecommunication
centers or hospitals, take a proper provision
against noise.
The erroneous operation of air conditioner may be
induced by inverter equipment, independent power
device, medical equipment or communication
equipment.
Do not wash the unit with water.
If washed with water, electric shock may be caused.
Do not handle the switch with wet hands.
Otherwise electric shock can be resulted.
Be very careful about unit transportation.
For special use as for foods, animals/plants,
precision equipment or art objects, the applicability
should be confirmed beforehand.
As the use for the applications other than that
designed originally may result in the deterioration of the
quality. Consult your dealer in this regard.
The unit should not be carried by only one person if it is
more than 20kg. It occasionally causes the damage of
the unit and health to be impaired.
Some unit use PP bands for packing. Do not use any PP
band for delivery purpose. It may cause the injury.
Do not touch the heat exchanger fins with your bear hands.
Doing so may cut your hands.
When carrying in outdoor unit, be sure to support it at four
points. Carrying in and lifting with 3-point support may
make outdoor unit unstable, resulting in a fall of it.
Be sure to safety dispose the packing materials.
Packing materials, such as catches and other metal or
wooden parts, may cause stabs or other injuries.
Do not use the unit under a special atmosphere.
Installing the unit at the following places may cause a
trouble, a place where is much machine oil, salt ,
humidity or dust, spa district, a place full of sulfur gas,
volatile gas, or corrosive gas, a place near high
frequency processing machine.
Thermal insulation of the drain pipes is necessary
prevent dew condensation.
If the drain pipes are not properly insulated,
condensation will result and drip on ceiling, floor or other
possessions.
Do not leave the mounting base being damaged.
The damaged base may cause the falling down of the
unit which may give injury.
Turn on the main power switch more than 6 hours
before starting operation.
Do not turn the main power switch OFF during seasons
of heavy use, doing so can result in failure.
The unit should be securely installed level surface.
When the unit inclines, it causes the water leak and the
breakdown.
Please confirm the horizontal with the spirit level.
Do not touch the compressor or refrigerant piping
without wearing glove on your hands.
Touching directly such part can cause a burn or
frostbite as it becomes high or low temperature
according to the refrigerant state.
Install drain piping (hose) according to this
Installation Manual to ensure proper drainage.
Improper drain piping (hose) may cause water leakage
and damage to furniture or other possessions.
The unit must be properly earth connected.
Do not connect the earth wire to gas pipe, city water
pipe, lightning rod or telephone earth wire.
Do not touch the metal edges inside the unit
without wearing glove on your hands.
Touching directly it may injure your hands.
Improper earth connection may cause electrical shock.
Do not remove the panel or the fan guard from the
unit when it is running.
You could be injured if you touch rotating, hot or high-
voltage parts.
When installing at a watery place, provide an
electric leak breaker.
Failure to mount the electric leak breaker may cause
electrical shock.
Do not operate the air conditioner without the air
filter set place.
Use breaker or fuse with proper capacity.
Make sure that each appliance has a main power
Dust may accumulate, and cause a failure.
switch.
Using a wire or copper wire instead of proper capacity
can cause fire or trouble.
At emergency (if you smell something burning), stop
operation and turn the power source switch off.
Continuing the operation without eliminating the
emergency state may cause a machine trouble, fire, or
electrical shock.
Other appliances connected to the same line could cause
an overload.
For the power lines, use standard cables of
sufficient current capacity.
Otherwise, current leakage, overheating or fire may
occur.
After stopping operation, be sure to wait for five
minutes before turning off the main power switch.
Otherwise, water leakage or unit failure may occur.
When installing the power lines, do not apply
tension to the cables.
The tighten or loosen the connections may cause generate
heat and cause fire.
Remote controller is not installed for the place
where direct sunshine strikes.
Remote controller is not pushed with the thing
sharpening ahead.
It occasionally causes the electric shock and the break-
down.
A thing embarrassed which gets wet under the unit
is not put.
When the room is high humidity or when the drain pipe
is clogged, water may drip from the indoor unit.
- 3 -
A COMPLETE LINE UP
PEH-5
14.4
PE(H)-7
17.9
PE(H)-8
22.0
PE(H)-10 PE(H)-15 PE(H)-20
28.8
44.0
150,200
37,900
44.0
57.6
196,600
49,600
57.6
kW
Btu/h
kcal/h
kW
49,150
12,400
14.4
61,000
15,400
18.8
75,100
18,900
22.0
98,300
24,800
28.8
Cooling capacity
Heating capacity
(PEH only)
49,150
12,400
64,100
16,200
75,100
18,900
98,300
24,800
150,200
37,900
196,600
49,600
Btu/h
kcal/h
Note: Cooling & heating capacities are based following conditions.
Cooling: Indoor:27 DB, 19 WB; Outdoor: 35 DB
Heating: Indoor:21 DB; Outdoor: 7 DB, 6 WB (PEH only)
Cooling and Heating capacities are based 5m pipe length
Indoor unit
Example PEH-7
Outdoor unit
Example PUH-7
- 4 -
FEATURES
Labour saving installation.
High sensible cooling capacity.
The sensible cooling capacity has been significantly
improved through balanced optimised heat
exchanger design.
The unit operation can commence immediately after
connecting to the power supply, refrigerant piping,
drain piping, ducting and control system.
Comfort heating. (PEH only)
The PEH series are designed to provide effective
heating even when the outside temperature is down
Wide electrical control capability.
All series is flexible mechanical control
configuration.
In addition Global Remote Controller is prepared as
special order.
The Global Remote Controller gives the programmable
weekly timer, compressor anti-short cycle timer(3min.),
cool/heat/fan/auto changeover etc.(Heat and auto
changeover are only PEH.)
The factory standard is for provision of 24 volt terminal
block to enable a field wired control of contractors
choice to be connected.
to -10
.
Highly efficient operation.
The EER(Energy Efficiency Ratio) on these models
is greatly improved by revised design specifications
and by being manufactured stringently to Mitsubishi
Electric high quality standards.
Flexibility of Supply Air Delivery
PE, PEH-15,20 feature belt driven Supply Air fans
enabling accurate matching of actual airflow rates
to the specified quantities. Accurate commissioning
is assisted by the capability to change pulleys and
belts if necessary to achieve the desired air balance.
Please consult your local Mitsubishi Electric Sales
office for application advice on these control.
Low ambient cooling. (Special order)
In applications with relatively high internal loads,
there may be a requirement for all series to
operate on cooling at low ambient conditions.
Special order parts is available to maintain the
refrigeration circuit in balance at outdoor temperatures
as low as -5
.
Please consult your local Mitsubishi Electric Sales
office for application advice on these parts.
Grobal Remote Controller
DESCRIPTIONS
With the development of all series demands
for such features as light weight, compactness,
Mitsubishi Electric air conditioners series PE(H)/PU(H)
are available in a wide range of sizes and models to
enables the designer to select the best model for
each application.
All series units are completely assembled, wired and
strictly tested at the factory.
increased capacity, appropriate static pressure, air
flow control, and having flexibility of inter facing
energy saving electronic controls, Mitsubishi
Electric have met market expectations.
- 5-
MECHANICAL SPECIFICATIONS
General
Condenser Coils
All units are factory assembled, piped, internally wired.
They are also tested and checked under a strict quality
control system in the factory.
Unnecessary power input due to higher discharge
pressure is avoided by high performance designs of
cross-finned coil.
Exterior surfaces of all units of outdoor unit are
phosphatized, zinc-coated steel with powder coating
and ivory white baked enamel finish.
Condenser coils are made of 9.52mm OD, 0.35mm
thick seamless copper tubes mechanically bonded to
0.12mm thick aluminium fins and factory pressure
and leak tested at 3.3MPa.
Refrigeration Controls
Refrigeration controls include condenser fan,
evaporator fan and compressor contactors.
Evaporator Fans
The sirocco fans are made of galvanised steel and
balanced to proved accurate air flow performance at
low noise level.
Compressors
All units have high efficiency type hermetic line starting
compressors.
Condenser Fan
Compressors are equipped with thermal overload
protector, over-current relay and high pressure
protection control.
The direct-drive propeller fan is dynamically balanced,
to ensure smooth airflow.
Crankcase heaters are standard.
A weatherproof three-phase squirrel cage induction
motor is used to drive the condenser fan.
Evaporator Coils
Highly efficient cross-finned coil are applied to provide a
larger cooling capacity with low air speed on the coil.
Coils are made of 9.52mm OD and 0.35mm thick
seamless copper tubing mechanically bonded to 0.12mm
thick aluminium fins and are factory leak tested at a
pressure of 3.3MPa. They are provided with strainers
attached to the capillary tubes to further ensure a clean
system.
TYPICAL INSTALLATION EXAMPLE
PU(H)
PE(H)
PE(H)
PU(H)
- 6-
MODEL-DESIGNATION BREAKDOWN
1
P E-10 M Y C
Service reference
Design Sequence
Electrical Supply
Y = 3 phase 380~415V 50Hz 4 wires
In case of PE(H)-7 Indoor unit
Y = 1 phase 220~240V 50Hz 2 wires
(
)
Compressor Horsepower
5 = 5 HP
7 = 7 HP
8 = 7.5 HP
10= 10 HP
15= 15 HP
20= 20 HP
Series Number
PE = Indoor unit
PEH = Indoor unit
PU = Outdoor unit
PUH = Outdoor unit
- 7 -
SPECIFICATIONS
Cooling only
PE-7~20MYC
PE-15MYC
PE-20MYC
Model name
PE-7MYC
PE-8MYC
PE-10MYC
Service
reference
PE-15MYC-EU
PE-20MYC-EU
PE-7MYC-EU
PE-8MYC-EU
PE-10MYC-EU
1PH 2W220~240V 50Hz
3PH 4W380 ~ 415V 50Hz
3PH 4W380 ~ 415V 50Hz
Power supply
Indoor
3PH 4W 380~415V 50Hz
17.9
Outdoor
Total cooling capacity
22.0
28.8
44.0
150,200
37,900
35.2
57.6
196,600
49,600
46.1
kW
Btu/h
kcal/h
kW
61,100
75,100
18,900
17.6
98,300
24,800
23.0
15,400
14.3
Sensible cooling capacity
48,800
60,100
15,100
78,500
19,800
120,200
30,200
157,300
39,600
Btu/h
kcal/h
%
12,300
Capacity step
Refrigerant
Refrigerant charge
0-100
0-50-100
R-22
8.7
kg
5.7
5.0
2 ✕ 4.8
2 ✕ 9.7
Capillary tube
PE-10MYC
Refrigerant control
PE-15MYC
PE-20MYC
Indoor Unit
PE-7MYC
PE-8MYC
Model name
Service
reference
PE-15MYC-EU
PE-20MYC-EU
PE-7MYC-EU
PE-8MYC-EU
PE-10MYC-EU
Galvanized steel
External finish
Dimension
706
865
Height
Width
Depth
mm
mm
mm
kg
428
1,993
212
1,615
1,690
180
1,415
650
70
67
84
Net weight
Cross fin coil
Indoor coil
Centrifugal (Galvanized) - Direct drive
Centrifugal (Galvanized) - Belt drive
Indoor fan
Indoor fan motor
Three phase induction motor
Single phase induction motor
1 ✕ 3.7
180
1 ✕ 0.7
70
1 ✕ 1.0
90
kW
CMM
1 ✕ 2.2
140
No. ✕ Motor output
1 ✕ 0.21
60
Indoor fan air flow
CFM
L/S
2,119
1,000
2,472
1,167
12.5
125
3,179
1,500
4,945
2,333
6,358
3,000
External static
pressure
mmAq
Pa
20
200
55
56
59
25.4
61
62
Sound pressure level
Drain connection
dB(A)
mm
Outdoor unit
PU-7MYC
PU-8MYC
PU-10MYC
PU-15MYC
PU-20MYC
Model name
Service
reference
PU-7MYC1-EU(S)
PU-8MYC1-EU(S) PU-10MYC1-EU(S) PU-15MYC1-EU(S) PU-20MYC1-EU(S)
Acrylic resin coating
Munsell 5Y 8/1
External finish
Color
980
1,400
700
1,230
998
961
1,996
Dimension
Height
Width
Depth
mm
mm
mm
kg
998
230
360
205
285
Net weight
202
Hermetic line start(reciprocating)
Compressor
2 ✕ 7.5
No. ✕ Motor output
1 ✕ 5.5
1 ✕ 7.5
kW
2 ✕ 5.5
1 ✕ 5.0
Outdoor coil
Cross fin coil
Outdoor fan
Propeller-Direct drive
Outdoor fan motor
No. ✕ Motor output
Outdoor fan air flow
Three phase induction motor
2 ✕ 0.09
190
2 ✕ 0.15
220
1 ✕ 0.24
240
2 ✕ 0.24
480
kW
CMM
CFM
L/S
210
7,415
3,000
65
6,711
3,167
65
7,770
3,667
65
8,477
4,000
67
16,954
8,000
68
Sound pressure level
Protection devices
dB(A)
High pressure switch, freeze & frost protection, Fuse
Over current relay (comp & indoor fan, outdoor fan)
Internal thermostat (comp & indoor fan, outdoor fan)
Note1.Cooling capacity is based on the following conditions.
Indoor;27ËšCDB,19ËšCWB, Outdoor;35ËšCDB
Cooling capacity is based 5m pipe length.
2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.
3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.
4.The measuring point of the Sound pressure level is 1m from the unit surface.
5.Specification subject to change without notice.
- 8 -
PEH-5,7,8MYA
Model name
Service
reference
Heat pump
PEH-5MYA
PEH-7MYA
PEH-7MYA-EU
PEH-8MYA
PEH-5MYA-EU
PEH-8MYA-EU
1PH 2W220~240V 50Hz
3PH 4W380~415V 50Hz
3PH 4W380~415V 50Hz
Power supply
Indoor
3PH 4W380~415V 50Hz 3PH 4W380~415V 50Hz
3PH 4W380~415V 50Hz
Outdoor
22.0
75,100
18,900
17.6
14.4
49,150
12,400
11.5
17.9
61,100
15,400
14.3
Total cooling capacity
kW
Btu/h
kcal/h
kW
Sensible cooling capacity
Sensible heating capacity
39,400
10,000
14.4
48,800
12,300
18.8
60,100
15,100
22.0
Btu/h
kcal/h
kW
Btu/h
kcal/h
49,150
12,400
64,100
16,200
75,100
18,900
Capacity step
0-100
R-22
%
Refrigerant
Refrigerant charge
Refrigerant control
kg
5.0
5.7
6.6
Capillary tube
Indoor Unit
PEH-5MYA
PEH-7MYA
PEH-8MYA
Model name
Service
reference
PEH-5MYA-EU
PEH-7MYA-EU
PEH-8MYA-EU
External finish
Dimension
Galvanized steel
Height
Width
Depth
mm
mm
mm
kg
428
650
1,415
70
1,095
60
67
Net weight
Cross fin coil
Indoor coil
Centrifugal (Galvanized) - Direct drive
Indoor fan
Indoor fan motor
Three phase induction motor
Three phase induction motor Single phase induction motor
kW
No. ✕ Motor output
1 ✕ 0.45
1 ✕ 0.21
1 ✕ 0.7
CMM
42
60
70
Indoor fan air flow
CFM
L/S
1,483
700
2,119
1,000
2,472
1,167
External static
pressure
mmAq
Pa
12.5
125
55
56
Sound pressure level
Drain connection
Outdoor unit
dB(A)
mm
25.4
PUH-7MYC
PUH-5MYE
PUH-8MYC
PUH-8MYC1-EU(S)
PUH-8MYE
Model name
Service
reference
PUH-5MYE-EU
PUH-7MYC1-EU(S)
PUH-8MYE-EU
Acrylic resin coating
External finish
Color
Munsell 5Y 8/1
1,175
1,000
550
1,175
1,250
550
980
1,400
700
Dimension
Height
Width
Depth
mm
mm
mm
kg
188
214
Net weight
211
150
Hermetic line start(reciprocating)
Compressor
No. ✕ Motor output
kW
1 ✕ 3.73
1 ✕ 5.5
Outdoor coil
Cross fin coil
Outdoor fan
Propeller-Direct drive
Outdoor fan motor
No. ✕ Motor output
Outdoor fan air flow
Three phase induction motor
1 ✕ 0.15
95
2 ✕ 0.09
167
1 ✕ 0.35
200
kW
CMM
CFM
L/S
3,355
1,583
57
5,898
2,783
65
7,063
3,333
65
Sound pressure level
Protection devices
dB(A)
High pressure switch, freeze & frost protection, Fuse
Over current relay (comp & indoor fan, outdoor fan)
Internal thermostat (comp & indoor fan, outdoor fan)
Note 1. Cooling and heating capacities are based on the following conditions.
Cooling indoor; 27ËšCDB, 19ËšCWB, outdoor :35ËšCDB
Heating indoor; 21ËšCDB,
outdoor :7.0ËšCDB, 6.0ËšCWB
Cooling and heating capacities are based 5m pipe length.
2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.
3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.
4.The measuring point of the Sound pressure level is 1m from the unit surface.
5.Specification subject to change without notice.
- 9 -
PEH-10,15,20MYA
Model name
Heat pump
PEH-10MYA
PEH-15MYA
PEH-20MYA
Service
reference
PEH-10MYA-EU
PEH-15MYA-EU
PEH-20MYA-EU
Power supply
Indoor
3PH 4W380 ~ 415V 50Hz
3PH 4W380 ~ 415V 50Hz
44.0
Outdoor
28.8
98,300
24,800
23.0
57.6
196,600
49,600
46.0
Total cooling capacity
kW
Btu/h
kcal/h
kW
150,200
37,900
35.2
Sensible cooling capacity
Sensible heating capacity
78,500
19,800
28.8
Btu/h
kcal/h
kW
120,200
30,200
44.0
157,000
39,600
57.6
98,300
24,800
0-100
Btu/h
kcal/h
150,200
37,800
196,600
49,500
Capacity step
0-50-100
%
R-22
Refrigerant
Refrigerant charge
Refrigerant control
kg
9.9
2 ✕ 6.6
2 ✕ 9.7
Capillary tube
Indoor Unit
Model name
PEH-10MYA
PEH-15MYA
PEH-20MYA
Service
reference
PEH-10MYA-EU
PEH-15MYA-EU
Galvanized steel
PEH-20MYA-EU
External finish
Dimension
Height
Width
Depth
mm
mm
mm
kg
428
706
865
1,615
1,690
180
1,993
212
650
84
Net weight
Cross fin coil
Indoor coil
Centrifugal (Galvanized) - Direct drive
Centrifugal (Galvanized) - Belt drive
Indoor fan
Indoor fan motor
Three phase induction motor
1 ✕ 1.0
90
1 ✕ 2.2
140
1 ✕ 3.7
180
kW
CMM
No. ✕ Motor output
Indoor fan air flow
CFM
L/S
4,945
2,333
6,358
3,000
3,179
1,500
20
External static
pressure
mmAq
Pa
12.5
125
59
200
61
62
Sound pressure level
Drain connection
dB(A)
mm
25.4
PUH-10MYC
PUH-10MYE
PUH-15MYC
PUH-20MYC
Outdoor unit
Model name
Service
reference
PUH-10MYC1-EU(S)
PUH-10MYE-EU
PUH-15MYC1-EU(S)
PUH-20MYC1-EU(S)
Acrylic resin coating
Munsell 5Y 8/1
External finish
Color
980
1,400
700
1,175
1,250
550
1,200
Dimension
Height
Width
Depth
mm
mm
mm
kg
1,951
1,080
240
221
431
472
Net weight
Hermetic line start(reciprocating)
Compressor
No. ✕ Motor output
kW
1 ✕ 7.5
2 ✕ 5.5
2 ✕ 7.5
Outdoor coil
Cross fin coil
Outdoor fan
Propeller-Direct drive
Outdoor fan motor
No. ✕ Motor output
Outdoor fan air flow
Three phase induction motor
2 ✕ 0.15
190
0.35
200
2 ✕ 0.35
2 ✕ 185
2 ✕ 6,534
2 ✕ 3,083
69
kW
CMM
CFM
L/S
6,711
3,167
7,063
3,333
Sound pressure level
Protection devices
dB(A)
65
High pressure switch, freeze & frost protection, Fuse
Over current relay (comp & indoor fan, outdoor fan)
Internal thermostat (comp & indoor fan, outdoor fan)
Note 1. Cooling and heating capacities are based on the following conditions.
Cooling indoor; 27ËšCDB, 19ËšCWB, outdoor :35ËšCDB
Heating indoor; 21ËšCDB,
outdoor :7.0ËšCDB, 6.0ËšCWB
Cooling and heating capacities are based 5m pipe length.
2.Refergirant charge volumes are factory charged (at 5m piping length).Refrigerant is enclosed with the outdoor unit.
3.Capacity is gross capacity which do not include a deduction for evaporator fan motor heat.
4.The measuring point of the Sound pressure level is 1m from the unit surface.
5.Specification subject to change without notice.
- 10 -
ELECTRICAL DATA
PE-7~20MYC-EU
Cooling
PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU
VOLT
ITEM
PU-7MYC1-EU
PU-8MYC1-EU
7.8
PU-10MYC1-EU PU-15MYC1-EU PU-20MYC1-EU
TOTAL INPUT
kW
A
7.2
14.6
-
10.1
18.9
74
17.6
29.6
83
22.0
39.1
78
TOTAL RUN CURRENT
POWER FACTOR
14.2
74
%
A
PE-7
240V
START CURRENT
74
83
82
119
140
6.0
10.7
0.8
3.2
0.4
0.7
6.8
12.3
0.6
1.2
0.4
8.6
15.9
1.0
2.0
0.5
1.0
2X7.65
2X12.45
1.7
2X9.2
2X15.95
2.4
4.8
2X0.6
2X1.2
COMPRESSOR INPUT
RUN CURRENT
kW
A
PE-
8
20
INDOOR FAN INPUT
RUN CURRENT
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
415V
3.5
0.6
1.2
kW
A
0.7
TOTAL INPUT
kW
A
7.2
15.9
-
7.8
15.5
74
10.1
20.7
74
17.6
32.3
83
22.0
42.7
78
TOTAL RUN CURRENT
POWER FACTOR
START CURRENT
%
A
PE-7
220V
81
91
90
131
152
6.0
11.6
0.8
3.5
0.4
0.8
6.8
13.4
0.6
1.3
0.4
0.8
8.6
17.6
1.0
2.1
0.5
1.0
2X7.65
2X13.65
1.7
2X9.2
2X17.55
2.4
5.2
2X0.6
2X1.2
COMPRESSOR INPUT
RUN CURRENT
kW
A
PE-
8
20
INDOOR FAN INPUT
RUN CURRENT
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
380V
3.8
0.6
1.2
kW
A
- 11 -
PEH-5,7,8MYA-EU
Cooling
PEH-5MYA-EU
PEH-7MYA-EU
PEH-8MYA-EU
VOLT
ITEM
PUH-5MYE-EU
5.5
PUH-7MYC1-EU
PUH-8MYC1-EU
PUH-8MYE-EU
7.9
TOTAL INPUT
kW
A
7.2
14.6
-
7.8
14.2
76
TOTAL RUN CURRENT
POWER FACTOR
9.5
80
69
14.7
75
83
%
A
PEH-7
240V
START CURRENT
74
83
4.7
8.1
0.54
0.9
0.25
0.5
6.0
10.7
0.8
3.2
0.4
0.7
6.8
12.3
0.6
1.2
0.4
0.7
6.77
12.3
0.6
1.2
0.53
1.2
COMPRESSOR INPUT
RUN CURRENT
INDOOR FAN INPUT
RUN CURRENT
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
PEH-
8
20
kW
A
415V
kW
A
TOTAL INPUT
kW
A
5.5
10.4
80
7.2
15.9
-
7.8
15.5
76
7.9
16.0
75
TOTAL RUN CURRENT
POWER FACTOR
START CURRENT
%
A
PEH-7
220V
69
81
91
91
4.7
8.85
0.54
1.0
0.25
0.55
6.0
11.6
0.8
3.5
0.4
0.8
6.8
13.4
0.6
1.3
0.4
0.8
6.77
13.4
0.6
1.3
0.53
1.3
COMPRESSOR INPUT
RUN CURRENT
INDOOR FAN INPUT
RUN CURRENT
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
PEH-
8
20
kW
A
380V
kW
A
Heating
PEH-5MYA-EU
PEH-7MYA-EU
PEH-8MYA-EU
VOLT
ITEM
PUH-5MYE-EU
4.5
PUH-7MYC1-EU
PUH-8MYC1-EU
PUH-8MYE-EU
6.6
TOTAL INPUT
kW
A
6.3
13.6
-
6.5
12.4
73
TOTAL RUN CURRENT
POWER FACTOR
8.5
73
69
12.9
71
83
%
A
PEH-7
240V
START CURRENT
74
83
3.7
5.1
9.7
0.8
3.2
0.4
0.7
5.5
10.5
0.6
1.2
0.4
0.7
5.47
10.5
0.6
1.2
0.53
1.2
COMPRESSOR INPUT
RUN CURRENT
INDOOR FAN INPUT
RUN CURRENT
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
PEH-
7.1
0.54
0.9
0.25
0.5
8
20
kW
A
415V
kW
A
TOTAL INPUT
kW
A
6.3
14.9
-
6.5
13.6
73
6.6
14.1
71
4.5
9.2
74
TOTAL RUN CURRENT
POWER FACTOR
START CURRENT
%
A
PEH-7
220V
81
91
91
69
5.1
10.6
0.8
3.5
0.4
0.8
5.5
11.5
0.6
1.3
0.4
0.8
5.47
11.5
0.6
1.3
0.53
1.3
COMPRESSOR INPUT
RUN CURRENT
INDOOR FAN INPUT
RUN CURRENT
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
3.7
7.75
0.54
1.0
0.25
0.55
PEH-
8
20
kW
A
380V
kW
A
- 12 -
PEH-10,15,20MYA-EU
Cooling
PEH-10MYA-EU
PEH-15MYA-EU
PUH-15MYC1-EU
16.9
PEH-20MYA-EU
PUH-20MYC1-EU
21.8
VOLT
ITEM
PUH-10MYC1-EU
PUH-10MYE-EU
10.2
19.1
74
TOTAL INPUT
kW
A
10.1
18.9
74
TOTAL RUN CURRENT
POWER FACTOR
30.9
76
119
39.3
77
140
%
A
PEH-7
240V
START CURRENT
82
82
8.57
15.9
1.0
8.67
15.9
1.0
2X6.77
2X12.2
2.3
2X9.12
2X16.1
2.5
COMPRESSOR INPUT
RUN CURRENT
INDOOR FAN INPUT
RUN CURRENT
kW
A
PEH-
8
20
kW
A
415V
2.0
2.0
4.1
4.7
0.53
1.0
0.53
1.2
2X0.53
2X1.2
2X0.53
2X1.2
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
TOTAL INPUT
kW
A
10.1
20.7
74
10.2
21.0
74
16.9
33.7
76
21.8
42.9
77
TOTAL RUN CURRENT
POWER FACTOR
START CURRENT
%
A
PEH-7
220V
90
90
131
152
2X9.12
2X17.6
2.5
8.57
17.6
1.0
8.67
17.6
1.0
2X6.77
2X13.3
2.3
COMPRESSOR INPUT
RUN CURRENT
INDOOR FAN INPUT
RUN CURRENT
kW
A
PEH-
8
20
kW
A
380V
2.1
2.1
4.5
5.1
0.53
1.1
0.53
1.3
2X0.53
2X1.3
2X0.53
2X1.3
OUTDOOR FAN INPUT
RUN CURRENT
kW
A
Heating
PEH-10MYA-EU
PEH-15MYA-EU
PUH-15MYC1-EU
14.5
PEH-20MYA-EU
PUH-20MYC1-EU
17.2
VOLT
ITEM
PUH-10MYC1-EU
PUH-10MYE-EU
8.6
TOTAL INPUT
kW
A
8.3
16.0
72
TOTAL RUN CURRENT
POWER FACTOR
16.2
72
82
26.9
75
115
33.2
72
136
%
A
PEH-7
240V
START CURRENT
82
6.77
13.0
1.0
7.07
13.0
1.0
COMPRESSOR INPUT
RUN CURRENT
kW
A
2X5.57
2X10.2
2.3
2X6.82
2X13.05
2.5
PEH-
8
20
kW
A
INDOOR FAN INPUT
RUN CURRENT
415V
2.0
2.0
4.1
4.7
0.53
1.0
0.53
1.2
2X0.53
2X1.2
2X0.53
2X1.2
kW
A
OUTDOOR FAN INPUT
RUN CURRENT
TOTAL INPUT
kW
A
8.3
17.5
72
8.6
17.8
72
14.5
29.4
75
17.2
36.3
72
TOTAL RUN CURRENT
POWER FACTOR
START CURRENT
%
A
PEH-7
220V
90
90
126
148
6.77
14.4
1.0
COMPRESSOR INPUT
RUN CURRENT
kW
A
7.07
14.4
1.0
2X5.57
2X11.15
2.3
2X6.82
2X14.25
2.5
PEH-
8
20
kW
A
INDOOR FAN INPUT
RUN CURRENT
380V
2.1
2.1
4.5
5.1
0.53
1.1
kW
A
0.53
1.3
2X0.53
2X1.3
2X0.53
2X1.3
OUTDOOR FAN INPUT
RUN CURRENT
- 13 -
SELECTION PROCEDURE
1. Model Selection (With actual examples)
First step, to select the approximate model:
Based on the cooling load and the cooling capacity listed in the capacity table, select the applicable model.
Second step, to select the model:
To select the model, the following conditions must be known:
(1) Total cooling load or sensible cooling load
(2) Indoor conditioned temperature (WB*1, DB)
(3) Designed outdoor temperature (DB)*2
(4) Designed air flow
(5) Designed external static pressure (= Wind pressure loss of air duct)*3
Notes:
*1. The correct WB is required since it has a serious effect on the capacity.
*2. The cooling capacity decreases as the outdoor temperature increases. Therefore, the estimated highest
temperature during an air conditioning time frame is the "designed outdoor temperature". However, it is
recommended that the abnormal outdoor temperature which may occur once or twice a year be excluded from
the calculation to avoid selection of an excessively large capacity model.
*3. The wind pressure loss of an air duct should be calculated correctly. If a value having an excessive allowance
is used, an excessively large model will be selected. Moreover, an excessively high air flow will be induced
during actual operation causing the generation of high operating sounds and carry-over of condensed water.
(Step-1) Confirmation of operation range
Confirm that the conditions given above for the model to be selected are within the
operation range listed on Page 36.
(Step-2) Calculation of actual air flow, external static pressure, and fan motor input
Based on the designed air flow and external static pressure, obtain the actual air flow,
actual external static pressure, and fan motor power input from the fan performance
table for the model selected. For an explanation of how to use the fan performance
table, see the following examples.
Example: PE-8MYC, 50Hz
Example 1. (To operate with values near to the designed air flow and external static pressure.)
Condition : Designed air flow 70CMM
Designed external static pressure 60Pa
Calculation : The designed point is A. Therefore, duct resistance line passing A is
Fan Performance Curve 50Hz
Fan speed
(rpm)
(Pa)
dotted line.
450
Recommended Range
Therefore, actual point is B for ∆ connection
Actual air flow = 77CMM
400
350
300
For connection
1400
1300
operation line
Actual external static pressure = 70Pa
Notes: Duct resustance line is secondary curve.
B
1200
A
250
200
150
100
60Pa
1100
1000
For connection
operation line
900
800
50
0
50
55
60
65
70
75 77 80
Air flow (CMM)
- 14 -
(Step-3) Calculation of net capacity
Based on the indoor conditioned temperature (WB,DB), designed outdoor temperature (DB), and the
actual air flow obtained in Step-2, obtain the gross capacity from the gross capacity tables (pages
16~35). Then, calculate the net capacity from the formula below by using the fan motor input obtained
in Step-2.
Net capacity (kW) = Gross capacity (kW) - Fan motor input (kW)
OUTDOOR DBËšC
Example: PE-8MYC
INDOOR INDOOR
40.0
Condition:
DBËšC
26
WBËšC
19
Q kW SHC kW SHF
21.3 16.3 0.77
T/I kW
8.3
Indoor conditioned temp. : 26ËšCDB, 19ËšCWB
Designed outdoor temp. : 40ËšCDB
Actual air flow : 77CMM
Fan motor input : 0.6kW (See P.11)
Calculation :
Factor for Various Air Flow
CMM
L/S
60
70
80
The sections of the gross capacity table applicable
for the above conditions are shown right.
PE-8MYC-EU
COOLING
AIR VOLUME
1,000
1,167
1,330
CAPACITY
TOTAL INPUT
SHC
0.976
0.991
0.963
1.0
1.0
1.0
1.025
1.009
1.044
At 26ËšCDB, 19ËšCWB of Indoor,
Q = 21.3, SHC = 16.3, T/I = 8.3
Therefore, when air flow is 77(CMM)
Q = 21.3 ✕ (1+(1.025 - 1.0) ✕ 7/10*) 21.7(kW)
SHC = 16.3 ✕ (1+(1.044 - 1.0) ✕ 7/10*) 16.8(kW)
T/I = 8.3 ✕ (1+(1.009-1.0))✕ 7/10*) 8.4(kW)
Note * : 7/10 = (77-70)/(80-70)
Therfore, the net capacity is,
Net total cooling capacity = 21.7 (kw) - 0.6(kW)
= 21.1 (kW)
Net sensible cooling capacity = 16.8 (kW) - 0.6 (kW)
= 16.2 (kW)
2. Efficiency Calculation
• System energy efficienty
• Refrigerant cycle energy efficienty
Net cooling capacity (kW)
Compressor input (kW)
Gross total cooling capacity (kW)
(1) COP =
(2) ERR =
(1) COP =
(2) ERR =
Compressor input (kW)
Net cooling capacity (kW)
Total input (kW)
Gross total cooling capacity (kW)
Total input (kW)
1kW = 3412Btu/h
Notes: 1. COP : Coefficient of performance
2. EER : Energy efficiency ratio
3. Temperature condition of COP, EER (ARI Standard Ratings)
Indoor entering air temp. : 80ËšFDB (=27ËšCDB), 66ËšFWB(=19ËšCWB)
Outdoor entering air temp. : 95ËšFDB (=35ËšCDB)
4. Total input = Compressor input + Indoor fan motor input + Outdoor fan motor input (page 11).
- 15 -
CAPACITY TABLES
- 16 -
- 17 -
- 18 -
- 19 -
- 20 -
- 21 -
- 22 -
- 23 -
- 24 -
- 25 -
- 26 -
- 27 -
- 28 -
- 29 -
- 30 -
- 31 -
- 32 -
- 33 -
- 34 -
- 35 -
OPERATION RANGE
The range of working temperatures is as below.
Make sure which unit you are using and confirm the range of application.
Cooling
Heating (PEH only)
50
15
10
5
46
40
30
20
10
Range for
continuous operation
0
Range for
continuous operation
- 5
-10
0
-5
Range for
-15
continuous operation
Use for low ambient
cooling parts
-10
10
15
20 2425
30
10
15
20
25 27 30
Indoor temp.(ËšCWB)
Indoor temp.(ËšCDB)
Note
Caution:
As an applicable humidity outside standard for both indoors and outdoors, we
recommend use within a range of 35-80% relative humidity.
The use of your air conditioner
outside the range of working
temperature and humidity can
result in serious failure.
However, it is a condition that there is no be dewy in surfaces of electric parts.
- 36 -
FAN PERFORMANCE
PE-7MYC-EU
PEH-7MYA-EU
PEH-5MYA-EU
Fan Performance Curve
50Hz
Fan Performance Curve
50Hz
Fan speed
(rpm)
Fan speed
(rpm)
(Pa)
450
(Pa)
450
Recommended Range
Recommended Range
400
350
300
400
350
300
1400
1300
For Hi speed
operation line
1200
For connection
operation line
250
200
150
100
250
200
150
100
1300
1200
For Low speed
operation line
1100
1000
900
For connection
operation line
1100
1000
800
50
0
50
0
900
50
800
45
35
40
55
48 50
55
60
65
70 72 75
Air flow (CMM)
Air flow (CMM)
PE-10MYC-EU
PEH-10MYA-EU
PE-8MYC-EU
PEH-8MYA-EU
Fan Performance Curve
50Hz
Fan Performance Curve
Fan speed
(rpm)
Fan speed
(rpm)
50Hz
(Pa)
450
(Pa)
450
Recommended Range
Recommended Range
400
350
300
400
350
300
For connection
operation line
For connection
operation line
1400
1300
1400
1300
1200
1200
250
200
150
100
250
200
150
100
1100
1000
For connection
operation line
For connection
operation line
1100
1000
900
800
50
0
50
0
800
90
900
- 37 -
60
70
80
100
50
55
60
65
70
75
80
Air flow (CMM)
Air flow (CMM)
Airflow
Model
CMM
L/S
PE-15MYC-EU, PEH-15MYA-EU
Total static
pressure
(Pa)
PE-15MYC-EU
PEH-15MYA-EU
110
1830
768
139.7
5.5
254
10
B45
2.2
898
114.3
4.5
120
130
2170
768
139.7
5.5
140
2330
768
139.7
5.5
150
2500
768
139.7
5.5
160
2670
170
2830
-
-
-
-
-
2000
FAN SPEED
rpm
768
139.7
5.5
-
-
-
-
-
-
-
PULLEYSIZE
(MOTOR SIDE)
mm
inch
200
PULLEYSIZE
(FAN SIDE)
BELT SIZE
mm
inch
inch
kw
254
10
B45
2.2
254
10
254
10
254
10
B45
2.2
B45
2.2
B45
2.2
-
-
Fan Performance Curve
50Hz
MOTOR
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
898
114.3
4.5
898
114.3
4.5
898
114.3
4.5
898
114.3
4.5
898
114.3
4.5
177.8
7
898
114.3
4.5
177.8
(Pa)
Recommended Range
300
177.8
7
177.8
7
177.8
7
177.8
7
177.8
7
1000
7
Fan speed
(rpm)
B38X2 B38X2 B38X2
B38X2 B38X2 B38X2
B38X2
2.2
971
139.7
5.5
203.2
8
B40X2
3.7
1067
152.4
MOTOR
2.2
942
152.4
6
228.6
9
B44
2.2
1008
127
5
2.2
942
152.4
6
2.2
942
152.4
6
2.2
942
152.4
6
2.2
971
139.7
5.5
2.2
971
139.7
5.5
203.2
8
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1300
800
600
228.6
9
228.6
9
228.6
9
203.2
8
400
1200
B44
2.2
1008
127
5
B44
2.2
1008
127
5
B44
2.2
1008
127
5
B40X2 B40X2
MOTOR
3.7
1067
152.4
6
3.7
1067
152.4
6
203.2
8
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1100
1000
6
500
177.8
7
177.8
7
177.8
7
177.8
7
203.2
8
203.2
8
B40X2
3.7
1119
139.7
5.5
177.8
B37X2 B37X2 B37X2
B37X2 B40X2 B40X2
MOTOR
3.7
1119
139.7
5.5
177.8
7
3.7
1119
139.7
5.5
3.7
1119
139.7
5.5
3.7
1119
139.7
5.5
3.7
1119
139.7
5.5
3.7
1119
139.7
5.5
177.8
7
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
400
200
600
700
800
177.8
7
177.8
7
177.8
7
177.8
7
900
7
B38X2 B38X2 B38X2
B38X2 B38X2 B38X2
B38X2
3.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
800
700
MOTOR
3.7
1190
127
5
152.4
6
3.7
1190
127
5
3.7
1190
127
5
3.7
1190
127
5
3.7
-
-
3.7
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
600
152.4
6
152.4
6
152.4
6
-
-
500
B36X2 B36X2 B36X2
B36X2
-
MOTOR
3.7
1258
177.8
7
203.2
8
3.7
3.7
3.7
-
0
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
110
120
130
140
150
160
170
Air flow (CMM)
standard point
B42
3.7
MOTOR
Std.
PE-20MYC-EU
PEH-20MYA-EU
Airflow
Model
CMM
L/S
PE-20MYC-EU, PEH-20MYA-EU
Total static
pressure
(Pa)
150
160
180
200
3330
692
127
5
220
3670
-
240
4000
2500
627
127
5
279.4
11
2670
627
127
5
279.4
11
3000
692
127
5
FAN SPEED
rpm
-
-
-
-
-
-
PULLEYSIZE
(MOTOR SIDE)
mm
inch
-
-
200
PULLEYSIZE
(FAN SIDE)
BELT SIZE
mm
inch
inch
kw
254
10
254
10
-
-
-
Fan Performance Curve
B44X2 B44X2 B42X2
B42X2
3.7
773
127
5
MOTOR
3.7
768
139.7
5.5
254
10
3.7
768
139.7
5.5
254
10
3.7
773
127
5
-
-
773
127
5
228.6
9
(Pa)
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
773
127
5
228.6
9
Recommended Range
1000
Fan speed
(rpm)
300
228.6
9
228.6
9
B43X2 B43X2 B40X2
B40X2 B40X2 B40X2
MOTOR
3.7
942
152.4
6
228.6
9
3.7
942
152.4
6
228.6
9
3.7
942
152.4
6
3.7
942
152.4
6
3.7
942
152.4
6
228.6
9
3.7
942
152.4
6
228.6
9
1300
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
800
600
228.6
9
228.6
9
400
1200
B42X2 B42X2 B42X2
B42X2 B41X2 B41X2
MOTOR
3.7
1008
127
5
177.8
7
3.7
1008
127
5
177.8
7
3.7
1008
127
5
3.7
1067
152.4
6
5.5
1067
152.4
6
203.2
8
5.5
1067
152.4
6
203.2
8
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1100
1000
500
177.8
7
203.2
8
B37X2 B37X2 B37X2
B39X2 B39X2 B39X2
MOTOR
3.7
1119
139.7
5.5
177.8
7
3.7
1119
139.7
5.5
177.8
7
3.7
1119
139.7
5.5
5.5
1119
139.7
5.5
5.5
1119
139.7
5.5
177.8
7
5.5
-
-
900
800
700
600
400
200
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
600
700
800
177.8
7
177.8
7
-
B37X2 B37X2 B37X2
B37X2 B37X2
-
MOTOR
5.5
1229
152.4
6
177.8
7
5.5
1229
152.4
6
177.8
7
5.5
1229
152.4
6
5.5
5.5
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
1229
152.4
6
177.8
7
177.8
7
0
B38X2 B38X2 B38X2
B38X2
MOTOR
5.5
1258
177.8
7
203.2
8
5.5
1258
177.8
7
203.2
8
5.5
1258
177.8
7
203.2
8
5.5
150 160
180
195200
220
240
FAN SPEED
PULLEYSIZE
(MOTOR SIDE)
PULLEYSIZE
(FAN SIDE)
BELT SIZE
rpm
mm
inch
mm
inch
inch
kw
-
-
-
-
-
-
-
Air flow (CMM)
standard point
B41X2 B41X2 B41X2
5.5 5.5 5.5
MOTOR
Std.
- 38 -
Pulley outside dimensions are shown below: (Unit : mm)
(1) Shape of belt groove
e
f
w
L0
V-belt
thickness
(Reference)
Shape of Nominal
V-belt Dia. øP.C (˚
a
)
W
L0
K
K0
e
f
r
1
r2
r3
r1
r3
a
Over 125
Under 160
34 15.86
r
2
r
2
Over 160
36
38
12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0
1~2
11
16.07
16.29
B
Under 200
Over 200
Sectional plan of V-belt
16.5mm
40Ëš
B type
(2) Shape of motor pulley boss (Unit : mm)
C
MOTOR
CAPACITY
(kW)
A
B
C
+0.028
+ 0.128
+ 0.007
+0.018
2.2, 3.7
5.5
28
31
41
8
+ 0.007
-0.018
+ 0.128
+ 0.009
+0.028
+ 0.007
+0.018
-0.018
38
10
- 39 -
SOUND DATA
Indoor units
Sound Levels
OCTAVE BAND FREQ. Hz
PWL
SPL
MODEL
dB(A)
dB(A)
63Hz
60.5
125Hz
57.5
250Hz
57.5
500Hz
52.5
1000Hz
50.5
2000Hz
43
4000Hz
34.5
8000Hz
28.5
PEH-5MYA-EU
63
55
PE-7MYC-EU
PEH-7MYA-EU
PE-8MYC-EU
PEH-8MYA-EU
PE-10MYC-EU
PEH-10MYA-EU
PE-15MYC-EU
PEH-15MYA-EU
PE-20MYC-EU
PEH-20MYA-EU
62
63
62
25
32
60
61
54
55
53
54
50
51
42.5
43.5
48
37
38
31.5
32.5
36
63
64
67
69
70
55
56
59
61
62
62.5
40
58.5
47
59.5
52
53
43.5
52
36.5
51
55
57.5
57.5
44
49
53.5
56.5
53
Outdoor units
Sound Levels
OCTAVE BAND FREQ. Hz
PWL
SPL
MODEL
dB(A)
dB(A)
63Hz
68
125Hz
58
250Hz
57
500Hz
52.5
1000Hz
52
2000Hz
47.5
4000Hz
49
8000Hz
40
68
57
65
65
PUH-5MYE-EU
PU-7MYC1-EU
PUH-7MYC1-EU
PU-8MYC1-EU
PUH-8MYC1-EU
76
62
62
63.5
63.5
62
62
62
62
60
60
57.5
57.5
54
54
54
54
76
76
76
65
65
PUH-8MYE-EU
45.4
64.5
58
65
58
64
58.5
62.5
61
60
60
57
51.5
54.5
47
53
PU-10MYC1-EU
PUH-10MYC1-EU
45.4
68
58
72
69
51
51
58
70
58.5
65
61
60
62
65
65
60
57
59
64
64
51.5
53
47
76
78
79
80
80
65
67
68
69
69
PUH-10MYE-EU
PU-15MYC1-EU
49.5
53
PU-20MYC1-EU
66
70.5
59
65
56.5
55
43
64
50.5
51.5
PUH-15MYC1-EU
PUH-20MYC1-EU
43
59
64.5
55.5
Position mesurement
Indoor unit
Outdoor unit
PE(H)
PU(H)
1m
Service
panel side
Inlet
Outlet
1m
1m
- 40 -
OUTLINE DIMENSIONS
PEH-5
POWER SUPPLY
104
135 66
782
130 130 130 130 130
34
66
CABLE ENTRY ø27
HOLES:18-ø3.1
(Bottom side)
CONTROL
CABLE ENTRY ø27
(Bottom side)
AIR INLET DUCT
FLANGE
105 40
OPTIONAL PARTS
CABLE ENTRY ø27
(Bottom side)
960
20
20
CONTROL BOX
HOLES:14-ø3.1
HOLES:4-ø12
55
130 130 130
55
AIR OUTLET DUCT
FLANGE
1095
1000
920
650
530
50
15
70
40
40
15
210
500
210
REFRIGERANT
PIPE ø19.05
(3/4)
REFRIGERANT
PIPE ø12.7
(1/2)
AIR OUTLET
AIR INLET
944
33
562
DRAIN:RC1
PE(H)-7,8
104
1102
34
31
HOLES:24- 3.1
POWER SUPPLY
CABLE ENTRY 27
135 31
130 130 130 130 130 130 130 130
(Bottom side)
CONTROL
CABLE ENTRY 27
(Bottom side)
AIR INLET DUCT
FLANGE
40
105
OPTIONAL PARTS
CABLE ENTRY 27
(Bottom side)
1280
20
20
CONTROL BOX
HOLES:22- 3.1
HOLES:4- 12
45
130 130 130 130 130 130 130
45
AIR OUTLET DUCT
FLANGE
1415
1320
1240
1000
650
530
50
15
70
40
40
15
120
120
REFRIGERANT PIPE
25.4
(1)
REFRIGERANT PIPE
15.88
(5/8)
AIR
AIR
OUTLET
INLET
562
33
1264
DRAIN:Rc1
- 41 -
PE(H)-10
104
1302
34
POWER SUPPLY
CABLE ENTRY 27
(Bottom side)
HOLES:26- 3.1
66 130 130 130 130 130 130 130 130 130 66
135
105
AIR INLET DUCT
FLANGE
40
CONTROL
CABLE ENTRY 27
(Bottom side)
OPTIONAL PARTS
CABLE ENTRY 27
(Bottom side)
1480
20
20
CONTROL BOX
HOLES:22- 3.1
45
130 130 130 130 130 130 130
45
HOLES:4- 12
AIR OUTLET DUCT
FLANGE
1615
1520
650
530
70
50
40
40
1440
1000
220
220
15
15
REFRIGERANT PIPE
28.6
(1-1/8)
REFRIGERANT PIPE
15.88
(5/8)
AIR
OUTLET
AIR
INLET
1464
33
562
DRAIN:Rc 1
PE(H)-15
1690
1418
1300=130X10
HOLES:34- 3.1
70 120
49
AIR INLET DUCT
FLANGE
59
59
130
POWER SUPPLY
CABLE ENTRY 27
(BOTTOM SIDE)
CONTROL
CABLE ENTRY 27
(BOTTOM SIDE)
REFRIGERANT
PIPE 15.88 (5/8)
REFRIGERANT
PIPE 25.4 (1)
25
25
OPTIONAL PARTS
1637
HOLES:4- 12
CABLE ENTRY 27
REFRIGERANT
PIPE 15.88 (5/8)
CONTROL BOX
REFRIGERANT
PIPE 25.4 (1)
34
130
81
AIR OUTLET DUCT
FLANGE
46
46
910=130X7
1002
HOLES:24- 3.1
484
101
VIEW A
865
746
69
50
15
15
AIR OUTLET
AIR INLET
AIR OUTLET
AIR INLET
A
1587
50
50
DRAIN: Rc1
- 42 -
PE(H)-20
1993
1648
1560=130X12
HOLES:38- 3.1
70 193
49
AIR INLET DUCT
FLANGE
44
44
130
POWER SUPPLY
CABLE ENTRY
(BOTTOM SIDE)
27
CONTROL
CABLE ENTRY 27
(BOTTOM SIDE)
REFRIGERANT
PIPE 15.88 (5/8)
REFRIGERANT
PIPE 28.6
25
1940
OPTIONAL PARTS
CABLE ENTRY 27
25
(1-1/8)
HOLES:4- 12
REFRIGERANT
PIPE 15.88 (5/8)
CONTROL BOX
REFRIGERANT
PIPE 28.6 (1-1/8)
130
AIR OUTLET DUCT
FLANGE
44
81
21
1170=130X9
1212
21
142
HOLES:28- 3.1
536
865
746
VIEW A
50
69
50
15
15
AIR OUTLET
AIR INLET
AIR OUTLET
AIR INLET
A
1890
50
50
DRAIN:Rc 1
- 43 -
PUH-5
AIR INLET
AIR INLET
Holes :4-12X20
AIR OUTLET
21
1040
1000
21
550
SERVICE PANEL
131
126
REFRIGERANT PIPE
ø12.7 (1/2)
CABLE ENTRY
Holes : 2-ø15
21
REFRIGERANT PIPE
ø19.05(3/4)
Hole : ø15
275
275
18
75
400
75
PU(H)-7,8,10
(Upper blow)
AIR INLET
AIR INLET
200
1000
CABLE ENTRY 25X40
AIR OUTLET
350
700
Holes: 4-12X20
SERVICE PANEL
REFRIGERANT PIPE
ø15.88 (5/8)
AIR INLET
120
REFRIGERANT PIPE
PU(H)- 7,8:ø25.4(1)
PU(H)- 10:ø28.6(1-1/8)
34
18
108
160
25
1400
25
540
700
25
25
- 44 -
PUH-8,10
(Side blow)
AIR INLET
AIR INLET
Holes : 4-12X20
21
1290
1250
21
AIR OUTLET
550
SERVICE PANEL
REFRIGERANT PIPE
ø15.88(5/8)
130
CABLE ENTRY
44
49
56
REFRIGERANT PIPE
PUH-8:ø25.4(1)
PUH-10:ø28.6(1-1/8)
Hole : ø15
Holes : 2-ø15
275
275
75
400
75
PU-15
AIR INLET
AIR INLET
AIR INLET
998
AIR OUTLET
998
HOLES: 4-Uø15
SERVICE PANEL
REFRIGERANT PIPE
ø15.88(5/8)
REFRIGERANT PIPE
ø25.4(1)
No.1
No.2
78
CONTROL
169
242
CABLE ENTRY ø27
50
137
721
137
POWER SUPPLY
CABLE ENTRY ø43
- 45 -
PU-20
AIR INLET
AIR INLET
AIR INLET
HOLES: 6-ø15
No.1
No.2
2036
17
17
REFRIGERANT PIPE
ø28.6(1-1/8)
REFRIGERANT PIPE
ø15.88(5/8)
1996
AIR OUTLET
998
SERVICE PANEL
CONTROL
CABLE ENTRY ø27
POWER SUPPLY
CABLE ENTRY ø47
213 80
392
756475
PUH-15,20
Holes : 4-12X20
27
2005
994
27
830
478.5
CONTROL BOX
SERVICE PANEL
REFRIGERANT PIPE
ø15.88 (5/8)
REFRIGERANT PIPE
PUH-15:ø25.4(1)
PUH-20:ø28.6(1-1/8)
No.2
No.1
68
25
911
128
1080
54
1951
2059
54
- 46 -
Note: In the case of installation are shown below, it is possible to use the unit by connecting the duct.
However, the pressure loss must be 30Pa (3mmAg) or less.
Duct work is local supply.
DUCT
DUCT
- 47 -
WIRING DIAGRAMS
PE-7MYC-EU (STANDARD)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
C4
1
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
PU-7MYC1-EU
N
BLUE
2
3
1
2
3
WHITE
BLACK
RED
WHITE
BLACK
F3(3.15A)
MF2
MF3
PE
WHITE
BLACK
49C
C5
52C
51F2
TB5
15
63H
GRAY
51C
CZ2
CZ2
CH
30
CZ
CR2
14
52C
30
CZ
JUMPER
Power supply, Single Phase
TB4
C1
TB2
L
TB4
5
RED
1
2
50Hertz
51F1
220 240Volt,
52F
C1
RED
5
6
Hi
6
7
BROWN
C
MF1
Low
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
PE-7MYC-EU
N
SW2(FIELD SUPPLY)
BLUE
BLUE
4
TB4
52F
F1
(3.15A)
GRAY
1
RED
SWITCH BOX
(FIELD SUPPLY)
CZ1
PE
TB3 15
F2
51F1
(3.15A)
15
23WA
C3
1
OUTDOOR
26L
SW1
C3
3
Tr
FZ
CZ2
AC
AC
24V
220
240V
2
3
TB4
30FZ
CR1
CZ1
14
14
52F
30
FZ
FZ
GRAY
4
BLUE
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Please remove the jumper wire ( Mark) in the above
diagram if you use the Switch <SW2> at local.
If the Switch <SW2> is not used, the Fan motor
(indoor) drives at high speed.
TB1
F1
5
Crankcase heater
Fuse (3.15A)
6.Specification subject to change without notice.
3
Caution,
Transformer
Internal thermostat
Over current relay
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
(compressor)
(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat (freeze protection)
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (on)
Switch (Fan Hi-Low)
Thermostat (room temp.)
Run capacitor
26L
Option controller connection.
PAC-204RC (Option)
terminal no.
CZ1, 2
30CZ, FZ
Symbol No. Function
1
2
3
4
Power (Active)
Cooling operation
Fan operation
24VAC(L)
COMP
FAN HI
24VAC(N)
TB4
Power (Neutral)
C
C1, 3 ~ 5
CR1, 2
Connector
Surge killer
- 48 -
PE-8,10MYC-EU (STANDARD)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
C4
1
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
PU-8, 10MYC1-EU
N
2
3
1
2
3
WHITE
BLACK
RED
BLUE
WHITE
BLACK
F3(3.15A)
MF2
MF3
PE
WHITE
BLACK
49C
C5
52C
51F2
TB5
15
63H
GRAY
51C
CZ2
CZ2
CH
30
CZ
CR2
14
52C
30
CZ
Power supply,
380 415Volt,
3Phase
50Hertz
TB2
L1
51F1
52F
C1
C2
RED
1
RED
1
2
3
RED
2
3
WHITE
BLUE
WHITE
BLUE
WHITE
BLACK
L2
L3
MF1
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
F1(3.15A)
RED
PE-8,10MYC-EU
N
51F1
52F
TB4
1
GRAY
C1
4
SWITCH BOX
(FIELD SUPPLY)
PE
CZ1
TB3 15
49F
C1
5
F2
(3.15A)
15
C3
1
23WA
OUTDOOR
26L
C3
3
Tr
SW1
CZ2
FZ
AC
220
240V
AC
24V
CR1
2
3
30FZ
TB4
14
14
52F
CZ1
30
FZ
FZ
GRAY
4
BLUE
Attach the accessory
Remove
C1
C2
1
2
3
1
2
3
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
1
2
3
MF1
Contactor (compressor)
Contactor (fan I/D)
Terminal block
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
TB1
5
Crankcase heater
Fuse (3.15A)
Transformer
Internal thermostat
Internal thermostat
Over current relay
Note:1.The dotted lines show field wiring.
F1
3
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
(indoor fan)
(compressor)
(compressor)
49F
5.Specification subject to change without notice.
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat (freeze protection)
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
Caution,
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
26L
CZ1, 2
30CZ, FZ
Option controller connection.
PAC-204RC (Option)
C1~5
CR1, 2
Symbol No. Function
terminal no.
1
2
3
4
Power (Active)
Cooling operation
Fan operation
24VAC(L)
COMP
FAN HI
24VAC(N)
TB4
Power (Neutral)
- 49 -
PE-15MYC-EU (STANDARD)
TB1
L1
OUTDOOR UNIT
52C1
51C1
RED
RED
Power supply, 3 Phase
380~415 Volt, 50Hertz
RED
L2
L3
WHITE
BLACK
WHITE
BLACK
MC1
MF2
WHITE
BLACK
52F2
51F2
C1
N
1
2
3
BLUE
RED
RED
52C2
51C2
WHITE
BLACK
WHITE
BLACK
PE
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY)
WHITE
BLACK
WHITE
BLACK
MC2
PU-15MYC1-EU ---100A
F3 (3.15A)
51
F2
52
C1
52
C2
49C1
51C1
49C2
51C2
TB4
52
C1
52
C2
11 12
GRAY
CZ
2-1
63H1
63H2
30
CH1 CH2
CZ
2-2
2
30
CZ1
CZ2-1
CR3
CZ2-2
CR2
CZ2
52
C1
52
C2
52
F2
2
13
30
30
CZ2
CZ1
TB2
51F1
52F1
INDOOR UNIT
Power supply, 3 Phase
380~415 Volt, 50Hertz
L1
L2
L3
RED
WHITE
BLACK
MF1
BLUE
N
F1
52F1
(3.15A)
1
PE
GRAY
TB3
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
PE-15MYC-EU ---30A
C3
1
CZ CZ
1-1 1-2
SWITCH BOX (FIELD SUPPLY)
26L1
F2
(3.15A)
C3
3
TB3
Tr
C8
1
OUTDOOR
11 12
11 12
AC
26L2
AC
220
24V
240V
C8
3
23
WA
23
WA
SW1
FZ
CZ
2-1
CZ
2-2
30
FZ
CR1
3
4
2
52
F1
TB3
30
FZ
CZ
CZ
1-2
13
FZ
1-1
GRAY
13
5
Symbol
MC1,2
MF1
Name
Note:1.The dotted lines show field wiring.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
MF2
5.Specification subject to change without notice.
52C1,2
52F1
52F2
Caution,
1.To protect each Fan motor and Compressor from abnormal
TB1
CH1,2
F1
Tr
4
current, Over current relays <51C1,2>, <51F1,2,3> are installed.
Therefore, do not change factory set value of Over current
relays.
3
49C1,2
51C1,2
51F1
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
51F2
Option controller connection.
63H1,2
26L1,2
FZ
PAC-204RC (Option)
Symbol No. Function
Thermostat (freeze protection)
Auxiliary relay (fan)
terminal no.
1
2
3
4
5
Power (Active)
Cooling operation
Cooling operation
Fan operation
24VAC(L)
COMP1
COMP2
FAN HI
30FZ
Auxiliary relay (fan)
TB3
CZ1-1,2/2-1,2 Auxiliary relay
30CZ1,2
<SW1>
<23WA>
C1, 3, 8
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
Power (Neutral)
24VAC(N)
CR1
2
3
Timer
- 50 -
PE-20MYC-EU (STANDARD)
TB1
OUTDOOR UNIT
51C1
51C2
52C1
52C2
52F2
L1
L2
L3
RED
RED
Power supply, 3 Phase
380~415 Volt, 50Hertz
RED
WHITE
BLACK
WHITE
BLACK
MC1
MC2
WHITE
BLACK
N
BLUE
RED
RED
PE
WHITE
BLACK
WHITE
BLACK
CIRCUIT BREAKER
(FIELD SUPPLY)
PU-20MYC1-EU---125A
51F2
51F3
C1
C2
1
2
3
RED
RED
(3.15A)
F3
WHITE
BLACK
WHITE
BLACK
MF2
MF3
1
2
3
RED
RED
49C1
49C2
52
52
WHITE
BLACK
WHITE
BLACK
C1 C2
51
F2
51
F3
52
C1
52
C2
63H1
51C1
63H2
51C2
TB4
11 12
GRAY
CH1 CH2
2
CZ
2-1
30
CZ1
30
CZ2
CZ2-1
52
CR3
CZ2-2
CR2
CZ
2-2
52
F2
52
2
C1
C2
30
30
CZ2
CZ1
13
TB2
51F1
52F1
INDOOR UNIT
Power supply, 3 Phase
380~415 Volt, 50Hertz
L1
L2
L3
RED
WHITE
BLACK
MF1
52F1
BLUE
N
F1
(3.15A)
1
PE
GRAY
TB3
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
PE-20MYC-EU---30A
C3
1
CZ CZ
1-1 1-2
SWITCH BOX (FIELD SUPPLY)
26L1
F2
(3.15A)
C3
3
TB3
Tr
C8
1
OUTDOOR
11 12
11 12
AC
26L2
AC
220
C8
3
24V
240V
23
23
WA
SW1
FZ
WA
CZ
2-1
CZ
2-2
30
FZ
CR1
3
4
2
52
F1
TB3
30
FZ
CZ
CZ
1-2
13
FZ
1-1
5
GRAY
13
Symbol
MC1,2
MF1
MF2,3
52C1,2
52F1
Name
Note:1.The dotted lines show field wiring.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
Caution,
52F2
TB1
1.To protect each Fan motor and Compressor from abnormal
4
current, Over current relays <51C1,2>, <51F1,2,3> are installed.
Therefore, do not change factory set value of Over current
relays.
CH1,2
F1
Tr
3
49C1,2
51C1,2
51F1,2
51F2,3
63H1,2
26L1,2
FZ
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
Thermostat (freeze protection)
Auxiliary relay (fan)
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
2
3
4
5
Power (Active)
Cooling operation
Cooling operation
Fan operation
24VAC(L)
COMP1
COMP2
FAN HI
30FZ
Auxiliary relay (fan)
TB3
CZ1-1,2/2-1,2 Auxiliary relay
30CZ1,2
<SW1>
<23WA>
C1~3, 8
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Power (Neutral)
24VAC(N)
CR1
2
3
Surge killer
Timer
- 51 -
PE-7MYC-EU
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
C4
C5
F3(3.15A)
1
2
3
1
2
3
RED
RED
PU-7MYC1-EU
N
BLUE
WHITE
BLACK
RED
WHITE
BLACK
MF2
MF3
PE
49C
WHITE
BLACK
TB5
15
52C
GRAY
51F2
63H
CZ2
51C
CZ2
14
CH
30
CZ
CR2
52C
30
CZ
JUMPER
Power supply, Single Phase
50Hertz
TB4
C1
TB2
L
TB4
5
1
2
RED
51F1
220 240Volt,
52F
C1
RED
5
6
Hi
6
7
BROWN
BLUE
C
MF1
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
Low
PE-7MYC-EU
SW2(FIELD SUPPLY)
4
N
BLUE
F1
TB4
52F
(3.15A)
GRAY
1
RED
SWITCH BOX
(FIELD SUPPLY)
CZ1
PE
51F1
F2
(3.15A)
TM
(3MIN)
C3
1
TB3
23WA
15
26L
15
OUTDOOR
SW1
Tr
C3
3
FZ
AC
220
240V
CZ2
AC
24V
2
3
TB4
30FZ
TM
CR1
CZ1
14
14
52F
30
FZ
FZ
GRAY
4
BLUE
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Please remove the jumper wire ( Mark) in the above
diagram if you use the Switch <SW2> at local.
If the Switch <SW2> is not used, the Fan motor
(indoor) drives at high speed.
TB1
F1
5
6.When PAC-204RC is used, Timer(TM)is unneccessary.
7.Specification subject to change without notice.
3
(compressor)
(compressor)
Internal thermostat
Over current relay
Caution,
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat (freeze protection)
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (on)
Switch (Fan Hi-Low)
Thermostat (room temp.)
Run capacitor
26L
CZ1, 2
30CZ, FZ
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
2
3
4
Power (Active)
Cooling operation
Fan operation
24VAC(L)
COMP
FAN HI
24VAC(N)
TB4
C
Power (Neutral)
C1, 3~5
CR1, 2
TM
Connector
Surge killer
Timer (Anti short cycle)
- 52 -
PE-8,10MYC-EU
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
C4
1
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
PU-8, 10MYC1-EU
BLUE
N
2
3
1
2
3
WHITE
BLACK
RED
WHITE
BLACK
F3(3.15A)
MF2
MF3
PE
WHITE
BLACK
49C
C5
52C
51F2
TB5
15
63H
GRAY
51C
CZ2
CZ2
CH
30
CZ
CR2
14
52C
30
CZ
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
51F
52F
C1
C2
1
RED
RED
1
2
3
RED
2
3
WHITE
BLUE
WHITE
BLUE
L2
L3
WHITE
BLACK
MF1
1
F3(3.15A)
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
PE-8, 10MYC-EU
RED
N
TB4
52F
GRAY
51F1
SWITCH BOX
(FIELD SUPPLY)
CZ1
PE
C1
4
F2
(3.15A)
49F
TM
(3MIN)
C1
5
23WA
TB3
15
C3
1
OUTDOOR
15
26L
SW1
Tr
C3
3
FZ
CZ2
AC
24V
AC
220
CR1 240V
TM
30FZ
TB4
2
3
14
14
52F
CZ1
30
FZ
FZ
GRAY
4
BLUE
Attach the accessory
Remove
C1
C2
1
2
3
1
2
3
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
1
2
3
MF1
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse (3.15A)
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
TB1
F1
5
Note:1.The dotted lines show field wiring.
3
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Transformer
(indoor fan)
(compressor)
(compressor)
Internal thermostat
Internal thermostat
Over current relay
49F
5.When PAC-204RC is used, Timer(TM)is unneccessary.
6.Specification subject to change without notice.
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat (freeze protection)
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
Caution,
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
26L
CZ1, 2
30CZ, FZ
Option controller connection.
PAC-204RC (Option)
terminal no.
C1~ 5
CR1, 2
TM
Symbol No. Function
1
2
3
4
Power (Active)
Cooling operation
Fan operation
24VAC(L)
Timer (Anti short cycle)
COMP
FAN HI
24VAC(N)
TB4
Power (Neutral)
- 53 -
PE-15MYC-EU
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)
OUTDOOR UNIT
TB1
52C1
51C1
RED
RED
L1
Power supply, 3 Phase
380~415 Volt, 50Hertz
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC1
MF2
WHITE
BLACK
51F2
52F2
C1
N
1
2
3
RED
RED
52C2
51C2
BLUE
WHITE
BLACK
WHITE
BLACK
PE
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY)
WHITE
BLACK
WHITE
BLACK
MC2
PU-15MYC1-EU ··· 100A
F3(3.15A)
51
F2
49C1
51C1
52
C1
52
C2
49C2
51C2
CZ2-2
CZ2-1
TB4
52
52
TM
(3min)
C1 C2
11 12
GRAY
52
C2
TM
(3min)
52
C1
52
C2
52
C1
CZ
2-1
63H1
63H2
CH1 CH2
CZ
2-2
2(2sec)
CR3
30
CZ1
30
CZ2
CR2
CZ2-1
52
CZ2-2
52
C2
52
F2
2
TM
C1
13
30
CZ1
30
CZ2
TB2
51F1
52F1
INDOOR UNIT
L1
L2
L3
RED
Power supply, 3 Phase
380~415 Volt, 50Hertz
WHITE
BLACK
MF1
N
BLUE
F1
52F1
(3.15A)
1
GRAY
PE
TB3
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
CZ
1-1
CZ
1-2
C3
1
PE-15MYC-EU ··· 30A
SWITCH BOX (FIELD SUPPLY)
26L1
F2
(3.15A)
C3
3
TB3
Tr
AC
C8
1
OUTDOOR
11
12
12
26L2
AC
24V
220~
240V
11
C8
3
23
WA
23
WA
SW1
FZ
CZ
2-1
CZ
2-2
30
FZ
CR1
3
4
2
52
F1
TB3
30
FZ
CZ
1-1
CZ
1-2
13
FZ
GRAY
5
13
Symbol
Name
MC1,2
MF1
MF2
52C1,2
52F1
52F2
TB1~4
CH1,2
F1~3
Tr
49C1,2
51C1,2
51F1
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.When PAC-204RC is used, Timer(TM)is unneccessary.
6.Specification subject to change without notice.
Caution,
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,
do not change factory set value of Over current relays.
2.To protect the starting Compressor<MC1,2>at the same time, Timer
<2> is installed. Therefore, do not change factory set value of this Timer.
3.To protect the starting Compressor<52C1,2>frequently, Timer
<TM> is installed. Therefore, do not change factory set value of this Time
51F2
63H1,2
26L1,2
FZ
Thermostat (freeze protection)
Auxiliary relay (fan)
30FZ
Auxiliary relay (fan)
CZ1-1,2/2-1,2 Auxiliary relay
Option controller connection.
30CZ1,2
<SW1>
<23WA>
C1, 3, 8
CR1~3
2
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
PAC-204RC (Option)
Symbol No. Function
terminal no.
24VAC(L)
1
2
3
4
5
Power (Active)
Cooling operation
Cooling operation
Fan operation
COMP1
COMP2
FAN HI
TB3
Timer
TM
Timer (Anti short cycle.)
Power (Neutral)
24VAC(N)
- 54 -
PE-20MYC-EU
(SPECIAL ORDER : ANTI SHORT CYCLE TIMER)
OUTDOOR UNIT
TB1
52C1
51C1
51C2
RED
RED
L1
L2
L3
Power supply, 3 Phase
380~415 Volt, 50Hertz
RED
WHITE
BLACK
WHITE
BLACK
MC1
MC2
WHITE
BLACK
BLUE
N
52C2
RED
RED
PE
WHITE
BLACK
WHITE
BLACK
CIRCUIT BREAKER
(FIELD SUPPLY)
PU-20MYC1-EU ··· 125A
52F2
51F2
51F3
C1
1
RED
WHITE
BLACK
RED
F3(3.15A)
2
3
WHITE
BLACK
MF2
MF3
C2
1
2
3
RED
WHITE
BLACK
RED
WHITE
BLACK
49C1
49C2
52 52
C1 C2
CZ2-2
CZ2-1
51
F2
51
F3
52
52
TM
(3min)
C1
C2
63H1
51C1
63H2
51C2
52
C2
TM
(3min)
52
52
TB4
C1
C2
52
C1
11 12
GRAY
CH1 CH2
2(2sec)
CR3
CZ
2-1
30
CZ1
30
CR2
CZ2-1
52
CZ2-2
CZ
2-2
CZ2
52
52
F2
2
TM
C1
C2
30
30
CZ2
CZ1
13
TB2
51F1
52F1
INDOOR UNIT
Power supply, 3 Phase
380~415 Volt, 50Hertz
L1
L2
L3
RED
WHITE
BLACK
MF1
N
BLUE
F1
(3.15A)
52F1
1
GRAY
PE
TB3
51F1
CIRCUIT BREAKER
(FIELD SUPPLY)
PE-20MYC-EU ··· 30A
CZ
1-1
CZ
1-2
C3
1
SWITCH BOX (FIELD SUPPLY)
26L1
F2
C3
3
(3.15A)
TB3
Tr
AC
C8
1
OUTDOOR
11
11
12
12
26L2
AC
24V
220~
240V
C8
3
SW1
23
WA
23
WA
FZ
CZ
2-1
CZ
2-2
30
FZ
CR1
3
4
2
52
F1
TB3
30
FZ
CZ
CZ
1-2
13
FZ
1-1
GRAY
5
13
Symbol
MC1,2
MF1
MF2,3
52C1,2
52F1
Name
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
52F2
5.When PAC-204RC is used, Timer(TM)is unneccessary.
6.Specification subject to change without notice.
TB1~4
CH1,2
F1~3
Caution,
Tr
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,
do not change factory set value of Over current relays.
49C1,2
51C1,2
51F1
2.To protect the starting Compressor <MC1,2>at the same time, Timer
<2> is installed. Therefore, do not change factory set value of this Time
3.To protect the starting Compressor<52C1,2> frequently, Timer
<TM> is installed. Therefore, do not change factory set value of this Ti
51F2,3
63H1,2
26L1,2
FZ
Thermostat (freeze protection)
Auxiliary relay (fan)
30FZ
Auxiliary relay (fan)
CZ1-1,2/2-1,2 Auxiliary relay
Option controller connection.
30CZ1,2
<SW1>
<23WA>
C1~3, 8
CR1~3
2
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
Timer
PAC-204RC (Option)
Symbol No. Function
terminal no.
24VAC(L)
COMP1
COMP2
FAN HI
1
2
3
4
5
Power (Active)
Cooling operation
Cooling operation
Fan operation
TB3
TM
Timer (Anti short cycle.)
Power (Neutral)
24VAC(N)
- 55 -
PE-7MYC-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
Power supply,
3Phase
TB1
L1
52C
51C
380 415Volt,50Hertz
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
52F3
51F2
C4
C6
2
F3(3.15A)
WHITE
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
1
2
3
RED
RED
PU-7MYC1-EU
N
BLUE
WHITE
BLACK
BLACK
RED
3
1
WHITE
BLACK
MF2
49C
PE
52F2
51F2
1
23C
5
52C
C4
4
TB5
3
15
52F4
49F
GRAY
1
RED
H
C4
5
2
3
WHITE
BLACK
MF3
63H
CZ2
52
F3
52
F2
C5
51C
CZ2
52F3
52F2
52F4
CR2
CH
14
30
CZ
52C
30
CZ
JUMPER
Power Supply, Single Phase
220 240Volt,50Hertz
TB4
C1
TB2
L
TB4
5
1
2
RED
51F1
52F1
C1
RED
5
Hi
6
7
BROWN
BLUE
C
6
MF1
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
Low
PE-7MYC-EU
4
N
SW2(FIELD SUPPLY)
BLUE
F1
TB4
(3.15A)
52F1
GRAY
1
RED
SWITCH BOX
CZ1
(FIELD SUPPLY)
PE
TB3 15
51F1
F2
(3.15A)
C3
1
15
23WA
OUTDOOR
26L
SW1
C3
3
Tr
FZ
CZ2
AC
24V
AC
220
2
3
240V
TB4
30FZ
CR1
CZ1
14
14
52F1
30
FZ
FZ
GRAY
4
BLUE
Note:1.The dotted lines show field wiring.
Compressor motor
Fan motor (indoor)
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Please remove the jumper wire ( Mark) in the above
diagram if you use the Switch <SW2> at local.
If the Switch <SW2> is not used, the Fan motor
(indoor) drives at high speed.
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Ambient temperature
Terminal block
52F1
52F2
23C
TB1
CH
F1
4
6.Specification subject to change without notice.
5
Crankcase heater
Fuse (3.15A)
Transformer
Internal thermostat
Internal thermostat(fan O/D)
Over current relay
Over current relay(fanI/D,O/D)
Thermostat (freeze protection)
High-pressure switch
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (on)
Switch (Fan Hi-Low)
Thermostat (room temp.)
Run capacitor
Caution,
3
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
Tr
(compressor)
49F
26L
(compressor)
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
CZ1, 2
30CZ, FZ
1
2
3
4
Power (Active)
Cooling operation
Fan operation
24VAC(L)
COMP
FAN HI
24VAC(N)
TB4
Power (Neutral)
C
C1, 3~6
CR1, 2
Connector
Surge killer
- 56 -
PE-8,10MYC-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
Power Supply, 3Phase
TB1
380 415Volt, 50Hertz
52C
51C
RED
RED
L1
L2
L3
RED
WHITE
BLACK
WHITE
BLACK
MC
52F3
51F2
C6
CIRCUIT BREAKER
(FIELD SUPPLY)100A
C4
WHITE
1
2
3
RED
2
3
1
RED
PU-8,10MYC1-EU
N
BLUE
WHITE
BLACK
WHITE
BLACK
BLACK
RED
F3(3.15A)
MF2
52F2
PE
49C
51F2
1
23C
5
52C
52F4
1
RED
C4
4
3
2
3
WHITE
BLACK
MF3
49F2
H
TB5
GRAY
C4
5
15
C5
63H
52
F3
52
F2
51C
CZ2
CZ2
52F3
52F2
52F4
CH
30
CZ
CR2
14
52C
30
CZ
Power Supply, 3Phase
380 415Volt, 50Hertz
TB2
L1
51F
52F1
C1
C2
1
2
3
RED
RED
1
2
3
RED
WHITE
BLUE
WHITE
BLUE
WHITE
BLACK
L2
L3
MF1
CIRCUIT BREAKER
(FIELD SUPPLY)15A
F1(3.15A)
PE-8,10MYC-EU
RED
N
TB4
1
52F1
GRAY
51F1
SWITCH BOX
(FIELD SUPPLY)
C1
4
PE
CZ1
TB3 15
49F1
F2
(3.15A)
C1
5
C3
1
15
23WA
OUTDOOR
26L
C3
3
Tr
SW1
CZ2
FZ
AC
AC
220
240V
24V
CR1
2
3
30FZ
TB4
14
14
52F1
CZ1
30
FZ
FZ
GRAY
4
BLUE
Attach the accessory
Remove
C1
C2
1
2
3
1
2
3
1
2
3
MF1
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Ambient temperature
Terminal block
Crankcase heater
Fuse (3.15A)
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
52F1
52F2
23C
TB1
CH
4
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5
F1
3
5.Specification subject to change without notice.
Transformer
Tr
49F1
49F2
(indoor fan)
(outdoor fan)
(compressor)
(compressor)
Internal thermostat
Internal thermostat
Internal thermostat
Over current relay
Caution,
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
Over current relay(fanI/D,O/D)
Thermostat (freeze protection)
High-pressure switch
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
26L
Option controller connection.
CZ1, 2
30CZ, FZ
PAC-204RC (Option)
terminal no.
Symbol No. Function
1
2
3
4
Power (Active)
Cooling operation
Fan operation
24VAC(L)
COMP
FAN HI
24VAC(N)
TB4
C1~6
CR1, 2
Power (Neutral)
- 57 -
PE-15MYC-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
OUTDOOR UNIT
TB1
52C1
51C1
RED
RED
L1
Power supply, 3 Phase
380~415 Volt, 50Hertz
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC1
C2
WHITE
BLACK
51F2
52F3
C1
1
N
RED
RED
2
RED
52C2
51C2
BLUE
2
3
3
1
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
RED
PE
RED
MF2
CIRCUIT BREAKER
(FIELD SUPPLY)
WHITE
BLACK
WHITE
BLACK
MC2
52F2
PU-15MYC1-EU ··· 100A
F3(3.15A)
51
F2
49C1
51C1
52
C1
52
49C2
C2
TB4
52
52
C1 C2
51C2
63H2
26D
11 12
GRAY
CZ
2-1
63H1
H
CH1 CH2
CZ
2-2
2
52
F3
52
F2
30
30
CR3
CR2
CZ2-1
52
CZ2-2
CZ1
CZ2
52
C2
52
F2
52
F3
2
C1
13
30
CZ1
30
CZ2
TB2
51F1
52F1
INDOOR UNIT
L1
L2
L3
RED
Power supply, 3 Phase
380~415 Volt, 50Hertz
WHITE
BLACK
MF1
52F1
N
BLUE
F1
(3.15A)
1
GRAY
PE
TB3
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
PE-15MYC-EU ··· 30A
C3
1
SWITCH BOX (FIELD SUPPLY)
CZ
1-1
CZ
1-2
26L1
F2
(3.15A)
C3
3
TB3
Tr
C8
1
OUTDOOR
12
11
AC
220~
240V
26L2
AC
11
12
C8
3
24V
SW1
23
23
FZ
WA
WA
CZ
2-1
CZ
2-2
30
FZ
CR1
3
4
2
52
F1
TB3
30
FZ
CZ
1-1
CZ
1-2
13
FZ
GRAY
5
13
Symbol
MC1,2
MF1
MF2
52C1,2
52F1
Name
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
Thermostat (freeze protection)
Auxiliary relay (fan)
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
52F2
TB1~4
CH1,2
F1~3
Tr
49C1,2
51C1,2
51F1
51F2,3
63H1,2
26L1,2
FZ
Caution,
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays <51C1,2>,<51F1,2> are installed. Therefore,
do not change factory set value of Over current relays.
2.To protect the starting Compressor <MC1,2>at the same time,Timer
<2> is installed. Therefore, do not change factory set value of this Timer.
30FZ
Auxiliary relay (fan)
CZ1-1,2/2-1,2 Auxiliary relay
Option controller connection.
30CZ1,2
<SW1>
<23WA>
C1~3, 8
CR1~3
2
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
Timer
PAC-204RC (Option)
Symbol No. Function
terminal no.
24VAC(L)
COMP1
COMP2
FAN HI
1
2
3
4
5
Power (Active)
Cooling operation
Cooling operation
Fan operation
TB3
26D
Thermostat (ambient temp.)
Power (Neutral)
24VAC(N)
- 58 -
PE-20MYC-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
OUTDOOR UNIT
Power supply, 3 Phase
TB1
L1
380~415 Volt, 50Hertz
52C1
52C2
51C1
51C2
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC1
MC2
WHITE
BLACK
N
RED
RED
BLUE
PE
WHITE
BLACK
WHITE
BLACK
CIRCUIT BREAKER
(FIELD SUPPLY)
PU-20MYC1-EU ··· 125A
51F2
C1
52F2
TB5
TB5
F3(3.15A)
1
2
3
RED
L1-1
L2-1
L3-1
L1-2
L2-2
L3-2
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
MF2
49C1
49C2
52
52
51F3
C1 C2
52F3
51
F2
51
F3
52
52
C1 C2
52F4
63H1
51C1
63H2
51C2
Tr2
26D3
26D1
FZ
4
FZ
2
FZ
2
FZ
3
FZ
5
FZ FZ FZ
5
6
7
CH1 CH2
TB4
51F4
C2
52F5
TB6
TB6
2
1
2
3
RED
L1-1
L2-1
L3-1
L1-2
L2-2
L3-2
RED
RED
26D2
H
H
26D4
11 12
GRAY
RED
WHITE
BLACK
30
CZ1
30
CZ2
WHITE
BLACK
WHITE
BLACK
CR3
CZ2-1
52
CR2
CZ2-2
52
52
F2
52
F4
52
F5
52
F7
MF3
FZ2
FZ5
WHITE
BLACK
CZ
2-1
2
51F5
C1
C2
52
F3
52
F6
52F6
H
H
CZ
2-2
30
CZ1
30
CZ2
FZ3
FZ6
FZ
3
FZ
6
52F7
Tr3
FZ4
FZ7
13
INDOOR UNIT
Power supply, 3 Phase
380~415 Volt, 50Hertz
TB2
L1
51F1
52F1
RED
L2
L3
WHITE
BLACK
MF1
N
BLUE
F1
52F1
(3.15A)
1
GRAY
PE
TB3
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
C3
1
PE-20MYC-EU ··· 30A
CZ CZ
1-1 1-2
SWITCH BOX (FIELD SUPPLY)
26L1
F2
C3
3
(3.15A)
TB3
Tr1
AC
C8
1
OUTDOOR
11 12
11 12
26L2
AC
220~
240V
C8
3
24V
SW1
23
23
FZ1
WA
WA
CZ
2-1
CZ
2-2
30
FZ
CR1
3
4
2
52
TB3
F1
30
FZ
CZ
1-1
CZ
1-2
13
FZ1
GRAY
5
13
Symbol
MC1,2
MF1
MF2,3
52C1,2
52F1
52F2~7
TB1~6
CH1,2
F1~3
Name
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
Caution,
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays <51C1,2>,<51F1~5> are installed. Therefore,
do not change factory set value of Over current relays.
2.To protect the starting Compressor <MC1,2>at the same time,Timer
<2> is installed. Therefore, do not change factory set value of this Timer.
Tr1~3
49C1,2
51C1,2
51F1
51F2~F5
63H1,2
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
26L1,2
FZ1
Thermostat (freeze protection)
Auxiliary relay (fanI/D)
30FZ
Auxiliary relay (fanI/D)
CZ1-1,2/2-1,2 Auxiliary relay
Option controller connection.
30CZ1,2
<SW1>
<23WA>
C1~3, 8
CR1~3
2
Auxiliary relay (check)
Switch (on)
Thermostat (room temp.)
Connector
Surge killer
PAC-204RC (Option)
Symbol No. Function
terminal no.
24VAC(L)
COMP1
COMP2
FAN HI
1
2
3
4
5
Power (Active)
Cooling operation
Cooling operation
Fan operation
Timer
TB3
26D1~4
FZ2~7
Thermostat (ambient temp.)
Auxiliary relay (fan O/D)
Power (Neutral)
24VAC(N)
- 59 -
PEH-5MYA-EU (STANDARD)
Power Supply, 3Phase
TB1
MC
50Hertz
52C
INTERNAL
380~415Volt,
51C
RED
RED
L1
L2
L3
PROTECTOR
RED
WHITE
BLACK
WHITE
BLACK
51F2
C4
X1
1
RED
RED
N
BLUE
2
3
WHITE
BLACK
WHITE
BLACK
F3(3.15A)
MF2
PE
CIRCUIT BREAKER
(FIELD SUPPLY)
HZ2
PUH-5MYE-EU···50A
T1
X3 X1 X2
X1
52C
51F2
C7
3
26
TB4
15
13
D2
63H
GRAY
C7
1
51C
CZ2
21
S4
T1
CZ2 HZ2
C6
1
26
X3
CH
X2
D1
30
CZ
CR2
C6
3
14
52C
30
CZ
X1
X2
Power Supply, 3Phase
50Hertz
TB2
380~415Volt,
51F1
C2
52F
C1
WHITE
BLUE
RED
1
2
3
1
L1
L2
L3
RED
RED
X
Y
Z
U
2
WHITE
BLACK
WHITE
V
MF1
3
W
BLUE
F1
(3.15A)
RED
F1
N
TB3
52F
PE
GRAY
1
51F1
SWITCH BOX
(FIELD SUPPLY)
CIRCUIT BREAKER
(FIELD SUPPLY)
CZ1 HZ1
C1
4
PEH-5MYA-EU···15A
TB3 15
13
F2
(3.15A)
SW1
15
13
COOL
C
HEAT
49F
OUTDOOR
H
SW2
Tr
C1
5
CZ2 HZ2
23
WA
FZ
AC
AC
220~
24V
CR1
240V
3
2
4
TB3
30FZ
14
14
52F
HZ1
CZ1
30
FZ
FZ
GRAY
5
BLUE
Attach the accessory
Symbol
Name
MC
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Transformer
Remove
C2
C1
1
2
3
2
3
1
MF1
MF2
52C
52F
TB1~4
CH
2
3
1
MF1
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
F1~3
Tr
49F
Internal thermostat(indoor fan)
Over current relay(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Note:1.The dotted lines show field wiring.
51C
51F1,2
63H
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Specification subject to change without notice.
26D1,2 Thermostat (defrost)
Caution,
21S4
FZ
4-Way valve
Auxiliary relay (fan)
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C>,<51F1,2>are installed. Therefore,
do not change factory set value of Over current relays.
CZ1,2
HZ1,2
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Option controller connection.
30CZ,FZ Auxiliary relay (check)
X1
X2,3
<SW1>
<SW2>
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
2
3
Power (Active)
24VAC(L)
COMP1
4WV
Cooling operation
Revercing Valve
for Heating operation
Fan operation
<23WA> Thermostat (room temp.)
C1,2,4,6,7 Connector
T1
TB3
4
5
FAN HI
24VAC(N)
Timer (defrost)
Surge killer
Power (Neutral)
CR1,2
- 60 -
PEH-7MYA-EU (STANDARD)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
C4
X1
1
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
PUH-7MYC1-EU
BLUE
N
2
3
1
2
3
WHITE
BLACK
RED
WHITE
BLACK
F3(3.15A)
MF2
MF3
PE
WHITE
BLACK
HZ2
49C
C5
T1
X3 X1 X2
X1
52C
51F2
C7
3
26
TB5
15
13
D2
63H
GRAY
C7
1
51C
CZ2
21
T1
S4
HZ2
CZ2
C6
1
26
X3
CH
X2
D1
30
CZ
CR2
C6
3
14
52C
30
CZ
X1
X2
JUMPER
Power supply,
220 240Volt,
Single Phase
50Hertz
TB4
C1
TB2
L
TB4
6
RED
1
2
51F1
52F
C1
RED
5
6
Hi
7
8
BROWN
C
MF1
Low
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
PEH-7MYA-EU
N
SW3(FIELD SUPPLY)
BLUE
BLUE
4
TB4
52F
F1
(3.15A)
GRAY
1
RED
SWITCH BOX
(FIELD SUPPLY)
CZ1 HZ1
PE
51F1
TB3 15
13
F2
(3.15A)
SW1
15
13
COOL
HEAT
OUTDOOR
C3
1
H
C
HZ1
26L
SW2
Tr
23
C3
3
WA
FZ
HZ2
CZ2
AC
220
240V
24V
3
2
4
TB4
30FZ
CR1
CZ1 HZ1
14
14
52F
30
FZ
FZ
GRAY
5
BLUE
Note:1.The dotted lines show field wiring.
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Please remove the jumper wire ( Mark) in the above
diagram if you use the Switch <SW3> at local.
If the Switch <SW3> is not used, the Fan motor
(indoor) drives at high speed.
TB1
5
Crankcase heater
Fuse (3.15A)
6.Specification subject to change without notice.
F1
3
Transformer
Internal thermostat
Over current relay
Over current relay(fanI/D,O/D)
High-pressure switch
Caution,
(compressor)
(compressor)
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
26L
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
CZ1, 2
HZ1, 2
30CZ, FZ
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP
2
TB3
Reversing valve
for Heating operation
4WV
3
4
5
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
3
Switch (Fan Hi-Low)
Thermostat (room temp.)
Run capacitor
C
C1, C3
7
Connector
T1
Timer (defrost)
CR1, 2
Surge killer
- 61 -
PEH-8,10MYA-EU (STANDARD)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
C4
X1
1
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY)
BLUE
N
2
3
1
2
3
WHITE
BLACK
RED
WHITE
BLACK
F3(3.15A)
MF2
PE
WHITE
BLACK
PUH-8, 10MYC1-EU ··· 100A
PUH-8,10MYE-EU ···100A
HZ2
MF3
49C
C5
MF3 is only PUH-8,10MYC1-EU.
T1
X3 X1 X2
X1
52C
51F2
C7
3
26
TB4 (In case of PUH-8,10MYE-EU)
TB5 (In case of PUH-8,10MYC1-EU)
15
13
D2
63H
GRAY
C7
1
51C
CZ2
21
S4
T1
HZ2
CZ2
C6
1
26
X3
CH
X2
D1
30
CZ
CR2
C6
3
14
52C
30
CZ
X1
X2
Power supply,
380 415Volt,
3Phase
50Hertz
TB2
L1
51F1
52F
C1
C2
1
RED
RED
1
2
3
RED
2
3
WHITE
BLUE
WHITE
BLUE
WHITE
BLACK
L2
L3
MF1
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
F1(3.15A)
RED
PEH-8,10MYA-EU
N
TB4
1
52F
GRAY
F2
51F1
SWITCH BOX
(FIELD SUPPLY)
C1
4
PE
CZ1 HZ1
TB3 15
13
49F
C1
5
SW1
(3.15A)
15
13
HEAT
COOL
C
OUTDOOR
C3
1
H
HZ1
FZ
26L
Tr
SW2
CZ2
HZ2
C3
3
23
WA
AC
AC
220
240V
24V
CR1
3
2
4
30FZ
TB4
14
14
52F
CZ1 HZ1
30
FZ
FZ
GRAY
5
BLUE
Attach the accessory
Remove
C1
C2
1
2
3
1
2
3
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
1
2
3
MF1
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse (3.15A)
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
TB1
F1
5
Note:1.The dotted lines show field wiring.
3
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Transformer
(indoor fan)
(compressor)
(compressor)
Internal thermostat
Internal thermostat
Over current relay
49F
5.Specification subject to change without notice.
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
Caution,
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
26L
Auxiliary relay (fan)
CZ1, 2
HZ1, 2
30CZ, FZ
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP
2
TB4
Reversing valve
for Heating operation
4WV
3
Thermostat (room temp.)
Connector (C5 is PUH-8,10MYC1-EU only.)
Timer (defrost)
4
5
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
C1~7
T1
CR1, 2
Surge killer
- 62 -
PEH-15,20MYA-EU (STANDARD)
L1
L2
L3
Power supply, 3 Phase
380~415 Volt, 50Hertz
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
N
BLUE
RED
RED
PE
WHITE
BLACK
WHITE
BLACK
CIRCUIT BREAKER
(FIELD SUPPLY)
RED
RED
PUH-15MYC1-EU---100A
PUH-20MYC1-EU---125A
WHITE
BLACK
WHITE
BLACK
HZ2
(3.15A)
F3
RED
RED
WHITE
BLACK
WHITE
BLACK
T2
3
T1
3
49C1
49C2
X1 X2 X5
C6
X3
X2 X6
C7
X4
26
D3
26
D4
GRAY
63H1
51C1
63H2
51C2
C6
C4
C7
C5
1
1
1
1
CH1 CH2
26
D2
26
D1
X3
X4
2
30
CZ1
30
CZ2
C4
3
3
C5
CZ2-1
CR3
CR2
CZ2-2
S4-2
S4-1
L1
L2
L3
RED
Power supply, 3 Phase
380~415 Volt, 50Hertz
WHITE
BLACK
BLUE
N
F1
(3.15A)
GRAY
PE
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
PEH-15,20MYA-EU---30A
C3
1
CZ CZ
1-1 1-2
HZ1
26L1
F2
(3.15A)
C3
3
C8
1
HZ1
COOL
C
HEAT
AC
26L2
AC
220
C8
3
24V
240V
H
C
H
30
FZ
CR1
1-1
1-2
GRAY
Note:1.The dotted lines show field wiring.
Symbol
MC1,2
MF1
MF2,3
52C1,2
52F
Name
Compressor motor
Fan motor (indoor)
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Fan motor (outdoor)
5.Specification subject to change without notice.
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Caution,
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C1,2>,<51F1,2,3> are installed. Therefore,
do not change factory set value of Over current relays.
TB1
4
CH1,2
F1
Tr
3
Transformer
49C1,2
51C1,2
51F1
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
Auxiliary relay (fan)
Auxiliary relay (fan)
Option controller connection.
PAC-204RC (Option)
51F2,3
63H1,2
26L1,2
26D1
Symbol No. Function
terminal no.
1
2
Power (Active)
24VAC(L)
COMP1
Cooling or Heating
4
operation
21S4-1,2
FZ
30FZ
Cooling or Heating
operation
COMP2
4WV
3
4
TB3
Reversing valve
for Heating operation
CZ1-1,2/2-1,2 Auxiliary relay
5
6
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
HZ1,2
30CZ1,2
X1,2
Auxiliary relay (heater)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Thermostat (room temp.)
Connector
X3
6
<SW1>
<SW2>
<23WA>
C1~8
T1,2
Timer (defrost)
2
CR1
Timer
Surge killer
3
- 63 -
PEH-5MYA-EU
SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,
(
PROTECT FOR COOL AIR BLOW.
)
Power Supply, 3Phase
TB1
L1
MC
50Hertz
52C
51C
INTERNAL
380~415Volt,
RED
RED
PROTECTOR
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
51F2
C4
X1
1
RED
RED
N
BLUE
2
3
WHITE
BLACK
WHITE
BLACK
F3(3.15A)
MF2
PE
CIRCUIT BREAKER
(FIELD SUPPLY)
HZ2
PUH-5MYE-EU···-50A
T1
X3 X1 X2
X1
52C
51F2
C7
3
26
TB4
15
13
16
D2
63H
GRAY
C7
1
X3
17
51C
CZ2
21
S4
T1
HZ2
CZ2
C6
1
26
X3
CH
X2
D1
30
CZ
CR2
C6
3
14
52C
30
CZ
X1
X2
Power Supply, 3Phase
50Hertz
TB2
380~415Volt,
51F1
C2
52F
C1
WHITE
BLUE
RED
1
2
3
1
L1
L2
L3
RED
RED
X
Y
Z
U
V
W
2
3
WHITE
BLACK
WHITE
BLUE
MF1
F1
(3.15A)
RED
N
TB3
52F
PE
GRAY
1
51F1
SWITCH BOX
(FIELD SUPPLY)
CIRCUIT BREAKER
(FIELD SUPPLY)
PEH-5MYA-EU···U15A
CZ1 HZ1
C1
4
OUT
DOOR
16
F2
TM
SW1
HEAT
(3.15A)
16
(3MIN)
49F
COOL
TB3 15
15
13
13
X3
17
17
C
H
Tr
SW2
C1
5
23
OUTDOOR
FZ
WA
TM
AC
24V
AC
220~
CZ2
HZ2
CR1
3
2
4
240V
TB3
30FZ
14
14
52F
CZ1
HZ1
30
FZ
FZ
GRAY
5
BLUE
Attach the accessory
Symbol
MC
Symbol
21S4
FZ
Name
Name
4-Way valve
Auxiliary relay (fan)
C2
Remove
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
C1
1
2
3
2
3
1
MF1
MF2
52C
52F
2
3
1
CZ1,2
HZ1,2
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
MF1
Contactor (compressor)
Contactor (fan I/D)
30CZ,FZ Auxiliary relay (check)
TB1~4 Terminal block
X1
Contactor (fan O/D)
CH
Crankcase heater
Fuse (3.15A)
Transformer
X2,3
Auxiliary relay (defrost)
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
F1~3
Tr
<SW1> Switch (operation mode)
<SW2> Switch (on)
49F
51C
Internal thermostat(indoor fan) <23WA> Thermostat (room temp.)
Over current relay(compressor) C1~4,6,7 Connector
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.When PAC-204RC is used, Timer(TM)is unneccessary.
6.Specification subject to change without notice.
51F1,2 Over current relay(fanI/D,O/D) T1
Timer (defrost)
63H
High-pressure switch
CR1,2
TM
Surge killer
26D1,2 Thermostat (defrost)
Timer (Anti short cycle)
Option controller connection.
Symbol No. Function
Caution,
PAC-204RC (Option)
terminal no.
24VAC(L)
COMP1
4WV
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C>,<51F1,2>are installed. Therefore,
do not change factory set value of Over current relays.
1
2
3
Power (Active)
Cooling operation
Revercing Valve
for Heating operation
Fan operation
TB3
4
5
FAN HI
24VAC(N)
Power (Neutral)
- 64 -
PEH-7MYA-EU
SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,
(
PROTECT FOR COOL AIR BLOW.
)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
X1
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
C4
C5
F3(3.15A)
1
2
3
1
2
3
RED
RED
PUH-7MYC1-EU
N
BLUE
WHITE
BLACK
RED
WHITE
BLACK
MF2
MF3
HZ2
PE
49C
WHITE
BLACK
TB5
T1
15
13
X3 X1 X2
X1
16
52C
GRAY
51F2
63H
X3
17
C7
3
26
D2
CZ2 HZ2
C7
1
51C
CZ2
21
T1
S4
C6
1
14
X3
26
D1
CH
X2
30
CZ
CR2
C6
3
52C
30
CZ
X2
X1
JUMPER
Power supply, Single Phase
50Hertz
TB4
C1
TB2
L
TB4
6
1
2
RED
51F1
220 240Volt,
52F
C1
RED
5
6
Hi
7
8
BROWN
BLUE
C
MF1
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
Low
PEH-7MYA-EU
SW3(FIELD SUPPLY)
4
N
BLUE
F1
TB4
52F
(3.15A)
GRAY
1
RED
SWITCH BOX
CZ1 HZ1
(FIELD SUPPLY)
51F1
PE
F2
(3.15A)
TM
SW1
HEAT
(3MIN)
TB3
13
15
COOL
C3
1
OUT
DOOR
26L
15
13
16
HZ1
C
H
SW2
OUTDOOR
C3
3
Tr
23
16
X3
17
17
WA
FZ
AC
220
240V
CZ2
HZ2
AC
24V
3
2
4
TB4
30FZ
TM
CR1
CZ1 HZ1
14
14
52F
30
FZ
FZ
GRAY
5
BLUE
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.Please remove the jumper wire ( Mark) in the above
diagram if you use the Switch <SW3> at local.
If the Switch <SW3> is not used, the Fan motor
(indoor) drives at high speed.
TB1
F1
5
Crankcase heater
Fuse (3.15A)
3
6.When PAC-204RC is used, Timer(TM)is unneccessary.
7.Specification subject to change without notice.
Transformer
Internal thermostat
Over current relay
(compressor)
(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
Caution,
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
26L
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
CZ1, 2
HZ1, 2
30CZ, FZ
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP
2
TB4
Reversing valve
for Heating operation
4WV
3
Switch (Fan Hi-Low)
Thermostat (room temp.)
Run capacitor
3
4
5
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
C
C1, 3~7
Connector
T1
Timer (defrost)
CR1, 2
TM
Surge killer
Timer (Anti short cycle)
- 65 -
PEH-8,10MYA-EU
SPECIAL WIRING : ANTI SHORT CYCLE TIMER.,
(
PROTECT FOR COOL AIR BLOW.
)
Power supply,
380 415Volt,
3Phase
50Hertz
TB1
L1
52C
51C
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
51F2
C4
X1
1
RED
RED
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
PUH-8, 10MYE-EU
PUH-8, 10MYC1-EU
BLUE
N
2
3
1
2
3
WHITE
BLACK
RED
WHITE
BLACK
F3(3.15A)
MF2
PE
WHITE
BLACK
HZ2
MF3
49C
C5
MF3 is only PUH-8,10MYC1-EU.
T1
X3 X1 X2
X1
52C
51F2
C7
3
26
TB4 (In case of PUH-8,10MYE-EU)
TB5 (In case of PUH-8,10MYC1-EU)
16
X3
17
15
13
D2
63H
GRAY
C7
1
51C
CZ2
21
T1
S4
HZ2
CZ2
C6
1
26
X3
CH
X2
D1
30
CZ
CR2
C6
3
14
52C
30
CZ
X1
X2
Power supply,
380 415Volt,
3Phase
50Hertz
TB2
L1
51F
52F
C1
C2
1
RED
RED
1
2
3
RED
2
3
WHITE
BLUE
WHITE
BLUE
L2
L3
WHITE
BLACK
MF1
1
F3(3.15A)
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
PEH-8, 10MYA-EU
RED
N
BLUE
TB4
51F1
52F
GRAY
C1
4
SWITCH BOX
CZ1 HZ1
TM
(FIELD SUPPLY)
PE
49F
OUT
DOOR
F2
C1
5
16
SW1
(3.15A)
(3MIN)
COOL
C
HEAT
16
X3
17
17
TB3
13
13
15
C3
1
OUTDOOR
15
H
HZ1
FZ
26L
Tr
SW2
C3
3
23
WA
CZ2 HZ2
AC
24V
AC
220
TM
CR1 240V
3
2
4
30FZ
TB4
14
14
52F
CZ1 HZ1
30
FZ
FZ
GRAY
5
BLUE
Attach the accessory
Remove
C1
C2
1
2
3
1
2
3
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
1
2
3
MF1
Contactor (compressor)
Contactor (fan I/D)
Terminal block
This circuit diagram shows connections.
(If the external static Pressure is less
than 30 Pa, change to connections.)
TB1
5
Crankcase heater
Fuse (3.15A)
Transformer
Note:1.The dotted lines show field wiring.
F1
3
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
(indoor fan)
(compressor)
(compressor)
Internal thermostat
Internal thermostat
Over current relay
Over current relay(fanI/D,O/D)
High-pressure switch
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
49F
5.When PAC-204RC is used, Timer(TM)is unneccessary.
6.Specification subject to change without notice.
Caution,
26L
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
Auxiliary relay (fan)
CZ1, 2
HZ1, 2
30CZ, FZ
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Auxiliary relay (check)
Contactor (fan O/D)
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
Power (Active)
24VAC(L)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Thermostat (room temp.)
Connector (C5 is PUH-8,10MYC-EU only.)
Timer (defrost)
Cooling or Heating
COMP
2
operation
TB4
Reversing valve
for Heating operation
Fan operation
Power (Neutral)
4WV
3
4
5
FAN HI
24VAC(N)
C1~7
- 66 -
CR1, 2
Surge killer
Timer (Anti short cycle)
PEH-15,20MYA-EU
(SPECIAL WIRING : ANTI SHORT CYCLE TIMER)
OUTDOOR UNIT
Power supply, 3 Phase
380~415 Volt, 50Hertz
TB1
52C1
51C1
RED
RED
L1
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC1
MF2
WHITE
BLACK
51F2
C1
N
X1
1
2
3
RED
RED
BLUE
WHITE
BLACK
WHITE
BLACK
PE
CIRCUIT BREAKER
(FIELD SUPPLY)
PUH-15MYC1-EU ··· 100A
PUH-20MYC1-EU ··· 125A
52C2
51C2
RED
RED
WHITE
BLACK
WHITE
BLACK
MC2
MF3
51F3
C2
X2
(3.15A)
HZ2
1
2
3
RED
F3
RED
WHITE
BLACK
WHITE
BLACK
T1
3
T2
3
CZ2-1
49C1
49C2
CZ2-2
X1 X2 X5
C6
X3
X2 X6
C7
X4
51
F2
51
F3
TM
(3min)
52
52
C1 C2
TM
(3min)
26
D3
26
D4
52
TB4
11 12 13
C2
63H1
51C1
63H2
51C2
52
C1
52
C1
52
C2
C6
C4
1
C7
C5
1
GRAY
1
1
CH1 CH2
26
D1
26
D2
CZ
2-1
X3
X4
2
HZ2
CZ
2-2
30
CZ1
30
CZ2
C4
T1
3
3
C5
CR2
CR3
CZ2-1
CZ2-2
52
TM
21
S4-2
52
C1
2
X3
X2
X6
C2
30
CZ1
30
CZ2
21
S4-1
X1
X5
T2
X4
14
TB2
INDOOR UNIT
Power supply, 3 Phase
380~415 Volt, 50Hertz
51F1
52F
L1
L2
L3
RED
WHITE
BLACK
MF1
N
BLUE
F1
52F
(3.15A)
1
GRAY
PE
TB3
F2
(3.15A)
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
CZ
1-1
CZ
1-2
HZ1
Tr
PEH-15,20MYA-EU ··· 30A
C3
1
AC
SWITCH BOX (FIELD SUPPLY)
SW1
AC
220~
240V
26L1
24V
C3
3
OUT
DOOR
TB3
HZ1
11
12
13
C8
1
COOL HEAT
OUTDOOR
26L2
11
12
13
C
H
C
H
C8
3
SW2
CZ
2-1
FZ
23
WA
HZ2
CZ
2-2
30
FZ
3
2
4
5
TB3
CR1
30
FZ
CZ
1-1
CZ
1-2
14
HZ1
FZ
52F
GRAY
6
14
Symbol
MC1,2
MF1
Name
Compressor motor
Fan motor (indoor)
MF2,3
52C1,2
52F
TB1~4
CH1,2
F1~3
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Crankcase heater
Fuse (3.15A)
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
5.When PAC-204RC is used, Timer(TM)is unneccessary.
6.Specification subject to change without notice.
Tr
Transformer
Internal thermostat(compressor)
49C1,2
51C1,2
51F1
51F2,3
63H1,2
26L1,2
26D1~4
21S4-1,2
FZ
Over current relay(compressor)
Over current relay(fanI/D)
Over current relay(fanO/D)
High-pressure switch
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
Auxiliary relay (fan)
Auxiliary relay (fan)
Caution,
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C1,2>,<51F1,2,3>are installed. Therefore,
do not change factory set value of Over current relays.
2.To protect the starting Compressor <MC1,2>at the same time, Timer
<2> is installed. Therefore, do not change factory set value of this Timer.
3.To protect the starting Compressor<52C1,2> frequently, Timer
<TM> is installed. Therefore, do not change factory set value of this Timer.
30FZ
CZ1-1,2/2-1,2 Auxiliary relay
HZ1,2
30CZ1,2
X1,2
X3~6
<SW1>
<SW2>
<23WA>
C1~8
T1,2
Auxiliary relay (heater)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Thermostat (room temp.)
Connector
Timer (defrost)
Option controller connection.
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP1
2
Cooling or Heating
operation
Reversing valve
for Heating operation
COMP2
4WV
3
4
TB3
2
Timer
Surge killer
Timer (Anti short cycle)
5
6
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
CR1~3
TM
- 67 -
PEH-7MYA-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
Power supply,
3Phase
TB1
L1
52C
51C
380 415Volt,50Hertz
RED
RED
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC
52F3
X1
51F2
C4
C8
2
F3(3.15A)
WHITE
CIRCUIT BREAKER
(FIELD SUPPLY) 100A
1
2
3
RED
RED
PUH-7MYC1-EU
N
BLUE
WHITE
BLACK
BLACK
RED
3
1
WHITE
BLACK
MF2
HZ2
49C
HZ2
PE
52F2
TB5
15
13
51F2
T1
1
X3 X1 X2
X1
23C
5
52C
GRAY
C4
4
3
C7
52F4
49F
3
1
RED
H
CZ2 HZ2
26
D2
C4
5
2
3
WHITE
BLACK
MF3
63H
C7
1
52
F3
52
F2
C5
21
S4
T1
51C
CZ2
C6
1
14
52F3
52F2
52F4
CR2
X3
26
D1
CH
X2
30
CZ
C6
3
52C
30
CZ
X1
X2
JUMPER
Power Supply, Single Phase
220 240Volt,50Hertz
TB4
C1
TB2
L
TB4
6
1
2
RED
51F1
52F1
C1
RED
5
6
Hi
7
8
BROWN
C
MF1
CIRCUIT BREAKER
(FIELD SUPPLY) 15A
Low
PEH-7MYA-EU
4
N
SW3(FIELD SUPPLY)
BLUE
F1
BLUE
TB4
52F1
(3.15A)
GRAY
1
RED
SWITCH BOX
CZ1 HZ1
(FIELD SUPPLY)
PE
51F1
TB3 15
13
F2
(3.15A)
SW1
15
13
COOL
C
HEAT
C3
1
OUTDOOR
26L
H
HZ1
SW2
C3
3
Tr
23
WA
FZ
CZ2
HZ2
AC
AC
24V
220
3
2
4
240V
TB4
30FZ
CR1
CZ1 HZ1
14
14
52F1
30
FZ
FZ
GRAY
5
BLUE
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
MC
MF1
FZ
CZ1, 2
HZ1, 2
30CZ, FZ
X1
Compressor motor
Fan motor (indoor)
Auxiliary relay (fan)
3.Color of earth wire is yellow and green twisting.
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Switch (Fan Hi-Low)
Thermostat (room temp.)
Run capacitor
Connector
Timer (defrost)
Surge killer
4-Way valve
Thermostat (defrost)
Thermostat (freeze protection)
4.Not specified color of wire is brown.
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Contactor (fan O/D)
Ambient temperature
Terminal block
Crankcase heater
Fuse (3.15A)
MF2, 3
52C
52F1
52F2, 3
52F4
23C
TB1
CH
F1
5.Please remove the jumper wire ( Mark) in the above
diagram if you use the Switch <SW3> at local.
If the Switch <SW3> is not used, the Fan motor
(indoor) drives at high speed.
X2, 3
6.Specification subject to change without notice.
<SW1>
<SW2>
<SW3>
<23WA>
C
C1, 3
T1
CR1, 2
21S4
Caution,
5
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
3
Tr
8
Transformer
(compressor)
(fan O/D)
(compressor)
49C
49F
51C
51F1,2
63H
Internal thermostat
Internal thermostat
Over current relay
Option controller connection.
Over current relay(fanI/D,O/D) 26D1, 2
PAC-204RC (Option)
High-pressure switch
26L
Symbol No. Function
terminal no.
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP
2
TB4
Reversing valve
for Heating operation
4WV
3
4
5
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
- 68 -
PEH-8,10MYA-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
Power Supply, 3Phase
TB1
380 415Volt, 50Hertz
52C
51C
RED
RED
L1
L2
L3
RED
WHITE
BLACK
WHITE
BLACK
MC
52F3
51F2
X1
C8
CIRCUIT BREAKER
(FIELD SUPPLY)100A
C4
WHITE
1
2
3
RED
2
3
1
RED
PUH-8,10MYC1-EU
N
BLUE
WHITE
BLACK
WHITE
BLACK
BLACK
RED
F3(3.15A)
PUH-8,10MYE-EU
MF2
HZ2
52F2
PE
49C
HZ2
51F2
T1
C7
1
X3 X1 X2
X1
23C
5
52C
52F4
C5
1
RED
C4
4
3
MF3 is only PUH-8,10MYC1-EU.
MF3
2
3
WHITE
BLACK
3
49F2
H
26
D2
C4
5
TB4 (In case of PUH-8,10MYE-EU)
TB5 (In case of PUH-8,10MYC1-EU)
C7
1
63H
15
13
52
F3
52
F2
GRAY
21
S4
T1
51C
CZ2
C6
1
26
D1
52F3
52F2
52F4
X3
CZ2 HZ2
CH
X2
30
CZ
C6
CR2
3
52C
30
CZ
X2
X1
14
Power Supply, 3Phase
380 415Volt, 50Hertz
TB2
L1
51F
52F1
C1
C2
1
RED
RED
1
2
3
RED
2
3
WHITE
BLUE
WHITE
BLUE
WHITE
BLACK
L2
L3
MF1
CIRCUIT BREAKER
(FIELD SUPPLY)15A
F1(3.15A)
RED
PEH-8,10MYA-EU
N
TB4
1
52F1
51F1
GRAY
F2
C1
4
SWITCH BOX
PE
CZ1 HZ1
(FIELD SUPPLY)
49F1
TB3 15
13
C1
5
SW1
HEAT
(3.15A)
15
13
COOL
C
C3
1
OUTDOOR
H
26L
HZ1
FZ
Tr
SW2
CZ2 HZ2
C3
3
23
WA
AC
AC
220
240V
24V
CR1
3
2
4
30FZ
TB4
14
14
52F1
CZ1
HZ1
30
FZ
FZ
GRAY
5
BLUE
Note:1.The dotted lines show field wiring.
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
MC
MF1
FZ
CZ1, 2
HZ1, 2
30CZ, FZ
X1
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Contactor (fan O/D)
Contactor (fan O/D)
Ambient temperature
Terminal block
Crankcase heater
Fuse (3.15A)
Auxiliary relay (fan)
Auxiliary relay (compressor)
Auxiliary relay (4-way valve)
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Switch (Fan Hi-Low)
Thermostat (room temp.)
High-pressure switch
Connector (C5 is PUH-8,10MYC1-EU only.)
Timer (defrost)
MF2, 3
52C
52F1
52F2, 3
52F4
23C
TB1
CH
F1
Tr
49C
49F1
49F2
51C
5.Specification subject to change without notice.
Caution,
X2, 3
1.To protect each Fan motor and Compressor from abnormal
current, Over current relays <51C>, <51F1,2> are installed.
Therefore, do not change factory set value of Over current
relays.
<SW1>
<SW2>
<SW3>
<23WA>
63H
C1~8
T1
CR1, 2
21S4
26D1, 2
26L
5
3
Transformer
Option controller connection.
(compressor)
(fan I/D)
(fan O/D)
Internal thermostat
Internal thermostat
Internal thermostat
Over current relay
PAC-204RC (Option)
Surge killer
4-Way valve
Thermostat (defrost)
Thermostat (freeze protection)
Symbol No. Function
terminal no.
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP
(compressor)
2
Over current relay(fanI/D,O/D)
51F1,2
TB4
Reversing valve
for Heating operation
4WV
3
4
5
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
- 69 -
PEH-15,20MYA-EU
(SPECIAL ORDER : LOW AMBIENT COOLING)
OUTDOOR UNIT
TB1
L1
52C1
51C1
RED
RED
Power supply,
3 Phase
380~415 Volt,
50Hertz
RED
WHITE
BLACK
WHITE
BLACK
L2
L3
MC1
WHITE
BLACK
51F2
C1
RED
52F2
TB5
TB5
N
1
2
3
RED
L1-1
L2-1
L3-1
L1-2
L2-2
L3-2
RED
BLUE
RED
WHITE
BLACK
WHITE
BLACK
PE
WHITE
BLACK
MF2
WHITE
CIRCUIT BREAKER
(FIELD SUPPLY)
51F3
BLACK
52C2
51C2
52F3
RED
RED
PUH-15MYC1-EU ··· 100A
PUH-20MYC1-EU ··· 125A
WHITE
BLACK
WHITE
BLACK
MC2
52F4
Tr2
F3
(3.15A)
HZ2
51F4
C2
RED
52F5
T1
3
T2
TB6
TB6
1
2
3
RED
L1-1
L2-1
L3-1
L1-2
L2-2
L3-2
X1 X2 X5
X3
X2 X6
X4
RED
RED
49C1
49C2
WHITE
BLACK
WHITE
BLACK
WHITE
BLACK
MF3
WHITE
BLACK
C6
C7
3
52
52
51F5
51
F2
51
F3
26
D3
26
D4
C1 C2
52F6
FZ
4
26D5
26D7
C6
C4
1
C7
C5
1
FZ
2
FZ
7
FZ
2
FZ
3
FZ
5
FZ
5
FZ
6
63H1
51C1
63H2
51C2
1
1
52F7
Tr3
CH1 CH2
TB4
11 12 13
26
D1
26
D2
H
H
26D8
26D6
52
F2
X3
X4
52
F4
52
F5
52
F7
GRAY
FZ2
FZ5
C4
3
3
C5
2
52
52
F6
H
30
CZ1
30
CZ2
H
CZ
2-1
CR3
21
S4-2
CR2
CZ2-1
F3
CZ2-2
52
HZ2
T1
X3
X2
X6
FZ3
FZ6
CZ
2-2
FZ
3
FZ
6
52
C1
21
S4-1
2
C2
X1
X5
T2
X4
30
CZ1
30
CZ2
FZ4
FZ7
14
TB2
L1
INDOOR UNIT
Power supply,
3 Phase
380~415 Volt,
50Hertz
51F1
52F1
RED
L2
L3
WHITE
BLACK
MF1
N
BLUE
F1
52F
(3.15A)
1
GRAY
PE
TB3
CIRCUIT BREAKER
(FIELD SUPPLY)
51F1
CZ CZ
1-1 1-2
HZ1
PEH-15,20MYA-EU ··· 30A
C3
1
SWITCH BOX (FIELD SUPPLY)
SW1
F2
26L1
(3.15A)
TB3
Tr1
C3
3
11 12 13
11 12 13
COOL HEAT
C8
1
AC
HZ1
FZ1
OUTDOOR
AC
220~
240V
26L2
24V
C
H
C
H
SW2
C8
3
CZ
2-1
23
WA
HZ2
CZ
2-2
30
FZ
CR1
3
2
4
5
TB3
52
F1
CZ
1-1
CZ
1-2
14
FZ1
HZ1
30
FZ
GRAY
6
14
Symbol
MC1,2
MF1
MF2,3
52C1,2
52F1
TB1~6
CH1,2
F1~3
Name
Compressor motor
Fan motor (indoor)
Fan motor (outdoor)
Contactor (compressor)
Contactor (fan I/D)
Terminal block
Note:1.The dotted lines show field wiring.
Crankcase heater
Fuse (3.15A)
2.The figure in the parentheses show field supply parts.
3.Color of earth wire is yellow and green twisting.
4.Not specified color of wire is brown.
Tr1~3
Transformer
49C1,2
51C1,2
51F1~5
63H1,2
Internal thermostat(compressor)
Over current relay(compressor)
Over current relay(fanI/D,O/D)
High-pressure switch
5.Specification subject to change without notice.
Caution,
1.To protect each Fan motor and Compressor from abnormal current,
Over current relays<51C1,2>,<51F1~5>are installed. Therefore,
do not change factory set value of Over current relays.
26L1,2
Thermostat (freeze protection)
Thermostat (defrost)
4-Way valve
26D1~4
21S4-1,2
FZ1,30FZ
Auxiliary relay (fan I/D)
2.To protect the starting Compressor <MC1,2>at the same time,Timer
CZ1-1,2/2-1,2 Auxiliary relay
HZ1,2
30CZ1,2
X1,2
Auxiliary relay (heater)
<2> is installed. Therefore, do not change factory set value of this Timer.
Auxiliary relay (check)
Contactor (fan O/D)
Auxiliary relay (defrost)
Switch (operation mode)
Switch (on)
Thermostat (room temp.)
Connector
Timer (defrost)
Timer
Surge killer
Thermostat (ambient temp.)
Contactor (fan O/D)
Auxiliary relay (fan O/D)
X3~6
Option controller connection.
<SW1>
<SW2>
<23WA>
C1~8
T1,2
2
CR1~3
26D5~8
52F2~7
FZ2~7
PAC-204RC (Option)
Symbol No. Function
terminal no.
1
Power (Active)
Cooling or Heating
operation
24VAC(L)
COMP1
2
Cooling or Heating
operation
Reversing valve
for Heating operation
COMP2
4WV
3
4
TB3
5
6
Fan operation
Power (Neutral)
FAN HI
24VAC(N)
- 70 -
ELECTRICAL OPERATION FLOW CHARTS
PE-7,8,10MYC-EU
PEH-5MYA-EU, PEH-7,8,10MYA-EU
START
POWER ON
START
POWER ON
CH ON
CH ON
30FZ,30CZ ON (SELF HOLD)
30FZ,30CZ ON (SELF HOLD)
NO
NO
SW2 ON?
SW1 ON?
YES
YES
FZ ON
FZ ON
52F ON
MF1 OPERATE
52F ON
MF1 OPERATE
NO
SW1 COOL?
HZ1,2 ON
21S4 ON
NO
23WA ON?
YES
YES
NO
CZ1,2
ON
23WA ON?
NO
23WA ON?
YES
YES
52C
MC
MF2, 3 OPERATE
ON
OPERATE
CZ1
ON
CZ1,2
ON
52C
MC
MF2, 3 OPERATE
ON
OPERATE
CH
OFF
52C
MC
ON
OPERATE
MF2, 3 OPERATE
CH
OFF
SAFETY
NO
DEVICE OFF?
CH OFF
YES
SAFETY
DEVICE OFF?
NO
30CZ OFF
NO
CONDENSING
TEMP -12
?
52C
MC
MF1
OFF
STOP
Note
YES
YES
26D1, 2 ON
30CZ OFF
MF2,3 STOP
52C
MC
MF1
OFF
STOP
Note
X1 ON
X2 ON (SELF HOLD)
MF2,3 STOP
CH
ON
21S4 OFF
MF2, 3 STOP
SERVICE CALL
CH
ON
NO
CONDENSING
TEMP
6
?
SERVICE CALL
YES
26D1, 2 OFF
Note.
1. When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.
But the unit doesn't work correctly (not cooling and heating ).
X1, 2 OFF
Then, turn off the power supply and check outdoor unit.
21S4 ON
MF2, 3 OPERATE
- 71 -
PE-15MYC-EU
PE-20MYC-EU
START
POWER ON
START
POWER ON
CH1,2 ON
CH1,2 ON
30FZ,30CZ1,2 ON (SELF HOLD)
30FZ,30CZ1,2 ON (SELF HOLD)
NO
NO
SW1 ON?
SW1 ON?
YES
YES
FZ ON
FZ ON
52F1 ON
52F1 ON
MF1 OPERATE
MF1 OPERATE
NO
NO
23WA ON?
23WA ON?
YES
YES
CZ1-1,CZ2-1 ON
CZ1-1,CZ2-1 ON
52C1 ON
52C1 ON
MC1 OPERATE
MF2 OPERATE
MC1 OPERATE
MF2 OPERATE
CH 1
OFF
CH 1
OFF
CZ1-2,CZ2-2 ON
TIMER 2 ON
CZ1-2,CZ2-2 ON
TIMER 2 ON
NO
NO
PASS THE 3 MIN?
PASS THE 3 MIN?
52C2 ON
52C2 ON
MC2 OPERATE
MC2 OPERATE
MF3 OPERATE
CH2 OFF
CH2 OFF
No.1 SAFETY
DEVICE OFF?
No.2 SAFETY
DEVICE OFF?
No.1 SAFETY
DEVICE OFF?
No.2 SAFETY
DEVICE OFF?
NO
NO
NO
NO
YES
YES
YES
YES
30CZ1 OFF
30CZ2 OFF
30CZ1 OFF
30CZ2 OFF
52C1
MC1
MF2
OFF
STOP
STOP
52C2
MC2
MF2
OFF
STOP
STOP
52C1
MC1
MF2,3 STOP
OFF
STOP
52C2
MC2
MF2,3 STOP
OFF
STOP
CH1 ON
CH2 ON
CH1 ON
CH2 ON
SERVICE CALL
SERVICE CALL
Note.
When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.
But the unit doesn't work correctly (not cooling ).
Then, turn off the power supply and check outdoor unit.
When the fault of indoor unit is occurred, both indoor unit and outdoor unit is stop.
- 72 -
PEH-15,20MYA-EU
START
POWER ON
CH1,2 ON
30FZ,30CZ1,2 ON (SELF HOLD)
NO
SW2 ON?
YES
FZ ON
52F1 ON
MF1 OPERATE
NO
HZ1,2 ON
SW1 COOL?
21S4-1,2 ON
T1,T2 ON
YES
NO
NO
23WA ON?
23WA ON?
YES
YES
CZ1-1,CZ2-1 ON
CZ1-1,CZ2-1 ON
52C1
MC1
MF2
ON
OPERATE
OPERATE
52C1
MC1
MF2
ON
OPERATE
OPERATE
CH 1
OFF
CH 1
OFF
CZ1-2,CZ2-2 ON
TIMER ON
CZ1-2,CZ2-2 ON
TIMER ON
2
2
NO
NO
PASS THE 3 MIN?
YES
PASS THE 3 MIN?
YES
NO
CONDENSING
TEMP -12
?
52C2
MC2
MF3
ON
OPERATE
OPERATE
52C2
MC2
MF3
ON
OPERATE
OPERATE
YES
ON
26D1
4
CH 2
OFF
CH 2
OFF
X1,2,5,6 ON
X3,4
ON (SELF HOLD)
21S4-1,2 OFF
MF2, 3 STOP
No.1 SAFETY
DEVICE OFF?
No.2 SAFETY
DEVICE OFF?
No.1 SAFETY
DEVICE OFF?
No.2 SAFETY
DEVICE OFF?
NO
NO
NO
NO
NO
YES
YES
YES
YES
CONDENSING
TEMP
6
?
30CZ1 OFF
30CZ2 OFF
30CZ1 OFF
30CZ2 OFF
YES
52C1
MC1
MF2
OFF
STOP
STOP
52C2
MC2
MF3
OFF
STOP
STOP
52C1
MC1
MF2
OFF
STOP
STOP
52C2
MC2
MF3
OFF
STOP
STOP
26D1
X1
4
OFF
6
OFF
CH1 ON
CH2 ON
CH1 ON
CH2 ON
21S4-1,2 ON
MF2, 3 OPERATE
SERVICE CALL
SERVICE CALL
Note.
When the fault of outdoor unit is occurred, the fan(MF1) of indoor unit continues to work.
But the unit doesn't work correctly (not cooling ).
Then, turn off the power supply and check outdoor unit.
When the fault of indoor unit is occurred, both indoor unit and outdoor unit is stop.
- 73 -
REFRIGERANT SCHEMATICS
PE-7,8,10,15,20MYC-EU
INDOOR
PE
OUTDOOR
PU
Evaporator
Condenser
High
pressure
switch
Service
port
Check
joint
Strainer
Ball valve
Interconnecting refrigerant piping
(by others)
COOL
Muffler
Accumulator
Check
joint
Compressor
Interconnecting refrigerant piping
(by others)
Strainer
Capillary
Tube
Ball valve
Note:PE-15,20MYC-EU is comprised of two refrigerant cycles.
PEH-5,7,8,10,15,20MYA-EU
INDOOR
PEH
OUTDOOR
PUH
Evaporator
Condenser
High
pressure
switch
Service
port
Check
joint
4-Way
valve
Strainer
Ball valve
Strainer
Interconnecting refrigerant piping
(by others)
HEAT COOL
Muffler
Accumulator
Check
joint
Compressor
Capillary
Tube
Capillary
Tube
Inter connecting refrigerant piping
(by others)
Check
valve
Strainer
Strainer
Check
valve
Ball valve
Note:PEH-15,20MYA-EU is comprised of two refrigerant cycles.
- 74 -
SAFETY & CONTROL DEVICES
PE-7,8,10MYC-EU
PE-15,20MYC-EU
PE-7MYC-EU
PU-7MYC1-EU
PE-8MYC-EU
PU-8MYC1-EU
PE-10MYC-EU
PU-10MYC1-EU
ITEM
NO.
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
51C
49C
63H
51F1
19.0A
22.0A
31.0A
105 ± 5 ˚C OFF
83 ± 11 ˚C ON
2.94MPa OFF
3.5A
INDOOR FAN MOTOR OVER CURRENT RELAY
5.0A
5.0A
INDOOR FAN MOTOR INTERNAL THERMOSTAT
OUTDOOR FAN MOTOR OVER CURRENT RELAY
-
150 Ëš C OFF
2.5A
51F2
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE
-
150 ËšC OFF
3.15A
F1
3
PE-15MYC-EU
PE-20MYC-EU
ITEM
NO.
PU-15MYC1-EU PU-20MYC1-EU
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
51C1,2
49C
63
22.0A 31.0A
105 ± 5 ˚C OFF 83 ± 11 ˚C ON
3.24MPa OFF
INDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE
51F1
51F2,3
-
4.6A
7.2A
2.5A
150 ËšC OFF
3.15A
F1
3
- 75 -
PEH-7,8,10MYA-EU
PEH-15,20MYA-EU
PEH-8MYA-EU
PUH-8MYC1-EU
PUH-8MYE-EU
PEH-5MYA-EU
PUH-5MYE-EU
PEH-7MYA-EU
PUH-7MYC1-EU
ITEM
NO.
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
51C
49C
15.0A
19.0A
22.0A
110 ± 5˚C OFF
61 ± 9˚C ON
105 ± 5˚C OFF
83 ± 11˚C ON
HIGH PRESSURE SWITCH
63H
26D1
26D2
51F1
2.94MPa OFF
-12 ± 2 ˚C ON
6 ± 2 ˚C OFF
5.0A
FROST PROTECTOR
INDOOR FAN MOTOR OVER CURRENT RELAY
3.5A
3.5A
INDOOR FAN MOTOR INTERNAL THERMOSTAT
OUTDOOR FAN MOTOR OVER CURRENT RELAY
-
150Ëš C OFF
2.5A
51F2
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE
-
150ËšC OFF
3.15A
F1
3
PEH-10MYA-EU
PUH-10MYC1-EU
PUH-10MYE-EU
PEH-15MYA-EU
PUH-15MYC1-EU
PEH-20MYA-EU
PUH-20MYC1-EU
ITEM
NO.
COMPRESSOR OVER CURRENT RELAY
COMPRESSOR INTERNAL THERMOSTAT
HIGH PRESSURE SWITCH
51C1,2
49C
63H
26D1
26D2
51F1
51F
31.0A
22.0A
31.0A
105 ± 5 ˚ C OFF 83 ± 11˚C ON
2.94MPa OFF
-12 ± 2 ˚C ON
FROST PROTECTOR
6 ± 2 ˚C OFF
INDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR OVER CURRENT RELAY
OUTDOOR FAN MOTOR INTERNAL THERMOSTAT
FUSE
5.0A
4.6A
2.5A
7.2A
-
150Ëš C OFF
3.15A
F1
3
- 76 -
SPECIAL ORDER
Model
Service ref.
Model
-
-
PE-7MYC
PE-8MYC
PE-10MYC PE-15MYC PE-20MYC
Cooling only
Heat pump
PE-7MYC-EU PE-8MYC-EU PE-10MYC-EU PE-15MYC-EU PE-20MYC-EU
Description
PEH-5MYA PEH-7MYA PEH-8MYA PEH-10MYA PEH-15MYA PEH-20MYA
Service ref.
PEH-5MYA-EU PEH-7MYA-EU PEH-8MYA-EU PEH-10MYA-EU PEH-15MYA-EU PEH-20MYA-EU
Release
2000 year
*
Low Ambient Cooling
Global Remote Controller
Anti corrosion
(Service reference)
(PUH-8MYC-EUS, (PUH-10MYC-EUS,
(PUH-5MYE-EUS) (PUH-7MYC-EUS)
(PUH-15MYC-EUS) (PUH-20MYC-EUS)
PUH-8MYE-EUS)
PUH-10MYE-EUS)
* Low ambient cooling
It is possible to conduct cooling operation under an outdoor temperature even down to -5 ËšC.
- 77 -
PHYSICAL DATA
PE-7,8,1015,20MYC-EU
]
[
PRODUCT
PACKAGE AIR COOLED HEATPUMP UNITS
Product type
PE SERIES
PE-10MYC-EU
PU-10MYC1-EU
28.8
Product number :
Indoor unit
Outdoor unit
PE-7MYC-EU
PU-7MYC1-EU
17.9
PE-8MYC-EU
PU-8MYC1-EU
22.0
PE-15MYC-EU
PU-15MYC1-EU
44.0
PE-20MYC-EU
PU-20MYC1-EU
57.6
Cooling capacity (AS1861)
kW
kW
kW
14.3
17.6
23.0
35.2
46.1
Sensible Cooling capacity (AS1861)
Cooling power consumption (Input)
Basic temperature condition cooling
Basic temperature condition cooling
7.2
7.8
10.1
16.9
22.7
Indoor
Outdoor
27 DB/19 WB
35 DB
[ELECTRICAL]
<Indoor unit>
Volts
Hz
240
415
50
Design voltage
Cy
cles
Power supply
Volts 1PH-240V
3PH-415V
240/24
415
Control voltage
Voltage change
Voltage change
Fan motor output
Fan motor current
Max.
Min.
Volts
Volts
240
220
380
HP(kW) 0.28(0.21) 0.94(0.70) 1.34(1.0) 2.95(2.2) 4.96(3.7)
Amps
3.2
1.2
2.0
3.5
4.8
<Outdoor unit>
Design voltage
Cycles
Volts
Hz
415
50
Power supply
Voltage change
Voltage change
Volts
Volts
Volts
3PH-415V
415
Max.
Min.
380
HP(kW) 2X0.12(2X0.09)
2X0.2(2X0.15)
0.32(0.24) 2X0.32(2X0.24)
Fan motor output
Fan motor current
Amps
0.7
1.0
1.2
2X1.2
[COMPRESSOR]
Make
MITSUBISHI
Model
Type
JH519YE JH521YE JH527YE
HERMETIC LINE START (RECIPROCATING)
JH521YE JH527YE
Number of compressor
Nominal motor
Locked rotor current
Normal run current (AS1861)
Swept volume
Bore
1
2
HP(kW) 6.7(5.0)
7.4(5.5) 10.1(7.5)
83
15.5
160.8
10.1(7.5)
85
19.2
7.4(5.5)
83
15.5
Amps
Amps
cc/rev
mm
76
13.0
149
85
19.2
201
ø44.45
201
160.8
Stroke
mm
24.0
25.9
Speed
Number of cylinders
rpm
2900
5
4
4
3000
5
4500
ml
3000
4500
Oil charge
Type of oil
DIAMOND MS32(N-1) OR SUNISO 3GS(D)
watts
62
72
62
72
Crankcase heater
[REFRIGERATION SYSTEM]
Refrigerant
Refrigerant charge per circuit
Number of refrigerant control
Refrigerant control
R22
8.7
kg
m
5.7
5.0
1
4.8
9.7
2
Capillary tube
50
Limit of pipe's length
mtrs
mtrs
20 (In case of indoor unit above outdoor unit)
30 (In case of outdoor unit above indoor unit)
Limit of pipe's height difference
- 78 -
Product number
Indoor unit
Outdoor unit
PE-7MYC-EU
PU-7MYC1-EU
PE-8MYC-EU
PU-8MYC1-EU
PE-10MYC-EU
PU-10MYC1-EU
PE-15MYC-EU
PU-15MYC1-EU
PE-20MYC-EU
PU-20MYC1-EU
[INDOOR AIR CIRCUIT]
2
Number of blowers
Diameter of blowers
Width of blowers
mm
mm
250
380
245
275
270
374
Direct drive
Belt drive
Blower drive
2.2
3.5
2333
3.7
4.8
3000
kW
A
L/s
Pa
mm
mm
0.21
3.2
1000
0.70
1.2
1167
125
1.00
2.0
1500
Fan motor output
Fan motor run current
Air quantity
External static pressure
Supply air dimensions(hxw)
Return air dimensions(hxw)
[EVAPORATOR]
200
341 X 1102
248 X 998
341X1302
412X1000 412X1209
596X1415
Number of evaporator
Face area
1
0.50
0.86
1.00
sq.m
0.42
4
Rows deep
4
15
24
Rows high
1300
3.0
1415
2.7
1615
3.0
Finned length
Face velocity
mm
m/s
1100
2.2
2.8
Fin per meter
474/2.11
513/1.95 474/2.11 513/1.95
0.115
Aluminium / Ring
Fin material thickness
Fin material/Type
Tube diameter
Gauge of copper tube
Pipe type
mm
mm
mm
9.52
0.35
Plain tube
Groove tube
Number of circuit
10
16
24
[OUTDOOR AIR CIRCUIT]
Number of fans
Diameter of fan
Blower drive
2
600
1
2
mm
954
Direct drive
Quantity of motor
Fan motor output
Fan motor run current
2
1
2
0.24
2X0.36
kW
A
L/s
2X0.09
0.7
3167
2X0.15
1.0
1.2
4000
2X1.2
8000
quantity
Air
3000
3667
[CONDENSER]
Number of condensers
Face area
Rows deep
Rows high
2
sq.m
2 X 2.1
32
1.32
2
40
1.35
2
30
1
2
30
30
mm
m/s
2706
2696
1299
1.5
1775
3.0
Finned length
Face velocity
1.4
1.5
6.25/1.6
474 / 2.7 625 / 1.6 538 / 1.86
0.115
Fin per meter/Pitch
Fin material thickness
Fin material/Type
Tube diameter/Gauge
Pipe type
mm
mm
Aluminium / Ring
9.52 / 0.35
Groove tube
Plain tube
6
Number of circuit
7
11
- 79 -
Product number
Indoor unit
Outdoor unit
PE-7MYC-EU
PU-7MYC1-EU
PE-8MYC-EU
PU-8MYC1-EU
PE-10MYC-EU
PU-10MYC1-EU
PE-15MYC-EU
PU-15MYC1-EU
PE-20MYC-EU
PU-20MYC1-EU
[ENCLOSURE AND FRAME]
mm
mm
mm
mm
mm
mm
428
706
height
width
depth
height
width
depth
1415
1615
1690
1993
Dimension
Indoor unit
650
980
1400
700
865
1230
998
961
1996
Outdoor unit
Dimension
998
External finish (indoor unit)
Galvanized steel
Acrylic resin coationg (Color: Munsell 5Y8/1)
(outdoor unit)
External finish
mm
mm
kg
1.2
25.4
84
230
59
65
67
76
Panel thickness
Condense drain size
Weight Indoor unit
Weight Outdoor unit
Sound pressure level (indoor unit)
Sound pressure level (outdoor unit)
Sound power level (indoor unit)
Sound power level (outdoor unit)
180
285
61
67
69
212
360
62
68
70
67
202
55
65
63
70
205
56
65
64
kg
dbA
dbA
dbA
dbA
76
76
78
79
- 80 -
PEH-5,7,8MYA-EU
]
[
PRODUCT
PACKAGE AIR COOLED HEATPUMP UNITS
PEH SERIES
Product type
Product number :
Indoor unit
Outdoor unit
PEH-5MYA-EU
PUH-5MYE-EU
14.4
PEH-7MYA-EU
PUH-7MYC1-EU
17.9
PEH-8MYA-EU
PUH-8MYC1-EU
PUH-8MYE-EU
22.0
17.6
7.8
22.0
6.5
Cooling capacity (AS1861)
kW
kW
kW
kW
kW
11.5
6.0
14.4
14.3
7.2
18.8
6.3
Sensible Cooling capacity (AS1861)
Cooling power consumption (Input)
Heating capacity (AS1861)
Heating power consumption
4.5
Indoor
Outdoor
Indoor
Basic temperature condition cooling
Basic temperature condition cooling
Basic temperature condition heating
Basic temperature condition heating
27 DB/19 WB
35 DB
21 DB
7
DB/6 WB
Outdoor
[ELECTRICAL]
<Indoor unit>
Volts
Hz
Design voltage
415
240
415
Cy
50
cles
Power supply
Volts
3PH-415V
1PH-240V
3PH-415V
Control voltage
Voltage change
Voltage change
Fan motor output
Fan motor current
240/24
Max.
Min.
Volts
Volts
HP(kW)
Amps
415
380
0.6(0.45)
415
380
0.94(0.70)
240
220
0.28(0.21)
1.1/1.0
3.2
1.2
<Outdoor unit>
Design voltage
Cycles
Volts
Hz
415
50
Power supply
Voltage change
Voltage change
Fan motor output
Fan motor current
Volts
Volts
Volts
HP(kW)
Amps
3PH-415V
415
Max.
Min.
380
0.2(0.15)
1.0
0.47(0.35)
2X0.12(2X0.09)
0.7
[COMPRESSOR]
Make
Model
Copeland
CRNQ-0500-TFD
MITSUBISHI
JH521YE
JH519YE
Type
HERMETIC LINE START (RECIPROCATING)
1
Number of compressor
Nominal motor
Locked rotor current
Normal run current (AS1861)
Swept volume
Bore
HP(kW)
Amps
Amps
cc/rev
mm
5.0(3.73)
6.7(5.0)
7.4(5.5)
65
76
83
8.6
101.92
13.0
149
15.5
160.8
ø49.78
26.19
ø44.45
Stroke
mm
25.9
24.0
rpm
2900
Speed
2
1952
CALUMET RO 15 OR WITCO 3GS
40
4
3000
Number of cylinders
Oil charge
Type of oil
ml
DIAMOND MS32(N-1) OR SUNISO 3GS(D)
watts
62
Crankcase heater
[REFRIGERATION SYSTEM]
Refrigerant
R22
kg
5.7
6.6
Refrigerant charge per circuit
Number of refrigerant controls
Refrigerant control
5.0
1
Capillary tube
4-way valve
Reverse cycle defrost
50
Reverse cycle valve
Defrost system
Limit of pipe's length
m
mtrs
mtrs
20 (In case of indoor unit above outdoor unit)
30 (In case of outdoor unit above indoor unit)
Limit of pipe's height difference
- 81 -
Product number
Indoor unit
Outdoor unit
PEH-5MYA-EU
PUH-5MYE-EU
PEH-7MYA-EU
PUH-7MYC1-EU
PEH-8MYA-EU
PUH-8MYC1-EU
PUH-8MYE-EU
[INDOOR AIR CIRCUIT]
1
2
Number of blowers
Diameter of blowers
Width of blowers
mm
mm
250
275
245
275
Direct drive
Blower drive
0.45
1.1/1.0
700
100
342X781
248X498
0.21
3.2
1000
0.70
1.2
1167
kW
A
L/s
Pa
mm
mm
Fan motor output
Fan motor run current
Nominal air quantity
External static pressure
Supply air dimensions(hxw)
Return air dimensions(hxw)
[EVAPORATOR]
125
341X1102
342X1118
248X998
Number of evaporator
Face area
Rows deep
Rows high
Finned length
1
4
sq.m
0.3
0.42
15
15
780
2.5
1100
2.2
1100
2.8
mm
m/s
Face velocity
513/1.95
474/2.11
474/2.11
Fin per meter / pitch
Fin material thickness
Fin material/Type
Fin coating
Tube diameter
Gauge of copper tube
Pipe type
0.115
mm
Aluminium / Ring
NA 510 D*1
9.52
mm
mm
0.35
Plain tube
10
Groove tube
7
Groove tube
Number of circuit
[OUTDOOR AIR CIRCUIT]
Number of fans
Diameter of fan
Blower drive
1
2
600
1
800
mm
Direct drive
1
0.35
1.2
1
0.35
1.2
Quantity of motor
Fan motor output
Fan motor run current
2
2X0.09
0.7
kW
A
L/s
1583
2783
3333
Nominal air quantity
[CONDENSER]
Number of condensers
Face area
2
2X2.1
2
1
1.3
1
1.58
sq.m
Rows deep
Rows high
44
30
44
mm
m/s
Finned length
Face velocity
1000
1.56
2706
1.35
1400
1.95
Fin per meter/Pitch
Fin material thickness
Fin material/Type
Tube diameter/Gauge
Pipe type
513/1.95
474 /2.11
0.115
Aluminium / Ring
513 /1.95
mm
mm
9.52 / 0.35
Groove tube
7
Number of circuit
11
11
Specifications subject to change without noice
*1 Corrosion proof property : Salt spray JIS Z 2371, 500hrs Humiditiy test 50C 98% 500hrs.
*2 Corrosion proof property : Salt spray JIS Z 2371, 1000hrs Humiditiy test 50C 98% 1000hrs.
- 82 -
Product number
Indoor unit
Outdoor unit
PEH-5MYA-EU
PUH-5MYE-EU
PEH-7MYA-EU
PUH-7MYC1-EU
PE-8MYA-EU
PUH-8MYC1-EU
PUH-8MYE-EU
[ENCLOSURE AND FRAME]
428
mm
mm
mm
mm
mm
mm
height
width
depth
height
width
depth
1095
1415
Dimension
Indoor unit
650
980
1400
1175
1000
550
1175
1250
550
Outdoor unit
Dimension
700
External finish (indoor unit)
Galvanized steel
Acrylic resin coationg (Color: Munsell 5Y8/1)
(outdoor unit)
External finish
mm
mm
kg
1.2
25.4
Panel thickness
Condense drain size
Weight Indoor unit
Weight Outdoor unit
Sound pressure level (indoor unit)
Sound pressure level (outdoor unit)
Sound power level (indoor unit)
Sound power level (outdoor unit)
60
150
67
211
70
56
64
kg
214
65
188
dbA
dbA
dbA
dbA
55
63
57
68
76
- 83 -
PEH-10,15,20MYA-EU
]
[
PRODUCT
PACKAGE AIR COOLED HEATPUMP UNITS
PEH SERIES
Product type
Product number :
Indoor unit
Outdoor unit
PEH-15MYA-EU
PUH-15MYC1-EU
44.0
PEH-20MYA-EU
PUH-20MYC1-EU
57.6
PEH-10MYA-EU
PUH-10MYC1-EU
PUH-10MYE-EU
28.8
23.0
10.1
28.8
8.3
Cooling capacity (AS1861)
kW
kW
kW
kW
kW
35.2
16.8
44.0
14.1
46.0
22.7
57.6
19.3
Sensible Cooling capacity (AS1861)
Cooling power consumption (Input)
Heating capacity (AS1861)
Heating power consumption
Indoor
Outdoor
Indoor
Basic temperature condition cooling
Basic temperature condition cooling
Basic temperature condition heating
Basic temperature condition heating
27 DB/19 WB
35 DB
21 DB
7
DB/6 WB
Outdoor
[ELECTRICAL]
<Indoor unit>
Volts
Hz
Design voltage
415
50
Cy
cles
Power supply
Volts
3PH-415V
240/24
415
Control voltage
Voltage change
Voltage change
Fan motor output
Fan motor current
Max.
Min.
Volts
Volts
HP(kW)
Amps
380
1.34(1.0)
2.0
1.34(1.0)
2.0
2.95(2.20)
4.1
4.96(3.70)
4.7
<Outdoor unit>
Design voltage
Cycles
Volts
Hz
415
50
Power supply
Voltage change
Voltage change
Fan motor output
Fan motor current
Volts
Volts
Volts
HP(kW)
Amps
3PH-415V
415
Max.
Min.
380
2X0.2(2X0.15)
1.0
0.47(0.35)
1.2
2X0.47(2X0.35)
2X1.2
[COMPRESSOR]
Make
Model
MITSUBISHI
JH521YE
HERMETIC LINE START (RECIPROCATING)
JH527YE
JH527YE
Type
Number of compressor
Nominal motor
Locked rotor current
Normal run current (AS1861)
Swept volume
Bore
1
10.1(7.5)
85
19.2
201
2
HP(kW)
Amps
Amps
cc/rev
mm
7.4(5.5)
83
15.5
10.1(7.5)
85
19.2
160.8
201
ø44.45
25.9
Stroke
mm
rpm
Speed
Number of cylinders
2900
5
4
5
ml
4500
3000
4500
Oil charge
Type of oil
DIAMOND MS32(N-1) OR SUNISO 3GS(D)
watts
72
62
72
Crankcase heater
[REFRIGERATION SYSTEM]
Refrigerant
R22
kg
6.6
9.7
Refrigerant charge per circuit
Number of refrigerant controls
Refrigerant control
Reverse cycle valve
Defrost system
9.9
1
2
Capillary tube
4-way valve
Reverse cycle defrost
50
m
Limit of pipe's length
mtrs
mtrs
20 (In case of indoor unit above outdoor unit)
30 (In case of outdoor unit above indoor unit)
Limit of pipe's height difference
- 84 -
Product number
Indoor unit
Outdoor unit
PEH-15MYA-EU
PUH-15MYC1-EU
PEH-20MYA-EU
PUH-20MYC1-EU
PEH-10MYA-EU
PUH-10MYC1-EU
PUH-10MYE-EU
[INDOOR AIR CIRCUIT]
2
Number of blowers
Diameter of blowers
Width of blowers
mm
mm
250
275
Direct drive
280
245
275
Belt drive
Blower drive
1.00
2.0
1500
1.00
1.8
1500
2.20
4.5
2333
3.70
4.7
3000
kW
A
L/s
Pa
mm
mm
Fan motor output
Fan motor run current
Nominal air quantity
External static pressure
Supply air dimensions(hxw)
Return air dimensions(hxw)
[EVAPORATOR]
125
200
341X1302
342X1318
412X1000
412X1209
248X998
596X1415
Number of evaporator
Face area
1
0.50
2
sq.m
0.86
0.98
Rows deep
4
15
1300
3.0
24
Rows high
Finned length
Face velocity
1415
2.7
1615
3.0
mm
m/s
513/1.95
513/1.95
0.115
592/1.69
Fin per meter / pitch
Fin material thickness
Fin material/Type
Fin coating
mm
Aluminium / Ring
NA 510 D*1 (NA 549*2)
mm
mm
9.52
0.35
Tube diameter
Gauge of copper tube
Pipe type
Groove tube
16
Plain tube
Number of circuit
10
24
[OUTDOOR AIR CIRCUIT]
Number of fans
Diameter of fan
Blower drive
2
600
1
2
mm
800
Direct drive
1
0.35
1.2
2
Quantity of motor
Fan motor output
Fan motor run current
2
kW
A
2X0.15
1.0
2X0.35
1.3
L/s
3167
2X3083
3333
Nominal air quantity
[CONDENSER]
Number of condensers
Face area
2
1
1.58
2
sq.m
2X2.1
2X1.07
2X1.32
Rows deep
3
Rows high
30
44
37
mm
m/s
Finned length
Face velocity
2706
1.35
1400
1.95
2800
2.89
2.34
Fin per meter/Pitch
Fin material thickness
Fin material/Type
Tube diameter/Gauge
Pipe type
474/2.11
513/1.95
0.115
Aluminium / Ring
474 /2.11
mm
mm
9.52 / 0.35
Groove tube
Number of circuit
11
11
14
16
Specifications subject to change without noice
*1 Corrosion proof property : Salt spray JIS Z 2371, 500hrs Humiditiy test 50ËšC 98% 500hrs.
*2 Corrosion proof property : Salt spray JIS Z 2371, 1000hrs Humiditiy test 50ËšC 98% 1000hrs.
(anti corrosion as special order)
- 85 -
Product number
Indoor unit
Outdoor unit
PEH-15MYA-EU
PUH-15MYC1-EU
PEH-20MYA-EU
PUH-20MYC1-EU
PEH-10MYA-EU
PUH-10MYC1-EU
PUH-10MYE-EU
[ENCLOSURE AND FRAME]
428
1615
650
706
865
1200
1951
1080
mm
mm
mm
mm
mm
mm
height
width
depth
height
width
depth
1690
1993
Dimension
Indoor unit
980
1400
700
1175
1250
550
Outdoor unit
Dimension
External finish (indoor unit)
Galvanized steel
Acrylic resin coationg (Color: Munsell 5Y8/1)
(outdoor unit)
External finish
mm
mm
kg
1.2
25.4
Panel thickness
Condense drain size
Weight Indoor unit
Weight Outdoor unit
Sound pressure level (indoor unit)
Sound pressure level (outdoor unit)
Sound power level (indoor unit)
Sound power level (outdoor unit)
180
431
61
212
472
62
84
221
kg
240
dbA
dbA
dbA
dbA
59
65
67
76
69
80
69
70
- 86 -
INSTALLATION
Space required around unit.
1.
Indoor unit
Dimension of the unit and space necessary for sevicing.
PE(H)-15,20
PEH-5 PE(H)-7, 8, 10
180
380
B
A
200
400
B
A
Ceiling access panel
Ceiling access panel
A
B
A
B
PEH - 5
PE(H) - 7, 8
PE(H) - 10
1560 1000
1880 1320
2080 1520
PE(H) - 15
PE(H) - 20
2187 1587
2490 1890
Outdoor unit
Secure enough space necessary for servicing, installing, and for proper function of the unit.
To prevent short-cycling, remove obstacles as much as possible.
PUH-5, 8, 10 (Side blow)
(1) At a single installation
Service panel
Inlet surface
150 over
Inlet surface
150 over
150 over
500 over
Inlet
surface
Inlet
surface
Outlet surface
300 over
Outlet surface
Service panel
With the inlet surface facing a wall.
With the outlet surface facing a wall.
(2) Relation of unit when many set up unit.
300
over
500 over
500 over
500 over
500 over
Please set the unit that the inlet air and the outlet air are not influenced.
- 87 -
PU(H)-7,8, 10 (Upper blow)
(1) At a single installation
The obstacle is on the outlet side. (Fig 1)
The obstacle is in three directions. (Fig 2,3)
The obstacle is in four directions. (Fig 4)
ceiling
1200
over
However, the
outlet side must
be opened.
The right and left side
and the back and forth
side must be opened.
300 over
500 over
Service Panel
Fig 2
Fig 1
If this side is service
panel, you need 500
over. If this side is inlet,
you need 300 over.
All "A" is 500 over.
However, outlet side
must be opened.
And the obstacle in
two directions must be
lower than the unit.
However, if the service
panel is an interior side,
the right or left side
need 500 over.
A
A
300 over
300 over
Fig 3
Fig 4
(2) Relation of unit when many set up unit. (Fig 5,6,7)
If this side is
service panel,
you need 500 over.
If this side is inlet,
you need 300 over.
Service-panel
A
A
A
A
300 over
300 over
500
over
500 over
300 over
Fig 6 All "A" is 500 over.
Fig 5
Service-panel
A
A
A
A
A
Fig 7 All "A" is 500 over in any case.
- 88 -
PU-15
(1) At a single installation
The obstacle is on the outlet side. (Fig 1)
The obstacle is in four directions. (Fig 2)
300 over
500 over
ceiling
However, the outlet
1500
over
side must be opened.
The right and left side
and the back and forth
side must be opened.
300 over
300 over
Service Panel
Fig 1
Fig 2
(2) Relation of unit when many set up unit. (Fig 3,4)
If this side is service panel, you
need 500 over.
If this side is inlet, you need 300 over.
Service-panel
If this side is
If this side is
service panel, you
need 500 over.
If this side is inlet,
you need 300 over.
service panel, you
need 500 over.
If this side is inlet,
you need 300 over.
500
A
A
A
over
300 over
300 over
Fig 4 All "A" is 500 over.
Service-panel
Fig 3
PU-20
(1) At a single installation
The obstacle is on the outlet side. (Fig 1)
The obstacle is in four directions. (Fig 2)
300 over
However, the outlet
side must be opened.
ceiling
500 over
1500
over
300 over
300 over
The right and left side
and the back and forth
side must be opened.
Service Panel
Fig 2
Fig 1
(2) Relation of unit when many set up unit. (Fig 3,4,5)
300 over
500 over
Service-panel
If this side is
If this side is
servicepanel, you
need 500 over.
servicepanel, you
need 500 over.
500
If this side is inlet,
you need 300 over.
If this side is inlet,
you need 300 over.
300 over
over
A
A
A
300 over
A
Service-panel
Fig 4 All "A" is 500 over.
Fig 3
If this side is
service panel, you
need 500 over.
If this side is inlet,
you need 300 over.
300 over
A
A
A
300 over
Fig 5 All "A" is 500 over in any case.
- 89 -
PUH-15, 20
(1) At a single installation
The obstacle is on the outlet side. (Fig 1)
The obstacle is in four directions. (Fig 2)
The obstacle is in three directions. (Fig 3,4)
ceiling
1500
over
However, outlet side
must be opened.
500 over
300 over
The right and left side
and the back and forth
side mustbeopened.
And the obstacle in
two directions must be
lower than the unit.
300 over
Service Panel
Fig 2
Fig 1
However, the outlet side must be opened.
300 over
Service-panel
500 over
300 over
300 over
Service-panel
Fig 3
Fig 4
(2) Relation of unit when many set up unit. (Fig 5,6,7)
500 over
Service-panel
If this side is
If this side is
servicepanel, you
need 500 over.
servicepanel, you
need 500 over.
500
If this side is inlet,
you need 300 over.
If this side is inlet,
you need 300 over.
300 over
over
300 over
A
A
A
A
Service-panel
Fig 5
Fig 6 All "A" is 500 over.
If this side is
service panel, you
need 500 over.
If this side is inlet,
you need 300 over.
300 over
A
A
A
300 over
Fig 7 All "A" is 500 over in any case.
2. Preparation before installing
Reinforcement
Indoor unit
Please use the specified hanging bolt in any case.
Hanging bolt is local supply.
Please use the method below or use the angle and the
rectangular lumber, etc. and install the hanging bolt.
Insert etc
100-150kg
Hanging bolt
M10 (PEH-5,PE(H)-7,8,10)
M12 (PE(H)-15,20)
- 90 -
3. Installation of the unit.
Indoor unit
Please carry the packed until parallelly to installed place.
Please install the unit before construction of the ceiling -lined.
PEH-5 PE(H)- 7, 8, 10
U washer
Nut
Washer
Nut
PE(H)- 15, 20
Nut (M10)
Nut (M10)
Washer
Washer
Ceiling
Nut (M10)
Nut (M10)
Outdoor unit
Fix unit tightly with bolts as shown below so that unit will be securely fixed
in place use concrete or angle foundation of unit.
At the time of bottom piping of refrigerant pipe, build a 100mm or higher
foundation so that piping will go through bottom of unit.
Anchor bolt (local arrangement)
PUH-5 PU(H)-7, 8, 10 M8
PU(H)-15, 20
M10
Installation pitch
Concrete foundation
- 91 -
Duct construction.
Provide canvas flexible ducting between unit when connect to the duct-work.
The duct unit must use a nonflammable material.
Provide sufficient insulation for prevent dewdrop.
Duct earth
Canvas Duct
Duct earth
Canvas Duct
Duct
Duct
Drain pan
Inlet
Outlet
Duct-work length 850mm or more
Lifting method.
When the unit is to be lifted and moved, attach ropes to the suspension plates(3 p.c.s)
provided on the top of the unit.
When the unit is lifted, it 's center of gravity tends to shift the unit one side and so balance,
such as that in the figure below, should be attained.
The angles at which the ropes suspend the unit should be at least 60 at the compressor end
and at least 45 at the condenser end. Care should be taken to avoid contact with the main unit
while carrying.
It is necessary to protect the unit with the blanket so that the ropes should not injure the unit.
Hook (as directly aligned over
the center of gravity as possible.
MITSUBISHI
ELECTRIC
Example PUH-15, 20
- 92 -
Piping connection
Warning.
Please follow the following procedures, during the piping connection work is carried out.
If the procedures are not followed properly, the refrigerant and valve sheet might gush out from the ball valve.
It might cause the injury.
In case of Brazing type
1. Open the ball valve cap before removing the by-pass tube.
Then, turn the knob of the ball valve from ’close’ to ’open’
position.
2. Please repeat to close and open the ball valve of gas and liquid side at the same time (3 times or more).
And finally make sure the ball valve is at close position.
CLOSE
OPEN
3. Cut part A (two places) of the by-pass tube as shown in figure below.
Caution
CUT
There will be small amount of refrigerant gushed
out of the by-pass tube at the moment.
CUT
4. Make sure that the ball valve is wrapped with enough wet cloth, during the brazing of the by-pass tube
(for cooling purpose). Make sure the temperature of ball valve is below 100 degree centigrade. (If the
temperature of the ball valve is over 100 degree centigrade, the refrigerant and valve sheet might gush
out from the ball valve. It might cause the injury.)
enough wet
cloth
5. Please make sure the ball valve is cool enough when removing the by-pass tube. Wait for a while for
further cooling of the ball valve, before the piping connection work begins.
6. When the piping connection begins. Again, make sure that the ball valve is wrapped with enough wet
cloth, during the brazing for cooling the ball valve. Make sure the temperature of ball valve is below 100
degree centigrade. (If the temperature of the ball valve is over 100 degree centigrade, the refrigerant and
valve sheet might gush out from the ball valve. It might cause the injury.)
7. Before charging the refrigerant, vacuum the pipes to clear all the air and water.
8. Charge the additional amount of refrigerant according to the table.
9.Turn the knob of the ball valve to ’open’ position after leak check.
10. Finally, put the cap back to the ball valve.
- 93 -
In case of Flare, Flange type
1. PROCEDURE TO CONNECT THE EXTENSION PIPE.
Proceed with the connection as follows:
(1) Open the ball valve cap before cutting the by-pass tube.(Fig.1)
(2) Check the ball valve section is completely closed.(Fig.2)
(3) Cut two parts of the by-pass tube.(Fig.4)
Fig. 1
Valve knob
Caution
Valve knob
There will be small amount of refrigerant gushed out
of the by-pass tube at the moment.
(4) Remove the connection pipe assy.(Fig.5)
Throw away the packing.
Open
Close
Fig. 2
cut
Fig. 3
Do not brazing the pipe while the flange assy connect the ball
valve. (Except the PUH-5)
(5) Remove the by-pass tube.(Fig.6)
Braze the extension pipe with the flange assy. (Except the PUH-5)
cut
(6) Connect the extension pipes with the packing between the ball
valve and the flange.(Fig.7)
Fig. 4
Use the attached new packing certainly.
Pipe assy
Unit side
Fig. 5
2. HANDLING PRECAUTIONS.
(1) The extension pipes should be connected with the valve knob
completely closed. (Fig.2)
throw away
Check leak test the part of flange and flare.
By-pass tube
(2) Before charging the refrigerant, vacuum the pipes to clear all the air
and water.
Flange assy
Extension pipe
(3) Charge the additional amount of refrigerant according to the table.
(4) Turn the ball valve knob to "Open" position after leak check again.
(Fig.3)
Fig. 6
(5) Finally, put the cap back to the ball valve.
Unit side
Extension pipe
Fig. 7
use the attached new packing
- 94 -
Refrigerant piping.
4.
Extension piping and installation parts are field supply.
Perform the work only after carefully reading the
appropriate instructions.
A
Install the unit where the refrigerant piping is shortest,
the difference between the indoor unit and outdoor unit
is smallest.
When the outdoor unit is lower.
As pipes purchased in the market may contain
dust, below them off with dry inlet gas.
Take care not to allow dust and water content to enter
the piping during pipe processing or installing.
Minimize the number of bends, and make the bending
radius as long as possible.
B
Always observe the restriction(allowable length, height
difference, pipe diameter) on the refrigerant piping.
For soldering & brazing, use high-quality materials.
When the outdoor unit is higher.
Never purge air with a refrigerant. Always use a vacuum pump for purging.
Provide proper insulation to the piping . Insufficient insulation cause poor cooling/heating
performance or condensation drip, leading to unexpected trouble.
Do not insulate gas or low pressure pipe and liquid or high pressure pipe together.
For the connection of the refrigerant piping, leave the valve of the outdoor unit fully closed
(as set before shipment), and no operate it until the connection between the indoor/outdoor
units and refrigerant piping, refrigerant leak test and evacuation work have been completed.
The maximum permissible values are shown below.
Remove the cover (grommet) attached sheet metal at exit of heat exchanger pipe of indoor
unit before connecting the local piping.
(This cover is protect the pipe from sheet metal edge at unit transportation.)
Please insulate liquid pipe & gas pipe (two places for each) with an insulated pipe of the
attachment after connecting piping.
Bad example
Good example
Finishing tape
Insulating material
Insulating material
Finishing tape
Liquid pipe
Liquid pipe
Electric wire
Gas pipe
Electric wire
Gas pipe
PEH-5 PE(H)-7 PE(H)-8 PE(H)-10 PE(H)-15 PE(H)-20
Dimension A (m)
20
20
20
20
20
20
Dimension B (m)
Number of bends
30
15
50
30
15
50
30
15
50
30
15
50
30
15
50
30
15
50
Total piping length (m)
Liquid pipe (mm)
Piping
12.7
15.88
25.4
15.88
25.4
15.88
28.6
2x15.88 2x15.88
2x25.4 2x28.6
size
Gas pipe (mm)
19.05
- 95 -
Airtight test
Airtight test should be made by pressurizing nitrogen gas to 3Mpa.
For the test method, refer to the following figure.
(Make a test with the valve closed. Be also sure to pressurize both liquid and gas pipe.)
The test result can be judged good if the pressure has not been reduced after leaving
for about one day after completion of nitrogen pressurization.
Nitrogen gas
To indoor unit
System analyzer
Low knob
a.
b.
c.
d.
e.
f
b
g
h
i
High knob
c
Valve
f.
Liquid gas
g.
e
d
a
j
Gas pipe
Outdoor unit
Service port
h.
i.
j.
Evacuation
Evacuation should be made from the service port provided on the outdoor unit’s valve to
the vacuum pump commonly used for both liquid pipe and gas pipe.
(Make evacuation from both liquid pipe and gas pipe with valve closed.)
Remember :Never carry out air purge by refrigerant.
System analyzer
To indoor unit
a.
b.
c.
d.
e.
e
b
f
Low knob
High knob
h
Valve
Liquid gas
g
a
f.
g.
c
d
Gas pipe
i
j
h.
i.
j.
Outdoor unit
Service port
Vacuum pump
Additional refrigerant charge
The mount of refrigerant charged in this unit is a appropriate for 5-meter long refrigerant pipes.
Refer to the table below and add the corresponding amount of refrigerant if the pipes are
extended.
The outdoor unit of PE-5,8,10 have side
blow type and upper blow type.
(The refrigerant is charged in the outdoor unit.)
Factory charge refer to the table below.
Factory charge
Refrigerant piping length
30m 35m 40m 45m 50m
5m 10m 15m 20m 25m
Outdoor unit
unit
PU-7
Upper blow
Side blow
PU-8
PU-7
5.7
5.0
0
0.8 1.6
2.4 3.2 4.0 4.8 5.6
6.4 7.2
PU-10
PU-15
PU-8
charge
mount
R-22
PU-10
PU-15
PU-20
8.7
0
2x0.8 2x1.6 2x2.4 2x3.2 2x4.0 2x4.8 2x5.6 2x6.4
2x7.2
PU-20
charge
mount
R-22
2x4.8
2x9.7
0
0
0.5 1.0 1.5 2.0 2.5 3.0 3.5 4.0 4.5
0.8 1.6 2.4 3.2 4.0 4.8 5.6 6.4 7.2
PUH-5
PUH-7
PUH-8
PUH-10
PUH-15
PUH-20
(kg)
5.0
PUH-5
(kg)
PUH-7
PUH-8
PUH-10
5.7
6.6
9.9
0
0
0.8 1.7 2.5 3.3 4.2 5.0 5.8 6.7 7.5
PUH-8
6.6
9.9
PUH-10
2x0.8 2x1.7 2x2.5 2x3.3 2x4.2 2x5.0 2x5.8 2x6.7
2x7.5
PUH-15 2x6.6
2x9.7
PUH-20
- 96 -
Drain piping
5.
•Incline the drain piping to the outside (drain side) as shown in the figure below.
•The outlet of the indoor unit drain pipe is Rc1.
•After completion of piping, confirm that drainage is good and that there are no leaks.
Indoor unit drain piping
Install thermal insulation
to prevent dew
The drain piping should have a drain trap.
>
A 70mm
=
>
>
x
B= 2 C= 70mm
Slope
20mm/m
>
C 35mm
=
Drain piping
Drain pan
The drain pipe
should extend
Drain trap
Open drain
below this level.
- 97 -
Electric wiring
6.
Construct the earth connection.
All electrical work must be carried out by a suitable qualified electrical trades-person and in
accordance with local supply authority requirements and associated regulators.
The outdoor unit is to be wired directly from an electrical distribution board either by a circuit
breaker (preferred) or HRC fuse.
Fix power source wiring to control box by using buffer bushing for tensible force (PG
connection or the like). Connect control wiring to control terminal block through the knockout
hole of control box using ordinary bushing.
NOTE: Earth wiring must be connected.
Arrangement such as terminal block in control box
Control module of indoor unit
Control module of indoor unit
PEH-5, PE(H)-7, 8,10
PE(H)-15, 20
PE(H)-7 only
Terminal block for
connection wires to
Outdoor unit and
remote controller
PEH-15, 20 only
F1
30FZ
F1 3.15A
F1
Tr
Terminal block for
connection wires to
Outdoor unit and
remote controller
C
FZ
F2 3.15A
F2
TB3
F2
30FZ
PEH-15, 20 52F&51F1
PE-15, 20 52F1&51F1
CZ1-1
PEH only
Tr
52F
&
51F1
CZ1-2
TB3
Terminal block for
power supply wires
Terminal block for
power supply wires
FZ
TB2
PEH-15, 20 HZ1
PE-15, 20
FZ
HZ1
CZ1
TB2
Screw for earth
connection
Bush and band for
the power supply
Bush and band for
the power supply
Bush for the thermistor
Bush for the thermistor
Screw for earth
connection
Bush and band for the connection wires
to Outdoor unit and remote controller
Bush and band for the connection wires
to Outdoor unit and remote controller
Control module of outdoor unit (PUH-5, 8, 10)
Side blow
Screw for earth
connection
51F2
30CZ
X3
T1
X2
F3
52C
&
51C
Terminal block
for power supply
wires
CZ2 HZ2
TB1
TB4
X1
Terminal block for
connection wires
to Indoor unit
Band for wires
- 98 -
Control module of outdoor unit PU-15
Control module of outdoor unit PU(H)-7, 8, 10
Upper blow
PUH only
F3
Terminal block for
power supply wires
T1
F3
52C
&
51C
2
F3 3.1
52C1
&
51C1
52C2
&
51C2
52F2
&
PUH only
TB1
51F2
30CZ1 30CZ2
CZ
CZ
51F2
2-1 2-2
TB4
X1
PUH only
Screw for earth
connection
Terminal block for
connectioon wires
to Indoor unit
Terminal block for
connection wires to
Indoor unit
Bush for wires
TB5
X2
X3
Screw for earth
TB1
connection
Terminal block for
power supply wires
Band for wires
Control module of outdoor unit PU-20
Control module of outdoor unit PUH-15,20
52F2&
51F2
Screw for earth
connection
52C2
&
51C2
51F3
51F2
51F3
X3
X4
X5
T1
T2
2
F3
52C1
&
51C1
52C2
&
51C2
30 30
CZ1CZ2
52C1
2
X1
X2
X6 30CZ1 30CZ2
CZ
CZ
&
TB1
51C1
2-1 2-1
HZ2
TB4
CZ
2-2
CZ
2-1
Screw for earth
connection
TB4
Terminal block for
connection wires
to Indoor unit
F3
TB1
Terminal block for
connectioon wires
to Indoor unit
Terminal block for
power supply wires
Bush for wires
Terminal block for
power supply wires
Bush for wires
- 99 -
Method for connecting electric wire
Please do the wiring after consulting the electric power
company of jurisdiction beforehand in the instruction.
(1) The entire wiring diagram of unit.
a
a
Power supply
b. Main switch/fuse (field supply)
a.
b
d
b
PE
PE
c.
Power supply wiring for outdoor unit
Power supply wiring for indoor unit
In case of PE-7,8,10
In case of PE-15,20
j
j
c
d.
e.
Outdoor unit
Indoor unit
PEH-5, 7, 8, 10
f.
g
Connection wiring for indoor
/ outdoor units (polarity)
In case of PEH-15,20
g.
i
In case of PE-7, 8, 10
e
f
Remote controller (field supply)
h.
In case of PE-15, 20
h
PEH-5, 7, 8, 10
Connection wiring for indoor
/ remote controller (no polarity)
i.
j.
In case of PEH-15, 20
Earth
(2) Power supply construction and electric wiring connection of indoor and outdoor unit.
In case of
PEH-5
In case of PE(H)-15,20
PE(H)-7,8,10
B
G
H
H
A
3phase
PE(H)-7:Single phase
PE
N
L1
L2
L3
13 14 15
11 12 13 14
PEH-5
PE(H)-7,8,10
PE(H)-15,20
15A
15A
30A
C
C
D 3 phase
PUH-5
50A
50A
60A
100A
125A
PU(H)-7,8
PU(H)-10
PU(H)-15
PU(H)-20
PEH only
PEH only
13 14 15
PE
N
L1
L2
L3
11 12 13 14
G
H
H
E
F
Indoor unit
A.
B. Power cable wiring
Control cable wiring
C.
(Fixing wire-- Do not remove)
D. Outdoor unit
Breaker
E.
F. Fuse
G. Power supply terminal bed
H. Control cable terminal bed
- 100 -
(3) Indoor unit and remote controller.(OPTION:PAC-204RC)
Connect the wires on the basis of the following wiring diagram.
PE(H)-15,20
PEH-5, PE(H)-7,8,10
TB4
1
TB3
1
GRAY
GRAY
F2
(3.15A)
F2
(3.15A)
Tr
Tr
AC24V
GRAY
AC
220
240V
AC24V
GRAY
AC
220
240V
TB4
TB3
2
3
2
3
4
CZ CZ
1-1 1-2
FZ
FZ
CZ1
4
5
(4) Wiring example (For metal piping)
Over current
Breaker
capacity
Power
cable
Control
Earth cable
protection switch
wiring
15A
15A
15A
PEH - 5
2.0mm2
15A
15A
15A
2.0mm2 over
2.0mm2over
2.0mm2over
2.0mm2over
2.0mm2over
PE(H) - 7 2.0mm2
PE(H) - 8 2.0mm2
Cable or
wire of
0.75mm2
(24VDC)
2.0mm2
2.0mm2
15A
30A
15A
30A
PE(H) -10
PE(H) -15
2.0mm2
30A
2.0mm2over
30A
PE(H) -20
8mm 2
50A
50A
8mm2over
8mm2over
PUH - 5
PU(H) - 7 8mm 2
50A
50A
The grounding wire must be of the same
diameter as the power cable wires.
Table above is an example.
The selection of other capacities should be
determined in accordance with the relevant
standards.
Cable or
8mm 2
50A
60A
8mm 2over wire of
PU(H) - 8
50A
0.75mm2
(24VDC)
PU(H) -10 14mm2
PU(H) -15 14mm2
PU(H) -20 22mm2
60A
14mm2 over
14mm2 over
22mm2 over
100A
125A
100A
125A
(5) Selecting earth leakage breaker (NV)
To select NF or NV instead of a combination of Class B fuse switch use the following.
In the case of Class B fuse rated 15A.
Fuse
Earth leakage breaker
(class B)
(with over-load protection)
NV is a product of
PEH - 5
15A
15A
15A
15A
NV30-CA
15A 30mA 0.1s or less
15A 30mA 0.1s or less
15A 30mA 0.1s or less
15A 30mA 0.1s or less
MITSUBISHI ELECTRIC.
Table above is an example.
The selection of other
capacities should be
PE(H) - 7
PE(H) - 8
PE(H) - 10
NV30-CA
NV30-CA
NV30-CA
determined in accordance with
the relevant standards.
PE(H) -15
PE(H) -20
PUH - 5
30A
30A
50A
NV50-CP
NV50-CP
NV50-CA
30A 30mA 0.1s or less
30A 30mA 0.1s or less
50A 100mA 0.1s or less
Note.
PU(H) - 7
PU(H) - 8
PU(H) - 10
PU(H) - 15
PU(H) - 20
50A
50A
NV50-CA
NV50-CA
NV60-CA
50A 100mA 0.1s or less
50A 100mA 0.1s or less
60A 100mA 0.1s or less
All electrical wiring must be
comply with local electrical
authority regulations.
60A
100A
125A
NV100-CP 100A 100mA 0.1s or less
NV225-CP 125A 100mA 0.1s or less
- 101 -
7. The putting condition of the belt.
(PE(H)-15,20 only)
1.Set the parallel angle of the fan and the motor pulley as shown in the table and figure 1 below.
2.Set the tension of the per one belt when the flexion load is within the range as shown in the figure 1
below at the proper flexion. (A=4.5mm)
3.Adjust the suitable tension after the belt sit properly across the pulley (after more 24-28 hours working).
When the new belt is used, adjust the suitable tension about the 1.3 times of the maximum value of the
flexion load.
4.Readjust the belt every 2,000 hours after the first adjustment.
Exchange the belt when the belt's surroundings length has expanded by 2% including the first expansion
of the belt. (about 1%)
(about 8,000 hours converted working time)
table
parallel angle
note
K ( )
pulley
pulley
10 or less gap of 3mm every 1m
K
Flexion load(W)
1.4 2.2kg
K
K
A
A=4.5mm
K
Figure1 Parallel degree of pulley
Figure2 Belt tension
8. Before starting the Trial run.
Check items
(1) Check to see wheter there are refrigerant leakage, and slack power or transmission cable.
(2) Conform that 500V megohmmeter shows 1.0M ohm or more between power supply terminal and
ground.
(3) Do not operate in the case of 1.0M ohm or less.
Note : Never carry out megger-ohm check over terminal control board.
Otherwise the control board would be broken.
(4) Check to see wheter both gas and liquid valves are fully opened.
Note : Be sure to tighten caps.
(5) Turn universal power supply at least 6 hours before gettig test run in order to current to crank heater.
If current-carrying hours are too short, it may result in a malfunction of compressor.
(6) Confirm operation of high-pressure switch.
If the two lead wires of the outdoor unit fan motor are disconnected from the connector and cooling
is performed, the high-pressure switch should operate and stop the unit after 5 to 10 minutes.
(7) Confirm that the fans of the indoor and outdoor unit rotate in the correct direction.
Change the power supply phase connections if it is rotating in the reverse direction.
Perform trial operation after completion of the above items.
- 102 -
INSTRUCTIONS FOR USE
1.Check points for operation.
Check the following points before you operate your air conditioner.
(1)Check that there is nothing blocking the flow of air from the air outlet into the air inlet.
Indoor unit
Inlet grille
Outlet grille
Ceiling
Ceiling
Obstacle blocking air outlet
Obstacle blocking air inlet
Outdoor unit
Obstacle blocking air inlet.
(2)Make sure the air conditioner is properly grounded by checking the ground terminal.
Ground
- 103 -
2.Caution for use.
Keep the following points in mind to safeguard against failures and breakdowns.
(1) This air conditioner does not restart within 3min.
after shut down.
3 Minutes
(These models have a crankcase heater in the
compressor. If the air conditioner is shut down
for a short time, please do not turn the power
switch to OFF, but turn the operation switch to OFF.)
Operation
Shutdown
(2) If the air conditioner is shut down by a power failure,
set the operation switch to OFF. When the power
is restored, normal air conditioner operation can
be resumed.
(3) Do not stick rods or other objects through the air
outlet during operation since this may result in
equipment damage or personal injury.
3.Maintenance.
For superior performance and lasting durability, please do not forget to conduct
proper and regular maintenance.
Warning
1.Do not wash the unit with water.
If washed with water, electrical shock may be caused.
2.Ahead of the maintenance.
For safety, turn the power source off before service work.
3.1 Cleaning the Air Filter
Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location.
Clean more regularly if the air filter gets very dirty.
If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate.
Failure to clean the air filter may result in equipment breakdown or malfunctions.
3.2 Cleaning panels
Clean dirt off front panel as follows.
Use a household neutral cleanser such as for dishes or
vegetables. Moisten a soft cloth with the cleanser, then wipe
lightly. Next,wipe three or four times with another soft cloth
moisten with water. Finally, wipe off all the remaining
cleanser with a soft cloth.
Fingermarks
Grease
Neutral
Cleanser
Moisten a soft cloth with the alcohol, then wipe off lightly.
Isopropyl alcohol is sold at stores as reagents in small
quantities.
Adhesive
Paste
Isopropyl
alcohol
Note:
Alcohol is highly combustible. Take extreme care
when handling. Also, do not use paint or adhesive
thinner.
- 104 -
3.3 Cleaning the Outdoor Unit Heat Exchanger
If you use your air conditioner for prolonged periods,
the outdoor heat exchanger will become dirty, impairing
its function and reducing air conditioners performance.
Consult your equipment supplier or air conditioning
contractor on how to clean the heat exchanger.
Heat
exchanger
4.When beginning to use air conditioner again.
Please turn on the power supply after confirming an following check is done and
abnormality is not found.
(1) It is confirmed that air inlet and outlet are not blocked.
(2) It is confirmed that the earth connection line does not come off.
The earth connection line is occasionally installed in the outdoor unit.
(3) It is confirmed that there are neither lifting , blocking , nor bending about the drain-hose.
Keep the power switch ON for more than 6hours before starting operation,
to operate the crankcase heater to drive refrigerant out of oil.
Do not turn the power supply OFF during seasons of heavy use.
Doing so can result in failure .
5.When the air conditioner is not to be used for a long time.
(1) If the air conditioner is not to be used for a long time due to a seasonal change etc.,run it for 4-5hours
with the air blowing until the inside is completely dry.
Failing to do so can result the growth of unhygienic, unhealthy mold in scattered areas throughout
the room.
(2) When it is not to be used for an extended time, keep the < power supply >turned OFF.
If the power supply is kept on, several watts or several tens of watts will be wasted.
Also, the accumulation of dust, etc., can result in fire.
5-1 In case of failure.
(1) Never remodel the air conditioner.
Consult your dealer for any repair service.
Improper repair work can result in water leakage, electric shock, fire, etc.
(2) If the poser breaker is frequently activated, get in touch with your dealer.
Leaving the unit as it is under such conditions can result in fire or failure.
(3) If the refrigeration gas blows out or leaks, stop the operation of the air conditioner.
(4) Thoroughly ventilate the room, and contact your dealer.
Leaving the unit as it is can result in accidents due to oxygen deficiency.
6.Transferring work, and construction
6-1 Transfer of installation.
(1) When removing and reinstalling the air conditioner when you enlarge your home, remodel, or move,
consult with your dealer in advance to ascertain the cost of the professional engineering work required
for transferring the installation.
(2) Please do not mix the one other than a specified refrigerant when you add the refrigerant (R-22) at the
installation and the transferring.
(3) When moving or reinstalling the air conditioner, consult with your dealer.
Defective installation can result in electric shock, fire, etc.
- 105 -
6-2 Place for installation.
Please do not use the unit in the following places.
(1) Place where a lot of oil (The machine oil is contained), moistures, and dust exist.
(2) Place where a lot of salinities such as beach districts exists.
(3) Place where sulfur gas, volatile gas, and corroded gas are filled.
(4) Place where acid solution is frequently used.
(5) Place where special spray is frequently used.
(6) Hot spring zone.
(7) Never machine (high cycle welding machine etc.) generating highcycle.
(8) Place where ventilation entrance of outdoor units is closed by snowfall.
(9) The unit must be installed on stable, level surface.
The main body might corrode when the unit is used in such a place, the refrigerant leak, the performance of
the unit decrease remarkably, and it cause the damage of parts of the unit.
6-3 Regarding electric work.
(1) The electrical work must be undertaken by a person who is qualified as an electric engineer according to
the (technical standard respecting electrical installation), (internal wiring rules), and the installation
instruction manual with the absolute use of exclusive circuits.
(2) Please install a special power supply in the power supply.
(3) Please install the earth connection for the electric shock prevention.
(4) Never connect the grounding wire to a gas pipe, water pipe, arrester, or telephone grounding wires.
For details, consult with your dealer.
(5) In some types of installation sites, the installation of an earth leakage breaker is mandatory. For details,
consult with your dealer.
(6) The breaker and the fuse must use the one of correct capacity.
6-4 Conseration of the noise.
(1) Take sufficient measures against noise when installing the air conditioners at hospitals or
communication-related businesses.
(2) If the air conditioner is used in any of the above-mentioned environments, frequent operational failure
can be excepted.
It is advisable to avoid these type of installation sites.
For further details, consult with your dealer.
(3) Choose a place where cool or warm air and noise from the outdoor air outlet of the air conditioner do
not inconvenience the neighbours.
(4) If any alien object is placed near the air outlet of the unit, decreased performance and increased noise
can result.
Avoid placing any obstacles adjacent to the air outlet.
(5) If the air conditioner produces any abnormal sound, consult with your dealer.
6-5 Disposing of the unit.
When you need to dispose of the unit, consult your dealer.
If pipes are removed incorrectly, refrigerant (fluorocarbon gas) may blow out and come into contact with
your skin, causing injury.
Releasing refrigerant into the atmosphere also damages the environments.
6-6 Maintenance and inspection.
(1) If the air conditioner is used throughout several seasons, the insides can get dirty, reducing the
performance.
(2) Depending upon the conditions of usage, foul odours can be generated and drainage can deteriorate
due to dust and dirt, etc.
- 106 -
7.Trouble shooting
Before you ask for repair service, check the following points:
Cause
Troubleshooting
State of Machine
Press the [ON/OFF] button after power restoration.
Power failure.
The power supply is turned OFF.
Turn the power supply ON.
Replace fuse.
It does not run.
The fuse in the power supply is gone.
The earth leakage breaker is gone.
Improper temperature adjustment.
Put in the earth leakage breaker.
Air flows out but it does not cool or heat
enough.
After checking the set temperature.
Clean up the filter.
The filter is filled with dust and dirt.
There are some obstacles at the air inlet and
outlet of the units.
Remove.
Windows and doors are open.
Insufficient refrigerant charge.
Close.
Contact with your installing contractor.
Wait for a while.
Cool or warm air does not come out.
The restart-preventing circuit is in operation for
3 minutes.
(To protect the compressor, a 3-minute restart-
preventing circuit is built into the unit.
Therefore, there are occasions sometimes when
the compressor does not start running immediately.
There are cases when it does not run for as long
as 3 minutes.)
Wait for a while.
(Heating operation starts after ending defrosting
operation.)
Indoor unit operation was started anew during
the heating and defrosting operation.
(5 10 HP only)
The set temperature of thermostat is
excessively high for cooling.
excessively low for heating. (PEH only)
For temperature control,
decrease the set temperature at cooling.
increase the set temperature at heating. (PEH only)
Fan runs but compressor do not run.
The room temperature is
excessively low for cooling.
Can not be operated as it is out of temperature
control range.
excessively high for heating. (PEH only)
Fan runs but stops immediately.
Air outlet and inlet are blocked.
Remove blocking matter.
Fogged white steam is discharged from
the indoor unit.
When the indoor temperature and humidity are It is not a breakdown.
high, such a phenomenon is occasionally had
at the beginning of system operation.
Please use as it is.
Water or steam is discharged from the
outdoor unit.
At cooling, water which places to cooling piping It is not a breakdown.
and piping connection part drops.
When heating, water which places to the heat
exchanger drops. (PEH only)
Please use as it is.
On heating, the air flow stops although a set
temperature is not reached. (PEH only)
Frost adheres to the outdoor coil when the
temperature on the outside is low and humidity Please use as it is.
is high. This frost is melted.
It is not a breakdown.
- 107 -
HOW TO OPERATE (OPTION PAC-204RC)
Display section
G
B
C
H
A
A
B
[Current/start/ending time] Display
Operation mode
Displays the status of operation.
D F
C
[Checking] Display
This displays indication when some abnormality
occurs in the unit.
E
D
E
F
[Set temperature] Display
Displays the set temperature.
[Operation] Lamp
Lights up during operation, goes off during stop.
[Room temperature] Display
Displays the temperature of the air sucked in
during operation.
G [Fan speed] Display
This displays indication High-speed or Low-speed.
H [Key lock] Display
This display indication during key lock function active.
For purposes of explanation, all the displays on this page are shown
in their lit condition. This configuration does not occur in the actual
unit.
Before starting operation
* Make sure that the power supply is turned ON before use. (Keep the power supply turned ON at all times
when the air conditioner is in use. Use of the unit without power can result in compressor failure.)
Warning:
Check and confirm the power circuit before use. For the contents, refer to the previously described chapter
[Crucial points to be observedfor safety].
1-1 ON / OFF
A
Start an operation
Press the [ON/OFF] button
Operation lamp lights up and operation starts.
1
Stop an operation
Press the [ON/OFF] button again
Operation lamp goes off and operation stops.
* Once the buttons have been set, pressing of the [ON/OFF] button
only can repeat the same operation thereafter.
* During operation, the operation lamp above the [ON/OFF] button
lights up.
A
Operation lamp
Caution:
Even if the operation button is pressed immediately after the operation is once stopped, operation is not
restarted for about 3 minutes. This function protects the machine. It automatically starts operation after the
lapse of approximately 3 minutes.
- 108 -
1-2 Selecting operation
When selecting operation
A
Press the [MODE] button
Consecutive press of the [MODE] button switches the operation
over to "FAN", "COOL", "HEAT" and
of operation,check the display.
"AUTO". For the contents
For fan
Press the [MODE] button and bring up the "FAN"
display.
1
* The fan operation functions to circulate the air in the room.
* The temperature of the room cannot be set by fan operation.
Caution:
Never expose your body directly to cool air for a long time.
Excessive exposure to cool air is bad for your health, and
should therefore be avoided.
A
Operation mode display
For cooling
Press the [MODE] button and bring up the "COOL" display.
For heating
Press the [MODE] button and bring up the "HEAT" display.
Caution:
* When the air conditioner is used together with burners, thoroughly
ventilate the area. Insufficient ventilation can result in accidents due to oxygen deficiency.
* Never place a burner at a place where it is exposed to the airflow from the air conditioner.
Doing so can result in imperfect combustion of the burner.
For Auto change over
Press the [MODE]button and bring up the "AUTO" display
This function is special order. Please consult your local Mitsubishi Electric Sales office for application
advice on this function.
Because this function need low ambient cooling parts as option.
Indoor temperature can be set within the following range.
Indoor temperature setting range:17~30ËšC
1-3 Room temperature adjustment
To change room temperature
A
1
Press the room temperature button and set the room tempe-
rature of your choice.
Press
or
once changes the setting by 1 .
If the pressing is continued, the setting continues to change by 1 .
1
* Indoor temperature can be set within the following range.
Cooling
Heating
19 30
17 28
* It is impossible to set the room temperature by the air-blow
operation
1 Press
and
together, the unit of temperature
A
Set temperature display and room
temperature display
change " " (degree-centigrade) and " " (degree-Fahren-
heit)
F
- 109 -
1-4 Time setting
Clock key
A
B
1 Press the key one time will activate set clock mode.
Press the key again will disable set clock mode.
2 4
Under set clock mode, the real time clock and present day
setting can be changed by pressing Day key, Hour key or
Minute key.
2
3
7-Days timer key
1 There are two keys for timer. One is ON Timer, another is
Off Timer.
5
Press the key one time will activate set timer mode.
Press the key again will disable set timer mode.
1
4
2 4
Under set timer mode, the 7-days timer setting can be
changed by pressing Day key, Hour key or Minute key.
A
B
Current time display
Timer Hold/Resume display
Day key
2
During set clock mode or set timer mode, press the key will change the day setting.
Hour key
3
During set clock mode or set timer mode, press the key will change the hour setting.
Minute key
4
During set clock mode or set timer mode, press the key will change the minute setting.
Timer Hold/Resume key
If 7-days timer is set, then the word "Timer Active" is displayed.
5
To clear all the timers setting, Press and hold the hold key until the word "Timer Active" is not displayed.
To resume the timer setting after timers have been held, press and hold the key until the word " Timer
Active" is displayed.
1-5 Other function
Key lock
1
Press the "MINUTE" key three times consecutively,
"KEY LOCK" symbol will appear on LCD screen.
At this time, only "ON-OFF" key is valid.
This function purpose is protect from mischief of child etc.
To cancel the key lock function, Please press "MINUTE" key
three times consecutively again.
Test run
2
Press the "TEST" key two times consecutively.
The unit will run and finished automatically after two hours.
2
1
- 110 -
1-6.Trouble shooting
Before you ask for repair service, check the following points:
Cause
Troubleshooting
State of Machine
It does not run
Remote Controller
"ON-OFF "display is
not lit up
No display appears
even when the [ON/
OFF] button is
pressed.
Press the [ON/OFF] button after power restoration.
Power failure
The power supply is turned OFF.
Turn the power supply ON.
Replace fuse.
The fuse in the power supply is gone.
The earth leakage breaker is gone.
Put in the earth leakage breaker.
After checking the set temperature and inlet
temperature on the liquid crystal display, refer to
[To change room temperature] on page 107, and
operate the adjustment button.
Air flows out but it
does not cool
enough or heat
enough.
The liquid crystal
display shows that
it is in the state of
operation.
Improper temperature adjustment.
Clean up the filter.
The filter is filled with dust and dirt.
There are some obstacles at the air inlet and
outlet of the indoor and outdoor units.
Remove.
Close.
Windows and doors are open.
Wait for a while.
(To protect the compressor, a 3-minute restart-
preventing circuit is built into the indoor unit.
Therefore, there are occasions sometimes when
the compressor does not start running immedi-
ately. There are cases when it does not run for as
long as 3 minutes.)
The liquid crystal
display shows that
it is in operation.
The restart-preventing circuit is in operation for
3 minutes.
Cool air or warm air
does not come out.
Wait for a while.
(Heating operation starts after ending defrosting
operation.)
Indoor unit operation was started anew during
the heating and defrosting operation.
(5 10 HP only)
Can not change to
Heat mode when
DIP switch1 is not correct
Change the DIP switch off to on.
(Refer to Instruction manual for Installation.)
Can not change
to Heat mode
press the "MODE" key.
Error Display
Indicate
E01
Cause
Troubleshooting
Automatically reset to restoration error.
Room temperature sensor open.
E02
Room temperature sensor short.
Automatically reset to restoration error.
Push the On-Off switch.(OFF to ON)
E03
Error input from Indoor unit or
Outdoor unit.
- 111 -
SPECIFICATION GUIDELINES
Air to air reverse cycle split air conditioning system.
The systems shall operate at out door ambient temperatures as high as
.
The system shall have a total cooling capacity of
at DB and
kW or greater with an indoor air quantity of
L/s
WB entering indoor coil temperature with a
temperature entering the outdoor coil.
The system shall have a sensible heat capacity of
kW or greater with a room DB temperature of
.
The total heating capacity (without electric element heaters) shall be kW or greater at
WB outdoor air conditions, with
DB,
of indoor air entering indoor coil at
DB.
The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be
equipped with a crankcase heater.
Coils shall be of non-ferrous construction with mechanically bonded aluminum plate fins Outdoor coils
shall be made, of 9.52mm OD, 0.35mm thick formless copper tubes mechanically bonded to 0.12mm
thick aluminum plate fins.
Face area of the coil shall not be less than
3.3 MPa pressure. The indoor coil face area shall be not less than
m2 The coil shall be factory pressure and leak tested at
m2
.
Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to
ensure smooth airflow and shall discharge vertically and be direct driven by a weatherproof three
phase squirrel cage
kW induction motor.
The system shall be factory wired and all electrical wiring must comply with the Local wiring code (Controls
and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal
and current sensitive overload devices.
An automatic defrost control shall be included to accomplish defrosting (only if required) every
for a period of minutes.
minutes
High pressure switch (pre-set) shall be factory installed.
The enclosure is weatherproof casing constructed of phosphatized, zinc coated steel with powder coating.
(OUTDOOR UNIT)
The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall
be located in the pillars. (OUTDOOR UNIT)
The unit shall have a drain connection provided (25mm BSP:male thread).
The enclosure shall have openings provided for power connections.
Access for both service and installation shall be provided to compressors, control wiring, and fans.
Side panels and top panels shall be removable for easy service access.
)
mm (INDOOR UNIT
The unit maximum dimensions shall be : height:
: height:
mm, width:
mm, width:
mm and depth:
mm and depth:
mm (OUTDOOR UNIT)
Due to continuous product development, these guidelines are subject to change.
- 112 -
MEMO
- 113 -
DATA BOOK PE,PEH
MITSUBISHI ELECTRIC CORPORATION
HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100-0005,TELEX J24532 CABLE MELCO TOKYO
New publication effective Dec. 1999.
Specifications subject to change without notice.
Issuued in Dec. 1999 MEE99K014
|
Mitsubishi Electronics P500ymf C User Manual
Philips Sc486 Dectsbc User Manual
Precisionaire 425t Panel User Manual
Radio Shack 23 039 User Manual
Ricoh Aficio Mp C3000 User Manual
Sanyo Stb0810c1 User Manual
Sanyo Uf553450l User Manual
Soleus Air Soleusair Sg Ttw 12hc 26 User Manual
Tanaka Pf 2600 User Manual
Tru Test 2 J User Manual