		 AIR-COOLED ROOFTOP PACKAGED AIR CONDITIONERS   
					Series   
					: 
					COOLING ONLY PR-5,8,10,15,20   
					: 
					HEAT PUMP   
					PRH-5,8,10,15,20   
					PRH-5,8,10,15,20-L   
					DATA BOOK   
				SAFETY FOR USE   
					Before conducting installation work, please read this ''SAFETY FOR USE'' carefully   
					for correct installation.   
					Since the caution items shown here contain important description relative to safety, please   
					observe them without fail.   
					Erroneous handling gives a high possibility to induce serious results such as   
					death or heavy injury.   
					Warning   
					Erroneous handling may induce serious injury depending on the situation.   
					Caution   
					After reading, please keep it with you together the Instruction Manual, and read it again at the   
					movement of the unit.   
					Warning   
					Never repair the unit, remodel or transfer it to   
					another site by yourself.   
					If they are performed improperly, water leakage, electric   
					shock or fire may result. If you need to have the unit   
					repaired or moved, consult your dealer.   
					The unit should not be installed by the user.   
					If the unit is installed improperly, explosion, water   
					leakage, electric shock or fire may be result.   
					Consult your dealer or specialist subcontractor for   
					repair and movement.   
					For installation, conduct the work correctly by   
					following the Installation Manual.   
					Improper installation may cause a fire, electrical shock   
					or water leakage.   
					Use only the specified refrigerant (R-22) to charge   
					the refrigerant circuit.   
					Do not mix it with any other refrigerant and do not allow   
					air to remain in the circuit.   
					Air enclosed in the circuit can cause high pressure resulting   
					in a rupture and other hazards.   
					Install the unit on a spot sufficiently durable against   
					the unit weight.   
					Insufficient durability can cause an injury by the falling   
					down of unit.   
					After completing installation work, make sure that   
					refrigerant gas has not leaked.   
					If refrigerant gas has leaked and exposed to fan heater,   
					stove, oven and so on, it may generate noxious gases.   
					All electric work must be performed by licensed   
					technician, according to local regulations and the   
					instructions given in this manual.   
					The units should be powered by dedicated power lines.   
					Power lines with insufficient capacity or improper   
					electrical work may result in electric shock or fire.   
					Take a proper measure to suppress the critical   
					concentration of refrigerant if leaked when   
					installing the unit in a small room.   
					The limit density is made not to be exceeded even if the   
					refrigerant leaks by any chance.   
					You are necessary to ventilation measures to prevent   
					the accident. If the refrigerant leaks, hypoxia accident   
					may caused.   
					Use only the specified cables for wiring.   
					The connections must be made secured without   
					tension the terminals.   
					Improper connection or fastening can cause a fire or   
					electrical shock.   
					For the countermeasure to be taken, consult your   
					dealer.   
					The unit should be installed according to the   
					instructions in order to minimize the risk of damage   
					from earthquakes, typhoons or strong winds.   
					Improper installation work can cause an injury by the   
					falling down of the unit.   
					The terminal block cover of unit must be firmly   
					attached to prevent entry of dust and moisture.   
					Improper mounting of the cover cause electric shock or   
					fire.   
					Use only optional parts authorised by Mitsubishi   
					Electric.   
					If the accessories are installed improperly, water   
					leakage, electric shock or fire may result.   
					Ask your dealer or an authorised company to install   
					them.   
					The unit must be installed on stable, flat surface,   
					in a place where there is no accumulation of snow,   
					leaves or rubbish.   
					The unit should be installed in a location where air   
					and noise emitted by the unit will not disturb the   
					neighbors.   
					If the unit is loosely mounted, it may fall, and cause injury.   
					- 2 -   
				Caution   
					Arrange the configuration of wiring not to bring up   
					Refrain from installing the unit in an area where   
					flammable gas can accumulate around the unit.   
					If the flammable gas can accumulate around the unit, an   
					explosion can occur.   
					When the unit is installed at telecommunication   
					centers or hospitals, take a proper provision   
					against noise.   
					The erroneous operation of air conditioner may be   
					induced by inverter equipment, independent power   
					device, medical equipment or communication   
					equipment.   
					While the erroneous operation of medical equipment or   
					communication equipment may caused by the air   
					conditioner.   
					the panel and terminal cover, and fasten the panel   
					and terminal cover securely.   
					The poor mounting of the panel or terminal cover may   
					cause the heat generation of the terminal connection,   
					a fire or electrical shock.   
					Do not wash the unit with water.   
					If washed with water, electrical shock may be caused.   
					Do not handle the switch with wet hands.   
					Otherwise electrical shock can be resulted.   
					Be very careful on handling the unit.   
					When carrying in outdoor unit, be sure to support it at   
					four points.   
					Carrying in and lifting with 3-point support may make   
					outdoor unit unstable, resulting in a fall of it.   
					The unit should not be carried by only one person if it is   
					more than 20kg.   
					For special use as for foods, animals/plants,   
					precision equipment or art objects, the applicability   
					should be confirmed beforehand.   
					As the use for the applications other than that   
					designed originally may result in the deterioration of the   
					quality. Consult your dealer in this regard.   
					Do not use the unit under a special atmosphere.   
					Installing the unit at the following places may cause a   
					trouble, a place where much machine oil, salt sonnet,   
					humidity or dust, spa district, a place full of sulfur gas,   
					volatile gas, or corrosive gas, a place near high   
					frequency processing machine.   
					Thermal insulation of the drain pipes is necessary   
					prevent dew condensation.   
					If the drain pipes are not properly insulated,   
					condensation will result and drip on ceiling, floor or other   
					possessions.   
					The drain piping must process by surely,and insulate   
					the drain piping not to be dewy.   
					Some units use PP bands for packing.   
					Do not use any PP band for delivery purpose.   
					Do not touch the heat exchanger fins with your bear   
					hands.   
					Doing so may cut your hands.   
					Be sure to safely dispose the packaging materials.   
					Packaging materials, such as catches and other metal   
					or wooden parts, may cause stabs or other injuries.   
					Tear off and discard plastic packing bags so that   
					children will not play any of them.   
					If children play with a plastic bag which was not torn off,   
					it may cause a risk of suffocation.   
					The base and attachments of the unit should be   
					periodically checked for looseness, cracks or other   
					damage.   
					If such defects are left uncorrected, the unit may fall and   
					cause personal injury or property damage.   
					When the room humidity exceeds 80% or when the   
					drain pipe is clogged, water may drip from the indoor   
					unit. The outdoor unit produces condensation during the   
					heating operation.   
					Make sure to provide drainage around the outdoor unit if   
					such condensation is likely to cause damage.   
					Turn on the main power switch more than 6 hours   
					before starting operation.   
					Do not turn the main power switch OFF during seasons   
					of heavy use, doing so can result In failure.   
					Do not touch the compressor or refrigerant piping   
					without wearing glove on your hands.   
					Touching directly such part can cause a burn or   
					frostbite as it becomes high or low temperature   
					according to the refrigerant state.   
					Do not touch the metal edges inside the unit   
					without wearing glove on your hands.   
					Touching directly it may injure your hands.   
					Do not remove the front panel or the fan guard from   
					the unit when it is running.   
					You could be injured if you touch rotating, hot or high-   
					voltage parts.   
					Install drain piping according to this Installation   
					Manual to ensure proper drainage.   
					Place thermal insulation on the pipes to prevent   
					condensation.   
					Improper drain piping may cause water leakage and   
					damage to furniture or other possessions.   
					The unit must be properly earth connected.   
					Do not connect the earth wire to gas pipe, city water   
					pipe, lightning rod or telephone earth wire.   
					Improper earth connection may cause electrical shock.   
					When installing at a watery place, provide an   
					electric leak breaker.   
					Failure to mount the electric leak breaker may cause   
					electrical shock.   
					Use breaker or fuse with proper capacity.   
					Make sure that there is a main power switch.   
					Using a wire or a copper wire instead of proper capacity   
					of fuse can cause fire or trouble.   
					Other appliances connected to the same line could cause   
					an overload.   
					Do not operate the air conditioner without the air   
					filter set place.   
					Dust may accumulate, and cause a failure.   
					At emergency (if you smell something burning), stop   
					operation and turn the power source switch off.   
					Continuing the operation without eliminating the   
					emergency state may cause a machine trouble, fire, or   
					electrical shock.   
					For the power lines, use standard cables of   
					sufficient current capacity.   
					Otherwise, current leakage, overheating or fire may   
					occur.   
					After stopping operation, be sure to wait for five   
					minutes before turning off the main power switch.   
					Otherwise, water leakage or unit failure may occur.   
					When installing the power lines, do not apply   
					tension to the cables.   
					The tighten or loosen the connections may cause generate   
					heat and cause fire.   
					- 3 -   
				A COMPLETE LINE UP   
					PR-5YC   
					PRH-5YA   
					PRH-5YA-L   
					(PRH ONLY)   
					Cooling capacity Heatling capacity   
					14,000 kcal/h   
					55,600 BTU/h   
					16.3 kW   
					13,000 kcal/h   
					51,600 BTU/h   
					15.1 kW   
					PR-8YC   
					PRH-8YA   
					PRH-8YA-L   
					(PRH ONLY)   
					Heatling capacity   
					19,800 kcal/h   
					78,600 BTU/h   
					23 kW   
					Cooling capacity   
					20,500 kcal/h   
					81,300 BTU/h   
					23.8 kW   
					PR-10YC   
					PRH-10YA   
					PRH-10YA-L   
					(PRH ONLY)   
					Cooling capacity Heatling capacity   
					25,500 kcal/h   
					101,200 BTU/h   
					29.7 kW   
					27,500 kcal/h   
					109,100 BTU/h   
					32 kW   
					PR-15YC   
					PRH-15YA   
					PRH-15YA-L   
					(PRH ONLY)   
					Heatling capacity   
					39,100 kcal/h   
					155,100 BTU/h   
					45.5 kW   
					Cooling capacity   
					39,800 kcal/h   
					157,900 BTU/h   
					46.3 kW   
					PR-20YC   
					PRH-20YA   
					PRH-20YA-L   
					(PRH ONLY)   
					Heatling capacity   
					52,600 kcal/h   
					208,700 BTU/h   
					61.2 kW   
					Cooling capacity   
					52,300 kcal/h   
					207,500 BTU/h   
					60.8 kW   
					- 4 -   
				FEATURES   
					High Sensible Cooling Capacity   
					Labor Saving Installation   
					The sensible cooling capacity has been significantly   
					improved through optimized heat exchanger design.   
					Because of the single unit configuration, all   
					refrigeration work can be omitted. The unit operation   
					can commence immediately after connection to the   
					power supply, drain piping, ducting and control   
					system.   
					Comfort Heating   
					The PRH series are designed to provide effective heating   
					even when the outside temperature is down to 0˚C. The   
					PRH-L series are designed to provide effective heating   
					even when the outside temperature is down to -10˚C.In   
					addition, the twin circuit models, PRH-15,20YA,   
					PRH-15,20YA-L are provided with control features that   
					prevents both refrigeration circuits defrosting at the same   
					time. This ensures constant comfort conditions during   
					defrost and varying loads.   
					Low Ambient Cooling   
					In applications with relatively high internal loads,   
					there may be a requirement for all series to operate   
					on cooling at low ambient conditions. An optional   
					accessory is available to maintain the refrigeration   
					circuit in balance at outdoor temperatures as low as   
					0˚C (PRH only).In case of PR,PRH-L is -5˚C.   
					Please consult your local Mitsubishi Electric Sales   
					office for application advice on this accessory.   
					Highly Efficient Operation   
					The EER (Energy Efficiency Ratio) on these models is   
					greatly improved by revised design specifications and by   
					being manufactured stringently to Mitsubishi Electric   
					high quality standards.   
					Wide Electrical Control Capability   
					All series may be ordered in either of two control   
					configurations.   
					The factory standard is for provision of a 24 volt   
					terminal block to enable a field wired control of the   
					contractors choice to be connected.   
					Flexibility of Supply Air Delivery   
					Alternatively, for models PR-5-10YC,PRH-5-10YA,   
					PRH-5-10YA-L the intelligent "K" series remote   
					control system may be ordered. The K control   
					utilizes a microprocessor and includes liquid crystal   
					display with touch pad for adjustment of control   
					parameters.   
					These options give the flexibility to enable   
					connection to Building Management Systems,   
					smoke spill cycles, economy cycles, remote   
					monitoring etc.   
					All series feature belt driven Supply Air fans enabling   
					accurate matching of actual airflow rates to the specified   
					quantities. Accurate commissioning is assisted by the   
					capability to exchange pulleys and belts if necessary to   
					achieve the desired air balance.   
					Please consult your local Mitsubishi Electric Sales   
					office for application advice on these controls.   
					- 5 -   
				DESCRIPTIONS   
					compressors, air-cooled condensers, evaporator   
					MITSUBISHI ELECTRIC Rooftop Air Conditioners   
					Series PR,PRH,RPH-L are available in a wide   
					range of sizes and models to enable the designer   
					to select the best model for each application.   
					The complete range has been designed for   
					outdoor installation, and the units are provided with   
					the latest technological features to ensure   
					economical, reliable and comfortable ducted type   
					air conditioning.   
					fans, condenser fans and auxiliary and control   
					equipment, completely packaged in a water-proof   
					enclosure.   
					With the development of all series demands for   
					such features as light weight, compactness,   
					increased capacity, appropriate static pressure , air   
					flow control, and having flexibility of inter-facing   
					energy saving electronic controls Mitsubishi   
					Electric have met market expectations.   
					All series units are completely assembled, wired   
					and strictly tested at the factory. They consist of a   
					MECHANICAL SPECIFICATIONS   
					General   
					Condenser Coils   
					All units are factory assembled, piped, internally   
					wired and fully charged with R-22. They are also   
					tested and checked under a strict quality control   
					system in the factory. All units are designed for   
					outdoor rooftop or ground level installation. Exterior   
					surfaces of all units are phosphatized, zinc-coated   
					steel with acrylic resin primer and ivory white baked   
					enamel finish.   
					Unnecessary power input due to higher   
					discharge pressure is avoided by high   
					performance designs of cross-finned coils.   
					Condenser coils are made of 9.52mm OD,   
					0.35mm thick seamless copper tubes   
					mechanically bonded to 0.12mm thick aluminium   
					plate fins. Each coil is factory pressure and leak   
					tested at 3.3MPa.   
					Refrigeration Controls   
					Evaporator Fans   
					Refrigeration controls include condenser fan,   
					evaporator fan and compressor contactor. Each   
					circuit of the unit has a separate set of refrigeration   
					controls. PR, PRH,PRH-L-15,20 units have two   
					independent circuits.   
					Belt-drive, forward curved, centrifugal type fans   
					made of galvanized steel are used to deliver an   
					accurate airflow at low noise level.   
					Condenser Fan   
					This direct-drive propeller fan is dynamically   
					balanced, to ensure smooth airflow. A weather-   
					proof three-phase squirrel cage induction motor   
					is used to drive the condenser fan.   
					Compressors   
					All units have high efficiency type hermetic line   
					starting compressors. Compressors are equipped   
					with thermal overload protector, overcurrent relay   
					and high pressure protection controls. Crankcase   
					heaters are standard .   
					Evaporator Coils   
					Highly efficient cross-finned coils are applied to   
					provide a larger cooling capacity with low air speed   
					on the coil. Coils are made of 9.52mm OD and   
					0.35mm thick seamless copper tubing   
					mechanically bonded to 0.12mm thick aluminium   
					fins and are factory leak tested at a pressure of   
					3.3MPa. They are provided with strainers attached   
					to the capillary tubes to further ensure a clean   
					system.   
					- 6-   
				TYPICAL INSTALLATION EXAMPLE   
					PR   
					PRH   
					PRH-L   
					- 7-   
				SPECIFICATIONS   
					PR-5YC   
					PR-8YC   
					PR-10YC   
					PR-15YC   
					PR-20YC   
					PRH-5YA   
					PRH-8YA   
					PRH-10YA   
					PRH-15YA PRH-20YA   
					ITEM   
					PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L   
					kW   
					BTU/h   
					kcal/h   
					kW   
					16.3   
					55,600   
					14,000   
					13   
					23.8   
					81,300   
					20,500   
					19.7   
					29.7   
					101,200   
					25,500   
					25.3   
					46.3   
					157,900   
					39,800   
					38.4   
					60.8   
					207,500   
					52,300   
					50.2   
					TOTAL COOLING CAPACITY   
					(GROSS)   
					SENSIBLE COOLING CAPACITY   
					(GROSS)   
					BTU/h   
					kcal/h   
					kW   
					44,400   
					11,200   
					15.1   
					67,100   
					16,900   
					23   
					86,500   
					21,800   
					32   
					130,900   
					33,000   
					45.5   
					171,400   
					43,200   
					61.2   
					TOTALHEATING CAPACITY   
					(GROSS)   
					(PRH-YA,PRH-YA-L ONLY)   
					BTU/h   
					kcal/h   
					% 
					51,600   
					13,000   
					78,600   
					19,800   
					0-100   
					109,100   
					27,500   
					155,100   
					39,100   
					208,700   
					52,600   
					CAPACITY STEPS   
					REFRIGERANT   
					0-50-100   
					R22(FACTORY CHARGED)   
					CAPILLARY TUBE   
					REFRIGERANT CONTROL   
					EXTERNAR FINISH   
					COLOR(MUNSELL NO.)   
					HEIGHT   
					ACRYLIC RESIN COATING   
					MUNSELL 5Y8/1   
					mm   
					mm   
					mm   
					kg   
					1,000   
					1,200   
					1,990   
					1,840   
					DIMENSION   
					WIDTH   
					DEPTH   
					1,000   
					299   
					1,300   
					1,600   
					393   
					NET WEIGHT   
					COMPRESSOR   
					MOTOR OUTPUT   
					INDOOR COIL   
					FAN   
					413   
					698   
					729   
					HERMETIC LINE START(RECIPROCATING)   
					kW   
					3.73   
					5.6   
					7.5   
					2 
					X 
					5.6   
					2 
					X 
					7.5   
					CROSS FINCOIL   
					CENTRIFUGAL (GALVANIZED STEEL) - BELT DRIVE   
					THREE PHASE CAGE INDUCTION MOTOR   
					FAN MOTOR   
					FAN MOTOR OUTPUT   
					kW   
					CMM   
					CFM   
					L/S   
					0.75   
					54   
					1.1   
					84   
					1.5   
					2.2   
					168   
					3 
					100   
					190   
					NOMINAL AIR FLOW   
					1,907   
					900   
					10   
					2,967   
					1,400   
					10   
					3,532   
					5,934   
					2,800   
					20   
					6,711   
					3,160   
					20   
					1,660   
					EXTERNAL STATIC   
					PRESSURE   
					mmAq   
					Pa   
					10   
					100   
					100   
					100   
					200   
					200   
					OUTDOOR COIL   
					FAN   
					CROSS FIN COIL   
					PROPELLER -DIRECT DRIVE   
					FAN MOTOR   
					THREE PHASE CAGE INDUCTION MOTOR   
					X 
					X 
					FANMOTOR OUTPUT   
					kW   
					CMM   
					CFM   
					L/S   
					0.15   
					95   
					0.35   
					185   
					0.35   
					185   
					2 
					0.35   
					185   
					2 
					0.35   
					185   
					2 
					X 
					2 
					X 
					NOMINAL AIR FLOW   
					X 
					X 
					3,355   
					1,583   
					6,534   
					3,083   
					6,534   
					3,083   
					25.4   
					2 
					6,534   
					3,083   
					2 
					6,534   
					3,083   
					2 
					2 
					X 
					X 
					DRAIN CONNECTION   
					mm   
					HIGHPRESSURE SWITCH,FUSE   
					PROTECTION DEVICES   
					OVER CURRENT RELAY (COMP.& INDOOR FAN,OUTDOOR FAN)   
					INTERNAL THERMOSTAT (COMP. & OUTDOOR FAN)   
					ANTISHORT-CYCLE TIMER,FREEZE & FROST PROTECTOR   
					NOTE 1. NOMINAL COOLING & HEATING CAPACITIES ARE BASED FOLLOWING CONDITIONS.   
					COOLING : INDOOR:27˚CDB, 19˚C WB ; OUTDOOR:35˚CDB.   
					HEATING : INDOOR:21˚CDB ; OUTDOOR:7DB, 6˚C WB.   
					2. CAPACITIES ARE GROSS CAPACITIES WHICH DO NOT INCLUDE A DEDUCTION FOR EVAPORATOR   
					FAN MOTOR HEAT.   
					- 8 -   
				ELECTRICAL DATA   
					Cooling   
					PR-5YC   
					PR-8YC   
					PR-10YC   
					PR-15YC   
					PR-20YC   
					PRH-5YA   
					PRH-8YA   
					PRH-10YA   
					PRH-15YA   
					PRH-20YA   
					VOLT   
					ITEM   
					PRH-5YA-L PRH-8YA-L   
					PRH-10YA-L PRH-15YA-L PRH-20YA-L   
					TOTAL INPUT   
					kW   
					A 
					5.4   
					10.3   
					73   
					8.3   
					15.9   
					73   
					11.4   
					20.2   
					79   
					16.8   
					30.8   
					76   
					22.7   
					39.1   
					81   
					TOTAL RUNCURRENT   
					POWER FACTOR   
					START CURRENT   
					% 
					A 
					62   
					87   
					100   
					115   
					135   
					415V COMPRESSOR INPUT   
					RUNCURRENT   
					kW   
					A 
					3.92   
					7.44   
					1.24   
					2.26   
					0.24   
					0.6   
					6.46   
					11.70   
					1.30   
					2.90   
					0.54   
					1.3   
					9.22   
					15.62   
					1.64   
					3.28   
					0.54   
					1.3   
					2 X 6.55   
					2 X 11.74   
					2.62   
					2 X9.30   
					2 X15.22   
					3.02   
					I/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					4.72   
					6.06   
					O/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					2 X 0.54   
					2 X 1.3   
					2 X0.54   
					2 X 1.3   
					TOTAL INPUT   
					kW   
					A 
					5.4   
					11.2   
					73   
					8.3   
					17.3   
					73   
					11.4   
					21.9   
					79   
					16.8   
					33.6   
					76   
					22.7   
					42.6   
					81   
					TOTAL RUNCURRENT   
					POWER FACTOR   
					START CURRENT   
					% 
					A 
					68   
					95   
					109   
					126   
					147   
					380V COMPRESSOR INPUT   
					RUNCURRENT   
					kW   
					A 
					3.92   
					8.06   
					1.24   
					2.48   
					0.24   
					0.66   
					6.46   
					12.71   
					1.30   
					3.17   
					0.54   
					1.42   
					9.22   
					16.90   
					1.64   
					3.58   
					0.54   
					1.42   
					2 X 6.55   
					2 X 12.80   
					2.62   
					2 X9.30   
					2 X16.57   
					3.02   
					I/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					5.16   
					6.62   
					O/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					2 X 0.54   
					2 X 1.42   
					2 X0.54   
					2 X1.42   
					(PRH,PRH-L Only)   
					Heating   
					PRH-5YA   
					PRH-8YA   
					PRH-10YA   
					PRH-15YA   
					PRH-20YA   
					VOLT   
					ITEM   
					PRH-5YA-L PRH-8YA-L PRH-10YA-L PRH-15YA-L PRH-20YA-L   
					kW   
					A 
					4.8   
					9.8   
					68   
					7.0   
					14.1   
					69   
					9.6   
					18.2   
					73   
					14.4   
					27.2   
					74   
					19.3   
					34.8   
					77   
					TOTAL INPUT   
					TOTAL RUNCURRENT   
					POWER FACTOR   
					% 
					A 
					62   
					87   
					100   
					111   
					131   
					START CURRENT   
					415V COMPRESSOR INPUT   
					RUNCURRENT   
					kW   
					A 
					3.32   
					6.94   
					1.24   
					2.26   
					0.24   
					0.6   
					5.16   
					9.90   
					1.30   
					2.90   
					0.54   
					1.3   
					7.42   
					13.62   
					1.64   
					3.28   
					0.54   
					1.3   
					2 X5.35   
					2 X9.94   
					2.62   
					2 X7.60   
					2 X13.07   
					3.02   
					I/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					4.72   
					6.06   
					O/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					2 X0.54   
					2 X 1.3   
					2 X0.54   
					2 X 1.3   
					kW   
					A 
					4.8   
					10.7   
					68   
					7.0   
					15.4   
					69   
					9.6   
					20.0   
					73   
					14.4   
					29.6   
					74   
					19.3   
					38.1   
					77   
					TOTAL INPUT   
					TOTAL RUNCURRENT   
					POWER FACTOR   
					START CURRENT   
					% 
					A 
					68   
					95   
					109   
					121   
					143   
					380V COMPRESSOR INPUT   
					RUNCURRENT   
					kW   
					A 
					3.32   
					7.56   
					1.24   
					2.48   
					0.24   
					0.66   
					5.16   
					10.81   
					1.30   
					3.17   
					0.54   
					1.42   
					7.42   
					15.00   
					1.64   
					3.58   
					0.54   
					1.42   
					2 X5.35   
					2 X10.8   
					2.62   
					2 X7.60   
					2 X14.32   
					3.02   
					I/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					5.16   
					6.62   
					O/D FAN INPUT   
					RUNCURRENT   
					kW   
					A 
					2 X0.54   
					2 X1.42   
					2 X0.54   
					2 X1.42   
					- 9 -   
				CAPACITY TABLES   
					- 10 -   
				- 11 -   
				- 12 -   
				- 13 -   
				- 14 -   
				- 15 -   
				- 16 -   
				- 17 -   
				- 18 -   
				- 19 -   
				Operation range   
					PR-YC   
					Cooling   
					50   
					46   
					40   
					30   
					20   
					10   
					0 
					-10   
					10   
					15   
					20 2425   
					30   
					Indoor temp.(˚CWB)   
					PRH-YA   
					Heating   
					Cooling   
					50   
					46   
					15   
					40   
					10   
					5 
					30   
					20   
					10   
					0 
					- 5   
					0 
					-10   
					10   
					-10   
					10   
					15   
					20 2425   
					30   
					15   
					20   
					25 27 30   
					Indoor temp.(˚CWB)   
					Indoor temp.(˚CDB)   
					Heating   
					Cooling   
					PRH-YA-L   
					50   
					46   
					15   
					40   
					10   
					5 
					30   
					20   
					10   
					0 
					- 5   
					0 
					-10   
					10   
					-10   
					10   
					15   
					20 2425   
					30   
					15   
					20   
					25 27 30   
					Indoor temp.(˚CWB)   
					Indoor temp.(˚CDB)   
					- 20-   
				FAN PERFORMANCE   
					Airflow   
					PR-5YC   
					CMM   
					45   
					750   
					1230   
					139.7   
					5.5   
					165.1   
					6.5   
					B39   
					0.75   
					1330   
					139.7   
					5.5   
					50   
					55   
					60   
					PRH-5YA   
					PRH-5YA-L   
					L/S   
					830   
					1320   
					920   
					1450   
					1000   
					1450   
					FAN SPEED   
					rpm   
					PULLEYSIZE   
					mm   
					inch   
					127   
					5 
					139.7   
					5.5   
					139.7   
					5.5   
					(MOTOR SIDE)   
					Operation range   
					100   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					mm   
					inch   
					inch   
					kw   
					139.7   
					5.5   
					B36   
					0.75   
					1450   
					139.7   
					5.5   
					139.7   
					5.5   
					B37   
					0.75   
					1580   
					152.4   
					6 
					139.7   
					5.5   
					B37   
					0.75   
					1580   
					152.4   
					6 
					139.7   
					5.5   
					B40   
					1.1   
					1610   
					127   
					5 
					139.7   
					5.5   
					B39   
					1.1   
					1600   
					139.7   
					5.5   
					127   
					5 
					B39   
					1.1   
					- 
					- 
					- 
					Fan speed   
					MOTOR   
					(rpm)   
					700   
					600   
					500   
					400   
					300   
					200   
					100   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					200   
					152.4   
					6 
					External   
					static   
					pressure   
					(Pa)   
					1800   
					1700   
					B38   
					0.75   
					1450   
					139.7   
					5.5   
					139.7   
					5.5   
					B37   
					0.75   
					1610   
					127   
					5.0   
					114.3   
					4.5   
					B35   
					0.75   
					MOTOR   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					1600   
					1500   
					139.7   
					5.5   
					B40   
					1.1   
					- 
					114.3   
					4.5   
					B37   
					1.1   
					- 
					- 
					- 
					- 
					- 
					300   
					1400   
					MOTOR   
					1300   
					1200   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					1100   
					400   
					- 
					- 
					- 
					45   
					750   
					50   
					830   
					60   
					1000   
					(CMM)   
					( / s)   
					- 
					- 
					- 
					- 
					- 
					- 
					MOTOR   
					- 
					- 
					- 
					Airflow   
					Std.   
					Airflow   
					CMM   
					L/S   
					60   
					1000   
					1000   
					70   
					1170   
					1090   
					80   
					1330   
					1310   
					90   
					1500   
					1310   
					95   
					1580   
					1450   
					PR-8YC   
					FAN SPEED   
					rpm   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					mm   
					inch   
					mm   
					114.3   
					4.5   
					114.3   
					4.5   
					114.3   
					4.5   
					114.3   
					4.5   
					127   
					5.0   
					PRH-8YA   
					165.1   
					152.4   
					127   
					127   
					127   
					100   
					200   
					PRH-8YA-L   
					(FAN SIDE)   
					BELT SIZE   
					inch   
					inch   
					kw   
					6.5   
					B39   
					1.1   
					1230   
					139.7   
					5.5   
					165.1   
					6.5   
					B41   
					1.1   
					1450   
					127   
					5.0   
					127   
					5.0   
					B38   
					1.1   
					1580   
					152.4   
					6.0   
					139.7   
					5.5   
					B40   
					1.1   
					1740   
					152.4   
					6.0   
					127   
					5.0   
					B39   
					1.1   
					6.0   
					B39   
					1.1   
					1320   
					127   
					5.0   
					139.7   
					5.5   
					B39   
					1.1   
					1450   
					127   
					5.0   
					127   
					5.0   
					B38   
					1.1   
					1600   
					139.7   
					5.5   
					127   
					5.0   
					B39   
					1.1   
					1740   
					152.4   
					6.0   
					127   
					5.0   
					B36   
					1.5   
					5.0   
					B37   
					1.1   
					1450   
					127   
					5.0   
					127   
					5.0   
					B38   
					1.1   
					1580   
					152.4   
					6 
					139.7   
					5.5   
					B37   
					1.5   
					1690   
					177.8   
					7.0   
					152.4   
					6.0   
					B39   
					1.5   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					5.0   
					B37   
					1.5   
					1450   
					127   
					5.0   
					127   
					5.0   
					B35   
					1.5   
					1600   
					139.7   
					5.5   
					127   
					5.0   
					B35   
					1.5   
					- 
					- 
					- 
					- 
					- 
					5.0   
					B35   
					1.5   
					1580   
					152.4   
					6.0   
					139.7   
					5.5   
					Operation range   
					MOTOR   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					Fan speed (rpm)   
					600   
					500   
					400   
					300   
					200   
					100   
					1800   
					1700   
					B37   
					1.5   
					External   
					static   
					pressure   
					(Pa)   
					MOTOR   
					1600   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					1.5kW   
					1500   
					1400   
					1.1kW   
					300   
					400   
					500   
					1300   
					1200   
					1100   
					MOTOR   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					1000   
					60   
					1000   
					70   
					1170   
					80   
					1330   
					90   
					1500   
					(CMM)   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					( 
					/ s)   
					MOTOR   
					Airflow   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					MOTOR   
					- 
					Std.   
					- 21 -   
				PR-10YC   
					Airflow   
					90   
					1500   
					1320   
					127   
					CMM   
					L/S   
					100   
					1660   
					110   
					1830   
					120   
					2000   
					1550   
					190.5   
					7.5   
					177.8   
					7.0   
					B39   
					2.2   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					PRH-10YA   
					PRH-10YA-L   
					FAN SPEED   
					rpm   
					mm   
					1450   
					139.7   
					5.5   
					1450   
					139.7   
					5.5   
					PULLEYSIZE   
					(MOTOR SIDE)   
					Operation range   
					inch   
					mm   
					5.0   
					139.7   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					139.7   
					139.7   
					100   
					200   
					inch   
					inch   
					kw   
					5.5   
					B35   
					1.5   
					1450   
					139.7   
					5.5   
					139.7   
					5.5   
					B36   
					1.5   
					1580   
					152.4   
					6 
					139.7   
					5.5   
					B37   
					1.5   
					1710   
					165.1   
					6.5   
					5.5   
					B36   
					1.5   
					1450   
					139.7   
					5.5   
					139.7   
					5.5   
					B36   
					1.5   
					1600   
					139.7   
					5.5   
					127   
					5.0   
					B33   
					2.2   
					1740   
					152.4   
					6.0   
					5.5   
					B33   
					2.2   
					1600   
					139.7   
					5.5   
					127   
					5.0   
					B33   
					2.2   
					1740   
					152.4   
					6.0   
					127   
					5.0   
					B34   
					2.2   
					- 
					Fan speed   
					MOTOR   
					(rpm)   
					600   
					External   
					static   
					pressure   
					(Pa)   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					500   
					1800   
					1700   
					400   
					MOTOR   
					1600   
					300   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					1500   
					2.2kW   
					300   
					200   
					1400   
					1.5kW   
					1300   
					100   
					MOTOR   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					1200   
					- 
					- 
					- 
					- 
					- 
					- 
					90   
					100   
					1670   
					110   
					1830   
					120   
					2000   
					(CMM)   
					( / s)   
					400   
					139.7   
					5.5   
					B35   
					2.2   
					127   
					5.0   
					B34   
					2.2   
					1500   
					Airflow   
					MOTOR   
					Std.   
					Airflow   
					120   
					CMM   
					130   
					140   
					2330   
					690   
					114.3   
					4.5   
					241.3   
					9.5   
					150   
					2500   
					730   
					127   
					5.0   
					160   
					170   
					2830   
					760   
					127   
					5.0   
					241.3   
					9.5   
					180   
					PR-15YC   
					L/S   
					2000   
					2170   
					2670   
					3000   
					FAN SPEED   
					rpm   
					640   
					101.6   
					4.0   
					640   
					101.6   
					4.0   
					730   
					127   
					5.0   
					810   
					127   
					5.0   
					PRH-15YA   
					PRH-15YA-L   
					PULLEYSIZE   
					(MOTOR SIDE)   
					mm   
					inch   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					mm   
					inch   
					inch   
					kw   
					228.6   
					228.6   
					254   
					254   
					228.6   
					100   
					200   
					9.0   
					9.0   
					10.0   
					10.0   
					9.0   
					Operation range   
					B37   
					2.2   
					2 
					B37   
					2 
					B39   
					2.2   
					2 
					B41   
					2 
					B41   
					2 
					B40   
					2 
					B39   
					2 
					MOTOR   
					2.2   
					810   
					127   
					5.0   
					2.2   
					850   
					127   
					5.0   
					2.2   
					890   
					2.2   
					890   
					2.2   
					910   
					127   
					5.0   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					760   
					127   
					5.0   
					810   
					127   
					5.0   
					External   
					static   
					pressure   
					(Pa)   
					Fan speed   
					139.7   
					5.5   
					139.7   
					5.5   
					(rpm)   
					800   
					241.3   
					9.5   
					228.6   
					9.0   
					228.6   
					9.0   
					215.9   
					8.5   
					228.6   
					9.0   
					228.6   
					9.0   
					203.2   
					8.0   
					B40   
					2 
					B39   
					2 
					B39   
					2 
					B38   
					2 
					B39   
					2 
					B39   
					2 
					B37   
					2 
					700   
					MOTOR   
					2.2   
					910   
					127   
					5.0   
					2.2   
					910   
					127   
					5.0   
					2.2   
					910   
					127   
					5.0   
					2.2   
					970   
					127   
					5.0   
					2.2   
					1000   
					139.7   
					5.5   
					2.2   
					970   
					127   
					5.0   
					3.0   
					1040   
					127   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					1200   
					600   
					5.0   
					300   
					400   
					500   
					600   
					203.2   
					8.0   
					203.2   
					8.0   
					203.2   
					8.0   
					190.5   
					7.5   
					203.2   
					8.0   
					190.5   
					7.5   
					177.8   
					7.0   
					3.0kW   
					2.2kW   
					2 
					2 
					2 
					2 
					2 
					2 
					2 
					B37   
					B37   
					B37   
					B36   
					B37   
					B36   
					B35   
					500   
					MOTOR   
					2.2   
					1040   
					127   
					2.2   
					1040   
					127   
					2.2   
					1040   
					127   
					2.2   
					1040   
					127   
					3.0   
					1040   
					127   
					3.0   
					1040   
					127   
					3.0   
					- 
					1100   
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					400   
					5.0   
					5.0   
					5.0   
					5.0   
					5.0   
					5.0   
					- 
					1000   
					177.8   
					7.0   
					177.8   
					7.0   
					177.8   
					7.0   
					177.8   
					7.0   
					177.8   
					7.0   
					177.8   
					7.0   
					- 
					- 
					900   
					300   
					B35   
					B35   
					B35   
					B35   
					B35   
					B35   
					- 
					2 
					2 
					2 
					2 
					2 
					2 
					MOTOR   
					2.2   
					1120   
					127   
					2.2   
					1140   
					139.7   
					5.5   
					3.0   
					1120   
					127   
					3.0   
					1120   
					127   
					3.0   
					- 
					3.0   
					- 
					- 
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					800   
					200   
					- 
					- 
					- 
					5.0   
					5.0   
					5.0   
					- 
					- 
					- 
					700   
					165.1   
					6.5   
					177.8   
					7.0   
					165.1   
					6.5   
					165.1   
					6.5   
					- 
					- 
					- 
					- 
					- 
					- 
					100   
					600   
					B34   
					2 
					B36   
					2 
					B34   
					2 
					B34   
					2 
					- 
					- 
					- 
					MOTOR   
					2.2   
					1210   
					127   
					3.0   
					1230   
					139.7   
					5.5   
					3.0   
					1230   
					139.7   
					5.5   
					3.0   
					- 
					- 
					- 
					FAN SPEED   
					PULLEYSIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					120   
					2000   
					140   
					2330   
					160   
					2670   
					180   
					3000   
					(CMM)   
					/ s)   
					5.0   
					- 
					- 
					- 
					( 
					152.4   
					6.0   
					165.1   
					6.5   
					165.1   
					6.5   
					- 
					- 
					- 
					- 
					- 
					- 
					Airflow   
					B33   
					2 
					B35   
					2 
					B35   
					2 
					- 
					- 
					- 
					MOTOR   
					3 
					3 
					3 
					- 
					- 
					- 
					Std.   
					- 22 -   
				Airflow   
					170   
					2830   
					730   
					CMM   
					L/S   
					180   
					3000   
					810   
					190   
					3170   
					810   
					200   
					3330   
					840   
					210   
					3500   
					910   
					220   
					3670   
					940   
					FAN SPEED   
					rpm   
					PR-20YC   
					mm   
					inch   
					PULLEY SIZE   
					127   
					5.0   
					254   
					10.0   
					B43   
					3.0   
					127   
					5.0   
					228.6   
					9.0   
					B41   
					3.0   
					910   
					127   
					5.0   
					203.2   
					8.0   
					127   
					5.0   
					228.6   
					9.0   
					B41   
					3.0   
					910   
					127   
					5.0   
					203.2   
					8.0   
					139.7   
					5.5   
					241.3   
					127   
					5.0   
					203.2   
					8.0   
					B39   
					3.0   
					1000   
					139.7   
					5.5   
					203.2   
					8.0   
					139.7   
					5.5   
					215.9   
					(MOTOR SIDE)   
					PRH-20YA   
					PRH-20YA-L   
					PULLEY SIZE   
					(FAN SIDE)   
					BELT SIZE   
					mm   
					inch   
					inch   
					kw   
					100   
					200   
					9.5   
					8.5   
					2 
					2 
					2 
					2 
					2 
					2 
					B42   
					B41   
					MOTOR   
					3.0   
					910   
					127   
					5.0   
					203.2   
					8.0   
					4.0   
					970   
					127   
					5.0   
					190.5   
					7.5   
					FAN SPEED   
					PULLEY SIZE   
					(MOTOR SIDE)   
					PULLEY SIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					850   
					127   
					5.0   
					215.9   
					8.5   
					B40   
					3.0   
					940   
					139.7   
					5.5   
					215.9   
					8.5   
					External   
					static   
					pressure   
					(Pa)   
					Operation range   
					Fan speed   
					2 
					2 
					B39   
					2 
					B39   
					2 
					B39   
					2 
					B40   
					2 
					B38   
					(rpm)   
					MOTOR   
					3.0   
					1000   
					139.7   
					5.5   
					203.2   
					8.0   
					3.0   
					1040   
					127   
					5.0   
					177.8   
					7.0   
					3.0   
					1040   
					127   
					5.0   
					177.8   
					7.0   
					4.0   
					1040   
					127   
					5.0   
					177.8   
					7.0   
					B37   
					4.0   
					- 
					- 
					4.0   
					700   
					FAN SPEED   
					PULLEY SIZE   
					(MOTOR SIDE)   
					PULLEYSIZE   
					(FAN SIDE)   
					rpm   
					mm   
					inch   
					mm   
					inch   
					- 
					- 
					- 
					- 
					- 
					300   
					400   
					600   
					1200   
					2 
					2 
					2 
					2 
					2 
					BELT SIZE   
					MOTOR   
					inch   
					kw   
					B41   
					B40   
					B37   
					B37   
					- 
					- 
					3.0   
					1040   
					127   
					5.0   
					177.8   
					7.0   
					3.0   
					1040   
					127   
					5.0   
					177.8   
					7 
					4.0   
					1060   
					139.7   
					5.5   
					190.5   
					7.5   
					B39   
					4.0   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					4.0   
					1120   
					127   
					5.0   
					165.1   
					6.5   
					500   
					FAN SPEED   
					PULLEY SIZE   
					(MOTOR SIDE)   
					PULLEY SIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					1100   
					- 
					- 
					- 
					- 
					400   
					4.0kW   
					3.0kW   
					B37   
					2 
					B37   
					2 
					2 
					B36   
					2 
					1000   
					300   
					MOTOR   
					3.0   
					1140   
					139.7   
					5.5   
					177.8   
					7.0   
					4.0   
					1120   
					127   
					5.0   
					165.1   
					6.5   
					4.0   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					FAN SPEED   
					PULLEY SIZE   
					(MOTOR SIDE)   
					PULLEY SIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					900   
					200   
					500   
					800   
					B38   
					4 
					2 
					B36   
					2 
					MOTOR   
					4 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					100   
					700   
					FAN SPEED   
					PULLEY SIZE   
					(MOTOR SIDE)   
					PULLEY SIZE   
					(FAN SIDE)   
					BELT SIZE   
					rpm   
					mm   
					inch   
					mm   
					inch   
					inch   
					kw   
					1230   
					139.7   
					5.5   
					165.1   
					6.5   
					600   
					170   
					2830 3000   
					180   
					200   
					3330   
					220   
					3670   
					(CMM)   
					B37   
					4.0   
					2 
					( 
					/ s)   
					MOTOR   
					- 
					Airflow   
					Std.   
					- 23 -   
				Pulley outside dimensions are shown below: (Unit : mm)   
					(1) Shape of belt groove   
					e 
					f 
					Sectional plan of V-belt   
					w 
					L0   
					V-belt   
					thickness   
					(Reference)   
					Shape of Nominal   
					V-belt Dia. øP.C ( ˚   
					a 
					W 
					L0   
					K 
					K0   
					e 
					f 
					r1   
					r2   
					r3   
					16.5mm   
					) 
					r1   
					r3   
					Over 125   
					Under 160   
					34 15.86   
					a 
					r2 r2   
					Over 160   
					36   
					38   
					12.5 5.5 9.5 19.0 12.5 0.2~0.5 0.5~1.0   
					1~2   
					11   
					16.07   
					16.29   
					B 
					Under 200   
					40˚   
					Over 200   
					B type   
					(2) Shape of motor pulley boss (Unit : mm)   
					C 
					PR-5 10   
					MOTOR   
					CAPACITY   
					A 
					B 
					C 
					PRH-5 10 Pulley for blower & motor   
					(kW)   
					+0.009   
					0 
					+0.073   
					+0.040   
					0.75   
					19   
					24   
					24   
					28   
					28   
					38   
					15.5   
					20.0   
					20.0   
					23.9   
					23.9   
					33.0   
					6 
					8 
					- 0.004   
					- 0.2   
					+0.009   
					- 0.004   
					0 
					+0.073   
					+0.040   
					1.1   
					1.5   
					- 0.2   
					+0.009   
					- 0.004   
					0 
					+0.073   
					+0.040   
					8 
					- 0.2   
					+0.009   
					- 0.004   
					0 
					+0.073   
					+0.040   
					2.2, 3.0   
					4.0   
					8 
					- 0.2   
					+0.009   
					- 0.004   
					0 
					+0.073   
					+0.040   
					8 
					- 0.2   
					+0.018   
					- 0.002   
					0 
					+0.089   
					+0.050   
					5.5   
					10   
					- 0.2   
					PR-8 20   
					PR-5   
					PRH-5   
					PR-15,20   
					PRH-8 20   
					c 
					PRH-15, 20 Pulley for blower & motor   
					MODEL   
					a 
					b 
					c 
					PR-5   
					-0.020   
					0 
					19   
					20   
					20   
					25   
					PRH-5   
					-0.007   
					- 0.1   
					PR-8,10   
					-0.020   
					-0.007   
					0 
					0 
					- 0.1   
					16.5   
					21.0   
					6 
					8 
					PRH-8, 10   
					- 0.036   
					-0.020   
					-0.007   
					PR-15,20   
					0 
					0 
					- 0.1   
					- 0.036   
					PRH-15, 20   
					(3) Shape of motor (Unit : mm)   
					L 
					AC   
					SHAFT   
					Diameter   
					Limits   
					TBW   
					AD   
					AE   
					+0.009   
					-0.004   
					+0.018   
					-0.002   
					19 to 28   
					32 to 48   
					ED   
					F 
					E 
					øD   
					Shaft   
					tapped   
					DH x EH   
					deep   
					Holes   
					K Dia.   
					EB   
					E 
					AA   
					AA   
					LL   
					A CRS   
					AB   
					C 
					B CRS   
					BB   
					BC   
					Frame Fixing   
					OUT PUT Size   
					Shaft   
					General   
					ED DH EH AA AB BB BC   
					A 
					B 
					C 
					H 
					K 
					D 
					E 
					F 
					G 
					L 
					HA AC AD AE EB LL TBW TBH   
					0.75   
					1.1   
					80   
					125 100 50   
					80 10 19   
					90 10 24   
					90 10 24   
					40   
					50   
					50   
					60   
					60   
					6 
					8 
					8 
					8 
					8 
					15.5 25 M6 16 27 157 127 13.5 295   
					20 32 M8 19 28 174 152 38.5 320   
					20 32 M8 19 28 174 152 13.5 320   
					23.9 40 M10 22 28 184 170 15 371   
					23.9 40 M10 22 35 218 170 15 377   
					4 
					4 
					4 
					4 
					4 
					5 
					158 132 102 1.5 75 103 103   
					178 140 110 1.5 100 103 103   
					178 140 110 1.5 100 103 103   
					208 138 120 1.6 23 103 103   
					215 164 130 1.6 23 131 131   
					257 189 154 1.6 26 131 131   
					90SN 140 100 56   
					90N 140 125 56   
					1.5   
					2.2,3.0   
					4.0   
					100L 160 140 63 100 12 28   
					112M 190 140 70 112 12 28   
					132S 216 140 89 132 12 38   
					5.5   
					80 10 33 56 M12 28 38 243 208 53 458   
					- 24 -   
				NC CURVES   
					PR-5YC   
					PRH-5YA   
					PRH-5YA-L   
					50Hz   
					CONDITION   
					A scale   
					62db   
					63 Hz   
					67   
					125 Hz   
					63   
					250 Hz   
					62   
					500 Hz   
					61   
					1000 Hz   
					57   
					2000 Hz   
					50   
					4000 Hz   
					45   
					8000 Hz   
					43   
					COOLING &   
					HEATING   
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					20   
					NC-70   
					NC-60   
					NC-50   
					NC-40   
					NC-30   
					NC-20   
					10   
					over   
					45   
					63   
					90   
					125   
					180   
					250   
					355   
					500   
					710   
					1000   
					1400   
					2000   
					2800   
					4000   
					5600   
					8000   
					all   
					octave-band frequency [Hz]   
					Note. The measuring point is 1m from the comp. service panel.   
					PR-8YC   
					PRH-8YA   
					PRH-8YA-L   
					50Hz   
					CONDITION   
					A scale   
					64db   
					63 Hz   
					70   
					125 Hz   
					67   
					250 Hz   
					62   
					500 Hz   
					60   
					1000 Hz   
					58   
					2000 Hz   
					56   
					4000 Hz   
					52   
					8000 Hz   
					50   
					COOLING &   
					HEATING   
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					20   
					10   
					NC-70   
					NC-60   
					NC-50   
					NC-40   
					NC-30   
					NC-20   
					over   
					all   
					45   
					63   
					90   
					125   
					180   
					250   
					355   
					500   
					710   
					1000   
					1400   
					2000   
					2800   
					4000   
					5600   
					8000   
					octave-band frequency [Hz]   
					Note. The measuring point is 1m from the comp. service panel.   
					- 25 -   
				PR-10YC   
					PRH-10YA   
					PRH-10YA-L   
					50Hz   
					CONDITION   
					A scale   
					64db   
					63 Hz   
					71   
					125 Hz   
					69   
					250 Hz   
					63   
					500 Hz   
					61   
					1000 Hz   
					59   
					2000 Hz   
					57   
					4000 Hz   
					49   
					8000 Hz   
					44   
					COOLING &   
					HEATING   
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					NC-70   
					NC-60   
					NC-50   
					NC-40   
					NC-30   
					NC-20   
					20   
					10   
					over   
					all   
					45   
					63   
					90   
					125   
					180   
					250   
					355   
					500   
					710   
					1000   
					1400   
					2000   
					2800   
					4000   
					5600   
					8000   
					octave-band frequency [Hz]   
					Note. The measuring point is 1m from the comp. service panel.   
					PR-15YC   
					PRH-15YA   
					PRH-15YA-L   
					50Hz   
					CONDITION   
					A scale 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz   
					COOLING &   
					HEATING   
					68db   
					76   
					76   
					68   
					65   
					62   
					59   
					51   
					48   
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					20   
					NC-70   
					NC-60   
					NC-50   
					NC-40   
					NC-30   
					NC-20   
					10   
					over   
					45   
					63   
					90   
					125   
					180   
					250   
					355   
					500   
					710   
					1000   
					1400   
					2000   
					2800   
					4000   
					5600   
					8000   
					all   
					octave-band frequency [Hz]   
					Note. The measuring point is 1m from the comp. service panel.   
					- 26 -   
				50Hz   
					PR-20YC   
					PRH-20YA   
					PRH-20YA-L   
					CONDITION   
					A scale   
					68db   
					63 Hz   
					73.5   
					125 Hz   
					77   
					250 Hz   
					70   
					500 Hz   
					65   
					1000 Hz 2000 Hz 4000 Hz 8000 Hz   
					COOLING &   
					HEATING   
					60   
					58   
					51   
					48   
					90   
					80   
					70   
					60   
					50   
					40   
					30   
					NC-70   
					NC-60   
					NC-50   
					NC-40   
					NC-30   
					NC-20   
					20   
					10   
					over   
					all   
					45   
					63   
					90   
					125   
					180   
					250   
					355   
					500   
					710   
					1000   
					1400   
					2000   
					2800   
					4000   
					5600   
					8000   
					octave-band frequency [Hz]   
					Note. The measuring point is 1m from the comp. service panel.   
					OUTLINE DIMENSIONS   
					PR-5YC   
					PRH-5YA   
					PRH-5YA-L   
					25   
					1030   
					25   
					16-ø3.5 HOLES   
					(1030)   
					25   
					CONDENSER AIR OUTLET   
					65   
					10   
					25   
					200   
					200   
					850   
					200   
					200   
					25   
					A 
					SUPPLY AIR DUCT FLANGE   
					25   
					A(DETAIL)   
					RETURN AIR DUCT FLANGE   
					6-15X25 MTG HOLES   
					10   
					65   
					900   
					30   
					210   
					210   
					210   
					210   
					30   
					850   
					900   
					75   
					75   
					50   
					40   
					50   
					40   
					1600   
					16-ø3.5 HOLES   
					1000   
					49   
					607   
					944   
					470   
					SUPPLY AIR   
					CONDENSER AIR INLET   
					(2 SIDES)   
					CONTROL BOX   
					RETURN AIR   
					22   
					22   
					54.5   
					80   
					54.5   
					971   
					DRAIN 1B PT   
					1534   
					WIRING HOLE   
					80   
					4- ø25   
					SASPENSION HOLES   
					424   
					1080   
					- 27 -   
				PR-8,10YC   
					PRH-8, 10YA   
					PRH-8, 10YA-L   
					20-ø3.5 HOLES   
					25   
					1330   
					25   
					(1330)   
					25   
					65   
					10   
					35   
					180   
					180   
					180   
					180   
					180   
					180   
					35   
					CONDENSER AIR   
					OUTLET   
					1150   
					A 
					SUPPLY AIR DUCT FLANGE   
					25   
					A(DETAIL)   
					RETURN AIR DUCT FLANGE   
					6-15X25 MTG HOLES   
					1200   
					190 190   
					10   
					65   
					30   
					190   
					190   
					190   
					190   
					30   
					75   
					1150   
					1200   
					1300   
					75   
					1600   
					20-ø3.5 HOLES   
					50   
					40   
					50   
					40   
					49   
					607   
					944   
					470   
					SUPPLY AIR   
					CONTROL BOX   
					CONDENSER AIR INLET   
					(2 SIDES)   
					RETURN AIR   
					22   
					54.5   
					22   
					54.5   
					80   
					80   
					1271   
					1380   
					4-ø25   
					SASPENSION HOLES   
					DRAIN 1B PT   
					1534   
					WIRING HOLE   
					424   
					PR-15,20YC   
					PRH-15, 20YA   
					PRH-15, 20YA-L   
					26-ø3.5 HOLES   
					25   
					2010   
					25   
					25   
					2010   
					62   
					60 150 200 200 200 200 200 200 200 150   
					1820   
					60   
					10   
					CONDENSER AIR OUTLET   
					A 
					25   
					SUPPLY AIR DUCT FLANGE   
					A (DETAIL)   
					RETURN AIR DUCT FLANGE   
					1879   
					6-15X25 MTG HOLES   
					10   
					62   
					39.5   
					200 200 200 200 200 200 200 200 200 39.5   
					85   
					85   
					1820   
					1879   
					1990   
					26-ø3.5 HOLES   
					55.5   
					35   
					55.5   
					35   
					1840   
					43   
					717   
					1080   
					990   
					540   
					SUPPLY AIR   
					CONTROL BOX   
					CONDENSER   
					AIR INLET   
					(3 SIDES)   
					RETURN AIR   
					RETURN AIR   
					101   
					131   
					22   
					54.5   
					22   
					WIRING HOLE   
					DRAIN 1B PT   
					1742.7   
					1951   
					2060   
					4-ø25   
					54.5   
					556.5   
					SUSPENSION HOLES   
					37   
					- 28 -   
				WIRING DIAGRAMS   
					PR-5, 8, 10YC (STANDARD)   
					Power Supply   
					3Phase   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					380~415Volt   
					50Herts   
					PR- 5YC ···40A   
					PR- 8YC ···50A   
					PR-10YC ···60A   
					TB1   
					51C   
					52C   
					INTERNAL   
					MC   
					L1   
					L2   
					L3   
					RED   
					RED   
					PROTECTOR   
					RED   
					WHITE   
					WHITE   
					BLACK   
					WHITE   
					BLACK   
					BLACK   
					TB2   
					RED   
					51F2   
					TB2   
					1 
					RED   
					R1   
					RED   
					R2   
					S2   
					T2   
					MF2   
					N 
					BLUE   
					WHITE   
					BLACK   
					WHITE   
					BLACK   
					WHITE   
					BLACK   
					S1   
					T1   
					2 
					3 
					PE   
					52F   
					51F1   
					RED   
					RED   
					WHITE   
					BLACK   
					MF1   
					F 
					INTERNAL   
					F 
					(3.15A)   
					PROTECTOR   
					TB3   
					11   
					11   
					TB4   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					15   
					51F1   
					F 
					SW1   
					(3.15A)   
					GL   
					RL   
					51F2   
					63H   
					FZ1   
					52C   
					Tr   
					23   
					WA   
					SW2   
					51   
					1 
					C 
					AC   
					AC   
					24V   
					220~   
					240V   
					3 
					2 
					4 
					5 
					6 
					TB4   
					26L   
					3 
					CZ   
					CZ   
					CH   
					52F   
					CZ   
					FZ0   
					FZ1   
					TM   
					(3MIN)   
					52C   
					8,20YC ONLY   
					30   
					CZ   
					30   
					CZ   
					TM   
					FZ0   
					FZ1   
					30   
					CZ   
					7 
					52C   
					12 TB3   
					TB3   
					12   
					Caution,   
					Symbol   
					Name   
					1.To protect each Fan motors and Compressors from abnormal current,   
					these Over current relays<51C>,<51F1,2>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					MC   
					MF1   
					MF2   
					52C   
					52F   
					TB1~4   
					CH   
					F 
					Tr   
					51C   
					51F1, 2   
					63H   
					26L   
					Compressor motor   
					Fan motor (in door)   
					Fan motor (out door)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					Transformer   
					Over current relay(compressor)   
					Over current relay (fan I/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Timer (anti short cycle)   
					Auxiliary relay (fan)   
					Auxiliary relay (compressor)   
					Auxiliary relay (check)   
					Switch (off)   
					Note:   
					1.The dotted lines show field wiring.   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					5.Specification subject to change without notice.   
					TM   
					FZ0·1   
					CZ   
					30CZ   
					<SW1>   
					<SW2>   
					<GL>   
					Switch (on)   
					Lamp (operation)   
					<RL>   
					Lamp (check)   
					Thermostat (room temp.)   
					<23WA>   
					- 29 -   
				PR-15, 20YC (STANDARD)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					Power supply   
					3Phase   
					380~415Volt   
					50Hertz   
					PR -15YC···100A   
					PR -20YC···125A   
					MC1   
					INTERNAL   
					PROTECTOR   
					52C1   
					51C1   
					TB1   
					L1   
					L2   
					L3   
					Red   
					White   
					Red   
					Red   
					White   
					Black   
					Black   
					Black   
					TB2   
					R11   
					51F2   
					R12   
					S12   
					T12   
					1 
					2 
					3 
					Red   
					Red   
					Red   
					Blue   
					S11   
					T11   
					White   
					Black   
					N 
					White   
					Black   
					White   
					Black   
					MF2   
					PE   
					MC2   
					51C2   
					INTERNAL   
					PROTECTOR   
					52C2   
					Red   
					Red   
					Red   
					White   
					White   
					Black   
					Black   
					INTERNAL   
					PROTECTOR   
					Black   
					TB3   
					51F3   
					Red   
					Red   
					21   
					21   
					21   
					22   
					22   
					22   
					1 
					2 
					3 
					R 
					S 
					T 
					R 
					S 
					T 
					White   
					Black   
					White   
					Black   
					MF3   
					52F   
					51F1   
					Red   
					INTERNAL   
					PROTECTOR   
					Red   
					White   
					Black   
					MF1   
					F 
					F(3.15A)   
					TB4 11   
					TB4 14   
					51F1   
					TB5   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					FZ0   
					F 
					30   
					30   
					(3.15A)   
					CZ2-2   
					CZ1-2   
					RL1   
					RL2   
					SW1   
					23WA   
					GL   
					High   
					Low   
					51F2   
					51F3   
					SW2   
					Tr   
					63   
					63   
					AC   
					H1   
					H2   
					CZ1   
					CZ2   
					220~   
					240V   
					AC   
					CZ1   
					CZ2   
					24V   
					51C1   
					1 
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					51C2   
					1 
					TB5   
					52 52   
					C1 C2   
					52   
					C2   
					52   
					C1   
					52   
					TM   
					TM   
					CZ1   
					C2   
					(3MIN)   
					(3MIN)   
					26   
					L1   
					26   
					L2   
					52   
					C1   
					FZ0   
					CH2   
					CZ2   
					52   
					3 
					3 
					F 
					FZ1   
					FZ1   
					TM   
					CH1   
					2 
					52   
					C1   
					FZ0   
					(2SEC)   
					30   
					30   
					30   
					CZ1-1   
					30   
					CZ2-1   
					CZ1   
					CZ2   
					2 
					FZ1   
					52   
					C2   
					C3Z20-1   
					C3Z10-1   
					C3Z10-2   
					C3Z20-2   
					9 
					TB4 12   
					TB412   
					Caution,   
					Symbol   
					MC1·2   
					Name   
					1.To protect each Fan motors and Compressors from abnormal current,   
					these Over current relays <51C1,2> , <51F1,2,3> are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressors from frequently "ON-OFF" ,timer <TM> is   
					installed. Therefore,do not change factory set value of this timer.   
					3.This timer <2> installed so that two compressors may never start at   
					the same time. The unit stop if the set value of the timer is changed.   
					Compressor motor   
					Fan motor (in door)   
					Fan motor (out door)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					MF1   
					MF2·3   
					52C1·2   
					52F   
					TB1~5   
					CH1·2   
					F 
					Crankcase heater   
					Fuse   
					Note:   
					Tr   
					51C1·2   
					Transformer   
					1.The dotted lines show field wiring.   
					Over current relay(compressor)   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					51F1~3 Over current relay (fan I/D,O/D)   
					63H1·2   
					26L1·2   
					TM   
					2 
					High-pressure switch   
					Thermostat(freeze protection)   
					Timer (anti short cycle)   
					Timer   
					5.Specification subject to change without notice.   
					FZ0·1   
					Auxiliary relay (fan)   
					CZ1·2   
					30CZ1-1,2   
					30CZ2-1,2   
					<SW1>   
					<SW2>   
					<GL>   
					Auxiliary relay (compressor)   
					Auxiliary relay (check)   
					Auxiliary relay (check)   
					Switch (off)   
					Switch (on)   
					Lamp (power on)   
					<RL1·2> Lamp (check)   
					<23WA> Thermostat (room temp.)   
					- 30 -   
				PR-5, 8, 10YC   
					(SPECIAL ORDER : K CONTROL)   
					Power supply   
					3Phase   
					380~415Volt   
					50Hertz   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					MC   
					INTERNAL   
					PR- 5YC ···40A   
					PR- 8YC ···50A   
					PR-10YC ···60A   
					PROTECTOR   
					TB1   
					L1   
					52C   
					51C   
					Red   
					Red   
					White   
					Black   
					Red   
					L2   
					L3   
					White   
					Black   
					Black   
					51F2   
					TB2   
					1 
					2 
					3 
					1 
					2 
					Red   
					R 
					R 
					N 
					Blue   
					White   
					Black   
					S1   
					S 2   
					MF2   
					1 
					2 
					T 
					T 
					PE   
					52F   
					51F1   
					Red   
					Red   
					DSA   
					CN   
					1 
					White   
					Black   
					MF1   
					Blue   
					Green/Yellow   
					Black   
					3 
					INTERNAL   
					PROTECTOR   
					F(3.15A)   
					TB3 11   
					11   
					15   
					TH2   
					30   
					IB   
					CZ   
					51F1   
					51F2   
					63H   
					FZ   
					TB4   
					A 
					B 
					C 
					D 
					52F   
					51C   
					CZ   
					FZ   
					Tr   
					TH5   
					CZ   
					52C   
					CH   
					FZ   
					52C   
					30   
					CZ   
					R/C   
					30   
					CZ   
					8,10YC ONLY   
					TB3 12   
					TB3 12   
					Caution,   
					Name   
					Symbol   
					MC   
					To protect each Fan motors and Compressor from abnormal current,   
					these Over current relays<51C>,<51F1,2>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					Compressor motor   
					Fan motor(indoor)   
					Fan motor(outdoor)   
					Contactor(compressor)   
					Contactor(fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MF1   
					MF2   
					52C   
					52F   
					TB1~4   
					CH   
					F 
					Tr   
					51C   
					51F1,2   
					63H   
					FZ   
					Note:   
					1.The dotted lines show field wiring.   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					Transformer   
					Over current relay(compressor)   
					Over current relay(fanI/D,O/D)   
					High-pressure switch   
					Auxiliary relay(fan)   
					5.Specification subject to change without notice.   
					CZ   
					30CZ   
					IB   
					Auxiliary relay(compressor)   
					Auxiliary relay(check)   
					Indoor board   
					TH2   
					TH5   
					R/C   
					DSA   
					Thermistor(pipe)   
					Thermistor(room temp.)   
					Remote controller   
					Surge absorber circuit board   
					- 31 -   
				PR-5, 8, 10YC   
					(SPECIAL ORDER : LOW TEMPERATURE)   
					CIRCUIT BREAKER   
					Power supply   
					3Phase   
					380~415Volt   
					50Hertz   
					MC   
					(FIELD SUPPLY)   
					INTERNAL   
					PR - 5YC ···40A   
					PR - 8YC ···50A   
					PR -10YC ···60A   
					PROTECTOR   
					TB1   
					L1   
					51C   
					52C   
					Red   
					White   
					Black   
					Red   
					Red   
					L2   
					L3   
					White   
					Black   
					Black   
					51F2   
					TB2   
					52F2   
					TB2   
					1 
					2 
					3 
					Red   
					2 
					2 
					2 
					2 
					2 
					2 
					R 
					1 
					R 
					1 
					R 
					S 
					T 
					R 
					S 
					T 
					Red   
					Red   
					White   
					Black   
					N 
					Blue   
					White   
					S1   
					S 1   
					White   
					Black   
					MF2   
					PE   
					Black   
					T 
					1 
					T 
					1 
					52F1   
					51F1   
					51F3   
					Red   
					Red   
					52F3   
					52F4   
					White   
					Black   
					MF1   
					Black   
					Tr1   
					INTERNAL   
					PROTECTOR   
					F(3.15A)   
					TB3 11   
					11   
					51F3   
					TB4   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					15   
					14   
					F 
					51F1   
					51F2   
					63H   
					(3.15A)   
					RL   
					SW1   
					FZ1   
					GL   
					23WA   
					TB4   
					26D3   
					SW2   
					FZ   
					2 
					FZ   
					3 
					FZ   
					4 
					Tr2   
					FZ   
					2 
					AC   
					220~   
					AC   
					51   
					1 
					C 
					240V   
					24V   
					2 
					3 
					4 
					5 
					52   
					F1   
					6 
					26D4   
					52   
					F2   
					52   
					F4   
					CZ   
					FZ2   
					CZ   
					26L   
					3 
					52   
					F3   
					FZ0   
					TM   
					52C   
					CH   
					52   
					C 
					CZ   
					(3MIN)   
					FZ3   
					FZ1   
					30   
					CZ   
					30   
					FZ   
					3 
					CZ   
					FZ1   
					52C   
					FZ0   
					TM   
					FZ4   
					30   
					CZ   
					7 
					8,10YC ONLY   
					12   
					TB3 12   
					Caution,   
					Symbol   
					MC   
					Name   
					1.To protect each Fan motors and Compressor from abnormal current,   
					these Over current relays<51C>,<51F1,2,3>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					Compressor motor   
					Fan motor (indoor)   
					Fan motor (outdoor)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MF1   
					MF2   
					52C   
					52F1   
					TB1~4   
					CH   
					Note:   
					1.The dotted lines show field wiring.   
					F 
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					Tr1·2   
					51C   
					51F1,2,3   
					63H   
					26L   
					Transformer   
					Over current relay(compressor)   
					Over current relay(fanI/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Timer (anti short cycle)   
					5.Specification subject to change without notice.   
					TM   
					FZ0,1 Auxiliary relay (fan)   
					CZ   
					Auxiliary relay (compressor)   
					30CZ   
					<SW1>   
					Auxiliary relay (check)   
					Switch (off)   
					<SW2>   
					<GL>   
					<RL>   
					Switch (on)   
					Lamp (operation)   
					Lamp (check)   
					<23WA> Thermostat (room temp.)   
					52F2~4   
					FZ2~4   
					Contactor (fan O/D)   
					Auxiliary relay (fan O/D)   
					- 32 -   
				PR-15, 20YC   
					(SPECIAL ORDER : LOW TEMPERATURE)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					Power supply   
					3Phase   
					380~415Volt   
					50Hertz   
					PR -15YC···100A   
					PR -20YC···125A   
					MC1   
					INTERNAL   
					PROTECTOR   
					52C1   
					51C1   
					TB1   
					L1   
					L2   
					L3   
					Red   
					White   
					Black   
					Red   
					Red   
					White   
					Black   
					Black   
					TB2   
					R11 R11   
					51F2   
					TB2   
					52F2   
					Red   
					1 
					2 
					3 
					Red   
					Red   
					R12   
					R12   
					Red   
					White   
					Black   
					Blue   
					N 
					White   
					Black   
					White   
					Black   
					S11 S11   
					T11 T11   
					S12 S12   
					White   
					Black   
					MF2   
					T12   
					T12   
					PE   
					51F4   
					MC2   
					51C2   
					INTERNAL   
					PROTECTOR   
					52C2   
					52F3   
					Red   
					Red   
					Red   
					White   
					White   
					Black   
					Black   
					INTERNAL   
					PROTECTOR   
					Black   
					52F4   
					Tr1   
					51F3   
					TB3   
					TB3   
					52F5   
					1 
					2 
					3 
					Red   
					22   
					22   
					22   
					R 
					S 
					T 
					22   
					22   
					22   
					R 
					S 
					T 
					21   
					21   
					R 
					S 
					T 
					21   
					Red   
					R 
					S 
					T 
					Red   
					White   
					Black   
					21   
					White   
					Black   
					White   
					Black   
					MF3   
					21   
					21   
					51F5   
					52F6   
					52F   
					51F1   
					Red   
					INTERNAL   
					PROTECTOR   
					52F7   
					Red   
					Tr2   
					White   
					Black   
					MF1   
					F 
					F(3.15A)   
					TB4 11   
					TB5   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					FZ0   
					51F1   
					TB4   
					11   
					F 
					30   
					30   
					(3.15A)   
					CZ1-2   
					CZ2-2   
					RL1   
					RL2   
					SW1   
					23WA   
					51F4   
					51F2   
					51F5   
					High   
					Low   
					GL   
					26D3   
					26D1   
					51F3   
					63   
					SW   
					2 
					FZ   
					2 
					FZ   
					2 
					FZ   
					FZ   
					5 
					FZ   
					3 
					FZ   
					4 
					FZ   
					6 
					FZ   
					7 
					Tr   
					5 
					63   
					AC   
					H1   
					H2   
					51C2   
					1 
					CZ1   
					CZ2   
					220 ~   
					240V   
					AC   
					CZ1   
					CZ2   
					24V   
					51C1   
					1 
					2 
					3 
					5 
					6 
					8 
					4 
					7 
					TB5   
					52 52   
					C1 C2   
					52   
					26D4   
					26D2   
					C2   
					52   
					52   
					C2   
					52   
					F2   
					52   
					F4   
					52   
					F5   
					52   
					F7   
					TM   
					TM   
					FZ2   
					FZ5   
					CZ1   
					C1   
					(3MIN)   
					(3MIN)   
					26   
					L1   
					26   
					L2   
					52   
					C1   
					FZ0   
					52   
					F3   
					52   
					F6   
					CZ2   
					CH2   
					52   
					3 
					3 
					F 
					FZ6   
					FZ3   
					FZ1   
					FZ1   
					TM   
					CH1   
					2 
					FZ   
					3 
					FZ   
					6 
					52   
					C1   
					FZ0   
					(2SEC)   
					30   
					30   
					30   
					CZ1-1   
					30   
					CZ2-1   
					CZ1   
					2 
					CZ2   
					FZ1   
					52   
					C2   
					FZ4   
					FZ7   
					30   
					30   
					C3Z10-1   
					C3Z10-2   
					10   
					CZ2-1   
					CZ2-2   
					TB4 12   
					TB4 12   
					Symbol   
					Name   
					Caution,   
					1.To protect each Fan motors and Compressors   
					from abnormal current,these Over current relays<51C1,2>,   
					<51F1~5>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressors from frequently "ON-OFF",timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					3.This timer<2>installed so that two compressors may never start at   
					the same time. The unit stop if the set value of the timer is changed.   
					Compressor motor   
					Fan motor (indoor)   
					Fan motor (outdoor)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MC1·2   
					MF1   
					MF2·3   
					52C1·2   
					52F1   
					TB1~5   
					CH1·2   
					F 
					Tr1~3   
					51C1·2   
					51F1~5   
					63H1·2   
					26L1·2   
					TM   
					Transformer   
					Note:   
					Over current relay(compressor)   
					Over current relay (fan I/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Timer (anti short cycle)   
					Timer   
					1.The dotted lines show field wiring.   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					2 
					5.Specification subject to change without notice.   
					FZ0·1   
					Auxiliary relay (fan)   
					Auxiliary relay (compressor)   
					Auxiliary relay (check)   
					Auxiliary relay (check)   
					Switch (off)   
					CZ1·2   
					30CZ1-1, 2   
					30CZ2-1, 2   
					<SW1>   
					<SW2>   
					<GL>   
					Switch (on)   
					Lamp (operation)   
					<RL1·2>   
					Lamp (check)   
					<23WA>   
					26D1~4   
					52F2~7   
					Thermostat (room temp.)   
					Thermostat (ambiemt temp.)   
					Contactor (fan O/D)   
					Auxiliary relay (fan O/D)   
					FZ2~7   
					- 33 -   
				PR-5, 8, 10YC   
					(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					PR - 5YC ···40A   
					PR - 8YC ···50A   
					PR -10YC ···60A   
					Power supply   
					3Phase   
					380~415Volt   
					50Hertz   
					MC   
					INTERNAL   
					PROTECTOR   
					TB1   
					52C   
					51C   
					L1   
					Red   
					Red   
					White   
					Red   
					L2   
					L3   
					White   
					Black   
					Black   
					Black   
					51F2   
					TB2   
					TB2   
					1 
					2 
					3 
					52F2   
					R 
					S 
					T 
					R 
					S 
					T 
					R 
					R2   
					S 2   
					T2   
					1 
					1 
					1 
					1 
					1 
					1 
					2 
					Red   
					Red   
					Red   
					Blue   
					N 
					S 2   
					T2   
					White   
					Black   
					White   
					Black   
					MF2   
					White   
					Black   
					PE   
					52F1   
					51F1   
					51F3   
					Red   
					Red   
					52F3   
					DSA   
					CN   
					1 
					White   
					Black   
					MF1   
					Blue   
					Green/Yellow   
					Black   
					3 
					52F4   
					Tr1   
					INTERNAL   
					PROTECTOR   
					F(3.15A)   
					TB3 11   
					11   
					TH2   
					51F3   
					30   
					15   
					14   
					IB   
					CZ   
					51F1   
					FZ1   
					51F2   
					63H   
					51C   
					26D3   
					FZ   
					2 
					FZ   
					2 
					FZ   
					3 
					FZ   
					4 
					A 
					B 
					C 
					D 
					TB4   
					52   
					F1   
					FZ1   
					CZ   
					Tr2   
					26D4   
					52   
					F2   
					52   
					F4   
					FZ2   
					TH5   
					52   
					F3   
					CZ   
					52C   
					CH   
					FZ1   
					FZ3   
					52C   
					30   
					FZ   
					3 
					CZ   
					R/C   
					30   
					CZ   
					FZ4   
					8,10YC ONLY   
					12   
					TB3 12   
					Caution,   
					Symbol   
					MC   
					MF1   
					MF2   
					52C   
					52F1   
					TB1~4   
					CH   
					Name   
					To protect each Fan motors and Compressor from abnormal current,   
					these Over current relays<51C>,<51F1,2,3>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					Compressor motor   
					Fan motor(indoor)   
					Fan motor(outdoor)   
					Contactor(compressor)   
					Contactor(fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					Note:   
					1.The dotted lines show field wiring.   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					F 
					Tr1·2   
					51C   
					51F1,2,3   
					63H   
					FZ1   
					CZ   
					Transformer   
					(compressor)   
					Over current relay   
					5.Specification subject to change without notice.   
					Over current relay(fanI/D,O/D)   
					High-pressure switch   
					Auxiliary relay(fan)   
					Auxiliary relay(compressor)   
					Auxiliary relay(check)   
					Indoor board   
					30CZ   
					IB   
					TH2   
					52F2~4   
					FZ2~4   
					Thermistor(pipe)   
					Contactor(fan O/D)   
					Auxiliary relay(fan O/D)   
					Thermistor(room temp)   
					Remote controller   
					Surge absorber circuit board   
					TH5   
					R/C   
					DSA   
					- 34 -   
				PRH-5, 8, 10YA   
					PRH-5, 8, 10YA-L (STANDARD)   
					CIRCUIT BREAKER   
					Power Supply   
					3Phase   
					(FIELD SUPPLY)   
					PRH- 5YA,   
					PRH- 5YA-L   
					PRH- 8YA,   
					···40A   
					380~415Volt   
					50Hertz   
					···50A   
					···60A   
					PRH- 8YA-L   
					PRH-10YA,   
					TB1   
					51C   
					PRH-10YA-L   
					52C   
					INTERNAL   
					MC   
					L1   
					L2   
					L3   
					RED   
					RED   
					PROTECTOR   
					RED   
					WHITE   
					WHITE   
					BLACK   
					WHITE   
					BLACK   
					BLACK   
					TB2   
					RED   
					51F2   
					TB2   
					X1   
					1 
					2 
					3 
					RED   
					R1   
					RED   
					R2   
					S2   
					T2   
					MF2   
					N 
					BLUE   
					WHITE   
					BLACK   
					WHITE   
					BLACK   
					WHITE   
					BLACK   
					S1   
					T1   
					PE   
					52F   
					51F1   
					RED   
					RED   
					WHITE   
					BLACK   
					MF1   
					F 
					INTERNAL   
					F 
					(3.15A)   
					PROTECTOR   
					TB3   
					11   
					11   
					TB4   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					15   
					HZ   
					HZ   
					13   
					51F1   
					F 
					SW2   
					14   
					SW1   
					(3.15A)   
					COOL   
					C 
					HEAT   
					GL   
					RL   
					51F2   
					63H   
					FZ1   
					52C   
					Tr   
					X1   
					H 
					SW3   
					26   
					D2   
					23   
					WA   
					C 
					51   
					1 
					AC   
					AC   
					24V   
					21   
					S4   
					220~   
					240V   
					3 
					2 
					4 
					5 
					6 
					7 
					TB4   
					26L   
					3 
					CZ   
					TM   
					CZ   
					CH   
					52F   
					CZ   
					HZ   
					FZ0   
					26   
					D1   
					X2   
					FZ1   
					52C   
					8,10YA,   
					YA-L   
					ONLY   
					X1   
					X2   
					(3MIN)   
					30   
					CZ   
					30   
					CZ   
					TM   
					FZ0   
					FZ1   
					30   
					CZ   
					8 
					52C   
					12 TB3   
					TB3   
					12   
					Caution,   
					Symbol   
					Name   
					1.To protect each Fan motors and Compressors from abnormal current,   
					these Over current relays<51C>,<51F1,2>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressor from frequently "ON-OFF" ,timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					MC   
					MF1   
					MF2   
					52C   
					52F   
					TB1~4   
					CH   
					F 
					Tr   
					51C   
					51F1, 2   
					63H   
					Compressor motor   
					Fan motor (in door)   
					Fan motor (out door)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					Note:   
					1.The dotted lines show field wiring.   
					Transformer   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					Over current relay(compressor)   
					Over current relay (fan I/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Thermostat (defrost)   
					5.Specification subject to change without notice.   
					26L   
					26D1·2   
					TM   
					Timer (anti short cycle)   
					4-Way valve   
					Auxiliary relay (fan)   
					21S4   
					FZ0·1   
					CZ   
					HZ   
					30CZ   
					X1·2   
					<SW1>   
					<SW2>   
					<SW3>   
					<GL>   
					<RL>   
					Auxiliary relay (compressor)   
					Auxiliary relay (heater)   
					Auxiliary relay (check)   
					Auxiliary relay (defrost)   
					Switch (operation mode)   
					Switch (off)   
					Switch (on)   
					Lamp (operation)   
					Lamp (check)   
					Thermostat (room temp.)   
					<23WA>   
					- 35 -   
				PRH-15, 20YA   
					PRH-15, 20YA-L (STANDARD)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					PRH-15YA   
					PRH-15YA-L   
					PRH-20YA   
					Power supply   
					3Phase   
					380~415Volt   
					50Herts   
					···100A   
					MC1   
					···125A   
					INTERNAL   
					PRH-20YA-L   
					PROTECTOR   
					52C1   
					51C1   
					TB1   
					L1   
					L2   
					L3   
					Red   
					White   
					Red   
					Red   
					White   
					Black   
					Black   
					Black   
					TB2   
					R12   
					51F2   
					X1   
					1 
					2 
					3 
					Red   
					Red   
					R11   
					S11   
					T11   
					Red   
					Blue   
					N 
					White   
					Black   
					White   
					Black   
					S12   
					T12   
					White   
					Black   
					MF2   
					MC2   
					51C2   
					INTERNAL   
					PROTECTOR   
					52C2   
					Red   
					Red   
					Red   
					White   
					White   
					Black   
					Black   
					INTERNAL   
					PROTECTOR   
					Black   
					TB3   
					51F3   
					X2   
					1 
					2 
					3 
					21   
					21   
					21   
					22   
					22   
					22   
					R 
					S 
					T 
					R 
					S 
					T 
					Red   
					Red   
					White   
					Black   
					White   
					Black   
					MF3   
					52F   
					51F1   
					Red   
					INTERNAL   
					PROTECTOR   
					Red   
					White   
					Black   
					MF1   
					F 
					F(3.15A)   
					TB4 11   
					TB5   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					FZ0   
					51F1   
					51F2   
					HZ   
					HZ   
					14   
					F 
					30   
					30   
					SW1   
					C 
					(3.15A)   
					CZ2-2   
					CZ1-2   
					HEAT   
					COOL   
					RL1   
					RL2   
					SW2   
					TB4 13   
					GL   
					C 
					H 
					H 
					51F3   
					SW3   
					High   
					Low   
					3 
					Tr   
					X1 X2   
					X2   
					63   
					63   
					23WA   
					AC   
					H1   
					H2   
					CZ1   
					CZ2   
					220~   
					240V   
					AC   
					CZ1   
					CZ2   
					24V   
					51   
					C1   
					51   
					C2   
					2 
					4 
					5 
					6 
					7 
					8 
					9 
					26   
					TB5   
					52 52   
					C1 C2   
					21   
					52   
					C2   
					D4   
					26   
					S41   
					1 
					1 
					D3   
					52   
					C1   
					52   
					TM   
					TM   
					21   
					CZ1   
					HZ   
					C2   
					(3MIN)   
					(3MIN)   
					26   
					L1   
					26   
					L2   
					S42   
					26   
					52   
					C1   
					FZ0   
					CH2   
					CZ2   
					X4   
					52   
					F 
					26   
					D2   
					X3   
					3 
					3 
					D1   
					FZ1   
					FZ1   
					TM   
					CH1   
					2 
					X2   
					52   
					C1   
					FZ0   
					(2SEC)   
					30   
					30   
					X1   
					30   
					CZ1-1   
					30   
					CZ2-1   
					CZ1   
					CZ2   
					2 
					X4   
					FZ1   
					X3   
					52   
					C2   
					C3Z20-1   
					C3Z10-1   
					C3Z10-2   
					C3Z20-2   
					10   
					TB4 12   
					TB4 12   
					Caution,   
					Symbol   
					MC1·2   
					Name   
					1.To protect each Fan motors and Compressors from abnormal current,   
					these Over current relays<51C1,2>,<51F1,2,3>are installed.   
					Compressor motor   
					Fan motor (in door)   
					Fan motor (out door)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MF1   
					MF2·3   
					52C1·2   
					52F   
					TB1~5   
					CH1·2   
					F 
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressors from frequently "ON-OFF" ,timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					3.This timer<2>installed so that two compressors may never start at   
					the same time. The unit stop if the set value of the timer is changed.   
					Note:   
					Tr   
					Transformer   
					1.The dotted lines show field wiring.   
					51C1·2   
					51F1~3   
					63H1·2   
					26L1·2   
					26D1~4   
					TM   
					Over current relay(compressor)   
					Over current relay (fan I/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Thermostat (defrost)   
					Timer (anti short cycle)   
					Timer   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					5.Specification subject to change without notice.   
					2 
					21S41·42   
					4-Way valve   
					FZ0·1   
					CZ1·2   
					HZ   
					30CZ1-1,2   
					30CZ2-1,2   
					X1~4   
					<SW1>   
					<SW2>   
					<SW3>   
					<GL>   
					Auxiliary relay (fan)   
					Auxiliary relay (compressor)   
					Auxiliary relay (heater)   
					Auxiliary relay (check)   
					Auxiliary relay (check)   
					Auxiliary relay (defrost)   
					Switch (operation mode)   
					Switch (off)   
					Switch (on)   
					Lamp (operation)   
					<RL1·2>   
					<23WA>   
					Lamp (check)   
					Thermostat (room temp.)   
					- 36 -   
				PRH-5, 8, 10YA   
					PRH-5, 8, 10YA-L   
					(SPECIAL ORDER : K CONTROL)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					PRH- 5YA,   
					···40A   
					Power supply   
					3Phase   
					380~415Volt   
					50Herts   
					PRH- 5YA-L   
					PRH- 8YA,   
					PRH- 8YA-L···50A   
					PRH-10YA,   
					PRH-10YA-L···60A   
					MC   
					INTERNAL   
					PROTECTOR   
					TB1   
					L1   
					52C   
					51C   
					Red   
					Red   
					White   
					Black   
					Red   
					L2   
					L3   
					White   
					Black   
					Black   
					51F2   
					TB2   
					X1   
					1 
					2 
					3 
					1 
					2 
					Red   
					R 
					R 
					N 
					Blue   
					White   
					Black   
					S1   
					S 2   
					MF2   
					1 
					2 
					T 
					T 
					PE   
					52F   
					51F1   
					Red   
					Red   
					DSA   
					White   
					Black   
					CN   
					MF1   
					Blue   
					Green/Yellow   
					Black   
					1 
					3 
					INTERNAL   
					PROTECTOR   
					F(3.15A)   
					TB3 11   
					11   
					15   
					TH2   
					HZ   
					HZ   
					14   
					30   
					IB   
					CZ   
					51F1   
					51F2   
					13   
					FZ   
					X1   
					63H   
					51   
					TB4   
					A 
					B 
					C 
					D 
					21   
					S4   
					52F   
					HZ   
					CZ   
					FZ   
					CM   
					26   
					D2   
					Tr   
					TH5   
					26   
					D1   
					X2   
					CZ   
					52C   
					CH   
					FZ   
					X1   
					52C   
					30   
					X2   
					CZ   
					R/C   
					30   
					CZ   
					8,10YA,YA-L ONLY   
					TB3 12   
					TB3 12   
					Caution,   
					Name   
					Symbol   
					MC   
					To protect each Fan motors and Compressor from abnormal current,   
					these Over current relays<51C>,<51F1,2>are installed.   
					Therefore,do not change factory set value of these Over current   
					relays.   
					Compressor motor   
					Fan motor(indoor)   
					Fan motor(outdoor)   
					Contactor(compressor)   
					Contactor(fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MF1   
					MF2   
					52C   
					52F   
					TB1~4   
					CH   
					Note:   
					1.The dotted lines show field wiring.   
					F 
					Tr   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					Transformer   
					51C   
					51F1,2   
					63H   
					26D1·2   
					21S4   
					FZ   
					Over current relay(compressor)   
					Over current relay(fanI/D,O/D)   
					High-pressure switch   
					Thermostat(defrost)   
					5.Specification subject to change without notice.   
					4-Way valve   
					Auxiliary relay(fan)   
					CZ   
					HZ   
					30CZ   
					X1·2   
					IB   
					Auxiliary relay(compressor)   
					Auxiliary relay(heater)   
					Auxiliary relay(check)   
					Auxiliary relay(defrost)   
					Indoor board   
					TH2   
					TH5   
					R/C   
					DSA   
					Thermistor(pipe)   
					Thermistor(room temp.)   
					Remote controller   
					Surge absorber circuit board   
					- 37 -   
				PRH-5, 8, 10YA   
					PRH-5, 8, 10YA-L   
					(SPECIAL ORDER : LOW TEMPERATURE)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					PRH- 5YA,   
					···40A   
					Power supply   
					3Phase   
					PRH- 5YA-L   
					MC   
					INTERNAL   
					PRH- 8YA,   
					PRH- 8YA-L   
					PRH-10YA,   
					···50A   
					380~415Volt   
					50Herts   
					PROTECTOR   
					···60A   
					TB1   
					L1   
					51C   
					52C   
					PRH-10YA-L   
					Red   
					White   
					Black   
					Red   
					Red   
					L2   
					L3   
					White   
					Black   
					Black   
					51F2   
					TB2   
					X1   
					52F2   
					TB2   
					1 
					2 
					3 
					2 
					2 
					2 
					2 
					2 
					2 
					R 
					1 
					R 
					1 
					R 
					S 
					T 
					R 
					S 
					T 
					Red   
					Red   
					Red   
					White   
					Black   
					N 
					Blue   
					S1   
					S 1   
					White   
					Black   
					White   
					Black   
					MF2   
					PE   
					T 
					1 
					T 
					1 
					52F1   
					51F1   
					51F3   
					Red   
					Red   
					52F3   
					52F4   
					White   
					Black   
					MF1   
					Black   
					Tr1   
					INTERNAL   
					PROTECTOR   
					F(3.15A)   
					TB3 11   
					11   
					51F3   
					TB4   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					HZ   
					16   
					15   
					HZ   
					14   
					F 
					51F1   
					51F2   
					63H   
					SW1   
					COOL   
					TB313   
					(3.15A)   
					HEAT   
					RL   
					SW2   
					FZ1   
					GL   
					C 
					H 
					26D3   
					X1   
					SW3   
					23WA   
					FZ   
					2 
					FZ   
					3 
					FZ   
					4 
					Tr2   
					FZ   
					2 
					AC   
					21   
					S4   
					220~   
					AC   
					240V   
					24V   
					51   
					C 
					26   
					D2   
					2 
					3 
					4 
					5 
					6 
					7 
					52   
					F1   
					26D4   
					52   
					F2   
					52   
					F4   
					CZ   
					FZ2   
					TB4   
					1 
					CZ   
					HZ   
					26   
					X2   
					26L   
					3 
					52   
					F3   
					FZ0   
					D1   
					TM   
					52C   
					CH   
					52   
					C 
					CZ   
					(3MIN)   
					FZ3   
					X1   
					FZ1   
					30   
					CZ   
					30   
					X2   
					FZ   
					3 
					CZ   
					FZ1   
					52C   
					FZ0   
					TM   
					FZ4   
					30   
					CZ   
					8 
					8,10YA,   
					12   
					YA-L ONLY   
					TB3 12   
					Caution,   
					Symbol   
					MC   
					Name   
					1.To protect each Fan motors and Compressor from abnormal current,   
					these Over current relays<51C>,<51F1,2,3>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressor from frequently "ON-OFF",timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					Compressor motor   
					Fan motor (indoor)   
					Fan motor (outdoor)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MF1   
					MF2   
					52C   
					52F1   
					TB1~4   
					CH   
					Note:   
					1.The dotted lines show field wiring.   
					F 
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					Tr1·2   
					51C   
					51F1,2,3   
					63H   
					26L   
					26D1~4   
					TM   
					21S4   
					Transformer   
					Over current relay(compressor)   
					Over current relay(fanI/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Thermostat (defrost)   
					5.Specification subject to change without notice.   
					Timer (anti short cycle)   
					4-Way valve   
					FZ0,1 Auxiliary relay (fan)   
					CZ   
					Auxiliary relay (compressor)   
					HZ   
					Auxiliary relay (heater)   
					Auxiliary relay (check)   
					Auxiliary relay (defrost)   
					Switch (operatin mode)   
					Switch (off)   
					30CZ   
					X1·2   
					<SW1>   
					<SW2>   
					<SW3>   
					<GL>   
					Switch (on)   
					Lamp (operation)   
					<RL>   
					Lamp (check)   
					<23WA>   
					52F2~4   
					FZ2~4   
					Thermostat (room temp.)   
					Contactor (fan O/D)   
					Auxiliary relay (fan O/D)   
					- 38 -   
				PRH-15, 20YA   
					PRH-15, 20YA-L   
					(SPECIAL ORDER : LOW TEMPERATURE)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					PRH-15YA   
					Power supply   
					3Phase   
					380~415Volt   
					50Herts   
					···100A   
					PRH-15YA-L   
					PRH-20YA   
					MC1   
					INTERNAL   
					···125A   
					PROTECTOR   
					PRH-20YA -L   
					52C1   
					51C1   
					TB1   
					L1   
					L2   
					L3   
					Red   
					White   
					Black   
					Red   
					Red   
					White   
					Black   
					Black   
					TB2   
					R11 R11   
					51F2   
					TB2   
					X1   
					52F2   
					1 
					2 
					3 
					Red   
					R12   
					S12 S12   
					T12 T12   
					R12   
					Red   
					Red   
					Red   
					Blue   
					N 
					White   
					Black   
					S11 S11   
					T11 T11   
					White   
					Black   
					White   
					Black   
					White   
					Black   
					MF2   
					PE   
					51F4   
					MC2   
					51C2   
					INTERNAL   
					PROTECTOR   
					52C2   
					52F3   
					Red   
					Red   
					Red   
					White   
					White   
					Black   
					Black   
					INTERNAL   
					PROTECTOR   
					Black   
					52F4   
					Tr1   
					51F3   
					TB3   
					TB3   
					52F5   
					X2   
					1 
					2 
					3 
					22   
					22   
					22   
					R 
					S 
					T 
					22   
					22   
					22   
					R 
					S 
					T 
					21   
					21   
					R 
					S 
					T 
					21   
					Red   
					R 
					S 
					T 
					Red   
					Red   
					21   
					White   
					Black   
					White   
					Black   
					White   
					Black   
					MF3   
					21   
					21   
					51F5   
					52F6   
					52F   
					51F1   
					Red   
					INTERNAL   
					PROTECTOR   
					52F7   
					Red   
					Tr2   
					White   
					Black   
					MF1   
					F 
					F(3.15A)   
					TB4 11   
					TB5   
					1 
					SWITCH BOX   
					(FIELD SUPPLY)   
					HZ   
					18   
					FZ0   
					51F1   
					HZ   
					TB4 14   
					F 
					30   
					30   
					SW1   
					C 
					(3.15A)   
					CZ1-2   
					CZ2-2   
					HEAT   
					COOL   
					RL1   
					RL2   
					SW2   
					TB4 13   
					51F4   
					51F2   
					51F5   
					GL   
					26D3   
					FZ   
					26D1   
					C 
					H 
					H 
					51F3   
					63   
					SW3   
					FZ   
					FZ   
					FZ   
					5 
					FZ   
					3 
					FZ   
					4 
					FZ   
					6 
					FZ   
					7 
					High   
					Low   
					Tr   
					X1 X2   
					X2   
					2 
					2 
					5 
					63   
					23WA   
					AC   
					H1   
					H2   
					CZ1   
					CZ2   
					220~   
					240V   
					AC   
					CZ1   
					CZ2   
					24V   
					51   
					51   
					2 
					3 
					4 
					5 
					6 
					7 
					8 
					9 
					C1   
					C2   
					26   
					TB5   
					52 52   
					C1 C2   
					21   
					52   
					C2   
					D4   
					26   
					26D4   
					S41   
					26D2   
					1 
					1 
					D3   
					52   
					52   
					C2   
					52   
					F2   
					52   
					F4   
					52   
					F5   
					52   
					F7   
					TM   
					TM   
					FZ2   
					FZ5   
					21   
					S42   
					CZ1   
					HZ   
					C1   
					(3MIN)   
					(3MIN)   
					26   
					L1   
					26   
					L2   
					52   
					C1   
					FZ0   
					26   
					D2   
					52   
					F3   
					52   
					F6   
					CH2   
					CZ2   
					X4   
					52   
					F 
					26   
					X3   
					3 
					3 
					D1   
					FZ6   
					FZ3   
					FZ1   
					FZ1   
					TM   
					CH1   
					2 
					FZ   
					FZ   
					6 
					X2   
					52   
					C1   
					FZ0   
					(2SEC)   
					3 
					30   
					30   
					X1   
					30   
					CZ1-1   
					30   
					CZ2-1   
					CZ1   
					2 
					CZ2   
					X4   
					FZ1   
					X3   
					52   
					C2   
					FZ4   
					FZ7   
					30   
					30   
					C3Z10-1   
					C3Z10-2   
					10   
					CZ2-1   
					CZ2-2   
					TB4 12   
					TB4 12   
					Symbol   
					Name   
					Caution,   
					1.To protect each Fan motors and Compressors   
					Compressor motor   
					Fan motor (indoor)   
					Fan motor (outdoor)   
					Contactor (compressor)   
					Contactor (fan I/D)   
					Terminal block   
					Crankcase heater   
					Fuse   
					MC1·2   
					MF1   
					MF2·3   
					52C1·2   
					52F1   
					TB1~5   
					CH1·2   
					F 
					from abnormal current,these Over current relays<51C1,2>,   
					<51F1~5>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					2.To protect the compressors from frequently "ON-OFF",timer<TM>is   
					installed. Therefore,do not change factory set value of this timer.   
					3.This timer<2>installed so that two compressors may never start at   
					the same time. The unit stop if the set value of the timer is changed.   
					Tr1~3   
					Transformer   
					Note:   
					51C1·2   
					51F1~5   
					63H1·2   
					26L1·2   
					26D1~4   
					TM   
					Over current relay(compressor)   
					Over current relay (fan I/D,O/D)   
					High-pressure switch   
					Thermostat(freeze protection)   
					Thermostat (defrost)   
					Timer (anti short cycle)   
					Timer   
					1.The dotted lines show field wiring.   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					5.Specification subject to change without notice.   
					2 
					4-Way valve   
					21S41·42   
					FZ0·1   
					CZ1·2   
					HZ   
					30CZ1-1, 2   
					30CZ2-1, 2   
					X1~4   
					<SW1>   
					<SW2>   
					<SW3>   
					<GL>   
					Auxiliary relay (fan)   
					Auxiliary relay (compressor)   
					Auxiliary relay (heater)   
					Auxiliary relay (check)   
					Auxiliary relay (check)   
					Auxiliary relay (defrost)   
					Switch (operation mode)   
					Switch (off)   
					Switch (on)   
					Lamp (operation)   
					<RL1·2>   
					Lamp (check)   
					<23WA>   
					26D1~4   
					52F2~7   
					Thermostat (room temp.)   
					Thermostat (ambiemt temp.)   
					Contactor (fan O/D)   
					Auxiliary relay (fan O/D)   
					- 39 -   
				PRH-5, 8, 10YA   
					PRH-5, 8, 10YA-L   
					(SPECIAL ORDER : K CONTROL & LOW TEMPERATURE)   
					CIRCUIT BREAKER   
					(FIELD SUPPLY)   
					PRH- 5YA,   
					···40A   
					Power supply   
					PRH- 5YA-L   
					3Phase   
					PRH- 8YA,   
					···50A   
					380~415Volt   
					50Hertz   
					PRH- 8YA-L   
					PRH- 10YA   
					MC   
					INTERNAL   
					···60A   
					PROTECTOR   
					PRH-10YA-L   
					TB1   
					52C   
					51C   
					L1   
					Red   
					Red   
					White   
					Red   
					L2   
					L3   
					White   
					Black   
					Black   
					Black   
					51F2   
					TB2   
					TB2   
					X1   
					1 
					2 
					3 
					52F2   
					R 
					S 
					T 
					R 
					S 
					T 
					R 
					R2   
					S 2   
					T2   
					1 
					1 
					1 
					1 
					1 
					1 
					2 
					Red   
					Red   
					Red   
					Blue   
					N 
					S 2   
					T2   
					White   
					Black   
					White   
					Black   
					MF2   
					White   
					Black   
					PE   
					52F1   
					51F1   
					51F3   
					Red   
					Red   
					52F3   
					DSA   
					White   
					Black   
					CN   
					1 
					3 
					MF1   
					Blue   
					Green/Yellow   
					Black   
					52F4   
					Tr1   
					INTERNAL   
					PROTECTOR   
					F(3.15A)   
					TB3 11   
					11   
					TH2   
					51F3   
					HZ   
					16   
					HZ   
					30   
					15   
					14   
					IB   
					CZ   
					TB3 13   
					51F1   
					FZ1   
					51F2   
					63H   
					26D3   
					X1   
					FZ   
					2 
					FZ   
					FZ   
					3 
					FZ   
					4 
					A 
					B 
					C 
					D 
					TB4   
					2 
					52   
					F1   
					21   
					S4   
					FZ1   
					HZ   
					CZ   
					26   
					D2   
					Tr2   
					51   
					C 
					26D4   
					52   
					F2   
					52   
					F4   
					FZ2   
					TH5   
					26   
					D1   
					X2   
					52   
					F3   
					CZ   
					52C   
					CH   
					FZ1   
					FZ3   
					X1   
					52C   
					30   
					X2   
					FZ   
					3 
					CZ   
					R/C   
					30   
					FZ4   
					CZ   
					12   
					8,10YA,YA-L ONLY   
					TB3 12   
					Caution,   
					Symbol   
					MC   
					Name   
					To protect each Fan motors and Compressor from abnormal current,   
					these Over current relays<51C>,<51F1,2,3>are installed.   
					Therefore,do not change factory set value of these Over current relays.   
					Compressor motor   
					Fan motor(indoor)   
					Fan motor(outdoor)   
					Contactor(compressor)   
					Contactor(fan I/D)   
					Terminal block   
					MF1   
					MF2   
					52C   
					52F1   
					TB1~4   
					CH   
					Note:   
					1.The dotted lines show field wiring.   
					Crankcase heater   
					Fuse   
					2.The figure in the parentheses show field supply parts.   
					3.Color of earth wire is yellow and green twisting.   
					4.Not specified color of wire is brown.   
					F 
					Tr1·2   
					51C   
					51F1,2,3   
					63H   
					26D1~4   
					21S4   
					FZ1   
					CZ   
					HZ   
					30CZ   
					X1·2   
					IB   
					Transformer   
					(compressor)   
					Over current relay   
					5.Specification subject to change without notice.   
					Over current relay(fanI/D,O/D)   
					High-pressure switch   
					Thermostat(defrost)   
					4-Way valve   
					Auxiliary relay(fan)   
					Auxiliary relay(compressor)   
					Auxiliary relay(heater)   
					Auxiliary relay(check)   
					Auxiliary relay(defrost)   
					Indoor board   
					TH2   
					52F2~4   
					FZ2~4   
					Thermistor(pipe)   
					Contactor(fan O/D)   
					Auxiliary relay(fan O/D)   
					Thermistor(room temp)   
					Remote controller   
					Surge absorber circuit board   
					TH5   
					R/C   
					DSA   
					- 40 -   
				ELECTRICAL OPERATION FLOW CHARTS   
					PR-5, 8, 10YC   
					START   
					POWER ON   
					CH ON   
					GL ON   
					30CZ ON (SELF HOLD)   
					NO   
					SW2 ON?   
					YES   
					FZ0,1 ON (SELF HOLD)   
					52F ON   
					MF1 OPERATE   
					YES   
					NO   
					23WA ON?   
					YES   
					CZ ON   
					TM ON   
					NO   
					PASS THE 3 MIN.?   
					YES   
					52C ON   
					MC OPERATE   
					MF2 OPERATE   
					CH OFF   
					SAFETY   
					NO   
					DEVICE OFF?   
					YES   
					30CZ OFF   
					52C OFF   
					MC STOP   
					MF2 STOP   
					RL ON   
					CH ON   
					SERVICE CALL   
					- 41 -   
				PRH-5, 8, 10YA   
					PRH-5, 8, 10YA-L   
					START   
					POWER ON   
					CH ON   
					GL ON   
					30CZ ON (SELF HOLD)   
					NO   
					SW3 ON?   
					YES   
					FZ0,1 ON (SELF HOLD)   
					52F ON   
					MF1 OPERATE   
					NO   
					NO   
					SW1 COOL?   
					HZ ON   
					YES   
					21S4 ON   
					23WA ON?   
					NO   
					23WA ON?   
					YES   
					CZ ON   
					YES   
					CZ ON   
					TM ON   
					TM ON   
					NO   
					PASS THE 3 MIN.?   
					YES   
					NO   
					PASS THE 3 MIN.?   
					YES   
					52C ON   
					MC OPERATE   
					MF2 OPERATE   
					52C ON   
					MC OPERATE   
					MF2 OPERATE   
					CH OFF   
					CH OFF   
					SAFETY   
					NO   
					DEVICE OFF?   
					NO   
					CONDENSING   
					< 
					TEMP. -12˚C?   
					= 
					YES   
					30CZ OFF   
					YES   
					26D1, 2 ON   
					52C OFF   
					MC STOP   
					MF2 STOP   
					X1 ON   
					X2 ON (SELF HOLD)   
					RL ON   
					CH ON   
					21S4 OFF   
					MF2 STOP   
					SERVICE CALL   
					NO   
					CONDENSING   
					< 
					TEMP. 6˚C?   
					= 
					YES   
					26D1, 2 OFF   
					X1, 2 OFF   
					21S4 ON   
					MF2 OPERATE   
					- 42 -   
				PR-15, 20YC   
					START   
					POWER ON   
					CH1, 2 ON   
					GL ON   
					30CZ1, 30CZ2 ON (SELF HOLD)   
					NO   
					SW2 ON?   
					YES   
					FZ0, FZ1 ON (SELF HOLD)   
					52F ON   
					MF1 OPERATE   
					YES   
					NO   
					23WA No.1 ON?   
					YES   
					CZ1 ON   
					TM1 ON   
					NO   
					PASS THE 3 MIN.?   
					YES   
					52C1 ON   
					MC1 OPERATE   
					MF2 OPERATE   
					CH1 OFF   
					NO   
					23WA No.2 ON?   
					YES   
					CZ2 ON   
					TM2 ON   
					NO   
					PASS THE 2 SEC.?   
					YES   
					52C2 ON   
					MC2 OPERATE   
					MF3 OPERATE   
					CH2 OFF   
					NO   
					No.2 SAFETY   
					DEVICE OFF?   
					NO   
					No.1 SAFETY   
					DEVICE OFF?   
					YES   
					30CZ2 OFF   
					YES   
					30CZ1 OFF   
					52C2 OFF   
					MC2 STOP   
					MF3 STOP   
					52C1 OFF   
					MC1 STOP   
					MF2 STOP   
					RL2 ON   
					RL1 ON   
					CH1 ON   
					CH2 ON   
					SERVICE CALL   
					- 43 -   
				PRH-15, 20YA   
					PRH-15, 20YA-L   
					HZ ON   
					START   
					POWER ON   
					21S41, 2 ON   
					CH1, 2 ON   
					NO   
					23WA No.2 ON?   
					GL ON   
					YES   
					CZ1 ON   
					30CZ1, 30CZ2 ON (SELF HOLD)   
					TM1 ON   
					NO   
					SW3 ON?   
					NO   
					NO   
					YES   
					PASS THE 3 MIN.?   
					FZ0, FZ1 ON (SELF HOLD)   
					YES   
					52F ON   
					MF1 OPERATE   
					TM2 ON   
					NO   
					NO   
					PASS THE 2 SEC.?   
					YES   
					SW1 COOL?   
					YES   
					52C2 ON   
					MC2 OPERATE   
					MF3 OPERATE   
					23WA No.1 ON?   
					YES   
					CH2 OFF   
					CZ1 ON   
					TM1 ON   
					NO   
					23WA No.1 ON?   
					YES   
					NO   
					PASS THE 3 MIN.?   
					YES   
					52C1 ON   
					MC1 OPERATE   
					MF2 OPERATE   
					52C1 ON   
					MC1 OPERATE   
					MF2 OPERATE   
					CH1 OFF   
					CH1 OFF   
					NO   
					No.1 CONDENSING   
					< 
					TEMP. -12˚C?   
					= 
					NO   
					23WA No.2 ON?   
					YES   
					26D1, 3 ON   
					YES   
					CZ2 ON   
					X1 ON   
					NO   
					X3 ON (SELF HOLD)   
					No.2 CONDENSING   
					TEMP. -12˚C?   
					= 
					TM2 ON   
					< 
					21S41 OFF   
					MF2 STOP   
					YES   
					NO   
					PASS THE 2 SEC.?   
					YES   
					26D2, 4 ON   
					X2 ON   
					NO   
					No.1 CONDENSING   
					< 
					X4 ON (SELF HOLD)   
					52C2 ON   
					MC2 OPERATE   
					MF3 OPERATE   
					TEMP. 6˚C?   
					= 
					21S42 OFF   
					MF3 STOP   
					YES   
					26D1, 3 OFF   
					CH2 OFF   
					No.2 SAFETY   
					DEVICE OFF?   
					NO   
					X1, 3 OFF   
					NO   
					No.2 CONDENSING   
					NO   
					No.1 SAFETY   
					DEVICE OFF?   
					< 
					TEMP. 6˚C?   
					= 
					YES   
					21S41 ON   
					MF2 OPERATE   
					30CZ2 OFF   
					YES   
					YES   
					30CZ1 OFF   
					52C2 OFF   
					MC2 STOP   
					MF3 STOP   
					YES   
					No.1 DEFROST   
					OPERATION?   
					52C1 OFF   
					MC1 STOP   
					MF2 STOP   
					NO   
					RL2 ON   
					21S42 ON   
					MF2 OPERATE   
					RL1 ON   
					CH1 ON   
					CH2 ON   
					SERVICE CALL   
					- 44 -   
				REFRIGERANT SCHEMATICS   
					PR-5YC   
					Condenser   
					Evaporator   
					ø19.05   
					High   
					Check   
					pressure   
					joint   
					switch   
					ø19.05   
					Check   
					joint   
					Pressure   
					gauge   
					ø12.7   
					Check   
					joint   
					ø22.2   
					Check   
					joint   
					Compressor   
					Capillary   
					Tube   
					ø12.7   
					ø12.7   
					Strainer   
					Dryer   
					: OPTION   
					Notes: This schematics shows one refrigerant cycle.   
					PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is   
					composed of two refrigerant cycles.   
					PR-8, 10, 15, 20YC   
					Condenser   
					Evaporator   
					ø19.05   
					High   
					pressure   
					switch   
					Check   
					joint   
					ø19.05   
					Check   
					joint   
					Pressure   
					gauge   
					ø12.7   
					Check   
					joint   
					ø22.2   
					Check   
					joint   
					Compressor   
					Capillary   
					Tube   
					ø12.7   
					ø12.7   
					Strainer   
					Dryer   
					: OPTION   
					- 45 -   
				PRH-5YA   
					Condenser   
					Evaporator   
					ø19.05   
					High   
					pressure   
					switch   
					4-Way   
					valve   
					Check   
					joint   
					Check   
					joint   
					ø19.05   
					Pressure   
					gauge   
					ø12.7   
					Check   
					joint   
					ø22.2   
					Check   
					joint   
					Compressor   
					Capillary   
					Tube   
					Capillary   
					Tube   
					ø12.7   
					ø12.7   
					Strainer   
					Check Strainer   
					valve   
					Dryer   
					: OPTION   
					Notes: This schematics shows one refrigerant cycle.   
					PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is   
					composed of two refrigerant cycles.   
					PRH-8, 10, 15, 20YA   
					Condenser   
					Evaporator   
					8, 15YA: ø22.0   
					10, 20YA: ø25.4   
					High   
					pressure   
					switch   
					4-Way   
					valve   
					Check   
					joint   
					8, 15YA: ø22.0   
					10, 20YA: ø25.4   
					Pressure   
					gauge   
					Muffler   
					ø15.88   
					ø15.88   
					Check   
					joint   
					Check   
					joint   
					ø25.4   
					Check   
					joint   
					Compressor   
					Capillary   
					Tube   
					Capillary   
					Tube   
					ø12.7   
					ø12.7   
					Strainer   
					Check Strainer   
					valve   
					Dryer   
					: OPTION   
					- 46 -   
				PRH-5YA-L   
					Condenser   
					Evaporator   
					ø19.05   
					High   
					pressure   
					switch   
					4-Way   
					valve   
					Check   
					joint   
					Check   
					joint   
					ø19.05   
					Pressure   
					gauge   
					ø12.7   
					Check   
					joint   
					ø22.2   
					Check   
					joint   
					Accumulator   
					Compressor   
					Capillary   
					Tube   
					Capillary   
					Tube   
					ø12.7   
					ø12.7   
					Strainer   
					Check Strainer   
					valve   
					Dryer   
					: OPTION   
					Notes: This schematics shows one refrigerant cycle.   
					PR-15,20YC or PRH-15,20YA or PRH-15,20YA-L is   
					composed of two refrigerant cycles.   
					PRH-8, 10,15,20YA-L   
					Condenser   
					Evaporator   
					8,15YA-L: ø22.0   
					10,20YA-L: ø25.4   
					High   
					pressure   
					switch   
					4-Way   
					valve   
					Check   
					joint   
					8,15YA-L: ø22.0   
					10,20YA-L: ø25.4   
					Pressure   
					gauge   
					Muffler   
					ø15.88   
					ø15.88   
					Check   
					joint   
					Check   
					joinøt25.4   
					Check   
					joint   
					Accumulator   
					Compressor   
					Capillary   
					Tube   
					Capillary   
					Tube   
					ø12.7   
					ø12.7   
					Strainer   
					Check Strainer   
					valve   
					Dryer   
					: OPTION   
					- 47 -   
				SAFETY & CONTROL DEVICES   
					PR-5YC   
					PRH-5YA   
					PRH-5YA-L   
					PR-8YC   
					PRH-8YA   
					PRH-8YA-L   
					PR-10YC   
					PRH-10YA   
					PRH-10YA-L   
					ITEM   
					NO.   
					COMPRESSOR OVER CURRENT RELAY   
					COMPRESSOR INTERNAL THERMOSTAT   
					HIGH PRESSURE SWITCH   
					51C   
					- 
					26.0A   
					27.5A   
					120˚C OFF   
					2.94MPa OFF   
					-2˚C IN   
					31.0A   
					110˚C OFF   
					130˚C OFF   
					63H   
					26L   
					26D1,2   
					51F1   
					51F2   
					- 
					FREEZE PROTECTOR   
					FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L)   
					INDOOR FAN MOTOR OVER CURRENT RELAY   
					OUTDOOR FAN MOTOR OVER CURRENT RELAY   
					OUTDOOR FAN MOTOR INTERNAL THERMOSTAT   
					FUSE (CONTROL CIRCUIT)   
					-12˚C IN, 6˚C OUT   
					3.2A   
					2.3A   
					3.6A   
					2.0A   
					150˚C OFF   
					3.15A   
					F 
					FUSE (OPERATION CIRCUIT)   
					F 
					3.15A   
					OUTDOOR FAN MOTOR OVER CURRENT RELAY   
					(USE THE OPTIONAL PARTS : LOW AMBIENT PARTS)   
					51F3   
					NO.   
					2.0A   
					PR-15YC   
					PRH-15YA   
					PRH-15YA-L   
					PR-20YC   
					PRH-20YA   
					PRH-20YA-L   
					ITEM   
					COMPRESSOR OVER CURRENT RELAY   
					COMPRESSOR INTERNAL THERMOSTAT   
					HIGH PRESSURE SWITCH   
					51C1,2   
					27.5A   
					31.0A   
					- 
					63H1,2   
					26L1,2   
					26D1,2,3,4   
					51F1   
					51F2,3   
					- 
					120˚C OFF   
					130˚C OFF   
					2.94MPa OFF   
					FREEZE PROTECTOR   
					-2˚C IN   
					FROST PROTECTOR (ONLY PRH-YA,PRH-YA-L)   
					INDOOR FAN MOTOR OVER CURRENT RELAY   
					OUTDOOR FAN MOTOR OVER CURRENT RELAY   
					OUTDOOR FAN MOTOR INTERNAL THERMOSTAT   
					FUSE (CONTROL CIRCUIT)   
					-12˚C IN, 6˚COUT   
					5.0A   
					6.6A   
					2.0A   
					150˚C OFF   
					3.15A   
					F 
					FUSE (OPERATION CIRCUIT)   
					F 
					3.15A   
					OUTDOOR FAN MOTOR OVER CURRENT RELAY   
					(USE THE OPTIONAL PARTS : LOW AMBIENT PARTS)   
					51F4,5   
					2.0A   
					ACCESSORY AVAILABILITY   
					PARTS CODE   
					PRH-8YA   
					- 
					MODEL NAME   
					DESCRIPTION   
					PR-5YC   
					PRH-5YA   
					- 
					PRH-5YA-L   
					PR-8YC   
					PRH-8YA-L   
					PR-10YC   
					PRH-10YA   
					- 
					PRH-10YA-L   
					PR- YC-K   
					PRH- YA-K   
					PRH- YA-LK   
					PR- YC   
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					- 
					K-Remote controller   
					- 
					- 
					- 
					- 
					- 
					- 
					PAC-201LC   
					- 
					PAC-202LC   
					- 
					PAC-203LC   
					- 
					- 
					PRH- YA   
					PRH- YA-L   
					PR- YC   
					PRH- YA   
					PRH- YA-L   
					PR- YC   
					- 
					- 
					PAC-201LC   
					- 
					- 
					- 
					PAC-202LC   
					- 
					- 
					- 
					PAC-203LC   
					- 
					Lowtemperaturecooling   
					Pressuregauge   
					Finguard   
					- 
					- 
					PAC-201LC   
					- 
					- 
					PAC-202LC   
					- 
					- 
					PAC-203LC   
					PAC001PG   
					- 
					- 
					PAC002PG   
					- 
					- 
					PAC003PG   
					- 
					- 
					- 
					- 
					PAC001PG   
					- 
					- 
					PAC002PG   
					- 
					- 
					PAC003PG   
					- 
					- 
					PAC001PG   
					- 
					- 
					PAC002PG   
					- 
					- 
					PAC003PG   
					PAC101FG   
					- 
					- 
					PAC102FG   
					- 
					- 
					PAC103FG   
					- 
					- 
					PRH- YA   
					PRH- YA-L   
					- 
					- 
					PAC101FG   
					- 
					- 
					- 
					PAC102FG   
					- 
					- 
					- 
					PAC103FG   
					- 
					PAC101FG   
					PAC102FG   
					PAC103FG   
					PARTS CODE   
					DESCRIPTION   
					MODEL NAME   
					PR-15YC   
					PRH-15YA   
					PRH-15YA-L   
					PR-20YC   
					PRH-20YA   
					PRH-20YA-L   
					PR- YC   
					PAC-201LCX2(PCS)   
					- 
					- 
					PAC-201LCX2(PCS)   
					- 
					- 
					Lowtemperaturecooling   
					PRH- YA   
					PRH- YA-L   
					PR- YC   
					- 
					- 
					PAC-201LCX2(PCS)   
					- 
					- 
					- 
					PAC-201LCX2(PCS)   
					- 
					- 
					- 
					PAC-201LCX2(PCS)   
					- 
					- 
					PAC-201LCX2(PCS)   
					PAC001PGX2(PCS)   
					- 
					PAC001PGX2(PCS)   
					- 
					Pressuregauge   
					Finguard   
					PRH- YA   
					PRH- YA-L   
					PR- YC   
					PRH- YA   
					PRH- YA-L   
					- 
					- 
					PAC001PGX2(PCS)   
					- 
					- 
					- 
					PAC001PGX2(PCS)   
					- 
					- 
					- 
					PAC001PGX2(PCS)   
					- 
					- 
					PAC001PGX2(PCS)   
					PAC104FG   
					- 
					- 
					- 
					- 
					PAC105FG   
					- 
					- 
					PAC104FG   
					- 
					- 
					- 
					PAC105FG   
					- 
					PAC104FG   
					PAC105FG   
					:Factory install   
					:Field install   
					- 48 -   
				PHYSICAL DATA   
					[PRODUCT]   
					ROOFTOP AIR-COOLED HEATPUMP PACKAGED AIR CONDITIONERS   
					Product type   
					PR,PRH,PRH-L SERIES   
					PR-10YC   
					Product number: Cooling type   
					PR-5YC   
					PR-8YC   
					PR-15YC   
					PR-20YC   
					Product number: Heat pump   
					Product number: Heat pump   
					PRH-5YA   
					PRH-5YA-L   
					PRH-8YA   
					PRH-10YA   
					PRH-10YA-L   
					PRH-15YA   
					PRH-15YA-L   
					PRH-20YA   
					PRH-20YA-L   
					PRH-8YA-L   
					28.1   
					23.8   
					19.7   
					8.3   
					Capacity   
					kw   
					kW   
					kW   
					kW   
					17.6   
					16.3   
					13   
					35.2   
					52.8   
					46.3   
					38.4   
					16.8   
					0.18   
					45.5   
					14.4   
					70.3   
					60.8   
					50.2   
					22.7   
					0.11   
					61.2   
					19.3   
					Coolingcapacity(AS1861)   
					29.7   
					SensibleCooling capacity(AS1861)   
					Cooling power consumption(Input)   
					ByPass Factor   
					25.3   
					5.4   
					11.4   
					0.19   
					15.1   
					4.6   
					0.24   
					23   
					0.18   
					Heating capacity (AS1861) (Only PRH-YA,PRH-YA-L)   
					Heating power consumption (Only PRH-YA,PRH-YA-L)   
					kW   
					kW   
					32   
					7 
					9.6   
					[ELECTRICAL]   
					Design voltage   
					Cycles   
					Volts   
					Hz   
					415   
					50   
					Phases   
					3 
					Power supply   
					Control voltage   
					Maximum voltage   
					Minimum voltage   
					Approx. starting current   
					Volts   
					Volts   
					Volts   
					Volts   
					Amps   
					415   
					240/24   
					415   
					380   
					100   
					62   
					87   
					115   
					135   
					Unit current (Nominal voltage and AS1861   
					maximum conditions)   
					Amps   
					12.8   
					20.6   
					25.7   
					37.9   
					50.9   
					Fan motorhp   
					HP   
					Amps   
					rpm   
					1.0   
					1.5   
					2 
					3 
					4 
					Fan motorcurrent   
					Fan motor speed   
					[COMPRESSOR]   
					Make   
					2.26   
					1,400   
					2.90   
					1,410   
					3.28   
					4.72   
					1,420   
					6.06   
					COPELAND   
					Model   
					CRNQ-0500-TFD QR90K1-TFD   
					QR12M1-TFD   
					QR90K1-TFD   
					QR12M1-TFD   
					2 
					Type   
					HERMETIC LINE START (RECIPROCATING)   
					Quantity   
					1 
					1 
					1 
					2 
					Nominalmotorhp   
					Locked rotor current   
					Normalrun current(AS1861)   
					Swept volume   
					HP   
					Amps   
					Amps   
					cc/rev   
					mm   
					5 
					7.5   
					10   
					2 
					✕ 
					7.5   
					2 
					✕ 
					10   
					59.5   
					7.65   
					101.92   
					49.78   
					26.19   
					83.4   
					11.7   
					177.45   
					95.2   
					15.62   
					221.8   
					83.4   
					95.2   
					2✕   
					11.74   
					2 
					✕ 
					15.22   
					2 
					✕ 
					177.45   
					2 
					✕221.8   
					Bore   
					55.58   
					4 
					Stroke   
					mm   
					18.29   
					22.86   
					2,900   
					18.29   
					22.86   
					Speed   
					rpm   
					Numberof cylinders   
					Oil charge   
					2 
					ml   
					2,070   
					3,250   
					2✕3,250   
					Type of oil   
					Calumet R015 or Witco 3GS   
					70   
					watts   
					40   
					2✕70   
					Crankcase heater   
					[REFRIGERATION SYSTEM]   
					Refrigerant   
					R22   
					5.8   
					Refrigerant charge per circuit   
					Numberof refrigerant controls   
					Refrigerant control   
					Reverse cycle valve (Only PRH-YA,PRH-YA-L)   
					kg   
					3.6   
					1 
					4.6   
					1 
					2✕4.6   
					2✕5.8   
					1 
					2 
					2 
					Capillary tube   
					4-Way valve   
					Reverse cycle defrost   
					Defrost system (Only PRH-YA,PRH-YA-L)   
					[EVAPORATOR]   
					Quantity   
					1 
					1 
					1 
					2 
					2 
					Facearea   
					sq.m   
					0.53   
					3 
					0.69   
					4 
					2✕0.65   
					Rows deep   
					3 
					3 
					4 
					Rows high   
					26   
					26   
					26   
					30   
					30   
					Finned length   
					Face velocity   
					Fins per meter   
					Fin materialthickness   
					Finmaterial   
					mm   
					m/s   
					800   
					1.7   
					512   
					1,046   
					2.4   
					2✕850   
					2.0   
					2.2   
					2.4   
					512   
					512   
					0.12   
					473   
					2.11   
					11   
					512   
					1.95   
					15   
					mm   
					Aluminium   
					1.95   
					Fins pitch   
					mm   
					mm   
					mm   
					1.95   
					10   
					1.95   
					13   
					Tube diameter   
					Gauge of copper tube   
					Numberof circuits   
					9.52   
					0.35   
					17   
					- 49 -   
				[PRODUCT]   
					ROOFTOP PACKAGE AIR COOLED HEATPUMP AND COOLING ONLY UNITS   
					PRH SERIES   
					Product type   
					Product number : Heat pump   
					[INDOOR AIR CIRCUIT]   
					Number of blowers   
					PRH-5YA   
					PRH-8YA   
					PRH-10YA   
					PRH-15YA   
					PRH-20YA   
					1 
					2 
					2 
					2 
					2 
					Diameterof blowers   
					mm   
					mm   
					253   
					393   
					282   
					Width of blowers   
					Blower drive   
					182   
					Beltdrive   
					1.5   
					Fan motor output   
					Normal fan motor run current   
					Air quantity   
					kW   
					A 
					0.75   
					2.26   
					900   
					1.1   
					2.2   
					3.0   
					2.90   
					1,400   
					3.28   
					4.72   
					2,800   
					6.06   
					3,160   
					L/s   
					1,660   
					Externalstatic pressure   
					Pa   
					100   
					200   
					Supply air dimensions(h   
					Return air dimensions(h   
					[CONDENSER]   
					Quantity   
					✕ 
					w)   
					mm ✕mm   
					300 ✕850   
					410 ✕900   
					300 ✕1,150   
					410 ✕1,200   
					428 ✕1,820   
					464 ✕1,879   
					✕w)   
					mm ✕mm   
					1 
					1.3   
					3 
					1 
					1.12   
					3 
					1 
					1.46   
					3 
					2 
					2 
					2✕1.32   
					3 
					Facearea   
					sq.m   
					2✕1.07   
					Rows deep   
					3 
					Rows high   
					30   
					23   
					30   
					30   
					37   
					Finned length   
					Face velocity   
					mm   
					m/s   
					1,700   
					1.2   
					473   
					1,920   
					2✕1,400   
					2.8   
					2.1   
					473   
					0.12   
					2.9   
					2.3   
					Fins per meter   
					Fin material thickness   
					Fin material   
					473   
					473   
					473   
					mm   
					Aluminium   
					Fins pitch   
					mm   
					mm   
					mm   
					2.11   
					11   
					2.11   
					2.11   
					9.52   
					0.35   
					15   
					2.11   
					2.11   
					Tube diameter   
					Gauge of copper tube   
					Numberof circuits   
					11   
					1 
					11   
					2 
					14   
					2 
					[OUTDOOR AIR CIRCUIT]   
					Number of fans   
					1 
					600   
					- 
					1 
					Diameter of fans   
					mm   
					mm   
					800   
					645   
					Pitch of fans   
					Fan drive   
					- 
					- 
					990   
					Direct drive   
					Fan motor output   
					Quantity   
					kw   
					0.15   
					1 
					0.35   
					1 
					0.35   
					1 
					2✕0.35   
					2 
					2✕0.35   
					2 
					Normal fan motor run current   
					Fan motor speed   
					Amps   
					rpm   
					0.6   
					650   
					1.3   
					1.3   
					2✕1.3   
					2✕1.3   
					Air quantity   
					L/s   
					1,583   
					3,083   
					1,300   
					2✕3,083   
					[ENCLOSURE AND FRAME]   
					height   
					mm   
					mm   
					mm   
					1,000   
					1,600   
					1,200   
					1,990   
					1,840   
					Dimension   
					Color   
					width   
					depth   
					1,000   
					Munsell 5Y8/1   
					Panel thickness   
					mm   
					mm   
					1.2   
					Condensate drain size   
					25.4   
					Weight   
					kg   
					299   
					73   
					393   
					75   
					413   
					75   
					698   
					79   
					729   
					79   
					Sound power level   
					Sound pressure level   
					dbA   
					dbA   
					62   
					64   
					64   
					68   
					68   
					- 50 -   
				INSTALLATION   
					All series of air conditioners are designed for outdoor installations and are to be placed on a slab or   
					rooftop, however if the air conditioner is to be installed in a plant room application, please contact your   
					equipment supplier prior to installation.   
					Access for both service and installation must be provided to the compressors, control wiring and fans as   
					shown below.   
					1.Clearances   
					(1) Care must be taken to prevent recirculation of   
					the condenser air. To stabilize compressor   
					condensing pressures it is recommended that   
					wherever possible the condenser air inlet side   
					be faced away from prevailing winds.   
					(2) For rooftop installation, the type of mounting   
					base depends on the roof construction. A built-   
					up roof may not support the weight of the unit   
					and so it may be necessary to support the unit   
					by adding structural members below it.   
					(3) The units are equipped with hoisting   
					plates for rigging and hoisting of the unit.   
					The hoisting plates are located in the base   
					of the unit.   
					When hoisting the unit with a crane,   
					spreader bars must be used to prevent   
					damage to side panels by the supporting   
					cables.   
					PR-15,20YC   
					PRH-15,20YA   
					PRH-15,20YA-L   
					PR-5 10YC   
					PRH-5~10YA   
					PRH-5~10YA-L   
					300mm(min. clearance)   
					300mm(min. clearance)   
					Condenser inlet   
					1,000mm(min. clearance)   
					Evaporator coil service   
					Condenser inlet   
					700mm(min. clearance)   
					Electrical   
					control circuit   
					1,000mm(min. clearance)   
					and compressor   
					Evaporator coil service   
					service   
					Condenser inlet   
					300mm(min. clearance)   
					1,000mm(min. clearance)   
					Evaporator coil service   
					1,500mm(min. clearance)   
					Condenser outlet   
					1,500mm(min. clearance)   
					Condenser outlet   
					2.Roof Mounting   
					(1) The figure shows the use of the roof curb available   
					for mounting these units.   
					(2) The curb should be sealed and fixed to the roof by   
					weather stripping. A suggested means of sealing   
					the unit and roof curb is shown below.   
					4-ø15roof mounting holes   
					6-ø15   
					Roof curb   
					Unit mounting holes   
					Unit   
					Seal with tar   
					Roof deck   
					Roof curb   
					- 51 -   
				3.Duct Work   
					PRH unit   
					Vertical air   
					plenum   
					(1) All series units are equipped with horizontal   
					supply and return air openings. Duct connection to   
					the unit should be made with duct flanges and   
					secured directly to the air openings with flexible   
					duct connectors to avoid normal noise transmission.   
					Plenum   
					divider   
					Insulation   
					Roof curb   
					(2) For vertical air supply, a field supply plenum should   
					be used.   
					The figure below shows the recommended method   
					for duct connection.   
					Roof curb   
					Duct   
					(3) To prevent air leakage, all duct seams should be   
					taped.   
					Roof line   
					Duct   
					Singleduct   
					divider   
					Ducts run in air spaces that are not air-conditioned   
					must be insulated and provided with a vapor barrier.   
					Ducts exposed to the outside must be   
					weatherproofed. For quiet operation, we   
					recommend that the insulation on the supply duct   
					be placed inside, lining the duct.   
					Duct connection with a vertical air plenum   
					(4) Where ducts from the outside enter a building, the   
					duct openings in the building should be sealed with   
					weather stripping to prevent rain, duct, sand,etc.   
					from entering the building.   
					(5) Correctly sized filters must be fitted and there is no   
					provision within the unit, however the filters may be   
					installed in the return air.   
					4.Drain piping   
					(1) A 1 FPT condensate drain fitting is provided. The   
					drain pipe can be led out at the right or left side.   
					Under standard specifications, it is led out at the left   
					side and the right side is covered.   
					> 
					A 70mm   
					= 
					> 
					B 2C   
					Drain piping   
					= 
					> 
					C 2XE.S.P   
					= 
					(2) The drain pipe must be provided with a trap on the   
					outside of the unit and also installed at an incline for   
					proper drainage, as shown below.   
					The drain pipe   
					should extend   
					below this level.   
					Drain trap   
					Note:ESP=External Static Pressure   
					(3) To prevent condensate formation and leakage,   
					provide the drain pipe with insulation to safeguard   
					against sweating.   
					Drain trap for condensate   
					(4) Upon completion of the piping work, check that there   
					is no leakage and that the water drains off properly.   
					- 52 -   
				5.Electrical Wiring   
					Remove the panel on the right side (PR,PRH-5 10) or the rear side (PR,PRH-15,20) of the unit and   
					connect the units power supply wiring to the proper terminals in the control box, as shown below.   
					PR-5YC   
					PRH-5YA   
					PRH-5YA-L   
					PR-8YC   
					PRH-8YA   
					PRH-8YA-L   
					PR-10YC   
					PRH-10YA   
					PRH-10YA-L   
					PR-15YC   
					PRH-15YA   
					PRH-15YA-L   
					PR-20YC   
					PRH-20YA   
					PRH-20YA-L   
					MODEL   
					INDOOR FAN MOTOR OUTPUT <kW>   
					2 
					0.75   
					1.1   
					1.1   
					1.5   
					1.5   
					2.2   
					2.2   
					3.0   
					3.0   
					4.0   
					<mm   
					mm   
					> 
					> 
					5.5   
					5.5   
					40   
					5.5   
					5.5   
					50   
					8 
					8 
					22   
					22   
					22   
					22   
					POWER SUPPLY   
					EARTH   
					WIRING   
					2 
					< 
					< A >   
					60   
					100   
					100   
					MAIN SWITCH   
					Std.   
					Control box   
					Terminal block   
					Terminal block   
					Control box   
					power supply   
					power supply   
					Wiring for PR,PRH-15,20(rear view)   
					Wiring for PR,PRH-5 10(right side view)   
					TN-NET SYSTEM (For European models only)   
					L1   
					L2   
					L3   
					N 
					PE   
					Note:   
					All electrical wiring must be comply with local electrical authority regulations.   
					6.Final Checks   
					After having installed the unit, check that:   
					(1) The unit is fixed securely.   
					(2) The unit is installed properly.   
					(3) The drain pipe is provided with a drain trap.   
					(4) The electrical wiring has been connected correctly and the terminal screws have been properly   
					tightened.   
					(5) The duct work has been performed correctly.   
					7.Trial Operation   
					(1) Before turning the unit on, measure the resistance between the terminals of the electrical parts and   
					ground with a 500V megger and check that the value is at least 1MΩ. If the measured value is below 1MΩ,   
					do not operate the unit.   
					(2) Check the operation of the high pressure switch by activating it. Operation should stop when the two leads   
					of the outdoor unit fan motor are removed from the contactor and cooling continues for 5~10min.   
					(3) Check that the indoor and outdoor fans are rotating in the proper direction.   
					(4) After having checked the above points, proceed with a trial operation of the unit.   
					- 53 -   
				INSTRUCTIONS FOR USE   
					1.CHECK POINTS FOR OPERATION   
					Check the following points before you operate your air conditioner.   
					(1) Check that there is nothing blocking the flow of air from the air outlet into the air inlet.   
					Indoor Unit   
					Outlet grille   
					Inlet grille   
					Ceiling   
					Ceiling   
					Obstacle blocking air inlet   
					Obstacle blocking air inlet   
					Outdoor Unit   
					Obstacle blocking air inlet   
					(2) Make sure the air conditioner is properly grounded by checking the ground terminal .   
					Ground   
					- 54 -   
				2.CAUTION FOR USE   
					Keep the following points in mind to safeguard against failures and breakdowns.   
					(1) This air conditioner does not restart within 3min.   
					after shut down.   
					3 Minutes   
					(These models have a crankcase heater in the   
					Shutdown   
					Operation   
					compressor. If the air conditioner is shut down   
					for a short time, please do not turn the power   
					switch to OFF, but turn the operation switch to OFF.)   
					(2) If the air conditioner is shut down by a power failure,   
					set the operation switch to OFF. When the power is   
					restored, normal air conditioner operation can be   
					resumed.   
					(3) Do not stick rods or other objects through the air   
					outlet during operation since this may result in   
					equipment damage or personal injury.   
					3.MAINTENANCE   
					For superior performance and lasting durability, please do not forget to conduct   
					proper and regular maintenance.   
					3.1 Cleaning the Air Filter   
					Clean the air filter about once a week with a neutral cleanser and leave it to dry in a shady location. Clean   
					more regularly if the air filter gets very dirty.   
					If the filter gets blocked, air will not be sucked in properly, and the cooling effect will deteriorate. Failure to   
					clean the air filter may result in equipment breakdown or malfunctions.   
					3.2 Cleaning panels   
					Clean dirt off front panel as follows.   
					Fingermarks   
					Use a household neutral cleanser such as for   
					dishes or vegetables. Moisten a soft cloth with   
					Neutral   
					Cleanser   
					the cleanser, then wipe lightly. Next,wipe three   
					or four times with another soft cloth moisten   
					Grease   
					with water. Finally, wipe off all the remaining   
					cleanser with a soft cloth.   
					Moisten a soft cloth with the alcohol, then wipe   
					off lightly. Isopropyl alcohol is sold at stores as   
					reagents in small quantities.   
					Adhesive   
					Isopropyl   
					alcohol   
					Note:   
					Alcohol is highly combustible. Take extreme   
					Paste   
					care when handling. Also, do not use paint or   
					adhesive thinner.   
					3.3 Cleaning the Outdoor Unit Heat Exchanger   
					If you use your air conditioner for prolonged periods,   
					the outdoor heat exchanger will become dirty, impairing   
					its function and reducing air conditioners performance.   
					Consult your equipment supplier or air conditioning   
					contractor on how to clean the heat exchanger.   
					Heat exchanger   
					Heat exchanger   
					- 55 -   
				4. PREPARING FOR OPERATION AFTER PROLONGED SHUTDOWN   
					When the usage season starts, proceed with the following before starting operation:   
					(1)Clean the air filter.   
					(2)Do not use the unit immediately. Turn the main power switch on for a period of 3 hours before restarting   
					cooling / heating operation. This allows the compressors to come up to the correct operation temperatures.   
					Failure to do this, could cause compressor failure.   
					5.PREPARING FOR PROLONGED SHUTDOWN   
					After the usage season is over, prepare the air conditioner for later use by:   
					(1)Setting the power switch to OFF.   
					(2)Consulting your Air conditioning specialist for detailed information.   
					6.TROUBLESHOOTING   
					If any trouble occurs, turn the operation (start or run) switch off immediately.   
					Symptom   
					Possible cause   
					Power failure.   
					Remedy   
					Wait for power supply   
					recovery.   
					Both fan and compressor   
					do not run.   
					Blown fuse of power   
					source switch.   
					Contact your   
					Air conditioning specialist   
					. 
					Excessively low power   
					source voltage.   
					Ask your electric power   
					company.   
					For temperature control,   
					• decrease the set   
					temperature at cooling.   
					• increase the set   
					temperature at heating.   
					The set temperature of   
					thermostat is   
					• excessively high for   
					cooling.   
					• excessively low for   
					heating.   
					Fan runs but compressor   
					does not run.   
					Can not be operated as   
					it is out of temperature   
					control range.   
					The room temperature is   
					• excessively low for   
					cooling.   
					• excessively high for   
					heating.   
					Air outlet and inlet   
					are blocked.   
					Remove blocking matter.   
					Clean it.   
					Fan runs but stops   
					immediately.   
					The filter installed in   
					the field is clogged   
					with dust.   
					Windows and doors are   
					being opened.   
					Close them.   
					Air outlet and inlet   
					are blocked.   
					Remove blocking matter.   
					Runs but without   
					cooling/heating.   
					For temperature control,   
					• decrease the set   
					temperature at cooling.   
					• increase the set   
					temperature at heating.   
					The set temperature of   
					thermostat is   
					• excessively high for   
					cooling.   
					• excessively low for   
					heating.   
					Insufficient   
					refrigerant charge.   
					Contact your   
					Air conditioning specialist   
					. 
					Note:   
					If the unit does not operate normally after troubleshooting, please contact your local equipment supplier or   
					air conditioning contractor.   
					- 56 -   
				SPECIFICATION GUIDELINES   
					Please supply and install a one piece, air to air reverse cycle air conditioning system.   
					The system shall be completely assembled, tested and have a complete refrigeration charge ready for   
					installation and operation from the factory.   
					The system shall operate at outdoor ambient temperatures as high as 46˚C.   
					The system shall have a total cooling capacity of   
					L/s at ˚C db and ˚C wb entering indoor coil temperature with a   
					entering   
					the outdoor coil.   
					kW or greater with an indoor air quantity of   
					˚C temperature   
					The system shall have a sensible heat capacity of   
					˚C.   
					kW or greater with a room db temperature of   
					The total heating capacity (without electric element heaters) shall be   
					kW or greater at   
					˚Cdb,   
					˚C wb outdoor air conditions, with   
					˚C of indoor air entering indoor coil at ˚C db. One   
					kW electric heater element (accessory) shall be furnished.   
					The compressors shall be a welded high efficiency hermetic type with internal vibration isolation and be   
					equipped with a crankcase heater.   
					Compressors shall be protected by a factory installed anti-cycle device and provide a 3 minute delay before   
					compressor can restart.   
					Coils shall be of non-ferrous construction with mechanically bonded aluminium plate fins. Outdoor coils   
					shall be made, of 9.52mm OD, 0.35mm thick seamless copper tubes mechanically bonded to 0.12mm thick   
					aluminium plate fins.   
					Coils with multiple stage refrigeration systems shall consist of independent circuits. Face area of the coil   
					2 
					shall not be less than   
					M . The coil shall be factory pressure and leak tested at 3,233 kPa pressure.   
					2 
					The indoor coil face area shall be not less than   
					M .   
					Multi-wing propeller type fans shall be fitted at the condenser and shall be dynamically balanced, to ensure   
					smooth airflow and shall discharge vertically and be direct driven by a weatherproof three phase squirrel   
					cage   
					kW induction motor.   
					The system shall be factory wired and all electrical wiring must comply with the Local wiring code. (Controls   
					and control wiring shall be supplied by the contractor). Compressors and fan motors shall have both internal   
					and current sensitive overload devices.   
					An automatic defrost control shall be included to accomplish defrosting (only if required) every   
					minutes for a period of   
					minutes.   
					A low voltage transformer (24V) shall be factory installed in the unit for an external control circuit.   
					High pressure switch (pre-set) shall be factory installed.   
					The enclosure shall be a single, enclosed, weatherproof casing constructed of phosphatised, zinc coated   
					steel with acrylic resin primer and ivory white baked enamel finish.   
					The unit shall be provided with hoisting plates for rigging and hoisting the unit. The hoisting plates shall be   
					located in the base of the unit.   
					The unit shall have a 25mm OD male drain connection provided. The drain pipe shall be accessible from   
					either the left or right side of the unit. A blanking cap shall be provided to cap the drain outlet not being   
					used.   
					The duct (field supply) shall be fully insulated with fiber glass insulation to prevent sweating and to minimize   
					sound.   
					Each unit shall have a drain pan of 1mm thick steel coated with epoxy resin enamel.   
					The enclosure shall have openings provided for power connections. Access for both service and installation   
					shall be provided to compressors, control wiring, filters, electric heaters (when fitted) and fans.   
					Side panels and top panels shall be removable for easy service access.   
					The unit maximum dimensions shall be : height:   
					mm, width:   
					mm and depth:   
					mm.   
					Due to continuous product development, these guidelines are subject to change.   
					- 57 -   
				MEMO   
					- 58 -   
				DATA BOOK PR,PRH   
					MITSUBISHI ELECTRIC CORPORATION   
					HEAD OFFICE DENKI BLDG., MARUNOUCHI,TOKYO 100,TELEX J24532 CABLE MELCO TOKYO   
					New publication effective Jan. 1999.   
					Specifications subject to change without notice.   
					Issuued in January. 1999 MEE98K036   
					Printed in Japan.   
				 | 
Nokia Extra Power Dc 11 User Manual
Panasonic Hq 2051th User Manual
Samsung Aqv18j User Manual
Sanyo Rcs Sh80ug User Manual
Sharp Af 08erl User Manual
Sharp Afs80fx User Manual
Soleus Air Air Conditioner Gm Ttw 12ese User Manual
Sony Bcg 34hue User Manual
Universal Power Group Consumer Battery Solutions User Manual
Xerox All In One Printer Workcenter M20 User Manual