WHITE-RODGERS
COMFORT-SET 90® SERIES
HEAT PUMP INSTALLATION/CONFIGURATION
INSTALLATION
DESCRIPTION
This White-Rodgers Automatic Setback
Digital Thermostat uses microcomputer
technology to provide precise time and
temperature control. This thermostat offers
the flexibility to design heating and cooling
programs that fit building needs. This
thermostat is adaptable to most 24 volt
residential forced air heat pump systems with
electric or fossil fuel auxiliary.
SPECIFICATIONS
1F94-371: 7 Day programming; residen-
Standard Systems:
Single-stage or two-stage compressor
heat pump.
Operating Ambient Temperature:
32° to 110°F (0° to 43°C)
Operating Humidity Range:
90% non-condensing max.
tial applications
ELECTRICAL DATA
THERMAL DATA
Electrical Rating:
Shipping Temperature Range:
-4° to 149°F (-20° to 65°C)
Setpoint Temperature Range:
45° to 99°F (7° to 37°C)
20 to 30 VAC, 50/60 Hz with common
0.05 to 1.5 Amps per terminal
2.5 Amps maximum total load (all
terminals combined)
PRECAUTIONS
This thermostat is intended for use with a
low voltage system. Do not use on a line
voltage system.
WARNING
!
CAUTION
!
Do not short out terminals on gas valve
or primary control to test. Short or
incorrect wiring will damage thermostat
and could cause personal injury and/or
property damage.
To prevent electrical shock and/or
equipment damage, disconnect electric
power to system at main fuse or circuit
breaker box until installation is
complete.
Do not exceed ratings shown in the Specifi-
cations section, above. If in doubt about the
electrical ratings of your heating/cooling
system, have it inspected by a qualified
heating and air conditioning contractor or
licensed electrician.
Do not use on circuits exceeding
specified voltage. Higher voltage will
damage thermostat and could cause
shock or fire hazard.
NOTE
Read all instructions thoroughly before
beginning installation.
All wiring must conform to local and
national electrical codes and ordinances.
Thermostat installation and all compo-
nents of the system shall conform to
Class II circuits per the NEC code.
This control is a precision instrument, and
should be handled carefully. Rough handling
or distorting components could cause the
control to malfunction.
Part No. 37-6186B
Replaces 37-6186A
0121
Download from Www.Somanuals.com. All Manuals Search And Download.
HEAT PUMP TERMINAL OUTPUTS
Use the terminal output information below to
help you wire the thermostat properly for
your heat pump system type. After wiring,
see CONFIGURATION section for proper
thermostat configuration.
Refer to equipment manufacturers’ instruc-
tions for specific system wiring information.
This thermostat is designed to operate a
single-transformer system. If you have a two-
transformer system, cut and tape off one
transformer. If transformer safety circuits
are in only one of the systems, remove the
transformer of the system with NO safety
circuits. If required, replace remaining
transformer with a 75VA Class II transformer.
After disconnecting one transformer, the two
commons must be jumpered together.
You can configure the thermostat for use
with the following heat pump system types:
HEAT PUMP TYPE 1. Single-stage
compressor system; gas or electric backup.
HEAT PUMP TYPE 2. Multi-stage or two-
compressor system; gas or electric backup.
HEAT PUMP TYPE 3. System requiring
separate signals for heat (W1, W2, W3) and
cool (Y1); gas or electric backup.
THERMOSTAT TERMINALS (Upper)
L
PH
D
SA
SB
SC
OT
Malfunction Light X-10 Module Input Not Used Remote Sense A Remote Sense B Remote Sense C
Outdoor Sensor
THERMOSTAT TERMINALS (Lower)
SYSTEM
E
C
R
W3/A1
W2
E2/P
W1
Y2
Y1
B
O
G
Single-stage compressor system; gas or electric backup
E2 - Emergency
mode constant
output.
P - All other modes
constant output.
Heat mode 3rd
stage.
Emergency mode
2nd stage.
Heat and cool Energized in
Emergency
mode first
stage
Blower/Fan Energized
on call for Heat and
Cool
24 Volt
(Common)
24 Volt Emergency mode
(Hot) 3rd stage
Heat mode
2nd stage
modes 1st
stage
Heat, Off,
Emergency
Mode
Energized in
Cool Mode
Heat Pump 1*
No Output
(compressor)
Multi-stage or two compressor system; gas or electric backup
E2 - Emergency
mode constant
output.
P - All other modes
constant output.
Heat and cool Heat and cool Energized in
Emergency
mode first
stage
Blower/Fan Energized
on call for Heat and
Cool
24 Volt
(Common)
24 Volt Emergency mode Emergency mode
(Hot) 3rd stage 2nd stage.
Heat mode
3rd stage
modes 2nd
stage
modes 1st
stage
Heat, Off,
Emergency
Mode
Energized in
Cool Mode
Heat Pump 2*
(compressor 2) (compressor 1)
System requiring separate signals for heat (W1, W2) and cool (Y1); gas or electric backup
E2 - Emergency
Heat mode 3rd
stage.
Heat mode 2nd
stage.
Energized in
Emergency
mode first
stage
mode constant
output.
Blower/Fan Energized
on call for Heat and
Cool
24 Volt
(Common)
24 Volt
(Hot)
Heat mode
1st stage
Cool mode 1st Heat, Off,
Energized in
Cool Mode
Heat Pump 3**
No Output
Emergency mode Emergency mode
stage
Emergency
Mode
P - All other modes
constant output.
3rd stage
2nd stage
* If system does not provide connection to E, jumper W1 to E to provide Aux heating in emergency mode.
** If system does not provide connection to E, jumper W2 to E to provide Aux heating in emergency mode.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CONFIGURATION
SWITCHES
RESET SWITCH
See the Troubleshooting section at the end
of this document for more information about
the function of this switch.
E2/P SWITCH
1
2
The E2/P switch is located on the back of the
thermostat body (see fig. 2). This switch
controls how the E2/P terminal of the
thermostat will be energized. When the
switch is in the E2 position (down), the E2/P
terminal will be energized only when in
emergency heat. When the switch is in the P
position (up), the E2/P terminal will always
be energized except when in emergency heat.
Consult the equipment manufacturer or a
qualified heating/cooling service person
before setting this switch. If your system has
no connection to E2/P, no change in the
switch setting is required.
S18
S19
P
E2
Reset switch
1
2 E2/P switch
Figure 2. Switch locations on back of thermostat body
INSTALLER CONFIGURATION
BEFORE TURNING POWER ON, please
read the following instructions. Before
operating the system, you must configure
the thermostat to operate properly with
your equipment.
or a qualified heating and air conditioning
service person. If your system controls fan
operation (as with most fossil fuel systems),
set this item to OFF. Note that with heat
pump systems, the fan always cycles with the
compressor.
TIME
buttons. Then press and hold SET
and
DAY
SET
for approximately 3 seconds to
enter the Installer menu. The display will
change to show the first item on the Installer
menu (multi-stage/heat pump selection). Use
the following text, along with the Installer
table on page 5, to guide you through the
menu.
The thermostat, as it comes from the factory,
is configured to operate a standard single
stage heat pump system. In this configura-
tion, the thermostat will turn on the fan
immediately on a call for heat. If you are
unsure whether your system requires the
thermostat to control the fan, contact your
furnace/air conditioning system manufacturer
or a qualified heating/air conditioning
service person.
SET CYCLE HEAT, COOL, AUX
(ANTICIPATION).
Once in the menu, you set each item to the
(Installer table steps 3 through 5). These
items allow the cycle times in heating,
cooling and auxiliary to be increased or
decreased. The factory set values can be
adjusted higher for longer cycles or lower for
shorter cycles.
proper selection using
or
, then
FWD
momentarily press TIME
to change
BACK
the display to the next step or TIME
to return to the previous item.
To exit the menu at any time and return to
NOTE: Some manufacturers still instruct you
to set the anticipator to the current draw of
the equipment. That instruction applies only
to mercury bulb or mechanical thermostats; it
does not apply to this digital thermostat. As
configured at the factory, this thermostat will
maintain an accurate temperature. No
further adjustment is necessary, although
you can use these menu items to customize
the performance of the thermostat to your
requirements.
Your new thermostat has an Installer menu,
which allows you to customize the thermostat
to meet your requirements. (The thermostat
also has a User menu and a Keypad
Lockout menu. These menus are explained
further in the Operating Instructions.)
RUN
program operation, press PROGRAM
.
HEAT PUMP COMPRESSOR
CONFIGURATION.
(Installer table step 1) Use this item to select
the number of heat pump compressors and
how they are connected.
The menu settings can be changed at any time
to meet system or personal requirements.
ELECTRIC HEAT FAN
CONFIGURATION.
ENTERING THE CONFIGURATION
MENUS.
(Installer table step 2.) This menu item
The adjustment range for HEATING is from
9 to 40 for heat pump. The factory preset is
13. The adjustment range for COOLING is
from 9 to 40. The factory preset is 13. The
heating and cooling settings will not go
below 9 because compressors require a
longer cycle. The adjustment range for
AUXILIARY is from 1 to 40. The factory
preset is 6.
determines whether fan control will be
After properly wiring the thermostat, turn on
power to the system. Momentarily press
RUN
through the thermostat or through the heating
system. If you have an electric heat or other
system that REQUIRES the thermostat to
control the fan, set this item ON. This allows
the thermostat to energize the fan immedi-
ately on a call for heat. If you are unsure if
the system requires the thermostat to control
the fan, contact the equipment manufacturer
PROGRAM
to make certain the
thermostat is in the run program mode, then
BACK
FWD
press TIME
and TIME
at the
same time to enter the User Configuration
menu. When the display changes to the first
item in the configuration menu, release the
(Continued on page 6)
4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER TABLE
NOTE: You must be in the User
Configuration Menu to enter the
FWD
Installer Menu. Press TIME
BACK
and TIME
at same time.
See
Page
Step
Press Button(s)
Displayed (Factory Default) Press
or
to select:
COMMENTS
TIME
DAY
Selects:
4
4
1
SET
and SET
HEAT PUMP
(1)
2 OR 3
1. one compressor on Y1.
2. two compressors on Y1, Y2.
3. one compressor on W1.
(hold for approx.
3 seconds)
Fan cycles with call for Emergency heat if ON.
Fan always cycles with pump stages.
ELECT HEAT FAN
(ON)
OFF
4
4
2
3
4
5
6
7
8
9
TIME FWD
FWD
Selects HEAT anticipation adjustment.
TIME
9 to 40
9 to 40
1 to 40
SET CYCLE HEAT
(13)
FWD
TIME
SET CYCLE COOL
(13)
Selects COOL anticipation adjustment.
4
4
6
FWD
TIME
SET CYCLE AUX
(06)
Selects AUXILIARY stage anticipation adjustment.
Selects time delay for COOL fan OFF.
FWD
TIME
COOL FAN DELAY OFF
(00)
0 to 127 seconds
FWD
TIME
FAN DELAY ON
(01)
Selects time delay for fan ON for compressor stages.
1 to 30 seconds
0 to 127 seconds
6
6
6
FWD
TIME
HEAT FAN DELAY OFF
(00)
Selects time delay for HEAT fan OFF in Emergency
mode only when ELECT HEAT FAN (Step 2) is ON.
FWD
TIME
Fossil Fuel Kit Alternative option. Turns compressor
OFF if Auxiliary is ON for longer than one minute.
(Heat Pump 1 & 2)
PUMP
(ON)
OFF
Selects compressor short-cycle protection enabled
or OFF.*
COMP LOCK
(OFF)
ON
ON
6
10
11
12
TIME FWD
FWD
TIME
ECON
(OFF)
Economizer option. Long Y1 cycles for cooling
with outdoor air
6
6
Allows selection of HEAT, EMER and COOL or
HEAT, EMER, COOL and AUTO with SYSTEM
button.
TIME
HEAT-EMER-OFF-COOL- HEAT-EMER-OFF-COOL
AUTO
FWD
Selects Remote Sensor A (connected to SA) if ON.
Selects Remote Sensor B (connected to SB) if ON.
Selects Remote Sensor C (connected to SC) if ON.
13
14
TIME
REMT SEN A
(OFF)
ON
ON
6
6
FWD
FWD
REMT SEN b
(OFF)
TIME
FWD
REMT SEN C
(OFF)
6
7
TIME
ON
15
16
FWD
STAT SEN L
(ON)
OFF
When OFF, disables local sensor if a remote sensor
is enabled.
TIME
Returns to normal operation
PROGRAM
RUN
* NOTE: COMP LOCK OFF permanently
defeats compressor lockout. You must turn
this selection ON if you do not have a
system that already provides compressor
short-cycle protection. Please see “Lockout
Bypass Option” to temporarily override
compressor lockout.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
The chart below shows how this adjustment
range affects thermostat performance.
need for a separate fossil fuel kit, although
we recommend that you consult the heat
pump system manufacturer before using this
feature instead of a kit. This item will allow
the thermostat to turn the heat pump
ECONOMIZER FEATURE.
(Installer table step 11). This item allows
longer Y1 cycles for cooling with outdoor
air.
PROGRAMMABLE COOL FAN-OFF
AND FAN-ON DELAY.
(Installer table steps 6 and 7.) These items
allow a selection of 0 to 127 seconds of fan-
off delay after the thermostat has satisfied the
call for cool, or a fan-on delay of 1 to 30
seconds on a call for cool (or heat pump
compressor activation).
compressor off if the auxiliary is on for more
than one minute, to prevent compressor head
pressure from getting too high. To use this
feature instead of a kit, select PUMP OFF.
DISABLING AUTOMATIC
CHANGEOVER MODE.
(Installer table step 12). This thermostat, as
configured at the factory, provides automatic
changeover, which allows the thermostat to
switch between heating and cooling to
maintain temperature. In this configuration,
when you press the SYSTEM button, the
thermostat will go through HEAT-EMER-
OFF-COOL-AUTO. Select HEAT-EMER-
OFF-COOL to disable the automatic
changeover feature.
COMPRESSOR LOCKOUT.
(Installer table step 10). This thermostat is
capable of protecting the system against
premature compressor failure by “locking
out” the compressor for at least five minutes
after each cycle. When the thermostat is in
compressor lockout, the word COOL will
flash on the display. With heat pump
systems, the word HEAT will flash if the
lockout occurs during a heat cycle. During
this period, the compressor will not be
energized.
The fan-off delay allows the fan to continue
running after the compressor has shut off.
This distributes the cool air that would
otherwise stay trapped in the air conditioning
coils through the ducts. Ideally the timing
would be set so the fan shuts off just as the
cool air is exhausted. If this timing is set too
long the fan may begin blowing warm air
before it shuts off. Shortening the fan-off
delay will prevent this.
OPTIONAL REMOTE TEMPERA-
TURE SENSE.
(Installer table steps 13 through 15). Up to
three remote sensors (part # F145-1328) can
be attached to this thermostat to sense indoor
temperature at locations away from the
thermostat. Each sensor may be located as
far as 200 feet away from the thermostat.
This is an excellent feature if the thermostat
is in a poor location for sensing temperature
or if you want to install the thermostat in a
separate room to prevent tampering. (Refer
to the installation instructions included with
the remote sensor for proper installation and
wiring.) After installing and connecting the
remote sensor(s) to the thermostat, use these
menu items to enable each remote indoor
temperature sensor (A, b and/or C). Note that
if SENSOR A, b or C are set to ON in the
menu, but no sensor is installed, or if the
sensor is not functioning, when you exit the
menu, CHECK STAT SYSTEM will be
displayed. To correct this, check for proper
remote sensor installation and wiring. If
necessary, return to the menu and be sure that
the remote sensor items are set correctly.
A short delay to allow the A-coil to cool
off (or warm up in heat pump) before the
fan turns on may be preferred. This also
allows the compressor and the fan to come
on at slightly different times, which allows
full power to the compressor on start up.
Recommended setting for fan-on delay is
10 seconds or less. A system that does not
have a high head pressure cutout should
have a delay of 10 seconds or less.
If the system has short-cycle protection, this
item should not need to be enabled. How-
ever, if your system does not have short-
cycle protection, turn COMP LOCK ON.
This will protect the compressor from short-
cycling and potential premature compressor
failure.
Note that COMP LOCK OFF permanently
disables compressor lockout. If you need to
temporarily disable compressor lockout,
please see Lockout Bypass Option.
PROGRAMMABLE HEAT FAN-OFF
DELAY.
Lockout Bypass Option
(Installer table step 8.) This item allows a
selection of 0 to 127 seconds of fan-off delay
after the thermostat has satisfied the call for
heat when ELECT HEAT FAN is selected
ON and system is in Emergency mode.
FOR QUALIFIED SERVICE TECH-
NICIANS’ USE ONLY.
HOMEOWNERS SHOULD NOT USE
THIS FEATURE DUE TO POSSIBIL-
ITY OF EQUIPMENT OR PROP-
ERTY DAMAGE, OR PERSONAL
INJURY.
The fan-off delay allows the fan to continue
running after the burner, heating element,
etc. has shut off. This distributes the heat that
would otherwise stay trapped in the ducts.
Ideally the timing would be set so the fan
shuts off just as the warm air is exhausted. If
this timing is set too long the fan may begin
blowing cool air before it shuts off. Shorten-
ing the fan-off delay will prevent this.
COMPRESSOR SHORT TERM CYCLE
PROTECTION
The temperature at each remote sensor can
be displayed by pressing the light button
twice within one second with the thermostat
in program run or hold mode. Temperatures
at the outdoor and indoor remote sensors will
be displayed with subsequent presses of the
light button in the following order (if
If this thermostat has been configured to
provide short-cycle protection, during the
5-minute lockout period the thermostat
will lock out the compressor to allow
head pressure to stabilize. To override
this feature for one cycle while testing
PUMP (FOSSIL FUEL KIT ALTER-
NATIVE).
TIME
thermostat operation, press SET
(Installer table step 9) This item controls heat
pump compressor operation with a fossil fuel
auxiliary. This menu item may eliminate the
connected): outdoor sensor, sensor L, A, b, C.
DAY
and SET
buttons at the same time.
(Continued on page 7)
HEATING
COOLING
Anticipation Value Cycle Length Differential Temperature Cycle Length Differential Temperature
1–8
9–20
21–40
Aux Only
Shorter
Longer
0.4–0.6°F (0.2–0.3°C)
0.6–1.0°F (0.3–0.6°C)
1.0–1.6°F (0.6–0.9°C)
N/A
N/A
Shorter
Longer
0.6–1.0°F (0.3–0.6°C)
1.0–1.6°F (0.6–0.9°C)
These numbers are approximate and represent operation with a typical system. Actual
temperature differentials and run times may vary widely based on your building and equip-
ment, as well as outdoor temperature conditions.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
(Installer table step 16). If you wish to sense
indoor temperature using ONLY the remote
sensor(s), use this menu item to disable the
temperature sensor in the thermostat
(designated as the L sensor).
OUTDOOR TEMPERATURE
SENSE.
OPTIONAL ACTIVATE RUN PRG
BY TELEPHONE
This thermostat can also display outdoor
temperature, if you install an outdoor remote
sensor with an outdoor temperature sensor
probe (F145-1378). Refer to the remote
sensor installation instructions for proper
installation and wiring. Refer to the Operat-
ing Instructions to enable this feature and
display outdoor temperature on the thermo-
stat.
With the optional X-10 Telephone Responder
(Model TR551, Radio Shack catalog RSU#
10037778) and Universal Low Voltage
Module (UM506, Radio Shack catalog RSU#
10037752) installed, you can make a
telephone call to run your program if the
thermostat has been set to Hold or Vacation
Hold. Figure 3 shows typical wiring
connections for installing the X-10 equip-
ment. The switch on the Universal Low
Voltage module must be set to the “Momen-
tary” position.
When operating with remote sensor(s), the
thermostat will calculate an average of the
sensed temperatures in all enabled sensor
locations (A, B, C and/or L), then display the
average temperature as the room tempera-
ture. During programming, you can also
assign each enabled sensor different
priorities during different program periods.
This allows the system to maintain a
comfortable environment by giving higher
priority to occupied locations. At the same
time, efficient system operation is enhanced
by giving lower priority to unoccupied
locations. For detailed instructions on this
feature, see the Operating Instructions.
This option must be enabled on the User
menu (see Operating Instructions).
PH
After using the Installer menu to properly
configure the thermostat for your system,
RUN
4
press PROGRAM
.
1
2
1
3
Thermostat terminals
1
2
3
4
5
4
X-10 Universal Low Voltage Module
X-10 Telephone Responder Module
To 115 VAC power source
To telephone line
C
5
Figure 3. Optional X-10 connection
CHECK THERMOSTAT OPERATION
FAN OPERATION
COOLING SYSTEM
HEAT PUMP AUXILIARY
OPERATION TEST
If your system does not have a G terminal
connection, skip to “Heating System”
section.
CAUTION
!
Follow these steps to energize all stages of
heat or cool to permit system checks during
installation.
To prevent compressor and/or property
damage, if the outdoor temperature is
below 50°F (10°C), DO NOT operate the
cooling system.
1. Turn power on to the system.
HEAT: Press
to raise temperature
RUN
2. Press PROGRAM
.
setting to 99°F, then hold for five seconds.
The second and third stage heat relays will
energize immediately for test purposes. The
LED indicator will glow green for first stage
and yellow for second stage.
FAN
RUN
3. Press
until FAN ON is displayed.
1. Press PROGRAM
.
The fan should begin to operate.
SYSTEM
2. Press
3. Press
until COOL is displayed.
FAN
4. Press
until FAN AUTO is
to adjust thermostat setting
displayed. The fan should stop operating.
below room temperature. The fan should
come on (after the fan-on delay time, if any),
followed by cold air circulation.
COOL: Press
to lower temperature
HEATING SYSTEM
setting to 45°F, then hold for five seconds.
The second stage cool relay will energize
immediately for test purposes. The LED
indicator will glow green for first stage and
yellow for second stage.
RUN
1. Press PROGRAM
.
4. Press
to adjust temperature setting
SYSTEM
2. Press
until HEAT is displayed. If
above room temperature. The cooling system
should stop operating, and the fan should
stop running (after the fan-off delay time, if
any).
the heating system has a standing pilot,
ensure that it is lit.
EMERGENCY: Press
to select
SYSTEM
3. Press
to adjust thermostat setting
EMER mode. The LED indicator will glow
red for emergency mode. A flashing light
indicates a malfunction in the system.
above room temperature. The heating system
should begin to operate.
4. Press
to adjust temperature below
room temperature. The heating system
should stop operating.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
To reset the thermostat, press and release
RESET BUTTON
RESETTING THERMOSTAT CON-
FIGURATION AND PROGRAM-
MING
RUN
FAN
PROGRAM
, then press the
,
If the thermostat does not respond when keys
are pressed, or the thermostat is not operating
properly, you may use the reset button
located on the back of the thermostat body
(see fig. 2). Thermostat programming and
configuration will not be affected by
pressing the reset button. However, the clock
will need to be reset.
BACK
TIME
and buttons at the same
time. This will reset the thermostat to factory
default programs and configuration. The
display will momentarily go blank, then all
segments on the display will momentarily be
shown. The thermostat will then go into the
HOLD mode and will maintain factory preset
temperatures.
The thermostat can be reset back to default
programs and configuration. Removing
power from the thermostat will not reset it,
because the default settings are maintained in
permanent memory. Before resetting the
thermostat, you may want to make note of
the previously selected configuration and
programming. You must reconfigure and
reprogram the thermostat after resetting it
using this method.
WHITE-RODGERS
EMERSON ELECTRIC CO.
9797 REAVIS ROAD
ST. LOUIS, MISSOURI 63123-5398