WHITE-RODGERS 90 SERIES
1F95CA-391
MULTI-STAGE/HEAT PUMP INSTALLATION/CONFIGURATION
INSTALLATION
DESCRIPTION
This White-Rodgers Digital Thermostat uses
microcomputer technology to provide precise
time, humidity, and temperature control. This
thermostat offers the flexibility to design
heating and cooling programs that fit
building needs. This thermostat is adaptable
to most 24 volt residential forced air multi-
stage or heat pump systems with electric or
fossil fuel auxiliary.
SPECIFICATIONS
1F95CA-391: 7 Day programming;
Standard Systems:
Multi-stage gas, oil, electric.
OperatingAmbient Temperature:
32° to 110°F (0° to 43°C)
residential applications.
Single-stage or two-stage compressor
heat pump.
Operating Humidity Range:
90% non-condensing max.
ELECTRICAL DATA
Electrical Rating:
Shipping Temperature Range:
-4° to 149°F (-20° to 65°C)
THERMAL DATA
20 to 30 VAC, 50/60 Hz with common
0.05 to 1.5 Amps per terminal
2.5 Amps maximum total load (all
terminals combined).
Setpoint Temperature Range:
45° to 99°F (7° to 37°C)
Hardwired only.
C terminal is required.
PRECAUTIONS
Do not exceed ratings shown in the Specifi-
cations section, above. If in doubt about the
electrical ratings of your heating/cooling
system, have it inspected by a qualified
heating and air conditioning contractor or
licensed electrician.
WARNING
!
CAUTION
!
Do not short out terminals on gas valve
or primary control to test. Short or
incorrect wiring will damage thermostat
and could cause personal injury and/or
property damage.
To prevent electrical shock and/or
equipment damage, disconnect electric
power to system at main fuse or circuit
breaker box until installation is
complete.
All wiring must conform to local and
national electrical codes and ordinances.
Do not use on circuits exceeding
specified voltage. Higher voltage will
damage thermostat and could cause
shock or fire hazard.
NOTE
This control is a precision instrument, and
should be handled carefully. Rough handling
or distorting components could cause the
control to malfunction.
Read all instructions thoroughly before
beginning installation.
Thermostat installation and all compo-
nents of the system shall conform to
Class II circuits per the NEC code.
This thermostat is intended for use with a
low voltage system. Do not use on a line
voltage system.
White-Rodgers is a division
of Emerson Electric Co.
Part No. 37-6583A
0504
Download from Www.Somanuals.com. All Manuals Search And Download.
MULTI-STAGE TERMINAL OUTPUTS
Refer to equipment manufacturers’ instruc-
tions for specific system wiring information.
This thermostat is designed to operate a
Use the terminal output information below to
help you wire the thermostat properly for
your multi-stage system. After wiring, see
CONFIGURATION section for proper
thermostat configuration.
single-transformer system. If you have a two-
transformer system, cut and tape off one
transformer. If transformer safety circuits are
in only one of the systems, remove the
transformer of the system with NO safety
circuits. If required, replace remaining
transformer with a 75VA Class II transformer.
After disconnecting one transformer, the two
commons must be jumpered together.
You can configure the thermostat for use
with either multi-stage electric heat systems
or multi-stage gas systems. When configured
for electric heat, the G terminal (blower/fan)
will be energized on a call for heat, using the
installer table (pgs. 5 & 6).
THERMOSTAT TERMINALS (Upper)
L
SA
SB
Remote Sense B
SC
OT
Malfunction Light/
Comfort Alert
Remote Sense A
Remote Sense C
Outdoor Sensor
Interface Module
THERMOSTAT TERMINALS (Lower)
SYSTEM
C
R
HM
W2
DHM
E/W1
Y2
Y1
B
O
G
24 Volt
(Common)
Cool mode
1st stage
Cool mode
2nd stage
Heat mode
2nd stage
Heat mode
1st stage
Blower/Fan
Energized on
call for Cool
(and Heat if
configured
to Electric Heat).
Multi-Stage
24 Volt
(Hot)
Energized in Heat
and Off Mode
Energized in
Cool Mode
Energizes on a
call for heat if
Humidity setpoint is
above room
E2/P switch in the P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
humidity.
call for Dehumidification.
HEAT PUMP TERMINAL OUTPUTS
Refer to equipment manufacturers’ instruc-
tions for specific system wiring information.
This thermostat is designed to operate a
Use the terminal output information below to
help you wire the thermostat properly for
your heat pump system type. After wiring,
see CONFIGURATION section for proper
thermostat configuration.
single-transformer system. If you have a two-
transformer system, cut and tape off one
transformer. If transformer safety circuits are
in only one of the systems, remove the
transformer of the system with NO safety
circuits. If required, replace remaining
transformer with a 75VA Class II transformer.
After disconnecting one transformer, the two
commons must be jumpered together.
You can configure the thermostat for use
with the following heat pump system types:
HEAT PUMP TYPE 1. Single-stage
compressor system; gas or electric backup.
HEAT PUMP TYPE 2. Multi-stage or two-
compressor system; gas or electric backup.
THERMOSTAT TERMINALS (Upper)
SB
Remote Sense B
L
SA
SC
OT
Malfunction Light/
Comfort Alert
Remote Sense A
Remote Sense C
Outdoor Sensor
Interface Module
THERMOSTAT TERMINALS (Lower)
SYSTEM
C
R
HM
W2
DHM
E/W1
Y2
Y1
B
O
G
Single-stage compressor system; gas or electric backup
24 Volt
Heat and
Cool mode
1st stage
No Output
Heat mode
3rd stage,
Emergency Mode
2nd stage
Heat mode
2nd stage,
Emergency Mode
1st stage
Blower/Fan
Energized on
call for Heat and Cool
Heat Pump 1
24 Volt
(Hot)
Energized in Heat,
Off, Emergency
Mode
Energized in
Cool Mode
Energizes on a
call for heat if
Humidity setpoint is
above room
E2/P switch in P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
(Common)
(compressor 1)
humidity.
call for Dehumidification.
Multi-stage or two compressor system; gas or electric backup
24 Volt
Heat and
Cool mode
1st stage
Heat and
Cool mode
2nd stage
Emergency Mode
2nd stage
Heat mode
3rd stage,
Emergency Mode
1st stage
Heat Pump 2
24 Volt
(Hot)
Energized in Heat,
Off, Emergency
Mode
Energized in
Cool Mode
Energizes on a
call for heat if
Humidity setpoint is
above room
E2/P switch in P position,
Energizes on a call for
Dehumidification.
E2/P switch in E2 position,
De-energizes on a
Blower/Fan
Energized on
call for Heat and Cool
(Common)
(compressor 1)
(compressor 2)
humidity.
call for Dehumidification.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
CONFIGURATION
SWITCHES
RESET SWITCH
See the Troubleshooting section at the end
of this document for more information about
the function of this switch.
1
2
E2/P SWITCH (DHM) TERMINAL
FUNCTION
S18
The E2/P switch is located on the back of
the thermostat body (see fig. 2). This switch
controls how the DHM terminal will be
energized.
S19
P
1. In the P position (up) the DHM terminal will
be energized on a call for dehumidification.
E2
2. In the E2 position (down) the DHM terminal
will always be energized except on a call for
dehumidification. The switch must be in the E2
position on some electronically controlled
variable speed blower systems.
Reset switch
1
2 E2/P switch
Figure 2. Switch locations on back of thermostat body
DEHUMIDIFICATIONWIRINGWITHOUT AN ELECTRONICALLY CONTROLLEDVARIABLE SPEED BLOWER SYSTEM
FOR SINGLE STAGE COMPRESSOR SYSTEM ONLY
If you have a single stage compressor system see the diagram below. A relay (customer provided) should be installed as shown in Fig. 5 to
switch the fan speed to the next lower speed on a call for dehumidification from the thermostat.The reduction in air flow allows the coil to remove
more humidity from the air. The relay should be rated for blower motor load. Since this configuration reduces the air flow in cooling, the anti-
freeze-up control (White-Rodgers CAFC) or equivalent is recommended. The CAFC prevents the air conditioning coil from freezing due to low
air flow, dirty filters, low refrigerant pressure, etc. The CAFC snaps onto the suction line close to the evaporator coil as possible and breaks the
compressor circuit when the suction line drops below 38°F and re-make the circuit at 46°F.
NOTE: If you have a two stage compressor, the thermostat software will lengthen cycle times for the first stage of cool. The longer cycles will
improve dehumidification while cooling, allowing the DHM terminal not to be used on a two stage compressor system.
Selecting P - DHM Energizes on call for
P
Dehumidification
Selecting E2 - DHM Deenergizes on call for
E2
Dehumidification
DHM
R
C
Y1
G
HIGH
3-4 speed
Blower
Motor
MED. HIGH
LOW
N.C.
N.O.
Customer supplied relay
rated for blower motor load
Furnace
Control
Module
HOT
120 VAC
NEUTRAL
TRANSFORMER
Figure 3. Typical Wiring for Dehumidifier System
HM
R
HM
R
Humidifier
System
Relay
90-290Q
or equivalent
HOT
HOT
24 VAC
24 VAC
120 VAC
120 VAC
I
I
NEUTRAL
NEUTRAL
HOT
TRANSFORMER
TRANSFORMER
Humidifier
System
120 VAC
NEUTRAL
Figure 5.Typical Wiring for 24V Humidifier System
Figure 4. Typical Wiring for 120V Humidifier System
4
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER CONFIGURATION
BEFORE TURNING POWER ON, please
read the following instructions. Before
operating the system, you must configure
the thermostat to operate properly with
your equipment.
HEAT PUMP COMPRESSOR
CONFIGURATION.
PROGRAMMABLE COOL FAN-
OFF AND FAN-ON DELAY.
(Installer table step 2; this item is displayed
only when heat pump was selected in step 1.)
Use this item to select the number of heat
pump compressors.
(Installer table steps 7 and 8.) These items
allow a selection of 0 to 127 seconds of fan-
off delay after the thermostat has satisfied the
call for cool, or a fan-on delay of 1 to 30
seconds on a call for cool (or heat pump
compressor activation).
The thermostat, as it comes from the factory,
is configured to operate a standard multi-
stage electric forced hot air system with a
single stage air conditioning compressor
and fan. In this configuration, the thermostat
will turn on the fan immediately on a call for
heat. If you are unsure whether your system
requires the thermostat to control the fan,
contact your furnace/air conditioning system
manufacturer or a qualified heating/air
conditioning service person.
ELECTRIC HEAT FAN
CONFIGURATION.
The fan-off delay allows the fan to continue
running after the compressor has shut off.
This distributes the cool air that would
otherwise stay trapped in the air conditioning
coils through the ducts. Ideally the timing
would be set so the fan shuts off just as the
cool air is exhausted. If this timing is set too
long the fan may begin blowing warm air
before it shuts off. Shortening the fan-off
delay will prevent this.
(Installer table step 3.) This item determines
whether fan control will be through the
thermostat or through the heating system. If
you have an electric heat or other system that
REQUIRES the thermostat to control the fan,
set this item ON. This allows the thermostat
to energize the fan immediately on a call for
heat. If you are unsure if the system requires
the thermostat to control the fan, contact the
equipment manufacturer or a qualified
heating and air conditioning service person.
If your system controls fan operation (as
with most fossil fuel systems), set this item
to OFF. Note that with heat pump systems,
the fan always cycles with the compressor.
Your new thermostat has an Installer table,
which allows you to customize the thermostat
to meet your requirements.
A short delay to allow the A-coil to cool
off (or warm up in heat pump) before the
fan turns on may be preferred. This also
allows the compressor and the fan to come
on at slightly different times, which allows
full power to the compressor on start up.
Recommended setting for fan-on delay is
10 seconds or less.
(The thermostat also has a User menu,
Keypad Lockout menu and a Service
menu; these menus are explained further
in the Operating Instructions.)
The menu settings can be changed at any time
to meet system or personal requirements.
SET CYCLE HEAT, COOL, AUX
(ANTICIPATION).
ENTERING THE CONFIGURATION
MENUS
(Installer table steps 4 through 6; step 6 is for
heat pump only). These items allow the cycle
times in heating, cooling and auxiliary (heat
pump systems only) to be increased or
decreased. The factory set values can be
adjusted higher for longer cycles or lower for
shorter cycles.
PROGRAMMABLE HEAT FAN-
OFF DELAY.
After properly wiring the thermostat, turn on
power to the system. Momentarily press
RUN
(Installer table step 9.) This item allows a
selection of 0 to 127 seconds of fan-off delay
after the thermostat has satisfied the call for
heat if ELECT HEAT FAN (Step 3) is
selected ON.
PROGRAM
to make certain the
thermostat is in the run program mode, then
BACK
FWD
press TIME
and TIME
at the
same time to enter the User Configuration
menu. When the display changes to the first
item in the configuration menu, release the
TIME
NOTE: Some manufacturers still instruct you
to set the anticipator to the current draw of
the equipment. That instruction applies only
to mercury bulb or mechanical thermostats; it
does not apply to this digital thermostat. As
configured at the factory, this thermostat will
maintain an accurate temperature. No further
adjustment is necessary, although you can
use these items to customize the performance
of the thermostat to your requirements.
The fan-off delay allows the fan to continue
running after the burner, heating element,
etc. has shut off. This distributes the heat that
would otherwise stay trapped in the ducts.
Ideally the timing would be set so the fan
shuts off just as the warm air is exhausted. If
this timing is set too long the fan may begin
blowing cool air before it shuts off. Shorten-
ing the fan-off delay will prevent this.
buttons. Then press and hold SET
and
DAY
SET
for approximately 3 seconds to
enter the Installer table. The display will
change to show the first item on the Installer
table (multi-stage/heat pump selection). Use
the following text, along with the Installer
table, to guide you through the selections.
PUMP (FOSSIL FUEL KIT ALTER-
NATIVE STEPS 10 - 13).
Once in the table, you set each item to the
The adjustment range for HEATING is from
1 to 40 (9 to 40 for heat pump). The factory
preset is 5 (13 for heat pump). The adjust-
ment range for COOLING is from 9 to 40.
The factory preset is 12 (13 for heat pump).
The cooling will not go below 9 because
compressors require a longer cycle. The
adjustment range for AUXILIARY (heat
pump only) is from 1 to 40. The factory
preset is 6.
proper selection using
or
, then
FWD
press TIME
to change the display to
(Installer table step 10; heat pump only) This
item controls heat pump compressor
BACK
the next item or TIME
to return to the
previous item.
operation with a fossil fuel auxiliary. This
item may eliminate the need for a separate
fossil fuel kit, although we recommend that
you consult the heat pump system manufac-
turer before using this feature instead of a
kit. This item will allow the thermostat to
turn the heat pump compressor off if the
auxiliary is on for more than one minute,
to prevent compressor head pressure from
getting too high. To use this feature instead
of a kit, select PUMP OFF.
To exit the table at any time, press PRO-
RUN
GRAM
.
MULTI-STAGE/HEAT PUMP MODE.
(Installer table step 1.) Use this item to select
the system type (multi-stage or heat pump).
IF YOU HAVE A HEAT PUMP SYSTEM,
you must select HEAT PUMP here. This
sets up proper default values for most heat
pump systems. This selection also makes
available some additional menu items that
apply only to heat pump systems.
The chart on page 7 shows how this
adjustment range affects thermostat perfor-
mance.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
INSTALLER TABLE
FWD
NOTE:You must be in the User Configuration Menu to enter the Installer Table. Firmly press TIME
and
BACK
TIME
at same time and release to enter the Configuration Menu.
See
Page
Step
Press Button(s)
Displayed (Factory Default) Press UP or DOWN to select:
COMMENTS
1
MLTI STG
HEAT PUMP
Selects type of system. Selecting HEAT PUMP
makes additional items for heat pump systems
available.
Firmly Press
SET TIME and
SET DAY (hold
5
for approx. 3 seconds)
2
HEAT PUMP
(1)
2
1. One compressor on Y1.
2. Two compressor on Y1, Y2.
5
TIME FWD
(Heat Pump ONLY)
Fan cycles with call for heat if ON. Fan always
cycles with pump stages.
3
4
ELEC HEAT FAN
(ON)
OFF
5
5
TIME FWD
Selects HEAT anticipation adjustment.
Selects COOL anticipation adjustment.
SET CYCL (05)
for MLTI_STG, (13) for
HEAT PUMP 1, (24)
for HEAT PUMP 2
1 to 40 for multi-stage
9 to 40 for heat pump
TIME FWD
9 to 40
5
SET CYCL (24)
5
TIME FWD
for MLTI_STG, (13) for
HEA PUMP 1, (24)
T
for HEAT PUMP 2
Selects AUXILIARY stage anticipation adjustment.
(Heat Pump ONLY)
6
7
8
SET CYCL AUX
(08)
1 to 40
5
5
5
TIME FWD
(Heat Pump ONLY)
Selects time delay for COOL fan OFF.
COOL FAN DELA OFF
(00)
0 to 127 seconds
1 to 30 seconds
TIME FWD
Selects time delay for fan ON. Applies only to
compressor stages for heat pump or COOL.
FAN DELA ON
(01)
TIME FWD
Selects time delay for fan ON only when
ELECT HEAT FAN (Step 3) is ON.
9
HEAT FAN DELA OFF
(00)
0 to 127 seconds
OFF
5
5
TIME FWD
Fossil Fuel Kit Alternative option. Turns compressor
OFF if Auxiliary is ON for longer than one minute.
(Heat Pump 1 & 2)
10
PUMP
(ON)
TIME FWD
(Heat Pump ONLY)
Available if Pump (Step 10) is OFF. Selects the
delay between de-energizing fossil fuel stage and
restarting Heat Pump stage.
7
11
12
13
COMP OFF DELA
(60)
(0) to (99)
5 F to 50 F
(01) to (09)
TIME FWD
(Heat Pump ONLY)
Available if Pump (Step 10) is OFF and OUTDOOR
Sensor ON. Selects outdoor balance point
temperature for Heat Pump.
(Balance point temperature)
bPT (35 F)
7
7
TIME FWD
(Heat Pump ONLY)
Available if Pump (Step 10) is OFF and OUTDOOR
Sensor OFF. The higher the number the sooner the
auxilary stage energizes. The lower the number the
longer period of time before auxiliary is energized.
(Balance point)
bP (05)
TIME FWD
(Heat Pump ONLY)
Available if configured for HEAT PUMP. Adjustable
from 99-10. Lowers the Blower speed if the Heat
Pump duty cycle is above the selected value in
percentage.
14
15
(Programmable Blower
Balance Point) bbP
(OFF)
10 to 99%
7
TIME FWD
(Heat Pump ONLY)
Selects compressor short-cycle protection.*
COMP LOCK
(OFF)
ON
ON
TIME FWD
7
7
7
Selects active Comfort Alert. Requires CA module
and CA interface module.
CA
(OFF)
16
17
TIME FWD
TIME FWD
Allows selection of HEAT and COOL or HEAT,
COOL and AUTO with SYSTEM button. (EMER
appears in sequence after HEAT if HEAT PUMP
is selected).
HEAT-OFF COOL-AUTO
or HEAT-EMER-OFF-
COOL-AUTO
HEAT-OFF-COOL or
HEAT-EMER-OFF-
COOL (for heat pumps)
(for heat pumps)
Program RUN
Returns to Normal Operation.
* Note: COMP LOCK OFF permanently defeats compressor lockout. You must turn this selection ON if you do not have a system that already provides
compressor short-cycle protection. Please see “Lockout Bypass Option” to temporarily override compressor lockout.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
module. Turn this feature ON to achieve
active protection, enabling the thermostat to
identify certain fault codes when compressor
damage is possible and react to those codes
by turning the compressor off.
COMPRESSOR OFF DELAY
PROGRAMMABLE BLOWER
BALANCE POINT
Installer table, step 11 is available if the
fossil fuel kit alternative option (PUMP OFF)
is selected.
Installer table step 14, bbP, is available only
when configured for Heat Pump systems, and
wired as shown in Fig. 3.
This item allows a selection of 0 to 99
seconds, which is the time that the compres-
sor will continue to run after the point that
the auxiliary heat is energized. Running the
compressor after the Auxiliary has started
prevents cool air from creating drafts prior to
the heat exchanger reaching normal tempera-
tures. The factory default value of 60
seconds is typical for most systems. Consult
with your equipment’s manufacturer before
increasing this time.
If the system is running a high percentage of
the time due to cold weather conditions, the
output vent air temperature may be cooler
than normal thus creating a drafty room
condition. This feature will reduce the draft
by lowering the blower speed with the DHM
terminal. The lower speed will make the air
temperature slightly warmer and more
comfortable.
Lockout Bypass Option
FOR QUALIFIED SERVICE TECH-
NICIANS’ USE ONLY.
HOMEOWNERS SHOULD NOT USE
THIS FEATURE DUE TO POSSIBIL-
ITY OF EQUIPMENT OR PROP-
ERTY DAMAGE, OR PERSONAL
INJURY.
COMPRESSOR SHORT TERM CYCLE
PROTECTION
Example: If you want the blower to go to a
lower speed when the system is running
greater than 50% of the time,then reduce the
Blower Balance Point to 50%.
BALANCE POINT TEMPERATURE
If this thermostat has been configured to
provide short-cycle protection, during the
5-minute lockout period the thermostat
will lock out the compressor to allow
head pressure to stabilize. To override
this feature for one cycle while testing
Installer table step 12, bPT, is available only
if the fossil fuel kit option is selected and the
outdoor temperature sensor is used (see the
user menu in the owner manual).
To turn this feature OFF, press
to 99
then press once more to display OFF.
COMPRESSOR LOCKOUT.
This item allows a selection of 5 to 50° F,
which is the outdoor temperature below
which the thermostat will not energize heat
pump compressor stages. It will use
Auxiliary heat stages (only) until the outdoor
temperature raises 3° above the selected
temperature and then allow compressor
stages to operate. The factory default value
of 35° F is typical for most systems.
TIME
(Installer table step 15). This thermostat is
capable of helping to protect the system
against premature compressor failure by
“locking out” the compressor for at least five
minutes after each cycle. When the thermo-
stat is in compressor lockout, the word
COOL will flash on the display. With heat
pump systems, the word HEAT will flash if
the lockout occurs during a heat cycle.
During this period, the compressor will not
be energized.
thermostat operation, press SET
DAY
and SET
buttons at the same time.
If the system has short-cycle protection, this
item should not need to be enabled. How-
ever, if your system does not have short-
cycle protection, turn COMP LOCK ON.
This will protect the compressor from short-
cycling and potential premature compressor
failure.
BALANCE POINT
Installer table step 13, bP, is available only if
the fossil fuel kit option is selected and the
outdoor temperature sensor is not used. The
Balance Point influences when second stage
comes on. The factory default creates
approximately 1° F between stages. Increas-
ing the setting decreases the separation
between stages. Decreasing the value
increases stage separation. This adjustment
allows a small change in the operation of
your heat pump system versus your auxiliary
system relative to the thermostat adjustment.
Note that COMP LOCK OFF permanently
disables compressor lockout. If you need to
temporarily disable compressor lockout,
please see Lockout Bypass Option.
COMFORT ALERT WITH ACTIVE
PROTECTION.
(Installer table step 16). The Comfort Alert
diagnostics product diagnoses system and
electrical problems in the air conditioning
outdoor systems with single phase Copeland
Scroll compressors. Abnormal conditions are
indicated by flashing ALERT codes on the
yellow LED on the Comfort Alert module.
The flash codes are transmitted to the
thermostat by the ComfortAlert Thermostat
interface module. The ComfortAlert
compatible thermostat displays a CHECK
SYSTEM icon that flashes at the same rate as
the yellow ALERT LED on the Comfort Alert
DISABLING AUTOMATIC
CHANGEOVER MODE.
(Installer table step 17). This thermostat, as
configured at the factory, provides automatic
changeover, which allows the thermostat to
switch between heating and cooling to
maintain temperature. In this configuration,
when you press the SYSTEM button, the
thermostat will go through HEAT-OFF-
COOL-AUTO modes (HEAT-EMER-OFF-
COOL-AUTO for heat pumps). Select
HEAT(-EMER)-OFF-COOL to disable the
automatic changeover feature.
Pump
Stage
Decreasing
Indoor
temperature
Stage separation
1˚F at setting 05
Fossil
Auxiliary
Stage
Higher number
Lower number
(Continued)
HEATING
COOLING
Anticipation Value Cycle Length Differential Temperature Cycle Length Differential Temperature
1–8
9–20
21–40
Shorter
Longer
0.4–0.6°F (0.2–0.3°C)
0.6–1.0°F (0.3–0.6°C)
1.0–1.6°F (0.6–0.9°C)
N/A
N/A
Shorter
Longer
0.6–1.0°F (0.3–0.6°C)
1.0–1.6°F (0.6–0.9°C)
Hydronic
These numbers are approximate and represent operation with a typical system. Actual temperature differentials and
run times may vary widely based on your building and equipment, as well as outdoor temperature conditions.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
SERVICE REMINDER
The Service Button Menu allows you to view or program as many as 4 reminders that indicate when service is required.
1. Humidifiers = A programmable run time in hours to indicate on the LCD when the humidifier will need to be serviced.
2. Air Filters = A programmable run time in hours to indicate on the LCD when the filter will need to be serviced or replaced.
3. UV Lights = A programmable run time in days to indicate on the LCD when the Ultra-Violet Bulb will need to be replaced.
4. Service Timer = A programmable run time in days to indicate on the LCD when to call your service contractor.
To enter the Service Button Menu when no service reminders are on the display, press and release the SERVICE button. Press
FWD
TIME
to step through the menu items. To turn a menu item OFF or ON when selected, press
or
. If you are
RUN
setting an item to ON, you can then use
or
to select the time interval. Press
to exit the menu and return to
normal operation.
When a service reminder appears on the display, press the SERVICE button to remove it and reset the timer to begin the count
down to the next service interval.
Service Button Menu
Step
Press Button(s)
Displayed
(Factory Default)
Press
or
to select:
COMMENTS
1
SERVICE
PAD TIME
(OFF) Hrs
or
(ON)
or
(OFF)
Set Humidifier Maintenance Reminder.
REM PAD TIME
No. of Hrs
Selects time intervals in increments of 25 hours. The RUN
time accumulates when the HM terminal is energized.
2
3
SET PAD TIME
(100) Hrs
25 to 1975
FWD
TIME
(If PAD TIME is ON)
Set Air Filter Maintenance Reminder.
FWD
FLTR TIME
(OFF) /Hrs
or
(ON)
or
(OFF)
TIME
REM FLTR TIME
No. of Hrs
Selects time intervals in increments of 25 hours.
The RUN time accumulates when the fan is operating.
4
5
SET FLTR TIME
(200) Hrs
25 to 1975
FWD
TIME
(If FLTR TIME is ON)
Selects UV Light Maintenance Reminder.
UV TIME
(OFF) Days
or
(ON)
or
(OFF)
FWD
TIME
REM UV TIME
No. of Days
Selects time intervals in increments of 25 days. The RUN
time is the calendar time from when it is entered or reset.
SET UV TIME
(375) Days
25 to 1975
FWD
6
7
TIME
(If UV TIME is ON)
Selects Routine Maintenance Service Call Reminder.
SERV TIME
(OFF) Days
or
(ON)
or
(OFF)
FWD
TIME
REM SERV TIME
No. of Days
Selects time intervals in increments of 25 days. The RUN
time is the calendar time from when it is entered or reset.
SET SERV TIME
(175) Days
25 to 1975
FWD
8
TIME
(If SERV TIME is ON)
Returns to Normal Operation.
RUN
PRGM
8
Download from Www.Somanuals.com. All Manuals Search And Download.
CHECK THERMOSTAT OPERATION
FAN OPERATION
MULTI-STAGE/HEAT PUMP
DEHUMIDIFICATION SYSTEM
(IF INSTALLED)
AUXILIARY OPERATION TEST
Follow these steps to energize all stages of
hear or cool to permit system checks during
installation.
If your system does not have a G terminal
Connection, skip to HEATING SYSTEM
section below.
1. Press
until COOL is shown at the
SYSTEM
top of the display.
2. Press the HUMIDITY % button once and
1. Turn power on to the system.
RUN
HEAT: Press
to raise temperature
release. Then press
to the minimum
2. Press PROGRAM
.
setting to 99°F, then hold for five seconds.
The second and third stage (heat pump only)
heat relays will energize immediately for test
purposes. The LED indicator will glow green
for first stage and yellow for second stage, and
flashing yellow for third stage (heat pump
only).
humidity setpoint and hold for 7 seconds
until ON is displayed. It assures that the
Dehumidifier will call for dehumidifica-
tion when the thermostat calls for COOL
as outlined in the following steps.
FAN
3. Press
until FAN ON is displayed.
The fan should begin to operate.
FAN
4. Press
until FAN AUTO is
displayed. The fan should stop operating.
3. Press PROGRAM
4. Press the HOLD button.
5. Press to lower the temperature
.
RUN
HEATING SYSTEM
1. Press PROGRAM
.
RUN
COOL: Press
to lower temperature
SYSTEM
2. Press
until HEAT is displayed. If
setting to 45°F, then hold for five seconds.
The second stage cool relay will energize
immediately for test purposes. The LED
indicator will glow green for the first stage
and yellow for second stage.
setting 1°F below room temperature. The
1st stage of the cooling system should
begin to operate and the LED indicator
will glow Green. The lowercase letter
d will appear to the right of HOLD,
indicating that the thermostat is calling
for Dehumidification.
the heating system has a standing pilot,
ensure that it is lit.
3. Press the
setting above room temperature. The
heating system should begin to
operate.
4. Press the
setting below room temperature. The
heating system should stop operating.
to adjust thermostat
EMERGENCY (heat pump only): Press
to select EMER mode. The LED
SYSTEM
to adjust thermostat
indicator will glow red for first stage (Aux) in
emergency mode.
A flashing red LED indicates a malfunction
in the system.
6. Press the temperature
to lower your
setpoint 4°F below room temperature, the
DHM terminal will energize causing the
FAN to go to high speed.
7. Press the HUMIDITY % button and set
your desired dehumidification setpoint
COOLING SYSTEM
HUMIDIFIER SYSTEM
(IF INSTALLED)
CAUTION
!
in % RH using the
8. Press PROGRAM
change.
and
to accept the
.
To prevent compressor and/or property
damage, if the outdoor temperature is
below 50°F (10°C), DO NOT operate the
cooling system.
1. Press
until HEAT is shown at the
SYSTEM
RUN
top of the display.
2. Press the HUMIDITY % button once and
release. Then press the
to the
maximum humidity setpoint and hold for 7
seconds until ON is displayed. It assures
that the Humidifier will call for humidity
when the thermostat calls for HEAT as
outlined in the following steps.
RUN
1. Press the PROGRAM
.
SYSTEM
2. Press
3. Press
until COOL is displayed.
to adjust thermostat setting
below room temperature. The fan should
come on (after the fan-on delay time, if
any), followed by cold air circulation.
to adjust temperature setting
above room temperature. The cooling
system should stop operating, the fan
should stop running (after the fan-off
delay time, if any).
3. Press PROGRAM
4. Press the HOLD button.
5. Press to raise the temperature
.
RUN
4. Press
setting 4°F above room temperature.
The 1st stage (LED Green) and then 2nd
stage (LED Yellow) will be energized.
The HM terminal will also energize for
humidification. The lowercase letter h
will appear to the right of HOLD,
indicating that the thermostat is calling for
Humidification.
6. Press PROGRAM
to end the
RUN
HEAT/HUMIDIFIER test. NOTE: Be
sure to press the Humidity button and
reset the humidity to the level you desire.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
To reset the thermostat, press and release
RESET BUTTON
RESETTING THERMOSTAT
CONFIGURATION AND
PROGRAMMING
RUN
FAN
PROGRAM
, then press the
,
If the thermostat does not respond when keys
are pressed, or the thermostat is not operating
properly, you may use the reset button
located on the back of the thermostat body
(see fig. 2). Thermostat programming and
configuration will not be affected by
pressing the reset button. However, the clock
will need to be reset.
BACK
TIME
and buttons at the same
time. This will reset the thermostat to
factory default programs and configuration.
The display will momentarily go blank,
then all segments on the display will
momentarily be shown. The thermostat will
then go into the HOLD mode and will
maintain factory preset temperatures.
The thermostat can be reset back to default
programs and configuration. Removing
power from the thermostat will not reset it,
because the default settings are maintained in
permanent memory. Before resetting the
thermostat, you may want to make note of
the previously selected configuration and
programming. You must reconfigure and
reprogram the thermostat after resetting it
using this method.
TROUBLESHOOTING
Symptom
Possible Cause
Corrective Action
Thermostat Does Not Follow Program
1. AM or PM set incorrectly in program.
2. AM or PM set incorrectly on clock.
3. Voltage spike or static discharge.
Check current clock and program settings including
AM or PM designations for each time period. If a
voltage spike or a static discharge occurs use
the reset operation listed above.
Blank Display and/or Keypad Not Responding 1. Voltage spike or static discharge.
Replace batteries and check heat/cool system
for proper operation. If a voltage spike occurs
use the Reset Operation listed above.
2. Battery change required.
No Heat/No Cool/No Fan
(Common Problems)
1. Blown fuse or tripped circuit breaker.
2. Furnace power switch to OFF.
Replace fuse or reset breaker.
Turn switch to ON.
3. Furnace blower compartment door or
panel loose or not properly installed.
Replace door panel in proper position to engage
safety interlock or door switch.
No Heat
1. Pilot light not lit.
Re-light pilot.
2. SYSTEM button not pressed to display HEAT. Set SYSTEM button until HEAT is displayed and
raise temperature above room temperature.
3. Loose connection to thermostat or system.
Verify thermostat and system wires are securely
attached.
4. Furnace Lock-Out Condition. Heat may also
be intermittent.
Many furnaces have safety devices that shut
down when a lock-out condition occurs.If the
heat works intermittently contact the furnace
manufacturer or local service person for
assistance.
5. Heating system requires service or
thermostat requires replacement.
Diagonistic: Set SYSTEM button until HEAT is
displayed and raise setpoint above room
temperature.Within a few seconds the thermostat
should make a soft click sound.This sound
usually indicates the thermostat is operating
properly. If the thermostat does not click, try the
reset operation listed on the previous page.If the
thermostat does not click after being reset
contact your heating and cooling service person
or place of purchase for replacement. If the
thermostat clicks, contact the furnace manufacturer
or a service person to verify the heating system is
operating correctly.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
TROUBLESHOOTING
Symptom
No Cool
Possible Cause
Corrective Action
1. SYSTEM button not pressed to display COOL. Set SYSTEM button until COOL is displayed and
raise temperature below room temperature.
2. Loose connection to thermostat or system.
Verify thermostat and system wires are securely
attached.
3. Cooling system requires service or
thermostat requires replacement.
Same procedure as diagnostic for No Heat
condition except press the SYSTEM button until
COOL is displayed and lower the setpoint below
room temperature.There may be up to a five minute
delay before the thermostat clicks in Cooling.
Heat, Cool or Fan Runs Constantly.
1. Possible short in wiring.
2. Possible short in thermostat.
3. Possible short in Heat/Cool/Fan system.
4. FAN button pressed to display FAN ON.
Check each wire connection to verify they are not
shorted or touching together.No bare wire should
out from under terminal screws.Try resetting the
thermostat as described on the previous page.If
the condition persists the manufacturer of your
system or service person can instruct you on how
to test the Heat/Cool system for correct operation.If
the system operates correctly, replace the thermostat.
Furnace Cycles Too Fast or Too Slow
(narrow or wide temperature swing)
1. The location of the thermostat and/or the size
of the Heating System equipment may be
influencing the cycle rate.
Digital thermostats normally provide precise
temperature control and may cycle faster than
some older mechanical models.A faster cycle
rate means the unit turns on on off more frequently
but runs for a shorter time so there is no increase
in energy use. If you would like to increase the
cycle time, refer to page 6 under Installer Table for
settings. If an acceptable cycle rate is not acheived
by the adjustment in the InstallerTable then you
may want to contact a local heating and air
conditioning service person for further suggestions.
Cooling Cycles Too Fast or Too Slow
(narrow or wide temperature swing)
1. The location of the thermostat and/or the size
of the Cooling System can influence the
rate.
The cycle rate for cooling is fixed and can not be
adjusted. Contact a local service person for
suggestions.
Thermostat Setting and Thermostat
Thermometer Disagree
1. Thermostat thermometer setting requires
adjustment.
The thermometer can be adjusted +/- 5 degrees.
SeeTemperature Display Adjustment in the
Operating Manual under Configuration.
Thermostat Display Shows CHCK PAD,
CHNG FLTR, CALL SERV UV, CALL SERV
1. Thermostat service indicators.
These indicators can be reset or modified in the
service button menu (see pg.8).
11
Download from Www.Somanuals.com. All Manuals Search And Download.
FAQs
Why does the system run with the
setpoint and room temperature the
same?
In cooling, as the room temperature falls you will eventually reach the setpoint tem-
perature. The system will continue to run until it reaches the low side of the tempera-
ture setting. As an example: If set to 78 degrees with the room temperature falling the
thermostat will continue to call for cool as the temperature decreases in the following
manner. 78.9, 78.8, 78.7, 78.6, 78.5, 78.4, 78.3, 78.2, at approximately 78.2 the
thermostat will quit calling for cool. This is why it is not unusual for the room tempera-
ture and set temperature to read the same but the system continues to run. The
amount of time it takes for the system to shut off is dependent on system sizing,
thermostat location, etc. Note: The thermostat display only displays whole numbers.
Internally the thermostat calculates decimals.
In heating as the room temperature increases the system will continue to run until the
thermostat reaches the high side of the temperature setpoint.
Digitals are engineered to a specific response rate. Compared to a thermometer it will
seem slow. When left to acclimate and control temperature it will provide precise
temperature control on a properly sized system.
Why is the temperature change
display so slow?
Any time your program is running and you would like to override it for a specific
How do I temporarily Override the
program and Hold Til Timing?
amount of time, press
or
until the temperature you want is displayed. The
display will indicate HOLD, and the number of hours remaining in the hold period will
be indicated with the word HRS. To adjust the length of time for the override, press
TIME FWD or TIME BACK. The time you select will become the new number of hours
for the Hold Til timing. Once your time is selected, let the thermostat revert back to
normal operation on its own to accept the change.
Many furnaces have safety devices that shut the system down when a lock-out
condition occurs in the furnace. If the thermostat is turned off or the call for heat is
cancelled (by lowering and then raising the set temperature) the furnace may start
operating again. A diagnostic to see if the thermostat is operating when the room
temperature is below the thermostat setting (in heat) is to lower the setting below the
room temp. Within about 3 seconds the thermostat should make a soft click sound.
This sound is the thermostat turning off the call for heat and usually indicates the
thermostat is operating properly. If the thermostat does not click you would be
suspicious of the thermostat and try resetting it by following it’s reset operation. If the
thermostat does not click after being reset contact your heating and cooling service
person or place of purchase for a replacement. If the thermostat clicks and the heat
works intermittently contact the furnace manufacturer or local service person. They
will want to observe the condition when it is not working.
What is the thermostat ClickTest?
You can raise and lower the temperature a few degrees above and below the room
temperature and each time expect to hear the thermostat click on and off within a few
seconds. If it clicks, it is operating properly.
The Emerson logo is a
trademark and a service mark
of Emerson Electric Co.