USER’S INFORMATION,
MAINTENANCE AND
SERVICE MANUAL
EFFICIENCY
RATING
CERTIFIED
ISO 9001
Certified Quality
Management System
HIGH EFFICIENCY
TUBULAR HEAT EXCHANGER SERIES
MODELS: PS9 / FC9S / FL9S
(Single Stage Downflow/Horizontal)
TABLE OF CONTENTS
CONTACT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
USER’S INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
INSTRUCTIONS FOR EXAMINING THE
FURNACE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
HOW YOUR GAS FURNACE WORKS . . . . . . . . . . . . . . . . . . . . . .3
START-UP AND SHUTDOWN INSTRUCTIONS . . . . . . . . . . . . . . .3
Read the Instructions Below Before Trying to Start the
Furnace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Operating Instructions: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
To Turn Off the Appliance: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
FURNACE USER MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . .4
Blower Care . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Air Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Removing Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Motor Lubrication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
SERVICE AND MAINTENANCE MANUAL . . . . . . . . . . . . . . . . . . . . .5
SAFETY SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
FURNACE MAINTENANCE SECTION . . . . . . . . . . . . . . . . . . . . . . .5
SEQUENCE OF OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Continuous Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Intermittent Blower - Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Heating Cycle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Hot Surface Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CLEANING SECTION . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Burner Removal/Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Cleaning the Secondary Heat Exchanger . . . . . . . . . . . . . . . . . . .6
Cleaning the Vent / Air Intake System . . . . . . . . . . . . . . . . . . . . . .6
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
FURNACE CONTROL DIAGNOSTICS . . . . . . . . . . . . . . . . . . . . . . .6
DIAGNOSTIC FAULT CODE STORAGE AND RETRIEVAL . . . . . .7
REPLACEMENT PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
REPLACEMENT PART CONTACT INFORMATION . . . . . . . . . . . . .10
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
LIMITED WARRANTY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
CONTACT INFORMATION
•
•
Contact us by mail:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
The manufacturer recommends that the user read all sec-
tions of this manual and keep the manual for future refer-
ence.
SECTION I: USER’S INFORMATION
SAFETY
1. The furnace area must be kept clear and free of combustible mate-
rials, gasoline and other flammable vapors and liquids.
2. Insulating materials may be combustible. The furnace must be
kept free and clear of insulating materials. The furnace area must
be examined when installed in an attic or other insulated space or
when insulation is added to be sure that the insulation material has
been kept away from the furnace.
FIRE OR EXPLOSION HAZARD - Failure to follow safety
warnings exactly could result in serious injury, death, or prop-
erty damage.
— Do not store or use gasoline or other flammable vapors
and liquids in the vicinity of this or any other appli-
ance.
3. The furnace needs air for combustion in order to operate properly
and safely. Do not block or obstruct air openings on the furnace,
air openings to the area where the furnace is installed, or spaces
around the furnace.
— WHAT TO DO IF YOU SMELL GAS:
•
•
Do not try to light any appliance.
4. Follow the instructions exactly as shown on the OPERATING
INSTRUCTION LABEL or the Start-up and Shutdown Instructions
on Page 3 of this manual when lighting the furnace or turning the
furnace off.
Do not touch any electrical switch; do not use any phone
(including cell phone) in your building.
•
•
Leave the building immediately.
5. Should the gas supply fail to shut off or if overheating occurs, shut
off the gas valve to the furnace before shutting off the electrical
supply.
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
If you cannot reach your gas supplier, call the fire depart-
ment.
6. Do not use this furnace if any part has been under water. A flood-
damaged furnace is extremely dangerous. Attempts to use the fur-
nace can result in fire or explosion. A qualified service agency
should be contacted to inspect the furnace and replace all gas
controls, control system parts, electrical parts that have been wet
or the furnace if deemed necessary.
— Installation and service must be performed by a quali-
fied installer, service agency or the gas supplier.
127237-UUM-A-0605
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
HOW YOUR GAS FURNACE WORKS
To Turn Off the Appliance:
Your furnace is a very easy appliance to take for granted. Season after
season, it sits there in your home, keeping you warm and comfortable.
For this reason, you may never have given much thought to the way
your furnace operates. In order to get the safest and most efficient oper-
ation from your furnace, you should understand how your furnace does
its job.
1. Set the thermostat to lowest setting.
2. Turn off all electric power to the appliance if service is to be per-
formed.
3. Remove burner access panel.
4. Move gas control switch to the “OFF” position.
5. Replace burner access panel.
When you set your thermostat to provide more heat in your home, you
are starting the heating cycle of the furnace. First, the inducer motor
starts to purge the heat exchanger of any remaining gases. Next, the
hot surface igniter glows and after a warm-up period the gas valve
opens and ignition occurs. A short time later, the blower starts and dis-
tributes the warm air throughout the home. When the temperature set-
ting on your thermostat is reached, the gas valve closes, the main
burners are turned off, and the blower continues to run until the remain-
ing warm air in the system is distributed. When the blower stops, the
heating cycle has ended.
Should overheating occur, or the gas valve fail to shut off,
turn the external manual gas valve in the gas supply line to
the furnace to the “off” position and let the furnace cool off
before shutting off the electrical power supply. Refer to
Figures 5 & 6.
START-UP AND SHUTDOWN INSTRUCTIONS
OUTLET
PRESSURE
PORT
VENT PORT
Read the Instructions Below Before Trying to Start the
Furnace
INLET
OUTLET
WRENCH
BOSS
INLET
PRESSURE
PORT
MAIN REGULATOR
ADJUSTMENT
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury, and/or loss of life.
ON/OFF SWITCH
(Shown in ON position)
A. This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the
burner by hand.
FIGURE 4: Gas Valve - White Rodgers
EXTERNAL MANUAL
SHUTOFF VALVE
B. BEFORE OPERATING; smell all around the appliance area for
gas. Be sure to smell next to the floor because some gas is
heavier than air and will settle on the floor.
TO GAS
SUPPLY
TO GAS
SUPPLY
C. Use only your hand to push the gas control switch to the “on” posi-
tion. Never use tools. If the switch will not operate by hand, don’t
try to repair it, call a qualified service technician. Force or
attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control,
which has been under water.
GROUNDED JOINT UNION
MAY BE INSTALLED
INSIDE OR OUTSIDE UNIT.
DRIP
LEG
Operating Instructions:
FIGURE 5: Gas Piping
1. STOP! Read the safety information above.
2. Set the thermostat to the lowest setting.
3. Turn off all electric power to the appliance.
4. Remove burner door.
MANUAL
SHUT-OFF
VALVE
DRIP
LEG
GAS
PIPE
5. Move gas control switch to the “OFF” position. Do not force.
GAS BURNERS
GAS VALVE
6. Wait five (5) minutes to clear out any gas. If you then smell gas,
STOP! Follow “B” in the safety information above. If you don’t
smell gas, go to next step.
GAS
PIPE
7. Move gas control switch to the “ON” position. Do not force.
8. Replace burner door.
MANUAL
SHUT-OFF VALVE
DRIP
LEG
9. Turn on all electric power to the appliance.
10. Set thermostat to the desired setting. Burner will light, which may
take 30-60 seconds.
FIGURE 6: Horizontal Gas Piping
11. After three (3) trials for ignition, if the appliance will not operate fol-
low the instructions, “TO TURN OFF THE APPLIANCE” and call
your service technician or gas supplier.
NOTE: The spring-loaded safety cut-off switch, mounted on the blower
deck, behind the indoor fan access panel will automatically cut
off the electrical power supply to the furnace when the blower
panel is removed. As a safety precaution, all electrical power
and the gas supply to the furnace should be turned off before
servicing.
Unitary Products Group
3
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
3. After you determine the cabinet size and what return configuration
you have, look up the recommended filter size from Table 1.
FURNACE USER MAINTENANCE
Removing Filters
Most downflow furnaces have their filters located on the top of the fur-
nace in an external filter rack. To check filters you should:
Before proceeding, be sure the area is well ventilated. Turn
the thermostat OFF. If the blower is running, wait until it
stops automatically. Turn OFF the gas and electrical power
supplies to the furnace. Check all metal parts and surfaces
to be sure they have cooled to room temperature before
you begin.
1. Follow the instructions to turn off the appliance before servicing.
2. Filters are installed in the return air plenum above the blower
assembly. An “A” frame assembly supports the filters. Lift the filter
slightly and remove for service.
3. Follow the instructions “HOW TO CLEAN YOUR FURNACE’S FIL-
TER”.
Blower Care
Even with good filters properly in place, blower wheels and motors will
become dust laden after long months of operation. The entire blower
assembly should be inspected annually. If the motor and wheel are
heavily coated with dust, they can be brushed and cleaned with a vac-
uum cleaner. If the blower cannot be properly cleaned without removing
it from the furnace, then this service must be performed by a qualified
service agency.
4. Reverse the procedure to reinstall filters.
5. Follow the operating instructions to place appliance in operation.
FILTER RACK
(factory supplied with some furnaces)
RACK AND FILTERS SECURED
INSIDE BLOWER SECTION
FOR SHIPMENT
CASING SIZE DIMENSION FH
The blower can be serviced/removed through the blower access panel
on the inside of the furnace. If there is a combustion air pipe installed
inside the furnace, it may have to be removed to access the blower
access panel. After the combustion air pipe is removed, it is easy to
remove the inside blower access panel by removing the screws of the
access panel. Blower is now ready to be serviced through the opening.
If the blower has to be removed through the inside blower access panel,
then the top and bottom angles will have to be removed to slide the
blower out of the furnace.
14-1/2”
17-1/2”
21”
13-1/4”
12-1/2”
11-1/2”
9-3/4”
24-1/2”
NOTE: FILTER ACCESS THROUGH
DUCTWORK MUST BE PROVIDED
FOR REMOVAL AND CLEANING
BRANCH
DUCTS
FILTERS
FILTER
RACK
DUCTWORK
FH
CROSS SECTION A-A
(with Plenum and filters)
Make sure you DO NOT move the clip-on weight on the
indoor fan wheel when cleaning the wheel. This weight is
used to balance the wheel. Moving the weight will cause
the fan wheel to vibrate.
FIGURE 7: Filter Rack Assembly and Attachment
Externally Mounted Air Filters
Some installations may have the air filter in a rack attached to the cas-
ing of the furnace or placed in the return air duct. You can gain access
to the filter by pulling on the door or unscrewing the retaining screw,
then slide the filter(s) out of its channel. Replace throw away filter(s)
with the same size new filter(s). Throw away filter(s) may be replaced
with cleanable filter(s) at this time. Cleanable filter(s) may be cleaned as
described in the manufacturer instructions or as described below and
then re-installed.
Air Filters
The filters should be checked every 3 months. On new construction,
check the filters every week for the first four weeks and every three
weeks after that, especially if the indoor fan is running continuously.
When replacing the filter(s), refer to Table 1 to be sure you install the
right size filter for your furnace. Dirty filters greatly restrict the flow of air
and may cause damage to the moving parts of the furnace. If the filters
become clogged the heat exchangers and blower motor could overheat
resulting in a potentially dangerous situation.
How to Clean your Filter
Never operate your furnace without a suitable air filter.
Use the following procedure to determine the filter size.
1. Measure the furnace width and use that measurement to deter-
mine the cabinet width.
High-velocity filters may be cleaned with a vacuum cleaner or washed
with a garden hose. Be sure to shake off excess water and allow filter to
completely dry before re-installing the filter.
To replace the filter after cleaning you must do the following:
1. Slide filter into place.
•
•
•
•
A 14-1/2” wide cabinet is a “A” cabinet.
A 17-1/2” wide cabinet is a “B” cabinet.
A 21” wide cabinet is a “C” cabinet.
A 24-1/2” wide cabinet is a “D” cabinet.
2. Snap the door on or place the door in position and tighten the
retaining screws, if provided.
3. Make sure the door is secure to the end of the filter rack.
2. Locate the cabinet size on Table 1 then determine whether you
have a bottom or side return air duct using the following method.
a. If the return air filter is on the left or right side of the furnace it
is a side return
4. For filter grilles, place the filter into the grilles, close the grille cover
and tighten the retaining screw.
Every time the filters are changed the following items should be visually
inspected:
b. If the air filter is on the bottom of the furnace then you have a
bottom return.
•
•
Check combustion air and vent pipe for blockage or leakage.
Check all components to be sure they are in good condition and
that there are no obvious signs of deterioration.
c. If the air filters are on the bottom and the side of the furnace
then you have a bottom and side return. You must replace
both air filters. Table 1 will indicate 2 filters by using brackets
with the number two (2).
•
•
Check the drain lines to make sure there are no cracks or leaks.
Check for dirt or lint on any surfaces or on components. Do not try
to clean any of the surfaces or components. Cleaning of the fur-
nace and its components must be done by a qualified service pro-
fessional.
d. If the air filters are on both sides of the furnace then you have
a two sided return. You must replace both air filters. Table 1
will indicate 2 filters by using brackets with the number two
(2).
4
Unitary Products Group
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
If, during the inspection of your furnace, you find any of the following
conditions:
SEQUENCE OF OPERATION
The following describes the sequence of operation of the furnace. Refer
to Figure 1 for component location.
•
•
•
•
Excessive amounts of dust and lint on components.
Damaged or deteriorated components or surfaces.
Leaks or blockage in the vent pipe passages.
Continuous Blower
Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the ON position the thermostat circuit is completed
between terminals R and G. The motor will operate on the speed tap
selected on the Continuous Fan Speed Jumper on the control board (HI
COOL, LO COOL, or HEAT pins).
Water on any surface inside or outside of the furnace.
Do not operate the furnace, call a certified dealer / servicing contractor
to check and / or clean your furnace, or for more information if you have
questions about the operation of your furnace.
If all components appear to be in good operating condition, replace the
front panels. Turn ON the gas and electrical power supplies to the fur-
nace, and set thermostat to the desired temperature.
Intermittent Blower - Cooling
Cooling/heating thermostats have a fan switch that has an ON and
AUTO position. In the AUTO position the thermostat circuit is completed
between terminals R and G when there is a call for cooling. The motor
will operate on the speed tap wire that is connected to the HI COOL ter-
minal on the control board. When used with two-stage cooling units, the
motor will operate on the speed tap connected to the LO COOL terminal
when first stage cooling is operating. The motor will operate on the
speed tap connected to the HI COOL terminal when second stage cool-
ing is operating. The fan off setting is fixed at 60 seconds for SEER
enhancement.
Motor Lubrication
The motors in these furnaces are permanently lubricated, and do not
require periodic oiling.
TABLE 1: Filter Sizes
CFM
Input / Output
BTU/H (kW)
Cabinet
Size
Top Return
Filter in(cm)
(m3/min)
1200 (34)
1200 (34)
1200 (34)
1600 (45)
1600 (45)
2000 (57)
40/37 (11.72/10.84)
60/55 (17.57/16.10)
80/75 (23.42/21.96)
80/75 (23.42/21.96)
100/95 (29.28/27.82)
100/95 (29.28/27.82)
A
B
B
C
C
C
D
(2) 14 x 20 (36 x 51)
(2) 14 x 20 (36 x 51)
(2) 14 x 20 (36 x 51)
(2) 14 x 20 (36 x 51)
(2) 14 x 20 (36 x 51)
(2) 14 x 20 (36 x 51)
(2) 14 x 20 (36 x 51)
Heating Cycle
When the thermostat switch is set on HEAT and the fan is set on AUTO,
and there is a call for heat, a circuit is completed between terminals R
and W of the thermostat. When the proper amount of combustion air is
being provided, the pressure switch will close, the ignition control pro-
vides a 17-second warm-up period, the gas valve then opens, the gas
starts to flow, ignition occurs and the flame sensor begins its sensing
function. The blower motor will energize 30 seconds after the gas valve
opens, if a flame is detected. Normal furnace operation will continue
until the thermostat circuit between R and W is opened, which causes
the ignition system and gas valve to de-energize and the burner flames
to be extinguished. The vent motor will operate for 15 seconds and the
blower motor will operate for the amount of time set by the fan-off delay
jumper located on the control board. See Figure 8. The heating cycle is
complete, and ready for the start of the next heating cycle.
120/112 (35.14/32.80) 2000 (57)
SECTION II: SERVICE AND MAINTENANCE
MANUAL
SAFETY SECTION
The following safety rules must be followed when servicing the
furnace.
ELECTRIC SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
RED - LOW SPEED
YELLOW - MED. LOW SPEED
BLACK - HIGH SPEED
BLUE -MED. HIGH SPEED
Improper servicing could result in dangerous operation,
serious injury, and death or property damage.
NEUTRALS
•
•
•
Before servicing, disconnect all electrical power to the fur-
nace.
When servicing controls, label all wires prior to discon-
necting. Reconnect wires correctly.
CONTINUOUS
FAN SPEED
JUMPER
Verify proper operation after servicing.
FAN OFF
ADJUSTMENT
JUMPER
FURNACE MAINTENANCE SECTION
The furnace should be cleaned and adjusted by a certified dealer or
qualified service contractor once a year or before the start of every
heating season. The following items must be cleaned and serviced or
replaced if there are signs of deterioration.
FIGURE 8: Typical Heat/Cool Speed Tap Connections
1. The vent terminal screen (if applicable).
If the flame is not detected within 2 seconds of the gas valve opening,
the gas valve is shut off and a retry operation begins. If the flame is lost
for 2 seconds during the 10-second stabilization period, the gas valve is
shut off and a retry operation begins. During a retry operation, the vent
motor starts a 15 second inter-purge and the ignitor warm-up time is
extended to 27 seconds. If the flame is established for more than 10
seconds after ignition during a retry, the control will clear the ignition
attempt (retry) counter. If three retries occur during a call for heat, the
furnace will shut down for one hour. If at the end of the one hour shut
down there is a call for heat, the furnace will initiate a normal start cycle.
If the problem has not been corrected the furnace will again lockout
after three retries.
2. The furnace vent and combustion air intake passageways. Should
it be necessary to service the vent/air intake system, the manufac-
turer recommends this service be conducted by a qualified service
agency. The operation of this appliance requires the reassembly
and resealing of the vent/air intake system.
3. The furnace burners, ignitor and flame sensor.
4. The condensate collection and disposal system. If any disassem-
bly of components containing flue or vent gases is required, a
qualified service agency must perform the service.
Unitary Products Group
5
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
A momentary loss of gas supply, flame blowout, or a faulty flame probe
circuit will result in a disruption in the flame and be sensed within 1 sec-
ond. The gas valve will de-energize and the control will begin a recycle
operation. A normal ignition sequence will begin after a 15 second inter-
purge. If during the five recycles the gas supply does not return, or the
fault condition is not corrected the ignition control will lockout for one
hour.
10. Restore electrical power and gas supply to the furnace.
11. Check furnace operation.
Cleaning the Secondary Heat Exchanger
1. Follow steps 1 - 7 under cleaning the Heat Exchanger.
2. Remove the vent piping from the vent blower housing. Disconnect
the drain lines from the vent blower housing and from the conden-
sate drain pan. Remove the vent blower housing blower and the
condensate pan.
During burner operation, a momentary loss of power for 50 milliseconds
or longer will de-energize the gas valve. When the power is restored,
the gas valve will remain de-energized and the ignition sequence will
immediately restart.
3. Using a stiff wire brush, remove the loose scale or soot from each
tube.
4. Vacuum the secondary heat exchanger.
Hot Surface Ignition System
5. Finish the cleaning procedure by following steps 9 - 11 under
cleaning the Heat Exchanger.
Cleaning the Vent / Air Intake System
HOT SURFACE IGNITION SYSTEM
Should it be necessary to service the vent / air intake system, the man-
ufacturer recommends this service be conducted by a qualified service
agency.
Do not attempt to light this furnace by hand (with a
match or any other means). There may be a potential
shock hazard from the components of the hot surface
ignition system. The furnace can only be lit automatically
by its hot surface ignition system.
The operation of this appliance requires the reassembly and resealing
of the vent / air intake system as specified in the “Combustion Air and
Vent System” located in the Installation Manual.
FURNACE CLEANING SECTION
NOTE: The cleaning operations listed below must be performed only by
TROUBLESHOOTING
The following visual checks should be made before troubleshooting:
a qualified service agency.
1. Check to see that the power to the furnace and the ignition control
module is ON.
2. The manual shut-off valves in the gas line to the furnace must be
open.
Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and danger-
ous operation. Verify proper operation after servicing.
3. Make sure all wiring connections are secure.
4. Review the sequence of operation. Start the system by setting the
thermostat above the room temperature. Observe the system’s
response. Then use the troubleshooting section in this manual to
check the system’s operation.
Burner Removal/Cleaning
The main burners should be checked periodically for dirt accumulation.
If cleaning is required, follow this procedure:
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
Never bypass pressure switch to allow furnace opera-
tion. To do so will allow furnace to operate under poten-
tially hazardous conditions.
3. Remove the upper access panel and remove the burner box cover.
Do not try to repair controls. Replace defective controls
with UPG Source 1 Parts.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
Never adjust pressure switch to allow furnace operation.
5. Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
FURNACE CONTROL DIAGNOSTICS
6. Remove burners from the burner assembly.
7. Burners may be cleaned by rinsing in hot water.
8. Reassemble the burners in the reverse order.
The furnace has built-in, self-diagnostic capability. If a system problem
occurs, a blinking LED shows a fault code. The LED can flash red,
green or amber to indicate various conditions. It is located behind a
clear view port in the blower compartment door.
Cleaning the Heat Exchanger
The control continuously monitors its own operation and the operation
of the system. If a failure occurs, the LED will indicate the failure code. If
the failure is internal to the control, the light will stay on continuously. In
this case, the entire control should be replaced, as the control is not
field repairable.
1. Turn off the electrical power to the unit.
2. Turn off the gas supply at the external manual shut-off valve and
loosen the ground union joint.
3. Remove the upper access panel and remove the burner box cover.
4. Disconnect wires from flame sensor, rollout switch and HSI igniter.
Remove igniter carefully, as it is easily broken.
Flash sequence codes 1 through 11 are as follows: LED will turn “on” for
1/4 second and “off” for 1/4 second. This pattern will be repeated the
number of times equal to the code. For example, six “on” flashes equals
a number 6 fault code. All flash code sequences are broken by a 2 sec-
ond “off” period.
5. Remove the screws that hold the burner box assembly to the vest
panel and remove the assembly.
6. Remove the vent pipe assembly, vent blower and condensate pan.
7. The heat exchanger is now exposed.
SLOW GREEN FLASH: Normal operation.
SLOW AMBER FLASH: Normal operation with call for heat.
8. With a long flexible wire brush, clean inside each tube at both the
top and bottom. The brush must pass around the rear heat
exchanger tubes. Then vacuum loose the scale and dirt from each
tube.
RAPID RED FLASH: Twinning error, incorrect 24V phasing. Check
twinning wiring.
RAPID AMBER FLASH: Flame sense current is below 1.5 microamps.
9. Replace all components in reverse order. Reconnect all wiring.
Check and clean flame sensor. Check for proper gas flow.
6
Unitary Products Group
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
1 RED FLASH: This indicates that flame was sensed when there was
not a call for heat. With this fault code the control will turn on both the
inducer motor and supply air blower. A gas valve that leaks through or
is slow closing would typically cause this fault.
4 AMBER FLASHES: Y present with no G call. Normally, both Y and G
are energized on a call for cooling. If a Y signal is present with no G sig-
nal, check to see that the wire from the G terminal on the board to the
wall thermostat has not broken or disconnected.
2 RED FLASHES: This indicates that the normally open pressure
switch contacts are stuck in the closed position. The control confirms
these contacts are open at the beginning of each heat cycle. This would
indicate a faulty pressure switch or miswiring.
STEADY ON RED: Control failure. Replace control board.
60-MINUTE AUTOMATIC RESET FROM LOCKOUT: This control
includes a “watchdog” type circuit that will reset from a lockout condition
after 60 minutes. Operational faults 6,7,8 will be reset. This provides
protection to an unoccupied structure if a temporary condition exists
causing a furnace malfunction. An example would be a low incoming
gas supply pressure preventing unit operation. When the gas pressure
is restored, at some point the “watchdog” would restart the unit and pro-
vide heat for the house.
3 RED FLASHES: This indicates the normally open pressure switch
contact did not close after the inducer was energized. This could be
caused by a number of problems: faulty inducer, blocked vent pipe, bro-
ken pressure switch hose or faulty pressure switch.
4 RED FLASHES: This indicates that a primary or auxiliary limit switch
has opened its normally closed contacts. With this fault code the control
will operate the supply air blower and inducer. This condition may be
caused by: dirty filter, improperly sized duct system, incorrect blower
speed setting, incorrect firing rate or faulty blower motor.
NOTE: If a flame is detected the control flashes the LED for 1/8 of a
second and then enters a flame stabilization period.
IGNITION CONTROL (P/N 031-01972-000)
Normal flame sense current is approximately
3.7 microamps DC (µa)
Low flame signal warning starts at 1.5 microamps.
Low flame signal control lockout point is
0.9 microamps DC (µa)
5 RED FLASHES: This fault is indicated if the normally closed contacts
in the rollout switch opens. The rollout control is manually reset. If it has
opened, check for proper combustion air, proper inducer operation, and
primary heat exchanger failure or burner problem. Be sure to reset the
switch after correcting the failure condition.
DIAGNOSTIC FAULT CODE STORAGE AND
RETRIEVAL
The control in this furnace is equipped with memory that will store up to
five error codes to allow a service technician to diagnose problems
more easily. This memory will be retained even is power to the furnace
is lost. This feature should only be used by a qualified service tech-
nician.
6 RED FLASHES: This indicates that after the unit was operating, the
pressure switch opened 4 times during the call for heat. If the main
blower is in a “Delay on” mode it will complete it, and any subsequent
delay off period. The furnace will lock out for one hour and then restart.
7 RED FLASHES: This fault code indicates that the flame could not be
established. This no-light condition occurred 3 times (2 retries) during
the call for heat before locking out. Low gas pressure, faulty gas valve,
dirty or faulty flame sensor, faulty hot surface ignitor or burner problem
may cause this.
The control stores up to five separate error codes. If more than five
error codes have occurred since the last reset, only the five most recent
will be retained. The furnace control board has a button, labeled "LAST
ERROR" that is used to retrieve error codes. This function will only work
if there are no active thermostat signals. So any call for heating, cooling
or continuous fan must be terminated before attempting to retrieve error
codes.
8 RED FLASHES: This fault is indicated if the flame is lost 5 times (4
recycles) during the heating cycle. This could be caused by low gas
pressure, dirty or faulty flame sensor or faulty gas valve. The furnace
will lock out for one hour and then restart.
9 RED FLASHES: Indicates reversed line voltage polarity or grounding
problem. Both heating and cooling operations will be affected. Check
polarity at furnace and branch. Check furnace grounding including the
transformer ground. Check that flame probe is not shorted to chassis.
To retrieve the error codes, push the LAST ERROR button. The LED on
the control will then flash the error codes that are in memory, starting
with the most recent. There will be a two-second pause between each
flash code. After the error codes have all been displayed, the LED will
resume the normal slow green flash after a five second pause. To
repeat the series of error codes, push the button again.
10 RED FLASHES: Gas flow with no call for heat. Check gas valve and
gas valve wiring.
11 RED FLASHES: This indicates that a primary or auxiliary limit switch
has opened its normally-closed contacts and has remained open for
more than five minutes. This condition is usually caused by a failed
blower motor or blower wheel. Cycle power (24 VAC) to the control to
reset the hard lockout condition after correcting the failure condition.
If there are no error codes in memory, the LED will flash two green
flashes. To clear the memory, push the LAST ERROR button and hold it
for more than five seconds. The LED will flash three green flashes when
the memory has been cleared, then will resume the normal slow green
flash after a five-second pause.
Thermostat Satisfied
Thermostat Calling for Heat
(Seconds)
0
2
17
22
52
0
Fan on Delay
30 Seconds
ON
ON
ON
THERMOSTAT
INDUCER
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
15 Sec.
Post
Purge
IGNITOR
OFF
ON
MAIN VALVE
OFF
ON
HUMIDIFIER
OFF
OFF
OFF
OFF
ELECTRONIC
AIR CLEANER
ON
ON
OFF
OFF
CIRCULATING
BLOWER
60, 90, 120, 180 SEC.
Selectable Fan Off Delay
FIGURE 9: Furnace Control Event Schedule
Unitary Products Group
7
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
SECTION III: REPLACEMENT PARTS LIST
35
32
17
7
26
55
74
13
45
85
75
2
34
88
27
72
18
41
42
71
67
11
5
14
10
9, 37
46
29
15
16
17
56
74
1
52
54
48
65
58
49
24
56,57
2
4
21
20
62
25
50
14
22
5
28
51
6
30
44
43
53
14
47
6
28
23
44
66
19
10
30
9,37
36
43
46
33
40
82
8
Unitary Products Group
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
ITEM
DESCRIPTION
ITEM
DESCRIPTION
MISCELLANEOUS
MOTOR
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
PLUG, WINDOW, CLEAR - 1.5”
1
2
MOTOR,DIRECT DRIVE BLOWER
MOTOR, INDUCER ASS’Y
COMBUSTION AIR TRANSITION, 3-WAY
TUBING, SILICONE (Gray, .188 ID, 2.83 ft. req’d)
TUBING, SILICONE (Preformed)
ELECTRICAL
3
4
CAPACITOR, RUN
TUBING, SILICONE (Gray, .188 ID, 1.25 ft. req’d)
GASKET, COMBUSTION BLOWER
GASKET, CONDENSATE PAN
SWITCH, LIMIT (INDUCER)
LIMIT, TEMPERATURE (Primary)
LIMIT, FLAME ROLL-OUT
CONTROL, FURNACE MODULE
FUSE
5
6
GASKET, UPPER CONDENSATE PAN (2 Req’d)
GASKET, GAS CONTROLS
7
8
GASKET, CONDENSING COIL
9
IGNITER
GASKET, COMBUSTION AIR TRANSITION
10
11
12
13
14
SENSOR, FLAME
SWITCH, PRESSURE
SWITCH, DOOR
VENT PIPE 2” X 15.25” LG.
GROMMET, MOTOR (3 Req’d)
FERRULE (3 Req’d)
TRANSFORMER
VALVE, GAS
COMBUSTION BLWR RESTRICTOR
AIR MOVING
15
16
HOUSING, BLOWER
WHEEL, BLOWER
RETAINER, SQUARE
RESTRICTOR, TUBE
FABRICATED PARTS
PANEL, BLOWER COVER
WASHER, FLAT FIBERGLASS (2 Req’d)
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
BRACKET, CONDENSATE TRAP
BURNER, MAIN GAS
COIL, CONDENSING
SHELF, BLOWER
HARNESS, MAIN WIRING
MOUNT, 1 PC. MOTOR
ORIFICE, BURNER (Natural #45)
TRAP, CONDENSATE
HEAT EXCHANGER ASS’Y
MANIFOLD, GAS
WIRING DIAGRAM
45 DEG. STREET ELBOW 2”
DRAIN TUBE, CONDENSATE TRAP
DRAIN TUBE, COMBUSTION BLOWER
DRAIN TUBE, CONDENSATE PAN
DRAIN TUBE, STRAIGHT 21” LG.
DRAIN TUBE, RAIN GUTTER
DRAIN HOSE ASSEMBLY
DRAIN TUBE, CONDENSATE
LOCKNUT, CONDUIT (1/2”)
ADAPTER, INSERT
SHIELD, PAN
PAN, CONDENSATE
PANEL, VEST ACCESS
PANEL, BLOWER ACCESS
WRAPPER, BURNER BOX
CHANNEL, TOE PLATE
COVER, GAS CONTROL
PANEL, BOTTOM
PANEL, TOP
SUPPORT, BURNER
WRAPPER, CABINET
BRACKET, FILTER
BUSHING, THREADED
FILTER, AIR (2 Req’d) (20 x 14 x .75)
BAFFLE, BURNER BOX
PLATE, DIFFUSER
GROMMET, MANIFOLD
BRACKET, IGNITER
BRACKET, DOOR SWITCH
BRACKET, DOOR
DRAIN TUBE, VENT PIPE
DOOR KNOB (Black)
BOTTOM PANEL, BURNER BOX
TOP MOUNTING BRACKET
BOTTOM MOUNTING BRACKET
RETAINER, DOOR KNOB
NUT, SELF-THREADING
SIGHT GLASS, OVAL
NOTE: *Not Shown
Major components and suggested stocking items are shown with shaded item number.
Unitary Products Group
9
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
FIELD INSTALLED ACCESSORIES - NON-ELECTRICAL
DESCRIPTION
MODEL NO.
1NP0347
1CT0302
1CT0303
1PS0904
1PS0901
1PS0902
1PS0903
1NK0301
1HT0901
1CB0314
1CB0317
1CB0321
1CB0324
1TK0914
1TK0917
1TK0921
1TK0924
1VK0901
USED WITH
PROPANE (LP) CONVERSION KIT
ALL MODELS
CONCENTRIC INTAKE/VENT 2”
CONCENTRIC INTAKE/VENT 3”
ALL MODELS EXCEPT 120 MBH
ALL MODELS
40
60/100/120
HIGH ALTITUDE PRESSURE SWITCH KIT
(Does Not Include Orifices)
80/1200
80/1600
CONDENSATE NEUTRALIZER KIT
SIDEWALL VENT TERMINATION KIT
ALL MODELS
ALL MODELS
14-1/2” CABINET
17-1/2” CABINET
21” CABINET
24 1/2” CABINET
14-1/2” CABINET
17-1/2” CABINET
21” CABINET
24 1/2” CABINET
All MODELS
COMBUSTIBLE FLOOR BASE
COIL TRANSITION KIT
3-WAY TRANSITION KIT
REPLACEMENT PART CONTACT INFORMATION
This is a generic parts list. To request a complete parts list, refer to the contact information below:
1. Search for a part or browse the catalog.
2. Find a dealer or distributor.
3. Customer Service contact information.
a. Click on the “Brand Links” button
b. Click on the “Customer Service” button
• You can contact us by mail. Just send a written request to:
York International
Consumer Relations
5005 York Drive
Norman, OK 73069
10
Unitary Products Group
Download from Www.Somanuals.com. All Manuals Search And Download.
127237-UUM-A-0605
SECTION IV: WIRING DIAGRAM
FIGURE 10: Wiring Diagram
Unitary Products Group
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Limited Warranty
UPG warrants this product to be free from defects in factory workmanship and material under normal use and service and will, at its option, repair or replace
any parts that prove to have such defects according to the terms outlined on this warranty. This warranty covers only the equipment described by the Product
Model Number and Serial Number listed on the Warranty Registration Card.
UPG warrants the primary heat exchangers in the product to be free from defects in factory workmanship and material under normal use and service and will at
its option, repair or furnish a replacement heat exchanger, either new or reconditioned, that meets the intended fit, use and function of the original heat
exchanger for any heat exchanger furnished by UPG which proves to have such defects within the duration of warranty coverage. Alternatively, UPG may, at its
option, extend a replacement allowance to be applied toward the purchase of a new furnace or packaged unit marketed by UPG. The exact amount of the
allowance will be determined at the discretion of UPG, based upon current market conditions, but in no case shall this allowance exceed thirty (30) percent of
the original consumer purchase price of the furnace, excluding such items as ductwork, wiring, piping and installation costs. UPG shall have no responsibility
hereunder for installation, shipping, handling or other charges except as specifically provided herein.
For your benefit and protection, return the Warranty Registration Card to UPG promptly after installation. This will initiate the warranty period and allow us to
contact you, should it become necessary. In the absence of a recorded Warranty Registration Card, the warranty period will begin upon product shipment from
UPG.
This warranty extends only to the original consumer purchaser and is non-transferable. For this warranty to apply, the product must be installed according to
UPG recommendations and specifications, and in accordance with all local, state, and national codes; and the product must not be removed from its place of
original installation. The warranty period for repair or replacement parts provided hereunder shall not extend beyond the warranty period stated on the reverse
side of this warranty
HEAT EXCHANGER
FURNACE TYPE
Residential Applications
Original Owner
Lifetime
PARTS
Non-Residential
Applications
10
5
90% PS9 / FC9S / FL9S
UPG strongly recommends regular periodic preventative maintenance on this equipment. The person most familiar with the equipment in your HVAC system is
a UPG dealer. The UPG dealer can ensure your maintenance program meets the conditions of the "UPG Warranty", maximize the efficiency of the equipment,
and service your unit within the mandated guidelines with regard to unlawful discharge of refrigerants into the atmosphere.
This warranty applies only to products installed in the United States and Canada.
EXCLUSIONS
This warranty does not cover any:
1.
2.
3.
Shipping, labor, or material charges.
Damages resulting from transportation, installation, or servicing.
Damages resulting from accident, abuse, fire, flood, alteration, or acts of God (tampering, altering, defacing or removing the product serial number will
serve to void this warranty).
4.
5.
6.
7.
8.
Damages resulting from use of the product in a corrosive atmosphere.
Damages resulting from inadequacy or interruption of electrical service or fuel supply, improper voltage conditions, blown fuses, or other like damages.
Cleaning or replacement of filters.
Damages resulting from failure to properly and regularly clean air and/or water side of condenser and evaporator.
Damages resulting from: (I) freezing of condenser water or condensate; (II) inadequate or interrupted water supply; (III) use of corrosive water; (IV) fouling
or restriction of the water circuit by foreign material or like causes.
9.
Damages resulting from operation with inadequate supply of air or water.
10. Damages resulting from use of components or accessories not approved by UPG (vent dampers, etc.).
11. Increase in fuel or electric cost.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABIL-
ITY AND FITNESS FOR A PARTICULAR PURPOSE.
SOME STATES DO NOT ALLOW THE DISCLAIMER OF IMPLIED WARRANTY, SO THAT THE ABOVE DISCLAIMER MAY NOT APPLY TO YOU.
SOME STATES ALLOW ONLY A PARTIAL LIMITATION ON IMPLIED WARRANTIES TO LIMIT THE DURATION OF IMPLIED WARRANTIES TO THE DURA-
TION OF THE EXPRESS WARRANTY. IN SUCH STATES, THE DURATION OF IMPLIED WARRANTIES IS HEREBY EXPRESSLY LIMITED TO THE DURA-
TION OF THE EXPRESS WARRANTY ON THE FACE HEREOF.
IN NO EVENT, WHETHER AS A RESULT OF BREACH OF WARRANTY OR CONTRACT, TORT (INCLUDING NEGLIGENCE) STRICT LIABILITY OR OTH-
ERWISE, SHALL UPG BE LIABLE FOR SPECIAL, INCIDENTAL, OR CONSEQUENTIAL DAMAGES, INCLUDING BUT NOT LIMITED TO LOSS OF USE OF
THE EQUIPMENT OR ASSOCIATED EQUIPMENT, LOST REVENUES OR PROFITS, COST OF SUBSTITUTE EQUIPMENT OR COST OF FUEL OR ELEC-
TRICITY. THE ABOVE LIMITATIONS SHALL INURE TO THE BENEFIT OF UPG'S SUPPLIERS AND SUBCONTRACTORS. THE ABOVE LIMITATION ON
CONSEQUENTIAL DAMAGES SHALL NOT APPLY TO INJURIES TO PERSONS IN THE CASE OF CONSUMER GOODS.
SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, OR FOR STRICT
LIABILITY IN TORT, SO THAT THE ABOVE EXCLUSIONS AND LIMITATIONS MAY NOT APPLY TO YOU.
UPG DOES NOT ASSUME, OR AUTHORIZE ANY OTHER PERSON TO ASSUME FOR UPG, ANY OTHER LIABILITY FOR THE SALE OF THIS PRODUCT.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS. YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
For Owner's Information:
PRODUCT MODEL. NO. ____________________ INSTALLATION DATE ______________________________
UNIT SERIAL NO. _________________________ INSTALLING DEALER ______________________________
Subject to change without notice. Printed in U.S.A.
127237-UUM-A-0605
Copyright © by Unitary Products Group 2005. All rights reserved.
Supersedes: 104449-UUM-A-1204
Unitary
Products
Group
5005
York
Drive
Norman
OK
73069
Download from Www.Somanuals.com. All Manuals Search And Download.
|