Large Capacity Thin Twin
Washer•Dryer – 120/240 Volt
®
Installation Instructions
Home
Appliances
IMPORTANT:
Read and save
these instructions.
IMPORTANT:
Installer: Leave Installation Instructions
with the homeowner.
Homeowner: Keep Installation Instructions
for future reference.
Save Installation Instructions for local
electrical inspector’s use.
Part No. 3397616 Rev. B
Download from Www.Somanuals.com. All Manuals Search And Download.
Before you start...
Do Not store or operate washer/dryer
below 32°F (some water may remain in
washer). Proper operation of dryer
cycles requires temperatures above
45°F. See Use & Care Guide for
Your safety and the safety of others are
very important.
DANGER
We have provided many important safety messages
in this manual and on your appliance. Always read
and obey all safety messages.
You can be killed or seriously injured if you
don’t immediately follow instructions.
“Winterizing” information.
WARNING
Check code requirements: Some codes
limit or do not permit installation of
clothes dryers in garages, closets,
mobile homes and sleeping quarters.
Contact your local building inspector.
This is the safety alert symbol.
This symbol alerts you to potential
hazards that can kill or hurt you and
others.
You can be killed or seriously injured if you don’t
follow instructions.
All safety messages will tell you what the potential
hazard is, tell you how to reduce the chance of
injury, and tell you what can happen if the
instructions are not followed.
All safety messages will follow the safety alert
symbol and either the word “DANGER” or
“WARNING”. These words mean:
Check utilities: Proper, water and
electrical supply connections must be
available.
Check location where washer/dryer will
be installed. Proper installation is your
responsibility. The washer/dryer must not
be installed or stored in an area where it
will be exposed to water and/or
WARNING
weather. Make sure you have
everything necessary for correct
installation.
Hot and cold water
Water heater: Set to deliver 140°F
water to the washer.
Explosion Hazard
faucets: Must be within
4 feet of the back of
the washer/dryer and
provide water pressure
of 5-100 PSI.
Keep flammable materials and vapors,
such as gasoline, away from dryer.
Laundry tub drain system: Needs a
20-gallon laundry tub. Top of tub
must be at least 34 inches high and
no higher than 72 inches from floor.
Failure to do so can result in death,
explosion, or fire.
If a longer drain hose is needed,
drain hose (Part No. 388423) and
hose extension kit (Part No. 285442)
are available from a Whirlpool-
authorized parts distributor.
Location: Should be large enough to
fully open dryer door to 90°. See Panel
G for “Recessed and closet installation
instructions” and “Product dimensions.”
Grounded electrical connection is
required. See “Electrical requirements.”
Dryer may be exhausted from the
rear or left or right side. Exhausting
through the side requires Part No.
279823. See “Exhaust requirements,”
Panels C and D.
Standpipe drain system: Needs
a two-inch diameter standpipe
with minimum carry-away
capacity of 17 gallons per
minute. Top of standpipe must
be at least 34 inches high and
no higher than 72 inches from
floor.
Drain hose
Untape and
may also be
open washer
Four-inch metal exhaust vent is
required.
installed to a
lid. Remove
laundry tub or
packages
floor drain
and hoses
SEE RECESSED AREA INSTRUCTIONS
ON PANEL G.
system.
Floor drain system requires a
siphon break, Part No.
285320, available from a
Whirlpool-authorized
parts distributor.
from washer.
See Panel F.
Important: Observe all
governing codes and
ordinances.
Level floor:
1-inch maximum
slope under entire
washer/dryer.
Support: Floor must be sturdy enough to
support washer/dryer weight, with water
and clothes, of 500 pounds.
Tools and materials
WARNING
Power supply cord
needed for installation:
Local codes may permit the use of a
U.L.-listed, 120/240-volt minimum, 30-
ampere, dryer power supply cord kit
(pigtail). Power supply cord should be
Type SRD or SRDT and be at least four
feet long. The wires that connect to the
dryer must end with ring terminals or
spade terminals with upturned ends.
A 3/4", U.L.-listed strain relief must be
installed where the power supply cord
connects to the dryer (see Figures 1
ut
kn
Electrical Shock Hazard
Plug into a grounded 4-prong outlet.
Failure to do so can result in death or
electrical shock.
level
safety glasses
and 2).
spade
Electrical requirements
terminals with
upturned ends
gloves
A four-wire or three-wire, single-phase,
120/240-volt, 60-Hz, AC-only electrical
supply (or four-wire or three-wire,
3/4" U.L.-listed
strain relief
NEUTRAL
(white)
pliers
Phillips screwdriver
120/208-volt, if specified on the
model/serial rating plate) is required on
a separate, 30-ampere circuit, fused on
both sides of the line. A time-delay fuse
or circuit breaker is recommended. The
model/serial rating plate is located in
the door well behind the dryer door on
the front of the opening.
It is the personal responsibility and
obligation of the customer to contact a
qualified electrician to assure that the
electrical installation is adequate and in
conformance with the National
Electrical Code, ANSI/NFPA 70 — latest
edition*, and all local codes and
ordinances.
flat-blade
adjustable
wrench (two
may be
screwdriver
NEUTRAL
ground prong
ground wire
(green)
required)
ring
terminals
Four-wire power supply cord
NEMA 14-30P
Figure 1
spade
terminals with
upturned ends
ring terminals
This blade connected
to this conductor.
NEUTRAL
Copies of the standards listed above may be
obtained from:
* National Fire Protection Association
Batterymarch Park
Quincy, Massachusetts 02269
3/4" U.L.-listed
strain relief
NEUTRAL
(white or center)
Three-wire power supply cord
NEMA 10-30P
Panel A
Figure 2
Download from Www.Somanuals.com. All Manuals Search And Download.
A.
For use where
local codes
Four-wire connection...
permit use of
flexible power
supply cord.
WARNING
WARNING
four-wire
three-wire
receptacle(14-30R) receptacle(10-30R)
Figure 3
Figure 4
Fire Hazard
Fire Hazard
Four-wire installation is recommended
(required for mobile homes): The power
supply cord must have four, No.-10
copper wires and match a four-wire
receptacle of NEMA Type 14-30R (see
Figure 3). The fourth wire (ground
conductor) must be identified with a
green cover and the neutral conductor
by a white cover.
Three-wire installation (if a four-wire
system is not available): The power
supply cord must have three, No.-10
copper wires to match a three-wire
receptacle of NEMA Type 10-30R (see
Figure 4).
Use a new UL approved 30 ampere
power supply cord.
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
Use a UL approved strain relief.
Disconnect power before making
electrical connections.
Disconnect power before making
electrical connections.
Connect neutral wire (white or center
wire) to center terminal (silver).
Connect neutral wire (white or center
wire) to center terminal (silver).
Ground wire (green or bare wire) must
be connected to green ground
connector.
Ground wire (green or bare wire) must
be connected to green ground
connector.
Connect remaining 2 supply wires to
remaining 2 terminals (gold).
Connect remaining 2 supply wires to
remaining 2 terminals (gold).
Securely tighten all electrical
connections.
Securely tighten all electrical
connections.
Failure to do so can result in death,
fire, or electrical shock.
Failure to do so can result in death,
fire, or electrical shock.
Direct wire
The washer/dryer can be connected
directly to fused disconnect or circuit
breaker box with four-wire or three-wire
flexible armored or non-metallic
sheathed copper cable (with ground
wire). Do Not use two-wire with bare
ground wire. All current-carrying wires
must be insulated.
DIRECT WIRE
POWER SUPPLY CORD
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Strip 5 inches of outer covering from
end of cable. Leave bare ground
wire at 5 inches. Cut 1-1/2 inches
from 3 remaining insulated wires.
Strip insulation back 1 inch (see
Figure 6).
center silver-
ground wire (green
colored terminal
block screw and
neutral white wire
with yellow stripes)
A conduit connector must be installed
at junction box. USE ONLY 10-GAUGE
SOLID COPPER WIRE. DO NOT USE
ALUMINUM WIRE. Allow four feet of slack
in the line so dryer can be moved if
servicing is ever necessary.
3-1/2"
3/4" U.L.-listed
strain relief
1"
power supply cord
ground wire (green)
external ground
connector
red
white
black
to disconnect
box
NEUTRAL
Electrical connection
wires stripped
of insulation
Figure 5
This dryer is manufactured with the
cabinet-ground conductor connected
to the NEUTRAL (center) of the wiring
harness at the terminal block. If local
codes do NOT permit this type of
connection, use “Four-wire connection”
instructions.
1. Disconnect the power supply.
2. Remove terminal block cover.
bare ground
wire
10-gauge, 3-wire
with ground wire
(Romex)
3. Install copper, four-wire power
supply cord through strain relief.
4. Remove the ground wire (green
with yellow stripes) from the external
ground connector and fasten
under center, silver-colored
terminal block screw.
5. Connect the ground wire (green) of
the copper, four-wire power supply
cord to the external ground
connector.
6. Connect the neutral wire (white) of
the power supply cord to the
center, silver-colored terminal screw
of the terminal block. Connect the
other wires to the outer terminals.
Tighten screws firmly.
5"
Direct wire preparation
Figure 6
GROUND INSTRUCTIONS: This appliance
must be grounded. In the event of
malfunction or breakdown, ground will
reduce the risk of electric shock by
providing a path of least resistance for
electric current.
Shape the end of each
u-shaped
hook
wire into a “U” shaped
hook (see Figure 7). The
bare ground wire must
be 4-1/2" long after
forming the hook.
Figure 7
If using a power supply cord, the plug
must be plugged into an appropriate
outlet that is properly installed and
grounded in accordance with all local
codes and ordinances.
4. Install copper, four-wire power
supply cable through strain relief.
5. Remove the ground wire (green with
yellow stripes) from the external
ground connector and fasten under
center, silver-colored terminal block
screw.
6. Slide the hook end of the ground
wire (bare) of the four-wire power
supply cable under the external
ground connector screw. Squeeze
hook end of wire together. Tighten
screw.
If using a direct wire connection, this
appliance must be connected to a
grounded metal, permanent wiring
system; or an equipment-ground
conductor must be run with the circuit
conductors and connected to the
equipment-ground terminal or lead on
the appliance.
7. Tighten strain relief screws.
8. Replace the terminal block cover.
7. Connect the neutral wire (white) of
the power supply cable to the
center, silver-colored terminal screw
of the terminal block using the same
method. Connect the other wires to
the outer terminals. Tighten screws
firmly.
WARNING - Improper connection of the
equipment-ground conductor can
result in a risk of electric shock. Check
with a qualified electrician or
serviceman if you are in doubt as to
whether the appliance is properly
grounded. Do not modify the power
supply cord plug. If it will not fit the
outlet, have a proper outlet installed by
a qualified electrician.
8. Tighten strain relief screws.
9. Replace the terminal block cover.
If the house has aluminum wiring, follow
the procedure below:
a) Connect a section of 8 gauge solid
copper wire to the connector block.
b) Connect the aluminum wiring to the
added section of copper wire using
special connectors designed and
Underwriters Laboratories Listed for
joining copper to aluminum. Follow
the electrical connector
manufacturer's recommended
procedure.
c) Aluminum/copper connection must
conform with local codes and
industry accepted wiring practices.
Panel B
Download from Www.Somanuals.com. All Manuals Search And Download.
B.
Exhaust requirements
Three-wire connection...
WARNING
Where local codes permit
connecting cabinet-ground
conductor to the neutral wire:
Where local codes permit
connecting cabinet-ground
conductor to the neutral wire of the
power supply cable:
WARNING
WARNING
Fire Hazard
Use a heavy metal vent.
Do not use a plastic vent.
Do not use a metal foil vent.
Failure to do so can result in death or
fire.
Fire Hazard
Fire Hazard
Use a new UL approved 30 ampere
power supply cord.
Use 10 gauge solid copper wire.
Use a UL approved strain relief.
Important: Observe all governing codes
and ordinances.
It is recommended that you exhaust
your dryer to the outside for best
performance. Moisture and lint indoors
may cause:
• Lint to gather around the dryer where
it can be fuel for a fire.
• Moisture damage to woodwork,
furniture, paint, wallpaper, carpet,
etc.
• Housecleaning problems and health
problems.
If the washer/dryer is installed in a
confined area such as a bedroom,
bathroom or closet, it must be
Use a UL approved strain relief.
Disconnect power before making
electrical connections.
Disconnect power before making
electrical connections.
Connect neutral wire (white or center
wire) to center terminal (silver).
Connect neutral wire (white or center
wire) to center terminal (silver).
Ground wire (green or bare wire) must
be connected to green ground
connector.
Ground wire (green or bare wire) must
be connected to green ground
connector.
Connect remaining 2 supply wires to
remaining 2 terminals (gold).
Connect remaining 2 supply wires to
remaining 2 terminals (gold).
Securely tighten all electrical
connections.
Securely tighten all electrical
connections.
Failure to do so can result in death,
fire, or electrical shock.
Failure to do so can result in death,
fire, or electrical shock.
exhausted to the outside and provision
must be made for enough air for
ventilation. Check governing codes and
ordinances. Also refer to the “Recessed
and closet installation instructions” on
Panel G.
Dura Safe vent products are
recommended and are available from
your dealer. See Panel G.
Four-inch diameter vent is required.
Use a heavy metal vent. Do not use plastic or
metal foil vent.
• Do Not use non-metal flexible vent, or
exhaust hoods with magnetic latches.
• Do Not exhaust dryer into a chimney,
furnace, cold air vent, attic or crawl space,
or any other vent used for venting.
• Do Not install flexible vent in enclosed walls,
ceilings or floors.
Rigid metal vent is recommended to prevent
crushing and kinking.
Flexible metal vent must be fully extended
and supported when the dryer is in its final
position.
Remove excess flexible vent to avoid
sagging and kinking that may result in
reduced air flow.
An exhaust hood should cap the exhaust
vent to prevent rodents and insects from
entering the home.
POWER SUPPLY CORD
DIRECT WIRE
center silver-colored
terminal block screw and
neutral white wire
ground wire (green
with yellow stripes)
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Strip 3-1/2 inches of outer covering from
end of cable. If using three-wire cable
with I wire, cut the bare wire even with
outer covering. Strip 1 inch of insulation
from the end of each insulated wire (see
Figure 9).
TM
Bare wire cut short. Wire is not
used. Dryer is grounded through
direct wire cable.
external ground connector
3/4" U.L.-listed
strain relief
Figure 8
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Install copper three-wire power supply
cord through strain relief.
4. Remove the ground wire (green with
yellow stripes) from under center, silver-
colored terminal block screw and
connect to external ground connector
(see Figure 8).
5. Connect the neutral wire (white or
center) of the power supply cord to the
center, silver-colored terminal screw of
the terminal block. Connect the other
wires to the outer terminals. Tighten
screws firmly.
1"
red
to disconnect
box
NEUTRAL
wires stripped
of insulation
white
black
10-gauge, 3-wire or,
10-gauge, 3-wire with
ground wire (Romex)
3-1/2"
Direct wire preparation
Figure 9
u-shaped
hook
Shape the end of each
wire into a “U” shaped
hook (see Figure 10).
6. Tighten strain relief screws.
7. Replace the terminal block cover.
Figure 10
Exhaust outlet hood must be at least 12
inches from the ground or
any object that may be in
the path of the exhaust
ground wire (green with
yellow stripes)
center silver-colored
terminal block screw and
neutral white wire
(such as flowers, rocks or
Where local codes DO NOT permit
connecting the cabinet-ground
conductor to the neutral (white)
wire:
bushes, etc.).
12" min.
If using an existing exhaust
system, clean lint from entire
length of system and make sure exhaust
hood is not plugged with lint.
Replace any plastic or metal foil vent with
rigid metal or flexible metal vent.
Use clamps to seal all joints. Do not use duct
tape, screws or other fastening devices that
extend into the interior of the vent to secure
vent.
Service check: Back pressure in any exhaust
system used must not exceed 0.6 inches in
water column measured with an incline
manometer at the point that exhaust vent
connects to dryer.
external ground connector
POWER SUPPLY CORD
OR DIRECT WIRE
Figure 11
4. Install copper, three-wire power supply
cable through strain relief.
5. Remove the ground wire (green with
yellow stripes) from under center, silver-
colored terminal block screw and
connect to external ground connector
(see Figure 11).
6. Slide the hook end of the neutral (white
or center) wire from the three-wire
power supply cable under the center,
silver-colored terminal screw of the
terminal block. Squeeze the hook end of
the wire together. Tighten screw.
center silver-colored
terminal block screw and
neutral white wire
ground wire (green
with yellow stripes)
external
ground
connector
separate copper
ground wire
Connect separate copper ground wire
from external ground connector
to approved ground.
Figure 12
7. Connect the other wires to the
outer terminals using the same method.
Tighten screws firmly (see Figure 11).
8. Tighten strain relief screws.
9. Replace the terminal block cover.
1. Disconnect the power supply.
2. Remove terminal block cover.
3. Install solid copper, power supply cord or
cable through strain relief.
4. Remove the ground wire (green with
yellow stripes) from the external ground
connector.
5. Connect the ground wire (green with
yellow stripes) and the neutral (white)
wire of the power supply cord or direct
wire cable to the center, silver-colored
terminal screw of the terminal block.
Connect the other wires to the outer
terminals. Tighten screws (see Figure 12).
6. Connect a separate copper ground wire
(No.-10 minimum) from the external
ground screw to an adequate ground.
7. Tighten strain relief screws.
8. Replace the terminal block cover.
Panel C
Download from Www.Somanuals.com. All Manuals Search And Download.
The exhaust vent can be
routed up, down, left,
right or straight out the
back of the
Now start...
with washer/dryer in laundry area.
washer/dryer. Space
requirements are
WARNING
provided on Panel G
and on the rear panel
of the washer/dryer.
Use the straightest path
you can, to avoid 90°
turns.
Excessive Weight Hazard
washer
coupling
Use two or more people to move and
install washer/dryer.
7.Insert a flat washer into each end
of the inlet hoses. Check that washers
are firmly seated in couplings.
Failure to do so can result in back or
other injury.
Maximum length of the exhaust system
depends upon the type of vent used,
number of elbows and the type of
exhaust hood. The maximum length for
both rigid and flexible vent is shown in
the chart.
Truck only from rear to prevent product
damage.
cold
1.Put on safety glasses and gloves.
Inlet valves are
plastic. Do not strip
or crossthread.
hot
4"
2-1/2"
Rear, Side or Bottom Exhaust
Number
of 90°
turns
Maximum
length of
vent
Four-inch
8.Attach hose to bottom (hot
water) inlet valve opening first; then
second hose to top (cold water) inlet
valve. Tighten couplings by hand. Use
pliers to make an additional two-thirds
turn.
2.Open washer lid. Take hoses and
diameter vent
parts packages out of basket. Close lid.
rigid metal
vent
42 ft
34 ft
26 ft
0
1
2
drain hose
clamp
yellow clamp
IMPORTANT: THIS PROCEDURE
MUST BE FOLLOWED TO ASSURE
PROPER INSTALLATION.
26 ft
21 ft
16 ft
0
1
2
flexible metal
vent
4 washers
1/4"
clamp
The maximum length using a 2" x 6" rectangular
vent with 2 elbows and a 2-1/2" (TYPE C) exhaust
hood is 8 ft.
3.Remove parts from package.
max.
Check that all parts were included.
For exhaust systems not covered by the
exhaust length chart, see Service
Manual, Part No. 603197, available from
a Whirlpool-authorized parts distributor.
1/4"
drain hose
drain hose
connector
Four-inch exhaust hood is preferred.
However, a 2-1/2-inch exhaust hood
may be used. A 2-1/2-inch exhaust
hood creates greater back pressure
than other hood types. For permanent
installation, a stationary exhaust system
is required.
Exhausting the dryer
through the side of the
washer/dryer requires
the use of Side Exhaust
Kit, Part No. 279823,
available from a
9.To prevent the drain hose from
coming off or leaking, it must be
1. Wet the inside end of the drain hose
with tap water. DO NOT USE ANY
OTHER LUBRICANT.
2. Squeeze ears of drain hose clamp
with pliers to open and place clamp
over the end of the drain hose.
3. While holding clamp open, work end
of drain hose onto drain connector.
installed per the following instructions:
Pull the shipping
strap completely
out of the washer.
cotter
pins
Whirlpool-authorized
parts distributor. Follow
kit Installation
Instructions for proper
exhaust installation.
4. Position clamp over the drain hose
area marked “clamp.” Release
clamp. Clamp should be 1/4 inch
from end of drain hose.
4.Pull to completely remove the
shipping strap with 2 cotterpins from the
inside of the washer/dryer.
Save the shipping strap for use in Step 18.
Mobile home installation
This washer/dryer is suitable for mobile
home installations. The installation of the
washer/dryer must conform to the
Manufactured Home Construction and
Safety, Title 24 CFR, Part 3280 (formerly
the Federal Standard for Mobile Homes
Construction and Safety, Title 24, HUD
Part 280, latest edition).
5.Tilt washer/dryer forward. Check
that rear leveling legs move up and
down freely so that washer/dryer can
be properly leveled in Step 15.
6.Disconnect the power supply.
Connect power supply cord or cable to
dryer. See “Electrical connection,”
Panels B and C. Do Not plug power
supply cord into outlet or reconnect
power at this time.
Mobile home exhaust
requirements: The
washer/dryer must
have an outside
exhaust. If the dryer is
exhausted through
the floor and the
area under the
mobile home is
enclosed, the
outside
wall
Use new hoses and washers that came
with your washer/dryer.
Replace inlet hoses after 5 years of use
to reduce the risk of hose failure. Inspect
and replace inlet hoses if bulges, kinks,
cuts, wear, or leaks are found. When
replacing your inlet hoses, mark the
date of replacement on the label with a
permanent marker.
skirting
exhaust system
must terminate
outside the
floor
enclosed area
enclosed area.
Extension beyond the enclosure will
prevent lint and moisture buildup under
the mobile home.
Panel D
Download from Www.Somanuals.com. All Manuals Search And Download.
10.Standpipe or
laundry tub drain system:
Open yellow clamp and
slide over “hook” end of
drain hose to secure the
rigid and corrugated
sections together.
corner posts in the center of
the washer/dryer.
13.Before attaching water inlet
hoses, run water through both faucets
into a bucket. This will get rid of particles
in water lines that might clog hoses.
Mark which is the hot water faucet.
Floor drain system: Do
Not install “hook” end of drain hose to
corrugated section. Consult your
plumber for proper installation.
16.If washer/dryer is not level,
carefully tilt washer/dryer backward
until front of washer/dryer is 3-4 inches
off of floor. Insert 4 corner posts under
washer/dryer about 6 inches from the
left leg. Loosen nuts on each front leg.
Adjust the front legs up or down. Tilt
washer/dryer backward and remove
corner posts. Gently lower the
Slide washer/dryer onto cardboard or
hardboard before moving across floor to
avoid damaging floor covering.
Replace inlet hoses after 5 years of use
to reduce the risk of hose failure. Inspect
and replace inlet hoses if bulges, kinks,
cuts, wear, or leaks are found. When
replacing your inlet hoses, mark the
date of replacement on the label with a
permanent marker.
11.If you have room to work from
either side of the washer/dryer, move
washer/dryer close to final position so
you can easily complete the following
steps. (Go to Step 12.)
washer/dryer to the floor. Repeat Step
15 and 16 until washer/dryer is level.
14.Attach bottom inlet hose (inlet
marked “H”) to hot water faucet.
Attach top inlet hose (inlet marked “C”)
to cold water faucet. Tighten couplings
to the faucets by hand. Use pliers to
make final two-thirds turn.
Move washer/dryer to its permanent
location. Remove
cardboard/hardboard from under
washer/dryer.
If you are working in a closet or
recessed area, move the washer/dryer
into final position and remove
cardboard or hardboard from under
washer/dryer. Remove the access
panel by removing three Phillips-head
screws and one bumper, located at the
top of the access panel. Set panel,
screws and bumper aside. Complete
the following steps through the access
area.
17.When washer/dryer is level,
use adjustable wrench to turn nuts on
front legs up tightly against
washer/dryer base. If nuts are not tight
against washer/dryer base, the
washer/dryer may vibrate.
Secure the drain hose to the laundry
tub or standpipe with the shipping strap
removed from the back of the washer.
12.Put “hook” end of drain hose
into laundry tub or standpipe. Check for
proper length of drain hose.
16"
15.Carefully move the
washer/dryer into final position.Tilt
washer/dryer forward raising back legs
1 inch off of floor to adjust rear, self-
leveling legs. Gently lower washer/dryer
to floor. Check levelness of the
18.After shipping strap has been
removed (Step 4), look for the words
“cut here” marked on the shipping
strap, about 16 inches from plug end.
Cut the shipping strap at this mark. Pull
shipping strap out of the power supply
cord.
washer/dryer by placing a carpenter’s
level on top of the washer, first side to
side; then front to back. If washer/dryer
is not level, check that rear leveling legs
move up and down freely. If washer/
dryer is level, go to Step 17.
Numbers
correspond
to steps.
11. 20. 28.
6. 23. 30.
21. 22.
15.
9.
7.
8.
12. 19.
10.
7.
14.
Pull shipping strap
with 2 cotterpins
completely out of
washer.
4. 18. 19.
Panel E
Download from Www.Somanuals.com. All Manuals Search And Download.
Check that hose is not twisted or kinked
and is securely in place.
ut
kn
B
C
A
level
afety glasses
Phillips screwdriver
clamp
gloves
22.Connect exhaust vent to
washer/dryer and then to the exhaust
hood.
• Use the straightest path possible to
avoid 90° turns.
strap
strap
strap
adjustable
wrench (two
may be
pliers
19.Put “hook” end of drain hose
in laundry tub or standpipe. Tightly wrap
the shipping strap around the drain
hose and laundry tub or standpipe as
shown in Figures A and B. Push plug into
the nearest hole in the shipping strap.
If the water inlet faucets and drain
standpipe are recessed, put “hook” end
of drain hose in standpipe. Tightly wrap
the shipping strap around the drain
hose and faucet body (not the handles
or stems) as shown in Figure C. Push plug
into the nearest hole in the shipping
strap.
flat-blade
required)
screwdriver
• Use clamp to seal all joints in the
exhaust system.
• Use caulking compound to seal
exterior wall opening around exhaust
hood.
26.Check that you have all of
your tools.
23.CHECK ELECTRICAL
REQUIREMENTS. BE SURE YOU HAVE
CORRECT ELECTRICAL SUPPLY AND
RECOMMENDED GROUND METHOD.
Check the Installation Instructions to see
that you have completed each step.
Complete any missed steps before you
continue.
27.Turn on water faucets and
check for leaks. Tighten couplings if
there is leaking. Do Not overtighten; this
could cause damage to faucet.
Hose must be cut exactly to length so
“hook” end is held tightly over edge of
standpipe.
28.Replace access panel. Be
sure to tighten the three Phillips-head
screws at the top of the access panel.
Replace the bumper under the center
screw.
If drain hose cannot be strapped in
place, it must be cut exactly to
length so the “hook” end is held
D
tightly over the edge of the
tub or standpipe. See
Figure D.
If a longer drain hose is
needed, drain hose (Part
No. 388423) and hose
extension kit (Part No.
285442) are available
from a Whirlpool-
authorized
29.Read the Use and Care
Guide to fully understand your new
washer/dryer. Open dryer door. Check
to be sure lint screen is in its proper
position. Wipe out drum.
24.Check that all parts are now
installed. See parts list, Panel D. If there is
an extra part, go back through steps to
see which step was skipped.
parts
30.Plug power supply cord into
grounded outlet. Reconnect the power
supply. Now start the washer and allow
it to complete the regular cycle.
distributor. If
drain hose
must be
shortened,
use hose kit
(Part No.
285442).
31.Start dryer and allow it to
complete a full heat cycle to make sure
it is working properly.
Note: If washer/dryer is moved to adjust
drain hose, the washer/dryer must be
leveled again. Repeat Steps 15-17.
Place cardboard under the
washer/dryer and carefully move
washer/dryer to avoid damaging floor
covering.
You have successfully installed your
new Whirlpool washer/dryer. To get the
most efficient use from your new
Whirlpool washer/dryer, read your
Use and Care Guide.
Congratulations!
Keep Installation Instructions nearby
where you can refer to them. They’ll
make reinstalling your Whirlpool
washer/dryer in another home as
easy as the first installation.
25.Check that you removed all
the shipping pieces including the
shipping strap with its 2 cotterpins and
plug. Dispose of all materials in proper
manner.
If you do not remove the shipping strap,
your washer/dryer may “walk” away
from its location.
20.If you did not remove the
access panel in Step 11, remove three
Phillips-head screws and one bumper,
located at the top of the access panel.
Set the panel, screws and bumper
aside.
21.Determine the length of
exhaust vent that is needed to connect
the dryer to the exhaust hood. (See
“Exhaust requirements,” Panels C and D.)
Panel F
Download from Www.Somanuals.com. All Manuals Search And Download.
Recessed area minimum
installation spacing
Product dimensions
Recessed and closet
Most installation will require at least 5 inch
clearance behind the dryer for the dryer vent.
0" *
0" *
0" *
installation instructions
Location must be large enough to fully open dryer
This washer/dryer may be installed in a
recessed area or closet.
door.
6"
26-1/4"
The installation spacing is in inches and
is minimum allowable. Additional
dryer
spacing should be considered for ease
of installation, servicing and compliance
with local codes and ordinances.
28"
72-3/4"
If closet door is installed, the minimum
unobstructed air openings in top and
bottom are required. Louvered doors
with equivalent air openings are
acceptable. Closet installation must be
exhausted.
48"
5"
washer
34-3/4"
33-1/4"
Other installations must use the minimum
dimensions indicated.
side view
front view
Recessed, non-exhausted installation must use only the
rear exhaust position and Exhaust Deflector Part No. 694609.
32-1/4"
Note: If recessed installation is exhausted to the side or rear,
6" must be available above the washer/dryer but all other
spacing can be 0".
side view
27-3/8"
Closet installation must be exhausted outdoors.
WARNING - To reduce the risk of fire, this appliance MUST BE EXHAUSTED OUTDOORS.
13-11/16"
13-11/16"
0" ***
closet door
closet door
6"
3"
48 sq. in. **
48 sq. in. **
1" min.
exhaust
outlet
1-1/2"
hot
36-3/4"
water
inlet
27"
28-1/2"
drain
cold
water
inlet
outlet
24 sq. in. **
24 sq. in. **
5"
recess
depth
3"
front view
side view
22-3/4"
13-1/2"
*Additional clearances for wall, door and floor moldings may be required or if external exhaust
elbow is used.
recess width
**Opening is minimum for closet door. Louvered door with equivalent air openings is acceptable.
***Additional space may be needed for exhaust elbow.
rear view
TM
For more information,
or to easily place your
order, call
Periscopes For Offset
Dura Safe
Outlets, Tight Installations
SURE CONNECTTM Vent Kit
N Provides 2 1/2” clearance
between dryer and wall
Kits Make Installation Easy
1
2
N Great for closet
2 / "
NProvides 4 1/2”
clearance between
dryer and wall
1-800-442-9991
installations
N 0"-18", 18”-29” or
29”- 50” periscopes
include one male
snap-lock fitting,
one extra long
2 1/ 2
"
NSnap-Lock fittings
To have your venting
professionally installed,
call
NTotal kit length
8 feet
0"-18" : Part #4396037
18"-29" : Part #4396011
29"-50" : Part #4396014
draw-band collar
and one clamp
NAdditional vent can
be snapped between
0"-18" Periscope
1-800-253-1301
N Use when vent outlets
Part #4396028
sections for
overlap or are offset
longer runs
for the nearest
authorized service
provider.
N Excess length can
be trimmed to fit
Part #4396037
Kit Contains:
2- 4' vent sections with attached close elbows
1- Wall plate for close clearance installations
2- 4" clamps
18"-29" and 29"-50" Periscope
Sections separate,
fittings can face
same or opposite
Swivel collar
wall connection
Telescoping
sections
Swivel collar
Extra long
band-clamp
for dryer
Beveled edges
allow corner
installations
.
connection
Dura Safe and Sure Connect are Trademarks of Whirlpool, U.S.A.
18"-29" : Part #4396011
29"-50" : Part #4396014
Panel G
Download from Www.Somanuals.com. All Manuals Search And Download.
If washer/dryer does
not operate properly...
If you need assistance... If you need service...
The Whirlpool Customer Interaction Center
will answer any questions about operating
or maintaining your washer/dryer not
covered in the Installation Instructions. The
Whirlpool Customer Interaction Center is
open 24 hours a day, 7 days a week. Just
dial 1-800-253-1301 — the call is free.
When you call, you will need the
washer/dryer model number and serial
number. Both numbers can be found on the
model/serial rating plate located in the
door well behind the dryer door on front of
opening.
In the event that your Whirlpool
appliance should need service, call the
dealer from whom you purchased the
appliance or a Whirlpool-authorized
service company. A Whirlpool-
authorized service company is listed in
the Yellow Pages of your telephone
directory under “Appliances —
Check the following to be sure that:
1. Electrical supply is connected.
2. House fuse or circuit breaker is intact
and tight.
3. Washer lid or dryer door is closed.
4. Controls are set in a running or “ON”
position.
5. Dryer start button has been firmly
pushed.
6. Make sure shipping strap has been
completely removed and was used to
secure the drain hose to the laundry
tub or standpipe.
Household — Major — Service and
Repair.” You can also obtain the service
company’s name and telephone
number by dialing, free, within the
continental United States, the Whirlpool
Customer Interaction Center telephone
number, 1-800-253-1301. A special
operator will tell you the name and
number of your nearest Whirlpool-
designated service company.
Maintain the quality built into your
Whirlpool appliance — call a Whirlpool-
designated service company.
When moving the
washer/dryer...
• Disconnect the power supply cord,
then tape securely to the
washer/dryer.
• Tape the drum to the front panel.
Tape the lint screen in place. Tape
the dryer door closed.
• Wedge a blanket between the tub
ring and cabinet top to restrict tub
movement.
• Turn front leveling legs all the way in.
CORPORATION
Part No. 3397616 Rev. B
© 2000 Whirlpool Corporation
® Registered Trademark of Whirlpool, U.S.A.
Prepared by Whirlpool Corporation,
Benton Harbor, Michigan 49022
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|