Westinghouse Water Pump MA7200 2001 2 N1 User Manual

MA7200 PLUS INVERTER  
SERIES  
PUMP Quick Start Manual  
1 to 2 HP  
Models- MA7200-2001/2-N1 (230V)  
&
MA7200-4001/2-N1 (460V)  
Rev. 1.3 - May 27th 2008  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
Step 4 - Check Pump Motor Operation  
Enter 10.00Hz for the frequency reference and set parameter Sn-08 =1 to disable Reverse  
Direction operation. Note: The output from the inverter is displayed in Hz as factory default. If  
desired, the output may be displayed in per cent (%) of full speed. (see appendix)  
to  
;
0
1
1 - Press the  
2 - Press the  
key twice  
key  
Flashing  
Flashing  
3 - Press the  
2 Seconds  
key to  
.
1
Flashing  
`
______________________________________________________________  
3
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
Press the RUN key, and check the pump direction of rotation. If the direction is not correct, press  
the STOP key and wait until the motor has come to a complete STOP. Next, power down the  
inverter.  
Danger  
After the power has been turned OFF, wait at least 5 minutes until the charge  
indicator extinguishes completely before touching any wiring, circuit boards or  
components.  
Reverse any two of the pump motor connections at the inverter ( U(T1),V(T2), or W(T3) ). Next,  
following STEP 2, power-up the inverter; the motor direction should now be correct.  
Step 5 – Select Method of Control  
Before selecting the method of control, verify that the inverter is in the STOP mode.  
There are two methods of control or combinations thereof that may be selected; Keypad, and  
Analog Signal.  
RUN / STOP Command - Can be provided from the keypad or from an external contact  
(see Fig. 2a).  
Speed Reference – Can be from the keypad or from an external analog signal (0 – 10 VDC or  
4 – 20 mA). see Fig’s 3a,3b, and 3c.  
The RUN/STOP method of control is set by parameter Sn – 04 and the Speed Reference is set  
by parameter Sn – 05. The following Table shows the values to be set when selecting.  
Start / Stop  
Sn – 04=  
Speed Reference  
Value  
Sn – 05=  
*0  
1
Keypad  
External Contact  
Keypad  
External Analog  
* NOTE  
The factory default for Sn – 04 and Sn – 05 is set to 0; Digital Operator (Keypad) No  
further parameter changes are necessary if this is the desired method of control. If  
External Contact set to Sn – 04 or External Analog set to Sn – 05 is desired then  
proceed as follows.  
______________________________________________________________  
4
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
______________________________________________________________  
5
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
After the method of control has been selected, if external control wiring is required, (e.g. external  
analog) power pown the inverter before removing any covers or making any connections.  
In the following pages are wiring examples for Start / Stop, E-Stop, Restart, and Analog  
Connections.  
Danger  
After the power has been turned OFF, wait at least 5 minutes until the charge  
indicator extinguishes completely before touching any wiring, circuit boards, or  
components.  
______________________________________________________________  
6
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
DIGITAL INPUT / OUTPUT terminal connections ( 1 – 2 HP )  
Fig’s 2a, 2b, and 2c below show the control terminal connections for input control functions. The  
connections shown are typical and the user is referred to the MA7200 Manual if additional  
information is required. Fig. 2d shows an example for the use of the Fault Output Relay.  
STOP  
RUN  
______________________________________________________________  
7
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
ANALOG INPUT terminal connections ( 1 – 2 HP )  
Fig’s 3a,3b, and 3c.show the various analog input schemes that can be used to control the  
output frequency and thus the speed of the pump motor when External Analog is selected by  
Sn-05 in Step 5. Only one method may be used as the input source with Fig. 3a Potentiometer  
Input being most common.  
______________________________________________________________  
8
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
MA7200 PLUS BLOCK DIAGRAM  
Fig. 4 is an overall basic electrical connection diagram for MA7200 PLUS inverters rated 1 to 2  
HP. It is used in conjunction with the other sections of this guide to give the user the  
ability to successfully start up a Pump application. More detailed information is available in the  
MA7200 PLUS Manual to which the user is referred if further information is required.  
______________________________________________________________  
9
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
Appendix A-  
Changing display to read output speed in percent (%) of full speed.  
The display is factory defaulted to show the inverter output frequency in Hz. If desired, the  
display can be changed to show the output frequency as a percentage of full speed. To do this  
parameter Cn-28 must be changed from (00000) to (00001) as follows:  
To set parameter Cn-28 = 1  
(Display Percent)  
Resulting Display  
Keypad Steps  
PRGM  
An – 01 -  
key  
1 - Press the  
DRIVE  
Freq. Cmd. 1  
Cn – 01 -  
Input Voltage  
DSPL  
2 - Press the  
3 - Press the  
key 3 times  
Cn-28-  
key until display shows  
Operator DSPL Unit  
Flashing  
EDIT  
Cn-28 = 00000  
4 - Press the  
key  
ENTER  
Operator DSPL Unit  
Flashing  
Cn-28 = 00001  
5 - Press the  
6 - Press the  
key  
Operator DSPL Unit  
Flashing  
EDIT  
key to save  
Entry Accepted  
2 Seconds  
Flashing  
ENTER  
Cn-28 = 00001  
Operator DSPL Unit  
PRGM  
DRIVE  
7 - Press the  
key to return to the main display.  
______________________________________________________________ 10  
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MA7200 PLUS Inverter 1 to 2 HP Pump Quick Start Manual  
_______________________________________________________________  
Appendix B -  
Removing the LCD Digital Operator and Inverter Cover(s)  
______________________________________________________________ 11  
TECO – Westinghouse Motor Company  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Whirlpool Washer 8316243 User Manual
Windsor Vacuum Cleaner SRS12 User Manual
Yale Door 400 4400 User Manual
Yamaha Music Pedal FP8215 User Manual
Zanussi Clothes Dryer TE350 User Manual
Zanussi Convection Oven 239504 User Manual
Zanussi Convection Oven 240204 User Manual
Zanussi Freezer ZRB 2725 W User Manual
Zanussi Refrigerator ZECB 300 W User Manual
Zanussi Washer Dryer WDL 1282 User Manual