Waterford Appliances Stove LEPRECHAUN 90 OSA User Manual

LEPRECHAUN 90 O.S.A  
WOODBURNING STOVE  
SAFETY NOTICE  
Please read this entire manual before you install and use your new room heater. Failure to follow instructions  
may result in property damage, bodily injury or even death.  
This appliance is hot while in operation and retains its heat for a long period of time after use. Children,  
aged or infirm persons should be supervised at all times and should not be allowed to touch the hot  
working surfaces while in use or until the appliance has thoroughly cooled.  
If this stove is not properly installed, a house fire may result. For your safety, follow the installation directions.  
Contact local building or fire officials about restrictions and installation inspection requirements in your area.  
The stove must be connected to a UL/ULC listed high temperature residential type H.T. and building heating  
appliance chimney or an approved masonry chimney with flue liner.  
INSTALLATION AND OPERATING INSTRUCTIONS  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Rear Exit:  
FLOOR PROTECTION  
Fit the heat shield as follows:  
When installing this heater on a combustible floor, a  
floor protector, consisting of a layer of non-com-  
bustible material at least 3/8” (9.5mm) thick or 1/4”  
(6mm) thick covered with 1/8” (3mm) sheet metal is  
required to cover the area under the heater and to  
extend to at least 18” (450mm) at the front and 8”  
(200mm) to the sides and rear. This will provide pro-  
tection from sparks and embers which may fall out  
from the door when stoking or fuelling.  
Screw the four 4” 100mm x 1/4” 6mm tie bolts to the  
back panel (item 11). Fit the four 1” spacers (item  
31) over the tie bolts. Fit the inner heat shield (item  
28) without blanking plate onto the four tie bolts.  
Now fit the other four 1” 25mm spacers over the tie  
bolts and fit the outer heat shield (item 30) without  
blanking plate. Tighten the whole assembly togeth-  
er using the four 1/4” 6mm nuts and washers pro-  
vided.  
(200mm)  
(200mm)  
(450mm)  
(200mm)  
(50mm)  
(50mm)  
LOCATION  
There are several conditions to be considered when  
selecting a location for your Leprechaun 90 O.S.A.  
a.  
b.  
c.  
d.  
Distance from a suitable chimney  
(see chimneys).  
Position in the area to be heated, central  
locations are usually best.  
Allowance for proper clearances to  
combustibles.  
Obstruction in the ceiling, upper floor or roof,  
for example, ducting plumbing, electrical  
fittings and wiring, overhead fixed  
furnishings, etc.  
e.  
For safety, and to avoid draughts, avoid  
locations close to an exit.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING  
g.  
Air inlets traversing cavity walls should  
include a continuous duct across the cavity.  
The duct should be installed in such a man  
ner as not to impair the weather resistance  
of the cavity.  
DO NOT OBSTRUCT FREE AIR SUPPLY TO THE  
AIR INLET DUCT LOCATED AT THE BACK OF  
THE STOVE.  
h.  
l.  
Joints between air vents and outside walls  
should be sealed to prevent ingress of mois  
ture.  
This stove is listed for Mobile home installa  
tion provided it is properly connected to an  
outside air supply and a listed chimney with  
a ceiling support and spark arrester.  
DO NOT CONNECT TO OR USE IN CONJUNC-  
TION WITH ANYAIR DISTRIBUTION DUCTWORK  
UNLESS SPECIFICALLY APPROVED FOR SUCH  
INSTALLATIONS.  
OUTSIDE AIR CONNECTION  
This stove may be connected direct to the outside of  
the house for its combustion air supply.  
MOBILE HOME INSTALLATION  
Note: It is recommended to use the shortest  
possible outside air supply ducts. Supply ducts with  
long runs, multi bends and corners may reduce air  
volume supply due to excessive drag.  
In addition to standard installation instructions the  
following requirements are mandatory for installation  
in a Mobile Home.  
CAUTION: Do not obstruct combustion air opening.  
1.  
The stove must be permanently bolted to the  
floor of the Mobile Home using the floor  
screws provided.  
2.  
3.  
4.  
The stove must have a permanent outside  
air source for combustion.  
The stove must be grounded to the steel  
chassis of the Mobile Home.  
When connecting this stove to an outside air supply  
the optional outside air kit must be used, which  
includes a spigot, wire mesh, and fixing screws.  
A listed chimney system, roof thimble, spark  
arrestor and roof flashing kit suitable for use  
in Mobile Homes must be used.  
If the chimney exits the Mobile Home at a  
location other than through the roof, and  
exits at a point 7ft. (2100mm) or less above  
the ground level on which the Mobile Home  
is positioned, a guard or method of enclosing  
the chimney shall be fitted at the point of exit  
for a height up to 7 ft.(2100mm).  
The chimney shall be attached directly to the  
room heater and shall extend at least 3 ft.  
(910mm) above the part of the roof through  
which it passes. The top of the chimney  
should project at least 2 ft. (610mm) above  
the highest elevation of any part of the  
Mobile Home within 10 ft. (3050mm) of the  
chimney.  
a.  
b.  
Fit the cast iron spigot into the air inlet (Part  
No. 39).  
Connect a 4” (100mm) stainless steel, gal  
vanised ridge or flexible pipe to the air inlet  
spigot.  
5.  
c.  
d.  
e.  
f.  
Fit a 4” (100mm) stainless steel or gal-  
vanised sweep bend to the outside of the air  
supply pipe.  
Fit the stainless mesh to the downturn of the  
bend terminus using the fixing screws sup  
plied with the outside air kit.  
Make sure that all joints are secured using  
the fixing screws supplied with the outside  
air kit.  
The outside air terminus must be fitted with  
the 1/4” (6mm) x 1/4” (6mm) stainless wire  
mesh to prevent leaves and rodents entering  
from the out side.  
6.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
WALL PROTECTORS  
7.  
8.  
9.  
The chimney system shall comply with the  
standard for Chimney’s Factory-Built  
Residential Type and Building Heating  
Appliances UL 103.  
Any openings in a chimney guard if used  
must not permit the entrance of a 3/4”  
(19mm) diameter rod.  
CAUTION: THE STRUCTURAL INTEGRI  
TY OF THE MOBILE HOME ROOF,  
FLOOR, WALLS AND CEILING MUST BE  
MAINTAINED.  
10.  
Check any other local building code as other  
local codes may apply.  
11.  
WARNING: DO NOT INSTALL IN A  
SLEEPING ROOM  
Materials and products listed for the purpose of  
reducing clearance to combustibles shall be  
installed in accordance with the conditions of the  
listing and the clearances may be reduced by the  
percentage reduction as stated in the wall shield  
manufacturer’s instructions.  
For clearance reduction systems using an air space  
between the combustible wall and the wall protector,  
adequate air circulation shall be provided by one of  
the following methods.  
1.  
Adequate air circulation may be provided by  
leaving all edges of the wall protector open  
with at least a 1” 25mm air gap.  
2.  
If the wall protector is mounted on a single  
flat wall away from corners, adequate air cir-  
culation may be provided by leaving bottom  
and top edges open with at least a 1” 25mm  
air gap.  
3.  
Wall protectors that cover two walls in a cor-  
ner shall be open at the bottom and top  
edges with at least a 1” 25mm air gap.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Chimney, installed in accordance with the manufac-  
turers instructions or a lined masonry chimney  
acceptable to the authority having jurisdiction.  
4.  
All clearances shall be measured from the  
outer surface of the combustible material to  
the nearest point on the surface of the  
Leprechaun 90 O.S.A., disregarding any  
intervening protection applied to the com-  
bustible material.  
CHIMNEY CONNECTORS  
THE CHIMNEY CONNECTOR is a smokepipe used  
to connect the Leprechaun 90 O.S.A. Stove to the  
approved chimney described above. The CHIMNEY  
CONNECTOR must be made of CORROSION  
RESISTANT STEEL 24 gauge or heavier (“black” or  
“blued”, or equivalent treated steel).  
When using a manufactured wall shield system  
observe local building codes and by-laws.  
CHIMNEYS  
Consult the LOCALBUILDING CODE in all cases as  
to the particular requirements concerning the  
installation of SOLID FUEL TYPE ROOM  
HEATERS. This Leprechaun 90 O.S.A. WOOD  
BURNING STOVE is intended to be installed in  
accordance with National Fire Protection  
Associations Standard for Chimneys, Fireplaces  
and Vents. NFPA 211-1977.  
Be sure too fasten the chimney connectors together  
and also to the flue outlet of the stove through the  
holes provided. Use at least two screws for each  
joint. Be sure the joints are tight and fully secured.  
Chimney connectors shall not pass through an attic,  
or roof space, closet or similar concealed space, or  
a floor or ceiling. Where passage through a wall, or  
partition of combustible construction is desired, the  
installation shall conform to CAN/CSA -B 365,  
Installation code for Solid Fuel Burning Appliances  
and Equipment.  
The chimney must have a CROSS SECTIONAL  
AREA of at least 193.5 sq. cm. (30 sq. inches). It is  
best connected to a chimney of the same size, as  
connection to a larger size may result in somewhat  
less draught.  
Connectors should maintain a pitch or rise of at least  
1/4” (6mm) to the foot from the stove to the chimney.  
It should be installed so as to avoid sharp turns or  
other construction features that would create exces-  
sive resistance to the flow of flue gases. It should be  
securely supported with joints fastened with sheet-  
metal screws, rivets, or other approved means. The  
entire length of a connector should be readily acces-  
sible for inspection, cleaning and replacement.  
The Leprechaun 90 O.S.A. is a Radiant Room  
Heater and must be connected to a chimney of the  
proper size and type, capable of providing an ade-  
quate continuous draught of 0.06wg minimum. It is  
best to connect to a chimney of the same size as the  
stove spigot. DO NOT CONNECT TO A CHIMNEY  
SERVING ANOTHER APPLIANCE.  
Minimum chimney height is 14’ 10” (4.5m) from floor  
on which stove is installed. An existing masonry  
chimney should be inspected, and if necessary,  
repaired by a competent mason or relined, using an  
approved relining system. The stove must be  
connected to a chimney with a minimum continuous  
draught of 0.06”wg. Poor draught conditions will  
result in poor performance.  
The connector may pass through walls or partitions  
constructed of combustible materials provided the  
connector is either listed for wall pass-through or is  
routed through a device listed for a wall pass-  
through and is installed in accordance with the con-  
ditions of the listing.  
Any unexposed metal that is used as part of a wall  
pass-through system and is exposed to flue gases  
shall be constructed of stainless steel or other equiv-  
alent material that will resist corrosion, softening or  
Note: Connection to type “B” Gas Vents, approved  
for connection to a certain gas burning appliance will  
only result in a fire.  
o
cracking from flue gas at temperatures up to 982 C.  
CHIMNEY TYPES - USA ONLY  
CONNECTING TO MASONRY CHIMNEY  
The stove must be connected to a UL 103 Listed  
residential Type HT and Building Heating, Appliance  
chimney installed in accordance with the manufac-  
turers instructions or a masonry chimney  
constructed in accordance with NFPA 211 Chimney  
vents and Solid Fuel Burning Appliances.  
The connector to a masonry chimney must extend  
through the wall to the liner face or liner but not  
beyond, and must be firmly cemented to masonry.  
The connector may pass through walls or partitions  
constructed of combustible material to a masonry  
chimney provided the connector system selected is  
installed in accordance with the proper clearances  
and conditions (See figures A,B,C,D page 8 & 9).  
CHIMNEY TYPES - CANADA ONLY  
The stove must be connected to an Underwriters  
o
Laboratories of Canada labelled Factory Built 650 C  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
Leg  
Ashtray  
Base  
U.S. ENVIRONMENTAL PROTECTION AGENCY  
Certified to Comply with July 1990  
Particulate Emission Standards  
Maximum Heat Output up to 33,000 BTU’s/hr  
Heat Output Range 9,000 - 26,700 BTU’s/hr  
LEPRECHAUN 90 O.S.A.  
WOOD BURNING STOVE  
Base Heat Shield  
Combustion Chamber Base Plate  
Fire Door  
Side Panels  
Inside Fire Door  
Door Latch  
EXPLODED VIEW  
9.  
10.  
11.  
12.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
20.  
21.  
22.  
23.  
24.  
25.  
26.  
27.  
28.  
29.  
30.  
31.  
32.  
33.  
34.  
35.  
36.  
37.  
38.  
39.  
40.  
41.  
42.  
43.  
44.  
Top Side of Top Baffle  
Back Panel  
Back Baffle  
Hob  
Spigot  
Hotplate  
Front Frame  
Back Sealing Plate  
Back Sealing Plate Gasket  
Door Catch  
Window Sealing Tape  
Window Glass  
Fire Fence  
Front Side Brick (2)  
Rear Side Brick (2)  
Bottom Bricks  
Lower Side of Top Baffle  
Air Baffle  
Inside Back Heat Shield  
Door Sealing Rope  
Outside Back Heat Shield  
Spacers  
Optional Pipe Shield  
Heat Shield Blanking Plate  
Tie Bolts  
Top Baffle Plate Gasket  
Back Panel Gasket  
Side Panel Gaskets  
Back Baffle Gasket  
Primary & Secondary Air Spigot  
Primary and Secondary Air Flap  
Cast Iron Spacer  
Connecting Rod  
Primary Air Control Lever  
Primary & Secondary Air Spigot  
Flange  
44  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
THIMBLES  
2.  
Solid insulated listed factory-built chimney  
length of the same inside diameter as the  
chimney connector and having 1” (25mm) or  
more of insulation with a min. 9” (230mm) air  
space between the outer wall of the chimney  
length and combustibles. The inner end of  
the chimney length shall be flush with the  
inside of the masonry chimney flue and shall  
be sealed to the flue and to the brick mason-  
ry penetration with non water-soluble refrac-  
tory cement. Supports should be securely  
fastened to wall supports and the chimney  
length shall not penetrate the chimney liner.  
Thimbles for chimneys or vent connectors should be  
of fire clay (ASTM C 315, specifications for Clay  
Flue Linings), galvanised steel of minimum thick-  
ness of 24 gauge, or material of equivalent durabili-  
ty. Thimbles should be installed without damage at  
the liner. The thimble should extend through the  
wall to, but not beyond, the inner face of the liner  
and should be firmly cemented to masonry.  
Thimbles should be located to provide adequate  
pitch or rise of chimney or vent connectors and,  
where the ceiling above the appliance is constructed  
of combustible material, the location of the thimble  
should provide minimum clearance required for the  
connector as specified in section under Minimum  
Clearances.  
Minimum chimney clearance from masonry to  
sheet steel supports and combustibles 2” (50mm)  
(230mm)  
Non-soluable  
refractory  
cement  
Chimney  
length flush  
with inside  
of flue  
Insulation material used as part of wall pass-through  
system should be of non-combustible material and  
should have a thermal conductivity of 1.0 Btu. in./ft.F  
(4.88 kg.cal/hr.m.c) or less. All clearances and thick-  
nesses are minimums; larger clearances and thick-  
nesses are acceptable. Any material used to close  
up the opening for the connector should be of non-  
combustible material. A connector to a masonry  
chimney, except for System 2 (under heading  
Chimney Connector System, Thimbles and  
Clearances), shall extend to piece through the wall  
pass-through system and the chimney wall to the  
inner face of the flue liner, but not beyond.  
Masonry  
chimney  
constructed to  
NFPA 211  
Factory built chimney length  
Air space 9” (230mm) minimum  
FIGURE B  
3.  
Sheet steel chimney connector, min. 24  
gauge in thickness, with a ventilated thimble,  
min. 24 gauge in thickness, having two 1”  
(25mm) air channels, separated from com-  
bustibles by a min. of 6” (150mm) of glass  
fibre insulation. Opening should be covered  
and thimble supported with a sheet steel  
support, min. 24 gauge in thickness.  
Supports should be securely fastened to  
wall surfaces on all sides and should be  
sized to fit and hold chimney section.  
Fasteners used to secure chimney sections  
should not penetrate chimney flue liner.  
CHIMNEY CONNECTOR SYSTEMS, THIMBLES,  
AND CLEARANCES FROM COMBUSTIBLE  
WALLS  
1.  
Minimum 3 1/2” (90mm) thick brick masonry  
wall framed into combustible wall with a min.  
of 12” (305mm) brick separation from clay  
liner to combustibles. Fire clay liner (ASTM  
C315 or equivalent) min. 5/8” (16mm) wall  
thickness, should run from outer surface of  
brick wall to, but not beyond, the inner sur-  
face of chimney flue liner and should be  
firmly cemented in place.  
Minimum chimney clearance to sheet steel  
supports and combustibles 2” (50mm)  
Two air channels  
each 1” (25mm)  
Chimney  
connector  
Minimum 6” (150mm)  
glass fibre insulation  
Minimum chimney clearance to  
brick and combustibles 2” (50mm)  
Sheet steel  
Two ventilated air  
channels each 1”  
supports  
(25mm) constructed  
of sheet steel  
Minimum clearance 12” (300mm) of brick  
Fire Clay Liner  
FIGURE C  
4.  
Solid insulated listed factory-built chimney  
length with an inside diameter 2” (50mm)  
larger than the chimney connector and hav-  
ing 1” (25mm) or more of insulation, serving  
as a pass-through for a single wall sheet  
steel chimney connector of min. 24 gauge  
thickness, with a min. 2” (50mm) air space  
Chimney connector  
Minimum 12” (300mm)  
to combustibles  
Masonry  
Chimney  
constructed to  
NFPA 211  
FIGURE A  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
between the outer wall of chimney section  
and shall be 12” (305mm). Chimney  
section concentric with and spaced 1”  
(25mm) away from connector by means of  
sheet steel support plates on both ends of  
chimney section. Opening shall be covered  
and chimney section supported on both  
sides with sheet steel supports of min. 24  
gauge thickness.  
other listed chimney connector from the appliances  
flue outlet up through the fireplace damper and  
smoke chamber, terminating at the first flue tile, or  
by installing a stainless steel or other listed relining  
system from the flue outlet up the entire length of the  
chimney, where necessary.  
Supports should be securely fastened to wall sur-  
faces on all sides and shall be sized to fit and hold  
chimney section. Fasteners used to secure chimney  
sections should not penetrate chimney flue liner.  
Minimum chimney clearance  
to sheet steel supports and  
combustibles 2” (50mm)  
Chimney  
Section  
Minimum clearances 2” (50mm)  
1” (25mm) air  
space to  
chimney length  
Air Space 2”  
(50mm)  
In Canada when connecting to a masonry fire place  
the steel chimney connector must terminate at the  
top of the chimney or flue liner.  
Chimney length  
FIGURE D  
MASONRY FIRE PLACE  
The stove maybe installed on the hearth extension  
of a masonry fireplace. In Canada a continuous  
liner must be provided from the flue collar of the  
stove to the top of the chimney. In the USA a con-  
tinuous chimney flue is required. A minimum clear-  
ance of 25” (635mm) is required to combustible  
mantle and a minimum clearance of 14” (355mm) to  
side trim, which extends less than 2” (50mm) from  
the face of the fireplace. (See Section under  
Minimum Clearances to Combustibles).  
Flue Liner  
Stainless Steel  
Chimney Connector  
Insulated non-combustible  
throat seal  
Before the installation the entire fireplace system  
should be inspected for condition and code compli-  
ance prior to connecting to the fireplace chimney.  
Older fireplaces and chimneys may not have been  
constructed to current-day codes.  
VENTILATION & COMBUSTION AIR  
REQUIREMENTS  
The fireplace and chimney should be in, or brought  
up to, acceptable conditions and proper clearances  
should be met before connecting to the fireplace  
chimney.  
Ventilation and an adequate air supply is necessary  
to supply combustion air to the appliance. Refer to  
your local Authority for current requirements in your  
jurisdiction.  
The size of the flue must be considered. If the fire-  
place chimney is too large, a relining system may be  
installed using an approved relining system.  
Outside combustion air may be required if:  
The solid-fuel-fired appliance does not draw  
steadily, smoke rollout occurs, fuels burns  
poorly, or back drafts occur whether or not  
there is combustion present.  
Connection to a masonry chimney may be done by  
breaching into the chimney from the front of the fire-  
place, no less than 8” (200mm) above the bottom of  
the first flue tile, by installing a stainless steel or  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.  
Existing fuel-fired equipment in the house,  
such as fireplaces or other heating appli-  
ances, smell, do not operate properly, suffer  
smoke roll-out when opened, or back-draft  
whether or not there is combustion present.  
Opening a window slightly on a calm  
(windless) day alleviates any of the above  
symptoms.  
The house is equipped with a well-sealed  
vapour barrier and tight fitting windows  
and/or has any powered devices that  
exhaust house air. (e.g. Extraction Hood or  
Tumble Dryers etc..)  
has caught fire adjust the primary air settings  
to suit the heat requirements.  
2.  
3.  
The logs will burn slowly towards the rear of  
the fire chamber and the rate of burning is  
adjustable at all times by means of the pri-  
mary air settings. The more air (wider open  
ing) the faster the burning. Do not overfire  
the stove. If the stove or chimney connector  
glows, you are overfiring the stove.  
When the fire is reduced to embers, open the  
door and carefully rake the embers towards  
the front of the fire chamber and reload with  
logs. After fuelling the stove hold the fire  
door (part number 6) cracked open for 3-5  
minutes to enhance combustion, close the  
fire door (item 6) and adjust the Primary air  
settings to give the required heat output.  
Keep all combustible materials at least three  
feet away from the stove and connector  
pipes. Never dry clothing on or over the  
stove or within three feet of it.  
3.  
4.  
5.  
6.  
There is excessive condensation on win-  
dows in the winter.  
A ventilation system is installed in the house.  
If these or other indications suggest that infiltration  
air is inadequate, additional combustion air should  
be provided from the outdoors. Outside combustion  
air can be provided to the appliance by the following  
means:  
4.  
5.  
6.  
Use the main top of the stove for boiling, sim-  
mering etc. You will soon learn the best  
ways and means of using the stove in order  
to attain maximum efficiency.  
1.  
2.  
Direct connection: Refer to O.S.A. Hook-up  
in this manual.  
Indirect method: for an appliance not  
certified for direct connection of outside  
combustion air, the outside air is ducted to a  
point no closer than (12”) 300mm from the  
appliance, to void affecting the performance  
of the appliance.  
A mechanical ventilation system: if the  
house has a ventilation system (air change  
or heat recovery):  
a. The ventilation system may be able  
to provide sufficient combustion make-up  
air for the solid-fuel-fired appliance.  
b. The householder should be informed that  
the ventilation system might need to be  
re-balanced by a ventilation technician  
after installation of the appliance.  
Disposal of Ashes - Ashes should be  
placed in a metal container with a tight fitting  
lid. The closed container of ashes should be  
placed on a non-combustible floor or on the  
ground, well away from all combustible  
materials, pending final disposal. If the  
ashes are disposed of by burial in soil or oth-  
erwise locally dispersed, there should be  
retained in the closed container until all cin-  
ders have thoroughly cooled.  
3.  
7.  
Creosote - Formation and Need for  
Removal when wood is burned slowly, it pro  
duces tar and other organic vapours, which  
combine with expelled moisture to form cre-  
osote. The creosote vapours condense in  
the relatively cool chimney flue of a slow-  
burning fire. As a result, creosote residue  
accumulates on the flue lining. When ignited  
this creosote makes an extremely hot fire.  
SPILLAGE TEST  
1.  
Light/burn appliance under normal condi-  
tions in accordance with this installation  
manual.  
Close all doors and windows.  
Operate all appliances requiring a full rate  
(eg. extraction hoods, tumble dryers etc).  
Check for spillage.  
The chimney connector and chimney should be  
inspected at least twice monthly during the heating  
season to determine if a creosote build-up has  
occurred. If creosote has accumulated it should be  
removed to reduce the risk of a chimney fire.  
2.  
3.  
4.  
LIGHTING  
1. Lay a few crumpled sheets of paper on the  
Inspect the chimney connector frequently. Tap the  
connector with your finger when the pipe is cool. If  
you hear a dull echo, the pipe may need cleaning.  
Disassemble the chimney connector and clean the  
sections. Replace corroded pipe sections. The fit-  
ting of a slip-joint in the stove pipe makes the dis-  
mantling easy for cleaning and inspection of chim-  
ney and stove.  
hearth, then a few small sticks or kindling to  
get the fire started. Open the fire door and  
light paper. Close the door and open the pri-  
mary air control ALL THE WAY. The fire will  
catch the kindling quickly, after which a full  
size log may be placed on top. After the log  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
When inspecting a masonry chimney, start at the  
cleanout door, normally found in the basement, at  
the base of the chimney, or on the outside. If your  
chimney does not have a clean-out door it must be  
inspected and cleaned by removing stove from  
chimney.  
WARNING: DO NOT CLEAN STOVE WHEN HOT.  
GLASS  
1.  
How to Clean:  
IMPORTANT: NEVER LEAVE THE STOVE  
UNATTENDED WHEN THE FIREDOOR IS IN THE  
CRACKED OPEN POSITION.  
The glass will clean itself when there is sufficient  
heat generated by burning fuel. The Air Way system  
provides pre-heated warm air which keeps the glass  
clean.  
UNDER NO CIRCUMSTANCES SHOULD ANY  
FLAMMABLE LIQUIDS, KEROSENE, GAS OIL  
LINE, NAPHTHA, ENGINE OIL, LIGHTER FLUID  
OR CHARCOAL - STARTERS BE USED TO  
LIGHT OR “FRESHEN UP” THE FIRE. NEVER  
USE MANUFACTURED LOGS. KEEP ALL SUCH  
LIQUIDS WELL AWAY FROM STOVE WHILE IN  
USE  
WARNING: DO NOT OPERATE THE STOVE  
WITH BROKEN GLASS.  
2.  
(a)  
How to Replace:  
Open the door (item 6) and remove the 4  
1/4” (6.4mm) counter sunk screws from the  
inside Fire Door (item 8) and lift it away.  
Remove the broken glass and gasket, take  
the replacement glass and fit gasket.  
(b)  
DO NOT USE GRATE OR ELEVATE FIRE - BUILD  
WOOD FIRE DIRECTLY ON HEARTH.  
DO NOT BURN GARBAGE/RUBBISH IN THIS  
UNIT.  
NOTE: If the gasket is damaged, use a new gasket  
DOOR ASSEMBLY  
PRIMARY AIR SETTINGS  
MAXIMUM - Pull control lever (item 43) all the way  
towards the front.  
LOW (MIN) - Push the control lever (item 43) all the  
way towards the back.  
(c)  
(d)  
Replace the glass and fit the Inside Fire Door  
(item 8). Tighten the 4 fixing screws.  
Close the door to make sure that it is sealing  
properly against the Front Frame (item 16).  
VITREOUS ENAMEL CLEANING  
General cleaning must be carried out when the  
stove is cool.  
FUNCTION DIAGRAM OF LEPRECHAUN 90  
O.S.A. WOOD BURNING STOVE  
If this stove is finished in a high gloss vitreous  
enamel, to keep the enamel in the best condition  
observe the following tips:  
1.  
2.  
Wipe over daily with a soapy damp cloth,  
followed by a polish with a clean dry duster.  
For stubborn deposits a soap impregnated  
pad can be carefully used on the vitreous  
enamel.  
3.  
DO NOT USE ABRASIVE PADS OR OVEN  
CLEANSERS CONTAINING CITRIC ACID  
ON ENAMELLED SURFACES. ENSURE  
THAT THE CLEANSER MANUFACTUR  
ERS INSTRUCTIONS ARE ADHERED TO.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING: USE ONLY CERAMIC GLASS 5mm  
THICK. ABUSE SUCH AS STRIKING, SLAMMING  
AND USE OF SUBSTITUTE MATERIALS  
SHOULD BE AVOIDED.  
3.  
4.  
A practiced evacuation plan.  
A plan to deal with a chimney fire as follows:  
IN THE EVENT OF A CHIMNEY FIRE  
FIRE SAFETY  
(a)  
(b)  
(c)  
(d)  
Notify the fire department.  
Prepare occupants for immediate evacuation  
Close all openings into the stove.  
While awaiting fire department watch for igni-  
tion to adjacent combustibles from over  
heated stove pipe or hot embers or sparks  
from the chimney.  
To provide reasonable fire safety, the following  
should be given serious consideration:  
1.  
2.  
The installation of smoke detectors.  
A conveniently located Class A fire extin-  
guisher to contend with small fires resulting  
from burning embers.  
LEPRECHAUN 90 O.S.A.  
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS:  
SIDE WALL TO STOVE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 INCHES - 510 mm  
BACK WALL TO CHIMNEY CONNECTOR .................................18 INCHES - 460mm  
BACK WALL TO STOVE TOP & REAR EXIT..............................141/2” INCHES - 370mm  
CEILING TO HORIZONTAL CONNECTOR.................................18 INCHES - 460mm  
CORNER......................................................................................13 INCHES - 330mm  
MANTLE CLEARANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25 INCHES - 635mm  
SIDE TRIM ...................................................................................14 INCHES - 355mm  
FLOOR PROTECTION  
When installing this heater on a combustible floor, a floor protector consisting of a layer of non-combustible  
material at least 3/8” thick or 1/4” thick covered with 1/8” sheet of metal is required to cover the area under the  
heater to extend at least 18” at the front and 8” to the sides and back of stove. This will provide protection from  
sparks and ember which may fall out from the door when stoking or refuelling.  
Waterford Stanley Ltd.,  
Bilberry, Waterford, Ireland.  
Tel: 051-302300  
Fax: 051-302375  
Rev: 001: DP030814  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taylor Freezer thick shake freezers User Manual
Teac Clock Radio SLD80R User Manual
TechniSat Flat Panel Television HD VISION 40 PVR User Manual
Telstrat Network Card Argent User Manual
Toastmaster Bread Maker 1170S User Manual
Toastmaster Microwave Oven RRMW1 User Manual
Toshiba Computer Drive HDD2189 User Manual
Transcend Information Computer Drive JetFlash T3 User Manual
Vizio Car Satellite TV System E601i A3 User Manual
Vulcan Hart Tiller ML 114950 User Manual