VINO-1500SSW
VINO-2500SSW
Installer’s Instruction
Federal law requires that WINE-MATE split cooling systems be
installed by an EPA certified refrigeration technician.
WINE-MATE split system is shipped as components and is ready for use only
after a certified refrigeration technician has properly installed, charged and tested
the system. Proper installation is critical. Vinotemp can only warrant the quality of
the components. The installation and proper operation of the system must be
warranted by the installer. Installation of the system must be done in accordance
with all state and local building codes.
The condensing unit and evaporator unit are connected by a liquid line and an
insulated suction line that are supplied by the installer. These lines must be
properly sized for the distance between the two units. After the units and the lines
are installed, the system must be pressure tested. If no leaks are found,
evacuate and charge system with R134A. Refrigerant amount will vary
depending on the length of line set.
1. Condensing Unit
• Place the condensing units WM-150SCU and 250SCU in a properly
ventilated location. If it is not, heat exhausted by the condensing unit will
build up and the cooling system will not operate properly.
• Leave minimum 5 feet clearance for the exhaust side and leave minimum
1 foot clearance for the fresh air intake side.
• Condensing unit shall be elevated to avoid possible flooding and shaded
from direct sun. It shall not be exposed to temperatures higher than 110
°F or lower than 45 °F (optional low ambient kit for 20 °F).
2. Evaporator Unit
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Pressure, Superheat and Subcooling Readings
NOTES: THE VALVES MUST BE IN THE MIDDLE POSITIONS TO READ
PROPERLY.
Complaint
Possible Causes
a. Compressor may be bad
b. Expansion valve opened, too
much oil
a. High suction pressure and low head pressure
b. High suction pressure and low head pressure
Low superheat and low subcooling
c. High suction pressure and high head pressure
Low superheat and high subcooling
c. Overcharge
d. High to normal suction pressure and high head pressure d. Non-condensable gas
Low subcooling
e. High suction pressure and high head pressure
Low subcooling
f. High suction pressure and high head pressure
High superheat
e. Air restricted, dirty condenser,
bad condenser fans
f. High room temperature, high
evaporator load
g. Low suction pressure and low head pressure
High superheat and low subcooling
g. Undercharge
h. Low suction pressure and low to normal head pressure
High superheat and high subcooling
h. Liquid line restricted after
receiver,
restricted
solenoid
valve
i. Low suction pressure and low head pressure
Low subcooling
i. Suction line restricted
j. Low suction pressure and low head pressure
Low superheat and low subcooling
j. Air restricted at evaporator,
evaporator iced
k. Low suction pressure and low to normal head pressure
High superheat and normal to high subcooling
l. Low suction pressure and normal head pressure
High superheat and normal subcooling
k. Evaporator restricted
l. Expansion valve restricted
m. Low suction pressure and high head pressure
High superheat and high subcooling
m. Both evaporator and condenser
restricted
n. Low suction pressure and high head pressure
High superheat and high subcooling
n. Liquid line restricted before
receiver
o. low to normal suction pressure and high head pressure
High to normal superheat and high subcooling
o. Condenser restricted
6. Valve Operation
SPINDLE BACK POSITION SPINDLE FRONT POSITION SPINDLE MIDDLE POSITION
Fig. 2.1 Valve Operation
- 2 -
Download from Www.Somanuals.com. All Manuals Search And Download.
Back Position: Process and manometer port closed for normal operation
Front Position: Main connection to liquid or suction line closed
Middle Position: All ports open for vacuum, charge and measurement
7. Electrical Wiring
Fig. 2.2 VINO1500-2500SSW Wiring Diagram (DIGITAL CONTROLLER)
- 3 -
Download from Www.Somanuals.com. All Manuals Search And Download.
8. Use of the adjustable low pressure control (if applicable)
Cut out = 5 psig; Cut in = 25 psig; Differential = 20 psig
It may need to adjust the setting in the field to get the right cycle time.
Fig. 2.3 Adjustable Pressure Control
9. Condensing Unit Troubleshooting
Unit not running
a. Incorrect power supply
b. Incorrect or loose wirings
c. Failed components
a. Check for proper voltage
b. Check all wirings and connections
c. Check start relay, start capacitor, overload
protector, compressor.
d. Liquid refrigerant in the compressor
d. Call service for OEM information
e. Low pressure switch shutting down the system e. Check for system restriction or low
refrigerant
- 4 -
Download from Www.Somanuals.com. All Manuals Search And Download.
|