Vermont Casting Indoor Fireplace DVHVAC36 User Manual

Rear Direct Vent  
Model: DVHVAC36  
INSTALLER/CONSUMER  
SAFETY INFORMATION  
PLEASE READ THIS MANUAL  
BEFORE INSTALLING AND USING  
APPLIANCE  
WARNING!  
IF THE INFORMATION IN THIS  
MANUAL IS NOT FOLLOWED  
EXACTLY, A FIRE OR EXPLOSION  
MAY RESULT CAUSING PROPERTY  
DAMAGE, PERSONAL INJURY OR  
LOSS OF LIFE.  
FOR YOUR SAFETY  
Installation and service must be  
performed by a qualified installer,  
service agency or the gas supplier.  
WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not touch any electric switch; do  
not use any phone in your  
Homeowner's Installation  
and Operating Manual  
building.  
Immediately call your gas supplier  
from your neighbor's phone. Follow  
the gas suppliers instructions.  
S
G
N
E
D
If you cannot reach your gas supplier  
call the fire department.  
CERTIFIED  
C
E
D
R
E
I
T
I
F
DO NOT STORE OR USE  
GASOLINE OR OTHER  
FLAMMABLE VAPORS AND  
LIQUIDS IN THE VICINITY OF THIS  
OR ANY OTHER APPLIANCE.  
INSTALLER: Leave this manual with the appliance.  
CONSUMER: Retain this manual for future reference.  
10001195 1/07 Rev. 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Installation & Operating Instructions  
12. This fireplace requires adequate ventilation and  
This gas fireplace should be installed by a qualified  
combustion air to operate properly.  
13. The unit must be adjusted to obtain a temperature  
rise of 25-55°F, at maximum input rate.  
installer in accordance with local building codes and with  
current CSA-B149.1 Installation codes for Gas Burning  
Fireplaces and Equipment. For U.S.A Installations follow  
local codes and/or the current National Fuel Gas Code.  
ANSI Z223.1/NFPA 54.  
14. The fireplace must be electrically grounded in  
accordance with local codes. In the United States,  
all electrical and grounding must also conform to the  
current National Electric Code, ANSI/NFPA No. 70. In  
Canada, all electrical and grounding for the unit must  
also conform to the current Canadian Electrical Code  
Part 1, CSA Standard C22.1  
15. Field wiring to the appliance must meet or exceed  
the specifications for type T wire and must withstand a  
minimum of 180°F temperature rise.  
In the Commonwealth of Massachusetts, all gas fitting  
and installation of this heater shall only be done by a  
licensed gas fitter or licensed plumber.  
FOR SAFE INSTALLATION AND OPERATION PLEASE  
NOTE THE FOLLOWING:  
1. This fireplace gives off high temperatures and should  
be located out of high traffic areas and away from  
furniture and draperies.  
2. Children and adults should be alerted to the hazards  
of the high surface temperatures of this fireplace and  
should stay away to avoid burns or ignition of clothing.  
3. Children should be carefully supervised when they are  
in the same room as your fireplace.  
4. Under no circumstances should this fireplace be modi-  
fied. Parts removed for servicing should be replaced  
prior to operating this fireplace again.  
5. Installation and any repairs to this fireplace should  
be carried out by a qualified service person. A profes-  
sional service person should be contacted to inspect  
this fireplace annually. Make it a practice to have all of  
your gas fireplaces checked annually. More frequent  
cleaning may be required due to excess lint and dust  
from carpeting, bedding material, etc.  
6. Control compartments, burners and air passages in  
this fireplace should be kept clean and free of dust  
and lint. Make sure that the gas valve and pilot light  
are turned off before you attempt to clean this fire-  
place.  
7. The venting system (chimney) of this fireplace should  
be checked at least once a year and if needed your  
venting system should be cleaned.  
8. Keep the area around your fireplace clear of combusti-  
ble materials, gasoline and other flammable vapor and  
liquids. This fireplace should not be used as a drying  
rack for clothing, nor should Christmas stockings or  
decorations be hung in the area of it.  
9. Under no circumstances should any solid fuels (wood,  
coal, paper or cardboard etc.) be used in this fire-  
place.  
16. Service access must be provided for the service and  
replacement of the blower motor, air filter etc. The use  
of CFM Corporation mantels designed for this product  
is recommended.  
IMPORTANT:  
PLEASE REVIEW THE FOLLOWING CAREFULLY  
Itisnormalforreplacesfabricatedofsteeltogiveoff  
someexpansionand/orcontractionnoisesduringthe  
start up or cool down cycle. Similar noises are found  
with your furnace heat exchanger or car engine.  
It is not unusual for your CFM Corporation gas  
fireplace to give off some odor the first time it is  
burned. This is due to the curing of the paint and any  
undetected oil from the manufacturing process.  
Pleaseensurethatyourroomiswellventilated-open  
all windows.  
It is recommended that you burn your fireplace for at  
least ten (10) hours the first time you use it.  
The appliance may be installed in an aftermarket  
permanently located, manufactured (mobile) home,  
where not prohibited by local codes.  
This appliance is only for use with the type of gas  
indicated on the rating plate. This appliance is not  
convertible for use with other gases unless a certi-  
fied kit is used.  
Proposition 65 Warning: Fuels used in gas, wood-  
burning or oil fired appliances, and the products of  
combustion of such fuels, contain chemicals known to  
the State of California to cause cancer, birth defects  
and other reproductive harm.  
10. The flow of combustion and ventilation air must not  
be obstructed in any way.  
California Health & Safety Code Sec. 25249.6  
11. Whether the fireplace is installed directly on  
carpeting, vinyl tile or any combustible material other  
than wood, this fireplace must be installed on a metal  
or wood panel extending the full width and depth of  
the fireplace.  
10001195  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Fireplace Dimensions  
U
L
V
Z
G
V
H
W
F
E
T
X
I
K
B
C
J
P
Q
R
O
N
D
A
M
L
Fig. 2 Fireplace specifications.  
Ref.  
A
B
C
D
E
DVHVAC36  
36" (914 mm)  
34¹⁄₄" (870 mm)  
Ref.  
N
O
P
Q
R
S
T
U
V
DVHVAC36  
9⁵⁄₈"  
6⁷⁄₈"  
2⁹⁄₃₂"  
2"  
(245 mm)  
(175 mm)  
(58 mm)  
(51 mm)  
21"  
33"  
(533 mm)  
(838 mm)  
63⁵¹⁄₆₄" (1621 mm)  
70" (1780 mm)  
3¹³⁄₁₆" (97 mm)  
F
4"  
1/2"  
18"  
(102 mm)  
(13 mm)  
(457 mm)  
G
H
I
J
K
16⁵⁄₃₂" (410 mm)  
21⁵⁄₃₂" (537 mm)  
38³⁄₁₆" (970 mm)  
28¹⁵⁄₁₆" (735 mm)  
33¹⁄₂" (851 mm)  
18³⁄₁₆" (462 mm)  
13²¹⁄₃₂" (347 mm)  
16⁷⁄₂₁" (412 mm)  
83¹⁄₈" (2111 mm)  
W
X
Y
5³⁄₈"  
(136 mm)  
L
M
58³⁄₄" (1493 mm)  
41⁹⁄₁₆" (1056 mm)  
Z
4
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
5. Attach the metal conduit from the fireplace cabinet  
to the 7/8" diameter hole in the side of the air cir-  
culating blower section using the nut provided. Do  
not feed the two yellow wires which are outside the  
conduit through the hole. Insert the terminal on the  
white wire (common) into position 1 on the jack plug.  
Insert the terminal on the black wire (cooling speed)  
into position 2 on the jack plug. Insert the terminal on  
the red wire (heating speed), into position 3, 4 or 5  
on the jack plug. If unsure, select position 4 on the  
jack plug for heating speed and adjust if necessary.  
If desired the speed selections can be changed later.  
Refer to Figure 8 Wiring Diagram.  
Locating Your Gas Fireplace  
B
E
A
Y
C
X
Y
D
X
F
WARNING: Ensure that all three wires are properly  
inserted into jack plug, even if an optional air condi-  
tioner is not to be used.  
LU584-3  
6. Reinstall jack plug into motor and replace access  
panel.  
Fig. 1 Locate gas fireplace.  
A) Flat on wall  
D) *Room divider  
Y) 6" minimum  
B) Cross corner  
E) *Flat on wall corner F) Chase installation  
C) **Island  
7. Place the coil cabinet section onto the right side of  
the fireplace cabinet so the access panel faces the  
front of the unit. (Fig. 3) Remove the access panel  
and secure the coil cabinet to the fireplace cabinet  
using 8 of the #8 screws provided.  
NOTE (Fig. 1):  
** Island (C) and Room Divider (D) installation is possible as  
long as the horizontal portion of the vent system (X) does not  
exceed 20' (6m). See details in Venting Section.  
* When you install your CFM Corporation fireplace in (D) Room  
divider or (E) Flat on wall corner positions (Y), a minimum of 6"  
(153mm) clearance must be maintained from the perpendicular  
wall and the front of the fireplace.  
8. Connect the 1/4" quick connect terminals of the two  
yellow wires from the fireplace cabinet to the high  
limit safety control located on the top of the coil cabi-  
net.  
Clearance to Combustibles  
Blower Section  
Coil Cabinet  
Back.............................................................. 0" (0 mm)  
Side............................................................... 0" (0 mm)  
Floor.............................................................. 0" (0 mm)  
Top................................................................ 0" (0 mm)  
Flue...................................................... 2" (51 mm) Top  
..............................................1" (25 mm) Sides/Bottom  
Unit Assembly  
The DVHVAC36 is shipped in three cartons. The first  
carton contains the fireplace cabinet. The second car-  
ton contains the air circulating blower section and the  
third carton contains the coil cabinet. Unpack all three  
sections before following the assembly instructions:  
Fireplace Cabinet  
1. Place the air circulating blower section onto the left  
side of the fireplace cabinet. (Fig. 3)  
2. Ensure the damper plate below the blower assembly  
works freely without binding. Rotate it downwards  
and ensure that it returns to a closed position.  
3. Secure air circulating blower section to fireplace  
cabinet using 8 of the #8 screws provided.  
FP1399  
Fig. 3 DVHVAC36 unit assembly.  
4. Remove the access panel on the front of the air cir-  
culating blower section by removing the #10-24 nuts.  
Remove the jack plug from the air circulating blower  
motor by gently depressing tab.  
10001195  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Framing and Finishing  
Mantel  
1. Choose fireplace location.  
2. Place fireplace into position and secure to floor with  
D
1¹⁄₂" screws, or nails. The holes to secure the fire-  
place to the floor are located just behind the access  
door grille on the left and right hand side of the  
fireplace.  
C
Adjustable Drywall Strip  
B
(Nailing Flange)  
A
B
Screw  
Position  
Drywall  
Depth  
A
C
A
B
C
1/2" (13 mm)  
5/8" (16 mm)  
3/4" (19 mm)  
Top Louvre Opening  
Side View  
Front Glass  
Electrical  
Knock-  
Out  
Optional Hearth  
Adjustable  
1/2", 5/8" &  
3/4" Spacing  
Gas Knock-Out  
Electrical Cable  
Knock-Out  
FP1023  
FP1400  
Fig. 4 Adjustable drywall strip (nailing flange).  
Mantel Chart  
3. Frame in fireplace. It is important to allow for finished  
face when setting the depth of the frame.  
Ref.  
From Top  
Ref.  
Depth  
(Max.)  
7" (178 mm)  
any  
Louvre (Min.)  
15¹⁄₅" (394 mm)  
48" (1219 mm)  
4. Attach fireplace to frame using adjustable frame  
drywall strips (located behind access door for ship-  
ping). Preset depth to suit facing material (adjustable  
to 1/2", 5/8" or 3/4" depths). (Fig. 4)  
A
B
C
D
Mantel Leg Chart  
From Fireplace  
5. Screw through slotted holes in drywall strip and then  
screw into pre-drilled holes on fireplace side. Meas-  
ure from face of fireplace to face of drywall strip to  
determine final depth. (Fig. 4)  
Depth  
(Max.)  
Side (Min.)  
7¹⁄₂" (191 mm)  
1³⁄₄" (44 mm)  
Fig. 5 Combustible mantel installation.  
Supply Air Duct Systems  
Return Air Plenum  
The DVHVAC36 fireplace has three 6" (152 mm) diam-  
eter supply air outlets. Duct runs of up to 65 equivalent  
feet (19.8 m) using 6" (152 mm) round duct (or equiva-  
lent), are permissible. Duct runs of up to 40 equivalent  
feet (12.2 m) are permitted using 5" (127 mm) round  
duct (or equivalent). Runs of up to 30 equivalent feet  
(9 m) are permitted when using 4" (102 mm) round duct  
(or equivalent). In all cases, size and install the supply  
air system using industry approved standards which  
result in a quiet and low static system.  
The DVHVAC36 is equipped with a 16" x 16" (256 x  
256 mm) return air duct connection. Size and install the  
return air system using industry approved standards  
that result in a quiet and low static system.  
Air Conditioning  
The coil cabinet has been sized to fit most major brands  
of evaporator coil. (Fig. 6) The brackets supplied inside  
the coil cabinet represent the lowest height above the  
fireplace cabinet that the coil may be mounted. For best  
results, it is recommended that low air restriction types  
6
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
of coils be used with this product. When using 4" or 5"  
(102 or 127 mm) diameter duct work, the maximum air  
conditioning system size should be limited to 1.5 tons  
(18,000 BtuH). When using 6" (152 mm) diameter duct,  
air conditioners of up to 2 tons (24,000 BtuH) may be  
used. Total static pressure of the system above the out-  
let from the fireplace cabinet should not exceed 0.40"  
w.c. with the air circulating blower on high speed, when  
using the maximum air conditioning capacity.  
DVHVAC36  
Certified to  
ANSI Z21.88-2005 / CSA 2.33-2005  
Vented Gas Fireplace Heaters  
Unit: B12AC0, B12BC0  
Do not use this fireplace if any part of it  
has been under water. Immediately call a  
qualified service technician to inspect the  
fireplace and replace any part of the control  
which has been under water.  
Two rails come factory mounted in the coil cabinet.  
These represent the minimum clearance between the  
evaporator coil and the fireplace cabinet top. Do not  
mount an evaporator coil below the level of the rails.  
Gas Inlet & Manifold Pressures  
Supply Pressure  
Minimum  
Maximum  
Natural  
5.5" w.c.  
14.0" w.c.  
3.5" w.c.  
LP (Propane)  
11.0" w.c.  
14.0" w.c.  
Final Finishing  
Noncombustible materials such as brick and tile can  
be extended over the front face of the unit (Do not  
cover louvres or glass door). If a trim kit is going to  
be installed, brick and tile will have to be installed flush  
with the side of this appliance.  
Manifold Pressure  
10.0" w.c.  
High Elevations  
Input ratings are shown in BTU per hour and are  
certified without deration for elevations up to  
4,500 feet (1,370 m) above sea level.  
Hearth  
A hearth is not mandatory, however it is recommended  
for aesthetic purposes. We recommend a noncombus-  
tible hearth which projects out 12" (305 mm) or more in  
front of this unit.  
For elevations above 4,500 feet (1,370 m) in USA,  
installations must be in accordance with the  
current ANSI Z223.1/NFPA 54 and/or local codes  
having jurisdiction.  
Cold climate installation recommendation:  
When installing this unit against a non-  
insulated exterior wall or chase, it is  
mandatory the outer walls be insulated to  
conform to applicable insulation codes.  
In Canada, please consult provincial and/or local  
authorities having jurisdiction for installations at  
elevations above 4,500 feet (1,370 m).  
Gas Specifications  
Max.  
Input  
Min.  
Input  
Model  
Fuel  
Gas Control BTUH BTUH  
E
DVHVAC36RN Natural Gas Millivolt HI/LO  
DVHVAC36RP Propane Gas Millivolt HI/LO  
40,000 25,000  
40,000 25,000  
D
Gas Line Installation  
When purging gas line, the front glass  
must be removed.  
C
The gas pipeline can be brought in through the right  
side or left side of the appliance as well as the bottom.  
Knockouts are provided at convenient locations to allow  
for the gas pipe installation and testing of any gas con-  
nection.  
A
Rails  
B
FP1401  
Ref.  
A
B
Dimension  
21" (534 mm)  
17⁷⁄₁₇" (443 mm)  
3⁷⁄₁₆" (88 mm)  
The gas line connection can be made with properly  
tinned 3/8" copper tubing, 3/8" rigid pipe or an approved  
flex connector.  
C
Always check for gas leaks with a mild  
soap and water solution. Do not use an  
open flame for leak testing.  
D
E
20⁷⁄₁₆" (519 mm)  
8¹⁄₂" (217 mm)  
Fig. 6 Coil cabinet dimensions.  
10001195  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
The gas control is equipped with a captured screw type  
pressure test point, therefore it is not necessary to pro-  
vide a 1/8" test point up stream of the control.  
1/2" Gas Supply  
1/2" NPT x 1/2" Flare  
Shut-off Valve  
When using copper or flex connector use only approved  
fittings. When using black iron pipe always provide a  
union so the gas line can be easily disconnected for  
burner or fan servicing. (Fig. 7) Refer to gas specifica-  
tions for pressure details and ratings.  
3/8" Flex Line  
(From Valve)  
The fireplace valve must not be subjected to any test  
pressures exceeding 1/2 psi. Isolate or disconnect this  
or any other gas appliance control from the gas line  
when pressure testing.  
FP297a  
Fig. 7 Typical gas supply installation.  
Electrical Specifications  
120V AC  
60Hz  
Less than 12 Amps  
1/3 Horsepower  
8
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Electrical  
Refer to Figure 8 for field wiring.  
5. Electrically ground the unit in accordance with  
local codes, or in the absence of local codes in  
accordance with the Canadian Electrical Code, Part  
1 (CSA Standard C22.1) in Canada, or with the  
National Electric Code (ANSI/NFPA No. 70) in the  
United States.  
1. Select fuse and wire size according to rating plate  
amperage.  
2. Install a separate fused disconnect switch near the  
unit for service purposes.  
3. Knockouts are provided on both sides of cabinet for  
electrical wiring.  
6. The circuit board is equipped with two (2) accessory  
terminals. The terminal marked "Air Cleaner" and  
"Humidifier" are rated for 120V 0.5 Amps and are  
energized with the air circulating blower. Connect the  
neutral leg of the accessory to the 120V neutral wire.  
4. Install room thermostat (24 volt) according to  
instructions provided with thermostat, using 18  
gauge wire or larger.  
EMERGENCY  
HEAT  
SWITCH  
GAS VALVE  
TP/TH  
TP  
TH  
FLAME  
ADJUST  
RED  
WHITE  
13 BLUE  
ACB  
12 YELLOW  
16 YELLOW  
LIMIT  
17 GREEN  
10 BLUE  
1
2
3
4
5
6
11 GREEN  
4
5
1
HUMIDIFIER  
ACB HEAT  
R
4 RED  
2 RED  
W1  
5 WHITE  
18 GRAY  
3 BLACK  
G
Y
ACB COOL  
AIR CLEANER  
19 YELLOW  
20 GREEN  
GND  
XFORMER  
1
3
9 YELLOW  
110 VAC HOT  
6 BLACK  
7 WHITE  
1 WHITE  
8 BLUE  
8 BLUE  
110 VAC HOT  
110 VAC RTN  
L1  
L2  
GREEN  
FP1413  
Fig. 8 DVHVAC36 wiring diagram.  
General Venting  
This model is approved to be vented either through the  
side wall, or vertically through the roof.  
24" (610 mm) from the front of the termination hood.  
Do not locate termination hood where excessive snow  
or ice build up may occur. Be sure to check vent termi-  
nation area after snow falls, and clear to prevent ac-  
cidental blockage of venting system. When using snow  
blowers, make sure snow is not directed towards vent  
termination area.  
Only venting components specifically approved and  
labelled for this fireplace may be used.  
Minimum clearances between vent pipes and com-  
bustible materials is 1" (25 mm).  
Venting terminals shall not be recessed into a wall or  
siding.  
Location of Vent Termination  
It is imperative that the vent termination be located ob-  
serving the minimum clearances as shown on Page 10.  
Horizontal venting must be installed on a level plane  
without an inclining or declining slope.  
*Check with local codes or in absence of same with  
CSA B149.1 Installation Codes (1991) for Canada or for  
U.S.A. Installations follow the current National Fuel Gas  
There must not be any obstruction such as bushes,  
garden sheds, fences, decks or utility buildings within  
Code, ANSI Z223.1/NFPA 54.  
9
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
General Venting Information - Termination Location  
INSIDE  
CORNER DETAIL  
G
V
N
H
N
A
D
E
B
V
L
C
B
B
 
�  
V
V
B
Fixed  
Closed  
V
V
Operable  
Operable  
F
B
M
V
A
X
J
B
I
K
X
V
CFM145a  
AREA WHERE TERMINAL IS NOT PERMITTED  
VENT TERMINATION  
X
AIR SUPPLY INLET  
V
Canadian Installations1  
US Installations2  
A = Clearance above grade, veranda, porch,  
deck, or balcony  
12” (30cm)  
12” (30cm)  
B = Clearance to window or door that may be  
opened  
6” (15cm) for appliances  
< 10,000Btuh (3kW), 12” (30cm)  
for appliances > 10,000 Btuh (3kW) and  
< 100,000 Btuh (30kW), 36” (91cm)  
for appliances > 100,000 Btuh (30kW)  
6” (15cm) for appliances  
< 10,000 Btuh (3kW), 9”  
(23cm) for appliances > 10,000  
Btuh (3kW) and < 50,000 Btuh  
(15kW), 12” (30cm) for  
appliances > 50,000 Btuh (15kW)  
C = Clearance to permanently closed window  
12” (305mm) recommended to  
prevent window condensation  
12” (305mm) recommended to  
prevent window condensation  
D = Vertical clearance to ventilated soffit located  
above the terminal within a horizontal  
distance of 2 feet (610mm) from the center  
line of the terminal  
18” (458mm)  
18” (458mm)  
E = Clearance to unventilated soffit  
F = Clearance to outside corner  
G = Clearance to inside corner (see next page)  
12” (305mm)  
see next page  
see next page  
12” (305mm)  
see next page  
see next page  
H = Clearance to each inside of center line  
extended above meter/regulator assembly  
3’ (91cm) within a height of 15’  
above the meter/regulator assembly  
3’ (91cm) within a height of 15’  
above the meter/regulator assy  
I = Clearance to service regulator vent outlet  
3’ (91cm)  
3’ (91cm)  
J = Clearance to nonmechanical air supply inlet 6” (15cm) for appliances < 10,000  
to building or the combustion air inlet to any Btuh (3kW), 12” (30cm) for  
6” (15cm) for appliances  
< 10,000 Btuh (3kW), 9”  
(23cm) for appliances > 10,000  
Btuh (3kW) and < 50,000 Btuh  
(15kW), 12” (30cm) for  
other appliances  
appliances > 10,000 Btuh (3kW) and <  
100,000 Btuh (30kW), 36” (91cm)  
for appliances > 100,000 Btuh (30kW)  
appliances > 50,000 Btuh (15kW)  
K = Clearance to a mechanical air supply inlet  
6’ (1.83m)  
3’ (91cm) above if within 10’  
(3m) horizontally  
L = Clearance above paved sidewalk or paved 7’ (2.13m)†  
driveway located on public property  
7’ (2.13m)†  
M = Clearance under veranda, porch, deck or  
balcony  
12” (30cm)‡  
12” (30cm)‡  
N = Clearance above a roof shall extend a minimum of 24” (610mm) above the highest point when it passes through the roof  
surface, and any other obstruction within a horizontal distance of 18” (450mm).  
1 In accordance with the current CSA-B149 Installation Codes  
2 In accordance with the current ANSI Z223.1/NFPA 54 National Fuel Gas Codes  
† A vent shall not terminate directly above a sidewalk or paved driveway which is located between two single family dwellings and serves  
both dwellings  
‡ only permitted if veranda, porch, deck or balcony is fully open on a minimum 2 sides beneath the floor:  
NOTE: 1. Local codes or regulations may require different clearances.  
2. The special venting system used on Direct Vent fireplaces are certified as part of the appliance, with clearances tested and app-  
roved by the listing agency.  
3. CFM Corporation assumes no responsibility for the improper performance of the appliance when the venting system does not  
meet these requirements.  
Fig. 9 Termination clearances.  
10  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Termination Clearances  
Termination clearances for buildings with combustible and noncombustible exteriors.  
Inside Corner  
Alcove Applications*  
Outside Corner  
D
C
C
F =  
Combustible  
6" (152 mm)  
G =  
Combustible  
6" (152 mm)  
V
G
V
Noncombustible  
2" (51 mm)  
V
E
Noncombustible  
2" (51 mm)  
O
F
Balcony -  
with no side wall  
Balcony -  
with perpendicular side wall  
E = Min. 6” (152 mm) for  
non-vinyl sidewalls  
Min. 12” (305 mm) for  
vinyl sidewalls  
O = 8’ (2.4 m) Min.  
M
No.  
of Caps  
M
V
DMin.  
CMax.  
V
1
2
3
4
3’ (.9 mm) 2 x DActual  
6’ (1.8 m) 1 x DActual  
9’ (2.7 m) 2/3 x DActual  
12’ (3.7 m) 1/2 x DActual  
P
Combustible &  
Noncombustible  
M =  
Combustible &  
Noncombustible  
12" (305 mm)  
M = 24" (610 mm)  
P = 20” (508 mm)  
DMin. = # of Termination caps x 3  
CMax. = (2 / # termination caps) x DActual  
584-15  
*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions  
specified for vinyl or non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All  
mechanical air intakes within 10’ (1 m) of a termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All  
gravity air intakes within 3’ (914 mm) of a termination cap must be a minimum of 1’ (305 mm) below the termination cap.  
Fig. 10 Termination clearances.  
General Information Assembling Vent Pipes  
Canadian Installations:  
To join the twist lock pipes together, simply align the  
beads of the male end with the grooves of the female  
end, then while bringing the pipe together, twist the pipe  
until the flange on the female end contacts the external  
flange on the male end. It is recommended that you  
secure the joints with three (3) sheet metal screws,  
however this is not mandatory with twist lock pipe. (Fig.  
11)  
Venting system must be installed in accordance with the  
current CSA-B149.1 installation code.  
USA Installations:  
The venting system must conform with local codes and/  
or the current National Fuel Gas code ANSI Z223.1/  
NFPA 54.  
Only venting components manufactured by CFM Corpo-  
ration can be used in Direct Vent systems.  
To make it easier to assemble the joints we suggest  
putting a lubricant (Vaseline or similar) on the male end  
of the twist lock pipe prior to assembly.  
Twist Lock Pipes  
Male End  
Female End  
When using CFM Corporation twist-lock pipe it is not  
necessary to use sealant on the joints. The only areas  
of the venting system that need to be sealed with high  
temperature silicone sealant are the collars on the  
fireplace and termination, and the sliding joint of any  
telescopic vent section used in the system.  
Screw Holes  
TWL100  
Fig. 11 Twist-lock pipe joints.  
10001195  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
How to Use the Vent Graph  
Corner Installation  
1. Determine the height of the center of the horizontal  
vent pipe exiting through the outer wall. Using this  
dimension on the Sidewall Vent Graph (Fig. 12),  
locate the point it intersects with the slanted graph  
line.  
When the DVHVAC36 unit is installed in a corner,  
Figure 1, Option B, the vent configuration must fol-  
low the Vertical Sidewall Installation Instructions.  
Rear Wall Venting Applications  
2. From the point of this intersection, draw a vertical  
line to the bottom of the graph.  
This appliance may be vented directly to a termination  
located on the rear wall behind the appliance.  
3. Select the indicated dimension, and position the fire-  
place in accordance with same. (Refer to examples  
Fig. 12)  
NOTE: It is not necessary to seal the vent pipe joints for  
any rear vent applications.  
Only CFM Corporation venting components are  
approved to be used in these applications. Refer to  
“Venting Components” listed for different installation  
requirements.  
EXAMPLE A:  
If the vertical dimension from the floor of the unit is 11'  
(3.4m) the horizontal run to the face of the outer wall  
must not exceed 14' (4.3 m).  
The maximum horizontal distance between the rear  
of the appliance and the outside face of the rear wall  
is 20” (508 mm). (Fig. 13)  
EXAMPLE B:  
If the vertical dimension from the floor of the unit is 7'  
(2m), the horizontal run to the face of the outer wall  
must not exceed 8¹⁄₂' (2.6 m).  
Minimum clearances between vent pipe and com-  
bustible materials are as follows:  
Sidewall Venting Graph  
Top - 2” (51 mm)  
Sides - 1” (25 mm)  
Bottom - 1” (25 mm)  
(Dimensions in Feet)  
30  
29  
28  
27  
26  
25  
24  
23  
22  
21  
20  
19  
18  
17  
16  
15  
14  
13  
20"  
(508mm)  
FP1403  
Fig. 13 Rear vent application.  
Rear Wall Installations  
STEP 1  
12  
Locate vent opening on wall. To locate hole center, refer  
to appropriate fireplace dimensions on Page 4.  
eg: A  
11  
10  
9
Combustible Walls (Fig. 14): Cut a 10³⁄₈" x 9³⁄₈" (265 x  
240 mm) hole through the exterior wall and frame as  
shown.  
8
7
eg: B  
6
5
4
3
Noncombustible Walls (Fig. 14): Hole opening must be  
7¹⁄₂" (191 mm) in diameter.  
STEP 2  
Measure wall thickness and cut adjustable zero clear-  
ance sleeve parts to proper length (MAXIMUM 12" /  
305 mm). Adjust sleeve to maximum (10³⁄₈" x 9³⁄₈" / 265  
x 240 mm) and attach to firestop with #8 sheet metal  
screws (supplied). (Fig. 15) Install firestop assembly.  
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20  
Horizontal dimension from the outside face of the wall  
to the center of the fireplace vent flange  
Fig. 12 Sidewall venting graph. (Dimensions in feet)  
12  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
STEP 4  
Vent Opening for Combustible Wall  
Slip 4" (102 mm) and 7" (178 mm) pipes onto respec-  
tive flue collars. Make sure to fix to the fireplace collar  
the 4" pipe with three (3) screws before fixing the 7"  
pipe on the 7" collar. Both pipes must be on a level  
plane. (Fig. 17)  
9³⁄₈"  
(240 mm)  
Framing  
Detail  
10³⁄₈"  
(265 mm)  
STEP 5  
Guide the vent termination 4" collar into the 4" pipe then  
the 7" collar into the 7" pipe. Do not force the venting  
into position. If the pipes do not line up with the termina-  
tion collars, disassemble elbows or pipes and reattach  
to the fireplace collar.  
Fireplace  
Hearth  
Vent Opening for Noncombustible Wall  
STEP 6  
Recheck the fireplace to make sure it is levelled, prop-  
erly positioned and nailed or screwed to the floor.  
7¹⁄₂"  
(190 mm)  
If applied, the fireplace adjustable frame drywall strips  
(nailing flanges) should be fastened. Refer to Framing  
and Finishing.  
VO584-100  
Fig. 14 Locate vent opening on wall.  
Adjustable  
Zero Clearance  
Sleeve  
Max. Length  
12" (305 mm)  
Finished  
Wall  
#8 Screws  
(2)  
Vent Termi-  
nation  
#8  
Screws  
(2)  
#8 Screws (2)  
Firestop  
Adjustable Zero Clearance Sleeve  
ZCS101  
FP1005  
Fig. 15 Adjustable zero clearance sleeve.  
Fig. 17 Side view of final unit location.  
STEP 3  
Vertical Sidewall Applications  
Measure from fireplace collar face to face of outside  
wall (add 2" (51 mm) for vent pipe overlap). Mark pipes  
and cut to length. It is very important that the two pipes  
are flush with the outside wall once the fireplace is in its  
final location. (Fig. 16)  
Since it is very important that the vent-  
ing system maintain its balance between  
the combustion air intake and the flue  
gas exhaust, certain limitations as to vent  
configurations apply and must be strictly  
adhered to.  
Zero Clearance Sleeve  
The graph showing the relationship between vertical  
and horizontal side wall venting will help to determine  
the various vent lengths allowable. (Fig. 12)  
Minimum clearance between vent pipes  
and combustible materials is 1" (25 mm)  
on top, bottom and sides unless otherwise  
noted.  
Firestop  
FP1404  
When vent termination exits through foundation less  
than 20" (508 mm) below siding outcrop, the vent pipe  
must flush up with the siding. A 7DVSS must also be  
used.  
Fig. 16 Firestop and zero clearance sleeve in place.  
10001195  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
It is always best to locate the fireplace in such a way  
that minimizes the number of offsets and horizontal vent  
length.  
Example: According to the vent chart the maximum  
horizontal vent length is 20' (6 m) when the vertical  
height is 7.5' (2.3 m) from fireplace base height. If  
one (1) 90° elbow is required in the horizontal vent, it  
must be reduced to 17' (5.2 m).  
The horizontal vent run refers to the total length of vent  
pipe from the flue collar of the fireplace to the face of  
the outer wall.  
The maximum number of elbow degrees in a sys-  
tem is 270°. (This does not include transition elbow  
from rear vent to vertical vent.) (Fig. 21)  
Horizontal plane means no vertical rise exists on this  
portion of the vent assembly.  
For some installations, it may be desirable to have  
some amount of the horizontal vent run immediately  
after the fireplace. A vertical rise must be used but can  
be located anywhere in the vent system, to meet the  
parameters identified in the venting graph.  
Maximum  
3' (914mm)  
The maximum horizontal vent run is 20' (6 m) when  
the vertical vent rise is 7¹⁄₂' (2.3 m). (Fig. 18)  
Maximum  
20 ft. (6.1m)  
Vertical Dimen-  
sion 7¹⁄₂' (2.3m)  
48"  
(1.2m)  
Minimum when  
Horizontal Run is  
20' (6m)  
12"  
(305mm)  
7TDVRT90  
Elbow  
15 ft.  
(4.6m)  
CFM142  
Fig. 19 Maximum horizontal vent run with 90° elbows directly  
off back of unit.  
B
7'  
(2.1m)  
7.5'  
(2.3m)  
A
10'  
(3m)  
7TDVRT90  
Elbow  
CFM141  
7' 6"  
(2.3m)  
A + B = 17' (5.2m) Max.  
Fig. 18 Maximum number of 90° elbows is three.  
The maximum number of 90° elbows per side wall  
installation is three (3).  
The maximum number of 45° elbows permitted per  
side wall installation is two (2). These elbows can be  
installed in either the vertical or horizontal run.  
CFM147  
Fig. 20 Maximum vent run with elbows.  
When one (1) 90° elbow is installed directly onto  
another off the back of the fireplace the maximum  
horizontal vent length is 36" (914 mm). (Fig. 19)  
Sample:  
4
Elbow 1  
Elbow 2  
Elbow 3  
Elbow 4  
=
=
=
=
90°  
45°  
45°  
90°  
For each 45° elbow installed in the horizontal run  
(while maintaining a constant horizontal plane), the  
length of the horizontal run MUST be reduced by 18"  
(457 mm). This does not apply if the 45° elbows are  
installed on the vertical part of the vent system.  
Total angular variation = 270°  
1 + 2 + 3 + 4 = 270o  
3
2
If a 90° elbow is used in the horizontal vent run  
(level height maintained) the maximum horizontal  
vent length is reduced by 36" (914 mm) (Fig. 20)  
This does not apply if the 90° elbows are used to  
increase or redirect a vertical rise.  
1
CFM132  
Fig. 21 Maximum number of elbows.  
14  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
STEP 2  
IMPORTANT Minimum clearance between vent  
pipes and combustible materials is 1" (25mm) on bot-  
tom, sides and top.  
Measure wall thickness and cut adjustable zero clear-  
ance sleeve parts to proper length (MAXIMUM 12" /  
305mm). (Fig. 23) Adjust sleeve to minimum (9³⁄₈" x 9³⁄₈"  
/ 240 x 240 mm) and attach to firestop with #8 sheet  
metal screws (supplied). Assemble sleeve and attach  
to firestop with #8 sheet metal screws (supplied). Install  
firestop assembly.  
A vent starter kit plus a transition elbow  
must be used in Vertical Sidewall Installa-  
tions. The 4" pipe must be centered inside  
the 7" pipe coming off the transition elbow.  
Canadian & USA Installations:  
Zero clearance sleeve is only required for  
combustible walls.  
The venting system must conform with local codes, or  
in the absence of local codes, with the National Fuel  
Gas Code, ANSI Z223.1/NFPA 54 - latest edition, or  
CSA B149.1 Installation Code.  
Adjustable  
Zero Clearance  
Sleeve  
Max. Length  
12" (305 mm)  
Only CFM Corporation venting components specifically  
approved and labelled for this fireplace may be used.  
#8 Screws  
(2)  
Vertical Sidewall Installations  
#8  
Screws  
STEP 1  
(2)  
#8 Screws (2)  
Locate vent opening on the wall. It may be necessary  
to first position the fireplace and measure to obtain hole  
location. Depending on whether the wall is combustible  
or noncombustible, cut opening to size. (Fig. 22)  
Firestop  
Adjustable Zero Clearance Sleeve  
ZCS101  
For combustible walls first frame in opening.  
Fig. 23 Adjustable zero clearance sleeve.  
Combustible Walls (Fig. 22): Cut a 9³⁄₈" x 9³⁄₈" (240 x  
240 mm) hole through the exterior wall and frame.  
STEP 3  
Noncombustible Walls (Fig. 22): Hole opening must  
be 7¹⁄₂" (190 mm) in diameter.  
Apply a bead of high temperature sealant to the inner  
and outer flue collars of the fireplace and using ap-  
propriate venting component(s) attach to fireplace with  
three (3) screws. (Fig. 24) Follow with the installation  
of the inner and outer elbow. Again, secure joints with  
three (3) sheet metal screws. Wipe off any excess high  
temperature sealant.  
Vent Opening for Combustible Wall  
9³⁄₈"  
(240 mm)  
Framing  
Detail  
9³⁄₈"  
(240 mm)  
Ensure Pipes  
are Concentric  
Fireplace  
Hearth  
Vent Opening for Noncombustible Wall  
7¹⁄₂"  
(190 mm)  
 
VO584-100  
Bead of Seal-  
ant  
(If Necessary)  
Fig. 22 Locate vent opening on wall.  
CFM143  
Fig. 24 Apply sealant to inner and outer pipe.  
10001195  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
STEP 4  
STEP 6  
Measure the horizontal length requirement including a  
2" (51 mm) overlap, i.e. from the elbow to the outside  
wall finish plus 2", or the distance required if installing a  
second 90° elbow. (Fig. 25)  
Apply high temperature sealant to 4" (102 mm) and 7"  
(178 mm) collars or the termination 1" (25 mm) away  
from the end. Guide the vent termination's 4" and 7" col-  
lars into their respective vent pipes. Double check that  
the vent pipes overlap the collars by 2" (51 mm). Secure  
the termination to the wall with screws provided and  
caulk around the wall plate to weatherproof. (Fig. 27)  
X
Always install  
horizontal vent-  
ing on a level  
plane.  
X
X
CFM136  
CFM138  
Fig. 25 Measure horizontal length including 2" overlap.  
Fig. 27 Horizontal length requirement.  
STEP 5  
STEP 7  
Use appropriate length of pipe section - telescopic or  
fixed - and install the horizontal vent sections. The 20"  
(508 mm) section of pipe which goes through the wall is  
packaged with the 7TDVSK starter kit, and can be cut  
to suit if necessary. (Fig. 26)  
Support the horizontal pipes every 36" (914 mm) with  
metal pipe straps. Make sure the horizontal vent pipe is  
installed on a level horizontal plane.  
STEP 8  
Sealing vent pipe and firestop gaps with  
high temperature sealant will restrict cold  
air being drawn in around the fireplace.  
Re-check the fireplace to make sure that it is levelled,  
properly positioned and nailed or screwed to the floor.  
If applied, the fireplace's adjustable frame drywall strips  
(nailing flanges) should be fastened. Refer to "Framing  
& Finishing" section.  
X
High Temperature  
Sealant  
Below Grade Installation  
When it is not possible to meet the required vent ter-  
minal clearances of 12" (305 mm) above grade level, a  
snorkel termination, #7TDVSNORK is required. It allows  
installation depth of down to 7" (178 mm) below grade  
level. The 7" is measured from the center of the hori-  
zontal vent pipe as it penetrates through the wall.  
Ensure sidewall venting clearances are observed.  
If venting system is installed below ground,  
a window well with adequate and proper  
drainage to be installed around the termi-  
nation area is recommended.  
The maximum horizontal run with 24" (610 mm)  
vertical rise is 36" (914 mm) from the back of the  
fireplace to the face of the exterior wall. Refer to the  
vent graph on Page 12 for extended horizontal run if  
the vertical rise exceeds 24" (610 mm).  
CFM137  
Fig. 26 Apply high temperature sealant.  
16  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
1. Establish vent hole through the wall. (Fig. 22)  
Vertical Through-the-Roof Applications  
2. Remove soil to a depth of approximately 16" (406 mm)  
below base of snorkel. Install window well (not sup-  
plied). Refill hole with 12" (305 mm) of coarse gravel  
leaving a clearance of approximately 4" (102 mm)  
below snorkel. (Fig. 28)  
This gas fireplace has been approved for:  
Vertical installations up to 40' (12 m) in height. Up to  
10' (3 m) horizontal vent run can be installed within  
the vent system using a maximum of three (3) 90°  
elbows.  
3. Install vent system. Refer to Page 12, Steps 2  
through 5.  
4. Ensure a watertight seal is made around the vent  
pipe coming through the wall.  
5. Apply high temperature sealant caulking (supplied)  
around the 4" and 7" snorkel collars.  
Maximum  
10' (3m)  
6. Slide into the vent pipe and secure to the wall.  
Minimum 8'  
(2.4m)/ Maxi-  
mum 40' (12m)  
Vertical Rise  
7. Level the soil to maintain a 4" (102 mm) clearance  
below snorkel. (Fig. 28)  
Do not backfill around snorkel. A clearance  
of at least 4" (102 mm) must be maintained  
below the snorkel.  
Pipe Straps Every 3'  
(914mm)  
Zero Clearance  
Sleeve  
7TDVSNORK  
(Snorkel)  
Firestop  
CFM148  
Screws  
4" (102mm)  
Clearance  
Min.  
7" Pipe  
Fig. 30 Support straps for horizontal runs.  
Up to two (2) 45° elbows may be used within the  
horizontal run. For each 45° elbow used on the hori-  
zontal level, the maximum horizontal length must be  
reduced by 18" (457 mm).  
Window  
Well  
24" (608mm)  
Minimum*  
Gravel  
Drain  
Example: Maximum horizontal length:  
0 x 45° elbows = 10' (3 m)  
1 x 45° elbows = 8¹⁄₂' (2.6 m)  
Foundation Wall  
2 x 45° elbows = 7' (2.1 m)  
*A minimum of 24" (608mm)  
vertical pipe must be installed  
when using the 7TDVSNORK  
Kit.  
A minimum of an 8' (2.4 m) vertical rise.  
Two (2) sets of 45° elbows offset within these verti-  
cal installations. From 0 to a maximum of 8' (2.4m)  
of vent pipe can be used between elbows. (Fig. 30)  
BG400  
Fig. 28 Below grade installation.  
7DVCS must be used to support offsets. (Fig. 31)  
This application will require that you first determine  
the roof pitch and use the appropriate 7DVSKV (A, B  
or F). Refer to Venting Components on Page 21.  
Snorkel  
Vertical Through-the-Roof Installation  
1. Locate your fireplace.  
Foudation Recess  
Recess Bracket  
Wall Screws  
2. Plumb to center of the 4" flue collar from ceiling  
above and mark position.  
3. Cut opening equal to 9³⁄₈" x 9³⁄₈" (240 x 240 mm).  
Sheet Metal  
Screws  
Watertight Seal  
Around Pipe  
4. Proceed to plumb for additional openings through  
the roof. In all cases, the opening must provide a  
minimum of 1" clearance to the vent pipe, i.e., the  
hole must be at least 9³⁄₈" x 9³⁄₈" (240 x 240 mm).  
BG401  
Fig. 29 Snorkel installation, recessed foundation.  
10001195  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Attic Insulation  
Shield  
Max 8'  
(2.4 m)  
Joist  
Typical Ceil-  
ing Support  
Application  
45°  
40'  
(12 m)  
Max 8'  
(2.4 m)  
11"  
Upper Floor  
Joist  
11"  
Ceiling In-  
stallation  
45°  
Firestop Spacer  
Nails (4)  
CFM100  
Fig. 32 Place firestop spacer(s) and secure.  
Typcal Roof  
Support Ap-  
plication  
Fig. 31 Typical vertical roof application.  
3 #5 Sheet Metal  
Screws per Joint  
5. Place fireplace into position.  
Sealant  
Storm Collar  
6. Place firestop(s) #7DVFS or attic insulation shield  
#7DVAIS into position and secure. (Fig. 32)  
7. Install roof support (Fig. 33) and roof flashing, mak-  
ing sure upper flange is below the shingles. (Fig. 33)  
TWL101a  
8. Install appropriate pipe sections until the venting is  
above the flashing. (Fig. 33)  
Fig. 33 Roof flashing.  
9. Install storm collar and seal around pipe.  
Vent Termination  
10. Add additional vent lengths for proper height. (Fig.  
34)  
2'  
Storm Collar  
(610mm)  
Min.  
11. Apply high temperature sealant to 4" and 7" collars  
of vertical vent termination and install.  
Roof Flashing  
Roof Support  
Attic Insulation  
If there is a room above ceiling level,  
firestop spacers must be installed on both  
the bottom and the top side of the ceiling  
joists. If an attic is above ceiling level a  
7DVAIS (Attic Insulation Shield) must be  
installed. (Fig. 32)  
40'  
(12.m)  
Shield  
Attic Insula-  
tion  
Joists  
Joists  
The enlarged ends of the vent section al-  
ways face downward. (Fig. 33)  
FP1022  
Fig. 34 Typical straight-up installation.  
18  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Twist Lock Venting Components  
7TDVRVT - Through the Wall Rear Vent Termination  
Starter Kit -Model 7TDVSK - Sidewall Venting  
Starter Kit -Model 7TDVSKV - Vertical Venting  
for 7TDVSKV-A order 1/12 to 6/12 roof pitch  
for 7TDVSKV-B order 7/12 to 12/12 roof pitch  
for 7TDVSKV-F order flat roof  
Starter Kit - Model 7TDVSKS - Snorkel Kit  
Snorkel Termination - 7TDVSNORK  
for Below Grade Installation  
45o Elbow  
7TDV45 for Rear Vent to Vertical Vent  
or Vertical/Horizontal Offsets  
90o Transition Elbow  
7TDVRT90 for Rear Vent to Vertical Vent  
90° Elbow  
7TDV90 Vertical/Horizontal Offset  
Telescopic vent sections  
7TDVP1218 - 12" to 18" adjustable length  
7TDVP3566 - 35" to 64" adjustable length  
Pipe sections for vertical or horizontal venting  
Model 7TDVP8  
Model 7TDVP12  
Model 7TDVP24  
Model 7TDVP36  
Model 7TDVP48  
Firestop Spacer  
Model 7DVFS  
Attic Insulation Shield  
Model 7DVAIS  
Vertical/Horizontal Combination Offset Support  
Model 7DVCS  
10001195  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Operating Instructions  
General Glass Information  
Glass  
Frame  
Only glass approved by Vermont Casting,  
Majestic Products should be used on this  
fireplace.  
Fireplace  
Front  
The use of non-approved replacement glass will void  
all product warranties.  
Clamps  
Care must be taken to avoid breakage of the glass.  
Do not operate appliance with glass front  
removed, cracked or broken.  
Replacement of the glass (complete with gasket)  
is available through your Majestic Fireplaces  
dealer and should be done by a licensed  
qualified service person.  
Window  
Frame  
Assembly  
Window  
Frame  
Assem-  
bly  
Pull Clamp Hook  
FP1405  
Push  
Clamp  
Handle  
Louvre Removal  
To remove top louvre,  
pull louvre up and  
then lift out. (Fig. 35)  
Fig. 36 Window frame assembly removal.  
be cleaned two or three times with a non-ammonia  
household cleaner and warm water (we recommend  
gas fireplace glass cleaner). After that the glass should  
be cleaned two or three times during each heating  
season depending on the circumstances present.  
2.  
Top Lou-  
vre  
Assembly  
1.  
Clean glass after first two weeks of  
operation.  
Window  
Do not clean glass when it is hot.  
Do not use abrasive cleaners.  
Do not strike or slam the glass.  
Frame As-  
sembly  
FP1227  
Fig. 35 Remove top louvre as-  
sembly.  
Installation of Logs &  
Burner Lava Rock Material  
Window Frame Assembly Removal  
Refer to Figure 37.  
1. Shut off gas.  
1. Remove window frame assembly.  
2. Remove logs from packaging.  
2. Let the fireplace cool if it has been operating.  
3. Remove top louvre assembly. (See Louvre Removal)  
4. Open the lower louvre assembly.  
3. Place rear log (B15) on rear bracket (ensure log is  
seated properly, levelled and centered to the unit),  
so it will not move from side to side and it is firmly  
positioned on the bracket.  
5. Release the two clamps at the bottom of the window  
frame by pulling down on the clamp handles. (Fig.  
36)  
4. Slip front ember log (B12) down in the front deflector.  
6. Tilt window frame assembly out slightly at the bot-  
tom, lift the frame up and away from the fireplace.  
5. Place front left log (B13) on top burner, left side. Use  
log's bottom holes to locate it into the left bracket log  
locator studs.  
7. To replace window frame assembly, reverse this  
procedure.  
6. Place front right log (B14) on top of burner, right  
side. Use log's bottom holes to locate it into the right  
bracket log locator studs.  
Glass Cleaning  
It will be necessary to clean the glass periodically.  
During start-up, condensation, which is normal, forms  
on the inside of the glass and causes lint, dust and  
other airborne particles to cling to the glass surface.  
Also initial paint curing may deposit a slight film on  
the glass. It is therefore recommended the glass  
7. Place burner lava rock on top of burner. (Fig. 37)  
Refer to "Setting Temperature Rise".  
8. Place top right log (B17) onto locator notches.  
Ensure log is secure.  
20  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
9. Place top left log (B16) onto locator notches. Ensure  
log is secure.  
Emergency Heat  
In the event of a power outage, the DVHVAC36 unit can  
be run in an emergency heat mode. Simply turn the unit  
on by toggling the rocker switch located on the front of  
the electrical junction box to the  
Top logs must be placed properly onto  
notches.  
B17  
"ON" position. This will turn on  
B16  
the fireplace burner in a low fire  
B15  
condition. The unit will provide  
heat to the room in which the  
fireplace is installed. When power  
is restored, toggle the emergency  
heat switch to the "OFF" position.  
B14  
B13  
NOTE: When in the emergency  
heat mode, the air circulating fan  
will not operate. In order to pre-  
vent overheating of the duct work,  
the unit will periodically cycle on  
and off. The length of cycles will  
depend upon factors such as the  
length and design of the duct-  
work, interior temperature and  
venting arrangements.  
B12  
LG310  
NOTE: When the electricity is off,  
Fig. 37 DVHVAC36 log placement.  
the thermostat will not operate  
Setting Temperature Rise  
the unit. The unit must be controlled manually through  
the emergency heat switch located on the front of the  
electrical junction box.  
With the unit installed and operating at equilibrium,  
adjust the temperature rise through the unit to between  
25° and 50° Farenheit.  
Flame Characteristics  
Lava Rock  
It is important to periodically perform a visual check  
of the pilot and the burner flames. Compare them to  
Figures 39 & 40. If any of the flames appear abnormal,  
contact a qualified service provider for service and  
adjustment.  
The lava rock provided with this fireplace must be  
placed on the firebox base on either side of the burner  
assembly.  
Under no circumstances should this lava  
rock be placed on any part of the burner  
assembly.  
3/8" - 1/2"  
Flame Adjustment  
The DVHVAC36 is equipped with a HI/LO flame adjust-  
ment knob located on the front of the electrical junction  
box. Rotating the knob will adjust the flame height and  
heat output of the unit. (Fig. 38)  
FP1229a  
Turn  
counterclockwise  
Fig. 40 Correct pilot flame appearance.  
Turn clockwise  
to decrease  
to increase  
flame height  
flame height  
Fig. 38 Flame adjustment knob for SIT valve.  
10001195  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
LG311  
Fig. 39 Correct burner flame pattern for DVHVAC36.  
Inspecting the Venting System  
This appliance venting system was designed and con-  
structed to develop a positive flow adequate to remove  
flue gases to the outside atmosphere.  
Firebox  
Back  
Refractory  
Back Panel  
Any foreign objects in the venting system, except those  
designed specifically for the venting system, may cause  
spillage of flue gases.  
To inspect the venting heat exchanger system, make  
sure the main gas valve is off. Remove window frame  
assembly. (Refer to Window Frame Assembly Removal  
section) Using a flashlight, check the area above the  
baffle in the combustion dome. Clean if necessary.  
Rear Log Support  
H102a  
Fig. 41 Place back refractory into support and swing into  
position.  
Inspecting the Venting/Heating  
Exchange System  
Any foreign objects or corrosion in the heat exchanger  
or venting system may cause spillage or leakage of the  
gases into the living space.  
Adjustable  
Tabs  
Adjustable  
Tabs  
Ceramic Refractory Installation  
Back  
Panel  
Side  
Panel  
Side  
Panel  
1. Remove window frame assembly and logs.  
Log Support  
Burner Tray  
2. Place refractory side supports so that the hole fits  
over the screw head on the firebox floor.  
Base Side  
Refractory  
3. Place refractory base sides on the floor of the fire-  
box.  
Base  
Side Re-  
fractory  
4. Attach adjustable tabs, packed with refractory, onto  
the studs found on the top of the firebox using the  
2-10/24 nuts provided.  
Base Side Supports  
FP1231  
Fig. 42 Ceramic refractory installation.  
5. Place back refractory - small brick edge down into  
support and swing into position. (Fig. 41)  
6. Slide side panels into side supports and behind side  
tab and adjust, fitting the ceramic tight to the side of  
the firebox. Tighten nuts. (Fig. 42)  
Mortar lines must be aligned.  
22  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Lighting & Operating Instructions  
For fireplaces equipped with SIT 825 MIllivolt Gas Valve  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING:If you do not follow these instructions exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
A. This heater has a pilot which must be lit manu-  
ally. When lighting the pilot follow these instruc-  
tions exactly.  
instructions.  
If you cannot reach your gas supplier, call  
the Fire Department  
B. BEFORE LIGHTING smell all around the heater  
area for gas. Be sure to smell next to the floor  
because some gas is heavier than air and will  
settle on the floor.  
C. Use only your hand to push in or turn the gas  
control knob. Never use tools. If the knob will not  
push in or turn by hand, do not try to repair it, call a  
qualified service technician. Applying force or any  
attempted repair may result in a fire or explosion.  
WHAT TO DO IF YOU SMELL GAS  
Do not try to light any fireplace  
Do not touch any electric switch  
Do not use any phone in your building  
D. Do not use this fireplace if any part has been under  
water. Immediately call a qualified service techni-  
cian to inspect the heater and to replace any part of  
the control system and any gas control which has  
been under water.  
Immediately call your gas supplier from a  
neighbor's phone. Follow the gas supplier's  
Lighting Instructions  
1. STOP! Read the safety information above.  
2. Turn the ON/OFF swtich to "OFF" position or  
set the thermostat to lowest setting.  
3. Turn off all electrical power to the fireplace.  
4. Open control access panel.  
ing the piezo spark ignitor until a flame appears.  
Continue to hold the control knob in for about one  
(1) minute after the pilot is lit. Release knob and it  
will pop back up. Pilot should remain lit. If it goes  
out, repeat steps 5 through 8.  
5. Remove glass door before lighting pilot. (See  
Glass Door Removal)  
3/8" - 1/2"  
6. Push in gas control knob slightly and turn  
clockwise  
to "OFF".  
OFF  
PILOT  
2
If knob does not pop up when released, stop  
O
and immediately call your service technician or  
gas supplier.  
Honeywell  
If after several tries, the pilot will not stay lit,  
Euro SIT  
SIT NOVA  
turn the gas control knob to "OFF" and call your  
service technician or gas supplier.  
7. Wait fifteen (15) minutes to clear out any gas.  
Then smell for gas, including near the floor. If  
you smell gas, STOP! Follow "B" in the safety  
information above. If you do not smell gas, go  
to the next step.  
8. Visibly locate pilot by the main burner.  
9. Turn knob on gas control counterclockwise  
to "PILOT".  
11. Turn gas control counterclockwise  
"ON" position.  
to the  
12. Replace glass door.  
13. Turn on all electrical power to the fireplace.  
14. Turn the ON/OFF swtich to "ON" position or set  
the thermostat to desired setting.  
15. This valve is equipped with a HI/LO feature. Set  
fireplace input as desired.  
10. Push the control knob all the way in and hold.  
Immediately light the pilot by repeatedly depress-  
To Turn Off Gas To Heater  
1. Turn the On/Off switch to Off position or set the  
thermostat to lowest setting.  
3. Open control access panel.  
4. Push in gas control knob slightly and turn clock-  
2. Turn off all electric power to the fireplace if  
service is to be performed.  
wise  
to "OFF". Do not force.  
5. Close control access panel.  
10001195  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Troubleshooting the Gas Control System  
SIT NOVA 825 Millivolt Valve  
NOTE: Before troubleshooting the gas control system, be sure external gas shut off is in the "ON" position.  
SYMPTOM  
POSSIBLE CAUSES  
CORRECTIVE ACTION  
1.Spark ignitor will not light  
A. Defective or misaligned  
electrode at pilot.  
Using a match, light pilot. If pilot lights, turn off  
pilot and push the red button again. If pilot will not  
light - check gap at electrode and pilot-should be  
1/8" to have a strong spark.  
B. Defective ignitor (Push Button)  
Push Piezo Ignitor Button. Check for spark at  
electrode and pilot. If no spark to pilot, and elec  
trode wire is properly connected, replace ignitor.  
2. Pilot will not stay lit after  
carefully following lighting  
instructions.  
A. Defective pilot generator  
(thermocouple)  
Check pilot flame. Must impinge on thermo-  
couple/thermopile. Note: this pilot burner assem  
bly utilizes both-a thermocouple and a thermopile.  
The thermocouple operates the main valve  
operation (On and Off). Clean and or adjust pilot for  
maximum flame impingement on thermopile and  
thermocouple.  
B. Defective automatic valve  
Turn valve knob to “Pilot”. Maintain flow to pilot;  
millivolt meter should read greater than 10 mV. If  
the reading is okay and the pilot does not stay on,  
replace the gas valve. Note: An interrupter block  
(not supplied) must be used to conduct this test.  
3. Pilot burning, no gas to  
main burner, Valve knob  
"ON", thermostat "ON"  
A. Thermostat or wires defective  
Check wall switch and wires for proper connections.  
B. Thermopile may not be  
generating sufficient  
millivoltage.  
1. Be sure wire connections from thermopile at  
gas valve terminals are tight and thermopile is  
fully inserted into pilot bracket.  
2. One of the wall switch wires may be grounded.  
Remove wall switch wires from valve terminals if  
pilot now stays lit, trace wall switch wiring for  
ground. May be grounded to fireplace or gas  
supply.  
3. Check thermopile with millivolt meter. Take  
reading at thermopile terminals of gas valve.  
Should read 325 millivolts while holding valve  
knob depressed in pilot position and wall switch  
“Off”. Replace faulty thermopile if reading is below  
specified minimum.  
C. Plugged burner orifice.  
Check burner orifices for debris and remove.  
D. Defective automatic valve  
operator.  
Turn valve knob to “On”, place wall switch to “On”  
millivolt meter should read greater than 100 mV. If  
the reading is okay and the burner does not come  
on, replace the gas valve.  
E. Transformer defective.  
F. Power Not ON.  
G.heat demand satisfied.  
4. Frequent pilot outage  
problem.  
A. Pilot flame may be too low  
or blowing (high) causing the  
pilot safety to drop out.  
Clean and/or adjust pilot flame for maximum flame  
impingement on thermopile and thermocouple.  
B. Possible blockage of the vent  
terminal.  
Check the vent terminal for blockage  
24  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Maintenance  
1. It is important to keep the burner and the burner  
Cleaning the Standing  
compartment clean. This must be done periodically,  
at least once per season.  
Pilot Control System  
The burner and control system consist of:  
2. Clean the brass trim using a soft clean cloth, slightly  
dampened with lemon oil and buff with a soft clean  
cloth. DO NOT use brass polish or household clean-  
ers as these products will damage the brass trim.  
Lemon oil can be obtained at supermarkets or hard-  
ware stores.  
burner tube  
pilot assembly  
millivolt gas valve  
gas orifice  
thermopile  
Most of these components may require only an  
occasional checkup and cleaning and some may  
require adjustment. If repair is necessary, it should  
be performed by a qualified technician.  
3. Periodically check and clean the air circulating  
blower wheel of any debris. Blower motors are  
prelubricated for extended bearing life. No further  
lubrication is required. WARNING: Disconnect power  
before servicing the air circulating blower.  
1. Turn off pilot light at gas valve.  
2. Allow fireplace to cool if it has been operating.  
4. The air filter should be inspected monthly and re-  
placed when necessary with a 16" x 16" x 1" filter.  
3. Remove window frame assembly. (Refer to Window  
Frame Assembly Removal section.)  
5. When servicing, check all electrical wiring for loose  
connections.  
4. Remove logs.  
5. Vacuum burner compartment especially around  
orifice primary air openings.  
WARNING: Disconnect power before serv-  
icing.  
6. Visually inspect pilot. Brush or blow away any dust  
or lint accumulation.  
6. Contact your local representative to arrange an an-  
nual service program.  
7. Reinstall logs.  
8. Ignite pilot - Refer to Lighting Instructions.  
9. Reinstall window frame assembly.  
To obtain proper operation, it is imperative that the pilot  
and burner’s flame characteristics are steady, not lifting  
or floating.  
Typically, the top 3/8” to 1/2” (10mm or 13mm) of the  
thermopile should be engulfed in the pilot flame. (Refer  
to Page 21, Figure 40)  
To adjust pilot burner: (by qualified service technician)  
1. Remove pilot adjustment cap  
2. Adjust pilot screw to provide properly sized flame.  
3. Replace pilot adjustment cap.  
The primary air shutter is set at factory and should  
only be adjusted, if necessary, by a qualified service  
technician.  
10001195  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
5
21  
4a,b  
35  
7a/b  
11  
22  
6a/b  
c/d  
16a,b  
3
29  
23  
20  
2
9
24  
14  
27  
17  
15  
18  
12  
28  
34  
31  
13  
19  
10  
8a/b  
30  
26  
32  
33  
25  
1e  
1f  
29  
1d  
1c  
1b  
1a  
1195  
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,  
without notice.  
DVHVAC36  
Ref. Description  
1. Log Set Complete  
1a. Log Ember Front  
1b. Log Front Left  
1c. Log Front Right  
1d. Log Rear  
DVHVAC36  
10001196  
B12  
B13  
B14  
B15  
26  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
DVHVAC36 (continued)  
Ref. Description  
DVHVAC36  
1e. Log Top Left  
B16  
1f. Log Top Right  
B17  
2. Lava Rock (Package)  
3. Burner Lava Rock (Package)  
4a. Burner Housing and tiles Nat.  
4b. Burner Housing and tiles Prop.  
5. Ceramic Tile (single)  
6a. Orifice Main Burner Nat.  
6b. Orifice Front Burner Nat.  
6c. Orifice Main Burner Prop.  
6d. Orifice Front Burner Prop.  
7a. Pilot Assembly Nat. (3 Way)  
7b. Pilot Assembly Prop. (3 Way)  
8a. Orifice Pilot Nat.  
10001454  
57897  
10001047  
10001048  
57803  
See Rating Plate for Orifice Size  
See Rating Plate for Orifice Size  
See Rating Plate for Orifice Size  
See Rating Plate for Orifice Size  
10002264  
10002265  
54273  
8b. Orifice Pilot Prop.  
9. Pilot (3 Way)  
10. Pilot Tubing w/fittings  
11. Manifold Tubing w/fittings  
12. Thermocouple  
54272  
10001295  
53211  
57318  
53373  
13. Thermopile  
51827  
14. Electrode Ignitor w/cable  
15. Ignitor Piezo  
10001297  
52464  
16a. Valve SIT 825 Nat. (RN)  
16b. Valve SIT 825 Prop. (RP)  
17. Glass with Gasket  
18. Gasket Glass  
10001059  
10001060  
54427  
57317  
19. Frame Window Assembly  
20. Clamp Frame Window  
21. Top Louvre Assembly  
22. Bottom Louvre Assembly  
23. Access Door Hinge  
24. Blower Housing / Wheel  
25. Blower Motor  
26. Capacitor  
27. Heat Exchanger  
28. Limit Control Sensor  
29. Circuit Board  
30. Transformer  
10001425  
54174  
10000037  
10000038  
52356  
10001164  
10005689  
10001166  
10000893  
10001172  
10001167  
7522409  
31. Potentiometer  
32. Knob  
33. Air Filter  
34. Rocker Switch  
10001168  
10001169  
10001171  
53606  
35. Ceramic Refractory Kit  
10001341  
10001195  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
Optional Accessories  
Decorative Bay Window  
When fitting the bay window kits, the  
original front frame/glass assembly must  
remain in place. The bay window kit is fit-  
ted over the existing front glass.  
Brass Window  
Top  
Ceramic Re-  
fractory  
Ceramic Re-  
fractory  
1. Remove existing bottom louvre assembly and hinges  
from fireplace. (Set aside the two (2) self tapping  
screws).  
Brass Window Bottom  
Brass Bottom  
FP1407  
2. Remove existing top louvre from fireplace.  
Fig. 43 DVHVAC36 bay window.  
3. Assemble Bay Window Kit according to instructions  
supplied with kit.  
4. Place the two pieces of ceramic refractory along the  
base of the bay window. (Fig. 43)  
5. Hang bay window assembly over existing window  
frame assembly.  
Do not remove existing window frame as-  
sembly.  
6. Re-install upper louvre assembly.  
Remove all plastic from brass trims.  
7. Bottom brass trim is removable when unit is installed  
with marble or tile surround which covers the fire-  
place bottom.  
28  
10001195  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DVHVAC36  
10001195  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LIMITED LIFETIME WARRANTY  
PRODUCT COVERED BY THIS WARRANTY  
All Vermont Castings gas stoves, gas inserts, and gas fireplaces, and all Majestic brand gas fireplaces equipped with  
an Insta-Flame Ceramic Burner, or standard steel tube burner.  
BASIC WARRANTY  
Any part and/or component replaced under the provisions of this  
warranty is covered for six months or the remainder of the original  
warranty, whichever is longest.  
CFM Corporation (hereinafter referred to collectively as the Company)  
warrants that your new Vermont Castings or Majestic Gas Fireplace/  
Stove is free from manufacturing and material defects for a period of  
one year from the date of purchase, subject to the following conditions  
and limitations.  
This warranty is limited to the repair of or replacement of part(s) found  
to be defective in material or workmanship, provided that such part(s)  
have been subjected to normal conditions of use and service, after  
said defect is confirmed by the Company’s inspection.  
EXTENDED LIFETIME WARRANTY  
The company may, at its discretion, fully discharge all obligations  
with respect to this warranty by refunding the wholesale price of the  
defective part(s)  
The heat exchanger, where applicable, and combustion chamber  
of every Vermont Castings or Majestic gas product is warranted for  
life against through wall perforation. All appliances equipped with an  
Insta-Flame Ceramic Burner have limited lifetime coverage on the  
ceramic burner plaque. Warrantees are made to the original owner  
subject to proof of purchase and the conditions and limitations listed  
on this Warranty Document  
Any installation, labor, construction, transportation, or other related  
costs/expenses arising from defective part(s), repair, replacement,  
or otherwise of same, will not be covered by this warranty, nor shall  
the Company assume responsibility for same. Further, the Company  
will not be responsible for any incidental, indirect, or consequential  
damages except as provided by law.  
COMPONENT WARRANTY  
CAST IRON: All external and internal cast iron parts are warranted for a  
period of three years.  
SOME STATES DO NOT ALLOW FOR THE EXCLUSION OR  
LIMITATIONS OF INCIDENTALAND CONSEQUENTIAL DAMAGES  
OR LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY  
LASTS, SO THE ABOVE LIMITATIONS MAY NOT APPLY TO YOUR  
CIRCUMSTANCES. THIS WARRANTY GIVES YOU SPECIFIC  
RIGHTSANDYOUMAYHAVEOTHERRIGHTSWHICHVARYFROM  
STATE TO STATE.  
Note:OnporcelainenamelnishedexternalpartsandaccessoriesThe  
Company offers no Warranty on chipping of enamel surfaces. Inspect  
all product prior to accepting it for any damage to the enamel.  
Thesaltairenvironmentofcoastalareasorahighhumidityenvironment  
can be corrosive to the porcelain enamel finish. These conditions can  
cause rusting of the cast iron beneath the porcelain enamel finish,  
which will cause the finish to flake off.  
All other warranties-expressed or implied- with respect to the product,  
its components and accessories, or any obligations/liabilities on the  
part of the Company are hereby expressly excluded.  
Dyelotvariationswithreplacementpartsand/oraccessoriescanoccur  
and are not covered by warranty.  
The Company neither assumes, nor authorizes any third party to  
assume on its behalf, any other liabilities with respect to the sale of  
this Vermont Castings, Majestic product  
GLASS DOORS: Glass doors are covered for a period of one year.  
Glass doors are not warranted for breakage due to misuse or accident.  
Glass doors are not covered for discoloration or burned in stains due to  
environmental issues, or improper cleaning and maintenance.  
Thewarrantiesasoutlinedwithinthisdocumentdonotapplytochimney  
componentsorothernonVermontCastings,Majesticaccessoriesused  
in conjunction with the installation of this product..  
BRASS PLATED PARTS AND ACCESSORIES: Brass parts should be  
cleaned with Lemon oil only. Brass cleaners cannot be used. Mortar  
mix and masonry cleaners may corrode the brass finish. The Company  
will not be responsible for, nor will it warrant any brass parts which are  
damaged by external chemicals or down draft conditions.  
Damage to the unit while in transit is not covered by this warranty but  
is subject to claim against the common carrier. Contact the dealer  
from whom you purchased your fireplace/stove (do not operate the  
appliance as this might negate the ability to process the claim with the  
carrier).  
GAS VALVES: Gas valves are covered for a period of one year  
The Company will not be responsible for:  
ELECTRONIC AND MECHANICAL COMPONENTS: Electronic and  
mechanical components of the burner assembly are covered for one year.  
All steel tube burners are warranted for one year.  
a) Down drafts or spillage caused by environmental conditions such  
as near-by trees, buildings, roof tops, hills, or mountains.  
b) Inadequate ventilation or negative air pressure caused by  
mechanical systems such as furnaces, fans, clothes dryers, etc.  
ACCESSORIES: Unless otherwise noted all components and CFM  
Corporation company supplied accessories are covered for a period of  
one year.  
This warranty is void if:  
a) The fireplace has been operated in atmospheres contaminated by  
chlorine, fluorine, or other damaging chemicals.  
CONDITIONS AND LIMITATIONS  
b) Thereplacehasbeensubjectedtoprolongedperiodsofdampness  
or condensation  
c) Anydamagestothereplace,combustionchamber,heatexchanger  
orothercomponentsduetowater, orweatherdamage, whichisthe  
result of but not limited to, improper chimney/venting installation.  
d) Any alteration, willful abuse, accident, or misuse of the product  
This new Vermont Castings or Majestic product must be installed by  
a competent, authorized, service contractor. A licensed technician, as  
prescribedbythelocaljurisdictionmustperformanyinstallation/service  
work. It must be installed and operated at all times in accordance with  
the Installation and Operating instructions furnished with the product.  
Any alteration, willful abuse, accident, or misuse of the product shall  
nullify this warranty.  
has occurred.  
This warranty is non-transferable, and is made to the original owner,  
provided that the purchase was made through an authorized supplier  
of the Company.  
IF WARRANTY SERVICE IS NEEDED…  
1) Contactyoursupplier. Makesureyouhaveyourwarranty, your  
sales receipt, and the model/serial number of your Vermont  
Castings, Majestic product.  
2) DO NOT ATTEMPT TO DO ANY SERVICE WORK  
YOURSELF.  
The customer must pay for anyAuthorized Dealer in-home travel fees  
or service charges for in-home repair work. It is the dealers option  
whether the repair work will be done in the customer’s home or in the  
dealer’s shop.  
Ifuponinspection,thedamageisfoundtobethefaultofthemanufacturer,  
repairs will be authorized at no charge to the customer parts and/or  
labor.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Efficiency Ratings  
Model  
EnerGuide Ratings  
Fireplace Efficiency (%) Fan-OFF  
Steady State (%)  
D.O.E.  
(AFUE%)  
77.1  
Fan-ON  
84  
DVHVAC36RN  
DVHVAC36RP  
76  
76  
83  
84  
85  
77.1  
CFM Corporation  
410 Admiral Blvd. • Mississauga, Ontario, Canada L5T 2N6  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technics Headphones WX H3050 User Manual
Texas Instruments Cell Phone 3000 MCU User Manual
Timex Watch Performance Watch User Manual
Toastmaster Mixer RHHMRET User Manual
Toshiba Fax Machine TF 461 User Manual
Tributaries TV Cables HX101 User Manual
Verilux Vacuum Cleaner UV C User Manual
Video Products Computer Hardware PCHD HDMI SCALER User Manual
Wagner SprayTech Power Roller Cordless Power Roller User Manual
Watlow Electric Electric Heater Responsive Heater User Manual