STR/CVR Series
Woodburning Fireplace
Homeowner's Installation
and Operating Manual
For Models:
STR33
STR36
STR42
CVR36
CVR42
For use in U.S./Canada
Underwriter's Laboratories
Report No. MH6018
DO NOT DISCARD THIS MANUAL: Retain for future use.
7412961 3/06 Rev. 15
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
STR Series Woodburning Fireplace
F
G
12"
24" Total
Unit Width
�
�
Framing Width
Will be 24" Minus
2 x (Drywall Thickness)
STR33
STR36 STR42
36" 42"
914mm 1067mm
40" 46"
1016mm 1168mm
20" 23"
508mm 584mm
49���" 53���"
A 33"
838mm
C
B
37"
940mm
C 18���"
470mm
D 49���"
18���"
1267mm 1267mm 1368mm
E 52���" 52���" 56���"
1340mm 1340mm 1442mm
F
11"
279mm
11"
279mm 343mm
8" 11"
203mm 279mm
29 ����"� 35����"
741mm 894mm
13���"
7���"
G
8"
203mm
J 26���"�
680mm
E
�
D
37"
36"
12"
21"
J
14���"
7���"
9���"
12"
A
Outside
Air
Gas Line Access
B
Fig. 1 STR Series specifications and framing.
CVR Series Woodburning Fireplace
F
G
��"
��" Total
Unit Width
�
�
Framing Width
Will be 24" �����
2 x (Drywall Thickness)
CVR36
CVR42
42"
A
36"
C
914 mm 1067 mm
40" 46"
1016 mm 1168 mm
20" 23"
508 mm 584 mm
49���" 53���"
1267 mm 1368 mm
52���" 56���"
1340 mm 1442 mm
11" 13���"
280 mm 340 mm
8" 11"
203 mm 280 mm
29����" 35���"
741 mm 895 mm
B
C
D
E
F
18���"
����"
E
D
G
J
37"
36"
��"
��"
J
�����"
����"
����"
��"
A
B
Outside
Air
Gas Line
Access
Fig. 2 CVR Series specifications and framing.
7412961
3
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
STR/CVR Series Woodburning Fireplace
Flue
Damper
Flue
Collar
Header
Standoffs
Outer Collar
Ledge
Brackets
Outer
Dome
Outer
Dome
Flue Damper
Control
(Inside)
Brick liner on
Sides and Hearth
Gas Line
Knock-out
(Both Sides)
Gas Line
Access
Outside Air
Control
Screen
Firebox
Hearth
Wood Grate
Air Inlet
Metal Safety Strips,
shown not in place
(1, 2, or 3 Pieces)
Outside Air Access
CVR Fireplace
STR Fireplace
FP701
Fig. 3 STR/CVR Parts Identification.
B
A
FP1545
Front/Back Width
A
Side Width
B
STR33
26"
17¹⁄₈"
(660 mm)
(435 mm)
STR/CVR36
STR/CVR42
29"
(737 mm)
17¹⁄₈"
(435 mm)
35"
17¹⁄₈"
(889 mm)
(435 mm)
Fig. 3a Hearth dimensions.
7412961
4
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Chase Installation
Insulation methods shown are optional
for cold climate, not a requirement for
unit operation.
Termination Cap
Storm Collar
Pan Flashing
Batt Insulation
(cut out around
firestop)
Draftstop
Firestop
Ceiling Level
Outer Dome
Refer to Figures 21
and 26 for clearance
information.
Finish Wall
Surround
Ledge Brackets
Nailing Flange
Gas Access
(both sides)
Screen
Outside Air Cover Plate
Grate
Firebox
Outside Air
Control
FP704
Fig. 4 Fireplace and chase parts identification.
7412961
5
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Chimney Requirements - Offset Installations
OFFSET
CHIMNEY FLUE EXIT
RISE
CHIMNEY
SECTION
FP282
30˚
ELBOW
RETURN
ELBOW
30˚ Elbow Offsets
B
G
A
G
1'
Offset
3"
8¹⁄₄"
3' 4'
Rise
1¹⁄₂'
0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
30˚
OFFSET
ELBOW
0
1
0
2
1
0
2
0
0
1
0
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
1
1
0
1
1
0
2
1
0
2
1
0
2
1
3
2
1
3
2
1
3
2
4
3
2
4
3
2
4
3
5
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
11"
20"
D
C
0
0
0
0
1
0
0
1
0
0
2
0
1
2
0
1
3
0
2
3
1
2
0
1
3
0
2
3
1
2
0
1
3
0
2
3
1
2
0
E
6 FT.
RISE
11¹⁄₄" 25¹⁄₄"
13¹⁄₂" 29¹⁄₄"
16¹⁄₂" 34¹⁄₄"
20¹⁄₄" 40³⁄₄"
21³⁄₄" 43¹⁄₂"
26¹⁄₄" 51¹⁄₄"
28¹⁄₂" 55¹⁄₄"
31¹⁄₂" 60¹⁄₄”
34¹⁄₂" 65¹⁄₂"
37¹⁄₂" 70³⁄₄"
41¹⁄₂" 77³⁄₄"
45" 83³⁄₄"
47¹⁄₄" 87¹⁄₂"
51"
53¹⁄₄"
56¹⁄₄" 103¹⁄₄"
59¹⁄₄" 108¹⁄₂"
62¹⁄₄" 113¹⁄₂"
64¹⁄₂" 117¹⁄₂"
68¹⁄₄"
70¹⁄₂"
74¹⁄₄" 134¹⁄₂"
78" 140³⁄₄"
81"
84" 151¹⁄₄"
87" 156¹⁄₂"
89¹⁄₄" 160¹⁄₄"
93" 166³⁄₄"
95¹⁄₄" 170³⁄₄"
99¹⁄₄" 177³⁄₄"
SKCS8
SUPPORT
30˚
RETURN
ELBOW
H
OFFSET
H
30˚
OFFSET
ELBOW
B
HEARTH
FLOOR
Example 1
Example 2
Example 3
Notes: G + H cannot exceed 20 feet.
FP720
94"
98"
Air Space Clearances:
SK8 (2-wall) = 1¹⁄₂" , and 11CF (2-wall) = 2"
Illustration Key
C. The chimney cannot be more than 30˚
(45˚ in Canada) from the vertical plane in
any installation*.
The following safety rules apply to
offset installations (letters correspond
with illustration above):
124"
128"
D. The maximum length of the angled run
of the total chimney system is 20 feet. (G
plus H cannot exceed 20 feet.)
A. Height of the chimney is measured
from the hearth to the chimney exit.
2
E. A chimney support (Models TCS8A or
11CS) is required every 6 feet of angled
run of chimney. Chimney supports are re-
quired for every 30 feet and 60 feet (SK8
& CF11 pipe) of vertical chimney height
above the hearth.
2
2
2
2
2
2
2
146"
CVR / STR Series
Maximum:
Minimum:
90'0"
Without Elbows
With 2 Elbows*
With 4 Elbows*
15'6"
17'6"
21' 0"
Determine the offset distance of your
chimney arrangement from the centerline
of the fireplace to the centerline of the
chimney where it is to pass through the
first ceiling.
B. Do not use more than 4 elbows per
2 101¹⁄₄" 181³⁄₄"
2 104¹⁄₄" 186¹⁄₄"
2 107¹⁄₄" 191¹⁄₂"
chimney.
Attach the straps of the return (top)
elbow to a structural framing member.
2
3
3
3
110¹⁄₄" 196³⁄₄"
114" 203¹⁄₄"
117³⁄₄" 209³⁄₄"
120" 213¹⁄₂"
NOTE: This offset distance may not be
your full offset distance. See Examples 2
and 3.
The offset (first) elbow of any pair does
not have straps.
* In Canada, two (2) SK845 are allowed.
3 123³⁄₄"
220"
Fig. 5 Chimney system requirements.
7412961
6
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Planning Information
Preplanning an installation is very important to ensure
safety and to save time and money. An installer must
predetermine where a fireplace will be set and how the
chimney system will be run.
The Ten Foot Rule
Major U.S. building codes specify a minimum chimney
height above the roof top. The “Ten Foot Rule” is a fire
safety rule and not a draft rule. To ensure proper draft,
it is recommended that you always meet or exceed the
“Ten Foot Rule,” especially when installing a termination
on a high pitch roof. (Fig. 7)
NOTE: STR33/36 and CVR36 models use CFM Cor-
poration SK8 (2-wall) chimney systems. STR/CVR42
Fireplaces use only model 11CF chimney system.
Mounting the Fireplace
The key points of the "Ten Foot Rule" are:
1. If the horizontal distance from the chimney to the
peak of the roof is 10' (3m) or less, the top of the
chimney must be at least 2' (610mm) above the peak
of the roof, but never less than 3' (914mm) in height
above the highest point where it passes through the
roof.
A fireplace may only be mounted on the following sur-
faces:
1. A flat combustible surface.
2. A raised wooden platform.
3. A concrete block or other solid object placed beneath
each of the four (4) corners of the fireplace.
2. If a horizontal distance from the chimney to the peak
of the roof is more than 10' (3m), a chimney height
reference point is established on the surface of the
roof a distance of 10' (3m) from the chimney in a
horizontal plane. The top of the chimney must be
at least 2' (610mm) above the reference point, but
never less than 3' (914mm) in height above the high-
est point where it passes through the roof.
The fireplace must be spaced 1/2" (13mm) from a com-
bustible back wall and 1/2" (13mm) from a combustible
side wall or support. (Page 14, Fig. 20)
Planning the Chimney Run
Determine how the chimney will be run, length of run
and chimney components required to complete the
job. (Fig. 6) Never install a chimney below minimum
heights.
0 To 10'
2' Min.
MODEL SK &
MODEL 11 CF
2 WALL CHIMNEY
TOTAL
LENGTH
INSTALLED
LENGTH
L
L
L
0 To 10'
3'
T
1
1
Min.
(L )
T
(L )
1
2' Min.
3'
SK81 / 11CF1
SK818 / 11CF18
SK83 / 11CF3
SK84 / 11CF4
�����
�����
�����
�����
"
"
"
"
�����
�����
�����
�����
"
"
"
"
Min.
Reference
Point
AC246
FP705
Fig. 7 Ten Foot Rule illustration.
Fig. 6 Installed lengths of chimney sections.
In planning a chimney system, it is important to know:
1. The height of a chimney is measured from the
hearth to the exit point on the termination.
2. A chimney cannot be offset more than 30° from a
vertical plane.
3. A chimney may run straight up or it may be neces-
sary to offset it to avoid obstructions.
4. The maximum length of an angled run (total chimney
system) is 20' (6m).
5. No more than 2 offsets (4 total 30˚ elbows in U.S./or
2 total 45° elbows in Canada) per fireplace may be
used.
6. A guy wire stabilizer is required for chimneys extend-
ing more than 6' (1.8m) above a roof line.
7412961
7
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Chimney Supports
Installation
The chimney system is supported by the fireplace for
vertical chimney heights less than 20' (6m) above the
hearth. Chimney supports are required if the vertical
height exceeds 20' (6m). Locate chimney supports
at ceiling holes or other structural framing at 20' (6m)
heights. Spacing between chimney supports must not
exceed 20' (6m). Use Chimney Support Model SKCS8
for SK8 chimney, and Model 11CS for 11CF chimney.
(NOTE: the chimney support can not be mounted
directly to the fireplace.) Support provided by elbow
straps fulfills the support requirement only if they are
spaced as previously described. (A chimney support is
2¹⁄₂" (64mm) long when installed.)
Insulating Fireplace Enclosure for Cold
Climates
If you live in a cold climate, it is not required but
highly recommended that you insulate fireplace
enclosure to eliminate cold air penetration as much
as possible.
Insulate base of fireplace with a non-combustible
insulation rated for a minimum of 300°F. Insulating
is very important for outside wall installations over
a concrete slab. If fireplace is installed on a platform,
insulation should be placed on top of the platform
before fireplace is set. (Fig. 9)
Angled chimney runs require a support every 6' (1.8m)
in addition to the elbow straps. Chimney supports are
used for this function. (Fig. 9)
When a fireplace is installed in a chase or on a
outside wall, enclosure should be treated like any
outside wall in a home. Insulation should be installed
on the inside wall as well as the outside wall(s). In
a chase, it is also a good idea to install a firestop at
the first ceiling level above the fireplace and enclose
the chase with sheeting material. Insulation may
then be installed above sheeting material to assure
the space around the fireplace is totally protected.
(Fig. 4)
Chase Installation
A chase is a vertical box-like structure which encloses
the fireplace and/or chimney. Chases are typically built
on the outside of the house with fireplace opening cut
into the outer wall of a room. (Page 5, Fig. 4)
If you need help in determining fireplace location or how
the chimney system should be run, contact your Majes-
tic dealer for assistance.
When installing the chimney, DO NOT caulk be-
tween outer pipe and firestop. It is vital that some air
be allowed to flow through this very thin gap.
CAUTION: WHEN INSTALLING A FIREPLACE
IN AN INSULATED ENCLOSURE, BE SURE ALL
REQUIRED AIR SPACES ARE MAINTAINED. (Page
14, Fig. 20)
Chimney Sup-
port Strap
SKCS8
FP284
Fig. 8 Chimney support installation
7412961
8
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Chimney Set-up
Framing
Since you have already preplanned the chimney run,
you should know exactly how the installation is to
be accomplished — how much pipe is required, the
number of elbows, if any, and type of termination to be
used.
Framing can be constructed before or after the fireplace
is set in place, however, most installers build the frame
before setting the fireplace.
Frame fireplace with 2 x 4 lumber or heavier materi-
als. Refer to framing dimensions in Figures 1, 2, 3 or 4
for basic fireplace specifications. Headers and support
studs must be turned on end as illustrated on Page 5,
Figure 4.
CAUTION: REPORT TO YOUR DEALERS ANY
PARTS DAMAGED IN SHIPMENT, SPECIFICALLY
CHECK THE END CONNECTION OF CHIMNEY SEC-
TIONS AND ELBOWS.
NOTE: Framing should be positioned to accommodate
wall covering and fireplace facing material. Maintain
1/2" (13mm) air space between the outer dome and
any combustible framing materials that may be sup-
ported by the ledge brackets. Refer to Figures 20
and 26 for details.
NOTE: STR33/36 and CVR36 models use CFM Cor-
poration SK8 (2-wall) chimney systems. STR/CVR42
Fireplaces use only model 11CF chimney system.
Straight-Up Chimney Installation
To locate the centerline of the flue put the fireplace in
final position and place a plumb bob from the ceiling to
the center of the fireplace flue collar. Mark this spot on
the ceiling. Draw a line through that mark to either side
of the firebox and indicate dimension X to locate the
side wall framing. (Fig. 10) Be sure to observe clear-
ance requirements for side and parallel combustible
walls as noted in Page 16, Figure 23.
Hard, Flat
Surface
Offset Installation
In order to clear an obstruction, it may be necessary
to offset chimney from vertical. This is accomplished
by using CFM Corporation elbows. Use the 30° Offset
Elbow table on Page 6 to determine proper offset and
parts required.
Each offset requires two (2) elbows. The second elbow
is equipped with support straps. It is very important to
install the second elbow in each offset as close to the
ceiling or support as possible so that the elbow straps
can be secured to framing members to help support the
weight of the chimney.
Insulation
Plateform
FP706
Determine offset distance of your chimney arrangement
from centerline of fireplace to centerline of chimney
where it is to pass through ceiling.
Fig. 9 Insulating between platform and fireplace.
Locate center point of the chimney on ceiling as though
a straight up chimney arrangement is to be used.
Measure your offset dimension from the chimney center
point on the ceiling.
7412961
9
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Actual Centerpoint
Framing the Ceiling Hole
Chimney
Centerline
Frame the ceiling chimney hole as shown in Figure
12. It is good practice to use framing lumber that is the
same size as the ceiling joists; this is a requirement at
attic level.
X
Side of
STR/CVR
The following table gives firestop spacer model num-
bers:
Plumb Line
Plumb Bob
Angle of Chimney at Ceiling
Size of Chimney
8" Flue
Vertical
SKFS2A
14¹⁄₂" x 14¹⁄₂"
30°
SKFS6A
14¹⁄₂" x 25¹⁄₂"
Imaginary
Centerpoint
"SK" Series
(368mm x 368mm) (368mm x 648mm)
FS2A
FS6A
11" CF 2-Wall
17¹⁄₂" x 17¹⁄₂"
17⁷⁄₈" x 29⁵⁄₈"
(445mm x 445mm) (454mm x 753mm)
Fig. 11 Ceiling chimney hole sizes necessary for installing
firestop spacer.
The inside dimension of the frame must be the same
as the hole size selected from Figure 12 in order to
provide the required air space (1¹/₂" (38mm)with SK8,
2" (51mm) with Model 11CF) between the outside
diameter of the chimney and the edges of the framed
MODEL
X =
STR 33: 19" (483mm)
STR36 / CVR36: 20�/�" 521mm)
STR42 / CVR42: 23�/�" (597mm)
ceiling hole.
FP707
Existing
Ceiling
Joists
A/B
A/B
Fig. 10 Locate centerline of chimney with plumb line.
Chimney Hole
Ceiling Chimney Hole/
Possible Obstructions
The size of the hole in ceiling will vary with the angle at
which the chimney passes through ceiling.
Drive a nail up through ceiling at marked chimney cen-
ter point. Go to floor above and see where hole will be
cut. Check to see where existing ceiling joists and other
possible obstructions are located...i.e. wiring, plumbing
etc... If necessary, re-position chimney and/or fireplace
to avoid obstructions.
New Framing
Members
A "SK8" Series framing = 14���" X 14���" (368 x 368mm)
B 11CF framing = 17���" X 17���" (445 x 445mm)
Cutting the Hole
FP551A
Cover fireplace collar opening and cut proper sized
chimney hole in chimney. The SK8 pipe allows you to
run pipe through a typical 16” on center joist without
cutting joists.
Fig. 12 Typical frame for ceiling chimney hole.
7412961
10
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Positioning, Safety Strips,
Securing the Fireplace
Slide fireplace into position.
Lift the fireplace front slightly and slide the metal safety
strips under front bottom edge about 1¹⁄₂" (38mm), al-
lowing the remainder to extend in front of firebox. Over-
lap strips at least 1/2" (13mm) to provide a positive joint.
(Flat safety strips are packed with fireplace.) (Fig. 13)
Metal Safety
Strips
(1, 2 or 3 pieces)
Safety strips are used to ensure that any combustible
materials in front of the fireplace are protected even
though a noncombustible hearth extension is required.
If fireplace is to be elevated above the floor, a “Z”
shaped metal safety strip must be fabricated and used
to protect combustible surfaces in front of the fireplace.
This “Z” shaped safety strip is not provided but must be
fabricated of metal with each horizontal leg at least 1¹⁄₂"
(38mm) wide and equal in length to the metals strips
provided with the fireplace.
"Z"
Safety
Strip
(not supplied)
Fire-
Place
���" (13mm)
Min. Overlap
Plat-
Form
Hearth Ext.
����"
(38mm)
FP708
Fig. 13 Safety strip installation.
NOTE: Safety strips are not required over non-com-
bustible floors where all supports at the base of the
fireplace are noncombustible.
Eight (8) nailing flanges are supplied with the fireplace
(found on the fireplace hearth). To level the box and
secure it firmly in place, remove the nailing flanges from
the hearth and install at the sides of the fireplace as
shown in Figure 14.
Standoffs
Side-Nailing
Flanges
Outside Air Kit
An outside air kit damper is installed in all STR/CVR
Series Fireplaces. If desired, or if local codes mandate
the use of an air kit, then an AK-MST is required to
complete the installation (from air kit to the outdoors). If
the outside air kit is to be used, the AK-MST Air Ter-
mination Kit MUST be installed BEFORE the fireplace
is enclosed. Refer to the AK-MST instructions for field
installation. The outside air kit control is located in the
lower left hand side of the fireplace behind the screen
panel. (Fig. 15) To operate, simply lift up to close or
push down to open .
Model STR
FP709
Fig. 14 Fasten fireplace in position.
CLOSED
OPEN
FP710
Fig. 15 Outside air operation.
7412961
11
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Installing the Chimney System
Pipe Section
Start by attaching the first chimney section to the collar
on top of the fireplace.
Pipe Rim
Install the pipe as pictured in Figure 16. When you
get a good lock, you will hear the pipe clearly snap
together. Once sections are snap-locked in place, it is
extremely difficult to get them apart. Make sure the
pipe is firmly snapped and locked together as each
pipe section is mounted.
Hem
Lance
Pipe
Rim
When installing elbows, only outer pipe will snap-
lock. Middle pipes simply slide into position. Be sure
to always attach straps on upper elbow to a structural
framing member. (Fig. 17)
Continue installing the pipe as required until pipe is
installed up through the ceiling. At this point, you must
install a firestop spacer. Refer to Figure 18 for appropri-
ate spacer orientation.
FP711
Fig. 16 Install pipe, listening for the snap-lock to fasten.
Installing the Firestop Spacer
in the Ceiling Hole
Elbow Strap
Support Structure
A firestop spacer is used to keep pipe spaced properly
and required for safety.
Nail the firestop spacer (at each corner) to the framing
members of the ceiling hole. NOTE: A firestop spacer
is not required at the roof.
Elbow Strap
(must be tight)
Ceiling
Hole Fram-
ing
Hole sizes listed in Figure 12 for angled firestop spac-
ers provide minimum required air space to chimney
pipe for ceiling thickness up to 8" (203mm). When
combined thickness of ceiling material, ceiling joists
and flooring material exceeds 8" (203mm), adjustments
must be made in framing to assure that minimum air
spaces to chimney are maintained.
Angle Firestop
Angled Strap
Chimney Support
Strap
(must be tight)
Proper Firestop Spacer Installation
FP270/271
Fig. 17 Attach straps to a structural framing member.
Figure 18 shows different installation procedures for
both an area that is an attic and an area that is not an
attic.
If the area above the ceil-
Attic Installation
Ceiling Installation
ing is not an attic, posi-
tion the firestop spacer
with the flange on the ceil-
ing side and the angled
portion extending up into
the hole.
Nails (4)
Joist
Firestop
Spacer
If the area above the
Firestop
Spacer
ceiling is an attic, position
the firestop spacer with
the flange on the top of
the framed hole and the
Joist
Nails (4)
angled portion extending
FP593
down into the hole.
Fig. 18 Installing firestop spacer.
7412961
12
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Firestop spacers are not available for nor are they re-
quired on vertical walls.
Attic Insula-
tion Shield
DO NOT put any sealant around the area where the
outer pipe slides through the firestop spacer. If you
seal this area, it may cause a fire hazard.
Nails
(4 required)
Canadian Requirements
for Insulation Shield
In Canada, an attic insulation shield is required to pre-
vent attic insulation from contacting the chimney sec-
tion. Framing dimensions for the chimney hole should
measure 14¹⁄₂" x 14¹⁄₂" (368 x 368mm)(SK8). (An attic
shield MUST be installed on top of attic joists (above
the floor level). Refer to Figure 19.
Attic Joist
Base
Flanges
Ceiling
Model 11CF chimney is not approved
for use in Canada.
Install the attic insulation shield with the flanges on its
base extending down into the framing hole. Nail each
corner of attic insulation shield to the framing members
of the ceiling hole using 8d nails. Attic shields are not
required at the roof.
FP263
Fig. 19 Attic shield installlation (Canadian requirement).
Locate Chimney Centerpoint on Roof
Continue Installing Pipe to Complete Run
Use same procedure detailed in locating centerpoint of
the flue system.
Continue attaching pipe sections to complete system
to next level always being careful that the pipe is firmly
snapped locked in place before proceeding to next pipe
section.
Drive a nail up through roof at the centerpoint. This will
determine center point on outside of the roof.
Cut and Frame Roof Hole
Chimney Supports
Size of roof hole varies with the type of chimney termi-
nation installed. Refer to installation instructions pro-
vided with the chimney termination to find correct size
of roof hole.
If chimney supports are required, they are installed the
same as elbows. Nail chimney support straps to ad-
jacent structural framing, as shown on Figure 8, Page
8. Bend straps as necessary and make sure they are
secure so they will support the weight of the chimney.
A chimney support is 2¹⁄₂" (64mm) long when installed.
Consider this dimension when determining how many
straight chimney sections are needed.
NOTE: The air space dimensions in this manual
that pertain to model 11CF chimney pipe have been
changed from 2" to 1" (51 - 25mm) clearance for first
joist space only. This change only applies to Majes-
tic Fireplaces models STR42 and CVR42 fireplaces.
Because of framing concerns these models, and only
these models, have been tested and approved at the
reduced clearance. In all other cases the minimum air
space referred to on the UL label on the 11CF pipe
must be maintained. A special firestop is shipped with
these units that will maintain the 1" (25mm) clearance
at the first joist. The chimney hole size for this firestop
will be 15¹⁄₂" (394mm). Refer to Figure 18 for ceiling
joist installation instructions.
NOTE: Chimney supports are generally used in long
runs in a chase installation. A chimney support can-
not be mounted directly to the fireplace.
Additional Ceilings
If you encounter additional ceilings, repeat same steps
required for first ceiling installation. Refer to firestop
illustration on Page 12, Figure 18.
Penetrating the Roof
There must be an air space (1¹⁄₂" (38mm) with SK8 and
1" (25mm) with 11CF) between outermost portion of
chimney sections and any adjacent combustible sur-
faces. (Fig. 20) (Combustible surfaces include burnable
materials such as: ceiling members, joists, flooring,
combustible insulation and roof structures.)
Run pipe to roofline. Since chimney system must be
vented to the out-of-doors, you must use an approved
termination.
If a chase is used, refer to the installation manual pro-
vided with the termination cap.
7412961
13
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
WARNING: DO NOT PACK REQUIRED AIR SPACES
WITH INSULATION OR OTHER MATERIALS.
Air Space Clearances
Mark an outline of the roof hole around the center of the
point nail. NOTE: Hole dimensions given in the chim-
ney top installation instructions are horizontal dimen-
sions; therefore, the hole size must be marked on the
roof accordingly.
Combustible framing material MUST NOT
penetrate AIR SPACE (shaded areas).
1���" (38mm)
������
������
1"
Cover the opening of the installed chimney so debris
cannot get into the system.
(51mm)
�����������
����
Standoff
Cut and frame the hole. It is good practice to use fram-
ing lumber that is the same size as the rafters. Install
the frame securely because the chimney top and flash-
ing anchored to the frame must be able to withstand
heavy winds.
�Maintain
����" (13mm)
air space
to sides
���" (13mm) air space
to sides
Front View
Side View
Install Remainder of Chimney Sections
Since you have already preplanned the height of your
termination according to the Ten Foot Rule, continue to
install pipe to the predetermined height.
Firestop
Wall
Shield
Check the chimney top installation instructions for
details on how high above the roof top the chimney sec-
tions (all pipes) should extend.
Installing Top Housing or Termination
���" (13mm)
Follow the installation instructions provided with the
chimney termination you have selected.
Air Space
to Sides
Installing Chimney In a Chase
Refer to Page 5, Figure 4 for an illustration of a typical
chase installation.
CAUTION: Treatment of firestop spacers and construc-
tion of chase may vary with type of building. These
instructions are not a substitute for local building codes.
You must check your local building codes to determine
specific requirements for your city or state. NOTE:
Other building materials may be required in addition to
Firestop Spacers.
0" Clearance
to Floor
Hearth
Extension
Only noncombustible
material may be applied
as facing to the black
fireplace surround.
FP717
Fig. 20 Minimum clearances to combustibles.
rial is used below a flat mantel shelf, consult your local
building codes for minimum clearance from top of fire-
place opening to bottom of mantel shelf.
Finishing
CAUTION: All joints between the finished wall and the
fireplace surround (top/sides) must be sealed with non-
combustible material to prevent cold air leakage into the
room. Only noncombustible material may be applied
to the facing of the fireplace surround. (Black painted
area) (Fig. 20)
NOTE: No side wall protection is required for fireplaces
installed at 45° to two (2) side walls (corner installation).
Adjacent combustible side walls that are within 16"
(406mm) (STR33/36 and CVR36) and 20" (508mm)
(STR42 and CVR42) of fireplace opening must be pro-
tected with CFM Corporation Wall Shield Model SP40
or a specifically built wall shield described in Figure 20
& 24.
Finish Wall
Finish the wall with material of your choice. Do not
install a combustible mantel shelf less than 12"
(305mm) above the front opening. Do not install a
mantel face plate less than 6" (159mm) from top of
fireplace opening. (Fig. 21) If a combustible mate-
Often a decorative surround or vertical portion of the
mantel is desired. If this is constructed of any combus-
tible material, it must be within the safe zone indicated
in Figure 24.
7412961
14
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Mantel Clearance -
No Noncombustible Facing Material
Mantel Clearance -
with Noncombustible Facing Material
Finished Wall
Standoff
12"
(305mm)
Max.
Finished Wall Combustible
Combustible
Mantel and Trim
12"
(305mm)
Max.
Mantel and Trim
Standoff
1/2"
1/2"
2 x 4 Stud
2 x 4 Stud
12"
(305mm)
Min.
12"
(305mm)
Min.
Noncombustible Mate-
rial
Noncombustible Mate-
rial
Header
Ledge Bracket
Header
Ledge Bracket
Noncombustible Facing Material
6'
Fireplace
Front
Fireplace
Front
(159mm)
Min.
*
Fireplace Opening
Fireplace Opening
* Minimum width from top of sur-
round to bottom of screen rail
���"
2 x 4 Stud
Finished Wall
Must be sealed with
noncombustible material
Fireplace
Front
FP721
Fig. 21 Fireplace surround flush with finished wall.
Face Plate
*
1���"
Ref.
* *
Combustible materials are
permitted within a shaded area
shown in Figure 23, titled
Minimum Wall Clearances.
*12" (305mm) from top of fireplace opening.
** 6" (159mm) from top of fireplace opening.
(Noncombustible material must separate the
black face surround of the fireplace and any
combustible mantel material)
MA81
Fig. 22 Combustible mantel clearances.
7412961
15
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Side Wall Protection
Examples of wall shield insulation:
All joints (top, bottom and sides) where wall or deco-
rative facing material meets fireplace surround must
be completely sealed with a noncombustible material.
(Figs. 20 and 24)
1. Manville - CERAFORM 126, K=.27,
1/2 inches thick
2. CFM Corporation - EH2416, K = .458,
1 inch thick required.
The special wall shield design described in Figure 20 is
an alternate method of adding protection to side walls
and can be used in place of the SP40 with the same
wall clearances specified for the SP40. Rt must =1.85
minimum.
Minimum Dimensions to Side Walls
(for on-site contruction)
Model
STR33
44"
(1118mm)
16"
(406mm)
1/2"
(13mm)
--
STR36
44"
(1118mm)
16"
(406mm)
1/2"
(13mm)
--
STR42
44"
(1118mm)
20"
(508mm)
1/2"
(13mm)
--
CVR36
44"
(1118mm)
16"
(406mm)
1/2"
(13mm)
36"
CVR42
44"
(1118mm)
20"
(508mm)
1/2"
(13mm)
36"
Parallel Side Wall
to Movable Doors
Perpendicular
Side Wall to Firebox Opening
Air Space to Sides
or Back of Unit
A
B
C
D
End Panel Parallel
to End of Unit
(914mm)
(914mm)
Perpendicular Side Wall
Perpendicular Side Wall
B
C
B
C
C
D
A
A
Parallel Side Wall
Parallel Side Wall
CVR Series
STR Series
FP723
Fig. 23 Minimum firebox dimensions from combustible materials.
7412961
16
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Minimum Hearth Extension Dimensions
(for On-Site Construction)
Minimum Wall Clearances
STR
WITH
WITHOUT
Noncombustible
Surround Facing
Noncombustible
Surround Facing
Shaded area starts
CVR
G
G
4" BRICK
(Example material)
1/2" away from
edge of unit
4"
H
G
G
H
J
J
Firebox
Opening
E
E
D
F**
Seal cracks
between the
fireplace
and hearth
extension with
noncombustible
material
A - Min. clearance
to combustible
perpendicular wall
C**
May install
noncombustible
decorative
covering
OR .018" min.
sheet metal
Side
Wall
Side
Wall
B - Min. clearance
to combustible
perpendicular wall when
Fireplace
Hearth
using noncombustible wall shield*
Combustible material permitted within shaded area.
Noncombustible wall shield requires 1" CFM Corporation
EH2416 insulation (minimum R Value = 1.85) between
decorative noncombustible rigid covering and combustible wall.
Minimum height and width is 40" x 40".
Dimension/degree of angle will vary depending on thickness
of noncombustible surround facing.
4" MIN.
*
Minimum
Insulation
Value "R"
Safety strips
must overlap
���" minimum
Combustible
Floor
**
A
B
C
D
E
F
G
H
J
K
STR33/36 CVR36
16"
12"
48° 41°
18"
14"
8"
16"
48"
24"
(406mm) (305mm)
20" 12"
(508mm) (305mm)
(457mm) (356mm) (203mm) (406mm) (1219mm) (610mm)
18" 14' 12" 20" 61¹⁄₂" 24"
(457mm) (356mm) (305mm) (508mm) (1562mm) (610mm)
STR42 CVR42
42° 35°
FP714
Fig. 24 Combustible side wall protection and hearth extension dimensions.
WARNING: HEARTH EXTENSION MUST BE IN-
STALLED IN ACCORDANCE WITH FIGURES 24 AND
25.
Hearth Installation
A hearth extension is required to protect a combustible
floor in front of the fireplace. Refer to Figure 24 for mini-
mum dimensions and mounting detail.
Alternate noncombustible materials may be used
providing the (total) thermal resistance (Rt value) of the
alternate material employed is greater than or equal to
R = 1.09. Thermal resistance (R) or thermal conductivity
(K), may be obtained from manufacturer of the material.
Factors are related by the formula K = 1/R.
Note: Hearth Extension must not cover the air inlet
opening of a fireplace.
The hearth extension described in Figure 24 must be a
durable noncombustible material with a minimum (total)
Rt value of 1.09; refer to Figure 25 for examples. The
overall height (above a combustible floor), depth and
width must be as indicated, with the extension centered
to the fireplace opening.
T = given thickness
R = thermal resistance for a given thickness (T)
K = thermal conductivity
Noncombustible material with a lower R value may
be used, provided thickness of material is sufficiently
greater to maintain an equivalent (total) thermal resis-
tance (Rt).
The top of the insulation material must be covered with
a noncombustible decorative covering or a piece of
.018” minimum sheet metal, to protect hearth extension
material. (Fig. 24)
Secure the hearth extension to the floor to prevent
shifting, using trim molding or other similar means at
three (3) outer edges. Seal crack between the fireplace
hearth and hearth extension with a noncombustible
material. (Figs. 24 and 26)
7412961
17
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Example of Determining Hearth Extension
Equivalents
To determine the thickness required for any new mate-
Seal Cracks Between Fireplace and Hearth
Extension with Noncombustible Material
rial:
Noncombustible
Material 7¹⁄₂"
Lower Surround
NEW
required
thickness
K of new material (per inch)
K of listed material (per inch)
thickness
of listed
material
Noncombustible
Material
Max. Thickness
Fireplace
Hearth
=
X
Combustible
Floor
Example for Common Brick
T (new) = 5.0 / 0.458 x 0.50 in. = 5.46 in. (new required
thickness).
1/4" Min. Thickness
Majestic Safety
Strips Must be
Overlapped 1/2"
Min.
Minimum Insulation
Value R-0.94
FP1170
COMMON MATERIALS AND FACTORS
Fig. 27 Hearth extension dimensions.
MINIMUM
THICKNESS
R
MATERIAL
K*
Recessed Installation - STR33/36, CVR36 Only
EH2416
�����������������
1.09 0.50 in.**
0.458
Noncombustible
Material
(if desired)
Minimum
36” (914 mm)
A
Common Brick
0.10 5.46 in.**
5.0
Insulation
R Value is for ��� inch.
* Units of K = BTU/SQ FT/HR/˚F/IN
** Thickness of Listed Material
with Minimum
6”
R Value
(152 mm)
Minimum
of 2.75
Minimum
33”
(838 mm)
FP533AD
Fig. 25 Hearth extension material factors.
2”
2”
(51 mm)
2x4"
Stud
(51 mm)
Hearth Extension
Wall Covering
A
Noncombustible
Decorative
Facing
�/�"
Minimum .030 Thick Stain-
less Steel Plate
�/�"
Outer Dome
Insulation with Minimum R
Value of 2.75
Seal all cracks
between fireplace
surround and wall
materials with
noncombustible
material.
NOTE: �/�"
air space
between
Outer Dome
and
Minimum .030
Thick Stainless
Steel Plate
Maximum
10”
(254 mm)
2x4" Header -
Do not notch at
standoffs.
combustible
materials
Noncombustible
Decorative
Covering
Seal crack
Maximum
14”
(356 mm)
between fireplace
and hearth extension
with noncombustible
material.
Hearth Extension
Insulation
Hearth
Extension
FP1608
Side View
View A
Safety Strips -
Must be overlapped
���" minimum.
NOTE: If noncombustible material is not used between the
stainless steel plate and fireplace opening, the steel must
be attached to the front of the unit a minimum of four (4)
places on each piece with sheet metal screws no longer
than 1/2".
FP719
Fig. 26 Finish wall treatments and gap sealing.
NOTE: The size of the insulation and stainless steel
plate must be within limits stated above and covers all
combustible framing material.
Fig. 28 Recessed installation.
7412961
18
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Installing Line for Gas Logs
Fireplace Top View
Majestic Fireplaces are designed to accept a 1/2"
(13 mm) gas line for installation of an approved gas ap-
pliance. (CFM Corporation manufactures a wide variety
of gas logs for use in Majestic fireplaces.)
Hole in
Outer
Supply Line
1"
Casing
Gas Line
Tube
Repack Insu-
lation
Be sure to have the appliance installed in accordance
with building codes.
Gas connection may enter from either left or right side
of the fireplace.
Locate appropriate gas line in the outer casing of fire-
place and remove insulation from gas line tube. (Fig. 29)
Ceramic
Knockout
From inside the fireplace, locate the knockout on the
firebrick -- be sure you are on the appropriate or "gas
line" side of the fireplace. Using a flat bladed screw-
driver or small chisel and hammer, carefully tap around
the knockout until it loosens and falls out.
Hole in
(Both Sides
on STR)
Outer Cas-
ing
Install 1/2" (13 mm) certified gas pipe through opening.
After gas pipe installation is complete, use insulation
that was removed from gas line tube to repack space
around the pipe. Material should be inserted from
outside of the fireplace and packed tightly to totally seal
between the pipe and tube.
FP716
Fig. 29 Gas line access.
CAUTION: WHEN USING DECORATIVE
GAS APPLIANCE, FLUE DAMPER MUST
BE SET IN FULLY OPEN POSITION. IF YOU
HAVE GLASS DOORS ON THE FIREPLACE,
THEY MUST ALSO BE FULLY OPENED.
NOTE: Gas pipe should not come in contact with
any wood structures until it has reached a point at
least 1" (25 mm) away from fireplace side.
Note: Local codes may require removal of flue damper
when installing any type of gas appliance in a fireplace.
WARNING: DO NOT OPERATE AN
UNVENTED GAS LOG SET IN THIS FIRE-
PLACE WITH THE CHIMNEY REMOVED.
NOTE: When installing an ANSI Z21.11.2 ventless ap-
pliance, the fninshing material used for the mantel must
be rated at 250°F or greater.
WARNING: WHEN INSTALLING AN
UNVENTED GAS LOG SET, THE CFM
CORPORATION MODEL AH3244BK OR
AH3244PB 4" ADJUSTABLE HOOD MUST
BE USED.
BTU input of a gas appliance installed in fireplace
should be rated less than 100,000 BTU/Hr.
Gas pipe installation is intended for connection to a
decorative gas appliance only when (1.) incorporating
an automatic shutoff device and (2.) complying with the
Standard for Decorative Gas Appliances for Installation
in Vented Fireplaces (ANSI Z21.60) or CSA draft re-
quirements for Gas-Fired Log Lighters for Woodburning
Fireplaces (Draft No. 4, August 1993).
Decorative gas appliance should be installed in accor-
dance with the National Fuel Gas Code, ANSI Z223.1/
NFPA 54 (latest edition).
If installing an unvented gas log set, refer to statement below:
Only unvented gas log sets which have been found to comply
with the Standard for Unvented Room Heaters, ANSI Z21.11.2,
are to be installed in this fireplace.
7412961
19
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
1, 2, 3
4a
4b
d
e
b
5a
7
6
a
8
9
c
13
5b
12
10
11
14
961
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
without notice.
CVR36/42 SERIES
Ref. Description
CVR36
RP102
CVR42
RP161
1. Flue Damper
2. Damper Actuator
7548170
7512903
3030126
7554342
7554338
7554340
5584139
3102103
3102102
3101104
3079147
3079148
3079130
7512135
3080145
20000399
5069164
2056100
20003212
7548169
7512903
3032112
7554342
7554340
7554340
5584139
3101105
3101103
3101104
3079147
3079148
3079130
7512135
3080145
20000399
5069164
2058100
20003212
3. Damper Handle Push Nut
4a. Screen Rod Assembly - Side (two per fireplace)
4b. Screen Rod Assembly - End
5a. Screen Assembly - Side (four per fireplace)
5b. Screen Assembly - End
6. Screen Pulls (four per fireplace)
7a. Firebrick - Hearth
7b. Firebrick - Side Ash Lip (two per fireplace)
7c. Firebrick - End Ash Lip
7d. Firebrick - Side
7e. Firebrick - Side Filler (two per fireplace)
8. Top Brick Retainers (two per fireplace)
9. Cable Clips (twelve per fireplace)
10. End Panel (Glass and Extrusion)
11. Tempered Glass (two per fireplace)
12. Nailing Flange (four per fireplace)
13. Basket Grate
14. O.S.A. Assy.
7412961
20
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
1, 2, 3
4
d
c
5
7
b
8
a
6
9
11
10
12
61
CFM Corporation reserves the right to make changes in design, materials, specifications, prices and discontinue colors and products at any time,
without notice.
STR33/36/42 SERIES
Ref. Description
STR33
RP102
STR36
RP102
STR42
RP161
1. Flue Damper
2. Damper Handle
7548170
7512903
3049122
7554338
5584139
3100103
3100102
3079147
3079148
3079130
7512135
5069164
2056100
20003212
7548170
7512903
3030126
7554338
5584139
3102103
3102102
9079147
3079148
3079130
7512135
5069164
2056100
20003212
7548169
7512903
3032112
7554340
5584139
3101105
3101103
3079147
3079148
3079130
7512135
5069164
2058100
20003212
3. Damper Handle Push Nut
4. Screen Rod Assembly (two per fireplace)
5. Screen Assembly (four per fireplace)
6. Screen Pulls (four per fireplace)
7a. Firebrick - Hearth
7b. Firebrick - Side Ashlip (two per fireplace)
7c. Firebrick - Side (two per fireplace)
7d. Side Filler (four per fireplace)
8. Top Brick Retainers (four per fireplace)
9. Cable Clips (eight per fireplace)
10. Nailing Flange (eight per fireplace)
11. Basket Grate
12. O.S.A. Assy.
7412961
21
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Accessories
The following accessories for this appliance are available from your local Majestic Fireplaces distributor. Should you
need additional information beyond what your distributor can furnish, contact: CFM Corporation, 2695 Meadowvale
Blvd., Mississauga, Ontario, Canada L5N 8A3, Attn: Technical Services.
CAUTION: This fireplace and chimney assembly is a highly engineered system, and, as such, must be oper-
ated only with CFM Corporation approved components. If you use an unapproved component to make any
modifications, you may create a possible fire hazard and will void the CFM Corporation warranty. In addition,
such action may void the coverage provided by the owner’s insurance.
Accessory
Description
Model Number
Glass Door
Bi-Fold door set
Brushed Brass finish
33GDKBB - STR33
36GDKBB - STR36, CVR36
42GDKBB - STR42, CVR42
Black finish
33GDKBK - STR33
36GDKBK - STR36
42GDKBK - STR42
Polished Brass finish
Pewter finish
33GDKDP - STR33
36GDKDP - STR36
42GDKDP - STR42
33GDKS - STR33
36GDKS - STR36, CVR 36
42GDKS - STR42, CVR42
Outside Air Termination
Hearth Extension Insulation
Basket Grate
Completes connection from air kit to
out-of-doors
AK-MST
EH2416
Provides hearth extension floor
protection
Holds firewood in firebox
RBG36ST (33" & 36" models)
RBG42ST (42" models)
Hearth Patch Compound
Patch cracks in hearth
HPC-1
Contact your Majestic Fireplaces distributor or dealer for finishing
Marble and Mantels, available in a wide selection of styles.
7412961
22
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
Chimney Components
U.S.
Component
Description
Model Number
Round Top Termination Round termination to be used with SK8 chimney
system. (Flashing not included.)
RLTSK8
Round Top Termination Round termination to be used with 11CF chimney
system. (Flashing not included.)
RLTCF11
RLTSK8L
RLTCF11L
PKDSBL
Long Round Top
Termination
Round top to be used with a chase installation
utilizing SK8 chimneysystem.
Long Round Top
Termination
Round top to be used with a chase installation
utilizing 11CF chimney system.
Knock-down Shroud -
Pyramid
Black pyramid knock-down shroud used for
chase installations with any RLT round top
termination. Gives appearance of a pyramid cap.
Knock-down Shroud -
Square
Black square knock-down shroud used for
chase installations with any RLT round top
termination. Gives appearance of a square cap.
SKDSBL
Adaptor required
T20B
Square Termination
Adapter
Top housing with simulated brick pattern.
(Red, Tan or Black) Proper adapter must be
used. Includes flashing.
Required adapters for T20B top housing.
CF8CA (SK8)
8CA (11CF)
Housing Extensions
Flashing
Extends Square Termination on steep pitched roofs. 202036
Metal finishing required around Contemporary
Termination to prevent rain leakage.
8-6-12 with 8" flue:
0-6/12 pitch
8-12-12 with 8" flue:
6/12-12/12 pitch
Square Termination
Top housing of simulated brick pattern
available in red, tan or white. Appropriate
adapter required. Flashing included.
T20B
SK8
Pipe used to build 8" SK8 flue systems.
SK81 (1' Long)
SK818 (1¹⁄₂' Long)
SK83 (3' Long)
SK84 (4' Long)
Chimney Sections
11CF Chimney Sections Pipe used to build 11" (11CF) flue systems.
11CF1 (1' Long)
11CF18 (1¹⁄₂' Long)
11CF3 (3' Long)
11CF4 (4' Long)
Chimney Elbows
Elbow used to create an offset in a
SK830 / 2 (SK8)
chimney system. Only 30˚ elbows available.
Packaged 2 per carton (offset and return).
11CF30 / 2 (11CF)
7412961
23
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
U.S. Chimney Components, cont'd.
Component
Description
Model Number
Firestop
Required at each floor level of chimney
installation. (Plus attic on multi-story installation.)
SKFS2A — SK8
(8" straight flue)
SKFS6A — SK8
(8" 30˚ inclined flue)
FS2A (Model 11CF)
(straight flue)
FS6A (Model 11CF)
(30˚ inclined flue)
Chimney Support
Used to support chimney for each of: 20' vertical
height and 6' of angled chimney run.
SKCS8 - SK8
11CS - 11CF
Canada
Description
Model Number
Component
Attic Insulation Shield
Used to prevent insulation from coming in
contact with the chimney system.
Used to build chimney systems exposed above
roof.
AIS-SK - SK8
SK8 Chimney Sections
SK818CAN (1¹⁄₂') SK8
SK84CAN (4') SK8
45˚ Chimney Elbows
Provides 45˚ offset and return. FOR CANADIAN
INSTALLATIONS ONLY. For use with
SK845/2
SK8 chimney only. (Maximum use of 2, or 1pair.)
7412961
24
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
7412961
25
Download from Www.Somanuals.com. All Manuals Search And Download.
STR/CVR Series Woodburning Fireplaces
7412961
26
Download from Www.Somanuals.com. All Manuals Search And Download.
LIMITED WARRANTY & 30 YEAR PROTECTION PLAN
For MAJESTIC FIREPLACES® PRE-ENGINEERED Fireplace Systems
operated at all times under normal conditions, use and service
according to the operative instructions furnished with the Fire-
place, and only if and so long as the Fireplace is not removed
from its original installation.
(2) This warranty is non-transferrable, and is made to the
original owner, provided that the purchase was made through
an authorized supplier of the Company.
(3) The sole and exclusive remedies for breach of any war-
ranties hereunder shall be for the repair, replacement or provi-
sion of a replacement part at CFM Corporation then current list
price, FOB CFM Corporation factory, for any defective part as
specified in paragraphs A through D.
(4)CFM Corporation shall not be liable for damage from any
smoking of a MAJESTIC FIREPLACES Pre-Engineered Fire-
place System related to environmental geographic conditions
(such as, for example, nearby structures or roof peaks, trees,
hills, or mountains), inadequate ventilation, or negative air
pressure in the place where the Fireplace system is installed,
related to any mechanical system (such as, for example, fur-
naces, fans, air conditioners, clothes dryers, etc.)
(5) Except as otherwise expressly specified in paragraphs
A through D, NONE OF THESE WARRANTIES COVER, AND
CFM CORPORATION SHALL NOT BE RESPONSIBLE FOR,
ANY CONSTRUCTION, INSTALLATION, LABOR, TRANS-
PORTATION OR OTHER COSTS OR EXPENSES ARISING
FROM A DEFECTIVE PART, ITS REPAIR OR REPLACEMENT
OR OTHERWISE, NOR SHALL CFM CORPORATION IN ANY
EVENT BE RESPONSIBLE FOR ANY INDIRECT, INCIDENTAL
OR CONSEQUENTIAL DAMAGES EXCEPT TO THE EXTENT
REQUIRED BY LAW. Some states do not allow the exclusion
or limitation of incidental or consequential damages, so this
exclusion or limitation may not apply to you.
CFM Corporation warrants its MAJESTIC FIREPLACES®
Pre-Engineered Fireplace (“Fireplace”) and the CFM Corpora-
tion supplied firegrate, glass doors, outside air system, fan mo-
tor, and liners to be free from defects in material or workman-
ship, as follows:
A. Fireplace and Chimney Components: (exclusive of CFM
Corporation-supplied firegrate, glass doors, outside air sys-
tem, fan motor, and liners all of which are covered by separate
warranties under paragraphs B through D below): At its option
for a period of thirty (30) years from the date the Fireplace is
installed, CFM Corporation will;
(1) For a period of five (5) years from the date the Fireplace
is installed, CFM Corporation, at its option, will repair or replace
any defective part without charge.
(2) Thereafter, through the 10th year after the date the
Fireplace is installed, if replacement parts are available, CFM
Corporation will provide a replacement for any defective part
without charge for the part itself. The consumer must pay for
everything else other than the part.
(3) Thereafter, through the 30th year after the date the
Fireplace is installed, if replacement parts are available,CFM
Corporation will provide a replacement for any defective part
at a cost to the consumer of CFM Corporation then current list
price, FOB CFM Corporation factory.
B. Firegrate, Glass Doors, Outside Air System:
For a period of 90 days from the date the Fireplace is
installed CFM Corporation, at its option, will provide a replace-
ment for any defective part, without charge for the part itself,
FOB CFM Corporation factory, (The consumer must pay for
everything else other than the part.).
C. Fan Motor:
NO IMPLIED WARRANTIES, INCLUDING THE IMPLIED
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE, SHALL REMAIN IN EFFECT AFTER
THE EXPIRATION OF THE WARRANTIES SET FORTH IN
PARAGRAPHS A THROUGH D. Some states do not allow limi-
tations on how long an implied warranty lasts, so this limitation
may not apply to you.
In order to obtain performance of any of the above warranty
obligations write to CFM Corporation at this address:
CFM Corporation
(1) For a period of one (1) year from the date the Fireplace is
installed, CFM Corporation, at its option, will repair or replace
any defective part without charge.
(2) Thereafter, through the 30th year after the date the Fire-
place is installed CFM Corporation, at its option, if replacement
parts are available, will provide a replacement for any defective
part at a cost to the consumer of CFM Corporation then current
list price, FOB CFM Corporation factory.
D. Liners (Refractory or Metal):
(1) For a period of two (2) years from the date the Fireplace
is installed, CFM Corporation, at its option, will repair or replace
any defective part without charge.
(2) Thereafter, through the 30th year after the date the Fire-
place is installed CFM Corporation, if replacement parts are
available, will provide a replacement for any defective part at a
cost to the consumer of CFM Corporation then current list price,
FOB CFM Corporation factory.
This warranty is subject to the following conditions and limita-
tions:
(1) This warranty is extended only to a Fireplace installed in
the continental United States, the state of Alaska and Canada;
only if and so long as the Fireplace is installed according to
the installation instructions furnished with the Fireplace, and
2695 Meadowvale Blvd.
Mississauga, Ontario, Canada L5N 8A3
Attention: Director of Warranty Services
Since local building requirements may vary greatly through-
out the country, users of CFM Corporation products should
determine in advance whether there are any building code
restrictions on the use of a specific product. CFM CORPORA-
TION MAKES NO REPRESENTATION OR WARRANTY RE-
GARDING, AND SHALL NOT BE RESPONSIBLE FOR, ANY
BUILDING CODE COMPLIANCE.
The foregoing warranties give you specific legal rights and
you may also have other rights which vary from state to state.
7412961
27
Download from Www.Somanuals.com. All Manuals Search And Download.
CFM Corporation
2695 Meadowvale Blvd. • Mississauga, Ontario, Canada L5N 8A3
Download from Www.Somanuals.com. All Manuals Search And Download.
|