Tyco Smoke Alarm F3200 User Manual

F3200  
FIRE INDICATOR PANEL  
INSTALLATION & PROGRAMMING MANUAL  
F3200 PRODUCT MANUAL  
Document Number: LT0122  
Issue .......... 2.7;  
5 July 2001  
-- A P P R O V A L S --  
AUSTRALIAN STANDARD AS1603.4 1987 (Incl. Amdt 1 & 2)  
AUSTRALIAN STANDARD AS4050(INT) 1992  
- SSL Listing Number afp789  
AUSTRALIAN STANDARD AS3548 1995 Class A  
The F3200 Fire Indicator Panel is manufactured for  
Tyco Services Fire & Safety  
25 Cleeland Road  
Oakleigh South  
VIC 3167  
AUSTRALIA  
Tel : +61-3-9543 2220  
Fax : +61-3-9543 2155  
COPYRIGHT (C) 2001  
Information contained in this document is subject to copyright, and shall not be reproduced  
in any form whatsoever, without the written consent of Tyco Services Fire & Safety.  
Information contained in this document is believed to be accurate and reliable, however  
Tyco Services Fire & Safety reserves the right to change the content without prior notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
TABLE OF CONTENTS  
End User Liability Disclaimer ................................................................................................... ii  
Amendments .......................................................................................................................... vi  
6.3  
INITIALISING, ACCESSING, DE-ACCESSING, PRINTING, SAVING, LOADING &  
Issue 2.7  
5 July 2001  
Page iii  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Document No: LT0122  
APPENDIX A  
APPENDIX B  
COMPATIBLE ACTUATING DEVICES (DETECTORS)....................... A-1  
F3200 CONFIGURATION SHEETS....................................................... B-1  
Page iv  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
AMENDMENTS  
ISSUE  
1
DATE  
COMMENTS  
ECN  
20/04/94 Original. Corresponds to V1.10 software, which  
includes RZDUs, multiple access codes, revised print  
menu, NSW Coder, Programmable Alarm Text, Inst  
Alarm Text (not in V1.01)  
2
30/01/95 Was WP5.1. Upgraded for small FIP,6A PSU.  
Upgraded ordering info, AS1668 Application, Detector  
List and added I.S.(9.4). Also some  
2162  
2360  
corrections.  
2.1  
01/02/96 Auto-Test Disable note added to 6.4.4.  
Note 10 (Pg A-5) modified.  
Table III updated.  
Applications note 9.5 added.  
PA0443 added to Ordering Info P4-5.  
2.2  
2.3  
16/04/96 Deleted paragraph headed "C29BEx" in Section  
9.4.3.4.  
2417  
2620  
01/12/97 F3200 V2.00 software release.  
Chapters 6, 7 modified.  
Network programming Chapter 11 added.  
Daylight saving, output logic control of zone LEDs,  
selectable event types for history and printing,  
database verify, database CRC recall.  
Controller Board was 1931-2-1.  
2709  
2742  
2.4  
2.5  
09/04/98 Section 1.3.2 add V2.01-V2.04 details.  
"Minute" timers 65-72, Section 3.8.  
Section 4.1 new part numbers, Figs 6.1.2 and 7.1.1.  
Fault Action Text & PC Programming Section 6.4.3.  
RDU zone name transmission Section 7.6. Output  
logic commands for zone isolate, zone de-isolate, and  
zone reset, Section 7.4.9. RDU wiring Section 8.8.  
Add AS/NZ 3548 Class A warning.  
22/03/99 V2.06 software. Section 1.3 add V2.06. Section 6.4.4  
Bells/Ancil Isol key disabling; mains frequency  
50/60Hz. Section 11.3.5, 11.11, 11.12 ACK  
2937  
Broadcast Specific SID. System Configuration Sheets  
Page 2 and Network Parameters.  
2.6  
2.7  
14/06/00 Corresponds to V2.07/V2.08 software. Changes  
throughout but mainly Sections 5.5, 5.6, 6.3.7, 6.4.4  
and Chapters 12 and 13 added.  
05/07/01 Corresponds to V2.09 software. New buzzer mode &  
sounder silence options in Chapter 6. Sect 7.2.4  
change to SAD type. Section 7.4.6 SNA option new.  
Section 7.5 Relay supervision. Appendix A Simplex  
detectors. Appendix B modified. Section 3.3.5.2 NDU  
Quiescent current added. Section 12.8 NZ mode  
installation added.  
3079  
3165  
Chapter 8 Installation revised and Section 9.2 Gas  
Flood revised. Complete re-print.  
3154  
Issue 2.7  
5 July 2001  
Page v  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Document No: LT0122  
THIS PAGE IS INTENTIONALLY LEFT BLANK  
Page vi  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Introduction  
CHAPTER 1  
INTRODUCTION  
Issue 2.7  
5 July 2001  
Page 1-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Introduction  
Document No: LT0122  
1.1  
SCOPE  
This manual provides information for the personnel responsible for planning, ordering,  
installing and programming an F3200 Fire Alarm System. It is assumed that such staff have  
been trained to plan/install fire alarm equipment and are familiar with the relevant standards.  
The manual is divided into the following chapters:  
Chapter 1  
Chapter 2  
Chapter 3  
Chapter 4  
Chapter 5  
Introduction: Information on this manual.  
System Description: A description of the structure of the F3200 FIP.  
Specifications: A detailed specification for the F3200 FIP.  
Ordering Information: Part numbers for the various system components.  
Configuring a FIP: General information and detail on fitting of various links  
and resistors when configuring a system.  
Chapter 6  
Chapter 7  
Programming: An introduction to programming and a description of the  
programming menus and global parameters.  
System Configuration: Detail on specific programmable options in the FIP  
I/O.  
Chapter 8  
Chapter 9  
Chapter 10  
Installation & Wiring: Detail of installation and field wiring.  
Applications: Detail of configuration and wiring for specific applications.  
Alignment, Adjustment & Placing Into Operation: Detail on how to adjust an  
F3200 in the field and place it into operation.  
Chapter 11  
Networking: Detail on programmable options for networked F3200s and  
NDUs.  
Chapter 12  
Chapter 13  
NZ Operation: Describes operation of the NDU in NZ mode.  
Tandem LCD Mode: Describes operation of Tandem LCD mode.  
Appendix A 1.  
Compatible Detectors: A list of detectors which are approved for use  
with F3200.  
2.  
Detector Configuration: Detail on AZC and zone configuration for  
specific detector types.  
Appendix B Configuration Forms: A set of master forms for recording programming detail.  
Page 1-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Introduction  
1.2  
ASSOCIATED DOCUMENTATION  
1.2.1  
PRODUCT  
Additional information on the AS1603.4 approved F3200 FIP is found in the following product  
manuals.  
F3200 Operator's Manual  
A guide to the operation and maintenance of the F3200 FIP.  
Part Number LT0119 is a loose A4 version.  
Part Number LT0120 is a bound A5 version.  
F3200 Technical Manual  
A technical description of the F3200 system and modules.  
Part Number LT0121.  
F3200 Installation &  
Programming Manual  
This manual.  
Part Number LT0122.  
F3200 Panel-Link Upgrade Upgrade instructions on how to make the F3200 panel  
and Installation Manual network capable. Part Number LT0198.  
Information on the AS4428.1 approved F3200 is found in the following manuals:  
F3200 AS4428.1 Operator’s Manual  
For panels that comply with AS4428.1  
LT0251 is in A4, loose leaf form.  
LT0250 is in A5, bound form.  
F3200 AS4428.1 Installation &  
Configuration Manual  
Provides information for designing, installing  
and commissioning an F3200 and NDU. Part  
Number LT0255.  
F3200 AS4428.1 Programming Manual  
Provides information for programming  
an F3200 and NDU. Part Number LT0256.  
1.2.2  
STANDARDS  
This manual makes reference to the following Australian and New Zealand Standards:  
AS1603.4  
Automatic Fire Detection and Alarm Systems  
Part 4 - Control and Indicating Equipment.  
AS4050 (int)  
Fire Detection and Fire Alarm Systems - Fire Fighter's Control  
and Indicating Facilities.  
AS1668  
SAA Mechanical Ventilation and Airconditioning Code.  
AS1670.1  
Automatic Fire Detection and Alarm Systems - System Design,  
Installation and Commissioning.  
AS4428.1  
NZS4512  
Fire Detection, Warning, Control and Intercom Systems -  
Control and Indicating Equipment  
Part 1 : Fire  
Automatic Fire Alarm Systems in Buildings  
Issue 2.7  
5 July 2001  
Page 1-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Introduction  
Document No: LT0122  
1.3  
PRODUCT HISTORY LOG  
1.3.1  
HARDWARE  
Part No.  
Description  
Iss  
Rev  
Date  
Drawing  
PA0490  
Controller/  
Display  
A
A
A
A
B
B
B
B
C
D
A
A
A
A
C
B
C
1
2
3
1
2
3
4
5
6
9
1
2
1
2
4
3
4
11/11/93  
24/02/94  
16/06/94  
13/10/93  
28/02/94  
10/06/94  
21/02/95  
14/05/97  
11/11/97  
14/05/01  
27/09/93  
29/04/99  
10/09/93  
22/09/99  
10/04/01  
04/02/99  
02/05/00  
1931-2  
PA0491  
MAF/PSU  
1931-3  
PA0492  
PA0493  
8 ZONE MODULE  
8 RELAY MODULE  
1931-4  
1931-5  
PA0773  
PA0797  
RS485 Comms Bd  
F3200  
Controller/  
Display  
1901-139  
1931-84-1  
PA0804  
F3200  
B
C
2
4
29/09/97  
02/05/00  
Used as replace-  
ment board for all  
F3200/NDU panels  
1931-84-1  
Networkable  
Controller/  
Display  
1.3.2  
SOFTWARE  
Part No.  
Description  
Revision  
Date  
Comments  
SF0089  
SF0089  
SF0089  
F3200 EPROM  
F3200 EPROM  
F3200 EPROM  
V1.00  
V1.01  
V1.10  
12/12/93  
24/02/94  
13/05/94  
Pre-production  
1st production  
Includes RZDU, multiple  
access, etc.  
SF0164  
SF0175  
SF0178  
F3200 EPROM  
NDU EPROM  
F3200 EPROM  
V2.00  
V2.00  
V2.00  
Nov. 1997  
Nov. 1997  
Nov. 1997  
Networking  
First Release  
Non-networking  
SF0164  
SF0175  
SF0178  
F3200 EPROM  
NDU EPROM  
F3200 EPROM  
V2.01  
V2.01  
V2.01  
Feb. 1998  
Feb. 1998  
Feb. 1998  
F3200 Networked  
Non-Networked  
SF0178  
SF0164  
SF0175  
SF0178  
F3200 EPROM  
F3200 EPROM  
NDU EPROM  
F3200 EPROM  
V2.02  
V2.03  
V2.03  
V2.03  
Mar. 1998  
April 1998  
April 1998  
April 1998  
Non-Networked  
F3200 Networked  
Non-Networked  
SF0164  
SF0175  
SF0178  
F3200 EPROM  
NDU EPROM  
F3200 EPROM  
V2.04  
V2.04  
V2.04  
August 1998 Networked  
August 1998  
August 1998 Non-Networked  
SF0164  
SF0175  
SF0178  
F3200 Net EPROM V2.05  
NDU EPROM V2.05  
F3200 Std EPROM V2.05  
Feb 1999  
Feb 1999  
Feb 1999  
Page 1-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Introduction  
SOFTWARE HISTORY LOG (CONTINUED)  
SF0164  
SF0175  
SF0178  
F3200 Net EPROM  
NDU EPROM  
F3200 Std EPROM  
V2.06  
V2.06  
V2.06  
Mar 1999  
Mar 1999  
Mar 1999  
SF0229  
SF0230  
SF0231  
F3200, Std Panel, c/w Tandem  
F3200, Networked, c/w Tandem  
NDU, c/w Tandem  
V2.07  
V2.07  
V2.07  
May 2000  
May 2000  
May 2000  
SF0229  
SF0230  
SF0231  
F3200, Std Panel, c/w Tandem  
F3200, Networked, c/w Tandem  
NDU, c/w Tandem  
V2.08  
V2.08  
V2.08  
July 2000  
July 2000  
July 2000  
SF0229  
SF0230  
SF0231  
F3200, Std Panel, c/w Tandem  
F3200, Networked, c/w Tandem  
NDU, c/w Tandem  
V2.09  
V2.09  
V2.09  
May 2001  
May 2001  
May 2001  
Issue 2.7  
5 July 2001  
Page 1-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Introduction  
Document No: LT0122  
1.4  
GLOSSARY OF ABBREVIATIONS  
The following abbreviations are used throughout this manual:  
A/C  
ac  
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
:
Air Conditioning  
Alternating Current  
Active End of Line  
Ampere Hour  
Ancillary Relay 1  
Alarm Zone Circuit, or Detection Zone  
Alarm Zone Facility, or Group  
Alarm Verification Facility, or Check Alarm  
Board  
Control & Indicating Equipment  
Character  
Circuit  
COMMON relay contact  
Direct current  
Electrically Erasable Programmable Read Only Memory  
Extra Low Voltage  
End Of Line (device)  
End of Line Resistor  
Expansion  
Electrically Erasable Programmable Read Only Memory ....  
Fire Fighter's Control & Indicating Facility  
Fire Indicator Panel  
Flat Ribbon Cable  
Input/Output  
AEOL  
AHr  
ANC 1  
AZC  
AZF  
AVF  
Bd  
CIE  
Char  
CCT  
COM  
dc  
EEPROM  
ELV  
EOL  
EOLR  
Expn  
E2  
FFCIF  
FIP  
FRC  
I/O  
LCD  
LED  
MAF  
Max  
Min  
MCP  
MOV  
msec  
NC  
Liquid Crystal Display  
Light Emitting Diode  
Master Alarm Facility  
Maximum  
Minimum  
Manual Call Point (Break Glass Switch)  
Metal Oxide Varistor (Used for Surge Protection)  
Millisecond  
Normally Closed  
Normally Open  
Number  
Nominal  
Personal Computer (small computer)  
Printed Circuit Board  
Power Supply Unit  
Positive Temperature Co-efficient (Thermistor)  
Module Relay Number 1 (program abbreviation)  
Module Relay Number 1 (text abbreviation)  
Return Air Duct (Air Conditioning Plant)  
Root Mean Square  
NO  
No  
Nom  
PC  
PCB  
PSU  
PTC  
R1  
RL1  
RAD  
RMS  
Reqd  
RTC  
RZDU  
SAD  
SID  
Required  
Real Time Clock  
Remote Zone Display Unit  
Supply Air Duct (Air Conditioning Plant)  
System Identification Number (Network device)  
square millimetre  
Programmable Timer Number 1 (program abbreviation)  
Terminal  
sq mm  
T1  
Tmnl  
V1  
Programmable Variable Number 1  
Page 1-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Introduction  
GLOSSARY OF ABBREVIATIONS (CONTINUED)  
VA  
VB  
VNB  
+VBF  
+VNBF  
Z1  
Zn1  
8RM  
8ZM  
:
:
:
:
:
:
:
:
:
Volts Amperes  
Battery Backed Voltage  
Non Battery Backed Voltage  
Fused Battery-Backed Voltage  
Fused Non-Battery-Backed Voltage  
Zone Number 1 (program abbreviation)  
Zone Number 1 (text abbreviation)  
8 Relay Module  
8 Zone Module  
1.5  
GLOSSARY OF TERMINOLOGY  
The following terminology is used throughout this manual:  
Ancillary Equipment :  
Ancillary Relay  
Equipment external to Fire Alarm system  
Relay in FIP which operates Ancillary equipment  
Mode for one person testing of detectors  
Output for driving additional LEDs/relays  
Bits per second  
Output from FIP to other equipment  
Pre-programming option or logic equation i.e. one that exists  
without the user programming it.  
:
Auto-Reset  
Auxiliary Output  
Baud  
:
:
:
:
:
Control Output  
Default  
Detector  
Fire Control Station  
the  
Mapping  
Zone  
:
:
Alarm Detection Device (electrical transducer)  
Fire Brigade Authority, or any other authority which receives  
FIP alarm signals.  
Programmable causal relationship between inputs and outputs  
Fire searchable area of building represented by a unique  
number and name in the FIP, and associated with the AZC of  
the same number.  
:
:
Issue 2.7  
5 July 2001  
Page 1-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Introduction  
Document No: LT0122  
THIS PAGE INTENTIONALLY LEFT BLANK  
Page 1-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
CHAPTER 2  
SYSTEM DESCRIPTION  
Issue 2.7  
5 July 2001  
Page 2-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
2.1  
OVERVIEW  
2.1.1  
GENERAL  
The F3200 is a self-contained, modular, intelligent Fire Indicator Panel (FIP) which performs  
the functions of the Control and Indicating Equipment (CIE) as specified by the Australian  
Standard AS1603.4 Automatic Fire Detection and Alarm Systems.  
It is also available in formats that comply with AS4428.1. Refer to the relevant manuals that  
apply to the AS4428.1 approved products.  
The F3200 has a high degree of flexibility and expandability, catering for medium to very  
large buildings from 8 zones or less, to 64 zones maximum. Refer to the constraints  
specified in Section 3.1.3. More panels and zones can be added through the use of the  
Vigilant Panel-link Network and the appropriate networkable F3200s.  
This manual is also used for the installation of an NDU (Network Display Unit). NDU  
operation is described in Section 11.11. An NDU may be programmed to operate in either  
Australian mode (default) or New Zealand mode, and the operation of an NDU in New  
Zealand mode is described in Chapter 12.  
2.1.2  
DETECTOR CIRCUITS  
The F3200 detector interface electronics caters for a wide range of detectors, including  
various types which have high alarm current requirements. It also caters for interfacing to:  
Intrinsically safe circuit barriers/isolators (hazardous areas).  
Long line circuits e.g. from a sub-indicator FIP.  
Tamper-proof circuits e.g. for water valve supervision.  
A full range of compatible detectors is listed in the Appendix A.  
2.1.3  
DISPLAYS  
The primary display of the F3200 is a 2 line by 40 character LCD on which status messages  
and prompts are shown. The LCD has backlight illumination which is turned on when there  
is an alarm or operator interaction.  
Common conditions such as zone ALARM, ISOLATED and FAULT, and various system  
states such as BELLS ISOLATED are displayed on LEDs adjacent to the LCD.  
The display panel composed of the LCD, LEDs and operator keypad meets the requirements  
of AS4050 (int) for a Fire Fighter's Control and Indicating Facility (FFCIF).  
As an optional extra, individual zone status (ALARM, ISOLATE and FAULT) can be  
displayed on LEDs by fitting the appropriate number of 16 Zone LED Display Bds.  
The F3200 electronics includes, as standard, an open collector transistor output for each  
zone which can be used to drive an internal or remote mimic display.  
Page 2-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
FIG 2.1.1  
F3200, STANDARD CABINET - FRONT VIEW  
Issue 2.7  
5 July 2001  
Page 2-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
FIG 2.1.2  
F3200 OPERATOR DISPLAY PANEL  
Page 2-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
FIG 2.1.3  
F3200 - SMALL CABINET  
Issue 2.7  
5 July 2001  
Page 2-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
2.1.4  
OUTPUTS  
The F3200 MAF/PSU Module provides 7 relays as standard. These are used for signalling  
to the Brigade (Fire Control Station) and for switching alarm bells and ancillary equipment  
such as door holders, airconditioning shutdown, etc.  
When more than 7 relays are required, additional sets of 8 can be added by fitting 8 Relay  
Modules.  
All outputs, including the open collectors on the 8 Zone Modules, are individually  
programmable by a logic equation of zone and FIP status.  
2.1.5  
POWER SUPPLY  
The F3200 has a 3 Amp battery charger/power supply as standard. There is adequate room  
for large batteries.  
An optional 6 Amp battery charger/power supply is available. This is factory fitted, but is not  
available in the small cabinet FIPs.  
Fuse protected battery backed and non-battery backed supplies are available to power  
external loads such as bells, illuminated signs, interposing relays, gas release solenoids,  
door holders, etc.  
2.1.6  
REMOTE DISPLAY & PRINTER  
A serial port is included in the F3200 to provide a 3 or 4 wire link to a Remote Zone Display  
Unit (RZDU). Several versions of F3200 remote displays are available, including the small,  
Remote LCD unit.  
The F3200 also has a serial port to drive a logging printer, which records all events as they  
occur, with time and date. Logging of relay events is programmable. For network systems,  
events from other selected devices on the network may be logged into the history and  
printed on the local printer, and events generated locally by this system may be printed by  
some other device on the network.  
2.1.7  
NETWORKING  
Networking of F3200s allows the sharing of zone, event and alarm information, the ability to  
remotely control other F3200s, and, overall, the expansion of an F3200 system beyond 64  
zones.  
Networking is achieved through a different software version and the fitting of an RS485  
Communications board.  
Page 2-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
2.2  
PHYSICAL STRUCTURE  
The F3200 has a rugged, lockable painted steel cabinet, which houses 19 inch rack-mount  
equipment and comes in two height options (both have the same width and depth). The  
standard cabinet accommodates 15U total and the small cabinet accommodates 8U (where  
1U = 1 3/4" = 44.5mm).  
The Operator Display has a screened, polyester overlay mounted on a hinged inner door  
fitted to the top 4U position. The Controller/Display pcb mounts directly to the rear of this  
door.  
Standard Cabinet  
In the standard cabinet the space below the 4U Operator Display panel is covered by a  
blanking plate, but there is provision for mounting other equipment (e.g. a 7U hinged inner  
door for a mimic, or 16 Zone LED Display Bds), in place of this blanking plate.  
There is provision for mounting additional equipment in the bottom 4U (e.g. an AS1668  
control rack), but this would encroach on battery space.  
The outer door has a large acrylic window to allow viewing of the equipment inside.  
Four versions of FIP are available in this cabinet. The FP0551, which caters for up to 64  
zones, has a cardframe fitted to the rear wall as shown in Fig 2.2.1. The FP0550 has  
provision (pcb stand-offs) for mounting up to three 8 way modules (i.e. 3 x 8 Zone or 8 Relay  
Modules) on the rear wall. Both are supplied with 1 8 Zone Module fitted.  
Versions of these two FIPs are also available with a 6 Amp power supply:  
FP0713 (8 module capacity), and FP0712 (3 module capacity).  
Small Cabinet  
In the small cabinet, only 1U (of the 4U) below the 4U Operator Display is visible through the  
outer window. The gap is covered by a blanking plate (2U), which can be replaced by a  
bracket for mounting a limited range of equipment, eg. a 1U AIU bracket, or a 1U 1 Zone  
Gas Control Panel.  
A 6A PSU or a 7U LED Display door cannot be fitted.  
Up to four 8 way modules can be mounted on the rear wall, but the bottom two of these  
share space with the batteries. Mounting arrangement and maximum capacity are shown in  
Fig 2.2.2.  
Only one FIP is available (FP0583), and this comes with one 8 Zone Module fitted (in the top  
left position).  
Issue 2.7  
5 July 2001  
Page 2-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
Note: FP0551 and FP0713 have the cardframe as shown.  
FP0550 and FP0712 have the modules (3 max.) mounted on the rear wall.  
FIG 2.2.1  
F3200 STANDARD CABINET - INTERNAL LAYOUT  
Page 2-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
FIG 2.2.2  
F3200, SMALL CABINET, MAXIMUM CONFIGURATIONS  
Issue 2.7  
5 July 2001  
Page 2-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
2.3  
SYSTEM STRUCTURE  
2.3.1  
PCB MODULES  
The 6 printed circuit boards which are used in an F3200 are as follows:  
Controller/Display  
Mounts on 4U inner door.  
Includes:  
LCD, status LEDs and buzzer  
keypad connection  
5Vdc supply  
voltage monitors for battery charger  
microprocessor & memory  
serial I/O bus control for all other modules  
reference voltage generation for I/O modules  
UARTs and serial port electronics  
real time clock calendar integrated circuit  
FRC connection to other modules.  
MAF/PSU  
Mounts on cabinet rear wall.  
Includes: battery charger/PSU  
22V regulator for detector circuits  
Brigade & Ancillary relays and supervision circuitry  
MCP & door switch inputs  
screw terminals (most demountable) for field wiring  
FRC connection to other modules.  
8 Zone Module  
Mounts on cabinet rear or in cardframe.  
Includes:  
electronics to I/F to 8 Alarm Zone Circuits (AZCs)  
8 open collector auxiliary outputs  
demountable screw terminals for field wiring  
FRC connection to other modules.  
8 Relay Module  
Mounts on cabinet rear or in cardframe.  
Includes:  
8 relays and supervision circuitry  
demountable screw terminals for field wiring  
FRC connection to other modules.  
16 Zone LED Display  
Mounts on 7U inner door.  
Includes:  
16 sets of 3 LEDs  
electronics to control the LEDs (serial bus)  
Page 2-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
RS485 "Panel-Link" Network Board  
Connects to the Controller/Display Board  
Includes:  
RS485 Board used for connection to the Vigilant Network.  
FIG 2.3.1  
SYSTEM STRUCTURE  
Issue 2.7  
5 July 2001  
Page 2-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
2.3.2  
INTER-CONNECTION & STRUCTURE  
A basic F3200 system has one Controller/Display, one MAF/PSU, and one 8 Zone Module,  
all connected by Flat Ribbon Cable (FRC) on a common Input/Output (I/O) Bus.  
Additional 8 Zone Modules and/or 8 Relay Modules can be fitted to the I/O bus, with a  
maximum of eight 8 way modules. This is shown in the block diagram of Fig 2.3.1.  
The physical maximums are:  
three 8 way modules in an FP0550 or FP0712.  
four 8 way modules in an FP0583 (with restrictions)  
eight 8 way modules in an FP0551 or FP0713.  
Expansion is from top to bottom.  
The I/O Bus Out of one module connects to the I/O Bus In of the next module via the 20 way  
FRC provided (LM0053).  
No link or "End of Bus" is required on the last module because the data from the furthest  
output shift register is fed into the furthest input shift register via the wrap-around resistor as  
shown in Fig 2.3.2.  
Refer to Section 3.1.3 Specifications for detail on the structural arrangement of AZCs and  
relays.  
To further extend these capabilities, up to 64 F3200s may be networked together, with full  
sharing of information and remote control of each panel by a master panel.  
16 Zone LED Display bds are driven from a separate serial bus on the Controller/Display.  
They receive power from the MAF/PSU via two power leads. Where more than one is  
required they are connected in series (up to 4 maximum) from right to left (as viewed from  
the front) on the FIP. The 26 way FRC from J13 of the Controller goes to J1 ("From  
Previous") of the right hand Display Bd. Zone 1 (default) corresponds to the top LEDs on  
the left hand Display Bd. The last board requires the "end of bus" minijump connector to be  
fitted. Note that a special FRC cable is required to connect the Controller Board to the first  
Display Board (LM0092).  
Where LED Display bds are fitted, the default programming requires one Display bd (16  
zones) for every two 8 Zone Modules, i.e. one for 1-16 zones, two for 17-32 zones, etc.  
Zone 1 corresponds to the top row of 3 LEDs on the left most Display. Zone 2 to the row  
below it, etc, (top to bottom, left to right).  
LED Display bds may also annunciate relay status, i.e. Alarm <-> relay energised, Isolated  
<-> relay isolated, Fault <-> relay wiring fault (i.e. supervision fault).  
The default programming for displaying both zone and relay status requires one Display bd  
for every two 8 way modules (zone and relay).  
Page 2-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Description  
INTER-CONNECTION & STRUCTURE (CONTINUED)  
The relay LEDs simply follow the zone LEDs in the same order that they occur in the  
modules. E.g. a system with three 8 Zone Modules and two 8 Relay Modules would require  
3 Display bds. Relay 1 would be annunciated on the 25th row of LEDs and the last 8 rows  
would be unused as shown in Fig 2.3.3.  
Mapping zones and relays to LEDs in other patterns is programmable.  
FIG 2.3.2  
SERIAL DATA FLOW IN THE I/O BUS  
Issue 2.7  
5 July 2001  
Page 2-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Description  
Document No: LT0122  
Zone  
Module  
Relay  
Display  
1
8
1
........1  
1
8
8ZM 1  
8
1
9
1
8
1
8
9
8ZM 2  
8ZM 3  
16  
........16  
........1  
16  
17  
24  
17  
24  
2
1 1  
25  
32  
8RM 1  
8RM 2  
8 8....16  
1 9....1  
8 16....  
33  
40  
3
LAST 8 UNUSED  
16  
FIG 2.3.3  
DISPLAY STRUCTURE  
(DEFAULT MAPPING)  
EXAMPLE FOR SYSTEM WITH 3 8ZM & 2 8RM  
The F3200 can be configured to have a lesser number of Display Bds than required by the  
default structure, with selective mapping of zones/relays to Display LEDs.  
Page 2-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
CHAPTER 3  
SYSTEM SPECIFICATIONS  
Issue 2.7  
5 July 2001  
Page 3-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
3.1  
GENERAL  
3.1.1  
FIP PART NUMBER & DESCRIPTION  
Refer to Section 4 also.  
FP0550, F3200 FIP, NO CARDFRAME, 24 ZONE MAX, 1931-15  
Includes:  
Full size cabinet (ie. standard cabinet)  
Controller/Display with FFCIF LCD & Keypad  
MAF/PSU (includes 7 relays, 3A PSU)  
1 x 8 Zone Module with standard EOLRs  
Modules fit to cabinet rear wall (up to 3 modules max)  
FP0551, F3200 FIP, C/W CARDFRAME, 64 ZONE MAX, 1931-16  
Includes:  
Full size cabinet (ie. standard cabinet)  
Controller/Display with FFCIF LCD & Keypad  
MAF/PSU (includes 7 relays, 3A PSU)  
Cardframe (can house up to 8 modules)  
1 x 8 Zone Module fitted in cardframe  
includes standard EOLRs  
FP0583, F3200 FIP, SMALL CABINET  
Includes:  
Small cabinet  
Controller/Display with FFCIF LCD & Keypad  
MAF/PSU (includes 7 relays, 3A PSU)  
1 x 8 Zone Module with standard EOLRs  
Modules fit to cabinet rear wall (up to 4 modules max)  
FP0712, F3200 FIP, NO CARDFRAME, 24 ZONE MAX, C/W 6 AMP PSU  
Includes:  
Full size cabinet (ie. standard cabinet)  
Controller/Display with FFCIF LCD & Keypad  
MAF/PSU (includes 7 relays, 6A PSU)  
1 x 8 Zone Module with standard EOLRs  
Modules fit to cabinet rear wall (up to 3 modules max)  
FP0713, F3200 FIP, 64 ZONE MAX, C/W 6 AMP PSU  
Includes:  
Full size cabinet (ie. standard cabinet)  
Controller/Display with FFCIF LCD & Keypad  
MAF/PSU (includes 7 relays, 6A PSU)  
Cardframe (can house up to 8 modules)  
1 x 8 Zone Module fitted in cardframe  
includes standard EOLRs  
3.1.2  
SYSTEM EXPANSION  
Expansion to the base panels is by adding 8 way zone input or relay output modules, or by  
networking multiple panels together.  
FP0553, F3200 8 ZONE INPUT EXPANSION KIT  
Includes:  
8 Zone Module, FRC, 8 x EOLR (std)  
FP0554, F3200 8 RELAY EXPANSION KIT  
Includes:  
Page 3-2  
8 Relay Module, FRC, 8 x Minijump links (for supervision selection)  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
3.1.3  
ENVIRONMENTAL  
Operating Temperature  
:
-5°C to 45°C (Ambient)  
95% maximum @ 40°C (non-condensing)  
Relative Humidity  
:
3.2  
MECHANICAL SPECIFICATIONS  
CABINETS  
Style  
:
Wall mounting  
Hinged outer door with large window (hinges to left)  
Accepts 19" rack mounting equipment  
4U Display on hinged inner door (hinges to right)  
Construction :  
Welded steel  
Material  
Size  
:
:
1.2mm and 1.6mm mild steel  
- Standard  
- Small  
:
:
750mm (H) x 550mm (W) x 210mm (D) * (Iss B cabinet)  
410mm (H) x 550mm (W) x 210mm (D) *  
* MCP is an additional 20mm.  
Finish  
:
:
Powdercoat BFF-998-CW  
Cream Wrinkle  
(Iron Phosphate pre-treat)  
Weight  
Unpackaged  
20kg  
22kg  
17kg  
22kg  
Packaged  
22kg  
24kg  
19kg  
24kg  
FP0550  
FP0551  
FP0583  
FP0712  
FP0713  
24kg  
26kg  
Issue 2.7  
5 July 2001  
Page 3-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
3.3  
ELECTRICAL SPECIFICATIONS  
3.3.1  
MAINS SUPPLY  
Voltage  
Current  
Frequency  
Termination  
:
:
:
:
240Vac +6% -10%  
0.5A  
50Hz  
For up to 2.5sq mm TPS  
3 Way block with wire protectors  
3.3.2  
BATTERY CHARGER & PSU  
Input Voltage  
:
31Vac rms  
(Transformer sec)  
Charger Voltage  
:
:
27.3Vdc (nominal at 20°C)  
Temperature  
Compensation  
-36mV per °C nominal  
Non-Battery Backed :  
Voltage  
28.0 nominal  
Max Total Current  
:
3Adc for std PSU (Charger, Quiescent & Alarm)  
6Adc (for 6A PSU only)  
Max Bell Current  
:
:
2Adc  
2Adc  
Max. Ancillary  
Current on VBF1  
Max. Ancillary  
Current on VBF2  
:
:
2Adc (allows 3A max LED Display)  
2Adc (e.g. for door holders)  
Max. Ancillary  
Current on VNBF  
(VBF <-> battery backed, fused. VNBF <-> non-battery backed, fused)  
Current Limit  
Standard PSU  
6A PSU  
Battery to  
MAF/PSU  
:
:
:
:
PTC, 6A nom, 3.6A min  
3.3A nom, 3.0A min  
(see notes below)  
6.7A nom, 6.0A min  
PSU/Charger  
Notes  
1)  
2)  
The 6A PSU is factory fitted in the FP0712 and FP0713. It is  
not available in the FP0583.  
For the 6A PSU, the PTCs on the MAF are shorted out and a  
Derwent 10A thermal cutout is wired between the battery +  
terminal and the MAF/PSU.  
Page 3-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
STATE  
MIN  
NOM  
28.125  
26.57  
24.33  
22.0  
MAX  
COMMENTS  
Charger High  
Charger Low  
Battery Low  
Standby Off  
Notes:  
28.05  
26.40  
24.15  
21.5  
28.20 Adjust with pot  
26.75  
24.55  
22.5 For voltage falling  
1. All voltages stated in VDC at temperature of 20°C.  
2. Apply temperature compensation of -36 mV/°C for temperature deviation from 20°C.  
3. This applies also to charger voltage 27.3 VDC.  
4. There are thermal delays, therefore if checking or adjusting in field ensure unit has been  
running for some hours.  
5. Standby Relay is normally energised (on), and turns off for Battery fail.  
TABLE 3.3.2  
BATTERY AND CHARGER MONITORING VOLTAGE SPECIFICATIONS  
3.3.3  
BATTERY  
Battery Voltage  
Compatible Makes  
:
24Vdc nominal (2 x 12Vdc)  
Sonnenschein A200 & Sonnenschein A300 series  
Powersonic PS12 series  
Yuasa NP series  
Capacity  
:
:
6 to 50 Ahr  
(dependent on configuration)  
Space (mm)  
- Standard Cabinet  
Up to 220H, 440W, 175D (Iss B cabinet)  
- Small Cabinet  
Up to 200H, 185W, 175D (3 modules fitted)  
Up to 200H, 370W, 125D (4 modules fitted)  
(Refer to Fig 2.2.2)  
Battery Test Load  
:
46 Ohm nominal. Suitable for 6 Ahr battery (with quiescent  
current)  
Provision for fitting extra resistors  
NOTE:  
BATTERY TEST RESISTORS (R52, R53) MUST BE REMOVED FOR NEW  
ZEALAND OPERATION.  
3.3.4  
FUSES  
Location  
:
MAF/PSU PCB  
Number  
F1  
F2  
F3  
F4  
F5  
F7  
Name  
+VBF1  
+VBF2  
+VNBF  
+VE  
Mains In  
+VBELLS  
Size  
Rating  
Type  
5 x 20mm  
5 x 20mm  
5 x 20mm  
5 x 20mm  
5 x 20mm  
5 x 20mm  
2A  
6A  
2A  
2A  
6A  
2A  
Glass Cartridge, Std  
Glass Cartridge, Std  
Glass Cartridge, Std  
Glass Cartridge, Std  
Glass Cartridge, Std  
Glass Cartridge, Std  
Issue 2.7  
5 July 2001  
Page 3-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
3.3.5  
CURRENT CONSUMPTION  
3.3.5.1  
F3200 Quiescent & Alarm Currents  
At 24Vdc battery supply, nominal currents:  
Quiescent  
130mA  
Alarm (2 Zone)  
275mA  
FP0550, FP0551, FP0583, FP0712, FP0713  
(notes 1-4)  
8 Zone Module  
- all AZCs disabled  
- all AZCs enabled (notes 2-6)  
Current per enabled AZC (note 3)  
4mA  
82mA  
10mA  
97mA  
8 Relay Module  
- all supervision disabled  
- all supervision enabled  
Current per relay on  
4mA  
6mA  
11mA  
MAF/PSU  
- all relays off  
9mA  
Current per Ancillary Relay  
(includes bells)  
Current per Brigade Relay  
11mA  
16mA  
11mA  
16mA  
22V Supply (supplies 8 Zones) max rating  
800mA  
Controller/Display  
- LCD backlight off, status LEDs off  
- LCD backlight on, status LEDs off  
Current per status LED on  
19mA  
75mA  
3mA  
16 Zone LED Display  
RS485 network interface board PA0773  
0mA  
7.5mA  
16mA/LED (steady)  
Total electronics and detector max rating 2000mA  
Notes  
1.  
FP0550/551/583/712/713 currents include Controller/Display, MAF/PSU and 1 x 8ZM  
with all ACZs enabled and with EOLRs (2K7 for mode 1 or 2).  
2.  
Quiescent current for an enabled AZC is for modes 1 or 2 (standard or high current)  
and includes the 2k7 EOL, but not the detector current (up to 4mA detector current  
per AZC).  
3.  
4.  
5.  
Quiescent current is only 2.5mA per AZC for mode 3 and 1mA for mode 4.  
Alarm current is for AZC mode 1, refer AZC specifications for other modes.  
The 8 Zone Modules (8ZMs) are supplied from the fused battery supply via the 22V  
regulator which has a maximum rating. The 8 Relay Modules (8RMs) are supplied  
directly from the fused battery supply.  
6.  
Quiescent and alarm currents do not include external loads e.g. door holders, bells,  
etc.  
Page 3-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
3.3.5.2  
NDU Quiescent and Alarm Currents  
Slimline NDU (FP0714/FP0773/FP07744)  
Operating Voltage  
Termination  
:
:
24Vdc (18-28V)  
For up to 2.5sqmm TPS  
Quiescent  
25mA  
Alarm  
80mA  
Current Consumption :  
Full cabinet NDU (FP0715)  
Quiescent  
70mA  
85mA  
Alarm  
165mA  
150mA  
Current Consumption (Aust mode)1  
Current Consumption (NZ mode)2  
1.  
2.  
Includes controller, MAF/PSU, energised standby relay, PA0773 RS485 Bd, LCD  
backlight off in quiescent state.  
Includes controller, MAF/PSU, NZ Display Extender, energised standby and alarm  
relays, PA0773 RS485 Bd. LCD backlight off in quiescent state.  
3.  
4.  
Refer to Section 3.3.5.1 for additional module currents.  
For FP0774 the I-Hub currents must be added.  
Issue 2.7  
5 July 2001  
Page 3-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
3.4  
INPUT SPECIFICATIONS  
3.4.1  
AZC SPECIFICATIONS  
General  
Terminations  
On 8 Zone Module, 2 per AZC.  
Demountable screw terminal 1.5sq mm cable max.  
Number  
8 AZCs per 8 Zone Module.  
64 max per system.  
End of Lines (EOLs)  
Mode  
EOL  
1 Standard  
2 High Current  
3 Low Current  
4 Tamper  
2k7, 5%, 400mW resistor  
2k7, 5%, 400mW resistor  
10k, 5%, 400mW resistor  
EOL002B active EOL  
None  
5 Disabled  
Circuit Resistance & Capacitance  
Mode  
Capacitance  
Resistance  
1, 2 & 4  
3
500nF  
1000nF  
50 Ohm max  
800 Ohm max for B2 Alarm  
2k Ohm max for B3 Alarm  
Voltages  
Min  
Typ  
Max  
Detector Supply  
on MAF/PSU (note 1)  
21.2V  
22.0V  
22.2V  
(21.8V)  
18.75V  
18.0V  
at AZC terminals  
at end of circuit  
20.3V  
20.3V  
22.1V  
22.1V  
Alarm Voltage Thresholds  
Band B3 upper threshold  
17.2V  
17.5V  
13.1V  
17.8V  
Band B3 lower threshold  
Band B2 upper threshold  
12.75V  
13.45V  
Band B2 lower threshold  
Band B1 upper threshold  
2.7V  
0V  
2.9V  
0V  
3.1V  
0V  
Band B1 lower threshold  
Page 3-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
AZC SPECIFICATIONS (CONTINUED)  
Min  
Typ  
Max  
AZC current limit (note 1)  
13.5mA  
(14.5mA)  
15.5mA 16.5mA  
EOL & detector quiescent  
EOL, no detectors  
11.95mA  
7.0mA  
(7.2mA)  
7.8mA  
8.2mA  
Fault threshold  
Detector quiescent  
Notes  
4.4mA  
0mA  
5.75mA  
6.8mA  
4.0mA  
1.  
The minimum figures shown are for battery voltage greater than the minimum  
Standby (Battery Fail) level i.e. 21.5V. The figures shown in brackets are for a  
battery voltage greater than 22.5V.  
2.  
Modes 1 & 2 have the same thresholds before the Alarm state is latched. For Mode  
2 additional current is turned on once the Alarm state is latched (refer to Graph  
3.4.2).  
Min  
Typ  
Max  
Mode 3 Only  
Current into short circuit  
34.3mA  
14.8mA 15.3mA  
Current into 800 Ohm (note 3)  
Current into 2000 Ohm (note 4)  
EOLR Current  
14.2mA  
8.0mA  
8.2mA  
2mA  
8.4mA  
Minimum current for EOLR & 2k circuit  
1.64mA  
Modes 3 & 4  
Fault thresholds  
Maximum allowable load or circuit leakage  
0.85mA  
1.28mA 1.59mA  
0.5mA  
Notes  
3.  
4.  
I.e. short at end of an 800 Ohm circuit (gives voltage band B2 alarm, ref graph 3.4.1).  
I.e. short at end of a 2000 ohm circuit (gives voltage band B3 alarm, ref graph 3.4.1).  
MCP Zener Diode  
For voltage band B3 operation  
BZT03C15 3W, 15V.  
Issue 2.7  
5 July 2001  
Page 3-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
AZC SPECIFICATIONS (CONTINUED)  
Detector Alarm Currents  
The current available to a latched detector is the AZC supply current at the detector "Alarm"  
voltage minus the EOLR current and the remaining quiescent current at that voltage.  
The following graphs show current/voltage characteristics for the various modes of  
operation.  
GRAPH 3.4.1  
AZC CURRENT LIMIT CHARACTERISTICS (MODES 1 & 2)  
ICL = Current Limit  
IAV = Current Available to Detectors with EOLR fitted  
IAV = ICL - IEOLR  
GRAPH 3.4.2  
AZC CURRENT VS VOLTAGE : MODE 1 (STANDARD)  
Page 3-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
ICL+R = Current sourced through current limit and pull up resistor  
IAV = Current available to detectors with EOLR fitted  
IAV = ICL+R - IEOLR  
GRAPH 3.4.3  
AZC CURRENT VS VOLTAGE MODE 2 (HIGH CURRENT)  
A short circuit at the end of an 800 Ohm line will give a B2 (Detector Operated) alarm.  
A short circuit at the end of a 2k Ohm line will give a B3 (programmable) condition.  
GRAPH 3.4.4  
ACZ CURRENT VS VOLTAGE MODES 3 & 4 (LOW CURRENT & TAMPER)  
Issue 2.7  
5 July 2001  
Page 3-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
AZC SPECIFICATIONS (CONTINUED)  
Timing  
Standard Delay  
2.3 sec (2.0 - 2.6 sec)  
(into Alarm, Fault, Normal)  
AZC Reset  
5.3 sec (5.0 - 5.6 sec)  
AZC Ignore Period 1  
(after Reset)  
2 sec nom (plus std 2.3 sec delay)  
AZC Ignore Period 2  
1 sec nom (plus std 2.3 sec delay)  
(after Start Up or Programming)  
AZC Time Into Alarm  
Programmable 0-250 sec  
Programmable 0-250 sec  
AZC Time Out of Alarm  
Refer to Section 7.2.4 for detail on other sequences and programmable delays.  
3.4.2  
MAF/PSU INPUTS  
Battery Termination  
One pair screw terminals; 4sq mm max cable  
AC Input  
31V rms; 3.6A rms; 2.8mm tab terminals  
Door Switch  
5V, 0.5mA, Unsupervised, 4 Way .1" pcb header, J6  
5V, 1mA, 2k7 EOLR, 4 Way .1" pcb header, J6  
MCP  
Spare Inputs (not fitted)  
5V, 0.5mA, Unsupervised, Cabinet internal use only, 4 Way  
.1" pcb header, J5  
Relay Supervision  
Anc 1 Sup/Anc 2 Sup  
Modes of Operation  
One screw terminal each  
1 Door holder (Default for Anc 1)  
2 Load (Default for Anc 2)  
Relay Off  
Door Holder Mode expects Voltage Present  
Relay On  
No Voltage Present  
Open Circuit or Voltage Present  
Load mode expects  
Resistive to 0V  
3.65V Nom  
Voltage Threshold  
(Door Holder Mode)  
Supervision Current  
0mA @ +5V, 1mA @ 0V  
Load Resistance  
(Load Mode)  
400 Ohm - 10k Ohm  
less than 400 Ohm with series diode at load.  
14 Ohm absolute minimum.  
Bells Relay  
Form  
Reverse polarity - requires series diode at each device  
Page 3-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
MAF/PSU INPUTS (CONTINUED)  
End of Line Resistor  
No. of Circuits  
Type  
1
2
3
3k3, 5%, 250mW resistor  
6k8, 5%, 250mW resistor  
10k, 5%, 250mW resistor  
Supervision Current  
Circuit Resistance  
0mA @ +5V, 1.5mA @ 0V, +ve to BELLS- terminal  
100 Ohm max.  
3.4.3  
CONTROLLER/DISPLAY INPUTS  
Spare DC Input/Output  
24Vdc nom demountable screw terminal, 4 way, J5  
Spare Input  
22V, 10k Ohm pull up resistor  
Provision for supervision (up to 5 band)  
Spare Inputs IP0, 1, 2  
(not fitted)  
Unsupervised, Cabinet internal use only  
+5V, 100k pull up resistor, 10 Way FRC header, J10  
Serial I/O  
RZDU Refer Section 3.5.3; Others 3.5.2  
3.4.4  
8 RELAY MODULE SUPERVISION  
Form  
Load monitoring  
Relay Off  
Resistance to 0V  
Relay On  
Voltage Present  
Expects  
Selected By  
Minijump link on pcb & programming of FIP  
Disabled (unsupervised)  
Default Programming  
Load Resistance  
400 Ohm - 10k Ohm  
Less than 400 Ohm with series diode at load  
14 Ohm absolute minimum  
Voltage Threshold  
Supervision Current  
3.65V nom.  
0mA @ +5V, 1mA @ 0V  
3.4.5  
NZ MODE DISPLAY EXTENDER BOARD INPUTS  
The Display Extender Board is used with New Zealand operation only. The inputs it  
provides are : Silence Alarms, Trial Evac, Building Services Restore, Lamp Test and  
External Defect. All inputs have closure to zero volts to assert the input. An input may be  
left open or unconnected if not used. Refer to section 12.8 for wiring.  
All Inputs  
Closure below 1.5V @ 0.35mA required to activate.  
Open voltage = 5V  
Issue 2.7  
5 July 2001  
Page 3-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
3.5  
OUTPUT SPECIFICATIONS  
3.5.1  
8 ZONE MODULE OUTPUTS  
Darlington open collector  
Type  
Switch to 0V  
Voltage Rating  
Current Rating  
28.5V max, "off" state  
1V max @ 30mA, "on" state  
1.1V max at 100mA  
100mA max per O/P, 0.6A max per module  
1A max per FIP.  
Transient Protection  
Terminations  
Allows external wiring  
8 Way demountable screw terminal  
1.5sq mm max. cable  
Operation  
Default  
Programmable  
O/C 1 = Zone 1 Alarm  
O/C 2 = Zone 2 Alarm  
etc.  
3.5.2  
8 RELAY MODULE OUTPUTS  
Form  
1 Pole changeover contacts  
Voltage-free when unsupervised  
Termination  
Rating  
Demountable screw terminals  
1.5sq mm max cable  
ELV only  
30V, 2Adc resistive  
30V, 1Adc inductive  
Note The relays are 2 pole, with the second pole terminated on pcb pads.  
Operation  
Programmable  
Ref 3.4.4.  
Supervision  
Looping Terminals  
2 Sets of 4 joined  
voltage-free terminals per module  
Page 3-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
3.5.3  
MAF/PSU OUTPUTS  
Brigade Relays  
Number  
Standby  
4
Normally energised  
De-energises on battery fail or panel fail  
Fault, Isolated, Alarm  
Form  
Normally de-energised  
Energise on active state  
1 Pole changeover contacts  
Voltage-free  
Termination  
Rating  
Demountable screw terminals  
1.5sq mm max cable  
ELV only  
30V, 5Adc resistive  
30V, 3Adc inductive  
Isolation  
1500V rms contact to coil  
Ancillary & Bells  
Number  
3
Anc 1, Anc 2  
1 Pole changeover contacts  
Voltage-free  
Termination  
Rating  
Demountable screw terminals  
1.5sq mm max cable  
ELV only  
30V, 2Adc resistive  
30V, 1Adc inductive  
(Note: The relays are 2 pole, with second pole terminated on pcb pads).  
Operation  
Default  
Programmable  
Active on any unisolated Zone Alarm.  
Separate terminal (ref 3.4.2)  
Supervision  
Anc 3/Bells  
2 pole relay  
Link selectable function  
Standard Format  
Bells  
Switched 24Vdc output  
2 terminals, Bells +, -  
Demountable screw terminals  
1.5sq mm max cable  
Issue 2.7  
5 July 2001  
Page 3-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
MAF/PSU OUTPUTS (CONTINUED)  
Option  
1 Pole changeover contacts  
Voltage-free  
Snip Links Lk2, 3, 4.  
Rating  
ELV only  
30V, 2Adc resistive  
30V, 1Adc inductive  
24V, 1.5Adc inductive bells  
Operation  
Default  
Programmable  
Active on any unisolated zone alarm  
Supervision  
On Bells +, - only  
(ref 3.4.2)  
Power Supply Outputs  
0Vdc  
Termination  
1 non-demountable screw terminal  
4sq mm max cable  
2 demountable screw terminals  
1.5sq mm max cable  
1 2.8mm tab terminal (LED Display)  
Battery Backed DC Supply  
Rating  
27.3Vdc nom.  
(24V battery nom)  
2Adc, fused.  
+VBF1  
Termination  
1 non-demountable screw terminal  
4sq mm max cable  
1 demountable screw terminal  
1.5sq mm max cable  
+VBF2  
Termination  
1 non-demountable screw terminal  
4sq mm max cable  
1 demountable screw terminal  
1.5sq mm max cable  
1 2.8mm tab terminal (LED Display)  
Page 3-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
MAF/PSU OUTPUTS (CONTINUED)  
Non-Battery Backed DC Supply  
Rating  
28Vdc nom  
2Adc, fused  
+VNBF  
Termination  
1 non-demountable screw terminal  
4sq mm max cable  
1 demountable screw terminal  
1.5sq mm max cable  
RZDU Comms  
Tx, Rx, 0V  
3 Wire (+VBF2 also available)  
1200 Baud  
Transmission Rate  
Protocol  
Vigilant F4000  
Termination  
Demountable screw terminals  
1.5sq mm max cable  
3.5.4  
CONTROLLER/DISPLAY OUTPUTS  
Spare Parallel Outputs  
(not fitted)  
Number  
6
Type  
CMOS  
Voltage Rating  
Termination  
Serial I/O  
0-5V  
10 Way FRC pcb header, J10  
Printer/Programmer Port  
Form  
Pseudo RS232  
Rx, Tx, 0V signals only  
Transient Protection  
Transmission Rate  
Protocol  
Allows external wiring  
9600 Baud  
ASCII Xon, Xoff  
Termination  
4 Way .156" male molex (J1)  
9 Way Miniature D available via transition cable  
Part number LM0041  
Female Pins (socket)  
Issue 2.7  
5 July 2001  
Page 3-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
CONTROLLER/DISPLAY (CONTINUED)  
Pin 2 3 5 1  
4
6 7  
8
Tx Rx 0V └──┴──┘ └──┘  
25 Way Miniature D available via transition cable Part Number  
LM0042  
Female Pins (socket)  
Pin 2 3 7 6  
8
20  
Rx Tx 0V └──┴──┘  
Alternative Function  
(on same serial port)  
Serial Port 0  
10 Way FRC header, J2  
UART signals: RXD, TXD, RTS-, CTS-, DCD-  
5V levels; 0V, +5V, +24V also available  
Network 1  
Network 2  
10 Way FRC header, J7  
(fitted only for network systems)  
10 Way FRC header, J9  
(fitted only for network systems)  
UART signals for Network 1/2  
RXD, TXD, RTS-, CTS-, DCD-  
5V levels; 0V, +5V, +24V also available  
3.5.5  
RS485 BOARD  
CMOS Modem:  
10 Way FRC header  
+12V, RXD- TXD-, RTS-, CTS-, 0V, DCD-, +5V  
Network:  
6 Way demountable screw terminals  
RS485 standard signals  
A+, A-, B+, B-, 0V ISOL, Earth  
3.5.6  
NZ DISPLAY EXTENDER BOARD OUTPUTS  
This is used in New Zealand mode only. Refer to section 12.8 for wiring of the outputs on  
the unprotected termination board. The Display Extender Board already has common  
Normal, Defect and Fire status LEDs fitted to it, but these may be replicated externally if  
necessary. There are also ancillary defect and fire outputs which are active low open  
collector, and an output to drive an index lamp.  
All Outputs (except LAMP)  
Open collector pulldown to 0V  
Off voltage = 30Vmax  
On voltage = 1.1V @ 100mA (max)  
On Current = 100mA max  
LAMP +  
Open collector pull up to VBATT  
Off voltage = 0V  
On voltage = VBATT-1V  
On current = 400mA max  
LAMP -  
Connected to Battery –  
Page 3-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
System Specifications  
3.6  
CONTROLS  
KEYPAD  
Type  
:
:
Polyester Membrane  
Buzzer gives short "beep" for valid keypress  
Keypress  
Number of  
Keys  
FFCIF Keys  
Other Keys  
:
:
:
34 (plus 5 concealed with no function)  
ACK; RESET; ISOL; BRIG TEST  
Ref F3200 Operator's Manual for description  
INTERNAL CONTROLS  
Mains On Switch in cabinet  
Database Write Protect  
:
Function  
Form  
:
:
Enables/disables writing to EEPROM  
2 position minijump shunt, Lk7  
On Controller/Display PCB  
E2 INIT  
Function  
:
:
Initiates self-programming of system configuration on system power  
up (i.e. number of modules, etc)  
Requires DATABASE WRITE PROTECT to be in WRITE position.  
Form  
2 Way .1" male pins on Controller/Display PCB  
Short circuit pins to initiate.  
BUZZER  
Mounted on Controller/Display pcb  
Type  
Frequency  
:
:
Piezo Electric  
2800Hz nominal  
Sound Level :  
70dB min at 1m (outer door closed)  
Issue 2.7  
5 July 2001  
Page 3-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
System Specifications  
Document No: LT0122  
3.7  
DISPLAYS  
Standard Display  
Includes  
:
:
:
:
:
LCD; FFCIF LEDs; System Status LEDs  
19", 4U  
3 (common indicators & common controls)  
Complies with AS4050 (int) - 1992  
2 Lines of 40 characters  
Panel Size  
FFCIF Type  
Standard  
LCD Size  
5.5mm (H) x 3.2mm (W) per character  
40 Characters max.  
30 Characters max.  
Site Name  
Zone Name  
Relay Name  
:
:
:
30 Characters max.  
FFCIF LEDs :  
System  
Status LEDs :  
ALARM (red); ISOLATED (yellow); FAULT (yellow)  
MAINS ON (green); CHGR/BATT FAULT (yellow); SYSTEM FAULT  
(yellow); ANCILLARY ISOLATED (yellow); BELLS ISOLATED (yellow)  
Mains On (green), Fuse Blown (yellow) on MAF/PSU pcb.  
Internal  
Status  
LEDs  
:
Optional Additional Display  
Requires 1 x ME0060 plus:  
1 x FZ3031 plus 1-3 FP0475 as required.  
Note: FZ3031 contains the FRC cable (LM0092) that is  
required to connect the Controller Board to the first  
Display Board.  
ME0060, MECH ASSY, 1901-79, F4000 RAC, EXT INNER DOOR  
(19", 7U, mounts up to 4 of 16 Zone LED Display Bd)  
FP0475, FP, 16 ZONE LED DISPLAY EXTENDER KIT, 1901-26  
Includes  
:
1 x 16 Zone LED Display Bd; FRC; Power leads; zone name label  
(FP0475 has 0.5m FRC, FZ3031 has 1.2m FRC).  
Format  
:
7U Parallel LED display mounts directly below the standard 4U LCD.  
The LCD and common LEDs operate as per standard. Zone status is  
additionally shown on the zone LEDs.  
FFCIF Type  
Zone LEDs  
:
:
2 (individual zone indicators and common controls)  
ALARM (red); FAULT (yellow); ISOLATED (yellow)  
Name Space :  
10mm x 60mm per zone on paper label.  
E.g. 2 lines of 23 characters at 10 per inch.  
Page 3-20  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Ordering Information  
CHAPTER 4  
ORDERING INFORMATION  
Issue 2.7  
5 July 2001  
Page 4-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Ordering Information  
Document No: LT0122  
4.1  
ORDERING INFORMATION  
The following lists the part numbers for the range of products and spares associated with the  
AS1603.4 approved F3200. It includes a brief description where considered necessary.  
FA1227,FAB,1931-24,F3200 BLANK PANEL,PLASTIC,9.5U  
FA1235,FAB,1919-27-5,F3200,FLUSH SURROUND (P) (STD CABINET)  
FA1298,FAB,1919-27-6,F3200,SMALL FLUSH SURROUND (P)  
FA1299,FAB,1919-27-7,F3200,STD + BATT BOX,FLUSH SURROUND (P)  
FA1300,FAB,1919-27-8,F3200,SMALL + BATT BOX,FLUSH SURROUND (P)  
FP0475,16 ZONE LED DISPLAY EXTENDER KIT,1901-26  
(includes Display Bd, 0.5m FRC, power leads and label master. Cannot be used for first  
LED Display. See FZ3031)  
FP0550,F3200 FIP,NO CARDFRAME,24 ZONE MAX,1931-15  
(ref Section 3.1.1)  
FP0551,F3200 FIP,C/W CARDFRAME,64 ZONE MAX,1931-16  
(ref Section 3.1.1)  
FP0553,F3200 8 ZONE INPUT EXPANSION KIT  
(ref Section 3.1.2)  
FP0554,F3200 8 RELAY EXPANSION KIT  
(ref Section 3.1.2)  
FP0556,F3200 CABINET,EMPTY,C/W DOOR,WINDOW,LOCK  
FP0557,F3200 CABINET,EMPTY,C/W BLANK OUTER DOOR  
FP0558,F3200 REMOTE LCD DISPLAY UNIT, FULL CABINET & MAF/PSU  
Similar to FP0550, but with RDU Controller and Software, No 8ZM. Previously called RZDU.  
Refer to manuals LT0133 and LT0148.  
FP0559,F3200 REMOTE LCD,DISPLAY UNIT,SLIMLINE,WALL MOUNT  
(small, low profile cabinet with F3200 RDU Controller fitted, no MAF or PSU)  
FP0570,FP,1937-3-1,LOCAL GAS CONTROL STATION,AUTO  
(wall mounting box with flip cover break glass "Gas Start" switch and double action toggle  
"Gas Inhibit" switch, includes buzzer and LEDs)  
FP0572,FP,1937-3-2,LOCAL GAS CONTROL STATION,MANUAL  
(as per above, but without "Gas Inhibit" switch, LED and buzzer)  
FP0576,FP,F3200,BATTERY BOX  
FP0577,FP,REMOTE LCD DISPLAY UNIT,4U 19" RAC UNIT  
(Includes ME0064 plus I/F PCB, FRC, earth wire, RDU, Operator's Manual, door switch (c/w  
bracket and loom) and MCP loom).  
FP0583,FP,F3200 FIP,SMALL CABINET  
FP0584,FP,F3200,SMALL EMPTY CABINET,FULL WINDOW  
FP0585,FP,REMOTE LCD DISPLAY,SMALL CABINET,C/W MAF/PSU  
Page 4-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Ordering Information  
ORDERING INFORMATION (CONTINUED)  
FP0712,FP,F3200 FIP,NO CARDFRAME,24 ZONE MAX,6A PSU  
FP0713,FP,F3200,FIP,64 ZONE MAX,6A PSU  
FP0714,FP,NETWORK DISPLAY UNIT (NDU),SLIMLINE,WALL MOUNT  
FP0715,FP,NETWORK DISPLAY UNIT (NDU),FULL CAB & MAF/PSU  
FP0731,FP,RDU TO NDU UPGRADE KIT  
FP0733,FP,NETWORK DISPLAY UNIT,4U 19" RACK MTG,NO MAF/PSU  
FP0749,FP,F3200 6A PSU UPGRADE KIT,1931-44  
Kit to purchase to upgrade on existing panel to a 6A PSU.  
FP0772,FP,REMOTE LCD DISPLAY (RDU),SLIMLINE,FLUSH MOUNT  
Same as FP0559 except is a flush mounting cabinet.  
FP0773,FP,NETWORK DISPLAY UNIT (NDU),SLIMLINE,FLUSH MOUNT  
Same as FP0714 except is a flush mounting cabinet.  
FP0774,FP,NDU,NETWORK DISPLAY,C/W I-HUB,SLIMLINE,SURFACE  
Surface mount NDU, contains I-Hub for networking.  
FZ3010,F3200,16 ZONE,STD CAB,NO CARDFRAME,NO LED,1U SHELF  
(FP0550 with second 8ZM and 1U document shelf fitted)  
FZ3024,F3200,8 ZONE,NO CARDFRAME,NO LEDS,7U BLANK,1U SHELF  
(FP0550 with 7U blank hinged door and 1U document shelf fitted)  
FZ3027,F3200,64 ZONE,C/W LEDS,1U SHELF  
FZ3031,KIT,F3200,16 ZONE LED DISPLAY,LHS POSITION  
(as per FP0475, but with 1.2m FRC, allows mtg of Display Bd in furthest left position.  
Required for first display).  
FZ3034,F3200,8 ZONE,NO CARDFRAME,NO LEDS,6A PSU  
FZ3051,F3200,1 ZONE GAS CONTROL,SMALL CABINET  
FZ9002,FP,19" RAC,7U BLANK INNER DOOR  
FZ9009,KIT,19" RAC,3U AIU BRKT (mounts 2 Melbourne F.B. AIUs)  
FZ9010,KIT 19" RAC,1U AIU BRKT (mounts 2 Melbourne F.B. AIUs)  
(These include bracket and screws, etc, The 1U item is 1U at the front, but larger at the rear,  
as required for F3200 small cabinet).  
KT0072,KIT,F3200,CARDFRAME UPGRADE  
KT0075,KIT,F3200,PSU UPGRADE,3A TO 6A,1931-44 (Factory fitted option only)  
KT0111 KIT,1945-1-1,AS1668 CONTROL MODULE,TYPE 1 (refer PBG0015)  
KT0112 KIT,1945-1-2,AS1668 CONTROL MODULE,TYPE 2 (refer PBG0015)  
KT0113 KIT,1945-1-3,AS1668 CONTROL MODULE,TYPE 3 (refer PBG0015)  
LM0041,LOOM,1888-58,PROG PORT TO 9 PIN SERIAL  
(cable to connect printer/computer to Controller, has 9 pin min D)  
Issue 2.7  
5 July 2001  
Page 4-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Ordering Information  
Document No: LT0122  
ORDERING INFORMATION (CONTINUED)  
LM0042,LOOM,1888-62,PROG PORT TO 25 PIN SERIAL  
(cable to connect printer/computer to Controller, has 25 pin min D)  
LM0044,LOOM,1901-81-1,DISPLAY EXTENDER FRC,2M  
LM0045,LOOM,1901-81-2,DISPLAY EXTENDER FRC,5M  
LM0046,LOOM,1901-81-3,DISPLAY EXTENDER FRC,0.5M  
LM0049,LOOM,1901-81-4,DISPLAY EXTENDER FRC,0.25M  
LM0053,LOOM,1931-28-1,F3200 20 WAY FRC,300MM  
(standard FRC for interconnecting 8 way modules, included in FP0553, 554)  
LM0092,LOOM 1901-88 CONTROLLER TO 1ST DISPLAY, FRC, 1.2M  
(connects Display Bd to Controller, allows mounting of Display Bd in furthest left position,  
included with FZ3031).  
LT0119 LITERATURE,1931-17,F3200 OPERATOR'S MANUAL,A4,LOOSE  
LT0120 LITERATURE,1931-18,F3200 OPERATOR'S MANUAL,A5  
LT0121 LITERATURE,1931-19,F3200 TECHNICAL MANUAL  
LT0122 LITERATURE,1931-20,F3200 PROGRAMMING & INSTALLATION MANUAL  
LT0130 LITERATURE,1931-32,F3200 PRESENTATION,ACAD12 DISK  
LT0133 LITERATURE,1931-46,REMOTE LCD UNIT,OPERATOR MANUAL,A4  
LT0135 LITERATURE,1931-52,F3200 ARCHITECTS SPEC,A4  
LT0148 LITERATURE,1931-64,RDU INSTALLATION & PROGRAM MANUAL  
LT0212 LITERATURE,RDU TO NDU UPGRADE INSTRUCTIONS  
ME0060,MECH ASSY,1901-79,RAC CABINET,EXT INNER DOOR  
(hinged 7U inner door for mounting Display Bds on, includes screws, perspex window, cage  
nuts and pcb standoffs)  
ME0063,MECH ASSY,1931-15-1,F3200 4U HINGED CONTROL PANEL  
(4U hinged door with keypad and Controller/Display pcb mounted on it).  
ME0064,MECH ASSY,1931-15-1,F3200 4U HINGED RDU CONTROL PANEL  
(4U hinged door with no-name keypad and RDU Controller/Display mounted on it).  
ME0065,MECH ASSY,1931-47,1 ZONE GAS CONTROL 7U DOOR  
ME0066,MECH ASSY,1931-47,2 ZONE GAS CONTROL 7U DOOR  
ME0067,MECH ASSY,1931-47,3 ZONE GAS CONTROL 7U DOOR  
ME0068,MECH ASSY,1931-47,4 ZONE GAS CONTROL 7U DOOR  
(ME0065-68 include screened 7U door, field connector and looms for connecting to 8RMS  
and 8ZMs, screws and cage nuts - for 1,2,3 or 4 gas zones)  
Page 4-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Ordering Information  
ORDERING INFORMATION (CONTINUED)  
ME0069,MECH ASSY,1931-57,1 ZONE, 1U GAS CONTROL PANEL  
(similar to ME0065 except on a non-hinged, 1U panel)  
ME0072,MECH ASSY,1931-70,F3200 RACK MTG GEARPLATE  
(allows F3200 internals to be fitted to a RAC cabinet. Factory fit option only. See Note 1)  
ME0155,MECH ASSY,694-384,19" 4U CFA ASSEMBLY  
ME0250,MECH ASSY,1919-35,RAC CABINET,IP65,20U X 200 (ie. waterproof)  
ME0258,MECH ASSY,1919-21-2,RAC CABINET,1U SHELF,135 DEEP  
(includes screws and cage nuts for mounting to FIP)  
PA0443,PCB ASSY,1841-18,CONTACT CONVERSION MODULE  
PA0491,PCB ASSY,1931-3,F3200 MAF/PSU  
PA0492,PCB ASSY,1931-4,F3200 8 ZONE MODULE (See FP0553)  
PA0493,PCB ASSY,1931-5,F3200 RZDU CONTROLLER/DISPLAY (See FP0554)  
PA0703,PCB ASSY,1931-27,F3200 REMOTE I/F BD  
PA0707,PCB ASSY,1931-39,F3200 3A RECTIFIER BD  
PA0773,PCB ASSY,1901-139-3,RS485 COMMS BD,CMOS;FRC ONLY  
PA0797,PCB ASSY,1931-84-1,F3200 CONTROLLER/DISPLAY  
PA0798,PCB ASSY,1931-84-2,F3200 RDU CONTROLLER/DISPLAY  
PA0804,PCB ASSY,1931-84-1,F3200 CTRL NETWORK/NDU,NO S/W  
RR0509,RESISTOR,WIRE WOUND,10W,68 OHM  
SF0089,SOFTWARE,F3200 FIRE CONTROLLER,V1.10 EPROM  
SF0094,SOFTWARE,REMOTE LCD DISPLAY,RDU,V1.35 EPROM  
SF0164,SOFTWARE,F3200 FIRE CONTROLLER NETWORKED,V2.04,EPROM  
SF0175,SOFTWARE,NETWORK DISPLAY UNIT (NDU),V2.04,EPROM  
SF0178,SOFTWARE,F3200 FIRE CONTROLLER,V2.04,EPROM  
SF0179,SOFTWARE,REMOTE LCD DISPLAY,RDU,V2.02 EPROM  
SF0229,SOFTWARE,F3200,STD PANEL,C/W TANDEM,V2.09 EPROM  
SF0230,SOFTWARE,F3200,NETWORKED,C/W TANDEM,V2.09,EPROM  
SF0231,SOFTWARE,NDU,C/W TANDEM,V2.09,EPROM  
Issue 2.7  
5 July 2001  
Page 4-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Ordering Information  
Document No: LT0122  
ORDERING INFORMATION (CONTINUED)  
NEW ZEALAND OPERATION ONLY  
A variety of display options are available to satisfy varying NZ requirements. These are  
covered in detail in Section 12.8. Ordering codes are included for the various components  
for each option. Major items are as follows:  
PA0499  
PA0742  
PA0741  
PA0754  
PA0753  
PCB ASSY, NZ DISPLAY EXTENDER BOARD  
NZ Display Extender Board in standard 16 Zone LED board format.  
PCB ASSY, PFD NZ DISPLAY EXTENDER BOARD, 24V  
NZ Display Extender Board in format suitable for “picture frame” cabinet.  
PCB ASSY, PFD 16 ALARM LED DISPLAY, 24V  
“Picture Frame” format 16 Zone display board (alarm LEDs only).  
PCB ASSY, PFD 16 ZONE FULL STATUS, 24V  
“Picture Frame” format 16 Zone display board (all LEDs fitted).  
PCB ASSY, PICTURE FRAME DISPLAY, 16 LED MIMIC, 24V  
“Picture Frame” cabinet format board for mimicking 16 Fire LEDs from Display  
board.  
PA0760  
PCB ASSY, NZ DISPLAY EXTENDER, PFD MIMIC  
“Picture Frame” cabinet format board for mimicking 3 LEDs from Display  
Extender Board.  
PA0483  
PA0772  
PA0769  
ME0074  
ME0076  
ME0073  
PCB, UNPROTECTED TERMINATION BOARD  
With a 26 way FRC gives access Display Extender Board inputs and outputs.  
PCB ASSEMBLY, PFD TERMINATION BOARD  
Breaks 26-way display FRC out to multicore cable (12 way).  
PCB, UNPROTECTED TERMINATION BOARD, C/W RESISTORS  
Versions of PA0483 with 3k3 resistor per output for LED current limit.  
PICTURE FRAME DISPLAY, F/S NZ LOCK, C/W INDEX  
Wall mounting “Picture frame” display cabinet.  
PICTURE FRAME DISPLAY, R/S NZ LOCK, C/W INDEX  
Window mounting, “Picture frame” display cabinet.  
PICTURE FRAME DISPLAY, F/S 003 LOCK, C/W INDEX  
Wall mounting “Picture frame” display cabinet with 003 lock.  
Page 4-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Configuring a FIP  
CHAPTER 5  
CONFIGURING A FIP  
Issue 2.7  
5 July 2001  
Page 5-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Configuring a FIP  
Document No: LT0122  
5.1  
GENERAL  
An F3200 FIP is configured to suit a particular customer's requirements by:  
Fitting and connecting the required pcb modules;  
adding appropriate battery test resistors when necessary;  
adjusting or removing links on the pcbs;  
programming the FIP.  
The detectors, manual call points (MCPs), warning devices, ancillary equipment and field  
wiring that are connected to the FIP must match the FIP configuration.  
The FIP configuration data, which is entered during programming, is stored in the non-  
volatile memory database. The database may be saved to a computer for backup storage,  
or reloaded from a computer.  
All programmable options have a default option for the most likely usage. That is, for many  
applications, no programming other than entry of site and zone names will be necessary.  
Programming is described in detail in Chapters 6, 7, 11 and 12. The rest of this chapter  
describes configuration of the hardware.  
5.2  
MODULE CONFIGURATION  
The required modules are fitted to the F3200 as described in Section 2.3.2. Note that 8 way  
modules are connected Bus Out to Bus In with all 8 Zone Modules preceding any 8 Relay  
Modules. (Refer also to Section 8.1.3).  
The F3200 does various self-tests on start up and includes checking to see what modules  
are present (including 16 Zone LED Display Bds). It displays the results on the LCD. If the  
modules present do not agree with the programmed database then the FIP annunciates this  
and remains inactive.  
E2 Initialisation causes the Controller/Display to accept the modules found as present and  
stores this configuration in the database. E2 Initialisation also clears all other data  
programmed in the database. Refer to Section 6.3.1.  
Where it is desired to add a module to an existing system this can be done by programming  
the Module Configuration through the keyboard (see Section 7.1).  
For servicing, modules can be temporarily removed as detailed in Section 10.2 of the  
Operator's Manual. This temporary configuration is not stored in the database.  
Page 5-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Configuring a FIP  
5.3  
BATTERY & POWER SUPPLY  
5.3.1  
GENERAL  
The F3200 FIP has a dc power supply, which also serves as battery charger and requires a  
24V sealed lead acid battery (i.e. 2 x 12V batteries in series) to be fitted. (See Section 3.3.3  
for compatible batteries). Battery leads with 4.8mm Quick Connect receptacles (for  
connecting to the battery tabs) are included.  
Charger Rating (Refer to AS1670.1 Section 8.2)  
The standard F3200 has a 3A power supply. Versions are also available with a 6A PSU.  
This has a second mains transformer, a 3A rectifier pcb and a larger heatsink connected to  
the MAF/PSU. Several components on the pcb are also upgraded.  
When a 6A power supply is fitted, the standard PTC on the MAF/PSU are shorted out and  
additional battery protection must be fitted (see Section 5.3.6).  
To comply with AS1670.1 the power supply rating must be sufficient to charge the batteries  
while powering the panel with 2 zones in alarm. This must include all remaining quiescent  
loads, common alarm load, plus 2 (or 20%, whichever is the larger) of all connected fire  
suppression systems in the active state (i.e. solenoids, warning signs, etc).  
The definition of charging the batteries is supplying enough current to charge them within 24  
hours to provide a capacity that will support 5 hours of FIP quiescent load (i.e. with mains  
off) followed by 0.5 hour of alarm load for two worst-case zones.  
The recommended order of performing calculations is listed in Section 5.3.2.  
Battery Rating (Refer to AS1670-1 Section 8.2).  
The battery capacity must be sufficient to support 24 hours of quiescent load (i.e. with mains  
off), followed by 0.5 hour of alarm for the two worst case zones.  
Notes  
1.  
2.  
3.  
The quiescent load includes the FIP electronics (in normal state) plus any external  
normally energised loads that operate from the battery backed supply. Hence door  
holders are normally supplied from a non-battery backed supply.  
Alarm load includes FIP electronics (in alarm state) plus any external loads such as  
bells, air conditioning shutdown relays, etc, plus the 2 (or 20%) fire suppression  
zones.  
The capacity of a battery depends on the rate (i.e. current) at which it is discharged.  
Most batteries are quoted at a 20 hours discharge e.g. a 10Ahr battery will supply  
0.5A for 20 hours. At 3 times the current (i.e. 1.5A) the same battery will discharge in  
typically 5.6 hours, i.e. the capacity is only 8.5Ahr. At 10 times the rate the capacity  
is approximately 75% of the 20 hour rate capacity (i.e. 7.5Ahr). Hence for alarm  
loads it is safest to derate the capacity to 75%.  
Issue 2.7  
5 July 2001  
Page 5-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Configuring a FIP  
Document No: LT0122  
GENERAL (CONTINUED)  
4.  
The approvals laboratory recommends using 90% derating of batteries used on  
F3200 because the battery fail voltage (Standby) is 22V instead of 21V (as used on  
some other FIPs). The local approval body may not require this, however, because  
although the F3200 will not generate new alarms below the "battery fail voltage", it  
will maintain any alarms and outputs that occurred when the voltage was higher than  
the battery fail voltage. AS1670.1 1995 does, however, recommend 80% derating of  
batteries for the effect of ageing, ie. multiply the required battery capacity (at end of  
life) by 1.25 when calculating the required capacity for a new battery.  
5.  
For maximum physical battery sizes refer to "Battery Size". (Refer to Section 5.3.4).  
5.3.2  
BATTERY/CHARGER CALCULATIONS  
The recommended order of calculations is as follows:  
1.  
Calculate the FIP quiescent load (Iq) from the figures given in Section 3.3.5. Note  
that the detector load for each AZC has to be added to the quiescent current per  
AZC. Calculate In separately, where In is the external non-alarm, non-battery  
backed load on the FIP PSU (e.g. door holders).  
2.  
3.  
Calculate the FIP alarm load (Ia) for 2 zones in alarm from Section 3.3.5. (Include all  
external loads e.g. bells, relays).  
Calculate the 5 hour/0.5 hour battery capacity for the charger requirement as follows:  
Cap (5 hr) = (5 x Iq) + (0.5 Ia x 1.33) Ahr  
= 5Iq + 0.66Ia where  
Iq = quiescent current  
Ia = alarm current  
Note that the 1.33 multiplier increases the required capacity to allow for an alarm  
load of up to 10 times the quiescent load (i.e. 75% derating of capacity).  
4.  
5.  
Find the greater of Iq + In, or Ia. Calculate the power supply/charger requirement (Ic)  
as follows and check that it is less than 3A. (If greater a 6A charger is required).  
Ic = I + Cap (5 hr) ÷ 24e where I is the greater of Iq + In, or Ia, and e is the changing  
efficiency of the particular battery being used, at the current being used (typically  
80%, ie. (cap/24) x 1.25).  
Calculate the battery capacity as follows:  
Cap (24 hr) = (24 x Iq + 0.66 Ia) x 1.25  
(See note 4 of Section 5.3.1 regarding the x 1.25 multiplier).  
Select a battery which has a rated capacity (i.e. 20 hr rating) equal to or above that  
just calculated. (Refer to Sections 3.3.3 and 5.3.4 for approved types).  
Page 5-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Configuring a FIP  
5.3.3  
EXAMPLE BATTERY/CHARGER CALCULATIONS  
An example FP0551 FIP has the following configuration:  
3 8ZMs total (i.e. 2 x FP0553 expansion modules fitted)  
1 8RM fitted  
20 AZCs enabled, 4 disabled  
42mA total detector current on the 20 AZCs  
350mA of door holders off +VNBF  
5 relays on the 8RM used, with supervision enabled, all switching 24V, 50mA relays,  
normally de-energised.  
Ancillary relay 1 (on the MAF) switching a 24V, 100mA load  
A Bell circuit with 0.75A of 24V bell load.  
Calculate the required battery capacity and check the power supply load.  
Steps  
1.  
The quiescent load (Iq) for the mains fail situation is:  
130mA (FIP including one 8ZM)  
+
+
82mA (second 8ZM, all AZCs enabled)  
4mA (third 8ZM, basic current only)  
+ 4 x 10mA (third 8ZM, current for 4 AZCs)  
+
+
42mA (detector current)  
6mA (8RM, supervision enabled)  
304mA  
Say Iq = 0.30A for mains off.  
The quiescent load for mains on is Iq plus the door holders (In = 0.35A) i.e. 0.65A.  
2.  
Say, for example, that the 2 zones in alarm can, at most, turn on 3 of the 5 module  
relays plus all the bells and the Anc 1 load.  
The alarm load for 2 zones in alarm is therefore:  
275mA (FIP including 1 8ZM, 2 zone alarm, MAF relays)  
+
+
+
+
82mA (second 8ZM, quiescent only)  
44mA (third 8ZM, quiescent only)  
42mA (detector current)  
6mA (basic 8RM current)  
+ 3 x 11mA (3 relays on 8RM)  
+ 3 x 50mA (loads on 3 relays)  
+
+
100mA (Ancillary 1 relay load)  
750mA (Bells load)  
1482mA  
Say Ia = 1.48A (the door holders are switched off in alarm).  
Cap (5 hr) = 5 x 0.3 + 0.66 x 1.48 Ahr = 2.49 Ahr  
Battery charger current required is:  
3.  
4.  
Ia (1.48A) is greater than Iq + In, (0.65A), therefore:  
Ic = 1.48A + (2.49/24) x 1.25 = 1.61A (where the 1.25 allows for charging efficiency e  
of 0.8) i.e. 3A is sufficient.  
5.  
Battery capacity  
Cap (24 hr) = [(24 x 0.3) + 0.66 x 1.48] x 1.25 = 10.2Ah.  
Issue 2.7  
5 July 2001  
Page 5-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Configuring a FIP  
Document No: LT0122  
Suggest that two 12V, 10 Ahr sealed batteries from list in Section 3.3.3. would be  
adequate (or next size up, e.g. 17 Ahrs).  
Note that these require a 68E, 10W battery test resistor to be fitted to the tabs on the  
MAF/PSU as described in Section 5.3.5.  
5.3.4  
BATTERY SIZE  
The maximum battery size given in the specification, Section 3.3.3, of 220mm x 220mm x  
175mm, is imposed by the cardframe, which obstructs insertion and removal of batteries in  
the bottom of the cabinet.  
The maximum sizes which fit within this size are:  
Sonnenschein  
Powersonic  
Yuasa  
Century Yuasa  
IRH BB Battery  
Panasonic  
A212/36A  
PS-12400  
NP38-12  
PS-12400  
BP40-12  
LC-X1242P(AP)  
NP38-12  
36 AHr  
40 Ahr  
38 Ahr  
40 Ahr  
40 Ahr  
42 Ahr  
38 Ahr  
YHZ Power  
If batteries larger than this are required, then the cardframe can be made removable by  
replacing the 3 pop rivets with M4 or M5 screws and nuts.  
For an FP0550, or an FP0551 with a removable cardframe, the maximum allowable size is  
220H x 260W x 175D.  
The maximum sizes which fit within this restriction are:  
Sonnenschein  
Powersonic  
Yuasa  
A212/50A  
PS-12600  
NP38-12  
50 Ahr  
60 Ahr  
38 Ahr  
Fitting and removing batteries of this maximum size is difficult, and may require the removal  
of any modules or brackets fitted in the bottom of the cabinet.  
These very large size batteries may also impede the plugging in and removal of modules  
fitted to the bottom position of the cardframe.  
Battery Combinations  
Large capacity batteries can be made up of two parallel sets of 24V batteries of smaller  
capacities. This allows easier fitting, and allows larger capacities, and a greater range of  
capacity, to be achieved than is possible with a single pair (as indicated above).  
Examples of combinations that will fit in an FP0551 with no cardframe removal required.  
1.  
2 Powersonic PS-12330 (33 Ahr) batteries in parallel with 2 Powersonic PS-12100  
(10 Ahr) batteries gives a total of 43 Ahr.  
2.  
2 sets of 2 Powersonic PS-12280 (28 Ahr) will provide 56Ahr and will fit side by side  
on the bottom of an FP0551.  
Page 5-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Configuring a FIP  
5.3.5  
BATTERY TEST RESISTORS  
The standard battery test resistor is suitable for a battery of capacity of up to 6.5AHr.  
For larger batteries, additional resistors must be fitted, either directly to the MAF/PSU pcb (in  
R34 and/or between Battery Test tabs), or within the FIP and wired to the Battery test tabs.  
Where the additional resistors are carrying a current of greater than 0.7A, a 24Vdc relay  
must be fitted to switch the load as shown in Fig 5.3.1. (Note the diode polarity, the end is  
marked on the case).  
Battery test current is calculated as 0.1C at 25V where C is the battery ampere hours. E.g.  
1A test current is required for a 10Ahr battery.  
The standard battery test current of 0.65A includes FIP quiescent current. Table 5.3.1  
shows the additional battery test resistors that must be fitted for various battery sizes. It is  
calculated using the quiescent current of a base FP0550 (or FP0551). In general, a FIP  
requiring larger batteries will have a higher quiescent current than that of a base FP0550,  
and so a smaller additional test current than that shown could be used.  
Because the battery test runs only for 1 minute and is then disabled for greater than 1  
minute, resistors may be used at full power rating, or even slightly greater. (Resistors of  
power ratings greater than that shown may be used).  
Total  
Test  
Current  
A
Additional  
Test  
Current  
A
Relay  
Resistor  
Combination  
Ohms/Watts  
Battery  
Capacity  
Ahr  
Additional  
Resistance  
Ohms  
Rating  
Amps  
(at 24Vdc)  
6.5  
10  
17  
.65  
1.0  
1.7  
-
-
-
-
.35  
1.05  
71.4  
23.8  
68E 10W  
-
22E 20W  
OR 27E 20W//  
180E 5W  
2
28  
2.8  
2.15  
11.6  
12E 50W//  
330E 2W  
2.5  
OR 10E 50W  
33  
40  
3.3  
4.0  
2.65  
3.35  
9.43  
7.46  
10E 50W//  
150E 5W  
3
4
15E 50W//  
15E 50W  
OR 10E 50W//  
27E 20W  
60  
6.0  
5.35  
4.67  
4E7 100W  
OR 10E 50W//  
10E 50W//  
68E 10W  
6
Note : // means "wired in parallel with".  
TABLE 5.3.1  
BATTERY TEST RESISTORS  
Issue 2.7  
5 July 2001  
Page 5-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Configuring a FIP  
Document No: LT0122  
A.  
B.  
FOR ADDITIONAL TEST LOAD GREATER THAN 0.7A AND ALARM  
LOAD/CHARGER CURRENT LESS THAN 3A.  
FOR ALARM LOAD/CHARGER CURRENT GREATER THAN 3A.  
FIG 5.3.1  
CONNECTION OF BATTERY TEST RELAY/RESISTOR  
Page 5-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Configuring a FIP  
5.3.6  
BATTERY OVERCURRENT PROTECTION  
The MAF/PSU has two parallel PTCs, rated to carry over 3A, for battery overcurrent  
protection.  
Where the Alarm load from the battery to FIP is greater than 3A (i.e. with mains failed), or  
where a 6A power supply is used, an external, self-resetting, overcurrent device of suitable  
rating (greater than 6A, less than 35A e.g. Derwent, 10A Type D (connected to pins 1 and  
3)) must be wired between the battery terminals on the MAF/PSU and the battery (see Fig  
5.3.2). For this option the PTCs must be shorted by soldering a suitable copper wire  
between the two adjacent test points +VB and BATT+ (TP11 and TP16 on the MAF/PSU).  
For a FIP supplied with a 6A PSU, this is done in the factory and the Derwent cut-out is  
included.  
FIG 5.3.2  
BATTERY OVERCURRENT PROTECTION FOR LOADS GREATER THAN 3A  
5.3.7  
POWERING AN F3200 FROM AN EXTERNAL DC SUPPLY  
To comply with AS1670.1 F3200 uses a 240Vac supply as the primary power source and  
back-up batteries as the secondary power source. However the F3200 may be powered  
from an external dc supply. This must be battery backed, or have another form of secondary  
source to comply with AS1670.1. The supply must provide a voltage and current within  
F3200’s operating range (preferably 25-27Vdc).  
The following wiring instruction connects the dc supply voltage onto the ac (low voltage)  
input so that the Mains on LEDs on both the MAF/PSU and Controller PCBs are illuminated.  
Because this signal is not ac, the Controller generates a ‘Mains Fail’ condition and  
automatically disables the charger monitoring and battery tests.  
With no mains (ac) present the real time clock (RTC) on the Controller Display will use the  
crystal time base instead of mains 50Hz and will therefore not be as accurate. The accuracy  
of the clock can be improved by installing V3.XX F3200 software instead of V2.XX software.  
Refer to LT0255/LT0256.  
Issue 2.7  
5 July 2001  
Page 5-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Configuring a FIP  
Document No: LT0122  
POWERING AN F3200 FROM AN EXTERNAL DC SUPPLY (CONTINUED)  
Without a mains connection, F3200 will indicate “Mains Fail” in a system fault recall but this  
is not actually a fault and can be ignored.  
WIRING  
Disconnect the secondary wires of the transformer from the AC IN tabs on the MAF/PSU.  
Cable tie them safely out of the way (if the mains is not connected they will not be live).  
Connect the DC supply –ve to the BATTERY – terminal, and the +ve to the BATTERY +  
and, if the mains power on LED is to be lit, to the J3/1 AC IN tab on the MAF/PSU. This  
requires a 2mm crimp receptacle (or alternatively may be soldered and preferably covered  
with sleeving).  
If the maximum alarm load can be greater than 3.5Adc, but less than 7A, fit a second PTC  
(Vigilant part RR0917) to the R43 position on the MAF/PSU (adjacent to the existing PTC,  
R42). If the alarm load can be greater than 7A then short out the PTCs (connect TP16 to  
TP11) and fuse the external supply with a sufficient rating to meet the maximum alarm load,  
but not so high as to not blow on a short circuit or wiring fault.  
The +VNBF output (J7A) must not be used.  
CURRENT CALCULATIONS  
Add an extra 80mA to the stated F3200 quiescent and alarm currents if the connection to the  
J3/1 AC IN terminal is made (the connection to J3/1 is optional).  
PROGRAMMING  
If battery low monitoring is enabled, a Battery Low Fault will occur if the supply voltage falls  
below a specified threshold.  
If the version of software installed supports them (not all do), then the following parameters  
should be set as shown. All values are disabled by default.  
Mains fail is fault after 8 hours  
Charger high/low fault  
Battery connection monitoring  
Hourly battery test  
Daily 40 min battery test  
Battery low monitoring  
-
-
-
-
-
-
disable  
disable  
disable  
disable  
disable  
enable/disable as desired  
Page 5-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Configuring a FIP  
5.4  
LINKS ON PCB MODULES  
5.4.1  
CONTROLLER/DISPLAY  
Apart from E2INIT (SW1) and DATABASE WRITE PROTECT/ENABLE (Lk7) all links on the  
Controller Display are factory set. (These configure the pcb for memory chips used, other  
functions, and type e.g. as a FIP Controller or an RZDU Controller).  
SW1 and Lk7 are described in Section 6.3.1.  
5.4.2  
MAF/PSU  
Of the 4 links on the MAF/PSU, 3 are for field adjustment as follows:  
Lk2-Lk4  
Bells/ANC 3  
-
-
Fitted in factory to provide switched 24V output.  
(Bells+, Bells-).  
Snip all 3 for clean changeover contacts (NO,  
COM, NC).  
Note that Lk2-Lk4 must remain fitted if Bells supervision is required (No links are required for  
Ancillary Relay 1, 2 supervision).  
One is for factory configuration as follows:  
Lk1  
Master/RZDU  
-
-
Fitted for Master.  
Snipped for RZDU (3-wire isolated connection  
to FIP).  
5.4.3  
8 RELAY MODULE  
The 8 three position links (Lk1-Lk8) select load supervision for each relay.  
U <-> unsupervised (voltage free)  
S <-> supervised  
The default setting (factory set) is unsupervised. Note that in addition to shifting the  
minijump for supervision, supervision must be enabled during programming.  
5.4.4  
16 ZONE LED DISPLAY  
The last Display Bd in the chain (i.e. in furthest left position as viewed from the front)  
requires the minijump provided to be fitted to Lk1.  
Issue 2.7  
5 July 2001  
Page 5-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Configuring a FIP  
Document No: LT0122  
5.5  
ERROR MESSAGES DURING FIP CONFIGURATION  
Listed below are some error messages that can appear on the LCD during installation.  
Refer also to Section 6.6.3 System Faults in the Operator Manual LT0119.  
Error messages that can occur on startup or exit from program mode  
"Shift reg clocking fault"  
"Invalid # shift regs.Total # regs=xxx # input regs=xxx"  
These messages indicate a hardware fault with the shift register bus that connects the  
Controller, MAF/PSU, 8 Zone, and 8 Relay modules. The fault could be on the Controller,  
the interconnecting FRCs or any of the connected boards. Try connecting just the MAF/PSU  
on its own and with different cables to isolate the problem.  
"Shift reg driver fault"  
This message indicates a problem with the software driver for the shift register bus.  
"Clock crystal timebase check fail"  
This message indicates a hardware fault on the Controller.  
"Clock chip ram write read fail"  
"Clock register write read fail"  
"Clock startup fault"  
These messages indicate a hardware fault on the Controller.  
"Eprom CRC fail"  
This message indicates the checksum of the software program code is incorrect. This can be  
caused by a damaged EPROM or some other hardware fault on the Controller.  
Error messages that can occur on entry to program mode  
"This database is invalid and should be reinitialised-net dbase in non net panel"  
This message is produced on entry to program mode when a database created with  
networked F3200 or NDU software is used with non-networked software. This is unusable  
and the database should be re-initialised and reprogrammed.  
Page 5-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
CHAPTER 6  
PROGRAMMING  
Issue 2.7  
5 July 2001  
Page 6-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
6.1  
INTRODUCTION  
6.1.1  
GENERAL  
The F3200 has two main levels of programming. The first level is accessible to the Operator  
(via the keypad) and does not require entry of an access code. It allows the setting of  
parameters, such as time and date, which do not affect the basic structure of the system.  
The second level allows entering of data into the database to configure the operation of the  
FIP. It is accessible only by fitting the WRITE ENABLE link on the Controller and entering  
an access code on the keypad. When this level has been accessed, Alarm and other I/O  
processing is stopped.  
The FIP can be programmed from the keypad and the database can be saved to a  
computer, and restored from a computer, in binary format. (Currently, the database can not  
be configured off line on a computer. It can only be configured from the FIP keypad).  
It is recommended that, for each FIP, configuration sheets specifying Text and all  
parameters, be filled out before programming commences. Some suggested master sheets  
are included in Appendix B. A set of completed sheets should be kept in the contract file.  
NOTES  
1. When filling out configuration sheets it is only necessary to record any non-default  
parameters.  
2. It is necessary to install and configure the modules before the other programming,  
such as text entry, is performed.  
The recommended order of configuration and programming is shown in Section 6.1.4.  
6.1.2  
MENU STRUCTURE & PARAMETER ENTRY  
The Programming menu structure of the F3200 takes the form of an inverted tree, with a  
display screen for every branch. Each screen shows an item with parameters to be  
changed, a prompt, or a menu of options.  
Options are normally preceded by numbers, and the desired choice is made by pressing the  
appropriate digit on the numeric keypad (1-9).  
The general method of programming is to step down the branches of the tree by selecting  
options until the sub-level which contains the items to be programmed (e.g. Configure  
Zones) is reached. Items (e.g. Zone 1, Zone 2, etc) can be stepped through by use of the  
"NEXT" and "PREV" keys.  
When an item is selected, the attributes (e.g. MAF Mapping) are selected by use of the  
horizontal cursors (! "). For each attribute selected the options are displayed. Options  
(e.g. N for non-mapped, M for mapped) are selected by use of the vertical cursor (#), or, in  
cases where there are more than two choices, pressing the digit associated with the desired  
option.  
When all the desired attributes for an item have been selected they are saved into the  
database (where applicable) by pressing "ACK".  
The "CLEAR ESC" (Escape) key is used to return up levels in the menu tree. To get from  
one branch of the tree to another branch of the tree, generally "CLEAR ESC" must be  
repeatedly pushed until the menu option gives the choice of the two branches.  
Page 6-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
GENERAL (CONTINUED)  
If "CLEAR ESC" is pressed enough times, the programming mode display is exited and the  
database checksum is calculated.  
BASE DISPLAY  
PRESS “SET” KEY  
TO ENTER  
FIG 6.1.1  
MENU STRUCTURE  
Details of the programming menu are shown in Figures 6.1.2A-C.  
Figure 6.1.2A is for V1.00 and V1.01 software  
Figure 6.1.2B is for V1.10 software  
Figure 6.1.2C is for V2.0X software, noting that some commands are only available from  
specific versions onwards.  
Fig 6.1.2C and 6.1.2D1/D2 are for V2.0X software but note that some options are not  
provided in “older” software versions.  
Issue 2.7  
5 July 2001  
Page 6-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
THIS PAGE LEFT INTENTIONALLY BLANK  
Page 6-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
6.1.3  
PROGRAMMING KEYS  
Looking at the keypad (or picture in Fig 2.1.2) the user will observe a 4x4 "numeric" keypad,  
and a row of function keys across the bottom. The function keys from "RECALL" to "BELLS  
ISOL" all have two functions e.g. "BELLS ISOL/DELETE". In programming mode, these  
keys operate the bottom functions i.e. "DELETE", "INSERT", etc. An exception is  
"RECALL/(" which will be either "RECALL" or "(" depending on the programming function  
selected.  
The logic functions in the right hand column of the 4 x 4 "numeric" keypad are used for  
entering output logic equations. The symbol and the word represent the same function e.g.  
logical "OR" is represented in an equation by the symbol "+".  
During text entry the "NOT" key may be used to enter a blank space.  
6.1.4  
1.  
RECOMMENDED PROCEDURE FOR CONFIGURATION &  
PROGRAMMING  
System Design  
Determine all system requirements; decide number of 8ZMs, 8RMs, LED Display (if  
any); allocate zones and relays. Fill out configuration sheets with programming for  
detector type, relay supervision, output logic, etc.  
2.  
Battery & PSU  
Calculate battery and PSU requirements as per Section 5. Decide on battery  
capacity. Check that physical size of battery fits with proposed mechanical  
arrangement.  
3.  
4.  
Configure Hardware  
With mains power off and battery disconnected. Fit battery test resistor (if required).  
Install modules and fit any relay supervision links required.  
E2 Init  
Fit links Lk7, SW1 and turn mains power on to perform Database Initialisation as per  
Section 6.3.1. Check that modules configured by Controller match modules installed.  
5.  
6.  
Access Database  
As per Section 6.3.2, using default code.  
Assign Access Codes  
As per Section 6.4.2. Note that the first code is the master code, and should be  
known by the System Designer or Service Supervisor as appropriate.  
7.  
8.  
Enter Text  
As per Section 6.4.3. Copy names for FIP, zones and relays from configuration  
sheets.  
Global Parameters  
Enter any global parameters different from the defaults such as auto-test inhibit  
dates, FIP MCP zone (if other than Zone 1), as per Section 6.4. Fig 6.1.2 can be  
used as a flow chart. Work from top to bottom, left to right.  
9.  
Enter System Configuration Parameters  
Refer to Fig 7.1.1. Enter all the circuit, zone, output logic, relay supervision and  
RZDU parameters from the configuration sheets that differ from the defaults. Start at  
the left side of Fig 7.1.1 (circuits), and work from left to right through each branch,  
starting at the lowest numbered item (e.g. zone, relay) and stepping through to the  
largest number for each item configured.  
Page 6-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
6.1.5  
10  
RECOMMENDED PROCEDURE FOR CONFIGURATION &  
PROGRAMMING (CONTINUED)  
Checking  
When all parameters are entered, either:  
1.  
Print the database (as per Section 6.3.4) and compare the printout against  
the configuration sheets (check each parameter for each item and tick off).  
or  
2.  
If a printer is not available, de-access the database as per Section 6.3.3,  
enter "View Parameter" mode and check each parameter of each item (tick  
off) noting any mistakes. Re-access database and correct mistakes.  
11.  
Update RDU Programming  
Update the programming (including zone names) of any connected RDUs. F3200  
V2.03 (or later) software allows the sending of zone names to an RDU through the  
RDU comms link. This is initiated with a command at the FIP and requires the RDU  
to have its database link (Lk7) in the write enable position. RDU software V2.01 or  
later supports this feature. Refer Section 6.2.1.  
12.  
13.  
Testing  
As part of commissioning, with test loads rather than real ones (e.g. for  
airconditioning shut-down and gas flood). Check the operation of detectors  
(including LED brightness and remote LEDs). Check the operation of logic and  
timers from inputs to outputs.  
Save Database  
When satisfied that the configuration parameters and logic are correct, save the  
database onto a disk (if a computer is available) and keep it in case the database  
ever needs to be restored, or in case a future FIP has similar logic and could be  
copied from this one and edited.  
After saving the database a verify operation should be done as described in Section  
6.3.7.  
Issue 2.7  
5 July 2001  
Page 6-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
6.2  
SET MENU & OPERATOR PROGRAMMING  
FUNCTIONS  
6.2.1  
GENERAL  
From the base display, pressing the "SET" key enters the programming menu as shown in  
Fig 6.1.2. This gives the Operator programming options as follows:  
1 Set Time; 2 Set Date; 3 View Data; 4 Program Data; 5 Bds Present;  
6 More  
Operator Accessible Options  
Options 1,2 and 5 are Operator accessible and do not affect the database.  
Set Time and Set Date are self-explanatory (they are described in the Operator's Manual,  
Sections 6.9 and 6.10 respectively).  
Option 5, Boards Present, allows temporary removal/re-instalment of one or more modules  
and is described in the Operator's Manual, Section 10.2.  
Database Options  
Option 3:view data, and 4:program data, require an access code to be entered.  
View Data is described below. Program Data selects the database configuration menu and  
is described in Section 6.4.  
Options to print and save the database are accessed using the PRINT key from the base  
display and allow the database to be printed or saved in a computer file are described in  
Section 6.3.4.  
Option 6:more produces a second menu of 1:RZDU zone name transmit.  
This option is used to initiate the transmission of all zone and module relay names to any  
RDUs. This is described in Section 7.6.  
6.2.2  
VIEW DATA PARAMETERS  
The View Data option has a menu structure parallel to the program data menu structure and  
allows the user to view the FIP database configuration without possibly changing it. To alter  
the database the Program Data option must be used. Refer to Section 6.4.  
View Data mode does not stop processing of alarms (as Program Mode does) and, thus,  
should be used to view programmed information on an operational FIP.  
NOTE  
Access to this menu can only be gained by entering the correct access code.  
Refer to Section 6.3.2.  
Page 6-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
6.3  
INITIALISING, ACCESSING, DE-ACCESSING,  
PRINTING, SAVING, LOADING & VERIFYING THE  
DATABASE  
6.3.1  
INITIALISING THE DATABASE  
The E2 INIT (initialisation) sequence causes the FIP to accept the module configuration  
found and store this in its database. Note that this also sets all other parameters to the  
default option and erases all other programmable data in the database e.g. zone names,  
output logic equations. It should, therefore, only be done on an unprogrammed system.  
Whenever the panel is powered up or down, Lk7 should always be in the write protect  
position.  
Steps  
1.  
Fit the minijump on the DATABASE link, Lk7 (top right of Controller/Display) in the  
WRITE PROTECT position, (i.e. NOT write enabled).  
2.  
3.  
With the batteries disconnected, turn the FIP mains power off.  
Short circuit pins SW1 (top centre of Controller/Display) with the minijump, then turn  
the power on.  
4.  
When the start up sequence is completed the LCD prompts you to write enable the  
database by moving Lk7 to the write enable position.  
Move Lk7 to the write enable position.  
You will then be prompted on the LCD to remove SW1 and press "ACK".  
Remove the minijump from SW1 (place it on one pin only), and press "ACK" to  
complete the sequence, or "CLEAR-ESC" to abort it.  
6.3.2  
ACCESSING THE DATABASE  
When programming the database the DATABASE link (Lk7 on Controller/Display) must be  
in the WRITE ENABLE position. At all other times it must be in the WRITE PROTECT  
position.  
With Lk7 on the Controller in the WRITE ENABLE position, selecting "Program Data" from  
the SET menu prompts for entry of the 6 digit access code. The default access code is 0 0 0  
0 0 0.  
When access has been granted, the Program data menu is displayed and a new access  
code can be entered (option 1, refer to Section 6.4.2).  
The access code for the FIP should be recorded in the FIP contract file to enable future  
reconfiguration. Where multiple users have individual codes then they should have a system  
for remembering their own code.  
Issue 2.7  
5 July 2001  
Page 6-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
ACCESSING THE DATABASE (CONTINUED)  
WARNINGS  
1. When the database is accessed the Controller de-energises the Standby relay (i.e.  
transmits Standby) and stops processing. If this signals "Alarm" to the Brigade the  
appropriate arrangements should be made.  
2. On a FIP that has been commissioned, if there is concern that changes made to the  
database (e.g. programming circuits) may cause a false alarm, then either the  
Brigade should be isolated or the appropriate zones should be isolated before  
entering "Program Mode".  
6.3.3  
DE-ACCESSING THE DATABASE  
It is important to make an orderly exit from programming mode (by use of "CLEAR ESC")  
before replacing Lk7 in the WRITE PROTECT position or turning the FIP power off.  
This allows the Controller to calculate the checksum for the revised database.  
If an orderly exit is not made and the Controller finds its checksum does not match the  
checksum stored it will remain in Standby with I/O processing inactive. It is then necessary  
to re-access the database, and re-exit to allow it to calculate a new checksum. When this is  
"Acknowledged", I/O processing re-starts, and the Standby relay is re-energised (but not  
while all zones are isolated unless programmed to do so).  
NOTES  
1. Lk7 must be fitted to the WRITE PROTECT position after the database has been de-  
accessed.  
2. If zones were de-isolated before programming commenced, they should be checked  
for status before being de-isolated after programming has finished. If any show  
"alarm" then these must be checked to see if the alarm is genuine.  
3. All zones and relays associated with any new modules configured (including E2  
Initialisation) will be automatically isolated when the database is de-accessed, and  
need to be checked and de-isolated as per note 2. above.  
6.3.4  
PRINTING & SAVING THE DATABASE  
Once a FIP is programmed and commissioned, it is recommended that a disk containing  
both a copy of the database in binary format and a printout of the database be kept in the  
contract file. The printout should be carefully checked against the original configuration  
setup sheets. A new database printout should be done after any subsequent modification to  
the database.  
The printer or computer is connected to the PRINTER/PROGRAMMER connector (J1) at the  
bottom left corner of the Controller/Display. Suitable cables for connection are described in  
Section 3.5.4.  
When programming the FIP, remember to set the correct data for the printer (default is 60  
lines per page, 9600 Baud).  
Set the computer serial port for the same Baud rate. The computer serial port should also  
be set to 8 data bits, no parity, 1 stop bit, and Xon/Xoff handshaking should be enabled.  
Page 6-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
PRINTING & SAVING THE DATABASE (CONTINUED)  
To print or save the database, use the PRINT key from the base display (i.e. press  
CLEAR/ESC repeatedly until the base display is showing then press PRINT) and select  
option 3 to print the database or option 5 to save the database, then enter the access code.  
To print just the output logic part of the database, select option 4.  
NOTE  
These functions do not require the DATABASE link (Lk7) to be fitted in the  
WRITE ENABLE position.  
Saving the Database on a Computer  
The FIP database may be saved (in binary format) on a computer (e.g. a laptop PC). The  
saved database can then be reloaded into the FIP (or another F3200) at some future time  
and this is much faster than reprogramming the entire database from the FIP keypad.  
To initiate a database save, first setup the PC to capture the data to a disk file using a  
program such as PROCOMM. From the "print" menu (press the PRINT key from the base  
display as described above), select option 5:save database, enter the access code, then  
press the "ENTER" key to initiate the save.  
The FIP display will show:  
"Print in Progress. Press RESET to Cancel"  
while the database save is in progress.  
With V2.08 or later software, the operator will then be prompted to do a database verify.  
NOTE  
The F3200 FIP responds to XON (CTRL Q) and XOFF (CTRL S) handshake  
characters for both the save database and print database. If it receives an  
XOFF character it will suspend transmitting data until it receives an XON character.  
If the print or save database operation does not appear to be working, try typing  
Control Q on the PC.  
6.3.5  
RESTORING THE DATABASE FROM A COMPUTER  
The database saved in a disk file on a computer may be restored as follows:  
Enter program mode as described in section 6.3.2 and select option 5:DBload from the main  
program mode menu, then select Option 1 : load database.  
The message:  
“Press ACK, then start sending the new database”  
will appear.  
Connect the computer to the FIP as described in Section 6.3.4. Press the "ACK" key on the  
FIP keypad and then initiate the transmission of the database file from the computer.  
The FIP must receive a complete database with the correct number of records or it will  
display an error message.  
Issue 2.7  
5 July 2001  
Page 6-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
RESTORING THE DATABASE FROM A COMPUTER (CONTINUED)  
Note: The FIP will transmit XON, XOFF characters for handshaking if it needs to slow down  
the rate of data being sent to it. So, where possible, the computer should be set up  
for XON XOFF handshaking. If XON/XOFF handshaking is not available, or if errors  
occur, then a slower baud rate (2400) should be used.  
6.3.6  
DATABASE CONVERSION  
An F3200 database in EEPROM created with F3200 V1.10 software (or earlier) is not  
directly usable in F3200 V2.00 (onwards) software, but may be made usable by running a  
conversion process. The conversion may be done either on powerup, or after loading a  
V1.10 format database. Before performing the conversion it is desirable to save a copy of  
the V1.10 database and check it carefully against the converted database at the completion  
of the conversion.  
At Powerup  
Install V2.xx software, set the database write protect link to write protect, ensure EEPROM  
initialise link SW1 is not installed and power the panel up. After power-up the operator will  
be prompted to write enable the database and press ACK to initiate the conversion. After  
the conversion has been completed, the panel will perform a watchdog reset and reboot  
itself.  
After Database Load  
If a V1.10 format database is loaded into V2.00 or later software, the operator will be  
prompted to initiate the conversion process. After the conversion is complete the panel will  
perform a watchdog reset and reboot itself.  
Output Logic  
There is slightly less EEPROM available for output logic in a V2.XX format database than a  
V1.10 database. If the V1.10 database output logic memory is very full, it is possible that  
some equations will be deleted during the conversion process. If this happens, it will be  
indicated to the operator on the LCD with the message "Some output logic lost!".  
6.3.7  
VERIFYING A SAVED DATABASE  
With V2.07 or earlier software, a database verify operation can be initiated by entering  
program mode, selecting Option 5 : DBload from the main program menu, then Option 2 :  
Database Verify.  
With V2.08 or later software, a database verify can also be initialised without entering  
program mode – press the SET key from the base display, then press the SET key again to  
select the second menu and selection Option 3 : Database Verify. With V2.08 or later  
software, following a database save, the operator is immediately prompted to do a database  
verify.  
After the database verify has been initiated on the keypad, the database should be sent from  
the computer to the panel. The success or failure of the verify will be indicated on the LCD.  
The RESET key can be pressed to terminate the verify operation at any time.  
Page 6-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
6.4  
PROGRAM DATA MENU, TEXT & GLOBAL  
PARAMETERS  
6.4.1  
GENERAL  
The Program Data menu (refer to Fig 6.1.2) allows the user to program the following options:  
1:Access Codes; 2:Text; 3:Global Data; 4:System Configuration; and 5:DBload.  
Option 5:DBload is described in Section 6.3.5, and System Configuration is described in  
Chapter 7. Option 3:Global Data is described in Section 6.4.4. The other options are  
described in the following sections.  
A summary of the programmable options and their default values is shown in Table 6.4.1 at  
the end of this chapter.  
6.4.2  
ACCESS CODES  
Up to 10 separate 6 digit access codes are available (numbered 0-9), and each one has  
provision for the users' initials (3 characters). The initials of the last user to change the  
database are stored in the database. When the database is de-accessed, the user number  
and initials are logged with the event.  
The default access code for user 0 is 000000. There is no default code for users 1-9. User  
0 can change any access codes (users 0-9), but users 1-9 can change only their own access  
code.  
To enter or edit an access code, enter the user number (0-9) from the keypad. This gives  
the options of: 1 : Access Code; 2 : Initials; 3 : Delete.  
1.  
To enter a New Access Code, select Option 1. Enter the new six digits, and then re-  
enter them to confirm.  
2.  
To enter The New Three initials, select Option 2.  
The LCD will display the alphabet on the bottom line. Move the cursor through the  
alphabet using the ! " cursor keys. Press "ENTER" when the desired letter is  
selected. Press "ACK" to save the entered initials.  
"DELETE" will delete an entry. "EDIT" will toggle the cursor between the top line  
(initials) and the bottom line (alphabet).  
3.  
To Delete an Access Code, select Option 3 for that user. Press "ACK" to remove the  
code for that user. The initials remain but can be edited as in 2 above.  
Note that no two users should have the same code. Access code 000000 should not be  
used for any user as it will be known by all service people familiar with F3200.  
Issue 2.7  
5 July 2001  
Page 6-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
6.4.3  
TEXT ENTRY  
The Text option allows entry of the following:  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
a 40 character name for the site  
a 30 character name for each zone  
a 30 character name for each module relay  
a 30 character name for each ancillary relay  
a 6 character name for each of the 9 programmable alarm text messages.  
a 40 character fault action text.  
a 12 character Tandem LCD password.  
Text can be programmed with the keypad or with a PC connected to the Printer/Programmer  
port (refer Section 6.4.3.2).  
6.4.3.1  
PROGRAMMING TEXT WITH THE KEYPAD  
When an item (e.g. Zone 01) is selected, press "EDIT", "ENTER" or """ to enable text entry  
for that item.  
Text entry has two fields. The top field contains the text which has been entered and the  
bottom field contains an array of characters which may be entered.  
Each field has one of two cursors. The active cursor may be moved through the field it is  
in by use of the ! " cursor keys to select a character, or position in text. The inactive cursor  
$ shows where the active cursor would be if it was in that field.  
Holding the ! " keys down causes rapid movement.  
There is a choice of 3 lines of characters in the bottom field (upper case letters, lower case  
letters, numbers and symbols). These may be scrolled by use of the # and % cursor keys  
when the active cursor is in the bottom line. Note that numbers can be entered directly from  
the keypad, and the "NOT" key inserts a blank space.  
"EDIT"  
swaps the cursors between the two fields.  
"INSERT"  
"DELETE"  
toggles entry between "insert" and "typeover" modes.  
acts as backspace for a character just entered, or deletes any character in the  
text selected by the cursor (active or inactive).  
"ACK"  
saves the text and returns the cursor to the item number.  
step through items (e.g. zones).  
"NEXT" &  
"PREV"  
"RECALL"  
allows copying of the text from any zone or relay to any other zone or relay.  
(Select zone/relay to be copied into. Press "RECALL" and select zone/relay  
and number of zone/relay to be copied from. "ENTER" transfers the text.  
This can then be edited).  
Page 6-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
PROGRAMMING TEXT WITH THE KEYPAD (CONTINUED)  
Example of Entry of Site Name  
Enter the site name "Penrose No 1 Store".  
From the Text Entry menu select option 1, Site.  
The LCD has the inactive cursor in the first position of the top field and the active cursor on  
A in the bottom field.  
Move the cursor right with the " key until the letter P is selected.  
Press "ENTER". The letter P should appear in the top field.  
Scroll the bottom line with the % key to the lower case alphabet.  
Move the cursor with the " key until the letter e is selected.  
Press "ENTER".  
Repeat for the other letters in Penrose.  
To put a space after "Penrose" press the "NOT" key.  
To enter the number 1 in "No 1" press the "1" key.  
Mistakes can be corrected by use of the "EDIT", "DELETE", and "INSERT" keys.  
When the correct name is entered in the top field press "ACK".  
Alarm Text Message  
The Alarm Text Message (Detector type) has 7 default options as specified in AS1603.4 and  
shown in Fig 7.1.1. These include Smoke, Heat, FSW, etc (where FSW = flow switch).  
There are 2 blank options (8 and 9) off the end of the bottom field which may be accessed  
by the " key.  
All of these messages may be edited by the user. However, it is recommended that where  
non-default messages are required (e.g. flame, sub-FIP), then options 8 and 9 are used first.  
Fault Action Text  
When a fault occurs at the panel, the buzzer is turned on steady and if the LCD is currently  
showing the base display then the text "A fault is present in the system" is shown on the top  
line of the LCD and a 40 character user programmed text message is shown on the bottom  
line of the LCD. The fault action text is cleared from the LCD when any key is pressed or  
when the buzzer is turned off.  
The 40 character user programmed text message could be used to show the name and  
phone number of the local service company. When an EEPROM (database) reinitialise is  
done, default fault action text of "Contact your service company" is assigned.  
Issue 2.7  
5 July 2001  
Page 6-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
6.4.3.2  
TEXT PROGRAMMING WITH A PC  
F3200 allows the text names for zones, relays, etc, to be entered from a PC using the F3200  
printer port.  
F3200 software V1.00 does not support this feature at all. Software V1.10 and V2.00 support  
all the commands with the exception of the fault action text (F command). Software V2.01  
onwards adds support for the F command. This feature is present in standard F3200  
panels, networked F3200 panels, and the NDU. V2.07 adds the Tandem LCD password.  
To program text from a PC enter program mode using the keypad and LCD in the usual way  
and select programming of text.  
When the LCD is showing the Text entry menu:  
Text 1:Site 2:Zone 3:Relay 4:Anc relay 5:Alarm text 6:Fault text 7:Tandem pwd  
the PC connected to the printer/programmer serial port is able to enter text.  
The LCD must remain showing this menu. Pressing any keys on the F3200 front panel  
keypad will terminate the entry of text from the PC. To initiate the entry of text, the ENTER  
key must first be pressed on the PC. A Tandem LCD user with a local connection must  
press the EDIT key to get into text entry mode at this point and terminate the text entry by  
typing Q ENTER.  
This will give a prompt of:  
Enter Znn, Rnn, An, S, Tn, In, F, P, Q :  
The type of text being entered must first be selected by entering one of the options listed  
followed by the ENTER key. Lower case z, r, a, s, t, i, f, p or q may be used if desired. Any  
other characters entered will be ignored.  
To exit from the serial port text  
Programming process type: Q ENTER  
or press the CLEAR key on the F3200 keypad.  
To enter a zone name type: Znn ENTER  
where nn is the zone number (1-64).  
To enter a module relay name type: Rnn ENTER  
where nn is the module relay number (1-64).  
To enter an ancillary relay name type: An ENTER  
where n = 1, 2 or 3.  
To enter the site name type: S ENTER  
To enter an alarm text type: Tn ENTER  
where n is the alarm text number (1 to 9).  
To enter an access code user initials type: In ENTER  
where n is the access code (user number 0 to 9).  
To enter Fault action text type: F ENTER  
To enter the Tandem LCD password type: P ENTER  
If a valid selection is entered the message:  
"Enter Text :"  
will appear. The desired text should now be entered, followed by ENTER.  
Page 6-20  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
TEXT PROGRAMMING WITH A PC (CONTINUED)  
The DELETE or BACKSPACE keys may be used to delete the last character typed, and the  
ESCAPE key may be used to abort the text entry for the selected item.  
After the ENTER key is pressed the message "Saved OK" will appear if the text has been  
saved correctly into EEPROM.  
To load a file of text names from the PC into the F3200 panel, the file should be set up as  
shown in the following example. The names may actually be in any order, and it is not  
necessary to have a name for every zone or relay, etc.  
Ensure that the last name in the file is followed by a carriage return before the end of the file,  
i.e. put a blank line at the end of the file.  
The characters S, Z, R, etc, must always be in column 1 and the text names must also start  
in column 1 (unless leading spaces are required, but this is unlikely).  
S
40 character site name  
(blank lines are allowed)  
Z1  
Example text name for zone 1  
Z2  
Name for zone 2  
Z3  
This name has leading spaces  
Z4  
This name does not have leading spaces  
.
.
.
Z23  
This name will be cut at 30 characters as it is too long  
Z24  
Name for zone 24  
R1  
Name for module relay 1  
.
.
.
R64  
Name for module relay 64  
A1  
Name for ancillary 1 relay  
A2  
Name for ancillary 2 relay  
A3  
Name for ancillary 3 relay  
T1  
Smoke  
T4  
Manual  
T9  
Therml  
(limited to six characters)  
Issue 2.7  
5 July 2001  
Page 6-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
(three characters)  
TEXT PROGRAMMING WITH A PC (CONTINUED)  
I0  
JEH  
I1  
MJS  
.
.
I9  
BAC  
F
Phone VIGILANT FIRE 7903600  
(40 characters max)  
To initiate the loading of the file into the F3200 panel, enable remote text entry as described  
above. Run a terminal emulation program on the PC and press ENTER on the PC.  
When the message:  
Enter Znn, Rnn, An, S, Tn, In, F, P, Q :  
appears, send the file containing the text names to the F3200 panel using the "transmit file"  
command of the terminal emulator.  
If possible set the terminal emulator to use XON/XOFF flow control or else set the line  
transmit delay to 100 milliseconds.  
After loading the text names into F3200, do a database printout to check that all names have  
been assigned correctly.  
Refer to Section 6.3.4 for information on the setup of the F3200 serial port. Remember to  
set the baud rate of the PC to that programmed into the F3200 for its printer port.  
6.4.4  
GLOBAL DATA  
Option 3:Global data from the main Program menu, or Option 2:Global data from the view  
menu provides a tree of menus that allow many options to be set.  
The options provided in the global data menu tree depend on the version of software being  
used.  
There are two different menu trees listed below, the first of which is for V2.06 or earlier  
software, and the second is for V2.07 and later software.  
For V2.06 or earlier software  
Some options shown in these menus are not available in earlier versions of software.  
1:Auto Test; 2:FIP MCP Zone; 3:FFCIF Mode; 4:All zones isolated; 5:More.  
Option 5:more gives the following menu.  
1:Brigade Test Relay Activate; 2:Printer Setup; 3:Country Coder; 4:more  
Option 4:more gives a further menu.  
1:Daylight saving start  
3:Mains 50/60Hz  
2:Daylight saving end  
4:Keys enable  
Page 6-22  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
GLOBAL DATA (CONTINUED)  
For V2.07 and later software  
1:Auto test; 2:FIP MCP; 3:FFCIF options; 4:All zones isolated; 5:More  
3:FFCIF options provides the following:  
FFCIF zones (MAF only, all, none)  
Auto Ack enable/disable  
FFCIF type 2/3  
Remote Ack enable/disable  
FFCIF alarm = bells on enable/disable  
Display cause by default enable/disable  
Always flash non-MAF alarm LEDs – enable/disable  
Always send non-MAF FF alarm to RDU – enable/disable  
5:more selects the following menu  
1:Brigade test relay activate; 2:Printer setup;  
3:Country coder; 4:more  
4:More selects the following menu  
1:Daylight saving start; 3:Mains/battery  
2:Daylight saving end; 4:More  
3:Mains/battery provides the following  
Mains frequency 50/60Hz  
Mains fail action  
Battery low monitor enable  
Battery tests enable  
Charger fault monitor  
4:More selects the following menu  
1:Keys enable; 2:Remote sounder silence  
3:Buzzer mode; 4:New Zealand mode options  
The above items are described in more detail in the following pages.  
Auto Test  
The automatic test of memory, AZCs, etc, occurs at a programmed time every day except on  
weekends or programmed inhibit dates. This is to reduce the cost of callouts should the  
auto-test discover a "fault". Only the basic statutory holidays, 25/12, 26/12, 01/01, 02/01 &  
weekends are inhibited by default. Other state/company specific ones should be added.  
Note that the default programming does not include an alarm test of each AZC (zone) and to  
disable the Auto Test completely set the Auto Test start time to 24:00:00.  
FIP MCP  
The default mapping for the FIP MCP is to zone 1, but any configured zone may be selected.  
Note that in "special" FIPs which do not have an MCP fitted it should be disabled to prevent  
Fault occurring on the zone it is mapped to. To disable it, select zone 0.  
WARNING  
It is possible to map the FIP MCP to a zone which is not configured.  
This would not be displayed or logged and the MCP is disabled.  
Issue 2.7  
5 July 2001  
Page 6-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
GLOBAL DATA (CONTINUED)  
FFCIF options  
The parameters which can be programmed to configure the FFCIF operation are:  
FFCIF type  
The default type of FFCIF operation is, 3 where an alarm is automatically displayed on the  
LCD and alarms must be individually acknowledged. Where LED displays are fitted for each  
zone and the automatic display with individual acknowledgement is not required, type 2 may  
alternatively be selected. This is described in Section 5.10 of the Operator's Manual.  
Selecting this option forces the FFCIF queue to accept MAF zones only.  
FFCIF zones  
The FFCIF operation as described in the Operator's Manual Chapter 5 is Type 3 and  
normally only puts zones which are mapped to the MAF into the FFCIF queue. Alternatively,  
the FFCIF queue can be programmed to accept all zones, or no zones (disabled).  
An example of an alternative follows:  
Assume an owner has two buildings, each with its own Brigade connected FIP. It is required  
that any alarm on one FIP must show as a single alarm on the other, but this repeat  
indication must not initiate a second alarm call to the Brigade.  
The zone on each FIP which indicates alarm for the other FIP cannot be mapped to the MAF  
(and probably Bells or Anc1, Anc2) so that it will not call the Brigade.  
To make the alarm sound the buzzer, be displayed in the FFCIF, etc, the FFCIF should be  
programmed as "All Zones" rather than "MAF Only". This assumes that there are no other  
non-MAF mapped zones for which alarms are not to be displayed in the FFCIF).  
FFCIF RDU remote ack  
If enabled this allows FFCIF alarms to be acknowledged by RZDUs. If disabled,  
acknowledgement commands from RZDU devices will not be accepted but reset and isolate  
commands from RZDU devices will still be accepted. For network systems refer also to  
Section 11.7.  
FFCIF auto ack.  
If enabled, all alarms entered into the local FFCIF alarm list will be flagged as  
"acknowledged" automatically. This does not result in the alarm being acknowledged at any  
RZDUs or, for network systems at other network devices.  
Bells on for FFCIF Alarm  
If enabled, the bells will be activated whenever there is any entry in the local FFCIF alarm  
queue. This can be used, for example, to activate the bells if an alarm is received from  
another networked panel. Regardless of whether this option is enabled or disabled, the bells  
are still activated if any local zone mapped to the bells is in alarm.  
FFCIF Display cause by default  
As standard, the first line of the F3200 FFCIF Alarm display shows:  
Alarm Time, Alarm Type, Acknowledge State, Number of Alarms.  
When the "AND" key is pressed, the first line changes to:  
Cause, Number of Alarms.  
If the Display cause by default option is enabled, the first line is shown as:  
Page 6-24  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
GLOBAL DATA (CONTINUED)  
Cause Preview, Alarm Type, Acknowledge State, Number of Alarms.  
and when the "AND." key is pressed, the first line changes to:  
Full Cause, Alarm Time, Number of Alarms.  
The Cause Preview consists of the first section of the Full Cause.  
Note: This setting affects ALL events, network or local, shown on the local F3200. It does  
not affect the format of information sent to other F3200s on a network, or to RDUs.  
Each of those devices will display alarms consistent with their own programming  
options and capabilities.  
FFCIF option Always flash non-MAF alarm LEDs – enable/disable  
This option is available with V2.07 or later software. By default this is disabled. If enabled  
the zone LED (if any) for a non-MAF zone will flash when a new alarm occurs on the zone.  
This allows the alarm to appear as an unacknowledged alarm at an RDU which may be  
showing the alarm in its FF alarm list. At an RDU, each zone can be programmed as to  
whether it should be entered into the RDU FF alarm list when the zone goes into alarm. This  
allows the choice of whereabouts in the system particular zone alarms are displayed.  
FFCIF option Always send RDU non-MAF FF alarms – enable/disable  
This option is available with V2.07 or later software. This is disabled by default.  
If enabled, alarms on all zones are sent to the RDU as displayable FF alarms. The RDU  
then has the choice of which alarms it displays. In V2.06 or earlier software, a displayable  
FF alarm was sent to an RDU only if the alarm was entered into the F3200’s FF alarm list.  
All zones isolated (Standby Operation)  
AS1603.4 suggests that the Standby relay should de-energise if all zones are isolated. This  
function may be disabled if allowed by the local Fire Brigade.  
Brigade Test  
Brigade Test normally energises the MAF Alarm relay when the Brigade Test key on the FIP  
(or RZDU) is pressed for 2 seconds. This function may be disabled if the Fire Brigade does  
not permit it.  
Note that if an output logic equation is programmed for the Alarm relay, (e.g. a special test  
sequence) this parameter has no effect (except for networked systems). (Refer to BGT  
token in Section 7.4.3).  
For network systems, if the MAF alarm relay is programmed to operate for local brigade test  
then this also means that the MAF status transmitted onto the network will include a brigade  
test state of TRUE when a local FIP (or RZDU) brigade test is done. If the local MAF alarm  
relay is programmed not to operate for local brigade test then the brigade test state  
transmitted onto the network is always FALSE. If a brigade test state of TRUE is received  
from another panel on the network and this panel is programmed to use the MAF status of  
that panel then the local MAF alarm relay and LED will operate regardless of the  
programming of the local brigade test parameter.  
Issue 2.7  
5 July 2001  
Page 6-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
GLOBAL DATA (CONTINUED)  
Country Coder (alarm signalling)  
This is only required for FIPs connected to Brigades with NSW Country Coder equipment.  
It allows the selection of a code of 1 to 6 pulses to be signalled on the FIP Brigade Alarm  
relay. These occur in a repeated sequence of 3 seconds off followed by 1 second on for  
each pulse, with a space of 1 second between pulses.  
Select the coder option and enter the digit for the required number of pulses.  
The default code (0) programs standard Alarm relay operation.  
Printer setup  
The printer setup menu options are:  
1:Lines per page; 2:Baud Rate; 3:Print relay controls; 4:more  
Option 1:lines per page, determines how often a new page/page heading is printed and  
option 2:baud rate allows the baud rate of the printer serial port to be selected.  
Option 3 allows the enabling/disabling of the printing of relay control events  
(activate/deactivate).  
Option 4:more gives a further menu: 1:Event printing; 2:Select print evt; 3:Select history evt  
Option 1 allows event printing to be enabled or disabled. When event printing is  
disabled no events at all are printed and the size of the history queue is doubled.  
Options 2 and 3 allow the selection of which types of events are to be printed and  
which type are to be logged to history. There are six different types which can be  
individually enabled or disabled, and these are shown as  
1:Zone 2:System 3:Sys run 4:Cct 5:Pnt 6:Relay.  
Numeric keys 1 to 6 are used to enable or disable each type. A 'Y' character is  
shown if the type is enabled and 'N' for disabled.  
Zone events include zone alarm, reset, isolate etc.  
System events include "system test passed", "system power up" etc, and includes all  
events which are not one of the other 5 types.  
Sys run (system running), is for the daily "auto test passed" event (or for network  
systems the daily "system running" event).  
Cct (circuit) and pnt (point) apply only to network systems.  
Relay events include local ancillary and module relay events such as isolate, fault,  
operate test, and (de)activate. If relay events are enabled then local relay activate  
and relay deactivate events may be separately disabled (as described in the previous  
menu). For network systems, module relay and ancillary relay events are sent onto  
the network as zone events and hence the printing and history logging of them is  
controlled by the zone type option and not the relay event type option. However, it is  
possible to disable the transmission of relay activate and deactivate events onto the  
network - refer to section 11.8.  
Page 6-26  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
GLOBAL DATA (CONTINUED)  
Daylight saving start/end  
This allows the selection of a date and time and a time difference for the start and end of  
daylight saving to allow the panel to automatically set the time forward or back. The  
programming of the start and end is identical and is described jointly here. At the  
programmed start date/time the time will be put forward by the programmed start time  
difference and at the programmed end date/time the time will be put back by the  
programmed end time difference. There are two menus used, and to swap between the two  
menus the cursor right/left keys are used.  
The first menu gives options of 1:month; 2:hour; 3:minute; 4:day.  
Setting the month to zero disables the daylight saving process for either the start or end,  
whichever is selected i.e. they can be disabled independently and the month must be set to  
zero for both the start and end to disable them both. Otherwise, set the month to a value 1-  
12 to select months JANUARY to DECEMBER.  
Options 2:hour and 3:minute determine the time of day that the daylight saving process is to  
change the time. The hour is set to a value 0-23 to select midnight through to 11pm. The  
minute is set to 0-59.  
Option 4:day gives a menu which allows the setting of which day of the month the time is to  
be changed.  
The menu gives options 1:last weekday of; 2:Nth weekday of; 3:date.  
Only one of options 1,2,3 can be chosen, but the daylight saving start setting may be  
different to the end setting.  
Option 1:last weekday of, will prompt for the entry of a weekday selection, 1 to 7 (1=Sunday,  
7=Saturday) so that the day selected is then the last Sunday (say) of the month. This will  
mean that the daylight saving change will occur on the last Sunday (say) of the month  
regardless of the month or year.  
Option 2:Nth weekday of, will prompt firstly for a value 1-4, to select the first, second, third or  
fourth weekday, and then prompt for a weekday selection, 1 to 7 (1=Sunday, 7=Saturday) so  
that the day selected is then, say, the third Sunday of the month - regardless of the month or  
year.  
Option 3:date allows the entry of a specific day 1-31 to select the day of the month i.e. 1  
being the first day of the month etc.  
The second of the two daylight saving menus has options of 1:hour and 2:minute. This  
allows the setting of the time difference in hours (0-23) and minutes (0-59) which is the  
amount of time to be added or subtracted when the daylight saving change occurs. These  
values must be programmed for both daylight saving start and end and will most likely be the  
same but do not have to be.  
Daylight saving will start and end on different dates and times, depending on the country or  
state the FIP is located in.  
Issue 2.7  
5 July 2001  
Page 6-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
GLOBAL DATA (CONTINUED)  
The following table indicates suitable settings:  
COUNTRY/STATE  
FORWARD  
BACKWARD  
ENABLE  
D
MONTH SUNDA  
Y
HOUR MONTH SUNDA  
HOUR  
Y
L
L
3
-
NSW, ACT, VIC, SA  
TAS (1)  
Y
Y
Y
N
10  
10  
10  
-
L
L
1
-
2
2
2
-
3
3
3
-
3
3
2
-
NZ  
WA, NT, QLD (2)  
NOTE: (1)  
(2)  
Tasmania may start Daylight Saving earlier at their discretion.  
WA, NT and QLD do not have Daylight Saving.  
Mains/Battery Options  
Most of these options are available only in V2.07 or later software and are intended for  
installations which have to meet the requirements of the Australian Standard AS4428.1  
1998.  
Mains fail = fault after 8 hours  
If this is enabled, then when mains has been failed continuously for 8 hours a fault will be  
signalled.  
Charger fault monitor – if enabled, signals a fault when the charger is high or low.  
Battery low monitoring – if enabled, a fault is signalled when a battery low voltage occurs.  
For a slimline NDU with no MAF board, the battery very low threshold is used as the battery  
low threshold. Battery low monitoring and battery connection tests are not required for  
AS1603.4 but are required for AS4428.1.  
Battery connection test – if enabled, the battery connection will be checked every 30  
seconds by reducing the charger voltage.  
Hourly battery capacity test – if enabled, a 60 second battery test will be done automatically  
on the hour.  
Daily battery capacity test – if enabled, a 40 minute battery test will be done automatically at  
the start of the daily auto test or at 9am if there is no auto test. WARNING: older versions of  
F3200 must have the battery test resistors R52, R53 removed from the MAF board if this test  
is enabled.  
Keys Enable  
V2.06 or earlier software  
V2.06 or earlier software allows two specific keys – BELLS ISOL and ANCIL ISOL- to be  
programmed as enabled or disabled. When disabled, the key will be ignored but the isolate  
functions that are normally accessible with these keys can be done using zones 193 to 197.  
Page 6-28  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
GLOBAL DATA (CONTINUED)  
V2.07 or later software  
Enablement of Keys in 4 Operating States  
V2.07 or later software allows each keyboard key to be enabled or disabled in each of 4  
operating states. This allows the keyboard functionality to be configured for each  
different installation. It is recommended that the key enablement feature in V2.07 not be  
used (upgrade to V2.08 or higher).  
A use for this feature might be to disable specific keys such as BELLS ISOL and ANCIL  
ISOL where they are not required, or to disable RESET and ISOL keys in FF mode so  
that the user cannot reset or isolate the alarms. The options for disabling the BELLS  
ISOL and ANCIL ISOL keys in earlier software have been removed in V2.07 onwards.  
Another use is for an NDU to have selected keys enabled when the door is closed.  
The four states and the default key enablements are :  
1
2
3
4
- FF mode with door open  
- default all keys enabled  
- default all keys disabled  
- default all keys enabled  
- default all keys disabled  
- FF mode with door closed  
- Non FF mode with door open  
- Non FF mode with door closed  
"FF mode" refers to when the FFCIF alarm list is being displayed. When FF mode is  
active, the principal keys used are those enclosed in the red border on the keypad -  
ACK, RESET, ISOL, NEXT and PREV. BELLS ISOL and ANCIL ISOL are possibly also  
used in FF mode.  
Non-FF mode refers to operation when the FF alarm list is not being displayed.  
When the panel is in program mode or has a database checksum error, all keys are  
automatically enabled. Also, if the database write protect link is in the enable position then  
the SET key, NUMERIC keys and CLEAR key are automatically enabled to allow entry to  
program mode. For a Tandem LCD connection, all "remote" keys are automatically enabled.  
Note that disabling a particular key does not prevent a particular function from being done  
another way e.g. if the ISOL key is disabled, a zone can still be isolated by pressing the  
ZONE key from the base display and using the menu option. Enabling RECALL, NEXT,  
PREV, CLEAR, ACK and NUMERIC keys and disabling ZONE, ISOL, RESET, RELAY,  
TEST, ALARM TEST, and FAULT TEST keys allows recall of information without allowing  
reset, isolate, test or programming functions. Enabling the SET key allows the time and date  
to be set but also allows access to the "boards present" function which may not be desirable.  
The RECALL key generally allows recall of off-normal states but can also be used to display  
the status of any zone or point by selecting zone or point from the menu then selecting the  
"status" option.  
After the keys enable option has been selected from the menu, one of the four modes can  
then be chosen. There are 5 "pages" of options for each mode which can be stepped  
through using the NEXT and PREV keys. Pressing the EDIT key at this point displays the  
currently selected mode and allows all keys for the selected mode to be enabled or disabled  
with a single command.  
Issue 2.7  
5 July 2001  
Page 6-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
GLOBAL DATA (CONTINUED)  
Remote Sounder Silence  
This option is available in V2.07 or later software. Selecting this option shows a menu of:  
1:sysflt reset [Y/N]  
2:ffcif actions [Y/N] 3:all commands [Y/N]  
These options determine whether a remote networked panel or RDU can silence the buzzer  
at this panel. If “sysflt reset” is set to “Y” the buzzer is turned off when a Reset System  
Faults command is received from a remote panel. If “FF actions” is set to yes then FF  
commands of ACK, RESET or ISOLATE received from RDUs or network panels will silence  
the buzzer.  
If “all commands” is set to yes then all zone reset and isolate commands sent to this panel  
will silence the buzzer.  
For V2.09 or later software, pressing the right arrow key from the above menu selects a  
further menu as follows.  
Global network sounder silence  
1:Any Key Tx  
2:Cmd Tx  
3:Receive  
These options apply only to network systems. “Any key TX” when enabled, means that if the  
buzzer is sounding locally and is silenced by pressing a key (any key) then a buzzer silence  
command is sent to all panels on the network. Option “3:receive” is used to select whether  
this panel obeys a buzzer silence command received from another panel on the network.  
Option”2:Cmd Tx”, selects whether an operator can initiate the sending of a buzzer silence  
command onto the network using a specific command. This operator command is accessed  
by pressing the System key from the base display and selecting option 3:Silence All.  
Buzzer Mode  
NOTE: Some of these options are not available in “older” software.  
Selecting the “Buzzer Mode” option shows the following menu.  
Buzzer enable 1:Alarms Y/N 2:Zone faults Y/N 3:System faults Y/N  
These options allow the selection of whether the buzzer sounds for alarms, zone faults or  
system faults.  
Pressing the right arrow key from the above menu shows a further menu.  
1:Buzzer sound for non-MAF zone faults [Y/N]  
2:Fault sounder after 8 hrs fault [Y/N]  
Pressing the right arrow key from this menu shows  
1:Fault sounder after 8 hrs isolate [Y/N]  
The parameter “Buzzer sound for non-MAF zone faults” is used to select whether a fault on  
a non-MAF zone should cause the fault buzzer to come on.  
Enabling “Fault sounder after 8 hrs fault” re-activates the buzzer if the buzzer has been  
silenced due after a fault and the fault has remained for 8 hours. The AS4428.1 Standard  
requires this to be enabled.  
Page 6-30  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
GLOBAL DATA (CONTINUED)  
The parameter “Fault sounder after 8 hrs isolate” enables the fault buzzer to be activated if  
an isolate state (zone or relay) has been present for 8 hours with no operator intervention.  
The AS4428.1 Standard requires this to be enabled.  
New Zealand Mode  
This option is available with V2.08 or later software and only for an NDU (not for F3200).  
The programmable options that are specifically for New Zealand mode are described in  
Chapter 12, and are as follows:  
1.  
2.  
3.  
4.  
5.  
New Zealand mode enabled Y/N  
Display bd Y/N  
Batt vlow = alarm Y/N  
Evac defect is fault Y/N  
External defect is fault Y/N  
When New Zealand mode is changed from disabled to enabled, a number of parameters are  
set to New Zealand settings. When New Zealand mode is changed from enabled to  
disabled, these parameters are set to Australian settings and are as follows:  
PARAMETER  
AUSTRALIAN DEFAULT  
NEW ZEALAND DEFAULT  
New Zealand mode enabled  
Batt vlow is alarm  
Evac defect is fault  
N
N
N
N
Y
N
Y
Y
External defect is fault  
Zone alarm buzzer enabled  
Zone fault buzzer enabled  
System fault buzzer enabled  
Fault sounder after 8 hours fault  
Fault sounder after 8 hours isolate  
Y
Y
Y
N
N
Y
N
N
N
N
Mains fail is fault after 8 hours  
Battery low is fault  
N
N
N
N
N
N
1
N
Y
Y
N
Y
Battery connection test enabled  
Hourly battery test enabled  
Daily 40 minute battery test enabled  
Charger high/low is fault  
MCP maps to zone  
N
None  
The Australian default settings are to comply with AS1603.4. Compliance with AS4428.1  
has different settings.  
Issue 2.7  
5 July 2001  
Page 6-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
The following table lists all of the programmable non-network parameters. The defaults  
listed are for Australian operation. The previous section lists items that have defaults  
specific to New Zealand operation.  
Item  
Options  
Default  
Access Codes  
Qty 1-10  
1 (User 0)  
6 Digits  
Time  
000000 (User 0)  
9:00am  
Autotest Time  
Autotest Inhibit  
Autotest Alarm  
FIP MCP  
FFCIF Type  
FFCIF Mode  
Dates For No Test  
Alarm Test Yes/No  
Zone, Disable  
2/3  
MAF Zones Only/  
All Zones/Disabled  
Enabled/Disabled  
Enabled/Disabled  
Enabled/Disabled  
Enabled/Disabled  
Enabled/Disabled  
Stat Holidays, weekends  
No alarm test  
Zone 1, Enabled  
Type 3  
MAF Zones Only  
FFCIF RZDU Remote Ack  
FFCIF Auto Ack  
FFCIF Alarm Bells  
FFCIF Display Cause  
FFCIF always flash non-maf  
alarm LEDs  
Enabled  
Disabled  
Disabled  
Disabled  
Disabled  
FFCIF always send non-maf alarm  
to RDU  
Enabled/Disabled  
Disabled  
All zones isolated = Standby  
Brig Test  
Standby operate/not operate  
Operate/Not MAF Alarm Relay Operates Alm Relay (V2.07  
or earlier)  
operates  
No operation (V2.08 or later)  
Printer  
Lines Per Page  
Baud Rate  
60  
9600  
Print Relay Operates  
Event printing  
Enabled  
Enabled  
Printer and history  
Event type selections for  
history & printer -  
- zone, system, sys run,  
circuit, point, relay.  
Disabled/1-6 Pulses  
Start time/date/diff  
End time/date/diff  
50/60Hz  
All types enabled  
Disabled  
Last SUN, OCT, 2am, 1 hr  
Last SUN, MAR, 3am, 1 hr  
50Hz  
Coder (NSW Cty)  
Daylight saving start  
Daylight saving end  
Mains 50/60Hz  
Mains fault is fault after 8 hours  
Battery low monitor  
Battery connection monitor  
Hourly battery test  
Daily 40 minute battery test  
Charger high/low = Fault  
Alarm buzzer  
Zone fault buzzer  
System fault buzzer  
Buzzer for non-MAF zone faults  
Fault sounder after 8 hours fault  
Fault sounder after 8 hours isolate  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Disabled  
Disabled  
Disabled  
Disabled  
Disabled  
Disabled  
Enabled  
Enabled  
Enabled  
Disabled  
Disabled  
Disabled  
TABLE 6.4.1  
PROGRAMMABLE PARAMETERS  
Continued .......  
Issue 2.7  
Page 6-32  
5 July 2001  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
Item  
Options  
Default  
Bells Isol Key (V2.06 or earlier)  
Ancil Isol Key (V2.06 or earlier)  
Keys enable  
Enable/Disable  
Enable/Disable  
Enable/Disable  
Enabled (V2.06 or earlier)  
Enabled (V2.06 or earlier)  
All keypad keys for:  
Door open/Door closed  
FF mode/non-FF mode  
Door open – all enabled  
Door closed – all disabled  
Remote sounder silence options  
Global network sounder silence  
Enable/Disable sysflt reset,  
ffcif actions, all commands  
Sysflt reset – enabled  
ffcif actions – enabled  
Any KeyTX  
Cmd TX  
Receive  
Enabled  
Enabled  
Enabled  
MAF board (NDU only)  
8 Zone Modules  
8 Relay Modules  
16 LED Display  
Display LEDs  
Present/not present  
Number Fitted 0-8  
Number Fitted 0-8  
Number Fitted 0-4  
Zones/Relays to LEDs  
1 Smoke  
1-1 in order  
1 Smoke  
Alarm Text  
(Detector Type)  
2 Heat  
3 FSW (Flowswitch)  
4 Manual  
5 Valve  
6 PSW (Pressure Switch)  
7 SPKLR (Sprinkler)  
8 & 9 Blank - All Programmable  
As per Alarm Text  
1 (Standard)  
Inst Alarm Text  
AZC Mode  
4 Manual  
1 Std  
2 (Hi Current)  
3 (Lo Current)  
4 (Tamper)  
5 (Disabled)  
TABLE 6.4.1  
PROGRAMMABLE PARAMETERS  
Continued .......  
Issue 2.7  
5 July 2001  
Page 6-33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
Item  
Options  
Default  
AZC Time Delay  
1 (Std)  
1 Std (2.3 Sec)  
2 (AVF/RAD)  
3 (SAD)  
4 (Delay)  
Delay (4)  
T1 into Alarm  
T2 out of Alarm  
1 (Inst Alarm)  
2 (Alarm)  
30 Seconds  
0 Seconds  
1 Inst Alarm  
Cct B1 (0-3V)  
3 (Normal)  
4 (Fault)  
Cct B3 (13-17.5V)  
1 (Inst Alarm)  
1 Inst alarm (V2.XX  
software)  
2 (Alarm)  
3 (Normal)  
For V1.XX software the  
default is Normal (3).  
4 (Fault)  
Zones  
Latch/Non Latch  
Latch  
Mapped/Not Mapped  
to MAF/Status Only  
Mapped/Not Mapped  
to ANC1, ANC2, BELLS  
Operation on Logic Function  
Operation on Logic Function  
Mapped  
Mapped  
MAF Brig Relays  
Open collector 1-64  
As Named  
Zone 1-64 Non Iso Alarm  
Respectively  
Variables  
Timers  
Type/Delay  
No Operation  
Module relays 1-64  
Configuration and logic  
equation, Text name  
Supervision: disabled  
Latching: No  
Map to MAF: Yes  
LED: Yes  
Isolatable: Yes  
Testable: Yes  
Sup Act: Yes  
No logic equation  
Supervision: disabled  
Latching: No  
Anc 1 Relay  
Configuration, logic equation  
Text name  
Map to MAF: Yes  
Doorholder mode  
Isolatable: Yes  
Testable: Yes  
Sup Act: Yes  
No logic equation  
Anc 2 Relay  
Configuration, logic equation, Supervision: disabled  
Text name  
Latching: No  
Map to MAF: Yes  
Load mode  
Isolatable: Yes  
Testable: Yes  
Sup Act: Yes  
No logic equation  
TABLE 6.4.1  
PROGRAMMABLE PARAMETERS (CONTINUED)  
Continued .......  
Page 6-34  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming  
Item  
Options  
Default  
Anc 3 Relay  
Configuration, logic  
equation, Text name  
Supervision: disabled  
Latching: No  
Map to MAF: Yes  
Isolatable: Yes  
Testable: Yes  
Sup ACT: Yes  
No logic equation  
RDU Protocol  
RDU 1-8  
LCD/non-LCD  
Enabled/Disabled  
Protocol A/B  
LCD  
Disabled  
A
1
MCP Zone  
TABLE 6.4.1  
PROGRAMMABLE PARAMETERS (CONTINUED)  
New Zealand mode  
Enable/Disable  
Enabled if NZ Display  
present  
Display extender board  
Battery very low alarm  
Evac defect fault  
Installed/Not installed  
Enable/Disable  
Enable/Disable  
Disabled  
Enabled in NZ mode  
Enabled in NZ mode  
External defect fault  
Enable/Disable  
TABLE 6.4.2  
PROGRAMMABLE PARAMETERS (NEW ZEALAND ONLY)  
Issue 2.7  
5 July 2001  
Page 6-35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming  
Document No: LT0122  
THIS PAGE LEFT INTENTIONALLY BLANK  
Page 6-36  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
CHAPTER 7  
PROGRAMMING SYSTEM CONFIGURATION  
Issue 2.7  
5 July 2001  
Page 7-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
7.1  
SYSTEM CONFIGURATION MENU  
The System Configuration menu is Option 4 in the Program Data menu (as shown in Fig  
6.1.2). It allows programming of the parameters which determine the way the F3200  
hardware operates. The menu includes the following:  
1 Circuits (AZCs); 2 Zones; 3 Modules; 4 Output Logic; 5 Relay (Supervision); 6 RZDUs and  
will also include option 7:Network for a networked system.  
Fig 7.1.1A shows the System Configuration menu and its hierarchial structure for V1.10  
software, Figure 7.1.1B for V2.00 to V2.08 software and Figure 7.1.1C for V2.09 or later.  
The diagram may be used in two ways as follows:  
1.  
When a user needs to change one particular parameter in an existing FIP, Fig's 6.1.2  
and 7.1.1 act as a "road map" that show the path required to access that parameter.  
2.  
When initially programming a new FIP, these diagrams may be used as a flowchart.  
Working from top to bottom, left to right, on first Fig 6.1.2 and then Fig 7.1.1, the  
entire database can be programmed.  
This shows that modules should be configured before circuits, zones or relays.  
Detail on each is shown in the following sections.  
CONFIGURING MODULES  
Selecting the modules option causes the LCD to display the modules configured and the  
modules present. E.g. Relay 1/2 means that 1 8RM is configured, but 2 are present.  
Select:  
1 (Zone) to change the number of 8ZMs;  
2 (Relay) to change the number of 8RMs;  
3 (Display) to change the number of LED Display Bds.  
4 (MAF) to enable/disable the MAF board (NDU only)  
Acknowledge the warning ("ACK") and then enter the new number of that particular module  
to be configured (e.g. press "2", "ENTER" to configure 2 modules).  
WARNING  
Changing the number of 8 zone or relay modules configured will automatically change  
the number of zones or relays allocated in the database. The mapping of zones/relays  
to LEDs on an LED Display may well be altered. It needs to be manually checked, and  
adjusted if necessary. Refer to Sections 7.3.3 and 7.5.3.  
Page 7-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
7.2  
CONFIGURING CIRCUITS (AZCS)  
7.2.1  
GENERAL  
When the configure circuits option is selected, the LCD displays a message, and then  
automatically selects AZC 01, or the last AZC programmed. For the selected AZC it displays  
a list of attributes which can be programmed, and the option that is currently selected for that  
attribute. The list may be stepped through by use of ! " keys. As each attribute is  
selected, the options for it are displayed on the bottom line.  
Attributes include:  
Alarm Text; Mode; Delay; Voltage Band B1; Voltage Band B3; Delay 1; Delay 2; Instant  
Alarm Text.  
When all the desired attribute options have been selected, press "ACK" to save the data,  
and then use "NEXT" or "PREV".  
7.2.2  
ALARM TEXT  
The Alarm text (detector type) selected is displayed as part of the Alarm message on the  
LCD and printer. The software makes allowance for the fact that MCPs may be connected  
to a circuit with detectors. For example, if an AZC has both smoke detectors and MCPs on  
it, then the alarm text should be Smoke.  
An AZC Alarm (see Section 7.2.5) will be displayed as a "SMOKE" Alarm, but an AZC  
Instant Alarm (MCP) will be displayed as a "MANUAL" Alarm (see below).  
Of the 9 options of alarm text, 1-7 have default text as shown on Fig 7.1.1 (i.e. 1 smoke, 2  
heat, etc) but 8 and 9 are blank. All are programmable as described in Section 6.4.3.  
The default alarm text is "SMOKE".  
Instant Alarm Text  
The Instant Alarm text is also programmable with the same options. The default is  
"MANUAL".  
7.2.3  
MODE  
The electronics on the 8 Zone Module which interfaces to an AZC (i.e. detector circuit) has a  
15mA current limited supply from +22V, and a pull up resistor to +22V. These are software  
controlled (i.e. turned on or off) and different combinations are used for different applications,  
giving five modes of operation as follows.  
Select the correct mode for the particular type of detectors being used on the AZC (refer to  
Appendix A2).  
Mode 1  
Standard  
15mA current limit from +22V supply.  
2k7 EOL.  
Suits most detectors.  
Mode 2  
High Current  
15mA current limit from +22V supply.  
2k7 EOL.  
Page 7-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
MODE (CONTINUED)  
Switches in additional pull up resistor to +22V in Alarm.  
Suits detectors with high alarm current requirement or remote LED indicators.  
(Refer to Appendix A2).  
Mode 3  
Mode 4  
Mode 5  
Low Current  
680 Ohm pull up resistor to +22V supply.  
10k EOL.  
Suits high resistance, low current circuit e.g. sub-indicator panel monitoring.  
Tamper  
680 Ohm pull up resistor to +22V supply.  
Requires EOL002Z active EOL.  
Suits supervision of "tamper-protected" sprinkler valves.  
Disabled  
Current limit and pull up disabled.  
No EOL required.  
Suits unused AZCs (saves quiescent current).  
7.2.4  
TIME DELAYS  
The standard time delay on any change of state is 2.3 secs (2.0-2.6 secs) i.e. to Alarm, to  
Fault, to Normal. During this time the input conditions are continually read (and debounced).  
The input must be continuously in the new state for the duration of the time delay to cause a  
change of state.  
There are two programmable time delays assigned to each circuit i.e. delay into alarm Delay  
1 (D1) and delay out of alarm Delay 2 (D2). One, or both of these are also used to generate  
the other time delay types as follows, AVF = Alarm Verification, RAD = Return Air Detector,  
SAD = Supply Air Detector.  
Note that the actual time delay also depends on the new condition (i.e. alarm or instant  
alarm). The operation of the SAD type was changed in V2.09 software.  
Delay Type  
1 Std  
Delay To Alarm  
Inst Alarm 2.3  
Delay to Normal  
(applies to cct not zone)  
2.3  
2.3  
Alarm  
2.3  
2 AVF/RAD  
3 SAD  
Inst Alarm 2.3  
Alarm (AVF/RAD sequence  
using D1)  
2.3  
2.3  
For V2.08 or earlier  
Inst. Alarm 2.3  
Alarm (AVF/RAD sequence  
Using D1)  
2.3  
D2  
For V2.09 or later  
Inst. Alarm 2.3  
If D1 is zero (default) the into  
Alarm time is 2.3 seconds  
If D1 is non-zero the delay into  
Alarm is AVF (using D1).  
2.3  
D2  
Issue 2.7  
5 July 2001  
Page 7-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
TIME DELAYS (CONTINUED)  
4 Delay  
Depends on "into alarm time"  
For D1 > 0  
Inst Alarm 2.3  
Alarm 2.3 + D1  
For D1 = 0  
2.3  
D2  
Inst alarm .2-.8 seconds  
Alarm .2-.8 seconds  
.2-.8 seconds  
D2 + .2  
Default Settings for Delays  
Delay Type  
2 AVF/RAD  
3 SAD  
D1  
11  
D2  
-
65  
65  
0 (2.3)  
11 (V2.08 or earlier)  
0 (V2.09 or later)  
30  
4 DELAY  
All times are in seconds.  
There is a minimum time delay of 2.3 seconds before acceptance of any new state except  
for a type 4 (DELAY) circuit with an into alarm time of zero, (D1=0), where the minimum time  
is reduced to .4 seconds (typically .4, minimum .2, maximum .8 seconds).  
D1 and D2 are programmable to 0-250 seconds but if set to zero, a minimum delay of 2.3  
seconds ( or .4) is still applied.  
Hence for a type 4 circuit with D1=0, D2=5, the into alarm delay is .2 to .8 seconds and the  
out of alarm delay is 5.2 - 5.8 seconds. For a type 4 circuit with D1=30 and D2=0, the into  
alarm delay is 32.3 seconds and the out of alarm delay is 2.3 seconds.  
Type 4 circuit with into alarm delay of zero  
The into alarm time for both detector operated (alarm) and for mcp (instant alarm) is .2 to .8  
seconds (typically .4 seconds). The delay into and out of fault and out of instant alarm is  
also .2-.8 seconds. The delay out of alarm is the out of alarm delay (D2) with a minimum of  
.2-.8 seconds.  
Note that programming an AZC for any time delay type resets programming of voltage bands  
B1 and B3 for that AZC to the default options. (These can be subsequently re-programmed,  
see Section 7.2.5).  
SAD & Delay Types  
SAD and Delay circuits (types 3 & 4) with D2 greater than zero, require non-latching  
detectors. The corresponding zones must also be programmed as non-latching.  
AVF/RAD Sequence  
Recognition of a detector's first operation occurs after 2.3 seconds. However, with AVF this  
does not generate alarm immediately.  
A delay of 3.4 seconds occurs and then the circuit is reset for 5.3 seconds. The circuit is  
then re-energised and ignored for 2.3 seconds. The sum of the delay, reset and ignore  
periods (default = 11 seconds) equals the D1 value, with alteration of D1 only affecting the  
delay period. E.g. setting D1 to 30 will provide a 22.4 second delay, followed by the reset  
and ignore period.  
If the detector re-operates in the following 150 seconds then an alarm is generated  
immediately. If it does not the sequence re-starts.  
Page 7-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
Reset Delay  
When an AZC is reset, automatically (during AVF), manually, or from an output logic  
command, the AZC is turned off for a period of 5.1 - 5.7 seconds.  
7.2.5  
VOLTAGE BANDS  
The F3200 monitors the AZC voltage and decides the circuit status on the basis of which  
one of 5 voltage bands it is in, as shown in Table 7.2.1.  
Voltage band B2 (3V to 13V) always generates Alarm (detector operated). B1 (0V to 3V)  
and B2 (13V to 17.5V) are programmable as to whether they generate Instant Alarm (MCP  
operated), Alarm (Detector Operated), Normal or Fault.  
This allows:  
1.  
Detectors with high alarm voltages (13V to 17.5V) to be used by programming B3 to  
be Alarm (detector operated);  
2.  
High current mode to be used on detectors with resistive bases (e.g. for LED  
brightness, remote LED) even though this may increase alarm voltage above band  
B2 if the LED was to become disconnected;  
3.  
4.  
MCPs to be distinguished from operated detectors on the same AZC e.g. by  
programming B1 to be Instant Alarm for MCPs shorting the circuit.  
MCPs to be used with a 15V Zener diode (program B3 to be Instant Alarm) so that  
MCP operation does not reset an operated detector.  
Notes  
1.  
Point 3 above allows operation of a time delay (e.g. AVF) on the detectors, while  
MCPs cause an Instant Alarm (i.e. 2 second delay only).  
2.  
If two devices with different Alarm voltages on the same circuit both operate, then the  
one with the lowest Alarm voltage will determine the voltage (and hence state) of the  
AZC. E.g. for MCPs wired to short a detector circuit, MCP operation will cause the  
AZC to see voltage band B1.  
Where detector operation has caused Alarm (Detector operated) on the zone,  
subsequent MCP operation will not initiate a new event (Instant Alarm) on the same  
zone unless the zone has been reset between events.  
3.  
4.  
When testing operation of detectors with Auto-Reset mode, the voltage state of the  
AZC (B1, etc) is continuously displayed on the LCD (ref Operators Manual, Section  
7.4).  
Programming an AZC for any time delay type (refer to Time Delays in Section 7.2.4)  
resets B1 & B3 to the default options for that time delay.  
Issue 2.7  
5 July 2001  
Page 7-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
VOLTAGE BANDS (CONTINUED)  
Voltage bands and their interpretation for modes 1, 2 and 3 are shown in Table 7.2.1  
following.  
Band Voltage  
Status  
Default Status  
Fault (Open Circuit)  
Normal  
B5  
B4  
B3  
21-22VFault (Open Circuit)  
17.5-21V  
13-17.5V  
Normal  
Programmable  
Normal (V1.XX software)  
Instant alarm (V2.XX software)  
B2  
B1  
3-13V  
0-3V  
Alarm  
Alarm  
(Detector Operated) (Detector Operated)  
Programmable Instant Alarm (Manual)  
TABLE 7.2.1  
AZC VOLTAGE BANDS FOR MODES 1-3  
In Mode 4, for AZC normal the voltage is in B5 with pulses into B4 due to the active end-of-  
line device. B2 is Alarm (valve operated). B3 is programmable to Alarm or Fault only  
(default is Alarm). B1 is programmable (default is Fault). All other conditions are Fault  
(Tamper).  
Page 7-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
7.3  
CONFIGURING ZONES  
7.3.1  
GENERAL  
The programmable options for each zone as shown in Fig 7.1.1 are:  
Latch/Non-Latch; Map/Non Map to MAF/Status Only; Map/Non-Map to Anc1;  
Map/Non-Map to Anc2; Map/Non-Map to Bells; Map to LED.  
Mapping a zone to an output e.g. to ANC1 (Ancillary Relay 1) causes the output to operate  
when that zone goes into alarm. Mapping will only be effective if the output retains its  
default programming (i.e. does not have a logic equation programmed for it).  
A non-latching zone will return to normal from Fault or Alarm if the AZC returns to normal. It  
is, therefore, only meaningful when used with a non-latching detector e.g. as is used in some  
air conditioning ducts, or flow switches.  
7.3.2  
MAPPING TO MAF  
Mapping to the MAF allows 1 of 3 options as follows:  
Mapped to MAF  
Not mapped to MAF  
Status Only  
A zone mapped to the MAF causes the Brigade relays (Alarm, Fault, Isolate) to turn on for  
the corresponding condition on the zone. It also enters the Alarm (FFCIF) queue on Alarm  
and is included in the Alarms, Faults and Isolated totals.  
Zones not mapped to the MAF will not do this, unless the FFCIF is programmed for "All  
Zones".  
Status Only Zone  
A zone programmed as "Status Only" will NOT:  
Operate the Brigade relays;  
Enter the FFCIF queue;  
Operate the common LEDs or buzzer on alarm or fault;  
Add to the totals in the base display (not even "other");  
Be logged in the printer or history queues;  
Be tested by System or Auto Test.  
Status zones may be mapped to Anc1, etc, and may be used in output logic equations, but  
will not be included in the output logic tokens NML, ALM, FLT, NMA, NMF, MUA and ISO.  
Status zones can be mapped to LEDs on a LED Display Board where fitted.  
7.3.3  
MAPPING ZONES TO LEDS  
Where 16 Zone LED Displays are fitted, zones and relays have a default mapping to the  
LEDs as described in Section 2.3.2. Other mappings are programmable but currently only 1-  
1 mapping of zones/relays to LEDs is supported (i.e. only one zone or one relay can be  
mapped to the one set of LEDs). Also a zone or relay can be mapped to only one set of  
LEDs (or not shown on LEDs at all, i.e. LED = 0).  
Issue 2.7  
5 July 2001  
Page 7-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
MAPPING ZONES TO LEDS (CONTINUED)  
For this reason, when changing zone to LED mapping it is necessary to disable the LED  
mapping of the zone/relays (by selecting LED 0) which have a default mapping to the LEDs  
which other zones are to be mapped to. (It is suggested that the programmer works from  
largest zone number to smallest for this).  
The LEDs on the 16 Zone LED display board may also be controlled by an output logic  
equation. This is described in section 7.4.8. Any of the LEDs which are controlled by output  
logic should not be mapped to by zones or relays.  
Page 7-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
7.4  
PROGRAMMING OUTPUTS  
7.4.1  
GENERAL  
The F3200 outputs (Ancillary Relays, MAF Brigade Relays, 8 Zone Module open collectors  
and 8 Relay Module relays) may be programmed to operate on a logic equation of zone and  
FIP status. Zone LEDs may also be controlled by an output logic equation. Output logic  
equations may also be used to isolate, de-isolate or reset zones. The Ancillary Relays  
(including Anc3 /Bells) and the Open Collector outputs each have a default logic equation  
but the module relays do not. By default, Ancillary Relays and Bells operate on an alarm on  
any zone mapped to operate that output. By default, open collector output n is active when  
zone n is in alarm. The LEDs on the 16 zone LED display boards may be controlled by  
output logic using a relay equation where the relay number is in the range 65 to 256.  
The outputs which can be programmed are shown in the Output Logic Menu in Fig 7.1.1 and  
described in Section 7.4.6.  
The logic equation takes the form of:  
Output = [operand] operator [operand] operator [operand] ...  
E.g. RL1 = Z3A + Z4A means that Module relay number 1 will energise when zone 3 is in  
alarm or zone 4 is in alarm (or both). Zone 3 alarm and zone 4 alarm are operands (inputs)  
and the logic operator is OR (+).  
Some examples of equations are shown in Section 7.4.4.  
Output Logic  
:
Number of "small" equations  
Number of "()" per equation  
Equation Size (note 1)  
Number of variables available  
Number of network variables  
Number of seconds timers available  
Number of minutes timers available  
Type of timer (see following)  
Time range of timers  
Error margin of seconds  
timers 1-64  
Error margin of minutes timers 65-72  
Output Logic Processing Time  
(refer to note 2 following)  
289 maximum  
14 maximum  
100 bytes max  
256  
128 per SID  
64 (1-64)  
8 (65-72)  
Stretch/Pulse  
0-250 seconds/minutes  
0-1 sec plus  
O/P Logic Time  
0-1 Minute  
0-1 second  
1.  
2.  
The maximum size of an equation is approximately 30-40 operands plus operators.  
It is 100 token bytes, where most operands use 2 bytes, and operators use 1 byte.  
The Controller continually "updates" the status of the inputs to the output logic  
equations, processes the equations, and updates the resultant outputs. The  
processing time taken is dependent on the number and size of the equations.  
A timer is started by a logic equation, and then operates the output via another logic  
equation. There is a processing delay added to the timer delay.  
For a system with only 10-20 small to medium sized equations, the processing delay  
should be of the order of 100 msec, and an approximate 1 second timer can be used.  
For a system with the maximum number of equations the processing time may delay  
beyond the 1 second stated, so that a delay programmed as "1 second" would cause  
a real delay (from input event to output options) in excess of 3 seconds.  
Issue 2.7  
5 July 2001  
Page 7-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
GENERAL (CONT’D)  
3.  
When programming logic equations, the amount of programming memory left can be  
viewed by using the "free space" option of the OUTPUT LOGIC menu.  
7.4.2  
LOGIC OPERATORS  
The logic operators allowed are as follows:  
OR (+)  
C = A + B  
logical or  
C is active if A is active or B is active.  
AND (.)  
C = A . B  
logical and  
C is active if A is active and B is active.  
XOR (@)  
C = A @ B  
exclusive or  
C is active if A is active and B is not, or B is active and A is not (i.e. if A and B  
are in opposite states).  
NOT (^)  
B = ^ A  
Logical inverse  
B is active if A is not active  
B is not active if A is active.  
These Operators each have a key in the right hand column of the 4 x 4 keypad.  
Using "1" to represent a "true" condition or "on" (active) state and "0" to represent a "false"  
condition or "off" (inactive) state, the following tables show the function of the logic operators  
for the various combinations of inputs (operands) A and B.  
A
B
A + B  
A . B  
A @ B  
^ A  
^ B  
0
0
1
1
0
1
0
1
0
1
1
1
0
0
0
1
0
1
1
0
1
1
0
0
1
0
1
0
TRUTH TABLE  
Priorities & Evaluation  
Equations are evaluated from left to right with the following priority:  
Brackets > NOT > AND > OR, XOR (within brackets the priority is the same).  
Example:  
R1 = (Z1A + Z2A) . ^ Z3F means relay 1 is active if:  
Zone 1 is in alarm or Zone 2 is in alarm; and Zone 3 is not in fault  
This is different to R1 = Z1A + Z2A . ^Z3F which means relay 1 is active if :  
Zone 1 is in alarm, or if  
Zone 2 is in alarm and Zone 3 is not in fault.  
Brackets "(" and ")" are used to group parts of an equation together so that the default  
operator priority can be overridden.  
In an equation, the number of "(" must always equal the number of ")".  
"(" and ")" are a second function of the "RECALL" and "PRINT" keys.  
Page 7-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
7.4.3  
LOGIC OPERANDS  
Two types of operand exist. (Operands are items that can be used within an equation i.e. as  
inputs).  
The first is an item which requires a further qualifier e.g. Zone  
requires a zone number (1-64) and a condition e.g. Alarm. (The zone item and alarm  
condition are abbreviated to ZN and Alm in the LCD option menu, but become Z and A when  
entered into an equation). Hence, when entering a zone operand, it must be qualified by  
entering first the zone number, and then the zone condition e.g. Z14A is zone 14 in alarm.  
The second type of operand is a token which needs no further qualification e.g. BLO which is  
Battery Voltage Low.  
In the following documentation the first type of operand (when qualified e.g. Z1A) and the  
second type of operand, are both called "tokens".  
7.4.3.1  
Operands Type 1  
Abbr Name  
In Equation  
AR  
R
V
Example (Token)  
AR2F  
R4I  
V7  
AR  
RL  
VL  
Ancillary Relay  
Module Relay  
Variable  
ZN  
TM  
OC  
ZR  
NA  
NV  
Zone  
Timer  
Open Collector Output  
Zone Range (n of m)  
New Alarm  
Z
T
OC  
Z:()  
Z3A  
T15  
OC32  
Z1:8(2)A  
NA[ACK;Z1F,Z5F,Z7F]  
NV3:120  
NA[r1..;s1..]  
NVsid:varnum  
Network variable  
Zone (ZN)  
Zxxq  
where xx = 1 - 64, (see note 1 below), q can be A,F,I,N,D,M,R as follows :  
A -  
Alarm . ^ (Isolated + Auto-reset mode) (i.e. Alarm in a zone which is not  
isolated or in Auto-reset mode).  
F -  
I -  
Fault . ^ (Isolated + Auto-reset mode).  
Isolated + Auto-reset mode.  
N -  
D -  
Normal - true when none of A, F or I are true.  
True if the current state of the circuit input is "Detector Operated" (Alarm). I.e.  
the voltage is in voltage band B2, or B1 or B3 and these are programmed as  
"Alarm". (See note 4 and warning below).  
M -  
R -  
True if the current state of the circuit input is "MCP Operated" (Instant Alarm)  
i.e. the voltage is in voltage band B1 or B3 and these are programmed as  
"Instant Alarm". (See note 4 and warning below).  
True if a reset is currently being applied to the zone. This is true for the  
duration of the 5 second reset applied to the circuit when the zone is reset by  
an Operator; for the 5 second AVF reset; and also for the 15 second Auto-  
reset mode reset.  
Following the reset of a zone there is a 2 second ignore period during which  
time this token returns false.  
Issue 2.7  
5 July 2001  
Page 7-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
OPERANDS TYPE 1 (CONTINUED)  
Notes:  
1.  
2.  
When entering numbers, leading zeros need not be entered.  
Alarm and Fault refer to the latched status for a latching zone and the current status  
for a non-latching zone.  
3.  
4.  
None of these zone tokens are affected by the programming of a zone as MAF  
mapped, non-MAF or status only.  
The circuit input refers to the "debounced" circuit input prior to the 2.3 second filter  
and zone "latch". That is, it takes 80-240 milliseconds to change state, is a non-  
latching condition, and is independent of zone programming or isolation (including  
the automatic isolation in Auto-Reset mode). Refer also to Section 7.4.10.  
WARNING  
The zone operands ZnD (detector operated) and ZnM (MCP operated) can return a value  
which is not the true condition of the circuit input in a number of situations as follows:  
1.  
During zone reset (other than AVF reset or Auto-Reset mode reset) the ZnD and  
ZnM operands will be the value that existed at the start of the reset. This includes  
the 2 second post reset delay, a total of 7 seconds. After this they will be the current  
state of the circuit input. This is true only for V1.10 software onwards. For earlier  
V1.0X versions of software ZnD and ZnM are both FALSE for the duration of the  
reset.  
2.  
During AVF reset and Auto-Reset mode reset the state of the circuit input is forced to  
be B1 (Band 1) during the actual 5 second/15 second circuit reset and at the end of  
this period may temporarily be any of the values B1, B2, B3, B4 or B5 until the circuit  
and detectors power up again.  
Thus the operands ZnD and ZnM may be true during these times depending on the  
programming of the circuit.  
Band B2 always maps to detector operated/alarm. Bands B1 and B3 may be  
programmed to map to any of MCP operated (instant alarm), Detector Operated  
(alarm), fault and normal. During AVF Reset and Auto-Reset mode reset the tokens  
ZnD and ZnM will follow the state of the circuit. E.g. If B1 is programmed as instant  
alarm then ZnM will return true during the reset when the state of the circuit is B1.  
3.  
During System Test and Auto-Test circuit alarm testing, any circuit which has an  
alarm test applied to it will be in band B3. Operands ZnD and ZnM will return true or  
false according to the programming of band B3.  
Note that not all zones are tested by System Test and Auto-Test. Zones which are  
not tested include:  
1.  
2.  
3.  
4.  
Isolated zones.  
Zones which are already in alarm or fault at the start of the test.  
Status only zones.  
Zones where the current input state is B1 and B1 is programmed to be  
normal.  
4.  
During zone alarm test the ZnD operand will return true if the test operates correctly.  
Page 7-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
OPERANDS TYPE 1 (CONTINUED)  
Zone Range (ZR)  
Zxx:yy(zz)q  
where xx, yy, zz = 1 - 64, yy > xx , (yy - xx) + 1 > zz  
q can be A,F,I,N,D,M,R as above.  
The operand returns true if the number of zones in the range xx to yy in the specified  
condition is zz or greater. If zz is zero at least one zone must be in the specified condition  
for the operand to be true (i.e. 0 and 1 are the same).  
Example  
R4 = Z2:6(2)A means that relay number 4 will energise when at least any two zones in the  
range 2 to 6 go into the alarm state simultaneously.  
Note that the range includes the zones from xx to yy so allocation of zones is important  
when using this operand.  
Note also that a zone range with zz = 1 is simply the OR of all the zones in the range and  
that a range of xx..yy with zz = yy - xx + 1 is simply an AND function.  
Z1:10(1)A = Z1A + Z2A + Z3A + Z4A + Z5A + Z6A + Z7A + Z8A + Z9A + Z10A  
Z11:13(3)F = Z11F . Z12F . Z13F  
Relay (RL) (i.e. Module Relay)  
Rxxq  
where xx = 1 - 64  
q can be A,F,I,N as follows  
A -  
F -  
I -  
True if the relay is currently activated and not isolated.  
True if the supervision is currently in fault and not isolated.  
True if the relay is isolated.  
N -  
True if none of A,F or I are true.  
The module relay tokens are not affected by whether the relay is mapped to the MAF or not.  
The F condition may be latching or non-latching (as programmed under relay supervision for  
that relay).  
Ancillary Relay (AR)  
ARxq  
where x is 1,2,3 for Ancillary Relay 1,2,3  
q can be A, F, I or N as for the module relays  
For Ancillary 3 (which can be Bells, refer to Section 3.5.3) the conditions of A, F, I and N are  
not affected by whether the relay is used as Ancillary 3 (i.e. controlled by output logic) or  
used as Bells (controlled by zone alarm and Auto-reset mode).  
The relay tokens are not affected by whether the relay is mapped to the MAF or not. The F  
condition may be latching or non-latching (as programmed under relay supervision for that  
relay).  
Issue 2.7  
5 July 2001  
Page 7-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
OPERANDS TYPE 1 (CONTINUED)  
Open Collector (OC)  
OCxx  
where xx = 1-64  
OCxx is true if OCxx is active from its own logic equation and false if OCxx is inactive.  
New Alarm (NA)  
The New Alarm token (NA) is a set/reset latch, which incorporates two lists of tokens. One  
list of tokens "sets" the latch i.e. when a token goes true the latch goes true and stays true,  
even if the token returns to false. The other list of tokens "resets" the latch i.e. when a token  
goes true the latch returns to false and stays false until a token in the "set" list goes from  
false to true. On power up, NA is false. NA takes the form:  
NA[r1,r2,....rn;s1,s2,....sm]  
where r1-rn is the list of tokens which reset the latch and  
s1-sm is the list of tokens which set the latch.  
Entry of an NA token into an equation is described in Section 7.4.5.  
If a set and a reset token were to both go true at the same time, then reset will override set,  
ie. the latch will turn off.  
Variables  
Vxxx  
where xxx = 1 - 256  
A variable is a "label" operand which may be equated to a common block of logic that occurs  
in the equations of more than one output. Using a variable saves re-entering and repeating  
the execution of the identical portion of the logic equations.  
Note that all variables are set to "false" on power up.  
Network Variables  
NVsss:nnn  
where sss = SID number 1-254 and nnn = variable number 0-127.  
A networked F3200 or NDU has 128 network variables of its own that it may assign values to  
with an equation e.g. NV5=Z1A+Z2A  
The state of the 128 local network variables is transmitted onto the network for use by other  
systems. This panel receives network variables from other systems and may use their  
values in equations but may not assign values to network variables from other systems.  
All network variables are set to FALSE on power up.  
Page 7-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
OPERANDS TYPE 1 (CONTINUED)  
Timers  
Txx  
where xx = 1 - 64 for seconds timers and 65-72 for minutes timers.  
Timers allow outputs to be timed from inputs. They all have two time delays associated with  
them and can be "stretch" timers or "pulse" timers, and the default configuration sets both  
delays to zero, and all timers are set to "false" on power up.  
A stretch timer (S) follows the programmed input with two programmable periods i.e. Input  
on to Output on, and Input off to Output off.  
A pulse timer (P) is initiated by the input with two programmable delays, i.e. Input on to  
Output on, and Output "on" duration.  
Examples:  
These examples show a seconds based timer 1-64, but the same logic  
applies to the minutes based timers.  
1.  
T1 [S20:30] = Z1A (Alarm State on Zone 1)  
Z1A  
T1  
ON  
OFF  
ON  
OFF  
20sec  
30sec  
2.  
T5 [P30:25] = Z1A  
ON  
Z1A  
T5  
OFF  
ON  
OFF  
30sec  
25sec  
Notes  
1.  
If the input turns off before the first delay has expired, the timer is reset. Timing will  
restart from zero when the input next turns on.  
2.  
3.  
Any changes to the input while a pulse timer output is on will not affect the output.  
For a pulse time of 0, the output may or may not momentarily turn on.  
Issue 2.7  
5 July 2001  
Page 7-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
7.4.3.2  
Operands Type 2  
ACK When the "ACK" key is pressed with the base display selected this returns true for  
between 1 and 2 complete passes of all output logic equations.  
ALM True if 1 or more local MAF zones is in alarm, or true in New Zealand mode if a  
latched battery very low alarm is present.  
BEL See discussion on Bells/Anc3 in Ancillary Relay Tokens.  
Always false if Bells is isolated or silenced by network silence - otherwise , true if:  
1.  
2.  
3.  
4.  
Non isolated zone mapped to Bells is in alarm, or  
Bell test in progress  
2 second ring for Auto-reset mode for non isolated zone mapped to bells.  
For networked systems, a network MAF alarm state received from another  
panel and this panel is programmed to use it and this panel is also  
programmed with "receive network bells control" enabled.  
In New Zealand mode, true if Trial Evac operated.  
5.  
BFT This is available in V2.07 or later software and is true when there is a battery  
connection fault or a battery capacity fault. Note the battery connection tests and  
battery capacity tests must be enabled for them to produce faults.  
BGT True if the brigade test key on the local FIP or an RZDU has been held down for 2  
seconds - at which point this token returns true while the key remains down (even if  
the brigade test has been programmed to not operate the Brigade Alarm relay). For  
networked systems, this token is not true for a brigade test initiated at another panel  
on the network.  
BLI  
Bells Isolate. For V2.07 or earlier software, BLI is true if the bells are isolated locally.  
For V2.08 or later, BLI is time if the bells are isolated locally or if they are silenced by  
a received network silence state. Note: for the bells to be silenced locally by a  
received network silence state, this panel must have “receive network bells silence”  
enabled and must also have “use MAF status” enabled for the particular SID sending  
the network silence. For New Zealand mode, BLI is not set time by the local silence  
alarms keyswitch (refer NSA).  
BLO Battery low. True if the last battery test failed. Remains true until a successful test  
has been completed. If battery low fault monitoring is enabled it will also be set true  
by a battery low fault.  
BSR New Zealand mode local services restore operated.  
BTS True if a battery test is currently in progress.  
CGF This is available in V2.07 or later software and is true when there is a charger fault  
and charger fault monitoring is enabled.  
FLT  
ISO  
True if 1 or more local MAF-mapped zones or module/ancillary relays are in fault.  
True if 1 or more local MAF-mapped zones or module/ancillary relays are isolated.  
MFL True if the mains is currently failed. If it is desired to detect a condition of mains  
failed continuously for 8 hours then timer logic must be used in conjunction with this  
token.  
MUA True if there are 1 or more unacknowledged alarms in the FFCIF queue.  
NED New Zealand mode external defect input true.  
Page 7-20  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
OPERANDS TYPE 2 (CONTINUED)  
NEV New Zealand mode evac defect input true.  
NMA True if 1 or more non MAF-mapped zones are in alarm.  
NMF True if 1 or more non MAF-mapped zones or non MAF-mapped module/ancillary  
relays are in fault.  
NML For Australian operation, the NML token is false if any of the conditions (including  
network states) which cause either the Brigade Alarm or Brigade Fault relay to  
operate (if not controlled by output logic) are true. Note this does not include  
conditions which cause the standby relay to de-energise and do not energise Brigade  
Defect (e.g. fuse blown, database checksum error). The SFT token includes  
conditions which de-energise standby but not Brigade Fault.  
For New Zealand operation the NML token is true if there are no abnormal  
conditions.  
NSA New Zealand mode local silence alarms operated.  
ODR True if the outer door is currently open.  
PLI  
True if the "Plant" flag is set to isolated.  
The PLI token may be used to isolate a set of relays from the single option on the  
Ancillary Isolate key menu. The equation of each relay to be isolated must take the  
form Rn = (eqn) .^PLI.  
The PLI token is not mapped to the MAF (i.e. Plant Isolate does not operate the  
Brigade Isolate relay, common Isolate LEDs, etc). To have the Isolate relay operate  
on PLI it is necessary to program it as follows: ISO = ISO + PLI.  
When PLI is true, the Ancillary Isolated LED is on (as it is if either ancillary relay 1 or  
2 is isolated, or any module relay is isolated).  
RST When the "RESET" key is pressed with the base display selected this returns true for  
between 1 and 2 complete passes of all output logic equations.  
STS True if a system test or auto test is currently in progress.  
SOA This is available in V2.07 or later software and is true when the alarm buzzer is  
currently sounding.  
SOF This is available in V2.07 or later software and is true when the fault buzzer is  
currently sounding.  
SFT True if any system fault is present (refer to Operator's Manual Section 6.6.3).  
TEV New Zealand mode local trial evac operated.  
Issue 2.7  
5 July 2001  
Page 7-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
7.4.4  
EXAMPLES OF LOGIC EQUATIONS  
Example 1 - Use of Variables  
Assume that two relays are required with similar logic equations, as follows:  
R1 = (Z1A + Z2A + Z9A + Z10A) .^ Z3A  
R9 = (Z1A + Z2A + Z9A + Z10A) .^ Z11A  
Rather than enter both equations in full, it is easier to assign a variable to the common  
section of logic and enter three equations as follows:  
V2 = Z1A + Z2A + Z9A + Z10A  
R1 = V2.^Z3A  
R9 = V2.^Z11A  
Example 2 - Use of Zone Range and Timers In a Deluge System  
A manned area in a building has a high risk of fire but some chance of false operation of a  
smoke detector. The area is protected by a solenoid operated deluge system. It is  
considered best to run three separate smoke detector circuits through the area, and have a  
"voting" system. Also, there is to be one circuit with heat detectors and mcps, and a circuit  
of different coloured mcps which function as "Inhibit Deluge".  
The logic specified by the consultants is that any smoke, heat or mcp operation sounds an  
Alert warning tone in the area.  
If any 2 of the 3 smoke circuits operate, an Evacuate tone is sounded, and 20 seconds later  
the deluge is to operate if no one has operated "Inhibit".  
If an mcp or heat detector operates, the Evacuate tone and timer are to start and "Inhibit"  
must not prevent the deluge from operating.  
Solution:  
By assigning the smoke and thermal circuits consecutively, the zone range operand can be  
used. Inhibit is assigned a separate zone which is configured as non-mapped to MAF,  
ANC1, ANC2 and BELLS.  
The "zones" could be assigned as follows:  
Zones Z9, Z10, Z11 are the smoke circuits  
Zone Z12 is the heat/mcp circuit  
Zone Z13 is the "Inhibit" circuit  
Relay R4 switches the "Zone Alert"  
Relay R5 switches the "Zone Evacuate"  
Relay R6 switches the "Zone Deluge" solenoid.  
The appropriate names for zones and relays would be entered as text. For thermal  
detectors with electronic bases and all mcps "shorting" the circuits, the AZCs would be  
configured with:  
AZC 12 as "Heat", with B1 = Alarm;  
AZC 13 as "Manual" with B1 = Instant Alarm.  
Page 7-22  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
EXAMPLES OF LOGIC EQUATIONS (CONTINUED)  
The logic may be entered using the zone range (ZR) option as follows:  
R4 = Z9:12(1)A (i.e. alert on any of zones 9-12 in alarm)  
V1 = (Z9:11(2)A.^Z13A)+Z12A (i.e. any two of zones 9-11 in alarm  
with Zone 13 not in alarm, or Zone 12 in alarm).  
R5 = V1 (evacuate tone)  
T1[S20:0]=V1 (stretch timer, input delay 20 sec)  
R6 = T1 (deluge)  
The variable, V1 is used to start the timer rather than relay R5, so that if someone operates  
R5 e.g. by the Test Relay function, there is no chance of it starting the time delay and  
initiating the deluge (R6).  
Example 3 - Use of Timers  
Timers have been partly described already in Section 3.8. Timers 1 to 64 are "seconds  
based" with a range of 0 to 250 seconds, and timers 65 to 72 are "minutes based" with a  
range of 0 to 250 minutes.  
A certain building has an outdoor yard with a very loud sounder. It is too loud to be left on  
continuously. For any alarm in the premises it is desired to give one set of three 5 second  
bursts on the sounder with 5 second delays between the bursts (Bells must operate as  
standard).  
Solution:  
A relay (say R7) is assigned to switch the sounder. Three pulse timers (say T5, T6, T7) are  
required.  
T5[P0:5] = ALM  
T6[P10:5] = ALM  
T7[P20:5] = ALM  
R7 = T5 + T6 + T7  
Issue 2.7  
5 July 2001  
Page 7-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
EXAMPLES OF LOGIC EQUATIONS (CONTINUED)  
Example 4 - Use of Timer To Make Continuous Pulsing  
A building has a loud "hooter" to attract the operator to the FIP. The hooter is relay driven  
and must pulse 1 second on, 1 second off, on occurrence of any alarm until it is  
acknowledged.  
Solution:  
Use a timer to make a 1 second on, 1 second off oscillator. A relay (say Anc2) and a timer  
(say T1) are assigned. The MUA (MAF unacknowledged alarm) is used as follows:  
T1[S1:1] = ^T1  
MUA  
ANC2 = T1.MUA  
ALARM  
ACKNOWLEDGE  
7.4.5  
ENTERING EQUATIONS  
Entering equations from the keypad is similar to entering text, but includes entering logical  
operators and brackets from specific keys.  
When an output (e.g. Relay 01) is selected, press "EDIT", "ENTER" or """ to enable  
equation entry for that output.  
Equation entry has two fields. The top field contains the equation which has been entered  
and the bottom field contains an array of operands which may be entered. "NOT" or "(" may  
also be entered directly from their keys.  
Each field has one of two cursors. The active cursor may be moved through the field it is  
in by use of the ! " cursors to select an operand or position in the equation. The inactive  
cursor $ shows where the active cursor would be if it was in that field.  
There is a choice of 5 lines of operands in the bottom field. These may be scrolled by use of  
the # and % keys. Note that numbers and operators can be entered directly from the  
keypad.  
"EDIT"  
toggles the cursor between the two fields.  
"DELETE"  
acts as backspace for a token just entered, or deletes any token/operator in  
the equation selected by the cursor (active or inactive).  
"ACK"  
saves the equation.  
"NEXT" &  
"PREV"  
step through outputs (e.g. relays).  
Notes:  
1.  
2.  
Observe the priorities specified in Section 7.4.2.  
It is recommended that brackets be used when entering a string of operands to make  
checking easier.  
Page 7-24  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
ENTERING EQUATIONS (CONTINUED)  
3.  
When an equation has been entered, check it, and count the number of "(" and the  
number of ")" to ensure they are the same.  
4.  
It is recommended that all equations be written on forms (such as in Appendix B)  
before they are entered, and then checked against the forms after they have been  
entered).  
Example  
Enter an equation to program module relay 5 to activate if Zones 9 or 10 go into alarm, but  
not if Open Collector 4 is active (say open collector 4 drives a status LED and has a logic  
equation entered to do this).  
The equation is:  
R5 = (Z9A + Z10A).^OC4  
From the "System Configuration" menu (4), select "Output Logic" (4) followed by "relay" (1).  
Use "NEXT" to step onto Relay 5 (R5)  
Press  
LCD Shows  
"""  
R5 = $  
(NOT AR RL VL N TM OC ZR NA NV  
"("  
R5 = ( $  
(NOT AR RL VL N TM OC ZR NA NV  
"ENTER"  
"9", "ENTER"  
"1"  
R5 = (Z █  
R5 = (Z9 █  
R5 = (Z9A $  
"OR"  
R5 = (Z9A + $  
(NOT AR RL VL N TM OC ZR NA NV  
"ENTER"  
"1" "0" "ENTER"  
"1"  
R5 = (Z9A + Z █  
R5 = (Z9A + Z10 █  
R5 = (Z9A + Z10A $  
R5 = (Z9A + Z10A) $  
")"  
"AND" "NOT"  
R5 = (Z9A + Z10A).^ $  
(NOT AR RL VL N TM OC ZR NA NV  
""" """  
(NOT AR RL VL ZN TM C ZR NA NV  
R5 = (Z9A + Z10A) .^OC █  
"ENTER"  
"4" "ENTER"  
"ACK"  
R5 = (Z9A + Z10a) .^ OC4 █  
R= (Z9A + Z10A) .^ OC4  
Equation Saved OK  
Issue 2.7  
5 July 2001  
Page 7-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
ENTERING EQUATIONS (CONTINUED)  
The next relay can be selected. Note that Z9A and Z10A could have been entered as zone  
range ZR9:10(1)A.  
Entering an NA Operand  
To enter an NA operand, do the following:  
1.  
2.  
3.  
Select NA with the in the bottom line and press "ENTER".  
Select the first token in the "RESET" group with the cursor keys and enter it.  
Select the next token in the "RESET" group and enter it (the , will automatically be  
inserted when this token is entered).  
4.  
When all the "RESET" tokens are entered, press one of the Operator keys ("AND",  
"OR", etc) then enter the "SET" tokens (on the right side of the ;).  
5.  
6.  
Select the desired token with the cursor keys.  
When all the "SET" tokens are entered, press "AND", "OR", "XOR" or "NOT" to exit  
from NA. If the NA is the last token in an equation and the operand just entered is  
not required, press "DELETE".  
Notes:  
1.  
A logic equation or another NA token cannot be entered directly into an NA operand.  
If they are required they must be entered as a variable (i.e. equate a variable to the  
desired equation).  
2.  
Multiple NA tokens can be used, but each one must be qualified by listing the group  
of tokens as it is entered. Should the same latch be desired as an operand in various  
equations, it would be expedient to assign a variable as the NA, and then call up the  
variable in equations. This saves re-entering the NA with its lists of operands.  
7.4.6  
THE OUTPUT LOGIC PROGRAMMING MENUS  
The Output Logic programming menus are shown in Fig 7.1.1 and include the following:  
Menu 1  
Relay (module relay); Variable; Timer; Open Collector; Ancillary Relay; Net Var;  
Menu 2  
MAF Relay; Zone Isol; Zone De-Isol; Zone Reset; free space  
Menu 3  
SNA (sounder activate - software V2.09 onwards)  
Menu 1  
Relay - this option is used to enter equations for the physical module relays (relay  
numbers 1 - 64) and to control zone LEDs (relay numbers 65 - 256).  
Variable - for variables 1 - 256  
Timer - timers 1 to 64 are seconds based and 65 to 72 are minutes based.  
Page 7-26  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
THE OUTPUT LOGIC PROGRAMMING MENUS (CONTINUED)  
Open Collectors - 1 to 64 corresponding to the AZC boards installed.  
Ancillary Relay - MAF ancillary relays 1,2,3.  
Net Var - network variables 1 - 256 (network systems only).  
Menu 2  
MAF Relay - Standby, Fault, Isolate, Alarm  
Zone Isol, Zone De-isol, Zone Reset - these commands can be applied to alarm  
zones (zones 1-64), module relays (zones 65 - 128), ancillary relays (zones  
193-196) and plant (zone 197). These are described in section 7.4.9.  
free space - this option is used to display the number of free and used output logic  
blocks - output logic storage memory is organised into 16 byte blocks.  
Menu 3  
SNA - for V2.09 or later software, this is used to control the fault sounder. When the  
equation changes from false to true, the fault sounder is activated and the SOF  
token becomes true. Pressing any key will silence the sounder. SNA must go  
false then true again to re-activate the sounder. The fault sounder will also be  
activated by any conditions in the system that normally activate it.  
7.4.7  
PROGRAMMING RELAYS  
When programming relays, the following points should be observed:  
1.  
2.  
The default operation of the F3200 MAF Brigade relays conform to AS1603.4.  
Programming relays for operation, other than default, may contravene the standard.  
If programming the Alarm relay with a logic equation and it is desired to have it  
operate during Brigade Test, then the equation entered should include the BGT  
token. For network systems, note that the ALM token does not include any alarm  
status received from other panels on the network.  
3.  
4.  
Although the MAF Standby relay may be programmed to operate off a logic  
equation, it is still de-energised (by hardware) for the Battery Very Low condition.  
If it is desired to use the Plant Isolate option of the "ANCIL ISOL" function menu, all  
relays to be isolated must include the PLI token in their equations. E.g. R3 = (Z5A +  
Z6A) . ^PLI.  
5.  
6.  
It is not recommended to program normally energised relays because Global  
Isolate and Plant Isolate de-energise them. Also, they increase FIP quiescent  
current. All relays have normally closed contacts (i.e. for relay de-energised).  
If Anc3 has a logic equation entered for it, it no longer operates as "Bells" and is not  
affected by the "BELLS ISOL" key. The key does still set the BLI token and so, if  
desired, another relay (e.g. a module relay) could be programmed to operate on a  
logic equation which includes BEL or BLI (and hence be isolated by "BELLS ISOL").  
The BELLS ISOLATED LED operates from BLI and is not affected by the  
programming of Anc3.  
Issue 2.7  
5 July 2001  
Page 7-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
7.  
Equations may be entered for relays 1-64 even through the appropriate 8 Relay  
Modules are not fitted. The resulting states could be sent to an RDU or another  
device on the RZDU bus.  
8.  
When driving the fault relay with logic, the following should be noted.  
The fault relay can be controlled with logic by the equation  
FLT = ... - some logic  
It is recommended that the SFT token is included in the equation for the fault relay.  
e.g.  
FLT = FLT + SFT + …  
The FLT token is true when one or more MAF mapped non-isolated zones or  
module/ancillary relays are in fault.  
The SFT token is true for system faults - these are listed in detail in section 6.6 of  
the F3200 Operator's Manual LT0119.  
With no logic equation driving the brigade fault relay, the relay will energise for the  
following things.  
1. non isolated maf zone/relay faults  
2. all battery/ mains/ charger faults  
3. RZDU system faults  
4. circuit failed system auto test  
5. network associated faults (discards, scan fails, zone or system faults received  
from other panels)  
6. NZ mode defects (NDU only)  
If you drive the fault relay with logic  
FLT = FLT + SFT  
then the fault relay will energise for some additional conditions which don't cause the  
fault relay to operate when there is no equation FLT = …  
These include the conditions which normally cause the Standby relay to de-energise  
rather than energising the fault relay e.g. EEPROM database checksum error or  
LED display board fault.  
For network systems, FLT = FLT + SFT does not include zone or system faults  
received from other panels.  
9.  
For network systems, when driving the isolate relay from logic, the equation  
ISO = ISO  
does not include any maf isolate conditions received from other network panels.  
7.4.8  
CONTROLLING ZONE LEDS  
An output logic equation controlling a "module relay" where the relay number is in the range  
65 to 256 is used to control a zone LED. F3200 allows a maximum of four 16 zone LED  
display boards corresponding to 64 zones. Relay equations with relay numbers 65-128 are  
used to control the alarm LEDs 1 to 64. Relay equations with relay numbers 129-192 are  
used to control the fault LEDs 1 to 64. Relay equations with relay numbers 193-256 are  
used to control the isolate LEDs 1 to 64. Relay numbers 65-256 cannot be used in the "right  
hand side" part of an equation as an operand. The LEDs being controlled will be either on  
steady or off - they cannot be selected to flash.  
It is necessary to ensure that no zone or module relay is mapped to any LED being  
controlled by logic (mapping of zones to LEDs is described in section 7.3.3).  
Page 7-28  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
CONTROLLING ZONE LEDS (CONTINUED)  
For example, an equation of R65=Z1:20(1)A  
will result in alarm LED 1 turning on steady whenever one or more zones in the range 1 to  
20 has an unisolated alarm.  
An equation of R256=PLI , will result in isolate LED 64 turning on steady when PLANT is  
isolated.  
An equation of R129=SFT , will result in fault LED 1 turning on steady whenever there is a  
system fault.  
RDU Zones 129-192  
If any output logic equations are used to control zone LEDs, then the status transmitted to an  
RZDU will include data for "zones" 129 to 192 (otherwise zones 129 to 192 are not sent to  
an RZDU). The status of zones 129 to 192 as sent to an RZDU is generated from the output  
logic equations which control the LEDs, where zones 129-192 correspond to LEDs 1 to 64.  
For example, with equations  
R65=Z1:20(1)A, R129=Z1:20(1)F and R193=Z1:20(1)I  
then the status of zone 129 at an RZDU would show alarm if any of zones 1 to 20 at the  
F3200 controller had an unisolated alarm, and similarly for fault and isolate.  
NOTE At the F3200 controller, zones 129 to 192 actually correspond to open collector  
outputs and are NOT the same as zones 129 to 192 at an RZDU.  
7.4.9  
PROGRAMMING ZONE ISOLATE/DE-ISOLATE/RESET COMMANDS  
F3200 allows the programming of equations which initiate zone isolate, zone deisolate or  
zone reset commands. These commands have the same effect as if the operator initiated  
the command using the keypad. With V2.08 or earlier software, these commands can be  
used with alarm zones only (zones 1 to 64). With V2.09 or later, these commands can be  
used with module relays (using zone numbers 65 to 128), ancillary relays (zones 193 to 196)  
and plant (zone 197).  
7.4.9.1  
ENTERING OUTPUT LOGIC ZONE COMMANDS  
Selecting one of the menu options from output logic menu two "4:Zone isol 5:Zone deisol  
6:Zone reset" will show the first programmed equation of that type. Pressing NEXT and  
PREV steps forward and back through the list of equations of that type. The equation is  
shown with a "first zone" and "last zone" and the command is applied to the range of zones  
specified inclusively. If the first zone is the same as the last zone then the command applies  
to that zone only. If there are no equations of the selected type then a "blank" equation is  
shown with the first zone and last zone equal to zero. A "blank" equation is also shown after  
stepping through all existing equations of the selected type and this can be used to enter a  
new equation.  
Issue 2.7  
5 July 2001  
Page 7-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
ENTERING OUTPUT LOGIC ZONE COMMANDS (CONTINUED)  
When an existing equation (call it "E1") is shown, the first and/or last zone may be modified  
and if an equation with the new first and last zone does not already exist then the "right hand  
side" of equation "E1" will be copied into the new equation (call it E2). Equation E2 may  
then be modified if desired, or immediately saved. When equation E2 is saved the user will  
be given the choice of either deleting/overwriting the prior equation E1 or of keeping the  
existing equation E1 and creating a completely new equation E2. This allows the user to  
modify the first or last zone of an existing equation (E1) and save it without having to then go  
back and delete the previously existing equation E1 (and perhaps forgetting to). It also  
allows the "right hand side" of an existing equation to be copied to a new equation with a  
different range of zones. The DELETE and INSERT keys may be used to modify the copied  
equation as with normal equation editing.  
The logic equations for zone commands are entered as:  
ZRn:m="equation" to reset zones n to m inclusive  
ZIn:m="equation" to isolate zones n to m inclusive  
ZDn:m="equation" to deisolate zones n to m inclusive  
If n and m have the same value then the command applies to that single zone.  
There may be only one equation of each type (reset/isolate/deisolate) with the same first  
zone/last zone. E.g. it is not possible to have both ZI3:7=BLI and ZI3:7=Z1I as two separate  
equations. The logic should be combined into one equation.  
When an existing equation is recalled or has just been saved, the cursor will be positioned  
on the "I", "D" or "R" immediately to the left of the "first zone" number. The "up arrow" key  
may be used to cycle through "I" (isolate), "D" (deisolate), or "R" (reset) and if the equation  
of the new type exists it will be recalled otherwise it will be created and the "right hand side"  
of the previously shown equation will be copied into the new equation.  
After entering all of the zone isolate/deisolate/reset equations it is recommended that they be  
checked by printing the database to a printer or computer, or by stepping through the list of  
equations on the LCD. Check that the equations are correct and that no unwanted  
equations have been inadvertently left in the list. An entire equation may be deleted using  
the DELETE key when the cursor is on the left hand side of the equals (=) sign of the  
equation.  
W A R N I N G  
To view the zone command logic equations that have been programmed, the preferred  
method is to “PRINT” the database or output logic to a computer or printer. If this is not  
possible then the equations can be viewed on the LCD. To do this, select one of the options  
4:Zone Isol, 5:Zone deisol or 6:Zone reset and use the NEXT and PREV keys to step  
through the entire list. DO NOT use the up arrow/down arrow keys to swap between isolate,  
de-isolate or reset types and do not enter explicit zone numbers as this may create a new  
equation where one did not previously exist (as a convenience, the previously displayed  
equation is copied to the new one if there is no equation already defined for the new type or  
zone numbers).  
Hence if you wish to view existing equations, use only the NEXT and PREV keys.  
Page 7-30  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
7.4.9.2  
OPERATION OF OUTPUT LOGIC ZONE COMMANDS  
Reset Command  
A single zone or a range of zones may be reset. All zones in the specified range will be  
reset, regardless of whether they are in alarm or not, as if the zones had been reset by an  
operator from the keypad.  
The output logic initiates the reset command whenever the equation on the right hand side is  
true. If the equation is still true at the end of the reset then another reset will be immediately  
initiated, and this will repeat until the equation becomes false. Therefore, to avoid repeated  
resets the equation should be arranged so that it becomes false before the end of the reset.  
The equation needs to be true for only one pass of the output logic for the zone reset to be  
initiated.  
Isolate / Deisolate Commands  
A single zone or a range of zones may be isolated/deisolated. The command will be applied  
to all zones in the specified range regardless of the type of zone.  
Whenever the right hand side of the equation is true, the zones will immediately be  
isolated/deisolated if they are not already isolated/ deisolated.  
If an equation to isolate/deisolate a zone is continually true, and an operator enters the  
opposite command using the LCD/keypad, then the zone will briefly change but will quickly  
revert back due to the output logic.  
Therefore the logic equation should be arranged so that the equation is only true for a brief  
time or on a change of state. The NA operator may be used for this purpose.  
7.4.9.3  
EXAMPLE EQUATIONS  
(i)  
The equation ZI3:7=BLI will cause zones 3 to 7 (inclusive) to be isolated whenever  
BLI is true, i.e. the bells are isolated. If the operator manually deisolates any of  
zones 3 to 7 then the output logic will immediately isolate them again if BLI is true.  
(ii)  
An external switch is used to isolate or deisolate a group of zones. The equation  
ZI5:8=Z16M will result in zones 5, 6, 7 and 8 being isolated when zone 16 (the  
switch) is in a short circuit state. If it is necessary to deisolate the zones again when  
zone 16 is taken out of short circuit then a second equation is needed, perhaps  
ZD5:8=^Z16M.  
However, including these two equations would prevent an operator from isolating or  
deisolating the zones using the keypad because one or other of the two equations  
(whichever has a TRUE "right hand side") is continually attempting to isolate or  
deisolate the zones. An "NA" function can be used to overcome this as follows.  
V1=NA(V1;Z16M)  
V2=^Z16M  
V3=NA(V3;V2)  
ZI5:8=V1  
ZD5:8=V3  
The output logic will isolate/deisolate the zones only when a transition of zone 16  
into/out of the short circuit state occurs. Only one of variables V1 or V3 is true for  
exactly one complete pass of the output logic after a transition of zone 16.  
Issue 2.7  
5 July 2001  
Page 7-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
EXAMPLE EQUATIONS (CONTINUED)  
(iii)  
To reset a zone after it has been in alarm for 30 seconds.  
T1[S30:0]=Z1A  
ZR1:1=T1  
After zone 1 alarm (Z1A) has been true for 30 seconds, timer T1 will become true  
and a reset command will be issued to zone 1. This will immediately cause Z1A to  
become false, resulting in timer T1 becoming false and removing the reset command  
initiation. If the zone subsequently goes back into alarm, then after a further 30  
seconds it will be reset again.  
Note: If the zone is isolated then it will NOT be reset 30 seconds after being in alarm  
due to the fact that the Z1A token is false for an isolated zone.  
7.4.10  
USING THE ZND AND ZNM TOKENS  
Some applications require the use of a switch, where the state of the switch can be  
accessed in output logic. One of the zone output logic tokens listed in Section 7.4.3.1 would  
normally be used to access the state of the switch - ZnA, ZnF, ZnN, ZnD, ZnM, ZnI or ZnR.  
For example if a short circuit state is produced when the switch closes then band B1 could  
be programmed as instant alarm and the ZnM token will become true when the state of the  
circuit is short circuit/B1.  
The ZnD and ZnM tokens have a faster "response" time (80-240 millisecs) than ZnA or ZnF.  
As described in section 7.2.4 "Time Delays", for V2.XX software a type 4 circuit with an into  
alarm delay of zero has an actual delay of 200 to 800 millisecs (typically 400 millisecs) which  
means that the ZnA and ZnF tokens become true within 200 to 800 millisecs. Otherwise the  
time delay for the ZnA and ZnF tokens is 2.0 to 2.3 seconds. The ZnD and ZnM tokens are  
not affected by whether the zone is isolated or not (unlike ZnA and ZnF) but the ZnI token  
can be used in an equation to qualify the ZnD and ZnM tokens if necessary.  
Which zone token to use and which circuit delay type to program depends on the response  
time required for the switch.  
There are some other special considerations to note when using the ZnD and ZnM tokens.  
In particular, during system or auto test or at the termination of a zone alarm test the circuit  
input may be briefly in the band B3 state long enough for ZnD or ZnM token to become  
briefly true. During system/auto test if band B3 is programmed as "detector operated" or as  
"instant alarm" then the ZnD or ZnM tokens will be true for the 1 to 2 seconds that the circuit  
is in band B3 during the test.  
A "status only zone" (refer Section 7.3.2 configuring zones), does not get tested during  
system or auto test and hence will not have the problem of the circuit going into band B3  
during system test.  
During zone alarm test the state of the circuit will appear to be in band B2 (unlike  
system/auto test). However, if the zone test is terminated by pressing the ACK key without  
resetting the zone, then the circuit will appear to be in band B3 for a short time (approx 200  
millisecs) - long enough to cause the ZnD or ZnM tokens to return true for a short time,  
depending on the programming of band B3. When a zone is reset the ZnD and ZnM tokens  
are prevented from changing during the 7 second reset operation as described in section  
7.4.3.1.  
Therefore for a "status only zone" it is recommended that band B3 be programmed as  
normal rather than instant alarm.  
Note that for V2.XX software the default mapping for band B3 is "instant alarm" which is the  
state that causes the ZnM token to be true.  
Page 7-32  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
7.5  
RELAY SUPERVISION  
7.5.1  
GENERAL  
The Ancillary relays (Anc1 and Anc2) and Bells relay on the MAF/PSU, and the Module  
relays all have the option of supervision (i.e. checking the wiring from a relay to its load to  
see that it is not "short" or "open" circuited).  
In F3200, the supervision also includes a "confirmation" function i.e. it expects to "see" a  
different state after a relay has been activated. If an incorrect state is "seen" by the  
supervision, before or after relay activation, then it generates a "fault" condition for that relay.  
Supervision in the activated state can be disabled for “load” mode if it is not required, for  
example when the relay switches the load to 0V.  
For each relay the supervision can be disabled if not required, mapped to the MAF, and  
made latching or non-latching. Anc 1 + 2 relays can be programmed for two different modes  
of supervision - door holder or load mode. All relays can also be individually made non-  
isolatable (stops the Operator isolating them) and non-testable.  
The Relay (Supervision) menu (Option 5 on the System Configuration menu) has two  
options as follows: 1 Bells/Ancillary Relays; 2 Module Relays. The options for selecting  
relays as Isolatable, Testable and Supervise Activated state are available in V2.09 or later  
software.  
7.5.2  
BELLS & ANCILLARY RELAY SUPERVISION  
This is option 1 in the Relay Supervision menu.  
Refer to Section 3.4.2 for the electrical characteristics of the Bells and Anc1, Anc2 relay  
supervision.  
Ancillary Relay Supervision  
The options which may be entered for Anc1, 2 and Anc3 are:  
Supervision enabled (E) or disabled (D).  
Supervision latching (L) or non-latching (N) (i.e. the fault condition).  
Fault and isolate mapped (M) or not mapped (N) to the MAF.  
Supervision is load (L) or door holder (D) mode (not for ANC3).  
Isolatable (yes/no)  
Testable (yes/no)  
Supervise Activated State (yes/no)  
The default setup (by EEPROM initialise) is.  
ANC 1: supervision disabled, non-latching, mapped to MAF, Door holder, isolatable,  
testable, activated state supervised.  
ANC 2: supervision disabled, non-latching, mapped to MAF, Load mode, isolatable,  
testable, activated state supervised.  
ANC 3: supervision disabled, non-latching, mapped to MAF, isolatable, testable, activated  
state supervised.  
Issue 2.7  
5 July 2001  
Page 7-33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
7.5.3  
MODULE RELAY SUPERVISION  
This is option 2 of the Relay Supervision menu.  
To program module relay supervision the desired relay number is selected by use of the  
"NEXT" and "PREV" keys.  
The options which may be selected are:  
Supervision enabled (E) or disabled (D).  
Supervision latching (L) or non-latching (N) (i.e. the fault condition).  
Fault and isolate mapped (M) or not mapped to the MAF.  
Supervision and relay status mapped to LED n on an LED Display (where fitted).  
Isolatable (yes/no)  
Testable (yes/no)  
Supervise Activated State (yes/no)  
The mode of monitoring is always "load" (refer to Sections 3.4.4 and 8.6).  
The mapping of the relay status (activated, isolated, fault or normal) to LEDs on an LED  
Display is described in Sections 2.3.2 and 7.3.3.  
Page 7-34  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Programming System Configuration  
7.6  
RDU  
The connection of RDUs (RZDUs, Remote LCDs) to a FIP is described in Sections 2.1.6 and  
8.9.  
An F3200 panel transmits the status of its alarm zones and module relay zones to an RDU.  
The F3200 panel may have from zero to 64 alarm zones and these zones are always  
mapped to zones 1 to 64 at the RZDU. The F3200 panel may have from zero to 64 module  
relays and for F3200 V2.00 and later software these relays are always mapped to zones 65  
to 128 at the RZDU. NOTE :- In F3200 V1.10 this was not the case. F3200 V1.10 mapped  
the module relays to zones in the range 1-64 and the first module relay mapped to the first  
free zone after the alarm zones.  
In F3200 V2.00 or later software, the first module relay always maps to zone 65 at the  
RZDU. i.e. at an RDU, a recall of zone 65 on the LCD will show the status of the first  
module relay in the F3200 panel and a recall of zone 1 on the LCD at an RDU will show the  
status of the first alarm zone in the F3200 panel. This numbering is not affected by the  
mapping of zones to LEDs at either the panel or at the RDU. e.g the first module relay in the  
F3200 panel could map to LED 1 in the panel and to LED 33 at the RDU but is still recalled  
onto the RDU LCD as zone 65.  
F3200 V2.07 and later software allows equations for relays 1 to 64 to be entered even if  
there is no physical relay installed at the FIP. The logic state calculated for the equation is  
sent as the alarm state for the corresponding zone 65 to 128 sent to the RDU.  
F3200 V2.00 and later software will also transmit the status of "zones" 129-192 to the RZDU  
if it has any output logic equations controlling a relay where the relay number is greater than  
64. An output logic equation controlling a relay with a relay number in the range 65 to 192 is  
actually controlling one of the 64 zone LEDs and is mapped to zones 129-192 for  
transmission to an RZDU. Refer to section 7.4 for further information.  
The RZDU menu (option 6 in the System Configuration menu) has two options as follows: 1  
Protocol Type; 2 RZDU config  
Protocol Type  
The two protocols available for communication between the F3200 FIP and RZDUs are:  
LCD - the newer Vigilant protocol with greater flexibility.  
Non-LCD - the older Vigilant protocol that may need to be used with some old version  
RZDUs, IO-NET or Colour Graphic software version.  
The default protocol is LCD. Non-LCD can be selected by pressing "ENTER". If LCD  
protocol is used, each RZDU may then be programmed as using either LCD-A or LCD-B.  
LCD-A is normally used but LCD-B may be used with some versions of RDU and will allow a  
bell test command to be initiated at an RDU. The selection of LCD-A or LCD-B must be  
done in both the panel and the RZDU. A mixture of LCD-A and LCD-B type RZDUs may be  
used on the same panel.  
RZDU config  
RZDUs 1-8 can be selected by use of the "NEXT" key. The cursor left and right keys are  
used to step through the items that can be programmed for each RZDU. The cursor up key  
is used to enable or disable each rzdu and to select LCD-A or LCD-B.  
Issue 2.7  
5 July 2001  
Page 7-35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Programming System Configuration  
Document No: LT0122  
RDU (CONTINUED)  
The RZDU MCP can be mapped to a FIP zone by entering a zone number.  
Transmitting Zone Names to an RDU  
F3200 V2.03 software or later and RDU V2.01 software or later allow the downloading of  
zone and module relay names to connected RDUs using the comms link to the RDU. This is  
initiated from the SET menu described in Section 6.2.1. A password is required to initiate  
this command.  
To save the zone names at an RDU, it must have its database write protect link in the write  
enable position.  
After the command is initiated the FIP will send up to 8 zone names to the RDUs every 2  
seconds. The current zone number being sent is displayed on the LCD. The CLEAR key  
may be used to terminate the process at any time. The FIP will send the names of up to 64  
alarm zones and 64 module relays.  
The F3200 FIP (all software versions) will also send the name of a zone to an RDU  
whenever an FFCIF alarm is generated for that zone. If programmed to, the RDU will save  
the zone name received with an FFCIF alarm event into its database.  
Some RDUs support software write protection of their database, which allows them to have  
their database write protect link permanently left in the write enable position and thus receive  
the new zone names from the F3200.  
Page 7-36  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
CHAPTER 8  
INSTALLATION & WIRING  
Issue 2.7  
5 July 2001  
Page 8-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.1  
INSTALLATION  
8.1.1  
CABINET INSTALLATION  
The location of the F3200 FIP is chosen by the Fire Authority and building owner (or owner’s  
representative) in accordance with the Australian Standard AS1670.1.  
If the cardframe needs to be made removable to allow fitting/removing  
of large batteries, this should be done prior to cabinet installation. (Refer to Section  
8.1.2).  
The cabinet is normally fixed to a wall with four 6 mm screws or bolts. The drilling details are  
shown in Fig 8.1.1.  
The following conditions are required:  
1.  
2.  
3.  
4.  
Dry Area, moderate ambient temperature, 45°C absolute maximum.  
Not exposed to direct sunlight.  
Not subject to outdoor conditions without suitable protection.  
The LCD should be at average eye level and must not be higher than1850 mm or  
lower than 750 mm above floor level (see Fig 8.1.1).  
5.  
6.  
Clear access and viewing for Firefighters and operators.  
At least 1 metre free space should be provided in front of and on sides of the FIP for  
installation and maintenance.  
7.  
8.  
Must not be installed in hazardous areas as defined in AS3000.  
If recessed into a wall:  
i.  
Allow for the door to open at least 145°.  
ii.  
Prevent water entering the cabinet - seal unused knockouts and any top cable  
entries. Preferably use bottom cable entry, with cables going down 100 mm  
below cabinet before rising.  
It should not be necessary to drill within the cabinet, but if drilling or filing is  
required, remove the PCBs first. Clean out all swarf before replacing the PCBs.  
Use antistatic precautions when handling the PCBs.  
WARNING  
The F3200 is a Class A product. In a domestic environment it may cause radio  
interference in which case the user may be required to take adequate measures.  
Page 8-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
430 (8U Cabinet)  
415 (15U Cabinet)  
<───────────────────────────────>│  
┌─────────────────────────────────────────┐ ───  
102 (8U Cab)  
150 (15U Cab)  
───────────────│── o ─────────────────────────────── o ──│────  
o/6.0  
/o6.0│  
280 8U  
CABINET  
450 15U  
CABINET  
o ─────────────────────────────── o ──│────  
o/6.0  
/o6.0  
1750 (MAX)  
1220 (MIN)  
└─────────────────────────────────────────┘  
ALL DIMENSIONS IN MILLIMETRES  
FINISHED FLOOR LEVEL  
▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄▄  
/ / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / / /  
FIG 8.1.1  
FIP CABINET MOUNTING DETAILS  
Issue 2.7  
5 July 2001  
Page 8-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.1.2  
CARDFRAME INSTALLATION  
A KT0072 Cardframe upgrade kit can be fitted to a 15U F3200 to allow it to take more than  
three 8 way modules. In older versions, the cardframe mounts directly to the rear of the  
cabinet. In newer versions, the cardframe is fitted to a gear plate that may be removed when  
the cabinet is mounted to the wall.  
1.  
If the system does not require large batteries (refer to Section 4.3.4) it may be  
fitted as follows, using a pop rivet gun and M4 nut driver. With FIP power not  
connected, batteries not fitted.  
a.  
For an older cabinet that is removed from the wall:  
1.  
2.  
3.  
Remove all 8 way modules.  
Remove the 3 sets of PCB standoffs on the left side rear of the cabinet.  
Remove the M4 nuts, washers and PCB spacers from the 3 M4 studs on the  
left side of the cabinet.  
4.  
5.  
Fit the Cardframe over the studs with the M3 bushes on the right hand side.  
Refit the 3 PCB spacers, washers and nuts on the inside (do not yet fully  
tighten).  
6.  
7.  
From the cabinet rear, with the Cardframe firmly against the cabinet, insert  
the 3 pop rivets provided into the holes in the Cardframe, and rivet.  
Tighten the M4 nuts on the studs.  
b.  
c.  
2.  
If the cabinet is mounted to the wall the procedure is the same as above except:  
In step 2, the standoffs need to be cut off.  
In step 6, the rivets need to be inserted from the front.  
For a newer cabinet with a gear plate, the procedure is similar except that the gear  
plate is to be removed and the cardframe fitted to it.  
If a system requires the Cardframe to be removable to allow the  
fitting/removing of larger batteries, then the procedure is similar to that described  
above, but, instead of pop rivets, M4 screws should be used as follows:  
1.  
2.  
Use three M4 x 10 or M4 x 12 screws, with nuts, and shakeproof washers.  
Fit the screws with the heads outside the cabinet rear, washers and nuts  
inside the Cardframe.  
3.  
Put some Locktite (or equivalent power glue) under the heads of the screws  
(but not on the threads).  
4.  
5.  
Tighten the nuts on the screws initially holding the heads of screws.  
Subsequent removal of the nuts (after the Locktite has dried) should be  
possible without removing the cabinet from the wall.  
Page 8-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
8.1.3  
MODULE INSTALLATION  
The 8 Zone Modules and any 8 Relay Modules are fitted in order, from top to bottom. The  
FRCs fit under each PCB, from BUS OUT of the top one to Bus IN of the next one (see Fig  
8.1.2).  
Observe the following:  
(a)  
When mounting to the cabinet the M3 mounting screw per module should be  
tightened firmly to earth the module.  
(b)  
Modules and FRCs need to be fitted one at a time in the Cardframe. It is easier to  
start from the bottom module and work up.  
(c)  
(d)  
Care should be taken not to scrape an FRC against the bottom of the PCB above it.  
There are redundant slots in the Cardframe to allow for either 6 module even spacing  
or 8 module even spacing. Choose the correct slots.  
(e)  
On the Cardframe finger tighten the single M3 screw firmly into the notch in each  
PCB as this earths the module.  
FIG 8.1.2  
MODULE CONNECTION WITHIN A CARDFRAME  
Issue 2.7  
5 July 2001  
Page 8-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.1.4  
LED DISPLAY INSTALLATION  
When LED Displays are required, the 7U inner door (ME0060) is fitted to the standard  
cabinet directly below the 4U Operator Display with the M6 screws, washers and cage nuts  
provided. The hinge is on the right hand side. Click the cage nuts in from the inside. (7U  
doors cannot be fitted to a small cabinet).  
The flat M6 washers have a sharp edge and a rounded edge. Fit washers to the screws with  
the rounded edge facing the metalwork (to avoid damaging the paint).  
The Display Bds mount to the inner door on the standoffs supplied. (FZ3031 for LH position,  
FP0475 for others, both include the PCB, standoffs, FRC, power leads, diffuser and label  
master).  
Fit the FRCs and Minijump link as shown in Fig 8.1.3.  
The LED Display power leads from the MAF/PSU must always be fitted.  
8.1.5  
ZONE LABELLING  
Zone labelling for the LED Displays can be done simply on a typewriter or word processor.  
Note: For a typewriter use a photocopy of the label supplied with the Display Bd.  
The type format is:  
(a)  
(b)  
(c)  
(d)  
6 lines per inch.  
20 characters at 10 CPI or 24 characters at 12 CPI.  
2 lines per zone window.  
1 line between each zone window.  
To install the zone naming label:  
(a)  
Cut the typed label around the border, or cut the word processor sheet to 3mm to the  
left of the text then 60mm wide and 220mm long.  
(b)  
(c)  
(d)  
(e)  
Loosen the 4 Phillips-Head screws holding the display window.  
Align zone text with windows.  
Tape top and bottom of zone label.  
Align clear, matt finish, light diffuser with the 3 columns of LED holes (next to the  
label) with matt side in. Tape in place.  
(f)  
Tape blank sheets to unused zone window(s).  
Replace display window and fasten the 4 screws.  
(g)  
Page 8-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
════════════════╗  
╔══════════╗  
╔══════════╗ ╔══════════╗  
J13 ║  
┌┐ ║ LM0092  
CONTROLLER │├──╨────┐  
│├──╥──┐ │FRC ║  
└┘  
│ │  
│ │  
ZONES  
║ ─ ─ ─ ║ ZONES  
ZONES  
════════════════╝ │ │  
48 TO 64 ║  
║ 17 TO 32 ║ ║ 1 TO 16  
│ │  
│ │  
EXT+  
RED  
EXT+  
EXT  
RED┌───┼─┼────╫─oo──────╫───────╫─oo──────╫──╫─o  
LK1 ║  
│ ┌─┼─┼────╫─oo──────╫───────╫─oo──────╫──╫─o FITTED ║  
│ │ │ │  
═════════════╗ │ │ │ │  
║ │ │ │ │  
-
BLACK ║  
-
J1 J2  
╚═╤═╤══╤═╤═╝  
J1 J2  
╚═╤═╤══╤═╤═╝ ╚═╤═╤══════╝  
J1 J2  
J15 ║ │ │ │ └──────┘ │ │ └──── ─ ────┘ │ │ └──────┘ │  
LED  
+o──╫─┘ │ └──────────┘ └────── ─ ──────┘ └──────────┘  
DISPLAY -o──╫───┘  
DISPLAY FRC  
BLACK  
The order of the Display Boards is as viewed  
from the rear (i.e. inside).  
MAF/PSU  
═════════════╝  
FIG 8.1.3  
DISPLAY BOARD CONNECTION  
Note that a special loom (LM0092) is required to connect the first Display Board to the  
Controller Board. This is included in the F3200 LED Display Kit (FZ3031).  
For an NDU in New Zealand mode, if a NZ Display Extender board is fitted then it is added  
to the end of the display board chain after the last 16 zone display board (if any) and link Lk1  
on the last 16 zone display board must be NOT fitted. The NZ Display Extender does not  
need a link fitted to it, its presence indicates to the NDU that it is the last board in the chain.  
When programming the number of Display Bd, the Display Extender is not counted, but is  
individually programmed as fitted/not fitted.  
The Unprotected Termination board, PA0483, connects to the NZ Display Extender via FRC.  
The NZ specific wiring connects to this Termination board.  
Issue 2.7  
5 July 2001  
Page 8-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.2  
FIELD WIRING  
8.2.1  
GENERAL  
Cabling should comply with all the points in AS1670.1, Section 8.17. Note the requirements  
for segregation and identification.  
The cabling should, in general, be of not less than 0.75mm² cross sectional area, insulated  
and have red PVC sheathing. Joins should only occur in enclosed terminal boxes, and it is  
important that all terminations be good. I.e.  
no bare wire protruding from the terminal;  
no insulation inside the clamp part of the terminal;  
wire not cut or "nicked" during stripping;  
wire not soldered;  
wire not "doubled back" in the demountable terminals with leaf type strain relief  
clamps;  
all terminals firmly tightened;  
neat service loop;  
goose neck where servicing requires cable movement;  
coil of spare cable in wall/ceiling to allow for mistake/alteration.  
Note that it is best to carry out parts of the initial survey during installation, in particular,  
resistance and insulation testing.  
W A R N I N G  
Apart from the Mains supply to the FIP, only ELV cabling should enter the cabinet.  
FIG 8.2.1  
SCREW TERMINAL CABLE CONNECTION  
Page 8-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
FIG 8.2.2  
GOOSENECK CABLING  
8.2.2  
MAINS WIRING  
The mains (240Vac) supply must be connected in accordance with AS1670.1 and AS3000  
regulations.  
Ensure the mains cables to the FIP are isolated at the Distribution Board  
before connecting to the FIP.  
The mains cable connects to the 3 way terminal block mounted to the cabinet rear behind  
the mains cover.  
(a)  
(b)  
Remove the mains cover with a Pozi screw-driver.  
Shape the mains cable to fit through the grommet in the slot in the top of the cover,  
cut to length and strip only 20mm of the PVC cable sheath.  
(c)  
Connect the wires:  
blue (black) to N  
brown (red) to A  
green/yellow (green) to E  
Take care when stripping not to "nick" wires.  
Cable tie the cable to the cabinet.  
Refit the mains cover .  
(d)  
(e)  
Issue 2.7  
5 July 2001  
Page 8-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.3  
AZC WIRING  
Detectors must be installed and wired as per AS1670.1. Observe the requirements for  
conductor type and size.  
Connection to the particular MCPs, detectors or bases must be as specified by the  
manufacturer. Similarly for remote LED connection.  
AZCs must be wired as per Fig 8.3.1 with "In" of the first detector connected to the 8ZM, and  
the EOLR to the "out" of the furthest detector.  
Examples of illegal wiring are shown in Fig 8.3.3.  
┌─────────────┐  
8ZM  
┌──────┐ ┌──────┐  
┌──────┐  
│├─┤  
┌────┼o+ +o┼──┼o+ +o┼── ─ ─ ─ ─ ─┼o+ +o┼──────────┼───┤│O+  
┌┴┐  
EOL│ │  
└┬┘  
│├─┤ CCTn │  
OUT IN│ │OUT IN│  
OUT IN│  
┌────┼───┤│O-  
│├─┤  
││O│  
└────┼o- -o┼──┼o- -o┼── ─ ─ ─ ─ ─┼o- -o┼─────┘  
└──────┘ └──────┘ └──────┘  
└─────────────┘  
FIG 8.3.1  
CORRECT AZC DETECTOR WIRING  
The Tyco SU0600 MCP may be used on a circuit that has detectors on it, so that activation  
of the MCP does not reset the indication on any already activated detector. Wiring of the  
SU0600 is shown in Fig 8.3.2. The zone must be programmed with B3 = Instant Alarm.  
SU0600  
FIG 8.3.2  
TYCO SU0600 CONNECTION  
Page 8-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
┌─┐  
E├───┼o+ +o┼──┼o+ +o┼── ─ ─ ─ ─ ─┼o+ +o┼────_──────────┤O+  
O│ │OUT IN│ │OUT IN│ │OUT IN│ ├─┤ AZC  
L├───┼o- -o┼──┼o- -o┼── ─ ─ ─ ─ ─┼o- -o┼────┼──_───────┤O-  
┌──────┐ ┌──────┐  
┌──────┐  
├─┤  
└─┘  
└──────┘ └──────┘  
└──────┘  
├─┤  
┌─┐  
┌──────┐ ┌──────┐  
┌──────┐  
X X  
E├───┼o+ +o┼──┼o+ +o┼── ─ ─ ─ ─ ─┼o+ +o┼────┘ │ X X  
O│ │OUT IN│ │OUT IN│ │OUT IN│  
L├───┼o- -o┼──┼o- -o┼── ─ ─ ─ ─ ─┼o- -o┼───────┘ X X  
X
└─┘  
└──────┘ └──────┘  
└──────┘  
X X  
┌─┐  
┌──────┐ ┌──────┐  
┌──────┐  
├─┤  
E├───┼o+ +o┼──┼o+ +o┼──────_─────┼o+ +o┼───────────────┤O+  
O│ │OUT IN│ │OUT IN│ │OUT IN│ ├─┤ AZC  
L├───┼o- -o┼──┼o- -o┼──────┼──_──┼o- -o┼───────────────┤O-  
└─┘  
└──────┘ └──────┘  
└──────┘  
├─┤  
┌──────┐  
X X  
o+ +o┼────┘ │ X X  
OUT IN│  
o- -o┼───────┘ X X  
X
└──────┘  
X X  
┌─┐  
┌──────┐  
┌──────┐  
┌──────┐  
├─┤  
E├───┼o+ +o┼────_─────┼o+ +o┼────┼o+ +o┼───────────────┤O+  
O│ │OUT IN│ │OUT IN│ │OUT IN│ ├─┤ AZC  
L├───┼o- -o┼────┼──_──┼o- -o┼────┼o- -o┼───────────────┤O-  
└─┘  
└──────┘  
└──────┘  
└──────┘  
├─┤  
┌─┐  
┌──────┐  
X X  
E├───┼o+ +o┼────┘ │ X X  
O│ │OUT IN│  
L├───┼o- -o┼───────┘ X X  
└─┘ └──────┘ X X  
X
┌──────┐ ┌─┐ ┌──────┐  
o+ +o┼─┤E├──┼o+ +o┼────┼o+ +o┼───┼o+ +o┼──────────────┤O+  
OUT IN│ │O│ │OUT IN│ │OUT IN│ │OUT IN│ ├─┤ CCT  
o- -o┼─┤L├──┼o- -o┼────┼o- -o┼───┼o- -o┼──────────────┤O-  
┌──────┐  
┌──────┐  
├─┤  
└──────┘ └─┘ └──────┘  
└──────┘  
└──────┘  
├─┤  
X X  
X X  
X
X X  
X X  
FIG 8.3.3  
EXAMPLES OF INCORRECT AZC WIRING  
Issue 2.7  
5 July 2001  
Page 8-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.4  
MAF ANCILLARY RELAY WIRING  
The original (AS1603.4) F3200 has a single Warning System output and Isolate Switch,  
namely the Anc3/Bells relay, configured as Bells +/-, and the “Bells Isolate” key.  
It is now typical for FIPs to control two outputs, i.e. a single, External Bell, and a separate  
building Warning System which produces tones to AS2220 (as specified in AS4428.1).  
The MAF module has 3 Ancillary Relays. Typically, Anc 1 is used for door holders, air-  
conditioning shutdown etc; Anc 2 is used for the External Bell; and Anc 3/Bells is used for  
the Warning System. Wiring of the External Bell should be as per Fig 8.4.2 using Anc 2. The  
Warning System is covered in Section 8.5. Anc 1 and Anc 2 each have 1 set of voltage free  
contacts available on screw terminals, and a second set to which the screw terminals are not  
fitted as standard. Where supervision of wiring is required, the supervision (SUP) input is  
used as shown in the following figures.  
Door Holder Wiring  
Door holders are typically powered through normally closed contacts from the non-battery  
backed supply (+VNBF). As door holders are inductive, a suppression diode should be fitted  
between 0V and the door holder positive line.  
Where door holders have individual manual release buttons, suppression should be fitted at  
each device.  
Observe polarity, the cathode of the suppression diode is connected to the  
positive line.  
Where supervision is required, the recommended connection is as shown in Fig 8.4.1 A or B  
with a return from the furthest door holder. The alternative shown in Fig 8.4.1 A does not  
supervise the loop.  
The 24V relay used at the end of the loop in Fig 8.4.1 B only needs to switch low current.  
"Door Holder" mode supervision "looks for" the presence of voltage when the ancillary relay  
is de-energised.  
Plant Relay/Solenoid Wiring  
Where a plant relay is to be energised on Ancillary Relay operation it would typically be  
powered through normally open contacts from a battery-backed supply.  
If wiring supervision is required, it is connected as shown in Fig 8.4.2. "Load" mode  
supervision looks for a resistance to 0V when the ancillary relay is de-energised. For a very  
low resistance load (ref Specifications Section 3.4.2) a series diode must be fitted as shown.  
Heavy Load Wiring  
If a load greater than 2A resistive (1A dc inductive) needs to be controlled by F3200 then this  
can be achieved with the addition of a 24V Bell Monitor Board (PA0494). This can switch up  
to 5A dc (resistive) and supervises the load wiring for open and short circuit faults.  
Further details for the Bell Monitor Board are contained in LT0190. A representative wiring  
diagram is shown in Figure 8.4.3. If the load exceeds 2A dc then the power connection must  
be taken off +VBF2 or directly off the battery terminals via a suitable fuse (but not the +VBF1  
terminal). The fuse and wiring are supervised by the Bell Monitor Board, as it will generate a  
fault if power to it fails.  
Page 8-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
W A R N I N G  
Apart from the mains supply to the FIP only ELV wiring may enter the cabinet.  
Relays must not be used to directly switch medium or high voltage.  
+VNBF o─────┐  
┌─  
SUPERVISION RETURN  
| SUP o─────┼─────────┬───────────────────────────────────────┐  
|
ANCIL| NC  
1 |  
o─────┘  
<- ALTERNATIVE  
| COM o───────┬───────┴───┬───────────┬───────────┬───────────┤  
└─  
╒╧╕  
│ │1N4004  
└┬┘  
┌┴┐  
└┬┘  
┌┴┐  
└┬┘  
┌┴┐  
└┬┘  
┌┴┐  
└┬┘  
0V  
o───────┴───────────┴───────────┴───────────┴───────────┘  
SUPPRESSION  
DIODE  
DOOR HOLDERS  
A.  
WITH SUPERVISION OF LOOP POSITIVE WIRING ONLY  
+VNBF o─────┐  
┌─  
SUPERVISION RETURN  
| SUP o─────┼───────────────────────────────────────────┐  
|
ANCIL| NC  
o─────┘  
1 |  
| COM o───────┬───────┬───────┬───────┬─────┬─────┬───┐ │  
└─  
╒╧╕  
*│ │  
└┬┘  
┌┴┐  
└┬┘ *│ │  
│ │  
╒╧╕ ┌─┴─┐ o NO  
│ │ /  
└┬┘ └─┬─┘ o COM  
└─┘  
+24V RELAY  
┌┴┐  
└┬┘  
┌┴┐  
└┬┘  
0V  
o───────┴───────┴───────┴───────┴─────┴─────┘  
* SUPPRESSION DOOR HOLDERS  
DIODE  
B.  
WITH SUPERVISION OF LOOP POSITIVE AND NEGATIVE WIRING  
FIG 8.4.1  
EXAMPLE OF DOOR HOLDER WIRING WITH SUPERVISION  
Issue 2.7  
5 July 2001  
Page 8-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
+VBF1 o─────┐  
┌─  
| SUP o──┐  
|
ANCIL| NC  
1A |  
o──┘  
| NO  
|
o─────┘  
LOAD  
(SEE NOTE)  
| COM o───────────────────────────────────────────┬───────────┐  
└─  
┌┴┐  
└┬┘  
╒╧╕  
│ │  
└┬┘  
0V  
o───────────────────────────────────────────┴───────────┘  
SUPPRESSION  
DIODE  
Note: For a load of less than 400 Ohms a diode of suitable current rating must be added in  
series with the load at the load as shown below.  
──────┬───┐  
┌─┴─┐╒╧╕  
──────┐  
┌┴┐  
LOAD│  
└─┬─┘└┬┘  
├───┘  
┌┴┐  
││ │DIODE  
│ │DIODE  
╘╤╛  
├───┐  
OR  
┌─┴─┐╒╧╕  
│ │DIODE  
╘╤╛  
LOAD│  
││ │DIODE  
└─┬─┘└┬┘  
0V ──────┘  
0V ─────┴───┘  
FIG 8.4.2  
EXAMPLE OF PLANT RELAY WIRING WITH SUPERVISION  
VBF  
NO  
Bell Monitor Rev 3  
EOLR  
EOLR  
Ancil  
Relay  
C
Evac  
Evac+  
+V  
NC  
SUP  
0V  
Ext Def-  
Evac-  
0V  
Up to 3 branches of  
Load.  
FIGURE 8.4.3  
EXAMPLE OF SUPERVISING MULTIPLE BRANCHES OF MULTIPLE LOADS  
Page 8-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
8.5  
WARNING SYSTEM WIRING  
The typical configuration allocates the Ancil 3/Bells relay to drive the Warning System, and  
has links Lk2-4 fitted so that a switched 24V output is available at the +/- terminals. The  
supervision allows for up to 3 branches of wiring, with each requiring its own end of line  
resistor (EOLR). The value of the EOLR varies with the number of branches such that the  
combined total is always 3K3. The EOLR must be fitted at the end of each branch.  
Branches  
EOLR  
3k3  
6k8  
1
2
3
10k  
The Ancil 3/Bells output can be used to directly control alerting devices such as sounders  
(that generate tones to AS2220), AVIs, strobes etc. If each device does not have an internal  
series diode then a series diode must be fitted at each device. The diode must be rated to  
carry the current of the device. Fig 8.5.1 shows a dual branch system with diodes fitted to  
each device.  
Note the Vigilant AVI requires an external series diode to be fitted at each device. Multiple  
AVIs cannot presently be synchronised because the sync line carries the signal and is not  
supervised (a revision of this is planned.) Refer to Fig 8.5.1. The AVIs should be used with  
only two wires (+24V and EVAC-, or +24V and ALERT-), which is 3 Wire mode, but may  
have to be used in 2-wire mode with the +ve lead connected to ALERT- (EVAC+) and the  
–ve to EVAC- to get the required selection (e.g. Evac tone, top and bottom lamps both on).  
The Bells +/- output is limited to 2A dc resistive max. (Note that loads such as AVIs, Mini-  
Gens are considered resistive, whereas loads such as Solenoids and bells are inductive). A  
load of up to 5A dc resistive can be accommodated by use of a Bell Monitor Board and a  
separate, 6A dc, inline fuse. See Fig 8.5.6.  
A relay on an 8 Relay Module can also be used to control and supervise a circuit of  
evacuation devices. This is shown in Figure 8.5.3. Note that both poles of the relay are  
needed and the relay needs to be programmed so that it doesn’t supervise the wiring when it  
is activated (requires V2.09 or greater software). Although shown with only 1 circuit of  
evacuation wiring, it can actually support two branches, using a 27k EOL resistor on each.  
The Ancil 3/Bells relay can also be used to activate (and supervise) external tone generation  
devices such as Mini-Gen, T-GEN, Microvac and QE90 this is covered in following sections.  
MINI-GEN  
The Vigilant Mini-Gen has an internal diode and can be connected with up to three branches  
of speakers as per the instructions included with each unit. The 10k EOLR fitted to each  
speaker line must be rated at 2W and is supplied with the unit. Refer Fig 8.5.2. If less than 3  
branches are required, 10K 2W is still fitted to the end of each branch, with the other EOLRs  
being fitted to the +/- dc input terminals of the furthest Mini-Gen. Refer to the instructions for  
details.  
The Mini-Gen can be link selected to produce an Alert tone, an Evac tone, an automatic  
change from Alert to Evac after 1 minute, or an automatic change after 3 minutes. If desired,  
it can be configured to produce Evac, with a relay switching the tone to Alert. For this, a mini-  
jumper is fitted to link V, and the supplied 3 way connector fitted to link A/B with normally  
closed relay contacts shorting pin 2 to 3 (position B) to produce Alert. When the contacts  
open, the tone will change to Evac. Note that this applies only to Mini-Gen Rev 3 bds with  
V2.00 or greater software, and for internal wiring of the relay to the Mini-Gen (i.e. the Mini-  
Gen must be mounted within, or adjacent to the FIP.)  
Issue 2.7  
5 July 2001  
Page 8-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
T-GEN 50  
The Vigilant T-GEN 50 is permanently powered, requiring a supervised Alarm- signal from  
the FIP rather than switched power. The BELLS- terminal can be used for this unchanged.  
Alternatively, an open collector output (if the T-GEN is in or adjacent to the F3200 panel),  
another Ancil relay on the MAF, or an 8RM relay can be used as per Section 3.5 of the T-  
GEN Installation Instructions, LT0186. Note that a 3k3 EOLR should be used for the BELLS  
relay, and is also suitable for the other ANCIL and Module relays.  
MICROVAC AND QE90  
The Anc 3/Bells output can be used to activate a Microvac/QE90 and to supervise the link  
for a fault condition. A 24V relay (e.g. PA0730 General Purpose Relay Bd) is required to be  
mounted within the Microvac/QE90, and the wiring as shown in Fig 8.5.4.  
Alternatively the Anc 3/Bells output can be made voltage-free (remove Lks 2, 3, 4 on the  
MAF) and a spare 8 Zone Input can be used to supervise the Microvac/QE90. This  
arrangement, shown in Fig 8.5.5, does away with the relay, but requires a 4-wire connection  
and one spare input. The input should be programmed as a status-only zone and the fault  
state included in the logic equation to generate a Warning System fault. E.g. for zone 16  
WSF = Z16F.  
A high level link can be achieved between the F3200 and QE90 using the RZDU  
communications output. This is only suitable for when the F3200 and QE90 are co-located,  
as there is no duplication of the cable. Details for this wiring are contained in the QE90  
Installation and Commissioning Manual LT0088. In addition, the QE90 needs to be  
supervised for a fault condition. This can be done as shown in Fig 8.5.5 using a spare zone  
input or as in 8.5.4 using the Ancil 3/Bells output supervision.  
┌───────────┬───────────┬──────────┐  
┌┴┐  
│ │  
╘╤╛  
┌┴┐  
│ │  
╘╤╛  
┌─┴─┐  
┌─┴─┐  
┌┴┐  
│ │6k8  
└┬┘  
└─┬─┘  
└─┬─┘  
┌─────┴───────────┴──────────┘  
+ o────────────┬───────────┴─────┼─────┬───────────┬──────────┐  
┌┴┐  
│ │DIODE  
╘╤╛  
┌┴┐  
│ │  
╘╤╛  
┌┴┐  
│ │  
╘╤╛  
ANCIL 3  
BELLS  
┌─┴─┐  
┌─┴─┐  
┌─┴─┐  
┌┴┐  
│ │6k8  
└┬┘  
└─┬─┘  
└─┬─┘  
└─┬─┘  
- o────────────┴─────────────────┴─────┴───────────┴──────────┘  
FIG 8.5.1  
EXAMPLE OF WIRING WITH 2 SUPERVISED BRANCHES  
FOR DEVICES WITH NO INTERNAL SERIES DIODE  
Page 8-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
EOLR  
10k 2W  
FIRE PANEL  
DC IN  
LINE  
OUT  
Bells +  
Bells -  
+
+
-
+
-
S
24V  
Mini-Gen  
(PA0895)  
EOLR  
10k 2W  
F3200  
-
2-W LINK  
FITTED  
DC IN  
LINE  
OUT  
+
+
-
-
S
+
24V  
Mini-Gen  
(PA0895)  
EOLR  
10k 2W  
2-W LINK  
FITTED  
-
FIG 8.5.2  
EXAMPLE OF MULTIPLE MINI-GENS WITH 3 BRANCHES OF SPEAKERS  
+VBF  
NO  
Pole 2 NC  
C
Pole 1 NO  
4K7 EOLR  
(27k for dual  
branch)  
NC  
C
0V  
S
Note that this configuration requires that the relay confirmation (ACT) be disabled, which  
requires V2.09 or greater software.  
FIG 8.5.3  
EXAMPLE OF A SUPERVISED EVAC CCT USING 2 POLES OF AN 8RM RELAY  
Issue 2.7  
5 July 2001  
Page 8-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
+
F3200  
EOL  
NC NO  
C
ANCIL 3  
BELLS  
Normally -  
closed  
Fault relay  
*
-
FIP I/P  
(* = EOL for QE90/MICROVAC)  
MICROVAC OR QE90  
FIG 8.5.4  
WIRING ANCIL 3 TO MICROVAC/QE90  
NO  
MICROVAC  
QE90  
EOL  
MICROVAC/  
QE90  
FIP I/P  
ANCIL 3  
C
Remove  
Lk2, 3, 4  
on MAF  
+
Normally -  
closed  
Fault relay  
F3200  
AZC  
-
*
MICROVAC OR QE90  
(* = EOLR for F3200 AZC)  
FIG 8.5.5  
WIRING ANCIL 3 AND 8ZM INPUT TO MICROVAC/QE90  
Page 8-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
6Adc  
Batt -  
Fuse  
Bell Monitor Rev 3  
EOLR  
EOLR  
0V  
Evac+  
+V  
BELLS +  
BELLS -  
Evac  
0V  
Evac-  
Ext Def-  
Up to 3 branches of  
Load.  
2K7  
NC  
Anc 3  
NO  
Lk2  
Lk3  
Lk4  
Notes  
1.  
2.  
Wire an in-line fuse holder with 6A fuse from Batt+.  
The Bell Monitor must be Rev 3 or greater and is supplied with instructions, adhesive  
based stand-offs, and EOLRs.  
FIGURE 8.5.6  
USING BELL MONITOR BOARD ON ANCIL 3/BELLS RELAY  
Issue 2.7  
5 July 2001  
Page 8-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.6  
MODULE RELAY WIRING  
The 8 Relay Module relays each have one set of voltage free change-over contacts (ie one  
pole) accessible via screw terminals, to switch plant equipment. The second pole of each  
relay can be accessed by fitting a 3-way de-mountable connector block pair CN0488 and  
CN0206.  
There are two sets of four inter-connected, voltage free, looping terminals per module that  
can be used for looping supplies onto relays or loads.  
If the load switched is inductive e.g. a solenoid coil, a suppression diode must be fitted as  
shown in Fig 8.6.1.  
Supervision  
Supervision of the field wiring from the FIP to the load is shown in Fig 8.6.1. This only works  
for a single load, or multiple co-located loads wired in parallel (though for multiple co-located  
loads, the supervision will not detect a fault if one load becomes disconnected). It requires  
the load or an EOLR to be connected between the relay COM terminal and the FIP 0V, and  
the supervision link on the module to be fitted in the "S" position. If the COM output does not  
‘see’ a supply voltage or open circuit when the relay is activated, then the relay must be  
programmed to not supervise the load when actived (requires V2.09 or greater software).  
An example of supervising a circuit of multiple, separately located loads using 2 poles of one  
relay is shown in Fig 8.5.3.  
+VBF o─────┐  
┌─  
| NO  
o─────┘  
|
RLn | NC  
|
o
INDUCTIVE LOAD  
(SEE NOTE)  
| COM o───────────────────────────────────────────┬───────────┐  
└─  
┌─┴─┐  
╒╧╕  
│ │  
└┬┘  
S
───o o  
└─┬─┘  
0V o───────────────────────────────────────────┴───────────┘  
SUPPRESSION  
a.  
DIODE  
Note: For a load of less than 400 Ohms a diode of suitable current rating must be wired in  
series with the load at the load as shown in b. below.  
──────┬───┐  
INDUCTIVE┌─┴─┐╒╧╕  
──────┐  
┌┴┐  
LOAD│  
└─┬─┘└┬┘  
├───┘  
┌┴┐  
││ │DIODE  
│ │DIODE  
╘╤╛  
├───┐  
INDUCTIVE┌─┴─┐╒╧╕  
OR  
│ │DIODE  
╘╤╛  
0V ──────┘  
LOAD│  
└─┬─┘└┬┘  
0V ─────┴───┘  
││ │DIODE  
b.  
FIG 8.6.1  
EXAMPLES OF MODULE RELAY WIRING WITH SUPERVISION  
Page 8-20  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
8.6.1  
DUAL POLE – POLARITY REVERSAL OUTPUT  
Two relays; or 1 relay, an open collector output and an external 2 pole relay (e.g. PA0730);  
can be arranged to provide a supervised dual-polarity output suitable for driving dual strobes  
(Alert and Evacuate) or some visual warning devices (e.g. an AVI). The output is normally  
off (supervising voltage only), but can turn on with 24V in one polarity or in the other polarity.  
This is shown in Figure 8.6.2.  
If the dual pole relay is a second 8RM relay then the additional connector blocks need to be  
fitted (CN0260 and CN0488). Supervision is not enabled on this relay. The supervision on  
the other relay will detect any short circuit, but may not detect an open circuit with multiple  
sets of strobes/AVIs. This will depend on the type of strobe/AVI and the quantity remaining  
connected.  
The relay should be programmed to operate when either strobe is required, and the open  
collector output (or 2nd relay) is programmed to operate for Evacuate.  
Note that many strobes have a large capacitor inside them that causes a large in-rush  
current at power on. Therefore it may be necessary to add some series resistance if the  
cable length to the first set of strobes is not enough to limit the current. Add 10-20 ohms for  
a total strobe current of <100mA, 8-10 ohms for 100mA, and 2 x RR1007 NTCs in series for  
300mA-1A.  
+24V  
NC  
NO  
Relay 1  
C
Supervision Input  
Dual Pole Relay  
(PA0730 or 8RM)  
NO  
C
C
+
-
NC  
NO  
EVAC-  
AVI  
ALERT-  
Open  
Collector  
4k7  
Alert +  
Evac +  
NC  
Strobes  
0V  
FIGURE 8.6.2  
DUAL POLARITY OUTPUT FOR STROBES/AVI  
Issue 2.7  
5 July 2001  
Page 8-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.7  
OPEN COLLECTOR WIRING  
8.7.1  
LED MIMIC DISPLAYS  
It is expected that the most common use the open collector outputs will be to switch LEDs on  
"mimic" displays. These outputs are approved for field connection, so may be used to  
"drive" remote mimics. Typical connection is shown in Fig 8.7.1.  
8.7.2  
INTERFACING TO OTHER EQUIPMENT  
Where the open collector outputs are used to switch inputs to other systems, such as an  
Evacuation System or Plant Computer, there are two main options as follows:  
1.  
Direct Coupling  
The open collector output switches the equipment input to less than 1V (typically  
0.6V at 1mA). E.g. it may be used to switch a 5V CMOS input, or monitored 5V, 12V  
or 20V input. Refer to Fig 8.7.2.  
Note that for this to work, the 0V supply of the equipment must be connected to the  
0V supply of the FIP. This may not be desired, especially if the equipment has a  
power supply connection to earth.  
Note also that the open collector output has protection diodes to the FIP positive and  
negative supplies and should not connected to inputs that could be "pulled" to a  
voltage above or below these supplies, even with mains failed and battery voltage  
low.  
2.  
Isolated Coupling  
The open collector output can be used to switch a relay, or an optocoupler as shown  
in Fig 8.7.3. When the open collector is "on", the optocoupler transistor is also "on".  
┌───┐  
+VBF │  
├───────────────────────────────────────┬──────┬───────────────  
└───┘  
┌┴┐  
│ │  
└┬┘  
┌┴┐  
│ │ RESISTOR  
└┬┘ E.G. 4K7  
LED  
┌───┐  
OCn  
OCm  
├───────────────────────────────────────┘  
└───┘  
┌───┐  
├──────────────────────────────────────────────┘  
└───┘  
FIG 8.7.1  
EXAMPLE OF LED MIMIC WIRING  
Page 8-22  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
─┬─  
┌┴┐  
│ │  
└┬┘  
┌─┴─┐  
+┌─┴─┐  
OCn  
├───────────────────────────────┤  
├───┴──────────────────────  
└─┬─┘  
└─┬─┘  
Cct n  
EOLR  
┌─┴─┐  
┌─┴─┐  
0V  
├───────────────────────────────┤  
├───── 0V  
└─┬─┘  
└─┬─┘  
F3200  
OTHER EQUIPMENT  
FIG 8.7.2  
EXAMPLE OF INTERFACING TO OTHER EQUIPMENT, DIRECT COUPLING  
┌───┐  
+VBF  
├───────────────────────────┐  
OPTOCOUPLER  
└───┘  
┌┴┐  
RESISTOR │ │  
E.G. 4K7 └┬┘  
┌───┐  
┌─────┤  
+  
└───┘  
/ C  
Cct n  
>
┌───┐  
└┬──┘  
\ E  
├───────────────────────────┘  
┌───┐  
OCn  
└─────┤  
└─┬─┘  
OTHER EQUIPMENT  
-  
F3200  
FIG 8.7.3  
EXAMPLE OF INTERFACING TO OTHER EQUIPMENT, OPTICAL ISOLATION  
8.8  
ASE INSTALLATION AND WIRING  
A Vigilant ASE may be mounted in an F3200 panel or an NDU in a large cabinet. Two kits  
are available, namely KT0199 and KT0212. Both are 3U hinged front panels  
accommodating 1 or 2 ASE or V-Modem units (or a combination) respectively. The kits  
include mounting parts and fitting instructions.  
The ASE should be wired directly off the battery via its own fuse. Wiring of the ASE FP0740  
EOL unit is as per the ASE installation instructions. The red wires are wired across the MAF  
Alarm relay NC and C terminals, the yellow wires across the MAF Fault relay NC and C  
terminals, and the blue wires across the MAF Isolate relay NC and C terminals. No other  
connections to these relays are permitted when the ASE EOL unit is used.  
Locating the ASE remote from the panel has additional requirements under AS4428.1  
(Clause 2.10) that currently cannot be met.  
Issue 2.7  
5 July 2001  
Page 8-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.9  
RDU WIRING  
A FIP may drive up to 8 Remote Display Units (RDUs) that are programmed to send  
information back to the FIP. More "monitoring only" devices may be connected to the FIP  
RZDU Tx line. Some RDUs have their own power, but others require their power (24Vdc) to  
be supplied from the FIP or an approved PSU with battery backup.  
The RDUs are all connected in parallel on common Tx and Rx circuits. Star and Bus wiring  
connections are permitted as shown in Fig 8.8.1.  
NOTE: TX from the FIP goes to RX on ALL RDUs  
RX from the FIP goes to TX on ALL RDUs  
Fig 8.8.1 shows an example of interconnection between both MAF and Non-MAF configured  
RDU(s) and the FIP.  
NOTES:  
To maintain electrical isolation:  
(1)  
Lk1 on the MAF/PSU Board should be cut for RDUs with their own  
MAF/PSU module.  
(2)  
Non-MAF configured RDUs that are powered by a PSU other than the  
FIP must have Lk3 on the Remote Termination Board cut and Lk14 on  
the Controller in the “R” position.  
Cable Limitations  
The maximum distance to the furthest RDU is determined by the cable type used and the  
wiring arrangement.  
(1)  
The MAXIMUM line resistance loop (FIP TX out, 0V return must not be greater than  
150 Ω.  
(2)  
The MAXIMUM inter-wire capacitance at the FIP RZDU terminals MUST NOT  
exceed 100 nF. This must be the total of all cables used - not just the length to the  
furthest RDU. Typically this is 1km of TPS cabling.  
(3)  
The +V and 0V cables must be of sufficient size to avoid excessive voltage drops to  
RDUs when they are drawing maximum current (e.g. lamp test).  
Page 8-24  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Installation & Wiring  
FIP  
J11  
FP0558 MAF CONFIGURED RDU  
MAF Bd connector J11  
(Cut Lk1 on MAF/PSU)  
┌─┐  
┌─┐  
╔══════════════╡O+VBF2  
O+VBF2  
├─┤  
├─┤  
╔══════╡OTX  
╔══════════════════╡OTX  
RZDU  
COMMS  
├─┤  
├─┤  
╔═══╬═══════╬══════╡O0V  
╔═════════════╡O0V  
├─┤  
├─┤  
╔════╬══════╡ORX  
╔════════╡ORX  
└─┘  
└─┘  
█════╣════════════════════╝  
█═══╬══╬════╬═════════════════════════╝  
█══════════════════════════════╝  
FP0559  
NON-MAF CONFIGURED RDU  
FP0559  
NON-MAF CONFIGURED RDU  
EXTERNALLY POWERED  
(Cut Lk3 on Remote Term)  
Ext 24V PSU  
┌─┐+24V  
┌─┐  
──┐  
╚══╬════╬══════╡O│  
╚═══════════╡O+24V  
──┘  
├─┤0V  
O│  
├─┤0V  
├─┤  
╚══════════════╡O0V  
├─┤  
╚══════║════║══════╡O╞══════════════════════════════╡O0V  
──┐  
├─┤RX  
╚══════╡O╞══════════════════════════════╡ORX  
├─┤TX ├─┤  
├─┤  
RZDU  
COMMS  
╚═══════════╡O╞══════════════════════════════╡OTX  
└─┘ └─┘  
──┘  
Connectors J1 & 2, Remote Termination Bd  
FIG 8.8.1  
EXAMPLE OF RDU COMS WIRING  
Issue 2.7  
5 July 2001  
Page 8-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Installation & Wiring  
Document No: LT0122  
8.10  
SLIMLINE NDU (FP0714) WIRING  
MCP Connection  
A slimline NDU has the facility for connection of an MCP, but the MCP has to be mounted on  
the wall, immediately adjacent to the NDU.  
Connection is made to pins 3 & 4 of J5, the 4 way "Spare Input Connector" on the NDU  
Controller/Display Bd. The wiring to the MCP itself is detailed in the figure below. For an  
NDU in New Zealand mode refer to Chapter 12.  
FIG 8.9.1  
FP0714 NDU MCP CONNECTION  
8.11  
INSTALLATION OF 19" NDU (FP0733)  
The NDU is available as a 19" rack mount kit (FP0733). This must be installed as follows to  
meet the EMC requirements.  
Using the RS485 board as a template, drill 4 x 3.5mm holes and deburr. Scrape away any  
paint on the inside face and mount the metal standoffs using 4 M3 x 6 screws and  
shakeproof washers. Mount the RS485 board onto the standoffs using M3 x 6 screws and  
M3 crinkle washers.  
Mount the 4U inner door onto the 19" rack and earth to the cabinet using the earth lead  
supplied.  
Run the 10 way FRC from J7 (Network 1) on the Controller to J1 on the RS485 board,  
keeping it tight against the cabinet metalwork by using FRC clamps.  
Run +24V to the J5 terminals on the Controller, and the network cables to J3 on the RS485  
board. Connect any screen on the network cables to the 0V ISO terminal on the RS485  
board.  
Page 8-26  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
CHAPTER 9  
APPLICATIONS  
Issue 2.7  
5 July 2001  
Page 9-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
9.1  
AS1668 AIR CONDITIONING CONTROL  
9.1.1  
GENERAL  
The following features of F3200 allow it to be easily adapted to Air Conditioning Plant  
Control (referred to as AS1668 which is the relevant Australian Standard):  
19" Rack mounting cabinet with standard light grey blank panels available,  
including 9½U (plastic), 7U metal (hinged), 4U metal, 3U metal;  
Standard modules available which include a pcb module (3 options) with switch  
and LEDs, a connector block for field wiring, and labels (see Fig 9.1.1).  
Programable open collector output for driving LEDs (can enter logic equations for  
RUN, FAULT, STOPPED);  
Programmable relays for fan controls;  
Programmable time delays on duct sampling AZCs, with RAD and SAD options;  
Programmable AZCs for control inputs with two useable alarm states plus normal  
(plus faults) per AZC (i.e. logic equations can differentiate "manual" alarm  
(instant) from "detector" alarm (alarm);  
Programmable zones, allows non-latch, non-MAF (non-FFCIF), non-  
Bells/Ancillaries, status only (i.e. Fan Control Panel output relays can switch  
AZCs and the corresponding zones can be programmed as "non-fire" zones with  
optional levels of "transparency" within the Fire Alarm System e.g. Faults, Alarms  
can be included/not included in the "totals" display and the "recalls").  
The standard AS1668 pcb modules are held to the front panel (rear) by a nut on the  
threaded shaft of the rotary switch which is attached to the pcb. The LEDs mount in black  
plastic bushes and are soldered to the pcb (chrome bezel LEDs are available and can also  
be accommodated by the pcb). The adhesive label is black on clear, and the standard  
panels are light grey.  
The standard colours for RUN, FAULT and STOP (stopped) are red, yellow and green,  
respectively.  
Detail is shown in Product Bulletin PBG0015.  
FIG 9.1.1  
STANDARD AS1668 MODULE PANEL LAYOUT  
Page 9-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
FIG 9.1.2  
F3200 WITH TYPICAL AS1668 PANEL (10 UNITS)  
9.1.2  
CIRCUITS & ZONES  
FIP End Inputs  
The "off", "auto" and "on" inputs from the AS1668 Control Module can be connected to 0, 1  
or 2 AZCs as desired.  
One AZC per fan control is cheaper, but does not allow the LCD zone text to display "fan off"  
and "fan on", though the fan name can put in the zone text, and for options A and C  
following, the word "off" could be programmed as zone text so that "Manual" Alarm is "on"  
and "off" Alarm is "off".  
For option B, the text LCD would display "fault" for "off". Zone text would normally only be  
viewed by a zone status recall as AS1668 control inputs will (generally) be programmed as  
"status" zones (i.e. non-FFCIF).  
Figs 9.1.3 and 9.1.4 show both options. Option 1 requires a Zener diode or a resistor (e.g.  
560E) to give B2 voltage.  
Note that the option shown in Fig 9.1.3 B ("off" <-> "fault") corresponds to the standard  
AS1668 Module circuits 2, 3 & 4 (see drawings 1945-1-1/4 following) and so is the  
"preferred" option for configuring with standard hardware.  
Issue 2.7  
5 July 2001  
Page 9-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
CIRCUITS & ZONES (CONTINUED)  
The option in Fig 9.1.3 A could be implemented by "tacking" the 560E resistor (or 6V8  
Zener) onto the pcb. The 2 AZC option (Fig 9.1.4) could also be implemented by soldering  
the extra resistor and wires onto the unused contact of the rotary switch on the pcb.  
In all cases, "auto" is zone "normal".  
OFF  
┌──────────────o  
AUTO  
┌──┐  
╒╧╕  
┌─────o─────o──────────────────────┤ │+  
└──┘  
6V8│ │  
┌┴┐  
ON o  
AZC  
OR └┬┘ 2K7│ │  
560E│ └┬┘  
┌──┐  
└──────┴────────┴─────────────────────────┤ │-  
└──┘  
A.  
WITH A ROTARY SWITCH, "ON" IS B1 (INSTANT), "OFF" IS B2 (ALARM).  
OFF  
o
AUTO  
┌──┐  
┌────────────o─────o──────────────────────┤ │+  
┌┴┐  
2K7│ │  
└──┘  
ON o  
AZC  
└┬┘  
┌──┐  
└───────────────┴─────────────────────────┤ │-  
└──┘  
B.  
WITH A ROTARY SWITCH, "ON" IS B1 (INSTANT), "OFF" IS FAULT.  
OFF  
┌──────────────o  
AUTO  
┌──┐  
╒╧╕  
──────o───┬──────────────────┤ │+  
└──┘  
6V8│ │  
OR └┬┘  
560E│  
ON o  
┌┴┐  
│ │2K7  
└┬┘  
AZC  
┌──┐  
└───────────────┴──────┴──────────────────┤ │-  
└──┘  
C.  
WITH A CENTRE-OFF TOGGLE SWITCH, "ON" IS B1 (INSTANT), "OFF" IS B2  
(ALARM).  
FIG 9.1.3  
FAN CONTROL SWITCH WIRING WITH SINGLE AZC  
Page 9-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
CIRCUITS & ZONES (CONTINUED)  
For options A and C in Fig 9.1.3, configure circuit Alarm Text as "manual" and voltage band  
B1 as "Instant Alarm" (refer to table below).  
Voltage  
Band  
Default  
State  
Program  
State  
Fan  
Control  
B5  
B4  
B3  
B2  
B1  
Fault  
Normal  
Switch wiring open circuit  
"Auto"  
"Auto"  
"Off"  
Normal  
Alarm  
Inst Alarm  
"On"  
Configure the zone as non-latch, Status, non Anc1/Anc2/Bells.  
In output logic, "off" is ZnD, "On" is ZnM, (for AZC number n).  
For Option B in Fig 9.1.3, configuration is similar but in the output logic, "off" is ZnF and "on"  
is ZnA.  
For two AZC inputs:  
┌──┐  
┌───────┬─────────────────────────────┤ │+  
┌┴┐  
│ │2K7  
└┬┘  
└──┘  
AZC 1  
┌──┐  
OFF o  
AUTO o───o───┼─────────────────────────────┤ │-  
┌┴┐  
│ │2K7  
└──┘  
ON o  
└┬┘  
┌──┐  
└───────┴─────────────────────────────┤ │+  
└──┘  
AZC 2  
┌──┐  
-  
└──┘  
FIG 9.1.4  
FAN CONTROL WITH TWO AZCs & ROTARY (OR CENTRE-OFF) SWITCH  
Program B1 for both AZCs as "Instant Alarm", Alarm Text as "Manual".  
Zone 1  
Zone 2  
Both  
Alarm  
Alarm  
Normal  
"Fan Control Off"  
"Fan Control On"  
"Fan Control Auto"  
Configure both zones as non-latch, Status, non Anc1/Anc2/Bells.  
Fan Inputs  
The exact requirement depends on the particular fan motor controller, and the contacts  
available (e.g. "Run", "Fault"). Commonly "Run" is provided by an air flow switch (AFS), and  
is required to connect to an AZC so that it can become part of a logic equation (as per  
circuits 3 & 4 of standard module 1945-1-1/4 following).  
Issue 2.7  
5 July 2001  
Page 9-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
CIRCUITS & ZONES (CONTINUED)  
Where a "Fault" contact is available, along with "Run", both can be put onto a single AZC  
with the NO "Fault" contact shorting the AZC and voltage band B1 programmed as "Fault"  
(refer to Fig 9.1.5 A). Alternatively, the NC "Fault" contact can be put in series for open  
circuit Fault, and the NO "Run" contact can short the AZC, with B1 programmed as "Alarm"  
(ZnD). (Refer to Fig 9.1.5 B). Note that in A, Fault overrides Run, and in B, Run overrides  
Fault. The priority in B can be reversed, but not in A.  
The zone should be configured as non-latching.  
If a "run" contact is used to short a Zener across the AZC (i.e. run is B2 = Alarm) and the  
normal state of the fan is "run", then the zone mapping to MAF should be configured as  
"Status Only" so that the fan "Run" state is not shown in the "Totals" or "Alarm Recalls".  
┌──┐  
NC  
┌──┐  
┌───────┬────────┬───────┤ │+  
┌─────o───o──────┬───────┤ │+  
RUN o FAULT o  
└──┘  
FAULT  
o RUN  
/ NO  
o
RUN  
└──┘  
┌┴┐ NO /  
NO /  
┌┴┐  
│ │2K7  
└┬┘  
│ │2K7 o  
o
AZC  
AZC  
└┬┘  
╒╧╕6V8  
│ │OR  
└┬┘560E  
┌──┐  
┌──┐  
└───────┴────────┴───────┤ │-  
A. └──┘  
└────────────────┴───────┤ │-  
B.  
└──┘  
FIG 9.1.5  
EXAMPLE OF FAN RUN & FAULT WIRING TO AZC  
9.1.3  
RELAYS  
The exact number of relays per fan control and the logic required depends on the particular  
building and air conditioning plant.  
Typically, one relay is required per fan to switch an interposing relay in the fan control  
equipment, with a possible logic equation as follows:  
R5 = Z15D + Z15N.Z5A i.e. ("off") or ("auto" and duct alarm)  
(ie. the relay turns on to turn the fan off).  
Where:Relay 5 is the Fan Control relay for a normally running fan  
Zone 5 is the associated Air Duct Smoke circuit  
Zone 15 is the associated Fan Control switch circuit with ...  
Z15D (band B2) = "Fan Off"  
Z15M (band B1) = "Fan On"  
Z15N (bands B3, B4) = "Auto"  
Note that the zone range facility is useful in programming controls where selective,  
automatic switching is required. E.g. if zones 1-10 correspond to ducts in levels 1-10 of a  
building, and the logic requires Relay 5 to operate if Zone 5 is in alarm but zones 1-4 and 6-  
10 are not, the equation for R5 above would become:  
Page 9-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
CIRCUITS & ZONES (CONTINUED)  
R5 = Z15D + Z15N.Z5A.^ (Z1:4(1)A+Z6:10(1)A)  
Note also, that if the interposing relay (fan control input) is 24V at less than 100mA then an  
open collector (O/C) may be used as per circuit 1 of 1945-1-1/4 following.  
9.1.4  
LEDS  
The 3 LEDs may be: switched directly as per circuits 1 and 2 of 1945-1; driven off 3 open  
collector (O/C) outputs or driven off 2 O/Cs with a Zener diode as shown in Fig 9.1.6 and  
1945-1-3. Note that where the FIP has a number of detector circuits, the open collector  
outputs associated with these AZCs may be used for driving the AS1668 LEDs and so it  
doesn't matter if the AS1668 panel requires more open collectors than circuits.  
+VBF  
─┬─  
3K3  
┌──┐  
RUN ├───────>├────█████────────┤ │ OC1  
Red  
└──┘  
┌──┐  
3K3  
FAULT ├───────>├────█████────────┤ │ OC2  
Yellow  
└──┘  
┌──┐  
3K3  
STOP └───────>├────█████────────┤ │ OC3  
Green └──┘  
A.  
THREE OPEN COLLECTOR O/PS PER FAN (Ref 1945-1-4).  
+VBF  
─┬─  
3k3  
RUN  
┌──┐  
├────█████───┬───>├────────┤ │ OC1  
Red  
└──┘  
STOP Green  
╒╧╕  
│ │3V9 ZENER  
└┬┘  
─┴─  
3K3  
0V FAULT  
┌──┐  
└────█████───────>├────────┤ │ OC2  
Yellow └──┘  
B.  
TWO OPEN COLLECTOR O/PS PER FAN (Ref 1945-1-3).  
For other LEDs (eg. Chrome Bezel LEDs) a lower value (higher current) resistor may be  
required.  
FIG 9.1.6  
WIRING OF FAN CONTROL LEDS  
Issue 2.7  
5 July 2001  
Page 9-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
CIRCUITS & ZONES (CONTINUED)  
Note that the logic requested for the LEDs in Option B is as follows:  
LEDs  
OUTPUTS  
RUN  
off  
on  
x
FAULT  
off  
x
STOPPED  
OC1  
off  
on  
x
OC2  
off  
x
on  
off  
x
on  
on  
Where x = off or on (don't care).  
9.1.5  
AS1668 CONTROL MODULE & DRAWINGS  
The following drawings are of 4 typical configurations using the AS1688 Control Module,  
1945-1.  
Circuit 1 uses Module Type 1 (KT0111)  
Circuit 2 uses Module Type 2 (KT0112)  
Circuits 3 and 4 both use Module Type 3 (KT0113), with selective "snipping" out of  
components as required.  
1945-1-1, AS1668 CONTROL MODULE, CIRCUIT 1  
1945-1-2, AS1668 CONTROL MODULE, CIRCUIT 2  
1945-1-3, AS1668 CONTROL MODULE, CIRCUIT 3  
1945-1-4, AS1668 CONTROL MODULE, CIRCUIT 4  
Page 9-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TO OTHER AS1668  
TERMINAL BLOCKS  
+24V  
(RED)  
(RED)  
1
+24V (RED)  
1
LOAD (+)  
+24V  
TO OTHER AS1668  
+24V  
CONTROL/INDICATORS  
(RED)  
1
1
AFS  
AIR  
FLOW  
SWITCH  
CLOSE  
FOR  
STOPPED  
+24V  
AFS  
1
1
(GREEN)  
ON  
FOR  
RUN  
AFS  
C
A
B
LOAD  
(FAN)  
5V6  
BZX55  
1N4148  
1N4148  
LD3  
RED  
LD1  
GRN  
LD2  
YEL  
"RUN"  
"STOP"  
"FAULT"  
TO OTHER AS1668  
CONTROL/INDICATORS  
O/C = 0.1A MAX  
RELAY = 1A MAX  
0V  
(BLACK)  
F
E
3K3  
3K3  
0V  
L-  
ON  
1
1
0V (BLACK)  
(BROWN)  
1
1
1
(WHITE)  
1
0V  
LOAD (-)  
SW1  
O/C IN  
AUTO CONTROL  
AUTO  
OFF  
AS1668  
TERMINAL  
BLOCK  
PA0726  
1945-1-1  
FIRE  
SYSTEM  
I/O  
ON FOR RUN  
0V  
0V  
RELAY  
CONTACT  
OPEN COLLECTOR  
OUTPUT  
UNLESS OTHERWISE STATED:  
ALL RESISTANCE IN OHMS  
ALL RESISTORS 1/4W, 5%  
ALL CAPACITANCE IN FARADS  
22-Aug-1997  
18:17:43  
THIS DOCUMENT MUST NOT BE COPIED NOR THE CONTENTS PASSED ON TO  
ANY THIRD PARTY WITHOUT THE CONSENT OF THE COMPANY.  
CONFIDENTIAL:  
AS1668  
FIRE & EVACUATION SYSTEMS  
ISS/REV  
AMENDMENTS  
ECO  
DRN CHKD AUTH APVD DATE  
CONTROL MODULE (CCT 1)  
SYSTEM/CIRCUIT DIAGRAM  
1
ORIGINAL  
MINOR CORRECTIONS  
-
-
CJL  
CJL  
LSC  
CJL  
RAC  
RAC  
DSCP 27.4.95  
DSCP 27.7.95  
211 MACES ROAD, CHRISTCHURCH 8006, NZ  
P.O. BOX 19-545, CHRISTCHURCH 8030, NZ  
1.1  
SIZE  
DRAWING NUMBER  
SHEET NUMBER  
ISS/REV  
PART NUMBER  
A3  
1945-1-1  
1
1
1.1  
PA0726  
of  
Download from Www.Somanuals.com. All Manuals Search And Download.  
+24V SWITCHED  
LOAD (+)  
RLY (COM)  
1
(ORANGE)  
(ORANGE)  
1
SUPERVISED  
RELAY OUTPUT  
+24V SW  
1
1
1
1
RLY (NO)  
+24V  
5V6  
3K3  
BOTH  
COMPONENTS  
IN  
+24V  
+24V  
(RED)  
C
3K3  
POSITION B  
TO OTHER AS1668  
CONTROL/INDICATORS  
+24V  
(RED)  
LD1  
GRN  
LD3  
RED  
LD2  
YEL  
"STOP"  
"RUN"  
"FAULT"  
I
F
O
5V6  
BZX55  
1N4148  
1N4148  
LOAD  
(FAN)  
AFS  
AFS  
1
(GREEN)  
1
1
AIR  
FLOW  
SWITCH  
CLOSE  
FOR  
RUN  
0V  
AFS  
1A MAX  
1
OFF  
AUTO  
ON  
SW1  
I/P  
1
1
(BROWN)  
1
1
+
Q
REOL  
FIT AS  
REQUIRED  
AZC  
-
UNLESS OTHERWISE STATED:  
PA0727  
I/P COM  
(BLACK)  
1945-1-2  
ALL RESISTANCE IN OHMS  
ALL RESISTORS 1/4W, 5%  
ALL CAPACITANCE IN FARADS  
LOAD (-)  
1
0V (BLACK)  
(BLACK)  
1
0V  
FIRE  
SYSTEM  
I/O  
AS1668  
TERMINAL  
BLOCK  
TO OTHER AS1668  
CONTROL/INDICATORS  
TO OTHER AS1668  
TERMINAL BLOCKS  
0V  
0V  
(BLACK)  
(BLACK)  
22-Aug-1997  
18:17:08  
THIS DOCUMENT MUST NOT BE COPIED NOR THE CONTENTS PASSED ON TO  
ANY THIRD PARTY WITHOUT THE CONSENT OF THE COMPANY.  
CONFIDENTIAL:  
AS1668  
FIRE & EVACUATION SYSTEMS  
ISS/REV  
AMENDMENTS  
ECO  
DRN CHKD AUTH APVD DATE  
CONTROL MODULE (CCT 2)  
SYSTEM/CIRCUIT DIAGRAM  
1
ORIGINAL  
-
-
CJL  
CJL  
LSC  
CJL  
RAC  
RAC  
DSCP 27.4.95  
DSCP 27.7.95  
211 MACES ROAD, CHRISTCHURCH 8006, NZ  
P.O. BOX 19-545, CHRISTCHURCH 8030, NZ  
1.1  
MINOR CORRECTIONS  
SIZE  
DRAWING NUMBER  
SHEET NUMBER  
ISS/REV  
PART NUMBER  
A3  
1945-1-2  
1
1
1.1  
PA0727  
of  
Download from Www.Somanuals.com. All Manuals Search And Download.  
+24V SWITCHED  
RLY (COM)  
1
(ORANGE)  
(ORANGE)  
1
LOAD (+)  
SUPERVISED  
RELAY OUTPUT  
1
1
RLY (NO)  
+24V  
+24V  
+24V  
(RED)  
1
C
3K3  
B
3K3  
TO OTHER AS1668  
CONTROL/INDICATORS  
+24V  
(RED)  
LD3  
LD1  
LD2  
RED  
"RUN"  
GRN  
"STOP"  
YEL  
"FAULT"  
RUN O/C  
FAULT O/C  
0V  
1
1
(BLUE)  
1
1
1
OPEN COLLECTOR 1  
OPEN COLLECTOR 2  
I
5V6  
BZX55  
LOAD  
(FAN)  
(YELLOW)  
1A MAX  
OFF  
AUTO  
ON  
SW1  
I/P  
1
1
1
(BROWN)  
(BLACK)  
(VIOLET)  
1
1
+
Q
REOL  
FIT AS  
REQUIRED  
AZC1  
PA0728  
1945-1-3  
I/P COM  
-
AFS(+)  
1
+
AIR  
FLOW  
SWITCH  
REOL  
* FIT REOL IF  
AZC2  
UNLESS OTHERWISE STATED:  
*
AND AS REQUIRED  
1
1
(GREY)  
1
1
ALL RESISTANCE IN OHMS  
ALL RESISTORS 1/4W, 5%  
ALL CAPACITANCE IN FARADS  
-
AFS(-)  
(BLACK)  
LOAD (-)  
0V (BLACK)  
0V  
FIRE  
AS1668  
TERMINAL  
BLOCK  
PCB MODIFICATION INFORMATION:  
CUT OUT COMPONENT IN POSITION "A" (3K3)  
SYSTEM  
I/O  
CUT OUT COMPONENT IN POSITION "L" (0E LINK)  
TO OTHER AS1668  
CONTROL/INDICATORS  
TO OTHER AS1668  
TERMINAL BLOCKS  
0V  
0V  
(BLACK)  
ON PCB, ADD ’-3’ AFTER 1945-1 WITH INDELIBLE PEN.  
22-Aug-1997  
18:18:18  
THIS DOCUMENT MUST NOT BE COPIED NOR THE CONTENTS PASSED ON TO  
ANY THIRD PARTY WITHOUT THE CONSENT OF THE COMPANY.  
CONFIDENTIAL:  
AS1668  
FIRE & EVACUATION SYSTEMS  
ISS/REV  
AMENDMENTS  
ECO  
DRN CHKD AUTH APVD DATE  
CONTROL MODULE (CCT 3)  
SYSTEM/CIRCUIT DIAGRAM  
1
ORIGINAL  
-
-
CJL  
CJL  
LSC  
CJL  
RAC  
RAC  
DSCP 27.4.95  
DSCP 27.7.95  
211 MACES ROAD, CHRISTCHURCH 8006, NZ  
P.O. BOX 19-545, CHRISTCHURCH 8030, NZ  
1.1  
MINOR CORRECTIONS  
SIZE  
DRAWING NUMBER  
SHEET NUMBER  
ISS/REV  
PART NUMBER  
A3  
1945-1-3  
1
1
1.1  
PA0728  
of  
Download from Www.Somanuals.com. All Manuals Search And Download.  
+24V SWITCHED  
RLY (COM)  
1
(ORANGE)  
(ORANGE)  
1
LOAD (+)  
SUPERVISED  
RELAY OUTPUT  
1
1
RLY (NO)  
+24V  
+24V  
(RED)  
+124V  
C
3K3  
A
3K3  
B
3K3  
TO OTHER AS1668  
CONTROL/INDICATORS  
+24V  
(RED)  
LD3  
LD1  
LD2  
RED  
GRN  
YEL  
"RUN"  
"STOP"  
"FAULT"  
1
1
1
(BLUE)  
R1UN O/C  
OPEN COLLECTOR 1  
OPEN COLLECTOR 2  
OPEN COLLECTOR 3  
LOAD  
(FAN)  
FAULT O/C  
(YELLOW)  
(GREEN)  
1
1
STOP O/C  
1A MAX  
STOP  
AUTO  
RUN  
SW2  
I/P  
1
1
1
(BROWN)  
(BLACK)  
(VIOLET)  
1
1
+
Q
AZC1  
REOL  
FIT AS  
REQUIRED  
PA0728  
1945-1-3  
I/P COM  
-
1
AFS(+)  
+
UNLESS OTHERWISE STATED:  
AIR  
FLOW  
SWITCH  
REOL  
AZC2  
* FIT REOL IF  
AND AS REQUIRED  
ALL RESISTANCE IN OHMS  
ALL RESISTORS 1/4W, 5%  
ALL CAPACITANCE IN FARADS  
*
1
1
(GREY)  
1
1
-
AFS(-)  
2
(BLACK)  
0V (BLACK)  
LOAD (-)  
0V  
AS1668  
TERMINAL  
BLOCK  
FIRE  
SYSTEM  
I/O  
PCB MODIFICATION INFORMATION:  
CUT OUT COMPONENT IN POSITION "G" (0E LINK)  
CUT OUT COMPONENT IN POSITION "I" (5V6 ZENER)  
TO OTHER AS1668  
CONTROL/INDICATORS  
TO OTHER AS1668  
TERMINAL BLOCKS  
0V  
0V  
(BLACK)  
ON PCB, ADD ’-4’ AFTER 1945-1 WITH INDELIABLE PEN.  
22-Aug-1997  
18:18:38  
THIS DOCUMENT MUST NOT BE COPIED NOR THE CONTENTS PASSED ON TO  
ANY THIRD PARTY WITHOUT THE CONSENT OF THE COMPANY.  
CONFIDENTIAL:  
AS1668  
FIRE & EVACUATION SYSTEMS  
ISS/REV  
AMENDMENTS  
ECO  
DRN CHKD AUTH APVD DATE  
CONTROL MODULE (CCT 4)  
SYSTEM/CIRCUIT DIAGRAM  
1
ORIGINAL  
-
-
CJL  
CJL  
LSC  
CJL  
RAC  
RAC  
DSCP 27.4.95  
DSCP 27.7.95  
211 MACES ROAD, CHRISTCHURCH 8006, NZ  
P.O. BOX 19-545, CHRISTCHURCH 8030, NZ  
1.1  
MINOR CORRECTIONS  
SIZE  
DRAWING NUMBER  
SHEET NUMBER  
ISS/REV  
PART NUMBER  
A3  
1945-1-4  
1
1
1.1  
PA0728  
of  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
9.2  
GAS FLOOD  
9.2.1  
GENERAL  
The following features of the F3200 make it well suited to "Gas Flood" control:  
AZC Alarm Text for "pressure switch", "manual", can be used for the various inputs;  
Zones can be programmed as latch/non-latch, MAF/non-MAF as required, e.g. non-latch,  
non-MAF, for "Gas Inhibit" input;  
Zone range operand allows easy programming of "voting systems" on detector circuits  
e.g. 2 out of 3;  
Open collector O/Ps can be programmed to drive LEDs such as "Gas Initiated", "Gas  
Inhibited", etc;  
Programmable timers included as standard (0-250 sec);  
Programmable relays, with supervision option;  
Operation not fixed by hardware, as virtually any required logic equation for outputs  
(using AND, OR, NOT, XOR) can be entered;  
Fuse protected battery-backed supplies available via 2A fuse and 6A fuse;  
Standard hinged, screened 7U Gas Flood door available complete with LEDs, switches  
and looms for 1, 2, 3, 4 Gas Zones (Part Number ME0065 to ME0068 respectively);  
Standard non-hinged, screened 1U Panel as per above for 1 Gas Zone (Part Number  
ME0069);  
Standard Local Control Stations (LCSs) and AVI warning signs available. (LCS includes  
"Gas Start", "Gas Inhibit" switches, status LEDs). AVIs include AS2220 Alert and Evac  
tones and can be ordered with screens such as FIRE ALARM / DO NOT ENTER, etc.  
Note that the following implementation has, as standard, supervision of only the Gas release  
relay output wiring, and not of the Stage 1 and Stage 2 warning signs. By allocating extra  
relays (or using the second pole) and fitting diodes at each sign, the warning sign circuits  
could be supervised (refer Figures 8.5.3, 8.6.2, 9.2.5 and 9.2.6).  
9.2.2  
LOGIC & CONFIGURATION  
A commonly used logic diagram for a dual circuit Gas Flood Zone (i.e. protected area,  
sometimes called 'risk') is shown in Fig 9.2.1. This can be used with ME0065-69 and one or  
more Local Control Stations (FP0570) per protected area.  
The logic equations for it may be as follows.  
where:  
OC1 = Gas Initiated LED  
OC2 = Manual Activation LED (i.e. LCS Gas Start)  
OC3 = Gas Discharged LED  
(i.e. Timer Running)  
OC4 = System Inoperative (i.e. any isolate or fault in Gas Control System)  
OC5 = Gas Inhibited LED  
Zone 1 = Detector Cct 1  
Zone 2 = Detector Cct 2  
Zone 3 = Gas Start (LCS)  
Zone 4 = Gas Released (Pressure Switch)  
Zone 5 = Gas Inhibit (LCS)  
Zone 6 = Gas Isolated (i.e. Gas Isolate switch operated, see note 3)  
Zone 7 = Lock-off Valve (if required, see note 9)  
Issue 2.7  
5 July 2001  
Page 9-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
LOGIC & CONFIGURATION (CONTINUED)  
Relay 1 = Alert O/P (1st stage sign FIRE ALARM)  
Relay 2 = Evac O/P (2nd stage sign EVACUATE and DO NOT ENTER)  
Relay 3 = Gas Release Solenoid  
Relay 4 = System Inoperative sign  
Isolate = Guard Relay (see note 2)  
Timer  
T1 [S30:0] = V1  
30 Second time delay from "Gas Initiated" (second stage).  
Variables  
V1 = Z1A.Z2A.^Z5A + Z3A  
Open Collector LEDs  
OC1 = V1  
OC2 = Z3A  
OC3 = Z4A  
OC4 = Z5A + OC5 + Z7A + Z4:7(1)I + Z1:7(1)F + R3F +R1I+R2I +R4I (see notes 2,9)  
OC5 = Z6A+Z1:3(1)I + R3I + Guard Iso (if isolatable, see note 2)  
Relays  
R1 = Z1A + Z2A + Z3A + Z4A  
R2 = Z4A + V1  
R3 = T1  
R4 = OC4  
ISO (or Rn) = V1  
(Alert)  
(Evac)  
(Gas Release)  
(System Inoperative)  
(Guard) (see note 2)  
Configure Circuits  
AZC  
Circuit 1  
Circuit 2  
Gas Start  
Gas Released  
Gas Inhibit  
Gas Isolated  
Lock-off Valve  
Alarm Text  
Smoke (1)  
Smoke (1)  
MCP/Manual (4)  
FSW (3) or PSW (6)  
MCP/Manual (4)  
MCP/Manual (4)  
VMD/Valve (5)  
B1  
-
-
-
Alarm (2)  
-
If required (see note 3)  
If required (see note 9)  
(Circuits 1 and 2 use all default settings).  
Configure Zones  
Zone  
Latch MAF Anc1 Anc2 Bells  
Circuit 1  
Circuit 2  
-
-
-
-
-
-
-
-
-
-
Gas Start  
N ?  
-
N
N
N
-
-
N
N
N
-
-
N
N
N
-
-
N
N
N
-
-
N
(see note 10)  
Gas Released  
Gas Inhibit  
Gas Isolated  
Lock-off Valve  
N If required (see note 3)  
N If required (see note 9)  
(Zones 1-4 use all default settings. Zone 3 may be required to be non-latching. See note 10.)  
Page 9-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
LOGIC & CONFIGURATION (CONTINUED)  
Configure Relay Supervision  
Relay  
Enable  
Y
Latch MAF LED Isolate  
Test Sup.Act  
Gas Release  
-
-
-
-
-
-
By default, relays are isolatable and testable but this can be changed if desired.  
For all configuration, only items that have to be changed from default are shown.  
9.2.3  
NOTES  
1.  
The variable V1 is used to initiate the timer rather than OC1 because outputs  
(including OC) can be tested from the keypad. It is not desirable to have a "test"  
function initiating the timer which releases gas.  
2.  
The Guard relay is used to reduce the chances of accidental Gas Release (e.g. by  
someone performing a "Test " on the Gas Release Relay). (The test function may be  
inhibited, as may Isolate.) It uses a normally open set of contacts and is inserted  
between +VBF2 and the NO terminal of the Gas Release relay (R3). It is preferable  
to use an unused Brigade Relay (rated at 5A dc resistive) e.g. Isolate, if available  
(not Standby), else an ancillary relay, or a module relay (each rated at 2Adc resistive)  
on a separate 8RM to Gas Release. For multiple zones, a Module Relay "Guard"  
relay can be common for 2 Gas zones, or Brigade Relay "Guard" relay can be  
common to up to 5 Gas zones for 1A actuator loads. The common Guard relay  
should be programmed to operate off the OR of the variables. For example:  
ISO = V1 + V2 + V3 for a 3 Risk FIP which used ISO as the Guard relay.  
If a Module relay, Rn, is used as the Guard relay, then +RnI should be added to the  
equations for OC4 and OC5. (Similarly if an ancillary relay is used).  
Unused Brigade relays may also be used as an alternative to the module relays  
shown to switch the sounders where the load exceeds 2Adc.  
3.  
The Gas Isolated switch turns on the Gas Isolated LEDs on the 1U/7U Panel and  
LCSs directly, and causes a Gas Release relay supervision fault. The third set of  
contacts on the Gas Isolate switch is connected to AZC 6 (Gas Isolated) as shown on  
Drawing 1931-47,57 for ME0065,69 so that "Gas Isolated" status can show on the  
LCD, be logged, and repeat from the FIP to an RZDU or remote FIP via a network.  
The suitable EOLR is to be soldered across the switch contacts (yellow and black  
remit wires) at time of building.  
4.  
5.  
Snub (suppress) inductive loads (e.g. solenoids) with a suitably rated reverse diode.  
The Gas Isolate switch isolates both +ve and -ve supplies to the solenoid. When not  
isolated, however, the -ve supply is connected to 0V and only the positive supply is  
switched by the relay. This allows the relay supervision to check for resistance from  
the relay "common" contact to 0V.  
7.  
8.  
See Section 9.2.4 re use of actuators.  
Solenoids are typically less than 400 Ohms and require a diode (of sufficient rating)  
to be wired in series at the solenoid to allow supervision. If two solenoids are  
connected in parallel on one circuit the supervision will not detect one being  
disconnected. Where multiple release circuits are diode connected (+ve & -ve legs)  
onto a common solenoid, the supervision will detect shorts, but not all opens.  
Issue 2.7  
5 July 2001  
Page 9-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
NOTES (CONTINUED)  
9.  
If a Lock-off valve is not required, then Z7 is not required and can be left out of the  
equations. Note that AS4124.1 requires the Lock-off Valve to isolate both poles of the  
Gas Release solenoid / actuator. This is not done within the ME wiring and would  
therefore need to be done externally with microswitches (or a relay).  
10.  
The standard LCS Gas Start switch automatically turns on when the glass is broken.  
Some customers may require a different switch that can be turned off after the glass  
is broken, and hence cancel the timer and prevent gas release.  
9.2.4  
USE OF ACTUATORS  
Where a CV-98 actuator is used it must be connected in series with the 427354 current  
regulator, fitted at the furthest point to act as the EOL. Where series resistors have been  
used (in existing circuits) to limit the current, a series diode must be fitted as the EOL. It  
must be a silicon diode (not Schottky) rated at 1Adc or greater, e.g. 1N5404. See Fig 9.2.4.  
A single actuator should be connected in reverse, i.e. with the black wire to the incoming  
+ve voltage, so that the supervision can detect that the element has been fired.  
Multiple actuators may be connected in series on one circuit, but each must have the red  
wire to the incoming +ve voltage. Note the supervision cannot detect the difference between  
an unfired element (<2 Ohm) and a fired one (3 series forward diodes).  
a)  
With current regulator at furthest point (EOL)  
b)  
With limiting resistor (not recommended method).  
FIGURE 9.2.4  
CONNECTING MULTIPLE ACTUATORS  
Page 9-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
USE OF ACTUATORS (CONTINUED)  
The maximum number of actuators connected in series in one circuit is dependent on the  
cable resistance. The following are estimates for the Metron Protractor and 427354 current  
limiter, and are not confirmed by the manufacturer (consult the manufacturer).  
Allow: 21V as worst case battery voltage; 6.5V drop for regulator; 2.5V drop per actuator; 1V  
drop for diode EOL; 1V per Ohm of cable resistance.  
Based on these estimates up to 4 actuators may be fitted to a circuit with up to 3.5 Ohms  
cable resistance and a diode EOL.  
9.2.5  
AVI SIGNS  
The AVI is a single, illuminated, 24Vdc warning sign with an internal sounder that produces  
AS2220 Alert and Evacuate warning tones. It has two independent sets of lamps (i.e. top  
and bottom) and two signal inputs, and can be configured to provide the combinations of  
tone and illumination required for Gas Flood warning signs. It can be ordered with one of a  
number of standard faceplates with wording such as FIRE ALARM / EVACUATE AREA.  
AVIs have three pairs of terminals that accept inputs from the FIP, namely '+24V', 'ALERT-',  
and 'EVAC-'. They can be connected and operated in two modes, namely 2-wire and 3-wire.  
The typical connection for 3-wire mode has the +VBF supply connected to +24V, with  
switched 0V signals to ALERT- and EVAC- respectively.  
In 2-wire mode, the +24V terminals are not used. For an EVAC input, the +ve supply is  
connected to ALERT- (i.e EVAC+) and the -ve supply (0V) is switched to EVAC-, and vice  
versa for Alert. However currently the ME0065-69 arrangements do not support this wiring.  
Note the System Inoperative sign is configured and wired in 2 wire mode.  
In its present form, multiple AVIs cannot be supervised if they have their tones synchronised.  
Multiple AVIs on one circuit require a series diodes to be fitted at each sign (i.e. one per  
tone) and two relays (per tone) to allow the circuit to be supervised. See Figures 9.2.5 and  
9.2.6. The logic for each relay is shown alongside the relay (note the numbering is different  
to Figure 9.2.1).  
All signs should be configured for flashing illumination as that attracts attention and saves  
power. Note the AVI has incandescent lamps that draw a large current.  
The configuration of some commonly used signs is as follows.  
Function  
Illuminate  
Top  
Both  
Tone Note  
Alert  
Evac  
1
2
3
4
Top:  
Bottom:  
FIRE ALARM  
EVACUATE AREA  
Top:  
Bottom:  
FIRE ALARM  
DO NOT ENTER  
Top  
Both  
Alert  
Evac  
Top:  
Bottom:  
DO NOT ENTER  
XXXX GAS DISCHARGE  
Top  
Both  
Evac a.  
Evac a.  
Both:  
XXXX SYSTEM INOPERATIVE  
Both  
None  
Options for XXXX include: CO2; INERGEN; FM-200; NAF S III.  
Issue 2.7  
5 July 2001  
Page 9-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
AVI SIGNS (CONTINUED)  
Function Input Lamps Tone Mode DIL SW DIL Sw Lk1,2  
Lk3  
Lk6  
Notes  
On  
Alert 3-wire 1,3,5,6 2,4,7,8  
Evac std  
Off  
1
Alert-  
Both  
Top  
Both  
1-2  
1-2  
On  
2
Alert-  
Both  
Top  
Both  
Alert 3-wire 1,3,5,6 2,4,7,8  
Evac std  
1-2  
1-2  
On  
3
4
Evac-  
Alert-  
Both  
Both  
Evac 2-wire 2,3,5,6 1,4,7,8  
None 3-wire 1,3,5,6, 2,4,7  
2-3  
1-2  
1.2  
2-3  
Off  
On  
b.  
spcl  
8
Notes  
a.  
The option of top lamps with Evac tone for one input, and both lamps with Evac tone  
for the other, is not directly supported. But it can be arranged by mounting the AVI  
upside down.  
b.  
For this configuration the +ve supply is wired into Alert-, not +24V.  
FIG 9.2.3  
CONNECTION OF MULTIPLE LGCSs  
9.2.6  
DRAWINGS  
The following drawings are included:  
1931-47 1 Zone Gas Flood Door, Circuit Diagram  
1937-2 Local Gas Control Station, Circuit Diagram  
Page 9-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
FIGURE 9.2.1  
GAS FLOOD LOGIC DIAGRAM  
Issue 2.7  
5 July 2001  
Page 9-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
FIG 9.2.2  
LOCAL GAS CONTROL STATION, FRONT VIEW  
Page 9-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
Notes  
1.  
2.  
3.  
Only the wiring to AVIs making tones is supervised (the Sync wire is not supervised).  
The supervising relays should be programmed to not supervise in the activated state.  
This AVI should be mounted upside down, with the DNE face plate up the right way.  
FIGURE 9.2.5  
WIRING MULTIPLE SUPERVISED 2 STAGE SIGNS  
Issue 2.7  
5 July 2001  
Page 9-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
Notes  
1.  
The second pole of the relay is used by fitting connectors CN0260, CN0488 to the  
holes in the 8RM.  
2.  
3.  
4.  
If only one sign is used, the diode need not be fitted.  
Both tones should be disabled in the AVI.  
If Supervision is not required, the second pole is not required and the AVI +24V  
terminal can be wired directly to the Gas Flood +24V terminal.  
FIGURE 9.2.6  
WIRING MULTIPLE SUPERVISED SYSTEM INOPERATIVE SIGNS  
Page 9-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
9.3  
SUB FIP MONITORING  
9.3.1  
GENERAL  
A sub-FIP is a Fire Indicator Panel (e.g. a Gas Flood Panel) which may not be connected  
directly to the Brigade, but repeats its common conditions (e.g. Fire, Fault) to another FIP.  
AS1670.1 allows for the cabling from FIP to sub-FIP to be less than 0.75sqmm, and the  
resistance may be considerably greater than that used in standard detector circuits. The  
"Low Current Mode" for an F3200 AZC allows supervision of sub-FIPs on circuits with high  
resistance.  
The limitations caused by the resistance in sub-FIP monitoring circuits are shown in the  
following 3 cases.  
1.  
Loop Resistance Less than 150 Ohms  
For a detector circuit programmed for standard mode the maximum loop resistance is 50  
Ohms, but where there is no detector load (i.e. clean contacts are used) the resistance may  
be up to 150 Ohms.  
Therefore it is recommended that for loop circuits of less than 150 Ohms, "standard mode"  
be used for sub-FIP monitoring.  
All voltage bands are potentially usable, but it is recommended that B3 NOT be used for any  
condition as the circuit voltage drop of up to 2.5V needs to be allowed for. B2 can be used  
with a 5V6 or 6V8 zener diode to detect Alarm i.e. ZnA, and B1 can be used to detect Alarm  
(ZnD) or Instant Alarm (ZnM).  
2.  
Loop Resistance of 150 Ohm to 800 Ohm  
For this resistance range the AZC has to be programmed into "Low Current Mode", and  
voltage band B1 should be programmed as Fault or Alarm but must not be used to detect  
the Fault signal from the sub-FIP (i.e. by shorting the circuit with the Fault contacts).  
Shorting the circuit at the sub-FIP will cause B2 Alarm.  
Because the voltage drop in the circuit wiring is between 3.8V and 12V, depending on loop  
resistance, it is recommended that B3 not be used to detect a signal (for safety sake it is  
advisable to program B3 as Alarm and B1 as Alarm or Fault. Note that only a short  
somewhere within the circuit wiring can cause B1).  
3.  
Loop Resistance of 800 Ohm to 2000 Ohm  
For this resistance range the AZC has to be programmed into "low current mode", and the  
voltage band B3 has to be programmed as Alarm. Shorting the circuit at the sub-FIP will  
cause either a B2 or B3 Alarm depending on the loop resistance (nominal B2/B3 threshold is  
1100 Ohm).  
B1 may be programmed as Fault or Alarm, but must not be used to detect the Fault signal  
from the sub-FIP.  
Issue 2.7  
5 July 2001  
Page 9-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
9.3.2  
CONNECTION  
There are various connection possibilities depending on the particular local requirements for  
Standby and Isolate, and the loop resistance. One or two AZCs may be required.  
Where Standby is required as a separate signal at the Main FIP it can be signalled as Alarm  
on a second AZC and the corresponding zone programmed as non-MAF, non-Anc1, etc.  
Isolate could be signalled as "Fault" on the same AZC (ref Fig 9.3.1 and Fig 9.3.2).  
The Main FIP Brigade Standby and Isolate relays could be reprogrammed to include the  
"standby" zone "alarm" and "fault" conditions, or separate module relays could be  
programmed to operate on the zone "alarm" and "fault" conditions. These would then be  
connected to the Brigade transmitting device in series/parallel with the Standby and Isolate  
contacts of the MAF Brigade relays as appropriate.  
Note that the EOL required depends on the mode programmed for the AZC.  
FAULT (NC)  
┌──┐  
┌─────────o──o────┬──────┤ │+  
┌┴┐  
EOL│ │  
└┬┘  
o
└──┘  
AZC1  
/ ALARM  
o (NO) ┌──┐  
└─────────────────┴──────┤ │-  
└──┘  
ISOLATE (NC)  
┌──┐  
┌─────────o──o────┬──────┤ │+  
┌┴┐  
EOL│ │  
└┬┘  
o
└──┘  
/ STANDBY AZC2  
o (NC) ┌──┐  
└─────────────────┴──────┤ │-  
└──┘  
FIG 9.3.1  
EXAMPLE OF SUB-FIP MONITORING USING 2 AZCS  
FAULT  
ISOLATE  
STANDBY  
┌──┐  
┌─────────o──o───────o──o───────o──o──────┬───────┤ │+  
┌┴┐  
EOL│ │  
└┬┘  
(NC)  
(NC)  
(NO)  
o
└──┘  
AZCn  
/ ALARM  
o (NO) ┌──┐  
└─────────────────────────────────────────┴───────┤ │-  
└──┘  
Fault, Isolate and Standby are all represented by ZnF in the Main FIP.  
FIG 9.3.2  
EXAMPLE OF SUB-FIP MONITORING USING 1 AZC  
Page 9-20  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
FAULT  
ISOLATE  
┌──┐  
┌─────────o──o───────o──o──────┬──────────┬───────┤ │+  
(NC)  
(NC)  
└──┘  
┌┴┐  
2K7│ │  
o STDBY  
/ (NC)  
o
o ALARM  
/ (NO)  
o
AZCn  
└┬┘  
╒╧╕  
5V6 OR 470E │ │  
└┬┘  
┌──┐  
└──────────────────────────────┴──────────┴───────┤ │-  
└──┘  
Program B1 as Instant, ZnM represents "Alarm"  
ZnD represents "Standby"  
ZnF represents "Fault" or "Isolate"  
FIG 9.3.3  
EXAMPLE OF SUB-FIP MONITORING FOR RESISTANCE CASE 1 ONLY  
Note the warnings for testing an AZC (i.e. Test Alarm, Test Fault) when the ZnM and ZnD  
tokens are used in logic equations. (See Section 7.4.3.1).  
Issue 2.7  
5 July 2001  
Page 9-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
9.4  
FIRE DETECTION IN HAZARDOUS AREAS  
(EXPLOSIVE ATMOSPHERES)  
9.4.1  
REFERENCES  
AS 2380  
Electrical Equipment for Explosive Atmospheres - Explosion-Protection  
Techniques.  
AS 2381  
Electrical Equipment for Explosive Atmospheres - Selection, Installation &  
Maintenance.  
AS 2430  
IEC79  
Classification of Hazardous Areas.  
Electrical Apparatus for Explosive Atmospheres.  
Electrical Equipment for Hazardous Areas (handbook).  
SAA HB13  
9.4.2  
GENERAL  
A hazardous area is one which has a potentially explosive atmosphere due to combustible  
gases, liquids or dusts. In such an area there has to be a constraint to prevent an electrical  
fault from causing an explosion.  
For fire detection in hazardous areas there are two main options:  
1)  
Use approved IS (Intrinsically Safe) detectors and bases with IS isolators or Zener  
barriers and approved cabling.  
2)  
Use approved detectors with explosion proof housings and compatible cabling. (E.g.  
Olsen V41B, (V42B), V44B, T54B). These are not discussed further in this section  
as the constraints are primarily mechanical.  
Note that in addition to equipment selection and inter-connection, there are other  
requirements for wiring in hazardous areas that must be satisfied.  
These include (but are not limited to):  
Matching “Ex” rating of equipment chosen with hazardous area classification.  
Ensuring cable capacitance and inductance is within the limits of the repeaters used  
(see Tables 9.4.3, 9.4.4, 9.4.5 for more details).  
Providing adequate physical protection for equipment according to local hazardous  
area wiring regulations.  
Using cable of the correct insulation and physical strength according to local  
hazardous area wiring regulations.  
Complying with manufacturer’s instructions for mounting of “Ex” rated devices.  
Inspection and certification of the finished installation.  
Page 9-22  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
9.4.3  
INTRINSICALLY SAFE DETECTION  
There are two types of device which may be inserted in a detector circuit between the FIP  
and the detectors to limit the electrical energy flow into the area and provide IS detection:  
1)  
2)  
Galvanically (transformer) isolated repeaters (isolators).  
Zener barriers (shunt barriers with fuses). These limit the circuit voltage relative to  
earth, and the circuit current.  
Although Zener barriers are cheaper than isolators they require a special Intrinsic  
Safety Earth, and precautions, and are therefore not recommended.  
9.4.3.1  
ISOLATED REPEATERS  
There are several options for using isolated repeaters, each with differing limitations and  
expense.  
The options are:  
1.  
2.  
3.  
Use a 6 terminal isolating repeater where large numbers of smoke and/or flame  
detectors are required (see Section 9.4.3.2).  
Use a lower-cost 4 terminal isolating repeater and a ZAU401 (Rev 2) where lower  
numbers of smoke and/or flame detectors are required (see Section 9.4.3.3).  
Use a 4 terminal isolating repeater where all detectors generate a short circuit alarm  
condition (see Section 9.4.3.4).  
For these the total capacitance and inductance of the detectors and cables on the IS circuit  
must be less than that specified in Table 9.4.1. The gases and vapours in each Gas group  
are listed in IEC 79-12.  
GAS GROUP  
MAX. CAPACITANCE  
MAX. INDUCTANCE  
Class IIA or Group D  
Class IIB or Group C  
Class IIC or Group A or B  
1.04uF  
0.39uF  
0.13uF  
31.9mH  
12.6mH  
3.6mH  
TABLE 9.4.1  
MAXIMUM CAPACITANCE & INDUCTANCE PER IS CIRCUIT  
For isolated repeaters, the cable core to core capacitance can be used, rather than core to  
earth which, for bunched conductors on metal trays, may be higher. (Note that for Zener  
barriers, the core to earth capacitance is relevant). The values used in this section for a  
typical TPS pair, or multicore cable (unshielded) are:  
TPS  
C = 100nF/km (i.e. 100 pF/m), L = 0.8mH/km  
Cable manufacturers may quote differing values for specific cables.  
It is the responsibility of the System Engineer to check that the cable  
used has values less than or equal to the above values, and that the total capacitance and  
inductance for each circuit meet the requirements.  
The values specified for the detectors are shown in Table 9.4.2.  
Issue 2.7  
5 July 2001  
Page 9-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
ISOLATED REPEATERS (CONTINUED)  
DETECTOR  
CAPACITANCE  
INDUCTANCE  
RESISTANCE  
(FW ONLY)  
C29BEx/Z94C  
R24Bex  
1Nf  
3.3nF  
84nF/km  
66nF/km  
57nF/km  
1.5nF  
4nF  
1.5nF  
1.5nF  
1.5nF  
1.5nF  
0
1uH (0.001mH)  
1.5mH  
0.62mH/km  
0.83mH/km  
0.89mH/km  
FW68  
FW105  
FW180  
S231i+  
S121  
MS302Ex  
MF301Ex  
100Ω/km  
100Ω/km  
100Ω/km  
0
0
0
0
0
0
0
0
0
MR301Ex (Photo)  
MR301TEX (HPO)  
T56B (Heat)  
(Z500N base)  
T54B (Heat)  
0
0
TABLE 9.4.2  
CAPACITANCE & INDUCTANCE PER I.S. DETECTOR  
Notes  
1.  
The KHD0-ICS/Ex 251 or KFD0-CS-Ex 2.51P is effectively two KHD0-ICS/Ex 151 or  
KFD0-CS-Ex 1.51P isolators (respectively) in one package.  
2.  
The resistance quoted in Table 9.4.2 for fire wire is per wire, thus the circuit  
resistance of the pair is twice that amount.  
3.  
4.  
The FW68 and FW105 fire wires are not currently listed as IS.  
The MS302Ex, MF301Ex, MR301Ex, MR301TEx, S121 and S231i+ detectors are  
currently not SSL approved.  
For each of the following configuration options a table is included showing the limits of  
detector quantity and cable length.  
Page 9-24  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
9.4.3.2  
6 TERMINAL ISOLATED REPEATER  
The following 6 terminal isolating repeaters can connect an F3200 zone to an IS detection  
circuit using the circuit of Figure 9.4.3.2.  
Pepperl & Fuchs  
Pepperl & Fuchs  
KHD3-ICR/Ex130 200  
KFD2-CR-Ex1.30 200  
OR  
FIG 9.4.3.2  
F3200 IS CIRCUIT USING 6-TERMINAL REPEATERS  
Relay or Open Collector  
For each AZC there must be either: a corresponding relay (e.g. Module Relay RLn) with  
normally closed contacts breaking the supply to the Isolator as shown; or an open collector  
output switching the supply 0V as shown. As the open collector is standard with an 8ZM it is  
the cheapest alternative.  
Issue 2.7  
5 July 2001  
Page 9-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
6 TERMINAL ISOLATED REPEATER (CONTINUED)  
Programming & Limitations  
All detector types require the circuit to be programmed for Mode 1 (Std) with voltage band  
B1 programmed as Alarm.  
The open collector must be programmed as OCn = ^ZnR, or the Relay must be programmed  
as Rn = ZnR (i.e. Zone n not in Reset or Zone n in Reset respectively).  
There can be no differentiation of voltage bands (B1, B2, B3) i.e. the FIP cannot differentiate  
between MCP and detector operation on the same circuit.  
Any alarm on the detector circuit (either a short circuit or detector operation) will cause a B1  
or a B2 voltage level on the FIP AZC, depending on the battery voltage.  
Detector quantity and circuit length limits are shown in Table 9.4.3.  
GAS GROUP 11A OR 11B  
CCT LENGTH  
GAS GROUP 11C  
CCT LENGTH  
DETECTOR  
PART  
QTY  
QTY  
40(M)  
TYPE  
BASE  
Z94C  
1.0mm²  
0.75mm²  
1.00mm²  
0.75mm²  
SMOKE  
C29BEx  
40(M)  
3km(R)  
2.2km(R)  
0.9km(C)  
(90nF)  
0.9km(C)  
(90nF)  
(100Ω)  
(100Ω)  
33  
0.97km(C)  
(97nF)  
0.97km(C)  
(97nF)  
20  
1.1km(C)  
(110nF)  
1.3km(C)  
(130nF)  
1.2km(C)  
(120nF)  
1.3km TOT  
(130nF)  
1.3km(C)  
(130nF)  
1.1km(C)  
(110nF)  
1.3km(C)  
(130nF)  
1.1km(R)  
(50Ω)  
1.3km TOT  
(130nF)  
1.3km(C)  
(130nF)  
1
FLAME  
HEAT  
R24BEx  
FW105  
-
-
7(M)  
-
1.5km(R)  
(50Ω)  
-
1.1km(R)  
(50Ω)  
-
2(M)  
-
(100Ω TOT)  
3km(R)  
(100Ω)  
(100Ω TOT)  
2.2km(R)  
(100Ω)  
40(M)  
40(M)  
HEAT  
HEAT  
T54B  
T56B  
-
Z500N  
40(M)  
11(M)  
3km(R)  
2.2km(R)  
40(M)  
1.13KM(C)  
(130nF)  
1.3km(C)  
(130nF)  
(100Ω)  
(100Ω)  
HEAT  
S231i+  
-
3KM (R)  
2.2KM (R)  
11(M)  
5
1.13km(C)  
(113nF)  
1.22km(C)  
(122nF)  
1.28km(C)  
(128nF)  
0.02km(C)  
(2nF)  
1.13KM(C)  
(113nF)  
1.22km(C)  
(122nF)  
1.28km(C)  
(128nF)  
0.02km(C)  
(2nF)  
(100Ω)  
(100Ω)  
1
FLAME  
S121  
-
40(M)  
40(M)  
3km(R)  
(100Ω)  
2.2km(R)  
(100Ω)  
32(M)  
20  
0.5km(C)  
(50nF)  
0.5km(C)  
(50nF)  
10  
0.9km(C)  
(90nF)  
0.9km(C)  
(90nF)  
1
1.26km(C)  
(126nF)  
0.7km(C)  
(70nF)  
1.26km(C)  
(126nF)  
0.7km(C)  
(70nF)  
FLAME  
MS302Ex  
M300  
3km(R)  
2.2km(R)  
40(M)  
20  
(100Ω)  
(100Ω)  
1km(C)  
1km(C)  
(100nF)  
1.28km(C)  
(128nF)  
(100nF)  
1.28km(C)  
(128nF)  
1
ION  
PHOTO  
HPO  
MF301Ex  
MR301Ex  
MR301TEx  
M300  
M300  
M300  
40(M)  
40(M)  
40(M)  
(SAME AS MS302Ex)  
(SAME AS MS302Ex)  
(SAME AS MS302Ex)  
TABLE 9.4.3  
MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR 6-TERMINAL REPEATER  
Page 9-26  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
6 TERMINAL ISOLATED REPEATER (CONTINUED)  
Notes  
1.  
Circuit lengths quoted are from the isolator to the EOL. An extra 50 Ohms of cable  
from the FIP to the isolator is also allowed (1.5km of 1.0mm², 1.1km of 0.75mm²).  
The length quoted is the maximum for the corresponding quantity of detectors.  
2.  
3.  
4.  
Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω  
per km (return) is used for 1 mm².  
The maximum resistances shown for the fire wire circuits must include both cable  
and fire wire (see Table 9.4.2 and associated note 2).  
The letter in ( ) after the cable length, and the value in ( ) under the cable length  
specify which parameter out of capacitance (C), inductance (L) and resistance (R)  
provides the limitation, and what the maximum value is.  
5.  
6.  
The (M) after a detector quantity indicates the maximum quantity allowed per circuit.  
The maximum allowable detector quiescent (or 2 second switch on) current is 3.5mA  
(only relevant to R24BEx).  
7.  
The C23BEx detector (old type) would be compatible but has not been tested in this  
configuration.  
9.4.3.3  
4 TERMINAL ISOLATED REPEATER WITH ZONE ADAPTOR UNIT  
ZAU401  
With the addition of the ZAU401 Zone Adaptor Unit (PA0838), lower-cost 4-terminal isolating  
repeaters can be used with the F3200 panel.  
The ZAU401 can be thought of as a single zone circuit module that can be added to a panel  
to make it compatible with a wider range of detectors – in particular when using IS repeaters.  
The ZAU401 can support up to 2mA of quiescent detector current and uses a 3k9 5% EOL  
resistor.  
Wiring of the ZAU401 and the isolating repeater to the panel is shown in Figure 9.4.3.3.  
Note that only one ZAU401 can be connected to each of the panel’s zone circuits.  
The following 4-terminal isolating repeaters can be used to connect the ZAU401 to an IS  
detection circuit. (Note that dual channel repeaters have two separate repeaters, and can  
connect two circuits with two ZAU401s).  
Pepperl & Fuchs  
Pepperl & Fuchs  
Pepperl & Fuchs  
Pepperl & Fuchs  
KHD0-ICS/Ex 1.51 (single channel)  
KHD0-ICS/Ex 2.51 (dual channel)  
KFD0-CS-Ex 1.51P (single channel)  
KFD0-CS-Ex 2.51P (dual channel)  
MTL5061 (dual channel)  
Measurement Technology Ltd  
Issue 2.7  
5 July 2001  
Page 9-27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
4-Terminal Isolating  
Repeater  
Panel  
24V  
KHD0_  
OR  
KFD0_  
OR  
ZAU401 (Rev 2)  
(PA0838)  
-
+
EOL  
3k9  
5%  
1 BATT+  
Ex DETECTOR  
Ex DETECTOR  
+
2 ZONE+  
3 EOL+  
4 EOL-  
5 ZONE-  
6 BATT-  
To Panel  
EOL*  
MTL5061  
+
-
Zone Circuit  
T+ 3  
TC 2  
T-  
-
1
* EOL to suit Panel  
SAFE AREA  
HAZARDOUS AREA  
FIG 9.4.3.3  
F3200 WITH ZAU401 & 4 TERMINAL IS REPEATER  
Programming & Limitations  
The circuit should be programmed as Mode 1 (standard). Voltage bands B1 and B3 can be  
left at default, though it is better to program B1 as fault. Voltage band B3 is not generated  
by a ZAU401 so can be left at the default setting (which is “normal” for V1.XX software and  
“instant alarm” for V2.XX software).  
Note that all alarms from the ZAU401 will give voltage band B2 i.e. the FIP cannot  
differentiate between MCP and detector operation, and voltage B1 represents a short on the  
circuit between the FIP and the ZAU401 (i.e. internal wiring fault).  
Detector quantity and circuit length limits are shown in Table 9.4.4.  
Page 9-28  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
4 TERMINAL ISOLATED REPEATER WITH ZONE ADAPTOR UNIT ZAU401 (REV 2)  
(CONTINUED)  
GAS GROUP 11A OR 11B  
CCT LENGTH  
GAS GROUP 11C  
CCT LENGTH  
DETECTOR  
PART  
QTY  
QTY  
40(M)  
TYPE  
BASE  
Z94C  
1.0mm²  
0.75mm²  
1.00mm²  
0.75mm²  
SMOKE  
C29BEx  
40(M)  
3km(R)  
2.2km(R)  
0.9km(C)  
(90nF)  
0.9km(C)  
(90nF)  
(100Ω)  
(100Ω)  
33  
0.97km(C)  
(97nF)  
0.97km(C)  
(97nF)  
20  
1.1km(C)  
(110nF)  
1.3km(C)  
(130nF)  
0.5km(C)  
(17Ω)  
1.3km TOT  
(130nF)  
1.3km(C)  
(130nF)  
1.1km(C)  
(110nF)  
1.3km(C)  
(130nF)  
0.37km(R)  
(17Ω )  
1.3km TOT  
(130nF)  
1.3km(C)  
(130nF)  
1
FLAME  
HEAT  
R24BEx  
FW105  
-
-
2(M)  
-
0.5km(R)  
(17Ω)  
-
.37km(R)  
(17Ω)  
-
2(M)  
-
(100Ω TOT)  
3km(R)  
(100Ω)  
(100Ω TOT)  
2.2km(R)  
(100Ω)  
40(M)  
40(M)  
HEAT  
HEAT  
T54B  
T56B  
-
Z500N  
40(M)  
4(M)  
3km(R)  
2.2km(R)  
40(M)  
1.13km(C)  
(130nF)  
1.3km(C)  
(130nF)  
(100Ω)  
(100Ω)  
HEAT  
S231i+  
S121  
-
-
3KM (R)  
(100Ω)  
2.2KM (R)  
(100Ω)  
4(M)  
1
1.24KM(C)  
(124nF)  
1.28km(C)  
(128nF)  
1.24KM(C)  
(124nF)  
1.28km(C)  
(128nF)  
FLAME  
16(M)  
16(M)  
3km(R)  
(100Ω)  
2.2km(R)  
(100Ω)  
16(M)  
10  
0.66km(C)  
(66nF)  
0.9km(C)  
(90nF)  
0.66km(C)  
(66nF)  
0.9km(C)  
(90nF)  
1
126km(C)  
(126nF)  
1.26km(C)  
(126nF)  
FLAME  
MS302Ex  
M300  
3km(R)  
2.2km(R)  
16(M)  
10  
1.06km(C)  
(106nF)  
1.15km(C)  
(115nF)  
1.06km(C)  
(106nF)  
1.15km(C)  
(115nF)  
(100Ω)  
(100Ω)  
1
1.28km(C)  
(128nF)  
1.28km(C)  
(128nF)  
ION  
PHOTO  
HPO  
MF301Ex  
MR301Ex  
MR301TEx  
M300  
M300  
M300  
16(M)  
16(M)  
16(M)  
(SAME AS MS302Ex)  
(SAME AS MS302Ex)  
(SAME AS MS302Ex)  
TABLE 9.4.4  
MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR  
ZAU401 (REV 2) & 4-TERMINAL REPEATER  
Notes  
1.  
Circuit lengths quoted are total from the FIP to the EOL. The length quoted is the  
maximum for the corresponding quantity of detectors.  
2.  
3.  
4.  
Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω  
per km (return) is used for 1 mm².  
The maximum resistances shown for the fire wire circuits must include both cable  
and fire wire (see Table 9.4.2 and associated note 2).  
The letter in ( ) after the cable length, and the value in ( ) under the cable length  
specify which parameter out of capacitance (C), inductance (L) and resistance (R)  
provides the limitation, and what the maximum value is.  
5.  
6.  
The (M) after a detector quantity indicates the maximum quantity allowed per circuit.  
The maximum allowable detector quantity corresponds to a quiescent current of  
1.8mA for C29BEx, 0.3mA for R24BEx.  
Issue 2.7  
5 July 2001  
Page 9-29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
9.4.3.4  
4 TERMINAL ISOLATED REPEATER ALONE  
When all the detectors on the IS circuit will generate a short circuit alarm condition it is  
possible to use the lower-cost, 4-terminal isolating repeater without a ZAU401. This is  
shown in Figure 9.4.3.4.  
The following 4-terminal isolating repeaters can be used. (Note that dual channel repeaters  
have two separate repeaters, and can connect two circuits to the panel).  
Pepperl & Fuchs  
Pepperl & Fuchs  
Pepperl & Fuchs  
Pepperl & Fuchs  
KHD0-ICS/Ex 1.51 (single channel)  
KHD0-ICS/Ex 2.51 (dual channel)  
KFD0-CS-Ex 1.51P (single channel)  
KFD0-CS-Ex 2.51P (dual channel)  
MTL5061 (dual channel)  
Measurement Technology Ltd  
SEE  
TEXT  
FIG 9.4.3.4  
SHORT-CIRCUITING DETECTORS WITH 4 TERMINAL REPEATER  
Programming & Limitations  
The required EOL resistance is lower than the standard 2k7. Two methods for obtaining the  
correct EOL value are:  
1.  
Place a 22K 5% resistor in parallel with the supplied 2k7 EOL. This achieves the  
required value.  
2.  
Or just use a 2k2 5% resistor as the EOL.  
The circuit should be programmed as Mode 1, B3 as Normal, and B1 should be programmed  
as Fault.  
There can be no differentiation between MCP and detector operation on the same circuit.  
Detector quantity and circuit length limits are shown in Table 9.4.5.  
Page 9-30  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
4 TERMINAL ISOLATED REPEATER ALONE (CONTINUED)  
DETECTOR  
PART  
GAS GROUP 11A OR 11B  
CCT LENGTH  
GAS GROUP 11C  
CCT LENGTH  
QTY  
-
QTY  
-
TYPE  
HEAT  
BASE  
-
1.0mm²  
0.75mm²  
1.00mm²  
0.75mm²  
FW105  
NOTE 2 & 3  
NOTE 2 & 3  
1.3km TOT  
(130nF)  
1.3km TOT  
(130nF)  
(68Ω TOT)  
(68Ω TOT)  
HEAT  
HEAT  
T54B  
T56B  
-
40(M)  
2km(R)  
1.5km(R)  
40(M)  
1.3km(C)  
(130nF)  
1.3km(C)  
(130nF)  
(68Ω TOT)  
(68Ω)  
Z500N  
40(M)  
2km(R)  
1.5km(R)  
40(M)  
1.3km(C)  
(130nF)  
1.3km(C)  
(130nF)  
(100Ω)  
(68Ω)  
TABLE 9.4.5  
MAXIMUM DETECTOR QUANTITY & CABLE LENGTH FOR 4 TERMINAL  
REPEATER ALONE  
Notes  
1.  
Circuit lengths quoted are from the isolator to the EOL. The length quoted is the  
maximum for the corresponding quantity of detectors.  
2.  
3.  
4.  
Cable resistance shown is for the circuit, ie. both cables in the pair. The value of 34Ω  
per km (return) is used for 1 mm².  
The maximum resistances shown for the fire wire circuits must include both cable  
and fire wire (see table 9.4.2 and associated note 2).  
The letter in ( ) after the cable length, and the value in ( ) under the cable length  
specify which parameter out of capacitance (C), inductance (L) and resistance (R)  
provides the limitation, and what the limiting value is.  
5.  
The (M) after a detector quantity indicates the maximum quantity allowed per circuit.  
Issue 2.7  
5 July 2001  
Page 9-31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
9.5  
USE OF NORMALLY CLOSED CONTACTS  
There may be some situations where it is necessary to monitor a set of normally-closed  
contacts which open on "alarm".  
As standard these cannot be wired directly to the F3200 AZC terminals.  
The Vigilant Contact Conversion Module (part number PA0443) may be used as a  
conversion interface between the contacts and an F3200 AZC.  
This small, encapsulated module has three wires protruding from it.  
These must be connected between the normally closed contact and the AZC as shown in  
Figure 9.5.1, using suitable screw terminal blocks.  
The module applies a low impedance to the AZC when the alarm contacts open, and so the  
circuit must be programmed as B1 = Alarm.  
FIG 9.5.1  
NORMALLY CLOSED CONTACT WIRING TO F3200 AZC  
Page 9-32  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Applications  
9.6  
SPECIAL CONNECTIONS TO DETECTORS  
9.6.1  
CONNECTING THE S231I+ OR S231F+ (USING ZAU401 REV 2)  
* * W A R N I N G * *  
Even though the S231i+ is listed as hazardous area rated, this compatibility is for a direct  
connection – not through an intrinsically-safe isolator, and thus cannot be used in hazardous  
area applications. For IS applications refer to Section 9.4.  
The S231i+ and S231f+ detectors are not directly compatible with the F3200. However,  
compatibility can be achieved by using the PA0838 ZAU401 (Rev 2) Zone Adaptor unit  
between the panel and the detectors.  
The ZAU401 can be thought of as a single zone circuit module that can be added to a panel  
to make it compatible with a wider range of detectors. The ZAU401 supports up to 2mA of  
quiescent detector current, thus only 5 S231i+ or S231f+ detectors can be used on each  
ZAU401. It operates off the panel’s 24V supply and consumes 20mA in the normal state.  
Only one ZAU401 can be connected to each circuit on the panel. Also, do not use a Rev 1 or  
non-Vigilant manufactured ZAU401 as these have different characteristics.  
A 220E 5W resistor (Vigilant part number RR0415) must be placed in series with the  
detector circuit at the ZAU401 to limit the maximum current to any detectors in alarm.  
Wiring of the ZAU401 to the panel and S231i+ / S231f+ detectors is shown in Figure 9.6.1.1.  
* EOL to suit Panel used.  
PANEL  
DETECTORS  
Panel  
24V  
ZAU401 (Rev 2)  
(PA0838)  
2 ZONE+  
3 EOL+  
4 EOL-  
-
+
1 BATT+  
5W  
220E  
+
To Panel  
EOL*  
EOL  
3k9  
5%  
T+ 3  
TC 2  
Zone Circuit  
S231i+  
DETECTORS  
5 ZONE-  
6 BATT-  
-
T-  
1
QTY 5 MAXIMUM  
FIGURE 9.6.1.1  
ZAU401 (REV 2) AND S231i+ or S231f+  
Issue 2.7  
5 July 2001  
Page 9-33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Applications  
Document No: LT0122  
THIS PAGE INTENTIONALLY LEFT BLANK  
Page 9-34  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Alignment, Adjustment & Placing into Operation  
CHAPTER 10  
ALIGNMENT, ADJUSTMENT &  
PLACING INTO OPERATION  
Issue 2.7  
5 July 2001  
Page 10-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Document No: LT0122  
Alignment, Adjustment & Placing into Operation  
10.1  
ALIGNMENT & ADJUSTMENT  
All the F3200 modules (pcbs) are tested and aligned in the factory before being supplied to  
the customer or fitted to a FIP. The only field adjustments that may be necessary are to set  
the LCD contrast and the battery charger voltage.  
Controller/Display  
VR2 LCD Contrast  
Adjust for best readability of the LCD when viewed from the  
front of an installed FIP.  
Factory adjustments include:  
VR1 Set 1.2V Ref  
Adjust for Charger High voltage of 28.1V to 28.15V.  
Adjust until the 15.9V reference on TP15 is 15.90Vdc.  
VR3 Adjust 15.9V  
R94, Fault Threshold  
R105  
Snip as required to set Fault Threshold to  
nominal 19.03V.  
MAF/PSU  
PT1 Battery Charger Voltage  
Should the battery charger voltage need adjusting, the method is as follows:  
1.  
Run the system with the door closed for at least 30 minutes to allow components to  
"warm up" (the longer the better).  
2.  
Calculate the required no-load battery charging voltage by taking 27.3V for 20°C and  
subtracting approximately 0.1V for every 3°C above 20°C, or adding approximately  
0.1V for every 3°C below 20°C.  
3.  
4.  
With the system not in Alarm, disconnect the batteries.  
Measure the voltage at the battery terminals and adjust to the voltage calculated in  
Step 2 by turning PT1.  
5.  
Re-connect the batteries.  
PT2 +22V Supply is factory set and should not need field adjustment.  
Page 10-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Alignment, Adjustment & Placing into Operation  
10.2  
PLACING INTO OPERATION  
10.2.1  
GENERAL  
This chapter describes the procedure to place an F3200 FIP into operation. It assumes that  
the mains and other field wiring has been connected, but that the battery has not. Note that  
all electronic modules were tested and adjusted in the factory and should need no further  
adjustment.  
Before switching on power, inspect the cabinet and internals. Check as follows:  
1.  
2.  
3.  
Check that all equipment is securely mounted, and that all cables are connected at  
the appropriate points. The factory checklist is included.  
Check that the 8 way modules and (if required) the 16 Zone LED Displays are fitted  
and connected correctly. (See Sections 2.3.2, 5.2 and 8.1).  
Check that (if required) the additional battery test resistors, 6A power supply and  
overcurrent protection device are fitted as per Chapter 5 (with PTCs shorted). Note  
that batteries are not yet connected.  
4.  
5.  
Check that links Lk2-4 on the MAF are fitted (unless Anc3, clean contacts is being  
used), and module relay supervision links are fitted in the S position for relays which  
require supervision.  
Check that the field wiring of AZC and relays is as per the "As Built" wiring diagrams  
and corresponds to the configuration of modules and links.  
The "MAINS ISOLATE SWITCH" is located at the top right hand side of the cabinet rear, to  
the left of the mains transformer, behind the inner display door. This controls the mains  
power to the FIP, charger and power supply, and should be left on once the FIP is  
operational.  
NOTE: The Battery is not disconnected by the "MAINS ISOLATE SWITCH".  
Issue 2.7  
5 July 2001  
Page 10-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Document No: LT0122  
Alignment, Adjustment & Placing into Operation  
10.2.2  
POWER UP  
To place the F3200 FIP into operation, perform the following steps:  
STEP 1  
STEP 2  
Ensure that the Mains Isolate Switch is OFF.  
Ensure that 240 VAC is connected to the panel from the mains distribution  
switchboard.  
STEP 3  
Ensure that Lk7 on the controller is set to the DATABASE WRITE PROTECT  
position before powering on the panel. If an E2INIT is required before  
programming, fit minijump SW1. (Refer to Section 6.3.1).  
Turn the Mains Isolate Switch ON.  
STEP 4  
STEP 5  
STEP 6  
STEP 7  
STEP 8  
Check that the buzzer sounds and all LEDs on the Operator Display panel  
flash for 2 seconds (except Mains On).  
Check that the green "MAINS ON" LED indicator is on.  
The Controller performs tests on its memory, electronics, and the LCD.  
Check that the LCD has good visibility. The LCD displays the FIP PCB  
configuration before showing the Base Display.  
If doing an E2INIT, set Lk7 to the DATABASE WRITE position, then remove  
minijump SW1 and press "ACK" to complete the sequence.  
Install and connect the batteries.  
Take care not to short the battery leads or connect in reverse polarity when  
connecting.  
STEP 9  
If required, complete programming as per Chapters 6 and 7 and then fit Lk7  
on the Controller to the DATABASE PROTECT position.  
STEP 10  
Perform a Battery Test.  
-
If this fails check the battery connections, leave for 24 hours and then  
retest.  
STEP 11  
Perform a Bells and System Test (de-isolate all zones first).  
A full commissioning test should be carried out as per AS1670.1.  
Page 10-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Alignment, Adjustment & Placing into Operation  
10.2.3  
COMMISSIONING CHECKLIST  
The following checklist should have been completed and supplied by the manufacturer. It  
should be placed with other System Configuration Information. Commissioning staff should  
check the installed FIP against it. (Note that all pcbs are electronically tested and adjusted  
before being fitted to the FIP).  
1.  
CABINET & GENERAL  
A)  
Cabinet colour - Standard Cream Wrinkle (BFF 998 CW)  
- Other: ____________________________________  
B)  
C)  
D)  
E)  
F)  
G)  
H)  
I)  
Cabinet undamaged (Paint OK)  
Door aligned correctly  
Window undamaged and fitted correctly  
MCP fitted and undamaged  
Cabinet Door locks firmly, operates microswitch  
Lock - 003 Type & two keys supplied  
Door seals fitted to top and sides  
Display Keypad and 4U door fitted & aligned correctly  
Cardframe fitted, card fits frame correctly ..(FP0551 only)  
Standoffs fitted to cabinet rear (none missing)  
Operator Manual and battery leads included  
VIGILANT label completed, fitted  
J)  
K)  
L)  
M)  
2.  
PCBS & WIRING  
A)  
B)  
C)  
D)  
E)  
F)  
G)  
MAF/PSU Fitted securely on standoffs  
Controller/Display fitted securely  
8ZM fitted securely, earth screw fitted  
FRC Looms fitted correctly  
MCP & door switch wires fitted to J6 of MAF/PSU, secured  
Earth wire fitted to display door  
All 3 modules earth to cabinet metal  
Issue 2.7  
5 July 2001  
Page 10-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Document No: LT0122  
Alignment, Adjustment & Placing into Operation  
COMMISSIONING CHECKLIST (CONTINUED)  
3.  
POWER SUPPLY  
A)  
B)  
C)  
D)  
E)  
F)  
G)  
Mains Wired correctly, MOV, cap fitted  
"Mains Isolate Switch" and "NAE" label fitted  
Mains Earth wired to stud, good contact  
Mains Switch neon off/on for switch off/on  
MAF/PSU Mains On LED on, Fuse Blown LED off  
VRECT at DC IN tab 40-42Vdc  
Charger Voltage 27.25-27.4V warm, 27.5-27.75V cold  
4.  
OPERATION  
A)  
B)  
C)  
D)  
E)  
F)  
G)  
H)  
I)  
LEDs flash, aligned with windows, "MAINS ON" LED on  
Buzzer pulses with microswitch operated, Lk7 in Write  
Controller LK7 in "Protect" position  
LCD contrast correct for front view  
De-isolate zones, system test pass on all (8) circuits  
FIP MCP Programmed to Zone 1; Other: ___________ OK  
"ALM" LED flashes & buzzer pulses for MCP operation  
Acknowledge silences buzzer, Zone Resets  
Controller Lk2 fitted (not in Service mode)  
SERIAL NUMBER  
TEST PASSED  
DATE : ……….............  
SIGNATURE : ……………….......................  
Page 10-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
CHAPTER 11  
NETWORK PROGRAMMING  
Issue 2.7  
5 July 2001  
Page 11-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.1  
INTRODUCTION  
11.1.1  
PANEL-LINK NETWORK  
Networking enables up to 64 F3200 FIPs to be interconnected via single or duplicated 2 wire  
connections, and information to be exchanged between FIPs.  
Alarms occurring on any FIP on the network may be displayed and acknowledged on the  
LCD FFCIF of any other FIP. Similarly output logic variables are available on the network,  
enabling data from any FIP to be used as input parameters in logic equations on any other  
FIP in the system.  
Commands can be entered at one networked F3200 to reset, isolate, de-isolate, test and  
recall/search for status for zones on other networked FIPs.  
Networked F3200s can also send and receive system commands from the network such as  
isolation/de-isolation of bells, system test and bells test.  
Intended usages for the Panel-Link are:  
(i)  
Connection of two or more fire panels together to share data and expand fire panel  
capability, either by co-locating two systems, or having them geographically  
separate.  
(ii)  
Connection of printers, BMS systems and PCs using Vigilant PTM or PMB to receive  
data from panels on the network.  
(iii)  
Connection of a Fire Panel to an Evacuation System for network connection initiation  
of evacuation sequences.  
To enable FIPs to be identified on the network, each FIP is configured with a System  
Identification Number (or SID) in the range 1 to 254. This number must be unique for each  
device on the network.  
11.1.2  
NETWORK APPLICATION OVERVIEW  
The main benefits of networking F3200s are the sharing of zone, event and alarm  
information, the ability to remotely control other F3200s, and overall, to expand the size of an  
F3200 system beyond 64 zones.  
F3200s are programmable in a number of ways to customise the type of information to be  
shared, how it is to be shared, and the extent to which remote control is permitted.  
The Network Configuration menu is Option 7 in the Program Data menu (as is shown in  
Figure 6.1.2C). It allows programming of the parameters which determine the way the  
F3200 networking operates.  
Page 11-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
Network Application Overview (Continued)  
The menu includes the following options:  
1. Config, 2. SIDs, 3. MAF, 4. Cmds, 5. FFCIF, 6. Events, 7. Net-variables, 8. Status;  
1.  
2.  
3.  
4.  
5.  
Config defines the network type, the critical timing parameters, whether this panel  
sends link integrity messages, and the group membership for this panel.  
The Network SID settings define which other panels on the network the F3200 is to  
send or receive information or commands.  
The Network MAF settings control the usage of common panel status for brigade  
interfaces and status totals for display to system operators.  
The Network Command settings are associated with the sending and receiving of  
commands to/from other panels.  
The FFCIF application settings control the sending of FFCIF alarm events to other  
panels on the network. Receiving FFCIF alarm events is programmed in the Network  
SID menu.  
6.  
7.  
8.  
The Network Event settings are associated with the transmitting of event information  
onto the network.  
The Network Variable settings control the transmitting of network variable data onto  
the network.  
Network Status configuration controls the refreshing of zone status onto the network.  
Figure 11.1.1 shows the Network Configuration menu and its hierarchial structure.  
When a user needs to change one particular parameter in an existing FIP, Figure 11.1.1 acts  
as a "road map" that shows the path required to access that parameter.  
Detail on each menu is shown in the following sections.  
Issue 2.7  
5 July 2001  
Page 11-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.2  
PROGRAMMING METHODS  
11.2.1  
DATA FILTERS - THE SID LIST & GROUPS LIST  
The Panel-Link network utilises a number of concepts to allow a network designer to  
determine not only what information gets onto the network, but where that information can  
be used.  
The first concept is the SID list: an F3200 can only use Network Logic, MAF data and MAF  
totals from units whose SID is in the list and can only send and receive commands, recall  
zones and monitor the scan status (link integrity) for SIDs in the SID list.  
The second concept is the Group Membership list. This concept affects Event Annunciation  
(FFCIF alarms) and Event Logging, where the events are broadcast onto the network. Each  
unit on the network is programmed for membership in any number of the 8 groups possible.  
Events contain the group membership list of the unit that generated the event.  
11.2.2  
NETWORK MAF STATUS  
An F3200 panel transmits (if programmed to) its MAF status and totals (alarm, fault, isolate  
and "other" as shown on the base display) onto the network for use by other panels. Other  
panels will use that MAF status to drive their own MAF outputs (alarm, fault, isolate, standby  
and bells outputs) only if they are programmed to use the MAF status that comes from this  
panel (refer to SID list programming section 11.4.3 "use MAF relay option"). This allows the  
brigade connection/signalling to be done at only one panel on the network if desired  
(although it may be done by more than one panel if necessary).  
The totals received from other panels on the network may be added to the local totals of this  
panel and shown on the base display. If any of the totals (alarm, fault, isolate) shown on the  
base display of this panel are non zero then the corresponding front panel LED will be on.  
The MAF status transmitted onto the network includes the following information. All of the  
states are normally false and become true for an off normal condition.  
1.  
MAF alarm state.  
True if any non isolated MAF mapped zone is in alarm.  
When true, this will cause any panel on the network which is programmed to use the  
MAF data from this panel, to energise the MAF alarm relay. When true, it will also  
cause the receiving panel to energise the bells relay (if the bells at the receiving  
panel are not isolated or silenced). See NOTE 1 below.  
2.  
MAF fault state.  
True if any non isolated MAF mapped zone or relay is in fault.  
When true, this will cause any panel on the network which is programmed to use the  
MAF data from this panel, to energise the MAF fault relay and, (if the receiving panel  
is an F3200 panel), to turn its buzzer on when a new fault occurs.  
3.  
4.  
MAF isolate state.  
True if any MAF mapped zone or relay is isolated. When true, this will cause any  
panel on the network which is programmed to use the MAF data from this panel, to  
energise the MAF isolate relay.  
MAF standby state.  
True if there is any "standby fault" present (e.g. all zones isolated). When true, this  
will cause any panel on the network which is programmed to use the MAF data from  
this panel to generate a system fault.  
Page 11-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 NETWORK PROGRAMMING MENU STRUCTURE  
FIGURE 11.1.1 F3200 NETWORK  
PROGRAMMING MENU STRUCTURE  
FOR V2.xx SOFTWARE  
FROM SYSTEM CONFIG  
19 MARCH 1999  
LT122P1.CFL  
5
8
6
4
3
7
1
2
NET CONFIG  
SID  
MAF  
NET CMDS  
FFCIF  
EVENTS  
NET VARIABLE  
STATUS  
1
2
3
ENABLED  
TX RATE  
FAST TX  
3
1
2
ENABLE  
TX REFRESH RATE  
MAX COS RATE  
2
3
1
1
TX EVENTS  
TX UPDATES  
TX RLY CTRLS  
TX CMD TEXT  
1
2
2
2
1
3
TX ISO/RESET  
TX TIME/DATE  
TX ACK  
TX EVENT TEXT  
RX NET ACK  
TX SID  
TX ALARMS  
3
SYS EVENT TEXT  
1
2
4
3
RX TIME/DATE  
ACK TIME  
WORK TIME  
NetMAF3  
1
NetMAF1  
1
NetMAF2  
1
2
2
COS RATE  
TX TIME  
BELLS CONTROL  
TX NET SILENCE  
RX NET SILENCE  
NetSID2  
3
NetSID1  
1
2
3
4
6
2
5
4
LINK RX  
LOG EVNTS  
RX FFCIF  
TX CMD  
RX CMD  
MAF RELAY  
MAF TOTALS  
STATUS SEARCH  
TRAILING FF  
SID #  
NetPg2  
1
NetPg1  
4
1
5
4
3
2
3
2
LOCAL SID #  
MODE  
NIC  
RX TIMEOUT  
TX DELAY  
ACK TIME  
DUP TIME  
LEADING FF  
NetPg4  
1
NetPg3  
1
2
4
2
3
4
5
3
ACK BROADCASTS  
BAUD RATE  
RETRIES  
SLOTS  
MODEB  
LINK RX TIME  
GROUPS  
LINK TX  
LINK TX TIME  
1
NetPg5  
ACK BROADCASTS TO SPECIFIC SID  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
NETWORK MAF STATUS (CONTINUED)  
5.  
6.  
7.  
System fault state.  
True if any system fault is present. When true, this will cause any panel on the  
network which is programmed to use the MAF data from this panel, to energise the  
MAF fault relay and, (if the receiving panel is an F3200 panel), to turn its buzzer on  
when a new fault occurs.  
Brigade test state.  
True if a brigade test has been initiated (by holding down the brigade test key for 2  
seconds) AND the local MAF alarm relay, (if any), is programmed to operate for a  
local brigade test. When true, this will cause any panel on the network which is  
programmed to use the MAF data from this panel, to energise the MAF alarm relay.  
Silence alarms state.  
True if the bells are isolated and the panel is programmed to send bells isolate as  
network silence. When true, this will cause any panel on the network which is  
programmed to use the MAF data from this panel AND is programmed to allow the  
receiving of network bells silence, to keep the bells off. For New Zealand operation  
this also includes the state of the silence alarms keyswitch.  
NOTE 1.  
In F3200 each zone may be individually mapped to MAF, BELLS, ANC1, and ANC2.  
However, the mapping of a zone to BELLS, ANC1 and ANC2 has NO effect on the MAF  
data transmitted on the network - it effects only the local relays on that panel. Mapping a  
zone to bells will cause the bells to turn on at the local panel of that zone but not at a remote  
panel. Mapping a zone to the MAF may cause the bells to turn on at a remote panel when  
the zone goes into alarm. Mapping a zone to ANC1/ANC2 will cause the respective ancillary  
relay to turn on at the local panel of that zone but not at a remote panel.  
At any F3200 panel, the MAF status and totals it is currently receiving from any other panel  
may be viewed by recalling net panel status ( from the base display press [RECALL]  
[RECALL] [3] - refer also to the F3200 operator's manual ).  
F3200 output logic tokens affected by network MAF status  
The output logic tokens in an F3200 panel that are affected by the MAF status received from  
other panels are listed below. These tokens are not affected by MAF status from another  
panel unless that panel is programmed into the SID list of this panel and has "use MAF relay  
data" option enabled (refer section 11.4.3).  
NML This token is described in Section 7.4.3.2 and is affected by any network states  
which cause the Brigade Alarm or Brigade Fault relays to operate at this panel. This  
includes MAF alarm, MAF fault or system fault received from a SID that this panel is  
programmed to use the MAF status of.  
BEL False if the bells are locally isolated or if  
[common network bells silence is true AND this panel has "receive network bells  
SILENCE" enabled], otherwise true if  
1.  
2.  
3.  
4.  
Local 5 second bells test occurring.  
2 second ring for alarm on local zone in auto reset mode.  
Alarm on any local non isolated zone mapped to bells  
Common network maf alarm AND "receive network bells CONTROL"  
enabled.  
5.  
Any entry in the FFCIF alarm queue and bells on for FFCIF alarm has been  
enabled with programming.  
Note: For New Zealand operation, BEL will become true if the trial evac keyswitch is  
operated regardless of bells isolation or silence alarms.  
Page 11-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
NETWORK MAF STATUS (CONTINUED)  
BLI  
-
true if the bells are isolated at this panel or if the bells are silenced from the  
network. A bells silence state received from a network panel will be applied  
at this panel if 1. “use maf status” is enabled at this panel for the remote panel  
and 2. this panel has “allow receive net bells silence” enabled. (Refer Section  
11.5.3).  
No other output logic tokens are affected by MAF status from other panels.  
11.2.3 PROGRAMMING METHODOLOGY  
1) SID designation  
A unique SID number (1-254) must be given to every fire panel and network accessory  
(PTM,NLDU,PMB etc). Numbering can be achieved in different ways, for example a multi-  
building senario.  
Each main FIP in each building could have a SID number starting with 10, 20, 30 etc. Every  
FIP in the same building could then be consecutively numbered after the main FIP, or  
perhaps a number which may signify the level in the building of which the FIP is located. (ie  
SID number 22 could mean the second slave FIP in building 2. The master FIP would be  
20)  
2) Group Membership  
Groups could be allocated on the basis of buildings, for example all units in one building are  
members of the same group. A printer in a building allocated as Group One will only print  
Group One events.  
Units can, if necessary, belong to more than one group, eg. there may be three independent  
groups for three buildings on site, but a unit in a site monitoring office can be a member of all  
three groups.  
To continue the example, the Group One printer prints only Group One events, but the site  
monitoring printer prints all events from Groups One, Two and Three.  
Units that receive the events are permitted to process them only if there is at least one group  
that the sender and receiver have in common.  
The groups concept also applies to Alarm annunciation on the F3200 LCD. An F3200 can  
be programmed whether to receive alarms from other FIPs on the network. If this is so, the  
F3200 will only display alarms from sending FIPs that have a Group common to the  
receiving F3200.  
For example, a building has 3 FIPs which are members of Group 7. Two are sub-FIPs,  
which only display alarms from any of the 3 FIPs in Group 7. The main FIP can display its  
own alarms, plus those of the other two. However, the main FIP could be programmed to  
also be a member of Group 4, thus alarms from a panel in Group 4, eg. another building,  
could be displayed on the main FIP's LCD.  
3) SID LIST programming  
Section 11.4 describes the programming of the SID list. Each SID on the network that this  
panel needs to know about must be programmed into the SID list of this panel. Determine  
what functions are to be performed by each SID and what information is to be shared by  
which SIDs. The SID list provides a number of options which can be enabled or disabled per  
SID. A master SID will probably have nearly all of these options set to YES, while a slave  
SID will probably have less options enabled.  
Issue 2.7  
5 July 2001  
Page 11-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
PROGRAMMING METHODOLOGY (CONTINUED)  
4) Determine whether acknowledge of broadcasts is to be enabled.  
Some of the messages transmitted on the network are "broadcast" i.e. not directed to one  
particular SID but to all SIDs. A single device on the network may be programmed to  
acknowledge these broadcast messages to provide some confirmation that the broadcast  
message was received by other devices. All non-broadcast messages are acknowledged by  
the SID that the message is directed to. Enabling acknowledge of broadcasts does increase  
the loading on the network.  
It is recommended that if an F3200 panel is to acknowledge broadcasts then it should be the  
most lightly loaded FIP on the network, taking into consideration the number of circuits,  
amount of output logic and the number of display boards. If a PTM protocol translation  
module), NLDU (network LED display unit), NDU (network display unit), or PMB (Panel-Link  
MODBUS bridge) is present then it is preferable to use one of them to do the acknowledging  
of broadcasts, rather than an F3200 panel.  
5) Determine NET MAF Configuration  
This allows a panel to send out its MAF status/totals to other panels, which may combine it  
with their own, and the status of other panels, to control a single brigade interface. MAF  
status is not controlled by network groups.  
6) Network Variable Setup  
Determine what information needs to be sent to other panels using network variables. If  
individual brigade signals are required per panel on the network then network variables can  
be used to transfer status.  
Page 11-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
11.3  
NETWORK CONFIGURATION MENU  
These configuration settings determine how the F3200 communicates with other panels on  
the network. In general, most settings should be left at default values. However, there may  
be some settings that need to be customised for some installations.  
The < and > keys allow movement between five menus NetPg1 through NetPg5.  
11.3.1  
NETPG1 OPTIONS  
1. SID: (1-254)  
This is the network address (SID number) of this F3200, allowing for the unique identification  
of zones, events, and for remote controls to be sent to this F3200. The SID for any device  
on the network must be a unique number between 1 and 254. It is recommended that all  
Fire Alarm Panels are numbered sequentially from 1 upwards, so as to make numbering  
consistent. This is because the SID is combined with the local zone number to form a  
network zone number.  
2. Mode : (Multidrop/Point to point)  
In general, this must be left as multidrop. In some special cases, point to point mode be  
may be selected, eg. a single F3200 connected to one other device. Point to Point mode  
requires a full duplex data path between this panel and one other device.  
3. NIC : (Yes/No)  
Is set to "Yes" only if another device on the network is configured to acknowledge  
broadcasts. Acknowledgment of broadcasts provides extra confirmation that a message  
sent has been received. Panel throughput is reduced as the F3200 must wait for an  
acknowledgement before it can transmit further messages. It is recommended that  
acknowledgement of broadcasts is enabled on the network. This means that every panel  
has the NIC option set to yes except for the panel doing the acknowledging (See NetPg4  
option 1, section 11.3.4).  
4. RX Timeout : (1-250)  
Number of 5 millisecond time periods of delay before a channel is assumed to be free.  
5. TX Delay : (1-250)  
Scaling factor for randomised delay before transmission. Measured in 5 millisecond time  
periods.  
11.3.2  
NETPG2 OPTIONS  
1. Ack time : (1-9999)  
Time to wait for Acknowledge before retransmission. Measured in 1 millisecond time  
periods.  
2. DUP time : (1-9000)  
Time during which duplicate messages are ignored. Measured in 1 millisecond periods.  
3. Leading FF : (0-250)  
Number of $FF preamble characters transmitted after asserting RTS, before sending a  
message.  
4. Trailing FF : (0-250)  
Number of $FF characters inserted after a message to ensure that the message is  
transmitted by the UART before RTS is deassserted.  
Issue 2.7  
5 July 2001  
Page 11-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.3.3  
NETPG3 OPTIONS  
1. Link TX : (Yes/No)  
This controls whether the F3200 sends Link Integrity messages. This should be enabled for  
every panel.  
2. Link TX time : (1-250)  
Time period (in seconds) between successive Link Integrity Transmissions from this SID.  
3. Link RX time : (1-250)  
Maximum time period (in seconds) permitted between the reception of successive Link  
Integrity messages from any SID, before generating Net Scan Fail events.  
4. Groups : ([12345678])  
This setting controls the usage of the following information types:  
- FFCIF Alarm Information  
- Network Event Information  
Groups can be used to limit where the information is printed out or displayed, for example an  
F3200 can belong to any combination of 8 groups, or none. The group data is sent out with  
alarm and event information, and panels receiving this information are able to process the  
data only if the sender is a member of at least one group that the receiving F3200 is a  
member of.  
If the group number is shown then this F3200 is a member of that group. Membership can  
be changed by pressing keys 1-8.  
11.3.4  
1.  
NETPG4 OPTIONS  
ACK broadcasts : (Yes/No)  
This selects whether this panel does the acknowledging of broadcasts or not. Only one  
device on the entire network should be programmed to do acknowledging of broadcasts.  
Refer also to section 11.3.1 item 3 (NIC). If acknowledge of broadcasts is enabled then all  
devices on the network should be programmed to expect acknowledge of broadcasts, which,  
in the case of F3200/NDU is the NIC option described in section 11.3.1.  
It is recommended that if an F3200 panel is to acknowledge broadcasts then it should be the  
most lightly loaded FIP on the network, taking into consideration the number of circuits,  
amount of output logic and the number of display boards.  
2.  
Baud rate.  
This sets the baud rate for the network. The choices are 300, 600, 1200, 2400, 4800, 9600  
and 19200 baud.  
3.  
Retries (0-250)  
This parameter sets the number of times a message will be retransmitted if an acknowledge  
is not received for it. After all attempts to transmit the message have been made, the  
message is discarded and a “Netmsg Discard” event is generated. If the device the  
message is being sent to has scan failed, then only one transmission of the message is  
done. For V2.08 or earlier software the maximum number of retries allowed was 15.  
4.  
Slots (8, 16, 32)  
There are only three allowable values for this parameter - 8, 16 or 32. When a panel wants  
to transmit onto the network it selects a random slot position from slot 1 up to slot 8/16/32  
depending on the maximum slot number set by this parameter. The greater the number of  
devices connected to the network, the greater the number of slots needed.  
Page 11-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
NETPG4 OPTIONS (CONTINUED)  
For 1-12 devices, select 8 slots  
For 13-24 devices, select 16 slots  
For 25 or more devices, select 32 slots  
5.  
Mode B  
This is a numeric value 0-7 which is used to control some of the network operations as  
follows. This value should be changed only under instruction from a systems engineer. For  
normal operation a value of 3 should be used.  
Early Collision Detection  
Values 0-3 enable early collision detection  
Values 4-7 disable early collision detection  
Message Combination  
Values 0, 4  
Values 1, 5  
Combine no messages  
Combine "ack" messages into a single network access with up to  
maximum of 10 ack messages combined.  
Combine application messages when possible. This includes  
combining MAF status, MAF totals, Netvars and Link Integrity A and  
B.  
Values 2, 6  
Values 3, 7  
11.3.5  
Combine both ACK messages and application messages.  
NETPG5 OPTIONS  
Ack broadcasts to specific SID  
1.  
If this parameter is set to a non-zero SID number XYZ then this panel will send an  
acknowledge to a broadcast sent by SID XYZ. If this parameter is set to zero then this  
feature is disabled.  
Only one device on a network (say SID XYZ), should be programmed to acknowledge all  
broadcasts but it can have its own broadcasts acknowledged if another panel on the network  
has "ACK broadcasts to specific SID" set to XYZ.  
Issue 2.7  
5 July 2001  
Page 11-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.4  
SID CONFIGURATION  
Up to 64 panels may be configured on the Panel-Link network, and each panel must have a  
unique SID (System Identification) number.  
In general, the SID number of every device on the network should be entered into the SID  
list of this panel and should have "Link RX" enabled (section 11.4.2). This allows this F3200  
to monitor all other devices on the network. Any device on the network which is not in the  
SID list of this panel will be completely ignored i.e. all messages received from it will be  
discarded and no messages will be sent to it.  
Hence, if a panel is not in the SID list, it's information cannot be used. It may be that some  
panels do not have every SID programmed into their SID list. For example, a system may  
have multiple slave devices which all appear in the SID list of a master panel but do not  
appear in the SID list of each others panels.  
On entry to the programming of the SID list the total number of SIDs currently in the SID list  
will be displayed.  
There are two ways of moving through the SID list. By pressing the 'NEXT' or 'PREV' keys  
you can step through the list of programmed SIDs, or by using the Up/Down arrow keys to  
move sequentially through the SID numbers 1-254. The number of a specific SID to be  
programmed may also be entered by selecting option 1 from either menu 1 or menu 2.  
Each SID has two configuration menus which can be scrolled through using the < or > keys.  
The DELETE key can be used to delete a SID from the list. The EDIT key can be used to  
display a menu which has options for setting or clearing all the settings for the current SID  
and for turning on or off the display of a full description of each item as it is being changed.  
Turning the full description display off allows faster programming.  
11.4.1  
SID MENU ONE  
1. SID : (1-254)  
Change the network SID number that is being viewed/modified.  
2. Link RX : (Yes/No)  
When enabled, the link integrity transmissions from the selected SID are monitored by this  
panel, and if no transmissions are received for a programmed length of time (section 11.3.3  
Link RX time) a system fault is generated. Link RX should be enabled in this panel for all  
SIDs that this panel needs to receive information from or wishes to monitor the presence of.  
3. Log events : (Yes/No)  
If yes, events received from the selected SID are logged to the local history queue and also  
to the local printer but will only be printed on the printer if event printing is enabled. Only  
certain types of events will be logged to the history and printer according to the programming  
of event type selections described in section 6.4.4.  
4. RX FFCIF : (Yes/No)  
If enabled, FFCIF Alarms received from the selected SID will be placed into the local FFCIF  
alarm list providing that the two panels have at least one common group. The remote SID  
must also be programmed to send FFCIF alarms. FFCIF alarms received from remote  
network panels do not get sent to local RZDUs - local RZDUs receive only alarms for zones  
local to this panel.  
Page 11-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
SID MENU ONE (CONTINUED)  
If the F3200 is programmed to receive FFCIF events from a particular SID, then it is also  
able to send Ack, Reset and Isolate commands for the event back to the originating SID  
(providing that reset and isolate of remote alarms is also enabled - refer section 11.7 FFCIF  
config).  
5. TX CMD : (Yes/No)  
If enabled this allows this panel to send commands to the selected SID. This includes zone  
reset/isolate/test commands as well as system commands such as system test/battery  
test/bell test. If disabled, this panel is still allowed to recall the status of zones from the  
selected SID but not control them.  
6. RX CMD : (Yes/No)  
If enabled this allows this panel to receive and execute commands from the selected SID. If  
disabled, commands received from the selected SID will be ignored but a recall of zone  
status will still be permitted. NOTE :- this option does not affect FFCIF commands received  
from another panel which will still be accepted, (if FFCIF TX alarms is enabled), even if the  
RX CMD option here is disabled. (refer also section 11.7 FFCIF configuration).  
11.4.2  
SID MENU TWO  
1. SID : (1-254)  
Change the SID number that is being viewed/modified.  
2. Use MAF relay data : (Yes/No)  
If enabled, MAF data received from the selected SID will be used by this panel i.e. combined  
with local MAF status and possibly MAF status of other SIDs and used to drive the brigade  
signalling etc. Refer to section 11.2.2 for a description of network MAF status.  
3. Use MAF totals : (Yes/No)  
If enabled, the totals received from the selected SID are included in the totals shown on this  
panel. If enabled, it also means that a non zero total received from the selected SID, (alarm,  
fault or isolate), will cause the corresponding LED on the front panel to turn on. Also, if  
enabled, the buzzer will turn on when a new MAF or system fault (as received in the MAF  
status) is received from the selected SID. The buzzer will turn on if "use MAF totals" is  
enabled even if "use MAF relay data" is disabled for the selected SID.  
4. Status search : (Yes/No)  
If enabled, a recall of off normal zones will include the selected SID in the search. If  
disabled, an off normal recall will not search the SID but specific zones from that SID may  
still be recalled using their network zone number.  
Issue 2.7  
5 July 2001  
Page 11-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.5  
NETWORK MAF CONFIGURATION  
As described in section 11.2.2, a panel will transmits its MAF status and totals onto the  
network for use by other panels, if programmed to. If both the “Refresh Tx Time” and the  
“Max COS rate” listed below are zero then this panel will not transmit MAF status.  
The MAF status and totals are transmitted at regular intervals, defined by the 'Refresh TX  
time'. If a change of MAF Status occurs the new MAF status will be transmitted immediately  
as long as the minimum time specified by 'Max Cos TX Rate' has elapsed since the last  
transmission of MAF status.  
If individual brigade signals are required per panel on the network, Network Variables can be  
used to transfer the status and to control the relays.  
The < and > keys allow movement between two menus named NetMAF1 and NetMAF2.  
11.5.1  
OPTIONS UNDER NETMAF1  
F3200 V2.07 or later software allows the following options to be set to zero. If both are zero,  
the panel will never send MAF status onto the network.  
1. Refresh TX time : (0-250)  
A value in seconds which specifies the rate at which a refresh of the network MAF  
status/totals of this SID should be transmitted onto the network.  
2. Max COS rate : (0-250)  
This is a value in seconds which specifies the maximum rate at which MAF status can be  
transmitted into the network. If set to zero then MAF status is sent according to the Refresh  
Tx time and is not sent for every change of state.  
11.5.2  
OPTIONS UNDER NETMAF2  
1. Receive net bells control : (Yes/No)  
If enabled, allows the local bell relay to operate when a MAF alarm occurs on another panel.  
The SID number of the remote panel must also be entered into the SID list of this panel and  
have "Use MAF relay data" enabled if a MAF alarm at the remote panel is to operate the  
bells at this panel.  
2. Send bell isolate as net silence : (Yes/No)  
If enabled will cause this panel to send a network silence state onto the network when the  
local bells are isolated. This can then silence the bells at any other network panel that has  
"Allow receive net bells silence" enabled (see Section 11.5.3) AND is programmed to use  
the MAF status of this panel.  
11.5.3  
OPTIONS UNDER NETMAF3  
1. Allow receive net bells silence. (Yes/No)  
If enabled, allows this panel to use a network silence state received from a remote panel to  
keep the local bells off (providing the remote panel also appears in the SID list of this panel  
and has "use MAF relay data" enabled). Hence, isolating the bells at a remote panel can  
cause it to transmit a network silence state which is received by the local panel and will  
cause the bells to remain off at the local panel.  
If disabled, any network silence state received from other panels is ignored.  
Page 11-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
11.6  
NET COMMANDS  
The Network Command configuration provides some parameters involved in the sending  
and receiving of commands to/from other devices on the network.  
When F3200 issues a command, it may take some time for the message to be sent on the  
network, processed by the receiver, and the response sent back. The length of time the  
F3200 will wait for the response is defined as the 'ACK time' (Net Command Acknowledge  
Delay Time). A device that is processing a command that cannot be replied to immediately  
will send a "response pending" message at a rate defined by the 'Work time'. This message  
indicates to the sender of the command that the command is still being processed, and the  
required response cannot yet be given. An F3200 receiving the response pending message  
will extend the time that it waits for the required response.  
1. ACK time : (1-250 seconds)  
Net Command ACK Delay Time. Length of time the F3200 will wait for a response before  
displaying an error message.  
2. Work time : (1-250 seconds)  
Command Work TX Time. If a message cannot be sent immediately a "response pending"  
message is sent at a rate determined by this. Work time should be less then ACK time.  
3. RX Time/Date : (Yes/No)  
If enabled, this allows this panel to process a "new time/date" command received from the  
network and to set its clock time/date from the time/date in the received message. If  
disabled, this panel will ignore new time/date command messages received. See also "TX  
time/date" below.  
For V2.07 or earlier software, the time and date received from another SID will be processed  
only if the SID appears in the SID list of this panel and has the “Rx commands” option  
enabled . V2.08 or later software do not require this.  
4. TX Time/Date : (Yes/No)  
If enabled, this panel will transmit (broadcast) a "new time/date" command onto the network  
at the following times.  
1.  
2.  
3.  
4.  
When the local time/date is set manually from the keypad.  
At 12 pm and 12 am every day.  
Whenever the local time is changed due to daylight saving.  
Whenever this panel receives a message indicating that another panel has just  
powered up.  
In all cases the time/date is broadcast onto the network and will therefore be received by all  
devices on the network, but whether each device uses the command to set its local  
time/date depends on the device type (i.e. F3200, F4000, PTM etc) and its programming.  
It is preferable, but not essential, that only one panel on the network (or network segment) is  
configured to transmit time/date. F3200 panels and NDUs with a MAF board maintain their  
local time very accurately (using 50 hz mains frequency), but an NDU without a MAF board  
has a less accurate local time clock and, if possible, should not be configured to transmit  
time/date onto the network.  
Issue 2.7  
5 July 2001  
Page 11-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.7  
NET FFCIF CONFIGURATION  
This determines whether FFCIF alarm events are sent onto the network, and can provide an  
extra level of confirmation that alarm events have been received by one or more devices on  
the network. FFCIF alarms sent onto the network will be entered into the FFCIF alarm list of  
another panel only if the panel sending the alarm has at least one group in common with the  
panel receiving the alarm (refer section 11.3.3 groups). For F3200 and NDUs the SID list  
programming also determines whether FFCIF alarms received from other panels are entered  
into the FFCIF alarm list of this panel.  
Alarms which are entered into the local FFCIF alarms list may be either local alarms or  
alarms which have come from other panels. In both cases, these alarms can be  
acknowledged from either the local panel or from a remote panel but it is possible to disable  
the acceptance of acknowledgments which come from remote network devices and to force  
all FFCIF alarms to be acknowledged locally - see item 3 "Remote ACK" below.  
If FFCIF auto ack is enabled, (refer section 6.4.4), any alarms which are entered into the  
local FFCIF alarm list (i.e. both local alarms and remote alarms) are automatically flagged as  
"acknowledged", but this does not result in any acknowledge indication or command being  
sent onto the network.  
Options under FFCIF1  
1. TX alarms : (Yes/No)  
If enabled, any FFCIF alarm that is entered into the FFCIF list of this panel will also be sent  
onto the network. Setting this to enabled also determines whether this panel accepts FFCIF  
commands from other panels to acknowledge, reset or isolate FFCIF alarms. NOTE :- an  
FFCIF command is not the same as a zone command. If FFCIF alarms are not being  
transmitted onto the network then FFCIF commands will not be accepted from other panels  
but zone/system commands etc. may still be accepted depending on the RX CMD option  
programmed in the SID list of this panel. Refer also section 11.4.2 SID list RX CMD option.  
Note, an FFCIF command is either an acknowledge, reset, or isolate command which is  
initiated when the associated ACK, RESET or ISOLATE key is pressed from within FFCIF  
mode i.e. when the FFCIF alarm list is being displayed. Zone commands or system  
commands are initiated using the ZONE or SYSTEM keys.  
2. Dedicated TX SID : (0-254)  
If this parameter is zero, then any FFCIF alarms that are transmitted onto the network, ( i.e.  
TX alarms enabled ), will be broadcast, (i.e. received by all devices on the network), and  
each device can individually decide, ( according to group programming and SID list  
programming), whether to enter that FFCIF alarm into its own FFCIF alarm list.  
If this parameter is non zero then FFCIF alarms will not be broadcast onto the network but  
will be sent specifically to the SID specified by this number. No devices on the network other  
than the specified SID will receive FFCIF alarms sent by this panel.  
If FFCIF alarms are broadcast onto the network, then confirmation of delivery can be  
provided by setting "acknowledge of broadcasts" enabled (refer section 11.3.1 NIC option).  
If FFCIF alarms are directed to one specific SID then that SID will acknowledge receipt of  
the alarm and acknowledge of broadcasts is not involved. If acknowledge of broadcasts is  
not enabled, (or this device is doing the acknowledge of broadcasts), and only one other  
device is required to receive FFCIF alarms from this SID, then it is preferable to set the "TX  
dedicated SID" parameter here to a specific SID number.  
Page 11-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
FFCIF CONFIGURATION (CONTINUED)  
3. Remote ACK : Yes/No  
If enabled, this allows alarms in the local FFCIF alarm list to be acknowledged by commands  
from remote network devices. If disabled, then any alarm which is entered into the local  
FFCIF alarm list must be acknowledged locally - this applies to both alarms generated by  
local zones and alarms which come from remote devices. If acceptance of remote  
acknowledgements is disabled (i.e. all alarms must be acknowledged locally), FFCIF  
commands, (or zone commands), to reset or isolate will still be accepted and a reset or  
isolate performed but the alarm will not be taken out of the local FFCIF alarm list until it has  
been acknowledged locally. The remote ack acceptance parameter here affects only  
commands coming from network devices and does not affect commands coming from local  
RZDU devices. Acceptance of acknowledgement from local RZDU devices can be enabled  
or disabled with a separate parameter described in section 6.4.4 (FFCIF mode).  
Options under FFCIF2  
1.TX iso/reset cmds  
If enabled this allows this panel to send FFCIF reset or FFCIF isolate commands to remote  
panels. The local FFCIF alarm list may contain alarms which were generated by alarms on  
local zones or alarms which originated from remote network devices. When an FFCIF reset  
or isolate command is initiated, (by pressing RESET or ISOLATE keys when in FFCIF  
mode), all acknowledged local alarms will always be reset or isolated but for acknowledged  
alarms which originated from remote network devices, a reset or isolate command will be  
sent to the remote network device only if this parameter is enabled.  
2.TX ack cmds  
If enabled this allows this panel to send FFCIF acknowledge commands to remote network  
panels to acknowledge alarms which originated from remote panels.  
When an FFCIF alarm is being displayed it can be acknowledged by pressing the ACK key.  
If the alarm originated locally, then the word "ACKD" will appear on the display and an  
"acknowledge indication" will be sent on the network and also sent to local RZDU devices. If  
the alarm originated from a remote network device then the word "ACKD" will appear on the  
display, (i.e. it will be flagged as acknowledged), and if the "TX ack cmds" parameter here is  
enabled then an acknowledge command will be transmitted onto the network to the device  
which originated the alarm.  
Issue 2.7  
5 July 2001  
Page 11-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.8  
NETWORK EVENT CONFIGURATION  
The network event parameters determine the transmission of event log information onto the  
network.  
When an event occurs, (e.g. zone isolate, zone alarm, system test fail etc.), the event is  
logged into the local history queue and printed on the local event printer (if event printing is  
enabled - refer section 6.4.4), and the event may also be transmitted onto the network if  
transmission of events is enabled. If an event is transmitted onto the network, some of the  
parameters here determine whether additional text data is included with the event.  
The event and it's text may be used by a network printer (e.g. PTM or NDU), network history  
logger, (e.g. an NDU or another F3200 panel), graphics display, or NLDU (network led  
display unit).  
If an NLDU is being used on the network to display zones from this panel, then transmission  
of events and events and event updates should be enabled, but an NLDU (LED display unit),  
does not need any of the text information. If events from this panel are to be logged into the  
history of a remote panel then transmission of events and all event text should be enabled  
but transmission of "event updates" is not required for remote history logging. Colour  
graphics displays require everything to be sent i.e. events, event updates and all text.  
Check with the user manuals of each particular device type on the network to find what  
information they require.  
To reduce the loading of the network, transmission of events, event updates or text should  
be disabled unless it is needed.  
Options under Events1  
1.Transmit events : (Yes/No)  
If enabled, on the occurrence of a new event, the event will be transmitted onto the network  
(as well as logged into local history).  
2.Transmit event updates : (Yes/No)  
Event updates are used to update the status of an object (e.g. zone), when the status has  
changed but has not produced a printable event. e.g. an alarm on an isolated zone does not  
produce a printable event but the status of the zone has changed. Colour graphics displays  
and NLDUs need updated zone status and hence transmission of event updates should be  
enabled if they are displaying status from this panel. Remote event printers or remote event  
history logging do not require event update transmission enabled.  
3. TX relay controls : (Yes/No)  
If disabled, activate and deactivate events for local module and ancillary relays will not be  
sent onto the network and hence will not be logged to the printer and history of any remote  
device. Other relay events such as isolate and fault will still be sent on the network.  
NOTE - relay events are always sent onto the network as zone events.  
Page 11-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
NETWORK EVENT CONFIGURATION (CONTINUED)  
Options under Events2  
1. Zone/relay cmd text tx : (Yes/No)  
If enabled, the text name of the zone or relay will be transmitted onto the network along with  
the event for zone/relay command event types. "Command" type events include isolate,  
deisolate, reset, alarm test, fault test, operate test, auto reset test.  
2. Zone/relay event text tx : (Yes/No)  
If enabled, the text name of the zone or relay will be transmitted onto the network along with  
the event for zone/relay non-command event types. These include zone alarm, zone fault  
and zone normal.  
3. Sys event text tx : (Yes/No)  
If enabled, the text associated with a system event will be included when the event is  
transmitted onto the network. An NLDU (LED display unit), does not require system event  
text, but remote event printers or remote event history loggers do require system event text.  
Issue 2.7  
5 July 2001  
Page 11-19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.9  
NETWORK LOGIC VARIABLES  
Network Variables can be used to transfer output logic status between panels for  
applications such as:  
(i)  
Fan controls.  
(ii)  
(iii)  
(iv)  
(v)  
Remote zone mimics.  
Transfer of zone alarm status between panels.  
Transfer of alarm status to a common Evacuation Panel interface.  
Transfer of brigade relay status for multiple brigade interfaces at one panel.  
An F3200 is always able to modify and use it's own network variables - this gives an extra  
128 Variables for use, but they should be used sparingly as processing of network variables  
takes longer than ordinary output logic variables.  
The local F3200 will only send it's own Network variables onto the network if 'TX enabled' is  
set to Yes. The transmit rate is programmed by "TX refresh rate". If a change of state  
occurs, the network variables will be transmitted immediately providing the minimum time  
specified by Max COS TX rate has elapsed since the last transmission.  
The "Max COS TX rate" should be less than the "TX refresh rate". Both times should be set  
so that an F3200 does not clog up the network with messages. The "Max COS rate" should  
be set to the longest time possible, taking into consideration the configuration of the panel.  
In general, the default settings should be adequate.  
1. TX enabled : (Yes/No)  
Enable sending of network logic variables onto the network.  
2. TX refresh rate : (0-255 seconds)  
Transmit refresh rate for network logic variables. A value of 255 for the TX refresh rate will  
result in the Netvar data being refreshed at the same rate as MAF status refresh (Section  
11.5.1), and the Netvar message will be transmitted in a single burst at the same time as  
MAF status and MAF totals messages. This also requires the "Mode B" parameter to be set  
to 3 (refer network configuration programming Section 11.3.4).  
3. Max COS TX rate : (0-250 seconds)  
Max rate on COS to transmit network logic variables.  
Page 11-20  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
11.10  
NET STATUS REFRESH  
The Network Status application provides a continual refresh of zone status onto the network.  
This information may be used for example, by colour graphics systems to display zone  
status.  
Enabling of the Network Status application is only necessary when there is a device on the  
network, eg. some colour graphics systems, that require this information. Otherwise, it  
should be left disabled, to reduce network traffic. Note that F3200s generate network status,  
but do NOT use it. Check with the user manuals of the other devices on the network to see  
if they require status refresh data to be sent from this panel.  
1. Status refresh enabled : (Yes/No)  
Determines whether this F3200 sends zone status data onto the network. If disabled, no  
refreshes or changes of status will be sent onto the network. However, the F3200 will still  
respond to requests for status from other devices on the network.  
2. TX rate : (0-250)  
A value in seconds which is the normal background refresh rate of status.  
3. Fast TX rate : (0-255)  
A value in seconds which is the faster background refresh rate. This is used when the  
F3200 first starts running, and whenever another device on the network requests a faster  
refresh, ie. the other device may be initialising.  
Issue 2.7  
5 July 2001  
Page 11-21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.11  
NDU OPERATION  
An NDU can be thought of as an F3200 FIP without any alarm zone modules or relay  
modules. An NDU also has an option of MAF board present/not present.  
An NDU can be programmed to operate in “New Zealand” mode rather than the default  
Australian mode. New Zealand mode operation is described in Chapter 12.  
An NDU without a MAF board is physically quite small, convenient to use, and is powered  
from an external source. An NDU with a MAF board may perform brigade signalling  
functions and also has ancillary and bell relays.  
Even though an NDU does not have any 8 zone or 8 relay modules, it does have 16 alarm  
zones. The local MCP (or connected RDU MCP), if any, may be mapped to any one of  
these 16 zones. Each of the 16 zones may be isolated, de-isolated, or reset, but cannot be  
tested. Each zone can be programmed as latching/non-latching, MAF/non-MAF, etc. Even  
though an NDU zone which does not have an MCP mapped cannot go into alarm, it may be  
useful as an object which can be isolated or de-isolated.  
Otherwise an NDU will perform all the functions of an F3200 panels, including  
sending/receiving network zone commands, network event printing, and FFCIF alarm  
display.  
An NDU may be programmed with output logic, the same as F3200, and may send and  
receive network logic variables on the network.  
An NDU without a MAF board may still perform functions of Bells or Ancillary Relay  
Isolate/De-Isolate/Test, and the output logic tokens associated with these may be used so  
that these conditions can be accessed from other panels.  
An NDU without a MAF board may be used to do Bells Isolate operation, and, with  
appropriate programming, may be used to silence the bells throughout the network, or it can  
be used just to display the Bells Isolate/Network Silence state of the network.  
The keypad on an NDU without a MAF board is physically accessible all the time, but when  
the cabinet is locked the NDU software disables the keypad even though the keypad is  
physically accessible.  
The operation of the Bells Isol and Ancil Isol keys may be disabled as described in Section  
6.4.4.  
Section 4.1.1 of the F3200 Operator’s Manual describes the interpretation of the front panel  
LEDs on an NDU.  
If an NDU is programmed to use the totals sent by another device on the network, then the  
NDU will turn its buzzer on if a new MAF fault, Standby condition or new System fault occurs  
on the remote device.  
Programming an NDU  
All of the programmable network parameters listed in Table 6.4.1 Chapter 6 and section  
11.13 are relevant to an NDU with the following points to note.  
MAF board present/not present  
The MAF board must be programmed as present or not present. This is done by selecting  
System Config from the main programming menu and then option 3:Modules.  
Page 11-22  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
NDU OPERATION (CONTINUED)  
Network setup  
The parameters for Link TX time, Link RX time, groups etc should be programmed as for a  
standard F3200.  
Network SID configuration.  
All 8 items that can be enabled per SID are relevant to an NDU and should be enabled or  
disabled as necessary.  
Network MAF config  
The MAF status transmitted onto the network by an NDU may include alarm, isolate, fault,  
brigade test, system fault, standby, and silence alarms.  
Network command config  
An NDU may send and receive commands on the network such as system tests, zone tests,  
zone isolate/deisolate etc. All of the commands described in the F3200 Operator's Manual  
apply to an NDU except that an NDU has no open collector outputs or module relays.  
FFCIF config  
This operates the same as F3200.  
Network Event Config  
An NDU may transmit events, event updates and text.  
Network Variable Config  
An NDU may send and receive output logic network variables.  
Network Status Config  
An NDU may have transmission of network status refresh data enabled, if desired, and this  
will cause it to transmit the status of its local zones which include alarm zones 1-16, bells,  
ancillary relays, and plant isolate zones.  
Issue 2.7  
5 July 2001  
Page 11-23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
11.12 DEFAULT VALUES FOR PANEL-LINK VARIABLES  
Item  
Parameters  
Default  
Network Setup  
Local SID Number  
Mode  
1-254  
Multidrop/Pnt to Pnt  
Yes/No  
0
Multidrop  
No  
NIC  
RX Timeout  
TX Delay  
ACK Time  
DUP Time  
Leading FF  
Trailing FF  
Link TX  
1-250 5 millisecs  
1-250 5 millisecs  
1-9999 millisecs  
1-9000 millisecs  
0-250 characters  
0-250 seconds  
Yes/No  
2
1
800  
2000  
1
1
Yes  
Link Tx Time  
Link RX Time  
Groups  
1-250 seconds  
1-250 seconds  
Any combination of 1  
to 8  
5
50  
[12345678]  
ACK Broadcasts  
Baud rate  
Retries  
Slots  
Mode B  
Yes/No  
300 up to 19200  
0-15  
8, 16, 32  
0-7  
No  
9600  
5
8
3
0
ACK Bcasts Specific SID  
0-254  
Network SID Configuration (per SID)  
Link RX  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
No  
No  
No  
No  
No  
No  
No  
No  
Log Events  
RX FFCIF  
TX CMD  
RX CMD  
Use MAF data  
Use MAF totals  
Status search  
Network MAF Config  
Refresh TX Time  
Max COS rate  
1-250 seconds  
0-250 seconds  
20  
2
Receive net bells  
control  
Send net silence  
Receive net silence  
Yes/No  
Yes/No  
Yes/No  
No  
No  
No  
Network Command Config  
ACK Time  
Work Time  
RX net time/date  
TX net time/date  
1-250 seconds  
1-250 seconds  
Yes/No  
10  
3
Yes  
No  
Yes/No  
FFCIF Config  
TX Alarms  
Dedicated TX SID  
RX Net ACK  
TX iso/reset cmds  
TX ack cmds  
Yes/No  
0-254 (0=all)  
Yes/No  
Yes/No  
Yes/No  
No  
0
No  
No  
No  
Page 11-24  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Network Programming  
Item  
Parameters  
Default  
Network Event Config  
Transmit events  
Transmit event updates  
Transmit relay operates  
Zone/Relay cmd text tx  
Zone/Rly event text tx  
System event text tx  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
Yes/No  
No  
No  
No  
No  
No  
Yes  
Network Variable Config  
TX enabled  
TX Refresh Rate  
Max COS TX rate  
Yes/No  
0-255 seconds  
0-250 seconds  
No  
20  
5
Network Status Config  
Refresh enabled  
TX Refresh Rate  
Fast TX rate  
Yes/No  
0-250 seconds  
0-250 seconds  
No  
23  
7
Issue 2.7  
5 July 2001  
Page 11-25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Network Programming  
Document No: LT0122  
THIS PAGE INTENTIONALLY LEFT BLANK  
Page 11-26  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
CHAPTER 12  
NEW ZEALAND OPERATION  
Issue 2.7  
5 July 2001  
Page 12-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
12.1  
GENERAL  
New Zealand mode operation may be enabled on an NDU but not on an F3200 fire panel.  
An NDU with New Zealand mode enabled may be connected to a Panel-link network of  
panels which also have “New Zealand” mode enabled. The NDU may be used with or  
without a MAF board, and optionally with a NZ Display Extender board. The NDU may not  
have any RZDU or RDU connected to it.  
If a MAF board is used, the NDU may be used as the main brigade connection point of the  
network. The MAF board has relays for signalling alarm (normally energised), fault (normally  
de-energised) and standby (normally energised and normally wire-ORed with fault). The  
MAF board also provides a supervised BELL relay, two supervised ancillary relays, and an  
“isolate” relay; all of which can be controlled by output logic if desired.  
12.2  
NZ DISPLAY EXTENDER BOARD  
The New Zealand extender board, if fitted, is added to the end of the 16 zone LED display  
board chain (if any), and provides the common Normal, Defect, and Fire LEDs, as well as  
other New Zealand specific inputs and outputs.  
The last 16 zone LED display board must have link Lk1 not fitted. If there are no 16 zone  
LED display boards then the New Zealand display extender board is connected directly to  
J13 on the Controller.  
The New Zealand Display Extender board has the following inputs and outputs.  
Inputs (all active low)  
Trial Evac/Sprinkler operated (shared)  
Silence alarms  
External defect  
Lamp test  
Services restore  
Brigade test/brigade isolate (shared)  
Evac defect  
Outputs  
Fire LED  
Defect LED  
Normal LED  
Ancil defect  
Ancil fire  
Lamp  
Evac Defect/External Defect  
The Defect and External Defect inputs may be programmed as to whether a defect is  
signalled for them or not. If defect is not signalled then they can be used as general purpose  
inputs accessible in output logic.  
Page 12-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
DISPLAY EXTENDER BOARD (CONTINUED)  
Services Restore  
When the Services Restore input is activated, the BSR logic token is set true and this can be  
used in output logic to turn outputs off or on if necessary.  
Trial Evac  
When the Trial Evac input is activated, the Bell relay is energised and the BEL logic token is  
set true regardless of any silence alarms or bells isolate condition. By default, Ancillary 3  
relay is the bell relay. The Ancillary 3 relay (or any relay), can be controlled with output  
logic. The TEV logic token can be used to get an output to operate when Trial Evac is  
asserted, however, when outputs are controlled this way, isolation of the output overrides  
Trial Evac which contravenes NZS4512. It may be necessary to program such relay outputs  
as non-isolatable – refer to section 7.5 Relay outputs.  
Silence Alarms  
When the silence alarms input is activated, the Bell relay is de-energised and the BEL logic  
token is set false unless trial evac is asserted.  
Brigade Test/Brigade Isolate  
These conditions share the same input and when true, result in an “abnormal” system state  
(but defect is not signalled) that can be recalled with a system fault recall.  
Lamp Test  
This input can be used to test all the LEDs including the front panel LEDs, the LEDs on the  
New Zealand Display Extender board, the index lamp and any 16 zone LED display boards.  
The New Zealand Display Extender board is connected to a PA0483 termination board. The  
termination board wiring connections are shown in Fig 12.2.1 below.  
I/O 01  
I/O 02  
I/O 03  
I/O 04  
I/O 05  
I/O 06  
I/O 07  
I/O 08  
I/O 16  
I/O 15  
I/O 14  
I/O 13  
I/O 12  
I/O 11  
I/O 10  
I/O 09  
SPARE-  
ANC DEF-  
ANC FIRE-  
FIRE-  
SPKLR OP-  
TRIAL EVAC-  
SIL ALMS-  
0V  
EXT DEF-  
PA0483  
DEFECT-  
NORMAL-  
LAMP-  
LAMP TEST-  
BRIG ISOL/TEST-  
BSR-  
+V  
EVAC DEF-  
LAMP+  
FIG 12.2.1  
NEW ZEALAND EXTENDER TERMINATION BOARD  
Issue 2.7  
5 July 2001  
Page 12-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
12.3  
MANUAL CALLPOINT (MCP)  
An NDU with a MAF board may have an MCP connected to the MAF board (refer Fig 12.3.1  
for wiring).  
An NDU without a MAF board may have an MCP connected to screw terminals 3 and 4 of  
standalone connector J5 on the Controller board as shown in Fig 12.3.2.  
The MCP is disabled by default. To enable it, it should be mapped to one of the 16 alarm  
zones (1-16) on the NDU. To map the MCP to a zone, select option 3:Global data from the  
main programming menu, then option 2:FIP MCP.  
The zone the MCP is mapped to can be programmed with a name, whether it is  
latching/non-latching, maf/non-maf, etc (refer to Fig 7.1.1B for zone options). If the zone is a  
status-only zone, then the MCP input can be used as a general purpose input, and its status  
can be accessed in output logic by using the zone status tokens (ZnA, ZnF, ZnW, and ZnI)  
of the zone it maps to.  
There is a one second delay applied to any change of state on the MCP input. If the zone  
the MCP maps to is a MAF zone then a brigade alarm will result after this time delay.  
MCP  
+ J6-3  
C
NC  
To connector J6 on  
the MAF/PSU board  
RESISTOR  
2K7  
- J6-4  
FIG 12.3.1  
NZ MODE MCP WIRING FOR NDU MAF BOARD  
MCP SWITCH NORMALLY CLOSED  
+ J5-3  
C
NC  
“STANDALONE” Connector  
J5 on the Controller  
RESISTOR  
10K  
- J5-4  
FIG 12.3.2  
NZ MODE MCP WIRING FOR “SLIMLINE” NDU  
Page 12-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
12.4  
PROGRAMMABLE OPTIONS  
There are a number of parameters that need to be set for New Zealand operation according  
to the installation requirements. These are detailed below.  
Fig 6.1.2D2 shows that they are accessed by selecting option 3:Global data, then 5:more,  
4:more, 4:more, then 4: New Zealand options.  
A database re-initialise will select New Zealand mode by default if a New Zealand Display  
Extender board is fitted. If a New Zealand Display Extender board is not fitted, New Zealand  
mode must be programmed manually.  
New Zealand Mode Programmable Parameters  
1. New Zealand mode – enable/disable  
When this parameter is enabled, the user is asked whether a number of other  
parameters (detailed below) should automatically set to their New Zealand mode  
settings. When this parameter is changed from enabled to disabled, the values of a  
number of parameters are set back to non-New Zealand mode settings.  
2. New Zealand Display Extender board fitted – Y/N  
If a New Zealand Display Extender board is fitted, this should be set to Y.  
3. Battery Very Low = Alarm – Y/N  
If this is enabled, a brigade alarm will be signalled on power-up or whenever the supply  
voltage reaches the battery very low threshold. The bells are not activated for this alarm.  
4. Evac Defect is fault – Y/N  
External defect is fault – Y/N  
These two parameters select whether the corresponding input on the New Zealand  
Display Extender will result in a defect (fault) being signalled when the input is asserted.  
If sent to N then the input is available as a general purpose input, the state of which can  
be accessed using the logic tokens NEV and NED respectively.  
5. Battery testing & monitoring  
There are four parameters, that for an NDU with no MAF board only the battery low  
monitor parameter needs to be set – the others are “don’t care”.  
(a) Battery low monitor – enable/disable  
For an NDU with a MAF board, this should be enabled. If enabled, then when the  
supply voltage falls below the battery low threshold a defect will be signalled.  
For an NDU with no MAF board, if this option is enabled then a defect is signalled  
when the supply voltage falls to the battery very low threshold.  
(b) Battery connection check – enable/disable  
This is enabled by default. When enabled, the battery connection is checked every  
28 seconds by reducing the charger voltage for 500 milliseconds and monitoring the  
battery voltage.  
(c) Hourly battery test  
This is disabled by default and is not required for New Zealand operation. When  
enabled, every hour the charger voltage is reduced for 60 seconds to check the  
battery voltage.  
Issue 2.7  
5 July 2001  
Page 12-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
PROGRAMMABLE OPTIONS (CONTINUED)  
(d) Daily battery test  
This is enabled by default. When enabled, every 24 hours (beginning at the auto test  
start time) the charger voltage is reduced for 40 minutes and the battery voltage is  
monitored.  
Parameter Defaults for New Zealand Mode  
The following is a list of the values set when New Zealand mode is enabled by a database  
re-initialise or when New Zealand mode is manually enabled.  
New Zealand Display Extender fitted  
Battery very low alarm  
Evac defect is fault  
External defect is fault  
Battery low monitor  
Battery connection test  
Hourly battery test  
Daily battery test  
Charger fault monitoring  
Mains fail = fault after 8 hours  
MCP  
Alarm buzzer  
Zone and system fault buzzer  
Daylight saving start and end time  
- as appropriate  
- disabled  
- enabled  
- enabled  
- enabled  
- enabled  
- disabled  
- enabled  
- disabled  
- disabled  
- disabled  
- enabled  
- disabled  
- enabled  
The daylight saving start time for New Zealand is set to 2am on the first Sunday in October  
and the end time is set to 2am on the third Sunday in March.  
12.5  
LOGIC TOKENS  
The full list of logic tokens is given in Section 7.4.3.2. Logic tokens that are valid only in  
New Zealand mode are:  
NSA local silence alarms (this does not include any received network bells silence  
State – refer BLI).  
TEV Local trial evac operated.  
BSR Local services restore operated.  
NEV Evac defect input asserted.  
NED External defect input asserted.  
Page 12-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
12.6  
SYSTEM STATES & INDICATIONS  
Faults, alarms and system faults can be recalled using the Recall key.  
A recall of system faults will display in addition to system faults, any system states (such as  
trial evac) that are present.  
The bells isolate LED flashes at 2Hz when the local silence alarms switch is activated,  
flashes at 1Hz when the bells are silenced by a bells isolate or silence alarms at some other  
panel, and is on steady when the bells are isolated locally.  
Door Interlock Buzzer  
If the door is closed when any of the brigade isolate/test, services restore, trial evac, silence  
alarms inputs are asserted, or the bells are isolated locally, or the database is write enabled,  
then the buzzer sounds a unique cadence to warn the user.  
Abnormal Conditions  
The NDU sends a state of "abnormal" on the network when it has any local off normal  
condition.  
The common normal LED on the NZ Display Extender Board is off and the NML logic token  
is false whenever any of the following are true.  
1. There is any local abnormal condition (refer below).  
2. There is a "local" abnormal condition at any panel on the network that the NDU is  
programmed to "indicate for" i.e any panel in the SID list of the NDU with the "use MAF  
relay data" option enabled.  
3. There is any off normal total in the list of totals shown on the base display of the NDU.  
This includes any off normal totals that come from other panels on the network that the  
NDU is programmed to show totals for. i.e any panel in the NDU SID list that has the  
"use MAF totals" option enabled.  
Local Abnormal Conditions  
The conditions that generate local abnormal are:  
1.  
2.  
Any alarm, fault or isolate state on any of the NDUs 16 zones that are not "Status  
Only".  
Any fault or isolate state on any of ancillary 1, ancillary 2 or bells relays on the  
MAF/PSU board.  
3.  
4.  
5.  
6.  
7.  
When the "plant" is isolated i.e. when the logic token PLI is true.  
When the bells are locally isolated.  
When there is a latched battery very low alarm state.  
When the panel is in program mode or the database is write enabled.  
When any of silence alarms, trial evac, services restore, brigade isolate or brigade test  
are locally operated.  
8.  
When there is any battery, mains or charger fault. Battery faults include battery low,  
battery connection and battery capacity faults. This does not include failure of a  
manual battery test.  
9.  
When there is a battery very low state and battery very low alarm is disabled.  
10. Evac defect or external defect true if enabled to be fault.  
Issue 2.7  
5 July 2001  
Page 12-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
SYSTEM STATES & INDICATIONS (CONTINUED)  
11. An off normal state is indicated (also defect) for approximately 10 seconds after any  
restart of the panel.  
12. When there is a "link integrity" fail for any network SID that this panel is monitoring or  
when the NDU does not receive an acknowledge to a message it transmits on the  
network to a SID that is supposed to be responding.  
13. When there is a shift register bus fault.  
14. When there is a fault with the "LCD".  
15. When there is a fault with the non volatile RAM on the clock chip.  
16. When there is a database (EEPROM) checksum error.  
17. When the MAF/PSU module is not connected if it is required or connected when not  
required.  
18. When there is a fault with the keypad connection.  
19. When there is a fault with the LED display board connection. e.g. NZ display extender  
board or 16 zone LED display board not present when required or connected when not  
required.  
20. When there is an EPROM checksum error.  
21. When the main system RAM fails.  
22. When all 16 zones on the NDU are isolated and "all zones isolated" is programmed as  
being a fault.  
23. When an error occurs in the execution of output logic e.g. invalid logic token or  
accessing a network variable for a network panel whose SID number does not appear  
in the SID list of the NDU (this fault will occur immediately upon exit from program  
mode).  
24. When a fuse on the MAF/PSU board is blown.  
25. When the IC that drives the network serial port does not store its programmed settings  
correctly. This could occur if the IC was not installed.  
26. When an RZDU is connected that is not required.  
27. When the panel is not powered up or is continually restarting or not executing its ROM  
program correctly.  
12.7  
NETWORK PARAMETER PROGRAMMING  
Chapter 11 of this manual (LT0122) describes the network parameters that can be  
programmed in an NDU.  
The network parameters of particular importance for an NDU in NZ mode are:  
1. The SID list (Section 11.4 – SID configuration).  
2. Network MAF configuration (Section 11.5).  
3. Network FFCIF configuration (Section 11.7).  
Page 12-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
12.7.1  
THE SID LIST  
Normally, all other panels on the network are entered into the SID list of the NDU, with 8  
options able to be set for each panel.  
If the NDU is the brigade connection point of the system, then probably all 8 options will be  
enabled for every SID in the list. When the option “use MAF relay data” is enabled for a SID,  
the NDU will signal the brigade for faults and alarms received from that SID.  
Even if the NDU is not the main brigade connection point of the system, it may still need to  
have the “use MAF relay data” option enabled for SIDs in its SID list for the following  
reasons.  
1. To signal alarm and defect on the New Zealand Display Extender board LEDs and  
outputs when an alarm or defect occurs on another panel.  
2. To control the NDU bell relay, if any, for an alarm or trial evac condition on another  
panel.  
3. To display the network bells silence state by flashing the bells isolate LED.  
The most situations, the NDU should have the “use MAF totals” option enabled for each  
panel in the SID list that it has “use MAF relay data” enabled.  
The “RX FFCIF” option should be enabled in the SID list for any panel that the NDU is to  
display FFCIF alarms for.  
12.7.2  
NETWORK MAF CONFIGURATION  
Section 11.5 of this manual describes these options:  
1. “Receive net bells control”  
This option should be enabled if the NDU bell relay is to operate when a MAF alarm or  
Trial Evac on another panel is to operate the bell relay at this panel.  
2. “Send bell isolate as net silence”  
This option, if enabled, means that a local bells isolate state is sent onto the network as  
network bells silence and also that a defect is signalled for bells isolate. If this option is  
disabled, a defect is not signalled for bells isolate. When the local silence alarms  
keyswitch (if any) is operated, a network bells silence state is always sent on the network  
regardless of the “send bell isolate as net silence” parameter.  
3. “Allow receive net bells silence”  
This option must be enabled if the NDU is to keep its alarm bells (if any) off in response  
to a network silence state sent from another panel.  
12.7.3  
NETWORK FFCIF CONFIGURATION  
Section 11.7 of this manual describes the options for this. The Tx alarms option should be  
enabled if the NDU should send an FFCIF alarm on the network when its local MCP zone  
goes into alarm.  
Issue 2.7  
5 July 2001  
Page 12-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
12.8 INSTALLATION : NZ DISPLAY EXTENDER BOARD  
& BRIGADE DISPLAYS  
12.8.1  
GENERAL  
An NDU is not normally used as a brigade connection point. If an NDU is used as a brigade  
connection point then, in general, a separate display panel must be provided if there needs  
to be zone alarm indication to the attending Fire Brigade staff. The common MAF status  
display is provided by mounting an NZ Display Extender Board (PA0499 or PA0762), in the  
NDU cabinet and wiring to display in a separate cabinet in one of three different ways as  
shown in Fig 12.8.1, 12.8.2, and 12.8.3.  
Sixteen-zone display boards are not normally connected to an NDU, but the three diagrams  
show how they can be connected if necessary. An NDU allows a maximum of four 16-zone  
display boards and each individual LED (48 LEDs per board) must be controlled using output  
logic which is generally too cumbersome for normal use.  
The second cabinet is necessary because the LEDs mounted inside the NDU cabinet do not  
meet the requirements of NZ4512 with regard to visibility and viewing access. An NLDU  
(Network LED Display Unit), can often be used to more conveniently drive 16-zone display  
boards and show individual zone information as part of the brigade mimic display.  
Any Ancillary Control Zone indicators on this external display must be coloured differently or  
be segregated from the zone alarm and common indicators, and be clearly labelled.  
There are several methods for providing a separate display panel. Two approaches are  
detailed below.  
NOTE 1:  
NOTE 2:  
The information provided here is very similar to the information in the RDU  
installation manual LT0148 which may be useful to refer to.  
As stated above, 16 zone display boards are not normally connected to an  
NDU, nevertheless, the following sections describe how to do it if necessary.  
If an NLDU is used to drive 16 zone display boards, then the NLDU user  
manual LT0188 must also be referred to.  
12.8.2  
MIMIC DISPLAY  
A mimic display uses the mimic outputs from the NDU’s internal 16 Zone LED Indicator  
Boards to drive alarm LEDs in an external display. Each group of 16 zone alarms and the  
common indicators are extended in a separate 26 way FRC to the external display.  
The number of FRCs between the NDU and the external display limit the practical separation  
distance. Since the cabling is not supervised in any way, the Fire Service or approving  
authority may place restrictions on this distance. The cable must be well protected  
mechanically by conduit, trunking or equivalent.  
These parts are available for constructing displays of this type:  
FP0475  
FZ3031  
LM0044  
LM0045  
FP,16 ZONE LED DISPLAY EXTENDER KIT (C/W LOOM)  
16 ZONE LED DISPLAY EXTENDER KIT, RHS POSITION  
LOOM, DISPLAY EXTENDER FRC,2M,26 WAY  
LOOM, DISPLAY EXTENDER FRC,5M,26 WAY  
(Longer and 3-way looms can be made to special order)  
Page 12-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
MIMIC DISPLAY (CONTINUED)  
LM0092  
PA0483  
PA0499  
PA0769  
LOOM, CONTROLLER TO FIRST DISPLAY, 1.2m  
PCB ASSY, IOR UNPROTECTED TERMINATION BOARD  
PCB ASSY, NZ DISPLAY EXTENDER BOARD  
PCB ASSY,16 O/P MIMIC TERMINATION BOARD,C/W RESISTORS  
(As for PA0483 but 3k3 resister per output)  
PA0753  
PA0760  
PCB ASSY,PICTURE FRAME DISPLAY,16 LED MIMIC,24V  
PCB ASSY,NZ DISPLAY EXTENDER,PFD MIMIC  
Suitable cabinets for Mimic Displays include:  
ME0073  
ME0074  
ME0076  
PICTURE FRAME DISPLAY,F/S, EMPTY,003 LOCK,C/W INDEX  
PICTURE FRAME DISPLAY,F/S,EMPTY,60124 LOCK,C/W INDEX  
PICTURE FRAME DISPLAY,R/S,EMPTY,60124 LOCK,C/W INDEX  
or various FP1600/OMEGA 64 empty cabinets and the PA0787 FP1600 Mimic Display  
Board provide an alternative format.  
At the display panel there are two possibilities:  
(i)  
Geographic Plan Mimic - the FRCs from the NDU are connected to Termination  
boards (PA0483). Individual LEDs with series resistors are mounted on the display  
panel and wired to these Termination boards. Figure 12.8.1 shows this arrangement.  
Alternatively, the PA0769 Termination Board has 3k3 resistors already fitted (gives  
7mA LED current which is adequate for interior use).  
(ii)  
Column Format - where arrangement of zone alarms into columns is acceptable,  
LED Mimic Display boards can be used. This simplifies the wiring considerably.  
The Picture Frame Display (ME0074 or ME0073 Front Service, or ME0076 Rear  
Service) is a suitable cabinet, and also has mounting hardware for four 16 zone  
Display mimic boards (PA0753), plus one Common Indicator and Index Lamp Mimic  
board (PA0760). Figure 12.8.2 shows this arrangement.  
Note that a special 3-way FRC is required for the Display Extender board, so that the  
miscellaneous inputs are accessible in the NDU cabinet. This is not a standard part,  
and will need to be made up to suit the application.  
12.8.3  
ACTIVE DISPLAY  
An active display is driven from the NDU display chain and is economical for large mimics.  
The Picture Frame Display (PFD) cabinet is suitable for housing an active display with a 12  
way shielded cable linking it to the NDU (ref. Figures 12.8.3 and 12.8.4). No supervision  
requirements for this cable are specified in NZS 4512, but because some individual wires in  
the cable are not supervised (though the cable as a whole is), good fire alarm practice  
dictates that the distance between the panel and indicating unit should be limited for  
principal brigade mimics. The wiring should also be well protected by conduit, trunking or  
equivalent. An electrical limit of 30 metres applies to this connection.  
The following parts are available for constructing displays of this type:  
PA0742  
PA0741  
PA0754  
FP0646  
PFD NZ DISPLAY EXTENDER BOARD,24V  
PFD DISPLAY 16 ALARM LED,24V (ALARM LEDS ONLY)  
PFD 16 ZONE,FULL STATUS,24V (ALL LEDS)  
16 ZONE ALARM KIT (PA0741,FRC LOOM,POWER LEADS)  
Issue 2.7  
5 July 2001  
Page 12-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
ACTIVE DISPLAY (CONTINUED)  
FP0678  
PA0772  
PA0483  
LM0056  
LM0046  
LM0092  
16 ZONE FULL STATUS KIT (PA0754,FRC LOOM,POWER LEADS)  
PFD TERMINATION BOARD (FRC TO MULTICORE)  
UNPROTECTED TERMINATION BOARD  
LOOM,DISPLAY EXTENDER FRC,1.4M,26 WAY  
LOOM, DISPLAY EXTENDER FRC,0.5M,26 WAY  
LOOM,CONTROLLER TO FIRST DISPLAY,1.2M  
ME0073  
ME0074  
ME0076  
PICTURE FRAME DISPLAY,F/S,EMPTY,003 LOCK,C/W INDEX  
PICTURE FRAME DISPLAY,F/S,EMPTY,60124 LOCK,C/W INDEX  
PICTURE FRAME DISPLAY,R/S,EMPTY,60124 LOCK,C/W INDEX  
A PA0772 PFD Termination Board is mounted in the NDU cabinet and in the PFD.  
12.8.4 DISPLAY EXTENDER BOARD MISCELLANEOUS TERMINATION  
The miscellaneous signals available through a NZ Display Extender Board are accessible  
via a 26 way FRC and PA0483 unprotected termination board. A termination pin out  
diagram is given in Fig 12.8.5. Refer to section 3 for electrical specifications of these  
signals, and to section 12.2 for their logical functions.  
Page 12-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
NDU Cabinet  
External Mimic Display Cabinet  
Note: 16 zone  
display boards are  
not normally  
connected to an  
NDU.  
Wiring to individual  
Zone LEDs with  
series resistors  
To NDU  
controller Bd.  
J13  
etc  
All shaded cables 26 way FRC.  
The first cable from the NDU Controller must be LM0092 (FZ3031 kit)  
FIG 12.8.1 - REMOTE PLAN MIMIC DISPLAY  
Issue 2.7  
5 July 2001  
Page 12-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
NDU Cabinet  
(Special 3 Way cable)  
16 Zone  
Display  
Board  
PA0454  
(FP0475  
including  
FRC  
)
Note: 16 zone  
display boards are  
not normally  
connected to an  
NDU.  
16 Zone  
Display  
Board  
PA0454  
(FP0475  
including  
FRC  
)
To NDU controller Bd.  
J13  
Etc.  
All shaded cables 26 way FRC.  
The First cable from the NDU controller must be LM0092 (FZ3031 kit).  
FIG 12.8.2 - REMOTE MIMIC USING PICTURE FRAME DISPLAY CABINET  
Page 12-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
NDU Cabinet  
NDU Controller  
Board  
Optional 16 Zone  
Display Boards PA0454  
(FP0475)  
J13  
LM0092  
PA0772 PFD  
Term Board  
12 Core  
Shielded  
Cable  
Picture Frame Display Cabinet  
(30m Max)  
PFD 16 Zone Display Boards  
PA0741 (alarm only)  
PA0754 (full status)  
26  
way  
FRC  
Termination  
Board  
PA0483  
PA0772 PFD  
Term Board  
Miscellaneous Inputs  
Note: This configuration will not generally be used. Refer to Section 12.8.1.  
FIG 12.8.3  
NDU WITH ACTIVE DISPLAY BOARDS  
IN SEPARATE PICTURE FRAME DISPLAY CABINET  
Issue 2.7  
5 July 2001  
Page 12-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
NDU Cabinet  
PFD Termination  
Board. PA0772  
Links LK1 & LK2  
not fitted.  
J1  
J3  
12  
11  
10  
9
8
7
From  
Main  
Display  
Boards  
26 Way  
FRC  
6
5
4
3
2
1
C
B
A
J2  
Earth  
12 Core  
Shielded  
Cable  
Pin1 - Pin 1  
:
Pin 12 - Pin 12  
Picture Frame Display Cabinet  
(30m max)  
PFD Termination  
Board. PA0772  
Links LK1 & LK2  
fitted.  
J1  
J3  
12  
11  
10  
9
To  
Display  
Boards  
26 Way  
FRC  
8
7
6
5
4
3
2
1
C
B
A
J2  
Earth  
FIG 12.8.4  
WIRING OF NDU TO PFD (ACTIVE DISPLAY)  
Page 12-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
New Zealand Operation  
Outputs  
spare  
anc defect 2├─┤  
anc fire 3├─┤  
fire led 4├─┤  
defect led 5├─┤  
normal led 6├─┤  
┌────────────┬─┬─┬─┬─┬───────────────┐  
Inputs  
└─┴─┴─┴─┘  
1├─┐  
0 Volt  
┌─┤  
├─┤  
├─┤  
├─┤  
├─┤  
├─┤  
├─┤  
├─┤  
└─┤  
16 Sprinkler Operated  
15 Trial evac  
14 Silence alarms  
13 Ext defect  
12 Lamp test  
11 Brigade Isol/Test  
26 way FRC  
┌────────────┐  
└───── ─────┘  
Lamp-  
Lamp+  
7├─┤  
8├─┤  
├─┘  
10 BSR  
9 Evac Defect  
+24 Volt  
┌─┬─┬─┬─┐  
└────────────┴─┴─┴─┴─┴───────────────┘  
FIG 12.8.5  
Terminations from NZ mode Display Extender Board on  
unprotected termination board (PA0483).  
NOTE:  
Sprinkler Operated and Trial Evac share the same input and are electrically connected on  
the Display Extender Board. On an F4000, input 10 is used as Brigade Test and Services  
Restore (BSR) is not provided.  
Issue 2.7  
5 July 2001  
Page 12-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
New Zealand Operation  
Document No: LT0122  
THIS PAGE INTENTIONALLY LEFT BLANK  
Page 12-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Tandem LCD Mode  
CHAPTER 13  
TANDEM LCD MODE  
Issue 2.7  
5 July 2001  
Page 13-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
F3200 Installation & Programming Manual  
Tandem LCD Mode  
Document No: LT0122  
13.1  
TANDEM LCD MODE  
Tandem mode allows the LCD and keyboard of an F3200 panel or NDU to be operated from  
a device on the printer/programmer port or from another device on the network.  
F3200 or NDU V2.07 or later software allow Tandem LCD mode operation.  
There are three “modes” of Tandem LCD operation and only one mode may be active at any  
one time.  
1. Local Tandem LCD mode.  
A terminal or computer connected to serial port zero of the Controller can initiate local  
Tandem LCD mode by “pressing” the RETURN/ENTER key, entering the password and  
selecting the “L” option.  
This mode allows full programming of the Controller to be done including database load,  
save and verify, and "text load”. “Text load” refers to the loading of text names for zones  
and relays.  
To initiate this using a local Tandem LCD connection, select the main text programming  
menu “1:site, 2:zone, 3:relay” etc, and press the EDIT key on the remote device’s  
keypad. The remote text entry prompt will then be output.  
2. “Controlled” Tandem LCD mode.  
A networked F3200 or NDU can have its LCD accessed across the network and be  
“controlled” via a Tandem LCD connection to the serial port of another panel on the  
network. In this mode, database save, load, verify and text load operations cannot be  
done.  
3. “Controlling” Tandem LCD mode.  
A networked F3200 and NDU allows a Tandem LCD connection to its local serial port to  
access the LCD of another panel on the network. This mode is initiated by entering the  
SID number of the panel being connected to after entering the Tandem LCD password.  
A password is required to enter tandem LCD mode. A password of up to 12 characters can  
be programmed using Option 7 from the F3200 text programming menu.  
Page 13-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix A  
APPENDIX A1  
COMPATIBLE ACTUATING DEVICES (DETECTORS)  
The following detectors are compatible with the F3200 System. The maximum number of  
detectors per circuit is indicated by the columns 4mA and IS, for Standard and Intrinsically  
Safe applications. For IS application refer to Section 9.4.  
╔═══════════════════════════════════════════════════════╤══════════════╗  
DETECTORS COMPATIBLE WITH F3200 FIP  
╟─────────────┬─────────────────────────────────────────┼───────┬──────╢  
TYPE DESCRIPTION 4mA IS  
╠═════════════╪═════════════════════════════════════════╪═══════╪══════╣  
B111B #BEAM TYPE SMOKE DETECTOR (SEE NOTE 7) 40 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
B21B BEAM TYPE SMOKE DETECTOR 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
C23B *&IONISATION SMOKE DETECTOR 40 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
C23BEx x*&IONISATION SMOKE DETECTOR (IS) 40 35  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
C24B IONISATION SMOKE DETECTOR 40 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
C29B IONISATION SMOKE DETECTOR 40 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
C29BEX xIONISATION SMOKE DETECTOR (IS) 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
DL01191A BEAM SMOKE DETECTOR 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
FW81B #HEAT DETECTOR CABLE FW68, FW105 (IS)  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
P24B PHOTOELECTRIC SMOKE DETECTOR 40 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
P29B PHOTOELECTRIC SMOKE DETECTOR 36 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
P61B *PHOTOELECTRIC SMOKE DETECTOR (REV J) 40 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
P76B PHOTOELECTRIC SMOKE DETECTOR NON LATCHING│ 10 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
P136 PHOTOELECTRIC SMOKE DETECTOR NON LATCHING│ │ 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
R23B &INFRARED FLAME DETECTOR 36 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
R24B DUAL SPECTRUM INFRARED FLAME DETECTOR 0  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
R24BEX x+DUAL SPECTRUM INFRARED FLAME DETECTOR(IS)│ │ 7  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
T54B +x#PROBE TYPE E HEAT DETECTOR -IS/FLAMEPROOF40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
T56B xHEAT DETECTOR TYPES A, B, C, D 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
V41B +x#ULTRAVIOLET FLAME DETECTOR 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
V42B +x#ULTRAVIOLET FLAME DETECTOR SLAVE N/A N/A  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
V44B +x#ULTRAVIOLET FLAME DETECTOR 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
SU0600 │15V MCP 40 -  
MAX NO.  
1
1
1
1
8
8
8
╚═════════════╧═════════════════════════════════════════╧═══════╧══════╝  
Table I Grinnell Detector Range  
Issue 2.7  
5 July 2001  
Page A-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix A  
Document No: LT0122  
╔═══════════════════════════════════════════════════════╤══════════════╗  
DETECTORS COMPATIBLE WITH F3200 FIP MAX NO  
╟─────────────┬─────────────────────────────────────────┼───────┬──────╢  
TYPE DESCRIPTION 4mA IS  
╠═════════════╪═════════════════════════════════════════╪═══════╪══════╣  
MD614 HEAT DETECTOR 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MF614 IONISATION SMOKE DETECTOR 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR614 PHOTOELECTRIC SMOKE DETECTOR 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR614T HIGH PERFORMANCE OPTICAL SMOKE DETECTOR 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MU614 CARBON MONOXIDE DETECTOR 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MS302Ex INFRA-RED FLAME DETECTOR 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S111 │INFRA-RED FLAME DETECTORS (IS) 40 35  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S121 │INFRA-RED FLAME DETECTORS (IS) 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S131 │INFRA-RED FLAME DETECTORS (IS) 40 35  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S231i+/f+ INFRA-RED FLAME DETECTOR (refer Sections │  
9.4 and 9.6)  
5
11  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MF301Ex IONISATION SMOKE DETECTOR 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR301Ex PHOTOELECTRIC SMOKE DETECTOR 40 40  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR301TEX HIGH PERFORMANCE OPTICAL SMOKE DETECTOR 40 40  
╟─────────────┴─────────────────────────────────────────┴───────┴──────╢  
WITH M614 OR M300 BASE AS APPROPRIATE  
╚══════════════════════════════════════════════════════════════════════╝  
Table II  
Tyco Detectors  
╔═══════════════════════════════════════════════════════╤══════════════╗  
DETECTORS COMPATIBLE WITH F3200 FIP  
╟─────────────┬─────────────────────────────────────────┼───────┬──────╢  
TYPE DESCRIPTION 4mA IS  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9618EA HEAT DETECTOR – TYPE A 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9619EA HEAT DETECTOR – TYPE B 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9621EA HEAT DETECTOR – TYPE D 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9603EA IONISATION DETECTOR 40 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9601EA PHOTOELECTRIC DETECTOR 40 -  
MAX NO  
╚═════════════╧═════════════════════════════════════════╧═══════╧══════╝  
Table III  
Simplex Detectors  
Page A-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix A  
BASES COMPATIBLE WITH DETECTORS  
DET/ Z51B Z52B Z54B Z55B Z56 Z56N Z500 Z500 Z91C Z94  
BASE  
&
N
&
&
Z54B  
MK2  
Z94C MH2  
C24B  
C29B  
X
X
X
X
X
X
&
&
&
&
&
&
&
&
'
C29B  
Ex  
&
P24B  
P29B  
T56B  
X
X
X
X
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
&
Table IV  
Grinnell Detector/Base Range  
&
These detector/base combinations are compatible.  
X
These detector base combinations have been used in the past, however they are  
technically incorrect (see Product Bulletin PBD0004).  
'
The combination of Z94 base and MH2 heater unit is not SSL approved.  
Note that Z52, Z55, Z56N and Z500N are non-electronic bases (ie. non-latching, non-  
indicating) and do not add any extra voltage to the detector in alarm (eg. if a T56B heat  
detector is used with these, it shorts directly across the AZC).  
╔═════════════════════════════════════════════════════════╤═══════╗  
DETECTORS COMPATIBLE WITH F3200 FIP  
╟─────────┬───────────────────────────────────────────────┼───────╢  
TYPE DESCRIPTION 4mA  
╠═════════╪═══════════════════════════════════════════════╪═══════╣  
DCD-A (DCC-A & DCA-B-60R) HEAT DETECTOR TYPE A 40  
╟─────────┼───────────────────────────────────────────────┼───────╢  
DCD-C (DCC-C & DCA-B-90R) HEAT DETECTOR TYPE C 40  
╟─────────┼───────────────────────────────────────────────┼───────╢  
DFJ-60B (DFE-60B & DFB-60B) HEAT DETECTOR TYPE B 40  
╟─────────┼───────────────────────────────────────────────┼───────╢  
DFJ-90D (DFE-90D & DFB-90D) HEAT DETECTOR TYPE D 40  
╟─────────┼───────────────────────────────────────────────┼───────╢  
SIJ-ASN (SIH-AM & SIF-A)IONISATION SMOKE DETECTOR 40  
╟─────────┼───────────────────────────────────────────────┼───────╢  
SLR-AS (SLK-A & SLG-AM) PHOTOELECTRIC SMOKE DETECTOR 40  
╟─────────┼───────────────────────────────────────────────┼───────╢  
HF-24A ULTRAVIOLET FLAME DETECTOR 18  
╟─────────┴───────────────────────────────────────────────┴───────╢  
MAX NO.║  
ALL WITH YBC-RL/4AH4, YBF-RL/4AH4 OR YBF-RL/4AH4M OR YBO-R/4A  
BASE  
╚═════════════════════════════════════════════════════════════════╝  
Table V  
HOCHIKI Detector Range  
Issue 2.7  
5 July 2001  
Page A-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix A  
Document No: LT0122  
╔═══════════════════════════════════════════════════════╤═══════╗  
DETECTORS CERTIFIED WITH F3200 FIP MAX NO.║  
╟─────────────┬─────────────────────────────────────────┼───────╢  
TYPE DESCRIPTION 4mA  
╠═════════════╪═════════════════════════════════════════╪═══════╣  
SERIES 60 APOLLO HEAT DETECTOR TYPES A, B, C, D 40  
╟─────────────┼─────────────────────────────────────────┼───────╢  
SERIES 60 APOLLO PHOTOELECTRIC SMOKE DETECTOR 40  
╟─────────────┼─────────────────────────────────────────┼───────╢  
SERIES 60 APOLLO IONISATION SMOKE DETECTOR 40  
╟─────────────┴─────────────────────────────────────────┴───────╢  
ALL WITH 45681-200 BASES  
╠═════════════╤═════════════════════════════════════════╤═══════╣  
MK VIII* FLAMEGUARD HEAT DETECTOR TYPE A 22  
╟─────────────┼─────────────────────────────────────────┼───────╢  
MK VIII* FLAMEGUARD HEAT DETECTOR TYPE C 11  
╟─────────────┴─────────────────────────────────────────┴───────╢  
(NOTE 9) DETECTOR HAS INTEGRAL LED & TERMINALS  
╠═════════════╤═════════════════════════════════════════╤═══════╣  
MK5*, MK6* INTERTEC HEAT DETECTOR TYPES A,B,C,D 22  
╟─────────────┴─────────────────────────────────────────┴───────╢  
(NOTE 9) DETECTOR HAS INTEGRAL LED & TERMINALS  
╠═════════════╤═════════════════════════════════════════╤═══════╣  
ZAU401 REV2ZONE ADAPTOR UNIT (INTERFACE)  
1
╚═══════════════════════════════════════════════════════════════╝  
Table VI  
Other Detectors  
REMOTE INDICATORS (LEDS) WITH COMPATIBLE DETECTORS/BASES  
REM  
IND/  
Z51B  
Z52B  
Z54B  
Z54B  
MK2  
Z55B  
Z56  
Z500  
Z91C  
Z94C  
MUB  
BASE  
&
&
E500  
&
&
&
&
&
E500  
MK2  
&
&
&
DET/REM IND  
E500  
E500 MK2  
C23B  
R23B  
R24B  
P76B  
&
&
&
&
&
&
&
Table VII  
Grinnell Detector/Base & Remote LED Range  
The E500 remote indicators are designed to operate across typically 5V.  
E500  
E500 Mk2  
R = 180Ω, VF LED = 2.2V typical  
R = 1.2kΩ, VF LED = 1.75V typical  
Page A-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix A  
ACTUATING DEVICE COMPATIBILITY  
NOTES  
1)  
2)  
The maximum number of detectors per AZC allowed by the standard is 40.  
Those detectors shown in brackets are old models and have the same characteristics  
as the current models.  
3)  
Detectors indicated by a "x" may be used in INTRINSICALLY SAFE AREAS in  
conjunction with approved and compatible, intrinsically safe adaptors. The number  
allowed in a particular circuit may be less than the maximum shown. See Section  
9.4.  
V41/42/44B detectors have flameproof enclosures.  
4)  
Detectors indicated by a "+", which are used in HOSTILE CLIMATIC  
ENVIRONMENTS, may be directly connected to the panel, if they are not required to  
be intrinsically safe.  
5)  
6)  
Detectors indicated by a "*", are not current models and should not be used for new  
installations.  
Detectors indicated by an "&", normally use an incandescent lamp which will have a  
low intensity when used in mode 1.  
The lamp can be replaced with an LED kit.  
7)  
8)  
The B111B beam and V41B/V42B/V44B flame detectors require power from the  
fused +24 VDC supply.  
Hard Contact devices are indicated by a "#". Where an AZC has only hard contact  
detectors the circuit resistance may be up to 150 Ohms maximum to guarantee  
voltage band B1 operation.  
9)  
There is a 12V version of Flameguard which may be used by adding a Zener diode.  
The Intertec detectors require a series diode to be fitted for compatibility. Both of  
these are detailed in Product Bulletin PBF0080.  
10)  
The Olsen FW81B code for fire wire has been replaced by FW followed by the  
temperature rating in °C, eg. FW68, FW105. Only FW68 is currently approved and  
listed.  
Issue 2.7  
5 July 2001  
Page A-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix A  
Document No: LT0122  
APPENDIX A2  
PROGRAMMING FOR DETECTOR TYPE  
1.  
GENERAL  
The default programming (i.e. pre-programmed options) for AZCs (circuits) and zones are  
shown on the top of the "F3200 INPUT CONFIGURATION" sheet in Appendix B. They are  
as follows:  
Circuits  
┌──────────┬────────────┬───────────┬─────────────────┬───────────────┐  
Alarm  
Text  
Mode  
Delay  
(Type)  
Voltage Band  
B1 (0-3V)  
Voltage Band  
B3 (13-17.5V) │  
├──────────┼────────────┼───────────┼─────────────────┼───────────────┤  
│ 1 Smoke │ 1 Standard │1 Standard │ 1 Instant Alarm │1 Instant Alarm│  
└──────────┴────────────┴───────────┴─────────────────┴───────────────┘  
Zones  
┌──────────┬───────────┬───────────┬───────────┬───────────┬───────────┐  
Latch/  
Non-Latch to MAF  
Mapped/Not Mapped/Not Mapped/Not Mapped/Not LED Map  
to Anc1 │To Anc2 To Bells (Zone n)  
├──────────┼───────────┼───────────┼───────────┼───────────┼───────────┤  
Latch Mapped Mapped Mapped Mapped LED n  
└──────────┴───────────┴───────────┴───────────┴───────────┴───────────┘  
The default "circuit" programming suits most of the common "electronic" (as opposed to  
"hard contact") smoke detectors and hard contact detectors in electronic bases, where these  
are not used with external (remote) LED indicators.  
Where other types of detector are used, or detectors are used to switch remote LED  
indicators directly so that the alarm voltage is out of the B2 range (approx. 3V-13V), the  
circuit will have to be programmed accordingly. In some cases constraints are also applied  
to zone programming. For example, where a non-latching detector (e.g. Olsen P76B) is  
used for air duct sampling, then as well as programming the circuit for the appropriate RAD  
or SAD time delay sequence, the zone should be programmed as non-latching.  
Programming circuits and zones is described in Sections 7.2 and 7.3 of this manual. The  
following describes the relationships between detector types and circuit programming.  
2.  
ALARM TEXT  
Choose the appropriate text for each detector type e.g. smoke (default) for smoke detectors,  
heat for thermal detectors, etc. There is provision for creating new names if the standard  
ones are not sufficient.  
The Instant Alarm text may also be changed if required (default is manual).  
3.  
MODE  
Mode 1 (standard) suits most detectors where remote LEDs are not used.  
High Current Detectors  
The following detectors require the F3200 circuit to be programmed into high current mode  
(mode 2) to give sufficient LED (lamp) illumination current.  
Page A-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix A  
APPENDIX A2 (CONTINUED)  
Olsen C23B, C23BEx, R23B, R24B (and Ex where applicable), Flameguard, Intertec, Apollo  
Series 60.  
Remote LEDs  
Where remote LEDs are used, mode 2 may have to be selected to give sufficient current for  
illumination, depending on the particular LED kit used.  
Where mode 2 is selected, some detectors require voltage band B3 to be programmed as  
Alarm. See tables I-V.  
4.  
DELAY TYPE  
Delay types 2 and 3 with a delay out of alarm (Delay 2 greater than 0) require a non-latching  
detector (e.g. Olsen P76B).  
5.  
VOLTAGE BANDS  
The following tables I-V show the expected alarm voltage band for each type of detector in  
Mode 1 (standard) and Mode 2 (high current). A “-“ means there is no need to use Mode 2  
(and it should not be used).  
Where a value other than B2 is shown (e.g. B1 or B3), then that voltage band must be  
programmed as Alarm.  
Hard Contact Detectors  
Hard contact detectors that are not fitted to an electronic base may also be connected  
directly across the circuit. Program the detector type as appropriate (e.g. heat, flowswitch)  
and voltage band B1 as Alarm (detector operated).  
If detectors and MCPs are to be used on the same circuit, with differentiation between them  
(e.g. for AVF), then it is necessary to use 15V MCPs and program B3 = Instant Alarm. This  
means that 15V MCPs cannot be used on the same circuit as any detector that requires B3  
= Alarm.  
╔════════════════════════════════════════════════════╤═════════════════╗  
DETECTORS COMPATIBLE WITH F3200 FIP  
VOLTAGE BANDS  
FOR MODES 1 & 2 ║  
╟─────────┬──────────────────────────────────────────┼────────┬────────╢  
TYPE DESCRIPTION MODE 1 │ MODE 2 ║  
╠═════════╪══════════════════════════════════════════╪════════╪════════╣  
DCD-A (DCA-B-60R & DCC-A) HEAT DETECTOR TYPE A B2 B3  
╟─────────┼──────────────────────────────────────────┼────────┼────────╢  
DCD-C (DCA-B-90R & DCC-C) HEAT DETECTOR TYPE C B2 B3  
╟─────────┼──────────────────────────────────────────┼────────┼────────╢  
DFJ-60B (DFB-60B & DFE-60B) HEAT DETECTOR TYPE B B2 B3  
╟─────────┼──────────────────────────────────────────┼────────┼────────╢  
DFJ-90D (DFB-90D & DFE-90D) HEAT DETECTOR TYPE D B2 B3  
╟─────────┼──────────────────────────────────────────┼────────┼────────╢  
SIJ-ASN (SIF-A & SIH-AM) IONISATION SMOKE DETECTORB2 B3  
╟─────────┼──────────────────────────────────────────┼────────┼────────╢  
SLR-AS (SLK-A & SLG-AM) PHOTOELECTRIC SMOKE  
DETECTOR  
B2  
B3  
╟─────────┼──────────────────────────────────────────┼────────┼────────╢  
HF-24A ULTRAVIOLET FLAME DETECTOR B2 B3  
╚═════════╧══════════════════════════════════════════╧════════╧════════╝  
Table I HOCHIKI Detector Range  
Issue 2.7  
5 July 2001  
Page A-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix A  
Document No: LT0122  
╔═══════════════════════════════════════════════════════╤══════════════╗  
DETECTORS COMPATIBLE WITH F3200 FIP  
VOLTAGE BAND  
FOR MODES 1&2 ║  
╟─────────────┬─────────────────────────────────────────┼───────┬──────╢  
TYPE DESCRIPTION MODE 1 │MODE 2║  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MD614 HEAT DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MF614 IONISATION SMOKE DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR614 PHOTOELECTRIC SMOKE DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR614T HIGH PERFORMANCE OPTICAL SMOKE DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MU614 CARBON MONOXIDE DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MS302Ex INFRA-RED FLAME DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S111 │INFRA-RED FLAME DETECTORS (IS) B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S121 │INFRA-RED FLAME DETECTORS (IS) B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S131 │INFRA-RED FLAME DETECTORS (IS) B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
S231i+/f+ INFRA-RED FLAME DETECTOR(IS)(Refer 9.6.1)B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MF301Ex IONISATION SMOKE DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR301Ex PHOTOELECTRIC SMOKE DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
MR301TEx HIGH PERFORMANCE OPTICAL SMOKE DETECTOR B2 -  
╚═════════════╧═════════════════════════════════════════╧═══════╧══════╝  
Table II  
Tyco Detectors  
╔═══════════════════════════════════════════════════════╤══════════════╗  
DETECTORS COMPATIBLE WITH F3200 FIP  
VOLTAGE BAND  
FOR MODES 1&2 ║  
╟─────────────┬─────────────────────────────────────────┼───────┬──────╢  
TYPE DESCRIPTION MODE 1 │MODE 2║  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9618EA HEAT DETECTOR – TYPE A B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9619EA HEAT DETECTOR – TYPE B B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9621EA HEAT DETECTOR – TYPE D B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9603EA IONISATION DETECTOR B2 -  
╟─────────────┼─────────────────────────────────────────┼───────┼──────╢  
4098-9601EA PHOTOELECTRIC DETECTOR B2 -  
╚═════════════╧═════════════════════════════════════════╧═══════╧══════╝  
Table III  
Simplex Detectors  
Page A-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix A  
╔══════════════════════════════════════════════════════╤═══════════════╗  
DETECTORS CERTIFIED WITH F3200 FIP  
VOLTAGE BANDS  
(SSL # 336)  
FOR MODES 1 & 2║  
╟─────────────┬────────────────────────────────────────┼────────┬──────╢  
TYPE DESCRIPTION MODE 1 │MODE 2║  
╠═════════════╪════════════════════════════════════════╪════════╪══════╣  
B1  
B111B  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3  
BEAM TYPE SMOKE DETECTOR SEE NOTE 1│  
-  
B21B  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3  
BEAM TYPE SMOKE DETECTOR  
-  
C23B  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3  
IONISATION SMOKE DETECTOR SEE NOTE 3B2 *  
C23BEx  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
C24B IONISATION SMOKE DETECTOR B2 B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
C29B IONISATION SMOKE DETECTOR B2 B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
C29BEX IONISATION SMOKE DETECTOR (IS) B2 * B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3 B3  
IONISATION SMOKE DETECTOR SEE NOTE 3B2 *  
DLO1191A  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B1  
BEAM SMOKE DETECTOR  
FW81B  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
P24B PHOTOELECTRIC SMOKE DETECTOR B2 B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
P29B PHOTOELECTRIC SMOKE DETECTOR B2 B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
P61B PHOTOELECTRIC SMOKE DETECTOR (REV J) B2 -  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3 B3  
HEAT DETECTOR CABLE FW68, FW105 (IS) │  
B2  
P76B  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
P136 PHOTOELECTRIC SMOKE DETECTOR (NOTE 2)B2 -  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
R23B INFRARED FLAME DETECTOR B2 * B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3  
PHOTOELECTRIC SMOKE DETECTOR (NOTE 2)│  
R24B  
DUAL SPECTRUM INFRARED FLAME DETECTORB2 *  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
R24BEX  
DUAL SPECTRUM INFRARED FLAME DETECTOR│  
(IS) B2 *  
B3  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
T54B  
PROBE TYPE E HEAT DETECTOR  
(IS OR FLAMEPROOF)  
B1  
-  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
T56B  
HEAT DETECTOR TYPES A, B, C, D  
(IS WITH Z55 BASE) SEE NOTE 1B2  
B2  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
V41B  
ULTRAVIOLET FLAME DETECTOR  
B1  
SEE NOTE 1│  
-  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
V42B ULTRAVIOLET FLAME DETECTOR SLAVE - -  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
V44B  
ULTRAVIOLET FLAME DETECTOR  
B1  
SEE NOTE 1│  
-  
╟─────────────┼────────────────────────────────────────┼────────┼──────╢  
B3 B3  
SU0600  
╟─────────────┴────────────────────────────────────────┴────────┴──────╢  
DETECTORS WITH BASES AS APPLICABLE  
15V MCP  
╚══════════════════════════════════════════════════════════════════════╝  
Table IV TYCO Detector Range  
Issue 2.7  
5 July 2001  
Page A-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix A  
Document No: LT0122  
╔════════════════════════════════════════════════════╤═════════════════╗  
DETECTORS CERTIFIED WITH F3200 FIP  
(SSL # 336)  
VOLTAGE BANDS  
FOR MODES 1 & 2 ║  
╟─────────────┬──────────────────────────────────────┼────────┬────────╢  
TYPE DESCRIPTION MODE 1 │ MODE 2 ║  
╠═════════════╪══════════════════════════════════════╪════════╪════════╣  
B3  
╟─────────────┼──────────────────────────────────────┼────────┼────────╢  
B3  
╟─────────────┼──────────────────────────────────────┼────────┼────────╢  
B3  
╠═════════════╧══════════════════════════════════════╧════════╧════════╣  
ALL WITH 45681-200 BASES  
╠═════════════╤══════════════════════════════════════╤════════╤════════╣  
B3  
╟─────────────┼──────────────────────────────────────┼────────┼────────╢  
B3  
╠═════════════╪══════════════════════════════════════╪════════╪════════╣  
B2  
╟─────────────┼──────────────────────────────────────┼────────┼────────╢  
B2  
SERIES 60 APOLLO HEAT DETECTOR TYPES A, B, C, D B2 * │  
SERIES 60 APOLLO PHOTOELECTRIC SMOKE DETECTOR  
B2 * │  
B2 * │  
SERIES 60 APOLLO IONISATION SMOKE DETECTOR  
MKVIII  
MKVIII  
MK5, MK6  
ZAU401  
FLAMEGUARD HEAT DETECTOR TYPE A, 24V - * │  
FLAMEGUARD HEAT DETECTOR TYPE C, 24V - * │  
INTERTEC HEAT DETECTOR TYPES A,B,C,D B2 * │  
ZONE ADAPTOR UNIT (REV 2)  
B2  
╚═════════════╧══════════════════════════════════════╧════════╧════════╝  
Table V  
Other Detectors  
Notes  
1.  
Hard contact devices without "electronic" bases give voltage band B1 unless a 6V8  
zener diode is wired in series with the contacts which gives B2 alarm.  
2.  
The P76B requires band B3 to be programmed as Alarm (detector operated) though  
typical operation for both modes 1 and 2 will give B2 voltage (just less than 12V).  
For non-latching operation the zone must be programmed as non-latching.  
3.  
4.  
5.  
The C23B and C23BEx (old types of detectors) may have a nominal 6V/30mA bulb in  
them which require Mode 2 for illumination. The bulbs may have been replaced with  
LEDs. Although the bulb would typically give B2 operation, it is safest to program B3  
as Alarm. The R23B with an LED needs only B2 in Mode 2. (Note that the  
incandescent lamps do not meet the SSL005 Standard).  
Detectors shown with an "*" need to be programmed for Mode 2 to give sufficient  
lamp illumination. The Flameguard detectors require Mode 2 for latching and require  
an extra resistor (270E, 5W) to be switched in from +VBF to the AZC+ terminal for  
LED illumination. If relay n is used to boost AZCm, the logic for the relay is Rn =  
ZmA.^ZmR.  
For IS applications refer to Section 9.4.  
WARNING  
Detectors which require voltage band B3 to be programmed as Alarm  
(detector operated) cannot have an MCP with a 15V Zener Diode (e.g. SU0600)  
connected to the same circuit.  
Page A-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
APPENDIX B  
F3200 CONFIGURATION SHEETS  
The following pages are suggested as master forms for programming. It is recommended  
that they be photocopied, and a complete set be filled out for each FIP before programming  
is started.  
When programming is complete, the database printout should be checked against the  
sheets.  
A copy of the database printout and completed sheets should be kept in the contract file for  
each installation.  
Issue 2.7  
5 July 2001  
Page B-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
THIS PAGE INTENTIONALLY BLANK  
Page B-2  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200/NDU SYSTEM CONFIGURATION PAGE 1  
REF:...............  
This set of configuration sheets contains all programmable parameters. Fill in values for all  
parameters that are being changed from the default settings.  
................................................................................  
(SITE NAME - 40 CHARACTERS MAXIMUM)  
8 Zone modules :  
0 – 8  
MAF module present Y/N  
LED Display boards : 0 – 4  
8 Relays modules : 0 – 8  
MAF RELAY OUTPUTS  
ENABLE  
LATCH  
NAME  
MAF  
MODE  
ISOL  
TEST SUP  
ACT  
ANC1  
ANC2  
ANC3  
LOGIC EQUATION  
ANC1  
ANC2  
ANC3  
STANDBY  
FAULT  
ISOLATED  
ALARM  
ACCESS CODES 0-9  
USER INITIALS  
0
1
2
3
4
5
6
7
8
9
Issue 2.7  
5 July 2001  
Page B-3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200/NDU SYSTEM CONFIGURATION PAGE 2  
REF:...............  
AUTO TEST  
Alarm test enable/disable Y/N:  
Start time:  
Inhibit dates:  
SYSTEM OPTIONS  
FIP MCP Zone 0 – 64  
All zones isolated = standby  
Activate relay for Brigade Test  
FFCIF zones: MAF only/all/none  
FFCIF type  
FFCIF auto ack enable/disable  
FFCIF allow remote ack from RDU  
FFCIF display cause by default  
FFCIF alarm Bells on  
Y/N  
Y/N  
2/3  
Y/N  
Y/N  
Y/N  
Y/N  
Y/N  
Y/N  
FFCIF flash non maf alarm LEDs  
FFCIF send non maf alarm to RDU  
Country coder 0 – 6  
Fault action text ……………………………………………………………  
PSU/BATTERY OPTIONS  
Mains enabled  
Y/N  
Y/N  
Y/N  
Y/N  
Mains Frequency  
50/60  
8 hours mains fail = fault  
Charger high/low = fault  
Battery low = fault  
Battery connection test enable  
Hourly Battery test enable  
Daily Battery test enable  
Y/N  
Y/N  
Y/N  
BUZZER OPTIONS  
Zone alarm buzzer enable  
Zone fault buzzer enable  
System fault buzzer enable  
Non-maf zone faults buzzer  
Faults resound after 8 hours  
Y/N  
Y/N  
Y/N  
Y/N  
Y/N  
Remote sys fault reset silences  
Remote FFCIF action silences  
Remote any command silences  
Receive network sounder silence Y/N  
Send any key net sounder  
silence  
Y/N  
Y/N  
Y/N  
Y/N  
Sounder after 8 hours isolate  
Y/N  
Allow net sounder silence cmd  
Y/N  
NEW ZEALAND MODE OPTIONS  
New Zealand mode enabled  
Battery very low is alarm  
NZ Display Extender bd present  
Y/N  
Y/N  
Y/N  
Evac defect is fault  
External defect is fault  
Y/N  
Y/N  
Page B-4  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200/NDU SYSTEM CONFIGURATION PAGE 3  
REF:...............  
Key  
Non-FF Mode  
Door Open  
Key Enabled  
Y/N  
FF Mode  
Door Open  
Key Enabled  
Y/N  
Non-FF Mode  
FF Mode  
Door Closed  
Key Enabled  
Y/N  
Door Closed  
Key Enabled  
Y/N  
Prev  
Next  
Ack  
Reset  
Isolate  
Relay  
Bell Isol  
Warn Sys Isol  
AIF Mode  
Clear  
Recall  
Ancil Isol  
Zone  
System  
Numeric  
Enter  
Batt Test  
OR  
AND  
XOR  
NOT  
Print  
Set  
Test  
Alarm Test  
Fault Test  
Brigade Test  
DEFAULT IS  
DEFAULT IS  
DEFAULT IS  
DEFAULT IS  
ALL ENABLED ALL ENABLED  
ALL DISABLED ALL DISABLED  
Issue 2.7  
5 July 2001  
Page B-5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200/NDU SYSTEM CONFIGURATION PAGE 4  
REF:...............  
RDU PARAMETERS  
RZDU protocol Type: LCD  
Non-LCD  
RZDU 1 – 8  
Enabled Y/N  
Protocol A/B  
MCP Zone  
ALARM TEXT NAMES  
Program Text No Default  
Text No Default  
Program  
1
2
3
4
5
Smoke  
Heat  
FSW  
Manual  
Valve  
6
7
8
9
PSW  
SPKLR  
Page B-6  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200/NDU SYSTEM CONFIGURATION PAGE 5  
REF:...............  
Event printing enable/disable Y/N  
Printer lines per page 0 – 250  
Printer baud rate 300 – 9600  
Print relay activate/de-activate events Y/N  
EVENT TYPES LOGGED TO PRINTER AND HISTORY  
PRINTER Y/N HISTORY Y/N  
ZONES  
SYSTEM  
SYS RUN  
CIRCUIT  
POINT  
RELAY  
DAYLIGHT SAVING PARAMETERS  
START  
END  
MONTH  
HOUR  
MINUTE  
DAY: (one of next 1,2,3)  
1: LAST WEEKDAY OF  
(MON-SUN)  
2: Nth WEEKDAY OF  
(MON-SUN)  
3: DATE  
TIME DIFFERENCE:  
HOUR  
MINUTE  
Issue 2.7  
5 July 2001  
Page B-7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200 AZC CONFIGURATION  
REF:...............  
Number of Zone Modules Fitted ………………….  
AZC PROGRAMMING  
FIELD WIRING  
A
L
M
T
M
O
D
E
D
L
B
1
B
3
D
L
D
L
I
8ZM  
NO.  
CCT  
NO.  
N
S
T
Y
Y
1
Y
2
1
1
1
1
1
-
-
4
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
1
2
3
4
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Page B-8  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200/NDU ZONE CONFIGURATION  
REF:...............  
ZONE PROGRAMMING  
ZONE NAME  
L
M
A
F
A
N
C
1
A
N
C
2
B
E
L
L
LED  
A
T
C
H
ZONE NO  
Defaults  
L
M
M
M
M
ZONE  
NO.  
1
2
3
1
2
3
4
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Issue 2.7  
5 July 2001  
Page B-9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200/NDU OPEN COLLECTOR OUTPUT  
FUNCTION & LOGIC EQUATION  
REF:...............  
8ZM  
NO.  
OUT  
PUT  
FUNCTION NAME  
LOGIC EQUATION  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
1
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
2
3
4
Page B-10  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200 RELAY CONFIGURATION  
REF:...............  
8RM  
NO.  
RLY  
NO.  
PROGRAMMING  
TEXT NAME  
E
N
A
B
L
L
M
A
F
I
T
E
S
T
S
U
P
-
L
E
D
(30 CHARACTERS)  
A
T
C
H
S
O
L
A
C
E
E
N
M
Y
Y
Y
DEFAULTS  
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
1
2
3
4
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Issue 2.7  
5 July 2001  
Page B-11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200/NDU RELAY FUNCTIONS  
& LOGIC EQUATIONS  
REF:...............  
8RM NO.  
RELAY  
NO.  
NAME  
LOGIC EQUATION  
1
2
3
1
2
3
1
2
3
4
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Page B-12  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200 RELAY FIELD WIRING  
REF:...............  
Number of 8RMs:...............  
8RM NO.  
RELAY  
NO.  
NAME  
FIELD WIRING  
1
2
3
1
2
3
1
2
3
4
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
Issue 2.7  
5 July 2001  
Page B-13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200/NDU ZONE DISPLAY  
BOARD LED CONTROL  
REF:...............  
PAGE..... of ......  
LOGICAL  
RELAY  
NO  
LED  
SET  
(1-64)  
ALARM,  
FAULT,  
ISOLATE  
LOGIC EQUATION  
(65-256)  
Page B-14  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200/NDU TIMERS, VARIABLES,  
REF:...............  
NETWORK VARIABLES & ZONE ISOLATE/  
DEISOLATE/RESET EQUATIONS  
TIMER/VARIABLE/  
NETVARS/ZONE  
CMD/SNA  
LOGIC EQUATION  
Issue 2.7  
5 July 2001  
Page B-15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
F3200/NDU CONFIGURATION SHEETS  
REF:...............  
NETWORK PARAMETERS  
FILL IN VALUES FOR ALL PARAMETERS THAT ARE BEING CHANGED FROM  
DEFAULT.  
NETWORK SETUP  
LOCAL SID NUMBER  
NIC Y/N  
RX TIMEOUT  
DUP TIME  
TX DELAY  
ACK TIME  
LEADING FF  
TRAILING FF  
LINK RX TIME  
BAUD RATE  
MODE B 0 – 7  
LINK TX Y/N  
GROUPS  
LINK TX TIME  
ACK BROADCASTS Y/N  
SLOTS  
RETRIES  
ACK BROADCASTS  
TO SPECIFIC SID  
MODE: MULTIDROP/POINT TO POINT M/P  
NETWORK MAF CONFIG  
REFRESH TX TIME  
MAX COS RATE  
SEND BELLS SILENCE Y/N  
RECEIVE BELLS CONTROL Y/N  
RECEIVE BELLS SILENCE Y/N  
NETWORK COMMAND CONFIG  
ACK TIME  
WORK TIME  
RX NET TIME/DATE Y/N  
TX NET TIME/DATE Y/N  
NETWORK FFCIF CONFIG  
TX ALARMS Y/N  
DEDICATED TX SID  
TX ACK CMDS Y/N  
RX NET ACK Y/N  
TX ISO/RESET CMDS Y/N  
NETWORK EVENT CONFIG  
TRANSMIT EVENTS Y/N  
TRANSMIT EVENT UPDATES Y/N  
ZONE/RELAY CMD TEXT TX Y/N  
SYSTEM EVENT TEXT TX Y/N  
TRANSMIT RELAY OPERATES Y/N  
ZONE/RLY EVENT TEXT TX Y/N  
NETWORK VARIABLE CONFIG  
TX ENABLED Y/N  
TX REFRESH RATE  
MAX COS TX RATE  
NETWORK STATUS REFRESH CONFIG  
REFRESH ENABLED Y/N  
TX REFRESH RATE  
FAST TX RATE  
Page B-16  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Document No: LT0122  
F3200 Installation & Programming Manual  
Appendix B  
F3200/NDU CONFIGURATION  
REF:...............  
NETWORK SID LIST CONFIGURATION  
SID  
NO.  
1-254  
LINK  
RX  
Y/N  
LOG  
EVNT FFCIF  
Y/N Y/N  
RX  
TX  
CMD  
Y/N  
RX  
CMD  
Y/N  
USE  
USE STATUS  
MAF TOTALS SEARCH  
Y/N  
Y/N  
Y/N  
Issue 2.7  
5 July 2001  
Page B-17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
F3200 Installation & Programming Manual  
Appendix B  
Document No: LT0122  
THIS PAGE INTENTIONALLY LEFT BLANK  
Page B-18  
5 July 2001  
Issue 2.7  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taylor Scale TE22 User Manual
Toshiba DVD VCR Combo MD13N1C User Manual
Traulsen Refrigerator RRI264LPUT FHS User Manual
Tripp Lite Power Supply 200803016 95 2924 User Manual
Tyco Motorized Toy Car B5115 0920 User Manual
Ultra Start Automobile Alarm 4500 User Manual
Vermont Casting Indoor Fireplace DVBR36RN User Manual
ViewSonic Car Speaker VSACC27951 1 User Manual
ViewSonic Computer Monitor G220F User Manual
Wayne Dalton Radio 3990 372 User Manual