Insight™
Ducted Air Handler
Cooling Only Split System Air Conditioning
30 to 50 MBh - 50 Hz
Air Handler Models
TWE030C
Condensing Models
TTB524-536C
TTA030-060C
TWE040C
TWE050C
TWE5-PRC000-EN
April 1999
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
AIR HANDLING UNITS
Features
New Features
Improved filter access and latch -
Eliminate current T-bar and shipping
bracket.
Provision for 1 1/8” thick field supplied
electrostatic filter
Ships horizontal
•
•
•
Six way convertibility- horizontal (left
and right), upflow, downflow (front and
rear access)
•
•
•
•
•
Electrical, refrigerant, condensate and
blower access convertible to either side
•
•
Reversible Duct Flanges - Fits up to
1 1/2” duct board
Corrosion resistant galvanized steel with
attractive finish
Improve controls access with control
box mounted next to blower.
Internally enhanced finned coil tubes
Direct drive motor
•
•
•
•
•
40 VA transformer with 5 amp
automotive style fuse on 3 tons and less
TWE
Standard filters
5 Amp automotive style fuse replaces
Bussman “red cap” fuse on 3.5 to 5 ton
models
Multi-speed blower
220 volt primary and 24 volt secondary
transformer
Blower mounting brackets improved -
Front access to screw with power driver
•
Insulated cabinet
•
•
•
•
Improved bottom carton cushioning
•
•
External access to heater circuit breakers
Start kits are not required
1” thick foil faced insulation for all
models
Built-in indoor fan delay function for
increased efficiency. No kit required.
TTA
TTB
CONDENSING UNITS
Features:
Benefits:
Vertical Air Discharge
High Efficiency TRANE Climatuff®
Compressor
Flexibility in application
Quality and reliability
•
•
•
•
•
Uniform covering for a smooth,
attractive and corrosion-resistant finish
Powder Paint finish
•
•
Brazed or flare connections
TWE5-PRC000-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
System
Performance
95º F Indoor
Outdoor Unit
Indoor Unit
*MBh
kW
CFM
CMH
Ducted Air Handlers
TTB524CA00A
TTB530CA00A
TTB530CA00A
TTB536CA00A
TTA030CD00A†
TTA030CD00A†
TTA040CD00A†
TTA040CD00A†
TTA050CD00A†
TTA060CD00A†
TWE030CA40B
TWE030CA40C
TWE040CA40C
TWE040CA40C
TWE030CA40B
TWE040CA40C
TWE040CA40C
TWE050CA50D
TWE050CA50D
TWE050CA50D
25.8
30.8
32.4
39.0
30.5
32.5
41.0
43.9
52.7
62.8
6.9
8.4
9.5
10.1
8.9
9.4
12.0
12.8
15.4
18.4
900
1000
1200
1200
1000
1125
1325
1600
1800
1800
1520
1689
2038
2038
1689
1900
2238
2703
3040
3040
†Outdoor: 380-415/50/3, Indoor: 220-240/50/1
*Cooling capacity is based on 94ºF outside ambient, 80ºF DB/67ºF WB air on coil.
4
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Nomenclature
TW
E
0
30
C
A
4
0
A
0
1,2
3
4
5,6
7
8
9
10
11
12
Digit 7
Digit 1,2 - Product Type
TW = Split System Component
Heat Pump Compatible
C = Development Sequence
Digit 8 - Voltage
A = 220/1/50
Digit 3 - Airflow Configuration
E = Convertible
Digit 9 - Refrigerant Flow Control
4 = Accutron Flow Control/
Check Valve
Digit 4 - Refrigerant Connections
0 = Brazed
5 = Flare
5 = Bleed TXV
Digit 10 - Not Used
Digits 5,6 - Nominal Capacity
30 = 30 MBh
Digit 11 - Minor Design Change
40 = 40 MBh
50 = 50 MBh
Digit 12 - Service Digit
TWE5-PRC000-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Product
Data
Table 1 — TWE Product Specifications
Model
TWE030CA40B
TWE040CA40C
TWE050CA50D
Power Conn.— Volts/Ph/Hz
Indoor Coil - Type
Rows
220/1/50
Plate Fin
3
220/1/50
Plate Fin
3
220/1/50
Plate Fin
3
Fins per inch (Fins per 25.4mm)
Face Area ft2-(m2)
Tube Size in. (mm)
Refrigerant Control
Drain Conn. Size in. (mm)
Duct Connections
Indoor Fan - Type
No. Used
14
14
14
3.21 (.30)
5.04 (.47)
6.19 (.58)
3
3
3
/
8
(9.52)
/
8
(9.52)
/
8
(9.52)
FCCV
4
FCCV
4
FCCV
4
3
3
3
/
NPT
/
NPT
/
NPT
—————————— SEE OUTLINE DRAWING ———————————
Centrifugal
1
Centrifugal
1
Centrifugal
1
Diameter in. (mm)
Width in. (mm)
Type Drive - No. Speeds
Airflow (High)
10.0 (254.0)
8.0 (203.2)
Direct - 3
10.0 (254.0)
10.0 (254.0)
Direct - 3
11.0 (279.4)
10.0 (254.0)
Direct - 3
CFM @ 0.0 in. w.g.
CMH @ 0.0 mm w.g.
No. Motors - HP
Motor RPM
—————————— SEE FAN PERFORMANCE TABLE ——————————
—————————— SEE FAN PERFORMANCE TABLE ——————————
1 - 1/3
1000
220/1/50
2.6
1 - 1/3
900
1 - 3/4
900
220/1/50
4.5
10.1
Volts/Ph/Hz
220/1/50
2.1
F.L. Amps
L.R. Amps
3.3
4.2
Filters
Vertical Applications
Filter Furnished
Type Furnished
No.-Size-Thickness
Horizontal Applications
Filter Furnished
Type Recommended
No.-Size-Thickness
Refrigerant Line Size
Line Size ID Gas in. (mm)
Line Size ID Liquid in. (mm)
Dimensions (H x W x D)
Crated - in.
Yes
Throwaway
1 - 20 x 20 - 1
Yes
Throwaway
1 - 20 x 20 - 1
Yes
High Velocity
1 - 2 2 x 20 - 1
No
No
No
—————————— SEE NOTE BELOW ——————————
—————————— SEE NOTE BELOW ——————————
7
/
8
(22.23)
(9.52)
11/8 (28.56)
11/8 (28.56)
3
3
3
/8
/8
(9.52)
/8
(9.52)
44.5 x 24.0 x 23.5
(1130 x 610 x 597)
43.0 x 21.5 x 21.0
(1092 x 546 x 533)
53.25 x 26.0 x 23.5
(1353 x 660 x 597)
52.0 x 23.5 x 21.0
(1321 x 597x 533)
59.5 x 26.0 x 23.5
(1511 x 660 x 597)
58.0 x 23.5 x 21.0
(1473 x 597 x 533)
- (mm)
Uncrated - in.
- (mm)
Weight Ibs. (kg)
Shipping
125 (56.7)
115 (52.2)
165 (74.8)
150 (68.0)
198 (898)
183 (83.0)
Net
Minimum filter size for horizontal applications based on airflow selection and calculated as follows:
Low Velocity Filter: Face Area (ft2) = CFM/300
High Velocity Filter: Face Area (ft2) = CFM/500
6
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Product
Data
Table 2 — TTB5 Product Specifications1,2
Model
TTB524CA00A
TTB530CA00A
Power Conn. — Volts/Ph/Hz
Min. Brch. Cir. Ampacity3
Br. Cir. Max. (Amps)
Prot. Rtg. Recmd. (Amps)
Compressor Type
No. Used - No. Speeds
Volts/Ph/Hz
200-230/1/50
200-230/1/50
19
20
30
30
30
30
Climatuff® Reciprocating
1 — 1
Climatuff® Reciprocating
1 — 1
200-230/1/50
13.9 — 60
180-253
200-230/1/50
13.9 — 79
180-253
R.L. Amps - L.R. Amps
Voltage Utilization Range
Brch. Cir. Selec. Cur. Amps
Outdoor Fan - Type
Dia. - in. (mm) - No. Used
Type Drive - No. Speeds
CFM @ 0.0 in. w.g.4
CMH @ 0.0 mm w.g.
No. Motors
13.9
14.9
Propeller
18 (457) — 1
Direct — 1
1925
Propeller
18 (457) — 1
Direct — 1
2225
908
1050
1
(124)
1
(124)
1
1
Motor HP (W)
/6
/6
Motor Speed RPM
Volts/Ph/Hz
1100
200-230/1/50
1.30
1100
200-230/1/50
1.30
F.L. Amps
Outdoor Coil - Type
Rows - Fins/in. (Fins/mm)
Face Area - ft2 (m2)
Tube Size - in. (mm)
Refrigerant
Spine Fin™
1 — 24 (1)
Spine Fin™
1 — 24 (1)
10.96 (1.02)
14.93 (1.39)
3
3
/8
(10)
/8
(10)
R-225 - lbs. (kg)
4 lbs, 15 oz. (2.24)
6 lbs, 11 oz. (3.03)
Factory Supplied
Line Size - O.D. Gas6 - in. (mm)
Line Size - O.D. Liq.6 - in. (mm)
Dimensions (H x W x D)
Crated - in.
Yes
Yes
3
3
/
4
(20)
/
4
(20)
5/16 (8)
5/16 (8)
263/8 x 267/8 x 267/8
(670 x 683 x 683)
See Outline Dwg.
333/8 x 267/8 x 267/8
(848 x 683 x 683)
See Outline Dwg.
- (mm)
Uncrated
Weight lbs. (kg)
Shipping
176 (79.8)
166 (75.3)
184 (83.5)
174 (78.9)
Net
Notes:
1Rated in accordance with ARI Standard 210/240.
2Rated in accordance with ARI Standard 270.
3Calculated in accordance with National Electric Code. Suitable for use with HACR circuit breakers or fuses.
4Standard air — dry coil — outdoor.
5This value approximate. For more precise value see unit nameplate and service instructions.
6Max. linear length 80 ft.; max. lift — suction 60 ft.; max. lift — liquid 60 ft. Max. length of precharged tubing 50 ft. For greater length refer to
Refrigerant Piping Manual Pub. No. 32-3009.
TWE5-PRC000-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Product
Data
Table 3 — TTB5 Product Specifications1,2
Model
Power Conn. - Volts/Ph/Hz
Min. Brch. Cir. Ampacity3
Br. Cir. Max. (Amps)
TTB536CA00A
200-230/1/50
24
40
40
Prot. Rtg. Recmd. (Amps)
Compressor Type
No. Used - No. Speeds
Volts/Ph/Hz
Climatuff® Reciprocating
1 — 1
200-230/1/50
17.6 — 95
180-253
R.L. Amps - L.R. Amps
Voltage Utilization Range
Brch. Cir. Selec. Cur. Amps
Outdoor Fan - Type
Dia. in. (mm) - No. Used
Type Drive - No. Speeds
CFM @ 0.0 in. w.g.4
CMH @ 0.0 mm w.g.
No. Motors
17.6
Propeller
18 (457) — 1
Direct — 1
2225
1050
1
(124)
1
Motors HP (W)
/6
Motor Speed RPM
Volts/Ph/Hz
1100
200-230/1/50
1.30
F.L. Amps
Outdoor Coil - Type
Rows - Fins/in. (Fins/mm)
Face Area - ft2 (m2)
Tube Size - in. (mm)
Refrigerant
Spine Fin™
1 — 24 (1)
14.93 (1.39)
3
/8
(10)
R-225 - lbs. (kg)
6 lbs, 11 oz. (3.03)
Factory Supplied
Line Size - O.D. Gas6 - in. (mm)
Line Size - O.D. Liq.6 - in. (mm)
Dimensions (H x W x D)
Crated - in.
Yes
3
/
4
(20)
5/16 (8)
333/8 x 267/8 x 267/8
(848 x 683 x 683)
See Outline Dwg.
- (mm)
Uncrated
Weight lbs. (kg)
Shipping
203 (92.1)
193 (87.5)
Net
Notes:
1Rated in accordance with ARI Standard 210/240.
2Rated in accordance with ARI Standard 270.
3Calculated in accordance with National Electric Code. Suitable for use with HACR circuit breakers or fuses.
4Standard air — dry coil — outdoor.
5This value approximate. For more precise value see unit nameplate and service instructions.
6Max. linear length 80 ft.; max. lift — suction 60 ft.; max. lift — liquid 60 ft. Max. length of precharged tubing 50 ft. For greater
length refer to Refrigerant Piping Manual Pub. No. 32-3009.
8
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Product
Data
Table 4 — TTA Product Specifications
Model
TTA030CD00A
380-415/3/50
TTA040CD00A
380-415/3/50
TTA050CD00A
380-415/3/50
TTA060CD00A
380-415/3/50
Power Conn. - Volts/Ph/Hz
Fuse Size - max. amps
Compressor - Type
No. Used - No. Speeds
Volts/Ph/Hz
Per Local Codes
Per Local Codes
Per Local Codes
Per Local Codes
—————————— Climatuff® Reciprocating ——————————
1 - 1
380-415/3/50
5.0
1 - 1
380-415/3/50
7.0
1 - 1
380-415/3/50
9.0
1 - 1
380-415/3/50
10.6
F.L. Amps1
L.R. Amps
51.0
51.0
71.0
64.0
Outdoor Fan - Type
No. Used
Propeller
Propeller
Propeller
Propeller
1
1
1
1
Diameter in. (mm)
Type Drive - No. Speeds
CFM @ 0.0 in. w.g.
CMH @ 0.0 mm w.g.
No. Motors - HP
Motor Speed (RPM)
Volts/Ph/Hz
18 (457)
Direct-1
1815
18 (457)
Direct-1
1845
22 (559)
Direct-1
2225
26 (660)
Direct-1
4250
3083
3134
3780
7220
1 - 1/4
1 - 1/4
1 - 1/3
1 - 1/3
1 (900)
400/1/50
0.80
1 (900)
400/1/50
0.80
1 (690)
400/1/50
1.00
1 (690)
400/1/50
1.70
F.L. Amps
Outdoor Coil - Type
No. Rows - Fins/in.
Face Area ft2 (m2)
Tube Size in. (mm)
Refrigerant
Spine Fin™
1 - 24
Spine Fin™
1 - 24
Spine Fin™
1 - 24
Spine Fin™
1 - 24
12.22 (1.14)
16.84 (1.57)
25.50 (2.37)
35.39 (3.29)
3
3
3
3
/8
(9.52)
/8
(9.52)
/8
(9.52)
/8
(9.52)
R-222 - lbs. (kg)
Line Size - OD Gas in. (mm)
Line Size - OD Liq. in. (mm)
Dimensions (H x W x D)
Crated - in.
5 Ibs, 12 oz. (2.61)
7 Ibs, 2 oz. (3.23)
9 Ibs, 2 oz. (4.14)
13 Ibs, 0 oz. (5.90)
7
/
8
(22.3)
(9.52)
11/8 (28.6)
11/8 (28.6)
11/8 (28.6)
3
3
3
3
/
8
/8
(9.52)
/8
(9.52)
/8
(9.52)
25.0 x 30.0 x 26.5
(635 x 762 x 673)
24.3 x 28.3 x 24.6
(617 x 719 x 625)
33.3 x 30.0 x 26.5
(846 x 762 x 673)
32.8 x 28.3 x 24.6
(833 x 719 x 625)
41.3 x 34.8 x 31.3
(1049 x 884 x 795)
40.6 x 32.9 x 28.8
(1031 x 836 x 732)
45.5 x 41.0 x 37.0
(1156 x 1041 x 940)
44.8 x 38.9 x 34.8
(1138 x 988 x 884)
- (mm)
Uncrated - in.
- (mm)
Weight- lbs. (kg)
Shipping
190.0 (86.2)
181.0 (82.1)
211.0 (95.7)
200.0 (90.7)
254.0 (115.2)
239.0 (108.4)
333.0 (151.0)
314.0 (142.0)
Net
1At ARI system rating conditions of 80° F-DB/67° F-WB indoor & 95° F-DB outdoor.
2Rated for 25 feet (7.5 meters) of evacuated refrigerant piping.
TWE5-PRC000-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
English Units
TTB524CA00A WITH TWE030CA40B
TTB530CA00A WITH TWE030CA40B
AT 900 CFM
AT 1000 CFM
GROSS CAPACITY IN BTU/H x 1000
GROSS CAPACITY IN BTU/H x 1000
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
D.B. W.B. CAP.
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
29.0* 2.05
D.B. W.B. CAP.
72
20.9
17.6
13.9
10.2
20.7
17.4
13.8
10.0
20.6
17.3
13.6
9.9
74
76
78
80
24.6*
24.4
20.7
17.0
24.3*
24.2
20.6
72
74
76
78
80
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
22.9
24.7
26.6
28.6
22.6
24.4
26.2
28.1
22.3
24.0
25.8
27.7
21.5
23.2
24.9
26.7
20.8
22.4
24.0
25.7
19.3
20.7
22.2
23.8
22.6
19.3
15.6
11.9
22.4
19.1
15.5
11.7
22.3*
19.0
15.3
11.6
21.7*
18.6
14.9
11.2
21.1*
18.3
14.6
10.8
19.8*
17.6
13.9
10.1
23.4*
21.0
17.3
13.6
23.1*
20.8
17.2
13.4
22.9*
20.7
17.0
13.3
22.3*
20.3
16.6
12.9
21.6*
20.0
16.3
12.5
20.3*
19.3
15.6
11.8
24.0*
22.7
19.0
15.3
23.8*
22.5
18.9
15.1
23.5*
22.4
18.7
15.0
22.8*
22.0
18.4
14.6
22.2*
21.7
18.0
14.2
20.8*
20.8*
17.3
13.5
1.90
1.97
2.04
2.11
2.01
2.07
2.14
2.21
2.11
2.18
2.25
2.32
2.20
2.26
2.33
2.40
2.29
2.35
2.41
2.48
2.47
2.53
2.58
2.64
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
27.4
29.5
31.6
33.9
27.1
29.1
31.2
33.4
26.7
28.7
30.8
33.0
25.8
27.8
29.8
31.9
25.0
26.8
28.8
30.8
23.2
25.0
26.7
28.6
24.2
20.5
16.5
12.3
24.1
20.4
16.3
12.1
23.9
20.2
16.1
11.9
23.5
19.8
15.7
11.5
23.1
19.4
15.3
11.1
22.3
18.6
14.5
10.3
26.1
22.4
18.4
14.2
25.9
22.3
18.2
14.0
25.8
22.1
18.0
13.8
25.4
21.7
17.6
13.4
25.0
21.3
17.2
13.0
23.5*
20.4
16.3
12.2
27.6*
24.3
20.2
16.1
27.3*
24.1
20.1
15.9
27.0*
24.0
19.9
15.7
26.3*
23.6
19.5
15.3
25.6*
23.1
19.1
14.9
24.2*
22.3
18.2
14.0
28.3*
26.2
22.1
18.0
28.0*
26.0
21.9
17.8
27.7*
25.9
21.8
17.6
27.0*
25.4
21.4
17.2
26.3*
25.0
20.9
16.8
24.7*
24.2
20.1
15.9
85
90
85
90
28.1
24.0
19.8
2.12
2.20
2.28
28.7* 2.15
27.9
23.8
19.7
28.4*
27.7
23.7
19.5
2.23
2.31
2.39
2.25
2.33
2.41
2.49
16.8
24.0*
24.0*
20.4
95
95
16.7
20.2
16.9
13.2
9.5
19.9
16.6
12.9
9.1
23.4*
23.4*
20.1
27.6* 2.34
100
105
115
100
105
115
27.3
23.2
19.1
26.6*
2.42
2.50
2.58
2.43
16.3
22.7*
22.7*
19.7
26.9* 2.51
22.8
18.6
2.59
2.67
25.3* 2.62
25.3* 2.69
15.9
19.2
15.9
12.2
8.4
21.3*
21.3*
19.0
22.0
17.8
2.77
2.84
15.2
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
775
X0.98
X0.99
1025
X1.01
X1.01
AIRFLOW
SENS. CAP.
775
X0.94
1025
X1.06
AIRFLOW
TOTAL CAP.
COMPR. KW
1000
X1.00
X1.00
1000
X1.00
X1.00
AIRFLOW
SENS. CAP.
1000
X1.00
1000
X1.00
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 25800 BTUH
AIRFLOW = 900 CFM
COMPRESSOR POWER = 2245 WATTS
I.D. FAN POWER = 425 WATTS
O.D. FAN POWER = 165 WATTS
S.E.E.R. = 8.71 BTUH/WATT
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 30800 BTUH
AIRFLOW = 1000 CFM
COMPRESSOR POWER = 2410 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 170 WATTS
S.E.E.R. = 9.80 BTUH/WATT
E.E.R. = 9.10 BTUH/WATT
E.E.R. = 10.20 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
10
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
Metric Units
TTB524CA00A WITH TWE030CA40B
TTB530CA00A WITH TWE030CA40B
AT 1528 CMH
AT 1700 CMH
GROSS CAPACITY IN KILOWATTS
GROSS CAPACITY IN KILOWATTS
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
D.B. W.B. CAP.
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
D.B. W.B. CAP.
22.2
6.1
5.2
4.1
3.0
6.1
5.1
4.0
2.9
6.0
5.1
4.0
2.9
5.9
5.0
3.9
2.8
5.8
4.9
3.8
2.7
5.6
4.7
3.6
2.5
23.3
6.6
5.7
4.6
3.5
6.6
5.6
4.5
3.4
24.4
6.9*
25.6
7.0*
26.7
7.2*
22.2
7.1
6.0
4.8
3.6
7.1
6.0
4.8
3.5
7.0
5.9
4.7
3.5
6.9
5.8
4.6
3.4
6.8
5.7
4.5
3.3
6.5
5.4
4.2
3.0
23.3
7.6
6.6
5.4
4.2
7.6
6.5
5.3
4.1
7.6
6.5
5.3
4.0
7.4
6.4
5.2
3.9
24.4
8.1*
25.6
8.3*
26.7
8.5*
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
6.7
7.2
7.8
8.4
6.6
7.1
7.7
8.2
6.5
7.0
7.6
8.1
6.3
6.8
7.3
7.8
6.1
6.6
7.0
7.5
5.7
6.1
6.5
7.0
1.90
1.97
2.04
2.11
2.01
2.07
2.14
2.21
2.11
2.18
2.25
2.32
2.20
2.26
2.33
2.40
2.29
2.35
2.41
2.48
2.47
2.53
2.58
2.64
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
8.0
8.6
9.3
9.9
7.9
8.5
9.1
9.8
7.8
8.4
9.0
9.7
7.6
8.1
8.7
9.3
7.3
7.9
8.4
9.0
6.8
7.3
7.8
8.4
2.05
2.12
2.20
2.28
2.15
2.23
2.31
2.39
2.25
2.33
2.41
2.49
2.34
2.42
2.50
2.58
2.43
2.51
2.59
2.67
2.62
2.69
2.77
2.84
29.4
32.2
35.0
37.8
40.6
46.1
6.2
5.1
4.0
6.8*
6.1
5.0
3.9
6.7*
6.1
5.0
3.9
6.5*
5.9
4.9
3.8
6.3*
5.9
4.8
3.7
5.9*
5.7
4.6
3.5
6.7
5.6
4.5
7.0*
6.6
5.5
4.4
6.9*
6.6
5.5
4.4
6.7*
6.4
5.4
4.3
6.5*
6.4
5.3
4.2
6.1*
6.1
5.1
4.0
7.1
6.1
5.0
7.1*
7.1
6.0
4.9
7.0*
7.0
6.0
4.9
6.9*
6.9
5.9
4.8
6.7*
6.7
5.8
4.7
6.2*
6.2
5.6
4.5
29.4
32.2
35.0
37.8
40.6
46.1
7.1
5.9
4.7
8.0*
7.1
5.9
4.7
7.9*
7.0
5.8
4.6
7.7*
6.9
5.7
4.5
7.5*
6.8
5.6
4.4
7.1*
6.5
5.3
4.1
7.7
6.5
5.3
8.2*
7.6
6.4
5.2
8.1*
7.6
6.4
5.2
7.9*
7.4
6.3
5.0
7.7*
7.3
6.1
4.9
7.2*
7.1
5.9
4.7
8.2
7.0
5.8
8.4*
8.2
7.0
5.8
8.3*
8.1
6.9
5.7
8.1*
8.0
6.8
5.6
2.0*
7.9
6.7
5.4
7.4*
7.4
6.4
5.2
6.5*
5.6
4.5
3.4
6.4*
5.4
4.4
3.3
6.2*
5.4
4.3
3.2
5.8*
5.2
4.1
3.0
7.3*
6.2
5.0
3.8
6.9*
6.0
4.8
3.6
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
0.368
X0.98
X0.99
0.486
X1.01
X1.01
AIRFLOW
SENS. CAP.
0.368
X0.94
0.486
X1.06
AIRFLOW
TOTAL CAP.
COMPR. KW
0.472
X1.00
X1.00
0.472
X1.00
X1.00
AIRFLOW
SENS. CAP.
0.472
X1.00
0.472
X1.00
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 7.54 KW
AIRFLOW = 0.42 CMS
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.02 KW
AIRFLOW = 0.47 CMS
AIRFLOW = 900. CFM
AIRFLOW = 1000. CFM
COMPRESSOR POWER = 2245 WATTS
I.D. FAN POWER = 425 WATTS
O.D. FAN POWER = 165 WATTS
COP = 2.67
COMPRESSOR POWER = 2410 WATTS
I.D. FAN POWER = 440 WATTS
O.D. FAN POWER = 170 WATTS
COP = 2.99
EER = 9.10 BTU/WATT
EER = 10.20 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
TWE5-PRC000-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
English Units
TTB530CA00A WITH TWE040CA40C
TTB536CA00A WITH TWE040CA40C
AT 1200 CFM
AT 1200 CFM
GROSS CAPACITY IN BTU/H x 1000
GROSS CAPACITY IN BTU/H x 1000
O.D.
I.D. TOTAL
D.B. W.B. CAP.
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
D.B. W.B. CAP.
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
72
74
76
78
80
72
74
76
78
80
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
29.1
31.2
33.4
35.7
28.7
30.8
32.9
35.1
28.3
30.3
32.4
34.6
27.4
29.3
31.3
33.4
26.5
28.3
30.2
32.2
24.6
26.3
28.1
29.9
27.5
22.9
17.8
12.7
27.3
22.7
17.6
12.5
27.1
22.5
17.4
12.3
26.7
22.1
17.0
11.9
26.3
21.7
16.6
11.4
24.8*
20.8
15.7
10.6
29.3*
25.2
20.2
15.0
29.0*
25.0
20.0
14.8
28.6*
24.8
19.8
14.6
27.9*
24.4
19.3
14.2
27.1*
24.0
18.9
13.8
25.5*
23.1
18.1
12.9
30.1*
27.5
22.5
17.4
29.7*
27.3
22.3
17.2
29.4*
27.1
22.1
16.9
28.6*
26.7
21.7
16.5
27.8*
26.3
21.2
16.1
26.1*
25.5
20.4
15.2
30.8*
29.9
24.8
19.7
30.4*
29.7
24.6
19.5
30.1*
29.5
24.4
19.3
29.2*
29.0
24.0
18.8
28.4*
28.4*
23.6
18.4
26.7*
26.7*
22.7
17.6
31.5* 2.18
31.5* 2.26
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
35.2
37.8
40.5
43.3
34.6
37.1
39.8
42.5
33.9
36.4
39.0
41.7
32.7
35.1
37.6
40.2
31.5
33.8
36.2
38.7
29.1
31.2
33.4
35.7
30.5
25.9
20.9
15.7
30.2
25.6
20.5
15.4
29.9
25.3
20.2
15.0
29.3
24.7
19.7
14.5
28.8
24.2
19.1
13.9
27.6
23.0
18.0
12.8
32.8
28.3
23.2
18.0
32.5
27.9
22.9
17.7
32.2
27.6
22.6
17.4
31.7
27.1
22.0
16.8
31.1
26.5
21.4
16.2
29.4*
25.4
20.3
15.1
35.2
30.6
25.5
20.4
34.7*
30.3
25.2
20.0
34.1*
30.0
24.9
19.7
33.2*
29.4
24.3
19.2
32.2*
28.8
23.8
18.6
30.2*
27.7
22.6
17.5
36.0*
32.9
27.9
22.7
35.5*
32.6
27.6
22.4
35.0*
32.3
27.2
22.1
34.0*
31.7
26.7
21.5
33.0*
31.2
26.1
20.9
30.9*
30.0
25.0
19.8
36.9* 2.61
85
90
85
90
35.3
30.2
25.0
2.72
2.83
2.94
27.1
22.0
2.34
2.42
31.1* 2.29
31.1* 2.37
36.4* 2.75
35.0
29.9
24.7
2.85
2.96
3.08
26.9
21.8
2.45
2.54
30.7* 2.40
30.7* 2.48
35.8* 2.88
95
95
34.6
29.6
24.4
2.99
3.10
3.21
26.7
21.6
2.56
2.65
29.9* 2.49
29.9* 2.57
34.8* 2.98
100
105
115
100
105
115
34.1
29.0
23.8
3.09
3.20
3.31
26.3
21.2
2.65
2.74
29.0* 2.58
29.0* 2.66
33.7* 3.08
33.5
28.4
23.3
3.18
3.29
3.40
25.9
20.7
2.74
2.83
27.3* 2.76
27.3* 2.84
31.6* 3.29
31.6* 3.38
25.0
19.9
2.92
3.01
27.3
22.1
3.48
3.59
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
1200
X1.00
X1.00
1200
X1.00
X1.00
AIRFLOW
SENS. CAP.
1200
X1.00
1200
X1.00
AIRFLOW
TOTAL CAP.
COMPR. KW
1200
X1.00
X1.00
1200
X1.00
X1.00
AIRFLOW
SENS. CAP.
1200
X1.00
1200
X1.00
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32400 BTUH
AIRFLOW = 1200 CFM
COMPRESSOR POWER = 2562 WATTS
I.D. FAN POWER = 325 WATTS
O.D. FAN POWER = 170 WATTS
S.E.E.R. = 10.82 BTUH/WATT
E.E.R. = 10.60 BTUH/WATT
GROSS CAPACITY = 39000 BTUH
AIRFLOW = 1200 CFM
COMPRESSOR POWER = 3099 WATTS
I.D. FAN POWER = 325 WATTS
O.D. FAN POWER = 170 WATTS
S.E.E.R. = 10.95 BTUH/WATT
E.E.R. = 10.85 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION AND 5/16 LIQUID LINE
12
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
Metric Units
TTB530CA00A WITH TWE040CA40C
TTB536CA00A WITH TWE040CA40C
AT 2039 CMH
AT 2039 CMH
GROSS CAPACITY IN KILOWATTS
GROSS CAPACITY IN KILOWATTS
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
D.B. W.B. CAP.
22.2
8.1
6.7
5.2
3.7
8.0
6.7
5.2
3.7
7.9
6.6
5.1
3.6
7.8
6.5
5.0
3.5
7.7
6.4
4.9
3.3
23.3
8.6*
24.4
8.8*
25.6
9.0*
8.8
7.3
5.8
8.9*
8.7
7.2
5.7
8.8*
8.6
7.1
5.7
8.6*
8.5
26.7
9.2*
9.2*
7.9
D.B. W.B. CAP.
22.2
8.9
7.6
6.1
4.6
8.8
7.5
6.0
4.5
8.8
7.4
5.9
4.4
8.6
7.2
5.8
4.2
8.4
7.1
5.6
4.1
8.1
6.7
5.3
3.8
23.3
9.6
8.3
6.8
5.3
9.5
8.2
6.7
5.2
9.4
8.1
6.6
5.1
9.3
7.9
6.4
4.9
9.1
7.8
6.3
4.7
24.4
10.3
9.0
25.6
10.5*
9.6
26.7
10.8*
10.3
8.8
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
8.5
9.1
9.8
10.5
8.4
9.0
9.6
10.3
8.3
8.9
9.5
10.1
8.0
8.6
9.2
9.8
7.8
8.3
8.8
9.4
7.2
7.7
8.2
8.8
2.18
2.26
2.34
2.42
2.29
2.37
2.45
2.54
2.40
2.48
2.56
2.65
2.49
2.57
2.65
2.74
2.58
2.66
2.74
2.83
2.76
2.84
2.92
3.01
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
10.3
11.1
11.9
12.7
10.1
10.9
11.7
12.5
9.9
10.7
11.4
12.2
9.6
2.61
2.72
2.83
2.94
2.75
2.85
2.96
3.08
2.88
2.99
3.10
3.21
2.98
3.09
3.20
3.31
3.08
3.18
3.29
3.40
3.29
3.38
3.48
3.59
29.4
32.2
35.0
37.8
40.6
46.1
7.4
5.9
4.4
8.5*
7.3
5.9
4.3
8.4*
7.3
5.8
4.3
8.2*
7.1
5.7
4.2
7.9*
7.0
5.5
4.0
7.5*
6.8
5.3
3.8
8.1
6.6
5.1
8.7*
8.0
6.5
5.0
8.6*
7.9
6.5
5.0
8.4*
7.8
6.4
4.8
8.1*
7.7
6.2
4.7
7.6*
7.5
6.0
4.5
29.4
32.2
35.0
37.8
40.6
46.1
7.5
8.2
6.4
6.0
10.2*
8.9
7.4
5.9
10.0*
8.8
7.3
5.8
9.7*
8.6
7.1
5.6
9.4*
8.4
6.7
10.4*
9.6
8.1
6.6
10.3*
9.5
8.0
6.5
10.0*
9.3
7.8
6.3
9.7*
9.1
7.3
9.1*
9.1*
7.9
10.7*
10.3
8.8
6.4
7.2
9.0*
9.0*
7.8
10.5*
10.1
8.7
6.3
7.1
8.8*
8.8*
7.7
10.2*
10.0
8.5
7.0
9.9*
9.8
8.3
6.8
10.3
11.0
11.8
9.2
7.0
5.5
6.2
8.3*
8.3*
6.9
8.5*
8.5*
7.6
6.1
8.0*
8.0
7.3
5.8
9.9
10.6
11.3
8.5
9.1
9.8
7.0
5.4
8.8*
8.1
6.6
5.1
7.6
6.1
9.1*
8.8
7.3
5.8
5.4
7.3*
7.8*
7.8
6.7
8.6*
9.3*
9.3*
8.0
6.1
4.6
3.1
7.4
5.9
4.4
5.2
10.5
6.5
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
566
566
AIRFLOW
566
566
AIRFLOW
566
566
AIRFLOW
566
566
TOTAL CAP.
COMPR. KW
X1.00
X1.00
X1.00
X1.00
SENS. CAP.
X1.00
X1.00
TOTAL CAP.
COMPR. KW
X1.00
X1.00
X1.00
X1.00
SENS. CAP.
X1.00
X1.00
VALUES AT ARI RATING CONDITIONS
VALUES AT ARI RATING CONDITIONS
GROSS CAPACITY = 9.48 KW
AIRFLOW = 0.57 CMS
COMPRESSOR POWER = 2562WATTS
I.D. FAN POWER = 325 WATTS
O.D. FAN POWER = 170 WATTS
COP = 3.11
GROSS CAPACITY = 11.41 KW
AIRFLOW = 0.57 CMS
COMPRESSOR POWER = 3099 WATTS
I.D. FAN POWER = 325 WATTS
O.D. FAN POWER = 170 WATTS
COP = 3.18
EER = 10.60 BTU/WATT
EER = 10.85 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCTION AND 5/16 IN. LIQUID LINES
TWE5-PRC000-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
English Units
TTA030CD WITH TWE030CA4
TTA030CD WITH TWE040CA4-B
AT 1000 CFM
AT 1125 CFM
GROSS CAPACITY IN BTU/H x 1000
GROSS CAPACITY IN BTU/H x 1000
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
D.B. W.B. CAP.
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
30.7* 2.34
D.B. W.B. CAP.
72
74
76
78
80
72
74
76
78
80
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
27.3
29.5
31.7
34.1
26.8
28.9
31.1
33.4
26.3
28.3
30.5
32.7
25.6
27.6
29.7
31.8
24.9
26.9
28.9
31.0
23.6
25.4
27.3
29.2
21.8
18.5
14.9
11.2
21.6
18.3
14.7
10.9
21.4
18.1
14.4
10.7
21.1
17.8
14.1
10.4
20.8
17.5
13.8
10.1
20.2
16.9
13.2
9.5
23.5
20.2
16.6
12.9
23.3
20.0
16.4
12.6
23.1
19.8
16.1
12.4
22.8
19.5
15.8
12.1
22.5
19.2
15.5
11.8
21.9
18.6
14.9
11.2
25.2
21.9
18.3
14.6
25.0
21.7
18.1
14.3
24.8
21.5
17.8
14.1
24.5
21.2
17.5
13.8
24.2
20.9
17.2
13.5
23.7*
20.3
16.6
12.9
26.9
23.6
20.0
16.3
26.7
23.4
19.8
16.0
26.4*
23.2
19.5
15.8
25.9*
22.9
19.2
15.5
25.3*
22.6
18.9
15.2
24.2*
22.0
18.3
14.6
27.9* 2.27
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
29.4
31.7
34.0
36.5
28.8
31.0
33.3
35.6
28.2
30.3
32.5
34.8
27.4
29.4
31.5
33.8
26.6
28.5
30.6
32.7
25.0
26.8
28.7
30.6
24.8
20.9
16.5
12.1
24.6
20.6
16.2
11.8
24.3
20.3
15.9
11.5
23.9
20.0
15.6
11.1
23.6
19.6
15.2
10.8
22.9
18.9
14.5
10.0
26.8
22.9
18.5
14.1
26.6
22.6
18.2
13.8
26.3
22.3
18.0
13.5
26.0
22.0
17.6
13.1
25.6
21.6
17.3
12.8
25.0
21.0
16.6
12.1
28.9
24.9
20.6
16.1
28.6
24.6
20.3
15.8
28.3*
24.4
20.0
15.5
27.7*
24.0
19.6
15.2
27.0*
23.7
19.3
14.8
25.7*
23.0
18.6
14.1
30.0*
27.0
22.6
18.1
29.5*
26.7
22.3
17.8
29.0*
26.4
22.0
17.6
28.3*
26.0
21.7
17.2
27.6*
25.7
21.3
16.8
26.3*
25.0
20.6
16.1
85
90
25.3
21.7
18.0
2.35
2.43
2.51
85
90
29.0
24.6
20.2
2.42
2.50
2.59
27.5* 2.38
30.2* 2.45
25.1
21.5
17.7
2.46
2.54
2.63
28.7
24.3
19.9
2.53
2.62
2.71
27.1* 2.49
29.7* 2.57
95
24.9
21.2
17.5
2.57
2.65
2.74
95
28.4
24.0
19.6
2.65
2.73
2.82
26.5* 2.61
29.0* 2.69
100
105
115
24.6
20.9
17.2
2.69
2.77
2.85
100
105
115
28.1
23.7
19.2
2.77
2.85
2.94
26.0* 2.73
28.3* 2.81
24.3
20.6
16.9
2.80
2.88
2.96
27.7
23.3
18.9
2.89
2.97
3.05
24.8* 2.97
26.9* 3.06
23.7
20.0
16.3
3.04
3.11
3.19
26.9*
22.6
18.2
3.13
3.20
3.28
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
975
X0.98
X0.99
1275
X1.01
X1.01
AIRFLOW
SENS. CAP.
975
X0.94
1275
X1.06
AIRFLOW
TOTAL CAP.
COMPR. KW
975
X0.98
X0.99
1275
X1.01
X1.01
AIRFLOW
SENS. CAP.
975
X0.94
1275
X1.06
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 32500 BTUH
AIRFLOW = 1125 CFM
GROSS CAPACITY = 32500 BTUH
AIRFLOW = 1125 CFM
COMPRESSOR POWER = 2733 WATTS
I.D. FAN POWER = 290 WATTS
O.D. FAN POWER = 227 WATTS
E.E.R. = 9.60 BTUH/WATT
COMPRESSOR POWER = 2733 WATTS
I.D. FAN POWER = 290 WATTS
O.D. FAN POWER = 227 WATTS
E.E.R. = 9.60 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION AND 3/8 LIQUID LINE
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
14
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
Metric Units
TTA030CD00A WITH TWE030CA40B
TTA030CD00A WITH TWE040CA40C
AT 1700 CMH
AT 1911 CMH
GROSS CAPACITY IN KILOWATTS
GROSS CAPACITY IN KILOWATTS
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
D.B. W.B. CAP.
22.2
6.4
5.4
4.4
3.3
6.3
5.4
4.3
3.2
6.3
5.3
4.2
3.1
6.2
5.2
4.1
3.0
6.1
5.1
4.0
3.0
5.9
5.0
3.9
2.8
23.3
6.9
5.9
4.9
3.8
6.8
5.9
4.8
3.7
6.8
5.8
4.7
3.6
6.7
5.7
4.6
3.5
6.6
5.6
4.5
3.5
6.4
5.4
4.4
3.3
24.4
7.4
6.4
5.4
4.3
7.3
6.4
5.3
4.2
7.3
6.3
5.2
4.1
7.2
6.2
5.1
4.0
7.1
6.1
5.0
4.0
25.6
7.9
6.9
5.9
4.8
7.8
6.9
5.8
4.7
26.7
8.2*
D.B. W.B. CAP.
22.2
7.3
6.1
4.8
3.5
7.2
6.0
4.7
3.5
7.1
5.9
4.7
3.4
7.0
5.9
4.6
3.3
6.9
5.7
4.5
3.2
6.7
5.5
4.2
2.9
23.3
7.9
6.7
5.4
4.1
7.8
6.6
5.3
4.0
7.7
6.5
5.3
4.0
7.6
6.4
5.2
3.8
7.5
6.3
5.1
3.8
7.3
6.2
4.9
3.5
24.4
8.5
7.3
6.0
4.7
8.4
7.2
5.9
4.6
25.6
8.8*
26.7
9.0*
8.5
7.2
5.9
8.8*
8.4
7.1
5.8
8.7*
8.3
7.0
5.7
8.5*
8.2
6.9
5.6
8.3*
8.1
6.8
5.5
7.9*
7.9*
6.6
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
8.0
8.6
9.3
10.0
7.9
8.5
9.1
9.8
7.7
8.3
8.9
9.6
7.5
8.1
8.7
9.3
7.3
7.9
8.5
9.1
6.9
7.4
8.0
8.6
2.27
2.35
2.43
2.51
2.38
2.46
2.54
2.63
2.49
2.57
2.65
2.74
2.61
2.69
2.77
2.85
2.73
2.80
2.88
2.96
2.97
3.04
3.11
3.19
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
8.6
9.3
10.0
10.7
8.4
9.1
9.8
10.4
8.3
8.9
9.5
10.2
8.0
8.6
9.2
9.9
7.8
8.4
9.0
9.6
7.3
7.9
8.4
9.0
2.34
2.42
2.50
2.59
2.45
2.53
2.62
2.71
2.57
2.65
2.73
2.82
2.69
2.77
2.85
2.94
2.81
2.89
2.97
3.05
3.06
3.13
3.20
3.28
29.4
32.2
35.0
37.8
40.6
46.1
7.4
6.4
5.3
8.1*
7.4
6.3
5.2
7.9*
7.3
6.2
5.1
7.8*
7.2
6.1
5.0
7.6*
7.1
6.0
5.0
7.3*
6.9
5.9
4.8
29.4
32.2
35.0
37.8
40.6
46.1
7.9
6.6
5.3
8.6*
7.8
6.5
5.2
8.5*
7.7
6.4
5.2
8.3*
7.6
6.4
5.0
8.1*
7.5
6.2
4.9
7.7*
7.3
6.0
4.7
7.7*
8.3*
6.8
5.7
4.6
7.6*
6.7
5.6
4.5
7.4*
6.6
5.5
4.5
7.1*
6.4
5.4
4.3
7.1
5.9
4.5
8.1*
7.0
5.7
4.5
7.9*
6.9
5.7
4.3
7.5*
6.7
5.4
4.1
6.9*
5.9
4.9
3.8
5.3
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
975
X0.98
X0.99
1275
X1.01
X1.01
AIRFLOW
SENS. CAP.
975
X0.94
1275
X1.06
AIRFLOW
TOTAL CAP.
COMPR. KW
975
X0.98
X0.99
1275
X1.01
X1.01
AIRFLOW
SENS. CAP.
975
X0.94
1275
X1.06
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 8.94 KW
AIRFLOW = 0.57 CMS
COMPRESSOR POWER = 2653 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 227 WATTS
EER = 8.75 BTU/WATT
GROSS CAPACITY = 9.5 KW
AIRFLOW = 1913 CMH
COMPRESSOR POWER = 2653 WATTS
I.D. FAN POWER = 430 WATTS
O.D. FAN POWER = 227 WATTS
EER = 8.75 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCTION AND 7/8 IN. LIQUID LINES
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCTION AND 7/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
TWE5-PRC000-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
English Units
TTA040CD WITH TWE040CA4B
TTA040CD WITH TWE050CA5C
AT 1325 CFM
AT 1600 CFM
GROSS CAPACITY IN BTU/H x 1000
GROSS CAPACITY IN BTU/H x 1000
O.D.
D.B.
I.D. GROSS
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
D.B.
I.D. GROSS
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
41.3* 42.2* 3.16
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
CAP.
36.9
39.7
42.6
45.6
36.2
38.9
41.7
44.6
35.4
38.0
40.8
43.6
34.5
37.0
39.7
42.4
33.5
36.0
38.6
41.2
31.6
33.9
36.3
38.8
72
74
76
78
80
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
CAP.
40.5
43.4
46.4
49.5
39.4
42.2
45.1
48.2
38.4
41.1
43.9
46.8
37.3
39.9
42.6
45.4
36.1
38.7
41.3
44.0
33.9
36.2
38.7
41.2
72
74
76
78
80
29.5
25.0
20.0
14.9
29.2
24.7
19.7
14.6
28.9
24.3
19.3
14.2
28.5
23.9
18.9
13.8
28.1
23.5
18.5
13.4
27.3
22.7
17.7
12.6
31.8
27.3
22.3
17.2
31.5
27.0
22.0
16.9
31.2
26.6
21.7
16.6
30.8
26.2
21.2
16.1
30.4
25.8
20.8
15.7
29.6
25.0
20.0
14.9
34.1
29.6
24.6
19.6
33.8
29.3
24.3
19.2
33.5
29.0
24.0
18.9
33.1
28.5
23.5
18.4
32.7
28.1
23.1
18.0
31.8*
27.3
22.3
17.2
36.4
31.9
26.9
21.9
36.1
31.6
26.6
21.5
37.7* 3.24
34.2
28.6
22.5
16.2
33.8
28.2
22.0
15.8
33.3
27.7
21.6
15.3
32.9
27.3
21.1
14.8
32.4
26.8
20.6
14.4
31.5
25.8
19.7
13.4
37.0
31.5
25.3
19.1
36.6
31.0
24.9
18.6
36.2
30.6
24.4
18.1
35.7
30.1
23.9
17.7
35.2
29.6
23.5
17.2
34.1*
28.7
22.5
16.2
39.9
34.3
28.1
21.9
39.4
33.8
27.7
21.4
38.7*
33.4
27.2
21.0
37.7*
32.9
26.7
20.5
36.8*
32.4
26.3
20.0
34.9*
31.5
25.3
19.1
85
34.2
29.3
24.2
3.37
3.51
3.64
85
37.1
31.0
24.7
39.9
33.8
27.5
3.29
3.43
3.57
37.1* 3.39
40.4* 41.3* 3.29
90
33.9
28.9
23.8
3.53
3.66
3.81
90
36.7
30.5
24.2
39.5
33.3
27.1
3.42
3.57
3.71
35.6* 36.5* 3.54
39.6* 40.4* 3.42
95
31.3
26.3
21.2
33.6
28.6
23.5
3.68
3.82
3.97
95
36.2
30.0
23.8
39.0
32.9
26.6
3.56
3.70
3.85
34.9* 35.7* 3.70
38.6* 39.5* 3.55
100
105
115
30.9
25.9
20.7
33.2
28.2
23.1
3.84
3.99
4.14
100
105
115
35.7
29.6
23.3
38.5
32.4
26.1
3.69
3.84
4.00
34.1* 34.9* 3.85
37.7* 38.5* 3.69
30.4
25.4
20.3
32.8
27.7
22.6
4.00
4.15
4.31
35.2
29.1
22.8
38.1
31.9
25.6
3.83
3.98
4.14
32.5* 33.3* 4.17
35.7* 36.5* 3.96
29.6
24.6
19.5
31.9
26.9
21.8
4.32
4.48
4.65
34.3
28.1
21.9
36.5* 4.11
31.0
24.7
4.26
4.42
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
1150
X0.98
X0.99
1500
X1.02
X1.01
AIRFLOW
SENS. CAP.
1150
X0.94
1500
X1.06
AIRFLOW
TOTAL CAP.
COMPR. KW
1375
X0.98
X0.99
1775
X1.01
X1.01
AIRFLOW
SENS. CAP.
1375
X0.93
1775
X1.05
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 40800 BTUH
AIRFLOW = 1325 CFM
COMPRESSOR POWER = 3820 WATTS
I.D. FAN POWER = 380 WATTS
O.D. FAN POWER = 197 WATTS
E.E.R. = 9.00 BTUH/WATT
GROSS CAPACITY = 43900 BTUH
AIRFLOW = 1570 CFM
COMPRESSOR POWER = 3720 WATTS
I.D. FAN POWER = 530 WATTS
O.D. FAN POWER = 197 WATTS
E.E.R. = 9.45 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
16
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
Metric Units
TTA040CD00A WITH TWE050CA50D
TTA040CD00A WITH TWE040CA40C
AT 2250 CMH
AT 2717 CMH
GROSS CAPACITY IN KILOWATTS
GROSS CAPACITY IN KILOWATTS
O.D.
I.D. TOTAL
D.B. W.B. CAP.
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
22.2
10.0
8.4
6.6
4.7
9.9
8.3
6.4
4.6
9.8
8.1
6.3
4.5
9.6
8.0
6.2
4.3
9.5
7.9
6.0
4.2
9.2
7.6
5.8
3.9
23.3
10.8
9.2
7.4
5.6
10.7
9.1
7.3
5.4
10.6
9.0
7.1
5.3
10.5
8.8
7.0
5.2
10.3
8.7
6.9
5.0
10.0*
8.4
24.4
11.7
10.0
8.2
6.4
11.5
9.9
8.1
6.3
11.3*
9.8
8.0
6.2
11.0*
9.6
7.8
6.0
10.8*
9.5
7.7
5.9
10.2*
9.2
25.6
12.1*
10.9
9.1
26.7
12.4*
11.7
9.9
D.B. W.B. CAP.
22.2
8.6
7.3
5.9
4.4
8.6
7.2
5.8
4.3
8.5
7.1
5.7
4.2
8.4
7.0
5.5
4.0
8.2
6.9
5.4
3.9
8.0
6.7
5.2
3.7
23.3
9.3
8.0
6.5
5.0
9.2
7.9
6.4
5.0
9.1
7.8
6.4
4.9
9.0
7.7
6.2
4.7
8.9
7.6
6.1
4.6
8.7
7.3
5.9
4.4
24.4
10.0
8.7
7.2
5.7
9.9
8.6
7.1
5.6
9.8
8.5
7.0
5.5
9.7
8.4
6.9
5.4
25.6
10.7
9.3
26.7
11.0*
10.0
8.6
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
11.9
12.7
13.6
14.5
11.5
12.4
13.2
14.1
11.3
12.0
12.9
13.7
10.9
11.7
12.5
13.3
10.6
11.3
12.1
12.9
9.9
3.16
3.29
3.43
3.57
3.29
3.42
3.57
3.71
3.42
3.56
3.70
3.85
3.55
3.69
3.84
4.00
3.69
3.83
3.98
4.14
3.96
4.11
4.26
4.42
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
10.8
11.6
12.5
13.4
10.6
11.4
12.2
13.1
10.4
11.1
12.0
12.8
10.1
10.8
11.6
12.4
9.8
10.5
11.3
12.1
9.3
9.9
10.6
11.4
3.24
3.37
3.51
3.64
3.39
3.53
3.66
3.81
3.54
3.68
3.82
3.97
3.70
3.84
3.99
4.14
3.85
4.00
4.15
4.31
4.17
4.32
4.48
4.65
29.4
32.2
35.0
37.8
40.6
46.1
29.4
32.2
35.0
37.8
40.6
46.1
7.9
6.4
10.6
9.3
7.8
6.3
10.4*
9.2
7.7
6.2
10.2*
9.1
7.6
6.1
10.0*
8.9
7.4
5.9
9.5*
8.7
7.2
5.7
7.2
8.1
7.1
11.8*
10.8
8.9
12.1*
11.6
9.8
10.9*
9.9
8.5
7.0
7.1
7.9
11.6*
10.6
8.8
11.8*
11.4
9.6
10.7*
9.8
8.4
6.9
7.0
7.8
11.3*
10.5
8.7
11.6*
11.3
9.5
10.5*
9.7
8.3
6.8
6.8
7.6
11.0*
10.3
8.5
11.3*
11.2
9.3
9.6*
10.2*
8.2
6.8
5.3
9.3*
8.0
6.5
5.0
9.6
8.1
6.6
9.8*
9.3
7.9
6.4
6.7
7.5
10.5*
10.0
8.2
10.7*
10.7
9.1
10.6
11.3
12.1
6.6
4.7
7.4
5.6
6.4
7.2
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
1375
X0.98
X0.99
1775
X1.01
X1.01
AIRFLOW
SENS. CAP.
1375
X0.93
1775
X1.05
AIRFLOW
TOTAL CAP.
COMPR. KW
1150
X0.98
X0.99
1500
X1.02
X1.01
AIRFLOW
SENS. CAP.
1150
X0.94
1500
X1.06
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 12.0 KW
AIRFLOW = 2253 CMS
GROSS CAPACITY = 12.0 KW
AIRFLOW = 2253 CMS
COMPRESSOR POWER = 3720 WATTS
I.D. FAN POWER = 380 WATTS
O.D. FAN POWER = 197 WATTS
EER = 9.00 BTU/WATT
COMPRESSOR POWER = 3820 WATTS
I.D. FAN POWER = 380 WATTS
O.D. FAN POWER = 197 WATTS
EER = 9.00 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
TWE5-PRC000-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
English Units
TTA060CD WITH TWE050CA5C
TTA050CD WITH TWE050CA5C
AT 1800 CFM
AT 1800 CFM
GROSS CAPACITY IN BTU/H x 1000
GROSS CAPACITY IN BTU/H x 1000
O.D.
D.B.
I.D. GROSS
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
D.B.
I.D. GROSS
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
CAP.
57.5
61.6
65.8
70.2
56.2
60.2
64.3
68.6
54.9
58.8
62.8
66.9
53.5
57.3
61.2
65.2
52.2
55.8
59.6
63.5
49.4
52.8
56.4
60.0
72
74
76
78
80
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
CAP.
48.8
52.1
55.5
59.0
47.6
50.8
54.1
57.5
46.4
49.5
52.7
56.0
45.1
48.1
51.2
54.4
43.8
46.7
49.6
52.7
41.2
43.8
46.6
49.4
72
74
76
78
80
43.6
37.4
30.6
23.5
43.0
36.9
30.0
22.9
42.5
36.3
29.4
22.3
41.9
35.7
28.8
21.7
41.3
35.0
28.2
21.1
40.1
33.8
26.9
19.9
46.8
40.6
33.7
26.7
46.2
40.0
33.1
26.1
45.6
39.4
32.5
25.5
45.0
38.8
31.9
24.9
44.4
38.2
31.3
24.2
43.2
37.0
30.1
23.0
49.9
43.7
36.8
29.8
49.3
43.1
36.2
29.2
48.7
42.5
35.7
28.6
48.1
41.9
35.0
28.0
47.5
41.3
34.4
27.4
46.3
40.1
33.2
26.2
53.0
46.8
40.0
32.9
52.5
46.3
39.4
32.3
51.9
45.7
38.8
31.7
51.3
45.1
38.2
31.1
50.7
44.5
37.6
30.5
56.2
50.0
43.1
36.1
55.6
49.4
42.5
35.5
4.71
4.87
5.04
5.22
4.90
5.06
5.23
5.40
39.4
33.2
26.3
19.3
38.9
32.7
25.8
18.8
38.4
32.1
25.3
18.3
37.8
31.6
24.7
17.7
37.3
31.0
24.2
17.2
36.2
29.9
23.0
16.1
42.5
36.3
29.4
22.4
42.0
35.8
28.9
21.9
41.5
35.3
28.4
21.4
40.9
34.7
27.8
20.8
40.4
34.1
27.3
20.3
39.3
33.0
26.1
19.2
45.6
39.4
32.5
25.5
45.1
38.9
32.0
25.0
44.6
38.4
31.5
24.5
44.0
37.8
30.9
23.9
43.5
37.2
30.4
23.4
41.6*
36.1
29.2
22.3
48.7
42.5
35.6
28.6
47.9*
42.0
35.1
28.1
49.9*
45.6
38.7
31.7
48.9*
45.1
38.2
31.2
3.62
3.75
3.89
4.03
3.77
3.91
4.05
4.19
3.93
4.07
4.21
4.35
4.09
4.23
4.37
4.51
4.25
4.38
4.52
4.67
4.57
4.71
4.84
4.98
85
85
90
90
55.0* 5.09
47.0* 47.9*
95
48.8
41.9
34.9
5.25
5.42
5.59
95
41.5
34.6
27.6
44.6
37.7
30.7
54.0* 5.31
45.9* 46.8*
100
105
115
48.2
41.3
34.3
5.47
5.63
5.79
100
105
115
40.9
34.0
27.0
44.0
37.1
30.1
52.9* 5.53
44.8* 45.7*
47.6
40.7
33.7
5.68
5.84
6.00
40.3
33.5
26.5
43.4
36.6
29.6
49.4* 50.6* 5.98
42.5* 43.4*
43.2
36.3
29.3
46.4
39.5
32.4
6.12
6.26
6.41
39.2
32.3
25.4
42.3
35.4
28.5
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
1525
X0.98
X0.98
1975
X1.01
X1.01
AIRFLOW
SENS. CAP.
1525
X0.94
1975
X1.04
AIRFLOW
TOTAL CAP.
COMPR. KW
1525
X0.98
X0.99
1975
X1.01
X1.01
AIRFLOW
SENS. CAP.
1525
X0.93
1975
X1.04
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 62500 BTUH
AIRFLOW = 1750 CFM
GROSS CAPACITY = 52500 BTUH
AIRFLOW = 1750 CFM
COMPRESSOR POWER = 5402 WATTS
I.D. FAN POWER = 730 WATTS
O.D. FAN POWER = 386 WATTS
E.E.R. = 9.15 BTUH/WATT
COMPRESSOR POWER = 4202 WATTS
I.D. FAN POWER = 730 WATTS
O.D. FAN POWER = 202 WATTS
E.E.R. = 9.75 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
18
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance Data
Cooling
Metric Units
TTA060CD WITH TWE050CA5C
TTA050CD WITH TWE050CA5C
AT 3056 CMH
AT 3056 CMH
GROSS CAPACITY IN KILOWATTS
GROSS CAPACITY IN KILOWATTS
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
O.D.
I.D. TOTAL
SENS. CAP. AT ENTERING D.B. TEMP.
COMPR.
KW
D.B. W.B. CAP.
22.2
12.8
11.0
9.0
23.3
13.7
11.9
9.9
24.4
14.6
12.8
10.8
8.7
25.6
15.5
13.7
11.7
9.6
26.7
16.5
14.7
12.6
10.6
16.3
14.5
12.5
10.4
16.1*
14.3
12.3
10.2
15.8*
14.1
12.1
10.0
15.5*
13.9
11.9
9.9
D.B. W.B. CAP.
22.2
11.5
9.7
23.3
12.5
10.6
8.6
24.4
13.4
11.5
9.5
25.6
14.3
12.5
10.4
8.4
26.7
14.6*
13.4
11.3
9.3
14.3*
13.2
11.2
9.1
14.0*
13.1
11.0
9.0
13.7*
12.9
10.9
8.8
13.4*
12.7
10.7
8.7
12.7*
12.4
10.4
8.4
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
16.8
18.0
19.3
20.6
16.5
17.6
18.8
20.1
16.1
17.2
18.4
19.6
15.7
16.8
17.9
19.1
15.3
16.3
17.5
18.6
14.5
15.5
16.5
17.6
4.71
4.87
5.04
5.22
4.90
5.06
5.23
5.40
5.09
5.25
5.42
5.59
5.31
5.47
5.63
5.79
5.53
5.68
5.84
6.00
5.98
6.12
6.26
6.41
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
14.3
15.3
16.3
17.3
13.9
14.9
15.9
16.8
13.6
14.5
15.4
16.4
13.2
14.1
15.0
15.9
12.8
13.7
14.5
15.4
12.1
12.8
13.7
14.5
3.62
3.75
3.89
4.03
3.77
3.91
4.05
4.19
3.93
4.07
4.21
4.35
4.09
4.23
4.37
4.51
4.25
4.38
4.52
4.67
4.57
4.71
4.84
4.98
29.4
32.2
35.0
37.8
40.6
46.1
29.4
32.2
35.0
37.8
40.6
46.1
7.7
5.7
6.9
7.8
6.6
7.5
12.6
10.8
8.8
13.5
11.7
9.7
14.4
12.6
10.6
8.6
15.4
13.6
11.5
9.5
11.4
9.6
7.6
12.3
10.5
8.5
13.2
11.4
9.4
14.0*
12.3
10.3
8.2
6.7
7.6
5.5
6.4
7.3
12.5
10.6
8.6
13.4
11.5
9.5
14.3
12.5
10.5
8.4
15.2
13.4
11.4
9.3
11.3
12.2
10.3
8.3
13.1
11.3
9.2
13.8*
12.2
10.1
8.1
9.4
7.4
5.4
6.5
7.5
6.3
7.2
12.3
10.5
8.4
13.2
11.4
9.3
14.1
12.3
10.3
8.2
15.0
13.2
11.2
9.1
11.1
12.0
10.2
8.1
12.9
11.1
9.1
13.4*
12.0
10.0
7.9
9.3
7.2
5.2
6.4
7.3
6.1
7.0
12.1
10.3
8.3
13.0
11.2
9.2
13.9
12.1
10.1
8.0
14.9
13.0
11.0
8.9
10.9
9.1
7.1
5.0
11.8
10.0
8.0
12.7
10.9
8.9
13.1*
11.8
9.8
6.2
7.1
5.9
6.9
7.8
11.7
12.7
10.8
8.8
13.6
11.7
9.7
14.5*
12.7
10.6
8.6
14.8*
13.6
11.6
9.5
10.6
8.8
6.7
11.5
9.7
7.6
12.2*
10.6
8.6
12.5*
11.5
9.5
9.9
7.9
5.8
6.7
7.7
4.7
5.6
6.5
7.4
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
CORRECTION FACTORS - OTHER AIRFLOWS (MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
COMPR. KW
1525
X0.98
X0.98
1975
X1.01
X1.01
AIRFLOW
SENS. CAP.
1525
X0.94
1975
X1.04
AIRFLOW
TOTAL CAP.
COMPR. KW
1525
X0.98
X0.99
1975
X1.01
X1.01
AIRFLOW
SENS. CAP.
1525
X0.93
1975
X1.04
VALUES AT 95/80/67 RATING CONDITIONS
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 14.6 KW
AIRFLOW = 3056 CMH
GROSS CAPACITY = 14.6 KW
AIRFLOW = 3056 CMH
COMPRESSOR POWER = 4202 WATTS
I.D. FAN POWER = 730 WATTS
O.D. FAN POWER = 202 WATTS
EER = 9.75 BTU/WATT
COMPRESSOR POWER = 4202 WATTS
I.D. FAN POWER = 730 WATTS
O.D. FAN POWER = 202 WATTS
EER = 9.75 BTU/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCTION AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
* DRY COIL CONDITION (TOTAL CAPACITY = SENSIBLE CAPACITY)
TOTAL CAPACITY AND COMP. KW ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F
TWE5-PRC000-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Evaporator Fan Performance
BLOWER PERFORMANCE — TWE030CA40B — WET COIL
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
MED
220 VOLTS
MED
CFM
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200
CMH
Hl
LO
Hl
LO
1018.8
1103.7
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
0.72 (179.4)
0.62 (154.4)
0.51 (127.0)
0.40
0.29
0.18
0.06
0.71
0.61
0.50
0.39
0.28
0.17
0.08
(176.9)
(152.0)
(124.6)
(97.1)
(69.7)
(42.3)
(19.9)
0.86 (214.2)
0.75 (186.8)
0.65 (161.9)
0.54 (134.5)
0.43 (107.1)
0.84 (209.2)
0.72 (179.4)
0.62 (154.4)
0.51 (127.0)
(99.6)
(72.2)
(44.8)
(14.9)
0.89 (221.7)
0.81 (201.8)
0.72 (179.4)
0.63 (156.9)
0.53 (132.0)
0.42 (104.6)
0.87 (216.7)
0.79 (196.8)
0.69 (171.9)
0.61 (152.0)
0.51 (127.0)
0.40
0.31
0.22
0.10
0.40
0.30
0.17
0.02
(99.6)
(74.7)
(42.3)
(5.0)
0.32
0.21
0.10
(79.7)
(52.3)
(24.9)
(99.6)
(77.2)
(54.8)
(24.9)
0.31
0.20
0.08
(77.2)
(49.8)
(19.9)
NOTES:
Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. for horizontal left.
BLOWER PERFORMANCE — TWE040CA40C — WET COIL
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
MED
220 VOLTS
MED
CFM
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
CMH
Hl
LO
Hl
LO
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0
0.58 (144.5)
0.61 (152.0)
0.58 (144.5)
0.54 (134.5)
0.51 (127.0)
0.47 (117.1)
0.43 (107.1)
0.55 (137.0)
0.52 (129.5)
0.48 (119.6)
0.44 (109.6)
0.61 (152.0)
0.57 (142.0)
0.53 (132.0)
0.49 (122.1)
0.45 (112.1)
0.58
0.52
0.49
0.45
0.40
0.35
0.30
0.22
0.17
0.10
(144.5)
(129.5)
(122.1)
(112.1)
(99.6)
(87.2)
(74.7)
(54.8)
(42.3)
(24.9)
0.40
0.34
0.28
0.22
0.15
0.08
0.00
0.26
(99.6)
(84.7)
(69.7)
(54.8)
(37.4)
(19.9)
(0.0)
0.57 (142.0)
0.50 (124.6)
0.45 (112.1)
0.53 (132.0)
0.48 (119.6)
0.43 (107.1)
0.40
0.36
0.31
0.26
0.21
0.17
0.11
0.06
0.01
0.00
(99.6)
(89.7)
(77.2)
(64.8)
(52.3)
(42.3)
(27.4)
(14.9)
(2.5)
0.38
0.34
0.29
0.24
0.18
0.13
0.07
0.01
(94.7)
(84.7)
(72.2)
(59.8)
(44.8)
(32.4)
(17.4)
(2.5)
0.40
0.37
0.32
0.28
0.01
0.18
0.12
0.08
0.02
(99.6)
(92.2)
(79.7)
(69.7)
(2.5)
(44.8)
(29.9)
(19.9)
(5.0)
0.39
0.35
0.31
0.22
0.21
0.15
0.11
0.05
(97.1)
(87.2)
(77.2)
(54.8)
(52.3)
(37.4)
(27.4)
(12.5)
(64.8)
NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. for horizontal left.
20
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
BLOWER PERFORMANCE — TWE050CA50D — WET COIL
EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)
UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
MED
220 VOLTS
MED
CFM
900
CMH
Hl
LO
Hl
LO
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0
2631.9
2716.8
2801.7
2886.6
2971.5
3056.4
3141.3
3226.2
3311.1
950
0.63 (156.9)
0.61 (152.0)
0.58 (144.5)
0.54 (134.5)
0.50 (124.6)
0.45 (112.1)
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950
0.62
0.60
0.57
0.53
0.49
0.44
0.38
0.32
0.25
0.18
0.11
0.00
(154.4)
(149.5)
(142.0)
(132.0)
(122.1)
(109.6)
(94.7)
(79.7)
(62.3)
(44.8)
(27.4)
(0.0)
0.61 (152.0)
0.57 (142.0)
0.53 (132.0)
0.49 (122.1)
0.45 (112.1)
0.39
0.33
0.26
0.18
0.10
0.01
(97.1)
(82.2)
(64.8)
(44.8)
(24.9)
(2.5)
0.64 (159.4)
0.59 (147.0)
0.56 (139.5)
0.52 (129.5)
0.48 (119.6)
0.44 (109.6)
0.40 (99.6)
0.35 (87.2)
0.31 (77.2)
0.26 (64.8)
0.21 (52.3)
0.16 (39.9)
0.11 (27.4)
0.05 (12.5)
0.62 (154.4)
0.59 (147.0)
0.56 (139.5)
0.52 (129.5)
0.49 (122.1)
0.47 (117.1)
0.45 (112.1)
0.41 (102.1)
0.61 (152.0)
0.58 (144.5)
0.55 (137.0)
0.52 (129.5)
0.48 (119.6)
0.44 (109.6)
0.40
0.35
0.30
0.25
0.20
0.14
0.08
0.02
(99.6)
(87.2)
(74.7)
(62.3)
(49.8)
(34.9)
(19.9)
(5.0)
0.40
0.35
0.28
0.20
0.13
0.07
0.01
(99.6)
(87.2)
(69.7)
(49.8)
(32.4)
(17.4)
(2.5)
0.36
0.30
0.24
0.17
0.10
0.02
(89.7)
(74.7)
(59.8)
(42.3)
(24.9)
(5.0)
NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle
Subtract 0.06" W.G. for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G for horizontal left.
TWE5-PRC000-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Pressure Drop (Inches) - Electric Heaters
PRESSURE DROP FOR ELECTRIC HEATERS
IN AIR HANDLER MODELS
NUMBER OF RACKS
1
2
3
4
5
AIRFLOW AIRFLOW
AIR PRESSURE DROP
CFM
600
CMH
IN. W.G. (PASCALS)
1018.8
1188.6
1358.4
1528.2
1698.0
1867.8
2037.6
2207.4
2377.2
2547.0
2716.8
2886.6
3056.4
3226.2
3396.0
0.01
0.01
0.02
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
(2.5)
(2.5)
0.02
0.02
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.15
0.17
(5.0)
(5.0)
0.02
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.10
0.11
0.12
0.14
0.16
0.18
0.20
(5.0)
(5.0)
700
800
(5.0)
(7.5)
(7.5)
0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)
900
(7.5)
(7.5)
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(24.9)
(27.4)
(29.9)
(34.9)
(39.9)
(44.8)
(49.8)
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
(10.0)
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(24.9)
(27.4)
(32.4)
(34.9)
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(24.9)
(27.4)
(32.4)
(37.4)
(42.3)
0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23
0.26
(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)
(64.8)
NOTES:
1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
2. Heater model numbers may have additional suffix digits.
HEATER RACKS
HEATER
NO. OF
MODEL NO.
BAY96X1405
BAY96X1406
BAY96X1408
BAY96X1410
BAY96X1411
BAY96X1415
BAY96X1419
BAY96X1421
BAY96X1426
BAY96X3411
BAY96X3415
RACKS
1
2
2
2
3
3
4
4
5
3
3
22
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Supplementary
Heaters
THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.
TWE030C-HEATER MODEL NUMBER BAY96X
Unit
1405
1406
1408,F
1410,F 1410A
1411
1411A
1415
1419
1421
3411
3415
Position
Vertical
Upflow
Vertical
Application
A/C or Elec. Furnace
Heat Pump
A/C or Elec. Furnace
4.0 KW 4.8 KW
6.4 KW
8.0 KW 8.8 KW 8.8 KW
8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
M
L
H
L
M
L
H
L
M
L
H
L
M
L
H
L
L
L
L
L
L
L
L
L
L
L
H
L
L
L
L
Downflow Heat Pump
Horizontal A/C or Elec. Furnace
Left
Horizontal A/C or Elec. Furnace
Right Heat Pump
Heat Pump
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 and 1426 not approved for this model.
TWE040C-HEATER MODEL NUMBER BAY96X
Unit
1405
1406
1408,F
1410,F 1410A
1411
1411A
1415
1419
1421
3411
3415
Position
Vertical
Upflow
Vertical
Application
A/C or Elec. Furnace
Heat Pump
4.0 KW 4.8 KW
6.4 KW
8.0 KW 8.8 KW 8.8 KW
8.8 KW 12.8 KW 16.0 KW 17.6 KW 8.8 KW 12.8 KW
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
M
L
L
L
L
L
L
L
M
L
L
H
L
L
H
L
L
H
L
L
M
L
L
M
L
A/C or Elec. Furnace
Downflow Heat Pump
Horizontal A/C or Elec. Furnace
Left
Horizontal A/C or Elec. Furnace
Right Heat Pump
L
L
H
L
H
L
H
L
L
L
L
L
Heat Pump
L
L
H
L
H
L
H
L
L
L
L
L
L
H
H
H
L
L
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 1414 not approved for this model.
TWE050C-HEATER MODEL NUMBER BAY96X
Unit
1405
1406
1408,F
1410,F
1410A
1415
1419
1421
1426
3415
Position
Vertical
Upflow
Vertical
Application
A/C or Elec. Furnace
Heat Pump
4.0 KW
—
L
—
L
—
L
4.8 KW
—
L
—
L
—
L
6.4 KW
8.0 KW
8.8 KW
12.8 KW
16.0 KW
17.6 KW 21.6 KW 12.8 KW
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
L
M
L
H
L
H
L
M
L
M
L
L
H
L
L
L
L
L
L
L
L
L
A/C or Elec. Furnace
Downflow Heat Pump
Horizontal A/C or Elec. Furnace
Left
Horizontal A/C or Elec. Furnace
Right Heat Pump
H
L
H
L
Heat Pump
H
L
M
H
L
H
—
L
—
L
(L) Low, (M) Medium, (H) High indicate minimum heating speed setting for blower/motor operation. 14141,A & 1414 not approved for this model.
TWE5-PRC000-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
System
Wiring
Diagram
24
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
TWE030-050C Outline Drawing
All dimensions are in inches (mm)
FLOW
MINIMUM UNIT CLEARANCE SALE
MODEL NO.
TWE030CA4
A
43.00
B
15.57
C
21.50
D
19.50
E
20.28
F
CONTROL
TO COMBUSTIBLE
MATERIAL (REQUIRED)
SERVICE CLEARANCE
(RECOMMENDED)
21.63
FCCV
FCCV
TXV
(1092.2) (395.5) (761.1) (495.3) (515.1) (549.4)
51.75 24.32 23.50 21.50 22.28 23.63
(1134.5) (617.7) (596.9) (761.1) (565.9) (600.2)
57.90 30.47 23.50 21.50 22.28 23.63
(1470.7) (773.9) (596.9) (761.1) (565.9) (600.2)
SIDES
FRONT
BACK
0
0
0
0
1
(0)
2
21
0
(50.8)
(533.4)
(0)
TWE040CA4
TWE050CA5
(0)
(0)
(0)
(25.4)
INLET DUCT
OUTLET DUCT
1
(25.4)
TWE5-PRC000-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
1 INCH = (25.40 MILLIMETERS)
TTB524-536CA Outline Drawing
All dimensions are in inches (mm)
CABINET
SIZE
PT. NO.
A
B
C
D
E
1
3
TTB524CA
25A
251/2
11/16
/2
/4
5/16
(8)
5/16
(8)
(648) 14 UNS-2A 20UNF-2A
(19
1
3
TTB530CA/
TTB536CA
25C
321/2
11/16
/2
/
4
(826) 14 UNS-2A 20UNF-2A
(19)
FLARE NUT TORQUE
TORQUE FT-LBS (NEWTON METERS)
APPLIED TUBE SIZE
MINIMUM
8 (11.0)
MAXIMUM
10 (14.0)
15 (20.0)
25 (34.0)
35 (47.0)
55 (75.0)
60 (81.0)
1
/4
(6.35)
5/16 (7.94)
10 (14.0)
15 (20.0)
25 (34.0)
40 (54.0)
50 (68.0)
3
/
8
(9.52)
1
/
2
(12.70)
(15.88)
(19.05)
5
3
/
8
/
4
BACK-UP
HEX SIZE
1 1/16-14 = 1 1/16
(27)
1
/
2-20 = 1/2
(13)
SERVICE PANEL
ELECTRICAL AND REFRIGERANT
COMPONENTS CLEARANCES
PER PREVAILING CODES
TOP DISCHARGE AREA SHOULD BE
UNRESTRICTED FOR AT LEAST 1524
(5 FEET) ABOVE UNIT. UNIT SHOULD BE
PLACED SO ROOF RUN-OFF WATER
DOES NOT POUR DIRECTLY ON UNIT
AND SHOULD BE AT LEAST 305 (12”)
FROM WALL AND ALL SURROUNDING
SHRUBBERY ON TWO SIDES. OTHER
TWO SIDES UNRESTRICTED.
“C”SAE MALE FLARE FOR “E” O.D. TUBE SIZE
CONNECTION WITH 1/4” SAE FLARE
PRESSURE TAP FITTING.
“B”SAE MALE FLARE FOR “D” O.D. TUBE SIZE
CONNECTION WITH 1/4” SAE FLARE
PRESSURE TAP FITTING.
26
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
TTA030-060C Outline Drawing
All dimensions are in inches (mm)
TOP DISCHARGE AREA SHOULD BE
UNRESTRICTED FOR AT LEAST FIVE (5)
FEET ABOVE UNIT. UNIT SHOULD BE
PLACED SO ROOF RUN-OFF WATER
DOES NOT POUR DIRECTLY ON UNIT,
AND SHOULD BE AT LEAST 12” (305)
FROM WALL AND ALL SURROUNDING
SHRUBBERY ON TWO SIDES. OTHER
TWO SIDES UNRESTRICTED.
FIG. 1
MODEL
TTA030C
Figure
1
A
B
C
D
/8
E
/8
7
3
24 3/8
28 1/4
24 5/8
(619.1) (714.4)
32 3/4 28 1/4
(831.9) (714.4)
40 5/8 32 7/8
(1031.9) (835.0)
44 3/4 38 7/8
(1136.7) (987.4)
(625.5) (22.2) (9.53)
3
TTA040C
TTA050C
TTA060C
1
2
2
24 5/8
1 1/8
/
8
(625.5) (28.6) (9.53)
3
28 3/4
1 1/8
/
8
(730.3) (28.6) (9.53)
34 3/4
1 1/8
/
8
3
FIG. 2
(882.7) (28.6) (9.53)
TWE5-PRC000-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensional
Data
TWE030 Through 050 Convertibility
Six (6) Way Convertibility
OneUnit-4Applications
EasyConversiontoOppositeSideAccess
28
TWE5-PRC000-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
General
Coil
Blower coil units shall be completely
factory assembled including coil,
condensate drain pan, fan, motor, filters
and controls in an insulated casing that
can be applied in horizontal or vertical
configuration.
Aluminum fin surface shall be
mechanically bonded to 3/8-inch OD
copper tubing. Coils shall be factory
pressure and leak tested.
Fan
Forward curved, dynamically and
statically balanced with three-speed
direct drive shall be standard, fan motor
bearing shall be permanently lubricated.
This new line of TWE-C air handlers
provides exclusive compact size
combined with simple four-way
convertibility in three sizes. The unit
ships in the right hand horizontal
configuration and converts to vertical
upflow just by standing the unit on end.
No tools required. Simple coil rotation
provides downflow and horizontal left
applications.
Controls
Fan contactor, and plug-in module for
accessory electric heat control shall be
included. TWE models shall also include
check valves.
Filters
Filters shall be included as standard.
The four-way convertibility provides you
inventory benefits and service/
Accessories
installation flexibility. The simple
conversion provides opposite side
access for installation and service.
Electric Heaters — Shall be available in a
wide range of capacities and voltages
with various staging options and plug in
control wiring. Heaters shall fit inside
internal compartment.
Casing
Units shall have rugged sheet metal and
steel frame construction and shall be
painted with an enamel finish. Casing
shall be insulated and knockouts shall be
provided for electrical power and control
wiring.
Refrigerant Circuits
The TWE units shall have a single
refrigerant circuit. TWE03-040C
refrigerant circuit shall be controlled by a
flow control check valve (FCCV). The
TWE050C refrigerant circuit shall be
controlled by a factory-installed thermal
expansion valve.
TWE5-PRC000-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
File No.
TWE5-PRC000-EN 4/99
TWE5-PRC000-EN 2/98
Supersedes
TheTraneCompany
InternationalUnitaryProductsGroup
3600PammelCreekRoad
La Crosse, WI 54601-7599
Stocking Location La Crosse
SinceTheTraneCompanyhasapolicyofcontinuousproductimprovement, itreservestherighttochangedesign
andspecificationwithoutnotice.
AnAmericanStandardCompany