Installation
Operation
Maintenance
Voyager™ II Rooftop units
Cooling onlyTKD/TKH 155 175 200 250
Reversible WKD/WKH 125 155 200
Gas-FiredYKD/YKH 155 175 200 250
R22 - R407C Refrigerant
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
General information
Warranty
Refrigerant
Storage
Warranty is based on the general
terms and conditions of the
manufacturer.The warranty is void if
the equipment is repaired or
The refrigerant provided by the
manufacturer meets all the
Take precautions to prevent
condensate formation inside the
unit's electrical components and
motors when:
1. The unit is stored before it is
installed; or,
2. The unit is set on the roof curb
and temporary auxiliary heat is
provided in the building.
requirements of our units. When
using recycled or reprocessed
refrigerant, it is advisable to ensure
its quality is equivalent to that of a
new refrigerant. For this, it is
necessary to have a precise analysis
made by a specialized laboratory. If
this condition is not respected, the
manufacturer warranty could be
cancelled.
modified without the written
approval of the manufacturer, if the
operating limits are exceeded or if
the control system or the electrical
wiring is modified. Damage due to
misuse, lack of maintenance or
failure to comply with the
manufacturer's instructions or
recommendations is not covered by
the warranty obligation. If the user
does not conform to the rules of
this manual, it may entail
Isolate all side panel service
entrances and base pan openings
(e.g., conduit holes, S/A and R/A
openings, and flue openings) to
minimize ambient air from entering
the unit until it is ready for start-up.
Maintenance contract
It is strongly recommended that you
sign a maintenance contract with
your local Service Agency.This
contract provides regular
maintenance of your installation by
a specialist in our equipment.
Regular maintenance ensures that
any malfunction is detected and
corrected in good time and
minimizes the possibility that
serious damage will occur. Finally,
regular maintenance ensures the
maximum operating life of your
equipment. We would remind you
that failure to respect these
installation and maintenance
instructions may result in
cancellation of warranty and
liabilities by the manufacturer.
Do not use the unit's heater as
temporary heat without completing
the start-up procedures detailed
under "Unit Start-Up".
TheTrane Company will not assume
responsibility for equipment
damage resulting from
accumulation of condensate on the
unit electrical components.
Training
To assist you in obtaining the best
use of it and maintaining it in
perfect operating condition over a
long period of time, the
manufacturer has at your disposal a
refrigeration and air conditioning
service school.The principal aim of
this is to give operators and
immediate cancellation of the
warranty.
technicians a better knowledge of
the equipment they are using, or
that is under their charge. Emphasis
is particularly given to the
importance of periodic checks on
the unit operating parameters as
well as on preventive maintenance,
which reduces the cost of owning
the unit by avoiding serious and
costly breakdown.
RT-SVX19A-E4
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Foreword
2
2
2
2
3
3
3
3
3
Warnings and Cautions
Safety recommendations
Reception
Warranty
Refrigerant
Maintenance contract
Storage
Training
Installation
6
Reception of units
6
Roof curb installation
7
Dimensions/Weights/Clearances
Installing the unit
8
10
12
13
14
15
17
20
26
Condensate drain piping
Gas pipework installation
Filter installation
Supply fan adjustment
Component air pressure drops
Supply fan performances
Electrical connection
Controls
31
Control wiring
31
33
36
37
38
38
38
38
38
39
CO sensors
2
Remote potentiometer
Fire thermostat
Clogged filter detector
Smoke detector
High temperature safety thermostat
Remote fault relay
Thermostats
Communication Interfaces
4
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Unit Options
40
Hot water coil
40
41
41
42
43
Electric Heater
Soft Starter
0 - 25% fresh air hood
Barometric relief
Operation
44
Operation with a conventional thermostat
Setting the economizer
Test procedures
44
47
49
50
51
54
55
55
56
56
56
57
Test modes
Unit start-up
Cooling without an Economizer
Low Ambient Operation
Cooling with an Economizer
Economizer Set-Up
ReliaTel™ Control Heating Operation
Ignition Module
Final installation checklist
Maintenance
58
End user routine maintenance
Service technician maintenance
Troubleshooting
58
59
60
RT-SVX19A-E4
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
General information :The
installation must conform to all
local standards and regulations.
There are two ways to handle the
unit:
1. Use the openings in the wooden
frame to handle the machine
using a fork lift, in accordance
with applicable safety
Reception of units
Rooftop unit
regulations.
The unit is supplied on a wooden
frame. It is recommended to check
the machine's condition upon
reception.
2. Use a lifting beam correctly
adjusted to fit the unit
(Figure 1a).
Unit handling
The units are supplied on the truck
but are not unloaded. An opening is
provided on each corner of the unit
base to facilitate handling.
4 shackles and 4 slings are required.
Use a lifting beam to prevent the
cables pressing too hard on top of
the unit during lifting.
Figure 1a indicates the position of
the center of gravity and the lifting
recommendations.
Important: For unit to fit on the
roof curb the fork lift pockets must
be removed.
Figure 1a - Unit handling
B
A
1 = Clevis
2 = Base Rail
3 = Spreader Bar
L = Length (Center of Gravity)
W = Width (Center of Gravity)
Refer toTable 2 for weights and center of gravity.
6
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 1 - Sling lengths and maximum unit weight
Roof curb Installation
(TKD-WKD-YKD
accessories)
Maximm weight
Unit size
A (mm)
B (mm)
kg
125
155
175
400
500
3000
3000
3000
3500
3500
1900
1900
1900
2200
2200
644
773
Roof curbs are available as an
accessory for "downflow" units to
support the unit and ensure the
water tightness between the rooftop
and the roof.Two types of roof
curbs are available:The standard
version to allow the installation of
the unit on a flat roof and the
adjustable version for a sloped roof
installation. (See Figure 1b for the
maximum slope correction of
adjustable roofcurb.)
810
1001
1027
Figure 1b - Maximum slope correction of adjustable roof curb.
The adjustable roof curbs are
supplied pre-assembled on a skid.
Two types of self-adhesive seals are
provided separately. (40 mm wide
for the perimeter, 20 mm wide for
the cross pieces). Make sure they
are properly installed where
indicated to assure an adequate
curb to unit seal.
Instructions for the roof curb
assembly and installation with curb
dimensions are provided with each
roof curb kit.
Figure 2 - Waterproofing
4
3
1
2
1 = Roofcurb
2 = Roof membrane
3 = Seal
4 = Rooftop
RT-SVX19A-E4
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Dimensions/Weights/Clearances
Figure 3 - Minimum clearances
Table 2 - Minimum clearances (mm)
Minimum clearance
UNIT
1
2
3
4
5
YKD/YKH 155
YKD/YKH 175
YKD/YKH 200
YKD/YKH 250
TKD/TKH 155
TKD/TKH 175
TKD/TKH 200
TKD/TKH 250
WKD/WKH 125
WKD/WKH 155
WKD/WKH 200
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1900
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1800
1220
1220
1220
1220
1220
1220
1220
1220
1220
1220
1220
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1000
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
1300
The structure accommodating the unit(s) must be designed to support the
equipment in operation, as a minimum. Refer toTable 3a and the space
requirement plan.
8
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 3a - Weigths & center of gravity (Figure 1)
Maximum weight
Corner Weight (1)
Center of Gravity
Shipping
Net
(kg)
698
735
920
946
623
660
841
866
625
642
871
A
B
C
D
Length (L)
Width (W)
(mm)
737
UNIT
(kg)
866
(kg)
243
251
324
327
219
227
297
300
218
228
291
(kg)
176
188
242
251
159
172
221
230
159
162
226
(kg)
118
127
151
159
103
112
138
145
105
105
155
(kg)
162
169
203
208
142
149
185
206
144
147
199
(mm)
1143
1168
1321
1346
1143
1168
1321
1346
1143
1143
1346
YKD/YKH 155
YKD/YKH 175
YKD/YKH 200
YKD/YKH 250
TKD/TKH 155
TKD/TKH 175
TKD/TKH 200
TKD/TKH 250
WKD/WKH 125
WKD/WKH 155
WKD/WKH 200
902
737
1128
1154
790
838
838
711
827
711
1050
1075
792
838
838
711
809
711
1080
889
1. Corner weights are given for information only. All models must be supported continuously by a curb or equivalent frame support.
Table 3b - Weights of Options & accessories
Motorized
Outside Air
Damper
Standard Roof Adjustable Roof
Manual Outside
Air Damper
UNIT
Curb
Curb
220
220
260
260
Economizer
30
Electric heater Hot water coil
YKD 155
YKD 175
YKD 200
YKD 250
YKH 155
YKH 175
YKH 200
YKH 250
TKD 155
TKD 175
TKD 200
TKD 250
TKH 155
TKH 175
TKH 200
TKH 250
WKD 125
WKD 155
WKD 200
WKH 125
WKH 155
WKH 200
93
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
27
27
34
34
27
27
34
34
27
27
34
34
27
27
34
34
27
27
34
27
27
34
93
30
107
107
37
37
30
30
37
37
93
93
220
220
260
260
30
14
14
18
18
14
14
18
18
18
18
18
18
18
18
85
85
30
107
107
37
110
110
37
30
30
37
37
93
93
180
220
260
20
85
85
30
107
37
110
20
30
37
Notes :
Net weight should be added to unit weight when ordering factory installed accessories.
To estimate shipping weight add 2.3 kg to net weight.
RT-SVX19A-E4
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installing the unit
1) Unit mounting on roof
Fix the rooftop curb on the joint
beam of the building's structure.
Make the rooftop curb's sealing
surface level using angle brackets
adjusted by screw bolts, located
around its perimeter. Place the
adhesive seals on the curb's sealing
surface (perimeter and cross
Figure 4
pieces). Make the rooftop leak-tight
around the curbs before installing
the unit, in compliance with current
construction standards.
Note:The unit must be installed
perfectly level to ensure
condensates flow from the
condensate tray.
The rooftop unit nests into the curb
and is supported by it. Position the
unit, taking care to comply with the
indicated directions: the unit's
discharge and intake openings must
match those of the curb.
1 = Frame
2) Installing the unit on the ground
Figure 5
To install the unit on the ground, its
base must be level and supported
securely.
For horizontal discharge units, a
support is required such as a metal
or concrete slab whose height must
be determined according to the
amount of snow cover, to prevent
problems with condensation
drainage and obstruction of the
external coil. If necessary use an
anti-vibration material between the
rooftop unit's base and the support.
Note: Unit installation must comply
to local codes
1 = Concrete slab
10 RT-SVX19A-E4
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
. Installation of a section of
flexible ducts to limit
transmission of the unit's
vibrations
. Use of movable vanes or
deflectors to reduce the sound
level.
Connection of duct
network
1) Downflow discharge units
(TKD,WKD,YKD)
Using the rooftop curb
•
The rooftop curb must be
insulated on the outside walls at
the discharge and intake
openings to prevent
2) Horizontal discharge units
(TKH,WKH,YKH)
•
The intake and discharge ducts
must be insulated (thermal
insulation).
The duct section located outside
must be leak-tight.
Provide a flexible connector to
prevent transmission of the unit
vibrations.This flexible duct
must be installed inside the
building.
condensation in the ducts.
•
The rims around the discharge
and intake openings make it
possible to attach the flanges on
the ends of the ducts. If you are
using rigid duct ends
•
•
recommended on the rooftop
curb plan, it is essential to fix
these components before
installing the unit.
•
For the design of the duct
network, comply with
recommendations currently
applicable on the market, in
particular:
Note: In case of use ofTKH, WKH or
YKH units with economizer option,
temperature and humidity sensors
must be installed in return duct.
Economizer linkage is factory
mounted but the damper position
must be adjusted on site.
Figure 6 - Condensate Drain location
1 = Condensate drain connection
A =TKH/YKH 155, 175, 200, 250 - WKH 125,155, 200
B =TKD/YKD 155, 175, 200, 250 - WKD 125,155,200
RT-SVX19A-E4
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Condensate drain piping
A 42mm PVC condensate drain
connection with P-trap is provided.
Follow local codes and standard
piping practices when running the
drain line. Install a trap and be sure
to fill with water before starting the
unit. Pitch the line downward, away
from the unit to avoid long, level,
horizontal runs. Refer to Figure 7.
Figure 7 - Condensate drain line connection
1 = Static pressure drain pan
2 = Panel enclosure
3 = 42mm PVC drain
4 = Cleanout plug
12
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
CAUTION! Should the pressure at
the unit valve gas inlet be higher
than 0.035 bar, an expansion valve
must be installed.
CAUTION!The gas pipework must
not exert any stress on the burner
gas connection.
Gas pipework installation
The installation must conform to all
standards and regulations.
Note: Expansion valve must be
The gas supply pipework and gas
stop valve to be installed near the
unit must be sized so as to assure
the gas pressure is sufficient at the
unit inlet when operating at full
load.
The pipework must be self-
supporting and the final connection
to the burner must be made by a
flexible pipe. Provide a dust
protection (filter) upstream the unit
connection.
adapted to the type of gas used:
•
•
•
G 20 : 20 mb
G 25 : 25 mb
G 31 : (Propane): 37 or 50 mb
Table 4 - Gas burner models
Unit
Burner size
G350A
YKD/H
YKD/H
YKD/H
YKD/H
155
175
200
250
G350A
G350A
G350A
SeeTable 38 for burner
performance.
Gas leak check procedure
1. Vent the gas line
2. Gas supply line pressure test:
close valve 4 and open valve 2
Figure 8 -Typical gas supply Pipework
3. Leak-check the gas pipe
Look for gas pipe leaks using
"Typol", "1000 bulles" or a similar
product. Do not use soapy water.
WARNING! Never use an open
flame to check for gas leaks.
Required gas pressure at the unit
inlet connection are given in
Table 37.
Note:To operate with propane gas,
the burner is fitted with a pressure
limiter (supplied byTrane)
1 = Evaporator section
2 = Gas burner section
3 = Condenser section
4 = Gas supply connection
5 = Gas supply line
6,8 = Gas stop valve (Field supplied)
7 = Expansion valve (Field supplied)
9 = Filter (Field supplied)
RT-SVX19A-E4
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
CAUTION! Do not operate unit
without filters in place.
Filter installation
To gain access to filters, remove the
supply fan access panel on
downflow units and the filter access
panel on the end for horizontal
units.
The maximum pressure drops
allowable on filters are:
EU2/G2: 120 Pa
EU4/G4: 150 Pa
Each unit ships with 40 or 50 mm
thick filters. Number and size of
filters is determined by size and
configuration of the unit.
Table 5 - Filter arrangement
EU2/G2
EU4/G4
Size
UNIT
Qty
Size
Qty
2
4
2
4
8
4
4
8
4
4
2
4
2
4
8
4
4
8
4
4
2
4
2
4
8
4
4
2
(508x508x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x508x50)
(508x635x50)
(508x635x50)
(508x508x50)
(508x635x50)
(498x498x40)
(500x625x50)
(498x498x40)
(500x625x50)
(500x625x50)
(498x498x40)
(500x625x50)
(500x625x50)
(498x498x40)
(500x625x50)
(498x498x40)
(500x625x50)
(498x498x40)
(500x625x50)
(500x625x50)
(498x498x40)
(500x625x50)
(500x625x50)
(498x498x40)
(500x625x50)
(498x498x40)
(500x625x50)
(498x498x40)
(500x625x50)
(500x625x50)
(498x498x40)
(500x625x50)
YKH/YKD 155
4
2
YKH/YKD 175
4
YKH 200
YKD 200
YKH 250
YKD 250
8
4
4
8
4
4
2
4
2
4
8
4
4
8
4
4
2
4
2
4
8
4
4
TKH/TKD 155
TKH/TKD 175
TKH 200
TKD 200
TKH 250
TKD 250
WKH/WKD 125
WKH/WKD 155
WKH 200
WKD 200
14
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
b. Add static pressure drop of the
accessories installed on the
unit. (Table 7,8 & 9)
c. Add the total accessory static
pressure drop (from step 1b) to
the design external static
pressure (from step 1a).The
sum of these two values is the
total system external static
pressure.
2. Using theTables 10 through 20 to
find the external static pressure
that most closely approximates
total system external static
pressure.Then locate the
Supply fan adjustment
Use the following procedure to
determine the proper adjustment of
the supply fan for a specific
application.
1. Determine total external static
pressure about system and
accessories.
appropriate airflow rate for your
unit.The value obtained
represents the brake horsepower
for the supply fan motor and the
fan RPM.
a. Obtain the design airflow rate
and the design external static
pressure drop through the
distribution system.
3. Adjust motor sheave according
toTable 6.
Table 6 - Motor sheave / Fan speed
Fan Speed (RPM)
Standard Drive
6 turns
Open
566
5 turns
4 turns
Open
637
3 turns
Open
672
2 turns
1 turns
Open
743
UNIT
YKD/YKH 155
YKD/YKH 175
YKD/YKH 200
YKD/YKH 250
TKD/TKH 155
TKD/TKH 175
TKD/TKH 200
TKD/TKH 250
WKD/WKH 125
WKD/WKH 155
WKD/WKH 200
Open
601
769
550
619
601
769
550
619
566
601
550
Open
708
906
659
712
708
906
659
712
667
708
659
Closed
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
724
815
860
951
696
743
513
586
623
588
650
681
566
637
672
743
724
815
860
951
696
743
513
586
623
588
650
681
533
600
633
700
743
566
637
672
513
586
623
696
Fan Speed (RPM)
Oversized Drive
6 turns
Open
672
5 turns
Open
714
4 turns
Open
756
3 turns
Open
798
2 turns
Open
840
1 turns
Open
882
UNIT
YKD/YKH 155
YKD/YKH 175
YKD/YKH 200
YKD/YKH 250
TKD/TKH 155
TKD/TKH 175
TKD/TKH 200
TKD/TKH 250
WKD/WKH 125
WKD/WKH 155
WKD/WKH 200
Closed
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
791
840
711
890
939
989
1038
835
680
742
773
804
690
722
714
754
786
818
850
672
756
798
840
882
791
840
711
890
939
989
1038
835
680
742
773
804
690
722
769
754
786
818
850
724
815
860
906
951
513
550
619
586
623
659
696
588
650
681
712
743
RT-SVX19A-E4
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 9 -Typical fan, motor, and sheave
assembly
To increase airflow
Loosen variable sheave set screw
and turn sheave clockwise.
To decrease airflow
Loosen variable sheave set screw
and turn sheave counter-clockwise.
To increase belt tension
Loosen the nut (next to the idler
sheave) that secures the sheave in
place. With a wrench, apply
pressure clockwise on the outside
nut (round headed one), until
tension desired is reached. While
holding pressure with the tension
nut, retighten the nut next to the
idler sheave.
A = Fan Housing
B =Terminal Block
C = Fan Sheave
D = Plastic Bushing
E = BeltTension Adjustment Bolt
F = Idler Pulley
Table 6b - Belt tensioning
Fan pulley
Type /
diam. (mm)
Fan pulley
Type /
diam. (mm)
Belt
deflexion
(mm)
Deflexion Deflexion Belt tensionBelt tension
TK* /YK* /
Motor kW
WK*
Belt type
/ lengh (mm)
effort
effort
mini
N
maxi
N
mini kg
maxi kg
125
155
175
200
250
125
155
175
200
250
1,5
1,5
3
BK90 / 222
BK85 / 210
BK130 / 324
BK160 / 400
BK190 / 476
BK130 / 324
BK140 / 349
BK140 / 349
BK190 / 476
BK190 / 476
1VP44 / 105
1VP44 / 105
1VP44 / 105
1VL40 / 95
BX68 / 1727
BX68 / 1727
BX75 / 1905
BX90 / 2286
BX96 / 2438
BX75 / 1905
BX77 / 1955
BX75 / 1905
BX96 / 2438
BX96 / 2438
5,89
6
2,4
2,4
2,4
2,4
2,4
2,4
2,4
2,4
2,4
2,4
2,9
2,9
2,9
2,9
2,9
2,9
2,9
2,9
2,9
2,9
400
400
400
400
400
400
400
400
400
400
500
500
500
500
500
500
500
500
500
500
6,05
6,96
6,91
5,85
6,17
5,45
6,87
6,32
3
4,6
3
1VP50 / 121
1VP44 / 105
1VP44 / 105
1VP56 / 136
1VP56 / 136
1VP56 / 136
3
4,6
4,6
4,6
16
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Component air pressure drops
Table 7 -YKD/YKH Pressure drop through accessories
Filter
Filter
Economizer Economizer
100%
outside air
100%
return air
Airflow
EU2/G2
EU4/G4
6800
7650
8500
9350
10200
7870
13
16
19
22
26
17
21
25
30
35
12
15
19
23
27
11
14
17
20
23
18
24
29
36
43
17
21
26
31
36
27
30
34
37
40
30
34
38
43
47
26
30
33
37
41
23
26
29
33
36
32
36
41
46
51
30
34
38
43
47
8
10
12
14
16
10
12
15
17
20
29
37
45
55
65
33
41
51
61
72
46
58
71
86
102
52
65
80
96
114
6
7
8
9
10
7
8
9
11
12
6
8
9
11
13
6
YKD/YKH 155
YKD/YKH 175
YKD 200
8860
9850
10840
11830
8970
10090
11210
12330
13450
8970
10090
11210
12330
13450
11280
12690
14100
15510
16920
11280
12690
14100
15510
16920
8
9
YKH 200
11
13
10
12
14
17
19
10
12
14
17
19
YKD 250
YKH 250
RT-SVX19A-E4
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 8 -TKD/TKH Pressure drop through accessories
Filter
Filter
Economizer
Economizer
Electric
heater
Hot water coil
Downflow only
100%
outside air
100%
return air
Airflow
EU2/G2
EU4/G4
6800
7650
13
16
19
22
26
17
21
25
30
35
12
15
19
23
27
11
14
17
20
23
18
24
29
36
43
17
21
26
31
36
27
30
34
37
40
30
34
38
43
47
26
30
33
37
41
23
26
29
33
36
32
36
41
46
51
30
34
38
43
47
8
10
12
14
16
10
12
15
17
20
29
37
45
55
65
33
41
51
61
72
46
58
71
86
102
52
65
80
96
114
6
7
7
33
40
48
56
65
42
51
61
72
83
33
40
48
56
65
-
9
TKD/TKH 155
TKD/TKH 175
TKD 200
8500
8
11
13
16
10
13
16
19
23
13
17
21
25
30
13
17
21
25
30
20
25
32
38
46
19
24
29
35
42
9350
9
10200
7870
10
7
8860
8
9850
9
10840
11830
8970
11
12
6
10090
11210
12330
13450
8970
8
9
11
13
6
10090
11210
12330
13450
11280
12690
14100
15510
16920
11280
12690
14100
15510
16920
8
-
TKH 200
9
-
11
13
10
12
14
17
19
10
12
14
17
19
-
-
49
59
71
82
95
-
TKD 250
-
TKH 250
-
-
-
18
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 9 - WKD/WKH Pressure drop through accessories
Economizer
Economizer
100%
Filter
EU2/G2
Filter
EU4/G4
100%
Electric
heater
Hot water coil
Downflow only
Airflow
5720
outside air
return air
9
21
24
27
30
33
27
30
34
37
40
26
30
33
37
41
23
26
29
33
36
6
5
6
4
37
45
53
62
72
33
40
48
56
65
33
40
48
56
65
-
6430
11
14
17
20
13
16
19
22
26
12
15
19
23
27
11
14
17
20
23
7
6
WKD/WKH 125
WKD/WKH 155
WKD 200
7140
9
6
7
7850
10
12
8
7
9
8560
8
12
7
6800
6
7650
10
12
14
16
29
37
45
55
65
33
41
51
61
72
7
9
8500
8
11
13
16
13
17
21
25
30
13
17
21
25
30
9350
9
10200
8970
10
6
10090
11210
12330
13450
8970
8
9
11
13
6
10090
11210
12330
13450
8
-
WKH 200
9
-
11
13
-
-
RT-SVX19A-E4
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Supply fan performances
Table 10 -YK 155 External static pressure
External Static Pressure (Pa)
125 150
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
564 587 1.07 610 1.15 633 1.23 655 1.31 677 1.39
25
50
75
100
175
200
225
250
3
m /h
6800
7650
8500
9350
10200
1
560 1.14 583 1.23 605 1.31 627 1.39 648 1.48 669 1.56 690 1.65 710 1.74
559 1.31 584 1.41 606 1.5 628 1.6 649 1.69 669 1.78 689 1.87 708 1.97 727 2.06 746 2.16
610 1.72 633 1.83 654 1.94 675 2.04 694 2.14 713 2.24 732 2.34 750 2.45 767 2.55 785 2.65
661 2.21 683 2.33 703 2.45 722 2.56
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
699 1.47 719 1.55 739 1.63 758 1.71 777 1.79 795 1.86 813 1.94 830 2.01 847 2.09 863 2.16
729 1.82 749 1.92 768 2.01 787 2.1 806 2.19 824 2.28 841 2.37 858 2.46 875 2.55
764 2.25 782 2.35 800 2.45 818 2.55
6800
7650
8500
9350
10200
Standard drive
Oversized drive
20
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 11 -YK 175 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
726 1.58 748 1.66 770 1.74 791 1.83 813 1.92 835 2.02
7870
8860
9850
10840
11830
751 1.96 772 2.05 792 2.13 811 2.22 831 2.31 850 2.4 869 2.5 888 2.6
779 2.41 801 2.52 822 2.62 841 2.72 859 2.82 877 2.91 895 3.01 912 3.11 929 3.21 947 3.31
852 3.19 874 3.31 893 3.42 911 3.53 928 3.64 945 3.75 961 3.85 977 3.96 993 4.07 1009 4.18
926 4.12 946 4.25
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
857 2.12 879 2.22 900 2.33 921 2.44 942 2.55 962 2.65 981 2.75 1000 2.86 1018 2.96 1036 3.06
907 2.7 927 2.81 946 2.92 965 3.03 985 3.15
7870
8860
9850
10840
11830
964 3.42 981 3.53 998 3.64 1016 3.76 1033 3.88
1024 4.29
Standard drive
Oversized drive
Table 12 -YK 200 External static pressure
External Static Pressure (Pa)
125 150
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
530 1.5 551 1.61 572 1.74 593 1.87 614
25
50
75
100
175
200
225
250
3
m /h
8970
2
10090
11210
12330
13450
529 1.71 548 1.83 567 1.94 586 2.06 604 2.18 623 2.31 641 2.45
530 1.99 551 2.12 570 2.24 588 2.36 606 2.48 623 2.61 640 2.74 657 2.87 673 3.01
548 2.41 573 2.58 594 2.73 613 2.87 630
3
646 3.13 662 3.27 678 3.4 693 3.54 709 3.69
593 3.1 617 3.29 638 3.46 656 3.61 672 3.76 688 3.9 703 4.05 718 4.19
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
633 2.14 652 2.27 670 2.4 688 2.54 705 2.67 721 2.8 737 2.93 753 3.06 768 3.19 783 3.31
660 2.6 679 2.75 697 2.91 714 3.06 731 3.21 747 3.35 763 3.5 778 3.65 793 3.8 808 3.95
690 3.16 707 3.31 724 3.47 741 3.64 757 3.81 773 3.98 789 4.14 804 4.31
724 3.84 739 3.99 754 4.15 770 4.31
8970
10090
11210
12330
13450
Standard drive
Oversized drive
RT-SVX19A-E4
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 13 -YK 250 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
606 1.62 625 1.72 643 1.82
9870
11280
12690
14100
15510
16920
603 1.88 620 1.97 637 2.07 653 2.17 670 2.27 686 2.37
602 2.18 622 2.30 640 2.41 657 2.52 673 2.63 688 2.74 704 2.85 719 2.96 733 3.08
639 2.77 660 2.92 679 3.06 696 3.19 712 3.32 727 3.44 742 3.56 756 3.68 770 3.80 784 3.92
699 3.65 719 3.82 736 3.98 753 4.13 768 4.27 782 4.40 796 4.54 810 4.67 823 4.81 836 4.94
758 4.70 777 4.89 794 5.06 810 5.23 824 5.39 838 5.54
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
662 1.92 681 2.03 699 2.15 717 2.26 735 2.36 752 2.48 768 2.59 784 2.69 800 2.81 815 2.91
702 2.48 718 2.59 734 2.70 750 2.82 767 2.94 783 3.08 800 3.20 815 3.33 831 3.46 846 3.59
748 3.19 762 3.30 776 3.42 791 3.54 805 3.66 819 3.79 834 3.92 848 4.05
797 4.05 810 4.17 823 4.30 836 4.43 849 4.55
9870
11280
12690
14100
15510
16920
848 5.08
Standard drive
Oversized drive
Table 14 -TK 155 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
565 0.7 599 0.77 633 0.85 665 0.93 697 1.02 728 1.1 758 1.19
6800
7650
8500
9350
10200
571 0.82 603 0.9 634 0.99 665 1.07 694 1.16 723 1.25 752 1.34 780 1.44
580 0.97 613 1.07 643 1.16 672 1.25 700 1.34 727 1.43 754 1.53 781 1.63 807 1.73
590 1.13 624 1.24 656 1.35 684 1.46 711 1.55 738 1.65 763 1.75 788 1.86 813 1.96 838 2.07
637 1.44 670 1.57 699 1.69 727 1.81 753 1.92 777 2.02 801 2.13 825 2.24 848 2.35 871 2.46
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
6800
7650
8500
9350
10200
787 1.28 815 1.37 842 1.46 868 1.54
808 1.53 836 1.63 862 1.74
833 1.83 858 1.93 883 2.04
862 2.18 885 2.29 909 2.4
894 2.58
Standard drive
Oversized drive
22
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 15 -TK 175 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
593 0.95 623 1.03 651 1.11 679 1.19 706 1.28 733 1.37 761 1.47 788 1.57 815 1.68
623 1.21 653 1.31 680 1.4 706 1.49 731 1.58 756 1.67 780 1.77 805 1.87 829 1.97 853 2.08
687 1.64 714 1.75 739 1.85 763 1.95 786 2.05 809 2.15 831 2.25 853 2.36 875 2.47 897 2.58
750 2.16 775 2.28 799 2.4 821 2.51 843 2.62 864 2.73 884 2.84 905 2.95 925 3.07 945 3.18
814 2.78 837 2.92 860 3.05 881 3.17 901 3.29 921 3.41 940 3.53 959 3.65 978 3.77 996 3.89
7870
8860
9850
10840
11830
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
842 1.79 869 1.91 896 2.03 921 2.15 946 2.27 970 2.39 994 2.51 1016 2.63 1038 2.75
877 2.19 901 2.31 925 2.43 949 2.56 973 2.69 997 2.83 1020 2.96 1043 3.1
919 2.7 941 2.82 962 2.94 984 3.07 1006 3.2 1027 3.33
7870
8860
9850
10840
11830
965 3.3 985 3.43 1005 3.55 1025 3.68 1044 3.82
1015 4.02 1033 4.15
Standard drive
Oversized drive
Table 16 -TK 200 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
512 0.98 542 1.09 571 1.21 600 1.33 629 1.45 656 1.58 684 1.72
8970
10090
11210
12330
13450
519 1.16 547 1.28 575 1.39 601 1.51 627 1.64 653 1.77 679 1.91 704 2.05
528 1.36 557 1.5 584 1.63 610 1.76 634 1.89 658 2.02 682 2.16 705 2.3 729 2.44
537 1.58 568 1.74 596 1.9 622 2.05 647 2.19 670 2.33 692 2.47 714 2.62 735 2.77 757 2.92
580 2.01 609 2.19 636 2.37 661 2.54 684 2.7 706 2.85 728 3.01 748 3.16 768 3.32 788 3.48
External Static Pressure (Pa)
275
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
710 1.86 735 759 2.14 783 2.27 805 2.41 827 2.55
300
325
350
375
400
425
450
475
500
3
m /h
8970
2
10090
11210
12330
13450
729 2.2 753 2.35 777 2.5 800 2.66 823 2.81
752 2.6 774 2.75 797 2.92 819 3.08 841 3.25
778 3.08 799 3.24 820 3.4 841 3.57
808 3.64 828 3.81
Standard drive
Oversized drive
RT-SVX19A-E4
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 17 -TK 250 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
585 1.31 609 1.42 632 1.51 654 1.6 675 1.69 695 1.78
9870
11280
12690
14100
15510
16920
606 1.63 633 1.77 657 1.9 679 2.02 700 2.13 720 2.24 739 2.35
599 1.8 628 1.97 655 2.15 681 2.31 704 2.47 726 2.62 747 2.76 766 2.89 785 3.02
631 2.2 654 2.38 679 2.57 705 2.76 729 2.96 752 3.14 774 3.32 795 3.49 814 3.65 832 3.8
690 2.9 711 3.08 733 3.28 756 3.5 779 3.71 801 3.93 822 4.13 842 4.33
749 3.73 768 3.92 788 4.14 809 4.36
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
714 1.86 733 1.94 751 2.02 769 2.1 786 2.17 802 2.25 818 2.32 834 2.39 849 2.46 864 2.53
757 2.45 775 2.55 793 2.65 810 2.74 827 2.84 843 2.93 859 3.02 874 3.11 889 3.19 904 3.28
803 3.14 820 3.26 837 3.38 853 3.49 869 3.61 885 3.72 901 3.83 916 3.93 931 4.04
850 3.95 866 4.09 883 4.23 898 4.37
9870
11280
12690
14100
15510
16920
Standard drive
Oversized drive
Table 18 - WK 125 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
562 0.55 601 0.63 639 0.71 675 0.8 709 0.89 741 0.98
8970
10090
11210
12330
13450
548 0.6 584 0.68 620 0.76 655 0.84 690 0.93 723 1.03 755 1.13
544 0.68 578 0.75 611 0.83 644 0.91 676
1
708 1.09 739 1.19 770 1.29
542 0.77 577 0.85 609 0.93 640 1.01 670 1.1 700 1.19 730 1.28 759 1.38 788 1.48
541 0.85 578 0.96 612 1.05 643 1.14 671 1.23 699 1.32 727 1.41 755 1.51 782 1.61 809 1.71
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
772 1.06 802 1.15 830 1.24 857 1.33 883 1.41 909 1.5 933 1.59 957 1.68
786 1.23 815 1.32 843 1.42 871 1.52 897 1.62 922 1.72 947 1.82
800 1.4 829 1.51 857 1.62 884 1.73 911 1.84 936 1.94 960 2.05
816 1.59 844 1.7 872 1.82 898 1.94 925 2.06 950 2.18
5720
6430
7140
7850
8560
835 1.82 862 1.94 888 2.05 913 2.18 939 2.3
Standard drive
Oversized drive
24
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 19 - WK 155 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
566 0.7 599 0.77 632 0.85 664 0.93 696 1.02 727 1.11 757 1.2
6800
7650
8500
9350
10200
571 0.82 604 0.9 634 0.99 664 1.07 694 1.16 723 1.25 751 1.34 779 1.44
578 0.95 612 1.05 644 1.15 673 1.25 700 1.34 727 1.43 754 1.53 780 1.63 806 1.73
586 1.09 622 1.22 655 1.33 685 1.44 712 1.55 739 1.65 764 1.75 788 1.86 813 1.96 837 2.07
633 1.39 667 1.53 698 1.66 726 1.78 753 1.9 778 2.02 803 2.13 826 2.24 848 2.35 871 2.47
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
6800
7650
8500
9350
10200
787 1.29 816 1.38 843 1.47
807 1.54 834 1.64 861 1.74
832 1.83 857 1.94 882 2.04
861 2.18 884 2.29
893 2.58
Standard drive
Oversized drive
Table 20 - WK 200 External static pressure
External Static Pressure (Pa)
125 150
25
50
75
100
175
200
225
250
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
521 1.01 550 1.12 579 1.24 608 1.36 636 1.49 664 1.62 691 1.76
8970
10090
11210
12330
13450
14570
15690
16810
529 1.2 557 1.32 584 1.44 610 1.56 636 1.68 662 1.82 687 1.95 712 2.1
540 1.42 569 1.56 595 1.69 621 1.82 645 1.95 669 2.08 692 2.22 715 2.36 738 2.51
552 1.66 582 1.82 610 1.98 635 2.13 659 2.27 681 2.41 704 2.55 725 2.7 747 2.85 768
3
597 2.11 625 2.3 651 2.47 675 2.64 698 2.8 720 2.95 741 3.11 761 3.26 781 3.42 801 3.58
638 2.59 666 2.8 692 3.01 716 3.2 740 3.39 762 3.58 783 3.75 803 3.92
677 3.1 707 3.37 735 3.61 761 3.85
715 3.66 748 3.98
External Static Pressure (Pa)
275
300
325
350
375
400
425
450
475
500
3
m /h
RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW) RPM (kW)
717 1.9 742 2.04 766 2.17 789 2.31 811 2.45 833 2.58
737 2.25 761 2.4 785 2.56 808 2.71 830 2.87
761 2.66 784 2.82 806 2.98 828 3.15
8970
10090
11210
12330
13450
14570
15690
16810
789 3.16 810 3.32 831 3.49
820 3.75 840 3.91
Standard drive
Oversized drive
RT-SVX19A-E4
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Over current protection
Electrical connection
The branch circuit feeding the unit
must be protected in accordance
with national or local codes and
max unit amps indicated inTable 21
to 28.
The electric panel is located in the
unit compressor section. Remove
the compressor access panel. The
unit is designed to run with 400 V
+/- 5%/50 Hz/ 3 ph.
Power wiring
Factory supplied Disconnect switch
(Option)
The unit power supply must be
provided by 4-wire cable with cross-
sectional areas complying with
legislation.
The disconnect switch is factory
mounted. It is located on the side of
the Electrical panel and equipped
with fuses as standard.
The power supply cables must be
laid in leak-tight pipes and pass
through the bottom of the electric
panel.The cables must not be taut.
Appropriate connectors must be
provided. Flexible pipe supports are
required to prevent noise
transmission in the building
structure. Ensure all the connections
are tightened.
Note:
Figure 10 - Power supply
1. earthing must be executed in
accordance with local legislation.
2. the machines are designed for a
short-circuit current of 10 kA. In
the event of a higher application,
contact yourTrane sales office.
TKD/TKH, WKD/WKH units:
YKD/YKH units:
1 = Power supply from the bottom or from the side.
26
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Scroll compressors
The direction of rotation may be
reversed by interchanging any two
of the line wires. It is this possible
interchange of wiring that makes a
phase sequence indicator necessary
if the operator is to quickly
Compressor electrical phasing
Proper phasing of the electrical
power wiring is critical for proper
operation and reliability of the scroll
compressor and fans.
determine the phase rotation of the
compressor motor.
Proper rotation of the scroll
compressor must be established
before the unit is started.This is
accomplished by confirming that
the electrical phase sequence of the
power supply is correct.The motor
is internally connected for clockwise
rotation with the inlet power supply
phased A, B, C.
The "ABC" indicator on the face of
the phase indicator will glow if
phase is ABC for terminals L1, L2,
L3.
CAUTION! After completion of
wiring, check all electrical
connections, and ensure all
connections are tight. Replace and
secure all electrical box covers and
access doors before leaving unit or
connecting power to circuit
supplying unit.
CAUTION! Units with Scroll
compressors are not equipped with
crankcase heaters.
Table 21 - Electrical data -YKD/YKH Unit Wiring
Electrical Characteristics Unit amps
Standard Evaporator
Fan Motor
Maximum
WARNING !
Disconnect all power,including
remote disconnects, and discharge
all capacitors before servicing.
Follow proper lockout/tagout
procedures to ensure the power
cannot be inadvertently energized.
After power is removed, allow
4 minutes for capacitors to
Oversized Evaporator
Fan Motor
Maximum
Overcurrent
Protective
Device (Fuse
or Circuit
Overcurrent
Protective
UNIT
MPS
Minimum
Circuit
Ampacity
Minimum
circuit
Device (Fuse
ampacity
or Circuit
Breaker)
Breaker)
discharge. Verify with an
Without Electric heat option
appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and/or
discharge capacitors before
servicing could result in death or
serious injury. For additional
information regarding the safe
discharge of capacitors, seeTrane
Service Bulletin PROD-SVB06A.
TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
WKD/H 125
WKD/H 155
WKD/H 200
YKD/H 155
YKD/H 175
YKD/H 200
YKD/H 250
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
35
50
50
63
63
40
50
63
50
50
63
63
36.9
41.9
44.5
-
50
50
63
-
41
44
46.4
31.9
35.1
50.4
35.6
42.3
44.6
46.4
33.8
37
40
50
63
50
50
63
-
50.9
37.5
43.2
45.1
-
With Electric heat
TKD/H 155
TKD/H 175
TKD/H 200
TKD/H 250
WKD/H 125
WKD/H 155
WKD/H 200
400/3/50
41
43
63
63
80
80
80
80
125
43
43
63
63
80
-
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
61
61
62
-
68
69.9
73.1
105
80
80
125
71.2
104.5
RT-SVX19A-E4
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 22 - Electrical data -TKD/TKH Compressor motor and condenser motor
YKD/H
YKD/H
175
YKD/H
200
YKD/H
250
155
Compressor
Number
2
2
2
2
Type
Scroll
Scroll
Scroll
Scroll
Model
9T / 5T
15.0 / 8.5
118 / 65.5
10T / 6.7T
15.1 / 11.4
118 / 101
9T / 9T
14.7 / 14.7
118 / 118
10T / 10T
15.3 / 15.3
118 / 118
Nominal Amps (1)
Locked rotor Amps (2)
(A)
(A)
Outdoor Fan
3
Nominal Airflow
Type
(m /h)
15350
Axial
660
Direct
2
19750
Axial
660
Direct
2
21000
Axial
710
23500
Axial
710
Diameter
(mm)
Drive type
Direct
2
Direct
2
Number / Voltage
Motor HP
(kW)
(A)
0.25
1.6
0.25
1.6
0.56
2.3
0.56
2.3
Motor Rated Amps (1)
Motor Locked rotor Amps (2)
Motor RPM
(A)
3.8
3.8
5.8
5.8
(rpm)
925
925
925
925
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
Table 23 - Electrical data -YKD/YKH Compressor motor and condenser motor
TKD/H
TKD/H
175
TKD/H
200
TKD/H
250
155
Compressor
Number
2
2
2
2
Type
Scroll
Scroll
Scroll
Scroll
Model
9T / 5T
15.0 / 8.5
118 / 65.5
10T / 6.7T
15.1 / 11.4
118 / 101
9T / 9T
14.7 / 14.7
118 / 118
10T / 10T
15.3 / 15.3
118 / 118
Rated Amps (1)
Locked rotor Amps (2)
(A)
(A)
Outdoor Fan
3
Nominal Airflow
Type
(m /h)
(mm)
15350
Axial
660
Direct
2
19750
Axial
660
Direct
2
21000
Axial
710
23500
Axial
710
Diameter
Drive type
Direct
2
Direct
2
Number
Motor HP
(kW)
(A)
0.25
1.6
0.25
1.6
0.56
2.3
0.56
2.3
Motor Rated Amps (1)
Motor Locked rotor Amps (2)
Motor RPM
(A)
3.8
3.8
5.8
5.8
(rpm)
925
925
925
925
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
28
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 24 - Electrical data - WKD/WKH Compressor motor and condenser motor
WKD/H
WKD/H
155
WKD/H
200
125
Compressor
Number
2
2
2
Type
Scroll
Scroll
Scroll
Model
6T / 6T
10.0 / 10.0
74 / 74
7.5T /7.5T
12.1 / 12.1
79 / 79
10T / 10T
17.5 / 17.5
98 / 98
Rated Amps (1)
Locked rotor Amps (2)
(A)
(A)
Outdoor Fan
3
Nominal Airflow
Type
(m /h)
15300
Axial
660
Direct
2
15850
Axial
660
Direct
2
23600
Axial
710
Diameter
(mm)
Drive type
Direct
2
Number
Motor HP
(kW)
(A)
0.25
1.6
0.25
1.6
0.56
2.3
Motor Rated Amps (1)
Motor Locked rotor Amps (2)
Motor RPM
(A)
3.8
3.8
5.8
(rpm)
925
925
950
(1) At Eurovent rating conditions : Indoor return Air (27°C DB / 19°C WB) - Ambiant 35°C
(2) per motor
Table 25 - Electrical data -TKD/TKH Supply fan motor
YKD/H
155
YKD/H
YKD/H
YKD/H
250
175
200
Indoor Fan
3
Nominal Airflow
(m /h)
8500
150
9850
75
11210
175
14100
75
Static pressure available (4)
Maximum static pressure available (5)
Type
(Pa)
(Pa)
350
375
450
375
FC Centrifugal
15" / 15"
Belt
FC Centrifugal
15" / 15"
Belt
FC Centrifugal
18" / 18"
Belt
FC Centrifugal
18" / 18"
Belt
Diameter / Width
(in / in)
Drive type
Number
#
1
1
1
1
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
(kW)
(A)
2.2 / 3.0
4.6 / 6.5
36.4 / 57
1450 / 2870
3.0 / 4.6
6.5 / 9.0
57 / 71.9
2870 / 2900
3.0 / 4.6
6.5 / 9.0
57 / 71.9
2870 / 2900
4.6 / -
9 / -
Motor Locked rotor Amps (Standard/Oversized) (A)
71.9 / -
2900 / -
Motor RPM (Standard/Oversized)
(rpm)
(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available
RT-SVX19A-E4
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 26 - Electrical data -YKD/YKH Supply fan motor
TKD/H
155
TKD/H
175
TKD/H
200
TKD/H
250
Indoor Fan
Nominal Airflow
3
(m /h)
8500
175
9850
250
11210
200
14100
125
Static pressure available (4)
Maximum static pressure available (5)
Type
(Pa)
(Pa)
325
400
375
350
FC Centrifugal
15" / 15"
Belt
FC Centrifugal
15" / 15"
Belt
FC Centrifugal
18" / 18"
Belt
FC Centrifugal
18" / 18"
Belt
Diameter / Width
(in / in)
Drive type
Number
#
1
1
1
1
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
(kW)
(A)
2.2 / 3.0
4.6 / 6.5
36.4 / 57
1450 / 2870
3.0 / 4.6
6.5 / 9.0
57 / 71.9
2870 / 2900
3.0 / 4.6
6.5 / 9.0
57 / 71.9
2870 / 2900
4.6 / -
9 / -
Motor Locked rotor Amps (Standard/Oversized) (A)
71.9 / -
2900 / -
Motor RPM (Standard/Oversized)
(rpm)
(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available
Table 27 - Electrical data - WKD/WKH Supply fan motor
WKD/H
WKD/H
155
WKD/H
200
125
Indoor Fan
3
Nominal Airflow
(m /h)
7140
200
8500
175
11210
200
Static pressure available (4)
Maximum static pressure available (5)
Type
(Pa)
(Pa)
425
325
350
FC Centrifugal
15" / 15"
Belt
FC Centrifugal
15" / 15"
Belt
FC Centrifugal
18" / 18"
Belt
Diameter / Width
(in / in)
Drive type
Number
#
1
1
1
Motor HP (Standard/Oversized)
Motor Rated Amps (Standard/Oversized)
Motor Locked rotor Amps (Standard/Oversized)
Motor RPM (Standard/Oversized)
(kW)
(A)
2.2 / 3.0
4.6 / 6.5
36.4 / 57
1450 / 2870
2.2 / 3.0
4.6 / 6.5
36.4 / 57
1450 / 2870
3.0 / 4.6
6.5 / 9.0
57 / 71.9
2870 / 2900
(A)
(rpm)
(4) At the nominal airflow with standard drive
(5) At the nominal airflow with oversized drive when available
Table 28 - Electrical data - Combustion Blower Motorr
YKD/H
YKD/H
175
YKD/H
200
YKD/H
250
155
Gas burner
Heating Models
G350
G350
G350
G350
Heating Input (G20)
Heating Output
(kW)
(kW)
(%)
77
77
77
77
69.3
69.3
69.3
69.3
Steady State Efficiency
No. Burners
90
90
90
90
1
2
1
2
1
2
1
2
No. Stages
Gas Connection Pipe Size
3/4" NPT
3/4" NPT
3/4" NPT
3/4" NPT
30
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
TraneTHS01,THS02,THP01 and
THP02Thermostats are directly
connected to RTRM board
(J7 connector).TRANETHS02 and
THP03 thermostats are directly
connected to RTRM board
(J6 connector).
Control wiring
The control circuit is 24 V AC. Unit
includes a 400/24 V transformer.
WARNING!The unit disconnect
switch must be opened and locked
open. Risk of injury and
electrocution.
Install the electrical link between the
thermostat (thermostat terminal
strip) and the unit (J6 or J7
CAUTION!The unit 24 V transformer
must not be used to power
connector) in compliance with the
interconnection diagram.The low
voltage wiring must not be laid in
the same pipes as the power cables.
accessories mounted on site, other
than those proposed byTrane.
Unit controlled by thermostat
Figure 11 -Thermostat wiring
The sizes and lengths of the
thermostat connection wires are
given inTable 29.The total
resistance of these control cables
must not exceed 5 ohms. If the
resistance exceeds this value the
thermostat may not operate with
the same precision.
RTRM
3J6
7
8
7
8
7
8
7
8
THP03
SR6
9
9
1
2
S2
S1
9
9
10
11
12
14
10
11
12
14
10
10
11
12
14
11
12
14
Table 29 - Zone sensor wire size and
maximum length
1
RTRM
3J6
SR6
1
2
1
2
1
2
1
2
1
2
3
3
3
4
5
3
4
5
Maximum length
4
5
4
5
THS03
1
6
7
6
7
Zone sensor wire size
6
7
6
7
8
8
8
8
Wire
size
(mm²)
Maximum
wire lengh
(m)
9
9
9
9
10
10
11
12
14
10
10
11
12
14
(WH)
11
12
14
(GN)
(RD)
(BK)
THA01
THS/THP 03
0.33
0.5
0.75
1.3
45
76
115
185
300
10
RTRM
2
3J7
0
0
Conventionnal
thermostat
THS/THP 01-02
0.33
0.5
0.75
1.3
W1
G
W1
G
15
THS02
4239070
23
Y1
Y2
R
37
THP02
4240530
Y1
Y2
R
2
60
24V
24V(C)
COM
RTRM
3J7
W1
W2
G
W1
W2
G
THS01
4239060
Y1
Y2
R
Y1
Y2
R
THP01
4240520
24V
COM
24V(C)
RT-SVX19A-E4
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Unit controlled by BAS
Unit controlled byTracker™
supervisor
Each unit must be equipped with a
TCI-R board. A communication bus
(twisted shielded pair) must link
eachTCI-R to theTrane RoofTop
Manager (RTM) or to the
The units must also be equipped
with theTCI-R communication
board. One remote sensor is
required on each unit for a constant
flow volume. In the case of a
variable flow installation
(VariTrac™) these sensors must not
be installed. A twisted shielded pair
must be used for the
communication link.The main
functions of theTracker™ supervisor
are control of setpoints, timetable
management (Programming) and
display of faults. For more details
refer to the supervisor
communication gateway (in the
case of an external BAS). Connect
one temperature sensor to each
®
unit. LonTalk communication
interface LTCl-R board allows ICS
communication between a
ReliaTel™ unit and LonTalk
®
communication applications.
documentation.
32
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
CO sensors
2
Wall-mounted and duct-mounted
CO sensors
2
Table 30 - Specifications
WaII-mounted
Duct-mounted
Measuring range CO
0-200 ppm
2
<+/- [30 ppm CO
+ 2%
of reading]
(included
repeatability and
caiibration
2
<+/- [40 ppm CO +
2
3%
of reading]
(included repeatability
and calibration
uncertainty)
Accuracy at 25°C
Non-linearity
uncertainty)
<1.0% full scale
Ternperature dependence
of output
0.3% full scale/°C
<5.0% fulI scale /
5 years
Long-term stability
Recomrnended
calibration interval
5 years
Response time
1 minute (0-63%)
15-35°C
Operating temperature
Storage temperature
- 5-45°C
-20-70°C
0-85% relative
humidity
Humidity range
Airflow range
0-10 m/s)
Output signals (jumper
selectable)
0-10Vdc
Resolution of anaIog
outputs
10 ppm CO2
Recomrnended external
load
Current output:
max 500
Voltage output:
min. 1000
Power supply
Nominal 24Vac
<5 VA
Power consumption
Warm-up time
<15 minutes
108 x 80 x 36
Dimensions (mm)
80 x 80 x 200
RT-SVX19A-E4
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Power supply requirements
Wiring the duct-mounted CO
sensor
1. Connect the DCV signal lwire to
the connector DCV of the ECA
2. Connect the power according to
the guidelines in Power supply
requirements.
2
CAUTION! Make sure that you
connect the power wire only to the
24V terminal. Connecting the power
wire to the output terminal may
result in equipment damage.
The CO sensor is designed to
2
To connect the wall mounted CO
sensor, Refer to the wiring diagram
provided in the unit.
operate with a nominal 24 Vac
supply.The power supply should
maintain the voltage between 20 to
26 Vac.
2
Mounting the wall-mounted sensor
1. Select a proper location in the
Table 31 - CO sensor wire size
2
room to mount the CO sensor.
2
Cross
Maximum wire
section
Iength
Look for an interior wall with
good air circulation,
approximately 1.4 m from the
floor.
(mm2)
(mn)
0.25
50
0.5
1
100
200
2. Remove the back plate from the
sensor and thread the power
wires and output signal wire
through the hole in the back
plate.
Wiring the wall-mounted CO
sensor
2
For surface wiring, make cut-
outs with pliers to the thinner
section of the upper or lower
edge of the back plate and to
thread the wires through.
DVC setpoint potentiometer on
economizer module can be adjusted
as follows:
0% - 500ppm, 50% - 1000 ppm,
100% - 1500ppm
3. Mount the back plate to the wall
with screws. Note that the arrow
on the back plate shows the
mounting direction.
The outside air damper will
modulate from minimum position
setting to up to 100% while
attempting to maintain the CO
2
setpoint.
To connect the wall mounted CO
2
sensor, Refer to the wiring diagram
provided in the unit.
Figure 12 - Jumper settings
OUTPUT
SELECTION
JUMPERS
34
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Mounting the duct-mounted CO
sensor
1. Select a proper location on the
CO sensor maintenance
2
2
This CO sensor has excellent
2
stability and requires no
duct to mount the CO sensor.
2
maintenance. In most environments
the recommended calibration
interval is five years. A trained
service technician can use a
2. Drill a 22-25 mm hole in the
mounting surface for sensor
insertion (Figure 13).
portable CO meter to certify sensor
3. Attach the mounting plate to the
duct wall with four screws.
4. Insert the sensor through the
mounting plate, adjusting the
depth for optimal air sensing.
2
calibration. If, when checking the
sensor, the reading differs too much
from the reference value, the sensor
can be recalibrated in the field. A
calibration kit, software, and
calibration gases are required. If
certified accuracy is required, the
sensor must be calibrated against
accurate and traceable calibration
gases in a laboratory. ConsultTrane
BAS for further details.
Figure 13 - Duct-mounted CO sensor
2
5
1 /8 in.( 42 mm)
7
/8 in.(2 2 mm)
5
1 /8 in.
(42 mm)
Figure 14 - Duct-mounted CO insertion depth
2
1
1
1
2 /2 in.(64 mm)
3 /8 - 5 /2 in. (80 - 140mm)
RT-SVX19A-E4
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Note:This potentiometer allows to
adjust the permanent fresh air
intake from 0 to 50%.
Remote potentiometer
To install the remote potentiometer,
cut the jumper WL on the
economizer ECA board, and connect
the wires to P and P1.
0 W corresponds to closed fresh air
damper.
270 W corresponds to 50% open
fresh air damper.
Note:This potentiometer allows to
adjust the permanent fresh air
intake from 0 to 50%.
0 W corresponds to closed fresh air
damper.
270 W corresponds to 50% open
fresh air damper.
Figure 15 - Remote potentiometer dimensions
Figure 16 - Remote potentiometer wiring
P
P
1 = Remote potentiometer
2 = ECA Board
WH = White wire
RD = Red Wire
BU = Blue wire
_____ Factory wiring
-------- Field wiring
36
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Note: Do not permit element guard
to touch internal parts. Do not
locate sensor where the air
Fire thermostat
There are two sensors in the fire
thermostat Kit: Sensor X13100040-
01 is factory-set to open at 57°C.
Sensor X13100040-02 is set to open
at 115°C.
circulation is restricted by baffles.
Connection of the fire thermostat
withTCI board : Refer to the wiring
diagram provided in the unit.
Sensors are mounted directly in the
ductwork.They should be installed
where elements can respond quickly
to air temperature changes. If not
possible, the sensor may be
installed on a suitable bracket so
the air is drawn across the element.
Sensor X13100040-01 has to be
mounted in the return air duct.
Sensor X13100040-02 has to be
mounted in the supply air duct.
Connection withoutTCI board
Connect according to the standard
wiring diagram provided on the
unit.
Remove sensor cover and fasten
control securely with screws. Loads
connected must not exceed 2 amps,
30V Ac.
Figure 17 - Duct mounting of fire thermostat
1 = Fire thermostat
2 = Hole in the duct
RT-SVX19A-E4
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Clogged filter detector
High temperature safety
thermostat
This additional safety device is a
manual reset thermostat for gas
fired units (YKD/YKH), required
mainly by the French ERP
regulation. It is located in the gas
burner section. It stops the gas
burner and the supply air fan when
the supply air temperature rises to
120°C.
Thermostats
6 thermostats are available:
This device is mounted in the filter
section.The sensor measures the
difference in pressure before and
after the filter section.The
information is sent to theTHP03
thermostat, to aTracker™ or to a
BMS.
THS01/THP01,THS02/THP02 and
THS03/THP03.
"THS" are non programmable
thermostats, "THP" are
programmable.
01 and 02 series are conventional
thermostat, 03 series are dedicated
to the controller.
Smoke detector
This device is used to detect smoke
in the air stream. It includes a
factory mounted detector connected
to a central panel, both fitted in the
fan section.
Remote fault relay
This is a factory mounted relay used
to send alarm signals (dry contact)
to a local BMS or a local control
panel. With this relay, the
compressor, heating, fan and power
supply alarm output signals from
the controller are reported to a
single dry contact.
When smoke is detected, it shuts off
the unit. A dry contact is available
on the control panel for a remote
default.
Table 32 -Thermostats features
THS01
THP01
THS02
THP02
THS03
THP03
non-programmable
programmable
X
-
X
-
X
-
-
X
-
X
-
X
electronic
X
X
X
X
X
X
unit control type design
interface card needed
for Cooling Only units
for Heat Pump units
for Gas Fired units
Cooling stages
electromech.
electromech.
electromech.
electromech.
Reliatel
Reliatel
CTI*
CTI*
CTI*
CTI*
none
none
X
-
X
-
-
X
-
-
X
-
X
X
X
2
X
X
X
2
X
2
X
2
2
2
auxiliary heating stages
(elec. heater, HWC )
2
2
1
1
2
2
heating stages
(heat pump mode)
none
none
1
1
1
1
liquid crystal display
X
X
X
X
-
X
*some important features are lost while using the CTI card.
Note: thermostats are powered up by the rooftop control (24V)
38
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Other accessories available
Communication Interfaces
TRANE Communication Interface
(TCI-R) board
Remote temperature sensor to be
used withTHS/THP 01-02
TZS01: Remote room temperature
sensor to be used withTHS/THP 03,
Tracker or Varitrac systems.
This is an electronic board, factory-
mounted in the main control panel,
needed to allow communication
between aTRANE Integrated
Comfort system (TRACKER or
Varitrac CCP2) and the unit. (COM3-
COM4)
DTS: Duct temperature sensor to be
used withTHS/THP 03
TZS02: Remote room temperature
sensor with adjustable thumwheel
setpoint to be used withTracker or
Varitrac systems
LON Communication Interface
(LCI-R) board
TZS04: Room temperature sensor
with adjustable thumbwheel and
override button, to be used with
Tracker or Varitrac systems
This is an electronic board, factory-
mounted in the main control panel,
needed to allow communication on
®
a LonTalk Network at the unit level.
Refer to separate documentation for
more information.
®
LonTalk . Communication Interface
(LCI-R) board
This interface board allows Voyager
®
units to communicate on a LonTalk
Network at the unit level. Network
variables are based on the
®
LonMark . Space Comfort Controller
Functional ProfileTemplate.The LCI-
V uses a FreeTopology transceiver
FTT-10A.The FTT-10A transceiver
supports non-polarity sensitive, free
topology wiring, allowing the
system installer to use star, bus,
and loop architecture.The LCI-V can
also be connected to an optional
HighTemperature Limit Switch if
installed with the rooftop unit. For
more information, see attached
manual LTCI-IN-1.
RT-SVX19A-E4
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
Hot water coil: Installation and
connection
Hot water coil
(Down flow units only)
In order to prevent water to freeze
up in the coil during unoccupied
period or shutdown limited period,
it is recommended to use ethylene
glycol.The services of a water
treatment specialist are
recommended if water used can
cause scaling deposits or erosion.
Insulate all the water piping likely to
be exposed to freezing
temperatures in order to avoid
freeze up of the coil and heat losses.
The water distribution network must
be fitted with vents in places where
air is likely to be trapped.
In order to prevent water to freeze
up in the coil during unoccupied
period or shutdown limited period,
a thermostat opens when there is a
risk of freeze-up.The services of a
water treatment specialist are
recommended if water used can
cause scaling deposits or erosion.
Insulate all the water piping likely to
be exposed to freezing
temperatures in order to avoid
freeze up of the coil and heat losses.
The water distribution network must
be fitted with vents in places where
air is likely to be trapped.
The hot water coil is factory
Table 33 - Ethylene glycol percentage
mounted in the discharge section.
Two holes are provided to connect
the hot water coil.They are located
at the base of the unit. Remove the
central panel to access the coil,
using an 8 mm wrench (the bolts
are located on the bottom part of
the panels).The tubes for entering
and leaving water are equipped
with a threaded female connector.
Ethylene glycol
Freezing point
percentage
(%)
10
(°C)
-4
20
-10
Water connection inlet/outlet: 1 ¼"
ISO R7.
Figure 18 - Hot water coil connections
40
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
Electric Heater
Soft Starter
Electric heaters are fitted on the fan
discharge.
The soft starter is used to achieve a
progressive supply fan start and a
reduced starting current as well as
the motor starting torque.This
option is well adapted for textile
duct applications. It is factory
Heaters have two heating stages
and provided with two types of
overheat thermostats:
•
Automatic reset thermostats
which stop the electric heater
when the air temperature rises to
76°C. Automatic reset at 60°C. No
alarm output available.
installed in the main control panel.
The soft starter gradually increases
the voltage of the supply fan motor
until it reaches full line voltage.
•
The manual reset thermostat
which stop the unit when the air
temperature rises to 120°C. No
alarm output available.
The starting time can be adjusted
from 0 to 64 seconds but the soft
starter is factory set to the
maximum starting time value,
64 seconds.
Figure 19 - Soft starter
1
Supply
Start / Line
Stop / Load
6
Urg.
Stop
Motor
Softstarter
5
4
Ctrl
Byp.
Diag.
INITAL
TORQUE
Time(s)
3
2
1 =Three phase mains connections
2 = Motor connections
3 = Settings
4 = Status outputs
5 = Controls
6 = LEDs
RT-SVX19A-E4
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
This option includes for the hood
itself, a wire mesh and a slidable
damper.
0 - 25% fresh air hood
The 0-25% fresh air hood allows to
introduce fresh air into the unit.
The slidable damper has to be
adjusted manually by removing the
screws and sliding it off up or down
(Figure 20).
This is a manual device fitted on the
back of the unit, sized for a
maximum of 25% of the nominal
rooftop air flow.
The amount of fresh air introduced
is then permanently fixed.
Figure 20 - 0-25% manual fresh air hood
1
3
2
1 = Intake hood
2 = Wire mesh
3 = Slidable damper
42
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
This option includes exhaust hoods
and gravity dampers located in the
return air section (Figure 22). When
the pressure of the building
increase, the gravity dampers open
and relieve air to the outside.
Barometric relief
The barometric relief allows to
minimize overpressure in the
building caused by the introduction
of fresh air.This option is typically
installed when fresh air intake is
below 25% of the nominal air flow
and when the return air pressure
drop is below 25Pa.
If the return air duct pressure drop
is higher than the building
overpressure, the gravity dampers
will not open.
If the return air duct pressure drop
is lower than the building
overpressure, the gravity dampers
will open and releive air outside of
the building.
Figure 21 - Economizer flow chart with barometric relief
S
R
S
E
R
F
F
Downflow version
Horizontal flow version
R = return
S = supply
F = fresh air
E = exhaust
RT-SVX19A-E4
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
•
•
•
•
Remote Sensing Capabilities are
not available on most
mechanical thermostats.
SpaceTemperature Averaging
capabilities are not available on
most mechanical thermostats.
27½ to 50 VAV – Conventional
thermostat input terminals are
inactive.
Built in Night Set Back and
Unoccupied Functions function
differently with a conventional
mechanical thermostat.
A built-in algorithm which allows
for automatic reset of the
Customers occasionally require
operation with a conventional
thermostat rather than a zone
sensor. In some cases there is a
preference for a specific thermostat
model, and in others there is
reluctance to adopt newer
technology that may not be as well
understood as conventional
thermostats. In addition, non-Trane
Building Controllers typically
provide an interface to HVAC
equipment based on a conventional
thermostat interface. Units applied
with this type of controller need to
accept conventional thermostat
inputs.
Operation with a
conventional thermostat
The ReliaTel module has
conventional thermostat
connections as well as Zone Sensor
Module connections. When a
conventional thermostat is
controlling the unit, operation
differs as follows.
•
Supply AirTempering feature is
not available. If outdoor air is
being introduced through the
equipment, discharge air
•
temperature may be cold when
not actively heating.
discharge air temperature while
economizing is not available.
•
•
Proportional Integral (PI) control
is not available.
Conventional thermostat signals
represent direct calls for unit
functions. In their simplest
applications, thermostat contacts
directly control contactors or other
load switching devices.This function
provides inputs for the thermostat
signals and processing to enhance
reliability and performance.
The terminal strip for attaching the
thermostat wires is located on the
RTRM module in the control
compartment.
Zone Sensor Diagnostics are
only available on the RTRM
module on the J6 terminals,
instead of at the Zone Sensor in
the space.
The purpose of each terminal is
discussed in the next section.
•
•
Intelligent Fall-Back is not
available. If a failure occurs in
the device controlling the
COM
T
Compressor protection and
equipment, operation will cease.
reliability enhancement functions
(HPC, LPC, Minimum On/Off timers,
etc.). All operate the same whether
applied with zone sensors or a
conventional thermostat.
Heat Pump Smart Recovery and
Smart Staging is not available.
Heat Pump operation becomes
more costly unless the generic
control being applied can
accomplish this.
X2
Y2
W2
G
Logic is also provided to cause
appropriate unit functions when
inappropriate thermostat signals are
provided. Simultaneous calls for
heating and cooling will be ignored,
and the fan will be turned on with a
call for heating or cooling even if
the fan request is not detected.
W1/0
Y1
R
If the thermostat is immediately
changed from a heating to a cooling
call, or vice versa, there will be a
five minute delay before the new
call will initiate.
44
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Thermostat signals are as follows:
Conventional thermostat –
Gas/ Electric, Electric Heat:
Conventional thermostat –
Heat Pump
R 24VAC power to thermostat
Function when
Input/connection energized
Y1 Call for compressor 1 or first
stage cooling
Function when
Input/connection energized :
Cooling mode:
G (fan)
G (fan)
Fan runs continuously
except during
unoccupied mode
(see next page)
Y2 Call for compressor 2 or 2nd
stage cooling
Fan runs continuously
except during
unoccupied mode
(see next page)
G Call for supply fan
W1 Call for heat 1
Y1 (compressor 1 Compressor #1 runs
or economizer)
or economizer
operates
O (reversing valve Reversing valve in
W2 Call for heat 2
during cooling)
cool mode
Heat pump only:
Y1 + O
Compressor #1 runs
Y2 (compressor 2 Compressor #2 also
or compressor 1 runs, or #1
while economizing)compressor runs
while economizing
(first stage cooling) or economizer
operates
Y1 +Y2 + O
X2 Call for emergency heat
O Switchover valve On = cooling,
Off = heating
Compressor #2 also
runs, or #1
(2nd stage cool)
W1 (gas / electric 1st stage heat
heat first stage)
compressor runs
while economizing.
T Bias for heat anticipation for those
mechanical thermostats that use
this function
W2 (gas / electric 2nd stage heat (if
Heating mode:
G (fan)
heat 2nd stage)
available)
Fan runs continuously
except during
unoccupied mode
(see below)
Y1 (both
Both compressors
compressors 1st run
stage heat)
Y2 (during heating No change
– nothing happens)
W2 (electric heat 2nd stage (electric)
2nd stage)
X2 (electric heat Electric heat only –
only) no compressors
heat
T (provides heat anticipation signal for
those mechanical thermostats that use this
feature. If the thermostat used does not
have a “T” terminal, disregard this
terminal.
RT-SVX19A-E4
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Unoccupied mode:
Cooling/Economizer Operation:
If the thermostat being used is
programmable, it will have its own
strategy for unoccupied mode and
will control the unit directly. If a
mechanical thermostat is being
used, a field applied time clock with
relay contacts connected to J6-11
and J6-12 can initiate an
If unit does not have an economizer,
the Cool/Econ Stage 1 and Stage 2
will call directly for mechanical
cooling (compressor) stages. If the
unit has an economizer, the
Cool/Econ stages will function as
follows.
unoccupied mode as follows:
•
•
Contacts open: Normal occupied
operation.
Contacts closed: Unoccupied
operation as follows - Fan in
auto mode regardless of fan
switch position. Economizer
closes except while economizing
regardless of minimum position
setting.
Table 34 - Cooling/Economizer Operation withThermostat1,2
OK to
Thermostat Thermostat Call for Economizer Compressor Staging
Economize?
Y1
Y2
Cooling
Request
No
No
On
Off
Inactive
Compressor Output 1
Off
On
On
On
Inactive
Inactive
Compressor Output 2
Compressor
Outputs 1 & 2
No
Yes
Yes
Yes
On
Off
On
Off
On
On
Active
Active
Active
Off
Compressor off
Compessor
46
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Table 35 - ECA board LED
Setting the economizer
or 0-50% motorized hood
(option)
OFF:
ON:
No Power or Failure
Normal, OK to Economize
Slow Flash: Normal, Not OK to
Economize
The ECA board is mounted on the
damper actuator.To access the ECA
board on economizers:
Fast Flash: Communications Failure
Pulse Flash: Error Code:
1 Flash:
Actuator Fault
•
Remove the access panel located
on the economizer section.
The electrical power must be
disconnected to set the
minimum position and check the
economizer.
Disconnect the power supply,
put the thermostat fan selector
to "ON" and the "HEAT/COOL"
selector to "OFF".This puts the
damper in the minimum
2 Flashes:
3 Flashes:
4 Flashes
5 Flashes:
6 Flashes:
7 Flashes:
8 Flashes:
9 Flashes:
C0 Sensor
2
•
RA Humidity Sensor
RATemp Sensor
OA Quality Sensor
OA Humidity Sensor
OATernp Sensor
MATemp Sensor
RAM Fault
•
•
10 Flashes: ROM Fault
ventilation position.
11 Flashes: EEPROM Fault
To set the required minimum
ventilation air position, turn the
dial on the ECA clockwise to
increase ventilation, or anti-
clockwise to decrease ventilation.
The damper will open at this
setting whenever the fan circuit
is powered up.
When the arrow on the dial
adjustment screw is pointing to 8
o'clock, the minimum position is
roughly 0%. When the dial is
pointing to 12 o'clock it is
roughly 25%, and when the dial
is pointing to 4 o'clock it is
roughly 50%
While setting the minimum position
the damper may move toward the
new setting in several small steps.
Once the damper has remained in
the same position for 10 to
15 seconds it can be assumed it is
in the new position.
•
To check the damper is functioning
correctly, the ECA is equipped with
an indicator light in the middle of
the board.This light operates as in
Table 35.
RT-SVX19A-E4
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Figure 22 - Minimum fresh air adjustment
+
2-10 VDC
POWER EXHAUST
1
2
+
-
POWER EXAHUST
EXF
MAT
FEEDBACK
CONTACTS
INPUT
1
MIXED AIR SENSOR
1
2
PPUUTT
2-10 VDC
+
-
INPUT COMMON
CONTROL
OUTPUT
COMMON
1
2
OAH/
OAE
OHS INPUT
N
C
O
O
T
N
U
N
S
E
E
C
D
T
-
E
O
D
A
TO
T
IS
1
2
OAT
RAT
MIN POS.
SETPOINT
T
RA INPUT
1
2
0-50%
COMMON
LED
GREEN
ABCD
SETTINGS
C
O
S
M
IN
M
P
ON
1
2
RAH/
RAE
RH
UT
T
CO2 “PURGE”
ADJUSTMENT
500-1500 PPM
SETPOINT
1
2
CO SENSOR INPUT
2
DCV
P1
COMMON
P
-
MODBUS
+
COMMON
24VAC
SHORTED=CLOSED
OPEN=ON CARD POT.
270 omega = 50%
REMOTE
MINIMUM
POTENTIOMETER
WHT
WHT
RED
RED
BLUE
BLUE
1 = ECA board
48
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
WARNING! If any operating checks
must be performed with the unit
operating, it is the technician's
responsibility to recognize any
possible hazards and proceed in a
safe manner. Failure to do so could
result in severe personal injury or
death due to electrical shock or
contact with moving parts.
Test mode procedure at the
ReliaTel™ control board
Test procedures
Operating checklist before start-up
Operating the unit from the roof
using the test mode at the
ReliaTel™ control board.
•
Unit is level, with sufficient
clearance all round
•
Duct network is correctly sized
according to the unit
configuration, insulated, and
water-tight
CAUTION! Before proceeding with
the following test procedures, make
sure that thermostat or zone sensor
is off.
•
Condensate drainage line is
correctly sized, equipped with a
trap, and sloped
Power-up initialization
CAUTION! Use one of the following
"Test" procedures to bypass some
time delays and to start the unit at
the control panel.
CAUTION! Before proceeding with
any test procedure or operation,
make sure that crankcase heaters
have been energized for at least 8
hours.
•
•
Filters are in position, of correct
size and quantity and clean
Wiring is correctly sized and
connected in accordance with
wiring diagrams
Each step of unit operation can be
activated individually by
temporarily shorting across the
"Test" terminals for two to three
seconds.The Liteport LED located
on the RTRM module will blink
when the test mode has been
initiated.The unit can be left in any
"Test" step for up to one hour
before it will automatically
terminate, or it can be terminated
by opening the main power
disconnect switch. Once the test
mode has been terminated, the
Liteport LED will glow continuously
and the unit will revert to the
"System" control.
Units equipped with Scroll
compressors do not have crankcase
heaters.
•
Power supply lines are protected
by recommended fuses and
correctly earthed
Note:
•
•
•
Thermostat is correctly wired
and positioned
Unit is checked for refrigerant
charge and leaks
Indoor and outdoor fans rotate
freely and are fixed on shafts
Upon power initialization, the RTRM
performs self-diagnostic checks to
insure that all internal controls are
functional. It also checks the
configuration parameters against
the components connected to the
system.The Liteport LED located on
the RTRM module is turned "On"
within 1 second of power-up if
internal operation is okay.
•
•
Supply fan rotation speed is set
Access panels and doors are
replaced to prevent air entering
and risks of injury
•
Checking of the gas heating
section, in accordance with
above procedure
RT-SVX19A-E4
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
2. AutoTest Mode
Test modes
This method is not recommended
for start-up due to the short timing
between individual component
steps.This method initiates the
different components of the unit,
one at a time, when a jumper is
installed across the test terminals.
The unit will start the first test step
and change to the next step every
30 seconds. At the end of the test
mode, control of the unit will
automatically revert to the applied
"System" control method.
There are 2 methods in which the
"Test" mode can be cycled with the
test button:
1. StepTest Mode
This method initiates the different
components of the unit, one at a
time, by temporarily shorting across
the two test terminals for two to
three seconds. For the initial start-
up of the unit, this method allows
the technician to cycle a component
"On" and have up to 1 hour to
complete the check.
For unit test steps and test modes,
values to cycle the various
components, refer toTable 36.
Table 36 - ServiceTest Guide for Component Operation on gas-fired units
Indoor
Fan
Compressor Compressor
Step
Mode
Economizer
Heat 1
Heat 2
Outdoor 1 Outdoor 2
1
2
1
2*
3
Fan On
Econ.
CooI1
CooI2
Heat1
Heat2
On
On
On
On
On
On
Min
Open
Min
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
On
On
Off
Off
Off
Off
**
4
Min
**
5
Min
Off
Off
6
Min
* With Optional Accessory
** "Off" If temperature falls below 16° ( 1°)°C, "On" if temperature rises above 18°( 1°)°C.
Note: Steps for optional accessories and modes not present in unit will be skipped.
50
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Note: Unit to be installed outside
only.
Unit start-up
Verification of gas valve settings -
(Reserved for the qualified gas
technician)
Note: Expansion valve must be
adapted to the type of gas used:
•
•
•
G 20: 20 mb
G 25: 25 mb
G 31 (Propane): 37 or 50 mb
WARNING! Improper gas valve
setting may lead to burner
destruction and people injury.
Note: Unit factory-set for G20.
Figure 23 - Gas valve
1 = Negative pressure controller
2 = Safety solenoid valve
3 = Gas injector
4 = Air inlets
5 =To the burner
6 = Fan
7 = Gas unit
8 = Minimum gas pressure cut-out
RT-SVX19A-E4
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Table 37 - Marking category of the gas section in different countries
Country
Category
Type of gas
G20
FR
CH+ES-GB-IE-PT
II2H3P
IT
NL
BE
LU-DE
AT-DK-Fl-SE
I2H
II2E+3P
II2H3+
II2L3P
I2E+ & I3P
I2E & I3P
Pressure in mbar
20
25
37
20
-
20
-
-
20
25
37
20
20
50
20
G25
25
30
-
-
G31
37
37
Table 38 - Gas burner data
G350
YK* 155-175-200-225
1
Burner
G350
3
Natural Gas G20 (20mbar) 34.02 MJ/m (15°C-1013)
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
Reduced rate
CO %
8.1
3
Gas Flow (15 C-1013 mbar)
Heating Capacity
Heating Rate
(m /h)
(kW)
(kW)
%
8.13
69.3
69.1
77
76.8
90
Efficiency
90
< 0.001%
9 ppm
9.7%
G20 - 20mbar
@ 400V-3-50Hz
Nox ppm
Smoke analysis
CO
%
2
Burner
G350
3
Natural Gas G25 (20 ou 25 mbar) 29.30 MJ/m (15°C-1013)
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
Reduced rate
CO %
8.8
3
Gas Flow (15 C-1013 mbar)
Heating Capacity
Heating Rate
(m /h)
(kW)
(kW)
%
8.21
62.9
59.5
71.5
66.8
88
Efficiency
89
< 0.001%
-
G25 - 25mbar
@ 400V-3-50Hz
Nox ppm
Smoke analysis
CO
%
7. 4 %
2
Burner
G350
3
Propane Gas G31 (30, 37ou 50 mbar) 88.00 MJ/m (15 C-1013)
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
Reduced rate
Nominal rate
2.7
3
Gas Flow (15 C-1013 mbar)
Gas Flow (15 C-1013 mbar)
Heating Capacity
(m /h)
2.56
5.1
(kg/h)
(kW)
(kW)
4.9
57.5
55.3
65.3
62.6
88
Heating Rate
Efficiency
%
Reduced rate
88.3
98
Nominal rate
Combustion Air Flow
(Avec E=25%)
3
(m /h)
Reduced rate
CO %
93
< 0.001%
-
G31 - 37mbar
@ 400V-3-50Hz
Nox ppm
Smoke analysis
CO
%
8.9%
2
52
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Starting the unit in cooling mode
Operating pressures
Final installation checklist
•
Are all power cables tightened?
Check torque of power
cables contact !
Is the condenser fan and indoor
blower operating correctly, i.e.
correct rotation and without
undue noise?
Are the compressors operating
correctly and has the system
been checked for leaks?
Have the voltage and running
currents been checked to
determine if they are within
limits?
Have the air discharge grilles
been adjusted to balance the
system?
Has the ductwork been checked
for air leaks and any
condensation?
Has the air temperature rise
been checked?
Before start-up, ensure that all
power cables are tightened.
After the unit has operated in
cooling mode for a short period of
time, install pressure gauges on the
gauge ports of the discharge and
suction line valves.
Verify that the unit airflow rate is
adjusted according to the
information provided in the "Supply
fan adjustment" section of this
manual.
•
Note:To bypass time delays and
verify the operation of this unit from
the roof, use the "Test procedure"
section in this manual. Check the
suction and discharge pressures.
•
•
To start the unit in cooling mode:
•
Place the zone sensor system
switch in the "COOL" position.
Note: Always route refrigerant
hoses through the port hole
provided and ensure that the
compressor access panel is in place.
•
Position the cooling setpoint
approximately 10° below room
temperature and place the fan
switch in the "AUTO" or "ON"
position.
•
•
Cooling shutdown
•
Turn on unit main power supply.
To exit the test mode, disconnect
unit power for 3-5 seconds and
reapply. When running the unit
using the zone sensor as the
control, position the selector switch
to "OFF".
The condenser fan motor,
compressor and supply fan motor
should operate automatically.
•
•
There will be a delay of up to
5 minutes before the unit starts in
cooling mode.
Has the indoor airflow been
checked and adjusted if
necessary?
Has the unit been checked for
tubing and sheet metal rattles or
any unusual noises?
There may be a delay of up to
3 minutes before compressors shut
down and an additional one minute
before the fan shuts down in this
setting.
•
•
Do not de-energize main power
disconnect except when unit is to
be serviced. Power is required to
keep the compressor crankcase
warm and boil off refrigerant in the
oil (except on units with Scroll
compressors).
Are all covers and panels in
place and properly fastened?
RT-SVX19A-E4
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
ReliaTel™ is a microelectronic
control feature, which provides
operating functions that are
significantly different from
conventional electro-mechanical
units.The master module is the
ReliaTel™ Refrigeration Module
(RTRM).
Evaporator Fan Operation
Cooling without an
Economizer
When the fan selection switch is set
to the "Auto" position, the RTRM
energizes the (K6) relay coil
approximately one second after
energizing the compressor
contactor coil (CC1) in the cooling
mode. In heating mode, the RTRM
energizes the (K6) relay coil
approximately 45 seconds after gas
ignition. Closing the K6 contacts on
the RTRM energizes the supply fan
relay (F) coil to start the supply fan
motor (IDM).
When the system switch is set to
the "Cool" position and the zone
temperature rises above the cooling
setpoint controlband, the RTRM
energizes the (K9) relay coil located
on the RTRM. When the K9 relay
contacts close, the compressor
contactor (CC1) coil is energized
provided the low pressure control
(LPC1) and high pressure control
(HPC1) are closed. When the CC1
contacts close, compressor (CPR1)
and the outdoor fan motor (ODM)
start to maintain the zone
The RTRM provides compressor
antishort cycle timing functions
through minimum "Off" and "On"
timing to increase reliability,
performance and to maximize unit
efficiency.
Upon power initialization, the RTRM
performs self-diagnostic checks to
insure that all internal controls are
functioning. It checks the
configuration parameters against
the components connected to the
system.
The RTRM de-energizes the fan
relay (F) approximately 60 seconds
after the cooling requirement has be
satisfied to enhance unit efficiency.
temperature to within 2 F of the
sensor setpoint at the sensed
location.
When the heating cycle is
terminated, the supply fan relay (F)
coil is de-energized approximately
90 seconds after the heating
requirement.
If the first stage of cooling can not
satisfy the cooling requirement, the
RTRM energizes the (K10) relay coil
located on the RTRM. When the
(K10) relay contacts close, the
compressor contactor (CC2) coil is
energized provided the low
pressure control (LPC2) and high
pressure control (HPC2) are closed.
When the CC2 contacts close,
compressor (CPR2) starts to
The LED located on the RTRM
module is turned "On" within one
second after power-up if all internal
operations are okay.
When the fan selection switch is set
to the "On" position, the RTRM
keeps the supply fan relay coil (F)
energized for continuous fan motor
operation.
When the unit is equipped with the
optional clogged filter switch, wired
between terminals J7-3 and J7-4 on
the ReliaTel™ Options Module
(RTOM), the RTRM produces an
analog output if the clogged filter
switch (CFS) closes for two minutes
after a request for fan operation.
When the system is connected to a
remote panel, the "SERVICE" LED
will be turned on when this failure
occurs.
maintain the zone temperature to
within 2 F of the sensor setpoint
at the sensed location.
54
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
The ECA continues to modulate the
economizer damper open/closed to
keep the mixed air temperature that
is calculated by the RTRM.
Low Ambient Operation
Cooling with an
Economizer
The economizer is utilized to control
the zone temperature providing the
outside air conditions are suitable.
During low ambient operation,
outside air temperature below 13ºC,
the RTRM will cycle the compressor
and outdoor fan motor "Off" for
approximately three minutes after
every 10 minutes of accumulated
compressor run time.The supply
fan motor (IDM) will continue to
operate during this evaporator
defrost cycle (EDC) and the
compressor and outdoor fan will
return to normal operation once the
defrost cycle has terminated and
the compressor "Off" time delay has
been satisfied.
If economizing is not possible, the
ECA drives the damper to the
minimum position setpoint when
the supply fan relay (F) is energized
and allows mechanical cooling
operation. When the unit is
equipped with the optional fan
failure switch, wired between
terminals J7-5 and J7-6 on the
RTOM, the RTRM will stop all
cooling functions and produce an
analog output if the fan failure
switch (FFS) does not open within
40 seconds after a request for fan
operation. When the system is
connected to a remote panel, the
"SERVICE" LED will flash when this
failure occurs.
Outside air is drawn into the unit
through modulating dampers. When
cooling is required and economizing
is possible, the RTRM sends the
cooling request to the unit
economizer actuator (ECA) to open
the economizer damper.The RTRM
tries to cool the zone utilizing the
economizer to slightly below the
zone temperature setpoint. If the
mixed air sensor (MAS) senses that
the mixed air temperature is below
53ºF, the damper modulates toward
the closed position. If the zone
temperature continues to rise above
the zone temperature setpoint
controlband and the economizer
damper is full open, the RTRM
energizes the compressor contactor
(CC1). If the zone temperature
continues to rise above the zone
temperature setpoint controlband
and the economizer damper is fully
open, the RTRM energizes the
compressor contactor (CC2).
RT-SVX19A-E4
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
3. Comparative Enthalpy - By
utilizing a humidity sensor and a
temperature sensor in both the
return air stream and the
Economizer Set-Up
Ignition Module
Adjusting the minimum position
potentiometer located on the unit
economizer Actuator (ECA) sets the
required amount of ventilation air.
Two Stage (IGN) runs self-check
(including verification that the gas
valve is de-energized). (IGN) checks
the high-limit switches (TC01 &
TC02) for normally closed contacts.
With 115 VAC power supplied to the
ignition module (IGN), the hot
surface ignition probe (IP) is
preheated for approximately
45 seconds.The gas valve (GV) is
energized for approximately
7 seconds for trial for ignition, to
ignite the burner.
outdoor air stream, the unit
control processor (RTRM) will be
able to establish which
conditions are best suited for
maintaining the zone
Two of the three methods for
determining the suitability of the
outside air can be selected utilizing
the enthalpy potentiometer on the
ECA, as described below:
1. AmbientTemperature -
controlling the economizing
cycle by sensing the outside air
dry bulb temperature.TheTable
below lists the selectable dry
bulb values by potentiometer
setting.
2. Reference Enthalpy - controlling
the economizer cycle by sensing
the outdoor air humidity.The
Table below lists the selectable
enthalpy values by
temperature, i.e. indoor
conditions or outdoor conditions.
The potentiometer located on
the ECA is non-functional when
both the temperature and
humidity sensors are installed.
Once the burner is ignited, the hot
surface ignition probe (IP) is de-
energized by the ignition module
(IGN) and functions as the flame
sensing device.
Table 39 - Potentiometer Setting
Dry BuIb
(°C)
23*
21
Enthalpy
(KJ/kg)
63
Potentiometer
Setting
A
If the burner fails to ignite, the
ignition module will make two more
attempts before locking out.The
green LED will indicate a lock out by
two fast flashes. An ignition lockout
can be reset by:
1. Opening for 3 seconds and
closing the main power
disconnect switch
2. By switching the "Mode" switch
on the zone sensor to "OFF" and
then to the desired position
3. Allowing the ignition control
module to reset automatically
after one hour.
B
58
C
D
19
53
17
51
potentiometer setting.
*Factory Setting
If the outside air enthalpy value
is less than the selected value,
the economizer is allowed to
operate.
ReliaTel™ Control Heating
Operation
When the system switch is set to
the "Heat" position and the zone
temperature falls below the heating
setpoint controlband, a heat cycle is
initiated when the RTRM
communicates ignition information
to the Ignition module (IGN).
56
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Refer to the ignition control module
diagnostics section for the LED
diagnostic definitions.
Final installation checklist
•
Is the condenser fan and indoor
blower operating correctly, i.e.:
correct rotation and without
undue noise?
When the fan selection switch is set
to the "Auto" position, the RTRM
energizes the supply fan relay (F)
coil approximately 30 second after
initiating the heating cycle to start
the supply fan motor (IDM).
•
•
•
Are the compressors operating
correctly and has the system
charge been checked?
Has the gas module been
installed as per the procedure in
this manual?
Have the voltage and running
currents been checked to
determine if they are with in
limits?
The automatic reset high limit
(TCO1), located in the bottom right
corner of the burner compartment,
protects against abnormally high
leaving air temperatures.
The automatic reset fan fail limit
(TCO2), located in the upper middle
section of the supply fan board,
protects against abnormally high
heat buildup which could occur
because of extended cycling of the
high limit (TCO1) or if the supply
fan motor (IDM) fails to operate.
ShouldTCO2 open, the RTRM will
energize the supply fan relay (F) in
an attempt to start the fan motor.
The RTRM signals that a heat failure
has occurred by flashing the "Heat"
LED on the zone sensor.
•
•
Have the air discharge grilles
been adjusted to balance the
system?
Has the ductwork been checked
for air leaks and any
condensation?
•
•
Has the heating air temperature
rise been checked?
Has the indoor airflow been
checked and adjusted if
necessary?
•
•
Has the unit been checked for
tubing and sheet metal rattles
orany unusual noises?
Are all covers and panels in
placeand properly fastened?
There is a Green LED located in the
Ignition Control Module.The table
below lists the diagnostics and the
status of the LED during the various
operating states.
To keep the unit operating safely
and efficiently, the manufacturer
recommends that a qualified service
technician check the entire system
at least once each year, or more
frequently if conditions warrant.
Table 40 -LED status
Diagnostics
Green LED
Off
Red LED
Off
1. Powered but no heat dernand
2. Heat demand without fault
Flash ing
Off
3. No flame detection on ignition - or signal detected
and then lost
Off
Flashing
4. Gas unit incorrectly wired or flame signal detected on
a heat demand
Steady
Off
Flashing
Steady
5. Internal fault
RT-SVX19A-E4
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
To keep the unit operating safely
and efficiently, the manufacturer
recommends that a qualified service
technician check the entire system
at least once each year, or more
frequently if conditions warrant it.
End user routine
maintenance
Some of the periodic maintenance
functions for the unit can be
undertaken by the end user.This
includes replacing (disposable) or
cleaning (permanent) air filters,
cleaning unit cabinet, cleaning the
condenser coil, and carrying out a
general unit inspection on a regular
basis.
WARNING! Disconnect the power
supply before removing access
panels to service the unit. Failure to
disconnect power before attempting
any servicing can result in severe
injury or death.
Air filters
It is very important for the central
duct system air filters to be kept
clean.
These should be inspected at least
once a month when the system is in
constant operation (in new
buildings, the filters should be
checked every week for the first four
weeks). If disposable-type filters are
used, they should only be replaced
with ones of the same type and size.
Table 41 - Refrigerant charge
Refrigerant charge
(kg) (R22/R407C)
Unit model and size
Number of circuits
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
1
1
1
2
2
3.5
3.7
4.5
3.7/2.1
3.5/3.0
Note: Refrigerant charges are given for information only. Check unit nameplate for exact values.
58
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Note: Do not attempt to clean
disposable filters. Permanent filters
can be cleaned by washing with a
mild detergent and water. Ensure
that the filters are thoroughly dry
before reinstalling them in the unit
(or duct system).
Service technician
maintenance
Before the cooling season, your
service technician may examine the
following areas of your unit:
•
•
•
Filters, for cleaning or
replacement
Motors and drives system
components
Economizer gaskets, for
replacement if necessary
Note: Replace permanent filters
annually if washing fails to clean
them, or they show signs of
deterioration. Be sure to use the
same type and size as were
originally installed.
•
•
Condenser coils, for cleaning
Safety controls, for mechanical
cleaning
Condenser coil
Unfiltered air circulates through the
unit's condenser coil and can cause
the coil's surface to become
clogged with dust, dirt, etc.To clean
the coil, brush the coil surface in the
direction of the fins with a soft
bristled brush.
•
Electrical components and
wiring, for replacement and
tightening of connections as
necessary
•
•
Condensate drain, for cleaning
Unit duct connections, to ensure
they are physically sound and
sealed to the unit casing
Unit mounting support, to
ensure that it is sound
Keep all vegetation away from the
condenser coil area.
•
•
Hot water coil (option)
The unit, to ensure there is no
obvious deterioration
Stop the unit. Do not disconnect the
main supply to the unit.This will
permit the anti-frost protection to
continue to operate, and avoid
water to freeze-up in the coil.
Before the heating season, your
service technician may examine the
following areas of your unit:
•
The unit, to ensure that the
condenser coil can receive the
required airflow (that the
condenser fan grille is not
obstructed)
•
•
The control panel wiring, to
verify that all electrical
connections are tight, and that
wire insulation is intact
Clean burner area, verify the gas
heat system operates properly.
RT-SVX19A-E4
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5. If no failures are indicated, use
one of theTEST mode
System Status Checkout Procedure
Troubleshooting
"System Status" is checked by using
one of the following two methods:
The RTRM has the ability to provide
the service personnel with some
unit diagnostics and system status
information. Before turning the
main power disconnect switch "Off",
follow the steps below to check the
ReliaTel™
procedures described in the unit
"Start-Up" section to start the
unit.This procedure will allow
you to check all of the RTRM
outputs, and all of the external
controls (relays, contactors, etc.)
that the RTRM outputs energize,
for each respective mode.
Method 1
If the Zone Sensor Module (ZSM) is
equipped with a remote panel with
LED status indication, you can check
the unit within the space. If the ZSM
does not have LED's, use Method 2.
Refrigeration Module (RTRM). All
diagnostics & system status
information stored in the RTRM will
be lost when the main power is
turned "Off".
Proceed to Step 6.
6. Step the system through all of
the available modes, and verify
operation of all outputs, controls,
and modes. If a problem in
operation is noted in any mode,
you may leave the system in that
mode for up to one hour while
troubleshooting. Refer to the
sequence of operations for each
mode, to assist in verifying
proper operation. Make the
necessary repairs and proceed to
Steps 7 and 8.
7. If no abnormal operating
conditions appear in the test
mode, exit the test mode by
turning the power "Off" at the
main power disconnect switch.
8. Refer to the individual
component test procedures if
other microelectronic
THS/P03 have the remote panel
indication feature.The LED
descriptions are listed below:
1. Verify that the Liteport LED on
the RTRM is burning
LED 1 (System) "On" during
normal operation. "Off" if a system
failure occurs or the LED fails.
"Flashing" indicates test mode.
continuously. If the LED is lit, go
to Step 3.
2. If the LED is not lit, verify that
24 VAC is present between J1-1
and J1-2. If 24 VAC is present,
proceed to Step 3. If 24 VAC is
not present, check the unit main
power supply, check transformer
(TNS1). Proceed to Step 3 if
necessary.
LED 2 (Heat) "On" when the heat
cycle is operating. "Off" when the
heat cycle terminates or the LED
fails. "Flashing" indicates a heating
failure.
LED 3 (Cool) "On" when the
cooling cycle is operating. "Off"
when the cooling cycle terminates
or the LED fails. "Flashing" indicates
a cooling failure.
3. Utilizing "Method 1" or
"Method 2" in the system status
diagnostic section, check the
following: System status,
Heating status, Cooling status. If
a System failure is indicated,
proceed to Step 4. If no failures
are indicated, proceed to Step 5.
LED 4 (Service) "On" indicates a
clogged filter. "Off" during normal
operation. "Flashing" indicates an
supply fan failure.
components are suspect.
4. If a System failure is indicated,
recheck Steps 1 and 2. If the LED
is not lit in Step 1, and 24 VAC is
present in Step 2, the RTRM has
failed. Replace the RTRM.
60
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Below is the complete listing of
failure indication causes:
Cooling Failure
Simultaneous Heat and Cool Failure
1. Emergency Stop is activated
1. Cooling and heating set point
(slide pot) on the zone sensor
has failed. Refer to the "Zone
SensorTest Procedure" section.
2. Zone temperature thermistor
ZTEMP on ZTS failed. Refer to
the "Zone SensorTest Procedure"
section.
3. CC1 or CC2 24 VAC control circuit
has opened, check CC1 & CC2
coils, and any of the controls
below that apply to the unit
(HPC1, HPC2).
4. LPC1 has opened during the
3 minute minimum "on time"
during 4 consecutive compressor
starts, check LPC1 or LPC2 by
testing voltage between the J1-8
& J3-2 terminals on the RTRM
and ground. If 24 VAC is present,
the LPC's has not tripped. If no
voltage is present, LPC's has
tripped.
System failure
Method 2
Check the voltage between
terminals 6 and 9 on J6, it should
read approximately 32 VDC. If no
voltage is present, a system failure
has occurred. Refer to Step 4 in the
previous section for the
The second method for determining
system status is done by checking
voltage readings at the RTRM (J6).
The system indication descriptions
and the approximate voltages are
listed below.
recommended troubleshooting
procedure.
System Failure
Measure the voltage between
terminals J6-9 & J6-6.
Heating Failure
Verify Heat Failure by Ignition
Module (IGN) LED indicator:
Normal Operation = approximately
32 VDC
OFF: No Power or Failure
ON: Normal
System Failure = less than 1 VDC,
approximately 0.75 VDC
Slow Flash: Normal, Heat Call
Fast Flash: Error Code:
Test Mode = voltage alternates
between 32 VDC & 0.75 VDC
1
2
3
4
5
6
Flash: Communication Failure
Flashes: System Lockout
Flashes: Pressure Switch Fail
FlashesTC01 orTC02 Open
Flashes: Flame w/o Gas Valve
Flashes: Flame Rollout Open
Heat Failure
Measure the voltage between
terminals J6-7 & J6-6.
Service Failure
1. If the supply fan proving switch
has closed, the unit will not
operate (when connected to
RTOM), check the fan motor,
belts, and proving switch.
Heat Operating = approximately
32 VDC
Heat Off = less than 1 VDC,
approximately 0.75 VDC
2. Clogged filter switch has closed,
check the filters.
Heating Failure = voltage alternates
between 32 VDC & 0.75 VDC
Cool Failure
Measure the voltage between
terminals J6-8 & J6-6.
Cool Operating = approximately
32 VDC
Cool Off = less than 1 VDC,
approximately 0.75 VDC
Cooling Failure = voltage alternates
between 32 VDC & 0.75 VDC
RT-SVX19A-E4
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Service Failure
Resetting Cooling and Ignition
Lockouts
ZoneTemperature Sensor (ZTS)
Service Indicator
Measure the voltage between
terminals J6-10 & J6-6.
Cooling Failures and Ignition
The ZSM SERVICE LED is a generic
indicator that will signal the closing
of a Normally Open switch at any
time, providing the Indoor Motor
(IDM) is operating.This indicator is
usually used to indicate a clogged
filter, or an air side fan failure.
Clogged Filter = Approximately
32 VDC.
Lockouts are reset in an identical
manner. Method 1 explains
resetting the system from the space,
Method 2 explains resetting the
system at the unit.
Normal = Less than 1 VDC,
approximately 0.75 VDC
Fan Failure = voltage alternates
between 32 VDC & 0.75 VDC.
Note: Before resetting Cooling
Failures and Ignition Lockouts,
check the Failure Status Diagnostics
by the methods previously
explained.
The RTRM will ignore the closing of
this Normally Open switch for 2 ( 1)
minutes.This helps prevent
nuisance SERVICE LED indications.
The exception is the LED will flash
40 seconds after the fan is turned
"On" if the Fan Proving Switch is not
made.
To use LED's for quick status
information at the unit, purchase a
ZSM and connect wires with
alligator clamps to terminals 6
through 10.
Diagnostics will be lost when the
power to the unit is disconnected.
Connect each respective terminal
wire (6 through 10) from the Zone
Sensor to the unit J6 terminals 6
through 10.
Method 1
Clogged Filter Switch
To reset the system from the zone,
turn the "Mode" selection switch at
the zone sensor to the "Off"
position.
This LED will remain lit the entire
time that the Normally Open switch
is closed.The LED will be turned off
immediately after resetting the
switch (to the Normally Open
position), or any time that the IDM
is turned "Off".
Note: If the system is equipped
with a programmable zone sensor
THS03, the LED indicators will not
function while the ZSM is
connected.
After approximately 30 seconds,
turn the "Mode" selection switch to
the desired mode, i.e. Heat, Cool or
Auto.
If the switch remains closed, and
the IDM is turned "On", the SERVICE
LED will be turned "On" again after
the 2 ( 1) minute ignore delay.
Method 2
To reset the system at the unit,
cycle the unit power by turning the
disconnect switch "Off" and then
"On".
This LED being turned "On", will
have no other affect on unit
operation. It is an indicator only.
Lockouts can be cleared through the
building management system. Refer
to the building management system
instructions for more information.
Fan Failure Switch
When the "Fan Failure" switch is
wired to the RTOM, the LED will
remain flashing the entire time the
fan proving switch is closed,
indicating a fan failure, and it will
shut the unit operations down.
62
RT-SVX19A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Table 42 -Thermistor Resistance /
Temperature Chart
ZoneTemperature Sensor (ZTS)Test
Note:These procedures are not for
programmable or digital models
and are conducted with the Zone
Sensor
Temperature/resistance coefficient is
negative.
Temperature
Resistance
(kOhms)
103
(°C)
-21
-15
-9
Module electrically removed from
the system.
74.65
54.66
46.94
40.4
Test 1
-7
ZoneTemperatureThermistor
(ZTEMP)
-4
-1
34.85
30.18
26.22
22.85
19.96
17.47
This component is tested by
measuring the resistance between
terminals 1 and 2 on the Zone
Temperature Sensor.
2
4
7
10
13
16
18
21
24
27
29
32
35
38
15.33
13.49
11.89
10.5
9.297
8.247
7. 3 3
6.528
5.824
RT-SVX19A-E4
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature order number
Date
RT-SVX19A-E4
0805
Supersedes
RT-SVX04A and RT-SVX05A
Europe
Literature stocking location
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.
A business of American Standard
For more information, contact your localTrane
sales office or e-mail us at [email protected]
American Standard Europe BVBA
Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium
Download from Www.Somanuals.com. All Manuals Search And Download.
|