Tracer Controllers
Tracer MP580/581
Programmable Controllers
September 2001
CNT-PRC002-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Product overview . . . . . . . . . . . . . . . . . . . 4
Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Product models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Inputs and outputs . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Graphical programming . . . . . . . . . . . . . . . . . . . . . . 6
Interoperability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operator display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 8
Network architecture . . . . . . . . . . . . . . . 10
Wiring diagram . . . . . . . . . . . . . . . . . . . . 11
Enclosure interior. . . . . . . . . . . . . . . . . . . 12
Specifications . . . . . . . . . . . . . . . . . . . . . 13
CNT-PRC002-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Product overview
The Tracer MP580 programmable
controller is factory-installed on Trane
Modular and T-Series Climate Changer
air handlers.
Frame-mounted Tracer MP581
The frame-mounted Tracer MP581
consists of a circuit board and a
termination board mounted in a two-
piece modular frame assembly. This
modular design allows the circuit board
to be programmed at a different location
while installation and wiring are
The Tracer MP581 programmable
controller is available for field installation
for a variety of heating, ventilating, and
air-conditioning (HVAC) applications.
completed. The frame-mounted Tracer
MP581 can be mounted in new
equipment or an existing enclosure.
Applications
Tracer MP580/581 controllers support a
wide variety of building control
applications, including:
Tracer MP581 in a NEMA-1 enclosure
The Tracer MP581 with enclosure
consists of the frame assembly
• Air-handler control
• Support of the LonMark Space Com-
fort Controller (SCC) profile and the
Discharge Air Controller (DAC) profile
for air handlers
• Control of mechanical-room equip-
ment, including cooling towers,
pumps, boilers, and heat exchangers
• Supervisory control of an HVAC net-
work for mid-sized buildings
• Nearly any control process needed in
a commercial building
mounted in an enclosure compliant with
National Electrical Manufacturers
Association (NEMA) type-1 standards. A
line-to-low voltage transformer provides
power to the electronics. The enclosure
has a hinged door and plenty of room for
input and output wiring. The complete
assembly is UL-listed.
Inputs and outputs
Tracer MP580/581 controllers have the
following inputs and outputs (illustrated
in Figure 8 on page 11):
Product models
• 12 universal inputs
Several models of Tracer MP580/581
controllers are available. Tracer MP581
models are illustrated in Figure 1 on
page 5. Operator-display touch screens
are available as an option for all models.
Dry contact binary (including pulse
accumulation), 0–20 mA, 0–10 Vdc,
linear resistance, or thermistor. Four
of the twelve inputs can be used
directly with resistance temperature
detectors (RTDs).
Tracer MP580 on Trane air handlers
The Tracer MP580 controller is available
packaged with Trane Modular and
T-Series Climate Changer air handlers.
The controller is factory wired to all
sensors, actuators, valves, starters, and
other items shipped with the air handler.
Factory testing of connected points
helps minimize field commissioning
time and expense.
• Static pressure input
Specialized input for a Trane
differential pressure sensor
(5 Vdc, 0–5 in. wc).
• 6 binary outputs
12 VA at 24 Vac powered relay
contacts.
• 6 analog outputs
0–10 Vdc or 0–20 mA.
4
CNT-PRC002-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 1: Tracer MP581 and operator display models
Tracer MP581 with optional operator display
Tracer MP581 without operator display
Portable operator display
Stand-alone operator display
Frame-mounted Tracer MP581
CNT-PRC002-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
Graphical programming
Operator display
The Tracer graphical programming (TGP)
editor, shown in Figure 3 on page 7,
eliminates the need for line-by-line
programming. The TGP editor is a
software component of Trane’s Rover
service tool. TGP has the following
advantages:
The optional operator-display touch
screen is an intuitive operator interface
for monitoring and changing building
control functions. With the operator
display you can:
• Monitor space temperature, relative
humidity, and other variables
• Easy to learn—programming is as
easy as assembling logic blocks with a
computer mouse, much like creating a
flow chart.
• Powerful—the TGP editor has built-in
PID functions and more than 50 logic
blocks for building programs.
• Self documenting—programs can be
printed and used as pictorial represen-
tations of sequences of operation (see
Figure 4 on page 7).
• Programs are stored in the controller
along with their graphical
• Change setpoints and scheduled
occupancy times
• Identify and troubleshoot problems
• View and reset controller alarms
• Manually override outputs
The operator display includes a 7-day
time clock that gives Tracer MP580/581
controllers the ability to manage time-of-
day scheduling, with two on/off times
per day and up to 20 exception
schedules per year.
Figure 2 shows a typical operator display
screen.
representation, and can be uploaded,
viewed, and re-used.
Figure 2: Typical status screen
Interoperability
Tracer MP580/581 controllers
communicate by means of the LonTalk
protocol. The controllers can be
configured to conform to the LonMark
Space Comfort Controller (SCC) profile
or the Discharge Air Controller (DAC)
profile. Tracer MP580/581 controllers
can work with any control system that
supports the LonTalk protocol and uses
FTT10-A communications.
The operator display is available in the
following configurations:
• Door-mounted on the Tracer MP581
• Stand-alone operator display for
mounting up to 20 ft (7 m) away from
a Tracer MP580 or MP581
• Portable operator display for
temporary connections to the Tracer
MP580/581 or Tracer AH540/541
Figure 1 on page 5 illustrates the
operator displays available for the
Tracer MP581.
6
CNT-PRC002-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 3: TGP editor showing a supply fan program
Figure 4: TGP printout of a hot water valve program
CNT-PRC002-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
Figure 5 shows the dimensions of the
frame-mounted Tracer MP581 controller.
Figure 6 on page 9 shows the
dimensions of the Tracer MP581
NEMA-1 enclosure.
Figure 5: Frame-mounted Tracer MP581 dimensions
8
CNT-PRC002-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 6: Tracer MP581 enclosure dimensions
CNT-PRC002-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Network architecture
Tracer MP580/581 controllers can
operate as stand-alone controllers, on a
peer-to-peer network, or as part of a
Tracer Summit building automation
system (see Figure 7).
With an operator display, you can
monitor information and make control
changes on a peer-to-peer network.
Figure 7: Tracer MP581 controller as part of a building automation system with Trane LonTalk controllers
Tracer Summit
PC Workstation
Tracer MP581
Building
controlunit
(BCU)
Tracer ZN511
Tracer ZN521
Comm 5 (LonTalk)
communications link
Tracer MP501
Tracer MP503
Rover service tool
Tracer AH541
10
CNT-PRC002-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring diagram
Figure 8 shows typical input and output
connections to the termination board.
For details on inputs and outputs, see
“Inputs and outputs” on page 4.
Figure 8: Wiring diagram
<1000 ft
(300 m)
Powered output
0–10 Vdc output
Load > 500 Ω
<1000 ft
(300 m)
<300 ft
(100m)
Temperature sensor
<1000 ft
(300 m)
0–20 mA sensor
CNT-PRC002-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Enclosure interior
Figure 9 shows the interior of the Tracer
MP581 NEMA-1 enclosure.
Figure 9: Tracer MP581 enclosure interior
Line-to-low voltage
power transformer
Main circuit board
Mounting location
for optional static
pressure sensor
Termination board
12
CNT-PRC002-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Specifications
Power requirements
Weight
Nominal rating: 24/120/230 Vac;
50/60 Hz; 1 phase
With NEMA-1 enclosure: 15 lb (7 kg)
Frame-mounted: 2 lb (1 kg)
Voltage utilization range
Mounting
NEMA-1 enclosure: wall-mounted with
#10 (5 mm) screws
24 Vac (frame-mounted): 19–30 Vac
120 Vac nominal: 98–132 Vac
230 Vac nominal: 184–254 Vac
Frame-mounted: #8 (4 mm) screws
Operating environment
Temperature
Analog-to-digital conversion
Resolution: 12 bits
Without display: From –40°F to 158°F
(–40°C to 70°C)
With display: From 32°F to 122°F
(0°C to 50°C)
Digital-to-digital conversion
Resolution: 12 bits
Humidity: 10–90% non-condensing
Microprocessor
Storage environment
Temperature
Without display: From –58°F to 203°F
(–50°C to 95°C)
Motorola MC68332 20 MHz
Memory
RAM: 512 K
With display: From –13°F to 149°F
(–25°C to 65°C)
ROM: 2 MB Flash
EEPROM: 256 K
Humidity: 10–90% non-condensing
Operator interface
Available enclosures
Video graphics adapter (VGA) backlit
liquid crystal display (LCD) with touch
screen; 4.5 in. × 3.4 in. (115 mm ×
86 mm) viewable area; resolution of
320 × 240 pixels
Tracer MP580: metal enclosure
packaged with air handler
Tracer MP581
NEMA-1 enclosure
Frame-mounted (no enclosure)
Time clock
Included with operator display; crystal
controlled, super-capacitor backed
Dimensions
Tracer MP580 enclosure
15 in. × 8 ½ in. × 5 in.
Battery
(381 mm × 215 mm × 127 mm)
Not required—backed by super capacitor
for seven days under normal operating
conditions; all other programs backed by
non-volatile memory
Tracer MP581 NEMA-1 enclosure
16 ½ in. × 14 ¾ in. × 5 ½ in.
(418 mm × 373 mm × 140 mm)
Frame-mounted Tracer MP581
10 ¼ in. × 8 in. × 3 ½ in.
(260 mm × 203 mm × 89 mm)
Agency listings/compliance
CE—Immunity (directive 89/336/EEC)
EN 50090-2-2:1996
Minimum clearances
NEMA-1 enclosure
12 in. (30 cm) top, bottom, and right
24 in. (60 cm) left
36 in. (90 cm) front
CE—Emissions (directive 89/336/EEC)
EN 50090-2-2:1996
EN 61000-3-2:1995
EN 61000-3-3:1995
UL and C-UL listed
Energy management system
Frame-mounted
½ in. (1.3 cm) top, right, and front
6 in. (15 cm) left (for I/O wiring)
3 in. (8 cm) bottom (for
UL 916
FCC approved: Part 15, Class A
communications wiring)
CNT-PRC002-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
File Number
CNT-PRC002-EN
PL-ES-CNT-000-PRC002-0901
New
Supersedes
The Trane Company
An American Standard Company
Stocking Location
La Crosse
For more information contact
your local district office or
e-mail us at [email protected]
Since The Trane Company has a policy of continuous product and product data improvement, it
reserves the right to change design and specifications without notice.