Trane Heat Pump TWA PRC001 EN User Manual

Split System Heat Pumps  
Split System Heat Pumps  
7 1/2 through 20Ton - 50 Hz  
Air Handlers  
5 through 20Ton - 50 Hz  
July 2000  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction  
2
4
6
Features and Benefits  
Application Considerations  
Selection Procedure  
Model Number Description  
General Data  
7
8
9
Performance Data  
12  
Cool and Heat Performance  
Fan Performance  
12  
24  
31  
Electric Power  
Connection andWiring  
Dimension andWeights  
Mechanical Specifications  
33  
39  
55  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Heat Pumps  
Air Handlers  
• 3-D® Scroll compressors  
• Low voltage terminal board  
• Expansion valve(s)  
• ModelTWA155-200B have dual  
compressors with independent  
refrigerant circuits  
• Compressor motor overload protection  
• Control transformer  
• Convertible  
• PVC double-sloped, removeable drain  
pan  
• Fan relay  
• High and low pressure cut-out  
switches  
• Efficient evaporator coil  
• Baked enamel finish  
• Filter access panel  
• Internal pressure relief valve  
• Liquid line filter drier, factory installed  
• Holding charge of dry nitrogen  
• Copper tube, aluminum plate fin coils  
• Low ambient cooling to 35° F (1.7° C)  
as manufactured  
Weather resistant baked enamel finish  
• Heavy gauge steel cabinet  
• Mounting/lifting rails under base  
• 1” (25.4 mm) throwaway filters  
standard with provisions for field  
supplied 2”  
(50.8 mm) filters  
• Adjustable belt drive motor  
• Single point power entry to electric  
heaters  
• Refrigerant piping and/or electrical  
connections provided from either side  
Odysseyair handler versatility is further  
increased by a complete line of optional  
accessories designed to match and easy  
to install:  
All condensing units offer these optional  
accessories:  
• Head Pressure Control — Low Ambient  
CoolingTo 0° F (-17.8° C)  
• Coil Guards Kits  
• Isolators both Rubber-in-Shear and  
SpringType  
• Discharge Plenum and Grille  
• Return Grille  
• Anti-Short-Cycle Kit  
• Subbase  
• Time Delay Relay  
• Electric Heaters  
• High Static Evaporator Motor  
• Isolators both Rubber-in-Shear and  
SpringType  
4
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Heat Pump Options  
Trane split systems have been specified  
in thousands of applications and you’ll  
find Odyssey will win you even more  
jobs with its smaller, more manageable  
cabinet.  
Odyssey air handler versatility is further  
increased by a complete line of  
accessories designed to match and  
install smoothly:  
• Discharge Plenum and Grille  
• Return Grille  
The Odysseysplit system product line  
includes heat pumps in both single and  
dual compressor options.  
TWA075A andTWA100A single  
compressor models feature single  
refrigeration circuitry lowering job  
installation costs by requiring only one  
set of refrigerant lines.These units are  
ideal for either the low cost, new  
construction jobs as well as renovation  
and replacement buildings.  
Air Handlers Offer More Flexibility  
Flexibility is a key to meeting changing  
market requirements. Odyssey split  
systems offer various compressor  
options and convertible air handlers.The  
air handlers can be installed either  
vertically in a mechanical room or  
horizontally above a ceiling. And it  
doesn’t require any removal of panels or  
reconfiguration of the drain pan to make  
either airflow application work. All the air  
handlers feature factory installed belt  
drive and ball bearing evaporator fans  
with adjustable sheaves for maximum  
airflow performance.The standard motor  
on theTWE100A air handler will deliver  
4000 cfm (1888 l/s) at 0.8” (20.32 mm)  
ESP. Plus oversized motors are available  
for higher static applications.  
• Subbase  
• Electric Heaters  
• High Static Evaporator Motor  
• Isolators both Rubber-in-Shear and  
SpringType  
• A Full Line of Thermostats  
In addition, Odyssey modelsTWA155B  
throughTWA200B are dual compressor  
units that give true standby protection; if  
one compressor fails, the second will  
automatically start-up. Also, the first  
compressor can be serviced without  
shutting down the unit since refrigerant  
circuits are independent.  
OdysseyA Complete Split System  
Odyssey delivers the flexibility to select a  
complete system that meets your  
particular job requirements. Air Handlers  
are designed, tested and rated with  
condensing units to let you select the  
proper match between capacity and  
load. Condensing units can also be  
matched withTrane built-up air handlers.  
These matched systems can be quickly  
engineered for specific applications.  
Dual compressors are not just for  
protection, they also save energy costs.  
Most buildings are designed for the peak  
load requirements yet the building  
usually operates at less than peak load.  
During light load conditions only one  
compressor functions to maintain the  
space comfort thus reducing the need  
for energy.  
LowAmbient Cooling Operation  
Each condensing unit can operate to  
35° F (1.7° C) as standard. An accessory  
Head Pressure Control gives you the  
capability to operate to 0° F (-17.8° C). All  
condensing units offer these accessories:  
• Head Pressure Control  
• Coil Guard Kits  
• Isolators both Rubber-in-Shear and  
SpringType  
• Anti-Short-Cycle Kit  
• Time Delay Relay  
TWA-PRC001-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Application of this product should be  
within the catalogued airflow and  
performance considerations.The System  
Selection Program will simulate product  
performance for a set of given  
conditions. It is recommended that the  
program should be run at the lowest  
outdoor ambient and supply air flow  
rates requiring cooling or heating  
operation for a particular unit. For more  
information on the System Selection  
Program contact your localTrane  
Representative.  
should be reviewed with the localTrane  
Representative.  
pressure control will allow operation to  
0° F (-17.8° C) outdoor ambient.When  
using these units with control systems  
such as bypass changeoverVariable Air  
Volume, consider the requirement for a  
head pressure control to allow low  
ambient cooling.  
LowAmbient Cooling  
As manufactured, these units can  
operate to 35° F (1.7° C) in the cooling  
mode of operation. An accessory head  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate  
serviceability, maximum capacity and  
peak operating efficiency. Actual  
clearances that appear inadequate  
Typical Horizontal Air HandlerApplication  
TypicalVerticalAir Handler Application  
Typical Split System Application  
6
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedure  
Cooling Capacity  
actualTotal Static Pressure is 1.10 - 0.10 =  
1.00 in. (27.9 - 2.5 = 25.4 mm)  
(275 - 25 = 250 Pa)  
Air Delivery Selection  
Step 1 — Calculate the buildings total  
and sensible cooling loads at design  
conditions. Use theTrane calculation  
form or any other standard accepted  
method.  
External static pressure drop through the  
air distribution system has been  
calculated to be 0.77 inches (19.6 mm) of  
water gauge. FromTable PD-24 static  
pressure drop through the electric heater  
is 0.12 inches (3.0 mm) of water (0.77 +  
0.12 = .89 in.) (19.6 + 3.0 = 22.6 mm).  
EnterTable PD-15 forTWE090A4 at 2500  
cfm (1180 l/s) and .90 static pressure.The  
standard motor at 790 rpm will give the  
desired airflow.  
With 2500 cfm (1180 l/s) and 1.00 inches  
(250 Pa) (0.8 kW),Table 26-1 shows a 1.07  
Bhp.  
Step 2 — Size the equipment usingTable  
PD-1. Match the cooling loads at design  
conditions.  
Note:The formula below the table can be  
used to calculate Fan Motor Heat,  
Constant x Motor Power =  
Fan Motor Heat  
Example:The following are the building  
cooling requirements  
3.5 x Bhp = MBh  
a
3.5 x 1.07  
= 3.75 MBh  
Electrical Characteristics: 380-415/50/3  
1.375 x (kW) = kW  
1.375 x 0.8 = 1.1 kW  
b
Summer Design Conditions: Entering  
Evaporator Coil: 80 DB/67WB  
(27 DB/19WB° C)  
NetTotal Cooling Capacity  
= 79.6 MBh – 3.75 = 75.85 MBh  
= 23.3 kW - 1.1 = 22.2 kW  
Net Sensible Cooling Capacity  
= 57.1 MBh – 3.75 = 53.35 MBh  
= 16.7 MBh - 1.1 = 15.6 kW  
Outdoor Ambient: 95° F (35° C)  
c
Total Cooling Load: 75 MBh (22kW)  
d
Sensible Cooling Load: 53 MBh  
(15.5 kW)  
Heating Capacity  
Step 1 — Calculate the building heating  
load using theTrane calculation form or  
any other standard accepted method.  
e
Airflow: 2500 cfm (1,180 l/s)  
External Static Pressure: 0.77 in.  
(19.6 mm) w.g. (193 Pa)  
Step 2 — Size the equipment usingTable  
PD-9 to match the heating loads at  
Table PD-1 shows that aTWA075A  
matched with aTWE075A has a gross  
cooling capacity of 82.4 MBh (24.1 kW)  
and 59.5 MBh (17.4 kW) sensible capacity  
at 95 DB (35° C) ambient and 2500 cfm  
(1180 l/s) and 80 DB/67WB (27 DB/19WB)  
air entering the evaporator.  
design conditions.The following are  
building heating requirements:  
a
Total Heating Load: 110 MBh (32.2 kW)  
b
Outdoor Ambient (Winter): 17° F  
(-8.3° C) DB  
c
To find the net cooling capacities, fan  
motor heat must be subtracted.  
Determine the total unit static pressure:  
Indoor ReturnTemperature: 70° F  
(21.1° C) DB  
d
External Static  
0.77 in  
Airflow: 2500 cfm (1180 l/s)  
Table PD-9 indicates the mechanical  
heating portion of the heat pump will  
provide 37.5 MBh (11.0 kW) for the winter  
design conditions.  
(19.6 mm) (193 Pa)  
Standard Filter  
0.10 in  
1 in. (25.4 mm)  
(2.5 mm) (25 Pa)  
Supplementary Electric Heat  
0.23 in  
Step 3 — Because 37.5 MBh (11.0 kW) is  
less than the buildings required heating  
capacity, a supplementary heater must  
be selected. 110 - 37.5 = 72.5 MBh (32.2 -  
11.0 = 21.2 kW) minimum heater capacity.  
(5.8 mm) (57 Pa)  
Total Static Pressure  
1.10 in  
FromTable PD-25, the 24.22 kW heater  
has a capacity of 82,670 Btuh. FromTable  
34-1, the 24.22 kW heater at 400V  
indicates the heater model number is  
BAYHTRL435A.This heater will be  
adequate to cover the residual heat  
capacity needed for the application.  
(27.9 mm) (275 Pa)  
Note:The Evaporator Fan Performance  
Table has included the effect of a 1 in.  
(25.4 mm) filter already.Therefore, the  
TWA-PRC001-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Number  
Description  
Split System Heat Pump Model Nomenclature  
T
W
A
0
7
5
A
D
0
0
D
A
1
2
3
4
5
6
7
8
9
10  
11  
12  
Digit 8 - Electrical Characteristics  
Digits 1, 2, 3 - ProductType  
TWA = Split System Heat Pump  
D = 380-415/3/50  
Digit 9, 10 - Factory - Installed Options  
Digits 4, 5, 6 - Nominal Gross Cooling Capacity  
(MBh)  
00 = Packed Stock  
0S = Black Epoxy Coated Coil  
075 = 75  
100 = 100  
155 = 155  
200 = 200  
Digit 11- Minor Design Sequence  
D = Fourth  
Digit 12- Service Digit  
Digit 7- Major Development Sequence  
A = First  
A = Single Compressor  
B = Dual Compressor  
Air Handler Model Nomenclature  
T
W
E
0
5
0
A
D
0
0
C
A
1
2
3
4
5
6
7
8
9
10  
11  
12  
Digit 8 - Electrical Characteristics  
Digits 1, 2, 3 - ProductType  
D = 380-415/3/50  
TWE = Cooling Convertible  
Digit 9, 10 - Factory - Installed Options  
00 = Packed Stock  
Digits 4, 5, 6 - Nominal Gross Cooling  
Capacity (MBh)  
Digit 11- Minor Design Sequence  
C = Third  
050 = 50  
075 = 75  
100 = 100  
155 = 155  
200 = 200  
Digit 12- Service Digit  
A = First  
Digit 7- Refrigerant Circuit  
A = Single  
B = Dual  
8
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(Heat Pumps)  
Table GD-1 General Data Heat Pumps  
TWA075A  
TWA100A  
Cooling Performance1  
Gross Cooling Capacity, BTUH (KW)  
Matched Air Handler, BTUH (KW)  
Heat Pump Only2, BTUH (KW)  
ARI Net Cooling Capacity3  
System Power KW  
Heat Pump Only Power KW  
Heating Performance  
ARI Heating with Matched Air Handler  
HighTemperature Capacity, BTUH (KW)  
LowTemperature Capacity, BTUH (KW)  
Compressor  
82,000 (23.97)  
109,000 (31.97)  
105,000 (30.75)  
105,000 (30.75)  
10.32  
82,000 (23.97)  
80,000 (23.35)  
7.36  
6.61  
9.22  
75,000 (21.82)  
47,000 (13.84)  
106,000 (31.05)  
69,000 (20.29)  
Number  
Type  
No. Speeds  
1
3D®Scroll  
1
1
3D®Scroll  
1
No. Motors  
1
1
Motor HP (KW)  
6.25 (4.7)  
2875  
8.8  
8.33 (6.21)  
2875  
8.8  
Motor RPM  
ARI Sound Rating (Bels)4  
System Data5  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Outdoor Coil —Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft. (m2)  
Rows  
1
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
19.2 (1.78)  
2
1
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
24.0 (2.23)  
2
Fins Per Inch (Fins per mm)  
Outdoor FanType  
No. Used  
18 (457)  
Propeller  
1
18 (457)  
Propeller  
1
Diameter, in. (mm)  
DriveType  
26.00 (660.4)  
Direct  
28.00 (711)  
Direct  
No. Speeds  
1
1
CFM6, (L/S)  
4700 (2218.2)  
1
6700 (3161.7)  
1
No. Motors  
Motor HP (KW)  
0.33 (.24)  
925  
18.0 (8.16)  
0.75 (.56)  
925  
24.25 (11.0)  
Motor RPM  
R-22 Refrigerant Charge, Lbs7 (Kg)  
Notes:  
1. Cooling Performance is rated at 95° F (35° C) ambient, 80° F (26.7° C) entering dry bulb, 67° F (19.4° C) entering wet  
bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include the  
effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for  
operation to 20% of nominal cfm. Rated accordance with ARI Standard 210.  
2. Condensing Unit Only Gross Cooling Capacity rated at 45° F (7.2° C) saturated suction temperature and at 95° F  
(35° C) ambient.  
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. (7.2 m) of 1.375, 0.500 OD interconnect-  
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated  
Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80° F (26.7° C) ambient, 80° F (26.7° C)  
entering dry bulb, and 67° F (19.4° C) entering wet bulb at ARI rated cfm.  
4. ARI Sound Rating is rated in accordance with ARI Standard 270.  
5. System Data based on maximum linear length 80 ft. (26.7 m)Maximum lift: suction 60 ft. (18.3 m) liquid 60 ft. (18.3  
m) For greater lengths, refer to refrigerant piping applications manual.  
6. Outdoor Fan Cfm is rated with standard air-dry coil outdoor.  
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. (7.6 m) of  
interconnecting refrigerant lines.  
TWA-PRC001-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(Heat Pumps)  
Table GD-2 General Data Heat Pumps  
TWA155B  
TWA200B  
Cooling Performance1  
Gross Cooling Capacity, BTUH (KW)  
Matched Air Handler, BTUH (KW)  
Condensing Unit Only2, BTUH (KW)  
ARI Net Cooling Capacity3  
166,000 (48.57)  
216,000 (63.24)  
209,000 (61.18)  
196,000 (61.18)  
20.61  
161,000 (47.04)  
160,000 (46.74)  
14.98  
System Power KW  
Condensing Unit Power KW  
13.20  
18.52  
Heating Performance  
ARI Heating with Matched Air Handler  
HighTemperature Capacity, BTUH (KW) 151,000 (44.27)  
206,000 (60.26)  
135,000 (39.66)  
LowTemperature Capacity, BTUH (KW)  
95,000 (27.67)  
Compressor  
Number  
Type  
No. Speeds  
2
3D®Scroll  
1
2
3D®Scroll  
1
No. Motors  
2
2
Motor HP  
6.25 (4.7)  
2875  
8.8  
8.33 (6.21)  
2875  
8.8  
Motor RPM, (KW)  
ARI Sound Rating (Bels)4  
System Data5  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Outdoor Coil Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft. (m2)  
Rows  
2
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
38.4 (3.57)  
2
2
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
48.0 (4.46)  
2
Fins Per Inch(mm)  
Outdoor FanType  
No. Used  
18 (457)  
Propeller/Propeller  
2
18 (457)  
Propeller/Propeller  
2
Diameter, in. (mm)  
DriveType  
26.00/26.00 (660.4/660.4)  
Direct/Direct  
1
28.00/28.00 (711/711)  
Direct/Direct  
1
13400 (6323.5)  
2
No. Speeds  
CFM6, (L/S)  
9800 (4624.6)  
2
No. Motors  
Motor HP, (KW)  
Motor RPM  
0.33 (.24)  
925  
36.0 (16.32)  
0.75 (.56)  
925  
48.5 (22.0)  
R-22 Refrigerant Charge, Lbs7 (Kg)  
Notes:  
1. Cooling Performance is rated at 95° F (35° C) ambient, 80° F (26.7° C) entering dry bulb, 67° F (19.4° C) entering  
wet bulb and nominal cfm listed. ARI rating cfm is 350 cfm/ton for this product. Gross capacity does not include  
the effect of fan motor heat. ARI capacity is net and includes the effect of fan motor heat. Units are suitable for  
operation to 20% of nominal cfm. Rated accordance with ARI Standard 210.  
2. Condensing Unit Only Gross Cooling Capacity rated at 45° F (7.6° C) saturated suction temperature and at 95° F  
(35° C) ambient.  
3. ARI Net Cooling Capacity is calculated with matched blower coil and 25 ft. (7.6 m) of 1.375, 0.500 OD interconnect-  
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated  
Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80° F (26.7° C) ambient, 80° F (26.7° C)  
entering dry bulb, and 67° F (19.4° C) entering wet bulb at ARI rated cfm.  
4. ARI Sound Rating is rated in accordance with ARI Standard 270.  
5. System Data based on maximum linear length 80 ft. (26.7 m)Maximum lift: suction 60 ft. (18.3 m) liquid 60 ft. (18.3  
m) For greater lengths, refer to refrigerant piping applications manual.  
6. Outdoor Fan Cfm is rated with standard air-dry coil outdoor.  
7. Refrigerant (operating) charge is for condensing unit (all circuits) with matching blower coils and 25 ft. (7.6 m) of  
interconnecting refrigerant lines.  
10  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(Air Handlers)  
Table GD-3 General Data Air Handlers  
TWE050A  
TWE075A  
TWE100A  
TWE100B  
System Data1  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Indoor Coil Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft. (m2)  
Rows  
1
1
1
2
1.120 (28.4)  
0.38 (9.7)  
Plate Fin  
0.375 (9.5)  
5.00 (.47)  
3
1.380 (35.0)  
0.50 (12.7)  
Plate Fin  
0.375 (9.5)  
8.07 (.75)  
3
1.380 (35.0)  
0.50 (12.7)  
Plate Fin  
0.375 (9.5)  
11.18 (1.0)  
3
1.380 (35.0)  
0.50 (12.7)  
Plate Fin  
0.375 (9.5)  
11.18 (1.0)  
3
Fins Per Inch  
12  
12  
12  
12  
Refrigerant Control  
Drain Connection No.  
ExpansionValve ExpansionValve ExpansionValve ExpansionValve  
4
4
4
4
Drain Connection Size, in. (mm) 0.75 (19.0)  
0.75 (19.0)  
PVC  
0.75 (19.0)  
PVC  
0.75 (19.0)  
PVC  
Drain ConnectionType  
Indoor FanType  
No. Used  
PVC  
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal  
1
1
15.0 (381)  
15.0 (381)  
Belt  
1
15.0 (381)  
15.0 (381)  
Belt  
1
15.0 (381)  
15.0 (381)  
Belt  
Diameter, in. (mm)  
Width, in. (mm)  
DriveType  
12.0 (304.8)  
12.0 (304.8)  
Belt  
No. Speeds  
1
1
1
1
CFM, (L/S)  
No. Motors  
1670 (788.2)  
1
2500 (1179.9)  
1
3325 (1569.2)  
1
3325 (1569.2)  
1
Motor HP, (KW)  
— Standard/Oversized  
0.75/1.0 (.55/.74) 1.0/1.5 (.74/1.11) 1.5/2.0 (1.11/1.49) 1.5/2.0 (1.11/1.49)  
Motor RPM (Standard)  
Motor Frame Size (Standard)  
Filters Type  
Furnished  
1425  
1425  
56  
Throwaway  
1425  
56  
Throwaway  
1425  
56  
Throwaway  
56  
Throwaway  
Yes  
Yes  
3
Yes  
4
Yes  
4
No.  
1/1  
Recommended Size, in. (mm) 16x20x1/20x20x1  
16x25x1  
16x25x1  
16x25x1  
406.4x508x25.  
406.4/635/25.4  
406.4/635/25.4  
406.4/635/25.4  
4/508x508x25.4  
Table GD-3 General Data Continued  
TWE155B  
TWE200B  
System Data  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Indoor Coil Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft. (m2)  
Rows  
2
2
1.38 (35.0)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
21.63 (2.01)  
3
1.38 (35.0)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
16.33 (1.52)  
3
Fins Per Inch  
12  
12  
Refrigerant Control  
Drain Connection No.  
Drain Connection Size, in. (mm)  
Drain ConnectionType  
Indoor FanType  
No. Used  
Diameter, in. (mm)  
Width, in. (mm)  
DriveType  
ExpansionValve  
ExpansionValve  
4
1.000 (25.4)  
PVC  
FC Centrifugal  
2
15.0 (381)  
15.0 (381)  
Belt  
4
1.000 (25.4)  
PVC  
FC Centrifugal  
2
15.0 (381)  
15.0 (381)  
Belt  
No. Speeds  
1
1
CFM, (L/S)  
5000 (2360.0)  
6650 (3138.4)  
No. Motors  
1
1
Motor HP, (KW)  
— Standard/Oversized  
2.0/3.0 (1.49/2.24)  
3.0/5.0 (2.24/3.72)  
Motor RPM (Standard)  
Motor Frame Size (Standard)  
Filters Type  
1425  
145T  
Throwaway  
Yes  
1425  
184T  
Throwaway  
Yes  
Furnished  
No.  
8
4/4  
Recommended Size, in. (mm)  
15x20x2  
16x20x2/16x25x2  
381x508x50.8  
406.4x508x50.8/406.4x635x50.8  
Notes:  
1. ARI certified with various condensing units per ARI Standard 210. Refer to Performance Data section in this catalog.  
TWA-PRC001-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-1 — Gross Cooling Capacities (MBh) TWA075A Heat Pump with TWE075A Air Handler  
Ambient Temperature  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
CFM  
2250  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75  
80  
85  
90  
75.7 60.5 83.8 50.3 92.4 34.1 73.2 59.2 80.9 49.1 89.1 32.9 70.2 57.7 77.5 47.8 85.3 31.6 66.7 56.0 73.6 46.2 81.1 30.2  
76.2 70.8 84.0 58.2 92.4 44.8 73.7 69.5 81.1 57.0 89.1 43.6 70.8 68.1 77.6 55.4 85.4 42.2 67.5 66.4 73.8 53.8 81.2 40.7  
78.3 78.3 84.1 68.4 92.5 55.4 76.1 76.1 81.2 67.1 89.3 54.2 73.6 73.6 77.8 65.6 85.5 52.8 70.6 70.6 74.0 63.9 81.4 51.3  
82.3 82.3 84.6 78.7 92.7 65.9 80.0 80.0 81.8 77.5 89.4 64.5 77.4 77.4 78.6 76.0 85.6 63.0 74.3 74.3 75.0 74.4 81.5 61.4  
2500  
2750  
3000  
75  
80  
85  
90  
77.2 63.4 85.3 49.5 93.9 34.7 74.6 62.1 82.3 48.2 90.5 33.6 71.4 60.5 78.8 46.8 86.6 32.2 67.8 58.8 74.8 45.2 82.2 30.6  
77.9 74.7 85.5 61.0 93.9 46.4 75.4 73.4 82.4 59.5 90.5 45.1 72.4 72.0 78.9 58.0 86.7 43.7 68.9 68.9 75.0 56.3 82.4 42.2  
80.9 80.9 85.6 72.0 94.1 57.9 78.6 78.6 82.6 70.7 90.7 56.7 75.9 75.9 79.2 69.2 86.8 55.3 72.8 72.8 75.3 67.5 82.6 53.7  
85.0 85.0 86.4 83.4 94.1 69.1 82.7 82.7 83.6 82.1 90.8 67.8 79.8 79.8 79.9 79.9 87.0 66.3 76.6 76.6 76.7 76.7 82.7 64.7  
75  
80  
85  
90  
78.5 66.1 86.5 51.2 95.1 35.3 75.7 64.8 83.4 49.9 91.6 34.1 72.5 63.2 79.8 48.4 87.6 32.7 68.9 61.5 75.8 46.8 83.1 31.1  
79.4 78.5 86.6 63.4 95.2 47.8 76.5 76.5 83.6 62.0 91.7 46.6 73.8 73.8 80.0 60.5 87.7 45.2 70.7 70.7 75.9 58.8 83.3 43.6  
83.1 83.1 86.9 75.4 95.3 60.3 80.7 80.7 83.9 74.1 91.8 59.0 77.9 77.9 80.4 72.6 87.9 57.6 74.6 74.6 76.5 70.9 83.5 55.8  
87.4 87.4 88.1 87.9 95.4 72.3 84.9 84.9 85.0 85.0 92.0 71.0 82.0 82.0 82.0 82.0 88.0 69.5 78.6 78.6 78.7 78.7 83.7 67.8  
75  
80  
85  
90  
79.5 68.8 87.6 52.8 96.1 35.8 76.8 67.4 84.4 51.5 92.5 34.5 73.5 65.9 80.7 50.0 88.4 33.1 69.8 64.1 76.6 48.4 83.9 31.5  
80.7 80.7 87.7 65.8 96.2 49.2 78.3 78.3 84.6 64.4 92.6 47.9 75.4 75.4 80.9 62.8 88.6 46.5 72.2 72.2 76.8 61.1 84.1 45.0  
85.1 85.1 88.1 78.8 96.4 62.6 82.6 82.6 85.0 77.4 92.7 61.1 79.6 79.6 81.5 75.9 88.7 59.6 76.3 76.3 77.5 74.2 84.3 58.0  
89.5 89.5 89.6 89.6 96.5 75.4 86.9 86.9 87.0 87.0 93.0 74.1 83.8 83.8 83.9 83.9 89.0 72.5 80.4 80.4 80.5 80.5 84.6 70.9  
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.  
Table PD-1 — Gross Cooling Capacities (KW) TWA075A Heat Pump withTWE075AAir Handler  
Ambient Temperature  
85  
95  
105  
67  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
61  
67  
73  
61  
67  
73  
61  
67  
73  
L/S  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
1062  
24  
27  
29  
32  
22.2 17.7 24.5 14.7 27.1 10.0 21.4 17.3 23.7 14.4 26.1 9.6 20.5 16.9 22.7 14.0 25.0 9.3 19.5 16.4 21.6 13.5 23.7 8.8  
22.3 20.7 24.6 17.0 27.1 13.1 21.6 20.4 23.7 16.7 26.1 12.8 20.7 19.9 22.7 16.2 25.0 12.4 19.8 19.5 21.6 15.7 23.8 11.9  
22.9 22.9 24.6 20.0 27.1 16.2 22.3 22.3 23.8 19.6 26.1 15.9 21.5 21.5 22.8 19.2 25.0 15.5 20.7 20.7 21.7 18.7 23.8 15.0  
24.1 24.1 24.8 23.1 27.1 19.3 23.4 23.4 23.9 22.7 26.2 18.9 22.7 22.7 23.0 22.3 25.1 18.5 21.8 21.8 22.0 21.8 23.9 18.0  
1180  
1298  
1416  
24  
27  
29  
32  
22.6 18.6 25.0 14.5 27.5 10.2 21.8 18.2 24.1 14.1 26.5 9.8 20.9 17.7 23.1 13.7 25.3 9.4 19.9 17.2 21.9 13.2 24.1 9.0  
22.8 21.9 25.0 17.9 27.5 13.6 22.1 21.5 24.1 17.4 26.5 13.2 21.2 21.1 23.1 17.0 25.4 12.8 20.2 20.2 21.9 16.5 24.1 12.4  
23.7 23.7 25.1 21.1 27.5 17.0 23.0 23.0 24.2 20.7 26.6 16.6 22.2 22.2 23.2 20.2 25.4 16.2 21.3 21.3 22.1 19.8 24.2 15.7  
24.9 24.9 25.3 24.4 27.6 20.2 24.2 24.2 24.5 24.0 26.6 19.9 23.4 23.4 23.4 23.4 25.5 19.4 22.4 22.4 22.5 22.5 24.2 18.9  
24  
27  
29  
32  
23.0 19.4 25.3 15.0 27.8 10.3 22.2 19.0 24.4 14.6 26.8 10.0 21.2 18.5 23.4 14.2 25.6 9.6 20.2 18.0 22.2 13.7 24.3 9.1  
23.3 23.0 25.4 18.5 27.9 14.0 22.4 22.4 24.5 18.2 26.8 13.6 21.6 21.6 23.4 17.7 25.7 13.2 20.7 20.7 22.2 17.2 24.4 12.8  
24.3 24.3 25.4 22.1 27.9 17.6 23.6 23.6 24.6 21.7 26.9 17.3 22.8 22.8 23.5 21.3 25.7 16.9 21.9 21.9 22.4 20.8 24.4 16.3  
25.6 25.6 25.8 25.7 27.9 21.2 24.9 24.9 24.9 24.9 26.9 20.8 24.0 24.0 24.0 24.0 25.8 20.3 23.0 23.0 23.0 23.0 24.5 19.9  
24  
27  
29  
32  
23.3 20.1 25.6 15.5 28.1 10.5 22.5 19.7 24.7 15.1 27.1 10.1 21.5 19.3 23.6 14.6 25.9 9.7 20.4 18.8 22.4 14.2 24.6 9.2  
23.6 23.6 25.7 19.3 28.2 14.4 22.9 22.9 24.8 18.9 27.1 14.0 22.1 22.1 23.7 18.4 25.9 13.6 21.1 21.1 22.5 17.9 24.6 13.2  
24.9 24.9 25.8 23.1 28.2 18.3 24.2 24.2 24.9 22.7 27.1 17.9 23.3 23.3 23.8 22.2 26.0 17.5 22.3 22.3 22.7 21.7 24.7 17.0  
26.2 26.2 26.2 26.2 28.2 22.1 25.4 25.4 25.5 25.5 27.2 21.7 24.5 24.5 24.6 24.6 26.0 21.2 23.5 23.5 23.6 23.6 24.8 20.8  
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.  
12  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-2 — Gross Cooling Capacities (MBh) TWA100A Heat Pump with TWE100AAir Handler  
Ambient Temperature  
85  
95  
105  
67  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb  
73 61  
61  
67  
73  
61  
67  
73  
61  
67  
73  
CFM  
3000  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75  
80  
85  
90  
101.6 80.9 111.8 67.1 122.7 45.2 97.7 79.0 107.6 65.4 118.1 43.6 93.6 76.9 103.2 63.6 113.2 41.9 89.4 74.8 98.6 61.7 108.2 40.1  
102.1 94.6 112.0 77.2 122.7 59.2 98.4 92.6 107.8 75.3 118.0 57.5 94.4 90.6 103.4 73.5 113.2 55.7 90.4 88.6 98.8 71.5 108.2 53.8  
104.6 104.6 112.1 90.6 122.8 72.8 101.3 101.3 107.9 88.7 118.2 71.1 97.9 97.9 103.5 86.7 113.4 69.3 94.3 94.3 98.9 84.6 108.4 67.4  
109.6 109.6 112.7 104.1 122.9 86.4 106.3 106.3 108.6 102.2 118.3 84.6 102.8 102.8 104.4 100.2 113.5 82.8 99.1 99.1 100.1 98.2 108.5 80.7  
3325  
3650  
3975  
75  
80  
85  
90  
103.4 84.5 113.7 65.6 124.6 46.0 99.4 82.5 109.4 63.8 119.8 44.4 95.2 80.5 104.8 61.9 114.8 42.7 90.9 78.3 100.1 59.9 109.6 40.8  
104.3 99.5 113.9 80.6 124.6 61.1 100.4 97.5 109.5 78.7 119.8 59.3 96.4 95.5 104.8 76.6 114.9 57.5 92.0 92.0 100.2 74.6 109.7 55.6  
107.8 107.8 114.0 95.0 124.7 75.9 104.4 104.4 109.6 93.1 120.0 74.1 100.8 100.8 105.2 91.1 115.0 72.3 97.0 97.0 100.6 89.0 109.9 70.4  
113.0 113.0 114.9 109.8 124.8 90.6 109.5 109.5 110.8 107.9 120.0 88.6 105.8 105.8 106.5 105.9 115.1 86.7 102.0 102.0 101.9 101.9 110.0 84.7  
75  
80  
85  
90  
105.0 88.0 115.3 67.7 126.1 46.8 100.9 85.9 110.8 65.8 121.2 45.0 96.6 83.9 106.1 63.9 116.1 43.2 92.2 81.7 101.3 62.0 110.8 41.3  
106.2 104.2 115.4 83.8 126.1 62.8 102.3 102.3 110.9 81.7 121.3 61.1 98.0 98.0 106.2 79.7 116.2 59.2 94.3 94.3 101.4 77.6 111.0 57.4  
110.6 110.6 115.6 99.3 126.3 78.8 107.0 107.0 111.2 97.3 121.4 77.0 103.3 103.3 106.7 95.3 116.4 75.2 99.4 99.4 102.0 93.3 111.1 73.3  
115.9 115.9 117.0 115.4 126.3 94.4 112.3 112.3 112.2 112.2 121.5 92.5 108.4 108.4 108.4 108.4 116.5 90.5 104.5 104.5 104.4 104.4 111.3 88.5  
75  
80  
85  
90  
106.3 91.3 116.6 69.7 127.5 47.4 102.2 89.3 112.0 67.8 122.4 45.6 97.9 87.2 107.3 65.9 117.2 43.7 93.4 85.0 102.4 63.9 111.8 41.9  
107.4 107.4 116.7 86.6 127.5 64.5 103.9 103.9 112.1 84.7 122.5 62.7 100.1 100.1 107.4 82.6 117.3 60.9 96.2 96.2 102.5 80.5 112.0 59.0  
113.0 113.0 117.1 103.4 127.6 81.6 109.3 109.3 112.7 101.5 122.7 79.8 105.5 105.5 108.1 99.4 117.5 78.0 101.5 101.5 103.3 97.4 112.2 76.1  
118.5 118.5 118.4 118.4 127.7 98.2 114.8 114.8 114.7 114.7 122.8 96.3 110.8 110.8 110.7 110.7 117.6 94.3 106.6 106.6 106.6 106.6 112.4 92.3  
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.  
Table PD-2 — Gross Cooling Capacities (KW) TWA100A Heat Pump with TWE100A Air Handler  
Ambient Temperature  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
L/S  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
1416  
24  
27  
29  
32  
29.7 23.7 32.7 19.7 35.9 13.2 28.6 23.1 31.5 19.1 34.6 12.8 27.4 22.5 30.2 18.6 33.1 12.3 26.2 21.9 28.9 18.1 31.7 11.8  
29.9 27.7 32.8 22.6 35.9 17.3 28.8 27.1 31.6 22.1 34.6 16.8 27.6 26.5 30.3 21.5 33.2 16.3 26.5 25.9 28.9 20.9 31.7 15.8  
30.6 30.6 32.8 26.5 35.9 21.3 29.7 29.7 31.6 26.0 34.6 20.8 28.7 28.7 30.3 25.4 33.2 20.3 27.6 27.6 29.0 24.8 31.7 19.7  
32.1 32.1 33.0 30.5 36.0 25.3 31.1 31.1 31.8 29.9 34.6 24.8 30.1 30.1 30.6 29.3 33.2 24.2 29.0 29.0 29.3 28.8 31.8 23.6  
1569  
1723  
1876  
24  
27  
29  
32  
30.3 24.7 33.3 19.2 36.5 13.5 29.1 24.2 32.0 18.7 35.1 13.0 27.9 23.6 30.7 18.1 33.6 12.5 26.6 22.9 29.3 17.5 32.1 11.9  
30.5 29.1 33.3 23.6 36.5 17.9 29.4 28.6 32.1 23.0 35.1 17.4 28.2 28.0 30.7 22.4 33.6 16.8 26.9 26.9 29.3 21.8 32.1 16.3  
31.6 31.6 33.4 27.8 36.5 22.2 30.6 30.6 32.1 27.2 35.1 21.7 29.5 29.5 30.8 26.7 33.7 21.2 28.4 28.4 29.4 26.1 32.2 20.6  
33.1 33.1 33.6 32.2 36.5 26.5 32.1 32.1 32.4 31.6 35.1 25.9 31.0 31.0 31.2 31.0 33.7 25.4 29.9 29.9 29.8 29.8 32.2 24.8  
24  
27  
29  
32  
30.7 25.8 33.8 19.8 36.9 13.7 29.5 25.2 32.4 19.3 35.5 13.2 28.3 24.6 31.1 18.7 34.0 12.7 27.0 23.9 29.7 18.1 32.5 12.1  
31.1 30.5 33.8 24.5 36.9 18.4 30.0 29.9 32.5 23.9 35.5 17.9 28.7 28.7 31.1 23.3 34.0 17.3 27.6 27.6 29.7 22.7 32.5 16.8  
32.4 32.4 33.8 29.1 37.0 23.1 31.3 31.3 32.6 28.5 35.6 22.6 30.2 30.2 31.2 27.9 34.1 22.0 29.1 29.1 29.9 27.3 32.5 21.5  
33.9 33.9 34.3 33.8 37.0 27.6 32.9 32.9 32.8 32.8 35.6 27.1 31.8 31.8 31.7 31.7 34.1 26.5 30.6 30.6 30.6 30.6 32.6 25.9  
24  
27  
29  
32  
31.1 26.7 34.1 20.4 37.3 13.9 29.9 26.1 32.8 19.9 35.9 13.3 28.7 25.5 31.4 19.3 34.3 12.8 27.3 24.9 30.0 18.7 32.7 12.3  
31.5 31.5 34.2 25.4 37.3 18.9 30.4 30.4 32.8 24.8 35.9 18.4 29.3 29.3 31.4 24.2 34.4 17.8 28.2 28.2 30.0 23.6 32.8 17.3  
33.1 33.1 34.3 30.3 37.4 23.9 32.0 32.0 33.0 29.7 35.9 23.4 30.9 30.9 31.6 29.1 34.4 22.8 29.7 29.7 30.3 28.5 32.9 22.3  
34.7 34.7 34.7 34.7 37.4 28.8 33.6 33.6 33.6 33.6 35.9 28.2 32.4 32.4 32.4 32.4 34.4 27.6 31.2 31.2 31.2 31.2 32.9 27.0  
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.  
TWA-PRC001-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-3 — Gross Cooling Capacities (MBh) TWA155A Heat Pump with TWE155AAir Handler  
Ambient Temperature  
85  
95  
105  
67  
115  
Enter.  
Dry  
EnteringWet Bulb  
73 61  
CFM  
4500  
Bulb  
61  
67  
73  
61  
67  
73  
61  
67  
73  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75 152.8 121.6169.0 101.2 186.3 68.7 147.6 119.0 163.1 98.8 179.6 66.4 141.5 116.0 156.2 96.0 171.9 63.7 134.4 112.5 148.4 92.9 163.4 60.8  
80  
85  
90  
153.5 142.2 169.3 117.1 186.4 90.4 148.5 139.6 163.5 114.7 179.7 87.9 142.6 136.6 156.4 111.4 172.1 85.0 135.8 133.3 148.7 108.0 163.7 82.0  
157.6 157.6 169.5 137.4 186.6 111.5 153.3 153.3 163.7 134.8 180.0 109.0 148.1 148.1 156.9 131.8 172.5 106.2 142.1 142.1 149.2 128.4 164.1 103.1  
165.7 165.7 170.4 158.1 186.8 132.2 161.1 161.1 164.8 155.5 180.2 129.6 155.7 155.7 158.2 152.6 172.7 126.6 149.6 149.6 150.9 149.3 164.3 123.4  
5000  
5500  
6000  
75  
80  
85  
90  
155.8 127.4 172.1 99.7 189.4 70.0 150.4 124.7 166.0 97.1 182.4 67.6 144.0 121.6 158.8 94.2 174.5 64.9 136.7 118.1 150.8 90.9 165.7 61.8  
156.9 150.0 172.2 122.3 189.5 93.4 151.8 147.5 166.1 119.7 182.6 90.9 145.7 144.4 159.1 116.6 174.7 88.1 138.7 138.7 151.1 113.1 166.0 84.9  
162.9 162.9 172.7 144.6 189.8 116.5 158.3 158.3 166.6 141.9 182.9 114.0 152.8 152.8 159.6 138.9 175.1 111.2 146.5 146.5 151.8 135.5 166.5 108.0  
171.3 171.3 174.1 167.4 189.9 138.9 166.4 166.4 168.3 164.8 183.1 136.2 160.7 160.7 160.9 160.9 175.4 133.2 154.3 154.3 154.4 154.4 166.8 129.9  
75  
80  
85  
90  
158.3 132.9 174.6 103.0 191.8 71.3 152.8 130.2 168.3 100.5 184.7 68.7 146.2 127.0 161.0 97.5 176.5 65.9 138.8 123.5 152.7 94.2 167.5 62.7  
160.1 157.7 174.8 127.4 192.0 96.3 154.1 154.1 168.6 124.6 184.9 93.8 148.6 148.6 161.3 121.5 176.9 90.9 142.3 142.3 153.1 118.0 168.0 87.8  
167.4 167.4 175.3 151.5 192.3 121.3 162.6 162.6 169.2 148.8 185.3 118.8 156.8 156.8 162.0 145.7 177.1 115.4 150.3 150.3 154.0 142.3 168.3 112.1  
176.1 176.1 177.5 176.4 192.6 145.3 171.0 171.0 171.2 171.2 185.6 142.6 165.0 165.0 165.2 165.2 177.6 139.6 158.3 158.3 158.5 158.5 168.9 136.2  
75  
80  
85  
90  
160.5 138.2 176.8 106.3 193.9 72.2 154.8 135.5 170.3 103.7 186.6 69.6 148.1 132.3 162.8 100.7 178.3 66.7 140.6 128.7 154.4 97.4 169.1 63.6  
162.6 162.5 177.0 132.2 194.1 99.1 157.7 157.7 170.6 129.4 186.9 96.5 151.9 151.9 163.2 126.3 178.7 93.7 145.4 145.4 154.8 122.7 169.7 90.5  
171.5 171.5 177.7 158.2 194.3 125.6 166.4 166.4 171.4 155.5 187.1 122.9 160.4 160.4 164.1 152.4 179.0 119.8 153.6 153.6 156.1 148.9 170.1 116.4  
180.4 180.4 180.6 180.6 194.8 151.5 175.1 175.1 175.2 175.2 187.6 148.8 168.9 168.9 169.0 169.0 179.5 145.7 161.9 161.9 162.1 162.1 170.6 142.3  
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.  
Table PD-3 — Gross Cooling Capacities (KW) TWA155A Heat Pump withTWE155AAir Handler  
Ambient Temperature  
85  
95  
105  
67  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
61  
67  
73  
61  
67  
73  
61  
67  
73  
L/S  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
2124  
24  
27  
29  
32  
44.7 35.6 49.5 29.6 54.6 20.1 43.2 34.8 47.8 28.9 52.6 19.4 41.4 34.0 45.7 28.1 50.3 18.7 39.4 32.9 43.5 27.2 47.8 17.8  
44.9 41.6 49.6 34.3 54.6 26.5 43.5 40.9 47.9 33.6 52.6 25.7 41.7 40.0 45.8 32.6 50.4 24.9 39.8 39.0 43.5 31.6 47.9 24.0  
46.1 46.1 49.6 40.2 54.6 32.6 44.9 44.9 47.9 39.5 52.7 31.9 43.4 43.4 45.9 38.6 50.5 31.1 41.6 41.6 43.7 37.6 48.0 30.2  
48.5 48.5 49.9 46.3 54.7 38.7 47.2 47.2 48.2 45.5 52.8 37.9 45.6 45.6 46.3 44.7 50.6 37.1 43.8 43.8 44.2 43.7 48.1 36.1  
2360  
2596  
2832  
24  
27  
29  
32  
45.6 37.3 50.4 29.2 55.4 20.5 44.0 36.5 48.6 28.4 53.4 19.8 42.2 35.6 46.5 27.6 51.1 19.0 40.0 34.6 44.2 26.6 48.5 18.1  
46.0 43.9 50.4 35.8 55.5 27.4 44.4 43.2 48.6 35.0 53.5 26.6 42.7 42.3 46.6 34.1 51.2 25.8 40.6 40.6 44.2 33.1 48.6 24.9  
47.7 47.7 50.6 42.3 55.6 34.1 46.3 46.3 48.8 41.6 53.6 33.4 44.7 44.7 46.7 40.7 51.3 32.5 42.9 42.9 44.4 39.7 48.7 31.6  
50.1 50.1 51.0 49.0 55.6 40.7 48.7 48.7 49.3 48.3 53.6 39.9 47.1 47.1 47.1 47.1 51.3 39.0 45.2 45.2 45.2 45.2 48.8 38.0  
24  
27  
29  
32  
46.4 38.9 51.1 30.2 56.2 20.9 44.7 38.1 49.3 29.4 54.1 20.1 42.8 37.2 47.1 28.6 51.7 19.3 40.6 36.2 44.7 27.6 49.0 18.4  
46.9 46.2 51.2 37.3 56.2 28.2 45.1 45.1 49.4 36.5 54.1 27.5 43.5 43.5 47.2 35.6 51.8 26.6 41.7 41.7 44.8 34.6 49.2 25.7  
49.0 49.0 51.3 44.4 56.3 35.5 47.6 47.6 49.5 43.6 54.3 34.8 45.9 45.9 47.4 42.7 51.8 33.8 44.0 44.0 45.1 41.7 49.3 32.8  
51.6 51.6 52.0 51.7 56.4 42.6 50.1 50.1 50.1 50.1 54.3 41.8 48.3 48.3 48.4 48.4 52.0 40.9 46.4 46.4 46.4 46.4 49.4 39.9  
24  
27  
29  
32  
47.0 40.5 51.8 31.1 56.8 21.1 45.3 39.7 49.9 30.4 54.6 20.4 43.4 38.7 47.7 29.5 52.2 19.5 41.2 37.7 45.2 28.5 49.5 18.6  
47.6 47.6 51.8 38.7 56.8 29.0 46.2 46.2 50.0 37.9 54.7 28.3 44.5 44.5 47.8 37.0 52.3 27.4 42.6 42.6 45.3 35.9 49.7 26.5  
50.2 50.2 52.0 46.3 56.9 36.8 48.7 48.7 50.2 45.5 54.8 36.0 47.0 47.0 48.1 44.6 52.4 35.1 45.0 45.0 45.7 43.6 49.8 34.1  
52.8 52.8 52.9 52.9 57.0 44.4 51.3 51.3 51.3 51.3 54.9 43.6 49.4 49.4 49.5 49.5 52.6 42.7 47.4 47.4 47.5 47.5 50.0 41.7  
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.  
14  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-4 — Gross Cooling Capacities (MBh) TWA200A Heat Pump with TWE200AAir Handler  
Ambient Temperature  
85  
95  
105  
67  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb  
73 61  
61  
67  
73  
61  
67  
73  
61  
67  
73  
CFM  
6000  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75 200.7 159.3220.9132.5242.6 89.4 192.9 155.4212.4129.1233.3 86.1 184.8151.3203.6125.5223.6 82.8 176.4 147.1 194.5 121.8213.6 79.3  
80  
85  
90  
201.5 186.0 221.2 152.1 242.5 117.0 194.0 182.1 212.8 148.5 233.3 113.4 186.2 178.1 204.0 144.7 223.7 109.8 178.1 174.0 194.7 140.4 213.8 106.2  
206.2 206.2 221.4 178.3 242.8 143.7 199.7 199.7 213.0 174.4 233.6 140.2 192.9 192.9 204.3 170.5 224.0 136.5 185.8 185.8 195.2 166.4 214.1 132.8  
216.2 216.2 222.3 204.7 243.0 170.3 209.5 209.5 214.2 200.8 233.8 166.8 202.5 202.5 205.8 196.9 224.1 162.6 195.2 195.2 197.2 193.0 214.3 158.7  
6675  
7350  
8025  
75  
80  
85  
90  
204.4 166.6 224.8 129.6 246.5 91.1 196.4 162.6 216.1 125.9 236.9 87.8 188.1 158.5 207.0 122.1 226.9 84.3 179.4 154.2 197.6 118.3 216.6 80.6  
205.8 195.9 225.1 159.0 246.5 120.7 198.1 192.0 216.2 154.9 236.9 117.2 190.2 188.0 207.2 151.0 227.1 113.6 181.5 181.5 197.9 146.9 216.8 109.8  
212.7 212.7 225.3 187.3 246.7 149.9 205.9 205.9 216.7 183.3 237.2 146.3 198.8 198.8 207.7 179.3 227.4 142.7 191.4 191.4 198.6 175.3 217.2 138.9  
223.1 223.1 226.9 216.3 246.8 178.4 216.1 216.1 218.7 212.4 237.3 174.6 208.8 208.8 210.2 208.5 227.6 170.8 201.2 201.2 201.0 201.0 217.4 166.8  
75  
80  
85  
90  
207.6 173.6 228.0 133.8 249.6 92.7 199.4 169.5 219.1 130.1 239.8 89.1 190.8 165.4 209.8 126.3 229.6 85.5 182.1 161.1 200.2 122.4 219.1 81.8  
209.7 205.5 228.1 165.1 249.7 124.3 202.0 201.6 219.3 161.2 239.9 120.8 193.6 193.6 210.0 157.2 229.8 117.1 186.1 186.1 200.5 153.0 219.4 113.4  
218.4 218.4 228.6 195.9 250.0 155.8 211.3 211.3 219.9 192.0 240.3 152.2 203.9 203.9 210.8 187.9 230.2 148.5 196.2 196.2 201.5 183.8 219.8 144.8  
229.1 229.1 231.1 227.5 250.1 186.4 221.9 221.9 221.7 221.7 240.4 182.5 214.3 214.3 214.1 214.1 230.4 178.6 206.3 206.3 206.2 206.2 220.0 174.6  
75  
80  
85  
90  
210.3 180.3 230.8 137.8 252.3 93.8 202.0 176.2 221.6 134.1 242.3 90.3 193.3 172.0 212.1 130.3 231.9 86.6 184.4 167.7 202.4 126.4 221.1 82.8  
212.4 212.4 231.0 171.2 252.4 127.7 205.3 205.3 221.9 167.2 242.5 124.2 197.8 197.8 212.5 163.1 232.1 120.5 190.1 190.1 202.8 159.0 221.5 116.7  
223.4 223.4 231.6 204.3 252.7 161.5 216.1 216.1 222.8 200.3 242.8 157.9 208.4 208.4 213.6 196.2 232.3 153.7 200.5 200.5 204.1 192.1 221.7 149.7  
234.5 234.5 234.3 234.3 252.9 194.0 227.0 227.0 226.8 226.8 243.1 190.1 219.0 219.0 218.9 218.9 232.8 186.2 210.8 210.8 210.7 210.7 222.2 182.1  
Note: All temperatures are in degrees Fahrenheit. Airflow is in cfm.  
Table PD-4 — Gross Cooling Capacities (KW)TWA200A Heat Pump withTWE200AAir Handler  
AmbientTemperature  
85  
95  
105  
67  
115  
Enter.  
Dry  
Bulb  
EnteringWet Bulb  
73 61  
61  
67  
73  
61  
67  
73  
61  
67  
73  
L/S  
ID  
Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
2832  
24  
27  
29  
32  
58.8 46.7 64.7 38.8 71.0 26.2 56.5 45.5 62.2 37.8 68.3 25.2 54.1 44.3 59.6 36.7 65.5 24.2 51.6 43.1 57.0 35.7 62.5 23.2  
59.0 54.5 64.8 44.5 71.0 34.2 56.8 53.3 62.3 43.5 68.3 33.2 54.5 52.1 59.7 42.4 65.5 32.2 52.1 50.9 57.0 41.1 62.6 31.1  
60.4 60.4 64.8 52.2 71.1 42.1 58.5 58.5 62.4 51.1 68.4 41.0 56.5 56.5 59.8 49.9 65.6 40.0 54.4 54.4 57.2 48.7 62.7 38.9  
63.3 63.3 65.1 59.9 71.2 49.9 61.3 61.3 62.7 58.8 68.5 48.8 59.3 59.3 60.3 57.7 65.6 47.6 57.2 57.2 57.7 56.5 62.7 46.5  
3150  
3469  
3787  
24  
27  
29  
32  
59.9 48.8 65.8 37.9 72.2 26.7 57.5 47.6 63.3 36.9 69.4 25.7 55.1 46.4 60.6 35.8 66.4 24.7 52.5 45.2 57.9 34.6 63.4 23.6  
60.3 57.4 65.9 46.6 72.2 35.4 58.0 56.2 63.3 45.4 69.4 34.3 55.7 55.0 60.7 44.2 66.5 33.3 53.1 53.1 57.9 43.0 63.5 32.2  
62.3 62.3 66.0 54.8 72.2 43.9 60.3 60.3 63.4 53.7 69.5 42.8 58.2 58.2 60.8 52.5 66.6 41.8 56.0 56.0 58.1 51.3 63.6 40.7  
65.3 65.3 66.4 63.3 72.2 52.2 63.3 63.3 64.0 62.2 69.5 51.1 61.1 61.1 61.6 61.1 66.6 50.0 58.9 58.9 58.9 58.9 63.7 48.8  
24  
27  
29  
32  
60.8 50.8 66.8 39.2 73.1 27.1 58.4 49.6 64.1 38.1 70.2 26.1 55.9 48.4 61.4 37.0 67.2 25.0 53.3 47.2 58.6 35.8 64.1 23.9  
61.4 60.2 66.8 48.3 73.1 36.4 59.1 59.0 64.2 47.2 70.3 35.4 56.7 56.7 61.5 46.0 67.3 34.3 54.5 54.5 58.7 44.8 64.2 33.2  
64.0 64.0 66.9 57.4 73.2 45.6 61.9 61.9 64.4 56.2 70.3 44.6 59.7 59.7 61.7 55.0 67.4 43.5 57.5 57.5 59.0 53.8 64.4 42.4  
67.1 67.1 67.7 66.6 73.2 54.6 65.0 65.0 64.9 64.9 70.4 53.4 62.7 62.7 62.7 62.7 67.5 52.3 60.4 60.4 60.4 60.4 64.4 51.1  
24  
27  
29  
32  
61.6 52.8 67.6 40.4 73.9 27.5 59.1 51.6 64.9 39.3 70.9 26.4 56.6 50.4 62.1 38.2 67.9 25.4 54.0 49.1 59.3 37.0 64.7 24.3  
62.2 62.2 67.6 50.1 73.9 37.4 60.1 60.1 65.0 49.0 71.0 36.4 57.9 57.9 62.2 47.8 68.0 35.3 55.7 55.7 59.4 46.5 64.9 34.2  
65.4 65.4 67.8 59.8 74.0 47.3 63.3 63.3 65.2 58.6 71.1 46.2 61.0 61.0 62.5 57.5 68.0 45.0 58.7 58.7 59.8 56.3 64.9 43.8  
68.7 68.7 68.6 68.6 74.1 56.8 66.5 66.5 66.4 66.4 71.2 55.7 64.1 64.1 64.1 64.1 68.2 54.5 61.7 61.7 61.7 61.7 65.1 53.3  
Note: All temperatures are in degrees Celsius. Airflow is in liters per second.  
TWA-PRC001-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(TWA075A)  
Table PD-5 Gross Cooling Performance (MBh) TWA075A Heat Pump Only  
ODTemp  
Suction ReferenceTemperature °F  
°F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
165  
70.0  
4.58  
191  
170  
77.4  
4.67  
197  
176  
85.1  
4.78  
203  
182  
93.1  
4.89  
209  
188  
101.3  
5.02  
215  
195  
109.6  
5.14  
222  
65  
75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
68.2  
5.04  
75.2  
5.15  
82.5  
5.27  
90.1  
5.39  
97.8  
105.6  
5.65  
5.52  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
219  
225  
72.3  
5.71  
231  
79.2  
5.84  
238  
86.4  
5.97  
245  
93.6  
6.10  
252  
101.1  
6.24  
85  
95  
65.5  
5.59  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
250  
62.3  
6.22  
256  
68.7  
6.35  
263  
75.3  
6.48  
270  
82.0  
6.61  
277  
88.9  
6.74  
284  
95.9  
6.88  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
283  
58.6  
6.93  
289  
64.6  
7.06  
296  
70.8  
7.18  
304  
77.1  
7.31  
311  
83.7  
7.45  
319  
90.3  
7.59  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
318  
54.4  
7.72  
325  
60.0  
7.83  
332  
65.8  
7.95  
340  
71.8  
8.08  
347  
78.0  
8.22  
355  
84.4  
8.36  
Table PD-5 Gross Cooling Performance (KW) TWA075A Heat Pump Only  
ODTemp  
Suction ReferenceTemperature °C  
°C  
-1.1  
1.7  
4.4  
7.2  
10  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1136  
20.5  
1173  
22.6  
1213  
24.9  
1255  
27.2  
1298  
29.7  
1343  
32.1  
18.3  
23.9  
29.4  
35.0  
40.6  
OD Unit Power (kW)  
4.58  
4.67  
4.78  
4.89  
5.02  
5.14  
Head pressure (kPA)  
Capacity (kW)  
1315  
20.0  
5.04  
1355  
22.0  
5.15  
1397  
24.2  
5.27  
1440  
26.4  
5.39  
1484  
28.6  
5.52  
1531  
30.9  
5.65  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1509  
19.2  
5.59  
1552  
21.2  
5.71  
1596  
23.2  
5.84  
1642  
25.3  
5.97  
1689  
27.4  
1738  
29.6  
6.24  
OD Unit Power (kW)  
6.10  
Head pressure (kPA)  
Capacity (kW)  
1721  
18.3  
6.22  
1766  
20.1  
6.35  
1812  
22.0  
6.48  
1860  
24.0  
6.61  
1909  
26.0  
6.74  
1959  
28.1  
6.88  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1948  
17.2  
1995  
18.9  
7.06  
2043  
20.7  
7.18  
2093  
22.6  
7.31  
2144  
24.5  
7.45  
2197  
26.5  
7.59  
OD Unit Power (kW)  
6.93  
Head pressure (kPA)  
Capacity (kW)  
2192  
15.9  
7.72  
2240  
17.6  
7.83  
2290  
19.3  
7.95  
2341  
21.0  
8.08  
2395  
22.8  
8.22  
2450  
24.7  
8.36  
46.1  
48.9  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2320  
15.3  
8.13  
2369  
16.9  
8.24  
2419  
18.5  
8.36  
2471  
20.2  
8.49  
2526  
22.0  
8.62  
2583  
23.8  
8.76  
16  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(TWA100A)  
Table PD-6— Gross Cooling Performance (MBh) TWA100A Heat Pump Only  
ODTemp  
Suction ReferenceTemperature °F  
°F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
175  
94.8  
6.26  
181  
104.0  
6.41  
187  
113.6  
6.57  
194  
123.5  
6.74  
201  
133.7  
6.93  
208  
144.2  
7.12  
65  
Head press PSIG  
200  
207  
213  
220  
227  
235  
75  
85  
Cap. Btuh/1000  
OD Unit KW  
90.4  
6.92  
99.1  
7.08  
108.1  
7.25  
117.5  
7.44  
127.3  
7.64  
137.3  
7.85  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
229  
85.7  
7.70  
235  
93.9  
7.88  
242  
102.5  
8.07  
250  
111.5  
8.27  
257  
120.8  
8.49  
265  
130.4  
8.71  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
259  
80.7  
8.60  
266  
88.6  
8.79  
274  
96.8  
9.00  
282  
105.4  
9.22  
290  
114.2  
9.44  
298  
123.3  
9.67  
95  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
293  
75.5  
9.60  
300  
83.0  
9.82  
308  
91.0  
10.05  
316  
99.2  
10.28  
325  
107.6  
10.51  
334  
116.2  
10.74  
105  
115  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
328  
70.0  
10.72  
337  
77.4  
10.96  
345  
85.0  
11.21  
354  
92.9  
11.45  
363  
100.9  
11.69  
372  
109.0  
11.92  
Table PD-6 Gross Cooling Performance (MBh) TWA100A Heat Pump Only  
ODTemp  
Suction ReferenceTemperature °F  
°C  
-1.1  
1.7  
4.4  
7.2  
10  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1206  
27.7  
1247  
30.4  
6.41  
1290  
33.3  
6.57  
1336  
36.2  
6.74  
1383  
39.2  
6.93  
1432  
42.2  
7.12  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
6.26  
Head pressure (kPA)  
Capacity (kW)  
1382  
26.5  
6.92  
1425  
29.0  
7.08  
1470  
31.7  
7.25  
1518  
34.4  
7.44  
1568  
37.3  
7.64  
1621  
40.2  
7.85  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1576  
25.1  
7.70  
1622  
27.5  
7.88  
1670  
30.0  
8.07  
1721  
32.7  
8.27  
1774  
35.4  
8.49  
1829  
38.2  
8.71  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1788  
23.6  
8.60  
1837  
25.9  
8.79  
1888  
28.3  
9.00  
1941  
30.9  
9.22  
1997  
33.5  
9.44  
2055  
36.1  
9.67  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
2017  
22.1  
9.60  
2069  
24.3  
9.82  
2124  
26.6  
2181  
29.0  
2240  
31.5  
2300  
34.0  
OD Unit Power (kW)  
10.05  
10.28  
10.51  
10.74  
Head pressure (kPA)  
Capacity (kW)  
2265  
20.5  
2321  
22.7  
2379  
24.9  
2440  
27.2  
2502  
29.5  
2565  
31.9  
OD Unit Power (kW)  
10.72  
10.96  
11.21  
11.45  
11.69  
11.92  
TWA-PRC001-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(TWA155A)  
Table PD-7 Gross Cooling Performance (MBh) TWA155A Heat Pump Only  
ODTemp  
Suction Reference Temperature °F  
°F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
165  
137.2  
9.13  
170  
151.6  
9.33  
176  
166.8  
9.54  
182  
182.4  
9.77  
188  
195  
65  
75  
198.5  
10.02  
214.9  
10.27  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
191  
197  
203  
209  
215  
191.6  
11.02  
222  
207.0  
11.29  
133.6  
10.06  
147.5  
10.29  
161.8  
10.52  
176.6  
10.77  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
219  
128.5  
11.16  
225  
141.7  
11.40  
232  
155.4  
11.65  
238  
169.3  
11.91  
245  
252  
85  
183.6  
12.18  
198.1  
12.46  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
250  
256  
263  
147.6  
12.94  
270  
277  
284  
95  
122.2  
12.43  
134.7  
12.68  
160.8  
13.20  
174.3  
13.47  
188.1  
13.75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
283  
114.9  
13.85  
289  
296  
304  
311  
319  
105  
115  
126.7  
14.10  
138.8  
14.35  
151.2  
14.61  
164.0  
14.89  
177.1  
15.17  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
318  
325  
117.7  
15.65  
332  
340  
347  
355  
106.7  
15.41  
129.1  
15.89  
140.8  
16.15  
152.9  
16.42  
165.4  
16.70  
Table PD-7 Gross Cooling Performance (KW) TWA155A Heat Pump Only  
ODTemp  
Suction Reference Temperature °C  
°C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1136  
40.2  
9.13  
1174  
44.4  
9.33  
1213  
48.8  
9.54  
1255  
53.4  
9.77  
1299  
58.1  
1343  
62.9  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
10.02  
10.27  
Head pressure (kPA)  
Capacity (kW)  
1315  
39.1  
1355  
43.2  
1397  
47.4  
1440  
51.7  
1485  
56.1  
1532  
60.6  
OD Unit Power (kW)  
10.06  
10.29  
10.52  
10.77  
11.02  
11.29  
Head pressure (kPA)  
Capacity (kW)  
1510  
37.6  
1552  
41.5  
1597  
45.5  
1642  
49.6  
1690  
53.8  
1738  
58.0  
OD Unit Power (kW)  
11.16  
11.40  
11.65  
11.91  
12.18  
12.46  
Head pressure (kPA)  
Capacity (kW)  
1722  
35.8  
1767  
39.5  
1813  
43.2  
1860  
47.1  
1909  
51.0  
1960  
55.1  
OD Unit Power (kW)  
12.43  
12.68  
12.94  
13.20  
13.47  
13.75  
Head pressure (kPA)  
Capacity (kW)  
1949  
33.6  
1996  
37.1  
2044  
40.6  
2093  
44.3  
2145  
48.0  
2197  
51.9  
OD Unit Power (kW)  
13.85  
14.10  
14.35  
14.61  
14.89  
15.17  
Head pressure (kPA)  
Capacity (kW)  
2192  
31.2  
2241  
34.5  
2291  
37.8  
2342  
41.2  
2395  
44.8  
2451  
48.4  
OD Unit Power (kW)  
15.41  
15.65  
15.89  
16.15  
16.42  
16.70  
18  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(TWA200A)  
Table PD-8 Gross Cooling Performance (MBh) TWA200A Heat Pump Only  
OD Temp  
Suction Reference Temperature °F  
° F  
30  
35  
40  
45  
50  
55  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
177  
187.4  
12.50  
183  
189  
196  
203  
210  
65  
75  
205.7  
12.81  
224.7  
13.14  
244.4  
13.49  
264.7  
13.86  
285.6  
14.25  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
203  
209  
216  
223  
230  
238  
178.8  
13.84  
196.0  
14.17  
213.9  
14.53  
232.6  
14.91  
252.1  
15.32  
272.1  
15.75  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
231  
238  
245  
253  
260  
269  
85  
169.4  
15.42  
185.8  
15.79  
203.0  
16.18  
220.8  
16.60  
239.3  
17.04  
258.4  
17.49  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
262  
159.6  
17.24  
269  
175.3  
17.65  
277  
191.7  
18.08  
285  
293  
302  
95  
208.8  
18.52  
226.4  
18.98  
244.5  
19.44  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
296  
304  
164.3  
19.74  
312  
320  
329  
338  
105  
115  
149.2  
19.29  
180.1  
20.20  
196.5  
20.68  
213.4  
21.15  
230.6  
21.62  
Head press PSIG  
Cap. Btuh/1000  
OD Unit KW  
332  
340  
349  
358  
367  
377  
138.5  
21.55  
153.1  
22.05  
168.4  
22.55  
184.1  
23.05  
200.2  
23.54  
216.5  
24.01  
Table PD-8 — Gross Cooling Performance (KW) TWA200A Heat Pump Only  
ODTemp  
Suction ReferenceTemperature °C  
°C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1219  
54.9  
1261  
60.2  
1305  
65.8  
1351  
71.5  
1399  
77.5  
1449  
83.6  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
12.50  
12.81  
13.14  
13.49  
13.86  
14.25  
Head pressure (kPA)  
Capacity (kW)  
1397  
52.3  
1441  
57.4  
1487  
62.6  
1536  
68.1  
1588  
73.8  
1642  
79.7  
OD Unit Power (kW)  
13.84  
14.17  
14.53  
14.91  
15.32  
15.75  
Head pressure (kPA)  
Capacity (kW)  
1593  
49.6  
1640  
54.4  
1689  
59.4  
1741  
64.7  
1796  
70.1  
1852  
75.7  
OD Unit Power (kW)  
15.42  
15.79  
16.18  
16.60  
17.04  
17.49  
Head pressure (kPA)  
Capacity (kW)  
1808  
46.7  
1857  
51.3  
1910  
56.1  
1965  
61.1  
2022  
66.3  
2081  
71.6  
OD Unit Power (kW)  
17.24  
17.65  
18.08  
18.52  
18.98  
19.44  
Head pressure (kPA)  
Capacity (kW)  
2040  
43.7  
2093  
48.1  
2149  
52.7  
2207  
57.5  
2268  
62.5  
2329  
67.5  
OD Unit Power (kW)  
19.29  
19.74  
20.20  
20.68  
21.15  
21.62  
Head pressure (kPA)  
Capacity (kW)  
2290  
40.5  
2348  
44.8  
2408  
49.3  
2470  
53.9  
2533  
58.6  
2597  
63.4  
OD Unit Power (kW)  
21.55  
22.05  
22.55  
23.05  
23.54  
24.01  
TWA-PRC001-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-9 — Gross Heating Capacities (MBh)  
TWA075A Heat Pump with TWE075A Air Handler At 2500 CFM  
Outdoor  
Heating Capacity (BTUH/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
34.9  
35.5  
36.5  
37.9  
30.4  
31.5  
33.1  
35.0  
37.5  
40.3  
43.5  
47.1  
51.1  
55.4  
60.1  
64.8  
69.7  
74.8  
80.2  
85.6  
91.2  
96.8  
102.5  
28.5  
30.0  
31.8  
34.0  
36.7  
39.7  
43.1  
46.9  
51.0  
55.3  
60.0  
64.7  
69.6  
74.7  
79.9  
85.3  
90.8  
96.2  
101.9  
26.9  
28.6  
30.6  
33.2  
36.1  
39.3  
42.9  
46.8  
50.9  
55.3  
60.0  
64.7  
69.5  
74.5  
79.6  
84.9  
90.2  
95.6  
101.2  
5.5  
5.5  
5.4  
5.4  
5.4  
5.4  
5.5  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.7  
6.9  
7.1  
5.6  
5.6  
5.6  
5.6  
5.7  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
7.0  
5.7  
5.7  
5.8  
5.8  
5.9  
6.0  
6.1  
6.2  
6.3  
6.4  
6.6  
6.8  
6.9  
7.1  
5.8  
5.9  
5.9  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.6  
7.8  
8.0  
8.2  
8.4  
39.7  
42.0  
44.8  
48.0  
51.7  
55.8  
60.3  
65.0  
69.9  
75.1  
80.6  
86.2  
92.0  
97.8  
7
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
7.3  
7.5  
7.7  
7.9  
7.1  
7.3  
7.5  
7.7  
103.7  
8.1  
Table PD-9 — Gross Heating Capacities (KW)  
TWA075A Heat Pump withTWE075A Air Handler At 1180 L/S  
Outdoor  
Heating Capacity (KW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
-27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0 . 0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
10.2  
10.4  
10.7  
11.1  
8.9  
9.2  
9.7  
8.4  
8.8  
9.3  
7.9  
8.4  
9.0  
9.7  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6 . 8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7. 4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7. 7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
10.3  
11.0  
11.8  
12.7  
13.8  
15.0  
16.2  
1 7. 6  
19.0  
20.4  
21.9  
23.5  
25.1  
26.7  
28.3  
30.0  
10.0  
10.7  
11.6  
12.6  
13.7  
14.9  
16.2  
1 7. 6  
19.0  
20.4  
21.9  
23.4  
25.0  
26.6  
28.2  
29.8  
11.6  
10.6  
11.5  
12.6  
13.7  
14.9  
16.2  
1 7. 6  
18.9  
20.3  
21.8  
23.3  
24.9  
26.4  
28.0  
29.6  
12.3  
13.1  
14.1  
15.1  
16.3  
1 7. 7  
19.0  
20.5  
22.0  
23.6  
25.2  
26.9  
28.6  
30.4  
7.9  
8 . 1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
Airflow = 2500 cfm (1179 L/s)  
Correction Factors - Other Airflows  
(Table Value x Correction Factor = Value at new airflow)  
HeatingCapacity(HighTemp.)=75,000(21.82)  
HeatingCapacity(LowTemp.)=47,000(13.84)  
Compressor Power (High Temp) = 5.41 kW  
Compressor Power (Low Temp) = 4.55 kW  
Coeff. Of Perf. (High Temp) = 3.2  
Coeff. Of Perf. (Low Temp) = 2.3  
Outdoor Fan Power = 550 watts  
Airflow  
2250CFM  
1061L/s  
x0.99  
2750CFM  
1297L/s  
x1.01  
HeatingCapacity  
Compressor Kw  
x1.02  
x0.98  
Indoor Fan Power = 800 watts  
Values at ARI Rating Conditions of:  
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)  
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)  
Note:  
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.  
20  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-10 — Gross Heating Capacities (MBh)  
TWA100A Heat Pump withTWE100A Air Handler At 3325 CFM  
Outdoor  
Heating Capacity (BTUH/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
21.9  
33.4  
40.8  
46.7  
52.3  
57.7  
63.2  
68.9  
74.8  
80.9  
87.3  
93.6  
100.2  
107.1  
114.4  
121.9  
129.7  
137.7  
145.9  
39.6  
43.6  
47.5  
43.0  
46.0  
49.2  
52.8  
56.5  
60.6  
65.1  
69.9  
75.1  
80.6  
86.5  
92.6  
98.9  
105.6  
112.7  
120.1  
127.8  
135.6  
143.7  
44.8  
47.3  
50.2  
53.4  
57.0  
5.6  
6.2  
6.6  
6.8  
7.0  
7.2  
7.4  
7.5  
7.7  
7.3  
7.5  
7.6  
7.8  
7.9  
7.9  
8.0  
8.1  
8.2  
8.4  
8.5  
8.6  
8.8  
9.0  
9.1  
9.4  
9.6  
9.8  
10.1  
10.3  
10.6  
10.9  
11.2  
11.6  
8.4  
8.5  
8.6  
8.7  
8.8  
8.9  
9.1  
9.2  
9.4  
51.5  
55.7  
60.1  
64.8  
69.8  
75.1  
80.8  
86.8  
92.9  
99.3  
106.0  
113.2  
120.6  
128.3  
136.2  
144.3  
7
60.8  
65.1  
69.8  
74.9  
80.3  
86.2  
92.2  
98.5  
105.2  
112.3  
119.7  
127.3  
135.1  
143.2  
8.1  
8.2  
8.4  
8.5  
8.7  
8.9  
9.1  
9.3  
9.5  
9.8  
10.1  
10.4  
10.7  
11.0  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
7.9  
9.6  
9.8  
8.0  
8.2  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
9.9  
10.1  
10.3  
10.6  
10.9  
11.2  
11.5  
11.9  
12.2  
Table PD-10 — Gross Heating Capacities (KW)  
TWA100A Heat Pump withTWE100A Air Handler At 1570 L/S  
Outdoor  
Heating Capacity (KW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
-27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2 . 8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
6.4  
9.8  
11.6  
12.8  
13.9  
15.1  
16.3  
17.6  
19.0  
20.4  
22.0  
23.7  
25.4  
2 7. 2  
29.1  
31.0  
33.1  
35.3  
37.6  
39.9  
42.3  
12.6  
13.5  
14.4  
15.4  
16.6  
17.8  
19.1  
20.5  
22.0  
23.6  
25.3  
2 7. 1  
29.0  
30.9  
33.0  
35.2  
37.4  
13.1  
13.9  
14.7  
15.6  
16.7  
17.8  
19.1  
20.4  
21.9  
23.5  
25.2  
2 7. 0  
28.8  
30.8  
32.9  
35.0  
37.3  
39.6  
41.9  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6 . 9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
11.9  
13.7  
15.3  
16.9  
18.5  
20.2  
21.9  
23.7  
25.6  
2 7. 4  
29.3  
31.3  
33.5  
35.7  
38.0  
40.3  
42.7  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
39.7  
42.1  
Airflow = 3325 cfm (1569 L/s)  
Correction Factors - Other Airflows  
(Table Value x Correction Factor = Value at new airflow)  
HeatingCapacity(HighTemp.)=106,000(31.05)  
HeatingCapacity(LowTemp.)=69,000(20.29)  
Compressor Power (High Temp) = 7.61 kW  
Compressor Power (Low Temp) = 6.38 kW  
Coeff. Of Perf. (High Temp) = 3.30  
Coeff. Of Perf. (Low Temp) = 2.4  
Outdoor Fan Power = 644 watts  
Airflow  
3000CFM  
1416L/s  
x0.99  
3675CFM  
1734L/s  
x1.01  
HeatingCapacity  
Compressor Kw  
x1.02  
x0.98  
Indoor Fan Power = 1,170 watts  
Values at ARI Rating Conditions of:  
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)  
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)  
Note:  
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.  
TWA-PRC001-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-11 — Gross Heating Capacities (MBh)  
TWA155B Heat Pump withTWE155B Air Handler At 5000 CFM  
Outdoor  
Heating Capacity (BTUH/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
69.7  
71.1  
73.1  
76.0  
79.8  
84.5  
90.2  
96.7  
104.2  
112.6  
121.8  
131.3  
141.4  
151.9  
163.0  
174.4  
186.2  
198.0  
210.0  
60.9  
63.2  
66.4  
70.4  
75.4  
81.1  
87.7  
95.1  
103.2  
111.9  
121.4  
131.0  
140.9  
151.3  
162.2  
173.3  
184.6  
196.0  
207.6  
57.2  
60.2  
63.9  
68.4  
73.9  
80.0  
87.0  
94.6  
102.9  
111.8  
121.3  
130.8  
140.7  
151.0  
161.6  
172.5  
183.6  
194.8  
206.2  
54.0  
57.4  
61.6  
66.8  
72.7  
79.3  
86.6  
94.4  
102.8  
111.8  
121.3  
130.7  
140.5  
150.6  
161.0  
171.7  
182.6  
193.5  
204.8  
11.1  
11.0  
11.0  
10.9  
10.9  
11.0  
11.1  
11.2  
11.3  
11.5  
11.7  
12.0  
12.3  
12.6  
12.9  
13.2  
13.6  
14.0  
14.4  
11.4  
11.3  
11.4  
11.4  
11.5  
11.6  
11.8  
12.0  
12.2  
12.5  
12.8  
13.1  
13.4  
13.8  
14.1  
14.5  
14.9  
15.3  
15.7  
11.5  
11.6  
11.6  
11.7  
11.9  
12.1  
12.3  
12.5  
12.8  
13.1  
13.4  
13.8  
14.1  
14.5  
14.8  
15.2  
15.6  
16.0  
16.4  
11.8  
11.8  
12.0  
12.1  
12.3  
12.6  
12.8  
13.1  
13.4  
13.7  
14.1  
14.4  
14.8  
15.2  
15.6  
15.9  
16.3  
16.7  
17.1  
7
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
Table PD-11 Gross Heating Capacities (KW)  
TWA155B Heat Pump withTWE155B Air Handler At 2360 L/S  
Outdoor  
Heating Capacity (KW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
-27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
20.4  
20.8  
21.4  
22.3  
23.4  
24.7  
26.4  
28.3  
30.5  
33.0  
35.7  
38.5  
41.4  
44.5  
47.7  
17.8  
18.5  
19.4  
20.6  
22.1  
23.8  
25.7  
27.8  
30.2  
32.8  
35.5  
38.3  
41.3  
44.3  
47.5  
16.8  
17.6  
18.7  
20.0  
21.6  
23.4  
25.5  
27.7  
30.1  
32.7  
35.5  
38.3  
41.2  
44.2  
47.3  
50.5  
53.8  
57.0  
60.4  
15.8  
16.8  
18.0  
19.6  
21.3  
23.2  
25.3  
27.6  
30.1  
32.7  
35.5  
38.3  
41.1  
44.1  
47.2  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
51.1  
54.5  
58.0  
61.5  
50.7  
54.0  
57.4  
50.3  
53.5  
56.7  
60.0  
60.8  
Correction Factors - Other Airflows“(Table Value  
Correction Factor = Value at new airflow)  
Airflow = 5000 cfm (2360 L/s)  
HeatingCapacity(HighTemp.)=151,000(44.27)  
HeatingCapacity(LowTemp.)=95,000(27.67)  
Compressor Power (High Temp) = 10.94 kW  
Compressor Power (Low Temp) = 9.18 kW  
Coeff. Of Perf. (High Temp) = 3.2  
Airflow  
4500CFM 5500CFM“  
2124 L/s 2596 L/s  
HeatingCapacity  
Compressor Kw  
x 0.99  
x 1.02  
x 1.01  
x 0.98  
Coeff. Of Perf. (Low Temp) = 2.3  
Outdoor Fan Power = 1100 watts  
Indoor Fan Power = 1700 watts  
Values at ARI Rating Conditions of:  
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)  
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)  
Note:  
1.Rated with 25 feet of 1-3/8"" suction and 1/2"" liquid line."  
22  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(System)  
Table PD-12 — Gross Heating Capacities (MBh)  
TWA200B Heat Pump withTWE200B Air Handler At 6675 CFM  
Outdoor  
Heating Capacity (BTUH/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
43.5  
68.9  
82.3  
80.3  
87.1  
94.2  
85.7  
91.0  
97.0  
88.4  
93.0  
98.4  
10.8  
12.3  
13.0  
13.4  
13.8  
14.1  
14.5  
14.8  
15.1  
15.4  
15.7  
16.0  
16.4  
16.7  
17.2  
14.5  
14.8  
15.1  
15.3  
15.6  
15.8  
16.1  
16.4  
16.7  
17.1  
17.4  
17.8  
18.2  
18.6  
19.1  
19.6  
20.1  
20.6  
21.2  
15.6  
15.8  
16.0  
16.2  
16.4  
16.7  
17.0  
17.3  
17.6  
18.0  
18.4  
18.8  
19.2  
19.7  
20.2  
20.7  
21.2  
21.8  
22.4  
16.5  
16.7  
16.8  
17.1  
17.3  
17.6  
17.9  
18.2  
18.5  
18.9  
19.4  
19.8  
20.3  
20.8  
21.3  
21.9  
22.4  
23.0  
23.7  
93.2  
101.6  
109.4  
117.8  
126.8  
136.4  
146.7  
157.6  
169.3  
181.2  
193.5  
206.5  
220.3  
234.6  
249.2  
264.0  
279.4  
103.6  
110.8  
118.6  
127.2  
136.5  
146.5  
157.2  
168.8  
180.5  
192.7  
205.7  
219.4  
233.6  
248.2  
262.9  
278.2  
104.5  
111.3  
118.8  
127.1  
136.1  
146.0  
156.6  
168.1  
179.8  
192.0  
205.0  
218.7  
232.9  
247.4  
262.1  
277.2  
103.5  
113.7  
124.2  
135.0  
146.2  
157.9  
170.2  
182.4  
195.1  
208.4  
222.4  
236.9  
251.7  
266.7  
282.3  
7
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
17.6  
18.1  
18.5  
19.1  
Table PD-12 — Gross Heating Capacities (KW)  
TWA200B Heat Pump with TWE200B Air Handler At 3150 L/S  
Outdoor  
Heating Capacity (KW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
12.7  
20.2  
24.1  
27.3  
30.3  
33.3  
36.4  
39.5  
42.8  
46.2  
49.8  
53.4  
57.1  
61.0  
65.1  
69.4  
73.7  
78.1  
82.7  
23.5  
25.5  
27.6  
29.7  
32.0  
34.5  
37.1  
39.9  
42.9  
46.2  
49.6  
53.0  
56.7  
60.5  
64.5  
68.7  
73.0  
77.3  
25.1  
26.6  
28.4  
30.3  
32.4  
34.7  
37.2  
40.0  
42.9  
46.0  
49.4  
52.8  
56.4  
60.2  
64.3  
68.4  
72.7  
77.0  
25.9  
27.2  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
28.8  
30.6  
32.6  
34.8  
37.2  
39.9  
42.7  
45.9  
49.2  
52.6  
56.2  
60.0  
64.0  
68.2  
72.4  
76.7  
81.2  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
81.8  
81.5  
Correction Factors - Other Airflows  
(Table Value x Correction Factor = Value at new airflow)  
Airflow = 6700 cfm (3162 L/s)  
Heating Capacity (High Temp.) = 206,000 (60.26)  
Heating Capacity (Low Temp.) = 135,000 (39.66)  
Compressor Power (High Temp) = 14.92 kW  
Compressor Power (Low Temp) = 12.62 kW  
Coeff. Of Perf. (High Temp) = 3.2  
Airflow  
6000CFM  
2832L/s  
x0.99  
7325CFM  
3457L/s  
x1.01  
HeatingCapacity  
Compressor Kw  
x1.02  
x0.98  
Coeff. Of Perf. (Low Temp) = 2.4  
Values at ARI Rating Conditions of:  
70F(21.1C)and47/43F(8.3/6.1C)(HighTemp.Cond.)  
70F(21.1C)and17/15F(-8.3/-9.4C)(LowTemp.Cond)  
Outdoor Fan Power = 1,100 watts  
Indoor Fan Power = 2,290 watts  
Note:  
1. Rated with 25 feet of 1-3/8” suction and 1/2" liquid line."  
TWA-PRC001-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(Air Handler)  
Table PD-13 — Evaporator Fan Performance —TWE050A  
External Static Pressure (Inches of Water Gauge)  
.10"  
.20"  
.30"  
.40" .50" .60" .70" .80"  
.90"  
1.00"  
1.10"  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
0.75 HP Standard Motor and Drive  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 973 0.68 1006 0.71  
607 0.36 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 984 0.71  
625 0.38 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 995 0.74  
601 0.35 648 0.40 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 1005 0.77  
625 0.36 671 0.41 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76  
642 0.40 687 0.45 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80  
659 0.44 703 0.49 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84  
674 0.48 722 0.54 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89  
1.0HPOversizedMotorandHighStaticDrive  
Table PD-13— Evaporator Fan Performance —TWE050A  
External Static Pressure (Pascal)  
25  
50  
75  
100 125 150  
174  
199  
224  
249  
274  
L/S  
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM BHP RPM BHP RPM KW RPM KW RPM KW  
0.56 Standard Motor and Drive  
661  
708  
755  
802  
850  
897  
944  
991  
646 0.28 698 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 973 0.51 1006 0.53  
607 0.27 661 0.30 713 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 984 0.53  
625 0.28 676 0.32 727 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 995 0.55  
601 0.26 648 0.30 696 0.33 744 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 1005 0.57  
625 0.27 671 0.31 716 0.34 762 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57  
642 0.30 687 0.34 731 0.37 776 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60  
659 0.33 703 0.37 745 0.40 790 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.67  
674 0.36 722 0.40 770 0.45 817 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66  
0.75KWOversizedMotorandHighStaticDrive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in  
0.5 turn increments.  
Table PD-14 — Blower Speeds  
Motor DriveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
High Static  
N/A  
N/A  
590  
713  
639  
772  
688  
832  
737  
891  
786  
951  
835  
1009  
24  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(Air Handler)  
Table PD-15 — Evaporator Fan Performance TWE075A  
External Static Pressure (In. Of Water Column)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.10  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2000  
2125  
2250  
2375  
2500  
2625  
2750  
2875  
3000  
443 0.44 489 0.49 535 0.54 581 0.59 627 0.64 673 0.69 719 0.74 765 0.79 791 0.83 818 0.89  
453 0.46 499 0.52 546 0.57 592 0.63 638 0.68 684 0.74 730 0.79 771 0.85 798 0.90 825 0.96  
463 0.49 510 0.55 556 0.61 602 0.67 649 0.73 695 0.79 742 0.85 776 0.91 804 0.97 831 1.03  
473 0.51 520 0.57 567 0.64 613 0.70 660 0.77 706 0.83 753 0.90 782 0.97 810 1.03 838 1.10  
445 0.47 489 0.54 533 0.60 578 0.67 622 0.73 667 0.80 711 0.86 756 0.93 784 0.99 813 1.07 842 1.14  
464 0.50 506 0.57 548 0.63 589 0.69 631 0.76 672 0.82 714 0.88 757 0.95 786 1.01 815 1.09 844 1.17  
484 0.53 523 0.59 562 0.66 601 0.72 640 0.78 678 0.84 717 0.91 758 0.97 787 1.03 817 1.12 847 1.21  
504 0.56 540 0.62 576 0.68 612 0.74 648 0.81 684 0.87 720 0.93 759 0.99 789 1.05 819 1.15 850 1.24  
524 0.59 557 0.65 590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17 853 1.27  
1.0 HP Standard Motor  
andHighStaticDrive  
1.0 HP Standard Motor  
and Low Static Drive  
1.5 HP Oversized Motor  
andHighStaticDrive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway  
filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are  
made in 0.5 turn increments.  
Table PD-15— Continued  
External Static Pressure (In. Of Water Column)  
120 1.30 1.40 1.50 1.60  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
CFM  
2000  
2125  
2250  
2375  
2500  
2625  
2750  
2875  
3000  
844 0.96 871 1.02 897 1.09 924 1.15 950 1.21  
852 1.03 879 1.09 906 1.16 933 1.22  
859 1.10 886 1.17 914 1.23 942 1.30  
866 1.17 894 1.24 922 1.30 950 1.37  
870 1.21 899 1.29 928 1.36  
874 1.25 903 1.33 932 1.42  
877 1.29 907 1.38 937 1.47  
880 1.33 911 1.43 942 1.52  
884 1.37 915 1.48 946 1.58  
Table PD-15 — Evaporator Fan Performance TWE075A  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125 150 174  
199  
224  
249  
274  
L/S  
944  
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW  
443 0.33 489 0.37 535 0.40 581 0.44 627 0.48 673 0.51 719 0.55 765 0.59 791 0.62 818 0.66  
453 0.34 499 0.39 546 0.43 592 0.47 638 0.51 684 0.55 730 0.59 771 0.63 798 0.67 825 0.72  
463 0.37 510 0.41 556 0.45 602 0.50 649 0.54 695 0.59 742 0.63 776 0.68 804 0.72 831 0.77  
473 0.38 520 0.43 567 0.48 613 0.52 660 0.57 706 0.62 753 0.67 782 0.72 810 0.77 838 0.82  
445 0.35 489 0.40 533 0.45 578 0.50 622 0.54 667 0.60 711 0.64 756 0.69 784 0.74 813 0.80 842 0.85  
464 0.37 506 0.43 548 0.47 589 0.51 631 0.57 672 0.61 714 0.66 757 0.71 786 0.75 815 0.81 844 0.87  
484 0.40 523 0.44 562 0.49 601 0.54 640 0.58 678 0.63 717 0.68 758 0.72 787 0.77 817 0.84 847 0.90  
504 0.42 540 0.46 576 0.51 612 0.55 648 0.60 684 0.65 720 0.69 759 0.74 789 0.78 819 0.86 850 0.92  
524 0.44 557 0.48 590 0.53 624 0.57 657 0.62 690 0.66 723 0.71 760 0.75 790 0.80 821 0.87 853 0.95  
1003  
1062  
1121  
1180  
1239  
1298  
1357  
1416  
.75 KW Standard Motor  
andHighStaticDrive  
.75 KW Standard Motor  
and High Static Drive  
1.12 KW Oversized Motor  
andHighStaticDrive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway  
filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are  
made in 0.5 turn increments.  
Table PD-15 — Continued  
External Static Pressure (Pascal)  
324 349 374  
299  
398  
L/S  
944  
RPM KW RPM KW RPM KW RPM KW RPM KW  
844 0.72 871 0.76 897 0.81 924 0.86 950 0.90  
852 0.77 879 0.81 906 0.87 933 0.91  
859 0.82 886 0.87 914 0.92 942 0.97  
866 0.87 894 0.92 922 0.97 950 1.02  
870 0,90 899 0.96 928 1.01  
1003  
1062  
1121  
1180  
1239  
1298  
1357  
1416  
874 0.93 903 0.99 932 1.06  
877 0.96 907 1.03 937 1.10  
880 0.99 911 1.07 942 1.13  
884 1.02 915 1.10 946 1.18  
Table PD-16 — Blower Speeds  
Motor DriveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
Low Static N/A  
High Static N/A  
N/A  
600  
428  
700  
650  
464  
750  
700  
499  
800  
750  
535  
850  
800  
571  
900  
850  
606  
950  
TWA-PRC001-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(Air Handler)  
Table PD-17 — Evaporator Fan Performance TWE100A,TWE100B  
External Static Pressure (In. Of Water Column)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.20  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2600  
2775  
2950  
3125  
3300  
3475  
3650  
3825  
4000  
460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 679 0.79 717 0.87 744 0.94 772 1.01 826 1.16  
473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 686 0.85 723 0.93 748 1.00 775 1.07 830 1.20  
487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 693 0.91 728 0.99 751 1.06 779 1.12 833 1.25  
501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 700 0.97 734 1.05 755 1.11 783 1.18 737 1.30  
520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 710 1.06 740 1.13 759 1.19 787 1.25 841 1.37  
541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 721 1.16 746 1.21 764 1.28 793 1.34 846 1.48  
562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 732 1.27 753 1.31 772 1.38 801 1.45 853 1.59  
582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 739 1.38 763 1.44 787 1.51 815 1.58 862 1.74  
602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 747 1.50 773 1.58 801 1.64 829 1.71 872 1.89  
1.5 HP Standard Motor  
andDrive  
2.0 HP Oversized Motor  
andHighStaticDrive  
1.5 HP Standard Motor  
and Low Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway  
filters.  
Table PD-17— Continued  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are  
made in 0.5 turn increments.  
External Static Pressure (In. Of Water Column)  
1.40 1.60  
CFM  
RPM BHP RPM BHP  
4. Low Static Drive must be field supplied.  
2600  
2775  
2960  
3125  
3300  
3475  
3650  
3825  
4000  
881 1.30 936 1.45  
884 1.36 938 1.51  
886 1.41 939 1.57  
889 1.47 941 1.64  
892 1.54 945 1.73  
897 1.63 950 1.85  
902 1.73 955 1.99  
912 1.89 960 2.18  
922 2.04 965 2.30  
Table PD-17— Evaporator Fan Performance TWE0100A,TWE100B  
External Static Pressure (Pascal)  
25  
50  
75  
100 125 150  
174  
199  
224  
249  
274  
L/S  
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW  
1227  
1310  
1392  
1475  
1557  
1640  
1723  
1805  
1888  
460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 0.59 717 0.65 744 0.70 772 0.75 826 0.87  
473 0.28 576 0.34 613 0.40 649 0.45 686 0.51 723 0.57 748 0.63 775 0.69 830 0.75 884 0.80 938 0.89  
487 0.32 519 0.37 552 0.43 587 0.50 623 0.56 658 0.62 693 0.68 728 0.74 751 0.79 779 0.84 833 0.93  
501 0.37 532 0.42 565 0.48 599 0.54 632 0.60 666 0.66 700 0.72 734 0.78 755 0.83 783 0.88 737 0.97  
520 0.43 548 0.48 581 0.54 613 0.60 644 0.66 677 0.73 710 0.79 740 0.84 759 0.89 787 0.93 841 1.02  
541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.80 721 0.87 746 0.90 764 0.95 793 1.00 846 1.10  
562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 0.95 753 0.98 772 1.03 801 1.08 853 1.19  
582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 1.03 763 1.07 787 1.13 815 1.18 862 1.30  
602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 773 1.18 801 1.22 829 1.28 872 1.41  
1.49 KW Oversized Motor  
andHighStaticDrive  
1.12 KW Standard  
Motor and Drive  
.75 KW Standard Motor  
and Low Static Drive  
Notes:  
1. Performance based on a wet coil and 1 inch (25.4 mm) throwaway  
filters.  
Table PD-17— Continued  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 3.0 turns open. Adjustments are  
made in 0.5 turn increments.  
External Static Pressure (Pascal)  
349  
398  
4. Low Static Drive must be field supplied.  
L/S  
RPM KW RPM KW  
1227  
1310  
1392  
1475  
1557  
1640  
1723  
1805  
1888  
881 0.97 936 1.08  
506 1.01 540 1.13  
886 1.05 939 1.17  
889 1.10 941 1.22  
892 1.15 945 1.29  
897 1.22 950 1.38  
902 1.29 955 1.48  
912 1.41 960 1.63  
922 1.52 965 1.72  
Table PD - 18 — Blower Speeds  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
Low Static N/A  
High Static N/A  
N/A  
587  
453  
606  
629  
485  
641  
671  
518  
677  
713  
550  
713  
755  
583  
748  
796  
615  
784  
26  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(Air Handler)  
Table PD-19 — Evaporator Fan Performance — TWE155B  
External Static Pressure (Inches of Water Column)  
.10"  
.20"  
.30"  
.40"  
.50" .60" .70" .80" .90"  
1.00"  
1.20"  
140  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2.0HPStandardMotorandDrive  
3.0HPOversizedMotor  
andHighStaticDrive  
4000  
4250  
4500  
4750  
5000  
5260  
5500  
5750  
6000  
628 1.34 653 1.38 678 1.43 692 1.48 708 1.52 723 1.57 738 1.60 749 1.61 759 1.62 795 1.66 851 1.85 907 2.03  
633 1.37 658 1.41 683 1.46 697 1.51 713 1.55 728 1.60 743 1.62 751 1.63 770 1.64 806 1.71 862 1.90 918 2.11  
637 1.40 662 1.44 687 1.49 701 1.53 717 1.58 732 1.63 747 1.64 754 1.65 782 1.67 817 1.76 873 1.96 929 2.19  
641 1.42 666 1.50 691 1.53 705 1.61 721 1.63 736 1.65 751 1.66 765 1.67 793 1.72 828 1.81 884 2.01 940 2.27  
645 1.44 670 1.52 695 1.56 710 1.65 725 1.67 739 1.68 758 1.70 777 1.74 806 1.81 839 1.91 896 2.13  
650 1.46 675 1.53 700 1.59 716 1.67 728 1.70 741 1.73 765 1.75 790 1.82 819 1.92 849 2.03 907 2.28  
652 1.47 678 1.55 703 1.63 721 1.71 734 1.75 747 1.78 775 1.83 804 1.92 832 2.03 861 2.15 920 2.44  
653 1.48 680 1.57 706 1.68 726 1.76 743 1.81 761 1.86 789 1.94 817 2.04 846 2.16 875 2.29 935 2.61  
655 1.49 681 1.59 709 1.74 731 1.80 752 1.87 774 1.94 803 2.05 831 2.17 860 2.29 889 2.44 950 2.78  
Table PD-19 — Evaporator Fan Performance TWE155B  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125 150 174  
199  
224  
249  
299  
349  
L/S  
RPM KW RPM KW RPM KW RPM KW RPM KW RPM KW RPM BHP RPM BHP RPM KW RPM KW RPM KW RPM KW  
1.49KWStandardMotorandDriveSystem  
2.24KWOversizedMotor  
andHighStaticDriveSystem  
1888  
2006  
2124  
2242  
2360  
2482  
2596  
2714  
2832  
628 1.00 653 1.03 678 1.07 692 1.10 708 1.13 723 1.17 738 1.19 749 1.20 759 1.21 795 1.24 851 1.38 907 1.51  
633 1.02 658 1.05 683 1.09 697 1.13 713 1.16 728 1.19 743 1.21 751 1.22 770 1.22 806 1.28 862 1.42 918 1.57  
637 1.04 662 1.07 687 1.11 701 1.14 717 1.18 732 1.22 747 1.23 754 1.23 782 1.25 817 1.31 873 1.46 929 1.63  
641 1.06 666 1.12 691 1.14 705 1.20 721 1.22 736 1.23 751 1.24 765 1.25 793 1.28 828 1.35 884 1.50 940 1.69  
645 1.07 670 1.13 695 1.16 710 1.23 725 1.25 739 1.25 758 1.27 777 1.30 806 1.35 839 1.42 896 1.59  
650 1.09 675 1.14 700 1.19 716 1.25 728 1.27 741 1.29 765 1.30 790 1.36 819 1.43 849 1.51 907 1.70  
652 1.10 678 1.16 703 1.22 721 1.28 734 1.30 747 1.33 775 1.36 804 1.43 832 1.51 861 1.60 920 1.82  
653 1.10 680 1.17 706 1.25 726 1.31 743 1.30 761 1.39 789 1.45 817 1.52 846 1.61 875 1.71 935 1.95  
655 1.11 681 1.19 709 1.30 731 1.34 752 1.35 774 1.45 803 1.53 831 1.62 860 1.71 889 1.82 950 2.07  
Notes:  
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn increments.  
Table PD-20Blower Speeds  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
High Static  
619  
777  
648  
806  
677  
835  
705  
863  
734  
892  
763  
921  
N/A  
950  
TWA-PRC001-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
(Air Handler)  
Table PD-21— Evaporator Fan Performance TWE200B  
External Static Pressure (In. Of Water Column)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.20  
140  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
5200  
5525  
5850  
6175  
6500  
6825  
7150  
7475  
7800  
461 0.74 503 0.91 545 1.07 587 1.03 619 1.17 685 1.40 723 1.59 750 1.74 777 1.89 851 2.19 898 2.39  
479 0.88 521 1.04 563 1.21 605 1.21 640 1.35 701 1.58 739 1.77 766 1.92 793 2.07 859 2.37 906 2.60  
497 1.01 539 1.18 581 1.34 623 1.39 661 1.53 717 1.76 755 1.95 782 2.10 809 2.25 868 2.55 915 2.81  
473 0.99 515 1.15 557 1.31 599 1.48 641 1.57 682 1.71 732 1.94 769 2.12 796 2.27 823 2.43 877 2.73 924 3.02  
492 1.12 534 1.28 576 1.45 618 1.61 660 1.75 702 1.90 748 2.12 784 2.30 811 2.45 838 2.60 886 2.91 933 3.22  
510 1.25 552 1.42 594 1.59 636 1.75 678 1.91 723 2.10 763 2.30 794 2.47 820 2.62 846 2.77 894 3.09 941 3.42  
528 1.38 570 1.56 612 1.73 654 1.90 697 2.07 744 2.30 779 2.49 804 2.64 830 2.78 855 2.94 903 3.26 950 3.62  
550 1.61 594 1.77 640 1.92 683 2.08 721 2.29 760 2.50 790 2.67 815 2.81 840 2.96 865 3.11 914 3.47 959 3.85  
572 1.83 618 1.97 668 2.10 712 2.27 746 2.52 776 2.69 802 2.84 826 2.99 851 3.13 876 3.27 926 3.67 969 4.08  
3.0Standard  
Motorand  
LowStaticDrive LowStaticDrive  
3.0 HP Standard  
Motor and Field-Supplied  
5HPOversizedMotor  
andHighStaticDrive  
Notes:  
Table PD-21— Continued  
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in  
0.5 turn increments.  
External Static Pressure (In. Of Water Column)  
1.60 1.80  
CFM  
RPM BHP RPM BHP  
5200  
5525  
5850  
5175  
8500  
8825  
7150  
7475  
7800  
944 2.75 989 3.12  
952 2.96 997 3.33  
961 3.17 1006 3.54  
970 3.38 1015 3.75  
978 3.59 1023 3.96  
986 3.80  
994 4.01  
1003 4.25  
1012 4.50  
Table PD-21— Evaporator Fan Performance TWE200B  
External Static Pressure (Pascal)  
25  
50  
75  
100 125 150  
174  
199  
224  
249  
299  
349  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2454  
2608  
2761  
2914  
3068  
3221  
3374  
3528  
3681  
461 0.55 503 0.68 545 0.80 587 0.77 619 0.87 685 1.04 723 1.19 750 1.30 777 1.41 851 1.63 898 1.78  
479 0.66 521 0.78 563 0.90 605 0.90 640 1.01 701 1.18 739 1.32 766 1.43 793 1.54 859 1.77 906 1.94  
497 0.75 539 0.88 581 1.00 623 1.04 661 1.14 717 1.31 755 1.45 782 1.57 809 1.68 868 1.90 915 2.10  
473 0.74 515 0.86 557 0.98 599 1.10 641 1.17 682 1.28 732 1.45 769 1.58 796 1.69 823 1.81 877 2.04 924 2.52  
492 0.84 534 0.95 576 1.08 618 1.20 660 1.30 702 1.42 748 1.58 784 1.72 811 1.83 838 1.94 886 2.17 933 2.40  
510 0.93 552 1.06 594 1.19 636 1.30 678 1.42 723 1.57 763 1.72 794 1.84 820 1.95 846 2.07 894 2.30 941 2.55  
528 1.03 570 1.16 612 1.29 654 1.42 697 1.54 744 1.72 779 1.86 804 1.97 830 2.07 855 2.19 903 2.43 950 2.70  
550 1.20 594 1.32 640 1.43 683 1.55 721 1.71 760 1.87 790 1.99 815 2.10 840 2.21 865 2.32 914 2.59 959 2.87  
572 1.36 618 1.47 668 1.57 712 1.69 746 1.88 776 2.01 802 2.12 826 2.23 851 2.33 876 2.44 926 2.74 969 3.04  
StandardMotor 3.0 HP Standard  
3.0HPand  
LowStaticDrive LowStaticDrive  
Motor and Field-Supplied  
5HPOversizedMotor  
andHighStaticDrive  
Notes:  
Table PD-21— Continued  
1. Performance based on a wet coil and 2 inch (51 mm) throwaway filters.  
2. Tabulated brake horsepower is the motor shaft output required.  
3. Factory setting of motor sheave is 1.5 turns open. Adjustments are made in 0.5 turn  
increments.  
External Static Pressure (Pascal)  
398 448  
CFM  
RPM BHP RPM BHP  
2454  
2608  
2761  
2914  
3068  
3221  
3374  
3528  
3681  
944 2.05 989 2.33  
952 2.21 997 2.48  
961 2.36 1006 2.64  
970 2.52 1015 2.80  
978 2.68 1023 2.95  
941 2.55 986 2.83  
994 2.99  
Table PD-22 — Blower Speeds  
Motor SheaveTurns Open  
1003 3.17  
1012 3.36  
Drive  
6
5
4
3
2
1
0
Standard  
Low Static  
Field-Supplied Low Static  
High Static  
706  
457  
574  
N/A  
732  
478  
595  
821  
758  
500  
617  
862  
784  
521  
638  
903  
811  
542  
659  
945  
837  
563  
680  
986  
863  
585  
702  
1027  
28  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-23— Discharge PlenumAnd GrilleAssemblyThrow Distance Air Handler  
Unit  
Louver Angle Deflection Position  
Model No.  
CFM  
L/S  
Straight  
20, Ft. (m)  
40, Ft. (m)  
55, Ft. (m)  
1400  
1600  
1800  
2000  
2200  
2100  
661  
755  
850  
944  
1038  
38 (11.6)  
42 (12.8)  
46 (14.0)  
48 (14.6)  
51 (15.5)  
49 (14.9)  
24 (7.3)  
22 (6.7)  
26 (7.9)  
29 (8.8)  
33 (10.1)  
36 (11.0)  
31 (9.4)  
18 (5.5)  
20 (6.1)  
22 (6.7)  
24 (7.3)  
25 (7.6)  
27 (8.2)  
31 (9.4)  
37 (11.3)  
43 (13.1)  
50 (15.2)  
38 (11.6)  
TWE050  
TWE075  
991  
2400  
2700  
3000  
3200  
3600  
1133  
1274  
1416  
1510  
1699  
52 (15.9)  
55 (16.8)  
58 (17.7)  
56 (17.1)  
62 (18.9)  
43 (13.1)  
48 (14.6)  
53 (16.2)  
46 (14.0)  
51 (15.5)  
35 (10.7)  
38 (11.6)  
42 (12.8)  
38 (11.6)  
42 (12.8)  
29 (8.8)  
31 (9.4)  
32 (9.8)  
30 (9.1)  
33 (10.1)  
4000  
4400  
4800  
4300  
4900  
1888  
2077  
2265  
2029  
2313  
66 (20.1)  
71 (21.6)  
76 (23.2)  
42 (12.8)  
47 (14.3)  
57 (17.4)  
62 (18.9)  
67 (20.4)  
32 (9.8)  
47 (14.3)  
52 (15.9)  
56 (17.1)  
29 (8.8)  
32 (9.8)  
35 (10.7)  
38 (11.6)  
42 (12.8)  
21 (6.4)  
25 (7.6)  
TWE100  
TWE155  
TWE200  
38 (11.6)  
5400  
6000  
5600  
6400  
2549  
2832  
2643  
3020  
52 (15.9)  
57 (17.4)  
50 (15.2)  
56 (17.1)  
44 (13.4)  
49 (14.9)  
40 (12.2)  
46 (14.0)  
37 (11.3)  
41 (12.5)  
33 (10.1)  
38 (11.6)  
29 (8.8)  
32 (9.8)  
27 (8.2)  
30 (9.1)  
7200  
8000  
3398  
3776  
62 (18.9)  
66 (20.1)  
51 (15.5)  
57 (17.4)  
42 (12.8)  
47 (14.3)  
33 (10.1)  
35 (10.7)  
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).  
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by  
throw factor:  
Terminal Velocity  
50 FPM (.25 m/s)  
100 FPM (.51 m/s)  
150 FPM (.76 m/s)  
Throw Factor  
x
x
x
1.50  
.75  
.50  
PD-24 — Static Pressure DropThroughAccessories Air Handler  
Discharge  
Unit  
Model No.  
Return Grille  
Plenum and Grille2  
Electric Heaters (Kw)  
CFM  
L/S  
In.W.C.1 Pascal In.W.C.1 Pascal  
3.5-7  
10-14  
17-24  
35  
1400  
1600  
2000  
2100  
661  
755  
944  
991  
.09  
.12  
.18  
.05  
(22.4)  
(29.9)  
(44.8)  
(12.5)  
.16  
.21  
.33  
.19  
(39.8)  
(52.3)  
(82.2)  
(47.3)  
.06  
08  
.13  
.06  
.08  
.13  
.03  
.12  
.14  
.19  
.05  
TWE050A  
TWE075A  
.02  
.08  
2400  
3000  
1133  
1416  
.08  
.13  
(19.9)  
(32.4)  
.27  
.40  
(67.2)  
(99.6)  
.03  
.06  
.06  
.12  
.08  
.17  
.12  
.23  
TWE100A  
TWE100B  
2800  
3200  
4300  
1321  
1510  
2029  
.04  
.07  
.07  
(10.0)  
(17.4)  
(17.4)  
.34  
.43  
.18  
(84.7)  
(107.1)  
(44.8)  
.03  
.06  
.02  
.04  
.13  
.02  
.14  
.19  
.04  
.20  
.26  
.05  
4800  
6000  
5600  
2265  
2832  
2643  
.09  
.15  
.07  
(22.4)  
(37.4)  
(17.4)  
.23  
.34  
.32  
(57.3)  
(84.7)  
(79.7)  
.03  
.06  
.04  
.03  
.06  
.04  
.06  
.12  
.10  
.08  
.17  
.15  
TWE155B  
TWE200B  
6400  
8000  
3020  
3776  
.11  
.17  
(27.4)  
(42.3)  
.43  
.66  
(107.1)  
(164.3)  
.06  
.10  
.0-6  
.10  
.13  
.20  
.19  
.30  
1. Return air filter ESP included in Fan Performance Table data.  
2. At louver opening angle of 42° F (5.5° C). For ESP at other angle openings, see accessory Installer’s Guide.  
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).  
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by  
throw factor:  
Terminal Velocity  
50 FPM (.25 m/s)  
100 FPM (.51 m/s)  
150 FPM (.76 m/s)  
Throw Factor  
x
x
x
1.50  
.75  
.50  
.
TWA-PRC001-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Performance  
Data  
Table PD-25 — Auxiliary Electric Heat Capacity Air Handler  
No.  
Stage 1  
Stage 2  
Btuh  
Total  
Unit  
Total  
of  
KW  
Btuh  
KW  
KW  
KW  
Btuh  
KW  
Model No.  
KW Stages Input  
Output Output Input  
Output Output Output Output  
TWE050, 075,100  
3.47  
6.92  
10.39  
17.31  
1
1
1
2
3.47  
9.92  
10.39  
10.39  
11,851  
23,606  
35,457  
35,457  
3.47  
6.92  
10.39  
10.39  
11,851  
23,606  
35,457 10.39  
3.47  
6.92  
6.92  
23,606  
6.92 59,063 17.31  
TWE075, 100A, 100 24.22  
2
13.83  
47,213  
13.83  
10.39  
35,457 10.39 82,670 24.22  
TWE155, 200  
6.94  
13.83  
20.78  
34,62  
1
1
2
2
6.94  
13.83  
13.83  
20.78  
23,701  
47,213  
47,213  
70,915  
6.94  
13.83  
13.83  
20.78  
6.94  
23,701  
23,701  
47,213 13.83  
6.94  
6.94 70,915 20.78  
13.89 118,128 34.61  
13.84  
47,213  
*Heaters are rated at 400v. For other than rated voltage,  
2
2
Voltage  
Voltage  
Rated Voltage  
Capacity =  
x Rated Capacity and KW =  
x Rated KW.  
(
)
(
)
Rated Voltage  
30  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-1— Electrical Characteristics — Motors — Air Handler  
Standard Fan Motor  
Oversized Fan Motor  
Unit  
Amps  
Amps  
Model No.  
TWE050  
TWE075  
TWE100  
TWE155  
TWE200  
Volts  
Phase  
FLA  
1.4  
3.2  
3.6  
4.6  
7.6  
LRA  
8.2  
19.7  
25.5  
37.5  
39.2  
Phase  
FLA  
1.8  
4.0  
5.3  
6.9  
9.0  
LRA  
21.6  
25.5  
37.5  
39.2  
65.1  
380/415  
380/415  
380/415  
380/415  
380/415  
3
3
3
3
3
3
3
3
3
3
Table ED-2 — UnitWiring — Air Handler  
Minimum  
Circuit  
Ampacity  
Maximum Fuse  
Size or Maximum  
Circuit Breaker  
Unit  
Model No.  
Unit Operating  
Voltage Range  
TWE050  
TWE075  
TWE100  
380/415  
380/415  
380/415  
2
4
5
15  
15  
15  
TWE155  
TWE200  
380/415  
380/415  
6
10  
15  
15  
Table ED-3— Electrical Characteristics — Motors — 60 Cycle — Heat Pumps  
Compressor Motor  
Condenser Fan Motor  
Amps  
FLA LRA  
Amps  
Unit  
RLA  
(Ea.)  
LRA  
(Ea.)  
Model No.  
No.  
Volts  
Phase  
No.  
Volts  
Phase  
(Ea.)  
(Ea.)  
TWA075AD  
TWA100AD  
TWA155BD  
TWA200BD  
1
1
2
2
380/415  
380/415  
380/415  
380/415  
3
3
3
3
11.0  
14.9  
11.0  
14.9  
90.0  
118.0  
90.0  
1
1
2
2
380/415  
380/415  
380/415  
380/415  
1
1
1
1
1.6  
2.7  
1.6  
2.7  
3.7  
7.0  
3.7  
7.0  
118.0  
Table ED-4 — UnitWiring — Heat Pumps  
Minimum  
Circuit  
Ampacity  
Maximum Fuse  
Size or Maximum  
Circuit Breaker  
Unit  
Model No.  
Unit Operating  
Voltage Range  
TWA075  
TWA100  
380/415  
380/415  
18.0  
25.6  
30  
40  
TWA155  
TWA200  
380/415  
380/415  
31.6  
45.2  
40  
60  
TWA-PRC001-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Electrical  
Data  
Table ED-5— UnitWiringWith Electric Heat (Single Point Connection) Air Handlers  
Heater  
Model No.  
Heater  
KW Rating1  
3.47  
To Use  
with Unit  
Control  
Stages  
Minimum  
Maximum  
Circuit Ampacity 2  
Fuse Breaker Size 2  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL435A  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL435A  
BAYHTRM410A  
BAYHTRM420A  
BAYHTRM430A  
BAYHTRM450A  
BAYHTRM410A  
BAYHTRM420A  
BAYHTRM430A  
BAYHTRM450A  
1
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
2
9
17  
24  
39  
11  
15  
20  
25  
40  
15  
20  
30  
45  
60  
15  
25  
30  
45  
60  
30  
40  
60  
90  
40  
50  
60  
90  
6.92  
TWE050AD  
10.39  
17.31  
3.47  
6.92  
18  
26  
41  
56  
12  
19  
27  
42  
57  
21  
36  
51  
81  
25  
40  
55  
85  
10.39  
17.31  
24.22  
3.47  
TWE075AD  
6.92  
10.39  
20.78  
24.22  
6.94  
13.83  
20.78  
34.62  
6.94  
TWE100AD,TWE100BD  
TWE155BD  
13.83  
20.78  
34.62  
TWE200BD  
1. KW ratings are at 400v for 3 phase, 400v air handlers  
2
2
Voltage  
Voltage  
Rated Voltage  
For other than rated voltage, ampacity =  
x Rated Capacity and KW =  
Rated KW.  
(
)
(
)
Rated Voltage  
2. Any power supply and circuits must be wired and protected in accordance with local codes.  
3. Field wire must be rated at least 75° C.  
4. Field wire must be rated at least 90° C.  
32  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Jobsite  
Connections  
Wiring shown with dashed lines is to be  
furnished and installed by the customer.  
All customer- supplied wiring must be  
copper only and must conform to NEC  
and local electrical codes. Codes may  
require line of sight between disconnect  
switch and unit.  
NOTE:  
1.When electric heater accessory is used  
single point power entry or dual point  
power entry is field optional. Single point  
power entry option is through electric  
heater only.  
TWA050/TWE050  
FieldWiring:  
A
B
C
— 3 power wires. Line voltage.  
— 3 power wires. Line voltage.  
— Heat pump thermostat: 6 wires,  
24 volts.  
— Electric heat: add 2 additional  
wires, 24 volts.  
— 2 wires, 24 volts.  
D
— Outdoor thermostat: add 1  
additional wire per ODT, 24 volts.  
— Electric heat: add 1 additional  
wire, 24 volts.  
(2)TWA050/TWE100B  
FieldWiring:  
A
B
C
— 3 power wires. Line voltage.  
— 3 power wires. Line voltage.  
— Heat pump thermostat: 7 wires,  
24 volts Electric Heat: add 2  
additional wires, 24 volts.  
— 5 wires, 24 volts to outdoor  
section ‘A’’ 2 wires, 24 volts to  
outdoor section ‘’B’’ 2 wires, 24  
volts between outdoor sections  
A’’ ‘’B’’  
— Electric heat: add 1 additional  
wire, 24 volts.  
— Outdoor thermostat: add 1  
additional wire, 24 volt.  
TWA075A/TWE075A;  
TWA100A/TWE100A  
FieldWiring:  
D
— 9 wires, 24 volts.  
— Electric heat: add 4 additional  
wires, 24 volts.  
— Outdoor thermostat: add 3  
additional wires, 24 volts.  
A
B
C
— 3 power wires, line voltage.  
— 3 power wires, line voltage.  
— Heat pump thermostat: 6 wires,  
24 volts.  
D
TWA155B/TWE155B;  
TWA200B/TWE200B  
FieldWiring:  
A
B
C
— Electric heat: add 2 additional  
wires, 24 volts.  
— 6 wires, 24 volts.  
— 3 power wires, line voltage.  
— 3 power wires, line voltage.  
— Heat pump thermostat: 7 wires,  
24 volts.  
— Electric heat: add 2 additional  
wires, 24 volts.  
— 7 wires, 24 volts.  
D
— Outdoor thermostat: add 1  
additional wire, 24 volts.  
— Electric heat: add 1 additional  
wire, 24 volts.  
(2)TWA075A/TWE155B;  
(2)TWA100A/TWE200B  
FieldWiring:  
D
— Electric heat: add 4 additional  
wires, 24 volts.  
A
B
C
— 3 power wires, line voltage.  
— 3 power wires, line voltage.  
— Heat pump thermostat: 7 wires,  
24 volts.  
— Outdoor thermostat: add 1  
additional wire, 24 volts.  
— Electric heat: add 2 additional  
wires, 24 volts.  
TWA-PRC001-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(Heat Pump)  
Heat Pump — Single Compressor  
Typical unit wiring diagram. For specific  
wiring, see individual Service Facts.  
34  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(Heat Pump)  
TWA-PRC001-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(Heat Pump)  
Heat Pump — Dual Compressors  
Typical unit wiring diagram. For specific  
wiring, see individual Service Facts.  
36  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(Heat Pump)  
TWA-PRC001-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical  
Wiring  
(Air Handler)  
Air Handler  
Typical unit wiring diagram. For specific  
wiring, see individual Service Facts.  
38  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Heat Pump)  
Figure DD-1 — TWA075 Heat Pump  
All dimensions are in inches and millimeters.  
Note 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
TWA-PRC001-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Heat Pump)  
Figure DD-2 — 10TonTWA100A Heat Pump  
All dimensions are in inches and millimeters.  
Note 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
40  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Heat Pump)  
Figure DD-3 — TWA155B Heat Pump  
All dimensions are in inches and millimeters.  
Note 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
TWA-PRC001-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Heat Pump)  
Figure DD-4 — TWA200B Heat Pump  
All dimensions are in inches and millimeters.  
Note 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
42  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handler)  
Figure DD-5 — TWE050AAir Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
TWA-PRC001-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handler)  
Figure DD-6 TWE075A Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
44  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handler)  
Figure DD-7—TWE100AAir Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
TWA-PRC001-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handler)  
Figure DD-8TWE100BAir Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
46  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handlers)  
Figure DD-9—TWE050A, 075A, 100A andTWE100BAir Handler  
All dimensions are in inches and millimeters.  
Table DD-1 Air Handler Dimensions — in. (mm)  
Model No.  
TWE050A  
AA  
AB  
AC  
AD  
AE  
AF  
AJ  
AK  
AL  
35 5/8  
(905)  
12 1/16  
1 5/8  
32 1/4  
2 15/16  
(74.6)  
32 1/4  
7 13/16  
12 3/8  
34 9/16  
(878)  
(306.4)  
(41.3)  
(819.2)  
(819.2)  
(198.4)  
(314.3)  
16  
(406.4)  
16  
(406.4)  
16  
(406.4)  
TWE075A  
TWE100A  
TWE100B  
45 1/8  
16  
(406.4)  
16  
(406.4)  
16  
(406.4)  
1 11/16  
41 15/16  
6 5/8  
41 3/4  
7
36 7/8  
(1146.2)  
(42.9)  
(1065.2)  
(168.3)  
(1060.5)  
(177.8)  
(936.6)  
61 1/8  
1 11/16  
57 15/16  
6 5/8  
57 13/16  
7
36 7/8  
(1552.6)  
(42.9)  
(1471.6)  
(168.3)  
(1468.4)  
(177.8)  
(936.6)  
61 1/8  
1 11/16  
57 15/16  
6 5/8  
57 13/16  
7
36 7/8  
(1552.6)  
(42.9)  
(1471.6)  
(168.3)  
(1468.4)  
(177.8)  
(936.6)  
TWA-PRC001-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handler)  
Figure DD-10— TWE155B Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
48  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handlers)  
Figure DD-11 TWE200BAir Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dimensions do not include 1/2”  
(12.7mm) access panel depth.  
2. Removable drain pan and attached drain connection may be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection must be removed to slide drain pan out  
for cleaning. Access plate must be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
removal of pan on drain connection end of unit.  
TWA-PRC001-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Air Handlers)  
Figure DD-12TWE155B and 200BAir Handlers  
All dimensions are in inches and millimeters.  
Table DD-2 Air Handler Dimensions — in. (mm)  
Model No.  
TWE155B  
TWE200B  
A
B
C
D
E
F
G
H
J
77 1/4 (1962.2)  
89 1/4 (2267)  
1 3/16 (30.2)  
1 11/16 (42.9)  
48 (1219.2)  
50 13/16 (1290.6) 11 1/2 (292.1)  
11 7/16 (290.5)  
18 (457.2)  
20 1/8 (511.2)  
3 3/8 (85.7)  
3 1/16 (77.8)  
35 1/16 (890.6)  
39 1/8 (993.8)  
73 7/8 (1876.4)  
82 7/8 (2105)  
3 3/4 (95.3)  
4 9/16 (115.9)  
Table DD-2Air Handler Dimensions — in. (mm) (Continued)  
Model No.  
TWE155B  
TWE200B  
K
L
M
N
P
Q
R
S
T
35 1/16 (890.6)  
39 1/8 (993.8)  
2 13/16 (71.4)  
4 7/8 (123.8)  
18 (457.2)  
20 (508)  
3 9/16 (90.5)  
3 (76.2)  
2 7/8 (73)  
35 1/16 (890.6)  
39 1/8 (993.8)  
3 3/4 (95.3)  
4 9/16 (115.9)  
35 1/16 (890.6)  
39 1/8 (993.8)  
73 3/8 (1863.7)  
82 7/8 (2105)  
4 13/16 (122.2)  
50  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Accessories)  
Figure DD-13— Electric Heater forTWE050, 075, 100Air Handlers  
All dimensions are in inches and millimeters.  
Figure DD-14 — Electric Heater forTWE155 and 200Air Handlers  
TWA-PRC001-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dimensional  
Data  
(Accessories)  
Table DD-3 — Discharge Plenum And Grille  
Dimensions — in. (mm)  
Figure DD-15 — Discharge Plenum and Grille  
All dimensions are in inches and millimeters.  
Model  
Model No.  
A
B
C
TWE050 BAYPLNM015  
TWE075 BAYPLNM016  
TWE100 BAYPLNM017  
3715/16 2115/16  
28  
(963.6) (557.2) (711.2)  
471/2  
(1206.5) (635) (711.2)  
631/2  
25 28  
(1612.9) (635) (711.2)  
25  
28  
Table DD-4 — Discharge Plenum And Grille  
Dimensions — in. (mm)  
For Use with Electric Heat  
Model  
Model No.  
A
B
C
29  
TWE050 BAYPLNM025  
TWE075 BAYPLNM026  
TWE100 BAYPLNM027  
TWE155 BAYPLNM028  
TWE200 BAYPLNM029  
3715/16 2115/16  
(963.6) (557.2) (736.6)  
471/2  
(1206.5) (635) (736.6)  
631/2  
25 29  
(1612.9) (635) (736.6)  
791/2 2711/16  
35  
(2019.3) (703.3) (889)  
921/2  
35  
(2349.5) (773.1) (889)  
25  
29  
307/16  
Table DD-5 — Subbase Dimensions — in.  
(mm)  
Figure DD-16 — Subbase  
Model  
Model No.  
A
B
TWE050 BAYBASE001  
TWE075 BAYBASE002  
TWE100 BAYBASE003  
TWE155 BAYBASE004  
TWE200 BAYBASE005  
38  
22  
(965.2)  
(558.8)  
471/2  
25  
(635)  
(1206.5)  
631/2  
25  
(1612.9)  
(635)  
791/2  
275/8  
(2019.3)  
(701.7)  
921/2  
307/16  
(2349.5)  
(773.1)  
52  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
(Heat Pumps)  
TableW-1 — Unit and CornerWeights — Lbs (Kg)  
Unit  
Shipping  
Net  
CornerWeights  
Model No.  
TWA075A  
Maximum — lbs (Kg) Maximum — lbs (Kg)  
1
2
3
4
390  
343  
(155.6)  
112  
(50.8)  
89  
(40.4)  
63  
(28.6)  
79  
(35.8)  
(176.9)  
TWA100A  
TWA155B  
TWA200B  
468  
414  
146  
106  
68  
94  
(212.3)  
(187.8)  
(66.2)  
(48.1)  
(30.1)  
(42.6)  
816  
(370.1)  
970  
(440.0)  
740  
(335.7)  
885  
(401.4)  
195  
(88.5)  
253  
(114.8)  
186  
(84.4)  
250  
(113.4)  
175  
(79.4)  
190  
(86.2)  
184  
(83.5)  
192  
(87.1)  
TableW-2 AccessoryWeights — Net Lbs (Kg)  
Unit  
RIS  
Steel Spring  
Isolators  
Anti Short  
Coil  
Guard  
Low  
Ambient  
Model No.  
Isolators  
CycleTimer  
Thermostats  
TWA075A  
2
(.9)  
12  
(5.4)  
1
(.5)  
8
(3.6)  
1
(.5)  
23  
(10.4)  
TWA100A  
TWA155B  
TWA200B  
2
12  
1
11  
1
23  
(.9)  
(5.4)  
(.5)  
(5)  
(.5)  
(10.4)  
2
(.9)  
2
(.9)  
12  
(5.4)  
12  
(5.4)  
1
(.5)  
1
(.5)  
22  
(10)  
34  
(15.4)  
1
(.5)  
1
(.5)  
23  
(10.4)  
23  
(10.4)  
TWA155B, 200B  
TWA075A, 100A  
TWA-PRC001-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
(Air Handlers)  
TableW-3 Air Handlers, Coils,And CornerWeights — Lbs (Kg)1  
Unit  
Shipping  
Net  
CornerWeights Vertical  
CornerWeights — Horizontal  
Model No.  
TWE050  
Maximum (lbs)  
Maximum (lbs)  
#1  
59  
(26.8)  
#2  
59  
(26.8)  
#3  
59  
(26.8)  
#4  
59  
(26.8)  
A
54  
(24.5)  
B
64  
(29)  
C
D
54  
(24.5)  
298  
(135)  
262  
(118.9)  
64  
(29.03)  
TWE075  
TWE100  
TWE125  
TWE200  
388  
346  
79  
79  
79  
79  
77  
84  
81  
73  
(176)  
(157)  
(35.9)  
(35.9)  
(35.9)  
(35.9)  
(35)  
(38.1)  
(36.7)  
(33.1)  
473  
(214.6)  
754  
(342)  
886  
(401.9)  
419  
(190.1)  
690  
(313)  
820  
(372)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
102  
(46.3)  
174  
(79)  
185  
(84)  
113  
(51.3)  
156  
(70.8)  
228  
(103.4)  
113  
(51.3)  
190  
(86.2)  
221  
(100.3)  
102  
(46.3)  
170  
(77.1)  
179  
(81.2)  
Note:  
1.  
If application requires steam or hot water heating coils, field supplied isolators must be utilized.  
Vertical  
TWE050, 075, 100  
Vertical  
TWE155, 200  
Horizontal  
TWE050, 075, 100  
Horizontal  
TWE155, 200  
TableW-4AccessoryWeights — Lbs (Kg)  
RIS  
RIS  
Steel Spring Steel Spring  
Discharge  
Plenum  
Discharge  
Plenum  
Electric  
Heat  
Min. Max.  
Isolator  
Floor  
Isolator  
Suspended  
Mount  
Isolator  
Floor  
Isolator  
Suspended  
Mount  
Unit  
Model No.  
Return  
Air Grille  
Oversized  
Motor  
And Grille1  
And Grill2  
Subbase  
Mount  
Mount  
TWE050  
58  
(26.3)  
93  
(42.2)  
3
(1.4)  
32/43  
(14.5/19.5)  
14  
(6.4)  
31  
(14.1)  
2
(.9)  
9
(4)  
12  
(5.4)  
6
(2.7)  
TWE075  
TWE100  
TWE155  
TWE200  
73  
123  
5
27/45  
19  
48  
2
6
12  
6
(33.1)  
(55.8)  
(2.3)  
(12.3/20.4)  
(8.6)  
(21.8)  
(.9)  
(2.7)  
(5.4)  
(2.7)  
92  
(41.7)  
124  
(56.3)  
145  
(65.8)  
156  
(70.8)  
230  
(104.3)  
264  
(119.8)  
7
(3.2)  
10  
(4.5)  
12  
(5.4)  
27/45  
(12.3/20.4)  
79/100  
(35.8/45.4)  
79/100  
(35.8/45.4)  
23  
(10.4)  
27  
(12.3)  
31  
(14.06)  
50  
(22.7)  
80  
(36.3)  
88  
(40)  
2
(.9)  
2
(.9)  
2
(.9)  
7
(3.2)  
7
(3.2)  
9
(4)  
12  
(5.4)  
12  
(5.4)  
12  
(5.4)  
6
(2.7)  
6
(2.7)  
6
(2.7)  
Note:  
1.  
2.  
For use when no heat is supplied.  
For use with electric heat.  
54  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
low evaporator coil temperatures are  
encountered.  
Controls  
Heat Pumps  
Heat pump units shall be completely  
factory wired with necessary controls  
and contactor pressure lugs or terminal  
block for power wiring. Control wiring  
shall be 24-volt control circuit which  
includes fusing and control transformer.  
Units shall provide external location for  
mounting a fused disconnect device.  
Time delay timers to prevent  
General  
Refrigeration System — Dual  
Compressor  
Unit shall be assembled on heavy gauge  
steel mounting/lifting rails and shall be  
weather proofed. Unit shall include a  
hermetic scroll or reciprocating  
compressor(s), plate fin condenser coil,  
fans and motors, controls, and holding  
charge of nitrogen. Operating Range  
shall be between 115° F and 35° F in  
cooling as standard from factory. Unit  
shall be UL 1995 listed and rated in  
accordance with ARI Standard 210/240 or  
340/360.  
TWA155B,TWA200B units shall have  
two separate and independent  
refrigeration circuits. Each refrigeration  
circuit shall have an integral subcooling  
circuit. A refrigeration filter drier shall be  
provided as standard. Unit shall have  
both a liquid line and suction gas line  
service valve with gauge ports.  
compressors in dual compressor units  
from simultaneous start-up and anti-  
recycle timers are available as optional  
accessories.  
Unit shall have twoTrane direct drive,  
hermetic scroll compressors with  
centrifugal oil pump and provide positive  
lubrication to all moving parts. Motor  
shall be suction gas-cooled and shall  
have a voltage utilization range of plus or  
minus 10 percent of nameplate voltage.  
Crankcase heater, discharge line  
thermostat, internal temperature, and  
current-sensitive motor overloads shall  
be included for maximum protection.  
Scroll type compressor shall provide  
inherently low vibration and noise by  
having no suction and discharge valves.  
External high and low pressure cutout  
devices shall be provided. Evaporator  
defrost control provided in indoor  
blower coil shall prevent compressor  
slugging by temporarily interrupting  
compressor operation when low  
evaporator coil temperatures are  
encountered.  
Defrost Controls  
Casing  
Electronic timed initiated, temperature  
terminated defrost system with choice  
of 50, 70, or 90 minute cycle shall be  
included.Timed override limits defrost  
cycle to 10 minutes.  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Units surface shall be tested 500 hours  
in salt spray test. Unit shall have  
removable end panels which allow  
access to all major components and  
controls.  
LowAmbient Operation  
Standard units shall start and operate to  
approximately 35° F (1.7° C) when  
matched withTrane air handlers and  
coils. Optional head pressure control  
accessory permits operation to 0° F  
(-17.8° C).  
Refrigeration System — Single  
Compressor  
ACCESSORIES  
TWA075A,TWA100A units shall have a  
single refrigeration circuit. Each  
LowAmbient Head Pressure Control —  
This accessory shall modulate the RPM  
of unit outdoor fan motor in response  
to outdoor ambient temperatures and  
liquid line temperature. Accessory  
provides unit cooling operation to  
outdoor temperatures of 0° F (-17.8° C).  
refrigeration circuit has an integral  
subcooling circuit. A refrigeration filter  
drier, expansion valve, and check valves  
shall be provided as standard.The unit  
shall have both a liquid line and suction  
gas line service valve with gauge port.  
Condenser Coil  
Coils shall be internally finned or smooth  
bore, 3/8" (10mm) copper tubes  
mechanically bonded to a configured  
aluminum plate fin as standard. Coil  
shall be factory pressure and leak tested  
to 420 psig (2,930 kPa) air pressure.  
Metal grilles with PVC coating for coil  
protection is optional.  
Vibration Isolation Packages This  
accessory shall reduce transmission of  
noise and vibration to building  
structures, equipment, and adjacent  
spaces. Packages shall be available in  
either neoprene-in-shear or spring-flex  
types.  
Unit shall have one direct drive,Trane  
hermetic scroll compressor with  
centrifugal oil pump providing positive  
lubrication to moving parts. Motor shall  
be suction gas-cooled and shall have a  
voltage utilization range of plus or minus  
10 percent of nameplate voltage.  
Time Delay Relay —This accessory  
shall prevent compressors in dual  
compressor unit from coming on line  
simultaneously.Timer shall be 24-volt,  
60 cycle, with four minute timing  
period.  
Crankcase heater, discharge line  
Condenser Fan And Motor(s)  
thermostat, internal temperature, and  
current-sensitive motor overloads shall  
be included for maximum protection.  
Scroll type compressor shall provide  
inherently low vibration and noise by  
having no suction and discharge valves.  
External high and low pressure cutout  
devices shall be provided. Evaporator  
defrost control provided in indoor  
blower coil unit shall prevent  
Direct-drive, statically and dynamically  
balanced, 26 or 28 inch (660 or 711 mm)  
propeller fan(s) with aluminum blades  
and electro-coated steel hubs shall be  
used in draw-through vertical discharge  
position. Either permanently lubricated  
totally enclosed or open construction  
type motors shall be provided and shall  
have built-in current and thermal  
Anti-Short-CycleTimer —This  
accessory shall prevent rapid on-off  
compressor cycling in light load  
conditions by not allowing compressor  
to operate for 5-7 minutes upon  
shutdown.This accessory shall consist  
of a 24-volt, 60 cycle, solid state timing  
device with either 5 or 7 minute fixed-  
off timing period.  
overload protection. Motor(s) shall have  
either ball or sleeve bearing type.  
compressor slugging by temporarily  
interrupting compressor operation when  
TWA-PRC001-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Mechanical  
Specifications  
Condenser Coil Guard — Metal grille  
with PVC coating shall be provided to  
alleviate coil damage.  
internally wye connected on 400 volt,  
three phase. Each 400 volt heater shall  
have automatic line break high limit  
controls.  
internally enhanced copper tubing and  
shall be factory pressure and leak tested  
at 375 psig (2586 kPa). Coil is arranged  
for draw-through airflow and shall  
provide a double sloped condensate  
drain pan constructed of PVC plastic.The  
drain pan shall be removable for  
cleaning.The condensate drain pan can  
be installed in any of four positions  
allowing for vertical or horizontal  
Black Epoxy Coated Condenser Coil —  
This factory installed option is designed  
to provide corrosion protection of air  
cooled condenser coils for seacoast  
application. The black epoxy coil  
protection is a factory applied thermoset  
vinyl coating, bonded to normal  
aluminum fin stock. The uniform  
thickness of the bonded vinyl layer  
exhibits excellent corrosion protection in  
salt spray tests performed in accordance  
with ASTM B177.  
Discharge Plenums and Grilles —  
Accessory discharge plenums shall be  
available for vertical, free discharge  
applications. Plenums shall be  
constructed of heavy-gauge, zinc coated,  
galvanized steel finished with baked  
enamel to match the air handler unit.  
Grilles shall be satin finished aluminum  
and have four-way adjustable louvers.  
application and providing external  
connections on either side of the unit.  
Evaporator Fan  
Double inlet, double width, forward  
curved, centrifugal-type fan(s) with  
adjustable belt drive shall be standard.  
Thermal overload protection shall be  
standard on motor. Fan and motor  
bearings shall be permanently  
lubricated. Oversized motors shall be  
available as an option for high static  
application. All indoor fan motors meet  
the U.S. Energy Policy Act of 1992  
(EPACT)  
ReturnAir Grilles Accessory return air  
grille shall be provided for vertical front,  
free return applications. Grilles shall be  
installed in place of the front lower side  
panel. Grille shall be satin finished  
Air Handlers  
General  
aluminum with non-adjustable louvers.  
Air handler units shall be completely  
factory assembled including coil,  
condensate drain pan, fan motor(s),  
filters, and controls in an insulated  
casing that can be applied in either  
vertical or horizontal configuration. Unit  
shall be rated and tested in accordance  
with ARI standard 210/240 or 340/360.  
Unit shall be UL listed and labeled in  
accordance with UL 1995 for indoor  
blower coil units.  
Mounting Subbase —The accessory  
shall be available for vertical floor mount  
configurations. Subbase shall be  
constructed of heavy gauge, zinc coated,  
galvanized steel with baked enamel  
finish to match air handler unit. Subbase  
is required in the vertical air flow  
application for condensate drain  
trapping and when isolators are  
required.  
Controls  
Magnetic evaporator fan contactor, low  
voltage terminal strip, check valve(s), and  
single point power entry shall be  
included. All necessary controls shall be  
factory-installed and wired. Evaporator  
defrost control shall be included to  
prevent compressor slugging by  
temporarily interrupting compressor  
operation when low evaporator coil  
temperatures are encountered.  
Casing  
Vibration Isolators —This accessory  
shall reduce transmission of noise and  
vibration to building structures,  
equipment, and adjacent spaces.  
Packages shall be available in either  
neoprene-in shear or spring-flex types in  
floor or suspended mountings.  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Casing shall be completely insulated  
with cleanable, foil faced, fire-retardant,  
permanent, odorless, glass fiber  
material. All insulation edges shall be  
either captured or sealed. Knockouts  
shall be provided for unit electrical  
power and refrigerant piping  
Filters  
One inch, throw-away filters shall be  
standard onTWE050A,TWE075A,  
TWE100A andTWE120B model air  
handlers. Filters shall be accessible from  
the side coil access panel. Filter rack can  
be field converted to two inch capability.  
Two inch, throw-away filters shall be  
standard onTWE155B andTWE200B  
models.  
Oversized Motors — Field installed  
oversized motors shall be available for  
high static pressure applications.  
CONTROL OPTIONS  
Standard IndoorThermostats Two  
stage heating and cooling operation or  
one stage heating and cooling  
thermostats shall be available in either  
manual or automatic changeover.  
connections. Captive screws shall be  
standard on all access panels.  
Refrigeration System  
ACCESSORIES  
TheTWE050A,TWE075A,TWE100A units  
shall have a single refrigeration circuit  
and theTWE100B,TWE155B,TWE200B  
units shall have dual refrigeration  
circuits. Each refrigeration circuit is  
controlled by a factory installed thermal  
expansion valve.  
Electric Heaters — UL and CSA  
Programmable Electronic Night Setback  
Thermostat —The option shall provide  
heating setback and cooling setup with 7-  
day programming capability.  
approved electric heat modules shall be  
available for installation directly on fan  
discharge. Electric heaters shall be  
available in a wide range of capacities  
with one or two stage control, single-  
point electric power connection, and  
terminal strip connections. Electric  
heater elements shall be constructed of  
heavy-duty nickel chromium elements  
OutdoorThermostat —This option shall  
provide staging control of electric  
heaters based on a set outdoor  
temperature.  
Evaporator Coil  
Configured aluminum fin surface shall  
be mechanically bonded to 3/8" (10 mm)  
56  
TWA-PRC001-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File Number  
TWA-PRC001-EN  
PL-UN-TWA-PRC001-EN-07-00  
TWA-PRC001-EN-05/98  
TheTrane Company  
Supersedes  
An American Standard Company  
Stocking Location  
Inland - LaCrosse  
For more information contact your  
local distributor (dealer), local district  
office, or e-mail us at  
SinceTheTrane Company has a policy of continuous product and product data improvement, it reserves the  
right to change design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Toshiba Copier GD 1060 User Manual
Toshiba DVD Recorder SD R5272 User Manual
Trane Thermostat TCONT401AN21MA User Manual
Transcend Information Digital Photo Frame PF810 User Manual
Troy Bilt Lawn Mower 13074 GTX 18 User Manual
Troy Bilt Lawn Mower T 439 User Manual
Vizio Home Theater Screen VHT215 User Manual
Waring Yogurt Maker YM350 User Manual
Wayne Septic System 332200 001 User Manual
Weber Gas Grill 43720 User Manual