Trane Heat Pump SSP PRC002 EN User Manual

Split System Heat Pumps  
Split System Heat Pumps  
TWA075A-TWA200B  
Air Handlers  
TWE050A-TWE200B  
50 Hz  
October 2003  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Contents  
Introduction  
2
4
6
Features and Benefits  
Application Considerations  
Selection Procedure  
7
8
9
Model Number Description  
General Data  
Performance Data  
12  
Cool and Heat Performance  
Fan Performance  
12  
24  
31  
Electric Power  
Connection and Wiring  
Dimension and Weights  
Mechanical Specifications  
33  
39  
55  
SSP-PRC002-EN  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Heat Pumps  
Air Handlers  
Low voltage terminal board  
• Expansion valve(s)  
• Convertible  
• PVC double-sloped, removeable drain  
pan  
• 3-D® Scroll compressors  
• ModelTWA155-200B have dual  
compressors with independent  
refrigerant circuits  
• Compressor motor overload protection  
• Control transformer  
• Fan relay  
• High and low pressure cut-out  
switches  
• Efficient evaporator coil  
• Baked enamel finish  
• Filter access panel  
• 1” (25.4 mm) throwaway filters  
standard with provisions for field  
supplied 2”  
Liquid line filter drier, factory installed  
• Holding charge of dry nitrogen  
• Copper tube, aluminum plate fin coils  
Low ambient cooling to 35°F (1.7°C) as  
manufactured  
(50.8 mm) filters  
• Weather resistant baked enamel finish  
• Heavy gauge steel cabinet  
• Mounting/lifting rails under base  
• Adjustable belt drive motor  
• Single point power entry to electric  
heaters  
• Refrigerant piping and/or electrical  
connections provided from either side  
Odysseyair handler versatility is further  
increased by a complete line of optional  
accessories designed to match and easy  
to install:  
• Discharge Plenum and Grille  
• Return Grille  
All condensing units offer these optional  
accessories:  
• Head Pressure Control — Low Ambient  
CoolingTo 0°F (-17.8°C)  
• Coil Guards Kits  
Isolators both Rubber-in-Shear and  
SpringType  
• Anti-Short-Cycle Kit  
• Time Delay Relay  
• Subbase  
• Electric Heaters  
• High Static Evaporator Motor  
Isolators both Rubber-in-Shear and  
SpringType  
4
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Features and  
Benefits  
Heat Pump Options  
Trane split systems have been specified  
in thousands of applications and youll  
find Odyssey will win you even more  
jobs with it’s smaller, more manageable  
cabinet.  
Odyssey air handler versatility is further  
increased by a complete line of  
accessories designed to match and  
install smoothly:  
• Discharge Plenum and Grille  
• Return Grille  
• Subbase  
• Electric Heaters  
• High Static Evaporator Motor  
Isolators both Rubber-in-Shear and  
SpringType  
The Odysseysplit system product line  
includes heat pumps in both single and  
dual compressor options.  
TWA075A and TWA100A single  
compressor models feature single  
refrigeration circuitry lowering job  
installation costs by requiring only one  
set of refrigerant lines.These units are  
ideal for low cost, new construction jobs  
as well as renovation and replacement  
buildings.  
Air Handlers Offer More Flexibility  
Flexibility is a key to meeting changing  
market requirements. Odyssey split  
systems offer various compressor  
options and convertible air handlers.The  
air handlers can be installed either  
vertically in a mechanical room or  
horizontally above a ceiling. And it  
doesnt require any removal of panels or  
reconfiguration of the drain pan to make  
either airflow application work. All the air  
handlers feature factory installed belt  
drive and ball bearing evaporator fans  
with adjustable sheaves for maximum  
airflow performance.The standard motor  
on the TWE100A air handler will deliver  
3325 cfm (5650 m3/h) at 0.8” (200 Pa)  
ESP. Plus oversized motors are available  
for higher static applications.  
• A Full Line of Thermostats  
In addition, Odyssey modelsTWA155B  
throughTWA200B are dual compressor  
units that give true standby protection; if  
one compressor fails, the second will  
automatically start-up. Also, the first  
compressor can be serviced without  
shutting down the unit since refrigerant  
circuits are independent.  
Odyssey— A Complete Split System  
Odyssey delivers the flexibility to select a  
complete system that meets your  
particular job requirements. Air Handlers  
are designed, tested and rated with  
condensing units to let you select the  
proper match between capacity and  
load. Condensing units can also be  
matched withTrane built-up air handlers.  
These matched systems can be quickly  
engineered for specific applications.  
Dual compressors are not just for  
protection, they also save energy costs.  
Most buildings are designed for the peak  
load requirements yet the building  
usually operates at less than peak load.  
During light load conditions only one  
compressor functions to maintain the  
space comfort thus reducing the need  
for energy.  
Low Ambient Cooling Operation  
Each condensing unit can operate to  
35°F (1.7°C) as standard. An accessory  
Head Pressure Control gives you the  
capability to operate to 0°F (-17.8°C). All  
condensing units offer these accessories:  
• Head Pressure Control  
• Coil Guard Kits  
Isolators both Rubber-in-Shear and  
SpringType  
• Anti-Short-Cycle Kit  
• Time Delay Relay  
SSP-PRC002-EN  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application  
Considerations  
Application of this product should be  
within the catalogued airflow and  
performance considerations.  
Low Ambient Cooling  
As manufactured, these units can  
operate to 35°F (1.7°C) in the cooling  
mode of operation. An accessory head  
pressure control will allow operation to  
0°F (-17.8°C) outdoor ambient. When  
using these units with control systems  
such as bypass changeover Variable Air  
Volume, consider the requirement for a  
head pressure control to allow low  
ambient cooling.  
Clearance Requirements  
The recommended clearances identified  
with unit dimensions should be  
maintained to assure adequate  
serviceability, maximum capacity and  
peak operating efficiency. Actual  
clearances that appear inadequate  
should be reviewed with the localTrane  
Representative.  
Typical Horizontal Air Handler Application  
TypicalVertical Air Handler Application  
Typical Split System Application  
6
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Selection  
Procedure  
Cooling Capacity  
External Static  
Standard Filter  
Supplementary Electric Heat  
0.23 in (57 Pa)  
0.77 in (193 Pa)  
0.10 in (25 Pa)  
a
Step 1 — Calculate the buildings total  
and sensible cooling loads at design  
conditions. Use theTrane calculation  
form or any other standard accepted  
method.  
Total Heating Load: 110 MBh (32.2 kW)  
b
Outdoor Ambient (Winter): 17°F  
(-8.3°C) DB  
Total Static Pressure 1.10 in (275 Pa)  
c
Indoor ReturnTemperature: 70°F  
(21.1°C) DB  
Step 2 — Size the equipment usingTable  
PD-1. Match the cooling loads at design  
conditions.  
Note:The Evaporator Fan Performance  
Table has included the effect of a 1 in.  
(250 Pa) filter already.Therefore, the  
actualTotal Static Pressure is 1.10 - 0.10 =  
1.00 in. (275 - 25 = 250 Pa).  
With 2500 cfm (4247 m3/h) and 1.00  
inches (250 Pa),Table 26-1 shows a 1.07  
bhp (0.8 kW).  
d
Airflow: 2500 cfm (4247 m3/h)  
Example:The following are the building  
cooling requirements  
Table PD-9 indicates the mechanical  
heating portion of the heat pump will  
provide 37.5 MBh (11.0 kW) for the winter  
design conditions.  
a
Electrical Characteristics: 380-415/50/3  
b
Summer Design Conditions: Entering  
Evaporator Coil: 80 DB/67 WB  
(27 DB/19WB°C)  
Outdoor Ambient: 95°F (35° C)  
Step 3 — Because 37.5 MBh (11.0 kW) is  
less than the buildings required heating  
capacity, a supplementary heater must  
be selected. 110 - 37.5 = 72.5 MBh (32.2 -  
11.0 = 21.2 kW) minimum heater capacity.  
Note:The formula below the table can be  
used to calculate Fan Motor Heat,  
Constant x Motor Power =  
Fan Motor Heat  
c
3.5 x bhp  
3.5 x 1.07  
= MBh  
= 3.75 MBh  
Total Cooling Load: 75 MBh (22kW)  
From Table PD-25, the 24.22 kW heater  
has a capacity of 82,670 Btu. From Table  
34-1, the 24.22 kW heater at 400V  
indicates the heater model number is  
BAYHTRL435A.This heater will be  
adequate to cover the residual heat  
capacity needed for the application.  
d
1.375 x (kW) = kW  
1.375 x 0.8 = 1.1 kW  
Sensible Cooling Load: 53 MBh  
(15.5 kW)  
e
NetTotal Cooling Capacity  
= 79.6 MBh – 3.75 = 75.85 MBh  
= 23.3 kW - 1.1 = 22.2 kW  
Net Sensible Cooling Capacity  
= 57.1 MBh – 3.75 = 53.35 MBh  
= 16.7 MBh - 1.1 = 15.6 kW  
Airflow: 2500 cfm (4247 m3/h)  
External Static Pressure: 0.77 in. wg  
(193 Pa)  
Air Delivery Selection  
External static pressure drop through the  
air distribution system has been  
Table PD-1 shows that a TWA075A  
matched with a TWE075A has a gross  
cooling capacity of 82.4 MBh (24.1 kW)  
and 59.5 MBh (17.4 kW) sensible capacity  
at 95 DB (35°C) ambient and 2500 cfm  
(4247 m3/h) and 80 DB/67 WB (27 DB/19  
WB) air entering the evaporator.  
Heating Capacity  
calculated to be 0.77 inches (192.5 Pa) of  
water gauge. From Table PD-24 static  
pressure drop through the electric heater  
is 0.12 inches (30 Pa) of water (0.77 + 0.12  
= .89 in.) (192.5 + 30 = 222.5 Pa). Enter  
Table PD-15 forTWE090A4 at 2500 cfm  
(4247 m3/h) and .90 in. (225 Pa) static  
pressure.The standard motor at 790 rpm  
will give the desired airflow.  
Step 1 — Calculate the building heating  
load using the Trane calculation form or  
any other standard accepted method.  
Step 2 — Size the equipment usingTable  
PD-9 to match the heating loads at  
design conditions.The following are  
building heating requirements:  
To find the net cooling capacities, fan  
motor heat must be subtracted.  
Determine the total unit static pressure:  
SSP-PRC002-EN  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model  
Num ber  
Description  
Split System Heat Pump Model Nomenclature  
T
W
A
0
7
5
A
D
0
0
D
A
1
2
3
4
5
6
7
8
9
10  
11  
12  
Digit 8 - Electrical Characteristics  
Digits 1, 2, 3 - Product Type  
TWA = Split System Heat Pump  
D = 380-415/3/50  
Digits 9, 10 - Factory - Installed Options  
Digits 4, 5, 6 - Nominal Gross Cooling Capacity  
(MBh)  
00 = No Options  
0S = Black Epoxy Coated Coil  
075 = 75  
100 = 100  
155 = 155  
200 = 200  
Digit 11- Minor Design Sequence  
D = Fourth  
Digit 12- Service Digit  
Digit 7- Major Development Sequence  
A = First  
A = Single Compressor  
B = Dual Compressor  
Air Handler Model Nomenclature  
T
W
E
0
5
0
A
D
0
0
C
A
1
2
3
4
5
6
7
8
9
10  
11  
12  
Digit 8 - Electrical Characteristics  
Digits 1, 2, 3 - Product Type  
D = 380-415/3/50  
TWE = Cooling Convertible  
Digit 9, 10 - Factory - Installed Options  
00 = No Options  
Digits 4, 5, 6 - Nominal Gross Cooling  
Capacity (MBh)  
Digit 11- Minor Design Sequence  
C = Third  
050 = 50  
075 = 75  
100 = 100  
155 = 155  
200 = 200  
Digit 12- Service Digit  
A = First  
Digit 7- Refrigerant Circuit  
A = Single  
B = Dual  
8
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(Heat Pum ps)  
Table GD-1 General Data Heat Pumps  
TWA075A  
TWA100A  
Cooling Perform ance1  
Gross Cooling Capacity, Btu (kW)  
Matched Air Handler, Btu (kW)  
Heat Pump Only2, Btu (kW)  
ARI Net Cooling Capacity3  
System Power kW  
Heat Pump Only Power kW  
Heating Perform ance  
ARI Heating with Matched Air Handler  
High Temperature Capacity, Btu (kW)  
Low Temperature Capacity, Btu (kW)  
Com pressor  
82,000 (23.97)  
109,000 (31.97)  
105,000 (30.75)  
105,000 (30.75)  
10.32  
82,000 (23.97)  
80,000 (23.35)  
7.36  
6.61  
9.22  
75,000 (21.82)  
47,000 (13.84)  
106,000 (31.05)  
69,000 (20.29)  
Number  
Type  
1
1
3D®Scroll  
3D®Scroll  
No. Speeds  
No. Motors  
1
1
1
1
Motor HP (kW)  
Motor RPM  
ARI Sound Rating (Bels)4  
System Data5  
6.25 (4.7)  
2875  
8.8  
8.33 (6.21)  
2875  
8.8  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Outdoor Coil —Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft (m2)  
Rows  
1
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
19.2 (1.78)  
2
1
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
24.0 (2.23)  
2
Fins Per Inch (Fins per mm)  
Outdoor Fan Type  
No. Used  
18 (457)  
Propeller  
1
18 (457)  
Propeller  
1
Diameter, in. (mm)  
DriveType  
26.00 (660.4)  
Direct  
28.00 (711)  
Direct  
No. Speeds  
1
1
CFM6, (m3/h)  
4700 (7985)  
1
6700 (11382)  
1
No. Motors  
Motor HP (kW)  
Motor RPM  
0.33 (.24)  
925  
18.0 (8.16)  
0.75 (.56)  
925  
24.25 (11.0)  
R-22 Refrigerant Charge, lb7 (kg)  
Notes:  
1. Cooling Perform ance is rated at 95°F (35°C) am bient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet  
bulb and nom inal cfm listed. ARI rating cfm is 350 cfm /ton for this product. Gross capacity does not include the  
effect of fan m otor heat. ARI capacity is net and includes the effect of fan m otor heat. Units are suitable for  
operation to ±20% of nom inal cfm . Rated accordance with ARI Standard 210.  
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.2°C) saturated suction tem perature and at 95°F  
(35°C) am bient.  
3. ARI Net Cooling Capacity is calculated with m atched blower coil and 25 ft (7.2 m ) of 1.375, 0.500 OD interconnect-  
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated  
Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) am bient, 80°F (26.7°C)  
entering dry bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm .  
4. ARI Sound Rating is rated in accordance with ARI Standard 270.  
5. System Data based on m axim um linear length 80 ft (26.7 m ). Maxim um lift: suction 60 ft (18.3 m ) liquid 60 ft (18.3  
m ). For greater lengths, refer to refrigerant piping applications m anual.  
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.  
7. Refrigerant (operating) charge is for condensing unit (all circuits) with m atching blower coils and 25 ft (7.6 m ) of  
interconnecting refrigerant lines.  
SSP-PRC002-EN  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(Heat Pum ps)  
Table GD-2 General Data Heat Pumps  
TWA155B  
TWA200B  
Cooling Perform ance1  
Gross Cooling Capacity, Btu (kW)  
Matched Air Handler, Btu (kW)  
Condensing Unit Only2, Btu (kW)  
ARI Net Cooling Capacity3  
System Power kW  
Condensing Unit Power kW  
Heating Perform ance  
ARI Heating with Matched Air Handler  
High Temperature Capacity, Btu (kW)  
LowTemperature Capacity, Btu (kW)  
Com pressor  
166,000 (48.57)  
216,000 (63.24)  
209,000 (61.18)  
196,000 (61.18)  
20.61  
161,000 (47.04)  
160,000 (46.74)  
14.98  
13.20  
18.52  
151,000 (44.27)  
95,000 (27.67)  
206,000 (60.26)  
135,000 (39.66)  
Number  
Type  
2
2
3D®Scroll  
3D®Scroll  
No. Speeds  
No. Motors  
1
2
1
2
Motor HP  
6.25 (4.7)  
2875  
8.8  
8.33 (6.21)  
2875  
8.8  
Motor RPM, (kW)  
ARI Sound Rating (Bels)4  
System Data5  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Outdoor Coil —Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft (m 2)  
Rows  
2
2
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
48.0 (4.46)  
2
1.375 (34.9)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
38.4 (3.57)  
2
Fins Per Inch(mm)  
Outdoor Fan Type  
No. Used  
18 (457)  
Propeller/Propeller  
18 (457)  
Propeller/Propeller  
2
2
Diameter, in. (mm)  
DriveType  
No. Speeds  
CFM6, (m3/h)  
26.00/26.00 (660.4/660.4)  
28.00/28.00 (711/711)  
Direct/Direct  
1
13400 (22764)  
2
Direct/Direct  
1
9800 (16649)  
2
No. Motors  
Motor HP (kW)  
0.33 (.24)  
925  
36.0 (16.32)  
0.75 (.56)  
925  
48.5 (22.0)  
Motor RPM  
R-22 Refrigerant Charge, lb7 (kg)  
Notes:  
1. Cooling Perform ance is rated at 95°F (35°C) am bient, 80°F (26.7°C) entering dry bulb, 67°F (19.4°C) entering wet  
bulb and nom inal cfm listed. ARI rating cfm is 350 cfm /ton for this product. Gross capacity does not include the  
effect of fan m otor heat. ARI capacity is net and includes the effect of fan m otor heat. Units are suitable for  
operation to ±20% of nom inal cfm . Rated accordance with ARI Standard 210.  
2. Condensing Unit Only Gross Cooling Capacity rated at 45°F (7.6°C) saturated suction tem perature and at 95°F  
(35°C) am bient.  
3. ARI Net Cooling Capacity is calculated with m atched blower coil and 25 ft (7.6 m ) of 1.375, 0.500 OD interconnect-  
ing tubing. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures. Integrated  
Part Load Value is based on ARI Standard 210/240/340. Units are rated at 80°F (26.7°C) am bient, 80°F (26.7°C)  
entering dry bulb, and 67°F (19.4°C) entering wet bulb at ARI rated cfm .  
4. ARI Sound Rating is rated in accordance with ARI Standard 270.  
5. System Data based on m axim um linear length 80 ft (26.7 m )Maxim um lift: suction 60 ft (18.3 m ) liquid 60 ft (18.3  
m ) For greater lengths, refer to refrigerant piping applications m anual.  
6. Outdoor Fan cfm is rated with standard air-dry coil outdoor.  
7. Refrigerant (operating) charge is for condensing unit (all circuits) with m atching blower coils and 25 ft (7.6 m ) of  
interconnecting refrigerant lines.  
10  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
General  
Data  
(Air Handlers)  
Table GD-3 General Data Air Handlers  
TWE050A  
TWE075A  
TWE100A  
TWE100B  
System Data 1  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Indoor Coil —Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft (m2)  
Rows  
1
1
1
2
1.120 (28.4)  
0.38 (9.7)  
Plate Fin  
0.375 (9.5)  
5.00 (.47)  
3
1.380 (35.0)  
0.50 (12.7)  
Plate Fin  
0.375 (9.5)  
8.07 (.75)  
3
1.380 (35.0)  
0.50 (12.7)  
Plate Fin  
0.375 (9.5)  
11.18 (1.0)  
3
1.380 (35.0)  
0.50 (12.7)  
Plate Fin  
0.375 (9.5)  
11.18 (1.0)  
3
Fins Per Inch  
12  
12  
12  
12  
Refrigerant Control  
Drain Connection No.  
Expansion Valve Expansion Valve Expansion Valve Expansion Valve  
4
4
4
4
Drain Connection Size, in. (mm) 0.75 (19.0)  
0.75 (19.0)  
PVC  
0.75 (19.0)  
PVC  
0.75 (19.0)  
PVC  
Drain Connection Type  
Indoor Fan Type  
No. Used  
PVC  
FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal  
1
1
15.0 (381)  
15.0 (381)  
Belt  
1
15.0 (381)  
15.0 (381)  
Belt  
1
15.0 (381)  
15.0 (381)  
Belt  
Diameter, in. (mm)  
Width, in. (mm)  
Drive Type  
12.0 (304.8)  
12.0 (304.8)  
Belt  
No. Speeds  
1
1
1
1
CFM, (m3/h)  
1670 (2837)  
1
2500 (4247)  
1
3325 (5649)  
1
3325 (5649)  
1
No. Motors  
Motor HP (kW)  
— Standard/Oversized  
0.75/1.0 (.55/.74) 1.0/1.5 (.74/1.11) 1.5/2.0 (1.11/1.49) 1.5/2.0 (1.11/1.49)  
Motor RPM (Standard)  
Motor Frame Size (Standard)  
Filters —Type  
Furnished  
1425  
1425  
56  
Throw aw ay  
1425  
56  
Throw aw ay  
1425  
56  
Throw aw ay  
56  
Throw aw ay  
Yes  
Yes  
3
Yes  
4
Yes  
4
No.  
1/1  
Recommended Size, in. (mm) 16x20x1/20x20x1  
406.4x508x25.  
16x25x1  
406.4/635/25.4  
16x25x1  
406.4/635/25.4  
16x25x1  
406.4/635/25.4  
4/508x508x25.4  
Table GD-3 General Data Continued  
TWE155B  
TWE200B  
System Data  
No. Refrigerant Circuits  
Suction Line, in. (mm) OD  
Liquid Line, in. (mm) OD  
Indoor Coil —Type  
Tube Size, in. (mm) OD  
Face Area, sq. ft (m2)  
Rows  
2
2
1.38 (35.0)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
1.38 (35.0)  
0.500 (12.7)  
Plate Fin  
0.375 (9.5)  
16.33 (1.52)  
21.63 (2.01)  
3
3
Fins Per Inch  
12  
12  
Refrigerant Control  
Drain Connection No.  
Drain Connection Size, in. (mm)  
Drain Connection Type  
Indoor Fan Type  
No. Used  
Diameter, in. (mm)  
Width, in. (mm)  
Drive Type  
Expansion Valve  
Expansion Valve  
4
4
1.000 (25.4)  
PVC  
FC Centrifugal  
1.000 (25.4)  
PVC  
FC Centrifugal  
2
15.0 (381)  
15.0 (381)  
Belt  
2
15.0 (381)  
15.0 (381)  
Belt  
No. Speeds  
1
1
CFM, (m3/h)  
5000 (8494)  
1
6650 (11297)  
1
No. Motors  
Motor HP (kW)  
— Standard/Oversized  
2.0/3.0 (1.49/2.24)  
3.0/5.0 (2.24/3.72)  
Motor RPM (Standard)  
Motor Frame Size (Standard)  
Filters —Type  
Furnished  
No.  
1425  
145T  
Throw aw ay  
1425  
184T  
Throw aw ay  
Yes  
Yes  
8
4/4  
Recommended Size, in. (mm)  
15x20x2  
381x508x50.8  
16x20x2/16x25x2  
406.4x508x50.8/406.4x635x50.8  
Notes:  
1. ARI certified with various condensing units per ARI Standard 210. Refer to Perform ance Data section in this catalog.  
SSP-PRC002-EN  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-1 — Gross Cooling Capacities (MBh) TWA075A Heat Pump with TWE075A Air Handler (I-P)  
Ambient Temperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
CFM  
2250  
(°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75  
80  
85  
90  
75.7 60.5 83.8 50.3 92.4 34.1 73.2 59.2 80.9 49.1 89.1 32.9 70.2 57.7 77.5 47.8 85.3 31.6 66.7 56.0 73.6 46.2 81.1 30.2  
76.2 70.8 84.0 58.2 92.4 44.8 73.7 69.5 81.1 57.0 89.1 43.6 70.8 68.1 77.6 55.4 85.4 42.2 67.5 66.4 73.8 53.8 81.2 40.7  
78.3 78.3 84.1 68.4 92.5 55.4 76.1 76.1 81.2 67.1 89.3 54.2 73.6 73.6 77.8 65.6 85.5 52.8 70.6 70.6 74.0 63.9 81.4 51.3  
82.3 82.3 84.6 78.7 92.7 65.9 80.0 80.0 81.8 77.5 89.4 64.5 77.4 77.4 78.6 76.0 85.6 63.0 74.3 74.3 75.0 74.4 81.5 61.4  
2500  
2750  
3000  
75  
80  
85  
90  
77.2 63.4 85.3 49.5 93.9 34.7 74.6 62.1 82.3 48.2 90.5 33.6 71.4 60.5 78.8 46.8 86.6 32.2 67.8 58.8 74.8 45.2 82.2 30.6  
77.9 74.7 85.5 61.0 93.9 46.4 75.4 73.4 82.4 59.5 90.5 45.1 72.4 72.0 78.9 58.0 86.7 43.7 68.9 68.9 75.0 56.3 82.4 42.2  
80.9 80.9 85.6 72.0 94.1 57.9 78.6 78.6 82.6 70.7 90.7 56.7 75.9 75.9 79.2 69.2 86.8 55.3 72.8 72.8 75.3 67.5 82.6 53.7  
85.0 85.0 86.4 83.4 94.1 69.1 82.7 82.7 83.6 82.1 90.8 67.8 79.8 79.8 79.9 79.9 87.0 66.3 76.6 76.6 76.7 76.7 82.7 64.7  
75  
80  
85  
90  
78.5 66.1 86.5 51.2 95.1 35.3 75.7 64.8 83.4 49.9 91.6 34.1 72.5 63.2 79.8 48.4 87.6 32.7 68.9 61.5 75.8 46.8 83.1 31.1  
79.4 78.5 86.6 63.4 95.2 47.8 76.5 76.5 83.6 62.0 91.7 46.6 73.8 73.8 80.0 60.5 87.7 45.2 70.7 70.7 75.9 58.8 83.3 43.6  
83.1 83.1 86.9 75.4 95.3 60.3 80.7 80.7 83.9 74.1 91.8 59.0 77.9 77.9 80.4 72.6 87.9 57.6 74.6 74.6 76.5 70.9 83.5 55.8  
87.4 87.4 88.1 87.9 95.4 72.3 84.9 84.9 85.0 85.0 92.0 71.0 82.0 82.0 82.0 82.0 88.0 69.5 78.6 78.6 78.7 78.7 83.7 67.8  
75  
80  
85  
90  
79.5 68.8 87.6 52.8 96.1 35.8 76.8 67.4 84.4 51.5 92.5 34.5 73.5 65.9 80.7 50.0 88.4 33.1 69.8 64.1 76.6 48.4 83.9 31.5  
80.7 80.7 87.7 65.8 96.2 49.2 78.3 78.3 84.6 64.4 92.6 47.9 75.4 75.4 80.9 62.8 88.6 46.5 72.2 72.2 76.8 61.1 84.1 45.0  
85.1 85.1 88.1 78.8 96.4 62.6 82.6 82.6 85.0 77.4 92.7 61.1 79.6 79.6 81.5 75.9 88.7 59.6 76.3 76.3 77.5 74.2 84.3 58.0  
89.5 89.5 89.6 89.6 96.5 75.4 86.9 86.9 87.0 87.0 93.0 74.1 83.8 83.8 83.9 83.9 89.0 72.5 80.4 80.4 80.5 80.5 84.6 70.9  
Note: All tem peratures are in degrees Fahrenheit. Airflow is in cfm .  
Table PD-1— Gross Cooling Capacities (kW) TWA075A Heat Pump with TWE075A Air Handler (SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
m3/h  
3823  
(°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
24  
27  
29  
32  
22.2 17.7 24.5 14.7 27.1 10.0 21.4 17.3 23.7 14.4 26.1 9.6 20.5 16.9 22.7 14.0 25.0 9.3 19.5 16.4 21.6 13.5 23.7 8.8  
22.3 20.7 24.6 17.0 27.1 13.1 21.6 20.4 23.7 16.7 26.1 12.8 20.7 19.9 22.7 16.2 25.0 12.4 19.8 19.5 21.6 15.7 23.8 11.9  
22.9 22.9 24.6 20.0 27.1 16.2 22.3 22.3 23.8 19.6 26.1 15.9 21.5 21.5 22.8 19.2 25.0 15.5 20.7 20.7 21.7 18.7 23.8 15.0  
24.1 24.1 24.8 23.1 27.1 19.3 23.4 23.4 23.9 22.7 26.2 18.9 22.7 22.7 23.0 22.3 25.1 18.5 21.8 21.8 22.0 21.8 23.9 18.0  
4248  
4673  
5098  
24  
27  
29  
32  
22.6 18.6 25.0 14.5 27.5 10.2 21.8 18.2 24.1 14.1 26.5 9.8 20.9 17.7 23.1 13.7 25.3 9.4 19.9 17.2 21.9 13.2 24.1 9.0  
22.8 21.9 25.0 17.9 27.5 13.6 22.1 21.5 24.1 17.4 26.5 13.2 21.2 21.1 23.1 17.0 25.4 12.8 20.2 20.2 21.9 16.5 24.1 12.4  
23.7 23.7 25.1 21.1 27.5 17.0 23.0 23.0 24.2 20.7 26.6 16.6 22.2 22.2 23.2 20.2 25.4 16.2 21.3 21.3 22.1 19.8 24.2 15.7  
24.9 24.9 25.3 24.4 27.6 20.2 24.2 24.2 24.5 24.0 26.6 19.9 23.4 23.4 23.4 23.4 25.5 19.4 22.4 22.4 22.5 22.5 24.2 18.9  
24  
27  
29  
32  
23.0 19.4 25.3 15.0 27.8 10.3 22.2 19.0 24.4 14.6 26.8 10.0 21.2 18.5 23.4 14.2 25.6 9.6 20.2 18.0 22.2 13.7 24.3 9.1  
23.3 23.0 25.4 18.5 27.9 14.0 22.4 22.4 24.5 18.2 26.8 13.6 21.6 21.6 23.4 17.7 25.7 13.2 20.7 20.7 22.2 17.2 24.4 12.8  
24.3 24.3 25.4 22.1 27.9 17.6 23.6 23.6 24.6 21.7 26.9 17.3 22.8 22.8 23.5 21.3 25.7 16.9 21.9 21.9 22.4 20.8 24.4 16.3  
25.6 25.6 25.8 25.7 27.9 21.2 24.9 24.9 24.9 24.9 26.9 20.8 24.0 24.0 24.0 24.0 25.8 20.3 23.0 23.0 23.0 23.0 24.5 19.9  
24  
27  
29  
32  
23.3 20.1 25.6 15.5 28.1 10.5 22.5 19.7 24.7 15.1 27.1 10.1 21.5 19.3 23.6 14.6 25.9 9.7 20.4 18.8 22.4 14.2 24.6 9.2  
23.6 23.6 25.7 19.3 28.2 14.4 22.9 22.9 24.8 18.9 27.1 14.0 22.1 22.1 23.7 18.4 25.9 13.6 21.1 21.1 22.5 17.9 24.6 13.2  
24.9 24.9 25.8 23.1 28.2 18.3 24.2 24.2 24.9 22.7 27.1 17.9 23.3 23.3 23.8 22.2 26.0 17.5 22.3 22.3 22.7 21.7 24.7 17.0  
26.2 26.2 26.2 26.2 28.2 22.1 25.4 25.4 25.5 25.5 27.2 21.7 24.5 24.5 24.6 24.6 26.0 21.2 23.5 23.5 23.6 23.6 24.8 20.8  
Note: All tem peratures are in degrees Celsius. Airflow is in liters per second.  
12  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-2 — Gross Cooling Capacities (MBh) TWA100A Heat Pump with TWE100A Air Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
CFM  
3000  
(°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75  
80  
85  
90  
101.6 80.9 111.8 67.1 122.7 45.2 97.7 79.0 107.6 65.4 118.1 43.6 93.6 76.9 103.2 63.6 113.2 41.9 89.4 74.8 98.6 61.7 108.2 40.1  
102.1 94.6 112.0 77.2 122.7 59.2 98.4 92.6 107.8 75.3 118.0 57.5 94.4 90.6 103.4 73.5 113.2 55.7 90.4 88.6 98.8 71.5 108.2 53.8  
104.6 104.6 112.1 90.6 122.8 72.8 101.3 101.3 107.9 88.7 118.2 71.1 97.9 97.9 103.5 86.7 113.4 69.3 94.3 94.3 98.9 84.6 108.4 67.4  
109.6 109.6 112.7 104.1 122.9 86.4 106.3 106.3 108.6 102.2 118.3 84.6 102.8 102.8 104.4 100.2 113.5 82.8 99.1 99.1 100.1 98.2 108.5 80.7  
3325  
3650  
3975  
75  
80  
85  
90  
103.4 84.5 113.7 65.6 124.6 46.0 99.4 82.5 109.4 63.8 119.8 44.4 95.2 80.5 104.8 61.9 114.8 42.7 90.9 78.3 100.1 59.9 109.6 40.8  
104.3 99.5 113.9 80.6 124.6 61.1 100.4 97.5 109.5 78.7 119.8 59.3 96.4 95.5 104.8 76.6 114.9 57.5 92.0 92.0 100.2 74.6 109.7 55.6  
107.8 107.8 114.0 95.0 124.7 75.9 104.4 104.4 109.6 93.1 120.0 74.1 100.8 100.8 105.2 91.1 115.0 72.3 97.0 97.0 100.6 89.0 109.9 70.4  
113.0 113.0 114.9 109.8 124.8 90.6 109.5 109.5 110.8 107.9 120.0 88.6 105.8 105.8 106.5 105.9 115.1 86.7 102.0 102.0 101.9 101.9 110.0 84.7  
75  
80  
85  
90  
105.0 88.0 115.3 67.7 126.1 46.8 100.9 85.9 110.8 65.8 121.2 45.0 96.6 83.9 106.1 63.9 116.1 43.2 92.2 81.7 101.3 62.0 110.8 41.3  
106.2 104.2 115.4 83.8 126.1 62.8 102.3 102.3 110.9 81.7 121.3 61.1 98.0 98.0 106.2 79.7 116.2 59.2 94.3 94.3 101.4 77.6 111.0 57.4  
110.6 110.6 115.6 99.3 126.3 78.8 107.0 107.0 111.2 97.3 121.4 77.0 103.3 103.3 106.7 95.3 116.4 75.2 99.4 99.4 102.0 93.3 111.1 73.3  
115.9 115.9 117.0 115.4 126.3 94.4 112.3 112.3 112.2 112.2 121.5 92.5 108.4 108.4 108.4 108.4 116.5 90.5 104.5 104.5 104.4 104.4 111.3 88.5  
75  
80  
85  
90  
106.3 91.3 116.6 69.7 127.5 47.4 102.2 89.3 112.0 67.8 122.4 45.6 97.9 87.2 107.3 65.9 117.2 43.7 93.4 85.0 102.4 63.9 111.8 41.9  
107.4 107.4 116.7 86.6 127.5 64.5 103.9 103.9 112.1 84.7 122.5 62.7 100.1 100.1 107.4 82.6 117.3 60.9 96.2 96.2 102.5 80.5 112.0 59.0  
113.0 113.0 117.1 103.4 127.6 81.6 109.3 109.3 112.7 101.5 122.7 79.8 105.5 105.5 108.1 99.4 117.5 78.0 101.5 101.5 103.3 97.4 112.2 76.1  
118.5 118.5 118.4 118.4 127.7 98.2 114.8 114.8 114.7 114.7 122.8 96.3 110.8 110.8 110.7 110.7 117.6 94.3 106.6 106.6 106.6 106.6 112.4 92.3  
Note: All tem peratures are in degrees Fahrenheit. Airflow is in cfm .  
Table PD-2 — Gross Cooling Capacities (kW) TWA100A Heat Pump with TWE100A Air Handler (SI)  
Ambient Temperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
m3/h  
5098  
(°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
24  
27  
29  
32  
29.7 23.7 32.7 19.7 35.9 13.2 28.6 23.1 31.5 19.1 34.6 12.8 27.4 22.5 30.2 18.6 33.1 12.3 26.2 21.9 28.9 18.1 31.7 11.8  
29.9 27.7 32.8 22.6 35.9 17.3 28.8 27.1 31.6 22.1 34.6 16.8 27.6 26.5 30.3 21.5 33.2 16.3 26.5 25.9 28.9 20.9 31.7 15.8  
30.6 30.6 32.8 26.5 35.9 21.3 29.7 29.7 31.6 26.0 34.6 20.8 28.7 28.7 30.3 25.4 33.2 20.3 27.6 27.6 29.0 24.8 31.7 19.7  
32.1 32.1 33.0 30.5 36.0 25.3 31.1 31.1 31.8 29.9 34.6 24.8 30.1 30.1 30.6 29.3 33.2 24.2 29.0 29.0 29.3 28.8 31.8 23.6  
5648  
6203  
6754  
24  
27  
29  
32  
30.3 24.7 33.3 19.2 36.5 13.5 29.1 24.2 32.0 18.7 35.1 13.0 27.9 23.6 30.7 18.1 33.6 12.5 26.6 22.9 29.3 17.5 32.1 11.9  
30.5 29.1 33.3 23.6 36.5 17.9 29.4 28.6 32.1 23.0 35.1 17.4 28.2 28.0 30.7 22.4 33.6 16.8 26.9 26.9 29.3 21.8 32.1 16.3  
31.6 31.6 33.4 27.8 36.5 22.2 30.6 30.6 32.1 27.2 35.1 21.7 29.5 29.5 30.8 26.7 33.7 21.2 28.4 28.4 29.4 26.1 32.2 20.6  
33.1 33.1 33.6 32.2 36.5 26.5 32.1 32.1 32.4 31.6 35.1 25.9 31.0 31.0 31.2 31.0 33.7 25.4 29.9 29.9 29.8 29.8 32.2 24.8  
24  
27  
29  
32  
30.7 25.8 33.8 19.8 36.9 13.7 29.5 25.2 32.4 19.3 35.5 13.2 28.3 24.6 31.1 18.7 34.0 12.7 27.0 23.9 29.7 18.1 32.5 12.1  
31.1 30.5 33.8 24.5 36.9 18.4 30.0 29.9 32.5 23.9 35.5 17.9 28.7 28.7 31.1 23.3 34.0 17.3 27.6 27.6 29.7 22.7 32.5 16.8  
32.4 32.4 33.8 29.1 37.0 23.1 31.3 31.3 32.6 28.5 35.6 22.6 30.2 30.2 31.2 27.9 34.1 22.0 29.1 29.1 29.9 27.3 32.5 21.5  
33.9 33.9 34.3 33.8 37.0 27.6 32.9 32.9 32.8 32.8 35.6 27.1 31.8 31.8 31.7 31.7 34.1 26.5 30.6 30.6 30.6 30.6 32.6 25.9  
24  
27  
29  
32  
31.1 26.7 34.1 20.4 37.3 13.9 29.9 26.1 32.8 19.9 35.9 13.3 28.7 25.5 31.4 19.3 34.3 12.8 27.3 24.9 30.0 18.7 32.7 12.3  
31.5 31.5 34.2 25.4 37.3 18.9 30.4 30.4 32.8 24.8 35.9 18.4 29.3 29.3 31.4 24.2 34.4 17.8 28.2 28.2 30.0 23.6 32.8 17.3  
33.1 33.1 34.3 30.3 37.4 23.9 32.0 32.0 33.0 29.7 35.9 23.4 30.9 30.9 31.6 29.1 34.4 22.8 29.7 29.7 30.3 28.5 32.9 22.3  
34.7 34.7 34.7 34.7 37.4 28.8 33.6 33.6 33.6 33.6 35.9 28.2 32.4 32.4 32.4 32.4 34.4 27.6 31.2 31.2 31.2 31.2 32.9 27.0  
Note: All tem peratures are in degrees Celsius. Airflow is in liters per second.  
SSP-PRC002-EN  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-3 — Gross Cooling Capacities (MBh) TWA155A Heat Pump with TWE155A Air Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
CFM  
4500  
(°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75  
80  
85  
90  
152.8 121.6 169.0 101.2 186.3 68.7 147.6 119.0 163.1 98.8 179.6 66.4 141.5 116.0 156.2 96.0 171.9 63.7 134.4 112.5 148.4 92.9 163.4 60.8  
153.5 142.2 169.3 117.1 186.4 90.4 148.5 139.6 163.5 114.7 179.7 87.9 142.6 136.6 156.4 111.4 172.1 85.0 135.8 133.3 148.7 108.0 163.7 82.0  
157.6 157.6 169.5 137.4 186.6 111.5 153.3 153.3 163.7 134.8 180.0 109.0 148.1 148.1 156.9 131.8 172.5 106.2 142.1 142.1 149.2 128.4 164.1 103.1  
165.7 165.7 170.4 158.1 186.8 132.2 161.1 161.1 164.8 155.5 180.2 129.6 155.7 155.7 158.2 152.6 172.7 126.6 149.6 149.6 150.9 149.3 164.3 123.4  
5000  
5500  
6000  
75  
80  
85  
90  
155.8 127.4 172.1 99.7 189.4 70.0 150.4 124.7 166.0 97.1 182.4 67.6 144.0 121.6 158.8 94.2 174.5 64.9 136.7 118.1 150.8 90.9 165.7 61.8  
156.9 150.0 172.2 122.3 189.5 93.4 151.8 147.5 166.1 119.7 182.6 90.9 145.7 144.4 159.1 116.6 174.7 88.1 138.7 138.7 151.1 113.1 166.0 84.9  
162.9 162.9 172.7 144.6 189.8 116.5 158.3 158.3 166.6 141.9 182.9 114.0 152.8 152.8 159.6 138.9 175.1 111.2 146.5 146.5 151.8 135.5 166.5 108.0  
171.3 171.3 174.1 167.4 189.9 138.9 166.4 166.4 168.3 164.8 183.1 136.2 160.7 160.7 160.9 160.9 175.4 133.2 154.3 154.3 154.4 154.4 166.8 129.9  
75  
80  
85  
90  
158.3 132.9 174.6 103.0 191.8 71.3 152.8 130.2 168.3 100.5 184.7 68.7 146.2 127.0 161.0 97.5 176.5 65.9 138.8 123.5 152.7 94.2 167.5 62.7  
160.1 157.7 174.8 127.4 192.0 96.3 154.1 154.1 168.6 124.6 184.9 93.8 148.6 148.6 161.3 121.5 176.9 90.9 142.3 142.3 153.1 118.0 168.0 87.8  
167.4 167.4 175.3 151.5 192.3 121.3 162.6 162.6 169.2 148.8 185.3 118.8 156.8 156.8 162.0 145.7 177.1 115.4 150.3 150.3 154.0 142.3 168.3 112.1  
176.1 176.1 177.5 176.4 192.6 145.3 171.0 171.0 171.2 171.2 185.6 142.6 165.0 165.0 165.2 165.2 177.6 139.6 158.3 158.3 158.5 158.5 168.9 136.2  
75  
80  
85  
90  
160.5 138.2 176.8 106.3 193.9 72.2 154.8 135.5 170.3 103.7 186.6 69.6 148.1 132.3 162.8 100.7 178.3 66.7 140.6 128.7 154.4 97.4 169.1 63.6  
162.6 162.5 177.0 132.2 194.1 99.1 157.7 157.7 170.6 129.4 186.9 96.5 151.9 151.9 163.2 126.3 178.7 93.7 145.4 145.4 154.8 122.7 169.7 90.5  
171.5 171.5 177.7 158.2 194.3 125.6 166.4 166.4 171.4 155.5 187.1 122.9 160.4 160.4 164.1 152.4 179.0 119.8 153.6 153.6 156.1 148.9 170.1 116.4  
180.4 180.4 180.6 180.6 194.8 151.5 175.1 175.1 175.2 175.2 187.6 148.8 168.9 168.9 169.0 169.0 179.5 145.7 161.9 161.9 162.1 162.1 170.6 142.3  
Note: All tem peratures are in degrees Fahrenheit. Airflow is in cfm .  
Table PD-3 — Gross Cooling Capacities (kW) TWA155A Heat Pump with TWE155A Air Handler (SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
m3/h  
7646  
(°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
24  
27  
29  
32  
44.7 35.6 49.5 29.6 54.6 20.1 43.2 34.8 47.8 28.9 52.6 19.4 41.4 34.0 45.7 28.1 50.3 18.7 39.4 32.9 43.5 27.2 47.8 17.8  
44.9 41.6 49.6 34.3 54.6 26.5 43.5 40.9 47.9 33.6 52.6 25.7 41.7 40.0 45.8 32.6 50.4 24.9 39.8 39.0 43.5 31.6 47.9 24.0  
46.1 46.1 49.6 40.2 54.6 32.6 44.9 44.9 47.9 39.5 52.7 31.9 43.4 43.4 45.9 38.6 50.5 31.1 41.6 41.6 43.7 37.6 48.0 30.2  
48.5 48.5 49.9 46.3 54.7 38.7 47.2 47.2 48.2 45.5 52.8 37.9 45.6 45.6 46.3 44.7 50.6 37.1 43.8 43.8 44.2 43.7 48.1 36.1  
8496  
9346  
10195  
24  
27  
29  
32  
45.6 37.3 50.4 29.2 55.4 20.5 44.0 36.5 48.6 28.4 53.4 19.8 42.2 35.6 46.5 27.6 51.1 19.0 40.0 34.6 44.2 26.6 48.5 18.1  
46.0 43.9 50.4 35.8 55.5 27.4 44.4 43.2 48.6 35.0 53.5 26.6 42.7 42.3 46.6 34.1 51.2 25.8 40.6 40.6 44.2 33.1 48.6 24.9  
47.7 47.7 50.6 42.3 55.6 34.1 46.3 46.3 48.8 41.6 53.6 33.4 44.7 44.7 46.7 40.7 51.3 32.5 42.9 42.9 44.4 39.7 48.7 31.6  
50.1 50.1 51.0 49.0 55.6 40.7 48.7 48.7 49.3 48.3 53.6 39.9 47.1 47.1 47.1 47.1 51.3 39.0 45.2 45.2 45.2 45.2 48.8 38.0  
24  
27  
29  
32  
46.4 38.9 51.1 30.2 56.2 20.9 44.7 38.1 49.3 29.4 54.1 20.1 42.8 37.2 47.1 28.6 51.7 19.3 40.6 36.2 44.7 27.6 49.0 18.4  
46.9 46.2 51.2 37.3 56.2 28.2 45.1 45.1 49.4 36.5 54.1 27.5 43.5 43.5 47.2 35.6 51.8 26.6 41.7 41.7 44.8 34.6 49.2 25.7  
49.0 49.0 51.3 44.4 56.3 35.5 47.6 47.6 49.5 43.6 54.3 34.8 45.9 45.9 47.4 42.7 51.8 33.8 44.0 44.0 45.1 41.7 49.3 32.8  
51.6 51.6 52.0 51.7 56.4 42.6 50.1 50.1 50.1 50.1 54.3 41.8 48.3 48.3 48.4 48.4 52.0 40.9 46.4 46.4 46.4 46.4 49.4 39.9  
24  
27  
29  
32  
47.0 40.5 51.8 31.1 56.8 21.1 45.3 39.7 49.9 30.4 54.6 20.4 43.4 38.7 47.7 29.5 52.2 19.5 41.2 37.7 45.2 28.5 49.5 18.6  
47.6 47.6 51.8 38.7 56.8 29.0 46.2 46.2 50.0 37.9 54.7 28.3 44.5 44.5 47.8 37.0 52.3 27.4 42.6 42.6 45.3 35.9 49.7 26.5  
50.2 50.2 52.0 46.3 56.9 36.8 48.7 48.7 50.2 45.5 54.8 36.0 47.0 47.0 48.1 44.6 52.4 35.1 45.0 45.0 45.7 43.6 49.8 34.1  
52.8 52.8 52.9 52.9 57.0 44.4 51.3 51.3 51.3 51.3 54.9 43.6 49.4 49.4 49.5 49.5 52.6 42.7 47.4 47.4 47.5 47.5 50.0 41.7  
Note: All tem peratures are in degrees Celsius. Airflow is in liters per second.  
14  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-4 — Gross Cooling Capacities (MBh) TWA200A Heat Pump with TWE200A Air Handler (I-P)  
AmbientTemperature (°F)  
85  
95  
105  
115  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°F)  
73 61  
61  
67  
73  
61  
67  
67  
73  
61  
67  
73  
CFM  
6000  
(°F) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
75  
80  
85  
90  
200.7 159.3 220.9 132.5 242.6 89.4 192.9 155.4 212.4 129.1 233.3 86.1 184.8 151.3 203.6 125.5 223.6 82.8 176.4 147.1 194.5 121.8 213.6 79.3  
201.5 186.0 221.2 152.1 242.5 117.0 194.0 182.1 212.8 148.5 233.3 113.4 186.2 178.1 204.0 144.7 223.7 109.8 178.1 174.0 194.7 140.4 213.8 106.2  
206.2 206.2 221.4 178.3 242.8 143.7 199.7 199.7 213.0 174.4 233.6 140.2 192.9 192.9 204.3 170.5 224.0 136.5 185.8 185.8 195.2 166.4 214.1 132.8  
216.2 216.2 222.3 204.7 243.0 170.3 209.5 209.5 214.2 200.8 233.8 166.8 202.5 202.5 205.8 196.9 224.1 162.6 195.2 195.2 197.2 193.0 214.3 158.7  
6675  
7350  
8025  
75  
80  
85  
90  
204.4 166.6 224.8 129.6 246.5 91.1 196.4 162.6 216.1 125.9 236.9 87.8 188.1 158.5 207.0 122.1 226.9 84.3 179.4 154.2 197.6 118.3 216.6 80.6  
205.8 195.9 225.1 159.0 246.5 120.7 198.1 192.0 216.2 154.9 236.9 117.2 190.2 188.0 207.2 151.0 227.1 113.6 181.5 181.5 197.9 146.9 216.8 109.8  
212.7 212.7 225.3 187.3 246.7 149.9 205.9 205.9 216.7 183.3 237.2 146.3 198.8 198.8 207.7 179.3 227.4 142.7 191.4 191.4 198.6 175.3 217.2 138.9  
223.1 223.1 226.9 216.3 246.8 178.4 216.1 216.1 218.7 212.4 237.3 174.6 208.8 208.8 210.2 208.5 227.6 170.8 201.2 201.2 201.0 201.0 217.4 166.8  
75  
80  
85  
90  
207.6 173.6 228.0 133.8 249.6 92.7 199.4 169.5 219.1 130.1 239.8 89.1 190.8 165.4 209.8 126.3 229.6 85.5 182.1 161.1 200.2 122.4 219.1 81.8  
209.7 205.5 228.1 165.1 249.7 124.3 202.0 201.6 219.3 161.2 239.9 120.8 193.6 193.6 210.0 157.2 229.8 117.1 186.1 186.1 200.5 153.0 219.4 113.4  
218.4 218.4 228.6 195.9 250.0 155.8 211.3 211.3 219.9 192.0 240.3 152.2 203.9 203.9 210.8 187.9 230.2 148.5 196.2 196.2 201.5 183.8 219.8 144.8  
229.1 229.1 231.1 227.5 250.1 186.4 221.9 221.9 221.7 221.7 240.4 182.5 214.3 214.3 214.1 214.1 230.4 178.6 206.3 206.3 206.2 206.2 220.0 174.6  
75  
80  
85  
90  
210.3 180.3 230.8 137.8 252.3 93.8 202.0 176.2 221.6 134.1 242.3 90.3 193.3 172.0 212.1 130.3 231.9 86.6 184.4 167.7 202.4 126.4 221.1 82.8  
212.4 212.4 231.0 171.2 252.4 127.7 205.3 205.3 221.9 167.2 242.5 124.2 197.8 197.8 212.5 163.1 232.1 120.5 190.1 190.1 202.8 159.0 221.5 116.7  
223.4 223.4 231.6 204.3 252.7 161.5 216.1 216.1 222.8 200.3 242.8 157.9 208.4 208.4 213.6 196.2 232.3 153.7 200.5 200.5 204.1 192.1 221.7 149.7  
234.5 234.5 234.3 234.3 252.9 194.0 227.0 227.0 226.8 226.8 243.1 190.1 219.0 219.0 218.9 218.9 232.8 186.2 210.8 210.8 210.7 210.7 222.2 182.1  
Note: All tem peratures are in degrees Fahrenheit. Airflow is in cfm .  
Table PD-4 — Gross Cooling Capacities (kW) TWA200A Heat Pump with TWE200A Air Handler (SI)  
AmbientTemperature (°C)  
29.4  
35.0  
40.6  
46.1  
Enter.  
Dry  
Bulb  
Entering Wet Bulb (°C)  
22.8 16.1  
16.1  
19.4  
22.8  
16.1  
19.4  
19.4  
22.8  
16.1  
19.4  
22.8  
m3/h  
(°C) Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens. Total Sens.  
10195  
24  
27  
29  
32  
58.8 46.7 64.7 38.8 71.0 26.2 56.5 45.5 62.2 37.8 68.3 25.2 54.1 44.3 59.6 36.7 65.5 24.2 51.6 43.1 57.0 35.7 62.5 23.2  
59.0 54.5 64.8 44.5 71.0 34.2 56.8 53.3 62.3 43.5 68.3 33.2 54.5 52.1 59.7 42.4 65.5 32.2 52.1 50.9 57.0 41.1 62.6 31.1  
60.4 60.4 64.8 52.2 71.1 42.1 58.5 58.5 62.4 51.1 68.4 41.0 56.5 56.5 59.8 49.9 65.6 40.0 54.4 54.4 57.2 48.7 62.7 38.9  
63.3 63.3 65.1 59.9 71.2 49.9 61.3 61.3 62.7 58.8 68.5 48.8 59.3 59.3 60.3 57.7 65.6 47.6 57.2 57.2 57.7 56.5 62.7 46.5  
11340  
12488  
13633  
24  
27  
29  
32  
59.9 48.8 65.8 37.9 72.2 26.7 57.5 47.6 63.3 36.9 69.4 25.7 55.1 46.4 60.6 35.8 66.4 24.7 52.5 45.2 57.9 34.6 63.4 23.6  
60.3 57.4 65.9 46.6 72.2 35.4 58.0 56.2 63.3 45.4 69.4 34.3 55.7 55.0 60.7 44.2 66.5 33.3 53.1 53.1 57.9 43.0 63.5 32.2  
62.3 62.3 66.0 54.8 72.2 43.9 60.3 60.3 63.4 53.7 69.5 42.8 58.2 58.2 60.8 52.5 66.6 41.8 56.0 56.0 58.1 51.3 63.6 40.7  
65.3 65.3 66.4 63.3 72.2 52.2 63.3 63.3 64.0 62.2 69.5 51.1 61.1 61.1 61.6 61.1 66.6 50.0 58.9 58.9 58.9 58.9 63.7 48.8  
24  
27  
29  
32  
60.8 50.8 66.8 39.2 73.1 27.1 58.4 49.6 64.1 38.1 70.2 26.1 55.9 48.4 61.4 37.0 67.2 25.0 53.3 47.2 58.6 35.8 64.1 23.9  
61.4 60.2 66.8 48.3 73.1 36.4 59.1 59.0 64.2 47.2 70.3 35.4 56.7 56.7 61.5 46.0 67.3 34.3 54.5 54.5 58.7 44.8 64.2 33.2  
64.0 64.0 66.9 57.4 73.2 45.6 61.9 61.9 64.4 56.2 70.3 44.6 59.7 59.7 61.7 55.0 67.4 43.5 57.5 57.5 59.0 53.8 64.4 42.4  
67.1 67.1 67.7 66.6 73.2 54.6 65.0 65.0 64.9 64.9 70.4 53.4 62.7 62.7 62.7 62.7 67.5 52.3 60.4 60.4 60.4 60.4 64.4 51.1  
24  
27  
29  
32  
61.6 52.8 67.6 40.4 73.9 27.5 59.1 51.6 64.9 39.3 70.9 26.4 56.6 50.4 62.1 38.2 67.9 25.4 54.0 49.1 59.3 37.0 64.7 24.3  
62.2 62.2 67.6 50.1 73.9 37.4 60.1 60.1 65.0 49.0 71.0 36.4 57.9 57.9 62.2 47.8 68.0 35.3 55.7 55.7 59.4 46.5 64.9 34.2  
65.4 65.4 67.8 59.8 74.0 47.3 63.3 63.3 65.2 58.6 71.1 46.2 61.0 61.0 62.5 57.5 68.0 45.0 58.7 58.7 59.8 56.3 64.9 43.8  
68.7 68.7 68.6 68.6 74.1 56.8 66.5 66.5 66.4 66.4 71.2 55.7 64.1 64.1 64.1 64.1 68.2 54.5 61.7 61.7 61.7 61.7 65.1 53.3  
Note: All tem peratures are in degrees Celsius. Airflow is in liters per second.  
SSP-PRC002-EN  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(TWA075A)  
Table PD-5 — Gross Cooling Performance (MBh) TWA075A Heat Pump Only (I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
165  
70.0  
4.58  
191  
170  
77.4  
4.67  
197  
176  
85.1  
4.78  
203  
182  
93.1  
4.89  
209  
188  
101.3  
5.02  
215  
195  
109.6  
5.14  
222  
65  
75  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
68.2  
5.04  
75.2  
5.15  
82.5  
5.27  
90.1  
5.39  
97.8  
105.6  
5.65  
5.52  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
219  
65.5  
5.59  
225  
72.3  
5.71  
231  
79.2  
5.84  
238  
86.4  
5.97  
245  
93.6  
6.10  
252  
101.1  
6.24  
85  
95  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
250  
62.3  
6.22  
256  
68.7  
6.35  
263  
75.3  
6.48  
270  
82.0  
6.61  
277  
88.9  
6.74  
284  
95.9  
6.88  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
283  
58.6  
6.93  
289  
64.6  
7.06  
296  
70.8  
7.18  
304  
77.1  
7.31  
311  
83.7  
7.45  
319  
90.3  
7.59  
105  
115  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
318  
54.4  
7.72  
325  
60.0  
7.83  
332  
65.8  
7.95  
340  
71.8  
8.08  
347  
78.0  
8.22  
355  
84.4  
8.36  
Table PD-5 — Gross Cooling Performance (kW) TWA075A Heat Pump Only (SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1136  
20.5  
1173  
22.6  
1213  
24.9  
1255  
27.2  
1298  
29.7  
1343  
32.1  
18.3  
23.9  
29.4  
35.0  
40.6  
OD Unit Power (kW)  
4.58  
4.67  
4.78  
4.89  
5.02  
5.14  
Head pressure (kPA)  
Capacity (kW)  
1315  
20.0  
5.04  
1355  
22.0  
5.15  
1397  
24.2  
5.27  
1440  
26.4  
5.39  
1484  
28.6  
5.52  
1531  
30.9  
5.65  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1509  
19.2  
5.59  
1552  
21.2  
5.71  
1596  
23.2  
5.84  
1642  
25.3  
5.97  
1689  
27.4  
1738  
29.6  
6.24  
OD Unit Power (kW)  
6.10  
Head pressure (kPA)  
Capacity (kW)  
1721  
18.3  
6.22  
1766  
20.1  
6.35  
1812  
22.0  
6.48  
1860  
24.0  
6.61  
1909  
26.0  
6.74  
1959  
28.1  
6.88  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1948  
17.2  
1995  
18.9  
7.06  
2043  
20.7  
7.18  
2093  
22.6  
7.31  
2144  
24.5  
7.45  
2197  
26.5  
7.59  
OD Unit Power (kW)  
6.93  
Head pressure (kPA)  
Capacity (kW)  
2192  
15.9  
7.72  
2240  
17.6  
7.83  
2290  
19.3  
7.95  
2341  
21.0  
8.08  
2395  
22.8  
8.22  
2450  
24.7  
8.36  
46.1  
48.9  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
OD Unit Power (kW)  
2320  
15.3  
8.13  
2369  
16.9  
8.24  
2419  
18.5  
8.36  
2471  
20.2  
8.49  
2526  
22.0  
8.62  
2583  
23.8  
8.76  
16  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(TWA100A)  
Table PD-6— Gross Cooling Performance (MBh) TWA100A Heat Pump Only (I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
175  
94.8  
6.26  
181  
104.0  
6.41  
187  
113.6  
6.57  
194  
123.5  
6.74  
201  
133.7  
6.93  
208  
144.2  
7.12  
65  
Head press psig  
200  
207  
213  
220  
227  
235  
75  
85  
Cap. Btu/1000  
OD Unit kW  
90.4  
6.92  
99.1  
7.08  
108.1  
7.25  
117.5  
7.44  
127.3  
7.64  
137.3  
7.85  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
229  
85.7  
7.70  
235  
93.9  
7.88  
242  
102.5  
8.07  
250  
111.5  
8.27  
257  
120.8  
8.49  
265  
130.4  
8.71  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
259  
80.7  
8.60  
266  
88.6  
8.79  
274  
96.8  
9.00  
282  
105.4  
9.22  
290  
114.2  
9.44  
298  
123.3  
9.67  
95  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
293  
75.5  
9.60  
300  
83.0  
9.82  
308  
91.0  
10.05  
316  
99.2  
10.28  
325  
107.6  
10.51  
334  
116.2  
10.74  
105  
115  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
328  
70.0  
10.72  
337  
77.4  
10.96  
345  
85.0  
11.21  
354  
92.9  
11.45  
363  
100.9  
11.69  
372  
109.0  
11.92  
Table PD-6 — Gross Cooling Performance (kW) TWA100A Heat Pump Only (SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1206  
27.7  
1247  
30.4  
6.41  
1290  
33.3  
6.57  
1336  
36.2  
6.74  
1383  
39.2  
6.93  
1432  
42.2  
7.12  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
6.26  
Head pressure (kPA)  
Capacity (kW)  
1382  
26.5  
6.92  
1425  
29.0  
7.08  
1470  
31.7  
7.25  
1518  
34.4  
7.44  
1568  
37.3  
7.64  
1621  
40.2  
7.85  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1576  
25.1  
7.70  
1622  
27.5  
7.88  
1670  
30.0  
8.07  
1721  
32.7  
8.27  
1774  
35.4  
8.49  
1829  
38.2  
8.71  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
1788  
23.6  
8.60  
1837  
25.9  
8.79  
1888  
28.3  
9.00  
1941  
30.9  
9.22  
1997  
33.5  
9.44  
2055  
36.1  
9.67  
OD Unit Power (kW)  
Head pressure (kPA)  
Capacity (kW)  
2017  
22.1  
9.60  
2069  
24.3  
9.82  
2124  
26.6  
2181  
29.0  
2240  
31.5  
2300  
34.0  
OD Unit Power (kW)  
10.05  
10.28  
10.51  
10.74  
Head pressure (kPA)  
Capacity (kW)  
2265  
20.5  
2321  
22.7  
2379  
24.9  
2440  
27.2  
2502  
29.5  
2565  
31.9  
OD Unit Power (kW)  
10.72  
10.96  
11.21  
11.45  
11.69  
11.92  
SSP-PRC002-EN  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(TWA15 5 A)  
Table PD-7 — Gross Cooling Performance (MBh) TWA155A Heat Pump Only (I-P)  
ODTemp  
°F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
165  
137.2  
9.13  
170  
151.6  
9.33  
176  
166.8  
9.54  
182  
182.4  
9.77  
188  
195  
65  
75  
198.5  
10.02  
214.9  
10.27  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
191  
197  
203  
209  
215  
222  
133.6  
10.06  
147.5  
10.29  
161.8  
10.52  
176.6  
10.77  
191.6  
11.02  
207.0  
11.29  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
219  
225  
232  
238  
245  
252  
85  
128.5  
11.16  
141.7  
11.40  
155.4  
11.65  
169.3  
11.91  
183.6  
12.18  
198.1  
12.46  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
250  
256  
263  
270  
277  
284  
95  
122.2  
12.43  
134.7  
12.68  
147.6  
12.94  
160.8  
13.20  
174.3  
13.47  
188.1  
13.75  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
283  
289  
296  
304  
311  
319  
105  
115  
114.9  
13.85  
126.7  
14.10  
138.8  
14.35  
151.2  
14.61  
164.0  
14.89  
177.1  
15.17  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
318  
325  
332  
340  
347  
355  
106.7  
15.41  
117.7  
15.65  
129.1  
15.89  
140.8  
16.15  
152.9  
16.42  
165.4  
16.70  
Table PD-7 — Gross Cooling Performance (kW) TWA155A Heat Pump Only (SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1136  
40.2  
9.13  
1174  
44.4  
9.33  
1213  
48.8  
9.54  
1255  
53.4  
9.77  
1299  
58.1  
1343  
62.9  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
10.02  
10.27  
Head pressure (kPA)  
Capacity (kW)  
1315  
39.1  
1355  
43.2  
1397  
47.4  
1440  
51.7  
1485  
56.1  
1532  
60.6  
OD Unit Power (kW)  
10.06  
10.29  
10.52  
10.77  
11.02  
11.29  
Head pressure (kPA)  
Capacity (kW)  
1510  
37.6  
1552  
41.5  
1597  
45.5  
1642  
49.6  
1690  
53.8  
1738  
58.0  
OD Unit Power (kW)  
11.16  
11.40  
11.65  
11.91  
12.18  
12.46  
Head pressure (kPA)  
Capacity (kW)  
1722  
35.8  
1767  
39.5  
1813  
43.2  
1860  
47.1  
1909  
51.0  
1960  
55.1  
OD Unit Power (kW)  
12.43  
12.68  
12.94  
13.20  
13.47  
13.75  
Head pressure (kPA)  
Capacity (kW)  
1949  
33.6  
1996  
37.1  
2044  
40.6  
2093  
44.3  
2145  
48.0  
2197  
51.9  
OD Unit Power (kW)  
13.85  
14.10  
14.35  
14.61  
14.89  
15.17  
Head pressure (kPA)  
Capacity (kW)  
2192  
31.2  
2241  
34.5  
2291  
37.8  
2342  
41.2  
2395  
44.8  
2451  
48.4  
OD Unit Power (kW)  
15.41  
15.65  
15.89  
16.15  
16.42  
16.70  
18  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(TWA2 0 0 A)  
Table PD-8 — Gross Cooling Performance (MBh) TWA200A Heat Pump Only (I-P)  
ODTemp  
° F  
Suction ReferenceTemperature °F  
30  
35  
40  
45  
50  
55  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
177  
183  
189  
196  
203  
210  
65  
75  
187.4  
12.50  
205.7  
12.81  
224.7  
13.14  
244.4  
13.49  
264.7  
13.86  
285.6  
14.25  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
203  
209  
216  
223  
230  
238  
178.8  
13.84  
196.0  
14.17  
213.9  
14.53  
232.6  
14.91  
252.1  
15.32  
272.1  
15.75  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
231  
238  
245  
253  
260  
269  
85  
169.4  
15.42  
185.8  
15.79  
203.0  
16.18  
220.8  
16.60  
239.3  
17.04  
258.4  
17.49  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
262  
269  
277  
285  
293  
302  
95  
159.6  
17.24  
175.3  
17.65  
191.7  
18.08  
208.8  
18.52  
226.4  
18.98  
244.5  
19.44  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
296  
304  
312  
320  
329  
338  
105  
115  
149.2  
19.29  
164.3  
19.74  
180.1  
20.20  
196.5  
20.68  
213.4  
21.15  
230.6  
21.62  
Head press psig  
Cap. Btu/1000  
OD Unit kW  
332  
340  
349  
358  
367  
377  
138.5  
21.55  
153.1  
22.05  
168.4  
22.55  
184.1  
23.05  
200.2  
23.54  
216.5  
24.01  
Table PD-8 — Gross Cooling Performance (kW) TWA200A Heat Pump Only (SI)  
ODTemp  
°C  
Suction ReferenceTemperature °C  
-1.1  
1.7  
4.4  
7.2  
10.0  
12.8  
Head pressure (kPA)  
Capacity (kW)  
1219  
54.9  
1261  
60.2  
1305  
65.8  
1351  
71.5  
1399  
77.5  
1449  
83.6  
18.3  
23.9  
29.4  
35.0  
40.6  
46.1  
OD Unit Power (kW)  
12.50  
12.81  
13.14  
13.49  
13.86  
14.25  
Head pressure (kPA)  
Capacity (kW)  
1397  
52.3  
1441  
57.4  
1487  
62.6  
1536  
68.1  
1588  
73.8  
1642  
79.7  
OD Unit Power (kW)  
13.84  
14.17  
14.53  
14.91  
15.32  
15.75  
Head pressure (kPA)  
Capacity (kW)  
1593  
49.6  
1640  
54.4  
1689  
59.4  
1741  
64.7  
1796  
70.1  
1852  
75.7  
OD Unit Power (kW)  
15.42  
15.79  
16.18  
16.60  
17.04  
17.49  
Head pressure (kPA)  
Capacity (kW)  
1808  
46.7  
1857  
51.3  
1910  
56.1  
1965  
61.1  
2022  
66.3  
2081  
71.6  
OD Unit Power (kW)  
17.24  
17.65  
18.08  
18.52  
18.98  
19.44  
Head pressure (kPA)  
Capacity (kW)  
2040  
43.7  
2093  
48.1  
2149  
52.7  
2207  
57.5  
2268  
62.5  
2329  
67.5  
OD Unit Power (kW)  
19.29  
19.74  
20.20  
20.68  
21.15  
21.62  
Head pressure (kPA)  
Capacity (kW)  
2290  
40.5  
2348  
44.8  
2408  
49.3  
2470  
53.9  
2533  
58.6  
2597  
63.4  
OD Unit Power (kW)  
21.55  
22.05  
22.55  
23.05  
23.54  
24.01  
SSP-PRC002-EN  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-9 — Gross Heating Capacities (MBh)  
TWA075A Heat Pump with TWE075A Air Handler At 2500 CFM (I-P)  
Outdoor  
Heating Capacity (Btu/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
34.9  
35.5  
36.5  
37.9  
30.4  
31.5  
33.1  
35.0  
37.5  
40.3  
43.5  
47.1  
51.1  
55.4  
60.1  
64.8  
69.7  
74.8  
80.2  
85.6  
91.2  
96.8  
102.5  
28.5  
30.0  
31.8  
34.0  
36.7  
39.7  
43.1  
46.9  
51.0  
55.3  
60.0  
64.7  
69.6  
74.7  
79.9  
85.3  
90.8  
96.2  
101.9  
26.9  
28.6  
30.6  
33.2  
36.1  
39.3  
42.9  
46.8  
50.9  
55.3  
60.0  
64.7  
69.5  
74.5  
79.6  
84.9  
90.2  
95.6  
101.2  
5.5  
5.5  
5.4  
5.4  
5.4  
5.4  
5.5  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.7  
6.9  
7.1  
5.6  
5.6  
5.6  
5.6  
5.7  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
7.0  
5.7  
5.7  
5.8  
5.8  
5.9  
6.0  
6.1  
6.2  
6.3  
6.4  
6.6  
6.8  
6.9  
7.1  
5.8  
5.9  
5.9  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.6  
7.8  
8.0  
8.2  
8.4  
39.7  
42.0  
44.8  
48.0  
51.7  
55.8  
60.3  
65.0  
69.9  
75.1  
80.6  
86.2  
92.0  
97.8  
7
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
7.3  
7.5  
7.7  
7.9  
7.1  
7.3  
7.5  
7.7  
103.7  
8.1  
Table PD-9 — Gross Heating Capacities (kW)  
TWA075A Heat Pump with TWE075A Air Handler At 4247 m3/h (SI)  
Outdoor  
Heating Capacity (kW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
-27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
10.2  
10.4  
10.7  
11.1  
8.9  
9.2  
9.7  
8.4  
8.8  
9.3  
7.9  
8.4  
9.0  
9.7  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
10.3  
11.0  
11.8  
12.7  
13.8  
15.0  
16.2  
17.6  
19.0  
20.4  
21.9  
23.5  
25.1  
26.7  
28.3  
30.0  
10.0  
10.7  
11.6  
12.6  
13.7  
14.9  
16.2  
17.6  
19.0  
20.4  
21.9  
23.4  
25.0  
26.6  
28.2  
29.8  
11.6  
10.6  
11.5  
12.6  
13.7  
14.9  
16.2  
17.6  
18.9  
20.3  
21.8  
23.3  
24.9  
26.4  
28.0  
29.6  
12.3  
13.1  
14.1  
15.1  
16.3  
17.7  
19.0  
20.5  
22.0  
23.6  
25.2  
26.9  
28.6  
30.4  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
Correction Factors - Other Airflows  
(Table Value x Correction Factor = Value at new airflow)  
Airflow = 2500 cfm (4247 m 3/h)  
Heating Capacity (High Tem p.) = 75,000 (21.82)  
Heating Capacity (Low Tem p.) = 47,000 (13.84)  
Com pressor Power (High Tem p) = 5.41 kW  
Com pressor Power (Low Tem p) = 4.55 kW  
Coeff. Of Perf. (High Tem p) = 3.2  
Airflow  
2250 cfm  
3822 m 3/h  
x0.99  
2750 cfm  
4672 m 3/h  
x1.01  
Heating Capacity  
Com pressor kW  
x1.02  
x0.98  
Coeff. Of Perf. (Low Tem p) = 2.3  
Outdoor Fan Power = 550 watts  
Values at ARI Rating Conditions of:  
Indoor Fan Power = 800 watts  
70F(21.1C)and 47/43F(8.3/6.1C)(High Tem p.Cond.)  
70F(21.1C)and 17/15F(-8.3/-9.4C)(Low Tem p. Cond)  
Note:  
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.  
20  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-10 — Gross Heating Capacities (MBh)  
TWA100A Heat Pump with TWE100A Air Handler At 3325 CFM (I-P)  
Outdoor  
Heating Capacity (Btu/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
21.9  
33.4  
40.8  
46.7  
52.3  
57.7  
63.2  
68.9  
74.8  
80.9  
87.3  
93.6  
100.2  
107.1  
114.4  
121.9  
129.7  
137.7  
145.9  
39.6  
43.6  
47.5  
43.0  
46.0  
49.2  
52.8  
56.5  
60.6  
65.1  
69.9  
75.1  
80.6  
86.5  
92.6  
98.9  
105.6  
112.7  
120.1  
127.8  
135.6  
143.7  
44.8  
47.3  
50.2  
53.4  
57.0  
5.6  
6.2  
6.6  
6.8  
7.0  
7.2  
7.4  
7.5  
7.7  
7.3  
7.5  
7.6  
7.8  
7.9  
7.9  
8.0  
8.1  
8.2  
8.4  
8.5  
8.6  
8.8  
9.0  
9.1  
9.4  
9.6  
9.8  
10.1  
10.3  
10.6  
10.9  
11.2  
11.6  
8.4  
8.5  
8.6  
8.7  
8.8  
8.9  
9.1  
9.2  
9.4  
51.5  
55.7  
60.1  
64.8  
69.8  
75.1  
80.8  
86.8  
92.9  
99.3  
106.0  
113.2  
120.6  
128.3  
136.2  
144.3  
7
60.8  
65.1  
69.8  
74.9  
80.3  
86.2  
92.2  
98.5  
105.2  
112.3  
119.7  
127.3  
135.1  
143.2  
8.1  
8.2  
8.4  
8.5  
8.7  
8.9  
9.1  
9.3  
9.5  
9.8  
10.1  
10.4  
10.7  
11.0  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
7.9  
9.6  
9.8  
8.0  
8.2  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
9.9  
10.1  
10.3  
10.6  
10.9  
11.2  
11.5  
11.9  
12.2  
Table PD-10 — Gross Heating Capacities (kW)  
TWA100A Heat Pump with TWE100A Air Handler At 5649 m3/h (SI)  
Outdoor  
Heating Capacity (kW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
-27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
6.4  
9.8  
11.9  
11.6  
12.8  
13.9  
15.1  
16.3  
17.6  
19.0  
20.4  
22.0  
23.7  
25.4  
27.2  
29.1  
31.0  
33.1  
35.3  
37.6  
12.6  
13.5  
14.4  
15.4  
16.6  
17.8  
19.1  
20.5  
22.0  
23.6  
25.3  
27.1  
29.0  
30.9  
33.0  
35.2  
37.4  
13.1  
13.9  
14.7  
15.6  
16.7  
17.8  
19.1  
20.4  
21.9  
23.5  
25.2  
27.0  
28.8  
30.8  
32.9  
35.0  
37.3  
39.6  
41.9  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
13.7  
15.3  
16.9  
18.5  
20.2  
21.9  
23.7  
25.6  
27.4  
29.3  
31.3  
33.5  
35.7  
38.0  
40.3  
42.7  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
39.9  
42.3  
39.7  
42.1  
Correction Factors - Other Airflows  
(Table Value x Correction Factor = Value at new airflow)  
Airflow = 3325 cfm (5649 m 3/h)  
Heating Capacity (High Tem p.) = 106,000 (31.05)  
Heating Capacity (Low Tem p.) = 69,000 (20.29)  
Com pressor Power (High Tem p) = 7.61 kW  
Com pressor Power (Low Tem p) = 6.38 kW  
Coeff. Of Perf. (High Tem p) = 3.30  
Airflow  
3000 cfm  
5097 m 3/h  
x0.99  
3675 cfm  
6243 m 3/h  
x1.01  
Heating Capacity  
Com pressor kW  
x1.02  
x0.98  
Coeff. Of Perf. (Low Tem p) = 2.4  
Outdoor Fan Power = 644 watts  
Values at ARI Rating Conditions of:  
Indoor Fan Power = 1,170 watts  
70F(21.1C)and 47/43F(8.3/6.1C)(High Tem p.Cond.)  
70F(21.1C)and 17/15F(-8.3/-9.4C)(Low Tem p. Cond)  
Note:  
1. Rated with 25 feet of 1-3/8" suction and 1/2" liquid line.  
SSP-PRC002-EN  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-11 — Gross Heating Capacities (MBh)  
TWA155B Heat Pump with TWE155B Air Handler At 5000 CFM (I-P)  
Outdoor  
Heating Capacity (BTUH/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
69.7  
71.1  
73.1  
76.0  
79.8  
84.5  
90.2  
96.7  
104.2  
112.6  
121.8  
131.3  
141.4  
151.9  
163.0  
174.4  
186.2  
198.0  
210.0  
60.9  
63.2  
66.4  
70.4  
75.4  
81.1  
87.7  
95.1  
103.2  
111.9  
121.4  
131.0  
140.9  
151.3  
162.2  
173.3  
184.6  
196.0  
207.6  
57.2  
60.2  
63.9  
68.4  
73.9  
80.0  
87.0  
94.6  
102.9  
111.8  
121.3  
130.8  
140.7  
151.0  
161.6  
172.5  
183.6  
194.8  
206.2  
54.0  
57.4  
61.6  
66.8  
72.7  
79.3  
86.6  
94.4  
102.8  
111.8  
121.3  
130.7  
140.5  
150.6  
161.0  
171.7  
182.6  
193.5  
204.8  
11.1  
11.0  
11.0  
10.9  
10.9  
11.0  
11.1  
11.2  
11.3  
11.5  
11.7  
12.0  
12.3  
12.6  
12.9  
13.2  
13.6  
14.0  
14.4  
11.4  
11.3  
11.4  
11.4  
11.5  
11.6  
11.8  
12.0  
12.2  
12.5  
12.8  
13.1  
13.4  
13.8  
14.1  
14.5  
14.9  
15.3  
15.7  
11.5  
11.6  
11.6  
11.7  
11.9  
11.8  
11.8  
12.0  
12.1  
12.3  
12.6  
12.8  
13.1  
13.4  
13.7  
14.1  
14.4  
14.8  
15.2  
15.6  
15.9  
16.3  
16.7  
17.1  
7
12.1  
12.3  
12.5  
12.8  
13.1  
13.4  
13.8  
14.1  
14.5  
14.8  
15.2  
15.6  
16.0  
16.4  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
Table PD-11 — Gross Heating Capacities (kW)  
TWA155B Heat Pump with TWE155B Air Handler At 8494 m3/h (SI)  
Outdoor  
Heating Capacity (kW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
-27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
20.4  
20.8  
21.4  
22.3  
23.4  
24.7  
26.4  
28.3  
30.5  
33.0  
35.7  
38.5  
41.4  
44.5  
47.7  
17.8  
18.5  
19.4  
20.6  
22.1  
23.8  
25.7  
27.8  
30.2  
32.8  
35.5  
38.3  
41.3  
44.3  
47.5  
16.8  
17.6  
18.7  
20.0  
21.6  
23.4  
25.5  
27.7  
30.1  
32.7  
35.5  
38.3  
41.2  
44.2  
47.3  
50.5  
53.8  
57.0  
60.4  
15.8  
16.8  
18.0  
19.6  
21.3  
23.2  
25.3  
27.6  
30.1  
32.7  
35.5  
38.3  
41.1  
44.1  
47.2  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
51.1  
54.5  
58.0  
61.5  
50.7  
54.0  
57.4  
50.3  
53.5  
56.7  
60.0  
60.8  
Correction Factors - Other Airflows“(Table Value  
Correction Factor = Value at new airflow)  
Airflow = 5000 cfm (8494 m 3/h)  
Heating Capacity (High Tem p.) = 151,000 (44.27)  
Heating Capacity (Low Tem p.) = 95,000 (27.67)  
Com pressor Power (High Tem p) = 10.94 kW  
Com pressor Power (Low Tem p) = 9.18 kW  
Coeff. Of Perf. (High Tem p) = 3.2  
Airflow  
4500 cfm  
5500 cfm  
7645 m 3/h 9344 m 3/h  
Heating Capacity  
Com pressor kW  
x 0.99  
x1.02  
x1.01  
x0.98  
Coeff. Of Perf. (Low Tem p) = 2.3  
Outdoor Fan Power = 1100 watts  
Values at ARI Rating Conditions of:  
Indoor Fan Power = 1700 watts  
70F(21.1C)and 47/43F(8.3/6.1C)(High Tem p.Cond.)  
70F(21.1C)and 17/15F(-8.3/-9.4C)(Low Tem p. Cond)  
Note:  
1.Rated with 25 feet of 1-3/8"" suction and 1/2"" liquid line."  
22  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Sys t e m )  
Table PD-12 — Gross Heating Capacities (MBh)  
TWA200B Heat Pump with TWE200B Air Handler At 6675 CFM (I-P)  
Outdoor  
Heating Capacity (BTUH/1000) At  
Total Power in Kilowatts At  
Temperature  
(°F)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
60  
70  
75  
80  
60  
70  
75  
80  
-18  
-13  
-8  
-3  
2
43.5  
68.9  
82.3  
80.3  
87.1  
94.2  
85.7  
91.0  
97.0  
88.4  
93.0  
98.4  
104.5  
111.3  
10.8  
12.3  
13.0  
13.4  
13.8  
14.1  
14.5  
14.8  
15.1  
15.4  
15.7  
16.0  
16.4  
16.7  
17.2  
14.5  
14.8  
15.1  
15.3  
15.6  
15.8  
16.1  
16.4  
16.7  
17.1  
15.6  
15.8  
16.0  
16.2  
16.4  
16.7  
17.0  
17.3  
17.6  
18.0  
18.4  
18.8  
19.2  
19.7  
20.2  
20.7  
21.2  
21.8  
22.4  
16.5  
16.7  
16.8  
17.1  
17.3  
17.6  
93.2  
101.6  
109.4  
117.8  
126.8  
136.4  
146.7  
157.6  
169.3  
181.2  
193.5  
206.5  
220.3  
234.6  
249.2  
264.0  
279.4  
103.6  
110.8  
118.6  
127.2  
136.5  
146.5  
157.2  
168.8  
180.5  
192.7  
205.7  
219.4  
233.6  
248.2  
262.9  
278.2  
103.5  
113.7  
124.2  
135.0  
146.2  
157.9  
170.2  
182.4  
195.1  
208.4  
222.4  
236.9  
251.7  
266.7  
282.3  
7
118.8  
127.1  
136.1  
146.0  
156.6  
168.1  
179.8  
192.0  
205.0  
218.7  
232.9  
247.4  
262.1  
277.2  
12  
17  
22  
27  
32  
37  
42  
47  
52  
57  
62  
67  
72  
17.9  
18.2  
18.5  
18.9  
19.4  
19.8  
20.3  
20.8  
21.3  
21.9  
22.4  
23.0  
23.7  
17.4  
17.8  
18.2  
18.6  
19.1  
19.6  
20.1  
20.6  
21.2  
17.6  
18.1  
18.5  
19.1  
Table PD-12 — Gross Heating Capacities (kW)  
TWA200B Heat Pump with TWE200B Air Handler At 11340 m 3/h (SI)  
Outdoor  
Heating Capacity (kW) At  
Total Power in Kilowatts At  
Temperature  
(°C)  
Indicated Indoor Dry BulbTemperature  
Indicated Indoor Dry BulbTemperature  
15.6  
21.1  
23.9  
26.7  
15.6  
21.1  
23.9  
26.7  
27.8  
-25.0  
-22.2  
-19.4  
-16.7  
-13.9  
-11.1  
-8.3  
-5.6  
-2.8  
0.0  
2.8  
5.6  
8.3  
11.1  
13.9  
16.7  
19.4  
22.2  
12.7  
20.2  
24.1  
27.3  
30.3  
33.3  
36.4  
39.5  
42.8  
46.2  
49.8  
53.4  
57.1  
61.0  
65.1  
69.4  
73.7  
78.1  
82.7  
23.5  
25.5  
27.6  
29.7  
32.0  
34.5  
37.1  
39.9  
42.9  
46.2  
49.6  
53.0  
56.7  
60.5  
64.5  
68.7  
73.0  
77.3  
25.1  
26.6  
28.4  
30.3  
32.4  
34.7  
37.2  
40.0  
42.9  
46.0  
49.4  
52.8  
56.4  
60.2  
64.3  
68.4  
72.7  
77.0  
25.9  
27.2  
5.5  
5.6  
5.7  
5.8  
5.9  
6.0  
6.2  
6.3  
6.5  
6.6  
6.8  
6.9  
7.1  
7.3  
7.5  
7.7  
7.9  
8.1  
8.4  
6.0  
6.1  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.6  
7.8  
8.0  
8.2  
8.4  
8.7  
8.9  
9.2  
6.2  
6.3  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
6.5  
6.6  
6.7  
6.9  
7.0  
7.2  
7.4  
7.5  
7.7  
28.8  
30.6  
32.6  
34.8  
37.2  
39.9  
42.7  
45.9  
49.2  
52.6  
56.2  
60.0  
64.0  
68.2  
72.4  
76.7  
81.2  
7.9  
8.1  
8.3  
8.5  
8.8  
9.0  
9.2  
9.5  
9.8  
10.0  
7.9  
8.1  
8.4  
8.6  
8.8  
9.1  
9.3  
9.6  
81.8  
81.5  
Correction Factors - Other Airflows  
(Table Value x Correction Factor = Value at new airflow)  
Airflow = 6675 cfm (11340 m 3/h)  
Heating Capacity (High Tem p.) = 206,000 (60.26)  
Heating Capacity (Low Tem p.) = 135,000 (39.66)  
Com pressor Power (High Tem p) = 14.92 kW  
Com pressor Power (Low Tem p) = 12.62 kW  
Coeff. Of Perf. (High Tem p) = 3.2  
Airflow  
6000 cfm  
7325 cfm  
10193 m 3/h 12444 m 3/h  
Heating Capacity  
Com pressor kW  
x0.99  
x1.02  
x1.01  
x0.98  
Coeff. Of Perf. (Low Tem p) = 2.4  
Values at ARI Rating Conditions of:  
Outdoor Fan Power = 1,100 watts  
70F(21.1C)and 47/43F(8.3/6.1C)(High Tem p.Cond.)  
70F(21.1C)and 17/15F(-8.3/-9.4C)(Low Tem p. Cond)  
Indoor Fan Power = 2,290 watts  
Note:  
1. Rated with 25 feet of 1-3/8” suction and 1/2" liquid line."  
SSP-PRC002-EN  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Air Ha n d le r)  
Table PD-13 — Evaporator Fan Performance TWE050A (I-P)  
External Static Pressure (Inches of Water Colum n)  
.10"  
.20"  
.30"  
.40" .50" .60" .70" .80"  
.90"  
1.00"  
1.10"  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
2100  
646 0.37 698 0.42 751 0.47 803 0.52 856 0.56 908 0.61 941 0.65 973 0.68 1006 0.71  
607 0.36 661 0.40 713 0.45 764 0.50 816 0.54 867 0.59 919 0.64 952 0.67 984 0.71  
625 0.38 676 0.43 727 0.48 778 0.52 828 0.57 879 0.62 930 0.67 963 0.70 995 0.74  
601 0.35 648 0.40 696 0.44 744 0.49 792 0.54 841 0.59 889 0.64 937 0.69 971 0.73 1005 0.77  
625 0.36 671 0.41 716 0.46 762 0.51 807 0.56 853 0.61 898 0.66 944 0.71 979 0.76  
642 0.40 687 0.45 731 0.50 776 0.55 820 0.60 865 0.66 909 0.71 951 0.75 987 0.80  
659 0.44 703 0.49 745 0.54 790 0.60 833 0.65 877 0.70 920 0.75 957 0.80 994 0.84  
674 0.48 722 0.54 770 0.60 817 0.65 857 0.70 897 0.75 936 0.80 973 0.85 1009 0.89  
0 .7 5 HP S t a n d a rd Mo t o r a n d S t a n d a rd S t a t ic Drive  
1 .0 HP Ove rs ize d Mo t o r a n d Hig h S t a t ic Drive  
Notes:  
1. Perform ance based on a wet coil and 1 inch (25.4 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are m ade in 0.5 turn increm ents.  
Table PD-13— Evaporator Fan Performance — TWE050A (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125  
150  
174  
199  
224  
249  
274  
m3/hr  
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
2379  
2549  
2718  
2888  
3058  
3228  
3398  
3568  
646 0.28 698 0.31 751 0.35 803 0.39 856 0.42 908 0.45 941 0.48 973 0.51 1006 0.53  
607 0.27 661 0.30 713 0.34 764 0.37 816 0.40 867 0.44 919 0.48 952 0.50 984 0.53  
625 0.28 676 0.32 727 0.36 778 0.39 828 0.43 879 0.46 930 0.50 963 0.52 995 0.55  
601 0.26 648 0.30 696 0.33 744 0.37 792 0.40 841 0.44 889 0.48 937 0.51 971 0.54 1005 0.57  
625 0.27 671 0.31 716 0.34 762 0.38 807 0.42 853 0.45 898 0.49 944 0.53 979 0.57  
642 0.30 687 0.34 731 0.37 776 0.41 820 0.45 865 0.49 909 0.53 951 0.56 987 0.60  
659 0.33 703 0.37 745 0.40 790 0.45 833 0.48 877 0.52 920 0.56 957 0.60 994 0.63  
674 0.36 722 0.40 770 0.45 817 0.48 857 0.52 897 0.56 936 0.60 973 0.63 1009 0.66  
0 .5 6 k W S t a n d a rd Mo t o r a n d S t a n d a rd S t a t ic Drive 0 .7 5 k W Ove rs ize d Mo t o r a n d Hig h S t a t ic Drive  
Notes:  
1. Perform ance based on a wet coil and 1 inch (25.4 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are m ade in 0.5 turn increm ents.  
Table PD-14 — Blower Speeds — TWE050A  
Motor DriveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
N/A  
590  
639  
688  
737  
786  
835  
High Static  
N/A  
713  
772  
832  
891  
951  
1009  
24  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Air Ha n d le r)  
Table PD-15 — Evaporator Fan Performance TWE075A (I-P)  
External Static Pressure (In. Of Water Colum n)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.10  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
2000  
2125  
2250  
2375  
2500  
2625  
2750  
2875  
3000  
443 0.44 489 0.49 535 0.54 581 0.59 627 0.64 673 0.69 719 0.74 765 0.79 791 0.83 818 0.89  
453 0.46 499 0.52 546 0.57 592 0.63 638 0.68 684 0.74 730 0.79 771 0.85 798 0.90 825 0.96  
463 0.49 510 0.55 556 0.61 602 0.67 649 0.73 695 0.79 742 0.85 776 0.91 804 0.97 831 1.03  
473 0.51 520 0.57 567 0.64 613 0.70 660 0.77 706 0.83 753 0.90 782 0.97 810 1.03 838 1.10  
445 0.47 489 0.54 533 0.60 578 0.67 622 0.73 667 0.80 711 0.86 756 0.93 784 0.99 813 1.07 842 1.14  
464 0.50 506 0.57 548 0.63 589 0.69 631 0.76 672 0.82 714 0.88 757 0.95 786 1.01 815 1.09 844 1.17  
484 0.53 523 0.59 562 0.66 601 0.72 640 0.78 678 0.84 717 0.91 758 0.97 787 1.03 817 1.12 847 1.21  
504 0.56 540 0.62 576 0.68 612 0.74 648 0.81 684 0.87 720 0.93 759 0.99 789 1.05 819 1.15 850 1.24  
524 0.59 557 0.65 590 0.71 624 0.77 657 0.83 690 0.89 723 0.95 760 1.01 790 1.07 821 1.17 853 1.27  
1 .0 HP S t a n d a rd Mo t o r  
and Low Static Drive  
1 .0 HP S t a n d a rd Mo t o r  
and Drive  
1 .5 HP Ove rs ize d Mo t o r  
a n d Hig h S t a t ic Drive  
Notes:  
1. Perform ance based on a wet coil and 1 inch (25.4 m m )  
throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output  
required.  
3. Factory setting of m otor sheave is 1.5 turns open.  
Adjustm ents are m ade in 0.5 turn increm ents.  
Table PD-15— Continued  
External Static Pressure (In. Of Water Colum n)  
1.20 1.30 1.40 1.50 1.60  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
844 0.96 871 1.02 897 1.09 924 1.15 950 1.21  
852 1.03 879 1.09 906 1.16 933 1.22  
859 1.10 886 1.17 914 1.23 942 1.30  
866 1.17 894 1.24 922 1.30 950 1.37  
870 1.21 899 1.29 928 1.36  
874 1.25 903 1.33 932 1.42  
877 1.29 907 1.38 937 1.47  
880 1.33 911 1.43 942 1.52  
884 1.37 915 1.48 946 1.58  
1 .5 HP Ove rs ize d Mo t o r  
2000  
2125  
2250  
2375  
2500  
2625  
2750  
2875  
3000  
a n d Hig h S t a t ic Drive  
1.0 HP Standard Motor  
and Drive  
Table PD-15 — Evaporator Fan Performance TWE075A (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125 150 174  
199  
224  
249  
274  
m3/hr  
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
3338  
3547  
3755  
3964  
4173  
4381  
4590  
4798  
5007  
443 0.33 489 0.37 535 0.4 581 0.44 627 0.48 673 0.51 719 0.55 765 0.59 791 0.62 818 0.66  
453 0.34 499 0.39 546 0.43 592 0.47 638 0.51 684 0.55 730 0.59 771 0.63 798 0.67 825 0.72  
463 0.37 510 0.41 556 0.45 602 0.5 649 0.54 695 0.59 742 0.63 776 0.68 804 0.72 831 0.77  
473 0.38 520 0.43 567 0.48 613 0.52 660 0.57 706 0.62 753 0.67 782 0.72 810 0.77 838 0.82  
445 0.35 489 0.4 533 0.45 578 0.5 622 0.54 667 0.6 711 0.64 756 0.69 784 0.74 813 0.8 842 0.85  
464 0.37 506 0.43 548 0.47 589 0.51 631 0.57 672 0.61 714 0.66 757 0.71 786 0.75 815 0.81 844 0.87  
484 0.4 523 0.44 562 0.49 601 0.54 640 0.58 678 0.63 717 0.68 758 0.72 787 0.77 817 0.84 847 0.9  
504 0.42 540 0.46 576 0.51 612 0.55 648 0.6 684 0.65 720 0.69 759 0.74 789 0.78 819 0.86 850 0.92  
524 0.44 557 0.48 590 0.53 624 0.57 657 0.62 690 0.66 723 0.71 760 0.75 790 0.8 821 0.87 853 0.95  
.75 kW Standard Motor  
and Low Static Drive  
.75 kW Standard Motor  
and Drive  
1.12 kW Oversized Motor  
a n d Hig h S t a t ic Drive  
Notes:  
Table PD-15 — Continued  
1. Perform ance based on a wet coil and 1 inch (25.4 m m )  
throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft  
output required.  
3. Factory setting of m otor sheave is 1.5 turns open.  
Adjustm ents are m ade in 0.5 turn increm ents.  
External Static Pressure (Pascal)  
299  
324 349 374  
398  
m3/hr  
RPM kW RPM kW RPM kW RPM kW RPM kW  
3338  
3547  
3755  
3964  
4173  
4381  
4590  
4798  
5007  
844 0.72 871 0.76 897 0.81 924 0.86 950 0.9  
852 0.77 879 0.81 906 0.87 933 0.91  
859 0.82 886 0.87 914 0.92 942 0.97  
866 0.87 894 0.92 922 0.97 950 1.02  
Table PD-16 — Blower Speeds — TWE075A  
870 0.9 899 0.96 928 1.01  
874 0.93 903 0.99 932 1.06  
877 0.96 907 1.03 937 1.1  
880 0.99 911 1.07 942 1.13  
884 1.02 915 1.1 946 1.18  
Motor DriveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
Low Static  
High Static N/A  
N/A  
N/A  
600  
428  
700  
650  
464  
750  
700  
499  
800  
750  
535  
850  
800  
571  
900  
850  
606  
950  
1 .1 2 k W Ove rs ize d Mo t o r a n d Hig h S t a t ic Drive  
.75 kW Standard Motor  
and Drive  
SSP-PRC002-EN  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Air Ha n d le r)  
Table PD-17 — Evaporator Fan Performance TWE100A, TWE100B (I-P)  
External Static Pressure (In. Of Water Colum n)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.20  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
1.5 HP Standard Motor and Low Static Drive  
2600  
2775  
2950  
3125  
3300  
3475  
3650  
3825  
4000  
460 0.32 493 0.39 527 0.47 565 0.55 603 0.63 641 0.71 679 0.79 717 0.87 744 0.94 772 1.01 826 1.16  
473 0.37 506 0.45 540 0.53 576 0.61 613 0.69 649 0.77 686 0.85 723 0.93 748 1.00 775 1.07 830 1.20  
487 0.43 519 0.50 552 0.58 587 0.67 623 0.75 658 0.83 693 0.91 728 0.99 751 1.06 779 1.12 833 1.25  
501 0.49 532 0.56 565 0.64 599 0.72 632 0.81 666 0.89 700 0.97 734 1.05 755 1.11 783 1.18 737 1.30  
520 0.58 548 0.65 581 0.73 613 0.81 644 0.89 677 0.98 710 1.06 740 1.13 759 1.19 787 1.25 841 1.37  
541 0.69 568 0.76 600 0.84 631 0.93 658 1.00 691 1.08 721 1.16 746 1.21 764 1.28 793 1.34 846 1.48  
562 0.82 588 0.88 618 0.97 648 1.05 671 1.11 703 1.19 732 1.27 753 1.31 772 1.38 801 1.45 853 1.59  
582 0.96 608 1.03 637 1.11 666 1.20 685 1.26 711 1.31 739 1.38 763 1.44 787 1.51 815 1.58 862 1.74  
602 1.11 628 1.17 656 1.26 683 1.35 698 1.40 720 1.43 747 1.50 773 1.58 801 1.64 829 1.71 872 1.89  
1 .5 HP S t a n d a rd Mo t o r a n d Drive  
2 .0 HP Ove rs ize d Mo t o r  
a n d Hig h S t a t ic Drive  
Notes:  
1. Perform ance based on a wet coil and 1 inch (25.4 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are  
m ade in 0.5 turn increm ents.  
Table PD-17— Continued  
External Static Pressure (In. Of Water Colum n)  
4. Low Static Drive m ust be field supplied.  
1.40 1.60  
CFM  
RPM BHP RPM BHP  
2 .0 HP Ove rs ize d Mo t o r a n d Hig h S t a t ic Drive  
2600  
2775  
2960  
3125  
3300  
3475  
3650  
3825  
4000  
881 1.30 936 1.45  
884 1.36 938 1.51  
886 1.41 939 1.57  
889 1.47 941 1.64  
892 1.54 945 1.73  
897 1.63 950 1.85  
902 1.73 955 1.99  
912 1.89 960 2.18  
922 2.04 965 2.30  
Table PD-17— Evaporator Fan Performance TWE0100A, TWE100B (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125  
150  
174  
199  
224  
249  
299  
m3/hr  
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
1.12 kW Standard Motor and Low Static Drive  
4417  
460 0.24 493 0.29 527 0.35 565 0.41 603 0.47 641 0.53 679 0.59 717 0.65 744 0.7 772 0.75 826 0.87  
473 0.28 506 0.34 540 0.4 576 0.45 613 0.51 649 0.57 686 0.63 723 0.69 748 0.75 775 0.8 830 0.89  
487 0.32 519 0.37 552 0.43 587 0.5 623 0.56 658 0.62 693 0.68 728 0.74 751 0.79 779 0.84 833 0.93  
501 0.37 532 0.42 565 0.48 599 0.54 632 0.6 666 0.66 700 0.72 734 0.78 755 0.83 783 0.88 737 0.97  
520 0.43 548 0.48 581 0.54 613 0.6 644 0.66 677 0.73 710 0.79 740 0.84 759 0.89 787 0.93 841 1.02  
4715  
5012  
5309  
5607  
5904  
6201  
6499  
6796  
541 0.51 568 0.57 600 0.63 631 0.69 658 0.75 691 0.8 721 0.87 746 0.9 764 0.95 793  
1
846 1.1  
562 0.61 588 0.66 618 0.72 648 0.78 671 0.83 703 0.89 732 0.95 753 0.98 772 1.03 801 1.08 853 1.19  
582 0.72 608 0.77 637 0.83 666 0.89 685 0.94 711 0.98 739 1.03 763 1.07 787 1.13 815 1.18 862 1.3  
602 0.83 628 0.87 656 0.94 683 1.01 698 1.04 720 1.07 747 1.12 773 1.18 801 1.22 829 1.28 872 1.41  
1 .1 2 k W S t a n d a rd Mo t o r a n d Drive  
1 .4 9 k W Ove rs ize d Mo t o r  
a n d Hig h S t a t ic Drive  
Notes:  
1. Perform ance based on a wet coil and 1 inch (25.4 m m )  
throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 3.0 turns open. Adjustm ents are  
m ade in 0.5 turn increm ents.  
Table PD-17— Continued  
External Static Pressure (Pascal)  
349 398  
RPM kW RPM kW  
4. Low Static Drive m ust be field supplied.  
m3/hr  
1 .4 9 k W Ove rs ize d Mo t o r a n d Hig h S t a t ic Drive  
4417  
4715  
5012  
5309  
5607  
5904  
6201  
6499  
6796  
881 0.97 936 1.08  
884 1.01 938 1.13  
886 1.05 939 1.17  
889 1.1 941 1.22  
892 1.15 945 1.29  
897 1.22 950 1.38  
902 1.29 955 1.48  
912 1.41 960 1.63  
922 1.52 965 1.72  
Table PD - 18 — Blower Speeds — TWE100A,TWE100B  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
N/A  
587  
453  
606  
745  
629  
485  
641  
789  
671  
518  
677  
833  
713  
550  
713  
877  
755  
583  
748  
920  
796  
615  
784  
965  
Low Static N/A  
High Static N/A  
High Static II N/A  
26  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Air Ha n d le r)  
Table PD-19 — Evaporator Fan Performance — TWE155B (I-P)  
External Static Pressure (Inches of Water Colum n)  
.10"  
.20"  
.30"  
.40"  
.50" .60" .70" .80"  
.90"  
1.00"  
1.20"  
1.40"  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
3 .0 HP Ove rs ize d Mo t o r  
2 .0 HP S t a n d a rd Mo t o r a n d Drive  
a n d Hig h S t a t ic Drive  
4000  
4250  
4500  
4750  
5000  
5260  
5500  
5750  
6000  
628 1.34 653 1.38 678 1.43 692 1.48 708 1.52 723 1.57 738 1.60 749 1.61 759 1.62 795 1.66 851 1.85 907 2.03  
633 1.37 658 1.41 683 1.46 697 1.51 713 1.55 728 1.60 743 1.62 751 1.63 770 1.64 806 1.71 862 1.90 918 2.11  
637 1.40 662 1.44 687 1.49 701 1.53 717 1.58 732 1.63 747 1.64 754 1.65 782 1.67 817 1.76 873 1.96 929 2.19  
641 1.42 666 1.50 691 1.53 705 1.61 721 1.63 736 1.65 751 1.66 765 1.67 793 1.72 828 1.81 884 2.01 940 2.27  
645 1.44 670 1.52 695 1.56 710 1.65 725 1.67 739 1.68 758 1.70 777 1.74 806 1.81 839 1.91 896 2.13  
650 1.46 675 1.53 700 1.59 716 1.67 728 1.70 741 1.73 765 1.75 790 1.82 819 1.92 849 2.03 907 2.28  
652 1.47 678 1.55 703 1.63 721 1.71 734 1.75 747 1.78 775 1.83 804 1.92 832 2.03 861 2.15 920 2.44  
653 1.48 680 1.57 706 1.68 726 1.76 743 1.81 761 1.86 789 1.94 817 2.04 846 2.16 875 2.29 935 2.61  
655 1.49 681 1.59 709 1.74 731 1.80 752 1.87 774 1.94 803 2.05 831 2.17 860 2.29 889 2.44 950 2.78  
Notes:  
1. Perform ance based on a wet coil and 2 inch (51 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are m ade in 0.5 turn increm ents.  
Table PD-19 — Evaporator Fan Performance TWE155B (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100  
125  
150  
174  
199  
224  
249  
299  
349  
m3/hr  
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
2 .2 4 k W Ove rs ize d Mo t o r  
1 .4 9 k W S t a n d a rd Mo t o r a n d Drive  
a n d Hig h S t a t ic Drive  
6796  
7221  
7646  
8070  
8495  
8937  
9345  
9769  
10194  
628  
1
653 1.03 678 1.07 692 1.1 708 1.13 723 1.17 738 1.19 749 1.2 759 1.21 795 1.24 851 1.38 907 1.51  
633 1.02 658 1.05 683 1.09 697 1.13 713 1.16 728 1.19 743 1.21 751 1.22 770 1.22 806 1.28 862 1.42 918 1.57  
637 1.04 662 1.07 687 1.11 701 1.14 717 1.18 732 1.22 747 1.23 754 1.23 782 1.25 817 1.31 873 1.46 929 1.63  
641 1.06 666 1.12 691 1.14 705 1.2 721 1.22 736 1.23 751 1.24 765 1.25 793 1.28 828 1.35 884 1.5 940 1.69  
645 1.07 670 1.13 695 1.16 710 1.23 725 1.25 739 1.25 758 1.27 777 1.3 806 1.35 839 1.42 896 1.59  
650 1.09 675 1.14 700 1.19 716 1.25 728 1.27 741 1.29 765 1.3 790 1.36 819 1.43 849 1.51 907 1.7  
652 1.1 678 1.16 703 1.22 721 1.28 734 1.3 747 1.33 775 1.36 804 1.43 832 1.51 861 1.6 920 1.82  
653 1.1 680 1.17 706 1.25 726 1.31 743 1.3 761 1.39 789 1.45 817 1.52 846 1.61 875 1.71 935 1.95  
655 1.11 681 1.19 709 1.3 731 1.34 752 1.35 774 1.45 803 1.53 831 1.62 860 1.71 889 1.82 950 2.07  
Notes:  
1. Perform ance based on a wet coil and 2 inch (51 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are m ade in 0.5 turn increm ents.  
Table PD-20— Blower Speeds — TWE155B  
Motor SheaveTurns Open  
Drive  
6
5
4
3
2
1
0
Standard  
High Static  
619  
777  
648  
806  
677  
835  
705  
863  
734  
892  
763  
921  
N/A  
950  
SSP-PRC002-EN  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
(Air Ha n d le r)  
Table PD-21— Evaporator Fan Performance TWE200B (I-P)  
External Static Pressure (In. Of Water Colum n)  
0.10  
0.20  
0.30  
0.40 0.50 0.60 0.70 0.80  
0.90  
1.00  
1.20  
140  
CFM  
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP  
5200  
5525  
5850  
6175  
6500  
6825  
7150  
7475  
7800  
461 0.74 503 0.91 545 1.07 587 1.03 619 1.17 685 1.40 723 1.59 750 1.74 777 1.89 851 2.19 898 2.39  
479 0.88 521 1.04 563 1.21 605 1.21 640 1.35 701 1.58 739 1.77 766 1.92 793 2.07 859 2.37 906 2.60  
497 1.01 539 1.18 581 1.34 623 1.39 661 1.53 717 1.76 755 1.95 782 2.10 809 2.25 868 2.55 915 2.81  
473 0.99 515 1.15 557 1.31 599 1.48 641 1.57 682 1.71 732 1.94 769 2.12 796 2.27 823 2.43 877 2.73 924 3.02  
492 1.12 534 1.28 576 1.45 618 1.61 660 1.75 702 1.90 748 2.12 784 2.30 811 2.45 838 2.60 886 2.91 933 3.22  
510 1.25 552 1.42 594 1.59 636 1.75 678 1.91 723 2.10 763 2.30 794 2.47 820 2.62 846 2.77 894 3.09 941 3.42  
528 1.38 570 1.56 612 1.73 654 1.90 697 2.07 744 2.30 779 2.49 804 2.64 830 2.78 855 2.94 903 3.26 950 3.62  
550 1.61 594 1.77 640 1.92 683 2.08 721 2.29 760 2.50 790 2.67 815 2.81 840 2.96 865 3.11 914 3.47 959 3.85  
572 1.83 618 1.97 668 2.10 712 2.27 746 2.52 776 2.69 802 2.84 826 2.99 851 3.13 876 3.27 926 3.67 969 4.08  
3 .0 HP S t a n d a rd  
Mo t o r a n d Lo w  
Static Drive  
3 HP S t a n d a rd  
Mo t o r a n d Lo w  
S t a t ic Drive S ys t e m II  
3 HP S t a n d a rd Mo t o r  
and Standard  
5 HP Ove rs ize d Mo t o r  
a n d Hig h S t a t ic  
Drive System  
Drive System  
Notes:  
1. Perform ance based on a wet coil and 2 inch (51 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are m ade in  
0.5 turn increm ents.  
Table PD-21— Continued  
External Static Pressure (In. Of Water Colum n)  
1.60 1.80  
4. Low static drive com ponents referencing this note are field supplied.  
CFM  
RPM BHP RPM BHP  
5 HP Ove rs ize d Mo t o r a n d Hig h S t a t ic Drive S ys t e m  
5200  
5525  
5850  
5175  
8500  
8825  
7150  
7475  
7800  
944 2.75 989 3.12  
952 2.96 997 3.33  
961 3.17 1006 3.54  
970 3.38 1015 3.75  
978 3.59 1023 3.96  
986 3.80  
994 4.01  
1003 4.25  
1012 4.50  
Table PD-21— Evaporator Fan Performance TWE200B (SI)  
External Static Pressure (Pascal)  
25  
50  
75  
100 125 150  
174  
199  
224  
249  
299  
349  
m3/hr  
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW  
8835  
9387  
9939  
461 0.55 503 0.68 545 0.8 587 0.77 619 0.87 685 1.04 723 1.19 750 1.3 777 1.41 851 1.63 898 1.78  
479 0.66 521 0.78 563 0.9 605 0.9 640 1.01 701 1.18 739 1.32 766 1.43 793 1.54 859 1.77 906 1.94  
497 0.75 539 0.88 581  
1
623 1.04 661 1.14 717 1.31 755 1.45 782 1.57 809 1.68 868 1.9 915 2.1  
10491  
11044  
11596  
12148  
12700  
13252  
473 0.74 515 0.86 557 0.98 599 1.1 641 1.17 682 1.28 732 1.45 769 1.58 796 1.69 823 1.81 877 2.04 924 2.52  
492 0.84 534 0.95 576 1.08 618 1.2 660 1.3 702 1.42 748 1.58 784 1.72 811 1.83 838 1.94 886 2.17 933 2.4  
510 0.93 552 1.06 594 1.19 636 1.3 678 1.42 723 1.57 763 1.72 794 1.84 820 1.95 846 2.07 894 2.3 941 2.55  
528 1.03 570 1.16 612 1.29 654 1.42 697 1.54 744 1.72 779 1.86 804 1.97 830 2.07 855 2.19 903 2.43 950 2.7  
550 1.2 594 1.32 640 1.43 683 1.55 721 1.71 760 1.87 790 1.99 815 2.1 840 2.21 865 2.32 914 2.59 959 2.87  
572 1.36 618 1.47 668 1.57 712 1.69 746 1.88 776 2.01 802 2.12 826 2.23 851 2.33 876 2.44 926 2.74 969 3.04  
2 .2 4 k W S t a n d a rd  
Mo t o r a n d Lo w  
Static Drive System  
2 .2 4 k W S t a n d a rd  
Mo t o r a n d Lo w  
S t a t ic Drive S ys t e m II  
2 .2 4 k W S t a n d a rd  
Mo t o r a n d S t a n d a rd  
Drive System  
3 .7 3 k W Ove rs ize d Mo t o r  
a n d Hig h S t a t ic Drive S ys t e m  
Notes:  
1. Perform ance based on a wet coil and 2 inch (51 m m ) throwaway filters.  
2. Tabulated brake horsepower is the m otor shaft output required.  
3. Factory setting of m otor sheave is 1.5 turns open. Adjustm ents are m ade in  
0.5 turn increm ents.  
Table PD-21— Continued  
External Static Pressure (Pascal)  
398 448  
RPM kW RPM kW  
4. Low static drive com ponents referencing this note are field supplied.  
m3/hr  
3 .7 3 k W Ove rs ize d Mo t o r  
a n d Hig h S t a t ic Drive S ys t e m  
8835  
9387  
9939  
944 2.05 989 2.33  
952 2.21 997 2.48  
961 2.36 1006 2.64  
970 2.52 1015 2.8  
978 2.68 1023 2.95  
Table PD-22 — Blower Speeds — TWE200B  
Motor SheaveTurns Open  
10491  
11044  
11596  
12148  
12700 1003 3.17  
13252 1012 3.36  
Drive  
6
5
4
3
2
1
0
986 2.83  
994 2.99  
Standard  
706  
457  
574  
N/A  
732  
478  
595  
821  
758  
500  
617  
862  
784  
521  
638  
903  
811  
542  
659  
945  
837  
563  
680  
986  
863  
585  
702  
Low Static I  
Low Static II  
High Static  
1027  
28  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
Table PD-23— Discharge Plenum And Grille Assembly Throw Distance — Air Handler  
Unit  
Louver Angle Deflection Position  
Model No.  
CFM  
m3/h  
Straight  
20, ft (m)  
40, ft (m)  
55, ft (m)  
1400  
1600  
1800  
2000  
2200  
2100  
2378  
2718  
3058  
3398  
3737  
3568  
38 (11.6)  
42 (12.8)  
46 (14.0)  
48 (14.6)  
51 (15.5)  
49 (14.9)  
24 (7.3)  
22 (6.7)  
26 (7.9)  
29 (8.8)  
33 (10.1)  
36 (11.0)  
31 (9.4)  
18 (5.5)  
20 (6.1)  
22 (6.7)  
24 (7.3)  
25 (7.6)  
27 (8.2)  
31 (9.4)  
37 (11.3)  
43 (13.1)  
50 (15.2)  
38 (11.6)  
TWE050  
TWE075  
2400  
2700  
3000  
3200  
3600  
4077  
4587  
5097  
5436  
6116  
52 (15.9)  
55 (16.8)  
58 (17.7)  
56 (17.1)  
62 (18.9)  
43 (13.1)  
48 (14.6)  
53 (16.2)  
46 (14.0)  
51 (15.5)  
35 (10.7)  
38 (11.6)  
42 (12.8)  
38 (11.6)  
42 (12.8)  
29 (8.8)  
31 (9.4)  
32 (9.8)  
30 (9.1)  
33 (10.1)  
4000  
4400  
4800  
4300  
4900  
6795  
7475  
8154  
7305  
8324  
66 (20.1)  
71 (21.6)  
76 (23.2)  
42 (12.8)  
47 (14.3)  
57 (17.4)  
62 (18.9)  
67 (20.4)  
32 (9.8)  
47 (14.3)  
52 (15.9)  
56 (17.1)  
29 (8.8)  
32 (9.8)  
35 (10.7)  
38 (11.6)  
42 (12.8)  
21 (6.4)  
25 (7.6)  
TWE100  
TWE155  
TWE200  
38 (11.6)  
5400  
5600  
6000  
6400  
9174  
9514  
10193  
52 (15.9)  
50 (15.2)  
57 (17.4)  
56 (17.1)  
44 (13.4)  
40 (12.2)  
49 (14.9)  
46 (14.0)  
37 (11.3)  
33 (10.1)  
41 (12.5)  
38 (11.6)  
29 (8.8)  
27 (8.2)  
32 (9.8)  
30 (9.1)  
10873  
7200  
8000  
12232  
13591  
62 (18.9)  
66 (20.1)  
51 (15.5)  
57 (17.4)  
42 (12.8)  
47 (14.3)  
33 (10.1)  
35 (10.7)  
Throw distance values are based on a terminal velocity of 75 FPM (0.38 m/s).  
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by  
throw factor:  
Term inal Velocity  
50 fpm (.25 m/s)  
100 fpm (.51 m/s)  
150 fpm (.76 m/s)  
Throw Factor  
x
x
x
1.50  
.75  
.50  
PD-24 — Static Pressure Drop Through Accessories — Air Handler  
Discharge  
Unit  
Model No.  
Return Grille  
In. wc1 Pascal In. wc1 Pascal  
Plenum and Grille2  
Electric Heaters (kW)  
CFM  
m3/h  
3.5-7  
10-14  
17-24  
35  
1400  
1600  
2000  
2100  
2378  
2718  
3398  
3568  
.09  
.12  
.18  
.05  
(22.4)  
(29.9)  
(44.8)  
(12.5)  
.16  
.21  
.33  
.19  
(39.8)  
(52.3)  
(82.2)  
(47.3)  
.06  
08  
.13  
.06  
.08  
.13  
.03  
.12  
.14  
.19  
.05  
.08  
TWE050A  
TWE075A  
.02  
2400  
3000  
4077  
5097  
.08  
.13  
(19.9)  
(32.4)  
.27  
.40  
(67.2)  
(99.6)  
.03  
.06  
.06  
.12  
.08  
.17  
.12  
.23  
TWE100A  
TWE100B  
2800  
3200  
4300  
4757  
5436  
7305  
.04  
.07  
.07  
(10.0)  
(17.4)  
(17.4)  
.34  
.43  
.18  
(84.7)  
(107.1)  
(44.8)  
.03  
.06  
.02  
.04  
.13  
.02  
.14  
.19  
.04  
.20  
.26  
.05  
4800  
5600  
6000  
8154  
9514  
10193  
.09  
.07  
.15  
(22.4)  
(17.4)  
(37.4)  
.23  
.32  
.34  
(57.3)  
(79.7)  
(84.7)  
.03  
.04  
.06  
.03  
.04  
.06  
.06  
.10  
.12  
.08  
.15  
.17  
TWE155B  
TWE200B  
6400  
8000  
10873  
13591  
.11  
.17  
(27.4)  
(42.3)  
.43  
.66  
(107.1)  
(164.3)  
.06  
.10  
.0-6  
.10  
.13  
.20  
.19  
.30  
1. Return air filter ESP included in Fan Perform ance Table data.  
2. At louver opening angle of 42°F (5.5°C). For ESP at other angle openings, see accessory Installers Guide.  
Throw distance values are based on a terminal velocity of 75 fpm (0.38 m/s).  
Throw distance values at other terminal velocities may be established by multiplying throw distances in table above by  
throw factor:  
Te rm in a l Ve lo c it y  
50 fpm (.25 m/s)  
100 fpm (.51 m/s)  
150 fpm (.76 m/s)  
Th ro w Fa c t o r  
x
x
x
1.50  
.75  
.50  
.
SSP-PRC002-EN  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pe rfo rm a n c e  
Data  
Table PD-25 — Auxiliary Electric Heat Capacity — Air Handler  
No.  
Stage 1  
Stage 2  
Btu  
Total  
Unit  
Total  
of  
kW  
Btu  
kW  
kW  
kW  
Btu  
kW  
Model No.  
kW Stages Input  
Output Output Input  
Output Output Output Output  
TWE050, 075,100  
3.47  
6.92  
10.39  
17.31  
1
1
1
2
3.47  
9.92  
10.39  
10.39  
11,851  
23,606  
35,457  
35,457  
3.47  
6.92  
10.39  
10.39  
11,851  
23,606  
35,457 10.39  
3.47  
6.92  
6.92  
23,606  
6.92 59,063 17.31  
TWE075, 100A, 100 24.22  
2
13.83  
47,213  
13.83  
10.39  
35,457 10.39 82,670 24.22  
TWE155, 200  
6.94  
13.83  
20.78  
34,62  
1
1
2
2
6.94  
13.83  
13.83  
20.78  
23,701  
47,213  
47,213  
70,915  
6.94  
13.83  
13.83  
20.78  
6.94  
13.84  
23,701  
47,213  
23,701  
47,213 13.83  
6.94  
6.94 70,915 20.78  
13.89 118,128 34.61  
*Heaters are rated at 400v. For other than rated voltage,  
2
2
Voltage  
Voltage  
Rated Voltage  
Capacity =  
x Rated Capacity and kW =  
x Rated kW.  
(
)
(
)
Rated Voltage  
30  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ele c t ric a l  
Da t a  
Table ED-1— Electrical Characteristics — Motors — Air Handler  
Standard Fan Motor  
Oversized Fan Motor  
Unit  
Amps  
Amps  
Model No.  
TWE050  
TWE075  
TWE100  
TWE155  
TWE200  
Volts  
Phase  
FLA  
1.4  
3.2  
3.6  
4.6  
7.6  
LRA  
8.2  
19.7  
25.5  
37.5  
39.2  
Phase  
FLA  
1.8  
4.0  
5.3  
6.9  
9.0  
LRA  
21.6  
25.5  
37.5  
39.2  
65.1  
380/415  
380/415  
380/415  
380/415  
380/415  
3
3
3
3
3
3
3
3
3
3
Table ED-2 — Unit Wiring — Air Handler  
Minimum  
Circuit  
Ampacity  
Maximum Fuse  
Size or Maximum  
Circuit Breaker  
Unit  
Model No.  
Unit Operating  
Voltage Range  
TWE050  
TWE075  
TWE100  
380/415  
380/415  
380/415  
2
4
5
15  
15  
15  
TWE155  
TWE200  
380/415  
380/415  
6
10  
15  
15  
Table ED-3— Electrical Characteristics — Motors — 50 Cycle — Heat Pumps  
Compressor Motor  
Condenser Fan Motor  
Amps  
FLA LRA  
Amps  
Unit  
RLA  
(Ea.)  
LRA  
(Ea.)  
Model No.  
No.  
Volts  
Phase  
No.  
Volts  
Phase  
(Ea.)  
(Ea.)  
TWA075AD  
TWA100AD  
TWA155BD  
TWA200BD  
1
1
2
2
380/415  
380/415  
380/415  
380/415  
3
3
3
3
8. 8  
90.0  
1
1
2
2
380/415  
380/415  
380/415  
380/415  
1
1
1
1
1.6  
2.7  
1.6  
2.7  
3.7  
7.0  
3.7  
7.0  
14.9  
11. 2  
14.9  
118.0  
94.8  
118.0  
Table ED-4 — Unit Wiring — Heat Pumps  
Minimum  
Circuit  
Ampacity  
Maximum Fuse  
Size or Maximum  
Circuit Breaker  
Unit  
Model No.  
Unit Operating  
Voltage Range  
TWA075  
TWA100  
380/415  
380/415  
12.6  
21.3  
50  
35  
TWA155  
TWA200  
380/415  
380/415  
28.4  
38.9  
35  
50  
SSP-PRC002-EN  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ele c t ric a l  
Da t a  
Table ED-5— Unit Wiring With Electric Heat (Single Point Connection) —Air Handlers  
Heater  
Model No.  
Heater  
kW Rating1  
3.47  
To Use  
with Unit  
Control  
Stages  
Minimum  
Maximum  
Fuse Breaker Size  
2
Circuit Ampacity 2  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL435A  
BAYHTRL405A  
BAYHTRL410A  
BAYHTRL415A  
BAYHTRL425A  
BAYHTRL435A  
BAYHTRM410A  
BAYHTRM420A  
BAYHTRM430A  
BAYHTRM450A  
BAYHTRM410A  
BAYHTRM420A  
BAYHTRM430A  
BAYHTRM450A  
1
1
1
2
1
1
1
2
2
1
1
1
2
2
1
1
2
2
1
1
2
2
9
17  
24  
39  
11  
15  
20  
25  
40  
15  
20  
30  
45  
60  
15  
25  
30  
45  
60  
30  
40  
60  
90  
40  
50  
60  
90  
6.92  
TWE050AD  
TWE075AD  
10.39  
17.31  
3.47  
6.92  
18  
26  
41  
56  
12  
19  
27  
42  
57  
21  
36  
51  
81  
25  
40  
55  
85  
10.39  
17.31  
24.22  
3.47  
6.92  
10.39  
20.78  
24.22  
6.94  
13.83  
20.78  
34.62  
6.94  
TWE100AD,TWE100BD  
TWE155BD  
13.83  
20.78  
34.62  
TWE200BD  
1. kW ratings are at 400v for 3 phase, 400v air handlers  
2
2
Voltage  
Voltage  
Rated Voltage  
For other than rated voltage, am pacity =  
x Rated Capacity and kW =  
Rated kW.  
(
)
(
)
Rated Voltage  
2. Any power supply and circuits m ust be wired and protected in accordance with local codes.  
3. Field wire m ust be rated at least 75°C.  
4. Field wire m ust be rated at least 90°C.  
32  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
J o b s it e  
Connections  
Wiring shown with dashed lines is to be  
furnished and installed by the customer.  
All customer- supplied wiring must be  
copper only and must conform to NEC  
and local electrical codes. Codes may  
require line of sight between disconnect  
switch and unit.  
NOTE:  
1.When electric heater accessory is used  
single point power entry or dual point  
power entry is field optional. Single point  
power entry option is through electric  
heater only.  
TWA050/TWE050  
Field Wiring:  
A
B
C
— 3 power wires. Line voltage.  
— 3 power wires. Line voltage.  
— Heat pump thermostat: 6 wires,  
24 volts.  
— Electric heat: add 2 additional  
wires, 24 volts.  
— 2 wires, 24 volts.  
D
— Outdoor thermostat: add 1  
additional wire per ODT, 24 volts.  
— Electric heat: add 1 additional  
wire, 24 volts.  
(2)TWA050/TWE100B  
Field Wiring:  
A
B
C
— 3 power wires. Line voltage.  
— 3 power wires. Line voltage.  
— Heat pump thermostat: 7 wires,  
24 volts Electric Heat: add 2  
additional wires, 24 volts.  
— 5 wires, 24 volts to outdoor  
section ’A 2 wires, 24 volts to  
outdoor section ’B’ 2 wires, 24  
volts between outdoor sections  
‘’A’ ‘’B’’  
TWA075A/TWE075A;  
TWA100A/TWE100A  
Field Wiring:  
D
— 9 wires, 24 volts.  
— Electric heat: add 4 additional  
wires, 24 volts.  
— Outdoor thermostat: add 3  
additional wires, 24 volts.  
A
B
C
— 3 power wires, line voltage.  
— 3 power wires, line voltage.  
— Heat pump thermostat: 6 wires,  
24 volts.  
D
TWA155B/TWE155B;  
TWA200B/TWE200B  
Field Wiring:  
A
B
C
— Electric heat: add 2 additional  
wires, 24 volts.  
— 3 power wires, line voltage.  
— 3 power wires, line voltage.  
— Heat pump thermostat: 7 wires,  
24 volts.  
— Electric heat: add 2 additional  
wires, 24 volts.  
D
— 6 wires, 24 volts.  
— Electric heat: add 1 additional  
wire, 24 volts.  
— Outdoor thermostat: add 1  
additional wire, 24 volt.  
— Outdoor thermostat: add 1  
additional wire, 24 volts.  
— Electric heat: add 1 additional  
wire, 24 volts.  
(2)TWA075A/TWE155B;  
(2)TWA100A/TWE200B  
Field Wiring:  
D
— 7 wires, 24 volts.  
— Electric heat: add 4 additional  
wires, 24 volts.  
A
B
C
— 3 power wires, line voltage.  
— 3 power wires, line voltage.  
— Heat pump thermostat: 7 wires,  
24 volts.  
— Outdoor thermostat: add 1  
additional wire, 24 volts.  
— Electric heat: add 2 additional  
wires, 24 volts.  
SSP-PRC002-EN  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typ ic a l  
Wirin g  
(He a t Pu m p )  
Heat Pump — Single Compressor  
Typical unit wiring diagram. For specific  
wiring, see individual Service Facts.  
34  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typ ic a l  
Wirin g  
(He a t Pu m p )  
SSP-PRC002-EN  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typ ic a l  
Wirin g  
(He a t Pu m p )  
Heat Pump — Dual Compressors  
Typical unit wiring diagram. For specific  
wiring, see individual Service Facts.  
36  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typ ic a l  
Wirin g  
(He a t Pu m p )  
SSP-PRC002-EN  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typ ic a l  
Wirin g  
(Air Ha n d le r)  
Air Handler  
Typical unit wiring diagram. For specific  
wiring, see individual Service Facts.  
38  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(He a t Pu m p )  
Figure DD-1 — TWA075 Heat Pump  
All dimensions are in inches and millimeters.  
No t e 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
SSP-PRC002-EN  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(He a t Pu m p )  
Figure DD-2 — 10Ton TWA100A Heat Pump  
All dimensions are in inches and millimeters.  
No t e 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
40  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(He a t Pu m p )  
Figure DD-3 — TWA155B Heat Pump  
All dimensions are in inches and millimeters.  
No t e 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
SSP-PRC002-EN  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(He a t Pu m p )  
Figure DD-4 — TWA200B Heat Pump  
All dimensions are in inches and millimeters.  
No t e 1  
MINIMUM CLEARANCE FOR PROPER  
OPERATION IS 36 INCHES (914 MM)  
FROM WALLS, SHRUBBERY, PRIVACY  
FENCES, ETC. MINIMUM CLEARANCE  
BETWEEN ADJACENT UNITS IS 72  
INCHES (1828 MM)  
42  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le r)  
Figure DD-5 — TWE050AAir Handlers  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dim ensions do not include 1/2”  
(12.7m m ) access panel depth.  
2. Rem ovable drain pan and attached drain connection m ay be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection m ust be rem oved to slide drain pan out  
for cleaning. Access plate m ust be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
rem oval of pan on drain connection end of unit.  
SSP-PRC002-EN  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le r)  
Figure DD-6 —TWE075A Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dim ensions do not include 1/2”  
(12.7m m ) access panel depth.  
2. Rem ovable drain pan and attached drain connection m ay be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection m ust be rem oved to slide drain pan out  
for cleaning. Access plate m ust be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
rem oval of pan on drain connection end of unit.  
44  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le r)  
Figure DD-7—TWE100A Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dim ensions do not include 1/2”  
(12.7m m ) access panel depth.  
2. Rem ovable drain pan and attached drain connection m ay be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection m ust be rem oved to slide drain pan out  
for cleaning. Access plate m ust be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
rem oval of pan on drain connection end of unit.  
SSP-PRC002-EN  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le r)  
Figure DD-8—TWE100B Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dim ensions do not include 1/2”  
(12.7m m ) access panel depth.  
2. Rem ovable drain pan and attached drain connection m ay be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection m ust be rem oved to slide drain pan out  
for cleaning. Access plate m ust be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
rem oval of pan on drain connection end of unit.  
46  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le rs )  
Figure DD-9—TWE050A, 075A, 100A andTWE100B Air Handler  
All dimensions are in inches and millimeters.  
Table DD-1 — Air Handler Dimensions — in. (mm)  
Model No.  
TWE050A  
AA  
AB  
AC  
AD  
AE  
AF  
AJ  
AK  
AL  
35 5/8  
(905)  
12 1/16  
1 5/8  
32 1/4  
2 15/16  
(74.6)  
32 1/4  
7 13/16  
12 3/8  
34 9/16  
(878)  
(306.4)  
16  
(406.4)  
16  
(406.4)  
16  
(406.4)  
(41.3)  
(819.2)  
(819.2)  
(198.4)  
(314.3)  
16  
(406.4)  
16  
(406.4)  
16  
(406.4)  
TWE075A  
TWE100A  
TWE100B  
45 1/8  
1 11/16  
41 15/16  
6 5/8  
41 3/4  
7
36 7/8  
(1146.2)  
(42.9)  
(1065.2)  
(168.3)  
(1060.5)  
(177.8)  
(936.6)  
61 1/8  
1 11/16  
57 15/16  
6 5/8  
57 13/16  
7
36 7/8  
(1552.6)  
(42.9)  
(1471.6)  
(168.3)  
(1468.4)  
(177.8)  
(936.6)  
61 1/8  
1 11/16  
57 15/16  
6 5/8  
57 13/16  
7
36 7/8  
(1552.6)  
(42.9)  
(1471.6)  
(168.3)  
(1468.4)  
(177.8)  
(936.6)  
SSP-PRC002-EN  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le r)  
Figure DD-10— TWE155B Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dim ensions do not include 1/2”  
(12.7m m ) access panel depth.  
2. Rem ovable drain pan and attached drain connection m ay be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection m ust be rem oved to slide drain pan out  
for cleaning. Access plate m ust be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
rem oval of pan on drain connection end of unit.  
48  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le rs )  
Figure DD-11 TWE200B Air Handler  
All dimensions are in inches and millimeters.  
Notes:  
1. Length, Width, and Height Dim ensions do not include 1/2”  
(12.7m m ) access panel depth.  
2. Rem ovable drain pan and attached drain connection m ay be  
installed on either end of unit in either the vertical or horizontal  
configuration. Plastic drain pan access plate on the end of unit  
opposite drain connection m ust be rem oved to slide drain pan out  
for cleaning. Access plate m ust be reinstalled after sliding drain  
pan back into unit.  
3. If periodic drain pan cleaning is required, allow room for partial  
rem oval of pan on drain connection end of unit.  
SSP-PRC002-EN  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Air Ha n d le rs )  
Figure DD-12—TWE155B and 200B Air Handlers  
All dimensions are in inches and millimeters.  
Table DD-2 — Air Handler Dimensions — in. (mm)  
Model No.  
TWE155B  
TWE200B  
A
B
C
D
E
F
G
H
J
77 1/4 (1962.2)  
89 1/4 (2267)  
1 3/16 (30.2)  
1 11/16 (42.9)  
48 (1219.2)  
50 13/16 (1290.6) 11 1/2 (292.1)  
11 7/16 (290.5)  
18 (457.2)  
20 1/8 (511.2)  
3 3/8 (85.7)  
3 1/16 (77.8)  
35 1/16 (890.6)  
39 1/8 (993.8)  
73 7/8 (1876.4)  
82 7/8 (2105)  
3 3/4 (95.3)  
4 9/16 (115.9)  
Table DD-2— Air Handler Dimensions — in. (mm) (Continued)  
Model No.  
TWE155B  
TWE200B  
K
L
M
N
P
Q
R
S
T
35 1/16 (890.6)  
39 1/8 (993.8)  
2 13/16 (71.4)  
4 7/8 (123.8)  
18 (457.2)  
20 (508)  
3 9/16 (90.5)  
3 (76.2)  
2 7/8 (73)  
35 1/16 (890.6)  
39 1/8 (993.8)  
3 3/4 (95.3)  
4 9/16 (115.9)  
35 1/16 (890.6)  
39 1/8 (993.8)  
73 3/8 (1863.7)  
82 7/8 (2105)  
4 13/16 (122.2)  
50  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Ac c e s s o rie s )  
Figure DD-13— Electric Heater forTWE050, 075, 100 Air Handlers  
All dimensions are in inches and millimeters.  
Figure DD-14 — Electric Heater forTWE155 and 200 Air Handlers  
SSP-PRC002-EN  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dim e n s io n a l  
Da t a  
(Ac c e s s o rie s )  
Table DD-3 — Discharge Plenum And Grille  
Dimensions — in. (mm)  
Figure DD-15 — Discharge Plenum and Grille  
All dimensions are in inches and millimeters.  
Model  
Model No.  
A
B
C
28  
TWE050 BAYPLNM015  
TWE075 BAYPLNM016  
TWE100 BAYPLNM017  
3715/16 2115/16  
(963.6) (557.2) (711.2)  
471/2  
(1206.5) (635) (711.2)  
631/2  
25 28  
(1612.9) (635) (711.2)  
25  
28  
Table DD-4 — Discharge Plenum And Grille  
Dimensions — in. (mm)  
For Use with Electric Heat  
Model  
Model No.  
A
B
C
29  
TWE050 BAYPLNM025  
TWE075 BAYPLNM026  
TWE100 BAYPLNM027  
TWE155 BAYPLNM028  
TWE200 BAYPLNM029  
3715/16 2115/16  
(963.6) (557.2) (736.6)  
471/2  
(1206.5) (635) (736.6)  
631/2  
25 29  
(1612.9) (635) (736.6)  
791/2 2711 /16  
35  
(2019.3) (703.3) (889)  
921/2  
35  
(2349.5) (773.1) (889)  
25  
29  
307/16  
Table DD-5 — Subbase Dimensions — in.  
(mm)  
Figure DD-16 — Subbase  
Model  
Model No.  
A
B
TWE050 BAYBASE001  
TWE075 BAYBASE002  
TWE100 BAYBASE003  
TWE155 BAYBASE004  
TWE200 BAYBASE005  
38  
22  
(965.2)  
(558.8)  
471/2  
25  
(635)  
(1206.5)  
631/2  
25  
(1612.9)  
(635)  
791/2  
275/8  
(2019.3)  
(701.7)  
921/2  
307/16  
(2349.5)  
(773.1)  
52  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
We ig h t s  
(He a t Pu m p s )  
Table W-1 — Unit and CornerWeights — lb (kg)  
Unit  
Shipping  
Net  
Corner Weights  
Model No.  
TWA075A  
Maximum — lb (kg) Maximum — lb (kg)  
1
112  
(50.8)  
2
89  
(40.4)  
3
63  
(28.6)  
4
79  
(35.8)  
390  
343  
(155.6)  
(176.9)  
TWA100A  
TWA155B  
TWA200B  
468  
414  
146  
106  
68  
94  
(212.3)  
(187.8)  
(66.2)  
(48.1)  
(30.1)  
(42.6)  
816  
(370.1)  
970  
(440.0)  
740  
(335.7)  
885  
(401.4)  
195  
(88.5)  
253  
(114.8)  
186  
(84.4)  
250  
(113.4)  
175  
(79.4)  
190  
(86.2)  
184  
(83.5)  
192  
(87.1)  
Table W-2 AccessoryWeights — Net lb (kg)  
Unit  
Model No.  
RIS  
Isolators  
Steel Spring  
Isolators  
Anti Short  
Cycle Timer  
Coil  
Guard  
Low  
Ambient  
Thermostats  
TWA075A  
2
(.9)  
12  
(5.4)  
1
(.5)  
8
(3.6)  
1
(.5)  
23  
(10.4)  
TWA100A  
TWA155B  
TWA200B  
2
12  
1
11  
1
23  
(.9)  
(5.4)  
(.5)  
(5)  
(.5)  
(10.4)  
2
(.9)  
2
(.9)  
12  
(5.4)  
12  
(5.4)  
1
(.5)  
1
(.5)  
22  
(10)  
34  
(15.4)  
1
(.5)  
1
(.5)  
23  
(10.4)  
23  
(10.4)  
TWA155B, 200B  
TWA075A, 100A  
SSP-PRC002-EN  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Weights  
(Air Ha n d le rs )  
Table W-3 Air Handlers, Coils, And CornerWeights — lb (kg)1  
Unit  
Shipping  
Net  
Corner Weights Vertical  
Corner Weights Horizontal  
Model No.  
TWE050  
Maximum (lbs)  
Maximum (lbs)  
#1  
59  
(26.8)  
#2  
59  
(26.8)  
#3  
59  
(26.8)  
#4  
59  
(26.8)  
A
54  
(24.5)  
B
64  
(29)  
C
64  
(29.03)  
D
54  
(24.5)  
298  
(135)  
262  
(118.9)  
TWE075  
TWE100  
TWE125  
TWE200  
Note:  
388  
346  
79  
79  
79  
79  
77  
84  
81  
73  
(176)  
(157)  
(35.9)  
(35.9)  
(35.9)  
(35.9)  
(35)  
(38.1)  
(36.7)  
(33.1)  
473  
(214.6)  
754  
(342)  
886  
(401.9)  
419  
(190.1)  
690  
(313)  
820  
(372)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
107  
(48.5)  
173  
(78.5)  
204  
(92.5)  
102  
(46.3)  
174  
(79)  
185  
(84)  
113  
(51.3)  
156  
(70.8)  
228  
(103.4)  
113  
(51.3)  
190  
(86.2)  
221  
(100.3)  
102  
(46.3)  
170  
(77.1)  
179  
(81.2)  
1. If application requires steam or hot water heating coils, field supplied isolators m ust be utilized.  
Vertical  
TWE050, 075, 100  
Vertical  
TWE155, 200  
Horizontal  
TWE050, 075, 100  
Horizontal  
TWE155, 200  
Table W-4AccessoryWeights — lb (kg)  
RIS  
RIS  
Steel Spring Steel Spring  
Discharge  
Plenum  
Discharge  
Plenum  
Electric  
Heat  
Min. Max.  
Isolator  
Floor  
Isolator  
Suspended  
Mount  
Isolator  
Floor  
Isolator  
Suspended  
Mount  
Unit  
Model No.  
Return  
Air Grille  
Oversized  
Motor  
And Grille1  
And Grill2  
Subbase  
Mount  
Mount  
TWE050  
58  
(26.3)  
93  
(42.2)  
3
(1.4)  
32/43  
(14.5/19.5)  
14  
(6.4)  
31  
(14.1)  
2
(.9)  
9
(4)  
12  
(5.4)  
6
(2.7)  
TWE075  
TWE100  
TWE155  
TWE200  
Note:  
73  
123  
5
27/45  
19  
48  
2
6
12  
6
(33.1)  
(55.8)  
(2.3)  
(12.3/20.4)  
(8.6)  
(21.8)  
(.9)  
(2.7)  
(5.4)  
(2.7)  
92  
(41.7)  
124  
(56.3)  
145  
(65.8)  
156  
(70.8)  
230  
(104.3)  
264  
(119.8)  
7
(3.2)  
10  
(4.5)  
12  
(5.4)  
27/45  
(12.3/20.4)  
79/100  
(35.8/45.4)  
79/100  
(35.8/45.4)  
23  
(10.4)  
27  
(12.3)  
31  
(14.06)  
50  
(22.7)  
80  
(36.3)  
88  
(40)  
2
(.9)  
2
(.9)  
2
(.9)  
7
(3.2)  
7
(3.2)  
9
(4)  
12  
(5.4)  
12  
(5.4)  
12  
(5.4)  
6
(2.7)  
6
(2.7)  
6
(2.7)  
1. For use when no heat is supplied.  
2. For use with electric heat.  
54  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Me ch a n ic a l  
S p e c ific a t io n s  
Refrigeration System — Dual  
Compressor  
block for power wiring. Control wiring  
shall be 24-volt control circuit which  
includes fusing and control transformer.  
Units shall provide external location for  
mounting a fused disconnect device.  
Time delay timers to prevent  
compressors in dual compressor units  
from simultaneous start-up and anti-  
recycle timers are available as optional  
accessories.  
Heat Pumps  
General  
TWA155B,TWA200B units shall have  
two separate and independent  
Unit shall be assembled on heavy gauge  
steel mounting/lifting rails and shall be  
weather proofed. Unit shall include a  
hermetic scroll or reciprocating  
compressor(s), plate fin condenser coil,  
fans and motors, controls, and holding  
charge of nitrogen. Operating Range  
shall be between 115° F and 35° F in  
cooling as standard from factory. Unit  
shall be UL 1995 listed and rated in  
accordance with ARI Standard 210/240 or  
340/360.  
refrigeration circuits. Each refrigeration  
circuit shall have an integral subcooling  
circuit. A refrigeration filter drier shall be  
provided as standard. Unit shall have  
both a liquid line and suction gas line  
service valve with gauge ports.  
Defrost Controls  
Unit shall have twoTrane direct drive,  
hermetic scroll compressors with  
centrifugal oil pump and provide positive  
lubrication to all moving parts. Motor  
shall be suction gas-cooled and shall  
have a voltage utilization range of plus or  
minus 10 percent of nameplate voltage.  
Crankcase heater, discharge line  
Electronic timed initiated, temperature  
terminated defrost system with choice  
of 50, 70, or 90 minute cycle shall be  
included.Timed override limits defrost  
cycle to 10 minutes.  
Casing  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Units surface shall be tested 500 hours  
in salt spray test. Unit shall have  
removable end panels which allow  
access to all major components and  
controls.  
Low Ambient Operation  
Standard units shall start and operate to  
approximately 35° F (1.7° C) when  
matched withTrane air handlers and  
coils. Optional head pressure control  
accessory perm its operation to 0° F  
(-17.8° C).  
thermostat, and current-sensitive motor  
overloads shall be included for  
maximum protection. Scroll type  
compressor shall provide inherently low  
vibration and noise by having no suction  
and discharge valves. External high and  
low pressure cutout devices shall be  
provided. Evaporator defrost control  
provided in indoor blower coil shall  
prevent compressor slugging by  
temporarily interrupting compressor  
operation when low evaporator coil  
temperatures are encountered.  
ACCESSORIES  
Low Ambient Head Pressure Control —  
This accessory shall modulate the RPM  
of unit outdoor fan motor in response  
to outdoor ambient temperatures and  
liquid line temperature. Accessory  
provides unit cooling operation to  
outdoor temperatures of 0° F (-17.8° C).  
Refrigeration System — Single  
Compressor  
TWA075A,TWA100A units shall have a  
single refrigeration circuit. Each  
refrigeration circuit has an integral  
subcooling circuit. A refrigeration filter  
drier, expansion valve, and check valves  
shall be provided as standard.The unit  
shall have both a liquid line and suction  
gas line service valve with gauge port.  
Condenser Coil  
Vibration Isolation Packages This  
accessory shall reduce transmission of  
noise and vibration to building  
structures, equipment, and adjacent  
spaces. Packages shall be available in  
either neoprene-in-shear or spring-flex  
types.  
Coils shall be internally finned or smooth  
bore, 3/8" (10mm) copper tubes  
mechanically bonded to a configured  
aluminum plate fin as standard. Coil  
shall be factory pressure and leak tested  
to 420 psig (2,930 kPa) air pressure.  
Metal grilles with PVC coating for coil  
protection is optional.  
Unit shall have one direct drive,Trane  
hermetic scroll compressor with  
centrifugal oil pump providing positive  
lubrication to moving parts. Motor shall  
be suction gas-cooled and shall have a  
voltage utilization range of plus or minus  
10 percent of nameplate voltage.  
Crankcase heater, discharge line  
thermostat, and current-sensitive motor  
overloads shall be included for  
Time Delay Relay —This accessory  
shall prevent compressors in dual  
compressor unit from coming on line  
simultaneously.Timer shall be 24-volt,  
60 cycle, with four minute timing  
period.  
Condenser Fan And Motor(s)  
Direct-drive, statically and dynamically  
balanced, 26 or 28 inch (660 or 711 mm)  
propeller fan(s) with aluminum blades  
and electro-coated steel hubs shall be  
used in draw-through vertical discharge  
position. Either permanently lubricated  
totally enclosed or open construction  
type motors shall be provided and shall  
have built-in current and thermal  
Anti-Short-Cycle Timer —This  
accessory shall prevent rapid on-off  
compressor cycling in light load  
conditions by not allowing compressor  
to operate for 5-7 minutes upon  
shutdown.This accessory shall consist  
of a 24-volt, 60 cycle, solid state timing  
device with either 5 or 7 minute fixed-  
off timing period.  
maximum protection. Scroll type  
compressor shall provide inherently low  
vibration and noise by having no suction  
and discharge valves. External high and  
low pressure cutout devices shall be  
provided. Evaporator defrost control  
provided in indoor blower coil unit shall  
prevent compressor slugging by  
temporarily interrupting compressor  
operation when low evaporator coil  
temperatures are encountered.  
overload protection. Motor(s) shall have  
either ball or sleeve bearing type.  
Controls  
Heat pump units shall be completely  
factory wired with necessary controls  
and contactor pressure lugs or terminal  
SSP-PRC002-EN  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Me ch a n ic a l  
S p e c ific a t io n s  
Condenser Coil Guard — Metal grille  
with PVC coating shall be provided to  
alleviate coil damage.  
internally wye connected on 400 volt,  
three phase. Each 400 volt heater shall  
have automatic line break high limit  
controls.  
internally enhanced copper tubing and  
shall be factory pressure and leak tested  
at 375 psig (2586 kPa). Coil is arranged  
for draw-through airflow and shall  
provide a double sloped condensate  
drain pan constructed of PVC plastic.The  
drain pan shall be removable for  
cleaning.The condensate drain pan can  
be installed in any of four positions  
allowing for vertical or horizontal  
Black Epoxy Coated Condenser Coil —  
This factory installed option is designed  
to provide corrosion protection of air  
cooled condenser coils for seacoast  
application. The black epoxy coil  
protection is a factory applied thermoset  
vinyl coating, bonded to normal  
aluminum fin stock. The uniform  
thickness of the bonded vinyl layer  
exhibits excellent corrosion protection in  
salt spray tests performed in accordance  
with ASTM B177.  
Discharge Plenums and Grilles —  
Accessory discharge plenums shall be  
available for vertical, free discharge  
applications. Plenums shall be  
constructed of heavy-gauge, zinc coated,  
galvanized steel finished with baked  
enamel to match the air handler unit.  
Grilles shall be satin finished aluminum  
and have four-way adjustable louvers.  
application and providing external  
connections on either side of the unit.  
Evaporator Fan  
Double inlet, double width, forward  
curved, centrifugal-type fan(s) with  
adjustable belt drive shall be standard.  
Thermal overload protection shall be  
standard on motor. Fan and motor  
bearings shall be permanently  
lubricated. Oversized motors shall be  
available as an option for high static  
application. All indoor fan motors meet  
the U.S. Energy Policy Act of 1992  
(EPACT).  
Return Air Grilles — Accessory return air  
grille shall be provided for vertical front,  
free return applications. Grilles shall be  
installed in place of the front lower side  
panel. Grille shall be satin finished  
Air Handlers  
General  
aluminum with non-adjustable louvers.  
Air handler units shall be completely  
factory assembled including coil,  
condensate drain pan, fan motor(s),  
filters, and controls in an insulated  
casing that can be applied in either  
vertical or horizontal configuration. Unit  
shall be rated and tested in accordance  
with ARI standard 210/240 or 340/360.  
Unit shall be UL listed and labeled in  
accordance with UL 1995 for indoor  
blower coil units.  
Mounting Subbase —The accessory  
shall be available for vertical floor mount  
configurations. Subbase shall be  
constructed of heavy gauge, zinc coated,  
galvanized steel with baked enamel  
finish to match air handler unit. Subbase  
is required in the vertical air flow  
application for condensate drain  
trapping and when isolators are  
required.  
Controls  
Magnetic evaporator fan contactor, low  
voltage terminal strip, check valve(s), and  
single point power entry shall be  
included. All necessary controls shall be  
factory-installed and wired. Evaporator  
defrost control shall be included to  
prevent compressor slugging by  
temporarily interrupting compressor  
operation when low evaporator coil  
temperatures are encountered.  
Casing  
Vibration Isolators —This accessory  
shall reduce transmission of noise and  
vibration to building structures,  
equipment, and adjacent spaces.  
Packages shall be available in either  
neoprene-in shear or spring-flex types in  
floor or suspended mountings.  
Unit casing shall be constructed of zinc  
coated, heavy gauge, galvanized steel.  
Exterior surfaces shall be cleaned,  
phosphatized, and finished with a  
weather-resistant baked enamel finish.  
Casing shall be completely insulated  
with cleanable, foil faced, fire-retardant,  
permanent, odorless, glass fiber  
material. All insulation edges shall be  
either captured or sealed. Knockouts  
shall be provided for unit electrical  
power and refrigerant piping  
Filters  
One inch, throw-away filters shall be  
standard onTWE050A,TWE075A,  
TWE100A andTWE120B model air  
handlers. Filters shall be accessible from  
the side coil access panel. Filter rack can  
be field converted to two inch capability.  
Two inch, throw-away filters shall be  
standard onTWE155B andTWE200B  
models.  
Oversized Motors — Field installed  
oversized motors shall be available for  
high static pressure applications.  
CONTROL OPTIONS  
Standard IndoorThermostats Two  
stage heating and cooling operation or  
one stage heating and cooling  
thermostats shall be available in either  
manual or automatic changeover.  
connections. Captive screws shall be  
standard on all access panels.  
Refrigeration System  
ACCESSORIES  
TheTWE050A,TWE075A,TWE100A units  
shall have a single refrigeration circuit  
and theTWE100B,TWE155B,TWE200B  
units shall have dual refrigeration  
circuits. Each refrigeration circuit is  
controlled by a factory installed thermal  
expansion valve.  
Electric Heaters — UL and CSA  
Programmable Electronic Night Setback  
Thermostat —The option shall provide  
heating setback and cooling setup with 7-  
day programming capability.  
approved electric heat modules shall be  
available for installation directly on fan  
discharge. Electric heaters shall be  
available in a wide range of capacities  
with one or two stage control, single-  
point electric power connection, and  
terminal strip connections. Electric  
heater elements shall be constructed of  
heavy-duty nickel chromium elements  
OutdoorThermostat —This option  
shall provide staging control of  
electric heaters based on a set  
outdoor temperature.  
Evaporator Coil  
Configured aluminum fin surface shall  
be mechanically bonded to 3/8" (10 mm)  
56  
SSP-PRC002-EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Literature Order Number  
File Number  
SSP-PRC002-EN  
PL-UN-SSP-PRC002-EN-1003  
TWA-PRC001-EN 1101  
The Trane Com pany  
An Am erican Standard Com pany  
w w w .trane.com  
Supersedes  
Stocking Location  
October Publication Electronic Only  
For more information contact your  
local office or e-mail us at  
SinceThe Trane Company has a policy of continuous product and product data improvement, it reserves the  
right to change design and specifications without notice.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tissot Watch 151_EN User Manual
Toshiba CRT Television 58L5400UC User Manual
Toshiba Laptop A215 S7422 User Manual
Toshiba Power Supply VF A5 User Manual
Tripp Lite Surge Protector 200609062 User Manual
Trojan Elliptical Trainer SOLO 200 User Manual
Valcom Power Supply VP 1124A User Manual
Vanguard Heating Water Heater PM200 User Manual
VTech Cordless Telephone 2121 User Manual
Vulcan Hart Range ML 52486 User Manual