Installation
Operation
Maintenance
Voyager™ I Rooftop Units
Cooling-onlyTSD/TSH 060 072 102 120
Reversible WSD/WSH 060 072 090
Gas-firedYSD/YSH 060 072 090 102 120
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
General information
Reception
Refrigerant
Maintenance contract
On arrival, inspect the unit before
signing the delivery note. In case of
visible damage:The consignee (or
the site representative) must specify
any damage on the delivery note,
legibly sign and date the delivery
note, and the truck driver must
countersign it.The consignee (or the
site representative) must notify
Trane Epinal Operations - Claims
team and send a copy of the
The refrigerant provided by the
manufacturer meets all the
It is strongly recommended that you
sign a maintenance contract with
your local Service Agency.This
contract provides regular
maintenance of your installation by
a specialist in our equipment.
Regular maintenance ensures that
any malfunction is detected and
corrected in good time and
minimizes the possibility that
serious damage will occur. Finally,
regular maintenance ensures the
maximum operating life of your
equipment. We would remind you
that failure to respect these
installation and maintenance
instructions may result in
requirements of our units. When
using recycled or reprocessed
refrigerant, it is advisable to ensure
its quality is equivalent to that of a
new refrigerant. For this, it is
necessary to have a precise analysis
made by a specialized laboratory. If
this condition is not respected, the
manufacturer warranty could be
cancelled.
delivery note.The customer (or the
site representative) should send a
registered letter to the last carrier
within 3 days of delivery.
Storage
Take precautions to prevent
condensate formation inside the
unit's electrical components and
motors when:
1.The unit is stored before it is
installed; or,
2.The unit is set on the roof curb
and temporary auxiliary heat is
provided in the building.
Isolate all side panel service
entrances and base pan openings
(e.g., conduit holes, S/A and R/A
openings, and flue openings) to
minimize ambient air from entering
the unit until it is ready for start-up.
Reception in France only:
immediate cancellation of the
warranty.
Concealed damage must be looked
for at delivery and immediately
treated as visible damage.
Training
Reception in all countries except
France:
To assist you in obtaining the best
use of it and maintaining it in
perfect operating condition over a
long period of time, the
manufacturer has at your disposal a
refrigeration and air conditioning
service school.The principal aim of
this is to give operators and
technicians a better knowledge of
the equipment they are using, or
that is under their charge. Emphasis
is particularly given to the
importance of periodic checks on
the unit operating parameters as
well as on preventive maintenance,
which reduces the cost of owning
the unit by avoiding serious and
costly breakdown.
In case of concealed damage:The
consignee (or the site
representative) must send a
registered letter to the last carrier
within 7 days of delivery, claiming
for the described damage. A copy of
this letter must be sent toTrane
Epinal Operations - Claims team.
Do not use the unit's heater as
temporary heat without completing
the start-up procedures detailed
under "Unit Start-Up".
Warranty
Warranty is based on the general
terms and conditions of the
manufacturer.The warranty is void
if the equipment is repaired or
modified without the written
TheTrane Company will not assume
responsibility for equipment
damage resulting from
accumulation of condensate on the
unit electrical components.
approval of the manufacturer, if the
operating limits are exceeded or if
the control system or the electrical
wiring is modified. Damage due to
misuse, lack of maintenance or
failure to comply with the
manufacturer's instructions or
recommendations is not covered by
the warranty obligation. If the user
does not conform to the rules of
this manual, it may entail
cancellation of warranty and
liabilities by the manufacturer.
RT-SVX20A-E4
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
General information
Foreword
Warnings and Cautions
Reception
2
2
2
3
3
3
3
3
3
Warranty
Refrigerant
Maintenance contract
Storage
Training
Installation
Reception of units
6
6
Roof curb installation
6
Dimensions/Weights/Clearances
Installing the unit
7
9
Connection of duct network
Condensate drain piping
Gas pipework installation
Filter installation
10
12
13
14
14
16
17
30
Supply fan adjustment
Component air pressure drops
Supply fan performances
Electrical connection
Controls
Control wiring
33
33
35
39
40
41
41
41
41
42
43
2
CO sensors
Remote potentiometer
Fire thermostat
Clogged filter detector
Smoke detector
High temperature safety thermostat
Remote fault relay
Thermostats
Communication Interfaces
4
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
Unit Options
Hot water coil
Electric Heater
Soft Starter
0 - 25% fresh air hood
Barometric relief
44
44
45
45
46
47
Operation
Operation with a conventional thermostat
Setting the economizer
Test procedures
48
48
50
52
53
54
56
57
57
58
58
58
59
Test modes
Unit Start-up
Cooling without an Economizer
Low Ambient Operation
Cooling with an Economizer
Economizer Set-Up
ReliaTel™ Control Heating Operation
Ignition Module
Final installation checklist
Maintenance
End user routine maintenance
Service technician maintenance
Troubleshooting
60
60
61
62
RT-SVX20A-E4
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 2 - Rigging
General information:The
Roof curb (accessory)
installation must conform to all
local standards and regulations.
Roof curbs are available as an
accessory for downflow units.The
curbs can be adjustable and
supplied pre-assembled on wooden
pallets, packed under plastic film.
Two types of self-adhesive seals are
provided to ensure the roof curb
seal is leak-tight (40 mm wide for
the perimeter, 20 mm wide for the
crosspieces).
Reception of units
Rooftop unit
1
There are two ways to handle the
unit:
1. Use the openings in the base to
handle the machine using a
forklift, in accordance with
applicable safety regulations.
2. Use a lifting beam correctly
adjusted to fit the unit (Figure 1).
2
Roof curb Installation
(TSD-WSD-YSD
accessories)
Roof curbs are available as an
accessory for "downflow" units to
support the unit and ensure the
water tightness between the rooftop
and the roof.
Unit handling
1 = Remove 2 fork lift brackets
The units are supplied on the truck
but are not unloaded. An opening is
provided on each corner of the unit
base to facilitate handling. Four
shackles and four slings are
required. Use a lifting beam to
prevent the cables pressing too hard
on top of the unit during lifting.The
structure accommodating the unit(s)
must be designed to support the
equipment in operation, as a
2 = Remove 2 metal runners and 3
wooden boards
Lift the unit enough to allow the
removal of two Fork Lift brackets
and hardware. Remove the two Fork
Lift brackets, two metal runners and
three wooden boards as shown in
Figure 2.
The curbs can be adjustable and
supplied pre-assembled on wooden
pallets, packed under plastic film.
Two types of self-adhesive seals are
provided separate. (40 mm wide for
the perimeter, 20 mm wide for the
cross pieces). Make sure they are
properly installed where indicated
to assure an adequate curb to unit
seal.
minimum. (Refer to Figures 1 and
2 andTables 2 and 3.)
Important: For unit to fit on the roof
curb the fork lift pockets must be
removed.
Instructions for the roof curb
assembly and installation with curb
dimensions are provided with each
roof curb kit.
Figure 1 - Unit handing
6
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 3 - Minimum clearances
Dimensions/Weights/
Clearances
The structure accommodating the
unit(s) must be designed to support
the equipment in operation, as a
minimum. Refer toTable 2 and the
space requirement plan.
Table 1 - Minimum recommended clearances
Unit size
Mimum clearances (mm)
1
2
3
4
5
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
1829
1829
1829
1829
1829
1829
1829
1829
1829
1829
1829
1829
1829
1219
1219
1219
1219
1219
1219
1219
1219
1219
1219
1219
1219
1219
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
914
Table 2 - Unit weights and center of gravity
Maximum weight
Corner weight (1)
Center of gravity
Unit Size
Shipping
(kg)
Net
(kg)
A
(kg)
B
(kg)
C
(kg)
D
(kg)
Length
(mm)
Width
(mm)
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
259
365
428
445
485
285
390
458
474
520
266
408
418
235
326
389
405
445
260
350
419
434
481
241
368
378
75
56
83
48
58
67
72
81
54
64
75
79
89
49
66
67
56
78
790
970
970
990
990
810
480
560
530
560
560
510
560
530
560
560
480
560
530
107
131
133
147
81
101
106
115
64
89
94
104
62
113
139
141
155
77
90
83
990
970
1020
1020
790
970
970
110
114
126
58
95
100
111
58
122
128
93
87
95
88
Notes:
(1) Corner weights are given for information only. All models must be supported continuously by a curb or
equivalent frame support.
RT-SVX20A-E4
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 4
Center of
gravity length
A
B
Center of
gravity width
C
D
Center of
gravity
Table 3 - Factory-installed options and accessories net weights (kg)
Motorized
Outside Air
Damper
Manual
Outside Air
Damper
Barometric
Relief
Oversized
Motor
Electric
Heaters
Hot water
coil
Unit size
Economizer
Roof Curb
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 1020
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
11,8
16,3
16,3
16,3
16,3
11,8
16,3
16,3
16,3
16,3
11,8
16,3
16,3
3,2
4,5
4,5
4,5
4,5
3,2
4,5
4,5
4,5
4,5
3,2
4,5
4,5
9,1
13,6
13,6
13,6
13,6
9,1
7,3
31,8
52,2
52,2
52,2
52,2
31,8
52,2
52,2
52,2
52,2
31,8
52,2
52,2
-
6,8
13,6
13,6
13,6
13,6
6,8
14,0
17,0
17,0
19,0
19,0
11,8
11,8
11,8
11,8
7,3
3,6
3,6
3,6
3,6
-
13,6
13,6
13,6
13,6
9,1
11,8
11,8
11,8
11,8
7,3
3,6
3,6
3,6
3,6
-
13,6
13,6
13,6
13,6
6,8
14,0
17,0
17,0
13,6
13,6
11,8
11,8
3,6
3,6
13,6
13,6
Notes:
(1) Weights for options not listed are < 3 kg.
(2) Net weight should be added to unit weight when ordering factory-installed accessories.
(3) Some accessories are not available on all units.
8
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 5 - Conversion to horizontal
discharge
3. Position duct covers as shown in
Figure 4.The supply duct cover is
installed (insulation side down)
over the downflow return
Installing the unit
Discharge Conversion
3
opening by engaging one side of
the panel under a retaining angle
and securing the other side with
3 screws.
If a unit is to be converted to
Vertical discharge, a panel must be
acquired fromTrane.
If a unit is to be converted to
Horizontal discharge, the following
conversion must be performed:
1. Remove the return and supply
duct covers.
4. Slide return duct cover
(insulation side up) into supply
openings until outer edge of the
duct cover engages with the two
retaining clips on the duct
flanges. Secure the outer edge of
the each duct cover with two
screws.
1
2. Apply gasket to the return duct
2
cover.
1 = Supply duct cover, insulation side
down
2 = Return duct cover with gasket
installed, insulation side up
3 = Edge of duct cover goes under
retaining angle
Unit mounting on roof
Fix the rooftop curb on the joint
beam of the building's structure.
Make the rooftop curb's sealing
surface level using angle brackets
adjusted by screw bolts, located
around its perimeter. Place the
adhesive seals on the curb's sealing
surface (perimeter and cross
pieces). Make the rooftop leak-tight
around the curbs before installing
the unit, in compliance with current
construction standards.
Note:The unit must be installed
perfectly level to ensure
condensates flow from the
condensate tray.
Figure 6 - Unit mounting on roof
The rooftop unit nests into the curb
and is supported by it. Position the
unit, taking care to comply with the
indicated directions: the unit's
discharge and intake openings must
match those of the curb.
1
1 = Frame
RT-SVX20A-E4
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Installing the unit on the ground
•
For the design of the duct
network, comply with
recommendations currently
applicable on the market, in
particular:
. Installation of a section of
flexible ducts to limit
transmission of the unit's
vibrations
Connection of duct
network
To install the unit on the ground, its
base must be level and supported
securely. For horizontal discharge
units, a support is required such as
a metal or concrete slab whose
height must be determined
according to the amount of snow
cover, to prevent problems with
condensation drainage and
obstruction of the external coil. If
necessary use an anti-vibration
material between the rooftop unit's
base and the support.
1) Downflow discharge units
(TSD,WSD,YSD)
Using the rooftop curb
•
The rooftop curb must be
insulated on the outside walls at
the discharge and intake
openings to prevent
. Use of movable vanes or
deflectors to reduce the sound
level.
condensation in the ducts.
The rims around the discharge
and intake openings make it
possible to attach the flanges on
the ends of the ducts. If you are
using rigid duct ends
•
2) Horizontal discharge units
(TSH,WSH,YSH)
•
The intake and discharge ducts
must be insulated (thermal
insulation).
The duct section located outside
must be leak-tight.
Provide a flexible connector to
prevent transmission of the unit
vibrations.This flexible duct
must be installed inside the
building.
Note: Unit installation must comply
to local codes
recommended on the rooftop
curb plan, it is essential to fix
these components before
installing the unit.
•
•
Note: In case of use of units with
economizer option, temperature
and humidity sensors must be
installed in return duct.
Economizer linkage is factory
mounted but the damper position
must be adjusted on site.
Figure 7 - Unit installation on the ground
1 = Concrete slab
10
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 4 - Duct dimensions for downflow units (mm)
Unit size
A
B
C
D
E
Flanges
TSD 060
619
610
819
875
875
816
357
356
357
451
451
444
411
394
411
451
451
444
459
457
459
875
875
838
356
356
356
356
356
356
32
32
32
31
31
31
YSD 060
WSD 060
TSD/WSD 072/090
TSD 102/120
YSD 072/090/102/120
Table 5 - Duct dimensions for downflow units (mm)
Unit size
A
B
C
D
TSH/WSH 060
591
591
832
832
337
337
425
425
375
375
606
606
438
438
489
489
YSH 060
TSH/WSH/YSH 072/090
TSH/YSH 102/120
Figure 8 - Duct dimensions for downflow units
Figure 9 - Duct dimensions for horizontal units
B
A
C
D
A
R
S
R
C
S
B
E
D
S = Supply
R = Return
S = Supply
R = Return
RT-SVX20A-E4
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Figure 10 - Condensate drain location
Condensate drain piping
A 3/4" condensate drain connection
with P-trap is provided. Follow local
codes and standard piping practices
when running the drain line. Install
a trap and be sure to fill with water
before starting the unit. Pitch the
line downward, away from the unit
to avoid long, level, horizontal runs.
Refer to Figure 11.
The condensate drain is reversible
to allow installation of a drain tap
on either side of the unit.
1
1 = Main condensate drain location
Figure 11 - Condensate drain line location
1 = Static pressure drain pan
2 = Panel enclosure
3 = ¾ " drain
4 = Cleanout plug
12
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
CAUTION! Should the pressure at
the unit valve gas inlet be higher
than 0.035 bar, an expansion valve
must be installed.
CAUTION!The gas pipework must
not exert any stress on the burner
gas connection.
Gas pipework installation
The installation must conform to all
standards and regulations.
Note: Expansion valve must be
The gas supply pipework and gas
stop valve to be installed near the
unit must be sized so as to ensure
the gas pressure is sufficient at the
unit inlet when operating at full
load.
The pipework must be self-
supporting and the final connection
to the burner must be made by a
flexible pipe. Provide a dust
protection (filter) upstream the unit
connection.
adapted to the type of gas used:
•
•
•
G 20: 20 mb
G 25: 25 mb
G 31 (Propane): 37 or 50 mb
Table 6 - Gas burner models
Unit
Burner size
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
G120
G200
G200
G250
G250
SeeTable 51 for burner
performance.
Gas leak check procedure
1. Vent the gas line
2. Gas supply line pressure test:
close valve 4 and open valve 2
3. Leak-check the gas pipe.
Figure 12 -Typical gas supply pipework
Look for gas pipe leaks using
"Typol", "1000 bulles" or a similar
product. Do not use soapy water.
WARNING! Never use an open
flame to check for gas leaks.
Required gas pressure at the unit
inlet connection are given in
Table 50.
Note:To operate with propane gas,
the burner is fitted with a pressure
limiter (supplied byTrane)
1 = Evaporator section
2 = Gas burner section
3 = Condenser section
4 = Gas supply connection
5 = Gas supply line
6, 8 = Gas stop valve (Field supplied)
7 = Expansion valve (Field supplied)
9 = Filter (Field supplied)
RT-SVX20A-E4
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Filter installation
Supply fan adjustment
To gain access to filters, remove the
supply fan access panel on
downflow units and the filter access
panel on the end for horizontal
units.
Use the following procedure to
determine the proper adjustment of
the supply fan for a specific
application.
1. Determine total external static
pressure about system and
accessories.
• Obtain the design airflow rate
and the design external static
pressure drop through the
distribution system.
• Add static pressure drop of the
accessories installed on the unit.
(Table 9)
Number and size of filters is
determined by size and
configuration of the unit. If
disposable filters were chosen as an
option, they are shipped in the
supply fan section.
CAUTION! Do not operate unit
without filters in place.
• Add the total accessory static
pressure drop (from step 1b) to
the design external static
pressure (from step 1a).The sum
of these two values is the total
system external static pressure.
2. Using theTables 10 through 35 to
find the external static pressure
that most closely approximates
total system external static
pressure.Then locate the
appropriate airflow rate for your
unit.The value obtained
The maximum pressure drops
allowable on filters are:
EU2/G2: 120 Pa
EU4/G4: 150 Pa
represents the brake horsepower
for the supply fan motor and the
fan RPM.
3. Adjust motor sheave according
toTable 8.
Table 7 - Filter arrangement
Unit
EU2/G2
EU4/G4
Size
Quantity
Size
Quantity
TSD/TSH/YSD/YSH/WSD/WSH 060
TSD/TSH/YSD/YSH/WSD/WSH 072
TSD/TSH/YSD/YSH/WSD/WSH 090
TSD/TSH/YSD/YSH 102
2
4
4
4
4
(508x762x25)
(406x635x50)
(406x635x50)
(508x635x50)
(508x635x50)
2
4
4
4
4
(500x750x25)
(395x625x50)
(395x625x50)
(500x625x50)
(500x625x50)
TSD/TSH/YSD/YSH 120
14
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
To increase airflow
To adjust belt
When removing or installing the
new belts, do not stretch them over
the sheaves. Loosen the belts using
the belt tension adjustment bolts on
the motor mounting base.
Loosen variable sheave set screw
and turn sheave clockwise.
The fan belts must be inspected
periodically to assure proper unit
operation. Replacement is
necessary if the belts appear frayed
or worn.
To decrease airflow
Once the new belts are installed,
adjust the belt tension.
Loosen variable sheave set screw
and turn sheave counter-clockwise.
Units with dual belts require a
matched set of belts to ensure equal
belt length.
Table 8 - Motor sheave / Fan speed
Fan speed (RPM)
Standard drive & motor
6 turns
Open
5 turns
Open
4 turns
Open
3 turns
Open
2 turns
Open
1 turns
Open
Unit
Closed
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
N/A
N/A
N/A
N/A
N/A
N/A
N/A
859
786
894
N/A
N/A
N/A
898
698
752
688
782
1036
806
913
836
950
898
698
752
967
751
806
737
838
1105
860
967
885
1006
967
751
806
1036
806
860
786
894
1174
913
1105
859
914
1174
913
1243
967
968
1020
934
835
950
1243
968
1075
982
1118
1105
859
914
885
1006
1312
1022
1129
1032
1174
1174
913
1062
1381
1074
N/A
1021
934
1062
1036
806
860
N/A
N/A
1243
967
968
1020
Fan speed (RPM)
Oversized drive & motor
6 turns
Open
5 turns
Open
4 turns
Open
3 turns
Open
2 turns
Open
1 turns
Open
Unit
Closed
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
N/A
N/A
1112
N/A
1062
-
1243
967
1182
971
1118
-
1311
1021
1252
1041
1174
-
1379
1075
1322
1111
1229
-
1450
1128
1392
1181
1285
-
1515
1183
1460
1251
1341
-
1588
1235
N/A
1321
N/A
-
N/A
1112
N/A
1062
N/A
N/A
1112
967
1182
971
1118
1243
967
1182
1021
1252
1041
1174
1311
1021
1252
1075
1322
1111
1229
1379
1075
1322
1128
1392
1181
1285
1450
1128
1392
1183
1460
1251
1341
1515
1183
1460
1235
N/A
1321
N/A
1588
1235
N/A
RT-SVX20A-E4
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Component air pressure drops
Table 9 - Pressure drop through accessories
Economizer
100%
outside air
Unit
size
Airflow
(m /h)
Filter
EU2/G2
Filter
EU4/G4
Electric
heater
Hot water
coil
3
3060
3400
3740
4080
31
38
46
55
50
55
61
66
38
46
55
64
17
21
25
30
49
55
62
68
060
072
090
102
120
3670
4080
4490
4900
13
16
19
23
37
42
46
50
27
29
31
33
7
9
46
52
58
64
11
13
4590
5100
5610
6120
19
24
29
35
47
52
57
62
33
39
45
52
12
15
20
25
66
74
83
92
5200
5780
6360
6940
16
20
25
30
42
47
52
57
40
50
62
75
8
64
72
81
90
10
12
15
6120
6800
7480
8160
22
27
33
40
50
55
61
66
52
62
73
85
11
14
17
20
84
95
106
117
16
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Supply fan performances
Table 10 -TSD 060 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
899 0.43 944 0.49 985 0.54 1023 0.59 1060 0.64 1093 0.69 1126 0.74
904 0.49 947 0.54 988 0.58 1028 0.64 1067 0.70 1104 0.76 1138 0.82 1171 0.87
918 0.57 958 0.62 998 0.67 1036 0.71 1073 0.76 1111 0.82 1147 0.89 1182 0.96 1215 1.02
930 0.65 977 0.71 1016 0.77 1053 0.82 1089 0.88 1124 0.93 1158 0.98 1191 1.03 1226 1.10 1258 1.17
909 0.71 950 0.76 990 0.80 1034 0.87 1074 0.93 1110 1.00 1143 1.06 1177 1.12 1209 1.17 1241 1.23 1272 1.29
-
-
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
2720
3060
3400
3740
4080
1160 0.79 1190 0.84 1222 0.90
1203 0.93 1232 0.98 1262 1.04
1246 1.09 1276 1.15 1306 1.21
1290 1.25
-
-
-
-
-
-
-
-
-
-
Table 11 -TSH 060 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
898 0.43 953 0.48 1001 0.54 1045 0.59 1087 0.65 1129 0.71 1168 0.77 1206 0.83 1241 0.89
897 0.48 953 0.54 1008 0.60 1058 0.67 1102 0.73 1143 0.79 1181 0.85 1219 0.92 1256 0.99 1291 1.05
908 0.54 961 0.60 1012 0.67 1062 0.74 1111 0.81 1157 0.88 1198 0.95 1237 1.02 1274 1.09 1309 1.16 1343 1.24
923 0.63 978 0.69 1028 0.76 1075 0.83 1120 0.91 1166 0.99 1211 1.06 1254 1.14 1294 1.22 1330 1.29
997 0.80 1049 0.87 1096 0.94 1140 1.02 1183 1.10 1223 1.18 1266 1.27
-
-
-
-
-
-
-
-
-
-
-
-
-
-
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
2720
3060
3400
3740
4080
1275 0.96 1306 1.02 1338 1.09
1326 1.12 1359 1.19 1390 1.26
1376 1.31
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 12 -TSD 072 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
726 0.41 769 0.47 811 0.52 851 0.58 889 0.65 925 0.71 960 0.77
706 0.43 751 0.49 792 0.55 832 0.61 871 0.67 908 0.74 944 0.81 978 0.87
732 0.51 777 0.58 818 0.64 856 0.71 893 0.77 930 0.84 964 0.91 998 0.99
715 0.54 758 0.60 802 0.68 845 0.75 883 0.82 919 0.89 953 0.96 986 1.04 1019 1.11
706 0.58 749 0.64 789 0.71 830 0.79 870 0.87 909 0.95 945
1.02 979
1.10 1011 1.18 1043 1.26
325
350
375
Fan
RPM
Fan
RPM
Fan
kW
3
m /h
kW
kW
RPM
3260
3670
4080
4490
4890
994 0.83 1026 0.89 1057 0.95
1010 0.94 1043 1.01 1073 1.08
1030 1.06 1063 1.14 1092 1.21
1051 1.19 1082 1.27 1112 1.35
1073 1.34 1103 1.42 1133 1.51
Table 13 -TSH 072 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
726 0.39 771 0.45 814 0.51 857 0.57 899 0.63 939 0.70 978 0.76 1015 0.83
716 0.42 762 0.48 804 0.54 843 0.60 883 0.67 922 0.74 960 0.81 996 0.87 1034 0.95
701 0.45 751 0.51 798 0.59 839 0.65 877 0.71 914 0.78 950 0.85 984 0.93 1020 1.00 1055 1.08
710 0.51 745 0.56 788 0.62 833 0.69 875 0.77 914 0.85 949 0.91 984 0.98 1016 1.06 1049 1.14 1081 1.23
726 0.58 762 0.64 795 0.70 828 0.76 869 0.82 911 0.91 950 0.99 986 1.07 1019 1.14 1051 1.22 1081 1.30 1112 1.38
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
3260
3670
4080
4490
4890
1051 0.90 1086 0.97 1118 1.04
1069 1.02 1103 1.09 1136 1.17
1089 1.16 1122 1.23 1154 1.31
1113 1.31 1144 1.40 1176 1.48
1141 1.47 1170 1.57 1199 1.66
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
18
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 14 -TSD 090 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
750 0.54 794 0.60 834 0.67 873 0.73 909 0.80 945 0.87 980 0.95 1013 1.02
787 0.66 830 0.74
871 0.82 908 0.89 943 0.96 977
1.04 1010 1.11 1043 1.19
747 0.68 789 0.74 827 0.82 867 0.90 906 0.98 944 1.06 980
1.15 1013 1.23 1045 1.31 1076 1.39
755 0.77 797 0.85 836 0.92 873 1.00 908 1.08
1.14 921 1.22 954 1.30
944
1.17 980 1.26 1016 1.35 1050 1.45 1081 1.54 1111 1.63
771 0.88 809 0.96 848 1.06 885
986 1.39 1019 1.49 1052 1.58 1085 1.69 1116 1.79 1148 1.89
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
4080
4590
5100
5610
6120
1046 1.10 1076 1.17 1106 1.25
1074 1.27 1105 1.36 1134 1.44
1105 1.47 1134 1.56 1163 1.65
1141 1.72 1168 1.80 1197 1.90
1177 1.99 1204 2.08 1232 2.18
Table 15 -TSH 090 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
-
769 0.54 814 0.61 855 0.67 893 0.73 929 0.81 965 0.88 999 0.96 1035 1.04 1070 1.12
773 0.62 817 0.68 862 0.76 904 0.85 941 0.92 975 0.98 1009 1.06 1041 1.14 1073 1.22 1104 1.31
989 1.12 1025 1.21 1056 1.28 1088 1.36 1117 1.44 1146 1.53
1.17 1000 1.25 1037 1.34 1073 1.45 1106 1.55 1136 1.63 1165 1.72 1194 1.80
942 1.22 970 1.30 996 1.37 1021 1.45 1052 1.52 1086 1.61 1121 1.71 1153 1.82 1184 1.93 1215 2.04 1242 2.13
-
-
771 0.68 805 0.74 837 0.81 870 0.87 912 0.94 951 1.03
842 0.89 873 0.96 903 1.03 930 1.10 963
913
1.14
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
4080
4590
5100
5610
6120
1104 1.19 1137 1.27 1168 1.35
1136 1.40 1167 1.48 1198 1.57
1176 1.62 1205 1.72 1233 1.82
1220 1.88 1248 1.98 1275 2.08
1269 2.22 1295 2.31 1319 2.40
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 16 -TSD 102 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4620
5200
5780
6350
6930
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
695 0.62 733 0.71 769 0.81 802 0.90 833
1.00 863 1.11
892 1.21
919 1.35
946 1.51
688 0.64 725 0.73 761 0.83 796 0.93 828
1.03 861
1.18 887
1.34 916
1.52 948
1.13
1.28
891 1.24
917 1.40
689 0.68 724 0.76 759 0.86 792 0.96 825 1.07 856
826 1.11 857 1.22 887
864 1.30 892 1.40 920
693 0.72 729 0.82 764 0.92 795 1.01
1.46 945 1.58
974
1.70
706 0.80 738 0.89 770 0.98 804 1.09 834 1.19
1.64 976 1.78 1002 1.91
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
4620
5200
5780
6350
6930
920
946
974
1.33 946 1.44 973 1.55 999 1.67 1025 1.79 1050 1.90 1073 2.02 1098 2.14
1.46 973 1.58 999 1.71 1024 1.83 1048 1.96 1072 2.09 1096 2.22 1119 2.34
1.63 1001 1.75 1026 1.88 1051 2.01 1074 2.14 1099 2.27 1121 2.41 1143 2.55
1001 1.82 1028 1.95 1054 2.08 1079 2.20 1103 2.34 1126 2.48 1148 2.62 1170 2.76
1029 2.04 1055 2.17 1081 2.30 1105 2.43 1130 2.58 1154 2.72 1176 2.85 1199 3.01
Table 17 -TSH 102 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4620
5200
5780
6350
6930
-
-
-
-
-
-
-
-
-
-
-
-
689 0.58 734 0.67 781 0.77 826 0.88 865 0.98 898
1.07 928
1.27 969
1.16
956 1.25
982 1.33
693 0.64 735 0.73 773 0.82 812 0.92 855 1.03 897 1.15 934
1.38 999 1.49 1026 1.58
711 0.75 743 0.82 781 0.91 819
1.12 865 1.23 899 1.34
828 1.23 857 1.31 883 1.39
1.01
853
1.11
886 1.21 925 1.34 964
930 1.45 960 1.56 994
1.47 1000 1.60 1034 1.73 1067 1.86
1.68 1028 1.82 1063 1.96 1098 2.11
735 0.89 770 0.97 799 1.04 830
796
1.14
913
1.48 945 1.60
977 1.72 1006 1.84 1034 1.96 1061 2.08 1093 2.23 1125 2.38
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
4620
5200
5780
6350
6930
1008 1.42 1033 1.51 1056 1.60 1079 1.69 1102 1.78 1125 1.87 1146 1.95 1168 2.04
1052 1.68 1078 1.78 1101 1.88 1124 1.98 1146 2.08 1168 2.18 1188 2.27 1209 2.37
1094 1.97 1120 2.08 1145 2.20 1168 2.31 1191 2.42 1213 2.53 1234 2.63 1254 2.74
1129 2.26 1158 2.40 1185 2.53 1210 2.66 1234 2.78 1256 2.90 1278 3.03 1299 3.15
1157 2.53 1188 2.70 1218 2.86 1245 3.01 1273 3.16 1297 3.31
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
20
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 18 -TSD 120 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
5440
6120
6800
7480
8160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
789 0.93 822 1.03 856
797 0.99 829 1.10 860 1.22 892
844 1.21 874 1.32 903 1.44 932
922 1.59 948 1.70 975
972 1.90 997 2.02 1022 2.14 1046 2.27 1071 2.41 1095 2.55
1.14 887
1.34 922
1.56 960
1.25
917 1.36
945 1.47
-
-
-
-
-
1.46 951 1.57
979 1.69
-
-
782
1.01
814
1.11
1.69 988 1.82 1015 1.95
803
1.14
834 1.24 864 1.36 894 1.48
1.82 1001 1.95 1028 2.09 1053 2.23
803
1.21 833 1.31 861 1.42 887 1.52
916
1.64 945 1.77
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
5440
6120
6800
7480
8160
973
1.60 999 1.72 1024 1.84 1048 1.97 1072 2.10 1095 2.23 1117 2.37 1140 2.51
1007 1.82 1033 1.94 1059 2.07 1082 2.20 1107 2.34 1130 2.49 1152 2.63 1173 2.77
1042 2.08 1068 2.21 1093 2.35 1117 2.48 1142 2.63 1164 2.76 1187 2.91 1209 3.06
1078 2.38 1103 2.52 1128 2.66 1152 2.81 1176 2.95 1198 3.10 1221 3.25
1119 2.70 1142 2.86 1166 3.02 1189 3.17 1212 3.33
-
-
-
-
-
-
-
-
Table 19 -TSH 120 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
5440
6120
6800
7480
8160
-
-
-
-
-
-
-
-
-
-
-
807 0.94 844 1.04
886
1.16 926 1.28 965
1.41 1000 1.53 1029 1.64 1057 1.75
-
792 0.99 829 1.08 865 1.19 898 1.30
930 1.41 965 1.53 1002 1.67 1038 1.81 1072 1.95 1106 2.10
986 1.73 1015 1.85 1044 1.98 1077 2.12 1111 2.28 1143 2.43
802
876
950
1.13
833 1.22 860 1.29 890 1.38 923 1.50 956 1.62
1.49 905 1.58 931 1.67 955 1.75 983 1.86 1014 1.99 1045 2.12 1072 2.25 1098 2.37 1125 2.51 1152 2.65 1182 2.81
1.91 977 2.02 1002 2.11 1025 2.20 1048 2.30 1074 2.42 1102 2.56 1131 2.71 1156 2.84 1181 2.98 1205 3.12 1229 3.27
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
5440
6120
6800
7480
8160
1084 1.86 1108 1.96 1132 2.06 1155 2.17 1177 2.27 1198 2.37 1219 2.48 1239 2.58
1134 2.22 1160 2.35 1185 2.47 1209 2.59 1231 2.70 1252 2.82 1274 2.94 1295 3.06
1174 2.58 1204 2.74 1232 2.90 1260 3.05 1283 3.18 1306 3.32
-
-
-
-
-
-
-
-
-
-
-
-
1211 2.97 1241 3.14 1270 3.31
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 20 -YSD 060 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1043 0.62 1078 0.67 1113 0.72 1145 0.77 1177 0.82
1066 0.70 1103 0.76 1137 0.82 1169 0.87 1202 0.93 1232 0.98
1052 0.73 1089 0.79 1126 0.85 1162 0.92 1196 0.98 1229 1.05 1260 1.11 1289 1.17
1051 0.82 1087 0.87 1122 0.92 1156 0.98 1190 1.03 1224 1.10 1257 1.17 1288 1.24 1320 1.32
-
-
-
-
1055 0.90 1093 0.97 1127 1.03 1160 1.09 1193 1.15 1225 1.20 1256 1.26 1288 1.32
-
-
-
-
-
-
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
2720
3060
3400
3740
4080
1208 0.87 1238 0.93 1268 0.98
1262 1.04 1290 1.09 1319 1.15
1319 1.24 1347 1.30
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Table 21 -YSH 060 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1069 0.63 1111 0.68 1151 0.74 1189 0.80 1225 0.87 1260 0.93 1293 0.99
1056 0.66 1100 0.73 1141 0.79 1180 0.85 1218 0.92 1255 0.98 1290 1.05 1324 1.12 1357 1.19
1033 0.70 1083 0.77 1131 0.84 1176 0.91 1216 0.98 1253 1.05 1289 1.13 1323 1.20 1357 1.27
-
-
-
-
-
-
-
-
-
-
-
-
1072 0.83 1117 0.90 1163 0.98 1209 1.06 1251 1.14 1292 1.21 1329 1.29
1161 1.06 1203 1.14 1245 1.23 1287 1.31
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
2720
3060
3400
3740
4080
1324 1.06 1355 1.13 1383 1.20
1390 1.26
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
22
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 22 -YSD 072 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
820 0.54 859 0.60 896 0.66 932 0.72 968 0.78 1000 0.84
814 0.58 854 0.64 891 0.71 928 0.78 963 0.84 996 0.91 1028 0.98
814 0.64 853 0.70 890 0.77 926 0.84 961 0.91 994 0.98 1027 1.05 1058 1.13
815 0.70 857 0.77 894 0.84 929 0.91 963 0.98 996
1.06 1028 1.14 1060 1.22 1090 1.29
818 0.77 860 0.85 899 0.93 936 1.01
970 1.08 1003 1.16 1035 1.24 1066 1.32 1096 1.40 1125 1.48
325
350
375
Fan
RPM
Fan
RPM
Fan
kW
3
m /h
kW
kW
RPM
3260
3670
4080
4490
4890
1033 0.90 1063 0.96 1094 1.03
1061 1.05 1091 1.12 1121 1.18
1090 1.21 1118 1.28 1149 1.36
1120 1.38 1150 1.46 1178 1.54
1155 1.57 1181 1.66 1210 1.75
Table 23 -YSH 072 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
824 0.52 866 0.59 907 0.65 947 0.71 986 0.78 1023 0.84 1059 0.92
-
826 0.57 865 0.64 903 0.71 943 0.78 979 0.84 1017 0.91 1053 0.98 1087 1.06
-
-
836 0.64 874 0.70 911 0.77 947 0.84 982 0.92 1017 1.00 1051 1.07 1085 1.15 1119 1.23
847 0.72 888 0.80 924 0.86 959 0.93 993 1.00 1026 1.08 1058 1.17 1089 1.25 1122 1.34 1153 1.42
818
0.74 858 0.81 900 0.88 940 0.97 977 1.05 1010 1.13 1042 1.20 1073 1.27 1104 1.36 1133 1.45 1163 1.54 1192 1.64
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
3260
3670
4080
4490
4890
1093 0.98 1126 1.06 1156 1.12
1121 1.13 1153 1.21 1185 1.29
1151 1.30 1182 1.38 1214 1.47
1184 1.50 1215 1.59
1221 1.72
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 24 -YSD 090 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
869 0.73 906 0.80 941 0.87 976 0.94 1009 1.01 1042 1.09 1073 1.17
887 0.85 922 0.92 958 0.99 991 1.07 1024 1.14 1055 1.22 1086 1.30 1117 1.39
865 0.89 905 0.98 943 1.06 979 1.15 1012 1.23 1044 1.31 1075 1.39 1105 1.47 1134 1.56 1163 1.65
1.13 965 1.22 1001 1.32 1036 1.41 1068 1.50 1099 1.59 1129 1.68 1157 1.77 1185 1.86 1212 1.95
1.24 963 1.33 995 1.42 1028 1.51 1061 1.61 1093 1.71 1126 1.82 1157 1.92 1185 2.02 1212 2.11 1239 2.21 1265 2.31
858 0.97 894 1.05 929
930
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
4080
4590
5100
5610
6120
1104 1.24 1134 1.32 1163 1.40
1146 1.47 1174 1.56 1203 1.65
1191 1.74 1218 1.83 1245 1.92
1238 2.04 1265 2.14 1292 2.24
1290 2.40 1316 2.51 1340 2.61
Table 25 -YSH 090 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4080
4590
5100
5610
6120
-
-
-
-
-
-
851 0.67 889 0.73 926 0.80 962 0.88 997 0.95 1031 1.03 1067 1.11 1101 1.19 1134 1.26
880 0.80 919 0.88 955 0.94 989 1.01 1022 1.09 1054 1.17 1086 1.26 1117 1.35 1148 1.43 1180 1.52
1.12 1023 1.21 1056 1.28 1086 1.36 1116 1.43 1146 1.52 1175 1.62 1204 1.72 1232 1.81
985 1.22 1023 1.30 1058 1.40 1092 1.51 1124 1.60 1154 1.68 1182 1.77 1210 1.85 1237 1.94 1264 2.04 1290 2.14
1029 1.47 1061 1.55 1096 1.64 1130 1.74 1162 1.85 1193 1.96 1222 2.06 1250 2.16 1276 2.25 1302 2.34 1327 2.43 1352 2.53
-
-
-
-
869 0.87 910 0.94 950 1.03 989
949 1.14
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
4080
4590
5100
5610
6120
1166 1.34 1197 1.42 1229 1.50
1210 1.60 1241 1.69 1269 1.78
1260 1.91 1287 2.00 1316 2.10
1316 2.25 1342 2.36 1367 2.46
1376 2.64 1401 2.75 1425 2.87
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
24
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 26 -YSD 102 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4620
5200
5780
6350
6930
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
787 0.85 819 0.96 850
1.06 879
1.23 918
1.44 959
1.69 999
1.17
907 1.27
934 1.39
971 1.58
-
-
-
-
794 0.92 827 1.02 859
1.13 890
1.34 946 1.46
-
-
-
-
805 1.00 837
1.11
869 1.22 900 1.33 929
1.56 986 1.68 1011 1.80
1.81 1025 1.94 1051 2.06
792 1.00 823
1.10
854 1.21 884 1.33
914
1.45 943 1.57 971
786
1.03 818
1.14
848 1.24 877 1.34 905 1.46 933 1.58
961 1.71 988 1.84 1015 1.97 1041 2.10 1067 2.23 1092 2.36
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
4620
5200
5780
6350
6930
960
997
1.50 987 1.62 1013 1.73 1038 1.85 1064 1.97 1087 2.09 1111 2.21 1134 2.34
1.70 1023 1.83 1047 1.95 1070 2.08 1094 2.21 1117 2.34 1140 2.47 1163 2.60
1037 1.93 1061 2.06 1085 2.19 1107 2.33 1130 2.46 1151 2.60 1174 2.75 1194 2.88
1077 2.19 1100 2.32 1123 2.46 1147 2.61 1168 2.75 1189 2.89 1211 3.04 1231 3.19
1117 2.50 1140 2.64 1164 2.78 1187 2.92 1208 3.07 1229 3.22
-
-
-
-
Table 27 -YSH 102 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4620
5200
5780
6350
6930
-
-
-
-
-
-
-
787 0.79 831 0.89 869 0.99 901
798 0.88 841 1.00 883 1.11 923 1.23 958 1.35 989 1.45 1017 1.55 1045 1.65 1070 1.75 1094 1.85
1.14 898 1.25 937 1.37 975 1.51 1011 1.64 1045 1.77 1075 1.89 1103 2.01 1128 2.12 1152 2.23
1.23 899 1.34 930 1.45 961 1.56 994 1.68 1028 1.82 1063 1.96 1097 2.11 1129 2.26 1159 2.40 1186 2.53 1210 2.65
1.57 970 1.70 999 1.81 1027 1.93 1055 2.05 1085 2.19 1118 2.34 1150 2.50 1181 2.66 1211 2.82 1239 2.97 1267 3.13
1.08 931
1.17 959
1.26 986
1.35 1011 1.43 1036 1.52
-
-
-
793 0.94 830 1.04 863
865
937
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
4620
5200
5780
6350
6930
1059 1.61 1082 1.69 1104 1.78 1127 1.87 1149 1.96 1170 2.05 1191 2.14 1212 2.24
1117 1.95 1139 2.05 1161 2.15 1182 2.24 1203 2.35 1222 2.44 1243 2.54 1262 2.64
1176 2.34 1198 2.45 1219 2.56 1241 2.67 1261 2.78 1280 2.88 1299 2.99 1319 3.11
1233 2.78 1256 2.90 1278 3.03 1298 3.15 1319 3.27
1291 3.27
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 28 -YSD 120 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
5440
6120
6800
7480
8160
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
891 1.26 921
1.37 949
1.66 999
1.49
976 1.61 1001 1.73
-
-
913
1.42 942 1.54 971
1.78 1025 1.90 1052 2.03
-
-
913
976
1.48 941 1.60
969 1.73 997 1.86 1024 1.99 1050 2.12 1076 2.26 1101 2.39
895 1.48 923 1.59 949 1.70
1.83 1003 1.96 1029 2.10 1054 2.24 1079 2.38 1104 2.53 1129 2.67 1153 2.81
939
1.75 967 1.87 992 1.99 1017 2.12 1042 2.24 1066 2.38 1090 2.52 1114 2.67 1138 2.83 1161 2.98 1184 3.14 1207 3.30
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
5440
6120
6800
7480
8160
1027 1.86 1051 1.99 1075 2.12 1098 2.25 1120 2.38 1143 2.52 1166 2.66 1189 2.80
1076 2.17 1100 2.30 1122 2.44 1145 2.58 1167 2.73 1188 2.87 1210 3.02 1230 3.17
1126 2.53 1149 2.67 1172 2.81 1194 2.96 1216 3.12 1236 3.26
-
-
-
-
-
-
-
-
-
-
-
-
1176 2.96 1200 3.11 1222 3.26
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Table 29 -YSH 120 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
5440
6120
6800
7480
8160
-
-
-
-
-
-
-
-
-
-
-
-
924 1.28 962 1.40
998 1.52 1028 1.64 1055 1.74 1082 1.85 1107 1.95 1131 2.06
921 1.37 955 1.49 992 1.63 1028 1.77 1063 1.91 1096 2.05 1126 2.19 1153 2.31 1178 2.43 1202 2.55
943
1.57 973 1.68 1002 1.80 1031 1.92 1062 2.06 1096 2.21 1129 2.36 1161 2.52 1192 2.68 1222 2.84 1249 2.99 1273 3.13
1031 2.06 1060 2.19 1086 2.32 1113 2.45 1139 2.57 1167 2.73 1198 2.90 1228 3.07 1257 3.24
-
-
-
-
-
-
-
-
-
-
-
-
1119 2.58 1146 2.79 1171 2.93 1195 3.07 1219 3.21 1243 3.36
-
-
-
-
-
-
325
350
375
400
425
450
475
500
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
kW
kW
kW
kW
kW
5440
6120
6800
7480
8160
1154 2.16 1176 2.27 1197 2.37 1218 2.47 1238 2.58 1257 2.68 1276 2.78 1296 2.89
1224 2.67 1247 2.79 1268 2.91 1288 3.02 1308 3.14 1328 3.26
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1296 3.26
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
26
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 30 - WSD 060 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
933 0.47 975 0.53 1014 0.58 1050 0.63 1085 0.68 1118 0.72
892 0.48 935 0.52 976 0.57 1016 0.62 1056 0.68 1093 0.74 1128 0.80 1160 0.86
904 0.55 945 0.60 985 0.65 1023 0.70 1061 0.75 1098 0.80 1135 0.86 1170 0.93 1203 1.00
913 0.63 959 0.68 1001 0.74 1038 0.80 1074 0.85 1109 0.90 1143 0.96 1177 1.01 1212 1.07 1244 1.14
933 0.74 972 0.78 1014 0.84 1056 0.90 1094 0.97 1128 1.03 1160 1.09 1193 1.15 1225 1.20 1256 1.26 1287 1.32
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
2720
3060
3400
3740
4080
1151 0.78 1183 0.83 1214 0.88
1192 0.91 1223 0.97 1252 1.02
1235 1.06 1265 1.12 1295 1.19
1276 1.21 1308 1.29
-
-
-
-
-
-
-
-
Table 31 - WSH 060 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
2720
3060
3400
3740
4080
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
941 0.47 990 0.52 1034 0.58 1077 0.64 1119 0.70 1158 0.75 1196 0.82 1231 0.88
937 0.52 992 0.58 1043 0.65 1088 0.71 1130 0.77 1169 0.83 1207 0.90 1244 0.96 1280 1.03
945 0.58 995 0.65 1045 0.72 1094 0.79 1141 0.86 1185 0.93 1224 1.00 1260 1.07 1295 1.14 1330 1.21
901 0.60 958 0.67 1009 0.73 1057 0.80 1101 0.88 1146 0.95 1192 1.03 1235 1.11 1277 1.18 1314 1.26
973 0.76 1026 0.84 1075 0.91 1120 0.98 1163 1.06 1204 1.14 1245 1.23
-
-
-
-
-
-
-
-
-
-
-
-
-
-
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
2720
3060
3400
3740
4080
1265 0.94 1298 1.00 1330 1.07
1314 1.10 1346 1.16 1380 1.24
1363 1.28
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 32 - WSD 072 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
705 0.38 751 0.44 794 0.50 835 0.56 874
0.62 912 0.68 948 0.75 982 0.81
736 0.47 779 0.53 821 0.59 860 0.65 898 0.72 936 0.79 971 0.86 1004 0.93
720 0.50 768 0.56 810 0.63 850 0.70 888 0.76 925 0.83 961 0.91 995 0.98 1027 1.06
709 0.53 753 0.60 799 0.67 843 0.75 882 0.82 919 0.89 954 0.97 987
1.04 1021 1.12 1053 1.20
705 0.58 749 0.64 791 0.72 832 0.79 874 0.88 914 0.96 950 1.04 985
1.12 1018 1.20 1050 1.28 1081 1.36
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
3260
3670
4080
4490
4890
1015 0.87 1047 0.93 1079 0.99
1037 1.00 1069 1.07 1099 1.14
1060 1.13 1091 1.21 1121 1.29
1085 1.28 1115 1.36 1145 1.45
1112 1.44 1140 1.53 1170 1.62
Table 33 - WSH 072 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
3260
3670
4080
4490
4890
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
750 0.42 794 0.48 838 0.55 882 0.61 923 0.67 963 0.73 1002 0.80 1038 0.87
695 0.40 745 0.46 789 0.51 830 0.58 871 0.65 910 0.72 950 0.79 987 0.86 1025 0.93 1060 1.00
737 0.49 787 0.57 831 0.64 870 0.70 908 0.76 944 0.84 980 0.92 1015 0.99 1051 1.07 1085 1.15
740 0.55 781 0.61 828 0.68 872 0.77 911 0.84 948 0.91 983 0.98 1016 1.06 1049 1.14 1081 1.23 1113 1.31
990 1.08 1023 1.15 1055 1.23 1086 1.31 1117 1.40 1147 1.49
761 0.64 795 0.70 828 0.76 871 0.83 913 0.91 953 1.00
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
3260
3670
4080
4490
4890
1073 0.94 1107 1.01 1140 1.09
1096 1.07 1129 1.15 1162 1.23
1118 1.23 1152 1.31 1185 1.39
1146 1.40 1178 1.49 1208 1.57
1178 1.59 1206 1.68 1236 1.77
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
28
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 34 - WSD 090 Available static pressure
External Static Pressure (Pa)
25
50
75
100
125
150
175
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
768 0.56 810 0.63 850 0.70 888 0.76 925 0.83 961 0.91 995 0.98 1027 1.06
763 0.63 807 0.70 850 0.78 889 0.85 926 0.93 961 1.00 995 1.08 1027 1.15 1059 1.23
770 0.71 810 0.78 849 0.86 890 0.95 929 1.03 967
1.12 1000 1.20 1034 1.28 1065 1.36 1095 1.45
782 0.83 823 0.90 861 0.97 897 1.05 933 1.12
969 1.23 1006 1.33 1041 1.42 1074 1.52 1104 1.60 1134 1.70
798 0.94 838 1.04
876
1.12
913
1.20 947 1.28 980 1.37 1013 1.47 1047 1.57 1080 1.67 1113 1.77 1144 1.88 1173 1.98
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
4080
4590
5100
5610
6120
1060 1.13 1091 1.21 1121 1.29
1091 1.32 1121 1.40 1151 1.49
1125 1.53 1154 1.62 1183 1.71
1163 1.79 1191 1.88 1217 1.97
1202 2.08 1229 2.17 1256 2.27
Table 35 - WSH 090 Available static pressure
External Static Pressure (Pa)
150 175
25
50
75
100
125
200
225
250
275
300
Fan
RPM
Fan
RPM
3
m /h
RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW RPM kW
kW
kW
4080
4590
5100
5610
6120
-
-
-
-
-
-
-
787 0.57 831 0.64 870 0.70 908 0.76 944 0.84 980 0.92 1015 0.99 1051 1.07 1085 1.15
753 0.59 792 0.65 839 0.72 882 0.80 922 0.88 958 0.95 992 1.02 1026 1.10 1058 1.18 1090 1.27 1122 1.36
1.08 1011 1.18 1044 1.25 1076 1.33 1106 1.41 1136 1.49 1165 1.59
988 1.22 1026 1.31 1062 1.42 1096 1.52 1129 1.61 1158 1.69 1187 1.78 1214 1.86
1.20 963 1.28 990 1.35 1016 1.43 1045 1.51 1079 1.59 1115 1.69 1148 1.80 1180 1.91 1210 2.02 1239 2.12 1266 2.21
-
789 0.71 822 0.78 853 0.84 892 0.91 935 0.99 974
862 0.93 892 1.01 921 1.08 951 1.15
934
325
350
375
Fan
RPM
Fan
RPM
Fan
RPM
3
m /h
kW
kW
kW
4080
4590
5100
5610
6120
1118 1.23 1152 1.31 1185 1.39
1153 1.45 1185 1.53 1216 1.62
1194 1.68 1223 1.78 1251 1.88
1242 1.96 1269 2.06 1296 2.17
1291 2.30 1317 2.39 1343 2.49
Standard drive
Oversize drive
Note : Data includes pressure drops for standard filters and wet coils
RT-SVX20A-E4
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Over current protection
Appropriate connectors must be
provided. Flexible pipe supports are
required to prevent noise
transmission in the building's
structure. Ensure all the connections
are tightened.
Electrical connection
The branch circuit feeding the unit
must be protected in accordance
with national or local codes and
maximum unit amps indicated in
Table 36.
The electric panel is located in the
unit compressor section. Remove
the compressor access panel.The
unit is designed to run with 400 V
+/- 5%/50 Hz/ 3 ph.
Note:
Power wiring
1. Earthing must be executed in
compliance to national and local
legislation.
2. The machines are designed for a
short-circuit current of 10 kA. In
the event of a higher application,
contact your local sales office.
Factory supplied disconnect switch
(option)
The unit's power supply must be
provided by 4-wire cable with cross-
sectional areas complying with
legislation.
The disconnect switch is factory
mounted. It is located in the
compressor section. Mount the
disconnect switch onto the exterior
of the unit, between the condenser
coil and the electrical panel (near
the unit top corner). Wire the
disconnect switch from the power
terminal block in the panel to the
disconnect switch with the wire
bundle provided by following the
electrical diagram found in the unit.
The power supply cables must be
laid in leak-tight pipes and pass
through the bottom of the electric
panel for units without electric
heaters and through the heat
section when electric heater option
is selected.The cables must not be
taut.
Compressor electrical phasing
Proper phasing of the electrical
power wiring is critical for proper
operation and reliability of the scroll
compressor and fans.
Proper rotation of the scroll
compressor must be established
before the unit is started.This is
accomplished by confirming that
the electrical phase sequence of the
power supply is correct.The motor
is internally connected for clockwise
rotation with the inlet power supply
phased A,B,C.
The direction of rotation may be
reversed by interchanging any two
of the line wires. It is this possible
interchange of wiring that makes a
phase sequence indicator necessary
if the operator is to quickly
Figure 13 - Power supply
determine the phase rotation of the
compressor motor.
1
1 = Power supply
30
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
The "ABC" indicator on the face of
the phase indicator will glow if
phase is ABC for terminals L1, L2,
L3.
WARNING! Disconnect all power,
including remote disconnects, and
discharge all capacitors before
servicing.
IMPORTANT! After completion of
wiring, check all electrical
Follow proper lockout/tagout
procedures to ensure the power
cannot be inadvertently energized.
After power is removed, allow
4 minutes for capacitors to
connections, and ensure all
connections are tight. Replace and
secure all electrical box covers and
access doors before leaving unit or
connecting power to circuit
supplying the unit.
discharge. Verify with an
appropriate voltmeter that all
capacitors have discharged. Failure
to disconnect power and/or
discharge capacitors before
servicing could result in death or
serious injury. For additional
information regarding the safe
discharge of capacitors, seeTrane
Service Bulletin PROD-SVB06A.
CAUTION! Units with scroll
compressors are not equipped with
crankcase heaters.
Table 36 - Unit wiring
Standard Supply Fan Motor
Oversized Supply Fan Motor
Maximum Overcurrent
Maximum Overcurrent
Main power
supply
(V/Ph/Hz)
Minimum Circuit
Protective Device (Fuse
Ampacity
Minimum circuit
Protective Device (Fuse
ampacity
Unit Model
and size
or Circuit Breaker)
(A)
or Circuit Breaker)
(A)
(A)
(A)
Without Electric heat option
TSD/TSH 060
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
18,2
24,4
26,2
28,3
32,6
18,2
24,4
26,2
28,3
32,6
20,1
23,1
26,2
32
32
40
40
40
32
32
40
40
40
32
32
40
19,3
25,5
27,2
29,3
32,6
-
32
32
40
40
40
-
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
25,5
27,2
29,3
32,6
21,2
24,2
27,2
32
40
40
40
32
32
40
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
With Electric heat
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
26,4
37,8
50
50
50
63
63
50
63
63
27,5
38,9
40,2
51,1
51,8
41,9
56,3
59,3
50
50
50
63
63
50
63
63
39,2
50,1
51,8
40,8
55,2
58,3
TSD/TSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
RT-SVX20A-E4
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Table 37 - Compressor and condenser motors
Compressor motor
Condensor fan motor
Main
Locked
rotor
amps
(A)
Main
power
supply
(V)
Locked
rotor
amps
(A)
Number
of
motors
Number
of
phases
Motor
HP
(kW)
Rated
amps
(A)
Number
of
motors
Number
of
phases
Motor
HP
(kW)
Rated
amps
(A)
Unit Model
and size
power
supply
(V)
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
1
1
1
2
2
1
1
1
2
2
1
1
1
400
400
400
400
400
400
400
400
400
400
400
400
400
3
3
3
3
3
3
3
3
3
3
3
3
3
4,2
5,6
10,3
13,7
74
95
1
1
1
2
2
1
1
1
2
2
1
1
1
400
400
400
400
400
400
400
400
400
400
400
400
400
1
1
1
1
1
1
1
1
1
1
1
1
1
0,3
1.0
3.0
3.0
3.0
3.0
1.0
3.0
3.0
3.0
3.0
1
2,8
7,1
7,1
7,1
7,1
2,8
7,1
7,1
7,1
7,1
2,8
7,1
7,1
0,56
0,56
0,56
0,56
0,3
6,2
14,3
100
4.5 / 2.8
10 / 7.5
74 / 48
4.5 / 3.5 10.7 / 9.2 74 / 62
4,2
5,6
10,3
13,7
74
95
0,56
0,56
0,56
0,56
0,3
6,2
14,3
100
4.5 / 2.8
10 / 7.5
74 / 48
4.5 / 3.5 10.7 / 9.2 74 / 62
4,5
5
11,8
12,6
14,3
74
101
100
0,56
0,56
3
6,2
3
Table 38 - Supply fan motor
Standard supply fan motor
Oversized supply fan motor
Main
power
supply
(V)
Locked
rotor
amps
(A)
Main
power
supply
(V)
Locked
rotor
amps
(A)
Number
Number
of
phases
Motor
HP
(kW)
Rated
amps
(A)
Number
of
motors
Number
of
phases
Motor
HP
(kW)
Rated
amps
(A)
Unit Model
of
and size
motors
TSD/TSH 060
TSD/TSH 072
TSD/TSH 090
TSD/TSH 102
TSD/TSH 120
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
WSD/WSH 060
WSD/WSH 072
WSD/WSH 090
1
1
1
1
1
1
1
1
1
1
1
1
1
400
400
400
400
400
400
400
400
400
400
400
400
400
3
3
3
3
3
3
3
3
3
3
3
3
3
1,1
1,1
1,5
1,5
2,2
1,1
1,1
1,5
1,5
2,2
1,1
1,1
1,5
3,2
3,2
4,3
4,3
5,3
3,2
3,2
4,3
4,3
5,3
3,2
3,2
4,3
25,3
25,3
36,4
36,4
57.0
-
1
1
1
-
-
-
3
3
3
-
-
-
-
400
400
400
-
1,5
2,2
2,2
-
4,3
5,3
5,3
-
36,4
57.0
57.0
-
25,3
25,3
36,4
36,4
57.0
-
-
-
-
-
-
1
1
1
-
400
400
400
-
3
3
3
-
1,5
2,2
2,2
-
4,3
5,3
5,3
-
36,4
57.0
57.0
-
25,3
25,3
36,4
-
-
-
-
-
-
1
1
400
400
3
3
1,5
2,2
4,3
5,3
36.4
57.0
32
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
CAUTION!The unit 24 V transformer
must not be used to power
accessories mounted on site, other
than those proposed byTrane.
Control wiring
The control circuit is 24 V AC. Unit
includes a 400/24 V transformer.
WARNING!The unit disconnect
switch must be opened and locked
open. Risk of injury and
electrocution.
Unit controlled by thermostat
Figure 14 -Thermostat wiring
J7
J6
RT-SVX20A-E4
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
TraneTHS01,THS02,THP01 and
THP02Thermostats are directly
connected to RTRM board
(J7 connector).
Unit controlled by BAS
Each unit must be equipped with a
TCI-R board. A communication bus
(twisted shielded pair) must link
eachTCI-R to theTrane RoofTop
Manager (RTM) or to the
TraneTHS03 andTHP03 thermostats
are directly connected to RTRM
board (J6 connector).
communication gateway (in the
case of an external BAS). Connect
one temperature sensor to each
Install the electrical link between the
thermostat (thermostat terminal
strip) and the unit (J6 or
J7 connector) in compliance with
the interconnection diagram.The
low voltage wiring must not be laid
in the same pipes as the power
cables.
®
unit. LonTalk communication
interface LTCl-R board allows ICS
communication between a
ReliaTel™ unit and LonTalk
®
communication applications.
Unit controlled byTracker™
supervisor
The sizes and lengths of the
thermostat connection wires are
given inTable 39.The total
resistance of these control cables
must not exceed 5 ohms. If the
resistance exceeds this value the
thermostat may not operate with
the same precision.
The units must also be equipped
with theTCI-R communication
board. One remote sensor is
required on each unit for a constant
flow volume. In the case of a
variable flow installation
(VariTrac™) these sensors must not
be installed. A twisted shielded pair
must be used for the
Table 39 - Zone sensor wire and
maximum length
communication link.The main
functions of theTracker™ supervisor
are control of setpoints, timetable
management (Programming) and
display of faults. For more details
refer to the supervisor
Maximum
Wire size
wire lengh
(mm²)
(m)
0,33
0,5
0,75
1,3
2
45
76
115
185
300
documentation.
34
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
The CO2 sensor is designed to
operate with a nominal 24 Vac
supply.The power supply should
maintain the voltage between 20 to
26 Vac.
CO2 sensors
Wall-mounted and duct-mounted
CO2 sensors
Power supply requirements
CAUTION! Make sure that you
connect the power wire only to the
24V terminal. Connecting the power
wire to the output terminal may
result in equipment damage.
Table 41 - CO2 sensor wire size
Maximum
Wire size
wire lengh
(mm²)
(m)
0,25
0,5
1
50
100
200
Table 40 - Specifications
Wall-mounted
Duct-mounted
Measuring range CO2
Accuracy at 25°C
0-2000 ppm
< +/- [40 ppm CO2 + 3% of
reading]
(included repeatability and
calibration uncertainty)
< +/- [30 ppm CO2 + 2% of
reading]
(included repeatability and
calibration uncertainty)
Non-linearity
< 1.0% full scale
0.3% full scale/°C
< 5.0% full scale/ 5 years
5 years
Temperature dependence of output
Long-term stability
Recommended calibration interval
Response time
1 minute (0-63%)
Operating temperature
Storage temperature
15-35°C
-5-45°C
-20-70°C
Humidity range
0-85% relative humidity
Airflow range
0-10 m/s)
Output signals (jumper selectable)
Resolution of analog outputs
0-10 Vdc
10 ppm CO2
Current output: max 500
Voltage output: min. 1000
Recommended external load
Power supply
Nominal 24 Vac
< 5 VA
Power consumption
Warm-up time
< 15 minutes
Dimensions (mm)
108 x 80 x 36
80 x 80 x 200
RT-SVX20A-E4
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Wiring the wall-mounted CO2
sensor
Wiring the duct-mounted CO2
sensor
1. Connect the common wire from
the controller to the ground
terminal (terminal 0) (Figure 16).
2. For voltage output, connect the
signal wire to terminal V.
3. Connect the power according to
the guidelines in Power supply
requirements.
DVC setpoint potentiometer on
economizer module can be adjusted
as follows:
0% - 500ppm, 50% - 1000 ppm,
100% - 1500ppm
The outside air damper will
modulate from minimum position
setting to up to 100% while
attempting to maintain the CO2
setpoint.
Figure 15 - Wall-mounted CO2 sensor wiring
Figure 16 -Terminal connections and LED locations
2
3
1
4
1 = Outer jumper
2 = Power terminal
3 = Ground terminal
4 = Output terminals
36
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Figure 17 - Wall-mounted CO2 sensor
Mounting the wall-mounted sensor
1. Select a proper location in the
room to mount the CO2 sensor.
Look for an interior wall with
good air circulation,
approximately 1.4 m from the
floor.
2. Remove the back plate from the
sensor and thread the power
wires and output signal wire
through the hole in the back
plate (Figure 17).
For surface wiring, make cut-
outs with pliers to the thinner
section of the upper or lower
edge of the back plate and to
thread the wires through.
1
3. Mount the back plate to the wall
with screws. Note that the arrow
on the back plate shows the
mounting direction.
4. On the circuit board, use the two
jumpers next to the terminal
block to set up the type of output
(0-10 Vdc) (Figure 18).
1 =Thinner section for cut-out
5. Insert the circuit board in the
back plate. (Figure 18.) Do not
press the metal tube while
inserting the circuit board.
6. Connect the power and signal
wires to the screw terminals of
the circuit board. Figure 16
shows the terminal locations.
Figure 18 - Jumper settings
RT-SVX20A-E4
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Mounting the duct-mounted CO2
sensor
1. Select a proper location on the
duct to mount the CO2 sensor.
2. Drill a 22-25 mm hole in the
mounting surface for sensor
insertion (Figure 19).
3. Attach the mounting plate to the
duct wall with four screws.
4. Insert the sensor through the
mounting plate, adjusting the
depth for optimal air sensing.
CO2 sensor maintenance
This CO2 sensor has excellentThis
CO2 sensor has excellent stability
and requires no maintenance. In
most environments the
recommended calibration interval is
five years. A trained service
technician can use a portable CO2
meter to certify sensor calibration.
If, when checking the sensor, the
reading differs too much from the
reference value, the sensor can be
recalibrated in the field. A
calibration kit, software, and
Figure 19 - Duct-mounted CO2 sensor
diameter
calibration gases are required. If
certified accuracy is required, the
sensor must be calibrated against
accurate and traceable calibration
gases in a laboratory. ConsultTrane
BAS for further details.
5
1 /8 in. (42 mm)
7
/8 in. (22 mm)
5
1 /8 in.
(42 mm)
Figure 20 - Duct-mounted CO2 sensor insertion depth
1
1
1
2 /2 in. (64 mm)
3 /8 - 5 /2 in. (80 - 140 mm)
38
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Note:This potentiometer allows to
adjust the permanent fresh air
intake from 0 to 50%.
Remote potentiometer
To install the remote potentiometer,
cut the jumper WL on the
economizer ECA board, and connect
the wires to J11 and J12.
0 W corresponds to closed fresh air
damper.
270 W corresponds to 50% open
fresh air damper.
Figure 21 - Remote potentiometer dimensions
Figure 22 - Remote potentiometer wiring
1 = Remote potentiometer
2 = ECA Board
WH = White wire
RD = Red Wire
BU = Blue wire
_____ Factory wiring
------- Field wiring
RT-SVX20A-E4
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Figure 24 - Connection of fire thermostat
withTCI board
Note: Do not permit element guard
to touch internal parts. Do not
locate sensor where the air
Fire thermostat
There are two sensors in the fire
thermostat Kit: Sensor X13100040-
01 is factory-set to open at 57°C,
Sensor X13100040-02 is set to open
at 115°C.
circulation is restricted by baffles.
At the selected location, cut a hole
to clear element guard and drill
holes for mounting screws
according to Figure 23. Connect
wires according to Figure 24.
1
Sensors are mounted directly in the
ductwork.They should be installed
where elements can respond
2
quickly to air temperature changes.
If not possible, the sensor may be
installed on a suitable bracket so
the air is drawn across the element.
Sensor X13100040-01 has to be
mounted in the return air duct.
Sensor X13100040-02 has to be
mounted in the supply air duct.
1 = Field-supplied emergency stop
device
2 = Remove factory-supplied jumper
Figure 23 - Duct mounting of fire
thermostat
1 = Fire thermostat
2 = Hole in the duct
40
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Clogged filter detector
Smoke detector
This device is mounted in the
indoor fan section.The sensor
measures the difference in pressure
before and after the filter section.
The information is sent to theTHP03
thermostat, to aTracker™ or to a
BMS.The setting range is 40 to
300 Pa.
This device is used to detect smoke
in the air stream. It includes a
factory mounted detector connected
to a central panel, both fitted in the
fan section.
When smoke is detected, it shuts off
the unit. A dry contact is available
on the control panel for a remote
default.
High temperature safety
thermostat
This additional safety device is a
manual reset thermostat for gas
fired units (YKD/YKH), required
mainly by the French ERP
regulation. It is located in the gas
burner section. It stops the gas
burner and the supply air fan when
the supply air temperature rises to
120°C.
Figure 25- Clogged filter sensor
Remote fault relay
2
This is a factory mounted relay used
to send alarm signals (dry contact)
to a local BMS or a local control
panel. With this relay, the
compressor, heating, fan and power
supply alarm output signals from
the controller are reported to a
single dry contact.
1
3
4
1 = Secure with one screw
2 = Route wire harness between coil blockoff and roof rib
3 = Secure with pop-in wire tie
4 = Remove filter if necessary
RT-SVX20A-E4
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
"THS" are non programmable
thermostats, "THP" are
programmable.
Thermostats
6 thermostats are available:
THS01/THP01,THS02/THP02 and
THS03/THP03.
01 and 02 series are conventional
thermostat, 03 series are dedicated
to the controller.
Table 42 -Thermostat features
THS01
THP01
THS02
THP02
THS03
THP03
non-programmable
programmable
X
-
X
-
X
-
-
X
-
X
-
X
electronic
X
X
X
X
X
X
unit control type design
interface card needed
for Cooling Only units
for Heat Pump units
for Gas Fired units
Cooling stages
electromech.
electromech.
electromech.
electromech.
Reliatel
Reliatel
-
-
-
-
-
-
-
-
X
-
X
-
X
X
X
2
X
X
X
2
X
-
X
-
X
2
X
2
2
2
auxiliary heating stages
(elec. heater, HWC )
2
2
1
1
2
2
heating stages
(heat pump mode)
none
none
1
1
1
1
liquid crystal display
X
X
X
X
-
X
Note: thermostats are powered up by the rooftop control (24V)
42
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
Other accessories available
Communication Interfaces
Remote temperature sensor to be
used withTHS/THP 01-02.
TRANE Communication Interface
(TCI-R) board
TZS01: Remote room temperature
sensor to be used withTHS/THP 03,
Tracker or Varitrac systems.
This is an electronic board, factory-
mounted in the main control panel,
needed to allow communication
between aTRANE Integrated
Comfort system (TRACKER or
Varitrac CCP2) and the unit. (COM3-
COM4)
DTS: Duct temperature sensor to be
used withTHS/THP 03.
TZS02: Remote room temperature
sensor with adjustable thumwheel
setpoint to be used withTracker or
Varitrac systems.
LON Communication Interface
(LCI-R) board
TZS04: Room temperature sensor
with adjustable thumbwheel and
override button, to be used with
Tracker or Varitrac systems.
This is an electronic board, factory-
mounted in the main control panel,
needed to allow communication on
®
a LonTalk Network at the unit level.
Refer to separate documentation for
more information.
®
LonTalk Communication Interface
(LCI-R) board allows Voyager units
®
to communicate on a LonTalk
Network at the unit level. Network
variables are based on the
®
LonMark . Space Comfort Controller
Functional ProfileTemplate.The
LCIV uses a FreeTopology
transceiver FTT-10A.The FTT-10A
transceiver supports non-polarity
sensitive, free topology wiring,
allowing the system installer to use
star, bus, and loop architecture.The
LCI-V can also be connected to an
optional HighTemperature Limit
Switch if installed with the rooftop
unit. For more information, see
attached manual LTCI-IN-1.
RT-SVX20A-E4
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
The hot water coil is factory
Hot water coil
mounted in the discharge section.
Two holes are provided to connect
the hot water coil.They are located
at the base of the unit. Remove the
central panel to access the coil,
using an 8 mm wrench (the bolts
are located on the bottom part of
the panels).The tubes for entering
and leaving water are equipped
with a threaded female connector.
(Down flow units only)
In order to prevent water to freeze
up in the coil during unoccupied
period or shutdown limited period,
a thermostat opens when there is a
risk of freeze-up.The services of a
water treatment specialist are
recommended if water used can
cause scaling deposits or erosion.
Insulate all the water piping likely to
be exposed to freezing
temperatures in order to avoid
freeze up of the coil and heat
losses.The water distribution
network must be fitted with vents in
places where air is likely to be
trapped.
Water connection inlet/outlet:
1 ¼" ISO R7.
Installation and connection
In order to prevent water to freeze
up in the coil during unoccupied
period or shutdown limited period,
it is recommended to use ethylene
glycol.The services of a water
treatment specialist are
recommended if water used can
cause scaling deposits or erosion.
Insulate all the water piping likely to
be exposed to freezing
temperatures in order to avoid
freeze up of the coil and heat
losses.The water distribution
network must be fitted with vents in
places where air is likely to be
trapped.
Table 43 - Ethylene glycol percentage
Ethylene glycol
Freezing point
percentage
(%)
10
(°C)
-4
Figure 26 - Hot water coil connections
20
-10
44
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
Electric Heater
Soft Starter
Electric heaters are fitted on the fan
discharge.
The soft starter is used to achieve a
progressive supply fan start and a
reduced starting current as well as
the motor starting torque.This
option is well adapted for textile
duct applications. It is factory
Heaters have two heating stages
and provided with two types of
overheat thermostats:
•
Automatic reset thermostats
which stop the electric heater
when the air temperature rises to
76°C. Automatic reset at 60°C. No
alarm output available.
installed in the main control panel.
The soft starter gradually increases
the voltage of the supply fan motor
until it reaches full line voltage.
•
The manual reset thermostat
which stop the unit when the air
temperature rises to 120°C. No
alarm output available.
The starting time can be adjusted
from 0 to 40 seconds but the soft
starter is factory set to the
maximum starting time value,
40 seconds.
Figure 27 - Soft starter
1
6
5
4
3
2
1 =Three phase mains connections
2 = Motor connections
3 = Settings
4 = Status outputs
5 = Controls
6 = LEDs
RT-SVX20A-E4
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
This option includes for the hood
itself, a wire mesh and a slidable
damper.
0 - 25% fresh air hood
The 0-25% fresh air hood allows to
introduce fresh air into the unit.
The slidable damper has to be
adjusted manually by removing the
screws and sliding it off up or down
(Figure 28).
This is a manual device fitted on the
back of the unit, sized for a
maximum of 25% of the nominal
rooftop air flow.
The amount of fresh air introduced
is then permanently fixed.
Figure 28 - 0-25% manual fresh air hood
1
3
2
1 = Intake hood
2 = Wire mesh
3 = Slidable damper
46
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Unit Options
This option includes exhaust hoods
and gravity dampers located in the
return air section. When the
pressure of the building increase,
the gravity dampers open and
relieve air to the outside.
Barometric relief
The barometric relief allows to
minimize overpressure in the
building caused by the introduction
of fresh air.This option is typically
installed when fresh air intake is
below 25% of the nominal air flow
and when the return air pressure
drop is below 25Pa.
If the return air duct pressure drop
is higher than the building
overpressure, the gravity dampers
will not open.
If the return air duct pressure drop
is lower than the building
overpressure, the gravity dampers
will open and relieve air outside of
the building.
Figure 29 - Economizer flow chart with barometric relief
S
R
S
E
R
F
F
Downflow version
Horizontal flow version
R = return
S = supply
F = fresh air
E = exhaust
RT-SVX20A-E4
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Figure 30 -Terminal strip
The terminal strip for attaching the
thermostat wires is located on the
RTRM module in the control
compartment.
Operation with a
conventional thermostat
The ReliaTel module has
conventional thermostat
connections as well as Zone Sensor
Module connections. When a
conventional thermostat is
controlling the unit, operation
differs as follows:
COM
T
When the unit is operating from a
conventional thermostat or other
binary input, the economizer
setpoint feature, relative to the
cooling and heating setpoints, is
lost.The economizer control is
based strictly on a signal from the
thermostat, but still maintains
mixed air temperature control of
53° 3°F when in the economizer
mode.The economizer enable and
disable function is still determined
by the outside air sensor through
the RTRM.
X2
Y2
•
Supply AirTempering feature is
not available. If outdoor air is
being introduced through the
equipment, discharge air
temperature may be cold when
not actively heating.
W2
G
•
•
Proportional Integral (PI) control
W1/0
Y1
is not available.
Zone Sensor Diagnostics are
only available on the RTRM
module on the J6 terminals,
instead of at the Zone Sensor in
the space.
If a single-stage thermostat is used,
only the economizer (if enabled) or
the compressor (if economizer is
disabled) will operate on a call for
cooling. A twostage thermostat is
required to achieve economizer
operation and compressor
R
•
•
Intelligent Fall-Back is not
available. If a failure occurs in
the device controlling the
equipment, operation will cease.
Heat Pump Smart Recovery and
Smart Staging is not available.
Heat Pump operation becomes
more costly unless the generic
control being applied can
accomplish this.
operation at the same time.
Customers occasionally require
operation with a conventional
thermostat rather than a zone
sensor. In some cases there is a
preference for a specific thermostat
model, and in others there is
reluctance to adopt newer
technology that may not be as well
understood as conventional
thermostats. In addition, non-Trane
Building Controllers typically
provide an interface to HVAC
equipment based on a conventional
thermostat interface. Units applied
with this type of controller need to
accept conventional thermostat
inputs.
With economizer enabled, aY1 call
for 1st stage cooling will be the
economizer.The damper will
modulate between minimum
position and 100% to maintain
mixed air temperature at 53° 3°. At
50°F the damper will be at
•
•
•
•
Remote Sensing Capabilities are
not available on most
mechanical thermostats.
minimum position. If the
SpaceTemperature Averaging
capabilities are not available on
most mechanical thermostats.
27½ to 50 VAV - Conventional
thermostat input terminals are
inactive.
Built in Night Set Back and
Unoccupied Functions function
differently with a conventional
mechanical thermostat.
economizer is enabled, aY2 call for
2nd stage cooling will start the first
compressor if required. If the
economizer is disabled, 1st stage
(Y1) will be the first compressor. If
the unit has two compressors, a call
for 2nd stage cooling (Y2) will start
the second compressor. When using
a conventional thermostat, or other
binary input, the ReliaTel controls
will only allow two stages of
cooling.
•
A built-in algorithm which allows
for automatic reset of the
discharge air temperature while
economizing is not available.
48
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Conventional thermostat signals
represent direct calls for unit
functions. In their simplest
applications, thermostat contacts
directly control contactors or other
load switching devices.This function
provides inputs for the thermostat
signals and processing to enhance
reliability and performance.
Logic is also provided to cause
appropriate unit functions when
inappropriate thermostat signals are
provided. Simultaneous calls for
heating and cooling will be ignored,
and the fan will be turned on with a
call for heating or cooling even if
the fan request is not detected.
Thermostat signals are as follows:
R 24VAC power to thermostat
Y1 Call for compressor 1 or first
stage cooling
Y2 Call for compressor 2 or 2nd
stage cooling
G Call for supply fan
W1 Call for heat 1
W2 Call for heat 2
If the thermostat is immediately
changed from a heating to a cooling
call, or vice versa, there will be a
five minute delay before the new
call will initiate.
Compressor protection and
reliability enhancement functions
(HPC, LPC, Minimum On/Off timers,
etc.). All operate the same whether
applied with zone sensors or a
conventional thermostat.
Heat pump only:
X2 Call for emergency heat
O Switchover valve On = cooling,
Off = heating
T Bias for heat anticipation for those
mechanical thermostats that use
this function
Table 44
Conventional thermostat Gas / Electric, Electric Heat
Function when energized
Input / connection
G (fan)
Fan runs continuously except during unoccupied mode (see next page)
Compressor #1 runs or economizer operates
Y1 (compressor 1 or economizer)
Y2 (compressor 2 or compressor 1 while economizing)
W1 (gas / electric heat first stage)
W2 (gas / electric heat 2nd stage)
Compressor #2 also runs, or #1 compressor runs while economizing
1st stage heat
2nd stage heat (if available)
Table 45
Conventional thermostat Heat pump
Function when energized
Input / connection
Cooling mode
G (fan)
Fan runs continuously except during unoccupied mode (see next page)
Reversing valve in cool mode
O (reversing valve during cooling)
Y1 + O (first cooling stage)
Y1 +Y2 + O (2nd cooling stage)
Heating mode
Compressor #1 runs or economizer operates
Compressor #2 also runs, or #1 compressor runs while economizing
G (fan)
Fan runs continuously except during unoccupied mode (see next page)
Both compressors run
Y1 (both compressors 1st heating stage)
Y2 (during heating nothing happens)
W2 (electric heat 2nd stage)
X2 (electric heat only)
No change
2nd stage (electric) heat
Electric heat only - no compressors
T (provides heat anticipation signal for those mechanical
thermostats that use this feature.
If the thermostat used does not have a "T" terminal, disregard
this terminal.)
RT-SVX20A-E4
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Unoccupied mode
Setting the economizer or
0-50% motorized hood
(option)
The ECA board is mounted on the
damper actuator.To access the ECA
board on economizers:
If the thermostat being used is
programmable, it will have its own
strategy for unoccupied mode and
will control the unit directly. If a
mechanical thermostat is being
used, a field applied time clock with
relay contacts connected to J6-11
and J6-12 can initiate an
•
Remove the filter access panel of
the unit.
•
The electrical power must be
disconnected to set the
unoccupied mode as follows:
•
Contacts open: Normal occupied
operation.
minimum position and check the
economizer.
•
Contacts closed: Unoccupied
operation as follows - Fan in
auto mode regardless of fan
switch position. Economizer
closes except while economizing
regardless of minimum position
setting.
•
•
Disconnect the power supply,
put the thermostat fan selector
to "ON" and the "HEAT/COOL"
selector to "OFF".This puts the
damper in the minimum
ventilation position.
To set the required minimum
ventilation air position, turn the
dial on the ECA clockwise to
increase ventilation, or anti-
clockwise to decrease ventilation.
The damper will open at this
setting whenever the fan circuit
is powered up (see Figure 25).
When the arrow on the dial's
adjustment screw is pointing to
8 o'clock, the minimum position
is roughly 0%. When the dial is
pointing to 12 o'clock it is
roughly 25%, and when the dial
is pointing to 4 o'clock it is
roughly 50% (see figure 25).
Cooling/Economizer Operation
If unit does not have an economizer,
the Cool/Econ Stage 1 and Stage 2
will call directly for mechanical
cooling (compressor) stages. If the
unit has an economizer, the
Cool/Econ stages will function as
shown inTable 46.
•
Table 46 - Cooling/Economizer Operation withThermostat
OK to
Thermostat Thermostat Call for Economizer Compressor Staging
Economize?
Y1
Y2
Cooling
Request
No
No
On
Off
Inactive
Compressor Output 1
Off
On
On
On
Inactive
Inactive
Compressor Output 2
Compressor
Outputs 1 & 2
No
Yes
Yes
Yes
On
Off
On
Off
On
On
Active
Active
Active
Off
Compressor off
Compessor
Notes:
40 to 50 ton CV only
This unit has 3 stages of cooling if using a zone sensor. If using a conventional thermostat it has 2 stages as
follows:
Y1 = 1st stage
Y1 +Y2 = 3rd stage
VAV
Thermostat inputs are ignored on VAV units.
50
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Table 47 - ECA board LED
To check the damper is functioning
correctly, the ECA is equipped with
an indicator light in the middle of
the board.This light operates as in
Table 42.
OFF:
No Power or Failure
ON:
Normal, OK to Economize
Normal, Not OK to
Economize
Slow Flash:
Fast Flash:
Pulse Flash:
1 Flash:
Communications Failure
Error Code
Actuator Fault
2 Flashes:
3 Flashes:
4 Flashes:
5 Flashes:
6 Flashes:
7 Flashes:
8 Flashes:
9 Flashes:
10 Flashes:
11 Flashes:
CO2 Sensor
RA Humidity Sensor
RA Temp Sensor
OA Quality Sensor
OA Humidity Sensor
OA Temp Sensor
MA Temp Sensor
RAM Fault
Figure 31 - Minimum fresh air adjustment
+
ROM Fault
2-10 VDC
FEEDBACK
INPUT
1
2
+
-
POWER EXHAUST
CONTACTS
EXF
1
EEPROM Fault
1
2
MIXED AIR SENSOR INPUT
COMMON
2-10 VDC
CONTROL
OUTPUT
MAT
+
-
COMMON
OHS INPUT
1
2
OAH/
OAE
NOT USED-OAT IS
CONNECTEDTO RTRM
1
2
OAT
RAT
While setting the minimum position
the damper may move towards the
new setting in several small steps.
Once the damper has remained in
the same position for 10 to 15
seconds it can be assumed it is in
the new position.
MIN POS.
SETPOINT
0-50%
1
2
RA INPUT
COMMON
GREEN
LED
ABCD
SETTINGS
COMMON
RHS INPUT
1
2
RAH/
RAE
CO2 "PURGE"
SETPOINT
ADJUSTTMENT
500-1500 PPM
1
2
CO2 SENSOR INPUT
COMMON
DCV
P1
P
-
MODBUS
+
COMMON
24VAC
SHORTED=CLOSED
OPEN=ON BOARD POT.
270 omega = 50%
REMOTE
MINIMUM
POTENTIOMETER
WHT
RED
BLUE
1 = ECA board
RT-SVX20A-E4
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
WARNING! If any operating checks
must be performed with the unit
operating, it is the technician's
responsibility to recognize any
possible hazards and proceed in a
safe manner. Failure to do so could
result in severe personal injury or
death due to electrical shock or
contact with moving parts.
Test mode procedure at the
ReliaTel™ control board
Test procedures
Operating checklist before start-up
Operating the unit from the roof
using the test mode at the
ReliaTel™ control board.
•
Unit is level, with sufficient
clearance all round
•
Duct network is correctly sized
according to the unit
CAUTION! Before proceeding with
the following test procedures, make
sure that thermostat or zone sensor
is off.
configuration, insulated, and
water-tight
•
Condensate drainage line is
correctly sized, equipped with a
trap, and sloped
Power-up initialization
CAUTION! Use one of the following
"Test" procedures to bypass some
time delays and to start the unit at
the control panel.
CAUTION! Before proceeding with
any test procedure or operation,
make sure that crankcase heaters
have been energized for at least
8 hours.
•
•
Filters are in position, of correct
size and quantity and clean
Wiring is correctly sized and
connected in accordance with
wiring diagrams
Each step of unit operation can be
activated individually by
temporarily shorting across the
"Test" terminals for two to three
seconds.The Liteport LED located
on the RTRM module will blink
when the test mode has been
initiated.The unit can be left in any
"Test" step for up to one hour
before it will automatically
terminate, or it can be terminated
by opening the main power
disconnect switch. Once the test
mode has been terminated, the
Liteport LED will glow continuously
and the unit will revert to the
"System" control.
Units equipped with Scroll
compressors do not have crankcase
heaters.
•
Power supply lines are protected
by recommended fuses and
correctly earthed
Thermostat is correctly wired
and positioned
Unit is checked for refrigerant
charge and leaks
Indoor and outdoor fans rotate
freely and are fixed on shafts
Supply fan rotation speed is set
Access panels and doors are
replaced to prevent air entering
and risks of injury
Checking of the gas heating
section, in accordance with
above procedure
•
•
•
Note: Upon power initialization, the
RTRM performs self-diagnostic
checks to insure that all internal
controls are functional. It also
checks the configuration parameters
against the components connected
to the system.The Liteport LED
located on the RTRM module is
turned "On" within 1 second of
power-up if internal operation is
okay.
•
•
•
52
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Table 48 - ServiceTest Guide for Component Operation on cooling only units
Test modes
There are 2 methods in which the
"Test" mode can be cycled with the
test button:
1. StepTest Mode
This method initiates the different
components of the unit, one at a
time, by temporarily shorting across
the two test terminals for two to
three seconds. For the initial startup
of the unit, this method allows the
technician to cycle a component
"On" and have up to 1 hour to
complete the check.
1
2*
3
Fan On
Economizer
Cool 1
On
On
On
On
On
On
Min
Open
Min
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
On
On
Off
Off
Off
Off
**
4
Cool 2
Min
**
5*
6*
Heat 1
Min
Off
Off
Heat 2
Min
2. AutoTest Mode
* With Optional Accessory
** "Off" If temperature falls below 16° ( 1°C), "On" if temperature rises above 18° ( 1°C).
This method is not recommended
for start-up due to the short timing
between individual component
steps.This method initiates the
different components of the unit,
one at a time, when a jumper is
installed across the test terminals.
The unit will start the first test step
and change to the next step every
30 seconds. At the end of the test
mode, control of the unit will
Note: Steps for optional accessories and modes not present in unit will be skipped.
Table 49 - ServiceTest Guide for Component Operation on Heat Pump Units
automatically revert to the applied
"System" control method.
For unit test steps and test modes,
values to cycle the various
components, refer toTables 48
and 49.
1
2*
3
Fan On
Economizer
Cool 1
On
On
On
On
On
On
Min
Open
Min
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
Off
On
On
Off
Off
Off
Off
Off
On
Off
Off
On
On
Off
Off
Off
Off
**
4
Cool 2
Min
**
5*
6*
Heat 1
Min
Off
Off
Heat 2
Min
* With Optional Accessory
** "Off" If temperature falls below 16° ( 1°C), "On" if temperature rises above 18° ( 1°C).
Note: Steps for optional accessories and modes not present in unit will be skipped.
RT-SVX20A-E4
53
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Figure 32 - Gas valve
Note: Unit to be installed outside
only.
Unit start-up
Verification of gas valve settings -
(Reserved for the qualified gas
technician)
G20 - 7.5mbar
G25 -10.5mbar
Note: Expansion valve must be
adapted to the type of gas used:
3/32"
•
•
•
G 20: 20 mb
G 25: 25 mb
G 31 (Propane): 37 or 50 mb
1
WARNING! Improper gas valve
setting may lead to burner
destruction and people injury.
Note: Unit factory-set for G20.
1 = Screw to set gas valve
Table 50 - Gas type designation per country
Destination countries
Pressure in mbar
Category
II2E+3P
I2E
FR
DE-LU-PL
20/25 37
20
CH-ES-GB-IE-PT-CZ-GR
20 37
25 30
20
II2H3P
II2L3P
I2H
NL
IT-AT-NO-FI-SE-EE-LT-LV
IT
BE
28-30/37
20/25
20
I3+
I2E
I2H
I3P
DK-SK-SI-TR
BE-PL
37
AT-DE-LU-HU-SK
HU
50
25
I3P
I2H
Table 51 - Gas burner data
Burner
G120
G200
G25
0,0
G250
Gas Type
G20
0,0
G25
0,0
G31
0,0
G20
0,0
G31
G20
0,0
G25
G31
0,0
Heating Input (kW)
Heating Output (kW)
Efficiency
0,0
41,9
93%
3,5
0,0
24,6
93%
2,8
25
25,1
93%
2,1
41,3
93%
4,7
41,7
93%
5,5
51,9
52,3
52,6
93%
4,4
93%
3,3
#DIV/0!
5,9
#DIV/0!
3
Gas Flow rate (Nm /h)
6,9
Specific Heating Capacity (MJ/kg)
Heating Output per stage (1st/2nd) (%)
Inlet pressure Min/Nominal/Max (mbar)
Low pressure switch setting (mbar)
Manifold pressure (mbar)
34,02
29,3
46,34
34,02
29,3
46,34
34,02
29,3
46,34
0%-100%
20 / 25 / 30
15
0%-70%-100%
0%-70%-100%
17 / 20 / 25
25 / 37 / 45
20
17 / 20 / 25
20 / 25 / 30
25 / 37 / 45
20
17 / 20 / 25
20 / 25 / 30
25 / 37 / 45
20
15
15
15
10,5
4
15
15
10,5
5
7,5
10,5
24,9
7,5
24,9
7,5
24,9
No of injectors
3
Injector size (Drill / mm)
(33) / 2.87mm
(51) / 1.70mm
(1/8") / 3.175mm
(49) / 1.85mm
(1/8") / 3.175mm
(49) / 1.85mm
Smoke analysis
G20 - 20mbar G25 - 25mbar G31 - 37mbar G20 - 20mbar G25 - 25mbar G31 - 37mbar G20 - 20mbar G25 - 25mbar G31 - 37mbar
Gas / Voltage
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
CO %
0.0012%
59 ppm
8,29%
0.0017%
44 ppm
9,20%
0.0003%
8.7 ppm
8,90%
0.0020%
10 ppm
7,10%
0.0015%
10 ppm
7,10%
0.0011%
11 ppm
8,28%
0.0020%
10 ppm
7,10%
0.0015%
10 ppm
7,10%
0.0011%
11 ppm
8,28%
Nox ppm
CO2 %
Notes:
3
(1) G20 heating output given for 34,02 MJ/m (15°C-1013)
(2) G25 heating output given for 29,30 MJ/m (15°C-1013)
3
(3) G31 heating output given for 46.34 MJ/kg
54
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Starting the unit in cooling mode
Operating pressures
Final installation checklist
•
Are all power cables tightened?
Check torque of power cables
contact !
Is the condenser fan and indoor
blower operating correctly, i.e.
correct rotation and without
undue noise?
Are the compressors operating
correctly and has the system
been checked for leaks?
Have the voltage and running
currents been checked to
determine if they are within
limits?
Have the air discharge grilles
been adjusted to balance the
system?
Has the ductwork been checked
for air leaks and any
condensation?
Has the air temperature rise
been checked?
Has the indoor airflow been
checked and adjusted if
necessary?
Before start-up, ensure that all
power cables are tightened.
After the unit has operated in
cooling mode for a short period of
time, install pressure gauges on the
gauge ports of the discharge and
suction line valves.
Verify that the unit airflow rate is
adjusted according to the
information provided in the "Supply
fan adjustment" section of this
manual.
•
Note:To bypass time delays and
verify the operation of this unit from
the roof, use the "Test procedure"
section in this manual. Check the
suction and discharge pressures.
•
•
To start the unit in cooling mode:
•
Place the zone sensor system
switch in the "COOL" position.
Position the cooling setpoint
approximately 10° below room
temperature and place the fan
switch in the "AUTO" or "ON"
position.
•
Note: Always route refrigerant
hoses through the port hole
provided and ensure that the
compressor access panel is in place.
•
•
•
Turn on unit main power supply.
Cooling shutdown
The condenser fan motor,
compressor and supply fan motor
should operate automatically.
To exit the test mode, disconnect
unit power for 3-5 seconds and
reapply. When running the unit
using the zone sensor as the
control, position the selector switch
to "OFF".
•
•
There will be a delay of up to
5 minutes before the unit starts in
cooling mode.
There may be a delay of up to
3 minutes before compressors shut
down and an additional one minute
before the fan shuts down in this
setting.
•
•
Has the unit been checked for
tubing and sheet metal rattles or
any unusual noises?
Are all covers and panels in
place and properly fastened?
Do not de-energize main power
disconnect except when unit is to
be serviced. Power is required to
keep the compressor crankcase
warm and boil off refrigerant in the
oil (except on units with Scroll
compressors).
RT-SVX20A-E4
55
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
ReliaTel™ is a microelectronic
control feature, which provides
operating functions that are
significantly different from
conventional electro-mechanical
units.The master module is the
ReliaTel™ Refrigeration Module
(RTRM).
Evaporator Fan Operation
Cooling without an
Economizer
When the fan selection switch is set
to the "Auto" position, the RTRM
energizes the (K6) relay coil
approximately one second after
energizing the compressor
contactor coil (CC1) in the cooling
mode. In heating mode, the RTRM
energizes the (K6) relay coil
approximately 45 seconds after gas
ignition. Closing the K6 contacts on
the RTRM energizes the supply fan
relay (F) coil to start the supply fan
motor (IDM).
When the system switch is set to
the "Cool" position and the zone
temperature rises above the cooling
setpoint controlband, the RTRM
energizes the (K9) relay coil located
on the RTRM. When the K9 relay
contacts close, the compressor
contactor (CC1) coil is energized
provided the low pressure control
(LPC1) and high pressure control
(HPC1) are closed. When the CC1
contacts close, compressor (CPR1)
and the outdoor fan motor (ODM)
start to maintain the zone
The RTRM provides compressor
antishort cycle timing functions
through minimum "Off" and "On"
timing to increase reliability,
performance and to maximize unit
efficiency.
Upon power initialization, the RTRM
performs self-diagnostic checks to
insure that all internal controls are
functioning. It checks the
configuration parameters against
the components connected to the
system.
The RTRM de-energizes the fan
relay (F) approximately 60 seconds
after the cooling requirement has
be satisfied to enhance unit
efficiency.
temperature to within 2 F of the
sensor setpoint at the sensed
location.
When the heating cycle is
terminated, the supply fan relay (F)
coil is de-energized approximately
90 seconds after the heating
requirement.
If the first stage of cooling can not
satisfy the cooling requirement, the
RTRM energizes the (K10) relay coil
located on the RTRM. When the
(K10) relay contacts close, the
compressor contactor (CC2) coil is
energized provided the low
pressure control (LPC2) and high
pressure control (HPC2) are closed.
When the CC2 contacts close,
compressor (CPR2) starts to
The LED located on the RTRM
module is turned "On" within one
second after power-up if all internal
operations are okay.
When the fan selection switch is set
to the "On" position, the RTRM
keeps the supply fan relay coil (F)
energized for continuous fan motor
operation.
When the unit is equipped with the
optional clogged filter switch, wired
between terminals J7-3 and J7-4 on
the ReliaTel™ Options Module
(RTOM), the RTRM produces an
analog output if the clogged filter
switch (CFS) closes for two minutes
after a request for fan operation.
When the system is connected to a
remote panel, the "SERVICE" LED
will be turned on when this failure
occurs.
maintain the zone temperature to
within 2 F of the sensor setpoint
at the sensed location.
56
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
The ECA continues to modulate the
economizer damper open/closed to
keep the mixed air temperature that
is calculated by the RTRM.
Low Ambient Operation
Cooling with an
Economizer
The economizer is utilized to control
the zone temperature providing the
outside air conditions are suitable.
During low ambient operation,
outside air temperature below 13ºC,
the RTRM will cycle the compressor
and outdoor fan motor "Off" for
approximately three minutes after
every 10 minutes of accumulated
compressor run time.The supply
fan motor (IDM) will continue to
operate during this evaporator
defrost cycle (EDC) and the
compressor and outdoor fan will
return to normal operation once the
defrost cycle has terminated and
the compressor "Off" time delay has
been satisfied.
If economizing is not possible, the
ECA drives the damper to the
minimum position setpoint when
the supply fan relay (F) is energized
and allows mechanical cooling
operation. When the unit is
equipped with the optional fan
failure switch, wired between
terminals J7-5 and J7-6 on the
RTOM, the RTRM will stop all
cooling functions and produce an
analog output if the fan failure
switch (FFS) does not open within
40 seconds after a request for fan
operation. When the system is
connected to a remote panel, the
"SERVICE" LED will flash when this
failure occurs.
Outside air is drawn into the unit
through modulating dampers. When
cooling is required and economizing
is possible, the RTRM sends the
cooling request to the unit
economizer actuator (ECA) to open
the economizer damper.The RTRM
tries to cool the zone utilizing the
economizer to slightly below the
zone temperature setpoint. If the
mixed air sensor (MAS) senses that
the mixed air temperature is below
53ºF, the damper modulates toward
the closed position. If the zone
temperature continues to rise above
the zone temperature setpoint
controlband and the economizer
damper is full open, the RTRM
energizes the compressor contactor
(CC1). If the zone temperature
continues to rise above the zone
temperature setpoint controlband
and the economizer damper is fully
open, the RTRM energizes the
compressor contactor (CC2).
RT-SVX20A-E4
57
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
3. Comparative Enthalpy - By
utilizing a humidity sensor and a
temperature sensor in both the
return air stream and the
Economizer Set-Up
Ignition Module
Adjusting the minimum position
potentiometer located on the unit
economizer Actuator (ECA) sets the
required amount of ventilation air.
Two Stage (IGN) runs self-check
(including verification that the gas
valve is de-energized). (IGN) checks
the high-limit switches (TC01 &
TC02) for normally closed contacts.
With 115 VAC power supplied to the
ignition module (IGN), the hot
surface ignition probe (IP) is
preheated for approximately
45 seconds.The gas valve (GV) is
energized for approximately
7 seconds for trial for ignition, to
ignite the burner.
outdoor air stream, the unit
control processor (RTRM) will be
able to establish which
conditions are best suited for
maintaining the zone
Two of the three methods for
determining the suitability of the
outside air can be selected utilizing
the enthalpy potentiometer on the
ECA, as described below:
1. AmbientTemperature -
controlling the economizing
cycle by sensing the outside air
dry bulb temperature.TheTable
below lists the selectable dry
bulb values by potentiometer
setting.
2. Reference Enthalpy - controlling
the economizer cycle by sensing
the outdoor air humidity.The
Table below lists the selectable
enthalpy values by
temperature, i.e. indoor
conditions or outdoor conditions.
The potentiometer located on
the ECA is non-functional when
both the temperature and
humidity sensors are installed.
Once the burner is ignited, the hot
surface ignition probe (IP) is de-
energized by the ignition module
(IGN) and functions as the flame
sensing device.
Table 52 - Potentiometer Setting
Dry BuIb
(°C)
23*
21
Enthalpy
(KJ/kg)
63
Potentiometer
Setting
A
If the burner fails to ignite, the
ignition module will make two more
attempts before locking out.The
green LED will indicate a lock out by
two fast flashes. An ignition lockout
can be reset by:
1. Opening for 3 seconds and
closing the main power
disconnect switch
2. By switching the "Mode" switch
on the zone sensor to "OFF" and
then to the desired position
3. Allowing the ignition control
module to reset automatically
after one hour.
B
58
C
D
19
53
17
51
potentiometer setting.
*Factory Setting
If the outside air enthalpy value
is less than the selected value,
the economizer is allowed to
operate.
ReliaTel™ Control Heating
Operation
When the system switch is set to
the "Heat" position and the zone
temperature falls below the heating
setpoint controlband, a heat cycle is
initiated when the RTRM
communicates ignition information
to the Ignition module (IGN).
58
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
Refer to the ignition control module
diagnostics section for the LED
diagnostic definitions.
Final installation checklist
•
Is the condenser fan and indoor
blower operating correctly, i.e.:
correct rotation and without
undue noise?
When the fan selection switch is set
to the "Auto" position, the RTRM
energizes the supply fan relay (F)
coil approximately 30 second after
initiating the heating cycle to start
the supply fan motor (IDM).
•
•
•
Are the compressors operating
correctly and has the system
charge been checked?
Has the gas module been
installed as per the procedure in
this manual?
Have the voltage and running
currents been checked to
determine if they are with in
limits?
The automatic reset high limit
(TCO1), located in the bottom right
corner of the burner compartment,
protects against abnormally high
leaving air temperatures.
•
•
Have the air discharge grilles
been adjusted to balance the
system?
Has the ductwork been checked
for air leaks and any
condensation?
The automatic reset fan fail limit
(TCO2), located in the upper middle
section of the supply fan board,
protects against abnormally high
heat buildup which could occur
because of extended cycling of the
high limit (TCO1) or if the supply
fan motor (IDM) fails to operate.
ShouldTCO2 open, the RTRM will
energize the supply fan relay (F) in
an attempt to start the fan motor.
The RTRM signals that a heat failure
has occurred by flashing the "Heat"
LED on the zone sensor.
•
•
Has the heating air temperature
rise been checked?
Has the indoor airflow been
checked and adjusted if
necessary?
•
•
Has the unit been checked for
tubing and sheet metal rattles
orany unusual noises?
Are all covers and panels in
placeand properly fastened?
There is a Green LED located in the
Ignition Control Module.The table
below lists the diagnostics and the
status of the LED during the various
operating states.
To keep the unit operating safely
and efficiently, the manufacturer
recommends that a qualified service
technician check the entire system
at least once each year, or more
frequently if conditions warrant.
Table 53 - LED status
Diagnostics
Green LED
Off
Red LED
Off
1. Powered but no heat dernand
2. Heat demand without fault
Flash ing
Off
3. No flame detection on ignition - or signal detected
and then lost
Off
Flashing
4. Gas unit incorrectly wired or flame signal detected on
a heat demand
Steady
Off
Flashing
Steady
5. Internal fault
RT-SVX20A-E4
59
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
To keep the unit operating safely
and efficiently, the manufacturer
recommends that a qualified service
technician check the entire system
at least once each year, or more
frequently if conditions warrant it.
End user routine
maintenance
Some of the periodic maintenance
functions for the unit can be
undertaken by the end user.This
includes replacing (disposable) or
cleaning (permanent) air filters,
cleaning unit cabinet, cleaning the
condenser coil, and carrying out a
general unit inspection on a regular
basis.
WARNING! Disconnect the power
supply before removing access
panels to service the unit. Failure to
disconnect power before attempting
any servicing can result in severe
injury or death.
Air filters
It is very important for the central
duct system air filters to be kept
clean.
These should be inspected at least
once a month when the system is in
constant operation (in new
buildings, the filters should be
checked every week for the first four
weeks). If disposable-type filters are
used, they should only be replaced
with ones of the same type and
size.
Table 54 - Refrigerant charge
Refrigerant charge
(kg) (R22/R407C)
Unit model and size
Number of circuits
YSD/YSH 060
YSD/YSH 072
YSD/YSH 090
YSD/YSH 102
YSD/YSH 120
1
1
1
2
2
3.5
3.7
4.5
3.7/2.1
3.5/3.0
Note: Refrigerant charges are given for information only. Check unit nameplate for exact values.
60
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Note: Do not attempt to clean
disposable filters. Permanent filters
can be cleaned by washing with a
mild detergent and water. Ensure
that the filters are thoroughly dry
before reinstalling them in the unit
(or duct system).
Service technician
maintenance
Before the cooling season, your
service technician may examine the
following areas of your unit:
•
•
•
Filters, for cleaning or
replacement
Note: Replace permanent filters
annually if washing fails to clean
them, or they show signs of
deterioration. Be sure to use the
same type and size as were
originally installed.
Motors and drives system
components
Economizer gaskets, for
replacement if necessary
Condenser coils, for cleaning
Safety controls, for mechanical
cleaning
•
•
Condenser coil
•
Electrical components and
wiring, for replacement and
tightening of connections as
necessary
Unfiltered air circulates through the
unit's condenser coil and can cause
the coil's surface to become
clogged with dust, dirt, etc.To clean
the coil, brush the coil surface in the
direction of the fins with a soft
bristled brush.
•
•
Condensate drain, for cleaning
Unit duct connections, to ensure
they are physically sound and
sealed to the unit casing
Unit mounting support, to
ensure that it is sound
The unit, to ensure there is no
obvious deterioration
•
•
Keep all vegetation away from the
condenser coil area.
Hot water coil (option)
Before the heating season, your
service technician may examine the
following areas of your unit:
Stop the unit. Do not disconnect the
main supply to the unit.This will
permit the anti-frost protection to
continue to operate, and avoid
water to freeze-up in the coil.
•
The unit, to ensure that the
condenser coil can receive the
required airflow (that the
condenser fan grille is not
obstructed)
•
•
The control panel wiring, to
verify that all electrical
connections are tight, and that
wire insulation is intact
Clean burner area, verify the gas
heat system operates properly.
RT-SVX20A-E4
61
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
5. If no failures are indicated, use
one of theTEST mode
System Status Checkout Procedure
Troubleshooting
"System Status" is checked by using
one of the following two methods:
The RTRM has the ability to provide
the service personnel with some
unit diagnostics and system status
information. Before turning the
main power disconnect switch "Off",
follow the steps below to check the
ReliaTel™
procedures described in the unit
"Start-Up" section to start the
unit.This procedure will allow
you to check all of the RTRM
outputs, and all of the external
controls (relays, contactors, etc.)
that the RTRM outputs energize,
for each respective mode.
Method 1
If the Zone Sensor Module (ZSM) is
equipped with a remote panel with
LED status indication, you can check
the unit within the space. If the ZSM
does not have LED's, use Method 2.
Refrigeration Module (RTRM). All
diagnostics & system status
information stored in the RTRM will
be lost when the main power is
turned "Off".
Proceed to Step 6.
6. Step the system through all of
the available modes, and verify
operation of all outputs, controls,
and modes. If a problem in
operation is noted in any mode,
you may leave the system in that
mode for up to one hour while
troubleshooting. Refer to the
sequence of operations for each
mode, to assist in verifying
proper operation. Make the
necessary repairs and proceed to
Steps 7 and 8.
7. If no abnormal operating
conditions appear in the test
mode, exit the test mode by
turning the power "Off" at the
main power disconnect switch.
8. Refer to the individual
component test procedures if
other microelectronic
THS/P03 have the remote panel
indication feature.The LED
descriptions are listed below:
1. Verify that the Liteport LED on
the RTRM is burning
LED 1 (System) "On" during normal
operation. "Off" if a system failure
occurs or the LED fails. "Flashing"
indicates test mode.
continuously. If the LED is lit, go
to Step 3.
2. If the LED is not lit, verify that
24 VAC is present between J1-1
and J1-2. If 24 VAC is present,
proceed to Step 3. If 24 VAC is
not present, check the unit main
power supply, check transformer
(TNS1). Proceed to Step 3 if
necessary.
LED 2 (Heat) "On" when the heat
cycle is operating. "Off" when the
heat cycle terminates or the LED
fails. "Flashing" indicates a heating
failure.
LED 3 (Cool) "On" when the cooling
cycle is operating. "Off" when the
cooling cycle terminates or the LED
fails. "Flashing" indicates a cooling
failure.
3. Utilizing "Method 1" or
"Method 2" in the system status
diagnostic section, check the
following: System status,
Heating status, Cooling status. If
a System failure is indicated,
proceed to Step 4. If no failures
are indicated, proceed to Step 5.
LED 4 (Service) "On" indicates a
clogged filter. "Off" during normal
operation. "Flashing" indicates an
supply fan failure.
components are suspect.
4. If a System failure is indicated,
recheck Steps 1 and 2. If the LED
is not lit in Step 1, and 24 VAC is
present in Step 2, the RTRM has
failed. Replace the RTRM.
62
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Below is the complete listing of
failure indication causes:
Cooling Failure
Simultaneous Heat and Cool Failure
1. Emergency Stop is activated
1. Cooling and heating set point
(slide pot) on the zone sensor
has failed. Refer to the "Zone
SensorTest Procedure" section.
2. Zone temperature thermistor
ZTEMP on ZTS failed. Refer to
the "Zone SensorTest Procedure"
section.
3. CC1 or CC2 24 VAC control circuit
has opened, check CC1 & CC2
coils, and any of the controls
below that apply to the unit
(HPC1, HPC2).
4. LPC1 has opened during the
3 minute minimum "on time"
during 4 consecutive compressor
starts, check LPC1 or LPC2 by
testing voltage between the J1-8
& J3-2 terminals on the RTRM
and ground. If 24 VAC is present,
the LPC's has not tripped. If no
voltage is present, LPC's has
tripped.
System failure
Method 2
Check the voltage between
terminals 6 and 9 on J6, it should
read approximately 32 VDC. If no
voltage is present, a system failure
has occurred. Refer to Step 4 in the
previous section for the
The second method for determining
system status is done by checking
voltage readings at the RTRM (J6).
The system indication descriptions
and the approximate voltages are
listed below.
recommended troubleshooting
procedure.
System Failure
Measure the voltage between
terminals J6-9 & J6-6.
Heating Failure
Verify Heat Failure by Ignition
Module (IGN) LED indicator:
Normal Operation = approximately
32 VDC
OFF: No Power or Failure
ON: Normal
System Failure = less than 1 VDC,
approximately 0.75 VDC
Slow Flash: Normal, Heat Call
Fast Flash: Error Code:
Test Mode = voltage alternates
between 32 VDC & 0.75 VDC
1
2
3
4
5
6
Flash: Communication Failure
Flashes: System Lockout
Flashes: Pressure Switch Fail
FlashesTC01 orTC02 Open
Flashes: Flame w/o Gas Valve
Flashes: Flame Rollout Open
Heat Failure
Measure the voltage between
terminals J6-7 & J6-6.
Service Failure
1. If the supply fan proving switch
has closed, the unit will not
operate (when connected to
RTOM), check the fan motor,
belts, and proving switch.
Heat Operating = approximately
32 VDC
Heat Off = less than 1 VDC,
approximately 0.75 VDC
2. Clogged filter switch has closed,
check the filters.
Heating Failure = voltage alternates
between 32 VDC & 0.75 VDC
Cool Failure
Measure the voltage between
terminals J6-8 & J6-6.
Cool Operating = approximately
32 VDC
Cool Off = less than 1 VDC,
approximately 0.75 VDC
Cooling Failure = voltage alternates
between 32 VDC & 0.75 VDC
RT-SVX20A-E4
63
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Service Failure
Resetting Cooling and Ignition
Lockouts
ZoneTemperature Sensor (ZTS)
Service Indicator
Measure the voltage between
terminals J6-10 & J6-6.
Cooling Failures and Ignition
The ZSM SERVICE LED is a generic
indicator that will signal the closing
of a Normally Open switch at any
time, providing the Indoor Motor
(IDM) is operating.This indicator is
usually used to indicate a clogged
filter, or an air side fan failure.
Clogged Filter = Approximately
32 VDC.
Lockouts are reset in an identical
manner. Method 1 explains
resetting the system from the space,
Method 2 explains resetting the
system at the unit.
Normal = Less than 1 VDC,
approximately 0.75 VDC
Fan Failure = voltage alternates
between 32 VDC & 0.75 VDC.
Note: Before resetting Cooling
Failures and Ignition Lockouts,
check the Failure Status Diagnostics
by the methods previously
explained.
The RTRM will ignore the closing of
this Normally Open switch for 2 ( 1)
minutes.This helps prevent
nuisance SERVICE LED indications.
The exception is the LED will flash
40 seconds after the fan is turned
"On" if the Fan Proving Switch is not
made.
To use LED's for quick status
information at the unit, purchase a
ZSM and connect wires with
alligator clamps to terminals 6
through 10.
Diagnostics will be lost when the
power to the unit is disconnected.
Connect each respective terminal
wire (6 through 10) from the Zone
Sensor to the unit J6 terminals 6
through 10.
Method 1
Clogged Filter Switch
To reset the system from the zone,
turn the "Mode" selection switch at
the zone sensor to the "Off"
position.
This LED will remain lit the entire
time that the Normally Open switch
is closed.The LED will be turned off
immediately after resetting the
switch (to the Normally Open
position), or any time that the IDM
is turned "Off".
Note: If the system is equipped
with a programmable zone sensor
THS03, the LED indicators will not
function while the ZSM is
connected.
After approximately 30 seconds,
turn the "Mode" selection switch to
the desired mode, i.e. Heat, Cool or
Auto.
If the switch remains closed, and
the IDM is turned "On", the SERVICE
LED will be turned "On" again after
the 2 ( 1) minute ignore delay.
Method 2
To reset the system at the unit,
cycle the unit power by turning the
disconnect switch "Off" and then
"On".
This LED being turned "On", will
have no other affect on unit
operation. It is an indicator only.
Lockouts can be cleared through the
building management system. Refer
to the building management system
instructions for more information.
Fan Failure Switch
When the "Fan Failure" switch is
wired to the RTOM, the LED will
remain flashing the entire time the
fan proving switch is closed,
indicating a fan failure, and it will
shut the unit operations down.
64
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
Table 55 -Thermistor Resistance /
Temperature Chart
ZoneTemperature Sensor (ZTS)Test
Note:These procedures are not for
programmable or digital models
and are conducted with the Zone
Sensor
Temperature/resistance coefficient is
negative.
Temperature
Resistance
(kOhms)
103
(°C)
-21
-15
-9
Module electrically removed from
the system.
74.65
54.66
46.94
40.4
Test 1
-7
ZoneTemperatureThermistor
(ZTEMP)
-4
-1
34.85
30.18
26.22
22.85
19.96
17.47
This component is tested by
measuring the resistance between
terminals 1 and 2 on the Zone
Temperature Sensor.
2
4
7
10
13
16
18
21
24
27
29
32
35
38
15.33
13.49
11.89
10.5
9.297
8.247
7. 3 3
6.528
5.824
RT-SVX20A-E4
65
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance
ToTest Humidity Sensors
Return Air Humidity Sensor
Outdoor Humidity Sensor
ECA
ECA
RAH/RAE
OAH/OAE
To test this circuit, place a DC milliamp meter in series with either of the leads to the humidity sensor. If the reading
is 0ma, polarity may be reversed. Reverse + & - and retest. If the reading does not correspond to the table below,
check the output voltage from the ECA with the sensor disconnected. It should be approximately 20VDC. If so, and
all connections are intact, replace the sensor. If 20VDC is not present, yet the ECA green LED is on, the ECA module
has failed.Humidity sensor accuracy : +/-10% RH.
Table 56 - Humidity sensor test
RH%
100%
97.7
DCma
20.000
19.636
19.286
18.947
18.621
18.305
18.000
17.705
17.419
17.143
16.875
16.615
16.364
16.119
15.882
15.652
15.429
15.211
15.000
14.795
14.595
14.400
14.211
14.026
13.846
13.671
13.500
13.333
13.171
13.012
12.857
12.706
12.558
RH%D
52.6
51.7
50.8
50.0
49.2
48.4
47.6
Cma
12.414
12.273
12.135
12.000
11.868
11.739
11.613
11.489
11.368
11.250
11.134
11.020
10.909
10.800
10.693
10.588
10.485
10.385
10.286
10.189
10.093
10.000
9.908
RH%
31.2
30.8
30.3
29.9
29.4
29.0
28.6
28.1
27.7
DCma
9.000
8.926
8.852
8.780
8.710
8.640
8.571
8.504
8.438
8.372
8.308
8.244
8.182
8.120
8.060
8.000
7.941
7.833
7.826
7.770
7.714
7.660
7.606
7.552
7.500
7.448
7.397
7.347
7.297
7.248
7.200
95.5
93.4
91.4
89.4
87.5
85.7
83.9
82.1
80.5
78.8
77.3
46.8
46.1
45.3
44.6
43.9
43.2
42.5
41.8
41.2
40.5
39.9
39.3
38.7
38.1
37.5
27.3
26.9
26.5
26.1
25.8
25.4
25.0
24.6
24.3
23.9
23.6
23.2
22.9
22.5
22.2
21.9
21.6
21.2
20.9
20.6
20.3
20.0
75.7
74.3
72.8
71.4
70.1
68.8
67.5
66.2
65.0
63.8
62.7
61.5
60.4
59.4
58.3
57.3
36.9
36.4
35.8
35.3
34.7
34.2
33.7
33.2
32.7
32.2
31.7
9.818
9.730
9.463
9.558
9.474
9.391
56.3
55.4
54.4
53.5
9.310
9.231
9.153
9.076
66
RT-SVX20A-E4
Download from Www.Somanuals.com. All Manuals Search And Download.
Notes
RT-SVX20A-E4
67
Download from Www.Somanuals.com. All Manuals Search And Download.
Literature Order Number
Date
RT-SVX20A-E4
0606
Supersedes
RT-SVX20A-E4_1105
Europe
Literature Stocking Location
Trane has a policy of continuous product and product data improvement and reserves the right to
change design and specifications without notice. Only qualified technicians should perform the
installation and servicing of equipment referred to in this publication.
For more information, contact your local
American Standard Europe BVBA
sales office or e-mail us at [email protected]
Registered Office: 1789 Chaussée de Wavre, 1160 Brussels - Belgium
Download from Www.Somanuals.com. All Manuals Search And Download.
|