Vertical
Self-Contained
Air Conditioning
Air and Water Cooled
5 - 15 Tons
60 Hz
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Contents
I
ntroduction
2
4
Features and Benefits
Model Number Description
General Data
8
9
Selection Procedure
Performance Data
Controls
10
11
36
37
47
51
Electrical Data
Dimensions
Mechanical Specification
PKG-PRC007-EN
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
The Genius line was built to provide not
only ultimate indoor comfort but also
the comfort of knowing that our self-
contained units are reliable as well as
easy to install and maintain.
Micro Controls
Trane was the first to introduce
Microelectronics to commercial unitary
products and has continued to expand
its application to other products.
Genius is the most flexible vertical self-
contained of the market. Suitable to use
in offices, residences or restaurants.
Available as water cooled, integrated air
cooled (or package unit) or with remote
air coded condenser; the modern design
of the Genius line allows you, for the first
time, to select the color of the unit.
The new self-contained with Micro
provides the highest performance,
reliability and best serviceability in the
industry. Trane, a world class
manufacturer can provide this winning
combination for your facility.
The Trane Micro, provided as a factory
installed option, was designed with two
thoughts in mind: reliability and comfort.
The Micro accurately orchestrates all
other system operations whether it is
heating or cooling.
Why Consider Self-Contained
Floor-by-Floor Systems?
Improved Cash Management
Factory installed options and testing:
Reduces field labor and installation risk
and improves system reliability
Requires less sophisticated maintenance
than built-up systems
•
•
Since it is factory mounted it will provide
smooth, trouble-free start-up.
SRVE
The microprocessor provides powerful
operation and diagnostic information.
The micro eliminates the need for a field
installed anti short-cycle timer and time
delay relays, which are an integral part
of the micro controller.
(with discharge plenum)
Tenant Satisfaction
Complete HVAC system on each floor or
area minimizes tenant inconvenience
during routine maintenance.
Tenants can control system after hours
to increase productivity and minimize
expense
•
•
Economical Operation
Floor-by-floor system results in energy
savings since only air conditioners on
floors requiring cooling need to operate
Annual system energy consumption
comparable to central chilled water
system but with significant energy
consumption reduction during partial
occupancy and after-hours
•
•
The IAQ standard, the microelectronics
and the simplified maintenance
capability were all considered a priority
during the design phase of this self-
contained unit.
Low First Cost
Factory packaged controls and piping
reduce field labor, installation time and
cost
•
•
Flexible arrangement to match most
building configurations
Assured Acoustical Performance
Horizontal discharge plenum provides
smooth airflow, reducing static pressure
losses for optimum acoustical
performance.
Scroll compressor design smooths gas
flow for quieter operation
•
•
Lower Installed Cost
Single point power connection
Single point water connection
Factory commissioned and tested
controls
•
•
•
•
Factory installed options
4
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Air Handling Section
3 Filter Types
To meet Commercial and Industrial
needs you can select the filter media for
the application.
In accordance to the ASHRAE Standard
62-89 for Indoor Air Quality, Trane has
developed an exclusive and innovative
design for the drain pan. This design
insures proper drainage, preventing
conditions of water stagnation that could
result in microbial growth.
Nylon Electrostatic Filters
Wire Mesh Permanent Filters
Throwaway Filters
Many other options available as special
(Contact your local Trane
Representative).
All the air handlers feature a factory
installed belt drive and ball bearing
evaporator fan with adjustable shelves.
The unit can be installed indoors; the
condenser air can be ducted to the
outside or installed in a remote location.
Scroll Compressor
offers significant efficiency and reliable
benefits. With fewer moving parts than
comparable reciprocating compressors,
there is less internal friction and
therefore greater efficiency. A smooth
compressor cycle, due to the low torque
variation, creates less stress on the
motor for greater reliability and
efficiency.
For free horizontal application, the
optional discharge plenum with
aluminum grills insures a quiet
operation and maintains the aesthetics
of the units.
In the return section an optional
aluminum grill grants an easy and
elegant installation.
How the Scroll Compressor Works
General
The compressor has two scrolls. The top
scroll is fixed and the bottom scroll
orbits. Each scroll has walls in a spiral
shape that intermesh.
Inlet — First Orbit
As the bottom scroll orbits, two
refrigerant gas pockets are formed and
enclosed.
Compression — Second orbit
The refrigerant gas is compressed as the
volume is reduced closer to the center of
the scroll.
Discharge — Third Orbit
The gas is compressed further and
discharged through a small port in the
center of the fixed scroll.
PKG-PRC007-EN
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Features and
Benefits
Genius is three times ingenious in many
ways.
Integrated Self-Contained Systems:
Profitable, Simple
Integrated Comfort™ System (ICS)
Trane’s Integrated Comfort™ system
improves job profit and increases job
control by combining Trane self-
3 Control Options
Standard Thermostat
Available in 3 models
All units are furnished with a standard
thermostat that can be installed
remotely or directly on the equipment.
SRVE - Self-contained unit with
INTEGRATED air cooled condenser
contained units and a Tracker® building
management system. This integrated
system provides total building comfort
and control. The primary motivation for
building owners/managers in making the
purchasing decision of an HVAC controls
system is no longer just saving energy; it
is having the ability to automate their
facilities and the convenience of interface
to control systems.
SIVE - Self contained unit with REMOTE
air-cooled condenser
SAVE - Self-contained WATER-cooled
unit with shell and tube condenser
Available 3 Colors
The attractive highly functional design of
the Genius line offers the customers the
selection of three equipment colors to
blend with any architectural style:
Gray
Black
Red
Programmable Thermostat (PT)
PT programming is very simple! PT has
a display that shows the hour, the day of
the week, the selected program and the
ambient temperature. PT can be
3 Motor Sizes
The units have the capability to meet any
static pressure application up to 1.5”
with their 3 options:
programmed for up to four setpoints for
each day of the week. Using the button
“timed-override” the customer can
prolong the machine operation beyond
the programmed schedule, according to
customer needs.
- Low Static Motor Option
- Medium Static Option
- High Static Option
As an additional benefit the Micro
allows the Genius to be integrated to
the Tracker. This ability allows the
multiple units to be controlled and
diagnosed from a central location, from
across town or even across the country.
Microcontrol
Just imagine the HVAC installed in your
facility capable of being scheduled,
monitored and let you know when it is
having problems.
This state of the art control offers a
complete family of sensors and wall
mounted devices to compliment the
capabilities of the Trane Micro.
3 Filter Options
Three filter options exist which may be
installed in Genius units.
1. Permanent washable filters of
electrostatic fabric (standard).
2. Disposable 2” filters.
3. The combination of the two placed in
series.
6
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Features
Summary
Quality and Reliability
Galvanized steel casing
Synthetic enamel paint
Innovative Drain Pan
Scroll Compressors
Wide range of Models available:
•
•
•
•
SRVE: Self Contained with Integral Air Cooled Condenser
SIVE: Self Contained with Remote Air Condenser
SAVE: Self Contained with Water cooled
Nominal Capacity: From 5 to 15 Tons
Flexibility
Air or Water Cooled
Free discharge plenum or ducted
discharge
Voltages available:
220/3/60, 440/3/60, 380/3/60 and 380/50/3
•
•
•
You can reach up to 1.5” esp with our Double Inlet Forward curved
Supply fan. It also has variable V-belt drives.
The case has been insulated with BIDIM insulation.
Other options:
Controls
Aluminum decorative grill
Plenum discharge box for free air discharge
Service Valves
Thermostat unit mounted or remote
Optional Programmable thermostat
Optional Microprocessor
•
•
•
•
Sight Glass
Solenoid Valve
ICS compatible, Tracker is your ideal
partner for small buildings applications.
Filters
Throwaway
Washable - Nylon type
Washable - Aluminum Mesh
•
•
•
PKG-PRC007-EN
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Model
Number
Description
8
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
General
Data
Table GD-1 — Genius – General Data
SAVE Model
Nominal TR Capacity
Length (mm)
Depth (mm)
Height (mm)
Height w/ Plenum Box (mm)
Net Weight (kg)
SRVE Model
Nominal TR Capacity
Length (mm)
Depth (mm)
050 T
5
075 T
7.5
1190
600
2000
2295
288
075 T
7.5
1190
720
2000
2295
310
100 2T
10
1500
600
2000
2295
376
100 2T
10
1500
830
2000
2295
416
125 2T
12.5
1700
600
2000
2295
440
125 2T
12.5
1700
1000
2000
2295
459
150 2T
15
1700
600
2000
2295
461
150 2T
15
1700
1000
2000
2295
490
960
600
2000
2295
247
050 T
5
960
720
2000
2295
268
050 T
5
Height (mm)
Height w/ Plenum Box (mm)
Net Weight (kg)
SIVE Model
075 T
7.5
100 2T
10
125 2T
12.5
150 2T
15
Nominal TR Capacity
Evaporator Units
Quantity/Model
1/SIVE050
960
1/SIVE075
1190
1/SIVE100
1500
1/SIVE125
1700
1/SIVE 150
1700
Length (mm)
Depth (mm)
Height (mm)
Height w/ Plenum Box (mm)
Net Weight (kg)
600
600
2000
2295
225
600
2000
2295
235
600
2000
2295
347
600
2000
2295
392
2000
2295
190
Condensing Units
Quantity/Model
Length (mm)
1/CRCB050
987
1/CRCB075
1241
1/CRCB100
1341
1/CRCB125
1646
1/CRCB150
1646
Depth (mm)
Height (mm)
631
890
631
890
631
941
714
1018
714
1247
Net Weight (kg)
93
124
139
180
212
Compressor
Quantity TR
1 / 5
1 / 7.5
2 / 5
5 + 7.5
2 / 7.5
Evaporator Coil
Rows
3
3
3
3
4
Finned Height (mm)
Finned Length (mm)
Finned Clearance (m)
FPF ( Fins Per Foot)
Evaporator Fan
536
711
0.38
132
508
965
0.49
132
612
1143
0.70
132
663
1328
0.88
132
714
1321
0.94
132
Quantity
1
270 x 270
0.5
1.0
1.0
1.5
3060
3825
1
321 x 321
0.5
1.5
2.0
3.0
4590
5740
2
270 x 270
0.5
1.5
2.0
3.0
6120
7650
2
321 x 321
0.5
2.0
3.0
4.0
7650
9560
2
321 x 321
1.0
3.0
4.0
5.0
9180
11475
Diameter x Length
Plenum Box Option (CV)
Standard Motor Option (CV)
Motor Option 1 (CV)
Motor Option 2 (CV)
Minimum Air Flow (m3/h)
Maximum Air Flow (m3/h)
Condenser Fan
(SRVE and CRCB)
Quantity
Diameter x Length
Motor (CV)
1
321 x 321
1.0
1
321 x 321
3.0
2
270 x 270
3.0
2
2
321 x 321
4.0
321 x 321
5.0
Air Flow (CFM)
5450
8315
9935
13930
17320
Water Condenser
(SAVE)
Minimum Water Flow GPM
Maximum Water Flow GPM
Maximum Pressure Drop (ca feet)
Condenser Coil
1.4
4.0
1.9
2.0
6.0
4.6
2.7
8.0
1.8
3.4
9.9
3.0
4.1
11.9
3.1
(SRVE, CRCB)
Rows
4
4
4
4
4
Finned Height (mm)
Finned Length (mm)
FPF (Fins per Foot)
711
762
168
813
1016
168
864
1143
168
940
1473
168
1168
1473
168
PKG-PRC007-EN
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Selection
Procedure
The selection of a Genius self-contained
unit can be accomplished in three easy
steps.
Since the difference between entering
and leaving water is 7°F multiply the
capacities and water flow by correction
factors on Capacity Correction Factor
Table.
Solution
1. Select Unit
Initially Select a 10-Ton Unit
1
LOAD: Determine the load requirements
for heating and cooling (include outside
air) using Trane’s load estimate forms,
TRACE® Easy/600 or any standard
method.
From Table PD-13
Cooling capacity multiplier
Sensible capacity multiplier
Water flow multiplier
1.01
1.05
1.39
80/67 EAT
95 F AMB = 118.7 MBh Total Gross
4200 CFM
86.6 MBh Sensible
60.6 x 1.01 = 61.21 MBh
43.5 x 1.01 = 43.94 MBh
14.5 x 1.39 = 20.16 GPM
2. Fan speed and BHP determination
2
UNIT TYPE: Self-contained air
conditioners are available in either
water-cooled or remote air-cooled
models to match individual needs.
3
Total Static Pressure
Evaporator
0.380 esp
Refer to Table PD-1 to determine
approximate brake horsepower and fan
rpm:
From Table PD-3
SELECT THE UNIT: The conditions under
which the unit must operate and the
design load will give the final selection.
1035 rpm and 0.66 bhp.
Evaporator
10-ton unit
4200 CFM = 1107 RPM
0.5 ESP = 1.63 BHP
Determine net capacities by subtracting
fan motor heat from gross capacities:
2.8 x 0.66 bph = 1.85 MBh
Net total capacity =
SELECTION EXAMPLE
Design Conditions
Water-cooled unit
Entering air temperature — 80/67 F
Total gross capacity required —
55,000 BTUH
Note: If values fall between cfm’s or
esp’s it is proper to interpolate between
values. Do not extrapolate beyond
values in catalog. Contact Trane
61.21 - 1.85 = 59.36 MBh
Net sensible capacity =
43.94 - 1.85 = 42.09 MBh
marketing department for assistance.
Supply air temperature DB
Entering water temperature — 85 F
Leaving water temperature — 92 F
Airflow — 1,950 CFM at 0.5” duct static
pressure.
Fan Motor Heat Equation
Qs = 1.085 x CFM x (Tr-TS)
42,090 = 1.085 x 1950 x (80-TS)
Fan motor heat = 2.8 x 1.63 = 4.56 MBh
Net total capacity = 118.7 - 4.50
= 114.14 MBh
Net sensible capacity = 86.6 - 4.56
= 82.04 MBh
TS = 80 -
42,090
(1.085) (1950)
Voltage
TS = 60.1°F
Unit Selection
Tentatively select a 5-ton unit — Model
SAVE050. Refer to Table PD-6 to obtain
gross total and sensible unit capabilities,
gpm, and leaving water temperature at
nominal conditions:
Air-Cooled
Design Conditions
— 80 F/67 F DB/WB return air
temperature
— 95 F Ambient
— 109300 BTUH Total Net
— 76500 BTUH Sensible Net
— 0.380 External Static Pressure
(evaporator fan)
— 4200 CFM
— 0.25 External static pressure
(condenser fan)
Conclusion:
Required — 109300 BTUH Total Net
76500 BTUH Total
Sensible Net
Provided — 114140 BTUH Total Net
82040 BTUH Total Net
Total MBh — 60.6
Sensible MBh — 43.5
GPM — 14.5
The 10-ton unit is the proper choice for
this application.
LWT — 95
The SAVE-050 meets the total and
sensible design requirements.
Required
1. Select unit
2. Fan speed and BHP for
a) Evaporator fan
b) Condenser fan
3. Supply air temperature DB
10
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Fan
Data
Performance
Data
Three transmission options exist for the
evaporator fan motor: Std. option,
option 1, option 2. In addition, there is an
option for those cases in which the unit
is operated with a plenum box. The
motors for each transmission option can
be found in the general facts tables.
Table PD-1 — Fan Performance SRVE/SIVE/SAVE 5 Tons
External static pressure with permanent air filter inches of water (Pa)
.08
(19.9)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
Model
5 TR
Airflow
(m3/h)
3060
3188
3315
3443
3570
3698
3825
Option
STD
CFM
1802
1877
1952
2028
2102
2178
2253
RPM
815
843
869
897
925
952
981
BHP
0.40
0.45
0.50
0.56
0.62
0.68
0.75
RPM
852
879
904
931
957
984
BHP
0.43
0.48
0.53
0.59
0.65
0.71
RPM
888
914
938
964
989
BHP
0.45
0.51
0.56
0.62
0.68
RPM
923
948
971
996
BHP
0.48
0.53
0.59
0.65
RPM
957
981
BHP
0.51
0.57
0.62
RPM
990
BHP
0.54
MT 1.0 CV
MS: 78,5 A 106,5
FS: 184 (8")
B: 1X A36
1003
External static pressure with permanent air filter inches of water (Pa)
.16
(39.8)
CFM (m3/h) RPM BHP RPM BHP
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
RPM BHP
.63
(156.9)
.79
(196.7)
RPM
1117
1136
1155
1175
1195
1215
1237
.94
(234.1)
1.10
(273.9)
RPM BHP
1234 0.83
1251 0.89
Model
Option 5 TR
Airflow
RPM BHP RPM BHP
RPM BHP
1055 0.61
1076 0.67
1096 0.73
1117 0.79
1139 0.85
1160 0.92
1183 0.99
BHP
0.68
0.74
0.80
0.86
0.93
1.00
1.07
RPM BHP
1176 0.75
1195 0.81
1212 0.88
1230 0.94
1249 1.01
1802
1877
1952
2028
2102
2178
2253
3060
3188
3315
3443
3570
3698
3825
MT 1.0 CV
1013 0.60
1035 0.66
1058 0.72
1081 0.78
1104 0.85
1128 0.92
MS: 78,5 A 106,5
FS: 133 (6")
OP1
1027 0.68
1020 0.71 1051 0.75
1045 0.78 1075 0.81
1071 0.85 1100 0.88
B: 1X A32
1015 0.74
1012 0.78 1042 0.81
External static pressure with permanent air filter inches of water (Pa)
.94
(234.1)
1.10
(273.9)
1.26
(313.7)
1.42
(353.6)
RPM
1343
1358
1372
1387
1403
1420
1437
1.57
(390.9)
Model
5 TR
Airflow
(m3/h)
3060
3188
3315
3443
3570
3698
3825
Option
OP2
CFM
RPM
BHP
RPM
BHP
RPM
1289
1305
1320
1337
1353
1371
1389
BHP
0.91
0.97
1.03
1.10
1.16
1.23
1.30
BHP
RPM
BHP
1.05
1.12
1.19
1.25
1.32
1.39
1802
1877
1952
2028
2102
2178
2253
0.98
1.05
1.11
1.18
1.24
1.31
1.39
1395
1409
1422
1437
1452
1467
MT 1.5 CV
MS: 78.5 A 106.5
BS: 108 (5")
B: 1X A31
1267
1284
1302
1320
1340
0.95
1.02
1.09
1.15
1.22
1269
1289
1.08
1.14
MT = Motor (CV).
MS = Motor Sheave, variable pitch (mm).
FS = Fan Sheave (mm).
B
= Belt.
PKG-PRC007-EN
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Fan
Data
Table PD-2 — Fan Performance SRVE/SIVE/SAVE 7.5 Tons
External static pressure with permanent air filter inches of water (Pa)
.08
(19.9)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
Model
7.5 TR
Airflow
(m3/h)
4590
4780
4970
5163
5355
5548
5740
Option
STD
CFM
2703
2815
2927
3041
3154
3267
3380
RPM
688
712
735
760
784
808
834
BHP
0.64
0.72
0.81
0.90
1.01
1.12
1.24
RPM
720
743
765
788
811
834
859
BHP
0.68
0.76
0.85
0.95
1.06
1.17
1.29
RPM
751
773
794
816
838
861
BHP
0.72
0.81
0.90
1.00
1.10
1.22
RPM
781
802
822
844
865
BHP
0.77
0.86
0.95
1.05
1.15
RPM
BHP
0.82
0.91
0.99
1.10
RPM
840
859
877
BHP
811
831
850
871
0.87
0.96
1.05
MT 1.5 CV
MS: 78,5 A 106,5
BS: 209 (9")
B: 1X A35
External static pressure with permanent air filter inches of water (Pa)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
.63
(156.9)
.79
(196.7)
.94
(234.1)
1.10
(273.9)
1.26
(313.7)
BHP RPM
1.42
(353.6)
Model
Option 7.5 TR
Airflow
CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM
BHP
1.51
2703
2815
2927
3041
3154
3267
3380
4590
4780
4970
5163
5355
5548
5740
896 0.97
913 1.06
931 1.16
950 1.08 1002 1.19 1052 1.30 1100
966 1.17 1017 1.28 1066 1.39 1113
982 1.26 1031 1.37 1079 1.49 1126
999 1.36 1047 1.47 1094 1.59 1140
1.41 1147
1.50
1.60
1.72
1.83
MT 2.0 CV
MS: 78,5 A 106,5
BS: 159 (7")
OP1
897 1.15 949 1.25
B: 1X A32
891 1.21
886 1.27 912 1.32
910 1.39 935 1.44
917 1.26 968 1.36 1016 1.47 1064 1.59 1110 1.71 1154
937 1.37 986 1.47 1034 1.58 1080 1.70 1125 1.83
959 1.49 1007 1.59 1053 1.70 1098 1.83 1142 1.96
885 1.34
External static pressure with permanent air filter inches of water (Pa)
1.26
(313.7)
1.42
(353.6)
1.57
(390.9)
Model
7.5 TR
Airflow
Option
OP2
CFM
(m3/h)
4590
4780
4970
5163
5355
5548
5740
RPM
BHP
RPM
BHP
RPM
1193
1204
1215
1227
1240
1253
1268
BHP
2703
2815
2927
3041
3154
3267
3380
1.60
1.75
1.88
2.03
2.17
2.34
2.50
MT 3.0 CV
MS: 80 A 110
BS: 118 (5")
B: 1X B27
1159
1171
1184
1198
1211
1227
1.61
1.74
1.86
2.01
2.16
2.32
1169
1185
1.97
2.15
MT = Motor (CV).
MS = Motor Sheave, variable pitch (mm).
FS = Fan Sheave (mm).
B
= Belt.
12
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Fan
Data
Table PD-3 — Fan Performance SRVE/SIVE/SAVE 10 Tons
External static pressure with permanent air filter inches of water (Pa)
.08
(19.9)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
Model
10 TR
Airflow
(m3/h)
6120
6375
6630
6885
7140
7395
7650
Option
STD
CFM
3604
3754
3905
4055
4205
4355
4505
RPM
839
866
895
924
954
984
BHP
0.84
0.94
1.04
1.16
1.29
1.42
RPM
875
902
929
957
986
BHP
0.89
0.99
1.10
1.22
1.35
RPM
911
936
963
989
BHP
0.94
1.05
1.16
1.28
RPM
945
969
995
BHP
1.00
1.11
1.23
RPM
979
1002
BHP
1.07
1.17
MT 1.5 CV
MS: 78,5 A 106,5
BS: 184 (8")
B: 1X A35
External static pressure with permanent air filter inches of water (Pa)
.08
(19.9)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
.63
(156.9)
.79
(196.7)
.94
(234.1)
1.10
(273.9)
1.26
(313.7)
Model
Option 10 TR
Airflow
CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3604 6120
3754 6375
1012 1.13 1075 1.26 1136 1.41 1195 1.55 1252 1.71 1307 1.87
1034 1.24 7096 1.38 1156 1.53 1213 1.68 1269 1.83
MT 2.0 CV
MS: 78,5 A 106,5 3905 6630
1027 1.29 1058 1.36 1118 1.51 1176 1.66 1232 1.81
OP1
BS: 133 (6")
B: 1X A31
4055 6885
4205 7140
4355 7395
1021 1.35 1051 1.42 1082 1.49 1140 1.64 1197 1.79
1017 1.42 1048 1.49 1078 1.56 1107 1.63 1164 1.78
1015 1.49 1045 1.55 1075 1.63 1104 1.70 1132 1.77
4505 7650 1013 1.56 1043 1.63 1072 1.70 1101 1.77 1130 1.84 1157 1.92
External static pressure with permanent air filter inches of water (Pa)
.63
(156.9)
.79
(96.7)
.94
(234.1)
1.10
(273.9)
1.26
(313.7)
1.42
(353.6)
RPM
1360
1375
1391
1407
1425
1444
1.57
(390.9)
RPM
1412
1425
1441
1456
1473
Model
10 TR
Airflow
CFM (m3/h) RPM
Option
OP2
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
BHP
2.01
2.14
2.28
2.42
2.56
2.71
BHP
2.16
2.29
2.43
2.57
2.71
3604
3754
3905
4055
4205
4355
4505
6120
6375
6630
6885
7140
7395
7650
MT 3.0 CV
MS: 80 A 110
BS: 118 (5")
B: 1X B31
1322
1340
1357
1376
1395
1414
1.98
2.12
2.26
2.40
2.54
2.69
1287
1305
1325
1346
1366
1.97
2.10
2.24
2.39
2.53
1252
1273
1295
1316
1.94
2.08
2.23
2.37
1220
1242
1265
1.93
2.07
2.22
1188
1212
1.92
2.06
MT = Motor (CV).
MS = Motor Sheave, variable pitch (mm).
FS = Fan Sheave (mm).
B
= Belt.
PKG-PRC007-EN
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Fan
Data
Table PD-4 — Fan Performance SRVE/SIVE/SAVE 12.5 Tons
External static pressure with permanent air filter inches of water (Pa)
.08
(19.9)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
.63
(156.9)
Model
Airflow
Option 12.5 TR
CFM (m3/h) RPM
BHP
RPM
BHP
0.89
1.01
1.12
1.24
1.37
1.50
1.65
RPM
BHP
0.98
1.09
1.20
1.32
1.46
1.60
1.75
RPM
735
751
768
785
804
821
841
BHP
RPM
768
783
799
816
833
850
BHP
1.18
1.27
1.39
1.51
1.65
1.79
RPM
BHP
1.29
1.37
1.49
1.61
1.75
RPM
8.61
BHP
1.50
4505
4694
4882
5069
5256
5445
5630
7650
7970
8290
8608
8925
9243
9560
630
649
670
690
711
731
753
0.81
0.93
1.04
1.15
1.28
1.41
1.56
666
684
703
723
743
762
783
701
718
736
754
774
792
812
1.08
1.18
1.29
1.41
1.55
1.69
1.85
800
814
830
845
862
MT 2.0 CV
MS: 78,5 A 106,5
BS: 184 (8")
STD
B: 1X A33
External static pressure with permanent air filter inches of water (Pa)
.39
(97.1)
.50
(124.5)
.63
(156.9)
.79
(195.7)
.94
(234.1)
1.10
(273.9)
Model
12.5 TR
Airflow
(m3/h)
7650
7970
8290
8608
8925
9243
9560
Option
OP1
CFM
RPM
868
BHP
1.95
RPM
BHP
RPM
BHP
RPM
BHP
1.62
1.79
1.91
2.04
2.18
2.33
2.49
RPM
975
985
BHP
RPM
BHP
2.06
2.23
2.35
2.48
4505
4694
4882
5069
5256
5445
5630
919
931
944
957
971
985
1000
1.88
2.00
2.13
2.26
2.40
2.55
1029
1038
1049
1060
MT 3.0 CV
MS: 79 A 105
FS: 169 (7")
B: 1X B32
874
888
902
918
932
949
1.57
1.69
1.82
1.97
2.11
2.27
997
1010
1023
1035
878
896
1.90
2.06
External static pressure with permanent air filter inches of water (Pa)
.94
(234.1)
1.10
(273.9)
1.26
(313.7)
1.42
(353.6)
RPM
1131
1139
1148
1156
1167
1177
1189
1.57
(390.9)
RPM
1179
1187
1195
1203
1213
Model
12.5 TR
Airflow
Option
OP2
CFM
4505
4694
4882
5069
5256
5445
5630
(m3/h)
7650
7970
8290
8608
8925
9243
9560
RPM
1050
BHP
RPM
BHP
RPM
1081
1089
1099
1109
1121
1131
1144
BHP
2.26
2.44
2.56
2.69
2.84
2.98
3.15
BHP
2.52
2.65
2.77
2.89
2.95
3.10
3.30
BHP
2.73
2.81
2.92
3.13
3.20
MT 4.0 CV
MS: 79 A 105
FS: 143 (6")
B: 1X B29
1073
1084
1098
2.62
2.77
2.93
2.71
MT = Motor (CV).
MS = Motor Sheave, variable pitch (mm).
FS = Fan Sheave (mm).
B
= Belt.
14
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Fan
Data
Table PD-5 — Fan Performance SRVE/SIVE/SAVE 15 Tons
External static pressure with permanent air filter inches of water (Pa)
.08
(19.9)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
Model
15 TR
Airflow
(m3/h)
9180
9563
9945
10323
10700
11088
11475
Option
STD
CFM
5406
5632
5857
6080
6302
6530
6758
RPM
664
686
707
728
749
771
793
BHP
1.22
1.36
1.52
1.69
1.88
2.08
2.30
RPM
696
717
737
757
777
798
BHP
1.30
1.45
1.61
1.79
1.98
2.19
RPM
728
747
766
785
804
BHP
1.38
1.54
1.71
1.89
2.08
RPM
759
777
795
813
BHP
1.48
1.64
1.81
1.99
RPM
789
806
BHP
1.57
1.73
RPM
818
BHP
1.66
MT 3.0 CV
MS: 79 A 105
FS: 219 (9")
B: 1X B35
External static pressure with permanent air filter inches of water (Pa)
.16
(39.8)
.24
(59.8)
.31
(77.2)
.39
(97.1)
.50
(124.5)
.63
(156.9)
.79
(196.7)
.94
(234.1)
1.10
(273.9)
1.26
(313.7)
Model
Option 7.5 TR
Airflow
CFM (m3/h) RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM
BHP RPM
2.52 1082
2.69
2.87
3.06
BHP
2.74
5406
5632
5857
6080
6302
6530
6758
9180
9563
9945
10323
10700
11088
875 1.87
890 2.03
906 2.21
921 2.40
936 2.59
930 2.08 983 2.30 1033
944 2.25 995 2.47 1045
958 2.43 1008 2.65 1057
972 2.61 1021 2.83 1069
986 2.80 1034 3.02
MT 4.0 CV
835 1.83
824 1.91 852 2.01
841 2.09 868 2.19
858 2.28 885 2.39
877 2.50 903 2.60
896 2.72 921 2.85
MS: 79 A 105
FS: 169 (7")
B: 1X B31
OP1
832 2.19
825 2.29 851 2.40
845 2.52 871 2.62
953 2.81 1002 3.02 1049 3.24
970 3.03 1017 3.23 1064 3.46
11475 819 2.41
External static pressure with permanent air filter inches of water (Pa)
1.10
(273.9)
1.26
(313.7)
1.42
(353.6)
1.57
(390.9)
Model
15 TR
Airflow
(m3/h)
9180
9563
9945
10323
10700
11088
11475
Option
OP2
CFM
RPM
BHP
RPM
BHP
RPM
BHP
2.95
3.13
3.33
3.53
3.77
4.00
4.20
RPM
BHP
5406
5632
5857
6080
6302
6530
6758
1130
1140
1150
1160
1171
1183
1195
1176
1185
1194
1204
1214
1225
1236
3.17
3.37
3.58
3.80
4.02
4.27
4.45
MT 5.0 CV
MS: 79 A 105
FS: 143 (6")
B: 1X B29
1093
1104
1115
1126
1139
1152
2.91
3.10
3.29
3.50
3.74
4.00
1081
1095
1108
3.26
3.48
3.71
MT = Motor (CV).
MS = Motor Sheave, variable pitch (mm).
FS = Fan Sheave (mm).
B
= Belt.
PKG-PRC007-EN
15
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-6 — Gross Cooling Capacities SAVE-050
English
ENT Water Temp (°F)
75
85
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
61
67
73
SHC GPM
CFM
1800
TGC SHC GPM TGC
SHC GPM TGC
SHC GPM
TGC
53.5
53.7
55.4
58.0
54.1
54.6
56.7
59.4
54.7
55.4
57.9
60.7
55.2
56.2
58.9
61.8
SHC GPM
TGC
59.9
59.9
59.8
59.9
60.7
60.6
60.6
60.8
61.3
61.3
61.2
61.6
61.9
61.8
61.8
62.3
SHC
34.4
42.6
49.4
56.0
35.3
43.5
51.1
58.1
36.1
45.3
52.8
60.0
37.0
46.5
54.5
61.7
GPM TGC
55.0
55.2
56.7
59.2
55.7
56.0
58.0
60.7
56.3
56.9
59.1
61.9
56.9
57.7
60.3
63.1
45.2
53.1
57.8
60.4
46.6
54.9
59.1
61.8
48.1
56.6
60.3
63.1
49.5
58.1
61.4
64.4
12.8
12.8
13.2
14.1
13.2
13.2
13.7
14.1
13.2
13.7
14.1
14.5
13.7
13.7
14.1
14.5
61.6
61.5
61.5
61.5
62.3
62.3
62.2
63.4
62.9
62.9
62.8
63.1
63.5
63.5
63.4
64.0
35.2
43.4
50.1
56.7
36.0
44.7
51.9
58.8
36.9
46.0
53.6
60.8
37.6
47.3
55.2
62.6
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
15.0
15.0
15.0
15.0
68.6
68.6
68.5
68.5
69.4
69.3
69.3
69.2
70.1
70.0
70.0
69.9
70.8
70.7
70.7
70.6
24.9
33.1
39.8
46.5
25.2
33.8
41.0
48.1
25.4
34.5
42.1
49.7
25.6
35.3
43.2
51.1
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
16.3
16.3
16.3
16.3
16.3
16.3
16.3
16.3
44.4
52.3
56.5
59.1
45.9
54.1
57.8
60.6
47.4
55.7
59.0
61.8
48.7
57.0
60.1
63.0
12.8
12.8
13.2
14.1
13.2
13.2
13.7
14.1
13.2
13.2
14.1
14.5
13.2
13.7
14.1
14.5
14.5
14.5
14.1
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
15.0
67.0
66.8
66.8
66.7
67.7
67.7
67.6
67.6
68.4
68.3
68.3
68.2
69.0
68.9
68.9
68.8
24.4
32.4
39.2
45.9
24.6
33.2
40.3
47.5
24.8
33.9
41.5
49.0
25.0
34.5
42.5
50.5
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
16.3
15.9
15.9
15.9
16.3
16.3
16.3
16.3
1950
2100
2250
Table PD-6 — Gross Cooling Capacities SAVE-050 (Cont.)
ENT Water Temp (°F)
95
Entering Wet Bulb Temperature (°F)
67
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
73
CFM
1800
TGC SHC GPM TGC
SHC GPM TGC
SHC GPM
51.9
52.2
54.2
56.8
52.5
53.0
55.4
58.1
53.1
54.0
56.5
59.3
53.7
54.8
57.6
60.4
43.7
51.5
55.2
57.9
45.2
53.1
56.5
59.2
46.6
54.6
57.6
60.5
48.0
55.9
58.7
61.5
12.8
12.8
13.7
14.1
13.2
13.2
13.7
14.1
13.2
13.7
14.1
14.5
13.2
13.7
14.1
15.0
58.3
58.2
58.2
58.3
59.0
58.9
58.9
59.1
59.6
59.5
59.5
59.9
60.2
60.1
60.1
60.8
33.7
41.9
48.6
55.2
34.5
43.3
50.4
57.2
35.4
44.5
52.2
59.1
36.2
45.8
53.8
60.8
14.1
14.1
14.1
14.1
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
14.5
15.0
65.2
65.1
65.1
65.0
65.9
65.8
65.8
65.7
66.5
66.5
66.4
66.4
67.2
67.1
67.1
67.0
23.6
31.8
38.5
45.3
23.8
32.6
39.7
46.8
24.2
33.3
40.8
48.3
24.4
33.9
41.9
49.8
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
15.9
16.3
16.3
16.3
16.3
1950
2100
2250
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
Capacity Correction Factor Table
Delta T
Water
(°F)
4.5
Total Cap.
MBh
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
MBh
1.01
GPM
2.21
1.39
1.00
0.79
0.66
0.56
7.2
1.01
1.00
1.00
1.00
10.0
12.6
15.3
18.0
0.99
16
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Water Cooled
60 Hz
Performance
Data
Table PD-6 — Gross Cooling Capacities SAVE-050
Metric
ENT Water Temp (°C)
24.0
29.5
Entering Wet Bulb Temperature (°C)
Ent.
DB
m3/h (°C)
24
16.0
19.5
23.0
16.0
19.5
23.0
TGC SHC
l/s
TGC
18.0
18.0
18.0
18.0
18.3
18.3
18.2
18.6
18.4
18.4
18.4
18.5
18.6
18.6
18.6
18.7
SHC
10.3
12.7
14.7
16.6
10.6
13.1
15.2
17.2
10.8
13.5
15.7
17.8
11.0
13.8
16.2
18.3
l/s
TGC
20.1
20.1
20.1
20.1
20.3
20.3
20.3
20.3
20.6
20.5
20.5
20.5
20.7
20.7
20.7
20.7
SHC
7.3
9.7
11.7
13.6
7.4
l/s
TGC
15.7
15.7
16.2
17.0
15.8
16.0
16.6
17.4
16.0
16.2
17.0
17.8
16.2
16.5
17.3
18.1
SHC
13.0
15.3
16.6
17.3
13.4
15.8
16.9
17.8
13.9
16.3
17.3
18.1
14.3
16.7
17.6
18.5
l/s
TGC
17.6
17.6
17.5
17.6
17.8
17.7
17.7
17.8
18.0
18.0
17.9
18.0
18.1
18.1
18.1
18.3
SHC
10.1
12.5
14.5
16.4
10.3
12.8
15.0
17.0
10.6
13.3
15.5
17.6
10.8
13.6
16.0
18.1
l/s
TGC
19.6
19.6
19.6
19.6
19.8
19.8
19.8
19.8
20.0
20.0
20.0
20.0
20.2
20.2
20.2
20.2
SHC
7.1
9.5
11.5
13.4
7.2
l/s
16.1
16.2
16.6
17.4
16.3
16.4
17.0
17.8
16.5
16.7
17.3
18.1
16.7
16.9
17.7
18.5
13.2
15.6
16.9
17.7
13.7
16.1
17.3
18.1
14.1
16.6
17.7
18.5
14.5
17.0
18.0
18.9
0.81
0.81
0.83
0.89
0.83
0.83
0.86
0.89
0.83
0.86
0.89
0.92
0.86
0.86
0.89
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.94
0.94
0.94
0.94
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.03
1.03
1.03
1.03
1.03
1.03
1.03
1.03
0.81
0.81
0.83
0.89
0.83
0.83
0.86
0.89
0.83
0.83
0.89
0.92
0.83
0.86
0.89
0.92
0.92
0.92
0.89
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.94
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.03
1.00
1.00
1.00
1.03
1.03
1.03
1.03
3060
3315
3570
3825
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
9.9
9.7
12.0
14.1
7.4
10.1
12.3
14.6
7.5
10.3
12.6
15.0
11.8
13.9
7.3
9.9
12.2
14.4
7.3
10.1
12.5
14.8
Table PD-6 — Gross Cooling Capacities SAVE-050 (Cont.)
ENT Water Temp (°C)
35.0
Entering Wet Bulb Temperature (°C)
19.5
Ent.
DB
16.0
23.0
m3/h (°C)
24
TGC SHC
l/s
TGC
17.1
17.1
17.1
17.1
17.3
17.3
17.3
17.3
17.5
17.4
17.4
17.6
17.6
17.6
17.6
17.8
SHC
9.9
l/s
TGC
19.1
19.1
19.1
19.0
19.3
19.3
19.3
19.3
19.5
19.5
19.5
19.5
19.7
19.6
19.6
19.6
SHC
6.9
9.3
11.3
13.3
7.0
l/s
15.2
15.3
15.9
16.6
15.4
15.5
16.2
17.0
15.6
15.8
16.6
17.4
15.7
16.1
16.9
17.7
12.8
15.1
16.2
17.0
13.2
15.6
16.6
17.4
13.7
16.0
16.9
17.7
14.1
16.4
17.2
18.0
0.81
0.81
0.86
0.89
0.83
0.83
0.86
0.89
0.83
0.86
0.89
0.92
0.83
0.86
0.89
0.94
0.89
0.89
0.89
0.89
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.92
0.94
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.00
1.03
1.03
1.03
1.03
3060
3315
3570
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
12.3
14.2
16.2
10.1
12.7
14.8
16.8
10.4
13.0
15.3
17.3
10.6
13.4
15.8
17.8
9.5
11.6
13.7
7.1
9.8
12.0
14.2
7.1
9.9
12.3
3825
14.6
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
Capacity Correction Factor Table
Delta T
Water
(°C)
2.5
4.0
5.5
7.0
8.5
10.0
Total Cap.
kW
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
kW
l/s
2.21
1.39
1.00
0.79
0.66
0.56
1.01
1.01
1.00
1.00
1.00
0.99
PKG-PRC007-EN
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-7 — Gross Cooling Capacities SAVE-075
English
ENT Water Temp (°F)
75
85
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
61
67
73
SHC GPM
CFM
2700
TGC SHC GPM TGC
SHC GPM TGC
SHC GPM
TGC
77.2
77.7
80.6
84.5
78.1
79.0
82.5
86.5
79.0
80.2
84.1
88.3
79.7
81.4
85.6
89.9
SHC GPM
TGC
86.8
86.7
86.6
86.8
87.9
87.6
87.6
88.1
88.7
88.6
88.6
89.3
89.6
89.5
89.4
90.4
SHC
48.8
60.6
70.4
79.9
50.0
63.0
72.9
82.7
51.2
64.4
75.4
85.4
52.3
66.2
77.7
87.8
GPM TGC
79.4
79.8
82.5
86.5
80.5
81.1
84.4
88.5
81.3
64.2
75.6
81.7
85.7
66.3
78.1
83.6
87.7
68.4
18.1
18.1
18.5
19.4
18.1
18.5
18.9
19.8
18.5
18.5
19.4
20.3
18.5
18.9
19.8
20.3
89.4
89.3
89.1
89.4
90.4
90.3
90.3
90.6
91.5
91.4
91.3
91.8
92.3
92.2
92.1
93.0
49.9
61.6
71.5
81.1
51.1
63.6
74.0
84.0
52.3
65.5
76.4
86.7
53.4
67.3
78.9
89.3
19.8 100.1
19.8 100.0
35.3
47.0
56.8
66.6
35.7
48.2
58.5
68.8
36.0
49.1
60.1
71.0
36.3
50.2
61.6
73.1
22.0
22.0
22.0
22.0
22.5
22.5
22.0
22.0
22.5
22.5
22.5
22.5
22.5
22.5
22.5
22.5
63.1
74.3
79.8
83.7
65.2
76.8
81.7
85.7
67.2
78.9
83.3
87.5
69.2
80.6
84.8
89.0
18.1
18.1
18.5
19.4
18.1
18.5
18.9
19.8
18.5
18.5
19.4
20.3
18.5
18.9
19.8
20.3
19.8
19.8
19.8
19.8
20.3
20.3
20.3
20.3
20.3
20.3
20.3
20.3
97.1
97.0
97.0
96.9
98.3
98.2
98.1
97.9
99.2
99.1
99.0
98.9
34.2
46.0
55.8
65.5
34.5
47.0
57.4
67.7
34.9
48.1
59.0
69.8
35.2
49.0
60.5
71.9
22.0
22.0
22.0
21.6
22.0
22.0
22.0
22.0
22.5
22.5
22.5
22.0
22.5
22.5
22.5
22.5
19.8
19.8
99.9
99.7
20.3 101.2
20.3 101.1
20.3 101.0
20.3 100.9
20.3 102.3
20.3 102.2
20.3 102.1
20.3 102.0
20.7 103.1
20.3 103.0
20.7 103.0
20.7 102.9
2925
3150
3375
124.4 80.3
86.1
90.3
82.2
83.5
87.7
92.1
85.3
89.5
70.2
82.3
86.8
91.2
20.3 100.1
20.3 100.0
20.3
20.7
99.9
99.7
Table PD-7 — Gross Cooling Capacities SAVE-075 (Cont.)
ENT Water Temp (°F)
95
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
CFM
2700
TGC SHC GPM TGC
SHC GPM TGC
SHC GPM
74.7
75.4
78.5
82.5
75.6
76.7
80.3
84.4
76.4
78.0
81.9
86.1
77.2
79.3
83.4
87.6
62.0
73.0
77.8
81.7
63.0
75.2
79.6
83.6
66.0
77.1
81.2
85.3
68.0
78.5
82.6
86.7
18.1
18.1
18.5
19.4
18.1
18.5
18.9
19.8
18.1
18.5
19.4
20.3
18.5
18.9
19.8
20.3
84.1
84.0
84.0
84.3
85.0
84.9
84.9
85.5
85.9
85.8
85.8
86.7
86.6
86.5
86.5
87.9
47.7
59.4
69.2
78.6
48.9
61.4
71.7
81.4
50.1
63.2
74.1
83.9
51.1
65.0
76.4
86.1
19.8
19.8
19.8
19.8
19.8
19.8
19.8
20.3
20.3
20.3
20.3
20.3
20.3
20.3
20.3
20.3
94.0
94.0
93.9
93.8
95.1
95.0
95.0
94.9
96.0
95.9
95.8
95.7
96.8
96.7
96.7
96.6
33.2
44.9
54.6
64.4
33.5
46.0
56.3
66.6
33.8
46.9
57.9
68.8
34.1
47.9
59.4
70.8
21.6
21.6
21.6
21.6
22.0
22.0
22.0
22.0
22.0
22.0
22.0
22.0
22.5
22.5
22.0
22.0
2925
3150
3375
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
Capacity Correction Factor Table
Delta T
Water
(°F)
4.5
Total Cap.
MBh
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
MBh
1.01
GPM
2.21
1.39
1.00
0.79
0.66
0.56
7.2
1.01
1.00
1.00
1.00
10.0
12.6
15.3
18.0
0.99
18
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-7 — Gross Cooling Capacities SAVE-075
Metric
ENT Water Temp (°C)
24.0
29.5
Entering Wet Bulb Temperature (°C)
Ent.
DB
m3/h (°C)
24
16.0
19.5
23.0
16.0
19.5
23.0
TGC SHC
l/s
TGC
26.2
26.2
26.1
26.2
26.5
26.5
26.5
26.6
26.8
26.8
26.7
26.9
27.1
27.0
27.0
27.2
SHC
14.6
18.1
21.0
23.8
15.0
18.6
21.7
24.6
15.3
19.2
22.4
25.4
15.7
19.7
23.1
26.2
l/s
TGC
29.3
29.3
29.3
29.2
29.7
29.6
29.6
29.6
30.0
29.9
29.9
29.9
30.2
30.2
30.2
30.2
SHC
10.3
13.8
16.6
19.5
10.5
14.1
17.1
20.2
10.6
14.4
17.6
20.8
10.6
14.7
18.1
21.4
l/s
TGC
22.6
22.8
23.6
24.8
22.9
23.1
24.2
25.3
23.1
23.5
24.6
25.9
23.4
23.9
25.1
26.3
SHC
18.5
21.8
23.4
24.5
19.1
22.5
23.9
25.1
19.7
23.1
24.4
25.6
20.3
23.6
24.9
26.1
l/s
TGC
25.4
25.4
25.4
25.4
25.7
25.7
25.7
25.8
26.0
26.0
26.0
26.2
26.2
26.2
26.2
26.5
SHC
14.3
17.8
20.6
23.4
14.6
18.5
21.4
24.2
15.0
18.9
22.1
25.0
15.3
19.4
22.8
25.7
l/s
TGC
28.4
28.4
28.4
28.4
28.8
28.8
28.7
28.7
29.1
29.0
29.0
29.0
29.3
29.3
29.3
29.2
SHC
10.0
13.5
16.3
19.2
10.1
13.8
16.8
19.8
10.2
14.1
17.3
20.5
10.3
14.4
17.7
21.1
l/s
23.3
23.4
24.2
25.3
23.6
23.8
24.7
25.9
23.8
36.5
25.2
26.5
24.1
24.5
25.7
27.0
18.8
22.2
23.9
25.1
19.4
22.9
24.5
25.7
20.0
23.5
25.0
26.2
20.6
24.1
25.4
26.7
1.14
1.14
1.17
1.22
1.14
1.17
1.19
1.25
1.17
1.17
1.22
1.28
1.17
1.19
1.25
1.28
1.25
1.25
1.25
1.25
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.31
1.28
1.31
1.31
1.39
1.39
1.39
1.39
1.42
1.42
1.39
1.39
1.42
1.42
1.42
1.42
1.42
1.42
1.42
1.42
1.14
1.14
1.17
1.22
1.14
1.17
1.19
1.25
1.17
1.17
1.22
1.28
1.17
1.19
1.25
1.28
1.25
1.25
1.25
1.25
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.31
1.39
1.39
1.39
1.36
1.39
1.39
1.39
1.39
1.42
1.42
1.42
1.39
1.42
1.42
1.42
1.42
4590
4970
5355
5740
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
Table PD-7 — Gross Cooling Capacities SAVE-075 (Cont.)
ENT Water Temp (°C)
35.0
Entering Wet Bulb Temperature (°C)
19.5
Ent.
DB
16.0
23.0
m3/h (°C)
24
TGC SHC
l/s
TGC
24.6
24.6
24.6
24.7
24.9
24.9
24.9
25.1
25.2
25.1
25.1
25.4
25.4
25.3
25.3
25.7
SHC
14.0
17.4
20.3
23.0
14.3
18.0
21.0
23.8
14.7
18.5
21.7
24.6
15.0
19.0
22.4
25.2
l/s
TGC
27.5
27.5
27.5
27.5
27.9
27.8
27.8
27.8
28.1
28.1
28.1
28.0
28.4
28.3
28.3
28.3
SHC
9.7
13.2
16.0
18.9
9.8
13.5
16.5
19.5
9.9
13.8
17.0
20.2
10.0
14.0
17.4
20.7
l/s
21.9
22.1
23.0
24.2
22.1
22.5
23.5
24.7
22.4
22.9
24.0
25.2
22.6
23.2
24.4
25.7
18.2
21.4
22.8
23.9
18.5
22.0
23.3
24.5
19.4
22.6
23.8
25.0
19.9
23.0
24.2
25.4
1.14
1.14
1.17
1.22
1.14
1.17
1.19
1.25
1.14
1.17
1.22
1.28
1.17
1.19
1.25
1.28
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.28
1.36
1.36
1.36
1.36
1.39
1.39
1.39
1.39
1.39
1.39
1.39
1.39
1.42
1.42
1.39
1.39
4590
4970
5355
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
5740
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
Capacity Correction Factor Table
Delta T
Water
(°C)
2.5
4.0
5.5
7.0
8.5
10.0
Total Cap.
kW
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
kW
l/s
2.21
1.39
1.00
0.79
0.66
0.56
1.01
1.01
1.00
1.00
1.00
0.99
PKG-PRC007-EN
19
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-8 — Gross Cooling Capacities SAVE-100
English
ENT Water Temp (°F)
75
85
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
61
67
73
SHC GPM
CFM
3600
TGC SHC GPM TGC
109.9 87.9
110.1 103.3 26.0 122.6
112.7 112.7 26.9 122.5
117.7 117.7 27.8 122.5 110.0 28.6 136.3
111.2 90.7
111.8 106.8 26.4 124.1
115.3 115.3 27.3 124.0 100.5 29.1 137.9
120.5 120.5 28.2 124.1 114.0 29.1 137.8
112.5 93.4
113.3 110.1 26.9 125.5
117.6 117.6 27.8 125.3 103.8 29.5 139.4
123.0 123.0 28.6 125.7 117.8 29.5 139.3
113.6 96.0
114.8 113.0 27.3 126.6
SHC GPM TGC
SHC GPM
TGC
106.7
SHC GPM
86.3
107.1 101.7 26.0
110.1 110.1 26.9
115.3 115.3 27.8
TGC
119.5
119.4
119.3
SHC
67.1
82.7
95.8
GPM TGC
28.6 133.2
28.6 133.1
28.6 133.0
28.6 132.9
29.1 134.7
29.1 134.6
29.1 134.5
29.1 134.4
29.1 136.1
29.1 136.0
29.1 135.9
29.5 135.8
29.5 137.3
29.5 137.2
29.5 137.1
29.5 137.0
26.0 122.7
68.5
84.1
97.1
28.6 136.6
28.6 136.5
28.6 136.4
48.7
64.4
77.4
90.3
49.2
65.8
79.6
93.3
49.6
67.2
81.7
96.2
50.1
68.5
83.7
99.0
31.7
31.7
31.7
31.7
31.7
31.7
31.7
31.7
32.2
32.2
32.2
32.2
32.6
32.6
32.2
32.2
26.0
47.5
63.1
76.1
89.0
47.9
64.6
78.3
92.0
48.4
65.9
80.4
94.9
48.7
67.3
82.5
97.7
31.3
31.3
31.3
31.3
31.7
31.7
31.7
31.7
32.2
32.2
31.7
31.7
32.2
32.2
32.2
32.2
119.3 108.6
26.4 124.2
70.1
86.7
29.1 138.2
29.1 138.0
108.0
89.2
26.4
120.9
120.7
120.7
68.7
85.3
99.1
3900
4200
4500
108.8 105.1 26.4
112.7 112.7 27.3
117.9 117.9 28.2
120.9 112.5
26.9 125.6
71.7
89.2
29.5 139.6
29.5 139.5
109.3
91.9
26.4
122.2
122.1
70.2
87.9
122.0 102.4
122.5 116.3
71.8
90.2
123.1 105.6
110.3 108.2 26.9
114.9 114.9 27.8
120.4 120.4 28.6
26.9 126.7
73.1
91.7
29.5 140.8
29.5 140.7
110.3
94.6
26.9
123.3
123.2
111.9 110.9 27.3
117.0 117.0 28.2
122.6 122.6 29.5
119.7 119.7 28.2 126.5 106.9 29.5 140.6
125.2 125.2 29.5 127.2 121.3 29.5 140.5
124.0 119.7
Table PD-8 — Gross Cooling Capacities SAVE-100 (Cont.)
ENT Water Temp (°F)
95
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
CFM
3600
TGC SHC GPM TGC
103.6 84.9
104.1 100.0 26.0 116.0
107.6 107.6 26.9 115.9
112.7 112.7 27.8 116.1 107.0 28.6 129.4
105.0 87.7
105.8 103.3 26.4 117.4
110.1 110.1 27.3 117.3
115.3 115.3 28.2 117.7 110.9 29.1 130.8
106.1 90.3
107.3 106.2 26.9 118.6
112.3 112.3 27.8 118.6 100.9 29.1 132.3
117.6 117.6 29.1 119.3 114.5 29.1 132.2
107.0 93.0
109.0 108.7 27.3 119.7
SHC GPM TGC
SHC GPM
26.0 116.1
65.6
81.4
94.3
28.6 129.7
28.6 129.6
28.6 129.5
46.1
61.8
74.8
87.7
46.7
63.2
76.9
90.6
47.1
64.6
79.1
93.5
47.5
65.9
81.2
96.4
31.3
31.3
31.3
31.3
31.7
31.7
31.7
31.7
31.7
31.7
31.7
31.7
32.2
32.2
32.2
32.2
26.4 117.5
67.3
83.9
97.6
29.1 131.1
28.6 131.0
28.6 130.9
3900
4200
26.4 118.8
68.8
86.4
29.1 132.5
29.1 132.4
26.9 119.8
70.4
88.8
29.5 133.6
29.5 133.5
4500
114.3 114.3 28.2 119.6 104.1 29.5 133.4
119.9 119.9 29.5 120.7 117.8 29.5 133.3
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
Capacity Correction Factor Table
Delta T
Water
(°F)
4.5
Total Cap.
MBh
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
MBh
1.01
GPM
2.21
1.39
1.00
0.79
0.66
0.56
7.2
1.01
1.00
1.00
1.00
10.0
12.6
15.3
18.0
0.99
20
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-8 — Gross Cooling Capacities SAVE-100
Metric
ENT Water Temp (°C)
24.0
29.5
Entering Wet Bulb Temperature (°C)
Ent.
DB
m3/h (°C)
24
16.0
19.5
23.0
16.0
19.5
23.0
TGC SHC
l/s
TGC
35.9
35.9
35.9
35.9
36.4
36.4
36.3
36.4
36.8
36.8
36.7
36.8
37.1
37.1
37.1
37.3
SHC
20.1
24.7
28.5
32.2
20.6
25.4
29.5
33.4
21.0
26.1
30.4
34.5
21.4
26.9
31.3
35.6
l/s
TGC
40.0
40.0
40.0
39.9
40.5
40.4
40.4
40.4
40.9
40.9
40.8
40.8
41.3
41.2
41.2
41.2
SHC
14.3
18.9
22.7
26.5
14.4
19.3
23.3
27.3
14.5
19.7
23.9
28.2
14.7
20.1
24.5
29.0
l/s
TGC
31.3
31.4
32.3
33.8
31.7
31.9
33.0
34.6
32.0
32.3
33.7
35.3
32.3
32.8
34.3
35.9
SHC
25.3
29.8
32.3
33.8
26.1
30.8
33.0
34.6
26.9
31.7
33.7
35.3
27.7
32.5
34.3
35.9
l/s
TGC
35.0
35.0
34.9
34.9
35.4
35.4
35.4
35.4
35.8
35.8
35.7
35.9
36.1
36.1
36.1
36.3
SHC
19.6
24.2
28.1
31.8
20.1
25.0
29.0
33.0
20.6
25.7
30.0
34.1
21.0
26.4
30.9
35.1
l/s
TGC
39.0
39.0
39.0
38.9
39.5
39.4
39.4
39.4
39.9
39.8
39.8
39.8
40.2
40.2
40.2
40.1
SHC
13.9
18.5
22.3
26.1
14.0
18.9
22.9
27.0
14.2
19.3
23.6
27.8
14.3
19.7
24.2
28.6
l/s
32.2
32.3
33.0
34.5
32.6
32.7
33.8
35.3
33.0
33.2
34.5
36.0
33.3
33.6
35.1
36.7
25.7
30.3
33.0
34.5
26.6
31.3
33.8
35.3
27.4
32.3
34.5
36.0
28.1
33.1
35.1
36.7
1.64
1.64
1.70
1.75
1.67
1.67
1.72
1.78
1.70
1.70
1.75
1.81
1.70
1.72
1.78
1.86
1.81
1.81
1.81
1.81
1.83
1.83
1.83
1.83
1.86
1.86
1.86
1.86
1.86
1.86
1.86
1.86
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.03
2.03
2.03
2.03
2.06
2.06
2.03
2.03
1.64
1.64
1.70
1.75
1.67
1.67
1.72
1.78
1.67
1.70
1.75
1.81
1.70
1.72
1.78
1.86
1.81
1.81
1.81
1.81
1.83
1.83
1.83
1.83
1.83
1.83
1.83
1.86
1.86
1.86
1.86
1.86
1.97
1.97
1.97
1.97
2.00
2.00
2.00
2.00
2.03
2.03
2.00
2.00
2.03
2.03
2.03
2.03
6120
6630
7140
7650
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
Table PD-8 — Gross Cooling Capacities SAVE-100 (Cont.)
ENT Water Temp (°C)
35.0
Entering Wet Bulb Temperature (°C)
19.5
Ent.
DB
16.0
23.0
m3/h (°C)
24
TGC SHC
l/s
TGC
34.0
34.0
34.0
34.0
34.4
34.4
34.4
34.5
34.8
34.7
34.7
34.9
35.1
35.1
35.0
35.4
SHC
19.2
23.8
27.6
31.4
19.7
24.6
28.6
32.5
20.2
25.3
29.6
33.6
20.6
26.0
30.5
34.5
l/s
TGC
38.0
38.0
37.9
37.9
38.4
38.4
38.4
38.3
38.8
38.8
38.8
38.7
39.1
39.1
39.1
39.1
SHC
13.5
18.1
21.9
25.7
13.7
18.5
22.5
26.6
13.8
18.9
23.2
27.4
13.9
19.3
23.8
28.2
l/s
30.4
30.5
31.5
33.0
30.8
31.0
32.3
33.8
31.1
31.4
32.9
34.5
31.4
31.9
33.5
35.1
24.9
29.3
31.5
33.0
25.7
30.3
32.3
33.8
26.5
31.1
32.9
34.5
27.3
31.8
33.5
35.1
1.64
1.64
1.70
1.75
1.67
1.67
1.72
1.78
1.67
1.70
1.75
1.83
1.70
1.72
1.78
1.86
1.81
1.81
1.81
1.81
1.83
1.81
1.81
1.83
1.83
1.83
1.83
1.83
1.86
1.86
1.86
1.86
1.97
1.97
1.97
1.97
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.00
2.03
2.03
2.03
2.03
6210
6630
7140
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
7650
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
Capacity Correction Factor Table
Delta T
Water
(°C)
2.5
4.0
5.5
7.0
8.5
10.0
Total Cap.
kW
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
kW
l/s
2.21
1.39
1.00
0.79
0.66
0.56
1.01
1.01
1.00
1.00
1.00
0.99
PKG-PRC007-EN
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-9 — Gross Cooling Capacities SAVE-125
English
ENT Water Temp (°F)
75
85
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
61
67
73
SHC GPM
CFM
4500
TGC SHC GPM TGC
135.8 109.8 31.3 151.7
136.1 129.4 31.7 151.6 105.3 34.4 169.1
140.1 140.1 32.2 151.5 121.8 34.4 168.9
146.6 146.6 33.5 151.6 138.1 34.4 168.7 113.2 37.9
137.3 113.5 31.7 153.6
138.2 133.7 31.7 153.5 108.6 34.8 171.0
143.2 143.2 32.6 153.3 126.2 34.8 170.8
149.9 149.9 33.9 153.7 143.2 34.8 170.7 117.0 38.3
138.9 117.0 32.2 155.3
140.3 137.7 32.2 155.1 111.7 35.2 172.7
146.2 146.2 33.5 154.9 130.3 35.2 172.6 102.4 38.8
153.1 153.1 34.8 155.7 147.9 35.2 172.4 120.8 38.3
140.2 120.2 32.2 156.7
140.7 140.0 32.6 156.5 114.9 35.2 174.2
148.8 148.8 33.9 156.3 134.3 35.2 174.1 104.9 38.8
SHC GPM TGC
85.3
SHC GPM
TGC
SHC GPM
TGC
147.4
SHC
83.5
147.3 103.4
147.1 119.9
147.5 136.1
GPM TGC
34.4 164.4
34.4 164.3
34.4 164.1
34.4 164.0
34.8 166.3
34.8 166.1
34.8 165.9
34.8 165.9
34.8 167.9
34.8 167.7
34.8 167.7
35.2 167.5
35.2 169.4
35.2 169.2
35.2 169.1
35.7 168.9
34.4 169.3
60.3
80.3
96.8
37.9
37.9
37.9
131.7 107.9 31.3
132.3 127.2 31.3
136.8 136.8 32.2
143.2 143.2 33.5
133.2 111.5 31.7
134.3 131.4 31.7
139.9 139.9 32.6
146.5 146.5 33.9
134.7 115.0 31.7
136.4 134.9 32.2
142.7 142.7 33.5
149.5 149.5 34.8
136.0 119.4 32.2
138.5 138.0 32.6
145.2 145.2 33.9
152.1 152.1 35.2
58.5
78.4
95.0
37.4
37.4
37.4
111.5 37.4
87.4
34.8 171.3
60.9
82.0
99.6
38.3
38.3
38.3
149.1
85.5
59.1
80.2
97.8
37.9
37.9
37.9
4875
5250
5625
149.3 107.0
148.9 124.3
149.4 141.0
115.3 37.9
89.4
35.2 172.8
61.5
83.8
38.8
38.8
150.7
87.5
59.6
82.0
38.3
38.3
150.5 109.8
150.4 128.4
151.4 145.6
100.5 38.3
119.0 38.3
91.2
35.2 174.4
62.0
85.5
38.8
38.8
151.9
89.4
60.2
83.7
38.8
38.8
151.9 113.0
151.7 132.4
153.4 149.7
103.1 38.8
122.4 38.8
155.9 155.9 35.2 157.6 152.1 35.7 174.0 124.3 38.8
Table PD-9 — Gross Cooling Capacities SAVE-125 (Cont.)
ENT Water Temp (°F)
95
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
CFM
4500
TGC SHC GPM TGC
127.6 105.9 31.3 142.9
128.4 124.8 31.3 142.7 101.4 33.9 159.4
133.4 133.4 32.2 142.6 118.0 33.9 159.2
139.7 139.7 33.5 143.0 134.0 34.4 159.1 109.5 37.4
129.0 109.6 31.3 144.5
132.6 128.7 31.7 144.4 104.7 34.4 161.0
136.4 136.4 33.0 144.2 122.3 34.4 161.0
142.9 142.9 34.4 145.0 138.7 34.8 160.8 113.4 37.9
130.3 113.0 31.7 146.0
132.6 132.0 32.2 145.8 107.9 34.8 162.5
139.0 139.0 33.5 145.6 126.4 34.8 162.4
SHC GPM TGC
81.6
SHC GPM
33.9 159.5
56.7
76.7
93.1
37.4
37.4
37.4
83.5
34.4 161.2
57.3
78.4
96.0
37.9
37.9
37.9
4875
5250
85.6
34.8 162.8
57.9
80.1
98.7
37.9
37.9
37.9
145.8 145.8 34.8 147.0 143.1 34.8 162.2 117.0 37.9
131.6 116.2 32.2 147.2
134.7 134.6 32.6 147.1 111.0 34.8 163.9
141.5 141.5 33.9 147.0 130.4 34.8 163.8 101.3 38.3
87.5
34.8 164.1
58.3
81.8
38.3
38.3
5625
148.4 148.4 35.2 161.5 147.0 35.2 163.7 120.6 38.3
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
Capacity Correction Factor Table
Delta T
Water
(°F)
4.5
Total Cap.
MBh
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
MBh
1.01
GPM
2.21
1.39
1.00
0.79
0.66
0.56
7.2
1.01
1.00
1.00
1.00
10.0
12.6
15.3
18.0
0.99
22
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-9 — Gross Cooling Capacities SAVE-125
Metric
ENT Water Temp (°C)
24.0
29.5
Entering Wet Bulb Temperature (°C)
Ent.
DB
m3/h (°C)
24
16.0
19.5
23.0
16.0
19.5
23.0
TGC SHC
l/s
TGC
44.5
44.4
44.4
44.4
45.0
45.0
44.9
45.0
45.5
45.4
45.4
45.6
45.9
45.8
45.8
46.2
SHC
25.0
30.9
35.7
40.5
25.6
31.8
37.0
42.0
26.2
32.7
38.2
43.3
26.7
33.7
39.3
44.6
l/s
TGC
49.6
49.5
49.5
49.4
50.2
50.1
50.1
50.0
50.6
50.6
50.6
50.5
51.1
51.0
51.0
51.0
SHC
17.7
23.5
28.4
33.2
17.8
24.0
29.2
34.3
18.0
24.6
30.0
35.4
18.2
25.0
30.7
36.4
l/s
TGC
38.6
38.8
40.1
42.0
39.0
39.3
41.0
42.9
39.5
40.0
41.8
43.8
39.8
40.6
42.5
44.6
SHC
31.6
37.3
40.1
42.0
32.7
38.5
41.0
42.9
33.7
39.5
41.8
43.8
35.0
40.4
42.5
44.6
l/s
TGC
43.2
43.2
43.1
43.2
43.7
43.7
43.6
43.8
44.1
44.1
44.1
44.4
44.5
44.5
44.5
44.9
SHC
24.5
30.3
35.1
39.9
25.0
31.4
36.4
41.3
25.6
32.2
37.6
42.7
26.2
33.1
38.8
43.9
l/s
TGC
48.2
48.1
48.1
48.1
48.7
48.7
48.6
48.6
49.2
49.1
49.1
49.1
49.6
49.6
49.5
49.5
SHC
17.1
23.0
27.8
32.7
17.3
23.5
28.6
33.8
17.5
24.0
29.4
34.9
17.6
24.5
30.2
35.9
l/s
39.8
39.9
41.0
42.9
40.2
40.5
42.0
43.9
40.7
41.1
42.8
44.9
41.1
41.2
43.6
45.7
32.2
37.9
41.0
42.9
33.3
39.2
42.0
43.9
34.3
40.3
42.8
44.9
35.2
41.0
43.6
45.7
1.97
2.00
2.03
2.11
2.00
2.00
2.06
2.14
2.03
2.03
2.11
2.20
2.03
2.06
2.14
2.22
2.17
2.17
2.17
2.17
2.20
2.20
2.20
2.20
2.22
2.22
2.22
2.22
2.22
2.22
2.22
2.25
2.39
2.39
2.39
2.39
2.42
2.42
2.42
2.42
2.45
2.45
2.45
2.42
2.45
2.45
2.45
2.45
1.97
1.97
2.03
2.11
2.00
2.00
2.06
2.14
2.00
2.03
2.11
2.20
2.03
2.06
2.14
2.22
2.17
2.17
2.17
2.17
2.20
2.20
2.20
2.20
2.20
2.20
2.20
2.22
2.22
2.22
2.22
2.25
2.36
2.36
2.36
2.36
2.39
2.39
2.39
2.39
2.42
2.42
2.42
2.42
2.45
2.45
2.45
2.45
7650
8285
8920
9560
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
Table PD-9 — Gross Cooling Capacities SAVE-125 (Cont.)
ENT Water Temp (°C)
35.0
Entering Wet Bulb Temperature (°C)
19.5
Ent.
DB
16.0
23.0
m3/h (°C)
24
TGC SHC
l/s
TGC
41.9
41.8
41.8
41.9
42.3
42.3
42.2
42.5
42.8
42.7
42.7
43.1
43.1
43.1
43.1
47.3
SHC
23.9
29.7
34.6
39.3
24.5
30.7
35.8
40.6
25.1
31.6
37.0
41.9
25.6
32.5
38.2
43.1
l/s
TGC
46.7
46.7
46.6
46.6
47.2
47.2
47.2
47.1
47.7
47.6
47.6
47.5
48.1
48.0
48.0
48.0
SHC
16.6
22.5
27.3
32.1
16.8
23.0
28.1
33.2
17.0
23.5
28.9
34.3
17.1
24.0
29.7
35.3
l/s
37.4
37.6
39.1
40.9
37.8
38.9
40.0
41.9
38.2
38.9
40.7
42.7
38.5
39.5
41.5
43.5
31.0
36.6
39.1
40.9
32.1
37.7
40.0
41.9
33.1
38.7
40.7
42.7
34.1
39.4
41.5
43.5
1.97
1.97
2.03
2.11
1.97
2.00
2.08
2.17
2.00
2.03
2.11
2.20
2.03
2.06
2.14
2.22
2.14
2.14
2.14
2.17
2.17
2.17
2.17
2.20
2.20
2.20
2.20
2.20
2.20
2.20
2.20
2.22
2.36
2.36
2.36
2.36
2.39
2.39
2.39
2.39
2.39
2.39
2.39
2.39
2.42
2.42
2.42
2.42
7650
8285
8920
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
9560
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
Capacity Correction Factor Table
Delta T
Water
(°C)
2.5
4.0
5.5
7.0
8.5
10.0
Total Cap.
kW
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
kW
l/s
2.21
1.39
1.00
0.79
0.66
0.56
1.01
1.01
1.00
1.00
1.00
0.99
PKG-PRC007-EN
23
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-10 — Gross Cooling Capacities SAVE-150
English
ENT Water Temp (°F)
75
85
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
61
67
73
SHC GPM
CFM
5400
TGC SHC GPM TGC
165.6 138.7 37.9 185.4 106.0 41.4 206.9
167.7 163.2 38.3 185.2 132.7 41.4 206.6
175.0 173.4 39.6 185.1 154.9 41.4 206.4 121.6 45.8
183.4 181.7 41.0 186.5 175.6 41.9 206.3 143.5 45.8
167.6 143.7 38.3 187.5 108.8 41.9 209.1
170.7 168.2 38.8 187.3 137.3 41.9 208.8 101.9 46.3
179.0 177.3 40.5 187.3 160.8 41.9 208.6 125.4 46.3
187.6 185.8 41.9 189.4 182.0 42.3 208.5 148.8 46.3
SHC GPM TGC
SHC GPM
72.8
99.4
TGC
SHC GPM
TGC
SHC
GPM TGC
41.4 200.2
41.4 200.0
41.4 199.9
41.4 199.7
41.4 202.3
41.4 202.1
41.4 202.0
42.3 201.8
41.9 204.1
41.9 203.9
41.9 203.8
42.7 203.7
42.3 205.8
42.3 205.6
42.3 205.4
43.2 205.3
45.8
45.8
160.4 136.3 37.4
163.0 160.0 37.9
170.6 169.0 39.6
178.8 177.1 41.0
162.3 141.2 37.9
166.0 164.3 38.8
174.4 172.7 40.1
182.9 181.2 41.9
164.1 145.8 38.3
169.2 167.5 39.2
177.8 176.1 41.0
186.5 184.7 42.7
164.1 150.2 38.8
172.1 170.5 39.6
180.9 179.2 41.4
189.8 188.0 43.2
179.6 103.6
179.3 130.3
179.3 152.4
181.0 172.6
181.3 106.4
181.2 135.1
181.4 158.2
183.9 178.8
183.2 109.1
183.0 139.2
183.4 163.7
186.8 184.0
184.8 111.7
184.6 143.4
185.3 169.0
189.7 187.9
70.4
97.1
45.4
45.4
119.2 45.4
141.2 45.4
73.5
46.3
71.1
99.5
45.8
45.8
5850
6300
6750
123.0 45.8
146.4 45.8
169.5 148.4 38.3 189.3 111.5 42.3 210.9
74.3
46.7
71.9
46.3
173.8 172.1 39.2 189.2 141.6 42.3 210.8 104.3 46.7
182.6 180.9 41.0 189.4 166.4 42.3 210.6 129.2 46.7
191.4 189.6 42.7 192.3 187.6 42.7 210.5 154.0 46.7
101.9 45.8
126.8 45.8
151.6 45.8
171.2 152.9 38.8 191.0 114.2 42.7 212.7
74.9
46.7
72.6
46.3
176.8 175.1 40.1 190.8 145.9 42.7 212.5 106.6 46.7
185.9 184.1 41.9 191.3 171.7 42.7 212.4 132.8 46.7
194.9 193.0 43.6 195.1 192.5 43.6 212.2 158.9 46.7
104.2 46.3
130.4 46.3
156.5 46.3
Table PD-10 — Gross Cooling Capacities SAVE-150 (Cont.)
ENT Water Temp (°F)
95
Entering Wet Bulb Temperature (°F)
Ent.
DB
(°F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
61
67
73
CFM
5400
TGC SHC GPM TGC
155.0 133.7 37.4 173.4 101.1 41.0 193.4
158.0 156.2 37.9 173.3 127.8 41.0 193.2
165.9 164.3 39.6 173.4 149.8 41.0 193.1 116.8 44.9
174.0 172.3 41.0 175.4 169.5 41.4 192.9 138.7 44.9
156.8 138.5 37.9 175.2 103.9 41.4 195.3
161.3 159.7 38.8 175.0 132.3 41.4 195.2
169.6 168.0 40.1 175.4 155.6 41.4 195.0 120.6 45.4
177.9 176.2 41.9 178.3 175.0 41.9 194.9 144.0 45.4
158.4 143.1 37.9 176.8 106.6 41.4 197.0
164.3 162.8 39.2 176.7 136.7 41.4 196.9
172.8 171.2 41.0 177.2 161.0 41.9 196.7 124.4 45.4
181.3 179.6 42.3 181.3 179.5 42.3 196.6 149.1 45.4
160.0 147.4 38.3 178.3 109.2 41.9 198.6
SHC GPM TGC
SHC GPM
68.0
94.6
44.9
44.9
68.7
97.1
45.4
45.4
5850
6300
69.5
99.4
45.8
45.8
70.1
45.8
6750
167.2 165.6 39.6 178.1 140.9 41.9 198.3 101.7 45.8
175.8 174.1 41.4 179.0 166.1 42.3 198.2 127.9 45.8
184.5 182.7 43.2 184.5 182.7 43.2 198.0 154.0 45.8
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
Capacity Correction Factor Table
Delta T
Water
(°F)
4.5
Total Cap.
MBh
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
MBh
1.01
GPM
2.21
1.39
1.00
0.79
0.66
0.56
7.2
1.01
1.00
1.00
1.00
10.0
12.6
15.3
18.0
0.99
24
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Water Cooled
60 Hz
Table PD-10 — Gross Cooling Capacities SAVE-150
Metric
ENT Water Temp (°C)
24.0
29.5
Entering Wet Bulb Temperature (°C)
Ent.
DB
m3/h (°C)
24
16.0
19.5
23.0
16.0
19.5
23.0
TGC SHC
l/s
TGC
54.3
54.3
54.2
54.6
54.9
54.9
54.9
55.5
55.5
55.4
55.5
56.3
56.0
55.9
56.1
57.2
SHC
31.1
38.9
45.4
51.4
31.9
40.2
47.1
53.3
32.7
41.5
48.8
55.0
33.5
42.8
50.3
56.4
l/s
TGC
60.6
60.5
60.5
60.5
61.3
61.2
61.1
61.1
61.8
61.8
61.7
61.7
62.3
62.3
62.2
62.2
SHC
21.3
29.1
35.6
42.1
21.5
29.9
36.7
43.6
21.8
30.6
37.8
45.1
21.9
31.2
38.9
46.6
l/s
TGC
47.0
47.7
50.0
52.4
47.6
48.6
51.1
53.6
48.1
49.6
52.1
54.6
48.1
50.4
53.0
55.6
SHC
39.9
46.9
49.5
51.9
41.4
48.1
50.6
53.1
42.7
49.1
51.6
54.1
44.0
49.9
52.5
55.1
l/s
TGC
52.6
52.5
52.5
53.0
53.2
53.1
53.2
53.9
53.7
53.6
53.7
54.7
54.1
54.1
54.3
55.6
SHC
30.3
38.2
44.6
50.6
31.2
39.6
46.3
52.4
32.0
40.8
48.0
53.9
32.7
42.0
49.5
55.1
l/s
TGC
58.7
58.6
58.6
58.5
59.3
59.2
59.2
59.1
59.8
59.7
59.7
59.7
60.3
60.2
60.2
60.1
SHC
20.6
28.5
34.9
41.4
20.8
29.2
36.0
42.9
21.1
29.9
37.1
44.4
21.3
30.5
38.2
45.9
l/s
48.5
49.1
51.3
53.7
49.1
50.0
52.5
55.0
49.7
50.9
53.5
56.1
50.1
51.8
54.5
57.1
40.6
47.8
50.8
53.2
42.1
49.3
52.0
54.5
43.5
50.4
53.0
55.6
44.8
51.3
53.9
56.6
2.39
2.42
2.50
2.58
2.42
2.45
2.56
2.64
2.42
2.47
2.58
2.70
2.45
2.53
2.64
2.75
2.61
2.61
2.61
2.64
2.64
2.64
2.64
2.67
2.67
2.67
2.67
2.70
2.70
2.70
2.70
2.75
2.89
2.89
2.89
2.89
2.92
2.92
2.92
2.92
2.95
2.95
2.95
2.95
2.95
2.95
2.95
2.95
2.36
2.39
2.50
2.58
2.39
2.45
2.53
2.64
2.42
2.47
2.58
2.70
2.45
2.50
2.61
2.72
2.61
2.61
2.61
2.61
2.61
2.61
2.61
2.67
2.64
2.64
2.64
2.70
2.67
2.67
2.67
2.72
2.86
2.86
2.86
2.86
2.89
2.89
2.89
2.89
2.92
2.89
2.89
2.89
2.92
2.92
2.92
2.92
9180
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
9945
10710
11475
Table PD-10 — Gross Cooling Capacities SAVE-150 (Cont.)
ENT Water Temp (°C)
35.0
Entering Wet Bulb Temperature (°C)
Ent.
DB
m3/h (°C)
24
16.0
19.5
23.0
TGC SHC
l/s
TGC
50.8
50.8
50.8
51.4
51.3
51.3
51.4
52.2
51.8
51.8
51.9
53.1
52.2
52.2
52.5
54.1
SHC
29.6
37.5
43.9
49.7
30.4
38.8
45.6
51.3
31.2
40.0
47.2
52.6
32.0
41.3
48.7
53.5
l/s
TGC
56.7
56.6
56.6
56.5
57.2
57.2
57.1
57.1
57.7
57.7
57.6
57.6
58.2
58.1
58.1
58.0
SHC
19.9
27.7
34.2
40.6
20.1
28.5
35.3
42.2
20.4
29.1
36.4
43.7
20.5
29.8
37.5
45.1
l/s
45.4
46.3
48.6
51.0
45.9
47.3
49.7
52.1
46.4
48.1
50.6
53.1
46.9
49.0
51.5
54.1
39.2
45.8
48.1
50.5
40.6
46.8
49.2
51.6
41.9
47.7
50.2
52.6
43.2
48.5
51.0
53.5
2.36
2.39
2.50
2.58
2.39
2.45
2.53
2.64
2.39
2.47
2.58
2.67
2.42
2.50
2.61
2.72
2.58
2.58
2.58
2.61
2.61
2.61
2.61
2.64
2.61
2.61
2.64
2.67
2.64
2.64
2.67
2.72
2.83
2.83
2.83
2.83
2.86
2.86
2.86
2.86
2.89
2.89
2.86
2.86
2.89
2.89
2.89
2.89
9180
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
9945
10710
11475
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
Capacity Correction Factor Table
Delta T
Water
(°C)
2.5
4.0
5.5
7.0
8.5
10.0
Total Cap.
kW
1.01
1.01
1.00
0.99
0.99
0.98
Sens. Cap.
kW
l/s
2.21
1.39
1.00
0.79
0.66
0.56
1.01
1.01
1.00
1.00
1.00
0.99
PKG-PRC007-EN
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-11 — Gross Cooling Capacities SRVE-050
English
Ambient Temperature (°F)
85
67
95
Entering Wet Bulb Temperature (°F)
73 61
Ent.
61
67
73
DB
(ºF) TGC
CFM
1800
SHC
44.2
52.0
56.0
58.6
45.7
53.7
57.2
60.0
47.2
55.3
58.4
61.2
48.5
56.6
59.5
62.3
TGC SHC
TGC
SHC TGC SHC TGC
SHC
33.4
41.7
48.4
54.9
34.2
42.9
50.2
56.9
35.1
44.3
51.9
58.7
35.8
45.6
53.5
60.3
TGC SHC
65.1 23.1
65.1 31.4
65.0 38.2
65.0 44.9
64.6 23.4
65.7 32.1
65.7 39.3
65.6 46.5
66.5 23.6
66.4 32.8
66.3 40.4
66.3 48.0
67.0 23.7
66.9 33.5
66.9 41.6
66.8 49.5
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
53.7
54.1
56.0
58.6
54.4
54.9
57.2
60.0
55.0
55.8
58.4
61.2
55.5
56.6
59.5
62.3
60.2
60.1
60.1
60.2
61.0
60.8
60.8
61.2
61.5
61.5
61.4
61.9
62.0
62.0
62.0
62.6
34.1
42.4
49.2
55.8
35.0
43.8
51.0
57.9
35.8
45.1
52.7
59.7
36.6
46.3
54.4
61.4
67.1
67.0
67.0
66.9
67.8
67.7
67.7
67.6
68.5
68.4
68.4
68.3
69.1
69.0
68.9
71.3
23.9
32.1
38.9
45.7
24.1
32.9
40.1
47.3
24.3
33.5
41.1
48.8
24.5
34.2
42.3
50.2
52.2
52.6
54.6
57.2
52.8
53.4
55.9
58.5
53.3
54.3
57.0
59.7
53.8
55.2
58.0
60.8
43.5
51.2
54.6
57.2
44.9
52.8
55.9
58.5
46.4
54.2
57.0
59.7
47.8
55.2
58.0
60.8
58.4
58.4
58.3
58.5
59.0
59.0
58.9
59.4
59.7
59.6
59.6
60.2
60.2
60.1
60.1
61.0
1950
2100
2250
Table PD-11 — Gross Cooling Capacities SRVE-050 (Cont.)
English
Ambient Temperature (°F)
105
67
115
67
SHC TGC SHC TGC
Entering Wet Bulb Temperature (°F)
Ent.
DB
(ºF) TGC
61
73
61
73
CFM
1800
SHC
42.7
50.2
53.3
55.8
44.2
51.7
54.5
57.0
45.6
52.9
55.5
58.2
47.0
53.7
56.5
59.1
TGC SHC
TGC
SHC
31.8
40.1
46.9
53.0
32.6
41.3
48.5
54.8
33.5
42.7
50.2
56.3
34.2
43.9
51.8
57.5
TGC SHC
60.6 21.5
60.6 29.8
60.5 36.6
60.5 43.2
61.3 21.7
61.2 30.4
61.2 37.6
61.1 44.8
61.7 21.9
61.7 31.2
61.6 38.8
61.6 46.3
62.2 22.2
62.1 31.8
62.1 39.9
62.0 47.8
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
50.6
51.1
53.3
55.8
51.1
51.9
54.5
57.0
51.6
52.9
55.5
58.2
52.2
53.7
56.5
59.1
56.6
56.5
56.5
56.7
57.1
57.1
57.1
57.6
57.7
57.7
57.7
58.4
58.2
58.1
58.2
59.3
32.6
40.8
47.7
54.1
33.5
42.2
49.4
56.0
34.2
43.5
51.1
57.6
35.1
44.7
52.7
59.0
63.0
63.0
62.9
62.9
63.6
63.6
63.5
63.5
64.1
64.1
64.0
64.0
64.7
64.7
64.6
64.6
22.4
30.5
37.4
44.1
22.6
31.3
38.5
45.7
22.8
32.0
39.6
47.3
23.0
32.6
40.7
48.7
48.9
49.5
51.8
54.3
49.4
50.5
52.9
55.4
49.9
51.4
54.0
56.5
50.4
52.3
54.8
57.5
42.0
49.2
51.8
54.3
43.4
50.5
52.9
55.4
44.9
51.4
54.0
56.5
46.1
52.3
54.8
57.5
54.6
54.5
54.5
54.9
55.1
55.1
55.1
55.8
55.7
55.5
55.7
56.5
56.1
56.1
56.2
57.5
1950
2100
2250
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
26
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-11 — Gross Cooling Capacities SRVE-050
Metric
Ambient Temperature (°C)
29.5
19.5
35.0
Entering Wet Bulb Temperature (°C)
23.0 16.0
Ent.
DB
16.0
SHC
19.5
23.0
m3/h (ºC) TGC
TGC SHC
TGC SHC TGC SHC TGC
SHC
14.0
17.5
20.3
23.1
14.3
18.0
21.1
23.9
14.7
18.6
21.8
24.6
15.0
19.1
22.5
25.3
TGC SHC
27.1
27.1 13.1
27.1 16.0
27.1 18.9
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
22.5
22.6
23.4
24.6
22.7
23.0
24.0
25.1
23.0
23.3
24.5
25.7
23.2
23.7
24.9
26.1
18.6
21.9
23.4
24.6
19.2
22.6
24.0
25.1
19.8
23.2
24.5
25.7
20.4
23.7
24.9
26.1
25.2
25.2
25.1
25.2
25.5
25.4
25.4
25.6
25.7
25.7
25.7
25.9
25.9
25.9
25.9
26.2
14.3
17.8
20.7
23.5
14.7
18.4
21.5
24.3
15.0
18.9
22.2
25.1
15.3
19.5
22.9
25.8
28.1
28.0
28.0
28.0
28.4
28.4
28.3
28.3
28.6
28.6
28.6
28.6
28.9
28.9
28.8
28.8
10.0
13.5
16.3
19.2
10.1
13.8
16.8
19.9
10.2
14.1
17.3
20.5
10.2
14.3
17.7
21.1
21.7
21.9
22.8
23.9
22.0
22.3
23.3
24.5
22.2
22.6
23.8
24.9
22.4
23.0
24.2
25.4
18.2
21.5
22.8
23.9
18.9
22.1
23.3
24.5
19.4
22.6
23.8
24.9
20.0
23.0
24.2
25.4
24.3
24.3
24.3
24.4
24.6
24.6
24.6
24.8
24.8
24.8
24.8
25.1
25.0
25.0
25.0
25.4
9.6
4590
4970
5355
5740
27.4
9.7
27.4 13.4
27.3 16.5
27.3 19.5
27.6
9.8
27.6 13.7
27.6 16.9
27.6 20.2
27.9
9.9
27.8 14.0
27.8 17.4
27.8 20.8
Table PD-11 — Gross Cooling Capacities SRVE-050 (Cont.)
Metric
Ambient Temperature (°C)
40.5
19.5
46
19.5
TGC SHC TGC SHC TGC
Entering Wet Bulb Temperature (°C)
Ent.
DB
16.0
23.0
16.0
23.0
m3/h (ºC) TGC
SHC
17.9
21.0
22.2
23.3
18.5
21.6
22.6
23.8
19.1
22.0
23.1
24.2
19.6
22.3
23.5
24.6
TGC SHC
SHC
13.2
16.7
19.6
22.2
13.6
17.3
20.3
22.9
13.9
17.8
21.0
23.4
14.2
18.3
21.6
23.8
TGC SHC
25.1
25.1 12.4
25.0 15.2
25.0 18.1
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
20.9
21.2
22.2
23.3
21.2
21.6
22.6
23.8
21.4
22.0
23.1
24.2
21.6
22.3
23.5
24.6
23.4
23.4
23.4
23.6
23.7
23.7
23.7
23.9
23.9
23.9
23.9
24.3
24.1
24.1
24.1
24.6
13.6
17.1
20.0
22.7
14.0
17.7
20.7
23.4
14.3
18.2
21.4
24.1
14.6
18.7
22.1
24.6
26.1
26.1
26.1
26.1
26.4
26.3
26.3
26.3
26.6
26.6
26.6
26.5
26.8
26.8
26.8
26.7
9.3
12.8
15.6
18.5
9.4
13.0
16.1
19.2
9.4
13.4
16.6
19.8
9.5
13.6
17.0
20.4
20.1
20.5
21.5
22.5
20.3
20.9
21.9
23.0
20.5
21.2
22.3
23.4
20.7
21.6
22.7
23.8
17.5
20.4
21.5
22.5
18.1
20.9
21.9
23.0
18.7
21.2
22.3
23.4
19.2
21.6
22.7
23.8
22.5
22.5
22.5
22.7
22.7
22.7
22.7
23.0
23.0
22.9
23.0
23.4
23.1
23.1
23.2
23.8
8.9
4590
4970
5355
25.3
9.0
25.3 12.7
25.3 15.7
25.3 18.8
25.5
9.1
25.5 13.0
25.5 16.2
25.5 19.4
25.7
9.2
5740
25.7 13.3
25.7 16.6
25.7 20.0
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
PKG-PRC007-EN
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-12 — Gross Cooling Capacities SRVE-075
English
Ambient Temperature (°F)
85
67
95
Entering Wet Bulb Temperature (°F)
73 61
Ent.
61
67
73
DB
(ºF) TGC
CFM
2700
SHC
63.5
74.7
80.0
84.0
65.6
77.1
81.8
85.8
67.6
79.2
83.5
87.6
69.5
80.9
85.0
89.0
TGC SHC
TGC
SHC TGC SHC TGC
SHC
47.7
59.6
69.4
78.9
48.9
61.5
72.0
81.6
50.0
63.4
74.4
84.1
51.2
65.2
76.6
86.2
TGC SHC
92.5 32.9
92.4 44.7
92.3 54.6
92.3 64.4
93.5 33.2
93.4 45.8
93.3 56.3
93.3 66.7
94.3 33.5
94.2 46.9
94.1 57.8
94.1 68.8
95.1 33.8
95.0 47.8
94.9 59.4
94.9 70.9
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
76.6
77.2
80.0
84.0
77.5
78.4
81.8
85.8
78.3
79.6
83.5
87.6
79.1
80.9
85.0
89.0
85.9
85.9
85.8
86.0
86.9
86.8
86.7
87.2
87.8
87.7
87.7
88.4
88.5
88.5
88.4
89.5
48.9
60.8
70.7
80.2
50.1
62.8
73.2
83.1
51.3
64.7
75.7
85.6
52.4
66.5
78.0
88.0
95.8
95.7
95.6
95.5
96.8
96.8
96.7
96.6
97.7
97.6
97.5
97.5
98.5
98.5
98.4
98.3
34.0
46.0
55.8
65.6
34.5
47.0
57.5
67.8
34.7
48.0
59.0
70.0
35.0
49.0
60.5
72.1
74.1
74.7
77.9
81.7
74.9
76.0
79.6
83.5
75.7
77.3
81.2
85.1
76.4
78.7
82.6
86.6
62.2
73.2
77.9
81.7
64.3
75.5
79.6
83.5
66.4
77.3
81.2
85.1
68.3
78.7
82.6
86.6
83.0
83.0
82.9
83.3
84.0
83.8
83.8
84.5
84.8
84.7
84.7
85.6
85.4
85.3
85.4
86.8
2925
3150
3375
Table PD-12 — Gross Cooling Capacities SRVE-075 (Cont.)
English
Ambient Temperature (°F)
105
67
115
67
SHC TGC SHC TGC
Entering Wet Bulb Temperature (°F)
Ent.
DB
(ºF) TGC
61
73
61
73
CFM
2700
SHC
61.0
71.6
75.7
79.4
63.1
73.6
77.3
81.1
65.1
74.9
78.8
82.6
67.0
76.2
80.1
84.1
TGC SHC
TGC
SHC
45.2
57.0
66.9
75.7
46.3
58.9
69.3
78.0
47.5
60.7
71.7
79.9
48.5
62.5
73.8
81.3
TGC SHC
85.6 30.4
85.5 42.3
85.4 52.0
85.4 61.9
86.4 30.7
86.3 43.2
86.3 53.7
86.2 64.1
87.1 31.0
87.0 44.3
87.0 55.3
86.9 66.3
87.8 31.3
87.7 45.3
87.6 56.8
87.6 68.3
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90
71.3
72.3
75.7
79.4
72.2
73.7
77.3
81.1
72.9
74.9
78.8
82.6
73.6
76.2
80.1
84.1
80.0
79.9
79.8
80.5
80.9
80.8
80.8
81.6
81.6
81.5
81.5
82.8
82.3
82.2
82.3
84.0
46.4
58.3
68.2
77.4
47.7
60.3
70.7
79.9
48.8
62.1
73.0
82.2
49.9
63.9
75.3
84.0
89.1
89.0
88.9
88.9
90.0
89.9
89.9
89.8
90.8
90.7
90.6
90.5
91.5
91.4
91.4
91.3
31.7
43.6
53.3
63.2
32.0
44.5
55.0
65.4
32.2
45.6
56.6
67.5
32.5
46.5
58.1
69.6
68.5
69.9
73.4
76.9
69.3
71.2
74.8
78.5
70.0
72.5
76.2
79.9
70.7
73.7
77.5
81.3
59.7
69.6
73.4
76.9
61.7
71.2
74.8
78.5
63.7
72.5
76.2
79.9
65.5
73.7
77.5
81.3
76.9
76.7
76.7
77.5
77.6
77.5
77.6
78.7
78.3
78.2
78.3
79.9
78.9
78.9
79.1
81.3
2925
3150
3375
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
28
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-12 — Gross Cooling Capacities SRVE-075
Metric
Ambient Temperature (°C)
29.5
19.5
35.0
Entering Wet Bulb Temperature (°C)
23.0 16.0
Ent.
DB
16.0
SHC
19.5
23.0
m3/h (ºC) TGC
TGC SHC
TGC SHC TGC SHC TGC
SHC
14.0
17.5
20.3
23.1
14.3
18.0
21.1
23.9
14.7
18.6
21.8
24.6
15.0
19.1
22.5
25.3
TGC SHC
27.1
27.1 13.1
27.1 16.0
27.1 18.9
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
22.5
22.6
23.4
24.6
22.7
23.0
24.0
25.1
23.0
23.3
24.5
25.7
23.2
23.7
24.9
26.1
18.6
21.9
23.4
24.6
19.2
22.6
24.0
25.1
19.8
23.2
24.5
25.7
20.4
23.7
24.9
26.1
25.2
25.2
25.1
25.2
25.5
25.4
25.4
25.6
25.7
25.7
25.7
25.9
25.9
25.9
25.9
26.2
14.3
17.8
20.7
23.5
14.7
18.4
21.5
24.3
15.0
18.9
22.2
25.1
15.3
19.5
22.9
25.8
28.1
28.0
28.0
28.0
28.4
28.4
28.3
28.3
28.6
28.6
28.6
28.6
28.9
28.9
28.8
28.8
10.0
13.5
16.3
19.2
10.1
13.8
16.8
19.9
10.2
14.1
17.3
20.5
10.2
14.3
17.7
21.1
21.7
21.9
22.8
23.9
22.0
22.3
23.3
24.5
22.2
22.6
23.8
24.9
22.4
23.0
24.2
25.4
18.2
21.5
22.8
23.9
18.9
22.1
23.3
24.5
19.4
22.6
23.8
24.9
20.0
23.0
24.2
25.4
24.3
24.3
24.3
24.4
24.6
24.6
24.6
24.8
24.8
24.8
24.8
25.1
25.0
25.0
25.0
25.4
9.6
4590
4970
5355
5740
27.4
9.7
27.4 13.4
27.3 16.5
27.3 19.5
27.6
9.8
27.6 13.7
27.6 16.9
27.6 20.2
27.9
9.9
27.8 14.0
27.8 17.4
27.8 20.8
Table PD-12 — Gross Cooling Capacities SRVE-075 (Cont.)
Metric
Ambient Temperature (°C)
40.5
19.5
46
19.5
TGC SHC TGC SHC TGC
Entering Wet Bulb Temperature (°C)
Ent.
DB
16.0
23.0
16.0
23.0
m3/h (ºC) TGC
SHC
17.9
21.0
22.2
23.3
18.5
21.6
22.6
23.8
19.1
22.0
23.1
24.2
19.6
22.3
23.5
24.6
TGC SHC
SHC
13.2
16.7
19.6
22.2
13.6
17.3
20.3
22.9
13.9
17.8
21.0
23.4
14.2
18.3
21.6
23.8
TGC SHC
25.1
25.1 12.4
25.0 15.2
25.0 18.1
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
20.9
21.2
22.2
23.3
21.2
21.6
22.6
23.8
21.4
22.0
23.1
24.2
21.6
22.3
23.5
24.6
23.4
23.4
23.4
23.6
23.7
23.7
23.7
23.9
23.9
23.9
23.9
24.3
24.1
24.1
24.1
24.6
13.6
17.1
20.0
22.7
14.0
17.7
20.7
23.4
14.3
18.2
21.4
24.1
14.6
18.7
22.1
24.6
26.1
26.1
26.1
26.1
26.4
26.3
26.3
26.3
26.6
26.6
26.6
26.5
26.8
26.8
26.8
26.7
9.3
12.8
15.6
18.5
9.4
13.0
16.1
19.2
9.4
13.4
16.6
19.8
9.5
13.6
17.0
20.4
20.1
20.5
21.5
22.5
20.3
20.9
21.9
23.0
20.5
21.2
22.3
23.4
20.7
21.6
22.7
23.8
17.5
20.4
21.5
22.5
18.1
20.9
21.9
23.0
18.7
21.2
22.3
23.4
19.2
21.6
22.7
23.8
22.5
22.5
22.5
22.7
22.7
22.7
22.7
23.0
23.0
22.9
23.0
23.4
23.1
23.1
23.2
23.8
8.9
4590
4970
5355
25.3
9.0
25.3 12.7
25.3 15.7
25.3 18.8
25.5
9.1
25.5 13.0
25.5 16.2
25.5 19.4
25.7
9.2
5740
25.7 13.3
25.7 16.6
25.7 20.0
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
PKG-PRC007-EN
29
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-13 — Gross Cooling Capacities SRVE-100
English
Ambient Temperature (°F)
85
67
95
Entering Wet Bulb Temperature (°F)
73 61
Ent.
DB
61
SHC
67
73
CFM
3600
(ºF) TGC
75 107.1
80 107.7 102.8 119.9
85 111.1 111.1 119.9
TGC SHC
TGC
SHC TGC SHC TGC
45.5 103.8 85.1 116.3
62.0 104.4 100.9 116.2
75.6 108.3 108.3 116.1
SHC
TGC SHC
86.8 120.1
66.3 134.0
82.8 133.9
96.6 133.7
64.6 129.7 43.8
81.2 129.6 60.4
94.9 129.5 74.1
90 116.4 116.4 120.0 110.1 133.6
89.4 113.5 113.5 116.4 108.3 129.4 87.7
75 108.6
80 109.3 106.4 121.4
85 113.7 113.7 121.3 100.2 135.3
90 119.0 119.0 121.6 114.1 135.2
89.7 121.5
67.9 135.5
85.6 135.4
45.9 105.1
63.4 106.1 104.3 117.5
78.0 110.7 110.7 117.4
88.1 117.6
66.4 131.1 44.4
85.5 131.0 61.9
98.5 130.9 76.4
3900
4200
4500
92.5 116.1 116.1 118.0 112.3 130.8 90.9
75 109.8
80 110.9 109.4 122.6
85 116.0 116.0 122.5 103.6 136.6
90 121.5 121.5 123.3 117.9 136.5
75 110.7
92.5 122.7
69.5 136.8
88.2 136.7
46.3 106.2
64.9 107.8 107.1 118.7
80.2 113.0 113.0 118.6 101.9 132.1 79.1
95.5 118.5 118.5 119.6 116.0 132.0 94.0
46.8 107.1
90.9 118.8
68.0 132.3 44.7
86.5 132.2 63.3
95.4 123.8
71.2 138.0
90.7 137.8
93.6 119.9
69.5 133.4 45.1
89.1 133.3 64.6
80 112.6 112.2 123.7
66.3 109.4 109.4 119.8
85 118.0 118.0 123.7 106.9 137.7
90 123.8 123.8 124.8 121.4 137.6
82.4 115.0 115.0 119.7 105.2 133.2 80.8
98.4 120.7 120.7 121.2 119.4 133.1 96.9
Table PD-13 — Gross Cooling Capacities SRVE-100 (Cont.)
English
Ambient Temperature (°F)
105
67
115
67
Entering Wet Bulb Temperature (°F)
73 61
Ent.
DB
(ºF) TGC
75 100.4
80 101.2
61
SHC
73
CFM
3600
TGC SHC
83.5 112.4
99.0 112.3
TGC
SHC TGC SHC TGC
SHC
TGC SHC
63.0 125.2
79.6 125.1
93.3 125.0
42.2
58.8
96.9
97.9
81.9 108.2
96.8 108.1
72.5 102.4 102.4 108.0
61.3 120.2 40.4
77.8 120.1 57.0
91.6 120.0 70.6
85 105.4 105.4 112.2
90 110.5 110.5 112.6 106.4 124.9
86.1 107.3 107.3 108.7 104.3 119.9 84.3
75 101.6
80 102.9 102.0 113.5
85 107.8 107.8 113.5
86.4 113.6
64.6 126.4
82.3 126.3
96.9 126.2
42.6
60.2
97.9
99.6
84.8 109.3
99.5 109.2
62.9 121.4 40.9
80.6 121.3 58.4
95.0 121.2 72.9
3900
4200
74.8 104.5 104.5 109.2
90 112.9 112.9 114.2 110.3
83.0
89.3 109.5 109.5 110.3 107.9 121.1 87.4
75 102.6
80 104.6 104.5 114.6
89.3 114.7
66.3 127.6
84.9 127.5
43.1
98.9
87.5 110.3
64.5 122.4 41.2
83.1 122.3 59.7
98.4 122.2 75.1
61.6 101.5 101.5 110.2
77.0 106.5 106.5 110.2
85 109.9 109.9 114.6 100.3 127.4
90 115.2 115.2 115.9 113.7 127.3
92.2 111.6 111.6 111.8 111.1 122.1 90.4
75 103.6
80 106.4 106.4 115.5
92.0 115.6
67.8 128.6
87.4 128.5
43.5
99.8
90.3 111.2
66.1 123.3 41.6
85.6 123.2 61.0
4500
62.9 103.1 103.1 111.1
85 111.8 111.8 115.6 103.4 128.4
90 117.3 117.3 117.4 116.6 128.3
79.1 108.3 108.3 111.2 101.6 123.1 77.3
95.2 113.6 113.6 113.5 113.5 123.0 93.3
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
30
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-13 — Gross Cooling Capacities SRVE-100
Metric
Ambient Temperature (°C)
29.5
19.5
35.0
Entering Wet Bulb Temperature (°C)
23.0 16.0
Ent.
DB
16.0
19.5
23.0
m3/h (ºC) TGC
SHC
25.4
30.1
32.5
34.1
26.3
31.2
33.3
34.9
27.1
32.1
34.0
35.6
27.9
32.9
34.6
36.3
TGC SHC
TGC SHC TGC SHC TGC
SHC
18.9
23.8
27.8
31.7
19.4
25.1
28.9
32.9
19.9
25.4
29.9
34.0
20.4
26.1
30.8
35.0
TGC SHC
38.0 12.8
38.0 17.7
37.9 21.7
37.9 25.7
38.4 13.0
38.4 18.1
38.4 22.4
38.3 26.6
38.8 13.1
38.7 18.6
38.7 23.2
38.7 27.5
39.1 13.2
39.1 18.9
39.0 23.7
39.0 28.4
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
31.4
31.6
32.5
34.1
31.8
32.0
33.3
34.9
32.2
32.5
34.0
35.6
32.4
33.0
34.6
36.3
35.2
35.1
35.1
35.2
35.6
35.6
35.5
35.6
36.0
35.9
35.9
36.1
36.3
36.2
36.2
36.6
19.4
24.3
28.3
32.3
19.9
25.1
29.4
33.4
20.4
25.8
30.3
34.6
20.9
26.6
31.3
35.6
39.3
39.2
39.2
39.2
39.7
39.7
39.6
39.6
40.1
40.0
40.0
40.0
40.4
40.4
40.3
40.3
13.3
18.2
22.2
26.2
13.4
18.6
22.9
27.1
13.6
19.0
23.5
28.0
13.7
19.4
24.1
28.8
30.4
30.6
31.7
33.2
30.8
31.1
32.4
34.0
31.1
31.6
33.1
34.7
31.4
32.1
33.7
35.4
24.9
29.6
31.7
33.2
25.8
30.6
32.4
34.0
26.6
31.4
33.1
34.7
27.4
32.1
33.7
35.4
34.1
34.0
34.0
34.1
34.5
34.4
34.4
34.6
34.8
34.8
34.7
35.0
35.1
35.1
35.1
35.5
6120
6630
7140
7650
Table PD-13 — Gross Cooling Capacities SRVE-100 (Cont.)
Metric
Ambient Temperature (°C)
40.5
19.5
46
19.5
TGC SHC TGC SHC TGC
Entering Wet Bulb Temperature (°C)
Ent.
DB
16.0
SHC
23.0
16.0
23.0
m3/h (ºC) TGC
TGC SHC
SHC
17.9
22.8
26.8
30.6
18.4
23.6
27.8
31.6
18.9
24.3
28.8
32.5
19.4
25.1
29.8
33.2
TGC SHC
35.2 11.8
35.2 16.7
35.2 20.7
35.1 24.7
35.6 12.0
35.5 17.1
35.5 21.4
35.5 25.6
35.9 12.1
35.8 17.5
35.8 22.0
35.8 26.5
36.1 12.2
36.1 17.9
36.1 22.6
36.0 27.3
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
29.4
29.6
30.9
32.4
29.8
30.1
31.6
33.1
30.1
30.7
32.2
33.8
30.3
31.2
32.8
34.4
24.5
29.0
30.9
32.4
25.3
29.9
31.6
33.1
26.2
30.6
32.2
33.8
27.0
31.2
32.8
34.4
32.9
32.9
32.9
33.0
33.3
33.2
33.2
33.5
33.6
33.6
33.6
33.9
33.9
33.9
33.9
34.4
18.5
23.3
27.3
31.2
18.9
24.1
28.4
32.3
19.4
24.9
29.4
33.3
19.9
25.6
30.3
34.2
36.7
36.7
36.6
36.6
37.0
37.0
37.0
24.3
37.4
37.4
37.3
37.3
37.7
37.7
37.6
37.6
12.4
17.2
21.2
25.2
12.5
17.6
21.9
26.2
12.6
18.0
22.5
27.0
12.7
18.4
23.2
27.9
28.4
28.7
30.0
31.4
28.7
29.2
30.6
32.1
29.0
29.7
31.2
32.7
29.3
30.2
31.7
33.3
24.0
28.4
30.0
31.4
24.8
29.2
30.6
32.1
25.6
29.7
31.2
32.7
26.4
30.2
31.7
33.3
31.7
31.7
31.6
31.8
32.0
32.0
32.0
32.3
32.3
32.3
32.3
32.8
32.6
32.5
32.6
33.2
6120
6630
7140
7650
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
PKG-PRC007-EN
31
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-14 — Gross Cooling Capacities SRVE-125
English
Ambient Temperature (°F)
85
67
95
Entering Wet Bulb Temperature (°F)
73 61
Ent.
DB
61
SHC
67
73
CFM
4500
(ºF) TGC
75 131.7 108.3 147.0
TGC SHC
TGC
83.5 163.7
SHC TGC SHC TGC
58.2 127.4 110.5 142.3
SHC
TGC SHC
81.5 158.2 56.2
80 132.4 127.7 146.9 103.7 163.5
85 137.0 137.0 146.8 120.4 163.2
78.2 128.3 125.2 142.1 101.5 158.0 76.4
95.0 133.5 133.5 141.9 118.4 157.9 93.1
90 143.3 143.3 147.1 136.5 163.1 111.6 139.6 139.6 142.5 134.2 157.7 109.6
75 133.3 112.0 148.8 85.5 165.3 58.7 128.9 109.9 143.7 83.4 159.7 56.7
4875
5250
5625
80 134.5 131.9 148.6 107.0 165.1
85 140.0 140.0 148.5 124.7 165.0
90 146.6 146.6 149.1 141.5 164.9 115.4 142.7 142.7 144.5 139.1 159.4 113.4
75 134.7 115.5 150.2 87.6 166.8 59.3 130.2 113.3 145.2 85.5 161.2 57.2
80 136.5 135.4 150.1 110.0 166.7 81.8 132.6 132.2 145.0 108.0 161.0 79.7
80.1 130.4 129.1 143.6 104.8 159.6 78.1
97.7 136.3 136.3 143.5 122.6 159.5 95.7
85 142.8 142.8 149.9 128.8 166.5 100.5 138.9 138.9 145.0 126.8 160.9 98.5
90 149.5 149.5 151.1 146.0 166.4 119.1 145.4 145.4 146.4 143.2 160.8 117.1
75 135.9 118.8 151.6
89.5 168.2
59.8 131.3 116.7 146.4
87.3 162.5 57.8
80 138.5 138.3 151.4 113.2 168.0
83.5 134.6 134.6 146.2 111.2 162.3 81.5
85 145.2 145.2 151.4 132.8 167.9 103.1 141.2 141.2 146.3 130.7 162.2 101.1
90 152.1 152.1 153.0 150.0 167.8 123.1 148.0 148.0 148.4 147.0 162.1 120.6
Table PD-14 — Gross Cooling Capacities SRVE-125 (Cont.)
English
Ambient Temperature (°F)
105
67
115
67
Entering Wet Bulb Temperature (°F)
73 61
Ent.
DB
(ºF) TGC
61
SHC
73
CFM
4500
TGC SHC
75 122.9 104.3 137.3
80 124.2 122.4 137.1
TGC
79.3 152.5
99.5 152.3
SHC TGC SHC TGC
54.2 118.3 102.1 131.9
74.3 120.0 119.4 131.8
SHC
TGC SHC
77.3 146.5 52.0
97.3 146.4 72.1
85 129.6 129.6 137.0 116.2 152.2
90 135.7 135.7 137.7 131.8 152.1 107.5 131.5 131.5 132.8 129.0 146.2 105.4
75 124.2 107.8 138.5 81.4 154.0 54.7 119.6 105.6 133.1 79.2 147.9 52.6
90.8 125.6 125.6 131.7 114.1 146.2 88.8
4875
5250
80 126.2 125.8 138.5 102.8 153.8
85 132.3 132.3 138.3 120.4 153.7
90 138.5 138.5 139.7 136.6 153.6 111.3 134.3 134.3 134.7 133.1 147.4 109.2
75 125.5 111.2 139.8 83.3 155.3 55.2 120.6 108.9 134.4 81.2 149.0 53.0
80 128.5 128.4 139.8 106.0 155.1
85 134.8 134.8 139.8 124.6 155.0
76.1 122.2 122.1 133.1 100.6 147.7 73.9
93.7 128.2 128.2 133.1 118.2 147.7 91.6
77.7 124.3 124.3 134.3 103.8 148.9 75.6
96.5 130.5 130.5 134.4 122.2 148.7 94.2
90 141.2 141.2 141.7 140.2 155.0 114.9 136.8 136.8 136.8 136.3 148.7 112.8
75 126.6 114.5 141.0 85.2 156.5 55.7 121.7 112.0 135.4 83.0 150.1 53.5
5625
80 130.6 130.6 140.9 109.0 156.2
85 137.1 137.1 141.0 128.4 156.2
79.3 126.5 126.5 135.4 106.7 150.0 77.2
98.9 132.7 132.7 135.6 125.9 149.9 96.8
90 143.6 143.6 143.7 143.2 156.0 118.5 139.1 139.1 139.1 139.0 149.7 116.3
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
32
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-14 — Gross Cooling Capacities SRVE-125
Metric
Ambient Temperature (°C)
29.5
19.5
35.0
Entering Wet Bulb Temperature (°C)
23.0 16.0
Ent.
DB
16.0
19.5
23.0
m3/h (ºC) TGC
SHC
31.7
37.4
40.1
42.0
32.8
38.6
41.0
43.0
33.9
39.7
41.8
43.8
34.8
40.5
42.5
44.6
TGC SHC
TGC SHC TGC SHC TGC
SHC
23.9
29.8
34.7
39.3
24.4
30.7
35.9
40.7
25.1
31.6
37.1
42.0
25.6
32.6
38.3
43.1
TGC SHC
46.3 16.5
46.3 22.4
46.3 27.3
46.2 32.1
46.8 16.6
46.8 22.9
46.7 28.0
46.7 33.2
47.2 16.8
47.2 23.4
47.1 28.9
47.1 34.3
47.6 16.9
47.5 23.9
47.5 29.6
47.5 35.3
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
38.6
38.8
40.1
42.0
39.1
39.4
41.0
43.0
39.5
40.0
41.8
43.8
39.8
40.6
42.5
44.6
43.1
43.0
43.0
43.1
43.6
43.5
43.5
43.7
44.0
44.0
43.9
44.3
44.4
44.4
44.4
44.8
24.5
30.4
35.3
40.0
25.1
31.3
36.5
41.5
25.7
32.2
37.7
42.8
26.2
33.2
38.9
43.9
48.0
47.9
47.8
47.8
48.4
48.4
48.4
48.3
48.9
48.9
48.8
48.8
49.3
49.2
49.2
49.2
17.1
22.9
27.8
32.7
17.2
23.5
28.6
33.8
17.4
24.0
29.4
34.9
17.5
24.5
30.2
36.1
37.3
37.6
39.1
40.9
37.8
38.2
39.9
41.8
38.1
38.9
40.7
42.6
38.5
39.4
41.4
43.4
32.4
36.7
39.1
40.9
32.2
37.8
39.9
41.8
33.2
38.7
40.7
42.6
34.2
39.4
41.4
43.4
41.7
41.6
41.6
41.7
42.1
42.1
42.1
42.3
42.5
42.5
42.5
42.9
42.9
42.8
42.9
43.5
7650
8285
8920
9560
Table PD-14 — Gross Cooling Capacities SRVE-125 (Cont.)
Metric
Ambient Temperature (°C)
40.5
19.5
46
19.5
TGC SHC TGC SHC TGC
Entering Wet Bulb Temperature (°C)
Ent.
DB
16.0
23.0
16.0
23.0
m3/h (ºC) TGC
SHC
30.6
35.9
38.0
39.8
31.6
36.9
38.8
40.6
32.6
37.6
39.5
41.4
33.5
38.3
40.2
42.1
TGC SHC
SHC
22.6
28.5
33.4
37.8
23.2
29.5
34.6
39.0
23.8
30.4
35.8
39.9
24.3
31.3
36.9
40.7
TGC SHC
42.9 15.2
42.9 21.1
42.8 26.0
42.8 30.9
43.3 15.4
43.3 21.6
43.3 26.8
43.2 32.0
43.7 15.5
43.6 22.1
43.6 27.6
43.6 33.0
44.0 15.7
43.9 22.6
43.9 28.4
43.9 34.1
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
36.0
36.4
38.0
39.8
36.4
37.0
38.8
40.6
36.8
37.6
39.5
41.4
37.1
38.3
40.2
42.1
40.2
40.2
40.1
40.3
40.6
40.6
40.5
40.9
41.0
41.0
41.0
41.5
41.3
41.3
41.3
42.1
23.2
29.2
34.0
38.6
23.9
30.1
35.3
40.0
24.4
31.1
36.5
41.1
25.0
31.9
37.6
42.0
44.7
44.6
44.6
44.6
45.1
45.1
45.0
45.0
45.5
45.4
45.4
45.4
45.8
45.8
45.8
45.7
15.9
21.8
26.6
31.5
16.0
22.3
27.5
32.6
16.2
22.8
28.3
33.7
16.3
23.2
29.0
34.7
34.7
35.2
36.8
38.5
35.0
35.8
37.5
39.3
35.3
36.4
38.2
40.1
35.7
37.1
38.9
40.7
29.9
35.0
36.8
38.5
30.9
35.8
37.5
39.3
31.9
36.4
38.2
40.1
32.8
37.1
38.9
40.7
38.6
38.6
38.6
38.9
39.0
39.0
39.0
39.5
39.4
39.3
39.4
40.1
39.7
39.7
39.7
40.7
7650
8285
8920
9560
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
PKG-PRC007-EN
33
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-15 — Gross Cooling Capacities SRVE-150
English
Ambient Temperature (°F)
85
67
95
Entering Wet Bulb Temperature (°F)
73 61
Ent.
DB
(ºF) TGC
61
SHC
67
73
CFM
5400
TGC SHC
TGC
SHC TGC SHC TGC
SHC
TGC SHC
75 161.0 135.9 179.6 102.9 199.5
80 163.6 159.3 179.5 129.6 199.4
69.6 155.3 133.2 173.1 100.3 192.3 67.0
96.2 158.5 155.3 172.9 127.0 192.1 93.6
85 171.2 168.0 179.5 151.7 199.2 118.2 166.2 163.1 173.1 149.0 191.9 115.8
90 179.2 175.9 181.2 171.8 199.1 140.3 174.2 170.9 175.2 168.4 191.9 137.7
75 162.9 140.7 181.5 105.7 201.5
80 166.6 163.5 181.3 134.2 201.3
85 174.9 171.6 181.5 157.5 201.2 122.1 169.7 166.5 175.0 154.6 193.8 119.5
90 183.2 179.7 184.0 177.7 201.1 145.5 177.9 174.5 178.1 173.8 193.7 142.9
70.2 157.1 138.0 174.8 103.1 194.1 67.7
98.6 161.7 158.6 174.7 131.5 194.0 96.0
5850
6300
6750
75 164.6 145.3 183.2 108.4 203.2
70.9 158.7 142.5 176.4 105.8 195.7 68.3
80 169.8 166.6 183.0 138.4 203.1 100.9 164.6 161.5 176.2 135.8 195.6 98.4
85 178.2 174.8 183.4 163.0 202.9 125.8 172.9 169.6 176.9 160.1 195.4 123.2
90 186.8 183.2 186.9 182.6 202.8 150.6 181.2 177.7 181.2 177.7 195.3 148.0
75 166.2 149.7 184.5 111.0 204.8
71.6 160.3 146.7 177.8 108.4 197.1 69.0
80 172.6 169.3 184.4 142.7 204.6 103.2 167.3 164.1 177.6 140.1 196.9 100.6
85 181.3 177.8 185.2 168.1 204.5 129.4 175.7 172.4 178.6 165.0 196.7 126.9
90 190.0 186.4 189.8 186.3 204.3 155.6 184.2 180.8 184.1 180.6 196.6 153.0
Table PD-15 — Gross Cooling Capacities SRVE-150 (Cont.)
English
Ambient Temperature (°F)
105
67
115
67
Entering Wet Bulb Temperature (°F)
73 61
Ent.
61
73
DB
CFM
5400
(ºF) TGC
SHC
TGC
SHC TGC
97.7 184.8
80 153.4 150.5 166.2 124.3 184.5
SHC TGC SHC TGC
64.4 143.1 127.4 159.3
91.0 148.0 145.2 159.2 121.6 176.8 88.4
SHC
TGC SHC
75 149.2 130.4 166.3
94.8 177.0 61.8
85 161.0 158.0 166.4 146.1 184.4 113.0 155.5 152.6 159.6 143.1 176.7 110.4
90 168.8 165.6 169.1 164.5 184.3 135.1 163.0 160.0 162.9 159.8 176.6 132.4
75 150.9 135.1 167.9 100.4 186.5
80 156.5 153.5 167.8 128.8 186.2
85 164.3 161.2 168.3 151.6 186.1 116.9 158.6 155.6 161.5 148.5 178.2 114.2
90 172.3 169.0 172.1 168.9 186.0 140.3 166.3 163.2 166.2 163.1 178.1 137.6
75 152.5 139.5 169.4 103.1 187.9
80 159.2 156.2 169.2 133.1 187.7
65.1 144.7 132.0 161.3
93.4 150.9 148.1 160.7 126.0 178.4 90.8
97.7 178.5 62.4
5850
6300
65.7 146.3 136.1 162.1 100.3 179.9 63.1
95.8 153.6 150.7 162.0 130.3 179.7 93.1
85 167.3 164.1 170.1 156.8 187.6 120.6 161.4 158.4 163.2 153.4 179.6 117.9
90 175.4 172.1 175.3 172.0 187.5 145.4 169.4 166.2 169.3 166.1 179.5 142.7
75 154.0 143.5 170.7 105.7 189.2
80 161.8 158.7 170.4 137.3 189.0
66.4 147.7 140.0 163.2 102.9 181.0 63.8
98.0 155.9 153.0 163.1 134.5 180.8 95.3
6750
85 170.0 166.8 171.8 161.6 188.9 124.2 164.0 160.9 164.9 157.9 180.7 121.5
90 178.3 174.9 178.2 174.8 188.8 150.3 172.0 168.8 172.0 168.8 180.7 147.5
Notes:
TGC = Total Gross Capacity (MBh)
SHC = Sensible Heat Capacity (MBh)
34
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Performance
Data
Air Cooled
60 Hz
Table PD-15 — Gross Cooling Capacities SRVE-150
Metric
Ambient Temperature (°C)
29.5
19.5
35.0
Entering Wet Bulb Temperature (°C)
23.0 16.0
Ent.
DB
16.0
19.5
23.0
m3/h (ºC) TGC
SHC
39.8
46.7
49.2
51.5
41.2
47.9
50.3
52.7
42.6
48.8
51.2
53.7
43.8
49.6
52.1
54.6
TGC SHC
TGC SHC TGC SHC TGC
SHC
29.4
37.2
43.7
49.3
30.2
38.5
45.3
50.9
31.0
39.8
46.9
52.1
31.8
41.0
48.4
52.9
TGC SHC
56.3 19.6
56.3 27.4
56.2 33.9
56.2 40.3
56.9 19.8
56.8 28.1
56.8 35.0
56.7 41.9
57.3 20.0
57.3 28.8
57.2 36.1
57.2 43.4
57.7 20.2
57.7 29.5
57.6 37.2
57.6 44.8
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
47.2
47.9
50.2
52.5
47.7
48.8
51.2
53.7
48.2
49.8
52.2
54.7
48.7
50.6
53.1
55.7
52.6
52.6
52.6
53.1
53.2
53.1
53.2
53.9
53.7
53.6
53.7
54.8
54.1
54.0
54.3
55.6
30.1
38.0
44.5
50.3
31.0
39.3
46.1
52.1
31.8
40.6
47.7
53.5
32.5
41.8
49.2
54.6
58.5
58.4
58.4
58.3
59.0
59.0
58.9
58.9
59.5
59.5
59.4
59.4
60.0
59.9
59.9
59.8
20.4
28.2
34.6
41.1
20.6
28.9
35.8
42.6
20.8
29.6
36.9
44.1
21.0
30.2
37.9
45.6
45.5
46.4
48.7
51.0
46.0
47.4
49.7
52.1
46.5
48.2
50.7
53.1
47.0
49.0
51.5
54.0
39.0
45.5
47.8
50.1
40.4
46.5
48.8
51.1
41.7
47.3
49.7
52.1
43.0
48.1
50.5
53.0
50.7
50.7
50.7
51.3
51.2
51.2
51.3
52.2
51.7
51.6
51.8
53.1
52.1
52.0
52.3
53.9
9180
9945
10710
11475
Table PD-15 — Gross Cooling Capacities SRVE-150 (Cont.)
Metric
Ambient Temperature (°C)
40.5
19.5
46
19.5
TGC SHC TGC SHC TGC
Entering Wet Bulb Temperature (°C)
Ent.
DB
16.0
23.0
16.0
23.0
m3/h (ºC) TGC
SHC
38.2
44.1
46.3
48.5
39.6
45.0
47.2
49.5
40.9
45.8
48.1
50.4
42.1
46.5
48.9
51.3
TGC SHC
SHC
27.8
35.6
41.9
46.8
28.6
36.9
43.5
47.8
29.4
38.2
44.9
48.7
30.1
39.4
46.3
49.5
TGC SHC
51.9 18.1
51.8 25.9
51.8 32.4
51.7 38.8
52.3 18.3
52.3 26.6
52.2 33.5
52.2 40.3
52.7 18.5
52.6 27.3
52.6 34.6
52.6 41.8
53.0 18.7
53.0 27.9
53.0 35.6
53.0 43.2
24
27
29
32
24
27
29
32
24
27
29
32
24
27
29
32
43.7
44.9
47.2
49.4
44.2
45.8
48.1
50.5
44.7
46.6
49.0
51.4
45.1
47.4
49.8
52.2
48.7
48.7
48.8
49.5
49.2
49.2
49.3
50.4
49.6
49.6
49.8
51.4
50.0
49.9
50.3
52.2
28.6
36.4
42.8
48.2
29.4
37.7
44.4
49.5
30.2
39.0
46.0
50.4
31.0
40.2
47.4
51.2
54.1
54.1
54.0
54.0
54.6
54.6
54.5
54.5
55.1
55.0
55.0
54.9
55.4
55.4
55.3
55.3
18.9
26.7
33.1
39.6
19.1
27.4
34.3
41.1
19.3
28.1
35.3
42.6
19.4
28.7
36.4
44.0
41.9
43.4
45.6
47.8
42.4
44.2
46.5
48.7
42.9
45.0
47.3
49.6
43.3
45.7
48.0
50.4
37.3
42.5
44.7
46.9
38.7
43.4
45.6
47.8
39.9
44.2
46.4
48.7
41.0
44.8
47.1
49.5
46.7
46.6
46.8
47.7
47.3
47.1
47.3
48.7
47.5
47.5
47.8
49.6
47.8
47.8
48.3
50.4
9180
9945
10710
11475
Notes:
TGC = Total Gross Capacity (kW)
SHC = Sensible Heat Capacity (kW)
PKG-PRC007-EN
35
Download from Www.Somanuals.com. All Manuals Search And Download.
Controls
The Genius line offers two Control
options: Standard Thermostat or
Microprocessor Control.
Demand limit: Automatically controls
the programmed electricity
consumption limits of the setup. This is
an important economic factor that
makes the cost of the TRACKER
insignificant when considered on an
annual scale.
so that the degree of wear will be similar
for each one.
The microprocessor control provides the
option for simple and direct
communication between the Genius and
TRACKER, Tracer or Tracer Summit
building administrators. This
communication is achieved simply by
interconnecting the Genius unit and the
building administration system with a
twisted pair cable.
Standard Thermostat
All units are supplied with a control
thermostat as standard feature. This
thermostat can be installed remotely or
in the equipment, according to the needs
of the client.
Record of tendencies: Records up to 192
temperature values during a time frame
that you determine. This function makes
it possible to do a posterior analysis of
the system’s performance.
Microprocessor Control
The Microprocessor Control UCP (unit
control processor) is factory assembled
and tested. It controls unit operation in
the independent mode (standalone) or it
allows communication when the unit is
working in an integrated comfort system
(Tracer, Tracer Summit, Tracker).
TRACKER
Record of alarms: The TRACKER
immediately identifies any breakdowns
in the system, which register as alarms.
Besides this, the TRACKER store in its
memory up to 32 alarms with
information including the date and time
of the event.
In addition to being able to control the
lighting of your house or building, this
panel can automatically control up to 12
Genius. It also allows sending air
conditioning system alarms to a
Maintenance Central 24 hours a day,
thus making possible various functions:
Some of the main advantages and
benefits of using the microprocessor are:
Access via telephone line: The TRACKER
can be programmed and supervised
through the telephone line. It can also, in
the same way, send warnings
Schedule programming: On the
TRACKER you do the annual operating
programming of each one of the
interconnected sets of equipment with
the possibility of setting two different
schedules for the initiation and
termination of operation for weekdays,
weekends and holidays. The objective is
to use the equipment only when
necessary. There is no need for you to
waste energy.
Great reliability: As we know, this type of
control has demonstrated itself to be
highly reliable, thus avoiding
decalibration or breakdown.
concerning any alarms.
Direct digital control: The Integral
Proportional Control allows more precise
temperature control of the area to be air-
conditioned. In addition, the temperature
sensing instrument is more sensitive
than the one used in traditional cases.
With this instrument joined to the UCP it
is possible to guarantee a setpoint
temperature of + - 0.5F.
Easy installation: The Genius and the
TRACKER leave the factory already
programmed and tested. Installation and
connection between them is done with a
twisted pair.
For more details, consult the TRACKER
Engineering Bulletin.
Interface with the operator: The
TRACKER has a functional keyboard and
liquid crystal display that provides the
user with a rapid visualization of the
system with a minimum of experience.
Access is restricted with a safety
password.
TRACER SUMMIT
This is the controller recommended for
very large installations. The Genius’s
microprocessor is also able to
communicate with the Tracer Summit
which provides complete integration of
these units with the Integrated Comfort
System.
Easy diagnosis: The controller allows the
operator to carry out easy and fast test to
verify the operation of the unit
components (fans and compressors).
Low suction pressure during start-up:
The controller ignores the low
Zoning: When a variable air volume
system is controlled, it is capable of
independently controlling the
temperature of up to 128 different zones,
thus optimizing the dimensions of your
equipment as well as your investment.
pressurestat information during
compressor start-up, thus avoiding that
the unit not start because of the low
pressure. If after 3 minutes the low
pressure is not within the correct range,
the unit will deactivate.
Varitrac is the name Trane has given to
our variable air volume system for small
installations. Airflow through the Genius
is constant while the air supply to each
zone is variable. So that this will happen,
a bypass gate returns airflow that was
not required by the zones to the system.
The variable air input in each zone is
controlled by a VAV box that includes a
microprocessor controller. This
Optimized start-up: The TRACKER
analyzes the most economical way to
turn on the equipment so that you get
the desired temperature at the
programmed time. This is applicable in
setups where various Genius units are
interconnected to the control system
and, instead of turning on all of them at
the same time, they are turned on at
different times to avoid peaks in energy
consumption.
Elimination of Compressor cycling: The
controller allows the compressor to run
for a minimum of three minutes,
followed by three minutes not running
(off) to make sure that there is adequate
oil return to the compressor(s).
controller regulates the amount of air
needed to maintain the desired
Alternation of Compressor operation:
The microprocessor will alternate the
compressors according to the number of
start-ups and hours of operation of each,
temperature. A panel called the Central
Control Panel (CCP) is used to program,
supervise and control the Varitrac
system. Trane personnel can program
the TRACKER and the CCP.
36
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Each unit model has three options for
electric heat.
The following table shows the options
and their capacities in kW.
Model
5 Ton
2 kW
4 kW
6 kW
7.5 Ton
3 kW
6 kW
10 Ton
4 kW
8 kW
2x6 kW
12.5 Ton
5 kW
2x5 kW
15 Ton
6 kW
2x6 kW
Option 1
Option 2
Option 3
9 kW
2x8 kW
2x9 kW
Table ED-1 — Genius – Electrical Features - SRVE/SIVE 050
Nominal Operation Values
Compressor
Fan Motor
KW
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
15.40
8.92
CNO
3.04
1.76
1.52
4.14
2.39
2.07
1.80
1.04
0.90
KW
CNO
3.04
1.76
1.52
3.04
1.76
1.52
3.04
1.76
1.52
STD
and
21.48
12.44
10.74
22.58
13.07
11.29
20.24
11.72
10.12
4.74
0.83
1.22
0.45
0.83
0.83
0.83
6.40
6.79
6.02
Option 1
7.70
15.40
8.92
7.70
15.40
Option 2
4.74
4.74
Plenum Box
Option
8.92
7.70
Maximum Operation Values
Compressor
CMO
19.90
11.52
9.95
Fan Motor
CMO
3.80
2.19
1.90
5.18
2.99
1.13
2.25
Fan Motor
CMO
3.80
2.19
1.90
3.80
2.19
1.90
3.80
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
STD
and
27.50
15.90
13.75
28.88
16.70
12.98
25.95
15.01
12.98
Option 1
19.90
11.52
9.95
19.90
11.52
9.95
Option 2
Plenum Box
Option
1.30
1.13
2.19
1.90
Start-up Values
Compressor
Fan Motor
LRA
19.00
11.00
9.50
28.60
16.56
14.30
9.90
Fan Motor
LRA
19.00
11.00
9.50
19.00
11.00
9.50
19.00
11.00
9.50
Fan
STD
and
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
Option 1
Option 2
Plenum Box
Option
5.73
4.95
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option and Option 1 - evaporator fan motor -1 CV.
Option 2 - evaporator fan motor -1.5 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Power of the condenser fan motor -1 CV.
Size the electrical wiring using the maximum operation currents.
PKG-PRC007-EN
37
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-2 — Genius – Electrical Features - SRVE/SIVE 050
Nominal Operation Values
Compressor
Fan Motor
KW
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
18.60
10.77
9.30
CNO
4.14
2.39
2.07
5.53
3.19
2.76
7.32
4.23
3.66
7.32
1.04
0.90
KW
CNO
7.32
4.23
3.65
7.32
4.23
3.65
7.32
4.23
3.65
7.32
4.23
3.65
30.06
17.39
15.02
31.45
18.19
15.71
33.24
19.23
16.61
33.24
16.04
13.85
STD
6.39
6.39
6.39
6.39
1.22
1.64
2.23
0.45
2.23
9.84
10.26
10.85
9.07
18.60
10.77
9.30
18.60
10.77
9.30
Option 1
Option 2
2.23
2.23
2.23
Plenum Box
Option
18.60
10.77
9.30
Maximum Operation Values
Compressor
CMO
Fan Motor
CMO
5.18
2.99
2.59
6.91
3.99
3.46
9.15
5.28
4.58
2.25
1.30
Fan Motor
CMO
9.15
5.28
4.58
9.15
5.28
4.58
9.15
5.28
4.58
9.15
5.28
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
39.32
22.73
19.66
41.04
23.73
20.52
43.28
25.02
21.64
36.38
21.04
18.19
STD
Option 1
Option 2
Plenum Box
Option
1.13
4.58
Start-up Values
Compressor
Fan Motor
Fan Motor
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
LRA
30.92
17.85
15.46
48.36
27.92
24.18
60.45
34.90
30.23
11.25
6.50
LRA
60.45
34.90
30.23
60.45
34.90
30.23
60.45
34.90
30.23
60.45
34.90
30.23
STD
Option 1
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -1.5 CV.
Option 1 - evaporator fan motor -2 CV.
Option 2 - evaporator fan motor -3 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Power of the condenser fan motor -3 CV.
Size the electrical wiring using the maximum operation currents.
38
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-3 — Genius – Electrical Features - SRVE/SIVE 100
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
KW
CNO
15.40
8.92
7.70
15.40
8.92
7.70
15.40
8.92
7.70
15.40
8.92
7.70
KW
CNO
KW
CNO
15.40
8.92
7.70
15.40
8.92
7.70
15.40
8.92
7.70
15.40
8.92
7.70
4.14
2.39
2.07
5.53
3.19
2.76
7.32
4.23
3.66
1.80
1.04
0.90
7.32
4.23
3.65
7.32
4.23
3.65
7.32
4.23
3.65
7.32
4.23
3.65
42.26
24.46
21.12
43.65
25.26
21.81
45.44
26.30
22.71
39.92
23.11
19.95
STD
4.74
4.74
1.22
2.23
12.93
13.35
13.94
12.16
Option 1
Option 2
4.74
4.74
4.74
4.74
4.74
4.74
1.64
2.23
0.45
2.23
2.23
2.23
Plenum Box
Option
Maximum Operation Values
Compressor 1
CMO
19.90
11.52
9.95
Compressor 2
CMO
19.90
11.52
9.95
Fan Motor
Fan Motor
CMO
9.15
5.28
4.58
9.15
5.28
4.58
9.15
5.28
4.58
9.15
5.28
Current
A
Fan
Voltage
CMO
5.18
2.99
2.59
6.91
3.99
3.46
9.15
5.28
4.58
2.25
1.30
1.13
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
54.13
31.31
27.06
55.86
32.31
27.93
58.10
33.60
29.05
51.20
29.62
25.60
STD
19.90
11.52
9.95
19.90
11.52
9.95
19.90
11.52
9.95
19.90
11.52
9.95
19.90
11.52
9.95
19.90
11.52
9.95
Option 1
Option 2
Plenum Box
Option
4.58
Start-up Values
Compressor 1
LRA
Compressor 2
Fan Motor
LRA
Fan Motor
LRA
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
128.00
74.10
64.00
30.92
17.85
15.46
48.36
27.92
24.18
60.45
34.90
30.23
11.25
6.50
60.45
34.90
30.23
60.45
34.90
30.23
60.45
34.90
30.23
60.45
34.90
30.23
STD
Option 1
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -1.5 CV.
Option 1 - evaporator fan motor -2 CV.
Option 2 - evaporator fan motor -3 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Power of the condenser fan motor -3 CV.
Size the electrical wiring using the maximum operation currents.
PKG-PRC007-EN
39
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-4 — Genius – Electrical Features - SRVE/SIVE 125
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
KW
CNO
15.40
8.92
7.70
15.40
8.92
7.70
15.40
8.92
7.70
15.40
8.92
7.70
KW
CNO
KW
CNO
18.60
10.77
9.30
5.53
3.19
2.76
7.32
4.23
3.66
9.28
5.36
4.64
1.80
1.04
0.90
9.28
5.36
4.64
9.28
5.36
4.64
9.28
5.36
4.64
9.28
5.36
4.64
48.81
28.24
24.40
50.60
29.28
25.30
52.56
30.41
26.28
45.08
26.09
22.54
STD
6.39
4.74
1.64
2.93
15.70
16.29
16.99
14.51
18.60
10.77
9.30
18.60
10.77
9.30
18.60
10.77
9.30
Option 1
Option 2
6.39
6.39
6.39
4.74
4.74
4.74
2.23
2.93
0.45
2.93
2.93
2.93
Plenum Box
Option
Maximum Operation Values
Compressor 1
CMO
Compressor 2
CMO
19.90
11.52
9.95
Fan Motor
Fan Motor
CMO
11.60
6.70
5.80
11.60
6.70
5.80
11.60
6.70
Current
A
Fan
Voltage
CMO
6.91
3.99
3.46
9.15
5.28
4.58
11.60
6.70
5.80
2.25
1.30
1.13
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
63.39
36.67
31.69
65.63
37.96
32.81
68.08
39.38
34.04
58.73
33.98
29.36
STD
19.90
11.52
9.95
19.90
11.52
9.95
19.90
11.52
9.95
Option 1
Option 2
5.80
11.60
6.70
5.80
Plenum Box
Option
Start-up Values
Compressor 1
LRA
Compressor 2
Fan Motor
LRA
Fan Motor
LRA
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
128.00
99.00
85.50
128.00
99.00
85.50
128.00
99.00
85.50
128.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
48.36
27.92
24.18
60.45
34.90
30.23
87.00
50.23
43.50
11.25
6.50
87.00
50.23
43.50
87.00
50.23
43.50
87.00
50.23
43.50
87.00
50.23
43.50
STD
Option 1
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -2 CV.
Option 1 - evaporator fan motor -3 CV.
Option 2 - evaporator fan motor -4 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Power of the condenser fan motor -4 CV.
Size the electrical wiring using the maximum operation currents
40
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-5 — Genius – Electrical Features - SRVE/SIVE 150
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
KW
CNO
18.60
10.77
9.30
18.60
10.77
9.30
18.60
10.77
9.30
18.60
10.77
9.30
KW
CNO
KW
CNO
18.60
10.77
9.30
7.32
4.23
3.66
9.28
5.36
4.64
11.61
6.70
9.30
3.04
1.76
9.30
11.61
6.70
5.80
11.61
6.70
5.80
11.61
6.70
5.80
11.61
6.70
1.52
56.13
32.47
28.06
58.09
33.60
29.04
60.42
34.94
30.20
51.85
30.00
25.92
STD
6.39
6.39
2.23
3.54
18.55
19.25
19.86
17.15
18.60
10.77
9.30
18.60
10.77
9.30
18.60
10.77
9.30
Option 1
Option 2
6.39
6.39
6.39
6.39
6.39
6.39
2.93
3.54
0.83
3.54
3.54
3.54
Plenum Box
Option
Maximum Operation Values
Compressor 1
CMO
Compressor 2
CMO
Fan Motor
Fan Motor
CMO
14.51
8.38
7.26
14.51
8.38
7.26
14.51
8.38
Current
A
Fan
Voltage
CMO
9.15
5.28
4.58
11.60
6.70
5.80
14.51
8.38
7.26
3.80
2.19
1.90
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
73.62
42.58
36.82
76.07
44.00
38.04
78.98
45.68
39.50
68.27
39.49
34.14
STD
Option 1
Option 2
7.26
14.51
8.38
7.26
Plenum Box
Option
Start-up Values
Compressor 1
LRA
Compressor 2
Fan Motor
LRA
Fan Motor
LRA
110.55
63.83
55.28
110.55
63.83
55.28
110.55
63.83
55.28
110.55
63.83
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
60.45
34.90
30.23
87.00
50.23
43.50
110.55
63.83
55.28
21.96
12.68
10.98
STD
Option 1
Option 2
Plenum Box
Option
55.28
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -3 CV.
Option 1 - evaporator fan motor -4 CV.
Option 2 - evaporator fan motor -5 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Power of the condenser fan motor -5 CV.
Size the electrical wiring using the maximum operation currents.
PKG-PRC007-EN
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-6 — Genius – Electrical Features - SAVE 050
Nominal Operation Values
Compressor
Fan Motor
Consumption Current
Fan
STD
and
Option 1
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
KW
CNO
KW
A
17.14
9.92
8.57
18.24
10.55
9.12
15.90
9.20
14.10
8.16
7.05
14.10
8.16
7.05
14.10
8.16
7.05
3.04
1.76
1.52
4.14
2.39
2.07
1.80
1.04
0.90
4.17
0.83
5.00
Option 2
4.17
4.17
1.22
0.45
5.39
4.62
Plenum Box
Option
7.95
Maximum operation values
Compressor
CMO
19.80
11.46
9.90
Fan Motor
Current
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
CMO
3.80
2.19
1.90
5.18
2.99
1.90
2.25
1.30
1.13
A
STD
and
23.60
13.65
11.80
24.98
14.45
11.80
22.05
12.76
11.03
Option 1
19.80
11.46
9.90
19.80
11.46
09.90
Option 2
Plenum Box
Option
Start-up values
Fan
STD
and
Option 1
Compressor
Fan Motor
LRA
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
21.96
12.68
10.98
21.96
17.85
10.98
11.25
6.50
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option and Option 1 - evaporator fan motor -1 CV.
Option 2 - evaporator fan motor -1.5 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Size the electrical wiring using the maximum operation currents.
42
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-7 — Genius – Electrical Features - SAVE 075
Nominal Operation Values
Compressor
Fan Motor
Consumption Current
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
KW
CNO
KW
CNO
KW
A
16.99
9.84
8.50
14.10
9.84
8.50
14.10
9.84
8.50
14.10
9.84
8.50
4.14
2.39
2.07
5.53
3.19
2.76
7.32
4.23
3.66
1.80
1.04
0.90
21.13
12.23
10.57
22.52
13.03
11.26
24.31
14.07
12.16
18.79
10.88
9.40
STD
5.68
1.22
6.90
Option 1
Option 2
5.68
5.68
5.68
1.64
2.23
0.45
7.32
7.91
6.13
Plenum Box
Option
Maximum operation values
Compressor
CMO
Fan Motor
Current
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
CMO
5.18
2.99
2.59
6.91
3.99
3.46
9.15
5.28
4.58
2.25
1.30
1.13
A
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
30.16
17.45
15.08
31.89
18.45
15.95
34.13
19.74
17.07
27.23
15.76
13.62
STD
Option 1
Option 2
Plenum Box
Option
Start-up values
Fan
Compressor
Fan Motor
LRA
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
LRA
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
30.92
17.85
15.46
48.36
27.92
24.18
60.45
34.90
30.23
11.25
6.50
STD
Option 1
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -1.5 CV.
Option 1 - evaporator fan motor -2 CV.
Option 2 - evaporator fan motor -3 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Size the electrical wiring using the maximum operation currents.
PKG-PRC007-EN
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-8 — Genius – Electrical Features - SAVE100
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
KW
CNO
KW
CNO
14.10
8.16
KW
CNO
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
14.10
8.16
7.05
14.10
8.16
7.05
14.10
8.16
7.05
14.10
8.16
7.05
4.14
2.39
2.07
5.53
3.19
2.76
7.32
4.23
3.66
1.80
1.04
0.90
32.34
18.71
16.17
33.73
19.51
16.86
35.52
20.55
17.76
30.00
17.36
15.00
STD
4.17
4.17
1.22
9.56
9.98
7.05
14.10
8.16
7.05
14.10
8.16
7.05
14.10
8.16
Option 1
Option 2
4.17
4.17
4.17
4.17
4.17
4.17
1.64
2.23
0.45
10.57
8.79
Plenum Box
Option
7.05
Maximum operation values
Compressor 1
CMO
19.80
11.46
9.90
Compressor 2
CMO
19.80
11.46
9.90
Fan Motor
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
CMO
5.18
2.99
2.59
6.91
3.99
3.46
9.15
5.28
4.58
2.25
1.30
1.13
44.78
25.91
22.39
46.51
26.91
23.26
48.75
28.20
24.38
41.85
24.22
20.93
STD
19.80
11.46
9.90
19.80
11.46
9.90
19.80
11.46
9.90
19.80
11.46
9.90
19.80
11.46
9.90
19.80
11.46
9.90
Option 1
Option 2
Plenum Box
Option
Start-up values
Fan
Compressor 1
Compressor 2
Fan Motor
LRA
Voltage
LRA
LRA
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
30.92
17.85
15.46
48.36
27.92
24.18
60.45
34.90
30.23
11.25
6.50
STD
Option 1
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -1.5 CV.
Option 1 - evaporator fan motor -2 CV.
Option 2 - evaporator fan motor -3 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Size the electrical wiring using the maximum operation currents.
44
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-9 — Genius – Electrical Features - SAVE125
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
KW
CNO
KW
CNO
14.10
8.16
KW
CNO
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
16.99
9.84
8.50
16.99
9.84
8.50
16.99
9.84
8.50
16.99
9.84
8.50
5.53
3.19
2.76
7.32
4.23
3.66
9.28
5.36
4.64
1.80
1.04
0.90
36.62
21.19
18.31
38.41
22.23
19.21
40.37
23.36
20.19
32.89
19.04
16.45
STD
5.68
4.17
1.64
11.49
12.08
12.78
10.30
7.05
14.10
8.16
7.05
14.10
8.16
7.05
14.10
8.16
Option 1
Option 2
5.68
5.68
5.68
4.17
4.17
4.17
2.23
2.93
0.45
Plenum Box
Option
7.05
Maximum Operation Values
Compressor 1
CMO
Compressor 2
CMO
19.80
11.46
9.90
Fan Motor
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
CMO
6.91
3.99
3.46
9.15
5.28
4.58
11.60
6.70
5.80
2.25
1.30
1.13
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
51.69
29.91
25.85
53.93
31.20
26.97
56.38
32.62
28.19
47.03
27.22
23.52
STD
19.80
11.46
9.90
19.80
11.46
9.90
19.80
11.46
9.90
Option 1
Option 2
Plenum Box
Option
Start-up Values
Fan
Compressor 1
Compressor 2
Fan Motor
LRA
Voltage
LRA
LRA
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
128.00
74.11
64.00
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
48.36
27.92
24.18
60.45
34.90
24.18
87.00
50.23
43.50
11.25
6.50
STD
Option 1
Option 2
Plenum Box
Option
5.63
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -2 CV.
Option 1 - evaporator fan motor -3 CV.
Option 2 - evaporator fan motor -4 CV.
Plenum box option - evaporator fan motor -0.5 CV.
Size the electrical wiring using the maximum operation currents.
PKG-PRC007-EN
45
Download from Www.Somanuals.com. All Manuals Search And Download.
Electrical
Data
Table ED-10 — Genius – Electrical Features - SAVE150
Nominal Operation Values
Compressor 1
Compressor 2
Fan Motor
Consumption
KW
Current
A
Fan
Voltage
KW
CNO
KW
CNO
16.99
9.84
KW
CNO
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
16.99
9.84
8.50
16.99
9.84
8.50
16.99
9.84
8.50
16.99
9.84
8.50
7.32
4.23
3.66
9.28
5.36
4.64
11.61
6.70
5.80
3.04
1.76
1.52
41.30
23.91
20.66
43.26
25.04
21.64
45.59
26.38
22.80
37.02
21.44
18.52
STD
5.68
5.68
2.23
13.59
14.29
14.90
12.19
8.50
16.99
9.84
8.50
16.99
9.84
8.50
16.99
9.84
Option 1
Option 2
5.68
5.68
5.68
5.68
5.68
5.68
2.93
3.54
0.83
Plenum Box
Option
8.50
Maximum Operation Values
Compressor 1
CMO
Compressor 2
CMO
Fan Motor
Current
A
Fan
Voltage
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
CMO
9.15
5.28
4.58
11.60
6.70
5.80
14.51
8.38
7.26
3.80
2.19
1.90
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
24.98
14.46
12.49
59.11
34.20
29.56
61.56
35.62
30.78
64.47
37.30
32.24
53.76
31.11
26.88
STD
Option 1
Option 2
Plenum Box
Option
Start-up Values
Fan
Compressor 1
Compressor 2
Fan Motor
LRA
Voltage
LRA
LRA
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
220V
380V
440V
220V
380V
440V
220V
380V
440V
220V
380V
440V
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
171.00
99.00
85.50
60.45
34.90
30.23
87.00
50.23
43.50
110.55
63.83
55.28
21.96
12.68
10.98
STD
Option 1
Option 2
Plenum Box
Option
To know which ventilation option should be used, consult the behavior of the
ventilation options.
•
CNO = Nominal operation current (A).
•
•
•
•
•
•
•
•
CMO = Maximum operation current.
LRA = Locked rotor amps.
STD Option - evaporator fan motor -3 CV.
Option 1 - evaporator fan motor -4 CV.
Option 2 - evaporator fan motor -5 CV.
Plenum box option - evaporator fan motor -1 CV.
Size the electrical wiring using the maximum operation currents.
46
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
SAVE
All dimensions are in
01 - Plenum box with optional supply screen
02 - Resistor box for heating (optional)
(control and power panel for external heating)
03 - Double [intake / exhaust] (evaporator) Centrifugal fan
04 - Supply motor
05 - Evaporating coil
06 - Return screen (optional)
07 - Filters
08 - Spacing for energy intake wire f 46.5 (right/left)
09 - Scroll compressor
10 - Drain f 1/2” BSP (left)
11 - Spacing for remote thermostat wire f 46.5
12 - Water intake and outlet (left/right)
13 - Electric panel for electric control model 100/125/150 (optional)
14 - Electric panel
15 - Electric panel for electric control model 050/075 (optional)
16 - Shell and tube condenser
Model
050
075
100
125
A
B
C
D
–
–
E
–
–
F
G
H
J
K
ø L
1”
1”
1 1/2”
1 1/2”
1 1/2”
38 (960)
47 (1190)
59 (1500)
67 (1700)
67 (1700)
9 (230)
15 (367)
7 (175)
8 (210)
8 (210)
13 (333)
16 (396)
13 (333)
16 (396)
16 (396)
16 (397)
17 (427)
17 (429)
17 (443)
17 (443)
5 (127)
2 (57)
5 (127)
2 (57)
2 (57)
11 (289)
13 (341)
11 (289)
13 (341)
13 (341)
10 (263)
10 (263)
8 (213)
8 (213)
8 (213)
5 (113)
5 (113)
4 (111)
4 (111)
4 (111)
9 (230)
10 (255)
10 (255)
13 (333)
16 (396)
16 (396)
150
PKG-PRC007-EN
47
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
SRVE
All dimensions are in
01 - Plenum box with optional supply screen
02 - Resistor box for heating (optional)
(control and power panel for external heating)
03 - Double [intake / exhaust] (evaporator) Centrifugal fan
04 - Supply motor
05 - Evaporating coil
06 - Return screen (optional)
07 - Filters
08 - Spacing for energy intake wire f 46.5 (right/left)
09 - Double [intake / exhaust] (condenser) Centrifugal fan
10 - Scroll compressor
11 - Drain f 1/2” BSP (left)
12 - Spacing for remote thermostat wire f 46.5
13 - Electric panel for electric control model 100/125/150 (optional)
14 - Electric panel
15 - Electric panel for electric control model 050/075 (optional)
16 - Shell and tube condenser
Model
050
075
100
125
A
B
C
D
–
–
E
–
–
F
G
H
J
K
L
M
38 (960)
47 (1190) 15 (367)
59 (1500)
67 (1700)
67 (1700)
9 (230)
13 (333)
16 (396)
13 (333)
16 (396)
16 (396)
16 (397)
17 (427)
17 (429)
17 (443)
17 (443)
5 (127)
2 (57)
5 (127)
2 (57)
2 (57)
11 (289)
13 (341)
11 (289)
13 (341)
13 (341)
5 (120)
5 (120)
9 (230)
16 (400)
16 (400)
47 (1180) 10 (258) 36 (920)
47 (1180) 10 (258) 45 (1150)
48 (1210) 10 (247) 58 (1460)
50 (1280)
59 (1510)
7 (175)
8 (210)
8 (210)
9 (230)
10 (255)
10 (255)
13 (333)
16 (396)
16 (396)
9 (240) 65 (1660)
9 (240) 65 (1660)
150
48
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Dimensions
SIVE
All dimensions are in
01 - Plenum box with optional supply screen
02 - Resistor box for heating (optional)
(control and power panel for external heating)
03 - Double [intake / exhaust] (evaporator) Centrifugal fan
04 - Supply motor
05 - Evaporating coil
06 - Return screen (optional)
07 - Filters
08 - Spacing for energy intake wire f 46.5 (right/left)
09 - Scroll compressor
10 - Drain f 1/2” BSP (left)
11 - Spacing for remote thermostat wire f 46.5
12 - Electric panel for electric control model 100/125/150 (optional)
13 - Electric panel
14 - Electric panel for electric control model 050/075 (optional)
15 - Prep for spacing for f 46.5 (right/left) lines
Model
050
075
100
125
A
B
C
D
–
–
E
–
–
F
G
H
J
–
–
K
–
–
D1
D2
–
–
5/8”
5/8”
3/4”
L1
L2
–
–
1/2”
1/2”
1/2”
38 (960)
47 (1190) 15 (367)
59 (1500)
67 (1700)
67 (1700)
9 (230)
13 (333)
16 (396)
13 (333)
16 (396)
16 (396)
16 (397) 5 (127) 11 (289)
17 (427) 2 (57) 13 (341)
17 (429) 5 (127) 11 (289)
17 (443)
17 (443)
5/8”
3/4”
5/8”
3/4”
3/4”
1/2”
1/2”
1/2”
1/2”
1/2”
7 (175)
8 (210)
8 (210)
9 (230) 13 (333)
10 (255) 16 (396)
10 (255) 16 (396)
6 (150)
6 (150)
6 (150)
8 (205)
8 (205)
8 (205)
2 (57)
2 (57)
13 (341)
13 (341)
150
PKG-PRC007-EN
49
Download from Www.Somanuals.com. All Manuals Search And Download.
CRCB
Dimensions
All dimensions are in
01 - Double [intake / exhaust] Centrifugal fan
02 - Terminal box
03 - Service panel
04 - Motor
05 - Condensing coil
06 - Spacing for ø 27 energy intake wire
07 - Refrigeration connections (only one setting)
Model
050
A
39
B
25
C
35
D
12
E
16
F
–
G
–
H
13
I
30
J
28
L
4
M
41
N
21
P
5
Q
–
R
–
ø L1 ø D1 ø L2
ø D2
–
1/2” 5/8”
–
(987) (631) (890) (295.5) (396)
49 25 35 17 16
(1241) (631) (890) (422.5) (396)
49 25 37 13
(1341) (631) (941) (212.5) (333) (230) (333) (289) (1143) (863.5) (97) (1383) (521) (159) (200) (255)
65 28 40 12 16 10 16 13 58 37 67 24 10
(1646) (714) (1018) (299.5) (396) (255) (396) (341) (1473) (940) (84) (1688) (604) (236) (200) (255)
65 28 49 12 16 10 16 13 58 46 67 24 10
(341) (762) (711) (110) (1029) (521) (132)
13 40 32 51 21
(341) (1016) (816.5) (110) (1283) (521) (132)
11 45 34 55 21
075
100
125
150
–
–
4
5
–
–
1/2” 3/4”
–
–
9
9
13
4
6
8
10
1/2” 5/8” 1/2”
1/2” 3/4” 1/2”
1/2” 3/4” 1/2”
5/8”
5/8”
5/8”
3
9
8
3
9
8
(1646) (714) (1247) (299.5) (396) (255) (396) (341) (1473) (1168) (84) (1688) (604) (236) (200) (255)
50
PKG-PRC007-EN
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Coils
Cabinet
Fans
All the coils (evaporator and condenser)
use tubes with 3/8” external diameter
and high efficiency aluminum fins,
Trane Wavy 3B model, mounted on the
evaporator coil with 132 fins per foot,
and on the condenser with 168 fins per
foot.
Manufactured of galvanized steel plate,
it is painted with anticorrosive primer
and high resistance synthetic enamel.
The cabinet is constructed with an
bottom tray, structural laterals, front
screen and cover and back cover. The
remote condenser cabinet is painted
with epoxy primer and high resistance
enamel and is also constructed of
galvanized steel plate.
Sirocco type centrifugal fans,
constructed of galvanized steel plate
with static and dynamically balanced
rotors. The evaporator array is sized to
overcome up to 1.6 inches of external
static pressure.
Filters
The copper tubes are expanded
The standard unit is furnished with
permanent washable filters of
electrostatic fabric.
mechanically to guarantee perfect
contact between fin and tube. All the
coils are tested for leaks. Evaporator
coils are tested at a pressure of 300
PSIG, and the condensers at 400 PSIG.
For frontal access to the evaporator
units, just loosen four screws to remove
the cover and the screen.
Also Available:
Metallic permanent filters (standard)
Disposable fiberglass filters of 1”
thickness
The tray for condensation water was
designed according to the interior air
quality standards of ASHRAE.
Return Screen
Screen of anodized aluminum profile
with vertical flanges. Vertical screens
provide excellent air distribution in the
coil. This option is recommended for
hulls in which the machine is visible in
the zone to be air-conditioned.
Combination in series of the two
previous filters
Copper-Copper Coils
Scroll Compressor
For applications where greater
resistance against corrosion is
necessary, coils with copper tubes and
fins can be manufactured. Offer as
special design.
All compressors of the Genius line are
scroll type. They are of high efficiency
using ports instead of valves, which
eliminates possible breakdowns. They
have 64% fewer moveable parts than a
reciprocating compressor of the same
capacity. Their operation is extremely
smooth and silent.
Plenum Box
The style of the plenum box is similar to
that of the cabinet and is sized to
guarantee silent operation. The plenum
box screen has a slight angle that allows
the air flow to be directed in a vertical or
lateral direction. A specific fan array
exists for use of the Genius unit with
plenum box (consult the general facts
tables).
Water-cooled condenser
Water-cooled condensers are “Shell and
Tube” type. They are manufactured with
copper tubes with integrated flanges,
expanded in steel mirrors, with grooved
holes, mounted in a steel casing and
cast iron covers, which are removable
for easy cleaning. The casing and covers
are protected with finishing paint.
This plenum should only be used when
the discharge from the unit is free into
the atmosphere. In the case of discharge
into a duct network, this option should
not be used.
Designed, constructed and tested
according to ASME standards, for work
pressure of 300 PSIG on the refrigerant
side and 150 PSIG on the water side.
PKG-PRC007-EN
51
Download from Www.Somanuals.com. All Manuals Search And Download.
Mechanical
Specifications
Safety and Protection Devices
The equipment is protected by high and
low pressure pressurestats with
automatic resets and fixed calibration,
internal thermostat with automatic reset
Electric Heating
in the compressor, current overload
relay for the compressor and overload
thermal relay for the fan motors.
Includes heating resistors, stainless steel
tubes, a contact unit, fuses, a control
thermostat and safety thermostat, all
properly installed.
Water-cooled condensers are protected
by a fusible top.
The control scheme considers the use of
heating resistors.
Regulating points for high and low pressure pressurestats
Machines with water condensation
Machines with air condensation
Stop - PSIG
275 +/- 15
395 +/- 15
25 +/- 8
Start-up - PSIG
185 +/-15
280 +/- 20
Tests
Machines with water and air condensation
80 +/- 12
Genius line equipment are shipped fully
tested from the factory. The standard
tests consist of visual inspections, leak
tests, fan start-up followed by start-up
and operation of the unit.
Cooling Components
has a screw connection. For the SAVE
and SRVE models, the filter is welded.
In the suction and discharge lines
Rotalock type service valves are
available. The liquid line has a 1/4” SAE
Schrader valve.
The following table shows the
refrigerant tube diameters relative to
the equipment cooling circuits.
Trane offers the following factory tests:
Basic production test with inspector.
Performance test.
Complete test with or without an
inspector present.
A drying filter is installed in the liquid
line. For the SIVE model the drying filter
Line diameter
5 TR circuit
7.5 TR circuit
Suction line
7/8”
1 1/8”
Discharge line
Liquid line
1/2”
1/2”
5/8”
3/4”
7/8”
10 TR circuit
1 1/8”
5/8”
Controls
High pressure pressurestat with manual
reset
Units are provided with a control
thermostat. This thermostat can be
installed remotely or in the equipment,
depending on the needs of the client.
Liquid Tank
Only for the SIVE model.
Liquid Viewer
As Option:
Programmable Thermostat
UCP Microprocessor Control
Auxiliary maintenance component,
indicates the existence of humidity
inside the equipment.
Service Valve
Service valve for the liquid line.
Solenoid Valve
Auxiliary component that allows
confinement of the refrigerant in the
condenser for later extraction.
Condensation Pressure Controller
A set with pressurestatic valves to
control the condensation pressure in
machines with air-cooled condensers.
Supply Voltage 220V, 380V, 440V,
triphasics, 60 Hz.
Literature Order Number
File Number
PKG-PRC007-EN
PL-UN-PKG-000-PRC007-EN-100
Supersedes
New
Stocking Location
La Crosse
The Trane Company
3600 Pammel Creek Road
La Crosse, WI 54601-7599
Since The Trane Company has a policy of continuous product improvement, it reserves the right to change
design and specifications without notice.
An American Standard Company
Download from Www.Somanuals.com. All Manuals Search And Download.
|