Toshiba Vacuum Cleaner HV6AS User Manual

Document: GF07Z301 Rev. 1  
INSTRUCTION MANUAL  
INSTALLATION - OPERATION - MAINTENANCE  
HV6AS Vacuum Circuit Breakers – Fixed Type  
4.8 & 7.2kV Voltage Classes  
APPLICABLE MODEL NUMBERS:  
(Manual Operation Types)  
HV6AS-U  
HV6AS-L  
(Motor Operation Types)  
HV6AS-MU  
HV6AS-ML  
Issued: 2/2000  
Supercedes First Issue Dated 2/99.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTRUCTION MANUAL  
For the Installation, Operation and Maintenance of  
HV6AS Vacuum Circuit Breakers – Fixed Type  
4.8 & 7.2kV Voltage Classes  
Never attempt to install, operate, maintain or dispose of this equipment until  
you have first read and understood all of the relevent product warnings and  
user directions that are contained in this Instruction Manual.  
WARNING  
To contact Toshiba, address all correspondence to:  
Field Service Department  
Toshiba International Corporation  
13131 West Little York Road  
Houston, Texas 77041 USA  
or call:  
(713) 466-0277  
(800) 231-1412  
(800) 527-1204 (Canada)  
Fax:  
(713) 466-8773  
Please complete the following information for your records and retain with this manual:  
Model: ___________________________________  
Serial Number:_____________________________  
Date of Installation:_________________________  
Inspected by: ______________________________  
Reference Number: _________________________  
© TOSHIBA INTERNATIONAL CORPORATION, 2000  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY  
Page 1  
IMPORTANT MESSAGES  
Read this manual and follow its instructions. Signal words such as  
DANGER, WARNING and CAUTION will be followed by important safety  
information that must be carefully reviewed.  
Indicates a situation which will result in death, serious injury, and severe  
property damage if you do not follow instructions.  
DANGER  
Means that you might be seriously injured or killed if you do not follow  
instructions. Severe property damage might also occur.  
WARNING  
Means that you might be injured if you do not follow instructions. Equipment  
damage might also occur.  
CAUTION  
NOTE  
Gives you helpful information  
READ SAFETY SIGNS  
To avoid injury, you must read and follow all safety signs.  
Keep the safety signs visible and in good shape. Never remove or cover any safety  
signs.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Page 2  
SAFETY  
QUALIFIED OPERATORS ONLY  
Only qualified persons are to install, operate, or service this equipment according to all  
applicable codes and established safety practices.  
A qualified person must:  
1)  
2)  
Carefully read the entire instruction manual.  
Be skilled in the installation, construction or operation of the equipment and  
aware of the hazards involved.  
3)  
4)  
5)  
Be trained and authorized to safely energize, deenergize, clear, ground,  
lockout and tag circuits in accordance with established safety practices.  
Be trained and authorized to perform the service, maintenance or repair of  
this equipment.  
Be trained in the proper care and use of protective equipment such as rubber  
gloves, hard hat, safety glasses, face shield, flash clothing, etc. in  
accordance with established practices.  
6)  
Be trained in rendering first aid.  
SAFETY CODES  
Toshiba HV6AS vacuum circuit breakers are designed and built in accordance with JIS  
C 4603-1990 and JEC-2300-1985. Installations must comply with all applicable state  
and local codes, adhere to all applicable National Electric Code (NFPA 70) standards  
and instructions provided in this manual.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SAFETY  
Page 3  
HAZARDOUS VOLTAGE will cause severe injury, death, fire, explosion and  
property damage.  
DANGER  
Turn off and lock out Primary and Control Circuit Power before servicing.  
Keep all panels and covers securely in place.  
Never Defeat, Modify, or Bypass any Safety Interlocks  
Qualified Operators only  
SAFETY....................................................................................................................................................1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 4  
TABLE OF CONTENTS  
INTRODUCTION ......................................................................................................................................6  
GENERAL DESCRIPTION.......................................................................................................................7  
Components..................................................................................................................................7  
Indicators and Controls.................................................................................................................8  
RECEIVING, INSPECTION AND HANDLING..........................................................................................9  
Receiving and Unpacking .............................................................................................................9  
Acceptance Inspection..................................................................................................................9  
Handling and Moving ..................................................................................................................10  
INSTALLATION......................................................................................................................................11  
Rating Verification.......................................................................................................................11  
Mounting the Circuit Breaker to a Panel .....................................................................................12  
Mounting Directly to a Shelf ........................................................................................................14  
Main Circuit Cable Connections..................................................................................................15  
Ground Connections ...................................................................................................................16  
Control Circuit Connections ........................................................................................................17  
Additional Auxiliary Switch ..........................................................................................................17  
PRE-ENERGIZATION CHECK ..............................................................................................................18  
General .......................................................................................................................................18  
Electrical Checks ........................................................................................................................18  
OPERATION...........................................................................................................................................19  
Manual Operation........................................................................................................................19  
Electrical Operation.....................................................................................................................19  
Undervoltage Trip........................................................................................................................24  
MAINTENANCE .....................................................................................................................................25  
Maintenance Program.................................................................................................................25  
Maintenance Record...................................................................................................................25  
Servicing Equipment ...................................................................................................................25  
Inspection and Maintenance Types ............................................................................................26  
Table 1. Tightening Torques......................................................................................................26  
Table 2. Check Points for Periodic Inspection ...........................................................................27  
Vacuum Check............................................................................................................................29  
DISPOSAL..............................................................................................................................................31  
STORAGE ..............................................................................................................................................32  
Storage........................................................................................................................................32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
Page 5  
Inspection During Storage...........................................................................................................32  
SPECIFICATIONS..................................................................................................................................33  
Table 3. Ratings – Manual Operation HV6AS-U and HV6AS-L Types......................................33  
Table 4. Ratings – Motor Operation HV6AS-MU and HV6AS-MU Types ..................................33  
WARRANTY AND LIMITATION OF LIABILITY.....................................................................................34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Page 6  
INTRODUCTION  
It is the intent of this manual to provide a guide for safely installing, operating and maintaining Toshiba  
vacuum circuit breakers. This manual consists of a section of general safety instructions and is marked  
throughout with warning symbols. Read this manual thoroughly before installation, operation and  
maintenance of this equipment.  
This manual and all accompanying drawings should be considered a permanent part of the equipment.  
They should be readily available for review and reference at all times. This manual is not intended to  
cover all details, combinations, or variations of the equipment. Always refer to drawings accompanying  
the equipment for additional details.  
All safety warnings must be followed to ensure personal safety. General safety instructions are  
found on pages 1 through 3. Read and save these instructions for future reference.  
Follow all precautions to attain proper equipment performance and longevity.  
Dimensions shown in the manual are in metric and/or their English equivalent.  
This manual is divided into major sections of interest, as follows:  
GENERAL DESCRIPTION – Provides a description of the equipment, information on major  
components and how they function, plus rating information.  
RECEIVING, INSPECTION AND HANDLING – Describes procedures for receiving, unpacking,  
inspecting, handling, lifting and moving the circuit breaker.  
INSTALLATION – Provides information on installing the circuit breaker in the switchgear cell along with  
breaker racking procedures.  
PRE-ENERGIZATION CHECK – Provides a checklist for preparing the equipment for energization.  
OPERATION – Provides information on manual and electrical operation of the circuit breaker, circuit  
diagrams, operating sequence description and operation of circuit breaker optional accessories.  
MAINTENANCE – Lists the basic maintenance procedures for this equipment necessary for safe and  
reliable operation.  
DISPOSAL – Lists procedures for the safe disposal of the equipment when the service life has expired.  
STORAGE – Provides guidelines for storing new equipment for an extended period of time.  
SPECIFICATIONS – Covers ratings and other specifications of the circuit breaker.  
WARRANTY AND LIMITATION OF LIABILITY – Details Toshiba International Corporation’s standard  
warranty terms.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
GENERAL DESCRIPTION  
Page 7  
The Toshiba HV6AS vacuum circuit breakers  
described in this manual are suitable for use on  
systems of 4.8kV and 7.2kV voltage classes  
which require interrupting ratings of 16kA and  
14kA respectively and a continuous current  
rating of 630A. The circuit breakers are intended  
for use in limited applications requiring small  
physical size and low maintenance.  
These breakers are designed for fixed panel  
mounting and are available with upper main  
circuit terminals (U, MU types) or rear terminals  
(L, ML types).  
The breakers are available as both manual and  
motor-operated types. Motor-operated breakers  
use a motor to charge the closing springs and to  
close the breaker upon command. Both types  
can be tripped electrically and also include  
undervoltage release.  
Fig. 1 U and MU Type Circuit Breaker (Upper  
Main Circuit Terminals)  
Arc interruption is accomplished inside sealed  
vacuum interrupters mounted on track-resistant  
insulators. Vacuum interrupters use low-surge  
contact materials which exhibit low current  
chopping levels reducing switching overvoltages.  
Fig. 1 and Fig. 2 illustrate and identify the major  
components of the circuit breakers.  
COMPONENTS LEGEND:  
1) Manual closing handle  
2) Manual trip lever  
3) On-Off indicator  
4) Spring charge indicator (MU and ML only)  
5) Operations counter  
6) Secondary control circuit terminal block  
7) Main circuit terminals  
8) Auxiliary switch  
9) Grounding terminal  
Fig. 2 L and ML Type Circuit Breaker (Rear  
Main Circuit Terminals)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Page 8  
GENERAL DESCRIPTION  
5) Operations Counter - Indicates the total  
accumulated number of times the circuit  
breaker has been closed.  
SAFETY DEVICES  
Safety interlocks and guards are provided as an  
integral part of the equipment design. These  
devices are provided for safety to the operator.  
Never defeat, modify or  
DANGER  
bypass any safety devices,  
interlocks or operating  
mechanism. This would  
make the equipment  
unsafe. Fire, explosion,  
severe injury, death and  
property damage could  
occur.  
Do not operate this  
equipment unless all  
WARNING  
covers and panels are in  
place.  
INDICATORS AND CONTROLS (Fig. 3)  
The following front panel indicators and controls  
are provided:  
Fig. 3 Indicators and Controls  
1) On-Off Indicator - Indicates if the circuit  
breaker is OFF (Green) or ON (Red). When  
the indicator reads OFF, the main contacts of  
the circuit breaker are open. When the  
indication is ON, the main contacts are  
closed.  
2) Closing Spring Status Indicator (MU, ML  
types only) - Indicates if the closing springs  
are CHARGED (Yellow) or DISCHARGED  
(White).  
3) Manual Closing Handle – Rotating the  
handle clockwise approximately 75° closes  
the circuit breaker (On-Off indicator changes  
to ON). When the handle is released, it  
returns to its normal position.  
4) Manual Trip Lever (Red) – Pushing the lever  
in the direction of the arrow trips the circuit  
breaker (On-Off indicator changes to OFF).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
RECEIVING, INSPECTION AND HANDLING  
Page 9  
RECEIVING AND UNPACKING  
Fig. 4 Closing Handle  
The circuit breaker units are subjected to factory  
production testing prior to being packed and  
shipped.  
ACCEPTANCE INSPECTION  
Confirm that the circuit breaker unit is complete,  
correct as specified and undamaged from  
shipment and handling.  
Upon receipt of the equipment, do the following:  
1) Make an immediate inspection for damage  
which might have occurred during shipment.  
If damage is discovered, it should be noted  
with the carrier prior to accepting the  
shipment, if possible.  
2) Carefully unpack the equipment sufficiently to  
check for missing parts or concealed  
damage.  
3) Check for the presence of accessories that  
are shipped with the circuit breaker:  
Fig. 5 Insulating Cylinder  
- Closing Handle (shipped loose with  
3) Keep the circuit breaker upright.  
Never lay the circuit  
breaker on its side or  
upside down. This may  
cause damage.  
CAUTION  
4) File a claim with the carrier for any damaged  
or missing items and immediately notify the  
nearest Toshiba representative.  
Do not install or energize  
equipment that has been  
damaged. Damaged  
WARNING  
equipment can fail during  
operation, resulting in fire  
and explosion.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Page 10  
RECEIVING, INSPECTION AND HANDLING  
.
HANDLING AND MOVING  
When handling and moving the circuit breaker,  
the techniques shown in this section may be  
used.  
Fig. 6 Correct Method for Handling the U and  
Care and caution should be used when handling  
the circuit breaker units to avoid damage to the  
equipment and personal injury. Always keep the  
circuit breaker in a generally upright position.  
Refer to Fig. 6 and Fig. 7 for the correct  
methods of lifting and moving the circuit  
breakers.  
MU Type Circuit Breakers  
Fig. 7 Correct Method for Handling the L and  
ML Type Circuit Breakers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
INSTALLATION  
Page 11  
at the installation location, a space heater should  
be installed inside the circuit breaker enclosure.  
Do not install this  
WARNING  
equipment in areas where  
unusual service conditions  
exist. Using this equipment  
in other than usual service  
conditions can result in  
equipment failure.  
NOTE:  
Temperature, altitude or other  
conditions outside of the usual limits  
may require derating or other special  
equipment. Contact your nearest  
Toshiba representative for additional  
information.  
Toshiba HV6AS circuit breakers are intended for  
use in usual service conditions as defined in  
IEEE C37.20.2. The temperature of the cooling  
air (ambient air temperature) surrounding the  
breaker should be between the limits of -5°C  
(23°F) and +40°C (104°F). The altitude of the  
equipment installation should not exceed 3300 ft  
(1000 m).  
RATING VERIFICATION  
Prior to Installation, the maximum fault current  
capacity of the power system at the point of  
installation should be verified. This value must  
not exceed the symmetrical interrupting  
capability of the circuit breaker.  
illustrates a typical circuit breaker nameplate.  
In particular, avoid the following installation  
conditions:  
Do not exceed the ratings  
DANGER  
specified on the circuit  
breaker nameplate or  
system accessories.  
Underrated equipment can  
fail during operation  
causing fire, explosion,  
severe injury, death, and  
property damage.  
- Excessive dust  
- Corrosive gases  
- Extreme variations in temperature  
- Very high or low humidity  
- Vibrations  
- Inclined locations  
If there is a chance that condensation can occur  
Fig. 8 Typical Circuit Breaker Nameplate  
TOSHIBA  
VACUUM CIRCUIT BREAKER  
TYPE HV6AS-MU-VV  
RATED VOLTAGE 7.2/4.8 kV, RMS SHORT CKT. AMPS  
14/16 kA, RMS  
FREQUENCY  
50/60 Hz INTERRUPTING TIME  
3 CYCLES  
120 VAC / 125 VDC  
125 VDC  
CONTINUOUS AMPS  
IMPULSE LEVEL  
DIELECTRIC  
CLOSE VOLTS  
630A, RMS  
60 kV, CREST  
22 kV AC RMS  
SHUNT TRIP VOLTS  
UV TRIP VOLTS  
MFG. STANDARD  
53 lbs  
120 VAC  
JIS C 4603-1990  
JEC-2300-1985  
WEIGHT  
24  
kg  
PARTS & WIRING, SEE INSTRUCTIONS  
GF07Z301  
SER. No. 98700221 MFG. DATE 7/98  
TOSHIBA INTERNATIONAL CORPORATION  
HOUSTON, TEXAS U.S.A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Page 12  
INSTALLATION  
Fig. 10 Align Breaker With Panel Cutout  
MOUNTING THE CIRCUIT BREAKER TO A  
PANEL  
The circuit breakers are designed to mount to a  
panel made from 11 ga. (.12 in.) thick steel. If  
the breaker must be mounted to a panel of  
different thickness, contact Toshiba.  
Panel cutout dimensions for the circuit breakers  
all breaker types.  
To mount the circuit breaker, follow the steps  
below:  
1. Loosen the small screw (M5) on the closing  
handle and remove the handle.  
Fig. 11 Fasten Breaker and Front Plate to  
2. Remove the four front plate mounting bolts  
(M8) from the circuit breaker (Fig. 9).  
Remove the spacer washers between the  
front plate and breaker and discard them  
(make sure none are left inside the breaker),  
3. Align the breaker with the cutout and  
mounting holes on the panel to which it is to  
be mounted (Fig. 10). Some breakers are  
furnished with two hooks which may be used  
to temporarily attach the breaker to the  
panel.  
4. Using the four M8 bolts removed in step 2,  
fasten the breaker and its front plate to the  
mounting panel (Fig. 11). The tightening  
torque should be 120-150 kgf-cm (9-11 ft-lb).  
Panel  
5. Replace the closing handle removed in step  
1 and the M5 screw. The screw should be  
tightened to a torque of 40-50 kgf-cm (35-43  
in-lb).  
Fig. 9 Remove Front Plate and Spacer  
Washers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
INSTALLATION  
Page 13  
0.343 DIA  
4 PLACES  
0.25  
0.38 RADIUS  
4 PLACES  
8.03  
0.25  
0.25  
0.25  
10.71  
Dimensions in Inches  
Fig. 12 Panel Cutout Dimensions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Page 14  
INSTALLATION  
Fig. 13 Mounting Breaker to Flat Plate or  
Angles  
MOUNTING DIRECTLY TO A SHELF  
The shelf should be flat and level within ± 0.5  
mm (± 0.02 in.). If there are any noticeable gaps  
between the breaker and the shelf, fill them in  
using flat washers as spacers.  
PANEL  
Check to make sure the breaker On-Off indicator  
shows OFF (green), then mount it by following  
the steps below:  
1. Fasten the breaker onto steel angles or to a  
flat plate (Fig. 13). Use M8 hex head bolts  
(either 50 mm or 35 mm). The tightening  
torque should be 120-150 kgf-cm (9-11 ft-lb).  
ANGLE  
2. Either mounting method shown in (Fig. 14)  
may be used.  
M8 x 35MM OR M8 x 50MM BOLT  
Fig. 14 Optional Hardware Orientation  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
INSTALLATION  
Page 15  
Fig. 15 Pass Cable Through Insulating  
MAIN CIRCUIT CABLE CONNECTIONS  
Cables which connect to the circuit breaker  
should be routed to avoid interference with sharp  
edges and moving parts. Minimum bending  
radius for the type of cable used should be  
observed.  
Power cables should be braced and/or laced to  
withstand short-circuit forces wherever such  
cables are unsupported. Power cables should  
be adequately sized to carry the maximum  
continuous current in accordance with NEC  
requirements and should have an adequate  
voltage rating. Cables should be dressed and  
terminated as appropriate to the voltage class  
and cable manufacturer’s recommendations.  
When terminating shielded cables, use  
termination kits appropriate for the system  
voltage to taper the insulation and reduce  
Cylinder  
Fig. 16 Fasten Cable to Main Circuit  
electrical stress.  
Follow the manufacturer’s  
installation instructions provided with the  
termination kit.  
To connect cables, follow the steps below:  
1. Pass the cable through the insulating  
cylinder (six cylinders are supplied with the  
2. Fasten the cable to the main circuit terminal  
(Fig. 16). Use 35 mm Class 8.8 M10 or M12  
hex head bolts, 2 flat washers, a lock  
washer and a nut. While securely preventing  
the bolt from rotating with a wrench, torque  
the nut to 250-315 kgf-cm (18-23 ft-lb) for  
M10 bolts or 450-565 kgf-cm (32-41 ft-lb) for  
M12 bolts.  
Terminal  
Use two wrenches to torque  
the connection to prevent  
applying excessive force to  
CAUTION  
the terminal which can  
damage the frame.  
3. Fasten the insulating cylinder in place, then  
check to make sure that the hook is engaged  
Fig. 17 Fasten Insulating Cylinder  
Download from Www.Somanuals.com. All Manuals Search And Download.  
       
Page 16  
INSTALLATION  
GROUND CONNECTIONS  
Fig. 18 Ground Connection for U and MU  
Type Breakers  
The circuit breaker must be grounded in  
accordance with the requirements of the National  
Electrical Code, Article 250 or applicable local  
standards.  
Proper grounding  
WARNING  
connections must be made  
to the circuit breaker before  
incoming power is applied.  
It is very important that the circuit breaker and its  
enclosure be adequately grounded to protect the  
operator from injury in the event of short circuits  
or other abnormal occurences and to ensure that  
the metal parts of the equipment, other than live  
parts, remain at ground potential.  
For U and MU type circuit breakers, the ground  
terminal is on the left side of the operating  
mechanism as viewed from the rear of the  
breaker. To make the ground connection, first  
remove the fastening M6 hex head bolt and  
crimp-on terminal (provided with the breaker)  
and crimp the terminal to the end of the ground  
the same bolt previously removed and torque to  
50-65 kgf-cm (43-56 in-lb).  
Fig. 19 Ground Connection for L and ML  
Type Breakers  
For L and ML type circuit breakers, the ground  
terminal is on the left side of the terminal block  
The same instructions as for the U and MU  
breaker above should be followed to attach the  
ground wire.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
INSTALLATION  
Page 17  
Fig. 20 Connection to Control Terminal  
CONTROL CIRCUIT CONNECTIONS  
Control circuit wiring is connected to the terminal  
block on the top of the operating mechanism  
(Fig. 20). Connect control wires in accordance  
with the appropriate wiring diagram shown in Fig.  
28 through Fig. 31 in the OPERATION section of  
this manual.  
On the U and MU type breakers, connections to  
auxiliary contacts are made directly to the  
On the L and ML type breakers, connections to  
auxiliary contacts are made to a terminal block  
Block  
Fig. 21 Auxiliary Contact Connections on U  
ADDITIONAL AUXILIARY SWITCH (Optional)  
An optional second auxiliary switch may be  
furnished, located on the right side as viewed  
from the rear of the breaker.  
When a second auxiliary switch is furnished,  
control wires are connected directly to the  
switch.  
and MU Type Breakers  
Fig. 22 Auxiliary Contact Connections on L  
and ML Type Breakers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
         
Page 18  
PRE-ENERGIZATION CHECK  
ELECTRICAL CHECKS  
GENERAL  
BEFORE  
Electrical shock hazard.  
ENERGIZING  
THE  
CIRCUIT  
Do not touch energized  
WARNING  
BREAKER for the first time, follow the procedure  
below to verify that the equipment is properly  
installed and functional.  
components during a test  
using auxiliary power.  
An electrical insulation resistance test should  
be performed to verify that the circuit breaker  
and associated field wiring are free from  
short circuits and grounds. Refer to the  
MAINTENANCE Section of this manual for  
additional information.  
Hazardous Voltage. Turn off  
DANGER  
and lock out all primary and  
control circuit power  
sources prior to performing  
this pre-energization check.  
Hazardous voltages are  
present during dielectric  
testing which can result in  
serious injury or death.  
High potential tests should  
be performed only by  
qualified personnel.  
Do not operate this  
equipment until a complete  
safety inspection has been  
made.  
WARNING  
WARNING  
Do not energize damaged  
equipment that has not  
WARNING  
been repaired or verified.  
The circuit breaker must be set to the OFF  
position before energizing incoming power.  
Do not remove, cover or  
WARNING  
destroy any safety signs.  
Do not operate this  
WARNING  
equipment until all panels  
and covers have been  
installed.  
All blocks or other temporary braces used for  
shipment must be removed.  
Before closing the enclosure, all metal chips,  
scrap wire and other debris left over from  
installation must be cleaned out.  
Cover all unused openings. Install all panels,  
guards and covers.  
A
supply of spare parts should be  
established.  
Instruction manuals and diagrams should be  
collected and filed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
OPERATION  
Page 19  
Fig. 23 Preparing to Manually Close Breaker  
MANUAL OPERATION  
Powerful springs. Do not  
WARNING  
place your hands or any  
part of your body inside  
the circuit breaker while  
the indicators show  
CHARGED (yellow) or ON  
(red).  
To avoid damaging the  
mechanism, do not close  
the circuit breaker when  
the On-Off Indicator shows  
ON (red).  
CAUTION  
MANUAL CLOSING (Motor-Operated MU and  
ML Types):  
1. Check to make sure that the On-Off  
indicator shows OFF (green).  
2. Attach the closing handle to the breaker if it  
is not already attached.  
Fig. 24 Manually Closing Breaker  
3. If the closing spring status indicator shows  
DISCHARGED (white):  
Turn the closing handle clockwise (Fig. 23).  
The breaker will close (On-Off indicator  
changes to ON) after the handle is turned  
approximately 75° (Fig. 24).  
NOTE  
If the handle is turned in small  
increments, the closing spring will  
store the energy from the handle  
action and the circuit breaker will  
close before 75° of rotation.  
If the closing spring status indicator shows  
CHARGED (yellow):  
Turn the closing handle clockwise. The  
breaker will close after the handle is turned  
approximately 10°.  
4. Release the handle, and it will return to its  
initial position.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Page 20  
OPERATION  
Fig. 25 Manually Opening Breaker  
MANUAL CLOSING (Manual Spring-Operated  
U and L Types):  
SYMBOL  
DESCRIPTION  
1. Check to make sure that the On-Off  
indicator shows OFF (green).  
2. Turn the closing handle clockwise. The  
breaker will close (On-Off indicator changes  
to ON) after the handle is turned  
approximately 75°.  
NOTE  
If the handle is turned in small  
increments, the closing spring will  
store the energy from the handle  
action and the circuit breaker will  
close before 75° of rotation.  
3. Release the handle, and it will return to its  
initial position.  
M
TC  
Motor  
Voltage Trip Coil  
MANUAL OPENING (All Types):  
UV  
Undervoltage Trip Coil  
Auxiliary Contacts (N.O.)  
Auxiliary Contacts (N.C.)  
Control Relay  
Control Relay Contact (N.O.)  
Control Relay Contact (N.C.)  
Auxiliary Relay  
1. Push the trip lever in the direction of the  
a1 to a6  
b1 to b6  
X
2. The On-Off indicator changes to OFF  
(green).  
X-a  
X-b  
Y
Y-a  
ELECTRICAL OPERATION  
Auxiliary Relay Contact (N.O.)  
Auxiliary Relay Contact (N.C.)  
Y-b  
The flow chart shown in Fig. 27 illustrates the  
sequence of electrical operation of the MU and  
ML type circuit breakers.  
LS1 to LS3 Limit Switches  
R1 to R4  
REC  
D
Resistors  
Rectifier  
Diode  
Refer to Fig. 26 and the circuit breaker  
determining external control circuit connections  
to the circuit breaker.  
C
SP  
RL  
GL  
Capacitor  
Surge Protector  
Red Lamp  
Green Lamp  
Fig. 26 Legend for Schematics  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
OPERATION  
Page 21  
Circuit Breaker Open  
Control Power Applied  
Motor Begins Operating  
Closing Springs Begin Charging  
Closing Springs Charged  
Motor Stops  
- - - - Spring Status Indicator Changes to Yellow  
- - - - Standby for Close Operation  
Closing Signal Given  
Motor Begins Operating  
Circuit Breaker Closes  
Auxiliary Relay Closes  
Anti-Pumping Circuit Completed  
Opening Signal Given  
Trip Coil Energized  
- - - - Spring Status Indicator Changes to White  
and On-Off Status Changes to ON  
- - - - Next Close Operation is Not Possible  
Unless Close Signal is Canceled  
- - - - On-Off Status Indicator Changes to OFF  
Circuit Breaker Opens  
Fig. 27 Electrical Operation Flow Chart for MU  
and ML Type Breakers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Page 22  
OPERATION  
+
OFF  
K
Circuit Breaker Components  
Shown Inside Box  
C4  
15 14  
13 12 11  
16 15 14 13 12 11  
a3 a2 a1 b3 b2 b1  
a6 a5 a4 b6 b5 b4  
125 VDC  
SUPPLY  
120 VAC  
SUPPLY  
UV  
TC  
25 24  
23 22 21  
26 25 24 23 22 21  
Optional Auxiliary Contacts  
C04  
N2  
RL  
GL  
-
K
N2 C4 C04  
Terminal Layout  
(As Viewed From Front of Circuit Breaker)  
Fig. 28 125 VDC Control Circuit Schematic for U Type Circuit Breaker  
Fig. 29 125 VDC Control Circuit Schematic for L Type Circuit Breaker  
+
OFF  
Circuit Breaker Components  
Shown Inside Box  
A2 A1  
B2 B1  
C4  
K
16 15 14 13 12 11  
a3 a2 a1 b2 b1  
b6 b5 b4 a6 a5 a4  
125 VDC  
SUPPLY  
120 VAC  
SUPPLY  
UV  
TC  
A02 A01 B02 B01  
26 25 24 23 22 21  
Optional Auxiliary Contacts  
C04  
N2  
RL  
GL  
-
B2 B02  
A1 A01 A2 A02 B1 B01  
K
N2 C4 C04  
Terminal Layout  
(As Viewed From Front of Circuit Breaker)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
OPERATION  
Page 23  
+
ON  
OFF  
Circuit Breaker Components  
Shown Inside Box  
C4  
PR3  
H
K
15 14  
13 12 11  
16 15 14 13 12 11  
SP  
D
REC  
X-a  
LS2  
X-a  
X-b  
Y-b Y-a LS1  
Y-b R4  
a3  
a2 a1 b3 b2 b1  
a6 a5 a4 b6 b5 b4  
125 VDC  
120 VAC  
SUPPLY SUPPLY  
M
R2  
R3  
UV  
TC  
LS3 LS3 R1 X-a  
C
25 24  
23 22 21  
26 25 24 23 22 21  
Optional Auxiliary Contacts  
X
Y
RL  
GL  
(Connect Wires Directly To  
Auxiliary Switch Terminals)  
C04 NT3  
N2  
Components Inside Dashed Box Located  
On Control Circuit Board  
-
PR3 NT3  
H
K
N2 C4 C04  
Terminal Layout  
(As Viewed From Front of Circuit Breaker)  
+
ON  
OFF  
K
Circuit Breaker Components  
Shown Inside Box  
C4  
PR3  
H
D
A2 A1  
B2 B1  
16 15 14 13 12 11  
SP  
REC  
X-a  
LS2  
X-a  
X-b  
Y-b Y-a LS1  
Y-b R4  
a3  
a2 a1 b2 b1  
b6 b5 b4 a6 a5 a4  
125 VDC  
SUPPLY SUPPLY  
120 VAC  
M
R2  
R3  
UV  
TC  
LS3 LS3 R1 X-a  
C
A02 A01 B02 B01  
26 25 24 23 22 21  
Optional Auxiliary Contacts  
X
Y
RL  
GL  
(Connect Wires Directly To  
Auxiliary Switch Terminals)  
C04 NT3  
N2  
Components Inside Dashed Box Located  
On Control Circuit Board  
-
PR3 NT3  
H
K
N2 C4 C04  
A1 A01  
A2 A02 B1 B01  
B2 B02  
Terminal Layout  
(As Viewed From Front of Circuit Breaker)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Page 24  
OPERATION  
UNDERVOLTAGE TRIP  
All HV6AS fixed mounted circuit breakers are  
furnished with an undervoltage trip device. The  
undervoltage trip device operates to trip the  
circuit breaker OFF unless 120VAC control  
power is present at the terminals of relay UV.  
When the circuit breakers are shipped, the  
undervoltage trip device is defeated by a factory-  
installed plug (Fig. 32). If this plug is left in  
place, the circuit breaker will operate normally  
without power applied to relay UV. Removing  
this plug (Fig. 33) activates the undervoltage trip  
function.  
Fig. 33 Removing Plug From UV Trip Device  
Fig. 32 Plug Installed in UV Trip Device  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
MAINTENANCE  
Page 25  
6) Comments  
MAINTENANCE PROGRAM  
The degree of detail of the record will depend  
somewhat on the operating conditions.  
In order to ensure continued reliable and safe  
operation of the equipment, a program of  
periodic maintenance must be established.  
Operating and environmental conditions will  
usually dictate the frequency of inspection  
required. NFPA Publication 70B "Electrical  
Equipment Maintenance" may be used as a  
guide for setting up the maintenance program.  
SERVICING EQUIPMENT  
For your safety, turn off and lock out main and  
control circuit power before servicing the circuit  
breaker. Certain minimum safety procedures  
must be followed:  
1) Only qualified personnel should attempt  
Contact with energized  
components can cause  
DANGER  
this service.  
severe injury, death and  
property damage. Turn off  
and lock-out primary and  
control circuit power before  
servicing.  
2) Never perform service on or next to  
exposed components energized with line  
voltage.  
Failure to adhere to these  
safety procedures can  
Improper maintenance can  
WARNING  
result in severe injury,  
death and property  
damage.  
WARNING  
WARNING  
cause severe injury, death  
and property damage. Only  
qualified and authorized  
persons are to install,  
operate or service this  
equipment.  
Grease is conductive. Do  
not allow grease or any  
other substances to  
contaminate insulating  
materials. Contaminated  
insulators can allow a  
short-circuit or ground  
fault to occur.  
NOTE:  
Refer to the SAFETY section of this  
manual for important information.  
MAINTENANCE RECORD  
Keep a permanent record of all maintenance  
work. At a minimum, this record should include  
information on:  
1) Items inspected  
2) Reports of any testing  
3) Equipment condition  
4) Corrective actions or adjustments  
5) Date of work  
Download from Www.Somanuals.com. All Manuals Search And Download.  
     
Page 26  
MAINTENANCE  
RECOMMENDED INSPECTION AND  
MAINTENANCE TYPES  
Screw  
Nominal  
Dia.  
Tightening Torque  
NOTE:  
Refer to the SAFETY section of this  
manual for important information.  
M4  
15-20 kgf-cm  
13-17 in-lb  
M5  
M6  
30-40 kgf-cm ()  
26-34 in-lb  
50-65 kgf-cm ()  
43-56 in-lb  
120-150 kgf-cm ()  
9-11 ft-lb  
250-315 kgf-cm ()  
18-23 ft-lb  
A. Acceptance Inspection  
This inspection confirms that the circuit  
breaker unit is complete, correct as specified,  
and undamaged from shipment. The  
procedure for this inspection is outlined in the  
RECEIVING, INSPECTION AND HANDLING  
section of this manual.  
M8  
M10  
M12  
450-565 kgf-cm ()  
32-41 ft-lb  
B. Patrol Inspection  
Inspection is made of the condition of the  
circuit breaker while it is energized. Check  
that no unusual sounds or smells exist  
externally.  
Inspection Frequency: Once every 6 months  
C. Periodic Inspection  
Inspection is performed wth the circuit  
breaker de-energized. The lubrication of  
sliding and rotating parts is checked and the  
mechanism is lubricated if needed.  
Inspection Frequency: Once every 1-3 years  
or every 3000 operations (normal). Once  
every 6 years (detailed).  
Refer to Table 2 for the schedule of Periodic  
Inspections.  
D. Unscheduled Inspection  
Inspections are implemented as required.  
Inspection Frequency: As needed  
NOTE:  
The inspection frequency and points  
to be inspected may vary from the  
above recommendations depending  
on the status of use, frequency of  
switching,  
amount  
of  
current  
interrupted and other factors.  
Table 1 Tightening Torques  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
MAINTENANCE  
Page 27  
Table 2 Check Points for Periodic Inspection  
Check Point  
Operating  
Check Item  
Loose bolts,  
Check Method  
Criteria  
Disposition  
Tighten using  
screwdriver or  
wrench.  
Make sure all bolts, nuts  
and screws are tight.  
Tighten if loose.  
tightening torques.  
Mechanism nuts or screws  
Dust or foreign  
matter inside  
Visual  
inspection.  
The circuit breaker  
should be clean and  
contain no foreign matter.  
Wipe with a clean  
dry cloth.  
Indicator  
operation  
Visual  
inspection.  
Make sure the number of Check the cause  
operations is correctly  
displayed.  
and repair.  
Warpage  
Visual  
inspection.  
There should be no  
warpage or missing  
parts.  
Check the cause  
and repair.  
Smooth  
operation  
Manual  
operation.  
Visual  
Make sure moving parts  
operate smoothly.  
Apply a small  
amount of  
lubrication.  
inspection or  
touch. Check  
lubrication.  
Main Circuit Discoloration  
due to heat  
Visual  
inspection.  
Make sure there is no  
discoloration.  
Check the cause  
and repair. Tighten  
connections to circuit  
from conducting  
parts  
torques.  
Loose bolts,  
nuts or screws  
Tighten using a  
wrench.  
Make sure all bolts, nuts  
and screws are tight.  
tightening torques.  
Dust on surface Visual  
Make sure there is no  
dust on the surface.  
Wipe with a clean,  
dry cloth.  
of vacuum  
interrupter  
inspection.  
Insulator  
Dust, foreign  
matter or  
damage  
Visual  
inspection.  
Make sure there is no  
dust, foreign matter or  
breakage.  
Wipe with a clean,  
dry cloth. If  
damaged, contact  
Toshiba.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Page 28  
MAINTENANCE  
Table 2. Check Points for Inspection (cont’d)  
Check Point  
Check Item  
Check Method  
Criteria  
What to do  
Repair if  
Auxiliary  
Switch  
Terminals loose Visual  
or disconnected inspection.  
Make sure terminals are  
not loose or disconnected. disconnected.  
Tighten if loose.  
Tighten using a  
screwdriver.  
tightening torques.  
Case/contacts  
Visual  
inspection.  
Make sure there is no  
damage or warping.  
Replace if damaged  
or warped.  
Control  
Circuits  
Smooth  
Energize the  
control circuit.  
Breaker (motor-operated  
type) should charge  
quickly and smoothly.  
If the circuit fails to  
operate, check the  
cause and repair.  
movement of  
motor charging  
mechanism  
Terminals loose Visual  
Make sure terminals are  
Repair if  
or disconnected inspection.  
not loose or disconnected. disconnected.  
Tighten if loose.  
Tighten using a  
screwdriver.  
tightening torques.  
Insulation  
Resistance  
Measure-  
ment  
Meaure main  
circuit to ground 1000V.  
Megger test at  
Resistance should be  
500Mor greater.  
If the insulation  
resistance is low,  
wipe off the vacuum  
interrupter and other  
insulation surfaces  
with a clean dry  
cloth and then  
Meaure  
between main  
circuit terminals  
Megger test at  
1000V.  
Resistance should be  
100Mor greater.  
repeat the test.  
Meaure control  
circuits to  
ground  
Megger test at  
500V.  
Resistance should be  
2Mor greater.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MAINTENANCE  
Page 29  
Hazardous voltages are  
VACUUM CHECK  
present during dielectric  
testing which can result in  
severe injury or death.  
Only qualified personnel  
should conduct this testing.  
WARNING  
A sufficient level of vacuum is necessary for  
proper performance of the vacuum interrupters.  
Although vacuum leaks are rare, the vacuum  
integrity should be checked periodically. The  
relationship between dielectric breakdown  
voltage of the contact gap and internal vacuum  
interrupter pressure has been found to be  
generally predictable. Therefore, vacuum  
interrupter integrity is checked by performing a  
high potential test across the open gap of the  
interrupter.  
TEST PROCEDURE:  
1. The circuit breaker should be disconnected  
from the main circuit and be in the OFF  
position.  
2. Connect all the line side primary terminals  
together and to the output of the vacuum  
checker or AC hi-pot machine. Connect all  
the load side primary terminals together and  
to the ground terminal of the vacuum checker  
or AC hi-pot machine.  
TEST EQUIPMENT:  
Toshiba offers a compact vacuum checker (Type  
CI35-1D) which enables a quick and easy check  
on vacuum interrupter internal pressure.  
Alternatively, any commercially available AC high  
potential tester may be used which is capable of  
delivering at least 25 milliamperes at 22 kV for a  
period of one minute.  
3. Increase the voltage from zero to 22kV AC at  
a rate of approximately 2kV per second.  
Hold the voltage at this value for 1 minute  
and observe the current drawn by the  
interrupter.  
PRECAUTIONS:  
4. Decrease the voltage back to zero.  
Applying abnormally high voltage across a pair of  
contacts in vacuum may produce X-rays. The  
radiation may increase with the increase in  
voltage and/or decrease in contact spacing. X-  
radiation produced during this test with  
recommended voltage and normal contact  
spacing is extremely low and well below the  
Fig. 34 Toshiba Portable Vacuum Checker  
maximum permitted by standards.  
As an  
additional safety measure, however, it is  
recommended that all personnel keep at least 1  
meter (3.3 ft) away from the vacuum circuit  
breaker while this test is performed.  
Radiation exposure hazard.  
X-rays may cause illness or  
injury. Stay at least 1 meter  
WARNING  
(3.3 ft) away from the circuit  
breaker during the vacuum  
check test .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Page 30  
MAINTENANCE  
CRITERIA:  
Fig. 35 Application of Test Voltage for  
Vacuum Check  
1. If a current flow above 5 milliamperes is  
observed or if breakdown occurs, one or  
more of the interrupters has insufficient  
vacuum and must be replaced.  
1 minute  
22kV AC  
(31kV DC)  
Exception:  
If the current exceeds 5  
milliamperes the first time the voltage is  
brought up, reduce the voltage to zero and  
increase it again. It may be necessary to  
repeat this procedure a few times.  
Voltage  
2. If the breaker fails to meet criteria 1, then  
repeat the test on each pole separately to  
identify the damaged interrupter or  
interrupters.  
Zero  
15 sec  
15 sec  
3. If the voltage can be held for 1 minute and  
the current flow does not exceed 5  
milliamperes, the interrupter has a sufficient  
vacuum level.  
Time  
After the test is complete, discharge any residual  
static charge from the primary terminals of the  
circuit breaker.  
If a vacuum checker or AC hi-pot tester is not  
available, a DC hi potential test may be  
conducted. If a DC test is conducted, the test  
voltage must be increased to 31kV DC. The test  
duration for DC tests and the criteria for  
acceptance remain the same as for AC tests.  
Do not use DC hi-pot  
testers which employ  
unfiltered half-wave  
WARNING  
rectifiers. The peak  
voltages produced by these  
testers may exceed the  
recommended value of  
31kV. This can result in the  
production of harmful X-  
rays and may invalidate the  
test results.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISPOSAL  
Page 31  
DISPOSAL  
Contact your state environmental agency for  
details on disposal of electrical components and  
packaging in your particular area.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
STORAGE  
Page 32  
STORAGE  
If the circuit breaker is to be stored for any length  
of time prior to installation, the following  
precautions should be taken:  
1) The original packing should be restored, if  
possible.  
2) Do not subject the equipment to moisture or  
sun rays. Store in cool, clean, and dry  
location.  
3) Place a dust cover over the circuit breaker  
packaging to protect against dirt and  
moisture.  
4) Store in an upright position.  
INSPECTION DURING STORAGE  
Routine scheduled inspection is necessary if  
storage is for an extended period. The unit  
should be checked for condensation, moisture,  
corrosion, and vermin.  
Prior to installation, the circuit breaker should be  
carefully examined for evidence of physical  
damage, corrosion, or other deterioration. Refer  
to the PRE-ENERGIZATION Section of this  
manual.  
The MAINTENANCE section of this manual  
describes various types of inspections  
recommended for this circuit breaker during the  
operation period.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
SPECIFICATIONS  
Page 33  
Table 3 Circuit Breaker Ratings – Manual Operation HV6AS-U and HV6AS-L Types  
Rated Voltage  
kV, rms  
kV, rms  
kV, crest  
A, rms  
Hz  
7.2  
4.8  
Rated Low Frequency Withstand Voltage  
Impulse Withstand Voltage  
Rated Continuous Current  
Rated Frequency  
22  
60  
630  
50/60  
Rated Short-Circuit Breaking Current  
Rated Short-Circuit Making Current  
Rated Short-Time Withstand Current (2 sec)  
Rated Interrupting Time (60Hz Basis)  
Opening Time  
kA, rms  
kA, crest  
kA, rms  
cycles  
msec  
14  
35  
16  
40  
12.5  
3
8 - 25  
Rated Control Voltage (Opening)  
Rated Control Voltage (Undervoltage Trip)  
Operating Duty  
V
DC 30, 125  
AC 120  
V
O - 1 min - CO - 3 min - CO  
2 N.O. - 2 N.C.  
Auxiliary Contacts  
Weight  
kg  
22 (U Type) 25 (L Type)  
Table 4 Circuit Breaker Ratings – Motor Stored Energy Operation HV6AS-MU and HV6AS-ML  
Types  
Rated Voltage  
kV, rms  
kV, rms  
kV, crest  
A, rms  
Hz  
7.2  
4.8  
Rated Low Frequency Withstand Voltage  
Impulse Withstand Voltage  
Rated Continuous Current  
Rated Frequency  
22  
60  
630  
50/60  
Rated Short-Circuit Breaking Current  
Rated Short-Circuit Making Current  
Rated Short-Time Withstand Current (2 sec)  
Rated Interrupting Time (60Hz Basis)  
Opening Time  
kA, rms  
kA, crest  
kA, rms  
cycles  
msec  
msec  
sec  
14  
35  
16  
40  
12.5  
3
8 - 25  
Closing Time  
150 - 300  
1.5 - 3  
Charging Time  
Rated Control Voltage (Closing/Charging)  
Rated Control Voltage (Opening)  
Rated Control Voltage (Undervoltage Trip)  
Operating Duty  
V
AC 120, DC 125  
DC 30, 125  
AC 120  
V
V
O - 1 min - CO - 3 min - CO  
2 N.O. - 2 N.C.  
Auxiliary Contacts  
Weight  
kg  
24 (MU Type) 27 (ML Type)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
Page 34  
WARRANTY AND LIMITATION OF LIABILITY  
Toshiba International Corporation ("Company") warrants that all equipment and parts described herein will be free  
from defects in materials and workmanship. THIS WARRANTY WILL EXPIRE EIGHTEEN (18) MONTHS AFTER  
THE DATE ON WHICH SUCH EQUIPMENT AND PARTS (EXCLUDING REPAIRED OR REPLACEMENT  
EQUIPMENT AND PARTS FURNISHED PURSUANT TO THIS WARRANTY) ARE SHIPPED BY THE COMPANY  
TO THE INITIAL PURCHASER OR TWELVE (12) MONTHS AFTER SUCH EQUIPMENT AND PARTS  
(EXCLUDING REPAIRED OR REPLACEMENT EQUIPMENT AND PARTS FURNISHED PURSUANT TO THIS  
WARRANTY) ARE FIRST PLACED IN OPERATION, WHICHEVER PERIOD FIRST EXPIRES.  
The Company will, at its option, repair or replace such equipment or part which is defective under the terms of the  
foregoing warranty, free of charge; provided the purchaser (1) promptly notifies the Company in writing of such  
defect, and (2) furnishes the Company satisfactory proof thereof, and (3) establishes that the equipment or part has  
been properly installed, maintained and operated within the limits of rated capacity and normal usage and in  
accordance with this manual, and (4) if requested by the Company, returns the defective equipment or part to the  
Company and pays all expenses incurred in connection with such return. The repaired or replacement equipment or  
part will be delivered, free of charge, to the purchaser F.O.B. the Company's warehouse or, at the Company's option,  
F.O.B. a Company authorized service shop, not loaded on truck or other carrier. The purchaser will pay the costs  
applicable to the equipment or part following such delivery, including, without limitation, all handling, transportation,  
assembly, insurance, testing and inspection charges.  
THE FOREGOING OBLIGATION TO REPAIR OR REPLACE EQUIPMENT PARTS SHALL BE THE SOLE AND  
EXCLUSIVE REMEDY OF THE PURCHASER, ITS CUSTOMERS AND USERS OF THE EQUIPMENT AND  
PARTS FOR BREACH OF THE FOREGOING WARRANTY. THE COMPANY WILL HAVE NO OBLIGATIONS TO  
DISASSEMBLE ANY EQUIPMENT OR PART WHICH IS DEFECTIVE WITHIN THE TERMS OF THE ABOVE  
WARRANTY OR TO INSTALL ANY REPAIRED OR REPLACEMENT PART OR EQUIPMENT OR TO PAY ANY  
COSTS INCURRED IN CONNECTION WITH ANY SUCH DISASSEMBLY OR INSTALLATION. THE COMPANY,  
TOSHIBA CORPORATION AND THEIR SUPPLIERS AND SUBCONTRACTORS HEREBY DISCLAIM ALL  
OTHER EXPRESS, STATUTORY AND IMPLIED WARRANTIES, INCLUDING, WITHOUT LIMITATION, ALL  
EQUIPMENT AND PARTS FURNISHED PURSUANT TO THE FOREGOING WARRANTY AND ALL IMPLIED  
WARRANTIES OF MERCHANTABILITY.  
The total liability of the Company, Toshiba Corporation and their suppliers and subcontractors for any loss, damage  
or claim, whether in contact, tort (including negligence and liability without fault), or otherwise, arising out of,  
connected with or resulting from the equipment and parts described in this manual or the performance or breach of  
any contract for the sale or supply of such equipment and parts, or from the design, manufacture, sale, delivery,  
resale, installation, technical direction or supervision of installation, inspection, testing, repair, replacement,  
operation, maintenance or use of any such equipment or part or any service relating thereto furnished by the  
Company shall not in any event exceed the price allocable to the equipment, part or service which gives claim, loss  
or damage. In no event, whether as a breach of contract or warranty, alleged negligence, liability without fault, or  
otherwise, shall the Company, Toshiba Corporation or their suppliers or subcontractors be liable for special or  
consequential damages, including, without limitation, loss or profits or revenue, loss of equipment described herein  
or any associated equipment, cost of capital, cost of substitute equipment or parts, facilities or services, down-time  
costs, labor costs or claims of customers of the purchaser for such damages.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TOSHIBA  
TOSHIBA INTERNATIONAL CORPORATION  
13131 W. Little York Road, Houston, TX 77041,  
U.S.A.  
Tel: (713) 466-0277Fax: (713) 466-8773  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Taylor Scale TE22 User Manual
Toshiba Computer Drive AF 512E User Manual
Toshiba Computer Drive HDTC610XK3B1 User Manual
Trane Air Conditioner RAUC C20 User Manual
Tripp Lite Power Supply XL INT User Manual
Uniden Headphones BTS200 User Manual
Verilux Indoor Furnishings VD08 User Manual
Vivitar Camcorder DVR 850W User Manual
VTech Cordless Telephone USB7200 User Manual
Watlow Electric Network Card RUI Gateway User Manual