ADJUSTABLE SPEED DRIVES
GX7 Series
Download from Www.Somanuals.com. All Manuals Search And Download.
Industrial Solutions
32’’
Small Footprint
Today, the high cost of real estate and space constraints in
existing facilities make size an important factor in drive selection.
Toshiba responds with the GX7. The GX7 provides proper cooling
of internal electronic components to ensure optimum performance
and durability even in a small footprint enclosure.
. 500 to 800 HP; Only 32 Inches Wide
. 95 Inches High and 30.5 Inches Deep
. Saves Real Estate on New Designs
. Easy Replacement for Dated Drives in Existing Facilities
95’’
Industrially Hardened
The GX7 Series has the highest overload capability available
for a 600 V, 500 HP and above drive. Rated at 110% continuous
current, 130% up to 120 seconds, the GX7 can withstand load
conditions that would cause other drives to fail.
The GX7 is ready for continuous, trouble-free operation in the
most demanding manufacturing environments. In addition, it is
designed for an operating environment of -10 to 40°C at elevations
of -1000 to 1000 meters.
Variety of Communication Options
In the fast-paced manufacturing world, coordinated
systems require drive-to-drive or drive-to-control system
communication. Toshiba’s GX7 comes standard with
RS232/485 and TTL communication ports. In addition to
the standard communications features, Toshiba offers a
number of popular industrial communication protocol options
including: Modbus RTU, Modbus Plus, Ethernet IP, Profibus
DP, DeviceNet and Johnson Controls Metasys N2.
Download from Www.Somanuals.com. All Manuals Search And Download.
Proven Technology
Advanced Electronic Operator Interface
The GX7’s Electronic Operator Interface (EOI) features a multi-line, graphics-capable,
plain English, back-lit LCD. The EOI is so intuitive that the manual is usually unneeded
to make setting adjustments. The GX7 has menu-driven programming as well as direct
access to the parameters. A high reliability rotary encoder makes programming easy.
Startup Wizard helps facilitate initial programming.
Configurables
• Easy to Remote-Mount the Display (up to 1000 Feet)
• Real-Time Clock Option (Stores up to 100 Past Faults with Date and Time Stamp)
• Graphics-Capable LCD to Aid in Diagnostics
• Flash-Upgradeable EOI Software
• Help from Toshiba Customizing Application-Specific Wizards
Standard Keypad Design for Low Voltage and Medium Voltage Drives
Monitor Software
The free monitor software allows the user to monitor and control critical operational
parameters using serial communication. The software contains real-time graphing, a very
useful tool for data analysis which allows files and tables to be created with the software
from the obtained data.
Process Control
The built-in Proportional/Integral/Derivative (PID) control loop provides regulation of
many processes without the need for external devices. Deviation limits, online switching,
and delay filtering functions are included to enhance the flexibility and reliability of PID
process control.
Download from Www.Somanuals.com. All Manuals Search And Download.
Meets or Exceeds
Your Specifications
GX7 Specifications
Standard Specifications
Item
Voltage Class
Maximum HP
Drive Rating (A)
Dimensions
600 VAC
600 HP
500 HP
481 A
700 HP
698 A
800 HP
770 A
601 A
95”H x 32”W x 30.5”D
Power Requirements
Output Frequency
Control Power
Tolerance
0 to 299 Hz
DC Bus Control Power
Voltage: ±10%; Frequency: ±2%
Control Specifications
Sine Wave PWM System; Flux Field Current Vector Control
Control Method
V/Hz Control
Constant Torque, Variable Torque, Open-Loop Vector, Auto or Manual Torque Boost, 5-Point V/Hz Custom Curves
130% for 120 Seconds; 110% Continuous
Overload Rating
Frequency Setting
Frequency Precision
Frequency Resolution
Acceleration / Deceleration
Speed Regulation
Torque Setting
Rotary Encoder Integrated into EOI, 0 to 10 V, ±10 V, 4 to 20 mA, Binary Input, Motorized Potentiometer Input
Analog Input: ±0.2% of Maximum Output Frequency; Digital Input: ±0.01% of Maximum Output Frequency
Panel Operation: 0.01 Hz; Analog Input 10 to 12-Bit A to D Converter: 0.1 Hz
0.1 to 6000 Seconds
Up to 0.1%; 60:1 Speed Range
±250% of the Rated Torque
Proportional Gain, Integral Gain, Feedback Settings Upper/Lower Deviation Limits, Feedback Source Delay Filter, Feedback Settings
Differential Gain
Set Point Control (PID)
Analog Inputs
Four Programmable: (1) 4 to 20 mA, (1) 0 to 10 V, (1) -10 to +10 V, (1) 1 to 10kΩ Potentiometer Connection
Two Programmable to 31 Functions
Analog Outputs
Discrete Inputs
Output Contacts
Signal Isolation
Power Terminals
Eight Programmable to 67 Functions; Expandable to N-Value
Three Output Terminals, Programmable to 52 Functions; Form C Contacts Rated 250 V AC, Two Amps Inductive
Available Three-Channel Signal Isolation for AM/FM Outputs and II Terminal Input, Rated at 750 V
Input (L1, L2, L3) Output (T1, T2, T3) DCL (PO, PA), DBR (PA, PB), DCBUS (PA, PC)
Control Board
Communication Ports
RS232/485 and TTL Ports Standard
Data Transmission
Profibus, DeviceNet, Modbus RTU, Modbus+, Metasys, Ethernet (Some Devices are External)
Main Protective
Functions
Current Limit, Overcurrent, Overvoltage, Undervoltage, Load-Side Short Circuit, Load-Side Ground Fault, Armature Short; Overtorque,
ASD Overload, Motor Overload, Heatsink Overheat, Open Output Phase, Loss of Feedback, CPU Error, Communications Error
Soft Stall
Retry
Automatic Load Reduction Control During Overload
Can Automatically Clear Fault Upon Trip; Programmable to 10 Tries with up to 10 Seconds Between Tries
Restart into a Rotating Motor
Restart
Interface
LCD/EOI (Liquid Crystal
Display/Electronic
Operator Interface)
Backlit LCD Display; Ability to Display Multiple Parameters on One Screen; Keypad may be Operated from External Power Source;
Software is Flash Upgradeable; Includes Multi-Function Rotary Encoder
LED Indicators
Keys
Monitoring
Run (Red)/Stop (Green), Remote/Local (Green), DC Bus Charge Indication (Red)
Local/Remote, Monitor/Program, Run, Enter, ESC, Stop/Reset, Up, Down
Main Display Shows Two Monitored Items Continuously, or Scrolls Up to 40 Items
User-Selectable and Configurable along with Scaling Factor Multiplier; Voltage Display Selectable: Volts or %;
Current Display Selectable: Amps or %.
Selectable Display Units
EOI Communication Ports
Remote-Mount Display
RS232/485 and TTL Ports Standard
Remote Mountable Up to 1000 Feet
Construction
Enclosure
Panel Construction
Cooling
NEMA 1, IP20, Gasketed and Filtered
Free-Standing, Front-Maintenance Type, Top or Bottom Access for Motor and Power Cables
Forced-Air Cooled Top-Mounted Fans may be Removed During Shipment or Installation
ANSI-61 Gray
Color
Ambient Conditions
-10 to 40°C (-14 to 104°F)
Max. 95% (Non-Condensing)
1000 Meters (3300 Feet) Above Sea Level or Less
Indoor, No Direct Sunlight, Protect from Corrosive Gases and/or Explosive Gases
Ambient Temperature
Humidity
Altitude
Installation
Standards
Electrical Compliance
NEC, ANSI
Download from Www.Somanuals.com. All Manuals Search And Download.
North American Headquarters and Manufacturing Facility (Houston, TX)
TOSHIBA — Quality by Design
Toshiba's culture and history is strongly rooted in quality. Our designs are
technologically innovative, and our products are manufactured from start to
end using only the highest quality domestic and foreign parts.
Product Warranty
Toshiba offers a comprehensive warranty program on its full line of industrial
products. Consult your salesperson or the factory for specific information.
Need to Know More?
information on Toshiba products and services.
Customer Support Services
Toshiba offers 24 hour service nationwide. For assistance of any type,
call: 1-800-231-1412.
ADJUSTABLE SPEED DRIVES
MOTORS
CONTROLS
UPS
INSTRUMENTATION
PLC
Available Through:
INDUSTRIAL DIVISION
13131 West Little York Road, Houston, Texas 77041
Tel 713/466-0277 Fax 713/466-8773
US 800/231-1412 Canada 800/872-2192 Mexico 01/800/527-1204
Copyright 1/2008