UNINTERRUPTIBLE POWER SYSTEM (UPS)
G8000 SERIES
INSTALLATION and
OPERATION MANUAL
480/480 V 100/150/225/300 kW
Document: 61001-001
July 2012
© Copyright 2012 Toshiba International Corporation
All rights reserved.
Download from Www.Somanuals.com. All Manuals Search And Download.
UNINTERRUPTIBLE POWER SYSTEM (UPS)
G8000 SERIES
INSTALLATION and OPERATION MANUAL
480/480 V 100/150/225/300 kW
Document: 61001-001
July 2012
© Copyright 2012 Toshiba International Corporation
All rights reserved.
G8000 Series Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
The Toshiba products listed in this document are intended for usage in general electronics applications
(computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic
appliances, etc.). These Toshiba products are neither intended nor warranted for usage in equipment
that requires extraordinarily high quality and/or reliability; nor are they intended to be used in equipment
that, if a malfunction or failure occurs, may result in loss of human life or bodily injury (collectively
referred to as “Unintended Usage”). Unintended Usage includes atomic energy control instruments,
airplane or spaceship instruments, transportation instruments, traffic signal instruments, combustion
control instruments, life support equipment, all types of safety devices, etc. Unintended Usage of Toshiba
products listed in this document shall be made at the customer’s own risk.
NOTICE
PLEASE INFORM TOSHIBA INTERNATIONAL CORPORATION OR AUTHORIZED
REPRESENTATIVE IN CASE OF INCONSISTENCIES, OMISSIONS, OR QUESTIONS.
The instructions contained in this manual are not intended to cover all of the details or variations in
equipment,nortoprovideforeverypossiblecontingencyconcerninginstallation,operation,ormaintenance.
Should further information be required or if problems arise which are not covered sufficiently contact your
Toshiba sales office.
The contents of this instruction manual shall not become a part of or modify any prior or existing
agreement, commitment, or relationship. The sales contract contains the entire obligation of Toshiba
International Corporation’s UPS Division. The warranty contained in the contract between the parties
is the sole warranty of Toshiba International Corporation’s UPS Division and any statements contained
herein DO NOT create new warranties or modify the existing warranty.
Any electrical or mechanical modifications to this equipment without prior written consent of Toshiba
International Corporation will void all warranties and may void the UL/CUL listing. Unauthorized
modifications can also result in personal injury, death, or destruction of the equipment.
QUALIFIED PERSONNEL ONLY
Qualified Personnel is one that has the skills and knowledge relating to the construction,
installation, operation, and maintenance of the electrical equipment and has received safety
training on the hazards involved (Refer to the latest edition of NFPA 70E for additional safety
requirements).
G8000 Series Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
UNINTERRUPTIBLE POWER SYSTEM (UPS)
Please complete the following information and retain for your records.
Unless otherwise specified, the warranty period for the UPS or UPS part is 12 months from the shipment
date (see Toshiba International Corporation bill of lading).
Unless otherwise specified, the warranty period for a UPS battery is 36 months from the shipment date
(see Toshiba International Corporation Bill of Lading for shipping date).
JOB NUMBER
MODEL NUMBER
SERIAL NUMBER
APPLICATION
SHIPMENT DATE
INSTALLATION DATE
INSPECTED BY
G8000 Series Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Purpose
This manual provides information on how to safely install and operate your Toshiba International
Corporation power electronics product. This manual includes a section of general safety instructions
that describes the warning labels and symbols that are used throughout the manual. Read the manual
completely before installing, operating, or performing maintenance on this equipment.
This manual and the accompanying drawings should be considered a permanent part of the equipment
and should be readily available for reference and review. Dimensions shown in the manual are in metric
and/or the English customary equivalent.
Toshiba International Corporation reserves the right, without prior notice, to update information, make
product changes, or discontinue any product or service identified in this publication.
Toshiba is a registered trademark of the Toshiba Corporation. All other product or trade references
appearing in this manual are registered trademarks of their respective owners.
Toshiba International Corporation shall not be liable for direct, indirect, special, or consequential damages
resulting from the use of the information contained within this manual.
This manual is copyrighted. No part of this manual may be photocopied or reproduced in any form without
the prior written consent of Toshiba International Corporation.
© Copyright 2008 Toshiba International Corporation
All rights reserved.
Printed in the U.S.A.
Toshiba’s Customer Support Center
Contact the Toshiba Customer Support Center for assistance with application information or for any
problems that you may experience with your Uninterruptible Power System (UPS).
Toshiba Customer Support Center
8 a.m. to 5 p.m. (CST) - Monday through Friday
USA Toll Free (877) 867-8773
Tel (713) 466-0277
Fax (713) 896-5212
You may also contact Toshiba by writing to:
Toshiba International Corporation
13131 West Little York Road
Houston, Texas 77041-9990
Attn: UPS Product Manager
For further information on Toshiba’s products and services, please visit our website at:
G8000 Series Installation and Operation Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
2.1 Symbols .......................................................................................................................2
2.2 Signal Words................................................................................................................3
2.3 Qualified Personnel......................................................................................................3
2.4 Factory Authorized Personnel......................................................................................4
Safety Precautions..............................................................................................................5
4.1 Disclaimer ....................................................................................................................5
4.2 General Maintenance...................................................................................................6
4.3 Transporting/Unpacking...............................................................................................6
4.4 Inspection/Storage.......................................................................................................8
Installation Precautions......................................................................................................9
Warning Labels....................................................................................................................14
6.1 Warning Label Locations..............................................................................................15
8.1 Transporting By Crane.................................................................................................20
8.2 Transporting By Forklift................................................................................................21
Storage/Operating Environment........................................................................................22
9.1 Operating Precautions .................................................................................................22
9.2 Maintenance Precautions ............................................................................................24
9.3 Disposal .......................................................................................................................25
10.1 Unpacking..................................................................................................................27
10.2 UPS Clearance ..........................................................................................................27
10.3 Anchor Bolts...............................................................................................................28
11 UPS Wiring .........................................................................................................................29
11.1 100 kVA Terminal Blocks and Power Cables..............................................................30
11.3 UPS Power Cable Knockout Plates ...........................................................................34
G8000 Series Installation and Operation Manual
i
Download from Www.Somanuals.com. All Manuals Search And Download.
11.4 External Breakers.......................................................................................................36
11.5 Grounding Wire..........................................................................................................36
11.6 Control Wires..............................................................................................................38
11.7 Grounding Configuration............................................................................................40
12 UPS Specifications............................................................................................................43
12.1 General Specification.................................................................................................43
12.2 Mechanical Specification ...........................................................................................43
12.3 Electrical Specification...............................................................................................45
13 Operator Interface .............................................................................................................46
13.1 Key-Switch and Buttons.............................................................................................47
13.2 LCD/LED Indicators ...................................................................................................48
13.3 LCD Indicators ...........................................................................................................49
13.4 Normal Display...........................................................................................................50
13.5 Fault Display ..............................................................................................................52
13.6 LCD Scroll..................................................................................................................53
14 Operating the UPS.............................................................................................................54
14.1 Operation Types.........................................................................................................55
14.2 Pre-operational Check ...............................................................................................55
14.3 Startup Procedures....................................................................................................56
14.4 Switch Power Supply (UPS→Bypass).......................................................................58
14.6 Complete Shutdown...................................................................................................60
14.7 Changing Between Float Charge and Equalize Charge ............................................61
14.9 Emergency Power Off (EPO).....................................................................................63
15 Troubleshooting ................................................................................................................63
15.1 Types of Errors...........................................................................................................63
15.2 Faults and Warnings Data Screen .............................................................................64
15.3 LCD Fault & Warning Displays...................................................................................65
15.4 Fault Messages..........................................................................................................66
15.5 LCD Scroll (w/ faults or warnings)..............................................................................68
15.6 Restoring UPS Operation ..........................................................................................69
G8000 Series Installation and Operation Manual
ii
Download from Www.Somanuals.com. All Manuals Search And Download.
1 Introduction
This manual provides information on how to safely operate your G8000 Series Uninterruptible Power
System (UPS). This manual includes a section of general safety instructions that describes the warning
labels and symbols that are used throughout the manual. Read the manual completely before installing,
operating, or performing maintenance on this equipment.
Qualified personnel should read this manual carefully before transporting, installing and wiring the UPS.
In addition have a thorough understanding of the information provided in the chapters titled:
• General Safety Instructions
• Important Safety Instructions
• Safety Precautions
• Installation Precautions
Please read the G8000 Series Operation Manual for important instructions on operating the UPS. This
manual and the accompanying drawings should be considered a permanent part of the equipment and
should be readily available for reference and review. Dimensions shown in the manual are in metric and/
or the English customary equivalent.
Keep the Installation Manual and the Operation Manual near the UPS for necessary reference.
SAVE THESE INSTRUCTIONS
G8000 Series Installation and Operation Manual
1
Download from Www.Somanuals.com. All Manuals Search And Download.
2 General Safety Instructions
DO NOT attempt to transport, install, operate, maintain or dispose of this equipment until you have read
and understood all of the product safety information provided in this manual.
2.1 Symbols
The symbols listed below are used throughout this manual. When symbols are used in this manual they
will include important safety information that must be carefully followed.
Safety Alert Symbol indicates that a potential
personal injury hazard exists.
Prohibited Symbol indicates DO NOT take action.
Mandatory Symbol indicates that the following
instruction is required.
Ground Symbol indicates the location of the
equipment grounding conductor.
Electrical - Voltage & Shock Hazard Symbol
indicates parts inside may cause electric shock.
Explosion Hazard Symbol indicates parts may
explode.
G8000 Series Installation and Operation Manual
2
Download from Www.Somanuals.com. All Manuals Search And Download.
2.2 Signal Words
The signal words listed below are used throughout this manual. When the words DANGER, WARNING,
CAUTION and ATTENTION are used in this manual they will include important safety information that
must be carefully followed.
The word DANGER in capital letters preceded by
the safety alert symbol indicates that an imminently
hazardous situation exists, if not avoided, will
DANGER
result in death or serious injury to personnel.
The word WARNING in capital letters preceded by
the safety alert symbol indicates that a potentially
hazardous situation exists, if not avoided, could
WARNING
result in death or serious injury to personnel.
The word CAUTION in capital letters preceded by
the safety alert symbol indicates that a potentially
hazardous situation exists, if not avoided, may
CAUTION
result in minor or moderate injury.
The word CAUTION in capital letters without
the safety alert symbol indicates a potentially
hazardous situation exists, if not avoided, may
CAUTION
result in equipment and property damage.
The word ATTENTION in capital letters without
the safety alert symbol indicates a potentially
hazardous situation exists, if not avoided, may
ATTENTION
result in equipment and property damage.
2.3 Qualified Personnel
Installation, operation, and maintenance shall be performed by Qualified Personnel Only. A Qualified
Person is one that has the skills and knowledge relating to the construction, installation, operation,
and maintenance of the electrical equipment and has received safety training on the hazards involved
(Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel shall:
•
•
Have read the entire operation manual.
Be familiar with the construction and function of the UPS, the equipment being driven, and the
hazards involved.
•
•
•
Able to recognize and properly address hazards associated with the application of motor-driven
equipment.
Be trained and authorized to safely energize, de-energize, ground, lockout/tagout circuits and
equipment, and clear faults in accordance with established safety practices.
Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves,
hard hats, safety glasses, face shields, flash clothing, etc., in accordance with established safety
practices.
G8000 Series Installation and Operation Manual
3
Download from Www.Somanuals.com. All Manuals Search And Download.
•
Be trained in rendering first aid.
2.4 Factory Authorized Personnel
Factory authorized personnel have been factory trained and certified to install, service, and repair the
UPS. Contact the Toshiba Customer Support Center for assistance in locating the factory authorized
personnel nearest you.
3 Important Safety Instructions
The following contains important instructions that should be followed during the installation, operation,
and maintenance of the G8000 Series UPS.
Please refer to the battery manufacturer’s instructions for details on operating, maintaining and/or
replacing the batteries for each system. Keep unauthorized personnel from batteries. Only a certified
service representative with battery experience should perform service on batteries.
CAUTION
Misuse of this equipment could result in personal injury and/or equipment damage.
In no event will Toshiba Corporation be responsible or liable for either indirect or
consequential damage or injury that may come from the use of this equipment.
The UPS system input and output is NOT equipped with an over-current protection device, or an
output disconnection at the AC output. The user should provide circuit breakers between the UPS AC
input (or Bypass input) and the power sources and between the UPS output and the critical load input.
The minimum device ratings are listed in Table 3.1.
TABLE 3.1 UPS MINIMUM DEVICE RATINGS
CapaCity
100 kVA
150 kVA
225 kVA
300 kVA
Rated output
480 V/277 V
480 V/277 V
480 V/277 V
480 V/277 V
iNput BReakeR RatiNg
480 V-200 A
output BReakeR RatiNg
480 V-150 A
480 V-300 A
480 V-225 A
480 V-450 A
480 V-350 A
480 V-500 A
480 V-450 A
The maximum operating ambient temperature is 86 °F (30 °C) at 1.0 PF, and 104 °F (40 °C) at 0.8 PF.
If the UPS is exposed to the same ambient temperature as the battery system, the maximum operating
ambient temperature is 86 °F (30 °C) at 1.0 PF, 90 °F (32 °C) at 0.8 PF. Table 3.2 lists the nominal battery
voltage.
TABLE 3.2 UPS NOMINAL BATTERY VOLTAGE
CapaCity
100 kVA
150 kVA
225 kVA
300 kVA
NomiNal Voltage
360 Vdc
Float Voltage
405 V
360 Vdc
405 V
360 Vdc
405 V
360 Vdc
405 V
G8000 Series Installation and Operation Manual
4
Download from Www.Somanuals.com. All Manuals Search And Download.
4 Safety Precautions
The Toshiba products listed in this document are intended for usage in general electronics applications
(computer, personal equipment, office equipment, measuring equipment, industrial robotics, domestic
appliances, etc.). These Toshiba products are neither intended nor warranted for use in equipment that,
if a malfunction or failure occurs, may result in loss of human life or bodily injury (collectively referred
to as “Unintended Usage”). Unintended Usage includes atomic energy control instruments, airplane
or spaceship instruments, transportation instruments, traffic signal instruments, combustion control
instruments, medical operating room or life support equipment, all types of safety devices, etc. Unintended
Usage of Toshiba products listed in this document shall be made at the customer’s own risk.
The application of the UPS without special consideration for equipment that supports human safety and/
or maintain public services may cause serious accidents.
4.1 Disclaimer
IN NO EVENT WILL TOSHIBA CORPORATION BE RESPONSIBLE OR LIABLE FOR EITHER
INDIRECT OR CONSEQUENTIAL DAMAGE OR INJURY THAT MAY COME FROM THE USE OF THIS
EQUIPMENT. ANY MODIFICATIONS WITHOUT AUTHORIZATION BY TOSHIBA COULD RESULT IN
PERSONAL INJURIES, DEATH OR DESTRUCTION OF THE UPS.
TOSHIBA RESERVES THE RIGHT TO MAKE CHANGES WITHOUT FURTHER NOTICE TO ANY
PRODUCTS HEREIN TO IMPROVE RELIABILITY, FUNCTION OR DESIGN. TOSHIBA DOES NOT
ASSUME ANY LIABILITY ARISING OUT OF THE APPLICATION OR USE OF ANY PRODUCT OR UPS
DESCRIBED HEREIN; NEITHER DOES IT CONVEY ANY LICENSE UNDER ITS PATENT RIGHTS,
NOR THE RIGHTS OF OTHERS.
G8000 Series Installation and Operation Manual
5
Download from Www.Somanuals.com. All Manuals Search And Download.
4.2 General Maintenance
WARNING
DO NOT remove the rear/side panels, or any sheet metla not
designed to be removed.
Removing rear/side panels may result in electric shock, burns,
personal injuries or UPS failure.
Keep the area arround the UPS clean.
Use a vacuum cleaner to clean the UPS.
Only factory authorized personnel sould perform internal general
maintenance on the UPS.
Contact the authorized Toshiba Customer Support Center or
an authorized Toshiba representative for informaton on proper
disposal of UPS components.
It is illegal to dispose of certain components without conforming to
environmental regulations for indusrial/commercial waste.
4.3 Transporting/Unpacking
WARNING
WhentransportingtheUPSbycrane,followtheSPECIFIEDWORKPROCEDURE.
The suspension wire angle should be less than 60°.
The UPS falling or overturning may cause crushing, trapping or other personal
injuries.
See Installation Manual: Chapter 8 - Transporting
DO NOT tilt the UPS more than 10° from upright position.
Tilting the UPS more than 10° may cause crushing, trapping or other
personal injuries.
G8000 Series Installation and Operation Manual
6
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION
DO NOT transport, move, store, or place the UPS on its side.
Forces due to heavy components inside may damage the UPS.
Avoid vibration or shock exceeding 0.5G.
Failing to observe this precaution may cause damage to the UPS.
DO NOT allow the UPS to suffer shock or impact when
unpacking.
Tools used to remove packaging materials may cause damage to the
UPS.
DO NOT push or pull on the sides of the packaging.or the
UPS to move it. Always use a crane, forklift, or pallet jack for
transporting and positioning the UPS.
Pushing/pulling on the sides of the unit to move it may result in damage
to the UPS. See Figure 4.1 Exterior Handling label.
Fig. 4.1 Exterior Handling label
BY CRANE:
- Cables should have sufficient rating
and equal length.
- Keep UPS leveled when lifting/lowering
and avoid impacts.
BY FORKLIFT:
- Verify forklift maximum load capacity.
Do not push or
pull from sides
- Ensure that the forks are long enough
to support the UPS and are inserted
properly.
Do not push or
pull from sides
CKSIDE
- Do not swing or tilt the UPS when
lifting and/or transporting.
BA
See manual for complete details.
FORKS (4 Ft. Minimum length)
WARNING:
Risk of tipping. For safe handling, lift UPS from back and sides only (as shown above)
G8000 Series Installation and Operation Manual
7
Download from Www.Somanuals.com. All Manuals Search And Download.
4.4 Inspection/Storage
Inspection
Upon receipt of the UPS, an inspection for shipping damage should be performed. Use caution when
removing the unit from the pallet. Refer to labels or documentation attached to packing material.
Unpacking
Check the unit for loose, broken, bent or otherwise damaged parts. If damage has occurred during shipping,
keep all original crating and packing materials for return to the shipping agent.
NOTE: The factory warranty does not apply to damage incurred during shipping!
Ensure that the rated capacity and the model number specified on the nameplate conform to the order
specifications.
Storage
During periods of non-use, the following guidelines are recommended for storage.
Storage Preparation
1) Power up the UPS and allow it to operate with no load for 24 hours to fully charge
the batteries.
2) Stop the unit.
3) Place the Main Circuit Breaker switch in the “OFF” position.
Storage Conditions
• For best results, store the UPS in the original shipping container and place on a wood
or metal pallet
• Storage temperature range: -4 to 104 °F (-20 to 40 °C)
• The optimum storage temperature is 70 °F (21 °C). A higher ambient temperature will
require recharging more frequently during storage
Avoid the following storage locations:
• Locations that are subject to extreme temperature changes or high humidity
• Locations that are subject to high levels of dust or metal particles
• Locations that are subject to excessive vibration
• Inclined floor surfaces
G8000 Series Installation and Operation Manual
8
Download from Www.Somanuals.com. All Manuals Search And Download.
5 Installation Precautions
CAUTION
Install the UPS in a controlled environment.
Improper storage and installation environment may deteriorate
insulation, shorten component life and cause malfunctions.
See Table 5.1 - UPS Installation Environment Standards
DO NOT tilt the UPS more than 10° from upright position.
Tilting the UPS more than 10° may cause crushing, trapping or other
personal injuries and cause physical damage to internal components.
WARNING
Keep the SPECIFIED CLEARANCE around the UPS.
Inadequate space around the UPS makes it difficult to perform
maintenance/inspections, will lead to insufficient ventilation, and/or
cause malfunctions.
Install anchor bolts to secure the UPS to the installation floor.
The UPS may fall during an earthquake if the anchor bolts are not
installed and secured.
Only factory authorized personnel should relocate, modify, or
replace parts in the UPS after initial installation.
Electrical shock, injury or UPS failure may occur if non-authorized
technicians attempt to modify or relocate the UPS.
Please contact Toshiba Customer Support Center if you plan to move
or make modifications to the UPS
G8000 Series Installation and Operation Manual
9
Download from Www.Somanuals.com. All Manuals Search And Download.
DO NOT block air vents.
Blocking the vents will increase the internal temperatures and may
result in UPS failure or fire.
DO NOT install the UPS where water may fall on it.
Water may cause electrical shock, personal injury or UPS failure.
DO NOT use floor wax that contains silicon in the UPS storage
area and/or nearby rooms.
Floor wax that contains silicon may cause static electricity.
WARNING
The UPS should be installed per local and/or national electric codes
by qualified personnel.
Faults or improper operation may occur if the UPS is not installed
properly.
When an external maintenance bypass is installed for the UPS,
before switching to external bypass, ensure that the UPS unit is
switched to AC Bypass mode and the UPS control panel display
verifies the unit is Bypass mode.
Switching to the external bypass while the unit is in UPS mode may
damage the UPS.
G8000 Series Installation and Operation Manual
10
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 5.1 - UPS INSTALLATION ENVIRONMENT STANDARDS
Item
Environment standard
Installation Location Indoors
Minimum operating temperature: 32 °F (0 °C).
Maximum operating temperature: 86 °F (30 °C) at 1.0 PF (UPS with/without
battery system).
Ambient
Temperature
Maximum operating temperature: 90 °F (32 °C) at 0.8 PF (UPS with battery
system).
Maximum operating temperature: 104 °F (40 °C) at 0.8 PF (UPS only).
Average 24-hour operating temperature: 86 °F (30 °C) at 1.0 PF and 41 – 95 °F
(5 – 35 °C) at 0.8 PF.
The relative humidity must be between 30 and 90% noncondensing due to
temperature changes.
Relative Humidity
Altitude
These specifications are for altitudes up to 3240 ft. (1000 m) above sea level.
Consult with the factory to determine the derating factor for installations above
3240 ft. (1000 m).
Installation environment must not have vibration frequencies 10 Hz – 20 Hz.
The acceleration due to vibrations less than 10 Hz must not exceed 0.5 G.
The acceleration due to vibrations 20 Hz – 50 Hz must not exceed 0.5 G.
The total amplitude due to vibrations 50 Hz – 100 Hz must not exceed 0.1 mm.
Vibration and
Mechanical Shock
Dust must not exceed normal atmospheric levels and must not include conductive
particles, silicone or oils.
Dust
No flammable and/or explosive gas.
Hydrogen sulfide (H2S)
Sulfurous acid gas (SO2)
Chlorine gas (Cl2)
Less than or equal to 0.0001 PPM
Less than or equal to 0.05 PPM
Less than or equal to 0.002 PPM
Less than or equal to 0.1 PPM
Less than or equal to 0.02 PPM
Flammable Gas
Ammonia gas (NH3)
Nitrous acid gas (NO2)
Nitrous oxides (NOx)
Ozone (O3)
Less than or equal to 0.02 PPM
Less than or equal to 0.002 PPM
Hydrochloric acid mist (HCl)
Less than or equal to 0.1 mg/m3
Installation Precautions
1) Install the unit in a stable, level and upright position that is free of excessive
vibration.
2) Install the unit where the ambient temperature is within the specified range.
3) DO NOT install the UPS in areas that are subject to high humidity.
4) DO NOT install the UPS in areas that allow exposure to direct sunlight.
5) DO NOT install the UPS in areas that allow exposure to high levels of airborne dust,
metal particles, or flammable gases.
6) DO NOT install the UPS in areas near sources of electrical noise. Ensuring a proper
earth ground will reduce the effects of electrical noise and will reduce the potential for
electrical shock.
G8000 Series Installation and Operation Manual
11
Download from Www.Somanuals.com. All Manuals Search And Download.
7) The UPS generates and can radiate radio-frequency energy during operation.Although
RFI noise filters are installed inside of the unit, there is no guarantee that the UPS will
not influence some sensitive devices that are operating near by. If such interference
is experienced, the UPS should be installed further away from the affected equipment
and/or powered from a different source than that of the installed equipment.
8) The user should provide over-current protection for hardwired UPS systems between
the UPS output and the load input.
9) After ensuring that all power sources are turned “OFF” and isolated in accordance with
established lockout/tagout procedures, connect the power source wiring of the correct
voltage to the input terminals of the UPS.
NOTE: Ensure the input phasing is connected in clockwise rotation (CW). UPS
internal circuitry is designed to disable further UPS operation if the input
phasing is installed in counter-clockwise rotation (CCW).
10) Connect the output terminals of the UPS to the load (refer to NEC Article 300 - Wiring
Methods and Article 310 - Conductors For General Wiring). Size the branch circuit
conductors in accordance with NEC Table 310.16 as published 9/2007.
WARNING
METAL CONDUIT IS NOT AN ACCEPTABLE GROUND.
Conductor Routing and Grounding
1) Use separate metal conduits for routing the input power, output power, and control
circuits.
2) Follow the wire size and tightening torque specifications.
3) Always ground the unit to reduce the potential for electrical shock and to help reduce
electrical noise.
4) A separate ground cable should be run inside the conduit with the input power, output
power, and control circuits.
G8000 Series Installation and Operation Manual
12
Download from Www.Somanuals.com. All Manuals Search And Download.
5.1 Wiring/Connection
WARNING
Perform wiring and connections with correct polarity.
Be careful when connecting the UPS to the battery system. A wrong
connection may cause damage to the UPS, battery, or charger.
Connect ONLY one (1) ground wire to the earth ground terminal.
A missing ground wire may cause an electrical shock hazard.
Connecting to more than one ground may cause a ground loop.
See Chapter 8 - UPS Wiring
DO NOT force, bend, or pull wires.
DO NOT damage wire insulation.
DO NOT place heavy objects on top of UPS.
Observe the above precautions when making wire connections or
handling the wires. Failing to observe these precautions may damage
the insulation of the wires or may cause a fire or an electric shock
hazard.
ATTENTION
Follow the torque criteria for tightening screws.
Loose connections may cause fire due to heating.
See Chapter 11 - UPS Wiring
G8000 Series Installation and Operation Manual
13
Download from Www.Somanuals.com. All Manuals Search And Download.
6 Warning Labels
Below are representative warning labels and their location on the UPS. Exterior Handling labels shown
in section 4.3, Transporting/Unpacking, are in the manual packet, and attached to the UPS shipping
covering and shipping pallet.
ATTENTION
Make sure all the warning labels are installed in the appropriate locations.
If a label is missing or illegible, contact Toshiba Customer Support Center or an
authorized representative.
(A) 48082
(B) 40308
DANGER
DANGER
AC VOLTAGE
HAZARDOUS VOLTAGES
Hazardous voltages are used in the operation
of this equipment and could cause severe personal
injury or loss of life.
The following precautions should be observed to
reduce the risk of injury or death.
This UPS receives power from more
than one source. Disconnect all AC
sources before performing any service
or testing inside this unit
Only qualified technicians familiar with this equipment and the
information supplied with it should be permitted to install and
operate this equipment.
Installation of electrical equipment must be done i n
accordance with National Electrical Code and any other state
or local codes. Proper grounding and conductor siz ing must
be installed for safe operation.
48082
During operation, keep all covers in place and cabi net
doors shut.
When performing visual inspections and maintenance, if
possible, be sure the UPS is turned off and the inc oming
AC feed is turned off and locked out.
The UPS and Battery Cabinet will have hazardous
voltages present even after the AC feed is turned off.
(C) 56875 FOR 100, 150, 225KVA
If it is necessary to make measurements with the power
on, do not touch any electrical connection points. Remove
all jewelry from wrists and fingers. Make sure test equipment
is in good, safe operating condition.
USE COPPER CONDUCTORS ONLY!
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE
1
2
3
4
5
6
7
8
9
10
W
11
N
12
13
While servicing, stand on some type of insulation, and be
sure not to be grounded.
U
V
W
U
V
W
N
U
V
-
+
480V
480V
AC OUTPUT
400V
480V
BYPASS INPUT
Follow the safety instructions given in the equipment manual
carefully and observe all danger, warning and cauti on notices.
AC INPUT
BATTERY
40308
(C) 58708 FOR 300KVA
USE COPPER CONDUCTORS ONLY !
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE AND TIGHTENING TORQUE
(D) 40830
WARNING
CRITICAL FUSE SIZING
1
2
3
6
7
8
9
10
U
11
V
12
W
4
5
Incorrect fuse replacement size
may result in fire or inadequate
equipment protection.
U
V
W
U
V
W
N
-
+
480V
400V
480V
AC OUTPUT
480V
BYPASS INPUT
AC INPUT
BATTERY
Replace only with same type
and rating of fuse.
PN 40830
G8000 Series Installation and Operation Manual
14
Download from Www.Somanuals.com. All Manuals Search And Download.
(E) 39561
(F) 58705 SERIAL LABEL
UNINTERRUPTIBLE POWER SUPPLY
(G) 57055
GND
DANGER
RISK OF ELECTRIC SHOCK
Capacitors stay charged after power
has been shut off.
Accidental contact with live parts can
cause personal injury and death.
Turn off and lock out all power sources.
Wait at least five (5) minutes for power
to dissipate then check voltage before
servicing.
39561
58705
LISTED
27E5
MFD. IN U.S .A. FR OM FOREIGN AND DOMES TIC C OMP ON ENTS
HOUSTON,TEXAS
®
®
(I) 40831
(J) 57053
CAUTION
CAUTION
8A
(control power source switch)
Heat sink not grounded.
Risk of electrical shock.
Do not turn off while operating.
Disconnect UPS and electrically
test heat sink before touching.
PN 40831
6.1 Warning Label Locations
FIGURE 6.2 – 100 KVA UPS WARNING LABELS
G8000 Series Installation and Operation Manual
15
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 6.3 – 150/225 KVA UPS WARNING LABELS
FIGURE 6.4 - 300 KVA UPS WARNING LABELS
G8000 Series Installation and Operation Manual
16
Download from Www.Somanuals.com. All Manuals Search And Download.
7 Weight and Dimensions
Table 7.1 lists the unit and shipping weights for G8000 UPS models illustrated in Figures 7.1 – 7.3.
TABLE 7.1 G8000 UPS UNIT AND SHIPPING WEIGHTS
Model
Unit
Shipping
100 kVA
1740 lb. (789 kg)
1790 lb. (812 kg)
150 kVA
225 kVA
300 kVA
2467 lb. (1119 kg)
2980 lb. (1352 kg)
4575 lb. (2075 kg)
2556 lb. (1159 kg)
3069 lb. (1392 kg)
4725 lb. (2143 kg)
“8A” SWITCH
TERMINAL
BLOCKS
GROUND BUS
FIGURE 7.1 – 100 KVA UPS EXTERIOR DIMENSIONS (INCHES)
G8000 Series Installation and Operation Manual
17
Download from Www.Somanuals.com. All Manuals Search And Download.
79.2
“8A” SWITCH
TERMINAL
BLOCKS
GROUND BUS
FIGURE 7.2 - 150/225 KVA UPS EXTERIOR DIMENSIONS (INCHES)
GROUND BUS
TERMINAL
BLOCKS
“8A” SWITCH
82.5
FIGURE 7.3 – 300 KVA UPS EXTERIOR DIMENSIONS (INCHES)
G8000 Series Installation and Operation Manual
18
Download from Www.Somanuals.com. All Manuals Search And Download.
8 Transporting
WARNING
WhentransportingtheUPSbycrane,followtheSPECIFIEDWORKPROCEDURE.
The suspension wire angle should be less than 60°.
The UPS falling or overturning may cause crushing, trapping or other personal
injuries.
DO NOT tilt the UPS more than 10° from upright position.
Tilting the UPS more than 10° may cause crushing, trapping or other
personal injuries.
CAUTION
DO NOT transport, move, store, or place the UPS on its side.
Excessive force applied from heavy components inside may damage
the UPS.
Avoid vibration or shock exceeding 0.5G.
Failing to observe this precaution may cause damage to the UPS.
DO NOT allow the UPS to suffer shock or impact when
unpacking.
Tools used to remove packaging materials may cause damage to the
UPS.
DO NOT install the UPS where water may fall on it.
Water may cause electrical shock, personal injury or UPS failure.
DO NOT push or pull on the sides of the packaging.or the
UPS to move it. Always use a crane, forklift, or pallet jack for
transporting and positioning the UPS.
Pushing/pulling on the sides of the unit to move it may result in damage
to the UPS. (See Figure 4.1 Exterior Handling label.)
The UPS may be packed in a crate for extra protection during transportation. Avoid impact or vibration
against the UPS during transportation. DO NOT expose the UPS directly to water.
G8000 Series Installation and Operation Manual
19
Download from Www.Somanuals.com. All Manuals Search And Download.
8.1 Transporting By Crane
Cables should have sufficient ratings and be of the same length. Make sure the suspension cables are
hooked at eyebolts. See Figure 8.1. Keep the angle less than 60° between cables.
Refer to Chapter 7 - Weight and Dimension for UPS cabinet weight.
Keep UPS leveled when lifting. DO NOT swing or tilt the UPS. Minimize the impact when lowering the
UPS to the floor. Figure 8.2 and 8.3 indicate unacceptable lifting.
Figure 8.4 and 8.5 show examples of acceptable and unacceptable operations.
Less than 60°
FIGURE 8.1 - CABLES AND EYEBOLTS TO LIFT THE UPS
More than 60°
Uneven Cables
FIGURE 8.2 - ANGLE MORE THAN 60°
FIGURE 8.3 - UNEVEN CABLES
FIGURE 8.4 - ACCEPTABLE OPERATION
FIGURE 8.5 - UNACCEPTABLE OPERATION
G8000 Series Installation and Operation Manual
20
Download from Www.Somanuals.com. All Manuals Search And Download.
8.2 Transporting By Forklift
Refer to Chapter 7 - Weight and Dimensions.
Verify forklift maximum load capacity and ensure that the forks are long enough to properly support the
UPS. Insert the forks into the space shown in Figure 8.6. Spaces for the forks are provided underneath
the UPS.
DO NOT swing or tilt UPS when lifting and/or transporting. Minimize the impact when lowering the UPS
to the floor.
100 - 225 kVA
Base
Secure the forks against the base then lift
Insert the forks here
300 kVA
Base
Secure the forks against the base then lift
Insert the forks here
FIGURE 8.6 -TRANSPORTING UPS BY FORKLIFT
G8000 Series Installation and Operation Manual
21
Download from Www.Somanuals.com. All Manuals Search And Download.
9 Storage/Operating Environment
Observe the following when storing the UPS.
•
•
Store UPS indoors.
Maximum storage time for the UPS between powered operation cycles is three years.
If the UPS has been stored for a period exceeding 36 months, contact your factory
authorized represnetative of guidance in starting the unit.
Temperature fluctuations should be minimized.
The optimal storage temperature range is 68 – 77 °F (20 – 25° C).
A maximum temperature range of 32 – 104 °F (0 – 40 °C) should be observed.
The optimal relative humidity at the storage location should be between 50 – 60%.
Humidity must not exceed 90%.
•
•
•
•
•
•
•
Avoid locations where UPS may be exposed to corrosive gas.
Avoid locations with dirt and/or dust.
TABLE 9.1 - UPS STORAGE/OPERATING ENVIRONMENT STANDARDS
Item
Environment standard
Storage Location
Indoors
Minimum storage temperature: 32 °F (0 °C)
Maximum storage temperature: 104 °F (40 °C)
Ambient Temperature
The relative humidity must be between 30 and 90% and without condensation
due to temperature changes.
Relative Humidity
Altitude
This equipment is rated for installations up to 3240 ft. (1000m) above
sea level. Consult with the factory to determine the derating factor for
installations above 3240 ft. (1000m).
Dust must not exceed normal atmospheric levels and must not include
conductive particles, silicone or oils.
Dust
No flammable and/or explosive gas.
Hydrogen sulfide (H2S)
Sulfurous acid gas (SO2)
Chlorine gas (Cl2)
Less than or equal to 0.0001 PPM
Less than or equal to 0.05 PPM
Less than or equal to 0.002 PPM
Less than or equal to 0.1 PPM
Less than or equal to 0.02 PPM
Flammable Gas
Ammonia gas (NH3)
Nitrous acid gas (NO2)
Nitrous oxides (NOx)
Ozone (O3)
Less than or equal to 0.02 PPM
Less than or equal to 0.002 PPM
Hydrochloric acid mist (HCl)
Less than or equal to 0.1 mg/m3
9.1 Operating Precautions
Initial startup/comisioning of the UPS should be performed by factory authorized personnel.
1) The UPS should not be powered up until the entire operation manual has been
read.
2) The voltage of the input power source must be within the rated input voltage
range. The input frequency range must be within the rated input frequency
range.
G8000 Series Installation and Operation Manual
22
Download from Www.Somanuals.com. All Manuals Search And Download.
3) The UPS should not be used with a load that has a rated input that is greater than the
rated output of the UPS.
4) If using the UPS to provide power to motors that require high starting current or with
motors that require a long starting time, call Toshiba support for guidance in over
sizing the UPS for lock rotor current.
5) DO NOT insert metal objects or combustible materials in the ventilation slots of the
UPS.
6) DO NOT place, hang, or paste any objects on the exterior surfaces of the UPS.
7) The capacitors in the UPS maintain a residual charge for a while after turning the UPS
off. The required discharge time for each UPS typeform is provided via a cabinet label
and a CHARGE LED. Wait for at least the minimum time indicated on the label and
ensure that the CHARGE LED has gone out before opening the door of the UPS once
the UPS power has been turned off.
8) DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales
representative for repair information.
9) Turn the power on only after installing ALL of the covers.
10) DO NOT remove any covers of the UPS when power is on.
11) If the UPS should emit smoke or an unusual odor or sound, turn the power off
immediately.
12) Warning signs should be placed on or near the load as a notification that the load is
being powered by the UPS.
13) Additional warnings and notifications shall be posted at the equipment installation
location as deemed required by Qualified Personnel.
WARNING
While operating in the inverter mode, placing the input breaker
in the “OFF” position will switch the UPS to the battery backup
mode.
The output of the UPS will continue uninterrupted to the load. The unit
must be in the bypass mode at the time that the breaker is placed in
the “OFF” position for the UPS to shutdown power to the load.
CAUTION
After an Emergency Power Off (EPO), DO NOT reset the breaker
until the UPS internal circuits have been fully discharged.
The UPS could be damaged if the unit is not fully discharged before
the breaker is reset.
G8000 Series Installation and Operation Manual
23
Download from Www.Somanuals.com. All Manuals Search And Download.
9.2 Maintenance Precautions
All internal maintenance sould be performed by factory authorized personnel.
1) Turn off, lockout, and tagout ALL power sources before connecting the power wiring to
the equipment or when performing maintenance.
2) Hardwire type UPS units are not equipped with an over-current protection device, nor
do they have an output disconnect for the AC output. A user-installed circuit breaker
should be provided between the UPS output and the load input.
3) The maximum ambient operating temperature is 86 °F (30 °C) at 1.0 PF, and 104 °F
(40 °C) at 0.8 PF.
4) Only factory authorized personnel should service the UPS. Contact Toshiba for the
the nearest authorized service center.
5) Battery servicing should be performed by factory authorized personnel only. Contact
your nearest factory authorized service center for battery replacement.
Qualified Personnel ONLY!
Qualified Personnel have the skills and knowledge relating to the construction, installation, operation,
and maintenance of the electrical equipment and has received safety training on the hazards involved
(Refer to the latest edition of NFPA 70E for additional safety requirements).
Qualified Personnel shall:
1) Have read the entire operation manual.
2) Be trained and authorized to safely energize, de-energize, ground, lockout and
tag circuits and equipment, and clear faults in accordance with established safety
practices.
3) Be trained in the proper use and care of protective equipment such as safety shoes,
rubbergloves, hardhats,safetyglasses, faceshields, flashclothing, etc.,inaccordance
with established safety practices.
4) Be trained in rendering first aid.
5) Be knowledgeable of batteries and the required handling and maintenance
precautions.
WARNING
Misuse of equipment could result in injury and equipment damage.
In no event will Toshiba Corporation be responsible or liable for either
indirect or consequential damage or injury that may result from the
misuse of this equipment.
G8000 Series Installation and Operation Manual
24
Download from Www.Somanuals.com. All Manuals Search And Download.
CAUTION
DO NOT dispose of the batteries in a fire.
The batteries may explode.
DO NOT open or mutilate the batteries.
Released electrolyte is harmful to the eyes and skin and could also
be toxic.
DANGER
A battery can present a risk of electrical shock and high short
circuit current.
9.3 Disposal
Please contact your local or state environmental agency for details on disposal of electrical components
and packaging in your particular area.
It is illegal to dump lead-acid batteries in landfills or dispose of them improperly.
Please help protect the Earth by contacting the environmental protection agencies in your area, the
battery manufacturer, or call Toshiba toll-free at (877) 867-8773 for more information about recycling
batteries.
G8000 Series Installation and Operation Manual
25
Download from Www.Somanuals.com. All Manuals Search And Download.
10 Installation
WARNING
Keep the SPECIFIED CLEARANCE around the UPS.
Inadequate space around the UPS makes it difficult to perform
maintenance/inspections, lead to insufficient ventilation, and/or will
cause malfunctions.
See Figure 10.1 - UPS Clearance
DO NOT tilt the UPS more than 10° from upright position.
Tilting the UPS more than 10° may cause crushing, trapping or other
personal injuries.
Install anchor bolts to secure the UPS to the installation floor.
The UPS may fall during an earthquake if the anchor bolts are not
installed and secured.
DO NOT transport, move, store, or place the UPS on its side.
Forces due to heavy components inside may damage the UPS.
DO NOT allow the UPS to suffer shock or impact when
unpacking.
Tools used to remove packaging materials may cause damage to the
UPS.
DO NOT push or pull on the sides of the packaging.or the
UPS to move it. Always use a crane, forklift, or pallet jack for
transporting and positioning the UPS.
Pushing/pulling on the sides of the unit to move it may result in damage
to the UPS. See Figure 4.1 Exterior Handling label.
G8000 Series Installation and Operation Manual
26
Download from Www.Somanuals.com. All Manuals Search And Download.
10.1 Unpacking
Unpack the UPS indoors on a paved floor. The UPS should be as close as possible to its final storage
location. Overhead traveling cranes should be used to unpack any G8000 Series UPS. If an overhead
traveling crane is not available, allow enough space for forklift operations to unpack the UPS crate. Then
remove the crate.
Points to observe
•
•
•
•
•
Retain all small articles during unpacking and installation.
Make sure that exterior paint is not scratched and that the UPS cabinet is not damaged.
DO NOT damage the UPS when using tools to remove packaging materials.
If provided, DO NOT remove the plastic sheet cover, until installation.
Do not remove the fan covers until UPS start up. The fan covers should be removed by factory
authorized personnel. Packing materials should be disposed by the appropriate means.
•
Immediately report any abnormalities to Toshiba Customer Support Center or an authorized
representative.
10.2 UPS Clearance
Maintain the indicated clearance during installation. See Figure 10.1. Ensure that the front and top air vents
are NOT blocked.
Top 16 in. (400 mm)
Front
44 in.
(1100 mm)
Back 0 in. (0 mm)
Side 0 in. (0 mm)
FIGURE 10.1 - UPS CLEARANCE
G8000 Series Installation and Operation Manual
27
Download from Www.Somanuals.com. All Manuals Search And Download.
10.3 Anchor Bolts
Install the anchor bolts to secure the UPS on the floor. See Figure 10.2 for anchor bolt installation detail.
Use 12mm (1/2”) diameter anchor bolts. There are 16mm (5/8”) diameter holes provided in the UPS base.
See Figure 10.3 for the hole locations and dimensions for the specified UPS models.
< 100kVA (T80S3K10KK6XS2H) >
Back
551mm
(21” 11/16)
4 x 12mm-Dia. (1/2”)
Front
754mm (29” 11/16)
< 100kVA (T80S3K10KK6XSNH) >
< 150/225kVA >
4 of 16mm-diameter
(5/8”) screw holes
Back
4 screw holes
(Side View)
551mm
(21” 11/16)
4 x 12mm-Dia. (1/2”)
Front
Anchor Bolt
1,170mm (46” 1/16)
FIGURE10.2
ANCHOR BOLT INSTALLATION DETAIL
< 250/300kVA >
Back
650mm
(25” 19/32)
8 x 12mm-Dia. (1/2”)
Front
572mm
(22” 1/2)
572mm
(22” 1/2)
572mm
(22” 1/2)
FIGURE 10.3
HOLE LOCATIONS/DIMENSIONS
ON BOTTOM OF UPS
G8000 Series Installation and Operation Manual
28
Download from Www.Somanuals.com. All Manuals Search And Download.
11 UPS Wiring
Note: Always consult your local and NEC electrical codes for wiring, cabling, and circuit protection device
requirements.
Figure 11.1 illustrates the external wiring of the G8000 UPS. See corresponding section to each wiring
term.
• Power cable connection at terminal blocks/buses and external breaker provision for the AC
input/output, Bypass Input and DC input.
• Earth ground wire at grounding terminal.
• Control wire terminal TB1 (battery cabinet and bypass breaker)
< UPS >
Bypass
3φ4W
Contactor + Thyristor
Bypass
Breaker
Bypass
Contactor
Input
AC Input
Contactor
3φ3W
Output
3φ4W
Input
Breaker
Output
Breaker
Inverter
Inverter
Contactor
Rectifier
Chopper
Charger
TB1
DC input
Battery
Breaker
Ground
Wire
< Battery Cabinet >
FIGURE 11.1 - EXTERNAL WIRING DIAGRAM
An external maintenance bypass may be installed in parallel with the UPS to allow servicing of the
G8000 while maintaining power to the UPS load. Contact the Toshiba Customer Service for further
information.
G8000 Series Installation and Operation Manual
29
Download from Www.Somanuals.com. All Manuals Search And Download.
11.1 100 kVA Terminal Blocks and Power Cables
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and
circuit protection device requirements.
The terminal blocks for the 100 kVA UPS are shown in Figure 11.2.
Recommended external cable size and tightening torque for a single battery string are listed in Table
11.3–11.5. For two or more battery strings consult with Toshiba Technical Support. Ensure that your
installation adheres to local and NEC electrical codes.
Use only copper wires for external cables.
1
2
3
4
5
6
7
8
9
10 11
12 13
U
V
W
U
V
W
N
U
V
W
N
+
-
BATTERY
BYPASS INPUT
AC OUTPUT
AC INPUT
FIGURE 11.2 - TERMINAL BLOCKS FOR 100 KVA UPS
TABLE 11.1 RECOMMENDED CABLE SIZE & TIGHTENING TORQUE FOR 100 KVA UPS
Block Number
Cable Size**
Tightening Torque
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
275 in.-lb. (3.2 kg-m)
1
2
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
AWG 1/0 or larger
Two AWG 2/0
3
4
5
6
7
8
9
10
11
*12
*13
Two AWG 2/0
* One battery string. (Consult factory if using more than one battery string.)
** Maximum cable size is AWG 2/0
G8000 Series Installation and Operation Manual
30
Download from Www.Somanuals.com. All Manuals Search And Download.
11.2 150, 225, and 300 kVA Buss Strip Terminals and Power Cables
Note: Always consult your site specific, local, state, and NEC electrical codes for wiring, cabling, and
circuit protection device requirements.
The 150, 225, and 300 kVA UPS units have buss strip power terminals. Figure 11.3 is a typical buss strip
for a 150/225 kVA UPS.
1.75 in.
(45 mm)
3 in.
(77 mm)
0.5 in. Dia.
(1.27 mm)
1.97 in.
1.77 in.
(50 mm)
(45 mm)
5.3 in. (135 mm)
FIGURE 11.3 - TERMINAL BUS DETAIL
Figure 11.4 shows the arrangement of the terminal buss strips for the 150 and 225 kVA UPS units. The
terminal buss strips are located inside, at the bottom of the UPS. The dashed line indicates the side
view of the bolt holes. Use 1/2 inch bolts to attach the lugs.
1
2
3
4
5
6
7
8
9
10
11
12
13
U
V
W
U
V
W
N
U
V
W
N
–
+
AC INPUT
BYPASS INPUT
AC OUTPUT
BATTERY
FIGURE 11.4 - TERMINAL BUSS ARRANGEMENT FOR 150 AND 225 KVA UPS
Figure 11.5 shows the arrangement of the terminal buss strips for the 300 kVA UPS. The buss strips are
located inside at the top of the unit.
10
12
1
2
3
6
7
8
11
4
5
9
U
V
W
–
+
U
V
W
N
U
V
W
AC INPUT
3-phase 3-wire
BATTERY
BYPASS INPUT
3-phase 4-wire
AC OUTPUT
3-phase 4-wire
FIGURE 11.5 - TERMINAL BUSS ARRANGEMENT FOR 300 KVA UPS
G8000 Series Installation and Operation Manual
31
Download from Www.Somanuals.com. All Manuals Search And Download.
For UPS’ equipped with buss strip terminals for the A/C INPUT, BYPASS INPUT, A/C OUTPUT and
BATTERY connections, Toshiba recommends using the compression lugs listed in Table 11.2, or their
equivalent, for cable terminations to be mounted on the bus strips.
See Table 11.3 – Table 11.5 for recommended cable sizes for the 150, 225, and 300 kVA UPS.
TABLE 11.2 RECOMMENDED CRIMP TYPE COMPRESSION LUGS FOR BUS STRIP TERMINALS
Wire Size
Wire
Strand
Class
Recommendation
Crimp tool Required
Burndy type Y35 or Y46
Vendor
Cat. No.
Color Key
Die Index
1/0
B
I
B
Burndy
Ilsco
Burndy
YA25
CRA-1/OL
YA25-LB
Pink
Pink
Black
12 / 348
12 / 348
13
2/0
B
I
B
Burndy
Ilsco
Burndy
YA26
CRA-2/OL
YA27-LB
Black
Black
Orange
13
13
14 / 101
3/0
B
I
B
Burndy
Ilsco
Burndy
YA-27
CRB-3/OL
YA28-LB
Orange
Orange
Purple
14 / 101
14 / 101
15
4/0
B
I
B
Burndy
Ilsco
Burndy
YA28
CRB-4/OL
YA29-LB
Purple
Purple
Yellow
15
15
16
300 MCM
B
I
B
Burndy
Ilsco
Burndy
YA30
CRA-30OL
YA32-LB
White
White
Red
17 / 298
17 / 298
18 / 324
350 MCM
600 MCM
B
I
Burndy
Ilsco
YA31L
CRA-350
Red
Red
18
18
B
I
Burndy
Ilsco
YA36L
CRA-600
Green
Green
22
22
TABLE 11.3 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 150 KVA UNIT
Block Number
Cable Size
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
AWG 4/0 or larger
Two 300 MCM or larger
Two 300 MCM or larger
Recommended Fastener Torque **
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
1
2
3
4
5
6
7
8
9
10
11
*12
*13
* One battery string. (Consult factory if using more than one battery string.)
** Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.
G8000 Series Installation and Operation Manual
32
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 11.4 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 225 KVA UNIT
Block Number
Cable Size
Recommended Fastener Torque **
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
1
2
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Two AWG 2/0 or larger
Three AWG 4/0 or larger
Three AWG 4/0 or larger
3
4
5
6
7
8
9
10
11
*12
*13
* One battery string. (Consult factory if using more than one battery string.)
** Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.
TABLE 11.5 RECOMMENDED CABLE SIZE AND FASTENER TORQUE FOR 300 KVA UPS
Bus Number
Cable Size
Recommended Fastener Torque **
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
540 in.-lb. (6.2 kg-m)
1
2
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Three 350 MCM or larger
Three 350 MCM or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
Two AWG 4/0 or larger
3
*4
*5
6
7
8
9
10
11
12
* One battery string. (Consult factory if using more than one battery string.)
** Fastener torque specified for: 1/2 in. diameter grade 5 steel bolt.
G8000 Series Installation and Operation Manual
33
Download from Www.Somanuals.com. All Manuals Search And Download.
11.3 UPS Power Cable Knockout Plates
Cable knockout plates are provided at the bottom of the 100 kVA UPS, and at the top and bottom of the
150/225 kVA UPS. (Older models of the G8000 150/225 kVA UPS do not come equipped with an upper
knockout plate.) The recommended hole locations are illustrated in Figure 11.6, 11.7, and 11.8.
The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening
behind the knockout plates.
PLATE #1
PLATE #2
3” Dia.
0.8”
2” Dia.
0.8”
AC OUTPUT
AC INPUT
BYPASS
BATTERY
CONTROL
WIRES
FIGURE 11.6 - BOTTOM CABLE KNOCKOUT PLATES FOR 100 KVA (T80S3K10KK6XS2H)
PLATE #1
PLATE #2
PLATE #3
4” Dia.
0.8”
2” Dia.
0.4”
AC OUTPUT
BATTERY
CONTROL
WIRES
AC INPUT
BYPASS
FIGURE 11.7 - BOTTOM CABLE KNOCKOUT PLATES 100 KVA (T80S3K10KK6XSNH); 150/225 KVA
4” Dia.
FIGURE 11.8 - TOP ACCESS KNOCKOUT PLATE (IF AVAILABLE - 150 AND 225 KVA ONLY)
G8000 Series Installation and Operation Manual
34
Download from Www.Somanuals.com. All Manuals Search And Download.
Figure 11.9 shows the four (4) cable knockout plates provided at the top of the 300 kVA UPS. Seven (7)
holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the
knockout plates.
PLATE #1
PLATE #4
PLATE #2
PLATE #3
2“ Dia.
2“ Dia.
1.5”
4” Dia.
0.4”
0.6”
0.6”
GROUND WIRE
CONTROL WIRES
-
+
0.8”
AC INPUT
BATTERY
BYPASS
AC OUTPUT
FIGURE 11.9 - TERMINAL KNOCKOUT PLATES FOR THE 300 KVA UPS
G8000 Series Installation and Operation Manual
35
Download from Www.Somanuals.com. All Manuals Search And Download.
11.4 External Breakers
The G8000 UPS units are not equipped with circuit breakers. Qualified personnel should provide the
external breakers for the AC input/output, bypass input and DC input.
See Figure 11.1 – External Wiring Diagram, for the circuit position of the breakers.
Table 11.6 shows the G8000 UPS minimum external breaker rating for each capacity. The bypass input and
the AC output require 3-pole breakers.
TABLE 11.6 EXTERNAL BREAKER RATING
AC Input / Bypass Input / AC Output
Minimum Breaker Rating
DC Input
Minimum Breaker Rating
Capacity
100 kVA
150 kVA
225 kVA
300 kVA
480 V - 200 A
480 V - 300 A
480 V - 450 A
480 V - 500 A
500 VDC – 500 A
500 VDC – 700 A
500 VDC – 1100 A
500 VDC – 1500 A
11.5 Grounding Wire
WARNING
Be sure to ground the UPS as specified.
Using the UPS without a proper ground will deteriorate the insulation,
cause leakage of currents and electric shock.The resistance to ground
should be less than or equal to 10 ohms.
The 100/150/225kVA earth grounding bus is located inside, at the bottom-front of the unit. The 300 kVA
earth grounding bus is located inside, at the top-left of the unit.
Use a AWG 2 (or 38 mm2) or larger cable for the grounding wire. Run the grounding wire through the
opening at the bottom, or through a hole in the top knockout plate (if available). See Figure 11.10. Connect
either the top or bottom earth ground bus, but not both, to the grounding wire.
The ground wire must have a crimp terminal with a 1/2 in. (12 mm) diameter bolt hole. The ground bus has
33/64 in. (13 mm) bolt hole. The connect the crimp terminal and ground bus together using a 7/16 in. (10
mm) diameter bolt.
G8000 Series Installation and Operation Manual
36
Download from Www.Somanuals.com. All Manuals Search And Download.
G8000 - 100 kVA
Ground bus
10 mm or
7/16 in. Bolt
12 mm or 1/2 in.
Terminal
AWG 2 (38 mm)
ground wire
Feed-through opening
To facility
earth ground
Facility earth ground.
Alternate ground wire routing
through top knockout plate.
G8000 - 150/225 kVA
Ground bus
10 mm or
7/16 in. Bolt
Note: Use either the top or the
bottom access for the ground
wire to connect to the ground
buss, but use only one ground
wire..
12 mm or 1/2 in.
Terminal
AWG 2 (38 mm)
ground wire
Feed-through opening
To facility
earth ground
Facility earth ground.
Ground wire routing through
top knockout plate.
G8000 - 300 kVA
Through knockout plate
on top (recommended)
10 mm or
7/16 in. Bolt
Ground bus
Note: Use either the top or the
bottom grounding point, but not
both. Doing so may degrade the
performance of the unit.
Alternate ground
wire location
FIGURE 11.10 - EARTH GROUND WIRE
G8000 Series Installation and Operation Manual
37
Download from Www.Somanuals.com. All Manuals Search And Download.
11.6 Control Wires
The control wires terminal layouts at TB1 (terminal bus 1) are shown below in Table 11.8.
TABLE 11.8 EXTERNAL CONNECTIONS
No.
1
I/O
Output
Output
Output
Output
Output
Input
Signal Name
Low Battery
Operation
Closed at Low Battery
2
Backup Operation
Fault
Closed during Backup Operation
Closed if Faults present
3
4
Inverter Supply
Warning
Closed during Normal Operation
Closed if Warnings present
5
6
P24
}
}
7
Input
Remote Run
P24
Close to run UPS
8
Input
9
Input
Remote Stop
Bypass Supply
Output Signal Ground
P24
Close to stop UPS
10
11
12
13
14
15
16
17
18
19
20
21
22
Output
Output
Input
Close during Bypass Operation
(Ground for pin #1 – 5 & #10)
Battery’s
}
}
}
}
Input
Battery Overheat
Overheat B-contact
Output
Output
Output
Output
Output
Output
Bypass Breaker
52C Trip Signal
72B Trip Signal
72B Aux. Contact
Shunt Trip Signal by EPO
Battery Breaker shunt trip
by EPO or Battery shutdown
Battery breaker’s
Auxiliary A-contact
Output
Output
External EPO
External EPO
Ext EPO (Customer) N.O. Contacts
Ext EPO (Customer) N.O. Contacts
}
Note: All control wiring should be #18 AWG (0.823 mm2) or larger.
G8000 Series Installation and Operation Manual
38
Download from Www.Somanuals.com. All Manuals Search And Download.
The UPS battery cabinet and bypass breaker should be wired as shown below in Figure 11.11.
Power Source
Jumper wire if battery
OH is not applied
TC
Bypass Breaker
To Bypass
Input
10
11
12
13
Power Source
for trip coil
14
15
16
17
18
19
20
21
22
Overheat
B-Contact
To DC
Input
Auxillary A-
contact
TB1
UPS Cabinet
Battery Cabinet
Ext. EPO (Customer) N.O. Contacts
FIGURE 11.11 - CONNECTION BETWEEN UPS, BATTERY CABINET & BYPASS BREAKER
G8000 Series Installation and Operation Manual
39
Download from Www.Somanuals.com. All Manuals Search And Download.
11.7 Grounding Configuration
This section describes the grounding configuration to be used with various AC service entrance configurations.
Inadequate grounding will cause problems at start-up. Connections for the ground line and the neutral
line must be made appropriately according to the system configuration.
11.7.1 Recommended configuration (for 4 wire input with Input Neutral
grounded)
Figure 11.12 shows recommended grounding configuration when the input neutral is grounded.
The neutral line at the input source is usually grounded. The neutral terminal in the UPS cabinet should
be disconnected from the ground bus. The neutral connection for the UPS bypass input should be
grounded.
Input Source
< UPS Cabinet >
3φ
3φ
N
N
3φ
3φ
N
3φ
3φ
To the
Load
N
G
G
G
G
Remove
Jumper Cable
FIGURE 11.12 - GROUNDING CONFIGURATION WITH INPUT NEUTRAL GROUNDED
A 2 AWG (or 38 mm2) jumper cable is provided between the neutral terminal and ground bus in the UPS
cabinet. The qualified personnel should remove the jumper cable in this configuration. The jumper cable
location is illustrated below.
100-225 kVA
300 kVA
Neutral
Terminal
Neutral
Terminal
Ground
Bus
Ground
Bus
Remove
Jumper
Cable
Remove
Jumper
Cable
FIGURE 11.13 - JUMPER CABLE BETWEEN THE NEUTRAL TERMINAL & GROUND BUS
G8000 Series Installation and Operation Manual
40
Download from Www.Somanuals.com. All Manuals Search And Download.
11.7.2 Grounding Configuration (without input neutral)
When the input source is wye-connected, the neutral line out to the bypass input should be left open. The
UPS is grounded by connecting the neutral terminal to the ground bus with the internal jumper cable. See
Figure 11.14.
The jumper cable should stay in place. See Figure 11.13 for the jumper cable location.
If a ground fault interrupter is installed, the UPS is likely to trip the interrupter during transferring to/from
the bypass circuit. It is recommended that the ground fault interrupter be set to a minimum delay of 0.5
seconds.
Input Source
< UPS Cabinet >
3φ
3φ
N
N
3φ
3φ
N
3φ
3φ
To the
Load
N
G
G
G
G
Jumper Cable
Remains in Place
FIGURE 11.14 - GROUNDING CONFIGURATION WITHOUT INPUT NEUTRAL
11.7.3 Recommended Configuration (for delta-input)
If the input source is a delta-connection (3-phase 3-wire) without ground, the neutral terminal in the UPS
cabinet must be connected to the ground bus with the internal jumper cable as shown in Figure 11.15.
The jumper cable should stay in place. See Figure 11.13 for the jumper cable location.
Input Source
< UPS Cabinet >
3φ
3φ
N
3φ
3φ
N
3φ
3φ
To the
Load
N
G
G
G
G
Jumper Cable
Remains in Place
FIGURE 11.15 - GROUNDING CONFIGURATION FOR NON-GROUNDED DELTA-INPUT
G8000 Series Installation and Operation Manual
41
Download from Www.Somanuals.com. All Manuals Search And Download.
11.7.4 Grounding Configuration (with corner-grounded delta-input)
If one phase of delta-input source is grounded (B-phase for example), the ground bus in the UPS cabinet
should NOT be connected to the neutral terminal of UPS output.
The jumper cable should be removed see Figure 11.13 for the jumper cable location.
During normal operation the UPS output is floating relative to the ground. An isolation transformer is
recommended at output distribution as shown in Figure 11.16.
Input Source
< UPS Cabinet >
Output Distribution
3φ
3φ
N
3φ
3φ
Bφ
N
3φ
3φ
3φ
To the
Load
N
G
G
G
G
Remove
Jumper Cable
FIGURE 11.16 - GROUNDING CONFIGURATION WITH CORNER-GROUNDED DELTA-INPUT.
G8000 Series Installation and Operation Manual
42
Download from Www.Somanuals.com. All Manuals Search And Download.
12 UPS Specifications
12.1 General Specification
Terms
Specification
Remarks
UL, cUL
Conforming Standard
UL1778-2001
PF = 1.0: 32 – 86 °F (0 – 30 °C)
PF = 0.8: 86 – 104 °F (30 – 40 °C)
Ambient Temperature
Relative Humidity
30% – 90%
Non-condensing
< 3280 ft. (< 1000 m)
Contact Toshiba Technical
Support for installation above
3280 ft. (1000 m)
Altitude
Audible Noise
68 dB (100/150/225 kVA), 72 dB (300 kVA)
3 MΩ
39 in. (1m) away from front
With 500V-Megger
Main Circuit
Insulation Resistance
AC 2 kV – 1 min.
AC 1.5 kV – 1 min.
AC 500 V – 1 min.
External Interface
Control Circuit
Insulation Breakdown
12.2 Mechanical Specification
100 kW:
T80S3K10KK6XS2H
Nominal Capacity
Cabinet Protection
Conformity
IEC298 IP20*
Exterior Paint
Sherwin Williams, HHT2-7055, 079 Beige Texture
FRONT: 1.6 mm (1/16 in.)
BACK/SIDE/TOP: 1.2 mm (3/64 in.)
BOTTOM: 3.2 mm (1/8 in.)
Panel Thickness
Input/Output
Cabling Entrance
BOTTOM
BOTTOM
Ground/Control
Wiring Entrance
W: 36.8 in. (935 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
Outline Dimension
Unit Weight
1740 lb. (789 kg)
1790 lb. (812 kg)
Shipping Weight
Floor Loading Per
Footprint
2180 lb./ft.2
(10,644 kg/m2)
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Clearance
34,121 BTU/h
(8598 kcal/h)
Heat Rejection
*IP20: Foreign objects that are 12 mm (15/32”) or larger are prevented from entering the enclosure of the UPS.
G8000 Series Installation and Operation Manual
43
Download from Www.Somanuals.com. All Manuals Search And Download.
12.2 Mechanical Specification (cont.)
Nominal Capacity
150 kW
225 kW
300 kW
Cabinet Protection
Conformity
IEC298 IP20*
Exterior Paint
Sherwin Williams, HHT2-7055, 079 Beige Texture
FRONT: 1/16 in. (1.6 mm)
BACK/SIDE/TOP: 3/64 in. (1.2 mm)
BOTTOM: 1/8 in. (3.2 mm)
Panel Thickness
Input/Output
Cabling Entrance
TOP and BOTTOM
TOP and BOTTOM
TOP
TOP
Ground/Control
Wiring Entrance
W: 55.1 in. (1400 mm)
D: 31.8 in. (808 mm)
H: 79.2 in. (2012 mm)
W: 76.8 in. (1951 mm)
D: 31.8 in. (808 mm)
H: 79.4 in. (2017 mm)
Outline Dimension
Unit Weight
2467 lbs (1119 kg) 2980 lbs (1352 kg)
2556 lbs (1159 kg) 3069 lbs (1392 kg)
4575 lbs (2075 kg)
4725 lbs (2143 kg)
Shipping Weight
Floor Loading Per
Footprint
3280 lbs/ft2
3733 lbs/ft2
2460 lbs/ft2
(16,014 kg/m2)
(18,226 kg/m2)
(12,011 kg/m2)
FRONT: 43 7/16 in. (1100 mm)
BACK/SIDE: 0 in. (0 mm)
TOP: 15 3/4 in. (400 mm)
Clearance
51,182 BTU/h
(12,897 kcal/h)
68,243 BTU/h
(17,197 kcal/h)
68,243 BTU/h
(17,197 kcal/h)
Heat Rejection
*IP20: Foreign objects that are 12 mm (15/32 in.) or larger are prevented from entering the enclosure of the UPS.
G8000 Series Installation and Operation Manual
44
Download from Www.Somanuals.com. All Manuals Search And Download.
12.3 Electrical Specification
WARNING
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if untrained
personnel open the front cover.
Nominal Capacity
100 kW
150 kW
225 kW
300 kW
AC Input Rated Capacity*
Input Voltage
110 kW (120 kW)
165 kW (180 kW) 245 kW (270 kW) 320 kW (320 kW)
480 V ( +10% to -15% ), 3-Phase 3-Wire
60 Hz ±5%
Input Frequency
Input Power Factor
Current Harmonic Distortion
Input Capacity Required*
0.95 – 1.00 Lagging ( at 100% Load )
4% Maximum ( at 100% Load )
111 kVA (124 kVA) 166 kVA (184 kVA) 250 kVA (274 kVA) 327 kVA (332 kVA)
Circuit Breaker Rating At 480 V
Input
200 A Trip
300 A Trip
450 A Trip
500 A Trip
* Capacity: Normal Mode (Recharge Mode)
Nominal Capacity
100 kW
150 kW
225 kW
300 kW
DC Input Voltage Window
Recharge Voltage Regulation
288 – 414 VDC
± 1.5%
Nominal Capacity
AC Output Rated Capacity*
Output Voltage
100 kW
150 kW
225 kW
300 kW
100 kVA (100 kW) 150 kVA (150 kW) 225 kVA (225 kW) 300 kVA (300 kW)
480/277 V ± 1%, 3-Phase 4-Wire
Output Power Factor
1.0 PF: 32 – 86 °F (0 – 30 °C)
0.8 PF: 86 – 104 °F (30 – 40 °C)
Voltage Distortion
3% with 100% Linear Load / 5% with Non-Linear Load
Transient Voltage Regulation
Transient Settling Time
Crest Factor
< ± 2%
< 50 ms
2.0
60 Hz ± 0.01% ( at Free-running Mode)
59 Hz – 61 Hz
Output Frequency
Synchronous Window To Utility Line
Frequency Slew Rate
Over Load Rating
1 Hz/Sec
100% – Continuous / 125% – 10 min. / 150% – 1 min.
* Capacity: Normal Mode (Recharge Mode)
G8000 Series Installation and Operation Manual
45
Download from Www.Somanuals.com. All Manuals Search And Download.
13 Operator Interface
Table 13.1 shows the functions of the operating buttons on the graphic display panel.
ATTENTION
Press an operating button for at least 0.5 seconds to change UPS modes. Press
the reset button for at least 5 seconds to reset the UPS.
The UPS may not respond if the button press is too short.
TABLE 13.1 BUTTON AND INDICATOR FUNCTIONS (See fig. 13.1 and 13.2)
#
1
2
3
4
5
6
7
8
9
Name
Function
OPERATION LOCK
STOP BUTTON
Enables/disables the buttons RUN, STOP, UPS, BYPASS, FLOAT/EQUAL, and RESET.
Stops the UPS. Transfers to bypass power if available.
Starts the UPS. Transfers the unit from bypass to UPS power.
Changes recharge mode between float charge and equalize charge.
Scrolls the LCD screens up.
RUN BUTTON
FLOAT/EQUAL BUTTON
SCROLL UP BUTTON
SCROLL DOWN BUTTON
RESET BUTTON
UPS BUTTON
Scrolls the LCD screens down.
Reset UPS faults and warnings shown on the LCD. (See Section 13.5)
Transfers from bypass operation to normal operation.
Transfers from normal operation to bypass operation.
“ON” during Bypass Supply.
BYPASS BUTTON
10 EPO BUTTON
11 LCD DISPLAY
Displays the operational, status, and warning/fault messages.
“FLASHES” during START or STOP sequence “ON” when operating in inverter mode.
“ON” after DC bus capacitors are fully charged through the converter.
“ON” with nominal AC input. “FLASHES” with AC input under-voltage (85%).
“ON” during float charge.
12 UPS SUPPLY LED
13 CONVERTER LED
14 AC INPUT LED
15 FLOAT CHARGE LED
16 EQUALIZE CHARGE LED
17 BATTERY LED
18 DISCHARGE LED
19 BYPASS INPUT LED
20 WARNING LED
21 FAULT LED
“ON” during equalize charge or protection charge while battery OH contact open.
“ON” when battery is connected. (aux-contact on)
“ON” during battery discharge.
“ON” with nominal bypass input. “FLASHES” when bypass is under-voltage (85%).
Normally “OFF”. “ON” when warning displayed on LCD. “FLASHES” when AC input is abnormal.
Normally “OFF”. “ON” when faults occur.
22 INVERTER LED
23 UPS LED
Lamp “FLASHES” during START or STOP sequence. “ON” when inverter is operating.
“ON” when the inverter output is connected to the UPS output.
“ON” with AC output connected to the bypass/inverter sources.
“ON” when the bypass power supplies the load
24 AC OUTPUT LED
25 BYPASS LED
G8000 Series Installation and Operation Manual
46
Download from Www.Somanuals.com. All Manuals Search And Download.
13.1 Key-Switch and Buttons
The key-switch and operating buttons on the graphic display panel are shown in Figure 13.1. See the
sections titled “Key-switch” and “Operating buttons” for each function.
5
6
1
2
3
4
7
9
8
10
EPO
FIGURE 13.1 – GRAPHIC DISPLAY PANEL KEY-SWITCH/OPERATING BUTTONS
G8000 Series Installation and Operation Manual
47
Download from Www.Somanuals.com. All Manuals Search And Download.
13.3 LCD Indicators
The operator can scroll through the following LCD display screens using the scroll buttons.
TABLE 13.1 - LCD DISPLAY SCREENS
Name
Description
Normal Display
Displays operational status, operational guidance, and measured
data.
Fault Display
Displays detailed data when a fault occurs.
Warning Display Displays detailed data when a warning occurs.
NORMAL DISPLAY
SCROLL UP
FAULT DISPLAY
SCROLL DOWN
WARNIG DISPLAY
FIGURE 13.3 - CHANGING SCREENS WITH SCROLL BUTTONS
G8000 Series Installation and Operation Manual
49
Download from Www.Somanuals.com. All Manuals Search And Download.
13.4 Normal Display
The Normal Display screen indicates the UPS operational status and provides various screens: an
operation guidance screens, mode screens and measured data screens. Table 13.2 shows these screens
page by page and illustrates the UPS Normal Display operational status screens.
TABLE 13.2 - NORMAL DISPLAY SCREEN EXAMPLES
OPERATIONAL STATUS SCREENS
Shows the UPS status at the top and guidance
message or measured data underneath.
BYPASS
Shows a guidance message at start up.
PRESS ‘RUN’ SWITCH
Shows the output voltage and current after start up.
UPS SUPPLY
AC-VO 480[V]
AC- I O 50[%]
Shows the UPS Operation mode.
OPERATION MODE
NORMAL OPERATION MODE
SYNC.
MEASUREMENT SCREENS
Output Voltage: Shows the output line-to-line
output voltage.
O/P VOLTAGE
VOLT. 480[V]
FREQ. 60.0[Hz]
Output Current: Shows the RMS output current
(%) for each phase..
O/P CURRENT (R.M.S.)
U
V
50[%]
50[%]
W 50[%]
G8000 Series Installation and Operation Manual
50
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 13.2 - CONTINUED
MEASUREMENT SCREENS
Shows the peak output current peak (%) for each phase.
Peak value of output current
O/P CURRENT (PEAK)
U
V
50[%]
50[%]
x 100 [%]
RMS value for rated current x 1.41
W 50[%]
Shows the AC Input Voltage (line-to-line) and frequency.
AC INPUT
AC I/P-V 480[V]
FREQ. 60.0[Hz]
Shows the Bypass Input Voltage (line-to-line voltage) and
frequency.
BYPASS INPUT
BYP I/P-V 480[V]
FREQ. 60.0[Hz]
Shows the remaining battery backup time with rated load
and cumulative discharged time.
BATTERY
BACK-UP RATING 10[MIN]
DISCHARGING 15[MIN]
Shows the internal DC bus voltage, battery voltage and
battery current.
DC INPUT
DC-V 632[V]
The battery current value displayed is negative during
recharge and positive during discharge.
BATT-V 400[V]
BATT- I 0[A]
Shows the cumulative UPS operation time, the
cumulative battery backup time and the number of battery
backup operations.
MODE COUNT
UPS
35[H]
BATTERY 56[MIN]
32[TIM]
The current time is displayed if there are no faults
recorded, or after the reset button is pressed.
CLOCK
Date is displayed in the mm-ddyyy format. The unit does
not calculate daylight savings time.
TIME 03-24-06 13:58
Time is displayed in the 24-hour format (e.g. 1:58 P.M. =
1358 Hrs.)
G8000 Series Installation and Operation Manual
51
Download from Www.Somanuals.com. All Manuals Search And Download.
13.5 Fault Display
The Fault Display screen displays the fault records until they are reset. The Warning Display screen
displays the warning records until they are reset. The fault records will remain in the memory until the
reset button is pressed for at least 5 seconds, even after the actual cause of the fault has been resolved.
Note that the fault records are not deleted when the UPS is turned off.
If the UPS is RESET while the system is in normal or bypass mode, the fault history is cleared and
operation continues.
If the UPS is RESET while the system is on backup mode, the system will power down, re-initialize, and
restart.
TABLE 13.3 FAULT & WARNING DISPLAY SCREEN EXAMPLES
A fault record is shown with time stamp.
FAULTS & WARNINGS
An arrow indicates that another record can be
displayed by pressing the up/down buttons.
1 FUSE BLOWN
09-09-06 08:05:30
↓ANOTHER ITEM
A warning record is shown with time stamp.
FAULTS & WARNINGS
An arrow indicates that another record can be
displayed by pressing the up/down buttons.
1 UPS OVERLOAD
09-09-06 08:05:30
↓ANOTHER ITEM
This screen is displayed if there are no
warnings recorded, or after the reset button is
FAULTS & WARNINGS
pressed.
NO ALARM
NO WARNING
G8000 Series Installation and Operation Manual
52
Download from Www.Somanuals.com. All Manuals Search And Download.
13.6 LCD Scroll
Scroll through the LCD display screens (see Figure 13.4), in sequence, using the “SCROLL UP” and
“SCROLL DOWN” buttons on the graphic display panel.
• SCROLL UP - Moves back to the previous screen
• SCROLL DOWN - Moves forward to the next screen
TABLE 13.4 DISPLAY SCREEN SCROLL SEQUENCE
UPS SUPPLY
FAULTS & WARNINGS
AC-VO 480[V]
NO FAULT
AC- I O 50[%]
NO WARNING
OPERATION MODE
CLOCK
Abbreveations
AC
–
Alternating
Current
NORMAL OPERATION
MODE SYNC.
TIME 03-24-06 13:58
DC
IO
–
–
Direct Current
Current
Output
MODE COUNT
I/P
–
–
–
Input
(The LCD displays a
diagram of the electrical
power flow.)
UPS
35[H]
O/P
VO
Output
BATTERY 56[MIN]
32[TIM]
Voltage
Output
O/P VOLTAGE
DC INPUT
DC-V 632[V]
BATT-V 400[V]
BATT- I 0[A]
VOLT. 480[V]
FREQ. 60.0[HZ]
O/P CURRENT (R.M.S.)
BATTERY
BACK-UP RATING 10[MIN]
U
V
50[%]
50[%]
50[%]
DISCHARGING
15[MIN]
W
O/P CURRENT (PEAK)
AC INPUT
BYPASS INPUT
U
V
W
50[%]
50[%]
50[%]
AC I/P-V 480[V]
FREQ. 60.0[HZ]
BYP I/P-V 480[V]
FREQ. 60.0[HZ]
G8000 Series Installation and Operation Manual
53
Download from Www.Somanuals.com. All Manuals Search And Download.
14 Operating the UPS
This section describes the basic procedures to operate the UPS. Figure 14.1 shows the location and
functions of the operating switches to operate the UPS.
WARNING
If the UPS produces smoke or smells strange, immediately turn
off all AC and DC input circuit breakers.
Continued operation may result in fire. Contact Toshiba or Authorized
representatives.
DO NOT turn off the control power supply switch (8A) during UPS
operation.
This may result in UPS faults.
EPO Switch
(Emergency Power Off Switch)
See Section 14.9
Control Power Supply Switch
FIGURE 14.1 - EPO AND CONTROL POWER SUPPLY OPERATING SWITCHES
G8000 Series Installation and Operation Manual
54
Download from Www.Somanuals.com. All Manuals Search And Download.
14.1 Operation Types
The operation types are summarized below.
TABLE 14.1 OPERATION TYPES
Operation
Description
Complete Shutdown
Turn off the control power supply. Shut down the UPS
completely.
Float / Equalize Charge Changing the battery recharge mode between float charge and
equalize charge.
Protection Charge
Automatic recharge mode transition from protection charge to
float charge.
Startup
Starting up and operating the UPS.
Stop
Stop the inverter and chopper/charger.
Switch Power Supply
Switching power supply source between UPS and Bypass.
14.2 Pre-operational Check
CAUTION
Perform the pre-operational check before operating the UPS.
Before operating the UPS:
1. Make sure all covers/panels are in place and secured.
2. Make sure the temperature in the UPS/Battery room is within specified limits.
3. Before starting the UPS, check the power source to make sure AC input power is on.
4. Make sure battery breaker’s auxiliary A-contact is connected to the terminal block TB1.
G8000 Series Installation and Operation Manual
55
Download from Www.Somanuals.com. All Manuals Search And Download.
14.3 Startup Procedures
The procedure to start the UPS is shown in Steps 1-5.
LED Key
- LED Off
- LED On
- LED Flash
STEP 1
SYSTEM INITIALIZE
Turn on the control power supply switch.
(Figure 14.1) and ensure the operation lock is
set to OPERATION. (Figure 13.1 - 1)
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
STEP 2
BYPASS
Wait for a few seconds.
PRESS ‘RUN’ SWITCH
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
STEP 3
BYPASS
Press the “RUN” button for at least 0.5
seconds.
UPS STARTING
WAIT FOR A WHILE
CONVERTER LED is “ON” and INVERTER
LED flashes.
UPS
AC
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
G8000 Series Installation and Operation Manual
56
Download from Www.Somanuals.com. All Manuals Search And Download.
Step 4-5 continues the procedure to start the UPS.
LED Key
- LED Off
- LED On
- LED Flash
BYPASS
STEP 4
Turn on the DC Input Breaker (72B) on the
external battery cabinet.
MOVE 72B TO ‘ON’ POSITION
BATTERIES LED is “ON”.
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
UPS SUPPLY
STEP 5
AC - Vo 480 V
AC - Io 50%
*Press the “UPS” button for at least 0.5
seconds. This completes UPS startup
procedure
UPS
BYPASS LED is “OFF”.
UPS LED is “ON”.
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
NOTE
*If the AC switch does not function, contact
Toshiba or authorized representatives.
If the bypass power source is out of
specification, this operation will be inhibited.
In order to switch manually, press the “UPS”
button for 5 seconds or more.
G8000 Series Installation and Operation Manual
57
Download from Www.Somanuals.com. All Manuals Search And Download.
14.4 Switch Power Supply (UPS→Bypass)
The procedure to transfer between the UPS supply and the bypass supply is shown in Steps 1-3
LED Key
- LED Off
- LED On
- LED Flash
STEP 1
UPS SUPPLY
Check AC INPUT LED and BYPASS
LED are on to make sure power is being
delivered to the UPS.
AC - Vo 480 v
AC - Io 50%
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
STEP 2
BYPASS
Press the “BYPASS” button for at least 0.5
seconds.
UPS LED is “OFF”.
BYPASS LED is “ON”.
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
STEP 3
BYPASS
Please wait until procedure is completed.
AC - Vo 480 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
UPS
INVERTER
CONVERTER
AC INPUT
NOTE
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
To change from Bypass to UPS supply,
SWITCH
BATTERIES
AC OUTPUT
follow the Startup Procedures - STEP 5.
If the AC switch does not function, contact
Toshiba or authorized representatives.
BYPASS
BYPASS INPUT
G8000 Series Installation and Operation Manual
58
Download from Www.Somanuals.com. All Manuals Search And Download.
14.5 Stop
The procedure to stop the UPS is shown in Steps 1-3.
LED Key
- LED Off
- LED On
- LED Flash
BYPASS
STEP 1
AC - Vo 480 V
AC - Io 50%
PRESS ‘UPS’ SWITCH
Transfer to Bypass supply as described in
Switch Power Supply.
UPS LED is “OFF”.
UPS
BYPASS LED is “ON”.
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
BYPASS
STEP 2
Turn off the DC Input Breaker (72B) on
the external battery cabinet, and, press
the G8000 “STOP” button for at least 0.5
seconds.
MOVE #72B TO ‘OFF’ POSITION
UPS
BATTERIES LED is “OFF”.
INVERTER
CONVERTER
AC INPUT
INVERTER LED flashes then “OFF”.
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
FLOAT CHARGE LED and CONVERTER
LED are “OFF”.
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
STEP 3
BYPASS
Wait until procedure is completed.
PRESS ‘RUN’ SWITCH
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
G8000 Series Installation and Operation Manual
59
Download from Www.Somanuals.com. All Manuals Search And Download.
14.6 Complete Shutdown
The procedure to turn off the control power and shut down the UPS completely is shown in Steps 1-6.
STEP 1
BYPASS
Transfer to Bypass supply as described in
Switch Power Supply.
DC-V 0 [V]
BATT-V 0 [V]
UPS LED is “OFF”.
BATT-I 0 [A]
BYPASS LED is “ON”.
STEP 2
Turn off the DC input breaker, and, press the
“STOP” button for at least 0.5 sec.
BATTERIES LED is “OFF”.
INVERTER LED flashes then “OFF”.
FLOAT CHARGE LED and CONVERTER
LED are “OFF”.
STEP 3
Please wait until procedure is completed.
STEP 4
Scroll the LCD screen to see the DC INPUT
and make sure DC bus voltage is 0V.
STEP 5
ATTENTION
*Turn off the control power supply switch (8A).
*STEP 5 - This operation is different from
the instructions displayed on the screen.
Nothing is displayed on the LCD.
All LED’s are “OFF”.
Be sure to perform the procedure as
specified in this manual.
STEP 6
Turn off all breakers at AC output, Bypass
Input and AC Output.
Shutdown is completed and UPS is isolated.
G8000 Series Installation and Operation Manual
60
Download from Www.Somanuals.com. All Manuals Search And Download.
14.7 Changing Between Float Charge and Equalize Charge
The procedure to change the recharge mode between float charge and equalize charge is shown in
Steps 1-3.
See the Note below for an explanation of Float and Equalize charge modes.
LED Key
- LED Off
- LED On
- LED Flash
STEP 1
UPS SUPPLY
Make sure that the FLOAT CHARGE LED
is “ON”.
AC - Vo 480 V
AC - Io 50%
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
UPS SUPPLY
STEP 2
Press FLOAT/EQUAL button for at least
0.5 sec.
AC - Vo 480 V
AC - Io 50%
Change completed.
UPS
EQUAL CHARGE LED is “ON”.
FLOAT CHARGE LED is “OFF”
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
STEP 3
Please wait until procedure is completed.
BYPASS
BYPASS INPUT
NOTE
In equalize charge mode, the battery
is charged for a programmed period at
a specified voltage (depending on the
battery spec), rather than the float charge,
in order to prevent voltage deviations
among battery cells. This should be done
once every six months if possible.
The G8000 UPS will automatically perform
the equalize recharge after battery backup
operation.
G8000 Series Installation and Operation Manual
61
Download from Www.Somanuals.com. All Manuals Search And Download.
14.8 Changing to Float Charge from Protection Charge (If applicable)
The manual procedure to change from protection charge to float charge is shown in Step 1-3.This
operation applies to batteries after they have experienced over temperature condition.
See the Note below for an explanation of float charge and protection charge.
LED Key
- LED Off
- LED On
- LED Flash
STEP 1
UPS SUPPLY
Make sure that the EQUAL CHARGE LED
is “ON”.
AC - Vo 480 V
AC - Io 50%
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
STEP 2
Make sure that the “BATT FAULT1” warning
goes away.
UPS SUPPLY
AC - Vo 480 V
AC - Io 50%
STEP 3
Press “FLOAT/EQUAL” button for at least
0.5 seconds.
UPS
INVERTER
CONVERTER
AC INPUT
Procedure completed.
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
NOTE
BYPASS
BYPASS INPUT
The battery is normally being charged at float
charge mode. To prevent thermal runaway
of the battery, this mode will automatically
be changed to protection charge when a
“BATT FAULT1” (Battery over temperature)
warning occurs.
In protection charge mode, the battery is
automatically charged at a voltage about 5%
lower than float charge.
If the “BATTFAULT1” warning message goes
away and a programmed duration is elapsed
(about 24 hours), this mode will automatically
be changed back to float charge. Thus, it is
not usually required to change the recharge
mode manually back to the float charge.
G8000 Series Installation and Operation Manual
62
Download from Www.Somanuals.com. All Manuals Search And Download.
14.9 Emergency Power Off (EPO)
Press the EPO switch for immediate shutdown of all power through the UPS. The signal from the EPO
is processed as a “hard fault” by the UPS and results in gate-blocks on the transistors and opens all the
internal contactors.
To Reset the UPS after triggering the EPO, do the following:
1. Shut Down the UPS as described in section 14.6.
2. Restart the UPS as described in section 14.3.
15 Troubleshooting
When an error occurs in the UPS, error data is displayed on the LCD screen. This section will describe
the types of errors, the error messages displayed on the LCD screen and the procedures to correct the
errors.
15.1 Types of Errors
The following types of errors may occur in the UPS:
TABLE 15.1 OPERATION TYPES
Name
Description
Fault (Trip)
The UPS has been tripped and has stopped operating.
The UPS is in Bypass mode.
Fault
Warning-1 (Input Power Failure) Power is supplied from the battery. When the warning is
corrected, power will automatically be supplied from the
AC input.
Warning-2 (Stop and Restart)
Warning (Operation Control)
(Guidance)
The UPS transfers to Bypass supply and the UPS stops
operating. When the warning is corrected, the UPS will
automatically be restarted and revert to UPS supply.
Warning
An error or a phenomena related to an error occurred.
Since this problem does not directly affect operation, the
system switches to synchronized mode.
An error or indication of an error has occurred, but
operation was not affected.
G8000 Series Installation and Operation Manual
63
Download from Www.Somanuals.com. All Manuals Search And Download.
15.2 Faults and Warnings Data Screen
This screen appears when a trip error is detected. Up to 10 screens of fault data can be displayed. Figure
15.1 and Table 15.2 show a sample screen and describe the data shown in the screen.
FAULTS & WARNINGS
1
2
1 UPS OVERLOAD
09-09-06 08:05:30
↓ANOTHER ITEM
3
4
FIGURE 15.1 - SAMPLE FAULT DATA SCREEN
TABLE 15.2 - FAULT AND WARNING DATA SCREEN DESCRIPTIONS
#
1
2
3
Name
Description
The number of the message in the order that it was detected (1 - 10).
(Up to 10 screens of fault data can be displayed.)
Number
Message
Time
Shows the type of the fault or warning message.
The date (mm-dd-yy) and time (in 24-hour format) the fault was
detected.
Indicates whether there is a fault screen before or after this screen.
Indicates there is a fault screen before this screen.
4
Scroll Indicator
↓ Indicates there is a fault screen after this screen.
↓ Indicates there are fault screens before and after this screen.
G8000 Series Installation and Operation Manual
64
Download from Www.Somanuals.com. All Manuals Search And Download.
15.3 LCD Fault & Warning Displays
When a fault occurs, a screen is shown as in Figure 15.2. When a warning occurs, a screen is shown as
in Figure 15.3. Select the desired fault or warning data to be displayed using the scroll buttons.
BYPASS
FAULT STOP
FAULTS & WARNINGS
1 FUSE BLOWN
09-09-06 08:05:30
FIGURE 15.2 - FAULT DISPLAY
UPS SUPPLY
AC-VO 480[V]
AC- I O 50[%]
FAULTS & WARNINGS
1 UPS OVERLOAD
09-09-06 08:05:30
FIGURE 15.3 - WARNING DISPLAY
G8000 Series Installation and Operation Manual
65
Download from Www.Somanuals.com. All Manuals Search And Download.
15.4 Fault Messages
Figure 15.4 show the locations for fault detection. Tables 15.3 through 15.7 gives details for the fault and
warning messages referred to in section “Fault Data Screen.” The “item” code associated with each fault
or warning message may be used to determine the physical location of the fault or warning by referring
to Figure 15.4. The UPS unit may be shipped with different protective configurations from the standard
shown in Figure 15.4, if specified by the customer. See the protective configuration indicated on the single
line diagram for each UPS.
47S
95S
27S
59S
59I
271
49
51I
45
Inverter
52R
83MC1
83MC
Battery
Chopper
30U
26
76C
5E
76
80PS
30ST
48
71F
80B1 80B2
26B
95C
59C
47C
27C
83BF
FIGURE 15.4 - PROTECTIVE DETECTOR LOCATIONS
TABLE 15.3 - FAULT (TRIP)
ITEM
LCD MESSAGE INDICATION
OVER HEAT
DESCRIPTION
26
HIGH TEMP IN THE CABINET.
30ST
48
(NO INDICATION)
STARTUP ERR
EMG.STOP
AN ERROR OCCURRED IN THE MAIN CONTROL MICROPROCESSOR (CPU).
STARTUP WAS NOT COMPLETED WITHIN THE NORMAL TIME FRAME.
AN EMERGENCY STOP WAS ACTIVATED VIA THE EXTERNAL CONTACT.
RECTIFIER, DC, OR INVERTER MAIN CIRCUIT FUSE BLOWN.
DC OVER-CURRENT - EXCESSIVE CURRENT IN DC CIRCUIT.
BATTERY VOLTAGE IS BELOW CUTOFF VOLTAGE.
5E
71F
76
FUSE BLOWN
DC OC
80B2
80PS
BATT. UV
CONT. PS. ERR
THE CONTROL POWER SUPPLY VOLTAGE FAILED.
TABLE 15.4 - WARNING – 1 (CONVERTER STOP/INPUT POWER ERROR)
ITEM
27S
47S
59S
95S
LCD MESSAGE INDICATION
AC I/P UV
DESCRIPTION
AC INPUT UNDERVOLTAGE - AC INPUT VOLTAGE IS TOO LOW.
AC INPUT PHASE ROTATION ERROR.
AC PHASE ERR
AC I/P OV
AC INPUT OVERVOLTAGE - AC INPUT VOLTAGE IS TOO HIGH.
AC INPUT FREQUENCY ERROR.
I/P FREQ. ERR
G8000 Series Installation and Operation Manual
66
Download from Www.Somanuals.com. All Manuals Search And Download.
TABLE 15.5 - WARNING - 2 (STOP AND RESTART)
Item
27I
30U
45
LCD Message Indication
Description
AC O/P UV
UNIT FAULT
DC OV
AC output voltage is low.
IGBT Stack Failure.
Over-voltage in DC circuit.
Output overload
49
AC O/P OL
INV. OC
Inverter over-current.
AC output voltage is high.
51I
59I
76C
AC O/P OV
BATT. OC
Over-current in Battery section.
TABLE 15.6 - WARNING (OPERATION CONTROL)
Item
27C
47C
59C
95C
LCD Message Indication
BYPASS UV
Description
Bypass input voltage is low.
BYPASS ERR.
BYPASS OV
Bypass input phase rotation error.
Bypass input voltage is high.
Bypass input frequency error.
BYPASS ASY.
TABLE 15.7 - WARNING (GUIDANCE)
Item
26B
LCD Message Indication
BATT. OVER HEAT
Description
Battery temperature is too high.
80B1 BATT. UV (ALM)
Battery voltage is near cutoff voltage.
G8000 Series Installation and Operation Manual
67
Download from Www.Somanuals.com. All Manuals Search And Download.
15.5 LCD Scroll (w/ faults or warnings)
This section describes how to scroll through the LCD screens when a fault has occurred (when Fault Data
screens exist).
Figure 15.5 shows the locations of the buttons to scroll the LCD screens. See Table 15.8 for details of the
scroll buttons and how they are used for screen scrolling.
5
6
7
FIGURE 15.5 - POSITION OF SCROLL AND RESET BUTTONS
TABLE 15.8 - BUTTON FUNCTIONS
#
5
6
Name
Function
SCROLL UP
SCROLL DOWN
Scrolls to the previous screen.
Scrolls to the following screen.
Resets the UPS faults and warnings shown on the LCD and deletes fault history data stored in
memory.
7
RESET
G8000 Series Installation and Operation Manual
68
Download from Www.Somanuals.com. All Manuals Search And Download.
15.6 Restoring UPS Operation
WARNING
Contact Toshiba in the event of malfunction or fault.
This UPS should be repaired only by factory authorized personnel.
Servicing by untrained personnel may extend the fault or result in
electric shock or personal injury.
Do NOT attempt to modify or relocate the UPS.
Electric shock, personal injury or fault may result if unauthorized
personnel attempt to modify or relocate the UPS. Be sure to contact
toshiba customer service if you need to modify or relocate the UPS.
Do not open the front and/or rear panels.
The parts inside carry energy-high current. Touching them may result
in electric shock, burns or fault.
The procedure to restore UPS operation is shown in Steps 1-2. The example shows the UPS restored
after a trip fault occurred on inverter over current with the message “INV. OC.”
STEP 1
LED Key
- LED Off
- LED On
Check the LCD screen.
Also check other fault data screens with
scroll buttons graphic panel.
BYPASS
1 INV. OC
07-15-07 08:05:30
STEP 2
Contact Toshiba Customer Support and
follow the directions given by the service
personnel.
↓ ANOTHER ITEM
UPS
INVERTER
CONVERTER
AC INPUT
FLOAT CHARGE
EQUAL CHARGE
DISCHARGE
AC
SWITCH
BATTERIES
AC OUTPUT
BYPASS
BYPASS INPUT
G8000 Series Installation and Operation Manual
69
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
Download from Www.Somanuals.com. All Manuals Search And Download.
INDUSTRIAL DIVISION
13131 West Little Your road, Houston, Texas 77041
Tel (713) 466-0277 Fax (713) 466-8773
U.S. (877) 867-8773 Canada (800) 872-2192 Mexico 01/800/527-1204
Printed in the U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|