LF410 /LF600
LF410 /LF602
15 to 200 mm (1/2" to 8")
Field Intelligent Device Series
Electromagnetic Flowmeter
Introduction
The electromagnetic flowmeter uses Faraday’s Law of
electromagnetic induction to measure the process flow.
The device consists of two units: a detector, through
which the fluid to be measured flows and in which
low-level signals proportional to flow rates are
obtained; and a converter, which supplies excitation
current to the detector, and amplifies the signals from
the detector and then processes and converts the
signals into the 4–20mAdc current signal or
communication signal. Thanks to the unique patented
magnetic field distribution technology, the meter is
highly immune for upstream flow disturbances.
Combined with multi-functional converter LF600
(combined type) or LF602 (separate type) equipped
with its original noise-suppression circuit and
arithmetic operation capability, LF410 has high
tolerance to noise, giving stable output even for slurry
fluid measurement. IR (Infrared) switches enable
parameter setting of the converter without removing
the cover. Flow direction can be set in either way, and
its 128 x 128 dot matrix LCD display allows the LCD
rotated to 90, 180 and 270 degrees with a software.
LF410/LF600
LF414/LF600
LF410
LF414
LF602
Figure2. LF410 series Flowmeters
*3
Certification number
Z01207
Specifications
ꢀOverall Specifications
The AF900 hand-held terminal (HART*1
communicator) can be used to communicate with the
flowmeter from a remote place. PROFIBUS-PA*2
interface is available as option.
Measurement range in terms of flow velocity:
0 – 0.3 m/s to 0 –10 m/s (0 –1.0 ft/s to 0 – 32.8 ft/s).
0 – 0.1 m/s to 0 – 0.3 m/s (0 – 0.3 ft/s to 0 – 1.0 ft/s)
range is available optionally.
*1: HART protocol (Highway Addressable Remote
Transducer) is a communication protocol for industrial
sensors recommended by the HCF (HART
Communication Foundation).
Accuracy: See the following graph.
Pulse output:
-
Vs > 0.5 m/s (1.64 ft/s): +/ 0.5 % of rate.
-
Vs < 0.5 m/s (1.64 ft/s): +/ 0.3% of rate
*2: PROFIBUS is the communication protocol for the
factory automation and process automation that
PROFIBUS Organization recommends. Instead of
analog control with a conventional analog signal
(4-20mA), it is one kind of the fieldbus which digitized
all signals. Flowmeters support PROFIBUS-PA.
-
+/ 1 mm/s (0.039 inch/s).
-
Current output: plus +/ 8 uA (0.05 % of
span)
Note: Span = Range in the magmeters.
Error
Absolute figure
(% of rate)
Converter
Converter
I/O
5.0
4.0
3.0
2.0
1.0
0.0
Power
supply
Signal cable
Terminal box
Power
supply
I/O
0
1
2
10
Flow Velosity (m/s)
Detector
Detector
Accuracy
Note: The accuracy above is measured under standard
operating conditions using the weighing method
at Toshiba's flow calibration facility.
Combined type
LF410/LF600
LF414/LF600
Separate type
LF410/LF602
LF414/LF602
*3: CE mark is under application.
Figure1. Configuration
No. EJL-114B
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
• PROFIBUS (opt.)
totalizer.
Protocol : PROFIBUS-PA
Fixed-value outputs — Outputs fixed-values for
Baurate : 31.25kbps
current and pulse outputs.
Bus voltage : 9-30Vdc
Consumption electric current of bus:less than
16mA
Zero adjustment — Executes zero adjustment
(on-stream at zero flow rate).
Output signals
Manufacture Ident-No. : 093BHEX
Standard Ident-No. : 9740HEX
Slave address : 0-126 (Default address is 126)
Profile : Profile Ver.3.01 for Process Control
Devices
Current output:
4–20mAdc (load resistance 0 to 750Ω)
Note: The current output cannot be used with
the PROFIBUS-PA ccommunication.
Function blocks : AI(Flow)×1 , Totalizer×1
Digital outputs — One point (std.) and one more
point is optionally available as follows.
LCD display: Full dot-matrix 128×128 dot LCD
display (back-light provided)
Digital output DO1 (std.):
The data on the LCD inside the converter can
rotate to 90, 180, and 270 degrees by a software,
without rotating the indicator itself. (Combined
type only)
Output type: Transistor open collector
Number of outputs: One point
Output capacity: 30Vdc, 200mA maximum
Digital output DO2 (opt.):
Parameter settings — Parameters can be set as
follows:
Output type: Solidstate relay output (non
polarity)
• IR Switches: Three key switches are provided to
set configuration parameters.
Number of outputs: One point
Output capacity: 150Vdc, 150mA maximum
or 150 V ac (peak to peak), 100mA maximum
• Digital communication: The AF900 hand-held
terminal or PROFIBUS is needed to set
parameters.
DO1 and DO2 functions — One of the following
functions can be assigned to DO1 (std.) and/or
DO2 (opt.)
•Zero adjustment: Zero point adjustment can be
started by pressing the switch in the converter.
• Pulse output (available only for DO1,DO2)
Pulse rate: 3.6 to 36,000,000 pulses/hr (DO1)
Damping: 0.5 to 60 seconds (selectable in 1 second
3.6 to
360,000 pulses/hr (DO2)
increments)
(Over 3,600,000 pulses/hr, auto-setting)
Pulse width: 0.5 to 500ms (but less than half of
the period for 100% flow rate)
Zero and span calibration: Built-in calibration
signal source allows converter unit check.
Note: The same and simultaneous pulse is not
available between DO1 and DO2.)
• Multi-range selection outputs (Note 1)
• High, High high, Low, and/or Low low alarm
outputs (Note 2)
• Empty pipe alarm output
• Digital Output Active Status (DO1 and DO2)
(Note 2)
Conditions when power fails: The outputs and
display will remain as follows when power fails.
Parameter setting values are stored in non-volatile
memory and the values will be restored when the
power returns to normal condition.
• Current output: 0mAdc
• Digital output: OFF
• LCD display: No display
• PROFIBUS: No communication
• Preset count output
• Converter failure alarm output
Power supply: One of the following can be selected:
• 100 to 240Vac, 50/60Hz (std.)
Note 1: Two outputs (DO1 and DO2) are needed for
4-range switching and forward/reverse
2-range switching.
Note 2: Normal Open (default set) or Normal Close
is selected for alarm outputs when
programming.
(allowable voltage 80 to 264Vac)
• 24Vdc (allowable voltage 18 to 36Vdc)
• 110Vdc (allowable voltage 90 to 130Vdc)
Surge protection: Arresters are installed in the
The Status when power failure is kept to
Normal Open.
power supply, and current signal output circuit.
Case: Aluminum alloy (equivalent of IP 67)
Communications output :
Coating: Acrylic resin-baked coating, pearl-gray
• HART(std.)
Digital signal is superimposed on 4–20mAdc
current signal as follows:
colored
• Conforms to HART protocol
Load resistance: 240 to 750Ω
Load capacitance: 0.25µF maximum
Load inductance: 4mH maximum
3
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
Cable connection ports:
Cable glands —
LF600 and LF602 without cFMus Approval:
Provided as standard
~
OD of cableφ11 13mm
Material Nylon 66
G (PF) 1/2 male screws.
Note: When PROFIBUS option is specified ,
~
cable grands size is φ6 8mm for signal
~
cable, φ11 13mm for power cable.
LF600 and LF602 with cFMus Approval:
Not provided, 1/2-14NPT male
screws are required.
Applicable diameter — 11 to 13mm
(0.433 to 0.512 inch)
Vibration resistance:
No resonance to the following levels of vibration:
• 10 to 150Hz with acceleration of 9.8m/s2
No defect in putting vibration to each
direction of 30Hz with 29.4 m/s2in 4h.
Note: Avoid using the flowmeter in an
environment with constant vibration.
Converter LF602 dimensions and weights:
See Figure 9 (for Separate type)
MTBF:220,000 hours at 25 deg.C (77 deg.F) based
on MIL-HDBK-217F
4
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
Installation
ꢀDimensions
Unit : mm
143
(35)
225
Unit : mm
133
225
(35)
131
131
64
L1
87
L1
BS16, DIN PN16 and JIS 10K dimensions:
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
L2
D1
Weight
(kg)
Meter size
(mm)
L1
L2
D1
Weight
(kg)
(mm)
(mm)
(mm)
(mm)
(mm)
(mm)
15
70
252
49
approx. 5
25
80
241
66
approx. 5
Note: 1 inch = 25.4mm
Note: 1 inch = 25.4mm
ANSI class 150 and class 300 dimensions:
ANSI class 150 and class 300 dimensions:
Meter size
(inch)
L1
L2
D1
Weight
(lb)
Meter size
(inch)
L1
L2
D1
Weight
(lb)
(inch)
(inch)
(inch)
(inch)
(inch)
(inch)
1/2
2.76
9.92
1.93
approx. 11
1
3.15
9.48
2.60
approx. 11
Figure 3. LF410/LF600 and LF414/LF600
flowmeters
Figure 4. LF410/LF600 and LF414/LF600
flowmeters
Meter size 15mm (1/2")
Meter size 25mm (1")
The dimension of L1 is changed when the material of
grounding ring is chosen Pt-Ir or Ta.
Meter size
L1
15mm (1/2”)
25mm (1”)
40mm (1 1/2”)
50mm (2”)
77mm (3.03 inch)
95mm (3.74 inch)
115mm (4.53 inch)
126mm (4.96 inch)
126mm (4.96 inch)
136mm (5.35 inch)
242mm (9.53 inch)
312mm (12.28 inch)
80mm (3”)
100mm (4”)
150mm (6”)
200mm (8”)
5
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
The dimension of L1 is changed when the material of
grounding ring is chosen Pt-Ir or Ta
Unit : mm
225
131
(35)
133
Meter size
15mm (1/2”)
25mm (1”)
L1
77mm (3.03 inch)
95mm (3.74 inch)
115mm (4.53 inch)
126mm (4.96 inch)
126mm (4.96 inch)
136mm (5.35 inch)
242mm (9.53 inch)
312mm (12.28 inch)
40mm (1 1/2”)
50mm (2”)
80mm (3”)
100mm (4”)
150mm (6”)
200mm (8”)
Unit : mm
R (PT)1/2Male Screw (Two Places)
88
40
126
91
(35)
L1
Note1: Eye bolts are provided at the top for flowmeters
sized 200mm (8").
BS16, DIN PN16 and JIS 10K dimensions
Meter size
(mm)
L1
(mm)
L2
(mm)
D1
(mm)
Weight
(kg)
40
50
80
100
150
200
100
110
110*
120*
230
264
280
306
338
407
458
85
approx. 6
approx. 7
approx. 8
approx. 10
approx. 22
approx. 32
102
127
159
216
267
64
L1
Note1: Cable glands are not provided for LF414 of FM
and CSA approved type.
300
Refer to the part of Cable connection port at
detector.
Note2: 1 inch = 25.4mm
ANSI class 150 and class 300 dimensions
Meter size
(inch)
L1
L2
D1
Weight
(lbs)
(inch)
(inch)
(inch)
BS16, DIN PN16 and JIS 10K dimensions:
1-1/2
3.94
4.33
4.33*
4.72*
9.06
10.39
11.02
12.04
13.30
16.02
18.03
3.35
4.02
5.00
6.26
8.50
10.51
approx. 13
approx. 15
approx. 18
approx. 22
approx. 49
approx. 70
Meter size
(mm)
L1
L2
D1
Weight
(kg)
2
3
4
6
8
(mm)
(mm)
(mm)
15
70
179
49
approx. 3
11.81
ANSI class 150 and class 300 dimensions:
Note: 1 inch = 25.4mm
Meter size
(inch)
L1
(inch)
L2
(inch)
D1
(inch)
Weight
(lb)
*When Teflon PFA lining is selected, L1 in the table
above becomes as follows:
1/2
2.76
7.05
1.93
approx. 7
ꢁ
L1: 115mm (4.53 inch) for meter size 80mm (3")
L1: 126mm (4.96 inch) for meter size 100mm (4")
Figure 6. Separate type detectors
LF410 and LF414
ꢁ
Meter size 15mm (1/2")
The dimension of L1 is changed when the material of
grounding ring is chosen Pt-Ir or Ta
Figure 5. LF410/LF600 and LF414/LF600
flowmeters
Meter sizes 40 (1 1/2") to 200mm (8")
Meter size
15mm (1/2”)
25mm (1”)
L1
77mm (3.03 inch)
95mm (3.74 inch)
115mm (4.53 inch)
126mm (4.96 inch)
126mm (4.96 inch)
136mm (5.35 inch)
242mm (9.53 inch)
312mm (12.28 inch)
40mm (1 1/2”)
50mm (2”)
80mm (3”)
100mm (4”)
150mm (6”)
200mm (8”)
6
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
Unit : mm
Unit : mm
R(PT)½ Male Screw (Two places)
(126)
91
R(PT)½Male Screw (Two places)
(126)
88
40
88
40
(35)
(35)
91
87
L1
L1
Note1: Cable glands are not provided for LF414 of FM
and CSA approved type.
Refer to the part Cable connection port at detector.
Note2: 1 inch = 25.4mm
Note1: Cable glands are not provided for LF414 of FM
and CSA approved type.
Refer to the part of Cable connection port at
detector.
Note2: Eye bolts are provided at the top for flowmeters
sized 200mm (8").
Note3: 1 inch = 25.4mm
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(mm)
L1
L2
D1
Weight
(kg)
approx. 3
(mm)
(mm)
(mm)
25
80
168
66
ANSI class 150 and class 300 dimensions:
BS16, DIN PN16 and JIS 10K dimensions:
Meter size
(inch)
L1
L2
D1
Weight
(lb)
Meter size
(mm)
L1
L2
D1
Weight
(kg)
(inch)
(inch)
(inch)
(mm)
(mm)
(mm)
1
3.15
6.61
2.60
approx. 7
40
50
80
100
150
200
100
110
110*
120*
230
190
207
232
264
324
385
85
approx. 4
approx. 5
approx. 6
approx. 9
approx. 21
approx. 35
102
127
159
216
267
Figure 7. Separate type detectors
LF410 and LF414
Meter size 25mm (1")
300
The dimension of L1 is changed when the material of
grounding ring is chosen Pt-Ir or Ta
ANSI class 150 and class 300 dimensions:
Meter size
15mm (1/2”)
25mm (1”)
L1
Meter size
(inch)
L1
L2
D1
Weight
(lbs)
77mm (3.03 inch)
95mm (3.74 inch)
115mm (4.53 inch)
126mm (4.96 inch)
126mm (4.96 inch)
136mm (5.35 inch)
242mm (9.53 inch)
312mm (12.28 inch)
(inch)
(inch)
(inch)
1-1/2
3.94
4.33
4.33*
4.72*
9.06
7.48
8.15
9.13
10.39
12.76
15.16
3.35
4.02
5.00
6.26
8.50
10.51
approx. 9
approx. 11
approx. 13
approx. 20
approx. 47
approx. 78
40mm (1 1/2”)
50mm (2”)
2
3
4
6
8
80mm (3”)
100mm (4”)
150mm (6”)
200mm (8”)
11.81
*When Teflon PFA lining is selected, L1 in the table
above becomes as follows:
ꢂL1: 115mm (4.53 inch) for meter size 80mm (3")
ꢂL1: 126mm (4.96 inch) for meter size 100mm (4")
Figure 8. Separate type detectors
LF410 and LF414
Meter size 40 (1 1/2") to 200mm (8")
7
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
4–Φ11
Unit : mm
13
151
25
82
Attachment
74±0.3
LCD display
Excitation cable ground
I/O cable ground
Ground terminal
(M4)
Power supply cable ground
Signal cable ground
Blind screw
IR Switch
Cable ground
Figure 9. Separate type converter LF602
ꢀExternal Connections
ꢃCombined type LF410/LF600 and LF414/LF600 flowmeters
Instrument Panel : Ordered separately
I/O Cable (CVV-S)
Ground terminal
Current output
(4~20mAdc) or
PROFIBUS
Intermediate
voltage (IV) wire,
5.5mm2 or more.
Digital Output 1
Signal common
for DI and DO
To be grounded
with 100Ω or less
ground resistance.
Digital Output 2
Digital Input
(20 to 30Vdc)
Grounded with
100Ω or less
ground resistance
Grounded with
100Ω or less
ground resistance
Power supply
1
*
Power Cable (CVV)
Power Switch
(External double-pole power switch)
*1 Locate an external double-pole power switch on the power line near the flowmeter within easy reach of operation.
Use the appropriate switch rating as shown below:
Switch rating: 250Vac, 6A or more
In rush current: 15A or more
Figure 10. Combined type LF410/LF600 and LF414/LF600
flowmeters Wiring Diagram
8
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
<Separate type LF410/LF602 and LF414/LF602 flowmeters>
Terminal board
Thick walled steel conduit
IV wire
5.5 mm2 or more
Grounded with 100Ω or less
ground resistance
Power switch
(External double-pole power switch )
[Instrument panel : ordered separately]
Signal cable
(2-wire shielded hard-rubber
sheathed cable)
Power supply
Current output (4~20mAdc)
or PROFIBUS
Digital output 1
Signal common for DI and DO
Connected detector
Digital output 2
Excitation cable
(3-wire shielded hard-rubber cable)
Digital input
(20~30Vdc)
Power cable
(CVV)
Digital input cable
(CVV-S)
Symbol
L1 (+)
L2 (-)
GND
FG
DI
DO1
DO2
COM
Description
Cable
Power supply
Power cable (CVV)
I/O cable (CVV-S)
Ground (for arrester)
Frame ground
Digital Input (20~30Vdc)
Digital Output 1
Digital Output 2
Signal Common for DI, DO1, DO2
Current Output (4~20mAdc)
+
-
Shielded cable for
PROFIBUS-PA
or PROFIBUS
X
Y
E
A
B
G
Excitation cable (for
LF602 only)
Excitation Output
Signal Input
Signal cable (for LF602
only)
Figure 11. Separate type LF410/LF602 and LF414/LF602
flowmeters wiring Diagram
9
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
(7) Only one PROFIBUS-PA cable goes through a
cable gland of the Electromagnetic Flowmeter.
Please use the junction box at system
configuration.
ꢀWiring Precautions
(1) Explosion proof type flowmeters are not
provided cable glands.
Refer to the part Cable connection port at
detector and converter.
(2) Connect the grounding wire (IV wire 5.5mm² or
more) to a good earth ground (100Ω or less
ground resistance). Make the wire as short as
possible. Do not use a common ground shared
with other equipment where earth current may
flow. An independent earth ground is
recommended.
(3) The allowable cable lengths between the detector
and converter for the separate type flowmeter
depend on the electrical conductivity of the
object fluid. See Figure 12 below.
300
200
100
50
30
10
5
3
(4) DO1, DO2 (opt.), and DI (opt.) use the same
common terminal (COM). This COM can not
connect to other equipments which have their
own ground terminal.
3
5
10 20 30 50100200
Conductivity (μS/cm)
Figure 12. Electrical Conductivity and
Cable Length
(Power supply for connecting to DI or DO,
etc…) Need to wire separately.
ꢀ Wiring Precautions (PROFIBUS)
(1) For wiring path, avoid places near electrical
equipment that may cause electromagnetic
induction or electrostatic induction interference
(such as a motor, transformer and wireless
transmitter).
(2) Use a PROFIBUS-PA cable for signal cable. In
addition, make sure to use a shielded cable to
improve noise resistance. Furthermore,
installation of signal cable in metal conduit is
recommended.
(3) General PROFIBUS-PA cables are designed for
indoor use where cables are not exposed to
humidity, rain, etc. When you install cables,
make sure to check the operating conditions such
as the operating temperature range of the cable
by contacting its manufacturer.
(4) When you carry out cable end treatment of
PROFIBUS-PA cable, use a dedicated cable
stripper etc. so that the core wire of the cable will
not be nicked or damaged. In addition, for cables,
be careful of allowable maximum bend diameter
etc. (Basically, do not install cables in a way
cables are twisted or bent.).
(5) Consider installing a PROFIBUS-PA arrester in
the communication path of PROFBUS-PA so
that the electromagnetic flowmeter will not be
affected by lightning etc.
(6) The electromagnetic flowmeter is not equipped
with terminating resistors.Use the terminating
resistor unit for PROFIBUS-PA or junction box,
if necessary.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
ꢀ Piping Precautions
(1) Design piping so that the flowmeter detector pipe
is always filled with the fluid being measured,
whether the fluid is flowing or not.
(2)The detector has no adjustable piping mechanism.
Install an adjustable short pipe where needed.
(3) The required straight pipe length should comply
with the requirements as follows.
(4) Be sure to grounding the flowmeter according to
below figure.
L
≧
L
≧
L
≧
5D
10D
0
When using a 90°bent, Tee, diffuser, or fully opened valve
When using other types of valves
When no valve plate protrudes into the detector pipe
Upstream side
Downstream side
L:Required straight pipe length
D:Meter size
Grounding of the Combined type and Separate type
Separate type
Combined type
Grounding
terminal
Grounding terminal
Grounding terminal
Grounding wire
Grounding wire
(100 ohm or less
ground resistance)
Gasket
(100 ohm or less
ground resistance)
Gasket
(100 ohm or less
ground resistance)
11
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
ꢀMeter Size
ꢀCalibration Range
If the calibration range is not specified, the standard
range as shown below will be used. If the range is
specified, we will use the specified range for
calibration.
To select the meter size:
See Figure 13 and find meter sizes within the
velocity of 0.1 to 10m/s for a specified full-scale
(measuring range high limit) flow. Select one that
has its full-scale velocity between 1 and 3m/s.
Table 1. Standard Flow Range
Note: Make sure the full-scale flow rate used for the
final planning stage stays within 10m/s in terms
of flow velocity.
Standard flow range
Flow rate Flow velocity Flow rate
mm (inch)
Meter size
(m³/h)
2
6
15
25
(m/s)
3.144
3.395
3.316
3.537
3.316
3.537
3.144
2.653
(gal/min)
25
15 (1/2)
25 (1)
40 (1 1/2)
50 (2)
75
175
300
650
1,000
2,500
4,500
Flow
velocity
(m/s)
80 (3)
60
100 (4)
150 (6)
200 (8)
100
200
300
Flow rate (m3/h)
Note: The unit of "gal/min" is not exchanged
(converted) by "m3/h".
For SI unit
Meter size
(mm)
Unit: m3/h
Flow rate
1 m/s
0.6361
1.767
4.523
7.067
18.09
28.27
63.61
113.1
ꢀPED matrix in each flange connection.
The following sizes fall under the category for PED
in each flange connection when the meter ships to
EU. All of them had complied with it from a notified
body.
0.3 m/s
0.1908
0.5301
1.357
2.120
5.428
8.482
19.08
33.93
10 m/s
6.361
17.67
45.23
70.67
180.9
282.7
636.1
1131
15
25
40
50
80
100
150
200
Table 2 PED matrix in each flange connection
Flange standard
Meter size
150 to 400mm
(6 to 16 inch)
250 to 400mm
(10 to 16 inch)
6 to 16 inch
DIN PN 16 and BS 16
DIN PN 10 and BS 10
ANSI 150 and JIS10K
For English unit
Meter size
Unit: gal/min
Flow rate
3.28ft/s
2.801
7.780
19.91
31.12
79.65
124.5
280.1
(150 to 400mm)
(inch)
0.98ft/s
0.8401
2.334
5.975
9.334
23.90
37.35
84.01
149.4
32.8ft/s
28.01
77.80
199.1
311.2
796.5
1,245
2,801
4,980
1/2
1
1 1/2
2
3
4
6
8
498.0
Figure 13. Flow Rate and Flow Velocity
12
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
ꢀ About establishment environment
Do not store or install the flowmeter in:
• Places where there is direct sunlight.
• Places where excessive vibration or mechanical
shock occurs.
• Places where high temperature or high humidity
conditions obtain.
• Places where corrosive atmospheres obtain.
• Places submerged under water.
• Place where there is slop floor. To put the
flowmeter temporarily on the floor, place it
carefully with something, such as stopper, to
support it so that the flowmeter will not topple over.
Ordering Information
1. When ordering the LF410 series flowmeters, refer
to Tables 3 and 4 (Type Specification Codes).
An entry must be made for each of the columns in
each of these tables.
2. Fluid characteristics:
(1) Type of fluid to be measured and its characteristics
(2) Fluid temperature
(3) Fluid pressure
(4) Electrical conductivity of the fluid
3. Measuring range
4. I/O function setting
5. Ordering scope:
In places like the following places, there is the case
that infrared switches do not function correctly. (If
this is unavoidable, use an appropriate cover.
•Places where gets very bright light onto operation
panel. (direct sunlight, reflection light of sunlight
by windowpanes, diffused reflection light of
strength etc.)
Flow calibration data: (required or not)
6. Other items
Specifications other than standard items
Consult Toshiba representative before ordering
when choose materials of the wetting parts such as
lining, electrodes, and grounding rings.
•Places where smoke and steam occur near.
•Places where a snow, ice or mud that may attached.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
Table 3. Specification Code (Wafer type detector LF410 Series)
Detector category
Normal type
Gr.-A Gr.-B Gr.-C Gr.-D
Model
Specification Code
Description
Ex. type
1
L
L
2
3
4
1
1
5
0
4
6
7
8
9
10 11 12 13 14
F
F
4
4
Normal specification type
√
√
Hazardous location certification type (Note 1)
√
√
Meter size
D
E
F
G
H
J
15mm (½")
25mm (1")
40mm (1½")
50mm (2")
80mm (3")
100mm (4")
150mm (6")
200mm (8")
√
√
√
√
√
√
√
√
√
√
√
√
K
L
√
√
√
√
Mounting Style
L
M
P
Detector/Converter combined type (LF410/LF600)
Detector/Converter separate type (LF410/LF602)
Detector/Converter combined type with PED (LF410/LF600) (Note 6)
Detector/Converter separate type with PED (LF410/LF602) (Note 6)
FM and CSA Class - I Division 2 type (Note 1)
Detector/Converter combined type (LF414/LF600)
Detector/Converter separate type (LF414/LF602)
√
√
√
√
√
√
√
√
Q
A
B
√
√
√
√
Connection flange standard (Note 2)
C
D
E
F
G
H
J
K
L
Z
ANSI 150
ANSI 300
BS PN 10
BS PN 16
DIN PN 10
DIN PN 16
JIS 10K
JIS 16K
JIS 20K
other
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢄ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢄ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
–
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
ꢁ
–
Electrode Material (Note 6)
316L stainless steel
Ti (titanium)
Pt-Ir (platinum/iridium)
Ta (tantalum)
B
C
D
E
F
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
–
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
–
Hastelloy C (Equivalent)
other
Z
Lining Material (Note 6)
Alkali-resistant ceramic (Note 3)
Acid-resistant ceramic (Note 3)
Teflon PFA
A
B
C
ꢁ
ꢁ
ꢄ
ꢁ
ꢁ
ꢄ
–
–
ꢁ
–
–
ꢁ
Grounding Ring Material (Note 6)
316 stainless steel
316L stainless steel
Ti (titanium)
C
D
E
F
G
H
Z
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
–
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢄ
–
Ta (tantalum)
Pt-Ir (platinum/iridium)
Hastelloy C (Equivalent)
other
Flow and calibration velocity range
0.3 to 10 m/s (standard range calibration)
0.3 to 10 m/s (specified range calibration)
0.1 to 10 m/s (specified range calibration)
Excitation and Signal Cables
A
B
C
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
A
B
C
not provided
30m cable, provided (Note 4)
other lengths, provided (Note 4)
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
Coating
A
B
C
D
E
no coating
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
ꢄ
ꢄ
–
ꢁ
ꢄ
ꢄ
ꢄ
–
ꢁ
ꢄ
ꢄ
ꢄ
phthalic acid resin coating pearl-gray colored (Note 5)
black tar epoxy resin 0.3 mm
black tar epoxy resin 0.5 mm
Black tar epoxy resin 0.5 mm for submersible type (Note 7)
Size code explanation: √ :Object ꢁ: Standard ꢄ: Option –: Not available
Note1: Cable glands are not provided. Refer to the part of “Cable connection port” at detector and converter.
Note2: Same shape of flange standard among ANSI 150, ANSI 300, BS10, BS16, DIN10, DIN16, JIS10K, JIS16K, and JIS20K.
Note3: The type of material used is alumina ceramic, this is suitable for both acid and alkali liquids.
This ceramic lining and the electrodes are held with seals, there are two types, one for acids, and the other for alkalis.
Note4: Separate type detector only. Specifyng the code “C”, indicate the length of cables from 1 to 300m in 1 meter increments.
Note5: Phthalic acid resin coating is standard for the flowmeter with meter size 15mm(1/2”), 150mm(6”), and 200mm(8”).
Note6: Consult Toshiba before ordering when choose materials at the wetting parts.
Note7: Ceramic lining only. (Teflon PFA lining is not available.)
Note8: Check the Table 2 whether your chosen meter size meets this directive or not when the meter is shipped to EU. If yes, need to choose this code.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
Table 4. Specification Code for converters
Model
Specification Code
Contents
LF600 LF602
1
L
2
3
6
4
5
6
7
8
9 10 11 12 13 14
type
type
F
0
Electromagnetic flowmeter converter
0
2
Integral (Combined) type
Separate (Remote) type
ꢁ
–
–
ꢁ
Purpose
A
F
Standard
cFMus class I, Division 2 approved
ꢁ
ꢄ
ꢁ
ꢄ
Shape
Integral type with case
ꢁ
A
B
–
ꢁ
–
Separate type with case
Converter mounting fitting
A
C
E
None
ꢁ
–
–
ꢄ
ꢁ
ꢄ
Panel, Accessory for wall mounting (BNP material: SUS304)
Accessory for pipe installation (BNP material: SUS304)
Digital input/output
1
2
Digital output points 1 (DO1)
Digital output points 2 (DO1+DO2) +Digital input point 1 (DI)
ꢁ
ꢄ
ꢁ
ꢄ
Current output and Communication function
1
2
Current output + HART communication
PROFIBUS communication (Current output is not usable)
ꢁ
ꢄ
ꢁ
ꢄ
Power supply
100Vac-240Vac, 50/60Hz
24Vdc
1
2
3
ꢁ
ꢄ
ꢄ
ꢁ
ꢄ
ꢄ
110Vdc
Instruction manual
Japanese
English
ꢄ
ꢁ
A
E
ꢄ
ꢁ
Code explanation: ꢁ: Standard ꢄ: Option
–: Not available
15
Download from Www.Somanuals.com. All Manuals Search And Download.
LF410/LF600 LF410/LF602
ISO9001 and ISO14001 are certified.
Specifications are subject to change without notice.
Printed in Japan 2006-10 (TDOC)
© TOSHIBA Corporation 2006
All Rights Reserved.
Misuse of this product can result in damages to property or human injury.
Read related manuals carefully before using this product.
No. EJL-114B