6 F 3 B 0 3 6 2
T2N Ethernet Port
Instruction Manual
REQUIREMENTS
·
Keep this instruction manual where it can be easily
referred to by users and those responsible for the
equipment.
·
·
Read this instruction manual carefully before using
the equipment.
After this instruction manual has been read, keep it
beside the equipment.
Contents
July, 1998
TOSHIBA CORPORATION
UM-TS02N**-E006
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Safety Precautions
Thank you for purchasing the Toshiba PU235N/245N CPU module, which is for use with the T2N
programmable controller.
This document describes the usage and handling of the PU235N/245N built-in Ethernet Port and
presents important cautionary items.
To use the PU235N/245N Ethernet Port safely, please read this document and all other related
documentation thoroughly and acquire thorough knowledge of the equipment and points that
require care before installing, operating, maintaining, or inspecting the PU235N/245N.
[Concerning Important Points]
1. The PU235N/245N is designed and manufactured for use with general industrial equipment,
including all types of production line control and manufacturing equipment.
The PU235N/245N is not designed or manufactured for use in equipment or systems on which
human lives depend.
Consult with your Toshiba sales representative in advance if you need to use an
PU235N/245N in a equipment or systems that are used in transportation equipment (such as
trains), medical applications, aerospace applications, nuclear reactor control, or underwater
relay equipment or other special contexts.
2. Although the PU235N/245N is manufactured under strict quality control, if an PU235N/245N
is to be used in critical equipment in which human lives could be endangered or in which large
losses could occur should the PU235N/245N fail, install safety equipment so that such
catastrophes cannot occur.
3. The PU235N/245N should only be installed, wired, used, or maintained by persons who have
a general knowledge of the handling of control equipment. Electrical shock, fires, failures, and
malfunctions can occur if an PU235N/245N is handled incorrectly. Persons whose knowledge
of control and electrical equipment is inadequate should avoid installing, wiring, using, or
maintaining this equipment, and should instead employ persons with the requisite specialized
knowledge.
4. This document and the related separate documentation is written for persons with a general
knowledge of programmable controllers and control equipment.
If you have any questions about the contents of this documentation, please feel free to contact
you Toshiba representative.
¾ 2 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Safety Precautions (continued)
[Warning indications]
This instruction manual provides important information to allow these products to be used safely
and correctly, to prevent in advance dangers to people managing or using this equipment or other
persons, and to prevent in advance losses to property. Be sure you thoroughly understand the
displays and symbols described below and follow the cautionary items and warnings included in
this document carefully.
Store this document carefully so that you can refer to it at any time even after you have read it.
Description of Safety Signs
Safety sign
Meaning
Indicates a potentially hazardous situation which could result in
death or serious injury if you do not follow the instructions.
WARNING
Indicates a potentially hazardous situation which may result in
minor or moderate injury and/or property damage if you do not
follow the instructions.
CAUTION
Explanations of Safety Symbols
Safety symbol
Meaning
This means "Hazard Alert" or "Beware of Hazard". The exact
nature of the hazard is shown in the triangle or described in text
near the triangle.
This is a safety alert symbol indicating a potential hazard. This
symbol is used together with a signal word.
¾ 3 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Safety Precautions (continued)
Precautions for operation
·
WARNING
1. Build emergency stop, interlock, and similar circuits outside the PU235N/245N.
If a breakdown or malfunction occurs in the PU235N/245N, there is the danger that someone could
be hurt or fatally injured. Also, other equipment could be damaged or a breakdown could occur.
T2N User's Manual - Hardware
3. Preparing for Operation (Hardware)
CAUTION
1. Take all necessary safety precautions before performing operations such as changing a running
program, forcing output, or switching to RUN (operate) or HALT (stop) modes.
Equipment can be damaged and breakdowns can be caused by operating this equipment
incorrectly.
T2N User's Manual - Hardware
Program Operation Manual
3. Preparing for Operation (Hardware)
¾ 4 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Safety Precautions (continued)
· Mounting in the base unit
CAUTION
1. The Ethernet Port is built-in the PU235N/245N. Do not remove the Ethernet Port from a
PU235N/245N.
2. The PU235N/245N itself should only be mounted or removed when all power is turned off. Similarly,
connections to the terminal block should only be made or removed when all power is turned off. Not
observing this precaution could result in electrical shocks, malfunctions, or damage to the
PU235N/245N or other equipment.
3. Do not allow foreign objects such as wire shreds to get into the PU235N/245N. This could result in
fire, breakdown, or malfunction.
4. Verify that connectors, cables, and the mounting of the PU235N/245N itself in the base unit are all
secured and that there is no play, missing screws, or disconnections in any of these parts.
If any of these parts is inadequately secured, breakdown or malfunction could occur as the result of
vibration.
3.3 Mounting in the Base Unit
·
Connecting to the network
CAUTION
1. Do not connect or disconnect cables when either the T2N or HUB power supply is turned on. This
can damage the PU235N/245N or cause it to malfunction.
2. When installing a 10BASE-T network, the cabling must be laid with adequate safety precautions and
in accordance with all applicable standards. Installation and wiring should be performed by a
qualified professional.
See the ISO/IEC8802-3 standard for installation environment standards.
3.1 Connecting to the Network
¾ 5 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Safety Precautions (continued)
Concerning:
·
·
·
·
Preparing for operation (software)
Computer link protocol and the PC link protocol transmission
Socket interface communication
RAS information
CAUTION
1. Chapters 4 - 7 present information related to using the functions provided by the Ethernet Port from
a T2N, including the instruction (request) format, important items that require attention, and sample
programs. That chapter also presents items considered necessary when using the Ethernet Port.
Make a point of understanding the content of chapter 4 thoroughly before writing programs that use
the Ethernet Port. The sample programs present basic examples of Ethernet Port usage, and should
be reviewed carefully before use in an actual system.
4. Preparing for operation (software)
5. Computer link protocol and the PC Link protocol transmission
6. Socket interface communication
7. RAS information
·
Installation environment and base unit mounting
CAUTION
1. Only use this equipment in the environment described in the T2N User's Manual - Hardware.
Use in any other environment can cause electrical shocks, fires, failures, and malfunctions.
2. Mount this equipment according to the mounting method specified in the T2N User's Manual -
Hardware.
Mounting in any direction other than the specified direction, or defective or inadequate mounting,
can result in the equipment falling, fires, failures, and malfunctions.
9.1 Installation Environment and Base Unit Mounting
¾ 6 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Safety Precautions (continued)
· Basic points in laying out a network
CAUTION
1. When laying network cable, take adequate safety measures and perform all operations in
accordance with the relevant standards. See the ISO/IEC8802-3 standard for details on laying
networks.
2. We strongly recommend hiring a qualified contractor who has specialized knowledge about safety
precautions and standards.
3. Avoid installing 10BASE5, 10BASE2 or 10BASE-T networks in environments that have high noise
levels. If it is necessary to install network cables in an environment subject to noise (electromagnetic
interference), use the noise reduction measures described elsewhere in this document.
9.2 Network Wiring
·
Maintenance
CAUTION
1. Always turn off the power before attaching or removing modules or cables. Electrical shock,
malfunctions, and breakdowns are possible if these operations are performed with the power on.
2. To keep the system operating normally at all times and to prevent trouble in advance, perform daily
inspections, periodic inspections, and cleaning.
3. Refer to the section on error recovery in this document if the Ethernet Port does not operate
correctly.
Contact your local Toshiba dealer or service representative if a breakdown occurs, and request that
the module be repaired or returned to Toshiba.
Operation and safety cannot be guaranteed if service is performed by anyone other than an
authorized Toshiba service representative.
4. Do not disassemble or modify the module hardware, and do not modify the module software.
Breakdowns or malfunctions may lead to fire, electrical shock, or injury.
5. Do not continue to use the module if it emits smoke or unusual odors, or if it is in an abnormal state
of any type.
Using the module in an abnormal state can lead to malfunctions, breakdowns, and electrical shock.
In such cases, immediately turn of all power and contact your local Toshiba dealer or service
representative.
Customers should never attempt repairs or modifications to this equipment themselves: repair and
modification operations are extremely dangerous.
Appendix 1 Maintenance and Inspection
¾ 7 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Usage Recommendations
This section collects the knowledge and operations that should be known by all users of this
equipment. Read this section carefully in conjunction with the safety precautions, thoroughly
master knowledge of the equipment, safety information, and the items that require attention, and
use the equipment correctly.
·
Support for 10BASE-T network
Usage Recommendations
1. Do not exceed the maximum cable length (100 m) in systems using 10BASE-T.
1.3 Basic Functionality
·
Ethernet Port registration
Usage Recommendations
1. Before performing the settings described in this chapter, register the Ethernet Port as T2N I/O. The
I/O type is ETHER (PU235N) or E/S (PU245N).
4.1 Ethernet Port Setup Flowchart (Software)
·
Restrictions on subnet masks
Usage Recommendations
1. The Ethernet Port does not allow the user to set the subnet mask. The Ethernet Port that the
network address number is 1 can use the subnet mask. Therefore the Ethernet Port cannot be used
in systems that operate a subnetwork.
4.4 Parameter Setup Request
¾ 8 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Usage Recommendations (continued)
· Computer link protocol transmission
Usage Recommendations
1. Since UDP/IP does not provide control functions to guaranteed communication reliability, higher
level protocols (such as retry) are required.
2. No processing is performed if a computer link protocol and a PC link protocol transmission
messages are received at any point other than a message transmission UDP socket.
5.1 Computer Link Protocol Transmission
5.3 PC Link Protocol Transmission (Data write)
5.4 PC Link Protocol Transmission (Data read)
·
Limitations on the T2N SEND and RECV instructions
Usage Recommendations
When using the SEND and RECV instructions:
1. When using fixed period interrupt programs, there are limitations on the number of words that can
be specified.
Appendix 4 Limitations on the T2N SEND and RECV Instructions
¾ 9 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Before Reading This Document
Thank you for purchasing a Toshiba PROSEC T2N multi-purpose programmable controller.
This manual describes the T2N Ethernet Port specifications and usage, and presents sample
programs for the Ethernet Port used with the PROSEC T2N.
The PU235N has Ethernet Port and the PU245N has Ethernet and TOSLINE-S20LP Port.
The T2N Ethernet Port is built-in a T2N and the T3H Ethernet module is independent module. It is
called “port” with this manual and called “station” with Ethernet Module EN311 for T3H
Instruction Manual are same meaning. This manual describes port.
When using this product, use the product correctly based on a thorough reading of this manual.
When using a T3H Ethernet module, see “Ethernet Module EN311 for T3H Instruction Manual”.
This document is organized as follows.
Chapter 1: Ethernet Port Overview
Presents an overview of the PU235N/245N Ethernet Port, including its functions, specifications,
and systems in which it can be used. Refer to this chapter to understand the basic performance of
the Ethernet Port.
Chapter 2: Ethernet Port Parts and Functions
Describes the function and names of the components of the Ethernet Port. Since this chapter
presents information required to understand the hardware settings described in the next chapter,
read this chapter carefully and use the Ethernet Port correctly.
Chapter 3: Preparing for Operation (Hardware)
Describes the hardware preparations and settings required to operate the Ethernet Port normally.
Chapter 4: Preparing for Operation (Software)
Describes the software settings required to operate the Ethernet Port normally, and presents
sample programs.
Chapter 5: Computer Link Protocol and the PC Link Protocol Transmission
Describes the instruction format used with computer link protocol and PC link protocol
transmission, and presents sample programs.
Chapter 6: Socket Interface Communication
Presents an overview of the socket interface, cautionary items, and the instruction format used on
the Ethernet Port with the socket interface, and presents sample programs.
Chapter 7: RAS Information
Describes the instruction format and the format of the Ethernet Port RAS information (including
port status and down information), and presents sample programs.
Chapter 8: Error Handling
Describes techniques for determining the causes of errors when Ethernet Port operation is
abnormal, and procedures for recovering from those errors.
¾ 10 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Chapter 9: Installation and Wiring
Describes the procedures for installing the Ethernet Port (and T2N), procedures for laying
transmission cable, and the nature of the construction required.
Appendix
Presents request code, completion status value, and error code tables and describes the minimum
transmission delay times and execution times for each instruction.
Note that in addition to this manual, Toshiba also provides a T2N User's Manual - Basic
Hardware and Function, a T-series Instruction Set, and a T-series Computer Link Operation
Manual. All these manuals should be read together.
Describes the configuration, specifications,
installation and wiring techniques,
·
T2N User's Manual - Basic Hardware
and Function
maintenance, and preventive maintenance
procedures for the T2N base system hardware
and describes the function provided by the
T2N CPU and the use of that CPU, and
presents information required for creating user
programs for the T2N.
(UM-TS02**-E001)
·
·
T-series Instruction Set
(UM-TS03***-E004)
Describes the detailed specifications of the
instruction words for the ladder and SFC
program languages, which are two of the
programming languages supported on the T2N.
T-series Computer Link Operation Manual
(UM-TS03***-E008)
Describes the specifications and use of
computer link protocol transmission, which is
built into the T2N CPU.
Registered trademarks:
Ethernet is a registered trademark of Xerox Corporation.
Cheapernet is not a registered trademark, but rather is a common name.
3 Com and Etherlink III are trademarks of 3 Com Corporation.
PC-NFS Pro is trademarks of Sun Microsystems, Inc..
Visual Ctt is trademarks of Microsoft Corporation.
Microsoft is trademarks of Microsoft Corporation.
UNIX is trademarks of UNIX System Laboratories, Inc..
¾ 11 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Contents
Safety Precautions¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 2
Usage Recommendations ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼8
Before Reading This Document¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 10
1. Ethernet Port Overview¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 14
1.1 System Configuration Using the Ethernet Port¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 14
1.2 LAN Standards and Terminology ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼15
1.3 Basic Functionality ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼16
1.4 Ethernet Port Specifications¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼21
1.5 Software Organization ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼22
2. PU235N/245N Parts and Functions ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 24
2.1 Front Panel¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼24
2.2 Component Functions¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 25
3. Preparing for Operation (Hardware)¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 26
3.1 Connecting to the Network¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 27
3.2 Network Wiring Equipment¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 28
4. Preparing for Operation (Software) ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 31
4.1 Ethernet Port Setup Flowchart (Software) ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 31
4.2 Ethernet Port Instruction Specifications¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 32
4.3 Ethernet Port Reset¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼39
4.4 Parameter Setup Request¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 41
4.5 Operating Mode Control Requests¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 46
5. Computer Link Protocol and the PC Link Protocol Transmission ¼¼¼¼¼¼¼¼¼ 50
5.1 Computer Link Protocol Transmission ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 50
5.2 Sample Computer Link Protocol Program ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 51
5.3 PC Link Protocol Transmission (Data write) ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 57
5.4 PC Link Protocol Transmission (Data read)¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 61
5.5 Sample PC Link Protocol Transmission Program¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 64
¾ 12 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6. Socket Interface Communication ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 68
6.1 Overview ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 68
6.2 Ethernet Port Socket Interface Usage Notes¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 72
6.3 Socket Interface Information ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 82
6.4 Using the Ethernet Port Socket Interface ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼84
6.5 Sample Programs ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼112
7. RAS Information ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼122
7.1 T2N Special Relays and Registers¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 123
7.2 Down Information ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼125
7.3 Remote Port Verification Request¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 126
7.4 Remote Port Loopback (for an Ethernet Port)
¼¼¼¼¼¼¼¼¼¼¼¼¼¼128
7.5 Time Setting ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼130
7.6 RAS Information Readout ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 132
8. Error Handling ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼140
8.1 LED Display ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼140
8.2 Status (error status) ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 143
8.3 T2N Special Relays and Registers ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 146
8.4 Socket Interface Information ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 147
8.5 Troubleshooting ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 148
9. Installation and Wiring ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼163
9.1 Installation Environment and Base Unit Mounting¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 163
9.2 Network Wiring ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼164
Appendix
Appendix 1 Maintenance and Inspection ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼ 169
Appendix 2 Request Code Table ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼171
Appendix 3 Status Table ¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼¼172
Appendix 4 Limitations on the T2N SEND and RECV Instructions ¼¼¼¼¼¼¼¼¼ 175
¾ 13 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
1. Ethernet Port Overview
1.1 System Configuration Using the Ethernet Port
This section describes the systems that can be configured using the PU235N/245N Ethernet Port
for the PROSEC T2N programmable controller. The remainder of this document refers to the
PROSEC T2N programmable controller as the T2N, and the Ethernet Port as the PU235N/245N
Ethernet Port.
The Ethernet Port is a communication port for connecting a T2N system to a 10BASE-T (Twisted
pair Ethernet) LAN (local area network). It is operated a T2N option module. The T2N connects
to the above mentioned LAN through the Ethernet Port and exchanges data with host computers
(workstations or personal computers) or other programmable controllers on the LAN.
The remainder of this section presents a system that uses the Ethernet Port. In this example, the
T2N is connected to host machines such as workstations and personal computers over a 10BASE-
T LAN and the T2N is connected to lower level controllers using a Toshiba proprietary control
LAN.
Host machine
Personal computer
Workstation
T3H:PROSEC-T3H
T2N:PROSEC-T2N
T2 :PROSEC-T2
S20LP:TOSLINE-20LP
F10:TOSLINE-F10
R-I/O: Remote I/O for F10
10BASE-T
HUB
PU235N
E
T
H
E
R
T
2
N
F
1
0
PU245N
E
T
H
E
R
S
T
2
N
2
0
L
P
TOSLINE-F10
TOSLINE-S20LP
PU245N
T
2
F
1
0
R-I/O
R-I/O
I/O I/O
T
3
H
S I/O I/O
T
2
N
E
T
H
E
R
S I/O
T
3
H
S I/O I/O
2
0
L
P
2
0
L
P
2
0
L
P
Figure 1.1 System Configuration Examples
¾ 14 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
1.2 LAN Standards and Terminology
The LANs commonly referred to as Ethernet LANs are defined by two standards, the Ethernet
version 2.0 standard (DIX) developed by DEC, Intel, and Xerox, and the ISO 8802-3 standard
(IEEE 802.3), which is an international version of the DIX standard. Since the ISO 8802-3
includes the DIX standard, network equipment built to those standards will be basically
compatible.
Since the Ethernet Port physical layer has a structure that conforms to the ISO 8802-3 standard,
users must be sure to use network equipment that conforms to the ISO 8802-3 standard.
The networking terminology used in this document is the terminology used in the ISO 8802-3
standard. Table 1.3 presents the correspondence between the DIX standard terminology (common
terms) and the ISO 8802-3 standard terminology.
Table 1.1 Networking Terminology Correspondences
DIX Standard
Ethernet
ISO 8802-3 Standard
10BASE5
Cheapernet
10BASE2
Coaxial cable
Transceiver cable
Transceiver
Coaxial cable
AUI (attachment unit interface) cable
MAU (medium attachment unit)
MAC address
Ethernet address
Ethernet is a registered trademark of Xerox, Corporation.
Cheapernet is not a registered trademark, but rather is a common name.
¾ 15 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
1.3 Basic Functionality
The Ethernet Port has the following main features.
1. T series computer link protocol transmission (slave port)
The host machine can upload or download user programs, execute control commands, and read or
write register data to a T2N on the 10BASE-T LAN using the T series computer link protocol.
This function can be used simply by making basic settings on the Ethernet Port from the T2N;
there is no need to write special user programs for the T2N.
Computer link protocol uses UDP/IP as the transmission protocol.
UDP/IP: User datagram protocol/Internet protocol.
Host machine
Personal computer
Workstation
Application
program
Response
10BASE-T
Request
Ethernet
Port
T2N operating
system
User program
Figure 1.2 T Series Computer Link Protocol Transmission (slave port)
¾ 16 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2. T series/PC link protocol transmission
The T2N can use the T series/PC link protocol to read or write register data on another T2N on the
10BASE-T LAN.
While T2N user programs for reading and writing are necessary to use the host functions, only the
basic Ethernet Port settings performed from the T2N are required to use the slave functions, and no
special user programs are required on the T2N.
PC link protocol transmission uses UDP/IP as the transmission protocol.
UDP/IP: User datagram protocol/Internet protocol .
PC link host station
User program
T2N operating
system
Ethernet
Port
Response
10BASE-T
Request
Ethernet
Port
T2N operating
system
User program
PC link slave station
Figure 1.3 T Series/PC Link Protocol Transmission
¾ 17 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
3. Socket interface support
This is a standard communications technique used on engineering workstations and similar
computers. Transmission between user programs on the T2N and host machines is possible using
the socket interface. There are eight sockets on an Ethernet Port and the transmission protocol
(TCP/IP or UDP/IP) can be specified for each socket.
TCP/IP: Transmission control protocol/Internet protocol
UDP/IP: User datagram protocol/Internet protocol
Host machine
Personal computer
Workstation
Application
program
Socket
Data transmission
10BASE-T
Ethernet
Port
Socket
T2N
User program
Figure 1.4 Socket Interface
¾ 18 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4. PC (programmable controller) gateway function
* This function is under development, but is currently not supported.
Toshiba plans to add support to the T2N for a gateway function between the Ethernet Port and the
TOSLINE-S20LP Port. This function will allow access to stations (PROSEC-T3H/T2N) on the
TOSLINE-S20LP from ports on the 10BASE-T LAN using the computer link protocol.
Host machine
Personal computer
Workstation
Application
program
Response
Request
10BASE-T
Ethernet
Port
T2N operating
system
PU245N
TOSLINE-
S20LP Port
TOSLINE-S20LP
Response
Request
TOSLINE
-S20LP
TOSLINE
-S20LP
TOSLINE
-S20LP
T3H
T3H
T2N
Figure 1.5 Gateway Function
¾ 19 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5. Support for 10BASE-T Network
The Ethernet Port can connect to a 10BASE-T network
10BASE-T is a LAN technology that uses baseband transmission, provides a data transmission
rate of 10 Mbps, and supports single segments of up to 100 meters in length.
This network uses 10BASE-T (Twisted pair cable) as the transmission cable.
The figure below shows the maximum interport separation.
Node
Node
Twisted pair cable
Twisted pair cable
100m
100m
HUB
500m
HUB
500m
HUB
500m
HUB
Coaxial cable (10BASE5)
It is regarded that HUB is repeater and a twisted pair cable is single segment (link
segment).
Figure 1.6 10BASE-T
Usage Recommendations
1. Do not exceed the maximum cable length (100 m) in systems using 10BASE-T.
¾ 20 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
1.4 Ethernet Port Specifications
Table 1.2 lists the Ethernet Port specifications. The general specifications of the Ethernet Port
conform to those of the T2N main unit.
Table 1.2 Functional Specifications
Item
Specification
Module type
PU235N/245N (Ethernet Port is built-in)
10BASE-T
Transmission
specifications
Media access method
Modulation
CSMA/CD
Baseband
Transmission topology
Transmission speed
Bus type
10 Mbps
Maximum distance between
ports
200 m (Case of single HUB)
1700 m (Case of four HUB)
100 m (Between port and HUB)
single port per segment
None
Maximum segment length
Maximum number of ports
Minimum port separation
Connector
8-pin modular connector (RJ-45)
Unshield twisted pair
Connecting cable
Transmission services
1. T series computer link protocol (slave port)
2. T series/PC link protocol
3. Socket interface (8 sockets)
4. PC gateway function (currently unsupported)
RAS functions
1. Self diagnostics at power on
ROM, RAM, LAN controller, EEPROM,
T2N interface buffer memory, MAC address
2. Test functions accessible from user programs
•
•
Remote port verification request
Remote port loopback test (Between T2N and T2N/T3H systems)
3. Data provided by RAS data readout
•
•
•
Event trace
LAN controller (network) information
Protocol state
4. Time/date setup function
5. Station status in the T2N special registers (SW)
6. Socket information in the T2N interface buffer
Consumed current [A]
External dimensions [mm]
Weight [grams]
0.6A (5V DC)
99.0 (W) ´ 122 (H)
200
Mounting method
Built-in T2N
Number of modules mountable
Access method
1 modules per T2N
SEND/RECV instructions (module control and transmission functions)
*
Segment: A network unit formed from a single transmission medium (twisted pair cable)
¾ 21 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
1.5 Software Organization
The Ethernet Port transmission functions (computer link protocol transmission, PC link protocol
transmission and socket interface transmission) are implemented with the software organization
shown in the figure.
T2N user program
SEND/RECV instruction
T2N Upper Protocol
software
T2N firmware
Computer link/PC link/socket interface
T2N internal bus
Ethernet Port interface
UDP
TCP
Ethernet
Port
IP
ARP
CSMA/CD
10BASE-T
ICMP
Figure 1.7 Software Organization
TCP (transmission control protocol)
Before transferring data with the remote port, a connection (virtual communication circuit) is first
established and then data is transferred. Transmission reliability is guaranteed by packet order
control, retransmission, flow control, and other techniques.
The Ethernet Port supports the following:
·
·
·
·
·
·
·
·
Response bit (ACK)
Push bit (PSH)
Synchronized bit (SYN)
Fin bit (FIN)
Retransferring
Window (flow) control
Segment division
Reporting of the maximum receivable segment length
The Ethernet Port does not support the reset bit (RST).
¾ 22 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
UDP (User datagram protocol)
Transfers data with the remote port in datagram units. Provides high-speed transfers since a
connection is not used, but does not have control functions that assure reliability, as does TCP.
Thus it requires support from a higher level protocol.
The Ethernet Port supports the:
·
the UDP checksum
function.
IP (Internet protocol)
Sends and receives data in the datagram format. Sends data in datagram units to the remote port
according to the IP address.
The Ethernet Port supports:
·
·
·
Data fragmentation and reassembly,
Direct routing, and
Broadcast
functions.
The Ethernet Port does not support the indirect routing and multicast functions.
Although the Ethernet Port physical layer structure conforms to the ISO8802-3 standard, it adopts
DIX standard frames as the data link frames (the IP datagram send/receive frames).
ARP (Address resolution protocol)
Searches for a port MAC address (Ethernet address) that has a specified IP address.
ICMP (Internet control message protocol)
Reports IP packet errors, verifies the state of the IP network, and supports related functions.
The Ethernet Port supports the:
·
·
·
Echo request/reply,
Timestamp request/reply, and
Information request
functions.
The Ethernet Port does not support the:
·
·
·
·
·
·
·
Destination unreachable,
Source quench,
Redirect,
Time exceeded for a datagram,
Parameter problem on datagram,
Information reply,
Address mask request, and
·
Address mask reply
functions.
¾ 23 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2. Ethernet Port Parts and Functions
This chapter describes the sections of the Ethernet Port and their functions.
2.1 Front Panel
ERUN ET/R
EACC
Ethernet Port LED Display
SRUN SONL SACC
STNH
STNL
TOSLINE-S20LP
Port parts
(PU245N only)
OTR1
OTR2
10BASE-T
Ethernet Port 10BASE-T
connector for connecting
transmission cable
Figure 2.1 PU235N/245N External Dimensions
¾ 24 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2.2 Component Functions
(1) LED Display
Indicators that display the Ethernet Port operating state.
ERUN ET/R
EACC
LED display
(All LED’s color is green)
Figure 2.2 LED’s display and name
Content Displayed
Table 2.1 LED Display Content
LED
Content
ERUN
Indicates whether or not the Ethernet Port is operating normally.
On.... The Ethernet Port is operating normally.
Off.... The Ethernet Port error occurred.
(Ether Run)
ET/R
Indicates whether or not the Ethernet Port is transmitting data or receiving data.
On.... Data transmission or receipt in progress
Off.... Data is not being transmitted or received.
(Ether Transmis-
sion / Receive)
EACC
Indicates whether or not the T2N is accessing the Ethernet Port.
On.... The T2N is accessing the Ethernet Port.
Off.... The T2N is not accessing the Ethernet Port.
(Ether Access)
(2) 10BASE-T connecting connector
This connector is used for connecting 10BASE-T twisted pair cable and Ethernet Port.
See section 3.1, " Connecting to the Network ", for detailed information on connection.
¾ 25 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
3. Preparing for Operation (Hardware)
This section presents the Ethernet Port setup.
WARNING
1. Build emergency stop, interlock, and similar circuits outside the PU235N/245N. If a breakdown or
malfunction occurs in the PU235N/245N, there is the danger that someone could be hurt or fatally
injured. Also, other equipment could be damaged or a breakdown could occur.
CAUTION
2. Take all necessary safety precautions before performing operations such as changing a running
program, forcing output, or switching to RUN (operate) or HALT (stop) modes.
Equipment can be damaged and breakdowns can be caused by operating this equipment incorrectly.
¾ 26 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
3.1 Connecting to the Network
The Ethernet Port supports 10BASE-T network.
(1) Connection to a 10BASE-T Network
This section describes the connection procedure starting from the state where the 10BASE-T
twisted pair cable is already supplied and ready to be connected. See section 9.2, "Network
Wiring", for details on wiring the 10BASE-T twisted pair cable.
PU235N/245N
Ethernet Port
To HUB
10BASE-T connection
connector
Twisted pair cable
Figure 3.1 Connection to a twisted pair cable
(1) Align the twisted pair cable with the 10BASE-T connector and insert the modular connector.
(2) Pull the 10BASE-T connector and verify that the connector is locked and cannot be pulled
out.
CAUTION
1. When installing a 10BASE5, 10BASE2 or 10BASE-T network, the cabling must be laid with adequate
safety precautions and in accordance with all applicable standards. Installation and wiring should be
performed by a qualified professional.
See the ISO/IEC8802-3 standard for installation environment standards.
Usage Recommendations
1. Do not exceed the maximum cable length (100 m) in systems using 10BASE-T.
2. A HUB and a twisted pair cable are required in systems configured using a 10BASE-T network.
(See section 3.2, "Network Wiring Equipment.")
These parts must be ordered separately if required.
¾ 27 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
3.2 Network Wiring Equipment
This section describes the wiring and related equipment that makes up the network to which the
Ethernet Port is connected. Since the Ethernet Port conforms to the ISO 8802-3 (IEEE 802.3)
standard, users should select equipment to be used in the network that also conforms to this
standard.
The following section introduces recommended wiring and related equipment. We strongly
recommend that these models be used when new items are needed.
Contact the manufacturer directly for detailed information on this equipment.
(1) 10BASE-T
Twisted pair cable
·
Catalog no.
ECM-04-¨¨¨M
¨¨¨:Length(1 to 100)
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
(Enable cross cable)
·
HUB
Catalog no.
ETH-807B ( 8 ports)
ETH-707A (16 ports)
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
(Enable cross cable)
¾ 28 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(2) 10BASE5
·
Coaxial cable
Catalog no.
EEA-9202-¨M+TMJ x 2
¨: Length
Standard outside 10.3 mm diameter, with terminators at both ends
diameter
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
·
·
·
·
·
Plugs
Catalog no.
EPL-6213
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Terminators
Adapters
Catalog no.
EEJ-6213
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Catalog no.
EAD-6213
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Grounding clamps
AUI cable
Catalog no.
EEL-6213
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Catalog no.
AUI15-¨M
¨: Length
Standard outside 6.5 mm diameter (thin wire), molded connectors
diameter
Length
1, 2, 3, 5, 10, and 15 meters
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Catalog no.
AUI50-¨M
¨: Length
Standard outside 10.5 mm diameter (thick wire), molded connectors
diameter
Length
20, 30, 40, and 50 meters
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
·
MAU
Catalog no.
ETR-6071 02
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
¾ 29 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(3) 10BASE2
·
Coaxial cable
Catalog no.
RG-58A/U
Standard outside 5.0 mm diameter, with BNC plugs at both ends
diameter
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
·
·
·
·
BNC plugs
T connectors
Adapters
Catalog no.
EPL-1067
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Catalog no.
ETS-8191
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Catalog no.
EAD-8191
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
Terminators
Catalog no.
EEJ-8191
Manufacturer
Showa Electric Wire & Cable Co., Ltd.
CAUTION
1. When installing a 10BASE5, 10BASE2 or 10BASE-T network, the cabling must be laid with
adequate safety precautions and in accordance with all applicable standards. Installation and wiring
should be performed by a qualified professional.
See the ISO/IEC8802-3 standard for installation environment standards.
¾ 30 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4. Preparing for Operation (Software)
This section describes setting up the Ethernet Port software for operation.
CAUTION
1. Chapter 4 presents information related to using the functions provided by the Ethernet Port from a
T2N, including the instruction (request) format, important items that require attention, and sample
programs.
Make a point of understanding the content of chapter 4 thoroughly before writing programs that use
the Ethernet Port. The sample programs present basic examples of Ethernet Port usage, and should
be reviewed carefully before use in an actual system.
4.1 Ethernet Port Setup Flowchart (Software)
This section presents the flowchart for Ethernet Port setup.
Start
There are two ways to reset the Ethernet Port:
·
·
Turn on the T2N power.
Apply the reset operation from a user program on the T2N.
For details on these reset operations, see section 4.3, "Ethernet Port
Reset."
Reset the Ethernet Port
The Ethernet Port parameters required for network transmission are
set up by a user program running on the T2N. For details on these
setup operations, see section 4.4, "Parameter Setup Request."
Set up the Ethernet Port
parameters from the T2N.
In this state, the system can handle remote port verification requests.
See section 7.3, "Remote Port Verification Request." In this state, the
system can respond to existence verification requests from other ports.
The Ethernet Port operating mode is set by user programs running on
the T2N. For details on these operations, see section 4.5, "Operating
Mode Control Requests."
Specify the Ethernet Port
operating mode from the
T2N.
In this state, the PC link and computer link protocol transmission
slave port functions are operating.
(Assuming that they have not been explicitly disabled by the
operating mode settings.)
End
Figure 4.1 Ethernet Port Setup Flowchart (Software)
Usage Recommendations
Before performing the settings described in this chapter, register the PU235N/245N as T2N I/O. The I/O
type is ETHER or E/S.
¾ 31 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4.2 Ethernet Port Instruction Specifications
Before discussing the software side of the Ethernet Port setup procedure, this section presents an
overview of the SEND and RECV instructions, which are the instructions that are used to control
the Ethernet Port from T2N user programs. Ethernet Port control and transmission control (PC link
protocol transmission and socket interface transmission) are performed solely using the SEND and
RECV instructions.
See the individual items for details on the actual requests sent to the Ethernet Port.
(1) Instruction format
Figure 4.2 shows the formats of the SEND and RECV instructions.
Input
Output
[ A
S E N D
R E C V
Register
B ]
Input
Output
[ A
B ]
Operand
Name
Device
INDEX
Index
Con-
stant
X
Y
S
L
R
Z
X
Y
S
L
R
W
T
C
D
F
I
O
I
J
K
W
W
W
W
W
W
W
A
B
Transfer parameter
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
ü
Status
Input
OFF
ON
Operation
Output
ERF
No execution
Execution
OFF
OFF
OFF
Transmission port instruction busy/instruction execution in OFF
progress (response wait)
Response reception complete (normal complete)
Instruction error
ON
ON
OFF
ON
Figure 4.2 SEND/RECV Instruction Formats
<Important items>
a. ERF is the S0051 special relay. See the T-series Instruction Set for information on ERF
usage.
b. For these instructions, instruction execution starts at the point the input changes state
from off to on.
c. Since these instructions span multiple scans, applications must hold the input in the on
state until the output goes to the on state.
If the input is turned off before the output goes on, the system will not be able to execute the
following instruction processing normally.
d. After instruction execution terminates, it is possible to start execution again by applying a
new input.
¾ 32 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(2) Transfer parameters (A)
The data required for a request to the Ethernet Port is set up in an area that starts in the register
indicated by [A]. Then the application executes a SEND or RECV instruction. Here we present an
overview of the structure of the transfer parameters. Tables 4.1 and 4.2 list the requests that can be
issued to an Ethernet Port.
A
3100H
CMD
Module designation
A + 1
Command number: Indicates the request type to the Ethernet
Port.
Parameters
A + 2
A + 3
M
Parameters:
This data differs depending on the type of
the request to the Ethernet Port.
Module designation:
3 (Module ID):
Designates the Ethernet Port mounted in the T2N.
Must be set to 3 for an Ethernet Port.
Must be set to 1 for an Ethernet Port.
This two-digit field must be set to 00.
1 (channel number):
00 (station number):
<Important items>
e. Do not modify the contents of the transfer parameters while an instruction execution is in
progress.
The SEND or RECV instruction may not complete.
Table 4.1 Instructions (Requests) to the Ethernet Port (Part 1)
Request
Function
Instruction
SEND
CMD
Reset request
Resets the Ethernet Port.
Sets up the Ethernet Port parameters.
0011H
0012H
Parameter setup
request
SEND
Operating mode
control request
Sets the operating mode.
SEND
SEND
RECV
SEND
RECV
SEND
SEND
0013H
0014H
0015H
0018H
0021H
0021H
000FH
¬
Remote port
verification request
Verifies the existence of another port on the network.
Reads out the Ethernet Port RAS information.
RAS information
readout request
Time set request
Sets the Ethernet Port internal clock
Time information for event trace (RAS information)
Register read request Reads register data from remote T2N into registers in the local
(PC link function) T2N.
Register write request Writes register data from the local T2N to registers in remote
(PC link function) T2N.
•
®
Remote port loopback Performs a loopback operation with another Ethernet Port on the
request
network.
UDP open request
UDP send request
UDP receive request
UDP close request
Opens a socket interface (UDP).
Sends data from a socket interface in the UDP open state.
SEND
SEND
0031H
0032H
0033H
0034H
Reads data received by a socket interface in the UDP open state. RECV
Closes (terminates) a socket interface in the UDP open state. SEND
CMD (command number): Indicates the request type to the Ethernet Port.
¾ 33 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 4.2 Instructions (Requests) to the Ethernet Port (Part 2)
Request
Function
Instruction
CMD
TCP open request
Opens a socket interface (TCP).
SEND
SEND
RECV
0035H
TCP send request
Sends data from a socket interface in the TCP open state.
0037H
0038H
®
TCP receive request Reads data received by a socket interface in the TCP open
state.
TCP close request
Closes (terminates) a socket interface in the TCP open state.
SEND
0039H
CMD (command number): Indicates the request type to the Ethernet Port.
<Important items>
f. Items ¬ to ® are CMD classes. Class ¬ is Ethernet Port control, • is PC link protocol
transmission, and ® is socket interface transmission.
·
·
·
For a single Ethernet Port, it is not possible to request another class ¬ CMD while a
class ¬ CMD is executing. This is also true for class • CMDs. If such a request is
issued, the status (described in the following status information) will be transmission port
busy, and the request will go to the wait state.
For a single Ethernet Port, when requesting a class ® CMD, it is not possible to request
another class ® command for a socket for which an instruction is executing. If such a
request is issued, the status (described in the following status) will be transmission port
busy, and the request will go to the wait state.
There are eight sockets, and each can independently accept and execute a class ®
instruction.
g. If the T2N switches from the run to the halt state and then back to the run state while an
instruction is executing, it is possible that the Ethernet Port could execute the request issued
immediately prior to the halt state. This section describes the handling required after
returning to the run state.
·
The T2N should always set the Ethernet Port to standby mode after the T2N returns to
run mode. (See 4.5.) Setting the Ethernet Port to standby mode causes all the requests
issued to the Ethernet Port to be discarded, computer link and PC link protocol
transmissions to be stopped, and the socket interface to be initialized, i.e. set to the
closed state.
·
Before setting the Ethernet Port to standby mode, verify the operating mode (See 4.5.)
with the Ethernet Port station status. (See section 7.1.) If the Ethernet Port is in run
mode, set it to standby mode. However, if it is in standby mode, there is no need to set it
to standby mode again.
¾ 34 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(3) Status (B)
The status during the execution of a SEND or RECV instruction and after that instruction
terminates is stored in the register shown at B. When TermSTS = 0BH, the detailed information
(Ethernet Port error information) will be loaded into the registers indicated at location B + 1.
Figure 4.3 shows the structure of the status information. Tables 4.3 and 4.4 list the TermSTS
values, and table 4.5 and 4.6 lists the contents of the detailed information.
B
Status
B+1
Detailed information
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
Sport NO
TermSTS
Only on an error 0: Error occurred at local station.
1: Error occurred at remote station.
Socket identifier: Only valid for socket interface transmission
instructions. ("0" for other instructions)
status 0: Initial state
busy 0: Initial state
1: Transmission port busy
1: While send requesting
2: Send complete and while waiting
response
abn 0: Normal complete
1: Error complete
3: Complete
Figure 4.3 Status Structure
<Important items>
h. The user program must set bits C and D to 0 before first activating a SEND/RECV
instruction. Failure to do so will cause the SEND/RECV instruction to not complete.
Also, do not write to the status during instruction execution. This will cause the
SEND/RECV instruction to not complete.
i. When the number of SEND/RECV instructions are used in the user program and their
instructions are executed simultaneously, separate the status and detailed information
register every instruction.
Table 4.3 TermSTS (Part 1)
TermSTS Status
Meaning
00H
01H
Normal complete
Register specification error
•
Occurs if a register other than XW, YW,W, LW, RW, D, F, T, C, or SW is
specified as the data storage register in one of the following requests.
Requests: RAS information readout, remote port loopback, UDP send/receive,
TCP send/receive, register read/write.
•
•
In a register read or write request, the request specified a read or write from a
T register to a register other than a T register.
(This also applies to C registers.)
02H
Response timeout
Occurs if a response is not received within the specified time for a remote port
loopback or register read/write request.
¾ 35 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 4.4 TermSTS (Part 2)
Meaning
TermSTS Status
03H Parameter error
•
•
•
Occurs if a value other than 3 is specified for the module ID.
Occurs if a value other than 1 is specified for the channel number.
Occurs if a command number other than one of the following is specified for a
SEND instruction.
000FH, 0011H - 0014H, 0018H, 0021H, 0031H, 0032H, 0034H, 0035H,
0037H, 0039H
•
Occurs if a command number other than one of the following is specified for a
RECV instruction.
0015H, 0021H, 0033H, 0038H
•
•
Occurs if a value other than 1 to 8 is specified for the socket identifier.
(See section 6.4 "Using the Ethernet Port Socket Interface".)
Occurs if an incorrect parameter is specified in a RAS information readout
request.
(See section 7.6 "RAS Information Readout ".)
04H
Memory write protect
(Reserved)
•
•
Occurs if an attempt to write is made when the remote registers were write
protected.
Occurs if an attempt to read is made when the local registers were write
protected.
05H
06H
Module error
•
•
•
Occurs if the Ethernet Port is down.
Occurs if the Ethernet Port is initializing.
Occurs if a T2N internal timer times out.
Requests: UDP open, UDP send, UDP close, TCP send, TCP close
Initialization in progress
Transmission complete
timeout
07H
08H
No send channel (CH)
•
•
Occurs if the corresponding Ethernet Port is not installed.
Port address out of range
Occurs if the local port IP address was specified for the remote destination IP
address.
Requests: Remote port loopback, register read/write
09H
0AH
Incorrect transmission word
count
•
•
Occurs if either 0 words or 486 or more words were specified for either a
register read/write or a remote port loopback request.
Occurs if either 0 words or 1001 or more words were specified for a UDC/TCP
send/receive request.
Boundary error
•
Occurs if the specified area (start address + register range) does not exist in
the T2N data storage registers.
Requests: RAS information readout, remote port loopback, UDP send/receive,
TCP send/receive, register read/write
0BH
0CH
Transmission error
•
•
Occurs if the Ethernet Port returns an error response.
Detailed information (the Ethernet Port response status) is stored at B+1.
No I/O response
(Reserved)
Occurs if the T2N cannot access the Ethernet Port.
0DH
0EH
Send data capacity
exceeded
•
•
Occurs if a request is discarded when a T2N internal resource insufficiency
occurs due to increasing amounts of transfer data.
Occurs if a T2N retransmission times out.
0FH
(Reserved)
¾ 36 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 4.5 Detailed Information (Ethernet Port Error Responses) PART1
Code
Error
Description
Normal complete
Local port fault
Local port standby
0001H Request completed normally
0002H The local port is in down mode
0003H In standby mode data transmission (socket interface transmission or PC link
protocol transmission) was requested.
Timeout
0020H Timeout occurred during TCP open processing or receive processing, or during
UDP receive processing.
Length error
0030H Incorrect send data length
Port mode error
0040H One of the following requests was issued in a mode other than standby mode:
a. Parameter setup, b. MAC address setup, c. Reset
MAC/IP not set up
0050H
Occurs if the MAC address or IP address is not set up.
Transmission prohibited state
0060H • Occurs if a PC link request was issued from the T2N in run mode in the
message transmission prohibited state.
• Occurs if a socket open, close, send, or receive request is issued by the T2N
in run mode in the socket interface transmission prohibited state.
Format error
0070H Occurs when there is a format error in the request text.
0071H Port number error
0072H Request code error
0073H Time setting: Year
0074H Time setting: Month
0075H Time setting: Day
0076H Time setting: Hour
0077H Time setting: Minute
0078H Time setting: Second
Opened
0080H Occurs if an open request is issued for an already open socket.
Unopened
0081H • Occurs if send, receive, or close request is issued for an unopened socket.
• Occurs if send, receive request is issued for TCP socket during receiving
CLOSE request (RCLOSE bit is 1).
Incorrect socket identifier
0082H Occurs if the socket identifier is out of range (1 to 8).
Incorrect control request
specification
0083H Occurs if a request that was prohibited by an operating mode control request is
issued.
• Occurs if a run request is issued in run mode.
• Occurs if a standby request is issued in standby mode.
• Occurs if a run request and a standby request are issued at the same time.
LAN controller driver error
0090H Occurs if the setting of the local port IP address and port number in the area
reserved for transmission fails.
0091H • Error in the TCP or UDP protocol (such as a transmission phase error)
• Occurs if send request is issued for TCP socket that remote port is down and
NOACK bit is 1.
0092H • Occurs if the setting of the remote port IP address in the remote port
information area (the NETDATA table) fails.
• Occurs if the remote port IP address network address differs from the local
port IP address network address.
¾ 37 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 4.6 Detailed Information (Ethernet Port Error Responses) PART2
Code
Error
Description
Memory pool allocation failure
Port 2 task start failure
Broadcast specification error
00A0H Occurs if the Ethernet Port internal OS fails to allocate memory.
00A1H Occurs if computer link or PC link socket identifier acquisition fails.
00A2H Occurs if the remote IP address is broadcast on a remote port verification
request.
MAC address specification error 00B0H BCC error
00B1H
00C0H
00C1H
Occurs if an error occurs after address saving on a MAC setup request.
Occurs if send request is issued for the Ethernet Port internal buffer fill.
The specifiable size from user program
Resource shortage error
Receive request from the T2N
< The Ethernet Port is receiving data size
00C2H
The specifiable size of user program beyond the limits from 1 to 1000.
¾ 38 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4.3 Ethernet Port Reset
This section describes the Ethernet Port reset procedures. There are two ways to reset an Ethernet
Port as follows:
(1) T2N power on
(2) Reset by a user program running on the T2N
In Ethernet Port reset processing, when one of the above resets occurs, the Ethernet Port first
performs the self check described below. If the self check completes normally, the Ethernet Port
switches to standby mode (the parameter setting wait state), thus completing the reset sequence. If
an error is discovered during the self check, the Ethernet Port goes to the down state.
·
Ethernet Port self check items
·
·
·
·
·
System ROM check
System RAM check
LAN controller check
T2N interface buffer memory check
EEPROM check
See section 4.5, "Operating Mode Control Requests", for more information on the Ethernet Port
operating modes.
(1) T2N power on
When power is applied to the T2N, power is also applied to the Ethernet Port, and the
PU235N/245N performs its reset processing sequence.
¾ 39 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(2) Reset request from the T2N
It is possible to initiate reset processing from user programs on the T2N. T2N can execute the reset
processing instruction on standby mode (See section 4.5). This section describes the format of the
reset processing instruction.
Reset request (using the SEND instruction)
a. Function
Reset request from a user program to an Ethernet Port.
b. Transfer parameters
Module designation
CMD number
A
3100H
A+1
CMD = 0011H
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
An error will occur if the Ethernet Port is in run mode or down mode.
Run mode - Status: Transmission error (TermSTS = 0BH)
Detailed information: Port mode error (0040H)
Down mode - Status: Module error/initialization in progress (TermSTS = 06H)
e. Sample program
This sample ladder program issues a reset request to the channel 1 Ethernet Port.
This program is executed by turning on the R0501 A contact.
Parameters: 12544:3100H, 00017:0011H
|R0501
R0601 |
1|-| |-----------------------------------------------------------( )--|
|
/* Reset request
*/
|R0601
|
2|-| |-+[ 12544 MOV RW000][ 00017 MOV RW001]--------------------------|
|
|
|
|
|
|
/* Designates the module and sets the CMD number. */
|
+[RW000 SEND RW010][ RST R0501]--------------------------------|
/* Sets the request.
*/
¾ 40 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4.4 Parameter Setup Request
This section describes the procedure for Ethernet Port parameter setup in the Ethernet Port from a
T2N user program. The Ethernet Port parameters consist of the following:
(1) Local port IP address
(2) UDP port number for computer link and PC link transmission
Here we first describe the IP address, subnet mask, and port number, which are the parameters
required for TCP/IP and UDP/IP transmission.
(1) IP address
The IP address is the address that specifies a particular port when transmitted data using the IP
(internet protocol). Therefore IP addresses must be set and managed so that they are not
duplicated. The following presents an overview of IP addresses.
a. IP address format
An address consists of a network address and a host address. The network address is an address
that specifies a particular network, and the host address is an address that specifies a particular
port on that network. The same network address must be assigned to all ports on the same (i.e., any
given) network.
An IP address is a 32-bit data item. IP addresses are written as the decimal values of each byte in
the 32-bit datum, with the decimal values separated by dots.
Example: 11000000 00000000 00000000 00000001 ® 192.0.0.1
IP addresses are divided into five classes, A through C, according to how many bits in the 32-bit
value are used as the network address. (The networking standards also define classes D and E, but
the Ethernet Port does not support them.) Figure 4.4 shows the classes A though C.
0
0
8
16
24
31
Class A
Class B
Class C
Network: 7
Host: 24 bits
• 127 values (networks)
• 16,777,214 values (hosts)
1 0
Network: 14 bits
Host: 16 bits
• 16384 values (networks)
• 65534 values (hosts)
1 1 0
Network: 21 bits
Host: 8 bits
• 2,097,152 values (networks)
• 254 values (hosts)
Figure 4.4 IP Address Class Divisions
In this system, networks with a large number of connected ports use class A addresses and
networks with s small number of connected ports use class C addresses. Class B addresses are
used for networks that fall between classes A and C. Expressed in decimal, the first byte of the
class A through C networks will be: 0 to 127 for class A, 128 to 191 for class B, and 192 to 223
for class C.
b. IP address acquisition
Taking future uses into account, we strongly recommend acquiring an official IP address.
¾ 41 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
c. Notes on IP addresses
The following IP addresses cannot be used with the Ethernet Port, both for the local port and for
remote port addresses.
·
·
·
Addresses starting with 127 (7FH).
Addresses in which the network address is all zeros or all ones.
Addresses in which the host address is all zeros or all ones.
d. Broadcast addresses
The only broadcast address that can be used with the Ethernet Port is 255.255.255.255
(FF.FF.FF.FF).
The broadcast address 0.0.0.0 used on some UNIX systems (4.2 BSD) cannot be used.
UNIX is an operating system used on engineering workstations (EWS) and other computers. There are
several versions of UNIX, including ones developed by AT&T Bell Laboratories Inc., and ones
developed by the University of California at Berkeley. In particular, 4.2 BSD is a version developed at
Berkeley.
(2) Subnets and the subnet mask
One technique for managing a network with a large number of ports is to divide that network into
multiple subnets. A subnet operates by taking some number of bits in the host address of the IP
address for each class, and using those bits as a subnetwork address. This allows the installation to
operate the network internally as multiple subnetworks, while the network is recognized externally
as a single network.
The subnet mask is used to determine how many bits of the host address to allocate as the subnet
address. In the subnet mask, the network address field and the subnetwork address field are set to 1
and the remaining field (the subnet host address field) is set to 0.
Example: When a subnetwork address field of 12 bits is used in a class A IP address.
1111 1111 1111 1111 1111 0000 0000 0000 (FFFFF000)
Network
address field
Subnetwork
address field
Host address
field
When a subnet mask is used, all ports on the subnetwork must use the same subnet mask.
In the Ethernet Port, the subnet mask cannot be set by the user. The subnet masks (with the
network address field filled with ones) for each class are generated automatically as shown in table
4.7 from the specified IP address.
Table 4.7 Relationship between the Local IP Address
and the Generated Subnet Mask on the Ethernet Port
Local IP Address
Subnet mask
class A
class B
class C
255.0.0.0 (FF000000)
255.255.0.0 (FFFF0000)
255.255.255.0 (FFFFFF00)
Usage Recommendations
1. The PU235N/245N does not allow the user to set the subnet mask. Therefore the Ethernet Port
cannot be used in systems that operate a subnetwork.
¾ 42 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(3) Port number
An IP address identifies a particular port on a network. However, since, on any given port, there
will be multiple applications using TCP/IP or UDC/IP to communicate with applications on other
ports, the question of to which application the data should be passed arises.
UDP ports have the role of acting as the point of contact between UDP and applications that
transfer data using UDP. UDP ports are managed using port numbers. In the same manner, TCP
uses TCP ports.
The combination of a port number and an IP address is called a socket. The Ethernet Port
transmits data to or from other ports using these sockets in the computer link protocol, the PC link
protocol, and in socket interface transmission.
The range of port numbers that can be used with the Ethernet Port is from 1024 to 65535,
for both TCP and UDP. This is because UNIX allocates port numbers 1 to 1023 for standard
services.
However, note that the same port number cannot be used for both TCP and UDP on the
Ethernet Port.
The following section describes the format of the parameter setup request.
Parameter setup request (using the SEND instruction)
a. Function
This is a request from a user program that sets up the Ethernet Port parameters in an Ethernet Port
in standby mode.
b. Transfer parameters
A
3100H
Module designation
CMD number
A+1
A+2
A+3
A+4
CMD = 0012H
Local port IP address for the
Ethernet Port
UDP port number for message
UDP port number used for computer link or PC
link protocol transmission.
·
IP address setup procedure: For the address 133.113.90.10
¯
85H. 71H. 5AH. 0AH
F
8 7
0
A+2
A+3
71H
0AH
85H
5AH
¾ 43 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
·
Message transmission UDP port number
As described in chapter 1, UDP/IP is used for both computer link and PC link protocol
transmission, which are collectively referred to as message transmission. These techniques use
dedicated UDP sockets that are separate from those used by socket interface transmission.
Set the port number to a value in the range 1024 to 65535. (UNIX allocates port numbers 1
to 1023 for standard services.)
The UDP port number specified at A+4 is the UDP port number allocated for message
transmission (receive). The two port numbers following that port number are automatically
allocated for message transmission (send). If computer link protocol/PC link protocol reception
is performed directed at the message transmission UDP port number specified at A+4, the
Ethernet Port/T2N will process the received data in the order received and send the result from
one of the message transmission send ports. (See figure 4.5.)
Ethernet Port
Message transmission receive port
(port number 2000)
Computer link/
PC link protocol transmission
Message transmission send port 1
(port number 2001)
Computer link protocol transmission
Message transmission send port 2
(port number 2002)
PC link protocol transmission
Figure 4.5
Relationship between Message Transmission Send
and Receive Port Numbers
As mentioned in the section on socket interface transmission, UDP port numbers used for message
transmission must not duplicate UDP socket port numbers or TCP socket port numbers.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
An error will occur if the Ethernet Port is in run mode or down mode.
Run mode - Status: Transmission error (TermSTS = 0BH)
Detailed information: Port mode error (0040H)
Down mode - Status: Module error (TermSTS = 06H)
·
An error occurs if a UDP port number is set to a value outside the range 1024 to 65535.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Port number error (0071H)
e. Sample program
This sample ladder program issues a parameter setup request to the channel 1 Ethernet Port.
¾ 44 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
This program is executed by turning on the R0502 A contact.
Parameters: 12544:3100H, 00018:0012H
29061:7185H, 02658:0A62H
|R0502
R0602 |
1|-| |-----------------------------------------------------------( )--|
|
/* Parameter setup request */
|R0602
|
2|-| |-+[ 12544 MOV RW000][ 00018 MOV RW001]--------------------------|
|
|
|
|
|
|
|
|
|
|
/* Designates the module and sets the CMD number. */
|
+[ 29061 MOV RW002][ 02658 MOV RW003][ 01025 MOV RW004]--------|
|
|
/* Sets the IP address, Port number. */
|
+[RW000 SEND RW010][ RST R0502]--------------------------------|
/* Sets the request.
*/
|
¾ 45 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4.5 Operating Mode Control Requests
This section describes the Ethernet Port operating modes and the procedures for controlling the
Ethernet Port operating mode from user programs on the T2N.
The Ethernet Port has the following operating modes:
(1) Initialization mode
·
·
·
This mode indicates that the Ethernet Port is executing reset processing.
If reset processing completes normally, the Ethernet Port switches to standby mode.
If reset processing exits with an error (e.g., if a self test error occurs) the Ethernet Port
switches to down mode.
·
During initialization, the Ethernet Port cannot execute requests from T2N user programs.
(2) Standby mode
·
·
·
In this mode, Ethernet Port parameter can set up.
Ethernet Port parameters cannot be set up in any mode other than standby mode.
After the Ethernet Port parameters have been set up, the Ethernet Port can be switched to run
mode by T2N user program instructions.
(3) Run mode
·
·
·
In this mode, the Ethernet Port can communicate with other ports.
The Ethernet Port can be switched to standby mode by T2N user program instructions.
In run mode, transfers using computer link/PC link protocol and transfers using the socket
interface can be independently enabled or disabled.
(4) Down mode
·
·
This mode indicates that the Ethernet Port is in an unrecoverable error state.
Once the Ethernet Port enters the down state, it can only be restored by turning the power off
(power cycling) and then on again.
·
The details of the down mode state can be verified by reading the data in the T2N interface
buffer memory.
(See chapter 7, "RAS Information.")
¾ 46 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Figure 4.6 shows the Ethernet Port mode transitions.
Power down
Power applied
Self check completes normally
Initialization
Standby
Reset request
Power on/off/on
cycle
Standby request
Self check terminates
in an error state.
Run request
Unrecoverable error
Unrecoverable error
Down
Run
Figure 4.6 Ethernet Port Mode Transitions
¾ 47 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
This section describes the operating mode control request instruction format.
Operating mode control request (using the SEND instruction)
a. Function
This is a request from a user program that controls the Ethernet Port operating mode.
b. Transfer parameters
A
3100H
Module designation
CMD number
A+1
A+2
CMD = 0013H
Specified information
Specified information
F
0
E
0
D
C
B
0
A
0
9
0
8
0
7
0
6
0
5
4
3
0
2
0
1
0
0
0
STBY
MTEN
RUN
STEN
Bit D: STBY (standby request)
Switches the Ethernet Port from run mode to standby mode.
Bit C: RUN (run request)
Switches the Ethernet Port from standby mode to run mode.
Bit 5: MTEN (message transmission enable/prohibit request)
Computer link/PC link protocol transmission enable/prohibit
1: Enable, 0: Prohibit
Bit 4: STEN (socket interface transmission enable/prohibit request)
Socket interface transmission enable/prohibit
1: Enable, 0: Prohibit
Examples: Standby request - 2000H
Run request - 1030H (Allows both message transmission and socket interface
transmission)
1010H (Allows socket interface transmission only)
1020H (Allows message transmission only)
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
¾ 48 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
d. Important items
·
Values other than 1010H, 1020H, 1030H, and 2000H may not be specified for the
specification information.
® Status: Transmission error (TermSTS = 0BH)
Detailed information: Incorrect control request specification (0083H)
·
·
Simultaneous run mode and standby mode requests (30x0H) cannot be executed.
® Status: Transmission error (TermSTS = 0BH)
Detailed information: Incorrect control request specification (0083H)
A mode that has already been established cannot be requested. However, requests that change
the MTEN/STEN state within the same mode do not cause an error.
® Status: Transmission error (TermSTS = 0BH)
Detailed information: Incorrect control request specification (0083H)
·
·
No execution is possible in down mode.
® Status: Module error/initialization in progress (TermSTS = 06H)
An error occurs if a control request that switches the Ethernet Port to run mode is issued
without first setting the IP address.
® Status: Transmission error (TermSTS = 0BH)
Detailed information: MAC/IP not set up (0050H)
e. Sample program
This sample ladder program issues a operating mode control request to the channel 1 Ethernet Port.
This program is executed by turning on the R0503 A point.
Parameters: 12544:3100H, 00019:0013H
04144:1030H
|R0503
R0603 |
1|-| |-----------------------------------------------------------( )--|
|
/* Control request
*/
|R0603
|
2|-| |-+[ 12544 MOV RW000][ 00019 MOV RW001]--------------------------|
|
|
|
|
|
|
|
|
|
|
/* Designates the module and sets the CMD number. */
|
+[ 04144 MOV RW002]--------------------------------------------|
|
|
/* Setup specified information. */
|
+[RW000 SEND RW010][ RST R0503]--------------------------------|
/* Sets the request.
*/
|
¾ 49 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5. Computer Link Protocol and the PC Link
Protocol Transmission
CAUTION
1. Chapter 5 presents information related to using the functions provided by the Ethernet Port from a
T2N, including the instruction (request) format, important items that require attention, and sample
programs.
Make a point of understanding the content of chapter 4 thoroughly before writing programs that use
the Ethernet Port. The sample programs present basic examples of Ethernet Port usage, and should
be reviewed carefully before use in an actual system.
This chapter describes computer link protocol transmission from a host computer and PC link
protocol transmission with the T2N.
5.1 Computer Link Protocol Transmission
The T series computer link protocol transmission was developed by Toshiba for use in controlling
the PROSEC-T Series programmable controllers. A host computer can, with respect to a T2N,
upload or download user programs, issue control commands, or read and write register data using
the T series computer link protocol.
When a T2N and a host computer communicate over an Ethernet Port using the computer link
protocol, they use UDP/IP as the transmission protocol.
When a host computer transmits to a T2N using computer link protocol, the host computer's UDP
socket is used. (Socket refers to the combination of an IP address and a port number.) The host
computer sends commands and data from its own UDP socket to the Ethernet Port message
transmission UDP socket.
When the T2N uses computer link protocol transmission, it simply performs the:
·
·
Parameter setup (IP address and the UDP port number for message transmission) and
Operating mode control (message transmission permission)
that were described in an earlier chapter. There is no need to create any special user programs on
the T2N.
See the T Series Computer Link Operation Manual (UM-TS03***-E008) for details on the
functions, specifications, and usage of T series computer link protocol transmission.
Usage Recommendations
1. Since UDP/IP does not provide control functions to guaranteed communication reliability, higher
level protocols (such as retry) are required.
2. No processing is performed if a computer link protocol transmission message is received at any
point other than a message transmission UDP socket.
¾ 50 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5.2 Sample Computer Link Protocol Program
This section presents a sample program that runs on the host computer (a personal computer or
workstation) and that uses computer link protocol transmission.
This program issues a read/write request for 32 words from the start of the T2N D registers.
Operating environment
·
·
Hardware: Toshiba J-3100PV
3Com Etherlink III (3C509/B)
PC-NFS Pro 1.1.1.0
Microsoft VisualC++ 1.0
Software:
Transfer parameters
·
·
·
·
Local IP address:
133. 113. 98. 200
3001
Local UDP port number:
Remote IP address:
133. 113. 98. 10
Remote UDP port number: 3001
/**********************************************************************/
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
SAMPLE.H
Write and read requests can be issued to other T2N units
by modifying this definition file.
(C) Copyright TOSHIBA Corporation 1995
All Rights Reserved
/**********************************************************************/
/*---------------------------*/
/* Definition declarations
/*---------------------------*/
#define MY_PORT 3001
#define DST_PORT 3001
*/
/* Local port number
/* Remote port number
/* Remote IP address
*/
*/
*/
#define DST_IP
#define LOOP
"133.113.98.10"
10
32
/* Data transmission execution count */
/* Data length */
#define DATASIZ
/* Computer link function = word units */
/* RECVFROM timeout time */
#define RECVTOUT 30
#define REG_TYPE "D"
/* Register type
*/
#define REG_ADR
"0000"
/* Register start address */
¾ 51 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
/**********************************************************************/
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
/*
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
*/
Sample program implementing register read and write processing
using the computer link protocol.
This program is a sample program designed to verify the T2N
Ethernet port computer link function.
This program issues read and write requests to the specified
T2N registers.
Also note that registers in other ports can be accessed by
modifying the SAMPLE.H definition file.
(C) Copyright TOSHIBA Corporation 1995
All Rights Reserved
/**********************************************************************/
/*---------------------------*/
/* Include declarations
*/
/*---------------------------*/
#define WIN31
/* This is a Windows 3.1 application. */
/* The COMM API is required. */
#define USECOMM
#include <string.h>
#include <stdio.h>
#include <stdlib.h>
#include <string.h>
#include <memory.h>
#include <sys¥types.h>
#include <fcntl.h>
#include <errno.h>
#include <sys¥socket.h>
#include <sys¥timeb.h>
#include <time.h>
#include <sys¥in.h>
#include <sys¥netdb.h>
#include "sample.h"
¾ 52 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
/*---------------------------*/
/* Prototype declarations */
/*---------------------------*/
int cl_send( int );
/* Register read/write processing */
void main()
{
int
int
int
ists;
/* Return status
/* Socket identifier */
/* Loop counter */
*/
isdp ;
i
;
struct sockaddr_in
Soc;
WORD wVersionRequested = (0,1);
WSADATA WsaDtata ;
/* WINSOC version number specification */
/* WINSOC data structure
/* initialization
*/
*/
*/
ists = 0 ;
/* Initial value setting
/* Windows socket initialization */
ists = WSAStartup( wVersionRequested, &WsaDtata ) ;
if( ists == 0 ){
/* If normal return:
*/
isdp = socket(AF_INET, SOCK_DGRAM, 0);
if( isdp != INVALID_SOCKET ){
Soc.sin_family = AF_INET;
Soc.sin_addr.s_addr = 0 ;
/* Create socket (UDP) */
/* If normal return:
*/
/* Set local IP address.
*/
Soc.sin_port = htons( MY_PORT ); /* Set local port number. */
/* Execute bind processing. */
ists = bind(isdp, (struct sockaddr *)&Soc, sizeof(Soc) );
if( ists != SOCKET_ERROR ){
for( i = 0; i < LOOP; i++){
/* If bind completed normally: */
/* Loop for the specified number
of times. */
ists = cl_send( isdp );
if( ists != 0 )
/* Register read/write processing
/* If an error occurred in
*/
register read/write processing: */
break ;
/* Terminate processing.
*/
*/
}
}
closesocket( isdp ) ;
/* Socket close processing
}
}
WSACleanup() ;
}
/* Report WINSOC termination. */
¾ 53 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
/* SLW */
/**********************************************************************/
/*
/*
/*
*/
*/
*/
cl_send - Register read/write processing
/**********************************************************************/
/*
/*
/*
/*
/*
*/
*/
*/
*/
*/
*/
*/
*/
*/
Calling sequence
cl_send();
/* Arguments: Isdp
/*
: int
: int
I
O
: socket identifier
: return status
/*
/*
ists
/**********************************************************************/
int cl_send( int Isdp )
{
int
int
int
int
int
int
int
j, k
ists = 0 ;
iret
;
/* Loop counter
/* Return status
/* Return status
*/
*/
*/
;
ircvsiz ;
isndsiz ;
/* Reception data length */
/* Data length
*/
*/
*/
*/
*/
*/
icunt
idat
;
;
/* Data setup index
/* Temporary
char csnd[ 1000 ] ;
char crcv[ 1000 ] ;
fd_set ibits;
/* Data send buffer
/* Data receive buffer
/* SELECT() bit mask
struct timeval timeout;
/* SELECT() timer value */
struct sockaddr_in
Snd, Rcv;
iret = -1 ;
memset( &Snd, 0x00, sizeof( Snd ) );
memset( &Rcv, 0x00, sizeof( Rcv ) );
memset( csnd, 0x00, sizeof( csnd ) );
/* Clear the send data buffer.
*/
*/
*/
*/
*/
memset( crcv, 0x00, sizeof( crcv ) );
/* Clear the receive data buffer.
/* Set up the register write send data.
sprintf( &csnd[ 0 ], "(A01DW" ) ; /* Set up the register write command.
/* Set the starting register number.
sprintf( &csnd[ strlen(csnd)], "%s", REG_TYPE );
sprintf( &csnd[ strlen(csnd) ], "%04s", REG_ADR );
sprintf( &csnd[ strlen( csnd) ], "," ) ;
idat = DATASIZ ;
/* Set the data count. */
¾ 54 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
sprintf( &csnd[ strlen( csnd ) ], "%02d", idat ) ;
sprintf( &csnd[ strlen( csnd) ], "," ) ;
icunt = 0 ;
/* Comparison data storage index. */
for( j = 0, k = 0; k < DATASIZ; k++ ){ /* Set register write data. */
sprintf( &csnd[ strlen( csnd) ], "%04X", k ) ;
j = j + 4 ;
sprintf( &csnd[ strlen( csnd) ], "," ) ;
j = j + 1 ;
icunt = icunt + 4 ;
}
sprintf( &csnd[ (strlen( csnd )) - 1], ")¥r" ) ;
isndsiz = strlen( csnd );
Snd.sin_family = AF_INET;
/* Set the send data length.
*/
Snd.sin_addr.s_addr = inet_addr( DST_IP ); /* Set the remote IP address.
*/
*/
*/
Snd.sin_port = htons( DST_PORT );
/* Set the remote port number.
/* Send a register write request.
ists = sendto( Isdp, csnd, isndsiz, 0,
(struct sockaddr *)&Snd,sizeof( Snd ) );
if ( ists == isndsiz ){ /* If the send length was OK. */
/* Set the SELECT argument.
*/
memset(&ibits,0x00,sizeof(fd_set));
/* Set the BIT initial value. */
timeout.tv_sec = RECVTOUT;
FD_SET(Isdp,&ibits);
/* Set the timeout time. */
/* BIT setup */
ists = select( 1, &ibits,0,0,(struct timeval *)&timeout);
if(ists > 0){ /* If normal return: */
/* Register write response reception */
ists = recvfrom( Isdp, crcv, sizeof( crcv ), 0
,(struct sockaddr *)&Rcv, &ircvsiz) ;
if ( ists > 5 ){
if( crcv[ 4 ] == 'C' && crcv[ 5 ] == 'E' ||
crcv[ 4 ] == 'E' && crcv[ 5 ] == 'E' ){
return( -1 ) ;
/* Register write response error */
}
/* Register read request creation */
memset( csnd, 0x00, sizeof( csnd ) ) ;
memset( crcv, 0x00, sizeof( crcv ) ) ;
sprintf( &csnd[ 0 ] , "(A01DR" );/* Register read command setup
*/
*/
/* Set up the starting reg. no.
sprintf( &csnd[ strlen(csnd)], "%s", REG_TYPE );
sprintf( &csnd[ strlen(csnd) ], "%04s", REG_ADR );
sprintf( &csnd[ strlen( csnd) ], "," ) ;
¾ 55 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
/* Set the data count.
*/
idat = DATASIZ ;
/* Register read data length. */
sprintf( &csnd[ strlen( csnd ) ], "%02d", idat ) ;
sprintf( &csnd[ strlen( csnd )], ")¥r" ) ;
isndsiz = strlen(csnd) ;/* Set up the data transmission length.
*/
*/
/* Send the register read command.
ists = sendto( Isdp, csnd, isndsiz, 0,
(struct sockaddr *)&Snd,sizeof( Snd ) );
if( ists == isndsiz ){
/* Set the BIT initial value. */
memset(&ibits,0x00,sizeof(fd_set));
timeout.tv_sec = RECVTOUT;
/* Set the timeout time. */
/* BIT setup */
FD_SET(Isdp,&ibits);
ists = select( 1, &ibits,0,0,
(struct timeval *)&timeout);
if(ists <= 0){ /* If timeout and error: */
return( -1 ) ; /* recvfrom timed out. */
}
/* Register read response reception
*/
*/
ists = recvfrom( Isdp, crcv, sizeof( crcv ), 0
,(struct sockaddr *)&Rcv, &ircvsiz) ;
if ( ists > 5 ){
if( crcv[ 6 ] == 'C' && crcv[ 7 ] == 'E' ){
iret = -1 ;
/* Register read response error
}
else{
iret = 0 ;
/* Register read response was normal. */
}
}
}
}
}
}
return( iret ) ;
}
¾ 56 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5.3 PC Link Protocol Transmission (Data write)
The T series PC link protocol allows one T2N on a network to write register data to another T2N
or T3H.
As is the case with the computer link protocol, the PC link protocol uses UDP/IP as its
transmission protocol.
The PC link main port uses a UDP socket for message transmission and transmits to the slave
Ethernet Port message transmission UDP socket. The user program that runs on the T2N of the
main port is discussed later.
When this function is used on the PC link slave port, the T2N simply performs the:
·
·
Parameter setup and
Operating mode control (message transmission permission)
that were described in an earlier chapter. There is no need to create any special user programs on
the T2N.
Usage Recommendations
1. Since UDP/IP does not provide control functions to guarantee communication reliability, higher level
protocols (such as retry) are required.
2. No processing is performed if a PC link protocol transmission message is received at any point
other than a message transmission UDP socket.
Register write request (using the SEND instruction)
a. Function
The register data specified by the local port (T2N) is written to the specified register on the remote
port (T2N or T3H).
b. Transfer parameters
A
3100H
CMD = 0021H
WordSize
SRID
Module designation
A+1
A+2
A+3
A+4
A+5
A+6
A+7
A+8
A+9
A+10
Command number
(1) Transfer register data length: 1 to 485 words
(2) Local port register type code
(3) Local port register number
(4) Remote port register type code
(5) Remote port register number
(6) Timer count
SRegNO
DRID
DRegNO
Timecnt
D-IPAddress
Remote port IP address (The input format is the
same as that for parameter setup requests.)
D-UDP PortNO
Remote port message transmission UDP port
number
(1) Transferred register data length
Specifies the transmission data length in word units. (1 to 485 words)
¾ 57 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
For the T/C registers, the data length will be between 1 and 323 words.
(2) Local port register type code
This code indicates the type of register in which the local port transmission source data is
stored. See figure 5.1 for the codes that can be specified.
(3) Local port register number
Specifies the starting number of the register specified by the local port register type code.
(4) Remote port register type code
This code specifies the type of the register at the remote port to which the transmitted data will
be written. See figure 5.1 for the codes that can be specified.
(5) Remote port register number
Specifies the starting number of the register specified by the remote port register type code.
(6) Timer count
Specifies a time used to limit the response time from the remote port in 0.1 second units.
F
E
0
A+10
0: Use the user-specified value (0.1 to 3276.7 seconds)
1: Use the default value of 30 seconds.
Figure 5.1 indicates the register type code that the local or remote port can specify the code. See
“T-series Instruction Set (Ladder, SFC)” (UM-TS03***-E004).
RID
Meaning
RID
Meaning
*1
*2
*3
*3
0000H
0001H
0002H
0003H
0004H
XW/YW registers
W register
F register (0 - 8191)
F register (0 - 65535)
T register
**05H
**06H
0007H
0008H
0009H
LW register
RW register
D register
C register
SW register
Figure 5.1 Register Type Code
*1 Includes the expansion F registers. One bank has 8k words (0 to 8191).
F
7
0
05H
Bank number ...00H: T2N internal registers
F0000 to F1023
01H to 03H: Expansion F registers
F0000 to F8191
¾ 58 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
*2 Includes the expansion F registers(Only T3H). One bank has 64K words (0 to 65535).
F
7
0
06
Bank number ...00H: T3H internal registers
F0000 to F32767
01H: Expansion F registers (IC card)
F0000 to F65535
02H: Expansion F registers (IC card)
F0000 to F57343
*3 The T and C registers hold data that has flags attached.
Supplement:
The transfer data length has a maximum of 323 words when data is transferred over the
Ethernet.
For the T registers, it is not possible to specify a range that spans both the basic T
registers (0 to 511) and the expansion T registers (512 to 999). The T3H has the expansion
T register, but the T2N does not have.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
The write operation is not synchronized with the remote port T2N/T3H scan operation.
If synchronization is necessary, applications must perform synchronization processing, such as
transferring the data to a separate registers at the start of the T2N scan.
·
·
The command number (0021H) is the same as the "Data Read".
A transfer word count error (TermSTS = 09H) occurs if the transferred register data length
exceeds the range 1 to 485 words (or 1 to 323 words for the T and C registers).
·
·
A register specification error (TermSTS = 01H) occurs if a value other than a stipulated value
is specified for the register type codes (SRID/DRID).
A register specification error (TermSTS = 01H) occurs if 0007H (the T register) is specified
for the local port register type code and a register other than the T register is specified for the
remote port register type code. This also holds for the C register.
·
·
A boundary error (TermSTS = 0AH) occurs if a range spanning both the base T registers (0 to
511) and the expansion T registers (512 to 999) is specified for the T register.
For data storage registers, a boundary error occurs if the specified area (start register + register
range) does not exist in either the local or remote ports.
Local port: TermSTS = 0AH, remote port: TermSTS = 8AH
·
A response timeout error (TermSTS = 02H) occurs if the response time from the remote port
exceeds the time specified by the timer counter value.
¾ 59 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
·
Write protection can be specified for each register type on the local T2N by using the special
coil settings described below. In this case, a memory write protect error (TermSTS = 04H) will
occur.
F
9
8
7
6
5
4
3
2
1
0
0: Write enabled
1: Write protected
SW067
SW C
T
F
D
RW LW W XW/YW
Special registers
Counter registers
Timer registers
Input/output registers
Link registers
Link relay registers
Auxiliary registers
Data registers
PC internal file registers
Expansion file registers (IC card)
·
When PC link transmission or the UDP socket interface is used, if an application
transmits to a nonexistent remote port, an transmission error (TermSTS = 0BH, detailed
information = 0020H) occurs.
¾ 60 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5.4 PC Link Protocol Transmission (Data read)
The T series PC link protocol allows a T2N on the network to read register data from another T2N
or T3H port's registers into its own registers.
As is the case with the computer link protocol, the PC link protocol uses UDP/IP as its
transmission protocol.
The PC link main port uses a UDP socket for message transmission and transmits to the slave
Ethernet Port message transmission UDP socket. The user program that runs on the main port is
discussed later.
When this function is used on the PC link slave port, the T2N simply performs the:
·
·
Parameter setup and
Operating mode control (message transmission permission)
that were described in an earlier chapter. There is no need to create any special user programs on
the T2N.
Usage Recommendations
1. Since UDP/IP does not provide control functions to guarantee communication reliability, higher level
protocols (such as retry) are required.
2. No processing is performed if a PC link protocol transmission message is received at any point
other than a message transmission UDP socket.
Register read request (using the RECV instruction)
a. Function
The register data specified by the remote port (T2N/T3H) is read to the specified register on the
local port (T2N).
b. Transfer parameters
A
3100H
CMD = 0021H
WordSize
SRID
Module designation
A+1
A+2
A+3
A+4
A+5
A+6
A+7
A+8
A+9
A+10
Command number
(1) Transfer register data length: 1 to 485 words
(2) Local port register type code
(3) Local port register number
(4) Remote port register type code
(5) Remote port register number
(6) Timer count
SRegNO
DRID
DRegNO
Timecnt
D-IPAddress
Remote port IP address (The input format is the same as that
for parameter setup requests.)
D-UDP PortNO
Remote port message transmission UDP port number
¾ 61 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(1) Transferred register data length
Specifies the transmission data length in word units. (1 to 485 words)
For the T/C registers, the data length will be between 1 and 323 words.
(2) Local port register type code
This code specifies the type of the local port register into which the data read out will be
stored. See table 5.1 for the codes that can be specified here.
(3) Local port register number
Specifies the starting number of the register specified by the local port register type code.
(4) Remote port register type code
This code specifies the type of the remote port register that holds the transmission source data.
See table 5.1 for the codes that can be specified.
(5) Remote port register number
Specifies the starting number of the register specified by the remote port register type code.
(6) Timer count
Specifies a time used to limit the response time from the remote port in 0.1 second units.
F
E
0
A+10
0: Use the user-specified value (0.1 to 3276.7 seconds)
1: Use the default value of 30 seconds.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
The read operation is not synchronized with the remote port T2N/T3H scan operation.
If synchronization is necessary, applications must perform synchronization processing, such as
transferring the data to a separate registers at the start of the T2N scan.
·
·
The command number (0021H) is the same as the "Data Write".
A transfer word count error (TermSTS = 09H) occurs if the transferred register data length
exceeds the range 1 to 485 words (or 1 to 323 words for the T and C registers).
·
·
A register specification error (TermSTS = 01H) occurs if a value other than a stipulated value
is specified for the register type codes (SRID/DRID).
A register specification error (TermSTS = 01H) occurs if 0007H (the T register) is specified
for the local port register type code and a register other than the T register is specified for the
remote port register type code. This also holds for the C register.
·
A boundary error (TermSTS = 0AH) occurs if a range spanning both the base T registers (0 to
511) and the expansion T registers (512 to 999) is specified for the T register.
¾ 62 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
·
For data storage registers, a boundary error occurs if the specified area (start register + register
range) does not exist in either the local or remote ports.
Local port: TermSTS = 0AH, remote port: TermSTS = 8AH
·
·
A response timeout error (TermSTS = 02H) occurs if the response time from the remote port
exceeds the time specified by the timer counter value.
Read protection can be specified for each register type on the local T2N by using the special
coil settings described below. In this case, a memory write protect error (TermSTS = 04H) will
occur.
F
9
8
7
6
5
4
3
2
1
0
0: Write enabled
1: Write protected
SW067
SW C
T
F
D
RW LW W XW/YW
Special registers
Counter registers
Timer registers
Input/output registers
Link registers
Link relay registers
Auxiliary registers
Data registers
PC internal file registers
Expansion file registers (IC card)
·
When PC link transmission or the UDP socket interface is used, if an application
transmits to a nonexistent remote port, an transmission error (TermSTS = 0BH, detailed
information = 0020H) occurs.
¾ 63 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5.5 Sample PC Link Protocol Transmission Program
This section presents a sample program that uses PC link protocol transmission.
This program creates increment data within the local port and writes it to the remote port's
registers. Next it reads out the same area and compares it with the data within the local port to
check that the function succeeded.
This program assumes that the parameter setup request and the operating mode control request
(message transmission permission) have already completed.
Local port IP address:
133. 113. 98. 10 (85H. 71H. 62H 0AH)
Local port message transmission UDP port number:
RW090: Execution count specification (1 to 32767)
2000
RW091: Operation when a comparison error occurs (continue: 0, stop: 1)
RW092: Transfer register data length (1 to 485 words)
RW093: Write time transfer source register type
RW094: Write time transfer source register start number
RW095: Write time transfer destination register type/read time readout source register type
RW096: Write time transfer destination register start number/read time readout source
register start number
RW097: Read time storage register type
RW098: Read time storage register start number
W0991, W0990:
Remote destination IP address
133. 113. 98. 20 (85H. 71H. 62H. 14H)
W0992: Remote destination message transmission UDP port number .......... 1025
This ladder program is executed by turn on the R0520 A contact.
¾ 64 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
|
|
|R0520
R0090 |
1|-| |------------------------------------------------------------( )--|
|
|
|
|
|/* PC link preparation */
|R0520
2|-| |---|^|-+[ 01000 MOV RW090][ 00000 MOV RW091][ 00400 MOV RW092]---|
/* Number of executions, Operation on error
|occurrence, Transfer data length */
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
+[ 00004 MOV RW093][ 01000 MOV RW094]---------------------|
|
|
/* Transmission source register type, start number */
|
+[ 00004 MOV RW095][ 02000 MOV RW096]---------------------|
|
|
/* Transfer destination register type, start number */
|
+[ 00004 MOV RW097][ 03000 MOV RW098]---------------------|
|
|
/* Storage register type, start number */
|
+[ 0341995909 DMOV W0991· W0990][ 01025 MOV W0992]---------|
/* Remote destination IP address, message transmission
|UDP port number */
|
|
|
|
|/* Data preparation */
|R0090 R009F
3|-| |-+-|/|-+-|^|-+[00001 MOV W0901][00900 MOV W0902][00000 MOV W0918]|
|
|
|
|
|
|
|
|R0091|
|
|-| |-+
|
+[W0946 MOV W0900][RW093 MOV W0916][RW094 MOV W0917]|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|R0098
R0098 |
+-|/|--[W0901 XFER W0901 -> W0916]-----+[ +1 W0917]--( )--|
|
|
|
|
|
|
|
|
|
|
|
|
+[ +1 W0918]------|
|
|
|
|
+[ +1 W0900]------|
|
|
+[RW092 = W0918][ SET R0092][ RST R0091][ RST R0520]------|
|
¾ 65 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
|/* Register write */
|R0092
|
|
4|-| |-+[12544 MOV W0903][00033 MOV W0904]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| /* Designates the module and sets the CMD number. */
|
|
+[RW092 MOV W0905]--------------------------------------------|
| /* Sets the transfer register data length.
|
*/
|
+[RW093 MOV W0906][RW094 MOV W0907]----------------------------|
| /* Sets the transmission source register type, start number. */
|
|
+[RW095 MOV W0908][RW096 MOV W0909]----------------------------|
| /* Sets the transfer destination register type, start number. */
|
|
+[00100 MOV W0910]---------------------------------------------|
| /* Sets the response time limit (10 seconds). */
|
|
+[W0991· W0990 DMOV W0912· W0911][W0992 MOV W0913]----------------|
| /* Remote destination IP address, message transmission UDP port
|number */
|
|
|
|
|
|
+[W0903 SEND W0914][SET R0093][RST R0092]----------------------|
/* Sets the request, and starts post-completion readout. */
|
|/* Register readout */
|R0093
|
|
5|-| |-+[12544 MOV W0920][00033 MOV W0921]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| /* Designates the module and sets the CMD number.
|
*/
|
+[RW092 MOV W0922]---------------------------------------------|
| /* Sets the transfer register data length.
|
*/
|
+[RW097 MOV W0923][RW098 MOV W0924]----------------------------|
| /* Sets the storage register type, start number. */
|
|
+[RW095 MOV W0925][RW096 MOV W0926]----------------------------|
| /* Sets the transfer destination register type, start number. */
|
|
+[00100 MOV W0927]---------------------------------------------|
| /* Sets the response time limit (10 seconds).
|
*/
|
+[W0991· W0990 DMOV W0929· W0928][W0992 MOV W0930]----------------|
| /* Remote destination IP address, message transmission UDP port
|number */
|
|
|
|
|
+[W0920 RECV W0931][SET R0094][RST R0093]----------------------|
/* Sets the request, and starts post-completion comparison. */
¾ 66 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
|/* Comparison check */
|R0094
|
|
6|-| |-+[00001 MOV W0940]------+[00001 MOV W0941][00980 MOV W0942]-------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
+[00001 MOV W0943][00981 MOV W0944]-------|
|
|
+-|^|--[RW094· RW093 DMOV W0948· W0947][RW098· RW097 DMOV W0950· W0949]|
|
|
|
|R0095
+-|/|---|^|-+[W0947 XFER W0940 -> W0941]--------------------------|
|
|
|
|
|
R0096 |
|
+[W0949 XFER W0940 -> W0943]---------------------( )--|
|
|
|
|R0096
+-| |-+[W0980 = W0981][ +1 RW190]---------------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
R0910
+[W0980 <> W0981][ +1 RW191]--| |---[ SET R0099][ RST R0094]|
|
|
|
R0095 |
+-|^|--[ +1 W0945][ +1 W0948][ +1 W0950]---------------( )--|
|
|
|
R0097 |
+[RW092 = W0945][ 00000 MOV W0945][ +1 W0946]----------( )--|
|
|R0097 R0099
|
+-| |---|/|-+[RW090 > W0946][SET R0091]-----------+[ RST R0094]---|
|
|
|
|
|
|
|
|
+[RW090 = W0946][00000 MOV W0946]-----+
¾ 67 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6. Socket Interface Communication
CAUTION
1. Chapter 6 presents information related to using the functions provided by the Ethernet Port from a
T2N, including the instruction (request) format, important items that require attention, and sample
programs. That chapter also presents items considered necessary when using the Ethernet Port.
Make a point of understanding the content of chapter 4 thoroughly before writing programs that use
the Ethernet Port. The sample programs present basic examples of Ethernet Port usage, and should
be reviewed carefully before use in an actual system.
This chapter describes the functions and positioning of the socket interface, and the differences
between the UDP socket interface and the TCP socket interface. Next, this chapter presents notes
on using the Ethernet Port socket interface and describes the procedures for using this
functionality.
6.1 Overview
This section describes the functions and positioning of the socket interface, and the differences
between the UDP socket interface and the TCP socket interface.
1. Positioning and functionality
The socket interface is a programming interface that allows user programs to use the TCP/IP and
UDP/IP functions. Socket interface communication is a communication technique that has become
standard on engineering workstations (EWS) and other networked computer systems.
The socket interface can be used for communication between host application programs and user
programs running on the T2N.
The Ethernet Port socket interface provides eight sockets, and the communication protocol (TCP/IP
or UDP/IP) used with the remote destination can be specified for each socket. User programs on
the T2N use the SEND and RECV instructions to use the socket interface.
TCP/IP (Transmission Control Protocol/Internet Protocol)
UDP/IP (User Datagram Protocol/Internet Protocol)
Figure 6.1 shows the positioning of the socket interface.
EWS
T2N
Application program
T2N user program
System
calls
SEND and RECV
instructions
OS (UNIX)
T2N firmware
Socket interface
UDP/TCP
IP
Socket interface
UDP/TCP
IP
CSMA/CD
CSMA/CD
Data
communication
TCP or UDP
Figure 6.1 Positioning of the Socket Interface
¾ 68 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2. Differences between the UDP socket interface and the TCP socket interface
a. UDP socket interface (See figure 6.2.)
·
·
·
·
Provides an in/out port (socket) for data communication between a transmission source port
and a transmission destination port.
Data for the transmission source and transmission destination (IP addresses and port numbers)
is specified in the send/receive data.
Since the transmission source and transmission destination are specified in each data item, a
UDP socket can communicate with multiple remote UDP sockets.
The UDP socket interface provides no control functionality such as reception verification using,
e.g. ACK (acknowledge) responses, or retransmission processing to assure transmission
reliability. Therefore, reliability must be assured by higher level protocols implemented by user
programs.
Transmission source port
UDP socket
Transmission destination port
UDP socket
Transmission data
Reception verification (only if
implemented by user programs)
Figure 6.2 UDP Sockets
¾ 69 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. TCP socket interface (See figures 6.3 and 6.4.)
·
In TCP communication, a pipe-like virtual communications line (connection) is established
between sockets on two ports that are communicating (sending and receiving), and since the
protocol handles control of reception verification and retransmission processing, it provides a
highly reliable communication.
·
There are two methods for establishing a connection: passive open and active open. In passive
open, the local socket is put into a state in which it is waiting for a request to establish a
connection from another port. In active open, a request is issued for the establishment of a
connection with a socket in the passive open state.
·
·
When establishing a connection between two ports, one port must first open a socket in passive
open mode, and the other port must perform an active open on a local socket with respect to a
remote socket that is in the passive open state.
Since the passive open socket port "provides" data transmission and other services, it is called
the "server."
·
·
Since the active open socket port "requests" services, it is called the "client."
A socket for which a connection has been established is unable to transfer data with any other
sockets unless that connection is first released.
·
Since sockets are connected by connections, there is no need to specify the transmission source
or transmission destination with every data item transmitted.
Transmission source port
TCP socket
Transmission destination port
TCP socket
Connection
Transmission data
Client side
Active open
Server side
Passive open
Reception verification
Figure 6.3 TCP Socket (Connection)
¾ 70 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Client side
Server side
(Active open)
(Passive open)
Closed state
Closed state
Passive open
Connection establishment request
Active open
Connection established
Connection established
Data transmission
Acknowledge response (ACK)
Next data transmission
Data transmission
Data reception
Next data transmission
Data transmission
Acknowledge response (ACK)
Data transmission
Data transmission
Data reception
Data reception
Next data transmission
Next data transmission
Acknowledge response (ACK)
Data transmission
Close request
Close request
Close request
Closed state
Close request
Closed state
Figure 6.4 TCP Connection Communication Procedure (Overview)
¾ 71 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6.2 Ethernet Port Socket Interface Usage Notes
This section presents points that require attention when using the socket interface on the Ethernet
Port for data transmission.
1. Data handling and data segmentation in UDP socket interface transmission and reception
a. In UDP socket interface transmission, data sent in a single transmission is handled by the
receiving Ethernet Port as a single data unit, and that data is transmitted to the T2N in a batch
operation by a receive request.
b. The size of data units that can be handled by the Ethernet Port socket interface in a single
operation is limited to a maximum of 2000 bytes. If the sending port sends a data unit larger
than 2000 bytes, the Ethernet Port UDP socket interface will not be able to receive that data.
Users should determine the maximum size of the data units to be sent or received at the
system design stage.
c. Transmitted data that exceeds 1472 bytes is divided (fragmented) into units of 1472 bytes.
This is the limit of the length of packets (data units flowing on the network) transmitted over
the network (10BASE-T). (See figure 6.8.)
For example, when transmitting a 2000 byte data set, which is the largest data size that can be
handled by the Ethernet Port, the phenomenon shown in figure 6.5 can occur.
(1) The sending T2N user program requests a transmission of 2000 bytes.
(2) The transmitted data is divided into two fragments, A (with 1472 bytes) and B (with 528
bytes) by the send side Ethernet Port.
(3) A and B are put onto the network in order.
(4) The receive side Ethernet Port connects the received data A and B, recovering the
original data.
(5) The data is accepted by a receive request from the receive side T2N for 2000 bytes of
data and the data is stored in the specified register. (See section 6.4 (3).)
d. In the UDP socket interface, after the transmitted data is reassembled to the original data it is
passed to the user program and stored in the specified register.
(The fragments A and B are reassembled to the original data by UDP/IP processing.)
Send side T2N
Ethernet Port
Network
Ethernet Port
Receive side T2N
¬ Send request
•
®
2000 bytes
1472 bytes
° Receive request
2000 bytes
¯
A
B
A
B
528 bytes
Receive response
Figure 6.5 Transmission Data Fragmentation in the UDP Socket Interface
¾ 72 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. The T2N receives the data which specifies the size of reception data in the transfer parameter
from the Ethernet Port.
f. Allocate an area one word larger than the transmitted data size as the T2N register
area that will hold the received data. As the result of a receive request, information
indicating the size of the transmitted data for the single operation plus the data transmitted in
the single operation will be stored in that area.
g. In receive request programs from the T2N, set the size of reception data to a value
equal to or larger than that of the maximum size for the transmission data in a single
operation. If the size of reception data is smaller than the transmitted size of transfer data to
socket, the data that exceed the specified size of reception data is canceled.
¾ 73 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2. Data handling and data segmentation in TCP socket interface transmission and reception
a. When using the TCP socket interface for data transmission, the data transmitted in a single
operation is handled by the receive side Ethernet Port as one section of a continuous data
stream that comes from the sender. (See figure 6.6.)
In this technique, the data is not handled as a single unit, as it is in UDP socket interface
transmission.
b. The amount of data transmitted to the T2N from the TCP socket interface due to a T2N
receive request will vary depending on both the timing with which the T2N issues the receive
request, and the timing with which the data arrives at the TCP socket interface.
c. In the Ethernet Port TCP socket interface, up to 4380 bytes of received data can be stored per
socket. Also note that up to 2000 bytes of data can be transferred to the T2N for a single
receive request from the T2N. For example, if the remote port sends 800 bytes at a time, then
the amount of received data per socket may be either 800, 1600, 2400, 3200, or 4000 bytes. If
the amount of received data is 800 or 1600 bytes, those 800 or 1600 bytes can be acquired by
the T2N by a receive request from the T2N. In cases where the amount of received data is
2400, 3200, or 4000 bytes, 2000 bytes will be transferred by the first receive request from the
T2N, and the remaining 400, 1200, or 2000 bytes can be transferred by issuing another
receive request from the T2N.
d. Therefore, to handle one unit of transmitted data as a single unit of data on the receiving side
as well, at the system design stage users must analyze both the data format (head/tail
delimiting codes, data sequencing) and the amount of data to be transmitted, and provide
routines to decode the transmitted data in the receiving T2N user software.
e. Allocate an area one word larger than the transmitted data size as the T2N register
area that will hold the received data. As the result of a receive request, information
indicating the size of the transmitted data for the single operation plus the data transmitted in
the single operation will be stored in that area.
Ethernet Port TCP socket interface
Consecutive data (up to 4380 bytes)
T2N
Receive request
Data received up to this
time
Max: 2000 bytes
Data received by
the T2N
Transmitted data
Receive response
Transferred data
Figure 6.6 Handling of Transmitted Data in the TCP Socket Interface
¾ 74 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
f. When the TCP socket interface is used, transmitted data is divided (fragmented) into units of a
size determined when the connection between the two sockets was established. The upper
limit of the fragment size is 1460 bytes. This is the limit of the length of packets (data units
flowing on the network) transmitted over the network. (See figure 6.8.)
For example, when transmitting a 2000 byte data set, which is the largest data size that can be
handled by the Ethernet Port, the phenomenon shown in figure 6.7 can occur. The largest
segment size that can be received in this case is 1460 bytes.
¬
•
The sending T2N user program requests a transmission of 2000 bytes.
The transmitted data is divided into two units called segments, A (with 1460 bytes) and
B (with 540 bytes) by the send side Ethernet Port.
®
¯
A and B are put onto the network in order.
The data that arrived at the receive side Ethernet Port is acquired by a receive request for
2000 bytes from the T2N, and stored in the user specified register area. (See section 6.3
(7).)
The amount of data that can be acquired by a TCP receive request differs depending on
the timing with which the T2N issues the receive request and the timing with which the
data arrives at the Ethernet Port.
·
If data has not yet arrived at the receive side Ethernet Port when the receive request is
issued:
®
When segment A arrives at the Ethernet Port, only segment A will be passed to
the requester.
·
·
If only segment A has arrived at the receive side Ethernet Port when the receive
request is issued:
®
Only segment A will be passed to the requester.
If segments A and B have arrived at the receive side Ethernet Port when the receive
request is issued:
®
A data item consisting of A and B will be passed to the requester.
°
If B was not received, another receive request can be issued from the T2N to acquire B.
¾ 75 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Ethernet Port
Send side T2N
Ethernet Port
Send side T2N
Network
¯First receive
request
2000 bytes
ÀSend request
2000 bytes
Á
Â
1460 bytes
A
1460 bytes
A
A
1460 bytes
B
°Second receive
request
B
540 bytes
2000 bytes
540 bytes
B
540 bytes
Figure 6.7 Transmission Data Fragmentation in the TCP Socket Interface
g. When the transmission data is fragmented as discussed above, the amount of data transferred
to the T2N in a TCP socket interface receive request differs depending both on the timing with
which the T2N issues the receive request and the timing with which the data arrives at the
Ethernet Port.
h. To handle single units of transmission data on the receiving side as single units as well, the
user software on the receiving side must recognize the end of the transferred data (either by
using counts in the transmitted data or by including an end marker in the transmitted data) and
iterate receive requests until all the transmitted data has been received.
i. User programs must store all incoming data so that the register area used to transfer
data to the T2N is not overwritten when using iterated receive requests.
¾ 76 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Preamble (7 bytes)
Signal used to synchronize reception
SFD (Start Frame Delimiter) (1 byte)
Remote port address (6 bytes)
Local port address (6 bytes)
Ethernet type (2 bytes)
0800H:IP, 0806H:ARP
IP header (20 bytes)
Packets
UDP header
(8 bytes)
TCP header
(20 bytes)
traveling on the
transmission
path
(72 to 1526
bytes)
UDP data field
(up to 1472 bytes)
IP datagram
(46 to 1500
bytes)
Data fields in
the packets
traveling on the
transmission
path
TCP data field
(up to 1460 bytes)
IP data field
(up to 1480
bytes)
FCS (Frame Check Sequence) (4 bytes)
32-bit CRC code for the sections of the packet
other than the preamble, the SFD, and the FCS.
(Packet error detection)
Figure 6.8 Packet Format/IP Datagram
¾ 77 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
3. Socket interface port numbers
a. Set the port numbers for local TCP and UDP sockets to values in the range 1024 to
65535. The Ethernet Port will issue an error if any other values are used. This is because the
port numbers from 1 to 1023 are allocated for UNIX workstation standard services.
b. There are cases where there are reserved ports with numbers outside the 1 to 1023 range on
specific workstations. Verify this on the workstations actually being used, and be sure that
these reserved port numbers are not duplicated on the Ethernet Port.
c. The same port number cannot be assigned to multiple sockets for TCP and UDP sockets. Be
especially careful not to duplicate UDP port numbers used for message transmission
(computer link protocol and PC link protocol transmission).
d. When TCP sockets and UDP sockets are used together in the same Ethernet Port, the same
port number cannot be used for both TCP and UDP sockets.
4. Notes that apply to both the UDP and the TCP socket interface
a. Careful attention to changes in bits in the socket status is required when using socket
interface send/receive requests.
b. When using multiple Ethernet Port functions at the same time, communication processing may
become slower, depending on the details of the user programs executing.
c. Communication efficiency may degrade if the network to which the Ethernet Port is connected
is heavily loaded.
d. Since processing a close request requires processing the send and receive requests issued to
that socket before the close request was issued, a significant amount of time may be required
to process some close requests.
e. The Ethernet Port includes a common transfer/reception buffer (of about 60k bytes) to hold
data. This common transfer/reception buffer is shared by all open sockets. In the Ethernet Port
TCP socket interface, up to 4380 bytes of received data can be stored per socket. In the case
of using all TCP sockets, this buffer of about 60k bytes do not become full. In the case of
UDP socket, the amount of reception data is no limit. So, if the T2N does not receive the
reception data in the socket, the common transfer/reception buffer may become full. In this
case, new incoming data will be discarded and the T2N can not transmit data, either (the send
request is insufficient resources error). To avoid this state, user programs should either
continuously issue receive requests and readout any data in the reception buffer, or else
monitor the socket status (See section 6.3) for the presence of reception data and perform
reception processing as required. If the insufficient resources error to not receive data occurs,
it is possible to cancel that the socket, the reception data becomes full, is closed.
f. Since Ethernet Port receive requests (both TCP and UDP) put the object socket in a wait state
waiting for data from the remote port, transmission over that socket is not possible.
If full-duplex communication with the remote port is required, set up two sockets, one for
transmission and one for reception.
g. There are a total of eight requests used for socket interface transmission. Of those, the T2N
waits internally for completion for the timeout time for five requests, namely,
·
·
UDP open, send, and close requests
TCP send and close requests
¾ 78 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
If the timeout time expires, the "transmission complete timeout (no instruction response)"
error is issued. Since this error has the same code as module failure errors, first check whether
or not the Ethernet Port has failed before attempting to recover from the error.
h. User programs specify the time limit until completion for the following three requests used in
socket interface transmission:
·
·
·
UDP receive request
TCP open request
TCP receive request
If this time limit is exceeded, a "timeout" error is issued. In particular, the Ethernet Port
reports the timeout error to the T2N.
i. The Ethernet Port uses a priority ordering in processing sockets 1 through 8. Therefore,
systems constructed so that socket 1 is activated frequently may not be able to process socket
8, resulting in "Transmission completion timeout" errors occurring. When constructing a
system, take the socket utilization conditions into account when allocating sockets.
Since the send/receive processing for each socket requires about 50 ms, applications that issue
send or receive requests to a given socket should leave an interval of at least 50 ms times the
number of sockets used between each request.
(Interval between requests to the same socket) ³ (Number of sockets used ´ 50 ms)
Similarly, the above intervals averaging 50 ms should be left between transmissions from
remote ports to the local port.
(Interval between remote port transmissions) ³ (Number of remote ports ´ 50 ms)
5. UDP socket interface notes
a. In transmission using UDP sockets, the user program must implement any processing required
to assure transmission reliability, such as verifying the reception of transmitted data and
retransmission.
b. It is possible to broadcast to all ports on the network using UDP sockets.
Send side:
Set the transmission destination address to "255.255.255.255". This is
"FF.FF.FF.FF" in hexadecimal. The "0.0.0.0" used by some UNIX
versions (in particular, 4.2 BSD) cannot be used.
Set the UDP port number for the socket to which you want to issue a
broadcast as the transmission destination object socket UDP port
number. It is convenient to prepare a dedicated socket in advance if
broadcast transmission is to be used.
Receive side: Specify "0.0.0.0" as the transmission source IP address.
Specify the UDP port number for the broadcast transmitting socket as the
transmission source UDP port number.
c. Data transmission between sockets on the same port is not supported by UDP.
d. When PC link transmission or the UDP socket interface is used, if an application
transmits to a nonexistent remote port, an transmission error (TermSTS = 0BH, detailed
information = 0020H) occurs.
¾ 79 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6. TCP socket interface notes
a. When a passive open is executed, the specified socket is put in the active open wait state. If
the remote IP address (DIPAddress) and the remote port object socket TCP port number
(DTCP_PORTNO) values are set to 0, the socket will be able to handle active opens from any
remote port.
b. A connection is established by an active open from another socket applied to a socket in the
passive open state. A connection cannot be established by a passive open from another socket
applied to a socket in the passive open state. Similarly, a connection cannot be established by
an active open from another socket applied to a socket in the active open state. That is, the
roles of two sockets for which a connection is to be established must be determined in
advance.
c. For a socket in the passive open state, it is not possible to open multiple connections from
other ports by issuing multiple active opens.
d. Connections cannot be established between sockets on the same port.
e. If transmission is impossible due to network congestion or other reason when a send request is
executed, the send request is stored internally in the Ethernet Port so that it can be sent later.
The number of items that can be stored is three per socket. If the Ethernet Port cannot store
the request, is returns an error.
f. If a close request is issued first for a connection that is being established, then it will be
possible to execute the next open request for the object sockets at the point when the close
request processing completes normally. On engineering workstation and personal computer
systems, TCP sockets on the port that performed the close processing for the open connection
cannot be opened again for a fixed period, usually about 1 to 2 minutes, although this time
varies between systems.
g. When the Ethernet Port issues a close request first, the Ethernet Port waits 10 seconds. If the
T2N using the same port number reopen request during waiting for 10 seconds, the T2N
becomes “LAN controller driver error”.
h. If a close request comes from the remote port TCP socket while a connection is established,
the local port must also close the socket. As a technique for checking for the reception of close
requests from the remote TCP socket, user programs should monitor the RCLOSE and CONN
bits in the socket status. (See section 6.3.) RCLOSE is set to 1 and CONN is set to 0 when a
close request is received from the remote TCP socket. The Ethernet Port will return an error if
send or receive requests are issued in this state. A receive request in the receive wait state also
returns an error.
i. The Ethernet Port in the current state does not support a keep alive function for TCP
connections. Verification from the Ethernet Port side to other ports is not performed.
However, the Ethernet Port does respond to verifications from other ports. (Responding to
verifications from other ports is performed independently of user programs.)
Therefore, the disappearance of remote ports cannot be detected at the TCP level. We
recommend using the detection techniques described in items j and k below to detect this
condition.
Keep alive function: A function that checks, at the TCP protocol level, whether or not the
connection is operating normally if there has been no activity over the
connection for a certain fixed period.
¾ 80 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
j. For a TCP receive request, the Ethernet Port simply waits for data from the remote port. In
situations where data is sent periodically from the remote port, reception wait timeouts, i.e. no
response from the remote port states, can be detected by setting a reception wait time limit.
The following techniques, among others, can be used to detect no response states when data is
sent with no fixed period.
·
·
Periodic execution of existence verification requests (See section 7.3.)
The techniques described in the next section, which use a separate TCP connection
One of the following problems may have occurred when there is no response from the remote
port:
·
·
·
The remote port may have gone down.
Power may have been lost.
The remote ports and/or local port may have become disconnected from the network.
k. With a connection established, if the no response state from the remote port continues when
data is sent and the Ethernet Port internal resend processing times out (the timeout time is
about 1 minute), the NOACK bit in the socket status (See section 6.3.) will be set to 1. User
programs should close such sockets.
Also note that the Ethernet Port will return an error if send or receive requests are issued in
this state.
User program send requests are seen as completing as soon as they are received by the
Ethernet Port. This means that even if the remote port goes to the no response state, a
number of send requests equal to the Ethernet Port internal storage capacity (i.e., three
requests) will complete normally. When the number of send requests exceeds the Ethernet
Port internal storage capacity, errors will be returned for all further send requests.
l. Segments with the reset bit (RST) set to 1 (reset segments) are not supported by the Ethernet
Port. If a reset segment is received from the remote port, the NOACK bit in the socket status
(see section 6.3) will be set to 1 about 32 seconds later. Such sockets should be closed.
Reset segment: A transmitted segment used to forcibly close a connection from one of the
ports. Connections are forcibly closed in this manner if an error that cannot
be recovered from by normal means such as retransmission has occurred, or
if a port has recovered after having gone down.
m. In the Ethernet Port TCP socket interface, when reception data in the Ethernet Port is
read out by a receive request from the T2N, the Ethernet Port sends an ACK
(acknowledge response) to the port that sent the data. Since an ACK will not be sent to
the sending port if the received data remains in the Ethernet Port if the T2N does not read out
that received data, the sending port will resend the data. If this state continues for a
predetermined period, the sending port may will decide that the TCP connection is abnormal
and close the connection. To prevent this from occurring, the T2N software should monitor the
RCV (receive data present) bit and issue receive requests when necessary.
¾ 81 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6.3 Socket Interface Information
The information for the eight socket interface sockets held by the Ethernet Port can be read out
with the T2N READ instruction. The Ethernet Port holds five words of socket status information
for each socket. User programs should access this information as necessary when using socket
interface transmission.
·
·
·
·
Remote port TCP/UDP port number
Remote port IP address
TCP/UDP port number for this socket
Socket status
Table 6.1 lists the structure of the socket interface information and the extended memory area
addresses.
Table 6.1 Socket Interface Information
Socket identifier
1
2
3
4
5
6
7
8
Remote port number (TCP only)
Remote port IP address (TCP only)
0F4BH 0F53H 0F5BH 0F63H 0F6BH 0F73H 0F7BH 0F83H
0F4CH 0F54H 0F5CH 0F64H 0F6CH 0F74H 0F7CH 0F84H
0F4DH 0F55H 0F5DH 0F65H 0F6DH 0F75H 0F7DH 0F85H
Local port TCP/UDP port number
Socket status
0F4EH 0F56H 0F5EH 0F66H 0F6EH 0F76H 0F7EH 0F86H
0F4FH 0F57H 0F5FH 0F67H 0F6FH 0F77H 0F7FH 0F87H
For UDP sockets, the remote port number and IP address data are invalid.
The socket status has the following structure.
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
TCP
AOPEN CONN RCLOSE
NOACK
UDP
POPEN
RCV
¾ 82 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Bit
no.
Bit
Condition under which the bit is set to 1
Condition under which the bit is reset to 0
F
E
D
C
TCP
TCP used by the socket
The socket closed in response to a close request
The socket closed in response to a close request
The socket closed in response to a close request
The socket closed in response to a close request
UDP
UDP used by the socket
TCP socket in active open state
AOPEN
POPEN
TCP socket in passive open state or UDP
socket in open state
B
CONN
TCP connection established
Disconnected by the local port with a close request
Disconnected by the remote port
A
9
RCV
Received text present
No received text
RCLOSE An established TCP connection disconnected The socket closed in response to a close request
by the remote port
8
NOACK
No response received from the remote port for The socket closed in response to a close request
a local port send operation in a state where a
TCP connection was established, and the TCP
resend function resulted in a timeout (because
the remote port was down, etc.).
If the wait time exceeds the set value during a When a TCP active open request is reissued.
TCP active open request.
This bit is not set to 1 for a TCP passive open
request timeout.
A socket status in which neither AOPEN nor POPEN is set to 1 indicates that the socket is in the
closed state.
Important items
This area is a read-only area. Do not attempt to write this data with the WRITE instruction. It will
no longer be possible to acquire correct data after such an operation.
Sample: Socket interface information readout program
|
|
|
|R0000
1|-| |-[03907 MOV RW010][00005 MOV RW011][H00FE READ RW010 -> D1000]--|
|
|
READ instruction description
H00FE: Module designation. The Ethernet Port must specify H00FE.
RW010: Specifies the start address of the socket status information.
If 03907 (0F4BH) is specified, the socket status information for
socket 1 will be read out.
RW011: Specifies the number of words (00005) to be read out.
D1000: Specifiesthestartingaddressoftheareatoholdthereadoutsocket
status information.
In this case, the read out downloaded information is stored at locations
D1000 to D1004.
Setting R0000 to 1 will store the socket status information for socket
1 at locations D1000 to D1004.
¾ 83 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6.4 Using the Ethernet Port Socket Interface
This section describes the requests used by T2N user programs to use UDP and TCP sockets.
There are eight types of request as listed below.
·
·
UDP socket (open request, send request, receive request, close request)
TCP socket (open request, send request, receive request, close request)
1. UDP open request (using the SEND instruction)
a. Function
This request opens any of the eight sockets.
Transmission protocol: UDP/IP
b. Transfer parameters
A
3100H
Module designation
Command number
A+1
A+2
A+3
CMD = 0031H
SportNO
Socket identifier (1 to 8)
Local port specified socket UDP port number
(1024 to 65535)
UDP_PORTNO
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Important items
·
After this request completes normally, UDP send, receive or close requests can be sent to the
socket.
·
An error is returned if an open request is issued for an already open socket.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Already open (0080H)
·
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
An error is returned if a value other than a local port specified socket UDP port number is
specified.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Port number error (0071H)
¾ 84 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Not only must the specified socket UDP port number on the local port not overlap with UDP
port numbers used for message transmission and previously used UDP port numbers, but it also
must not overlap with any TCP port number. An error will occur if the port number overlaps.
·
·
Status: Transmission error (TermSTS = 0BH)
Detailed information: Already open (0080H)
If the T2N internal completion wait time limit (2 seconds) is exceeded for this request, the error
listed below is returned.
Status: Send completion timeout (TermSTS = 06H)
In this case, first verify that the Ethernet Port is not in the down state by checking the station
status, and then verify the open/closed state of the socket in the socket status.
¾ 85 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. UDP open processing example
Ladder program flowchart
Error result
UDP open processing start
Socket status read/verify
No
Are bits C and D both 0?
(Closed state?)
The specified socket is already open.
Yes
Execute a UDP open request
(CMD = 0031H).
Hold the input of function block in the
on state until the SEND instruction
completes.
Instruction
completion
Verify the status
An error occurred in the open processing
and the specified socket could not be
opened.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate UDP open processing
¾ 86 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2. UDP send request/broadcast send request (using the SEND instruction)
a. Function
This request sends local port register data using an open UDP socket.
Amount of data sent: 1 to 1000 words
b. Transfer parameters
A
3100H
CMD = 0032H
SportNO
Module designation, 1: channel number
Command number
Socket identifier (1 to 8)
A+1
A+2
A+3
A+4
DIPAddress
Transmission destination IP address
(The input format is the same as that for the parameter
setup request.)
A+5
A+6
A+7
A+8
D_UDP_PORTNO
WordSize
Transmission destination object socket UDP port number
Transmission data length: 1 to 1000 words
Transmission data storage register type code
Transmission data storage register number
SRID
StreqNOD
Transmission data storage register type code: Type code for the register that holds the
transmission data. (See Figure 5.1)
Transmission data storage register number:
Starting number of the registers that hold the
transmission data.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Important items
·
The T/C register flag data is not transmitted if the T/C registers are not specified as storage
registers for transmitted data.
·
An error is returned if a send request is issued for a socket that is not yet opened.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
·
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
If the IP address of the local port is specified as the transmission destination IP address, it will
be possible to send data, but it will not be possible to receive that data with a receive request.
¾ 87 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Values in the range 1024 to 65535 can be specified as the object socket UDP port number for
·
the transmission destination. An error will be returned if a value outside that range is specified.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Port number error (0071H)
·
·
·
An error will be returned if a value of 0 words or 1001 or more words is specified as the
transmission data size.
Status: Transmission word count error (TermSTS = 09H)
The T2N performs an area check for the register area based on the transmission data storage
register type and number, and if an error is found it returns an error.
Status: Boundary error (TermSTS = 0AH)
If the T2N internal completion wait time limit (2 seconds) is exceeded for this request, the error
listed below is returned.
Status: Send completion timeout (TermSTS = 06H)
In this case, first verify that the Ethernet Port is not in the down state by checking the station
status, and then perform the required error handling (the send request etc.).
·
The Ethernet Port uses a priority ordering in processing sockets 1 through 8. Therefore,
systems constructed so that socket 1 is activated frequently may not be able to process socket 8,
resulting in the following error response:
Status: Send completion timeout (TermSTS = 06H)
When constructing a system, take the socket utilization conditions into account when allocating
sockets. Since the send/receive processing for each socket requires about 50 ms, applications
that issue send or receive requests to a given socket should leave an interval of at least 50 ms
times the number of sockets used between each request.
(Interval between requests to the same socket) ³ (Number of sockets used ´ 50 ms)
Similarly, the above intervals averaging 50 ms should be left between transmissions from
remote ports to the local port.
(Interval between remote port transmissions) ³ (Number of remote ports ´ 50 ms)
·
When PC link transmission or the UDP socket interface is used, if an application
transmits to a nonexistent remote port, an transmission error (TermSTS = 0BH, detailed
information = 0020H) occurs.
e. Broadcast transmission
It is possible to broadcast to all ports on the network using UDP sockets.
Send side: Set the transmission destination address to "255.255.255.255", ("FF.FF.FF.FF"
in hexadecimal).
The "0.0.0.0" used by some UNIX versions (in particular, 4.2 BSD) cannot be
used.
Specify the UDP port number for the socket to which you want to issue a
broadcast as the transmission destination object socket UDP port number.
¾ 88 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
f.
UDP transmission processing example
Ladder program flowchart
Error result
UDP transmission processing start
Socket status read/verify
The processing in this section can be
performed at this stage or at the point the
instruction terminates abnormally.
No
Are bits C and E both 1?
(Opened state?)
The specified UDP socket is in the closed
state. (Open processing is required.)
Yes
Execute a UDP send request
(CMD = 0032H).
Hold the input of function block in the
on state until the SEND instruction
completes.
Instruction
completion
Verify the status
An error occurred in transmission
processing.
Transmission from the specified socket is
not possible.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate UDP transmission
processing
¾ 89 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
3. UDP receive request/broadcast receive request (using the RECV instruction)
a. Function
If an opened UDP socket receives data, read the received data into registers on the local port.
If no data has been received, wait until data arrives (the wait time can be set) and then, after
reception, read the received data into the local port registers.
Reception data size: 1 to 1000 words.
b. Transfer parameters
A
3100H
CMD = 0033H
SportNO
Module designation
Command number
Socket identifier (1 to 8)
A+1
A+2
A+3
A+4
DIPAddress
Transmission destination IP address
(The input format is the same as that for the parameter
setup request.)
A+5
A+6
A+7
A+8
A+9
D_UDP_PORTNO
WordSize
DRID
Transmission source object socket UDP port number
Reception data length: 1 to 1000 words
Reception data storage register type code
Reception data storage register number
Reception wait timeout time
DregNO
TimeCNT
Reception data length:
Set this parameter to a value greater than or equal to
the largest size for transmission data that could be sent
to the object socket in a single operation.
Reception data storage register type code: Type code for the register that stores the received data.
(See Figure 5.1)
Reception data storage register number:
Starting number of the registers that store the received
data.
Reception wait timeout time:
Specified in 0.1 second units. (1 to 65535)
If zero is specified, the system is set to an unlimited
(infinite) wait state.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
¾ 90 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
d. Methods for storing reception data
· Allocate a reception data storage register area with a size equal to the size of the reception data
plus one word. The reception data count (the size of the transmission data for a single
operation) and the transmission data for a single operation will be stored in this area as shown
in the figure.
Reception data count (bytes)
¬ Start of the specified
register area
Reception data storage
register area
Reception data
·
The T2N checks for register area allocation of the reception data size plus one word and
returns an error if the register area does not exist.
Status: Boundary error (TermSTS = 0AH)
In this case, data is not transferred to the register area, and the data is discarded. The data is
not retained in the Ethernet Port either.
e. Important items
·
An error is returned if a receive request is issued for a socket that is not yet opened.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
·
·
It is not possible to receive data sent from the local port, even if the local port IP address is
specified at the transmission source IP address.
Values in the range 1024 to 65535 can be specified as the object socket UDP port number for
the transmission source. An error will be returned if a value outside that range is specified.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Port number error (0071H)
·
·
An error will be returned if a value of 0 words or 1001 or more words is specified as the
reception data size.
Status: Transmission word count error (TermSTS = 09H)
An error will be returned if the reception timeout time is exceeded.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Timeout(0020H)
·
Allocate a reception data storage register area with a size equal to the size of the
transmission data plus one word. The size of the transmission data for the single operation
and the size of reception data will be stored in this area.
¾ 91 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
If the transmission data size for a single operation is larger than the reception data size, the
section of the transmitted data that exceeds the specified reception size is discarded, resulting
in the following error response.
·
Status: Transmission error (TermSTS = 0BH)
Detailed information: Insufficient data size(00C1H)
If this error is occurred, a reception data storage register of the T2N enters the data following
below. The data of slash bar is not received to T2N and discarded.
The number of transferred bytes
from Ethernet Port to T2N
The size of
reception data
The size of reception
data of Ethernet Port
(Specify the T2N)
The reception data itself
·
The Ethernet Port uses a priority ordering in processing sockets 1 through 8. Therefore,
systems constructed so that socket 1 is activated frequently may not be able to process socket 8,
resulting in the following error response:
Status: Send completion timeout (TermSTS = 06H)
When constructing a system, take the socket utilization conditions into account when allocating
sockets. Since the send/receive processing for each socket requires about 50 ms, applications
that issue send or receive requests to a given socket should leave an interval of at least 50 ms
times the number of sockets used between each request.
(Interval between requests to the same socket) ³ (Number of sockets used ´ 50 ms)
Similarly, the above intervals averaging 50 ms should be left between transmissions from
remote ports to the local port.
(Interval between remote port transmissions) ³ (Number of remote ports ´ 50 ms)
f.
Broadcast reception
It is possible to broadcast to all ports on the network using UDP sockets.
Receive side: Specify the transmission source IP address to be "0.0.0.0".
Specify the UDP port number for the broadcast transmitting socket as the
transmission source UDP port number.
¾ 92 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
g. UDP reception processing example (Socket status monitoring type)
Ladder program flowchart
Error result
UDP reception processing start
The processing in this section can be
performed at this stage or at the point the
instruction terminates abnormally.
Socket status read/verify
No
No
Are bits C and E both 1?
(Opened state?)
The specified UDP socket is in the closed
state. (Open processing is required.)
Yes
The specified UDP socket has not received
data.
Is bit A set to 1?
(Reception text present.)
Yes
Execute a UDP receive request
(CMD = 0033H).
Hold the input of function block in the
on state until the RECV instruction
completes.
Instruction
completion
Verify the status
An error occurred in reception processing.
The specified socket could not receive the
data.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate UDP reception processing
¾ 93 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
h. UDP reception processing example (Receive request issued first type)
Ladder program flowchart
Error result
UDP reception processing start
The processing in this section can be
performed at this stage or at the point the
instruction terminates abnormally.
Socket status read/verify
No
Are bits C and E both 1?
(Opened state?)
The specified UDP socket is in the closed
state. (Open processing is required.)
Yes
Execute a UDP receive request
(CMD = 0033H).
Hold the input of function block in the
on state until the RECV instruction
completes.
Instruction
completion
Verify the status
Did
the operation
complete before being
timed out?
No
No
Text was not received within the time limit.
Yes
An error occurred in reception processing.
The specified socket could not receive the
data.
Handle the error according to the
completion and socket status.
Normal complete?
Yes
Terminate UDP reception processing
¾ 94 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4. UDP close request (using the SEND instruction)
a. Function
Close the open UDP socket.
Release the (unlimited wait state) receive request and terminate the UDP socket.
b. Transfer parameters
A
3100H
CMD = 0034H
SportNO
Module designation
Command number
A+1
A+2
Socket identifier (1 to 8)
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Important items
·
UDP close requests are processed with the highest priority and other executing requests are
discarded, even if the object socket is executing a UDP open, send, or receive request. Other
requests during the execution of this request will be discarded.
·
·
The next open request for the object socket can be executed as soon as the close request
completes normally.
An error is returned if a close request is issued for a socket that is not yet opened.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
·
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
A UDP receive request will result in an error being returned if an unlimited wait state UDP
receive request is terminated with this request.
Status: Transmission completion timeout (TermSTS = 06H)
Supplement:
The T2N sees its requests (module control and socket interface transmission) to the Ethernet
Port as being "transmission" requests. As a result, when a request is forcibly terminated and a
response is not received from the Ethernet Port, the result is a send request timeout even if the
instruction was a RECV instruction.
·
If the T2N internal completion wait time limit (2 seconds) is exceeded for this request, the error
listed below is returned.
Status: Send completion timeout (TermSTS = 06H)
In this case, first verify that the Ethernet Port is not in the down state by checking the station
status, and then verify the open/closed state of the socket in the socket status.
¾ 95 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. UDP close processing example
Ladder program flowchart
Error result
UDP close processing start
Socket status read/verify
No
The specified UDP socket is already in the
closed state.
Are bits C and E both 1?
(Opened state?)
Yes
Execute a UDP close request
(CMD = 0034H).
Hold the input of function block in the
on state until the SEND instruction
completes.
Instruction
completion
Verify the status
An error occurred in the close processing
and the specified socket could not be
closed.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate UDP close processing
¾ 96 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5. TCP open request (using the SEND instruction)
a. Function
This request opens (active/passive) any of the eight sockets.
Transmission protocol: TCP/IP
b. Transfer parameters
Module designation
Command number
Socket identifier (1 to 8)
Open type
A
3100H
CMD = 0035H
SportNO
A+1
A+2
A+3
A+4
A+5
Kind
Remote port IP address
DIPAddress
Remote port object socket TCP port number
Local port specified socket TCP port number
Open wait timeout time
A+6
A+7
A+8
DTCP_PORTNO
STCP_PORTNO
TimeCNT
Open type (1 or 2)
1: Active open (client side)
2: Passive open (server side)
Open wait timeout time: specified in 0.1 second units. (1 to 65535) If zero is specified, the
system is set to an unlimited (infinite) wait state.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Important items
·
After this request completes normally, TCP send, receive or close requests can be sent to the
socket.
·
An error is returned if an open request is issued for an already open socket.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Already open (0080H)
·
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
An error will be returned if a value outside the range 1024 to 65535 is specified for the local
port specified socket TCP port number.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Port number error (0071H)
¾ 97 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Not only must the specified socket TCP port number on the local port not overlap with any
·
TCP port number already in use in a local port socket, but it also must not overlap with any
UDP port numbers or UDP port numbers used for message transmission. An error will
occur if the port number overlaps.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Already open (0080H)
·
·
A connection to the local port itself cannot be established, even if the local port IP address is
specified as the remote port IP address.
Values in the range 1024 to 65535 can be specified as the object socket TCP port number for
the remote port. An error will be returned if a value outside that range is specified.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Port number error (0071H)
An error will be returned if the open timeout time is exceeded.
¬The passive open timeout
·
·
Status: Transmission error (TermSTS = 0BH)
Detailed information: Timeout(0020H)
•The active open timeout
Status: Transmission complete timeout (TermSTS = 06H)
While the open wait timeout limit can be set to any value in the range 0.1 to 6553.5 seconds or
unlimited (infinite), we recommend that the timeout limit be set in the range 0.1 to 32
seconds for active opens. This is because the Ethernet Port processing continuation time for
active open processing is 32 seconds. Even if the timeout limit is set to a value over 32
seconds, once 32 seconds has elapsed, the open processing will never actually be performed.
The system will be in an idle state until the specified time has elapsed.
·
·
·
When a passive open operation is executed, the specified socket goes to the active open wait
state. If the DIPAddress and DTCP_PORTNO values are set to 0, the socket is set to the state
in which a particular remote port is not specified. (In this state the socket can handle an active
open from any other (i.e., any remote) port on the network.)
A connection is established by an active open from another socket applied to a socket in the
passive open state. A connection cannot be established by a passive open from another socket
applied to a socket in the passive open state. Similarly, a connection cannot be established by
an active open from another socket applied to a socket in the active open state.
For a socket in the passive open state, it is not possible to open multiple connections from other
ports by issuing multiple active opens.
¾ 98 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. TCP open processing example
Ladder program flowchart
Error result
TCP open processing start
Socket status read/verify
No
Are bits C and D both 0?
(Closed state?)
The specified socket is already open
(active or passive).
Yes
Execute a TCP open request
(CMD = 0035H).
Active or passive
open
Hold the input of function block in the
on state until the SEND instruction
completes.
Instruction
completion
Verify the status
Did
the operation
complete before being
timed out?
No
No
Connection could not be established within
the time limit.
Yes
An error occurred during open processing
and the connection could not be
established.
Handle the error according to the
completion and socket status.
Normal complete?
Yes
Terminate TCP open processing
(Connection established)
¾ 99 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6. TCP send request (using the SEND instruction)
a. Function
This request sends local port register data using an open TCP socket.
Amount of data sent: 1 to 1000 words
b. Transfer parameters
Module designation
Command number
Socket identifier (1 to 8)
A
3100H
CMD = 0037H
SportNO
A+1
A+2
A+3
A+4
A+5
Transmission data length: 1 to 1000 words
Transmission data storage register type code
Transmission data storage register number
WordSize
SRID
StreqNOD
Transmission data storage register type code: Type code for the register that holds the
transmission data. (See Figure 5.1)
Transmission data storage register number:
Starting number of the registers that hold the
transmission data.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Important items
·
Send requests complete at the point they are stored in the Ethernet Port. This is to allow the
send to be performed later even if that send request cannot be executed immediately due to
network congestion or other problems. The Ethernet Port can store up to three requests per
socket, and the Ethernet Port returns an error for send requests that it cannot store.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Timeout(0020H)
·
·
The T/C register flag data is not transmitted if the T/C registers are not specified as storage
registers for transmitted data.
An error is returned if a send request is issued for a socket that is not yet opened.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
¾ 100 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
An error will be returned if a value of 0 words or 1001 or more words is specified as the
·
·
·
transmission data size.
Status: Transmission word count error (TermSTS = 09H)
The T2N performs an area check for the register area based on the transmission data storage
register type and number, and if an error is found it returns an error.
Status: Boundary error (TermSTS = 0AH)
If a close request from the remote port TCP socket has arrived while a connection is
established, and the user program issues a send request, the Ethernet Port returns the following
error.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
Verify the socket status (see section 6.3) RCLOSE and CONN bits, and close the socket.
·
With a connection established, if a no response state from the remote port continues when data
is sent and the Ethernet Port internal resend processing times out (the timeout time is about 1
minute), the NOACK bit in the socket status will be set to 1. User programs should close such
sockets. Errors will be returned for send/receive requests issued in this state.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Protocol error (0091H)
However, note that the Ethernet Port will return normal complete responses for TCP send
requests issued prior to the timeout, since the send requests from the T2N are stored internally
by the Ethernet Port.
When the number of send requests that can be stored is exceeded, errors will be returned for
that and all following send requests.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Timeout (0020H)
·
·
One of the following problems may have occurred when there is no response from the remote
port:
·
·
·
The remote port may have gone down.
Power may have been lost.
The remote ports and/or local port may have become disconnected from the network.
If the T2N internal completion wait time limit (2 seconds) is exceeded for this request, the error
listed below is returned.
Status: Send completion timeout (TermSTS = 06H)
In this case, first verify that the Ethernet Port is not in the down state by checking the station
status, and then perform the required error handling.
¾ 101 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
The Ethernet Port uses a priority ordering in processing sockets 1 through 8. Therefore,
systems constructed so that socket 1 is activated frequently may not be able to process socket 8,
resulting in the following error response:
·
Status: Send completion timeout (TermSTS = 06H)
When constructing a system, take the socket utilization conditions into account when allocating
sockets. Since the send/receive processing for each socket requires about 50 ms, applications
that issue send or receive requests to a given socket should leave an interval of at least 50 ms
times the number of sockets used between each request.
(Interval between requests to the same socket) ³ (Number of sockets used ´ 50 ms)
Similarly, the above intervals averaging 50 ms should be left between transmissions from
remote ports to the local port.
(Interval between remote port transmissions) ³ (Number of remote ports ´ 50 ms)
¾ 102 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. TCP transmission processing example
Ladder program flowchart
Error result
TCP transmission processing start
The processing in this section can be
performed at this stage or at the point the
instruction terminates abnormally.
Socket status read/verify
A connection has not been established with
the specified TCP socket. (Open processing
is required.)
No
No
Are bits B and F both 1?
(Is a connection established?)
Yes
The specified TCP socket is either:
• Closed by the remote port, or
• Not responding.
Are bits 8 and 9 both 0?
(In neither the RCLOSE nor NOACK
state?)
(The socket must be closed by the local
port.)
Yes
Execute a TCP send request
(CMD = 0037H).
Hold the input of function block in the
on state until the SEND instruction
completes.
Instruction
completion
Verify the status
An error occurred in transmission
processing.
Transmission from the specified socket is
not possible.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate TCP transmission
processing
¾ 103 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7. TCP receive request (using the RECV instruction)
a. Function
If an opened TCP socket receives data, read the received data into registers on the local T2N.
If no data has been received, wait until data arrives (the wait time can be set) and then, after
reception, read the received data into the local T2N registers.
Reception data size: 1000 words (fixed)
b. Transfer parameters
Module designation
A
3100H
CMD = 0038H
SportNO
WordSize
DRID
Command number
A+1
A+2
A+3
A+4
A+5
A+6
Socket identifier (1 to 8)
Reception data length: 1000 words
Reception data storage register type code
Reception data storage register number
Reception wait timeout time
DregNO
TimeCNT
Reception data length:
This parameter must be set to 1000 words.
Reception data storage register type code: Type code for the register that holds the received
data. (See Figure 5.1)
Reception data storage register number:
Starting number of the registers that hold the received
data.
Reception wait timeout time:
specified in 0.1 second units. (1 to 65535)
If zero is specified, the system is set to an unlimited
(infinite) wait state.
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Methods for storing reception data
·
Applications must allocate a reception data storage area of 1001 words. The reception data
count and the reception data (the data received by the object socket at the point the receive
request was issued) will be stored in this area as shown below.
Reception data count (bytes)
¬ Start of the specified
register area
Reception data storage
register area
Reception data
¾ 104 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
The T2N checks for register area allocation of the reception data size plus one word and
·
returns an error if the register area does not exist.
Status: Boundary error (TermSTS = 0AH)
In this case, data is not transferred to the register area, and the data is discarded. The data is
not retained in the Ethernet Port either.
e. Important items
·
An error is returned if a receive request is issued for a socket that is not yet opened.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
·
·
An error will be returned if a value of 0 words or 1001 or more words is specified as the
reception data size.
Status: Transmission word count error (TermSTS = 09H)
An error will be returned if the reception timeout time is exceeded.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Timeout(0020H)
·
If a close request from the remote port TCP socket has arrived while a connection is
established, and the user program issues a receive request, the Ethernet Port returns the
following error. Issuing a receive request in the receive wait state will also result in the
following error being returned.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
Verify the socket status (see section 6.3) RCLOSE and CONN bits, and close the socket.
·
·
Allocate a reception data storage register area per a socket with a size equal to the size of
the transmission data plus one word.
If the reception data size is larger than the reception data size of the receiving Ethernet Port,
the size of transmission data for the single operation and the size of reception data at that time
is transmitted to the T2N’s reception data storage register area.
·
Since a TCP receive request merely places the socket in the receive wait state, it cannot detect
remote ports that are not responding. Use one of the following methods to prevent this state.
·
·
·
Monitor for a no-response state by sending data periodically over a separate (different)
TCP connection.
Execute a remote port presence verification request for the remote port periodically. (See
section 7.3.)
Monitor the interval between data receptions when data is being received periodically.
(Receive request issued first type: specify a limited timeout limit.)
(Socket status monitoring type: monitor the interval between points when the received text
present bit is set to the on state.)
¾ 105 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
·
·
One of the following problems may have occurred when there is no response from the remote
port:
·
·
·
The remote port may have gone down.
Power may have been lost.
The remote ports and/or local port may have become disconnected from the network.
In the Ethernet Port TCP socket interface, when reception data in the Ethernet Port is
read out by a receive request from the T2N, the Ethernet Port sends an ACK
(acknowledge response) to the port that sent the data. Since an ACK will not be sent to the
sending port if the received data remains in the Ethernet Port if the T2N does not read out that
received data, the sending port will resend the data. If this state continues for a predetermined
period, the sending port may will decide that the TCP connection is abnormal and close the
connection. To prevent this from occurring, the T2N software should monitor the RCV (receive
data present) bit and issue receive requests when necessary.
·
With TCP receive requests, the amount of data transferred to the reception data storage register
area will differ with both the timing with which the T2N issued the receive request and the
timing with which the data arrives at the Ethernet Port. To handle single units of transmission
data on the receiving side as single units as well, the user software on the receiving side must
recognize the end of the transferred data (either by using counts in the transmitted data or by
including an end marker in the transmitted data) and iterate receive requests until all the
transmitted data has been received.
·
·
User programs must save all incoming data so that the register area used to transfer data to the
T2N is not overwritten when using iterated receive requests.
The Ethernet Port uses a priority ordering in processing sockets 1 through 8. Therefore,
systems constructed so that socket 1 is activated frequently may not be able to process socket 8,
resulting in the following error response:
Status: Send completion timeout (TermSTS = 06H)
When constructing a system, take the socket utilization conditions into account when allocating
sockets. Since the send/receive processing for each socket requires about 50 ms, applications
that issue send or receive requests to a given socket should leave an interval of at least 50 ms
times the number of sockets used between each request.
(Interval between requests to the same socket) ³ (Number of sockets used ´ 50 ms)
Similarly, the above intervals averaging 50 ms should be left between transmissions from
remote ports to the local port.
(Interval between remote port transmissions) ³ (Number of remote ports ´ 50 ms)
¾ 106 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
f.
TCP reception processing example (Socket status monitoring type)
Ladder program flowchart
Error result
TCP reception processing start
The processing in this section can be
performed at this stage or at the point the
instruction terminates abnormally.
Socket status read/verify
A connection has not been established with
the specified TCP socket. (Open processing
is required.)
No
No
No
Are bits B and F both 1?
(Is a connection established?)
Yes
The specified TCP socket is:
• Closed by the remote port
Is bit 9 set to 0?
(In the state other than RCLOSE?)
(The socket must be closed by the local
port.)
Yes
The specified TCP socket has not received
data.
Is bit A set to 1?
(Reception text present.)
Yes
Execute a TCP receive request
(CMD = 0038H).
Hold the input of function block in the
on state until the RECV instruction
completes.
Instruction
completion
Verify the status
An error occurred in reception processing.
The specified socket coule not receive the
data.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate TCP reception processing
¾ 107 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
g. TCP reception processing example (Receive request issued first type)
Ladder program flowchart
Error result
TCP reception processing start
The processing in this section can be
performed at this stage or at the point the
instruction terminates abnormally.
Socket status read/verify
A connection has not been established with
the specified TCP socket. (Open processing
is required.)
No
No
Are bits B and F both 1?
(Is a connection established?)
Yes
The specified TCP socket is:
• Closed by the remote port
Is bit 9 set to 0?
(In the state other than RCLOSE?)
(The socket must be closed by the local
port.)
Yes
Execute a TCP receive request
(CMD = 0038H).
Hold the input of function block in the
on state until the RECV instruction
completes.
Instruction
completion
Verify the status
Did
the operation
complete before being
timed out?
No
No
Text was not received within the time limit.
Yes
An error occurred in reception processing.
The specified socket could not receive the
data.
Handle the error according to the
completion and socket status.
Normal complete?
Yes
Terminate TCP reception processing
¾ 108 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8. TCP close request (using the SEND instruction)
a. Function
Close the open TCP socket.
Release the (unlimited wait state) receive request and terminate the TCP socket.
b. Transfer parameters
Module designation
Command number
Socket identifier (1 to 8)
A
3100H
CMD = 0039H
SportNO
A+1
A+2
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
SportNO
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
SportNO: Socket identifier (1 to 8)
TermSTS:See tables 4.3 and 4.4.
Detail information: See table 4.5.
d. Important items
·
TCP close requests are processed with the highest priority and other executing requests are
discarded, even if the object socket is executing a TCP open, send, or receive request. Other
requests during the execution of this request will be discarded.
·
An error is returned if a close request is issued for a socket that is not yet opened.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Unopened (0081H)
·
·
An error is returned if a value other than 1 to 8 is specified as the socket identifier.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Illegal socket identifier (0082H)
A TCP receive requests will result in an error being returned if an unlimited wait state
TCP open request/receive request is terminated with this request.
Status: Transmission completion timeout (TermSTS = 06H)
Supplement:
The T2N sees its requests (module control and socket interface transmission) to the Ethernet
Port as being "transmission" requests. As a result, when a request is forcibly terminated and a
response is not received from the Ethernet Port, the result is a send request timeout even if the
instruction was a RECV instruction.
·
If a close request is comes from the remote port TCP socket while a connection is established,
the local port must also close the socket. As a technique for checking for the reception of close
requests from the remote TCP socket, user programs should monitor the RCLOSE and CONN
bits in the socket status. (See section 6.3.)
¾ 109 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
If a close request is sent from the Ethernet Port TCP socket while a connection is established,
The T2N cannot reopen request using the same port number of the closed port number for 10
seconds or more since the Ethernet Port is set the close request.
·
Supplement:
On engineering workstation and personal computer systems, it may not be possible to reopen
a TCP socket on the port that performed the close processing for a fixed period.
·
·
The Ethernet Port which received a close request from the T2N replies to be received the T2N.
Therefore, a close request of the T2N completes the no waiting time. The Ethernet Port send a
close request to a remote port and is waiting for a close request from a remote port.
If the T2N executes a open request in the same port number while the Ethernet Port is waiting
for a close request from a remote port, a open request will result in an error being returned.
Status: Transmission error (TermSTS = 0BH)
Detailed information: Opened (0080H) or
LAN controller driver error (0090H/0092H)
¾ 110 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. TCP close processing example
Ladder program flowchart
Error result
TCP close processing start
This is not necessary in processing for which
the RCLOSE and NOACK bits have
become 1.
Socket status read/verify
No
Are bits B and F both 1?
(Is a connection established?)
The specified UDP socket is already in the
closed state.
Yes
Execute a TCP close request
(CMD = 0039H).
Hold the input of function block in the
on state until the SEND instruction
completes.
Instruction
completion
Verify the status
An error occurred in the close processing
and the specified socket could not be
closed.
Handle the error according to the
completion and socket status.
No
Normal complete?
Yes
Terminate TCP close processing
¾ 111 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6.5 Sample Programs
This section presents sample programs using UDP and TCP sockets.
1. UDP sockets
This is a sample program that issues the requests used with UDP sockets. It assumes that the
parameter set up and operating mode control requests (run mode/socket interface transmission
enable) have already completed.
a. UDP open request
This program issues a UDP open request for socket number 2 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0620.
Parameters:
12544: 3100H, 00049: 0031H
UDP port number: 4000
| /* UDP open request: executed when R0620 is set on.
*/
|
|
|
|R0620
1|-| |-+[12544 MOV RW000][00049 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup
*/
|
+[00002 MOV RW002][04000 MOV RW003]----------------------------|
|
|
/* Socket identifier, UDP port number setup */
|
+[RW000 SEND RW010][RST R0620]---------------------------------|
/* Turn R0620 off after request setup and completion. */
|
¾ 112 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. UDP close request
This program issues a UDP close request for socket number 2 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0623.
Parameters: 12544: 3100H, 00052: 0034H
| /* UDP close request: executed when R0623 is set on. */
|
|
|
|
|R0623
1|-| |-+[12544 MOV RW000][00052 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup
*/
|
+[00002 MOV RW002]---------------------------------------------|
|
|
/* Socket identifier setup */
|
+[RW000 RECV RW010][RST R0623]---------------------------------|
/* Turn R0623 off after request setup and completion. */
|
¾ 113 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
c. UDP send request
This program issues a UDP send request for socket number 2 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0622.
Parameters: 12544: 3100H, 00050: 0032H
0341995909: 14627185H
Transmission destination IP address: 133.113.98.20
Transmission destination object socket UDP port number: 3000
Transmission data word count: 1000
Transmission data storage registers: D1000 and above
| /* UDP send request: executed when R0622 is set on. */
|
|
|
|
|R0622
1|-| |-+[12544 MOV RW000][00050 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup */
|
+[00002 MOV RW002]---------------------------------------------|
|
|
/* Socket identifier setup */
|
+[0341995909 DMOV RW004· RW003][03000 MOV RW005]----------------|
|
|
/* Remote port IP address, port number setup */
|
+[01000 MOV RW006]---------------------------------------------|
|
|
/* Transmission data word count setup
*/
|
+[00004 MOV RW007][01000 MOV RW008]----------------------------|
/* Transmission data storage register type, storage register
|
|number setup */
|
|
|
|
|
|
+[RW000 SEND RW010][RST R0622]---------------------------------|
/* Turn R0622 off after request setup and completion. */
|
¾ 114 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
d. UDP receive request
This program issues a UDP send request for socket number 2 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0621.
Parameters: 12544: 3100H, 00051: 0033H
0341995909: 14627185H
Transmission source IP address: 133.113.98.20
Transmission source object socket UDP port number: 3000
Reception data word count: 1000
Reception data storage registers: D2500 and above
Reception timeout time: 1800 seconds
| /* UDP receive request: executed when R0621 is set on. */
|
|
|
|
|R0621
1|-| |-+[12544 MOV RW000][00051 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup
*/
|
+[00002 MOV RW002]---------------------------------------------|
|
|
/* Socket identifier setup */
|
+[0341995909 DMOV RW004· RW003][03000 MOV RW005]----------------|
|
|
/* Remote port IP address, port number setup */
|
+[01000 MOV RW006]---------------------------------------------|
|
|
/* Reception data word count setup */
|
+[00004 MOV RW007][02500 MOV RW008][18000 MOV RW009]-----------|
/* Reception data storage register type, storage register
|
|number, timeout time setup */
|
|
|
|
|
|
+[RW000 RECV RW010][RST R0621]---------------------------------|
/* Turn R0621 off after request setup and completion. */
|
¾ 115 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
2. TCP sockets
This is a sample program that issues the requests used with TCP sockets. It assumes that the
parameter set up and operating mode control requests (run mode/socket interface transmission
enable) have already completed.
a. TCP open request (passive)
This program issues a TCP open request (passive) for socket number 8 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0630.
Parameters: 12544: 3100H, 00053: 0035H
341995909: 14627185H
Remote port IP address: 133.113.98.20
Remote port object socket TCP port number:
Local port specified socket TCP port number:
Open request timeout time: 1800 seconds
4000
4000
| /* TCP passive open request: executed when R0630 is set on. */
|
|
|
|
|R0630
1|-| |-+[12544 MOV RW000][00053 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup */
|
+[00008 MOV RW002][00002 MOV RW003]----------------------------|
|
|
/* Socket identifier, open type setup
*/
|
+[0341995909 DMOV RW005· RW004][04000 MOV RW006]----------------|
|
|
/* Remote port IP address and port number setup */
|
+[04000 MOV RW007][18000 MOV RW008]----------------------------|
|
|
/* Local port number, timeout time setup
*/
|
+[RW000 SEND RW010][RST R0630]---------------------------------|
/* Turn R0630 off after request setup and completion. */
|
¾ 116 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. TCP open request (active)
This program issues a TCP open request (active) for socket number 8 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0640.
Parameters:
12544: 3100H, 00053: 0035H
341995909: 14627185H
Remote port IP address: 133.113.98.20
Remote port object socket TCP port number:
Local port specified socket TCP port number:
Open request timeout time: 1800 seconds
4000
4000
| /* TCP active open request: executed when R0640 is set on. */
|
|
|
|
|R0640
1|-| |-+[12544 MOV RW000][00053 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup */
|
+[00002 MOV RW002][00001 MOV RW003]----------------------------|
|
|
/* Socket identifier, open type setup
*/
|
+[RW106· RW105 DMOV RW005· RW004][RW107 MOV RW006]---------------|
|
|
/* Remote port IP address and port number setup */
|
+[RW107 MOV RW007][18000 MOV RW008]----------------------------|
|
|
/* Local port number, timeout time setup
*/
|
+[RW000 SEND RW010][RST R0640]---------------------------------|
/* Turn R0640 off after request setup and completion. */
|
¾ 117 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
c. TCP close request
This program issues a TCP close request for socket number 8 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0633.
Parameters: 12544: 3100H, 00057: 0039H
| /* TCP close request: executed when R0633 is set on. */
|
|
|
|
|R0633
1|-| |-+[12544 MOV RW000][00057 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup
*/
|
+[00008 MOV RW002]---------------------------------------------|
|
|
/* Socket identifier setup */
|
+[RW000 SEND RW010][RST R0633]---------------------------------|
/* Turn R0633 off after request setup and completion. */
|
¾ 118 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
d. TCP send request
This program issues a TCP send request for socket number 8 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0632.
Parameters: 12544: 3100H, 00055: 0037H
Transmission data word count: 1000
Transmission data storage registers: D1000 and above
| /* TCP send request: executed when R0632 is set on. */
|
|
|
|
|R0632
1|-| |-+[12544 MOV RW000][00055 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup */
|
+[00008 MOV RW002]---------------------------------------------|
|
|
/* Socket identifier setup */
|
+[01000 MOV RW003]---------------------------------------------|
|
|
/* Transmission data word count setup
*/
|
+[00004 MOV RW004][00000 MOV RW005]----------------------------|
/* Transmission data storage register type, storage register
|
|number setup */
|
|
|
|
|
|
+[RW000 SEND RW010][RST R0632]---------------------------------|
/* Turn R0632 off after request setup and completion. */
|
¾ 119 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. TCP receive request
This program issues a TCP receive request for socket number 8 on the Ethernet Port.
This ladder program is executed by turning on the A contact on the R0631.
Parameters: 12544: 3100H, 00056: 0038H
Reception data word count: RW103
Reception data storage registers: D4000 and above
Reception data transfer destination registers: D1001 and above
Reception timeout time: 1800 seconds
| /* TCP receive request: executed when R0631 is set on. */
|
|
|
|
|R0631
1|-| |-+[12544 MOV RW000][00056 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
/* Module designation, CMD number setup
*/
|
+[00008 MOV RW002][RW103 MOV RW003]----------------------------|
|
|
/* Socket identifier, reception data word count setup */
|
+[00004 MOV RW004][04000 MOV RW005][18000 MOV RW006]-----------|
/* Reception data storage register type, register number,
|
|timeout time setup */
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
+-|^|-+[00004 MOV RW021][04001 MOV RW022]----------------------|
|
|
|
|
|
|
|
|
|
|
|
| /* Data transfer source register type, number setup
|
*/
|
+[00001 MOV RW025]---------------------------------------|
| /* Data transfer count setup
|
*/
|
+[00004 MOV RW023][01001 MOV RW024]----------------------|
| /* Data transfer destination register type, number setup */
|
|
+[RW103 +
01000 -> RW008]-----------------------------|
/* Transmission event count setup */
|
+[SET R0635][RST R0631]----------------------------------------|
|
¾ 120 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
| /* TCP fragmented data reception processing */
|
|
|
|
|R0635 R063D
2|-| |-+-|/|--[RW000 RECV RW010][SET R063D]----------------------------|
|
|
/* Request setup
*/
|
|R063D
|
|
+-| |-+-|^|--[RTR1D4000]----------------------------------------|
|
|
/* Reception data count conversion (bytes to
|words) */
|
|R063E
|
|
+-|/|-+[RW021 XFER RW025 -> RW023]-----------------------|
|
|
|
|
|
|
|
|
/* Reception data transfer (D4001 to D1001) */
|
|
|
+[ +1 RW009][ +1 RW022][ +1 RW024]------------------|
/* Increment address and pointer. */
R063E |
|
|
|
+[RW009 >= D4000]------------------------------------( )--|
|
|
|
|
|
|
/* Reception data size check
*/
|
|R063E
|
+-| |-+[RW008 > RW024][ RST R063D]-----+[ 00000 MOV RW009]|
|
|
|
|
|
|
|
+[ 04001 MOV RW022]|
|
/* Processing for data less than the reception
|data size */
|
|
|
|
+[RW008 <= RW024]-----+[ RST R063D]-----------------|
|
|
|
|
+[ 00000 MOV RW009][RST R0635]|
|
/* Processing for data greater than the
|reception data size */
|
|
¾ 121 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7. RAS Information
This chapter describes the following RAS functions provided by the Ethernet Port.
CAUTION
1. Chapter 7 presents information related to using the functions provided by the Ethernet Port from a
T2N, including the instruction (request) format, important items that require attention, and sample
programs.
Make a point of understanding the content of chapter 4 thoroughly before writing programs that use
the Ethernet Port. The sample programs present basic examples of Ethernet Port usage, and should
be reviewed carefully before use in an actual system.
1. Ethernet Port status information
·
·
Station status (T2N special registers)
Down information (T2N interface buffer)
2. Test functions from user programs
·
·
Remote port verification request (corresponds to the UNIX ping command)
Inter-port loopback test (between T2N and T2N/T3H units)
3. Time setting function
4. Information provided by RAS information readout
·
·
·
·
LAN controller (network circuit) information
Protocol state
State of the T2N-Ethernet Port interface
Event trace
¾ 122 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7.1 T2N Special Relays and Registers
The Ethernet Port status information is reflected in the T2N special relays and special registers.
a. Special relays (the renewing cycle of 100 ms)
Special relay
Name
Function
S000B
Ethernet Port error
(warning)
1: The installed Ethernet Port unit is down.
(The T2N continues to operate.)
0: Reset the system from a user program after resolving the
error in the down Ethernet Port.
b. Special registers
T2N read out the internal station status of Ethernet Port and copy the SW register (the
renewing cycle of 100 ms).
Special registers Name
SW063
CH1 station status
c. Station status format
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
DOWN
STBY
MTEN
TEST
INZ
RUN
STEN
·
·
Bit F: DOWN (down)...........................................1: Down mode, 0: Other than down mode
Bit E: INZ (initialization).....................................1: Initialization in progress
0: Initialization completed
·
Bit D: STBY (standby).........................................1: Standby mode
0: Other than standby mode
·
·
·
·
Bit C: RUN (run)..................................................1: Run mode, 0: Other than run mode
Bit 5: MTEN (Message transmission)..................1: Enabled, 0: Prohibited
Bit 4: STEN (socket interface transmission).........1: Enabled, 0: Prohibited
Bit 0: TEST (test).................................................1: Test function execution in progress
¾ 123 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
d. Operation mode and station status of Ethernet Port
Each bit of station status has the following mean. If you want to judge the mode
(initialize mode/ run mode/ standby mode), look at the value of the register.
The mode of Ethernet Port
During initialize (Power on / Reset request)
Standby mode (initialize processing normally complete)
Run mode : Allows the message transmission
Run mode : Allows the socket interface
The station status
4000H
2000H
1020H
1010H
Run mode : Allows the message transmission
and socket interface
1030H
¾ 124 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7.2 Down Information
When an Ethernet Port goes to down mode, the factor that caused that transition is stored in the
T2N interface buffer as one word of data. This data can be read by the T2N with the READ
instruction.
Table 7.1 lists the down information error codes and the factors that caused the transition to down
mode.
Table 7.1 Down Information
Error code (H)
0010
Interpretation
Watchdog timeout
0020
Memory bus stall
0030
A TRAP occurred
0040
Jabbering timeout
0050
0160
0260
0360
0500, 0501
0502, 0503
0504
LAN controller check error
ROM BCC check data match error
System RAM area check error
T2N interface buffer check error
Semaphore acquisition error
Semaphore acquisition error
MBX receive error
0505
MBX send error
0506
0507
0508
TCP resend queue full
Acquired buffer in use
Error in acquiring initial buffer
Important items
This is a read-only area. Do not write to this area with the WRITE instruction. Subsequent reads
will not return correct down information.
Sample: Down information readout
|R0000
|
1|-| |--[04081 MOV RW010][00001 MOV RW011][H00FE READ RW010 -> D1000]--|
|
|
READ instruction description
H00FE: Module designation ... Ethernet Port must specify H00FE.
RW010: Specifies the 04081 (0FF1H) down information area.
0FF1H is the down information area for the Ethernet Port.
RW011: Specifies the number of words (00001) to be read out.
D1000: Specifies the register in which to store the read out down information.
In this case, the down information that is read out is stored in D1000.
The down information is stored in D1000 by turning R0000 on.
¾ 125 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7.3 Remote Port Verification Request
This request verifies the existence of the specified remote port, and corresponds to the UNIX ping
command. This request can be issued when the Ethernet Port operating mode is either run or
standby mode. The Ethernet Port will respond to this request if its operating mode is either run or
standby mode.
Remote port verification request (using the SEND instruction)
a. Function
This is a request that verifies the existence of the specified remote port.
b. Transfer parameters
A
3100H
Module designation
CMD number
A+1
A+2
A+3
CMD = 0014H
D- IP address
IP address of the remote station whose
existence is to be verified.
(The input format is the same as that for the
parameter setup request.)
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
This request is possible in run and standby modes. (The IP address of the local port must be set
up.)
·
The Ethernet Port returns a response to this request in run and standby modes. (The IP address
of the local port must be set up.)
·
·
If the remote port exists:
Normal return
If the remote port does not exist (within 4 seconds):
Status:
Transmission error (TermSTS = 0BH)
Detailed information: Timeout occurred (0020H)
¾ 126 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. Sample program
This sample ladder program issues a remote port verification request to the Ethernet Port.
This program is executed by turning on the R0504 A point.
Parameters: 12544:3100H, 00020:0014H, 341995909;14627185H
¯
85H. 71H. 62H. 14H
¯
133. 113. 98. 20
|R0504
R0604 |
1|-| |-----------------------------------------------------------( )--|
|
/* Remote port verification request */
|R0604
|
2|-| |-+[12544 MOV RW000][00020 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
/* Designates the module and sets the CMD number. */
|
+[341995909 DMOV RW003· RW002]----------------------------------|
|
|
/* Sets remote port IP address */
|
+[RW000 SEND RW010][RST R0504]---------------------------------|
/* Sets the request. */
|
¾ 127 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7.4 Remote Port Loopback (for an Ethernet Port)
This request sends test data to the specified remote Ethernet Port (T2N/T3H) and verifies that
transmission is being performed correctly by receiving that data looped back from the remote port.
A user program must compare the transmitted and received data for equivalence.
Remote port loopback request (using the SEND instruction)
a. Function
This request sends test data to the specified remote Ethernet Port (T2N/T3H) and verifies that
transmission is being performed correctly by receiving that data looped back from the remote port.
The T2N OS creates the test data.
b. Transfer parameters
A
3100H
CMD = 000FH
WordSize
SRID
Module designation
A+1
A+2
A+3
A+4
A+5
A+6
A+7
A+8
A+9
CMD number
Loopback data length: 1 to 485 words
Send data storage register type code
Send data storage register number
Loopback data storage register type code
Loopback data storage register number
Timer count
SRegNO
DRID
DRegNO
Timecnt
D-IPAddress
Loopback destination IP address
(The input procedure is the same as that for the parameter
setup request.)
A+10
D-UDP PortNO
Loopback destination message transmission UDP port number
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
This request cannot be executed unless message transmission is enabled with an operating
mode control request.
·
In response to a request from a user program, the T2N OS performs the processing using the
Ethernet Port PC link protocol.
·
·
·
User programs on the loopback destination do not take part in this operation.
A user program must compare the transmitted and loopback data for equivalence.
A transfer word count error (TermSTS = 09H) occurs if the loopback data length exceeds the
range 1 to 485 words (or 1 to 323 words for the T and C registers).
·
·
A register specification error (TermSTS = 01H) occurs if a value other than a stipulated value
is specified for the register type codes (SRID/DRID).
A register specification error (TermSTS = 01H) occurs if 0007H (the T register) is specified
for the send data storage register type code and a register other than the T register is specified
for the loopback data storage register type code. This also holds for the C register.
·
A boundary error (TermSTS = 0AH) occurs if a range spanning both the base T registers (0 to
511) and the expansion T registers (512 to 999) is specified for the T register.
¾ 128 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
For data storage registers, a boundary error (TermSTS = 0AH) occurs if the specified area
·
·
·
(start register + register range) does not exist in the local port.
A response timeout error (TermSTS = 02H) occurs if the loopback response time exceeds the
time specified by the timer counter value.
If the local port registers are write protected by setting the special coil, the memory write
protected status (TermSTS = 04H) is returned.
F
9
8
7
6
5
4
3
2
1
0
0: Write enabled
1: Write protected
SW067
SW C
T
F
D
RW LW W XW/YW
Special registers
Counter registers
Timer registers
Input/output registers
Link registers
Link relay registers
Auxiliary registers
Data registers
PC internal file registers
Expansion file registers (IC card)
e. Sample program
This sample ladder program issues a remote port loopback request to the Ethernet Port.
This program is executed by turning on the R0092 A point.
A user program must compare the transmitted and loopback data for equivalence.
Parameters:
12544:3100H, 00015:000FH
|R0092
|
1|-| |-+[12544 MOV W0903][00015 MOV W0904]----------------------------|
|
|
|
|
|
|
|
|
|
/* Designates the module and sets the CMD number. */
|
+[00485 MOV W0905]---------------------------------------------|
|
|
+[00004 MOV W0906][00000 MOV W0907]----------------------------|
|
/* Sets the loopback data length. */
|
/* Sets the send source register type and starting register
|number. */
|
|
|
|
|
+[00004 MOV W0908][00500 MOV W0909]----------------------------|
/* Sets the loopback destination register type and starting
|
|register number. */
|
|
|
|
|
|
|
|
+[00100 MOV W0910]---------------------------------------------|
|
|
/* Sets the response time limit. (10 seconds) */
|
+[341995909 DMOV W0912· W0911][01025 MOV W0913]-----------------|
/* Loopback destination IP address, message transmission UDP
|
|port number */
|
|
|
|
|
+[W0903 SEND W0914][RST R0092]---------------------------------|
/* Sets the request. */
7.5 Time Setting
The Ethernet Port internal time is set from the T2N. This information is used as the time
information in the Ethernet Port event trace.
¾ 129 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Time set request (using the SEND instruction)
a. Function
This request sets the Ethernet Port internal time from a user program.
b. Transfer parameters
A
3100H
Module designation
CMD number
A+1
A+2
A+3
A+4
CMD = 0018H
Month
Year
Day
Hour
Seconds
Minute
·
Enter the year, month, day, hour, minute, and seconds as BCD codes.
The date July 20, 1996 14:30:00 would be entered as:
A
3100H
0018H
0796H
1404H
0030H
12544
00024
01942
05124
00048
A+1
A+2
A+3
A+4
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
·
This request can be executed in run or standby mode.
The time set here is updated by the Ethernet Port internal timer, and thus may get out of
synchronization with the T2N time.
We recommend setting the Ethernet Port time once a day.
¾ 130 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. Sample program
This sample ladder program issues a time set request to the Ethernet Port.
This program is executed by turning on the R0508 A point.
Parameters: 12544:3100H, 00024:0018H, 01942:0796H, 05124:1404H, 00048:0030H
|R0508
R0608 |
1|-| |-----------------------------------------------------------( )--|
|
/* Time set request */
|R0608
|
2|-| |-+[12544 MOV RW000][00024 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
/* Designates the module and sets the CMD number.
*/
|
+[01942 MOV RW002][05124 MOV RW003][00048 MOV RW004]-----------|
|
|
/* Sets the year, month, day, hour, minute, and seconds. */
|
+[RW000 SEND RW010][RST R0508]---------------------------------|
/* Sets the request. */
|
¾ 131 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7.6 RAS Information Readout
This request reads out the Ethernet Port RAS information (internal error information and
phenomenon history) from a user program.
RAS information readout request (using the RECV instruction)
a. Function
This request reads out the Ethernet Port RAS information from a user program.
b. Transfer parameters
A
3100H
CMD = 0015H
DRID
Module designation
A+1
A+2
A+3
A+4
A+5
A+6
CMD number
RAS information storage register type
RAS information storage register start address
RAS request type
DRegNO
Kind
Start
Start position: Valid when Kind is 2 or 4.
Number of items read out: Valid when Kind is 4.
ReadCnt
(1) RAS information storage register type code
This code specifies the type of the register used to store the read out RAS information.
See figure 5.1 for the type codes that can be specified here.
(2) RAS information storage register start address
Specifies the start address for the registers specified by the local port register type code.
(3) RAS request type: specifies the type of RAS information read out
1: RAS counter..............LAN controller (line) information (See table 7.2.)
2: MIB information .......LAN controller interface, IP, TCP, and UDP information
(See tables 7.3 to 7.6.)
3: Maintenance data (Cannot be used.)
4: Event trace information (See table 7.7.)
5: RAS information clear
(4) Start position: Only valid when the readout request type is 2 (MIB information) or 4 (trace
information).
MIB information (2) ...... 0 = MIB_IF
1 = MIB_IP
2 = MIB_TCP
3 = MIB_UDP
Trace information (4)..... 0 to 160; 0 corresponds to the most recent information.
(5) Number of items read out: Only valid when the readout request type is 4 (trace
information).
1 to 30 items.
¾ 132 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
c. Status (See figure 4.3 for details on bits C, D, E and F.)
F
E
D
C
B
0
A
0
9
0
8
0
7
6
5
4
3
2
1
0
B
TermSTS
B+1
Detailed information (Only valid when TermSTS = 0BH.)
d. Important items
·
·
This request can be used in run and standby modes.
The read out RAS information is stored in the specified register area as shown below.
RAS information
word count
Specified register start address
¬
RAS information
A register area whose size is the size of the read out
RAS information plus one word must be allocated.
¬
·
·
A boundary error (TermSTS = 0AH) occurs if it is not possible to allocate an area that is the
size of the read out RAS information plus one word for the RAS information storage area.
A parameter error (TermSTS = 03H) occurs on any of the following transfer parameter
settings.
·
·
·
If the RAS request type (Kind) is out of range (a value other than 1 to 5).
If the start position (Start) is out of range (a value of 4 or larger) for MIB information.
If the start position (Start) is out of range (a value of 161 or larger) for event trace
information.
·
If the read count (ReadCnt) is out of range (a value of 31 or larger) for event trace
information.
¾ 133 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. Sample program
This sample ladder program issues a RAS information readout to the Ethernet Port.
This program is executed by turning on the R0505 A contact.
Parameters:
RAS storage registers: Starting at D0000.
RAS request type: Event trace information, reads out 30 items starting with the most
recent data.
12544:3100H, 00021:0015H
|R0505
R0605 |
1|-| |-----------------------------------------------------------( )--|
|
/* RAS information readout
*/
|R0605
|
2|-| |-+[12544 MOV RW000][00021 MOV RW001]----------------------------|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/* Designates the module and sets the CMD number.
*/
|
+[00004 MOV RW002][00000 MOV RW003]----------------------------|
|
|
/* Sets the RAS storage register type and start number
*/
|
+[00004 MOV RW004]---------------------------------------------|
|
|
/* Sets the RAS request type. */
|
+[00000 MOV RW005][00030 MOV RW006]----------------------------|
|
|
/* Sets the information readout start position and count. */
|
+[RW000 RECV RW010][RST R0505]---------------------------------|
/* Sets the request. */
|
¾ 134 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
f.
(1) RAS counters...........................LAN controller (line) information
Reads out 128 words of data using RAS information readout.
RAS information details
Table 7.2 RAS Counters
Symbol
Description
RAS_CNT [0]
RAS_CNT [1]
RAS_CNT [2]
Normal reception count
Bus read error (reception buffer read failure) count
Remote reset packet reception count
(Packets whose Ethernet header type was set to 0900H.)
RAS_CNT [3]
RAS_CNT [4]
RAS_CNT [5]
RAS_CNT [6]
RAS_CNT [7]
RAS_CNT [8]
Short packet (packet length under 60 bytes) reception count
Alignment error (The number of bits in the received data was not divisible by 8.) count
CRC error (received packet CRC check error) count
Overflow (Incoming packets discarded due to full receive buffer.) count
Remaining registers unused
·
·
·
·
·
·
·
RAS_CNT [127]
·
(2) MIB information: MIB_IF.......LAN controller interface information
Reads out 13 words of data using RAS information readout.
Table 7.3 MIB_IF
Symbol
Description
MIB_IF [0]
MIB_IF [1]
MIB_IF [2]
MIB_IF [3]
MIB_IF [4]
MIB_IF [5]
MIB_IF [6]
MIB_IF [7]
MIB_IF [8]
MIB_IF [9]
MIB_IF [10]
MIB_IF [11]
MIB_IF [12]
It is possible to use the interface number in this system
Reserved
Lower level layer of IP with interface type of protocol
Progress of time with changing states by the interface
Total number of octets (bytes) received by the interface
Number of non-broadcast/non-multicast packets transferred upstream
Number of broadcast/multicast packets transferred upstream
Number of packets discarded due to reception resource limitation
Number of packets discarded due to format errors
Number of packets sent to an undefined protocol
Total number of octets sent by the interface
Number of packets from upstream that were not broadcast or multicast packets
Number of packets from upstream that were broadcast or multicast packets
Packet:
A unit of data flowing on the transmission path. (See figure 7.1.)
¾ 135 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(3) MIB information: MIB_IP.......IP protocol information
Reads out 17 words of data using RAS information readout.
Table 7.4 MIB_IP
Symbol
Description
MIB_IP [0]
MIB_IP [1]
MIB_IP [2]
MIB_IP [3]
MIB_IP [4]
MIB_IP [5]
MIB_IP [6]
MIB_IP [7]
MIB_IP [8]
MIB_IP [9]
MIB_IP [10]
Indicate IP gateway in action or not action
Default TTL (Time to Live) of IP packet
Total number of IP datagrams received from the interface
Number of IP datagrams discarded due to format errors
Number of IP datagrams discarded due to incorrect delivery.
Number of IP datagrams sent out.
Number of IP datagrams sent to an undefined protocol
Number of IP datagrams transferred to upstream
Number of IP datagrams transferred from upstream
Number of IP datagrams discarded due to not exist route
The maximum number of seconds that maintained reception fragment and waiting
reassembly
MIB_IP [11]
MIB_IP [12]
MIB_IP [13]
MIB_IP [14]
MIB_IP [15]
MIB_IP [16]
Number of received IP fragments that required reassembly
Number of IP datagrams that were reassembled successfully
Number of IP datagrams for which reassembly failed
Number of IP datagrams that were fragmented successfully
Number of IP datagrams for which fragmentation failed an which were discarded
Number of created IP fragments
IP datagram: The IP header and IP data sections of a packet (See figure 7.1.)
IP fragment: Items that are divided into multiple IP datagrams when sending over 1500 bytes of
data.
Reassembly: Restoring data to its original form from fragmented IP datagrams
(4) MIB information: MIB_TCP .... TCP protocol information
Reads out 10 words of data using RAS information readout.
Table 7.5 MIB_TCP
Symbol
Description
MIB_TCP [0]
MIB_TCP [1]
MIB_TCP [2]
MIB_TCP [3]
MIB_TCP [4]
MIB_TCP [5]
MIB_TCP [6]
MIB_TCP [7]
MIB_TCP [8]
MIB_TCP [9]
The maximum of resent timeout (per ms)
Number of active open connections
Number of passive open connections
Number of times the connection open operation failed
Number of currently open connections
Number of segments received
Number of segments sent
Number of segments resent
Number of segments discarded due to format errors
Number of generated resets
Segment: The TCP header and TCP data block in an IP datagram (See figure 7.1.)
¾ 136 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(5) MIB information: MIB_UDP ... UDP protocol information
Reads out 4 words of data using RAS information readout.
Table 7.6 MIB_UDP
Symbol
Description
MIB_UDP [0]
MIB_UDP [1]
MIB_UDP [2]
MIB_UDP [3]
Number of UDP datagrams transferred upstream
Number of datagrams addressed to unused ports
Number of datagrams discarded due to format errors
Number of datagrams transferred from upstream
UDP datagrams: The UDP header and UDP data block in an IP datagram (See figure 7.1.)
(6) Event trace information
·
·
·
Record size:
16 bytes
160
Number of records:
Operation on overflow: Old information is updated. This means that it is always possible
to verify the 160 most recent event trace records.
·
Format:
Since this format is for Ethernet Port internal data, it is binary
codes. However, the time is expressed in BCD.
F
0
Event code
Detailed information 1
Detailed information 2
Detailed information 3
Detailed information 4
Month
Year
Day
Hour
Time information BCD
Seconds
Minute
¾ 137 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
·
Event trace item:
See table 7.7
Table 7.7 Event Trace Items
Event Detail information 1 (H) Detail information 2 (H) Detail information 3 (H) Detail information 4 (H) Content
code
0001H ROM error (0160)
RAM error (0260)
Initialization error
DPRAM error (0360)
0002H Program address
Error code
NMI (0000)
Read port contents
None
Watchdog timer flag
NMI occurrence factor
TRAP (0001)
Watchdog timer check
(0002)
Watchdog timer check
(0003)
Watchdog timer flag
0004H Power on (0001)
Reset switch (0002)
Start type
Software reset (0003)
0005H Initialization (0000)
Control request (0001)
0007H Task ID
Request code
Station status
Write port contents
Mode prior to change
Mode prior to change
Memory pool number
Mode after change
Mode after change
Error code
Mode change
(station status)
Instruction storage
buffer allocation error
0008H Task ID
Station status
Error code
Transmission prohibit
0009H Receive response code
T2N driver reception or
response code error
0100H CMD number (0011)
CMD number (0012)
Station status
Write port contents
T2N-Ethernet Port
interface
completion error
UDP port (0001)
Station status (0002)
Mode prior to change
Task start number
MAC setting flag
socket (0001)
UDP port number
Station status
CMD number (0013)
Mode after change
Task completion status
IP setting flag
0200H Task ID
Error code
Message transmission
completion error
bind (0002)
sendto (0003)
length (0004)
Length
recvfrom (0005)
Error code
0300H Task ID
Request code
Socket transmission
completion error
¾ 138 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Preamble (7 bytes)
Signal used to synchronize reception
SFD (Start Frame Delimiter) (1 byte)
Remote port address (6 bytes)
Local port address (6 bytes)
Ethernet type (2 bytes)
0800H:IP, 0806H:ARP
IP header (20 bytes)
Packets
UDP header
(8 bytes)
TCP header
(20 bytes)
traveling on the
transmission
path
(72 to 1526
bytes)
UDP data field
(up to 1472 bytes)
IP datagram
(46 to 1500
bytes)
Data fields in
the packets
traveling on the
transmission
path
TCP data field
(up to 1460 bytes)
IP data field
(up to 1480
bytes)
FCS (Frame Check Sequence) (4 bytes)
32-bit CRC code for the sections of the packet
other than the preamble, the SFD, and the FCS.
(Packet error detection)
Figure 7.1 Packet Format/IP Datagram
¾ 139 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8. Error Handling
This chapter describes the error analysis and recovery procedures for errors that occur while using
the Ethernet Port. Also refer to the T2N user's manual when recovering from Ethernet Port-related
errors.
8.1 LED Display
The Ethernet Port indicates its Ethernet Port status in the ERUN, ET/R and EACC LEDs.
Table 8.1 lists the state indicated by the ERUN LED. Note that the Ethernet Port operating mode
can be determined by the combination of the ERUN and ET/R LED display states as listed in table
8.2. User programs should read out and verify the down information error codes listed in table 8.2
using the READ instruction issued for the down information in the T2N interface buffer. (See
section 7.2, Down Information.)
Ethernet Port that fail (go to the down state) should be replaced.
Table 8.1 States Indicated by the ERUN LED
LED display
State
ERUN (Run)
Indicates the Ethernet Port normal/error (down mode) status.
Lit............. Ethernet Port normal
Off............ Ethernet Port error (down)
¾ 140 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 8.2 Ethernet Port Down States Indicated by ERUN, ET/R LED Combinations
LED combination displayed
State
ERUN lit
Ethernet Port operating normally in standby mode (parameter setup wait state)
The Ethernet Port goes to this state after power is first applied and after a reset.
Ethernet Port operating normally in run mode (transmission possible)
The Ethernet Port switches to this mode in response to an operating mode control
request.
(Parameter setup is required to switch the Ethernet Port to run mode.)
An error occurred during operation and the Ethernet Port is down.
ERUN off,
ET/R (Ethernet transmission/
Possible causes of the Ethernet Port going down
Down information error code
receive) blinking
Watchdog timeout occurred
Memory bus stall occurred
Trap occurred
0010
0020
0030
Jabbering timeout occurred
Semaphore acquisition error
Semaphore acquisition error
MBX reception error
0040
0500, 0501
0502, 0503
0504
MBX transmission error
No empty TCP resend queue
Acquired buffer was in use
Initial buffer acquisition error
0505
0506
0507
0508
Down mode due to the occurrence of an error during self diagnostics at power on.
Possible causes of the Ethernet Port going down
Down information error code
LAN controller check error
0050
0160
0260
0360
ROM BCC check found a discrepancy
System RAM area check error
T2N interface buffer check error
¾ 141 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
The EACC LED indicates when the T2N is accessing the Ethernet Port.
Table 8.3 States Indicated by the EACC LED
LED display
State
EACC (Access) Indicates whether or not the T2N is accessing the Ethernet Port.
·
·
·
Lit ........ The T2N is accessing the Ethernet Port.
Off ....... The T2N is not accessing the Ethernet Port.
Lights after Ethernet Port initialization completes when power is first applied. (Access starts.)
If this LED does not light after power is turned on:
Verify that the T2N is correctly connected to the base unit.
If this LED does not light at above, then the T2N itself is defective. Replace the T2N.
Supplement:
We recommend keeping spares on hand to minimize the time required to determine the
location of the fault using and to minimize the time required for recovery.
¾ 142 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8.2 Status (error status)
The status indicates the status during SEND/RECV instruction execution or after execution
completes. If a SEND/RECV instruction does not complete normally, refer to the detailed
information (Ethernet Port error response) and the status and review the instruction word format at
the T2N and Ethernet Port states (operating modes).
The detailed information is stored in the register following the completion status when the
completion status TermSTS value indicates a transmission error (0BH).
Figure 8.1 shows the structure of the status information. Tables 8.4 and 8.5 list the TermSTS
values, and table 8.6 lists the contents of the detailed information.
The status (error status) has the following structure.
B
Status
B + 1
Detailed information
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
Sport NO
TermSTS
Only on an error 0: Error occurred at local station.
1: Error occurred at remote station.
Socket identifier: Only valid for socket interface transmission
instructions. ("0" for other instructions)
status 0: Initial state
1: While send requesting
2: Send complete and while
waiting response
busy 0: Initial state
1: Transmission port busy
abn 0: Normal complete
1: Error complete
3: Receive complete
Figure 8.1 Status Structure
Table 8.4 TermSTS (Part 1)
Meaning
TermSTS Status
00H
01H
Normal complete
Register specification error
•
•
Occurs if a register other than XW, YW, W, LW, RW, D, F, T, C, or SW is
specified as the data storage register in one of the following requests.
Requests: RAS information readout, remote port loopback, UDP send/receive,
TCP send/receive, register read/write.
In a register read or write request, the request specified a read or write from a
T register to a register other than a T register.
(This also applies to C registers.)
02H
Response timeout
• Occurs if a response is not received within the specified time for a remote port
loopback or register read/write request.
¾ 143 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 8.5 TermSTS (Part 2)
TermSTS Status
03H Parameter error
Meaning
• Occurs if a value other than 3 is specified for the module ID.
• Occurs if a value other than 1 is specified for the channel number.
• Occurs if a command number other than one of the following is specified for a
SEND instruction.
000FH, 0011H - 0014H, 0018H, 0021H, 0031H, 0032H, 0034H, 0035H,
0037H, 0039H
• Occurs if a command number other than one of the following is specified for a
RECV instruction.
0015H, 0021H, 0033H, 0038H
• Occurs if a value other than 1 to 8 is specified for the socket identifier.
(See section 6.4 "Using the Ethernet Port Socket Interface".)
• Occurs if an incorrect parameter is specified in a RAS information readout
request.
(See section 7.6 "RAS Information Readout".)
• Occurs if an attempt to write is made when the remote registers were write
protected.
04H
Memory write protect
• Occurs if an attempt to read is made when the local registers were write
protected.
05H
06H
(Reserved)
• Occurs if the Ethernet Port is down.
Module error
• Occurs if the Ethernet Port is initializing.
Initialization in progress
• Occurs if a T2N internal timer times out.
Requests: UDP open, UDP send, UDP close, TCP send, TCP close
Transmission complete
timeout
• Occurs if the corresponding Ethernet Port is not installed.
07H
08H
No send channel (CH)
• Occurs if the local port IP address was specified for the remote destination IP
address.
Port address out of range
Requests: Remote port loopback, register read/write
• Occurs if either 0 words or 486 or more words were specified for either a
register read/write or a remote port loopback request.
09H
Incorrect transmission word
count
• Occurs if either 0 words or 1001 or more words were specified for a UDP/TCP
send/receive request.
• Occurs if the specified area (start address + register range) does not exist in
the T2N data storage registers.
Requests: RAS information readout, remote port loopback, UDP send/receive,
TCP send/receive, register read/write
0AH
0BH
Boundary error
Transmission error
• Occurs if the Ethernet Port returns an error response.
Detailed information (the Ethernet Port response status) is stored.
• Occurs if the T2N cannot access the Ethernet Port.
0CH
0DH
0EH
No I/O response
(Reserved)
• Occurs if a request is discarded when a T2N internal resource insufficiency
occurs due to increasing amounts of transfer data.
Send data capacity
exceeded
• Occurs if a T2N retransmission times out.
0FH
(Reserved)
When a transmission error (0BH) occurs, details of the Ethernet Port error response are stored in the
register following the status. (See table 8.6.)
¾ 144 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table 8.6 Detailed Information (Ethernet Port Error Responses)
Code
Error
Description
Normal complete
Local port fault
Local port standby
0001H Request completed normally
0002H The local port is in down mode
0003H Data transmission in standby mode (socket interface transmission or PC link
protocol transmission) was requested.
Timeout
0020H Timeout occurred during TCP open processing or receive processing, or during
UDP receive processing.
Length error
0030H Incorrect send data length
Port mode error
0040H One of the following requests was issued in a mode other than standby mode:
a. Parameter setup, b. MAC address setup, c. Reset
MAC/IP not set up
0050H
Occurs if the MAC address or IP address is not set up.
Transmission prohibited state
0060H • Occurs if a PC link request was issued from the T2N in run mode in the
message transmission prohibited state.
• Occurs if a socket open, close, send, or receive request is issued by the T2N
in run mode in the socket interface transmission prohibited state.
Format error
0070H Occurs when there is a format error in the request text.
0071H Port number error
0072H Request code error
0073H Time setting: Year
0074H Time setting: Month
0075H Time setting: Day
0076H Time setting: Hour
0077H Time setting: Minute
0078H Time setting: Second
Opened
0080H Occurs if an open request is issued for an already open socket.
0081H Occurs if send, receive, or close request is issued for an unopened socket.
0082H Occurs if the socket identifier is out of range (1 to 8).
Unopened
Incorrect socket identifier
Incorrect control request
specification
0083H Occurs if a request that was prohibited by an operating mode control request is
issued.
• Occurs if a run request is issued in run mode.
• Occurs if a standby request is issued in standby mode.
• Occurs if a run request and a standby request are issued at the same time.
LAN controller driver error
0090H Occurs if the setting of the local port IP address and port number in the area
reserved for transmission fails.
0091H Error in the TCP or UDP protocol (such as a transmission phase error)
0092H • Occurs if the setting of the remote port IP address in the remote port
information area (the NETDATA table) fails.
• Occurs if the remote port IP address network address differs from the local
port IP address network address.
Memory pool allocation failure
Port 2 task start failure
00A0H Occurs if the Ethernet Port internal OS fails to allocate memory.
00A1H Occurs if computer link or PC link socket identifier acquisition fails.
Broadcast specification error
00A2H Occurs if the remote IP address is broadcast on a remote port verification
request.
MAC address specification error 00B0H BCC error
00B1H
Occurs if an error occurs after address saving on a MAC setup request.
Insufficient resources error
00C0H Occurs if there are insufficient resources for UDP send or PC link transmission.
¾ 145 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8.3 T2N Special Relays and Registers
The Ethernet Port status information is reflected in the T2N special relays and special registers.
1. Special relays
Special relay
Name
Function
S000B
Ethernet Port error
(warning)
1: The installed Ethernet Port unit is down.
(The T2N continues to operate.)
0: Reset the system from a user program after resolving the
error in the down Ethernet Port.
2. Special registers
Special registers Name
SW063
CH1 station status
3. Station status format
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
DOWN
STBY
MTEN
TEST
INZ
RUN
STEN
·
·
Bit F: DOWN (down)...........................................1: Down mode, 0: Other than down mode
Bit E: INZ (initialization).....................................1: Initialization in progress
0: Initialization completed
·
Bit D: STBY (standby).........................................1: Standby mode
0: Other than standby mode
·
·
·
·
Bit C: RUN (run)..................................................1: Run mode, 0: Other than run mode
Bit 5: MTEN (Message transmission)..................1: Enabled, 0: Prohibited
Bit 4: STEN (socket interface transmission).........1: Enabled, 0: Prohibited
Bit 0: TEST (test).................................................1: Test function execution in progress
¾ 146 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8.4 Socket Interface Information
The information for the eight socket interface sockets held by the Ethernet Port can be read out
with the T2N READ instruction. (See Section 6.3 Socket Interface Information.) The Ethernet Port
holds five words of socket status information for each socket.
·
·
·
·
Remote port TCP/UDP port number
Remote port IP address
TCP/UDP port number for this socket
Socket status
Table 8.7 lists the structure of the socket interface information and the extended memory area
addresses.
Table 8.7 Socket Interface Information
Socket identifier
1
2
3
4
5
6
7
8
Remote port number (TCP only)
Remote port IP address (TCP only)
0F4BH 0F53H 0F5BH 0F63H 0F6BH 0F73H 0F7BH 0F83H
0F4CH 0F54H 0F5CH 0F64H 0F6CH 0F74H 0F7CH 0F84H
0F4DH 0F55H 0F5DH 0F65H 0F6DH 0F75H 0F7DH 0F85H
Local port TCP/UDP port number
Socket status
0F4EH 0F56H 0F5EH 0F66H 0F6EH 0F76H 0F7EH 0F86H
0F4FH 0F57H 0F5FH 0F67H 0F6FH 0F77H 0F7FH 0F87H
For UDP sockets, the remote port number and IP address data are invalid.
The socket status has the following structure.
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
TCP
AOPEN CONN RCLOSE
UDP POPEN RCV NOACK
Bit no. Bit
Condition under which the bit is set to 1
TCP used by the socket
Condition under which the bit is reset to 0
The socket closed in response to a close request
The socket closed in response to a close request
The socket closed in response to a close request
The socket closed in response to a close request
F
E
D
C
TCP
UDP
UDP used by the socket
AOPEN TCP socket in active open state
POPEN TCP socket in passive open state or UDP
socket in open state
B
CONN
TCP connection established
Disconnected by the local port with a close request
Disconnected by the remote port
No received text
A
9
RCV
Received text present
RCLOS An established TCP connection disconnected The socket closed in response to a close request
by the remote port
E
8
NOACK No response received from the remote port for The socket closed in response to a close request
a local port send operation in a state where a
TCP connection was established, and the TCP
resend function resulted in a timeout (because
the remote port was down, etc.).
If the wait time exceeds the set value during a When a TCP active open request is reissued.
TCP active open request.
This state does not occur for TCP passive
open requests.
A socket status in which neither AOPEN nor POPEN is set to 1 indicates that the socket is in the
closed state.
¾ 147 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8.5 Troubleshooting
1. If the Ethernet Port fails to come up normally (i.e., does not reach standby state.)
If the Ethernet Port is functional, then the Ethernet Port can be initialized and brought to the
standby state (with the ERUN LED lit) by applying power or by issuing a reset request.
START
No
No
Apply the rated line voltage to the primary side of
the power supply module.
Is power supplied to the T2N power
supply module?
Yes
Is the T2N correctly mounted in the
base unit?
Insert the PU235N/245N into its slot correctly.
Yes
Replace the PU235N/245N.
Read out the down information, and send both
that information and the PU235N/245N to
Toshiba.
2. If the Ethernet Port fails during operation
Recovery Replace the PU235N/245N.
procedure
Before replacing the PU235N/245N, read out the down information, and then send both that information
and the PU235N/245N to Toshiba.
3. If a SEND or RECV instruction fails complete
Recovery (1) Verify that the inputs of function block are held in the on state until the instruction completes.
procedure
(2) Determine whether the user program is writing to the status register while the instruction is executing.
¾ 148 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
4. If the Ethernet Port fails to enter run mode
This section assumes that the Ethernet Port has come up normally up to this point. Note that the
parameters must be set up with a parameter setup request before issuing the operating mode
control request used to switch the Ethernet Port from standby mode to run mode.
a. Parameter setup request
START
Execute a parameter setup request that sets up
the IP address and the message transmission
UDP port number.
No
No
Is the parameter setup request
executed?
Yes
Verify the status using the procedure described in
the item 3 " If a SEND or RECV instruction fails
complete" on page 148.
Does the SEND instruction
complete?
Yes
Check the status and resolve the
error.
To the operating mode control request flowchart
END
¾ 149 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. Operating mode control request
START
No
No
No
Set up correct specification information and issue
an operating mode control request.
Is an operating mode control
request executed?
Yes
Verify the status using the procedure described in
the item 3 " If a SEND or RECV instruction fails
complete" on page 148.
Does the SEND instruction
complete?
Yes
The Ethernet Port internal MAC address has
been corrupted.
Replace the PU235N/245N.
Have the parameters not been
set up yet?
Yes
Check the status and resolve the
error.
END
¾ 150 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5. If computer link protocol transmission fails
a. Host computer side (main port)
START
Is the transmission destination IP
No
Verify the slave Ethernet Port transmission
destination IP address.
address set to that of the slave
Ethernet Port?
Yes
Verify the slave Ethernet Port message
transmission UDP port number.
Supplement:
Is the transmission destination
No
message transmission UDP port
number correct?
Remember that there are separate send and
receive ports that each have their own
message transmission UDP port number.
Yes
No
No
Did the computer link protocol
return without errors?
Check the computer link protocol format.
Yes
1.Recheck the slave port IP address and
message transmission UDP port numbers.
Does a response come back if a
ping is issued to the slave Ethernet
Port?
2.Verify that there is no router on the network.
3.Check the network verification items.
Yes
Check the network verification
items, i.e., the items unrelated to
the Ethernet Port.
END
¾ 151 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. Ethernet Port side (slave port)
START
Set the Ethernet Port to run + message
transmission enabled using an operating mode
control request.
Is the station status such that run +
message transmission is enabled?
No
No
Yes
1. Check the main port side IP address.
2. Verify that there is no router on the network.
3. Check the network verification items.
Does a response come back if a
ping is issued to the host
computer?
Yes
Is the error counter read out from
the RAS information constant (i.e.,
not being incremented)?
(Use RAS information readout to
determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error:
Short packet
Yes
CRC error
END
¾ 152 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
6. If PC link protocol transmission fails
a. Main port side Ethernet Port
START
Verify the status using the procedure described in the
item 3 " If a SEND or RECV instruction fails complete"
on page 148.
No
No
Does the SEND/RECV instruction
complete?
Yes
Is the station status such that
run + message transmission is
enabled?
Was there a response timeout?
(TermSTS = 02H)
Yes
Yes
No
Set the Ethernet Port to run + message
transmission enabled using an
Check the status and
resolve the error.
operating mode control request.
Is the transmission destination IP
address set to that of the slave
Ethernet Port?
No
No
Verify the slave Ethernet Port transmission destination
IP address.
Yes
Verify the slave Ethernet Port message transmission
UDP port number.
Supplement:
Is the slave port message
transmission UDP port correct?
Remember that there are separate send and
receive ports that each have their own message
transmission UDP port number.
Yes
1. Recheck the slave port IP address and message
transmission UDP port numbers.
2. Verify that there is no router on the network.
3. Check the network verification items.
Does a response come back if a
ping is issued to the slave Ethernet
Port?
No
No
Yes
Is the error counter read out from
the RAS information constant (i.e.,
not being incremented)?
It is possible that there is an abnormality on the
network itself. Check the network verification items.
(Use RAS information readout to
determine this.)
RAS error counters: Alignment error:
Short packet
Yes
CRC error
END
¾ 153 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. Ethernet Port side (slave port)
START
Set the Ethernet Port to run + message
transmission enabled using an operating mode
control request.
Is the station status such that run +
message transmission is enabled?
No
No
Yes
1. Check the main port side IP address.
2. Verify that there is no router on the network.
3. Check the network verification items.
Does a response come back if a
ping is issued to the main Ethernet
Port?
Yes
Is the error counter read out from
the RAS information constant (i.e.,
not being incremented)?
(Use RAS information readout to
determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error:
Short packet
Yes
CRC error
END
¾ 154 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
7. If transmission using UDP sockets fails
a. Open and close requests
START
Verify the status using the procedure described in
the item 3 " If a SEND or RECV instruction fails
complete" on page 148.
No
No
Does the SEND instruction
complete?
Yes
Set the Ethernet Port to run + socket
transmission enabled using an operating mode
control request.
Is the station status such that run +
socket transmission is enabled?
Yes
Check the status and resolve the
error.
END
¾ 155 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. Send request
START
Verify the status using the procedure described in
the item 3 " If a SEND or RECV instruction fails
complete" on page 148.
No
No
Does the SEND instruction
complete?
Yes
Set the Ethernet Port to run + socket
transmission enabled using an operating mode
control request.
Is the station status such that run +
socket transmission is enabled?
Yes
Is the transmission destination IP
address set to that of the remote
Ethernet Port?
No
Verify the remote Ethernet Port transmission
destination IP address.
Yes
No
No
Open UDP ports on the local port and remote
ports.
Are the UDP ports on the local and
remote ports opened?
Yes
Does the status indicate normal
completion?
Resolve the problem by referring to the status.
Yes
1. Recheck the remote port IP address and
message transmission UDP port numbers.
Does a response come back if a
ping is issued to the remote
Ethernet Port?
No
2. Verify that there is no router on the network.
3. Check the network verification items.
Yes
Is the error counter read out from
the RAS information constant (i.e.,
not being incremented)?
(Use RAS information readout to
determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error:
Short packet
Yes
CRC error
END
¾ 156 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
c. Receive request
START
Verify the status using the
procedure described in the item
3 " If a SEND or RECV
instruction fails complete" on
page 148.
No
No
No
No
No
Did the RECV instruction
complete?
Was the wait time set to
unlimited?
Yes
Yes
¬
Set the Ethernet Port to run +
socket transmission enabled
using an operating mode control
request.
Did the instruction time out?
TermSTS = 0BH
Is the station status such that
run + socket transmission is
enabled?
Details = 0020H
Yes
Yes
¬
Open UDP ports on the local
port.
Is the local port open?
Yes
Resolve the problem by referring
to the status.
No
No
Is the remote port
transmitting?
Transmit a message at the
remote port.
Yes
Are the remote port IP
address and UDP port
number correct?
Verify the remote port IP address and UDP port
number.
Yes
1. Recheck the remote port IP address and
message transmission UDP port numbers.
2. Verify that there is no router on the network.
3. Check the network verification items.
Does a response come back
if a ping is issued to the
remote port?
No
Yes
Is the error counter read out
from the RAS information
constant (i.e., not being
incremented)?
(Use RAS information
readout to determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error
Short packet
Yes
CRC error
END
¾ 157 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
8. If Transmission Using TCP Sockets Fails
When troubleshooting TCP sockets, also refer to the section "TCP socket interface notes" in
section 6.2, Ethernet Port Socket Interface Usage Notes.
a. Open request
START
Verify the status using the
procedure described in the
item 3 " If a SEND or RECV
instruction fails complete"
on page 148.
No
No
No
No
Did the SEND instruction
complete?
Was the wait time set to
unlimited?
Yes
Yes
¬
Set the Ethernet Port to run
+ socket transmission
enabled using an operating
mode control request.
Did the instruction time out?
TermSTS = 0BH
Is the station status such that
run + socket transmission is
enabled?
Details = 0020H
Yes
Yes
¬
Resolve the problem by referring
to the status.
Is the program attempting to
issue an active open to a
socket in the passive open
state?
Decide which role each socket will play when
establishing a connection between a pair of
sockets.
No
Yes
Are the remote port IP
address and TCP port
number correct?
Verify the remote port IP address and TCP port
number.
No
No
Yes
1. Recheck the remote port IP address and
message transmission TCP port numbers.
2. Verify that there is no router on the network.
3. Check the network verification items.
Does a response come back
if a ping is issued to the
remote port?
Yes
Is the error counter read out
from the RAS information
constant (i.e., not being
incremented)?
(Use RAS information
readout to determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error
Short packet
Yes
CRC error
END
¾ 158 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. Close request
START
Verify the status using the procedure described in the
item 3 " If a SEND or RECV instruction fails
complete" on page 148.
No
No
Does the SEND instruction
complete?
Yes
Set the Ethernet Port to run + socket transmission
enabled using an operating mode control request.
Is the station status such
that run + socket
transmission is enabled?
Yes
Resolve the problem by
referring to the status.
END
¾ 159 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
c. Send request
START
Verify the status using the procedure described in the
item 3 " If a SEND or RECV instruction fails complete"
on page 148.
No
No
Does the SEND instruction
complete?
Yes
Is the station status such that
run + socket transmission is
enabled?
Set the Ethernet Port to run + socket transmission
enabled using an operating mode control request.
Yes
No
1
Was a TCP connection
established?
Open UDP ports on the local and remote ports.
Yes
Is the socket status
RCLOSE bit?
Close the socket.
Status: Unopened (TermSTS = 0BH, details = 0081H)
0
1
Is the socket status
NOACK bit?
Close the socket.
Status: Protocol error (TermSTS = 0BH, details = 0091H)
0
Does the status indicate a
timeout error?
No
Check the status and resolve the error.
TermSTS = 0BH
Details = 0020H
Yes
·
·
Requests cannot be accepted due to network congestion.
® Redesign the user program.
Transmission becomes impossible when the receive side user program accumulates data.
® Check the receive side processing.
1. Recheck the remote port IP address and message
Does a response come back
transmission TCP port numbers.
2. Verify that there is no router on the network.
3. Check the network verification items.
No
if a ping is issued to the
remote port?
Yes
Is the error counter read out
from the RAS information
constant (i.e., not being
incremented)?
(Use RAS information
readout to determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error
Short packet
Yes
CRC error
END
¾ 160 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
d. Receive request
START
Verify the status using the
procedure described in the
item 3 " If a SEND or RECV
instruction fails complete" on
page 148.
No
No
No
No
No
Did the RECV instruction
complete?
Was the wait time set to
unlimited?
Yes
Yes
¬
Set the Ethernet Port to run
+ socket transmission
enabled using an operating
mode control request.
Did the instruction time out?
TermSTS = 0BH
Is the station status such that
run + socket transmission is
enabled?
Details = 0020H
Yes
Yes
¬
Establish a connection with
the remote port.
Was a connection
established?
Yes
Resolve the problem by referring
to the status.
No
No
Is the remote port
transmitting?
Transmit a message at the
remote port.
Yes
1. Recheck the remote port IP address and
message transmission TCP port numbers.
2. Verify that there is no router on the network.
3. Check the network verification items.
Does a response come back
if a ping is issued to the
remote port?
Yes
Is the error counter read out
from the RAS information
constant (i.e., not being
incremented)?
(Use RAS information
readout to determine this.)
It is possible that there is an abnormality on the
network itself. Check the network verification
items.
No
RAS error counters: Alignment error
Short packet
Yes
CRC error
END
¾ 161 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
9. Network check items (Ethernet Port)
Check items
Countermeasure
Transmission
medium
installation
10BASE-T
1. Is the twisted pair cable connected
between the Ethernet Port and HUB?
1. Verify the twisted pair cable connections between the
Ethernet Port and HUB.
2. How long (in meters) are the twisted pair
cable (i.e. segment lengths)?
2. The maximum segment length for 10BASE-T cabling is
100 meters.
Network cable 1. Do all ports on the network respond to ping 1. Inspect the twisted pair cables for missing termination
check
correctly?
resistors and damage.
2. Is the collision frequently happen?
Can you confirm the table indicating the
collision?
2. Since network loading is heavy:
•
•
Transmission efficiency can be degraded (TCP), and
There is an increased possibility of packet loss (UDP).
Therefore, the circuit usage conditions should be reviewed.
3. Are the error counters read out from the
RAS information increasing as time
passes?
3. Check whether there are any defective (or substandard)
connections on the cables and HUB.
Check for the presence of noise sources in the vicinity of
the network cables.
Error counters: Alignment error, Short
packet, CRC error
¾ 162 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
9. Installation and Wiring
9.1 Installation Environment and Base Unit Mounting
The PU235N/245N must be used in the installation environment described in section 4.1,
"Installation Environment," of the T2N User's Manual - Hardware. Also, the PU235N/245N panel
must be installed in conformance with the notes and cautionary advice presented in section 4.1,
"Installation Environment."
CAUTION
1. Only use this equipment in the environment described in the T2N User's Manual - Hardware.
Use in any other environment can cause electrical shocks, fires, failures, and malfunctions.
2. Mount this equipment according to the mounting method specified in the T2N User's Manual -
Hardware.
Mounting in any direction other than the specified direction, or defective or inadequate mounting,
can result in the equipment falling, fires, failures, and malfunctions.
¾ 163 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
9.2 Network Wiring
See section 3.2, "Network Wiring Equipment," for details on the equipment that makes up the
network. This section presents an outline of the wiring laid inside the control panel and outside the
control panel. This section also presents individual notes on the twisted pair cables used, the
coaxial cables, the AUI cables, and the MAUs.
Basic points in laying out a network
CAUTION
1. When laying network cable, take adequate safety measures and perform all operations in
accordance with the relevant standards. See the ISO/IEC8802-3 standard for details on laying
networks.
2. We strongly recommend hiring a qualified contractor who has specialized knowledge about safety
precautions and standards.
3. Avoid installing 10BASE5, 10BASE2 or 10BASE-T networks in environments that have high noise
levels. If this is unavoidable, adopt the noise prevention measure described below.
1. Overview of wiring outside the control panel
a. Layout environment and required work
Lay out cables in a manner appropriate for the environment. The steps listed in the following table
are generally required.
Table 9.1 Wiring Environment and Work Operations
Environment in which cable is laid
Work operations
Major categories
Minor categories
Locations where cables will
not be damaged
Installation without protective pipes
Installation with protective pipes
Installation with protective pipes
Location where cables could Places where there is normally motion
be damaged
of people and objects
Places where cables may be influenced Installation with protective metal pipes
by humidity, chemicals, oils, or heat
Places where cables may be damaged Installation with protective pipes
by rats, mice, or other animals.
Places where cables may receive
strong mechanical shocks, or where
heavy physical loads may be placed on
the cables.
Installation with protective metal pipes
Locations where there is a
likelihood of electromagnetic
interference
Protective installation and separation
of cables.
Installation with protective metal pipes
The term "installation with protective pipes" means that either metal or PVC pipes may be used.
¾ 164 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
b. Overview of wiring without protective pipes
(1) To protect the cables, cables should be passed through flooring ducts or wire protecting cable
covers should be used.
Note that these cables should not be laid adjacent to cables carrying high currents.
(2) Lay cables in gaps in the walls so that they will not be damaged, and run cables under the
flooring under equipment so that electromagnetic interference will not occur.
(3) Observe the applicable cable separation standards when running cables in parallel with, when
crossing, or when approaching low-voltage indoor power lines.
(4) Fasten cables every 3 meters so that the cables are not damaged when attaching cables to
walls to position the away from the floor, or when running cables vertically.
(5) When bending cables, be sure that the radius of curvature of the bend does not exceed the
bending limit for the cable used.
c. Notes on piped cabling
(1) Do not run coaxial cable and lines carrying high currents in the same pipe.
(2) When bending pipes, do not bend pipes to an angle sharper than 90 degrees.
(3) When bending pipes, the radius of curvature must be at least 6 times the internal diameter of
the pipe, and must be no smaller than the minimum radius of curvature for bending of the
enclosed cables.
(4) Ground metal pipes.
d. Separation from other wiring
As a general principle, coaxial cable should be separated by at least 2 meters from power lines and
equipment that generates electric or magnetic fields. If it is difficult to achieve a separation of 2
meters, look up the actual voltage and current of the induction source in the table below to
determine the separation distance. However, since transmitted signals are weak signals, restrict
induction sources to no more than 440 volts and 100 amperes.
Table 9.2 Recommended Minimum Separation Distance
Induction source Minimum separation for parallel lines (mm)
Voltage, current
Over 440 V
Up to 440 V
Up to 220 V
Up to 110 V
Up to 60 V
Over 100 A Up to 100 A Up to 50 A Up to 10 A
2000
2000
2000
2000
2000
2000
600
600
600
500
2000
600
600
500
300
2000
600
500
300
150
¾ 165 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Considering resistance to noise, we recommend using either covered metal cable ducts or
protective steel pipe. Table 9.3 lists the recommended minimum separations for parallel lines in
this case.
Table 9.3 Recommended Minimum Separation Distance
(Covered metal ducts and metal pipe) (Units: mm)
Cable installation method
Parallel separation
Covered metal ducts or metal pipe
Up to Up to Up to
Up to
Up to
501 meters
10 meters 25 meters 100 meters 200 meters 500 meters or over
Power Up to 125 V, up to 10 A
10
10
10
50
50
150
200
250
100
200
250
250
200
250
250
250
250
250
250
250
cable
Up to 250 V, up to 50 A
Up to 400 V, up to 100 A
Up to 500 V, up to 200 A
50
100
200
100
Levels exceeding the above At least 500
When using cable ducts, install steel separators to separate power cables from coaxial cables as
shown in the figure below.
Metal duct
Separator
Power cable
Instrumentation power lines
Coaxial cable
Solenoid and other control signals
Figure 9.1 Duct Internal Layout Example
When laying cables in a pit, use separators in the same manner as when ducts are used.
Separator (steel)
Signal lines
Power source
Ground
(with a resistance to ground of 100W or less)
Figure 9.2 Pit Internal Layout Example
¾ 166 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
e. Wiring routes
The desirable routes for laying the transmission cable can be ordered as follows.
(1) Using a dedicated route
(2) Using a route dedicated to computer system related lines
(3) Using a route dedicated to general measurement equipment
(4) Using a route dedicated to plant control related lines
2. Overview of panel internal wiring
When 10BASE-T is used with the Ethernet Port, twisted pair cable is connected to the Ethernet
Port. Keep the following points in mind when wiring inside the control panel.
a. Wiring path
Use the weak-signal route within the panel for wiring the coaxial cable.
In particular, keep the coaxial cable at least 50 cm away from power supply cables.
b. Securing coaxial cable
Secure the coaxial cable with clamp materials so that the weight of the cable is not applied to the
cable's connectors.
Remember that the cable not must be bent beyond its minimum bending radius.
3. Notes on laying and wiring twisted pair cable (10BASE-T)
a. Only use this twisted pair cable in boards. Consult with a specialist contractor if twisted pair
cable must be routed out of boards.
4. Notes on laying and wiring 10BASE2 and 10BASE5 coaxial cable
a. Only use this coaxial cable indoors. Consult with a specialist contractor if coaxial cable must
be routed outdoors.
b. Connect terminators to both ends of the coaxial cable.
c. Insulate all exposed metal parts other than the coaxial cable installation point from ground
and other metal parts.
10BASE5: Plugs, adapters, terminators
10BASE2: BNC plugs, adapters, terminators, T connectors.
d. For safety, ground, at a single point, the coaxial cable's external conductor to a point with a
resistance to ground of 100 W or less.
Also, prepare a dedicated network system ground that is not shared with other equipment.
e. Contact the manufacturer of the cable with regard to the physical characteristics value of the
coaxial cable allowable minimum bending radius.
f. Avoid locations with high temperature, high humidity, dust, or oil mist when installing coaxial
cable.
¾ 167 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
5. Notes on laying and wiring AUI cable
a. When connecting the AUI cable to the MAU connectors, use the slide latches to secure the
connectors firmly.
b. Contact the manufacturer of the cable with regard to the physical characteristics value of the
AUI cable allowable minimum bending radius.
c. Avoid locations with high temperature, high humidity, dust, or oil mist when installing AUI
cable.
6. Notes on MAU (10BASE5) installation
a. Attach MAUs at the 2.5-meter separated marks on the coaxial cable.
b. Since the procedure for attaching MAUs to coaxial cable differs between manufacturer, refer
to the MAU user's manual.
c. Since the coaxial cable is grounded, the MAU main unit should be mounted insulated from
ground.
d. Do not install MAUs in the vicinity of equipment that generates electrical noise. If a MAU
must be installed in such a location, provide a MAU enclosure box, and mount the MAU
inside the box insulated from that box. Be sure to ground the MAU enclosure box.
e. Avoid locations with high temperature, high humidity, dust, or oil mist when installing MAU
cable.
¾ 168 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Appendix 1 Maintenance and Inspection
Periodic Inspection
Check the following items periodically, once every six months. Also, check these points if any
surrounding conditions or any aspect of the environmental changes.
Table A.1 Periodic Inspection Items
Inspection item
Inspection
Criterion
Resolution procedure
Power supply systems
Measure the power-supply
Voltages must be within the Adjust the input voltages to be
(T2N power supply/MAU voltage at the power-supply
stipulated ranges.
within the stipulated ranges.
power supply)
terminals.
Check for loose screws at the There must be no
Turn off (remove power from)
the power supply and tighten
down the screws with a
screwdriver.
power-supply terminals.
looseness.
Check for damage to the
power-supply cables.
There must be no damage. Turn off (remove power from)
the power supply and replace
the damaged cables.
Installation state
Is the module firmly locked in
place?
There must be no
looseness or play.
First press the module.
Transmission cable
connections
10BASE5: Are the AUI cables There must be no
First press the cable firmly into
the connector and then slide
the slide latch to the locked
position.
firmly locked in place?
looseness or play.
The 10BASE5 connector
slide latches must be in
their locked positions.
10BASE2: Are the coaxial
cables firmly locked in place?
There must be no
looseness or play.
First press the T-connector
firmly into position and then
engage the T-connector lock.
The T-connector locks
must be engaged.
10BASE-T: Are the twisted pair There must be no
First press the twisted pair
cables firmly locked in place?
looseness or play.
cable into modular connector.
The modular connector
locks must be engaged.
Transmission cable wiring 10BASE5/2/-T: Check for
There must be no damage. Stop the system, turn off
(remove power from) the power
supply and replace the
(See section 9.4,
"Network Wiring".)
damage to the cables.
damaged cables.
Are the cables installed near
any power or other cables?
There must be no power or Separate the cables from the
other similar cables in the power lines.
vicinity.
Shield the cables.
Ambient conditions
Verify that temperature,
humidity, vibration, and dust
levels are all within the
stipulated ranges.
The values must be within Improve the environment so
the ranges from the
general specifications for
the module.
that all aspects are within the
ranges stipulated in the
specifications.
¾ 169 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
CAUTION
1. Always turn off the power before attaching or removing modules, the terminal block, or cables.
Electrical shock, malfunctions, and breakdowns are possible if these operations are performed with
the power on.
2. To keep the system operating normally at all times and to prevent trouble in advance, perform daily
inspections, periodic inspections, and cleaning.
3. Refer to the section on error recovery in this document if the Ethernet Port does not operate
correctly.
Contact your local Toshiba dealer or service representative if a breakdown occurs, and request that
the module be repaired or returned to Toshiba.
Operation and safety cannot be guaranteed if service is performed by anyone other than an
authorized Toshiba service representative.
4. Do not disassemble or modify the module hardware, and do not modify the module software.
Breakdowns or malfunctions may lead to fire, electrical shock, or injury.
5. When measuring the voltages at the module terminal block during inspections, use adequate
caution.
There is a danger of electrical shock during this operation.
6. Only exchange modules with the power completely off.
Exchanging modules with the power on can lead to malfunctions, breakdowns, and electrical shock.
7. Do not continue to use the module if it emits smoke or unusual odors, or if it is in an abnormal state
of any type.
Using the module in an abnormal state can lead to malfunctions, breakdowns, and electrical shock.
In such cases, immediately turn of all power and contact your local Toshiba dealer or service
representative.
Customers should never attempt repairs or modifications to this equipment themselves: repair and
modification operations are extremely dangerous.
¾ 170 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Appendix 2 Request Code Table
This table lists the request codes (CMD) used with SEND/RECV instructions sent to the Ethernet
Port. Refer to the section/item indicated in the reference column in the table for detailed
explanations of the request codes.
Table A.2 Instructions (Requests) to the Ethernet Port
Request
Function
Instruction CMD/Class Reference
Reset request
Resets the Ethernet Port.
SEND
SEND
SEND
0011H/(1)
0012H/(1)
0013H/(1)
Section 4.3
Section 4.4
Section 4.5
Parameter setup request Sets up the Ethernet Port parameters.
Operating mode control
request
Sets the operating mode.
Remote port verification Verifies the existence of another port on the
request network.
SEND
RECV
SEND
0014H/(1)
0015H/(1)
0018H/(1)
0021H/(2)
0021H/(2)
000FH/(2)
Section 7.3
Section 7.6
Section 7.5
Section 5.4
Section 5.3
Section 7.4
RAS information readout Reads out the Ethernet Port RAS information.
request
Time set request
Sets the Ethernet Port internal clock
Time information for event trace
Register read request
(PC link function)
Reads register data from remote T2N into registers RECV
in the local T2N.
Register write request
(PC link function)
Writes register data from the local T2N to registers SEND
in remote T2N.
Remote port loopback
request
Performs a loopback test with another Ethernet
Port on the network.
SEND
UDP open request
UDP send request
UDP receive request
UDP close request
TCP open request
TCP send request
TCP receive request
TCP close request
Opens a UDP socket.
SEND
SEND
RECV
SEND
SEND
SEND
RECV
SEND
0031H/(3)
0032H/(3)
0033H/(3)
0034H/(3)
0035H/(3)
0037H/(3)
0038H/(3)
0039H/(3)
Section 6.4 (1)
Section 6.4 (2)
Section 6.4 (3)
Section 6.4 (4)
Section 6.4 (5)
Section 6.4 (6)
Section 6.4 (7)
Section 6.4 (8)
Transmits data from an open UDP socket.
Reads out data received by an open UDP socket.
Closes (terminates) an open UDP socket.
Opens a TCP socket.
Transmits data from an open TCP socket.
Reads out data received by an open TCP socket.
Closes (terminates) an open TCP socket.
·
The request code (CMD) types (1) to (3) have the following meanings.
Class (1) is module control, (2) is PC link protocol transmission, and (3) is socket interface
transmission.
·
·
·
For a single Ethernet Port, it is not possible to request another class (1) CMD while a class
(1) CMD is executing. This is also true for class (2) CMDs. If such a request is issued, the
status will be transmission port busy, and the request will go to the wait state.
For a single Ethernet Port, when requesting a class (3) CMD, it is not possible to request
another class (3) command for a socket for which an instruction is executing. If such a request
is issued, the status will be transmission port busy, and the request will go to the wait state.
There are eight sockets, and each can independently accept and execute a class (3) instruction.
¾ 171 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Appendix 3 Status Table
Figure a.1 lists the completion status and detailed information stored in the specified registers
during SEND/RECV instruction execution or at instruction completion. Tables A.3 and A.4 list
the contents of the TermSTS completion status, and table A.5 lists the contents of the detailed
information (the Ethernet Port error response) loaded into the next register after the register used
for the completion status.
F
E
D
C
B
A
9
8
7
6
5
4
3
2
1
0
B
Sport NO
TermSTS
Only on an error 0: Error occurred at local port.
1: Error occurred at remote port.
Socket identifier:Only valid for socket interface transmission
instructions. ("0" for other instructions)
status 0: Initial state
busy 0: Initial state
1: Transmission port busy
1: While send requesting
2: Send complete and while
waiting response
abn 0: Normal complete
1: Error complete
3: Complete
Figure A.1 Status Structure
Table A.3 TermSTS (Part 1)
Meaning
TermSTS Status
00H
01H
Normal complete
Register specification error
•
Occurs if a register other than XW, YW,W, LW, RW, D, F, T, C, or SW is
specified as the data storage register in one of the following requests.
Requests: RAS information readout, remote port loopback, UDP send/receive,
TCP send/receive, register read/write.
•
•
In a register read or write request, the request specified a read or write from a
T register to a register other than a T register.
(This also applies to C registers.)
02H
03H
Response timeout
Parameter error
Occurs if a response is not received within the specified time for a remote port
loopback or register read/write request.
•
•
•
Occurs if a value other than 3 is specified for the module ID.
Occurs if a value other than 1, 2, 3, or 4 is specified for the channel number.
Occurs if a command number other than one of the following is specified for a
SEND instruction.
000FH, 0011H - 0014H, 0018H, 0021H, 0031H, 0032H, 0034H, 0035H,
0037H, 0039H
•
Occurs if a command number other than one of the following is specified for a
RECV instruction.
0015H, 0021H, 0033H, 0038H
•
•
Occurs if a value other than 1 to 8 is specified for the socket identifier.
(See section 6.4 "Using the Ethernet Port Socket Interface".)
Occurs if an incorrect parameter is specified in a RAS information readout
request.
(See section 7.6 "RAS Information Readout ".)
¾ 172 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table A.4 TermSTS (Part 2)
Meaning
TermSTS Status
04H
Memory write protect
•
Occurs if an attempt to write is made when the remote registers were write
protected.
•
Occurs if an attempt to read is made when the local registers were write
protected.
05H
06H
(Reserved)
Module error
•
Occurs if the Ethernet Port is down.
Initialization in progress
•
•
Occurs if the Ethernet Port is initializing.
Transmission complete
timeout
Occurs if a T2N internal timer times out.
Requests: UDP open, UDP send, UDP close, TCP send, TCP close
07H
08H
No send channel (CH)
•
•
Occurs if the corresponding Ethernet Port is not installed.
Port address out of range
Occurs if the local port IP address was specified for the remote destination IP
address.
Requests: Remote port loopback, register read/write
09H
0AH
Incorrect transmission word
count
•
•
Occurs if either 0 words or 486 or more words were specified for either a
register read/write or a remote port loopback request.
Occurs if either 0 words or 1001 or more words were specified for a UDC/TCP
send/receive request.
Boundary error
•
Occurs if the specified area (start address + register range) does not exist in
the T2N data storage registers.
Requests: RAS information readout, remote port loopback, UDP send/receive,
TCP send/receive, register read/write
0BH
0CH
Transmission error
•
•
Occurs if the Ethernet Port returns an error response.
Detailed information (the Ethernet Port response status) is stored at B+1.
No I/O response
(Reserved)
Occurs if the T2N cannot access the Ethernet Port.
0DH
0EH
Send data capacity
exceeded
•
•
Occurs if a request is discarded when a T2N internal resource insufficiency
occurs due to increasing amounts of transfer data.
Occurs if a T2N retransmission times out.
0FH
(Reserved)
Details on the Ethernet Port error response when a transmission error (0Bh) occurs are stored in
the register following the status. (See table A5.)
¾ 173 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table A.5 Detailed Information (Ethernet Port Error Responses)
Code
Error
Description
Normal complete
Local port fault
Local port standby
0001H Request completed normally
0002H The local port is in down mode
0003H Data transmission in standby mode (socket interface transmission or PC link
protocol transmission) was requested.
Timeout
0020H Timeout occurred during TCP open processing or receive processing, or during
UDP receive processing.
Length error
0030H Incorrect send data length
Port mode error
0040H One of the following requests was issued in a mode other than standby mode:
a. Parameter setup, b. MAC address setup, c. Reset
MAC/IP not set up
0050H
Occurs if the MAC address or IP address is not set up.
Transmission prohibited state
0060H • Occurs if a PC link request was issued from the T2N in run mode in the
message transmission prohibited state.
• Occurs if a socket open, close, send, or receive request is issued by the T2N
in run mode in the socket interface transmission prohibited state.
Format error
0070H Occurs when there is a format error in the request text.
0071H Port number error
0072H Request code error
0073H Time setting: Year
0074H Time setting: Month
0075H Time setting: Day
0076H Time setting: Hour
0077H Time setting: Minute
0078H Time setting: Second
Opened
0080H Occurs if an open request is issued for an already open socket.
0081H Occurs if send, receive, or close request is issued for an unopened socket.
0082H Occurs if the socket identifier is out of range (1 to 8).
Unopened
Incorrect socket identifier
Incorrect control request
specification
0083H Occurs if a request that was prohibited by an operating mode control request is
issued.
• Occurs if a run request is issued in run mode.
• Occurs if a standby request is issued in standby mode.
• Occurs if a run request and a standby request are issued at the same time.
LAN controller driver error
0090H Occurs if the setting of the local port IP address and port number in the area
reserved for transmission fails.
0091H Error in the TCP or UDP protocol (such as a transmission phase error)
0092H • Occurs if the setting of the remote port IP address in the remote port
information area (the NETDATA table) fails.
• Occurs if the remote port IP address network address differs from the local
port IP address network address.
Memory pool allocation failure
Port 2 task start failure
00A0H Occurs if the Ethernet Port internal OS fails to allocate memory.
00A1H Occurs if computer link or PC link socket identifier acquisition fails.
Broadcast specification error
00A2H If the remote destination was specified to be broadcast in a remote port
verification request.
MAC address specification error 00B0H BCC error
00B1H
Occurs if an error occurs after address saving on a MAC setup request.
Insufficient resources error
00C0H Occurs if there are insufficient resources for UDP send or PC link transmission.
¾ 174 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Appendix 4 Limitations on the T2N SEND and RECV Instructions
When transmissions using the Ethernet Port occur with high frequency, the T2N internal
processing load increases and it is possible for this to interfere with the T2N periodic interrupts
and other internal operations. For example, the T2N processing load increase greatly when
requests from other ports and requests from the local port occur at the same time in a single
Ethernet Port. Therefore, the Ethernet Port must be used with the following limitations enforced.
Usage Recommendations
When using the SEND and RECV instructions, there are limitations on the interrupt periods that can be
set the fixed period interrupt programs.
(1) When using the PC link protocol with the Ethernet Port
The number of words that can be set for the SEND and RECV instructions is stipulated to be
either:
·
The number of words that the local port transmitted with the SEND instruction.
or:
·
The number of words that the local T2N transmitted in response to a data request issued
with the RECV instruction from a remote T2N.
When some number of words are transmitted by the local T2N with the SEND instruction and
some other number of words are transmitted due to a RECV instruction request from a remote, we
focus on the larger of the two word counts when transmission is through the same transmission
Ethernet Port.
T2N PU235N/
245N
In the figure to the left, the number of words
CH1
transmitted in CH1 is:
nr if ns < nr, and
ns if ns > nr.
Receive request due to a remote T2N RECV instruction
Response transmission for the RECV instruction (word count: nr)
Transmission path
Transmission to a remote T2N due to a T2N SEND instruction (word count: ns)
Figure A.2 Word Counts Considered with the PC Link Protocol
¾ 175 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
Table A.6 Number of Words that can be Transmitted Using PC Link Protocol with the Ethernet
Port
[When TCP/UDP socket transmission is not used]
Module classification
Processing time for function
instructions
Maximum specifiable number of transmission
words for local T2N SEND instructions or remote
T2N RECV instructions
PU235N
PU245N
4 ms (maximum)
5 ms (maximum)
3 ms (maximum)
4 ms (maximum)
5 ms (maximum)
485 words (maximum)
295 words (maximum)
485 words (maximum)
346 words (maximum)
131 words (maximum)
Conditions for the above table:
a. For the T2N configuration, this table assumes the configuration of figure A.3, in which T2N
(PU235N/245N) is mounted in the main base unit.
b. Refer to the T2N User's Manual - Hardware for the processing times for the instructions.
c. This table assumes that for PU245N, 128 words is specified for S20LP PC link protocol
transmission (SEND instruction on local port or RECV instruction from remote ports).
However, if S20LP PC link protocol transmission is not used, use the PU235N row in the
above table, even if there are PU245N unit installed.
d. If less than 128 words are used with the S20LP PC link protocol transmission, the number of
words that can be specified during PC link transmission on the Ethernet Port can be increased
over the values listed in table a.6. If the number of words for S20LP PC link protocol
transmission on the PU245N decreased on one word, the number of words for PC link
protocol transmission on the Ethernet Port can increase in one word. However, the maximum
number of words that can be specified during PC link transmission on the Ethernet Port is 485
words.
With the computer link and
loader not connected
T2N
(PU235N/
245N)
(main base unit)
Figure A.3 T2N Configuration when Using the PC Link Protocol
[Example] In case of the transmission with 1024 words in the TMOV instruction is executed.
Execution time required = 206 + 3.5 * n (the number of transmission words : 1024)
= 3790
In this case, the execution time required is under 4ms. Therefore, the maximum specifiable number
of transmission words are 485 words for PU235N, 346 words for PU245N.
[Attention] In case of using the instruction below, be careful to use the maximum specifiable
number of transmission. In the case of using another instruction, be careful, too.
TMOV,TNOT,TCMP,XFER,READ,WRITE
¾ 176 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(2) When using socket transmission (TCP or UDP) with the Ethernet Port
Table A.7 Number of Words that can be Transmitted Using TCP/UDP
Socket Transmission with the Ethernet Port
[When the PC link protocol is not used]
Module classification
Processing time for function instructions
Maximum number of words that can be specified in
socket transmission.
PU235N
PU245N
1 ms (maximum)
2 ms (maximum)
3 ms (maximum)
4 ms (maximum)
5 ms (maximum)
1 ms (maximum)
2 ms (maximum)
3 ms (maximum)
4 ms (maximum)
5 ms (maximum)
1000 words (maximum)
927 words (maximum)
712 words (maximum)
497 words (maximum)
282 words (maximum)
978 words (maximum)
763 words (maximum)
548 words (maximum)
333 words (maximum)
118 words (maximum)
Conditions for the above table:
a. For the T2N configuration, this table assumes the configuration of figure A.4, in which T2N
(PU235N/245N) is mounted in the main base unit.
b. Refer to the T2N User's Manual - Hardware for the processing times for the instructions.
c. This table assumes that for PU245N, 128 words is specified for S20LP PC link protocol
transmission (SEND instruction on local port or RECV instruction from remote ports).
However, if S20LP PC link protocol transmission is not used, use the PU235N row in the
above table, even if there are PU245N unit installed.
d. If less than 128 words are used with the S20LP PC link protocol transmission, the number of
words that can be specified during socket transmission on the Ethernet Port can be increased
over the values listed in table A.7. If the number of words for S20LP PC link protocol
transmission on the PU245N decreased on one word, the number of words for Socket
transmission on the Ethernet Port can increase in one word. However, the maximum number
of words that can be specified during PC link transmission on the Ethernet Port is 1000
words.
With the computer link and
loader not connected
T2N
(PU235N/
245N)
(main base unit)
Figure A.4 T2N Configuration when Using the Socket Interface
¾ 177 ¾
Download from Www.Somanuals.com. All Manuals Search And Download.
6 F 3 B 0 3 6 2
(3) When using the PC link protocol and socket transmission (TCP or UDP) with the Ethernet
Port.
Table A.8
Number of Words that can be Transmitted Using PC Link Protocol and
TCP/UDP Socket Transmission with the Ethernet Port with Ethernet
Port.
[When PC link transmission and TCP/UDP socket transmission is used either]
Module classification
Processing time for function
instructions
Maximum specifiable number of transmission words
for local T2N SEND instructions, remote T2N RECV
instructions or socket transmission
PU235N
1 ms (maximum)
2 ms (maximum)
3 ms (maximum)
4 ms (maximum)
5 ms (maximum)
1 ms (maximum)
2 ms (maximum)
3 ms (maximum)
4 ms (maximum)
5 ms (maximum)
1073 words (maximum)
858 words (maximum)
643 words (maximum)
428 words (maximum)
213 words (maximum)
1038 words (maximum)
823 words (maximum)
607 words (maximum)
392 words (maximum)
177 words (maximum)
PU245N
Conditions for the above table:
a. For the T2N configuration, this table assumes the configuration of figure A.5, in which T2N
(PU235N/245N) is mounted in the main base unit.
b. Refer to the T2N User's Manual - Hardware for the processing times for the instructions.
c. This table assumes that for PU245N, 128 words is specified for S20LP PC link protocol
transmission (SEND instruction on local port or RECV instruction from remote ports).
However, if S20LP PC link protocol transmission is not used, use the PU235N row in the
above table, even if there are PU245N unit installed.
d. The number of words is the maximum number words that can be specified during PC link
transmission and socket transmission. The maximum number of words that can be specified
during PC link transmission on Ethernet Port is 485 words, and during socket transmission on
Ethernet Port is 1000 words.
e. If less than 128 words are used with the S20LP PC link protocol transmission, the number of
words that can be specified during PC link transmission on the Ethernet Port can be increased
over the values listed in table A.8. If the number of words for S20LP PC link protocol
transmission on the PU245N decreased on one word, the number of words for PC link
protocol transmission or Socket transmission on the Ethernet Port can increase in one word.
However, the maximum number of words that can be specified during PC link transmission on
the Ethernet Port is 485 words, and during socket transmission on the Ethernet Port is 1000
words.
f. If the PU245N is used only Ethernet or S20LP PC link transmission, refer to the value listed
in table A.6 and if the PU245N is used only socket transmission on the Ethernet Port, refer to
the value listed table A.7.
With the computer link and
loader not connected
T2N
(PU235N/
245N)
(main base unit)
Figure A.5 T2N Configuration when Using the PC Link Protocol