E6581738  
TOSVERT VF-MB1/S15  
PROFIBUS-DP Option Function Manual  
PDP003Z  
NOTICE  
1. Read this manual before installing or operating. Keep this instruction manual on hand  
of the end user, and make use of this manual in maintenance and inspection.  
2. All information contained in this manual will be changed without notice. Please  
contact your Toshiba distributor to confirm the latest information.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
1. Introduction  
Thank you for purchasing the PROFIBUS-DP option “PDP003Z” for the VF-MB1/S15.  
Before using the PROFIBUS-DP option, please familiarize yourself with the product and  
be sure to thoroughly read the instructions and precautions contained in this manual.  
This option needs the option adaptor to connect VF-S15 which type form is SBP009Z.  
Please match here and buy it when SBP009Z is not at hand yet.  
In addition, please make sure that this manual and “Installation Manual” is delivered to  
the customer, and keep this function manual in a safe place for future reference or  
drive/interface inspection.  
This manual describes the supported functions for the “PDP003Z”.  
In conjunction with this manual, the following manuals are supplied by Toshiba, and they  
are essential both for ensuring a safe, reliable system installation as well as for realizing  
the full potential of the “PDP003Z”:  
- TOSVERT VF-MB1 Instruction Manual................................................E6581697  
- TOSVERT VF-S15 Instruction Manual.................................................E6581611  
- TOSVERT VF-MB1/S15 communication option Precautions Manual· E6581739  
- 1 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
Safety precautions  
On the drive and in its instruction manual, important information is contained for  
preventing injuries to users and damages to assets and for proper use of the device.  
Read the instruction manual attached to VF-MB1/S15 along with this instruction manual  
for completely understanding the safety precautions and adhere to the contents of these  
manuals.  
Explanation of markings  
Marking  
Meaning of marking  
Indicates that errors in operation may lead to death or serious injury.  
Warning  
Indicates that errors in operation may lead to injury (*1) to people or that these errors  
may cause damage to physical property. (*2)  
Caution  
(*1) Such things as injury, burns or shock that will not require hospitalization or long periods of  
outpatient treatment.  
(*2) Physical property damage refers to wide-ranging damage to assets and materials.  
Meanings of symbols  
Marking  
Meaning of marking  
Indicates prohibition (Don't do it).  
What is prohibited will be described in or near the symbol in either text or picture  
form.  
Indicates something mandatory (must be done).  
What is mandatory will be described in or near the symbol in either text or picture form.  
Indicates warning.  
What is warned will be described in or near the symbol in either text or picture form.  
Indicates caution.  
What the caution should be applied to will be described in or near the symbol in  
either text or picture form.  
- 2 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
General Operation  
Warning  
Never disassemble, modify or repair.  
Doing so could result in electric shock, fire and injury. For repairs, call your sales  
agency.  
Disassembly  
prohibited  
Do not attach this option to any drive other than the VF- MB1/S15.  
Doing so could result in electric shock or fire.  
Prohibited  
When the drive is energized, never detach the this option from the VF- MB1/S15.  
Doing so could result in electric shock.  
Don't place or insert any kind of object into the PDP003Z (electrical wire cuttings, rods,  
wires).  
Doing so could result in electric shock or fire.  
Do not allow water or any other fluid to come in contact with the PDP003Z.  
Doing so could result in electric shock or fire.  
Turn off the VF- MB1/S15 when installing and wiring this option.  
If the drive begins to emit smoke or an unusual odor, or unusual sounds, immediately  
turn power off.  
Mandatory  
If the equipment is continued in operation in such a state, the result may be fire. Call  
your local sales agency for repairs.  
Transportation & installation  
Warning  
Do not operate the drive if it is damaged or any component is missing.  
Doing so could result in electric shock or fire. Call your local sales agency for repairs.  
Do not place any inflammable substances near the VF- MB1/S15 drive.  
If an accident occurs in which flame is emitted, this could lead to fire.  
Do not install in any location where the drive could come into contact with water or other  
fluids.  
Prohibited  
Doing so could result in electric shock or fire.  
When installing this option, be careful not to touch the leads from parts on the reverse  
side of its circuit board.  
Doing so could result in injury.  
Operate under the environmental conditions prescribed in the instruction manual.  
Operations under any other conditions may result in malfunction.  
Mandatory  
- 3 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
Wiring  
Warning  
Shut off power when installing and wiring this option.  
Wait at least 15 minutes and check to make sure that the charge lamp (VF- MB1/S15) is  
no longer lit.  
Mandatory  
Electrical construction work must be done by a qualified expert.  
Installation or connection of input power by someone who does not have that expert  
knowledge may result in fire or electric shock.  
Operations  
Warning  
Do not touch switches when the hands are wet and do not try to clean the drive with a  
damp cloth.  
Prohibited  
Doing so could result in electric shock.  
Do not pull on any cable it self.  
Doing so could result in damage or malfunction.  
Cautions for the communication  
Warning  
Do not set the value that exceeds an effective range as data.  
The motor may suddenly restart or stop and that could result in injury.  
Prohibited  
Mandatory  
Check PROFIBUS state (using below status word bit) when the option unit is  
deactivated by an unusual event such as an operating error, power outage, failure, etc.  
- ZSW Status Word Bit 3 (Fault), Bt 7 (Warning)  
(The communication error occurs when "1" as value or this value cannot be read.)  
Deactivated option unit may cause an accident, if the PROFIBUS state is not checked.  
Make sure that the operation signals are STOP before clearing the drive’s fault.  
The motor may suddenly start and that may result in injuries.  
Disposal  
Caution  
For safety's sake, do not dispose of the disused drive yourself but ask an industrial  
waste disposal agent (*).  
Mandatory  
If the collection, transport and disposal of industrial waste is done by someone who is  
not licensed for that job, it is a punishable violation of the law. (Laws in regard to  
cleaning and processing of waste materials)  
(*) Persons who specialize in the processing of waste and known as “industrial waste  
product collectors and transporters” or “industrial waste disposal persons.”  
- 4 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
Notes on use  
Notes  
Do not install the drive where the temperature or the humidity will change rapidly.  
Keep a distance of 20cm or more between the drive 's power cable and the data  
transmission cable.  
Or the drive might malfunction because of noise.  
Insert a magnetic contactor or similar device between the drive and the power supply to  
ensure that power is turned off if an emergency stop command is entered through the  
network.  
- 5 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
2. Connection Information  
This option allows the VF-MB1/S15 drive to be communicated with the cyclic command  
transmission and monitoring of the original profile ("Vendor spec.", refer to Section 4) of  
our company other than application profile "Profile for Variable Speed Drives PROFIdrive  
(3.072), refer to Section 3" which PROFIBUS defines.  
When you use VF-MB1, the shielding is connected to the drive ground. When you use  
VF-S15, the shielding is connected to the grounding terminal of option adapter.  
2.1. Exterior features  
Status LED indicator  
(Refer to Section 2.2)  
Release Tab  
PROFIBUS connector  
(D-Sub 9pin)  
To align VF-MB1/S15 side-by-side horizontally, "Vertical" type PROFIBUS connector is  
necessary.  
- 6 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E6581738  
2.2. Status indicator  
The PDP003Z has two LEDs, ST (status) and DX (data exchange) to indicate the  
statuses of PROFIBUS-DP and the PDP003Z itself.  
ST (status)  
DX (data Exchange)  
ST (Status): Red LED  
LED  
Meanings  
Off  
No diagnostics present  
8 Hz (Blinking 4 times/1sec.):  
Waiting for parameterization or configuration  
2 Hz (Blinking 1 times/1sec.):  
Flashes  
PDP003Z station address is "126".  
DP status error  
* For example, a station address is not setcorrectly.  
Lights  
DX (Data exchange): Green LED.  
Indicates the status of the PROFIBUS network.  
It lights when the PDP003Z is on-line and data exchange is possible.  
- 7 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
2.3. VF-MB1/S15 Communication parameters  
In a network, VF-MB1/S15 (PDP003Z) serves as a PROFIBUS slave device. PDP003Z  
configuration is set by the following parameters.  
Default  
setting  
Parameter  
Function  
Adjustment range  
c150  
PDP003Z  
Station address  
PDP003Z  
2 to 126  
126  
The station address "126" cannot exchange data.  
0: 12 Mbit/s  
c151  
-
Baud rate Monitor  
1: 6 Mbit/s  
2: 3 Mbit/s  
3: 1.5 Mbit/s  
4: 500 kbit/s  
5: 187.5 kbit/s  
6: 93.75 kbit/s  
7: 19.2 kbit/s  
8: 9.6 kbit/s  
c152  
PDP003Z  
Profile Monitor  
0Telegram 1 (PROFIdrive)  
1Telegram 100 (Vender Spec. 1)  
2Telegram 101 (Vender Spec. 2)  
3Telegram 102 (Vender Spec. 3)  
0.0 to 20.0Hz  
-
c154  
c155  
c156  
c157  
c100  
c101  
JOG1 Frequency  
(STW.8)  
JOG2 Frequency  
(STW.9)  
5.0Hz  
5.0Hz  
10.0s  
50.0%  
0.0  
0.0 to 20.0Hz  
0.1 to 60.0s  
0.1 to 99.0%  
Tmax  
(ZSW.8)  
Tolerance  
(ZSW.8)  
Communication error 0.0 to 100.0 sec  
detection delay time  
Drive operation at the 0: Stop and Communication release *  
4
communications  
loss action  
(follows cmodand fmodsetting)  
1: None  
(Network wire breaks) 2: Deceleration stop  
3: Coast stop  
4: Emergency stop  
5: Preset speed operation command  
(Operating at the preset speed operation frequency  
set with c102)  
c102  
Preset speed  
0: None  
0
operation selection 1 to 15: Preset speed (sr1- sr7, f287- f295)  
c103**  
Communication  
time-out condition  
selection  
0: Disconnection detection  
1
1: When communication mode enable (Both cmod  
and fmodare set CANopen or COM option)  
2: 1+Driving operation  
f899  
fd67  
Network option  
reset setting  
PDP003Z versioon PDP003Z firmware version  
(ex. 0x1101 means "V1.01")  
0: None  
0
1: Resetting the PDP003Z and the drive  
-
*
Do not set at VF-MB1 V1.00.  
**  
***  
It is necessary to enable "Watchdog" function with the configurator.  
When the parameters are changed or to reset err8, the power must be cycled (or set f899to 1).  
After reset, the parameter changes become effective.  
Set 1to f899by the PROFIBUS communication might not be able to be set.  
**** When fmodor cmodis set to “Communication option”, VF-MB1/S15 drives without Net Reference  
(STW Bit 13) or Net Control (STW Bit 12) at PROFIdrive.  
Please note that drive keeps driving when the communication is lost if 1(None) is set to  
the parameter c101(Drive operation at the communications loss action).  
Caution  
- 8 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3. Profile  
3.1. Telegram  
Telegram of PDP003Z is set up by the configurator.  
The figures below show the Telegrams and configurations that the PDP003Z supports.  
PKW  
PZD  
PZD1  
STW  
ZSW  
PKE  
PWE  
PZD6  
Telegram 1: PROFIdrive (PPO TYPE 3, 2PZD)  
Telegram 100: Vendor Spec. (PPO TYPE 1, 4PKW / 2PZD)  
Telegram 101: Vendor Spec. (PPO TYPE 2, 4PKW / 6PZD)  
Telegram 102: Vendor Spec. (PPO TYPE 4, 6 ZD)  
PKW:  
PZD:  
Parameter ID/value  
Process Data, cyclically transferred  
PKE:  
IND:  
PWE:  
Parameter ID (1st and 2nd octet)  
Sub-index (3rd octet), 4th octet is reserved  
Parameter value (5th until 8th octet)  
STW:  
HSW:  
Control word  
Main setpoint  
ZSW:  
HIW:  
Status word  
Main actual value  
* There are some by which a high byte / low byte is conversely treated depending on a  
master.  
- 9 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E6581738  
3.2. STW Control Word Data  
PDP003Z supports only speed control mode.  
Bit Value Name  
Note  
ON  
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
---  
1
“Switched on” condition  
Normal stop.  
0
1
2
3
OFF  
No Coast Stop  
All "Coast Stop (OFF2)" commands are withdrawn  
Coast stop.  
Coast Stop (OFF 2)  
No Quick Stop  
All "Quick Stop (OFF3)" commands are withdrawn.  
Quick Stop  
Quick Stop (OFF 3)  
Enable Operation  
Disable Operation  
Enable Ramp Generator  
Reset Ramp Generator  
Unfreeze Ramp Generator  
The drive then runs-up to the setpoint.  
Normal stop.  
-
4
5
6
7
8
9
Output of the RFG is set to 0.  
-
Freeze Ramp Generator Freeze the actual setpoint entered by the RFG *.  
Enable Setpoint  
Disable Setpoint  
Fault Acknowledge  
No meaning  
The value selected at the input of the RFG is switched-in.  
The value selected at the input of the RFG is set to 0.  
Fault reset (0 -> 1)  
-
JOG 1 ON **  
VF-MB1/S15 drives with JOG 1 speed 1 (c154).  
Jogging stop, if "JOG 1" was previously ON. Stop drive  
according to VF-MB1/S15 setting parameter.  
JOG 1 OFF  
JOG 2 ON **  
VF-MB1/S15 drives with JOG 2 speed 2 (c155).  
Jogging stop, if "JOG 2" was previously ON. Stop drive  
according to VF-MB1/S15 setting parameter.  
JOG 2 OFF  
Control By PLC  
No Control By PLC  
Device-specification  
The control word and main setpoint are activated.  
The control word and main setpoint are inactivated.  
(Reserved.)  
10  
11  
12  
Net Control  
Local Control  
PDP003Z control is enabled.  
PDP003Z control is disabled.  
PDP003Z reference is enabled.  
PDP003Z reference is disabled.  
(Reserved.)  
0
1
Net Reference  
13  
0
Local Reference  
Device-specification  
Device-specification  
14  
15  
---  
---  
(Reserved.)  
* RFG: Ramp Function Generator  
** Operation is enabled, drive is in standstill and STW1 bit 4, 5, 6 = 0.  
- 10 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.3. ZSW Status Word Data  
Bit  
0
Valure  
1
Name  
Note  
Ready To Switch-on  
Not Ready To Switch-on  
Ready To Operate  
Not Ready To Operate  
Operation Enabled  
Operation Disabled  
Fault Present  
Power supply is switched on  
-
0
Refer to control word, bit 1.  
-
1
1
2
3
4
5
6
7
0
Drive follows setpoint.  
1
(Refer to control word 1, bit 3)  
-
VF-MB1/S15 tripped.  
VF-MB1/S15 is not tripped.  
-
0
1
No Fault  
0
Coast Stop Not Activated  
1
Coast Stop Activated (OFF 2) "Coast Stop (OFF 2)" command is present.  
Quick Stop Not Activated  
0
-
1
Quick Stop Activated (OFF 3) "Quick Stop (OFF 3)" command is present  
0
Control word bit1 or 2 is set to 0  
Switching On Inhibited  
1
or fault trip has been acknowledged.  
Switching On Not Inhibited  
Warning Present  
No Warning  
-
0
Drive still operational: Alarm in service parameter: No  
acknowledgement.  
1
Alarm not present or alarm has disappeared again  
0
Speed Error  
Within Tolerance Range  
Speed Error  
1
Refer to section 3.3.1.  
8
9
0
Out Of Tolerance Range  
Control Requested  
VF-MB1/S15 is controlled by PROFIBUS master.  
VF-MB1/S15 is controlled by another interface.  
1
No Control Requested  
0
f Or n Reached Or Exceeded Actual value Comparison value (setpoint)  
1
10  
f Or n Not Reached  
Device-specification  
Device-specification  
Device-specification  
Device-specification  
Device-specification  
-
0
(Reserved.)  
(Reserved.)  
(Reserved.)  
(Reserved.)  
(Reserved.)  
11  
12  
13  
14  
15  
----  
----  
----  
----  
----  
- 11 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.3.1.  
Tolerance Range (ZSW Bit 8)  
If the setpoint is changed:  
1. ZSW Bit 8 is set 0  
2. Calculate the tolerance.  
3. Start the timer which will time-out based on parameter Tmax.  
PDP003Z checks that the timer (Tmax) has not timed-out and if the actual value is within  
the tolerance. If both conditions are fulfilled ZSW Bit 8 is set 1 and the timer is stopped.  
The figure shows ZSW 8 when Tolerance (c157) is 50% and Tmax (c151) is 3s.  
Tolerance  
= 0x4000 * 50%  
setpoint  
actual value  
HIW  
HIW = 0x4000  
HIW = 0x3000  
HIW = 0x2000  
HIW = 0x1000  
HIW = 0x0000  
15s  
20s  
25s  
30s  
Time  
Tmax  
= 3s  
Tmax  
Tmax  
ZSW Bit 8  
- 12 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.4. State Machine  
ZSW Bit 6 = 1  
SWITCH-ON  
INHIBIT  
MAINS OFF  
Power ON  
STW Bit 0 = 0  
A
B
C
D
ZSW Bit 0 = 0  
NOT READY TO  
SWITCH-ON  
from any state  
FAULT  
STW Bit 3 = 0  
STW: xxxx xxxx xxxx x110  
ZSW Bit 2 = 0  
ZSW Bit 0 = 1  
ZSW Bit 3 = 1  
OPERATION  
INHIBIT  
READY TO  
FAULT  
SWITCH-ON  
STW: xxxx xxxx xxxx x111  
STW Bit 7 = 1  
from any state  
ZSW Bit 1 = 1  
0 -> 1  
READY TO  
OPERATE  
STW Bit 0 = 0  
STW Bit 3 = 1  
ZSW Bit 1 = 0  
Normal Stop  
OFF1  
ACTIVE  
from any state  
STW Bit 2 = 0  
from any state  
Frequency = 0  
STW Bit 1 = 0  
ZSW Bit 5 = 0  
ZSW Bit 4 = 0  
Coast stop  
OFF3  
OFF2  
ACTIVE  
ACTIVE  
Emergency Stop  
B
C
D
STW Bit 4 = 0  
ZSW Bit 2 = 1  
ENABLE  
C
D
OPERATION  
A
B
STW Bit 5 = 0  
STW Bit 6 = 0  
STW Bit 4 = 1  
STW Bit 4 = 0, Bit 5 = 0, Bit 6 = 0  
STW Bit 8 (or Bit 9)= 1  
RFG: ENABLE  
OUTPUT  
D
Jogging ON  
Jogging 1 or 2  
ACTIVE  
STW Bit 5 = 1  
STW Bit 8 (or Bit 9) = 0  
RFG: ENABLE  
RUN UP  
Jogging OFF  
Jogging 1 or 2  
PAUSE  
C
D
STW Bit 6 = 1  
ZSW Bit 8 = 1  
OPERATING  
STW: Control Word  
ZSW: Status Word  
: State  
: Condition  
Notes  
STW Bit 10, 12 = 1 or cmod= 4 is needed for above control.  
If cmodis set to Local (0, 1, 2 or 3), set 1 to STW Bit10 and 12 first after turning on the  
power supply of VF-MB1/S15.  
Check ZSW always and take care to give the command to STW.  
- 13 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.4.1.  
Examples of driving by the State Machine  
When using the PROFIdrive profile, the frequency reference is set to HSW. The setting  
value “0x0000” - ”0x4000” is equivalent to ”0” - ”Base frequency (parameter fh)”.  
When the reverse operation, the frequency reference is set with two's complement of the  
forward frequency reference. During running, HIW shows a output frequency.  
* fmodor cmodis set to “Communication option” on these examples.  
3.4.1.1. Example 1. 60Hz Forward running and Deceleration stop  
Set ”0x4000” to HSW and the following is set to STW in order.  
0000 0100 0000 0110 (= 0x0406)  
“READY TO SWITCH-ON”  
0000 0100 0000 0111 (= 0x0407)  
“READY TO OPERATE”  
0000 0100 0111 1111 (= 0x047F)  
“OPERATION”  
0000 0100 0111 1110 (= 0x047E)  
“OFF1 ACTIVE (Normal Stop)”  
3.4.1.2. Example 2. 30Hz Reverse running  
When the reverse operation, “0xE000” is set to HSW. “0xE000” is two's complement of  
the “0x2000” as the forward frequency reference 30Hz.  
The Setup to STW is same as the Example 1.  
3.4.1.3. Example 3. Inching and pause  
the following is set to STW in order.  
0000 0100 0000 0110 (= 0x0406)  
“READY TO SWITCH-ON”  
0000 0100 0000 0111 (= 0x0407)  
“READY TO OPERATE”  
0000 0101 0000 1111 (= 0x050F)  
“Jogging 1 ACTIVE”  
0000 0100 0100 1111 (= 0x040F)  
“Jogging 1 PAUSE”  
* The inching frequency is according to the parameter c154, c155on VF-MB1/S15.  
- 14 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
3.5. Access to the PROFIBUS parameter  
In the cyclic PROFIBUS-DP communication, the parameter data is transferred via Telegram  
100, 101. If the requirement is not executed, the cause is distinguished by octet 7 and 8.  
PKW  
PZD  
(Parameter ID/value)  
Process data (cyclically)  
PZD1  
STW  
ZSW  
PZD2  
HSW  
HIW  
PKE  
IND  
PWE  
Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Octet 6 Octet 7 Octet 8  
PKE (Parameter ID)  
15 14 13  
12  
11  
10  
9
8
7
6
5
4
3
2
1
0
AK  
(Task ID/Response ID)  
SPM  
PNU  
(Parameter number)  
AK (Request from Master to PDP003Z)  
Request ID  
Function  
Note  
0
1
2
6
No task  
Request parameter value  
for PNU access  
for PNU access  
Change parameter value (word)  
Request parameter value (array)  
for PNU access, VF-MB1/S15 parameter  
access  
7
Change parameter value (array)  
for PNU access, VF-MB1/S15 parameter  
access  
AK (Response from PDP003Z to Master)  
Response ID  
Function  
0
1
4
7
No response  
Transfer parameter value (word)  
Transfer parameter value (array)  
Task can not be executed, followed by error number  
0 = Illegal parameter number  
1 = Parameter value cannot be changed  
2 = Lower or upper limit violated  
3 = Erroneous sub index  
11 = No parameter change rights  
17 = Task cannot be executed due to operating status  
(e.g. parameter is currently read-only)  
18 = Other error  
102 = Request not supported  
SPM: always 0.  
- 15 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.6. PROFIBUS parameter (PNU)  
PNU  
915  
R/W  
R
data type  
Array [6]  
Unsigned16  
Note  
PNU 915, IND 0 = the drive parameter c001  
PNU 915, IND 1 = the drive parameter c002  
PNU 915, IND 2 = the drive parameter c003  
PNU 915, IND 3 = the drive parameter c004  
PNU 915, IND 4 = the drive parameter c005  
PNU 915, IND 5 = the drive parameter c006  
PNU 916, IND 0 = the drive parameter c021  
PNU 916, IND 1 = the drive parameter c022  
PNU 916, IND 2 = the drive parameter c023  
PNU 916, IND 3 = the drive parameter c024  
PNU 916, IND 4 = the drive parameter c025  
PNU 916, IND 5 = the drive parameter c026  
916  
R
Array [6]  
Unsigned16  
918  
922  
R
R
Unsigned16  
Unsigned16  
Station address monitor (same as the drive parameter c150).  
Telegram selection  
1, 100, 101, 102  
927  
R/W  
Unsigned16  
Operator control rights (parameter identification, PKW).  
Value: Mode  
0: Parameters cannot be written, only read  
(927 can be written).  
1: Parameters can be written and read (default).  
Control rights (process data, PZD).  
1: PZD part is enabled.  
928  
930  
R
R
Unsigned16  
Unsigned16  
Operating mode  
1 supports the speed control mode and the speed  
setpoint channel comprises RFG functionality.  
944  
947  
R
R
Unsigned16  
Array [1]  
Fault message counter  
Fault number  
Unsigned16  
Unsigned16  
963  
R
Detected baud rate:  
0 =  
9.6 kbit/s  
1 = 19.2 kbit/s  
2 = 93.75 kbit/s  
3 = 187.5 kbit/s  
4 =  
500 kbit/s  
6 = 1.5 Mbit/s  
7 =  
8 =  
9 =  
3 Mbit/s  
6 Mbit/s  
12 Mbit/s  
Array [5]  
Unsigned16  
964  
965  
R
R
Drive Unit identification  
IND 0 = PDP003Z ID (0x0C24)  
IND 1 = Manufacturer-ID (0x0190)  
IND 2 = VF-MB1/S15 CPU1 version  
IND 3 = VF-MB1/S15 firmware release year (yyyy)  
IND 4 = VF-MB1/S15 firmware release date (ddmm)  
Profile number of the PDP003Z (Profidrive, V4.1)  
Octet String2  
- 16 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.6.1.  
Examples of reading the PROFIdrive parameter  
3.6.1.1. Example 1. Reading the PNU 922 (Telegram)  
AK = 1 (Request parameter value)  
SPM = 0  
PNU = 922 (0x039A)  
PKE  
0
1
0
0
0
Requirement  
PKW  
PZD  
PKE  
13  
IND  
00  
PWE  
00  
9A  
00  
00  
00  
00  
65  
・・・  
Response (Value: 0x0065 = 101)  
13 9A 00 00  
00  
00  
00  
・・・  
3.6.1.2. Example 2. Reading the PNU 964, IND 0  
AK = 6 (Request parameter value (array))  
SPM = 0  
PNU = 964 (0x03C4)  
IND = 0 (PDP003Z ID)  
PKE  
0
0
0
0
0
Requirement  
PKW  
PZD  
PKE  
63  
IND  
00  
PWE  
00  
C4  
00  
00  
00  
00  
・・・  
Response (Value: 0x0C24 = PDP003Z ID)  
43  
C4  
00  
00  
00  
00  
0C  
24  
・・・  
- 17 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
3.7. Access to VF-MB1/S15 parameter  
When access to VF-MB1/S15 parameter, set “1” to the PNU. The communication number  
of the drive parameter is set to the subindex IND.  
Refer to the drive instruction manual about the communication number and unit.  
* This procedure changes the value of VF-MB1/S15 EEPROM.  
3.7.1.  
Examples of reading or changing VF-MB1/S15 parameter  
3.7.1.1. Example 1. Reading the basic parameter (cmod(command mode selection))  
AK = 6 (Request parameter value (array))  
SPM = 0  
PNU = 1  
IND = 0x0003 (cmodcommunication number)  
PKE  
0
0
0
0
1
Requirement  
PKW  
PZD  
PKE  
60  
IND  
00  
PWE  
00  
01  
03  
00  
00  
00  
・・・  
Response (Value: 0x0001 = Operation panel))  
40 01 00 03 00 00  
00  
01  
・・・  
3.7.1.2. Example 2. Reading the extended parameter (f219(VIC input point 2 frequency))  
AK = 6 (Request parameter value (array))  
SPM = 0  
PNU = 1  
IND = 0x0219 (f219communication number)  
PKE  
0
0
0
0
1
Requirement  
PKW  
PZD  
PKE  
60  
IND  
02  
PWE  
00  
01  
19  
00  
00  
00  
・・・  
Response (Value: 0x1770 (= 6000 -> 60.00Hz *))  
40 01 02 19 00 00 17  
70  
・・・  
* “0x1770” as reading value of “VIC input point 2 frequency” is  
0x1770 = 6000 (decimal number)  
Since the unit of “VIC input point 2 frequency” is 0.01Hz, set the following value.  
6000×0.01 = 60.00Hz  
- 18 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
3.7.1.3. Example 3. Reading the status monitor parameter (fe02(The operation frequency))  
AK = 6 (Request parameter value (array))  
SPM = 0  
PNU = 1  
IND = 0xFE02(fe02communication number)  
PKE  
0
0
0
0
1
Requirement  
PKW  
PZD  
PKE  
60  
IND  
FE  
PWE  
00  
01  
02  
00  
00  
00  
・・・  
Response (Value: 0x03E8 (= 1000 -> 10.00Hz))  
40 01 FE 02 00 00  
03  
E8  
・・・  
* The status monitor parameter can not be changed.  
3.7.1.4. Example 4. Changing the basic parameter (acc(acceleration time))  
AK = 7 (Change parameter value (array))  
SPM = 0  
PNU = 1  
IND = 0x0009 (acccommunication number)  
PKE  
0
1
0
0
1
Requirement (acc= 7.0 sec. -> 70 (= 0x0046) *)  
PKW  
PZD  
PKE  
70  
IND  
00  
PWE  
00  
01  
01  
09  
09  
00  
00  
00  
00  
46  
46  
・・・  
Response  
40  
00  
00  
・・・  
* When the “Acceleration time” is set to 7.0 sec., set the following value.  
(The unit of the “Acceleration time” is according to the parameter f519.)  
7.0/0.1 = 70 = 0x0046 (hexadecimal number)  
Notes  
When the control power is shut off by the instantaneous power failure,  
communication will be unavailable for a while.  
The Life of EEPROM is approximately 100,000 times. Avoid writing a command more  
than 100,000 times to the same parameter of the drive and the communication board.  
- 19 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
4. Vendor Spec. Profile  
Cyclic command transmission (the value of the parameter c001- c006) and  
monitoring (the value of the parameter c021- c026) are possible for PDP003Z by  
the original profile  
Select the ”Telegram 100”, ”Telegram 101” or ”Telegram 102” as the profile on the  
configuration. Refer to the PLC configurator documents.  
c001- c006setup value  
c021- c026setup value  
0: No action  
0: No action  
1: fa06(Communication command 1)  
2: fa23(Communication command 2)  
3: fa07(Fequency command, 0.01Hz)  
5: fa50(Terminal output data)  
6: fa51(FM analog output)  
1: fd01(Status information 1)  
2: fd00(Output frequency, 0.01Hz)  
3: fd03(Output current, 0.01%)  
4: fd05(Output voltage, 0.01%)  
5: fc91(Alarm information)  
6: fd22(PID feedback value, 0.01Hz)  
7: fd06(Input terminal board status)  
8: fd07(Output terminal status)  
9: fe36(VIB input, 0.01%)  
8: f601(Stall prevention level, %)  
13: acc(Acceleration time 1, 0.1s)*  
14: dec(Deceleration time 1, 0.1s) *  
15: ul(Upper limit,0.01Hz)  
16: vb(Torque boost value 1,0.1%)  
17: vlv(Base frequency voltage 1, 0.1V)  
10: fe35(VIA input, 0.01%)  
11: fe37(VIC input, 0.01%)  
12: fd04(Input voltage (DC detection), 0.01%)  
13: fd16(Estimated speed (real-time value), 0.01Hz)  
14: fd18(Torque, 0.01%)  
19: f880(Free notes)  
20: fd29(Input power, 0.01kW)  
21: fd30(Output power, 0.01kW)  
22: fe14(Cumulative operation time, hour)  
23: fe40(FM terminal output monitor, 0.01%)  
25: fd20(Torque current, 0.01%)  
26: fd23(Motor overload factor, 0.01%)  
27: fd24(Drive overload factor, 0.01%)  
28: fd25(PBR overload factor, %)  
29: fd26(Motor load factor, %)  
30: fd27(Drive load factor, %)  
31: fe56(Pulse train input, pps)  
32: fe70(Drive rated current, 0.1A)  
33: fe76(Input Watt-hour, 0.1kWh 10f749) **  
34: fe77(Output Watt-hour, 0.1kWh 10f749) **  
35: fd83(IGBT temperature, degree C)  
* The unit of acc, decis according to the parameter f519.  
** The unit of fe76, fe77is according to the parameter f749.  
- 20 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
4.1. How to use  
The purposes are adjustment by real time command transmission, and the monitor of an  
operation state by using cyclic communication of PROFIBUS.  
Example 1: Command transmitting  
When you want to set "0xC400" to parameter fa06, set “1 (fa06)” to parameter  
c001.  
And Since 0 and 1 byte of the PZD1 supports the parameter c001, if "0xC400" is set up  
here, "0xC400" will be set as fa06.  
VF-MB1  
PROFIBUS Master  
PDP003Z  
Parameter  
Value  
1 (FA06)  
...  
c001  
c002  
c003  
...  
...  
PZD1  
C4 00  
PZD2  
... ...  
PZD3  
... ...  
...  
"0xC400" is set as parameter fa06  
Example 2: State monitoring  
When you want to monitor the output current, set “3 (FD03)” to parameter c021.  
The value of the parameter fd03specified as 0 and1 byte of the PZD1 with the  
parameter c021is inputted.  
PROFIBUS Master  
VF-MB1  
PDP003Z  
Parameter  
Value  
c021  
c022  
c023  
...  
3 (FD03)  
...  
...  
...  
PZD1  
xx xx  
PZD2  
... ...  
PZD3  
... ...  
The value of a parameter fd03is outputted.  
- 21 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
4.2. The overview of the VF-MB1/S15 parameter  
Refer to a communication functional description (E6581726/E6581913) for details.  
4.2.1. fa06(Communication command1)  
bit  
Function  
Preset speed  
0
1
Note  
0
operation frequencies  
1
Preset speed operation is disabled  
or preset speed operation  
Preset speed  
frequencies (1-15) are set by  
specifying bits for preset speed  
operation frequencies 1-4.  
(0000: Preset speed operation OFF,  
001-1111: Setting of preset speed  
operation frequencies (1-15)  
1
2
3
operation frequencies  
2
Preset speed  
operation frequencies  
3
Preset speed  
operation frequencies  
4
THR 1: pt= setting value, thr  
THR 2: pt 0, f170,  
Motor selection (1 or 2)  
(THR 2 selection)  
Motor 1  
(THR 1)  
Motor 2  
(THR 2)  
4
5
=
f171, f172, f173  
PI D control  
Normal operation  
PI D off  
-
Acceleration/decele-  
ration pattern selection  
(1 or 2)  
Acceleration/dec  
eleration pattern AD1: acc, dec  
Acceleration/decel  
eration pattern 1  
(AD1)  
6
2
AD2: f500, f501  
(AD2 selection)  
(AD2)  
Forced DC  
braking  
Jog run  
7
8
9
DC braking  
OFF  
OFF  
-
-
-
Jog run  
Forward/reverse run  
selection  
Forward run  
Reverse run  
10  
11  
12  
13  
Run/stop  
Stop  
Standby  
OFF  
Run  
Cost stop  
-
-
Coast stop command  
Emergency stop  
Fault reset  
Emergency stop Always enable, "E" trip  
OFF  
Reset  
No data is returned from the drive  
Frequency priority  
selection  
Command priority  
selection  
Enabled regardless of the setting  
of fmod  
Enabled regardless of the setting  
of cmod  
14  
15  
OFF  
OFF  
Enabled  
Enabled  
* VF-S15:When 14(sr0) is set to fmod, preset speed operation frequency 0 is selected.  
- 22 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
4.2.2. fa23(Communication command 2)  
bit  
Function  
(Reserved)  
0
1
Note  
0
-
-
-
Electric power quantity  
reset  
Electric power quantity (fe76,  
fe77) reset  
1
OFF  
Reset  
2
3
4
5
6
(Reserved)  
(Reserved)  
(Reserved)  
(Reserved)  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
(Reserved)  
Maximum deceleration  
forced stop  
7
Normal  
Enabled  
-
Select  
acceleration/deceleration  
Acceleration/decele-  
ration selection 1  
8
00: Acceleration/deceleration 1  
01: Acceleration/deceleration 2  
10: Acceleration/deceleration 3  
1-4 by combination of two bits..  
AD1: acc, dec  
AD2: f500, f501  
AD3: f510, f511  
Acceleration/decele-  
ration selection 2  
9
10  
11  
(Reserved)  
(Reserved)  
-
-
-
-
-
-
OC stall 1: f601  
OC stall 2: f185  
12  
OC stall level switch  
OC stall 1  
OC stall 2  
13  
14  
15  
(Reserved)  
(Reserved)  
(Reserved)  
-
-
-
-
-
-
-
-
-
Note: Set 0 to reserved bit.  
- 23 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
4.2.3. fa07(frequency reference from internal option)  
Frequency reference is set up by 0.01Hz unit and the hexadecimal number.  
For example, when "Frequency reference" is set up to 80Hz, since the minimum unit is 0.01Hz,  
80 / 0.01 = 8000 = 0x1F40 (Hex.)  
4.2.4. fa50(Terminal output data from communication)  
By setting up the data of the bit 0 - 1 of terminal output data (fa50) from communication, setting data  
(OFF or ON) can be outputted to the output terminal.  
Please select the functional number 92 - 95 as the selection (f130- f138) of the output terminal  
function before using it.  
bit  
Output TB function name  
Specified data output 1  
(Output terminal No.: 92, 93)  
Specified data output 2  
(Output terminal No.: 94, 95)  
(Reserved)  
0
1
0
OFF  
ON  
1
OFF  
-
ON  
-
2-15  
Note: Set 0 to reserved bit  
4.2.5. fa51(Analog output (FM) data from communication)  
Use this function, set the FM terminal meter selection parameter (fmsl) to 18 (communication data  
output).  
This makes it possible to send out the data specified as FM analog output data (fa51) though the FM  
analog output terminal. Data can be adjusted in a range of 0 to 1000 (resolution of 10 bit).  
Please refer to "Meter setting and adjustment" Section of the VF-MB1/S15 instruction manual for details.  
- 24 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
4.2.6. fd01(Inverter operating status 1 (real time))  
bit  
Function  
Failure FL  
0
1
Note  
Under in  
progress  
0
No output  
-
Trip status includes rtryand  
the trip retention status are also  
regarded as tripped statuses.  
-
1
Failure  
Not tripped  
Tripped  
2
3
Alarm  
No alarm  
Normal  
Alarm issued  
Under voltage  
Under voltage (moff)  
-
THR1: pt= setting value, vl,  
vlv, vb, thr  
THR2: pt= 0, f170, f171,  
f172, f173  
Motor selection (1 or 2)  
(THR 2 selection)  
4
Motor 1 (THR1) Motor 2 (THR2)  
PID control  
permitted  
PID control  
prohibits  
5
6
7
PID control off  
-
Acceleration/deceleratio Acceleration/dec Acceleration/dec  
n pattern selection (1 or eleration pattern eleration pattern  
AD1: acc, dec  
AD2: f500, f501  
2)  
1 (AD1)  
2 (AD2)  
Forced DC  
braking  
DC braking  
OFF  
-
8
9
Jog run  
Forward / reverse run  
OFF  
Forward run  
Stop  
ST=ON  
No emergency  
stop status  
Jog run  
Reverse run  
Run  
ST=OFF  
Emergency  
stop status  
-
-
-
-
10 Run/stop  
11 Coast stop (ST = OFF)  
12 Emergency stop  
-
Standby: Initialization  
completed, not failure stop  
status, not alarm stop status  
(moff, llforced stop),  
ST=ON, and RUN=ON  
Standby: Initialization completed,  
not failure stop status and not  
alarm stop status (moff, ll  
forced stop)  
13 Standby ST=ON  
Start-up process  
Standby  
14 Standby  
Start-up process  
-
Standby  
-
15 (Undefined)  
-
Note: The bit described "Undefined" is unstable. Don't use the bit for the judgment.  
4.2.7. fd00(Output frequency (real time))  
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.  
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.  
Since the minimum unit is 0.01%,  
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)  
Also about the following parameters, these are the same as this.  
- fd22(Feedback value of PID (real time)) .............................Unit: 0.01Hz  
- fd16(Estimated speed (real time)).......................................Unit: 0.01Hz  
- fd29(Input power (real time))...............................................Unit: 0.01kW  
- fd30(Output power (real time))............................................Unit: 0.01kW  
- 25 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
4.2.8. fd03(Output current (real time))  
The output current is read into 0.01% of units and by the hexadecimal number.  
For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal  
number) is read out.  
Since the minimum unit is 0.01%,  
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)  
Also about the following parameters, these are the same as this.  
- fd05(Output voltage (real time)).............................................Unit: 0.01% (V)  
- fd04(Voltage at DC bus (real time)).......................................Unit: 0.01% (V)  
- fd18(Torque) ..........................................................................Unit: 0.01% (Nm)*  
* When the motor information connected to the drive set to the parameter (f405- f415), torque  
monitor value "100%" is same as the rated torque of a motor in general.  
4.2.9. fe35, fe36, fe37(Monitoring of the analog input VIA, VIB, VIC)  
VIA terminal board monitor: "Communication Number fe35"  
VIB terminal board monitor: "Communication Number fe36"  
VIC terminal board monitor: "Communication Number fe37"  
These monitors can also be used as A/D converters irrespective of the drive's control.  
VIA / VIC terminal board monitor is capable of reading the data from external devices in a range of 0.01  
to 100.00% (unsigned data: 0x0000 to 0x2710).  
VIB terminal board monitor is capable of reading the data from external devices in a range of -100.00 to  
100.00% (signed data: 0xD8F0 to 0x2710).  
If analog input mode is selected with the frequency setting mode selection parameter, however, keep in  
mid that any data entered via an analog terminal is regarded as a frequency command.  
4.2.10. fe14(Cumulative run time)  
The operated cumulative time is read by the hexadecimal number.  
For example, when cumulative operation time is 18 hours, 0x12 (18 hours) is read.  
0x12 (Hex.) = 18 (Dec., hour)  
4.2.11. fe40(Analog output (FM))  
The output value of FM terminal is read.  
The value range is set to 0 to 10000 (0x2710).  
- 26 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
4.2.12. fc91(Alarm code)  
Remarks  
(Code displayed on  
the panel)  
bit  
Function  
0
1
0
1
2
3
4
5
6
7
8
9
Over-current alarm  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Normal  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Alarming  
Dec., Under  
stop  
cflicking  
lflicking  
lflicking  
hflicking  
Inverter over load alarm  
Motor over load alarm  
Over heat alarm  
Over voltage alarm  
pflicking  
Main circuit undervoltage alarm  
main device overheat alarm  
Under current alarm  
Over-torque alarm  
Braking resistor overload alarm  
-
lflicking  
-
-
-
-
-
-
-
10 Cumulative operation hours alarm  
11 Option communication alarm  
12 Serial communication alarm  
13 MOFFMS (MSrelay off or MOFF)  
Refer to f302  
value  
Refer to f256  
value  
14 Stop after instantaneous power off  
15 Stop after LL continuance time  
-
-
Dec., Under  
stop  
4.2.13. fd06(Input TB Status)  
bit  
0
1
2
3
4
5
6
7
TB Name  
F
Function (Parameter)  
0
1
ON  
-
Input terminal function selection 1 (f111)  
Input terminal function selection 2 (f112)  
Input terminal function selection 3 (f113)  
Input terminal function selection 4 (f114)  
Input terminal function selection 5 (f115)  
Input terminal function selection 6 (f116)  
Input terminal function selection 7 (f117)  
Input terminal function selection 8 (f118)  
R
RES  
S1  
S2  
S3  
OFF  
VIB*1  
VIA*1  
(Undefined) -  
5 to 15  
-
Note: The bit described "Undefined" is unstable. Do not use the bit for the judgment.  
*1: VIA/ VIB are input terminal function when f109is logic input.  
*The input terminal function is selected by each parameter.  
- 27 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
4.2.14. fd07(Output TB Status)  
bit  
0
1
TB Name  
RY-RC  
OUT  
Function (Parameter)  
Output terminal function selection 1A (f130)  
Output TB Function select 2A (f131)  
Output TB Function select 3 (f132)  
-
0
1
OFF  
OFF  
OFF  
-
ON  
ON  
ON  
-
2
FL  
3 - 15  
(Undefined)  
Note: The bit described "Undefined" is unstable. Do not use the bit for the judgment.  
- 28 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E6581738  
5. Diagnostic  
When the communication loss occurs, PDP003Z returns the diagnosis telegram including  
the following information.  
Byte 1: Station Status 1  
Byte 2: Station Status 2  
Byte 3: Station Status 3  
Byte 4: Master station address  
Byte 5: PDP003Z Ident Number high byte (0x0C)  
Byte 6: PDP003Z Ident Number low byte (0x24)  
Byte 7: Diagnostic data lengh  
Byte 8: Status Type (Status message = 0x81)  
Byte 9: Slot Number (Slot number = 0x00)  
Byte 10: Specifier (0=No further diff, 1=Status comes, 2=Status goes)  
Byte 11: External diagnostic data length  
Byte 12: PDP003Z Station Address  
Byte 13: PDP003Z Profile  
Byte 14: Drive CPU1 Major version  
Byte 15: Drive CPU1 Minor version  
Byte 16: PDP003Z software version  
Byte 17: PDP003Z communication network Fault  
Byte 18: PDP003Z internal link Fault  
* It is necessary to set the parameter c101to "4".  
* It is necessary to set it by the configuration to include Byte 7 or more in the response.  
(The figure below is a setting for SIMATEC Step7.)  
- 29 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
6. DP-V1 function  
DP-V1 acyclic communication is mainly used to read/write the parameter. VF-MB1/S15  
parameter and the PROFIBUS parameter can be read/written using PDP003Z.  
The following setting is necessary in the configuration to communicate DP-V1.  
(The figure below is a setting for SIMATEC Step7.)  
Parameter access sequence to VF-MB1/S15 takes place as described in the following  
figure.  
Master  
PROFIBS DP-V1 Communication  
VF-MB1/S15  
Time  
Parameter  
Request  
Parameter  
Request  
Write Request  
Write Response (without Data)  
Read Request (without Data)  
Read Response (with Data)  
Parameter  
Processing  
Parameter  
Response  
Parameter  
Response  
- 30 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
6.1. Example1. Read the PROFIdrive parameter  
6.1.1.  
Write Request data table (Read PNU 964 (0x03C4) IND 4)  
Field  
Header DU0  
Header DU1  
Header DU2  
Description  
Value  
0x5F  
0x00  
0x2F  
0x0E  
0x01  
0x01  
0x01  
0x01  
0x10  
0x01  
0x03  
0xC4  
0x00  
0x04  
Slot number (0)  
Index (47)  
Length  
Header DU3  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Address (Byte 1)  
Parameter Address (Byte 2)  
Parameter Address (Byte 3)  
Parameter Address (Byte 4)  
Parameter Address (Byte 5)  
Parameter Address (Byte 6)  
Request Reference  
Axis  
Number of Parameters  
Attribute (0x10: Value)  
Number of Elements  
Parameter number (PNU), High byte  
Parameter number (PNU), Low byte  
Subindex (IND), High byte  
Subindex (IND), Low byte  
6.1.2.  
Read Response data table (positive)  
Field  
Header DU0  
Header DU1  
Header DU2  
Header DU3  
Description  
Slot number (0)  
Index (47)  
Value  
0x5E  
0x00  
0x2F  
0x08  
Length  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Value (Byte 1)  
Parameter Value (Byte 2)  
Parameter Value (Byte 3)  
Parameter Value (Byte 4)  
* Refer to Appendix.  
Request Reference (mirrored)  
Axis (mirrored)  
Number of Parameters  
Number of Values  
Values, High byte  
Values, Low byte  
0x01  
0x01  
0x01  
0x01  
0x06  
0x01  
0x0A **  
0x90 **  
** Value 0x0A90 is "2704" in decimal. This means "April 27".  
- 31 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
6.2. Example 2. Change the PROFIdrive parameter  
6.2.1.  
Write Request data table (Change, set 0 to PNU 927 (0x039F))  
Field  
Header (DU0)  
Header (DU1)  
Header (DU2)  
Description  
Value  
0x5F  
0x00  
0x2F  
0x0E  
0x01  
0x02  
0x01  
0x01  
0x10  
0x01  
0x03  
0x9F  
0x00  
0x00  
0x06  
0x01  
0x00  
0x00  
Slot number (0)  
Index (47)  
Header (DU3)  
Length  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Address (Byte 1)  
Parameter Address (Byte 2)  
Parameter Address (Byte 3)  
Parameter Address (Byte 4)  
Parameter Address (Byte 5)  
Parameter Address (Byte 6)  
Parameter Value (Byte 1)  
Parameter Value (Byte 2)  
Parameter Value (Byte 3)  
Parameter Value (Byte 4)  
* Refer to Appendix.  
Request Reference  
Axis  
Number of Parameters  
Attribute  
Number of Elements  
Parameter number (PNU), High byte  
Parameter number (PNU), Low byte  
Subindex (IND), High byte  
Subindex (IND), Low byte  
Number of Value  
Values, High byte  
Values, Low byte  
Read Response data table (positive)  
Field  
Header DU0  
Header DU1  
Header DU2  
Description  
Slot number (0)  
Index (47)  
Length  
Request Reference (mirrored)  
Axis (mirrored)  
Value  
0x5E  
0x00  
0x2F  
0x04  
0x01  
0x02  
0x01  
0x01  
Header DU3  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Number of Parameters  
6.2.2.  
Read Response data table (negative, set 2 to PNU 927)  
Field  
Header DU0  
Header DU1  
Header DU2  
Header DU3  
Description  
Value  
0x5E  
0x00  
0x2F  
0x08  
0x01  
0x82  
0x01  
0x01  
0x44  
0x01  
0x00  
0x01  
Slot number (0)  
Index (47)  
Length  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Value (Byte 1)  
Parameter Value (Byte 2)  
Parameter Value (Byte 3)  
Parameter Value (Byte 4)  
* Refer to Appendix.  
Request Reference (mirrored)  
Axis (mirrored)  
Number of Parameters  
Format (0x44: Error) *  
Numner of Vlaues  
- 32 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
6.3. Example 3. Read the VF-MB1/S15 parameter  
When access to VF-MB1/S15 parameter, set “1000” to the PNU.  
6.3.1.  
Write Request data table (Read fd04(Input voltage))  
Field  
Header DU0  
Header DU1  
Header DU2  
Description  
Value  
0x5F  
0x00  
0x2F  
0x0A  
0x01  
0x01  
0x01  
0x01  
0x10  
0x01  
0x03  
0xE8  
0xFD  
0x04  
Slot number (0)  
Index (47)  
Length  
Header DU3  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Address (Byte 1)  
Parameter Address (Byte 2)  
Parameter Address (Byte 3)  
Parameter Address (Byte 4)  
Parameter Address (Byte 5)  
Parameter Address (Byte 6)  
* Refer to Appendix.  
Request Reference  
Axis  
Number of Parameters  
Attribute  
Number of Elements  
Parameter number, High byte **  
Parameter number, Low byte **  
VF-MB1/S15 Parameter number, High byte  
VF-MB1/S15 Parameter number, Low byte  
** Parameter number is fixed to 0x03E8 (1000) for accessing to VF-MB1/S15 parameter.  
6.3.2.  
Read Response data table (positive)  
Field  
Header DU0  
Header DU1  
Description  
Value  
0x5E  
0x00  
Slot number (0)  
Index (47)  
Header DU2  
0x2F  
Header DU3  
Length  
0x08  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Value (Byte 1)  
Parameter Value (Byte 2)  
Parameter Value (Byte 3)  
Parameter Value (Byte 4)  
* Refer to Appendix.  
Request Reference (mirrored)  
Axis (mirrored)  
Number of Parameters  
Number of Values  
Values, High byte  
Values, High byte  
0x01  
0x01  
0x01  
0x01  
0x42  
0x01  
0x31 **  
0xEC **  
** Value 0x31EC is "12780" in decimal. This means "127.80 (%)".  
- 33 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
6.4. Example 4. Change the VF-MB1/S15 parameter  
When access to VF-MB1/S15 parameter, set “1000” to the PNU.  
* This procedure changes the value of VF-MB1/S15 EEPROM.  
6.4.1.  
Write Request data table (Change, set 7 to VF-MB1/S15 parameter f130)  
Field  
Header DU0  
Header DU1  
Header DU2  
Description  
Value  
0x5F  
0x00  
0x2F  
0x0E  
0x01  
0x02  
0x01  
0x01  
0x10  
0x01  
0x03  
0xE8  
0x01  
0x30  
0x42  
0x01  
0x00  
0x07  
Slot number (0)  
Index (47)  
Header DU3  
Length  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Address (Byte 1)  
Parameter Address (Byte 2)  
Parameter Address (Byte 3)  
Parameter Address (Byte 4)  
Parameter Address (Byte 5)  
Parameter Address (Byte 6)  
Parameter Value (Byte 1)  
Parameter Value (Byte 2)  
Parameter Value (Byte 3)  
Parameter Value (Byte 4)  
* Refer to Appendix.  
Request Reference  
Axis  
Number of Parameters  
Attribute  
Number of Elements  
Parameter number, High byte **  
Parameter number, Low byte **  
VF-MB1/S15 Parameter number, High byte  
VF-MB1/S15 Parameter number, Low byte  
Number of Value  
Value, High byte  
Value, Low byte  
** Parameter number is fixed to 0x03E8 (1000) for accessing to VF-MB1/S15 parameter.  
6.4.2.  
Read Response data table (positive)  
Field  
Header DU0  
Header DU1  
Header DU2  
Header DU3  
Description  
Value  
0x5E  
0x00  
0x2F  
0x04  
0x01  
0x02  
0x01  
0x01  
Slot number (0)  
Index (47)  
Length  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
* Refer to Appendix.  
Request Reference (mirrored)  
Axis (mirrored)  
Number of Parameters  
6.4.3.  
Read Response data table (negative,at set 256 to f130)  
Field  
Header DU0  
Header DU1  
Header DU2  
Header DU3  
Description  
Slot number (0)  
Value  
0x5E  
0x00  
0x2F  
0x08  
0x01  
0x82  
0x01  
0x01  
0x44  
0x01  
0x00  
0x02  
Index (47)  
Length  
Request Header (Byte 1)  
Request Header (Byte 2)  
Request Header (Byte 3)  
Request Header (Byte 4)  
Parameter Value (Byte 1)  
Parameter Value (Byte 2)  
Parameter Value (Byte 3)  
Parameter Value (Byte 4)  
* Refer to Appendix.  
Request Reference (mirrored)  
Axis (mirrored)  
Number of Parameters  
Numner of Vlaues  
- 34 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
E6581738  
7. PROFIBUS Local/Remote Operation  
The example below shows how to configure the VF-MB1 for local/remote operation.  
<Terminal function>  
F terminal............ RUN command  
R terminal............ Local (Terminal in this example) / PROFIBUS switching  
VIA terminal ........ Operation frequency command  
<Wiring>  
VF-MB1  
Variable resistor for adjustment  
10k ohm  
PP  
VIA  
CC  
SW1  
F
Operation command  
SOURCE SINK  
R
Local/PROFIBUS  
Switch  
P24  
OUT  
<Parameter setting>  
cmod(command mode selection) = 0 (terminal board)  
fmod(frequency setting mode selection 1) = 1 (VIA)  
f112(input terminal selection 2 (R)) = 48 (Local/PROFIBUS control)  
<Operation>  
R-CC terminal open:  
VF-MB1 is controlled as slave device of PROFIBUS.  
R-CC terminal closed:  
F-CC terminal short to RUN  
F-CC terminal open to STOP  
Output frequency is set up by the VIA signal input.  
8. GSD file  
As for acquisition of an GSD file for VF-MB1 and VF-S15, please contact your Toshiba  
distributor.  
- 35 -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
   
E6581738  
9. Appendix  
Function number  
0x5E: Read Request  
0x5F: Write Request  
0x5E: Positive response for Read request  
0x5F: Positive response for Write request  
0xDE: Negative response for Read request  
0xDF: Negative response for Write request  
Request ID  
0x01: Request the value  
0x02: Change the value  
Response ID  
0x01: Positive response for Request the value  
0x02: Positive response for Change the value  
0x81: Negative response for Request the value  
0x82: Negative response for Change the value  
Axis  
0x00: (Fixed for PDP003Z)  
Error number  
0x00: Impermissible parameter number  
0x01: Impermissible parameter number  
0x02: Low or High limit exceeded  
0x03: Faulty subindex  
0x04: No array  
0x05: Incorrect data type  
0x06: Setting not permitted (may only be reset)  
0x07: Description element cannot be changed  
0x09: No description data available  
0x0B: No operation priority  
0x0F: No text array available  
0x11: Request cannot be executed because of operating state  
0x14: Value impermissible  
0x15: Response too long  
0x17: Write Req., Illegal format/format of the parameter data is not supported  
0x18: Number of values are not consistent  
0x19: Axis/DO non existent  
0x20: Parameter text element cannot be changed  
Format  
0x01: Boolean  
0x02: Integer 8  
0x03: Integer 16  
0x04: Integer 32  
0x05: Unsigned 8  
0x06: Unsigned 16  
0x07: Unsigned 32  
0x08: FloatingPoint  
0x09: VisibleString  
0x10: OctetString  
0x12 TimeOfDay (with date indication)  
0x13: TimeDifference  
0x40: Zero  
0x41: Byte  
0x42: Word  
0x43: Double word  
0x44: Error  
- 36E -  
Download from Www.Somanuals.com. All Manuals Search And Download.  
           

Targus Mouse Mini Mouse User Manual
Tiger Table Top Game 7 701 User Manual
Timex Clock T020 User Manual
Toshiba Fax Machine GD 1260 User Manual
TrekStor Network Card maxi gu User Manual
Tripp Lite Mouse IN3008KB User Manual
Tripp Lite Network Cables F007 006 User Manual
Universal Remote Control Universal Remote UR2 CBL CV04 User Manual
Viking Range F20542B User Manual
Weber Charcoal Grill 3994601 User Manual