Toro Sprinkler TDC 100 200 User Manual

TDC-100/200  
User’s Guide  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Index  
Introduction - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4  
General Editing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 4  
Timing Mechanism Components - - - - - - - - - - - - - - - - - - - - - - - - - - 5  
Mother Board Components - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6  
Daughter Board Components - - - - - - - - - - - - - - - - - - - - - - - - - - - - 6  
Power-Up Diagnostics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7  
Home Key - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 7  
System Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 8–9  
Station Settings - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 10  
Scheduled Watering - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 11–13  
• Standard Irrigation Program - - - - - - - - - - - - - - - - - - - - - - - 11–12  
• Grow-In Irrigation Program - - - - - - - - - - - - - - - - - - - - - - - - - - 13  
Manual Watering - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14–15  
• Multi-Manual - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 14  
• Manual Syringe - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15  
• Manual Program - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 15  
% (Percent) Adjust - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16  
Start Key - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 16  
Pause / Resume Key - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 17–18  
Stop Key - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 18  
Diagnostics - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 19  
Fuse and Circuit Breaker Specifications - - - - - - - - - - - - - - - - - - - - 20  
Controller Specifications - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - 20  
Electromagnetic Compatibility - - - - - - - - - - - - - - - - - - - - - - - - - - - 20  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
Introduction  
The Toro TDC-100/200 combines modular flexibility, ease of use and increased programmability in a single controller.  
Modularity means flexibility. The TDC-100/200 can control up to 200 stations.  
The intuitive user interface is easy to use and includes a backlight for improved visibility in low-light conditions, yet it is  
completely viewable in direct sunlight. The faceplate’s combination of menu keys, navigation arrows and Input Dial  
allows for easy menu navigation and quick settings establishment.  
With 10 irrigation programs, the TDC-100/200 allows programming flexibility.  
General Editing  
Pressing a menu key on the TDC-100/200 will display menu items. Items with fields containing values that can be  
edited are called Entry Fields. Use the Arrow Keys  
to navigate through the menus and entry  
. Values will be  
will also  
fields. Modify any selected value by scrolling through the selection using the Input Dial  
saved automatically when you exit an entry field or press another menu key. Pressing the HOME Key  
save any modification and revert back to Home display.  
Additionally, if no keypad activity is detected within five minutes, the controller will automatically save any  
modifications and revert back to Home display.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Timing Mechanism  
TDC-100/200  
3
2
1
4
5
6
7
8
9
HOME  
MANUAL  
WATERING  
SCHEDULED  
WATERING  
DIAGNOSTICS  
STATION  
SETTINGS  
10  
11  
12  
13  
14  
%ADJUST  
START  
PAUSE/  
RESUME  
STOP  
SYSTEM  
SETTINGS  
1
Left and Right Arrows allow you to select the next entry field within the same menu line. Any  
changes will be saved after you exit that entry field.  
2
3
4
5
Up and Down Arrows allow you to scroll up and down through the menu items.  
LCD Panel is the display screen.  
Input Dial allows you to scroll through the value selection within the selected entry field.  
Home Key allows you to exit from any function menu and return the controller to normal operation. After  
pressing the Home Key, all modifications to the settings will be saved.  
6
7
Manual Watering Menu Key allows you to activate station(s) or program(s) manually.  
Scheduled Watering Menu Key allows you to create/modify irrigation programs. Use this function to  
assign the program type (Standard or Grow- In), watering days, start times, end times, delay times, syringe  
duration, repeats, soak time, stations, run times and maximum simultaneous stations per program.  
8
9
Diagnostics Menu Key allows you to run communications test with each decoder and solenoids.  
Station Settings Menu Key allows you to modify station parameters. Within this setting, you can set  
the station number and assign it to a specific decoder, decoder station and path, specify each station’s  
percent adjust, disable the station from any activity by placing a station hold for a specific number of days, set  
the station type to a switch and create or edit the station description/name.  
10  
Percent Adjust Menu Key allows you to adjust watering to a specific percentage range. The user can  
specify percentage adjustment for the system, programs and stations.  
11  
12  
Start Key will execute selected program or manual operation.  
Pause/Resume Key will pause currently activated program(s). Press the key while in pause and select  
Resume to continue operation.  
13  
14  
Stop Key will cancel currently running program(s) or station(s).  
System Settings Menu Key allows the user to modify the controller parameters. Users can specify  
the hold duration for controller’s activity, set language, time, date, day change, station delay, maximum  
number of stations to run simultaneously, adjust display contrast and specify sensor type. Within this menu,  
the user can also reset all programs, reset the station parameters and reset all disables.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
10  
Mother Board  
4
2
3
7
9
11  
5
6
12 13  
14  
8
15  
16  
Mother Board Components  
Daughter Board  
1
Station Watering LED  
Pump ON LED  
2
3
4
5
6
7
8
9
Pump Pressure LED  
Rain Sensor LED  
Power LED  
PC Connection LED  
Tx LED  
17  
Rx LED  
Mother Board Fuse, 3.15A Slow-Blow  
10 Timing Mechanism Cable Socket  
11 RS-232 Fiber/Wire Switch  
12 Pump Output  
13 Pump Pressure Input  
14 Rain Switch Input  
15 RS-232 Input  
Daughter Board Components  
16 Power LED  
17 Daughter Board Fuse (8), 3.15A Fast-Blow  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Power-Up Diagnostics  
Upon power-up, the controller will display:  
TDC–100/200 System  
Booting  
The TDC-100/200 will initiate a diagnostic test automatically during power-up. This function will take approximately  
ten seconds and it can not be bypassed. If a problem is detected during the diagnostic test, it will be indicated on the  
display.  
When completed, information will be displayed momentarily on the screen for five seconds. This status information  
can not be edited. The information is as follows:  
Line 1: TDC-100/200 Firmware Version and Revision Date  
Line 2: Detect: [xx stations, yy sensors] (xx = number of stations detected, yy = number of sensors detected)  
Line 3: Last Power Downtime Date and Time  
Example:  
Rev: D1.21, 04/25/06  
Detect:200sta, 00sen  
PD 05/24/06 10:51:20  
The default Home display will follow after the diagnostic display has timed-out.  
Home display example:  
Mon 08/07/06 10:50am  
Sec: 45  
Day Change: 12:00am  
Home Key  
Pressing the Home Key will revert to the default display. When editing irrigation programs, Station or System  
settings, pressing the Home Key will save any setting modifications and return the user to the Home display.  
Home display example:  
Mon 08/07/06 10:50am  
Sec: 45  
Mon 08/07/06 11:15am  
Sec: 50  
Rain  
Rain detected indicator for rain sensor  
equipped Decoder systems  
Day Change: 12:00am  
Day Change: 12:00am  
The Day Change line will display the next program start time (Next Start: HH:MM) if the current day is an active  
watering day. If the controller is running a program, the Day Change line will display Running XX programs to  
indicate the number of active programs.  
The following example display has two programs running with two stations manually activated, the display will read:  
Wed 08/09/06 06:50am  
Sec: 32  
Running 02 Programs  
(The “%” symbol before the runtime indicates that station 1 is percent adjusted.)  
(P01 indicates Program 01 is currently active)  
(The “D” symbol after the station number indicates that station 3 is disabled.)  
(The “P” symbol after the station number indicates that program 02 is paused.)  
P01 Sta01 %00:05:00  
P01 Sta02 00:05:00  
P01 Sta03D 00:05:00  
P02 Sta10P 00:10:00  
(“Man” indicates Manual Watering is currently active)  
(The “S” symbol after the station number indicates that program 02 is stacked.)  
Man Sta18S 00:05:00  
Man Sta19S 00:10:00  
Note: Program stacking occurs when the controller is running a program where the maximum simultaneous station  
limit is surpassed. Additional scheduled programs will be stacked (delayed) until an available station can be activated.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
System Settings  
System Settings allows you to set controller parameters such as Time, Date and Language.  
Use the Up or Down Arrows  
Use the Left and Right Arrow  
Use the Input Dial  
to navigate through the menus.  
to advance to the next entry field on the same menu line.  
to select values when editing.  
Language: –  
Default, English. Future option, Spanish, French, German and Italian.  
Use this function to set the current time.  
Clock Set: –  
Clock Mode: – Use this function to select the clock mode between Am/Pm (12-Hour) and 24-Hour mode.  
Date: – Use this function to set the current date.  
Day Change: – Use this function to set the “day change” time. The “day change” is the specified time that the  
controller will advance the date. The default day change is 12:00 am. Adjusting the day change  
time will allow programs to start throughout the night on the same active day schedule. Programs  
with runtimes beyond the day change time are allowed to finish.  
System Mode: – Use this function to toggle between Golf and Commercial modes.  
LP Shutdown: – The TDC system can be equipped with a low pressure system to detect system failure. Use this  
function to set the wait time until the controller reevaluates the low pressure condition before  
shutting the whole system down. This delay will eliminate system shutdown when pressure  
intermittently fluctuates.  
Sta Delay: –  
Use this function to set the controller’s station delay. The station delay determines the wait time  
before next station is activated when a station has concluded its watering cycle. This delay is used  
to allow the system to normalize between station activations.  
Max Sim Sta: – Use this function to set the maximum number of simultaneously operating stations. This threshold  
will be applied to all programs and manual irrigation functions. Each program can then be set with  
a lower limitation if necessary.  
Example: The controller is set with a maximum simultaneous active stations of 7. All programs in  
the controller will adhere to the 7 maximum active stations and each can be adjusted with a lower  
limit (6, 5, 4, etc.).  
Units: –  
Use this function to change the controller units between English (U.S. Standard) and Metric units.  
Display Adj: –  
Use this function to adjust the contrast of the LCD screen. Use the Input Dial  
darken or lighten the text display.  
to  
Sensor: –  
(For future use.)  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hold For: –  
Use this function to suspend controller operation and choose the suspension duration from Today,  
02-30 days, Permanent or None.  
Reset Prg’s: – Use this function to reset all controller irrigation program by selecting Yes. After selecting Yes,  
press the Up or Down Arrows  
to activate. The following will display:  
Reset All Programs  
to defaults  
05  
STOP to escape  
All program data will be erased after a successful reset.  
Reset Sta’s: –  
Use this function to reset all station settings by selecting Yes. After selecting Yes, press the Up or  
Down Arrows  
to activate. The following will display:  
Reset All Stations  
to defaults  
05  
STOP to escape  
All station settings will be erased after a successful reset.  
Reset Unit: –  
Use this function to reset the controller settings by selecting Yes. After selecting Yes, press the Up  
or Down Arrows  
to activate. The following will display:  
Reset All Defaults  
10  
STOP to escape  
After the 10-second countdown, the controller will reboot.  
Resetting the unit will erase all user-defined program data and configuration values in the  
controller’s memory.  
Reset Disab : – Use this function to reset all stations that are disabled by selecting Yes to the selection. After  
selecting Yes, press the Up or Down Arrows  
to activate. The following will display:  
Reset Sta Disables  
10  
STOP to escape  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Station Settings  
Station Settings allows you to set parameters specific to each station.  
Use the Up or Down Arrows  
to navigate through the menus.  
Use the Left and Right Arrow Keys  
to advance to the next entry field on the same menu line.  
Use the Input Dial  
to select values when editing.  
S01 –  
Select the station you want to edit in this field. Choose from  
Station 01 through the controller maximum station count of  
200.  
S100 100% 1STSTLAWN  
Decoder Addr: 38684  
Dec Sta: 4 Path: 2  
Disable: No  
100% –  
If weather or other condition requires irrigation program  
modification, it can be easily adjusted by changing the percent  
adjustment. Station operation can be reduced to 000% (Off) or  
increased up to 900%. 100% represents standard operation.  
Set Sta as a MV: NO  
Assn Sta to MV: 000  
Sched today: NONE  
Water today: NONE  
Decoder Addr: –  
Enter the decoder’s 5-digit address code that corresponds to  
the selected station.  
DecSta: –  
If using a 2 or 4-station decoder, select the decoder station to  
designate to the selected station.  
Is Switch: NO  
Hold Sta : NO  
Decoder Station Color Codes  
Cycles : 01 times  
Edit Name: 01TE020  
RED = Station 1, GREEN = Station 2, ORANGE = Station 3,  
BLUE = Station 4  
FlowSens:03StaFlo200  
Output Volts: 15  
Path: –  
Select the correct wire path (1 or 2). Enter wire path 01 for  
stations connected to the 1st daughter board and wire path 2  
for the 2nd daughter board.  
Disable: –  
Use this function to disable station operation by selecting Yes  
from the menu. Resume station operation by selecting No from  
the menu.  
Set Sta as a MV: – Use this function to designate the station to operate as a Master valve (up to 6) by selecting Yes.  
Suggestion: Assign station number that will not interfere with your programming such as  
100 or 200.  
Assn Sta to MV: – Use this function to assign a station to run with a specific master valve (Not available if the  
station is designated as a Master Valve).  
Sched Today: –  
Water Today: –  
Is Switch: –  
This function will display the total scheduled station runtime for the current day.  
This function will display the total station runtime that has occurred for the current day.  
Use this function to assign the selected station to a switch. When the switch (station) is  
activated, the Master Valve or Pump will not actuate.  
Hold Sta: –  
Use this function to delay operation for this station. Select the hold duration from 01–30 days,  
Permanent or None. This function is useful when a specific station needs to be deactivated  
without affecting any of the programs.  
Cycles: –  
(For Future Use)  
Edit Name: –  
Use this function to assign a name description to the station. In Golf mode, the naming format is  
XX-AA-YYY, where XX represents the golf course hole number, AA represents the area  
description acronym and YYY represents the sprinkler number within the area. By following the  
naming format, you can easily figure out where and what area the station is watering.  
Area Description Acronym Listing  
GR = Greens DR = Driving Range TE = Tee CL = Club House FW = Fairways  
LA = Landscape RF = Rough PG = Putting Green AP = Approaches MS = Misc.  
In Commercial mode, assign a 10-character name of your choice, such as “shrubs” or  
“back lawn”.  
Flow Sens: –  
(For future use.)  
Output Volts: –  
Use this function to select the controller’s output voltage. Select between 15 or 20 volts DC.  
Important! For proper operation, install compatible DC-latching solenoids only.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Scheduled Watering  
The TDC-100/200 features 10 fully-independent resident programs. With two types of programs to select from,  
you can further custom fit your irrigation programs to any landscape.  
Standard Irrigation Program will activate a station or group of stations with six start times on a daily basis. Each  
station will water for the duration specified in hours, minutes and seconds. Percent adjust and maximum number of  
simultaneous activate stations per program can be specified in this program.  
• Grow-In Irrigation Program will activate a station or group of stations for the length of their runtime. The program  
will repeat the cycle after the specified delay time expires and will repeat continuously between the set Start and  
End times. Percent adjust and the simultaneous activate stations can be specified in this program.  
To utilize these programs automatically or manually, each program must be configured.  
Standard Irrigation Program Setting:  
Standard Irrigation Program example: Create Program 02 with stations 6–10 running 15 minutes each and stations  
15–20 running 10 minutes each with no percent adjustments. Set the start time at 6:30 am with five maximum  
simultaneous active station.  
1. Press the Scheduled Watering Key  
Input Dial to select the program (P01–P10) you want to create or modify. For this example, select 2.  
2. Press the Right Arrow Key to standard to the Percent Adjust field. Normally this setting will be 100%  
. The cursor is initially located at the program selection field. Use the  
unless weather or other condition suggest that less or more irrigation is needed. Use the Input Dial  
to adjust the setting. For this example, no adjustment is needed.  
3. Press the Down Arrow  
operation. Select from None, Today, 0230 days or Permanent. For this example, select None.  
4. Press the Down Arrow to advance the cursor to the Type: field. Use the Input Dial  
the setting. For this example, set the Type to Standard.  
5. Press the Down Arrow to advance the cursor to the Days: field. Use the Input Dial  
to advance the cursor to the Hold: field. Use this function to suspend program  
to adjust  
to select  
the program activation interval from 01–30 days. Select 01 for everyday, 02 for every other day, 03 for every  
third day and so on. The example does not call for a set interval. Leave the Days: setting to SMTWTFS...  
6. Press the Down Arrow  
from any of the preset intervals (All, Alternate days, Weekdays only, Weekends only, None or User set). To  
create your own program activation interval, select Set:. Use the Right Arrow Key to select the day of the  
week you want to irrigate and use the Input Dial to activate (X) or deactivate (blank) the selection.  
to advance the cursor to the Set: field. Use the Input Dial  
to select  
For this example, activate M (monday), W (wednesday) and F (friday) only. MWF of the 1st and 2nd week  
should have an X mark under while the rest are blank.  
7. Press the Down Arrow  
time number. Each program can have a maximum of 24 start times. Use the Input Dial  
the start time being created or modified. Press the Right Arrow Key to advance to the time entry field.  
Use the Input Dial to select the start time in hours and minutes ( HH:MM). Repeat Step 7 for  
to advance the cursor to the Start: field. The first entry field will indicate the start  
to choose  
additional start times. For this example, set start time 01 to 05:45am.  
(Continued to the next page)  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Press the Down Arrow  
to advance the cursor to the Sta Dly: field. Use the Left and Right Arrow Keys  
to set the Station  
to navigate between the Hour and Minute fields. Use Input Dial  
Delay duration. Station delay is the wait period when a station finished watering and when the next station is  
activated. In most situations, station delay is used to allow slow -shutting valves time to fully close before  
activating another station and also to allow the water source, such as a well, to recover. For this example, set  
Station Delay to remain at 00.  
9. Press the Down Arrow  
to advance the cursor to the Syringe: field. Use the Input Dial  
to set  
the Syringe duration. When a syringe duration (0–99 minutes) is set, an asterisk is placed in front of the start  
time number to indicate that this start time is a syringe start. During a syringe, the stations will all activate for  
the syringe duration regardless of their assigned runtimes. For this example, do not set a Syringe duration.  
10. Press the Down Arrow  
to advance the cursor to the Repeats#: field. Use the Input Dial  
to  
enter the number of times the program will repeat the cycle. For this example,set Repeat to remain at 00.  
11. Press the Down Arrow  
the soak duration before the station is reactivated. For this example, set a soak duration of 00:10:00.  
12. Press the Down Arrow to advance the cursor to the Sta#: field. Use the Input Dial  
the first station being irrigated in the sequence. For this example, select station 06.  
13. Press the Right Arrow to advance the cursor to the next value. This value will indicate the last station in  
to advance the cursor to the Soak#: field. Use the Input Dial  
to enter  
to select  
the sequence. If irrigating only one station, this value will be the same as the first value. For this example,  
select station 10. With 6 being the first station and 10 being the last station, the program schedule will water  
stations 6, 7, 8, 9 and 10 in sequentially.  
14. Press the Right Arrow  
to advance the cursor to the next entry field. This entry field will indicate the  
runtime in hours, minutes and seconds ( HH:MM:SS). Use the Input Dial  
and the Right Arrow Key  
to select the appropriate runtime value. For this example, set the value to 00:15.  
Repeat Steps 8–10 to assign stations 10–20 with a runtime of 10 minutes.  
15. Press the Down Arrow  
to advance the cursor to the Simult: field. Use the Input Dial  
to select  
the maximum allowable simultaneous active station. For this example, set the value to 05.  
Note: The Program’s Simultaneous setting is limited to the System’s Simultaneous value.  
When finished, the display should read:  
P02 100% 01:15:00  
Hold: None  
Type: Standard  
Days: SMTWTFSSMTWTFS  
set>:  
Start : 01 05:45am  
Sta Dly: 00:00 (h:m)  
Syringe: 00 min  
Repeats: 00  
Soak: 00:10:00  
Sta#: 06-10 00:15  
Sta#: 15-20 00:10-  
Sta#: ––––––– ––:––  
Simult: 05  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Grow In Irrigation Program Setting:  
Grow In Irrigation Program example: Create program 3 with stations 21–30 for 5 minutes each with no percent  
adjustment. Set the start time at 6:30 am and the end time at 4:00 pm. Set the delay for 2 hours and 15 minutes and  
the maximum simultaneous active station to 5.  
1. Press the Scheduled Watering Key  
. The cursor is initially located at the program selection field. Use the  
Input Dial  
to select the program (P01–P10) you want to create or modify. For this example, select  
program 3.  
2. Press the Right Arrow Key  
to advance to the Percent Adjust field. Normally this setting will be 100%  
unless weather or other condition suggest that less or more irrigation is needed. Use the Input Dial  
to adjust the setting. For this example, no adjustment is needed.  
3. Press the Down Arrow  
operation. Select from None, Today, 0230 days or Permanent. For this example, select None.  
4. Press the Down Arrow to advance the cursor to the Type: field. Use the Input Dial  
the setting. For this example, set the Type to Grow-In.  
5. Press the Down Arrow to advance the cursor to the Start: field. This start time will indicate the starting  
point of the Grow-In cycle. Use the Input Dial to select the start time value. Use the Left and Right  
to advance the cursor to the Hold: field. Use this function to suspend program  
to adjust  
Arrow Keys  
to navigate between the Hours and Minutes fields. For this example, set the start time  
to 06:30am.  
6. Press the Down Arrow  
to advance the cursor to the End: field. This end time will indicate the end point of  
the Grow-In cycle. Use the Input Dial  
to select the end time value. Use the Left and Right Arrow  
Keys  
to navigate between the Hours and Minutes fields. For this example, set the end time to  
04:00pm.  
7. Press the Down Arrow  
to advance the cursor to the Delay: field. This delay time will determine the wait  
to select the delay time value. Use the Left and  
to navigate between the Hours and Minutes fields. For this example, set the  
time between program cycles. Use the Input Dial  
Right Arrow Keys  
delay time to 02:15.  
8. Press the Down Arrow  
to advance the cursor to the Sta#: field. Use the Input Dial  
to select  
the correct value of the first station being irrigated. For this example, select station 21.  
9. Press the Right Arrow  
to advance the cursor to the next value. This value will indicate the last station of  
the range. If irrigating only one station, this value should be the same as the first value. For this example, select  
station 30.  
10. Press the Right Arrow  
runtime in hours, minutes and seconds (HH:MM:SS). Use the Input Dial  
to select the appropriate runtime value. For this example, set the runtime to 00:05.  
to advance the cursor to the next entry field. This entry field will indicate the  
and the Right Arrow Key  
11. Press the Down Arrow  
to advance the cursor to the Simult: field. Use the Input Dial  
to select  
the maximum allowable simultaneous active station. For this example, set the value to 05.  
When finished, the display should read:  
P03 100% 00:50:00  
Hold: None  
Type: Grow In  
Start: 06:30am  
End: 04:00pm  
Delay: 02:15(hr:min)  
Sta#: 21–30 00:05  
Sta#: ----- --:--:--  
Simult: 05  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Manual Watering  
The Manual Watering functions are used for additional watering if the irrigation program is not sufficient.  
They can also be used to troubleshoot each station for proper operation. Pressing the Manual Watering Key will  
access three manual irrigation functions; Multi-Manual, Syringe and Program.  
M-Manual - Select M-Manual to activate a station or group of stations with a specified runtime.  
Multi-Manual Station Activation Directions  
Manual station activation example: Activate stations 1–12 with a runtime of 5 minutes each and limit watering to 3  
stations simultaneously.  
Note: The Multi-Manual function is limited to the maximum simultaneous station settings of the controller. In cases  
where a program is running and a multi-manual activated, the controller will activate all stations specified in the  
multi-manual in addition to the currently activated stations. Thus, the multi-manual will allow the controller to exceed  
the maximum simultaneous station settings.  
1. Press the Manual Watering Key  
.
2. The cursor should be located in the Manual field, use the Input Dial  
to select M-Manual.  
3. Press the Down Arrow  
to advance the cursor to the Sta#: field. Use the Input Dial  
to select  
the correct value of the first station being irrigated. For this example, select station 01.  
4. Press the Right Arrow  
to advance the cursor to the next value. This value will indicate the last station of  
the range. If irrigating only one station, this value should be the same as the first value. For this example, select  
station 12.  
5. Press the Right Arrow  
runtime in hours, minutes and seconds (HH:MM:SS). Use the Input Dial  
to select the appropriate runtime value. For this example, set the value to 00:05.  
to advance the cursor to the next entry field. This entry field will indicate the  
and the Right Arrow Key  
6. Press the Down Arrow  
to advance the cursor to the next entry field. Notice that a new Station: line was  
created. Fill this line only if irrigating multiple ranges of stations, otherwise, leave this line blank.  
7. Press the Down Arrow  
to advance the cursor to the Simult: field. Use the Input Dial  
to select  
the maximum simultaneous irrigating stations. For this example, set the value to 03.  
8. Once finished, press the Start Key  
the default display.  
to activate or press the Home Key  
to cancel and revert back to  
Note: Pressing the Home Key will save the entered values.  
When finished, the display should read:  
Manual: M-Manual  
Sta#: 01-12 00:05  
Sta#: ----- --:--  
Simult: 03  
Press START to water  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Syringe - Choose Syringe to activate all the stations in a selected irrigation program for a specified runtime.  
Note: The Maximum number of simultaneous stations set in the program still applies.  
Manual Syringe Activation Directions  
Syringe activation example: Manually activate all the stations in Program 3 for 2 minutes each.  
Note: An irrigation program must be configured to activate Manual Syringe.  
1. Press the Manual Watering Key  
2. The cursor should be located in the Manual field. Use the Input Dial  
3. Press the Down Arrow to advance the cursor to the Runtime: field. Use the Input Dial  
.
to select Syringe.  
to  
select the correct value of the runtime in minutes. For this example, set the value to 02 minutes.  
Note: The Runtime setting in Syringe will not affect the actual runtime in the program.  
4. Press the Down Arrow  
to advance the cursor to the Program: field. Use the Input Dial  
to  
select the correct program to syringe. For this example, select program 03.  
5. Once finished, press the Start Key  
the default display.  
to activate or press the Home Key  
to cancel and revert back to  
Note: Pressing the Home Key will save the entered values.  
When finished, the display should read:  
Manual: Syringe  
Runtime: 02 min  
Program: 03  
Press START to water  
Start Program - Select Start Prog to activate a watering program regardless of its set start time.  
Manual Program Activation Directions  
Start Program example: Manually activate Program 08.  
Note: An irrigation program must be configured to activate Manual Program. A program on hold can still be  
manually activated.  
1. Press the Manual Watering Key  
.
2. The cursor should be located in the Manual field. Use the Input Dial  
to select Start Prog.  
to advance the cursor to the Program: field. Use the Input Dial  
3. Press the Down Arrow  
to  
select the correct program value. For this example, select program 08.  
4. Once finished, press the Start Key  
the default display.  
to activate or press the Home Key  
to cancel and revert back to  
Note: Pressing the Home Key will save the entered values.  
When finished, the display should read:  
Manual: Start Prog  
Program: 08  
Press START to water  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
% (Percent) Adjust  
The percent adjust function allows you to fine tune irrigation programs. With weather conditions changing  
constantly, Percent Adjust allows you to tune your system easily without changing all the values in the program.  
Important: The settings do not override each other, instead, they multiple each other to get the effective adjustment.  
Example: Controller is set at 150%, Program is set at 125% and Station is set at 90%. The effective watering  
adjustment is calculated to be 1.5 x 1.25 x 0.9 = 1.68 or 168%.  
Percent Adjust...  
Global will adjust from 1–250%  
Program will adjust from 10–250%  
Station will adjust from 0–250%  
Global:  
100%  
Program : P01 100%  
Station : S01 100%  
% Adjust Directions  
1. Press the % Adjust Key  
. The cursor is initially located at the System % Adjust field. Use the Input Dial  
to adjust the controller watering up to 900% or down to 1%.  
Note: The controller adjustment will affect all stations and programs universally. Do not adjust the System %  
settings if adjustment is station or program specific.  
2. Press the Down Arrow  
program selection field. Use the Input Dial  
Arrow  
to advance the cursor to the Program: field. The first entry field will be the  
to select the program being adjusted. Press the Right  
to adjust the program  
to advance the percent adjustment field. Use the Input Dial  
watering up to 250% or down to 10%. Repeat step 2 to adjust additional programs.  
Note: Do not adjust the program % setting if adjustment is station specific.  
3. Press the Down Arrow  
to advance the cursor to the Station: field. The first entry field will be the station  
selection field. Use the Input Dial  
to select the station being adjusted. Press the Right Arrow  
to advance to the percent adjustment field. Use the Input Dial  
900% or down to 000%. Repeat step 3 to adjust additional stations.  
to adjust the station watering up to  
Note: Adjusting the station’s watering to 000% will prevent it from running within a program. Multi-Manual and  
Syringe are not affected by the % Adjustment.  
Start Key  
The Start key is used to execute a manual function.  
Note: Pressing the Start key while the controller is idle will prompt the Manual Watering menu.  
Multi-Manual Start Display  
Multi-Manual  
Starting  
03  
STOP to cancel  
Manual Syringe Start Display  
Syringe Starting  
Program 01  
03  
STOP to cancel  
Manual Start Program Display  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pause / Resume Key  
The Pause command is used to suspend active program or manual irrigation. The Pause function allows the  
user to specify the pause duration.  
Pause / Resume Function Directions  
Pause function example: Program 01 has been manually activated. Pause program 01 for 30 minutes.  
1. Press the Pause  
key.  
2. Use the Input Dial  
to select All, M-Man or Prg:XX (XX = the program number). If multiple programs  
to tab to the program number field before using the Input Dial to  
select the correct program number. For this example, select Prg: 01.  
are active, use the Right Arrow key  
3. Press the Down Arrow  
Right Arrow key  
to advance the cursor to the for: field. Use the Input Dial  
and the  
to select the pause duration in hours and minutes. For this example, set the pause  
duration to 00 hr 30 min.  
The display should read:  
Pause: Prg: 01  
for: 00hr 30 min  
Press PAUSE to pause  
00 Programs Paused  
Note: The default pause time is 00 hr 05 min minutes.  
4. Press the Pause  
key to initiate the Pause function.  
Resume Controller Activity example: Reactivate Program 01 watering.  
1. Press the Pause  
2. Use the Input Dial  
key.  
until the correct program or multi-manual operation is displayed.  
For this example, select Resume: Prg: 01.  
The display should read:  
Resume: Prg: 01  
Press PAUSE to pause  
01 Programs Paused  
3. Press the Pause  
key to release the Pause function.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Pause Function  
Pause Program XX  
TDC-100/200 Action  
Allow the start of other programs, multi-manuals and syringe. If the start time of the  
paused program occur’s again while still on Pause, that runtime will be stacked  
(delayed until the first occurrence is completed).  
If Program XX is already on Pause or Pause All is in effect, the new pause time-out  
will override the remaining pause time for program XX.  
Pause Multi-Manual  
Pause Syringe  
Allows any program or syringe start. If a new multi-manual is activated, the  
previous will be canceled.  
If Multi-Manual is already on Pause or Pause All is in effect, the new pause time-  
out will override the remaining pause time for the multi-manual.  
Allows any program or manual start. If a new syringe is activated for the same  
paused syringed program, the pause will be cancelled and activity will resume with  
the new runtime.  
If a syringed program is on Pause All, activating a new pause for the same syringe  
program will overwrite the remaining pause time with the new pause time for that  
syringed program.  
Pause All  
All currently running programs, multi-manual and syringe will be suspended until  
the pause time-out expires.  
New start is allowed only for Manual functions.  
Additional programs that are scheduled to start while Pause All is in effect will be  
stacked until the Pause time-out expires.  
Pause All Timed out  
All activity delayed by Pause All function will resume. Programs and Manual  
functions that were paused after the Pause All function will resume when their  
pause time-out expires.  
Resume Program XX  
Resume Multi-Manual  
Resume Syringe  
Resumes program XX activity.  
Resumes multi-manual activity.  
Resumes syringe activity.  
Resume All  
Resumes all irrigation activity.  
Cancel (Stop) Program XX  
If Program XX is paused, the pause status will be cancelled and activity terminated.  
If the same program is stacked, it will also be terminated.  
Cancel (Stop) Manual  
Cancel (Stop) All  
If Manual activity is paused, the pause status will be cancelled and the manual  
activity is terminated.  
All paused activities will be cancelled and all watering will be terminated.  
Stop Key  
Use the Stop function to cancel program or manual irrigation. If the controller has no current activity, pressing  
the Stop key will have no effect.  
Stop Function Directions  
Stop Function Example: Program 01 is activated automatically. Cancel watering for program 01.  
1. Press the Stop  
key.  
2. Use the Input Dial  
until the desired program or station to be cancelled is displayed.  
For this example, select Cancel: Prg: 01.  
The display should read:  
Cancel: Prg:01  
STOP to cancel water  
Running 01 programs  
P01 is running  
3. Press the Stop  
key to finalize the program cancelation.  
When finished, the display should read:  
Cancelling P01  
03  
STOP to escape  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Diagnostics  
The diagnostics function allows the user to monitor Radio Link status, check the firmware version, troubleshoot  
stations using the Sequence Stations options, monitor the system’s water usage, monitor all system’s sensor status,  
monitor system’s voltages, check alarm status, clear alarms and execute a self diagnostics to the system.  
Use this menu to check  
Use this menu to clear  
alarm codes once it’s  
been restored.  
Menu: Station Alarms  
No Station Alarms  
Menu: Clear Alarms  
Last code: 04  
08/21/06, 13:21:09  
alarm codes that have  
been activated. Use the  
codes to troubleshoot for  
possible errors and faults.  
Use this menu to run the  
system’s self diagnostic to  
troubleshoot the system.  
Use this menu to verify  
firmware version.  
Menu: RunDiagnostics  
Press START to start  
Menu: Revision  
Revision: 02.00  
Rev. Date 08/10/06  
Use this menu to  
Use this menu to monitor  
the system’s water usage.  
You can use this  
information to adjust your  
system as necessary.  
Menu: Seq Stations  
Menu: Water Use  
troubleshoot the system by  
sequencing through all the  
stations for 5 sec, 30 sec, 1  
min, 2 min or 5 min.  
On each for: 30 sec  
Press START to start  
No available  
Information  
While the controller is in the station sequence process,  
you can navigate to the next station or previous station  
by using the Right or Left arrows  
.
Use this menu to monitor  
sensors. Flow, pressure  
and alarm sensor  
information will be  
displayed here.  
Use this menu to monitor  
the system’s voltages.  
Menu: Sensor Monitor  
Menu: VA Monitor  
Battery Volt: 3.3  
LCD Voltage: 2.7  
No available  
Information  
Sample Alarm Display During Normal Operation:  
TDC indicates Check  
Alarms Status when a  
fault is detected within the  
system.  
Sun 05/17/06 11:04am  
Chk Alarms Sec: 36  
Press DOWN to list  
05/17/06, 11:05  
Station OPEN  
Station Alarms will list any  
detected system faults  
with descriptions for quick  
and easy system  
Next start: 07:00pm  
No comm w/ decoder  
v
troubleshooting.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fuse & Circuit Breaker Specifications  
Power Supply:  
1.5A On/Off Switch/Circuit Breaker – Main Power Input  
3.15A Fuse (Slow-Blow) – Field Output  
Mother Board: 3.15A Fuse  
Controller Specifications  
Line Voltage: 100, 220 or 240 VAC 50/60 Hz, 98 VA  
Current Draw (no load): 0.21A @ 100-120 VAC, 60 Hz or 0.10A @ 200-240 VAC, 50 Hz  
Current Draw (maximum load): 0.91A @ 100-120 VAC, 60 Hz or 0.45A @ 200-240 VAC, 50 Hz  
Current Load: 28 VAC  
Maximum Current Available for Load: 3.15A (90 VA)  
Maximum Load Per Station: 0.0036A (0.01 VA)  
Operating Temperature: -10°C to +60°C (14°F to 140°F)  
Storage Temperature: -30°C to +65°C (-22°F to 149°F)  
Electromagnetic Compatibility  
Radio complies with FCC Part 22 and Part 90 of the FCC Rules  
Domestic: This equipment has been tested and found to comply with the limits for a FCC Class A digital device,  
pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful  
interference when the equipment is operated in a commercial environment. The equipment generates, uses, and can  
radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause  
harmful interference to the radio communications. Operation in a residential area is likely to cause harmful interference  
in which case the user will be required to correct the interference at his own expense.  
© 2007 The Toro Company, Irrigation Division • An ISO-9000-Certified Facility  
Form Number 373-0379 Rev. C  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Technics Stereo System SC S2050 User Manual
Techno Source Handheld Game System 90630 User Manual
Telenetics Network Card 202T MIU202T User Manual
Texas Instruments Stereo Amplifier TPA6204A1 User Manual
TIMEX Weather Products Thermometer TX1001 User Manual
Tripp Lite Power Supply 700 HG User Manual
ViewSonic Computer Monitor VX2703MHLED User Manual
Viking Refrigerator DFSB542D User Manual
Viper Automobile Alarm Model 330V User Manual
Vulcan Hart Range VCH16 ML 126341 User Manual