Series Fan-Type
Unit Heaters
C E R T I F I E D
Installation/Operation FORM RZ-NA I-UDA
APPLIES TO:
Models UDAP and UDAS
Table of Contents
Page
FOR YOUR SAFETY
What to do if you smell gas:
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in
your building.
• Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call your fire
department.
Warnings ........................................ 1
Installation/Operation .............. 2-25
Check/Test/Startup ................. 26-28
Maintenance/Service .............. 28-36
Index (by page)
Burner ................................................... 16, 29
Burner Orifice ............................................ 30
Burner Removal ........................................... 29
California Warning Label .............................. 3
Clearances .................................................... 7
Installation Codes ......................................... 2
Confined Space (UDAP) ............................... 8
Dimensions ................................................ 4-5
Disconnect, Built-in (UDAS) ................16, 34
Door Switch (UDAS) ............................19, 33
Downturn Nozzle (Option) ............................ 4
Electrical Connections ............................... 16
Fan ............................................................... 32
Fan Motor...............................................22, 32
Flame Rollout Switch ......................... 18, 34
Gas Piping and Pressures ........................... 12
Gas Valve ...............................................22, 33
General .......................................................... 2
Hanging the Heater ...................................... 10
Hazard Intensity Levels ............................... 2
Heat Exchanger Maintenance ...................... 29
HighAltitude ............................................ 6, 14
Ignition System ...................................... 19, 31
Limit Control ......................................... 18, 33
Location (Heater) ........................................... 9
Maintenance Schedule ............................... 28
Pressure Switch (Combustion Air) ....... 17, 33
Replacement Parts ................ See Form P-UD
Sound Data ................................................... 6
Startup .......................................................... 26
Suspending Heater ....................................... 4
Technical Data ............................................... 6
Thermostat (Option) .................................. 17
Throw (Heater) .............................................. 9
Transformer .................................................. 33
Troubleshooting ................................... 34-36
Uncrating and Preparation ........................... 3
Valve Outlet Pressure ................................... 14
Vent System ............................................... 34
Venter Motor ............................................... 32
Venting Model UDAP ........ Use Form I-V-PV
Venting Model UDAP-CV Use Form I-V-CV
Venting Model UDAS ......... Use Form I-V-SC
Warranty ......................................................... 3
Wiring Diagrams .................................... 23-25
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
WARNING: Improper installation, adjustment, alteration,
service, or maintenance can cause property damage, injury,
or death. Read the installation, operation, and maintenance
instructions thoroughly before installing or servicing this
equipment.
WARNING: Gas-fired appliances are not designed for use in
hazardous atmospheres containing flammable vapors or
combustible dust, in atmospheres containing chlorinated or
halogenated hydrocarbons, or in applications with airborne
silicone substances. See Hazard Levels, page 2.
WARNING: Should overheating occur, or the gas supply fail to
shut off, shut off the manual gas valve to the appliance before
shutting off the electrical supply.
WARNING: Do not use this appliance if any part has been under
water. Immediately call a qualified service technician to inspect
the appliance and replace any gas control that has been under
water.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 1
Download from Www.Somanuals.com. All Manuals Search And Download.
Installations in aircraft hangars should be in accordance withANSI/NFPANo. 409
(latest edition), Standard for Aircraft Hangars; in public garages in accordance
with ANSI/NFPA No. 88A (latest edition), Standard for Parking Structures; and
for repair garages in accordance with ANSI/NFPA No. 88B (latest edition), Stan-
dard for Repair Garages. In Canada, installations in aircraft hangars should be in
accordance with the requirements of the enforcing authorities, and in public ga-
rages in accordance with CAN/CGA B149 codes.
Special Installations
(Aircraft Hangars/
Repair Garages/
Parking Garages)
If the heater is being installed in the state of California, the installer MUST attach
a warning label on the outside of the access door. The California Warning label is
shipped in the owner’s envelope along with this manual, the warranty form, and
any other paperwork that applies.
California Warning
Label
If installation is in California, select a location on the heater access panel. Be sure
the surface is clean and dry and adhere the label.
If the heater is being installed in the Commonwealth of Massachusetts, these units
must be installed by a licensed plumber or licensed gas fitter.
Massachusetts
Requirement
Refer to the limited warranty information on the Warranty Card in the "Owner's
Envelope".
3. Warranty
Warranty is void if ...
a. Wiring is not in accordance with the diagram furnished with the heater.
b. The unit is installed without proper clearance to combustible materials.
c. A fan model is connected to a duct system or if the air delivery system is
modified.
4. Uncrating and
Preparation
This unit was test operated and inspected at the factory prior to crating and was in
operating condition. If the heater has incurred any damage in shipment, document
the damage with the transporting agency and contact an authorized Reznor Dis-
tributor. If you are an authorized Distributor, follow the FOB freight policy proce-
dures as published by Thomas & Betts for Reznor products.
Check the rating plate for the gas specifications and electrical characteristics of the
heater to be sure that they are compatible with the gas and electric supplies at the
installation site.
Read this booklet and become familiar with the installation requirements of your
particular heater. If you do not have knowledge of local requirements, check with
the local gas company or any other local agencies who might have requirements
concerning this installation.
Before beginning, make preparations for necessary supplies, tools, and manpower.
If the installation includes optional vertical louvers, downturn nozzle, ceiling mount-
ing bracket, hanger kit, high altitude kit, multiple heater control, and/or stepdown
transformer, install these options before the heater is suspended. Follow the in-
structions included in the option package; option packages are shipped separately.
Other shipped separate items could include a vent/combustion air kit, high tem-
perature tape, a thermostat bracket kit, a thermostat, and/or a thermostat guard. Be
sure all options ordered are at the installation site.
IMPORTANT: Shipping brackets are attached with cabinet screws. When
removing shipping brackets, re-insert ALL screws into the cabinet.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 3
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Dimensions
M and N - Hanger Dimensions for both 2-pt and 4-pt Suspension
FIGURE 1 - Model UDAP,
Power Vented Fan Model
M
N
R - Hanger
Dimension for
2-pt Suspension
Combustion
P and Q -
Hanger
P
Air Inlet
Dimensions
for 4-pt
R
Thermostat
REAR
VIEW
Connection
Suspension
TOP VIEW
(30-125 Vertical;
150-400 Horizontal)
Q
3/8-16 Female Thread
- all suspension points
G
J
Line Voltage
Inlet (connects
at circuit board)
Vent Collar
(see Technical
Data for size)
External
Gas
Connection
K
H
B
E
F
1-1/4
(32)
D
FRONT
VIEW
RIGHT SIDE
VIEW
(Access Panel)
C
A
MODEL UDAP DIMENSIONS (inches 1/16)
Size
A
B
C
D
E
F
G
H
J
K
M
N
P
Q
13
13
13
13
13
R
30, 45 12-1/8 26-5/8
60
75
10 13-13/16 26 21-9/16 5-3/16 6-1/2 2-11/16 3-7/8 17-3/8 11/16 4-5/16
13 13-13/16 27 21-9/16 7-7/8
13 13-13/16 27-5/8 21-9/16 7-7/8
21 13-13/16 28-5/8 21-9/16 14-1/2 6-1/2
21 13-13/16 29-3/8 21-9/16 14-1/2 6-1/2
9-9/16
10-1/2
10-1/2
10-1/2
10-1/2
15-1/8 26-5/8
15-1/8 26-5/8
23-1/8 26-5/8
23-1/8 26-5/8
6-1/2
6-1/2
5-1/2
5-1/2
8-3/4
8-3/4
3-7/8 17-3/8 11/16 4-5/16
3-7/8 17-3/8 11/16 4-5/16
3-7/8 17-3/8 11/16 4-5/16
3-7/8 17-3/8 11/16 4-5/16
100
125
150, 175,
200
225, 250 26-1/8 38-3/16 22
300, 350,
400
20-1/8 38-3/16 16
23
23
23
42
42
42
35-3/8 8-1/2
8-1/4
5-7/16 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 16-3/8
6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 15-5/8
11-13/16 7-5/16 27-11/16 1-3/8 8-3/16 22-3/16 16-3/16
35-3/8 13-1/16 8-13/16
9
34-1/8
41
30
35-3/8 17-1/16
9
MODEL UDAP DIMENSIONS (mm 2)
Size
30, 45
60
A
B
C
D
E
F
G
H
J
68
140
140
222
222
K
98
98
98
98
98
M
N
17
17
17
17
17
P
Q
R
308
384
384
587
587
676
676
676
676
676
254
330
330
533
533
351
351
351
351
351
660
686
702
727
746
548
548
548
548
548
132
200
200
368
368
165
165
165
165
165
441
441
441
441
441
110
110
110
110
110
330
330
330
330
330
243
267
267
267
267
75
100
125
150, 175,
200
225, 250 664
300, 350,
400
511
970
970
406
559
762
584
584
584
1067
1067
1067
899
899
899
216
332
433
210
224
229
138
229
300
165
165
186
652
652
703
35
35
35
208
208
208
564
564
564
416
397
411
867
1041
Option CD3
Options CD2 and CD4
Size
30, 45
60, 75
100, 125
150, 175, 200
225, 250
300, 350, 400
FIGURE 2 -
With Optional
Downturn Nozzle
Dimension “U”
-- Applies to both
UDAP and UDAS
inches
7-1/8
mm
181
219
321
292
368
470
inches
mm
314
381
556
505
638
813
With
With
Option
CD3
12-3/8
15
Option
CD2
8-5/8
or CD4
12-5/8
11-1/2
14-1/2
18-1/2
21-7/8
19-7/8
25-1/8
32
U
U
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 4
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 3 - Model UDAS,
Separated Combustion Fan
Model
M and N - Hanger Dimensions
for both 2-pt and 4-pt Suspension
M
N
R - Hanger
Dimension for
2-pt Suspension
Combustion Air Connection
(see Technical Data for size)
T
P
Thermostat
S
R
REAR
VIEW
Connection
(30-45, 150-400
Horizontal;
TOP VIEW
P and Q -
Hanger
60-125 Vertical)
Dimensions
for 4-pt
Q
3/8-16 Female Thread
- all suspension points
Suspension
G
J
Line Voltage
Vent Connection
(see Technical
Data for size)
External
Gas
Connection
K
Inlet (connects in
H
sealed electrical box)
B
E
D
1-1/4
(32)
F
RIGHT SIDE
VIEW
(Access Panel)
C
FRONT
VIEW
A
MODEL UDAS DIMENSIONS (inches 1/16)
Size
A
B
C
D
E
F
G
H
J
K
M
N
P
Q
R
S
T
30, 45 12-1/8 26-5/8 10 13-13/16 26 21-9/16 5-3/16 6-1/2 2-11/16 3-7/8 17-3/8 11/16 4-5/16 13
60 15-1/8 26-5/8 13 13-13/16 27 21-9/16 7-7/8 6-1/2 5-1/2 3-7/8 17-3/8 11/16 4-5/16 13
75 15-1/8 26-5/8 13 13-13/16 27-5/8 21-9/16 7-7/8 6-1/2 5-1/2 3-7/8 17-3/8 11/16 4-5/16 13
100 23-1/8 26-5/8 21 13-13/16 28-5/8 21-9/16 14-1/2 6-1/2 8-3/4 3-7/8 17-3/8 11/16 4-5/16 13
125 23-1/8 26-5/8 21 13-13/16 29-3/8 21-9/16 14-1/2 6-1/2 8-3/4 3-7/8 17-3/8 11/16 4-5/16 13
150,
9-9/16 2-15/16 2-15/16
10-1/2 3-1/4 2-15/16
10-1/2 3-1/4 2-15/16
10-1/2 4-5/8 2-15/16
10-1/2 4-5/8 2-15/16
20-1/8 38-3/16 16
23
23
23
42 35-3/8 8-1/2 8-1/4 5-7/16 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 16-3/8 4-1/8 8-5/16
42 35-3/8 13-1/16 8-13/16 6-1/2 25-11/16 1-3/8 8-3/16 22-3/16 15-5/8 5-9/16 8-5/16
11-13/16 7-5/16 27-11/16 1-3/8 8-3/16 22-3/16 16-3/16 9-1/16 8-9/16
175,
200
225,
250
300,
350,
400
26-1/8 38-3/16 22
9
34-1/8 41
30
42 35-3/8 17-1/16
9
MODEL UDAS DIMENSIONS (mm 2)
Size
30, 45 308
60
A
B
C
D
E
F
G
H
J
68
140
140
222
222
K
M
N
17
17
17
17
17
P
Q
R
S
75
T
676 254 351
676 330 351
676 330 351
676 533 351
676 533 351
660
686
702
727
746
548
548
548
548
548
132
200
200
368
368
165
165
165
165
165
98
98
98
98
98
441
441
441
441
441
110
110
110
110
110
330
330
330
330
330
243
267
267
267
267
75
75
75
75
75
384
384
587
587
89
75
89
100
125
150,
175,
200
225,
250
300,
350,
400
117
117
511
664
970 406 584
970 559 584
1067 899
1067 899
1067 899
216
332
433
210
224
229
138
229
300
165
165
186
652
652
703
35
35
35
208
208
208
564
564
564
416
397
411
105
141
230
211
211
217
867 1041 762 584
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 5
Download from Www.Somanuals.com. All Manuals Search And Download.
6.Technical Data
(Data applies to both Models UDAP and UDAS unless noted otherwise.)
TECHNICAL DATA - Sizes 30 - 125
Size
30
30,000
8.8
45
45,000
13.2
83
60
60,000
17.6
83
75
75,000
22.0
83
100
105,000
30.8
83
125
120,000
35.2
83
BTUH
Input Heating Capacity
kw
Thermal Efficiency (%)
82
BTUH
kw
24,600
7.2
1/2
37,350
11.0
1/2
49,800
14.6
1/2
62,250
18.3
1/2
87,150
25.6
1/2
99,600
29.2
1/2
Output Heating Capacity A
Natural
Gas Connection (inches) B
Propane
1/2
1/2
1/2
1/2
1/2
1/2
Vent Connection C (inches diameter)
4
4
4
4
4
4
C
4
4
4
4
4
4
Combustion Air Inlet (inches diameter) - UDAS only
Control Amps (24 volt)
1.0
1.0
1.0
1.0
1.0
1.0
Full Load Amps (115 volt)
1.9
15
109
50
2.4
15
155
55
2.4
15
155
60
3.3
15
217
60
3.9
15
276
60
5.1
15
354
60
Maximum Over Current Protection (115V) D
Normal Power Consumption (watts)
Discharge Air Temperature Rise (°F)
CFM
456
12.9
0.96
0.09
475
145
0.02
N.A.
1550
10
629
17.8
0.96
0.09
656
200
0.03
N.A.
1550
10
769
21.8
1.25
0.12
616
188
0.03
N.A.
1550
12
961
27.5
1.25
0.12
770
238
0.06
N.A.
1550
12
1345
36.7
2.01
0.19
668
196
1/30
1/4
1537
45.9
2.01
0.19
763
245
1/20
1/4
Air Volume
M3/minute
ft2
Discharge Air Opening Area
M2
FPM
M/minute
Open
Enclosed
Output Velocity
Fan Motor HP E
Fan Motor RPM
Fan Diameter (inches)
1050
16
1050
16
Sound Level
dba @ 15 ft
40
40
40
49
54
55
(Data applies to both Models UDAP and UDAS unless noted otherwise.)
TECHNICAL DATA - Sizes 150 - 400
Size
150
175
200
225
250
300
350
400
BTUH
150,000
43.9
83
175,000
51.2
83
200,000
58.6
83
225,000
65.9
83
250,000
73.2
83
300,000
87.8
83
350,000
102.5
83
400,000
117.1
83
Input Heating Capacity
kw
Thermal Efficiency (%)
BTUH
kw
124,500
36.4
1/2
1/2
5
145,250
42.5
1/2
1/2
5
166,000
48.6
1/2
1/2
5
186,750
54.7
3/4
3/4
5
207,500
60.8
3/4
3/4
5
249,000
72.9
3/4
3/4
6
290,500
85.1
3/4
3/4
6
332,000
97.2
3/4
3/4
6
Output Heating Capacity A
Natural
Gas Connection (inches) B
Propane
Vent Connection C (inches diameter)
C
6
6
6
6
6
6
6
6
Combustion Air Inlet (inches diameter) - UDAS only
Control Amps (24 volt)
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
Full Load Amps (115 volt)
3.8
15
392
60
3.8
15
392
60
4.6
15
491
60
7.5
15
747
60
7.5
15
747
60
10.7
20
1086
60
10.7
20
1086
60
10.7
20
1086
60
Maximum Over Current Protection (115V) D
Normal Power Consumption (watts)
Discharge Air Temperature Rise (°F)
CFM
1921
54.4
2.56
0.24
752
229
1/6
2242
63.5
2.56
0.24
877
267
1/6
2562
72.5
2.56
0.24
1003
306
1/6
2882
81.6
3.51
0.33
820
250
1/4
3202
90.7
3.51
0.33
911
278
1/4
3843
108.8
4.79
0.45
802
244
1/2
4483
126.9
4.79
0.45
936
285
1/2
5123
145.1
4.79
0.45
1069
326
1/2
Air Volume
M3/minute
ft2
Discharge Air Opening Area
M2
FPM
Output Velocity
M/minute
Open
Enclosed
Fan Motor HP E
1/4
1/4
1/4
1/4
1/4
1/2
1/2
1/2
Fan Motor RPM
Fan Diameter (inches)
1050
18
1050
18
1050
18
1050
20
1050
20
1050
24
1050
24
1050
24
Sound Level
dba @ 15 ft
51
52
53
56
56
59
61
62
A
B
CSA ratings for altitudes to 2000 ft.
Size shown is for gas connection to a single-stage gas valve, not supply line size.
C
Smaller and/or larger vent and combustion air pipe diameters may be permissible. For Model UDAS refer to the Venting Installation Manual for Separated
Combustion Units. For Model UDAP refer to the Venting Installation Manual for Power Vented units. For a Model UDAP with Option AV6, refer to the
Venting Installation Manual for Common Venting.
D
MOCP = 2.25 x (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.
E
All other information is this table is based on a heater equipped with a standard 115 volt open fan motor.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 6
Download from Www.Somanuals.com. All Manuals Search And Download.
If the heater is being installed at an elevation above 2000 ft (610M), the input rate
will have to be derated. This is done by adjusting the valve outlet pressure.
7. High Altitude
Operation
In addition, if the heater is being installed at an altitude above 6000 ft (1830M), the
pressure switch will have to be changed. If ordered with the unit as Option DJ20 or
DJ21, the pressure switch is shipped separately.
Gas valve adjustment for
high altitude can only be
done after heater is
operating; see
Adjusting the valve outlet pressure is done after the heater is in operation; follow
the instructions in Paragraph 12. Capacities and inputs for derated units are also
listed in Paragraph 12.
If the pressure switch needs to be changed, do that before the heater is operated;
follow the instructions in FIGURE 4.
Paragraph 12.
FIGURE 4 - Installing High Altitude Pressure Switch required above 6000 ft (1830M) elevation
Model UDAP
Size
30
45
60 75
100
125
150 175 200 225 250 300 350 400
High Altitude Switch P/N
Negative Pressure OFF Setpoint "w.c.
Label color
197031
0.35
Purple
197032
0.45
Pink
197031
0.35
Purple
201160
1.00
Brown
201161
1.30
White
Model UDAP-CV with Option AV6 for Common Venting
Size
30
197029 197032 196362 196388
0.60 0.45 0.55 0.50
Lt Blue Pink White Orange
45
60 75
100
High Altitude Switch P/N
Negative Pressure OFF Setpoint "w.c.
Label color
Model UDAS
Size
30
45
60 75
100
125
150 175 200 225 250 300 350 400
High Altitude Switch P/N
Differential Pressure OFF Setpoint "w.c.
Label color
197029
0.60
Lt. Blue
196388 197030 197031
201160
1.00
Brown
201161
1.30
White
0.50
0.40
0.35
Orange Green
Purple
Instructions for Changing Pressure Switch
1. In the control compartment, locate the pressure switch.
Sizes 30-125 - On the back wall of the control compartment.
Sizes 150-400 - On the bracket on the bottom of the control compartment.
2. Mark and disconnect the two wires attached to the pressure switch.
3. Disconnect the sensing tube from the pressure switch.
4. Locate the two screws holding the switch mounting bracket. Remove the
screws (save screws) and the pressure switch.
Pressure Switch
5. Using the same screws, install the high altitude pressure switch. Attach the
sensing tube and wires.
Units must be installed so that the clearances in the table are provided for combus-
tion air space, inspection and service, and for proper spacing from combustible
construction. Clearance to combustibles is defined as the minimum distance from
the heater to a surface or object that is necessary to ensure that a surface tempera-
ture of 90°F above the surrounding ambient temperature is not exceeded.
8. Clearances
Clearances
Top
inches mm
Flue Connector
Access Panel
Non-Access Side
Bottom*
inches mm inches mm
Rear
Size
inches
mm
152
152
inches
mm
457
457
inches
mm
25
51
30-125
1
4
25
6
6
18
1
2
1
1
25
25
18
18
457
457
150-400
102
18
*Suspend the heater so that the bottom is a minimum of 5 feet (1.5M) above the floor.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 7
Download from Www.Somanuals.com. All Manuals Search And Download.
This heater must be supplied with the air that enters into the combustion process
and is then vented to the outdoors. Sufficient air must enter the equipment location
to replace that exhausted through the heater vent system. In the past, the infiltra-
tion of outside air assumed in heat loss calculations (one air change per hour) was
assumed to be sufficient. However, current construction methods using more insu-
lation, vapor barriers, tighter fitting and gasketed doors and windows, weather-
stripping, and/or mechanical exhaust fans may now require the introduction of
outside air through wall openings or ducts.
9. Combustion
Air - applies to
Model UDAP
and Model
UDAP-CV
The requirements for combustion and ventilation air depend upon whether the unit
is located in a confined or unconfined space. An "unconfined space" is defined as
a space whose volume is not less than 50 cubic feet per 1000 BTUH of the installed
appliance. Under ALL conditions, enough air must be provided to ensure there
will not be a negative pressure condition within the equipment room or space.
(Note: For Model
UDAS, see Venting
Manual for
combustion air
requirements.)
WARNING: Model UDAP and UDAP-CV power-vented unit
heaters are designed to take combustion air from the space in
which the unit is installed and are not designed for connection to
outside combustion air intake ducts. Connecting outside air ducts
voids the warranty and could cause hazardous operation. See
Hazard Levels, page 2.
Do not install a unit in a confined space without providing wall openings leading
to and from the space. Provide openings near the floor and ceiling for ventilation
and air for combustion as shown in FIGURE 5, depending on the combustion air
source as noted in Items 1, 2, and 3 below.
Combustion Air
Requirements for
a Heater Located
in a Confined
Add total BTUH of all appliances in the confined space and divide by figures
below for square inch free area size of each (top and bottom) opening.
Space - applies to
Model UDAP and
Model UDAP-CV
Confined Space:
A space whose volume is
less than 50 cubic feet
per 1000 BTUH of the
installed appliance input
rating
(2)
(2)
(3)
(1)
Confined
Space
FIGURE 5 - Definition of
Confined Space and
Required Openings for
Combustion Air
(3)
(1)
1. Air from inside the building -- openings 1 square inch free area per 1000
BTUH. Never less than 100 square inches free area for each opening. See (1) in
FIGURE 5.
2. Air from outside through duct -- openings 1 square inch free area per 2000
BTUH. See (2) in FIGURE 5.
3. Air direct from outside -- openings 1 square inch free area per 4000 BTUH.
See (3) in FIGURE 5.
NOTE: For further details on supplying combustion air to a confined space, see
the National Fuel Gas Code ANSI Z223.1a (latest edition).
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 8
Download from Www.Somanuals.com. All Manuals Search And Download.
Use the sound data in Paragraph 6, clearances in Paragraph 8; the combustion air
requirements in Paragraph 9; the throw tables, mounting height requirements, and
location recommendations below; the weights in Paragraph 11; and the venting
requirements in the Venting Manual to determine where to suspend the heater.
10. Unit Heater
Location
Heater Throw
*Louver angle listed in the table is relative to the top of the heater.
FIGURE 6 - Throw for Fan
Models UDAP and UDAS
NOTE: Throws listed are with
standard adjustable horizontal
louvers at the angles listed
(angle is relative to the top of
the heater). Throw pattern
changes with the addition of
optional vertical louvers and/or
downturn nozzles.
H
**Z is the point
X
when the air velocity
Y
drops below 50 feet
(15.2M) per minute.
Z**
Dimensions X, Y, and Z (feet) Model UDAP and Model UDAS with Standard Horizontal Louvers at Mounting Heights of 5 - 18 ft
30
45
60
75
100
125
H
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
5 ft
8 ft
6
7
6
-
-
-
14 30 -21°
13 26 -39°
11 22 -52°
7
9
9
8
-
16 40 -20°
8
18 45 -16°
9
20 57 -14°
9
20 59 -18° 10 22
65 -14°
63 -24°
60 -30°
57 -36°
53 -43°
47 -50°
40 -57°
16 37 -34° 10 18 42 -29° 12 22 54 -25° 11 21 56 -28° 12 23
15 33 -43° 10 17 39 -37° 12 22 52 -32° 12 20 52 -36° 13 24
12 27 -55° 10 16 34 -46° 12 21 48 -39° 11 19 47 -44° 14 23
10 ft
12 ft
14 ft
16 ft
18 ft
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
9
-
-
14 29 -56° 12 19 44 -46° 11 17 42 -51° 14 22
-
-
-
-
-
-
-
-
11 17 38 -54° 10 14 34 -58° 13 20
-
-
-
-
-
-
-
-
-
11 17
150
175
200
225
250
300
350
400
H
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
8 ft 13 24 73 -26° 15 28 90 -22° 16 30 93 -20° 14 27 86 -24° 16 29 93 -21° 15 28
10 ft 14 24 69 -32° 17 29 87 -27° 17 31 91 -25° 15 27 82 -30° 17 30 90 -26° 16 28
12 ft 14 24 64 -39° 18 29 84 -32° 18 31 88 -30° 16 27 78 -35° 18 30 87 -31° 17 28
14 ft 14 22 59 -45° 18 28 79 -37° 19 30 84 -34° 16 26 73 -41° 18 30 83 -36° 17 27
16 ft 13 20 53 -51° 18 27 74 -42° 19 29 79 -39° 16 24 67 -47° 19 28 78 -41° 17 25
18 ft 11 17 44 -58° 17 26 68 -48° 19 28 74 -44° 14 22 60 -53° 18 27 72 -46° 16 24
94 -24° 17 31 105 -20° 18 34 113 -17°
89 -29° 18 32 103 -25° 20 35 110 -21°
85 -34° 19 32 98 -30° 21 36 108 -25°
80 -40° 20 32 95 -34° 23 35 105 -29°
74 -45° 21 31 90 -38° 23 35 101 -33°
66 -51° 20 30 85 -43° 23 35 97 -37°
Dimensions X, Y, and Z (meters) Model UDAP and Model UDAS with Standard Horizontal Louvers at Mounting Heights of 1.5 - 5.5M
30
45
60
75
100
125
H
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
1.5 M 1.8 4.3 9.1 -21° 2.1 4.9 12.2 -20° 2.4 5.5 13.8 -16° 2.7 6.1 17.4 -14° 2.7 6.1 18.0 -18° 3.0 6.7 19.9 -14°
2.4 M 2.1 4.0 7.9 -39° 2.7 4.9 11.3 -34° 3.0 5.5 12.8 -29° 3.7 6.7 16.5 -25° 3.4 6.4 17.1 -28° 3.7 7.0 19.2 -24°
3.0 M 1.8 3.4 6.7 -52° 2.7 4.6 10.0 -43° 3.0 5.2 11.9 -37° 3.7 6.7 15.8 -32° 3.7 6.1 15.8 -36° 4.0 7.3 18.3 -30°
3.7 M
4.3 M
4.9 M
5.5 M
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2.4 3.7 8.2 -55° 3.0 4.9 10.4 -46° 3.7 6.4 14.6 -39° 3.4 5.8 14.3 -44° 4.3 7.0 17.4 -36°
-
-
-
-
-
-
-
-
-
-
-
-
2.7 4.3 8.8 -56° 3.7 5.8 13.4 -46° 3.4 5.2 12.8 -51° 4.3 6.7 16.1 -43°
-
-
-
-
-
-
-
-
3.4 5.2 11.6 -54° 3.0 4.3 10.4 -58° 4.0 6.1 14.3 -50°
-
-
-
-
-
-
-
-
3.4 5.2 12.2 -57°
150
175
200
225
250
300
350
400
H
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
X
Y
Z
2.4 M 4.0 7.3 22.3 -26° 4.6 8.5 27.4 -22° 4.9 9.1 28.0 -20° 4.3 8.2 26.2 -24° 4.9 8.8 28.3 -21° 4.6 8.5 28.7 -24° 5.2 9.4 32.0 -20° 5.5 11.3 34.4 -17°
3.0 M 4.3 7.3 21.0 -32° 5.2 8.8 26.6 -27° 5.2 9.4 27.7 -25° 4.6 8.2 25.0 -30° 5.2 9.1 27.4 -26° 4.9 8.5 27.1 -29° 5.5 9.8 31.4 -25° 6.1 10.7 33.5 -21°
3.7 M 4.3 7.3 19.5 -39° 5.5 8.8 25.6 -32° 5.5 9.4 26.8 -30° 4.9 8.2 23.8 -35° 5.5 9.1 26.5 -31° 5.2 8.5 25.9 -34° 5.8 9.8 29.9 -30° 6.4 11.0 32.9 -25°
4.3 M 4.3 6.7 18.0 -45° 5.5 8.5 24.1 -37° 5.8 9.1 25.6 -34° 4.9 7.9 22.3 -41° 5.5 9.1 25.3 -36° 5.2 8.2 24.4 -40° 6.1 9.8 29.0 -34° 7.0 10.7 32.0 -29°
4.9 M 4.0 6.1 16.2 -51° 5.5 8.2 22.6 -42° 5.8 8.8 24.1 -39° 4.9 7.3 20.4 -47° 5.8 8.5 23.8 -41° 5.2 7.6 22.6 -45° 6.4 9.4 27.4 -38° 7.0 10.7 30.8 -33°
5.5 M 3.4 5.2 13.4 -58° 5.2 7.9 20.7 -48° 5.8 8.5 22.6 -44° 4.3 6.7 18.3 -53° 5.5 8.2 21.9 -46° 4.9 7.3 20.1 -51° 6.1 9.1 25.9 -43° 7.0 10.7 26.9 -37°
Locate the heater so that it is a minimum of five feet (1.5M) above the floor and in
compliance with the clearances in Paragraph 8.
Location
Recommendations
WARNING: If touched, the vent pipe and internal heater surfaces
that are accessible from outside the heater will cause burns.
Suspend the heater a minimum of 5 feet (1.5M) above the floor.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 9
Download from Www.Somanuals.com. All Manuals Search And Download.
For best results, the heater should be placed with certain rules in mind. In general,
a unit should be located from 8 to 12 feet (2.4-3.7M) above the floor. Units should
always be arranged to blow toward or along exposed wall surfaces, if possible.
Where two or more units are installed in the same room, a general scheme of air
circulation should be maintained for best results.
10. Unit Heater
Location
(cont’d)
Suspended heaters are most effective when located as close to the working zone as
possible, and this fact should be kept in mind when determining the mounting
heights to be used. However, care should be exercised to avoid directing the dis-
charged air directly on the room occupants.
NOTE: Venting
requirements may
affect location.
Consult the Venting
Manual for this heater
before making final
determination.
Partitions, columns, counters, or other obstructions should be taken into consider-
ation when locating the unit heater so that a minimum quantity of airflow will be
deflected by such obstacles.
When units are located in the center of the space to be heated, the air should be
discharged toward the exposed walls. In large areas, units should be located to
discharge air along exposed walls with extra units provided to discharge air in
toward the center of the area.
At those points where infiltration of cold air is excessive, such as at entrance doors
and shipping doors, it is desirable to locate the unit so that it will discharge directly
toward the source of cold air from a distance of 15 to 20 feet (4.6-6.1M).
CAUTION: Do not locate the heater where it may be exposed to
water spray, rain, or dripping water.
The presence of chlorine vapors in the combustion air of gas-fired heating equip-
ment presents a potential corrosion hazard. Chlorine found usually in the form of
freon or degreaser vapors, when exposed to flame will precipitate from the com-
pound, and go into solution with any condensation that is present in the heat ex-
changer or associated parts. The result is hydrochloric acid which readily attacks
all metals including 300 grade stainless steel. Care should be taken to separate
these vapors from the combustion process. This may be done by wise location of
the unit vent and combustion air terminals with regard to exhausters or prevailing
wind directions. Chlorine is heavier than air. Keep these facts in mind when deter-
mining installation location of the heater in relation to building exhaust systems.
Hazards of Chlorine -
applies to location of
Model UDAS heater
with regard to
combustion air inlet
Before suspending the heater, check the supporting structure to be used to verify
that it has sufficient load-carrying capacity to support the weight of the unit.
11. Hanging the
Heater
Model UDAP
Size
lbs
30 45 60 75 100
125
101
46
150 175, 200 225
250
215
98
300
269
122
350
294
133
400
306
139
WARNINGS: Check the
supporting structure to
be used to verify that it
has sufficient load carry-
ing capacity to support
the weight of the unit.
Suspend the heater only
from the threaded nut
retainers or with a man-
ufacturer provided kit.
Do NOT suspend from
the heater cabinet.
54 59 67 72
24 27 30 33
96
44
172
78
187
85
203
92
kg
Model UDAS
Size
lbs
30 45 60 75 100
125
102
46
150 175, 200 225
250
216
98
300
270
122
350
295
134
400
307
138
55 60 68 73
25 27 31 33
97
44
173
78
188
85
204
93
kg
When the heater is lifted for suspension, support the bottom of the heater with
plywood or other appropriately placed material. If the bottom is not supported,
damage could occur. Before hanging, verify that all screws used for holding ship-
ping brackets were re-installed in the cabinet.
The heater is equipped for either two-point or four-point suspension. A 3/8"-16
threaded nut retainer is located at each suspension point. See Dimensions in Para-
graph 5 and the illustration in FIGURE 7A.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 10
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 7A - Suspending
the Heater with Rods from
the Threaded Nut Retainers
(either two or four point
suspension)
Be sure the threaded hanger rods
are locked to the heater as
illustrated.
3/8 threaded rod
(field supplied)
Add a 3/8 nut and
washer to lock the
hanger rod to the heater.
WARNING: Unit must
be level for proper
operation. Do not place
or add additional weight
to the suspended heater.
Hazard Levels, page 2.
Recommended maximum hanger
rod length is 6 feet (1.8M).
If ordered with swivel connectors for 1” pipe, Option CK8 or CK10, attach the
swivels at the threaded nut retainers. Suspend with 1” pipe. (See FIGURE 7B.)
Be sure the
Lock the swivel
connector to
the heater.
The connector
is threaded for
hanging from
a 1 pipe.
threaded swivel
connectors are
locked to the
heater as
FIGURE 7B - Swivel
Connectors to Suspend the
Heater from 1” Pipe, Option
CK8 (2-pt) or CK10 (4-pt)
illustrated.
If ordered with a ceiling suspension kit, Option CK22, follow the illustrated in-
structions in the kit. (See FIGURE 8.)
FIGURE 8 - Suspending the
Heater using Option CK22,
Ceiling Suspension Kit (no
hanger rods)
Available for
Sizes 30-125.
Allows the
heater to be
installed one
inch from the
ceiling.
NOR
Model UDAS - Whether using the suspension points or the hanger kit, when in-
stalling a Model UDAS, the unused suspension points on the control side of the
heater MUST be plugged. Plug these holes with the 3/8”-16 bolts and flat wash-
ers shipped in the bag with the heater. (See FIGURE 9.)
FIGURE 9 - Model UDAS -
Plug the unused suspension
points on the control side of
the heater with 3/8”-16
Plug any unused suspension points
on the control side with the 3/8-16
bolts and flat washers provided.
screws and flat washers
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 11
Download from Www.Somanuals.com. All Manuals Search And Download.
WARNING: This appliance is equipped for a maximum gas
supply pressure of 1/2 pound, 8 ounces, or 14 inches water column.
Supply pressure higher than 1/2 pound requires installation of
an additional lockup-type service regulator external to the unit.
12. Gas Piping
and
Pressures
WARNING: PRESSURE TESTING SUPPLY PIPING
Test Pressures Above 1/2 PSI: Disconnect the heater and manual valve from the
gas supply line which is to be tested. Cap or plug the supply line.
Test Pressures Below 1/2 PSI: Before testing, close the manual valve on the
heater.
Sizing
Gas
Supply
Capacity of Piping
Cubic Feet per Hour based on 0.3" w.c. Pressure Drop
Specific Gravity for Natural Gas -- 0.6 (Natural Gas -- 1000 BTU/Cubic Ft)
Specific Gravity for Propane Gas -- 1.6 (Propane Gas -- 2550 BTU/Cubic Ft)
Diameter of Pipe
Length
of
Line
1/2"
3/4"
1"
1-1/4"
1-1/2"
2"
Pipe Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane Natural Propane
20’
30’
40’
50’
60’
70’
80’
90’
100’
125’
150’
175’
200’
92
73
63
56
50
46
43
40
38
34
31
28
26
56
45
38
34
31
28
26
24
23
21
19
17
16
190
152
130
115
105
96
90
84
79
72
116
93
79
70
64
59
55
51
48
44
39
36
34
350
285
245
215
195
180
170
160
150
130
120
110
100
214
174
149
131
119
110
104
98
92
79
73
67
730
590
500
440
400
370
350
320
305
275
250
225
210
445
360
305
268
244
226
214
195
186
168
153
137
128
1100
890
760
670
610
560
530
490
460
410
380
350
320
671
543
464
409
372
342
323
299
281
250
232
214
195
2100
1650
1450
1270
1105
1050
990
930
870
780
710
1281
1007
885
775
674
641
604
567
531
476
433
397
372
64
59
55
650
610
61
Note: When sizing supply lines, consider possibilities of future expansion and increased requirements.
Refer to National Fuel Gas Code for additional information on line sizing.
All piping must be in accordance with requirements outlined in the National Fuel
Gas Code ANSI/Z223.1a (latest edition) or CAN/CGA-B149.1 and B149.2 (See
Paragraph 2). Gas supply piping installation should conform with good practice
and with local codes. Support gas piping with pipe hangers, metal strapping, or
other suitable material; do not rely on the heater to support the gas pipe.
WARNING: All
components of a gas
supply system must be
leak tested prior to
placing equipment in
service. NEVER TEST
FOR LEAKS WITH AN
OPEN FLAME. Failure
to comply could result in
personal injury,
The heater is orificed for operation with natural gas having a heating value of 1000
(± 50) BTUH per cubic ft or propane gas with a heating value of 2500 (± 100)
BTUH per cubic ft. If the gas at the installation does not meet these specifications,
consult the factory for proper orificing.
Pipe joint compounds (pipe dope) shall be resistant to the action of liquefied petro-
leum gas or any other chemical constituents of the gas being supplied.
Install a ground joint union and manual shutoff valve upstream of the unit control
system, as shown in FIGURE 10. Installation of a trap with a minimum 3" (76mm)
drip leg is required.
property damage or
death.
The unit is equipped with a nipple that extends outside the cabinet. The gas con-
nection is either 1/2” or 3/4”.
Gas Connection (inches)
Gas Connection Size
30 45 60 75 100 125 150 175 200 225 250 300 350 400
Natural 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Propane 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 12
Download from Www.Somanuals.com. All Manuals Search And Download.
Leak-test all connections by brushing on a leak-detecting solution.
FIGURE 10 - Gas
Ground
Joint Union
connection is at the pipe
nipple that extends outside
the cabinet
Manual shutoff
To Gas Valve
(inside the
cabinet)
Drip
Leg
From Gas Supply
(horizontal or vertical)
Illustration shows both a
vertical and horizontal gas
supply; requirements are
the same.
Pipe nipple extending
outside the cabinet.
Manual shutoff
To Gas Valve
(inside the
cabinet)
Drip
Leg
Ground
Joint
Union
Measuring valve outlet gas pressure cannot be done until the heater is in opera-
tion. It is included in the steps of the "Check-Test-Start" procedure in Paragraph
24. The following warnings and instructions apply.
Valve Outlet or
Orifice Pressure
Setting
WARNING: Valve outlet gas pressure must never exceed 3.5"
w.c. for natural gas and 10" w.c. for propane gas.
NOTE: Gas Conversion
Kits are available for
For Natural Gas: When the heater leaves the factory, the combination gas valve
is set so that the valve outlet gas pressure for a single stage valve or high fire of a
two stage valve is regulated to 3.5" w.c. Inlet supply pressure to the valve for
natural gas must be a minimum of 5" w.c. or as noted on the rating plate and a
maximum of 14" w.c.
changing from propane gas
to natural gas or natural gas
to propane gas. A factory-
authorized conversion kit
MUST be used.
For Propane Gas: When the heater leaves the factory, the combination gas valve
is set so that the valve outlet gas pressure for a single stage valve or high fire of a
two stage valve is regulated to 10" w.c. Inlet supply pressure to the valve for
propane gas must be a minimum of 11" w.c. and a maximum of 14" w.c.
Before attempting to measure or adjust valve outlet gas pressure, the inlet supply
pressure must be within the specified range both when the heater is in operation
and on standby. Incorrect inlet pressure could cause excessive valve outlet gas
pressure immediately or at some future time. If natural gas supply pressure is too
high, install a regulator in the supply line before it reaches the heater. If natural
gas supply pressure is too low, contact your gas supplier.
Instructions
Check Valve Outlet
Pressure (can only be
done after heater is
operating)
1) Locate the 1/8” output pressure tap on the valve (See FIGURE 11, page 14).
With the manual valve turned off to prevent flow to the gas valve, connect a
manometer to the 1/8" pipe outlet pressure tap in the valve. NOTE: A manom-
eter (fluid-filled gauge) is recommended rather than a spring type gauge due to
the difficulty of maintaining calibration of a spring type gauge.
NOTE: If operating at high
altitude, outlet pressure
requires adjustment. Follow
instructions on page 14.
2) Open the manual valve and operate the heater. (NOTE: On Model UDAS,
depress and hold the door safety switch.) Measure the outlet pressure of the gas
valve. Normally when operating at sea level, adjustments should not be neces-
sary to the factory setting. (For high altitude settings, see next paragraph.)
If adjustment is necessary, remove the cap from the adjustment screw(s). Set
pressure to correct settings by turning the regulator screw IN (clockwise) to
increase pressure. Turn regulator screw OUT (counterclockwise) to decrease
pressure.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Instructions for High Altitude Derate
12. Gas Piping
and
1. Determine the required valve outlet pressure for the elevation where the heater
will be operating. If unsure of the elevation, contact the local gas supplier.
Valve Outlet Pressure Settings by Elevation
Pressures
(cont’d)
Manifold Pressure Settings by Altitude for the UNITED STATES
Altitude
Natural Gas (inches w.c.)
Propane Gas (inches w.c.)
Single Stage and Two Stage Single Stage and Two Stage
Two Stage High Fire Low Fire Two Stage High Fire Low Fire
Feet
Meters
Derate by Valve
Outlet Pressure
Adjustment for High
Altitude Operation
0-2000
0-610
3.5
3.1
3.0
2.8
2.7
2.6
2.5
2.4
2.3
1.8
1.6
1.5
1.5
1.4
1.3
1.3
1.2
1.2
10.0
8.8
8.5
8.1
7.7
7.4
7.1
6.7
6.7
5.0
4.4
4.2
4.1
3.9
3.7
3.5
3.4
3.4
2001-3000 611-915
3001-4000 916-1220
4001-5000 1221-1525
5001-6000 1526-1830
6001-7000 1831-2135
7001-8000 2136-2440
8001-9000 2441-2745
9001-10000 2746-3045
This adjustment can only
be done after the heater is
in operation. It is included
in the startup procedures.
Manifold Pressure Settings by Altitude for CANADA
Natural Gas (inches w.c.) Propane Gas (inches w.c.)
Altitude
NOTE: If elevation is
above 6000 ft (1830M), a
high altitude pressure
switch is required; see
Paragraph 7.
Single Stage and Two Stage Single Stage and Two Stage
Two Stage High Fire Low Fire Two Stage High Fire Low Fire
Feet
Meters
0-2000
2001-4500 611-1373
0-610
3.5
2.8
1.8
1.5
10.0
8.1
5.0
4.1
2. Locate the 1/8” output pressure tap on the valve (See FIGURE 11). Turn the
knob on the top of the valve to “OFF”. Connect a manometer to the 1/8" pipe
outlet pressure tap in the valve. Use a water column manometer that is readable
to the nearest tenth of an inch.
FIGURE 11 - Top View of
Valves showing Outlet
Pressure Tap and
3. Single Stage and Two Stage High Fire - Turn the knob on the top of the valve
to “ON”. Remove the cap from the pressure adjusting screw and adjust the gas
train pressure to the pressure selected from the table above. Adjust pressure by
turning the regulator screw IN (clockwise) to increase pressure or OUT (coun-
terclockwise) to decrease pressure.
Adjustment Locations
Single-Stage Valve
Output
1/8” Output
Adjustment
Pressure Tap
Screw
Two Stage Low Fire - Disconnect the wire from the “HI” terminal on the gas
valve and check the low fire pressure. Turn the regulator screw to adjust the
low fire outlet pressure to the “Low Fire” pressure selected from the table. Re-
connect the wire to the gas valve.
Inlet
Pressure
Tap
4. Turn up the thermostat. (NOTE: On Model UDAS, depress and hold the door
safety switch.) Cycle the burner once or twice to properly seat the adjustment
spring in the valve.
Re-check the pressure(s). When the outlet pressure is right for the installation,
remove the manometer and replace the cap.
Two -Stage Valve
Check for leak at the pressure tap fitting.
Adjust Low
Pressure
Output
Adjust High
Pressure
Output
5. With the heater operating determine that the inlet pressure to the heater for
natural gas is between 5 and 13.5 inches w.c. and for propane between 10 and
13.5 inches w.c. Take this reading as close as possible to the heater (Heaters are
equipped with gas valves that have an inlet pressure tap.) If the inlet pressure is
not within the specified range, the inlet pressure must be corrected and Steps 3
and 4 repeated.
Inlet
Pressure
Tap
6. Find the High Altitude Adjustment label in the plastic bag that contained these
instructions. Using a permanent marker, fill-in the appropriate information from
the tables on page 15. Select a location for the label on the outside of the heater
access panel so that it will be conspicuous to anyone operating or servicing the
unit. Be sure the surface is clean and dry and adhere the label.
1/8” Output
Pressure
Tap
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 14
Download from Www.Somanuals.com. All Manuals Search And Download.
The input and/or the capacity of the heater changes with the derate. The tables
below list inputs and capacities at altitudes from sea level to 10,000 ft (3045M).
High Altitude
Capacity Changes
BTUH Inputs and Capacities by Altitude in the UNITED STATES for Model UDAP and Model UDAS
Thermal
Output
Capacity
Thermal
Output
Capacity
Thermal
Output
Capacity
Thermal
Output
Capacity
Normal
Input
Minimum Normal
Input Input
Minimum Normal
Input Input
Minimum Normal
Input Input
Minimum
Input
ALTITUDE
Feet
0-2000
2001-3000
Meters
0-610
611-915
Size 30
Size 45
Size 60
Size 75
30000 24600 30000 45000 37350
28200 23124 28200 42300 35109
45000 60000 49800 42000 75000 62250
42300 56400 46812
52500
39480 70500 58515 49350
38640 69000 57270 48300
3001-4000 916-1220 27600 22632 27600 41400 34362 41400 55200 45816
4001-5000 1221-1525 27000 22140 27000 40500 33615
40500 54000 44820 37800 67500 56025
39600 52800 43824 36960 66000 54780
38700 51600 42828 36120 64500 53535
37800 50400 41832 35280 63000 52290
36900 49200 40836 34440 61500 51045
36000 48000 39840 33600 60000 49800
47250
46200
45150
44100
43050
42000
5001-6000 1526-1830 26400 21648 26400 39600 32868
6001-7000 1831-2135 25800 21156 25800 38700 32121
7001-8000 2136-2440 25200 20664 25200 37800 31374
8001-9000 2441-2745 24600 20172 24600 36900 30627
9001-10000 2746-3045 24000 19680 24000 36000 29880
Feet
0-2000
Meters
0-610
Size 100
Size 125
Size 150
Size 175
105000 88200 73500 120000 100800 84000 150000 124500 105000 175000 145250 122500
2001-3000
611-915
98700 82908 69090 112800 94752
78960 141000 117030 98700 164500 136535 115150
77280 138000 114540 96600 161000 133630 112700
75600 135000 112050 94500 157500 130725 110250
73920 132000 109560 92400 154000 127820 107800
72240 129000 107070 90300 150500 124915 105350
70560 126000 104580 88200 147000 122010 102900
68880 123000 102090 86100 143500 119105 100450
67200 120000 99600 84000 140000 116200 98000
3001-4000 916-1220 96600 81144 67620 110400 92736
4001-5000 1221-1525 94500 79380 66150 108000 90720
5001-6000 1526-1830 92400 77616 64680 105600 88704
6001-7000 1831-2135 90300 75852 63210 103200 86688
7001-8000 2136-2440 88200 74088 61740 100800 84672
8001-9000 2441-2745 86100 72324 60270 98400 82656
9001-10000 2746-3045 84000 70560 58800 96000 80640
Feet
Meters
Size 200
Size 225
Size 250
Size 300
0-2000
0-610
200000 166000 140000 225000 186750 157500 250000 207500 175000 300000 249000 210000
2001-3000
611-915 188000 156040 131600 211500 175545 148050 235000 195050 164500 282000 234060 197400
3001-4000 916-1220 184000 152720 128800 207000 171810 144900 230000 190900 161000 276000 229080 193200
4001-5000 1221-1525 180000 149400 126000 202500 168075 141750 225000 186750 157500 270000 224100 189000
5001-6000 1526-1830 176000 146080 123200 198000 164340 138600 220000 182600 154000 264000 219120 184800
6001-7000 1831-2135 172000 142760 120400 193500 160605 135450 215000 178450 150500 258000 214140 180600
7001-8000 2136-2440 168000 139440 117600 189000 156870 132300 210000 174300 147000 252000 209160 176400
8001-9000 2441-2745 164000 136120 114800 184500 153135 129150 205000 170150 143500 246000 204180 172200
9001-10000 2746-3045 160000 132800 112000 180000 149400 126000 200000 166000 140000 240000 199200 168000
Feet
Meters
Size 350
Size 400
0-2000
0-610
350000 290500 245000 400000 332000 280000
2001-3000
611-915 329000 273070 230300 376000 312080 263200
3001-4000 916-1220 322000 267260 225400 368000 305440 257600
4001-5000 1221-1525 315000 261450 220500 360000 298800 252000
5001-6000 1526-1830 308000 255640 215600 352000 292160 246400
6001-7000 1831-2135 301000 249830 210700 344000 285520 240800
7001-8000 2136-2440 294000 244020 205800 336000 278880 235200
8001-9000 2441-2745 287000 238210 200900 328000 272240 229600
9001-10000 2746-3045 280000 232400 196000 320000 265600 224000
BTUH Inputs and Capacities by Altitude in CANADA for Models UDAP and UDAS
Thermal
Output
Capacity
Thermal
Output
Capacity
Thermal
Output
Capacity
Thermal
Output
Capacity
Normal
Input
Minimum Normal
Input Input
Minimum Normal
Input Input
Minimum Normal
Input Input
Minimum
Input
ALTITUDE
Feet
0-2000
Meters
0-610
Size 30
30000 24600
Size 45
Size 60
Size 75
30000 45000 37350
27000 40500 33615
Size 125
45000 60000 49800
40500 54000 44820
Size 150
42000 75000 62250
37800 67500 56025
Size 175
52500
47250
2001-4500 611-1373 27000 22140
Feet
Meters
Size 100
0-2000
0-610
105000 88200
73500 120000 100800 84000 150000 124500 105000 175000 145250 122500
2001-4500 611-1373 94500 79380
66150 108000 90720
75600 135000 113400 94500 157500 132300 110250
Feet
Meters
Size 200
Size 225
Size 250 Size 300
0-2000
0-610
200000 166000 140000 225000 186750 157500 250000 207500 175000 300000 249000 210000
2001-4500 611-1373 180000 151200 126000 202500 170100 141750 225000 189000 157500 270000 226800 189000
Feet
Meters
Size 350
Size 400
0-2000
0-610
350000 290500 245000 400000 332000 280000
2001-4500 611-1373 315000 264600 220500 360000 302400 252000
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 15
Download from Www.Somanuals.com. All Manuals Search And Download.
2
This heater has a one-piece TCORE ® burner assembly (patent pending) designed
13. Burner
to provide controlled flame stability without lifting or flashback with either natu-
ral or propane gas.
The burner can be removed as a unit for inspection or service; see Maintenance
Section for removal instructions.
All electrical wiring and connections, including electrical grounding MUST be
made in accordance with the National Electric Code ANSI/NFPA No. 70 (latest
edition) or, in Canada, with CSA Standard C22.1. In addition, the installer should
be aware of any local ordinances or gas company requirements that might apply.
14. Electrical
Supply and
Connections
CAUTION: Route wires
so that they do not
Check the rating plate on the heater for the supply voltage and current require-
ments. A dedicated line voltage supply with disconnect switch should be run di-
rectly from the main electrical panel to the heater. All external wiring must be
within approved conduit and have a minimum temperature rise rating of 60°C.
Conduit must be run so as not to interfere with the heater access panel. If the
installation requires a stepdown transformer (Option CG), follow the instructions
shipped with the option package for attaching the transformer to the heater.
contact the flue wrapper
or venter housing.
CAUTION: If any of the
original wire as supplied
with the appliance must
be replaced, it must be
replaced with wiring
material having a
temperature rating of at
least 105°C, except for
limit control, flame
The electrical supply enters at the rear of the heater (See FIGURE 13). Model
UDAS includes a built-in disconnect switch (20A @ 115V; 10A @ 230V Rating).
Model UDAS supply wiring connects to leads located inside a sealed electrical
box. To maintain the sealing feature of the electrical box, always replace the cover
plate. Model UDAP supply wiring connects directly to leads on the integrated
circuit board.
The circuit board (See FIGURE 12) is located inside on the bottom of the control
compartment. The circuit board is polarity sensitive. It is advisable to check the
electrical supply to be certain that the black wire is the “hot” wire and that the
white wire is the neutral wire. The supply connection made to “L1” on the circuit
board must be the “hot” wire.
rollout, and sensor lead
wires which must be
150°C. See Hazard
x
Spark
Transformer
Levels, page 2.
Fuse
Thermostat
Connections
Supply Wiring
Connections
NOTE: Circuit
FIGURE 12 - Supply
Wiring Connections at
the Circuit Board (DSI
Integrated Control
Module)
Fan/Blower
Off
Delay
board is polarity
sensitive; “hot” wire
Status
Lights
must be connected
to Terminal L1.
For all models, the terminal strip for 24 volt thermostat connections is located on
the outside of the cabinet at the back of the heater (See FIGURE 13). Wires from
the terminal strip are factory wired to the circuit board.
24V Control Wiring
Connections
Use either an optional thermostat available with the heater or a field-supplied 24-
volt thermostat. Install according to the thermostat manufacturer's instructions, pay-
ing particular attention to the requirements regarding the location of the thermo-
stat.
15.Thermostat
and
Connections
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 16
Download from Www.Somanuals.com. All Manuals Search And Download.
Make sure that the heat anticipator setting on the thermostat is 0.6 amps (or in
accordance with the amperage value noted on the wiring diagram of your heater).
Make thermostat connections at the terminal strip on the back of the heater. The
strip has four terminals, R, G, W1, and W2; refer to the wiring diagram.
FIGURE 13 - Terminal
Strip for 24-volt wiring
is on the outside rear
of the heater
Rear View - Model UDAP
Rear View - Model UDAS
NOTE: The size of heater
illustrated has a vertical
terminal strip. Some sizes
have a horizontal terminal
strip.
Terminal
Strip
Terminal
Strip
R
R
G
G
W1
W2
W1
W2
Built-in
Disconnect
Switch
Supply
Wiring
Entrance
Supply
Wiring
Entrance
If the heater was ordered with Option CM3, a kit for mounting the thermostat on
the rear of the heater is shipped separately. Follow the instructions in the option
package to attach the bracket.
Unit Mounted
Thermostat -
Option CM3
Select a snap-action thermostat when using the unit mounted thermostat bracket.
Do not use a mercury switch thermostat because the vibration may cause exces-
sive unit cycling. Be careful with the thermostat leads; shorting the thermostat
wires to a metal surface will cause the transformer to fail.
If the heater was ordered with a multiple heater control option, one thermostat can
be used to control up to six heaters. The option includes a 40VA transformer that
replaces the standard transformer in the “master” unit and a relay assembly that
attaches to the “slave” unit. Option CL31 provides for control of two heaters. If
control of additional heaters is desired (up to six total), Option CL32 which is the
relay assembly only must be added to each of the “slave” heaters.
Multiple Heater
Control - Option
CL31 and Option
CL32
The option packages are shipped separately and include complete instructions on
installation and wiring.
The combustion air proving switch is a pressure sensitive switch that monitors air
pressure to ensure that proper combustion airflow is available. On Model UDAP,
the switch is a single pole/normally open device which closes when a negative
pressure is sensed in the venter housing. On Model UDAS, the switch senses the
differential pressure between the negative pressure in the venter housing and the
pressure in the cabinet. (For switch location, see FIGURE 18, page 31.)
16. Combustion
Air Proving
Switch
(Pressure
Switch)
On startup when the heater is cold, the sensing pressure is at the most negative
level, and as the heater and flue system warm up, the sensing pressure becomes
less negative. After the system has reached equilibrium (about 20 minutes), the
sensing pressure levels off.
If a restriction or excessive flue length or turns cause the sensing pressure to be
outside the switch setpoint, the pressure switch will function to shutoff the main
burner. The main burner will remain off until the system has cooled and/or the flue
system resistance is reduced.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 17
Download from Www.Somanuals.com. All Manuals Search And Download.
The two Tables on the left below list the approximate water column negative pres-
sure readings and switch setpoints for sea level operating conditions for Model
UDAP and Model UDAP-CV heaters. The Table on the right lists the approximate
water column differential pressure readings and switch setpoints for sea level op-
erating conditions for Model UDAS heaters.
16. Combustion
Air Proving
Switch (cont’d)
DANGER: Safe operation of this unit requires proper venting
flow. NEVER bypass combustion air proving switch or attempt
to operate the unit without the venter running and the proper
flow in the vent system. Hazardous conditions could result. See
Hazard Levels, page 2.
Pressure Switch Settings
Startup Equilibrium Setpoint Setpoint
Startup Equilibrium Setpoint Setpoint
Model
UDAP
Label Switch
Color P/N
Model
UDAS
Label Switch
Color P/N
Cold
Hot
OFF
ON
Cold
Hot
OFF
ON
Negative Pressure Measured in " w.c.
Differential Pressure Measured in " w.c.
30
45
60
75
100
125
1.00
0.95
1.00
1.00
0.85
0.75
0.78
0.75
0.78
0.85
0.72
0.60
0.65
1.50
1.60
1.80
0.40
0.40
0.50
0.50
0.50
0.40
0.40
1.10
1.10
1.40
0.58
0.58
Green 197030
Green 197030
30
45
60
75
100
125
1.00
1.05
1.10
1.10
0.85
0.75
0.78
0.80
0.85
0.85
0.72
0.60
0.60
1.50
1.60
1.80
0.65
0.65
0.65
0.65
0.55
0.45
0.40
1.10
1.10
1.40
0.83 Yellow 197028
0.83 Yellow 197028
0.83 Yellow 197028
0.83 Yellow 197028
0.73 White 196362
0.68 Orange 196388
0.68 Orange 196388
0.68 Orange 196388
0.58
0.58
1.30
1.30
1.60
Green 197030
0.63
0.58
1.30
1.30
1.60
Pink 197032
Green 197030
Blue 201158
Blue 201158
Red 201159
150, 175 0.75
200, 225 2.20
250, 300 2.30
350, 400 2.60
Green 197030 150, 175 0.75
Blue 201158 200, 225 2.20
Blue 201158 250, 300 2.30
Red 201159 350, 400 2.60
Startup
Cold
Equilibrium Setpoint Setpoint
Model UDAP-CV
with Opt AV6
Label
Color
Switch
P/N
Hot
OFF
ON
Negative Pressure Measured in " w.c.
30
45
60
75
100
1.10
1.10
0.92
0.97
0.88
0.84
0.81
0.75
0.78
0.71
0.65
0.50
0.60
0.60
0.55
0.83 Yellow 197028
0.68 Orange 196388
0.78 Lt Blue 197029
0.78 Lt Blue 197029
0.73
White 196362
All units are equipped with a temperature activated auto reset limit control. The
control is factory set and is non-adjustable. If the setpoint is reached, the limit
control will interrupt the electric supply to the gas valve. This safety device pro-
vides protection in the case of motor failure or lack of airflow due to a restriction at
the inlet or outlet. (For location, see FIGURE 18, page 31.)
17. Limit Control
CAUTION: The auto reset limit control will continue to shut down
the heater until the cause is corrected. Never bypass the limit
control; hazardous conditions could result. See Hazard Intensity
Levels, page 2.
Sizes 30-125 are equipped with a temperature activated manually reset flame rollout
switch. The flame rollout switch is located at the top of the burner assembly. It is
factory set and is non-adjustable. If the setpoint is reached, the flame rollout acts to
interrupt the electric supply to the gas valve. If the flame rollout switch activates,
identify and correct the cause before resetting the switch. Refer to the Mainte-
nance Section for information on probable causes and instructions on resetting the
flame rollout switch. (For location, see FIGURE 18, page 31.)
18. Flame
Rollout
Switch -
Sizes 30-125
only
DANGER: If the manual reset flame rollout switch activates,
identify and correct the cause before resetting the switch. Never
bypass the flame rollout switch; hazardous conditions could result.
See Hazard Intensity Levels, page 2.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 18
Download from Www.Somanuals.com. All Manuals Search And Download.
All sizes of Model UDAS heaters are equipped with a door switch which prevents
the heater from operating when the service door panel is open. The service panel
of a Model UDAS is equipped with a pliable gasket material that fully seals the
door to provide added protection from building air entering the combustion zone
of the heater. (For switch location, see FIGURE 18, page 31.)
19. Door Switch
- Model
UDAS only
This heater is equipped with a direct spark integrated control module (circuit board).
The module monitors the safety devices and controls the operation of the fan and
venter motors and the gas valve between heat cycles.
20. Ignition
System
FIGURE 14 – DSI Integrated Control Module (circuit board)
x
Spark
Transformer
Fuse
Thermostat
Connections
Dip Switch
LED Lights
Fan/Blower
Off
Delay
Status
Lights
Flame Status - Yellow LED Codes
Steady ON....... Flame is sensed
Slow Flash ...... Weak flame (current below 1.0
microamps ±50%)
Fast Flash ........ Undesired Flame (valve open
and no call for heat)
Control Status - Green LED Codes
Steady ON....... Normal Operation, No call for heat
Fast Flash ........ Normal Operation, Call for heat
1 Flash ............ System Lockout, Failed to detect or sustain
flame
2 Flashes ......... Pressure Switch Did Not Close within 30
Seconds of Venter Motor
Fan/Blower OFF Delay Settings (dip switches)
SW-1 SW-2 Time
3 Flashes ......... High Limit or Flame Rollout Switch Open
4 Flashes ......... Pressure switch is closed before venter
motor is energized
Off
Off
On
On
Off
On
Off
On
120 seconds (factory setting)
90 seconds
160 seconds
Steady OFF ..... Blown Fuse, No Power, or Defective Board
180 seconds
1) Call for Heat - The thermostat calls for heat by energizing the “W” terminal.
The control checks to see that the limit switch is closed and the pressure switch is
open. If the limit switch is open, the control responds as defined in the “Abnormal
Heat Cycle, Limit Switch Operation”. If the pressure switch is closed, the control
will do four flashes on the green LED and wait indefinitely for the pressure switch
to open. If the pressure switch is open, the control proceeds to prepurge.
Normal Heat Cycle
Operating
Sequence
2) Prepurge - The control energizes the venter motor and waits for the pressure
switch to close. If the pressure switch does not close within 30 seconds of the
venter motor energizing, the control will do two flashes on the green LED. The
control will leave the venter motor energized indefinitely as long as the call for
heat remains and the pressure switch is open.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 19
Download from Www.Somanuals.com. All Manuals Search And Download.
When the pressure switch is proven closed, the control begins the prepurge time.
If flame is present any time while in prepurge, the prepurge time is restarted. If
flame is present long enough to cause lockout, the control responds as defined in
“Fault Modes, Undesired Flame”.
20. Ignition
System
(cont’d)
Normal Heat
Cycle Operating
Sequence (cont’d)
The control runs the venter motor for a 20 second prepurge time, then proceeds to
the ignition trial period.
3) Ignition Trial Period - The control energizes the spark and main gas valve.
The venter remains energized. If flame is sensed during the first 16 seconds, the
spark is de-energized and the control proceeds to heat fan/blower on delay. If
flame has not been sensed during the first 16 seconds, the control de-energizes the
spark output and keeps the gas valve energized for an additional one second flame
proving period. If flame is not present after the flame proving period, the control
de-energizes the gas valve and proceeds with ignition re-tries as specified in “Ab-
normal Heat Cycle, Ignition Re-try”. If flame is present, the control proceeds to
the fan/blower on delay.
4) Fan/Blower On Delay - The control waits for 30 seconds from the time the gas
valve opened and then energizes the fan/blower motor. The gas valve and venter
motor remain energized. The control proceeds to steady heat mode.
5) Steady Heat - Control inputs are continuously monitored to ensure limit and
pressure switches are closed, flame is established, and the thermostat call for heat
remains. When the thermostat call for heat is removed, the control de-energizes
the gas valve and begins post-purge and fan/blower off delay timing.
6) Post Purge - The venter motor output remains on for a 45 second post-purge
period after the thermostat is satisfied.
7) Fan/Blower Off Delay - The fan/blower motor is de-energized after a blower
off delay as selected by the dip switches. Timing begins when the thermostat is
satisfied. Delay times are as follows:
SW1 SW2 Time
OFF OFF 120 seconds (default when shipped)
OFF ON
90 seconds
OFF 160 seconds
ON 180 seconds
ON
ON
Interrupted Thermostat Call for Heat - If the thermostat demand for heat is
removed before the flame is recognized, the control will run the venter motor for
the post purge period and de-energize all outputs.
Abnormal Heat
Cycle Functions
If the thermostat demand for heat is removed after successful ignition, the control
will de-energize the gas valve, run the venter motor through post purge, and run
the fan/blower motor on heat speed for the selected delay off time.
Ignition Retry - If flame is not established on the first trial for ignition period, the
control de-energizes the gas valve and the venter motor remains energized for an
inter-purge period of 10 seconds. The spark and gas valve are then re-energized,
and the control initiates another trial for ignition.
If flame is not established on the second trial for ignition, the control de-energizes
the gas valve, energizes the fan/blower motor on heat speed, and venter motor
remains energized. The fan/blower motor is shut off after the longest selectable
fan delay time (180 seconds). When the fan/blower motor de-energizes, the spark
and gas valve are re-energized and the control initiates another trial for ignition.
(This fan delay is self-healing feature for an open auxiliary limit switch).
If flame is not established on the third trial for ignition period, the control de-
energizes the gas valve, and the venter motor remains energized for an inter-purge
period of 10 seconds. The control then re-energizes the gas valve and spark and
initiates another trial for ignition.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 20
Download from Www.Somanuals.com. All Manuals Search And Download.
If flame is not established on the fourth trial for ignition (initial try plus 3 re-tries),
the control de-energizes the gas valve and goes into lockout. The control goes to
one flash on the green LED to indicate ignition failure lockout.
Limit Switch Operation - The limit switch is ignored unless a call for heat is
present (W energized). If the limit switch is open and a call for heat is present, the
control de-energizes the gas valve and turns the fan/blower motor on heat speed
and runs the venter motor.
When the switch re-closes or the call for heat is lost, the control runs the venter
motor through post purge and runs the blower/fan motor through the selected fan
off delay. The control will return to normal operation after fan off delay is com-
pleted.
Pressure Switch - If the pressure switch opens before the trial for ignition period,
the venter motor will run through the pressure switch recognition delay (2 sec-
onds), the gas valve will be de-energized, and the venter motor will run through
the postpurge time. The control will re-start the heat cycle at the pressure switch
proving state if the call for heat still exists.
Pressure switch opening for less than 2 seconds during the trial for ignition period
shall not interrupt the heat cycle. (Gas valve will de-energize while the pressure
switch is open.)
If the pressure switch opens after a successful ignition, the control will de-energize
the gas valve. If flame is lost before the end of the 2 second pressure switch recog-
nition delay, the control will respond to the loss of flame. If the pressure switch
remains open for 2 seconds and the flame remains, the control de-energizes the gas
valve, the venter motor runs through post-purge, and the fan/blower motor runs on
heat speed through the selected fan off delay. When the fan off delay is over, the
fan/blower motor is de-energized, and a heat cycle is begun if the call for heat still
exists.
When the thermostat calls for continuous fan (G) without a call for heat, the fan
motor is energized after a .25 second delay. NOTE: This brief on delay is to allow
the “G” terminal to energize slightly before “Y” and an external changeover relay
to switch from “G” to “W” without causing momentary glitches in the fan/blower
output. The fan remains energized as long as the call for fan remains without a call
for heat.
Continuous Fan
Operation
If a call for heat (W) occurs during continuous fan, the fan/blower will de-ener-
gize.
A call for fan is ignored while in lockout.
Undesired Flame - If flame is sensed longer than 20 seconds while the gas valve
is de-energized, the control shall energize the venter motor and fan/blower motor
on heat speed. When flame is no longer sensed, the venter motor will run through
postpurge, and the fan/blower motor will run through the selected heat fan off
delay time. The control will do a soft lockout, but will still respond to open limit
and flame. The FLAME (yellow) LED shall flash rapidly when lockout is due to
undesired flame.
Fault Modes
Gas Valve Relay Fault - If the control senses the gas valve as energized for more
than one second when the control is not attempting to energize the gas valve, or the
gas valve is sensed as not energized when it is supposed to be energized, then the
control will lockout with green LED off. The control assumes either the contacts
of the relay driving the gas valve have welded shut, or the sensing circuit has
failed. The venter motor is forced off to open the pressure switch to stop gas flow
unless flame is present.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 21
Download from Www.Somanuals.com. All Manuals Search And Download.
If the gas valve was sensed as closed when it should be open, and has not de-
energized after the venter motor was shutoff for 15 seconds, then the venter motor
is re-energized to vent the unburned gas.
20. Ignition
System
(cont’d)
Fault Modes
(cont’d)
Soft Lockout - The control shall not initiate a call for heat or call for continuous
fan while in lockout. The control will still respond to an open limit and undesired
flame. Lockout shall automatically reset after one hour. Lockout may be manually
reset by removing power from the control for more than one second or removing
the thermostat call for heat for more than one and less than 20 seconds.
Hard Lockout - If the control detects a fault on the control board, the status LED
will be de-energized, and the control will lockout as long as the fault remains. A
hard lockout will automatically reset if the hardware fault clears.
Lockout
Power Interruption - During a momentary power interruption or at voltage levels
below the minimum operating voltage (line voltage or low voltage) the system will
self-recover without lockout when voltage returns to the operating range.
Power interruptions of less than 80mS shall not cause the control to change operat-
ing states. Power interruptions greater than 80mS may cause the control to inter-
rupt the current operating cycle and re-start.
The main operating gas valve is powered by the 24-volt control circuit through the
thermostat and safety controls. The main control valve is of the diaphragm type
providing regulated gas flow preset at the factory. (For location, see FIGURE 18,
page 31.)
21. Gas Valve
22. Fan Motor
WARNING: The operating valve is the prime safety shutoff. All
gas supply lines must be free of dirt or scale before connecting
the unit to ensure positive closure. See Hazard Levels, page 2.
The fan motor is equipped with thermal overload protection of the automatic reset
type. Should the motor refuse to run, it may be because of improper current char-
acteristics. Make certain that the correct voltage is available at the motor.
NOTE: If the unit is equipped with an optional totally enclosed motor or optional
voltage, the horsepower may be larger than the standard motor. Refer to the motor
nameplate to verify horsepower.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 22
Download from Www.Somanuals.com. All Manuals Search And Download.
23. Wiring Diagrams
FIGURE 15A - Typical Wiring Diagram for Model UDAP or Model UDAS, Single Stage
30 VA
LINE/1/60
SYSTEM TRANSFORMER
FACTORY WIRING
Y
W
R
FIELD WIRING
R
OPTIONAL FACTORY
WIRING
G
G
WIRE NUT
BR
GRD
SCREW
BK
G
W1
R
SW1
G
W
R
SEC
COM
L1
NEUTRAL NEUTRAL
L1
P3-1
Y
PR
Y
W
NEUTRAL
P3-2
G
FAN MOTOR
BK
BK
W
EAC/BLO
P3-3
W
G
DOOR INTERLOCK
(UDAS ONLY)
P3-4
P3-5
P1-8
P1-3
R
R
R
C
CAPACITOR
(SEE NOTE #6)
LED FLASH CODES
GREEN LED
STEADY ON NORMAL OPERATION NO CALL FOR HEAT
FAST FLASH NORMAL OPERATION CALL FOR HEAT
LIMIT CONTROL
W2
R
R
1 FLASH
2 FLASH
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS
OF VENTER ENERGIZED
R
R
3 FLASH
4 FLASH
LIMIT SWITCH OR ROLLOUT SWITCH OPEN
FLAME ROLLOUT
(MODELS 30-125 ONLY)
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS
ENERGIZED
STEADY OFF INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
P1-6
P1-5
P1-4
P1-2
P1-7
P1-9
Y
STEADY ON FLAME SENSED
PRESSURE SWITCH
SLOW FLASH WEAK FLAME
Y
Y
FAST FLASH UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)
BK
BL
FAN OFF DELAY
TEST
IND
S W 1
VENTER
MOTOR
TIME
1
2
GAS VALVE
90
OFF
OFF
ON
ON
FLAME
OK
BL
BR
W
W
BK
NEUTRAL
LED
LED
120
160
180
OFF
OFF
ON
G
Y
G
FLAME
R
ON
ELECTRODE
SPARK
CAPACITOR
(SEE NOTE #7)
BR
TRANSFORMER
DSI CONTROL
FLAME
GROUND
SPARK GAP
OPERATING SEQUENCE
FIELD CONTROL WIRING
1. SET THERMOSTAT AT LOWEST SETTING, (FAN SWITCH
AT "AUTO" POSITION, OPTION CL2 ONLY).
2. TURN ON MANUAL GAS VALVE.
3. TURN ON POWER TO UNIT.
4. SET THERMOSTAT AT DESIRED SETTING.
5. THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN
TOTAL WIRE
LENGTH
DISTANCE FROM
UNIT TO CONTROL
MIN. RECOMMENDED
WIRE GAUGE
#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE
150'
250'
350'
75'
125'
175'
MOTOR IS ENERGIZED.
8. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT
(SEE LIGHTING INSTRUCTIONS).
WIRING CODE
BLACK - BK
BROWN - BR
RED - R
9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION, OPTION CL2 ONLY.
ORANGE - O
YELLOW - Y
GREEN - G
BLUE - BL
PURPLE - PR
WHITE - W
NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.
4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.
5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT
VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS
150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.
8. SET THERMOSTAT ANTICIPATOR AT 0.6 AMPS.
UDAP & UDAS SERIES
WD# 185139 REV #1 AG1
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 23
Download from Www.Somanuals.com. All Manuals Search And Download.
23. Wiring Diagrams (cont’d)
FIGURE 15B - Typical Wiring Diagram for Model UDAP or Model UDAS, Single Stage with
Optional Air Recirculation
30 VA
LINE/1/60
SYSTEM TRANSFORMER
FACTORY WIRING
Y
FIELD WIRING
R
OPTIONAL FACTORY
G
WIRING
G
WIRE NUT
BR
GRD
SCREW
BK
SW1
G
W1
G
SEC
COM
L1
NEUTRAL NEUTRAL
L1
P3-1
P3-2
P3-3
P3-4
P3-5
P1-8
P1-3
PR
Y
Y
G
W
R
C
W
NEUTRAL
W1
FAN MOTOR
BK
BK
W
W2
EAC/BLO
G
DOOR INTERLOCK
(UDAS ONLY)
R
R
R
CAPACITOR
(SEE NOTE #6)
RH
RC
LED FLASH CODES
GREEN LED
STEADY ON NORMAL OPERATION NO CALL FOR HEAT
FAST FLASH NORMAL OPERATION CALL FOR HEAT
LIMIT CONTROL
W2
R
R
1 FLASH
2 FLASH
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME LOSSES
PRESSURE SWITCH DOES NOT CLOSE WITHIN 30 SECONDS
OF VENTER ENERGIZED
R
R
3 FLASH
4 FLASH
LIMIT SWITCH OR ROLLOUT SWITCH OPEN
FLAME ROLLOUT
(MODELS 30-125 ONLY)
PRESSURE SWITCH IS CLOSED BEFORE VENTER IS
ENERGIZED
P1-6
P1-5
P1-4
P1-2
P1-7
P1-9
STEADY OFF INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
Y
STEADY ON FLAME SENSED
PRESSURE SWITCH
Y
Y
SLOW FLASH WEAK FLAME
FAST FLASH UNDESIRED FLAME (VALVE OPEN & NO CALL FOR HEAT)
BK
W
BL
FAN OFF DELAY
TIME
TEST
IND
VENTER
MOTOR
GAS VALVE
90
120
160
180
OFF
OFF
ON
ON
FLAME
OK
BL
BR
W
BK
NEUTRAL
LED
LED
OFF
OFF
ON
G
Y
G
FLAME
R
ON
ELECTRODE
SPARK
CAPACITOR
(SEE NOTE #7)
TRANSFORMER
BR
DSI CONTROL
FLAME
GROUND
SPARK GAP
OPERATING SEQUENCE
FIELD CONTROL WIRING
1. SET THERMOSTAT AT LOWEST SETTING, FAN SWITCH AT "AUTO" POSITION.
2. TURN ON MANUAL GAS VALVE.
TOTAL WIRE
LENGTH
DISTANCE FROM
UNIT TO CONTROL
MIN. RECOMMENDED
3. TURN ON POWER TO UNIT.
WIRE GAUGE
4. SET THERMOSTAT AT DESIRED SETTING.
5. LOW STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE FAN MOTOR.
6. HIGH STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
7. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT FULL RATE.
8. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION.
#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE
150'
250'
350'
75'
125'
175'
9. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT
(SEE LIGHTING INSTRUCTIONS).
WIRING CODE
BLACK - BK
BROWN - BR
RED - R
ORANGE - O
YELLOW - Y
GREEN - G
BLUE - BL
NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.
4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.
PURPLE - PR
WHITE - W
5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT
VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS
150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.
8. SET THERMOSTAT SECOND STAGE ANTICIPATOR AT 0.6 AMPS. AND FIRST
STAGE ANTICIPATOR AT MINIMUM.
UDAP & UDAS SERIES
WD# 185306 REV#2
9. JUMPER THERMOSTAT TERMINALS G TO W1 AND RH TO RC IF FAN CONTROL FROM
THERMOSTAT FAN SWITCH IS DESIRED.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 24
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 15C - Typical Wiring Diagram for Model UDAP or Model UDAS, Two Stage Gas Valve
W1
30 VA
LINE/1/60
SYSTEM TRANSFORMER
FACTORY WIRING
Y
FIELD WIRING
R
R
OPTIONAL FACTORY
WIRING
G
G
WIRE NUT
BR
GRD
SCREW
BK
W2
G
G
W1
R
SW1
SEC
Y
COM
L1
NEUTRAL NEUTRAL
L1
P3-1
P3-2
P3-3
PR
Y
W
NEUTRAL
G
W
R
FAN MOTOR
BK
BK
W
W1
EAC/BLO
G
DOOR INTERLOCK
(UDAS ONLY)
P3-4
P3-5
P1-8
P1-3
R
R
CAPACITOR
(SEE NOTE #6)
RH
RC
LED FLASH CODES
C
GREEN LED
STEADY ON NORMAL OPERATION NO CALL FOR HEAT
FAST FLASH NORMAL OPERATION CALL FOR HEAT
LIMIT CONTROL
R
R
W2
1 FLASH
2 FLASH
IN LOCKOUT FROM FAILED IGNITIONS OR FLAME
W2
PRESSURE SWITCH DOES NOT CLOSE WITHIN
30 SECONDS OF VENTER ENERGIZED
O
R
R
3 FLASH
4 FLASH
LIMIT SWITCH OR ROLLOUT SWITCH OPEN
FLAME ROLLOUT
(MODELS 30-125 ONLY)
PRESSURE SWITCH IS CLOSED BEFORE
VENTER IS ENERGIZED
P1-6
P1-5
P1-4
P1-2
P1-7
P1-9
STEADY OFF INTERNAL CONTROL FAULT OR NO POWER
YELLOW LED
Y
ALT.
HONEYWELL
TWO STAGE
GAS VALVE
STEADY ON FLAME SENSED
SLOW FLASH WEAK FLAME
PRESSURE SWITCH
HONEYWELL
TWO STAGE
GAS VALVE
Y
Y
FAST FLASH UNDESIRED FLAME (VALVE OPEN & NO CALL
FOR HEAT)
BK
W
BL
BL
FAN OFF DELAY
TEST
MV
C
LO
C
IND
S W
VENTER
MOTOR
TIME
2
1
90
OFF
ON
FLAME
OK
BR
W
BK
BR
NEUTRAL
LED
LED
120
160
180
OFF
ON
OFF
OFF
ON
G
Y
G
FLAME
R
ON
ELECTRODE
SPARK
CAPACITOR
(SEE NOTE #7)
TRANSFORMER
O
O
BR
HI
HI
DSI CONTROL
FLAME
GROUND
SPARK GAP
OPERATING SEQUENCE
1. SET THERMOSTAT AT LOWEST SETTING, (FAN SWITCH AT "AUTO" POSITION, OPTION CL18 ONLY).
2. TURN ON MANUAL GAS VALVE.
FIELD CONTROL WIRING
3. TURN ON POWER TO UNIT.
TOTAL WIRE
LENGTH
4. SET THERMOSTAT AT DESIRED SETTING.
DISTANCE FROM
UNIT TO CONTROL
MIN. RECOMMENDED
5. LOW STAGE OF THERMOSTAT CALLS FOR HEAT, ENERGIZING THE VENTER MOTOR.
6. VENTER PRESSURE SWITCH CLOSES, FIRING UNIT AT LOW RATE.
WIRE GUAGE
#18 GA. WIRE
#16 GA. WIRE
#14 GA. WIRE
150'
250'
350'
75'
125'
175'
7. BURNER FLAME IS SENSED, AND IN 30 SECONDS THE FAN
MOTOR IS ENERGIZED.
8. HIGH STAGE OF THERMOSTAT CALLS FOR HEAT, FIRING UNIT AT FULL RATE.
9. SET FAN SWITCH AT "ON" POSITION FOR CONTINUOUS FAN OPERATION, OPTION CL18 ONLY.
10. IF THE FLAME IS EXTINGUISHED DURING MAIN BURNER OPERATION,
THE INTEGRATED CONTROL SYSTEM CLOSES THE MAIN VALVE AND
MUST BE RESET BY INTERRUPTING POWER TO THE CONTROL CIRCUIT
(SEE LIGHTING INSTRUCTIONS).
WIRING CODE
BLACK - BK
BROWN - BR
RED - R
ORANGE - O
YELLOW - Y
GREEN - G
BLUE - BL
NOTES
1. THE FOLLOWING CONTROLS ARE FIELD INSTALLED OPTIONS: THERMOSTAT
2. DOTTED WIRING INSTALLED BY OTHERS.
3. CAUTION: IF ANY OF THE ORIGINAL WIRING AS SUPPLIED WITH THE
APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL
HAVING A TEMPERATURE RATING OF AT LEAST 105° C. EXCEPT FOR SENSOR
LEAD WIRE, FLAME ROLLOUT AND LIMIT WIRING WHICH MUST BE 150° C.
4. USE 18 GA. WIRE FOR ALL WIRING ON THE UNIT.
5. LINE AND FAN MOTOR BRANCH WIRE SIZES SHOULD BE OF A SIZE TO PREVENT
VOLTAGE DROPS BEYOND 5% OF SUPPLY LINE VOLTAGE.
PURPLE - PR
WHITE - W
6. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON 115V MODELS
150-400 AND 208/230V MODELS 100-400.
7. CAPACITOR IS REMOTE MOUNTED AND INCLUDED ONLY ON MODELS 150 - 400.
8. SET THERMOSTAT FIRST STAGE ANTICIPATOR AT 0.6 AMPS AND
SECOND STAGE ANTICIPATOR AT 0.2 AMPS.
UDAP & UDAS SERIES
WD# 185244 REV #3 AG2
9. JUMPER THERMOSTAT TERMINALS RH TO RC.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 25
Download from Www.Somanuals.com. All Manuals Search And Download.
o Check to be sure that all screws used to hold shipping brackets were re-
24. Check
Installation
and Startup
installed in the heater cabinet.
o Check suspension. Unit must be secure and level.
o Check clearances from combustibles. Requirements are in Paragraph 8.
o Check vent system to be sure that it is installed according to the instructions
in the appropriate Vent Installation Manual as listed in Paragraph 1.
o Check piping for leaks and proper gas line pressure. Bleed gas lines of
Check the
installation prior
to startup:
trapped air. See Paragraph 12.
o Check electrical wiring. Be sure all wire gauges are as recommended. A
service disconnect switch should be used. Verify that fusing or circuit break-
ers are adequate for the load use.
o Check polarity. Verify that line voltage exists between the black “L1” and
earth ground.
o If installed in California, verify that California Warning Label is displayed
Heater
Startup:
WARNINGS: For your safety, read before operating. If you do
not follow these instructions exactly, a fire or explosion may
result causing property damage, personal injury, or loss of life.
• This appliance does not have a pilot. It is equipped with an ignition
device which automatically lights the burner. Do not try to light the
burner by hand.
• Before operating, smell all around the appliance area for gas. Be
sure to smell next to the floor because some gas is heavier than air
and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your
building.
• Immediately call your gas supplier from a neighbor's phone.
Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call your fire department.
• Use only your hand to turn the gas control ON/OFF knob on the
gas valve. Never use tools. If the valve ON/OFF knob will not turn
by hand, do not try to repair it. Call a qualified service technician.
Force or attempted repair may result in a fire or explosion.
• Should overheating occur, or the gas supply fail to shut off, turn off
the manual gas valve to the appliance before shutting off the
electrical supply.
• Do not use this appliance if any part has been under water. Imme-
diately call a qualified service technician to inspect the appliance
and to replace any part of the control system and any gas control
which has been under water.
1. Set thermostat at lowest setting.
Operating
Instructions and
Operating Sequence
2. Turn off all electric power to the appliance.
3. This appliance is equipped with an ignition device which automatically lights
the burner. Do not try to light the burner by hand. Open the access door and
locate the gas control (ON/OFF) knob on the gas valve. (See FIGURE 16.)
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 26
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Turn the gas control knob clockwise to "OFF".
FIGURE 16 - Gas Valve
ON/OFF Control Knob
5. Wait five (5) minutes to clear out any gas. Then smell for gas, including near
the floor. If you smell gas, STOP! and follow the steps in the WARNINGS
printed above or on the Operating Label on the heater. If you do not smell
gas, proceed to the next step.
Top View
6. Turn the gas control knob counterclockwise to "ON".
7. Close the access door.
8. Turn on the electric power to the heater.
9. Set the thermostat to the desired setting.
Gas Control
Knob
(shown in the
ON position)
Side View
NOTE: If the appliance does not operate, follow the instructions "To Turn Off
Gas to Appliance" printed below (and on the Operating Label on the heater) and
call your service technician.
Gas
Flow
Gas
Flow
10. Thermostat calls for heat, energizing the venter motor.
11. Venter pressure switch closes, firing the unit.
12. Burner flame is sensed and in 30 seconds after the gas valve is energized, the
fan motor is energized.
13. If the flame is extinguished during the main burner operation, the integrated
control system closes the main valve and must be reset by interrupting
power to the control circuit. (See lighting instructions on the heater.).
TO TURN OFF GAS TO THE APPLIANCE
1) Set thermostat to lowest setting
2) If service is to be performed, turn off all electric power to the appliance.
3) Open the access door.
4) Turn the gas control knob clockwise to "OFF". Do not force.
5) Close the access door.
o Vent System Testing Procedure - Model UDAP
Check installation
after startup:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required
in the National Fuel Gas Code, ANSI Z223.1 or CAN/CGA B149.1 and
B149.2, Installation Code for Gas Burning Appliances and Equipment, and
the venting installation manual. Determine that there is no blockage or
restriction, leakage, corrosion or other deficiencies that could cause an
unsafe condition.
3. In so far as practical, close all building doors and windows and all doors
between the space where the heater is and other spaces of the building. Turn
on clothes dryers and exhaust fans, such as range hoods and bathroom
exhausts, so they shall operate at maximum speed. Do not operate a sum-
mer exhaust fan. Close fireplace dampers.
4. Light the heater following the lighting instructions. Adjust the thermostat
for continued operation. Verify that combustion products are venting
properly. After determining that the heater vents properly, return doors,
windows, exhaust fans, and fireplace dampers to their previous conditions.
If improper venting is observed, the venting system must be corrected.
o With the unit in operation, measure valve outlet gas pressure. If operated at
high altitude, adjust outlet gas pressure for altitude.
See information and instructions in Paragraph 12.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 27
Download from Www.Somanuals.com. All Manuals Search And Download.
o Turn the unit off and on, pausing two minutes between each cycle. Observe
24. Startup
(cont’d)
for smooth ignition.
o Place the "Owner's Envelope" containing the Limited Warranty, this booklet,
and any control or optional information in an accessible location near the
heater. Follow the instructions on the envelope.
DANGER: The gas burner in this gas-fired equipment is designed and equipped to provide safe
controlled complete combustion. However, if the installation does not permit the burner to
receive the proper supply of combustion air, complete combustion may not occur. The result is
incomplete combustion which produces carbon monoxide, a poisonous gas that can cause death.
Safe operation of indirect-fired gas burning equipment requires a properly operating vent system
that vents all flue products to the outside atmosphere. FAILURE TO PROVIDE PROPER
VENTING WILL RESULT IN A HEALTH HAZARD WHICH COULD CAUSE SERIOUS
PERSONAL INJURY OR DEATH.
Always comply with the combustion air requirements in the installation codes and in Paragraph
9. Combustion air at the burner should be regulated only by manufacturer-provided equipment.
NEVER RESTRICT OR OTHERWISE ALTER THE SUPPLY OF COMBUSTION AIR TO
ANY HEATER. Model UDAP units installed in a confined space must be supplied with air for
combustion as required by Code and in Paragraph 9 of this heater installation manual.
MAINTAIN THE VENT OR VENT/COMBUSTION AIR SYSTEM IN STRUCTURALLY
SOUND AND PROPER OPERATING CONDITION.
WARNING: If you turn off the power supply, turn off the gas. See Hazard
Levels, page 2.
MAINTENANCE
AND SERVICE
The material contained in the MAINTENANCE AND SERVICE Section of this
manual is designed to aid a qualified service person in maintaining and servicing
this equipment. This heater will operate with a minimum of maintenance. To en-
sure long life and satisfactory performance, a heater that is operated under normal
conditions should be inspected and cleaned at the start of each heating season. If
the heater is operating in an area where an unusual amount of dust or soot or other
impurities are present in the air, more frequent maintenance is recommended.
When any service is completed, be careful to reassemble correctly to ensure that
no unsafe conditions are created. When re-lighting, always follow the lighting
instructions on the heater.
Maintenance Schedule - The following procedures should be carried out at least
annually (See FIGURE 18 and Paragraphs 26-39.):
25. Maintenance
Schedule
• Clean all dirt, lint, and grease from the combustion air opening (UDAP) and
venter assembly.
• Clean all dirt, lint, and grease from the fan blade, fan guard, and motor.
• Check the heat exchanger both internally and externally.
NOTE: If replacement
parts are required,
use only factory-authorized
parts.
• Check the burner for scale, dust, or lint accumulation. Clean if needed.
• Check the vent or vent/combustion air system for soundness. Clean openings.
Replace any parts that do not appear sound.
• Check the wiring for any damaged wire. Replace damaged wiring. (See Para-
graph 14 for replacement wiring requirements.)
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 28
Download from Www.Somanuals.com. All Manuals Search And Download.
2
This heater is equipped with a TCORE ® heat exchanger (patent pending).
26. Heat
Exchanger
Maintenance
Remove any external dirt or dust accumulation. Visually check the heat exchanger
for cracks and holes. If a crack or hole is observed, replace the heat exchanger.
NOTE: Inspection of the lower portion of the heat exchanger is done with the
burner removed. See the Burner Service section below for information on inspect-
ing the lower portion of the heat exchanger.
2
This heater is equipped with a TCORE ® burner (patent pending).
27. Burner
Inspect the burner/control compartment annually to determine if cleaning is nec-
essary. If there is an accumulation of dirt, dust, and/or lint, clean the compartment
and follow the instructions below to remove and clean the burner.
Maintenance
CAUTION: Use of eye protection is recommended.
Burner Removal
Instructions (Refer
to FIGURE 17.)
1. Outside the cabinet, shut the gas supply off at the manual valve ahead of the
union.
2. Turn off electric supply.
3. Disconnect the gas supply at the union outside of the cabinet.
4. Remove the access panel.
5. Disconnect the Gas Train and Move Out of the Way - At the gas valve,
mark and disconnect the wires. Carefully remove the burner orifice and
orifice adapter locking nut. Slide the orifice adapter out through the bracket
on the burner pushing the gas train to the right. This will move the gas train
out of the way.
6. Move the Control Assembly - Remove the two screws holding the control
assembly bracket. Being careful not to disconnect any wires, slide the control
assembly to the right.
7. Remove Secondary Air Baffles (Sizes 60-400 only) - Vertical along the right
side of the burner, locate the flat plate(s) identified as the secondary air
baffle(s). The quantity of baffles could be one to four depending on heater
FIGURE 17 - Burner
Removal (UDAP
illustrated; same process
for both UDAP and UDAS)
Burner Body Support (at least two per unit) - Remove screw attaching
to secondary air shield. Support remains attached to burner.
Secondary Air Shield
Burner
Orifice
Venturi Tube
Slide right; rotate
inward; pull out
Gas Valve
Disconnect gas train at
orifice and outside the
heater; slide to the right.
Slide Right
Secondary Air Baffle
Orifice Adapter Locking Nut
Control Bracket Screws -
Loosen bracket; slide right.
(Qty varies per size.)
Mark locations before removing.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 29
Download from Www.Somanuals.com. All Manuals Search And Download.
size. Each baffle is held in place by one screw. For re-assembly, on the
secondary air shield, mark the location (top and bottom) of each baffle.
Remove all baffles.
27. Burner
Maintenance
(cont’d)
Burner Removal
(cont’d)
8. Remove Burner Assembly
a) Locate the burner body supports. Depending on the size, the burner will
have two or more supports. At each support, remove the one screw that
attaches it to the secondary air shield
b) Holding the venturi tube, slide the entire burner assembly slightly to the
right to disengage the burner from the supports on the left. Then rotate
the open end of the venturi tube inward toward the heater. Carefully pull
the burner assembly out of the cabinet.
With the burner assembly removed, shine a flashlight on the burner ribbons. Look
for carbon buildup, scale, dust, lint, and/or anything that might restrict flow through
the spaces between the burner ribbons. Holding the burner assembly so that any
foreign material will fall away from the burner, use a stiff bristle brush to loosen
and remove any foreign material(s). If the burner is excessively dirty, remove one
of the burner end caps. Remove the four screws that hold the end cap to the burner
housing. Lightly tap the end cap to remove it.
Inspect and Clean the
Burner
Clean all foreign material from the burner and venturi. After the burner is thor-
oughly clean, replace the end cap making certain that it is tight against the burner
housing. NOTE: If any of the burner components are damaged or deteriorated,
replace the burner assembly.
Inspect the Lower Portion of the Heat Exchanger (with burner
assembly removed)
At the burner flame entrance of each tube, shine a bright light into each heat
exchanger section. With the light shining into the heat exchanger, observe the
outside for visible light. Repeat this procedure with each heat exchanger section.
If any light is observed, replace the heat exchanger.
Instructions to Re-Install the Burner (Refer to FIGURE 17)
1. Attach the Burner Assembly - Holding the venturi tube, slide the entire
burner assembly into position. Align the supports on the left side with the
slots in the burner shield; sliding the supports into the slots. On the right, re-
attach each burner body support to the secondary air shield.
2. Attach the Secondary Air Baffles (Sizes 60-400 only) - Re-attach the
secondary air baffles as marked. Baffles may be different sizes and each
must be attached in the correct location.
Re-Install the Burner
3. Attach the Control Assembly - Carefully slide the control assembly into
position. Re-attach with the same screws. Check to be sure all wire connec-
tions are secure.
4. Attach the Gas Train - Slide the gas train so that the orifice adapter is
through the bracket. Fasten the gas train to the bracket with the locking nut.
Install the gas orifice. Re-connect the wires to the gas valve.
5. Close the access panel.
6. Reconnect the gas supply at the union outside of the cabinet. Leak test the
connection with leak detecting solution.
7. Turn on the electric and the gas. Check for proper operation.
Burner orifice usually only needs to be replaced when installing a gas conversion
kit. If ordering a replacement orifice only, give BTUH content and specific grav-
ity of gas, as well as the model and serial number of the unit. When removing or
replacing the burner orifice be careful not to damage the venturi tube and/or the
bracket.
28. Burner
Orifice
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 30
Download from Www.Somanuals.com. All Manuals Search And Download.
FIGURE 18 - Location of Controls
Venter Motor (Size 30-75
illustrated. Venter motor
is in the same location for
all models, but appear-
ance is different.)
Flame Sensor
Flame Rollout Switch
(Sizes 30-125)
Pressure Switch
- Sizes 30-125
High Temperature
Limit Control
Model UDAS has a
collar for combustion
air pipe (not illustrated)
Interlock Door
Switch - UDAS only
Fan
Motor
Gas Valve
Terminal
Board (24V)
Disconnect Switch
- UDAS only
Electrical Box - UDAS only
Remove cover to connect
supply and access
Ignitor
Transformer
disconnect switch wires .
Always replace cover.
Control Panel Assy
located on the
Control Compartment
Bottom
Transformer
Pressure Switch
(Sizes 150-400)
Sizes 30-125
Sizes 150-400
Venter Motor
Capacitor
Circuit Board
(DSI Integrated
Control Module)
Circuit Board
(DSI Integrated
Control Module)
Optional
Fan Motor
Capacitor
Fan Motor
Capacitor
DSI Integrated Control Module (circuit board) - See FIGURE 19. The module
monitors the operation of the heater including ignition. The only replaceable com-
ponent is the 3 amp Type ATC or ATO fuse. If the fuse is blown, the problem is
most likely an external overload. Correct the problem and replace the fuse.
29. Ignition
System
Do not attempt to disassemble the control module. However, each heating season
check the lead wires for insulation deterioration and good connections.
Proper operation of the direct spark ignition system requires a minimum flame
signal of 1.0 microamps as measured by a microampmeter.
For further information and check out procedure on the direct spark ignition sys-
tem, refer to Paragraph 20 and the Troubleshooting Flow Chart in Paragraph 40.
FIGURE 19 - DSI
Integrated Control Module
(Circuit Board)
Only replaceable part
is a Type ATC or ATO 3
amp fuse (Color Code
Violet), P/N 201685
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 31
Download from Www.Somanuals.com. All Manuals Search And Download.
Ignitor - Refer to FIGURE 18 and locate the ignitor. Disconnect the wire; re-
move the screw and the ignitor. Clean the ignitor assembly with an emery cloth.
29. Ignition
System
Spark gap must be maintained to 1/8". See FIGURE 20.
FIGURE 20 - Ignitor
showing required
Spark Gap
(cont’d)
1/8 inch
(3.2mm)
Ignitor
measurement
IMPORTANT: When re-assembling, the brown ground wire must remain attached
to the ignitor.
CAUTION: Due to high voltage on the spark wire and electrode,
do not touch when energized. See Hazard Levels, page 2.
Flame Sensor - Refer to FIGURE 18 and locate the flame sensor. Disconnect the
wire; remove the screw and the flame sensor. Clean with an emery cloth.
Flame Sensor
Remove dirt and grease from the motor, the fan guard, and blades. Use care when
cleaning the fan blades to prevent causing misalignment or imbalance. Check that
the hub of the fan blades is secure to the shaft.
Follow these instructions for replacement of the fan guard, fan motor and/or fan
blades.
30. Fan Motor,
Fan Blades,
and Guard
1. If the heater is installed, turn off the gas and disconnect the electric power.
2. Open the access door and disconnect the fan motor wires, capacitor wires at the
capacitor, and ground screw.
3. Remove the assembled parts (the fan guard, the motor and the fan blade).
4. Disassemble and replace whatever parts are needed and reas-
semble using whatever part(s) are being replaced and the original
parts.
FIGURE 21 - Fan Blade
Position on the Shaft
Dimension A
Size inches mm
A
1
25
30
45
60
Fan
Blade
9/16 14
1-1/2 38
2-1/8 54
2-3/8 60
2-5/16 59
2-3/8 60
2-1/8 54
1-5/8 67
Be sure the fan blade is in the proper position on the shaft; refer to
the illustration and table in FIGURE 21.
Fan
Motor
75
Position the assembly on the heater. Attach the fan guard.
Rotate the fan blade to check for adequate clearance. If adjustment
is required, loosen the mounting screws, re-position the fan guard,
and tighten the screws. Rotate the fan blade and re-check for ad-
equate clearance. Repeat this procedure until the assembly is posi-
tioned properly.
100
125
150
175
200
225,
250,
300
350
400
2
51
5. Reconnect the fan motor wires according to the wiring diagram and close the
access panel.
6. Restore power to the heater and turn on the gas. Light, following the instructions
on the lighting instruction plate. Check for proper operation.
1-7/8 48
1-3/8 35
Remove dirt and grease from the motor casing, the venter housing, and the venter
wheel. Venter motor bearings are permanently lubricated. Follow these instruc-
tions for replacement of the venter motor and wheel assembly. Keep all hardware
removed to be used in re-assembling and installing the replacement parts.
1. Turn off the gas and disconnect the electric power.
31. Venter Motor
and Wheel
Replacement Instructions
2. Open the burner/control compartment access panel.
3. Disconnect the three venter motor wires at the DSI control, capacitor wires at
the capacitor (if applicable), and ground screw (located on the control panel).
4. Sizes 30 and 45 - Disconnect the gas train and move it out of the way. Discon-
nect the gas supply at the union outside of the cabinet. At the gas valve, mark
and disconnect the wires. Carefully remove the burner orifice and orifice adapter
locking nut. Slide the orifice adapter out through the bracket on the burner push-
ing the gas train to the right. This will move the gas train out of the way.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 32
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Holding the venter motor, remove the three or four screws that attach the venter
motor mounting plate to the venter housing. Remove the motor and wheel as-
sembly from the heater.
6. Re-assemble with the replacement venter motor and wheel assembly. See FIG-
URE 22.
7. Follow the wiring diagram to connect the venter wires.
8. Sizes 30 and 45 - Reconnect the gas supply at the union outside of the cabinet.
Leak test the connection with leak detecting solution.
9. Replace the access panel. Restore power to the heater and turn on the gas. Light,
following the instructions on the lighting instruction plate. Check for proper
operation.
FIGURE 22 - Venter Wheel
Position on Shaft
Venter Motor Plate
Venter Motor Plate
Fan
Venter Wheel,
Sizes 30-75
Venter Wheel,
Sizes 100-175*
Fan
Motor Mounting Bracket
Motor Mounting
Bracket
Motor Sizes
100-400
Motor
Sizes
30-75
*Venter wheel has
different appearance
on Sizes 200-400.
Motor spacing is
the same.
5/16” (8mm) inside
5/16” (8mm) inside
The gas valve requires no field maintenance except careful removal of external
dirt accumulation and checking of wiring connections. Instructions for testing
pressure settings re in Paragraph 12.
32. Operating
Gas Valve
WARNING: The operating valve is the
prime safety shutoff. All gas supply
lines must be free of dirt or scale before
connecting to the unit to ensure positive
closure. See Hazard Levels, page 2.
Optional
Two
Stage
Gas
Single
Stage
Gas
Valve
Valve
See FIGURE 18, page 31, for location. If it is determined that
the pressure switch needs replacing, use only the factory-autho-
rized replacement part that is designed for the model and size of
heater being serviced.
33. Combustion
Air Pressure
Switch
NOTE: A unit operating above 6000 ft elevation requires a high
altitude pressure switch. See Paragraph 7.
If it is determined that the limit control needs replacing, use only
a factory-authorized replacement part that is designed for the
size of heater.
34. Limit Control
For approximate limit location, see FIGURE 18, page 31.
If it is determined that the door switch needs replacing, use only
a factory-authorized replacement part that is designed for the
heater.
35. Door Switch
- UDAS only
For approximate switch location, see FIGURE 18, page 31.
See FIGURE 18, page 31, for location. Use a voltmeter to verify
that there are 24 volts output from the transformer. If the trans-
former is not functioning, it must be replaced. Use a replacement
36.Transformer
transformer identical to the factory-installed model.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 33
Download from Www.Somanuals.com. All Manuals Search And Download.
The cause of a flame rollout switch activating must be determined. Activation of
the manually reset flame rollout switch could be caused by one or more of the
following:
37. Flame
Rollout
• Restricted or plugged
heat exchanger
• Pressurization of the
heat exchanger
• Restricted combustion air inlet or exhaust outlet
in combination with a defective pressure switch
• Building exhaust
Switch -
Sizes 30-125
only
• Electrical power interruption during operation
If a flame rollout switch trips, inspect the burner/control compartment for signs of
excessive heat and burned wiring.
If the compartment appears normal, reset by depressing the red button on the
switch. 15 to 20 minutes are required for the switch to cool sufficiently for reset-
ting. A distinct click will be felt when the switch resets. Operate the furnace. If
the flame rollout switch trips again, determine and correct the cause before reset-
ting the switch.
For location, see
FIGURE 18, page 31.
If there is damage to the control compartment, repairs must be made before
resetting the switch.
If it is determined that the flame rollout switch needs replacing, use only the fac-
tory-authorized replacement part that is designed for that size of heater.
The disconnect switch is located in the sealed electrical box inside the con-
trol compartment with the toggle on the rear of the heater.
If it is determined that the disconnect switch needs replacing, use only the
factory-authorized replacement part that is designed for the heater. Always
replace electrical box cover.
38. Disconnect
Switch -
UDAS only
Check the complete system at least once a year. Inspection should include all joints,
seams, concentric adapter box (UDAS), inlet air guard or inlet air cap (UDAS), and
the vent terminal cap. Clean openings. Replace any defective parts.
39. Vent or Vent/
Combustion
Air System
40. Troubleshooting
Trial for Ignition
Call for Heat
DSI Integrated Control Module
(Circuit Board) Trial
Troubleshooting
Is there a
spark across gap at
ignitor?
YES
NO
Flowchart
Is there
spark voltage at
control?
Check high
voltage wire
continuity.
YES
NO
Does gas
ignite?
NO
YES
NO
Is there minimum
flame current at the
flame sensor?
Is the flame
sensor corroded?
Replace
control
module.
YES
YES
Clean flame
sensor.
Is there 24V P1-2
to power control?
YES
NO
NO
Is there
minimum flame current
at the control
Is the sensor
located in flame
correctly?
Check wiring
and/or 24VAC
transformer output.
YES
Replace control
module.
YES
Replace flame
sesnsor.
module?
NO
NO
Check connections to flame
sensor and/or moisture in the
burner assembly.
Reposition
flame sensor.
YES
Is gas
flowing?
NO
Check gas pressure
and supply voltage.
If either are low,
correct and repeat
startup.
Is the ignitor
position correct in the
gas flow?
Is there
24VAC at the gas
valve?
YES
Replace gas
valve.
YES
NO
NO
Is there 24VAC
from gas valve output on
control module to
chassis?
Replace
ignition
control
module.
Check wiring and
connections to
gas valve.
Reposition
spark ignitor.
YES
NO
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 34
Download from Www.Somanuals.com. All Manuals Search And Download.
The integrated circuit board monitors the operation of the heater and includes two
LED signal lights that indicate normal operation and various abnormal conditions.
If the heater fails to operate properly, check this signal to determine the cause and/
or to eliminate certain causes. See operating sequence in Paragraph 20.
Check the Lights on
the DSI Integrated
Control Module
(Circuit Board)
Do not attempt to repair the DSI integrated control module; the only field replace-
able component is the fuse.
IMPORTANT: When using a
multimeter to troubleshoot the
24 volt circuit, place the
meter’s test leads into the 5 or 9
pin connectors located on the
ignition control. Do not
remove connectors or terminals
from the electrical components.
Doing so can result in misinter-
preted readings due to the
ignition control board’s fault
mode monitoring circuits.
Control Status - Green LED Codes
Steady ON.. Normal Operation, No call
4 Flashes .... Pressure Switch is Closed
Before Venter Motor is
Energized
Steady OFF Blown fuse, No Power, or
for heat
Fast Flash ... Normal Operation, Call for
heat
Defective Board
1 Flash........ System Lockout, Failed to
Flame Status - Yellow LED Codes
detect or sustain flame
Steady ON.. Flame is sensed
2 Flashes .... Pressure Switch Did Not
Slow Flash . Weak flame (current below
Close within 30 Seconds of
1.0 microamps ± 50%)
Venter Motor
Fast Flash ... Undesired Flame (valve
3 Flashes .... High Limit or Flame
open and no call for heat)
Rollout Switch Open
General Troubleshooting
PROBLEM PROBABLE CAUSE
REMEDY
1. No power to unit.
1. Turn on power; check supply fuses or main circuit breaker. Turn on
built-in disconnect switch (Model UDAS only); replace switch if not
operating.
Venter motor
will not start
2. No 24 volt power to integrated circuit board. 2. Turn up thermostat; check control transformer output.
3. Integrated circuit board fuse blown.
4. No power to venter motor.
5. Integrated circuit board defective.
6. Defective venter motor.
3. Correct cause. Replace fuse (type ATC or ATO, 32VDC, 3A).
4. Tighten connections at circuit board and/or motor terminals.
5. Replace intergrated circuit board.
6. Replace venter motor. See Paragraph 31.
1. Open manual valve.
1. Manual valve not open.
Burner will
not light
2. Air in the gas line.
2. Bleed gas line (initial startup only).
3. Gas pressure too high or too low.
3. Supply pressure should be 5" - 14" w.c. for natural gas or 11" - 14" w.c.
for propane gas.
4. No Spark:
4.
a) Loose wire connections.
b) Transformer failure.
a) Be certain all wire connections are solid.
b) Be sure 24 volts is available.
c) Incorrect spark gap.
c) Maintain spark gap at 1/8".
d) Spark cable shorted to ground.
e) Spark electrode shorted to ground.
f) Burner not grounded.
g) Circuit board not grounded.
h.) Unit not properly grounded.
d) Replace worn or grounded spark cable.
e) Replace if ceramic spark electrode is cracked or grounded.
f) Make certain integrated circuit board is grounded to ignitor.
g) Make certain integrated circuit board is grounded to furnace chassis.
h.) Make certain unit is properly field grounded to earth ground and
properly phased (L1 to hot lead L2 to neutral).
i) Correct cause. Replace fuse (type ATC or ATO, 32VDC, 3A).
j) If 24 volt is available to the integrated circuit board and all other causes
have been eliminated, replace board.
i) Integrated circuit board fuse blown.
j.) Faulty intergrated circuit board.
5. Lockout device interrupting control circuit 5. Reset lockout by interrupting control at the thermostat or main power.
by above causes.
6. Interlock door switch open (UDAS only).
7. Combustion air proving switch
not closing.
6. Close access door or replace switch.
7.
a) Make sure unit is properly vented.
b) Remove obstructions from vent.
c) Replace faulty tubing to pressure switch.
8. Replace combustion air proving switch.
9.
8. Faulty combustion air proving switch.
9. Main valve not operating.
a) Defective valve.
a) If 24 volt is measured at the valve connections and valve remains
closed, replace valve.
b) Loose wire connections
b) Check and tighten all wiring connections.
Form RZ-NA I-UDA, Mfg #195673 Rev 5, Page 35
Download from Www.Somanuals.com. All Manuals Search And Download.
40. Troubleshooting (cont’d)
PROBLEM (cont’d)
Burner will not light
(cont’d)
PROBABLE CAUSE (cont’d)
10. Integrated circuit board does not power
main valve.
REMEDY (cont’d)
10.
a) Loose wire connections.
b) Flame sensor grounded.
a) Check and tighten all wiring connections.
b) Be certain flame sensor lead is not grounded or insulation or
ceramic is not cracked. Replace as required.
c) Supply pressure should be 5" - 14" w.c. for natural gas or 11" - 14"
w.c. for propane gas.
c) Incorrect gas pressure.
d) Cracked ceramic at sensor.
d) Replace sensor.
1. Gas pressure too high or too low.
1. Supply pressure should be 5" - 14" w.c. for natural gas or 11" - 14"
w.c. for propane gas.
Burner cycle on and off
2. Burner not grounded
3. Circuit board not grounded.
4. Faulty integrated circuit board
2. Make certain integrated circuit board is grounded to ignitor.
3. Make certain integrated circuit board is grounded to furnace chassis.
4. If 24 volt is available to the integrated circuit board and all other
causes have been eliminated, replace board.
5.
5. Combustion air proving switch
not closing.
a) Make sure unit is properly vented.
b) Remove obstructions from vent.
c) Replace faulty tubing to pressure switch.
6. Replace combustion air proving switch.
7. Be certain flame sensor lead is not grounded or insulation or ceramic
is not cracked. Replace as required.
6. Faulty combustion air proving switch.
7. Flame sensor grounded.
8. Cracked ceramic at sensor.
9. Incorrect polarity.
1. Incorrect valve outlet pressure or orifice.
2. Cycling on limit control.
8. Replace sensor.
9. Reverse line volt leads to integrated circuit board.
1. Check valve outlet pressure. See Rating plate for manifold pressure.
2. Check air throughput.
No heat (Heater
Operating)
3. Improper thermostat location or adjustment. 3. See thermostat manufacturer’s instructions.
1. Circuit open.
2. Defective integrated circuit board.
1. Check wiring and connections.
2. Replace board.
Fan or venter motor will
not run
3. Defective motor or starter.
3. Replace motor or starter.
1. Motor overload device cycling on and off. 1. Check motor load against motor rating plate. Replace motor if
needed.
Fan or venter motor
turns on and off while
burner is operating
Fan or venter motor cuts
out on overload
1. Low or high voltage supply.
2. Defective motor.
1. Correct electric supply.
2. Replace motor.
3. Poor air flow.
4. Defective bearing or lubrication.
3. Clean motor, fan, fan guard, filter, and coils.
4. Lubricate bearings (motor permitting) or replace motor.
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:
Contact the Installer
FIRST:
Name __________________________________________________________
Address_________________________________________________________
__________________________________________________________
__________________________________________________________
Phone _____________________________________
SECOND:
THIRD:
Contact the nearest distributor (See Yellow Pages). If no listing,
contact Authorized Factory Representative, 1-800-695-1901 (Press 1).
Contact
REZNOR®/ Thomas & Betts Corporation
150 McKinley Avenue
Mercer, PA 16137
Phone: (724) 662-4400
Date of
Model No. ______________Unit Serial No._____________________________ Installation _______________
©2003 Thomas & Betts Corporation, All rights reserved.
Printed in the U.S.A.
MANUFACTURER OF HEATING, COOLING, AND VENTILATING SYSTEMS
Trademark Note: Reznor®, TCORE2® , and
are trademarks of Thomas & Betts.
Form RZ-NA I-UDA, P/N 195673 Rev 5, Page 36
1/03 YL Form RZ-NA I-UDA (Version .5)
Download from Www.Somanuals.com. All Manuals Search And Download.
|