Thomas Betts Appliance Trim Kit RZ NA 441 OMS User Manual

INDOOR OR OUTDOOR, GAS,  
DIRECT-FIRED, MAKEUP AIR/  
HEATING SYSTEMS  
(Specifications subject to change without notice.)  
C E R T I F I E D  
Operation/Maintenance/Service  
Form RZ-NA 441-OMS  
Applies to:  
Model Series DV  
TABLE OF CONTENTS  
Page  
Page  
•Manifold Arrangements ................. 8  
•Gas Pressure Switches.................... 8  
12. Outside Air Ambient Cutoff ............ 8  
Page  
8. Temperature Limit Safety Controls ... 5  
•Manual Reset Limit Control ........... 5  
•Emergency Cut Off Limit Control .. 6  
9. Air Pressure Switches ........................ 6  
•Low Air Flow Switch ...................... 6  
•High Air Flow Switch ...................... 6  
MAINTENANCE  
SECTION ...................... 2-4  
Configuration ................................. 2  
Maintenance Schedule ................... 2  
1A. Blower Bearings .............................. 3  
1B. Blower Belts ................................... 3  
2. Filters ................................................. 3  
3. Manifold Gas Pressure ...................... 3  
4. Air Pressure ....................................... 4  
5. Circuit Indicator Board (check lights) 4  
13. Door Switch..................................... 9  
14. Inlet Air Controls ............................ 9  
•Air Flow Dampers ........................... 9  
•Damper Motor ................................. 9  
•Potentiometer .................................. 9  
•Pressure Null Switch ....................... 9  
•Photohelic Pressure Switch ........... 10  
15. Dirty Filter Switch ......................... 10  
16. Photoelectric Smoke Detector ....... 10  
17. Firestat ........................................... 10  
18. Freezestat ....................................... 10  
19. Troubleshooting ............................. 11  
•Bypass Damper (Optional) Air  
Flow Switches ................................ 6  
10. Ignition System................................ 6  
11. Gas Train Including Direct-Fired  
Burner, Gas Control Systems,  
6. Main Burner and Pilot Assembly ...... 4  
Manifold Arrangements and Gas  
Pressure Switches ............................. 7  
OPERATION/SERVICE  
•Direct-Fired Burner ........................ 7  
•Makeup Air Gas Control Systems .. 7  
SECTION ................... 5-15  
•Electronic Modulation Gas Control  
Options AG30, AG31, AG32,  
AG33, AG35, AG36 ...................... 7  
Controls - Location ....................... 5  
Chart 1 - General Troubleshooting  
Guide (Check the diagnostic lights on  
the circuit board)  
7. Electronic Circuit Board with  
Diagnostic Lights.............................. 5  
•Electronic Modulation Gas Control  
Option AG37 ................................. 7  
Index ................................................... 12  
References: Installation Manual, Form RZ 441  
Replacement Parts Manual, Form RZ 741  
FOR YOUR SAFETY  
KEEP THIS BOOKLET  
FOR MAINTENANCE AND  
SERVICE REFERENCE.  
WARNING: The use and storage of gasoline or  
other flammable vapors and liquids in the vicinity  
of this appliance is hazardous.  
If you smell gas:  
1. Open windows.  
Operating/Maintenance/Service  
Instructions  
The information in this manual applies to Model Series DV, di-  
rect-fired heating/makeup air systems. As with any gas burning  
equipment, regular maintenance procedures are required to en-  
sure continued safety, reliability and efficiency of the installa-  
tion.  
2. Don't touch electrical switches.  
3. Extinguish any open flame.  
4. Immediately call your gas supplier.  
WARNING: Improper installation, adjustment,  
alteration, service, or maintenance can cause  
property damage, injury or death. Read the  
installation, operation, and maintenance  
instructions thoroughly before installing or  
servicing this equipment.  
If service is required, this system should be serviced only by a  
qualified service person. Service information in this booklet is  
intended as a guideline for a qualified gas-fired equipment ser-  
vice person.  
Mfg No. 161442 Page 1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
R
1. Drive Components  
excessive motor and blower bearing wear. If adjustment is required,  
adjust belt tension by means of the adjusting screw on the motor base  
until the belt can be depressed 1/2" to 3/4" (Figure 2). Tighten the lock  
nut on the adjusting screw. Be sure the belt is aligned in the pulleys.  
The blower, motor and drive components are located in the blower  
cabinet at the top of the system. Systems with horizontal discharge  
have a cabinet with eight removable door panels. Systems with vertical  
discharge have a cabinet with six removable door panels. Remove the  
panels required to access the components being serviced.  
1A. Blower Bearings  
All blowers are Class I with pillow block bearings. Clean the fitting and  
add type NLG-2 or -2 standard grade grease. Add grease with a handgun  
until a slight bead of grease forms at the seal. Be careful not to unseat  
the seal by over lubricating.  
Figure 2 -  
Belt  
Tension  
3/4” (19mm)  
NOTE: If unusual environmental conditions exist (temperatures below  
32oF or above 200oF; moisture; or contaminants) more frequent lubri-  
cation is required.  
CAUTION: If the blower is unused for more than  
three months, the bearings should be purged with  
new grease prior to startup.  
R
E
2. Filters  
If the system includes filters, check the filters quarterly. Filters could  
be either in the optional inlet base or in an optional filter cabinet.  
If the filters are in the perimeter of the inlet base; they are two-inch  
permanent filters. Remove and clean the filters as needed.  
Recommended Bearing Lubrication Schedule in Months  
Bearing Bore Diameter (Inches)  
If the filters are in a filter cabinet (the filter cabinet is always between  
the inlet base and the burner/control section), remove the filter cabinet  
door panels to access the V-bank filter rack. Filters may be either 2"  
disposable, 1" or 2" permanent, or 1" or 2" disposable pleated. Clean or  
replace as needed.  
1/2  
>1 to  
>1-1/2 to  
RPM  
to 500  
501 - 1000  
1001 - 1500  
1501 - 2000  
to 1  
1-1/2  
1-15/16  
6
6
5
5
6
6
5
4
6
6
5
5
Sizes and Quantity of Filters in the Filter Cabinet  
( same for all types of filters)  
Size  
109  
112  
4
115  
-
118  
-
122  
16  
-
125  
16  
-
1B. Blower Belts  
Check belts for proper tension and wear. Adjust belt tension as needed.  
Replace worn belts.  
Proper belt tension is important to the long life of the belt and motor. A  
loose belt will cause wear and slippage. Too much tension will cause  
16" x 16"  
16" x 20"  
16" x 25"  
4
4
-
4
6
6
-
6
6
8
8
3. Manifold Gas Pressure  
S
Semiannually, check the gas pressure to the burner and to the pilot. Measure both manifold pressure and pilot supply pressure with the blower in  
operation. Refer to Figure 3 for pressure tap locations. Verify against pressures listed on the rating plate.  
Figure 3 - Location of  
pressure taps for  
measuring burner and  
pilot gas pressure.  
Measure with blower  
operating.  
Pilot  
Regulator  
Pilot Solenoid Valve  
Pilot Manifold  
Pilot Pressure Tap  
Manifold Pressure Tap  
Regulator  
Valve  
Valve  
Gas  
Supply  
Inlet Pressure Tap  
Page 3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 5 - Burner  
End Plate showing  
Hot Surface Ignitor  
S
4. Air Pressure  
Profile plate sensing tubes should be checked quarterly and cleaned no  
less than semiannually. If the sensing tubes become even partially  
blocked, false pressure readings may be relayed. To clean, remove the  
screened end caps. Clean the screens and the tubes, if necessary. Re-  
place the cleaned end caps. Check the pressure differential across the  
profile plate using a slope gauge. Air pressure differential should be  
between -.5" and -.7" w.c.  
Burner End Plate  
Flame Sensor  
Ignitor  
To attach the slope gauge, open the control compartment door panel.  
Just below the junction box, locate the tubing connections. Remove the  
cap at each connection and attach the slope gauge using two field-  
supplied 1/4" x 1/8" female NPT barbed tubing connections. For in-  
structions on measuring air pressure, see Service Section, Paragraph 9.  
5. Circuit Indicator Board (check  
lights)  
The circuit indicator board is located in the control compartment elec-  
trical box (See Figure 7). Check operation of all indicator lights by  
switching lights that are not lit with one that is currently lit. Replace all  
burned out indicator bulbs (P/N 125189).  
R
If air pressure does not unplug burner orifices or pilot tube, drill  
burner orifices with a Size #50 drill and/or pilot tube with a Size #55  
drill.  
WARNING: Do not enlarge burner ports or  
performance may be drastically affected.  
Inspect the upstream and downstream sides of the mixing plates.  
Remove any accumulation of scale or foreign material with a wire  
brush. If any mixing plate fasteners are loose or missing, tighten or  
replace. Always use zinc plated or stainless fasteners.  
Row of Bulbs  
Figure 4 - Circuit  
Indicator Board,  
P/N 151263  
If any cracks are present, replace that mixing plate. Because of the  
effect of flame temperature on the metal, fasteners may be difficult  
to remove. Be careful not to damage the gaskets that go between the  
mixing plates and the burner body. The gaskets are designed to  
overlap approximately 1/16" for tight air seal.  
Check bulbs not  
lit with other  
bulbs; replace  
any burned out  
bulbs  
5) Follow Steps in reverse order to re-install the pilot assembly. Close  
all panels and check for proper operation.  
Figure 6 - Illustration of the first Burner Section  
6. Main Burner and Pilot Assembly  
S
Mixing  
Plate  
For the most part, the burner and pilot are self cleaning. However, if the  
application is extremely dirty or dusty, cleaning of the burner and pilot  
may be necessary. Inspect the burner annually. Follow these instruc-  
tions. If it is necessary to replace any parts, use only factory-autho-  
rized replacements.  
1) Turn off the gas and power supply to the system.  
2) Remove the door panels in the burner/control cabinet (four or six  
depending on whether or not the system has return air). Locate the  
pilot.  
Full length of the  
burner is made up of a  
series of 6" or 12"  
burner sections in a  
linear or oval  
configuration  
3) Disconnect the two ignition wires (male and female quick connec-  
tions) and disconnect the flame sensor lead at the burner. Remove  
the set screw located in the ignitor tube (set screw holds the brass  
bushing in place). Carefully remove the brass bushing and the igni-  
tor.  
Check the hot surface ignitor for cracks or unusual deterioration.  
Check the flame rod for integrity. Replace the flame rod (P/N 131188)  
and/or the hot surface ignitor (P/N 121865) if not in good condition.  
4) Clean the burner and pilot by back-flushing, using high pressure air  
(40-80 lbs). Continue until dust particles are completely expelled  
from both the upstream and downstream sides of the burner.  
Burner  
WARNING: Burner profile plates are factory set  
to match CFM requirements.  
Do not adjust profile plates without contacting your  
Sales Representative for technical assistance.  
CAUTION: Wear eye protection while pressure  
cleaning and drilling.  
Page 4  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation/Service Section  
WARNING: Service work on this system  
should only be done by a qualified gas ser-  
vice person. The service information and  
the troubleshooting guides are intended as  
an aid to a qualified service person.  
Controls - Location, Operation, and Service  
To service this system, it is necessary to understand the normal operation  
of the controls and the function of the diagnostic circuit board. Refer to the  
electrical box drawing in Figure 7 and to the individual illustrations to  
identify and locate each of the controls. The wiring diagrams for this unit  
are located in the main electrical box.  
Figure 7 - Control Locations  
Time Delay  
Control  
Relays  
Outside Air Cutoff  
(high ambient limit control)  
Relay  
24-volt Terminals  
Return  
Air  
Damper  
Motor  
Bypass  
Damper  
Motor  
Ignition  
Module  
Motor  
Starter  
Maxitrol Amplifier  
or Signal Conditioner  
Circuit  
Board  
Service  
Switches  
Low  
High  
Optional  
Dirty Filter  
Pressure Switch  
Standard Pressure  
Switches  
Relay for  
Optional 2-Speed  
Starter  
Relay  
Optional Bypass Damper  
Pressure Switches  
Line Voltage  
Terminals  
NOTE: Wiring diagrams for the unit are located on the inside of the electrical box door.  
8. Temperature Limit Safety Controls  
7. Electronic Circuit Board with Diagnostic  
Lights  
Location: 1) Manual Reset Limit Switch is mounted on a 2x4  
electrical box located in the blower section. To access the manual  
reset, remove the blower section access panel to the left of the  
discharge (left when facing the discharge); 2) Emergency Cutoff  
Limit Control is in the burner/control cabinet just above the electri-  
cal box.  
Location: Control Compartment Electrical Box (See Figure 7)  
Function: The diagnostic lights on the circuit board are designed to assist  
in troubleshooting. When the system is operating properly, the lights on  
the circuit board are lit. If the system fails to operate properly, all lights on  
the circuit board up to that one that represents the component or system  
that has failed will be lit. For more detailed information, refer to the Trouble-  
shooting Guide in Paragraph 19.  
• Manual Reset Limit Control - Blower  
Cabinet  
Figure 9 -  
Manual Reset  
Limit  
Function: The  
manual reset limit  
is a temperature  
Figure 8 -  
Diagnostic  
Circuit  
activated safety  
control. Re-start  
of the system can  
be done only after  
the limit control is  
Capillary tubing is  
Column of 13  
in a holder that  
extends into the  
indicator  
bulbs; always  
replace  
Board,  
P/N 151263  
cooled and the reset button is depressed.  
burned out  
bulbs, P/N  
125189.  
CAUTION: If the manual reset limit activates,  
find and correct the cause before re-starting the  
system.  
Service: Failure of the manual reset limit requires replacement of  
the control.  
Page 5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Attach a slope gauge (0 to 1.0" scale) to the tubing connections in the  
control compartment. The two connections are located below the elec-  
trical control box. Remove the caps on the 1/8" NPT test connections  
and attach the slope gauge. (The recommended method for attaching the  
slope gauge is to use field-supplied 1/8" female NPT x 1/4" O.D. barbed  
hose connections.)  
8. Temperature Limit Safety Controls (cont'd)  
• Emergency Cut Off Limit Control  
Function: The emergency cut off is a fus-  
ible link high temperature limit which pro-  
vides one-time redundant protection  
Figure 11 - ECO  
Limit Control,  
against overheating. If the temperature  
P/N 82414  
A) If the system includes an optional discharge damper, before measur-  
ing burner differential air pressure, check to be sure that the damper  
is fully open.  
sensitive limit control malfunctions, the  
electrically activated emergency cutoff will  
shutdown the system.  
B) With the blower operating, the pressure differential on the slope  
gauge should read between -.5" and -.7" w.c. If the slope gauge  
reading is within those limits, no adjustments are necessary.  
Service: If this limit activates, the manual  
limit control has failed and must be re-  
placed. The cause for activating the emer-  
Setting 305oF  
If the slope gauge reading is not within the setpoint limits of the air  
flow switches (.2" to .9" w.c.), and the system is operating, replace  
the air pressure switch(es).  
gency cut off limit control must be found and corrected before re-  
starting the system.  
9. Air Pressure Switches  
Location: Control Compartment Electrical Box (See Figure 7.)  
If the slope gauge reading is not between -.5" and -.7" w.c., but  
within the setpoint limits, clean the sensing tubes (Follow the in-  
structions in Maintenance Section, Paragraph 4).  
Depending on the options selected, there are two or four switches.  
C) When air pressure is within the proper range, turn the disconnect  
switch OFF. Disconnect the manometer and the slope gauge. Re-  
place the caps removed to connect the slope gauge.  
Figure 12 - Air  
Pressure Switch  
Service: If the pressure check determines that an air flow switch is not  
functioning properly, the switch cannot be serviced and must be re-  
placed with an identical replacement. Low air pressure switch is P/N  
86986; high air pressure switch is P/N 86987; bypass damper switches,  
P/N 87249 (normally closed, set to open at .5" w.c.) or P/N 87250  
(normally open, set to close at .65" w.c.).  
• Low Air Flow Switch  
10. Ignition System  
Function: The low air flow switch is a velocity pressure switch that  
monitors air flow across the burner. Until the air flow attains adequate  
volume for combustion, the switch remains open. When the switch  
recognizes adequate air volume, it closes, permitting both the pilot and  
burner to operate. Low pressure switch is normally open; it closes on  
pressure rise at .2" w.c. Do not alter or adjust setting.  
Location: Ignition Controller Module in the Control Compartment  
Electrical Box (See Figures 7 and 13.); Ignitor and Flame Sensor on the  
Burner (See Figure 14.)  
Figure 13 - Ignition Control  
Module in the Electrical  
Compartment, P/N 157953  
Figure 14 - Ignitor, P/N  
121865, and Flame  
Sensor, P/N 134706, on  
the Burner  
• High Air Flow Switch  
Function: The high air flow switch is a velocity pressure switch that  
monitors air flow across the burner. If the high air flow switch senses air  
velocity above the prescribed limit, it will shutdown gas flow to the  
burner. High pressure switch is normally closed; it opens when pres-  
sure rises above .9" w.c. Do not alter or adjust setting.  
Sensor  
• Bypass Damper Air Flow Switches (systems  
with Air Control Options AR19, AR20, AR22, AR23,  
AR32, AR33, AR34, AR36, or AR37)  
Function: With a bypass damper, the volume of outside air supplied  
to the building is adjusted by a manually set potentiometer (Option  
AR19 and AR22) or automatically by a pressure null switch (Option  
AR20 or AR23), a photohelic pressure switch (Option AR36 or AR37),  
or a field-supplied computer signal (Option AR33 or AR34). With  
Options AR19, AR20, AR33, and AR36 the supply air is varied by  
adjusting the position of a damper at the blower discharge. With Op-  
tions AR22, AR23, AR34, and AR37, a return air damper is adjusted to  
vary the volume of return air. The unit is arranged so that a fixed amount  
(20%) of the rated volume flows over the burner at a constant velocity.  
The remainder (80%) of the rated air volume flows either through a  
balancing bypass damper or a combination of bypass and return air  
dampers. As the supply air volume is varied by the return air or dis-  
charge damper, the balancing damper is adjusted to maintain the re-  
quired air velocity over the burner. Adjustment of the bypass damper is  
controlled by the bypass damper pressure switches. One pressure  
switch is normally closed with a setting of .5" w.c.; the other is nor-  
mally open with a setting of .65" w.c. balancing bypass damper.  
Sensing Pressure Check: (requires a slope gauge, several feet of  
Ignitor  
Hot Surface Ignition System with Prepurge  
Time Delay and Flame Sensor with 100%  
Lockout  
Function: The ignition system including the controller, the hot surface  
ignitor, and the flame sensor function to ignite and prove the pilot  
flame. When there is a call for heat, the modular ignition controller is  
energized. When the controller reads 1.4 amps going to the hot surface  
ignitor, it opens the pilot valve for a 15-second trial for ignition. After  
the pilot flame rod senses pilot flame, the main gas valve is energized. If  
the pilot flame rod does not sense a pilot flame, the controller shuts  
down the pilot valve for a 10-second interpurge and then opens it again  
for a second ignition trial. If pilot flame is not proven on the second  
trial, the ignition controller locks out and must be manually reset by an  
interruption of the main circuit (disconnect switch).  
Service: The modular ignition controller does an internal self-check  
each time that it is energized and will lockout if not found to be func-  
1/4" O.D. tubing and two 1/4" O.D. barbed tees.)  
Page 6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For troubleshooting guides and further explanation of Maxitrol Series 14 and  
44 electronic modulation gas control systems, refer to the Maxitrol literature  
in the owner's envelope.  
tioning properly. If the ignition controller locks out and there is no  
other cause, the controller module must be replaced.  
The Option AG30, AG31, AG32 and AG35 electronic modulation systems  
are comprised of Maxitrol Series 14 controls. Options AG30 and AG31  
systems electronically maintain a constant discharge air temperature in the  
range of 55-90°F (55-75°F for C.G.A.). Option AG31 includes an overriding  
thermostat. Option AG32 system will maintain a constant discharge air  
temperature in the range of 80-130°F. Option AG35 maintains a discharge  
temperature range of 120-160°F.  
11. Gas Train Including Direct-Fired  
Burner, Gas Control Systems,  
Manifold Arrange-ments, and Gas  
Pressure Switches  
Direct-Fired Burner  
Function: The design of the direct-fired burner and the con-  
trolled velocity of air at the burner ensure complete combustion  
through the full range of burner sizes and gas inputs as determined  
by the gas control system. The velocity of air is controlled by the  
profile plates and monitored by a standard low and high air pres-  
sure switch.  
Figure 15 - Components of the Gas Control System (Maxitrol  
Series 14) used in Gas Control Options AG30, AG31, AG32,  
andAG35  
Mixing  
Tube  
Amplifier,  
P/N 148590  
Service: Refer to Paragraph 6 in the Maintenance Section for  
instructions on burner maintenance.  
WARNING: Burner profile plates are factory  
set to match CFM requirements. Do not adjust  
profile plates without contacting your Sales  
Representative for technical assistance.  
Temperature  
Selector  
Temperature  
Sensor  
Option AG33 electronic modulation system is comprised of Maxitrol Series  
44 controls. The low limit (20-60°F) and the high limit (60-140°F) for con-  
trol of discharge air temperature are set at the amplifier located in the control  
compartment. The space temperature is set at the remote selectrastat (55-  
90°F range) located in the space. When the temperature is below the space  
temperature setpoint, the control system operates the burner to automati-  
cally adjust the discharge air temperature within the maximum and minimum  
limits set on the amplifier.  
Makeup Air Gas Control Systems  
Electronic Modulation Gas Control  
Options AG30, AG31, AG32, AG33, AG35,  
AG36  
Refer to the wiring diagrams in the main electrical box to deter-  
mine which controls are on the system being serviced. NOTE: All  
field-supplied control wiring for Maxitrol controls must not be  
run inside conduit with line voltage wiring. To avoid any potential  
electrical interference, all field-supplied wiring for Maxitrol con-  
trols should be shielded wiring and must be grounded at the unit  
only.  
Figure 16 - Components of the Gas Control System (Maxitrol  
Series 44) used in Gas Control Option AG33  
Temperature  
Sensor,  
P/N 119617  
Function: These makeup air gas control systems provide heated  
makeup air at a temperature controlled by a discharge air sensor.  
Each system is equipped with electronic modulation controls  
that modulate burner flame from 1/25th of full fire input to full  
fire.  
Amplifier,  
P/N 157915  
Mixing Tube,  
P/N 90323  
Temperature  
Selector, P/N 86990  
Option AG36 is a special application gas train that is designed for controlling  
the environment of a paint booth operation. The system includes a Maxitrol  
A1494 amplifier, discharge air temperature sensor, dual remote discharge air  
temperature selector (drying selector 80-140°F and a spray selector 60-  
90°F), and two switches to control the operation of the modulating gas valve.  
The electronic modulating-type gas controls act in response to  
discharge and/or room air temperature sensors to change the gas  
flow rate to the burner, thus lengthening or shortening the flame.  
The BTU output is varied (modulated) to maintain the required  
discharge air temperature.  
These modulating gas control options are electronic because in all  
cases the gas valve acts to adjust the flow of the gas to the main  
burner in response to DC volts emanating from an amplifier.  
When the DC voltage is between 0 and 5 volts, the main valve seat  
is closed. Low fire flow is accomplished through a mechanical  
bypass. The low fire flow rate is set at the factory and should not  
need adjustment. However, if adjustment is necessary, refer to  
the Maxitrol literature that is included in the heater owner's enve-  
lope.  
Figure 17 - Components of the Gas Control System used in  
Option AG36 designed specifically for paint booths - controls  
are mounted on a remote console  
Selector,  
Amplifier,  
P/N  
P/N 133229  
133230  
All of the electronic modulating gas control burner systems in-  
clude low fire start. On an initial call for heat, the main burner  
ignites at its lowest input. During mild weather, the burner may  
then cycle off. Such full shutdown can be dictated by the outdoor  
ambient cutoff control. As the outside air temperature climbs  
above the setpoint of the outdoor ambient control, the burner  
control circuit is de-energized. When moderately cold outside air  
temperatures exist, the burner will modulate between low flame  
and high flame. Low fire start and the outdoor ambient control  
prevent the makeup air system from heating already warm air and  
providing "too much" heat to the building.  
Electronic Modulation  
Gas Control Option  
AG37  
Function: Control Option AG37  
does not have a duct sensor or ampli-  
fier. Instead, a Maxitrol A200 signal  
conditioner is activated by a cus-  
tomer-supplied input signal (either 4-  
20 milliamps or 0-10 volt) to control  
the modulation of the gas valve.  
Figure 18 - Maxitrol A200  
Signal Conditioner,  
P/N 134170, used in Gas  
Control Option AG37  
Page 7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11. Gas Train Including Direct-Fired Burner, Gas Control Systems, and Manifold  
Arrangements (cont'd)  
Service - All Maxitrol Controls: Check all electrical connec-  
tions. A qualified service person should refer to the Maxitrol Trouble-  
Figure 19 - Gas Manifold Control Components  
shooting Guides for assistance in identifying problems and determining  
the correct solution. None of the Maxitrol controls have field replace-  
Solenoid Valve  
able parts. All components must be replaced with identical replacement  
parts.  
Modulating/  
Regulating  
Valve  
Manifold Arrangements  
Description: The manifold is the gas train from the gas supply con-  
nection to the burner. The manifold selection ordered determines the  
manifold arrangement including all of the gas train components except  
the main control valve. Manifold arrangements are available for varying  
BTUH ranges and gas controls and include versions that meet FM or  
IRI requirements.  
Pilot Valve  
In addition to the Maxitrol valve and two solenoid valves, all manifold  
arrangements include main gas and pilot gas shut-off cocks, a pilot  
regulator, and a pilot solenoid valve.  
Pilot Regulator  
The table below lists the pressure drops through the various types of  
manifolds by option designation (BM). To determine the required mini-  
mum supply pressure for natural gas, add 5.0" w.c. to the natural gas  
manifold pressure drop. For propane gas, add 2.0" w.c.  
Manifold Pressure Drops (“ w.c.)  
Manifold Opt BM62  
BM63  
3/4"  
Nat  
BM64  
1"  
BM65  
1-1/4"  
BM67  
1-1/4"  
BM68  
2"  
BM53  
1-1/4"  
Nat  
.22  
.89  
BM66  
2"  
Manifold Size  
MBH  
250  
500  
750  
1"  
Nat  
.56  
2.23  
5.02  
--  
Pro  
.21  
.85  
1.91  
--  
Pro  
.25  
Nat  
.43  
Pro  
.17  
.66  
Nat  
.22  
.89  
Pro  
.09  
.34  
Nat  
.19  
.76  
Pro  
.07  
.29  
.65  
Nat  
.07  
.27  
Pro  
.03  
.10  
.23  
.41  
.65  
.93  
Pro  
.09  
.34  
.77  
Nat  
Pro  
.03  
.10  
.23  
.41  
.65  
.93  
.66  
2.65  
5.96  
--  
.07  
.27  
.61  
1.01 1.74  
2.27 3.91 1.49 2.01  
.77  
1.71  
.61  
2.01  
1000  
--  
--  
--  
--  
--  
--  
--  
--  
--  
6.95 2.65 3.58  
1.36  
2.13  
3.07  
3.04 1.16  
4.76 1.81  
6.85 2.61  
9.32 3.55  
1.09  
1.70  
2.44  
3.58 1.36 1.09  
5.59 2.13 1.70  
8.05 3.07 2.44  
1250  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
5.59  
8.05  
1500  
--  
1750  
--  
10.96 4.17  
3.33 1.27 10.96 4.17 3.33 1.27  
4.34 1.66 14.31 5.45 4.34 1.66  
5.50 2.09 18.11 6.90 5.50 2.09  
6.79 2.59 22.36 8.52 6.79 2.59  
8.21 3.13  
9.77 3.72  
2000  
--  
14.31 5.45 12.18 4.64  
18.11 6.90 15.41 5.87  
22.36 8.52 19.02 7.25  
--  
--  
2250  
--  
2500  
--  
2750  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
--  
8.21 3.13  
9.77 3.72  
3000  
--  
Gas Pressure Switches  
12. Outside Air Cutoff Control (Option BN2;  
required on C.G.A.-certified units)  
Location: The control is in the electrical  
Figure 20 - Gas  
Pressure Switches  
If the gas train includes either or both  
high and low gas pressure switches,  
the switches monitor gas pressure  
downstream from the safety valves.  
Figure 21 -  
Outside Air  
Cutoff Control  
box (See Figure 7.); the sensor is in the air  
inlet.  
If the gas pressure in a system equipped  
with a high gas pressure switch (Op-  
tion BP2) exceeds the setpoint, the  
switch will open the electrical circuit  
to the burner, stopping all gas flow.  
The high gas pressure switch is a manu-  
ally reset device.  
Function: After sensing pilot flame, the  
burner ignites at its lowest input rate. The  
"amount of heat" required to reach the de-  
sired discharge temperature also depends on  
the temperature of the incoming outside air.  
The outside air control is factory set at 60°F  
(adjustable 25-250°F). The burner reacts  
differently depending on the entering air tem-  
perature and the setting on the outside air  
control. The burner --  
Low, P/N 93850  
(automatic)  
A low gas pressure switch (Option  
BP3) will shutoff the gas flow if the  
gas pressure drops below the setpoint  
of the low pressure switch. The low  
gas pressure switch will automatically  
reset when the gas pressure rises above  
the setpoint.  
• may not ignite (pilot valve will not open);  
If the actual temperature of the outside  
air is above the setpoint on the outside air control, the burner will  
not ignite.  
• may modulate to satisfy discharge setting;  
• may shutdown; or  
High, P/N 93849  
(manual reset)  
(NOTE: Both high and low gas pres-  
sure switches incorporate a vent limiting device and do not require  
venting to the outdoors when used in an application installed indoors.)  
Page 8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Burner shutdown or modulating operation will depend on the tem-  
perature rise between the outside air and the discharge air setting.  
• may remain on continuous low fire.  
changes the position of the damper to provide either 100% outside air  
or 20% outside/80% return air. Control is from a SPDT toggle switch  
mounted on a 4x4 box (or if ordered, the switch is mounted on a remote  
console).  
zOption AR33 - 100% outside makeup air with variable supply air  
volume (CFM). The discharge damper controlling the variable air sup-  
ply is automatically controlled by a 0-10 VCD or 4-20 milliamp signal.  
In response to changes in the discharge damper setting, the bypass  
damper balances the volume of air so that the required fixed amount of  
air volume flows over the burner.  
If the outside air control is set too high, the burner will continuously  
burn on low fire as long as the control switch is set to "winter".  
When the outside air control is set properly for the climate, the system  
blower will continue to provide the required makeup air (ventilation) at  
the ambient outdoor temperature (burner not operating) even when the  
control switch is set to "winter".  
Service: If the control does not function properly, replace it with an  
identical switch.  
zOption AR34 - a combination of outside makeup air and bypass  
return air including modulating return air and bypass air dampers. The  
volume of outside air is regulated by a 0-10 VCD or 4-20 milliamp  
signal.  
13. Door Switch (Option BX1; required on  
C.G.A.-certified units)  
zOption AR35 - a constant supply of 100% makeup air to the unit but  
including a two-position inlet shutoff damper that closes the dampers  
when the system is not operating. The damper attaches to the duct  
flange of the optional inlet base (used only with the optional inlet base  
that has three closed sides and a duct connection for outside air).  
zOption AR36 - 100% outside makeup air with variable supply air  
volume (CFM). The discharge damper controlling the variable air sup-  
ply is automatically controlled by a remotely located photohelic pres-  
sure sensor. In response to changes in the discharge damper setting, the  
bypass damper balances the volume of air so that the required fixed  
amount of air volume flows over the burner.  
Location: The control is installed on an over-  
head door opening to control the operation of  
the heater to coincide with the opening and clos-  
ing of the door.  
Figure 22 -  
Door Switch,  
P/N 124253  
Function: The function of the switch is to ener-  
gize and interlock the heating unit when an out-  
side overhead door reaches approximately 80%  
of full open travel. The switch will de-energize  
the furnace when the overhead door closes ap-  
proximately 20%. The complete switch includes  
a limit switch electrically wired to the heater and a roller yoke for  
mechanical activation by a field-supplied trigger on the overhead door.  
zOption AR37 - a combination of outside makeup air and bypass  
return air including modulating return air and bypass air dampers. The  
volume of outside air is regulated by a remotely located photohelic  
pressure sensor.  
14. Inlet Air Controls  
WARNING: Burner profile plates are factory set  
to match CFM requirements.  
Do not adjust profile plates without contacting your  
Sales Representative for technical assistance.  
Air Flow Dampers  
Function: Dampers operate in response to controls to provide the  
rated flow of makeup air to the building.  
Service: Clean dampers of dust or dirt.  
Description: The system is equipped with one of the 11 types of  
inlet air control arrangements listed below. All systems provide a con-  
stant flow of outside air across the burner at the required air volume  
(CFM).  
Refer to the wiring diagrams in the main electrical box to determine  
which controls are on the system being serviced.  
zOption AR1 - a constant supply of 100% makeup air  
zOption AR19 - 100% outside makeup air with variable supply air  
volume (CFM). The discharge damper controlling the variable air sup-  
ply is controlled by a manually set remote potentiometer and can be  
varied from 100% to 20% of total rated air flow (CFM). In response to  
changes in the discharge damper setting, the bypass damper balances  
the volume of air so that the required fixed amount of air volume flows  
over the burner.  
zOption AR20- 100% outside makeup air with variable supply air  
volume (CFM). The discharge damper controlling the variable air sup-  
ply is automatically controlled by a building pressure sensor and can be  
varied from 100% to 20% of total rated air flow (CFM). In response to  
changes in the discharge damper setting, the bypass damper balances  
the volume of air so that the required fixed amount of air volume flows  
over the burner.  
Damper Motor  
Figure 23 -  
DamperMotor  
Function: The damper motor automatically ac-  
tuates the return air, bypass, and/or discharge  
dampers in response to an electrical control de-  
vice. The damper motor is direct-coupled to the  
dampers so there is no damper linkage to ad-  
just.  
Service: There is no service required on these  
motors other than external cleaning. If the mo-  
tors need replaced, replace with an identical  
damper motor.  
Potentiometer  
Function: The potentiometer is a manually set  
switch that operates either the discharge damper  
(Option AR19) or the return air damper (Op-  
tion AR22) providing a mixture of return and  
outside air. It is a remotely located switch that  
requires manual adjustment.  
Service: If the potentiometer does not func-  
tion properly, replace it with an identical switch.  
Figure 24 -  
Potentiometer,  
P/N 16110  
Pressure Null  
Switch (automatic  
building pressure  
sensor)  
Description/Function:  
The pressure null switch is  
a diaphragm operated differ-  
ential pressure switch used  
in makeup air applications  
to automatically control  
zOption AR22 - a combination of outside makeup air and bypass  
return air including modulating return air and bypass air dampers. The  
volume of outside air is regulated by a remotely located, manually set  
potentiometer.  
zOption AR23 - a combination of outside makeup air and bypass  
return air including modulating return air and bypass air dampers. The  
volume of outside air is regulated automatically by a remotely located  
building pressure sensor.  
Figure 25 -  
Pressure  
Null Switch  
(building  
pressure  
sensor),  
P/N 88052  
zOption AR32 - a combination of outside makeup air and bypass  
return air including a two-position actuator. The two position actuator  
Page 9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
switch is only on systems with an optional console that includes a dirty  
filter light. The pressure switch is set during installation so that the light  
will be activated at approximately 50% filter blockage. Contacts should  
close at .17 to 5.0" w.c. ± .05" w.c.  
14. Inlet Air Controls (cont'd)  
Pressure Null Switch (cont'd)  
building pressure. It maintains a selected positive or negative pressure  
setpoint by changing the amount of outside air being introduced to the  
building through modulating outside air damper. As more pressure is  
required in the building, the pressure null switch activates the damper  
motor driving the outside air damper towards the full open position  
(causing the bypass return air damper to go toward the closed posi-  
tion). Conversely, as less pressure is required, the switch drives the  
outside air damper in the opposite direction.  
Service: Clean the sensor tubes. If the dirty filter indicator system still  
does not function properly, check the setting of the switch. With clean  
filters in place, blower doors closed, and blower in operation, decrease  
the pressure setting by adjusting the set screw on the switch clockwise  
until the filter light is energized or screw is bottomed out. At that point,  
adjust the set screw three full turns counterclockwise or until the screw  
is top ended.  
Service: Clean the tubing and the screened ends of the pressure tap  
vents. Be sure that the switch is installed with the diaphragm in a  
vertical plane and that the pressure taps are sheltered from the wind.  
For further service, follow the manufacturer's instructions included  
with the switch.  
If it is determined that the switch needs replacing, use an identical  
switch. When a new switch is installed, it must be manually set; follow  
the instructions above.  
16. Photoelectric Smoke Detector (Option  
SA1)  
Photohelic Pressure Switch (automatic  
building pressure sensor)  
Figure 28 - Photoelectric Smoke  
Location: Field-mounted in  
Detector (cover removed), P/N  
159553, used with sampling tube,  
P/N 159714  
the discharge ductwork.  
Description/Function: The  
photohelic pressure switch is a  
Figure 26 -  
Function: The detector will  
shut down the system if  
smoke is detected in the dis-  
charge ductwork.  
Photohelic  
Pressure  
Sensor,  
P/N  
phototransister relay operated  
positive pressure switch used  
in makeup air applications to  
automatically control building  
pressure. It maintains a selected  
positive pressure setpoint by  
changing the amount of outside  
air being introduced to the  
Service: Clean the external  
surface. Check the wiring and  
connections.  
159893  
17. Firestat (Option BD5)  
building through a modulating outside air damper. As more pressure is  
required in the building, the switch activates the damper motor driving  
the outside air damper towards the full open position (causing the  
bypass return air damper to go toward the closed position). Con-  
versely, as less pressure is required, the switch drives the outside air  
damper in the opposite direction.  
Location: Field-mounted on the dis-  
charge ductwork so that the sensor  
extends into the duct. This control  
requires manual reset so should be  
mounted in an accessible location.  
Figure 29 -  
Firestat,  
P/N 42782  
Function: The firestat will shut  
down the system if the temperature  
in the ductwork reaches 200°F. The  
switch must be manually reset.  
Service: Clean the tubing and the screened ends of the pressure tap  
vents.  
If the interior of the switch is protected from dust, dirt, corrosive gases  
and fluids, years of trouble-free service may be expected. Zero adjust-  
ment should be checked and reset occasionally to maintain accuracy;  
follow the manufacturer's instructions included with the switch.  
Service: Clean the external surface. Check the wiring and connections.  
18. Freezestat (Option BE2)  
There are no field-repairable parts in this switch. If the switch should  
require repair, contact either the system or the switch manufacturer  
concerning switch replacement or repair.  
Location: The control is in the  
blower section electrical box; the  
sensing bulb is field-mounted in the  
discharge duct.  
Figure 30 - Freezestat  
Controller, P/N 126170  
15. Dirty Filter Switch  
Function: The freezestat will shut  
down the system if the discharge  
temperature falls below the  
setpoint. The switch is automatic  
and will startup the heater when  
the temperature reaches the  
setpoint.  
Location:Switch is located in the  
Figure 27 - Dirty Filter  
Pressure Switch, P/N  
105507  
main electrical box (See Figure 7);  
sensor tubes run to either side of  
the filter rack; indicator light is on  
the remote console.  
Function: The dirty filter  
switch is a pressure switch that  
activates an indicator light on the  
remote console when the filters  
need cleaned or replaced (See Ser-  
vice Section, Paragraph 2). This  
Service: Clean the external surface.  
Check the wiring and connections.  
REFERENCE: For service and troubleshooting information on the electrical controls, refer to the  
manufacturer's literature covering that component. Component literature is included in the literature  
envelope shipped with the system.  
Refer to Paragraph 19 for unit troubleshooting.  
Page 10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19. Troubleshooting  
Chart 1 - General Troubleshooting Guide (Check the diagnostic lights on the circuit board)  
Symptom or Problem  
1. Disconnect switch is closed, but "control power" light is not lit.  
Cause and Remedy  
1. Fuses are missing or blown in disconnect switch - replace fuses.  
2. Transformer not wired according to diagram - check wiring.  
3. Secondary 8A fuse (on transformer) is missing or blown - replace fuse.  
4. Indicator light is burned out - replace bulb (P/N 125189).  
2. Disconnect switch is closed, but "firestat normal" light is not lit. 1. See causes and remedies for Problem 1 above.  
2. Optional control relay or door switch contacts are open - to test,  
jump terminals 3 to 4 or 1 to 2.  
3. Firestat option not ordered - verify order/wiring diagram.  
4. Firestat manual reset tripped - reset firestat control.  
1. Freezestat option not ordered - verify order/wiring diagram.  
2. Freezestat relay contacts are open - checking setting on control.  
3. Indicator bulb is burned out - replace bulb (P/N 125189).  
1. End switch on damper motor not closed. - check end switch wiring.  
2. Faulty damper relay - replace relay.  
3. Damper motor miswired - rewire damper motor per wiring diagram.  
1. Blower motor not wired correctly - check wiring diagram on motor.  
2. Faulty motor starter - replace (check coil first).  
3. Disconnect closed, blower switch in test position,  
"firestat" light is lit, but "freezestat" light is not lit  
4. Disconnect closed, blower switch in test position, "firestat" and  
"freezestat" lights are lit, but "starter energized" light is not lit  
and the blower motor is not operating.  
5. Disconnect closed, blower switch in test position,  
"firestat", "freezestat" and "starter energized"  
lights are lit, but the blower motor is not operating.  
6. Disconnect closed; blower switch in test position; "firestat",  
"freezestat" and "starter energized" lights are lit and the  
blower motor is operating; but the "low air light" is not lit.  
7. Disconnect closed; blower switch in test position;  
"firestat", "freezestat", "starter energized" and "low  
air" lights are lit and the blower motor is operating;  
but the "high air light" is not lit.  
8. Disconnect closed; blower switch in test position; "firestat",  
"freezestat", "starter energized", "low air" and "high air"  
are lit; but the "limit control normal" light is not lit.  
9. Disconnect closed; blower switch in test position;  
"firestat", "freezestat", "starter energized", "low air",  
"high air" and "limit control normal" lights are lit;  
but the "ambient (outside air) cutoff normal" light is not lit.  
10. Disconnect closed; blower switch in test position;  
"firestat", "freezestat", "starter energized", "low air",  
"high air", "limit control normal" and "ambient (outside air)  
cutoff normal" lights are lit; but the "low gas  
3. Faulty blower motor relay - replace relay.  
1. Low air switch open - verify pressure drop at burner.  
2. Indicator light is burned out - replace bulb (P/N 125189).  
3. Faulty low air switch - replace pressure switch (P/N 86986).  
1. High air switch open - verify pressure drop at burner.  
2. Indicator light is burned out - replace bulb (P/N 125189).  
3. High air switch option not ordered - verify order/wiring diagram.  
4. Faulty high air switch - replace pressure switch (P/N 86987).  
1. Indicator light is burned out - replace bulb (P/N 125189).  
2. Tripped manual reset limit control(s) - reset manual control.  
3. Faulty manual limit control (s) - replace limit control.  
1. Indicator light is burned out - replace bulb (P/N 125189).  
2. High ambient control option not ordered - verify order/wiring diagram.  
3. High ambient control contacts open - check setting on control.  
1. Indicator light is burned out - replace bulb (P/N 125189).  
2. Low gas pressure switch option not ordered - verify order/wiring diagram.  
3. Low gas pressure switch contacts open - check setting on control.  
4. Low gas pressure switch contacts open - check gas pressure.  
5. Faulty gas pressure switch - replace gas pressure switch.  
1. Indicator light is burned out - replace bulb (P/N 125189).  
2. High gas pressure switch option not ordered - verify order/wiring diagram.  
3. High gas pressure switch contacts open - check setting on control.  
4. High gas pressure switch contacts open - check gas pressure.  
5. Manual reset on switch tripped - reset pressure switch manual reset.  
6. Faulty gas pressure switch - replace gas pressure switch.  
1. Lack of power at L1 on ignition module - ECO blown, find  
cause then replace ECO.  
pressure normal" light is not lit.  
11. Disconnect closed; blower switch in test position;  
"firestat", "freezestat", "starter energized", "low air",  
"high air", "limit controls normal", "ambient (outside air)  
cutoff normal" and "low gas pressure normal" lights are lit;  
but the "high gas pressure normal" light is not lit.  
12. Disconnect closed; blower and burner switches in run  
position; control switch is in "winter" position;  
"control power", "high gas normal"; "low gas normal";  
"firestat normal"; "system switch energized"; "starter  
energized" and "freezestat normal" lights are lit; but  
ignitor is not becoming energized or beginning to glow.  
2. Faulty burner enable relay - replace relay.  
3. Low stage relay contacts are not closed - check air controller or  
thermostat setting.  
4. Faulty low stage relay - replace relay.  
5. Faulty hot surface ignitor - check continuity at the ignition module  
and circuit board. If reading is greater than 5-6 ohms, replace ignitor.  
6. Faulty ignition module - replace entire module.  
13. Disconnect closed; blower and burner switches in run  
position; control switch is in "winter" position; "control power",  
1. Ignitor not reaching 1.4A threshold - check voltage and  
current to ignitor.  
high gas normal; "low gas normal"; "firestat normal"; "system 2. Faulty hot surface ignitor - check continuity, replace ignitor.  
switch energized"; "starter energized" and "freezestat normal" 3. Faulty ignition module - replace entire module.  
lights are lit; ignitor glowing but "pilot valve normal" light  
(thus the pilot valve) is not energized.  
Page 11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19. Troubleshooting (cont'd)  
Chart 1 (cont'd) - General Troubleshooting Guide (Check the diagnostic lights)  
Symptom or Problem (cont'd)  
14. Disconnect closed; blower and burner switches in run position; control  
switch is in "winter" position; "control power", high gas normal; "low  
Cause and Remedy (cont'd)  
1. Air in pilot gas line - bleed pilot line.  
2. Inadequate pilot gas pressure - verify pilot gas pressure (3.5" w.c.)  
gas normal"; "firestat normal"; "system switch energized"; "starter 3. Faulty pilot valve - replace pilot solenoid valve.  
energized" and "freezestat normal" lights are lit; ignitor has reached  
1.4A and has opened the pilot valve bringing on the "pilot valve normal"  
light; but the pilot flame is not present. (After two trials the unit will go  
into safety lockout requiring cycling of the main disconnect switch.)  
15. Disconnect closed; blower and burner switches in run position;  
control switch is in "winter" position; all status lights are lit  
except "main valve normal" light. The pilot flame is present  
and stable, but the (low stage portion or) main gas valve will not  
open, or rapid cycling of the main valve is occurring.  
4. Faulty ignition module - replace entire module.  
1. Microamp signal on flame rod is inadequate - check position and  
condition of flame rod and signal (minimum 0.5 microamps required.)  
2. Grounding for unit or flame rod inadequate - check ground path.  
3. Faulty main gas valve - replace main gas valve.  
4. Faulty ignition module - replace ignition module.  
5. Inadequate main gas pressure - verify main burner pressure.  
1. Faulty main gas valve - replace main gas valve.  
16. Disconnect closed; blower and burner switches in run position;  
control switch is in "winter" position; all status lights are lit; the  
pilot flame and low fire on the main burner are present and stable,  
but the unit will not progress to a high fire condition.  
2. Inadequate timing on high fire time delay relay - adjust setting.  
3. Faulty high fire time delay relay - replace time delay relay.  
4. High stage relay contacts are not closed - check control setting.  
5. Inadequate main gas pressure - verify main burner gas pressure.  
6. Faulty high stage relay - replace relay.  
7. Faulty ignition module - replace entire module.  
FOR SERVICE OR REPAIR, FOLLOW THESE STEPS IN ORDER:  
FIRST:  
Contact the Installer  
Name  
___________________________________________________________________________  
Address ___________________________________________________________________________  
___________________________________________________________________________  
___________________________________________________________________________  
Phone  
___________________________________________________________________________  
SECOND:  
THIRD:  
Contact the nearest distributor (See Yellow Pages). If no listing,  
contact Authorized Factory Representative, 1-800-695-1901 (Press 1).  
Contact REZNOR®/Thomas & Betts Corporation  
150 McKinley Avenue  
Mercer, PA 16137  
Phone: (724) 662-4400  
Model No.  
_____________________________________________  
Unit Serial No.  
_____________________________________________  
Date of Installation _____________________________________________  
Index .................................................. Page  
Index .................................................. Page  
Index .................................................. Page  
Filters ....................................................... 3  
Firestat .................................................... 10  
Freezestat ............................................... 10  
Gas Control Systems ............................... 7  
Gas Pressure ............................................ 3  
Gas Pressure Switches .............................. 8  
Inlet Air Controls ..................................... 9  
Limit Control ........................................... 5  
Main Burner ............................................. 4  
Maintenance Schedule ............................. 2  
Maintenance Section ......................... 2-4  
Maintenance/Service Access .................... 2  
Manifold Arrangements ........................... 8  
Operation/Service Section .............. 5-12  
Outside Air Cutoff Control ..................... 8  
Photoelectric Smoke Detector ................ 10  
Photohelic Pressure Sensor ..................... 10  
Pilot Assembly ........................................ 4  
Potentiometer ........................................... 9  
Pressure Null Switch ............................... 9  
Sensing Pressure Check ........................... 6  
Troubleshooting ..................................... 11  
Wiring Diagram ......................... In the main  
electrical box on the unit  
Air Pressure ............................................. 4  
Air Pressure Switches ............................... 6  
Blower Bearings ....................................... 3  
Circuit Indicator Board ............................ 4  
Control Locations .................................... 5  
Damper Motor ........................................ 9  
Direct-Fired Burner ................................. 7  
Dirty Filter Switch ................................ 10  
Drive Components ................................. 3  
Electronic Circuit Board with  
Diagnostic Lights ................................. 5  
Emergency Cut Off .................................. 6  
©2001 Thomas & Betts Corporation, All rights reserved.  
Printed in the U.S.A.  
MANUFACTURER OF HEATING, COOLING, AND VENTILATING SYSTEMS  
Trademark Note: Reznor® is registered in the United States and other countries.  
Page 12  
8/01 YL Form 441OMS (Version .1)  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Tektronix Printer Accessories 016 1130 00 User Manual
Teledyne Scuba Diving Equipment HEATED THC User Manual
Toshiba Model Vehicle 58 65L5400U User Manual
Uniden Cordless Telephone EXI7246C User Manual
United States Stove Electric Heater 2827 User Manual
Viking Range F20495 User Manual
Vivitek Projector D732MX User Manual
Vizio Video Game Sound System S5451w C2 User Manual
VTech Baby Toy 3 in 1 smart wheels User Manual
VTech Telephone DS3101 User Manual