Thermo Products Stud Sensor USDT2004 User Manual

USDT 2004  
Installation and User’s Guide  
Introduction  
General Information  
2
Installation  
Collector Sensor  
3
3
5
6
6
Control Box  
Power Connection  
Display Window  
Operation  
Basic Operation (Factory Setting for Only Two Sensors)  
Manual Operation Mode  
7
8
Three Sensor Operation  
9
Sensor Selection  
11  
12  
Alarm Functions and Diagnostics  
Energy Calculations  
Troubleshooting  
13  
14  
ã Thermo Technologies  
5560 Sterrett Place • Suite 115  
Columbia, Maryland 21044  
Phone 410.997.0778 • Fax 410.997.0779  
Revision 7, November 2005  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
Note: This installation procedure is for guidance only, and the installer should verify its  
suitability. Make sure that the solar system is physically installed, manually tested, and ready for  
controlled operation.  
he following safety precautions are strongly recommended:  
T
1. Before attempting to install and operate the unit read this instruction manual carefully.  
2. Only suitably qualified personnel should carry out installation and required maintenance.  
3. It is recommended that the unit be connected to the power supply via an isolating switch of 6  
amp.  
4. WARNING: When the unit is connected to the 115-volt power supply and the cover is  
opened, high voltage circuits will be exposed.  
When installing the unit, all required  
connections should be completed and the cover attached to the controller box before turning  
the power on. Ensure that all connections are secure. If any maintenance work is required  
isolate the unit from the power supply before removing the cover. Never leave the unit  
unattended if the cover has been removed and the power supply is connected.  
5. Do not exceed unit ratings of 3.15 amps (1/6 HP or 245 Watts pump).  
6. It is advisable to route power cables away from sensor cables.  
ensor installation: Temperature sensors may be installed in fluid lines by mounting in a  
tee or strapping it to the piping directly. For the system to function correctly, it is essential  
that the sensors are located and installed properly. They MUST be pushed completely  
into the optional sensor pockets (Thermowell is not supplied). Sensors must be well insulated in  
order to prevent them from being influenced by the ambient temperature.  
S
When used outdoors, water must not enter the immersion sleeves (lasting impedance change).  
Exposure to moisture (e.g. condensation) can diffuse through the cast resin and damage the  
sensor. In this event, heating at approx. 195 °F for one hour may reverse the damage.  
When sensors are used in open loops or swimming pools, corrosion-resistant immersion sleeve,  
(sensor pockets), must be used.  
l
Collector sensor (red cable with protective terminal box): Either push into a thermowell,  
(sensor pocket), which is soldered or riveted directly to the manifold (vacuum tubes). Alternately,  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
strap the sensor to the collector outlet pipe or the absorber (flat plate collectors) that projects from  
the collector housing. Ideally, house the collector sensor (encased in a suitable sensor pocket)  
into a T-piece on the collector return outlet. Protect the sensor cable from UV and moisture.  
l
Return (tank) sensor (white cable): The sensor required for the solar loop return is installed  
in the lower part of the storage tank. If there is no provision for this tank sensor, push the sensor  
beneath the insulation – keeping it close to the inner tank wall at the desire tank location.  
For external heat exchangers, the tank sensor should be installed with an immersion sleeve in the  
return leg (cold side) of the heat exchanger. In tanks with integrated heat exchangers, the sensor  
pocket should be fitted at the exchanger's return to the collector.  
l
Pool sensor installation: Place a heat conductive T-piece on the suction line directly at the  
pool outlet and screw in the sensor with an immersion sleeve (check corrosion resistance of the  
material used). Alternately, attach the sensor with clips or adhesive tape, using the appropriate  
thermal insulation to guard against environmental influences.  
l
Sensor cable extension: Sensor cables (22/4 AWG telephone cable, you need only two  
wires of 4) can be extended up to 150 ft. A connection between the sensor and extension can be  
established as follows:  
Cut the supplied heat-shrinkable tubing to desired length (about ½ ”). Slide tubing over one end of  
wire to be sliced (after removing enough outer insulation to accept the tubing). Splice the wire  
and slide tubing over the splice. Heat gently all around until tubing shrinks tight.  
Slide larger tubing (about ¾ “) over the entire completed splice. Heat gently all around until tubing  
shrinks tight. This connection can then be drawn gently into the pipe work. Only two of the wires  
are required for the sensor cable; the other two wires are spare wires.  
Caution: Do not overheat the tubing! Remove heat as soon as the tubing shrinks tight, as  
material will continue to shrink. With flame source, use even back and forth motion all around  
tubing. A heat gun may be used, if available. Let tubing cool for maximum strength.  
ontroller unit installation: For viewing comfort, the controller unit should be positioned  
at eye level. For optimum longevity, avoid extremes of temperature in the placement of  
electronic equipment. In addition, avoid heavy electrical loads, switches or contactors as these  
may cause electrical and electromagnetic interference with the unit (when switched on or off).  
C
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
Undo the screw at the top of the housing. The control electronics are mounted on the enclosure  
cover. The controller enclosure can be screwed to the wall with cable entry grommets pointed  
downwards. Use the supplied plastic bridges to secure power and sensor cables.  
Base of the unit to be mounted at eye-level and wired as shown above  
Caution: Controller wiring should only be done when the unit is not energized. It is possible to  
damage the control unit if it is assembled under voltage. Miniaturized terminal blocks are used for  
making wiring connections. The wire is held in place within the terminal with screw that provides  
excellent contact without damage to the wire.  
Sensor Cable Connection: Use up to an 18 AWG stranded wire to connect the sensor cables to  
the unit. The S1 terminal should be connected to the collector sensor (higher temperature); the  
S2 terminal is designated for the tank sensor (lower temperature). And the S3 terminal is  
reserved for the advanced usage of the unit such as third temperature sensor (in program mode  
1) or flow meter input for BTU operation in advanced programming mode.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ower Connections: A small blade screwdriver may be used to fasten miniaturized  
terminal block screws while the corresponding wire is inserted.  
P
NOTE 1: Always disconnect the controller from power supply before opening the housing.  
NOTE 2: The controller should be properly grounded. Flexible wires, 18/3 AWG  
(gauge/conductor) simplify connection to the terminals. The power terminal block will  
accommodate wire sizes to 14 AWG. All other connections should be secured and adequately  
tightened, as loose power connections will over-heat, and may cause fire.  
NOTE 3: It is important that the specified output loads (245 Watts) are not exceeded. Where  
these loads expect to exceed, external relays must be used. It is good practice to install a switch  
to disconnect the controller and pump from power. Always keep power cables away from sensor  
cables and other low voltage signal cables.  
NOTE 4: To protect against lightning damage, the system must be grounded according local  
regulation. Sensor failures due to the weather or electrostatic are mostly due to poor grounding.  
our controller displays requested information one at a time. The unit display window  
has three lines to inform you about the system's status, unit of displayed parameter  
and its value.  
Y
Upper Line Display  
Center Line Display Sensor ID and its reading in normal mode (user interface window)  
Lower Line Display Set-point indicator that illuminates only during programming mode  
Symbolic display of sensor location, reading unit, and operation domain  
ð
ï
ò
Push selection key once to move to the next selection; or increase the selected  
parameter by one unit.  
Push selection key once to move to the previous selection; or decrease the selected  
parameter by one unit.  
Push selection key once to enter the advanced (Par or *Men) mode. Once in selected  
mode, press one more time to select the parameter in that mode. Selected parameter  
blinks allowing the user to modify it. You can modify the selected parameter while the  
middle window blinks by pressing the ïor ðkey.  
ñ
Push selection key once to accept selection (blinking stops showing the new set-point  
steady) or go back to the previous selection.  
* Menmode is for use in advanced applications only. See P.9.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Use selection keys ïðduring normal system operation to display the desired parameter:  
o
T1 xxx  
T2 xxx  
T3 xxx  
Collector temperature in F  
Tank temperature in F  
o
Reading of the third sensor; if the third sensor is not used it displays a fixed  
reference temperature of 250oF  
Collector power in [kW]  
Energy collected in [MWh]  
Energy collected in [kWh]  
XX xxx  
YY xxx  
ZZ xxx  
GAL xx  
Flow rate [gallon/h]  
Operation Mode – Example: Following chart displays system temperatures  
At the upper text line, the icon for the text is always displayed. Program symbol is displayed  
during the setting of parameters at the lower text line. In addition, an arrow icon > is displayed  
while pump is running.  
Program Mode - Pressing the selection key ðseveral times allows you to enter into the  
program mode (Par). Push selection key òonce to enter the program mode.  
Basic Operation (Factory Setting for Only Two Sensors)  
PROGRAM 0: (basic 2-sensor program)  
Par  
Using the navigation key ^_ allows you to select the desired parameter while you are in  
the program mode. Press the selection key òonce to select the parameter in the  
window. Selected parameter blinks allowing you to modify it. You can modify the  
selected parameter while the middle window blinks by pressing the ïor ðkey. The  
unit accepts the new value by pressing the ñkey once. To avoid unintentional set-point  
changes, the user must enter the access code “32” to manipulate factory settings.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
RUV X.X – This display shows the software revision number.  
NR O This is PROGRAM 0 which indicates simple operation of unit as a Universal Solar  
Differential Temperature (USDT) controller. Change this value to 1 (NR 1) for activation of the  
third sensor or pulse flow meter input (PROGRAM 1).  
Hysteresis Bandwidth  
User can program hysteresis (temperature range for output control) by using max? and max=.  
For  
max?1  
Pump stops above tank temperature (T2)  
max=1  
Pump runs again below this set point (T2)  
Delta T Adjustment  
diff=1  
Pump runs when temperature difference between collector T1 (collector) and T2  
(tank) exceeds this value. Factory setting is 15 oF. Consult your collector  
manufacturer for the recommended value.  
diff?1  
Pump stops when temperature difference between collector T1 (collector) and T2  
(tank) reaches this value. Factory setting is 7 oF. Consult your collector  
manufacturer for the recommended value.  
Manual Operation Mode  
AUTO  
The above display indicates that the unit is working in automatic mode. The  
pump starts at a temperature difference of 15 oF and runs as long as ? T is  
above 7 oF. The B symbol appears in upper display line next to the collector  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
symbol while the pump is running. User can switch to manual mode by pressing  
òkey. By pressing ðkey while centerline blinks, a hand symbol Gin lower line  
shows manual operation. Pressing ðone more time lets you turn the pump ON or  
OFF. By pressing ñkey you change the pump operation.  
Advanced Operation (Setting for Three Sensors and Flow Rate Input)  
To change the factory setting of two sensors you need to advance to the Men domain using  
access code “64”:  
Navigation of advanced features of the unit and selection of parameters is the same as before by  
using ïòñðkeys:  
Advancing – Press the Advance key ïð briefly to advance to the next selection or to  
increase/decrease the set point of the selected parameter. Hold it down for fast change.  
Acceptance – Press Set-Up key òonce to select the parameter. Press ñkey to accept the  
selection or the set point.  
Three-Temperature Sensor Setting (PROGRAM 1):  
USDT 2004 accepts two different sensor types or a reference value. Press the  
Advance key ïðbriefly until SENSOR appears in centerline and press the key ò.  
Select S3 sensor and change the 250 reference value to read KTY sensor:  
Note: Tank over heating protection in program mode 1 (NR 1) controls the pump  
operation based on temperature reading by T2 and T3 sensor readings.  
Selection:  
S3  
Designation:  
KTY Thermistor sensor (2000 O at 25 C)  
Sensor 3 (tank) selection  
o
Accept this setting by pressing ñkey. If you wish to change set points for pump  
operation, follow instruction explained in Basic Operation section (these changes  
are made in Par domain).  
max?1  
Pump stops above tank temperature (T2)  
max=1  
Pump runs again below this set point (T2)  
max?2  
Pump stops above tank temperature (T3)  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
max=2  
Pump runs again below this set point (T3)  
Energy calculation mode (PROGRAM 1):  
USDT 2004 computes the energy production as a function of the temperature  
differential and fluid volume. In addition, the system anti-freeze (Glycol) percentage  
should be entered as it affects the thermal conductivity and heat transfer rate.  
Press the Advance key ïðbriefly until BTU appears in centerline and press the  
key ò. Designate sensor inputs for example T1 as collector inlet and T2 as  
collector outlet temperature. F SEN can be connected to a flow meter or be a  
constant number in a closed loop solar system.  
BTU  
Energy calculation mode  
S IN  
Sensor port selection for inlet temperature (1, 2, 3, --)  
S OUT  
F SEN  
outlet temperature (1, 2, 3, --)  
Sensor port selection for flow rate (1, 2, 3, --)  
Energy calculation will be initiated only after temperature sensor ports are  
designated. Flow rate can be either a constant number to be entered by user, or  
from a flow meter input. To activate the energy calculation without using the flow  
meter's impulse input, a dash (-) must be selected for F SEN channel followed by  
the constant flow rate in gph (gallon per hour) unit.  
LLP  
GAL  
Flow meter rate impulse number in liter per pulse, if flow meter is  
used  
Constant flow rate in gph instead of flow meter reading in (--)  
sensor mode  
GLYCOL  
CLEAR  
DIF  
Anti-freeze percentage  
Sets the BTU meter's counter to zero  
Sensor calibration  
The output of USDT 2004 unit is kW for system power and kWh or MWh for  
collected energy.  
dvanced Mode – USDT 2004 is extremely powerful. It can be used in wide range of applications  
such as a BTU meter, a boiler fuel optimizer, a swimming pool temperature differential  
controller, a greenhouse temperature regulator, an air handler, and more. Factory  
settings are exclusively for solar water heating systems in the USA market. However, all its  
parameters can be changed to meet the unique requirements of other applications. The user may  
use access code "64" to modify the USDT 2004 program mode and its parameters.  
A
Men  
This mode is for advanced applications  
The factory setting will be retrieved by pressing and holding òkey during powering of the  
unit. A “RESTOR” displays for three seconds while factory settings are restored.  
Selection of different sensor types, energy collection calculation parameters, system protection  
and optimization can be can be modified in advanced (Men Domain) mode.  
Mode  
Operation  
SENSOR  
SGUARD  
Selects sensor type  
Protects system from overheating and frost  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START  
ALARM  
BTU  
Starts pump at pre-set insolation (solar radiation intensity)  
Enables/Disables protection functions  
Energy calculation and setting  
ensor Designation USDT 2004 accepts two different sensor types or a reference  
value . User can program a constant reference temperature instead of a sensor output.  
The factory-preset sensor is the thermistor (KTY 10) type. The KTY 10 tank sensor,  
S
white wire, should be used in a conditioned environment and will not be permanently damaged up  
to 360 F.  
o
Selection:  
S1  
S2  
S3  
Sensor 1 (collector outlet) selection  
Sensor 2 (collector inlet) selection  
Sensor 3 (tank) selection  
Designation:  
o
PT  
PT 1000 sensor (1000 O at 0 C, not available in US market)  
o
KTY  
250  
- 4  
Thermistor sensor (2000 O at 25 C)  
250 oF reference temperature  
- 4 oF reference temperature  
Sensor wires can receive electromagnetic pulses, which can result in a wrong temperature  
reading. The USDT 2004 reads sensor values every 50 ms. It can bundle several readings and  
process their average.  
AV 1 Sensor 1 average  
AV 2 Sensor 2 average  
AV 3 Sensor 3 average  
The numbers of samples can be programmed from 4 to 20. The impedance characteristics of  
sensors temperature dependencies are represented in the following table:  
T
0
10  
20  
25  
30  
40  
50  
60  
70  
80  
90  
100°C  
R(KTY) 1630 1772 1922 2000 2080 2245 2417 2597 2785 2980 3182  
3392 W  
rost and overheating protections - Pump operation can be manipulated by the user in  
both collector stagnation and frost conditions. The set-up is possible in System Guard,  
SGUARD, domain.  
F
Overheating protection – The Circulation pump may not be powerful enough to circulate the  
heat transfer fluid in the solar loop with air pockets. User can program the pump to stop at a  
desired maximum collector temperature, shown by ? symbol, to protect the pump. The USDT  
2004 will take over the normal operation after the temperature decreases to an acceptable  
o
working temperature, shown as =. This feature is disabled at 299 F set point.  
Frost Protection – Frost protection in the sun-belt region is provided by circulating water in the  
solar loop when freezing conditions exist. Regardless of the temperature difference ? T, the  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
circulation pump runs when the collector temperature is below a programmable minimum  
temperature, shown by = symbol. The pump stops as soon as the temperature in the solar loop  
reaches a safe region programmed by the ? symbol. This feature is also disabled at the factory  
by entering - 4 oF.  
min= Pump runs below this temperature  
min? Pump stops above this temperature  
tart functions - The Circulation pump can be programmed to start on low insolation  
level. The Start function feature is useful when heat transferred to the collector sensor is  
not fast enough for early start; especially when the collectors are flat mounted.  
S
The enabled start function runs the pump at a given solar radiation or programmed temperature  
difference. The feature is disabled at the factory.  
START  
ENABL  
DISAB  
Start function screen  
Enable start function  
Disable start function  
If this feature is selected, following parameters must be adjusted for proper operation:  
SENS  
Pyranometer port designation (radiation monitoring sensor port)  
1
2
3
--  
Sensor 1  
Sensor 2  
Sensor 3  
Manual input in next step  
INS  
CIRC  
INT  
Radiation threshold in W/m2  
Pump runtime in seconds  
Maximum interval time in second  
Number of flushes  
FLU  
The following example activates the circulation pump at 200 W/m2 and runs it for 15 seconds. If  
rT condition is met within the time period, the pump stays on.  
INS  
20  
CIRC 15  
larm functions - User can enable the alarm function of the USDT 2004 in the ALARM  
screen. Status of sensors and circulation pump can be viewed if alarm function is active.  
A
A ON  
A OFF  
Alarm function enable  
Alarm function disable  
The status of the system can be monitored in the Stat Mode only if the corresponding feature is  
active. The following example shows a system condition with a circulation problem:  
OT OFF  
OT OK  
Overheating feature disable  
No overheating  
1 SHORT  
2 SHORT  
1 OPEN  
Short circuit in sensor 1 wiring  
Short circuit in sensor 2 wiring  
Disconnection in sensor 1 wiring  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 OPEN  
OK  
NO CIRC  
OK CIRC  
CLEAR  
Disconnection in sensor 2 wiring  
System operates normal  
o
r T is more than 108 F in last 30 minutes  
Pump is running  
Clears NO CIRC display after correction  
nergy calculation - Energy gain is calculated by obtaining the temperature increase of  
heat transfer fluid across the solar collector. The amount of fluid flow through the  
collector is registered by an in-line flow meter. USDT 2004 computes the energy production as a  
function of the temperature differential and fluid volume. In addition, the system anti-freeze  
(Glycol) percentage should be entered as it affects the thermal conductivity and heat transfer  
rate.  
E
BTU  
Energy calculation mode  
S IN  
S OUT  
Sensor port selection for inlet temperature (1, 2, 3, --)  
outlet temperature (1, 2, 3, --)  
F SEN  
Sensor port selection for flow rate (1, 2, 3, --)  
Energy calculation will be initiated only after temperature sensor ports are designated. Flow rate  
can be either a constant number to be entered by user, or from a flow meter input. To activate the  
energy calculation without using the flow meter's impulse input, a dash (-) must be selected for F  
SEN channel followed by the constant flow rate in gph (gallon per hour) unit.  
LLP  
GAL  
GLYCOL  
CLEAR  
DIF  
Flow meter rate impulse number in liter per pulse, if flow meter is used  
Constant flow rate in gph instead of flow meter reading in (--) sensor mode  
Anti-freeze percentage  
Sets the BTU meter's counter to zero  
Sensor calibration  
The output of USDT 2004 unit is kW for system power and kWh or MWh for collected energy.  
The energy calculation dependents on flow meter accuracy, the temperature sensors class, and  
their locations. The flow meter is a mechanical device and its accuracy fluctuates over time.  
Therefore, the user should calibrate the flow meter and incorporate temperature sensor tolerance.  
The supplied Thermistor sensor has an accuracy of ± 2 oF. DIF represents the temperature  
difference between two sensors. User can increase the accuracy of reading by adjusting the DIF  
parameter. The energy calculation becomes accurate at temperature range that this reading  
adjustment is made.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
roubleshooting  
T
In general, all of the settings in the menus Par and Men and the terminal should first be checked  
if there is a malfunction.  
Malfunction, but "realistic" temperature values:  
·
·
Check program number.  
Check the switch-on and switch-off thresholds and the set differential temperatures. Have  
the thermostat and differential thresholds already been reached?  
·
·
Were the settings in the submenus (Men) changed?  
Can the pump (output) be switched on and off in manual mode? If a forced pump “ON”  
and “OFF” lead to the appropriate reaction at the output, the unit is certainly in order.  
·
·
Are all of the sensors connected with the right terminals? Heat up the sensor using a  
cigarette lighter and watch the display.  
Did you change the reference temperature 250 (three sensor operation) to KTY?  
Incorrect display of temperature(s):  
·
·
·
Displayed values such as -999 if a sensor short-circuits  
or 999 if there is an interruption do not necessarily mean a material or terminal error.  
Are the right sensor types (KTY or PT1000) selected in the menu Men under SENSOR?  
The factory settings set all inputs to KTY.  
The sensor can also be checked without a measuring instrument by connecting the presumed  
defective sensor to a terminal that works and checking the display. The resistance measured by  
an ohmmeter should have the following value depending on the temperature:  
T
0
10  
20  
25  
30  
40  
50  
60  
70  
80  
90  
100°C  
R(KTY) 1630 1772 1922 2000 2080 2245 2417 2597 2785 2980 3182  
3392 W  
The settings of the parameters and menu functions ex works can be restored any time by  
pressing the down arrow (enter) while powering the controller. The sign that appears for three  
seconds on the display is RESTOR for load factory settings.  
If the system is not in operation while connected to the power supply, the 3.15A quick-blowing  
fuse that protects the control system and the output should be checked and exchanged if  
necessary.  
As the programs are constantly being improved, there may be a difference in the sensor, pumps,  
and program descriptions. Only the enclosed manual (identical serial number) applies for the  
equipment supplied. The program version for the manual must correspond to the equipment  
version.  
If the control system is found to be malfunctioning despite the checks described above, please  
contact your retailer or Thermo Technologies directly. The cause of the error can only be  
determined if the settings of the unit is known. The schematic diagram of the system in question  
is a great help to isolate the potential problem.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Targus Mouse Wireless Laser Rechargable Notebook Mouse User Manual
Terraillon Doll TPRO4300 User Manual
Transcend Information Computer Drive 25M User Manual
TRENDnet Network Router TEW812DRU User Manual
Vantec Network Card PCI PCI E Card CardBus User Manual
Vidikron Projection Television Vision 10 User Manual
Viking Refrigerator F20481 User Manual
Vita Mix Blender CREATIONS GALAXY CLASS User Manual
Vizio TV Antenna E320i B1 User Manual
Vulcan Hart Oven VCV4 User Manual