10 & 12 SEER
AIR HANDLER
INSTALLATION & SERVICE MANUAL
MODELS: AH1-A, AH2-A
PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION AND BEFORE
PERFORMING ANY SERVICE OR MAINTENANCE. THESE INSTRUCTIONS MUST
BE LEFT WITH THE USER AND SHOULD BE RETAINED FOR FUTURE
REFERENCE BY QUALIFIED SERVICE PERSONNEL.
: Improper installation, adjustment, alteration, service, or maintenance can
cause injury or property damage. Refer to this manual. For assistance or additional
information consult a qualified installer, service agency, or manufacturer listed below.
THERMO PRODUCTS, LLC.
BOX 217
NORTH JUDSON, IN 46366
PHONE: (574) 896-2133
MADE IN USA
MAC-165
ECN 4392-MA
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
SAFETY SECTION
This page contains various warnings and cautions found throughout this Service and Installation
Manual. Please read and comply with the statements on the cover and the statements below.
: Improper installation, adjustment, alteration, service, or maintenance can
cause injury or property damage. Refer to this manual. For assistance or additional
information consult a qualified installer, service agency, or manufacturer listed below.
: If drilling or screwing into panel or plate is necessary, make certain drill or screw
does not penetrate into any part of evaporator coil or hot water coil and cause damage. Personal
injury and/or property damage may result.
: Do not use this system if any part has been under water. Immediately call a
qualified service agency to inspect the system and to replace any part of the electrical or control
system which has been under water.
: The cooling and heating coils must be cleaned by a qualified service person.
: This air handler is not to be used to condition during construction.
: When testing electrical equipment, always follow standard electrical procedures
and precautions.
: DO NOT wet electronic components during hydronic testing. Wetting
electronic components may damage circuitry and cause a hazardous situation. Dry moisture from
all leads and terminals if wetting occurs. Wait at least 24 hours for the circuit to fully dry before
energizing the system.
: Personal injury or property damage could result from major repair or service of
this system by anyone other than a qualified contractor.
: If you do not follow these instructions exactly an unsafe condition may result
causing personal injury, loss of life or property damage.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
Installation and service personnel are required by some states to be licensed. Persons not
qualified shall not install this equipment nor interpret these instructions.
All local codes and regulations take precedence over the instructions in this manual and should
be followed accordingly. In the absence of local codes, installation must conform with these
instructions, regulations of the National Fire Protection Association and provisions of the
National Electric Code.
AIR HANDLER
Each air handler is capable of operation within a range of evaporator coil sizes. The evaporator
size specified is shipped as a separate item and must be installed by the contractor. Model AH2-
A will accommodate the 1060-G1, 1242-G1, 1042E, and 1048E. The AH1-A will accommodate
the 1024E, 1030E, 1036E, 1224-G1, 1230-G1 and 1236-G1.
The construction of the air handler permits easy knockdown and reassembly. See Figure A.
Figure A
2
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
FOLLOW THESE STEPS FOR KNOCKDOWN OF AIR HANDLER:
1. Start with unit setting in a vertical position. (Figure A)
2. Remove screws from bottom door, middle door, top door, and top front panel. Remove doors
and top panel of air handler.
3. Disconnect blower leads from blower terminal strip.
4. Remove screws that secure the blower pan to the side casings and the back casing.
5. Pull blower sub-assembly up and out the front of the unit.
6. Remove screws from the bottom and the casing back.
7. Remove casing back and side casings from the bottom.
REASSEMBLY OF AIR HANDLER
To reassemble the air handler, reverse steps above starting with number 7.
INSTALLATIONS OF A-COIL IN VERTICAL APPLICATIONS
A standard Thermo Pride A-coil is used in all air handlers. The coil and its attached drain pan are
installed in the air handler. See Figure B1.
Figure B1
3
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
INSTALLATIONS OF A-COIL IN HORIZONTAL APPLICATION
For the AH1-A, in all A-coil applications (1024E, 1030E, 1036E, and 1224-30G1) except the
1236G1, the A-coil spacer must be used.
For the AH2-A, in all A-coil applications the A-coil spacer must be used.
1. Remove bottom door of air handler.
2. Remove middle door of air handler.
3. Slide primary drain pan out of unit.
4. Set A-coil spacer in primary drain pan if needed. See Figure B2, #1 inset.
5. Set A-coil in place on primary drain pan.
6. Secure coil installation strip with aluminum tape as indicated in Figure B2, inset #2.
This makes a small ramp to slide the coil up and on the rear pocket brake.
7. Slide pan with coil into air handler making sure that the A-coil plastic pan is properly
positioned in the primary drain pan. Insure the plastic coil pan on base of the A-coil slides
into rear clip. See Figure B2.
8. Secure front of plastic pan to bottom of unit with supplied pan clip. See Figure B3 inset.
An extension for nut driver may be of benefit.
9. Pan should rest on pocket brakes on each side of side casing when properly installed.
IMPORTANT: When air handler is installed in attic above a finished ceiling, it is
recommended that a safety overflow pan with its own separate drain be installed under
the entire unit.
10. Remove trim plate from A-coil connections.
11. Cut out appropriate holes in insulation, remove appropriate knockouts, and realign coil
access panel and secure into place
12. Make appropriate liquid and suction line connections to coil and braze connections.
NOTE: A wet rag makes an excellent heat sink for tubing.
: If drilling or screwing into panel of plate is necessary, make certain drill does not
penetrate into any part of evaporator coil or hot water coil to avoid personal injury and/or
property damage.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
13. Position grommets in coil access panel to allow installation of trim plate, secure trim
plate in place with screws, and seal connections with duct sealer or equivalent.
NOTE: The air handler is factory assembled for left to right(horizontal) and vertical
applications. If a right to left horizontal application is desired, the fan center must be moved to
the right side casing which will position it above the primary drain pan.
Figure B2
5
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
Figure B3
INSTALLATION OF THE HOT WATER COIL:
1. Remove top door of air handler.
2. Slide hot water coil's side hanger brackets into coil channel(retaining channel) in the air
handler. See Figure B4 inset.
Figure B4
3. Push coil into unit until the coil is stopped by the back casing.
4. Cut out appropriate holes in insulation, realign top door and secure into place.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
5. Make appropriate hydronic connections to inlet(blower side) and outlet(duct side) of coil and
braze into place.
6. Seal connections through panel with duct sealer or equivalent.
: If drilling or screwing into panel or plate is necessary, make certain drill does not
penetrate into any part of evaporator coil or hot water coil. Personal injury and/or property
damage may result.
Figure C
NOTE: Drain lines must be pitched no less than 1/4" per foot away from the air handler.
TRIM PANEL INSTRUCTIONS:
Included as a loosely packed part in the condensate drain pan of both air handlers is two trim
panels. These panels are to be used in reducing the free area between both the hydronic coil lines
and the evaporator coil lines. The hydronic coil panel has two holes which the inlet and outlet
lines fit through. This panel is to be secured to the air handler via the prepunched holes and
included screws. The evaporator coil panel is a flat rectangular panel measuring 8-1/2” x 3”,
with a 1/2” brake on one edge. The 1/2” brake is to fit into the pocket brake of the side casing
and the larger part of the panel is to be attached to the bottom door via the prepunched holes and
included screws. This panel will close the gap that is created between the side of the air handler,
and the grommet panel that is installed on the evaporator coil.
BLOWER AIR ADJUSTMENT
The direct drive blower must be set in order to establish proper air movement. Use the following
steps to do this:
*For cooling only remove low speed connection to terminal block unless continuous fan is
desired.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
1. Determine the appropriate blower speed settings listed in tables below.
2. Set the blower motor speed to match air conditioning requirement, connect the red
wire(cooling tap) to the appropriate fan speed on the terminal strip located on the blower(see
Figure D).
3. Set the blower motor speed to match heating requirement, connect the orange wire(heating
tap) to the appropriate fan speed on the terminal strip located on the blower(see Figure D).
Figure D
Heating Tap Locations
40,000 (btuh)
White
60,000 (btuh)
White
80,000 (btuh)
White
100,000 (btuh)
White
Terminal Strip Speed
C
H
MH
ML
L
Orange
Orange
Orange
Orange
Cooling Tap Locations
2 Ton
White
2.5 Ton
White
3 Ton
White
3.5 Ton
White
4 Ton
White
5 Ton
White
Red
Terminal Strip Speed
C
H
MH
ML
L
Red
Red
Red
Red
Red
8
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
Recommended
Heating Capacity
(btuh)
Water Flow Rates
for Heating
(GPM)
40,000
60,000
80,000
100,000
4
6
8
10
DUCT SYSTEM
The duct system and load sizing calculation should follow the design standards of Air
Conditioning Contractors of America (ACCA) - manuals D & J - or the American Society of
Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE) Latest Edition
Fundamentals Volume.
To aid you in evaluating existing duct systems quickly, review the chart on Page 11 which shows
the CFM capacity for square inch areas, based on .10" wc static pressure (SP) loss on the supply
systems.
Each of the system's components (trunk lines, take-offs, runs and register and grill-free areas)
must be properly sized and matched together to ensure you are obtaining the air handling
capacity of the duct system. A 12x8 duct with a 400 CFM capacity, for example, WILL NOT
flow 400 CFM if the register(s) to which it connects can only flow a total of 200 CFM.
The air handling capacity MUST BE EQUAL TO the supply system at a minimum when sizing
the return air duct system. It is recommended to follow design parameters set down by ACCA or
ASHRAE on the return air duct systems.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
CFM CAPACITY CHARTS
AH1-A
.2 Duct Static Pressure
with heating coil
And applicable Evaporator Coil Model
CFM (HI) CFM (M. HI) CFM (M. LOW) CFM (LOW)
1024E and 1030E
1299
1756
1435
1438
1123
1202
1231
1193
992
821
880
861
860
1224-30G1
1036E
1236G1
1073
1055
1036
.2 Duct Static Pressure and applicable
Air Conditioning Coil Only
1024E and 1030E
1224-30G1
1390
1591
1575
1523
1243
1335
1307
1280
1085
986
1092
1074
905
921
911
913
1036E
1236G1
Heating coil
.2 Duct Static Pressure
.2 Duct Static Pressure + .3 additional
load
1514
1294
1261
1109
1055
964
889
785
AH2-A
.2 Duct Static Pressure
with heating coil
And Applicable Evaporator Coil Model
1060G1 and 1242G1
1042E
CFM (HI) CFM (M. HI) CFM (M. LOW) CFM (LOW)
2052
1915
1568
1632
1444
1433
1326
1296
1251
1034
1078
1054
1048E
.2 Duct Static Pressure and applicable
Air conditioning coil only
1060G1 and 1242G1
1042E
2371
1794
1717
1826
1580
1515
1487
1377
1400
1517
1132
1122
1048E
Heating coil only
.2 Duct Static Pressure
.2 Duct Static Pressure + .3 additional
load
2161
1977
1685
1459
1330
1200
1047
962
CFM CAPACITY
The CFM at .2 static pressure takes into account the resistance of the internal A-coil. The CFM at
a .5 static pressure accounts for the addition of an external hydronics coil which would typically
add .3 to the static pressure.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
DUCT SIZES FOR HOMES
Velocity Approximately 800 Feet Per Minute
THE INDOOR EVAPORATOR COIL
1. EVAPORATOR COIL is a finned coil through which air in the home is circulated. Heat
from the air is transferred to the liquid refrigerant inside the evaporator coil. The coils for use in
AH air handlers are in an A-shaped configuration (A Models).
2. CONDENSATE DRAIN PAN is attached to the bottom of the evaporator coil to collect
water condensed out of the air. A drain fitting is provided for connection to a convenient drain
point.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
TUBING LINE SETS
1. SUCTION LINE is an insulated large copper tube connecting the outlet of the A/C evaporator
to the suction inlet of the A/C CONDENSER.
2. LIQUID LINE is a single small tube connecting the outlet of the A/C condenser to the
expansion valve inlet on the A/C evaporator coil.
TUBING SIZE REFERENCE CHART
0’-50’ TOTAL LINE LENGTH
MODEL
SUCTION LINE
LIQUID LINE
1024 & 1030
1036 & 1042
1048 & 1060
3/4”
3/4”
7/8”
3/8”
3/8”
3/8”
50’-75’ TOTAL LINE LENGTH
MODEL
SUCTION LINE
LIQUID LINE
1024 & 1030
1036 & 1042
1048 & 1060
7/8”
1”
1”
3/8”
1/2”
1/2”
75’-100’ TOTAL LINE LENGTH
MODEL
SUCTION LINE
LIQUID LINE
1024 & 1030
1036 & 1042
1048 & 1060
1”
1-1/8”
1-1/8”
1/2”
5/8”
5/8”
0’-50’ TOTAL LINE LENGTH
MODEL
SUCTION LINE
LIQUID LINE
1224 & 1230
1236 & 1242
3/4”
7/8”
3/8”
1/2”
50’-75’ TOTAL LINE LENGTH
MODEL
SUCTION LINE
LIQUID LINE
1224 & 1230
1236 & 1242
7/8”
1”
3/8”
1/2”
12
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
75’-100’ TOTAL LINE LENGTH
MODEL
SUCTION LINE
LIQUID LINE
1224 & 1230
1236 & 1242
1”
1-1/8”
1/2”
5/8”
NOTES:
For line lengths over 25’ adjust charge accordingly per foot of variation from chart.
.65 oz. per foot for 3/8” and 3/4” line set
.674 oz. per foot for 3/8” and 7/8” line set
.694 oz. per foot for 1/2” and 7/8” line set
.72 oz. per foot for 1/2” and 1” line set
.76 oz. per foot for 5/8” and 1-1/8” line set
These charges are to be used in conjunction with a superheat measurement for best performance.
TUBING INSTALLATION
The compressor oil is constantly pumped through the refrigerant lines in normal operation of an
air conditioning system. To ensure proper lubrication of the compressor by avoiding oil
accumulation at undesirable points in the system, follow the guidelines listed below:
1. No traps in the suction line are necessary if the outdoor condensing unit is level with the
indoor evaporator coil or the indoor evaporator coil is 4 feet or less lower then the outdoor
condensing unit. Any horizontal runs of suction line should have minimum 1/2" pitch for
every 10 feet of line towards the outdoor condensing unit. See Figure F below.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
Figure F
2. A trap is necessary in the suction line at the indoor evaporator coil if the indoor evaporator coil
is more than 4 feet below the outdoor condensing unit.
NOTE: Multiple suction line traps are recommended for longer or multiple horizontal lines.
(See Fig. G1).
An inverted trap should be installed on the horizontal suction line near the evaporator coil to
prevent liquid flood back to the compressor (See Fig. G2) if the indoor evaporator coil is
located 10’ or more above the condensing unit.
14
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
A gradual loop in the tubing can be constructed to take up the excess tubing if you find that too
much tubing has been brought onto a job. Such a loop MUST be kept in a horizontal (flat) plane
to avoid trapping the oil.
Refrigerant lines should be inserted into a suitable conduit or raceway when the lines are to be
buried between the building and the outdoor condensing unit. The lines must be provided with
sufficient protection and support to prevent damage when installed above ground.
When making "on the job" tubing, a solder of 95% tin, 5% antimony or any of the silver solders
such as SilFos, Phos-Copper, Easy-Flo 35 or 45, should be used. No attempt will be made here to
instruct proper soldering or brazing technique but it is necessary that the installer be properly
instructed in accordance with good existing practices.
All joints and fittings must be properly leak tested as per EPA guidelines after “on the job”
tubing has been made up. The line set and the evaporator coil must be evacuated to 29.96” Hg
(1000 microns) or lower when all joints and fittings are leak free. The service valves on the
condenser may then be opened to release the refrigerant to the system. Verify proper system
performance. See condensing unit manual for additional performance data.
HOW TO MEASURE SUPERHEAT (NOTE: A good electric resistance thermometer and
accurate suction pressure gauge are necessary).
Superheat is measured by taking a temperature and pressure reading. See Figure I. The pressure
reading is gauged at the pressure port which is located on the suction service valve. The
temperature reading is taken at the evaporator coil on the header assembly in the 2:00 o'clock or
10:00 o'clock position with header assembly tube as the center of the clock.
Figure I
15
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
Read the temperature at header assembly to calculate the superheat. Then read the suction
pressure and then add the line loss of 2 lbs. for 25’ of tubing. Then convert pressure into
temperature.
Next, subtract the converted suction temperature from the measured coil header temperature and
the end result is the superheat.
EXAMPLE:
o
Measured Temp = 50 F
(Off header assembly at 10:00 or 2:00 position) See Figure I.
o
Measured Pressure = 71PSI + 2PSI = 73PSI which equates to a 43 F saturation temperature.
(Measured from pressure port)
(Listed temperature for measured pressure according to R-22 temperature scale on manifold
gauge or R-22 section of pressure temperature chart)
o
The difference equals the degrees superheat = 7 F
o
o
All 10 SEER models of Thermo Pride air conditioners should have a 3 F to 7 F superheat at an
o
o
o
o
85 F to 95 F outdoor temperature and a 70 F to 80 F indoor temperature. The superheat
o
o
temperature will not be accurate if the indoor temperature is not within the 70 F to 80 F range.
Therefore, an indoor temperature within the above range must be achieved before an accurate
superheat can be measured.
MEASURING TEMPERATURE DROP ACROSS THE “A” COIL:
o
o
The temperature drop across the coil should be around 15 F to 20 F difference between inlet and
outlet air. This should be measured as close to the air handler as possible, to eliminate duct
losses.
ELECTRICAL
All wiring must conform to the provisions of local codes or in the absence of local codes with the
provisions of the National Electrical Code, ANSI/NFPA No. 70-Latest Edition and this
instruction manual. Equivalent type wire must be used if any of the original wire supplied with
the unit needs to be replaced A 10 amp time delayed fuse or circuit breaker is recommended.
NOTE: Condensing unit is not included in above amp rating.
16
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
The following points must be checked by the installer and/or electrician before the air
conditioning system is started:
1. Check every electrical connection of "PUSH-ON" or "SCREW-ON" terminals to ensure it is
on tightly on its proper post.
2. Review wiring diagram for proper routing.
A loose terminal will cause poor flow of electrical power and result in very high current draw.
This can lead to blown fuses or burned wires.
UA ADAPTER CABINET
The UA adapter cabinet is designed to be used in conjunction with the AH AIR HANDLER to
allow a free standing (vertical discharge) installation. The UA cabinet is shipped completely
assembled and ready for installation.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
A return air opening can be cut in any of the four sides or the bottom of the UA cabinet. The AH
AIR HANDLER is then placed on the UA adapter cabinet, inlet side down. The AH rests on the
support angles of the UA adapter cabinet. The UA cabinet is equipped with a permanent
washable air filter.
When using the UA air handler, the coil drain and coil drain pan must be utilized in place of the
primary drain and primary drain pan found in the air handler.
AH AIR HANDLER RECOMMENDED SUSPENSION PROCEDURE
The detail below is the proper and safest way to suspend the AH. These components should be
easily found at your local hardware store.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
REPLACEMENT PARTS
19
Download from Www.Somanuals.com. All Manuals Search And Download.
All installations and services must be performed by qualified personnel.
AH2-A Air Handler with HC2-A Hydronic Coil
Outlet Air Temerature vs. Heating Capacity
(GPM,PSI,Coil Drop)
Low Speed
145
140
135
130
125
120
115
110
105
100
95
180 F Inlet Water Temp.
160 F Inlet Water Temp.
Medium Low
Medium High
7 GPM(.65,1.5' H2O)
8 GPM(.95,2.2' H2O)
9 GPM(1.17,2.7' H2O)
10 GPM(1.34,3.1' H2O)
High
140 F Inlet Water Temp.
90
40
60
80
100
120
Heating Capacity (Mbtuh)
AH1-AAir Handler withHC1-AHydronicCoil Outlet Air
Temperature vs. Heating Capacity
(GPM,PSI,Coil Drop)
140
Low Speed
180FInlet Water Temp.
Medium Low
130
120
110
100
90
Medium High
160FInlet Water Temp.
3 GPM(.476,1.1' H2O)
4 GPM(.823,1.9' H2O)
5 GPM(1.25,2.9' H2O)
6 GPM(1.65,3.8' H2O)
High
140FInlet Water Temp.
30
40
50
60
70
80
90
Heating Capacity (Mbtuh)
20
Download from Www.Somanuals.com. All Manuals Search And Download.
|